Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2023-10-16 08:55:16


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 10690.08 942.25 942.25
Net Site Energy 10481.63 923.88 923.88
Total Source Energy 25650.03 2260.85 2260.85
Net Source Energy 24989.87 2202.67 2202.67


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3008.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 455.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 150.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 390.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 607.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 112.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 241.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 2148.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 44.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 6750.83 3939.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3008.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 455.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 150.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 21.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 366.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 607.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 112.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 241.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 2148.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 21.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3008.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 455.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 150.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 390.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 607.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 112.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 241.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 2148.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 44.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 53.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 336.68 189.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 204.95 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 595.03 347.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 53.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 336.68 189.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 204.95 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 595.03 347.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 217.610 3.22
Wind Power 0.000 0.00
Power Conversion -9.16 -0.1
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 208.449 3.09
     
Electricity Coming From Utility 6542.385 96.91
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 6542.385 96.91
     
Total On-Site and Utility Electric Sources 6750.834 100.00
Total Electricity End Uses 6750.834 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 2083.50 99.31
Air to Air Heat Recovery for Heating 14.46 0.69
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2097.96 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 114.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 8430.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionElectricityGeneratedPropaneMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55
RunPeriod RUNPERIOD 1
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 6.2037 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 7.5557 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 7.5557 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 7.2603 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 3.7794 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.2151 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 7.7715 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.1806 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 4.4993 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.4132 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 7.7715 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 7.7715 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 12.1686 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 4.4993 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.5793 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.5793 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.2037 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 7.5557 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 7.5557 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 7.2603 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 3.7794 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.2151 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 7.7715 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.1806 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.4132 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.4132 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.4132 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.4132 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 4.4993 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.4132 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.4132 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.4132 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 7.7715 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 7.7715 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 12.1686 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 4.4993 18.58 0.0000  
Total 11345.29             5.5793 3.54 41.0437  
Conditioned Total 11345.29             5.5793 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.4264 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 27-JUL-19:10 26-DEC-18:10 - - - - - - - - - - 28-MAR-20:10
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 167634.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 37630.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9571.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 86131.51 104248.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 19286.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 28428.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 4439.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3832.47 183679.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1681.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 366903.44 287928.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 167634.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 37630.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9571.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56456.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 29272.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1216.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 17944.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 126.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 28428.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 4439.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3832.47 183679.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 771.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 669.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 2.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 9528.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1441.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 477.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5220.66 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1236.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1924.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 355.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 765.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.38 2329.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 141.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 21379.89 4270.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 839.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 127.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 42.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 109.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 169.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 31.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 67.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 205.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1884.47 376.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 839.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 127.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 42.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 109.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 169.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 31.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 67.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 205.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1884.47 376.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.55 0.591000 0.502000 1.28 1.00 0.500000 0.000645 0.000059 1.28 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.281207 0.181746 0.423000 0.118951 0.503459 0.500000 0.002096 0.000021 0.118951 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.252898 0.234022 0.544000 0.137577 0.624059 0.500000 0.001628 0.000013 0.137577 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.287729 0.434969 0.010000 0.002877 1.00 0.500000 0.000876 0.000019 0.075436 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.137077 0.526759 0.632000 0.086633 1.00 0.500000 0.000723 0.000012 0.086633 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.19 0.018666 0.010000 0.031858 0.300000 0.500000 0.020412 0.000025 0.098927 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.24 0.116242 0.820000 1.02 0.820000 0.500000 0.003278 0.000082 1.02 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.44 0.224533 0.640000 2.84 0.640000 0.500000 0.001697 0.000238 2.84 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.19 0.998106 0.599000 0.712305 1.00 0.500000 0.000382 0.000088 0.712305 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.14 0.118163 0.833000 1.78 0.833000 0.500000 0.003224 0.000118 1.78 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.24 0.112741 0.795000 1.78 0.795000 0.500000 0.003379 0.000119 1.78 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.14 0.066294 0.258000 0.551015 0.300000 0.500000 0.010337 0.000038 0.551015 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.687301 0.456916 0.274000 0.188320 1.00 0.500000 0.000834 0.000046 0.188320 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 6754.56 0.000059 140.85
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2431.00 0.000021 59.76
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1540.72 0.000013 34.13
MECH_FLR_1 VAV BOX REHEAT COIL 2155.59 0.000019 58.83
STORAGE_FLR_1 VAV BOX REHEAT COIL 1405.68 0.000012 32.90
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 2826.86 0.000025 77.15
CAFE_FLR_1 VAV BOX REHEAT COIL 9385.68 0.000082 203.71
LOBBY_FLR_1 VAV BOX REHEAT COIL 27184.01 0.000238 591.98
ROOM_1_FLR_3 FAN COIL HEATING COIL 2608.75 0.000023 74.54
ROOM_2_FLR_3 FAN COIL HEATING COIL 2607.81 0.000023 74.51
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 19391.95 0.000170 554.06
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 19397.25 0.000170 554.21
ROOM_5_FLR_3 FAN COIL HEATING COIL 2610.23 0.000023 74.58
ROOM_6_FLR_3 FAN COIL HEATING COIL 2609.29 0.000023 74.55
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 10115.78 0.000088 231.45
ROOM_1_FLR_6 FAN COIL HEATING COIL 808.87 0.000007 23.11
ROOM_2_FLR_6 FAN COIL HEATING COIL 808.33 0.000007 23.10
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 3921.45 0.000034 112.04
BANQUET_FLR_6 VAV BOX REHEAT COIL 13488.67 0.000118 287.80
DINING_FLR_6 VAV BOX REHEAT COIL 13591.82 0.000119 290.16
KITCHEN_FLR_6 VAV BOX REHEAT COIL 4288.48 0.000038 91.70
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 5312.99 0.000046 144.28
VAV WITH REHEAT HEATING COIL 59702.90 0.000522 1107.87
FLR_3_DOAS HEATING COIL 5950.05 0.000052 110.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.801778 0.000023 0.000272
ROOM_2_FLR_3 FAN COIL 0.811090 0.000023 0.000275
ROOM_3_MULT19_FLR_3 FAN COIL 4.32 0.000170 0.001431
ROOM_4_MULT19_FLR_3 FAN COIL 5.36 0.000170 0.001876
ROOM_5_FLR_3 FAN COIL 0.724179 0.000023 0.000248
ROOM_6_FLR_3 FAN COIL 0.730826 0.000023 0.000250
ROOM_1_FLR_6 FAN COIL 0.221277 0.000007 0.000075
ROOM_2_FLR_6 FAN COIL 0.223703 0.000007 0.000075
ROOM_3_MULT9_FLR_6 FAN COIL 0.907960 0.000034 0.000315
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 0.801778
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 0.811090
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 4.32
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.36
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.724179
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.730826
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.221277
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.223703
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 0.907960
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008813 12.80 0.008500 0.000272 0.801778  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008810 12.80 0.008500 0.000275 0.811090  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008720 12.80 0.008500 0.001431 4.32  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008936 12.80 0.008500 0.001876 5.36  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008848 12.80 0.008500 0.000248 0.724179  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008845 12.80 0.008500 0.000250 0.730826  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008784 12.80 0.008500 0.000075 0.221277  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008781 12.80 0.008500 0.000075 0.223703  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008906 12.80 0.008500 0.000315 0.907960  
VAV WITH REHEAT COOLING COIL 28.17 6.70 0.013136 11.09 0.008500 0.020725 20.58 724644.47
FLR_3_DOAS COOLING COIL 33.20 6.70 0.017167 11.94 0.008500 0.003098 2.05 108329.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 12.93 10.53 20.77 10.53 20.58 20.58 0.300000 0.511615 20.58
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 20.58  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 9.33
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 20.58
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.020725 0.000023
VAV WITH REHEAT_HEATC_CONTROLLER 0.000522  
FLR_3_DOAS_COOLC_CONTROLLER 0.003098 0.000154
FLR_3_DOAS_HEATC_CONTROLLER 0.000052  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.028640 4629.67  
HEATSYS1 PUMP 0.001933 576.23 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.001933 0.231902
COOLSYS1 0.028640 3.44
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 220898.71 220898.71 0.001933
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.028640 3205.28
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.028640 1001387.88 1004426.57 114.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.30 23.60 20.30 19.40 20.90 21.60 24.10 26.40 27.70 28.10 28.00 27.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Miami Intl Ap FL USA TMY3 WMO#=722020 25.82 -80.30 -5.00 11.00 101193 1.2027


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.49 8.70 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 6.204 5.380 0.000 0.000 0.000 0.000 11.584 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 7.556 10.760 0.000 0.000 0.000 0.000 18.316 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 7.556 10.760 0.000 0.000 0.000 0.000 18.316 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 7.260 5.380 0.000 0.000 0.000 0.000 12.640 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 3.779 2.690 0.000 0.000 0.000 0.000 6.469 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.215 61.680 535.850 0.000 0.000 0.000 602.745 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 7.772 5.380 0.000 0.000 0.000 0.000 13.152 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.181 8.070 0.000 0.000 0.000 0.000 16.251 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 4.499 0.000 0.000 0.000 0.000 0.000 4.499 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 7.772 67.820 0.000 0.000 0.000 0.000 75.592 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 7.772 67.820 0.000 0.000 0.000 0.000 75.592 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 12.169 512.243 2419.260 0.000 0.000 0.000 2943.672 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 4.499 0.000 0.000 0.000 0.000 0.000 4.499 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 12276.143 6.204 115.270 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 12276.143
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 506.769 7.556 46.797 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 506.769
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 586.840 7.556 46.797 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 586.840
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1192.447 7.260 449.641 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1192.447
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 358.135 3.779 175.557 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 358.135
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 406.984 5.215 48.451 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 406.984
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1467.746 7.772 10.314 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1467.746
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 10701.700 8.181 25.333 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10701.700
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 108.229 4.413 72.152 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.229
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1752.054 4.499 83.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1752.054
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 2577.487 7.772 10.314 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2577.487
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 2577.487 7.772 10.314 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2577.487
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1257.069 12.169 56.528 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1257.069
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1854.278 4.499 83.601 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1854.278


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.393 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.408 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 3.444 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 3.444 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.2994E-01
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.2994E-01
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.2994E-01
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5506
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5431
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 0.2994E-01
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 0.2994E-01
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
21 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
22 1 -21.915918 0.11588205 -6.3286394 0.20197014
23 0 21.365777 0.10835518 5.5011278  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
29 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
30 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
31 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
32 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
33 4 19.715055 0.51780401E-02 12.415669 -0.24584718
34 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
35 2 168.49726 0.99923307E-02 62.094262 -2.4465849
36 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
37 0 57.057407 0.91053392E-05 16.929182  
38 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
39 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
40 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
41 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
42 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
43 4 19.715055 0.51780401E-02 12.415669 -0.24584718
44 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
45 2 168.49726 0.99923307E-02 62.094262 -2.4465849
46 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
47 0 57.057407 0.91053392E-05 16.929182  
48 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
49 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
50 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
51 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
52 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
53 4 19.715055 0.51780401E-02 12.415669 -0.24584718
54 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
55 2 168.49726 0.99923307E-02 62.094262 -2.4465849
56 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
57 0 57.057407 0.91053392E-05 16.929182  
58 9 0.75525440E-15 0.44740194E-16 -0.12773695E-09 -0.17413973E-17
59 8 0.18775242E-07 0.18212309E-12 0.34440251E-03 -0.21348098E-09
60 7 -0.11242372E-01 0.98045077E-08 -0.21646224E-01 0.12782986E-03
61 6 0.37819669 0.34662877E-05 0.44889448 -0.44276875E-02
62 5 -4.9255264 0.13123097E-03 -4.2627871 0.59897552E-01
63 4 31.830222 0.10869568E-02 20.742026 -0.40655401
64 3 -108.73045 0.23952585E-02 -54.243141 1.4791387
65 2 194.65663 0.13606195E-02 76.609648 -2.8614229
66 1 -170.25011 0.14657319E-03 -54.889188 2.7295613
67 0 57.057407 0.84265852E-06 15.620975  
68 9 0.85297796E-15 0.46957990E-16 -0.12703153E-09 -0.54240268E-18
69 8 0.18675511E-07 0.18384479E-12 0.34329809E-03 -0.21234699E-09
70 7 -0.11209220E-01 0.99091673E-08 -0.21598424E-01 0.12745291E-03
71 6 0.37729561 0.35050755E-05 0.44812211 -0.44170661E-02
72 5 -4.9167295 0.13275736E-03 -4.2568331 0.59788477E-01
73 4 31.791289 0.11000280E-02 20.718704 -0.40603713
74 3 -108.64755 0.24248953E-02 -54.197012 1.4779412
75 2 194.57440 0.13778728E-02 76.567430 -2.8601173
76 1 -170.21971 0.14847322E-03 -54.877080 2.7290284
77 0 57.057407 0.85387380E-06 15.623112  
78 7 -0.54138470E-12 0.12463713E-14 -0.64276224E-14 0.11113167E-15
79 6 0.12246794E-07 0.15689727E-09 0.20336639E-09 -0.66085082E-11
80 5 -0.43638646E-04 0.91064443E-06 -0.10338442E-05 0.73798452E-07
81 4 0.19644206E-01 0.40532412E-03 0.96204216E-03 -0.14823791E-03
82 3 -1.4347347 0.16410182E-01 -0.13915079 0.27725787E-01
83 2 17.082538 0.80550987E-01 2.2432332 -0.47694951
84 1 -41.597683 0.53207822E-01 -6.4041654 1.4049886
85 0 26.083068 0.22662127E-02 4.4519555  
86 7 -0.64276224E-14 0.12463713E-14 -0.54138470E-12 0.11113167E-15
87 6 0.20336639E-09 0.15689727E-09 0.12246794E-07 -0.66085082E-11
88 5 -0.10338442E-05 0.91064443E-06 -0.43638646E-04 0.73798452E-07
89 4 0.96204216E-03 0.40532412E-03 0.19644206E-01 -0.14823791E-03
90 3 -0.13915079 0.16410182E-01 -1.4347347 0.27725787E-01
91 2 2.2432332 0.80550987E-01 17.082538 -0.47694951
92 1 -6.4041654 0.53207822E-01 -41.597683 1.4049886
93 0 4.4519555 0.22662127E-02 26.083068  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.248_SHGC_0.21 37 1 VerySmooth 1.408 1.408 1.000 0.210    
2 RESWINDOW_U_0.248_SHGC_0.21 38 1 VerySmooth 1.408 1.408 1.000 0.210    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   4.57814E-002 0.12126 0.67915 0.67915 0.29000 0.15345 0.21878 0.00000 0.84000 0.84000 8.56546E-002 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   4.57814E-002 0.12126 0.67915 0.67915 0.29000 0.15345 0.21878 0.00000 0.84000 0.84000 8.56546E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.680 0.5995
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.312 3.5001E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.2696E-002
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.2796E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.9673E-002
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.3938E-002
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.6907E-002
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.3515E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.9121E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 9.7843E-003
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.2057E-002
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.0912E-002
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.9809E-002
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.2490E-002
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.3855E-002
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.0008E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 3.2628E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.3264E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.1616E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.2337E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.6834E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.4066E-003
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5712E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.3605E-003
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8610E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0256E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.1616E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.2337E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.6834E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.4066E-003
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5712E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.3605E-003
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8610E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0256E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 35073.72220 35073.72220 2.55138 2.55138 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 22:20:00 28.48767 1.71582E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 8.70000 6.99286E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 3865.00000 3865.00000 0.28121 0.28121 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.03867 1.71650E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 1803.83420 1803.83420 7.74088E-002 7.92179E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3476.07431 3476.07431 0.25290 0.25290 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 29.74950 1.71606E-002 77.66889 12.54000 9.17335E-002 0.00000
6 RETAIL_2_FLR_1 Heating 815.32340 815.32340 3.49886E-002 9.17335E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 77.66889 12.54000 9.17335E-002 0.00000
7 MECH_FLR_1 Cooling 3955.64614 3955.64614 0.28773 0.28773 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 29.74950 1.71606E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1757.84603 1757.84603 7.54357E-002 7.54357E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1884.49246 1884.49246 0.13708 0.13708 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.08950 1.71632E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 948.90393 948.90393 4.07210E-002 5.77652E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 43791.90934 43791.90934 3.18581 3.18581 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 33.06600 1.71670E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2305.26515 2305.26515 9.89269E-002 9.89269E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 17002.09661 17002.09661 1.23804 1.23804 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 188.86188 142.30000 0.67638 0.00000
14 CAFE_FLR_1 Heating 4033.04691 4033.04691 0.17307 0.67638 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 188.86188 142.30000 0.67638 0.00000
15 LOBBY_FLR_1 Cooling 61005.22684 61005.22684 4.43960 4.43960 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.92700 1.71648E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 12202.65840 12202.65840 0.52366 1.89399 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 8178.66894 8178.66894 0.80178 0.80178 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 2608.75977 2608.75977 0.11261 0.11261 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 8273.65801 8273.65801 0.81109 0.81109 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.03867 1.71650E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 2607.82215 2607.82215 0.11257 0.11257 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 44093.62906 44093.62906 4.32217 4.32217 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.13300 1.71671E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 15043.42926 15043.42926 0.64936 0.83707 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 54677.14186 54677.14186 5.36000 5.36000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 31.70367 1.71644E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 15035.38883 15035.38883 0.64902 0.83730 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 7387.09469 7387.09469 0.72418 0.72418 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.82150 1.71627E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 2610.23983 2610.23983 0.11267 0.11267 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 7454.89576 7454.89576 0.73083 0.73083 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.82150 1.71627E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 2609.30184 2609.30184 0.11263 0.11263 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 16347.35360 16347.35360 1.18916 1.18916 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 31.25700 1.71635E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 6359.94416 6359.94416 0.27293 0.47476 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2257.18171 2257.18171 0.22128 0.22128 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 808.87306 808.87306 3.49155E-002 3.49155E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 8.70000 6.99286E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2281.92588 2281.92588 0.22370 0.22370 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 808.33600 808.33600 3.48924E-002 3.48924E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 8.70000 6.99286E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 9261.75089 9261.75089 0.90796 0.90796 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 33.20000 1.71672E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 3921.45207 3921.45207 0.16927 0.16927 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 8.70000 6.99286E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29365.05432 29365.05432 2.13876 2.13876 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.13300 1.71671E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 4094.47331 4094.47331 0.17571 1.18780 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 8.70000 6.99286E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30777.96033 30777.96033 2.24163 2.24163 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.13300 1.71671E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 4194.90682 4194.90682 0.18002 1.18780 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 8.70000 6.99286E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 29281.78761 29281.78761 2.13572 2.13572 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 32.59700 1.71661E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1390.76778 1390.76778 5.96774E-002 0.36735 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 8.70000 6.99286E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 9448.33349 9448.33349 0.68730 0.68730 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.13300 1.71671E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 4319.95995 4319.95995 0.18539 0.18539 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 8.70000 6.99286E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 381767.22 20.58296 20.58296 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 69913.47 7.23094 7.23094 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:50:00
3 FLR_3_DOAS Cooling Sensible 50573.62 13.80501 2.05125 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 19832.79 2.36393 2.05125 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.55138
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.59100
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50200
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.28080
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.44670E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.90918E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.28080
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6754.55691
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.90918E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 140.85464
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.28121
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18175
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.42300
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11895
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50346
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09633E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.12674E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11895
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2430.99925
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.12674E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 59.75816
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.25290
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23402
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54400
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13758
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.62406
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.62805E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.34789E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13758
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1540.72414
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.34789E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 34.12681
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.28773
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.43497
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.87729E-003
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.75925E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.88580E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.54357E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2155.58973
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.88580E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 58.83102
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.13708
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.52676
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.63200
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.66327E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.23291E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.22975E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.66327E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1405.67954
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.22975E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 32.89766
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.18581
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.86659E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.18581E-002
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.04115E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.47306E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.89269E-002
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2826.85738
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.47306E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 77.15148
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23804
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11624
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.82000
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.01519
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82000
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.27764E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.21100E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.01519
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9385.67755
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.21100E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 203.70882
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.43960
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22453
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.64000
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.84134
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64000
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.69685E-003
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.37818E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.84134
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 27184.00702
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.37818E-004
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 591.97779
113 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
114 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.80178
115 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.80178
116 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.28225E-005
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.71961E-004
118 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68256
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.81291E-003
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.71961E-004
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.80178
125 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2608.74862
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.28225E-005
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 74.53677
128 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
129 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.81109
130 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.81109
131 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.28143E-005
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.74886E-004
133 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68257
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.80961E-003
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.74886E-004
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.81109
140 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2607.81100
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.28143E-005
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 74.50998
143 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
144 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 4.32217
145 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 4.32217
146 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.69649E-004
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.43098E-003
148 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68352
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.71966E-003
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.43098E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 4.32217
155 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 19391.95039
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.69649E-004
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 554.06039
158 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
159 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.36000
160 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.36000
161 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.69696E-004
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.87592E-003
163 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68265
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.93629E-003
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.87592E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.36000
170 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 19397.25308
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.69696E-004
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 554.21193
173 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
174 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.72418
175 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.72418
176 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.28354E-005
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.47836E-004
178 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68251
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.84764E-003
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.47836E-004
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.72418
185 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2610.22867
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.28354E-005
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 74.57905
188 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
189 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.73083
190 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.73083
191 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.28272E-005
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.49919E-004
193 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68251
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.84464E-003
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.49919E-004
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.73083
200 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2609.29069
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.28272E-005
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 74.55225
203 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.18916
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.99811
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.59900
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.71231
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.81723E-004
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.84973E-005
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71231
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
214 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10115.78122
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.84973E-005
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 231.44622
217 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
218 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.22128
219 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.22128
220 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.07636E-006
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.45013E-005
222 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68261
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78418E-003
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.45013E-005
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.22128
229 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 808.87147
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.07636E-006
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 23.11056
232 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
233 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.22370
234 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.22370
235 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.07166E-006
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.52566E-005
237 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68261
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78104E-003
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.52566E-005
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.22370
244 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 808.33442
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.07166E-006
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 23.09521
247 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
248 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.90796
249 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.90796
250 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.43065E-005
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.15343E-004
252 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68241
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.90578E-003
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.15343E-004
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.90796
259 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3921.44590
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.43065E-005
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 112.04065
262 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.13876
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11816
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.83300
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78159
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.83300
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.22435E-003
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.18005E-004
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78159
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
273 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13488.66788
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.18005E-004
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 287.79632
276 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.24163
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11274
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.79500
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78210
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.79500
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.37944E-003
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.18907E-004
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78210
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
287 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13591.81570
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.18907E-004
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 290.16051
290 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.13572
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.62935E-002
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25800
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.55102
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.03370E-002
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.75175E-005
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.55102
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
301 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4288.48140
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.75175E-005
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 91.69600
304 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.68730
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.45692
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27400
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18832
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.33851E-004
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.64803E-005
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.18832
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
315 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5312.98644
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.64803E-005
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 144.28411
318 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 12.92641
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 10.53055
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 20.76632
321 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 10.53055
322 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 20.58296
323 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 20.58296
324 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
325 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.51162
326 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
333 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
334 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 20.58296
335 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
336 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 20.58296
337 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 9.32920
338 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.16987
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.08732
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.31357E-002
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 724644.47461
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.07247E-002
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 20.58296
346 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 59702.89988
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.22307E-004
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1107.86766
349 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 20.58296
350 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.07247E-002
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 2.29769E-005
352 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.22307E-004
353 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
355 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
356 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 33.20000
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.94186
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.71672E-002
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 108329.82081
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.09822E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
364 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 5950.04693
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.20536E-005
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 110.41113
367 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
368 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.09822E-003
369 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.53698E-004
370 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.20536E-005
371 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.86396E-002
372 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 4629.66940
373 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.93252E-003
374 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.23190
375 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.93252E-003
376 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 576.22735
377 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
378 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 220898.70523
379 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 220898.71000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.93252E-003
381 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.86396E-002
382 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.43675
383 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.86396E-002
384 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3205.27628
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.86396E-002
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1001387.88039
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1004426.57000
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 114.50463
389 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
390 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
391 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
392 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
393 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 6789.44
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2441.36
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1548.13
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2163.69
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1412.07
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 2837.48
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 9432.38
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 27318.88
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 2809.55
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 2808.54
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 20884.51
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 20890.22
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 2811.14
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 2810.13
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 10162.83
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 871.12
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 870.54
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 4223.23
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 13556.84
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 13660.48
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 4310.11
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 5333.05
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 53450.52
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 5326.93


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 13657.78 11543.67 2114.11 0.85 2418.20 24.53
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 13808.60 11674.84 2133.77 0.85 2446.36 24.81
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 72445.98 61793.39 10652.59 0.85 13053.31 132.39
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 93223.87 77896.13 15327.75 0.84 16175.01 164.06
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 12411.19 10455.34 1955.85 0.84 2185.95 22.17
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 12518.76 10548.93 1969.83 0.84 2206.06 22.38
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 3750.77 3178.98 571.79 0.85 667.59 6.77
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 3789.83 3213.07 576.76 0.85 674.94 6.85
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 15712.51 13165.44 2547.07 0.84 2740.01 27.79
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 619700.13 410201.23 209498.90 0.66 88695.92 899.60
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 68061.43 43715.72 24345.72 0.64 9312.93 94.46


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 4.12 14.07


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 8.3523690196E-003 1.6756860650E-002 Pass Pass 1.0084137858E-002 2.1047158106E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.3379349270E-002 2.7616492858E-002 Pass Pass 1.8218732522E-002 2.0498476897E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.0308319026E-002 2.4915318162E-002 Pass Pass 7.9463424487E-003 1.8723381136E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 2.7001527530E-005 4.4688436615E-005 Pass Pass 1.7163239133E-002 3.0459230722E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 9.9489521874E-003 1.1005700224E-002 Pass Pass 7.8510175917E-003 1.9825505366E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 1.9969901506E-004 3.4432577258E-004 Pass Pass 1.8432194331E-002 5.5660902184E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 5.3389372783E-002 6.3324586431E-002 Pass Pass 1.0428017855E-002 1.7400270337E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 2.8548299520E-002 3.6855977844E-002 Pass Pass 8.3561503695E-003 1.8588445810E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.2642892248E-002 0.3230386072 Pass Pass 7.1122997671E-002 0.1739994780 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 0.1088006512 0.2880044189 Pass Pass 8.0897986297E-002 0.2214541175 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.8086079658E-005 1.2358276334E-004 Pass Pass 2.8350862662E-002 3.8879122491E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 0.1127514393 0.2428401680 Pass Pass 6.2534491150E-002 0.1998434412 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2640765922E-002 0.3347747684 Pass Pass 0.1440986439 0.5564342184 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 0.1307971192 0.3488021345 Pass Pass 0.1451016110 0.8733205302 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 8.8553062181E-003 9.1752093859E-003 Pass Pass 7.6907270050E-003 1.9037414869E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2650448888E-002 0.3204116980 Pass Pass 0.1567750365 0.9460949325 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 0.1040364068 0.2891568563 Pass Pass 7.3519584817E-002 0.1753570530 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2647431136E-002 0.3174573926 Pass Pass 0.1010289667 0.3390277846 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 5.3634913713E-002 8.9098352515E-002 Pass Pass 1.0364698192E-002 2.1448291076E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 5.3576431691E-002 8.7572078636E-002 Pass Pass 1.0107029635E-002 2.0612648989E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 1.3772506471E-003 2.2194601596E-003 Pass Pass 2.1323767227E-002 3.9461837856E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 6.4740804293E-003 1.1268442933E-002 Pass Pass 1.4876107786E-002 1.9193111672E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3121.32 -89.7 -1239.1 -3334.9 13447.34 11905.06



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 65.00 29      
Feb 0.00 0      
Mar 0.00 0      
Apr 38.00 14      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 391.00 83      
Sep 0.00 0      
Oct 225.00 40      
Nov 0.00 0      
Dec 5.00 10      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.153 1.393 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.153 1.393 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.153 1.393 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.153 1.393 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.153 1.393 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.153 1.393 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.153 1.393 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.153 1.393 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.153 1.393 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.153 1.393 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.163 1.408 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.163 1.408 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.163 1.408 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.163 1.408 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.163 1.408 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.273 0.283 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 1.786 3.444 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 1.786 3.444 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 1.786 3.444 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 1.786 3.444 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 1.786 3.444 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 1.786 3.444 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 1.786 3.444 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 1.786 3.444 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 1.786 3.444 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 1.786 3.444 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 1.979 3.444 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 1.627 3.444 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 1.627 3.444 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 1.627 3.444 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 1.979 3.444 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 1.979 3.444 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 1.979 3.444 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   23.26 0.00 0.00 23.26 23.26 1.408 0.210 0.290             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   65.50 0.00 0.00 65.50 65.50 1.408 0.210 0.290             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   85.08 0.00 0.00 85.08 85.08 1.408 0.210 0.290             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 18.40 1.408 0.210 0.290             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 34.34 1.408 0.210 0.290             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 18.40 1.408 0.210 0.290             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 34.34 1.408 0.210 0.290             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   3.68 0.00 0.00 3.68 279.56 1.408 0.210 0.290             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   3.68 0.00 0.00 3.68 279.65 1.408 0.210 0.290             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 34.34 1.408 0.210 0.290             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 18.40 1.408 0.210 0.290             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 18.40 1.408 0.210 0.290             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 34.34 1.408 0.210 0.290             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   5.82 0.00 0.00 5.82 23.30 1.408 0.210 0.290             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   2.15 0.00 0.00 2.15 8.59 1.408 0.210 0.290             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   2.15 0.00 0.00 2.15 8.58 1.408 0.210 0.290             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   5.82 0.00 0.00 5.82 23.30 1.408 0.210 0.290             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 4.60 1.408 0.210 0.290             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 8.58 1.408 0.210 0.290             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 4.60 1.408 0.210 0.290             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 8.58 1.408 0.210 0.290             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   6.74 0.00 0.00 6.74 60.70 1.408 0.210 0.290             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   32.19 0.00 0.00 32.19 32.19 1.408 0.210 0.290             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   32.19 0.00 0.00 32.19 32.19 1.408 0.210 0.290             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 4.60 1.408 0.210 0.290             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   17.17 0.00 0.00 17.17 17.17 1.408 0.210 0.290             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 4.60 1.408 0.210 0.290             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   5.82 0.00 0.00 5.82 5.82 1.408 0.210 0.290             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   5.21 0.00 0.00 5.21 5.21 1.408 0.210 0.290             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   17.17 0.00 0.00 17.17 17.17 1.408 0.210 0.290             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 1.408 0.210 0.290                      
North Total or Average             432.95 1.408 0.210 0.290                      
Non-North Total or Average             780.84 1.408 0.210 0.290                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.2037 1978.83 12276.14 LightsWired LTG_SCH_BASEMENT 40.17 168.00 40.12 0.0000 Y 92.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 7.5557 67.07 506.77 LightsWired LTG_SCH_RETAIL 44.04 168.00 43.99 0.0000 Y 4.18
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 7.5557 77.67 586.84 LightsWired LTG_SCH_RETAIL 44.04 168.00 43.99 0.0000 Y 4.85
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 7.2603 164.24 1192.45 LightsWired LTG_SCH_MECHANIC 38.78 168.00 38.73 0.0000 Y 8.67
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 3.7794 94.76 358.14 LightsWired LTG_SCH_STORAGE 29.59 168.00 29.56 0.0000 Y 1.99
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.2151 78.04 406.98 LightsWired LTG_SCH_LAUNDRY 48.47 168.00 48.41 0.0000 Y 3.70
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 7.7715 188.86 1467.75 LightsWired LTG_SCH_DINING 36.01 168.00 24.25 0.0000 Y 6.68
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.1806 1308.19 10701.70 LightsWired LTG_SCH_LOBBY 41.54 168.00 39.20 0.0000 Y 78.74
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.4132 1863.81 8225.38 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.78
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.4132 1864.32 8227.62 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.79
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 4.4993 1557.62 7008.22 LightsWired LTG_SCH_CORRIDOR 41.54 168.00 41.50 0.0000 Y 54.59
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.4132 39.02 172.21 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.4132 39.02 172.19 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.4132 220.77 974.32 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 6.96
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 7.7715 331.66 2577.49 LightsWired LTG_SCH_DINING 36.01 168.00 30.16 0.0000 Y 14.59
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 7.7715 331.66 2577.49 LightsWired LTG_SCH_DINING 36.01 168.00 30.16 0.0000 Y 14.59
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 12.1686 103.30 1257.07 LightsWired LTG_SCH_KITCHEN 38.78 168.00 38.73 0.0000 Y 9.14
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 4.4993 412.12 1854.28 LightsWired LTG_SCH_CORRIDOR 41.54 168.00 41.50 0.0000 Y 14.44
Interior Lighting Total       5.5793 11345.29 63298.26               277.39


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10701.70 749.12
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10701.70 749.12
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1467.75 572.42
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1467.75 572.42
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2577.49 515.50
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2577.49 515.50
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2577.49 515.50
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2577.49 515.50


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 9571.94 AstronomicalClock -   83.82 83.82 150.61
Exterior Lighting Total 9571.94           150.61



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 220898.71 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1004426.57 3.11 1004603.12 3.11 4.12 14.07


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9509.35 13657.78 11543.67 2114.11 0.85 - 2418.20 24.53
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9611.61 13808.60 11674.84 2133.77 0.85 - 2446.36 24.81
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 50035.46 72445.98 61793.39 10652.59 0.85 - 13053.31 132.39
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 65593.20 93223.87 77896.13 15327.75 0.84 - 16175.01 164.06
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8665.81 12411.19 10455.34 1955.85 0.84 - 2185.95 22.17
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8738.64 12518.76 10548.93 1969.83 0.84 - 2206.06 22.38
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2605.00 3750.77 3178.98 571.79 0.85 - 667.59 6.77
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2631.41 3789.83 3213.07 576.76 0.85 - 674.94 6.85
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 11026.24 15712.51 13165.44 2547.07 0.84 - 2740.01 27.79
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 724644.47 619700.13 410201.23 209498.90 0.66 - 88695.92 899.60
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 108329.82 68061.43 43715.72 24345.72 0.64 - 9312.93 94.46
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 6754.56 6789.44 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2431.00 2441.36 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1540.72 1548.13 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2155.59 2163.69 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1405.68 1412.07 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2826.86 2837.48 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 9385.68 9432.38 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 27184.01 27318.88 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 2608.75 2809.55 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 2607.81 2808.54 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 19391.95 20884.51 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 19397.25 20890.22 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 2610.23 2811.14 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 2609.29 2810.13 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 10115.78 10162.83 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 808.87 871.12 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 808.33 870.54 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 3921.45 4223.23 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13488.67 13556.84 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13591.82 13660.48 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 4288.48 4310.11 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 5312.99 5333.05 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 59702.90 53450.52 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 5950.05 5326.93 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.24 0.00 0.00 1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.80 564.16 703.64 1.00 1.26 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.81 570.71 703.64 1.00 1.25 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 4.32 3041.23 703.64 1.00 0.98 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.36 3771.49 703.64 1.00 0.97 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.72 509.56 703.64 1.00 1.29 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.73 514.24 703.64 1.00 1.28 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.22 155.70 703.64 1.00 1.96 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.22 157.41 703.64 1.00 1.95 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.91 638.87 703.64 1.00 1.22 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1314.72 20.58 43639.46 2120.17 1.00 1.12 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.028640 4629.67 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.001933 576.23 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.028640 3205.28 111917.77 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.95 0.68 0.60
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.95 0.31 0.04



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 35073.72 35073.72 17.72 2.551 2.551 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 22:20:00 24.00 24.00 0.00919 28.49 0.01716 0.854 0.00
RETAIL_1_FLR_1 3865.00 3865.00 57.63 0.281 0.281 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00939 32.04 0.01717 0.079 0.00
RETAIL_2_FLR_1 3476.07 3476.07 44.76 0.253 0.253 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 24.00 24.00 0.00943 29.75 0.01716 0.092 0.00
MECH_FLR_1 3955.65 3955.65 24.08 0.288 0.288 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 24.00 24.00 0.00889 29.75 0.01716 0.000 0.00
STORAGE_FLR_1 1884.49 1884.49 19.89 0.137 0.137 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 24.00 24.00 0.00903 31.09 0.01716 0.058 0.00
LAUNDRY_FLR_1 43791.91 43791.91 561.15 3.186 3.186 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00857 33.07 0.01717 0.000 0.00
CAFE_FLR_1 17002.10 17002.10 90.02 1.238 1.238 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.99 0.01050 33.20 0.01717 0.676 0.00
LOBBY_FLR_1 61005.23 61005.23 46.63 4.440 4.440 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 23.99 0.01016 31.93 0.01716 1.894 0.00
ROOM_1_FLR_3 8178.67 8178.67 209.59 0.802 0.802 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00881 32.15 0.01717 0.062 0.00
ROOM_2_FLR_3 8273.66 8273.66 212.05 0.811 0.811 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 21.11 21.11 0.00881 32.04 0.01717 0.062 0.00
ROOM_3_MULT19_FLR_3 44093.63 44093.63 1797.99 4.322 4.322 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 21.11 21.11 0.00872 33.13 0.01717 0.837 0.00
ROOM_4_MULT19_FLR_3 54677.14 54677.14 2228.94 5.360 5.360 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00894 31.70 0.01716 0.837 0.00
ROOM_5_FLR_3 7387.09 7387.09 189.31 0.724 0.724 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00885 30.82 0.01716 0.062 0.00
ROOM_6_FLR_3 7454.90 7454.90 191.07 0.731 0.731 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00884 30.82 0.01716 0.062 0.00
CORRIDOR_FLR_3 16347.35 16347.35 41.98 1.189 1.189 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.00 24.00 0.00983 31.26 0.01716 0.475 0.00
ROOM_1_FLR_6 2257.18 2257.18 57.84 0.221 0.221 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00878 32.26 0.01717 0.015 0.00
ROOM_2_FLR_6 2281.93 2281.93 58.48 0.224 0.224 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00878 32.15 0.01717 0.015 0.00
ROOM_3_MULT9_FLR_6 9261.75 9261.75 377.56 0.908 0.908 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 21.11 21.11 0.00891 33.20 0.01717 0.099 0.00
BANQUET_FLR_6 29365.05 29365.05 88.54 2.139 2.139 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.98 0.01046 33.13 0.01717 1.188 0.00
DINING_FLR_6 30777.96 30777.96 92.80 2.242 2.242 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.98 0.01037 33.13 0.01717 1.188 0.00
KITCHEN_FLR_6 29281.79 29281.79 283.45 2.136 2.136 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01019 32.60 0.01717 0.367 0.00
CORRIDOR_FLR_6 9448.33 9448.33 22.93 0.687 0.687 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00917 33.13 0.01717 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 21.34 0.00699 8.70 0.00699 0.854 0.00
RETAIL_1_FLR_1 1803.83 1803.83 26.89 0.077 0.079 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00788 8.70 0.00699 0.079 0.00
RETAIL_2_FLR_1 815.32 815.32 10.50 0.035 0.092 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00790 8.70 0.00699 0.092 0.00
MECH_FLR_1 1757.85 1757.85 10.70 0.075 0.075 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00789 8.70 0.00699 0.000 0.00
STORAGE_FLR_1 948.90 948.90 10.01 0.041 0.058 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00788 8.70 0.00699 0.058 0.00
LAUNDRY_FLR_1 2305.27 2305.27 29.54 0.099 0.099 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00789 8.70 0.00699 0.000 0.00
CAFE_FLR_1 4033.05 4033.05 21.35 0.173 0.676 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00789 8.70 0.00699 0.676 0.00
LOBBY_FLR_1 12202.66 12202.66 9.33 0.524 1.894 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00789 8.70 0.00699 1.894 0.00
ROOM_1_FLR_3 2608.76 2608.76 66.85 0.113 0.113 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00783 8.70 0.00699 0.062 0.00
ROOM_2_FLR_3 2607.82 2607.82 66.84 0.113 0.113 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00783 8.70 0.00699 0.062 0.00
ROOM_3_MULT19_FLR_3 15043.43 15043.43 613.42 0.649 0.837 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00784 8.70 0.00699 0.837 0.00
ROOM_4_MULT19_FLR_3 15035.39 15035.39 612.93 0.649 0.837 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00784 8.70 0.00699 0.837 0.00
ROOM_5_FLR_3 2610.24 2610.24 66.89 0.113 0.113 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00783 8.70 0.00699 0.062 0.00
ROOM_6_FLR_3 2609.30 2609.30 66.88 0.113 0.113 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00783 8.70 0.00699 0.062 0.00
CORRIDOR_FLR_3 6359.94 6359.94 16.33 0.273 0.475 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00791 8.70 0.00699 0.475 0.00
ROOM_1_FLR_6 808.87 808.87 20.73 0.035 0.035 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00786 8.70 0.00699 0.015 0.00
ROOM_2_FLR_6 808.34 808.34 20.72 0.035 0.035 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00786 8.70 0.00699 0.015 0.00
ROOM_3_MULT9_FLR_6 3921.45 3921.45 159.86 0.169 0.169 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00786 8.70 0.00699 0.099 0.00
BANQUET_FLR_6 4094.47 4094.47 12.35 0.176 1.188 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00792 8.70 0.00699 1.188 0.00
DINING_FLR_6 4194.91 4194.91 12.65 0.180 1.188 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 21.00 21.00 0.00793 8.70 0.00699 1.188 0.00
KITCHEN_FLR_6 1390.77 1390.77 13.46 0.060 0.367 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00671 8.70 0.00699 0.367 0.00
CORRIDOR_FLR_6 4319.96 4319.96 10.48 0.185 0.185 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 21.00 21.00 0.00794 8.70 0.00699 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 20.58 20.58 7.23 7.23 20.5830 10.5306 20.5830 0.5116 0.3000
FLR_3_DOAS 13.81 2.05 2.36 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 6754.557 6754.557 1.280795 0.00005909 140.855   1/21 00:10:00   1/21 00:10:00 6754.56 6754.56 1.280795 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 0.00 0.00 6792.52 6792.52
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2430.999 2430.999 0.118951 0.00002127 59.758 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2431.00 2431.00 0.118951 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788393 50.9162 1803.83 0.00 2443.60 2443.60
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1540.724 1540.724 0.137577 0.00001348 34.127 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1540.72 1540.72 0.137577 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00789909 51.0128 815.32 0.00 1549.10 1549.10
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2155.590 2155.590 0.075436 0.00001886 58.831 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2155.59 2155.59 0.075436 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00789045 50.9576 1757.85 0.00 2166.28 2166.28
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1405.680 1405.680 0.086633 0.00001230 32.898 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1405.68 1405.68 0.086633 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788376 50.9150 948.90 0.00 1413.18 1413.18
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 2826.857 2826.857 0.098927 0.00002473 77.151 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2826.86 2826.86 0.098927 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788653 50.9329 2305.27 0.00 2840.88 2840.88
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 9385.678 9385.678 1.015194 0.00008211 203.709 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9385.68 9385.68 1.015194 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788508 50.9235 4033.05 0.00 9437.75 9437.75
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 27184.007 27184.007 2.841344 0.00023782 591.978 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 27184.01 27184.01 2.841344 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00789068 50.9591 12202.66 0.00 27334.67 27334.67
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 9509.349 -999.000 0.801778 0.00027196 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 9509.35 8828.46 0.801778 21.68 15.82 0.00881291 12.80 12.09 0.00850000 32.15 0.01716522 25.06 0.0000 21.11 0.00881291 56.4500 8178.67 0.00 9528.47 9216.83
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 2608.749 2608.749 0.112609 0.00002282 74.537 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2608.75 2608.75 0.112609 21.11 14.72 0.00782667 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00782667 50.2075 2608.76 0.00 2812.32 2812.32
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 9611.612 -999.000 0.811090 0.00027489 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown 7/21 17:20:00 9611.61 8930.15 0.811090 21.68 15.81 0.00880961 12.80 12.09 0.00850000 32.04 0.01716500 25.03 0.0000 21.11 0.00880961 56.4291 8273.66 0.00 9630.99 9323.73
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 2607.811 2607.811 0.112568 0.00002281 74.510 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2607.81 2607.81 0.112568 21.11 14.72 0.00782663 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00782663 50.2073 2607.82 0.00 2811.31 2811.31
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 50035.465 -999.000 4.322168 0.00143098 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 unknown 7/21 15:10:00 50035.46 47465.93 4.322168 21.68 15.74 0.00871966 12.80 12.09 0.00850000 33.13 0.01716709 25.31 0.0000 21.11 0.00871966 55.8579 44093.63 0.00 50143.98 50143.98
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 19391.950 19391.950 0.837072 0.00016965 554.060 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 19391.95 19391.95 0.837072 21.11 14.73 0.00783841 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00783841 50.2817 15043.43 0.00 20905.21 20905.21
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 65593.198 -999.000 5.360005 0.00187592 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 65593.20 59224.70 5.360005 21.68 15.92 0.00893629 12.80 12.09 0.00850000 31.70 0.01716436 24.94 0.0000 21.11 0.00893629 57.2282 54677.14 0.00 65725.43 61667.52
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 19397.253 19397.253 0.837300 0.00016970 554.212 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 19397.25 19397.25 0.837300 21.11 14.73 0.00783830 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00783830 50.2810 15035.39 0.00 20910.92 20910.92
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 8665.807 -999.000 0.724179 0.00024784 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 8665.81 7981.90 0.724179 21.68 15.85 0.00884764 12.80 12.09 0.00850000 30.82 0.01716268 24.71 0.0000 21.11 0.00884764 56.6693 7387.09 0.00 8684.50 8327.63
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 2610.229 2610.229 0.112673 0.00002284 74.579 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2610.23 2610.23 0.112673 21.11 14.72 0.00782675 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00782675 50.2080 2610.24 0.00 2813.92 2813.92
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 8738.643 -999.000 0.730826 0.00024992 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 8738.64 8054.47 0.730826 21.68 15.84 0.00884464 12.80 12.09 0.00850000 30.82 0.01716268 24.71 0.0000 21.11 0.00884464 56.6504 7454.90 0.00 8757.54 8403.94
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 2609.291 2609.291 0.112632 0.00002283 74.552 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2609.29 2609.29 0.112632 21.11 14.72 0.00782671 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00782671 50.2078 2609.30 0.00 2812.90 2812.90
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 10115.781 10115.781 0.712305 0.00008850 231.446 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 10115.78 10115.78 0.712305 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00790536 51.0526 6359.94 0.00 10170.13 10170.13
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2605.002 -999.000 0.221277 0.00007450 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 2605.00 2434.49 0.221277 21.68 15.79 0.00878418 12.80 12.09 0.00850000 32.26 0.01716543 25.09 0.0000 21.11 0.00878418 56.2684 2257.18 0.00 2610.36 2543.35
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 808.871 808.871 0.034916 0.00000708 23.111 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 808.87 808.87 0.034916 21.11 14.75 0.00785540 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00785540 50.3896 808.87 0.00 871.99 871.99
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2631.411 -999.000 0.223703 0.00007526 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 2631.41 2460.95 0.223703 21.68 15.79 0.00878104 12.80 12.09 0.00850000 32.15 0.01716522 25.06 0.0000 21.11 0.00878104 56.2486 2281.93 0.00 2636.84 2571.20
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 808.334 808.334 0.034892 0.00000707 23.095 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 808.33 808.33 0.034892 21.11 14.75 0.00785533 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00785533 50.3891 808.34 0.00 871.41 871.41
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 11026.242 -999.000 0.907960 0.00031534 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 unknown 7/21 14:50:00 11026.24 10023.74 0.907960 21.68 15.90 0.00890578 12.80 12.09 0.00850000 33.20 0.01716721 25.32 0.0000 21.11 0.00890578 57.0366 9261.75 0.00 11048.98 10444.13
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 3921.446 3921.446 0.169272 0.00003431 112.041 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 3921.45 3921.45 0.169272 21.11 14.75 0.00786166 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786166 50.4292 3921.45 0.00 4227.45 4227.45
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13488.668 13488.668 1.781587 0.00011800 287.796 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 13488.67 13488.67 1.781587 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00792424 51.1732 4094.47 0.00 13563.88 13563.88
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13591.816 13591.816 1.782097 0.00011891 290.161 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 13591.82 13591.82 1.782097 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00792592 51.1839 4194.91 0.00 13667.59 13667.59
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 4288.481 4288.481 0.551015 0.00003752 91.696 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 4288.48 4288.48 0.551015 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00671124 43.4287 1390.77 0.00 4312.38 4312.38
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 5312.986 5312.986 0.188320 0.00004648 144.284 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 5312.99 5312.99 0.188320 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00793627 51.2498 4319.96 0.00 5339.37 5339.37
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 724644.475 -999.000 20.582962 0.02072474 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 724644.47 426495.99 20.582962 28.17 21.33 0.01313572 11.09 11.09 0.00850000 33.20 0.01716721 25.32 45.3249 23.99 0.00979754 52.5958 282330.66 0.00 725708.06 426601.78
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 59702.900 59702.900 6.174888 0.00052231 1107.868 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:50:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:50:00 59702.90 59702.90 6.174888 8.70 8.70 0.00699286 16.70 13.18 0.00800000 8.70 0.00699286 8.70 151.0829 21.07 0.00767927 49.3894 43845.43 0.00 64719.73 64719.73
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 108329.821 -999.000 2.051317 0.00309822 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 108329.82 53987.08 2.051317 33.20 25.32 0.01716721 11.94 11.73 0.00850000 33.20 0.01716721 25.32 99.9965 21.11 0.00884406 56.6449 139906.14 0.00 108488.92 54853.91
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 5950.047 5950.047 0.615395 0.00005205 110.411 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5950.05 5950.05 0.615395 8.70 8.70 0.00699286 16.70 13.18 0.00800000 8.70 0.00699286 8.70 333.3216 21.11 0.00783851 50.2824 46053.55 0.00 6450.03 6450.03



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 6754.557 6754.557 1.280795 0.00005909 140.855 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 2.9974 3.057762   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 6754.56 6754.56 1.0000 1.54046221 1.280795 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.05908578 60.00 32.22 27.78 0.000 6754.56 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6560 0.00 0.00 6792.52 6792.52 1.54046221 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2430.999 2430.999 0.118951 0.00002127 59.758 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 1.0788 1.100504 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2431.00 2431.00 1.0000 0.14306649 0.118951 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.02126527 60.00 32.22 27.78 0.000 2431.00 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00788393 21.00 0.00788393 50.9162 1803.83 0.00 2443.60 2443.60 0.14306649 16.60 13.15 0.00800000 36934.7 33.35 19.13 0.00800000 54014.9
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1540.724 1540.724 0.137577 0.00001348 34.127 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 0.6837 0.697480 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1540.72 1540.72 1.0000 0.16546861 0.137577 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01347755 60.00 32.22 27.78 0.000 1540.72 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00789909 21.00 0.00789909 51.0128 815.32 0.00 1549.10 1549.10 0.16546861 16.60 13.15 0.00800000 36934.7 25.78 16.59 0.00800000 46296.7
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2155.590 2155.590 0.075436 0.00001886 58.831 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 0.9566 0.975827 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2155.59 2155.59 1.0000 0.09072944 0.075436 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01885612 60.00 32.22 27.78 0.000 2155.59 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00789045 21.00 0.00789045 50.9576 1757.85 0.00 2166.28 2166.28 0.09072944 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60811.0
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1405.680 1405.680 0.086633 0.00001230 32.898 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 0.6238 0.636346 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1405.68 1405.68 1.0000 0.10419648 0.086633 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01229624 60.00 32.22 27.78 0.000 1405.68 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00788376 21.00 0.00788376 50.9150 948.90 0.00 1413.18 1413.18 0.10419648 16.60 13.15 0.00800000 36934.7 29.90 18.00 0.00800000 50497.4
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 2826.857 2826.857 0.098927 0.00002473 77.151 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 1.2545 1.279708 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2826.86 2826.86 1.0000 0.11898324 0.098927 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.02472806 60.00 32.22 27.78 0.000 2826.86 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00788653 21.00 0.00788653 50.9329 2305.27 0.00 2840.88 2840.88 0.11898324 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60811.0
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 9385.678 9385.678 1.015194 0.00008211 203.709 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 4.1650 4.248860 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9385.68 9385.68 1.0000 1.22101351 1.015194 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.08210163 60.00 32.22 27.78 0.000 9385.68 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00788508 21.00 0.00788508 50.9235 4033.05 0.00 9437.75 9437.75 1.22101351 16.60 13.15 0.00800000 36934.7 24.18 16.02 0.00800000 44664.2
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 27184.007 27184.007 2.841344 0.00023782 591.978 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 12.0633 12.306096 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 27184.01 27184.01 1.0000 3.41739493 2.841344 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.23779329 60.00 32.22 27.78 0.000 27184.01 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00789068 21.00 0.00789068 50.9591 12202.66 0.00 27334.67 27334.67 3.41739493 16.60 13.15 0.00800000 36934.7 24.44 16.11 0.00800000 44933.4
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 9509.349 -999.000 0.801778 0.00027196 -999.000 -999.0000 1.00000 1.00000 1021.2228 1004.8586 1.2027 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.801778 0.96432956   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 0.9496 0.949599 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 9509.35 8828.46 1.0000 0.96432956 0.801778 21.68 15.82 0.00881291 44183.3 12.80 12.09 0.00850000 34322.2 0.27193337 6.70 15.03 8.33 0.000 9509.35 32.15 0.01716522 25.06 0.00000000 0.0000 21.11 0.00881291 21.11 0.00881291 56.4500 8178.67 0.00 9528.47 9216.83 0.96432956 21.68 15.83 0.00881291 44183.3 12.32 12.09 0.00868487 34302.4
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 2608.749 2608.749 0.112609 0.00002282 74.537 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.801778 0.96432956   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 1.1577 1.180971 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2608.75 2608.75 1.0000 0.13543884 0.112609 21.11 14.72 0.00782667 41094.2 40.00 21.17 0.00800000 60796.0 0.02282014 60.00 32.22 27.78 0.000 2608.75 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00782667 21.11 0.00782667 50.2075 2608.76 0.00 2812.32 2812.32 0.13543884 16.60 12.98 0.00782667 36495.9 36.97 20.14 0.00782667 57260.4
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 9611.612 -999.000 0.811090 0.00027489 -999.000 -999.0000 1.00000 1.00000 1021.2166 1004.8586 1.2027 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.811090 0.97552904   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 0.9598 0.959811 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown unknown unknown 7/21 17:20:00 Sensible 9611.61 8930.15 1.0000 0.97552904 0.811090 21.68 15.81 0.00880961 44174.9 12.80 12.09 0.00850000 34322.2 0.27485771 6.70 15.03 8.33 0.000 9611.61 32.04 0.01716500 25.03 0.00000000 0.0000 21.11 0.00880961 21.11 0.00880961 56.4291 8273.66 0.00 9630.99 9323.73 0.97552904 21.68 15.83 0.00880961 44174.9 12.32 12.09 0.00868482 34302.3
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 2607.811 2607.811 0.112568 0.00002281 74.510 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.811090 0.97552904   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 1.1573 1.180546 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2607.81 2607.81 1.0000 0.13539017 0.112568 21.11 14.72 0.00782663 41094.1 40.00 21.17 0.00800000 60796.0 0.02281194 60.00 32.22 27.78 0.000 2607.81 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00782663 21.11 0.00782663 50.2073 2607.82 0.00 2811.31 2811.31 0.13539017 16.60 12.98 0.00782663 36495.8 36.97 20.14 0.00782663 57260.3
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 50035.465 -999.000 4.322168 0.00143098 -999.000 -999.0000 1.00000 1.00000 1021.0494 1004.8586 1.2027 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 4.322168 5.19843977   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 4.9966 4.996518 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 unknown unknown unknown 7/21 15:10:00 Sensible 50035.46 47465.93 1.0000 5.19843977 4.322168 21.68 15.74 0.00871966 43947.3 12.80 12.09 0.00850000 34322.2 1.43083526 6.70 15.03 8.33 0.000 50035.46 33.13 0.01716709 25.31 0.00000000 0.0000 21.11 0.00871966 21.11 0.00871966 55.8579 44093.63 0.00 50143.98 50143.98 5.19843977 21.68 15.75 0.00871966 43947.3 12.24 12.09 0.00871966 34301.3
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 19391.950 19391.950 0.837072 0.00016965 554.060 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 4.322168 5.19843977   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 8.6055 8.778662 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 19391.95 19391.95 1.0000 1.00677850 0.837072 21.11 14.73 0.00783841 41124.1 40.00 21.17 0.00800000 60796.0 0.16963194 60.00 32.22 27.78 0.000 19391.95 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00783841 21.11 0.00783841 50.2817 15043.43 0.00 20905.21 20905.21 1.00677850 16.60 12.99 0.00783841 36525.6 36.97 20.15 0.00783841 57290.1
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 65593.198 -999.000 5.360005 0.00187592 -999.000 -999.0000 1.00000 1.00000 1021.4521 1004.8586 1.2027 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.360005 6.44668641   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 6.5502 6.550107 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 65593.20 59224.70 1.0000 6.44668641 5.360005 21.68 15.92 0.00893629 44496.9 12.80 12.09 0.00850000 34322.2 1.87573077 6.70 15.03 8.33 0.000 65593.20 31.70 0.01716436 24.94 0.00000000 0.0000 21.11 0.00893629 21.11 0.00893629 57.2282 54677.14 0.00 65725.43 61667.52 6.44668641 21.68 15.94 0.00893629 44496.9 12.32 12.09 0.00868688 34301.7
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 19397.253 19397.253 0.837300 0.00016970 554.212 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.360005 6.44668641   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 8.6078 8.781062 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 19397.25 19397.25 1.0000 1.00705380 0.837300 21.11 14.73 0.00783830 41123.9 40.00 21.17 0.00800000 60796.0 0.16967832 60.00 32.22 27.78 0.000 19397.25 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00783830 21.11 0.00783830 50.2810 15035.39 0.00 20910.92 20910.92 1.00705380 16.60 12.99 0.00783830 36525.3 36.97 20.15 0.00783830 57289.8
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 8665.807 -999.000 0.724179 0.00024784 -999.000 -999.0000 1.00000 1.00000 1021.2873 1004.8586 1.2027 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.724179 0.87099850   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 0.8654 0.865363 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 8665.81 7981.90 1.0000 0.87099850 0.724179 21.68 15.85 0.00884764 44271.5 12.80 12.09 0.00850000 34322.2 0.24781107 6.70 15.03 8.33 0.000 8665.81 30.82 0.01716268 24.71 0.00000000 0.0000 21.11 0.00884764 21.11 0.00884764 56.6693 7387.09 0.00 8684.50 8327.63 0.87099850 21.68 15.86 0.00884764 44271.5 12.32 12.09 0.00868530 34300.7
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 2610.229 2610.229 0.112673 0.00002284 74.579 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.724179 0.87099850   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 1.1583 1.181641 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2610.23 2610.23 1.0000 0.13551568 0.112673 21.11 14.72 0.00782675 41094.5 40.00 21.17 0.00800000 60796.0 0.02283309 60.00 32.22 27.78 0.000 2610.23 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00782675 21.11 0.00782675 50.2080 2610.24 0.00 2813.92 2813.92 0.13551568 16.60 12.98 0.00782675 36496.1 36.97 20.14 0.00782675 57260.6
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 8738.643 -999.000 0.730826 0.00024992 -999.000 -999.0000 1.00000 1.00000 1021.2817 1004.8586 1.2027 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.730826 0.87899237   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 0.8727 0.872637 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 8738.64 8054.47 1.0000 0.87899237 0.730826 21.68 15.84 0.00884464 44263.9 12.80 12.09 0.00850000 34322.2 0.24989393 6.70 15.03 8.33 0.000 8738.64 30.82 0.01716268 24.71 0.00000000 0.0000 21.11 0.00884464 21.11 0.00884464 56.6504 7454.90 0.00 8757.54 8403.94 0.87899237 21.68 15.86 0.00884464 44263.9 12.32 12.09 0.00868525 34300.7
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 2609.291 2609.291 0.112632 0.00002283 74.552 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.730826 0.87899237   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 1.1579 1.181216 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2609.29 2609.29 1.0000 0.13546699 0.112632 21.11 14.72 0.00782671 41094.3 40.00 21.17 0.00800000 60796.0 0.02282488 60.00 32.22 27.78 0.000 2609.29 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00782671 21.11 0.00782671 50.2078 2609.30 0.00 2812.90 2812.90 0.13546699 16.60 12.98 0.00782671 36496.0 36.97 20.14 0.00782671 57260.5
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 10115.781 10115.781 0.712305 0.00008850 231.446 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 4.4890 4.579376 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 10115.78 10115.78 1.0000 0.85671732 0.712305 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.08848824 60.00 32.22 27.78 0.000 10115.78 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00790536 21.00 0.00790536 51.0526 6359.94 0.00 10170.13 10170.13 0.85671732 16.60 13.15 0.00800000 36934.7 28.24 17.44 0.00800000 48805.8
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2605.002 -999.000 0.221277 0.00007450 -999.000 -999.0000 1.00000 1.00000 1021.1694 1004.8586 1.2027 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.221277 0.26613900   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 0.2601 0.260134 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 2605.00 2434.49 1.0000 0.26613900 0.221277 21.68 15.79 0.00878418 44110.3 12.80 12.09 0.00850000 34322.2 0.07449375 6.70 15.03 8.33 0.000 2605.00 32.26 0.01716543 25.09 0.00000000 0.0000 21.11 0.00878418 21.11 0.00878418 56.2684 2257.18 0.00 2610.36 2543.35 0.26613900 21.68 15.80 0.00878418 44110.3 12.32 12.09 0.00868442 34302.1
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 808.871 808.871 0.034916 0.00000708 23.111 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.221277 0.26613900   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 0.3589 0.366173 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 808.87 808.87 1.0000 0.04199428 0.034916 21.11 14.75 0.00785540 41167.2 40.00 21.17 0.00800000 60796.0 0.00707564 60.00 32.22 27.78 0.000 808.87 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00785540 21.11 0.00785540 50.3896 808.87 0.00 871.99 871.99 0.04199428 16.60 13.01 0.00785540 36568.6 36.97 20.16 0.00785540 57333.2
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2631.411 -999.000 0.223703 0.00007526 -999.000 -999.0000 1.00000 1.00000 1021.1635 1004.8586 1.2027 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.223703 0.26905642   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 0.2628 0.262771 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 2631.41 2460.95 1.0000 0.26905642 0.223703 21.68 15.79 0.00878104 44102.3 12.80 12.09 0.00850000 34322.2 0.07524893 6.70 15.03 8.33 0.000 2631.41 32.15 0.01716522 25.06 0.00000000 0.0000 21.11 0.00878104 21.11 0.00878104 56.2486 2281.93 0.00 2636.84 2571.20 0.26905642 21.68 15.80 0.00878104 44102.3 12.32 12.09 0.00868437 34302.0
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 808.334 808.334 0.034892 0.00000707 23.095 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.223703 0.26905642   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 0.3587 0.365930 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 808.33 808.33 1.0000 0.04196639 0.034892 21.11 14.75 0.00785533 41167.0 40.00 21.17 0.00800000 60796.0 0.00707094 60.00 32.22 27.78 0.000 808.33 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00785533 21.11 0.00785533 50.3891 808.34 0.00 871.41 871.41 0.04196639 16.60 13.01 0.00785533 36568.5 36.97 20.16 0.00785533 57333.0
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 11026.242 -999.000 0.907960 0.00031534 -999.000 -999.0000 1.00000 1.00000 1021.3954 1004.8586 1.2027 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.907960 1.09203934   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 1.1011 1.101075 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 unknown unknown unknown 7/21 14:50:00 Sensible 11026.24 10023.74 1.0000 1.09203934 0.907960 21.68 15.90 0.00890578 44419.1 12.80 12.09 0.00850000 34322.2 0.31531108 6.70 15.03 8.33 0.000 11026.24 33.20 0.01716721 25.32 0.00000000 0.0000 21.11 0.00890578 21.11 0.00890578 57.0366 9261.75 0.00 11048.98 10444.13 1.09203934 21.68 15.91 0.00890578 44419.1 12.32 12.09 0.00868632 34301.4
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 3921.446 3921.446 0.169272 0.00003431 112.041 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.907960 1.09203934   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 1.7402 1.775224 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 3921.45 3921.45 1.0000 0.20359044 0.169272 21.11 14.75 0.00786166 41183.1 40.00 21.17 0.00800000 60796.0 0.03430302 60.00 32.22 27.78 0.000 3921.45 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786166 21.11 0.00786166 50.4292 3921.45 0.00 4227.45 4227.45 0.20359044 16.60 13.02 0.00786166 36584.5 36.97 20.16 0.00786166 57349.0
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 13488.668 13488.668 1.781587 0.00011800 287.796 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 5.9858 6.106268 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 13488.67 13488.67 1.0000 2.14278349 1.781587 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.11799271 60.00 32.22 27.78 0.000 13488.67 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00792424 21.00 0.00792424 51.1732 4094.47 0.00 13563.88 13563.88 2.14278349 16.60 13.15 0.00800000 36934.7 22.81 15.52 0.00800000 43264.8
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 13591.816 13591.816 1.782097 0.00011891 290.161 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 6.0316 6.152963 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 Sensible 13591.82 13591.82 1.0000 2.14339764 1.782097 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.11889500 60.00 32.22 27.78 0.000 13591.82 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00792592 21.00 0.00792592 51.1839 4194.91 0.00 13667.59 13667.59 2.14339764 16.60 13.15 0.00800000 36934.7 22.85 15.54 0.00800000 43311.3
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 4288.481 4288.481 0.551015 0.00003752 91.696 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 1.9031 1.941379 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 4288.48 4288.48 1.0000 0.66272750 0.551015 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.03751368 60.00 32.22 27.78 0.000 4288.48 8.70 0.00699286 8.70 0.00000000 0.0000 20.26 0.00671124 21.00 0.00671124 43.4287 1390.77 0.00 4312.38 4312.38 0.66272750 16.60 13.15 0.00800000 36934.7 22.98 15.59 0.00800000 43441.7
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 5312.986 5312.986 0.188320 0.00004648 144.284 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 2.3577 2.405169 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:40:00 Sensible 5312.99 5312.99 1.0000 0.22650036 0.188320 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.04647558 60.00 32.22 27.78 0.000 5312.99 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00793627 21.00 0.00793627 51.2498 4319.96 0.00 5339.37 5339.37 0.22650036 16.60 13.15 0.00800000 36934.7 39.72 21.10 0.00800000 60508.1
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 724644.475 -999.000 20.582962 0.02072474 -999.000 -999.0000 1.00000 1.00000 1029.2586 1004.8586 1.2027 VAV WITH REHEAT FAN Fan:VariableVolume 20.582962 24.75592939   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 72.3640 72.364015 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 724644.47 426495.99 1.0000 24.75592939 20.582962 28.17 21.33 0.01313572 61845.7 11.09 11.09 0.00850000 32574.2 20.72262611 6.70 15.03 8.33 43639.464 681005.01 33.20 0.01716721 25.32 9.32920000 45.3249 23.99 0.00978442 23.99 0.00979754 52.5958 282330.66 0.00 725708.06 426601.78 24.75592939 28.17 21.35 0.01313572 61845.7 11.43 11.37 0.00834534 32531.2
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 59702.900 59702.900 6.174888 0.00052231 1107.868 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 VAV WITH REHEAT FAN Fan:VariableVolume 20.582962 24.75592939   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 26.4941 27.027275 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:50:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:50:00 Sensible 59702.90 59702.90 1.0000 7.42677882 6.174888 8.70 8.70 0.00699286 26343.9 16.70 13.18 0.00800000 37036.7 0.52225373 60.00 32.22 27.78 0.000 59702.90 8.70 0.00699286 8.70 9.32920000 151.0829 18.49 0.00773950 21.07 0.00767927 49.3894 43845.43 0.00 64719.73 64719.73 7.42677882 2.80 2.80 0.00699286 20338.7 11.36 9.92 0.00699286 29053.0
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 108329.821 -999.000 2.051317 0.00309822 -999.000 -999.0000 1.00000 1.00000 1036.7530 1004.8586 1.2027 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46711237   4197.9300 999.8980 28.63664508 15.03 6.70 8.33 1001387.88 10.8180 10.817968 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 Sensible 108329.82 53987.08 1.0000 2.46719911 2.051317 33.20 25.32 0.01716721 77354.4 11.94 11.73 0.00850000 33446.3 3.09790311 6.70 15.03 8.33 2195.006 106134.81 33.20 0.01716721 25.32 2.05124512 99.9965 21.11 0.00885273 21.11 0.00884406 56.6449 139906.14 0.00 108488.92 54853.91 2.46719911 33.20 25.34 0.01716721 77354.4 11.75 11.72 0.00855008 33381.9
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 5950.047 5950.047 0.615395 0.00005205 110.411 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46711237   4197.9300 999.8980 1.93232110 54.44 82.22 27.78 225344.38 2.6404 2.693564 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5950.05 5950.05 1.0000 0.74015973 0.615395 8.70 8.70 0.00699286 26343.9 16.70 13.18 0.00800000 37036.7 0.05204830 60.00 32.22 27.78 0.000 5950.05 8.70 0.00699286 8.70 2.05124512 333.3216 21.11 0.00783830 21.11 0.00783851 50.2824 46053.55 0.00 6450.03 6450.03 0.74015973 2.80 2.80 0.00699286 20338.7 11.36 9.92 0.00699286 29053.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000914 0.000000 0.000000 Sum   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 5217.00 1011.67 0.00
RETAIL_1_FLR_1 7300.50 1355.67 343.17
RETAIL_2_FLR_1 4860.33 2195.67 15.33
MECH_FLR_1 7107.67 888.67 79.67
STORAGE_FLR_1 2073.67 4692.67 0.00
LAUNDRY_FLR_1 8760.00 6166.50 6166.50
CAFE_FLR_1 4378.50 5347.00 2368.00
LOBBY_FLR_1 5214.00 4431.17 2620.83
ROOM_1_FLR_3 46.33 7983.17 46.33
ROOM_2_FLR_3 459.50 7922.33 404.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 322.00 8759.50 322.00
ROOM_5_FLR_3 42.67 7948.17 42.67
ROOM_6_FLR_3 470.67 7924.67 410.00
CORRIDOR_FLR_3 2084.33 5719.50 1341.83
ROOM_1_FLR_6 171.50 7407.83 135.50
ROOM_2_FLR_6 716.67 7339.00 573.00
ROOM_3_MULT9_FLR_6 158.67 7672.83 85.00
BANQUET_FLR_6 4150.50 5204.33 2167.50
DINING_FLR_6 5413.33 4019.00 2229.83
KITCHEN_FLR_6 8760.00 6895.17 6895.17
CORRIDOR_FLR_6 7174.83 1390.00 317.17
Facility 8760.00 8760.00 8430.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 3.00 0.00 3.00
ROOM_2_FLR_3 0.00 5.00 0.00 5.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 49.67 0.00 49.67
ROOM_5_FLR_3 0.00 0.33 0.00 0.33
ROOM_6_FLR_3 0.00 22.17 0.00 22.17
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 18.83 0.00 18.83
ROOM_2_FLR_6 0.00 15.33 0.00 15.33
ROOM_3_MULT9_FLR_6 0.00 62.67 0.00 62.67
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 114.33 0.00 114.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.620 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.307 0.132 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.025 0.044 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.329 0.049 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.508 0.049 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 11.887 0.141 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 2.979 0.103 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.238 0.043 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.342 0.169 0.000 0.065
ROOM_2_FLR_3 0.95 1.50 118.93 0.342 0.169 0.000 0.067
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.388 0.075 0.000 0.105
ROOM_5_FLR_3 0.95 1.50 118.94 0.342 0.169 0.000 0.065
ROOM_6_FLR_3 0.95 1.50 118.93 0.342 0.169 0.000 0.067
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.330 0.021 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.342 0.169 0.000 0.079
ROOM_2_FLR_6 0.95 1.50 118.93 0.342 0.169 0.000 0.081
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.388 0.138 0.000 0.125
BANQUET_FLR_6 144.99 249.90 1010.89 3.884 0.049 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 3.907 0.049 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 12.582 0.141 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.525 0.035 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.526 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 0.933 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.924 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.009 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.434 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 5.546 0.002 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 2.526 0.002 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.133 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.284 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.002 0.000 0.000
BANQUET_FLR_6 144.99 249.90 1010.89 3.446 0.001 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 3.522 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 5.017 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.310 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.79 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.047
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.56 142.30 748.35 188.86 0.0000 0.173
LOBBY_FLR_1 VAV WITH REHEAT 245.09 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.25 1604.23 35184.81 11345.29 0.0000 137.036


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 25609064.71 0.00 25609064.71 0.00 25609064.71 26946214.98 6640.89 236.32 1882.79 0.00
RETAIL_1_FLR_1 2971589.27 0.00 2971589.27 299317.48 3270906.75 2498216.28 3240.62 163.37 5356.01 0.00
RETAIL_2_FLR_1 2700954.31 0.00 2700954.31 115536.93 2816491.24 2294951.32 749.27 707.05 7303.68 0.00
MECH_FLR_1 1828442.66 0.00 1828442.66 273060.66 2101503.32 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1637440.59 0.00 1637440.59 157540.96 1794981.55 1821682.01 8732.17 17.33 10.50 0.00
LAUNDRY_FLR_1 31471601.07 0.00 31471601.07 372850.38 31844451.45 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 19135906.06 0.00 19135906.06 661658.24 19797564.30 14544917.54 865.01 670.69 7224.29 0.00
LOBBY_FLR_1 54936522.50 0.00 54936522.50 1890508.72 56827031.22 59728886.00 7754.64 250.01 755.35 0.00
ROOM_1_FLR_3 1406076.84 66861.55 1472938.38 173731.82 1646670.21 1946875.62 2433.33 5505.50 821.17 0.00
ROOM_2_FLR_3 1405912.09 68815.04 1474727.13 173718.57 1648445.70 1946647.51 2433.33 5505.79 820.88 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 48473.13 1148385.10 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19070354.14 67658.68 19138012.81 48486.38 19186499.19 26405105.73 2433.33 5586.37 740.30 0.00
ROOM_5_FLR_3 1406076.84 66956.82 1473033.65 173731.82 1646765.48 1946875.62 2433.33 5505.50 821.17 0.00
ROOM_6_FLR_3 1405912.09 68770.81 1474682.90 173718.57 1648401.47 1946647.51 2433.33 5505.67 821.00 0.00
CORRIDOR_FLR_3 13441912.79 0.00 13441912.79 210076.73 13651989.52 14972100.18 8746.00 8.33 5.67 0.00
ROOM_1_FLR_6 351519.21 80929.38 432448.59 173766.55 606215.14 486718.90 2225.14 5500.49 1034.37 0.00
ROOM_2_FLR_6 351478.02 82723.25 434201.27 173753.29 607954.56 486661.88 2230.64 5503.67 1025.69 0.00
ROOM_3_MULT9_FLR_6 2258331.41 81099.58 2339430.99 88905.05 2428336.03 3126920.42 2433.33 5495.00 831.67 0.00
BANQUET_FLR_6 33693889.63 0.00 33693889.63 424294.23 34118183.87 37458366.31 8751.83 8.17 0.00 0.00
DINING_FLR_6 33860715.93 0.00 33860715.93 424294.23 34285010.16 37458366.31 8642.08 50.92 67.00 0.00
KITCHEN_FLR_6 33858532.72 0.00 33858532.72 379841.71 34238374.43 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 5643594.78 0.00 5643594.78 371767.87 6015362.65 3961413.96 2295.08 71.84 6393.08 0.00
Total Facility 0.19E+10 7121225.04 0.19E+10 17507169.38 0.19E+10 0.43E+10 8760.00 6137.21 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 0.8121 0.0000 0.8121 0.0000 0.8121 0.8545 6640.89 236.32 1882.79
RETAIL_1_FLR_1 0.0942 0.0000 0.0942 0.0095 0.1037 0.0792 3240.62 163.37 5356.01
RETAIL_2_FLR_1 0.0856 0.0000 0.0856 0.0037 0.0893 0.0728 749.27 707.05 7303.68
MECH_FLR_1 0.0580 0.0000 0.0580 0.0087 0.0666 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0519 0.0000 0.0519 0.0050 0.0569 0.0578 8732.17 17.33 10.50
LAUNDRY_FLR_1 0.9980 0.0000 0.9980 0.0118 1.0098 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.6068 0.0000 0.6068 0.0210 0.6278 0.4612 865.01 670.69 7224.29
LOBBY_FLR_1 1.7420 0.0000 1.7420 0.0599 1.8020 1.8940 7754.64 250.01 755.35
ROOM_1_FLR_3 0.0446 0.0021 0.0467 0.0055 0.0522 0.0617 2433.33 5505.50 821.17
ROOM_2_FLR_3 0.0446 0.0022 0.0468 0.0055 0.0523 0.0617 2433.33 5505.79 820.88
ROOM_4_MULT19_FLR_3 0.6047 0.0021 0.6069 0.0015 0.6084 0.8373 2433.33 5586.37 740.30
ROOM_5_FLR_3 0.0446 0.0021 0.0467 0.0055 0.0522 0.0617 2433.33 5505.50 821.17
ROOM_6_FLR_3 0.0446 0.0022 0.0468 0.0055 0.0523 0.0617 2433.33 5505.67 821.00
CORRIDOR_FLR_3 0.4262 0.0000 0.4262 0.0067 0.4329 0.4748 8746.00 8.33 5.67
ROOM_1_FLR_6 0.0111 0.0026 0.0137 0.0055 0.0192 0.0154 2225.14 5500.49 1034.37
ROOM_2_FLR_6 0.0111 0.0026 0.0138 0.0055 0.0193 0.0154 2230.64 5503.67 1025.69
ROOM_3_MULT9_FLR_6 0.0716 0.0026 0.0742 0.0028 0.0770 0.0992 2433.33 5495.00 831.67
BANQUET_FLR_6 1.0684 0.0000 1.0684 0.0135 1.0819 1.1878 8751.83 8.17 0.00
DINING_FLR_6 1.0737 0.0000 1.0737 0.0135 1.0872 1.1878 8642.08 50.92 67.00
KITCHEN_FLR_6 1.0736 0.0000 1.0736 0.0120 1.0857 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.1790 0.0000 0.1790 0.0118 0.1907 0.1256 2295.08 71.84 6393.08
Total Facility 56.8869 0.2258 57.1128 0.4383 57.5511 73.7328 8760.00 6137.21 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.38E+09 0.00 0.38E+09 0.21E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 41597263.41 583815.10 42181078.51 64690340.46 8752.61 7.39 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 11.9626 0.0000 11.9626 6.7627 0.00 0.00 8760.00
FLR_3_DOAS 1.3190 0.0185 1.3376 2.0513 8752.61 7.39 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 142.51 0.00 0.00 0.00 0.00 8617.49 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6691.67 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 13.1557 0.0000 0.0000 0.0000 0.0000 11.9444 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.7269 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1345
Defaulted Fields 1183
Fields with Defaults 4013
Autosized Fields 349
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 6750.83 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
Electricity:Building 2110.86 28203.44 02-JAN-02:10 124003.41 02-JAN-20:10
Electricity:Zone:BASEMENT 235.57 2868.06 02-JAN-02:10 17194.07 02-JAN-20:10
Electricity:SpaceType:GENERAL 2103.77 28062.29 02-JAN-02:10 123762.08 02-JAN-20:10
InteriorLights:Electricity 455.32 4168.62 02-JAN-02:10 37630.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 92.46 840.16 02-JAN-02:10 7561.54 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 455.32 4168.62 02-JAN-02:10 37630.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 455.32 4168.62 02-JAN-02:10 37630.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 92.46 840.16 02-JAN-02:10 7561.54 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 455.32 4168.62 02-JAN-02:10 37630.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 14.37 182.36 02-JAN-02:10 1027.80 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 4.18 38.02 02-JAN-02:10 342.20 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 4.18 38.02 02-JAN-02:10 342.20 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 16.64 211.17 02-JAN-02:10 1190.20 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 4.85 44.03 02-JAN-02:10 396.26 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 4.85 44.03 02-JAN-02:10 396.26 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 21.14 255.50 02-JAN-02:10 1548.43 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.67 78.78 02-JAN-02:10 708.98 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.67 78.78 02-JAN-02:10 708.98 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.58 69.04 02-JAN-02:10 404.67 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.99 18.06 02-JAN-02:10 162.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.99 18.06 02-JAN-02:10 162.52 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 71.63 996.30 02-JAN-02:10 4875.27 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.70 33.61 02-JAN-02:10 302.47 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.70 33.61 02-JAN-02:10 302.47 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 21.02 293.25 02-JAN-02:10 1775.61 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 6.68 39.62 01-JAN-13:10 810.33 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 6.68 39.62 01-JAN-13:10 810.33 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 227.74 2868.89 02-JAN-02:10 16846.53 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 78.74 757.48 02-JAN-02:10 6817.32 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 78.74 757.48 02-JAN-02:10 6817.32 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 253.77 3619.58 02-JAN-10:10 20179.99 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 253.84 3620.57 02-JAN-10:10 20185.51 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 54.59 496.05 02-JAN-02:10 4464.45 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 54.59 496.05 02-JAN-02:10 4464.45 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 54.59 496.05 02-JAN-02:10 4464.45 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 3.85 55.20 01-JAN-02:10 290.10 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 3.85 55.19 01-JAN-02:10 290.07 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 30.06 428.75 02-JAN-10:10 2390.39 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 190.45 2407.41 02-JAN-02:10 8170.92 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 14.59 158.11 02-JAN-02:10 1423.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 14.59 158.11 02-JAN-02:10 1423.01 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 190.45 2407.41 02-JAN-02:10 8170.92 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 14.59 158.11 02-JAN-02:10 1423.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 14.59 158.11 02-JAN-02:10 1423.01 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 440.25 5906.67 02-JAN-02:10 18521.62 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 9.14 83.05 02-JAN-02:10 747.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 9.14 83.05 02-JAN-02:10 747.41 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 14.44 131.25 02-JAN-02:10 1181.23 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 14.44 131.25 02-JAN-02:10 1181.23 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 14.44 131.25 02-JAN-02:10 1181.23 02-JAN-20:10
InteriorEquipment:Electricity 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 44.53 744.27 16-MAR-22:30 2791.93 26-NOV-11:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 3249.37 7471.87 04-FEB-03:40 191307.90 27-JUL-18:10
LowTempRefrigeration:Refrigeration:Electricity 15.90 0.00 01-JAN-11:10 1306.51 21-APR-04:00
MedTempRefrigeration:Refrigeration:Electricity 21.54 642.68 16-MAR-15:10 717.37 28-AUG-13:10
Fans:Electricity 607.81 11861.05 21-DEC-04:00 39239.64 22-SEP-22:00
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityProduced:Facility 208.45 -0.00 30-DEC-17:30 33843.43 06-MAY-11:30
ElectricityProduced:Plant 208.45 -0.00 30-DEC-17:30 33843.43 06-MAY-11:30
Photovoltaic:ElectricityProduced 217.61 0.00 01-JAN-00:10 35245.84 06-MAY-11:30
PowerConversion:ElectricityProduced -9.16 -1402.41 06-MAY-11:30 0.00 01-JAN-00:10
Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
DCtoACInverter Ancillary:Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 870.89 19565.25 01-FEB-04:00 48323.37 22-SEP-22:00
ExteriorEquipment:Electricity 390.56 5777.98 02-JAN-02:20 23858.54 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 21.47 378.90 02-JAN-02:20 1270.25 02-JAN-07:20
ElectricityPurchased:Facility 6542.38 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
ElectricityPurchased:Plant 6542.38 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
Cogeneration:ElectricityPurchased 6542.38 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
General:Cogeneration:ElectricityPurchased 6542.38 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 6542.38 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
ElectricityNet:Plant 6542.38 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
Cogeneration:ElectricityNet 6542.38 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
General:Cogeneration:ElectricityNet 6542.38 71243.86 04-FEB-04:00 366903.44 27-JUL-19:10
General:Fans:Electricity 607.81 11861.05 21-DEC-04:00 39239.64 22-SEP-22:00
ExteriorLights:Electricity 150.61 0.00 01-JAN-07:20 9571.94 01-JAN-00:10
General:ExteriorLights:Electricity 150.61 0.00 01-JAN-07:20 9571.94 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 366.65 5383.28 01-JAN-00:10 22430.31 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.45 15.80 01-JAN-00:10 157.97 01-JAN-07:10
HeatRecovery:Electricity 241.61 6743.70 02-APR-09:00 8265.52 01-JAN-10:00
General:HeatRecovery:Electricity 241.61 6743.70 02-APR-09:00 8265.52 01-JAN-10:00
WaterSystems:Electricity 90.74 1086.56 11-MAY-01:00 4738.76 28-DEC-19:10
Water Heater:WaterSystems:Electricity 90.74 1086.56 11-MAY-01:00 4738.76 28-DEC-19:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 3008.81 1413.28 16-MAR-07:20 181382.53 28-JUL-15:30
General:Cooling:Electricity 3008.81 1413.28 16-MAR-07:20 181382.53 28-JUL-15:30
Pumps:Electricity 112.38 3255.63 27-DEC-08:10 4528.45 27-JUL-18:10
General:Pumps:Electricity 112.38 3255.63 27-DEC-08:10 4528.45 27-JUL-18:10
WIRED_LTG_ELECTRICITY 16.03 0.00 01-JAN-00:10 1324.60 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 3939.24 26805.16 02-JAN-02:10 287928.26 26-DEC-18:10
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 2150.40 13443.27 28-APR-09:00 188434.46 27-DEC-23:00
WaterSystems:NaturalGas 2148.53 13443.27 28-FEB-10:00 185853.65 17-JAN-21:20
Water Heater:WaterSystems:NaturalGas 2148.53 13443.27 28-FEB-10:00 185853.65 17-JAN-21:20
Heating:NaturalGas 1.88 0.00 01-JAN-00:10 22051.98 16-MAR-08:20
Boiler:Heating:NaturalGas 1.88 0.00 01-JAN-00:10 22051.98 16-MAR-08:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 10186.07 1307.46 16-MAR-07:20 616514.73 18-SEP-18:10
PlantLoopCoolingDemand:HVAC 10186.07 1307.46 16-MAR-07:20 616514.73 18-SEP-18:10
CoolingCoils:PlantLoopCoolingDemand 10186.07 1307.46 16-MAR-07:20 616514.73 18-SEP-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 28-MAR-20:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 28-MAR-20:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 28-MAR-20:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 28-MAR-20:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 28-MAR-20:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 28-MAR-20:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 09-JAN-08:00
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 09-JAN-08:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 42672.85 154140.72 05-FEB-03:10 2565651.75 18-SEP-18:10
EnergyTransfer:Building 6193.91 108234.65 04-FEB-08:00 324663.90 29-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 724.46 9115.90 04-FEB-04:00 34483.10 23-JUL-10:50
Refrigeration:EnergyTransfer 190.13 4168.03 16-MAR-22:10 10382.93 22-DEC-07:30
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 95.07 2084.01 16-MAR-22:10 5191.47 22-DEC-07:30
General:Refrigeration:EnergyTransfer 95.07 2084.01 16-MAR-22:10 5191.47 22-DEC-07:30
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 95.07 2084.01 16-MAR-22:10 5191.47 22-DEC-07:30
EnergyTransfer:Plant 24193.73 28311.34 04-FEB-04:00 1440087.48 18-SEP-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.77 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 73.29 2042.90 16-MAR-15:10 2564.27 28-AUG-13:10
EnergyTransfer:Zone:BASEMENT 458.47 11291.76 21-MAR-14:00 21792.44 22-SEP-21:00
Heating:EnergyTransfer 0.27 0.00 01-JAN-00:10 5407.79 04-FEB-09:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 0.27 0.00 01-JAN-00:10 5407.79 04-FEB-09:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 6098.58 105462.44 04-FEB-08:00 321069.81 29-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 458.47 11291.76 21-MAR-14:00 21792.44 22-SEP-21:00
General:Cooling:EnergyTransfer 6098.58 105462.44 04-FEB-08:00 321069.81 29-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 458.47 11291.76 21-MAR-14:00 21792.44 22-SEP-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 53.94 126.10 04-FEB-07:10 3521.30 09-DEC-12:30
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 53.94 126.10 04-FEB-07:10 3521.30 09-DEC-12:30
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 53.94 126.10 04-FEB-07:10 3521.30 09-DEC-12:30
EnergyTransfer:Zone:RETAIL_2_FLR_1 46.47 960.32 04-FEB-12:00 2492.24 28-JUL-20:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 46.47 960.32 04-FEB-12:00 2492.24 28-JUL-20:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 46.47 960.32 04-FEB-12:00 2492.24 28-JUL-20:10
EnergyTransfer:Zone:MECH_FLR_1 34.18 23.73 04-FEB-11:30 2822.58 28-JUL-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 34.18 23.73 04-FEB-11:30 2822.58 28-JUL-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 34.18 23.73 04-FEB-11:30 2822.58 28-JUL-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 26.73 451.97 04-FEB-10:20 1296.17 29-JUL-19:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 26.73 451.97 04-FEB-10:20 1296.17 29-JUL-19:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 26.73 451.97 04-FEB-10:20 1296.17 29-JUL-19:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 583.66 7390.46 04-FEB-06:00 37391.52 28-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 583.66 7390.46 04-FEB-06:00 37391.52 28-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 583.66 7390.46 04-FEB-06:00 37391.52 28-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 297.96 3683.13 16-MAR-08:10 12437.98 09-DEC-11:40
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 297.96 3683.13 16-MAR-08:10 12437.98 09-DEC-11:40
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 297.96 3683.13 16-MAR-08:10 12437.98 09-DEC-11:40
EnergyTransfer:Zone:LOBBY_FLR_1 935.19 20134.97 16-MAR-11:00 42328.33 28-JUL-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 935.19 20134.97 16-MAR-11:00 42328.33 28-JUL-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 935.19 20134.97 16-MAR-11:00 42328.33 28-JUL-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 90.79 0.00 01-JAN-08:00 9029.05 30-SEP-15:30
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.03 0.00 01-JAN-00:10 621.27 29-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.03 0.00 01-JAN-00:10 621.27 29-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 90.77 0.00 01-JAN-08:00 9029.05 30-SEP-15:30
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 90.77 0.00 01-JAN-08:00 9029.05 30-SEP-15:30
EnergyTransfer:Zone:ROOM_2_FLR_3 78.20 0.00 01-JAN-08:00 8897.39 28-JUL-15:30
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 0.03 0.00 01-JAN-00:10 639.13 16-MAR-22:00
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 0.03 0.00 01-JAN-00:10 639.13 16-MAR-22:00
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 78.17 0.00 01-JAN-08:00 8897.39 28-JUL-15:30
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 78.17 0.00 01-JAN-08:00 8897.39 28-JUL-15:30
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 465.90 0.00 14-JAN-16:10 36900.16 03-DEC-14:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 465.90 0.00 14-JAN-16:10 36900.16 03-DEC-14:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 465.90 0.00 14-JAN-16:10 36900.16 03-DEC-14:10
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 639.85 0.00 01-JAN-08:00 60464.41 21-JUN-21:00
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.07 0.00 01-JAN-00:10 3864.95 25-JAN-19:50
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.07 0.00 01-JAN-00:10 3864.95 25-JAN-19:50
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 639.78 0.00 01-JAN-08:00 60464.41 21-JUN-21:00
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 639.78 0.00 01-JAN-08:00 60464.41 21-JUN-21:00
EnergyTransfer:Zone:ROOM_5_FLR_3 91.68 0.00 01-JAN-08:00 7797.73 29-JUL-15:30
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.02 0.00 01-JAN-00:10 549.47 04-FEB-19:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.02 0.00 01-JAN-00:10 549.47 04-FEB-19:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 91.66 0.00 01-JAN-08:00 7797.73 29-JUL-15:30
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 91.66 0.00 01-JAN-08:00 7797.73 29-JUL-15:30
EnergyTransfer:Zone:ROOM_6_FLR_3 78.96 0.00 01-JAN-08:00 7862.84 04-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 0.02 0.00 01-JAN-00:10 598.77 16-MAR-22:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 0.02 0.00 01-JAN-00:10 598.77 16-MAR-22:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 78.93 0.00 01-JAN-08:00 7862.84 04-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 78.93 0.00 01-JAN-08:00 7862.84 04-JUL-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 225.55 5211.48 05-FEB-08:30 9818.95 22-SEP-21:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 225.55 5211.48 05-FEB-08:30 9818.95 22-SEP-21:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 225.55 5211.48 05-FEB-08:30 9818.95 22-SEP-21:10
EnergyTransfer:Zone:ROOM_1_FLR_6 22.39 0.00 01-JAN-08:00 2642.63 30-SEP-15:20
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.03 0.00 01-JAN-00:10 390.75 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.03 0.00 01-JAN-00:10 390.75 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 22.36 0.00 01-JAN-08:00 2642.63 30-SEP-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 22.36 0.00 01-JAN-08:00 2642.63 30-SEP-15:20
EnergyTransfer:Zone:ROOM_2_FLR_6 19.39 0.00 01-JAN-08:00 2590.97 28-JUL-15:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.05 0.00 01-JAN-00:10 440.87 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.05 0.00 01-JAN-00:10 440.87 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 19.34 0.00 01-JAN-08:00 2590.97 28-JUL-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 19.34 0.00 01-JAN-08:00 2590.97 28-JUL-15:20
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 132.39 0.00 01-JAN-08:00 11940.86 25-OCT-15:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.02 0.00 01-JAN-00:10 730.00 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.02 0.00 01-JAN-00:10 730.00 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 132.37 0.00 01-JAN-08:00 11940.86 25-OCT-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 132.37 0.00 01-JAN-08:00 11940.86 25-OCT-15:20
EnergyTransfer:Zone:BANQUET_FLR_6 533.11 10185.89 16-MAR-08:20 22032.64 28-JUL-22:00
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 533.11 10185.89 16-MAR-08:20 22032.64 28-JUL-22:00
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 533.11 10185.89 16-MAR-08:20 22032.64 28-JUL-22:00
EnergyTransfer:Zone:DINING_FLR_6 551.00 11730.95 16-MAR-09:20 23347.81 28-JUL-22:00
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 551.00 11730.95 16-MAR-09:20 23347.81 28-JUL-22:00
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 551.00 11730.95 16-MAR-09:20 23347.81 28-JUL-22:00
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 629.39 6793.96 04-FEB-04:00 29417.49 23-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 629.39 6793.96 04-FEB-04:00 29417.49 23-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 103.68 1267.73 04-FEB-07:50 6928.76 29-JUL-16:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 103.68 1267.73 04-FEB-07:50 6928.76 29-JUL-16:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 103.68 1267.73 04-FEB-07:50 6928.76 29-JUL-16:10
PlantLoopHeatingDemand:Facility 536.98 6417.29 21-JUL-01:20 40666.73 31-JAN-07:20
PlantLoopHeatingDemand:Plant 535.81 6417.29 21-JUL-01:20 39090.99 18-JAN-08:00
WaterSystems:PlantLoopHeatingDemand 535.81 6417.29 21-JUL-01:20 39090.99 18-JAN-08:00
General:WaterSystems:PlantLoopHeatingDemand 535.81 6417.29 21-JUL-01:20 39090.99 18-JAN-08:00
EnergyTransfer:HVAC 12285.20 7615.02 15-DEC-08:30 804080.67 18-SEP-18:10
HeatingCoils:EnergyTransfer 1.17 0.00 01-JAN-00:10 10820.84 16-MAR-08:20
PlantLoopHeatingDemand:HVAC 1.17 0.00 01-JAN-00:10 10820.84 16-MAR-08:20
HeatingCoils:PlantLoopHeatingDemand 1.17 0.00 01-JAN-00:10 10820.84 16-MAR-08:20
CoolingCoils:EnergyTransfer 10186.07 1307.46 16-MAR-07:20 616514.73 18-SEP-18:10
HeatRecoveryForHeating:EnergyTransfer 14.46 0.00 01-JAN-00:10 89092.26 04-FEB-06:10
HeatRecoveryForCooling:EnergyTransfer 2083.50 0.00 01-JAN-00:10 196330.01 31-JUL-24:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 535.81 6417.29 21-JUL-01:20 39090.99 18-JAN-08:00
WaterUse:WaterSystems:EnergyTransfer 535.81 6417.29 21-JUL-01:20 39090.99 18-JAN-08:00
Boilers:EnergyTransfer 1.15 0.00 01-JAN-00:10 13247.80 16-MAR-08:20
Chillers:EnergyTransfer 10276.45 4623.86 16-MAR-07:20 618977.84 18-SEP-18:10
HeatRejection:EnergyTransfer 13285.26 6037.14 16-MAR-07:20 795721.32 18-SEP-18:10
General:HeatRejection:EnergyTransfer 13285.26 6037.14 16-MAR-07:20 795721.32 18-SEP-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -458.473 0.000 0.000 135.120 92.464 143.105 0.000 0.000 0.000 87.785 0.000 0.000 0.000 0.000 0.000
RETAIL_1_FLR_1 0.000 0.000 0.000 -53.938 0.000 0.000 13.825 4.184 10.186 16.558 0.000 0.746 10.497 0.000 -1.562 0.000 -0.495 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -46.469 0.000 0.000 16.200 4.846 11.795 0.000 0.000 0.325 13.484 0.000 0.000 0.000 -0.181 0.000
MECH_FLR_1 0.000 0.000 0.000 -34.181 0.000 0.000 3.340 8.670 12.471 0.000 0.000 0.674 9.538 0.000 0.000 0.000 -0.512 -0.000
STORAGE_FLR_1 0.000 0.000 0.000 -26.730 0.000 0.000 2.715 1.987 3.598 0.000 0.000 0.472 18.157 0.000 0.000 0.000 -0.199 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -583.669 0.000 0.000 10.552 3.699 658.131 0.000 0.000 0.920 0.000 0.000 0.000 0.000 -0.720 -88.912
CAFE_FLR_1 0.000 0.000 0.000 -297.961 0.000 0.000 191.387 6.680 14.341 48.640 0.000 2.330 38.719 0.000 -3.246 0.000 -0.890 -0.000
LOBBY_FLR_1 0.000 0.000 0.000 -935.199 0.000 0.000 546.095 78.743 148.998 62.787 0.000 5.562 101.024 0.000 -4.970 0.000 -3.040 -0.000
ROOM_1_FLR_3 0.054 -76.779 0.000 -14.010 0.000 0.000 9.607 4.922 10.478 38.362 0.000 3.275 27.378 0.000 -2.184 0.000 -1.103 -0.000
ROOM_2_FLR_3 0.091 -63.684 0.000 -14.537 0.000 0.000 9.481 4.922 10.477 31.596 0.000 2.943 22.568 0.000 -2.364 0.000 -1.493 -0.001
ROOM_3_MULT19_FLR_3 0.000 -447.509 0.000 -18.385 0.000 0.000 0.000 58.777 194.997 184.522 0.000 3.265 70.470 0.000 -32.473 0.000 -13.662 0.000
ROOM_4_MULT19_FLR_3 0.271 -444.705 0.000 -195.219 0.000 0.000 180.956 58.793 195.050 115.042 0.000 16.921 98.764 0.000 -11.307 0.000 -14.566 -0.010
ROOM_5_FLR_3 0.046 -77.666 0.000 -14.014 0.000 0.000 9.603 4.922 10.478 39.369 0.000 3.268 27.229 0.000 -2.115 0.000 -1.119 0.000
ROOM_6_FLR_3 0.085 -64.442 0.000 -14.546 0.000 0.000 9.480 4.922 10.477 32.529 0.000 2.931 22.292 0.000 -2.241 0.000 -1.486 -0.001
CORRIDOR_FLR_3 0.000 0.000 0.000 -225.547 0.000 0.000 110.086 54.592 0.000 35.390 0.000 2.399 27.721 0.000 -3.429 0.000 -1.213 0.000
ROOM_1_FLR_6 0.086 -18.907 0.000 -3.505 0.000 0.000 2.403 1.231 2.620 9.551 0.000 0.824 6.494 0.000 -0.508 0.000 -0.289 -0.000
ROOM_2_FLR_6 0.128 -15.776 0.000 -3.634 0.000 0.000 2.371 1.230 2.619 7.874 0.000 0.734 5.418 0.000 -0.562 0.000 -0.402 -0.000
ROOM_3_MULT9_FLR_6 0.074 -109.879 0.000 -22.542 0.000 0.000 21.608 6.962 23.098 46.298 0.000 4.144 34.368 0.000 -2.290 0.000 -1.841 -0.000
BANQUET_FLR_6 0.000 0.000 0.000 -533.112 0.000 0.000 332.496 14.593 175.857 13.110 0.000 1.430 0.001 0.000 -1.372 0.000 -0.620 -2.383
DINING_FLR_6 0.000 0.000 0.000 -551.004 0.000 0.000 328.564 14.593 175.857 12.784 0.000 1.353 20.008 0.000 -1.501 0.000 -0.655 -0.000
KITCHEN_FLR_6 0.000 0.000 0.000 -629.386 0.000 0.000 27.946 9.139 540.650 26.525 0.000 0.911 25.786 0.000 -0.820 0.000 -0.751 -0.001
CORRIDOR_FLR_6 0.000 0.000 0.000 -103.677 0.000 0.000 28.138 14.444 0.000 16.081 0.000 0.891 46.631 0.000 -1.843 0.000 -0.665 0.000
Total Facility 0.836 -1319.348 0.000 -4779.738 0.000 0.000 1991.971 455.315 2355.282 737.018 0.000 56.317 714.333 0.000 -74.787 0.000 -45.903 -91.310


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 22-SEP-21:00 0.00 0.00 0.00 -21793.62 0.00 0.00 5924.40 6721.38 9125.55 0.00 0.00 0.00 22.29 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 09-DEC-12:30 0.00 0.00 0.00 -3520.92 0.00 0.00 225.91 95.05 252.59 3724.64 0.00 37.29 0.00 0.00 -0.00 0.00 0.00 -814.57
RETAIL_2_FLR_1 28-JUL-20:10 0.00 0.00 0.00 -2492.47 0.00 0.00 697.61 352.23 752.15 0.00 0.00 19.98 670.50 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 28-JUL-20:00 0.00 0.00 0.00 -2822.66 0.00 0.00 129.08 708.98 839.45 0.00 0.00 45.30 1099.84 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 29-JUL-19:00 0.00 0.00 0.00 -1296.19 0.00 0.00 85.11 126.40 203.92 0.00 0.00 49.26 831.50 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 28-JUL-20:00 0.00 0.00 0.00 -37391.85 0.00 0.00 408.88 302.47 44299.38 0.00 0.00 61.86 0.00 0.00 -0.00 0.00 0.00 -7680.74
CAFE_FLR_1 09-DEC-11:35 0.00 0.00 0.00 -12559.17 0.00 0.00 3033.20 49.52 355.63 9644.35 0.00 95.28 0.00 0.00 -0.00 0.00 0.00 -618.82
LOBBY_FLR_1 28-JUL-21:10 0.00 0.00 0.00 -42333.72 0.00 0.00 26439.98 4544.88 7389.94 314.61 0.00 386.73 3257.58 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_3 15-MAR-15:11 0.00 -10368.31 0.00 -606.53 0.00 0.00 235.28 106.08 200.18 6085.93 0.00 0.00 5089.01 0.00 -0.00 0.00 -741.66 0.00
ROOM_2_FLR_3 20-DEC-16:11 0.00 -10388.15 0.00 -528.97 0.00 0.00 235.28 106.07 200.16 3164.99 0.00 0.00 7430.34 0.00 -0.00 0.00 -219.73 0.00
ROOM_3_MULT19_FLR_3 03-DEC-14:05 0.00 -36909.35 0.00 0.00 0.00 0.00 0.00 1492.91 2548.95 39956.37 0.00 0.00 0.00 0.00 -0.00 0.00 -334.50 -6754.37
ROOM_4_MULT19_FLR_3 14-MAR-18:01 0.00 -66503.55 0.00 -10387.00 0.00 0.00 6374.47 4027.42 9021.83 754.97 0.00 171.44 56540.41 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 16-MAR-15:11 0.00 -9371.93 0.00 -650.88 0.00 0.00 235.28 106.08 200.18 1650.81 0.00 0.00 8373.15 0.00 -0.00 0.00 -542.71 0.00
ROOM_6_FLR_3 20-APR-08:51 0.00 -9354.49 0.00 -846.74 0.00 0.00 80.46 166.68 452.99 3749.92 0.00 10.95 5740.23 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 22-SEP-21:10 0.00 0.00 0.00 -9819.70 0.00 0.00 5246.15 2976.30 0.00 315.22 0.00 139.18 1142.84 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_6 15-MAR-15:11 0.00 -2843.25 0.00 -150.90 0.00 0.00 58.82 26.52 50.05 1506.86 0.00 0.00 1559.07 0.00 -0.00 0.00 -207.17 0.00
ROOM_2_FLR_6 18-APR-21:51 0.00 -2841.72 0.00 -186.72 0.00 0.00 98.33 63.45 89.55 0.00 0.00 0.00 2980.06 0.00 -157.26 0.00 -45.69 0.00
ROOM_3_MULT9_FLR_6 16-MAR-15:11 0.00 -11985.53 0.00 -1064.70 0.00 0.00 529.39 150.05 441.28 3738.09 0.00 0.00 9519.17 0.00 -0.00 0.00 -1327.75 0.00
BANQUET_FLR_6 28-JUL-22:00 0.00 0.00 0.00 -22032.94 0.00 0.00 15644.56 948.68 6747.90 175.85 0.00 78.57 0.00 0.00 -0.00 0.00 0.00 -1562.61
DINING_FLR_6 28-JUL-22:00 0.00 0.00 0.00 -23348.19 0.00 0.00 15644.41 948.68 6747.90 166.45 0.00 78.57 0.00 0.00 -0.00 0.00 0.00 -237.82
KITCHEN_FLR_6 23-JUL-10:50 0.00 0.00 0.00 -29410.93 0.00 0.00 464.27 249.14 23951.61 2521.32 0.00 126.01 2098.59 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 29-JUL-16:10 0.00 0.00 0.00 -6928.07 0.00 0.00 771.16 328.12 0.00 1137.71 0.00 158.31 4532.76 0.00 -0.00 0.00 0.00 0.00
Total Facility 29-JUL-18:02 0.00 -140240.44 0.00 -212525.49 0.00 0.00 65416.96 30153.81 113070.18 22876.47 0.00 6093.11 115155.40 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 31-JAN-09:03 2989.67 421.66 0.00 -421.66 0.00 0.00 94.21 166.70 453.05 1218.30 0.00 0.00 0.00 0.00 -0.00 0.00 -204.18 -4717.74
ROOM_2_FLR_3 24-JAN-19:04 3030.90 416.18 0.00 -416.18 0.00 0.00 340.51 337.15 484.60 0.00 0.00 0.00 0.00 0.00 -792.03 0.00 -209.03 -3192.09
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 20-DEC-16:14 18751.01 5653.90 0.00 -5653.90 0.00 0.00 4755.82 1267.05 3726.41 0.00 0.00 0.00 0.00 0.00 -887.02 0.00 -942.11 -26671.16
ROOM_5_FLR_3 03-FEB-16:14 2917.32 437.45 0.00 -437.45 0.00 0.00 241.69 106.08 200.18 904.97 0.00 0.00 0.00 0.00 -0.00 0.00 -696.96 -3673.28
ROOM_6_FLR_3 20-DEC-19:03 2924.04 418.33 0.00 -418.33 0.00 0.00 362.19 337.15 484.60 0.00 0.00 0.00 0.00 0.00 -770.87 0.00 -242.18 -3094.92
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 24-JAN-19:04 911.25 105.86 0.00 -105.86 0.00 0.00 83.87 84.30 121.16 0.00 0.00 0.00 0.00 0.00 -204.89 0.00 -53.36 -942.33
ROOM_2_FLR_6 03-FEB-19:03 926.96 105.68 0.00 -105.68 0.00 0.00 89.48 84.29 121.15 0.00 0.00 0.00 0.00 0.00 -175.84 0.00 -58.47 -987.56
ROOM_3_MULT9_FLR_6 20-MAR-08:03 3642.20 682.91 0.00 -682.91 0.00 0.00 215.90 235.79 998.70 675.77 0.00 0.00 0.00 0.00 -0.00 0.00 -329.25 -5439.10
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 21-DEC-09:04 -123217.22 122712.32 0.00 -122712.32 0.00 0.00 23165.04 15463.40 87870.62 74198.62 0.00 0.00 0.00 0.00 0.00 0.00 -5024.65 -72455.82



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 20.7663 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 20.5830 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 12.9264 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.5306 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.003540 12.5400 0.000610 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.003540 142.3000 0.000914 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.000963 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5514 2.5514 1.2808 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2812 0.2812 0.1190 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2529 0.2529 0.1376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2877 0.2877 0.0029 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1371 0.1371 0.0866 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1858 3.1858 0.0319 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2380 1.2380 1.0152 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.4396 4.4396 2.8413 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1892 1.1892 0.7123 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1388 2.1388 1.7816 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2416 2.2416 1.7821 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1357 2.1357 0.5510 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6873 0.6873 0.1883 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 20.7663 20.5830 20.7663 10.5306 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2808 1.2808 1.2808 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1406 0.1406 0.1190 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1376 0.1376 0.1376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1439 0.1439 0.0029 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0866 0.0866 0.0866 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5929 1.5929 0.0319 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0152 1.0152 1.0152 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8413 2.8413 2.8413 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7123 0.7123 0.7123 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7816 1.7816 1.7816 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7821 1.7821 1.7821 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0679 1.0679 0.5510 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3437 0.3437 0.1883 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 12.9264 10.5306 10.5306 10.5306 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 114.33
Number of hours not met 114.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1.88 22051.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3008.81 181382.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 455.32 37630.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 150.61 9571.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 21.47 1270.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 366.65 22430.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.45 157.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 607.81 39239.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 112.38 4528.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 241.61 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.76 2148.53 185853.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.90 1306.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 21.54 717.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1692.99 6750.83
Natural Gas 1788.84 3939.24
Additional 0.00 0.00
Total 3481.82 10690.08


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 217.61
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 40.13
Space Heating 0.00
Space Cooling 265.20
Fans (All) 53.57
Service Water Heating 8.00
Receptacle Equipment 145.30
Miscellaneous (All) 595.03
Subtotal 595.03


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.17
Service Water Heating 189.38
Miscellaneous (All) 347.21
Subtotal 347.21


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 4.26
Space Heating 0.02
Space Cooling 28.15
Fans (All) 5.69
Service Water Heating 20.95
Receptacle Equipment 32.15
Miscellaneous 8.79


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
PV_SCH 8760. 8760.
LTG_SCH_KITCHEN 2022. 8760.
LTG_SCH_DINING 1877. 8760.
LTG_SCH_BASEMENT 2095. 8760.
LTG_SCH_LOBBY 2166. 8760.
LTG_SCH_STORAGE 1543. 8760.
LTG_SCH_MECHANIC 2022. 8760.
LTG_SCH_LAUNDRY 2527. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2166. 8760.
LTG_SCH_RETAIL 2296. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 4394.50 4365.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8759.17 0.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 4394.50 0.00 0.00 0.00 0.00
Max 8760.00 4365.50 0.00 0.00 0.00
Average 8561.53 198.47 0.00 0.00 0.00
Sum 188353.67 4366.33 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4153.83 0.17 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.17 0.00 0.00 0.00
Average 288887.04 0.01 0.00 0.00 0.00
Sum 6355514.83 0.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8755.17 4.83 0.00 0.00 0.00
RETAIL_1_FLR_1 7989.50 770.50 0.00 0.00 0.00
RETAIL_2_FLR_1 8284.17 475.83 0.00 0.00 0.00
MECH_FLR_1 8628.67 131.33 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 7376.17 1383.83 0.00 0.00 0.00
LOBBY_FLR_1 6238.33 2521.67 0.00 0.00 0.00
ROOM_1_FLR_3 8746.17 13.83 0.00 0.00 0.00
ROOM_2_FLR_3 8502.50 257.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 3286.50 5473.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8592.67 167.33 0.00 0.00 0.00
ROOM_5_FLR_3 8747.00 13.00 0.00 0.00 0.00
ROOM_6_FLR_3 8456.50 303.50 0.00 0.00 0.00
CORRIDOR_FLR_3 7947.17 812.83 0.00 0.00 0.00
ROOM_1_FLR_6 8720.83 39.17 0.00 0.00 0.00
ROOM_2_FLR_6 8385.67 374.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8729.17 30.83 0.00 0.00 0.00
BANQUET_FLR_6 6858.67 1901.33 0.00 0.00 0.00
DINING_FLR_6 6587.67 2172.33 0.00 0.00 0.00
KITCHEN_FLR_6 7792.17 967.83 0.00 0.00 0.00
CORRIDOR_FLR_6 8035.83 724.17 0.00 0.00 0.00
Min 3286.50 0.00 0.00 0.00 0.00
Max 8760.00 5473.50 0.00 0.00 0.00
Average 7917.30 842.70 0.00 0.00 0.00
Sum 174180.50 18539.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 528871.83 459.17 0.00 0.00 0.00
RETAIL_1_FLR_1 43528.00 6651.00 0.00 0.00 0.00
RETAIL_2_FLR_1 53986.83 5169.17 0.00 0.00 0.00
MECH_FLR_1 8863.83 113.17 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 533728.83 176688.17 0.00 0.00 0.00
LOBBY_FLR_1 1213022.83 902406.17 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4075.83 78.17 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4102.83 51.17 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4080.17 73.83 0.00 0.00 0.00
CORRIDOR_FLR_3 86425.00 13933.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4008.33 145.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 825120.50 420594.50 0.00 0.00 0.00
DINING_FLR_6 771295.67 474419.33 0.00 0.00 0.00
KITCHEN_FLR_6 99994.00 8275.00 0.00 0.00 0.00
CORRIDOR_FLR_6 93747.17 12198.83 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1213022.83 902406.17 0.00 0.00 0.00
Average 197011.76 91875.29 0.00 0.00 0.00
Sum 4334258.67 2021256.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:55:16

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.368230E+11 19494.96 03-JAN-22:00 22.20 20.64 0.813709E+10 4837.15 25-JAN-23:10 12.20 8.81
February 0.323589E+11 17395.63 17-FEB-22:00 23.90 20.81 0.728215E+10 4837.10 22-FEB-23:10 18.30 15.01
March 0.348019E+11 15874.47 30-MAR-18:10 24.82 19.47 0.794160E+10 4837.09 28-MAR-21:10 24.82 19.47
April 0.344528E+11 16353.21 15-APR-18:10 29.82 21.94 0.770297E+10 4837.09 17-APR-22:10 22.70 17.05
May 0.368662E+11 16837.19 19-MAY-21:00 26.10 22.26 0.807641E+10 4837.09 24-MAY-21:10 24.40 22.88
June 0.368930E+11 18038.01 30-JUN-21:00 27.80 24.57 0.790836E+10 4837.09 21-JUN-21:10 27.80 24.57
July 0.404847E+11 19405.76 28-JUL-21:00 29.40 24.13 0.818108E+10 4837.09 14-JUL-22:10 29.40 24.13
August 0.416527E+11 20816.92 18-AUG-18:05 29.82 24.85 0.823288E+10 4837.07 31-AUG-21:30 27.70 24.63
September 0.421719E+11 21792.44 22-SEP-21:00 28.30 25.04 0.795627E+10 4837.08 05-SEP-22:10 28.30 25.04
October 0.433551E+11 21570.90 25-OCT-21:00 26.70 20.95 0.821813E+10 4837.08 27-OCT-22:10 23.80 21.85
November 0.399506E+11 21455.64 22-NOV-22:00 26.70 23.11 0.793776E+10 4837.09 15-NOV-00:20 26.70 23.11
December 0.386602E+11 20769.33 08-DEC-22:00 23.90 22.40 0.816667E+10 4837.11 14-DEC-01:10 15.68 14.80
                     
Annual Sum or Average 0.458471E+12         0.957414E+11        
Minimum of Months 0.323589E+11 15874.47   22.20 19.47 0.728215E+10 4837.07   12.20 8.81
Maximum of Months 0.433551E+11 21792.44   29.82 25.04 0.823288E+10 4837.15   29.40 25.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.367761E+10 3287.70 02-JAN-14:30 28.90 24.11 0.781868E+09 491.84 27-JAN-23:10 19.32 15.37
February 0.349908E+10 3263.88 11-FEB-14:30 28.85 24.07 0.717363E+09 491.84 22-FEB-23:10 18.30 15.01
March 0.383603E+10 2491.05 27-MAR-19:10 25.40 21.31 0.807271E+09 491.84 17-MAR-22:10 25.40 21.31
April 0.410973E+10 2783.44 15-APR-18:03 29.82 21.94 0.797152E+09 491.84 20-APR-22:10 22.20 16.88
May 0.454288E+10 2695.67 19-MAY-18:20 27.93 21.91 0.834442E+09 491.84 24-MAY-21:10 24.40 22.88
June 0.472122E+10 2890.68 29-JUN-18:15 30.00 24.84 0.812490E+09 491.84 21-JUN-21:10 30.00 24.84
July 0.531806E+10 3168.96 29-JUL-18:03 33.12 24.14 0.836769E+09 491.84 14-JUL-22:10 33.12 24.14
August 0.506916E+10 3048.77 31-AUG-18:15 29.03 24.52 0.837003E+09 491.82 30-AUG-21:30 29.03 24.52
September 0.535697E+10 3356.01 30-SEP-14:00 31.10 24.59 0.810272E+09 491.84 05-SEP-22:10 31.10 24.59
October 0.533440E+10 3504.84 25-OCT-14:30 30.00 22.37 0.834665E+09 491.84 27-OCT-22:10 23.80 21.85
November 0.448564E+10 3508.42 07-NOV-14:00 28.30 20.78 0.790879E+09 491.84 14-NOV-23:10 18.30 14.06
December 0.398693E+10 3521.30 09-DEC-12:30 27.20 22.50 0.789559E+09 491.84 11-DEC-23:10 17.62 13.99
                     
Annual Sum or Average 0.539377E+11         0.964973E+10        
Minimum of Months 0.349908E+10 2491.05   25.40 20.78 0.717363E+09 491.82   17.62 13.99
Maximum of Months 0.535697E+10 3521.30   33.12 24.84 0.837003E+09 491.84   33.12 24.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.340324E+10 1690.28 03-JAN-22:00 22.20 20.64 0.882171E+09 569.55 02-JAN-23:10 22.20 20.64
February 0.317016E+10 1726.30 11-FEB-21:20 22.03 20.10 0.810794E+09 569.55 22-FEB-23:10 18.30 15.01
March 0.361086E+10 2028.60 28-MAR-20:25 24.15 20.90 0.913608E+09 569.55 31-MAR-22:10 23.05 18.37
April 0.379447E+10 2308.94 13-APR-20:10 25.60 23.16 0.906509E+09 569.55 18-APR-22:10 17.62 12.99
May 0.413168E+10 2380.68 17-MAY-20:10 26.60 22.77 0.950335E+09 569.55 24-MAY-21:10 24.40 22.88
June 0.413321E+10 2481.33 09-JUN-20:30 29.40 24.96 0.928384E+09 569.55 21-JUN-21:10 24.50 22.87
July 0.447617E+10 2492.24 28-JUL-20:10 28.48 23.99 0.960023E+09 569.55 14-JUL-22:10 28.48 23.99
August 0.428680E+10 2478.49 17-AUG-20:10 28.22 24.59 0.957885E+09 569.53 30-AUG-21:30 27.25 23.62
September 0.418628E+10 2418.91 01-SEP-20:10 28.90 23.48 0.928186E+09 569.55 05-SEP-22:10 23.90 22.74
October 0.410213E+10 2327.94 06-OCT-20:10 26.70 23.40 0.951898E+09 569.55 27-OCT-22:10 23.80 21.85
November 0.365521E+10 2019.81 07-NOV-21:10 24.90 21.64 0.897182E+09 569.55 01-NOV-22:10 24.90 21.64
December 0.351829E+10 1914.74 08-DEC-21:10 24.32 22.14 0.896349E+09 569.55 01-DEC-23:10 24.32 22.14
                     
Annual Sum or Average 0.464685E+11         0.109833E+11        
Minimum of Months 0.317016E+10 1690.28   22.03 20.10 0.810794E+09 569.53   17.62 12.99
Maximum of Months 0.447617E+10 2492.24   29.40 24.96 0.960023E+09 569.55   28.48 23.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.853787E+09 1385.02 03-JAN-21:00 22.80 20.45 0.202401E+09 120.45 27-JAN-22:10 19.40 15.40
February 0.111764E+10 1531.75 17-FEB-21:00 23.90 20.81 0.183421E+09 120.45 21-FEB-22:10 18.03 14.22
March 0.148984E+10 1588.79 28-MAR-20:00 23.90 20.81 0.204185E+09 120.45 30-MAR-21:30 23.90 19.98
April 0.234585E+10 2080.89 14-APR-20:00 26.10 23.27 0.198744E+09 120.45 17-APR-21:30 23.05 17.57
May 0.369394E+10 2479.42 22-MAY-20:00 28.30 22.83 0.205440E+09 120.45 22-MAY-21:30 27.50 22.45
June 0.442964E+10 2774.62 29-JUN-20:00 28.90 25.14 0.199176E+09 120.45 14-JUN-21:30 28.90 25.14
July 0.489858E+10 2822.58 28-JUL-20:00 28.30 23.96 0.205006E+09 120.45 06-JUL-21:30 28.30 23.96
August 0.415770E+10 2611.19 18-AUG-20:00 28.90 24.83 0.205873E+09 120.45 30-AUG-21:30 27.25 23.62
September 0.415423E+10 2582.51 22-SEP-20:00 28.30 25.04 0.198646E+09 120.45 13-SEP-21:30 28.30 25.04
October 0.341145E+10 2242.42 03-OCT-20:00 27.80 25.31 0.205103E+09 120.45 19-OCT-21:30 24.15 19.34
November 0.231340E+10 1944.62 03-NOV-20:00 26.10 24.52 0.198107E+09 120.45 15-NOV-00:10 18.22 15.24
December 0.131449E+10 1664.77 01-DEC-20:50 21.97 19.19 0.202999E+09 120.45 04-DEC-00:00 18.30 15.62
                     
Annual Sum or Average 0.341805E+11         0.240910E+10        
Minimum of Months 0.853787E+09 1385.02   21.97 19.19 0.183421E+09 120.45   18.03 14.22
Maximum of Months 0.489858E+10 2822.58   28.90 25.31 0.205873E+09 120.45   28.90 25.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.193130E+10 960.95 01-JAN-11:35 26.30 21.34 0.131916E+09 85.01 03-JAN-22:30 21.95 20.39
February 0.179953E+10 989.56 11-FEB-19:10 23.40 21.47 0.121488E+09 86.23 17-FEB-22:30 23.90 20.81
March 0.203653E+10 997.10 30-MAR-18:10 24.82 19.47 0.136441E+09 86.48 30-MAR-21:49 23.90 20.07
April 0.214643E+10 1085.70 15-APR-17:50 30.28 22.14 0.138157E+09 90.19 14-APR-21:49 30.28 22.14
May 0.238806E+10 1123.39 22-MAY-18:10 30.40 23.74 0.149991E+09 92.66 22-MAY-21:49 27.30 22.27
June 0.244873E+10 1232.45 29-JUN-20:10 28.90 25.09 0.150016E+09 92.66 14-JUN-21:30 28.90 25.09
July 0.260747E+10 1296.17 29-JUL-19:00 32.20 24.21 0.155740E+09 92.66 06-JUL-21:30 32.20 24.21
August 0.247234E+10 1155.45 19-AUG-18:00 29.40 24.14 0.153197E+09 92.66 16-AUG-21:30 29.40 24.14
September 0.240716E+10 1141.52 09-SEP-18:00 30.00 25.17 0.148554E+09 92.66 18-SEP-21:30 28.30 25.27
October 0.236112E+10 1090.28 07-OCT-10:35 31.13 24.14 0.148796E+09 91.85 03-OCT-21:00 31.13 24.14
November 0.212451E+10 1029.66 04-NOV-18:00 26.70 24.69 0.137905E+09 89.58 03-NOV-22:10 26.70 24.69
December 0.200680E+10 1024.87 09-DEC-11:35 27.20 22.50 0.135055E+09 87.60 01-DEC-22:10 27.20 22.50
                     
Annual Sum or Average 0.267300E+11         0.170726E+10        
Minimum of Months 0.179953E+10 960.95   23.40 19.47 0.121488E+09 85.01   21.95 20.07
Maximum of Months 0.260747E+10 1296.17   32.20 25.17 0.155740E+09 92.66   32.20 25.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.463082E+11 35156.93 02-JAN-21:00 22.20 19.62 0.649331E+09 381.99 10-JAN-22:10 17.62 14.98
February 0.425232E+11 35087.16 17-FEB-21:00 23.90 20.81 0.587069E+09 381.59 28-FEB-22:10 19.42 14.35
March 0.479398E+11 35817.64 27-MAR-20:00 24.40 20.99 0.652382E+09 381.59 03-MAR-22:10 24.40 20.99
April 0.479497E+11 36566.54 14-APR-20:00 26.10 23.27 0.629491E+09 381.61 25-APR-21:10 22.88 20.54
May 0.509184E+11 36778.23 31-MAY-20:00 27.80 24.12 0.650695E+09 381.59 01-MAY-21:30 27.80 24.12
June 0.503918E+11 37061.50 09-JUN-20:00 29.40 24.96 0.630851E+09 381.58 01-JUN-21:30 29.40 24.96
July 0.524432E+11 37391.52 28-JUL-20:00 28.30 23.96 0.649316E+09 381.58 06-JUL-21:30 28.30 23.96
August 0.512639E+11 36961.49 31-AUG-20:00 27.80 24.58 0.652062E+09 381.58 30-AUG-21:30 27.80 24.58
September 0.500039E+11 36886.46 08-SEP-20:00 30.60 24.86 0.629173E+09 381.58 13-SEP-21:30 26.40 23.20
October 0.502833E+11 36548.47 06-OCT-20:00 26.70 23.40 0.649625E+09 381.58 05-OCT-21:30 26.70 23.40
November 0.470893E+11 35810.74 03-NOV-20:00 26.10 24.52 0.628112E+09 381.57 15-NOV-00:10 18.22 15.24
December 0.465451E+11 35430.48 08-DEC-21:00 24.40 22.09 0.649328E+09 381.58 20-DEC-22:10 10.50 8.09
                     
Annual Sum or Average 0.583660E+12         0.765743E+10        
Minimum of Months 0.425232E+11 35087.16   22.20 19.62 0.587069E+09 381.57   10.50 8.09
Maximum of Months 0.524432E+11 37391.52   30.60 24.96 0.652382E+09 381.99   29.40 24.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.238277E+11 11719.58 02-JAN-11:35 26.83 20.59 0.964336E+10 6460.47 13-JAN-23:10 23.90 21.21
February 0.217693E+11 11655.89 11-FEB-11:35 27.60 23.74 0.876286E+10 6362.32 22-FEB-22:40 18.67 14.87
March 0.238624E+11 11498.79 04-MAR-11:35 27.03 22.82 0.973191E+10 6387.74 27-MAR-21:40 24.60 21.74
April 0.238550E+11 11843.77 15-APR-17:30 30.85 22.41 0.947183E+10 6450.68 14-APR-21:40 30.85 22.41
May 0.252228E+11 11783.05 22-MAY-18:10 30.40 23.74 0.990557E+10 6457.28 22-MAY-22:10 26.93 22.26
June 0.250814E+11 11941.76 29-JUN-18:10 30.00 24.76 0.974670E+10 6460.36 02-JUN-22:10 30.00 24.76
July 0.264826E+11 12423.34 29-JUL-17:20 34.03 24.14 0.100917E+11 6460.65 28-JUL-22:30 34.03 24.14
August 0.260811E+11 12215.41 31-AUG-18:10 29.22 24.58 0.101355E+11 6460.61 31-AUG-22:30 27.45 24.55
September 0.261161E+11 12409.20 30-SEP-17:15 30.20 24.16 0.993722E+10 6460.68 08-SEP-22:30 30.20 24.16
October 0.267437E+11 12442.77 25-OCT-15:10 29.22 22.14 0.102458E+11 6461.32 25-OCT-21:19 26.50 21.25
November 0.247345E+11 12316.86 07-NOV-11:35 27.03 21.34 0.968113E+10 6462.60 10-NOV-23:10 22.52 20.48
December 0.241809E+11 12556.38 09-DEC-11:35 27.20 22.50 0.972821E+10 6462.59 08-DEC-23:10 27.20 22.50
                     
Annual Sum or Average 0.297958E+12         0.117082E+12        
Minimum of Months 0.217693E+11 11498.79   26.83 20.59 0.876286E+10 6362.32   18.67 14.87
Maximum of Months 0.267437E+11 12556.38   34.03 24.76 0.102458E+11 6462.60   34.03 24.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.719107E+11 34904.64 03-JAN-22:10 22.12 20.55 0.303274E+11 19186.03 02-JAN-23:10 22.12 20.55
February 0.659782E+11 34372.53 11-FEB-19:10 23.40 21.47 0.276190E+11 19186.14 22-FEB-23:10 18.30 15.01
March 0.735133E+11 34836.12 30-MAR-21:10 23.90 19.88 0.307568E+11 19186.18 31-MAR-22:10 23.05 18.37
April 0.746093E+11 37895.20 14-APR-21:10 25.50 22.67 0.302160E+11 19186.27 20-APR-22:10 22.20 16.88
May 0.809569E+11 39142.56 22-MAY-21:10 27.70 22.63 0.317095E+11 19186.11 24-MAY-21:10 24.40 22.88
June 0.819047E+11 41452.50 29-JUN-21:10 28.90 24.82 0.309939E+11 19186.10 21-JUN-21:10 28.90 24.82
July 0.866386E+11 42328.33 28-JUL-21:10 29.32 24.20 0.319931E+11 19186.15 14-JUL-22:10 29.32 24.20
August 0.842522E+11 41623.45 21-AUG-21:10 28.22 25.01 0.319949E+11 19183.87 30-AUG-21:30 27.25 23.62
September 0.831306E+11 42169.39 18-SEP-21:10 28.30 25.12 0.310255E+11 19186.08 05-SEP-22:10 28.30 25.12
October 0.828889E+11 40534.52 06-OCT-21:10 26.70 23.48 0.319389E+11 19186.00 27-OCT-22:10 23.80 21.85
November 0.757538E+11 38666.35 03-NOV-21:10 26.70 24.27 0.303982E+11 19186.03 21-NOV-22:40 24.40 22.66
December 0.736540E+11 37429.48 08-DEC-22:05 23.98 22.48 0.306582E+11 19186.10 01-DEC-23:10 23.98 22.48
                     
Annual Sum or Average 0.935191E+12         0.369631E+12        
Minimum of Months 0.659782E+11 34372.53   22.12 19.88 0.276190E+11 19183.87   18.30 15.01
Maximum of Months 0.866386E+11 42328.33   29.32 25.12 0.319949E+11 19186.27   29.32 25.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124249E+10 2729.56 25-JAN-16:11 17.80 8.74 99024543.45 56.69 03-JAN-00:49 17.80 8.74
February 0.132114E+10 2701.69 03-FEB-16:11 16.13 8.51 89558668.92 56.69 23-FEB-00:00 16.70 15.34
March 0.164093E+10 2743.79 15-MAR-15:11 17.40 8.95 99333565.82 56.69 26-MAR-01:39 22.97 20.91
April 0.193387E+10 2580.08 01-APR-18:02 26.93 23.20 96260931.78 56.69 22-APR-00:30 22.80 20.19
May 0.213233E+10 2591.25 29-MAY-15:12 32.97 24.38 99588191.64 56.69 02-MAY-01:49 32.97 24.38
June 0.215328E+10 2597.41 30-JUN-15:12 30.00 25.01 96424973.28 56.70 07-JUN-21:19 30.00 25.01
July 0.240966E+10 2589.98 25-JUL-18:02 29.90 24.64 99556777.97 56.69 07-JUL-22:49 29.90 24.64
August 0.229019E+10 2591.63 17-AUG-18:02 29.82 24.66 99646180.57 56.70 20-AUG-23:40 27.97 24.58
September 0.225385E+10 2582.95 01-SEP-18:02 29.90 23.26 96357322.69 56.70 01-SEP-23:10 27.80 23.87
October 0.220977E+10 2591.69 06-OCT-18:02 27.62 23.75 99568527.16 56.70 03-OCT-22:10 27.62 23.75
November 0.171950E+10 2583.51 03-NOV-15:12 28.30 24.37 96234761.17 56.69 21-NOV-03:00 25.60 21.37
December 0.138442E+10 2729.17 20-DEC-16:11 14.80 7.30 99012886.47 56.69 04-DEC-01:19 14.80 7.30
                     
Annual Sum or Average 0.226914E+11         0.117057E+10        
Minimum of Months 0.124249E+10 2580.08   14.80 7.30 89558668.92 56.69   14.80 7.30
Maximum of Months 0.240966E+10 2743.79   32.97 25.01 99646180.57 56.70   32.97 25.01



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.728573E+09 2683.42 24-JAN-19:01 13.72 7.28 0.102926E+09 74.17 03-JAN-22:10 13.72 7.28
February 0.861708E+09 2604.72 19-FEB-16:12 27.03 21.82 94637464.49 75.04 16-FEB-22:10 27.03 21.82
March 0.121300E+10 2716.91 15-MAR-20:11 14.80 8.22 0.105399E+09 77.68 30-MAR-21:10 23.90 19.88
April 0.164039E+10 2664.16 18-APR-21:51 17.80 13.01 0.101647E+09 79.05 10-APR-21:10 17.80 13.01
May 0.209257E+10 2613.53 11-MAY-15:12 29.23 22.86 0.100801E+09 74.94 25-MAY-21:10 23.90 22.59
June 0.217000E+10 2619.88 13-JUN-18:11 25.37 22.49 96940563.61 68.44 21-JUN-20:00 24.40 22.75
July 0.240463E+10 2614.61 22-JUL-15:12 31.87 26.22 0.100401E+09 78.54 14-JUL-21:10 31.87 26.22
August 0.223215E+10 2608.59 16-AUG-15:12 31.30 25.60 99961060.53 57.34 06-AUG-21:19 31.30 25.60
September 0.208388E+10 2611.66 01-SEP-18:02 29.90 23.26 97174291.08 76.78 05-SEP-21:10 23.90 22.65
October 0.190240E+10 2623.44 06-OCT-15:12 29.23 23.77 0.100434E+09 71.51 27-OCT-21:19 23.90 21.88
November 0.132395E+10 2565.57 17-NOV-16:12 28.87 22.20 98715370.09 74.25 06-NOV-22:10 28.87 22.20
December 0.888615E+09 2729.35 20-DEC-16:11 14.80 7.30 0.102922E+09 74.33 01-DEC-22:10 14.80 7.30
                     
Annual Sum or Average 0.195419E+11         0.120196E+10        
Minimum of Months 0.728573E+09 2565.57   13.72 7.28 94637464.49 57.34   13.72 7.28
Maximum of Months 0.240463E+10 2729.35   31.87 26.22 0.105399E+09 79.05   31.87 26.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.500772E+09 473.51 02-JAN-14:30 28.90 24.11 0.00 0.00 01-JAN-00:10 28.90 24.11
February 0.438986E+09 403.12 11-FEB-14:30 28.85 24.07 0.00 0.00 01-FEB-00:10 28.85 24.07
March 0.435128E+09 345.11 02-MAR-14:30 25.00 17.17 0.00 0.00 01-MAR-00:10 25.00 17.17
April 0.429619E+09 292.73 15-APR-20:10 26.52 21.98 0.00 0.00 01-APR-00:10 26.52 21.98
May 0.454017E+09 283.23 14-MAY-08:00 27.20 23.57 0.00 0.00 01-MAY-00:10 27.20 23.57
June 0.477529E+09 294.79 29-JUN-20:30 28.90 24.98 0.00 0.00 01-JUN-00:10 28.90 24.98
July 0.529496E+09 314.22 29-JUL-19:10 31.55 24.08 0.00 0.00 01-JUL-00:10 31.55 24.08
August 0.527581E+09 315.72 31-AUG-20:20 27.80 24.58 0.00 0.00 01-AUG-00:10 27.80 24.58
September 0.595416E+09 382.37 30-SEP-14:00 31.10 24.59 0.00 0.00 01-SEP-00:10 31.10 24.59
October 0.652946E+09 445.78 25-OCT-14:20 30.20 22.48 0.00 0.00 01-OCT-00:10 30.20 22.48
November 0.572332E+09 477.56 07-NOV-14:00 28.30 20.78 0.00 0.00 01-NOV-00:10 28.30 20.78
December 0.516419E+09 485.65 03-DEC-14:05 24.40 18.40 0.00 0.00 01-DEC-00:10 24.40 18.40
                     
Annual Sum or Average 0.613024E+10         0.00        
Minimum of Months 0.429619E+09 283.23   24.40 17.17 0.00 0.00   24.40 17.17
Maximum of Months 0.652946E+09 485.65   31.55 24.98 0.00 0.00   31.55 24.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.448606E+09 990.63 24-JAN-19:01 13.72 7.28 0.101702E+09 72.00 03-JAN-22:10 13.72 7.28
February 0.459891E+09 997.37 03-FEB-19:02 13.03 7.08 93349210.53 73.48 16-FEB-22:10 23.30 20.32
March 0.575962E+09 1011.72 14-MAR-18:01 24.13 14.61 0.103290E+09 73.34 31-MAR-21:10 23.27 18.08
April 0.679067E+09 994.73 17-APR-18:02 30.03 18.67 0.100018E+09 74.09 25-APR-21:10 22.88 20.54
May 0.846958E+09 998.57 17-MAY-08:61 27.38 22.30 0.100348E+09 74.29 25-MAY-21:10 23.90 22.59
June 0.887231E+09 997.92 17-JUN-08:62 26.88 22.12 96592749.67 65.73 21-JUN-20:00 24.40 22.75
July 0.935697E+09 992.91 29-JUL-18:02 33.12 24.14 99997865.00 76.16 14-JUL-21:10 33.12 24.14
August 0.875372E+09 987.89 11-AUG-08:61 29.40 24.14 99587515.68 56.69 22-AUG-22:30 27.50 24.44
September 0.829652E+09 986.94 01-SEP-08:61 28.07 24.19 96730603.16 74.65 05-SEP-21:10 23.90 22.65
October 0.772519E+09 983.32 17-OCT-18:02 25.50 18.09 99857010.12 70.33 27-OCT-21:10 23.90 21.88
November 0.621486E+09 1001.38 15-NOV-19:01 24.22 19.69 97895665.00 71.20 21-NOV-22:10 24.40 22.53
December 0.485686E+09 977.57 20-DEC-19:02 12.62 6.43 0.101861E+09 71.69 01-DEC-22:10 12.62 6.43
                     
Annual Sum or Average 0.841813E+10         0.119123E+10        
Minimum of Months 0.448606E+09 977.57   12.62 6.43 93349210.53 56.69   12.62 6.43
Maximum of Months 0.935697E+09 1011.72   33.12 24.19 0.103290E+09 76.16   33.12 24.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.128594E+10 2484.51 25-JAN-16:11 17.80 8.74 99198468.77 56.69 18-JAN-22:10 17.80 8.74
February 0.132016E+10 2425.74 03-FEB-16:11 16.13 8.51 89725008.06 56.69 21-FEB-00:10 18.22 15.54
March 0.161306E+10 2505.76 16-MAR-15:11 18.67 9.29 99522016.48 56.69 30-MAR-01:00 22.80 19.79
April 0.191600E+10 2365.59 11-APR-15:12 28.70 22.52 96346091.91 56.70 17-APR-21:49 22.88 17.28
May 0.213610E+10 2374.53 20-MAY-08:62 27.88 22.09 99633455.52 56.69 07-MAY-03:20 27.88 22.09
June 0.226908E+10 2372.32 14-JUN-15:12 30.40 23.51 96465744.53 56.69 01-JUN-23:10 30.40 23.51
July 0.248029E+10 2379.15 22-JUL-15:12 31.87 26.22 99587248.13 56.69 11-JUL-22:49 31.87 26.22
August 0.229143E+10 2377.09 22-AUG-15:12 28.30 25.24 99669330.46 56.70 29-AUG-21:40 27.20 23.47
September 0.233313E+10 2372.74 09-SEP-15:12 30.60 25.38 96387284.96 56.69 29-SEP-23:19 28.30 23.65
October 0.223783E+10 2377.00 12-OCT-15:12 29.27 23.90 99598696.52 56.70 25-OCT-22:40 25.37 21.64
November 0.172974E+10 2362.96 15-NOV-16:11 25.93 18.89 96313454.50 56.69 02-NOV-00:49 25.93 18.89
December 0.130171E+10 2479.79 20-DEC-16:11 14.80 7.30 99048782.66 56.69 02-DEC-00:10 14.80 7.30
                     
Annual Sum or Average 0.229145E+11         0.117150E+10        
Minimum of Months 0.128594E+10 2362.96   14.80 7.30 89725008.06 56.69   14.80 7.30
Maximum of Months 0.248029E+10 2505.76   31.87 26.22 99669330.46 56.70   31.87 26.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.764212E+09 2376.61 24-JAN-19:01 13.72 7.28 0.103125E+09 73.85 03-JAN-22:10 13.72 7.28
February 0.851898E+09 2524.68 28-FEB-09:51 24.40 16.28 94731569.65 74.04 17-FEB-22:10 24.40 16.28
March 0.119292E+10 2464.63 01-MAR-09:51 19.40 15.91 0.105122E+09 76.25 31-MAR-21:10 23.27 18.08
April 0.161708E+10 2550.34 20-APR-08:51 24.40 17.42 0.101640E+09 76.75 10-APR-21:10 24.40 17.42
May 0.209157E+10 2390.20 18-MAY-08:61 27.88 22.37 0.100928E+09 74.54 25-MAY-21:10 23.90 22.59
June 0.228422E+10 2420.96 13-JUN-18:11 25.37 22.49 97016341.91 69.22 21-JUN-20:00 24.40 22.75
July 0.247350E+10 2397.99 22-JUL-15:12 31.87 26.22 0.100482E+09 80.22 14-JUL-21:10 31.87 26.22
August 0.223326E+10 2386.83 30-AUG-15:12 29.80 23.93 99980449.50 57.22 06-AUG-21:19 29.80 23.93
September 0.215940E+10 2384.39 24-SEP-15:12 30.60 24.16 97271272.62 77.01 05-SEP-21:10 30.60 24.16
October 0.192214E+10 2384.01 17-OCT-08:61 25.78 18.68 0.100570E+09 72.65 27-OCT-21:19 23.90 21.88
November 0.132020E+10 2319.14 19-NOV-19:01 25.60 20.62 98946067.78 73.93 21-NOV-22:10 24.40 22.53
December 0.822752E+09 2302.80 20-DEC-16:11 14.80 7.30 0.102440E+09 72.47 07-DEC-22:10 14.80 7.30
                     
Annual Sum or Average 0.197332E+11         0.120225E+10        
Minimum of Months 0.764212E+09 2302.80   13.72 7.28 94731569.65 57.22   13.72 7.28
Maximum of Months 0.247350E+10 2550.34   31.87 26.22 0.105122E+09 80.22   31.87 26.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.426380E+10 2100.87 02-JAN-19:10 23.12 19.93 0.142469E+10 915.97 03-JAN-22:49 21.78 20.23
February 0.390840E+10 2057.97 11-FEB-18:40 24.23 22.11 0.129563E+10 894.74 17-FEB-23:10 23.90 20.81
March 0.442561E+10 2123.56 30-MAR-18:10 24.82 19.47 0.145884E+10 911.20 31-MAR-21:49 23.13 18.35
April 0.459024E+10 2284.91 15-APR-17:50 30.28 22.14 0.146264E+10 933.91 14-APR-21:49 30.28 22.14
May 0.490099E+10 2292.51 22-MAY-18:10 30.40 23.74 0.153884E+10 940.82 19-MAY-21:49 30.40 23.74
June 0.494227E+10 2351.85 11-JUN-10:35 30.93 23.60 0.153015E+10 951.83 29-JUN-21:40 28.90 24.82
July 0.524754E+10 2435.00 29-JUL-17:50 33.48 24.12 0.159359E+10 951.83 31-JUL-21:30 28.85 24.54
August 0.510244E+10 2366.05 21-AUG-18:08 29.40 24.96 0.158069E+10 951.83 23-AUG-21:40 26.70 22.56
September 0.503594E+10 2454.74 22-SEP-21:10 28.30 25.17 0.153954E+10 951.83 13-SEP-21:49 28.30 25.17
October 0.505156E+10 2315.05 07-OCT-10:35 31.13 24.14 0.157669E+10 951.84 25-OCT-21:19 26.50 21.25
November 0.456693E+10 2218.73 08-NOV-19:10 26.10 22.26 0.146464E+10 947.07 10-NOV-22:49 22.88 20.65
December 0.435073E+10 2194.92 09-DEC-11:35 27.20 22.50 0.144175E+10 927.57 08-DEC-23:10 27.20 22.50
                     
Annual Sum or Average 0.563865E+11         0.179077E+11        
Minimum of Months 0.390840E+10 2057.97   23.12 19.47 0.129563E+10 894.74   21.78 18.35
Maximum of Months 0.524754E+10 2454.74   33.48 25.17 0.159359E+10 951.84   30.40 25.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111734E+10 2979.06 25-JAN-16:11 17.80 8.74 98860245.06 56.70 11-JAN-04:40 17.80 8.74
February 0.126672E+10 2951.21 03-FEB-16:11 16.13 8.51 89438939.26 56.69 21-FEB-22:40 17.23 13.98
March 0.160051E+10 2994.24 15-MAR-15:11 17.40 8.95 99212796.43 56.69 29-MAR-22:49 23.40 20.30
April 0.193199E+10 2807.08 20-APR-18:01 23.22 16.86 96192694.88 56.69 16-APR-00:20 23.22 16.86
May 0.216481E+10 2790.18 07-MAY-15:12 26.33 21.16 99557946.02 56.69 20-MAY-01:30 26.10 22.78
June 0.218296E+10 2831.06 08-JUN-18:02 29.90 25.47 96397210.65 56.70 28-JUN-21:19 28.90 24.83
July 0.245378E+10 2820.28 12-JUL-18:02 28.90 25.29 99530078.59 56.70 28-JUL-21:49 28.98 24.44
August 0.231476E+10 2820.19 05-AUG-15:12 29.60 25.68 99612186.89 56.69 07-AUG-23:00 27.20 23.57
September 0.225183E+10 2847.84 30-SEP-15:12 31.10 24.59 96318751.64 56.69 24-SEP-02:39 31.10 24.59
October 0.215952E+10 2797.10 16-OCT-18:02 26.52 20.97 99516967.54 56.69 20-OCT-23:30 24.70 21.05
November 0.163666E+10 2787.22 07-NOV-16:12 28.13 22.24 96126459.62 56.69 08-NOV-23:00 25.00 21.11
December 0.127468E+10 2822.76 20-DEC-19:02 12.62 6.43 98850607.26 56.70 22-DEC-03:00 18.90 16.42
                     
Annual Sum or Average 0.223556E+11         0.116961E+10        
Minimum of Months 0.111734E+10 2787.22   12.62 6.43 89438939.26 56.69   17.23 8.74
Maximum of Months 0.245378E+10 2994.24   31.10 25.68 99612186.89 56.70   31.10 24.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.613286E+09 2940.73 24-JAN-19:01 13.72 7.28 0.102805E+09 75.14 03-JAN-22:10 13.72 7.28
February 0.822232E+09 2819.67 10-FEB-16:12 25.93 22.21 94813945.39 76.60 16-FEB-22:10 23.30 20.32
March 0.118831E+10 2969.52 15-MAR-20:11 14.80 8.22 0.105843E+09 79.12 31-MAR-21:19 23.23 18.15
April 0.166858E+10 3028.44 18-APR-21:51 17.80 13.01 0.101804E+09 82.32 18-APR-21:40 17.80 13.01
May 0.213385E+10 2854.74 10-MAY-16:31 25.53 22.56 0.100734E+09 76.06 25-MAY-21:10 23.90 22.59
June 0.220345E+10 2937.50 13-JUN-18:11 25.37 22.49 96939110.34 69.98 21-JUN-20:00 24.40 22.75
July 0.245350E+10 2839.05 12-JUL-18:02 28.90 25.29 0.100446E+09 81.97 14-JUL-21:10 23.22 22.08
August 0.225855E+10 2832.10 15-AUG-18:02 29.72 25.03 99914924.13 57.78 06-AUG-21:00 29.72 25.03
September 0.208429E+10 2836.33 08-SEP-18:02 31.02 24.58 97084649.30 78.28 05-SEP-21:10 31.02 24.58
October 0.185608E+10 2818.98 06-OCT-18:02 27.62 23.75 0.100203E+09 70.90 27-OCT-21:19 23.90 21.88
November 0.125299E+10 2827.99 01-NOV-15:12 27.03 21.23 98383823.55 74.37 21-NOV-22:10 24.40 22.53
December 0.800004E+09 2792.23 05-DEC-16:12 25.20 20.91 0.102613E+09 75.80 01-DEC-22:10 25.20 20.91
                     
Annual Sum or Average 0.193351E+11         0.120158E+10        
Minimum of Months 0.613286E+09 2792.23   13.72 7.28 94813945.39 57.78   13.72 7.28
Maximum of Months 0.245350E+10 3028.44   31.02 25.29 0.105843E+09 82.32   31.02 25.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109000E+10 1449.96 25-JAN-16:11 17.80 8.74 99293378.36 56.69 17-JAN-22:19 17.80 8.74
February 0.100955E+10 1386.40 11-FEB-16:12 27.60 24.09 89720581.57 56.70 22-FEB-22:49 18.48 14.89
March 0.106017E+10 1450.08 16-MAR-15:11 18.67 9.29 99375703.29 56.69 02-MAR-22:10 18.67 9.29
April 0.109788E+10 1366.81 15-APR-18:02 29.82 21.94 96205297.64 56.69 02-APR-23:00 29.82 21.94
May 0.118936E+10 1363.38 09-MAY-15:12 27.20 21.87 99559677.63 56.69 02-MAY-21:19 27.20 21.87
June 0.123324E+10 1368.83 25-JUN-15:12 29.63 24.46 96398541.20 56.69 17-JUN-04:19 29.63 24.46
July 0.134939E+10 1373.92 28-JUL-18:02 32.15 24.42 99529341.01 56.69 05-JUL-21:30 32.15 24.42
August 0.132759E+10 1384.00 31-AUG-15:12 32.03 24.91 99622379.59 56.69 02-AUG-22:49 32.03 24.91
September 0.142320E+10 1387.46 30-SEP-15:12 31.10 24.59 96377617.15 56.69 18-SEP-00:10 31.10 24.59
October 0.149919E+10 1398.12 06-OCT-15:12 29.23 23.77 99644994.73 56.69 07-OCT-23:30 26.70 23.62
November 0.129218E+10 1381.37 19-NOV-16:12 26.70 20.74 96338854.57 56.69 03-NOV-22:00 26.70 20.74
December 0.113613E+10 1389.92 06-DEC-16:12 25.93 22.26 99246788.77 56.69 04-DEC-01:00 25.93 22.26
                     
Annual Sum or Average 0.147079E+11         0.117131E+10        
Minimum of Months 0.100955E+10 1363.38   17.80 8.74 89720581.57 56.69   17.80 8.74
Maximum of Months 0.149919E+10 1450.08   32.15 24.91 99644994.73 56.70   32.15 24.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.413338E+11 19345.29 06-JAN-24:00 24.40 22.49 0.170718E+11 11348.83 03-JAN-23:10 24.40 22.49
February 0.382886E+11 19628.46 17-FEB-24:00 23.90 20.81 0.156180E+11 11348.98 15-FEB-23:10 23.90 20.81
March 0.432609E+11 19943.56 27-MAR-18:10 25.60 21.37 0.175477E+11 11349.11 31-MAR-22:10 23.05 18.37
April 0.438304E+11 20834.91 17-APR-18:10 30.03 18.67 0.172030E+11 11349.10 05-APR-22:10 30.03 18.67
May 0.469936E+11 21447.48 22-MAY-22:00 27.20 22.18 0.180761E+11 11348.81 25-MAY-22:10 23.98 22.31
June 0.465971E+11 21947.08 09-JUN-22:00 28.90 24.83 0.176966E+11 11347.99 21-JUN-21:19 24.60 22.99
July 0.486261E+11 22032.64 28-JUL-22:00 28.90 24.50 0.182057E+11 11349.09 14-JUL-22:10 28.90 24.50
August 0.475561E+11 21624.47 02-AUG-23:00 28.90 24.51 0.182112E+11 11345.07 02-AUG-23:30 28.90 24.51
September 0.459502E+11 21671.37 22-SEP-22:00 28.30 25.79 0.175127E+11 11348.96 05-SEP-22:10 28.30 25.79
October 0.460285E+11 20907.71 03-OCT-23:00 27.20 25.59 0.178729E+11 11348.81 27-OCT-22:10 23.80 21.85
November 0.426606E+11 20471.55 03-NOV-23:00 26.70 23.84 0.170022E+11 11348.85 21-NOV-22:40 24.40 22.66
December 0.419806E+11 19620.96 08-DEC-24:00 25.00 23.46 0.171935E+11 11348.98 01-DEC-23:10 25.00 23.46
                     
Annual Sum or Average 0.533106E+12         0.209211E+12        
Minimum of Months 0.382886E+11 19345.29   23.90 18.67 0.156180E+11 11345.07   23.05 18.37
Maximum of Months 0.486261E+11 22032.64   30.03 25.79 0.182112E+11 11349.11   30.03 25.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.427684E+11 20488.15 06-JAN-24:00 24.40 22.49 0.174389E+11 11348.83 03-JAN-23:10 24.40 22.49
February 0.395951E+11 20809.99 17-FEB-22:53 23.90 20.81 0.159415E+11 11348.99 15-FEB-23:10 23.90 20.81
March 0.447422E+11 21296.58 27-MAR-21:10 24.90 21.81 0.179012E+11 11349.11 31-MAR-22:10 23.05 18.37
April 0.452448E+11 21878.21 14-APR-22:00 25.00 21.97 0.175275E+11 11349.22 18-APR-22:10 17.62 12.99
May 0.485582E+11 22800.81 22-MAY-22:00 27.20 22.18 0.184066E+11 11348.82 25-MAY-22:10 23.98 22.31
June 0.482146E+11 23253.96 09-JUN-22:00 28.90 24.83 0.179877E+11 11348.16 21-JUN-21:19 24.60 22.99
July 0.502961E+11 23347.81 28-JUL-22:00 28.90 24.50 0.185132E+11 11349.09 14-JUL-22:10 28.90 24.50
August 0.491562E+11 22956.33 02-AUG-22:00 28.90 24.51 0.185240E+11 11345.31 20-AUG-23:19 28.13 24.58
September 0.474683E+11 22956.16 22-SEP-22:00 28.30 25.79 0.178161E+11 11348.97 05-SEP-22:10 28.30 25.79
October 0.474814E+11 22176.23 03-OCT-22:00 27.80 25.31 0.181973E+11 11348.82 27-OCT-22:10 23.80 21.85
November 0.440393E+11 21655.38 03-NOV-22:00 26.70 24.27 0.173242E+11 11348.84 21-NOV-22:40 24.40 22.66
December 0.434338E+11 20757.77 08-DEC-22:05 23.98 22.48 0.175654E+11 11348.98 01-DEC-23:10 23.98 22.48
                     
Annual Sum or Average 0.550998E+12         0.213144E+12        
Minimum of Months 0.395951E+11 20488.15   23.90 20.81 0.159415E+11 11345.31   17.62 12.99
Maximum of Months 0.502961E+11 23347.81   28.90 25.79 0.185240E+11 11349.22   28.90 25.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.500901E+11 27480.66 01-JAN-11:50 26.20 21.28 0.188681E+11 11319.59 28-JAN-18:10 23.12 19.99
February 0.459448E+11 27504.68 11-FEB-11:50 27.70 23.78 0.170437E+11 11319.63 25-FEB-18:10 22.62 15.41
March 0.516780E+11 27710.86 27-MAR-10:40 26.13 21.70 0.188762E+11 11319.66 25-MAR-17:10 26.13 21.70
April 0.518050E+11 28713.12 15-APR-10:50 29.63 22.91 0.182624E+11 11319.69 08-APR-17:10 29.63 22.91
May 0.548017E+11 28752.49 06-MAY-10:50 29.13 21.57 0.188718E+11 11319.68 20-MAY-17:10 29.22 21.97
June 0.540807E+11 29184.63 11-JUN-10:50 31.02 23.55 0.182661E+11 11319.68 10-JUN-17:10 31.02 23.55
July 0.564272E+11 29417.49 23-JUL-10:50 32.75 24.78 0.188682E+11 11319.68 01-JUL-17:10 32.75 24.78
August 0.553091E+11 28995.77 19-AUG-10:50 31.60 24.73 0.188754E+11 11319.67 19-AUG-17:10 30.82 24.23
September 0.538523E+11 28968.01 09-SEP-10:50 31.02 25.29 0.182617E+11 11319.68 16-SEP-17:10 30.40 23.74
October 0.543372E+11 28686.31 07-OCT-10:50 31.42 24.17 0.188690E+11 11319.66 21-OCT-17:10 26.93 20.07
November 0.506953E+11 27701.47 07-NOV-11:50 27.12 21.36 0.182588E+11 11319.58 25-NOV-18:10 25.32 22.09
December 0.503691E+11 27697.16 09-DEC-11:50 27.20 22.50 0.188681E+11 11319.63 02-DEC-18:10 27.20 22.50
                     
Annual Sum or Average 0.629391E+12         0.222189E+12        
Minimum of Months 0.459448E+11 27480.66   26.13 21.28 0.170437E+11 11319.58   22.62 15.41
Maximum of Months 0.564272E+11 29417.49   32.75 25.29 0.188762E+11 11319.69   32.75 24.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.563078E+10 5045.71 02-JAN-14:30 28.90 24.11 0.163506E+10 1007.40 02-JAN-23:10 20.50 19.70
February 0.564173E+10 5544.63 11-FEB-14:30 28.85 24.07 0.149849E+10 1007.40 21-FEB-22:10 18.03 14.22
March 0.672834E+10 4980.99 27-MAR-15:13 27.60 22.33 0.167972E+10 1007.40 10-MAR-23:10 27.60 22.33
April 0.794361E+10 5540.71 14-APR-15:23 30.00 24.33 0.165811E+10 1007.40 17-APR-21:30 23.05 17.57
May 0.978812E+10 5541.25 18-MAY-15:13 30.73 22.62 0.171782E+10 1007.40 24-MAY-21:10 24.40 22.88
June 0.106748E+11 6086.45 28-JUN-16:00 30.00 24.34 0.166578E+10 1007.40 21-JUN-21:10 30.00 24.34
July 0.117216E+11 6928.76 29-JUL-16:10 35.40 24.35 0.171454E+10 1007.40 14-JUL-22:10 35.40 24.35
August 0.107517E+11 6365.86 31-AUG-15:10 32.12 24.95 0.172161E+10 1007.39 30-AUG-21:30 32.12 24.95
September 0.108052E+11 6740.59 09-SEP-13:10 31.60 25.21 0.166133E+10 1007.40 05-SEP-22:10 31.60 25.21
October 0.993894E+10 6298.64 07-OCT-13:40 30.00 23.76 0.171517E+10 1007.40 19-OCT-21:19 24.23 19.31
November 0.776175E+10 5686.09 08-NOV-14:30 28.60 21.91 0.163689E+10 1007.40 01-NOV-22:10 28.60 21.91
December 0.629012E+10 5263.41 09-DEC-12:40 27.20 22.50 0.163829E+10 1007.40 04-DEC-23:10 27.20 22.50
                     
Annual Sum or Average 0.103677E+12         0.199428E+11        
Minimum of Months 0.563078E+10 4980.99   27.20 21.91 0.149849E+10 1007.39   18.03 14.22
Maximum of Months 0.117216E+11 6928.76   35.40 25.21 0.172161E+10 1007.40   35.40 25.21



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1427659.47 747.43 31-JAN-09:03 13.90
February 1753529.05 743.90 03-FEB-09:04 11.78
March 742818.37 740.61 21-MAR-08:03 12.57
April 261522.51 710.96 02-APR-08:05 18.77
May 36874.88 194.85 25-MAY-08:06 25.40
June 27708.94 167.39 13-JUN-08:06 25.87
July 7544.82 51.21 03-JUL-08:06 26.88
August 30260.77 117.59 12-AUG-08:07 22.70
September 62927.02 177.05 28-SEP-08:06 24.78
October 171310.64 674.23 17-OCT-08:04 25.78
November 396602.46 734.07 27-NOV-09:04 15.65
December 1518485.00 734.93 15-DEC-09:04 10.97
         
Annual Sum or Average 6437243.93      
Minimum of Months 7544.82 51.21   10.97
Maximum of Months 1753529.05 747.43   26.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1822782.42 757.72 24-JAN-19:04 13.72
February 2554989.32 740.66 05-FEB-09:03 15.37
March 918287.97 732.29 21-MAR-08:03 12.57
April 252006.42 679.81 21-APR-08:34 25.20
May 78026.31 530.38 01-MAY-08:35 25.93
June 11082.87 76.26 14-JUN-08:06 26.88
July 4933.75 57.56 18-JUL-08:06 28.98
August 32136.04 215.33 28-AUG-08:56 22.80
September 56570.71 203.60 28-SEP-08:06 24.78
October 151125.44 337.71 28-OCT-08:55 25.00
November 583293.62 714.95 12-NOV-09:05 14.68
December 1627693.51 756.73 20-DEC-09:03 12.30
         
Annual Sum or Average 8092928.37      
Minimum of Months 4933.75 57.56   12.30
Maximum of Months 2554989.32 757.72   28.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 266453.74 242.66 26-JAN-09:04 13.77
February 177381.69 212.01 04-FEB-09:06 10.47
March 86823.67 239.78 16-MAR-08:05 8.68
April 42670.39 132.67 05-APR-08:36 25.20
May 7334.48 73.34 27-MAY-08:57 23.90
June 8807.82 102.76 15-JUN-08:56 25.60
July 0.00 0.00 01-JUL-00:10 26.83
August 8689.34 72.41 28-AUG-08:56 22.80
September 0.00 0.00 01-SEP-00:10 27.05
October 27625.31 201.59 15-OCT-21:56 23.30
November 72260.02 131.12 27-NOV-09:06 15.65
December 242245.23 246.73 20-DEC-16:14 14.80
         
Annual Sum or Average 940291.69      
Minimum of Months 0.00 0.00   8.68
Maximum of Months 266453.74 246.73   27.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 985668.00 717.44 30-JAN-16:15 14.80
February 1434879.46 729.39 03-FEB-16:14 16.13
March 418699.71 707.49 16-MAR-18:04 18.22
April 83605.99 266.46 27-APR-08:06 23.40
May 107505.41 352.33 25-MAY-08:06 25.40
June 75440.74 226.97 15-JUN-08:06 23.68
July 21311.47 144.19 05-JUL-08:06 28.48
August 69075.29 252.85 28-AUG-08:06 23.72
September 26122.85 111.96 15-SEP-08:06 25.37
October 52261.60 249.59 02-OCT-08:06 27.57
November 272617.58 684.26 12-NOV-16:15 20.00
December 1127363.52 686.30 19-DEC-19:05 18.22
         
Annual Sum or Average 4674551.62      
Minimum of Months 21311.47 111.96   14.80
Maximum of Months 1434879.46 729.39   28.48



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1190044.04 710.05 30-JAN-19:05 15.10
February 2367683.53 638.21 03-FEB-17:24 14.70
March 326180.41 697.85 15-MAR-20:14 14.80
April 22717.11 161.22 12-APR-08:06 26.78
May 51067.22 197.93 26-MAY-08:06 25.68
June 45971.84 165.99 18-JUN-08:06 25.40
July 8697.20 101.47 05-JUL-08:06 28.48
August 45894.47 269.29 28-AUG-08:56 22.80
September 18862.39 142.97 15-SEP-08:06 25.37
October 81656.56 248.46 21-OCT-21:56 25.00
November 311966.51 544.59 11-NOV-22:55 16.70
December 1493803.75 731.01 20-DEC-19:03 12.62
         
Annual Sum or Average 5964545.03      
Minimum of Months 8697.20 101.47   12.62
Maximum of Months 2367683.53 731.01   28.48



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5309133.05 911.24 24-JAN-19:04 13.72
February 10027603.43 840.68 05-FEB-09:03 15.37
March 3652082.45 824.55 16-MAR-08:62 8.68
April 191821.46 788.46 20-APR-08:04 23.48
May 53760.38 195.66 25-MAY-08:06 25.40
June 45887.26 313.60 17-JUN-08:05 26.88
July 0.00 0.00 01-JUL-00:10 26.83
August 12575.30 62.99 08-AUG-08:05 29.68
September 44179.19 181.12 28-SEP-08:06 24.78
October 147784.60 538.61 17-OCT-08:04 25.78
November 1893218.33 851.58 14-NOV-09:04 20.87
December 8128868.80 887.58 15-DEC-16:14 19.23
         
Annual Sum or Average 29506914.24      
Minimum of Months 0.00 0.00   8.68
Maximum of Months 10027603.43 911.24   29.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11439611.56 911.60 24-JAN-19:04 13.72
February 15605144.44 926.95 03-FEB-19:03 13.03
March 4665217.36 908.31 15-MAR-20:14 14.80
April 434017.27 859.55 18-APR-08:53 19.40
May 110256.93 423.07 01-MAY-08:35 25.93
June 39562.39 216.45 17-JUN-08:05 26.88
July 1130.26 12.70 18-JUL-08:06 28.98
August 27819.24 102.06 28-AUG-08:56 22.80
September 164644.95 426.80 27-SEP-08:26 25.55
October 103542.60 267.36 20-OCT-08:35 26.27
November 2640756.04 768.99 13-NOV-09:52 19.40
December 17261210.75 907.97 20-DEC-19:03 12.62
         
Annual Sum or Average 52492913.78      
Minimum of Months 1130.26 12.70   12.62
Maximum of Months 17261210.75 926.95   28.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 198465.94 379.65 22-JAN-09:05 14.60
February 670211.22 316.12 24-FEB-09:04 18.17
March 269205.40 404.70 20-MAR-08:03 11.28
April 101421.25 180.11 02-APR-08:05 18.77
May 170604.53 181.32 04-MAY-08:06 26.78
June 80441.23 198.07 19-JUN-08:06 26.60
July 11805.07 81.93 10-JUL-08:06 25.92
August 77703.48 218.79 10-AUG-08:06 24.60
September 59104.06 188.95 15-SEP-08:06 25.37
October 52589.30 171.35 02-OCT-08:06 27.57
November 108888.33 185.20 29-NOV-09:06 25.68
December 251613.20 335.00 17-DEC-16:16 19.80
         
Annual Sum or Average 2052053.02      
Minimum of Months 11805.07 81.93   11.28
Maximum of Months 670211.22 404.70   27.57



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:05 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:10 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.785035E+10 7561.54 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.708815E+10 7561.54 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.787455E+10 7561.54 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.758419E+10 7561.54 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.786396E+10 7561.54 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.761897E+10 7561.54 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.782918E+10 7561.54 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.787758E+10 7561.54 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.758721E+10 7561.54 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.784733E+10 7561.54 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.761292E+10 7561.54 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.782918E+10 7561.54 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.924636E+11     0.143105E+12    
Minimum of Months 0.708815E+10 7561.54   0.109726E+11 9632.53  
Maximum of Months 0.787758E+10 7561.54   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.355268E+09 342.20 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.320774E+09 342.20 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.356363E+09 342.20 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.343222E+09 342.20 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.355884E+09 342.20 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.344797E+09 342.20 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.354310E+09 342.20 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.356500E+09 342.20 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.343359E+09 342.20 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.355131E+09 342.20 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.344523E+09 342.20 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.354310E+09 342.20 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.418444E+10     0.101856E+11    
Minimum of Months 0.320774E+09 342.20   0.780982E+09 685.60  
Maximum of Months 0.356500E+09 342.20   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.411401E+09 396.26 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.371458E+09 396.26 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.412669E+09 396.26 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.397453E+09 396.26 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.412115E+09 396.26 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.399276E+09 396.26 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.410292E+09 396.26 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.412828E+09 396.26 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.397611E+09 396.26 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.411243E+09 396.26 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.398959E+09 396.26 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.410292E+09 396.26 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.484560E+10     0.117950E+11    
Minimum of Months 0.371458E+09 396.26   0.904380E+09 793.93  
Maximum of Months 0.412828E+09 396.26   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.736067E+09 708.98 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.664602E+09 708.98 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.738336E+09 708.98 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.711111E+09 708.98 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.737344E+09 708.98 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.714372E+09 708.98 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.734082E+09 708.98 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.738620E+09 708.98 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.711395E+09 708.98 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.735784E+09 708.98 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.713805E+09 708.98 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.734082E+09 708.98 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.866960E+10     0.124712E+11    
Minimum of Months 0.664602E+09 708.98   0.956227E+09 839.45  
Maximum of Months 0.738620E+09 708.98   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.168723E+09 162.52 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.152342E+09 162.52 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.169243E+09 162.52 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.163003E+09 162.52 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.169016E+09 162.52 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.163750E+09 162.52 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.168268E+09 162.52 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.169308E+09 162.52 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.163068E+09 162.52 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.168658E+09 162.52 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.163620E+09 162.52 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.168268E+09 162.52 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.198727E+10     0.359760E+10    
Minimum of Months 0.152342E+09 162.52   0.275845E+09 242.16  
Maximum of Months 0.169308E+09 162.52   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314027E+09 302.47 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.283537E+09 302.47 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.314994E+09 302.47 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.303380E+09 302.47 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.314571E+09 302.47 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.304771E+09 302.47 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.313180E+09 302.47 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.315115E+09 302.47 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.303501E+09 302.47 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.313906E+09 302.47 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.304529E+09 302.47 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.313180E+09 302.47 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.369869E+10     0.679355E+11    
Minimum of Months 0.283537E+09 302.47   0.520895E+10 4572.80  
Maximum of Months 0.315115E+09 302.47   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.615288E+09 810.33 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.541428E+09 810.33 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.567841E+09 810.33 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.529249E+09 810.33 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.528294E+09 810.33 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.510732E+09 810.33 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.506931E+09 810.33 03-JUL-19:19 0.121533E+10 965.27 03-JUL-19:10
August 0.538861E+09 810.33 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.547495E+09 810.33 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.592766E+09 810.33 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.583175E+09 810.33 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.618266E+09 810.33 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.668033E+10     0.143405E+11    
Minimum of Months 0.506931E+09 810.33   0.109956E+10 965.27  
Maximum of Months 0.618266E+09 810.33   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.674356E+10 6817.32 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.607161E+10 6817.32 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.670486E+10 6817.32 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.643265E+10 6817.32 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.664824E+10 6817.32 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.644653E+10 6817.32 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.659320E+10 6817.32 03-JUL-19:19 0.126273E+11 10029.21 03-JUL-19:10
August 0.666913E+10 6817.32 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.646071E+10 6817.32 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.671470E+10 6817.32 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.652165E+10 6817.32 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.673568E+10 6817.32 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.787425E+11     0.148998E+12    
Minimum of Months 0.607161E+10 6817.32   0.114244E+11 10029.21  
Maximum of Months 0.674356E+10 6817.32   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65789991.58 59.53 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 59414784.75 59.53 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 65267117.48 59.53 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 63743496.62 59.53 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 65528554.53 59.53 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 63237765.93 59.53 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 66042856.93 59.53 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 65267117.48 59.53 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 63760640.03 59.53 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 65781419.88 59.53 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 63490631.27 59.53 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 66051428.64 59.53 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.773376E+09     0.256575E+10    
Minimum of Months 59414784.75 59.53   0.196843E+09 232.19  
Maximum of Months 66051428.64 59.53   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.115875E+10 1116.11 02-JAN-20:10 0.00 0.00
February 0.104624E+10 1116.11 01-FEB-20:10 0.00 0.00
March 0.116232E+10 1116.11 01-MAR-20:10 0.00 0.00
April 0.111946E+10 1116.11 03-APR-19:10 0.00 0.00
May 0.116076E+10 1116.11 01-MAY-19:10 0.00 0.00
June 0.112460E+10 1116.11 01-JUN-19:10 0.00 0.00
July 0.115562E+10 1116.11 03-JUL-19:10 0.00 0.00
August 0.116277E+10 1116.11 01-AUG-19:10 0.00 0.00
September 0.111991E+10 1116.11 01-SEP-19:10 0.00 0.00
October 0.115830E+10 1116.11 02-OCT-19:10 0.00 0.00
November 0.112370E+10 1116.11 01-NOV-19:10 0.00 0.00
December 0.115562E+10 1116.11 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.136481E+11     0.00 0.00
Minimum of Months 0.104624E+10 1116.11   0.00 0.00
Maximum of Months 0.116277E+10 1116.11   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.130046E+10 1423.01 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.115437E+10 1423.01 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.124782E+10 1423.01 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.117420E+10 1423.01 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.119237E+10 1423.01 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.114543E+10 1423.01 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.116853E+10 1423.01 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.120815E+10 1423.01 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.119557E+10 1423.01 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.126893E+10 1423.01 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.124232E+10 1423.01 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.129500E+10 1423.01 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.145932E+11     0.175857E+12    
Minimum of Months 0.114543E+10 1423.01   0.134904E+11 6747.90  
Maximum of Months 0.130046E+10 1423.01   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.130046E+10 1423.01 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.115437E+10 1423.01 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.124782E+10 1423.01 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.117420E+10 1423.01 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.119237E+10 1423.01 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.114543E+10 1423.01 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.116853E+10 1423.01 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.120815E+10 1423.01 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.119557E+10 1423.01 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.126893E+10 1423.01 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.124232E+10 1423.01 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.129500E+10 1423.01 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.145932E+11     0.175857E+12    
Minimum of Months 0.114543E+10 1423.01   0.134904E+11 6747.90  
Maximum of Months 0.130046E+10 1423.01   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.775957E+09 747.41 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.700619E+09 747.41 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.778349E+09 747.41 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.749649E+09 747.41 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.777303E+09 747.41 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.753087E+09 747.41 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.773865E+09 747.41 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.778648E+09 747.41 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.749948E+09 747.41 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.775658E+09 747.41 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.752489E+09 747.41 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.773865E+09 747.41 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.913943E+10     0.424019E+12    
Minimum of Months 0.700619E+09 747.41   0.325275E+11 16179.04  
Maximum of Months 0.778648E+09 747.41   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.122636E+10 1181.23 02-JAN-20:10 0.00 0.00
February 0.110729E+10 1181.23 01-FEB-20:10 0.00 0.00
March 0.123014E+10 1181.23 01-MAR-20:10 0.00 0.00
April 0.118478E+10 1181.23 03-APR-19:10 0.00 0.00
May 0.122848E+10 1181.23 01-MAY-19:10 0.00 0.00
June 0.119021E+10 1181.23 01-JUN-19:10 0.00 0.00
July 0.122305E+10 1181.23 03-JUL-19:10 0.00 0.00
August 0.123061E+10 1181.23 01-AUG-19:10 0.00 0.00
September 0.118525E+10 1181.23 01-SEP-19:10 0.00 0.00
October 0.122588E+10 1181.23 02-OCT-19:10 0.00 0.00
November 0.118927E+10 1181.23 01-NOV-19:10 0.00 0.00
December 0.122305E+10 1181.23 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.144444E+11     0.00 0.00
Minimum of Months 0.110729E+10 1181.23   0.00 0.00
Maximum of Months 0.123061E+10 1181.23   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.785035E+10 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.708815E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.787455E+10 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.758419E+10 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.786396E+10 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.761897E+10 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.782918E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.787758E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.758721E+10 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.784733E+10 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.761292E+10 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.782918E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.924636E+11 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.708815E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.787758E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.355268E+09 0.864900E+09 0.00 0.00 0.00 0.00 7102672.56 0.134639E+09
February 0.179968E+10 0.320774E+09 0.780982E+09 0.00 0.00 0.00 0.00 10918441.88 87901953.97
March 0.199990E+10 0.356363E+09 0.866718E+09 0.00 0.00 0.00 0.00 13388935.84 78041120.97
April 0.192973E+10 0.343222E+09 0.835931E+09 0.00 0.00 0.00 0.00 35416015.77 26375272.16
May 0.199475E+10 0.355884E+09 0.865939E+09 0.00 0.00 0.00 0.00 80793933.77 4006517.27
June 0.193394E+10 0.344797E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.111369E+09 221730.08
July 0.199054E+10 0.354310E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.129198E+09 1261800.15
August 0.199896E+10 0.356500E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.125488E+09 468919.60
September 0.192879E+10 0.343359E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.105863E+09 812220.92
October 0.199148E+10 0.355131E+09 0.864640E+09 0.00 0.00 0.00 0.00 78066311.01 4218409.84
November 0.192552E+10 0.344523E+09 0.838269E+09 0.00 0.00 0.00 0.00 37744951.07 44548559.43
December 0.199054E+10 0.354310E+09 0.863211E+09 0.00 0.00 0.00 0.00 10575962.12 0.112576E+09
                   
Annual Sum or Average 0.234744E+11 0.418444E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.745925E+09 0.495072E+09
Minimum of Months 0.179968E+10 0.320774E+09 0.780982E+09 0.00 0.00 0.00 0.00 7102672.56 221730.08
Maximum of Months 0.199990E+10 0.356500E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.129198E+09 0.134639E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.411401E+09 0.100156E+10 0.00 0.00 0.00 0.00 5274204.83 48498321.41
February 0.208403E+10 0.371458E+09 0.904380E+09 0.00 0.00 0.00 0.00 7782587.01 32449498.92
March 0.231589E+10 0.412669E+09 0.100366E+10 0.00 0.00 0.00 0.00 8661750.78 28694190.05
April 0.223463E+10 0.397453E+09 0.968011E+09 0.00 0.00 0.00 0.00 17281246.96 9836050.57
May 0.230993E+10 0.412115E+09 0.100276E+10 0.00 0.00 0.00 0.00 34790680.55 1418329.84
June 0.223950E+10 0.399276E+09 0.971170E+09 0.00 0.00 0.00 0.00 45986218.32 45992.86
July 0.230505E+10 0.410292E+09 0.999601E+09 0.00 0.00 0.00 0.00 52174377.42 432554.24
August 0.231480E+10 0.412828E+09 0.100396E+10 0.00 0.00 0.00 0.00 51214542.31 154249.21
September 0.223354E+10 0.397611E+09 0.968312E+09 0.00 0.00 0.00 0.00 43401978.33 289284.45
October 0.230614E+10 0.411243E+09 0.100126E+10 0.00 0.00 0.00 0.00 33517693.85 1534481.25
November 0.222975E+10 0.398959E+09 0.970719E+09 0.00 0.00 0.00 0.00 18274676.15 16483357.14
December 0.230505E+10 0.410292E+09 0.999601E+09 0.00 0.00 0.00 0.00 6433908.53 40985353.28
                   
Annual Sum or Average 0.271834E+11 0.484560E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.324794E+09 0.180822E+09
Minimum of Months 0.208403E+10 0.371458E+09 0.904380E+09 0.00 0.00 0.00 0.00 5274204.83 45992.86
Maximum of Months 0.231589E+10 0.412828E+09 0.100396E+10 0.00 0.00 0.00 0.00 52174377.42 48498321.41



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.736067E+09 0.105898E+10 0.00 0.00 0.00 0.00 6305428.46 0.137336E+09
February 0.440737E+09 0.664602E+09 0.956227E+09 0.00 0.00 0.00 0.00 9681225.23 90647503.03
March 0.489771E+09 0.738336E+09 0.106120E+10 0.00 0.00 0.00 0.00 11475193.68 80653217.11
April 0.472586E+09 0.711111E+09 0.102351E+10 0.00 0.00 0.00 0.00 30713913.37 28429900.44
May 0.488511E+09 0.737344E+09 0.106025E+10 0.00 0.00 0.00 0.00 72756166.46 4485328.76
June 0.473617E+09 0.714372E+09 0.102685E+10 0.00 0.00 0.00 0.00 0.101263E+09 239686.55
July 0.487480E+09 0.734082E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.117766E+09 1167195.59
August 0.489542E+09 0.738620E+09 0.106152E+10 0.00 0.00 0.00 0.00 0.113379E+09 919039.93
September 0.472357E+09 0.711395E+09 0.102382E+10 0.00 0.00 0.00 0.00 96403402.02 914784.57
October 0.487709E+09 0.735784E+09 0.105866E+10 0.00 0.00 0.00 0.00 70640477.15 4333667.64
November 0.471555E+09 0.713805E+09 0.102637E+10 0.00 0.00 0.00 0.00 34246661.73 46784685.32
December 0.487480E+09 0.734082E+09 0.105691E+10 0.00 0.00 0.00 0.00 9484417.88 0.116150E+09
                   
Annual Sum or Average 0.574883E+10 0.866960E+10 0.124712E+11 0.00 0.00 0.00 0.00 0.674116E+09 0.512061E+09
Minimum of Months 0.440737E+09 0.664602E+09 0.956227E+09 0.00 0.00 0.00 0.00 6305428.46 239686.55
Maximum of Months 0.489771E+09 0.738620E+09 0.106152E+10 0.00 0.00 0.00 0.00 0.117766E+09 0.137336E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.168723E+09 0.305485E+09 0.00 0.00 0.00 0.00 9116247.98 55745141.69
February 0.339028E+09 0.152342E+09 0.275845E+09 0.00 0.00 0.00 0.00 13239745.73 36060051.92
March 0.376747E+09 0.169243E+09 0.306128E+09 0.00 0.00 0.00 0.00 15526026.96 30408207.17
April 0.363528E+09 0.163003E+09 0.295253E+09 0.00 0.00 0.00 0.00 27538684.17 8313781.84
May 0.375778E+09 0.169016E+09 0.305852E+09 0.00 0.00 0.00 0.00 50551245.16 1226228.92
June 0.364321E+09 0.163750E+09 0.296217E+09 0.00 0.00 0.00 0.00 62627248.59 33765.25
July 0.374985E+09 0.168268E+09 0.304889E+09 0.00 0.00 0.00 0.00 70537878.83 446037.63
August 0.376571E+09 0.169308E+09 0.306219E+09 0.00 0.00 0.00 0.00 71654451.58 146397.03
September 0.363352E+09 0.163068E+09 0.295345E+09 0.00 0.00 0.00 0.00 60809844.95 139586.36
October 0.375161E+09 0.168658E+09 0.305393E+09 0.00 0.00 0.00 0.00 50261223.58 1071814.50
November 0.362735E+09 0.163620E+09 0.296079E+09 0.00 0.00 0.00 0.00 28780658.92 18455314.50
December 0.374985E+09 0.168268E+09 0.304889E+09 0.00 0.00 0.00 0.00 11010456.51 46854906.57
                   
Annual Sum or Average 0.442217E+10 0.198727E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.471654E+09 0.198901E+09
Minimum of Months 0.339028E+09 0.152342E+09 0.275845E+09 0.00 0.00 0.00 0.00 9116247.98 33765.25
Maximum of Months 0.376747E+09 0.169308E+09 0.306219E+09 0.00 0.00 0.00 0.00 71654451.58 55745141.69



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.314027E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 8440648.90 0.193921E+09
February 0.139600E+10 0.283537E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 13132875.10 0.128306E+09
March 0.155131E+10 0.314994E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 15664610.70 0.114818E+09
April 0.149688E+10 0.303380E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 41941349.24 38814094.81
May 0.154732E+10 0.314571E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 99353817.80 6121962.01
June 0.150015E+10 0.304771E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.138282E+09 326674.65
July 0.154405E+10 0.313180E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.160816E+09 1592723.03
August 0.155059E+10 0.315115E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.154827E+09 1254339.23
September 0.149615E+10 0.303501E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.131645E+09 1247594.42
October 0.154478E+10 0.313906E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 96465308.48 5914691.63
November 0.149361E+10 0.304529E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 46673614.12 64362182.60
December 0.154405E+10 0.313180E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 12874472.74 0.163533E+09
                   
Annual Sum or Average 0.182090E+11 0.369869E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.920117E+09 0.720212E+09
Minimum of Months 0.139600E+10 0.283537E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 8440648.90 326674.65
Maximum of Months 0.155131E+10 0.315115E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.160816E+09 0.193921E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.615288E+09 0.121771E+10 0.00 0.00 0.00 0.00 34816873.62 0.256091E+09
February 0.236489E+11 0.541428E+09 0.109956E+10 0.00 0.00 0.00 0.00 55030999.92 0.164012E+09
March 0.262800E+11 0.567841E+09 0.122027E+10 0.00 0.00 0.00 0.00 73900119.20 0.138271E+09
April 0.253579E+11 0.529249E+09 0.117692E+10 0.00 0.00 0.00 0.00 0.142225E+09 33937490.84
May 0.262123E+11 0.528294E+09 0.121917E+10 0.00 0.00 0.00 0.00 0.268281E+09 3666766.03
June 0.254132E+11 0.510732E+09 0.118076E+10 0.00 0.00 0.00 0.00 0.331996E+09 13371.90
July 0.261570E+11 0.506931E+09 0.121533E+10 0.00 0.00 0.00 0.00 0.366482E+09 496220.38
August 0.262677E+11 0.538861E+09 0.122063E+10 0.00 0.00 0.00 0.00 0.356839E+09 117101.74
September 0.253456E+11 0.547495E+09 0.117729E+10 0.00 0.00 0.00 0.00 0.298227E+09 236123.62
October 0.261693E+11 0.592766E+09 0.121734E+10 0.00 0.00 0.00 0.00 0.231643E+09 4364935.09
November 0.253025E+11 0.583175E+09 0.118021E+10 0.00 0.00 0.00 0.00 0.125714E+09 78085116.99
December 0.261570E+11 0.618266E+09 0.121533E+10 0.00 0.00 0.00 0.00 44868730.89 0.210256E+09
                   
Annual Sum or Average 0.308468E+12 0.668033E+10 0.143405E+11 0.00 0.00 0.00 0.00 0.233002E+10 0.889546E+09
Minimum of Months 0.236489E+11 0.506931E+09 0.109956E+10 0.00 0.00 0.00 0.00 34816873.62 13371.90
Maximum of Months 0.262800E+11 0.618266E+09 0.122063E+10 0.00 0.00 0.00 0.00 0.366482E+09 0.256091E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.674356E+10 0.126520E+11 0.00 0.00 0.00 0.00 85125804.58 0.824936E+09
February 0.702046E+11 0.607161E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.131216E+09 0.547055E+09
March 0.780153E+11 0.670486E+10 0.126786E+11 0.00 0.00 0.00 0.00 0.156832E+09 0.471921E+09
April 0.752779E+11 0.643265E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.313706E+09 0.156570E+09
May 0.778146E+11 0.664824E+10 0.126672E+11 0.00 0.00 0.00 0.00 0.606245E+09 23822105.42
June 0.754422E+11 0.644653E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.785706E+09 791158.85
July 0.776503E+11 0.659320E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.891693E+09 6465865.19
August 0.779788E+11 0.666913E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.870959E+09 2214132.88
September 0.752414E+11 0.646071E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.738779E+09 5280396.57
October 0.776868E+11 0.671470E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.568114E+09 26185482.15
November 0.751137E+11 0.652165E+10 0.122624E+11 0.00 0.00 0.00 0.00 0.305842E+09 0.279302E+09
December 0.776503E+11 0.673568E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.108082E+09 0.695582E+09
                   
Annual Sum or Average 0.915726E+12 0.787425E+11 0.148998E+12 0.00 0.00 0.00 0.00 0.556230E+10 0.304013E+10
Minimum of Months 0.702046E+11 0.607161E+10 0.114244E+11 0.00 0.00 0.00 0.00 85125804.58 791158.85
Maximum of Months 0.780153E+11 0.674356E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.891693E+09 0.824936E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 11425627.52 56129307.92
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 17488434.70 33909527.81
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 25028392.82 30217782.20
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 44066102.20 4043828.64
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 82926173.52 182739.10
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 0.102153E+09 11096.12
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.113268E+09 27174.13
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.110732E+09 95512.55
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 98536482.37 0.00
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 81422363.36 79280.25
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 44560921.40 14013817.55
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 17123965.42 45712002.92
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.748731E+09 0.184422E+09
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 11425627.52 0.00
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.113268E+09 56129307.92



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 9703269.76 59969629.35
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 14401409.92 38291838.56
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 20349689.13 34704885.18
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 39061011.48 7547348.43
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 81055714.57 446462.40
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 0.101276E+09 34544.41
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.112232E+09 361739.85
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.110173E+09 150231.71
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 97332992.34 72273.79
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 79984171.77 312958.06
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 42981535.35 16440732.58
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 15023735.23 49215530.27
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.723575E+09 0.207548E+09
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 9703269.76 34544.41
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.112232E+09 59969629.35



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 65789991.58 0.217935E+09 0.00 0.00 0.00 0.00 72327.25 38236580.79
February 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 129638.00 27742665.62
March 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 188679.31 27053695.51
April 0.00 63743496.62 0.210923E+09 0.00 0.00 0.00 0.00 1335006.82 14332112.85
May 0.00 65528554.53 0.217879E+09 0.00 0.00 0.00 0.00 4269081.66 5871869.78
June 0.00 63237765.93 0.210812E+09 0.00 0.00 0.00 0.00 6992157.98 2304288.04
July 0.00 66042856.93 0.217991E+09 0.00 0.00 0.00 0.00 9498503.05 2479305.87
August 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 8487131.75 2202280.28
September 0.00 63760640.03 0.210923E+09 0.00 0.00 0.00 0.00 7378726.35 3662692.47
October 0.00 65781419.88 0.217935E+09 0.00 0.00 0.00 0.00 3779046.03 5714561.48
November 0.00 63490631.27 0.210867E+09 0.00 0.00 0.00 0.00 712382.44 16427909.89
December 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 113336.43 33740437.05
                   
Annual Sum or Average 0.00 0.773376E+09 0.256575E+10 0.00 0.00 0.00 0.00 42956017.07 0.179768E+09
Minimum of Months 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 72327.25 2202280.28
Maximum of Months 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 9498503.05 38236580.79



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 2963420.78 16215873.79
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 4369106.92 10315667.81
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 6031563.67 8959826.11
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 11288601.36 1659549.64
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 22938841.93 93826.56
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 28537581.79 3093.78
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 31561558.06 50684.86
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 31051891.07 22982.85
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 27482021.39 5360.62
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 22754421.06 57615.20
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 12376464.14 4392164.94
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 4456606.93 13351538.89
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 0.205812E+09 55128185.07
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 2963420.78 3093.78
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 31561558.06 16215873.79



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 11345526.46 56635300.56
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 17425074.39 34349755.02
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 24930078.80 30864230.98
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 43902274.44 4165897.30
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 82750815.33 192743.08
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 0.101946E+09 11150.47
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.113093E+09 28218.13
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.110603E+09 96868.81
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 98380675.00 0.00
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 81293107.46 90153.51
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 44468710.93 14186337.98
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 17093302.43 45871624.93
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.747231E+09 0.186492E+09
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 11345526.46 0.00
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.113093E+09 56635300.56



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 9344646.42 60779230.83
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 14072273.27 38949996.22
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 20078188.72 35115300.43
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 38662505.98 7854769.14
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 80764674.47 576073.53
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 0.101021E+09 62432.22
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.112044E+09 420566.85
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.110042E+09 150422.00
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 97066220.22 126097.82
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 79628765.20 417041.03
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 42576542.27 16950097.73
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 14899682.20 48605995.37
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.720201E+09 0.210008E+09
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 9344646.42 62432.22
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.112044E+09 60779230.83



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.115875E+10 0.00 0.00 0.00 0.00 0.00 9624347.24 83851770.58
February 0.348285E+10 0.104624E+10 0.00 0.00 0.00 0.00 0.00 14912852.70 53709695.75
March 0.387034E+10 0.116232E+10 0.00 0.00 0.00 0.00 0.00 17202273.04 46940393.74
April 0.373454E+10 0.111946E+10 0.00 0.00 0.00 0.00 0.00 32605590.50 14383853.07
May 0.386038E+10 0.116076E+10 0.00 0.00 0.00 0.00 0.00 67223952.61 1892912.11
June 0.374269E+10 0.112460E+10 0.00 0.00 0.00 0.00 0.00 84517048.07 54915.65
July 0.385223E+10 0.115562E+10 0.00 0.00 0.00 0.00 0.00 94484407.46 668940.65
August 0.386853E+10 0.116277E+10 0.00 0.00 0.00 0.00 0.00 93859465.44 280387.56
September 0.373273E+10 0.111991E+10 0.00 0.00 0.00 0.00 0.00 78409989.52 361015.69
October 0.385404E+10 0.115830E+10 0.00 0.00 0.00 0.00 0.00 60104558.09 2506371.00
November 0.372639E+10 0.112370E+10 0.00 0.00 0.00 0.00 0.00 34306624.47 28815159.34
December 0.385223E+10 0.115562E+10 0.00 0.00 0.00 0.00 0.00 12567472.45 69803528.35
                   
Annual Sum or Average 0.454292E+11 0.136481E+11 0.00 0.00 0.00 0.00 0.00 0.599819E+09 0.303269E+09
Minimum of Months 0.348285E+10 0.104624E+10 0.00 0.00 0.00 0.00 0.00 9624347.24 54915.65
Maximum of Months 0.387034E+10 0.116277E+10 0.00 0.00 0.00 0.00 0.00 94484407.46 83851770.58



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 11075031.14 56490953.23
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 16976027.31 34119664.49
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 24349450.08 30321970.70
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 43159105.62 4072263.21
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 81912605.91 200135.01
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 0.101172E+09 13404.05
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.112235E+09 30862.93
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.109727E+09 97202.64
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 97576435.98 0.00
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 80446203.19 71165.85
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 43822808.75 14067495.05
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 16685253.22 45955616.10
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.739137E+09 0.185441E+09
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 11075031.14 0.00
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.112235E+09 56490953.23



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 9448967.17 60191298.75
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 13981991.61 38769241.08
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 19850064.09 35547444.84
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 38414039.98 7893032.98
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 80121739.43 454278.68
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 0.100311E+09 86233.95
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.111270E+09 521150.47
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.109197E+09 152241.67
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 96506969.97 87933.10
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 79255802.57 193708.55
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 42389828.02 16110393.45
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 14684117.46 49036236.84
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.715432E+09 0.209043E+09
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 9448967.17 86233.95
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.111270E+09 60191298.75



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 5552085.22 29471118.00
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 8572401.93 17799859.70
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 12394677.33 15805554.40
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 22081011.64 2093825.50
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 41920005.12 101068.66
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 51757889.22 6798.89
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 57424598.45 15203.27
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 56121461.78 48047.14
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 49817629.53 0.00
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 40967332.20 43885.81
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 22256440.24 7383673.39
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 8423247.39 24051595.00
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 0.377289E+09 96820629.77
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 5552085.22 0.00
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 57424598.45 29471118.00



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.130046E+10 0.149358E+11 0.00 0.00 0.00 0.00 27059548.57 0.169705E+09
February 0.415303E+11 0.115437E+10 0.134904E+11 0.00 0.00 0.00 0.00 39407639.41 0.113907E+09
March 0.461508E+11 0.124782E+10 0.149358E+11 0.00 0.00 0.00 0.00 44680150.63 99367299.45
April 0.445315E+11 0.117420E+10 0.144540E+11 0.00 0.00 0.00 0.00 81877818.83 30740517.01
May 0.460320E+11 0.119237E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.151231E+09 4231977.31
June 0.446286E+11 0.114543E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.192345E+09 101523.02
July 0.459349E+11 0.116853E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.217895E+09 938814.46
August 0.461292E+11 0.120815E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.213696E+09 287513.63
September 0.445099E+11 0.119557E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.187728E+09 659726.09
October 0.459565E+11 0.126893E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.152694E+09 3890869.08
November 0.444343E+11 0.124232E+10 0.144540E+11 0.00 0.00 0.00 0.00 87087695.00 54809977.84
December 0.459349E+11 0.129500E+10 0.149358E+11 0.00 0.00 0.00 0.00 34619230.76 0.141152E+09
                   
Annual Sum or Average 0.541708E+12 0.145932E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.143032E+10 0.619793E+09
Minimum of Months 0.415303E+11 0.114543E+10 0.134904E+11 0.00 0.00 0.00 0.00 27059548.57 101523.02
Maximum of Months 0.461508E+11 0.130046E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.217895E+09 0.169705E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.130046E+10 0.149358E+11 0.00 0.00 0.00 0.00 24401256.52 0.177370E+09
February 0.415303E+11 0.115437E+10 0.134904E+11 0.00 0.00 0.00 0.00 35734068.46 0.119397E+09
March 0.461508E+11 0.124782E+10 0.149358E+11 0.00 0.00 0.00 0.00 40215297.79 0.104864E+09
April 0.445315E+11 0.117420E+10 0.144540E+11 0.00 0.00 0.00 0.00 75991732.04 34038568.07
May 0.460320E+11 0.119237E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.142676E+09 5059592.45
June 0.446286E+11 0.114543E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.183823E+09 162888.06
July 0.459349E+11 0.116853E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.209190E+09 1243207.59
August 0.461292E+11 0.120815E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.204818E+09 424965.48
September 0.445099E+11 0.119557E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.179321E+09 953871.66
October 0.459565E+11 0.126893E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.144398E+09 4701081.21
November 0.444343E+11 0.124232E+10 0.144540E+11 0.00 0.00 0.00 0.00 81356363.01 58178494.93
December 0.459349E+11 0.129500E+10 0.149358E+11 0.00 0.00 0.00 0.00 31388493.05 0.148333E+09
                   
Annual Sum or Average 0.541708E+12 0.145932E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.135331E+10 0.654727E+09
Minimum of Months 0.415303E+11 0.114543E+10 0.134904E+11 0.00 0.00 0.00 0.00 24401256.52 162888.06
Maximum of Months 0.461508E+11 0.130046E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.209190E+09 0.177370E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.775957E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 8074376.65 0.200867E+09
February 0.369574E+10 0.700619E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 12628508.61 0.133412E+09
March 0.410691E+10 0.778349E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 14996156.03 0.119820E+09
April 0.396281E+10 0.749649E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 41089792.70 41561594.09
May 0.409635E+10 0.777303E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 98077030.78 6844400.62
June 0.397146E+10 0.753087E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.137408E+09 490094.84
July 0.408770E+10 0.773865E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.160316E+09 1854893.64
August 0.410499E+10 0.778648E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.154143E+09 1436332.17
September 0.396089E+10 0.749948E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.130829E+09 1612379.70
October 0.408962E+10 0.775658E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 95135801.63 6634251.59
November 0.395417E+10 0.752489E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 45587246.44 67274008.11
December 0.408770E+10 0.773865E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 12359104.58 0.169675E+09
                   
Annual Sum or Average 0.482060E+11 0.913943E+10 0.382987E+12 0.359593E+12 0.00 0.00 0.00 0.910643E+09 0.751481E+09
Minimum of Months 0.369574E+10 0.700619E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 8074376.65 490094.84
Maximum of Months 0.410691E+10 0.778648E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.160316E+09 0.200867E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.122636E+10 0.00 0.00 0.00 0.00 0.00 8298885.45 0.176686E+09
February 0.368610E+10 0.110729E+10 0.00 0.00 0.00 0.00 0.00 12620703.85 0.117467E+09
March 0.409620E+10 0.123014E+10 0.00 0.00 0.00 0.00 0.00 14759181.32 0.105674E+09
April 0.395248E+10 0.118478E+10 0.00 0.00 0.00 0.00 0.00 40128704.13 39711867.76
May 0.408566E+10 0.122848E+10 0.00 0.00 0.00 0.00 0.00 95737658.34 6653800.21
June 0.396110E+10 0.119021E+10 0.00 0.00 0.00 0.00 0.00 0.134211E+09 490727.02
July 0.407704E+10 0.122305E+10 0.00 0.00 0.00 0.00 0.00 0.156632E+09 1829398.07
August 0.409429E+10 0.123061E+10 0.00 0.00 0.00 0.00 0.00 0.150605E+09 1356399.45
September 0.395056E+10 0.118525E+10 0.00 0.00 0.00 0.00 0.00 0.127787E+09 1591117.94
October 0.407896E+10 0.122588E+10 0.00 0.00 0.00 0.00 0.00 92860391.11 6485781.16
November 0.394385E+10 0.118927E+10 0.00 0.00 0.00 0.00 0.00 44897808.94 60751189.41
December 0.407704E+10 0.122305E+10 0.00 0.00 0.00 0.00 0.00 12361489.62 0.146625E+09
                   
Annual Sum or Average 0.480803E+11 0.144444E+11 0.00 0.00 0.00 0.00 0.00 0.890899E+09 0.665322E+09
Minimum of Months 0.368610E+10 0.110729E+10 0.00 0.00 0.00 0.00 0.00 8298885.45 490727.02
Maximum of Months 0.409620E+10 0.123061E+10 0.00 0.00 0.00 0.00 0.00 0.156632E+09 0.176686E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 7561.54 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 7561.54 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 7561.54 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 7561.54 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 7561.54 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 7561.54 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 7561.54 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 7561.54 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 7561.54 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 7561.54 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 7561.54 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 7561.54 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   7561.54   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   7561.54   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 342.20 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 56.94 02-JAN-14:00 155.48 24-JAN-24:00
February 1169.53 01-FEB-00:10 342.20 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 62.70 11-FEB-14:00 202.94 04-FEB-07:00
March 1169.53 01-MAR-00:10 342.20 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 62.11 13-MAR-16:00 183.99 16-MAR-05:00
April 1169.53 01-APR-00:10 342.20 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 93.44 17-APR-15:00 106.30 02-APR-05:00
May 1169.53 01-MAY-00:10 342.20 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 117.90 22-MAY-13:00 36.06 07-MAY-05:20
June 1169.53 01-JUN-00:10 342.20 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 94.13 11-JUN-13:00 14.22 05-JUN-15:00
July 1169.53 01-JUL-00:10 342.20 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 130.79 29-JUL-16:00 14.28 14-JUL-21:52
August 1169.53 01-AUG-00:10 342.20 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 112.96 23-AUG-13:00 14.31 12-AUG-06:53
September 1169.53 01-SEP-00:10 342.20 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 93.86 13-SEP-13:00 19.14 05-SEP-06:00
October 1169.53 01-OCT-23:10 342.20 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 93.85 09-OCT-11:00 28.28 28-OCT-03:00
November 1169.53 01-NOV-00:10 342.20 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 69.13 17-NOV-15:00 155.22 27-NOV-03:00
December 1169.53 01-DEC-00:10 342.20 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 56.46 10-DEC-14:00 175.38 15-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   342.20   685.60   0.00 0.00 0.00 0.00 56.46   14.22  
Maximum of Months 1169.53   342.20   685.60   0.00 0.00 0.00 0.00 130.79   202.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 396.26 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 27.44 02-JAN-14:30 63.39 25-JAN-05:30
February 1354.32 01-FEB-00:10 396.26 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 28.14 11-FEB-14:00 82.56 04-FEB-07:00
March 1354.32 01-MAR-00:10 396.26 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 28.15 13-MAR-16:00 77.10 16-MAR-05:00
April 1354.32 01-APR-00:10 396.26 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 39.35 17-APR-15:00 42.83 02-APR-05:20
May 1354.32 01-MAY-00:10 396.26 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 49.07 22-MAY-13:00 14.45 07-MAY-05:25
June 1354.32 01-JUN-00:10 396.26 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 38.73 11-JUN-13:00 3.21 05-JUN-22:00
July 1354.32 01-JUL-00:10 396.26 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 51.74 29-JUL-16:00 5.51 14-JUL-21:52
August 1354.32 01-AUG-00:10 396.26 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 45.88 23-AUG-13:00 5.94 12-AUG-06:53
September 1354.32 01-SEP-00:10 396.26 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 39.23 13-SEP-13:00 7.50 05-SEP-06:00
October 1354.32 01-OCT-23:10 396.26 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 39.87 14-OCT-13:00 11.07 28-OCT-03:00
November 1354.32 01-NOV-00:10 396.26 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 30.00 17-NOV-15:00 62.47 27-NOV-03:00
December 1354.32 01-DEC-00:10 396.26 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 25.14 10-DEC-14:40 72.13 15-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   396.26   793.93   0.00 0.00 0.00 0.00 25.14   3.21  
Maximum of Months 1354.32   396.26   793.93   0.00 0.00 0.00 0.00 51.74   82.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 708.98 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 51.94 02-JAN-14:00 154.14 25-JAN-06:40
February 286.42 01-FEB-00:10 708.98 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 57.19 11-FEB-14:00 203.56 04-FEB-07:00
March 286.42 01-MAR-00:10 708.98 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 56.66 13-MAR-16:00 186.74 16-MAR-05:30
April 286.42 01-APR-00:10 708.98 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 85.24 17-APR-15:00 106.57 02-APR-06:00
May 286.42 01-MAY-00:10 708.98 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 107.56 22-MAY-13:00 37.04 01-MAY-06:00
June 286.42 01-JUN-00:10 708.98 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 85.87 11-JUN-13:00 12.97 05-JUN-15:00
July 286.42 01-JUL-00:10 708.98 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 119.31 29-JUL-16:00 13.03 14-JUL-21:52
August 286.42 01-AUG-00:10 708.98 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 103.04 23-AUG-13:00 19.57 28-AUG-12:00
September 286.42 01-SEP-00:10 708.98 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 85.63 13-SEP-13:00 19.43 05-SEP-06:00
October 286.42 01-OCT-23:10 708.98 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 85.62 09-OCT-11:00 31.40 28-OCT-03:00
November 286.42 01-NOV-00:10 708.98 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 63.07 17-NOV-15:00 156.73 27-NOV-03:00
December 286.42 01-DEC-00:10 708.98 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 51.50 10-DEC-14:00 178.02 15-DEC-06:40
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   708.98   839.45   0.00 0.00 0.00 0.00 51.50   12.97  
Maximum of Months 286.42   708.98   839.45   0.00 0.00 0.00 0.00 119.31   203.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 162.52 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 38.43 02-JAN-14:30 77.68 25-JAN-05:00
February 220.32 01-FEB-00:10 162.52 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 39.77 11-FEB-14:00 106.81 04-FEB-07:00
March 220.32 01-MAR-00:10 162.52 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 41.54 13-MAR-16:00 96.55 16-MAR-05:00
April 220.32 01-APR-00:10 162.52 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 54.06 17-APR-15:00 52.50 02-APR-05:00
May 220.32 01-MAY-00:10 162.52 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 65.27 22-MAY-13:00 16.17 07-MAY-05:15
June 220.32 01-JUN-00:10 162.52 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 50.78 11-JUN-13:00 4.87 05-JUN-15:00
July 220.32 01-JUL-00:10 162.52 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 69.09 29-JUL-16:00 7.33 14-JUL-21:51
August 220.32 01-AUG-00:10 162.52 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 61.01 23-AUG-13:00 7.01 12-AUG-06:53
September 220.32 01-SEP-00:10 162.52 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 52.55 13-SEP-13:00 7.61 05-SEP-06:00
October 220.32 01-OCT-23:10 162.52 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 54.27 14-OCT-13:00 12.20 28-OCT-03:00
November 220.32 01-NOV-00:10 162.52 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 42.36 17-NOV-15:00 78.95 27-NOV-03:00
December 220.32 01-DEC-00:10 162.52 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 35.05 10-DEC-14:40 90.94 15-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   162.52   242.16   0.00 0.00 0.00 0.00 35.05   4.87  
Maximum of Months 220.32   162.52   242.16   0.00 0.00 0.00 0.00 69.09   106.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 302.47 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 70.93 02-JAN-14:00 226.65 25-JAN-07:00
February 907.20 01-FEB-00:10 302.47 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 78.10 11-FEB-14:00 300.17 04-FEB-07:00
March 907.20 01-MAR-00:10 302.47 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 77.37 13-MAR-16:00 270.40 16-MAR-07:00
April 907.20 01-APR-00:10 302.47 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 116.40 17-APR-15:00 145.52 02-APR-06:00
May 907.20 01-MAY-00:10 302.47 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 146.87 22-MAY-13:00 50.57 01-MAY-06:00
June 907.20 01-JUN-00:10 302.47 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 117.25 11-JUN-13:00 17.71 05-JUN-15:00
July 907.20 01-JUL-00:10 302.47 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 162.92 29-JUL-16:00 17.80 14-JUL-22:03
August 907.20 01-AUG-00:10 302.47 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 140.70 23-AUG-13:00 26.72 28-AUG-12:00
September 907.20 01-SEP-00:10 302.47 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 116.92 13-SEP-13:00 26.53 05-SEP-06:00
October 907.20 01-OCT-23:10 302.47 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 116.88 09-OCT-11:00 42.86 28-OCT-03:00
November 907.20 01-NOV-00:10 302.47 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 86.11 17-NOV-15:00 215.98 27-NOV-07:00
December 907.20 01-DEC-00:10 302.47 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 70.33 10-DEC-14:30 253.01 15-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   302.47   4572.80   39726.58   0.00 0.00 0.00 70.33   17.71  
Maximum of Months 907.20   302.47   4572.80   39726.58   0.00 0.00 0.00 162.92   300.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 810.33 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 152.05 07-JAN-13:00 354.64 25-JAN-05:10
February 15368.40 01-FEB-00:10 810.33 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 164.28 02-FEB-14:00 450.82 04-FEB-07:00
March 15368.40 01-MAR-00:10 810.33 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 169.03 13-MAR-16:00 424.26 16-MAR-05:00
April 15368.40 01-APR-00:10 810.33 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 245.78 17-APR-15:00 210.48 02-APR-05:10
May 15368.40 01-MAY-00:10 810.33 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 310.51 22-MAY-13:00 57.36 01-MAY-05:00
June 15368.40 01-JUN-00:10 810.33 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 259.47 11-JUN-13:00 10.75 05-JUN-22:00
July 15368.40 01-JUL-00:10 810.33 03-JUL-19:19 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 330.07 29-JUL-16:00 22.84 14-JUL-22:00
August 15368.40 01-AUG-00:10 810.33 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 286.64 08-AUG-10:50 18.10 14-AUG-03:00
September 15368.40 01-SEP-00:10 810.33 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 245.29 14-SEP-10:50 18.17 04-SEP-22:00
October 15368.40 01-OCT-23:10 810.33 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 239.92 09-OCT-11:00 53.83 28-OCT-03:00
November 15368.40 01-NOV-00:10 810.33 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 168.12 17-NOV-15:00 345.51 27-NOV-03:00
December 15368.40 01-DEC-00:10 810.33 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 138.84 10-DEC-15:00 402.86 15-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   810.33   965.27   0.00 0.00 0.00 0.00 138.84   10.75  
Maximum of Months 15368.40   810.33   965.27   0.00 0.00 0.00 0.00 330.07   450.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 6817.32 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 440.72 02-JAN-14:40 1070.39 25-JAN-05:30
February 45622.98 01-FEB-00:10 6817.32 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 455.47 11-FEB-14:00 1386.91 04-FEB-07:00
March 45622.98 01-MAR-00:10 6817.32 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 473.54 13-MAR-16:00 1282.56 16-MAR-05:00
April 45622.98 01-APR-00:10 6817.32 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 667.97 17-APR-15:00 686.97 02-APR-05:30
May 45622.98 01-MAY-00:10 6817.32 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 828.32 22-MAY-13:00 227.24 07-MAY-05:40
June 45622.98 01-JUN-00:10 6817.32 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 667.39 11-JUN-13:00 52.38 05-JUN-22:00
July 45622.98 01-JUL-00:10 6817.32 03-JUL-19:19 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 886.92 29-JUL-16:00 90.21 14-JUL-21:54
August 45622.98 01-AUG-00:10 6817.32 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 777.35 23-AUG-13:00 89.98 14-AUG-03:00
September 45622.98 01-SEP-00:10 6817.32 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 664.32 13-SEP-13:00 124.71 05-SEP-06:00
October 45622.98 01-OCT-23:10 6817.32 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 660.62 09-OCT-11:00 206.91 28-OCT-03:00
November 45622.98 01-NOV-00:10 6817.32 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 499.79 17-NOV-15:00 1045.69 27-NOV-03:00
December 45622.98 01-DEC-00:10 6817.32 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 415.97 10-DEC-14:50 1216.28 15-DEC-05:30
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   6817.32   10029.21   0.00 0.00 0.00 0.00 415.97   52.38  
Maximum of Months 45622.98   6817.32   10029.21   0.00 0.00 0.00 0.00 886.92   1386.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.45 23-JAN-16:17 85.03 25-JAN-07:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 43.71 11-FEB-16:20 118.92 04-FEB-07:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 55.06 13-MAR-16:00 107.67 16-MAR-07:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 71.99 17-APR-15:20 47.71 02-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 11.55 10-MAY-15:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 3.97 05-JUN-15:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 3.98 14-JUL-17:40
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.39 21-AUG-16:00 8.14 28-AUG-12:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 73.36 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 11.54 26-OCT-14:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 51.80 17-NOV-16:20 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 45.49 10-DEC-16:20 97.18 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 37.45   0.00  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 94.53   118.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.45 23-JAN-16:50 85.02 25-JAN-07:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 43.71 11-FEB-16:20 118.91 04-FEB-07:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 107.41 16-MAR-07:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 71.98 17-APR-15:20 47.70 02-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 13.51 01-MAY-05:50
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 4.91 21-JUN-17:50
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 15.56 02-JUL-18:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 9.97 12-AUG-07:30
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 73.35 20-SEP-16:00 7.68 04-SEP-21:50
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 14.76 01-OCT-08:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 51.80 17-NOV-16:18 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 45.48 10-DEC-16:18 97.18 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 37.45   4.91  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 94.53   118.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 59.53 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 4.12 02-JAN-14:00 34.94 25-JAN-07:00
February 0.00 01-FEB-00:10 59.53 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 5.06 11-FEB-14:00 43.51 04-FEB-07:00
March 0.00 01-MAR-00:10 59.53 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 5.01 13-MAR-16:00 40.66 16-MAR-06:55
April 0.00 01-APR-00:10 59.53 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 10.13 17-APR-15:00 24.26 02-APR-06:00
May 0.00 01-MAY-00:10 59.53 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 14.12 22-MAY-13:00 11.81 01-MAY-06:00
June 0.00 01-JUN-00:10 59.53 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 10.20 11-JUN-13:00 7.07 05-JUN-15:00
July 0.00 01-JUL-00:10 59.53 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 16.23 29-JUL-16:00 7.52 14-JUL-21:51
August 0.00 01-AUG-00:10 59.53 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 13.28 23-AUG-13:00 8.70 28-AUG-12:00
September 0.00 01-SEP-00:10 59.53 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 10.17 13-SEP-13:00 8.63 05-SEP-06:00
October 0.00 01-OCT-00:10 59.53 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 10.17 09-OCT-11:00 10.78 28-OCT-04:00
November 0.00 01-NOV-00:10 59.53 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 6.14 17-NOV-15:00 33.51 27-NOV-07:00
December 0.00 01-DEC-00:10 59.53 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 4.08 10-DEC-14:10 38.40 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 4.08   7.07  
Maximum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 16.23   43.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 12.24 02-JAN-14:00 23.94 25-JAN-08:00
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 12.46 11-FEB-14:00 33.19 04-FEB-07:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 15.37 13-MAR-16:00 30.74 16-MAR-07:10
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 20.09 17-APR-15:20 13.31 02-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 22.33 29-MAY-16:00 3.96 01-MAY-05:50
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 19.63 10-JUN-16:00 1.11 05-JUN-15:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 26.38 29-JUL-16:00 2.90 14-JUL-18:00
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 20.48 21-AUG-16:00 2.20 12-AUG-07:30
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 20.47 20-SEP-16:00 0.95 04-SEP-21:50
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 19.51 14-OCT-16:00 3.13 26-OCT-14:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 14.46 17-NOV-16:20 22.38 27-NOV-07:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 12.70 10-DEC-16:18 27.45 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 12.24   0.95  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 26.38   33.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.45 23-JAN-16:50 89.80 25-JAN-08:10
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 43.71 11-FEB-16:20 118.92 04-FEB-07:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 55.06 13-MAR-16:00 110.40 16-MAR-07:10
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 71.99 17-APR-15:20 47.71 02-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 11.55 10-MAY-15:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 3.97 05-JUN-15:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 3.98 14-JUL-17:40
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.39 21-AUG-16:00 8.14 28-AUG-12:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 73.36 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 11.54 26-OCT-14:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 51.80 17-NOV-16:18 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 45.49 10-DEC-16:18 97.18 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 37.45   0.00  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 94.53   118.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.45 23-JAN-16:50 86.56 25-JAN-08:10
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 43.71 11-FEB-16:20 118.91 04-FEB-07:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 109.62 16-MAR-07:10
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 71.98 17-APR-15:20 47.70 02-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 16.53 01-MAY-07:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 7.64 13-JUN-07:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 17.05 14-JUL-18:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 9.91 12-AUG-07:30
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 73.35 20-SEP-16:00 7.92 04-SEP-21:50
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 14.51 01-OCT-08:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 51.80 17-NOV-16:20 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 45.49 10-DEC-16:20 97.18 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 37.45   7.64  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 94.53   118.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1116.11 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 45.94 02-JAN-14:05 111.62 25-JAN-05:00
February 2263.36 01-FEB-00:10 1116.11 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 51.95 11-FEB-14:00 149.57 04-FEB-07:00
March 2263.36 01-MAR-00:10 1116.11 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 51.69 13-MAR-16:00 138.91 16-MAR-05:00
April 2263.36 01-APR-00:10 1116.11 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 69.79 17-APR-15:00 74.67 02-APR-05:00
May 2263.36 01-MAY-00:10 1116.11 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 87.15 22-MAY-13:00 22.79 07-MAY-05:15
June 2263.36 01-JUN-00:10 1116.11 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 68.78 11-JUN-13:00 6.25 05-JUN-15:00
July 2263.36 01-JUL-00:10 1116.11 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 92.83 29-JUL-16:00 10.24 14-JUL-21:51
August 2263.36 01-AUG-00:10 1116.11 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 80.75 23-AUG-13:00 10.40 12-AUG-06:53
September 2263.36 01-SEP-00:10 1116.11 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 68.83 08-SEP-15:00 11.55 05-SEP-06:00
October 2263.36 01-OCT-23:10 1116.11 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 68.89 14-OCT-13:00 20.44 28-OCT-03:00
November 2263.36 01-NOV-00:10 1116.11 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 54.98 17-NOV-15:00 112.87 27-NOV-03:00
December 2263.36 01-DEC-00:10 1116.11 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 43.09 10-DEC-14:00 130.66 15-DEC-05:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1116.11   0.00 0.00 0.00 0.00 0.00 43.09   6.25  
Maximum of Months 2263.36   1116.11   0.00 0.00 0.00 0.00 0.00 92.83   149.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.06 23-JAN-16:20 85.47 25-JAN-07:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 43.25 11-FEB-16:20 119.38 04-FEB-07:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 54.66 13-MAR-16:00 105.71 16-MAR-06:50
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 71.61 17-APR-15:20 48.14 02-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 79.65 29-MAY-16:00 11.97 10-MAY-15:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 69.95 10-JUN-16:00 4.38 05-JUN-15:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.16 29-JUL-16:00 4.40 14-JUL-17:50
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.00 21-AUG-16:00 8.55 28-AUG-12:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 72.97 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.52 14-OCT-16:00 11.95 26-OCT-14:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 51.41 17-NOV-16:20 80.62 27-NOV-07:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 45.10 10-DEC-16:20 97.63 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 37.06   0.00  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 94.16   119.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.05 23-JAN-16:50 85.47 25-JAN-07:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 43.31 11-FEB-16:20 119.37 04-FEB-07:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 54.67 13-MAR-16:00 105.70 16-MAR-06:50
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 71.60 17-APR-15:20 48.67 18-APR-21:50
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 79.63 29-MAY-16:00 11.96 10-MAY-15:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 69.94 10-JUN-16:00 9.60 21-JUN-17:50
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.15 29-JUL-16:00 20.69 14-JUL-18:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.00 21-AUG-16:00 9.29 05-AUG-18:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 72.97 20-SEP-16:00 9.60 04-SEP-21:50
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.52 14-OCT-16:00 14.24 01-OCT-08:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 51.41 17-NOV-16:20 80.62 27-NOV-07:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 45.09 10-DEC-16:20 97.63 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 37.05   9.29  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 94.15   119.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 18.95 23-JAN-17:00 44.56 25-JAN-08:10
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 20.57 11-FEB-14:00 61.08 04-FEB-07:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 27.97 13-MAR-16:00 54.99 16-MAR-07:00
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 36.61 17-APR-15:20 24.63 02-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 40.75 29-MAY-16:00 6.12 10-MAY-15:00
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 35.79 10-JUN-16:00 2.24 05-JUN-15:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 48.16 29-JUL-16:00 2.25 14-JUL-17:40
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 37.35 21-AUG-16:00 4.38 28-AUG-12:00
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 37.23 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 35.46 14-OCT-16:00 6.12 26-OCT-14:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 25.12 17-NOV-16:20 41.25 27-NOV-07:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 21.91 10-DEC-16:20 49.95 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 18.95   0.00  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 48.16   61.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 1423.01 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 121.53 02-JAN-14:30 233.96 25-JAN-05:10
February 26988.77 01-FEB-00:10 1423.01 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 116.10 11-FEB-14:00 310.55 04-FEB-07:00
March 26988.77 01-MAR-00:10 1423.01 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 113.24 13-MAR-16:00 283.00 16-MAR-05:00
April 26988.77 01-APR-00:10 1423.01 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 158.18 17-APR-15:00 148.32 02-APR-05:30
May 26988.77 01-MAY-00:10 1423.01 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 196.10 22-MAY-13:00 47.68 01-MAY-05:00
June 26988.77 01-JUN-00:10 1423.01 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 160.14 11-JUN-13:00 13.41 05-JUN-22:00
July 26988.77 01-JUL-00:10 1423.01 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 211.83 29-JUL-16:00 21.95 14-JUL-21:54
August 26988.77 01-AUG-00:10 1423.01 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 189.18 23-AUG-13:00 17.28 14-AUG-03:00
September 26988.77 01-SEP-00:10 1423.01 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 164.61 13-SEP-13:00 22.62 05-SEP-06:00
October 26988.77 01-OCT-23:10 1423.01 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 164.55 09-OCT-11:00 41.68 28-OCT-03:00
November 26988.77 01-NOV-00:10 1423.01 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 130.77 17-NOV-15:00 226.34 27-NOV-03:00
December 26988.77 01-DEC-00:10 1423.01 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 115.03 10-DEC-15:00 266.07 15-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   1423.01   6747.90   0.00 0.00 0.00 0.00 113.24   13.41  
Maximum of Months 26988.77   1423.01   6747.90   0.00 0.00 0.00 0.00 211.83   310.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 1423.01 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 117.94 02-JAN-14:30 237.39 25-JAN-05:10
February 26988.77 01-FEB-00:10 1423.01 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 112.12 11-FEB-14:00 315.11 04-FEB-07:00
March 26988.77 01-MAR-00:10 1423.01 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 109.28 13-MAR-16:00 286.52 16-MAR-05:00
April 26988.77 01-APR-00:10 1423.01 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 154.32 17-APR-15:00 151.12 02-APR-06:00
May 26988.77 01-MAY-00:10 1423.01 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 191.96 22-MAY-13:00 50.57 01-MAY-05:00
June 26988.77 01-JUN-00:10 1423.01 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 155.62 11-JUN-13:00 13.41 05-JUN-22:00
July 26988.77 01-JUL-00:10 1423.01 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 207.33 29-JUL-16:00 21.95 14-JUL-21:54
August 26988.77 01-AUG-00:10 1423.01 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 185.02 23-AUG-13:00 20.62 12-AUG-06:53
September 26988.77 01-SEP-00:10 1423.01 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 160.57 13-SEP-13:00 25.85 05-SEP-06:00
October 26988.77 01-OCT-23:10 1423.01 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 160.24 09-OCT-11:00 44.51 28-OCT-03:00
November 26988.77 01-NOV-00:10 1423.01 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 127.21 17-NOV-15:00 229.29 27-NOV-03:00
December 26988.77 01-DEC-00:10 1423.01 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 111.31 10-DEC-15:00 269.19 15-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   1423.01   6747.90   0.00 0.00 0.00 0.00 109.28   13.41  
Maximum of Months 26988.77   1423.01   6747.90   0.00 0.00 0.00 0.00 207.33   315.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 747.41 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 70.91 02-JAN-14:00 232.38 25-JAN-07:00
February 2401.70 01-FEB-00:10 747.41 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 78.22 11-FEB-14:00 307.31 04-FEB-07:00
March 2401.70 01-MAR-00:10 747.41 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 77.55 13-MAR-16:00 276.99 16-MAR-07:00
April 2401.70 01-APR-00:10 747.41 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 117.26 17-APR-15:00 149.76 02-APR-05:00
May 2401.70 01-MAY-00:10 747.41 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 148.30 22-MAY-13:00 52.96 01-MAY-05:25
June 2401.70 01-JUN-00:10 747.41 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 118.12 11-JUN-13:00 19.42 05-JUN-15:00
July 2401.70 01-JUL-00:10 747.41 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 164.73 29-JUL-16:00 19.75 14-JUL-22:40
August 2401.70 01-AUG-00:10 747.41 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 142.02 23-AUG-13:00 28.67 12-AUG-08:58
September 2401.70 01-SEP-00:10 747.41 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 117.81 20-SEP-16:00 28.44 05-SEP-06:00
October 2401.70 01-OCT-23:10 747.41 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 117.77 09-OCT-11:00 45.16 28-OCT-03:00
November 2401.70 01-NOV-00:10 747.41 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 86.36 17-NOV-15:00 221.51 27-NOV-07:00
December 2401.70 01-DEC-00:10 747.41 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 70.30 10-DEC-14:00 259.25 15-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   747.41   14604.56   22492.83   0.00 0.00 0.00 70.30   19.42  
Maximum of Months 2401.70   747.41   14604.56   22492.83   0.00 0.00 0.00 164.73   307.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1181.23 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 69.25 02-JAN-14:00 199.40 25-JAN-05:00
February 2395.44 01-FEB-00:10 1181.23 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 76.40 11-FEB-14:00 257.59 04-FEB-07:00
March 2395.44 01-MAR-00:10 1181.23 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 75.68 13-MAR-16:00 240.64 16-MAR-05:00
April 2395.44 01-APR-00:10 1181.23 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 114.62 17-APR-15:00 139.74 02-APR-05:00
May 2395.44 01-MAY-00:10 1181.23 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 145.00 22-MAY-13:00 51.18 07-MAY-06:00
June 2395.44 01-JUN-00:10 1181.23 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 115.45 11-JUN-13:00 19.16 05-JUN-15:00
July 2395.44 01-JUL-00:10 1181.23 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 161.01 29-JUL-16:00 19.25 14-JUL-21:52
August 2395.44 01-AUG-00:10 1181.23 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 138.84 23-AUG-13:00 28.10 12-AUG-08:52
September 2395.44 01-SEP-00:10 1181.23 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 115.13 13-SEP-13:00 27.95 05-SEP-06:00
October 2395.44 01-OCT-23:10 1181.23 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 115.12 09-OCT-11:00 44.25 28-OCT-03:00
November 2395.44 01-NOV-00:10 1181.23 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 84.40 17-NOV-15:00 203.44 27-NOV-03:00
December 2395.44 01-DEC-00:10 1181.23 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 68.66 10-DEC-14:00 232.80 15-DEC-05:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1181.23   0.00 0.00 0.00 0.00 0.00 68.66   19.16  
Maximum of Months 2395.44   1181.23   0.00 0.00 0.00 0.00 0.00 161.01   257.59  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 19494.96 03-JAN-22:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
February 17395.63 17-FEB-22:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
March 15874.47 30-MAR-18:10 53675.50 40328.28 54753.33 0.00 0.00 0.00 0.00 0.00 0.00
April 16353.21 15-APR-18:10 46007.57 35287.33 48669.62 0.00 0.00 0.00 0.00 0.00 0.00
May 16837.19 19-MAY-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
June 18038.01 30-JUN-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
July 19405.76 28-JUL-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
August 20816.92 18-AUG-18:05 53675.50 40328.28 54753.33 0.00 0.00 0.00 0.00 0.00 0.00
September 21792.44 22-SEP-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
October 21570.90 25-OCT-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 21455.64 22-NOV-22:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
December 20769.33 08-DEC-22:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 15874.47   10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21792.44   53675.50 40328.28 54753.33 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3287.70 02-JAN-14:30 259.90 95.05 252.59 0.00 0.00 0.00 0.00 56.93 0.00
February 3263.88 11-FEB-14:30 389.84 95.05 252.59 0.00 0.00 0.00 0.00 56.41 0.00
March 2491.05 27-MAR-19:10 909.64 342.20 685.60 0.00 0.00 0.00 0.00 16.43 0.00
April 2783.44 15-APR-18:03 4678.13 1596.91 3464.10 0.00 0.00 0.00 0.00 66.86 0.00
May 2695.67 19-MAY-18:20 1819.27 608.35 1299.04 0.00 0.00 0.00 0.00 45.73 0.00
June 2890.68 29-JUN-18:15 1819.27 608.35 1299.04 0.00 0.00 0.00 0.00 69.20 0.00
July 3168.96 29-JUL-18:03 4678.13 1596.91 3464.10 0.00 0.00 0.00 0.00 103.73 0.00
August 3048.77 31-AUG-18:15 1819.27 608.35 1299.04 0.00 0.00 0.00 0.00 58.42 0.00
September 3356.01 30-SEP-14:00 389.84 95.05 252.59 0.00 0.00 0.00 0.00 81.58 0.00
October 3504.84 25-OCT-14:30 389.84 95.05 252.59 0.00 0.00 0.00 0.00 68.97 0.00
November 3508.42 07-NOV-14:00 259.90 95.05 252.59 0.00 0.00 0.00 0.00 49.66 0.00
December 3521.30 09-DEC-12:30 389.84 95.05 252.59 0.00 0.00 0.00 0.00 37.29 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2491.05   259.90 95.05 252.59 0.00 0.00 0.00 0.00 16.43 0.00
Maximum of Months 3521.30   4678.13 1596.91 3464.10 0.00 0.00 0.00 0.00 103.73 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1690.28 03-JAN-22:00 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 0.00 8.29
February 1726.30 11-FEB-21:20 1053.36 308.21 668.57 0.00 0.00 0.00 0.00 0.00 9.08
March 2028.60 28-MAR-20:25 2407.68 704.47 1504.29 0.00 0.00 0.00 0.00 0.67 0.00
April 2308.94 13-APR-20:10 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 7.25 0.00
May 2380.68 17-MAY-20:10 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 11.73 0.00
June 2481.33 09-JUN-20:30 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 24.14 0.00
July 2492.24 28-JUL-20:10 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 19.98 0.00
August 2478.49 17-AUG-20:10 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 18.96 0.00
September 2418.91 01-SEP-20:10 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 21.91 0.00
October 2327.94 06-OCT-20:10 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 12.13 0.00
November 2019.81 07-NOV-21:10 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 4.06 0.00
December 1914.74 08-DEC-21:10 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 1.43 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1690.28   1053.36 308.21 668.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2492.24   2407.68 704.47 1504.29 0.00 0.00 0.00 0.00 24.14 9.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1385.02 03-JAN-21:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 0.00 13.04
February 1531.75 17-FEB-21:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 0.00 1.11
March 1588.79 28-MAR-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 0.00 1.11
April 2080.89 14-APR-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 22.36 0.00
May 2479.42 22-MAY-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 45.42 0.00
June 2774.62 29-JUN-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 51.80 0.00
July 2822.58 28-JUL-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 45.30 0.00
August 2611.19 18-AUG-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 51.89 0.00
September 2582.51 22-SEP-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 45.63 0.00
October 2242.42 03-OCT-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 40.12 0.00
November 1944.62 03-NOV-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 22.35 0.00
December 1664.77 01-DEC-20:50 222.77 708.98 839.45 0.00 0.00 0.00 0.00 0.00 22.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1385.02   222.77 708.98 839.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2822.58   222.77 708.98 839.45 0.00 0.00 0.00 0.00 51.89 22.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 960.95 01-JAN-11:35 146.88 108.35 203.92 0.00 0.00 0.00 0.00 22.91 0.00
February 989.56 11-FEB-19:10 881.28 758.41 1223.53 0.00 0.00 0.00 0.00 2.71 0.00
March 997.10 30-MAR-18:10 1028.16 866.74 1376.47 0.00 0.00 0.00 0.00 11.64 0.00
April 1085.70 15-APR-17:50 146.88 108.34 178.43 0.00 0.00 0.00 0.00 42.04 0.00
May 1123.39 22-MAY-18:10 1028.16 866.74 1376.47 0.00 0.00 0.00 0.00 40.72 0.00
June 1232.45 29-JUN-20:10 195.84 144.46 229.41 0.00 0.00 0.00 0.00 29.88 0.00
July 1296.17 29-JUL-19:00 146.88 126.40 203.92 0.00 0.00 0.00 0.00 49.26 0.00
August 1155.45 19-AUG-18:00 146.88 108.34 178.43 0.00 0.00 0.00 0.00 33.35 0.00
September 1141.52 09-SEP-18:00 146.88 108.34 178.43 0.00 0.00 0.00 0.00 37.51 0.00
October 1090.28 07-OCT-10:35 146.88 90.28 178.43 0.00 0.00 0.00 0.00 47.37 0.00
November 1029.66 04-NOV-18:00 146.88 108.34 178.43 0.00 0.00 0.00 0.00 20.58 0.00
December 1024.87 09-DEC-11:35 146.88 90.28 178.43 0.00 0.00 0.00 0.00 25.37 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 960.95   146.88 90.28 178.43 0.00 0.00 0.00 0.00 2.71 0.00
Maximum of Months 1296.17   1028.16 866.74 1376.47 0.00 0.00 0.00 0.00 49.26 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 35156.93 02-JAN-21:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 26.72
February 35087.16 17-FEB-21:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 1.51
March 35817.64 27-MAR-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 5.84 0.00
April 36566.54 14-APR-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 30.53 0.00
May 36778.23 31-MAY-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 55.09 0.00
June 37061.50 09-JUN-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 77.89 0.00
July 37391.52 28-JUL-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 61.86 0.00
August 36961.49 31-AUG-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 55.20 0.00
September 36886.46 08-SEP-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 94.54 0.00
October 36548.47 06-OCT-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 39.15 0.00
November 35810.74 03-NOV-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 30.52 0.00
December 35430.48 08-DEC-21:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 5.84 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 35087.16   705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37391.52   705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 94.54 26.72



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11719.58 02-JAN-11:35 6830.40 99.04 711.25 0.00 0.00 0.00 0.00 97.35 0.00
February 11655.89 11-FEB-11:35 10245.60 99.04 711.25 0.00 0.00 0.00 0.00 122.87 0.00
March 11498.79 04-MAR-11:35 10245.60 99.04 711.25 0.00 0.00 0.00 0.00 111.05 0.00
April 11843.77 15-APR-17:30 10245.60 118.85 711.25 0.00 0.00 0.00 0.00 208.82 0.00
May 11783.05 22-MAY-18:10 71719.20 1683.77 5486.82 0.00 0.00 0.00 0.00 199.31 0.00
June 11941.76 29-JUN-18:10 71719.20 950.79 5486.82 0.00 0.00 0.00 0.00 187.34 0.00
July 12423.34 29-JUL-17:20 20491.20 237.70 1422.51 0.00 0.00 0.00 0.00 282.21 0.00
August 12215.41 31-AUG-18:10 71719.20 1927.17 5486.82 0.00 0.00 0.00 0.00 162.87 0.00
September 12409.20 30-SEP-17:15 20491.20 454.74 1422.51 0.00 0.00 0.00 0.00 180.73 0.00
October 12442.77 25-OCT-15:10 17076.00 99.04 711.25 0.00 0.00 0.00 0.00 137.17 0.00
November 12316.86 07-NOV-11:35 6830.40 99.04 711.25 0.00 0.00 0.00 0.00 95.10 0.00
December 12556.38 09-DEC-11:35 10245.60 99.04 711.25 0.00 0.00 0.00 0.00 95.28 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11498.79   6830.40 99.04 711.25 0.00 0.00 0.00 0.00 95.10 0.00
Maximum of Months 12556.38   71719.20 1927.17 5486.82 0.00 0.00 0.00 0.00 282.21 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 34904.64 03-JAN-22:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 0.00 141.86
February 34372.53 11-FEB-19:10 182491.92 31814.15 50673.90 0.00 0.00 0.00 0.00 0.00 7.70
March 34836.12 30-MAR-21:10 91245.96 9089.76 14779.89 0.00 0.00 0.00 0.00 0.00 7.63
April 37895.20 14-APR-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 110.85 0.00
May 39142.56 22-MAY-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 271.19 0.00
June 41452.50 29-JUN-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 358.75 0.00
July 42328.33 28-JUL-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 386.73 0.00
August 41623.45 21-AUG-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 309.15 0.00
September 42169.39 18-SEP-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 315.75 0.00
October 40534.52 06-OCT-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 198.81 0.00
November 38666.35 03-NOV-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 198.67 0.00
December 37429.48 08-DEC-22:05 182491.92 18179.51 29559.77 0.00 0.00 0.00 0.00 0.00 1.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 34372.53   45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 42328.33   182491.92 31814.15 50673.90 0.00 0.00 0.00 0.00 386.73 141.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2729.56 25-JAN-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 33.63
February 2701.69 03-FEB-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 45.25
March 2743.79 15-MAR-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 36.71
April 2580.08 01-APR-18:02 702.00 568.30 726.98 0.00 0.00 0.00 0.00 28.20 0.00
May 2591.25 29-MAY-15:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 67.19 0.00
June 2597.41 30-JUN-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 48.29 0.00
July 2589.98 25-JUL-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 47.81 0.00
August 2591.63 17-AUG-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 47.17 0.00
September 2582.95 01-SEP-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 47.73 0.00
October 2591.69 06-OCT-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 32.81 0.00
November 2583.51 03-NOV-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 37.51 0.00
December 2729.17 20-DEC-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 55.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2580.08   324.00 159.12 300.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2743.79   831.60 568.30 726.98 0.00 0.00 0.00 0.00 67.19 55.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2683.42 24-JAN-19:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 61.19
February 2604.72 19-FEB-16:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 28.80 0.00
March 2716.91 15-MAR-20:11 1121.40 590.02 1272.07 0.00 0.00 0.00 0.00 0.00 54.24
April 2664.16 18-APR-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 41.14
May 2613.53 11-MAY-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 43.48 0.00
June 2619.88 13-JUN-18:11 1386.00 842.88 1211.49 0.00 0.00 0.00 0.00 6.88 0.00
July 2614.61 22-JUL-15:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 60.42 0.00
August 2608.59 16-AUG-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 56.73 0.00
September 2611.66 01-SEP-18:02 831.60 505.73 726.90 0.00 0.00 0.00 0.00 47.90 0.00
October 2623.44 06-OCT-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 43.21 0.00
November 2565.57 17-NOV-16:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 41.54 0.00
December 2729.35 20-DEC-16:11 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 54.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2565.57   324.00 159.11 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2729.35   1800.00 842.88 1272.07 0.00 0.00 0.00 0.00 60.42 61.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 473.51 02-JAN-14:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 4.12 0.00
February 403.12 11-FEB-14:30 0.00 19.64 33.54 0.00 0.00 0.00 0.00 4.03 0.00
March 345.11 02-MAR-14:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 3.27
April 292.73 15-APR-20:10 0.00 59.53 178.01 0.00 0.00 0.00 0.00 0.00 0.37
May 283.23 14-MAY-08:00 0.00 33.33 232.19 0.00 0.00 0.00 0.00 0.92 0.00
June 294.79 29-JUN-20:30 0.00 52.98 178.01 0.00 0.00 0.00 0.00 4.11 0.00
July 314.22 29-JUL-19:10 0.00 59.53 159.95 0.00 0.00 0.00 0.00 8.96 0.00
August 315.72 31-AUG-20:20 0.00 52.98 178.01 0.00 0.00 0.00 0.00 2.05 0.00
September 382.37 30-SEP-14:00 0.00 19.64 33.54 0.00 0.00 0.00 0.00 8.17 0.00
October 445.78 25-OCT-14:20 0.00 16.67 30.96 0.00 0.00 0.00 0.00 6.49 0.00
November 477.56 07-NOV-14:00 0.00 16.67 30.96 0.00 0.00 0.00 0.00 2.97 0.00
December 485.65 03-DEC-14:05 0.00 39.29 67.08 0.00 0.00 0.00 0.00 0.00 4.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 283.23   0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 485.65   0.00 59.53 232.19 0.00 0.00 0.00 0.00 8.96 4.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 990.63 24-JAN-19:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 16.85
February 997.37 03-FEB-19:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 0.00 18.52
March 1011.72 14-MAR-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 2.26 0.00
April 994.73 17-APR-18:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 13.25 0.00
May 998.57 17-MAY-08:61 252.00 183.39 776.76 0.00 0.00 0.00 0.00 8.46 0.00
June 997.92 17-JUN-08:62 324.00 200.06 959.99 0.00 0.00 0.00 0.00 7.59 0.00
July 992.91 29-JUL-18:02 702.00 357.25 712.25 0.00 0.00 0.00 0.00 18.80 0.00
August 987.89 11-AUG-08:61 252.00 183.39 776.76 0.00 0.00 0.00 0.00 12.16 0.00
September 986.94 01-SEP-08:61 252.00 183.39 776.76 0.00 0.00 0.00 0.00 9.71 0.00
October 983.32 17-OCT-18:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 4.95 0.00
November 1001.38 15-NOV-19:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 2.45 0.00
December 977.57 20-DEC-19:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 0.00 18.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 977.57   252.00 183.39 712.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1011.72   970.20 370.95 959.99 0.00 0.00 0.00 0.00 18.80 18.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2484.51 25-JAN-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 33.39
February 2425.74 03-FEB-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 43.64
March 2505.76 16-MAR-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 27.66
April 2365.59 11-APR-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 39.95 0.00
May 2374.53 20-MAY-08:62 324.00 318.25 979.84 0.00 0.00 0.00 0.00 34.15 0.00
June 2372.32 14-JUN-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 50.91 0.00
July 2379.15 22-JUL-15:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 60.36 0.00
August 2377.09 22-AUG-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 36.95 0.00
September 2372.74 09-SEP-15:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 52.05 0.00
October 2377.00 12-OCT-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 43.39 0.00
November 2362.96 15-NOV-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 21.41 0.00
December 2479.79 20-DEC-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 55.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2362.96   324.00 159.12 300.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2505.76   680.40 318.25 979.84 0.00 0.00 0.00 0.00 60.36 55.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2376.61 24-JAN-19:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 58.44
February 2524.68 28-FEB-09:51 324.00 375.03 1019.23 0.00 0.00 0.00 0.00 2.40 0.00
March 2464.63 01-MAR-09:51 288.00 333.36 905.99 0.00 0.00 0.00 0.00 0.00 29.69
April 2550.34 20-APR-08:51 324.00 375.03 1019.23 0.00 0.00 0.00 0.00 2.74 0.00
May 2390.20 18-MAY-08:61 252.00 291.69 792.74 0.00 0.00 0.00 0.00 33.86 0.00
June 2420.96 13-JUN-18:11 1386.00 842.88 1211.49 0.00 0.00 0.00 0.00 6.35 0.00
July 2397.99 22-JUL-15:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 60.39 0.00
August 2386.83 30-AUG-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 47.00 0.00
September 2384.39 24-SEP-15:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 52.21 0.00
October 2384.01 17-OCT-08:61 324.00 375.03 1019.23 0.00 0.00 0.00 0.00 8.30 0.00
November 2319.14 19-NOV-19:01 819.00 662.94 848.04 0.00 0.00 0.00 0.00 19.41 0.00
December 2302.80 20-DEC-16:11 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 47.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2302.80   252.00 159.11 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2550.34   1386.00 842.88 1211.49 0.00 0.00 0.00 0.00 60.39 58.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2100.87 02-JAN-19:10 10562.33 5952.60 0.00 0.00 0.00 0.00 0.00 0.00 1.91
February 2057.97 11-FEB-18:40 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 9.49 0.00
March 2123.56 30-MAR-18:10 10562.33 5952.60 0.00 0.00 0.00 0.00 0.00 12.48 0.00
April 2284.91 15-APR-17:50 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 53.85 0.00
May 2292.51 22-MAY-18:10 10562.33 5952.60 0.00 0.00 0.00 0.00 0.00 54.67 0.00
June 2351.85 11-JUN-10:35 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 58.98 0.00
July 2435.00 29-JUL-17:50 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 75.96 0.00
August 2366.05 21-AUG-18:08 10562.33 5952.60 0.00 0.00 0.00 0.00 0.00 44.12 0.00
September 2454.74 22-SEP-21:10 2263.36 744.08 0.00 0.00 0.00 0.00 0.00 34.80 0.00
October 2315.05 07-OCT-10:35 1508.90 620.06 0.00 0.00 0.00 0.00 0.00 60.19 0.00
November 2218.73 08-NOV-19:10 10562.33 5952.60 0.00 0.00 0.00 0.00 0.00 19.59 0.00
December 2194.92 09-DEC-11:35 1508.90 620.06 0.00 0.00 0.00 0.00 0.00 30.28 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2057.97   1508.90 620.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2454.74   10562.33 5952.60 0.00 0.00 0.00 0.00 0.00 75.96 1.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2979.06 25-JAN-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 33.80
February 2951.21 03-FEB-16:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 45.53
March 2994.24 15-MAR-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 36.86
April 2807.08 20-APR-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 3.19 0.00
May 2790.18 07-MAY-15:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 24.73 0.00
June 2831.06 08-JUN-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 47.50 0.00
July 2820.28 12-JUL-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 41.19 0.00
August 2820.19 05-AUG-15:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 45.71 0.00
September 2847.84 30-SEP-15:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 53.98 0.00
October 2797.10 16-OCT-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 25.90 0.00
November 2787.22 07-NOV-16:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 34.58 0.00
December 2822.76 20-DEC-19:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 0.00 67.25
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2787.22   324.00 159.12 300.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2994.24   970.20 590.08 848.14 0.00 0.00 0.00 0.00 53.98 67.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2940.73 24-JAN-19:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 61.89
February 2819.67 10-FEB-16:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 21.78 0.00
March 2969.52 15-MAR-20:11 1121.40 590.02 1272.07 0.00 0.00 0.00 0.00 0.00 54.66
April 3028.44 18-APR-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 45.69
May 2854.74 10-MAY-16:31 972.00 265.18 1264.17 0.00 0.00 0.00 0.00 4.60 0.00
June 2937.50 13-JUN-18:11 1386.00 842.88 1211.49 0.00 0.00 0.00 0.00 3.90 0.00
July 2839.05 12-JUL-18:02 831.60 505.73 726.90 0.00 0.00 0.00 0.00 41.18 0.00
August 2832.10 15-AUG-18:02 831.60 505.73 726.90 0.00 0.00 0.00 0.00 46.53 0.00
September 2836.33 08-SEP-18:02 831.60 505.73 726.90 0.00 0.00 0.00 0.00 54.96 0.00
October 2818.98 06-OCT-18:02 831.60 505.73 726.90 0.00 0.00 0.00 0.00 32.76 0.00
November 2827.99 01-NOV-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 29.17 0.00
December 2792.23 05-DEC-16:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 16.71 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2792.23   583.20 159.11 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3028.44   1800.00 842.88 1272.07 0.00 0.00 0.00 0.00 54.96 61.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1449.96 25-JAN-16:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 18.26
February 1386.40 11-FEB-16:12 324.00 117.89 325.16 0.00 0.00 0.00 0.00 15.62 0.00
March 1450.08 16-MAR-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 14.92
April 1366.81 15-APR-18:02 702.00 357.25 712.25 0.00 0.00 0.00 0.00 23.57 0.00
May 1363.38 09-MAY-15:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 14.87 0.00
June 1368.83 25-JUN-15:12 324.00 117.89 325.16 0.00 0.00 0.00 0.00 22.98 0.00
July 1373.92 28-JUL-18:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 31.15 0.00
August 1384.00 31-AUG-15:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 30.75 0.00
September 1387.46 30-SEP-15:12 324.00 117.89 325.16 0.00 0.00 0.00 0.00 27.24 0.00
October 1398.12 06-OCT-15:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 21.03 0.00
November 1381.37 19-NOV-16:12 324.00 117.89 325.16 0.00 0.00 0.00 0.00 12.80 0.00
December 1389.92 06-DEC-16:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 9.93 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1363.38   324.00 100.03 294.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1450.08   831.60 357.25 712.25 0.00 0.00 0.00 0.00 31.15 18.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19345.29 06-JAN-24:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 5.02 0.00
February 19628.46 17-FEB-24:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 0.00 3.34
March 19943.56 27-MAR-18:10 125947.58 6057.78 40487.42 0.00 0.00 0.00 0.00 48.74 0.00
April 20834.91 17-APR-18:10 125947.58 5425.10 40487.42 0.00 0.00 0.00 0.00 117.50 0.00
May 21447.48 22-MAY-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 51.10 0.00
June 21947.08 09-JUN-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 79.04 0.00
July 22032.64 28-JUL-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 78.57 0.00
August 21624.47 02-AUG-23:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 78.95 0.00
September 21671.37 22-SEP-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 69.40 0.00
October 20907.71 03-OCT-23:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 51.06 0.00
November 20471.55 03-NOV-23:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 42.96 0.00
December 19620.96 08-DEC-24:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 15.04 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 19345.29   26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22032.64   125947.58 6057.78 40487.42 0.00 0.00 0.00 0.00 117.50 3.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20488.15 06-JAN-24:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 5.02 0.00
February 20809.99 17-FEB-22:53 188921.38 6640.73 47235.32 0.00 0.00 0.00 0.00 0.00 3.42
March 21296.58 27-MAR-21:10 53977.54 1897.35 13495.81 0.00 0.00 0.00 0.00 13.46 0.00
April 21878.21 14-APR-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 14.98 0.00
May 22800.81 22-MAY-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 51.10 0.00
June 23253.96 09-JUN-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 79.04 0.00
July 23347.81 28-JUL-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 78.57 0.00
August 22956.33 02-AUG-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 78.95 0.00
September 22956.16 22-SEP-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 69.40 0.00
October 22176.23 03-OCT-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 60.81 0.00
November 21655.38 03-NOV-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 42.96 0.00
December 20757.77 08-DEC-22:05 107955.07 3794.70 26991.61 0.00 0.00 0.00 0.00 0.00 2.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20488.15   26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23347.81   188921.38 6640.73 47235.32 0.00 0.00 0.00 0.00 79.04 3.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 27480.66 01-JAN-11:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 31.40 0.00
February 27504.68 11-FEB-11:50 800.57 207.61 14604.56 18744.03 0.00 0.00 0.00 53.60 0.00
March 27710.86 27-MAR-10:40 1067.42 415.23 29209.11 37488.05 0.00 0.00 0.00 30.41 0.00
April 28713.12 15-APR-10:50 800.57 207.61 14604.56 18744.03 0.00 0.00 0.00 81.20 0.00
May 28752.49 06-MAY-10:50 800.57 207.61 14604.56 18744.03 0.00 0.00 0.00 73.90 0.00
June 29184.63 11-JUN-10:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 101.40 0.00
July 29417.49 23-JUL-10:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 126.01 0.00
August 28995.77 19-AUG-10:50 800.57 207.61 14604.56 18744.03 0.00 0.00 0.00 109.68 0.00
September 28968.01 09-SEP-10:50 800.57 207.61 14604.56 18744.03 0.00 0.00 0.00 101.18 0.00
October 28686.31 07-OCT-10:50 800.57 207.61 14604.56 18744.03 0.00 0.00 0.00 106.94 0.00
November 27701.47 07-NOV-11:50 533.71 207.61 14604.56 18744.03 0.00 0.00 0.00 44.60 0.00
December 27697.16 09-DEC-11:50 800.57 207.61 14604.56 18744.03 0.00 0.00 0.00 46.01 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 27480.66   533.71 207.61 14604.56 18744.03 0.00 0.00 0.00 30.41 0.00
Maximum of Months 29417.49   1067.42 415.23 29209.11 37488.05 0.00 0.00 0.00 126.01 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5045.71 02-JAN-14:30 532.32 328.12 0.00 0.00 0.00 0.00 0.00 69.23 0.00
February 5544.63 11-FEB-14:30 798.48 328.12 0.00 0.00 0.00 0.00 0.00 68.59 0.00
March 4980.99 27-MAR-15:13 7984.80 1968.72 0.00 0.00 0.00 0.00 0.00 50.60 0.00
April 5540.71 14-APR-15:23 3992.40 984.36 0.00 0.00 0.00 0.00 0.00 84.43 0.00
May 5541.25 18-MAY-15:13 7984.80 1968.72 0.00 0.00 0.00 0.00 0.00 94.93 0.00
June 6086.45 28-JUN-16:00 1330.80 328.12 0.00 0.00 0.00 0.00 0.00 84.64 0.00
July 6928.76 29-JUL-16:10 1330.80 328.12 0.00 0.00 0.00 0.00 0.00 158.31 0.00
August 6365.86 31-AUG-15:10 1330.80 328.12 0.00 0.00 0.00 0.00 0.00 114.44 0.00
September 6740.59 09-SEP-13:10 1596.96 656.24 0.00 0.00 0.00 0.00 0.00 106.74 0.00
October 6298.64 07-OCT-13:40 798.48 328.12 0.00 0.00 0.00 0.00 0.00 84.48 0.00
November 5686.09 08-NOV-14:30 532.32 328.12 0.00 0.00 0.00 0.00 0.00 64.57 0.00
December 5263.41 09-DEC-12:40 798.48 328.12 0.00 0.00 0.00 0.00 0.00 44.84 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4980.99   532.32 328.12 0.00 0.00 0.00 0.00 0.00 44.84 0.00
Maximum of Months 6928.76   7984.80 1968.72 0.00 0.00 0.00 0.00 0.00 158.31 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.470818E+12 308689.29 06-JAN-20:10 0.345027E+12 286630.59 30-JAN-18:00
February 0.444806E+12 299066.39 10-FEB-20:40 0.310710E+12 286061.28 01-FEB-18:30
March 0.507852E+12 321232.81 13-MAR-19:10 0.340658E+12 285194.65 03-MAR-18:00
April 0.532132E+12 329492.69 14-APR-19:10 0.324251E+12 283839.83 03-APR-17:19
May 0.601749E+12 343247.34 22-MAY-19:10 0.329920E+12 282244.13 01-MAY-17:10
June 0.617694E+12 360271.54 29-JUN-19:19 0.315430E+12 280526.62 01-JUN-17:40
July 0.651678E+12 366903.44 27-JUL-19:10 0.323999E+12 279527.86 05-JUL-17:19
August 0.646695E+12 360241.13 21-AUG-19:10 0.325406E+12 280094.38 25-AUG-17:30
September 0.623347E+12 363465.10 18-SEP-19:10 0.318192E+12 281773.95 29-SEP-17:19
October 0.614777E+12 353083.93 03-OCT-19:10 0.333892E+12 283564.47 30-OCT-17:10
November 0.542483E+12 338510.54 03-NOV-19:00 0.328339E+12 285072.74 29-NOV-18:10
December 0.496802E+12 329311.49 08-DEC-21:00 0.343418E+12 287928.26 26-DEC-18:10
             
Annual Sum or Average 0.675083E+13     0.393924E+13    
Minimum of Months 0.444806E+12 299066.39   0.310710E+12 279527.86  
Maximum of Months 0.651678E+12 366903.44   0.345027E+12 287928.26  



Table of Contents

Report: EnergyConsumptionElectricityGeneratedPropaneMonthly

For: Meter

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ELECTRICITYPRODUCED:FACILITY [J] ELECTRICITYPRODUCED:FACILITY {Maximum} [W] ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} PROPANE:FACILITY [] PROPANE:FACILITY []
January 0.129516E+11 27059.96 24-JAN-12:30 0.00 0.00
February 0.143182E+11 29657.82 25-FEB-12:30 0.00 0.00
March 0.193103E+11 33795.21 15-MAR-12:30 0.00 0.00
April 0.211919E+11 32537.38 19-APR-12:30 0.00 0.00
May 0.213710E+11 33843.43 06-MAY-11:30 0.00 0.00
June 0.196528E+11 31765.00 06-JUN-11:30 0.00 0.00
July 0.217919E+11 31215.52 07-JUL-12:30 0.00 0.00
August 0.200980E+11 30067.89 02-AUG-11:30 0.00 0.00
September 0.172720E+11 30853.59 17-SEP-11:30 0.00 0.00
October 0.158231E+11 28986.88 06-OCT-11:30 0.00 0.00
November 0.126686E+11 24242.61 06-NOV-12:09 0.00 0.00
December 0.119998E+11 23360.55 31-DEC-12:30 0.00 0.00
           
Annual Sum or Average 0.208449E+12     0.00 0.00
Minimum of Months 0.119998E+11 23360.55   0.00 0.00
Maximum of Months 0.217919E+11 33843.43   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY [J]
January 0.389108E+11 0.143694E+11 0.140003E+12 0.331708E+11 0.464376E+11 0.905820E+10 0.00 0.158050E+12 0.00 0.00 0.193378E+11 0.770428E+10 0.00
February 0.350643E+11 0.123995E+11 0.126445E+12 0.299608E+11 0.425510E+11 0.824219E+10 0.00 0.162096E+12 0.00 0.00 0.176738E+11 0.696185E+10 0.00
March 0.386710E+11 0.129451E+11 0.140056E+12 0.331732E+11 0.477570E+11 0.920423E+10 0.00 0.194444E+12 0.00 0.00 0.201188E+11 0.770287E+10 0.00
April 0.373147E+11 0.117620E+11 0.135446E+12 0.321004E+11 0.481756E+11 0.904838E+10 0.00 0.227302E+12 0.00 0.00 0.198595E+11 0.746490E+10 0.00
May 0.384913E+11 0.114634E+11 0.140035E+12 0.331718E+11 0.524593E+11 0.964120E+10 0.00 0.283910E+12 0.00 0.00 0.210851E+11 0.770426E+10 0.00
June 0.372296E+11 0.107799E+11 0.135537E+12 0.321027E+11 0.529914E+11 0.957252E+10 0.00 0.307885E+12 0.00 0.00 0.204728E+11 0.745687E+10 0.00
July 0.383918E+11 0.112394E+11 0.139944E+12 0.331694E+11 0.561740E+11 0.998839E+10 0.00 0.330148E+12 0.00 0.00 0.211411E+11 0.771237E+10 0.00
August 0.385333E+11 0.118481E+11 0.140067E+12 0.331731E+11 0.552471E+11 0.992938E+10 0.00 0.325256E+12 0.00 0.00 0.211489E+11 0.770437E+10 0.00
September 0.374133E+11 0.122042E+11 0.135457E+12 0.321005E+11 0.546139E+11 0.962038E+10 0.00 0.310333E+12 0.00 0.00 0.204727E+11 0.746621E+10 0.00
October 0.387884E+11 0.134045E+11 0.139992E+12 0.331707E+11 0.544082E+11 0.973916E+10 0.00 0.292667E+12 0.00 0.00 0.211169E+11 0.770294E+10 0.00
November 0.376062E+11 0.136802E+11 0.135531E+12 0.321014E+11 0.494151E+11 0.916155E+10 0.00 0.234231E+12 0.00 0.00 0.196512E+11 0.744868E+10 0.00
December 0.389002E+11 0.145187E+11 0.139944E+12 0.331697E+11 0.475817E+11 0.917567E+10 0.00 0.182482E+12 0.00 0.00 0.195359E+11 0.771245E+10 0.00
                           
Annual Sum or Average 0.455315E+12 0.150614E+12 0.164846E+13 0.390565E+12 0.607812E+12 0.112381E+12 0.00 0.300881E+13 0.00 0.00 0.241614E+12 0.907421E+11 0.00
Minimum of Months 0.350643E+11 0.107799E+11 0.126445E+12 0.299608E+11 0.425510E+11 0.824219E+10 0.00 0.158050E+12 0.00 0.00 0.176738E+11 0.696185E+10 0.00
Maximum of Months 0.389108E+11 0.145187E+11 0.140067E+12 0.331732E+11 0.561740E+11 0.998839E+10 0.00 0.330148E+12 0.00 0.00 0.211489E+11 0.771245E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.363596E+09 0.00 0.192745E+12 0.00 0.00
February 0.137204E+12 0.00 0.387677E+09 0.00 0.173119E+12 0.00 0.00
March 0.152024E+12 0.00 0.390550E+09 0.00 0.188244E+12 0.00 0.00
April 0.146956E+12 0.00 45861805.90 0.00 0.177250E+12 0.00 0.00
May 0.151978E+12 0.00 24346605.60 0.00 0.177917E+12 0.00 0.00
June 0.147114E+12 0.00 20372190.11 0.00 0.168296E+12 0.00 0.00
July 0.151820E+12 0.00 9259135.71 0.00 0.172169E+12 0.00 0.00
August 0.152039E+12 0.00 28767677.56 0.00 0.173339E+12 0.00 0.00
September 0.146971E+12 0.00 21988671.78 0.00 0.171199E+12 0.00 0.00
October 0.151903E+12 0.00 29333379.64 0.00 0.181959E+12 0.00 0.00
November 0.147091E+12 0.00 0.112139E+09 0.00 0.181136E+12 0.00 0.00
December 0.151820E+12 0.00 0.442343E+09 0.00 0.191156E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.187623E+10 0.00 0.214853E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 9259135.71 0.00 0.168296E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.442343E+09 0.00 0.192745E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 37630.57 02-JAN-20:10 9571.94 01-JAN-00:10 88863.15 02-JAN-07:10 23858.54 02-JAN-07:19 29552.12 13-JAN-21:00 3831.66 06-JAN-22:00 0.00 01-JAN-00:10
February 37630.57 01-FEB-20:10 9571.94 01-FEB-00:10 88863.15 01-FEB-07:10 23858.54 24-FEB-07:19 28959.06 17-FEB-22:00 3917.01 11-FEB-16:40 0.00 01-FEB-00:10
March 37630.57 01-MAR-20:10 9571.94 01-MAR-00:10 88863.15 01-MAR-07:10 23858.54 13-MAR-06:19 29400.43 28-MAR-20:00 3971.49 13-MAR-18:10 0.00 01-MAR-00:10
April 37630.57 03-APR-19:10 9571.94 01-APR-00:10 88863.15 03-APR-06:10 23858.54 03-APR-06:19 31557.34 14-APR-21:19 4089.20 13-APR-18:10 0.00 01-APR-00:10
May 37630.57 01-MAY-19:10 9571.94 01-MAY-00:10 88863.15 01-MAY-06:10 23858.13 25-MAY-06:19 33443.45 22-MAY-21:00 4211.98 31-MAY-18:10 0.00 01-MAY-00:10
June 37630.57 01-JUN-19:10 9571.94 01-JUN-00:10 88863.15 01-JUN-06:10 23858.23 15-JUN-06:19 36699.38 29-JUN-21:00 4395.26 08-JUN-18:10 0.00 01-JUN-00:10
July 37630.57 03-JUL-19:19 9571.94 01-JUL-00:10 88863.15 03-JUL-06:10 23858.10 13-JUL-06:19 37628.64 28-JUL-21:00 4528.45 27-JUL-18:10 0.00 01-JUL-00:10
August 37630.57 01-AUG-19:10 9571.94 01-AUG-00:10 88863.15 01-AUG-06:10 23858.50 25-AUG-06:19 37859.59 21-AUG-21:49 4385.35 21-AUG-18:10 0.00 01-AUG-00:10
September 37630.57 01-SEP-19:10 9571.94 01-SEP-00:10 88863.15 01-SEP-06:10 23858.54 15-SEP-06:19 39239.64 22-SEP-21:00 4514.39 18-SEP-18:10 0.00 01-SEP-00:10
October 37630.57 02-OCT-19:10 9571.94 01-OCT-00:10 88863.15 02-OCT-06:10 23858.54 02-OCT-06:19 36409.07 06-OCT-21:19 4233.57 30-OCT-18:19 0.00 01-OCT-00:10
November 37630.57 01-NOV-19:10 9571.94 01-NOV-00:10 88863.15 01-NOV-06:10 23858.54 01-NOV-06:19 33993.01 03-NOV-21:19 4131.47 22-NOV-19:10 0.00 01-NOV-00:10
December 37630.57 01-DEC-20:10 9571.94 01-DEC-00:10 88863.15 01-DEC-07:10 23858.54 27-DEC-07:19 31945.10 08-DEC-21:00 4036.72 08-DEC-21:00 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 37630.57   9571.94   88863.15   23858.10   28959.06   3831.66   0.00  
Maximum of Months 37630.57   9571.94   88863.15   23858.54   39239.64   4528.45   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY {Maximum} [W] COGENERATION:ELECTRICITY {TIMESTAMP}
January 119784.11 02-JAN-13:00 0.00 0.00 8265.52 01-JAN-09:00 4738.62 12-JAN-19:10 0.00 01-JAN-00:10
February 138763.23 11-FEB-16:30 0.00 0.00 8265.52 07-FEB-09:00 4738.58 09-FEB-19:10 0.00 01-FEB-00:10
March 137046.31 13-MAR-15:30 0.00 0.00 8265.52 02-MAR-09:00 4738.60 30-MAR-18:10 0.00 01-MAR-00:10
April 151540.98 14-APR-15:30 0.00 0.00 8265.52 03-APR-08:00 4738.57 06-APR-18:10 0.00 01-APR-00:10
May 159058.29 29-MAY-18:10 0.00 0.00 8265.52 01-MAY-08:39 4738.49 04-MAY-18:10 0.00 01-MAY-00:10
June 167797.94 08-JUN-18:10 0.00 0.00 8265.52 21-JUN-20:00 4738.58 01-JUN-18:10 0.00 01-JUN-00:10
July 181382.53 28-JUL-15:30 0.00 0.00 8265.52 01-JUL-00:10 4738.75 13-JUL-18:10 0.00 01-JUL-00:10
August 172600.22 21-AUG-15:00 0.00 0.00 8265.52 05-AUG-19:30 4738.50 10-AUG-18:10 0.00 01-AUG-00:10
September 176743.48 18-SEP-18:10 0.00 0.00 8265.52 05-SEP-08:30 4738.62 07-SEP-18:10 0.00 01-SEP-00:10
October 162487.26 03-OCT-15:30 0.00 0.00 8265.52 19-OCT-08:09 4738.66 12-OCT-18:10 0.00 01-OCT-00:10
November 146249.68 03-NOV-18:10 0.00 0.00 8265.52 02-NOV-08:00 4738.73 30-NOV-19:10 0.00 01-NOV-00:10
December 134814.30 25-DEC-22:00 0.00 0.00 8265.52 02-DEC-09:00 4738.76 28-DEC-19:10 0.00 01-DEC-00:10
                     
Annual Sum or Average     0.00 0.00            
Minimum of Months 119784.11   0.00 0.00 8265.52   4738.49   0.00  
Maximum of Months 181382.53   0.00 0.00 8265.52   4738.76   0.00  



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 308689.29 06-JAN-20:10 37630.57 86131.51 9571.94 19287.45 25900.46 3758.00 0.00 113267.05 0.00
February 299066.39 10-FEB-20:40 37630.57 86131.51 9571.94 19290.81 24034.64 3611.63 0.00 105327.18 0.00
March 321232.81 13-MAR-19:10 37630.57 86131.51 9571.94 19287.45 25723.07 3904.12 0.00 125190.39 0.00
April 329492.69 14-APR-19:10 37630.57 86131.51 9571.94 19287.45 27151.23 3963.14 0.00 132568.73 0.00
May 343247.34 22-MAY-19:10 37630.57 86131.51 9571.94 19287.45 26771.00 4085.88 0.00 145746.62 0.00
June 360271.54 29-JUN-19:19 37630.57 86131.51 9571.94 19290.31 28595.64 4278.63 0.00 161115.94 0.00
July 366903.44 27-JUL-19:10 37630.57 86131.51 9571.94 19286.87 28428.60 4439.89 0.00 167634.08 0.00
August 360241.13 21-AUG-19:10 37630.57 86131.51 9571.94 19287.45 28875.63 4327.00 0.00 160402.48 0.00
September 363465.10 18-SEP-19:10 37630.57 86131.51 9571.94 19287.45 29343.77 4354.70 0.00 163135.75 0.00
October 353083.93 03-OCT-19:10 37630.57 86131.51 9571.94 19287.45 29389.49 4187.50 0.00 153581.73 0.00
November 338510.54 03-NOV-19:00 37630.57 86131.51 9571.94 19290.81 29659.38 4057.07 0.00 138821.68 0.00
December 329311.49 08-DEC-21:00 33461.95 87910.25 9571.94 14811.10 31945.10 4036.72 0.00 134129.17 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 299066.39   33461.95 86131.51 9571.94 14811.10 24034.64 3611.63 0.00 105327.18 0.00
Maximum of Months 366903.44   37630.57 87910.25 9571.94 19290.81 31945.10 4439.89 0.00 167634.08 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 9256.61 25-JAN-19:49 0.00 185853.65 17-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 13970.12 04-FEB-09:20 0.00 185191.50 01-FEB-21:00 0.00
March 104248.32 01-MAR-18:10 0.00 22051.98 16-MAR-08:20 0.00 181498.69 01-MAR-21:30 0.00
April 104248.32 01-APR-17:10 0.00 3367.31 24-APR-21:00 0.00 179934.93 03-APR-20:00 0.00
May 104248.32 01-MAY-17:10 0.00 3262.48 27-MAY-08:00 0.00 178328.76 01-MAY-20:49 0.00
June 104248.32 01-JUN-17:10 0.00 2815.69 15-JUN-08:00 0.00 176647.18 01-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 1029.25 17-JUL-15:20 0.00 175551.98 06-JUL-20:00 0.00
August 104248.32 01-AUG-17:10 0.00 3360.00 28-AUG-08:00 0.00 176377.12 31-AUG-20:00 0.00
September 104248.32 01-SEP-17:10 0.00 1372.40 05-SEP-08:30 0.00 177862.73 29-SEP-20:19 0.00
October 104248.32 02-OCT-17:10 0.00 2368.94 18-OCT-08:20 0.00 179729.56 31-OCT-20:00 0.00
November 104248.32 01-NOV-17:10 0.00 3902.91 27-NOV-22:00 0.00 181258.55 30-NOV-21:19 0.00
December 104248.32 01-DEC-18:10 0.00 9795.92 15-DEC-09:20 0.00 183971.74 31-DEC-22:30 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 1029.25   0.00 175551.98   0.00
Maximum of Months 104248.32   0.00 22051.98   0.00 185853.65   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.67 21.77 0.67 21.77
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.50 21.72 0.50 21.72
October 0.00 0.00 0.00 0.00 1.17 21.72 1.17 21.72
November 0.00 0.00 0.00 0.00 0.17 21.76 0.17 21.76
December 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
                 
Annual Sum or Average 0.00   0.00   3.00 21.73 3.00 21.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 21.77 1.17 21.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
April 0.00 0.00 0.00 0.00 1.33 21.72 1.33 21.72
May 0.00 0.00 0.00 0.00 0.67 21.80 0.67 21.80
June 0.00 0.00 0.00 0.00 0.67 21.81 0.67 21.81
July 0.00 0.00 0.00 0.00 0.67 21.75 0.67 21.75
August 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
September 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
October 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
                 
Annual Sum or Average 0.00   0.00   5.00 21.75 5.00 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.81 1.33 21.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
February 0.00 0.00 0.00 0.00 2.00 21.76 2.00 21.76
March 0.00 0.00 0.00 0.00 2.50 21.76 2.50 21.76
April 0.00 0.00 0.00 0.00 3.33 21.74 3.33 21.74
May 0.00 0.00 0.00 0.00 3.50 21.76 3.50 21.76
June 0.00 0.00 0.00 0.00 6.67 21.71 6.67 21.71
July 0.00 0.00 0.00 0.00 7.67 21.70 7.67 21.70
August 0.00 0.00 0.00 0.00 8.17 21.68 8.17 21.68
September 0.00 0.00 0.00 0.00 6.17 21.69 6.17 21.69
October 0.00 0.00 0.00 0.00 5.00 21.70 5.00 21.70
November 0.00 0.00 0.00 0.00 3.00 21.69 3.00 21.69
December 0.00 0.00 0.00 0.00 1.33 21.75 1.33 21.75
                 
Annual Sum or Average 0.00   0.00   49.67 21.71 49.67 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
Maximum of Months 0.00 0.00 0.00 0.00 8.17 21.76 8.17 21.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.33 21.68 0.33 21.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.33 21.79 1.33 21.79
February 0.00 0.00 0.00 0.00 1.67 21.77 1.67 21.77
March 0.00 0.00 0.00 0.00 3.17 21.87 3.17 21.87
April 0.00 0.00 0.00 0.00 5.33 22.03 5.33 22.03
May 0.00 0.00 0.00 0.00 2.00 22.03 2.00 22.03
June 0.00 0.00 0.00 0.00 0.83 21.92 0.83 21.92
July 0.00 0.00 0.00 0.00 0.67 21.85 0.67 21.85
August 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
September 0.00 0.00 0.00 0.00 1.83 21.84 1.83 21.84
October 0.00 0.00 0.00 0.00 2.33 22.12 2.33 22.12
November 0.00 0.00 0.00 0.00 2.00 21.92 2.00 21.92
December 0.00 0.00 0.00 0.00 0.83 21.93 0.83 21.93
                 
Annual Sum or Average 0.00   0.00   22.17 21.94 22.17 21.94
Minimum of Months 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
Maximum of Months 0.00 0.00 0.00 0.00 5.33 22.12 5.33 22.12



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
February 0.00 0.00 0.00 0.00 2.00 21.84 2.00 21.84
March 0.00 0.00 0.00 0.00 1.00 21.71 1.00 21.71
April 0.00 0.00 0.00 0.00 2.50 21.77 2.50 21.77
May 0.00 0.00 0.00 0.00 2.33 21.73 2.33 21.73
June 0.00 0.00 0.00 0.00 0.83 21.74 0.83 21.74
July 0.00 0.00 0.00 0.00 2.17 21.75 2.17 21.75
August 0.00 0.00 0.00 0.00 1.50 21.78 1.50 21.78
September 0.00 0.00 0.00 0.00 2.00 21.78 2.00 21.78
October 0.00 0.00 0.00 0.00 2.67 21.80 2.67 21.80
November 0.00 0.00 0.00 0.00 0.83 21.74 0.83 21.74
December 0.00 0.00 0.00 0.00 0.83 21.79 0.83 21.79
                 
Annual Sum or Average 0.00   0.00   18.83 21.77 18.83 21.77
Minimum of Months 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
Maximum of Months 0.00 0.00 0.00 0.00 2.67 21.84 2.67 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
March 0.00 0.00 0.00 0.00 1.33 21.72 1.33 21.72
April 0.00 0.00 0.00 0.00 3.17 21.75 3.17 21.75
May 0.00 0.00 0.00 0.00 2.83 21.76 2.83 21.76
June 0.00 0.00 0.00 0.00 1.67 21.80 1.67 21.80
July 0.00 0.00 0.00 0.00 2.33 21.79 2.33 21.79
August 0.00 0.00 0.00 0.00 1.50 21.73 1.50 21.73
September 0.00 0.00 0.00 0.00 1.33 21.73 1.33 21.73
October 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.33 21.75 0.33 21.75
                 
Annual Sum or Average 0.00   0.00   15.33 21.75 15.33 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.17 21.80 3.17 21.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.67 21.89 6.67 21.89
February 0.00 0.00 0.00 0.00 6.50 21.88 6.50 21.88
March 0.00 0.00 0.00 0.00 4.00 21.81 4.00 21.81
April 0.00 0.00 0.00 0.00 2.67 21.82 2.67 21.82
May 0.00 0.00 0.00 0.00 0.50 21.69 0.50 21.69
June 0.00 0.00 0.00 0.00 1.17 21.71 1.17 21.71
July 0.00 0.00 0.00 0.00 4.17 21.72 4.17 21.72
August 0.00 0.00 0.00 0.00 4.00 21.77 4.00 21.77
September 0.00 0.00 0.00 0.00 8.50 21.82 8.50 21.82
October 0.00 0.00 0.00 0.00 11.17 21.90 11.17 21.90
November 0.00 0.00 0.00 0.00 6.50 21.88 6.50 21.88
December 0.00 0.00 0.00 0.00 6.83 21.89 6.83 21.89
                 
Annual Sum or Average 0.00   0.00   62.67 21.85 62.67 21.85
Minimum of Months 0.00 0.00 0.00 0.00 0.50 21.69 0.50 21.69
Maximum of Months 0.00 0.00 0.00 0.00 11.17 21.90 11.17 21.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 138.17 23.64 345.67 23.86 0.00 23.86
February 169.17 23.48 221.33 23.72 0.00 23.72
March 358.83 23.27 145.50 23.43 0.00 23.43
April 242.33 23.26 144.33 23.46 0.00 23.46
May 57.50 23.25 370.00 23.80 0.00 23.80
June 0.33 23.36 427.50 23.95 0.00 23.95
July 0.00 0.00 496.67 23.98 0.00 23.98
August 0.00 0.00 598.83 23.96 0.00 23.96
September 0.00 0.00 682.33 23.96 0.00 23.96
October 0.00 0.00 728.50 23.96 0.00 23.96
November 11.17 23.74 596.67 23.95 0.00 23.95
December 34.17 23.67 459.67 23.92 0.00 23.92
             
Annual Sum or Average 1011.67 23.37 5217.00 23.85 0.00 23.85
Minimum of Months 0.00 0.00 144.33 23.43 0.00 23.43
Maximum of Months 358.83 23.74 728.50 23.98 0.00 23.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 287.67 22.56 365.67 23.31 13.17 23.32
February 202.00 22.63 402.83 23.48 10.17 23.49
March 193.33 22.66 505.33 23.56 22.17 23.57
April 58.33 23.08 605.50 23.83 9.33 23.83
May 51.33 23.72 734.00 23.94 44.50 23.93
June 48.33 23.95 720.00 23.98 48.33 23.98
July 21.50 23.94 744.00 23.99 21.50 23.99
August 49.17 23.88 720.00 23.96 47.67 23.96
September 33.83 23.93 720.00 23.98 33.83 23.98
October 45.33 23.79 737.67 23.96 44.83 23.95
November 105.17 22.88 603.00 23.79 28.00 23.80
December 259.67 22.54 442.50 23.42 19.67 23.43
             
Annual Sum or Average 1355.67 22.87 7300.50 23.78 343.17 23.79
Minimum of Months 21.50 22.54 365.67 23.31 9.33 23.32
Maximum of Months 287.67 23.95 744.00 23.99 48.33 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 554.00 22.64 75.17 22.77 0.00 22.77
February 392.33 22.64 128.33 22.91 0.00 22.91
March 358.83 22.65 227.00 23.09 0.00 23.09
April 173.17 22.83 359.67 23.51 0.00 23.51
May 48.33 22.86 520.00 23.75 0.00 23.75
June 10.33 23.34 568.33 23.84 4.50 23.84
July 2.33 23.71 668.50 23.86 2.00 23.86
August 30.00 22.96 587.50 23.81 3.00 23.81
September 4.83 22.94 619.50 23.84 0.00 23.84
October 25.67 23.14 555.00 23.80 5.83 23.80
November 177.17 22.73 362.17 23.43 0.00 23.43
December 418.67 22.59 189.17 22.96 0.00 22.96
             
Annual Sum or Average 2195.67 22.68 4860.33 23.47 15.33 23.47
Minimum of Months 2.33 22.59 75.17 22.77 0.00 22.77
Maximum of Months 554.00 23.71 668.50 23.86 5.83 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 245.83 23.53 303.17 23.79 6.83 23.79
February 167.83 23.50 348.17 23.84 12.67 23.84
March 162.17 23.47 425.17 23.85 8.67 23.86
April 0.50 24.00 621.67 24.00 0.00 24.00
May 0.00 0.00 744.00 24.00 0.00 24.00
June 0.00 0.00 720.00 24.00 0.00 24.00
July 0.00 0.00 744.00 24.00 0.00 24.00
August 0.00 0.00 744.00 24.00 0.00 24.00
September 0.00 0.00 720.00 24.00 0.00 24.00
October 0.00 0.00 744.00 24.00 0.00 24.00
November 58.33 23.82 571.50 23.98 0.00 23.98
December 254.00 23.64 422.00 23.86 51.50 23.87
             
Annual Sum or Average 888.67 23.57 7107.67 23.95 79.67 23.95
Minimum of Months 0.00 0.00 303.17 23.79 0.00 23.79
Maximum of Months 254.00 24.00 744.00 24.00 51.50 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.12 0.00 22.12 0.00 22.12
February 672.00 22.30 0.00 22.30 0.00 22.30
March 744.00 22.40 0.00 22.40 0.00 22.40
April 642.50 22.83 0.00 22.83 0.00 22.83
May 228.50 23.08 132.67 23.33 0.00 23.33
June 1.67 23.18 499.17 23.82 0.00 23.82
July 0.00 0.00 663.33 23.86 0.00 23.86
August 77.67 23.05 353.17 23.69 0.00 23.69
September 14.67 23.17 377.67 23.78 0.00 23.78
October 260.83 23.14 47.67 23.23 0.00 23.23
November 583.17 22.79 0.00 22.79 0.00 22.79
December 723.67 22.33 0.00 22.33 0.00 22.33
             
Annual Sum or Average 4692.67 22.52 2073.67 22.92 0.00 22.92
Minimum of Months 0.00 0.00 0.00 22.12 0.00 22.12
Maximum of Months 744.00 23.18 663.33 23.86 0.00 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 270.67 24.00 744.00 24.00 270.67 24.00
February 282.00 24.00 672.00 24.00 282.00 24.00
March 393.83 24.00 744.00 24.00 393.83 24.00
April 524.67 24.00 720.00 24.00 524.67 24.00
May 624.67 24.00 744.00 24.00 624.67 24.00
June 666.17 24.00 720.00 24.00 666.17 24.00
July 710.00 24.00 744.00 24.00 710.00 24.00
August 632.50 24.00 744.00 24.00 632.50 24.00
September 664.83 24.00 720.00 24.00 664.83 24.00
October 613.33 24.00 744.00 24.00 613.33 24.00
November 466.50 24.00 720.00 24.00 466.50 24.00
December 317.33 24.00 744.00 24.00 317.33 24.00
             
Annual Sum or Average 6166.50 24.00 8760.00 24.00 6166.50 24.00
Minimum of Months 270.67 24.00 672.00 24.00 270.67 24.00
Maximum of Months 710.00 24.00 744.00 24.00 710.00 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 520.67 22.29 256.50 22.57 120.00 22.66
February 443.33 22.30 246.83 22.60 116.17 22.68
March 532.67 22.29 251.50 22.56 153.00 22.67
April 509.50 22.39 286.00 22.66 184.83 22.78
May 529.50 22.53 309.17 22.82 235.17 22.94
June 482.50 22.71 340.67 22.99 244.17 23.12
July 385.50 22.92 407.33 23.13 238.83 23.23
August 437.00 22.85 415.00 23.08 248.00 23.19
September 320.67 23.21 528.00 23.26 239.00 23.35
October 332.83 23.14 574.17 23.23 245.50 23.30
November 372.50 22.75 445.00 23.02 198.00 23.10
December 480.33 22.35 318.33 22.67 145.33 22.75
             
Annual Sum or Average 5347.00 22.60 4378.50 22.89 2368.00 23.00
Minimum of Months 320.67 22.29 246.83 22.56 116.17 22.66
Maximum of Months 532.67 23.21 574.17 23.26 248.00 23.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 570.83 22.92 224.67 23.11 173.17 23.20
February 471.50 22.94 234.67 23.18 150.00 23.26
March 525.00 22.96 269.00 23.21 187.33 23.31
April 436.00 23.22 352.17 23.46 231.00 23.54
May 340.33 23.61 459.67 23.72 261.50 23.76
June 252.33 23.90 518.17 23.82 238.17 23.86
July 237.17 23.97 605.00 23.81 234.33 23.85
August 278.50 23.80 556.50 23.77 246.83 23.81
September 232.33 23.95 610.00 23.80 227.67 23.84
October 265.50 23.90 604.50 23.78 254.00 23.82
November 343.67 23.44 459.83 23.58 223.00 23.64
December 478.00 22.99 319.83 23.24 193.83 23.31
             
Annual Sum or Average 4431.17 23.34 5214.00 23.55 2620.83 23.61
Minimum of Months 232.33 22.92 224.67 23.11 150.00 23.20
Maximum of Months 570.83 23.97 610.00 23.82 261.50 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 731.00 21.69 6.17 21.70 6.17 21.71
February 650.50 21.69 7.33 21.70 7.33 21.72
March 710.67 21.67 7.50 21.68 7.50 21.70
April 669.00 21.67 0.83 21.67 0.83 21.67
May 670.67 21.63 1.00 21.63 1.00 21.63
June 633.50 21.59 0.00 21.59 0.00 21.59
July 633.17 21.54 0.00 21.54 0.00 21.54
August 643.33 21.56 6.50 21.58 6.50 21.59
September 617.83 21.55 0.33 21.55 0.33 21.55
October 654.50 21.59 2.00 21.60 2.00 21.60
November 662.83 21.64 3.50 21.65 3.50 21.66
December 706.17 21.64 11.17 21.66 11.17 21.68
             
Annual Sum or Average 7983.17 21.62 46.33 21.63 46.33 21.64
Minimum of Months 617.83 21.54 0.00 21.54 0.00 21.54
Maximum of Months 731.00 21.69 11.17 21.70 11.17 21.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 736.50 22.00 56.00 22.08 56.00 22.15
February 644.33 22.12 62.67 22.23 59.00 22.30
March 670.50 22.07 65.33 22.21 51.00 22.29
April 608.67 21.99 62.00 22.18 36.00 22.26
May 662.50 21.74 23.33 21.80 21.83 21.86
June 623.17 21.61 9.17 21.65 7.00 21.67
July 628.67 21.61 13.17 21.66 11.33 21.71
August 645.67 21.60 14.33 21.64 12.67 21.67
September 631.67 21.67 16.50 21.71 15.33 21.76
October 681.00 21.76 20.00 21.81 20.00 21.85
November 686.67 21.94 43.33 22.01 43.33 22.08
December 703.00 21.93 73.67 22.04 71.00 22.12
             
Annual Sum or Average 7922.33 21.84 459.50 21.93 404.50 21.99
Minimum of Months 608.67 21.60 9.17 21.64 7.00 21.67
Maximum of Months 736.50 22.12 73.67 22.23 71.00 22.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.87 34.00 21.92 34.00 21.96
February 672.00 22.03 49.17 22.11 49.17 22.17
March 744.00 22.03 47.17 22.10 47.17 22.16
April 719.67 22.10 30.50 22.15 30.50 22.20
May 744.00 21.85 20.00 21.89 20.00 21.92
June 719.83 21.79 7.00 21.81 7.00 21.82
July 744.00 21.82 11.50 21.85 11.50 21.88
August 744.00 21.77 8.33 21.78 8.33 21.80
September 720.00 21.81 11.83 21.83 11.83 21.85
October 744.00 21.80 18.17 21.83 18.17 21.86
November 720.00 21.88 35.50 21.94 35.50 21.99
December 744.00 21.90 48.83 21.96 48.83 22.02
             
Annual Sum or Average 8759.50 21.89 322.00 21.93 322.00 21.97
Minimum of Months 672.00 21.77 7.00 21.78 7.00 21.80
Maximum of Months 744.00 22.10 49.17 22.15 49.17 22.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 735.50 21.73 5.00 21.74 5.00 21.75
February 668.83 21.76 5.67 21.77 5.67 21.78
March 731.67 21.76 6.33 21.77 6.33 21.78
April 692.83 21.74 0.67 21.75 0.67 21.75
May 682.33 21.67 1.17 21.67 1.17 21.67
June 602.00 21.51 0.00 21.51 0.00 21.51
July 593.33 21.43 0.00 21.43 0.00 21.43
August 622.83 21.51 6.50 21.53 6.50 21.54
September 585.83 21.46 0.00 21.46 0.00 21.46
October 632.67 21.54 1.50 21.54 1.50 21.55
November 674.33 21.69 3.00 21.69 3.00 21.70
December 726.00 21.69 12.83 21.71 12.83 21.73
             
Annual Sum or Average 7948.17 21.63 42.67 21.64 42.67 21.65
Minimum of Months 585.83 21.43 0.00 21.43 0.00 21.43
Maximum of Months 735.50 21.76 12.83 21.77 12.83 21.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 733.33 22.06 56.17 22.15 54.67 22.23
February 655.33 22.20 62.67 22.31 58.17 22.39
March 707.50 22.20 63.00 22.33 51.50 22.42
April 634.67 22.10 61.50 22.29 37.50 22.39
May 664.33 21.76 26.33 21.85 21.83 21.91
June 582.00 21.51 10.83 21.56 6.50 21.58
July 574.50 21.46 14.17 21.53 10.83 21.59
August 629.00 21.56 14.67 21.61 13.33 21.64
September 605.00 21.61 17.17 21.68 15.00 21.73
October 693.83 21.81 21.17 21.88 19.67 21.93
November 707.83 22.03 48.17 22.13 47.00 22.22
December 737.33 21.98 74.83 22.08 74.00 22.15
             
Annual Sum or Average 7924.67 21.87 470.67 21.97 410.00 22.05
Minimum of Months 574.50 21.46 10.83 21.53 6.50 21.58
Maximum of Months 737.33 22.20 74.83 22.33 74.00 22.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 737.00 22.61 42.00 22.63 42.00 22.66
February 672.00 22.67 37.50 22.68 37.50 22.69
March 741.67 22.79 69.17 22.82 69.17 22.84
April 661.83 23.15 100.00 23.18 99.50 23.19
May 547.67 23.30 159.33 23.35 145.00 23.37
June 258.33 23.61 259.17 23.69 163.83 23.70
July 161.67 23.84 356.33 23.86 156.50 23.86
August 322.17 23.53 285.83 23.66 168.00 23.67
September 183.00 23.73 339.00 23.82 147.50 23.82
October 203.00 23.63 261.17 23.71 151.50 23.71
November 552.00 23.13 121.67 23.19 108.17 23.22
December 679.17 22.65 53.17 22.70 53.17 22.73
             
Annual Sum or Average 5719.50 23.03 2084.33 23.20 1341.83 23.26
Minimum of Months 161.67 22.61 37.50 22.63 37.50 22.66
Maximum of Months 741.67 23.84 356.33 23.86 168.00 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 695.00 21.58 17.17 21.61 17.17 21.63
February 612.33 21.57 20.83 21.59 19.50 21.61
March 660.50 21.53 18.50 21.55 18.50 21.57
April 613.17 21.51 11.17 21.54 8.00 21.56
May 607.67 21.45 7.33 21.47 5.33 21.48
June 577.83 21.42 4.00 21.43 1.17 21.44
July 580.83 21.37 6.83 21.40 0.00 21.40
August 596.33 21.42 18.00 21.47 10.50 21.50
September 568.33 21.39 13.50 21.43 6.67 21.45
October 600.33 21.43 12.83 21.46 9.67 21.48
November 622.50 21.52 15.83 21.55 13.50 21.58
December 673.00 21.53 25.50 21.55 25.50 21.58
             
Annual Sum or Average 7407.83 21.48 171.50 21.51 135.50 21.53
Minimum of Months 568.33 21.37 4.00 21.40 0.00 21.40
Maximum of Months 695.00 21.58 25.50 21.61 25.50 21.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 708.00 21.91 80.67 22.01 77.67 22.08
February 593.67 21.99 99.67 22.16 87.00 22.26
March 608.33 21.91 110.33 22.20 68.67 22.29
April 559.67 21.84 102.83 22.18 56.67 22.29
May 603.50 21.57 36.50 21.68 31.17 21.77
June 571.17 21.46 17.17 21.52 9.50 21.56
July 578.17 21.46 26.67 21.57 16.33 21.65
August 597.50 21.46 23.00 21.52 16.83 21.56
September 575.00 21.49 24.00 21.56 21.67 21.62
October 628.33 21.60 33.50 21.67 33.33 21.73
November 641.33 21.78 60.00 21.88 60.00 21.96
December 674.33 21.82 102.33 21.96 94.17 22.06
             
Annual Sum or Average 7339.00 21.70 716.67 21.84 573.00 21.93
Minimum of Months 559.67 21.46 17.17 21.52 9.50 21.56
Maximum of Months 708.00 21.99 110.33 22.20 94.17 22.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 658.67 21.57 17.17 21.60 8.83 21.62
February 598.83 21.59 14.17 21.62 11.67 21.64
March 682.83 21.63 18.17 21.65 18.17 21.67
April 661.33 21.65 6.17 21.66 6.17 21.67
May 686.17 21.66 5.83 21.67 5.83 21.68
June 638.67 21.60 0.50 21.60 0.50 21.61
July 641.17 21.56 0.50 21.56 0.50 21.56
August 643.17 21.56 7.50 21.58 7.50 21.59
September 593.67 21.49 6.33 21.51 4.00 21.52
October 612.83 21.49 22.50 21.56 4.50 21.57
November 607.17 21.52 24.17 21.58 5.00 21.59
December 648.33 21.54 35.67 21.62 12.33 21.64
             
Annual Sum or Average 7672.83 21.57 158.67 21.60 85.00 21.61
Minimum of Months 593.67 21.49 0.50 21.51 0.50 21.52
Maximum of Months 686.17 21.66 35.67 21.67 18.17 21.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 640.17 22.28 167.67 22.51 122.50 22.63
February 518.33 22.35 188.83 22.63 119.83 22.76
March 537.00 22.45 247.83 22.77 151.83 22.90
April 444.00 22.71 331.17 23.04 191.00 23.15
May 357.33 23.10 436.33 23.31 226.17 23.40
June 287.17 23.37 474.67 23.44 216.17 23.53
July 244.67 23.46 518.50 23.44 196.33 23.52
August 322.50 23.20 455.17 23.38 214.50 23.47
September 311.50 23.10 425.50 23.34 192.33 23.43
October 440.50 22.81 390.17 23.13 212.17 23.24
November 520.33 22.57 298.67 22.89 182.67 23.02
December 580.83 22.31 216.00 22.59 142.00 22.71
             
Annual Sum or Average 5204.33 22.70 4150.50 23.04 2167.50 23.16
Minimum of Months 244.67 22.28 167.67 22.51 119.83 22.63
Maximum of Months 640.17 23.46 518.50 23.44 226.17 23.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 530.33 22.44 216.33 22.74 126.17 22.86
February 432.00 22.54 257.33 22.89 122.17 23.00
March 424.83 22.70 332.33 23.05 161.50 23.16
April 305.67 23.14 432.67 23.33 193.00 23.42
May 263.33 23.64 582.33 23.49 236.17 23.56
June 229.33 23.82 621.83 23.53 220.83 23.61
July 211.33 23.86 668.67 23.51 208.00 23.58
August 242.33 23.73 603.00 23.52 222.83 23.60
September 209.00 23.71 559.67 23.52 189.33 23.59
October 294.33 23.30 478.67 23.42 210.00 23.50
November 394.50 22.87 365.50 23.17 190.17 23.28
December 482.00 22.52 295.00 22.86 149.67 22.97
             
Annual Sum or Average 4019.00 23.02 5413.33 23.27 2229.83 23.36
Minimum of Months 209.00 22.44 216.33 22.74 122.17 22.86
Maximum of Months 530.33 23.86 668.67 23.53 236.17 23.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 545.83 23.99 744.00 23.99 545.83 23.99
February 495.50 23.99 672.00 23.99 495.50 23.99
March 561.17 23.99 744.00 23.99 561.17 23.99
April 563.50 23.99 720.00 23.99 563.50 23.99
May 600.00 23.99 744.00 23.99 600.00 23.99
June 597.00 23.99 720.00 23.99 597.00 23.99
July 620.83 23.99 744.00 23.99 620.83 23.99
August 610.17 23.99 744.00 23.99 610.17 23.99
September 594.00 23.99 720.00 23.99 594.00 23.99
October 597.00 23.99 744.00 23.99 597.00 23.99
November 555.67 23.99 720.00 23.99 555.67 23.99
December 554.50 23.99 744.00 23.99 554.50 23.99
             
Annual Sum or Average 6895.17 23.99 8760.00 23.99 6895.17 23.99
Minimum of Months 495.50 23.99 672.00 23.99 495.50 23.99
Maximum of Months 620.83 23.99 744.00 23.99 620.83 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 367.50 23.09 291.33 23.46 44.17 23.49
February 229.00 23.03 368.50 23.60 47.17 23.61
March 223.50 23.12 486.33 23.71 40.33 23.72
April 46.67 23.76 659.17 23.97 31.17 23.97
May 16.67 23.95 742.83 24.00 16.67 24.00
June 3.00 24.00 720.00 24.00 3.00 24.00
July 2.17 24.00 744.00 24.00 2.17 24.00
August 12.00 23.98 744.00 24.00 12.00 24.00
September 9.83 24.00 720.00 24.00 9.83 24.00
October 21.67 23.98 744.00 24.00 21.67 24.00
November 120.67 23.28 573.33 23.86 39.00 23.86
December 337.33 22.99 381.33 23.49 50.00 23.51
             
Annual Sum or Average 1390.00 23.14 7174.83 23.85 317.17 23.85
Minimum of Months 2.17 22.99 291.33 23.46 2.17 23.49
Maximum of Months 367.50 24.00 744.00 24.00 50.00 24.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.81478 53.75123 0.39496 8.41667
February 672.00000 23.69507 54.60084 0.36800 7.99414
March 744.00000 23.48604 56.05505 0.32183 7.36377
April 720.00000 23.54093 59.17174 0.35794 7.76831
May 744.00000 23.69612 59.14898 -0.5359 11.14080
June 720.00000 23.80856 58.46906 -0.4955 10.23068
July 744.00000 23.88159 57.73897 -0.4649 9.58535
August 744.00000 23.91868 57.87231 -0.4478 9.23260
September 720.00000 23.94822 57.34577 -0.4329 8.96442
October 744.00000 23.95490 57.61986 0.47642 9.75937
November 720.00000 23.93594 56.57840 0.45814 9.43923
December 744.00000 23.86841 55.74320 0.42731 8.89913
           
Annual Sum or Average 8760.00000 23.79646 57.01806 0.03360 9.07464
Minimum of Months 672.00000 23.48604 53.75123 -0.5359 7.36377
Maximum of Months 744.00000 23.95490 59.17174 0.47642 11.14080



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.34042 55.35680 0.35757 8.83361
February 672.00000 23.47240 55.30408 0.40072 9.48955
March 744.00000 23.53909 56.08408 0.42295 9.85137
April 720.00000 23.78759 58.73613 0.51891 10.93042
May 744.00000 23.93788 59.36927 -0.2955 6.97340
June 720.00000 23.98632 59.20235 -0.2600 6.45759
July 744.00000 23.99579 58.58540 -0.2357 6.20349
August 744.00000 23.94445 59.43602 -0.2639 6.65499
September 720.00000 23.98731 58.56306 -0.2258 6.19978
October 744.00000 23.96276 58.84879 0.60905 12.87952
November 720.00000 23.76293 58.03734 0.52440 11.49083
December 744.00000 23.41644 57.71209 0.40582 9.64099
           
Annual Sum or Average 8760.00000 23.76217 57.95026 0.16152 8.79514
Minimum of Months 672.00000 23.34042 55.30408 -0.2955 6.19978
Maximum of Months 744.00000 23.99579 59.43602 0.60905 12.87952



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.84944 57.06428 0.21551 6.47697
February 672.00000 23.01226 57.03479 0.26078 7.04945
March 744.00000 23.13388 57.54219 0.29917 7.56675
April 720.00000 23.44996 59.96266 0.40545 8.73553
May 744.00000 23.62713 60.13042 -0.4566 9.69710
June 720.00000 23.72492 59.71254 -0.4175 8.86816
July 744.00000 23.79842 59.04503 -0.3850 8.26488
August 744.00000 23.71046 59.88634 -0.4209 8.98244
September 720.00000 23.76602 59.35727 -0.4003 8.56906
October 744.00000 23.67271 59.97165 0.47115 9.77595
November 720.00000 23.38563 59.48819 0.38257 8.47669
December 744.00000 23.02117 59.15857 0.27722 7.20018
           
Annual Sum or Average 8760.00000 23.43109 59.03931 0.01760 8.31167
Minimum of Months 672.00000 22.84944 57.03479 -0.4566 6.47697
Maximum of Months 744.00000 23.79842 60.13042 0.47115 9.77595



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.99970 49.48482 0.94863 24.48003
February 672.00000 23.99970 49.90209 0.97031 25.37558
March 744.00000 23.99967 50.71111 0.99601 26.42856
April 720.00000 23.99966 53.88434 1.05822 28.93655
May 744.00000 23.99953 54.46167 0.45710 10.11770
June 720.00000 23.99943 54.25200 0.49372 10.82536
July 744.00000 23.99943 53.98148 0.50783 11.11308
August 744.00000 23.99942 54.39720 0.46524 10.29227
September 720.00000 23.99944 54.11016 0.48306 10.59588
October 744.00000 23.99951 54.39832 1.07856 29.78924
November 720.00000 23.99957 53.11120 1.02977 27.76097
December 744.00000 23.99964 51.82505 0.97151 25.35018
           
Annual Sum or Average 8760.00000 23.99956 52.89052 0.78708 20.05146
Minimum of Months 672.00000 23.99942 49.48482 0.45710 10.11770
Maximum of Months 744.00000 23.99970 54.46167 1.07856 29.78924



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.48008 60.52733 0.26561 7.35235
February 672.00000 22.50802 60.93763 0.28035 7.42322
March 744.00000 22.41893 62.13904 0.26263 7.24468
April 720.00000 22.47847 65.56583 0.31035 7.53880
May 744.00000 22.56327 66.10939 -0.6242 14.02015
June 720.00000 22.69199 65.61774 -0.5665 12.65692
July 744.00000 22.78559 64.99288 -0.5246 11.51151
August 744.00000 22.77689 65.51738 -0.5341 11.98244
September 720.00000 22.99962 64.38003 -0.4402 9.86626
October 744.00000 23.03423 64.46177 0.48027 10.25456
November 720.00000 22.83417 63.54355 0.40452 9.18186
December 744.00000 22.56297 62.92561 0.30808 7.88441
           
Annual Sum or Average 8760.00000 22.67845 63.90779 -0.0336 9.76142
Minimum of Months 672.00000 22.41893 60.52733 -0.6242 7.24468
Maximum of Months 744.00000 23.03423 66.10939 0.48027 14.02015



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.00892 59.31438 0.29211 7.29577
February 672.00000 23.07751 59.60820 0.31523 7.62245
March 744.00000 23.06932 60.51898 0.32082 7.81965
April 720.00000 23.26605 63.35266 0.39965 8.69450
May 744.00000 23.44211 63.40946 -0.4680 10.07747
June 720.00000 23.55017 62.77929 -0.4191 9.07406
July 744.00000 23.60130 62.24272 -0.3961 8.61824
August 744.00000 23.54077 62.97331 -0.4231 9.16213
September 720.00000 23.61808 62.31070 -0.3912 8.53741
October 744.00000 23.57791 62.79737 0.49470 10.30340
November 720.00000 23.39849 62.05436 0.43011 9.25567
December 744.00000 23.12871 61.52140 0.34277 7.96490
           
Annual Sum or Average 8760.00000 23.35779 61.91794 0.03964 8.70895
Minimum of Months 672.00000 23.00892 59.31438 -0.4680 7.29577
Maximum of Months 744.00000 23.61808 63.40946 0.49470 10.30340



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.72112 55.27654 -0.0848 5.90600
February 672.00000 21.74141 55.03990 -0.0666 5.90960
March 744.00000 21.74591 54.94616 -0.0526 5.86783
April 720.00000 21.78812 55.78483 -0.0138 5.81281
May 744.00000 21.79735 56.42844 -1.0778 30.78705
June 720.00000 21.79953 56.83367 -1.0651 30.23171
July 744.00000 21.80365 56.26507 -1.0487 29.53071
August 744.00000 21.80070 56.93363 -1.0585 29.97280
September 720.00000 21.80236 56.32931 -1.0548 29.84084
October 744.00000 21.80141 55.98000 0.00742 5.78684
November 720.00000 21.77748 55.98940 -0.0282 5.83504
December 744.00000 21.72329 57.32418 -0.0620 5.84223
           
Annual Sum or Average 8760.00000 21.77529 56.10139 -0.4696 16.00432
Minimum of Months 672.00000 21.72112 54.94616 -1.0778 5.78684
Maximum of Months 744.00000 21.80365 57.32418 0.00742 30.78705



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.02171 57.76695 -0.0389 5.98221
February 672.00000 22.18849 56.86779 0.01404 6.16881
March 744.00000 22.24206 55.87970 0.04270 6.24095
April 720.00000 22.26503 56.49595 0.08553 6.27412
May 744.00000 21.91364 56.67091 -1.0410 29.33665
June 720.00000 21.84989 56.80430 -1.0463 29.51051
July 744.00000 21.87781 56.33004 -1.0237 28.62688
August 744.00000 21.83372 57.16659 -1.0518 29.71261
September 720.00000 21.87399 57.05137 -1.0445 29.45616
October 744.00000 21.89227 57.45802 0.01541 5.84011
November 720.00000 22.00134 58.15668 0.00766 5.90775
December 744.00000 22.02638 59.92253 -0.0120 5.97453
           
Annual Sum or Average 8760.00000 21.99732 57.21804 -0.4272 15.80908
Minimum of Months 672.00000 21.83372 55.87970 -1.0518 5.84011
Maximum of Months 744.00000 22.26503 59.92253 0.08553 29.71261



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.87068 56.16607 -0.1099 5.94657
February 672.00000 22.03267 56.34648 -0.0621 5.93616
March 744.00000 22.03270 56.22391 -0.0554 5.91059
April 720.00000 22.09699 57.55452 -0.0189 5.81502
May 744.00000 21.84515 57.13357 -1.1747 34.99194
June 720.00000 21.79319 57.01874 -1.1805 35.22921
July 744.00000 21.82095 56.95641 -1.1683 34.72549
August 744.00000 21.77014 57.47726 -1.1937 35.80681
September 720.00000 21.80622 57.49676 -1.1830 35.35989
October 744.00000 21.80115 58.15818 -0.0793 5.73575
November 720.00000 21.88459 57.97548 -0.0744 5.74183
December 744.00000 21.90012 58.78973 -0.0824 5.80800
           
Annual Sum or Average 8760.00000 21.88661 57.27980 -0.5348 18.15691
Minimum of Months 672.00000 21.77014 56.16607 -1.1937 5.73575
Maximum of Months 744.00000 22.09699 58.78973 -0.0189 35.80681



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.75234 54.66917 -0.0761 5.91432
February 672.00000 21.77118 54.81540 -0.0589 5.90942
March 744.00000 21.78542 54.66580 -0.0445 5.87347
April 720.00000 21.80416 55.38890 -0.0113 5.84788
May 744.00000 21.80755 56.18107 -1.0732 30.64070
June 720.00000 21.81132 56.30698 -1.0504 29.64510
July 744.00000 21.81337 55.82882 -1.0395 29.18958
August 744.00000 21.80798 56.71674 -1.0558 29.89904
September 720.00000 21.81125 55.93832 -1.0444 29.43486
October 744.00000 21.80914 55.80945 0.01125 5.80498
November 720.00000 21.79223 55.97780 -0.0229 5.83944
December 744.00000 21.73338 57.53066 -0.0644 5.83767
           
Annual Sum or Average 8760.00000 21.79163 55.82642 -0.4634 15.88064
Minimum of Months 672.00000 21.73338 54.66580 -1.0732 5.80498
Maximum of Months 744.00000 21.81337 57.53066 0.01125 30.64070



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.08459 56.90694 -0.0245 6.05481
February 672.00000 22.24733 56.39744 0.02662 6.20736
March 744.00000 22.27819 55.58019 0.04964 6.23728
April 720.00000 22.30473 56.11311 0.09285 6.44332
May 744.00000 21.93670 56.44123 -1.0327 29.14400
June 720.00000 21.86598 56.26084 -1.0307 28.92669
July 744.00000 21.89143 55.91336 -1.0133 28.28728
August 744.00000 21.84095 56.98863 -1.0488 29.62746
September 720.00000 21.89223 56.63433 -1.0313 28.98564
October 744.00000 21.91754 57.23835 0.02303 5.92494
November 720.00000 22.05255 57.88173 0.01950 6.01878
December 744.00000 22.00026 60.18362 -0.0227 5.93823
           
Annual Sum or Average 8760.00000 22.02419 56.88397 -0.4189 15.70595
Minimum of Months 672.00000 21.84095 55.58019 -1.0488 5.92494
Maximum of Months 744.00000 22.30473 60.18362 0.09285 29.62746



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.69972 57.45147 -0.0917 6.16411
February 672.00000 21.72523 56.61108 -0.0692 6.16888
March 744.00000 21.72912 56.27841 -0.0540 6.10869
April 720.00000 21.78197 56.93785 -0.0087 6.01045
May 744.00000 21.79560 57.15692 -1.0686 30.73387
June 720.00000 21.79737 57.26287 -1.0573 30.22543
July 744.00000 21.80274 56.60417 -1.0399 29.55530
August 744.00000 21.79818 57.45240 -1.0518 30.03886
September 720.00000 21.79893 56.99960 -1.0504 30.02697
October 744.00000 21.79631 57.11157 0.00931 5.97518
November 720.00000 21.76320 57.45373 -0.0310 6.03910
December 744.00000 21.70059 59.27893 -0.0686 6.08168
           
Annual Sum or Average 8760.00000 21.76587 57.22214 -0.4676 16.15391
Minimum of Months 672.00000 21.69972 56.27841 -1.0686 5.97518
Maximum of Months 744.00000 21.80274 59.27893 0.00931 30.73387



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.98786 59.69138 -0.0495 6.32824
February 672.00000 22.18304 58.05545 0.01457 6.59103
March 744.00000 22.25539 56.80540 0.04947 6.71946
April 720.00000 22.26198 57.28525 0.09282 6.62291
May 744.00000 21.90705 57.28683 -1.0329 29.36946
June 720.00000 21.84963 57.13946 -1.0379 29.51755
July 744.00000 21.88154 56.59825 -1.0130 28.66140
August 744.00000 21.82957 57.69115 -1.0452 29.76773
September 720.00000 21.86386 57.71051 -1.0417 29.66255
October 744.00000 21.86755 58.71342 0.01388 5.96458
November 720.00000 21.95752 59.61332 -0.0010 6.09158
December 744.00000 21.97604 61.67121 -0.0254 6.35111
           
Annual Sum or Average 8760.00000 21.98348 58.19232 -0.4258 16.02577
Minimum of Months 672.00000 21.82957 56.59825 -1.0452 5.96458
Maximum of Months 744.00000 22.26198 61.67121 0.09282 29.76773



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.77106 54.69336 -0.0599 6.17618
February 672.00000 21.77804 55.19390 -0.0539 6.13673
March 744.00000 21.76603 55.50574 -0.0626 6.06183
April 720.00000 21.78316 56.95759 -0.0436 5.96897
May 744.00000 21.79428 57.22389 -1.1269 33.14471
June 720.00000 21.79791 57.23340 -1.1117 32.45948
July 744.00000 21.80254 56.84921 -1.1006 32.01620
August 744.00000 21.80000 57.14645 -1.1043 32.18760
September 720.00000 21.81079 56.48420 -1.0801 31.26440
October 744.00000 21.81786 56.30287 0.00348 6.02247
November 720.00000 21.80163 55.84474 -0.0200 6.08169
December 744.00000 21.76879 56.71263 -0.0435 6.10455
           
Annual Sum or Average 8760.00000 21.79103 56.35202 -0.4863 17.03612
Minimum of Months 672.00000 21.76603 54.69336 -1.1269 5.96897
Maximum of Months 744.00000 21.81786 57.23340 0.00348 33.14471



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.39074 60.77395 0.20924 6.78465
February 672.00000 22.51341 60.90052 0.25413 7.22096
March 744.00000 22.61129 61.47257 0.29304 7.72452
April 720.00000 22.79673 64.36966 0.38125 8.57876
May 744.00000 22.97211 64.37486 -0.4817 10.73362
June 720.00000 23.07177 63.82810 -0.4330 9.79310
July 744.00000 23.08423 63.47702 -0.4234 9.51244
August 744.00000 23.02064 64.15895 -0.4584 10.31134
September 720.00000 22.98943 63.93934 -0.4702 10.57096
October 744.00000 22.86057 64.67087 0.40858 9.00995
November 720.00000 22.68774 63.85240 0.33739 8.10163
December 744.00000 22.46677 63.15638 0.25130 7.14243
           
Annual Sum or Average 8760.00000 22.78998 63.25896 -0.0128 8.79810
Minimum of Months 672.00000 22.39074 60.77395 -0.4817 6.78465
Maximum of Months 744.00000 23.08423 64.67087 0.40858 10.73362



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.61785 60.07690 0.27944 7.45967
February 672.00000 22.73727 60.20153 0.32345 7.99638
March 744.00000 22.83163 60.76875 0.36168 8.60563
April 720.00000 23.00887 63.63989 0.44736 9.68030
May 744.00000 23.18389 63.62913 -0.3874 8.89274
June 720.00000 23.27246 63.09116 -0.3415 8.15210
July 744.00000 23.28844 62.73911 -0.3308 7.90583
August 744.00000 23.22480 63.42349 -0.3665 8.58075
September 720.00000 23.19319 63.21328 -0.3789 8.80687
October 744.00000 23.06643 63.95194 0.47296 10.15363
November 720.00000 22.89758 63.14176 0.40270 9.06357
December 744.00000 22.69614 62.41253 0.32221 7.95533
           
Annual Sum or Average 8760.00000 23.00272 62.53502 0.06534 8.60588
Minimum of Months 672.00000 22.61785 60.07690 -0.3874 7.45967
Maximum of Months 744.00000 23.28844 63.95194 0.47296 10.15363



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.99184 56.53808 1.21574 37.16937
February 672.00000 23.99181 56.92166 1.23407 38.08882
March 744.00000 23.99179 57.64290 1.25614 39.09909
April 720.00000 23.99189 60.60624 1.31311 41.82949
May 744.00000 23.99184 60.99445 0.79394 21.31594
June 720.00000 23.99197 60.71721 0.82310 22.21417
July 744.00000 23.99211 60.44656 0.83851 22.85526
August 744.00000 23.99203 60.88828 0.80697 21.68098
September 720.00000 23.99215 60.58972 0.81614 22.00923
October 744.00000 23.99199 60.95132 1.33186 42.67867
November 720.00000 23.99195 59.87800 1.28567 40.47199
December 744.00000 23.99188 58.79772 1.23635 38.09195
           
Annual Sum or Average 8760.00000 23.99194 59.59337 1.07825 32.25168
Minimum of Months 672.00000 23.99179 56.53808 0.79394 21.31594
Maximum of Months 744.00000 23.99215 60.99445 1.33186 42.67867



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.12296 56.30979 0.00421 5.56044
February 672.00000 22.30296 56.22991 0.05096 5.64854
March 744.00000 22.39564 56.99288 0.08078 5.82188
April 720.00000 22.88786 59.16440 0.22239 6.17189
May 744.00000 23.39662 58.74453 -0.6011 12.74984
June 720.00000 23.72887 57.89573 -0.4850 9.98612
July 744.00000 23.82768 57.31225 -0.4509 9.28694
August 744.00000 23.59665 58.58145 -0.5291 11.03952
September 720.00000 23.64830 57.99170 -0.5123 10.61093
October 744.00000 23.33465 58.98803 0.34015 7.45080
November 720.00000 22.89784 58.57082 0.22214 6.38413
December 744.00000 22.35537 58.50037 0.07864 5.71709
           
Annual Sum or Average 8760.00000 23.04462 57.94911 -0.1330 8.05253
Minimum of Months 672.00000 22.12296 56.22991 -0.6011 5.56044
Maximum of Months 744.00000 23.82768 59.16440 0.34015 12.74984



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.61432 59.07100 0.09884 5.60362
February 672.00000 22.67185 59.40430 0.11543 5.64245
March 744.00000 22.79281 60.02109 0.15142 5.86129
April 720.00000 23.19026 62.37688 0.26892 6.60765
May 744.00000 23.37380 62.81462 -0.6586 14.24132
June 720.00000 23.63906 62.06493 -0.5676 11.81761
July 744.00000 23.76885 61.35925 -0.5247 10.81127
August 744.00000 23.63476 62.24287 -0.5681 11.89297
September 720.00000 23.74044 61.49532 -0.5332 11.05403
October 744.00000 23.65652 61.86815 0.38830 8.17333
November 720.00000 23.23913 61.55107 0.27690 6.80754
December 744.00000 22.73042 61.49382 0.14380 5.88705
           
Annual Sum or Average 8760.00000 23.25697 61.32318 -0.1191 8.72107
Minimum of Months 672.00000 22.61432 59.07100 -0.6586 5.60362
Maximum of Months 744.00000 23.76885 62.81462 0.38830 14.24132



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.48809 56.05247 0.31090 7.71048
February 672.00000 23.62592 55.82730 0.35142 8.36414
March 744.00000 23.70311 56.28420 0.37988 8.69754
April 720.00000 23.96923 58.46492 0.47514 9.78289
May 744.00000 23.99729 58.58438 -0.4000 8.34326
June 720.00000 23.99964 58.10043 -0.3865 8.11756
July 744.00000 23.99964 57.68470 -0.3808 8.02912
August 744.00000 23.99755 58.45584 -0.3893 8.16825
September 720.00000 23.99949 57.97516 -0.3858 8.13364
October 744.00000 23.99836 58.55954 0.50006 10.23077
November 720.00000 23.85380 58.16438 0.44204 9.39429
December 744.00000 23.50330 58.37126 0.33653 7.99992
           
Annual Sum or Average 8760.00000 23.84520 57.72075 0.06921 8.57975
Minimum of Months 672.00000 23.48809 55.82730 -0.4000 7.71048
Maximum of Months 744.00000 23.99964 58.58438 0.50006 10.23077



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.83755 55.69902 0.35673 7.95725
February 672.00000 23.87398 54.25340 0.36728 8.17769
March 744.00000 23.88398 55.02006 0.38206 8.38576
April 720.00000 23.99988 56.57211 0.44843 9.24347
May 744.00000 23.99982 57.10930 -0.4170 8.63413
June 720.00000 23.99978 56.82012 -0.3908 8.18704
July 744.00000 23.99977 56.42826 -0.3834 8.06630
August 744.00000 23.99977 57.40223 -0.4006 8.35311
September 720.00000 23.99978 56.82860 -0.3976 8.32407
October 744.00000 23.99981 57.33801 0.48096 9.83618
November 720.00000 23.98501 56.34848 0.44308 9.19051
December 744.00000 23.87608 57.03759 0.38908 8.38240
           
Annual Sum or Average 8760.00000 23.95481 56.41984 0.07130 8.56273
Minimum of Months 672.00000 23.83755 54.25340 -0.4170 7.95725
Maximum of Months 744.00000 23.99988 57.40223 0.48096 9.83618



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.158050E+12 125475.18 06-JAN-16:13 744.00 0.518419E+12 0.00 0.676469E+12 3.22 4.21 02-JAN-22:53 0.00 0.00
February 0.162096E+12 146216.75 11-FEB-16:13 672.00 0.530743E+12 0.00 0.692840E+12 3.23 4.07 11-FEB-22:54 0.00 0.00
March 0.194444E+12 143750.38 13-MAR-15:13 744.00 0.652853E+12 0.00 0.847297E+12 3.29 4.12 09-MAR-22:52 0.00 0.00
April 0.227302E+12 157872.61 14-APR-15:13 720.00 0.760872E+12 0.00 0.988175E+12 3.31 4.08 26-APR-21:53 0.00 0.00
May 0.283910E+12 167335.61 29-MAY-18:03 744.00 0.974152E+12 0.00 0.125806E+13 3.42 4.09 25-MAY-21:53 0.00 0.00
June 0.307885E+12 175590.28 08-JUN-18:03 720.00 0.106064E+13 0.00 0.136852E+13 3.44 4.08 18-JUN-21:53 0.00 0.00
July 0.330148E+12 188678.35 27-JUL-18:03 744.00 0.113378E+13 0.00 0.146393E+13 3.44 4.22 14-JUL-21:52 0.00 0.00
August 0.325256E+12 172600.22 21-AUG-16:00 744.00 0.111759E+13 0.00 0.144284E+13 3.43 4.17 12-AUG-08:53 0.00 0.00
September 0.310333E+12 184523.51 18-SEP-18:03 720.00 0.107678E+13 0.00 0.138711E+13 3.47 4.17 04-SEP-21:51 0.00 0.00
October 0.292667E+12 169741.47 03-OCT-15:13 744.00 0.101939E+13 0.00 0.131206E+13 3.47 4.06 27-OCT-21:53 0.00 0.00
November 0.234231E+12 154903.40 30-NOV-19:03 720.00 0.812096E+12 0.00 0.104633E+13 3.41 4.16 24-NOV-22:53 0.00 0.00
December 0.182482E+12 141003.98 25-DEC-22:53 744.00 0.619139E+12 0.00 0.801621E+12 3.30 4.22 24-DEC-22:53 0.00 0.00
                         
Annual Sum or Average 0.300881E+13     8760.00 0.102765E+14 0.00 0.132853E+14 3.37     0.00 0.00
Minimum of Months 0.158050E+12 125475.18   672.00 0.518419E+12 0.00 0.676469E+12 3.22 4.06   0.00 0.00
Maximum of Months 0.330148E+12 188678.35   744.00 0.113378E+13 0.00 0.146393E+13 3.47 4.22   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.222614E+09 0.00 120.76 18937.97 25-JAN-19:47 0.00 43.67 46.57 0.00 0.00 0.00 0.09 25-JAN-19:47
February 0.235049E+09 0.00 66.53 21217.82 04-FEB-09:06 0.00 40.62 42.38 0.00 0.00 0.00 0.10 04-FEB-09:06
March 0.239599E+09 0.00 61.05 20884.21 16-MAR-08:05 0.00 36.18 38.26 0.00 0.00 0.00 0.09 16-MAR-08:05
April 28476372.21 0.00 6.64 15406.61 24-APR-21:56 0.00 38.98 39.17 0.00 0.00 0.00 0.07 24-APR-21:56
May 14817011.04 0.00 2.89 11364.13 27-MAY-08:57 0.00 40.22 40.30 0.00 0.00 0.00 0.05 27-MAY-08:57
June 12348377.56 0.00 2.24 12159.06 15-JUN-08:56 0.00 44.17 44.22 0.00 0.00 0.00 0.06 15-JUN-08:56
July 5562456.99 0.00 1.27 3709.96 17-JUL-15:18 0.00 46.03 46.05 0.00 0.00 0.00 0.02 17-JUL-15:18
August 17412008.62 0.00 5.00 10092.66 28-AUG-08:56 0.00 46.63 46.73 0.00 0.00 0.00 0.05 28-AUG-08:56
September 13209768.70 0.00 2.47 5947.52 05-SEP-08:28 0.00 47.05 47.09 0.00 0.00 0.00 0.03 05-SEP-08:28
October 17748438.42 0.00 3.55 9855.78 21-OCT-21:56 0.00 46.78 46.84 0.00 0.00 0.00 0.04 21-OCT-21:56
November 68126996.30 0.00 30.77 13267.95 13-NOV-16:16 0.00 43.76 44.51 0.00 0.00 0.00 0.06 13-NOV-16:16
December 0.271989E+09 0.00 122.21 19381.95 17-DEC-22:57 0.00 40.31 43.51 0.00 0.00 0.00 0.09 17-DEC-22:57
                           
Annual Sum or Average 0.114695E+10 0.00 425.38     0.00 42.88 43.82 0.00 0.00 0.00    
Minimum of Months 5562456.99 0.00 1.27 3709.96   0.00 36.18 38.26 0.00 0.00 0.00 0.02  
Maximum of Months 0.271989E+09 0.00 122.21 21217.82   0.00 47.05 47.09 0.00 0.00 0.00 0.10  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.386410E+12 0.00 743.58 0.282413E+12 0.00 0.00 0.00 0.00 375198.43 06-JAN-23:00 200420.90 13-JAN-22:00 0.00 0.00 0.00
February 0.398541E+12 0.00 670.42 0.291489E+12 0.00 0.00 0.00 0.00 376278.00 11-FEB-19:03 200141.78 11-FEB-18:15 0.00 0.00 0.00
March 0.495657E+12 0.00 742.97 0.344253E+12 0.00 0.00 0.00 0.00 380767.64 09-MAR-21:30 221259.05 13-MAR-18:10 0.00 0.00 0.00
April 0.579168E+12 0.00 720.00 0.400047E+12 0.00 0.00 0.00 0.00 375700.61 01-APR-17:15 238942.59 17-APR-18:10 0.00 0.00 0.00
May 0.752110E+12 0.00 744.00 0.467088E+12 0.00 0.00 0.00 0.00 405701.76 24-MAY-18:20 245668.03 22-MAY-18:10 0.00 0.00 0.00
June 0.822531E+12 0.00 720.00 0.481687E+12 0.00 0.00 0.00 0.00 427372.85 08-JUN-18:10 249124.36 29-JUN-19:10 0.00 0.00 0.00
July 0.879030E+12 0.00 744.00 0.513409E+12 0.00 0.00 0.00 0.00 449513.25 27-JUL-21:00 263790.61 29-JUL-18:10 0.00 0.00 0.00
August 0.870110E+12 0.00 744.00 0.502051E+12 0.00 0.00 0.00 0.00 430207.03 21-AUG-21:00 250701.43 02-AUG-21:00 0.00 0.00 0.00
September 0.832710E+12 0.00 720.00 0.488004E+12 0.00 0.00 0.00 0.00 444512.03 25-SEP-21:20 255762.32 08-SEP-20:20 0.00 0.00 0.00
October 0.782628E+12 0.00 744.00 0.475860E+12 0.00 0.00 0.00 0.00 428316.71 03-OCT-21:00 239271.14 05-OCT-18:10 0.00 0.00 0.00
November 0.621609E+12 0.00 720.00 0.389191E+12 0.00 0.00 0.00 0.00 419261.38 21-NOV-20:50 227347.60 03-NOV-21:00 0.00 0.00 0.00
December 0.470277E+12 0.00 741.17 0.310781E+12 0.00 0.00 0.00 0.00 416677.03 25-DEC-20:10 210219.05 08-DEC-21:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.789078E+13 0.00 8754.14 0.494627E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.386410E+12 0.00 670.42 0.282413E+12 0.00 0.00 0.00 0.00 375198.43   200141.78   0.00 0.00 0.00
Maximum of Months 0.879030E+12 0.00 744.00 0.513409E+12 0.00 0.00 0.00 0.00 449513.25   263790.61   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.291328E+11 0.00 465.50 0.171881E+11 0.00 0.00 0.00 0.00 44155.10 07-JAN-09:02 18743.10 07-JAN-13:15 0.00 0.00 0.00
February 0.316601E+11 0.00 456.33 0.197265E+11 0.00 0.00 0.00 0.00 41142.31 11-FEB-19:02 19032.61 11-FEB-13:20 0.00 0.00 0.00
March 0.384607E+11 0.00 507.67 0.242583E+11 0.00 0.00 0.00 0.00 45817.78 14-MAR-08:62 19331.24 13-MAR-15:12 0.00 0.00 0.00
April 0.452088E+11 0.00 548.83 0.291241E+11 0.00 0.00 0.00 0.00 38973.05 22-APR-06:50 20281.32 17-APR-15:12 0.00 0.00 0.00
May 0.554947E+11 0.00 568.33 0.323240E+11 0.00 0.00 0.00 0.00 48557.43 28-MAY-18:03 20966.14 22-MAY-13:00 0.00 0.00 0.00
June 0.600198E+11 0.00 550.00 0.323998E+11 0.00 0.00 0.00 0.00 43341.73 18-JUN-20:50 20361.19 10-JUN-15:12 0.00 0.00 0.00
July 0.624021E+11 0.00 568.33 0.336486E+11 0.00 0.00 0.00 0.00 44901.42 02-JUL-18:03 21660.65 29-JUL-15:12 0.00 0.00 0.00
August 0.634315E+11 0.00 568.33 0.336299E+11 0.00 0.00 0.00 0.00 45991.92 12-AUG-08:03 20884.46 23-AUG-12:20 0.00 0.00 0.00
September 0.595970E+11 0.00 550.00 0.322242E+11 0.00 0.00 0.00 0.00 44301.83 04-SEP-21:51 20503.52 08-SEP-15:12 0.00 0.00 0.00
October 0.571178E+11 0.00 568.33 0.323065E+11 0.00 0.00 0.00 0.00 45227.74 01-OCT-08:15 20334.43 03-OCT-15:12 0.00 0.00 0.00
November 0.478862E+11 0.00 526.67 0.268434E+11 0.00 0.00 0.00 0.00 47104.65 08-NOV-09:02 19217.01 17-NOV-16:12 0.00 0.00 0.00
December 0.368102E+11 0.00 491.50 0.204584E+11 0.00 0.00 0.00 0.00 49518.84 23-DEC-19:03 18894.37 10-DEC-13:15 0.00 0.00 0.00
                               
Annual Sum or Average 0.587222E+12 0.00 6369.83 0.334132E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.291328E+11 0.00 456.33 0.171881E+11 0.00 0.00 0.00 0.00 38973.05   18743.10   0.00 0.00 0.00
Maximum of Months 0.634315E+11 0.00 568.33 0.336486E+11 0.00 0.00 0.00 0.00 49518.84   21660.65   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.520708E+10 0.00 632.30 0.250046E+10 0.00 0.00 0.00 0.00 14675.64 07-JAN-09:02 11637.57 24-JAN-19:01 0.00 0.00 0.00
February 0.566563E+10 0.00 578.98 0.293942E+10 0.00 0.00 0.00 0.00 14405.06 02-FEB-09:02 11608.94 03-FEB-16:11 0.00 0.00 0.00
March 0.716717E+10 0.00 657.93 0.390596E+10 0.00 0.00 0.00 0.00 15108.97 19-MAR-08:62 11635.72 15-MAR-15:11 0.00 0.00 0.00
April 0.854302E+10 0.00 668.06 0.494600E+10 0.00 0.00 0.00 0.00 13461.24 29-APR-18:02 10756.65 22-APR-18:02 0.00 0.00 0.00
May 0.968983E+10 0.00 705.72 0.564472E+10 0.00 0.00 0.00 0.00 13765.34 24-MAY-18:02 10790.01 22-MAY-15:12 0.00 0.00 0.00
June 0.998796E+10 0.00 685.39 0.584895E+10 0.00 0.00 0.00 0.00 13017.84 13-JUN-08:61 10779.54 30-JUN-15:12 0.00 0.00 0.00
July 0.111545E+11 0.00 713.20 0.677396E+10 0.00 0.00 0.00 0.00 12617.61 02-JUL-18:02 10778.92 25-JUL-18:02 0.00 0.00 0.00
August 0.106373E+11 0.00 708.87 0.629751E+10 0.00 0.00 0.00 0.00 14475.62 12-AUG-08:62 10797.48 22-AUG-15:12 0.00 0.00 0.00
September 0.104276E+11 0.00 687.99 0.621063E+10 0.00 0.00 0.00 0.00 13165.15 05-SEP-08:62 10759.43 26-SEP-18:02 0.00 0.00 0.00
October 0.100883E+11 0.00 709.06 0.592360E+10 0.00 0.00 0.00 0.00 13968.23 31-OCT-08:62 10822.97 05-OCT-18:02 0.00 0.00 0.00
November 0.771167E+10 0.00 660.42 0.411450E+10 0.00 0.00 0.00 0.00 14296.81 24-NOV-09:02 10804.54 03-NOV-15:12 0.00 0.00 0.00
December 0.600456E+10 0.00 638.62 0.299188E+10 0.00 0.00 0.00 0.00 15094.49 23-DEC-09:02 11639.42 20-DEC-16:11 0.00 0.00 0.00
                               
Annual Sum or Average 0.102285E+12 0.00 8046.53 0.580976E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.520708E+10 0.00 578.98 0.250046E+10 0.00 0.00 0.00 0.00 12617.61   10756.65   0.00 0.00 0.00
Maximum of Months 0.111545E+11 0.00 713.20 0.677396E+10 0.00 0.00 0.00 0.00 15108.97   11639.42   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.250686E+10 0.00 377.39 0.100353E+10 0.00 0.00 0.00 0.00 14800.08 07-JAN-09:52 11601.59 24-JAN-19:01 0.00 0.00 0.00
February 0.320106E+10 0.00 356.09 0.153755E+10 0.00 0.00 0.00 0.00 14627.87 17-FEB-09:21 11279.81 03-FEB-19:02 0.00 0.00 0.00
March 0.487024E+10 0.00 455.70 0.257036E+10 0.00 0.00 0.00 0.00 15726.62 14-MAR-08:21 11685.02 15-MAR-20:11 0.00 0.00 0.00
April 0.695139E+10 0.00 517.64 0.409182E+10 0.00 0.00 0.00 0.00 14714.06 14-APR-07:52 11060.78 18-APR-21:51 0.00 0.00 0.00
May 0.940996E+10 0.00 667.98 0.553738E+10 0.00 0.00 0.00 0.00 15183.24 30-MAY-07:52 10891.90 15-MAY-18:02 0.00 0.00 0.00
June 0.100276E+11 0.00 673.38 0.590679E+10 0.00 0.00 0.00 0.00 15087.41 13-JUN-07:51 10861.87 30-JUN-15:12 0.00 0.00 0.00
July 0.110698E+11 0.00 695.18 0.677776E+10 0.00 0.00 0.00 0.00 14452.75 14-JUL-21:51 11264.14 05-JUL-17:52 0.00 0.00 0.00
August 0.103567E+11 0.00 695.63 0.608871E+10 0.00 0.00 0.00 0.00 15051.31 12-AUG-08:52 11464.19 23-AUG-17:52 0.00 0.00 0.00
September 0.961449E+10 0.00 658.88 0.556026E+10 0.00 0.00 0.00 0.00 14704.53 16-SEP-08:61 10917.95 13-SEP-15:12 0.00 0.00 0.00
October 0.864338E+10 0.00 660.09 0.480400E+10 0.00 0.00 0.00 0.00 14808.58 31-OCT-08:32 10924.87 14-OCT-15:12 0.00 0.00 0.00
November 0.570977E+10 0.00 531.55 0.284607E+10 0.00 0.00 0.00 0.00 14772.57 19-NOV-09:31 10829.42 11-NOV-09:01 0.00 0.00 0.00
December 0.336086E+10 0.00 400.74 0.154853E+10 0.00 0.00 0.00 0.00 15280.29 10-DEC-09:01 11771.48 20-DEC-16:11 0.00 0.00 0.00
                               
Annual Sum or Average 0.857221E+11 0.00 6690.24 0.482728E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.250686E+10 0.00 356.09 0.100353E+10 0.00 0.00 0.00 0.00 14452.75   10829.42   0.00 0.00 0.00
Maximum of Months 0.110698E+11 0.00 695.63 0.677776E+10 0.00 0.00 0.00 0.00 15726.62   11771.48   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.409144E+11 0.00 724.50 0.246203E+11 0.00 0.00 0.00 0.00 38724.10 02-JAN-14:30 31848.06 17-JAN-14:05 0.00 0.00 0.00
February 0.360658E+11 0.00 652.01 0.204410E+11 0.00 0.00 0.00 0.00 35800.00 11-FEB-14:40 31485.74 11-FEB-14:20 0.00 0.00 0.00
March 0.364503E+11 0.00 724.22 0.179507E+11 0.00 0.00 0.00 0.00 30041.41 04-MAR-08:52 23328.79 02-MAR-14:30 0.00 0.00 0.00
April 0.365997E+11 0.00 707.03 0.163604E+11 0.00 0.00 0.00 0.00 26854.19 14-APR-16:20 17301.55 15-APR-20:10 0.00 0.00 0.00
May 0.405898E+11 0.00 727.00 0.173653E+11 0.00 0.00 0.00 0.00 28811.74 14-MAY-08:00 16637.78 14-MAY-08:00 0.00 0.00 0.00
June 0.438364E+11 0.00 706.50 0.194588E+11 0.00 0.00 0.00 0.00 28941.12 25-JUN-08:00 17670.04 29-JUN-20:20 0.00 0.00 0.00
July 0.484215E+11 0.00 741.00 0.228596E+11 0.00 0.00 0.00 0.00 30550.16 29-JUL-08:00 19840.80 29-JUL-19:10 0.00 0.00 0.00
August 0.484160E+11 0.00 739.11 0.228913E+11 0.00 0.00 0.00 0.00 30981.30 20-AUG-08:00 20218.07 20-AUG-08:00 0.00 0.00 0.00
September 0.536174E+11 0.00 719.33 0.293283E+11 0.00 0.00 0.00 0.00 35289.94 30-SEP-15:10 28739.96 30-SEP-13:50 0.00 0.00 0.00
October 0.574658E+11 0.00 741.00 0.340518E+11 0.00 0.00 0.00 0.00 38946.88 25-OCT-17:25 31568.37 24-OCT-13:30 0.00 0.00 0.00
November 0.492644E+11 0.00 710.17 0.283336E+11 0.00 0.00 0.00 0.00 38890.73 07-NOV-14:05 31747.56 26-NOV-13:00 0.00 0.00 0.00
December 0.431508E+11 0.00 732.23 0.243295E+11 0.00 0.00 0.00 0.00 39144.84 09-DEC-08:40 31307.29 04-DEC-16:27 0.00 0.00 0.00
                               
Annual Sum or Average 0.534792E+12 0.00 8624.10 0.277991E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.360658E+11 0.00 652.01 0.163604E+11 0.00 0.00 0.00 0.00 26854.19   16637.78   0.00 0.00 0.00
Maximum of Months 0.574658E+11 0.00 741.00 0.340518E+11 0.00 0.00 0.00 0.00 39144.84   31848.06   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.263261E+11 0.00 337.52 0.141966E+11 0.00 0.00 0.00 0.00 98338.96 07-JAN-09:52 75249.50 24-JAN-19:01 0.00 0.00 0.00
February 0.279084E+11 0.00 318.82 0.162302E+11 0.00 0.00 0.00 0.00 97056.48 17-FEB-09:21 76106.98 03-FEB-19:02 0.00 0.00 0.00
March 0.374132E+11 0.00 392.03 0.220315E+11 0.00 0.00 0.00 0.00 105639.24 14-MAR-08:21 75338.55 15-MAR-20:11 0.00 0.00 0.00
April 0.470134E+11 0.00 442.36 0.288714E+11 0.00 0.00 0.00 0.00 97139.11 22-APR-08:21 72122.57 17-APR-18:02 0.00 0.00 0.00
May 0.634092E+11 0.00 585.82 0.396724E+11 0.00 0.00 0.00 0.00 98530.32 25-MAY-21:51 72384.37 03-MAY-08:61 0.00 0.00 0.00
June 0.683060E+11 0.00 597.78 0.439564E+11 0.00 0.00 0.00 0.00 99089.73 18-JUN-21:51 72557.27 17-JUN-08:62 0.00 0.00 0.00
July 0.719689E+11 0.00 628.13 0.468097E+11 0.00 0.00 0.00 0.00 93644.46 14-JUL-21:51 71983.77 16-JUL-08:62 0.00 0.00 0.00
August 0.673123E+11 0.00 605.64 0.420881E+11 0.00 0.00 0.00 0.00 98997.71 12-AUG-08:52 71493.50 11-AUG-08:61 0.00 0.00 0.00
September 0.633540E+11 0.00 571.35 0.393439E+11 0.00 0.00 0.00 0.00 101850.50 16-SEP-07:53 71529.54 23-SEP-08:62 0.00 0.00 0.00
October 0.573564E+11 0.00 554.09 0.335251E+11 0.00 0.00 0.00 0.00 96951.86 31-OCT-08:32 71388.26 17-OCT-18:02 0.00 0.00 0.00
November 0.431352E+11 0.00 439.25 0.246125E+11 0.00 0.00 0.00 0.00 97101.34 22-NOV-09:01 72421.19 15-NOV-19:01 0.00 0.00 0.00
December 0.298986E+11 0.00 357.67 0.161915E+11 0.00 0.00 0.00 0.00 99831.13 10-DEC-09:01 74847.95 20-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.603402E+12 0.00 5830.46 0.367529E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.263261E+11 0.00 318.82 0.141966E+11 0.00 0.00 0.00 0.00 93644.46   71388.26   0.00 0.00 0.00
Maximum of Months 0.719689E+11 0.00 628.13 0.468097E+11 0.00 0.00 0.00 0.00 105639.24   76106.98   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.544288E+10 0.00 651.68 0.277028E+10 0.00 0.00 0.00 0.00 13101.19 07-JAN-09:02 10530.09 24-JAN-19:01 0.00 0.00 0.00
February 0.568064E+10 0.00 593.27 0.296690E+10 0.00 0.00 0.00 0.00 12590.91 10-FEB-09:02 10342.13 03-FEB-16:11 0.00 0.00 0.00
March 0.706272E+10 0.00 683.18 0.381609E+10 0.00 0.00 0.00 0.00 13728.98 19-MAR-08:62 10543.19 15-MAR-15:11 0.00 0.00 0.00
April 0.849002E+10 0.00 688.19 0.484887E+10 0.00 0.00 0.00 0.00 12229.53 29-APR-18:02 9782.49 10-APR-18:02 0.00 0.00 0.00
May 0.971086E+10 0.00 715.20 0.568140E+10 0.00 0.00 0.00 0.00 12643.98 24-MAY-18:02 9747.91 31-MAY-15:12 0.00 0.00 0.00
June 0.104991E+11 0.00 697.35 0.638498E+10 0.00 0.00 0.00 0.00 11062.78 18-JUN-18:02 9759.70 14-JUN-15:12 0.00 0.00 0.00
July 0.114690E+11 0.00 722.80 0.721317E+10 0.00 0.00 0.00 0.00 11317.58 02-JUL-18:02 9761.16 21-JUL-15:12 0.00 0.00 0.00
August 0.106492E+11 0.00 715.64 0.643459E+10 0.00 0.00 0.00 0.00 13145.22 12-AUG-08:62 9768.50 22-AUG-15:12 0.00 0.00 0.00
September 0.107840E+11 0.00 697.35 0.666941E+10 0.00 0.00 0.00 0.00 11792.63 05-SEP-08:62 9756.96 09-SEP-15:12 0.00 0.00 0.00
October 0.102257E+11 0.00 717.24 0.614268E+10 0.00 0.00 0.00 0.00 12659.02 31-OCT-08:62 9802.73 12-OCT-15:12 0.00 0.00 0.00
November 0.776259E+10 0.00 671.65 0.425249E+10 0.00 0.00 0.00 0.00 12996.12 24-NOV-09:02 9730.86 15-NOV-16:11 0.00 0.00 0.00
December 0.563817E+10 0.00 639.54 0.279878E+10 0.00 0.00 0.00 0.00 13725.50 23-DEC-09:02 10545.45 20-DEC-16:11 0.00 0.00 0.00
                               
Annual Sum or Average 0.103415E+12 0.00 8193.09 0.599796E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.544288E+10 0.00 593.27 0.277028E+10 0.00 0.00 0.00 0.00 11062.78   9730.86   0.00 0.00 0.00
Maximum of Months 0.114690E+11 0.00 722.80 0.721317E+10 0.00 0.00 0.00 0.00 13728.98   10545.45   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.272071E+10 0.00 386.58 0.122397E+10 0.00 0.00 0.00 0.00 13515.22 07-JAN-09:52 10187.65 24-JAN-19:01 0.00 0.00 0.00
February 0.318885E+10 0.00 381.68 0.156732E+10 0.00 0.00 0.00 0.00 13546.85 17-FEB-09:21 10257.99 28-FEB-09:51 0.00 0.00 0.00
March 0.480083E+10 0.00 477.14 0.251534E+10 0.00 0.00 0.00 0.00 14323.47 04-MAR-08:52 10270.71 15-MAR-20:11 0.00 0.00 0.00
April 0.687972E+10 0.00 529.63 0.396968E+10 0.00 0.00 0.00 0.00 13809.76 16-APR-08:51 10378.11 20-APR-08:51 0.00 0.00 0.00
May 0.941868E+10 0.00 675.98 0.557138E+10 0.00 0.00 0.00 0.00 13910.35 30-MAY-07:52 9852.77 19-MAY-15:12 0.00 0.00 0.00
June 0.105360E+11 0.00 683.20 0.648555E+10 0.00 0.00 0.00 0.00 14242.57 13-JUN-07:51 9943.35 22-JUN-07:52 0.00 0.00 0.00
July 0.113733E+11 0.00 703.69 0.720878E+10 0.00 0.00 0.00 0.00 13239.93 14-JUL-21:51 9937.53 05-JUL-17:52 0.00 0.00 0.00
August 0.103654E+11 0.00 702.67 0.619068E+10 0.00 0.00 0.00 0.00 13654.52 12-AUG-08:52 10191.65 23-AUG-17:52 0.00 0.00 0.00
September 0.996775E+10 0.00 667.27 0.595571E+10 0.00 0.00 0.00 0.00 14146.38 16-SEP-07:53 9963.91 17-SEP-07:52 0.00 0.00 0.00
October 0.875420E+10 0.00 666.32 0.489902E+10 0.00 0.00 0.00 0.00 13871.06 23-OCT-08:11 9834.88 25-OCT-15:12 0.00 0.00 0.00
November 0.572012E+10 0.00 541.93 0.296586E+10 0.00 0.00 0.00 0.00 14155.70 22-NOV-08:52 9692.09 11-NOV-09:01 0.00 0.00 0.00
December 0.308132E+10 0.00 388.46 0.143443E+10 0.00 0.00 0.00 0.00 14032.05 10-DEC-09:01 9909.00 20-DEC-16:11 0.00 0.00 0.00
                               
Annual Sum or Average 0.868069E+11 0.00 6804.55 0.499877E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.272071E+10 0.00 381.68 0.122397E+10 0.00 0.00 0.00 0.00 13239.93   9692.09   0.00 0.00 0.00
Maximum of Months 0.113733E+11 0.00 703.69 0.720878E+10 0.00 0.00 0.00 0.00 14323.47   10378.11   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.115753E+10 0.00 573.98 0.545594E+09 0.00 0.00 0.00 0.00 4229.98 07-JAN-09:02 3204.13 24-JAN-19:01 0.00 0.00 0.00
February 0.135624E+10 0.00 560.62 0.693232E+09 0.00 0.00 0.00 0.00 4096.40 02-FEB-09:02 3204.11 03-FEB-16:11 0.00 0.00 0.00
March 0.175519E+10 0.00 633.05 0.933268E+09 0.00 0.00 0.00 0.00 4283.19 19-MAR-08:62 3203.62 15-MAR-15:11 0.00 0.00 0.00
April 0.212766E+10 0.00 669.51 0.118977E+10 0.00 0.00 0.00 0.00 3871.05 16-APR-08:62 2962.00 20-APR-18:01 0.00 0.00 0.00
May 0.246122E+10 0.00 703.83 0.137368E+10 0.00 0.00 0.00 0.00 3884.66 24-MAY-18:02 2964.94 07-MAY-15:12 0.00 0.00 0.00
June 0.253662E+10 0.00 685.03 0.141168E+10 0.00 0.00 0.00 0.00 3800.17 13-JUN-08:61 2967.06 01-JUN-18:02 0.00 0.00 0.00
July 0.284305E+10 0.00 712.66 0.166141E+10 0.00 0.00 0.00 0.00 3578.88 24-JUL-08:62 2965.48 24-JUL-18:02 0.00 0.00 0.00
August 0.269041E+10 0.00 705.84 0.153049E+10 0.00 0.00 0.00 0.00 4238.78 12-AUG-08:62 2963.66 05-AUG-15:12 0.00 0.00 0.00
September 0.260727E+10 0.00 684.48 0.148208E+10 0.00 0.00 0.00 0.00 3873.37 05-SEP-08:62 2963.44 07-SEP-15:12 0.00 0.00 0.00
October 0.246365E+10 0.00 704.06 0.137517E+10 0.00 0.00 0.00 0.00 4069.11 31-OCT-08:62 2971.50 16-OCT-18:02 0.00 0.00 0.00
November 0.183257E+10 0.00 639.64 0.931727E+09 0.00 0.00 0.00 0.00 4099.34 24-NOV-09:02 2940.12 21-NOV-16:12 0.00 0.00 0.00
December 0.138213E+10 0.00 583.58 0.674394E+09 0.00 0.00 0.00 0.00 4360.68 23-DEC-09:02 3126.92 20-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.252135E+11 0.00 7856.28 0.138025E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.115753E+10 0.00 560.62 0.545594E+09 0.00 0.00 0.00 0.00 3578.88   2940.12   0.00 0.00 0.00
Maximum of Months 0.284305E+10 0.00 712.66 0.166141E+10 0.00 0.00 0.00 0.00 4360.68   3204.13   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.505100E+09 0.00 319.54 0.191720E+09 0.00 0.00 0.00 0.00 4192.42 07-JAN-09:52 3214.75 24-JAN-19:01 0.00 0.00 0.00
February 0.756860E+09 0.00 346.46 0.352607E+09 0.00 0.00 0.00 0.00 4159.25 17-FEB-09:21 3081.63 03-FEB-17:22 0.00 0.00 0.00
March 0.119641E+10 0.00 435.41 0.608119E+09 0.00 0.00 0.00 0.00 4468.28 14-MAR-08:21 3228.95 15-MAR-20:11 0.00 0.00 0.00
April 0.176488E+10 0.00 522.27 0.100038E+10 0.00 0.00 0.00 0.00 4184.49 22-APR-08:21 3167.85 18-APR-21:51 0.00 0.00 0.00
May 0.240206E+10 0.00 667.75 0.135832E+10 0.00 0.00 0.00 0.00 4362.00 30-MAY-07:52 2990.71 07-MAY-15:12 0.00 0.00 0.00
June 0.255243E+10 0.00 671.66 0.143559E+10 0.00 0.00 0.00 0.00 4293.07 13-JUN-07:51 3030.45 13-JUN-18:11 0.00 0.00 0.00
July 0.282811E+10 0.00 694.35 0.166696E+10 0.00 0.00 0.00 0.00 4137.75 14-JUL-21:51 3146.98 05-JUL-17:52 0.00 0.00 0.00
August 0.262230E+10 0.00 693.72 0.147334E+10 0.00 0.00 0.00 0.00 4247.72 12-AUG-08:52 3217.90 23-AUG-17:52 0.00 0.00 0.00
September 0.240739E+10 0.00 658.08 0.131789E+10 0.00 0.00 0.00 0.00 4197.62 16-SEP-08:61 3000.62 02-SEP-18:02 0.00 0.00 0.00
October 0.210425E+10 0.00 659.26 0.108620E+10 0.00 0.00 0.00 0.00 4205.98 26-OCT-08:61 2997.78 18-OCT-18:02 0.00 0.00 0.00
November 0.134679E+10 0.00 516.29 0.617193E+09 0.00 0.00 0.00 0.00 4181.31 19-NOV-09:31 3001.61 01-NOV-15:12 0.00 0.00 0.00
December 0.755862E+09 0.00 349.80 0.329339E+09 0.00 0.00 0.00 0.00 4388.39 10-DEC-09:01 2973.59 26-DEC-19:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.212424E+11 0.00 6534.59 0.114376E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.505100E+09 0.00 319.54 0.191720E+09 0.00 0.00 0.00 0.00 4137.75   2973.59   0.00 0.00 0.00
Maximum of Months 0.282811E+10 0.00 694.35 0.166696E+10 0.00 0.00 0.00 0.00 4468.28   3228.95   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.103238E+11 0.00 668.91 0.645531E+10 0.00 0.00 0.00 0.00 17251.20 07-JAN-09:02 13283.48 25-JAN-16:11 0.00 0.00 0.00
February 0.971900E+10 0.00 606.40 0.590021E+10 0.00 0.00 0.00 0.00 16857.30 02-FEB-09:02 12424.77 03-FEB-16:14 0.00 0.00 0.00
March 0.103067E+11 0.00 665.45 0.607465E+10 0.00 0.00 0.00 0.00 17942.25 19-MAR-08:62 13284.47 15-MAR-15:11 0.00 0.00 0.00
April 0.106743E+11 0.00 663.70 0.616608E+10 0.00 0.00 0.00 0.00 16120.65 29-APR-18:02 12307.88 22-APR-15:12 0.00 0.00 0.00
May 0.118073E+11 0.00 698.36 0.678099E+10 0.00 0.00 0.00 0.00 16810.56 24-MAY-18:02 12321.19 02-MAY-18:02 0.00 0.00 0.00
June 0.124294E+11 0.00 679.66 0.739905E+10 0.00 0.00 0.00 0.00 15430.64 13-JUN-08:61 12306.77 25-JUN-15:12 0.00 0.00 0.00
July 0.135954E+11 0.00 707.80 0.832999E+10 0.00 0.00 0.00 0.00 15356.31 02-JUL-18:02 12325.80 28-JUL-18:02 0.00 0.00 0.00
August 0.133839E+11 0.00 701.30 0.821064E+10 0.00 0.00 0.00 0.00 17760.92 12-AUG-08:62 12318.89 08-AUG-15:12 0.00 0.00 0.00
September 0.143046E+11 0.00 686.57 0.919770E+10 0.00 0.00 0.00 0.00 15913.65 05-SEP-08:62 12313.61 08-SEP-15:12 0.00 0.00 0.00
October 0.149039E+11 0.00 711.65 0.973863E+10 0.00 0.00 0.00 0.00 16991.46 31-OCT-08:62 12357.49 06-OCT-15:12 0.00 0.00 0.00
November 0.126844E+11 0.00 674.80 0.802611E+10 0.00 0.00 0.00 0.00 17293.54 24-NOV-09:02 12309.05 19-NOV-16:12 0.00 0.00 0.00
December 0.110551E+11 0.00 672.08 0.678573E+10 0.00 0.00 0.00 0.00 17805.23 23-DEC-09:02 12306.57 19-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.145188E+12 0.00 8136.69 0.890651E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.971900E+10 0.00 606.40 0.590021E+10 0.00 0.00 0.00 0.00 15356.31   12306.57   0.00 0.00 0.00
Maximum of Months 0.149039E+11 0.00 711.65 0.973863E+10 0.00 0.00 0.00 0.00 17942.25   13284.47   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 387.94 252.26 135.68 726.99 119.53 0.00 0.00 0.00
February 333.49 185.80 147.68 665.58 99.00 0.00 0.00 0.00
March 251.02 95.78 155.23 525.37 80.06 0.00 0.00 0.00
April 180.11 29.23 150.89 405.87 51.48 0.00 0.00 0.00
May 145.99 2.53 143.46 334.49 19.59 0.00 0.00 0.00
June 139.54 0.08 139.46 331.82 6.62 0.00 0.00 0.00
July 148.80 0.52 148.28 364.13 11.71 0.00 0.00 0.00
August 163.87 8.33 155.54 402.02 5.43 0.00 0.00 0.00
September 209.01 44.87 164.15 513.58 16.00 0.00 0.00 0.00
October 292.58 133.89 158.69 648.21 26.50 0.00 0.00 0.00
November 340.57 190.18 150.39 680.55 57.47 0.00 0.00 0.00
December 376.61 238.76 137.85 710.28 103.73 0.00 0.00 0.00
                 
Annual Sum or Average 247.08 98.16 148.93 525.06 49.54 0.00 0.00 0.00
Minimum of Months 139.54 0.08 135.68 331.82 5.43 0.00 0.00 0.00
Maximum of Months 387.94 252.26 164.15 726.99 119.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1092.40 710.34 382.06 2073.84 290.03 0.00 0.00 0.00
February 939.07 523.21 415.87 1908.99 228.67 0.00 0.00 0.00
March 706.84 269.72 437.12 1526.03 171.95 0.00 0.00 0.00
April 507.19 82.30 424.89 1204.36 88.25 0.00 0.00 0.00
May 411.09 7.13 403.96 1032.72 20.26 0.00 0.00 0.00
June 392.95 0.23 392.72 1039.48 3.63 0.00 0.00 0.00
July 419.01 1.45 417.56 1120.41 10.67 0.00 0.00 0.00
August 461.45 23.46 437.99 1232.17 2.62 0.00 0.00 0.00
September 588.57 126.35 462.22 1521.11 21.15 0.00 0.00 0.00
October 823.88 377.02 446.87 1882.03 40.10 0.00 0.00 0.00
November 959.03 535.55 423.48 1961.25 121.71 0.00 0.00 0.00
December 1060.50 672.32 388.18 2027.01 242.63 0.00 0.00 0.00
                 
Annual Sum or Average 695.77 276.40 419.37 1542.35 102.93 0.00 0.00 0.00
Minimum of Months 392.95 0.23 382.06 1032.72 2.62 0.00 0.00 0.00
Maximum of Months 1092.40 710.34 462.22 2073.84 290.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1419.09 922.77 496.32 2710.30 413.68 0.00 0.00 0.00
February 1219.91 679.67 540.24 2490.55 331.73 0.00 0.00 0.00
March 918.23 350.38 567.85 1981.71 257.92 0.00 0.00 0.00
April 658.87 106.92 551.95 1550.74 150.04 0.00 0.00 0.00
May 534.03 9.26 524.77 1300.57 46.74 0.00 0.00 0.00
June 510.46 0.30 510.16 1300.22 14.16 0.00 0.00 0.00
July 544.32 1.89 542.43 1415.46 26.75 0.00 0.00 0.00
August 599.44 30.47 568.97 1559.82 10.62 0.00 0.00 0.00
September 764.59 164.13 600.45 1965.42 43.28 0.00 0.00 0.00
October 1070.27 489.77 580.51 2447.07 69.75 0.00 0.00 0.00
November 1245.84 695.71 550.13 2553.10 183.18 0.00 0.00 0.00
December 1377.65 873.39 504.27 2645.80 352.33 0.00 0.00 0.00
                 
Annual Sum or Average 903.85 359.06 544.78 1990.97 157.59 0.00 0.00 0.00
Minimum of Months 510.46 0.30 496.32 1300.22 10.62 0.00 0.00 0.00
Maximum of Months 1419.09 922.77 600.45 2710.30 413.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 76.70 49.88 26.83 146.77 18.74 0.00 0.00 0.00
February 65.94 36.74 29.20 134.96 14.26 0.00 0.00 0.00
March 49.63 18.94 30.69 107.18 10.23 0.00 0.00 0.00
April 35.61 5.78 29.83 84.91 4.43 0.00 0.00 0.00
May 28.86 0.50 28.36 75.25 0.70 0.00 0.00 0.00
June 27.59 0.02 27.57 77.03 0.05 0.00 0.00 0.00
July 29.42 0.10 29.32 82.64 0.25 0.00 0.00 0.00
August 32.40 1.65 30.75 90.84 0.01 0.00 0.00 0.00
September 41.33 8.87 32.45 111.41 0.37 0.00 0.00 0.00
October 57.85 26.47 31.38 136.30 1.06 0.00 0.00 0.00
November 67.34 37.60 29.73 140.67 6.69 0.00 0.00 0.00
December 74.46 47.21 27.26 143.44 15.15 0.00 0.00 0.00
                 
Annual Sum or Average 48.85 19.41 29.45 110.83 5.96 0.00 0.00 0.00
Minimum of Months 27.59 0.02 26.83 75.25 0.01 0.00 0.00 0.00
Maximum of Months 76.70 49.88 32.45 146.77 18.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.66 28.21 37.45 121.62 36.74 0.00 0.00 0.00
February 82.90 37.80 45.10 162.06 27.98 0.00 0.00 0.00
March 103.12 47.43 55.69 200.50 19.81 0.00 0.00 0.00
April 113.55 53.02 60.53 234.59 8.23 0.00 0.00 0.00
May 103.35 40.13 63.22 235.79 1.32 0.00 0.00 0.00
June 87.21 24.49 62.72 216.70 0.10 0.00 0.00 0.00
July 97.25 30.03 67.22 240.28 0.48 0.00 0.00 0.00
August 97.21 31.70 65.51 236.37 0.03 0.00 0.00 0.00
September 82.88 24.47 58.42 205.30 0.73 0.00 0.00 0.00
October 82.60 32.29 50.30 190.18 2.02 0.00 0.00 0.00
November 67.59 24.56 43.03 145.82 13.06 0.00 0.00 0.00
December 67.63 29.98 37.65 130.57 29.04 0.00 0.00 0.00
                 
Annual Sum or Average 87.61 33.66 53.95 193.49 11.56 0.00 0.00 0.00
Minimum of Months 65.66 24.47 37.45 121.62 0.03 0.00 0.00 0.00
Maximum of Months 113.55 53.02 67.22 240.28 36.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.29 0.00 16.29 26.77 20.34 0.00 0.00 0.00
February 19.28 0.00 19.28 36.13 15.89 0.00 0.00 0.00
March 23.00 0.00 23.00 42.68 11.79 0.00 0.00 0.00
April 25.77 0.08 25.69 55.42 5.36 0.00 0.00 0.00
May 28.96 0.82 28.14 74.49 0.75 0.00 0.00 0.00
June 30.86 1.67 29.19 86.08 0.07 0.00 0.00 0.00
July 31.40 1.13 30.27 87.87 0.33 0.00 0.00 0.00
August 28.10 0.18 27.92 78.40 0.03 0.00 0.00 0.00
September 24.98 0.00 24.98 70.47 0.51 0.00 0.00 0.00
October 20.92 0.00 20.92 54.85 1.11 0.00 0.00 0.00
November 18.19 0.00 18.19 41.23 7.31 0.00 0.00 0.00
December 16.11 0.00 16.11 28.84 16.16 0.00 0.00 0.00
                 
Annual Sum or Average 23.68 0.32 23.35 57.04 6.60 0.00 0.00 0.00
Minimum of Months 16.11 0.00 16.11 26.77 0.03 0.00 0.00 0.00
Maximum of Months 31.40 1.67 30.27 87.87 20.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.66 28.21 37.45 122.62 37.49 0.00 0.00 0.00
February 82.90 37.80 45.10 162.21 29.51 0.00 0.00 0.00
March 103.12 47.43 55.69 199.81 21.75 0.00 0.00 0.00
April 113.55 53.02 60.53 233.21 10.04 0.00 0.00 0.00
May 103.35 40.13 63.22 234.95 1.43 0.00 0.00 0.00
June 87.21 24.49 62.72 216.13 0.13 0.00 0.00 0.00
July 97.25 30.03 67.22 239.72 0.61 0.00 0.00 0.00
August 97.21 31.70 65.51 236.36 0.05 0.00 0.00 0.00
September 82.88 24.47 58.42 205.79 0.94 0.00 0.00 0.00
October 82.60 32.29 50.30 191.12 2.05 0.00 0.00 0.00
November 67.59 24.56 43.03 146.62 13.62 0.00 0.00 0.00
December 67.63 29.98 37.65 131.40 29.75 0.00 0.00 0.00
                 
Annual Sum or Average 87.61 33.66 53.95 193.51 12.21 0.00 0.00 0.00
Minimum of Months 65.66 24.47 37.45 122.62 0.05 0.00 0.00 0.00
Maximum of Months 113.55 53.02 67.22 239.72 37.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 61.35 39.89 21.46 108.56 28.24 0.00 0.00 0.00
February 52.74 29.38 23.36 98.58 23.82 0.00 0.00 0.00
March 39.70 15.15 24.55 76.36 19.94 0.00 0.00 0.00
April 28.48 4.62 23.86 58.43 13.91 0.00 0.00 0.00
May 23.09 0.40 22.69 47.38 7.49 0.00 0.00 0.00
June 22.07 0.01 22.06 46.02 3.94 0.00 0.00 0.00
July 23.53 0.08 23.45 52.11 5.21 0.00 0.00 0.00
August 25.91 1.32 24.60 57.24 4.25 0.00 0.00 0.00
September 33.05 7.10 25.96 75.02 5.86 0.00 0.00 0.00
October 46.27 21.17 25.10 97.26 9.29 0.00 0.00 0.00
November 53.86 30.08 23.78 101.84 15.71 0.00 0.00 0.00
December 59.56 37.76 21.80 106.27 25.45 0.00 0.00 0.00
                 
Annual Sum or Average 39.07 15.52 23.55 76.99 13.55 0.00 0.00 0.00
Minimum of Months 22.07 0.01 21.46 46.02 3.94 0.00 0.00 0.00
Maximum of Months 61.35 39.89 25.96 108.56 28.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.03 0.00 13.03 22.21 15.38 0.00 0.00 0.00
February 15.43 0.00 15.43 30.05 11.67 0.00 0.00 0.00
March 18.40 0.00 18.40 35.87 8.17 0.00 0.00 0.00
April 20.62 0.07 20.56 46.67 3.15 0.00 0.00 0.00
May 23.17 0.66 22.52 62.75 0.43 0.00 0.00 0.00
June 24.69 1.34 23.35 72.12 0.01 0.00 0.00 0.00
July 25.12 0.90 24.22 73.72 0.14 0.00 0.00 0.00
August 22.48 0.15 22.34 66.20 0.00 0.00 0.00 0.00
September 19.99 0.00 19.98 59.56 0.18 0.00 0.00 0.00
October 16.74 0.00 16.74 46.84 0.53 0.00 0.00 0.00
November 14.55 0.00 14.55 34.92 5.22 0.00 0.00 0.00
December 12.89 0.00 12.89 24.03 12.07 0.00 0.00 0.00
                 
Annual Sum or Average 18.94 0.26 18.68 48.00 4.72 0.00 0.00 0.00
Minimum of Months 12.89 0.00 12.89 22.21 0.00 0.00 0.00 0.00
Maximum of Months 25.12 1.34 24.22 73.72 15.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 72.81 34.68 38.14 134.79 35.41 0.00 0.00 0.00
February 85.03 39.54 45.48 164.63 26.31 0.00 0.00 0.00
March 104.38 49.83 54.55 199.76 18.09 0.00 0.00 0.00
April 113.08 50.84 62.24 234.61 7.73 0.00 0.00 0.00
May 106.92 43.07 63.85 242.93 1.23 0.00 0.00 0.00
June 104.97 40.55 64.42 251.49 0.11 0.00 0.00 0.00
July 107.79 39.04 68.75 261.29 0.46 0.00 0.00 0.00
August 98.68 33.28 65.40 239.33 0.02 0.00 0.00 0.00
September 95.08 34.56 60.52 229.49 0.70 0.00 0.00 0.00
October 87.40 37.69 49.71 199.70 1.93 0.00 0.00 0.00
November 70.72 28.05 42.67 151.16 12.36 0.00 0.00 0.00
December 56.75 19.72 37.03 108.75 28.28 0.00 0.00 0.00
                 
Annual Sum or Average 91.98 37.54 54.44 201.63 10.99 0.00 0.00 0.00
Minimum of Months 56.75 19.72 37.03 108.75 0.02 0.00 0.00 0.00
Maximum of Months 113.08 50.84 68.75 261.29 35.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 76.70 49.88 26.83 146.34 18.67 0.00 0.00 0.00
February 65.94 36.74 29.20 134.59 14.11 0.00 0.00 0.00
March 49.63 18.94 30.69 106.75 10.02 0.00 0.00 0.00
April 35.61 5.78 29.83 84.61 4.24 0.00 0.00 0.00
May 28.86 0.50 28.36 75.10 0.68 0.00 0.00 0.00
June 27.59 0.02 27.57 76.59 0.06 0.00 0.00 0.00
July 29.42 0.10 29.32 82.36 0.25 0.00 0.00 0.00
August 32.40 1.65 30.75 90.76 0.01 0.00 0.00 0.00
September 41.33 8.87 32.45 111.10 0.38 0.00 0.00 0.00
October 57.85 26.47 31.38 136.13 1.03 0.00 0.00 0.00
November 67.34 37.60 29.73 140.46 6.62 0.00 0.00 0.00
December 74.46 47.21 27.26 143.42 14.92 0.00 0.00 0.00
                 
Annual Sum or Average 48.85 19.41 29.45 110.57 5.88 0.00 0.00 0.00
Minimum of Months 27.59 0.02 26.83 75.10 0.01 0.00 0.00 0.00
Maximum of Months 76.70 49.88 32.45 146.34 18.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.29 0.00 16.29 26.14 20.21 0.00 0.00 0.00
February 19.28 0.00 19.28 35.54 15.67 0.00 0.00 0.00
March 23.00 0.00 23.00 42.14 11.45 0.00 0.00 0.00
April 25.77 0.08 25.69 54.96 5.11 0.00 0.00 0.00
May 28.96 0.82 28.14 74.29 0.73 0.00 0.00 0.00
June 30.86 1.67 29.19 85.61 0.08 0.00 0.00 0.00
July 31.40 1.13 30.27 87.57 0.34 0.00 0.00 0.00
August 28.10 0.18 27.92 78.31 0.02 0.00 0.00 0.00
September 24.98 0.00 24.98 70.11 0.53 0.00 0.00 0.00
October 20.92 0.00 20.92 54.58 1.09 0.00 0.00 0.00
November 18.19 0.00 18.19 40.82 7.21 0.00 0.00 0.00
December 16.11 0.00 16.11 28.70 15.71 0.00 0.00 0.00
                 
Annual Sum or Average 23.68 0.32 23.35 56.67 6.47 0.00 0.00 0.00
Minimum of Months 16.11 0.00 16.11 26.14 0.02 0.00 0.00 0.00
Maximum of Months 31.40 1.67 30.27 87.57 20.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 72.81 34.68 38.14 135.49 36.08 0.00 0.00 0.00
February 85.03 39.54 45.48 164.34 27.69 0.00 0.00 0.00
March 104.38 49.83 54.55 198.84 19.74 0.00 0.00 0.00
April 113.08 50.84 62.24 232.87 9.41 0.00 0.00 0.00
May 106.92 43.07 63.85 241.95 1.33 0.00 0.00 0.00
June 104.97 40.55 64.42 250.90 0.14 0.00 0.00 0.00
July 107.79 39.04 68.75 260.72 0.61 0.00 0.00 0.00
August 98.68 33.28 65.40 239.33 0.04 0.00 0.00 0.00
September 95.08 34.56 60.52 229.89 0.91 0.00 0.00 0.00
October 87.40 37.69 49.71 200.44 1.96 0.00 0.00 0.00
November 70.72 28.05 42.67 151.53 12.86 0.00 0.00 0.00
December 56.75 19.72 37.03 109.50 28.62 0.00 0.00 0.00
                 
Annual Sum or Average 91.98 37.54 54.44 201.46 11.55 0.00 0.00 0.00
Minimum of Months 56.75 19.72 37.03 109.50 0.04 0.00 0.00 0.00
Maximum of Months 113.08 50.84 68.75 260.72 36.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.63 0.00 20.63 32.91 28.77 0.00 0.00 0.00
February 24.42 0.00 24.42 45.39 22.02 0.00 0.00 0.00
March 29.13 0.00 29.13 54.20 16.66 0.00 0.00 0.00
April 32.64 0.10 32.54 69.60 8.94 0.00 0.00 0.00
May 36.68 1.04 35.64 90.13 2.17 0.00 0.00 0.00
June 39.08 2.11 36.97 102.11 0.69 0.00 0.00 0.00
July 39.77 1.43 38.34 104.66 1.50 0.00 0.00 0.00
August 35.59 0.23 35.36 92.17 0.56 0.00 0.00 0.00
September 31.64 0.00 31.63 82.89 2.64 0.00 0.00 0.00
October 26.49 0.00 26.49 63.83 4.20 0.00 0.00 0.00
November 23.04 0.00 23.04 48.70 12.19 0.00 0.00 0.00
December 20.40 0.00 20.40 35.30 23.51 0.00 0.00 0.00
                 
Annual Sum or Average 29.99 0.41 29.57 68.60 10.27 0.00 0.00 0.00
Minimum of Months 20.40 0.00 20.40 32.91 0.56 0.00 0.00 0.00
Maximum of Months 39.77 2.11 38.34 104.66 28.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.60 0.00 7.60 12.13 10.61 0.00 0.00 0.00
February 9.00 0.00 9.00 16.73 8.12 0.00 0.00 0.00
March 10.74 0.00 10.74 19.98 6.14 0.00 0.00 0.00
April 12.03 0.04 11.99 25.66 3.30 0.00 0.00 0.00
May 13.52 0.38 13.14 33.23 0.80 0.00 0.00 0.00
June 14.41 0.78 13.63 37.64 0.25 0.00 0.00 0.00
July 14.66 0.53 14.13 38.58 0.55 0.00 0.00 0.00
August 13.12 0.08 13.03 33.98 0.21 0.00 0.00 0.00
September 11.66 0.00 11.66 30.56 0.97 0.00 0.00 0.00
October 9.77 0.00 9.77 23.53 1.55 0.00 0.00 0.00
November 8.49 0.00 8.49 17.95 4.49 0.00 0.00 0.00
December 7.52 0.00 7.52 13.01 8.67 0.00 0.00 0.00
                 
Annual Sum or Average 11.05 0.15 10.90 25.29 3.79 0.00 0.00 0.00
Minimum of Months 7.52 0.00 7.52 12.13 0.21 0.00 0.00 0.00
Maximum of Months 14.66 0.78 14.13 38.58 10.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.79 23.27 12.52 68.33 9.95 0.00 0.00 0.00
February 30.77 17.14 13.62 62.80 7.68 0.00 0.00 0.00
March 23.16 8.84 14.32 49.84 5.89 0.00 0.00 0.00
April 16.62 2.70 13.92 39.05 3.33 0.00 0.00 0.00
May 13.47 0.23 13.23 33.34 0.81 0.00 0.00 0.00
June 12.87 0.01 12.87 33.26 0.25 0.00 0.00 0.00
July 13.73 0.05 13.68 35.98 0.55 0.00 0.00 0.00
August 15.12 0.77 14.35 39.74 0.20 0.00 0.00 0.00
September 19.28 4.14 15.14 49.72 0.95 0.00 0.00 0.00
October 26.99 12.35 14.64 61.69 1.52 0.00 0.00 0.00
November 31.42 17.55 13.87 64.48 4.28 0.00 0.00 0.00
December 34.74 22.03 12.72 66.70 8.33 0.00 0.00 0.00
                 
Annual Sum or Average 22.79 9.06 13.74 50.35 3.63 0.00 0.00 0.00
Minimum of Months 12.87 0.01 12.52 33.26 0.20 0.00 0.00 0.00
Maximum of Months 35.79 23.27 15.14 68.33 9.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 97.14 63.16 33.97 185.46 27.01 0.00 0.00 0.00
February 83.50 46.52 36.98 170.44 20.85 0.00 0.00 0.00
March 62.85 23.98 38.87 135.29 15.99 0.00 0.00 0.00
April 45.10 7.32 37.78 106.00 9.04 0.00 0.00 0.00
May 36.56 0.63 35.92 90.49 2.19 0.00 0.00 0.00
June 34.94 0.02 34.92 90.28 0.68 0.00 0.00 0.00
July 37.26 0.13 37.13 97.67 1.49 0.00 0.00 0.00
August 41.03 2.09 38.95 107.87 0.55 0.00 0.00 0.00
September 52.34 11.23 41.10 134.94 2.59 0.00 0.00 0.00
October 73.26 33.52 39.74 167.45 4.13 0.00 0.00 0.00
November 85.28 47.62 37.66 175.00 11.60 0.00 0.00 0.00
December 94.30 59.78 34.52 181.04 22.62 0.00 0.00 0.00
                 
Annual Sum or Average 61.87 24.58 37.29 136.66 9.85 0.00 0.00 0.00
Minimum of Months 34.94 0.02 33.97 90.28 0.55 0.00 0.00 0.00
Maximum of Months 97.14 63.16 41.10 185.46 27.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 76.70 49.88 26.83 146.02 17.89 0.00 0.00 0.00
February 65.94 36.74 29.20 134.13 13.56 0.00 0.00 0.00
March 49.63 18.94 30.69 106.41 9.55 0.00 0.00 0.00
April 35.61 5.78 29.83 84.24 3.86 0.00 0.00 0.00
May 28.86 0.50 28.36 75.10 0.57 0.00 0.00 0.00
June 27.59 0.02 27.57 76.98 0.02 0.00 0.00 0.00
July 29.42 0.10 29.32 82.48 0.17 0.00 0.00 0.00
August 32.40 1.65 30.75 90.75 0.00 0.00 0.00 0.00
September 41.33 8.87 32.45 111.09 0.21 0.00 0.00 0.00
October 57.85 26.47 31.38 135.97 0.78 0.00 0.00 0.00
November 67.34 37.60 29.73 140.10 6.10 0.00 0.00 0.00
December 74.46 47.21 27.26 142.67 14.38 0.00 0.00 0.00
                 
Annual Sum or Average 48.85 19.41 29.45 110.38 5.56 0.00 0.00 0.00
Minimum of Months 27.59 0.02 26.83 75.10 0.00 0.00 0.00 0.00
Maximum of Months 76.70 49.88 32.45 146.02 17.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.66 28.21 37.45 120.74 34.92 0.00 0.00 0.00
February 82.90 37.80 45.10 160.95 26.53 0.00 0.00 0.00
March 103.12 47.43 55.69 199.11 18.47 0.00 0.00 0.00
April 113.55 53.02 60.53 233.09 7.18 0.00 0.00 0.00
May 103.35 40.13 63.22 234.94 1.07 0.00 0.00 0.00
June 87.21 24.49 62.72 216.15 0.05 0.00 0.00 0.00
July 97.25 30.03 67.22 239.58 0.32 0.00 0.00 0.00
August 97.21 31.70 65.51 235.84 0.01 0.00 0.00 0.00
September 82.88 24.47 58.42 204.76 0.40 0.00 0.00 0.00
October 82.60 32.29 50.30 189.91 1.45 0.00 0.00 0.00
November 67.59 24.56 43.03 145.25 11.84 0.00 0.00 0.00
December 67.63 29.98 37.65 129.67 27.50 0.00 0.00 0.00
                 
Annual Sum or Average 87.61 33.66 53.95 192.68 10.75 0.00 0.00 0.00
Minimum of Months 65.66 24.47 37.45 120.74 0.01 0.00 0.00 0.00
Maximum of Months 113.55 53.02 67.22 239.58 34.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.29 0.00 16.29 26.80 19.64 0.00 0.00 0.00
February 19.28 0.00 19.28 35.98 15.47 0.00 0.00 0.00
March 23.00 0.00 23.00 42.33 11.46 0.00 0.00 0.00
April 25.77 0.08 25.69 54.97 5.02 0.00 0.00 0.00
May 28.96 0.82 28.14 74.27 0.63 0.00 0.00 0.00
June 30.86 1.67 29.19 85.90 0.05 0.00 0.00 0.00
July 31.40 1.13 30.27 87.65 0.28 0.00 0.00 0.00
August 28.10 0.18 27.92 78.35 0.02 0.00 0.00 0.00
September 24.98 0.00 24.98 70.44 0.35 0.00 0.00 0.00
October 20.92 0.00 20.92 55.03 0.80 0.00 0.00 0.00
November 18.19 0.00 18.19 41.32 6.73 0.00 0.00 0.00
December 16.11 0.00 16.11 28.85 15.51 0.00 0.00 0.00
                 
Annual Sum or Average 23.68 0.32 23.35 56.92 6.29 0.00 0.00 0.00
Minimum of Months 16.11 0.00 16.11 26.80 0.02 0.00 0.00 0.00
Maximum of Months 31.40 1.67 30.27 87.65 19.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.66 28.21 37.45 122.22 36.11 0.00 0.00 0.00
February 82.90 37.80 45.10 161.38 28.72 0.00 0.00 0.00
March 103.12 47.43 55.69 198.44 21.10 0.00 0.00 0.00
April 113.55 53.02 60.53 231.73 9.38 0.00 0.00 0.00
May 103.35 40.13 63.22 234.09 1.19 0.00 0.00 0.00
June 87.21 24.49 62.72 215.55 0.09 0.00 0.00 0.00
July 97.25 30.03 67.22 238.99 0.51 0.00 0.00 0.00
August 97.21 31.70 65.51 235.83 0.03 0.00 0.00 0.00
September 82.88 24.47 58.42 205.31 0.64 0.00 0.00 0.00
October 82.60 32.29 50.30 190.98 1.47 0.00 0.00 0.00
November 67.59 24.56 43.03 146.36 12.54 0.00 0.00 0.00
December 67.63 29.98 37.65 130.97 28.51 0.00 0.00 0.00
                 
Annual Sum or Average 87.61 33.66 53.95 192.83 11.62 0.00 0.00 0.00
Minimum of Months 65.66 24.47 37.45 122.22 0.03 0.00 0.00 0.00
Maximum of Months 113.55 53.02 67.22 238.99 36.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 112.49 73.15 39.34 212.82 26.72 0.00 0.00 0.00
February 96.70 53.88 42.82 196.17 19.81 0.00 0.00 0.00
March 72.79 27.77 45.01 156.61 13.43 0.00 0.00 0.00
April 52.23 8.48 43.75 125.57 4.83 0.00 0.00 0.00
May 42.33 0.73 41.60 113.27 0.71 0.00 0.00 0.00
June 40.46 0.02 40.44 115.93 0.02 0.00 0.00 0.00
July 43.15 0.15 43.00 124.26 0.17 0.00 0.00 0.00
August 47.52 2.42 45.10 136.03 0.00 0.00 0.00 0.00
September 60.61 13.01 47.60 164.86 0.21 0.00 0.00 0.00
October 84.84 38.82 46.02 200.33 1.01 0.00 0.00 0.00
November 98.76 55.15 43.61 205.22 8.93 0.00 0.00 0.00
December 109.21 69.23 39.97 208.27 21.50 0.00 0.00 0.00
                 
Annual Sum or Average 71.65 28.46 43.18 163.12 8.07 0.00 0.00 0.00
Minimum of Months 40.46 0.02 39.34 113.27 0.00 0.00 0.00 0.00
Maximum of Months 112.49 73.15 47.60 212.82 26.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 114.02 0.00 114.02 203.06 131.31 0.00 0.00 0.00
February 134.96 0.00 134.96 272.22 101.17 0.00 0.00 0.00
March 160.99 0.00 160.99 323.17 75.21 0.00 0.00 0.00
April 180.41 0.57 179.84 414.58 34.31 0.00 0.00 0.00
May 202.71 5.74 196.98 535.66 7.22 0.00 0.00 0.00
June 216.00 11.68 204.31 609.83 1.17 0.00 0.00 0.00
July 219.80 7.90 211.90 626.45 3.34 0.00 0.00 0.00
August 196.69 1.27 195.42 559.06 0.89 0.00 0.00 0.00
September 174.85 0.02 174.84 507.34 5.52 0.00 0.00 0.00
October 146.43 0.00 146.43 403.40 10.53 0.00 0.00 0.00
November 127.32 0.00 127.32 307.38 49.47 0.00 0.00 0.00
December 112.78 0.00 112.78 218.12 104.91 0.00 0.00 0.00
                 
Annual Sum or Average 165.73 2.27 163.46 415.71 43.51 0.00 0.00 0.00
Minimum of Months 112.78 0.00 112.78 203.06 0.89 0.00 0.00 0.00
Maximum of Months 219.80 11.68 211.90 626.45 131.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 114.02 0.00 114.02 196.57 139.87 0.00 0.00 0.00
February 134.96 0.00 134.96 264.73 108.87 0.00 0.00 0.00
March 160.99 0.00 160.99 314.82 81.90 0.00 0.00 0.00
April 180.41 0.57 179.84 405.26 39.28 0.00 0.00 0.00
May 202.71 5.74 196.98 523.09 9.06 0.00 0.00 0.00
June 216.00 11.68 204.31 596.52 1.78 0.00 0.00 0.00
July 219.80 7.90 211.90 613.57 4.37 0.00 0.00 0.00
August 196.69 1.27 195.42 545.61 1.45 0.00 0.00 0.00
September 174.85 0.02 174.84 495.56 7.53 0.00 0.00 0.00
October 146.43 0.00 146.43 392.01 12.96 0.00 0.00 0.00
November 127.32 0.00 127.32 297.85 54.07 0.00 0.00 0.00
December 112.78 0.00 112.78 210.94 112.96 0.00 0.00 0.00
                 
Annual Sum or Average 165.73 2.27 163.46 405.38 47.58 0.00 0.00 0.00
Minimum of Months 112.78 0.00 112.78 196.57 1.45 0.00 0.00 0.00
Maximum of Months 219.80 11.68 211.90 613.57 139.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.29 0.00 16.29 66.05 12.13 0.00 0.00 0.00
February 19.28 0.00 19.28 78.44 10.50 0.00 0.00 0.00
March 23.00 0.00 23.00 87.55 8.02 0.00 0.00 0.00
April 25.77 0.08 25.69 104.21 4.16 0.00 0.00 0.00
May 28.96 0.82 28.14 123.83 1.18 0.00 0.00 0.00
June 30.86 1.67 29.19 135.34 0.24 0.00 0.00 0.00
July 31.40 1.13 30.27 138.19 0.55 0.00 0.00 0.00
August 28.10 0.18 27.92 127.54 0.23 0.00 0.00 0.00
September 24.98 0.00 24.98 120.05 0.87 0.00 0.00 0.00
October 20.92 0.00 20.92 103.83 1.47 0.00 0.00 0.00
November 18.19 0.00 18.19 87.47 5.39 0.00 0.00 0.00
December 16.11 0.00 16.11 70.48 10.04 0.00 0.00 0.00
                 
Annual Sum or Average 23.68 0.32 23.35 103.70 4.54 0.00 0.00 0.00
Minimum of Months 16.11 0.00 16.11 66.05 0.23 0.00 0.00 0.00
Maximum of Months 31.40 1.67 30.27 138.19 12.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 145.62 69.35 76.27 424.48 45.57 0.00 0.00 0.00
February 170.04 79.08 90.96 492.10 39.15 0.00 0.00 0.00
March 208.74 99.65 109.10 570.23 29.84 0.00 0.00 0.00
April 226.14 101.66 124.47 649.45 15.62 0.00 0.00 0.00
May 213.82 86.14 127.68 667.10 4.42 0.00 0.00 0.00
June 209.93 81.09 128.84 686.51 0.89 0.00 0.00 0.00
July 215.56 78.07 137.49 709.80 2.03 0.00 0.00 0.00
August 197.34 66.55 130.79 661.46 0.88 0.00 0.00 0.00
September 190.14 69.11 121.03 645.97 3.24 0.00 0.00 0.00
October 174.79 75.38 99.41 584.78 5.52 0.00 0.00 0.00
November 141.42 56.09 85.34 478.77 20.16 0.00 0.00 0.00
December 113.49 39.43 74.06 376.76 37.67 0.00 0.00 0.00
                 
Annual Sum or Average 183.95 75.08 108.87 579.27 16.98 0.00 0.00 0.00
Minimum of Months 113.49 39.43 74.06 376.76 0.88 0.00 0.00 0.00
Maximum of Months 226.14 101.66 137.49 709.80 45.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 76.70 49.88 26.83 188.76 12.06 0.00 0.00 0.00
February 65.94 36.74 29.20 178.99 10.35 0.00 0.00 0.00
March 49.63 18.94 30.69 152.67 7.93 0.00 0.00 0.00
April 35.61 5.78 29.83 133.20 4.14 0.00 0.00 0.00
May 28.86 0.50 28.36 123.77 1.17 0.00 0.00 0.00
June 27.59 0.02 27.57 125.86 0.23 0.00 0.00 0.00
July 29.42 0.10 29.32 132.49 0.54 0.00 0.00 0.00
August 32.40 1.65 30.75 139.88 0.23 0.00 0.00 0.00
September 41.33 8.87 32.45 161.51 0.86 0.00 0.00 0.00
October 57.85 26.47 31.38 186.30 1.46 0.00 0.00 0.00
November 67.34 37.60 29.73 188.47 5.34 0.00 0.00 0.00
December 74.46 47.21 27.26 187.12 9.96 0.00 0.00 0.00
                 
Annual Sum or Average 48.85 19.41 29.45 158.15 4.50 0.00 0.00 0.00
Minimum of Months 27.59 0.02 26.83 123.77 0.23 0.00 0.00 0.00
Maximum of Months 76.70 49.88 32.45 188.76 12.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.63 0.00 20.63 29.66 32.85 0.00 0.00 0.00
February 24.42 0.00 24.42 41.26 26.27 0.00 0.00 0.00
March 29.13 0.00 29.13 49.65 20.44 0.00 0.00 0.00
April 32.64 0.10 32.54 64.80 12.00 0.00 0.00 0.00
May 36.68 1.04 35.64 84.39 3.84 0.00 0.00 0.00
June 39.08 2.11 36.97 96.83 1.26 0.00 0.00 0.00
July 39.77 1.43 38.34 100.33 2.15 0.00 0.00 0.00
August 35.59 0.23 35.36 87.16 1.21 0.00 0.00 0.00
September 31.64 0.00 31.63 78.79 3.48 0.00 0.00 0.00
October 26.49 0.00 26.49 60.09 5.44 0.00 0.00 0.00
November 23.04 0.00 23.04 44.51 14.33 0.00 0.00 0.00
December 20.40 0.00 20.40 32.07 27.26 0.00 0.00 0.00
                 
Annual Sum or Average 29.99 0.41 29.57 64.24 12.48 0.00 0.00 0.00
Minimum of Months 20.40 0.00 20.40 29.66 1.21 0.00 0.00 0.00
Maximum of Months 39.77 2.11 38.34 100.33 32.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.46 0.00 18.46 26.53 29.39 0.00 0.00 0.00
February 21.85 0.00 21.85 36.91 23.50 0.00 0.00 0.00
March 26.06 0.00 26.06 44.42 18.28 0.00 0.00 0.00
April 29.20 0.09 29.11 57.97 10.73 0.00 0.00 0.00
May 32.81 0.93 31.89 75.50 3.44 0.00 0.00 0.00
June 34.96 1.89 33.07 86.64 1.13 0.00 0.00 0.00
July 35.58 1.28 34.30 89.76 1.92 0.00 0.00 0.00
August 31.84 0.21 31.63 77.98 1.08 0.00 0.00 0.00
September 28.30 0.00 28.30 70.50 3.12 0.00 0.00 0.00
October 23.70 0.00 23.70 53.77 4.87 0.00 0.00 0.00
November 20.61 0.00 20.61 39.82 12.82 0.00 0.00 0.00
December 18.26 0.00 18.26 28.69 24.39 0.00 0.00 0.00
                 
Annual Sum or Average 26.83 0.37 26.46 57.47 11.17 0.00 0.00 0.00
Minimum of Months 18.26 0.00 18.26 26.53 1.08 0.00 0.00 0.00
Maximum of Months 35.58 1.89 34.30 89.76 29.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 286.35 186.20 100.15 534.12 90.76 0.00 0.00 0.00
February 246.16 137.15 109.01 487.79 73.58 0.00 0.00 0.00
March 185.29 70.70 114.58 383.66 58.12 0.00 0.00 0.00
April 132.95 21.57 111.38 297.80 35.86 0.00 0.00 0.00
May 107.76 1.87 105.89 249.78 11.27 0.00 0.00 0.00
June 103.00 0.06 102.94 250.95 3.79 0.00 0.00 0.00
July 109.84 0.38 109.45 275.25 6.35 0.00 0.00 0.00
August 120.96 6.15 114.81 303.04 3.56 0.00 0.00 0.00
September 154.28 33.12 121.16 384.99 10.18 0.00 0.00 0.00
October 215.96 98.83 117.14 481.23 15.93 0.00 0.00 0.00
November 251.39 140.38 111.01 501.68 40.42 0.00 0.00 0.00
December 277.99 176.24 101.75 521.61 77.17 0.00 0.00 0.00
                 
Annual Sum or Average 182.38 72.45 109.93 388.85 35.41 0.00 0.00 0.00
Minimum of Months 103.00 0.06 100.15 249.78 3.56 0.00 0.00 0.00
Maximum of Months 286.35 186.20 121.16 534.12 90.76 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.103905E+10 0.675642E+09 0.363404E+09 0.194716E+10 0.320150E+09
February 0.806768E+09 0.449492E+09 0.357276E+09 0.161017E+10 0.239498E+09
March 0.672322E+09 0.256549E+09 0.415773E+09 0.140714E+10 0.214428E+09
April 0.466855E+09 75757544.16 0.391098E+09 0.105202E+10 0.133436E+09
May 0.391014E+09 6782770.30 0.384232E+09 0.895903E+09 52461088.17
June 0.361700E+09 214107.63 0.361486E+09 0.860066E+09 17148924.33
July 0.398545E+09 1382735.68 0.397163E+09 0.975283E+09 31360129.19
August 0.438907E+09 22310073.19 0.416597E+09 0.107678E+10 14540340.57
September 0.541765E+09 0.116300E+09 0.425465E+09 0.133121E+10 41481653.37
October 0.783645E+09 0.358602E+09 0.425043E+09 0.173617E+10 70967959.39
November 0.882765E+09 0.492959E+09 0.389806E+09 0.176397E+10 0.148960E+09
December 0.100871E+10 0.639488E+09 0.369220E+09 0.190242E+10 0.277823E+09
           
Annual Sum or Average 0.779204E+10 0.309548E+10 0.469656E+10 0.165583E+11 0.156225E+10
Minimum of Months 0.361700E+09 214107.63 0.357276E+09 0.860066E+09 14540340.57
Maximum of Months 0.103905E+10 0.675642E+09 0.425465E+09 0.194716E+10 0.320150E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.292589E+10 0.190256E+10 0.102332E+10 0.555457E+10 0.776809E+09
February 0.227181E+10 0.126574E+10 0.100607E+10 0.461824E+10 0.553206E+09
March 0.189321E+10 0.722424E+09 0.117079E+10 0.408732E+10 0.460553E+09
April 0.131463E+10 0.213328E+09 0.110131E+10 0.312170E+10 0.228738E+09
May 0.110107E+10 19099833.95 0.108197E+10 0.276603E+10 54265793.06
June 0.101852E+10 602912.96 0.101792E+10 0.269434E+10 9399469.37
July 0.112228E+10 3893692.52 0.111838E+10 0.300091E+10 28589734.61
August 0.123593E+10 62823695.11 0.117311E+10 0.330024E+10 7028601.41
September 0.152557E+10 0.327492E+09 0.119808E+10 0.394271E+10 54825871.05
October 0.220669E+10 0.100980E+10 0.119689E+10 0.504082E+10 0.107399E+09
November 0.248581E+10 0.138814E+10 0.109767E+10 0.508357E+10 0.315466E+09
December 0.284045E+10 0.180076E+10 0.103970E+10 0.542916E+10 0.649861E+09
           
Annual Sum or Average 0.219419E+11 0.871666E+10 0.132252E+11 0.486396E+11 0.324614E+10
Minimum of Months 0.101852E+10 602912.96 0.100607E+10 0.269434E+10 7028601.41
Maximum of Months 0.292589E+10 0.190256E+10 0.119808E+10 0.555457E+10 0.776809E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.380089E+10 0.247154E+10 0.132935E+10 0.725928E+10 0.110801E+10
February 0.295121E+10 0.164427E+10 0.130694E+10 0.602514E+10 0.802530E+09
March 0.245939E+10 0.938470E+09 0.152092E+10 0.530782E+10 0.690822E+09
April 0.170778E+10 0.277126E+09 0.143066E+10 0.401952E+10 0.388892E+09
May 0.143035E+10 24811771.28 0.140554E+10 0.348346E+10 0.125198E+09
June 0.132312E+10 783218.25 0.132234E+10 0.337017E+10 36691948.93
July 0.145790E+10 5058128.17 0.145284E+10 0.379118E+10 71653421.19
August 0.160555E+10 81611555.28 0.152394E+10 0.417783E+10 28452787.15
September 0.198181E+10 0.425431E+09 0.155638E+10 0.509436E+10 0.112185E+09
October 0.286662E+10 0.131179E+10 0.155483E+10 0.655422E+10 0.186806E+09
November 0.322921E+10 0.180327E+10 0.142593E+10 0.661763E+10 0.474795E+09
December 0.368991E+10 0.233928E+10 0.135063E+10 0.708650E+10 0.943687E+09
           
Annual Sum or Average 0.285037E+11 0.113234E+11 0.171803E+11 0.627871E+11 0.496972E+10
Minimum of Months 0.132312E+10 783218.25 0.130694E+10 0.337017E+10 28452787.15
Maximum of Months 0.380089E+10 0.247154E+10 0.155638E+10 0.725928E+10 0.110801E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.205438E+09 0.133586E+09 71851706.15 0.393101E+09 50181864.02
February 0.159512E+09 88872289.58 70640206.20 0.326492E+09 34503784.65
March 0.132930E+09 50724056.24 82206261.55 0.287073E+09 27396122.57
April 92306141.22 14978567.61 77327573.62 0.220097E+09 11471897.51
May 77311145.63 1341070.18 75970075.44 0.201540E+09 1887934.52
June 71515153.18 42332.76 71472820.42 0.199666E+09 129925.10
July 78800180.84 273390.59 78526790.24 0.221346E+09 677024.56
August 86780369.56 4411084.64 82369284.92 0.243305E+09 36491.98
September 0.107117E+09 22994421.70 84122489.48 0.288766E+09 962934.18
October 0.154941E+09 70901823.75 84038913.55 0.365074E+09 2848481.30
November 0.174538E+09 97466470.57 77071929.65 0.364614E+09 17342752.22
December 0.199439E+09 0.126438E+09 73001524.18 0.384198E+09 40587621.24
           
Annual Sum or Average 0.154063E+10 0.612029E+09 0.928600E+09 0.349527E+10 0.188027E+09
Minimum of Months 71515153.18 42332.76 70640206.20 0.199666E+09 36491.98
Maximum of Months 0.205438E+09 0.133586E+09 84122489.48 0.393101E+09 50181864.02



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.175861E+09 75554026.64 0.100307E+09 0.325760E+09 98396398.87
February 0.200547E+09 91453484.13 0.109094E+09 0.392067E+09 67688266.46
March 0.276196E+09 0.127044E+09 0.149152E+09 0.537025E+09 53050940.06
April 0.294310E+09 0.137417E+09 0.156893E+09 0.608055E+09 21338409.82
May 0.276804E+09 0.107479E+09 0.169325E+09 0.631531E+09 3529131.56
June 0.226048E+09 63472662.77 0.162575E+09 0.561681E+09 253333.30
July 0.260479E+09 80434695.21 0.180044E+09 0.643577E+09 1285848.87
August 0.260366E+09 84900100.50 0.175466E+09 0.633086E+09 70159.33
September 0.214836E+09 63419366.09 0.151416E+09 0.532128E+09 1896789.36
October 0.221226E+09 86491425.23 0.134735E+09 0.509368E+09 5401816.41
November 0.175192E+09 63651240.56 0.111540E+09 0.377977E+09 33844565.76
December 0.181149E+09 80296573.82 0.100853E+09 0.349719E+09 77783544.78
           
Annual Sum or Average 0.276301E+10 0.106161E+10 0.170140E+10 0.610197E+10 0.364539E+09
Minimum of Months 0.175192E+09 63419366.09 0.100307E+09 0.325760E+09 70159.33
Maximum of Months 0.294310E+09 0.137417E+09 0.180044E+09 0.643577E+09 98396398.87



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43628507.26 0.00 43628507.26 71707257.78 54482598.20
February 46643772.08 0.00 46643772.08 87417120.70 38445366.48
March 61602348.59 272.00 61602076.60 0.114323E+09 31566806.55
April 66805922.77 211458.97 66594463.80 0.143640E+09 13899225.23
May 77567406.39 2195123.81 75372282.59 0.199521E+09 2007431.50
June 79983703.15 4326216.13 75657487.03 0.223118E+09 184212.78
July 84105169.86 3021973.11 81083196.76 0.235340E+09 888311.81
August 75261829.50 486152.07 74775677.44 0.209979E+09 75323.10
September 64748310.87 6322.70 64741988.17 0.182664E+09 1333919.33
October 56031552.72 0.00 56031552.72 0.146910E+09 2985053.59
November 47148120.66 0.00 47148120.66 0.106868E+09 18944162.84
December 43154027.20 0.00 43154027.20 77250556.10 43279826.07
           
Annual Sum or Average 0.746681E+09 10247518.78 0.736433E+09 0.179874E+10 0.208092E+09
Minimum of Months 43154027.20 0.00 43154027.20 71707257.78 75323.10
Maximum of Months 84105169.86 4326216.13 81083196.76 0.235340E+09 54482598.20



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.175861E+09 75554026.64 0.100307E+09 0.328438E+09 0.100410E+09
February 0.200547E+09 91453484.13 0.109094E+09 0.392409E+09 71383602.41
March 0.276196E+09 0.127044E+09 0.149152E+09 0.535173E+09 58257284.83
April 0.294310E+09 0.137417E+09 0.156893E+09 0.604474E+09 26021549.66
May 0.276804E+09 0.107479E+09 0.169325E+09 0.629285E+09 3837336.35
June 0.226048E+09 63472662.77 0.162575E+09 0.560216E+09 328653.64
July 0.260479E+09 80434695.21 0.180044E+09 0.642078E+09 1646073.09
August 0.260366E+09 84900100.50 0.175466E+09 0.633063E+09 124576.00
September 0.214836E+09 63419366.09 0.151416E+09 0.533398E+09 2430972.36
October 0.221226E+09 86491425.23 0.134735E+09 0.511886E+09 5489495.32
November 0.175192E+09 63651240.56 0.111540E+09 0.380029E+09 35302628.94
December 0.181149E+09 80296573.82 0.100853E+09 0.351931E+09 79693699.10
           
Annual Sum or Average 0.276301E+10 0.106161E+10 0.170140E+10 0.610238E+10 0.384926E+09
Minimum of Months 0.175192E+09 63419366.09 0.100307E+09 0.328438E+09 124576.00
Maximum of Months 0.294310E+09 0.137417E+09 0.180044E+09 0.642078E+09 0.100410E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.164318E+09 0.106848E+09 57469935.70 0.290775E+09 75625327.00
February 0.127585E+09 71083695.03 56500928.45 0.238494E+09 57635898.94
March 0.106323E+09 40571176.48 65751932.95 0.204516E+09 53408627.32
April 73830230.13 11980471.49 61849758.64 0.151462E+09 36058477.21
May 61836618.86 1072642.83 60763976.04 0.126911E+09 20050434.14
June 57200746.85 33859.47 57166887.38 0.119292E+09 10211928.97
July 63027610.18 218668.99 62808941.19 0.139575E+09 13959230.15
August 69410491.77 3528166.06 65882325.72 0.153320E+09 11374291.64
September 85676490.20 18391879.71 67284610.49 0.194463E+09 15197443.35
October 0.123928E+09 56710180.87 67217763.04 0.260508E+09 24877785.37
November 0.139603E+09 77957672.78 61645284.13 0.263973E+09 40728373.56
December 0.159520E+09 0.101130E+09 58389607.23 0.284634E+09 68154255.13
           
Annual Sum or Average 0.123226E+10 0.489526E+09 0.742732E+09 0.242792E+10 0.427282E+09
Minimum of Months 57200746.85 33859.47 56500928.45 0.119292E+09 10211928.97
Maximum of Months 0.164318E+09 0.106848E+09 67284610.49 0.290775E+09 75625327.00



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 34907432.38 0.00 34907432.38 59481068.25 41195084.34
February 37319963.98 0.00 37319963.98 72691491.37 28243779.43
March 49288411.47 217.63 49288193.84 96083668.18 21879780.14
April 53451822.62 169189.60 53282633.02 0.120961E+09 8164530.83
May 62062150.71 1756331.83 60305818.89 0.168073E+09 1146473.68
June 63995444.36 3461431.67 60534012.68 0.186935E+09 38168.22
July 67293054.78 2417898.95 64875155.83 0.197459E+09 368597.64
August 60217444.71 388973.21 59828471.50 0.177307E+09 8764.48
September 51805514.90 5058.83 51800456.07 0.154377E+09 464450.66
October 44831184.01 0.00 44831184.01 0.125462E+09 1420967.20
November 37723496.33 0.00 37723496.33 90507975.57 13524120.22
December 34527798.01 0.00 34527798.01 64366100.60 32326469.11
           
Annual Sum or Average 0.597424E+09 8199101.71 0.589225E+09 0.151370E+10 0.148781E+09
Minimum of Months 34527798.01 0.00 34527798.01 59481068.25 8764.48
Maximum of Months 67293054.78 3461431.67 64875155.83 0.197459E+09 41195084.34



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195027E+09 92875897.09 0.102151E+09 0.361010E+09 94843282.29
February 0.205695E+09 95665196.11 0.110030E+09 0.398281E+09 63659106.52
March 0.279568E+09 0.133457E+09 0.146111E+09 0.535048E+09 48448802.91
April 0.293093E+09 0.131765E+09 0.161328E+09 0.608112E+09 20042844.00
May 0.286373E+09 0.115368E+09 0.171005E+09 0.650667E+09 3299687.92
June 0.272083E+09 0.105099E+09 0.166983E+09 0.651871E+09 275236.30
July 0.288698E+09 0.104559E+09 0.184140E+09 0.699838E+09 1220184.50
August 0.264295E+09 89125610.13 0.175169E+09 0.641032E+09 56564.79
September 0.246440E+09 89578277.52 0.156862E+09 0.594851E+09 1814975.02
October 0.234101E+09 0.100955E+09 0.133146E+09 0.534868E+09 5180413.45
November 0.183298E+09 72693177.46 0.110605E+09 0.391798E+09 32048834.68
December 0.151995E+09 52811336.97 99183346.68 0.291278E+09 75739001.59
           
Annual Sum or Average 0.290066E+10 0.118395E+10 0.171671E+10 0.635865E+10 0.346629E+09
Minimum of Months 0.151995E+09 52811336.97 99183346.68 0.291278E+09 56564.79
Maximum of Months 0.293093E+09 0.133457E+09 0.184140E+09 0.699838E+09 94843282.29



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.205438E+09 0.133586E+09 71851706.15 0.391966E+09 50006547.02
February 0.159512E+09 88872289.58 70640206.20 0.325594E+09 34143490.25
March 0.132930E+09 50724056.24 82206261.55 0.285928E+09 26836253.46
April 92306141.22 14978567.61 77327573.62 0.219322E+09 11002677.05
May 77311145.63 1341070.18 75970075.44 0.201153E+09 1825653.14
June 71515153.18 42332.76 71472820.42 0.198524E+09 149383.25
July 78800180.84 273390.59 78526790.24 0.220595E+09 673113.49
August 86780369.56 4411084.64 82369284.92 0.243093E+09 28500.75
September 0.107117E+09 22994421.70 84122489.48 0.287977E+09 983035.24
October 0.154941E+09 70901823.75 84038913.55 0.364608E+09 2769804.01
November 0.174538E+09 97466470.57 77071929.65 0.364072E+09 17155880.74
December 0.199439E+09 0.126438E+09 73001524.18 0.384146E+09 39963426.49
           
Annual Sum or Average 0.154063E+10 0.612029E+09 0.928600E+09 0.348698E+10 0.185538E+09
Minimum of Months 71515153.18 42332.76 70640206.20 0.198524E+09 28500.75
Maximum of Months 0.205438E+09 0.133586E+09 84122489.48 0.391966E+09 50006547.02



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43628507.26 0.00 43628507.26 70008646.69 54122534.97
February 46643772.08 0.00 46643772.08 85979833.20 37914643.63
March 61602348.59 272.00 61602076.60 0.112866E+09 30654701.60
April 66805922.77 211458.97 66594463.80 0.142453E+09 13244244.71
May 77567406.39 2195123.81 75372282.59 0.198986E+09 1945958.44
June 79983703.15 4326216.13 75657487.03 0.221911E+09 208389.25
July 84105169.86 3021973.11 81083196.76 0.234550E+09 909592.66
August 75261829.50 486152.07 74775677.44 0.209748E+09 66150.75
September 64748310.87 6322.70 64741988.17 0.181736E+09 1370967.14
October 56031552.72 0.00 56031552.72 0.146187E+09 2917487.67
November 47148120.66 0.00 47148120.66 0.105817E+09 18681287.26
December 43154027.20 0.00 43154027.20 76858042.66 42074344.35
           
Annual Sum or Average 0.746681E+09 10247518.78 0.736433E+09 0.178710E+10 0.204110E+09
Minimum of Months 43154027.20 0.00 43154027.20 70008646.69 66150.75
Maximum of Months 84105169.86 4326216.13 81083196.76 0.234550E+09 54122534.97



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195027E+09 92875897.09 0.102151E+09 0.362887E+09 96639680.20
February 0.205695E+09 95665196.11 0.110030E+09 0.397566E+09 66983476.15
March 0.279568E+09 0.133457E+09 0.146111E+09 0.532572E+09 52879588.97
April 0.293093E+09 0.131765E+09 0.161328E+09 0.603590E+09 24384410.51
May 0.286373E+09 0.115368E+09 0.171005E+09 0.648051E+09 3563971.89
June 0.272083E+09 0.105099E+09 0.166983E+09 0.650326E+09 355453.17
July 0.288698E+09 0.104559E+09 0.184140E+09 0.698316E+09 1636634.39
August 0.264295E+09 89125610.13 0.175169E+09 0.641015E+09 110371.06
September 0.246440E+09 89578277.52 0.156862E+09 0.595880E+09 2354755.60
October 0.234101E+09 0.100955E+09 0.133146E+09 0.536865E+09 5247344.37
November 0.183298E+09 72693177.46 0.110605E+09 0.392769E+09 33323068.05
December 0.151995E+09 52811336.97 99183346.68 0.293298E+09 76652312.04
           
Annual Sum or Average 0.290066E+10 0.118395E+10 0.171671E+10 0.635314E+10 0.364131E+09
Minimum of Months 0.151995E+09 52811336.97 99183346.68 0.293298E+09 110371.06
Maximum of Months 0.293093E+09 0.133457E+09 0.184140E+09 0.698316E+09 96639680.20



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55252751.64 0.00 55252751.64 88139952.29 77063002.82
February 59071394.28 0.00 59071394.28 0.109818E+09 53282489.37
March 78015487.60 344.47 78015143.14 0.145169E+09 44629669.46
April 84605485.97 267799.45 84337686.52 0.180398E+09 23184485.61
May 98234225.96 2779985.80 95454240.17 0.241406E+09 5818084.69
June 0.101294E+09 5478879.76 95815433.60 0.264671E+09 1784843.16
July 0.106514E+09 3827138.26 0.102687E+09 0.280324E+09 4012102.74
August 95314358.31 615680.92 94698677.39 0.246876E+09 1512530.02
September 81999650.32 8007.30 81991643.02 0.214841E+09 6844150.75
October 70960426.12 0.00 70960426.12 0.170952E+09 11257086.25
November 59710119.94 0.00 59710119.94 0.126234E+09 31585412.47
December 54651852.58 0.00 54651852.58 94542997.65 62979850.68
           
Annual Sum or Average 0.945624E+09 12977835.95 0.932646E+09 0.216337E+10 0.323954E+09
Minimum of Months 54651852.58 0.00 54651852.58 88139952.29 1512530.02
Maximum of Months 0.106514E+09 5478879.76 0.102687E+09 0.280324E+09 77063002.82



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 20368452.09 0.00 20368452.09 32492036.00 28408613.77
February 21776161.89 0.00 21776161.89 40483314.41 19642131.84
March 28759739.10 126.98 28759612.11 53515355.42 16452344.13
April 31189085.37 98721.97 31090363.40 66502046.03 8546761.39
May 36213203.25 1024817.87 35188385.37 88992096.35 2144786.93
June 37341278.17 2019741.94 35321536.23 97568698.34 657967.09
July 39265430.58 1410841.63 37854588.94 0.103339E+09 1479027.20
August 35136819.13 226965.48 34909853.65 91008577.23 557581.19
September 30228466.45 2951.82 30225514.63 79199445.67 2523037.36
October 26158951.31 0.00 26158951.31 63019953.59 4149960.06
November 22011622.61 0.00 22011622.61 46535232.60 11643690.88
December 20146935.81 0.00 20146935.81 34852463.65 23216980.75
           
Annual Sum or Average 0.348596E+09 4784167.70 0.343812E+09 0.797508E+09 0.119423E+09
Minimum of Months 20146935.81 0.00 20146935.81 32492036.00 557581.19
Maximum of Months 39265430.58 2019741.94 37854588.94 0.103339E+09 28408613.77



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95856434.08 62330717.53 33525716.55 0.183010E+09 26653200.86
February 74427887.75 41467452.19 32960435.56 0.151918E+09 18585951.38
March 62024750.61 23667640.24 38357110.37 0.133502E+09 15780675.98
April 43069673.53 6988939.29 36080734.24 0.101227E+09 8634269.36
May 36073069.01 625737.94 35447331.07 89292036.93 2157286.31
June 33368682.29 19752.29 33348930.00 86213850.26 645702.85
July 36767846.84 127562.95 36640283.89 96377599.02 1469033.13
August 40491370.74 2058194.32 38433176.42 0.106451E+09 538090.37
September 49980319.11 10729104.51 39251214.60 0.128867E+09 2472981.71
October 72294723.66 33082505.25 39212218.41 0.165239E+09 4078626.86
November 81438914.21 45477462.41 35961451.80 0.167121E+09 11081339.76
December 93057539.94 58995322.93 34062217.01 0.178655E+09 22318540.83
           
Annual Sum or Average 0.718851E+09 0.285570E+09 0.433281E+09 0.158787E+10 0.114416E+09
Minimum of Months 33368682.29 19752.29 32960435.56 86213850.26 538090.37
Maximum of Months 95856434.08 62330717.53 39251214.60 0.183010E+09 26653200.86



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.260174E+09 0.169178E+09 90995652.25 0.496727E+09 72342238.92
February 0.202013E+09 0.112551E+09 89461364.01 0.412336E+09 50446073.71
March 0.168348E+09 64238816.72 0.104109E+09 0.362351E+09 42831982.48
April 0.116900E+09 18969410.78 97930492.89 0.274750E+09 23435173.14
May 97909687.87 1698380.77 96211307.10 0.242357E+09 5855316.30
June 90569429.14 53611.76 90515817.38 0.234002E+09 1752569.60
July 99795457.01 346231.94 99449225.08 0.261589E+09 3987256.39
August 0.109902E+09 5586360.37 0.104316E+09 0.288931E+09 1460487.33
September 0.135657E+09 29120984.22 0.106536E+09 0.349770E+09 6712178.20
October 0.196223E+09 89792686.12 0.106430E+09 0.448493E+09 11070227.56
November 0.221042E+09 0.123435E+09 97606735.93 0.453601E+09 30077022.75
December 0.252577E+09 0.160125E+09 92451824.24 0.484906E+09 60577084.98
           
Annual Sum or Average 0.195111E+10 0.775096E+09 0.117601E+10 0.430981E+10 0.310548E+09
Minimum of Months 90569429.14 53611.76 89461364.01 0.234002E+09 1460487.33
Maximum of Months 0.260174E+09 0.169178E+09 0.106536E+09 0.496727E+09 72342238.92



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.205438E+09 0.133586E+09 71851706.15 0.391112E+09 47912513.83
February 0.159512E+09 88872289.58 70640206.20 0.324476E+09 32801024.51
March 0.132930E+09 50724056.24 82206261.55 0.285003E+09 25588391.67
April 92306141.22 14978567.61 77327573.62 0.218350E+09 10007460.98
May 77311145.63 1341070.18 75970075.44 0.201142E+09 1533919.18
June 71515153.18 42332.76 71472820.42 0.199526E+09 62431.26
July 78800180.84 273390.59 78526790.24 0.220920E+09 451918.73
August 86780369.56 4411084.64 82369284.92 0.243061E+09 9977.37
September 0.107117E+09 22994421.70 84122489.48 0.287952E+09 532630.28
October 0.154941E+09 70901823.75 84038913.55 0.364183E+09 2089379.43
November 0.174538E+09 97466470.57 77071929.65 0.363150E+09 15811862.05
December 0.199439E+09 0.126438E+09 73001524.18 0.382120E+09 38524828.12
           
Annual Sum or Average 0.154063E+10 0.612029E+09 0.928600E+09 0.348099E+10 0.175326E+09
Minimum of Months 71515153.18 42332.76 70640206.20 0.199526E+09 9977.37
Maximum of Months 0.205438E+09 0.133586E+09 84122489.48 0.391112E+09 47912513.83



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.175861E+09 75554026.64 0.100307E+09 0.323394E+09 93523909.79
February 0.200547E+09 91453484.13 0.109094E+09 0.389373E+09 64171565.42
March 0.276196E+09 0.127044E+09 0.149152E+09 0.533302E+09 49479967.62
April 0.294310E+09 0.137417E+09 0.156893E+09 0.604177E+09 18610734.41
May 0.276804E+09 0.107479E+09 0.169325E+09 0.629274E+09 2856853.06
June 0.226048E+09 63472662.77 0.162575E+09 0.560254E+09 117759.33
July 0.260479E+09 80434695.21 0.180044E+09 0.641697E+09 844075.27
August 0.260366E+09 84900100.50 0.175466E+09 0.631687E+09 19081.38
September 0.214836E+09 63419366.09 0.151416E+09 0.530736E+09 1026566.17
October 0.221226E+09 86491425.23 0.134735E+09 0.508657E+09 3885911.63
November 0.175192E+09 63651240.56 0.111540E+09 0.376481E+09 30677498.78
December 0.181149E+09 80296573.82 0.100853E+09 0.347309E+09 73653113.09
           
Annual Sum or Average 0.276301E+10 0.106161E+10 0.170140E+10 0.607634E+10 0.338867E+09
Minimum of Months 0.175192E+09 63419366.09 0.100307E+09 0.323394E+09 19081.38
Maximum of Months 0.294310E+09 0.137417E+09 0.180044E+09 0.641697E+09 93523909.79



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43628507.26 0.00 43628507.26 71775809.90 52617085.98
February 46643772.08 0.00 46643772.08 87031716.70 37423373.42
March 61602348.59 272.00 61602076.60 0.113372E+09 30686333.44
April 66805922.77 211458.97 66594463.80 0.142469E+09 13000594.63
May 77567406.39 2195123.81 75372282.59 0.198930E+09 1693254.65
June 79983703.15 4326216.13 75657487.03 0.222653E+09 130691.52
July 84105169.86 3021973.11 81083196.76 0.234771E+09 749021.50
August 75261829.50 486152.07 74775677.44 0.209843E+09 46344.14
September 64748310.87 6322.70 64741988.17 0.182573E+09 918783.14
October 56031552.72 0.00 56031552.72 0.147392E+09 2142350.74
November 47148120.66 0.00 47148120.66 0.107097E+09 17455074.57
December 43154027.20 0.00 43154027.20 77274789.63 41537826.70
           
Annual Sum or Average 0.746681E+09 10247518.78 0.736433E+09 0.179518E+10 0.198401E+09
Minimum of Months 43154027.20 0.00 43154027.20 71775809.90 46344.14
Maximum of Months 84105169.86 4326216.13 81083196.76 0.234771E+09 52617085.98



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.175861E+09 75554026.64 0.100307E+09 0.327350E+09 96703635.05
February 0.200547E+09 91453484.13 0.109094E+09 0.390419E+09 69489375.73
March 0.276196E+09 0.127044E+09 0.149152E+09 0.531509E+09 56513871.14
April 0.294310E+09 0.137417E+09 0.156893E+09 0.600634E+09 24325270.71
May 0.276804E+09 0.107479E+09 0.169325E+09 0.626989E+09 3190630.27
June 0.226048E+09 63472662.77 0.162575E+09 0.558693E+09 234647.93
July 0.260479E+09 80434695.21 0.180044E+09 0.640101E+09 1356648.69
August 0.260366E+09 84900100.50 0.175466E+09 0.631639E+09 78190.54
September 0.214836E+09 63419366.09 0.151416E+09 0.532164E+09 1663031.58
October 0.221226E+09 86491425.23 0.134735E+09 0.511514E+09 3936366.21
November 0.175192E+09 63651240.56 0.111540E+09 0.379358E+09 32506824.17
December 0.181149E+09 80296573.82 0.100853E+09 0.350779E+09 76365851.39
           
Annual Sum or Average 0.276301E+10 0.106161E+10 0.170140E+10 0.608115E+10 0.366364E+09
Minimum of Months 0.175192E+09 63419366.09 0.100307E+09 0.327350E+09 78190.54
Maximum of Months 0.294310E+09 0.137417E+09 0.180044E+09 0.640101E+09 96703635.05



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.301294E+09 0.195917E+09 0.105377E+09 0.570012E+09 71563292.36
February 0.233940E+09 0.130340E+09 0.103601E+09 0.474581E+09 47935869.95
March 0.194955E+09 74391696.48 0.120563E+09 0.419474E+09 35982393.36
April 0.135376E+09 21967506.89 0.113408E+09 0.325490E+09 12516469.14
May 0.113384E+09 1966808.12 0.111417E+09 0.303374E+09 1904763.14
June 0.104884E+09 62085.05 0.104822E+09 0.300498E+09 57737.23
July 0.115568E+09 400953.54 0.115167E+09 0.332820E+09 460709.37
August 0.127272E+09 6469278.96 0.120802E+09 0.364344E+09 4255.97
September 0.157097E+09 33723526.21 0.123374E+09 0.427313E+09 544743.21
October 0.227235E+09 0.103984E+09 0.123251E+09 0.536556E+09 2712512.78
November 0.255977E+09 0.142944E+09 0.113033E+09 0.531919E+09 23157634.28
December 0.292497E+09 0.185433E+09 0.107064E+09 0.557825E+09 57585325.05
           
Annual Sum or Average 0.225948E+10 0.897600E+09 0.136188E+10 0.514421E+10 0.254426E+09
Minimum of Months 0.104884E+09 62085.05 0.103601E+09 0.300498E+09 4255.97
Maximum of Months 0.301294E+09 0.195917E+09 0.123374E+09 0.570012E+09 71563292.36



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.305388E+09 0.00 0.305388E+09 0.543875E+09 0.351690E+09
February 0.326494E+09 0.00 0.326494E+09 0.658564E+09 0.244748E+09
March 0.431200E+09 1903.90 0.431198E+09 0.865579E+09 0.201453E+09
April 0.467624E+09 1480156.76 0.466144E+09 0.107460E+10 88921749.19
May 0.542951E+09 15365284.69 0.527586E+09 0.143471E+10 19348658.39
June 0.559865E+09 30282365.96 0.529582E+09 0.158068E+10 3042876.67
July 0.588714E+09 21153010.59 0.567561E+09 0.167789E+10 8934455.00
August 0.526813E+09 3402935.57 0.523410E+09 0.149738E+10 2377210.30
September 0.453221E+09 44257.23 0.453177E+09 0.131503E+10 14297133.42
October 0.392206E+09 0.00 0.392206E+09 0.108047E+10 28192726.45
November 0.330024E+09 0.00 0.330024E+09 0.796731E+09 0.128225E+09
December 0.302067E+09 0.00 0.302067E+09 0.584220E+09 0.281000E+09
           
Annual Sum or Average 0.522657E+10 71729914.70 0.515484E+10 0.131097E+11 0.137223E+10
Minimum of Months 0.302067E+09 0.00 0.302067E+09 0.543875E+09 2377210.30
Maximum of Months 0.588714E+09 30282365.96 0.567561E+09 0.167789E+10 0.351690E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.305388E+09 0.00 0.305388E+09 0.526491E+09 0.374622E+09
February 0.326494E+09 0.00 0.326494E+09 0.640434E+09 0.263379E+09
March 0.431200E+09 1903.90 0.431198E+09 0.843219E+09 0.219368E+09
April 0.467624E+09 1480156.76 0.466144E+09 0.105043E+10 0.101806E+09
May 0.542951E+09 15365284.69 0.527586E+09 0.140105E+10 24275514.36
June 0.559865E+09 30282365.96 0.529582E+09 0.154618E+10 4603469.45
July 0.588714E+09 21153010.59 0.567561E+09 0.164339E+10 11694203.15
August 0.526813E+09 3402935.57 0.523410E+09 0.146135E+10 3895052.25
September 0.453221E+09 44257.23 0.453177E+09 0.128449E+10 19511097.88
October 0.392206E+09 0.00 0.392206E+09 0.104996E+10 34714222.97
November 0.330024E+09 0.00 0.330024E+09 0.772028E+09 0.140139E+09
December 0.302067E+09 0.00 0.302067E+09 0.564978E+09 0.302559E+09
           
Annual Sum or Average 0.522657E+10 71729914.70 0.515484E+10 0.127840E+11 0.150057E+10
Minimum of Months 0.302067E+09 0.00 0.302067E+09 0.526491E+09 3895052.25
Maximum of Months 0.588714E+09 30282365.96 0.567561E+09 0.164339E+10 0.374622E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43628507.26 0.00 43628507.26 0.176901E+09 32493995.22
February 46643772.08 0.00 46643772.08 0.189753E+09 25405033.42
March 61602348.59 272.00 61602076.60 0.234492E+09 21480486.33
April 66805922.77 211458.97 66594463.80 0.270113E+09 10786845.58
May 77567406.39 2195123.81 75372282.59 0.331670E+09 3171804.46
June 79983703.15 4326216.13 75657487.03 0.350808E+09 617968.26
July 84105169.86 3021973.11 81083196.76 0.370125E+09 1466476.14
August 75261829.50 486152.07 74775677.44 0.341608E+09 627435.92
September 64748310.87 6322.70 64741988.17 0.311180E+09 2250196.99
October 56031552.72 0.00 56031552.72 0.278090E+09 3924738.56
November 47148120.66 0.00 47148120.66 0.226734E+09 13978903.69
December 43154027.20 0.00 43154027.20 0.188786E+09 26900287.34
           
Annual Sum or Average 0.746681E+09 10247518.78 0.736433E+09 0.327026E+10 0.143104E+09
Minimum of Months 43154027.20 0.00 43154027.20 0.176901E+09 617968.26
Maximum of Months 84105169.86 4326216.13 81083196.76 0.370125E+09 32493995.22



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.390026E+09 0.185739E+09 0.204287E+09 0.113692E+10 0.122054E+09
February 0.411360E+09 0.191317E+09 0.220043E+09 0.119048E+10 94707588.28
March 0.559096E+09 0.266896E+09 0.292200E+09 0.152730E+10 79921746.78
April 0.586145E+09 0.263512E+09 0.322633E+09 0.168338E+10 40495257.63
May 0.572705E+09 0.230719E+09 0.341986E+09 0.178675E+10 11835203.56
June 0.544126E+09 0.210184E+09 0.333943E+09 0.177943E+10 2310059.67
July 0.577355E+09 0.209103E+09 0.368253E+09 0.190112E+10 5440814.66
August 0.528552E+09 0.178239E+09 0.350313E+09 0.177164E+10 2369437.07
September 0.492846E+09 0.179144E+09 0.313702E+09 0.167436E+10 8396723.37
October 0.468168E+09 0.201896E+09 0.266273E+09 0.156627E+10 14783500.98
November 0.366570E+09 0.145376E+09 0.221194E+09 0.124096E+10 52246472.58
December 0.303968E+09 0.105615E+09 0.198353E+09 0.100911E+10 0.100894E+09
           
Annual Sum or Average 0.580092E+10 0.236774E+10 0.343318E+10 0.182677E+11 0.535455E+09
Minimum of Months 0.303968E+09 0.105615E+09 0.198353E+09 0.100911E+10 2310059.67
Maximum of Months 0.586145E+09 0.266896E+09 0.368253E+09 0.190112E+10 0.122054E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.205438E+09 0.133586E+09 71851706.15 0.505587E+09 32296528.25
February 0.159512E+09 88872289.58 70640206.20 0.433023E+09 25044918.56
March 0.132930E+09 50724056.24 82206261.55 0.408905E+09 21227035.46
April 92306141.22 14978567.61 77327573.62 0.345244E+09 10736483.31
May 77311145.63 1341070.18 75970075.44 0.331498E+09 3143214.90
June 71515153.18 42332.76 71472820.42 0.326232E+09 607187.46
July 78800180.84 273390.59 78526790.24 0.354850E+09 1458393.24
August 86780369.56 4411084.64 82369284.92 0.374652E+09 619571.74
September 0.107117E+09 22994421.70 84122489.48 0.418636E+09 2227831.17
October 0.154941E+09 70901823.75 84038913.55 0.498996E+09 3902468.43
November 0.174538E+09 97466470.57 77071929.65 0.488506E+09 13829394.23
December 0.199439E+09 0.126438E+09 73001524.18 0.501179E+09 26668468.57
           
Annual Sum or Average 0.154063E+10 0.612029E+09 0.928600E+09 0.498731E+10 0.141761E+09
Minimum of Months 71515153.18 42332.76 70640206.20 0.326232E+09 607187.46
Maximum of Months 0.205438E+09 0.133586E+09 84122489.48 0.505587E+09 32296528.25



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55252751.64 0.00 55252751.64 79432258.97 87972326.83
February 59071394.28 0.00 59071394.28 99806729.86 63550401.20
March 78015487.60 344.47 78015143.14 0.132983E+09 54737390.20
April 84605485.97 267799.45 84337686.52 0.167951E+09 31098222.16
May 98234225.96 2779985.80 95454240.17 0.226025E+09 10292448.14
June 0.101294E+09 5478879.76 95815433.60 0.250990E+09 3267936.67
July 0.106514E+09 3827138.26 0.102687E+09 0.268719E+09 5750929.30
August 95314358.31 615680.92 94698677.39 0.233446E+09 3243139.60
September 81999650.32 8007.30 81991643.02 0.204233E+09 9024475.20
October 70960426.12 0.00 70960426.12 0.160953E+09 14582246.63
November 59710119.94 0.00 59710119.94 0.115374E+09 37134481.48
December 54651852.58 0.00 54651852.58 85898798.54 73022139.49
           
Annual Sum or Average 0.945624E+09 12977835.95 0.932646E+09 0.202581E+10 0.393676E+09
Minimum of Months 54651852.58 0.00 54651852.58 79432258.97 3243139.60
Maximum of Months 0.106514E+09 5478879.76 0.102687E+09 0.268719E+09 87972326.83



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49434846.25 0.00 49434846.25 71068343.02 78707800.44
February 52851400.29 0.00 52851400.29 89297459.37 56858784.75
March 69800752.36 308.19 69800444.16 0.118981E+09 48973750.42
April 75696848.87 239601.18 75457247.69 0.150266E+09 27823697.20
May 87890534.18 2487263.83 85403270.35 0.202226E+09 9208692.35
June 90628405.96 4901974.48 85726431.48 0.224562E+09 2923835.32
July 95298381.76 3424155.11 91874226.65 0.240423E+09 5145378.24
August 85278117.52 550852.05 84727265.47 0.208865E+09 2901649.29
September 73365397.84 7164.16 73358233.68 0.182728E+09 8074232.16
October 63488562.12 0.00 63488562.12 0.144005E+09 13047042.67
November 53422870.55 0.00 53422870.55 0.103226E+09 33224310.95
December 48897219.58 0.00 48897219.58 76853979.36 65332302.87
           
Annual Sum or Average 0.846053E+09 11611319.00 0.834442E+09 0.181250E+10 0.352221E+09
Minimum of Months 48897219.58 0.00 48897219.58 71068343.02 2901649.29
Maximum of Months 95298381.76 4901974.48 91874226.65 0.240423E+09 78707800.44



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.766960E+09 0.498717E+09 0.268244E+09 0.143059E+10 0.243094E+09
February 0.595508E+09 0.331787E+09 0.263721E+09 0.118005E+10 0.177997E+09
March 0.496268E+09 0.189368E+09 0.306900E+09 0.102759E+10 0.155666E+09
April 0.344606E+09 55919456.26 0.288687E+09 0.771887E+09 92951532.33
May 0.288626E+09 5006614.61 0.283619E+09 0.669020E+09 30183934.52
June 0.266987E+09 158040.79 0.266829E+09 0.650472E+09 9818462.37
July 0.294185E+09 1020648.55 0.293164E+09 0.737221E+09 17003145.37
August 0.323977E+09 16467893.41 0.307509E+09 0.811672E+09 9538379.66
September 0.399899E+09 85845028.22 0.314054E+09 0.997886E+09 26397432.80
October 0.578440E+09 0.264698E+09 0.313742E+09 0.128892E+10 42665429.52
November 0.651604E+09 0.363871E+09 0.287732E+09 0.130036E+10 0.104781E+09
December 0.744566E+09 0.472030E+09 0.272536E+09 0.139709E+10 0.206698E+09
           
Annual Sum or Average 0.575163E+10 0.228489E+10 0.346674E+10 0.122628E+11 0.111680E+10
Minimum of Months 0.266987E+09 158040.79 0.263721E+09 0.650472E+09 9538379.66
Maximum of Months 0.766960E+09 0.498717E+09 0.314054E+09 0.143059E+10 0.243094E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 726.99 119.53 387.94 252.26 135.68 0.00 0.00
February 665.58 99.00 333.49 185.80 147.68 0.00 0.00
March 525.37 80.06 251.02 95.78 155.23 0.00 0.00
April 405.87 51.48 180.11 29.23 150.89 0.00 0.00
May 334.49 19.59 145.99 2.53 143.46 0.00 0.00
June 331.82 6.62 139.54 0.08 139.46 0.00 0.00
July 364.13 11.71 148.80 0.52 148.28 0.00 0.00
August 402.02 5.43 163.87 8.33 155.54 0.00 0.00
September 513.58 16.00 209.01 44.87 164.15 0.00 0.00
October 648.21 26.50 292.58 133.89 158.69 0.00 0.00
November 680.55 57.47 340.57 190.18 150.39 0.00 0.00
December 710.28 103.73 376.61 238.76 137.85 0.00 0.00
               
Annual Sum or Average 525.06 49.54 247.08 98.16 148.93 0.00 0.00
Minimum of Months 331.82 5.43 139.54 0.08 135.68 0.00 0.00
Maximum of Months 726.99 119.53 387.94 252.26 164.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2073.84 290.03 1092.40 710.34 382.06 0.00 0.00
February 1908.99 228.67 939.07 523.21 415.87 0.00 0.00
March 1526.03 171.95 706.84 269.72 437.12 0.00 0.00
April 1204.36 88.25 507.19 82.30 424.89 0.00 0.00
May 1032.72 20.26 411.09 7.13 403.96 0.00 0.00
June 1039.48 3.63 392.95 0.23 392.72 0.00 0.00
July 1120.41 10.67 419.01 1.45 417.56 0.00 0.00
August 1232.17 2.62 461.45 23.46 437.99 0.00 0.00
September 1521.11 21.15 588.57 126.35 462.22 0.00 0.00
October 1882.03 40.10 823.88 377.02 446.87 0.00 0.00
November 1961.25 121.71 959.03 535.55 423.48 0.00 0.00
December 2027.01 242.63 1060.50 672.32 388.18 0.00 0.00
               
Annual Sum or Average 1542.35 102.93 695.77 276.40 419.37 0.00 0.00
Minimum of Months 1032.72 2.62 392.95 0.23 382.06 0.00 0.00
Maximum of Months 2073.84 290.03 1092.40 710.34 462.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2710.30 413.68 1419.09 922.77 496.32 0.00 0.00
February 2490.55 331.73 1219.91 679.67 540.24 0.00 0.00
March 1981.71 257.92 918.23 350.38 567.85 0.00 0.00
April 1550.74 150.04 658.87 106.92 551.95 0.00 0.00
May 1300.57 46.74 534.03 9.26 524.77 0.00 0.00
June 1300.22 14.16 510.46 0.30 510.16 0.00 0.00
July 1415.46 26.75 544.32 1.89 542.43 0.00 0.00
August 1559.82 10.62 599.44 30.47 568.97 0.00 0.00
September 1965.42 43.28 764.59 164.13 600.45 0.00 0.00
October 2447.07 69.75 1070.27 489.77 580.51 0.00 0.00
November 2553.10 183.18 1245.84 695.71 550.13 0.00 0.00
December 2645.80 352.33 1377.65 873.39 504.27 0.00 0.00
               
Annual Sum or Average 1990.97 157.59 903.85 359.06 544.78 0.00 0.00
Minimum of Months 1300.22 10.62 510.46 0.30 496.32 0.00 0.00
Maximum of Months 2710.30 413.68 1419.09 922.77 600.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 267.35 54.43 142.36 78.08 64.28 0.00 0.00
February 296.47 41.69 148.83 74.54 74.29 0.00 0.00
March 307.39 29.74 152.75 66.37 86.38 0.00 0.00
April 319.48 12.64 149.16 58.79 90.36 0.00 0.00
May 311.03 2.02 132.21 40.63 91.58 0.00 0.00
June 293.73 0.15 114.80 24.50 90.30 0.00 0.00
July 322.92 0.73 126.67 30.13 96.54 0.00 0.00
August 327.21 0.04 129.61 33.34 96.26 0.00 0.00
September 316.70 1.10 124.21 33.34 90.87 0.00 0.00
October 326.47 3.07 140.44 58.76 81.68 0.00 0.00
November 286.20 19.46 134.93 62.16 72.77 0.00 0.00
December 273.68 43.86 142.10 77.19 64.91 0.00 0.00
               
Annual Sum or Average 304.12 17.31 136.47 53.07 83.40 0.00 0.00
Minimum of Months 267.35 0.04 114.80 24.50 64.28 0.00 0.00
Maximum of Months 327.21 54.43 152.75 78.08 96.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 149.15 57.59 81.95 28.21 53.74 0.00 0.00
February 198.23 45.29 102.18 37.80 64.38 0.00 0.00
March 242.36 33.40 126.12 47.43 78.69 0.00 0.00
April 288.59 15.37 139.32 53.10 86.22 0.00 0.00
May 309.41 2.15 132.31 40.95 91.36 0.00 0.00
June 302.21 0.20 118.07 26.16 91.91 0.00 0.00
July 327.59 0.94 128.65 31.16 97.49 0.00 0.00
August 314.76 0.07 125.31 31.88 93.43 0.00 0.00
September 276.26 1.45 107.86 24.47 83.39 0.00 0.00
October 245.97 3.16 103.52 32.29 71.22 0.00 0.00
November 187.83 20.91 85.78 24.56 61.22 0.00 0.00
December 160.03 45.70 83.75 29.98 53.77 0.00 0.00
               
Annual Sum or Average 250.48 18.74 111.29 33.99 77.30 0.00 0.00
Minimum of Months 149.15 0.07 81.95 24.47 53.74 0.00 0.00
Maximum of Months 327.59 57.59 139.32 53.10 97.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 108.56 28.24 61.35 39.89 21.46 0.00 0.00
February 98.58 23.82 52.74 29.38 23.36 0.00 0.00
March 76.36 19.94 39.70 15.15 24.55 0.00 0.00
April 58.43 13.91 28.48 4.62 23.86 0.00 0.00
May 47.38 7.49 23.09 0.40 22.69 0.00 0.00
June 46.02 3.94 22.07 0.01 22.06 0.00 0.00
July 52.11 5.21 23.53 0.08 23.45 0.00 0.00
August 57.24 4.25 25.91 1.32 24.60 0.00 0.00
September 75.02 5.86 33.05 7.10 25.96 0.00 0.00
October 97.26 9.29 46.27 21.17 25.10 0.00 0.00
November 101.84 15.71 53.86 30.08 23.78 0.00 0.00
December 106.27 25.45 59.56 37.76 21.80 0.00 0.00
               
Annual Sum or Average 76.99 13.55 39.07 15.52 23.55 0.00 0.00
Minimum of Months 46.02 3.94 22.07 0.01 21.46 0.00 0.00
Maximum of Months 108.56 28.24 61.35 39.89 25.96 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 22.21 15.38 13.03 0.00 13.03 0.00 0.00
February 30.05 11.67 15.43 0.00 15.43 0.00 0.00
March 35.87 8.17 18.40 0.00 18.40 0.00 0.00
April 46.67 3.15 20.62 0.07 20.56 0.00 0.00
May 62.75 0.43 23.17 0.66 22.52 0.00 0.00
June 72.12 0.01 24.69 1.34 23.35 0.00 0.00
July 73.72 0.14 25.12 0.90 24.22 0.00 0.00
August 66.20 0.00 22.48 0.15 22.34 0.00 0.00
September 59.56 0.18 19.99 0.00 19.98 0.00 0.00
October 46.84 0.53 16.74 0.00 16.74 0.00 0.00
November 34.92 5.22 14.55 0.00 14.55 0.00 0.00
December 24.03 12.07 12.89 0.00 12.89 0.00 0.00
               
Annual Sum or Average 48.00 4.72 18.94 0.26 18.68 0.00 0.00
Minimum of Months 22.21 0.00 12.89 0.00 12.89 0.00 0.00
Maximum of Months 73.72 15.38 25.12 1.34 24.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 280.79 53.74 149.52 84.55 64.97 0.00 0.00
February 299.04 40.24 150.96 76.28 74.68 0.00 0.00
March 306.12 27.72 154.01 68.77 85.24 0.00 0.00
April 319.16 11.92 148.69 56.61 92.07 0.00 0.00
May 318.02 1.90 135.78 43.57 92.21 0.00 0.00
June 328.08 0.16 132.56 40.56 92.00 0.00 0.00
July 343.65 0.71 137.21 39.14 98.07 0.00 0.00
August 330.09 0.03 131.08 34.92 96.15 0.00 0.00
September 340.60 1.08 136.40 43.43 92.97 0.00 0.00
October 335.82 2.97 145.25 64.16 81.09 0.00 0.00
November 291.59 18.96 138.05 65.65 72.41 0.00 0.00
December 251.92 42.95 131.21 66.92 64.29 0.00 0.00
               
Annual Sum or Average 312.10 16.77 140.83 56.95 83.88 0.00 0.00
Minimum of Months 251.92 0.03 131.08 34.92 64.29 0.00 0.00
Maximum of Months 343.65 53.74 154.01 84.55 98.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 160.78 55.44 89.10 34.68 54.43 0.00 0.00
February 199.08 42.56 104.31 39.54 64.76 0.00 0.00
March 240.19 30.40 127.38 49.83 77.55 0.00 0.00
April 287.77 14.46 138.85 50.92 87.93 0.00 0.00
May 316.25 2.06 135.88 43.89 91.99 0.00 0.00
June 336.51 0.22 135.83 42.22 93.61 0.00 0.00
July 348.29 0.95 139.19 40.17 99.02 0.00 0.00
August 317.64 0.07 126.78 33.46 93.32 0.00 0.00
September 300.00 1.43 120.06 34.56 85.50 0.00 0.00
October 255.01 3.04 108.32 37.69 70.63 0.00 0.00
November 192.07 19.77 88.91 28.05 60.86 0.00 0.00
December 137.93 44.06 72.86 19.72 53.14 0.00 0.00
               
Annual Sum or Average 257.87 17.77 115.66 37.87 77.79 0.00 0.00
Minimum of Months 137.93 0.07 72.86 19.72 53.14 0.00 0.00
Maximum of Months 348.29 55.44 139.19 50.92 99.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 297.13 74.65 161.16 86.44 74.72 0.00 0.00
February 294.58 57.89 147.69 63.67 84.02 0.00 0.00
March 258.97 44.35 125.88 32.82 93.06 0.00 0.00
April 240.25 24.55 106.39 10.16 96.23 0.00 0.00
May 247.12 5.91 100.22 2.29 97.93 0.00 0.00
June 263.28 1.86 101.30 2.92 98.38 0.00 0.00
July 276.87 4.07 105.41 2.13 103.28 0.00 0.00
August 273.77 1.52 104.86 3.17 101.69 0.00 0.00
September 298.10 7.15 114.92 15.38 99.54 0.00 0.00
October 316.45 11.37 136.51 45.88 90.64 0.00 0.00
November 305.63 32.06 148.23 65.17 83.06 0.00 0.00
December 295.32 62.39 156.97 81.81 75.16 0.00 0.00
               
Annual Sum or Average 280.55 27.18 125.70 34.20 91.51 0.00 0.00
Minimum of Months 240.25 1.52 100.22 2.13 74.72 0.00 0.00
Maximum of Months 316.45 74.65 161.16 86.44 103.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 265.84 51.88 142.36 78.08 64.28 0.00 0.00
February 294.58 39.59 148.83 74.54 74.29 0.00 0.00
March 305.25 27.75 152.75 66.37 86.38 0.00 0.00
April 317.30 11.01 149.16 58.79 90.36 0.00 0.00
May 310.04 1.64 132.21 40.63 91.58 0.00 0.00
June 293.12 0.07 114.80 24.50 90.30 0.00 0.00
July 322.06 0.48 126.67 30.13 96.54 0.00 0.00
August 326.59 0.01 129.61 33.34 96.26 0.00 0.00
September 315.85 0.60 124.21 33.34 90.87 0.00 0.00
October 325.88 2.23 140.44 58.76 81.68 0.00 0.00
November 285.10 17.69 134.93 62.16 72.77 0.00 0.00
December 272.05 41.60 142.10 77.19 64.91 0.00 0.00
               
Annual Sum or Average 302.87 16.12 136.47 53.07 83.40 0.00 0.00
Minimum of Months 265.84 0.01 114.80 24.50 64.28 0.00 0.00
Maximum of Months 326.59 51.88 152.75 78.08 96.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 148.74 55.47 81.95 28.21 53.74 0.00 0.00
February 197.24 44.07 102.18 37.80 64.38 0.00 0.00
March 240.59 32.37 126.12 47.43 78.69 0.00 0.00
April 286.65 14.36 139.32 53.10 86.22 0.00 0.00
May 308.34 1.80 132.31 40.95 91.36 0.00 0.00
June 301.45 0.14 118.07 26.16 91.91 0.00 0.00
July 326.64 0.78 128.65 31.16 97.49 0.00 0.00
August 314.17 0.05 125.31 31.88 93.43 0.00 0.00
September 275.75 1.00 107.86 24.47 83.39 0.00 0.00
October 246.01 2.27 103.52 32.29 71.22 0.00 0.00
November 187.66 19.26 85.78 24.56 61.22 0.00 0.00
December 159.59 43.79 83.75 29.98 53.77 0.00 0.00
               
Annual Sum or Average 249.68 17.83 111.29 33.99 77.30 0.00 0.00
Minimum of Months 148.74 0.05 81.95 24.47 53.74 0.00 0.00
Maximum of Months 326.64 55.47 139.32 53.10 97.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 212.82 26.72 112.49 73.15 39.34 0.00 0.00
February 196.17 19.81 96.70 53.88 42.82 0.00 0.00
March 156.61 13.43 72.79 27.77 45.01 0.00 0.00
April 125.57 4.83 52.23 8.48 43.75 0.00 0.00
May 113.27 0.71 42.33 0.73 41.60 0.00 0.00
June 115.93 0.02 40.46 0.02 40.44 0.00 0.00
July 124.26 0.17 43.15 0.15 43.00 0.00 0.00
August 136.03 0.00 47.52 2.42 45.10 0.00 0.00
September 164.86 0.21 60.61 13.01 47.60 0.00 0.00
October 200.33 1.01 84.84 38.82 46.02 0.00 0.00
November 205.22 8.93 98.76 55.15 43.61 0.00 0.00
December 208.27 21.50 109.21 69.23 39.97 0.00 0.00
               
Annual Sum or Average 163.12 8.07 71.65 28.46 43.18 0.00 0.00
Minimum of Months 113.27 0.00 40.46 0.02 39.34 0.00 0.00
Maximum of Months 212.82 26.72 112.49 73.15 47.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 203.06 131.31 114.02 0.00 114.02 0.00 0.00
February 272.22 101.17 134.96 0.00 134.96 0.00 0.00
March 323.17 75.21 160.99 0.00 160.99 0.00 0.00
April 414.58 34.31 180.41 0.57 179.84 0.00 0.00
May 535.66 7.22 202.71 5.74 196.98 0.00 0.00
June 609.83 1.17 216.00 11.68 204.31 0.00 0.00
July 626.45 3.34 219.80 7.90 211.90 0.00 0.00
August 559.06 0.89 196.69 1.27 195.42 0.00 0.00
September 507.34 5.52 174.85 0.02 174.84 0.00 0.00
October 403.40 10.53 146.43 0.00 146.43 0.00 0.00
November 307.38 49.47 127.32 0.00 127.32 0.00 0.00
December 218.12 104.91 112.78 0.00 112.78 0.00 0.00
               
Annual Sum or Average 415.71 43.51 165.73 2.27 163.46 0.00 0.00
Minimum of Months 203.06 0.89 112.78 0.00 112.78 0.00 0.00
Maximum of Months 626.45 131.31 219.80 11.68 211.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 196.57 139.87 114.02 0.00 114.02 0.00 0.00
February 264.73 108.87 134.96 0.00 134.96 0.00 0.00
March 314.82 81.90 160.99 0.00 160.99 0.00 0.00
April 405.26 39.28 180.41 0.57 179.84 0.00 0.00
May 523.09 9.06 202.71 5.74 196.98 0.00 0.00
June 596.52 1.78 216.00 11.68 204.31 0.00 0.00
July 613.57 4.37 219.80 7.90 211.90 0.00 0.00
August 545.61 1.45 196.69 1.27 195.42 0.00 0.00
September 495.56 7.53 174.85 0.02 174.84 0.00 0.00
October 392.01 12.96 146.43 0.00 146.43 0.00 0.00
November 297.85 54.07 127.32 0.00 127.32 0.00 0.00
December 210.94 112.96 112.78 0.00 112.78 0.00 0.00
               
Annual Sum or Average 405.38 47.58 165.73 2.27 163.46 0.00 0.00
Minimum of Months 196.57 1.45 112.78 0.00 112.78 0.00 0.00
Maximum of Months 613.57 139.87 219.80 11.68 211.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 679.28 69.75 238.61 119.22 119.39 0.00 0.00
February 749.47 59.94 255.26 115.82 139.44 0.00 0.00
March 810.37 45.70 281.37 118.59 162.79 0.00 0.00
April 886.86 23.93 287.52 107.52 180.00 0.00 0.00
May 914.70 6.78 271.65 87.46 184.19 0.00 0.00
June 947.71 1.36 268.37 82.77 185.60 0.00 0.00
July 980.47 3.12 276.38 79.30 197.08 0.00 0.00
August 928.88 1.35 257.84 68.38 189.46 0.00 0.00
September 927.54 4.97 256.45 77.99 178.46 0.00 0.00
October 874.91 8.44 253.56 101.85 151.71 0.00 0.00
November 754.69 30.86 226.95 93.69 133.26 0.00 0.00
December 634.35 57.65 204.06 86.64 117.42 0.00 0.00
               
Annual Sum or Average 841.10 26.00 256.48 94.81 161.66 0.00 0.00
Minimum of Months 634.35 1.35 204.06 68.38 117.42 0.00 0.00
Maximum of Months 980.47 69.75 287.52 119.22 197.08 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 587.41 150.09 325.44 186.20 139.24 0.00 0.00
February 564.57 121.96 292.42 137.15 155.28 0.00 0.00
March 477.15 96.26 240.47 70.70 169.77 0.00 0.00
April 420.37 58.40 194.80 21.77 173.03 0.00 0.00
May 409.52 18.40 177.25 3.84 173.42 0.00 0.00
June 434.35 6.10 177.05 4.07 172.98 0.00 0.00
July 465.28 10.36 185.18 3.09 182.10 0.00 0.00
August 468.18 5.85 188.38 6.58 181.80 0.00 0.00
September 534.27 16.77 214.22 33.13 181.10 0.00 0.00
October 594.99 26.16 266.16 98.83 167.34 0.00 0.00
November 585.16 66.71 295.04 140.38 154.65 0.00 0.00
December 581.03 127.48 316.65 176.24 140.41 0.00 0.00
               
Annual Sum or Average 509.92 58.43 239.20 73.23 165.96 0.00 0.00
Minimum of Months 409.52 5.85 177.05 3.09 139.24 0.00 0.00
Maximum of Months 594.99 150.09 325.44 186.20 182.10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.194716E+10 0.320150E+09 0.103905E+10 0.675642E+09 0.363404E+09 0.00 0.00
February 0.161017E+10 0.239498E+09 0.806768E+09 0.449492E+09 0.357276E+09 0.00 0.00
March 0.140714E+10 0.214428E+09 0.672322E+09 0.256549E+09 0.415773E+09 0.00 0.00
April 0.105202E+10 0.133436E+09 0.466855E+09 75757544.16 0.391098E+09 0.00 0.00
May 0.895903E+09 52461088.17 0.391014E+09 6782770.30 0.384232E+09 0.00 0.00
June 0.860066E+09 17148924.33 0.361700E+09 214107.63 0.361486E+09 0.00 0.00
July 0.975283E+09 31360129.19 0.398545E+09 1382735.68 0.397163E+09 0.00 0.00
August 0.107678E+10 14540340.57 0.438907E+09 22310073.19 0.416597E+09 0.00 0.00
September 0.133121E+10 41481653.37 0.541765E+09 0.116300E+09 0.425465E+09 0.00 0.00
October 0.173617E+10 70967959.39 0.783645E+09 0.358602E+09 0.425043E+09 0.00 0.00
November 0.176397E+10 0.148960E+09 0.882765E+09 0.492959E+09 0.389806E+09 0.00 0.00
December 0.190242E+10 0.277823E+09 0.100871E+10 0.639488E+09 0.369220E+09 0.00 0.00
               
Annual Sum or Average 0.165583E+11 0.156225E+10 0.779204E+10 0.309548E+10 0.469656E+10 0.00 0.00
Minimum of Months 0.860066E+09 14540340.57 0.361700E+09 214107.63 0.357276E+09 0.00 0.00
Maximum of Months 0.194716E+10 0.320150E+09 0.103905E+10 0.675642E+09 0.425465E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.555457E+10 0.776809E+09 0.292589E+10 0.190256E+10 0.102332E+10 0.00 0.00
February 0.461824E+10 0.553206E+09 0.227181E+10 0.126574E+10 0.100607E+10 0.00 0.00
March 0.408732E+10 0.460553E+09 0.189321E+10 0.722424E+09 0.117079E+10 0.00 0.00
April 0.312170E+10 0.228738E+09 0.131463E+10 0.213328E+09 0.110131E+10 0.00 0.00
May 0.276603E+10 54265793.06 0.110107E+10 19099833.95 0.108197E+10 0.00 0.00
June 0.269434E+10 9399469.37 0.101852E+10 602912.96 0.101792E+10 0.00 0.00
July 0.300091E+10 28589734.61 0.112228E+10 3893692.52 0.111838E+10 0.00 0.00
August 0.330024E+10 7028601.41 0.123593E+10 62823695.11 0.117311E+10 0.00 0.00
September 0.394271E+10 54825871.05 0.152557E+10 0.327492E+09 0.119808E+10 0.00 0.00
October 0.504082E+10 0.107399E+09 0.220669E+10 0.100980E+10 0.119689E+10 0.00 0.00
November 0.508357E+10 0.315466E+09 0.248581E+10 0.138814E+10 0.109767E+10 0.00 0.00
December 0.542916E+10 0.649861E+09 0.284045E+10 0.180076E+10 0.103970E+10 0.00 0.00
               
Annual Sum or Average 0.486396E+11 0.324614E+10 0.219419E+11 0.871666E+10 0.132252E+11 0.00 0.00
Minimum of Months 0.269434E+10 7028601.41 0.101852E+10 602912.96 0.100607E+10 0.00 0.00
Maximum of Months 0.555457E+10 0.776809E+09 0.292589E+10 0.190256E+10 0.119808E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.725928E+10 0.110801E+10 0.380089E+10 0.247154E+10 0.132935E+10 0.00 0.00
February 0.602514E+10 0.802530E+09 0.295121E+10 0.164427E+10 0.130694E+10 0.00 0.00
March 0.530782E+10 0.690822E+09 0.245939E+10 0.938470E+09 0.152092E+10 0.00 0.00
April 0.401952E+10 0.388892E+09 0.170778E+10 0.277126E+09 0.143066E+10 0.00 0.00
May 0.348346E+10 0.125198E+09 0.143035E+10 24811771.28 0.140554E+10 0.00 0.00
June 0.337017E+10 36691948.93 0.132312E+10 783218.25 0.132234E+10 0.00 0.00
July 0.379118E+10 71653421.19 0.145790E+10 5058128.17 0.145284E+10 0.00 0.00
August 0.417783E+10 28452787.15 0.160555E+10 81611555.28 0.152394E+10 0.00 0.00
September 0.509436E+10 0.112185E+09 0.198181E+10 0.425431E+09 0.155638E+10 0.00 0.00
October 0.655422E+10 0.186806E+09 0.286662E+10 0.131179E+10 0.155483E+10 0.00 0.00
November 0.661763E+10 0.474795E+09 0.322921E+10 0.180327E+10 0.142593E+10 0.00 0.00
December 0.708650E+10 0.943687E+09 0.368991E+10 0.233928E+10 0.135063E+10 0.00 0.00
               
Annual Sum or Average 0.627871E+11 0.496972E+10 0.285037E+11 0.113234E+11 0.171803E+11 0.00 0.00
Minimum of Months 0.337017E+10 28452787.15 0.132312E+10 783218.25 0.130694E+10 0.00 0.00
Maximum of Months 0.725928E+10 0.110801E+10 0.380089E+10 0.247154E+10 0.155638E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.716068E+09 0.145785E+09 0.381299E+09 0.209140E+09 0.172159E+09 0.00 0.00
February 0.717227E+09 0.100860E+09 0.360060E+09 0.180326E+09 0.179734E+09 0.00 0.00
March 0.823311E+09 79660147.85 0.409126E+09 0.177768E+09 0.231358E+09 0.00 0.00
April 0.828095E+09 32753312.24 0.386616E+09 0.152396E+09 0.234220E+09 0.00 0.00
May 0.833071E+09 5416654.99 0.354116E+09 0.108821E+09 0.245295E+09 0.00 0.00
June 0.761347E+09 383209.95 0.297563E+09 63514995.53 0.234048E+09 0.00 0.00
July 0.864922E+09 1961945.78 0.339279E+09 80708085.81 0.258571E+09 0.00 0.00
August 0.876391E+09 106509.68 0.347146E+09 89311185.15 0.257835E+09 0.00 0.00
September 0.820888E+09 2853631.25 0.321952E+09 86413787.79 0.235539E+09 0.00 0.00
October 0.874425E+09 8234495.47 0.376167E+09 0.157393E+09 0.218774E+09 0.00 0.00
November 0.741839E+09 50435541.07 0.349730E+09 0.161118E+09 0.188612E+09 0.00 0.00
December 0.733017E+09 0.117471E+09 0.380589E+09 0.206734E+09 0.173854E+09 0.00 0.00
               
Annual Sum or Average 0.959060E+10 0.545922E+09 0.430364E+10 0.167364E+10 0.263000E+10 0.00 0.00
Minimum of Months 0.716068E+09 106509.68 0.297563E+09 63514995.53 0.172159E+09 0.00 0.00
Maximum of Months 0.876391E+09 0.145785E+09 0.409126E+09 0.209140E+09 0.258571E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.399494E+09 0.154242E+09 0.219489E+09 75554026.64 0.143935E+09 0.00 0.00
February 0.479554E+09 0.109556E+09 0.247191E+09 91453484.13 0.155738E+09 0.00 0.00
March 0.649129E+09 89457002.98 0.337798E+09 0.127044E+09 0.210754E+09 0.00 0.00
April 0.748027E+09 39833463.42 0.361116E+09 0.137629E+09 0.223487E+09 0.00 0.00
May 0.828733E+09 5771948.23 0.354372E+09 0.109675E+09 0.244697E+09 0.00 0.00
June 0.783334E+09 512608.46 0.306032E+09 67798878.90 0.238233E+09 0.00 0.00
July 0.877409E+09 2525581.43 0.344584E+09 83456668.32 0.261128E+09 0.00 0.00
August 0.843042E+09 199605.60 0.335628E+09 85386252.57 0.250242E+09 0.00 0.00
September 0.716060E+09 3763479.27 0.279584E+09 63425688.79 0.216158E+09 0.00 0.00
October 0.658795E+09 8472736.26 0.277258E+09 86491425.23 0.190766E+09 0.00 0.00
November 0.486857E+09 54206116.83 0.222340E+09 63651240.56 0.158688E+09 0.00 0.00
December 0.428623E+09 0.122414E+09 0.224303E+09 80296573.82 0.144007E+09 0.00 0.00
               
Annual Sum or Average 0.789906E+10 0.590955E+09 0.350969E+10 0.107186E+10 0.243783E+10 0.00 0.00
Minimum of Months 0.399494E+09 199605.60 0.219489E+09 63425688.79 0.143935E+09 0.00 0.00
Maximum of Months 0.877409E+09 0.154242E+09 0.361116E+09 0.137629E+09 0.261128E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.290775E+09 75625327.00 0.164318E+09 0.106848E+09 57469935.70 0.00 0.00
February 0.238494E+09 57635898.94 0.127585E+09 71083695.03 56500928.45 0.00 0.00
March 0.204516E+09 53408627.32 0.106323E+09 40571176.48 65751932.95 0.00 0.00
April 0.151462E+09 36058477.21 73830230.13 11980471.49 61849758.64 0.00 0.00
May 0.126911E+09 20050434.14 61836618.86 1072642.83 60763976.04 0.00 0.00
June 0.119292E+09 10211928.97 57200746.85 33859.47 57166887.38 0.00 0.00
July 0.139575E+09 13959230.15 63027610.18 218668.99 62808941.19 0.00 0.00
August 0.153320E+09 11374291.64 69410491.77 3528166.06 65882325.72 0.00 0.00
September 0.194463E+09 15197443.35 85676490.20 18391879.71 67284610.49 0.00 0.00
October 0.260508E+09 24877785.37 0.123928E+09 56710180.87 67217763.04 0.00 0.00
November 0.263973E+09 40728373.56 0.139603E+09 77957672.78 61645284.13 0.00 0.00
December 0.284634E+09 68154255.13 0.159520E+09 0.101130E+09 58389607.23 0.00 0.00
               
Annual Sum or Average 0.242792E+10 0.427282E+09 0.123226E+10 0.489526E+09 0.742732E+09 0.00 0.00
Minimum of Months 0.119292E+09 10211928.97 57200746.85 33859.47 56500928.45 0.00 0.00
Maximum of Months 0.290775E+09 75625327.00 0.164318E+09 0.106848E+09 67284610.49 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 59481068.25 41195084.34 34907432.38 0.00 34907432.38 0.00 0.00
February 72691491.37 28243779.43 37319963.98 0.00 37319963.98 0.00 0.00
March 96083668.18 21879780.14 49288411.47 217.63 49288193.84 0.00 0.00
April 0.120961E+09 8164530.83 53451822.62 169189.60 53282633.02 0.00 0.00
May 0.168073E+09 1146473.68 62062150.71 1756331.83 60305818.89 0.00 0.00
June 0.186935E+09 38168.22 63995444.36 3461431.67 60534012.68 0.00 0.00
July 0.197459E+09 368597.64 67293054.78 2417898.95 64875155.83 0.00 0.00
August 0.177307E+09 8764.48 60217444.71 388973.21 59828471.50 0.00 0.00
September 0.154377E+09 464450.66 51805514.90 5058.83 51800456.07 0.00 0.00
October 0.125462E+09 1420967.20 44831184.01 0.00 44831184.01 0.00 0.00
November 90507975.57 13524120.22 37723496.33 0.00 37723496.33 0.00 0.00
December 64366100.60 32326469.11 34527798.01 0.00 34527798.01 0.00 0.00
               
Annual Sum or Average 0.151370E+10 0.148781E+09 0.597424E+09 8199101.71 0.589225E+09 0.00 0.00
Minimum of Months 59481068.25 8764.48 34527798.01 0.00 34527798.01 0.00 0.00
Maximum of Months 0.197459E+09 41195084.34 67293054.78 3461431.67 64875155.83 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.752058E+09 0.143931E+09 0.400464E+09 0.226462E+09 0.174003E+09 0.00 0.00
February 0.723427E+09 97355175.74 0.365207E+09 0.184537E+09 0.180670E+09 0.00 0.00
March 0.819923E+09 74232405.45 0.412498E+09 0.184181E+09 0.228317E+09 0.00 0.00
April 0.827275E+09 30886004.44 0.385400E+09 0.146744E+09 0.238656E+09 0.00 0.00
May 0.851790E+09 5094852.95 0.363684E+09 0.116709E+09 0.246975E+09 0.00 0.00
June 0.850395E+09 424552.96 0.343598E+09 0.105142E+09 0.238456E+09 0.00 0.00
July 0.920432E+09 1892164.67 0.367498E+09 0.104832E+09 0.262666E+09 0.00 0.00
August 0.884125E+09 84960.39 0.351075E+09 93536694.77 0.257538E+09 0.00 0.00
September 0.882825E+09 2795195.91 0.353557E+09 0.112573E+09 0.240985E+09 0.00 0.00
October 0.899470E+09 7943664.28 0.389041E+09 0.171857E+09 0.217185E+09 0.00 0.00
November 0.755797E+09 49131907.06 0.357836E+09 0.170160E+09 0.187677E+09 0.00 0.00
December 0.674753E+09 0.115032E+09 0.351434E+09 0.179249E+09 0.172185E+09 0.00 0.00
               
Annual Sum or Average 0.984227E+10 0.528804E+09 0.444129E+10 0.179598E+10 0.264531E+10 0.00 0.00
Minimum of Months 0.674753E+09 84960.39 0.343598E+09 93536694.77 0.172185E+09 0.00 0.00
Maximum of Months 0.920432E+09 0.143931E+09 0.412498E+09 0.226462E+09 0.262666E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.430625E+09 0.148491E+09 0.238655E+09 92875897.09 0.145779E+09 0.00 0.00
February 0.481615E+09 0.102968E+09 0.252339E+09 95665196.11 0.156673E+09 0.00 0.00
March 0.643327E+09 81423482.46 0.341170E+09 0.133458E+09 0.207713E+09 0.00 0.00
April 0.745889E+09 37475070.57 0.359899E+09 0.131977E+09 0.227923E+09 0.00 0.00
May 0.847037E+09 5509602.45 0.363940E+09 0.117563E+09 0.246377E+09 0.00 0.00
June 0.872237E+09 563444.85 0.352066E+09 0.109425E+09 0.242641E+09 0.00 0.00
July 0.932865E+09 2544667.64 0.372803E+09 0.107581E+09 0.265223E+09 0.00 0.00
August 0.850761E+09 174629.22 0.339556E+09 89611762.19 0.249945E+09 0.00 0.00
September 0.777593E+09 3703141.14 0.311189E+09 89584600.22 0.221604E+09 0.00 0.00
October 0.683018E+09 8131215.12 0.290132E+09 0.100955E+09 0.189177E+09 0.00 0.00
November 0.497837E+09 51255204.87 0.230446E+09 72693177.46 0.157753E+09 0.00 0.00
December 0.369431E+09 0.118002E+09 0.195149E+09 52811336.97 0.142337E+09 0.00 0.00
               
Annual Sum or Average 0.813224E+10 0.560242E+09 0.364735E+10 0.119420E+10 0.245314E+10 0.00 0.00
Minimum of Months 0.369431E+09 174629.22 0.195149E+09 52811336.97 0.142337E+09 0.00 0.00
Maximum of Months 0.932865E+09 0.148491E+09 0.372803E+09 0.133458E+09 0.265223E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.795833E+09 0.199931E+09 0.431652E+09 0.231509E+09 0.200143E+09 0.00 0.00
February 0.712637E+09 0.140039E+09 0.357288E+09 0.154019E+09 0.203269E+09 0.00 0.00
March 0.693627E+09 0.118785E+09 0.337148E+09 87906928.41 0.249241E+09 0.00 0.00
April 0.622719E+09 63643581.28 0.275764E+09 26324871.48 0.249439E+09 0.00 0.00
May 0.661895E+09 15824127.39 0.268430E+09 6128922.38 0.262301E+09 0.00 0.00
June 0.682424E+09 4809261.78 0.262574E+09 7571985.75 0.255002E+09 0.00 0.00
July 0.741576E+09 10893378.33 0.282343E+09 5711774.78 0.276631E+09 0.00 0.00
August 0.733261E+09 4063017.29 0.280844E+09 8487201.09 0.272357E+09 0.00 0.00
September 0.772669E+09 18543744.54 0.297865E+09 39861047.85 0.258004E+09 0.00 0.00
October 0.847590E+09 30441540.67 0.365637E+09 0.122875E+09 0.242762E+09 0.00 0.00
November 0.792200E+09 83095128.07 0.384203E+09 0.168913E+09 0.215290E+09 0.00 0.00
December 0.790982E+09 0.167118E+09 0.420434E+09 0.219121E+09 0.201313E+09 0.00 0.00
               
Annual Sum or Average 0.884741E+10 0.857186E+09 0.396418E+10 0.107843E+10 0.288575E+10 0.00 0.00
Minimum of Months 0.622719E+09 4063017.29 0.262574E+09 5711774.78 0.200143E+09 0.00 0.00
Maximum of Months 0.847590E+09 0.199931E+09 0.431652E+09 0.231509E+09 0.276631E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.712019E+09 0.138950E+09 0.381299E+09 0.209140E+09 0.172159E+09 0.00 0.00
February 0.712650E+09 95773290.67 0.360060E+09 0.180326E+09 0.179734E+09 0.00 0.00
March 0.817570E+09 74333395.25 0.409126E+09 0.177768E+09 0.231358E+09 0.00 0.00
April 0.822454E+09 28545254.92 0.386616E+09 0.152396E+09 0.234220E+09 0.00 0.00
May 0.830416E+09 4390672.21 0.354116E+09 0.108821E+09 0.245295E+09 0.00 0.00
June 0.759780E+09 179716.01 0.297563E+09 63514995.53 0.234048E+09 0.00 0.00
July 0.862617E+09 1295658.09 0.339279E+09 80708085.81 0.258571E+09 0.00 0.00
August 0.874748E+09 28801.62 0.347146E+09 89311185.15 0.257835E+09 0.00 0.00
September 0.818686E+09 1557455.14 0.321952E+09 86413787.79 0.235539E+09 0.00 0.00
October 0.872834E+09 5970034.34 0.376167E+09 0.157393E+09 0.218774E+09 0.00 0.00
November 0.738985E+09 45842619.38 0.349730E+09 0.161118E+09 0.188612E+09 0.00 0.00
December 0.728670E+09 0.111419E+09 0.380589E+09 0.206734E+09 0.173854E+09 0.00 0.00
               
Annual Sum or Average 0.955143E+10 0.508286E+09 0.430364E+10 0.167364E+10 0.263000E+10 0.00 0.00
Minimum of Months 0.712019E+09 28801.62 0.297563E+09 63514995.53 0.172159E+09 0.00 0.00
Maximum of Months 0.874748E+09 0.138950E+09 0.409126E+09 0.209140E+09 0.258571E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.398382E+09 0.148577E+09 0.219489E+09 75554026.64 0.143935E+09 0.00 0.00
February 0.477153E+09 0.106615E+09 0.247191E+09 91453484.13 0.155738E+09 0.00 0.00
March 0.644387E+09 86706311.37 0.337798E+09 0.127044E+09 0.210754E+09 0.00 0.00
April 0.743006E+09 37228194.43 0.361116E+09 0.137629E+09 0.223487E+09 0.00 0.00
May 0.825868E+09 4833376.09 0.354372E+09 0.109675E+09 0.244697E+09 0.00 0.00
June 0.781346E+09 364980.81 0.306032E+09 67798878.90 0.238233E+09 0.00 0.00
July 0.874864E+09 2097352.32 0.344584E+09 83456668.32 0.261128E+09 0.00 0.00
August 0.841481E+09 124396.17 0.335628E+09 85386252.57 0.250242E+09 0.00 0.00
September 0.714736E+09 2581079.25 0.279584E+09 63425688.79 0.216158E+09 0.00 0.00
October 0.658904E+09 6076477.10 0.277258E+09 86491425.23 0.190766E+09 0.00 0.00
November 0.486408E+09 49914624.97 0.222340E+09 63651240.56 0.158688E+09 0.00 0.00
December 0.427445E+09 0.117294E+09 0.224303E+09 80296573.82 0.144007E+09 0.00 0.00
               
Annual Sum or Average 0.787398E+10 0.562413E+09 0.350969E+10 0.107186E+10 0.243783E+10 0.00 0.00
Minimum of Months 0.398382E+09 124396.17 0.219489E+09 63425688.79 0.143935E+09 0.00 0.00
Maximum of Months 0.874864E+09 0.148577E+09 0.361116E+09 0.137629E+09 0.261128E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.570012E+09 71563292.36 0.301294E+09 0.195917E+09 0.105377E+09 0.00 0.00
February 0.474581E+09 47935869.95 0.233940E+09 0.130340E+09 0.103601E+09 0.00 0.00
March 0.419474E+09 35982393.36 0.194955E+09 74391696.48 0.120563E+09 0.00 0.00
April 0.325490E+09 12516469.14 0.135376E+09 21967506.89 0.113408E+09 0.00 0.00
May 0.303374E+09 1904763.14 0.113384E+09 1966808.12 0.111417E+09 0.00 0.00
June 0.300498E+09 57737.23 0.104884E+09 62085.05 0.104822E+09 0.00 0.00
July 0.332820E+09 460709.37 0.115568E+09 400953.54 0.115167E+09 0.00 0.00
August 0.364344E+09 4255.97 0.127272E+09 6469278.96 0.120802E+09 0.00 0.00
September 0.427313E+09 544743.21 0.157097E+09 33723526.21 0.123374E+09 0.00 0.00
October 0.536556E+09 2712512.78 0.227235E+09 0.103984E+09 0.123251E+09 0.00 0.00
November 0.531919E+09 23157634.28 0.255977E+09 0.142944E+09 0.113033E+09 0.00 0.00
December 0.557825E+09 57585325.05 0.292497E+09 0.185433E+09 0.107064E+09 0.00 0.00
               
Annual Sum or Average 0.514421E+10 0.254426E+09 0.225948E+10 0.897600E+09 0.136188E+10 0.00 0.00
Minimum of Months 0.300498E+09 4255.97 0.104884E+09 62085.05 0.103601E+09 0.00 0.00
Maximum of Months 0.570012E+09 71563292.36 0.301294E+09 0.195917E+09 0.123374E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.543875E+09 0.351690E+09 0.305388E+09 0.00 0.305388E+09 0.00 0.00
February 0.658564E+09 0.244748E+09 0.326494E+09 0.00 0.326494E+09 0.00 0.00
March 0.865579E+09 0.201453E+09 0.431200E+09 1903.90 0.431198E+09 0.00 0.00
April 0.107460E+10 88921749.19 0.467624E+09 1480156.76 0.466144E+09 0.00 0.00
May 0.143471E+10 19348658.39 0.542951E+09 15365284.69 0.527586E+09 0.00 0.00
June 0.158068E+10 3042876.67 0.559865E+09 30282365.96 0.529582E+09 0.00 0.00
July 0.167789E+10 8934455.00 0.588714E+09 21153010.59 0.567561E+09 0.00 0.00
August 0.149738E+10 2377210.30 0.526813E+09 3402935.57 0.523410E+09 0.00 0.00
September 0.131503E+10 14297133.42 0.453221E+09 44257.23 0.453177E+09 0.00 0.00
October 0.108047E+10 28192726.45 0.392206E+09 0.00 0.392206E+09 0.00 0.00
November 0.796731E+09 0.128225E+09 0.330024E+09 0.00 0.330024E+09 0.00 0.00
December 0.584220E+09 0.281000E+09 0.302067E+09 0.00 0.302067E+09 0.00 0.00
               
Annual Sum or Average 0.131097E+11 0.137223E+10 0.522657E+10 71729914.70 0.515484E+10 0.00 0.00
Minimum of Months 0.543875E+09 2377210.30 0.302067E+09 0.00 0.302067E+09 0.00 0.00
Maximum of Months 0.167789E+10 0.351690E+09 0.588714E+09 30282365.96 0.567561E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.526491E+09 0.374622E+09 0.305388E+09 0.00 0.305388E+09 0.00 0.00
February 0.640434E+09 0.263379E+09 0.326494E+09 0.00 0.326494E+09 0.00 0.00
March 0.843219E+09 0.219368E+09 0.431200E+09 1903.90 0.431198E+09 0.00 0.00
April 0.105043E+10 0.101806E+09 0.467624E+09 1480156.76 0.466144E+09 0.00 0.00
May 0.140105E+10 24275514.36 0.542951E+09 15365284.69 0.527586E+09 0.00 0.00
June 0.154618E+10 4603469.45 0.559865E+09 30282365.96 0.529582E+09 0.00 0.00
July 0.164339E+10 11694203.15 0.588714E+09 21153010.59 0.567561E+09 0.00 0.00
August 0.146135E+10 3895052.25 0.526813E+09 3402935.57 0.523410E+09 0.00 0.00
September 0.128449E+10 19511097.88 0.453221E+09 44257.23 0.453177E+09 0.00 0.00
October 0.104996E+10 34714222.97 0.392206E+09 0.00 0.392206E+09 0.00 0.00
November 0.772028E+09 0.140139E+09 0.330024E+09 0.00 0.330024E+09 0.00 0.00
December 0.564978E+09 0.302559E+09 0.302067E+09 0.00 0.302067E+09 0.00 0.00
               
Annual Sum or Average 0.127840E+11 0.150057E+10 0.522657E+10 71729914.70 0.515484E+10 0.00 0.00
Minimum of Months 0.526491E+09 3895052.25 0.302067E+09 0.00 0.302067E+09 0.00 0.00
Maximum of Months 0.164339E+10 0.374622E+09 0.588714E+09 30282365.96 0.567561E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.181938E+10 0.186810E+09 0.639092E+09 0.319325E+09 0.319767E+09 0.00 0.00
February 0.181311E+10 0.145004E+09 0.617517E+09 0.280189E+09 0.337327E+09 0.00 0.00
March 0.217049E+10 0.122416E+09 0.753629E+09 0.317620E+09 0.436009E+09 0.00 0.00
April 0.229874E+10 62018259.24 0.745257E+09 0.278702E+09 0.466555E+09 0.00 0.00
May 0.244992E+10 18148086.48 0.727584E+09 0.234256E+09 0.493328E+09 0.00 0.00
June 0.245647E+10 3535068.91 0.695625E+09 0.214552E+09 0.481073E+09 0.00 0.00
July 0.262609E+10 8364551.95 0.740261E+09 0.212398E+09 0.527863E+09 0.00 0.00
August 0.248790E+10 3615897.34 0.690594E+09 0.183136E+09 0.507458E+09 0.00 0.00
September 0.240418E+10 12874719.28 0.664711E+09 0.202145E+09 0.462566E+09 0.00 0.00
October 0.234335E+10 22608931.39 0.679140E+09 0.272797E+09 0.406343E+09 0.00 0.00
November 0.195615E+10 80001210.61 0.588256E+09 0.242843E+09 0.345414E+09 0.00 0.00
December 0.169903E+10 0.154422E+09 0.546561E+09 0.232053E+09 0.314508E+09 0.00 0.00
               
Annual Sum or Average 0.265248E+11 0.819819E+09 0.808823E+10 0.299001E+10 0.509821E+10 0.00 0.00
Minimum of Months 0.169903E+10 3535068.91 0.546561E+09 0.183136E+09 0.314508E+09 0.00 0.00
Maximum of Months 0.262609E+10 0.186810E+09 0.753629E+09 0.319325E+09 0.527863E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.157331E+10 0.401994E+09 0.871648E+09 0.498717E+09 0.372931E+09 0.00 0.00
February 0.136580E+10 0.295050E+09 0.707430E+09 0.331787E+09 0.375644E+09 0.00 0.00
March 0.127799E+10 0.257819E+09 0.644085E+09 0.189369E+09 0.454716E+09 0.00 0.00
April 0.108960E+10 0.151365E+09 0.504909E+09 56426856.89 0.448482E+09 0.00 0.00
May 0.109686E+10 49277584.98 0.474750E+09 10273864.23 0.464476E+09 0.00 0.00
June 0.112583E+10 15816228.10 0.458910E+09 10538895.02 0.448371E+09 0.00 0.00
July 0.124621E+10 27750713.12 0.495997E+09 8271941.92 0.487725E+09 0.00 0.00
August 0.125396E+10 15665996.62 0.504569E+09 17634426.37 0.486935E+09 0.00 0.00
September 0.138482E+10 43465719.07 0.555264E+09 85860199.68 0.469404E+09 0.00 0.00
October 0.159363E+10 70053814.56 0.712889E+09 0.264698E+09 0.448191E+09 0.00 0.00
November 0.151674E+10 0.172925E+09 0.764737E+09 0.363871E+09 0.400865E+09 0.00 0.00
December 0.155622E+10 0.341430E+09 0.848115E+09 0.472030E+09 0.376086E+09 0.00 0.00
               
Annual Sum or Average 0.160810E+11 0.184261E+10 0.754330E+10 0.230948E+10 0.523383E+10 0.00 0.00
Minimum of Months 0.108960E+10 15665996.62 0.458910E+09 8271941.92 0.372931E+09 0.00 0.00
Maximum of Months 0.159363E+10 0.401994E+09 0.871648E+09 0.498717E+09 0.487725E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 19.42 15.96 13.59 3.30 9.49 57.21 169.93 0.03
February 20.87 16.70 13.89 5.53 11.19 68.99 182.59 0.00
March 21.57 17.63 15.09 5.59 12.13 85.97 199.13 0.00
April 24.11 19.68 17.40 4.69 15.31 97.05 212.67 0.01
May 26.41 22.40 20.67 5.05 18.50 110.67 177.92 0.00
June 27.68 24.06 22.67 3.87 20.33 120.35 147.07 0.00
July 28.13 24.25 22.77 2.86 20.30 124.71 163.26 0.00
August 27.97 24.38 23.03 3.45 20.36 120.27 145.14 0.08
September 27.49 23.91 22.56 3.39 20.13 107.67 134.94 0.00
October 26.35 22.68 21.10 3.72 17.49 81.44 160.40 0.04
November 23.59 20.24 18.46 4.39 14.74 70.67 140.11 0.00
December 20.30 17.47 15.75 3.70 12.21 59.50 147.31 0.00
                 
Annual Sum or Average 24.51 20.80 18.94 4.12 16.04 92.16 164.97 0.01
Minimum of Months 19.42 15.96 13.59 2.86 9.49 57.21 134.94 0.00
Maximum of Months 28.13 24.38 23.03 5.59 20.36 124.71 212.67 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 28.90 02-JAN-14:20 24.35 22.57 2.37 19.46 142.33 666.50
February 29.40 11-FEB-13:00 24.15 22.20 4.60 20.75 178.50 682.00
March 29.40 13-MAR-15:00 22.41 19.40 6.20 21.27 178.00 499.00
April 32.20 17-APR-14:00 19.76 12.80 5.20 21.27 367.00 219.50
May 34.40 22-MAY-12:00 23.24 18.30 5.70 25.99 382.50 457.50
June 32.20 11-JUN-12:00 23.83 20.60 3.60 23.15 181.50 762.50
July 35.60 29-JUL-15:00 24.39 20.00 3.60 25.66 281.50 374.50
August 33.90 23-AUG-12:00 25.44 22.20 5.70 24.50 261.50 640.00
September 32.20 08-SEP-14:00 23.42 20.00 2.10 21.61 221.50 576.00
October 32.20 09-OCT-10:00 23.83 20.60 3.10 25.16 286.50 457.50
November 30.00 17-NOV-14:00 22.20 18.90 4.10 19.35 178.50 412.50
December 28.90 10-DEC-14:20 22.91 20.40 7.87 19.82 162.67 585.17
                 
Annual Sum or Average                
Minimum of Months 28.90   19.76 12.80 2.10 19.35 142.33 219.50
Maximum of Months 35.60   25.44 22.57 7.87 25.99 382.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 25-JAN-04:00 4.59 -1.7 3.10 -7.3 0.00 0.00
February 5.00 04-FEB-06:00 1.99 -2.8 5.70 -11.9 0.00 0.00
March 6.70 16-MAR-04:00 4.49 1.70 4.60 -9.2 0.00 0.00
April 14.40 02-APR-05:49 13.38 12.70 1.60 0.69 0.00 0.00
May 20.60 01-MAY-04:00 19.45 18.90 1.00 7.95 0.00 0.00
June 22.80 05-JUN-14:00 20.57 19.40 2.10 18.46 245.00 55.00
July 22.80 02-JUL-15:00 21.59 21.10 4.60 20.92 155.00 8.50
August 22.20 12-AUG-06:00 21.85 21.70 2.60 20.40 65.50 0.00
September 22.20 05-SEP-05:00 21.37 21.10 2.60 13.54 0.00 0.00
October 21.10 28-OCT-02:00 20.29 20.00 2.60 8.54 0.00 0.00
November 10.00 27-NOV-02:00 8.82 7.80 3.10 -4.6 0.00 0.00
December 7.80 15-DEC-05:40 5.61 3.13 6.37 -7.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 5.00   1.99 -2.8 1.00 -11.9 0.00 0.00
Maximum of Months 22.80   21.85 21.70 6.37 20.92 245.00 55.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.83 02-JAN-13:00 28.90 23.30 1.50 19.87 151.00 613.50
February 24.15 11-FEB-13:00 29.40 22.20 4.60 20.75 178.50 682.00
March 23.83 14-MAR-09:00 26.70 22.80 11.30 19.52 243.50 478.00
April 24.58 01-APR-15:00 28.30 23.30 3.60 16.30 93.50 759.50
May 26.05 28-MAY-14:00 28.90 25.00 5.20 25.66 289.00 98.50
June 26.06 28-JUN-11:00 28.90 25.00 1.50 22.98 404.50 373.50
July 26.39 12-JUL-10:00 30.60 25.00 4.60 23.82 287.50 574.00
August 26.46 21-AUG-15:00 32.20 24.40 3.60 24.50 205.50 366.00
September 26.31 22-SEP-16:00 30.00 25.00 6.20 28.91 54.00 21.00
October 26.52 01-OCT-11:00 29.40 25.60 6.20 28.43 283.50 0.00
November 25.31 04-NOV-13:00 27.80 24.40 2.10 26.48 199.00 3.00
December 24.31 24-DEC-14:00 27.20 23.30 2.10 23.66 201.50 114.50
                 
Annual Sum or Average                
Minimum of Months 23.83   26.70 22.20 1.50 16.30 54.00 0.00
Maximum of Months 26.52   32.20 25.60 11.30 28.91 404.50 759.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.30 02-JAN-13:00 28.90 24.83 1.50 19.87 151.00 613.50
February 22.80 11-FEB-16:19 27.60 24.09 5.70 18.94 101.33 565.33
March 22.80 14-MAR-09:20 25.57 23.60 9.63 22.18 176.17 527.17
April 23.30 01-APR-14:00 27.80 24.57 5.70 15.76 108.00 831.00
May 25.00 28-MAY-12:00 27.80 25.74 6.70 22.98 249.50 244.50
June 25.00 06-JUN-18:00 27.20 25.59 3.60 23.99 17.50 0.00
July 25.00 12-JUL-03:00 27.20 25.59 1.50 19.70 0.00 0.00
August 25.60 21-AUG-11:00 28.90 26.35 2.60 23.15 567.00 173.50
September 25.00 22-SEP-00:00 27.80 25.31 3.60 20.92 0.00 0.00
October 25.60 01-OCT-11:00 29.40 26.52 6.20 28.43 283.50 0.00
November 24.40 05-NOV-01:19 26.10 24.93 2.03 16.37 0.00 0.00
December 23.90 24-DEC-08:00 23.90 23.90 2.60 17.75 168.50 167.00
                 
Annual Sum or Average                
Minimum of Months 22.80   23.90 23.60 1.50 15.76 0.00 0.00
Maximum of Months 25.60   29.40 26.52 9.63 28.43 567.00 831.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 24.73 28.77 0.00
February 18.00 13.00 16.00 25.06 35.04 0.00
March 18.00 13.00 16.00 26.11 42.49 0.00
April 18.00 13.00 16.00 27.63 49.05 0.00
May 18.00 13.00 16.00 29.20 48.15 0.00
June 18.00 13.00 16.00 30.41 45.99 0.00
July 18.00 13.00 16.00 30.92 49.88 0.00
August 18.00 13.00 16.00 30.58 45.60 0.00
September 18.00 13.00 16.00 29.50 40.49 0.00
October 18.00 13.00 16.00 27.97 35.89 0.00
November 18.00 13.00 16.00 26.40 29.31 0.00
December 18.00 13.00 16.00 25.21 26.63 0.00
             
Annual Sum or Average 18.00 13.00 16.00 27.83 39.80 0.00
Minimum of Months 18.00 13.00 16.00 24.73 26.63 0.00
Maximum of Months 18.00 13.00 16.00 30.92 49.88 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770419E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -161411507.9 81.21 0.00 0.00
February 0.696176E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -145791176.3 81.21 0.00 0.00
March 0.770288E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161411756.3 81.21 0.00 0.00
April 0.746480E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156204686.9 81.21 0.00 0.00
May 0.770420E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161411660.1 81.21 0.00 0.00
June 0.745674E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156204587.3 81.21 0.00 0.00
July 0.771226E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161410942.9 81.21 0.00 0.00
August 0.770422E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -161411250.4 81.21 0.00 0.00
September 0.746614E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -156204030.7 81.21 0.00 0.00
October 0.770285E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161411270.3 81.21 0.00 0.00
November 0.744862E+10 -0.729242E+10 0.00 0.00 720.00 0.00 -156204386.2 81.21 0.00 0.00
December 0.771227E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -161411467.4 81.21 0.00 0.00
                     
Annual Sum or Average 0.907409E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190049E+10 81.21 0.00 0.00
Minimum of Months 0.696176E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -161411756.3 81.21 0.00 0.00
Maximum of Months 0.771227E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -145791176.3 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.973982E+11 -0.956669E+11 0.00 0.00 744.00 0.00 -0.173127E+10 81.25 0.00 0.00
February 0.874642E+11 -0.858973E+11 0.00 0.00 672.00 0.00 -0.156689E+10 81.25 0.00 0.00
March 0.950733E+11 -0.933322E+11 0.00 0.00 744.00 0.00 -0.174103E+10 81.24 0.00 0.00
April 0.895075E+11 -0.878243E+11 0.00 0.00 720.00 0.00 -0.168325E+10 81.24 0.00 0.00
May 0.898159E+11 -0.880812E+11 0.00 0.00 744.00 0.00 -0.173472E+10 81.25 0.00 0.00
June 0.849365E+11 -0.832612E+11 0.00 0.00 720.00 0.00 -0.167531E+10 81.24 0.00 0.00
July 0.869076E+11 -0.851790E+11 0.00 0.00 744.00 0.00 -0.172861E+10 81.23 0.00 0.00
August 0.874738E+11 -0.857460E+11 0.00 0.00 744.00 0.00 -0.172780E+10 81.24 0.00 0.00
September 0.864200E+11 -0.847488E+11 0.00 0.00 720.00 0.00 -0.167124E+10 81.24 0.00 0.00
October 0.918971E+11 -0.901705E+11 0.00 0.00 744.00 0.00 -0.172661E+10 81.24 0.00 0.00
November 0.915106E+11 -0.898391E+11 0.00 0.00 720.00 0.00 -0.167146E+10 81.24 0.00 0.00
December 0.965746E+11 -0.948452E+11 0.00 0.00 744.00 0.00 -0.172939E+10 81.24 0.00 0.00
                     
Annual Sum or Average 0.108498E+13 -0.106459E+13 0.00 0.00 8760.00 0.00 -0.203876E+11 81.24 0.00 0.00
Minimum of Months 0.849365E+11 -0.956669E+11 0.00 0.00 672.00 0.00 -0.174103E+10 81.23 0.00 0.00
Maximum of Months 0.973982E+11 -0.832612E+11 0.00 0.00 744.00 0.00 -0.156689E+10 81.25 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.515047E+11 -0.500354E+11 0.00 0.00 744.00 0.00 -0.146932E+10 58.98 0.00 0.00
February 0.460912E+11 -0.447596E+11 0.00 0.00 672.00 0.00 -0.133164E+10 58.98 0.00 0.00
March 0.495475E+11 -0.480644E+11 0.00 0.00 744.00 0.00 -0.148304E+10 58.98 0.00 0.00
April 0.457646E+11 -0.443316E+11 0.00 0.00 720.00 0.00 -0.143293E+10 58.98 0.00 0.00
May 0.449835E+11 -0.435094E+11 0.00 0.00 744.00 0.00 -0.147416E+10 58.98 0.00 0.00
June 0.418347E+11 -0.404127E+11 0.00 0.00 720.00 0.00 -0.142204E+10 58.97 0.00 0.00
July 0.424443E+11 -0.409780E+11 0.00 0.00 744.00 0.00 -0.146636E+10 58.97 0.00 0.00
August 0.429767E+11 -0.415118E+11 0.00 0.00 744.00 0.00 -0.146482E+10 58.97 0.00 0.00
September 0.430946E+11 -0.416782E+11 0.00 0.00 720.00 0.00 -0.141641E+10 58.98 0.00 0.00
October 0.467518E+11 -0.452884E+11 0.00 0.00 744.00 0.00 -0.146341E+10 58.98 0.00 0.00
November 0.474690E+11 -0.460521E+11 0.00 0.00 720.00 0.00 -0.141695E+10 58.98 0.00 0.00
December 0.507892E+11 -0.493221E+11 0.00 0.00 744.00 0.00 -0.146705E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.553252E+12 -0.535944E+12 0.00 0.00 8760.00 0.00 -0.173081E+11 58.98 0.00 0.00
Minimum of Months 0.418347E+11 -0.500354E+11 0.00 0.00 672.00 0.00 -0.148304E+10 58.97 0.00 0.00
Maximum of Months 0.515047E+11 -0.404127E+11 0.00 0.00 744.00 0.00 -0.133164E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.87 0.86 01-JAN-07:40 5863.24 35.56 267.50 294.83 711.26 25.26 204.67 270.67
February 304.33 0.87 0.86 01-FEB-07:00 1736.83 24.38 113.83 283.50 521.91 21.11 140.17 244.83
March 362.67 0.87 0.86 01-MAR-08:30 1090.32 18.60 0.00 333.00 433.02 20.84 150.17 272.67
April 357.50 0.87 0.86 01-APR-07:30 887.27 18.36 0.00 333.67 363.40 20.59 113.33 265.33
May 389.00 0.87 0.86 01-MAY-07:19 773.03 17.62 0.00 351.50 314.16 19.86 68.00 253.50
June 388.17 0.88 0.86 01-JUN-07:19 728.27 16.90 0.00 328.67 292.70 19.19 49.00 232.33
July 403.83 0.87 0.86 01-JUL-06:00 818.85 17.72 0.00 361.00 332.96 19.98 103.50 275.33
August 348.33 0.87 0.86 01-AUG-07:40 971.76 18.12 0.00 347.00 387.95 20.33 145.50 284.50
September 349.67 0.87 0.86 01-SEP-07:19 1192.02 18.35 0.00 319.67 461.16 20.53 175.17 266.83
October 323.50 0.87 0.86 02-OCT-08:09 1509.31 20.67 40.33 317.50 555.74 21.43 200.67 277.67
November 314.83 0.87 0.86 01-NOV-07:10 3503.84 30.90 237.83 295.33 630.74 23.71 216.83 267.00
December 282.67 0.86 0.86 01-DEC-08:39 6080.88 36.39 278.67 284.33 744.14 24.87 198.17 258.17
                         
Annual Sum or Average 4111.50 0.87     1922.31 22.12 938.17 3850.00 463.41 21.29 1765.17 3168.83
Minimum of Months 282.67 0.86 0.86   728.27 16.90 0.00 283.50 292.70 19.19 49.00 232.33
Maximum of Months 403.83 0.88 0.86   6080.88 36.39 278.67 361.00 744.14 25.26 216.83 284.50



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.25 0.22 01-JAN-07:40 6203.68 35.59 267.67 300.33 1049.32 25.16 198.17 289.67
February 304.33 0.25 0.22 01-FEB-07:49 2002.96 24.55 114.67 291.33 787.35 21.47 155.17 268.67
March 362.67 0.25 0.22 01-MAR-07:40 1289.77 19.38 0.17 344.50 631.36 21.38 198.67 312.17
April 357.50 0.25 0.22 01-APR-07:10 1038.27 19.34 0.00 344.00 513.83 21.30 207.50 316.17
May 389.00 0.26 0.22 01-MAY-06:49 894.55 18.75 0.00 369.50 435.15 20.71 175.67 327.33
June 388.17 0.28 0.22 01-JUN-06:49 841.40 18.10 0.00 349.33 405.33 20.10 147.83 301.17
July 403.83 0.26 0.22 01-JUL-06:40 944.04 18.86 0.00 376.83 457.62 20.83 216.67 333.83
August 348.33 0.26 0.22 01-AUG-06:00 1115.96 19.16 0.00 359.50 531.51 21.10 223.17 326.83
September 349.67 0.26 0.22 01-SEP-06:00 1369.21 19.28 0.50 330.33 637.53 21.22 224.83 302.50
October 323.50 0.25 0.22 02-OCT-07:19 1756.56 21.19 40.33 326.33 801.83 21.87 225.17 306.67
November 314.83 0.24 0.22 01-NOV-06:00 3785.25 30.96 239.00 303.50 910.44 23.91 230.00 284.83
December 282.67 0.24 0.22 01-DEC-08:39 6425.67 36.45 279.00 292.00 1085.89 24.87 200.67 273.00
                         
Annual Sum or Average 4111.50 0.25     2122.96 22.84 941.33 3987.50 662.99 21.84 2403.50 3642.83
Minimum of Months 282.67 0.24 0.22   841.40 18.10 0.00 291.33 405.33 20.10 147.83 268.67
Maximum of Months 403.83 0.28 0.22   6425.67 36.45 279.00 376.83 1085.89 25.16 230.00 333.83



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.66 0.60 01-JAN-09:50 354.53 13.62 0.00 261.17 179.81 17.67 0.00 112.50
February 304.33 0.64 0.60 01-FEB-08:50 413.27 14.60 0.00 264.17 201.04 18.47 0.00 149.00
March 362.67 0.63 0.60 01-MAR-12:00 499.88 15.59 0.00 329.33 237.02 19.34 0.00 227.50
April 357.50 0.62 0.60 01-APR-07:19 606.58 16.49 0.00 342.50 283.51 20.17 9.67 295.33
May 389.00 0.62 0.60 01-MAY-06:40 739.72 17.22 12.17 375.67 324.80 20.78 74.00 334.83
June 388.17 0.62 0.60 01-JUN-06:10 809.97 19.06 58.67 368.17 347.65 21.47 105.83 316.67
July 403.83 0.61 0.60 01-JUL-06:19 845.18 17.04 1.33 384.17 366.74 21.34 124.33 344.00
August 348.33 0.62 0.60 01-AUG-06:00 754.01 16.73 0.00 360.00 337.06 20.35 46.67 320.67
September 349.67 0.62 0.60 01-SEP-06:00 627.41 16.00 0.00 324.83 283.05 19.63 1.00 267.67
October 323.50 0.64 0.60 02-OCT-08:09 479.34 15.25 0.00 308.00 233.93 19.05 0.00 218.83
November 314.83 0.64 0.60 01-NOV-07:49 428.37 14.60 0.00 275.67 203.90 18.46 0.00 166.00
December 282.67 0.64 0.60 01-DEC-08:00 399.85 14.34 0.00 262.00 196.75 18.31 0.00 136.50
                         
Annual Sum or Average 4111.50 0.63     596.89 16.02 72.17 3855.67 272.74 19.71 361.50 2889.50
Minimum of Months 282.67 0.61 0.60   354.53 13.62 0.00 261.17 179.81 17.67 0.00 112.50
Maximum of Months 403.83 0.66 0.60   845.18 19.06 58.67 384.17 366.74 21.47 124.33 344.00



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.66 0.60 01-JAN-09:50 354.53 13.62 0.00 261.17 179.81 17.67 0.00 112.50
February 304.33 0.64 0.60 01-FEB-08:50 413.27 14.60 0.00 264.17 201.04 18.47 0.00 149.00
March 362.67 0.63 0.60 01-MAR-12:00 499.88 15.59 0.00 329.33 237.02 19.34 0.00 227.50
April 357.50 0.62 0.60 01-APR-07:19 606.58 16.49 0.00 342.50 283.51 20.17 9.67 295.33
May 389.00 0.62 0.60 01-MAY-06:40 739.72 17.22 12.17 375.67 324.80 20.78 74.00 334.83
June 388.17 0.62 0.60 01-JUN-06:10 809.97 19.06 58.67 368.17 347.65 21.47 105.83 316.67
July 403.83 0.61 0.60 01-JUL-06:19 845.18 17.04 1.33 384.17 366.74 21.34 124.50 344.00
August 348.33 0.62 0.60 01-AUG-06:00 754.01 16.73 0.00 360.00 337.06 20.35 46.67 320.67
September 349.67 0.62 0.60 01-SEP-06:00 627.41 16.00 0.00 324.83 283.05 19.63 1.00 267.67
October 323.50 0.64 0.60 02-OCT-08:09 479.34 15.25 0.00 308.00 233.93 19.05 0.00 218.83
November 314.83 0.64 0.60 01-NOV-07:49 428.37 14.60 0.00 275.67 203.90 18.46 0.00 166.00
December 282.67 0.64 0.60 01-DEC-08:00 399.85 14.34 0.00 262.00 196.75 18.31 0.00 136.50
                         
Annual Sum or Average 4111.50 0.63     596.89 16.02 72.17 3855.67 272.74 19.71 361.67 2889.50
Minimum of Months 282.67 0.61 0.60   354.53 13.62 0.00 261.17 179.81 17.67 0.00 112.50
Maximum of Months 403.83 0.66 0.60   845.18 19.06 58.67 384.17 366.74 21.47 124.50 344.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 428996.49 528.37 25-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 2114923.54 1010.62 03-FEB-24:00 0.00 0.00 0.00 0.00 0.00
March 691239.57 538.87 16-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 30156.49 301.56 15-NOV-10:58 0.00 0.00 0.00 0.00 0.00
December 2592539.33 651.83 27-DEC-02:70 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 5857855.42     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2592539.33 1010.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 591718.88 183.76 31-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 7712479.41 656.43 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 2604947.20 199.75 16-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 196276.54 76.40 16-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 11105422.04     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7712479.41 656.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 104287.20 113.69 26-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 4382814.61 172.98 04-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 377138.34 135.14 16-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4864240.14     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 4382814.61 172.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 37098780.10 1966.88 31-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 23779199.33 1967.06 03-FEB-09:20 0.00 0.00 0.00 0.00 0.00
March 0.122934E+09 3050.96 16-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 9647706.03 1683.19 28-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 2449830.12 1256.69 25-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 885006.48 702.06 22-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 2865662.11 1548.88 28-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1452383.12 868.16 02-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 14901009.67 1422.26 24-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 70525342.55 1930.57 29-DEC-09:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.286539E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122934E+09 3050.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 36508341.61 2906.87 27-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 9727995.54 1520.34 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 36657103.39 3286.85 16-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 197433.67 329.06 19-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 3795010.83 2212.78 13-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 30649078.28 2196.92 21-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.117535E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 36657103.39 3286.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 4904708.08 1549.20 26-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 5666065.55 1983.90 16-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 418216.33 368.90 13-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 3092992.78 1065.87 27-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 14081982.75     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 5666065.55 1983.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 5329.50 0.23 26-JAN-22:50 0.00 0.00 0.00 0.00 0.00
February 7093.54 14.09 28-FEB-10:07 0.00 0.00 0.00 0.00 0.00
March 5527.39 0.22 18-MAR-12:50 0.00 0.00 0.00 0.00 0.00
April 7140.05 0.23 07-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 6554.23 0.23 06-MAY-00:40 0.00 0.00 0.00 0.00 0.00
June 5635.72 0.23 19-JUN-00:50 0.00 0.00 0.00 0.00 0.00
July 8201.17 0.23 23-JUL-19:40 0.00 0.00 0.00 0.00 0.00
August 5312.50 0.23 31-AUG-19:20 0.00 0.00 0.00 0.00 0.00
September 4615.80 0.23 25-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 6708.96 0.23 25-OCT-02:20 0.00 0.00 0.00 0.00 0.00
November 7013.41 0.22 05-NOV-20:30 0.00 0.00 0.00 0.00 0.00
December 8120.64 0.23 10-DEC-23:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 77252.92     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4615.80 0.22   0.00 0.00 0.00 0.00 0.00
Maximum of Months 8201.17 14.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7265347.83 2710.29 17-JAN-09:04 0.00 0.00 0.00 0.00 0.00
February 17369710.55 2709.87 06-FEB-09:04 0.00 0.00 0.00 0.00 0.00
March 4406360.14 2710.52 20-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 1807581.96 2709.96 19-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 733220.93 1277.22 25-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 691878.02 1174.53 13-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 292267.26 743.68 03-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 602813.01 991.41 12-AUG-08:07 0.00 0.00 0.00 0.00 0.00
September 940657.51 1210.18 28-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 1278228.83 2709.45 17-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 2182589.29 2709.25 12-NOV-16:15 0.00 0.00 0.00 0.00 0.00
December 8336809.38 2709.65 27-DEC-19:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 45907464.72     0.00 0.00 0.00 0.00 0.00
Minimum of Months 292267.26 743.68   0.00 0.00 0.00 0.00 0.00
Maximum of Months 17369710.55 2710.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 15037460.40 2713.28 31-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 29781045.56 2712.26 26-FEB-09:54 0.00 0.00 0.00 0.00 0.00
March 5878487.19 2713.58 21-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 1786941.21 2711.45 21-APR-08:34 0.00 0.00 0.00 0.00 0.00
May 837538.22 2365.66 01-MAY-08:35 0.00 0.00 0.00 0.00 0.00
June 474404.66 830.74 14-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 205264.69 761.13 18-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 637658.31 1345.09 28-AUG-08:56 0.00 0.00 0.00 0.00 0.00
September 1052441.65 1298.54 28-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 1404249.09 1807.01 28-OCT-08:55 0.00 0.00 0.00 0.00 0.00
November 3534376.85 2647.89 12-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 17651030.49 2713.97 27-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 78280898.31     0.00 0.00 0.00 0.00 0.00
Minimum of Months 205264.69 761.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 29781045.56 2713.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 51504145.46 19896.14 25-JAN-09:04 0.00 0.00 0.00 0.00 0.00
February 34068218.01 19893.75 22-FEB-09:54 0.00 0.00 0.00 0.00 0.00
March 26593829.98 19890.20 16-MAR-08:05 0.00 0.00 0.00 0.00 0.00
April 10791032.14 16325.09 05-APR-08:36 0.00 0.00 0.00 0.00 0.00
May 3655396.49 12993.40 27-MAY-08:57 0.00 0.00 0.00 0.00 0.00
June 5069580.29 15106.88 15-JUN-08:56 0.00 0.00 0.00 0.00 0.00
July 1714816.94 3631.94 17-JUL-15:18 0.00 0.00 0.00 0.00 0.00
August 10212552.86 12823.10 28-AUG-08:56 0.00 0.00 0.00 0.00 0.00
September 6659686.22 7051.57 05-SEP-08:28 0.00 0.00 0.00 0.00 0.00
October 11477358.98 19894.76 15-OCT-21:56 0.00 0.00 0.00 0.00 0.00
November 22983920.03 15899.80 14-NOV-09:55 0.00 0.00 0.00 0.00 0.00
December 53396468.36 19894.55 21-DEC-09:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.238127E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1714816.94 3631.94   0.00 0.00 0.00 0.00 0.00
Maximum of Months 53396468.36 19896.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 6085272.47 2671.77 21-JAN-19:04 0.00 0.00 0.00 0.00 0.00
February 16784466.15 2674.56 03-FEB-16:14 0.00 0.00 0.00 0.00 0.00
March 2866803.00 2670.76 15-MAR-18:04 0.00 0.00 0.00 0.00 0.00
April 808237.89 1555.47 27-APR-08:06 0.00 0.00 0.00 0.00 0.00
May 833264.00 1874.69 25-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 583463.84 1408.90 15-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 174455.45 1092.28 05-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 630646.58 1504.33 28-AUG-08:06 0.00 0.00 0.00 0.00 0.00
September 273023.09 972.13 15-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 506895.59 1491.09 02-OCT-08:06 0.00 0.00 0.00 0.00 0.00
November 2181313.67 2674.76 12-NOV-16:15 0.00 0.00 0.00 0.00 0.00
December 7942275.69 2677.53 28-DEC-16:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 39670117.43     0.00 0.00 0.00 0.00 0.00
Minimum of Months 174455.45 972.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 16784466.15 2677.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 16489487.62 2680.24 31-JAN-19:04 0.00 0.00 0.00 0.00 0.00
February 27899587.05 2441.14 03-FEB-17:24 0.00 0.00 0.00 0.00 0.00
March 2654191.12 2654.80 15-MAR-20:14 0.00 0.00 0.00 0.00 0.00
April 327894.12 1157.31 12-APR-08:06 0.00 0.00 0.00 0.00 0.00
May 484298.58 1297.26 26-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 456614.34 1177.00 18-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 79863.96 931.75 05-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 441888.47 1551.72 28-AUG-08:56 0.00 0.00 0.00 0.00 0.00
September 212787.49 1088.96 15-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 670994.29 1480.52 21-OCT-21:56 0.00 0.00 0.00 0.00 0.00
November 2457949.36 2280.92 11-NOV-22:55 0.00 0.00 0.00 0.00 0.00
December 21859106.95 2674.29 20-DEC-19:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 74034663.35     0.00 0.00 0.00 0.00 0.00
Minimum of Months 79863.96 931.75   0.00 0.00 0.00 0.00 0.00
Maximum of Months 27899587.05 2680.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 18322985.94 827.75 22-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 18044225.94 789.02 05-FEB-09:03 0.00 0.00 0.00 0.00 0.00
March 10608838.24 843.40 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 346430.08 761.62 20-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 159108.47 321.25 25-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 143040.92 417.54 17-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 74815.30 117.20 13-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 122875.92 194.21 12-AUG-08:07 0.00 0.00 0.00 0.00 0.00
September 165323.44 307.10 28-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 323654.41 642.37 17-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 5913881.72 827.10 14-NOV-09:04 0.00 0.00 0.00 0.00 0.00
December 21110880.50 827.30 16-DEC-19:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 75336060.86     0.00 0.00 0.00 0.00 0.00
Minimum of Months 74815.30 117.20   0.00 0.00 0.00 0.00 0.00
Maximum of Months 21110880.50 843.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 30269035.55 843.83 25-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 25198931.38 847.17 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 11904082.13 847.45 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 676468.79 828.58 18-APR-08:53 0.00 0.00 0.00 0.00 0.00
May 229572.10 533.98 01-MAY-08:35 0.00 0.00 0.00 0.00 0.00
June 92518.16 327.50 17-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 50775.59 149.87 18-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 159458.62 232.87 28-AUG-08:56 0.00 0.00 0.00 0.00 0.00
September 353580.54 536.88 27-SEP-08:26 0.00 0.00 0.00 0.00 0.00
October 323251.54 388.05 20-OCT-08:35 0.00 0.00 0.00 0.00 0.00
November 7473169.04 838.77 13-NOV-09:52 0.00 0.00 0.00 0.00 0.00
December 36425819.22 841.30 27-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113157E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 50775.59 149.87   0.00 0.00 0.00 0.00 0.00
Maximum of Months 36425819.22 847.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7421434.89 3630.19 22-JAN-09:05 0.00 0.00 0.00 0.00 0.00
February 21498737.07 3265.40 24-FEB-09:04 0.00 0.00 0.00 0.00 0.00
March 9472981.42 3682.70 20-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 2154543.67 2287.00 02-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 3524621.63 2447.27 04-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 2621384.70 2590.71 19-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 2312691.88 1591.22 10-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 3001714.26 2768.12 10-AUG-08:06 0.00 0.00 0.00 0.00 0.00
September 2116605.94 2512.68 15-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 2111558.92 2357.27 02-OCT-08:06 0.00 0.00 0.00 0.00 0.00
November 3788612.46 2480.97 29-NOV-09:06 0.00 0.00 0.00 0.00 0.00
December 5535335.56 3513.92 17-DEC-16:16 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 65560222.39     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2111558.92 1591.22   0.00 0.00 0.00 0.00 0.00
Maximum of Months 21498737.07 3682.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.386410E+12 0.282413E+12 375198.43 06-JAN-23:00 182823.29 0.91
February 0.00 0.00 0.398541E+12 0.291489E+12 376278.00 11-FEB-19:03 196178.39 0.90
March 0.00 0.00 0.495657E+12 0.344253E+12 380767.64 09-MAR-21:30 188555.03 0.92
April 0.00 0.00 0.579168E+12 0.400047E+12 375700.61 01-APR-17:15 210426.76 1.00
May 0.00 0.00 0.752110E+12 0.467088E+12 405701.76 24-MAY-18:20 195921.51 1.00
June 0.00 0.00 0.822531E+12 0.481687E+12 427372.85 08-JUN-18:10 245833.70 1.00
July 0.00 0.00 0.879030E+12 0.513409E+12 449513.25 27-JUL-21:00 253472.82 1.00
August 0.00 0.00 0.870110E+12 0.502051E+12 430207.03 21-AUG-21:00 247618.35 1.00
September 0.00 0.00 0.832710E+12 0.488004E+12 444512.03 25-SEP-21:20 201958.73 1.00
October 0.00 0.00 0.782628E+12 0.475860E+12 428316.71 03-OCT-21:00 238213.55 1.00
November 0.00 0.00 0.621609E+12 0.389191E+12 419261.38 21-NOV-20:50 199665.58 0.98
December 0.00 0.00 0.470277E+12 0.310781E+12 416677.03 25-DEC-20:10 187076.06 0.96
                 
Annual Sum or Average 0.00 0.00 0.789078E+13 0.494627E+13       0.97
Minimum of Months 0.00 0.00 0.386410E+12 0.282413E+12 375198.43   182823.29 0.90
Maximum of Months 0.00 0.00 0.879030E+12 0.513409E+12 449513.25   253472.82 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.291328E+11 0.171881E+11 44155.10 07-JAN-09:02 17966.53 0.59
February 0.00 0.00 0.316601E+11 0.197265E+11 41142.31 11-FEB-19:02 17304.71 0.64
March 0.00 0.00 0.384607E+11 0.242583E+11 45817.78 14-MAR-08:62 17892.45 0.64
April 0.00 0.00 0.452088E+11 0.291241E+11 38973.05 22-APR-06:50 15765.07 0.76
May 0.00 0.00 0.554947E+11 0.323240E+11 48557.43 28-MAY-18:03 17368.47 0.76
June 0.00 0.00 0.600198E+11 0.323998E+11 43341.73 18-JUN-20:50 17293.38 0.76
July 0.00 0.00 0.624021E+11 0.336486E+11 44901.42 02-JUL-18:03 16563.10 0.76
August 0.00 0.00 0.634315E+11 0.336299E+11 45991.92 12-AUG-08:03 16296.77 0.76
September 0.00 0.00 0.595970E+11 0.322242E+11 44301.83 04-SEP-21:51 16433.24 0.76
October 0.00 0.00 0.571178E+11 0.323065E+11 45227.74 01-OCT-08:15 16390.72 0.76
November 0.00 0.00 0.478862E+11 0.268434E+11 47104.65 08-NOV-09:02 17154.94 0.72
December 0.00 0.00 0.368102E+11 0.204584E+11 49518.84 23-DEC-19:03 17101.19 0.66
                 
Annual Sum or Average 0.00 0.00 0.587222E+12 0.334132E+12       0.72
Minimum of Months 0.00 0.00 0.291328E+11 0.171881E+11 38973.05   15765.07 0.59
Maximum of Months 0.00 0.00 0.634315E+11 0.336486E+11 49518.84   17966.53 0.76



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.520708E+10 0.250046E+10 14675.64 07-JAN-09:02 7834.11 0.82
February 0.00 0.00 0.566563E+10 0.293942E+10 14405.06 02-FEB-09:02 8053.12 0.85
March 0.00 0.00 0.716717E+10 0.390596E+10 15108.97 19-MAR-08:62 7335.87 0.85
April 0.00 0.00 0.854302E+10 0.494600E+10 13461.24 29-APR-18:02 8790.43 0.93
May 0.00 0.00 0.968983E+10 0.564472E+10 13765.34 24-MAY-18:02 8505.61 0.95
June 0.00 0.00 0.998796E+10 0.584895E+10 13017.84 13-JUN-08:61 9091.05 0.95
July 0.00 0.00 0.111545E+11 0.677396E+10 12617.61 02-JUL-18:02 9377.84 0.96
August 0.00 0.00 0.106373E+11 0.629751E+10 14475.62 12-AUG-08:62 7989.22 0.95
September 0.00 0.00 0.104276E+11 0.621063E+10 13165.15 05-SEP-08:62 8951.94 0.96
October 0.00 0.00 0.100883E+11 0.592360E+10 13968.23 31-OCT-08:62 8370.65 0.95
November 0.00 0.00 0.771167E+10 0.411450E+10 14296.81 24-NOV-09:02 8128.09 0.92
December 0.00 0.00 0.600456E+10 0.299188E+10 15094.49 23-DEC-09:02 7489.94 0.85
                 
Annual Sum or Average 0.00 0.00 0.102285E+12 0.580976E+11       0.91
Minimum of Months 0.00 0.00 0.520708E+10 0.250046E+10 12617.61   7335.87 0.82
Maximum of Months 0.00 0.00 0.111545E+11 0.677396E+10 15108.97   9377.84 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.250686E+10 0.100353E+10 14800.08 07-JAN-09:52 7593.11 0.49
February 0.00 0.00 0.320106E+10 0.153755E+10 14627.87 17-FEB-09:21 8387.69 0.52
March 0.00 0.00 0.487024E+10 0.257036E+10 15726.62 14-MAR-08:21 7269.46 0.60
April 0.00 0.00 0.695139E+10 0.409182E+10 14714.06 14-APR-07:52 9082.76 0.72
May 0.00 0.00 0.940996E+10 0.553738E+10 15183.24 30-MAY-07:52 8823.45 0.90
June 0.00 0.00 0.100276E+11 0.590679E+10 15087.41 13-JUN-07:51 8603.50 0.94
July 0.00 0.00 0.110698E+11 0.677776E+10 14452.75 14-JUL-21:51 9217.29 0.93
August 0.00 0.00 0.103567E+11 0.608871E+10 15051.31 12-AUG-08:52 7634.11 0.93
September 0.00 0.00 0.961449E+10 0.556026E+10 14704.53 16-SEP-08:61 7932.58 0.92
October 0.00 0.00 0.864338E+10 0.480400E+10 14808.58 31-OCT-08:32 7806.09 0.89
November 0.00 0.00 0.570977E+10 0.284607E+10 14772.57 19-NOV-09:31 8165.58 0.74
December 0.00 0.00 0.336086E+10 0.154853E+10 15280.29 10-DEC-09:01 8555.31 0.53
                 
Annual Sum or Average 0.00 0.00 0.857221E+11 0.482728E+11       0.76
Minimum of Months 0.00 0.00 0.250686E+10 0.100353E+10 14452.75   7269.46 0.49
Maximum of Months 0.00 0.00 0.110698E+11 0.677776E+10 15726.62   9217.29 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.409144E+11 0.246203E+11 38724.10 02-JAN-14:30 27267.55 0.88
February 0.00 0.00 0.360658E+11 0.204410E+11 35800.00 11-FEB-14:40 31372.45 0.91
March 0.00 0.00 0.364503E+11 0.179507E+11 30041.41 04-MAR-08:52 18826.59 0.91
April 0.00 0.00 0.365997E+11 0.163604E+11 26854.19 14-APR-16:20 16333.12 0.98
May 0.00 0.00 0.405898E+11 0.173653E+11 28811.74 14-MAY-08:00 16637.78 0.98
June 0.00 0.00 0.438364E+11 0.194588E+11 28941.12 25-JUN-08:00 15707.09 0.98
July 0.00 0.00 0.484215E+11 0.228596E+11 30550.16 29-JUL-08:00 18915.64 1.00
August 0.00 0.00 0.484160E+11 0.228913E+11 30981.30 20-AUG-08:00 20218.07 0.99
September 0.00 0.00 0.536174E+11 0.293283E+11 35289.94 30-SEP-15:10 28170.48 1.00
October 0.00 0.00 0.574658E+11 0.340518E+11 38946.88 25-OCT-17:25 30425.25 1.00
November 0.00 0.00 0.492644E+11 0.283336E+11 38890.73 07-NOV-14:05 27743.53 0.99
December 0.00 0.00 0.431508E+11 0.243295E+11 39144.84 09-DEC-08:40 30987.38 0.97
                 
Annual Sum or Average 0.00 0.00 0.534792E+12 0.277991E+12       0.97
Minimum of Months 0.00 0.00 0.360658E+11 0.163604E+11 26854.19   15707.09 0.88
Maximum of Months 0.00 0.00 0.574658E+11 0.340518E+11 39144.84   31372.45 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.263261E+11 0.141966E+11 98338.96 07-JAN-09:52 51383.47 0.42
February 0.00 0.00 0.279084E+11 0.162302E+11 97056.48 17-FEB-09:21 55034.65 0.46
March 0.00 0.00 0.374132E+11 0.220315E+11 105639.24 14-MAR-08:21 45946.89 0.51
April 0.00 0.00 0.470134E+11 0.288714E+11 97139.11 22-APR-08:21 56752.10 0.61
May 0.00 0.00 0.634092E+11 0.396724E+11 98530.32 25-MAY-21:51 55667.31 0.79
June 0.00 0.00 0.683060E+11 0.439564E+11 99089.73 18-JUN-21:51 54535.78 0.83
July 0.00 0.00 0.719689E+11 0.468097E+11 93644.46 14-JUL-21:51 61769.61 0.84
August 0.00 0.00 0.673123E+11 0.420881E+11 98997.71 12-AUG-08:52 51093.15 0.81
September 0.00 0.00 0.633540E+11 0.393439E+11 101850.50 16-SEP-07:53 55488.71 0.79
October 0.00 0.00 0.573564E+11 0.335251E+11 96951.86 31-OCT-08:32 51429.52 0.74
November 0.00 0.00 0.431352E+11 0.246125E+11 97101.34 22-NOV-09:01 55562.81 0.61
December 0.00 0.00 0.298986E+11 0.161915E+11 99831.13 10-DEC-09:01 56810.07 0.47
                 
Annual Sum or Average 0.00 0.00 0.603402E+12 0.367529E+12       0.66
Minimum of Months 0.00 0.00 0.263261E+11 0.141966E+11 93644.46   45946.89 0.42
Maximum of Months 0.00 0.00 0.719689E+11 0.468097E+11 105639.24   61769.61 0.84



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.544288E+10 0.277028E+10 13101.19 07-JAN-09:02 7291.50 0.84
February 0.00 0.00 0.568064E+10 0.296690E+10 12590.91 10-FEB-09:02 7707.07 0.87
March 0.00 0.00 0.706272E+10 0.381609E+10 13728.98 19-MAR-08:62 6668.12 0.88
April 0.00 0.00 0.849002E+10 0.484887E+10 12229.53 29-APR-18:02 7971.63 0.96
May 0.00 0.00 0.971086E+10 0.568140E+10 12643.98 24-MAY-18:02 7610.48 0.96
June 0.00 0.00 0.104991E+11 0.638498E+10 11062.78 18-JUN-18:02 8797.54 0.97
July 0.00 0.00 0.114690E+11 0.721317E+10 11317.58 02-JUL-18:02 8605.16 0.97
August 0.00 0.00 0.106492E+11 0.643459E+10 13145.22 12-AUG-08:62 7255.76 0.96
September 0.00 0.00 0.107840E+11 0.666941E+10 11792.63 05-SEP-08:62 8241.10 0.97
October 0.00 0.00 0.102257E+11 0.614268E+10 12659.02 31-OCT-08:62 7617.91 0.96
November 0.00 0.00 0.776259E+10 0.425249E+10 12996.12 24-NOV-09:02 7370.53 0.93
December 0.00 0.00 0.563817E+10 0.279878E+10 13725.50 23-DEC-09:02 6792.70 0.85
                 
Annual Sum or Average 0.00 0.00 0.103415E+12 0.599796E+11       0.93
Minimum of Months 0.00 0.00 0.544288E+10 0.277028E+10 11062.78   6668.12 0.84
Maximum of Months 0.00 0.00 0.114690E+11 0.721317E+10 13728.98   8797.54 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.272071E+10 0.122397E+10 13515.22 07-JAN-09:52 6997.32 0.50
February 0.00 0.00 0.318885E+10 0.156732E+10 13546.85 17-FEB-09:21 8025.60 0.56
March 0.00 0.00 0.480083E+10 0.251534E+10 14323.47 04-MAR-08:52 8532.36 0.63
April 0.00 0.00 0.687972E+10 0.396968E+10 13809.76 16-APR-08:51 8840.99 0.74
May 0.00 0.00 0.941868E+10 0.557138E+10 13910.35 30-MAY-07:52 8188.36 0.91
June 0.00 0.00 0.105360E+11 0.648555E+10 14242.57 13-JUN-07:51 8845.58 0.95
July 0.00 0.00 0.113733E+11 0.720878E+10 13239.93 14-JUL-21:51 8470.77 0.95
August 0.00 0.00 0.103654E+11 0.619068E+10 13654.52 12-AUG-08:52 6922.44 0.94
September 0.00 0.00 0.996775E+10 0.595571E+10 14146.38 16-SEP-07:53 7881.67 0.93
October 0.00 0.00 0.875420E+10 0.489902E+10 13871.06 23-OCT-08:11 8484.47 0.90
November 0.00 0.00 0.572012E+10 0.296586E+10 14155.70 22-NOV-08:52 8629.65 0.75
December 0.00 0.00 0.308132E+10 0.143443E+10 14032.05 10-DEC-09:01 8024.70 0.52
                 
Annual Sum or Average 0.00 0.00 0.868069E+11 0.499877E+11       0.77
Minimum of Months 0.00 0.00 0.272071E+10 0.122397E+10 13239.93   6922.44 0.50
Maximum of Months 0.00 0.00 0.113733E+11 0.720878E+10 14323.47   8845.58 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.115753E+10 0.545594E+09 4229.98 07-JAN-09:02 1993.71 0.75
February 0.00 0.00 0.135624E+10 0.693232E+09 4096.40 02-FEB-09:02 2103.20 0.83
March 0.00 0.00 0.175519E+10 0.933268E+09 4283.19 19-MAR-08:62 1880.43 0.82
April 0.00 0.00 0.212766E+10 0.118977E+10 3871.05 16-APR-08:62 2270.01 0.93
May 0.00 0.00 0.246122E+10 0.137368E+10 3884.66 24-MAY-18:02 2258.86 0.95
June 0.00 0.00 0.253662E+10 0.141168E+10 3800.17 13-JUN-08:61 2330.30 0.95
July 0.00 0.00 0.284305E+10 0.166141E+10 3578.88 24-JUL-08:62 2499.74 0.96
August 0.00 0.00 0.269041E+10 0.153049E+10 4238.78 12-AUG-08:62 1986.07 0.95
September 0.00 0.00 0.260727E+10 0.148208E+10 3873.37 05-SEP-08:62 2265.22 0.95
October 0.00 0.00 0.246365E+10 0.137517E+10 4069.11 31-OCT-08:62 2118.97 0.95
November 0.00 0.00 0.183257E+10 0.931727E+09 4099.34 24-NOV-09:02 2003.14 0.89
December 0.00 0.00 0.138213E+10 0.674394E+09 4360.68 23-DEC-09:02 1883.48 0.78
                 
Annual Sum or Average 0.00 0.00 0.252135E+11 0.138025E+11       0.89
Minimum of Months 0.00 0.00 0.115753E+10 0.545594E+09 3578.88   1880.43 0.75
Maximum of Months 0.00 0.00 0.284305E+10 0.166141E+10 4360.68   2499.74 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.505100E+09 0.191720E+09 4192.42 07-JAN-09:52 1988.69 0.42
February 0.00 0.00 0.756860E+09 0.352607E+09 4159.25 17-FEB-09:21 2191.20 0.51
March 0.00 0.00 0.119641E+10 0.608119E+09 4468.28 14-MAR-08:21 1859.97 0.58
April 0.00 0.00 0.176488E+10 0.100038E+10 4184.49 22-APR-08:21 2277.44 0.73
May 0.00 0.00 0.240206E+10 0.135832E+10 4362.00 30-MAY-07:52 2300.08 0.90
June 0.00 0.00 0.255243E+10 0.143559E+10 4293.07 13-JUN-07:51 2221.03 0.93
July 0.00 0.00 0.282811E+10 0.166696E+10 4137.75 14-JUL-21:51 2541.76 0.93
August 0.00 0.00 0.262230E+10 0.147334E+10 4247.72 12-AUG-08:52 1964.15 0.93
September 0.00 0.00 0.240739E+10 0.131789E+10 4197.62 16-SEP-08:61 2051.20 0.91
October 0.00 0.00 0.210425E+10 0.108620E+10 4205.98 26-OCT-08:61 2250.81 0.89
November 0.00 0.00 0.134679E+10 0.617193E+09 4181.31 19-NOV-09:31 2134.27 0.72
December 0.00 0.00 0.755862E+09 0.329339E+09 4388.39 10-DEC-09:01 2144.72 0.47
                 
Annual Sum or Average 0.00 0.00 0.212424E+11 0.114376E+11       0.74
Minimum of Months 0.00 0.00 0.505100E+09 0.191720E+09 4137.75   1859.97 0.42
Maximum of Months 0.00 0.00 0.282811E+10 0.166696E+10 4468.28   2541.76 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.103238E+11 0.645531E+10 17251.20 07-JAN-09:02 8698.10 0.86
February 0.00 0.00 0.971900E+10 0.590021E+10 16857.30 02-FEB-09:02 9008.53 0.89
March 0.00 0.00 0.103067E+11 0.607465E+10 17942.25 19-MAR-08:62 7972.02 0.86
April 0.00 0.00 0.106743E+11 0.616608E+10 16120.65 29-APR-18:02 9580.04 0.92
May 0.00 0.00 0.118073E+11 0.678099E+10 16810.56 24-MAY-18:02 8996.28 0.94
June 0.00 0.00 0.124294E+11 0.739905E+10 15430.64 13-JUN-08:61 10055.41 0.94
July 0.00 0.00 0.135954E+11 0.832999E+10 15356.31 02-JUL-18:02 10098.74 0.95
August 0.00 0.00 0.133839E+11 0.821064E+10 17760.92 12-AUG-08:62 8299.15 0.94
September 0.00 0.00 0.143046E+11 0.919770E+10 15913.65 05-SEP-08:62 9664.42 0.95
October 0.00 0.00 0.149039E+11 0.973863E+10 16991.46 31-OCT-08:62 8881.76 0.96
November 0.00 0.00 0.126844E+11 0.802611E+10 17293.54 24-NOV-09:02 8427.79 0.94
December 0.00 0.00 0.110551E+11 0.678573E+10 17805.23 23-DEC-09:02 8252.33 0.90
                 
Annual Sum or Average 0.00 0.00 0.145188E+12 0.890651E+11       0.92
Minimum of Months 0.00 0.00 0.971900E+10 0.590021E+10 15356.31   7972.02 0.86
Maximum of Months 0.00 0.00 0.149039E+11 0.973863E+10 17942.25   10098.74 0.96



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 83.11 18937.97 25-JAN-19:47
February 0.00 0.00 01-FEB-00:05 97.16 21217.82 04-FEB-09:06
March 0.00 0.00 01-MAR-00:05 89.46 20884.21 16-MAR-08:05
April 0.00 0.00 01-APR-00:10 10.99 15406.61 24-APR-21:56
May 0.00 0.00 01-MAY-00:10 5.53 11364.13 27-MAY-08:57
June 0.00 0.00 01-JUN-00:10 4.76 12159.06 15-JUN-08:56
July 0.00 0.00 01-JUL-00:10 2.08 3709.96 17-JUL-15:18
August 0.00 0.00 01-AUG-00:10 6.50 10092.66 28-AUG-08:56
September 0.00 0.00 01-SEP-00:10 5.10 5947.52 05-SEP-08:28
October 0.00 0.00 01-OCT-00:10 6.63 9855.78 21-OCT-21:56
November 0.00 0.00 01-NOV-00:10 26.28 13267.95 13-NOV-16:16
December 0.00 0.00 01-DEC-00:10 101.55 19381.95 17-DEC-22:57
             
Annual Sum or Average 0.00     36.37    
Minimum of Months 0.00 0.00   2.08 3709.96  
Maximum of Months 0.00 0.00   101.55 21217.82  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 193555.45 485008.29 03-JAN-22:53 0.00 0.00 01-JAN-00:05
February 219387.88 547575.77 10-FEB-22:53 0.00 0.00 01-FEB-00:05
March 243747.35 548039.65 09-MAR-22:52 0.00 0.00 01-MAR-00:05
April 293546.39 554350.85 13-APR-18:03 0.00 0.00 01-APR-00:10
May 363706.76 579718.35 31-MAY-18:03 0.00 0.00 01-MAY-00:10
June 409197.37 624123.07 08-JUN-18:03 0.00 0.00 01-JUN-00:10
July 423306.28 637550.62 27-JUL-18:03 0.00 0.00 01-JUL-00:10
August 417258.78 615317.34 21-AUG-18:05 0.00 0.00 01-AUG-00:10
September 415423.14 649975.81 18-SEP-18:03 0.00 0.00 01-SEP-00:10
October 380597.75 604648.02 30-OCT-18:03 0.00 0.00 01-OCT-00:10
November 313308.62 597104.98 30-NOV-19:03 0.00 0.00 01-NOV-00:10
December 231160.04 588097.74 25-DEC-22:53 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 325864.19     0.00    
Minimum of Months 193555.45 485008.29   0.00 0.00  
Maximum of Months 423306.28 649975.81   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 20264.93 40743.55 20-JAN-07:20
February 0.00 0.00 01-FEB-00:05 20086.48 40618.46 02-FEB-07:57
March 0.00 0.00 01-MAR-00:05 19530.96 39838.45 01-MAR-07:56
April 0.00 0.00 01-APR-00:10 18692.34 38176.33 03-APR-06:55
May 0.00 0.00 01-MAY-00:10 17836.53 36472.94 01-MAY-06:57
June 0.00 0.00 01-JUN-00:10 17185.09 34806.13 01-JUN-06:58
July 0.00 0.00 01-JUL-00:10 16894.17 33796.82 03-JUL-07:00
August 0.00 0.00 01-AUG-00:10 17092.78 34546.04 31-AUG-06:54
September 0.00 0.00 01-SEP-00:10 17671.54 35975.93 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 18497.21 37887.77 31-OCT-07:00
November 0.00 0.00 01-NOV-00:10 19354.99 39550.76 30-NOV-07:55
December 0.00 0.00 01-DEC-00:10 19999.87 40505.64 29-DEC-07:55
             
Annual Sum or Average 0.00     18583.97    
Minimum of Months 0.00 0.00   16894.17 33796.82  
Maximum of Months 0.00 0.00   20264.93 40743.55  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.261333E+10 0.67 1299.30 01-JAN-09:59 0.87
February 0.236042E+10 0.67 1299.30 01-FEB-09:57 0.87
March 0.261333E+10 0.67 1299.30 01-MAR-07:05 0.87
April 0.252903E+10 0.67 1299.30 01-APR-01:00 0.87
May 0.261333E+10 0.67 1299.30 01-MAY-08:39 0.87
June 0.252903E+10 0.67 1299.30 01-JUN-02:30 0.87
July 0.261333E+10 0.67 1299.30 01-JUL-00:40 0.87
August 0.261333E+10 0.67 1299.30 01-AUG-01:50 0.87
September 0.252903E+10 0.67 1299.30 01-SEP-00:10 0.87
October 0.261333E+10 0.67 1299.30 01-OCT-02:30 0.87
November 0.252903E+10 0.67 1299.30 01-NOV-09:10 0.87
December 0.261333E+10 0.67 1299.30 01-DEC-00:50 0.87
           
Annual Sum or Average 0.307698E+11 0.67      
Minimum of Months 0.236042E+10 0.67 1299.30   0.87
Maximum of Months 0.261333E+10 0.67 1299.30   0.87



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.389671E+11 0.87 24257.09 03-JAN-22:00 1.19
February 0.354626E+11 0.88 23333.44 17-FEB-22:00 1.16
March 0.396281E+11 0.88 23097.82 30-MAR-21:10 1.15
April 0.394454E+11 0.90 25927.83 14-APR-21:20 1.24
May 0.425080E+11 0.92 27846.11 22-MAY-22:00 1.30
June 0.427719E+11 0.94 30833.38 29-JUN-22:00 1.38
July 0.452762E+11 0.95 31691.80 28-JUL-22:00 1.41
August 0.447883E+11 0.95 32032.45 21-AUG-21:50 1.42
September 0.442791E+11 0.96 33470.18 22-SEP-22:00 1.45
October 0.441809E+11 0.94 30624.39 06-OCT-21:20 1.38
November 0.406780E+11 0.91 28607.99 03-NOV-21:20 1.32
December 0.398053E+11 0.88 25988.21 08-DEC-22:17 1.24
           
Annual Sum or Average 0.497791E+12 0.92      
Minimum of Months 0.354626E+11 0.87 23097.82   1.15
Maximum of Months 0.452762E+11 0.96 33470.18   1.45



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.26 76.61 01-JAN-00:05 0.26
February 0.185347E+09 0.26 76.61 01-FEB-00:05 0.26
March 0.205205E+09 0.26 76.61 01-MAR-00:05 0.26
April 0.198586E+09 0.26 76.61 01-APR-00:10 0.26
May 0.205205E+09 0.26 76.61 01-MAY-00:10 0.26
June 0.198586E+09 0.26 76.61 01-JUN-00:10 0.26
July 0.205205E+09 0.26 76.61 01-JUL-00:10 0.26
August 0.205205E+09 0.26 76.61 01-AUG-00:10 0.26
September 0.198586E+09 0.26 76.61 01-SEP-00:10 0.26
October 0.205205E+09 0.26 76.61 01-OCT-00:10 0.26
November 0.198586E+09 0.26 76.61 01-NOV-00:10 0.26
December 0.205205E+09 0.26 76.61 01-DEC-00:10 0.26
           
Annual Sum or Average 0.241613E+10 0.26      
Minimum of Months 0.185347E+09 0.26 76.61   0.26
Maximum of Months 0.205205E+09 0.26 76.61   0.26



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 -0.0
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 -0.0
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:10 0.26
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.26
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.26
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.26
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.26
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.26
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.26
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.26
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.26
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.26
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.26
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.26
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.26
Maximum of Months 0.116283E+10 0.19 612.92   0.26



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.209736E+09 0.49 564.16 01-JAN-09:02 0.57
February 0.229591E+09 0.50 564.16 01-FEB-09:02 0.57
March 0.286267E+09 0.51 564.16 01-MAR-09:02 0.57
April 0.344180E+09 0.53 564.16 01-APR-08:62 0.57
May 0.382002E+09 0.54 564.16 01-MAY-08:61 0.57
June 0.388486E+09 0.55 564.16 01-JUN-08:61 0.57
July 0.442160E+09 0.55 564.16 01-JUL-08:62 0.57
August 0.417160E+09 0.55 564.16 01-AUG-08:62 0.57
September 0.410258E+09 0.55 564.16 01-SEP-08:61 0.57
October 0.395292E+09 0.55 564.16 01-OCT-08:62 0.57
November 0.296829E+09 0.53 564.16 01-NOV-08:62 0.57
December 0.235696E+09 0.49 564.16 01-DEC-09:01 0.57
           
Annual Sum or Average 0.403766E+10 0.53      
Minimum of Months 0.209736E+09 0.49 564.16   0.57
Maximum of Months 0.442160E+09 0.55 564.16   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.103115E+09 0.30 570.71 01-JAN-09:51 0.57
February 0.133544E+09 0.32 570.71 01-FEB-09:52 0.57
March 0.193431E+09 0.35 570.71 01-MAR-09:51 0.57
April 0.279596E+09 0.41 570.71 01-APR-08:52 0.57
May 0.373374E+09 0.51 570.71 01-MAY-08:31 0.57
June 0.392755E+09 0.54 570.71 01-JUN-08:61 0.57
July 0.440480E+09 0.54 570.71 01-JUL-08:62 0.57
August 0.403486E+09 0.54 570.71 01-AUG-08:62 0.57
September 0.373801E+09 0.52 570.71 01-SEP-08:61 0.57
October 0.331243E+09 0.51 570.71 01-OCT-08:51 0.57
November 0.215408E+09 0.42 570.71 01-NOV-08:51 0.57
December 0.133019E+09 0.32 570.71 01-DEC-09:21 0.57
           
Annual Sum or Average 0.337325E+10 0.44      
Minimum of Months 0.103115E+09 0.30 570.71   0.57
Maximum of Months 0.440480E+09 0.54 570.71   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.131438E+10 0.56 1494.67 27-JAN-14:30 0.58
February 0.115675E+10 0.56 1332.97 11-FEB-14:30 0.57
March 0.115955E+10 0.56 864.19 02-MAR-14:30 0.57
April 0.114182E+10 0.56 754.88 15-APR-20:10 0.57
May 0.121361E+10 0.56 749.63 14-MAY-08:00 0.57
June 0.127168E+10 0.56 765.40 29-JUN-20:20 0.57
July 0.139908E+10 0.57 806.58 29-JUL-19:10 0.57
August 0.139564E+10 0.57 819.34 20-AUG-08:00 0.57
September 0.154526E+10 0.57 960.81 30-SEP-13:50 0.57
October 0.168506E+10 0.57 1427.83 25-OCT-12:40 0.57
November 0.150496E+10 0.57 1474.63 07-NOV-14:05 0.57
December 0.137207E+10 0.56 1519.47 03-DEC-13:50 0.57
           
Annual Sum or Average 0.161599E+11 0.56      
Minimum of Months 0.114182E+10 0.56 749.63   0.57
Maximum of Months 0.168506E+10 0.57 1519.47   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.102117E+10 0.26 3771.49 01-JAN-09:51 0.57
February 0.111220E+10 0.27 3771.49 01-FEB-09:52 0.57
March 0.149988E+10 0.30 3771.49 01-MAR-09:51 0.57
April 0.190786E+10 0.35 3771.49 01-APR-08:52 0.57
May 0.258070E+10 0.45 3771.49 01-MAY-08:31 0.57
June 0.278695E+10 0.48 3771.49 01-JUN-08:61 0.57
July 0.295061E+10 0.48 3771.49 01-JUL-08:62 0.57
August 0.269843E+10 0.47 3771.49 01-AUG-08:62 0.57
September 0.254492E+10 0.46 3771.49 01-SEP-08:61 0.57
October 0.228876E+10 0.43 3771.49 01-OCT-08:51 0.57
November 0.169447E+10 0.35 3771.49 01-NOV-08:51 0.57
December 0.116459E+10 0.28 3771.49 01-DEC-09:21 0.57
           
Annual Sum or Average 0.242505E+11 0.38      
Minimum of Months 0.102117E+10 0.26 3771.49   0.57
Maximum of Months 0.295061E+10 0.48 3771.49   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.218631E+09 0.51 509.56 01-JAN-09:02 0.57
February 0.229891E+09 0.52 509.56 01-FEB-09:02 0.57
March 0.281617E+09 0.53 509.56 01-MAR-09:02 0.57
April 0.340667E+09 0.55 509.56 01-APR-08:62 0.57
May 0.384932E+09 0.55 509.56 01-MAY-08:61 0.57
June 0.417915E+09 0.55 509.56 01-JUN-08:61 0.57
July 0.458765E+09 0.56 509.56 01-JUL-08:62 0.57
August 0.418286E+09 0.55 509.56 01-AUG-08:62 0.57
September 0.430366E+09 0.55 509.56 01-SEP-08:61 0.57
October 0.404539E+09 0.55 509.56 01-OCT-08:62 0.57
November 0.303730E+09 0.53 509.56 01-NOV-08:62 0.57
December 0.220676E+09 0.50 509.56 01-DEC-09:01 0.57
           
Annual Sum or Average 0.411001E+10 0.54      
Minimum of Months 0.218631E+09 0.50 509.56   0.57
Maximum of Months 0.458765E+09 0.56 509.56   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.109862E+09 0.31 514.24 01-JAN-09:51 0.57
February 0.130187E+09 0.34 514.24 01-FEB-09:52 0.57
March 0.190831E+09 0.37 514.24 01-MAR-09:51 0.57
April 0.277611E+09 0.42 514.24 01-APR-08:52 0.57
May 0.376095E+09 0.52 514.24 01-MAY-08:31 0.57
June 0.420826E+09 0.54 514.24 01-JUN-08:61 0.57
July 0.457070E+09 0.54 514.24 01-JUL-08:62 0.57
August 0.406200E+09 0.54 514.24 01-AUG-08:62 0.57
September 0.395179E+09 0.53 514.24 01-SEP-08:61 0.57
October 0.343320E+09 0.51 514.24 01-OCT-08:51 0.57
November 0.217550E+09 0.43 514.24 01-NOV-08:51 0.57
December 0.121262E+09 0.32 514.24 01-DEC-09:21 0.57
           
Annual Sum or Average 0.344599E+10 0.45      
Minimum of Months 0.109862E+09 0.31 514.24   0.57
Maximum of Months 0.457070E+09 0.54 514.24   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 50048667.52 0.49 155.70 01-JAN-09:02 0.57
February 57378035.57 0.51 155.70 01-FEB-09:02 0.57
March 72078624.27 0.51 155.70 01-MAR-16:11 0.57
April 87473818.23 0.53 155.70 01-APR-08:62 0.57
May 97978295.64 0.54 155.70 01-MAY-08:61 0.57
June 98350283.76 0.54 155.70 01-JUN-08:61 0.57
July 0.112261E+09 0.55 155.70 01-JUL-08:62 0.57
August 0.105066E+09 0.54 155.70 01-AUG-08:62 0.57
September 0.101939E+09 0.54 155.70 01-SEP-08:61 0.57
October 96521067.78 0.54 155.70 01-OCT-08:62 0.57
November 71300742.60 0.52 155.70 01-NOV-08:62 0.57
December 57129936.00 0.50 155.70 01-DEC-09:01 0.57
           
Annual Sum or Average 0.100752E+10 0.53      
Minimum of Months 50048667.52 0.49 155.70   0.57
Maximum of Months 0.112261E+09 0.55 155.70   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 24752381.54 0.31 157.41 01-JAN-09:51 0.57
February 34043847.07 0.33 157.41 01-FEB-22:52 0.57
March 49335379.26 0.36 157.41 01-MAR-09:51 0.57
April 72238820.37 0.42 157.41 01-APR-08:52 0.57
May 95989770.94 0.51 157.41 01-MAY-08:31 0.57
June 99332351.56 0.53 157.41 01-JUN-08:61 0.57
July 0.112068E+09 0.53 157.41 01-JUL-08:62 0.57
August 0.102040E+09 0.53 157.41 01-AUG-08:62 0.57
September 93262312.46 0.52 157.41 01-SEP-08:61 0.57
October 81022956.11 0.51 157.41 01-OCT-08:51 0.57
November 52222281.02 0.43 157.41 01-NOV-08:51 0.57
December 34032285.13 0.33 157.41 01-DEC-09:21 0.57
           
Annual Sum or Average 0.850341E+09 0.44      
Minimum of Months 24752381.54 0.31 157.41   0.57
Maximum of Months 0.112068E+09 0.53 157.41   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.437458E+09 0.52 638.87 01-JAN-09:02 0.57
February 0.408770E+09 0.53 638.87 01-FEB-09:02 0.57
March 0.414527E+09 0.52 638.87 01-MAR-09:02 0.57
April 0.425806E+09 0.53 638.87 01-APR-08:62 0.57
May 0.465310E+09 0.54 638.87 01-MAY-08:61 0.57
June 0.490254E+09 0.54 638.87 01-JUN-08:61 0.57
July 0.543918E+09 0.55 638.87 01-JUL-08:62 0.57
August 0.531145E+09 0.54 638.87 01-AUG-08:62 0.57
September 0.586920E+09 0.55 638.87 01-SEP-08:61 0.57
October 0.620086E+09 0.55 638.87 01-OCT-08:62 0.57
November 0.527711E+09 0.54 638.87 01-NOV-08:62 0.57
December 0.456559E+09 0.52 638.87 01-DEC-09:01 0.57
           
Annual Sum or Average 0.590846E+10 0.53      
Minimum of Months 0.408770E+09 0.52 638.87   0.57
Maximum of Months 0.620086E+09 0.55 638.87   0.57



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 2976714.82 2705833.77 159.68 25-JAN-09:04 145.15 145.15 45.52 0.19
February 3243980.07 2948777.88 188.49 04-FEB-09:06 171.33 171.33 38.06 0.23
March 2250417.02 2045629.07 170.32 16-MAR-08:05 154.82 154.82 35.61 0.20
April 300832.05 273456.33 142.79 24-APR-21:56 129.80 129.80 37.86 0.17
May 170112.96 154632.68 127.25 27-MAY-08:57 115.67 115.67 41.36 0.15
June 174410.96 158539.56 156.22 15-JUN-08:56 142.01 142.01 44.22 0.18
July 90629.41 82382.13 59.64 17-JUL-15:18 54.21 54.21 46.14 0.06
August 292030.17 265455.43 154.88 28-AUG-08:56 140.78 140.78 46.76 0.18
September 232646.56 211475.72 88.34 05-SEP-08:28 80.30 80.30 45.38 0.10
October 303570.73 275945.79 150.31 15-OCT-21:56 136.63 136.63 47.79 0.18
November 899776.71 817897.03 156.07 27-NOV-09:06 141.87 141.87 44.69 0.18
December 3382214.83 3074433.28 175.37 21-DEC-09:04 159.41 159.41 44.98 0.21
                 
Annual Sum or Average 14317336.29 13014458.68            
Minimum of Months 90629.41 82382.13 59.64   54.21 54.21 35.61 0.06
Maximum of Months 3382214.83 3074433.28 188.49   171.33 171.33 47.79 0.23



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.341897E+09 0.310784E+09 578.47 06-JAN-23:00 525.83 525.83 6.72 12.09
February 0.368845E+09 0.335280E+09 701.94 11-FEB-16:23 638.06 638.06 6.72 13.15
March 0.488658E+09 0.444190E+09 782.22 13-MAR-18:03 711.04 711.04 6.72 13.78
April 0.615830E+09 0.559790E+09 904.84 13-APR-18:03 822.50 822.50 6.72 14.67
May 0.927706E+09 0.843285E+09 1035.35 31-MAY-18:03 941.13 941.13 6.72 15.53
June 0.114010E+10 0.103635E+10 1225.97 08-JUN-18:03 1114.40 1114.40 6.72 16.68
July 0.127497E+10 0.115895E+10 1358.21 27-JUL-18:03 1234.61 1234.61 6.72 17.41
August 0.121576E+10 0.110513E+10 1212.97 21-AUG-18:05 1102.59 1102.59 6.72 16.61
September 0.118789E+10 0.107979E+10 1349.11 18-SEP-18:03 1226.34 1226.34 6.72 17.36
October 0.102553E+10 0.932208E+09 1060.95 30-OCT-18:03 964.41 964.41 6.72 15.69
November 0.728404E+09 0.662119E+09 974.12 30-NOV-19:03 885.48 885.48 6.72 15.14
December 0.458963E+09 0.417197E+09 801.65 09-DEC-19:03 728.70 728.70 6.72 13.93
                 
Annual Sum or Average 0.977456E+10 0.888507E+10            
Minimum of Months 0.341897E+09 0.310784E+09 578.47   525.83 525.83 6.72 12.09
Maximum of Months 0.127497E+10 0.115895E+10 1358.21   1234.61 1234.61 6.72 17.41



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.858501E+10 0.780378E+10 3205.28 01-JAN-00:05 2913.60 2913.60 9.15 28.64
February 0.775420E+10 0.704857E+10 3205.28 01-FEB-00:05 2913.60 2913.60 7.49 28.64
March 0.858501E+10 0.780378E+10 3205.28 01-MAR-00:05 2913.60 2913.60 7.93 28.64
April 0.830808E+10 0.755204E+10 3205.28 01-APR-00:10 2913.60 2913.60 8.97 28.64
May 0.858501E+10 0.780378E+10 3205.28 01-MAY-00:10 2913.60 2913.60 9.19 28.64
June 0.830808E+10 0.755204E+10 3205.28 01-JUN-00:10 2913.60 2913.60 9.97 28.64
July 0.858501E+10 0.780378E+10 3205.28 01-JUL-00:10 2913.60 2913.60 9.96 28.64
August 0.858501E+10 0.780378E+10 3205.28 01-AUG-00:10 2913.60 2913.60 10.39 28.64
September 0.830808E+10 0.755204E+10 3205.28 01-SEP-00:10 2913.60 2913.60 10.00 28.64
October 0.858501E+10 0.780378E+10 3205.28 01-OCT-00:10 2913.60 2913.60 9.96 28.64
November 0.830808E+10 0.755204E+10 3205.28 01-NOV-00:10 2913.60 2913.60 9.52 28.64
December 0.858501E+10 0.780378E+10 3205.28 01-DEC-00:10 2913.60 2913.60 9.44 28.64
                 
Annual Sum or Average 0.101082E+12 0.918832E+11            
Minimum of Months 0.775420E+10 0.704857E+10 3205.28   2913.60 2913.60 7.49 28.64
Maximum of Months 0.858501E+10 0.780378E+10 3205.28   2913.60 2913.60 10.39 28.64



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 51.52 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:05 14.37 14.37 51.98 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:05 14.37 14.37 52.17 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.59 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 54.00 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 54.63 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.45 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 54.18 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 53.96 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 54.15 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 54.01 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:10 14.37 14.37 52.47 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 51.52 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.63 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 53.67 53.67 83.11 18937.97 25-JAN-19:47
February 0.00 0.00 01-FEB-00:05 40.37 40.37 97.16 21217.82 04-FEB-09:06
March 0.00 0.00 01-MAR-00:05 40.18 40.18 89.46 20884.21 16-MAR-08:05
April 0.00 0.00 01-APR-00:10 37.32 37.32 10.99 15406.61 24-APR-21:56
May 0.00 0.00 01-MAY-00:10 37.80 37.80 5.53 11364.13 27-MAY-08:57
June 0.00 0.00 01-JUN-00:10 42.08 42.08 4.76 12159.06 15-JUN-08:56
July 0.00 0.00 01-JUL-00:10 45.17 45.17 2.08 3709.96 17-JUL-15:18
August 0.00 0.00 01-AUG-00:10 46.69 46.69 6.50 10092.66 28-AUG-08:56
September 0.00 0.00 01-SEP-00:10 44.66 44.66 5.10 5947.52 05-SEP-08:28
October 0.00 0.00 01-OCT-00:10 48.08 48.08 6.63 9855.78 21-OCT-21:56
November 0.00 0.00 01-NOV-00:10 44.97 44.97 26.28 13267.95 13-NOV-16:16
December 0.00 0.00 01-DEC-00:10 43.65 43.65 101.55 19381.95 17-DEC-22:57
                 
Annual Sum or Average 0.00         36.37    
Minimum of Months 0.00 0.00   37.32 37.32 2.08 3709.96  
Maximum of Months 0.00 0.00   53.67 53.67 101.55 21217.82  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 193555.45 485008.29 03-JAN-22:53 10.74 6.70 0.00 0.00 01-JAN-00:05
February 219387.88 547575.77 10-FEB-22:53 11.26 6.70 0.00 0.00 01-FEB-00:05
March 243747.35 548039.65 09-MAR-22:52 11.27 6.70 0.00 0.00 01-MAR-00:05
April 293546.39 554350.85 13-APR-18:03 11.32 6.70 0.00 0.00 01-APR-00:10
May 363706.76 579718.35 31-MAY-18:03 11.53 6.70 0.00 0.00 01-MAY-00:10
June 409197.37 624123.07 08-JUN-18:03 11.90 6.70 0.00 0.00 01-JUN-00:10
July 423306.28 637550.62 27-JUL-18:03 12.02 6.70 0.00 0.00 01-JUL-00:10
August 417258.78 615317.34 21-AUG-18:05 11.83 6.70 0.00 0.00 01-AUG-00:10
September 415423.14 649975.81 18-SEP-18:03 12.12 6.70 0.00 0.00 01-SEP-00:10
October 380597.75 604648.02 30-OCT-18:03 11.74 6.70 0.00 0.00 01-OCT-00:10
November 313308.62 597104.98 30-NOV-19:03 11.68 6.70 0.00 0.00 01-NOV-00:10
December 231160.04 588097.74 25-DEC-22:53 11.60 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 325864.19         0.00    
Minimum of Months 193555.45 485008.29   10.74 6.70 0.00 0.00  
Maximum of Months 423306.28 649975.81   12.12 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 51.52 59.78 20264.93 40743.55 20-JAN-07:20
February 0.00 0.00 01-FEB-00:05 51.98 59.11 20086.48 40618.46 02-FEB-07:57
March 0.00 0.00 01-MAR-00:05 52.17 59.37 19530.96 39838.45 01-MAR-07:56
April 0.00 0.00 01-APR-00:10 53.59 58.37 18692.34 38176.33 03-APR-06:55
May 0.00 0.00 01-MAY-00:10 54.00 58.56 17836.53 36472.94 01-MAY-06:57
June 0.00 0.00 01-JUN-00:10 54.63 59.06 17185.09 34806.13 01-JUN-06:58
July 0.00 0.00 01-JUL-00:10 54.45 58.67 16894.17 33796.82 03-JUL-07:00
August 0.00 0.00 01-AUG-00:10 54.18 58.39 17092.78 34546.04 31-AUG-06:54
September 0.00 0.00 01-SEP-00:10 53.96 58.23 17671.54 35975.93 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 54.15 59.71 18497.21 37887.77 31-OCT-07:00
November 0.00 0.00 01-NOV-00:10 54.01 58.83 19354.99 39550.76 30-NOV-07:55
December 0.00 0.00 01-DEC-00:10 52.47 59.57 19999.87 40505.64 29-DEC-07:55
                 
Annual Sum or Average 0.00         18583.97    
Minimum of Months 0.00 0.00   51.52 58.23 16894.17 33796.82  
Maximum of Months 0.00 0.00   54.63 59.78 20264.93 40743.55  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 79636832.36 0.00 0.386410E+12 0.389671E+11 0.00 0.00
February 47717412.43 0.00 0.398541E+12 0.354626E+11 0.00 0.00
March 0.168930E+09 0.00 0.495657E+12 0.396281E+11 0.00 0.00
April 9845139.70 0.00 0.579168E+12 0.394454E+11 0.00 0.00
May 2449830.12 0.00 0.752110E+12 0.425080E+11 0.00 0.00
June 885006.48 0.00 0.822531E+12 0.427719E+11 0.00 0.00
July 0.00 0.00 0.879030E+12 0.452762E+11 0.00 0.00
August 2865662.11 0.00 0.870110E+12 0.447883E+11 0.00 0.00
September 0.00 0.00 0.832710E+12 0.442791E+11 0.00 0.00
October 1452383.12 0.00 0.782628E+12 0.441809E+11 0.00 0.00
November 19144393.31 0.00 0.621609E+12 0.406780E+11 0.00 0.00
December 0.107056E+09 0.00 0.470277E+12 0.398053E+11 0.00 0.00
             
Annual Sum or Average 0.439983E+09 0.00 0.789078E+13 0.497791E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.386410E+12 0.354626E+11 0.00 0.00
Maximum of Months 0.168930E+09 0.00 0.879030E+12 0.452762E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 5329.50 0.00 0.291328E+11 0.261333E+10 0.00 0.00
February 7093.54 0.00 0.316601E+11 0.236042E+10 0.00 0.00
March 5527.39 0.00 0.384607E+11 0.261333E+10 0.00 0.00
April 7140.05 0.00 0.452088E+11 0.252903E+10 0.00 0.00
May 6554.23 0.00 0.554947E+11 0.261333E+10 0.00 0.00
June 5635.72 0.00 0.600198E+11 0.252903E+10 0.00 0.00
July 8201.17 0.00 0.624021E+11 0.261333E+10 0.00 0.00
August 5312.50 0.00 0.634315E+11 0.261333E+10 0.00 0.00
September 4615.80 0.00 0.595970E+11 0.252903E+10 0.00 0.00
October 6708.96 0.00 0.571178E+11 0.261333E+10 0.00 0.00
November 7013.41 0.00 0.478862E+11 0.252903E+10 0.00 0.00
December 8120.64 0.00 0.368102E+11 0.261333E+10 0.00 0.00
             
Annual Sum or Average 77252.92 0.00 0.587222E+12 0.307698E+11 0.00 0.00
Minimum of Months 4615.80 0.00 0.291328E+11 0.236042E+10 0.00 0.00
Maximum of Months 8201.17 0.00 0.634315E+11 0.261333E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.389671E+11 0.386410E+12 79636832.36 0.576953E+09 0.207226E+11 0.00 0.00 0.00
February 0.354626E+11 0.398541E+12 47717412.43 0.345765E+10 0.227243E+11 0.00 0.00 0.00
March 0.396281E+11 0.495657E+12 0.168930E+09 0.215207E+10 0.411812E+11 0.00 0.00 0.00
April 0.394454E+11 0.579168E+12 9845139.70 0.423463E+09 0.646828E+11 0.00 0.00 0.00
May 0.425080E+11 0.752110E+12 2449830.12 0.151866E+09 0.175919E+12 0.00 0.00 0.00
June 0.427719E+11 0.822531E+12 885006.48 0.00 0.263242E+12 0.00 0.00 0.00
July 0.452762E+11 0.879030E+12 0.00 0.00 0.278918E+12 0.00 0.00 0.00
August 0.447883E+11 0.870110E+12 2865662.11 0.00 0.286130E+12 0.00 0.00 0.00
September 0.442791E+11 0.832710E+12 0.00 0.00 0.251292E+12 0.00 0.00 0.00
October 0.441809E+11 0.782628E+12 1452383.12 0.295793E+09 0.190187E+12 0.00 0.00 0.00
November 0.406780E+11 0.621609E+12 19144393.31 0.724804E+09 0.104855E+12 0.00 0.00 0.00
December 0.398053E+11 0.470277E+12 0.107056E+09 0.876350E+09 0.373323E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.497791E+12 0.789078E+13 0.439983E+09 0.865895E+10 0.173719E+13 0.00 0.00 0.00
Minimum of Months 0.354626E+11 0.386410E+12 0.00 0.00 0.207226E+11 0.00 0.00 0.00
Maximum of Months 0.452762E+11 0.879030E+12 0.168930E+09 0.345765E+10 0.286130E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.261333E+10 0.291328E+11 5329.50 0.125607E+10 0.475934E+10 0.00 0.00 0.00
February 0.236042E+10 0.316601E+11 7093.54 0.141572E+10 0.588444E+10 0.00 0.00 0.00
March 0.261333E+10 0.384607E+11 5527.39 0.105421E+10 0.126210E+11 0.00 0.00 0.00
April 0.252903E+10 0.452088E+11 7140.05 48415599.14 0.176259E+11 0.00 0.00 0.00
May 0.261333E+10 0.554947E+11 6554.23 0.00 0.370472E+11 0.00 0.00 0.00
June 0.252903E+10 0.600198E+11 5635.72 0.00 0.481008E+11 0.00 0.00 0.00
July 0.261333E+10 0.624021E+11 8201.17 0.00 0.503338E+11 0.00 0.00 0.00
August 0.261333E+10 0.634315E+11 5312.50 0.00 0.515779E+11 0.00 0.00 0.00
September 0.252903E+10 0.595970E+11 4615.80 0.00 0.466889E+11 0.00 0.00 0.00
October 0.261333E+10 0.571178E+11 6708.96 0.00 0.394017E+11 0.00 0.00 0.00
November 0.252903E+10 0.478862E+11 7013.41 0.377436E+09 0.226803E+11 0.00 0.00 0.00
December 0.261333E+10 0.368102E+11 8120.64 0.165302E+10 0.959127E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.307698E+11 0.587222E+12 77252.92 0.580488E+10 0.346312E+12 0.00 0.00 0.00
Minimum of Months 0.236042E+10 0.291328E+11 4615.80 0.00 0.475934E+10 0.00 0.00 0.00
Maximum of Months 0.261333E+10 0.634315E+11 8201.17 0.165302E+10 0.515779E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.389671E+11 79636832.36 0.386410E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.354626E+11 47717412.43 0.398541E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.396281E+11 0.168930E+09 0.495657E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.394454E+11 9845139.70 0.579168E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.425080E+11 2449830.12 0.752110E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.427719E+11 885006.48 0.822531E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.452762E+11 0.00 0.879030E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.447883E+11 2865662.11 0.870110E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.442791E+11 0.00 0.832710E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.441809E+11 1452383.12 0.782628E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.406780E+11 19144393.31 0.621609E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.398053E+11 0.107056E+09 0.470277E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.497791E+12 0.439983E+09 0.789078E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.354626E+11 0.00 0.386410E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.452762E+11 0.168930E+09 0.879030E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.261333E+10 5329.50 0.291328E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.236042E+10 7093.54 0.316601E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.261333E+10 5527.39 0.384607E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.252903E+10 7140.05 0.452088E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.261333E+10 6554.23 0.554947E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.252903E+10 5635.72 0.600198E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.261333E+10 8201.17 0.624021E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.261333E+10 5312.50 0.634315E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.252903E+10 4615.80 0.595970E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.261333E+10 6708.96 0.571178E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.252903E+10 7013.41 0.478862E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.261333E+10 8120.64 0.368102E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.307698E+11 77252.92 0.587222E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.236042E+10 4615.80 0.291328E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 8201.17 0.634315E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.163246E+10 0.351264E+10 0.00 26918502.39 0.464533E+09 0.00 0.137494E+11 0.00 0.61
February 0.229845E+10 0.287969E+10 0.00 15655662.39 0.141413E+10 0.00 0.798507E+10 0.00 0.60
March 0.511856E+10 0.349305E+10 0.00 6151268.63 0.391106E+10 0.00 0.422065E+10 0.00 0.59
April 0.418914E+09 0.376855E+10 0.00 4401361.03 0.488609E+10 0.00 0.242657E+10 0.00 0.59
May 0.00 0.111566E+11 0.00 627255.37 0.706661E+10 0.00 39887868.32 0.00 0.59
June 0.00 0.208942E+11 0.00 0.00 0.356268E+10 0.00 0.00 0.00 0.59
July 0.00 0.261967E+11 0.00 0.00 0.163567E+10 0.00 0.00 0.00 0.62
August 0.00 0.279738E+11 0.00 0.00 0.933079E+09 0.00 0.00 0.00 0.64
September 0.00 0.267493E+11 0.00 0.00 0.396302E+09 0.00 0.00 0.00 0.66
October 0.00 0.220334E+11 0.00 1797586.01 0.249251E+09 0.00 47004335.72 0.00 0.67
November 79286577.63 0.143933E+11 0.00 15501497.90 0.213175E+09 0.00 0.450124E+10 0.00 0.65
December 0.502933E+09 0.754970E+10 0.00 28570866.42 0.537449E+09 0.00 0.119975E+11 0.00 0.63
                   
Annual Sum or Average 0.100506E+11 0.170601E+12 0.00 99624000.14 0.252700E+11 0.00 0.449673E+11 0.00 0.62
Minimum of Months 0.00 0.287969E+10 0.00 0.00 0.213175E+09 0.00 0.00 0.00 0.59
Maximum of Months 0.511856E+10 0.279738E+11 0.00 28570866.42 0.706661E+10 0.00 0.137494E+11 0.00 0.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.898720E+09 0.401842E+09 0.00 2464042.85 60942495.22 0.00 0.571575E+09 0.00 1.15
February 0.581080E+09 0.433377E+09 0.00 2761722.01 59671152.69 0.00 0.429605E+09 0.00 1.18
March 0.569429E+09 0.786128E+09 0.00 1860256.40 58775652.20 0.00 0.327660E+09 0.00 1.16
April 83351132.83 0.996588E+09 0.00 1138386.36 66650992.62 0.00 0.197950E+09 0.00 1.22
May 1815.69 0.216341E+10 0.00 86274.51 32128938.91 0.00 3943071.58 0.00 1.27
June 0.00 0.308508E+10 0.00 0.00 6838826.08 0.00 0.00 0.00 1.34
July 0.00 0.364567E+10 0.00 0.00 0.00 0.00 0.00 0.00 1.43
August 0.00 0.348496E+10 0.00 0.00 81764770.86 0.00 0.00 0.00 1.39
September 0.00 0.351941E+10 0.00 0.00 7780666.60 0.00 0.00 0.00 1.50
October 0.00 0.275399E+10 0.00 163508.10 25450341.18 0.00 4164397.53 0.00 1.48
November 0.241882E+09 0.174647E+10 0.00 1000816.87 30519397.82 0.00 0.176316E+09 0.00 1.34
December 0.698351E+09 0.893518E+09 0.00 1844954.45 56136941.45 0.00 0.444337E+09 0.00 1.22
                   
Annual Sum or Average 0.307281E+10 0.239105E+11 0.00 11319961.55 0.486660E+09 0.00 0.215555E+10 0.00 1.31
Minimum of Months 0.00 0.401842E+09 0.00 0.00 0.00 0.00 0.00 0.00 1.15
Maximum of Months 0.898720E+09 0.364567E+10 0.00 2761722.01 81764770.86 0.00 0.571575E+09 0.00 1.50



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.142343E+10 0.125296E+09 0.00 202090.30 0.287053E+09 0.00 0.197438E+09 0.00 0.99
February 0.694229E+09 0.159512E+09 0.00 658393.46 0.297734E+09 0.00 0.402630E+09 0.00 1.00
March 0.683703E+09 0.409984E+09 0.00 638402.08 0.393703E+09 0.00 0.321322E+09 0.00 1.00
April 54598522.70 0.600037E+09 0.00 908143.33 0.369494E+09 0.00 0.255405E+09 0.00 1.02
May 2100.01 0.151054E+10 0.00 78708.75 0.534037E+09 0.00 4299689.03 0.00 1.04
June 0.00 0.234559E+10 0.00 0.00 0.407407E+09 0.00 0.00 0.00 1.05
July 0.00 0.284256E+10 0.00 0.00 0.242088E+09 0.00 0.00 0.00 1.07
August 0.00 0.253890E+10 0.00 0.00 0.512131E+09 0.00 0.00 0.00 1.05
September 0.00 0.244846E+10 0.00 0.00 0.314153E+09 0.00 0.00 0.00 1.05
October 5658.27 0.173253E+10 0.00 140817.91 0.460626E+09 0.00 4158358.86 0.00 1.02
November 0.335867E+09 0.964161E+09 0.00 174829.51 0.458664E+09 0.00 0.116317E+09 0.00 1.00
December 0.988122E+09 0.440452E+09 0.00 396783.42 0.369950E+09 0.00 0.266580E+09 0.00 1.00
                   
Annual Sum or Average 0.417996E+10 0.161180E+11 0.00 3198168.77 0.464704E+10 0.00 0.156815E+10 0.00 1.02
Minimum of Months 0.00 0.125296E+09 0.00 0.00 0.242088E+09 0.00 0.00 0.00 0.99
Maximum of Months 0.142343E+10 0.284256E+10 0.00 908143.33 0.534037E+09 0.00 0.402630E+09 0.00 1.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 20499084.97 0.177216E+09 0.00 644413.94 216929.62 0.00 0.113402E+09 0.00 0.10
February 9525257.06 0.220473E+09 0.00 975187.89 129656.89 0.00 0.171574E+09 0.00 0.14
March 10552595.27 0.435781E+09 0.00 760914.31 152180.16 0.00 0.120781E+09 0.00 0.17
April 0.00 0.615650E+09 0.00 1004088.20 0.00 0.00 0.146940E+09 0.00 0.28
May 0.00 0.177387E+10 0.00 84162.22 0.00 0.00 3170353.54 0.00 0.42
June 0.00 0.287086E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.51
July 0.00 0.330622E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.54
August 0.00 0.287202E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.47
September 0.00 0.267422E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.48
October 0.00 0.177370E+10 0.00 121209.26 0.00 0.00 3062236.96 0.00 0.39
November 2550174.40 0.102983E+10 0.00 536504.69 7175.16 0.00 95815678.49 0.00 0.28
December 15384100.38 0.444804E+09 0.00 728570.49 350554.80 0.00 0.146094E+09 0.00 0.15
                   
Annual Sum or Average 58511212.08 0.181946E+11 0.00 4855051.01 856496.63 0.00 0.800839E+09 0.00 0.33
Minimum of Months 0.00 0.177216E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.10
Maximum of Months 20499084.97 0.330622E+10 0.00 1004088.20 350554.80 0.00 0.171574E+09 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.102080E+10 0.00 0.00 0.00 0.258862E+09 0.00 0.00 0.00 0.51
February 0.688801E+09 0.00 0.00 0.00 0.286907E+09 0.00 0.00 0.00 0.51
March 0.630894E+09 0.00 0.00 0.00 0.500200E+09 0.00 0.00 0.00 0.51
April 0.192087E+09 13372803.63 0.00 244.45 0.571458E+09 0.00 459043.51 0.00 0.51
May 2738735.64 0.332103E+09 0.00 0.00 0.891468E+09 0.00 0.00 0.00 0.51
June 0.00 0.118658E+10 0.00 0.00 0.453227E+09 0.00 0.00 0.00 0.51
July 0.00 0.158194E+10 0.00 0.00 0.232836E+09 0.00 0.00 0.00 0.51
August 0.00 0.964703E+09 0.00 0.00 0.834764E+09 0.00 0.00 0.00 0.51
September 0.00 0.943895E+09 0.00 0.00 0.679174E+09 0.00 0.00 0.00 0.50
October 2618543.81 0.166482E+09 0.00 0.00 0.115867E+10 0.00 0.00 0.00 0.50
November 0.284853E+09 8930964.55 0.00 0.00 0.867711E+09 0.00 0.00 0.00 0.51
December 0.789591E+09 0.00 0.00 0.00 0.503920E+09 0.00 0.00 0.00 0.51
                   
Annual Sum or Average 0.361238E+10 0.519801E+10 0.00 244.45 0.723919E+10 0.00 459043.51 0.00 0.51
Minimum of Months 0.00 0.00 0.00 0.00 0.232836E+09 0.00 0.00 0.00 0.50
Maximum of Months 0.102080E+10 0.158194E+10 0.00 244.45 0.115867E+10 0.00 459043.51 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.510002E+10 0.00 68729378.32 0.00 0.00 0.182026E+11 0.00 11.56
February 0.00 0.559503E+10 0.00 56660904.00 0.00 0.00 0.123170E+11 0.00 11.67
March 0.00 0.993078E+10 0.00 50385983.22 0.00 0.00 0.112447E+11 0.00 11.80
April 0.00 0.114935E+11 0.00 24299031.50 0.00 0.00 0.347136E+10 0.00 11.96
May 0.00 0.243743E+11 0.00 1103665.55 0.00 0.00 39431462.53 0.00 12.10
June 0.00 0.330579E+11 0.00 0.00 0.00 0.00 0.00 0.00 12.18
July 0.00 0.357464E+11 0.00 0.00 0.00 0.00 0.00 0.00 12.11
August 0.00 0.356849E+11 0.00 0.00 0.00 0.00 0.00 0.00 12.00
September 0.00 0.325375E+11 0.00 0.00 0.00 0.00 0.00 0.00 12.02
October 0.00 0.260091E+11 0.00 1816699.02 0.00 0.00 41929696.83 0.00 11.91
November 0.00 0.176722E+11 0.00 24970655.24 0.00 0.00 0.506547E+10 0.00 11.79
December 0.00 0.980153E+10 0.00 53536058.51 0.00 0.00 0.142341E+11 0.00 11.54
                   
Annual Sum or Average 0.00 0.247003E+12 0.00 0.281502E+09 0.00 0.00 0.646166E+11 0.00 11.89
Minimum of Months 0.00 0.510002E+10 0.00 0.00 0.00 0.00 0.00 0.00 11.54
Maximum of Months 0.00 0.357464E+11 0.00 68729378.32 0.00 0.00 0.182026E+11 0.00 12.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.418353E+10 0.180175E+10 0.00 7231312.39 0.123179E+10 0.00 0.777134E+10 0.00 3.01
February 0.290600E+10 0.188854E+10 0.00 6995434.34 0.147355E+10 0.00 0.515864E+10 0.00 3.01
March 0.273775E+10 0.355745E+10 0.00 4796606.55 0.230408E+10 0.00 0.465050E+10 0.00 3.00
April 0.523440E+09 0.385586E+10 0.00 3536007.10 0.299742E+10 0.00 0.172936E+10 0.00 2.99
May 18103.48 0.809539E+10 0.00 465456.33 0.624059E+10 0.00 31609973.37 0.00 2.98
June 0.00 0.118368E+11 0.00 0.00 0.718588E+10 0.00 0.00 0.00 2.96
July 0.00 0.144506E+11 0.00 0.00 0.642529E+10 0.00 0.00 0.00 2.94
August 0.00 0.140858E+11 0.00 0.00 0.688148E+10 0.00 0.00 0.00 2.95
September 0.00 0.149043E+11 0.00 0.00 0.409539E+10 0.00 0.00 0.00 2.95
October 850005.25 0.122119E+11 0.00 703029.74 0.333578E+10 0.00 29177826.73 0.00 2.97
November 0.108016E+10 0.805540E+10 0.00 2705585.01 0.222801E+10 0.00 0.225515E+10 0.00 2.98
December 0.285923E+10 0.439357E+10 0.00 5503658.92 0.151253E+10 0.00 0.638799E+10 0.00 3.00
                   
Annual Sum or Average 0.142910E+11 0.991373E+11 0.00 31937090.38 0.459118E+11 0.00 0.280138E+11 0.00 2.98
Minimum of Months 0.00 0.180175E+10 0.00 0.00 0.123179E+10 0.00 0.00 0.00 2.94
Maximum of Months 0.418353E+10 0.149043E+11 0.00 7231312.39 0.718588E+10 0.00 0.777134E+10 0.00 3.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.161127E+11 0.364947E+10 0.00 17989394.61 0.488494E+10 0.00 0.173491E+11 0.00 1.22
February 0.937074E+10 0.443727E+10 0.00 20646740.27 0.500491E+10 0.00 0.132255E+11 0.00 1.22
March 0.103419E+11 0.874364E+10 0.00 16521459.96 0.773120E+10 0.00 0.103532E+11 0.00 1.22
April 0.116291E+10 0.973036E+10 0.00 17762625.69 0.965966E+10 0.00 0.515875E+10 0.00 1.22
May 0.00 0.248182E+11 0.00 2063461.46 0.162275E+11 0.00 88798351.69 0.00 1.24
June 0.00 0.397678E+11 0.00 0.00 0.157544E+11 0.00 0.00 0.00 1.26
July 0.00 0.481299E+11 0.00 0.00 0.131274E+11 0.00 0.00 0.00 1.26
August 0.00 0.440470E+11 0.00 0.00 0.170803E+11 0.00 0.00 0.00 1.25
September 0.00 0.447506E+11 0.00 0.00 0.109418E+11 0.00 0.00 0.00 1.26
October 116859.32 0.339935E+11 0.00 2970638.66 0.108178E+11 0.00 88226774.40 0.00 1.24
November 0.324092E+10 0.209068E+11 0.00 9305511.27 0.848807E+10 0.00 0.609228E+10 0.00 1.23
December 0.111267E+11 0.108178E+11 0.00 17340101.12 0.589872E+10 0.00 0.147748E+11 0.00 1.22
                   
Annual Sum or Average 0.513560E+11 0.293792E+12 0.00 0.104600E+09 0.125617E+12 0.00 0.671306E+11 0.00 1.24
Minimum of Months 0.00 0.364947E+10 0.00 0.00 0.488494E+10 0.00 0.00 0.00 1.22
Maximum of Months 0.161127E+11 0.481299E+11 0.00 20646740.27 0.170803E+11 0.00 0.173491E+11 0.00 1.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 7165230.78 0.314640E+09 82724.45 6063360.77 2454824.37 1863674.35 0.484019E+09 3597.85 0.34
February 4211335.01 0.298711E+09 60431.60 5029362.99 2903695.78 11751935.62 0.294789E+09 1987.62 0.34
March 11415585.71 0.451082E+09 160846.40 4230603.44 1221348.84 1326485.54 0.276204E+09 5208.35 0.34
April 18646.80 0.609187E+09 188006.69 1604780.69 947666.66 91196.22 43946006.08 3060.42 0.34
May 0.00 0.112077E+10 144922.00 0.00 2102978.02 0.00 0.00 1708.55 0.34
June 0.00 0.142782E+10 343324.97 0.00 0.00 0.00 0.00 1283.11 0.34
July 0.00 0.149571E+10 125583.84 0.00 0.00 0.00 0.00 348.98 0.34
August 0.00 0.152762E+10 369753.55 0.00 4688248.20 0.00 0.00 1327.99 0.34
September 0.00 0.138631E+10 571492.46 0.00 0.00 0.00 0.00 2911.14 0.34
October 0.00 0.118975E+10 474550.60 0.00 0.00 0.00 0.00 9231.02 0.34
November 566401.96 0.864852E+09 204500.56 1920468.47 2613159.56 319615.40 0.130390E+09 1833.01 0.34
December 3877861.23 0.472500E+09 118899.36 4541190.38 960964.98 1649138.30 0.341137E+09 3622.99 0.34
                   
Annual Sum or Average 27255061.47 0.111589E+11 2845036.52 23389766.75 17892886.41 17002045.43 0.157049E+10 36121.04 0.34
Minimum of Months 0.00 0.298711E+09 60431.60 0.00 0.00 0.00 0.00 348.98 0.34
Maximum of Months 11415585.71 0.152762E+10 571492.46 6063360.77 4688248.20 11751935.62 0.484019E+09 9231.02 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.136065E+09 0.243176E+09 452353.80 2106674.25 73492192.78 2660342.93 0.358221E+09 23372.73 0.34
February 75780321.35 0.230473E+09 154377.60 2520392.76 71000885.08 24968990.30 0.212475E+09 13697.50 0.34
March 78077715.43 0.361323E+09 222209.04 1966488.49 90858184.69 1876539.28 0.211221E+09 12943.27 0.34
April 16669618.00 0.517608E+09 230054.50 835710.16 92404438.03 5359.64 28144592.19 11663.36 0.34
May 0.00 0.107090E+10 142257.90 0.00 51838105.07 0.00 0.00 4003.91 0.34
June 0.00 0.140831E+10 120987.50 0.00 19559910.65 0.00 0.00 507.58 0.34
July 0.00 0.146453E+10 58497.31 0.00 31068698.70 0.00 0.00 220.31 0.34
August 0.00 0.151043E+10 195016.13 0.00 21872811.28 0.00 0.00 1112.56 0.34
September 0.00 0.134733E+10 543797.57 0.00 38843941.20 0.00 0.00 2567.45 0.34
October 0.00 0.113531E+10 509193.37 0.00 54272004.80 0.00 0.00 7682.22 0.34
November 35851262.44 0.776594E+09 395110.23 861514.21 90567453.97 503972.83 95964051.77 13259.52 0.34
December 0.103161E+09 0.373872E+09 650556.58 1613775.34 98985877.57 2401688.77 0.243988E+09 19581.39 0.34
                   
Annual Sum or Average 0.445604E+09 0.104399E+11 3674411.53 9904555.21 0.734765E+09 32416893.74 0.115001E+10 110611.79 0.34
Minimum of Months 0.00 0.230473E+09 58497.31 0.00 19559910.65 0.00 0.00 220.31 0.34
Maximum of Months 0.136065E+09 0.151043E+10 650556.58 2520392.76 98985877.57 24968990.30 0.358221E+09 23372.73 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 37872014.71 0.479260E+09 0.00 1570384.69 0.00 0.00 0.326810E+09 0.00 0.02
February 0.00 0.471121E+09 0.00 920614.18 11016384.05 0.00 0.143051E+09 0.00 0.02
March 26821395.07 0.498010E+09 0.00 808242.64 0.00 0.00 0.218923E+09 0.00 0.02
April 0.00 0.596344E+09 0.00 110624.89 17241826.69 0.00 38128614.28 0.00 0.02
May 0.00 0.919665E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.02
June 0.00 0.102826E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
July 0.00 0.110694E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
August 0.00 0.113334E+10 0.00 0.00 46058585.06 0.00 0.00 0.00 0.02
September 0.00 0.111902E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
October 0.00 0.101417E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
November 21990599.61 0.660617E+09 0.00 398567.70 0.00 0.00 46635825.36 0.00 0.02
December 23328509.84 0.675956E+09 0.00 1113973.39 4561665.52 0.00 0.221282E+09 0.00 0.02
                   
Annual Sum or Average 0.110013E+09 0.970271E+10 0.00 4922407.50 78878461.31 0.00 0.994831E+09 0.00 0.02
Minimum of Months 0.00 0.471121E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 37872014.71 0.113334E+10 0.00 1570384.69 46058585.06 0.00 0.326810E+09 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.184578E+10 0.315234E+10 1915165.75 33519779.43 0.114756E+10 19738394.74 0.487032E+10 52706.77 0.39
February 0.104344E+10 0.294697E+10 1606996.35 29925180.68 0.114296E+10 10470447.14 0.319906E+10 47456.74 0.39
March 0.106241E+10 0.464289E+10 1430333.27 24421951.49 0.149240E+10 6714668.98 0.288275E+10 35068.30 0.39
April 0.238014E+09 0.665928E+10 2274608.40 8677423.97 0.161614E+10 177892.89 0.372417E+09 39270.42 0.39
May 0.00 0.138301E+11 866019.21 0.00 0.140025E+10 0.00 0.00 5504.44 0.39
June 0.00 0.182711E+11 686408.23 0.00 0.109813E+10 0.00 0.00 7740.27 0.39
July 0.00 0.190422E+11 0.00 0.00 0.124548E+10 0.00 0.00 0.00 0.39
August 0.00 0.195980E+11 858370.34 0.00 0.118855E+10 0.00 0.00 5265.54 0.39
September 0.00 0.174602E+11 0.00 0.00 0.134984E+10 0.00 0.00 0.00 0.39
October 0.00 0.146385E+11 954260.17 0.00 0.150350E+10 0.00 0.00 26317.26 0.39
November 0.518894E+09 0.100279E+11 1431982.79 12549759.91 0.173872E+10 1803259.59 0.127327E+10 28930.12 0.39
December 0.140760E+10 0.481515E+10 3923046.08 24274933.53 0.160402E+10 10292234.59 0.332117E+10 38970.20 0.39
                   
Annual Sum or Average 0.611613E+10 0.135085E+12 15947190.57 0.133369E+09 0.165275E+11 49196897.92 0.159190E+11 287230.06 0.39
Minimum of Months 0.00 0.294697E+10 0.00 0.00 0.109813E+10 0.00 0.00 0.00 0.39
Maximum of Months 0.184578E+10 0.195980E+11 3923046.08 33519779.43 0.173872E+10 19738394.74 0.487032E+10 52706.77 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5526872.54 0.315281E+09 116009.89 6410070.71 1778933.61 1356594.71 0.485818E+09 5162.27 0.34
February 4211335.01 0.299138E+09 110211.87 5344212.20 2422767.75 10662832.94 0.295564E+09 6313.51 0.34
March 5788227.05 0.451775E+09 128158.38 4328196.38 561570.13 701064.69 0.282359E+09 4232.81 0.34
April 0.00 0.610245E+09 77238.94 1666422.98 0.00 17803.25 43976403.56 3536.10 0.34
May 0.00 0.112062E+10 285862.97 0.00 2102978.02 0.00 0.00 4963.12 0.34
June 0.00 0.142783E+10 325697.56 0.00 0.00 0.00 0.00 3475.88 0.34
July 0.00 0.149570E+10 136322.86 0.00 0.00 0.00 0.00 973.27 0.34
August 0.00 0.152783E+10 160528.47 0.00 4688248.20 0.00 0.00 3010.58 0.34
September 0.00 0.138670E+10 185673.00 0.00 0.00 0.00 0.00 1187.75 0.34
October 0.00 0.118994E+10 242425.41 0.00 54265.69 0.00 0.00 2299.10 0.34
November 566401.96 0.865090E+09 365998.82 2103491.30 2209172.68 343287.05 0.130183E+09 5475.87 0.34
December 6032186.14 0.472382E+09 203033.56 4498450.61 991958.43 1063417.33 0.339612E+09 6802.89 0.34
                   
Annual Sum or Average 22125022.69 0.111625E+11 2337161.73 24350844.17 14809894.52 14144999.96 0.157751E+10 47433.15 0.34
Minimum of Months 0.00 0.299138E+09 77238.94 0.00 0.00 0.00 0.00 973.27 0.34
Maximum of Months 6032186.14 0.152783E+10 365998.82 6410070.71 4688248.20 10662832.94 0.485818E+09 6802.89 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.135376E+09 0.244894E+09 190668.80 2575424.58 72051687.75 3824306.04 0.357277E+09 8437.32 0.34
February 75209069.69 0.231722E+09 135101.29 2697692.59 69781356.20 26792461.96 0.211046E+09 3220.39 0.34
March 77687403.36 0.361886E+09 116350.12 2182157.98 90410592.82 657380.93 0.212615E+09 3055.05 0.34
April 16578036.87 0.517739E+09 109616.02 895678.18 92404438.03 0.00 28181564.92 1056.44 0.34
May 0.00 0.107072E+10 327658.99 0.00 51838105.07 0.00 0.00 2316.16 0.34
June 0.00 0.140809E+10 341827.17 0.00 19559910.65 0.00 0.00 2093.26 0.34
July 0.00 0.146452E+10 69683.44 0.00 31068698.70 0.00 0.00 396.16 0.34
August 0.00 0.151138E+10 180638.37 0.00 20934778.78 0.00 0.00 1596.10 0.34
September 0.00 0.134769E+10 128055.23 0.00 38908154.89 0.00 0.00 851.76 0.34
October 0.00 0.113545E+10 369297.56 0.00 54272004.80 0.00 0.00 3751.78 0.34
November 35870857.74 0.776380E+09 462315.16 1049100.66 90718599.67 221784.65 96039058.20 9002.83 0.34
December 0.103448E+09 0.372355E+09 439203.69 1591169.94 0.100723E+09 11326234.06 0.234799E+09 11847.64 0.34
                   
Annual Sum or Average 0.444170E+09 0.104428E+11 2870415.85 10991223.93 0.732671E+09 42822167.64 0.113996E+10 47624.89 0.34
Minimum of Months 0.00 0.231722E+09 69683.44 0.00 19559910.65 0.00 0.00 396.16 0.34
Maximum of Months 0.135376E+09 0.151138E+10 462315.16 2697692.59 0.100723E+09 26792461.96 0.357277E+09 11847.64 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.839315E+10 0.00 0.00 0.00 0.212840E+10 0.00 0.00 0.00 0.33
February 0.566342E+10 0.00 0.00 0.00 0.235899E+10 0.00 0.00 0.00 0.33
March 0.518729E+10 0.00 0.00 0.00 0.411271E+10 0.00 0.00 0.00 0.33
April 0.157386E+10 69448876.77 0.00 4234.95 0.473911E+10 0.00 9279494.61 0.00 0.33
May 22518248.61 0.602116E+09 0.00 0.00 0.945664E+10 0.00 0.00 0.00 0.33
June 0.00 0.399620E+10 0.00 0.00 0.936037E+10 0.00 0.00 0.00 0.33
July 0.00 0.784106E+10 0.00 0.00 0.686566E+10 0.00 0.00 0.00 0.33
August 0.00 0.510956E+10 0.00 0.00 0.965871E+10 0.00 0.00 0.00 0.33
September 0.00 0.688201E+10 0.00 0.00 0.653484E+10 0.00 0.00 0.00 0.33
October 13568659.55 0.338367E+10 0.00 106273.52 0.751546E+10 0.00 7855082.31 0.00 0.33
November 0.233643E+10 0.475448E+09 0.00 4205.60 0.673242E+10 0.00 5664248.73 0.00 0.33
December 0.649212E+10 2173511.99 0.00 0.00 0.414112E+10 0.00 0.00 0.00 0.33
                   
Annual Sum or Average 0.296824E+11 0.283617E+11 0.00 114714.08 0.736044E+11 0.00 22798825.64 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.00 0.212840E+10 0.00 0.00 0.00 0.33
Maximum of Months 0.839315E+10 0.784106E+10 0.00 106273.52 0.965871E+10 0.00 9279494.61 0.00 0.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1313385.62 78821551.26 32767.62 1277070.86 439574.96 14438458.18 0.107749E+09 1487.69 0.34
February 1052833.75 74894599.26 7900.57 1074796.73 516267.88 11526970.47 65290885.94 468.04 0.34
March 2853599.22 0.112990E+09 32022.34 940049.70 94627.01 9603904.19 59896524.44 878.52 0.34
April 0.00 0.152548E+09 32475.60 357690.71 0.00 11109.92 11046356.81 605.93 0.34
May 0.00 0.280710E+09 43325.50 0.00 0.00 0.00 0.00 560.40 0.34
June 0.00 0.357017E+09 22798.10 0.00 0.00 0.00 0.00 462.67 0.34
July 0.00 0.373958E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.34
August 0.00 0.381972E+09 25936.75 0.00 1172062.05 0.00 0.00 104.10 0.34
September 0.00 0.346676E+09 44809.43 0.00 0.00 0.00 0.00 512.94 0.34
October 0.00 0.297491E+09 66017.14 0.00 0.00 0.00 0.00 1952.70 0.34
November 141600.49 0.216278E+09 19020.59 386909.40 620704.11 5041885.66 27728706.23 179.37 0.34
December 427981.67 0.118135E+09 19604.33 906647.69 240241.24 16766602.99 69700159.03 672.20 0.34
                   
Annual Sum or Average 5789400.75 0.279149E+10 346677.98 4943165.09 3083477.25 57388931.42 0.341412E+09 7884.57 0.34
Minimum of Months 0.00 74894599.26 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 2853599.22 0.381972E+09 66017.14 1277070.86 1172062.05 16766602.99 0.107749E+09 1952.70 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 33994860.05 61123116.50 128489.01 318600.16 18028526.99 22823523.41 67626200.67 5958.42 0.34
February 18900758.60 57888033.59 62376.52 509374.72 17457648.36 14627921.77 44898182.19 2340.82 0.34
March 19630263.26 90532222.81 57012.87 388617.82 22511576.78 9241785.73 44024823.26 3181.72 0.34
April 4144509.22 0.129376E+09 81743.12 186467.12 23101109.51 9520.05 7073323.61 4530.67 0.34
May 0.00 0.267754E+09 70005.47 0.00 12895440.56 0.00 0.00 1295.71 0.34
June 0.00 0.352074E+09 34684.18 0.00 4889977.66 0.00 0.00 400.67 0.34
July 0.00 0.366133E+09 14667.95 0.00 7767174.68 0.00 0.00 11.46 0.34
August 0.00 0.377575E+09 81639.73 0.00 5468202.82 0.00 0.00 207.97 0.34
September 0.00 0.336870E+09 97867.71 0.00 9710985.30 0.00 0.00 1875.56 0.34
October 0.00 0.283873E+09 81971.16 0.00 13568001.20 0.00 0.00 1139.56 0.34
November 8941929.17 0.194065E+09 133533.80 135903.31 22689027.84 6530631.40 17686736.43 4419.73 0.34
December 25641854.53 93982561.78 150307.45 245333.84 24244629.28 25444588.68 36459327.12 4576.04 0.34
                   
Annual Sum or Average 0.111254E+09 0.261125E+10 994298.98 1784296.97 0.182332E+09 78677971.04 0.217769E+09 29938.33 0.34
Minimum of Months 0.00 57888033.59 14667.95 0.00 4889977.66 0.00 0.00 11.46 0.34
Maximum of Months 33994860.05 0.377575E+09 150307.45 509374.72 24244629.28 25444588.68 67626200.67 5958.42 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4204887.44 0.507532E+09 33336.20 12234617.97 1866904.74 1624785.87 0.783569E+09 247.05 0.39
February 0.00 0.481618E+09 107469.23 8588793.92 2802036.08 16483100.22 0.482113E+09 2149.73 0.39
March 3158343.85 0.726069E+09 100628.47 6212899.08 549383.11 2596207.37 0.458910E+09 1510.88 0.39
April 0.00 0.980044E+09 208044.18 1966385.36 0.00 174223.77 71195948.23 5836.83 0.39
May 0.00 0.180033E+10 1248965.94 0.00 2105011.48 0.00 0.00 17357.44 0.39
June 0.00 0.229311E+10 681928.09 0.00 0.00 0.00 0.00 8230.09 0.39
July 0.00 0.240212E+10 368492.91 0.00 0.00 0.00 0.00 1108.40 0.39
August 0.00 0.245321E+10 922060.19 0.00 7529900.15 0.00 0.00 7731.26 0.39
September 0.00 0.222643E+10 1069535.46 0.00 0.00 0.00 0.00 5891.68 0.39
October 0.00 0.191109E+10 567768.77 0.00 0.00 0.00 0.00 5201.75 0.39
November 667316.99 0.138960E+10 433760.68 3420101.39 3548201.59 456464.32 0.209386E+09 4889.23 0.39
December 1625277.80 0.759170E+09 17052.82 8886042.59 1443230.80 1159939.70 0.552408E+09 3470.05 0.39
                   
Annual Sum or Average 9655826.08 0.179303E+11 5759042.95 41308840.31 19844667.95 22494721.25 0.255758E+10 63624.39 0.39
Minimum of Months 0.00 0.481618E+09 17052.82 0.00 0.00 0.00 0.00 247.05 0.39
Maximum of Months 4204887.44 0.245321E+10 1248965.94 12234617.97 7529900.15 16483100.22 0.783569E+09 17357.44 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.524767E+10 0.337852E+10 0.00 17764173.66 0.194909E+10 0.00 0.157271E+11 0.00 3.91
February 0.271489E+10 0.411847E+10 0.00 16503116.94 0.178850E+10 0.00 0.114339E+11 0.00 3.91
March 0.308735E+10 0.810748E+10 0.00 15730038.41 0.219857E+10 0.00 0.987463E+10 0.00 3.91
April 0.359087E+09 0.970749E+10 0.00 11902379.78 0.235651E+10 0.00 0.359533E+10 0.00 3.90
May 0.00 0.222001E+11 0.00 1193802.14 0.311203E+10 0.00 55709036.06 0.00 3.90
June 0.00 0.303045E+11 0.00 0.00 0.335645E+10 0.00 0.00 0.00 3.88
July 0.00 0.333626E+11 0.00 0.00 0.353082E+10 0.00 0.00 0.00 3.85
August 0.00 0.326667E+11 0.00 0.00 0.436178E+10 0.00 0.00 0.00 3.86
September 0.00 0.294693E+11 0.00 0.00 0.398929E+10 0.00 0.00 0.00 3.84
October 73273.42 0.229885E+11 0.00 1466673.59 0.436175E+10 0.00 52483107.89 0.00 3.86
November 0.119894E+10 0.143025E+11 0.00 7090247.06 0.377774E+10 0.00 0.465192E+10 0.00 3.88
December 0.397068E+10 0.817123E+10 0.00 15024507.51 0.220165E+10 0.00 0.122521E+11 0.00 3.90
                   
Annual Sum or Average 0.165787E+11 0.218777E+12 0.00 86674939.09 0.369842E+11 0.00 0.576432E+11 0.00 3.88
Minimum of Months 0.00 0.337852E+10 0.00 0.00 0.178850E+10 0.00 0.00 0.00 3.84
Maximum of Months 0.524767E+10 0.333626E+11 0.00 17764173.66 0.436178E+10 0.00 0.157271E+11 0.00 3.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.403242E+10 0.426283E+10 0.00 22061747.21 0.107833E+10 0.00 0.169497E+11 0.00 3.92
February 0.209748E+10 0.487331E+10 0.00 20157569.86 0.104884E+10 0.00 0.120673E+11 0.00 3.92
March 0.260912E+10 0.899885E+10 0.00 19241143.90 0.134457E+10 0.00 0.103697E+11 0.00 3.93
April 0.257187E+09 0.105239E+11 0.00 13958990.04 0.158661E+10 0.00 0.371404E+10 0.00 3.92
May 0.00 0.231646E+11 0.00 1309136.77 0.229619E+10 0.00 56114647.68 0.00 3.92
June 0.00 0.316759E+11 0.00 0.00 0.227694E+10 0.00 0.00 0.00 3.92
July 0.00 0.349392E+11 0.00 0.00 0.223806E+10 0.00 0.00 0.00 3.89
August 0.00 0.342515E+11 0.00 0.00 0.303111E+10 0.00 0.00 0.00 3.89
September 0.00 0.306570E+11 0.00 0.00 0.302574E+10 0.00 0.00 0.00 3.87
October 73294.42 0.243908E+11 0.00 1631776.98 0.307893E+10 0.00 52538948.10 0.00 3.88
November 0.708419E+09 0.157578E+11 0.00 8798497.45 0.240159E+10 0.00 0.514493E+10 0.00 3.90
December 0.324548E+10 0.887065E+10 0.00 18598201.04 0.152819E+10 0.00 0.129835E+11 0.00 3.91
                   
Annual Sum or Average 0.129502E+11 0.232366E+12 0.00 0.105757E+09 0.249351E+11 0.00 0.613378E+11 0.00 3.91
Minimum of Months 0.00 0.426283E+10 0.00 0.00 0.104884E+10 0.00 0.00 0.00 3.87
Maximum of Months 0.403242E+10 0.349392E+11 0.00 22061747.21 0.307893E+10 0.00 0.169497E+11 0.00 3.93



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.583508E+10 0.00 74253586.11 0.00 0.00 0.179989E+11 0.00 12.29
February 0.00 0.635453E+10 0.00 61032990.30 0.00 0.00 0.116587E+11 0.00 12.38
March 0.00 0.107625E+11 0.00 53607862.72 0.00 0.00 0.110017E+11 0.00 12.49
April 0.00 0.129954E+11 0.00 23594683.53 0.00 0.00 0.320740E+10 0.00 12.66
May 0.00 0.270667E+11 0.00 1015871.32 0.00 0.00 37327998.48 0.00 12.77
June 0.00 0.361959E+11 0.00 0.00 0.00 0.00 0.00 0.00 12.82
July 0.00 0.397719E+11 0.00 0.00 0.00 0.00 0.00 0.00 12.77
August 0.00 0.396790E+11 0.00 0.00 0.00 0.00 0.00 0.00 12.71
September 0.00 0.359160E+11 0.00 0.00 0.00 0.00 0.00 0.00 12.71
October 0.00 0.289625E+11 0.00 1652465.36 0.00 0.00 38786461.25 0.00 12.63
November 0.00 0.193643E+11 0.00 27129251.99 0.00 0.00 0.489092E+10 0.00 12.47
December 0.00 0.107553E+11 0.00 56850618.85 0.00 0.00 0.138282E+11 0.00 12.27
                   
Annual Sum or Average 0.00 0.273659E+12 0.00 0.299137E+09 0.00 0.00 0.626620E+11 0.00 12.58
Minimum of Months 0.00 0.583508E+10 0.00 0.00 0.00 0.00 0.00 0.00 12.27
Maximum of Months 0.00 0.397719E+11 0.00 74253586.11 0.00 0.00 0.179989E+11 0.00 12.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.195012E+10 0.692506E+09 0.00 1254592.04 58846158.24 0.00 0.275377E+09 0.00 0.37
February 0.101070E+10 0.776559E+09 0.00 3658157.29 65934982.63 0.00 0.550523E+09 0.00 0.40
March 0.108301E+10 0.152109E+10 0.00 2285357.19 41267579.70 0.00 0.326672E+09 0.00 0.42
April 94303554.20 0.207025E+10 0.00 2451005.98 14354856.71 0.00 0.383255E+09 0.00 0.49
May 0.00 0.476175E+10 0.00 218556.68 7078042.84 0.00 8507062.76 0.00 0.58
June 0.00 0.703360E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.64
July 0.00 0.813146E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.67
August 0.00 0.757254E+10 0.00 0.00 3445898.22 0.00 0.00 0.00 0.62
September 0.00 0.710504E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.64
October 0.00 0.521238E+10 0.00 318195.76 3111430.05 0.00 8215613.19 0.00 0.58
November 0.435544E+09 0.315447E+10 0.00 993832.12 26376972.61 0.00 0.200071E+09 0.00 0.49
December 0.141392E+10 0.149114E+10 0.00 1453480.70 89503730.74 0.00 0.334322E+09 0.00 0.40
                   
Annual Sum or Average 0.598760E+10 0.495228E+11 0.00 12633177.77 0.309920E+09 0.00 0.208694E+10 0.00 0.53
Minimum of Months 0.00 0.692506E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.37
Maximum of Months 0.195012E+10 0.813146E+10 0.00 3658157.29 89503730.74 0.00 0.550523E+09 0.00 0.67



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:55:16

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.194528E+12 0.225633E+10 0.287390E+11 0.804909E+11 0.690025E+12
February 0.223402E+12 0.518810E+09 0.819421E+10 0.294567E+11 0.705548E+12
March 0.309937E+12 -0.134127E+10 -0.121412E+11 -0.352172E+11 0.861656E+12
April 0.330428E+12 -0.431386E+10 -0.531619E+11 -0.142354E+12 0.100245E+13
May 0.323473E+12 -0.105388E+11 -0.143678E+12 -0.385570E+12 0.127166E+13
June 0.281674E+12 -0.142280E+11 -0.197288E+12 -0.539373E+12 0.138147E+13
July 0.294940E+12 -0.152786E+11 -0.217016E+12 -0.580963E+12 0.147716E+13
August 0.325064E+12 -0.154589E+11 -0.216594E+12 -0.589412E+12 0.145615E+13
September 0.241030E+12 -0.139080E+11 -0.195599E+12 -0.528780E+12 0.140020E+13
October 0.231175E+12 -0.112352E+11 -0.153719E+12 -0.419585E+12 0.132583E+13
November 0.174010E+12 -0.587826E+10 -0.830220E+11 -0.215133E+12 0.105977E+13
December 0.191655E+12 -268002401.7 -0.376761E+10 -0.842085E+10 0.815302E+12
           
Annual Sum or Average 0.312132E+13 -0.896738E+11 -0.123905E+13 -0.333486E+13 0.134472E+14
Minimum of Months 0.174010E+12 -0.154589E+11 -0.217016E+12 -0.589412E+12 0.690025E+12
Maximum of Months 0.330428E+12 0.225633E+10 0.287390E+11 0.804909E+11 0.147716E+13