Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:54

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2023-10-16 08:54:28


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 9288.70 818.73 818.73
Net Site Energy 9044.62 797.21 797.21
Total Source Energy 20110.26 1772.56 1772.56
Net Source Energy 19337.25 1704.43 1704.43


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 273.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1246.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 455.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 150.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 390.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 624.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 74.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 95.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 2405.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 43.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4820.60 4468.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 273.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1246.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 455.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 150.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 21.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 366.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 624.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 74.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 95.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 2405.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 21.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 273.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1246.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 455.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 150.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 390.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 624.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 74.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 95.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 2405.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 43.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 53.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 179.50 236.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 192.00 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 424.90 393.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 53.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 179.50 236.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 192.00 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 424.90 393.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 254.558 5.28
Wind Power 0.000 0.00
Power Conversion -10.48 -0.2
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 244.083 5.06
     
Electricity Coming From Utility 4576.514 94.94
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4576.514 94.94
     
Total On-Site and Utility Electric Sources 4820.597 100.00
Total Electricity End Uses 4820.597 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 171.03 43.16
Air to Air Heat Recovery for Heating 225.29 56.84
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 396.32 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 582.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 7686.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionElectricityGeneratedPropaneMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:54
RunPeriod RUNPERIOD 1
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [m] 1186.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 6.2037 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 7.5557 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 7.5557 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 7.2603 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 3.7794 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.2151 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 7.7715 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.1806 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 4.4993 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.4132 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 7.7715 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 7.7715 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 12.1686 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 4.4993 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.5793 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.5793 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.2037 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 7.5557 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 7.5557 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 7.2603 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 3.7794 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.2151 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 7.7715 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.1806 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.4132 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.4132 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.4132 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.4132 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 4.4993 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.4132 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.4132 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.4132 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 7.7715 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 7.7715 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 12.1686 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 4.4993 18.58 0.0000  
Total 11345.29             5.5793 3.54 41.0437  
Conditioned Total 11345.29             5.5793 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.4264 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 25-JUL-19:10 26-DEC-19:10 - - - - - - - - - - 07-FEB-21:49
Heating 0.00 109021.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 127863.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 37630.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9571.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 86131.51 87619.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 19286.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 35369.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 3070.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3687.44 207045.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1342.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 332219.46 403686.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 109021.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 127863.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 37630.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9571.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56456.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 37635.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1216.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 17944.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 126.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 35369.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 3070.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3687.44 207045.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 431.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 670.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 296.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3948.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1442.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 476.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5220.66 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1236.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1976.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 237.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 301.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.38 2607.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 139.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 15266.83 4843.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 26.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 348.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 127.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 42.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 109.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 174.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 20.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 26.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 229.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1345.65 426.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 26.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 348.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 127.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 42.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 109.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 174.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 20.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 26.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 229.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1345.65 426.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.47 0.610083 0.519000 1.28 1.00 0.500000 0.000625 0.000128 1.28 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.318641 0.160395 0.373000 0.118853 0.444313 0.500000 0.002375 0.000060 0.118853 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.242775 0.243780 0.567000 0.137653 0.650081 0.500000 0.001563 0.000031 0.137653 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.259455 0.482370 0.010000 0.002595 1.00 0.500000 0.000790 0.000041 0.075197 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.125955 0.573273 0.688000 0.086657 1.00 0.500000 0.000665 0.000030 0.086657 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.76 0.015803 0.010000 0.037630 0.300000 0.500000 0.024109 0.000055 0.101177 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.47 0.097854 0.690000 1.01 0.690000 0.500000 0.003894 0.000219 1.01 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.05 0.197327 0.562000 2.84 0.562000 0.500000 0.001931 0.000574 2.84 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.31 0.907810 0.545000 0.712554 1.00 0.500000 0.000420 0.000233 0.712554 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.44 0.103663 0.731000 1.78 0.731000 0.500000 0.003675 0.000293 1.78 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.56 0.098744 0.696000 1.78 0.696000 0.500000 0.003858 0.000295 1.78 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.49 0.056920 0.222000 0.552212 0.300000 0.500000 0.012039 0.000099 0.552212 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.765111 0.410449 0.246000 0.188217 1.00 0.500000 0.000928 0.000152 0.279227 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 5873.90 0.000128 169.60
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2741.01 0.000060 109.40
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1421.07 0.000031 45.84
MECH_FLR_1 VAV BOX REHEAT COIL 1865.46 0.000041 77.30
STORAGE_FLR_1 VAV BOX REHEAT COIL 1359.58 0.000030 47.68
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 2509.99 0.000055 104.00
CAFE_FLR_1 VAV BOX REHEAT COIL 10020.44 0.000219 320.30
LOBBY_FLR_1 VAV BOX REHEAT COIL 26244.05 0.000574 828.19
ROOM_1_FLR_3 FAN COIL HEATING COIL 4564.95 0.000100 206.15
ROOM_2_FLR_3 FAN COIL HEATING COIL 4563.04 0.000100 206.06
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 26189.74 0.000573 1182.68
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 26165.52 0.000572 1181.59
ROOM_5_FLR_3 FAN COIL HEATING COIL 4561.73 0.000100 206.00
ROOM_6_FLR_3 FAN COIL HEATING COIL 4559.82 0.000100 205.92
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 10656.42 0.000233 369.71
ROOM_1_FLR_6 FAN COIL HEATING COIL 1457.16 0.000032 65.80
ROOM_2_FLR_6 FAN COIL HEATING COIL 1456.88 0.000032 65.79
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 7053.31 0.000154 318.49
BANQUET_FLR_6 VAV BOX REHEAT COIL 13402.89 0.000293 408.81
DINING_FLR_6 VAV BOX REHEAT COIL 13508.23 0.000295 412.52
KITCHEN_FLR_6 VAV BOX REHEAT COIL 4505.89 0.000099 139.16
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6927.81 0.000152 287.08
VAV WITH REHEAT HEATING COIL 159606.82 0.003491 3418.55
FLR_3_DOAS HEATING COIL 14143.00 0.000309 302.92
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.973293 0.000100 0.000270
ROOM_2_FLR_3 FAN COIL 0.966287 0.000100 0.000268
ROOM_3_MULT19_FLR_3 FAN COIL 5.61 0.000573 0.001534
ROOM_4_MULT19_FLR_3 FAN COIL 6.28 0.000572 0.001825
ROOM_5_FLR_3 FAN COIL 0.864623 0.000100 0.000240
ROOM_6_FLR_3 FAN COIL 0.858829 0.000100 0.000239
ROOM_1_FLR_6 FAN COIL 0.259882 0.000032 0.000072
ROOM_2_FLR_6 FAN COIL 0.257708 0.000032 0.000071
ROOM_3_MULT9_FLR_6 FAN COIL 1.18 0.000154 0.000335
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 0.973293
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 0.966287
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.61
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.28
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.864623
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.858829
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.259882
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.257708
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.18
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008551 12.80 0.008500 0.000270 0.973293  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008551 12.80 0.008500 0.000268 0.966287  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008468 12.80 0.008468 0.001534 5.61  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008725 12.80 0.008500 0.001825 6.28  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008557 12.80 0.008500 0.000240 0.864623  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008557 12.80 0.008500 0.000239 0.858829  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.77 6.70 0.008548 12.80 0.008500 0.000072 0.259882  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.77 6.70 0.008548 12.80 0.008500 0.000071 0.257708  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.77 6.70 0.008626 12.80 0.008500 0.000335 1.18  
VAV WITH REHEAT COOLING COIL 29.68 6.70 0.008573 10.70 0.008500 0.013520 23.15 472740.67
FLR_3_DOAS COOLING COIL 38.10 6.70 0.006871 11.79 0.006871 0.001640 2.05 57348.72
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 13.43 10.54 23.26 10.54 23.15 23.15 0.300000 0.455145 23.15
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 23.15  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 9.33
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 23.15
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.013520 0.000035
VAV WITH REHEAT_HEATC_CONTROLLER 0.003491  
FLR_3_DOAS_COOLC_CONTROLLER 0.001640 0.000290
FLR_3_DOAS_HEATC_CONTROLLER 0.000309  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.020014 3235.39  
HEATSYS1 PUMP 0.007773 2317.85 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.007773 0.932818
COOLSYS1 0.020014 2.40
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 355358.74 355358.74 0.007773
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.020014 2239.97
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.020014 699808.53 700444.74 79.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.30 11.20 6.80 8.10 10.30 12.50 19.20 23.80 27.90 27.50 26.30 23.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 El Paso International Ap Ut TX USA TMY3 WMO#=722700 31.77 -106.50 -7.00 1186.00 87865 1.0443


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 17.94 21.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 6.204 5.380 0.000 0.000 0.000 0.000 11.584 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 7.556 10.760 0.000 0.000 0.000 0.000 18.316 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 7.556 10.760 0.000 0.000 0.000 0.000 18.316 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 7.260 5.380 0.000 0.000 0.000 0.000 12.640 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 3.779 2.690 0.000 0.000 0.000 0.000 6.469 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.215 61.680 535.850 0.000 0.000 0.000 602.745 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 7.772 5.380 0.000 0.000 0.000 0.000 13.152 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.181 8.070 0.000 0.000 0.000 0.000 16.251 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 4.499 0.000 0.000 0.000 0.000 0.000 4.499 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 7.772 67.820 0.000 0.000 0.000 0.000 75.592 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 7.772 67.820 0.000 0.000 0.000 0.000 75.592 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 12.169 512.243 2419.260 0.000 0.000 0.000 2943.672 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 4.499 0.000 0.000 0.000 0.000 0.000 4.499 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 12276.143 6.204 115.270 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 12276.143
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 506.769 7.556 46.797 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 506.769
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 586.840 7.556 46.797 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 586.840
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1192.447 7.260 449.641 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1192.447
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 358.135 3.779 175.557 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 358.135
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 406.984 5.215 48.451 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 406.984
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1467.746 7.772 10.314 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1467.746
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 10701.700 8.181 25.333 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10701.700
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 108.229 4.413 72.152 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.229
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1752.054 4.499 83.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1752.054
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 2577.487 7.772 10.314 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2577.487
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 2577.487 7.772 10.314 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2577.487
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1257.069 12.169 56.528 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1257.069
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1854.278 4.499 83.601 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1854.278


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.9589 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.167 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.181 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.021 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.034 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.3181 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.3181 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8756
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6894
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6793
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8120
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7993
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.883
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.883
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.56372661E-17 0.35603042E-16 -0.14834456E-09 -0.22354951E-17
29 8 0.21681598E-07 0.12895413E-12 0.37576420E-03 -0.24652724E-09
30 7 -0.12181032E-01 0.67087143E-08 -0.22998674E-01 0.13850277E-03
31 6 0.40370585 0.23395349E-05 0.47069069 -0.47283774E-02
32 5 -5.1745154 0.87537405E-04 -4.4305073 0.62984858E-01
33 4 32.931872 0.71743813E-03 21.398312 -0.42118042
34 3 -111.07522 0.15662534E-02 -55.540939 1.5130129
35 2 196.98158 0.88235367E-03 77.798628 -2.8983416
36 1 -171.10930 0.94326468E-04 -55.232514 2.7446195
37 0 57.057407 0.53780718E-06 15.562302  
38 9 0.13788181E-14 0.42316407E-16 -0.13850765E-09 -0.36591458E-17
39 8 0.20295421E-07 0.15509090E-12 0.36099725E-03 -0.23076592E-09
40 7 -0.11739701E-01 0.81955471E-08 -0.22363010E-01 0.13348467E-03
41 6 0.39171309 0.28760220E-05 0.46045976 -0.45870120E-02
42 5 -5.0574682 0.10819265E-03 -4.3518524 0.61533536E-01
43 4 32.414067 0.89103805E-03 21.090697 -0.41430552
44 3 -109.97331 0.19536482E-02 -54.932704 1.4970936
45 2 195.88922 0.11048200E-02 77.241099 -2.8809953
46 1 -170.70571 0.11852782E-03 -55.070977 2.7375462
47 0 57.057407 0.67841551E-06 15.589460  
48 9 0.13857471E-14 0.43057560E-16 -0.13784678E-09 -0.68945926E-17
49 8 0.20202246E-07 0.15680163E-12 0.35999259E-03 -0.22970649E-09
50 7 -0.11709634E-01 0.82948599E-08 -0.22319691E-01 0.13314280E-03
51 6 0.39089600 0.29121450E-05 0.45976168 -0.45773805E-02
52 5 -5.0494928 0.10959277E-03 -4.3464810 0.61434646E-01
53 4 32.378781 0.90287364E-03 21.069680 -0.41383702
54 3 -109.89821 0.19801908E-02 -54.891143 1.4960086
55 2 195.81476 0.11201274E-02 77.203021 -2.8798128
56 1 -170.67819 0.12019965E-03 -55.059979 2.7370639
57 0 57.057407 0.68811227E-06 15.591337  
58 9 0.14302076E-15 0.35792568E-16 -0.14541430E-09 -0.27421543E-17
59 8 0.21269444E-07 0.13686051E-12 0.37140784E-03 -0.24184090E-09
60 7 -0.12050952E-01 0.71525680E-08 -0.22811354E-01 0.13702371E-03
61 6 0.40017121 0.24988627E-05 0.46767819 -0.46867126E-02
62 5 -5.1400200 0.93645327E-04 -4.4073602 0.62557131E-01
63 4 32.779281 0.76858103E-03 21.307814 -0.41915444
64 3 -110.75053 0.16800125E-02 -55.362013 1.5083221
65 2 196.65975 0.94749847E-03 77.634567 -2.8932310
66 1 -170.99041 0.10139533E-03 -55.184883 2.7425359
67 0 57.057407 0.57877233E-06 15.570231  
68 9 0.33566835E-16 0.35384250E-16 -0.14478218E-09 -0.87565041E-18
69 8 0.21180494E-07 0.13854999E-12 0.37046393E-03 -0.24082951E-09
70 7 -0.12022754E-01 0.72481687E-08 -0.22770744E-01 0.13670309E-03
71 6 0.39940498 0.25332696E-05 0.46702484 -0.46776806E-02
72 5 -5.1325420 0.94967185E-04 -4.4023386 0.62464408E-01
73 4 32.746200 0.77967008E-03 21.288178 -0.41871522
74 3 -110.68014 0.17047184E-02 -55.323188 1.5073051
75 2 196.58997 0.96166638E-03 77.598974 -2.8921229
76 1 -170.96463 0.10293464E-03 -55.174560 2.7420841
77 0 57.057407 0.58770932E-06 15.571958  
78 7 -0.11407965E-14 0.23474115E-16 -0.22119674E-13 0.51962024E-15
79 6 0.16676876E-10 0.39440661E-11 0.52102403E-09 -0.18553030E-10
80 5 -0.80001662E-07 0.19215958E-07 -0.21848785E-05 0.17095694E-06
81 4 0.10228101E-03 0.72538432E-05 0.17630655E-02 -0.28160064E-03
82 3 -0.15120274E-01 0.25611913E-03 -0.21515117 0.43248511E-01
83 2 0.21482172 0.11124906E-02 2.8969963 -0.61829830
84 1 -0.54366453 0.69706713E-03 -7.1337069 1.5687761
85 0 0.34594624 0.12518961E-04 4.4521846  
86 7 -0.22119674E-13 0.23474115E-16 -0.11407965E-14 0.51962024E-15
87 6 0.52102403E-09 0.39440661E-11 0.16676876E-10 -0.18553030E-10
88 5 -0.21848785E-05 0.19215958E-07 -0.80001662E-07 0.17095694E-06
89 4 0.17630655E-02 0.72538432E-05 0.10228101E-03 -0.28160064E-03
90 3 -0.21515117 0.25611913E-03 -0.15120274E-01 0.43248511E-01
91 2 2.8969963 0.11124906E-02 0.21482172 -0.61829830
92 1 -7.1337069 0.69706713E-03 -0.54366453 1.5687761
93 0 4.4521846 0.12518961E-04 0.34594624  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.248_SHGC_0.21 37 1 VerySmooth 1.408 1.408 1.000 0.210    
2 RESWINDOW_U_0.248_SHGC_0.21 38 1 VerySmooth 1.408 1.408 1.000 0.210    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   4.57814E-002 0.12126 0.67915 0.67915 0.29000 0.15345 0.21878 0.00000 0.84000 0.84000 8.56546E-002 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   4.57814E-002 0.12126 0.67915 0.67915 0.29000 0.15345 0.21878 0.00000 0.84000 0.84000 8.56546E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.680 0.5995
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.312 3.5001E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.4941E-002
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.2891E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1053
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.6651E-002
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 7.2346E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.7154E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.9121E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 9.7843E-003
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1074
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.2391E-002
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1193
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.6948E-002
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 8.0053E-002
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.4112E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 3.2628E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.3264E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.2897E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.3310E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.7621E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0040E-002
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.6786E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.8096E-003
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8610E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0256E-002
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.2897E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.3310E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.7621E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0040E-002
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.6786E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.8096E-003
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8610E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0256E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 29501.28407 29501.28407 2.47158 2.47158 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 30.43000 6.85931E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 3803.06105 3803.06105 0.31864 0.31864 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 37.99167 6.87130E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2197.30494 2197.30494 0.10859 0.10859 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 2897.48666 2897.48666 0.24277 0.24277 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 35.41333 6.86719E-003 77.66889 12.54000 9.17335E-002 0.00000
6 RETAIL_2_FLR_1 Heating 791.33917 791.33917 3.91098E-002 9.17335E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 77.66889 12.54000 9.17335E-002 0.00000
7 MECH_FLR_1 Cooling 3097.29727 3097.29727 0.25946 0.25946 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 33.35500 6.86391E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1521.51899 1521.51899 7.51967E-002 7.51967E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1503.59725 1503.59725 0.12595 0.12595 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 35.84667 6.86787E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 963.18964 963.18964 4.76029E-002 5.77652E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44917.13755 44917.13755 3.76297 3.76297 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 36.97333 6.86968E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2047.26807 2047.26807 0.10118 0.10118 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 17537.20464 17537.20464 1.47069 1.47069 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 37.99167 6.87130E-003 188.86188 142.30000 0.67638 0.00000
14 CAFE_FLR_1 Heating 5377.77554 5377.77554 0.26578 0.67638 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 188.86188 142.30000 0.67638 0.00000
15 LOBBY_FLR_1 Cooling 60273.30499 60273.30499 5.05170 5.05170 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 13255.80517 13255.80517 0.65513 1.89399 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 8621.75368 8621.75368 0.97329 0.97329 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 4565.03298 4565.03298 0.22693 0.22693 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 8559.69215 8559.69215 0.96629 0.96629 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 36.45333 6.86884E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 4563.12153 4563.12153 0.22684 0.22684 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 49682.09148 49682.09148 5.60830 5.60830 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 26189.96497 26189.96497 1.30196 1.30196 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 55652.15018 55652.15018 6.28274 6.28274 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 37.71000 6.87086E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 26165.73985 26165.73985 1.30076 1.30076 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 7659.12188 7659.12188 0.86462 0.86462 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 33.48500 6.86412E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 4561.81275 4561.81275 0.22677 0.22677 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 7607.79689 7607.79689 0.85883 0.85883 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 33.16000 6.86360E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 4559.90101 4559.90101 0.22668 0.22668 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 15606.33015 15606.33015 1.30744 1.30744 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 37.84000 6.87107E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 7395.95981 7395.95981 0.36553 0.47476 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2302.11927 2302.11927 0.25988 0.25988 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 36.80000 6.86940E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1457.18868 1457.18868 7.24380E-002 7.24380E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2282.86408 2282.86408 0.25771 0.25771 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1456.90781 1456.90781 7.24240E-002 7.24240E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 10478.14474 10478.14474 1.18289 1.18289 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 7053.41036 7053.41036 0.35063 0.35063 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29062.31267 29062.31267 2.43794 2.43794 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38.10000 6.87148E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 5246.98904 5246.98904 0.25932 1.18780 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30510.41339 30510.41339 2.55937 2.55937 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38.10000 6.87148E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 5356.07626 5356.07626 0.26471 1.18780 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 29610.36975 29610.36975 2.48744 2.48744 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 36.93000 6.86961E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1984.47812 1984.47812 9.80654E-002 0.36735 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -5.20000 2.80840E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 9132.92265 9132.92265 0.76511 0.76511 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 38.10000 6.87148E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 5649.80852 5649.80852 0.27923 0.27923 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 409953.10 23.14956 23.14956 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 169060.66 7.35623 7.35623 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00
3 FLR_3_DOAS Cooling Sensible 54460.49 16.83519 2.05125 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 47141.68 4.00543 2.05125 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.47158
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.61008
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51900
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.28275
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.24505E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.28492E-004
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.28275
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5873.89653
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.28492E-004
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 169.59851
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.31864
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16039
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.37300
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11885
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44431
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.37539E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.99596E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11885
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2741.00853
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.99596E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 109.40384
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24277
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24378
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.56700
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13765
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65008
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.56288E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.10860E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13765
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1421.07063
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.10860E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 45.84212
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.25946
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.48237
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.59455E-003
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.89850E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.08070E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.51967E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1865.46090
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.08070E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 77.29630
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.12595
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.57327
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.68800
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.66569E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.64604E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.97409E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.66569E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1359.58373
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.97409E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 47.67609
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.76297
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.58030E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.76297E-002
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.41094E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.49061E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10118
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2509.99138
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.49061E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 104.00305
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.47069
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.78537E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69000
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.01478
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69000
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.89357E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.19198E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.01478
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10020.44459
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.19198E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 320.30121
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.05170
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19733
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.56200
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.83905
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56200
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.93080E-003
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.74089E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.83905
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 26244.04724
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.74089E-004
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 828.19093
113 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
114 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.97329
115 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.97329
116 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.98585E-005
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.69927E-004
118 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77084
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55097E-003
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.69927E-004
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.97329
125 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4564.95245
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.98585E-005
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 206.14985
128 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
129 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.96629
130 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.96629
131 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.98166E-005
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.68010E-004
133 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77084
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55133E-003
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.68010E-004
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.96629
140 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4563.04103
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.98166E-005
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 206.06356
143 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
144 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.60830
145 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.60830
146 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.72901E-004
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.53365E-003
148 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77126
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.46799E-003
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.46799E-003
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.53365E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.60830
155 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 26189.74236
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.72901E-004
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1182.68464
158 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
159 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.28274
160 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.28274
161 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.72371E-004
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.82541E-003
163 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77026
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.72524E-003
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.82541E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.28274
170 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 26165.51742
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.72371E-004
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1181.59119
173 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
174 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.86462
175 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.86462
176 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.97880E-005
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.40155E-004
178 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77083
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55656E-003
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.40155E-004
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.86462
185 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4561.73228
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.97880E-005
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 206.00449
188 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
189 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.85883
190 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.85883
191 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.97462E-005
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.38566E-004
193 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77083
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55686E-003
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.38566E-004
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.85883
200 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4559.82057
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.97462E-005
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 205.91819
203 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30744
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.90781
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54500
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.71255
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.19691E-004
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.33110E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71255
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
214 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10656.42170
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.33110E-004
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 369.71498
217 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
218 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.25988
219 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.25988
220 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.18755E-005
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.20112E-005
222 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77085
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54779E-003
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.20112E-005
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.25988
229 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1457.16383
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.18755E-005
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 65.79888
232 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
233 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.25771
234 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.25771
235 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.18694E-005
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.14166E-005
237 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77085
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54819E-003
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.14166E-005
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.25771
244 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1456.88296
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.18694E-005
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 65.78620
247 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
248 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.18289
249 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.18289
250 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.54291E-004
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.34803E-004
252 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77048
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.62626E-003
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.34803E-004
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.18289
259 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7053.31412
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.54291E-004
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 318.49162
262 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.43794
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10366
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.73100
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78213
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.73100
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.67539E-003
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.93189E-004
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78213
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
273 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13402.89235
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.93189E-004
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 408.80865
276 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.55937
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.87443E-002
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69600
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78132
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69600
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.85845E-003
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.95493E-004
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78132
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
287 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13508.22704
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.95493E-004
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 412.52041
290 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.48744
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 5.69196E-002
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22200
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.55221
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.20394E-002
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.85665E-005
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.55221
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
301 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4505.89170
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.85665E-005
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 139.15799
304 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.76511
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.41045
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24600
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18822
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.28252E-004
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.51546E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27923
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
315 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6927.81488
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.51546E-004
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 287.07651
318 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 13.43371
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 10.53641
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 23.26106
321 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 10.53641
322 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 23.14956
323 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 23.14956
324 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
325 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.45515
326 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
333 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
334 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 23.14956
335 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
336 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 23.14956
337 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 9.32920
338 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 29.67517
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.69814
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57259E-003
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 472740.66553
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.35203E-002
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 23.14956
346 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 159606.82299
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.49140E-003
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 3418.55428
349 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 23.14956
350 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.35203E-002
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.52203E-005
352 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.49140E-003
353 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
355 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
356 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 38.10000
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.79311
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 6.87148E-003
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 6.87148E-003
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 57348.72296
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.64017E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
364 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 14143.00265
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.09379E-004
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 302.92328
367 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
368 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.64017E-003
369 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.90331E-004
370 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.09379E-004
371 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.00144E-002
372 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 3235.39180
373 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 7.77348E-003
374 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.93282
375 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 7.77348E-003
376 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 2317.85300
377 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
378 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 355358.74383
379 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 355358.74000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 7.77348E-003
381 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.00144E-002
382 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.40173
383 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.00144E-002
384 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 2239.97087
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.00144E-002
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 699808.53080
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 700444.74000
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 79.85070
389 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
390 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
391 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
392 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
393 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 8921.21
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4162.94
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 2156.90
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2832.73
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 2066.30
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 3811.46
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 15210.78
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 39839.82
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 7724.66
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 7721.43
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 44317.15
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 44276.17
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 7719.22
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 7715.98
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 16196.62
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 2465.65
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 2465.17
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 11934.75
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 20349.43
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 20509.23
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 6840.83
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 10519.99
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 161150.05
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 14279.75


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 10533.19 8343.99 2189.21 0.79 889.78 9.02
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 10458.25 8284.48 2173.78 0.79 883.46 8.96
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 65772.92 53105.64 12667.28 0.81 6417.34 65.09
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 70772.60 55588.21 15184.40 0.79 6018.48 61.04
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 9369.49 7420.10 1949.39 0.79 791.65 8.03
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 9307.38 7370.79 1936.58 0.79 786.41 7.98
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 2810.38 2226.63 583.76 0.79 237.37 2.41
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 2787.14 2208.17 578.97 0.79 235.42 2.39
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 13028.48 10282.54 2745.94 0.79 1103.74 11.19
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 592033.51 374529.19 217504.31 0.63 122666.65 1244.15
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 49472.21 31519.61 17952.61 0.64 5383.03 54.60


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 4.12 14.07


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.248_SHGC_0.21 N/A 1.408 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.6639903430E-002 2.1878976067E-002 Pass Pass 6.6133219050E-003 1.8806394324E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 4.2576061165E-002 6.9637788607E-002 Pass Pass 1.6787613514E-002 2.4435290505E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.3093142117E-002 2.7142680603E-002 Pass Pass 7.5540526575E-003 1.9997878036E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.5247823674E-002 1.6082561473E-002 Pass Pass 3.6252564901E-002 0.2454290472 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 6.9026668540E-003 8.8880199914E-003 Pass Pass 1.1563791296E-002 2.3631039114E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 2.0082888857E-004 3.5395790974E-004 Pass Pass 2.0485651625E-002 5.9620101616E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 6.2589134849E-002 7.6813243151E-002 Pass Pass 1.0574886278E-002 1.8024805511E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 3.4421253507E-002 4.1689944178E-002 Pass Pass 7.9624759226E-003 1.8665184770E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 6.3600498817E-002 0.2047818707 Pass Pass 0.1817430916 0.4478858155 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 4.7720713512E-002 0.1665047793 Pass Pass 0.1512746100 0.3284135518 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.1001078532E-003 1.3167898343E-002 Pass Pass 7.2800585249E-002 0.1427972493 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.6306692688E-002 0.1355340167 Pass Pass 2.3967607683 27.2430454137 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 6.4987908592E-002 0.2159918295 Pass Pass 0.1622819260 0.3219206738 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 2.4732353529E-002 6.2140615992E-002 Pass Pass 0.1550538940 0.4673868065 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 1.0470589406E-002 1.0500453022E-002 Pass Pass 7.6600024150E-003 2.1644766605E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 5.6654333357E-002 0.1817877524 Pass Pass 0.1274250726 0.2722476810 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 5.4682882631E-002 0.1707544405 Pass Pass 0.3617404676 1.8113562799 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 8.2515596963E-002 0.2643532609 Pass Pass 0.2379010582 1.4956073668 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 5.2528979948E-002 0.1001260726 Pass Pass 9.9798164122E-003 2.3039299066E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 5.1713187426E-002 9.7050500763E-002 Pass Pass 9.4510174329E-003 2.1454859860E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 1.1441703936E-003 1.9002950793E-003 Pass Pass 2.2453955440E-002 4.3212777218E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 2.0092520148E-002 1.9374879866E-002 Pass Pass 7.8932703958E-003 1.8659050077E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3169.21 71.40 845.18 3143.38 5535.12 12764.31



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB -5.20 0.00 -5.20 Wetbulb [C] 2.20 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 38.10 13.00 18.10 Wetbulb [C] 3.90 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 6      
Feb 3.00 4      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 18.00 7      
Jul 27.00 16      
Aug 41.00 15      
Sep 0.00 0      
Oct 23.00 18      
Nov 0.00 0      
Dec 7.00 7      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.886 1.021 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.886 1.021 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.886 1.021 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.886 1.021 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.896 1.034 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.896 1.034 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.896 1.034 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.896 1.034 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.896 1.034 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.004 1.181 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.293 0.318 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.293 0.318 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.293 0.318 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.293 0.318 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.293 0.318 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.293 0.318 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.293 0.318 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.293 0.318 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.293 0.318 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.293 0.318 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.298 0.318 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.288 0.318 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.288 0.318 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.288 0.318 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.298 0.318 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.298 0.318 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.298 0.318 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   23.26 0.00 0.00 23.26 23.26 1.408 0.210 0.290             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   65.50 0.00 0.00 65.50 65.50 1.408 0.210 0.290             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   85.08 0.00 0.00 85.08 85.08 1.408 0.210 0.290             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 18.40 1.408 0.210 0.290             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 34.34 1.408 0.210 0.290             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 18.40 1.408 0.210 0.290             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 34.34 1.408 0.210 0.290             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   3.68 0.00 0.00 3.68 279.56 1.408 0.210 0.290             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   3.68 0.00 0.00 3.68 279.65 1.408 0.210 0.290             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 34.34 1.408 0.210 0.290             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 18.40 1.408 0.210 0.290             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 18.40 1.408 0.210 0.290             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 34.34 1.408 0.210 0.290             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   5.82 0.00 0.00 5.82 23.30 1.408 0.210 0.290             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   2.15 0.00 0.00 2.15 8.59 1.408 0.210 0.290             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   2.15 0.00 0.00 2.15 8.58 1.408 0.210 0.290             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   5.82 0.00 0.00 5.82 23.30 1.408 0.210 0.290             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 4.60 1.408 0.210 0.290             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 8.58 1.408 0.210 0.290             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 4.60 1.408 0.210 0.290             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.248_SHGC_0.21   8.58 0.00 0.00 8.58 8.58 1.408 0.210 0.290             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.248_SHGC_0.21   6.74 0.00 0.00 6.74 60.70 1.408 0.210 0.290             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   32.19 0.00 0.00 32.19 32.19 1.408 0.210 0.290             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   32.19 0.00 0.00 32.19 32.19 1.408 0.210 0.290             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 4.60 1.408 0.210 0.290             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   17.17 0.00 0.00 17.17 17.17 1.408 0.210 0.290             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   4.60 0.00 0.00 4.60 4.60 1.408 0.210 0.290             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   5.82 0.00 0.00 5.82 5.82 1.408 0.210 0.290             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   5.21 0.00 0.00 5.21 5.21 1.408 0.210 0.290             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.248_SHGC_0.21   17.17 0.00 0.00 17.17 17.17 1.408 0.210 0.290             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 1.408 0.210 0.290                      
North Total or Average             432.95 1.408 0.210 0.290                      
Non-North Total or Average             780.84 1.408 0.210 0.290                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.2037 1978.83 12276.14 LightsWired LTG_SCH_BASEMENT 40.17 168.00 40.12 0.0000 Y 92.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 7.5557 67.07 506.77 LightsWired LTG_SCH_RETAIL 44.04 168.00 43.99 0.0000 Y 4.18
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 7.5557 77.67 586.84 LightsWired LTG_SCH_RETAIL 44.04 168.00 43.99 0.0000 Y 4.85
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 7.2603 164.24 1192.45 LightsWired LTG_SCH_MECHANIC 38.78 168.00 38.73 0.0000 Y 8.67
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 3.7794 94.76 358.14 LightsWired LTG_SCH_STORAGE 29.59 168.00 29.56 0.0000 Y 1.99
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.2151 78.04 406.98 LightsWired LTG_SCH_LAUNDRY 48.47 168.00 48.41 0.0000 Y 3.70
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 7.7715 188.86 1467.75 LightsWired LTG_SCH_DINING 36.01 168.00 24.26 0.0000 Y 6.68
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.1806 1308.19 10701.70 LightsWired LTG_SCH_LOBBY 41.54 168.00 39.20 0.0000 Y 78.74
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.4132 1863.81 8225.38 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.78
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.4132 1864.32 8227.62 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.79
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 4.4993 1557.62 7008.22 LightsWired LTG_SCH_CORRIDOR 41.54 168.00 41.50 0.0000 Y 54.59
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.4132 39.02 172.21 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.4132 39.02 172.19 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.4132 220.77 974.32 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 6.96
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 7.7715 331.66 2577.49 LightsWired LTG_SCH_DINING 36.01 168.00 30.23 0.0000 Y 14.63
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 7.7715 331.66 2577.49 LightsWired LTG_SCH_DINING 36.01 168.00 30.23 0.0000 Y 14.63
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 12.1686 103.30 1257.07 LightsWired LTG_SCH_KITCHEN 38.78 168.00 38.73 0.0000 Y 9.14
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 4.4993 412.12 1854.28 LightsWired LTG_SCH_CORRIDOR 41.54 168.00 41.50 0.0000 Y 14.44
Interior Lighting Total       5.5793 11345.29 63298.26               277.46


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10701.70 749.12
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10701.70 749.12
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1467.75 572.42
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1467.75 572.42
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2577.49 515.50
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2577.49 515.50
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2577.49 515.50
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2577.49 515.50


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 9571.94 AstronomicalClock -   83.77 83.77 150.51
Exterior Lighting Total 9571.94           150.51



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 355358.74 0.90        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 700444.74 3.11 700567.86 3.11 4.12 14.07


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9438.21 10533.19 8343.99 2189.21 0.79 - 889.78 9.02
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9371.19 10458.25 8284.48 2173.78 0.79 - 883.46 8.96
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 53625.39 65772.92 53105.64 12667.28 0.81 - 6417.34 65.09
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 63826.89 70772.60 55588.21 15184.40 0.79 - 6018.48 61.04
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8397.22 9369.49 7420.10 1949.39 0.79 - 791.65 8.03
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8341.65 9307.38 7370.79 1936.58 0.79 - 786.41 7.98
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2517.93 2810.38 2226.63 583.76 0.79 - 237.37 2.41
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2497.14 2787.14 2208.17 578.97 0.79 - 235.42 2.39
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 11706.68 13028.48 10282.54 2745.94 0.79 - 1103.74 11.19
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 472740.67 592033.51 374529.19 217504.31 0.63 - 122666.65 1244.15
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 57348.72 49472.21 31519.61 17952.61 0.64 - 5383.03 54.60
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 5873.90 8921.21 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2741.01 4162.94 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1421.07 2156.90 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1865.46 2832.73 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1359.58 2066.30 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2509.99 3811.46 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10020.44 15210.78 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 26244.05 39839.82 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4564.95 7724.66 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4563.04 7721.43 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 26189.74 44317.15 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 26165.52 44276.17 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4561.73 7719.22 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4559.82 7715.98 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 10656.42 16196.62 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1457.16 2465.65 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1456.88 2465.17 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 7053.31 11934.75 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13402.89 20349.43 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13508.23 20509.23 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 4505.89 6840.83 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6927.81 10519.99 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 159606.82 161150.05 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 14143.00 14279.75 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.24 0.00 0.00 1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.97 684.84 703.64 1.00 1.20 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.97 679.91 703.64 1.00 1.21 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.61 3946.20 703.64 1.00 0.96 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.28 4420.77 703.64 1.00 0.96 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.86 608.38 703.64 1.00 1.23 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.86 604.30 703.64 1.00 1.24 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.26 182.86 703.64 1.00 1.82 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.26 181.33 703.64 1.00 1.83 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.18 832.33 703.64 1.00 1.16 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 23.15 51869.79 2240.64 1.00 1.11 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.020014 3235.39 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.007773 2317.85 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.020014 2239.97 111917.77 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.95 0.68 0.60
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.95 0.31 0.04



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 29501.28 29501.28 14.91 2.472 2.472 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 24.00 24.00 0.00932 30.43 0.00686 0.854 0.00
RETAIL_1_FLR_1 3803.06 3803.06 56.70 0.319 0.319 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00908 37.99 0.00687 0.079 0.00
RETAIL_2_FLR_1 2897.49 2897.49 37.31 0.243 0.243 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 24.00 24.00 0.00944 35.41 0.00687 0.092 0.00
MECH_FLR_1 3097.30 3097.30 18.86 0.259 0.259 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 24.00 24.00 0.00864 33.36 0.00686 0.000 0.00
STORAGE_FLR_1 1503.60 1503.60 15.87 0.126 0.126 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00874 35.85 0.00687 0.058 0.00
LAUNDRY_FLR_1 44917.14 44917.14 575.57 3.763 3.763 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 24.00 24.00 0.00854 36.97 0.00687 0.000 0.00
CAFE_FLR_1 17537.20 17537.20 92.86 1.471 1.471 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 23.99 0.01029 37.99 0.00687 0.676 0.00
LOBBY_FLR_1 60273.30 60273.30 46.07 5.052 5.052 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.01005 38.10 0.00687 1.894 0.00
ROOM_1_FLR_3 8621.75 8621.75 220.95 0.973 0.973 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00855 36.63 0.00687 0.062 0.00
ROOM_2_FLR_3 8559.69 8559.69 219.38 0.966 0.966 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 21.11 21.11 0.00855 36.45 0.00687 0.062 0.00
ROOM_3_MULT19_FLR_3 49682.09 49682.09 2025.87 5.608 5.608 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00847 38.10 0.00687 0.837 0.00
ROOM_4_MULT19_FLR_3 55652.15 55652.15 2268.69 6.283 6.283 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 21.11 21.11 0.00873 37.71 0.00687 0.837 0.00
ROOM_5_FLR_3 7659.12 7659.12 196.28 0.865 0.865 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00856 33.48 0.00686 0.062 0.00
ROOM_6_FLR_3 7607.80 7607.80 194.98 0.859 0.859 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00856 33.16 0.00686 0.062 0.00
CORRIDOR_FLR_3 15606.33 15606.33 40.08 1.307 1.307 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00967 37.84 0.00687 0.475 0.00
ROOM_1_FLR_6 2302.12 2302.12 59.00 0.260 0.260 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00855 36.80 0.00687 0.015 0.00
ROOM_2_FLR_6 2282.86 2282.86 58.51 0.258 0.258 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00855 36.63 0.00687 0.015 0.00
ROOM_3_MULT9_FLR_6 10478.14 10478.14 427.15 1.183 1.183 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00863 38.10 0.00687 0.099 0.00
BANQUET_FLR_6 29062.31 29062.31 87.63 2.438 2.438 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 23.98 0.01042 38.10 0.00687 1.188 0.00
DINING_FLR_6 30510.41 30510.41 91.99 2.559 2.559 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 23.98 0.01033 38.10 0.00687 1.188 0.00
KITCHEN_FLR_6 29610.37 29610.37 286.63 2.487 2.487 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01012 36.93 0.00687 0.367 0.00
CORRIDOR_FLR_6 9132.92 9132.92 22.16 0.765 0.765 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00902 38.10 0.00687 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 22.99 0.00281 -5.20 0.00281 0.854 0.00
RETAIL_1_FLR_1 2197.30 2197.30 32.76 0.109 0.109 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00754 -5.20 0.00281 0.079 0.00
RETAIL_2_FLR_1 791.34 791.34 10.19 0.039 0.092 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00751 -5.20 0.00281 0.092 0.00
MECH_FLR_1 1521.52 1521.52 9.26 0.075 0.075 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00740 -5.20 0.00281 0.000 0.00
STORAGE_FLR_1 963.19 963.19 10.16 0.048 0.058 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00745 -5.20 0.00281 0.058 0.00
LAUNDRY_FLR_1 2047.27 2047.27 26.23 0.101 0.101 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00740 -5.20 0.00281 0.000 0.00
CAFE_FLR_1 5377.78 5377.78 28.47 0.266 0.676 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00758 -5.20 0.00281 0.676 0.00
LOBBY_FLR_1 13255.81 13255.81 10.13 0.655 1.894 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00752 -5.20 0.00281 1.894 0.00
ROOM_1_FLR_3 4565.03 4565.03 116.99 0.227 0.227 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -5.20 0.00281 0.062 0.00
ROOM_2_FLR_3 4563.12 4563.12 116.95 0.227 0.227 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -5.20 0.00281 0.062 0.00
ROOM_3_MULT19_FLR_3 26189.96 26189.96 1067.94 1.302 1.302 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00752 -5.20 0.00281 0.837 0.00
ROOM_4_MULT19_FLR_3 26165.74 26165.74 1066.66 1.301 1.301 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00752 -5.20 0.00281 0.837 0.00
ROOM_5_FLR_3 4561.81 4561.81 116.90 0.227 0.227 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -5.20 0.00281 0.062 0.00
ROOM_6_FLR_3 4559.90 4559.90 116.87 0.227 0.227 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -5.20 0.00281 0.062 0.00
CORRIDOR_FLR_3 7395.96 7395.96 18.99 0.366 0.475 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00761 -5.20 0.00281 0.475 0.00
ROOM_1_FLR_6 1457.19 1457.19 37.34 0.072 0.072 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00759 -5.20 0.00281 0.015 0.00
ROOM_2_FLR_6 1456.91 1456.91 37.34 0.072 0.072 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00759 -5.20 0.00281 0.015 0.00
ROOM_3_MULT9_FLR_6 7053.41 7053.41 287.54 0.351 0.351 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00761 -5.20 0.00281 0.099 0.00
BANQUET_FLR_6 5246.99 5246.99 15.82 0.259 1.188 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00771 -5.20 0.00281 1.188 0.00
DINING_FLR_6 5356.08 5356.08 16.15 0.265 1.188 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00772 -5.20 0.00281 1.188 0.00
KITCHEN_FLR_6 1984.48 1984.48 19.21 0.098 0.367 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00678 -5.20 0.00281 0.367 0.00
CORRIDOR_FLR_6 5649.81 5649.81 13.71 0.279 0.279 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00776 -5.20 0.00281 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 23.15 23.15 7.36 7.36 23.1496 10.5364 23.1496 0.4551 0.3000
FLR_3_DOAS 16.84 2.05 4.01 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 5873.897 5873.897 1.282750 0.00012849 169.599 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5873.90 5873.90 1.282750 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 0.00 0.00 5900.20 5900.20
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2741.009 2741.009 0.118853 0.00005996 109.404 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2741.01 2741.01 0.118853 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00753529 42.2800 2197.30 0.00 2754.32 2754.32
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1421.071 1421.071 0.137653 0.00003109 45.842 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1421.07 1421.07 0.137653 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00750503 42.1113 791.34 0.00 1426.91 1426.91
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1865.461 1865.461 0.075197 0.00004081 77.296 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1865.46 1865.46 0.075197 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00740457 41.5543 1521.52 0.00 1874.38 1874.38
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1359.584 1359.584 0.086657 0.00002974 47.676 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1359.58 1359.58 0.086657 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00745178 41.8161 963.19 0.00 1366.65 1366.65
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 2509.991 2509.991 0.101177 0.00005491 104.003 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2509.99 2509.99 0.101177 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00739688 41.5127 2047.27 0.00 2522.00 2522.00
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 10020.445 10020.445 1.014778 0.00021920 320.301 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10020.44 10020.44 1.014778 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00757660 42.5087 5377.78 0.00 10062.56 10062.56
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 26244.047 26244.047 2.839054 0.00057409 828.191 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 26244.05 26244.05 2.839054 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00751543 42.1689 13255.81 0.00 26354.83 26354.83
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 9438.212 -999.000 0.973293 0.00026993 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 9438.21 9341.87 0.973293 21.77 14.21 0.00855097 12.80 10.82 0.00850000 36.63 0.00686912 17.72 0.0000 21.11 0.00855097 47.5750 8621.75 0.00 6893.45 6893.45
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 4564.952 4564.952 0.226931 0.00009986 206.150 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4564.95 4564.95 0.226931 21.11 13.04 0.00748878 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00748878 41.7369 4565.03 0.00 5109.05 5109.05
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 9371.189 -999.000 0.966287 0.00026801 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown 7/21 16:50:00 9371.19 9274.86 0.966287 21.77 14.21 0.00855133 12.80 10.82 0.00850000 36.45 0.00686884 17.67 0.0000 21.11 0.00855133 47.5769 8559.69 0.00 6844.63 6844.63
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 4563.041 4563.041 0.226836 0.00009982 206.064 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4563.04 4563.04 0.226836 21.11 13.04 0.00748862 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00748862 41.7360 4563.12 0.00 5106.91 5106.91
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 53625.393 -999.000 5.608297 0.00153365 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 53625.39 53625.39 5.608297 21.77 14.13 0.00846799 12.80 10.79 0.00846799 38.10 0.00687148 18.17 0.0000 21.11 0.00846799 47.1186 49682.09 0.00 42981.57 42981.57
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 26189.742 26189.742 1.301962 0.00057290 1182.685 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 26189.74 26189.74 1.301962 21.11 13.08 0.00752405 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00752405 41.9301 26189.96 0.00 29311.58 29311.58
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 63826.892 -999.000 6.282744 0.00182541 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 unknown 7/21 15:30:00 63826.89 61044.88 6.282744 21.77 14.35 0.00872524 12.80 10.82 0.00850000 37.71 0.00687086 18.05 0.0000 21.11 0.00872524 48.5322 55652.15 0.00 47065.85 45926.45
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 26165.517 26165.517 1.300758 0.00057237 1181.591 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 26165.52 26165.52 1.300758 21.11 13.08 0.00752353 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00752353 41.9272 26165.74 0.00 29284.47 29284.47
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 8397.223 -999.000 0.864623 0.00024016 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 8397.22 8302.22 0.864623 21.77 14.21 0.00855656 12.80 10.82 0.00850000 33.48 0.00686412 16.74 0.0000 21.11 0.00855656 47.6056 7659.12 0.00 6135.05 6135.05
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 4561.732 4561.732 0.226771 0.00009979 206.004 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4561.73 4561.73 0.226771 21.11 13.04 0.00748845 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00748845 41.7351 4561.81 0.00 5105.44 5105.44
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 8341.651 -999.000 0.858829 0.00023857 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 8341.65 8246.77 0.858829 21.77 14.21 0.00855686 12.80 10.82 0.00850000 33.16 0.00686360 16.64 0.0000 21.11 0.00855686 47.6073 7607.80 0.00 6094.55 6094.55
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 4559.821 4559.821 0.226676 0.00009975 205.918 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4559.82 4559.82 0.226676 21.11 13.04 0.00748830 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00748830 41.7342 4559.90 0.00 5103.30 5103.30
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 10656.422 10656.422 0.712554 0.00023311 369.715 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10656.42 10656.42 0.712554 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00760637 42.6727 7395.96 0.00 10712.04 10712.04
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2517.932 -999.000 0.259882 0.00007201 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 2517.93 2493.82 0.259882 21.77 14.20 0.00854779 12.80 10.82 0.00850000 36.80 0.00686940 17.78 0.0000 21.11 0.00854779 47.5575 2302.12 0.00 1838.71 1838.71
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1457.164 1457.164 0.072438 0.00003188 65.799 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1457.16 1457.16 0.072438 21.11 13.14 0.00759080 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00759080 42.2986 1457.19 0.00 1630.84 1630.84
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2497.143 -999.000 0.257708 0.00007142 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 2497.14 2473.03 0.257708 21.77 14.20 0.00854819 12.80 10.82 0.00850000 36.63 0.00686912 17.72 0.0000 21.11 0.00854819 47.5597 2282.86 0.00 1823.57 1823.57
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1456.883 1456.883 0.072424 0.00003187 65.786 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1456.88 1456.88 0.072424 21.11 13.14 0.00759076 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00759076 42.2984 1456.91 0.00 1630.53 1630.53
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 11706.677 -999.000 1.182895 0.00033480 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 11706.68 11415.06 1.182895 21.77 14.27 0.00862626 12.80 10.82 0.00850000 38.10 0.00687148 18.17 0.0000 21.11 0.00862626 47.9889 10478.14 0.00 8586.05 8586.05
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 7053.314 7053.314 0.350634 0.00015429 318.492 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7053.31 7053.31 0.350634 21.11 13.15 0.00760923 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00760923 42.3997 7053.41 0.00 7894.02 7894.02
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13402.892 13402.892 1.782133 0.00029319 408.809 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 13402.89 13402.89 1.782133 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00771371 43.2679 5246.99 0.00 13460.38 13460.38
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13508.227 13508.227 1.781320 0.00029549 412.520 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 13508.23 13508.23 1.781320 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00771922 43.2986 5356.08 0.00 13566.13 13566.13
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 4505.892 4505.892 0.552212 0.00009857 139.158 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 4505.89 4505.89 0.552212 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00677679 38.0749 1984.48 0.00 4525.09 4525.09
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 6927.815 6927.815 0.279227 0.00015155 287.077 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 6927.81 6927.81 0.279227 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00776461 43.5498 5649.81 0.00 6960.95 6960.95
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 472740.666 -999.000 23.149556 0.01352032 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 472740.67 468526.33 23.149556 29.68 16.85 0.00857259 10.70 9.97 0.00850000 38.10 0.00687148 18.17 40.2997 23.99 0.00971440 45.2876 276125.23 0.00 524953.66 477123.91
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 159606.823 159606.823 6.944867 0.00349140 3418.554 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 159606.82 159606.82 6.944867 -5.20 -5.20 0.00280840 16.70 11.86 0.00800000 -5.20 0.00280840 -5.20 134.3323 21.37 0.00671323 36.8657 51499.53 0.00 140287.81 140287.81
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 57348.723 -999.000 2.051317 0.00164017 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 57348.72 57348.72 2.051317 38.10 18.17 0.00687148 11.79 8.78 0.00687148 38.10 0.00687148 18.17 99.9965 21.11 0.00860402 47.8663 148890.06 0.00 50441.98 50441.98
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 14143.003 14143.003 0.615395 0.00030938 302.923 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 14143.00 14143.00 0.615395 -5.20 -5.20 0.00280840 16.70 11.86 0.00800000 -5.20 0.00280840 -5.20 333.3216 21.11 0.00752453 41.9327 80573.08 0.00 12431.12 12431.12



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 5873.897 5873.897 1.282750 0.00012849 169.599 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 1.6203 1.652948 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5873.90 5873.90 1.0000 1.33961646 1.282750 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.12847854 60.00 48.89 11.11 0.000 5873.90 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 44.8527 0.00 0.00 5900.20 5900.20 1.33961646 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41339.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2741.009 2741.009 0.118853 0.00005996 109.404 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 0.7561 0.771336 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2741.01 2741.01 1.0000 0.12412201 0.118853 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.05995352 60.00 48.89 11.11 0.000 2741.01 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00753529 21.00 0.00753529 42.2800 2197.30 0.00 2754.32 2754.32 0.12412201 16.60 13.15 0.00800000 36934.7 38.36 20.69 0.00800000 59125.2
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1421.071 1421.071 0.137653 0.00003109 45.842 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 0.3920 0.399897 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1421.07 1421.07 1.0000 0.14375570 0.137653 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.03108279 60.00 48.89 11.11 0.000 1421.07 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00750503 21.00 0.00750503 42.1113 791.34 0.00 1426.91 1426.91 0.14375570 16.60 13.15 0.00800000 36934.7 26.33 16.78 0.00800000 46860.7
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1865.461 1865.461 0.075197 0.00004081 77.296 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 0.5146 0.524951 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1865.46 1865.46 1.0000 0.07853032 0.075197 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.04080285 60.00 48.89 11.11 0.000 1865.46 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00740457 21.00 0.00740457 41.5543 1521.52 0.00 1874.38 1874.38 0.07853032 16.60 13.15 0.00800000 36934.7 40.01 21.18 0.00800000 60803.0
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1359.584 1359.584 0.086657 0.00002974 47.676 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 0.3750 0.382595 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1359.58 1359.58 1.0000 0.09049859 0.086657 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.02973790 60.00 48.89 11.11 0.000 1359.58 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00745178 21.00 0.00745178 41.8161 963.19 0.00 1366.65 1366.65 0.09049859 16.60 13.15 0.00800000 36934.7 31.41 18.50 0.00800000 52036.0
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 2509.991 2509.991 0.101177 0.00005491 104.003 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 0.6924 0.706326 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2509.99 2509.99 1.0000 0.10566256 0.101177 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.05490053 60.00 48.89 11.11 0.000 2509.99 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00739688 21.00 0.00739688 41.5127 2047.27 0.00 2522.00 2522.00 0.10566256 16.60 13.15 0.00800000 36934.7 40.01 21.18 0.00800000 60803.1
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 10020.445 10020.445 1.014778 0.00021920 320.301 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 2.7642 2.819811 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10020.44 10020.44 1.0000 1.05976514 1.014778 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.21917514 60.00 48.89 11.11 0.000 10020.44 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00757660 21.00 0.00757660 42.5087 5377.78 0.00 10062.56 10062.56 1.05976514 16.60 13.15 0.00800000 36934.7 25.91 16.64 0.00800000 46429.8
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 26244.047 26244.047 2.839054 0.00057409 828.191 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 7.2395 7.385226 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 26244.05 26244.05 1.0000 2.96491426 2.839054 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.57403070 60.00 48.89 11.11 0.000 26244.05 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00751543 21.00 0.00751543 42.1689 13255.81 0.00 26354.83 26354.83 2.96491426 16.60 13.15 0.00800000 36934.7 25.32 16.43 0.00800000 45823.6
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 9438.212 -999.000 0.973293 0.00026993 -999.000 -999.0000 1.00000 1.00000 1020.7358 1004.8586 1.0443 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.973293 1.01644029   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 1.3487 1.348660 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 9438.21 9341.87 1.0000 1.01644029 0.973293 21.77 14.21 0.00855097 43607.8 12.80 10.82 0.00850000 34322.2 0.26989909 6.70 15.03 8.33 0.000 9438.21 36.63 0.00686912 17.72 0.00000000 0.0000 21.11 0.00855097 21.11 0.00855097 47.5750 8621.75 0.00 6893.45 6893.45 1.01644029 21.77 15.63 0.00855097 43607.8 15.13 13.10 0.00855097 36825.8
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 4564.952 4564.952 0.226931 0.00009986 206.150 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.973293 1.01644029   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 1.2593 1.284604 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4564.95 4564.95 1.0000 0.23699136 0.226931 21.11 13.04 0.00748878 40235.3 40.00 19.53 0.00800000 60796.0 0.09984828 60.00 48.89 11.11 0.000 4564.95 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00748878 21.11 0.00748878 41.7369 4565.03 0.00 5109.05 5109.05 0.23699136 16.60 12.65 0.00748878 35640.4 37.76 20.13 0.00748878 57198.4
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 9371.189 -999.000 0.966287 0.00026801 -999.000 -999.0000 1.00000 1.00000 1020.7365 1004.8586 1.0443 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.966287 1.00912370   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 1.3391 1.339083 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown unknown unknown 7/21 16:50:00 Sensible 9371.19 9274.86 1.0000 1.00912370 0.966287 21.77 14.21 0.00855133 43608.7 12.80 10.82 0.00850000 34322.2 0.26798249 6.70 15.03 8.33 0.000 9371.19 36.45 0.00686884 17.67 0.00000000 0.0000 21.11 0.00855133 21.11 0.00855133 47.5769 8559.69 0.00 6844.63 6844.63 1.00912370 21.77 15.63 0.00855133 43608.7 15.13 13.10 0.00855133 36825.9
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 4563.041 4563.041 0.226836 0.00009982 206.064 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.966287 1.00912370   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 1.2587 1.284066 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4563.04 4563.04 1.0000 0.23689213 0.226836 21.11 13.04 0.00748862 40234.9 40.00 19.53 0.00800000 60796.0 0.09980647 60.00 48.89 11.11 0.000 4563.04 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00748862 21.11 0.00748862 41.7360 4563.12 0.00 5106.91 5106.91 0.23689213 16.60 12.65 0.00748862 35640.0 37.76 20.13 0.00748862 57198.0
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 53625.393 -999.000 5.608297 0.00153365 -999.000 -999.0000 1.00000 1.00000 1020.5816 1004.8586 1.0443 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.608297 5.85692201   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 7.6629 7.662723 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 53625.39 53625.39 1.0000 5.85692201 5.608297 21.77 14.13 0.00846799 43397.3 12.80 10.79 0.00846799 34241.4 1.53349438 6.70 15.03 8.33 0.000 53625.39 38.10 0.00687148 18.17 0.00000000 0.0000 21.11 0.00846799 21.11 0.00846799 47.1186 49682.09 0.00 42981.57 42981.57 5.85692201 21.77 15.56 0.00846799 43397.3 14.58 12.80 0.00846799 36058.7
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 26189.742 26189.742 1.301962 0.00057290 1182.685 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.608297 5.85692201   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 7.2245 7.369945 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 26189.74 26189.74 1.0000 1.35968010 1.301962 21.11 13.08 0.00752405 40325.3 40.00 19.53 0.00800000 60796.0 0.57284290 60.00 48.89 11.11 0.000 26189.74 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00752405 21.11 0.00752405 41.9301 26189.96 0.00 29311.58 29311.58 1.35968010 16.60 12.69 0.00752405 35729.7 37.76 20.15 0.00752405 57287.4
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 63826.892 -999.000 6.282744 0.00182541 -999.000 -999.0000 1.00000 1.00000 1021.0598 1004.8586 1.0443 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.282744 6.56126872   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 9.1206 9.120452 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 unknown unknown unknown 7/21 15:30:00 Sensible 63826.89 61044.88 1.0000 6.56126872 6.282744 21.77 14.35 0.00872524 44050.0 12.80 10.82 0.00850000 34322.2 1.82522072 6.70 15.03 8.33 0.000 63826.89 37.71 0.00687086 18.05 0.00000000 0.0000 21.11 0.00872524 21.11 0.00872524 48.5322 55652.15 0.00 47065.85 45926.45 6.56126872 21.77 15.78 0.00872524 44050.0 14.91 13.11 0.00865656 36876.7
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 26165.517 26165.517 1.300758 0.00057237 1181.591 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.282744 6.56126872   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 7.2179 7.363128 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 26165.52 26165.52 1.0000 1.35842243 1.300758 21.11 13.08 0.00752353 40324.0 40.00 19.53 0.00800000 60796.0 0.57231303 60.00 48.89 11.11 0.000 26165.52 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00752353 21.11 0.00752353 41.9272 26165.74 0.00 29284.47 29284.47 1.35842243 16.60 12.69 0.00752353 35728.4 37.76 20.15 0.00752353 57286.1
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 8397.223 -999.000 0.864623 0.00024016 -999.000 -999.0000 1.00000 1.00000 1020.7462 1004.8586 1.0443 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.864623 0.90295310   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 1.1999 1.199909 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 8397.22 8302.22 1.0000 0.90295310 0.864623 21.77 14.21 0.00855656 43621.9 12.80 10.82 0.00850000 34322.2 0.24013052 6.70 15.03 8.33 0.000 8397.22 33.48 0.00686412 16.74 0.00000000 0.0000 21.11 0.00855656 21.11 0.00855656 47.6056 7659.12 0.00 6135.05 6135.05 0.90295310 21.77 15.64 0.00855656 43621.9 15.11 13.10 0.00855656 36827.5
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 4561.732 4561.732 0.226771 0.00009979 206.004 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.864623 0.90295310   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 1.2584 1.283698 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4561.73 4561.73 1.0000 0.23682418 0.226771 21.11 13.04 0.00748845 40234.5 40.00 19.53 0.00800000 60796.0 0.09977784 60.00 48.89 11.11 0.000 4561.73 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00748845 21.11 0.00748845 41.7351 4561.81 0.00 5105.44 5105.44 0.23682418 16.60 12.65 0.00748845 35639.6 37.76 20.13 0.00748845 57197.5
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 8341.651 -999.000 0.858829 0.00023857 -999.000 -999.0000 1.00000 1.00000 1020.7468 1004.8586 1.0443 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.858829 0.89690226   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 1.1920 1.191968 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 8341.65 8246.77 1.0000 0.89690226 0.858829 21.77 14.21 0.00855686 43622.7 12.80 10.82 0.00850000 34322.2 0.23854136 6.70 15.03 8.33 0.000 8341.65 33.16 0.00686360 16.64 0.00000000 0.0000 21.11 0.00855686 21.11 0.00855686 47.6073 7607.80 0.00 6094.55 6094.55 0.89690226 21.77 15.64 0.00855686 43622.7 15.11 13.10 0.00855686 36827.6
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 4559.821 4559.821 0.226676 0.00009975 205.918 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.858829 0.89690226   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 1.2578 1.283160 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4559.82 4559.82 1.0000 0.23672493 0.226676 21.11 13.04 0.00748830 40234.1 40.00 19.53 0.00800000 60796.0 0.09973603 60.00 48.89 11.11 0.000 4559.82 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00748830 21.11 0.00748830 41.7342 4559.90 0.00 5103.30 5103.30 0.23672493 16.60 12.65 0.00748830 35639.2 37.76 20.13 0.00748830 57197.1
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 10656.422 10656.422 0.712554 0.00023311 369.715 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 2.9396 2.998779 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10656.42 10656.42 1.0000 0.74414279 0.712554 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.23308574 60.00 48.89 11.11 0.000 10656.42 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00760637 21.00 0.00760637 42.6727 7395.96 0.00 10712.04 10712.04 0.74414279 16.60 13.15 0.00800000 36934.7 30.72 18.28 0.00800000 51329.9
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2517.932 -999.000 0.259882 0.00007201 -999.000 -999.0000 1.00000 1.00000 1020.7299 1004.8586 1.0443 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.259882 0.27140257   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 0.3598 0.359796 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 2517.93 2493.82 1.0000 0.27140257 0.259882 21.77 14.20 0.00854779 43599.7 12.80 10.82 0.00850000 34322.2 0.07200384 6.70 15.03 8.33 0.000 2517.93 36.80 0.00686940 17.78 0.00000000 0.0000 21.11 0.00854779 21.11 0.00854779 47.5575 2302.12 0.00 1838.71 1838.71 0.27140257 21.77 15.63 0.00854779 43599.7 15.13 13.09 0.00854779 36824.8
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1457.164 1457.164 0.072438 0.00003188 65.799 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.259882 0.27140257   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 0.4020 0.410054 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1457.16 1457.16 1.0000 0.07564928 0.072438 21.11 13.14 0.00759080 40494.5 40.00 19.53 0.00800000 60796.0 0.03187225 60.00 48.89 11.11 0.000 1457.16 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00759080 21.11 0.00759080 42.2986 1457.19 0.00 1630.84 1630.84 0.07564928 16.60 12.75 0.00759080 35898.7 37.76 20.20 0.00759080 57456.7
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2497.143 -999.000 0.257708 0.00007142 -999.000 -999.0000 1.00000 1.00000 1020.7307 1004.8586 1.0443 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.257708 0.26913253   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 0.3568 0.356826 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 2497.14 2473.03 1.0000 0.26913253 0.257708 21.77 14.20 0.00854819 43600.7 12.80 10.82 0.00850000 34322.2 0.07140935 6.70 15.03 8.33 0.000 2497.14 36.63 0.00686912 17.72 0.00000000 0.0000 21.11 0.00854819 21.11 0.00854819 47.5597 2282.86 0.00 1823.57 1823.57 0.26913253 21.77 15.63 0.00854819 43600.7 15.13 13.09 0.00854819 36824.9
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1456.883 1456.883 0.072424 0.00003187 65.786 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.257708 0.26913253   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 0.4019 0.409975 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1456.88 1456.88 1.0000 0.07563470 0.072424 21.11 13.14 0.00759076 40494.3 40.00 19.53 0.00800000 60796.0 0.03186610 60.00 48.89 11.11 0.000 1456.88 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00759076 21.11 0.00759076 42.2984 1456.91 0.00 1630.53 1630.53 0.07563470 16.60 12.75 0.00759076 35898.6 37.76 20.20 0.00759076 57456.6
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 11706.677 -999.000 1.182895 0.00033480 -999.000 -999.0000 1.00000 1.00000 1020.8758 1004.8586 1.0443 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.182895 1.23533457   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 1.6728 1.672809 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 11706.68 11415.06 1.0000 1.23533457 1.182895 21.77 14.27 0.00862626 43798.7 12.80 10.82 0.00850000 34322.2 0.33476909 6.70 15.03 8.33 0.000 11706.68 38.10 0.00687148 18.17 0.00000000 0.0000 21.11 0.00862626 21.11 0.00862626 47.9889 10478.14 0.00 8586.05 8586.05 1.23533457 21.77 15.70 0.00862626 43798.7 14.96 13.10 0.00862626 36848.3
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 7053.314 7053.314 0.350634 0.00015429 318.492 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.182895 1.23533457   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 1.9457 1.984843 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7053.31 7053.31 1.0000 0.36617854 0.350634 21.11 13.15 0.00760923 40541.4 40.00 19.53 0.00800000 60796.0 0.15427570 60.00 48.89 11.11 0.000 7053.31 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00760923 21.11 0.00760923 42.3997 7053.41 0.00 7894.02 7894.02 0.36617854 16.60 12.77 0.00760923 35945.4 37.76 20.22 0.00760923 57503.2
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 13402.892 13402.892 1.782133 0.00029319 408.809 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 3.6972 3.771651 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 13402.89 13402.89 1.0000 1.86113796 1.782133 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.29315873 60.00 48.89 11.11 0.000 13402.89 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00771371 21.00 0.00771371 43.2679 5246.99 0.00 13460.38 13460.38 1.86113796 16.60 13.15 0.00800000 36934.7 23.69 15.84 0.00800000 44167.1
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 13508.227 13508.227 1.781320 0.00029549 412.520 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 3.7263 3.801293 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 13508.23 13508.23 1.0000 1.86028923 1.781320 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.29546270 60.00 48.89 11.11 0.000 13508.23 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00771922 21.00 0.00771922 43.2986 5356.08 0.00 13566.13 13566.13 1.86028923 16.60 13.15 0.00800000 36934.7 23.75 15.87 0.00800000 44227.2
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 4505.892 4505.892 0.552212 0.00009857 139.158 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 1.2430 1.267984 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 4505.89 4505.89 1.0000 0.57669286 0.552212 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.09855645 60.00 48.89 11.11 0.000 4505.89 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.49 0.00677679 21.00 0.00677679 38.0749 1984.48 0.00 4525.09 4525.09 0.57669286 16.60 13.15 0.00800000 36934.7 24.29 16.06 0.00800000 44781.4
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 6927.815 6927.815 0.279227 0.00015155 287.077 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 1.9111 1.949527 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 6927.81 6927.81 1.0000 0.29160542 0.279227 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.15153068 60.00 48.89 11.11 0.000 6927.81 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00776461 21.00 0.00776461 43.5498 5649.81 0.00 6960.95 6960.95 0.29160542 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60805.9
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 472740.666 -999.000 23.149556 0.01352032 -999.000 -999.0000 1.00000 1.00000 1020.7760 1004.8586 1.0443 VAV WITH REHEAT FAN Fan:VariableVolume 23.149556 24.17581559   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 67.5529 67.552858 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 Sensible 472740.67 468526.33 1.0000 24.17581559 23.149556 29.68 16.85 0.00857259 51731.2 10.70 9.97 0.00850000 32177.0 13.51894398 6.70 15.03 8.33 51869.788 420870.88 38.10 0.00687148 18.17 9.32920000 40.2997 23.99 0.00972090 23.99 0.00971440 45.2876 276125.23 0.00 524953.66 477123.91 24.17581559 29.68 18.39 0.00857259 51731.2 10.34 10.32 0.00778756 30017.2
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 159606.823 159606.823 6.944867 0.00349140 3418.554 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV WITH REHEAT FAN Fan:VariableVolume 23.149556 24.17581559   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 44.0282 44.914281 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 159606.82 159606.82 1.0000 7.25274468 6.944867 -5.20 -5.20 0.00280840 1771.3 16.70 11.86 0.00800000 37036.7 3.49104753 60.00 48.89 11.11 0.000 159606.82 -5.20 0.00280840 -5.20 9.32920000 134.3323 18.54 0.00701628 21.37 0.00671323 36.8657 51499.53 0.00 140287.81 140287.81 7.25274468 2.80 0.24 0.00280840 9851.8 21.95 10.06 0.00280840 29194.5
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 57348.723 -999.000 2.051317 0.00164017 -999.000 -999.0000 1.00000 1.00000 1017.6137 1004.8586 1.0443 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.14218037   4197.9300 999.8980 20.01239371 15.03 6.70 8.33 699808.53 8.1949 8.194916 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 57348.72 57348.72 1.0000 2.14225568 2.051317 38.10 18.17 0.00687148 55956.2 11.79 8.78 0.00687148 29186.0 1.63999890 6.70 15.03 8.33 2195.006 55153.72 38.10 0.00687148 18.17 2.05124512 99.9965 21.11 0.00859567 21.11 0.00860402 47.8663 148890.06 0.00 50441.98 50441.98 2.14225568 38.10 19.77 0.00687148 55956.2 14.96 11.35 0.00687148 32410.0
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 14143.003 14143.003 0.615395 0.00030938 302.923 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.14218037   4197.9300 999.8980 7.77268942 48.89 60.00 11.11 362510.48 3.9014 3.979923 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 14143.00 14143.00 1.0000 0.64267671 0.615395 -5.20 -5.20 0.00280840 1771.3 16.70 11.86 0.00800000 37036.7 0.30934702 60.00 48.89 11.11 0.000 14143.00 -5.20 0.00280840 -5.20 2.05124512 333.3216 21.11 0.00752571 21.11 0.00752453 41.9327 80573.08 0.00 12431.12 12431.12 0.64267671 2.80 0.24 0.00280840 9851.8 21.95 10.06 0.00280840 29194.5



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 23.15 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000914 0.000000 0.000000 Sum   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 1820.50 6976.33 1053.50
RETAIL_1_FLR_1 3431.50 5084.50 1103.50
RETAIL_2_FLR_1 2159.67 6658.83 1122.67
MECH_FLR_1 2442.00 5744.50 642.00
STORAGE_FLR_1 804.67 8380.00 767.50
LAUNDRY_FLR_1 8760.00 4421.67 4421.67
CAFE_FLR_1 2601.00 6709.33 1568.00
LOBBY_FLR_1 2709.83 6497.17 1660.00
ROOM_1_FLR_3 380.67 8022.83 266.33
ROOM_2_FLR_3 1142.17 7908.83 986.33
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 448.00 8748.50 448.00
ROOM_5_FLR_3 326.67 7895.50 263.83
ROOM_6_FLR_3 1292.00 7746.67 1024.50
CORRIDOR_FLR_3 1609.33 7825.67 1451.17
ROOM_1_FLR_6 1179.67 7798.00 861.50
ROOM_2_FLR_6 2172.33 7714.67 1843.00
ROOM_3_MULT9_FLR_6 244.00 8024.17 129.33
BANQUET_FLR_6 3177.33 5929.67 1607.00
DINING_FLR_6 3790.67 4955.33 1613.33
KITCHEN_FLR_6 8759.83 6805.50 6805.50
CORRIDOR_FLR_6 2837.83 5763.17 1039.50
Facility 8760.00 8760.00 7686.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 251.17 0.00 251.17
ROOM_2_FLR_3 0.00 245.67 0.00 245.67
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 122.17 0.00 122.17
ROOM_5_FLR_3 0.00 218.17 0.00 218.17
ROOM_6_FLR_3 0.00 275.50 0.00 275.50
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 289.00 0.00 289.00
ROOM_2_FLR_6 0.00 285.00 0.00 285.00
ROOM_3_MULT9_FLR_6 0.00 194.17 0.00 194.17
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 582.33 0.00 582.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.769 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.442 0.135 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.244 0.045 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.208 0.051 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.628 0.050 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 17.698 0.145 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 3.711 0.106 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.552 0.044 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.341 0.175 0.000 0.056
ROOM_2_FLR_3 0.95 1.50 118.93 0.342 0.175 0.000 0.059
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.388 0.078 0.000 0.090
ROOM_5_FLR_3 0.95 1.50 118.94 0.341 0.175 0.000 0.056
ROOM_6_FLR_3 0.95 1.50 118.93 0.342 0.175 0.000 0.057
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.410 0.021 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.341 0.175 0.000 0.066
ROOM_2_FLR_6 0.95 1.50 118.93 0.342 0.175 0.000 0.068
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.388 0.142 0.000 0.105
BANQUET_FLR_6 145.01 249.90 1010.89 4.907 0.050 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 4.988 0.051 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 18.046 0.146 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.565 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.458 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 0.890 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.836 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.008 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.387 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 7.009 0.002 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 2.431 0.002 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.104 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.258 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.002 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 3.282 0.001 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 3.425 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 6.176 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.298 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.047
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.173
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.036


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 31965478.73 0.00 31965478.73 0.00 31965478.73 26946214.98 4188.71 106.77 4464.52 0.00
RETAIL_1_FLR_1 3296373.68 0.00 3296373.68 309826.10 3606199.78 2498216.28 2382.19 124.77 6253.04 0.00
RETAIL_2_FLR_1 3295811.62 0.00 3295811.62 119593.27 3415404.89 2294951.32 449.53 536.38 7774.09 0.00
MECH_FLR_1 1160671.51 0.00 1160671.51 282647.43 1443318.95 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 2039569.77 0.00 2039569.77 163072.00 2202641.77 1821682.01 4806.53 73.65 3879.82 0.00
LAUNDRY_FLR_1 47023723.91 0.00 47023723.91 385940.64 47409664.54 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 23919664.37 0.00 23919664.37 684888.14 24604552.51 14544917.54 627.78 115.51 8016.72 0.00
LOBBY_FLR_1 69145197.28 0.00 69145197.28 1956881.84 71102079.13 59728886.00 4305.04 133.67 4321.29 0.00
ROOM_1_FLR_3 1406076.84 57261.50 1463338.34 179831.92 1643170.26 1946875.62 2433.00 5685.17 641.83 0.00
ROOM_2_FLR_3 1405912.09 60155.82 1466067.92 179818.20 1645886.12 1946647.51 2433.00 5686.58 640.42 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 50175.12 1150087.09 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19070354.14 57967.36 19128321.50 50188.84 19178510.34 26405105.73 2433.33 5735.40 591.27 0.00
ROOM_5_FLR_3 1406076.84 57403.39 1463480.23 179831.92 1643312.15 1946875.62 2433.00 5685.17 641.83 0.00
ROOM_6_FLR_3 1405912.09 58063.47 1463975.56 179818.20 1643793.77 1946647.51 2433.00 5685.17 641.83 0.00
CORRIDOR_FLR_3 16778346.06 0.00 16778346.06 217452.98 16995799.04 14972100.18 4803.07 73.83 3883.10 0.00
ROOM_1_FLR_6 351519.21 67860.24 419379.45 179868.73 599248.17 486718.90 2260.02 5686.12 813.85 0.00
ROOM_2_FLR_6 351478.02 69704.15 421182.17 179855.01 601037.18 486661.88 2258.23 5690.22 811.55 0.00
ROOM_3_MULT9_FLR_6 2258331.41 67925.32 2326256.73 92027.14 2418283.87 3126920.42 2433.17 5682.53 644.31 0.00
BANQUET_FLR_6 42667114.83 0.00 42667114.83 439194.23 43106309.06 37458366.31 4637.75 137.23 3985.01 0.00
DINING_FLR_6 43332723.95 0.00 43332723.95 439194.23 43771918.18 37458366.31 4313.91 119.29 4326.81 0.00
KITCHEN_FLR_6 48735589.95 0.00 48735589.95 393180.66 49128770.61 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 6092405.81 0.00 6092405.81 384823.29 6477229.10 3961413.96 2041.39 69.74 6648.87 0.00
Total Facility 0.20E+10 6085948.48 0.20E+10 18121884.23 0.20E+10 0.43E+10 8760.00 6167.58 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.0136 0.0000 1.0136 0.0000 1.0136 0.8545 4188.71 106.77 4464.52
RETAIL_1_FLR_1 0.1045 0.0000 0.1045 0.0098 0.1144 0.0792 2382.19 124.77 6253.04
RETAIL_2_FLR_1 0.1045 0.0000 0.1045 0.0038 0.1083 0.0728 449.53 536.38 7774.09
MECH_FLR_1 0.0368 0.0000 0.0368 0.0090 0.0458 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0647 0.0000 0.0647 0.0052 0.0698 0.0578 4806.53 73.65 3879.82
LAUNDRY_FLR_1 1.4911 0.0000 1.4911 0.0122 1.5034 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7585 0.0000 0.7585 0.0217 0.7802 0.4612 627.78 115.51 8016.72
LOBBY_FLR_1 2.1926 0.0000 2.1926 0.0621 2.2546 1.8940 4305.04 133.67 4321.29
ROOM_1_FLR_3 0.0446 0.0018 0.0464 0.0057 0.0521 0.0617 2433.00 5685.17 641.83
ROOM_2_FLR_3 0.0446 0.0019 0.0465 0.0057 0.0522 0.0617 2433.00 5686.58 640.42
ROOM_4_MULT19_FLR_3 0.6047 0.0018 0.6066 0.0016 0.6081 0.8373 2433.33 5735.40 591.27
ROOM_5_FLR_3 0.0446 0.0018 0.0464 0.0057 0.0521 0.0617 2433.00 5685.17 641.83
ROOM_6_FLR_3 0.0446 0.0018 0.0464 0.0057 0.0521 0.0617 2433.00 5685.17 641.83
CORRIDOR_FLR_3 0.5320 0.0000 0.5320 0.0069 0.5389 0.4748 4803.07 73.83 3883.10
ROOM_1_FLR_6 0.0111 0.0022 0.0133 0.0057 0.0190 0.0154 2260.02 5686.12 813.85
ROOM_2_FLR_6 0.0111 0.0022 0.0134 0.0057 0.0191 0.0154 2258.23 5690.22 811.55
ROOM_3_MULT9_FLR_6 0.0716 0.0022 0.0738 0.0029 0.0767 0.0992 2433.17 5682.53 644.31
BANQUET_FLR_6 1.3530 0.0000 1.3530 0.0139 1.3669 1.1878 4637.75 137.23 3985.01
DINING_FLR_6 1.3741 0.0000 1.3741 0.0139 1.3880 1.1878 4313.91 119.29 4326.81
KITCHEN_FLR_6 1.5454 0.0000 1.5454 0.0125 1.5579 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.1932 0.0000 0.1932 0.0122 0.2054 0.1256 2041.39 69.74 6648.87
Total Facility 59.6987 0.1930 59.8917 0.4537 60.3454 73.7328 8760.00 6167.58 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.37E+09 0.00 0.37E+09 0.21E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 31361654.67 496341.25 31857995.92 64690340.46 8760.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 11.7395 0.0000 11.7395 6.7627 0.00 0.00 8760.00
FLR_3_DOAS 0.9945 0.0157 1.0102 2.0513 8760.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 476.90 5781.68 0.00 0.00 0.00 2501.42 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6691.67 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 10.1247 12.9298 0.0000 0.0000 0.0000 9.3050 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.3020 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1344
Defaulted Fields 1183
Fields with Defaults 4016
Autosized Fields 349
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4820.60 59716.83 18-FEB-03:00 332219.46 25-JUL-19:10
Electricity:Building 2110.93 28203.44 02-JAN-02:10 124003.41 02-JAN-20:10
Electricity:Zone:BASEMENT 235.57 2868.06 02-JAN-02:10 17194.07 02-JAN-20:10
Electricity:SpaceType:GENERAL 2103.84 28062.29 02-JAN-02:10 123762.08 02-JAN-20:10
InteriorLights:Electricity 455.38 4168.62 02-JAN-02:10 37630.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 92.46 840.16 02-JAN-02:10 7561.54 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 455.38 4168.62 02-JAN-02:10 37630.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 455.38 4168.62 02-JAN-02:10 37630.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 92.46 840.16 02-JAN-02:10 7561.54 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 455.38 4168.62 02-JAN-02:10 37630.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 14.37 182.36 02-JAN-02:10 1027.80 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 4.18 38.02 02-JAN-02:10 342.20 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 4.18 38.02 02-JAN-02:10 342.20 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 16.64 211.17 02-JAN-02:10 1190.20 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 4.85 44.03 02-JAN-02:10 396.26 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 4.85 44.03 02-JAN-02:10 396.26 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 21.14 255.50 02-JAN-02:10 1548.43 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.67 78.78 02-JAN-02:10 708.98 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.67 78.78 02-JAN-02:10 708.98 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.58 69.04 02-JAN-02:10 404.67 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.99 18.06 02-JAN-02:10 162.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.99 18.06 02-JAN-02:10 162.52 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 71.63 996.30 02-JAN-02:10 4875.27 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.70 33.61 02-JAN-02:10 302.47 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.70 33.61 02-JAN-02:10 302.47 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 21.02 293.25 02-JAN-02:10 1775.61 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 6.68 39.62 01-JAN-13:10 810.33 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 6.68 39.62 01-JAN-13:10 810.33 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 227.74 2868.89 02-JAN-02:10 16846.53 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 78.74 757.48 02-JAN-02:10 6817.32 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 78.74 757.48 02-JAN-02:10 6817.32 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 253.77 3619.58 02-JAN-10:10 20179.99 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 253.84 3620.57 02-JAN-10:10 20185.51 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 54.59 496.05 02-JAN-02:10 4464.45 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 54.59 496.05 02-JAN-02:10 4464.45 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 54.59 496.05 02-JAN-02:10 4464.45 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 3.85 55.20 01-JAN-02:10 290.10 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 3.85 55.19 01-JAN-02:10 290.07 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 30.06 428.75 02-JAN-10:10 2390.39 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 190.48 2407.41 02-JAN-02:10 8170.92 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 14.63 158.11 02-JAN-02:10 1423.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 14.63 158.11 02-JAN-02:10 1423.01 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 190.48 2407.41 02-JAN-02:10 8170.92 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 14.63 158.11 02-JAN-02:10 1423.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 14.63 158.11 02-JAN-02:10 1423.01 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 440.25 5906.67 02-JAN-02:10 18521.62 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 9.14 83.05 02-JAN-02:10 747.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 9.14 83.05 02-JAN-02:10 747.41 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 14.44 131.25 02-JAN-02:10 1181.23 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 14.44 131.25 02-JAN-02:10 1181.23 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 14.44 131.25 02-JAN-02:10 1181.23 02-JAN-20:10
InteriorEquipment:Electricity 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 43.94 732.82 04-APR-22:30 2789.42 24-SEP-10:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 1449.29 2360.03 09-DEC-01:50 142408.97 14-JUN-18:10
LowTempRefrigeration:Refrigeration:Electricity 15.82 0.00 01-JAN-11:10 1306.60 11-AUG-04:00
MedTempRefrigeration:Refrigeration:Electricity 21.02 635.95 20-MAY-03:20 715.73 16-OCT-13:40
Fans:Electricity 624.00 11884.61 31-MAR-03:00 47005.79 07-AUG-21:20
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityProduced:Facility 244.08 -0.00 20-JUL-05:30 34554.33 22-APR-12:10
ElectricityProduced:Plant 244.08 -0.00 20-JUL-05:30 34554.33 22-APR-12:10
Photovoltaic:ElectricityProduced 254.56 0.00 01-JAN-00:10 37470.30 22-APR-12:30
PowerConversion:ElectricityProduced -10.48 -2915.96 22-APR-12:30 0.00 01-JAN-00:10
Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
DCtoACInverter Ancillary:Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 740.77 13539.16 24-NOV-03:10 56089.52 07-AUG-21:20
ExteriorEquipment:Electricity 390.56 5777.98 02-JAN-02:20 23858.54 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 21.47 378.90 02-JAN-02:20 1270.25 02-JAN-07:20
ElectricityPurchased:Facility 4576.51 53794.33 11-APR-12:00 332219.46 25-JUL-19:10
ElectricityPurchased:Plant 4576.51 53794.33 11-APR-12:00 332219.46 25-JUL-19:10
Cogeneration:ElectricityPurchased 4576.51 53794.33 11-APR-12:00 332219.46 25-JUL-19:10
General:Cogeneration:ElectricityPurchased 4576.51 53794.33 11-APR-12:00 332219.46 25-JUL-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4576.51 53794.33 11-APR-12:00 332219.46 25-JUL-19:10
ElectricityNet:Plant 4576.51 53794.33 11-APR-12:00 332219.46 25-JUL-19:10
Cogeneration:ElectricityNet 4576.51 53794.33 11-APR-12:00 332219.46 25-JUL-19:10
General:Cogeneration:ElectricityNet 4576.51 53794.33 11-APR-12:00 332219.46 25-JUL-19:10
General:Fans:Electricity 624.00 11884.61 31-MAR-03:00 47005.79 07-AUG-21:20
ExteriorLights:Electricity 150.51 0.00 01-JAN-07:20 9571.94 01-JAN-00:10
General:ExteriorLights:Electricity 150.51 0.00 01-JAN-07:20 9571.94 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 366.65 5383.28 01-JAN-00:10 22430.31 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.45 15.80 01-JAN-00:10 157.97 01-JAN-07:10
HeatRecovery:Electricity 95.30 0.00 01-JAN-08:00 8265.52 08-MAY-09:00
General:HeatRecovery:Electricity 95.30 0.00 01-JAN-08:00 8265.52 08-MAY-09:00
WaterSystems:Electricity 90.74 1086.56 01-AUG-01:30 4738.73 19-JAN-19:10
Water Heater:WaterSystems:Electricity 90.74 1086.56 01-AUG-01:30 4738.73 19-JAN-19:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1246.82 0.00 01-JAN-05:20 133869.77 14-JUN-18:10
General:Cooling:Electricity 1246.82 0.00 01-JAN-05:20 133869.77 14-JUN-18:10
Pumps:Electricity 74.88 47.91 01-NOV-14:10 3618.75 16-JUN-20:30
General:Pumps:Electricity 74.88 47.91 01-NOV-14:10 3618.75 16-JUN-20:30
WIRED_LTG_ELECTRICITY 16.03 0.00 01-JAN-00:10 1324.60 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4468.11 26805.16 04-JAN-02:10 403686.12 26-DEC-19:10
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 2679.27 13443.27 14-JUN-08:20 326090.07 26-DEC-24:00
WaterSystems:NaturalGas 2405.59 13443.27 14-JUN-08:20 210423.37 30-JAN-22:00
Water Heater:WaterSystems:NaturalGas 2405.59 13443.27 14-JUN-08:20 210423.37 30-JAN-22:00
Heating:NaturalGas 273.67 0.00 01-JAN-11:00 150833.72 02-FEB-03:30
Boiler:Heating:NaturalGas 273.67 0.00 01-JAN-11:00 150833.72 02-FEB-03:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 4038.88 0.00 01-JAN-05:20 510737.79 21-JUL-21:00
PlantLoopCoolingDemand:HVAC 4038.88 0.00 01-JAN-05:20 510737.79 21-JUL-21:00
CoolingCoils:PlantLoopCoolingDemand 4038.88 0.00 01-JAN-05:20 510737.79 21-JUL-21:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 07-FEB-21:50
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 07-FEB-21:50
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 07-FEB-21:50
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 07-FEB-21:50
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 07-FEB-21:50
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 07-FEB-21:50
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 05-JAN-08:00
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 05-JAN-08:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 20323.74 118021.42 16-JAN-14:50 1967524.41 21-JUL-21:00
EnergyTransfer:Building 5220.70 85909.18 26-DEC-15:00 301432.29 07-AUG-19:10
EnergyTransfer:Zone:KITCHEN_FLR_6 712.47 9574.40 27-DEC-04:00 34676.84 02-JUL-10:40
Refrigeration:EnergyTransfer 182.53 4016.66 08-MAR-23:10 10359.21 21-JUL-06:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.27 2008.33 08-MAR-23:10 5179.60 21-JUL-06:20
General:Refrigeration:EnergyTransfer 91.27 2008.33 08-MAR-23:10 5179.60 21-JUL-06:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.27 2008.33 08-MAR-23:10 5179.60 21-JUL-06:20
EnergyTransfer:Plant 10425.17 16781.21 01-NOV-15:10 1174295.57 21-JUL-21:00
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.58 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 69.69 1995.95 20-MAY-03:20 2552.82 16-OCT-13:40
EnergyTransfer:Zone:BASEMENT 357.64 7191.49 26-MAR-15:00 20503.50 22-SEP-21:00
Heating:EnergyTransfer 19.49 0.00 01-JAN-08:00 31831.50 26-DEC-16:20
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 19.49 0.00 01-JAN-08:00 31831.50 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 5109.95 82886.43 26-DEC-15:00 297866.99 07-AUG-19:10
Cooling:EnergyTransfer:Zone:BASEMENT 357.64 7191.49 26-MAR-15:00 20503.50 22-SEP-21:00
General:Cooling:EnergyTransfer 5109.95 82886.43 26-DEC-15:00 297866.99 07-AUG-19:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 357.64 7191.49 26-MAR-15:00 20503.50 22-SEP-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 38.78 0.25 30-DEC-07:30 3059.60 18-OCT-13:00
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.01 0.00 01-JAN-00:10 511.38 27-DEC-07:30
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.01 0.00 01-JAN-00:10 511.38 27-DEC-07:30
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 38.77 0.00 26-JAN-07:10 3059.60 18-OCT-13:00
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 38.77 0.00 26-JAN-07:10 3059.60 18-OCT-13:00
EnergyTransfer:Zone:RETAIL_2_FLR_1 37.09 633.91 26-DEC-15:00 2043.34 07-AUG-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 37.09 633.91 26-DEC-15:00 2043.34 07-AUG-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 37.09 633.91 26-DEC-15:00 2043.34 07-AUG-21:00
EnergyTransfer:Zone:MECH_FLR_1 15.42 16.98 28-DEC-11:30 1994.89 15-JUN-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 15.42 16.98 28-DEC-11:30 1994.89 15-JUN-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 15.42 16.98 28-DEC-11:30 1994.89 15-JUN-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 19.04 6.68 27-DEC-08:10 954.84 06-AUG-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 19.04 6.68 27-DEC-08:10 954.84 06-AUG-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 19.04 6.68 27-DEC-08:10 954.84 06-AUG-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 598.65 8192.16 27-DEC-05:00 39470.87 15-JUN-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 598.65 8192.16 27-DEC-05:00 39470.87 15-JUN-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 598.65 8192.16 27-DEC-05:00 39470.87 15-JUN-20:00
EnergyTransfer:Zone:CAFE_FLR_1 254.86 2364.02 26-DEC-11:30 11023.67 22-OCT-10:40
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 254.86 2364.02 26-DEC-11:30 11023.67 22-OCT-10:40
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 254.86 2364.02 26-DEC-11:30 11023.67 22-OCT-10:40
EnergyTransfer:Zone:LOBBY_FLR_1 800.40 16351.68 26-DEC-15:00 39985.68 07-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 800.40 16351.68 26-DEC-15:00 39985.68 07-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 800.40 16351.68 26-DEC-15:00 39985.68 07-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 64.67 0.00 01-JAN-08:00 7495.09 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 2.07 0.00 01-JAN-00:10 3720.04 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 2.07 0.00 01-JAN-00:10 3720.04 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 62.60 0.00 01-JAN-04:00 7495.09 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 62.60 0.00 01-JAN-04:00 7495.09 15-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 54.15 0.00 01-JAN-08:00 7515.18 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 4.14 0.00 01-JAN-08:00 4138.67 27-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 4.14 0.00 01-JAN-08:00 4138.67 27-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 50.02 0.00 01-JAN-00:10 7515.18 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 50.02 0.00 01-JAN-00:10 7515.18 15-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 359.63 0.00 01-JAN-03:10 36803.78 22-OCT-13:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 359.63 0.00 01-JAN-03:10 36803.78 22-OCT-13:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 359.63 0.00 01-JAN-03:10 36803.78 22-OCT-13:20
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 424.52 0.00 01-JAN-08:00 52253.44 11-JUN-08:40
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 1.97 0.00 01-JAN-00:10 12432.00 27-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 1.97 0.00 01-JAN-00:10 12432.00 27-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 422.55 0.00 01-JAN-08:00 52253.44 11-JUN-08:40
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 422.55 0.00 01-JAN-08:00 52253.44 11-JUN-08:40
EnergyTransfer:Zone:ROOM_5_FLR_3 65.70 0.00 01-JAN-08:00 6626.35 17-JUN-08:20
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 2.21 0.00 01-JAN-00:10 3594.04 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 2.21 0.00 01-JAN-00:10 3594.04 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 63.50 0.00 01-JAN-03:30 6626.35 17-JUN-08:20
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 63.50 0.00 01-JAN-03:30 6626.35 17-JUN-08:20
EnergyTransfer:Zone:ROOM_6_FLR_3 54.60 0.00 01-JAN-08:00 7095.14 14-JUN-08:20
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 4.21 0.00 01-JAN-08:00 4051.63 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 4.21 0.00 01-JAN-08:00 4051.63 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 50.39 0.00 01-JAN-00:10 7095.14 14-JUN-08:20
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 50.39 0.00 01-JAN-00:10 7095.14 14-JUN-08:20
EnergyTransfer:Zone:CORRIDOR_FLR_3 176.71 150.28 27-DEC-07:20 8835.66 16-JUN-21:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 176.71 150.28 27-DEC-07:20 8835.66 16-JUN-21:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 176.71 150.28 27-DEC-07:20 8835.66 16-JUN-21:10
EnergyTransfer:Zone:ROOM_1_FLR_6 16.70 0.00 01-JAN-08:00 2011.22 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 1.37 0.00 01-JAN-08:00 1146.02 26-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 1.37 0.00 01-JAN-08:00 1146.02 26-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 15.34 0.00 01-JAN-00:10 2011.22 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 15.34 0.00 01-JAN-00:10 2011.22 15-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 14.79 0.00 01-JAN-08:00 2015.43 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 2.27 0.00 01-JAN-08:00 1196.39 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 2.27 0.00 01-JAN-08:00 1196.39 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 12.52 0.00 01-JAN-00:10 2015.43 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 12.52 0.00 01-JAN-00:10 2015.43 15-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 98.31 0.00 01-JAN-08:00 9368.69 04-OCT-15:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 1.23 0.00 01-JAN-00:10 3362.80 27-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 1.23 0.00 01-JAN-00:10 3362.80 27-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 97.08 0.00 01-JAN-08:00 9368.69 04-OCT-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 97.08 0.00 01-JAN-08:00 9368.69 04-OCT-15:20
EnergyTransfer:Zone:BANQUET_FLR_6 478.37 9589.63 26-DEC-15:00 22061.35 16-JUN-22:00
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 478.37 9589.63 26-DEC-15:00 22061.35 16-JUN-22:00
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 478.37 9589.63 26-DEC-15:00 22061.35 16-JUN-22:00
EnergyTransfer:Zone:DINING_FLR_6 502.02 10822.33 26-DEC-12:00 23389.88 15-JUN-21:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 502.02 10822.33 26-DEC-12:00 23389.88 15-JUN-21:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 502.02 10822.33 26-DEC-12:00 23389.88 15-JUN-21:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 621.21 7308.24 27-DEC-04:00 29596.01 02-JUL-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 621.21 7308.24 27-DEC-04:00 29596.01 02-JUL-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 76.16 2.33 31-DEC-05:40 6030.83 03-JUL-15:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.02 0.00 01-JAN-00:10 1006.62 27-DEC-07:30
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.02 0.00 01-JAN-00:10 1006.62 27-DEC-07:30
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 76.14 0.00 27-JAN-07:10 6030.83 03-JUL-15:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 76.14 0.00 27-JAN-07:10 6030.83 03-JUL-15:10
PlantLoopHeatingDemand:Facility 891.17 7205.29 31-JUL-00:50 161864.28 28-JAN-07:30
PlantLoopHeatingDemand:Plant 648.50 7205.29 31-JUL-00:50 50252.65 27-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 648.50 7205.29 31-JUL-00:50 50252.65 27-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 648.50 7205.29 31-JUL-00:50 50252.65 27-JAN-07:10
EnergyTransfer:HVAC 4677.87 0.00 01-NOV-15:10 553623.26 21-JUL-18:10
HeatingCoils:EnergyTransfer 242.67 0.00 01-JAN-11:00 125264.66 27-DEC-04:10
PlantLoopHeatingDemand:HVAC 242.67 0.00 01-JAN-11:00 125264.66 27-DEC-04:10
HeatingCoils:PlantLoopHeatingDemand 242.67 0.00 01-JAN-11:00 125264.66 27-DEC-04:10
CoolingCoils:EnergyTransfer 4038.88 0.00 01-JAN-05:20 510737.79 21-JUL-21:00
HeatRecoveryForHeating:EnergyTransfer 225.29 0.00 01-JAN-08:00 199626.21 03-FEB-07:00
HeatRecoveryForCooling:EnergyTransfer 171.03 0.00 01-JAN-00:10 100522.70 21-JUL-18:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 648.50 7205.29 31-JUL-00:50 50252.65 27-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 648.50 7205.29 31-JUL-00:50 50252.65 27-JAN-07:10
Boilers:EnergyTransfer 239.94 0.00 01-JAN-11:00 131171.62 02-FEB-03:30
Chillers:EnergyTransfer 4099.32 0.00 01-JAN-05:20 511025.55 21-JUL-21:00
HeatRejection:EnergyTransfer 5346.14 0.00 01-JAN-05:20 631945.84 21-JUL-21:00
General:HeatRejection:EnergyTransfer 5346.14 0.00 01-JAN-05:20 631945.84 21-JUL-21:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -357.638 0.000 0.000 141.727 92.464 143.105 0.000 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -19.658
RETAIL_1_FLR_1 0.000 0.000 0.008 -38.769 0.000 0.000 14.356 4.184 10.186 19.851 0.000 0.451 0.001 0.000 -5.115 0.000 -2.264 -2.889
RETAIL_2_FLR_1 0.000 0.000 0.000 -37.090 0.000 0.000 16.592 4.846 11.795 0.000 0.000 0.194 4.532 0.000 0.000 0.000 -0.869 -0.000
MECH_FLR_1 0.000 0.000 0.000 -15.420 0.000 0.000 3.390 8.670 12.471 0.000 0.000 0.410 0.000 0.000 0.000 0.000 -2.212 -7.309
STORAGE_FLR_1 0.000 0.000 0.000 -19.042 0.000 0.000 2.871 1.987 3.598 0.000 0.000 0.296 11.342 0.000 0.000 0.000 -1.052 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -598.659 0.000 0.000 10.551 3.699 658.131 0.000 0.000 0.560 0.000 0.000 0.000 0.000 -3.145 -71.137
CAFE_FLR_1 0.000 0.000 0.000 -254.867 0.000 0.000 191.993 6.684 14.341 56.921 0.000 1.250 2.228 0.000 -13.685 0.000 -4.865 -0.000
LOBBY_FLR_1 0.000 0.000 0.000 -800.403 0.000 0.000 549.072 78.743 148.998 74.136 0.000 3.221 0.000 0.000 -19.171 0.000 -14.786 -19.811
ROOM_1_FLR_3 3.545 -53.547 0.000 -10.521 0.000 0.000 9.630 4.922 10.478 42.442 0.000 1.609 6.958 0.000 -10.380 0.000 -5.136 -0.001
ROOM_2_FLR_3 6.223 -41.234 0.000 -10.865 0.000 0.000 9.551 4.922 10.477 31.655 0.000 1.484 3.995 0.000 -10.740 0.000 -5.467 -0.001
ROOM_3_MULT19_FLR_3 0.000 -344.636 0.000 -14.993 0.000 0.000 0.000 58.777 194.997 223.338 0.000 2.970 1.887 0.000 -83.233 0.000 -39.106 -0.001
ROOM_4_MULT19_FLR_3 11.164 -286.850 0.000 -144.879 0.000 0.000 182.389 58.793 195.050 81.841 0.000 8.597 0.002 0.000 -57.102 0.000 -36.740 -12.263
ROOM_5_FLR_3 3.699 -54.468 0.000 -10.519 0.000 0.000 9.626 4.922 10.478 42.744 0.000 1.613 7.137 0.000 -10.062 0.000 -5.171 -0.001
ROOM_6_FLR_3 6.249 -41.536 0.000 -10.899 0.000 0.000 9.546 4.922 10.477 31.622 0.000 1.478 3.735 0.000 -10.146 0.000 -5.448 -0.001
CORRIDOR_FLR_3 0.000 0.000 0.000 -176.710 0.000 0.000 114.444 54.592 0.000 36.268 0.000 1.406 0.001 0.000 -13.575 0.000 -5.961 -10.464
ROOM_1_FLR_6 1.904 -13.241 0.000 -2.632 0.000 0.000 2.410 1.231 2.620 10.578 0.000 0.401 0.565 0.000 -2.532 0.000 -1.304 -0.000
ROOM_2_FLR_6 2.916 -10.462 0.000 -2.710 0.000 0.000 2.392 1.230 2.619 7.899 0.000 0.368 0.000 0.000 -2.614 0.000 -1.385 -0.254
ROOM_3_MULT9_FLR_6 2.676 -81.608 0.000 -16.923 0.000 0.000 21.635 6.962 23.098 53.259 0.000 1.983 7.460 0.000 -11.721 0.000 -6.822 -0.001
BANQUET_FLR_6 0.000 0.000 0.000 -478.373 0.000 0.000 328.294 14.626 175.857 9.183 0.000 0.738 0.000 0.000 -7.068 0.000 -3.265 -39.991
DINING_FLR_6 0.000 0.000 0.000 -502.026 0.000 0.000 323.771 14.626 175.857 8.918 0.000 0.705 0.000 0.000 -7.389 0.000 -3.355 -11.106
KITCHEN_FLR_6 0.000 0.000 0.000 -621.195 0.000 0.000 27.948 9.139 540.650 25.689 0.000 0.560 24.458 0.000 -4.016 0.000 -3.232 -0.000
CORRIDOR_FLR_6 0.000 0.000 0.019 -76.140 0.000 0.000 29.168 14.444 0.000 17.291 0.000 0.547 23.952 0.000 -6.416 0.000 -2.865 -0.000
Total Facility 38.378 -927.582 0.027 -4201.274 0.000 0.000 2001.358 455.384 2355.282 773.635 0.000 30.842 98.256 0.000 -274.966 0.000 -154.452 -194.887


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 22-SEP-21:00 0.00 0.00 0.00 -20503.92 0.00 0.00 5924.45 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1267.46
RETAIL_1_FLR_1 18-OCT-13:00 0.00 0.00 0.00 -3059.58 0.00 0.00 150.60 95.05 252.59 3580.92 0.00 38.38 0.00 0.00 -0.00 0.00 0.00 -1057.96
RETAIL_2_FLR_1 07-AUG-21:00 0.00 0.00 0.00 -2043.38 0.00 0.00 697.61 352.23 752.15 0.00 0.00 29.59 211.80 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 15-JUN-20:00 0.00 0.00 0.00 -1995.02 0.00 0.00 129.08 708.98 839.45 0.00 0.00 88.47 229.03 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 06-AUG-10:35 0.00 0.00 0.00 -957.42 0.00 0.00 44.61 54.17 101.96 0.00 0.00 44.33 712.35 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 15-JUN-20:00 0.00 0.00 0.00 -39471.63 0.00 0.00 408.86 302.47 44299.38 0.00 0.00 120.81 0.00 0.00 -0.00 0.00 0.00 -5659.89
CAFE_FLR_1 22-OCT-10:35 0.00 0.00 0.00 -11119.16 0.00 0.00 2999.30 59.42 406.43 9952.47 0.00 0.00 0.00 0.00 -0.00 0.00 -32.84 -2265.62
LOBBY_FLR_1 07-AUG-21:10 0.00 0.00 0.00 -39989.23 0.00 0.00 26440.11 4544.88 7389.94 590.36 0.00 456.69 567.25 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_3 15-JUN-18:03 0.00 -7017.66 0.00 -673.05 0.00 0.00 335.50 337.19 484.65 4620.31 0.00 290.83 1622.23 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 19-JUN-18:51 0.00 -7450.76 0.00 -800.13 0.00 0.00 289.30 337.15 484.60 1140.94 0.00 53.34 5945.55 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 22-OCT-13:15 0.00 -36806.97 0.00 0.00 0.00 0.00 0.00 1492.91 2548.95 41454.95 0.00 0.00 0.00 0.00 -0.00 0.00 -93.00 -8596.83
ROOM_4_MULT19_FLR_3 14-JUN-08:11 0.00 -49007.92 0.00 -9617.83 0.00 0.00 1612.28 1991.09 8433.45 7674.61 0.00 525.44 38388.89 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 18-JUN-08:62 0.00 -6260.64 0.00 -677.56 0.00 0.00 130.71 212.17 653.23 5891.13 0.00 79.30 0.00 0.00 -0.00 0.00 0.00 -28.33
ROOM_6_FLR_3 14-JUN-08:11 0.00 -7192.29 0.00 -836.90 0.00 0.00 71.66 166.68 452.99 6100.67 0.00 54.15 1183.04 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 16-JUN-21:10 0.00 0.00 0.00 -8836.95 0.00 0.00 5246.09 2976.30 0.00 429.54 0.00 235.83 0.00 0.00 -0.00 0.00 0.00 -50.82
ROOM_1_FLR_6 15-JUN-18:03 0.00 -1884.23 0.00 -168.97 0.00 0.00 83.87 84.30 121.16 1149.93 0.00 72.14 541.80 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 19-JUN-18:51 0.00 -1990.89 0.00 -202.90 0.00 0.00 71.14 84.29 121.15 280.34 0.00 11.98 1624.90 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 05-SEP-15:12 0.00 -8636.58 0.00 -1079.73 0.00 0.00 529.37 150.05 441.28 3124.31 0.00 213.51 5257.79 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 16-JUN-22:00 0.00 0.00 0.00 -22069.74 0.00 0.00 15643.66 948.68 6747.90 275.71 0.00 98.98 0.00 0.00 -0.00 0.00 0.00 -1645.19
DINING_FLR_6 15-JUN-21:10 0.00 0.00 0.00 -23391.82 0.00 0.00 15644.51 948.68 6747.90 240.54 0.00 118.64 0.00 0.00 -0.00 0.00 0.00 -308.45
KITCHEN_FLR_6 02-JUL-10:35 0.00 0.00 0.00 -29595.00 0.00 0.00 464.21 249.14 23951.61 2375.96 0.00 102.65 2451.44 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 03-JUL-15:10 0.00 0.00 0.00 -6031.24 0.00 0.00 771.14 328.12 0.00 906.05 0.00 160.89 3865.05 0.00 -0.00 0.00 0.00 0.00
Total Facility 20-SEP-18:02 0.00 -108549.24 0.00 -192020.06 0.00 0.00 76343.57 33461.95 120174.13 5608.16 0.00 4107.55 60873.94 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 27-DEC-07:30 0.00 0.00 511.30 0.00 0.00 0.00 358.03 190.11 433.01 0.00 0.00 0.00 0.00 0.00 -738.15 0.00 -284.37 -469.92
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 26-DEC-16:11 8520.78 289.59 0.00 -289.59 0.00 0.00 290.15 106.08 200.18 0.00 0.00 0.00 0.00 0.00 -917.42 0.00 -460.95 -7738.83
ROOM_2_FLR_3 27-DEC-09:01 8594.20 268.40 0.00 -268.40 0.00 0.00 108.88 166.68 452.99 0.00 0.00 0.00 0.00 0.00 -534.52 0.00 -529.02 -8259.22
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 26-DEC-16:11 48206.71 4725.35 0.00 -4725.35 0.00 0.00 5212.46 1267.05 3726.41 0.00 0.00 0.00 0.00 0.00 -5617.92 0.00 -2566.88 -50227.82
ROOM_5_FLR_3 26-DEC-16:11 8249.07 284.15 0.00 -284.15 0.00 0.00 290.85 106.08 200.18 0.00 0.00 0.00 0.00 0.00 -968.56 0.00 -458.81 -7418.82
ROOM_6_FLR_3 26-DEC-16:11 8304.40 266.39 0.00 -266.39 0.00 0.00 293.98 106.07 200.16 0.00 0.00 0.00 0.00 0.00 -964.81 0.00 -451.81 -7487.99
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 26-DEC-16:11 2584.15 68.89 0.00 -68.89 0.00 0.00 73.50 26.52 50.05 0.00 0.00 0.00 0.00 0.00 -220.36 0.00 -114.26 -2399.59
ROOM_2_FLR_6 26-DEC-16:11 2585.53 68.38 0.00 -68.38 0.00 0.00 73.50 26.52 50.04 0.00 0.00 0.00 0.00 0.00 -222.26 0.00 -114.06 -2399.26
ROOM_3_MULT9_FLR_6 26-DEC-16:11 11863.09 546.98 0.00 -546.98 0.00 0.00 631.13 150.05 441.28 0.00 0.00 0.00 0.00 0.00 -1139.57 0.00 -555.41 -11390.58
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 27-DEC-07:30 0.00 0.00 1006.56 0.00 0.00 0.00 733.34 656.24 0.00 0.00 0.00 0.00 0.00 0.00 -947.84 0.00 -354.63 -1093.67
Total Facility 26-DEC-16:11 5421.74 99999.69 0.00 -99999.69 0.00 0.00 60155.34 10072.63 73604.29 0.00 0.00 0.00 0.00 0.00 -24637.56 0.00 -12806.40 -111810.03



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 23.2611 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 23.1496 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 13.4337 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.5364 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.003540 12.5400 0.000610 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.003540 142.3000 0.000914 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.000963 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4716 2.4716 1.2827 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3186 0.3186 0.1189 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2428 0.2428 0.1377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2595 0.2595 0.0026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1260 0.1260 0.0867 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.7630 3.7630 0.0376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4707 1.4707 1.0148 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0517 5.0517 2.8391 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3074 1.3074 0.7126 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4379 2.4379 1.7821 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5594 2.5594 1.7813 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4874 2.4874 0.5522 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7651 0.7651 0.1882 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 23.2611 23.1496 23.2611 10.5364 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2827 1.2827 1.2827 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1593 0.1593 0.1189 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1377 0.1377 0.1377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1297 0.1297 0.0026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0867 0.0867 0.0867 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8815 1.8815 0.0376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0148 1.0148 1.0148 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8391 2.8391 2.8391 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7126 0.7126 0.7126 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7821 1.7821 1.7821 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7813 1.7813 1.7813 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2437 1.2437 0.5522 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3826 0.3826 0.1882 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 13.4337 10.5364 10.5364 10.5364 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 582.33
Number of hours not met 582.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 273.67 150833.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1246.82 133869.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 455.38 37630.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 150.51 9571.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 21.47 1270.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 366.65 22430.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.45 157.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 624.00 47005.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 74.88 3618.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 95.30 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.73 2405.59 210423.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.82 1306.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 21.02 715.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1692.39 4820.60
Natural Gas 1788.84 4468.11
Additional 0.00 0.00
Total 3481.23 9288.70


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 254.56
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 40.14
Space Heating 0.00
Space Cooling 109.90
Fans (All) 55.00
Service Water Heating 8.00
Receptacle Equipment 145.30
Miscellaneous (All) 424.90
Subtotal 424.90


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 24.12
Service Water Heating 212.03
Miscellaneous (All) 393.83
Subtotal 393.83


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 4.90
Space Heating 2.95
Space Cooling 13.42
Fans (All) 6.72
Service Water Heating 26.87
Receptacle Equipment 37.01
Miscellaneous 8.13


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
PV_SCH 8760. 8760.
LTG_SCH_KITCHEN 2022. 8760.
LTG_SCH_DINING 1877. 8760.
LTG_SCH_BASEMENT 2095. 8760.
LTG_SCH_LOBBY 2166. 8760.
LTG_SCH_STORAGE 1543. 8760.
LTG_SCH_MECHANIC 2022. 8760.
LTG_SCH_LAUNDRY 2527. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2166. 8760.
LTG_SCH_RETAIL 2296. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 7961.00 799.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8743.50 16.50 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 7961.00 0.00 0.00 0.00 0.00
Max 8760.00 799.00 0.00 0.00 0.00
Average 8722.93 37.07 0.00 0.00 0.00
Sum 191904.50 815.50 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8741.00 19.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8759.50 0.50 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8333.17 426.83 0.00 0.00 0.00
LOBBY_FLR_1 8249.50 510.50 0.00 0.00 0.00
ROOM_1_FLR_3 8759.83 0.17 0.00 0.00 0.00
ROOM_2_FLR_3 8718.33 41.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 7601.50 1158.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8750.67 9.33 0.00 0.00 0.00
ROOM_5_FLR_3 8759.83 0.17 0.00 0.00 0.00
ROOM_6_FLR_3 8639.17 120.83 0.00 0.00 0.00
CORRIDOR_FLR_3 8736.00 24.00 0.00 0.00 0.00
ROOM_1_FLR_6 8758.83 1.17 0.00 0.00 0.00
ROOM_2_FLR_6 8712.17 47.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8758.67 1.33 0.00 0.00 0.00
BANQUET_FLR_6 8308.33 451.67 0.00 0.00 0.00
DINING_FLR_6 8318.83 441.17 0.00 0.00 0.00
KITCHEN_FLR_6 8754.50 5.50 0.00 0.00 0.00
CORRIDOR_FLR_6 8749.67 10.33 0.00 0.00 0.00
Min 7601.50 0.00 0.00 0.00 0.00
Max 8760.00 1158.50 0.00 0.00 0.00
Average 8611.34 148.66 0.00 0.00 0.00
Sum 189449.50 3270.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50009.00 170.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59150.50 5.50 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 655916.67 54500.33 0.00 0.00 0.00
LOBBY_FLR_1 1933906.17 181522.83 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4152.67 1.33 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4153.17 0.83 0.00 0.00 0.00
CORRIDOR_FLR_3 99928.67 429.33 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4149.17 4.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1147625.00 98090.00 0.00 0.00 0.00
DINING_FLR_6 1151147.83 94567.17 0.00 0.00 0.00
KITCHEN_FLR_6 108247.00 22.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105761.67 184.33 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1933906.17 181522.83 0.00 0.00 0.00
Average 269364.39 19522.66 0.00 0.00 0.00
Sum 5926016.50 429498.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:28

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.286830E+11 12537.79 12-JAN-19:10 15.03 8.30 0.778117E+10 4821.86 06-JAN-22:10 15.03 8.30
February 0.227899E+11 11906.13 01-FEB-21:00 3.30 -1.9 0.638456E+10 4669.14 01-FEB-22:10 1.78 -2.6
March 0.226376E+11 10466.84 01-MAR-21:00 1.70 -3.0 0.655605E+10 4211.29 01-MAR-22:10 1.02 -3.3
April 0.229404E+11 11238.50 30-APR-10:35 24.07 13.08 0.640801E+10 4120.58 07-APR-22:10 24.07 13.08
May 0.253946E+11 11827.62 21-MAY-10:35 29.47 14.38 0.685523E+10 4254.92 12-MAY-22:10 29.47 14.38
June 0.262836E+11 12642.97 15-JUN-18:10 35.92 14.47 0.687607E+10 4403.07 23-JUN-22:10 23.40 15.27
July 0.307860E+11 14071.11 26-JUL-18:10 33.77 19.75 0.778951E+10 4837.08 18-JUL-22:10 33.77 19.75
August 0.345491E+11 17781.69 24-AUG-21:00 26.70 16.71 0.819077E+10 4837.20 11-AUG-04:30 26.70 16.71
September 0.376499E+11 20503.50 22-SEP-21:00 25.00 17.90 0.795786E+10 4837.35 19-SEP-04:10 25.00 17.90
October 0.382490E+11 20339.36 31-OCT-21:00 10.60 4.66 0.822093E+10 4837.29 10-OCT-21:19 10.60 4.66
November 0.352034E+11 19797.54 01-NOV-21:00 10.00 7.90 0.794489E+10 4837.37 01-NOV-01:10 10.00 7.90
December 0.324697E+11 17773.78 01-DEC-22:00 7.20 2.26 0.816938E+10 4837.14 13-DEC-00:40 7.57 6.48
                     
Annual Sum or Average 0.357636E+12         0.891344E+11        
Minimum of Months 0.226376E+11 10466.84   1.70 -3.0 0.638456E+10 4120.58   1.02 -3.3
Maximum of Months 0.382490E+11 20503.50   35.92 19.75 0.822093E+10 4837.37   33.77 19.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.236017E+10 2328.25 12-JAN-13:50 18.03 9.58 0.693294E+09 471.31 12-JAN-22:19 9.47 5.03
February 0.228774E+10 2400.21 07-FEB-13:30 20.30 9.54 0.639447E+09 491.78 06-FEB-22:30 20.30 9.54
March 0.250272E+10 1913.09 16-MAR-13:20 22.40 9.11 0.724947E+09 491.84 16-MAR-22:10 15.27 5.99
April 0.291581E+10 2012.05 03-APR-14:10 26.70 11.67 0.760670E+09 491.84 28-APR-22:10 21.52 12.87
May 0.340994E+10 2049.04 19-MAY-20:10 30.92 14.42 0.819807E+09 491.85 18-MAY-00:10 30.92 14.42
June 0.395302E+10 2371.60 15-JUN-18:17 35.73 14.50 0.810177E+09 491.85 30-JUN-22:10 28.43 17.10
July 0.412516E+10 2363.18 26-JUL-18:05 33.77 19.75 0.834873E+09 491.84 05-JUL-21:00 33.77 19.75
August 0.416714E+10 2480.33 27-AUG-12:00 33.30 15.93 0.835520E+09 491.86 11-AUG-04:10 33.30 15.93
September 0.418478E+10 2966.20 20-SEP-12:50 32.12 17.95 0.803053E+09 491.84 28-SEP-22:10 24.40 12.24
October 0.378657E+10 3059.60 18-OCT-13:00 27.80 18.14 0.801173E+09 491.85 10-OCT-21:10 27.80 18.14
November 0.289911E+10 2908.95 10-NOV-12:00 21.10 12.09 0.715032E+09 491.84 08-NOV-23:10 21.10 12.09
December 0.217642E+10 2138.84 16-DEC-13:30 14.45 3.99 0.679990E+09 455.44 15-DEC-22:30 14.45 3.99
                     
Annual Sum or Average 0.387686E+11         0.911798E+10        
Minimum of Months 0.217642E+10 1913.09   14.45 3.99 0.639447E+09 455.44   9.47 3.99
Maximum of Months 0.418478E+10 3059.60   35.73 19.75 0.835520E+09 491.86   33.77 19.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.265055E+10 1271.71 12-JAN-21:00 12.80 7.31 0.828763E+09 546.42 12-JAN-22:49 7.77 3.93
February 0.245772E+10 1316.81 21-FEB-21:00 15.00 4.44 0.758936E+09 559.26 21-FEB-22:40 11.47 3.03
March 0.279403E+10 1340.04 16-MAR-18:10 19.82 7.14 0.856326E+09 567.00 16-MAR-21:40 16.47 6.01
April 0.300349E+10 1602.22 28-APR-20:55 22.80 12.84 0.875674E+09 569.55 28-APR-22:10 21.52 12.87
May 0.336299E+10 1803.61 19-MAY-21:00 30.00 13.65 0.936171E+09 569.56 18-MAY-00:10 30.00 13.65
June 0.352048E+10 2029.08 15-JUN-21:00 33.30 13.72 0.924095E+09 569.56 30-JUN-22:10 28.43 17.10
July 0.364349E+10 1991.57 26-JUL-21:00 28.90 18.16 0.952028E+09 569.55 18-JUL-22:10 28.90 18.16
August 0.361485E+10 2043.34 07-AUG-21:00 31.70 16.85 0.954523E+09 569.57 11-AUG-04:10 24.22 15.27
September 0.342947E+10 1918.61 20-SEP-21:00 24.40 15.12 0.919649E+09 569.55 28-SEP-22:10 24.40 12.24
October 0.322994E+10 1835.45 05-OCT-21:00 23.30 16.16 0.923339E+09 569.56 10-OCT-21:10 14.13 9.16
November 0.278834E+10 1462.13 09-NOV-22:00 18.90 11.06 0.843242E+09 569.54 08-NOV-23:10 18.90 11.06
December 0.259438E+10 1228.15 07-DEC-21:00 9.40 3.58 0.818299E+09 535.22 15-DEC-23:10 13.80 4.57
                     
Annual Sum or Average 0.370897E+11         0.105910E+11        
Minimum of Months 0.245772E+10 1228.15   9.40 3.58 0.758936E+09 535.22   7.77 3.03
Maximum of Months 0.364349E+10 2043.34   33.30 18.16 0.954523E+09 569.57   30.00 18.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 66970860.93 334.20 03-JAN-22:00 12.80 6.21 0.188813E+09 120.45 11-JAN-22:10 11.10 5.44
February 97509760.80 525.93 07-FEB-21:55 15.00 7.49 0.174209E+09 120.45 23-FEB-23:00 7.80 4.30
March 0.192612E+09 753.44 16-MAR-21:00 17.20 5.94 0.198796E+09 120.46 10-MAR-22:10 17.20 5.94
April 0.951576E+09 1317.13 21-APR-20:00 26.10 11.77 0.198251E+09 120.46 17-APR-01:10 26.10 11.77
May 0.195114E+10 1668.03 31-MAY-20:00 29.40 14.60 0.205442E+09 120.46 18-MAY-03:09 29.40 14.60
June 0.271806E+10 1994.89 15-JUN-20:00 33.90 14.00 0.199179E+09 120.46 30-JUN-22:10 28.43 17.10
July 0.289572E+10 1956.64 03-JUL-20:00 28.30 19.12 0.205008E+09 120.46 05-JUL-21:00 27.80 17.53
August 0.267176E+10 1950.96 07-AUG-20:00 31.70 17.36 0.205876E+09 120.46 22-AUG-00:10 24.22 16.48
September 0.218620E+10 1664.52 22-SEP-20:00 26.10 18.64 0.198649E+09 120.46 19-SEP-04:19 26.10 18.64
October 0.132006E+10 1538.52 05-OCT-20:00 23.90 16.65 0.205105E+09 120.46 10-OCT-21:19 13.87 9.12
November 0.310548E+09 1001.79 09-NOV-21:00 20.00 11.27 0.193309E+09 120.45 01-NOV-01:10 20.00 11.27
December 58098745.94 207.20 15-DEC-22:00 14.40 4.62 0.185845E+09 120.45 11-DEC-22:19 14.40 4.62
                     
Annual Sum or Average 0.154202E+11         0.235848E+10        
Minimum of Months 58098745.94 207.20   12.80 4.62 0.174209E+09 120.45   7.80 4.30
Maximum of Months 0.289572E+10 1994.89   33.90 19.12 0.205876E+09 120.46   29.40 18.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109461E+10 643.80 01-JAN-11:35 13.87 8.54 0.117386E+09 72.82 03-JAN-22:49 10.97 5.44
February 0.110224E+10 695.13 20-FEB-11:35 20.37 8.19 0.107225E+09 75.20 07-FEB-23:10 20.37 8.19
March 0.137563E+10 716.47 16-MAR-10:35 20.03 8.28 0.120846E+09 76.95 16-MAR-21:49 16.28 6.02
April 0.162201E+10 840.67 30-APR-10:35 24.07 13.08 0.126012E+09 83.43 21-APR-22:10 24.07 13.08
May 0.186630E+10 889.35 31-MAY-18:10 30.92 15.25 0.138970E+09 87.66 31-MAY-22:10 27.12 13.11
June 0.196647E+10 954.00 18-JUN-10:35 32.43 16.35 0.141830E+09 91.12 16-JUN-21:49 32.43 16.35
July 0.204406E+10 955.46 03-JUL-18:10 36.28 18.94 0.146503E+09 90.74 03-JUL-21:49 26.20 18.51
August 0.200199E+10 957.34 06-AUG-10:35 31.67 18.03 0.145456E+09 91.19 07-AUG-21:49 29.45 17.70
September 0.186511E+10 905.74 23-SEP-10:35 27.23 18.46 0.136914E+09 87.90 22-SEP-22:10 27.23 18.46
October 0.174001E+10 874.06 05-OCT-10:35 27.60 18.63 0.133679E+09 86.24 05-OCT-22:10 22.98 16.25
November 0.139232E+10 765.12 10-NOV-11:35 20.93 12.02 0.118912E+09 79.71 09-NOV-22:40 20.93 12.02
December 0.971178E+09 647.00 16-DEC-11:35 12.77 3.51 0.117168E+09 72.24 15-DEC-23:10 12.77 3.51
                     
Annual Sum or Average 0.190419E+11         0.155090E+10        
Minimum of Months 0.971178E+09 643.80   12.77 3.51 0.107225E+09 72.24   10.97 3.51
Maximum of Months 0.204406E+10 957.34   36.28 18.94 0.146503E+09 91.19   32.43 18.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.481966E+11 37468.57 12-JAN-21:00 12.80 7.31 0.649338E+09 381.58 05-JAN-05:40 12.80 7.31
February 0.440687E+11 37799.38 21-FEB-20:55 15.00 4.44 0.587076E+09 381.62 06-FEB-22:10 15.00 4.44
March 0.494930E+11 37950.35 16-MAR-20:00 17.20 5.94 0.652391E+09 381.64 16-MAR-21:10 17.02 5.96
April 0.494091E+11 38755.76 28-APR-20:00 25.00 12.84 0.629512E+09 381.81 17-APR-01:10 25.00 12.84
May 0.522978E+11 39085.86 30-MAY-20:00 28.90 14.28 0.650735E+09 381.77 03-MAY-21:10 28.90 14.28
June 0.516610E+11 39470.87 15-JUN-20:00 33.90 14.00 0.630908E+09 381.81 16-JUN-21:10 32.52 14.90
July 0.531378E+11 39427.18 26-JUL-20:00 29.40 19.17 0.649359E+09 381.74 25-JUL-21:10 29.40 19.17
August 0.530607E+11 39382.62 04-AUG-20:00 33.30 17.89 0.652125E+09 381.78 25-AUG-21:10 27.62 14.77
September 0.507828E+11 39072.44 20-SEP-20:00 25.60 15.27 0.629238E+09 381.79 19-SEP-21:10 25.60 15.27
October 0.509652E+11 38846.69 05-OCT-20:00 23.90 16.65 0.649683E+09 381.75 03-OCT-21:19 23.90 16.65
November 0.477226E+11 38134.47 09-NOV-21:00 20.00 11.27 0.628143E+09 381.68 22-NOV-22:10 10.22 3.96
December 0.478592E+11 37271.24 15-DEC-21:00 14.40 4.76 0.649346E+09 381.59 13-DEC-00:10 14.40 4.76
                     
Annual Sum or Average 0.598654E+12         0.765785E+10        
Minimum of Months 0.440687E+11 37271.24   12.80 4.44 0.587076E+09 381.58   10.22 3.96
Maximum of Months 0.531378E+11 39470.87   33.90 19.17 0.652391E+09 381.81   32.52 19.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194756E+11 10248.25 01-JAN-11:35 13.87 8.54 0.938473E+10 6194.76 03-JAN-22:40 11.33 5.60
February 0.180102E+11 10218.14 19-FEB-11:35 19.03 7.40 0.855376E+10 6349.37 06-FEB-22:40 19.03 7.40
March 0.198724E+11 9813.30 05-MAR-11:35 16.83 7.89 0.950505E+10 6307.12 16-MAR-21:40 16.47 6.01
April 0.205453E+11 9917.53 19-APR-18:10 29.90 13.60 0.948449E+10 6462.42 03-APR-22:10 29.90 13.60
May 0.220796E+11 10251.17 31-MAY-18:10 30.92 15.25 0.100095E+11 6460.68 19-MAY-23:30 30.92 15.25
June 0.226263E+11 10728.24 15-JUN-18:10 35.92 14.47 0.996930E+10 6461.12 30-JUN-22:10 28.43 17.10
July 0.234717E+11 10795.33 26-JUL-18:10 33.77 19.75 0.102698E+11 6462.43 21-JUL-22:10 33.77 19.75
August 0.235733E+11 10954.73 07-AUG-21:10 31.25 17.07 0.103724E+11 6462.54 11-AUG-22:10 22.80 17.38
September 0.230757E+11 11014.98 17-SEP-10:35 29.47 15.71 0.100551E+11 6462.71 28-SEP-22:10 24.40 12.24
October 0.227690E+11 11118.51 22-OCT-10:35 22.23 13.01 0.101770E+11 6462.62 05-OCT-22:10 22.23 13.01
November 0.202464E+11 11033.79 11-NOV-10:53 16.10 7.51 0.943022E+10 6462.31 09-NOV-23:10 16.10 7.51
December 0.191195E+11 9971.09 10-DEC-11:35 15.93 7.48 0.926392E+10 6128.91 15-DEC-22:40 14.07 4.59
                     
Annual Sum or Average 0.254865E+12         0.116475E+12        
Minimum of Months 0.180102E+11 9813.30   13.87 7.40 0.855376E+10 6128.91   11.33 4.59
Maximum of Months 0.235733E+11 11118.51   35.92 19.75 0.103724E+11 6462.71   33.77 19.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.597078E+11 28242.15 12-JAN-22:10 10.03 5.38 0.298297E+11 19184.38 03-JAN-22:19 10.03 5.38
February 0.548512E+11 29323.26 22-FEB-22:04 14.40 4.90 0.271603E+11 19185.65 22-FEB-22:19 14.40 4.92
March 0.613991E+11 29960.47 16-MAR-21:10 17.02 5.96 0.303393E+11 19185.86 16-MAR-22:10 15.27 5.99
April 0.641059E+11 33872.72 21-APR-21:10 24.90 9.61 0.302044E+11 19189.22 17-APR-01:10 24.90 9.61
May 0.707304E+11 36562.80 31-MAY-21:10 28.13 13.59 0.317180E+11 19185.98 24-MAY-22:10 28.13 13.59
June 0.735602E+11 39172.77 15-JUN-21:10 32.57 13.55 0.310218E+11 19185.96 23-JUN-22:10 23.40 15.27
July 0.764164E+11 39053.68 26-JUL-21:10 28.62 18.19 0.319825E+11 19185.91 18-JUL-22:10 28.62 18.19
August 0.762099E+11 39985.68 07-AUG-21:10 31.25 17.07 0.321447E+11 19185.93 11-AUG-22:10 22.80 17.38
September 0.726671E+11 38400.01 21-SEP-21:10 26.10 17.46 0.310584E+11 19186.20 28-SEP-22:10 24.40 12.24
October 0.701172E+11 37738.03 05-OCT-21:10 23.22 16.17 0.317592E+11 19186.04 05-OCT-22:10 22.98 16.25
November 0.617173E+11 34013.25 09-NOV-22:10 18.53 10.92 0.298406E+11 19185.68 08-NOV-23:10 18.53 10.92
December 0.589151E+11 26814.82 15-DEC-21:00 14.40 4.76 0.295951E+11 19182.67 15-DEC-22:49 13.98 4.58
                     
Annual Sum or Average 0.800397E+12         0.366654E+12        
Minimum of Months 0.548512E+11 26814.82   10.03 4.76 0.271603E+11 19182.67   10.03 4.58
Maximum of Months 0.764164E+11 39985.68   32.57 18.19 0.321447E+11 19189.22   28.62 18.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.263627E+09 1812.10 12-JAN-16:12 18.53 10.06 97058731.16 56.69 04-JAN-02:20 18.53 10.06
February 0.384804E+09 1882.05 20-FEB-16:12 22.93 8.52 88213476.54 56.69 07-FEB-23:10 22.93 8.52
March 0.676675E+09 1882.04 16-MAR-15:12 22.60 8.60 98367497.26 56.69 16-MAR-23:19 10.53 4.80
April 0.134637E+10 1897.05 15-APR-15:12 27.20 11.79 96064235.80 56.69 17-APR-01:00 17.80 13.38
May 0.191467E+10 1906.02 17-MAY-15:12 29.40 13.34 99950797.25 57.03 16-MAY-21:10 29.40 13.34
June 0.230100E+10 1922.69 15-JUN-18:03 35.92 14.47 97230538.22 60.65 16-JUN-21:10 32.52 14.90
July 0.229563E+10 1905.88 31-JUL-18:02 33.22 19.45 99953979.46 56.70 26-JUL-02:39 33.22 19.45
August 0.217884E+10 1895.35 28-AUG-18:02 29.03 17.18 0.100035E+09 56.70 09-AUG-23:49 29.03 17.18
September 0.201654E+10 1897.39 01-SEP-18:02 31.13 18.07 96683111.61 56.70 19-SEP-23:30 22.75 14.80
October 0.145178E+10 1891.16 04-OCT-15:12 30.20 19.14 99393728.31 56.69 05-OCT-22:40 23.53 16.30
November 0.644487E+09 1862.96 07-NOV-16:12 21.33 10.14 94989850.71 56.69 09-NOV-22:19 18.17 10.78
December 0.174762E+09 1793.15 16-DEC-16:12 14.43 3.97 96740246.67 56.69 07-DEC-22:19 14.43 3.97
                     
Annual Sum or Average 0.156492E+11         0.116468E+10        
Minimum of Months 0.174762E+09 1793.15   14.43 3.97 88213476.54 56.69   10.53 3.97
Maximum of Months 0.230100E+10 1922.69   35.92 19.45 0.100035E+09 60.65   33.22 19.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 65532717.35 1729.56 30-JAN-16:12 15.60 6.03 95393155.26 56.69 03-JAN-22:10 15.60 6.03
February 0.127424E+09 1755.12 24-FEB-16:12 12.60 3.30 87740855.77 64.35 22-FEB-22:10 12.60 3.30
March 0.335962E+09 1832.82 21-MAR-15:12 24.60 9.46 0.100271E+09 69.50 16-MAR-21:40 24.60 9.46
April 0.106364E+10 2035.45 06-APR-18:11 14.63 6.39 99458787.38 74.51 28-APR-21:40 22.07 12.89
May 0.175924E+10 1981.51 20-MAY-08:51 26.70 12.19 0.102885E+09 78.33 23-MAY-21:10 22.02 16.25
June 0.222524E+10 2062.79 19-JUN-18:51 27.20 19.20 99481683.40 78.18 23-JUN-21:10 23.30 15.34
July 0.219459E+10 1892.84 09-JUL-18:02 32.62 18.79 0.102307E+09 74.84 18-JUL-21:00 19.40 19.40
August 0.196749E+10 1968.31 26-AUG-08:11 27.07 15.12 0.102711E+09 79.00 11-AUG-21:10 27.07 15.12
September 0.159862E+10 1887.73 29-SEP-21:51 19.40 9.20 0.100437E+09 77.63 13-SEP-21:10 19.40 9.20
October 0.895831E+09 1863.86 08-OCT-15:12 26.50 16.99 0.104085E+09 79.33 05-OCT-21:10 26.50 16.99
November 0.235958E+09 1764.26 12-NOV-16:12 14.80 7.06 94920685.59 68.57 09-NOV-22:40 14.80 7.06
December 34301744.28 1741.11 16-DEC-16:12 14.43 3.97 94798449.52 56.69 13-DEC-00:20 14.43 3.97
                     
Annual Sum or Average 0.125038E+11         0.118449E+10        
Minimum of Months 34301744.28 1729.56   12.60 3.30 87740855.77 56.69   12.60 3.30
Maximum of Months 0.222524E+10 2062.79   32.62 19.20 0.104085E+09 79.33   27.07 19.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268169E+09 432.82 12-JAN-14:25 18.60 9.87 0.00 0.00 01-JAN-00:10 18.60 9.87
February 0.266932E+09 409.61 07-FEB-13:40 20.20 9.50 0.00 0.00 01-FEB-00:10 20.20 9.50
March 0.254324E+09 326.08 07-MAR-13:10 20.78 8.64 0.00 0.00 01-MAR-00:10 20.78 8.64
April 0.331534E+09 296.57 03-APR-13:30 26.15 11.51 0.00 0.00 01-APR-00:10 26.15 11.51
May 0.394345E+09 288.34 31-MAY-20:20 29.03 14.28 0.00 0.00 01-MAY-00:10 29.03 14.28
June 0.476448E+09 324.99 15-JUN-20:20 33.70 13.91 0.00 0.00 01-JUN-00:10 33.70 13.91
July 0.499172E+09 320.93 02-JUL-20:40 33.17 16.98 0.00 0.00 01-JUL-00:10 33.17 16.98
August 0.520225E+09 336.32 07-AUG-20:20 31.70 17.19 0.00 0.00 01-AUG-00:10 31.70 17.19
September 0.571748E+09 422.80 19-SEP-13:30 33.35 16.80 0.00 0.00 01-SEP-00:10 33.35 16.80
October 0.526073E+09 484.30 22-OCT-13:15 25.97 14.61 0.00 0.00 01-OCT-00:10 25.97 14.61
November 0.387466E+09 468.43 09-NOV-13:15 22.97 12.22 0.00 0.00 01-NOV-00:10 22.97 12.22
December 0.235558E+09 380.05 07-DEC-14:00 15.60 6.73 0.00 0.00 01-DEC-00:10 15.60 6.73
                     
Annual Sum or Average 0.473199E+10         0.00        
Minimum of Months 0.235558E+09 288.34   15.60 6.73 0.00 0.00   15.60 6.73
Maximum of Months 0.571748E+09 484.30   33.70 17.19 0.00 0.00   33.70 17.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.137410E+09 634.22 13-JAN-19:02 13.12 6.39 95967880.64 56.69 03-JAN-22:10 13.12 6.39
February 0.176340E+09 667.64 21-FEB-21:32 14.60 4.38 87514573.01 67.77 22-FEB-22:10 14.40 4.90
March 0.280622E+09 698.85 15-MAR-21:52 19.40 7.29 98596509.05 70.19 09-MAR-22:10 19.40 7.29
April 0.483794E+09 729.89 20-APR-18:02 26.52 11.59 97523595.42 72.21 25-APR-21:49 18.22 11.64
May 0.688125E+09 756.23 20-MAY-08:51 26.70 12.19 0.101463E+09 73.98 23-MAY-21:10 22.02 16.25
June 0.828904E+09 771.39 14-JUN-08:11 27.93 12.20 98330930.74 74.17 23-JUN-21:10 23.30 15.34
July 0.841759E+09 739.19 06-JUL-08:61 26.38 18.59 0.101351E+09 71.06 18-JUL-21:00 19.40 19.40
August 0.753560E+09 731.88 29-AUG-21:51 22.20 14.62 0.101594E+09 76.00 14-AUG-21:10 22.20 14.62
September 0.607085E+09 728.49 20-SEP-18:02 31.05 16.15 98800331.29 72.95 13-SEP-21:10 31.05 16.15
October 0.442789E+09 719.51 19-OCT-21:52 19.40 9.71 0.101584E+09 73.78 05-OCT-21:10 19.40 9.71
November 0.213348E+09 660.63 08-NOV-22:52 14.40 8.09 93983053.66 68.23 09-NOV-22:49 17.07 10.34
December 0.106138E+09 641.10 16-DEC-09:02 8.48 2.42 95668154.62 56.69 08-DEC-22:10 8.48 2.42
                     
Annual Sum or Average 0.555987E+10         0.117238E+10        
Minimum of Months 0.106138E+09 634.22   8.48 2.42 87514573.01 56.69   8.48 2.42
Maximum of Months 0.841759E+09 771.39   31.05 18.59 0.101594E+09 76.00   31.05 19.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242549E+09 1617.55 03-JAN-16:12 20.20 7.65 97270017.10 56.69 03-JAN-22:10 12.43 6.06
February 0.425906E+09 1664.47 20-FEB-16:12 22.93 8.52 88671969.43 56.69 21-FEB-22:19 12.93 3.71
March 0.684998E+09 1666.87 16-MAR-15:12 22.60 8.60 98771409.41 56.69 22-MAR-21:10 11.52 4.66
April 0.140594E+10 1692.75 21-APR-15:12 31.83 15.27 96324626.56 56.69 17-APR-01:39 31.83 15.27
May 0.195780E+10 1722.32 20-MAY-08:62 24.37 10.75 99866905.33 56.71 15-MAY-21:10 24.37 10.75
June 0.236683E+10 1734.56 18-JUN-08:62 26.47 16.53 97012673.78 59.67 16-JUN-21:10 26.47 16.53
July 0.235380E+10 1727.69 03-JUL-08:62 29.18 17.25 99844323.18 56.69 11-JUL-00:30 26.40 16.87
August 0.223085E+10 1717.57 20-AUG-08:62 23.35 16.32 99888029.30 56.69 09-AUG-23:00 23.35 16.32
September 0.203251E+10 1706.29 16-SEP-15:12 32.20 18.22 96570882.94 56.69 19-SEP-23:30 22.75 14.80
October 0.137212E+10 1687.33 05-OCT-08:62 23.17 17.04 99298221.15 56.69 05-OCT-22:40 23.53 16.30
November 0.614815E+09 1655.87 08-NOV-16:12 22.93 10.99 95199466.44 56.69 01-NOV-01:39 22.93 10.99
December 0.185771E+09 1614.58 16-DEC-09:02 8.48 2.42 96940722.04 56.69 13-DEC-00:20 8.48 2.42
                     
Annual Sum or Average 0.158739E+11         0.116566E+10        
Minimum of Months 0.185771E+09 1614.58   8.48 2.42 88671969.43 56.69   8.48 2.42
Maximum of Months 0.236683E+10 1734.56   32.20 18.22 99888029.30 59.67   31.83 16.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 58086145.46 1525.41 31-JAN-09:02 10.78 4.13 95182086.46 56.69 01-JAN-05:30 10.78 4.13
February 0.176133E+09 1609.05 20-FEB-09:02 11.23 4.20 87779664.10 65.90 22-FEB-22:10 14.40 4.90
March 0.382425E+09 1629.92 21-MAR-15:12 24.60 9.46 99822595.23 67.69 15-MAR-21:30 24.60 9.46
April 0.111370E+10 1938.09 27-APR-08:51 20.60 11.74 99510026.76 73.02 28-APR-21:40 22.07 12.89
May 0.174754E+10 1994.07 20-MAY-08:51 26.70 12.19 0.103611E+09 74.88 17-MAY-21:00 26.70 12.19
June 0.224189E+10 2007.31 14-JUN-08:11 27.93 12.20 0.100203E+09 77.27 23-JUN-21:10 23.30 15.34
July 0.221116E+10 1931.97 04-JUL-08:62 25.18 18.51 0.103008E+09 72.84 20-JUL-21:00 21.10 21.10
August 0.197469E+10 1986.97 28-AUG-08:51 25.00 16.33 0.103316E+09 79.20 11-AUG-21:10 25.00 16.33
September 0.156408E+10 1960.10 19-SEP-08:51 26.10 16.81 0.101019E+09 76.18 06-SEP-21:10 26.10 16.81
October 0.845601E+09 1868.38 05-OCT-08:51 25.00 17.90 0.102939E+09 77.33 05-OCT-21:10 23.22 16.17
November 0.240786E+09 1720.61 09-NOV-09:51 18.30 8.77 94528102.79 67.72 09-NOV-22:40 17.43 10.49
December 42649432.08 1544.37 16-DEC-09:02 8.48 2.42 94740558.99 56.69 13-DEC-00:20 8.48 2.42
                     
Annual Sum or Average 0.125987E+11         0.118566E+10        
Minimum of Months 42649432.08 1525.41   8.48 2.42 87779664.10 56.69   8.48 2.42
Maximum of Months 0.224189E+10 2007.31   27.93 18.51 0.103611E+09 79.20   26.70 21.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.293434E+10 1482.75 01-JAN-11:35 13.87 8.54 0.125344E+10 795.95 03-JAN-22:49 10.97 5.44
February 0.284924E+10 1552.04 20-FEB-11:35 20.37 8.19 0.116336E+10 818.48 22-FEB-23:10 14.03 4.88
March 0.332544E+10 1604.17 16-MAR-18:10 19.82 7.14 0.133177E+10 839.50 16-MAR-21:49 16.28 6.02
April 0.365841E+10 1841.12 30-APR-10:35 24.07 13.08 0.138301E+10 889.49 21-APR-22:10 24.07 13.08
May 0.414409E+10 1944.53 20-MAY-18:00 31.70 15.22 0.151363E+10 935.79 19-MAY-22:10 31.70 15.22
June 0.435250E+10 2208.91 16-JUN-21:10 32.52 14.90 0.153695E+10 951.85 16-JUN-23:19 29.80 15.60
July 0.443084E+10 2036.57 26-JUL-18:10 33.77 19.75 0.156892E+10 951.84 03-JUL-21:40 33.77 19.75
August 0.437844E+10 2051.41 07-AUG-21:10 31.25 17.07 0.156718E+10 951.84 07-AUG-22:30 27.55 18.81
September 0.416817E+10 1991.67 23-SEP-10:35 27.23 18.46 0.149985E+10 951.84 20-SEP-21:49 27.23 18.46
October 0.391102E+10 1916.84 05-OCT-10:35 27.60 18.63 0.146493E+10 935.44 05-OCT-22:10 22.98 16.25
November 0.327096E+10 1677.99 10-NOV-11:35 20.93 12.02 0.130565E+10 868.89 01-NOV-00:10 20.93 12.02
December 0.275397E+10 1411.74 10-DEC-11:35 15.93 7.48 0.122943E+10 754.95 15-DEC-23:10 13.80 4.57
                     
Annual Sum or Average 0.441774E+11         0.168181E+11        
Minimum of Months 0.275397E+10 1411.74   13.87 7.14 0.116336E+10 754.95   10.97 4.57
Maximum of Months 0.443084E+10 2208.91   33.77 19.75 0.156892E+10 951.85   33.77 19.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191741E+09 1923.09 12-JAN-16:12 18.53 10.06 96446609.50 56.69 13-JAN-22:30 10.30 4.47
February 0.304889E+09 1997.86 20-FEB-16:12 22.93 8.52 87781865.01 56.70 13-FEB-00:30 22.93 8.52
March 0.575143E+09 1997.19 14-MAR-15:12 24.07 9.99 98030168.68 56.70 03-MAR-23:19 24.07 9.99
April 0.130968E+10 2024.34 15-APR-15:12 27.20 11.79 95977148.53 56.69 19-APR-21:10 28.12 12.29
May 0.193321E+10 2031.82 17-MAY-15:12 29.40 13.34 0.100024E+09 56.72 16-MAY-21:10 29.40 13.34
June 0.239743E+10 2053.20 15-JUN-18:03 35.92 14.47 97436855.69 60.76 16-JUN-21:10 32.52 14.90
July 0.240025E+10 2014.82 31-JUL-18:02 33.22 19.45 0.100100E+09 56.70 26-JUL-01:30 33.22 19.45
August 0.224351E+10 2011.40 28-AUG-18:02 29.03 17.18 0.100112E+09 56.70 07-AUG-01:19 29.03 17.18
September 0.201200E+10 2035.97 06-SEP-15:12 28.17 17.94 96699546.03 56.70 12-SEP-21:49 25.78 17.09
October 0.133615E+10 2014.48 03-OCT-15:12 30.93 18.47 99201380.89 56.70 05-OCT-21:40 22.97 16.21
November 0.509940E+09 1974.92 07-NOV-16:12 21.33 10.14 94517576.62 56.69 20-NOV-23:19 8.13 1.86
December 0.122544E+09 1900.13 16-DEC-16:12 14.43 3.97 96105475.52 56.69 13-DEC-00:20 14.43 3.97
                     
Annual Sum or Average 0.153365E+11         0.116243E+10        
Minimum of Months 0.122544E+09 1900.13   14.43 3.97 87781865.01 56.69   8.13 1.86
Maximum of Months 0.240025E+10 2053.20   35.92 19.45 0.100112E+09 60.76   33.22 19.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 42190799.38 1785.46 30-JAN-16:12 15.60 6.03 94545995.92 56.69 01-JAN-05:19 15.60 6.03
February 82553489.46 1815.10 24-FEB-16:12 12.60 3.30 87119968.19 62.11 22-FEB-22:10 12.60 3.30
March 0.249681E+09 1942.92 14-MAR-15:12 24.07 9.99 99916609.03 69.07 16-MAR-21:40 16.47 6.01
April 0.104025E+10 2159.72 06-APR-18:11 14.63 6.39 99377615.31 74.72 28-APR-21:40 22.07 12.89
May 0.180544E+10 2098.21 20-MAY-08:51 26.70 12.19 0.102752E+09 78.08 23-MAY-21:10 22.02 16.25
June 0.234881E+10 2193.89 19-JUN-18:51 27.20 19.20 99493119.96 77.70 23-JUN-21:10 23.30 15.34
July 0.232462E+10 2009.09 23-JUL-15:13 31.30 21.46 0.102282E+09 74.31 18-JUL-21:00 31.30 21.46
August 0.205636E+10 2083.42 26-AUG-08:11 27.07 15.12 0.102559E+09 78.82 11-AUG-21:10 27.07 15.12
September 0.161899E+10 1996.53 01-SEP-18:02 31.13 18.07 0.100089E+09 77.16 13-SEP-21:10 21.70 17.29
October 0.788805E+09 1978.35 04-OCT-15:12 30.20 19.14 0.103790E+09 79.09 05-OCT-21:10 23.22 16.17
November 0.142634E+09 1859.18 12-NOV-16:12 14.80 7.06 94195196.85 67.51 09-NOV-22:40 14.80 7.06
December 23493712.21 1810.90 16-DEC-16:12 14.43 3.97 93976238.99 56.69 21-DEC-04:19 2.43 -1.5
                     
Annual Sum or Average 0.125238E+11         0.118010E+10        
Minimum of Months 23493712.21 1785.46   12.60 3.30 87119968.19 56.69   2.43 -1.5
Maximum of Months 0.234881E+10 2193.89   31.30 21.46 0.103790E+09 79.09   31.30 21.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.527068E+09 1045.43 03-JAN-16:12 20.20 7.65 98432907.76 56.69 02-JAN-22:10 20.20 7.65
February 0.531482E+09 1074.08 20-FEB-16:12 22.93 8.52 89133158.17 56.69 06-FEB-22:00 22.93 8.52
March 0.553933E+09 1075.28 14-MAR-15:12 24.07 9.99 98737446.37 56.69 16-MAR-21:40 16.47 6.01
April 0.795323E+09 1068.16 15-APR-15:12 27.20 11.79 95920966.24 56.69 17-APR-00:49 18.12 11.72
May 0.995537E+09 1061.01 17-MAY-15:12 29.40 13.34 99521284.50 56.69 22-MAY-23:49 22.30 15.31
June 0.121544E+10 1061.17 01-JUN-15:12 36.50 14.52 96882215.15 60.90 15-JUN-21:10 32.57 13.55
July 0.126982E+10 1054.12 21-JUL-15:12 30.37 21.60 99670441.22 56.69 03-JUL-02:00 30.37 21.60
August 0.127275E+10 1076.73 21-AUG-15:12 32.40 18.02 99774931.19 56.69 09-AUG-22:00 32.40 18.02
September 0.128721E+10 1079.58 05-SEP-15:12 31.10 19.29 96602516.62 56.69 19-SEP-23:40 22.20 14.61
October 0.111258E+10 1079.21 31-OCT-15:12 21.50 7.69 99638552.68 56.69 18-OCT-22:40 21.50 7.69
November 0.750587E+09 1069.79 07-NOV-16:12 21.33 10.14 95681672.07 56.69 13-NOV-22:10 14.40 7.48
December 0.475486E+09 1035.79 16-DEC-16:12 14.43 3.97 98385883.98 56.69 05-DEC-22:19 14.43 3.97
                     
Annual Sum or Average 0.107872E+11         0.116838E+10        
Minimum of Months 0.475486E+09 1035.79   14.43 3.97 89133158.17 56.69   14.40 3.97
Maximum of Months 0.128721E+10 1079.58   36.50 21.60 99774931.19 60.90   32.57 21.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355583E+11 16537.66 03-JAN-24:00 12.20 6.21 0.172042E+11 11343.87 31-JAN-23:10 8.12 2.56
February 0.331444E+11 18251.84 22-FEB-22:06 14.40 4.90 0.157818E+11 11348.18 22-FEB-22:19 14.40 4.92
March 0.380891E+11 18602.81 15-MAR-21:54 19.40 7.29 0.178636E+11 11348.48 16-MAR-22:10 15.27 5.99
April 0.398882E+11 20433.85 19-APR-22:00 27.20 11.76 0.177845E+11 11348.71 28-APR-22:10 21.52 12.87
May 0.435450E+11 21422.15 31-MAY-22:00 27.30 13.26 0.186781E+11 11348.82 23-MAY-22:10 27.30 13.26
June 0.443138E+11 22061.35 16-JUN-22:00 31.10 15.68 0.182586E+11 11348.84 23-JUN-22:10 23.40 15.27
July 0.455523E+11 21808.96 25-JUL-22:00 30.00 17.19 0.187723E+11 11348.66 18-JUL-22:10 30.00 17.19
August 0.447737E+11 21938.10 07-AUG-21:40 29.90 17.57 0.188023E+11 11348.68 11-AUG-22:10 22.80 17.38
September 0.419095E+11 20896.57 22-SEP-22:00 25.00 17.90 0.179996E+11 11349.00 28-SEP-22:10 24.40 12.24
October 0.406792E+11 20299.86 05-OCT-21:52 22.80 16.23 0.182442E+11 11348.84 05-OCT-22:10 22.98 16.25
November 0.360256E+11 18504.90 09-NOV-22:54 16.70 10.18 0.170096E+11 11348.18 08-NOV-23:10 16.70 10.18
December 0.348904E+11 16385.08 15-DEC-24:00 13.30 4.57 0.170154E+11 11343.45 15-DEC-23:40 13.30 4.57
                     
Annual Sum or Average 0.478369E+12         0.213414E+12        
Minimum of Months 0.331444E+11 16385.08   12.20 4.57 0.157818E+11 11343.45   8.12 2.56
Maximum of Months 0.455523E+11 22061.35   31.10 17.90 0.188023E+11 11349.00   30.00 17.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.377207E+11 18260.79 03-JAN-22:10 12.43 6.06 0.178265E+11 11344.37 31-JAN-23:10 8.12 2.56
February 0.349954E+11 19216.77 07-FEB-23:00 15.60 8.35 0.162955E+11 11348.12 22-FEB-22:19 14.40 4.92
March 0.400561E+11 20087.96 15-MAR-21:54 19.40 7.29 0.183733E+11 11348.49 16-MAR-22:10 15.27 5.99
April 0.417280E+11 21827.26 19-APR-22:00 27.20 11.76 0.181012E+11 11349.89 17-APR-01:10 27.20 11.76
May 0.455599E+11 22757.76 31-MAY-21:50 27.47 13.33 0.189062E+11 11348.82 23-MAY-22:10 27.47 13.33
June 0.463630E+11 23389.88 15-JUN-21:10 32.57 13.55 0.184440E+11 11358.59 07-JUN-21:30 32.57 13.55
July 0.476397E+11 23189.17 26-JUL-21:30 28.05 18.23 0.189747E+11 11357.59 26-JUL-21:30 28.05 18.23
August 0.468185E+11 23329.09 07-AUG-21:30 30.35 17.43 0.190048E+11 11358.17 07-AUG-21:30 30.35 17.43
September 0.437678E+11 22185.73 22-SEP-22:00 25.00 17.90 0.182340E+11 11349.01 28-SEP-22:10 24.40 12.24
October 0.424296E+11 21596.18 05-OCT-21:52 22.80 16.23 0.185912E+11 11348.84 05-OCT-22:10 22.98 16.25
November 0.378266E+11 19873.16 09-NOV-22:54 16.70 10.18 0.174979E+11 11348.19 08-NOV-23:10 16.70 10.18
December 0.371170E+11 18232.33 15-DEC-22:10 14.32 4.61 0.176871E+11 11344.85 13-DEC-00:10 14.32 4.61
                     
Annual Sum or Average 0.502022E+12         0.217936E+12        
Minimum of Months 0.349954E+11 18232.33   12.43 4.61 0.162955E+11 11344.37   8.12 2.56
Maximum of Months 0.476397E+11 23389.88   32.57 18.23 0.190048E+11 11358.59   32.57 18.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.485273E+11 26323.96 01-JAN-11:50 14.13 8.64 0.188679E+11 11319.48 07-JAN-18:10 12.43 5.33
February 0.447796E+11 27235.03 20-FEB-11:50 20.73 8.30 0.170435E+11 11319.43 18-FEB-18:10 20.73 8.30
March 0.506607E+11 27418.74 19-MAR-10:50 19.03 7.15 0.188759E+11 11319.53 18-MAR-17:10 19.03 7.15
April 0.515973E+11 28797.72 30-APR-10:50 24.53 12.98 0.182622E+11 11319.65 15-APR-17:10 24.53 12.98
May 0.551112E+11 28947.46 21-MAY-10:40 29.47 14.38 0.188716E+11 11319.63 06-MAY-17:10 29.47 14.38
June 0.549479E+11 29460.55 18-JUN-10:40 32.43 16.35 0.182661E+11 11319.59 03-JUN-17:10 32.43 16.35
July 0.566831E+11 29605.88 02-JUL-10:40 32.23 20.13 0.188683E+11 11319.62 22-JUL-17:10 30.60 19.89
August 0.561597E+11 29494.63 06-AUG-10:40 31.67 18.03 0.188756E+11 11319.58 12-AUG-17:10 33.80 19.05
September 0.535752E+11 29116.26 17-SEP-10:40 29.47 15.71 0.182617E+11 11319.62 02-SEP-17:10 29.47 15.71
October 0.528613E+11 28618.82 01-OCT-10:50 27.23 14.39 0.188688E+11 11319.59 28-OCT-17:10 22.52 13.68
November 0.482822E+11 27024.06 10-NOV-11:50 21.02 12.06 0.182585E+11 11319.65 04-NOV-17:19 21.02 12.06
December 0.480203E+11 26285.41 10-DEC-11:50 16.32 7.64 0.188679E+11 11319.49 30-DEC-18:10 8.43 2.73
                     
Annual Sum or Average 0.621206E+12         0.222188E+12        
Minimum of Months 0.447796E+11 26285.41   14.13 7.15 0.170435E+11 11319.43   8.43 2.73
Maximum of Months 0.566831E+11 29605.88   32.43 20.13 0.188759E+11 11319.65   33.80 19.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.346306E+10 1780.13 01-JAN-11:50 14.13 8.64 0.140019E+10 909.73 12-JAN-22:30 8.90 4.67
February 0.339362E+10 1941.62 20-FEB-11:50 20.73 8.30 0.132967E+10 969.86 22-FEB-23:10 14.03 4.88
March 0.407700E+10 2411.45 16-MAR-15:13 22.60 8.60 0.155458E+10 1007.39 16-MAR-22:10 15.27 5.99
April 0.571159E+10 4545.97 28-APR-15:10 28.80 13.97 0.163097E+10 1007.51 17-APR-01:10 28.80 13.97
May 0.798662E+10 5216.34 30-MAY-15:10 34.32 17.72 0.171530E+10 1007.41 30-MAY-00:20 34.32 17.72
June 0.100444E+11 5726.41 17-JUN-17:20 36.10 16.68 0.166580E+10 1007.43 30-JUN-22:19 28.37 17.20
July 0.103021E+11 6030.83 03-JUL-15:10 37.38 18.88 0.171455E+10 1007.42 05-JUL-21:00 27.80 17.53
August 0.965527E+10 5928.26 07-AUG-15:10 35.37 18.63 0.172169E+10 1007.43 22-AUG-00:10 24.22 16.48
September 0.836170E+10 5648.95 02-SEP-13:40 31.83 18.70 0.165887E+10 1007.42 19-SEP-04:10 17.62 13.58
October 0.609152E+10 5233.67 03-OCT-13:40 32.07 19.44 0.168513E+10 1007.42 10-OCT-21:19 13.87 9.12
November 0.393931E+10 2980.40 10-NOV-12:20 19.80 11.75 0.148193E+10 1007.39 09-NOV-23:10 19.80 11.75
December 0.311305E+10 1711.96 16-DEC-11:50 13.03 3.53 0.135395E+10 877.87 15-DEC-23:10 13.03 3.53
                     
Annual Sum or Average 0.761392E+11         0.189126E+11        
Minimum of Months 0.311305E+10 1711.96   13.03 3.53 0.132967E+10 877.87   8.90 3.53
Maximum of Months 0.103021E+11 6030.83   37.38 19.44 0.172169E+10 1007.51   34.32 17.72



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 280099.97 91.87 27-JAN-07:30 -4.2
February 88341.19 37.60 03-FEB-07:10 -5.1
March 5732.96 13.74 02-MAR-07:05 -1.6
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 2034.07 3.39 28-NOV-05:00 -0.6
December 7667838.90 511.38 27-DEC-07:30 -4.2
         
Annual Sum or Average 8044047.08      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 7667838.90 511.38   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138066E+09 2064.33 14-JAN-16:11 7.97
February 75216134.04 1900.51 02-FEB-09:01 1.38
March 28293601.03 2073.28 02-MAR-09:01 0.47
April 724655.96 556.83 12-APR-08:03 11.15
May 201169.35 527.76 02-MAY-08:05 14.68
June 264.55 1.54 30-JUN-08:07 22.38
July 31618.90 145.62 19-JUL-08:07 20.78
August 16210.82 55.73 18-AUG-08:07 21.38
September 109054.11 328.24 27-SEP-08:06 19.27
October 426212.19 486.94 14-OCT-18:06 18.72
November 55844424.25 2077.94 27-NOV-09:01 3.98
December 0.219191E+09 2130.20 26-DEC-16:11 2.03
         
Annual Sum or Average 0.518121E+09      
Minimum of Months 264.55 1.54   0.47
Maximum of Months 0.219191E+09 2130.20   22.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.293545E+09 2118.64 27-JAN-09:01 -1.2
February 0.155829E+09 2113.14 02-FEB-09:01 1.38
March 49121420.32 2097.44 02-MAR-09:01 0.47
April 808108.14 533.41 12-APR-08:03 11.15
May 147119.23 513.93 02-MAY-08:05 14.68
June 10667.61 142.23 01-JUN-08:36 26.27
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 69507.62 477.09 29-SEP-06:25 15.80
October 715369.57 541.77 23-OCT-08:05 16.05
November 0.102902E+09 2096.57 28-NOV-16:11 11.33
December 0.431385E+09 2148.59 27-DEC-09:01 -0.7
         
Annual Sum or Average 0.103453E+10      
Minimum of Months 0.00 0.00   -1.2
Maximum of Months 0.431385E+09 2148.59   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5432697.87 626.19 27-JAN-16:12 9.60
February 3486261.39 586.95 02-FEB-16:12 10.60
March 697257.19 209.65 28-MAR-08:05 11.10
April 32033.56 116.52 12-APR-08:05 11.15
May 38.94 0.52 01-MAY-08:55 17.20
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 8541.95 34.63 31-OCT-08:07 15.37
November 1107602.67 319.97 28-NOV-16:11 11.33
December 15210977.75 634.30 26-DEC-16:11 2.03
         
Annual Sum or Average 25975411.31      
Minimum of Months 0.00 0.00   2.03
Maximum of Months 15210977.75 634.30   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.155304E+09 1996.64 14-JAN-16:11 7.97
February 72253134.31 606.50 27-FEB-09:02 9.60
March 29297054.11 1535.73 02-MAR-09:01 0.47
April 156991.45 258.88 11-APR-18:05 16.52
May 18882.50 136.74 03-MAY-08:06 19.18
June 6385.67 63.86 29-JUN-08:07 18.58
July 0.00 0.00 01-JUL-00:10 27.63
August 35403.50 112.31 16-AUG-18:07 18.98
September 7078.16 70.78 28-SEP-08:07 18.68
October 307801.57 481.25 15-OCT-18:05 18.72
November 63493220.69 2004.33 28-NOV-16:11 11.33
December 0.230753E+09 2062.28 26-DEC-16:11 2.03
         
Annual Sum or Average 0.551633E+09      
Minimum of Months 0.00 0.00   0.47
Maximum of Months 0.230753E+09 2062.28   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.309420E+09 2012.01 14-JAN-16:11 7.97
February 0.140022E+09 1968.46 02-FEB-16:12 10.60
March 54198090.99 1993.43 02-MAR-09:01 0.47
April 301765.92 200.62 01-APR-21:56 23.30
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 353.15 3.53 16-AUG-21:57 17.80
September 0.00 0.00 01-SEP-00:10 22.63
October 488905.44 496.40 13-OCT-15:15 15.37
November 0.116270E+09 2023.86 28-NOV-16:11 11.33
December 0.431259E+09 2076.11 26-DEC-16:11 2.03
         
Annual Sum or Average 0.105196E+10      
Minimum of Months 0.00 0.00   0.47
Maximum of Months 0.431259E+09 2076.11   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.358595E+09 2538.71 14-JAN-16:11 7.97
February 0.216733E+09 2525.91 02-FEB-09:01 1.38
March 0.112152E+09 2544.59 02-MAR-09:01 0.47
April 9833265.21 1136.32 11-APR-08:62 6.88
May 272402.92 475.90 10-MAY-08:05 20.78
June 6947.56 69.48 29-JUN-08:05 18.58
July 11551.39 68.50 18-JUL-08:07 24.08
August 47194.66 287.35 14-AUG-08:06 18.40
September 91632.24 296.63 28-SEP-08:05 18.68
October 1317471.62 514.06 11-OCT-08:03 12.15
November 0.177045E+09 2548.75 27-NOV-09:01 3.98
December 0.491802E+09 2584.16 26-DEC-16:11 2.03
         
Annual Sum or Average 0.136791E+10      
Minimum of Months 6947.56 68.50   0.47
Maximum of Months 0.491802E+09 2584.16   24.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.621084E+09 2571.80 06-JAN-09:01 2.07
February 0.366322E+09 2575.75 02-FEB-09:01 1.38
March 0.158584E+09 2569.23 02-MAR-09:01 0.47
April 10031228.17 1258.13 11-APR-08:62 6.88
May 164297.40 381.62 05-MAY-08:54 17.80
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 7965.26 106.20 30-AUG-08:55 23.30
September 75896.63 190.89 27-SEP-08:54 21.10
October 2310271.77 534.68 10-OCT-08:03 14.87
November 0.292947E+09 2565.42 28-NOV-16:11 11.33
December 0.816026E+09 2585.54 26-DEC-16:11 2.03
         
Annual Sum or Average 0.226755E+10      
Minimum of Months 0.00 0.00   0.47
Maximum of Months 0.816026E+09 2585.54   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 30136554.75 1287.22 15-JAN-16:11 10.00
February 18074098.82 401.59 26-FEB-16:15 18.13
March 12056670.43 890.41 02-MAR-09:01 0.47
April 521261.96 269.17 12-APR-08:03 11.15
May 153570.35 167.79 02-MAY-08:05 14.68
June 323.10 3.23 22-JUN-08:07 21.88
July 0.00 0.00 01-JUL-00:10 27.63
August 1080.99 10.81 24-AUG-08:07 21.60
September 11822.42 98.52 25-SEP-08:06 16.57
October 93513.41 275.96 07-OCT-18:05 17.62
November 19388986.37 1101.38 27-NOV-09:01 3.98
December 55917219.52 1318.13 26-DEC-16:11 2.03
         
Annual Sum or Average 0.136355E+09      
Minimum of Months 0.00 0.00   0.47
Maximum of Months 55917219.52 1318.13   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 642267.26 190.27 27-JAN-07:30 -4.2
February 781142.70 294.27 03-FEB-07:30 -4.2
March 0.00 0.00 01-MAR-00:05 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 17600262.58 1006.62 27-DEC-07:30 -4.2
         
Annual Sum or Average 19023672.54      
Minimum of Months 0.00 0.00   -4.2
Maximum of Months 17600262.58 1006.62   27.63



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.785035E+10 7561.54 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.708815E+10 7561.54 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.787455E+10 7561.54 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.758419E+10 7561.54 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.786396E+10 7561.54 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.761897E+10 7561.54 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.782918E+10 7561.54 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.787758E+10 7561.54 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.758721E+10 7561.54 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.784733E+10 7561.54 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.761292E+10 7561.54 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.782918E+10 7561.54 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.924636E+11     0.143105E+12    
Minimum of Months 0.708815E+10 7561.54   0.109726E+11 9632.53  
Maximum of Months 0.787758E+10 7561.54   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.355268E+09 342.20 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.320774E+09 342.20 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.356363E+09 342.20 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.343222E+09 342.20 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.355884E+09 342.20 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.344797E+09 342.20 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.354310E+09 342.20 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.356500E+09 342.20 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.343359E+09 342.20 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.355131E+09 342.20 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.344523E+09 342.20 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.354310E+09 342.20 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.418444E+10     0.101856E+11    
Minimum of Months 0.320774E+09 342.20   0.780982E+09 685.60  
Maximum of Months 0.356500E+09 342.20   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.411401E+09 396.26 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.371458E+09 396.26 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.412669E+09 396.26 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.397453E+09 396.26 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.412115E+09 396.26 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.399276E+09 396.26 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.410292E+09 396.26 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.412828E+09 396.26 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.397611E+09 396.26 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.411243E+09 396.26 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.398959E+09 396.26 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.410292E+09 396.26 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.484560E+10     0.117950E+11    
Minimum of Months 0.371458E+09 396.26   0.904380E+09 793.93  
Maximum of Months 0.412828E+09 396.26   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.736067E+09 708.98 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.664602E+09 708.98 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.738336E+09 708.98 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.711111E+09 708.98 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.737344E+09 708.98 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.714372E+09 708.98 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.734082E+09 708.98 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.738620E+09 708.98 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.711395E+09 708.98 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.735784E+09 708.98 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.713805E+09 708.98 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.734082E+09 708.98 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.866960E+10     0.124712E+11    
Minimum of Months 0.664602E+09 708.98   0.956227E+09 839.45  
Maximum of Months 0.738620E+09 708.98   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.168723E+09 162.52 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.152342E+09 162.52 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.169243E+09 162.52 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.163003E+09 162.52 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.169016E+09 162.52 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.163750E+09 162.52 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.168268E+09 162.52 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.169308E+09 162.52 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.163068E+09 162.52 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.168658E+09 162.52 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.163620E+09 162.52 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.168268E+09 162.52 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.198727E+10     0.359760E+10    
Minimum of Months 0.152342E+09 162.52   0.275845E+09 242.16  
Maximum of Months 0.169308E+09 162.52   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314027E+09 302.47 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.283537E+09 302.47 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.314994E+09 302.47 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.303380E+09 302.47 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.314571E+09 302.47 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.304771E+09 302.47 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.313180E+09 302.47 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.315115E+09 302.47 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.303501E+09 302.47 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.313906E+09 302.47 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.304529E+09 302.47 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.313180E+09 302.47 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.369869E+10     0.679355E+11    
Minimum of Months 0.283537E+09 302.47   0.520895E+10 4572.80  
Maximum of Months 0.315115E+09 302.47   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.627919E+09 810.33 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.545962E+09 810.33 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.576744E+09 810.33 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.521460E+09 810.33 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.522880E+09 810.33 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.488013E+09 810.33 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.503074E+09 810.33 03-JUL-19:19 0.121533E+10 965.27 03-JUL-19:10
August 0.539721E+09 810.33 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.540724E+09 810.33 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.606053E+09 810.33 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.587772E+09 810.33 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.623900E+09 810.33 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.668422E+10     0.143405E+11    
Minimum of Months 0.488013E+09 810.33   0.109956E+10 965.27  
Maximum of Months 0.627919E+09 810.33   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.676316E+10 6817.32 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.607753E+10 6817.32 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.671841E+10 6817.32 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.642370E+10 6817.32 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.663498E+10 6817.32 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.640892E+10 6817.32 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.659273E+10 6817.32 03-JUL-19:19 0.126273E+11 10029.21 03-JUL-19:10
August 0.667183E+10 6817.32 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.645683E+10 6817.32 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.673023E+10 6817.32 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.652617E+10 6817.32 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.673834E+10 6817.32 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.787428E+11     0.148998E+12    
Minimum of Months 0.607753E+10 6817.32   0.114244E+11 10029.21  
Maximum of Months 0.676316E+10 6817.32   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65789991.58 59.53 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 59414784.75 59.53 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 65267117.48 59.53 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 63743496.62 59.53 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 65528554.53 59.53 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 63237765.93 59.53 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 66042856.93 59.53 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 65267117.48 59.53 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 63760640.03 59.53 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 65781419.88 59.53 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 63490631.27 59.53 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 66051428.64 59.53 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.773376E+09     0.256575E+10    
Minimum of Months 59414784.75 59.53   0.196843E+09 232.19  
Maximum of Months 66051428.64 59.53   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.115875E+10 1116.11 02-JAN-20:10 0.00 0.00
February 0.104624E+10 1116.11 01-FEB-20:10 0.00 0.00
March 0.116232E+10 1116.11 01-MAR-20:10 0.00 0.00
April 0.111946E+10 1116.11 03-APR-19:10 0.00 0.00
May 0.116076E+10 1116.11 01-MAY-19:10 0.00 0.00
June 0.112460E+10 1116.11 01-JUN-19:10 0.00 0.00
July 0.115562E+10 1116.11 03-JUL-19:10 0.00 0.00
August 0.116277E+10 1116.11 01-AUG-19:10 0.00 0.00
September 0.111991E+10 1116.11 01-SEP-19:10 0.00 0.00
October 0.115830E+10 1116.11 02-OCT-19:10 0.00 0.00
November 0.112370E+10 1116.11 01-NOV-19:10 0.00 0.00
December 0.115562E+10 1116.11 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.136481E+11     0.00 0.00
Minimum of Months 0.104624E+10 1116.11   0.00 0.00
Maximum of Months 0.116277E+10 1116.11   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.131589E+10 1423.01 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.116365E+10 1423.01 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.125912E+10 1423.01 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.116644E+10 1423.01 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.118348E+10 1423.01 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.112659E+10 1423.01 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.115866E+10 1423.01 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.120709E+10 1423.01 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.119747E+10 1423.01 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.128379E+10 1423.01 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.125689E+10 1423.01 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.130644E+10 1423.01 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.146255E+11     0.175857E+12    
Minimum of Months 0.112659E+10 1423.01   0.134904E+11 6747.90  
Maximum of Months 0.131589E+10 1423.01   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.131589E+10 1423.01 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.116365E+10 1423.01 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.125912E+10 1423.01 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.116644E+10 1423.01 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.118348E+10 1423.01 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.112659E+10 1423.01 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.115866E+10 1423.01 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.120709E+10 1423.01 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.119747E+10 1423.01 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.128379E+10 1423.01 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.125689E+10 1423.01 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.130644E+10 1423.01 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.146255E+11     0.175857E+12    
Minimum of Months 0.112659E+10 1423.01   0.134904E+11 6747.90  
Maximum of Months 0.131589E+10 1423.01   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.775957E+09 747.41 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.700619E+09 747.41 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.778349E+09 747.41 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.749649E+09 747.41 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.777303E+09 747.41 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.753087E+09 747.41 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.773865E+09 747.41 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.778648E+09 747.41 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.749948E+09 747.41 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.775658E+09 747.41 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.752489E+09 747.41 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.773865E+09 747.41 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.913943E+10     0.424019E+12    
Minimum of Months 0.700619E+09 747.41   0.325275E+11 16179.04  
Maximum of Months 0.778648E+09 747.41   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.122636E+10 1181.23 02-JAN-20:10 0.00 0.00
February 0.110729E+10 1181.23 01-FEB-20:10 0.00 0.00
March 0.123014E+10 1181.23 01-MAR-20:10 0.00 0.00
April 0.118478E+10 1181.23 03-APR-19:10 0.00 0.00
May 0.122848E+10 1181.23 01-MAY-19:10 0.00 0.00
June 0.119021E+10 1181.23 01-JUN-19:10 0.00 0.00
July 0.122305E+10 1181.23 03-JUL-19:10 0.00 0.00
August 0.123061E+10 1181.23 01-AUG-19:10 0.00 0.00
September 0.118525E+10 1181.23 01-SEP-19:10 0.00 0.00
October 0.122588E+10 1181.23 02-OCT-19:10 0.00 0.00
November 0.118927E+10 1181.23 01-NOV-19:10 0.00 0.00
December 0.122305E+10 1181.23 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.144444E+11     0.00 0.00
Minimum of Months 0.110729E+10 1181.23   0.00 0.00
Maximum of Months 0.123061E+10 1181.23   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.785035E+10 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.708815E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.787455E+10 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.758419E+10 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.786396E+10 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.761897E+10 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.782918E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.787758E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.758721E+10 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.784733E+10 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.761292E+10 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.782918E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.924636E+11 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.708815E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.787758E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.355268E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.410023E+09
February 0.179968E+10 0.320774E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.318151E+09
March 0.199990E+10 0.356363E+09 0.866718E+09 0.00 0.00 0.00 0.00 154301.74 0.287712E+09
April 0.192973E+10 0.343222E+09 0.835931E+09 0.00 0.00 0.00 0.00 20606652.00 0.134287E+09
May 0.199475E+10 0.355884E+09 0.865939E+09 0.00 0.00 0.00 0.00 57740956.18 57747759.21
June 0.193394E+10 0.344797E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.117363E+09 18157551.39
July 0.199054E+10 0.354310E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.107582E+09 12573733.26
August 0.199896E+10 0.356500E+09 0.866978E+09 0.00 0.00 0.00 0.00 87215048.46 25464427.33
September 0.192879E+10 0.343359E+09 0.836191E+09 0.00 0.00 0.00 0.00 48616522.58 64947442.56
October 0.199148E+10 0.355131E+09 0.864640E+09 0.00 0.00 0.00 0.00 11501612.91 0.160937E+09
November 0.192552E+10 0.344523E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.325878E+09
December 0.199054E+10 0.354310E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.448447E+09
                   
Annual Sum or Average 0.234744E+11 0.418444E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.450780E+09 0.226433E+10
Minimum of Months 0.179968E+10 0.320774E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 12573733.26
Maximum of Months 0.199990E+10 0.356500E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.117363E+09 0.448447E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.411401E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.157626E+09
February 0.208403E+10 0.371458E+09 0.904380E+09 0.00 0.00 0.00 0.00 48480.90 0.121793E+09
March 0.231589E+10 0.412669E+09 0.100366E+10 0.00 0.00 0.00 0.00 564501.74 0.110542E+09
April 0.223463E+10 0.397453E+09 0.968011E+09 0.00 0.00 0.00 0.00 10931368.37 51943080.40
May 0.230993E+10 0.412115E+09 0.100276E+10 0.00 0.00 0.00 0.00 25943746.03 22484227.81
June 0.223950E+10 0.399276E+09 0.971170E+09 0.00 0.00 0.00 0.00 48412601.14 6963317.17
July 0.230505E+10 0.410292E+09 0.999601E+09 0.00 0.00 0.00 0.00 44584868.18 4750441.59
August 0.231480E+10 0.412828E+09 0.100396E+10 0.00 0.00 0.00 0.00 36458935.81 9646816.92
September 0.223354E+10 0.397611E+09 0.968312E+09 0.00 0.00 0.00 0.00 21424046.73 24998595.75
October 0.230614E+10 0.411243E+09 0.100126E+10 0.00 0.00 0.00 0.00 5845120.66 60924662.61
November 0.222975E+10 0.398959E+09 0.970719E+09 0.00 0.00 0.00 0.00 53761.96 0.124756E+09
December 0.230505E+10 0.410292E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.172876E+09
                   
Annual Sum or Average 0.271834E+11 0.484560E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.194267E+09 0.869304E+09
Minimum of Months 0.208403E+10 0.371458E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 4750441.59
Maximum of Months 0.231589E+10 0.412828E+09 0.100396E+10 0.00 0.00 0.00 0.00 48412601.14 0.172876E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.736067E+09 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.394580E+09
February 0.440737E+09 0.664602E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.309682E+09
March 0.489771E+09 0.738336E+09 0.106120E+10 0.00 0.00 0.00 0.00 244272.29 0.288446E+09
April 0.472586E+09 0.711111E+09 0.102351E+10 0.00 0.00 0.00 0.00 18596854.20 0.137836E+09
May 0.488511E+09 0.737344E+09 0.106025E+10 0.00 0.00 0.00 0.00 52225267.74 58412347.10
June 0.473617E+09 0.714372E+09 0.102685E+10 0.00 0.00 0.00 0.00 0.107018E+09 17542994.64
July 0.487480E+09 0.734082E+09 0.105691E+10 0.00 0.00 0.00 0.00 98033263.25 12121017.65
August 0.489542E+09 0.738620E+09 0.106152E+10 0.00 0.00 0.00 0.00 79520038.12 24973500.87
September 0.472357E+09 0.711395E+09 0.102382E+10 0.00 0.00 0.00 0.00 44348136.41 61653429.37
October 0.487709E+09 0.735784E+09 0.105866E+10 0.00 0.00 0.00 0.00 10483121.71 0.158174E+09
November 0.471555E+09 0.713805E+09 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.319084E+09
December 0.487480E+09 0.734082E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.429510E+09
                   
Annual Sum or Average 0.574883E+10 0.866960E+10 0.124712E+11 0.00 0.00 0.00 0.00 0.410469E+09 0.221201E+10
Minimum of Months 0.440737E+09 0.664602E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 12121017.65
Maximum of Months 0.489771E+09 0.738620E+09 0.106152E+10 0.00 0.00 0.00 0.00 0.107018E+09 0.429510E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.168723E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.197103E+09
February 0.339028E+09 0.152342E+09 0.275845E+09 0.00 0.00 0.00 0.00 434756.20 0.149930E+09
March 0.376747E+09 0.169243E+09 0.306128E+09 0.00 0.00 0.00 0.00 1737859.74 0.133469E+09
April 0.363528E+09 0.163003E+09 0.295253E+09 0.00 0.00 0.00 0.00 18878623.24 59393376.89
May 0.375778E+09 0.169016E+09 0.305852E+09 0.00 0.00 0.00 0.00 40588771.95 24140020.44
June 0.364321E+09 0.163750E+09 0.296217E+09 0.00 0.00 0.00 0.00 70417047.93 6790753.51
July 0.374985E+09 0.168268E+09 0.304889E+09 0.00 0.00 0.00 0.00 65480865.02 4109819.31
August 0.376571E+09 0.169308E+09 0.306219E+09 0.00 0.00 0.00 0.00 54430598.96 9367466.39
September 0.363352E+09 0.163068E+09 0.295345E+09 0.00 0.00 0.00 0.00 33652136.48 26986149.36
October 0.375161E+09 0.168658E+09 0.305393E+09 0.00 0.00 0.00 0.00 10566327.80 69980768.71
November 0.362735E+09 0.163620E+09 0.296079E+09 0.00 0.00 0.00 0.00 296369.44 0.151763E+09
December 0.374985E+09 0.168268E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.219314E+09
                   
Annual Sum or Average 0.442217E+10 0.198727E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.296483E+09 0.105235E+10
Minimum of Months 0.339028E+09 0.152342E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 4109819.31
Maximum of Months 0.376747E+09 0.169308E+09 0.306219E+09 0.00 0.00 0.00 0.00 70417047.93 0.219314E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.314027E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.572814E+09
February 0.139600E+10 0.283537E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.446286E+09
March 0.155131E+10 0.314994E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 175412.05 0.409315E+09
April 0.149688E+10 0.303380E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 25306599.18 0.189253E+09
May 0.154732E+10 0.314571E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 71303730.11 79757353.82
June 0.150015E+10 0.304771E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.146115E+09 23949205.55
July 0.154405E+10 0.313180E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.133852E+09 16547651.86
August 0.155059E+10 0.315115E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.108571E+09 34101707.34
September 0.149615E+10 0.303501E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 60546573.08 84189058.14
October 0.154478E+10 0.313906E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 14313878.17 0.215990E+09
November 0.149361E+10 0.304529E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.446354E+09
December 0.154405E+10 0.313180E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.626577E+09
                   
Annual Sum or Average 0.182090E+11 0.369869E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.560185E+09 0.314513E+10
Minimum of Months 0.139600E+10 0.283537E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 16547651.86
Maximum of Months 0.155131E+10 0.315115E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.146115E+09 0.626577E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.627919E+09 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.906310E+09
February 0.236489E+11 0.545962E+09 0.109956E+10 0.00 0.00 0.00 0.00 21750.22 0.697098E+09
March 0.262800E+11 0.576744E+09 0.122027E+10 0.00 0.00 0.00 0.00 2648538.14 0.618404E+09
April 0.253579E+11 0.521460E+09 0.117692E+10 0.00 0.00 0.00 0.00 71256190.67 0.273871E+09
May 0.262123E+11 0.522880E+09 0.121917E+10 0.00 0.00 0.00 0.00 0.175903E+09 0.110542E+09
June 0.254132E+11 0.488013E+09 0.118076E+10 0.00 0.00 0.00 0.00 0.310102E+09 31481791.78
July 0.261570E+11 0.503074E+09 0.121533E+10 0.00 0.00 0.00 0.00 0.290805E+09 20479446.98
August 0.262677E+11 0.539721E+09 0.122063E+10 0.00 0.00 0.00 0.00 0.234331E+09 44392461.40
September 0.253456E+11 0.540724E+09 0.117729E+10 0.00 0.00 0.00 0.00 0.132952E+09 0.127717E+09
October 0.261693E+11 0.606053E+09 0.121734E+10 0.00 0.00 0.00 0.00 32064330.73 0.329717E+09
November 0.253025E+11 0.587772E+09 0.118021E+10 0.00 0.00 0.00 0.00 55222.15 0.711277E+09
December 0.261570E+11 0.623900E+09 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.993930E+09
                   
Annual Sum or Average 0.308468E+12 0.668422E+10 0.143405E+11 0.00 0.00 0.00 0.00 0.125014E+10 0.486522E+10
Minimum of Months 0.236489E+11 0.488013E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 20479446.98
Maximum of Months 0.262800E+11 0.627919E+09 0.122063E+10 0.00 0.00 0.00 0.00 0.310102E+09 0.993930E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.676316E+10 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.269086E+10
February 0.702046E+11 0.607753E+10 0.114244E+11 0.00 0.00 0.00 0.00 296778.13 0.208346E+10
March 0.780153E+11 0.671841E+10 0.126786E+11 0.00 0.00 0.00 0.00 7154712.11 0.188714E+10
April 0.752779E+11 0.642370E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.177318E+09 0.880276E+09
May 0.778146E+11 0.663498E+10 0.126672E+11 0.00 0.00 0.00 0.00 0.433635E+09 0.377570E+09
June 0.754422E+11 0.640892E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.807747E+09 0.114824E+09
July 0.776503E+11 0.659273E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.744117E+09 79065091.33
August 0.779788E+11 0.667183E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.606570E+09 0.159913E+09
September 0.752414E+11 0.645683E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.353260E+09 0.412753E+09
October 0.776868E+11 0.673023E+10 0.126482E+11 0.00 0.00 0.00 0.00 90793375.52 0.102768E+10
November 0.751137E+11 0.652617E+10 0.122624E+11 0.00 0.00 0.00 0.00 335226.85 0.212333E+10
December 0.776503E+11 0.673834E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.294907E+10
                   
Annual Sum or Average 0.915726E+12 0.787428E+11 0.148998E+12 0.00 0.00 0.00 0.00 0.322123E+10 0.147859E+11
Minimum of Months 0.702046E+11 0.607753E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 79065091.33
Maximum of Months 0.780153E+11 0.676316E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.807747E+09 0.294907E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.224082E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 108124.40 0.171138E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 733261.14 0.152283E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 19438451.02 61331270.68
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 49622171.50 19826439.43
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 91686828.21 3314181.04
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 88966944.49 1071076.08
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 73337577.42 5221481.01
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 41766235.12 20156053.97
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 11603087.07 70022582.10
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 133316.49 0.169663E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.248041E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.377396E+09 0.114615E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 1071076.08
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 91686828.21 0.248041E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.218362E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 8538.25 0.168198E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 439359.37 0.153283E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 18617220.39 64803523.06
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 48043463.12 22936901.29
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 89495841.73 5162796.34
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 86293882.08 2613594.26
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 71416593.77 7755563.74
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 40284535.38 24169982.42
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 10752537.13 74856230.45
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 9991.33 0.167634E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.241587E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.365362E+09 0.115136E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 2613594.26
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 89495841.73 0.241587E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 65789991.58 0.217935E+09 0.00 0.00 0.00 0.00 0.00 85911943.73
February 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 0.00 68730725.22
March 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 0.00 65095347.89
April 0.00 63743496.62 0.210923E+09 0.00 0.00 0.00 0.00 1043560.63 34031187.64
May 0.00 65528554.53 0.217879E+09 0.00 0.00 0.00 0.00 4354958.44 17420802.35
June 0.00 63237765.93 0.210812E+09 0.00 0.00 0.00 0.00 11754079.94 7329332.03
July 0.00 66042856.93 0.217991E+09 0.00 0.00 0.00 0.00 9926286.90 6572749.88
August 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 7719413.09 9980561.95
September 0.00 63760640.03 0.210923E+09 0.00 0.00 0.00 0.00 3626715.72 18331149.23
October 0.00 65781419.88 0.217935E+09 0.00 0.00 0.00 0.00 656765.00 39091840.17
November 0.00 63490631.27 0.210867E+09 0.00 0.00 0.00 0.00 0.00 69363361.74
December 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 0.00 92688866.05
                   
Annual Sum or Average 0.00 0.773376E+09 0.256575E+10 0.00 0.00 0.00 0.00 39081779.71 0.514548E+09
Minimum of Months 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 0.00 6572749.88
Maximum of Months 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 11754079.94 92688866.05



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 0.00 61411991.36
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 44315.22 46898358.10
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 241232.04 42099414.66
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 5532068.59 17443380.83
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 13806817.28 6060876.39
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 25386620.49 1257119.04
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 24414223.46 560765.02
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 20310116.02 1933376.79
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 11664730.85 6350570.72
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 3348337.36 20002605.18
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 64254.71 46254014.05
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 0.00 68099986.33
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 0.104813E+09 0.318372E+09
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 560765.02
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 25386620.49 68099986.33



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.224856E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 114211.77 0.172542E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 752014.51 0.153776E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 19612318.09 62446107.59
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 49793347.42 20299932.35
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 91567175.77 3401304.06
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 88741456.37 1106522.93
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 73316826.84 5322091.39
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 41907658.59 20459962.67
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 11897569.88 70351744.48
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 153192.40 0.170288E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.248679E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.377856E+09 0.115353E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 1106522.93
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 91567175.77 0.248679E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.218127E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 11232.11 0.168863E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 443495.37 0.153903E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 18651187.06 66297392.31
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 47877222.65 25418673.37
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 88856382.47 6783682.61
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 85589383.20 3935154.08
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 70900888.59 9237991.40
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 39996417.14 26146635.31
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 10882984.15 74047130.89
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 37104.96 0.167173E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.241543E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.363246E+09 0.116148E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 3935154.08
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 88856382.47 0.241543E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.115875E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.270505E+09
February 0.348285E+10 0.104624E+10 0.00 0.00 0.00 0.00 0.00 210514.25 0.209308E+09
March 0.387034E+10 0.116232E+10 0.00 0.00 0.00 0.00 0.00 1215347.37 0.190677E+09
April 0.373454E+10 0.111946E+10 0.00 0.00 0.00 0.00 0.00 21067442.26 88188102.98
May 0.386038E+10 0.116076E+10 0.00 0.00 0.00 0.00 0.00 47428038.34 37666485.44
June 0.374269E+10 0.112460E+10 0.00 0.00 0.00 0.00 0.00 85761919.54 11934808.13
July 0.385223E+10 0.115562E+10 0.00 0.00 0.00 0.00 0.00 80446638.22 7570624.39
August 0.386853E+10 0.116277E+10 0.00 0.00 0.00 0.00 0.00 65819829.02 15926871.70
September 0.373273E+10 0.111991E+10 0.00 0.00 0.00 0.00 0.00 38311663.72 42526515.88
October 0.385404E+10 0.115830E+10 0.00 0.00 0.00 0.00 0.00 10979970.23 0.103682E+09
November 0.372639E+10 0.112370E+10 0.00 0.00 0.00 0.00 0.00 175727.26 0.215335E+09
December 0.385223E+10 0.115562E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.296925E+09
                   
Annual Sum or Average 0.454292E+11 0.136481E+11 0.00 0.00 0.00 0.00 0.00 0.351417E+09 0.149024E+10
Minimum of Months 0.348285E+10 0.104624E+10 0.00 0.00 0.00 0.00 0.00 0.00 7570624.39
Maximum of Months 0.387034E+10 0.116277E+10 0.00 0.00 0.00 0.00 0.00 85761919.54 0.296925E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.223350E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 98416.99 0.170857E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 695950.36 0.152301E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 18989679.95 61558986.52
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 48808893.96 20023583.20
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 90590315.57 3397414.51
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 87868492.28 1118073.35
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 72402251.58 5321068.35
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 41058793.08 20355044.68
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 11326510.07 70220609.59
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 120274.14 0.169375E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.247284E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.371960E+09 0.114516E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 1118073.35
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 90590315.57 0.247284E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.216888E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 9428.59 0.167430E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 412914.10 0.153190E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 18175027.20 65000232.06
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 47269217.89 22774841.37
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 88459992.47 4971679.51
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 85270019.52 2453798.24
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 70557397.33 7520138.44
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 39681407.56 23816733.88
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 10524227.74 74880516.34
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 7799.85 0.166672E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.240200E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.360367E+09 0.114580E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 2453798.24
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 88459992.47 0.240200E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.117200E+09
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 40751.71 89404076.82
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 345909.12 79135643.32
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 9853196.81 31706849.33
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 25374082.16 10243936.28
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 46805045.04 1730874.97
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 45309799.32 573448.82
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 37333394.71 2729354.38
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 21122474.44 10476197.83
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 5684586.20 36371645.59
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 43116.58 88233708.07
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 0.00 0.129899E+09
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 0.191912E+09 0.597705E+09
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 573448.82
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 46805045.04 0.129899E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.131589E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.592829E+09
February 0.415303E+11 0.116365E+10 0.134904E+11 0.00 0.00 0.00 0.00 304371.56 0.461190E+09
March 0.461508E+11 0.125912E+10 0.149358E+11 0.00 0.00 0.00 0.00 1830297.08 0.423370E+09
April 0.445315E+11 0.116644E+10 0.144540E+11 0.00 0.00 0.00 0.00 39921826.46 0.198549E+09
May 0.460320E+11 0.118348E+10 0.149358E+11 0.00 0.00 0.00 0.00 96738977.72 85391209.60
June 0.446286E+11 0.112659E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.180769E+09 26016882.88
July 0.459349E+11 0.115866E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.168017E+09 17989528.52
August 0.461292E+11 0.120709E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.139381E+09 35900553.72
September 0.445099E+11 0.119747E+10 0.144540E+11 0.00 0.00 0.00 0.00 85715359.31 90910333.80
October 0.459565E+11 0.128379E+10 0.149358E+11 0.00 0.00 0.00 0.00 24799704.28 0.222458E+09
November 0.444343E+11 0.125689E+10 0.144540E+11 0.00 0.00 0.00 0.00 433733.72 0.461035E+09
December 0.459349E+11 0.130644E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.649381E+09
                   
Annual Sum or Average 0.541708E+12 0.146255E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.737911E+09 0.326502E+10
Minimum of Months 0.415303E+11 0.112659E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 17989528.52
Maximum of Months 0.461508E+11 0.131589E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.180769E+09 0.649381E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.131589E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.608803E+09
February 0.415303E+11 0.116365E+10 0.134904E+11 0.00 0.00 0.00 0.00 116705.38 0.474156E+09
March 0.461508E+11 0.125912E+10 0.149358E+11 0.00 0.00 0.00 0.00 1195056.20 0.435821E+09
April 0.445315E+11 0.116644E+10 0.144540E+11 0.00 0.00 0.00 0.00 36630052.07 0.204065E+09
May 0.460320E+11 0.118348E+10 0.149358E+11 0.00 0.00 0.00 0.00 91772885.31 87494538.70
June 0.446286E+11 0.112659E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.175402E+09 26758613.87
July 0.459349E+11 0.115866E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.162160E+09 18634115.22
August 0.461292E+11 0.120709E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.134006E+09 37046589.85
September 0.445099E+11 0.119747E+10 0.144540E+11 0.00 0.00 0.00 0.00 80976277.95 93179626.52
October 0.459565E+11 0.128379E+10 0.149358E+11 0.00 0.00 0.00 0.00 22491249.77 0.229459E+09
November 0.444343E+11 0.125689E+10 0.144540E+11 0.00 0.00 0.00 0.00 267651.39 0.473444E+09
December 0.459349E+11 0.130644E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.666545E+09
                   
Annual Sum or Average 0.541708E+12 0.146255E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.705017E+09 0.335541E+10
Minimum of Months 0.415303E+11 0.112659E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 18634115.22
Maximum of Months 0.461508E+11 0.131589E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.175402E+09 0.666545E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.775957E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.586958E+09
February 0.369574E+10 0.700619E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.457698E+09
March 0.410691E+10 0.778349E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 145642.53 0.420286E+09
April 0.396281E+10 0.749649E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 25022328.90 0.195196E+09
May 0.409635E+10 0.777303E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 71062936.17 82897972.56
June 0.397146E+10 0.753087E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.146653E+09 25308113.66
July 0.408770E+10 0.773865E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.134033E+09 17775743.06
August 0.410499E+10 0.778648E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.108582E+09 35971683.71
September 0.396089E+10 0.749948E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 60325980.29 87571330.59
October 0.408962E+10 0.775658E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 14136749.41 0.222893E+09
November 0.395417E+10 0.752489E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.457986E+09
December 0.408770E+10 0.773865E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.641751E+09
                   
Annual Sum or Average 0.482060E+11 0.913943E+10 0.382987E+12 0.359593E+12 0.00 0.00 0.00 0.559962E+09 0.323229E+10
Minimum of Months 0.369574E+10 0.700619E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 17775743.06
Maximum of Months 0.410691E+10 0.778648E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.146653E+09 0.641751E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.122636E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.501421E+09
February 0.368610E+10 0.110729E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.398121E+09
March 0.409620E+10 0.123014E+10 0.00 0.00 0.00 0.00 0.00 189214.48 0.373627E+09
April 0.395248E+10 0.118478E+10 0.00 0.00 0.00 0.00 0.00 24475377.86 0.184409E+09
May 0.408566E+10 0.122848E+10 0.00 0.00 0.00 0.00 0.00 69381979.50 80608510.93
June 0.396110E+10 0.119021E+10 0.00 0.00 0.00 0.00 0.00 0.143340E+09 24824561.79
July 0.407704E+10 0.122305E+10 0.00 0.00 0.00 0.00 0.00 0.130987E+09 17449429.69
August 0.409429E+10 0.123061E+10 0.00 0.00 0.00 0.00 0.00 0.106107E+09 35245560.10
September 0.395056E+10 0.118525E+10 0.00 0.00 0.00 0.00 0.00 58902835.04 85259523.23
October 0.407896E+10 0.122588E+10 0.00 0.00 0.00 0.00 0.00 13789764.47 0.211673E+09
November 0.394385E+10 0.118927E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.408992E+09
December 0.407704E+10 0.122305E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.543636E+09
                   
Annual Sum or Average 0.480803E+11 0.144444E+11 0.00 0.00 0.00 0.00 0.00 0.547173E+09 0.286527E+10
Minimum of Months 0.368610E+10 0.110729E+10 0.00 0.00 0.00 0.00 0.00 0.00 17449429.69
Maximum of Months 0.409620E+10 0.123061E+10 0.00 0.00 0.00 0.00 0.00 0.143340E+09 0.543636E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 7561.54 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 7561.54 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 7561.54 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 7561.54 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 7561.54 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 7561.54 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 7561.54 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 7561.54 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 7561.54 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 7561.54 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 7561.54 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 7561.54 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   7561.54   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   7561.54   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 342.20 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 286.21 27-JAN-07:00
February 1169.53 01-FEB-00:10 342.20 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 300.77 03-FEB-07:00
March 1169.53 01-MAR-00:10 342.20 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 10.06 21-MAR-16:00 282.96 02-MAR-05:10
April 1169.53 01-APR-00:10 342.20 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 80.90 21-APR-14:00 194.39 12-APR-06:00
May 1169.53 01-MAY-00:10 342.20 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 108.34 21-MAY-14:00 138.27 02-MAY-06:00
June 1169.53 01-JUN-00:10 342.20 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 144.64 02-JUN-16:00 91.37 13-JUN-05:00
July 1169.53 01-JUL-00:10 342.20 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 139.37 02-JUL-16:00 58.36 05-JUL-06:00
August 1169.53 01-AUG-00:10 342.20 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 129.08 07-AUG-16:00 73.32 31-AUG-06:00
September 1169.53 01-SEP-00:10 342.20 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 97.61 19-SEP-14:00 156.25 30-SEP-06:00
October 1169.53 01-OCT-23:10 342.20 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 87.26 01-OCT-15:00 168.06 11-OCT-06:00
November 1169.53 01-NOV-00:10 342.20 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 244.79 17-NOV-04:00
December 1169.53 01-DEC-00:10 342.20 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 287.29 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   342.20   685.60   0.00 0.00 0.00 0.00 0.00   58.36  
Maximum of Months 1169.53   342.20   685.60   0.00 0.00 0.00 0.00 144.64   300.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 396.26 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 114.42 27-JAN-07:00
February 1354.32 01-FEB-00:10 396.26 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 3.31 20-FEB-15:00 120.42 03-FEB-07:00
March 1354.32 01-MAR-00:10 396.26 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 10.36 22-MAR-13:00 113.27 02-MAR-05:30
April 1354.32 01-APR-00:10 396.26 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 35.61 21-APR-14:00 81.19 12-APR-06:00
May 1354.32 01-MAY-00:10 396.26 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 45.15 19-MAY-14:00 57.09 02-MAY-06:00
June 1354.32 01-JUN-00:10 396.26 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 58.22 02-JUN-16:00 36.47 13-JUN-05:00
July 1354.32 01-JUL-00:10 396.26 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 56.73 02-JUL-16:00 23.87 05-JUL-06:00
August 1354.32 01-AUG-00:10 396.26 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 51.16 07-AUG-16:00 29.29 31-AUG-06:00
September 1354.32 01-SEP-00:10 396.26 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 39.79 19-SEP-14:00 63.35 30-SEP-06:00
October 1354.32 01-OCT-23:10 396.26 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 36.60 01-OCT-15:00 69.19 25-OCT-06:00
November 1354.32 01-NOV-00:10 396.26 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 4.34 03-NOV-16:00 99.97 17-NOV-04:00
December 1354.32 01-DEC-00:10 396.26 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 114.53 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   396.26   793.93   0.00 0.00 0.00 0.00 0.00   23.87  
Maximum of Months 1354.32   396.26   793.93   0.00 0.00 0.00 0.00 58.22   120.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 708.98 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 275.61 27-JAN-07:00
February 286.42 01-FEB-00:10 708.98 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 287.63 03-FEB-07:00
March 286.42 01-MAR-00:10 708.98 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 13.51 21-MAR-16:00 272.27 02-MAR-05:40
April 286.42 01-APR-00:10 708.98 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 73.80 21-APR-14:00 202.27 12-APR-06:00
May 286.42 01-MAY-00:10 708.98 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 98.84 21-MAY-14:00 141.87 02-MAY-06:00
June 286.42 01-JUN-00:10 708.98 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 131.95 02-JUN-16:00 86.21 13-JUN-05:00
July 286.42 01-JUL-00:10 708.98 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 127.14 02-JUL-16:00 58.98 05-JUL-06:00
August 286.42 01-AUG-00:10 708.98 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 117.75 07-AUG-16:00 70.06 31-AUG-06:00
September 286.42 01-SEP-00:10 708.98 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 89.05 19-SEP-14:00 153.93 30-SEP-06:00
October 286.42 01-OCT-23:10 708.98 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 79.60 01-OCT-15:00 171.55 25-OCT-06:00
November 286.42 01-NOV-00:10 708.98 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 242.51 17-NOV-04:00
December 286.42 01-DEC-00:10 708.98 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 275.01 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   708.98   839.45   0.00 0.00 0.00 0.00 0.00   58.98  
Maximum of Months 286.42   708.98   839.45   0.00 0.00 0.00 0.00 131.95   287.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 162.52 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 150.63 27-JAN-07:00
February 220.32 01-FEB-00:10 162.52 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 10.40 20-FEB-15:00 158.30 03-FEB-07:00
March 220.32 01-MAR-00:10 162.52 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 20.58 21-MAR-16:00 148.92 02-MAR-05:50
April 220.32 01-APR-00:10 162.52 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 50.76 21-APR-14:00 102.83 12-APR-06:00
May 220.32 01-MAY-00:10 162.52 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 63.41 19-MAY-16:00 71.06 02-MAY-06:00
June 220.32 01-JUN-00:10 162.52 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 81.03 02-JUN-16:00 44.17 13-JUN-05:00
July 220.32 01-JUL-00:10 162.52 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 77.92 01-JUL-16:51 28.25 05-JUL-06:00
August 220.32 01-AUG-00:10 162.52 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 71.41 07-AUG-16:00 34.25 31-AUG-06:00
September 220.32 01-SEP-00:10 162.52 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 57.30 19-SEP-16:00 79.64 30-SEP-06:00
October 220.32 01-OCT-23:10 162.52 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 53.40 01-OCT-15:00 86.69 11-OCT-06:00
November 220.32 01-NOV-00:10 162.52 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 11.55 03-NOV-16:00 127.67 28-NOV-05:00
December 220.32 01-DEC-00:10 162.52 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 151.19 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   162.52   242.16   0.00 0.00 0.00 0.00 0.00   28.25  
Maximum of Months 220.32   162.52   242.16   0.00 0.00 0.00 0.00 81.03   158.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 302.47 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 398.60 27-JAN-07:00
February 907.20 01-FEB-00:10 302.47 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:05 416.88 03-FEB-07:00
March 907.20 01-MAR-00:10 302.47 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 12.53 21-MAR-16:00 394.89 02-MAR-05:00
April 907.20 01-APR-00:10 302.47 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 100.77 21-APR-14:00 280.58 12-APR-06:00
May 907.20 01-MAY-00:10 302.47 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 134.95 21-MAY-14:00 193.72 02-MAY-06:00
June 907.20 01-JUN-00:10 302.47 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 180.17 02-JUN-16:00 117.71 13-JUN-05:00
July 907.20 01-JUL-00:10 302.47 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 173.60 02-JUL-16:00 80.53 05-JUL-06:00
August 907.20 01-AUG-00:10 302.47 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 160.80 07-AUG-16:00 95.66 31-AUG-06:00
September 907.20 01-SEP-00:10 302.47 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 121.60 19-SEP-14:00 210.17 30-SEP-06:00
October 907.20 01-OCT-23:10 302.47 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 108.69 01-OCT-15:00 234.23 25-OCT-06:00
November 907.20 01-NOV-00:10 302.47 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:10 344.11 28-NOV-05:00
December 907.20 01-DEC-00:10 302.47 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:05 400.10 27-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   302.47   4572.80   39726.58   0.00 0.00 0.00 0.00   80.53  
Maximum of Months 907.20   302.47   4572.80   39726.58   0.00 0.00 0.00 180.17   416.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 810.33 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 643.76 27-JAN-07:00
February 15368.40 01-FEB-00:10 810.33 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 12.20 22-FEB-16:00 675.49 03-FEB-07:00
March 15368.40 01-MAR-00:10 810.33 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 49.08 21-MAR-16:00 649.43 02-MAR-05:20
April 15368.40 01-APR-00:10 810.33 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 207.14 21-APR-15:00 447.27 12-APR-06:00
May 15368.40 01-MAY-00:10 810.33 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 272.29 21-MAY-14:00 306.39 02-MAY-06:00
June 15368.40 01-JUN-00:10 810.33 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 347.19 02-JUN-17:00 198.58 13-JUN-05:00
July 15368.40 01-JUL-00:10 810.33 03-JUL-19:19 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 344.81 02-JUL-16:00 119.25 05-JUL-06:00
August 15368.40 01-AUG-00:10 810.33 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 304.34 07-AUG-16:00 149.97 31-AUG-06:00
September 15368.40 01-SEP-00:10 810.33 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 222.78 19-SEP-16:00 342.99 30-SEP-06:00
October 15368.40 01-OCT-23:10 810.33 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 200.06 01-OCT-15:00 378.68 25-OCT-05:00
November 15368.40 01-NOV-00:10 810.33 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 11.85 08-NOV-15:40 570.22 17-NOV-04:00
December 15368.40 01-DEC-00:10 810.33 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 655.94 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   810.33   965.27   0.00 0.00 0.00 0.00 0.00   119.25  
Maximum of Months 15368.40   810.33   965.27   0.00 0.00 0.00 0.00 347.19   675.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 6817.32 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1928.03 27-JAN-07:00
February 45622.98 01-FEB-00:10 6817.32 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 40.74 20-FEB-16:00 2019.89 03-FEB-07:00
March 45622.98 01-MAR-00:10 6817.32 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 154.17 22-MAR-13:00 1923.71 02-MAR-05:40
April 45622.98 01-APR-00:10 6817.32 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 580.25 21-APR-14:00 1364.94 12-APR-06:00
May 45622.98 01-MAY-00:10 6817.32 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 749.51 19-MAY-14:00 955.43 02-MAY-06:00
June 45622.98 01-JUN-00:10 6817.32 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 958.72 02-JUN-16:00 596.75 13-JUN-05:00
July 45622.98 01-JUL-00:10 6817.32 03-JUL-19:19 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 946.34 02-JUL-16:00 407.85 05-JUL-06:00
August 45622.98 01-AUG-00:10 6817.32 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 845.15 07-AUG-16:00 484.95 31-AUG-06:00
September 45622.98 01-SEP-00:10 6817.32 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 649.33 19-SEP-14:00 1051.38 30-SEP-06:00
October 45622.98 01-OCT-23:10 6817.32 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 595.79 01-OCT-15:00 1159.35 25-OCT-06:00
November 45622.98 01-NOV-00:10 6817.32 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 54.78 08-NOV-15:00 1688.82 17-NOV-04:00
December 45622.98 01-DEC-00:10 6817.32 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 1940.21 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   6817.32   10029.21   0.00 0.00 0.00 0.00 0.00   407.85  
Maximum of Months 45622.98   6817.32   10029.21   0.00 0.00 0.00 0.00 958.72   2019.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.12 27-JAN-07:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 9.73 20-FEB-16:20 175.57 03-FEB-07:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 22.49 21-MAR-16:00 165.23 02-MAR-05:10
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 59.70 21-APR-15:20 112.77 12-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 73.24 19-MAY-16:00 72.67 02-MAY-06:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 99.53 02-JUN-16:40 37.51 13-JUN-05:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 96.71 03-JUL-16:00 20.31 05-JUL-06:00
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 85.02 07-AUG-16:00 29.71 14-AUG-07:20
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 65.02 19-SEP-16:00 80.18 30-SEP-06:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 58.24 01-OCT-16:40 91.19 25-OCT-06:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 14.87 03-NOV-16:00 141.79 28-NOV-05:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 167.75 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   20.31  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 99.53   175.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.11 27-JAN-07:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 3.54 06-FEB-14:00 175.56 03-FEB-07:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 22.50 21-MAR-16:00 165.22 02-MAR-05:10
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 60.54 21-APR-15:20 112.76 12-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 73.00 19-MAY-16:00 72.66 02-MAY-06:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 99.50 02-JUN-16:40 39.13 13-JUN-06:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 96.70 03-JUL-16:00 28.04 05-JUL-06:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 85.39 07-AUG-16:00 34.12 31-AUG-06:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 66.95 19-SEP-16:00 80.18 30-SEP-06:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 60.13 01-OCT-15:20 91.18 25-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 3.09 08-NOV-15:00 141.78 28-NOV-05:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 167.73 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   28.04  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 99.50   175.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 59.53 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 55.28 27-JAN-08:00
February 0.00 01-FEB-00:10 59.53 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 57.65 03-FEB-07:00
March 0.00 01-MAR-00:10 59.53 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 53.42 02-MAR-05:00
April 0.00 01-APR-00:10 59.53 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 8.77 21-APR-14:00 40.74 12-APR-06:00
May 0.00 01-MAY-00:10 59.53 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 13.22 21-MAY-14:00 29.86 02-MAY-06:00
June 0.00 01-JUN-00:10 59.53 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 19.16 02-JUN-16:00 19.91 13-JUN-05:00
July 0.00 01-JUL-00:10 59.53 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 18.29 02-JUL-16:00 15.04 05-JUL-06:00
August 0.00 01-AUG-00:10 59.53 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 16.61 07-AUG-16:00 17.05 31-AUG-06:00
September 0.00 01-SEP-00:10 59.53 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 11.48 19-SEP-14:00 32.04 30-SEP-06:00
October 0.00 01-OCT-00:10 59.53 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 9.78 01-OCT-15:00 35.22 25-OCT-06:00
November 0.00 01-NOV-00:10 59.53 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 48.34 17-NOV-04:00
December 0.00 01-DEC-00:10 59.53 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 54.41 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 0.00   15.04  
Maximum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 19.16   57.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 46.64 27-JAN-07:00
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 2.78 06-FEB-14:00 49.00 03-FEB-07:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 6.28 21-MAR-16:00 46.11 02-MAR-05:10
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 17.07 21-APR-15:20 31.47 12-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 22.00 19-MAY-16:00 20.28 02-MAY-06:00
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 27.84 02-JUN-16:00 10.47 13-JUN-05:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 26.99 02-JUL-16:00 7.41 05-JUL-06:00
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 25.40 07-AUG-16:00 9.66 16-AUG-21:40
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 20.33 19-SEP-16:00 22.38 30-SEP-06:00
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 18.12 01-OCT-15:20 25.45 25-OCT-06:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 3.01 08-NOV-14:00 39.57 28-NOV-05:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 46.82 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 0.00   7.41  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 27.84   49.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.12 27-JAN-07:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 10.60 20-FEB-16:20 175.57 03-FEB-07:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 22.51 21-MAR-16:00 165.23 02-MAR-05:50
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 61.07 21-APR-15:20 112.77 12-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 77.87 19-MAY-16:00 72.67 02-MAY-06:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 99.34 02-JUN-16:50 37.51 13-JUN-05:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 95.92 03-JUL-16:50 23.96 05-JUL-07:00
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 89.07 07-AUG-16:00 32.94 30-AUG-07:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 70.99 19-SEP-16:00 80.18 30-SEP-06:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 60.55 01-OCT-15:20 91.19 25-OCT-06:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 16.24 03-NOV-16:00 141.79 28-NOV-05:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 167.75 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   23.96  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 99.34   175.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.11 27-JAN-07:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.23 06-FEB-14:00 175.56 03-FEB-07:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 22.51 21-MAR-16:00 165.22 02-MAR-05:10
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 61.12 21-APR-15:20 112.76 12-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 76.89 19-MAY-16:00 72.67 02-MAY-06:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 98.45 02-JUN-16:50 40.91 13-JUN-06:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 95.84 03-JUL-16:50 34.78 05-JUL-07:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 89.01 07-AUG-16:00 38.99 30-AUG-07:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 72.19 19-SEP-16:00 80.18 30-SEP-06:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 63.93 01-OCT-15:20 91.18 25-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 6.96 03-NOV-16:00 141.78 28-NOV-05:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 167.73 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   34.78  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 98.45   175.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1116.11 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 201.21 27-JAN-07:00
February 2263.36 01-FEB-00:10 1116.11 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 8.71 20-FEB-16:00 211.43 03-FEB-07:00
March 2263.36 01-MAR-00:10 1116.11 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 19.76 21-MAR-16:00 200.19 02-MAR-05:00
April 2263.36 01-APR-00:10 1116.11 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 64.06 21-APR-14:00 144.29 12-APR-06:00
May 2263.36 01-MAY-00:10 1116.11 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 80.00 19-MAY-14:00 100.64 02-MAY-06:00
June 2263.36 01-JUN-00:10 1116.11 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 103.95 02-JUN-16:00 64.40 13-JUN-05:00
July 2263.36 01-JUL-00:10 1116.11 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 100.81 02-JUL-16:00 42.27 05-JUL-06:00
August 2263.36 01-AUG-00:10 1116.11 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 91.45 07-AUG-16:00 50.16 31-AUG-06:00
September 2263.36 01-SEP-00:10 1116.11 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 70.53 19-SEP-14:00 112.17 30-SEP-06:00
October 2263.36 01-OCT-23:10 1116.11 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 65.38 01-OCT-15:00 121.37 25-OCT-06:00
November 2263.36 01-NOV-00:10 1116.11 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 10.38 08-NOV-15:00 177.11 17-NOV-04:00
December 2263.36 01-DEC-00:10 1116.11 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 201.97 27-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1116.11   0.00 0.00 0.00 0.00 0.00 0.00   42.27  
Maximum of Months 2263.36   1116.11   0.00 0.00 0.00 0.00 0.00 103.95   211.43  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.55 27-JAN-07:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 8.95 20-FEB-16:20 176.00 03-FEB-07:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 22.12 21-MAR-16:00 165.66 02-MAR-05:10
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 58.76 21-APR-15:20 113.16 12-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 71.62 19-MAY-16:00 73.05 02-MAY-06:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 99.07 02-JUN-16:50 37.88 13-JUN-05:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 96.24 03-JUL-16:20 20.67 05-JUL-06:00
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 83.20 07-AUG-16:00 28.12 14-AUG-07:20
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 63.28 19-SEP-16:00 80.57 30-SEP-06:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 57.39 01-OCT-16:40 91.58 25-OCT-06:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 13.65 03-NOV-16:00 142.21 28-NOV-05:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 168.18 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   20.67  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 99.07   176.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.54 27-JAN-07:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 3.69 06-FEB-14:00 175.98 03-FEB-07:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 22.16 21-MAR-16:00 165.65 02-MAR-05:10
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 59.61 21-APR-15:20 113.15 12-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 71.38 19-MAY-16:00 73.05 02-MAY-06:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 98.64 02-JUN-16:50 37.88 13-JUN-05:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 96.23 03-JUL-16:20 26.62 18-JUL-21:50
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 83.59 07-AUG-16:00 32.28 16-AUG-21:30
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 65.34 19-SEP-16:00 80.56 30-SEP-06:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 59.15 01-OCT-15:20 91.57 25-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 2.73 08-NOV-15:00 142.20 28-NOV-05:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 168.16 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   26.62  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 98.64   175.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 85.72 27-JAN-07:00
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 3.69 22-FEB-16:20 90.05 03-FEB-07:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 11.30 21-MAR-16:00 84.76 02-MAR-05:10
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 30.58 21-APR-15:20 57.90 12-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 39.76 19-MAY-16:00 37.38 02-MAY-06:00
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 49.95 02-JUN-16:50 19.38 13-JUN-05:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 49.09 03-JUL-16:50 10.58 05-JUL-06:00
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 44.99 07-AUG-16:00 14.28 14-AUG-07:20
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 34.21 19-SEP-16:00 41.22 30-SEP-06:00
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 28.84 01-OCT-15:20 46.86 25-OCT-06:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 5.40 03-NOV-16:00 72.76 28-NOV-05:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 86.04 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 0.00   10.58  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 49.95   90.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 1423.01 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 433.69 27-JAN-07:00
February 26988.77 01-FEB-00:10 1423.01 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 17.20 20-FEB-16:00 453.24 03-FEB-07:00
March 26988.77 01-MAR-00:10 1423.01 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 39.64 22-MAR-13:00 432.86 02-MAR-05:10
April 26988.77 01-APR-00:10 1423.01 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 131.59 21-APR-14:00 309.59 12-APR-06:00
May 26988.77 01-MAY-00:10 1423.01 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 167.82 19-MAY-14:00 217.10 02-MAY-06:00
June 26988.77 01-JUN-00:10 1423.01 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 213.21 02-JUN-16:30 135.39 13-JUN-05:00
July 26988.77 01-JUL-00:10 1423.01 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 212.27 02-JUL-16:00 92.95 05-JUL-06:00
August 26988.77 01-AUG-00:10 1423.01 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 190.18 07-AUG-16:00 109.65 31-AUG-06:00
September 26988.77 01-SEP-00:10 1423.01 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 154.05 19-SEP-14:00 235.12 30-SEP-06:00
October 26988.77 01-OCT-23:10 1423.01 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 142.99 01-OCT-15:00 258.46 25-OCT-06:00
November 26988.77 01-NOV-00:10 1423.01 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 24.91 08-NOV-15:00 376.45 27-NOV-23:00
December 26988.77 01-DEC-00:10 1423.01 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 433.37 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   1423.01   6747.90   0.00 0.00 0.00 0.00 0.00   92.95  
Maximum of Months 26988.77   1423.01   6747.90   0.00 0.00 0.00 0.00 213.21   453.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 1423.01 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 440.06 27-JAN-07:00
February 26988.77 01-FEB-00:10 1423.01 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 11.87 20-FEB-16:00 459.44 03-FEB-07:00
March 26988.77 01-MAR-00:10 1423.01 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 34.62 22-MAR-13:00 438.10 02-MAR-05:10
April 26988.77 01-APR-00:10 1423.01 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 127.63 21-APR-14:00 314.02 12-APR-06:00
May 26988.77 01-MAY-00:10 1423.01 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 163.85 19-MAY-14:00 220.72 02-MAY-06:00
June 26988.77 01-JUN-00:10 1423.01 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 208.83 02-JUN-16:30 135.39 13-JUN-05:00
July 26988.77 01-JUL-00:10 1423.01 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 207.67 02-JUL-16:00 93.09 05-JUL-06:00
August 26988.77 01-AUG-00:10 1423.01 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 185.90 07-AUG-16:00 110.32 31-AUG-06:00
September 26988.77 01-SEP-00:10 1423.01 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 150.20 19-SEP-14:00 238.61 30-SEP-06:00
October 26988.77 01-OCT-23:10 1423.01 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 138.67 01-OCT-15:00 262.47 25-OCT-06:00
November 26988.77 01-NOV-00:10 1423.01 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 20.26 08-NOV-15:00 382.32 27-NOV-23:00
December 26988.77 01-DEC-00:10 1423.01 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 440.04 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   1423.01   6747.90   0.00 0.00 0.00 0.00 0.00   93.09  
Maximum of Months 26988.77   1423.01   6747.90   0.00 0.00 0.00 0.00 208.83   459.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 747.41 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 407.42 27-JAN-07:00
February 2401.70 01-FEB-00:10 747.41 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:05 426.04 03-FEB-07:00
March 2401.70 01-MAR-00:10 747.41 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 11.68 21-MAR-16:00 403.71 02-MAR-05:00
April 2401.70 01-APR-00:10 747.41 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 101.51 21-APR-14:00 287.13 12-APR-06:00
May 2401.70 01-MAY-00:10 747.41 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 136.32 21-MAY-14:00 198.61 02-MAY-06:00
June 2401.70 01-JUN-00:10 747.41 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 182.51 02-JUN-16:00 121.20 13-JUN-05:00
July 2401.70 01-JUL-00:10 747.41 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 175.80 02-JUL-16:00 83.30 05-JUL-06:00
August 2401.70 01-AUG-00:10 747.41 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 162.75 07-AUG-16:00 98.71 31-AUG-06:00
September 2401.70 01-SEP-00:10 747.41 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 122.72 19-SEP-14:00 215.39 30-SEP-06:00
October 2401.70 01-OCT-23:10 747.41 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 109.59 01-OCT-15:00 239.91 25-OCT-06:00
November 2401.70 01-NOV-00:10 747.41 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:10 351.96 28-NOV-05:00
December 2401.70 01-DEC-00:10 747.41 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:05 408.95 27-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   747.41   14604.56   22492.83   0.00 0.00 0.00 0.00   83.30  
Maximum of Months 2401.70   747.41   14604.56   22492.83   0.00 0.00 0.00 182.51   426.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1181.23 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 356.93 27-JAN-07:00
February 2395.44 01-FEB-00:10 1181.23 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 375.00 03-FEB-07:00
March 2395.44 01-MAR-00:10 1181.23 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 13.34 21-MAR-16:00 354.49 02-MAR-05:00
April 2395.44 01-APR-00:10 1181.23 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 99.23 21-APR-14:00 261.26 12-APR-06:00
May 2395.44 01-MAY-00:10 1181.23 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 133.32 21-MAY-14:00 188.04 02-MAY-06:00
June 2395.44 01-JUN-00:10 1181.23 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 178.42 02-JUN-16:00 118.71 13-JUN-05:00
July 2395.44 01-JUL-00:10 1181.23 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 171.86 02-JUL-16:00 81.62 05-JUL-06:00
August 2395.44 01-AUG-00:10 1181.23 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 159.08 07-AUG-16:00 96.72 31-AUG-06:00
September 2395.44 01-SEP-00:10 1181.23 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 119.99 19-SEP-14:00 204.88 30-SEP-06:00
October 2395.44 01-OCT-23:10 1181.23 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 107.12 01-OCT-15:00 222.66 11-OCT-06:00
November 2395.44 01-NOV-00:10 1181.23 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 314.05 17-NOV-04:00
December 2395.44 01-DEC-00:10 1181.23 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 358.26 27-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1181.23   0.00 0.00 0.00 0.00 0.00 0.00   81.62  
Maximum of Months 2395.44   1181.23   0.00 0.00 0.00 0.00 0.00 178.42   375.00  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 12537.79 12-JAN-19:10 53675.50 40328.28 54753.33 0.00 0.00 0.00 0.00 0.00 0.00
February 11906.13 01-FEB-21:00 8945.92 7561.54 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
March 10466.84 01-MAR-21:00 8945.92 7561.54 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
April 11238.50 30-APR-10:35 7667.93 5040.95 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
May 11827.62 21-MAY-10:35 7667.93 5040.95 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
June 12642.97 15-JUN-18:10 35783.66 26885.52 36502.22 0.00 0.00 0.00 0.00 0.00 0.00
July 14071.11 26-JUL-18:10 35783.66 26885.52 36502.22 0.00 0.00 0.00 0.00 0.00 0.00
August 17781.69 24-AUG-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
September 20503.50 22-SEP-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
October 20339.36 31-OCT-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 19797.54 01-NOV-21:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
December 17773.78 01-DEC-22:00 10223.90 6721.38 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 10466.84   7667.93 5040.95 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20503.50   53675.50 40328.28 54753.33 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2328.25 12-JAN-13:50 259.90 95.05 252.59 0.00 0.00 0.00 0.00 0.00 62.56
February 2400.21 07-FEB-13:30 259.90 95.05 252.59 0.00 0.00 0.00 0.00 0.00 37.97
March 1913.09 16-MAR-13:20 519.79 190.11 505.18 0.00 0.00 0.00 0.00 0.00 16.31
April 2012.05 03-APR-14:10 389.84 95.05 252.59 0.00 0.00 0.00 0.00 27.21 0.00
May 2049.04 19-MAY-20:10 1039.58 304.17 649.52 0.00 0.00 0.00 0.00 68.68 0.00
June 2371.60 15-JUN-18:17 2728.91 912.52 1948.56 0.00 0.00 0.00 0.00 114.74 0.00
July 2363.18 26-JUL-18:05 3638.54 1216.70 2598.08 0.00 0.00 0.00 0.00 96.65 0.00
August 2480.33 27-AUG-12:00 389.84 114.07 288.68 0.00 0.00 0.00 0.00 92.38 0.00
September 2966.20 20-SEP-12:50 259.90 95.05 252.59 0.00 0.00 0.00 0.00 80.63 0.00
October 3059.60 18-OCT-13:00 259.90 95.05 252.59 0.00 0.00 0.00 0.00 38.38 0.00
November 2908.95 10-NOV-12:00 259.90 95.05 252.59 0.00 0.00 0.00 0.00 0.00 29.81
December 2138.84 16-DEC-13:30 389.84 95.05 252.59 0.00 0.00 0.00 0.00 0.00 101.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1913.09   259.90 95.05 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3059.60   3638.54 1216.70 2598.08 0.00 0.00 0.00 0.00 114.74 101.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1271.71 12-JAN-21:00 1053.36 396.26 793.93 0.00 0.00 0.00 0.00 0.00 43.28
February 1316.81 21-FEB-21:00 2106.72 792.53 1587.86 0.00 0.00 0.00 0.00 0.00 34.68
March 1340.04 16-MAR-18:10 6320.16 2113.41 4512.87 0.00 0.00 0.00 0.00 0.00 13.19
April 1602.22 28-APR-20:55 2407.68 704.47 1504.29 0.00 0.00 0.00 0.00 0.00 4.75
May 1803.61 19-MAY-21:00 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 23.06 0.00
June 2029.08 15-JUN-21:00 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 35.40 0.00
July 1991.57 26-JUL-21:00 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 19.02 0.00
August 2043.34 07-AUG-21:00 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 29.59 0.00
September 1918.61 20-SEP-21:00 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 1.56 0.00
October 1835.45 05-OCT-21:00 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 0.00 2.77
November 1462.13 09-NOV-22:00 1203.84 352.23 752.15 0.00 0.00 0.00 0.00 0.00 20.35
December 1228.15 07-DEC-21:00 1053.36 396.26 793.93 0.00 0.00 0.00 0.00 0.00 56.57
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1228.15   1053.36 352.23 752.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2043.34   6320.16 2113.41 4512.87 0.00 0.00 0.00 0.00 35.40 56.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 334.20 03-JAN-22:00 254.59 630.21 795.27 0.00 0.00 0.00 0.00 0.00 107.68
February 525.93 07-FEB-21:55 509.18 1260.42 1590.53 0.00 0.00 0.00 0.00 0.00 85.49
March 753.44 16-MAR-21:00 254.59 630.21 795.27 0.00 0.00 0.00 0.00 0.00 64.51
April 1317.13 21-APR-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 19.19 0.00
May 1668.03 31-MAY-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 49.33 0.00
June 1994.89 15-JUN-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 88.47 0.00
July 1956.64 03-JUL-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 39.39 0.00
August 1950.96 07-AUG-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 69.70 0.00
September 1664.52 22-SEP-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 19.36 0.00
October 1538.52 05-OCT-20:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 0.00 0.96
November 1001.79 09-NOV-21:00 222.77 708.98 839.45 0.00 0.00 0.00 0.00 0.00 37.63
December 207.20 15-DEC-22:00 254.59 630.21 795.27 0.00 0.00 0.00 0.00 0.00 92.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 207.20   222.77 630.21 795.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1994.89   509.18 1260.42 1590.53 0.00 0.00 0.00 0.00 88.47 107.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 643.80 01-JAN-11:35 146.88 108.35 203.92 0.00 0.00 0.00 0.00 0.00 40.19
February 695.13 20-FEB-11:35 146.88 108.35 203.92 0.00 0.00 0.00 0.00 0.00 4.83
March 716.47 16-MAR-10:35 97.92 90.28 178.43 0.00 0.00 0.00 0.00 0.00 7.88
April 840.67 30-APR-10:35 146.88 108.35 203.92 0.00 0.00 0.00 0.00 9.80 0.00
May 889.35 31-MAY-18:10 685.44 577.83 917.65 0.00 0.00 0.00 0.00 41.68 0.00
June 954.00 18-JUN-10:35 146.88 108.35 203.92 0.00 0.00 0.00 0.00 48.36 0.00
July 955.46 03-JUL-18:10 685.44 577.83 917.65 0.00 0.00 0.00 0.00 66.06 0.00
August 957.34 06-AUG-10:35 146.88 108.35 203.92 0.00 0.00 0.00 0.00 44.33 0.00
September 905.74 23-SEP-10:35 146.88 90.28 178.43 0.00 0.00 0.00 0.00 22.89 0.00
October 874.06 05-OCT-10:35 97.92 90.28 178.43 0.00 0.00 0.00 0.00 26.02 0.00
November 765.12 10-NOV-11:35 97.92 90.28 178.43 0.00 0.00 0.00 0.00 0.00 6.44
December 647.00 16-DEC-11:35 146.88 90.28 178.43 0.00 0.00 0.00 0.00 0.00 47.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 643.80   97.92 90.28 178.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 957.34   685.44 577.83 917.65 0.00 0.00 0.00 0.00 66.06 47.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37468.57 12-JAN-21:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 148.91
February 37799.38 21-FEB-20:55 1411.20 604.94 9145.60 79453.15 0.00 0.00 0.00 0.00 118.12
March 37950.35 16-MAR-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 88.01
April 38755.76 28-APR-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 12.61 0.00
May 39085.86 30-MAY-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 61.20 0.00
June 39470.87 15-JUN-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 120.81 0.00
July 39427.18 26-JUL-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 67.45 0.00
August 39382.62 04-AUG-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 114.33 0.00
September 39072.44 20-SEP-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 20.15 0.00
October 38846.69 05-OCT-20:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 1.31
November 38134.47 09-NOV-21:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 51.39
December 37271.24 15-DEC-21:00 705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 125.84
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 37271.24   705.60 302.47 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39470.87   1411.20 604.94 9145.60 79453.15 0.00 0.00 0.00 120.81 148.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10248.25 01-JAN-11:35 10245.60 118.85 812.86 0.00 0.00 0.00 0.00 0.00 227.65
February 10218.14 19-FEB-11:35 10245.60 118.85 812.86 0.00 0.00 0.00 0.00 0.00 95.70
March 9813.30 05-MAR-11:35 10245.60 118.85 812.86 0.00 0.00 0.00 0.00 0.00 140.44
April 9917.53 19-APR-18:10 47812.80 1874.95 3657.88 0.00 0.00 0.00 0.00 159.54 0.00
May 10251.17 31-MAY-18:10 47812.80 977.75 3657.88 0.00 0.00 0.00 0.00 178.88 0.00
June 10728.24 15-JUN-18:10 47812.80 1040.57 3657.88 0.00 0.00 0.00 0.00 278.54 0.00
July 10795.33 26-JUL-18:10 47812.80 1065.38 3657.88 0.00 0.00 0.00 0.00 233.96 0.00
August 10954.73 07-AUG-21:10 15368.40 540.22 711.25 0.00 0.00 0.00 0.00 159.89 0.00
September 11014.98 17-SEP-10:35 10245.60 118.85 812.86 0.00 0.00 0.00 0.00 139.15 0.00
October 11118.51 22-OCT-10:35 10245.60 118.85 812.86 0.00 0.00 0.00 0.00 0.00 32.84
November 11033.79 11-NOV-10:53 51228.00 356.55 2438.58 0.00 0.00 0.00 0.00 0.00 183.18
December 9971.09 10-DEC-11:35 10245.60 118.85 812.86 0.00 0.00 0.00 0.00 0.00 171.23
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9813.30   10245.60 118.85 711.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11118.51   51228.00 1874.95 3657.88 0.00 0.00 0.00 0.00 278.54 227.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 28242.15 12-JAN-22:10 91245.96 9089.76 14779.89 0.00 0.00 0.00 0.00 0.00 950.65
February 29323.26 22-FEB-22:04 228114.90 22724.39 36949.72 0.00 0.00 0.00 0.00 0.00 634.35
March 29960.47 16-MAR-21:10 91245.96 9089.76 14779.89 0.00 0.00 0.00 0.00 0.00 459.09
April 33872.72 21-APR-21:10 91245.96 9089.76 14779.89 0.00 0.00 0.00 0.00 57.14 0.00
May 36562.80 31-MAY-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 262.56 0.00
June 39172.77 15-JUN-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 534.79 0.00
July 39053.68 26-JUL-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 293.48 0.00
August 39985.68 07-AUG-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 456.69 0.00
September 38400.01 21-SEP-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 134.26 0.00
October 37738.03 05-OCT-21:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 0.00 50.70
November 34013.25 09-NOV-22:10 45622.98 4544.88 7389.94 0.00 0.00 0.00 0.00 0.00 357.22
December 26814.82 15-DEC-21:00 35484.54 6817.32 10029.21 0.00 0.00 0.00 0.00 0.00 607.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 26814.82   35484.54 4544.88 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39985.68   228114.90 22724.39 36949.72 0.00 0.00 0.00 0.00 534.79 950.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1812.10 12-JAN-16:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 25.76
February 1882.05 20-FEB-16:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 0.00 0.17
March 1882.04 16-MAR-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 2.14
April 1897.05 15-APR-15:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 24.58 0.00
May 1906.02 17-MAY-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 37.09 0.00
June 1922.69 15-JUN-18:03 554.40 337.19 484.65 0.00 0.00 0.00 0.00 72.71 0.00
July 1905.88 31-JUL-18:02 693.00 421.49 605.82 0.00 0.00 0.00 0.00 58.53 0.00
August 1895.35 28-AUG-18:02 693.00 421.49 605.82 0.00 0.00 0.00 0.00 35.49 0.00
September 1897.39 01-SEP-18:02 693.00 421.49 605.82 0.00 0.00 0.00 0.00 46.94 0.00
October 1891.16 04-OCT-15:12 486.00 132.60 250.23 0.00 0.00 0.00 0.00 41.41 0.00
November 1862.96 07-NOV-16:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 9.33
December 1793.15 16-DEC-16:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 0.00 51.54
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1793.15   324.00 132.60 250.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1922.69   693.00 421.49 605.82 0.00 0.00 0.00 0.00 72.71 51.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1729.56 30-JAN-16:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 0.00 41.87
February 1755.12 24-FEB-16:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 0.00 61.93
March 1832.82 21-MAR-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 10.41 0.00
April 2035.45 06-APR-18:11 1386.00 842.88 1211.49 0.00 0.00 0.00 0.00 0.00 60.66
May 1981.51 20-MAY-08:51 432.00 424.28 1306.30 0.00 0.00 0.00 0.00 16.25 0.00
June 2062.79 19-JUN-18:51 1247.40 758.59 1090.34 0.00 0.00 0.00 0.00 13.34 0.00
July 1892.84 09-JUL-18:02 585.00 473.53 605.75 0.00 0.00 0.00 0.00 55.54 0.00
August 1968.31 26-AUG-08:11 432.00 424.28 1306.30 0.00 0.00 0.00 0.00 17.93 0.00
September 1887.73 29-SEP-21:51 1260.00 444.17 626.82 0.00 0.00 0.00 0.00 0.00 23.80
October 1863.86 08-OCT-15:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 21.02 0.00
November 1764.26 12-NOV-16:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 0.00 49.03
December 1741.11 16-DEC-16:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 0.00 50.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1729.56   324.00 159.11 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2062.79   1386.00 842.88 1306.30 0.00 0.00 0.00 0.00 55.54 61.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 432.82 12-JAN-14:25 0.00 33.33 61.92 0.00 0.00 0.00 0.00 0.00 13.74
February 409.61 07-FEB-13:40 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 10.82
March 326.08 07-MAR-13:10 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 9.85
April 296.57 03-APR-13:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 0.92
May 288.34 31-MAY-20:20 0.00 52.98 178.01 0.00 0.00 0.00 0.00 3.77 0.00
June 324.99 15-JUN-20:20 0.00 52.98 178.01 0.00 0.00 0.00 0.00 11.11 0.00
July 320.93 02-JUL-20:40 0.00 59.53 178.01 0.00 0.00 0.00 0.00 10.35 0.00
August 336.32 07-AUG-20:20 0.00 52.98 178.01 0.00 0.00 0.00 0.00 8.03 0.00
September 422.80 19-SEP-13:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 10.62 0.00
October 484.30 22-OCT-13:15 0.00 39.29 67.08 0.00 0.00 0.00 0.00 0.00 1.22
November 468.43 09-NOV-13:15 0.00 33.33 61.92 0.00 0.00 0.00 0.00 0.00 6.19
December 380.05 07-DEC-14:00 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 18.92
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 288.34   0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 484.30   0.00 59.53 178.01 0.00 0.00 0.00 0.00 11.11 18.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 634.22 13-JAN-19:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 0.00 14.99
February 667.64 21-FEB-21:32 801.00 264.96 890.31 0.00 0.00 0.00 0.00 0.00 13.45
March 698.85 15-MAR-21:52 900.00 199.47 438.70 0.00 0.00 0.00 0.00 0.00 5.43
April 729.89 20-APR-18:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 5.75 0.00
May 756.23 20-MAY-08:51 432.00 266.75 1279.98 0.00 0.00 0.00 0.00 5.36 0.00
June 771.39 14-JUN-08:11 324.00 235.79 998.70 0.00 0.00 0.00 0.00 6.91 0.00
July 739.19 06-JUL-08:61 288.00 209.59 887.73 0.00 0.00 0.00 0.00 4.05 0.00
August 731.88 29-AUG-21:51 1260.00 279.25 614.19 0.00 0.00 0.00 0.00 0.00 1.64
September 728.49 20-SEP-18:02 693.00 264.96 593.54 0.00 0.00 0.00 0.00 13.07 0.00
October 719.51 19-OCT-21:52 1080.00 239.36 526.45 0.00 0.00 0.00 0.00 0.00 5.99
November 660.63 08-NOV-22:52 900.00 199.47 438.70 0.00 0.00 0.00 0.00 0.00 13.51
December 641.10 16-DEC-09:02 324.00 200.06 959.99 0.00 0.00 0.00 0.00 0.00 23.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 634.22   288.00 199.47 438.70 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 771.39   1260.00 317.95 1279.98 0.00 0.00 0.00 0.00 13.07 23.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1617.55 03-JAN-16:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 14.62
February 1664.47 20-FEB-16:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 0.51 0.00
March 1666.87 16-MAR-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 1.52
April 1692.75 21-APR-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 50.83 0.00
May 1722.32 20-MAY-08:62 324.00 318.25 979.84 0.00 0.00 0.00 0.00 7.59 0.00
June 1734.56 18-JUN-08:62 324.00 318.25 979.84 0.00 0.00 0.00 0.00 19.82 0.00
July 1727.69 03-JUL-08:62 216.00 250.05 679.57 0.00 0.00 0.00 0.00 35.44 0.00
August 1717.57 20-AUG-08:62 324.00 318.25 979.84 0.00 0.00 0.00 0.00 1.87 0.00
September 1706.29 16-SEP-15:12 270.00 156.28 276.57 0.00 0.00 0.00 0.00 53.23 0.00
October 1687.33 05-OCT-08:62 216.00 250.05 679.57 0.00 0.00 0.00 0.00 0.57 0.00
November 1655.87 08-NOV-16:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.74 0.00
December 1614.58 16-DEC-09:02 324.00 318.25 979.84 0.00 0.00 0.00 0.00 0.00 90.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1614.58   216.00 156.28 276.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1734.56   583.20 318.25 979.84 0.00 0.00 0.00 0.00 53.23 90.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1525.41 31-JAN-09:02 216.00 250.02 679.49 0.00 0.00 0.00 0.00 0.00 70.24
February 1609.05 20-FEB-09:02 324.00 318.21 979.73 0.00 0.00 0.00 0.00 0.00 72.02
March 1629.92 21-MAR-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 10.88 0.00
April 1938.09 27-APR-08:51 288.00 333.36 905.99 0.00 0.00 0.00 0.00 0.00 27.56
May 1994.07 20-MAY-08:51 432.00 424.28 1306.30 0.00 0.00 0.00 0.00 6.66 0.00
June 2007.31 14-JUN-08:11 324.00 375.03 1019.23 0.00 0.00 0.00 0.00 13.54 0.00
July 1931.97 04-JUL-08:62 324.00 318.21 979.73 0.00 0.00 0.00 0.00 0.00 10.37
August 1986.97 28-AUG-08:51 288.00 333.36 905.99 0.00 0.00 0.00 0.00 0.00 2.92
September 1960.10 19-SEP-08:51 288.00 333.36 905.99 0.00 0.00 0.00 0.00 3.40 0.00
October 1868.38 05-OCT-08:51 288.00 333.36 905.99 0.00 0.00 0.00 0.00 0.00 2.62
November 1720.61 09-NOV-09:51 252.00 291.69 792.74 0.00 0.00 0.00 0.00 0.00 31.89
December 1544.37 16-DEC-09:02 324.00 318.21 979.73 0.00 0.00 0.00 0.00 0.00 87.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1525.41   216.00 159.11 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2007.31   583.20 424.28 1306.30 0.00 0.00 0.00 0.00 13.54 87.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1482.75 01-JAN-11:35 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 0.00 60.12
February 1552.04 20-FEB-11:35 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 0.00 11.43
March 1604.17 16-MAR-18:10 10562.33 5952.60 0.00 0.00 0.00 0.00 0.00 0.00 19.28
April 1841.12 30-APR-10:35 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 8.58 0.00
May 1944.53 20-MAY-18:00 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 56.19 0.00
June 2208.91 16-JUN-21:10 2263.36 744.08 0.00 0.00 0.00 0.00 0.00 58.96 0.00
July 2036.57 26-JUL-18:10 7041.55 3968.40 0.00 0.00 0.00 0.00 0.00 68.85 0.00
August 2051.41 07-AUG-21:10 2263.36 744.08 0.00 0.00 0.00 0.00 0.00 50.44 0.00
September 1991.67 23-SEP-10:35 1508.90 620.06 0.00 0.00 0.00 0.00 0.00 25.52 0.00
October 1916.84 05-OCT-10:35 1005.94 620.06 0.00 0.00 0.00 0.00 0.00 30.02 0.00
November 1677.99 10-NOV-11:35 1005.94 620.06 0.00 0.00 0.00 0.00 0.00 0.00 12.83
December 1411.74 10-DEC-11:35 1508.90 744.08 0.00 0.00 0.00 0.00 0.00 0.00 41.46
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1411.74   1005.94 620.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2208.91   10562.33 5952.60 0.00 0.00 0.00 0.00 0.00 68.85 60.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1923.09 12-JAN-16:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 26.11
February 1997.86 20-FEB-16:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 0.00 0.53
March 1997.19 14-MAR-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 6.17 0.00
April 2024.34 15-APR-15:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 24.02 0.00
May 2031.82 17-MAY-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 36.57 0.00
June 2053.20 15-JUN-18:03 554.40 337.19 484.65 0.00 0.00 0.00 0.00 72.14 0.00
July 2014.82 31-JUL-18:02 693.00 421.49 605.82 0.00 0.00 0.00 0.00 57.96 0.00
August 2011.40 28-AUG-18:02 693.00 421.49 605.82 0.00 0.00 0.00 0.00 35.06 0.00
September 2035.97 06-SEP-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 29.29 0.00
October 2014.48 03-OCT-15:12 486.00 132.60 250.23 0.00 0.00 0.00 0.00 45.90 0.00
November 1974.92 07-NOV-16:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 9.64
December 1900.13 16-DEC-16:12 324.00 187.54 331.88 0.00 0.00 0.00 0.00 0.00 51.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1900.13   324.00 132.60 250.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2053.20   693.00 421.49 605.82 0.00 0.00 0.00 0.00 72.14 51.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1785.46 30-JAN-16:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 0.00 40.23
February 1815.10 24-FEB-16:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 0.00 60.49
March 1942.92 14-MAR-15:12 583.20 159.11 300.24 0.00 0.00 0.00 0.00 6.97 0.00
April 2159.72 06-APR-18:11 1386.00 842.88 1211.49 0.00 0.00 0.00 0.00 0.00 61.18
May 2098.21 20-MAY-08:51 432.00 424.28 1306.30 0.00 0.00 0.00 0.00 15.80 0.00
June 2193.89 19-JUN-18:51 1247.40 758.59 1090.34 0.00 0.00 0.00 0.00 11.98 0.00
July 2009.09 23-JUL-15:13 216.00 125.01 221.23 0.00 0.00 0.00 0.00 48.15 0.00
August 2083.42 26-AUG-08:11 432.00 424.28 1306.30 0.00 0.00 0.00 0.00 19.08 0.00
September 1996.53 01-SEP-18:02 693.00 421.44 605.75 0.00 0.00 0.00 0.00 46.49 0.00
October 1978.35 04-OCT-15:12 486.00 132.59 250.20 0.00 0.00 0.00 0.00 41.42 0.00
November 1859.18 12-NOV-16:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 0.00 49.12
December 1810.90 16-DEC-16:12 324.00 187.52 331.84 0.00 0.00 0.00 0.00 0.00 49.30
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1785.46   216.00 125.01 221.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2193.89   1386.00 842.88 1306.30 0.00 0.00 0.00 0.00 48.15 61.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1045.43 03-JAN-16:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 0.00 8.32
February 1074.08 20-FEB-16:12 324.00 117.89 325.16 0.00 0.00 0.00 0.00 0.00 0.49
March 1075.28 14-MAR-15:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 2.91 0.00
April 1068.16 15-APR-15:12 324.00 117.89 325.16 0.00 0.00 0.00 0.00 12.47 0.00
May 1061.01 17-MAY-15:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 19.11 0.00
June 1061.17 01-JUN-15:12 486.00 83.36 245.16 0.00 0.00 0.00 0.00 39.16 0.00
July 1054.12 21-JUL-15:12 486.00 83.36 245.16 0.00 0.00 0.00 0.00 22.11 0.00
August 1076.73 21-AUG-15:12 486.00 83.36 245.16 0.00 0.00 0.00 0.00 27.60 0.00
September 1079.58 05-SEP-15:12 486.00 83.36 245.16 0.00 0.00 0.00 0.00 23.72 0.00
October 1079.21 31-OCT-15:12 486.00 83.36 245.16 0.00 0.00 0.00 0.00 0.00 5.03
November 1069.79 07-NOV-16:12 583.20 100.03 294.19 0.00 0.00 0.00 0.00 0.00 5.30
December 1035.79 16-DEC-16:12 324.00 117.89 325.16 0.00 0.00 0.00 0.00 0.00 27.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1035.79   324.00 83.36 245.16 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1079.58   583.20 117.89 325.16 0.00 0.00 0.00 0.00 39.16 27.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16537.66 03-JAN-24:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 0.00 177.89
February 18251.84 22-FEB-22:06 134943.84 4743.38 33739.51 0.00 0.00 0.00 0.00 0.00 143.84
March 18602.81 15-MAR-21:54 134943.84 4743.38 33739.51 0.00 0.00 0.00 0.00 0.00 68.63
April 20433.85 19-APR-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 44.24 0.00
May 21422.15 31-MAY-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 45.77 0.00
June 22061.35 16-JUN-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 98.98 0.00
July 21808.96 25-JUL-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 83.98 0.00
August 21938.10 07-AUG-21:40 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 82.40 0.00
September 20896.57 22-SEP-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 12.99 0.00
October 20299.86 05-OCT-21:52 215910.14 7589.41 53983.22 0.00 0.00 0.00 0.00 0.00 18.97
November 18504.90 09-NOV-22:54 134943.84 4743.38 33739.51 0.00 0.00 0.00 0.00 0.00 109.14
December 16385.08 15-DEC-24:00 26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 0.00 161.86
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16385.08   26988.77 474.34 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22061.35   215910.14 7589.41 53983.22 0.00 0.00 0.00 0.00 98.98 177.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18260.79 03-JAN-22:10 53977.54 1897.35 13495.81 0.00 0.00 0.00 0.00 0.00 174.44
February 19216.77 07-FEB-23:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 0.00 125.17
March 20087.96 15-MAR-21:54 134943.84 4743.38 33739.51 0.00 0.00 0.00 0.00 0.00 68.63
April 21827.26 19-APR-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 44.23 0.00
May 22757.76 31-MAY-21:50 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 48.12 0.00
June 23389.88 15-JUN-21:10 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 118.64 0.00
July 23189.17 26-JUL-21:30 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 56.43 0.00
August 23329.09 07-AUG-21:30 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 88.59 0.00
September 22185.73 22-SEP-22:00 26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 12.98 0.00
October 21596.18 05-OCT-21:52 215910.14 7589.41 53983.22 0.00 0.00 0.00 0.00 0.00 18.97
November 19873.16 09-NOV-22:54 134943.84 4743.38 33739.51 0.00 0.00 0.00 0.00 0.00 109.14
December 18232.33 15-DEC-22:10 53977.54 1897.35 13495.81 0.00 0.00 0.00 0.00 0.00 145.88
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18232.33   26988.77 948.68 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23389.88   215910.14 7589.41 53983.22 0.00 0.00 0.00 0.00 118.64 174.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26323.96 01-JAN-11:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 0.00 134.11
February 27235.03 20-FEB-11:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 0.00 44.19
March 27418.74 19-MAR-10:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 0.00 66.08
April 28797.72 30-APR-10:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 5.75 0.00
May 28947.46 21-MAY-10:40 1601.14 498.27 29209.11 37488.05 0.00 0.00 0.00 68.27 0.00
June 29460.55 18-JUN-10:40 1601.14 498.27 29209.11 37488.05 0.00 0.00 0.00 105.48 0.00
July 29605.88 02-JUL-10:40 1601.14 498.27 29209.11 37488.05 0.00 0.00 0.00 102.69 0.00
August 29494.63 06-AUG-10:40 1601.14 498.27 29209.11 37488.05 0.00 0.00 0.00 95.98 0.00
September 29116.26 17-SEP-10:40 1601.14 498.27 29209.11 37488.05 0.00 0.00 0.00 68.48 0.00
October 28618.82 01-OCT-10:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 40.22 0.00
November 27024.06 10-NOV-11:50 533.71 207.61 14604.56 18744.03 0.00 0.00 0.00 0.00 40.07
December 26285.41 10-DEC-11:50 800.57 249.14 14604.56 18744.03 0.00 0.00 0.00 0.00 103.26
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 26285.41   533.71 207.61 14604.56 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29605.88   1601.14 498.27 29209.11 37488.05 0.00 0.00 0.00 105.48 134.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1780.13 01-JAN-11:50 798.48 393.74 0.00 0.00 0.00 0.00 0.00 0.00 117.29
February 1941.62 20-FEB-11:50 798.48 393.74 0.00 0.00 0.00 0.00 0.00 0.00 35.46
March 2411.45 16-MAR-15:13 7984.80 1968.72 0.00 0.00 0.00 0.00 0.00 0.00 18.99
April 4545.97 28-APR-15:10 1330.80 328.12 0.00 0.00 0.00 0.00 0.00 58.53 0.00
May 5216.34 30-MAY-15:10 1330.80 328.12 0.00 0.00 0.00 0.00 0.00 125.38 0.00
June 5726.41 17-JUN-17:20 1596.96 787.49 0.00 0.00 0.00 0.00 0.00 145.91 0.00
July 6030.83 03-JUL-15:10 1330.80 328.12 0.00 0.00 0.00 0.00 0.00 160.89 0.00
August 5928.26 07-AUG-15:10 1330.80 328.12 0.00 0.00 0.00 0.00 0.00 137.67 0.00
September 5648.95 02-SEP-13:40 798.48 328.12 0.00 0.00 0.00 0.00 0.00 95.10 0.00
October 5233.67 03-OCT-13:40 532.32 328.12 0.00 0.00 0.00 0.00 0.00 98.18 0.00
November 2980.40 10-NOV-12:20 532.32 328.12 0.00 0.00 0.00 0.00 0.00 0.00 55.11
December 1711.96 16-DEC-11:50 798.48 328.12 0.00 0.00 0.00 0.00 0.00 0.00 128.66
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1711.96   532.32 328.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6030.83   7984.80 1968.72 0.00 0.00 0.00 0.00 0.00 160.89 128.66



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.305494E+12 206954.81 03-JAN-20:40 0.444840E+12 347502.12 26-JAN-18:00
February 0.288754E+12 223487.72 06-FEB-20:10 0.383041E+12 345364.88 01-FEB-21:00
March 0.332297E+12 235108.73 15-MAR-19:10 0.400373E+12 351259.55 01-MAR-21:49
April 0.386694E+12 291298.47 19-APR-19:10 0.353535E+12 311375.56 03-APR-17:49
May 0.460069E+12 310574.56 19-MAY-19:10 0.351084E+12 309634.23 02-MAY-17:10
June 0.503344E+12 331821.79 05-JUN-19:10 0.330633E+12 286414.57 08-JUN-17:40
July 0.546044E+12 332219.46 25-JUL-19:10 0.335911E+12 283873.11 03-JUL-17:10
August 0.514056E+12 328411.55 04-AUG-19:19 0.336208E+12 284029.22 31-AUG-17:19
September 0.464652E+12 309293.54 22-SEP-19:10 0.330478E+12 286288.36 29-SEP-17:19
October 0.397579E+12 305838.05 04-OCT-19:10 0.351345E+12 309693.39 31-OCT-17:40
November 0.317705E+12 238213.64 09-NOV-20:19 0.388131E+12 356857.96 27-NOV-22:00
December 0.303908E+12 201475.92 15-DEC-20:19 0.462526E+12 403686.12 26-DEC-19:10
             
Annual Sum or Average 0.482060E+13     0.446811E+13    
Minimum of Months 0.288754E+12 201475.92   0.330478E+12 283873.11  
Maximum of Months 0.546044E+12 332219.46   0.462526E+12 403686.12  



Table of Contents

Report: EnergyConsumptionElectricityGeneratedPropaneMonthly

For: Meter

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ELECTRICITYPRODUCED:FACILITY [J] ELECTRICITYPRODUCED:FACILITY {Maximum} [W] ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} PROPANE:FACILITY [] PROPANE:FACILITY []
January 0.130236E+11 24913.74 27-JAN-12:30 0.00 0.00
February 0.147651E+11 29257.37 24-FEB-11:39 0.00 0.00
March 0.219654E+11 34279.26 29-MAR-12:20 0.00 0.00
April 0.252990E+11 34554.33 22-APR-12:09 0.00 0.00
May 0.280163E+11 34554.33 05-MAY-11:50 0.00 0.00
June 0.277746E+11 33542.47 10-JUN-11:00 0.00 0.00
July 0.250354E+11 32140.55 22-JUL-11:00 0.00 0.00
August 0.234817E+11 31526.05 09-AUG-12:30 0.00 0.00
September 0.212047E+11 31630.48 09-SEP-12:30 0.00 0.00
October 0.173522E+11 28609.68 05-OCT-11:30 0.00 0.00
November 0.139064E+11 25389.98 05-NOV-11:39 0.00 0.00
December 0.122584E+11 22118.64 29-DEC-11:00 0.00 0.00
           
Annual Sum or Average 0.244083E+12     0.00 0.00
Minimum of Months 0.122584E+11 22118.64   0.00 0.00
Maximum of Months 0.280163E+11 34554.33   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY [J]
January 0.389739E+11 0.147829E+11 0.140003E+12 0.331708E+11 0.453348E+11 0.535226E+10 0.00 0.133003E+11 0.00 0.00 0.316219E+10 0.770429E+10 0.00
February 0.350933E+11 0.126464E+11 0.126445E+12 0.299608E+11 0.415296E+11 0.530216E+10 0.00 0.246916E+11 0.00 0.00 0.277966E+10 0.696184E+10 0.00
March 0.387161E+11 0.129968E+11 0.140056E+12 0.331732E+11 0.465563E+11 0.616080E+10 0.00 0.402179E+11 0.00 0.00 0.301558E+10 0.770286E+10 0.00
April 0.372825E+11 0.115667E+11 0.135446E+12 0.321004E+11 0.495250E+11 0.624032E+10 0.00 0.967487E+11 0.00 0.00 0.673413E+10 0.746490E+10 0.00
May 0.384549E+11 0.110843E+11 0.140035E+12 0.331718E+11 0.561720E+11 0.676229E+10 0.00 0.151301E+12 0.00 0.00 0.116496E+11 0.770426E+10 0.00
June 0.371316E+11 0.102917E+11 0.135537E+12 0.321026E+11 0.596037E+11 0.684750E+10 0.00 0.195111E+12 0.00 0.00 0.156271E+11 0.745688E+10 0.00
July 0.383677E+11 0.108259E+11 0.139944E+12 0.331694E+11 0.607707E+11 0.719308E+10 0.00 0.227007E+12 0.00 0.00 0.172885E+11 0.771237E+10 0.00
August 0.385348E+11 0.115667E+11 0.140067E+12 0.331731E+11 0.602170E+11 0.705345E+10 0.00 0.197748E+12 0.00 0.00 0.142168E+11 0.770438E+10 0.00
September 0.374065E+11 0.121296E+11 0.135457E+12 0.321005E+11 0.573464E+11 0.667847E+10 0.00 0.162535E+12 0.00 0.00 0.988475E+10 0.746623E+10 0.00
October 0.388470E+11 0.135883E+11 0.139992E+12 0.331707E+11 0.541006E+11 0.646875E+10 0.00 0.952118E+11 0.00 0.00 0.475002E+10 0.770292E+10 0.00
November 0.376445E+11 0.140305E+11 0.135531E+12 0.321015E+11 0.472007E+11 0.545447E+10 0.00 0.323166E+11 0.00 0.00 0.239051E+10 0.744870E+10 0.00
December 0.389313E+11 0.150011E+11 0.139944E+12 0.331697E+11 0.456470E+11 0.536668E+10 0.00 0.106303E+11 0.00 0.00 0.380151E+10 0.771243E+10 0.00
                           
Annual Sum or Average 0.455384E+12 0.150511E+12 0.164846E+13 0.390565E+12 0.624004E+12 0.748802E+11 0.00 0.124682E+13 0.00 0.00 0.953004E+11 0.907420E+11 0.00
Minimum of Months 0.350933E+11 0.102917E+11 0.126445E+12 0.299608E+11 0.415296E+11 0.530216E+10 0.00 0.106303E+11 0.00 0.00 0.239051E+10 0.696184E+10 0.00
Maximum of Months 0.389739E+11 0.150011E+11 0.140067E+12 0.331732E+11 0.607707E+11 0.719308E+10 0.00 0.227007E+12 0.00 0.00 0.172885E+11 0.771243E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.683477E+11 0.00 0.224574E+12 0.00 0.00
February 0.137204E+12 0.00 0.430156E+11 0.00 0.202822E+12 0.00 0.00
March 0.152024E+12 0.00 0.290006E+11 0.00 0.219349E+12 0.00 0.00
April 0.146956E+12 0.00 0.343839E+10 0.00 0.203140E+12 0.00 0.00
May 0.151978E+12 0.00 29642066.52 0.00 0.199076E+12 0.00 0.00
June 0.147114E+12 0.00 3538120.67 0.00 0.183516E+12 0.00 0.00
July 0.151820E+12 0.00 1664027.43 0.00 0.184089E+12 0.00 0.00
August 0.152039E+12 0.00 5724472.44 0.00 0.184164E+12 0.00 0.00
September 0.146971E+12 0.00 8198655.21 0.00 0.183499E+12 0.00 0.00
October 0.151903E+12 0.00 0.410504E+09 0.00 0.199031E+12 0.00 0.00
November 0.147091E+12 0.00 0.379096E+11 0.00 0.203130E+12 0.00 0.00
December 0.151820E+12 0.00 0.915012E+11 0.00 0.219204E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.273672E+12 0.00 0.240559E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 1664027.43 0.00 0.183499E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.915012E+11 0.00 0.224574E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 37630.57 02-JAN-20:10 9571.94 01-JAN-00:10 88863.15 02-JAN-07:10 23858.54 02-JAN-07:19 25182.09 13-JAN-19:10 3308.14 27-JAN-09:09 0.00 01-JAN-00:10
February 37630.57 01-FEB-20:10 9571.94 01-FEB-00:10 88863.15 01-FEB-07:10 23858.54 01-FEB-07:19 28340.63 22-FEB-22:10 3247.45 01-FEB-07:10 0.00 01-FEB-00:10
March 37630.57 01-MAR-20:10 9571.94 01-MAR-00:10 88863.15 01-MAR-07:10 23858.54 13-MAR-06:19 29735.39 16-MAR-21:00 3135.02 02-MAR-09:20 0.00 01-MAR-00:10
April 37630.57 03-APR-19:10 9571.94 01-APR-00:10 88863.15 03-APR-06:10 23858.27 04-APR-06:19 35917.19 19-APR-21:19 3190.91 28-APR-18:10 0.00 01-APR-00:10
May 37630.57 01-MAY-19:10 9571.94 01-MAY-00:10 88863.15 01-MAY-06:10 23858.21 03-MAY-06:19 40802.55 31-MAY-21:19 3371.65 25-MAY-18:10 0.00 01-MAY-00:10
June 37630.57 01-JUN-19:10 9571.94 01-JUN-00:10 88863.15 01-JUN-06:10 23857.50 23-JUN-06:19 45375.96 16-JUN-21:19 3618.75 16-JUN-20:30 0.00 01-JUN-00:10
July 37630.57 03-JUL-19:19 9571.94 01-JUL-00:10 88863.15 03-JUL-06:10 23857.74 19-JUL-06:19 43090.31 26-JUL-21:19 3390.26 21-JUL-20:00 0.00 01-JUL-00:10
August 37630.57 01-AUG-19:10 9571.94 01-AUG-00:10 88863.15 01-AUG-06:10 23858.27 14-AUG-06:19 47005.79 07-AUG-21:19 3388.71 22-AUG-20:10 0.00 01-AUG-00:10
September 37630.57 01-SEP-19:10 9571.94 01-SEP-00:10 88863.15 01-SEP-06:10 23858.48 28-SEP-06:19 43130.07 21-SEP-21:10 3566.90 18-SEP-18:10 0.00 01-SEP-00:10
October 37630.57 02-OCT-19:10 9571.94 01-OCT-00:10 88863.15 02-OCT-06:10 23858.54 02-OCT-06:19 41909.01 05-OCT-21:00 3352.48 01-OCT-18:10 0.00 01-OCT-00:10
November 37630.57 01-NOV-19:10 9571.94 01-NOV-00:10 88863.15 01-NOV-06:10 23858.54 01-NOV-06:19 35771.33 09-NOV-22:00 3125.07 17-NOV-06:19 0.00 01-NOV-00:10
December 37630.57 01-DEC-20:10 9571.94 01-DEC-00:10 88863.15 01-DEC-07:10 23858.54 11-DEC-07:19 25572.68 15-DEC-19:10 3344.83 07-DEC-07:19 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 37630.57   9571.94   88863.15   23857.50   25182.09   3125.07   0.00  
Maximum of Months 37630.57   9571.94   88863.15   23858.54   47005.79   3618.75   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY {Maximum} [W] COGENERATION:ELECTRICITY {TIMESTAMP}
January 45883.19 03-JAN-16:40 0.00 0.00 8265.52 05-JAN-05:19 4738.73 19-JAN-19:10 0.00 01-JAN-00:10
February 57475.88 20-FEB-16:19 0.00 0.00 8265.52 01-FEB-06:30 4738.49 02-FEB-19:10 0.00 01-FEB-00:10
March 67868.40 21-MAR-15:20 0.00 0.00 8265.52 02-MAR-01:49 4738.72 23-MAR-18:10 0.00 01-MAR-00:10
April 95778.41 19-APR-18:10 0.00 0.00 8265.52 01-APR-12:09 4738.61 20-APR-18:10 0.00 01-APR-00:10
May 111729.18 19-MAY-18:10 0.00 0.00 8265.52 08-MAY-08:00 4738.49 04-MAY-18:10 0.00 01-MAY-00:10
June 133869.77 14-JUN-18:10 0.00 0.00 8265.52 01-JUN-08:39 4738.50 29-JUN-18:10 0.00 01-JUN-00:10
July 133174.32 26-JUL-18:10 0.00 0.00 8265.52 04-JUL-08:30 4738.56 20-JUL-18:10 0.00 01-JUL-00:10
August 125492.75 04-AUG-18:10 0.00 0.00 8265.52 04-AUG-08:09 4738.58 24-AUG-18:10 0.00 01-AUG-00:10
September 111336.64 01-SEP-15:30 0.00 0.00 8265.52 19-SEP-08:00 4738.58 28-SEP-18:10 0.00 01-SEP-00:10
October 110255.02 04-OCT-18:10 0.00 0.00 8265.52 03-OCT-18:30 4738.45 26-OCT-18:10 0.00 01-OCT-00:10
November 62398.88 03-NOV-15:50 0.00 0.00 8265.52 03-NOV-15:30 4738.68 15-NOV-19:10 0.00 01-NOV-00:10
December 28330.68 23-DEC-14:00 0.00 0.00 8265.52 04-DEC-06:10 4738.60 07-DEC-19:10 0.00 01-DEC-00:10
                     
Annual Sum or Average     0.00 0.00            
Minimum of Months 28330.68   0.00 0.00 8265.52   4738.45   0.00  
Maximum of Months 133869.77   0.00 0.00 8265.52   4738.73   0.00  



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 206954.81 03-JAN-20:40 37630.57 86131.51 9571.94 19290.81 25143.17 2371.81 0.00 21674.27 0.00
February 223487.72 06-FEB-20:10 37630.57 86131.51 9571.94 19287.45 23574.44 2358.61 0.00 39214.38 0.00
March 235108.73 15-MAR-19:10 37630.57 86131.51 9571.94 19287.45 23721.33 2391.13 0.00 50645.75 0.00
April 291298.47 19-APR-19:10 37630.57 86131.51 9571.94 19287.45 31059.19 2686.25 0.00 91262.12 0.00
May 310574.56 19-MAY-19:10 37630.57 86131.51 9571.94 19287.45 34051.33 3272.93 0.00 107464.42 0.00
June 331821.79 05-JUN-19:10 37630.57 86131.51 9571.94 19286.86 33774.27 3558.95 0.00 127894.43 0.00
July 332219.46 25-JUL-19:10 37630.57 86131.51 9571.94 19286.82 35369.67 3070.08 0.00 127863.05 0.00
August 328411.55 04-AUG-19:19 37630.57 86131.51 9571.94 19290.81 37337.64 2997.63 0.00 121872.60 0.00
September 309293.54 22-SEP-19:10 37630.57 86131.51 9571.94 19287.45 36251.80 3035.49 0.00 104219.84 0.00
October 305838.05 04-OCT-19:10 37630.57 86131.51 9571.94 19287.45 33225.83 3015.27 0.00 103333.06 0.00
November 238213.64 09-NOV-20:19 37630.57 86131.51 9571.94 19290.81 27731.55 2399.79 0.00 49847.63 0.00
December 201475.92 15-DEC-20:19 37630.57 86131.51 9571.94 19290.81 24813.73 2342.97 0.00 16411.44 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 201475.92   37630.57 86131.51 9571.94 19286.82 23574.44 2342.97 0.00 16411.44 0.00
Maximum of Months 332219.46   37630.57 86131.51 9571.94 19290.81 37337.64 3558.95 0.00 127894.43 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 147273.44 28-JAN-07:40 0.00 210423.37 30-JAN-21:00 0.00
February 104248.32 01-FEB-18:10 0.00 150833.72 02-FEB-03:30 0.00 210408.01 06-FEB-21:00 0.00
March 104248.32 01-MAR-18:10 0.00 124817.36 02-MAR-01:39 0.00 209210.40 03-MAR-21:49 0.00
April 104248.32 01-APR-17:10 0.00 54945.45 12-APR-05:00 0.00 207552.46 06-APR-20:19 0.00
May 104248.32 01-MAY-17:10 0.00 4350.38 04-MAY-05:10 0.00 205385.91 02-MAY-17:10 0.00
June 104248.32 01-JUN-17:10 0.00 511.76 30-JUN-08:09 0.00 185702.83 01-JUN-18:00 0.00
July 104248.32 01-JUL-17:10 0.00 886.15 21-JUL-21:00 0.00 180026.18 03-JUL-20:19 0.00
August 104248.32 01-AUG-17:10 0.00 1132.30 17-AUG-08:09 0.00 180173.65 31-AUG-20:40 0.00
September 104248.32 01-SEP-17:10 0.00 1414.78 11-SEP-08:00 0.00 186762.06 30-SEP-21:00 0.00
October 104248.32 02-OCT-17:10 0.00 22534.18 25-OCT-02:00 0.00 205445.07 31-OCT-17:40 0.00
November 104248.32 01-NOV-17:10 0.00 125609.65 28-NOV-04:00 0.00 207853.31 30-NOV-21:49 0.00
December 104248.32 01-DEC-18:10 0.00 143273.21 26-DEC-09:09 0.00 209121.48 28-DEC-21:19 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 511.76   0.00 180026.18   0.00
Maximum of Months 104248.32   0.00 150833.72   0.00 210423.37   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.67 21.88 0.67 21.88
February 0.00 0.00 0.00 0.00 0.50 21.82 0.50 21.82
March 0.00 0.00 0.00 0.00 0.67 21.79 0.67 21.79
April 0.00 0.00 0.00 0.00 16.17 22.05 16.17 22.05
May 0.00 0.00 0.00 0.00 36.50 22.12 36.50 22.12
June 0.00 0.00 0.00 0.00 56.00 22.16 56.00 22.16
July 0.00 0.00 0.00 0.00 38.17 21.97 38.17 21.97
August 0.00 0.00 0.00 0.00 40.00 22.06 40.00 22.06
September 0.00 0.00 0.00 0.00 38.50 22.10 38.50 22.10
October 0.00 0.00 0.00 0.00 21.67 22.12 21.67 22.12
November 0.00 0.00 0.00 0.00 2.33 21.95 2.33 21.95
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   251.17 22.09 251.17 22.09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 56.00 22.16 56.00 22.16



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 15.00 22.03 15.00 22.03
May 0.00 0.00 0.00 0.00 41.50 22.14 41.50 22.14
June 0.00 0.00 0.00 0.00 65.17 22.19 65.17 22.19
July 0.00 0.00 0.00 0.00 45.83 21.99 45.83 21.99
August 0.00 0.00 0.00 0.00 42.00 22.02 42.00 22.02
September 0.00 0.00 0.00 0.00 29.83 22.00 29.83 22.00
October 0.00 0.00 0.00 0.00 6.17 21.96 6.17 21.96
November 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   245.67 22.08 245.67 22.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 65.17 22.19 65.17 22.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
April 0.00 0.00 0.00 0.00 8.50 21.81 8.50 21.81
May 0.00 0.00 0.00 0.00 19.17 21.87 19.17 21.87
June 0.00 0.00 0.00 0.00 32.17 21.92 32.17 21.92
July 0.00 0.00 0.00 0.00 24.67 21.88 24.67 21.88
August 0.00 0.00 0.00 0.00 16.83 21.86 16.83 21.86
September 0.00 0.00 0.00 0.00 14.33 21.84 14.33 21.84
October 0.00 0.00 0.00 0.00 6.00 21.82 6.00 21.82
November 0.00 0.00 0.00 0.00 0.17 21.80 0.17 21.80
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   122.17 21.88 122.17 21.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 32.17 21.92 32.17 21.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 21.74 0.50 21.74
February 0.00 0.00 0.00 0.00 1.50 21.81 1.50 21.81
March 0.00 0.00 0.00 0.00 0.67 21.74 0.67 21.74
April 0.00 0.00 0.00 0.00 11.67 21.91 11.67 21.91
May 0.00 0.00 0.00 0.00 30.00 21.98 30.00 21.98
June 0.00 0.00 0.00 0.00 56.83 22.01 56.83 22.01
July 0.00 0.00 0.00 0.00 36.17 21.96 36.17 21.96
August 0.00 0.00 0.00 0.00 32.00 21.95 32.00 21.95
September 0.00 0.00 0.00 0.00 30.83 21.94 30.83 21.94
October 0.00 0.00 0.00 0.00 14.00 21.89 14.00 21.89
November 0.00 0.00 0.00 0.00 3.67 21.86 3.67 21.86
December 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
                 
Annual Sum or Average 0.00   0.00   218.17 21.96 218.17 21.96
Minimum of Months 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
Maximum of Months 0.00 0.00 0.00 0.00 56.83 22.01 56.83 22.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
March 0.00 0.00 0.00 0.00 0.17 21.81 0.17 21.81
April 0.00 0.00 0.00 0.00 12.33 22.14 12.33 22.14
May 0.00 0.00 0.00 0.00 42.67 22.23 42.67 22.23
June 0.00 0.00 0.00 0.00 79.33 22.23 79.33 22.23
July 0.00 0.00 0.00 0.00 56.17 22.20 56.17 22.20
August 0.00 0.00 0.00 0.00 44.17 22.24 44.17 22.24
September 0.00 0.00 0.00 0.00 32.17 22.24 32.17 22.24
October 0.00 0.00 0.00 0.00 7.33 22.01 7.33 22.01
November 0.00 0.00 0.00 0.00 0.83 21.87 0.83 21.87
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   275.50 22.22 275.50 22.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 79.33 22.24 79.33 22.24



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.67 21.81 0.67 21.81
February 0.00 0.00 0.00 0.00 0.50 21.84 0.50 21.84
March 0.00 0.00 0.00 0.00 0.83 21.79 0.83 21.79
April 0.00 0.00 0.00 0.00 18.83 22.17 18.83 22.17
May 0.00 0.00 0.00 0.00 44.33 22.18 44.33 22.18
June 0.00 0.00 0.00 0.00 62.50 22.30 62.50 22.30
July 0.00 0.00 0.00 0.00 47.83 22.08 47.83 22.08
August 0.00 0.00 0.00 0.00 45.00 22.17 45.00 22.17
September 0.00 0.00 0.00 0.00 43.17 22.18 43.17 22.18
October 0.00 0.00 0.00 0.00 23.17 22.17 23.17 22.17
November 0.00 0.00 0.00 0.00 2.17 22.01 2.17 22.01
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   289.00 22.18 289.00 22.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 62.50 22.30 62.50 22.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 17.00 22.18 17.00 22.18
May 0.00 0.00 0.00 0.00 50.33 22.19 50.33 22.19
June 0.00 0.00 0.00 0.00 72.50 22.32 72.50 22.32
July 0.00 0.00 0.00 0.00 54.67 22.11 54.67 22.11
August 0.00 0.00 0.00 0.00 47.00 22.13 47.00 22.13
September 0.00 0.00 0.00 0.00 35.50 22.05 35.50 22.05
October 0.00 0.00 0.00 0.00 7.83 21.95 7.83 21.95
November 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   285.00 22.17 285.00 22.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 72.50 22.32 72.50 22.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.50 21.99 6.50 21.99
February 0.00 0.00 0.00 0.00 4.00 21.84 4.00 21.84
March 0.00 0.00 0.00 0.00 2.67 21.86 2.67 21.86
April 0.00 0.00 0.00 0.00 9.17 21.89 9.17 21.89
May 0.00 0.00 0.00 0.00 15.33 21.93 15.33 21.93
June 0.00 0.00 0.00 0.00 35.67 22.00 35.67 22.00
July 0.00 0.00 0.00 0.00 16.50 21.92 16.50 21.92
August 0.00 0.00 0.00 0.00 20.17 21.95 20.17 21.95
September 0.00 0.00 0.00 0.00 32.33 22.03 32.33 22.03
October 0.00 0.00 0.00 0.00 35.50 22.15 35.50 22.15
November 0.00 0.00 0.00 0.00 13.00 21.98 13.00 21.98
December 0.00 0.00 0.00 0.00 3.33 21.88 3.33 21.88
                 
Annual Sum or Average 0.00   0.00   194.17 22.00 194.17 22.00
Minimum of Months 0.00 0.00 0.00 0.00 2.67 21.84 2.67 21.84
Maximum of Months 0.00 0.00 0.00 0.00 35.67 22.15 35.67 22.15



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 23.31 0.00 23.31 0.00 23.31
February 672.00 22.31 0.00 22.31 0.00 22.31
March 744.00 21.53 9.33 21.53 9.33 21.52
April 720.00 21.66 0.00 21.66 0.00 21.66
May 744.00 21.99 11.33 21.99 11.33 21.99
June 720.00 22.32 82.83 22.34 82.83 22.36
July 667.00 23.26 412.00 23.35 386.50 23.38
August 301.67 23.88 508.50 23.90 271.17 23.91
September 242.67 23.99 493.67 23.96 231.50 23.97
October 179.83 23.94 287.17 23.95 60.83 23.96
November 538.67 23.94 15.67 23.94 0.00 23.94
December 702.50 23.85 0.00 23.85 0.00 23.85
             
Annual Sum or Average 6976.33 22.77 1820.50 22.97 1053.50 23.04
Minimum of Months 179.83 21.53 0.00 21.53 0.00 21.52
Maximum of Months 744.00 23.99 508.50 23.96 386.50 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 637.67 22.00 24.33 22.02 12.17 22.00
February 577.17 22.21 2.50 22.21 0.83 22.21
March 659.83 22.39 2.33 22.39 2.33 22.38
April 465.83 23.01 43.00 23.09 0.00 23.09
May 239.50 23.39 285.00 23.70 16.17 23.70
June 108.00 23.84 587.83 23.94 80.83 23.93
July 388.00 23.95 744.00 23.96 388.00 23.96
August 264.00 23.86 720.83 23.91 264.00 23.90
September 261.33 23.78 608.00 23.90 226.33 23.89
October 312.50 23.05 321.33 23.50 66.67 23.52
November 514.00 22.39 58.17 22.49 12.00 22.46
December 656.67 21.89 34.17 21.84 34.17 21.80
             
Annual Sum or Average 5084.50 22.70 3431.50 23.18 1103.50 23.24
Minimum of Months 108.00 21.89 2.33 21.84 0.00 21.80
Maximum of Months 659.83 23.95 744.00 23.96 388.00 23.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.21 0.00 22.21 0.00 22.21
February 672.00 22.34 0.00 22.34 0.00 22.34
March 744.00 22.46 0.00 22.46 0.00 22.46
April 656.83 22.98 1.67 22.98 0.00 22.98
May 473.67 23.20 121.17 23.33 20.83 23.34
June 309.83 23.45 336.83 23.68 94.50 23.71
July 415.17 23.80 596.50 23.80 398.83 23.81
August 339.83 23.66 534.33 23.75 283.83 23.76
September 342.67 23.62 427.33 23.71 248.83 23.73
October 518.67 23.14 141.83 23.26 75.83 23.30
November 698.17 22.70 0.00 22.70 0.00 22.70
December 744.00 22.10 0.00 22.10 0.00 22.10
             
Annual Sum or Average 6658.83 22.81 2159.67 23.06 1122.67 23.14
Minimum of Months 309.83 22.10 0.00 22.10 0.00 22.10
Maximum of Months 744.00 23.80 596.50 23.80 398.83 23.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 23.05 0.00 23.05 0.00 23.05
February 672.00 23.28 0.00 23.28 0.00 23.28
March 744.00 23.56 0.00 23.56 0.00 23.56
April 652.33 23.96 0.00 23.96 0.00 23.96
May 387.17 24.00 125.50 24.00 1.17 24.00
June 130.83 24.00 316.33 24.00 16.00 24.00
July 283.50 24.00 731.00 24.00 283.50 24.00
August 145.00 24.00 609.33 24.00 145.00 24.00
September 218.50 24.00 468.33 24.00 167.00 24.00
October 339.17 24.00 191.50 24.00 29.33 24.00
November 684.00 23.68 0.00 23.68 0.00 23.68
December 744.00 22.90 0.00 22.90 0.00 22.90
             
Annual Sum or Average 5744.50 23.55 2442.00 23.68 642.00 23.71
Minimum of Months 130.83 22.90 0.00 22.90 0.00 22.90
Maximum of Months 744.00 24.00 731.00 24.00 283.50 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.04 67.33 21.04 67.33 21.04
February 672.00 21.13 49.00 21.12 49.00 21.11
March 744.00 21.24 23.33 21.23 23.33 21.23
April 720.00 21.97 0.00 21.97 0.00 21.97
May 744.00 22.61 1.33 22.61 1.33 22.61
June 646.17 23.09 15.00 23.09 15.00 23.09
July 554.50 23.10 280.17 23.13 255.50 23.14
August 639.17 23.00 144.50 23.02 132.00 23.02
September 708.17 22.80 141.67 22.82 141.67 22.83
October 744.00 22.25 15.00 22.26 15.00 22.27
November 720.00 21.46 0.00 21.46 0.00 21.46
December 744.00 21.03 67.33 21.03 67.33 21.02
             
Annual Sum or Average 8380.00 22.02 804.67 22.07 767.50 22.10
Minimum of Months 554.50 21.03 0.00 21.03 0.00 21.02
Maximum of Months 744.00 23.10 280.17 23.13 255.50 23.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 175.50 24.00 744.00 24.00 175.50 24.00
February 156.33 24.00 672.00 24.00 156.33 24.00
March 174.33 24.00 744.00 24.00 174.33 24.00
April 224.50 24.00 720.00 24.00 224.50 24.00
May 376.00 24.00 744.00 24.00 376.00 24.00
June 528.17 24.00 720.00 24.00 528.17 24.00
July 739.83 24.00 744.00 24.00 739.83 24.00
August 685.33 24.00 744.00 24.00 685.33 24.00
September 608.00 24.00 720.00 24.00 608.00 24.00
October 410.17 24.00 744.00 24.00 410.17 24.00
November 187.50 24.00 720.00 24.00 187.50 24.00
December 156.00 24.00 744.00 24.00 156.00 24.00
             
Annual Sum or Average 4421.67 24.00 8760.00 24.00 4421.67 24.00
Minimum of Months 156.00 24.00 672.00 24.00 156.00 24.00
Maximum of Months 739.83 24.00 744.00 24.00 739.83 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 676.67 22.17 12.50 22.20 0.00 22.20
February 618.83 22.25 3.17 22.26 0.00 22.26
March 730.50 22.22 0.00 22.22 0.00 22.22
April 652.33 22.42 10.67 22.44 0.00 22.44
May 561.67 22.42 129.33 22.60 62.67 22.64
June 436.83 22.71 315.33 23.06 168.50 23.13
July 560.83 23.09 586.67 23.14 486.67 23.18
August 447.50 23.10 594.50 23.17 385.83 23.20
September 385.17 23.17 572.83 23.25 326.33 23.27
October 417.50 22.71 312.17 23.03 138.00 23.07
November 530.17 22.39 63.83 22.54 0.00 22.54
December 691.33 22.08 0.00 22.08 0.00 22.08
             
Annual Sum or Average 6709.33 22.50 2601.00 22.73 1568.00 22.81
Minimum of Months 385.17 22.08 0.00 22.08 0.00 22.08
Maximum of Months 730.50 23.17 594.50 23.25 486.67 23.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 730.83 22.81 0.00 22.81 0.00 22.81
February 658.83 22.88 0.00 22.88 0.00 22.88
March 730.00 22.89 0.83 22.89 0.00 22.89
April 566.83 23.06 30.17 23.11 0.00 23.11
May 421.83 23.12 194.50 23.35 67.17 23.39
June 362.00 23.41 390.17 23.64 173.17 23.68
July 533.17 23.74 638.33 23.72 518.67 23.73
August 421.00 23.71 608.67 23.71 404.50 23.72
September 384.00 23.69 548.67 23.72 342.33 23.73
October 355.83 23.30 283.67 23.49 154.17 23.53
November 589.33 23.06 14.83 23.08 0.00 23.08
December 743.50 22.76 0.00 22.76 0.00 22.76
             
Annual Sum or Average 6497.17 23.13 2709.83 23.31 1660.00 23.38
Minimum of Months 355.83 22.76 0.00 22.76 0.00 22.76
Maximum of Months 743.50 23.74 638.33 23.72 518.67 23.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.41 54.83 21.38 54.83 21.35
February 672.00 21.50 27.67 21.49 27.67 21.47
March 744.00 21.59 9.33 21.58 9.33 21.58
April 705.00 21.72 0.00 21.72 0.00 21.72
May 677.67 21.69 2.00 21.70 0.00 21.70
June 604.33 21.63 12.17 21.66 0.17 21.66
July 583.50 21.45 52.83 21.60 17.83 21.63
August 590.67 21.48 34.83 21.57 6.83 21.58
September 565.83 21.46 39.50 21.57 10.17 21.59
October 678.67 21.62 15.33 21.65 7.33 21.66
November 713.17 21.56 20.17 21.53 20.17 21.51
December 744.00 21.36 112.00 21.30 112.00 21.25
             
Annual Sum or Average 8022.83 21.54 380.67 21.55 266.33 21.54
Minimum of Months 565.83 21.36 0.00 21.30 0.00 21.25
Maximum of Months 744.00 21.72 112.00 21.72 112.00 21.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.06 198.67 21.00 198.67 20.95
February 672.00 21.32 122.83 21.24 122.83 21.19
March 738.33 21.65 32.33 21.62 32.33 21.58
April 693.17 21.94 5.50 21.97 0.00 21.97
May 650.17 21.93 11.00 21.96 1.83 21.97
June 550.17 21.74 46.83 21.91 8.17 21.93
July 560.33 21.72 121.67 22.04 74.50 22.19
August 580.83 21.77 80.83 21.99 51.83 22.09
September 581.83 21.91 83.50 22.09 69.67 22.21
October 676.17 21.94 38.17 22.02 25.67 22.05
November 717.83 21.45 49.50 21.40 49.50 21.36
December 744.00 20.97 351.33 20.90 351.33 20.86
             
Annual Sum or Average 7908.83 21.60 1142.17 21.61 986.33 21.59
Minimum of Months 550.17 20.97 5.50 20.90 0.00 20.86
Maximum of Months 744.00 21.94 351.33 22.09 351.33 22.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.16 90.00 21.14 90.00 21.12
February 672.00 21.29 58.83 21.26 58.83 21.23
March 744.00 21.49 6.17 21.49 6.17 21.48
April 720.00 21.80 0.00 21.80 0.00 21.80
May 744.00 21.96 0.00 21.96 0.00 21.96
June 715.17 22.00 0.50 22.00 0.50 22.00
July 739.50 21.99 64.50 22.09 64.50 22.17
August 741.83 21.98 31.17 22.03 31.17 22.07
September 720.00 22.01 48.83 22.07 48.83 22.12
October 744.00 21.85 10.67 21.86 10.67 21.88
November 720.00 21.32 10.33 21.31 10.33 21.31
December 744.00 21.11 127.00 21.08 127.00 21.05
             
Annual Sum or Average 8748.50 21.67 448.00 21.66 448.00 21.66
Minimum of Months 672.00 21.11 0.00 21.08 0.00 21.05
Maximum of Months 744.00 22.01 127.00 22.09 127.00 22.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.45 59.17 21.42 59.17 21.39
February 672.00 21.60 25.17 21.58 25.17 21.56
March 744.00 21.68 13.50 21.67 13.50 21.66
April 708.00 21.79 0.00 21.79 0.00 21.79
May 678.33 21.71 0.50 21.71 0.00 21.71
June 567.83 21.53 8.17 21.55 0.17 21.55
July 539.50 21.32 37.50 21.44 11.67 21.47
August 560.50 21.38 14.17 21.41 5.33 21.42
September 545.33 21.39 22.00 21.46 4.00 21.47
October 672.17 21.61 11.00 21.62 9.33 21.63
November 719.83 21.61 22.67 21.58 22.67 21.56
December 744.00 21.40 112.83 21.34 112.83 21.30
             
Annual Sum or Average 7895.50 21.55 326.67 21.55 263.83 21.54
Minimum of Months 539.50 21.32 0.00 21.34 0.00 21.30
Maximum of Months 744.00 21.79 112.83 21.79 112.83 21.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.05 204.00 21.00 204.00 20.98
February 672.00 21.36 110.50 21.30 110.50 21.26
March 744.00 21.71 40.67 21.67 40.67 21.64
April 691.83 22.02 11.50 22.08 0.00 22.08
May 605.17 21.87 46.50 22.13 2.83 22.15
June 504.00 21.68 80.83 22.11 12.50 22.18
July 525.00 21.77 130.50 22.23 73.00 22.46
August 527.50 21.72 106.00 22.14 54.50 22.30
September 561.50 22.01 97.33 22.35 70.00 22.53
October 709.00 21.99 38.00 22.04 30.33 22.06
November 718.67 21.42 63.67 21.37 63.67 21.33
December 744.00 20.97 362.50 20.92 362.50 20.89
             
Annual Sum or Average 7746.67 21.61 1292.00 21.70 1024.50 21.69
Minimum of Months 504.00 20.97 11.50 20.92 0.00 20.89
Maximum of Months 744.00 22.02 362.50 22.35 362.50 22.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.38 19.17 21.37 19.17 21.36
February 672.00 21.63 0.00 21.63 0.00 21.63
March 744.00 21.89 0.00 21.89 0.00 21.89
April 720.00 22.62 0.00 22.62 0.00 22.62
May 716.50 23.19 34.33 23.19 34.33 23.20
June 413.83 23.63 167.50 23.66 121.67 23.66
July 525.67 23.59 552.00 23.61 492.67 23.61
August 526.67 23.49 398.50 23.53 358.17 23.53
September 572.50 23.44 323.17 23.47 310.50 23.48
October 726.50 22.88 95.83 22.90 95.83 22.92
November 720.00 22.09 0.00 22.09 0.00 22.09
December 744.00 21.21 18.83 21.20 18.83 21.20
             
Annual Sum or Average 7825.67 22.48 1609.33 22.65 1451.17 22.76
Minimum of Months 413.83 21.21 0.00 21.20 0.00 21.20
Maximum of Months 744.00 23.63 552.00 23.66 492.67 23.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.30 159.33 21.21 159.33 21.15
February 672.00 21.42 127.83 21.36 127.83 21.31
March 744.00 21.53 74.50 21.48 74.50 21.44
April 687.50 21.66 11.00 21.66 10.17 21.65
May 644.50 21.62 10.67 21.65 0.83 21.65
June 549.17 21.51 49.50 21.66 2.00 21.66
July 543.67 21.39 113.33 21.68 27.50 21.71
August 555.00 21.40 98.50 21.64 23.33 21.66
September 541.33 21.40 108.50 21.66 30.00 21.69
October 660.50 21.55 52.83 21.61 32.33 21.62
November 712.33 21.48 100.67 21.40 100.67 21.34
December 744.00 21.25 273.00 21.15 273.00 21.10
             
Annual Sum or Average 7798.00 21.46 1179.67 21.49 861.50 21.45
Minimum of Months 541.33 21.25 10.67 21.15 0.83 21.10
Maximum of Months 744.00 21.66 273.00 21.68 273.00 21.71



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.91 386.83 20.82 386.83 20.78
February 672.00 21.20 275.50 21.09 275.50 21.03
March 734.00 21.56 116.83 21.47 116.33 21.40
April 681.67 21.89 18.33 21.92 11.50 21.91
May 621.83 21.86 22.83 21.92 4.83 21.93
June 504.33 21.65 83.83 21.92 11.33 21.94
July 527.83 21.67 171.83 22.09 80.50 22.22
August 546.50 21.70 130.50 22.00 64.83 22.11
September 558.33 21.82 132.17 22.06 82.67 22.15
October 663.17 21.86 81.33 21.97 57.33 22.00
November 717.00 21.33 190.33 21.22 189.33 21.15
December 744.00 20.83 562.00 20.78 562.00 20.75
             
Annual Sum or Average 7714.67 21.50 2172.33 21.49 1843.00 21.43
Minimum of Months 504.33 20.83 18.33 20.78 4.83 20.75
Maximum of Months 744.00 21.89 562.00 22.09 562.00 22.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 722.83 21.59 13.67 21.58 13.67 21.57
February 659.17 21.65 10.83 21.64 10.83 21.64
March 744.00 21.68 7.00 21.67 7.00 21.66
April 708.83 21.72 0.00 21.72 0.00 21.72
May 716.83 21.73 0.00 21.73 0.00 21.73
June 646.83 21.68 0.17 21.68 0.17 21.68
July 612.67 21.50 23.67 21.54 22.83 21.57
August 611.83 21.49 18.17 21.53 10.17 21.54
September 566.67 21.44 75.17 21.64 16.00 21.67
October 623.83 21.52 50.33 21.64 6.00 21.65
November 667.83 21.56 13.17 21.56 10.83 21.55
December 742.83 21.64 31.83 21.61 31.83 21.59
             
Annual Sum or Average 8024.17 21.61 244.00 21.63 129.33 21.63
Minimum of Months 566.67 21.44 0.00 21.53 0.00 21.54
Maximum of Months 744.00 21.73 75.17 21.73 31.83 21.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 715.67 22.39 0.00 22.39 0.00 22.39
February 615.33 22.51 4.83 22.52 0.00 22.52
March 655.33 22.66 9.17 22.67 0.00 22.67
April 406.50 22.72 77.67 22.90 0.00 22.90
May 236.33 22.95 319.00 23.37 68.00 23.40
June 219.50 23.58 527.00 23.62 172.00 23.66
July 500.83 23.72 725.17 23.59 499.67 23.62
August 403.67 23.65 667.33 23.56 396.67 23.59
September 400.67 23.38 547.83 23.46 328.83 23.50
October 423.17 22.79 272.33 23.11 141.83 23.18
November 618.50 22.52 27.00 22.57 0.00 22.57
December 734.17 22.33 0.00 22.33 0.00 22.33
             
Annual Sum or Average 5929.67 22.82 3177.33 23.08 1607.00 23.17
Minimum of Months 219.50 22.33 0.00 22.33 0.00 22.33
Maximum of Months 734.17 23.72 725.17 23.62 499.67 23.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 607.83 22.64 7.00 22.66 0.00 22.66
February 526.33 22.73 30.67 22.79 0.00 22.79
March 499.00 22.77 17.33 22.80 0.00 22.80
April 262.67 22.81 144.50 23.18 0.00 23.18
May 146.50 23.22 430.17 23.58 64.83 23.60
June 169.67 23.86 606.50 23.74 166.83 23.76
July 505.17 23.82 743.00 23.71 505.17 23.74
August 398.50 23.78 730.17 23.66 398.50 23.69
September 355.50 23.65 622.67 23.62 333.17 23.65
October 304.00 23.10 399.00 23.42 144.83 23.47
November 518.33 22.72 58.67 22.83 0.00 22.83
December 661.83 22.64 1.00 22.64 0.00 22.64
             
Annual Sum or Average 4955.33 23.05 3790.67 23.31 1613.33 23.39
Minimum of Months 146.50 22.64 1.00 22.64 0.00 22.64
Maximum of Months 661.83 23.86 743.00 23.74 505.17 23.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 503.50 23.99 744.00 23.99 503.50 23.99
February 461.33 23.99 672.00 23.99 461.33 23.99
March 514.67 23.99 744.00 23.99 514.67 23.99
April 513.67 23.99 720.00 23.99 513.67 23.99
May 555.83 23.99 744.00 23.99 555.83 23.99
June 605.83 23.99 720.00 23.99 605.83 23.99
July 742.00 23.99 744.00 23.99 742.00 23.99
August 688.33 23.99 744.00 23.99 688.33 23.99
September 648.67 23.99 720.00 23.99 648.67 23.99
October 574.33 23.99 744.00 23.99 574.33 23.99
November 503.50 23.99 720.00 23.99 503.50 23.99
December 493.83 23.99 743.83 23.99 493.83 23.99
             
Annual Sum or Average 6805.50 23.99 8759.83 23.99 6805.50 23.99
Minimum of Months 461.33 23.99 672.00 23.99 461.33 23.99
Maximum of Months 742.00 23.99 744.00 23.99 742.00 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.96 0.00 21.96 0.00 21.96
February 672.00 22.45 0.00 22.45 0.00 22.45
March 744.00 22.93 0.00 22.93 0.00 22.93
April 539.83 23.73 6.00 23.73 0.00 23.73
May 246.17 23.95 196.17 23.97 20.33 23.97
June 117.17 24.00 468.50 24.00 73.00 24.00
July 366.17 24.00 744.00 24.00 366.17 24.00
August 257.50 24.00 684.33 24.00 257.50 24.00
September 264.67 23.97 531.33 23.99 233.67 23.99
October 381.17 23.68 204.00 23.77 85.33 23.78
November 686.50 22.81 0.00 22.81 0.00 22.81
December 744.00 21.66 3.50 21.65 3.50 21.65
             
Annual Sum or Average 5763.17 22.92 2837.83 23.27 1039.50 23.35
Minimum of Months 117.17 21.66 0.00 21.65 0.00 21.65
Maximum of Months 744.00 24.00 744.00 24.00 366.17 24.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.30554 25.30342 0.05147 5.19176
February 672.00000 22.30810 23.42304 -0.2111 6.11474
March 744.00000 21.53240 23.01938 -0.4061 8.58321
April 720.00000 21.65743 27.37873 -0.3482 7.70914
May 744.00000 21.98866 38.96181 -1.3087 40.88824
June 720.00000 22.32194 48.41247 -1.1283 32.08991
July 744.00000 23.30631 59.07302 -0.7010 15.66058
August 744.00000 23.83124 54.24301 -0.5326 11.06626
September 720.00000 23.94933 50.27883 -0.4996 10.34017
October 744.00000 23.95941 40.79805 0.34631 7.63296
November 720.00000 23.94836 24.82004 0.22782 6.15835
December 744.00000 23.85890 21.92403 0.17476 5.71154
           
Annual Sum or Average 8760.00000 23.00327 36.56315 -0.3617 13.14222
Minimum of Months 672.00000 21.53240 21.92403 -1.3087 5.19176
Maximum of Months 744.00000 23.95941 59.07302 0.34631 40.88824



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.28265 26.39998 -0.1476 7.08925
February 672.00000 22.46304 23.21861 -0.1164 6.69341
March 744.00000 22.57319 21.92638 -0.0983 6.40039
April 720.00000 23.34436 24.92202 0.12884 6.27319
May 744.00000 23.75619 35.00928 -0.5929 13.23080
June 720.00000 23.95803 43.39953 -0.4258 8.99249
July 744.00000 23.96973 56.54013 -0.3273 7.30938
August 744.00000 23.92965 53.40122 -0.3607 7.94409
September 720.00000 23.90287 50.40692 -0.3785 8.51991
October 744.00000 23.56129 41.98556 0.33091 8.07118
November 720.00000 22.84519 26.54686 0.01889 6.85918
December 744.00000 22.13497 23.70458 -0.2083 7.51338
           
Annual Sum or Average 8760.00000 23.22991 35.71606 -0.1821 7.92074
Minimum of Months 672.00000 22.13497 21.92638 -0.5929 6.27319
Maximum of Months 744.00000 23.96973 56.54013 0.33091 13.23080



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.21394 26.79938 -0.1651 5.87656
February 672.00000 22.34200 23.61083 -0.1515 5.77334
March 744.00000 22.46231 22.33012 -0.1273 5.69133
April 720.00000 23.05484 25.83075 0.04928 5.50641
May 744.00000 23.42086 36.35583 -0.7305 16.91967
June 720.00000 23.64151 45.10197 -0.5813 12.54375
July 744.00000 23.66504 58.07196 -0.4840 10.21755
August 744.00000 23.64351 55.03882 -0.5136 10.86289
September 720.00000 23.63079 51.93126 -0.5399 11.51801
October 744.00000 23.31194 43.16658 0.23397 6.50797
November 720.00000 22.73023 27.14612 -0.0275 5.51367
December 744.00000 22.10269 24.11467 -0.2108 6.18551
           
Annual Sum or Average 8760.00000 23.02117 36.72220 -0.2716 8.61429
Minimum of Months 672.00000 22.10269 22.33012 -0.7305 5.50641
Maximum of Months 744.00000 23.66504 58.07196 0.23397 16.91967



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.99978 20.51389 0.80211 19.33690
February 672.00000 23.99977 17.72946 0.79630 19.11196
March 744.00000 23.99978 16.67307 0.80289 19.33123
April 720.00000 23.99997 20.58038 0.86502 21.61789
May 744.00000 24.00012 31.35834 0.34367 9.37244
June 720.00000 24.00022 40.43789 0.43887 10.74457
July 744.00000 24.00003 52.95683 0.52139 12.14056
August 744.00000 24.00027 50.00770 0.49532 11.70909
September 720.00000 24.00032 46.86678 0.46108 11.02845
October 744.00000 24.00026 37.47871 0.98102 26.04310
November 720.00000 24.00001 21.40700 0.83302 20.42017
December 744.00000 23.99988 18.00193 0.77865 18.53021
           
Annual Sum or Average 8760.00000 24.00004 31.26545 0.67592 16.60229
Minimum of Months 672.00000 23.99977 16.67307 0.34367 9.37244
Maximum of Months 744.00000 24.00032 52.95683 0.98102 26.04310



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.27349 29.09801 -0.0519 5.81703
February 672.00000 22.34296 25.98572 -0.0464 5.66255
March 744.00000 22.24050 24.87735 -0.0785 5.63880
April 720.00000 22.51327 28.90017 0.03602 5.60561
May 744.00000 22.66505 40.37065 -0.8180 20.06582
June 720.00000 22.92614 49.46260 -0.6382 14.54942
July 744.00000 22.95989 62.83436 -0.5356 11.82994
August 744.00000 23.03902 59.45521 -0.5281 11.65076
September 720.00000 23.19457 55.67644 -0.4896 10.77509
October 744.00000 23.02864 46.26968 0.30246 7.73741
November 720.00000 22.68787 29.63631 0.07808 6.25733
December 744.00000 22.16647 26.39128 -0.1014 5.94138
           
Annual Sum or Average 8760.00000 22.67075 40.01660 -0.2407 9.32408
Minimum of Months 672.00000 22.16647 24.87735 -0.8180 5.60561
Maximum of Months 744.00000 23.19457 62.83436 0.30246 20.06582



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.82518 28.86157 0.01175 5.36397
February 672.00000 22.89725 25.83478 0.01271 5.34614
March 744.00000 22.90909 24.70955 0.01038 5.41691
April 720.00000 23.24045 28.40307 0.12965 5.81000
May 744.00000 23.42205 39.00643 -0.6803 15.47847
June 720.00000 23.55108 47.72669 -0.5550 12.07941
July 744.00000 23.58669 60.64181 -0.4526 9.72797
August 744.00000 23.59633 57.54215 -0.4714 10.05977
September 720.00000 23.63596 54.33020 -0.4810 10.22567
October 744.00000 23.51279 45.28711 0.32408 7.51796
November 720.00000 23.19949 29.35972 0.12038 5.75211
December 744.00000 22.75657 26.23165 -0.0242 5.34711
           
Annual Sum or Average 8760.00000 23.26247 39.09220 -0.1725 8.19722
Minimum of Months 672.00000 22.75657 24.70955 -0.6803 5.34614
Maximum of Months 744.00000 23.63596 60.64181 0.32408 15.47847



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.40505 34.78079 -0.3816 8.67730
February 672.00000 21.50460 30.76230 -0.3602 8.39953
March 744.00000 21.58965 28.64684 -0.3240 7.94735
April 720.00000 21.75185 31.68783 -0.2098 6.94918
May 744.00000 21.83555 40.15543 -1.1799 35.71378
June 720.00000 21.89179 46.67569 -1.0775 31.01766
July 744.00000 21.85242 55.42148 -1.0458 29.62791
August 744.00000 21.84984 53.96974 -1.0660 30.54632
September 720.00000 21.84788 52.36023 -1.0798 31.30666
October 744.00000 21.77121 47.95086 -0.0990 6.16581
November 720.00000 21.57613 34.64433 -0.2944 7.78886
December 744.00000 21.35969 32.05096 -0.4239 9.34065
           
Annual Sum or Average 8760.00000 21.68692 40.83465 -0.6303 17.85110
Minimum of Months 672.00000 21.35969 28.64684 -1.1799 6.16581
Maximum of Months 744.00000 21.89179 55.42148 -0.0990 35.71378



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.06114 35.36289 -0.5005 10.53356
February 672.00000 21.31626 31.01491 -0.4435 9.63683
March 744.00000 21.67387 28.48618 -0.3388 8.24295
April 720.00000 22.02840 31.29712 -0.1709 6.79369
May 744.00000 22.12907 39.83955 -1.1018 32.27604
June 720.00000 22.15347 46.65495 -1.0002 27.93209
July 744.00000 22.11598 55.72412 -0.9673 26.65951
August 744.00000 22.12717 54.20290 -0.9955 27.70765
September 720.00000 22.20144 52.69986 -1.0073 28.19931
October 744.00000 22.12473 47.91273 -0.0604 6.16875
November 720.00000 21.45945 34.75304 -0.3678 8.58429
December 744.00000 20.97317 32.67809 -0.5526 11.63320
           
Annual Sum or Average 8760.00000 21.78219 40.96155 -0.6269 17.08215
Minimum of Months 672.00000 20.97317 28.48618 -1.1018 6.16875
Maximum of Months 744.00000 22.20144 55.72412 -0.0604 32.27604



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.15916 33.81721 -0.4683 9.69975
February 672.00000 21.29020 29.49948 -0.4504 9.40552
March 744.00000 21.49157 27.03192 -0.4012 8.56232
April 720.00000 21.80106 29.92201 -0.2839 7.23614
May 744.00000 21.96133 39.27658 -1.2690 39.46316
June 720.00000 22.01334 47.02764 -1.1774 35.13160
July 744.00000 22.00255 56.86276 -1.1233 32.77758
August 744.00000 21.98883 55.13042 -1.1541 34.06212
September 720.00000 22.01053 53.54319 -1.1763 35.04164
October 744.00000 21.84784 46.88370 -0.1764 6.14454
November 720.00000 21.32061 33.36783 -0.4157 8.80248
December 744.00000 21.11444 31.22498 -0.5012 10.34047
           
Annual Sum or Average 8760.00000 21.66857 40.38044 -0.7181 19.78701
Minimum of Months 672.00000 21.11444 27.03192 -1.2690 6.14454
Maximum of Months 744.00000 22.01334 56.86276 -0.1764 39.46316



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.45073 34.75639 -0.3748 8.56387
February 672.00000 21.59686 30.68285 -0.3326 8.11915
March 744.00000 21.67847 28.59412 -0.3006 7.79390
April 720.00000 21.81076 31.62912 -0.1878 6.85076
May 744.00000 21.85331 40.14816 -1.1661 35.07036
June 720.00000 21.90431 46.66884 -1.0642 30.46371
July 744.00000 21.86830 54.96510 -1.0355 29.22557
August 744.00000 21.85655 53.57453 -1.0590 30.24038
September 720.00000 21.85722 52.07829 -1.0747 31.07629
October 744.00000 21.77253 48.24931 -0.1027 6.20811
November 720.00000 21.61334 34.63598 -0.2886 7.74382
December 744.00000 21.39704 32.03520 -0.4147 9.15802
           
Annual Sum or Average 8760.00000 21.72182 40.74382 -0.6187 17.60394
Minimum of Months 672.00000 21.39704 28.59412 -1.1661 6.20811
Maximum of Months 744.00000 21.90431 54.96510 -0.1027 35.07036



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.04507 35.34231 -0.5059 10.53748
February 672.00000 21.35805 30.95545 -0.4253 9.24767
March 744.00000 21.70879 28.51218 -0.3266 7.94433
April 720.00000 22.12070 31.15547 -0.1427 6.72265
May 744.00000 22.29366 39.57044 -1.0468 30.93117
June 720.00000 22.29965 46.26971 -0.9492 27.03682
July 744.00000 22.24265 55.06449 -0.9246 26.01577
August 744.00000 22.25167 53.49457 -0.9551 27.04042
September 720.00000 22.34683 52.00311 -0.9637 27.50197
October 744.00000 22.06585 48.25713 -0.0769 6.10523
November 720.00000 21.42683 34.83922 -0.3766 8.57962
December 744.00000 20.96881 32.62790 -0.5509 11.58061
           
Annual Sum or Average 8760.00000 21.84580 40.74991 -0.6051 16.65472
Minimum of Months 672.00000 20.96881 28.51218 -1.0468 6.10523
Maximum of Months 744.00000 22.34683 55.06449 -0.0769 30.93117



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.29876 35.42674 -0.4367 9.74040
February 672.00000 21.42479 31.24477 -0.4053 9.27547
March 744.00000 21.53212 28.94357 -0.3584 8.61133
April 720.00000 21.73591 31.79744 -0.2192 7.28358
May 744.00000 21.84076 40.29076 -1.1754 35.81491
June 720.00000 21.91185 46.85464 -1.0569 30.48623
July 744.00000 21.86723 55.61354 -1.0264 29.11869
August 744.00000 21.85714 54.47336 -1.0524 30.28604
September 720.00000 21.84808 53.16101 -1.0764 31.53124
October 744.00000 21.74094 48.95716 -0.1134 6.41874
November 720.00000 21.49780 35.19601 -0.3403 8.60037
December 744.00000 21.25183 32.62639 -0.4814 10.55129
           
Annual Sum or Average 8760.00000 21.65139 41.29152 -0.6469 18.20148
Minimum of Months 672.00000 21.25183 28.94357 -1.1754 6.41874
Maximum of Months 744.00000 21.91185 55.61354 -0.1134 35.81491



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.90972 36.14304 -0.5678 12.12320
February 672.00000 21.20287 31.57810 -0.4982 10.87395
March 744.00000 21.60893 28.84573 -0.3749 9.01823
April 720.00000 22.01007 31.42444 -0.1789 7.13288
May 744.00000 22.10948 39.92452 -1.1022 32.56339
June 720.00000 22.15192 46.75245 -0.9844 27.56112
July 744.00000 22.11323 55.82987 -0.9515 26.25126
August 744.00000 22.10892 54.57885 -0.9882 27.64092
September 720.00000 22.15940 53.39789 -1.0152 28.74312
October 744.00000 22.08074 48.83601 -0.0776 6.42271
November 720.00000 21.33789 35.42182 -0.4272 9.73053
December 744.00000 20.82695 33.38013 -0.6202 13.37328
           
Annual Sum or Average 8760.00000 21.72043 41.41854 -0.6501 17.66763
Minimum of Months 672.00000 20.82695 28.84573 -1.1022 6.42271
Maximum of Months 744.00000 22.15940 55.82987 -0.0776 32.56339



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64186 35.99583 -0.2779 7.82227
February 672.00000 21.68482 31.88485 -0.2808 7.82288
March 744.00000 21.67688 29.55736 -0.2994 7.93532
April 720.00000 21.74419 32.93741 -0.2311 7.26869
May 744.00000 21.78997 41.68676 -1.2504 39.00681
June 720.00000 21.85104 47.94273 -1.1512 34.24875
July 744.00000 21.82265 56.02295 -1.1098 32.40677
August 744.00000 21.82117 54.66913 -1.1166 32.80451
September 720.00000 21.84067 53.27760 -1.1046 32.62047
October 744.00000 21.80753 48.23045 -0.0870 6.39284
November 720.00000 21.69121 35.64538 -0.2341 7.50579
December 744.00000 21.64596 33.48082 -0.3008 8.12188
           
Annual Sum or Average 8760.00000 21.75171 41.85154 -0.6225 18.73303
Minimum of Months 672.00000 21.64186 29.55736 -1.2504 6.39284
Maximum of Months 744.00000 21.85104 56.02295 -0.0870 39.00681



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.45004 28.94933 -0.0415 5.68503
February 672.00000 22.61199 25.74489 -0.0074 5.63403
March 744.00000 22.79599 24.46481 0.04703 5.61518
April 720.00000 23.16062 28.21171 0.19765 6.33458
May 744.00000 23.35209 39.03189 -0.5606 12.37961
June 720.00000 23.46968 47.95353 -0.4260 9.42793
July 744.00000 23.46449 60.91406 -0.3432 7.95699
August 744.00000 23.40954 58.13444 -0.3944 8.84096
September 720.00000 23.31473 55.25015 -0.4681 10.33875
October 744.00000 23.08984 46.05296 0.29245 7.41273
November 720.00000 22.68984 29.66362 0.04373 5.69711
December 744.00000 22.34837 26.31299 -0.0927 5.77346
           
Annual Sum or Average 8760.00000 23.01480 39.32302 -0.1470 7.60353
Minimum of Months 672.00000 22.34837 24.46481 -0.5606 5.61518
Maximum of Months 744.00000 23.46968 60.91406 0.29245 12.37961



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.84096 28.47849 0.07914 5.71683
February 672.00000 22.97118 25.37028 0.10355 5.77693
March 744.00000 23.12233 24.12403 0.14815 5.93374
April 720.00000 23.39246 27.80371 0.27296 6.97322
May 744.00000 23.53587 38.48055 -0.4701 10.24537
June 720.00000 23.63585 47.35190 -0.3409 7.88194
July 744.00000 23.63472 60.17792 -0.2570 6.69863
August 744.00000 23.57958 57.41935 -0.3086 7.39203
September 720.00000 23.50244 54.54716 -0.3773 8.53710
October 744.00000 23.32530 45.43663 0.36749 8.35067
November 720.00000 23.00983 29.24789 0.14264 5.98698
December 744.00000 22.76534 25.90013 0.03576 5.57816
           
Annual Sum or Average 8760.00000 23.27764 38.79293 -0.0513 7.09729
Minimum of Months 672.00000 22.76534 24.12403 -0.4701 5.57816
Maximum of Months 744.00000 23.63585 60.17792 0.36749 10.24537



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.99032 27.40011 0.99767 27.43534
February 672.00000 23.99022 24.58329 1.00051 27.53321
March 744.00000 23.99011 23.47616 1.01528 28.19816
April 720.00000 23.99041 27.21688 1.09276 31.76520
May 744.00000 23.99112 37.64962 0.65775 17.96146
June 720.00000 23.99202 46.38745 0.76101 20.51921
July 744.00000 23.99231 58.60339 0.83955 22.85452
August 744.00000 23.99243 55.75861 0.80470 21.80748
September 720.00000 23.99216 52.75828 0.76362 20.65096
October 744.00000 23.99130 43.69744 1.19340 36.14153
November 720.00000 23.99046 28.20064 1.03147 28.90868
December 744.00000 23.99031 25.02109 0.97119 26.34532
           
Annual Sum or Average 8760.00000 23.99110 37.65761 0.92697 25.83372
Minimum of Months 672.00000 23.99011 23.47616 0.65775 17.96146
Maximum of Months 744.00000 23.99243 58.60339 1.19340 36.14153



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.04127 25.11905 -0.4770 9.83145
February 672.00000 21.12937 21.72057 -0.4716 9.74501
March 744.00000 21.24155 20.37025 -0.4472 9.28633
April 720.00000 21.96709 23.85449 -0.2453 6.55401
May 744.00000 22.60691 34.45251 -1.0558 28.95029
June 720.00000 23.12774 43.09877 -0.8176 19.30905
July 744.00000 23.17316 56.80538 -0.7104 15.71843
August 744.00000 23.05257 53.75946 -0.7736 17.78778
September 720.00000 22.80686 51.22728 -0.8749 21.46531
October 744.00000 22.24676 42.38726 -0.0588 5.39052
November 720.00000 21.45839 25.54361 -0.3618 7.99927
December 744.00000 21.02939 22.11185 -0.5016 10.29952
           
Annual Sum or Average 8760.00000 22.07826 35.13720 -0.5670 13.55585
Minimum of Months 672.00000 21.02939 20.37025 -1.0558 5.39052
Maximum of Months 744.00000 23.17316 56.80538 -0.0588 28.95029



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.37781 28.95016 -0.4052 8.55265
February 672.00000 21.62567 25.47308 -0.3643 7.88849
March 744.00000 21.89409 24.05037 -0.3072 7.09894
April 720.00000 22.61842 27.48381 -0.1092 5.46978
May 744.00000 23.19980 37.85586 -0.8949 22.34407
June 720.00000 23.68578 46.41951 -0.6668 14.53295
July 744.00000 23.60128 59.86440 -0.6059 12.77615
August 744.00000 23.54350 56.82486 -0.6474 13.98378
September 720.00000 23.46878 53.87364 -0.6919 15.28860
October 744.00000 22.89185 45.36382 0.07509 5.37124
November 720.00000 22.09401 29.06075 -0.2273 6.40816
December 744.00000 21.20708 26.17967 -0.4642 9.54855
           
Annual Sum or Average 8760.00000 22.60468 38.54833 -0.4433 10.79945
Minimum of Months 672.00000 21.20708 24.05037 -0.8949 5.37124
Maximum of Months 744.00000 23.68578 59.86440 0.07509 22.34407



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.95652 28.03568 -0.2698 6.82054
February 672.00000 22.44913 24.48516 -0.1709 6.02806
March 744.00000 22.92658 22.95615 -0.0628 5.50099
April 720.00000 23.79642 25.31123 0.18070 5.98106
May 744.00000 23.98115 34.80350 -0.5950 12.66968
June 720.00000 23.99975 43.04591 -0.4986 10.32493
July 744.00000 23.99972 55.89550 -0.4101 8.51508
August 744.00000 23.99859 53.00579 -0.4397 9.07978
September 720.00000 23.98331 50.47430 -0.4763 9.91598
October 744.00000 23.80904 42.49684 0.30351 7.14456
November 720.00000 22.86221 27.91598 -0.0460 5.86101
December 744.00000 21.65654 25.51664 -0.3609 7.93708
           
Annual Sum or Average 8760.00000 23.28767 36.25211 -0.2380 7.99719
Minimum of Months 672.00000 21.65654 22.95615 -0.5950 5.50099
Maximum of Months 744.00000 23.99975 55.89550 0.30351 12.66968



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.05390 30.30286 -0.0284 5.25137
February 672.00000 23.27688 26.43933 -0.0031 5.25245
March 744.00000 23.56013 24.84516 0.05299 5.23721
April 720.00000 23.96661 23.13210 0.16383 5.67635
May 744.00000 23.99996 32.04607 -0.6539 14.16894
June 720.00000 23.99997 41.04355 -0.5592 11.67584
July 744.00000 23.99991 54.46289 -0.4622 9.47200
August 744.00000 23.99994 51.10523 -0.4932 10.12123
September 720.00000 23.99993 48.24922 -0.5255 10.90825
October 744.00000 23.99993 39.75977 0.30242 7.03616
November 720.00000 23.69471 27.99970 0.11731 5.51854
December 744.00000 22.89541 27.67356 -0.0816 5.41930
           
Annual Sum or Average 8760.00000 23.70513 35.66877 -0.1821 7.99543
Minimum of Months 672.00000 22.89541 23.13210 -0.6539 5.23721
Maximum of Months 744.00000 23.99997 54.46289 0.30242 14.16894



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.133003E+11 46614.17 03-JAN-16:13 556.91 0.424323E+11 0.00 0.557326E+11 2.43 3.27 04-JAN-20:40 0.00 0.00
February 0.246916E+11 57896.23 20-FEB-16:15 583.04 0.767454E+11 0.00 0.101437E+12 2.78 3.41 20-FEB-16:15 0.00 0.00
March 0.402179E+11 75114.56 14-MAR-15:12 704.81 0.124416E+12 0.00 0.164634E+12 3.01 3.77 14-MAR-15:12 0.00 0.00
April 0.967487E+11 98235.80 21-APR-15:15 719.08 0.308459E+12 0.00 0.405207E+12 3.16 4.16 28-APR-21:51 0.00 0.00
May 0.151301E+12 112535.30 19-MAY-18:05 744.00 0.485047E+12 0.00 0.636348E+12 3.17 3.95 17-MAY-21:51 0.00 0.00
June 0.195111E+12 134946.53 14-JUN-18:05 720.00 0.615029E+12 0.00 0.810140E+12 3.16 3.96 22-JUN-20:40 0.00 0.00
July 0.227007E+12 133939.77 26-JUL-18:05 744.00 0.780599E+12 0.00 0.100761E+13 3.45 4.60 18-JUL-21:51 0.00 0.00
August 0.197748E+12 126605.13 04-AUG-18:04 744.00 0.658987E+12 0.00 0.856735E+12 3.32 4.30 01-AUG-21:51 0.00 0.00
September 0.162535E+12 112598.79 01-SEP-15:14 720.00 0.558535E+12 0.00 0.721069E+12 3.39 4.50 03-SEP-21:51 0.00 0.00
October 0.952118E+11 112768.20 04-OCT-18:03 744.00 0.313712E+12 0.00 0.408924E+12 3.24 4.47 03-OCT-21:52 0.00 0.00
November 0.323166E+11 62398.88 03-NOV-15:50 606.27 0.101158E+12 0.00 0.133475E+12 2.69 3.68 09-NOV-09:51 0.00 0.00
December 0.106303E+11 35639.59 15-DEC-19:02 532.66 0.341983E+11 0.00 0.448286E+11 2.33 3.27 01-DEC-00:20 0.00 0.00
                         
Annual Sum or Average 0.124682E+13     8118.78 0.409932E+13 0.00 0.534614E+13 3.01     0.00 0.00
Minimum of Months 0.106303E+11 35639.59   532.66 0.341983E+11 0.00 0.448286E+11 2.33 3.27   0.00 0.00
Maximum of Months 0.227007E+12 134946.53   744.00 0.780599E+12 0.00 0.100761E+13 3.45 4.60   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.598076E+11 0.00 599.67 128252.46 28-JAN-07:40 0.00 44.75 57.50 0.30 0.00 0.06 0.36 28-JAN-07:40
February 0.377143E+11 0.00 471.73 131171.62 02-FEB-03:30 0.00 44.06 55.26 0.21 0.00 0.04 0.37 02-FEB-03:30
March 0.256201E+11 0.00 381.62 132990.71 02-MAR-09:01 0.00 40.83 50.76 0.12 0.00 0.03 0.37 02-MAR-09:01
April 0.307040E+10 0.00 69.29 48795.33 12-APR-06:00 0.00 40.66 42.76 0.01 0.00 0.00 0.14 12-APR-06:00
May 25765980.31 0.00 3.72 15609.73 02-MAY-08:05 0.00 46.36 46.44 0.00 0.00 0.00 0.04 02-MAY-08:05
June 3018682.39 0.00 0.85 2615.57 30-JUN-08:07 0.00 48.45 48.47 0.00 0.00 0.00 0.01 30-JUN-08:07
July 1416519.16 0.00 0.69 4524.06 21-JUL-21:58 0.00 49.05 49.06 0.00 0.00 0.00 0.01 21-JUL-21:58
August 4866800.13 0.00 1.69 3620.14 17-AUG-08:07 0.00 49.41 49.44 0.00 0.00 0.00 0.01 17-AUG-08:07
September 6938567.91 0.00 1.89 7187.44 11-SEP-08:57 0.00 50.39 50.41 0.00 0.00 0.00 0.02 11-SEP-08:57
October 0.363201E+09 0.00 47.49 20394.73 13-OCT-08:06 0.00 47.41 48.30 0.00 0.00 0.00 0.06 13-OCT-08:06
November 0.333323E+11 0.00 391.04 128514.13 28-NOV-16:11 0.00 44.29 53.78 0.16 0.00 0.04 0.36 28-NOV-16:11
December 0.799905E+11 0.00 647.70 182040.25 26-DEC-16:11 0.00 44.28 57.97 0.41 0.00 0.08 0.51 26-DEC-16:11
                           
Annual Sum or Average 0.239941E+12 0.00 2617.38     0.00 45.84 50.83 0.10 0.00 0.02    
Minimum of Months 1416519.16 0.00 0.69 2615.57   0.00 40.66 42.76 0.00 0.00 0.00 0.01  
Maximum of Months 0.799905E+11 0.00 647.70 182040.25   0.00 50.39 57.97 0.41 0.00 0.08 0.51  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.735597E+10 0.00 83.25 0.735597E+10 0.00 0.00 0.00 0.00 97826.64 03-JAN-17:00 97826.64 03-JAN-17:00 0.00 0.00 0.00
February 0.357677E+11 0.00 188.58 0.357677E+11 0.00 0.00 0.00 0.00 130386.03 20-FEB-16:15 130386.03 20-FEB-16:15 0.00 0.00 0.00
March 0.720688E+11 0.00 302.50 0.720688E+11 0.00 0.00 0.00 0.00 164116.31 14-MAR-18:10 164116.31 14-MAR-18:10 0.00 0.00 0.00
April 0.210249E+12 0.00 551.00 0.210249E+12 0.00 0.00 0.00 0.00 211174.27 19-APR-18:10 211174.27 19-APR-18:10 0.00 0.00 0.00
May 0.341748E+12 0.00 712.00 0.339650E+12 0.00 0.00 0.00 0.00 238014.13 28-MAY-10:35 231151.00 19-MAY-20:10 0.00 0.00 0.00
June 0.434809E+12 0.00 720.00 0.428348E+12 0.00 0.00 0.00 0.00 274802.82 19-JUN-18:10 256557.14 15-JUN-20:10 0.00 0.00 0.00
July 0.575268E+12 0.00 744.00 0.450319E+12 0.00 0.00 0.00 0.00 390180.42 21-JUL-21:00 252128.11 03-JUL-18:10 0.00 0.00 0.00
August 0.474622E+12 0.00 744.00 0.420981E+12 0.00 0.00 0.00 0.00 359285.98 11-AUG-20:00 256647.33 04-AUG-20:10 0.00 0.00 0.00
September 0.392229E+12 0.00 692.33 0.336047E+12 0.00 0.00 0.00 0.00 322920.33 09-SEP-20:00 232400.43 19-SEP-18:20 0.00 0.00 0.00
October 0.198647E+12 0.00 536.83 0.189666E+12 0.00 0.00 0.00 0.00 310491.35 03-OCT-19:55 220664.84 04-OCT-19:10 0.00 0.00 0.00
November 0.434875E+11 0.00 225.67 0.434875E+11 0.00 0.00 0.00 0.00 150611.77 03-NOV-16:00 150611.77 03-NOV-16:00 0.00 0.00 0.00
December 0.433284E+10 0.00 89.88 0.433284E+10 0.00 0.00 0.00 0.00 54499.31 09-DEC-13:00 54499.31 09-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.279059E+13 0.00 5590.04 0.253827E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.433284E+10 0.00 83.25 0.433284E+10 0.00 0.00 0.00 0.00 54499.31   54499.31   0.00 0.00 0.00
Maximum of Months 0.575268E+12 0.00 744.00 0.450319E+12 0.00 0.00 0.00 0.00 390180.42   256647.33   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.389195E+09 0.00 37.67 0.389195E+09 0.00 0.00 0.00 0.00 11015.35 03-JAN-17:00 11015.35 03-JAN-17:00 0.00 0.00 0.00
February 0.196624E+10 0.00 97.50 0.196624E+10 0.00 0.00 0.00 0.00 14147.22 20-FEB-16:12 14147.22 20-FEB-16:12 0.00 0.00 0.00
March 0.406941E+10 0.00 176.17 0.406941E+10 0.00 0.00 0.00 0.00 14783.01 22-MAR-15:12 14783.01 22-MAR-15:12 0.00 0.00 0.00
April 0.138040E+11 0.00 399.83 0.138040E+11 0.00 0.00 0.00 0.00 17603.89 21-APR-15:12 17603.89 21-APR-15:12 0.00 0.00 0.00
May 0.229551E+11 0.00 539.33 0.223895E+11 0.00 0.00 0.00 0.00 21921.47 24-MAY-13:00 18576.13 19-MAY-15:12 0.00 0.00 0.00
June 0.287850E+11 0.00 550.00 0.274840E+11 0.00 0.00 0.00 0.00 24534.76 27-JUN-24:00 19628.34 02-JUN-15:13 0.00 0.00 0.00
July 0.409763E+11 0.00 568.33 0.289621E+11 0.00 0.00 0.00 0.00 39037.79 21-JUL-08:03 19688.08 02-JUL-15:13 0.00 0.00 0.00
August 0.334889E+11 0.00 568.33 0.272298E+11 0.00 0.00 0.00 0.00 33349.38 03-AUG-06:25 19090.15 06-AUG-15:12 0.00 0.00 0.00
September 0.280526E+11 0.00 524.00 0.211888E+11 0.00 0.00 0.00 0.00 31964.14 22-SEP-08:03 18219.08 19-SEP-15:12 0.00 0.00 0.00
October 0.130966E+11 0.00 384.67 0.117143E+11 0.00 0.00 0.00 0.00 27787.51 03-OCT-20:20 17847.54 01-OCT-15:12 0.00 0.00 0.00
November 0.249625E+10 0.00 129.50 0.249625E+10 0.00 0.00 0.00 0.00 14436.71 09-NOV-16:12 14436.71 09-NOV-16:12 0.00 0.00 0.00
December 0.199728E+09 0.00 30.83 0.199728E+09 0.00 0.00 0.00 0.00 5697.71 10-DEC-14:00 5697.71 10-DEC-14:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.190279E+12 0.00 4006.17 0.161893E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.199728E+09 0.00 30.83 0.199728E+09 0.00 0.00 0.00 0.00 5697.71   5697.71   0.00 0.00 0.00
Maximum of Months 0.409763E+11 0.00 568.33 0.289621E+11 0.00 0.00 0.00 0.00 39037.79   19688.08   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.827957E+09 0.00 212.24 0.759643E+09 0.00 0.00 0.00 0.00 7986.47 12-JAN-16:12 7986.47 12-JAN-16:12 0.00 0.00 0.00
February 0.125200E+10 0.00 286.53 0.123677E+10 0.00 0.00 0.00 0.00 7984.36 18-FEB-16:12 7984.36 18-FEB-16:12 0.00 0.00 0.00
March 0.231627E+10 0.00 439.89 0.229052E+10 0.00 0.00 0.00 0.00 7985.93 12-MAR-15:12 7985.93 12-MAR-15:12 0.00 0.00 0.00
April 0.500494E+10 0.00 618.06 0.472549E+10 0.00 0.00 0.00 0.00 7986.10 20-APR-18:02 7986.10 20-APR-18:02 0.00 0.00 0.00
May 0.752204E+10 0.00 692.56 0.671793E+10 0.00 0.00 0.00 0.00 8847.76 28-MAY-08:62 8051.42 24-MAY-15:12 0.00 0.00 0.00
June 0.937067E+10 0.00 690.14 0.802955E+10 0.00 0.00 0.00 0.00 8918.67 29-JUN-08:62 8037.80 26-JUN-08:62 0.00 0.00 0.00
July 0.999817E+10 0.00 712.94 0.745651E+10 0.00 0.00 0.00 0.00 10494.04 19-JUL-08:62 8033.84 01-JUL-08:62 0.00 0.00 0.00
August 0.919799E+10 0.00 702.80 0.696184E+10 0.00 0.00 0.00 0.00 9540.51 14-AUG-08:62 8049.55 18-AUG-18:02 0.00 0.00 0.00
September 0.854472E+10 0.00 681.36 0.650396E+10 0.00 0.00 0.00 0.00 9704.79 23-SEP-18:02 8034.35 01-SEP-18:02 0.00 0.00 0.00
October 0.575921E+10 0.00 663.37 0.440234E+10 0.00 0.00 0.00 0.00 9259.93 04-OCT-08:62 8045.00 02-OCT-15:12 0.00 0.00 0.00
November 0.226482E+10 0.00 415.42 0.209455E+10 0.00 0.00 0.00 0.00 7986.39 25-NOV-16:12 7986.39 25-NOV-16:12 0.00 0.00 0.00
December 0.504217E+09 0.00 161.65 0.487247E+09 0.00 0.00 0.00 0.00 7985.44 13-DEC-16:12 7985.44 13-DEC-16:12 0.00 0.00 0.00
                               
Annual Sum or Average 0.625630E+11 0.00 6276.96 0.516663E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.504217E+09 0.00 161.65 0.487247E+09 0.00 0.00 0.00 0.00 7984.36   7984.36   0.00 0.00 0.00
Maximum of Months 0.999817E+10 0.00 712.94 0.802955E+10 0.00 0.00 0.00 0.00 10494.04   8051.42   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.137719E+09 0.00 46.73 0.129997E+09 0.00 0.00 0.00 0.00 7825.63 30-JAN-16:12 7825.63 30-JAN-16:12 0.00 0.00 0.00
February 0.238587E+09 0.00 102.10 0.233757E+09 0.00 0.00 0.00 0.00 7924.44 24-FEB-16:12 7924.44 24-FEB-16:12 0.00 0.00 0.00
March 0.843632E+09 0.00 255.75 0.825271E+09 0.00 0.00 0.00 0.00 7928.45 27-MAR-18:02 7928.45 27-MAR-18:02 0.00 0.00 0.00
April 0.372084E+10 0.00 486.94 0.349884E+10 0.00 0.00 0.00 0.00 8745.06 06-APR-18:11 8745.06 06-APR-18:11 0.00 0.00 0.00
May 0.677868E+10 0.00 586.84 0.610279E+10 0.00 0.00 0.00 0.00 9222.45 28-MAY-08:51 8455.28 20-MAY-08:51 0.00 0.00 0.00
June 0.896919E+10 0.00 617.20 0.777796E+10 0.00 0.00 0.00 0.00 9335.11 04-JUN-08:51 8908.15 18-JUN-07:32 0.00 0.00 0.00
July 0.943781E+10 0.00 633.08 0.717499E+10 0.00 0.00 0.00 0.00 10942.18 21-JUL-08:51 8380.59 11-JUL-07:52 0.00 0.00 0.00
August 0.814379E+10 0.00 604.81 0.623361E+10 0.00 0.00 0.00 0.00 10517.89 03-AUG-08:61 8393.17 26-AUG-08:11 0.00 0.00 0.00
September 0.653825E+10 0.00 542.38 0.494636E+10 0.00 0.00 0.00 0.00 10098.32 03-SEP-08:51 8479.29 09-SEP-17:52 0.00 0.00 0.00
October 0.315143E+10 0.00 459.77 0.217868E+10 0.00 0.00 0.00 0.00 9534.93 03-OCT-21:52 7961.89 04-OCT-18:02 0.00 0.00 0.00
November 0.580811E+09 0.00 205.87 0.490307E+09 0.00 0.00 0.00 0.00 7928.99 12-NOV-16:12 7928.99 12-NOV-16:12 0.00 0.00 0.00
December 55445921.03 0.00 16.69 53835635.55 0.00 0.00 0.00 0.00 7890.03 16-DEC-16:12 7890.03 16-DEC-16:12 0.00 0.00 0.00
                               
Annual Sum or Average 0.485962E+11 0.00 4558.15 0.396464E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 55445921.03 0.00 16.69 53835635.55 0.00 0.00 0.00 0.00 7825.63   7825.63   0.00 0.00 0.00
Maximum of Months 0.943781E+10 0.00 633.08 0.777796E+10 0.00 0.00 0.00 0.00 10942.18   8908.15   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.204228E+11 0.00 439.56 0.204219E+11 0.00 0.00 0.00 0.00 34961.56 12-JAN-14:25 34961.56 12-JAN-14:25 0.00 0.00 0.00
February 0.203562E+11 0.00 466.06 0.201152E+11 0.00 0.00 0.00 0.00 33121.84 07-FEB-13:40 33121.84 07-FEB-13:40 0.00 0.00 0.00
March 0.192018E+11 0.00 537.36 0.190216E+11 0.00 0.00 0.00 0.00 25972.04 07-MAR-13:10 25972.04 07-MAR-13:10 0.00 0.00 0.00
April 0.253771E+11 0.00 650.89 0.243412E+11 0.00 0.00 0.00 0.00 23649.73 03-APR-13:30 23649.73 03-APR-13:30 0.00 0.00 0.00
May 0.304047E+11 0.00 730.00 0.258544E+11 0.00 0.00 0.00 0.00 23035.89 19-MAY-20:20 23000.60 31-MAY-20:20 0.00 0.00 0.00
June 0.370388E+11 0.00 718.00 0.283622E+11 0.00 0.00 0.00 0.00 25886.40 07-JUN-20:20 25886.28 15-JUN-20:20 0.00 0.00 0.00
July 0.409057E+11 0.00 741.00 0.243096E+11 0.00 0.00 0.00 0.00 27810.86 15-JUL-07:40 22971.42 02-JUL-20:40 0.00 0.00 0.00
August 0.415682E+11 0.00 740.83 0.269093E+11 0.00 0.00 0.00 0.00 28364.51 05-AUG-08:00 26030.30 27-AUG-13:40 0.00 0.00 0.00
September 0.460845E+11 0.00 720.00 0.329229E+11 0.00 0.00 0.00 0.00 34361.11 19-SEP-13:30 29465.66 30-SEP-13:20 0.00 0.00 0.00
October 0.414235E+11 0.00 710.22 0.340681E+11 0.00 0.00 0.00 0.00 40442.42 22-OCT-13:15 37678.53 22-OCT-12:10 0.00 0.00 0.00
November 0.299880E+11 0.00 522.03 0.289329E+11 0.00 0.00 0.00 0.00 38645.35 10-NOV-12:00 37786.48 09-NOV-13:15 0.00 0.00 0.00
December 0.178172E+11 0.00 423.25 0.178172E+11 0.00 0.00 0.00 0.00 30776.10 07-DEC-14:00 30776.10 07-DEC-14:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.370589E+12 0.00 7399.20 0.303076E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.178172E+11 0.00 423.25 0.178172E+11 0.00 0.00 0.00 0.00 23035.89   22971.42   0.00 0.00 0.00
Maximum of Months 0.460845E+11 0.00 741.00 0.340681E+11 0.00 0.00 0.00 0.00 40442.42   37786.48   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.383048E+10 0.00 225.70 0.332584E+10 0.00 0.00 0.00 0.00 50602.48 16-JAN-09:02 50340.62 14-JAN-09:02 0.00 0.00 0.00
February 0.642231E+10 0.00 271.00 0.591347E+10 0.00 0.00 0.00 0.00 51913.19 21-FEB-21:32 51913.19 21-FEB-21:32 0.00 0.00 0.00
March 0.123305E+11 0.00 373.77 0.119309E+11 0.00 0.00 0.00 0.00 52776.74 22-MAR-20:22 52776.74 22-MAR-20:22 0.00 0.00 0.00
April 0.272475E+11 0.00 424.59 0.260851E+11 0.00 0.00 0.00 0.00 53787.32 05-APR-21:52 53787.32 05-APR-21:52 0.00 0.00 0.00
May 0.435612E+11 0.00 518.95 0.395448E+11 0.00 0.00 0.00 0.00 58312.81 23-MAY-21:51 54583.13 20-MAY-08:51 0.00 0.00 0.00
June 0.562394E+11 0.00 567.33 0.487453E+11 0.00 0.00 0.00 0.00 58345.92 19-JUN-18:51 56348.39 21-JUN-07:42 0.00 0.00 0.00
July 0.613447E+11 0.00 581.69 0.469682E+11 0.00 0.00 0.00 0.00 69833.08 21-JUL-08:51 55932.94 11-JUL-07:52 0.00 0.00 0.00
August 0.523016E+11 0.00 544.88 0.399651E+11 0.00 0.00 0.00 0.00 64874.91 03-AUG-08:61 55428.59 11-AUG-07:51 0.00 0.00 0.00
September 0.407100E+11 0.00 464.44 0.305085E+11 0.00 0.00 0.00 0.00 64963.46 23-SEP-21:52 53704.15 20-SEP-18:02 0.00 0.00 0.00
October 0.258010E+11 0.00 389.33 0.192838E+11 0.00 0.00 0.00 0.00 63234.48 03-OCT-21:52 53422.97 19-OCT-21:52 0.00 0.00 0.00
November 0.817925E+10 0.00 315.26 0.709468E+10 0.00 0.00 0.00 0.00 51496.49 08-NOV-22:52 51496.49 08-NOV-22:52 0.00 0.00 0.00
December 0.275223E+10 0.00 173.86 0.256114E+10 0.00 0.00 0.00 0.00 50403.98 09-DEC-09:02 50403.98 09-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.340720E+12 0.00 4850.79 0.281927E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.275223E+10 0.00 173.86 0.256114E+10 0.00 0.00 0.00 0.00 50403.98   50340.62   0.00 0.00 0.00
Maximum of Months 0.613447E+11 0.00 581.69 0.487453E+11 0.00 0.00 0.00 0.00 69833.08   56348.39   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.743881E+09 0.00 189.23 0.682936E+09 0.00 0.00 0.00 0.00 7102.99 31-JAN-09:02 7102.99 31-JAN-09:02 0.00 0.00 0.00
February 0.141938E+10 0.00 312.16 0.139213E+10 0.00 0.00 0.00 0.00 7103.15 05-FEB-09:02 7103.15 05-FEB-09:02 0.00 0.00 0.00
March 0.236087E+10 0.00 470.72 0.233555E+10 0.00 0.00 0.00 0.00 7103.25 28-MAR-08:62 7103.25 28-MAR-08:62 0.00 0.00 0.00
April 0.526739E+10 0.00 661.49 0.500164E+10 0.00 0.00 0.00 0.00 7103.05 20-APR-18:02 7103.05 20-APR-18:02 0.00 0.00 0.00
May 0.770845E+10 0.00 722.37 0.697268E+10 0.00 0.00 0.00 0.00 7513.65 28-MAY-08:62 7143.23 24-MAY-08:62 0.00 0.00 0.00
June 0.965528E+10 0.00 706.07 0.848216E+10 0.00 0.00 0.00 0.00 7910.48 29-JUN-08:62 7151.83 26-JUN-08:62 0.00 0.00 0.00
July 0.102672E+11 0.00 726.88 0.796673E+10 0.00 0.00 0.00 0.00 9355.28 19-JUL-08:62 7157.01 26-JUL-15:13 0.00 0.00 0.00
August 0.944003E+10 0.00 719.07 0.747625E+10 0.00 0.00 0.00 0.00 8488.33 14-AUG-08:62 7163.73 31-AUG-18:02 0.00 0.00 0.00
September 0.863597E+10 0.00 699.07 0.676969E+10 0.00 0.00 0.00 0.00 8544.71 23-SEP-18:02 7163.14 22-SEP-18:02 0.00 0.00 0.00
October 0.538345E+10 0.00 669.55 0.416478E+10 0.00 0.00 0.00 0.00 8397.51 15-OCT-08:62 7158.36 05-OCT-18:02 0.00 0.00 0.00
November 0.216367E+10 0.00 423.51 0.201480E+10 0.00 0.00 0.00 0.00 7332.74 03-NOV-08:62 7102.97 14-NOV-09:02 0.00 0.00 0.00
December 0.540091E+09 0.00 144.44 0.516509E+09 0.00 0.00 0.00 0.00 7102.93 10-DEC-09:02 7102.93 10-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.635857E+11 0.00 6444.56 0.537758E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.540091E+09 0.00 144.44 0.516509E+09 0.00 0.00 0.00 0.00 7102.93   7102.93   0.00 0.00 0.00
Maximum of Months 0.102672E+11 0.00 726.88 0.848216E+10 0.00 0.00 0.00 0.00 9355.28   7163.73   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.104959E+09 0.00 45.21 81848200.31 0.00 0.00 0.00 0.00 6830.64 31-JAN-09:02 6830.64 31-JAN-09:02 0.00 0.00 0.00
February 0.420071E+09 0.00 129.20 0.402433E+09 0.00 0.00 0.00 0.00 7055.07 20-FEB-09:02 7055.07 20-FEB-09:02 0.00 0.00 0.00
March 0.106237E+10 0.00 276.67 0.104234E+10 0.00 0.00 0.00 0.00 7056.00 28-MAR-08:62 7056.00 28-MAR-08:62 0.00 0.00 0.00
April 0.394513E+10 0.00 533.07 0.372504E+10 0.00 0.00 0.00 0.00 8048.33 27-APR-08:51 8048.33 27-APR-08:51 0.00 0.00 0.00
May 0.672810E+10 0.00 610.40 0.611144E+10 0.00 0.00 0.00 0.00 8845.44 28-MAY-08:51 8184.36 20-MAY-08:51 0.00 0.00 0.00
June 0.905252E+10 0.00 629.39 0.800038E+10 0.00 0.00 0.00 0.00 9233.85 20-JUN-08:62 8793.38 14-JUN-07:52 0.00 0.00 0.00
July 0.951992E+10 0.00 644.09 0.745790E+10 0.00 0.00 0.00 0.00 10136.13 21-JUL-08:51 8100.31 04-JUL-08:62 0.00 0.00 0.00
August 0.819866E+10 0.00 617.58 0.648115E+10 0.00 0.00 0.00 0.00 9696.19 02-AUG-08:51 8214.60 28-AUG-08:51 0.00 0.00 0.00
September 0.641476E+10 0.00 559.53 0.485441E+10 0.00 0.00 0.00 0.00 9656.55 09-SEP-08:51 8086.26 19-SEP-08:51 0.00 0.00 0.00
October 0.294889E+10 0.00 480.18 0.206299E+10 0.00 0.00 0.00 0.00 8781.12 05-OCT-08:51 7717.60 05-OCT-08:51 0.00 0.00 0.00
November 0.611975E+09 0.00 180.60 0.542804E+09 0.00 0.00 0.00 0.00 7378.82 09-NOV-09:51 7378.82 09-NOV-09:51 0.00 0.00 0.00
December 73611596.83 0.00 29.29 64084423.52 0.00 0.00 0.00 0.00 6898.52 16-DEC-09:02 6898.52 16-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.490810E+11 0.00 4735.23 0.408268E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 73611596.83 0.00 29.29 64084423.52 0.00 0.00 0.00 0.00 6830.64   6830.64   0.00 0.00 0.00
Maximum of Months 0.951992E+10 0.00 644.09 0.800038E+10 0.00 0.00 0.00 0.00 10136.13   8793.38   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.156443E+09 0.00 139.98 0.146933E+09 0.00 0.00 0.00 0.00 2131.04 18-JAN-16:12 2131.04 18-JAN-16:12 0.00 0.00 0.00
February 0.258809E+09 0.00 194.43 0.256997E+09 0.00 0.00 0.00 0.00 2130.52 18-FEB-16:12 2130.52 18-FEB-16:12 0.00 0.00 0.00
March 0.507184E+09 0.00 332.96 0.503682E+09 0.00 0.00 0.00 0.00 2130.90 12-MAR-15:12 2130.90 12-MAR-15:12 0.00 0.00 0.00
April 0.122509E+10 0.00 583.81 0.115527E+10 0.00 0.00 0.00 0.00 2130.91 20-APR-18:02 2130.91 20-APR-18:02 0.00 0.00 0.00
May 0.190157E+10 0.00 690.64 0.168624E+10 0.00 0.00 0.00 0.00 2414.24 28-MAY-08:62 2131.08 14-MAY-15:12 0.00 0.00 0.00
June 0.244947E+10 0.00 690.81 0.208714E+10 0.00 0.00 0.00 0.00 2457.51 29-JUN-08:62 2145.93 03-JUN-08:62 0.00 0.00 0.00
July 0.262878E+10 0.00 712.55 0.195146E+10 0.00 0.00 0.00 0.00 2928.79 19-JUL-08:62 2143.87 04-JUL-18:02 0.00 0.00 0.00
August 0.237502E+10 0.00 703.40 0.178249E+10 0.00 0.00 0.00 0.00 2638.85 18-AUG-08:62 2148.82 30-AUG-18:02 0.00 0.00 0.00
September 0.212982E+10 0.00 677.38 0.158594E+10 0.00 0.00 0.00 0.00 2684.80 09-SEP-08:62 2143.02 03-SEP-15:12 0.00 0.00 0.00
October 0.131694E+10 0.00 618.99 0.995989E+09 0.00 0.00 0.00 0.00 2564.37 09-OCT-08:62 2147.96 03-OCT-15:12 0.00 0.00 0.00
November 0.452523E+09 0.00 318.59 0.420814E+09 0.00 0.00 0.00 0.00 2131.03 25-NOV-16:12 2131.03 25-NOV-16:12 0.00 0.00 0.00
December 93436782.33 0.00 95.63 91275825.96 0.00 0.00 0.00 0.00 2130.77 13-DEC-16:12 2130.77 13-DEC-16:12 0.00 0.00 0.00
                               
Annual Sum or Average 0.154951E+11 0.00 5759.16 0.126642E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 93436782.33 0.00 95.63 91275825.96 0.00 0.00 0.00 0.00 2130.52   2130.52   0.00 0.00 0.00
Maximum of Months 0.262878E+10 0.00 712.55 0.208714E+10 0.00 0.00 0.00 0.00 2928.79   2148.82   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 21685294.63 0.00 22.47 20592681.82 0.00 0.00 0.00 0.00 2046.80 30-JAN-16:12 2046.80 30-JAN-16:12 0.00 0.00 0.00
February 35252445.00 0.00 53.39 34865904.12 0.00 0.00 0.00 0.00 2079.56 24-FEB-16:12 2079.56 24-FEB-16:12 0.00 0.00 0.00
March 0.152566E+09 0.00 165.95 0.150211E+09 0.00 0.00 0.00 0.00 2113.08 27-MAR-18:02 2113.08 27-MAR-18:02 0.00 0.00 0.00
April 0.917559E+09 0.00 463.89 0.859334E+09 0.00 0.00 0.00 0.00 2336.90 06-APR-18:11 2336.90 06-APR-18:11 0.00 0.00 0.00
May 0.174768E+10 0.00 588.57 0.156221E+10 0.00 0.00 0.00 0.00 2469.31 28-MAY-08:51 2259.49 20-MAY-08:51 0.00 0.00 0.00
June 0.238106E+10 0.00 619.09 0.205865E+10 0.00 0.00 0.00 0.00 2519.77 04-JUN-08:51 2328.46 19-JUN-18:51 0.00 0.00 0.00
July 0.251746E+10 0.00 634.73 0.191580E+10 0.00 0.00 0.00 0.00 2982.86 21-JUL-08:51 2208.35 11-JUL-07:52 0.00 0.00 0.00
August 0.213977E+10 0.00 608.72 0.162976E+10 0.00 0.00 0.00 0.00 2857.77 03-AUG-08:61 2247.27 26-AUG-08:11 0.00 0.00 0.00
September 0.165644E+10 0.00 543.66 0.122868E+10 0.00 0.00 0.00 0.00 2753.46 03-SEP-08:51 2272.14 09-SEP-17:52 0.00 0.00 0.00
October 0.677361E+09 0.00 413.56 0.463733E+09 0.00 0.00 0.00 0.00 2592.14 03-OCT-21:52 2123.39 02-OCT-15:12 0.00 0.00 0.00
November 78503404.92 0.00 106.50 64967015.29 0.00 0.00 0.00 0.00 2113.24 12-NOV-16:12 2113.24 12-NOV-16:12 0.00 0.00 0.00
December 9279821.12 0.00 8.76 8905495.42 0.00 0.00 0.00 0.00 2074.86 16-DEC-16:12 2074.86 16-DEC-16:12 0.00 0.00 0.00
                               
Annual Sum or Average 0.123346E+11 0.00 4229.30 0.999771E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 9279821.12 0.00 8.76 8905495.42 0.00 0.00 0.00 0.00 2046.80   2046.80   0.00 0.00 0.00
Maximum of Months 0.251746E+10 0.00 634.73 0.205865E+10 0.00 0.00 0.00 0.00 2982.86   2336.90   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.434229E+10 0.00 432.19 0.409506E+10 0.00 0.00 0.00 0.00 9863.21 08-JAN-16:12 9863.21 08-JAN-16:12 0.00 0.00 0.00
February 0.432018E+10 0.00 437.23 0.423633E+10 0.00 0.00 0.00 0.00 9863.70 18-FEB-16:12 9863.70 18-FEB-16:12 0.00 0.00 0.00
March 0.431828E+10 0.00 520.90 0.425711E+10 0.00 0.00 0.00 0.00 9863.49 27-MAR-15:12 9863.49 27-MAR-15:12 0.00 0.00 0.00
April 0.639478E+10 0.00 615.73 0.600858E+10 0.00 0.00 0.00 0.00 10032.52 18-APR-18:02 9864.18 21-APR-15:12 0.00 0.00 0.00
May 0.837581E+10 0.00 685.30 0.716032E+10 0.00 0.00 0.00 0.00 10901.82 28-MAY-08:62 9863.73 06-MAY-15:12 0.00 0.00 0.00
June 0.107895E+11 0.00 683.87 0.897371E+10 0.00 0.00 0.00 0.00 10818.09 29-JUN-08:62 9886.52 26-JUN-08:62 0.00 0.00 0.00
July 0.122344E+11 0.00 706.67 0.892935E+10 0.00 0.00 0.00 0.00 13521.45 19-JUL-08:62 9872.44 09-JUL-18:02 0.00 0.00 0.00
August 0.119002E+11 0.00 699.70 0.895427E+10 0.00 0.00 0.00 0.00 11949.65 02-AUG-08:62 9926.42 21-AUG-15:12 0.00 0.00 0.00
September 0.121217E+11 0.00 681.80 0.942916E+10 0.00 0.00 0.00 0.00 12375.49 23-SEP-18:02 9924.85 01-SEP-15:12 0.00 0.00 0.00
October 0.996985E+10 0.00 674.99 0.823516E+10 0.00 0.00 0.00 0.00 11460.33 04-OCT-08:62 9862.82 31-OCT-08:62 0.00 0.00 0.00
November 0.638060E+10 0.00 512.72 0.607773E+10 0.00 0.00 0.00 0.00 9939.71 03-NOV-08:62 9863.50 09-NOV-19:02 0.00 0.00 0.00
December 0.390340E+10 0.00 393.66 0.378614E+10 0.00 0.00 0.00 0.00 9863.16 10-DEC-09:02 9863.16 10-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.950509E+11 0.00 7044.77 0.801429E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.390340E+10 0.00 393.66 0.378614E+10 0.00 0.00 0.00 0.00 9863.16   9862.82   0.00 0.00 0.00
Maximum of Months 0.122344E+11 0.00 706.67 0.942916E+10 0.00 0.00 0.00 0.00 13521.45   9926.42   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 499.74 380.28 119.46 828.68 301.73 0.00 0.00 0.00
February 460.35 325.44 134.91 789.56 266.40 0.00 0.00 0.00
March 346.37 189.06 157.31 635.05 232.36 0.00 0.00 0.00
April 235.63 77.68 157.95 488.14 137.98 0.00 0.00 0.00
May 170.79 17.65 153.14 379.42 78.23 0.00 0.00 0.00
June 149.01 5.17 143.83 381.51 36.02 0.00 0.00 0.00
July 150.45 8.39 142.06 388.40 26.76 0.00 0.00 0.00
August 184.84 38.06 146.77 463.14 41.08 0.00 0.00 0.00
September 292.72 143.01 149.71 669.39 92.84 0.00 0.00 0.00
October 417.76 280.64 137.13 810.68 153.95 0.00 0.00 0.00
November 516.95 395.92 121.03 892.33 258.28 0.00 0.00 0.00
December 515.44 389.54 125.90 840.09 326.68 0.00 0.00 0.00
                 
Annual Sum or Average 327.58 186.79 140.79 629.47 162.18 0.00 0.00 0.00
Minimum of Months 149.01 5.17 119.46 379.42 26.76 0.00 0.00 0.00
Maximum of Months 516.95 395.92 157.95 892.33 326.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1407.24 1070.85 336.39 2337.81 843.90 0.00 0.00 0.00
February 1296.31 916.41 379.90 2230.40 738.34 0.00 0.00 0.00
March 975.35 532.39 442.97 1805.34 634.76 0.00 0.00 0.00
April 663.52 218.74 444.78 1413.60 352.84 0.00 0.00 0.00
May 480.93 49.71 431.22 1129.48 184.36 0.00 0.00 0.00
June 419.60 14.57 405.03 1146.15 78.02 0.00 0.00 0.00
July 423.65 23.63 400.02 1163.27 51.84 0.00 0.00 0.00
August 520.49 107.18 413.31 1362.03 90.45 0.00 0.00 0.00
September 824.27 402.70 421.58 1918.53 226.03 0.00 0.00 0.00
October 1176.39 790.25 386.14 2302.65 400.77 0.00 0.00 0.00
November 1455.70 1114.88 340.82 2515.81 707.89 0.00 0.00 0.00
December 1451.44 1096.91 354.54 2368.19 915.66 0.00 0.00 0.00
                 
Annual Sum or Average 922.44 525.99 396.45 1804.95 433.95 0.00 0.00 0.00
Minimum of Months 419.60 14.57 336.39 1129.48 51.84 0.00 0.00 0.00
Maximum of Months 1455.70 1114.88 444.78 2515.81 915.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1828.09 1391.09 436.99 3060.71 1164.22 0.00 0.00 0.00
February 1683.98 1190.47 493.51 2919.45 1021.20 0.00 0.00 0.00
March 1267.04 691.60 575.44 2354.62 887.49 0.00 0.00 0.00
April 861.95 284.15 577.80 1834.08 508.47 0.00 0.00 0.00
May 624.76 64.58 560.18 1448.73 275.84 0.00 0.00 0.00
June 545.08 18.92 526.15 1470.74 119.42 0.00 0.00 0.00
July 550.35 30.70 519.65 1492.47 85.09 0.00 0.00 0.00
August 676.15 139.24 536.91 1761.35 137.08 0.00 0.00 0.00
September 1070.78 523.13 547.65 2508.37 320.35 0.00 0.00 0.00
October 1528.19 1026.58 501.61 3012.61 559.90 0.00 0.00 0.00
November 1891.04 1448.29 442.75 3295.78 977.73 0.00 0.00 0.00
December 1885.51 1424.94 460.56 3096.77 1261.76 0.00 0.00 0.00
                 
Annual Sum or Average 1198.30 683.28 515.02 2350.85 607.91 0.00 0.00 0.00
Minimum of Months 545.08 18.92 436.99 1448.73 85.09 0.00 0.00 0.00
Maximum of Months 1891.04 1448.29 577.80 3295.78 1261.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.81 75.19 23.62 165.58 57.52 0.00 0.00 0.00
February 91.02 64.34 26.67 157.94 50.15 0.00 0.00 0.00
March 68.48 37.38 31.10 126.68 43.42 0.00 0.00 0.00
April 46.59 15.36 31.23 99.23 22.64 0.00 0.00 0.00
May 33.77 3.49 30.28 79.99 10.63 0.00 0.00 0.00
June 29.46 1.02 28.44 83.15 3.66 0.00 0.00 0.00
July 29.75 1.66 28.09 84.57 1.98 0.00 0.00 0.00
August 36.55 7.53 29.02 98.23 4.06 0.00 0.00 0.00
September 57.88 28.27 29.60 136.67 12.72 0.00 0.00 0.00
October 82.60 55.49 27.11 163.48 25.03 0.00 0.00 0.00
November 102.21 78.28 23.93 178.84 47.32 0.00 0.00 0.00
December 101.91 77.02 24.89 168.36 62.88 0.00 0.00 0.00
                 
Annual Sum or Average 64.77 36.93 27.84 128.36 28.40 0.00 0.00 0.00
Minimum of Months 29.46 1.02 23.62 79.99 1.98 0.00 0.00 0.00
Maximum of Months 102.21 78.28 31.23 178.84 62.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.51 41.78 32.73 105.57 115.31 0.00 0.00 0.00
February 84.20 44.58 39.62 126.56 100.93 0.00 0.00 0.00
March 116.01 62.59 53.43 189.32 83.01 0.00 0.00 0.00
April 133.25 72.36 60.89 247.38 41.67 0.00 0.00 0.00
May 143.73 77.42 66.31 293.48 19.64 0.00 0.00 0.00
June 139.37 75.10 64.28 317.63 6.78 0.00 0.00 0.00
July 123.82 61.80 62.02 286.13 3.62 0.00 0.00 0.00
August 120.02 61.47 58.55 266.46 7.53 0.00 0.00 0.00
September 123.55 69.41 54.13 255.72 23.94 0.00 0.00 0.00
October 106.08 62.31 43.77 196.53 48.41 0.00 0.00 0.00
November 87.87 53.38 34.49 137.45 95.37 0.00 0.00 0.00
December 70.44 37.97 32.48 95.07 127.47 0.00 0.00 0.00
                 
Annual Sum or Average 110.34 60.06 50.28 210.13 55.93 0.00 0.00 0.00
Minimum of Months 70.44 37.97 32.48 95.07 3.62 0.00 0.00 0.00
Maximum of Months 143.73 77.42 66.31 317.63 127.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.24 0.00 14.24 7.41 61.86 0.00 0.00 0.00
February 17.39 0.00 17.39 14.11 54.27 0.00 0.00 0.00
March 22.77 0.00 22.77 25.21 45.33 0.00 0.00 0.00
April 26.30 0.20 26.10 42.94 22.49 0.00 0.00 0.00
May 30.56 1.64 28.93 66.71 10.43 0.00 0.00 0.00
June 32.17 3.10 29.07 87.63 3.70 0.00 0.00 0.00
July 29.93 2.25 27.67 81.85 2.08 0.00 0.00 0.00
August 25.74 0.40 25.33 65.09 4.23 0.00 0.00 0.00
September 22.56 0.01 22.55 48.75 13.42 0.00 0.00 0.00
October 18.71 0.00 18.71 28.95 27.02 0.00 0.00 0.00
November 15.11 0.00 15.11 11.09 51.53 0.00 0.00 0.00
December 14.13 0.00 14.13 5.91 68.50 0.00 0.00 0.00
                 
Annual Sum or Average 22.49 0.64 21.86 40.61 30.29 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 5.91 2.08 0.00 0.00 0.00
Maximum of Months 32.17 3.10 29.07 87.63 68.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.51 41.78 32.73 109.33 112.37 0.00 0.00 0.00
February 84.20 44.58 39.62 129.77 99.05 0.00 0.00 0.00
March 116.01 62.59 53.43 190.90 82.91 0.00 0.00 0.00
April 133.25 72.36 60.89 247.39 42.74 0.00 0.00 0.00
May 143.73 77.42 66.31 292.27 20.51 0.00 0.00 0.00
June 139.37 75.10 64.28 315.85 7.09 0.00 0.00 0.00
July 123.82 61.80 62.02 284.48 3.92 0.00 0.00 0.00
August 120.02 61.47 58.55 265.59 8.08 0.00 0.00 0.00
September 123.55 69.41 54.13 255.95 25.02 0.00 0.00 0.00
October 106.08 62.31 43.77 197.65 49.63 0.00 0.00 0.00
November 87.87 53.38 34.49 140.43 93.71 0.00 0.00 0.00
December 70.44 37.97 32.48 98.97 124.35 0.00 0.00 0.00
                 
Annual Sum or Average 110.34 60.06 50.28 211.06 55.58 0.00 0.00 0.00
Minimum of Months 70.44 37.97 32.48 98.97 3.92 0.00 0.00 0.00
Maximum of Months 143.73 77.42 66.31 315.85 124.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 79.03 60.14 18.89 124.19 62.68 0.00 0.00 0.00
February 72.80 51.47 21.34 117.74 55.90 0.00 0.00 0.00
March 54.78 29.90 24.88 92.65 49.03 0.00 0.00 0.00
April 37.26 12.28 24.98 70.80 30.39 0.00 0.00 0.00
May 27.01 2.79 24.22 54.07 18.13 0.00 0.00 0.00
June 23.56 0.82 22.75 54.49 9.48 0.00 0.00 0.00
July 23.79 1.33 22.47 55.27 8.07 0.00 0.00 0.00
August 29.23 6.02 23.21 67.35 11.14 0.00 0.00 0.00
September 46.29 22.62 23.68 100.84 20.98 0.00 0.00 0.00
October 66.07 44.38 21.69 122.33 32.90 0.00 0.00 0.00
November 81.75 62.61 19.14 134.66 52.78 0.00 0.00 0.00
December 81.51 61.60 19.91 125.81 66.50 0.00 0.00 0.00
                 
Annual Sum or Average 51.80 29.54 22.26 93.18 34.73 0.00 0.00 0.00
Minimum of Months 23.56 0.82 18.89 54.07 8.07 0.00 0.00 0.00
Maximum of Months 81.75 62.61 24.98 134.66 66.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.40 0.00 11.40 5.73 50.42 0.00 0.00 0.00
February 13.92 0.00 13.92 11.45 43.64 0.00 0.00 0.00
March 18.22 0.00 18.22 21.07 35.67 0.00 0.00 0.00
April 21.04 0.16 20.88 36.40 16.92 0.00 0.00 0.00
May 24.45 1.31 23.15 56.19 7.45 0.00 0.00 0.00
June 25.74 2.48 23.26 73.64 2.39 0.00 0.00 0.00
July 23.94 1.80 22.14 68.81 1.22 0.00 0.00 0.00
August 20.59 0.32 20.27 55.21 2.76 0.00 0.00 0.00
September 18.05 0.01 18.04 41.51 9.45 0.00 0.00 0.00
October 14.97 0.00 14.97 24.71 20.23 0.00 0.00 0.00
November 12.09 0.00 12.09 9.29 40.78 0.00 0.00 0.00
December 11.31 0.00 11.31 4.35 56.07 0.00 0.00 0.00
                 
Annual Sum or Average 18.00 0.51 17.49 34.15 23.82 0.00 0.00 0.00
Minimum of Months 11.31 0.00 11.31 4.35 1.22 0.00 0.00 0.00
Maximum of Months 25.74 2.48 23.26 73.64 56.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 70.20 37.67 32.54 93.22 110.59 0.00 0.00 0.00
February 95.51 54.54 40.97 142.19 95.25 0.00 0.00 0.00
March 118.25 65.45 52.80 189.24 77.64 0.00 0.00 0.00
April 143.00 79.92 63.08 263.77 38.81 0.00 0.00 0.00
May 147.19 80.51 66.68 299.98 18.31 0.00 0.00 0.00
June 146.88 82.04 64.84 332.46 6.42 0.00 0.00 0.00
July 132.01 69.46 62.55 301.84 3.50 0.00 0.00 0.00
August 125.69 64.77 60.92 278.21 7.20 0.00 0.00 0.00
September 125.04 71.90 53.14 256.91 22.32 0.00 0.00 0.00
October 94.96 51.22 43.74 172.74 46.05 0.00 0.00 0.00
November 84.60 49.01 35.59 125.48 90.05 0.00 0.00 0.00
December 70.18 36.77 33.41 89.63 121.81 0.00 0.00 0.00
                 
Annual Sum or Average 112.80 61.90 50.90 212.36 52.97 0.00 0.00 0.00
Minimum of Months 70.18 36.77 32.54 89.63 3.50 0.00 0.00 0.00
Maximum of Months 147.19 82.04 66.68 332.46 121.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.81 75.19 23.62 165.21 57.22 0.00 0.00 0.00
February 91.02 64.34 26.67 157.09 50.05 0.00 0.00 0.00
March 68.48 37.38 31.10 125.85 43.17 0.00 0.00 0.00
April 46.59 15.36 31.23 98.45 22.51 0.00 0.00 0.00
May 33.77 3.49 30.28 79.50 10.46 0.00 0.00 0.00
June 29.46 1.02 28.44 82.71 3.56 0.00 0.00 0.00
July 29.75 1.66 28.09 84.19 1.91 0.00 0.00 0.00
August 36.55 7.53 29.02 97.96 3.98 0.00 0.00 0.00
September 57.88 28.27 29.60 136.37 12.52 0.00 0.00 0.00
October 82.60 55.49 27.11 163.33 24.59 0.00 0.00 0.00
November 102.21 78.28 23.93 178.44 46.98 0.00 0.00 0.00
December 101.91 77.02 24.89 167.95 62.68 0.00 0.00 0.00
                 
Annual Sum or Average 64.77 36.93 27.84 127.89 28.20 0.00 0.00 0.00
Minimum of Months 29.46 1.02 23.62 79.50 1.91 0.00 0.00 0.00
Maximum of Months 102.21 78.28 31.23 178.44 62.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.24 0.00 14.24 7.11 61.49 0.00 0.00 0.00
February 17.39 0.00 17.39 13.46 54.19 0.00 0.00 0.00
March 22.77 0.00 22.77 24.50 44.98 0.00 0.00 0.00
April 26.30 0.20 26.10 41.92 22.27 0.00 0.00 0.00
May 30.56 1.64 28.93 65.56 10.25 0.00 0.00 0.00
June 32.17 3.10 29.07 86.63 3.62 0.00 0.00 0.00
July 29.93 2.25 27.67 80.99 2.02 0.00 0.00 0.00
August 25.74 0.40 25.33 64.28 4.15 0.00 0.00 0.00
September 22.56 0.01 22.55 47.87 13.27 0.00 0.00 0.00
October 18.71 0.00 18.71 28.64 26.18 0.00 0.00 0.00
November 15.11 0.00 15.11 10.68 50.88 0.00 0.00 0.00
December 14.13 0.00 14.13 5.53 68.29 0.00 0.00 0.00
                 
Annual Sum or Average 22.49 0.64 21.86 39.90 30.02 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 5.53 2.02 0.00 0.00 0.00
Maximum of Months 32.17 3.10 29.07 86.63 68.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 70.20 37.67 32.54 96.72 107.02 0.00 0.00 0.00
February 95.51 54.54 40.97 145.39 92.98 0.00 0.00 0.00
March 118.25 65.45 52.80 191.08 77.17 0.00 0.00 0.00
April 143.00 79.92 63.08 263.40 39.71 0.00 0.00 0.00
May 147.19 80.51 66.68 297.34 19.11 0.00 0.00 0.00
June 146.88 82.04 64.84 329.34 6.71 0.00 0.00 0.00
July 132.01 69.46 62.55 299.08 3.78 0.00 0.00 0.00
August 125.69 64.77 60.92 276.10 7.68 0.00 0.00 0.00
September 125.04 71.90 53.14 255.71 23.27 0.00 0.00 0.00
October 94.96 51.22 43.74 173.91 46.72 0.00 0.00 0.00
November 84.60 49.01 35.59 128.52 87.76 0.00 0.00 0.00
December 70.18 36.77 33.41 92.97 117.98 0.00 0.00 0.00
                 
Annual Sum or Average 112.80 61.90 50.90 212.67 52.30 0.00 0.00 0.00
Minimum of Months 70.18 36.77 32.54 92.97 3.78 0.00 0.00 0.00
Maximum of Months 147.19 82.04 66.68 329.34 117.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.04 0.00 18.04 8.20 83.33 0.00 0.00 0.00
February 22.03 0.00 22.03 17.03 72.80 0.00 0.00 0.00
March 28.83 0.00 28.83 32.21 59.95 0.00 0.00 0.00
April 33.31 0.25 33.05 55.20 30.99 0.00 0.00 0.00
May 38.71 2.07 36.64 84.30 15.97 0.00 0.00 0.00
June 40.75 3.93 36.82 108.60 7.19 0.00 0.00 0.00
July 37.90 2.86 35.04 101.00 4.86 0.00 0.00 0.00
August 32.59 0.51 32.08 80.13 8.10 0.00 0.00 0.00
September 28.57 0.02 28.55 60.86 20.94 0.00 0.00 0.00
October 23.70 0.00 23.70 35.93 37.67 0.00 0.00 0.00
November 19.13 0.00 19.13 12.77 70.65 0.00 0.00 0.00
December 17.90 0.00 17.90 6.22 91.73 0.00 0.00 0.00
                 
Annual Sum or Average 28.49 0.81 27.68 50.38 41.87 0.00 0.00 0.00
Minimum of Months 17.90 0.00 17.90 6.22 4.86 0.00 0.00 0.00
Maximum of Months 40.75 3.93 36.82 108.60 91.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 6.65 0.00 6.65 3.02 30.72 0.00 0.00 0.00
February 8.12 0.00 8.12 6.28 26.84 0.00 0.00 0.00
March 10.63 0.00 10.63 11.87 22.10 0.00 0.00 0.00
April 12.28 0.09 12.19 20.35 11.43 0.00 0.00 0.00
May 14.27 0.76 13.51 31.08 5.89 0.00 0.00 0.00
June 15.02 1.45 13.57 40.03 2.65 0.00 0.00 0.00
July 13.97 1.05 12.92 37.23 1.79 0.00 0.00 0.00
August 12.02 0.19 11.83 29.54 2.99 0.00 0.00 0.00
September 10.53 0.01 10.53 22.44 7.72 0.00 0.00 0.00
October 8.74 0.00 8.74 13.25 13.89 0.00 0.00 0.00
November 7.05 0.00 7.05 4.71 26.04 0.00 0.00 0.00
December 6.60 0.00 6.60 2.29 33.81 0.00 0.00 0.00
                 
Annual Sum or Average 10.50 0.30 10.20 18.57 15.43 0.00 0.00 0.00
Minimum of Months 6.60 0.00 6.60 2.29 1.79 0.00 0.00 0.00
Maximum of Months 15.02 1.45 13.57 40.03 33.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 46.10 35.08 11.02 77.68 27.71 0.00 0.00 0.00
February 42.47 30.02 12.45 74.11 24.30 0.00 0.00 0.00
March 31.95 17.44 14.51 59.58 21.18 0.00 0.00 0.00
April 21.74 7.17 14.57 46.61 11.80 0.00 0.00 0.00
May 15.76 1.63 14.13 36.99 6.26 0.00 0.00 0.00
June 13.75 0.48 13.27 37.48 2.74 0.00 0.00 0.00
July 13.88 0.77 13.11 38.07 1.86 0.00 0.00 0.00
August 17.05 3.51 13.54 44.76 3.09 0.00 0.00 0.00
September 27.00 13.19 13.81 63.41 7.66 0.00 0.00 0.00
October 38.54 25.89 12.65 76.25 13.24 0.00 0.00 0.00
November 47.69 36.52 11.17 83.62 23.41 0.00 0.00 0.00
December 47.55 35.94 11.62 78.93 30.07 0.00 0.00 0.00
                 
Annual Sum or Average 30.22 17.23 12.99 59.69 14.39 0.00 0.00 0.00
Minimum of Months 13.75 0.48 11.02 36.99 1.86 0.00 0.00 0.00
Maximum of Months 47.69 36.52 14.57 83.62 30.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 125.13 95.22 29.91 210.84 75.20 0.00 0.00 0.00
February 115.27 81.49 33.78 201.14 65.96 0.00 0.00 0.00
March 86.73 47.34 39.39 161.72 57.48 0.00 0.00 0.00
April 59.00 19.45 39.55 126.50 32.02 0.00 0.00 0.00
May 42.77 4.42 38.35 100.39 17.00 0.00 0.00 0.00
June 37.31 1.30 36.02 101.72 7.44 0.00 0.00 0.00
July 37.67 2.10 35.57 103.32 5.04 0.00 0.00 0.00
August 46.28 9.53 36.75 121.50 8.38 0.00 0.00 0.00
September 73.30 35.81 37.49 172.10 20.78 0.00 0.00 0.00
October 104.61 70.27 34.34 206.95 35.94 0.00 0.00 0.00
November 129.44 99.14 30.31 226.96 63.55 0.00 0.00 0.00
December 129.06 97.54 31.53 214.24 81.60 0.00 0.00 0.00
                 
Annual Sum or Average 82.02 46.77 35.25 162.02 39.07 0.00 0.00 0.00
Minimum of Months 37.31 1.30 29.91 100.39 5.04 0.00 0.00 0.00
Maximum of Months 129.44 99.14 39.55 226.96 81.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.81 75.19 23.62 165.28 56.44 0.00 0.00 0.00
February 91.02 64.34 26.67 157.59 49.13 0.00 0.00 0.00
March 68.48 37.38 31.10 126.22 42.56 0.00 0.00 0.00
April 46.59 15.36 31.23 98.71 21.99 0.00 0.00 0.00
May 33.77 3.49 30.28 79.69 10.14 0.00 0.00 0.00
June 29.46 1.02 28.44 82.92 3.40 0.00 0.00 0.00
July 29.75 1.66 28.09 84.17 1.82 0.00 0.00 0.00
August 36.55 7.53 29.02 97.77 3.80 0.00 0.00 0.00
September 57.88 28.27 29.60 135.96 12.23 0.00 0.00 0.00
October 82.60 55.49 27.11 162.86 24.37 0.00 0.00 0.00
November 102.21 78.28 23.93 178.53 46.27 0.00 0.00 0.00
December 101.91 77.02 24.89 168.28 61.76 0.00 0.00 0.00
                 
Annual Sum or Average 64.77 36.93 27.84 127.97 27.73 0.00 0.00 0.00
Minimum of Months 29.46 1.02 23.62 79.69 1.82 0.00 0.00 0.00
Maximum of Months 102.21 78.28 31.23 178.53 61.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.51 41.78 32.73 105.49 112.82 0.00 0.00 0.00
February 84.20 44.58 39.62 126.34 98.66 0.00 0.00 0.00
March 116.01 62.59 53.43 188.68 81.16 0.00 0.00 0.00
April 133.25 72.36 60.89 246.25 40.44 0.00 0.00 0.00
May 143.73 77.42 66.31 292.18 18.70 0.00 0.00 0.00
June 139.37 75.10 64.28 316.33 6.34 0.00 0.00 0.00
July 123.82 61.80 62.02 284.78 3.34 0.00 0.00 0.00
August 120.02 61.47 58.55 265.27 7.06 0.00 0.00 0.00
September 123.55 69.41 54.13 254.50 23.02 0.00 0.00 0.00
October 106.08 62.31 43.77 195.88 47.03 0.00 0.00 0.00
November 87.87 53.38 34.49 137.31 92.96 0.00 0.00 0.00
December 70.44 37.97 32.48 95.23 124.80 0.00 0.00 0.00
                 
Annual Sum or Average 110.34 60.06 50.28 209.38 54.49 0.00 0.00 0.00
Minimum of Months 70.44 37.97 32.48 95.23 3.34 0.00 0.00 0.00
Maximum of Months 143.73 77.42 66.31 316.33 124.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.24 0.00 14.24 7.82 60.32 0.00 0.00 0.00
February 17.39 0.00 17.39 14.49 52.94 0.00 0.00 0.00
March 22.77 0.00 22.77 25.45 44.39 0.00 0.00 0.00
April 26.30 0.20 26.10 42.82 21.94 0.00 0.00 0.00
May 30.56 1.64 28.93 66.54 10.00 0.00 0.00 0.00
June 32.17 3.10 29.07 87.31 3.47 0.00 0.00 0.00
July 29.93 2.25 27.67 81.43 1.93 0.00 0.00 0.00
August 25.74 0.40 25.33 64.89 3.99 0.00 0.00 0.00
September 22.56 0.01 22.55 48.55 12.92 0.00 0.00 0.00
October 18.71 0.00 18.71 29.03 26.35 0.00 0.00 0.00
November 15.11 0.00 15.11 11.55 50.05 0.00 0.00 0.00
December 14.13 0.00 14.13 6.31 66.90 0.00 0.00 0.00
                 
Annual Sum or Average 22.49 0.64 21.86 40.65 29.49 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 6.31 1.93 0.00 0.00 0.00
Maximum of Months 32.17 3.10 29.07 87.31 66.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.51 41.78 32.73 109.75 109.65 0.00 0.00 0.00
February 84.20 44.58 39.62 129.97 96.62 0.00 0.00 0.00
March 116.01 62.59 53.43 190.46 81.13 0.00 0.00 0.00
April 133.25 72.36 60.89 246.26 41.66 0.00 0.00 0.00
May 143.73 77.42 66.31 291.02 19.61 0.00 0.00 0.00
June 139.37 75.10 64.28 314.58 6.64 0.00 0.00 0.00
July 123.82 61.80 62.02 283.13 3.63 0.00 0.00 0.00
August 120.02 61.47 58.55 264.47 7.60 0.00 0.00 0.00
September 123.55 69.41 54.13 254.90 24.06 0.00 0.00 0.00
October 106.08 62.31 43.77 197.14 48.37 0.00 0.00 0.00
November 87.87 53.38 34.49 140.83 91.01 0.00 0.00 0.00
December 70.44 37.97 32.48 99.60 121.56 0.00 0.00 0.00
                 
Annual Sum or Average 110.34 60.06 50.28 210.52 54.09 0.00 0.00 0.00
Minimum of Months 70.44 37.97 32.48 99.60 3.63 0.00 0.00 0.00
Maximum of Months 143.73 77.42 66.31 314.58 121.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 144.91 110.27 34.64 238.60 86.06 0.00 0.00 0.00
February 133.49 94.37 39.12 227.98 74.39 0.00 0.00 0.00
March 100.44 54.82 45.62 183.54 62.97 0.00 0.00 0.00
April 68.33 22.52 45.80 145.72 31.42 0.00 0.00 0.00
May 49.52 5.12 44.41 119.89 13.90 0.00 0.00 0.00
June 43.21 1.50 41.71 125.66 4.38 0.00 0.00 0.00
July 43.63 2.43 41.19 127.10 2.24 0.00 0.00 0.00
August 53.60 11.04 42.56 146.21 5.04 0.00 0.00 0.00
September 84.88 41.47 43.41 200.61 17.17 0.00 0.00 0.00
October 121.14 81.38 39.76 238.12 35.80 0.00 0.00 0.00
November 149.90 114.80 35.10 259.19 69.84 0.00 0.00 0.00
December 149.46 112.95 36.51 242.44 94.17 0.00 0.00 0.00
                 
Annual Sum or Average 94.99 54.16 40.83 187.65 41.30 0.00 0.00 0.00
Minimum of Months 43.21 1.50 34.64 119.89 2.24 0.00 0.00 0.00
Maximum of Months 149.90 114.80 45.80 259.19 94.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.70 0.00 99.70 46.32 456.83 0.00 0.00 0.00
February 121.75 0.00 121.75 95.78 398.46 0.00 0.00 0.00
March 159.36 0.00 159.35 179.90 328.88 0.00 0.00 0.00
April 184.10 1.41 182.70 312.54 167.34 0.00 0.00 0.00
May 213.94 11.45 202.49 482.86 82.36 0.00 0.00 0.00
June 225.21 21.72 203.49 629.54 34.00 0.00 0.00 0.00
July 209.48 15.78 193.69 584.28 22.11 0.00 0.00 0.00
August 180.14 2.83 177.31 469.32 38.30 0.00 0.00 0.00
September 157.92 0.09 157.82 358.75 100.70 0.00 0.00 0.00
October 130.99 0.00 130.99 211.76 193.95 0.00 0.00 0.00
November 105.74 0.00 105.74 76.17 375.17 0.00 0.00 0.00
December 98.93 0.00 98.93 34.92 501.15 0.00 0.00 0.00
                 
Annual Sum or Average 157.44 4.46 152.98 291.18 224.12 0.00 0.00 0.00
Minimum of Months 98.93 0.00 98.93 34.92 22.11 0.00 0.00 0.00
Maximum of Months 225.21 21.72 203.49 629.54 501.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.70 0.00 99.70 41.06 477.59 0.00 0.00 0.00
February 121.75 0.00 121.75 89.21 415.82 0.00 0.00 0.00
March 159.36 0.00 159.35 171.44 342.44 0.00 0.00 0.00
April 184.10 1.41 182.70 303.11 174.68 0.00 0.00 0.00
May 213.94 11.45 202.49 472.32 86.39 0.00 0.00 0.00
June 225.21 21.72 203.49 618.21 36.22 0.00 0.00 0.00
July 209.48 15.78 193.69 572.86 24.30 0.00 0.00 0.00
August 180.14 2.83 177.31 458.51 41.10 0.00 0.00 0.00
September 157.92 0.09 157.82 349.90 105.98 0.00 0.00 0.00
October 130.99 0.00 130.99 204.33 202.95 0.00 0.00 0.00
November 105.74 0.00 105.74 70.54 390.80 0.00 0.00 0.00
December 98.93 0.00 98.93 30.00 523.54 0.00 0.00 0.00
                 
Annual Sum or Average 157.44 4.46 152.98 282.79 234.30 0.00 0.00 0.00
Minimum of Months 98.93 0.00 98.93 30.00 24.30 0.00 0.00 0.00
Maximum of Months 225.21 21.72 203.49 618.21 523.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.24 0.00 14.24 25.97 44.62 0.00 0.00 0.00
February 17.39 0.00 17.39 38.06 40.18 0.00 0.00 0.00
March 22.77 0.00 22.77 55.11 34.39 0.00 0.00 0.00
April 26.30 0.20 26.10 84.37 18.40 0.00 0.00 0.00
May 30.56 1.64 28.93 113.98 9.92 0.00 0.00 0.00
June 32.17 3.10 29.07 137.86 4.33 0.00 0.00 0.00
July 29.93 2.25 27.67 131.74 2.71 0.00 0.00 0.00
August 25.74 0.40 25.33 114.16 4.42 0.00 0.00 0.00
September 22.56 0.01 22.55 94.94 10.30 0.00 0.00 0.00
October 18.71 0.00 18.71 66.07 18.32 0.00 0.00 0.00
November 15.11 0.00 15.11 35.52 36.23 0.00 0.00 0.00
December 14.13 0.00 14.13 23.16 49.75 0.00 0.00 0.00
                 
Annual Sum or Average 22.49 0.64 21.86 76.94 22.71 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 23.16 2.71 0.00 0.00 0.00
Maximum of Months 32.17 3.10 29.07 137.86 49.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 140.40 75.33 65.07 278.06 162.72 0.00 0.00 0.00
February 191.00 109.08 81.92 396.55 145.04 0.00 0.00 0.00
March 236.48 130.90 105.58 509.24 124.84 0.00 0.00 0.00
April 285.97 159.83 126.14 690.11 68.38 0.00 0.00 0.00
May 294.36 161.00 133.36 776.48 37.30 0.00 0.00 0.00
June 293.75 164.07 129.68 850.14 16.17 0.00 0.00 0.00
July 264.00 138.92 125.08 787.53 10.19 0.00 0.00 0.00
August 251.37 129.54 121.83 739.06 16.56 0.00 0.00 0.00
September 250.06 143.79 106.27 691.30 38.53 0.00 0.00 0.00
October 189.90 102.43 87.48 493.07 68.39 0.00 0.00 0.00
November 169.19 98.02 71.17 362.61 131.22 0.00 0.00 0.00
December 140.36 73.54 66.82 268.31 180.92 0.00 0.00 0.00
                 
Annual Sum or Average 225.59 123.80 101.79 570.77 83.06 0.00 0.00 0.00
Minimum of Months 140.36 73.54 65.07 268.31 10.19 0.00 0.00 0.00
Maximum of Months 294.36 164.07 133.36 850.14 180.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.81 75.19 23.62 192.65 43.38 0.00 0.00 0.00
February 91.02 64.34 26.67 188.77 38.86 0.00 0.00 0.00
March 68.48 37.38 31.10 160.08 33.98 0.00 0.00 0.00
April 46.59 15.36 31.23 140.37 18.62 0.00 0.00 0.00
May 33.77 3.49 30.28 125.79 10.03 0.00 0.00 0.00
June 29.46 1.02 28.44 132.03 4.29 0.00 0.00 0.00
July 29.75 1.66 28.09 133.31 2.70 0.00 0.00 0.00
August 36.55 7.53 29.02 146.78 4.40 0.00 0.00 0.00
September 57.88 28.27 29.60 183.45 10.28 0.00 0.00 0.00
October 82.60 55.49 27.11 203.35 18.18 0.00 0.00 0.00
November 102.21 78.28 23.93 210.57 34.97 0.00 0.00 0.00
December 101.91 77.02 24.89 195.33 48.18 0.00 0.00 0.00
                 
Annual Sum or Average 64.77 36.93 27.84 167.55 22.24 0.00 0.00 0.00
Minimum of Months 29.46 1.02 23.62 125.79 2.70 0.00 0.00 0.00
Maximum of Months 102.21 78.28 31.23 210.57 48.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.04 0.00 18.04 6.72 86.94 0.00 0.00 0.00
February 22.03 0.00 22.03 14.58 77.13 0.00 0.00 0.00
March 28.83 0.00 28.83 28.44 64.59 0.00 0.00 0.00
April 33.31 0.25 33.05 49.71 35.44 0.00 0.00 0.00
May 38.71 2.07 36.64 79.06 18.48 0.00 0.00 0.00
June 40.75 3.93 36.82 104.54 8.25 0.00 0.00 0.00
July 37.90 2.86 35.04 96.32 6.16 0.00 0.00 0.00
August 32.59 0.51 32.08 75.74 9.72 0.00 0.00 0.00
September 28.57 0.02 28.55 57.25 23.32 0.00 0.00 0.00
October 23.70 0.00 23.70 32.12 41.96 0.00 0.00 0.00
November 19.13 0.00 19.13 10.49 74.74 0.00 0.00 0.00
December 17.90 0.00 17.90 5.07 94.45 0.00 0.00 0.00
                 
Annual Sum or Average 28.49 0.81 27.68 46.84 44.94 0.00 0.00 0.00
Minimum of Months 17.90 0.00 17.90 5.07 6.16 0.00 0.00 0.00
Maximum of Months 40.75 3.93 36.82 104.54 94.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.14 0.00 16.14 6.01 77.79 0.00 0.00 0.00
February 19.71 0.00 19.71 13.05 69.01 0.00 0.00 0.00
March 25.80 0.00 25.80 25.45 57.79 0.00 0.00 0.00
April 29.80 0.23 29.57 44.47 31.71 0.00 0.00 0.00
May 34.63 1.85 32.78 70.74 16.53 0.00 0.00 0.00
June 36.46 3.52 32.94 93.53 7.38 0.00 0.00 0.00
July 33.91 2.55 31.35 86.18 5.51 0.00 0.00 0.00
August 29.16 0.46 28.70 67.77 8.69 0.00 0.00 0.00
September 25.56 0.01 25.55 51.22 20.87 0.00 0.00 0.00
October 21.20 0.00 21.20 28.74 37.55 0.00 0.00 0.00
November 17.12 0.00 17.12 9.38 66.87 0.00 0.00 0.00
December 16.01 0.00 16.01 4.54 84.50 0.00 0.00 0.00
                 
Annual Sum or Average 25.49 0.72 24.76 41.91 40.21 0.00 0.00 0.00
Minimum of Months 16.01 0.00 16.01 4.54 5.51 0.00 0.00 0.00
Maximum of Months 36.46 3.52 32.94 93.53 84.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 368.88 280.70 88.18 611.84 230.05 0.00 0.00 0.00
February 339.80 240.22 99.58 580.80 205.23 0.00 0.00 0.00
March 255.67 139.55 116.12 461.86 182.14 0.00 0.00 0.00
April 173.93 57.34 116.59 355.41 107.80 0.00 0.00 0.00
May 126.07 13.03 113.04 280.69 58.08 0.00 0.00 0.00
June 109.99 3.82 106.17 288.31 25.19 0.00 0.00 0.00
July 111.05 6.20 104.86 291.00 18.93 0.00 0.00 0.00
August 136.44 28.10 108.34 344.76 29.74 0.00 0.00 0.00
September 216.07 105.56 110.51 495.18 68.20 0.00 0.00 0.00
October 308.37 207.15 101.22 595.51 117.70 0.00 0.00 0.00
November 381.58 292.24 89.34 657.14 197.00 0.00 0.00 0.00
December 380.47 287.53 92.93 623.20 246.24 0.00 0.00 0.00
                 
Annual Sum or Average 241.80 137.88 103.92 464.71 123.46 0.00 0.00 0.00
Minimum of Months 109.99 3.82 88.18 280.69 18.93 0.00 0.00 0.00
Maximum of Months 381.58 292.24 116.59 657.14 246.24 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133851E+10 0.101855E+10 0.319964E+09 0.221953E+10 0.808166E+09
February 0.111368E+10 0.787299E+09 0.326377E+09 0.191011E+10 0.644466E+09
March 0.927717E+09 0.506385E+09 0.421331E+09 0.170093E+10 0.622351E+09
April 0.610757E+09 0.201344E+09 0.409413E+09 0.126525E+10 0.357649E+09
May 0.457442E+09 47283302.53 0.410158E+09 0.101623E+10 0.209540E+09
June 0.386227E+09 13409483.47 0.372818E+09 0.988886E+09 93364697.82
July 0.402961E+09 22480320.82 0.380480E+09 0.104030E+10 71669863.83
August 0.495070E+09 0.101948E+09 0.393122E+09 0.124049E+10 0.110026E+09
September 0.758725E+09 0.370674E+09 0.388050E+09 0.173506E+10 0.240639E+09
October 0.111893E+10 0.751654E+09 0.367276E+09 0.217132E+10 0.412347E+09
November 0.133994E+10 0.102622E+10 0.313719E+09 0.231292E+10 0.669464E+09
December 0.138055E+10 0.104333E+10 0.337221E+09 0.225010E+10 0.874982E+09
           
Annual Sum or Average 0.103305E+11 0.589058E+10 0.443993E+10 0.198511E+11 0.511466E+10
Minimum of Months 0.386227E+09 13409483.47 0.313719E+09 0.988886E+09 71669863.83
Maximum of Months 0.138055E+10 0.104333E+10 0.421331E+09 0.231292E+10 0.874982E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.376916E+10 0.286816E+10 0.900997E+09 0.626160E+10 0.226029E+10
February 0.313604E+10 0.221698E+10 0.919056E+09 0.539578E+10 0.178618E+10
March 0.261239E+10 0.142595E+10 0.118644E+10 0.483543E+10 0.170015E+10
April 0.171985E+10 0.566971E+09 0.115288E+10 0.366405E+10 0.914551E+09
May 0.128813E+10 0.133147E+09 0.115498E+10 0.302519E+10 0.493786E+09
June 0.108759E+10 37760221.31 0.104983E+10 0.297082E+10 0.202228E+09
July 0.113471E+10 63303101.21 0.107141E+10 0.311570E+10 0.138843E+09
August 0.139408E+10 0.287079E+09 0.110700E+10 0.364806E+10 0.242261E+09
September 0.213652E+10 0.104379E+10 0.109272E+10 0.497284E+10 0.585882E+09
October 0.315083E+10 0.211661E+10 0.103422E+10 0.616741E+10 0.107342E+10
November 0.377317E+10 0.288976E+10 0.883412E+09 0.652097E+10 0.183486E+10
December 0.388755E+10 0.293795E+10 0.949592E+09 0.634295E+10 0.245251E+10
           
Annual Sum or Average 0.290900E+11 0.165875E+11 0.125025E+11 0.569208E+11 0.136850E+11
Minimum of Months 0.108759E+10 37760221.31 0.883412E+09 0.297082E+10 0.138843E+09
Maximum of Months 0.388755E+10 0.293795E+10 0.118644E+10 0.652097E+10 0.245251E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.489635E+10 0.372591E+10 0.117045E+10 0.819780E+10 0.311826E+10
February 0.407389E+10 0.287999E+10 0.119391E+10 0.706274E+10 0.247049E+10
March 0.339364E+10 0.185239E+10 0.154126E+10 0.630661E+10 0.237705E+10
April 0.223418E+10 0.736528E+09 0.149766E+10 0.475394E+10 0.131797E+10
May 0.167335E+10 0.172965E+09 0.150038E+10 0.388029E+10 0.738798E+09
June 0.141284E+10 49052676.43 0.136379E+10 0.381216E+10 0.309549E+09
July 0.147405E+10 82234331.09 0.139182E+10 0.399742E+10 0.227910E+09
August 0.181099E+10 0.372932E+09 0.143806E+10 0.471761E+10 0.367158E+09
September 0.277546E+10 0.135595E+10 0.141951E+10 0.650169E+10 0.830339E+09
October 0.409311E+10 0.274959E+10 0.134352E+10 0.806897E+10 0.149962E+10
November 0.490157E+10 0.375397E+10 0.114760E+10 0.854266E+10 0.253428E+10
December 0.505014E+10 0.381657E+10 0.123357E+10 0.829438E+10 0.337949E+10
           
Annual Sum or Average 0.377896E+11 0.215481E+11 0.162415E+11 0.741363E+11 0.191709E+11
Minimum of Months 0.141284E+10 49052676.43 0.114760E+10 0.381216E+10 0.227910E+09
Maximum of Months 0.505014E+10 0.381657E+10 0.154126E+10 0.854266E+10 0.337949E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.264647E+09 0.201384E+09 63262840.52 0.443497E+09 0.154070E+09
February 0.220193E+09 0.155663E+09 64530892.66 0.382096E+09 0.121328E+09
March 0.183426E+09 0.100121E+09 83305334.62 0.339304E+09 0.116301E+09
April 0.120758E+09 39809150.64 80948993.88 0.257191E+09 58679249.69
May 90445255.74 9348720.99 81096534.75 0.214236E+09 28482567.25
June 76364923.40 2651285.19 73713638.21 0.215526E+09 9479105.66
July 79673300.15 4444745.52 75228554.63 0.226512E+09 5298966.64
August 97884800.12 20156891.76 77727908.36 0.263094E+09 10880363.26
September 0.150014E+09 73288714.47 76725115.99 0.354260E+09 32964548.88
October 0.221232E+09 0.148615E+09 72617473.30 0.437859E+09 67045788.10
November 0.264929E+09 0.202901E+09 62028222.36 0.463547E+09 0.122662E+09
December 0.272959E+09 0.206285E+09 66674853.38 0.450931E+09 0.168417E+09
           
Annual Sum or Average 0.204253E+10 0.116467E+10 0.877860E+09 0.404805E+10 0.895608E+09
Minimum of Months 76364923.40 2651285.19 62028222.36 0.214236E+09 5298966.64
Maximum of Months 0.272959E+09 0.206285E+09 83305334.62 0.463547E+09 0.168417E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.199569E+09 0.111916E+09 87652226.75 0.282747E+09 0.308841E+09
February 0.203701E+09 0.107840E+09 95860252.20 0.306170E+09 0.244162E+09
March 0.310729E+09 0.167634E+09 0.143095E+09 0.507063E+09 0.222345E+09
April 0.345384E+09 0.187569E+09 0.157815E+09 0.641198E+09 0.108015E+09
May 0.384974E+09 0.207370E+09 0.177604E+09 0.786054E+09 52611106.98
June 0.361256E+09 0.194651E+09 0.166604E+09 0.823288E+09 17579594.01
July 0.331644E+09 0.165525E+09 0.166119E+09 0.766366E+09 9706423.95
August 0.321462E+09 0.164640E+09 0.156821E+09 0.713690E+09 20160533.27
September 0.320234E+09 0.179923E+09 0.140311E+09 0.662817E+09 62049983.15
October 0.284129E+09 0.166893E+09 0.117236E+09 0.526388E+09 0.129660E+09
November 0.227771E+09 0.138362E+09 89409581.84 0.356268E+09 0.247203E+09
December 0.188677E+09 0.101695E+09 86982465.69 0.254624E+09 0.341424E+09
           
Annual Sum or Average 0.347953E+10 0.189402E+10 0.158551E+10 0.662667E+10 0.176376E+10
Minimum of Months 0.188677E+09 0.101695E+09 86982465.69 0.254624E+09 9706423.95
Maximum of Months 0.384974E+09 0.207370E+09 0.177604E+09 0.823288E+09 0.341424E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38150281.98 0.00 38150281.98 19856655.36 0.165678E+09
February 42077264.71 0.00 42077264.71 34131358.17 0.131286E+09
March 60976374.93 622.69 60975752.24 67510932.38 0.121408E+09
April 68172669.75 520702.85 67651966.90 0.111306E+09 58286976.38
May 81861711.97 4381309.74 77480402.23 0.178674E+09 27946524.53
June 83395339.51 8041631.04 75353708.48 0.227140E+09 9593761.28
July 80155107.15 6039143.52 74115963.63 0.219214E+09 5560937.87
August 68930604.05 1082745.78 67847858.27 0.174350E+09 11326064.83
September 58475990.39 34250.14 58441740.25 0.126362E+09 34787586.16
October 50121178.72 0.00 50121178.72 77550107.39 72379334.09
November 39157332.20 0.00 39157332.20 28749757.69 0.133558E+09
December 37854815.76 0.00 37854815.76 15822385.76 0.183459E+09
           
Annual Sum or Average 0.709329E+09 20100405.76 0.689228E+09 0.128067E+10 0.955270E+09
Minimum of Months 37854815.76 0.00 37854815.76 15822385.76 5560937.87
Maximum of Months 83395339.51 8041631.04 77480402.23 0.227140E+09 0.183459E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.199569E+09 0.111916E+09 87652226.75 0.292824E+09 0.300968E+09
February 0.203701E+09 0.107840E+09 95860252.20 0.313931E+09 0.239623E+09
March 0.310729E+09 0.167634E+09 0.143095E+09 0.511301E+09 0.222070E+09
April 0.345384E+09 0.187569E+09 0.157815E+09 0.641230E+09 0.110776E+09
May 0.384974E+09 0.207370E+09 0.177604E+09 0.782828E+09 54947073.63
June 0.361256E+09 0.194651E+09 0.166604E+09 0.818685E+09 18385212.64
July 0.331644E+09 0.165525E+09 0.166119E+09 0.761943E+09 10510082.36
August 0.321462E+09 0.164640E+09 0.156821E+09 0.711344E+09 21629001.65
September 0.320234E+09 0.179923E+09 0.140311E+09 0.663435E+09 64854276.47
October 0.284129E+09 0.166893E+09 0.117236E+09 0.529384E+09 0.132940E+09
November 0.227771E+09 0.138362E+09 89409581.84 0.363999E+09 0.242894E+09
December 0.188677E+09 0.101695E+09 86982465.69 0.265084E+09 0.333066E+09
           
Annual Sum or Average 0.347953E+10 0.189402E+10 0.158551E+10 0.665599E+10 0.175266E+10
Minimum of Months 0.188677E+09 0.101695E+09 86982465.69 0.265084E+09 10510082.36
Maximum of Months 0.384974E+09 0.207370E+09 0.177604E+09 0.818685E+09 0.333066E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.211676E+09 0.161075E+09 50600209.40 0.332628E+09 0.167872E+09
February 0.176120E+09 0.124505E+09 51614449.40 0.284843E+09 0.135226E+09
March 0.146712E+09 80080954.26 66631016.58 0.248160E+09 0.131315E+09
April 96587307.00 31840988.20 64746318.81 0.183503E+09 78783562.79
May 72341817.76 7477489.72 64864328.03 0.144819E+09 48556494.73
June 61079791.60 2120606.42 58959185.18 0.141231E+09 24561803.36
July 63725966.74 3555089.41 60170877.34 0.148037E+09 21605282.19
August 78292269.87 16122307.11 62169962.76 0.180400E+09 29847440.57
September 0.119987E+09 58619313.77 61367888.37 0.261378E+09 54375008.18
October 0.176951E+09 0.118868E+09 58082427.61 0.327642E+09 88112614.27
November 0.211901E+09 0.162288E+09 49612711.26 0.349028E+09 0.136804E+09
December 0.218324E+09 0.164995E+09 53329276.94 0.336982E+09 0.178118E+09
           
Annual Sum or Average 0.163370E+10 0.931549E+09 0.702149E+09 0.293865E+10 0.109518E+10
Minimum of Months 61079791.60 2120606.42 49612711.26 0.141231E+09 21605282.19
Maximum of Months 0.218324E+09 0.164995E+09 66631016.58 0.349028E+09 0.178118E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 30524271.22 0.00 30524271.22 15338857.48 0.135043E+09
February 33666273.83 0.00 33666273.83 27688880.95 0.105565E+09
March 48787566.16 498.22 48787067.94 56423928.54 95527990.29
April 54545365.14 416617.50 54128747.64 94340445.90 43854293.75
May 65498050.57 3505512.41 61992538.16 0.150491E+09 19957755.66
June 66725115.23 6434157.60 60290957.63 0.190873E+09 6183156.33
July 64132585.73 4831955.24 59300630.50 0.184310E+09 3257287.05
August 55151792.95 866311.44 54285481.51 0.147877E+09 7388149.73
September 46786993.37 27403.74 46759589.63 0.107600E+09 24488404.01
October 40102258.05 0.00 40102258.05 66180254.43 54175749.27
November 31330018.18 0.00 31330018.18 24084530.18 0.105714E+09
December 30287866.91 0.00 30287866.91 11643693.77 0.150182E+09
           
Annual Sum or Average 0.567538E+09 16082456.15 0.551456E+09 0.107685E+10 0.751336E+09
Minimum of Months 30287866.91 0.00 30287866.91 11643693.77 3257287.05
Maximum of Months 66725115.23 6434157.60 61992538.16 0.190873E+09 0.150182E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.188030E+09 0.100884E+09 87146214.64 0.249692E+09 0.296197E+09
February 0.231052E+09 0.131949E+09 99102822.95 0.343979E+09 0.230435E+09
March 0.316722E+09 0.175314E+09 0.141408E+09 0.506865E+09 0.207962E+09
April 0.370649E+09 0.207157E+09 0.163492E+09 0.683682E+09 0.100587E+09
May 0.394240E+09 0.215632E+09 0.178609E+09 0.803469E+09 49031196.87
June 0.380726E+09 0.212651E+09 0.168074E+09 0.861728E+09 16651440.72
July 0.353575E+09 0.186053E+09 0.167521E+09 0.808451E+09 9373059.28
August 0.336653E+09 0.173487E+09 0.163166E+09 0.745151E+09 19287338.38
September 0.324095E+09 0.186366E+09 0.137729E+09 0.665908E+09 57848610.90
October 0.254335E+09 0.137178E+09 0.117157E+09 0.462657E+09 0.123352E+09
November 0.219280E+09 0.127042E+09 92237110.17 0.325242E+09 0.233416E+09
December 0.187982E+09 98496300.25 89485454.53 0.240078E+09 0.326257E+09
           
Annual Sum or Average 0.355734E+10 0.195221E+10 0.160513E+10 0.669690E+10 0.167040E+10
Minimum of Months 0.187982E+09 98496300.25 87146214.64 0.240078E+09 9373059.28
Maximum of Months 0.394240E+09 0.215632E+09 0.178609E+09 0.861728E+09 0.326257E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.264647E+09 0.201384E+09 63262840.52 0.442492E+09 0.153260E+09
February 0.220193E+09 0.155663E+09 64530892.66 0.380026E+09 0.121088E+09
March 0.183426E+09 0.100121E+09 83305334.62 0.337077E+09 0.115632E+09
April 0.120758E+09 39809150.64 80948993.88 0.255190E+09 58343507.18
May 90445255.74 9348720.99 81096534.75 0.212920E+09 28022920.22
June 76364923.40 2651285.19 73713638.21 0.214392E+09 9218580.41
July 79673300.15 4444745.52 75228554.63 0.225498E+09 5111800.00
August 97884800.12 20156891.76 77727908.36 0.262365E+09 10661463.20
September 0.150014E+09 73288714.47 76725115.99 0.353477E+09 32440731.10
October 0.221232E+09 0.148615E+09 72617473.30 0.437458E+09 65863221.23
November 0.264929E+09 0.202901E+09 62028222.36 0.462513E+09 0.121763E+09
December 0.272959E+09 0.206285E+09 66674853.38 0.449833E+09 0.167882E+09
           
Annual Sum or Average 0.204253E+10 0.116467E+10 0.877860E+09 0.403324E+10 0.889287E+09
Minimum of Months 76364923.40 2651285.19 62028222.36 0.212920E+09 5111800.00
Maximum of Months 0.272959E+09 0.206285E+09 83305334.62 0.462513E+09 0.167882E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38150281.98 0.00 38150281.98 19036196.05 0.164704E+09
February 42077264.71 0.00 42077264.71 32562206.62 0.131086E+09
March 60976374.93 622.69 60975752.24 65622577.41 0.120478E+09
April 68172669.75 520702.85 67651966.90 0.108651E+09 57712991.73
May 81861711.97 4381309.74 77480402.23 0.175602E+09 27459914.72
June 83395339.51 8041631.04 75353708.48 0.224547E+09 9391855.15
July 80155107.15 6039143.52 74115963.63 0.216911E+09 5411083.05
August 68930604.05 1082745.78 67847858.27 0.172164E+09 11106215.29
September 58475990.39 34250.14 58441740.25 0.124070E+09 34391301.38
October 50121178.72 0.00 50121178.72 76703044.37 70126592.53
November 39157332.20 0.00 39157332.20 27681084.37 0.131887E+09
December 37854815.76 0.00 37854815.76 14809505.12 0.182916E+09
           
Annual Sum or Average 0.709329E+09 20100405.76 0.689228E+09 0.125836E+10 0.946671E+09
Minimum of Months 37854815.76 0.00 37854815.76 14809505.12 5411083.05
Maximum of Months 83395339.51 8041631.04 77480402.23 0.224547E+09 0.182916E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.188030E+09 0.100884E+09 87146214.64 0.259053E+09 0.286643E+09
February 0.231052E+09 0.131949E+09 99102822.95 0.351739E+09 0.224925E+09
March 0.316722E+09 0.175314E+09 0.141408E+09 0.511789E+09 0.206696E+09
April 0.370649E+09 0.207157E+09 0.163492E+09 0.682730E+09 0.102934E+09
May 0.394240E+09 0.215632E+09 0.178609E+09 0.796406E+09 51190841.56
June 0.380726E+09 0.212651E+09 0.168074E+09 0.853650E+09 17380499.47
July 0.353575E+09 0.186053E+09 0.167521E+09 0.801064E+09 10131583.37
August 0.336653E+09 0.173487E+09 0.163166E+09 0.739518E+09 20562069.76
September 0.324095E+09 0.186366E+09 0.137729E+09 0.662796E+09 60312436.10
October 0.254335E+09 0.137178E+09 0.117157E+09 0.465811E+09 0.125145E+09
November 0.219280E+09 0.127042E+09 92237110.17 0.333129E+09 0.227469E+09
December 0.187982E+09 98496300.25 89485454.53 0.249004E+09 0.315991E+09
           
Annual Sum or Average 0.355734E+10 0.195221E+10 0.160513E+10 0.670669E+10 0.164938E+10
Minimum of Months 0.187982E+09 98496300.25 87146214.64 0.249004E+09 10131583.37
Maximum of Months 0.394240E+09 0.215632E+09 0.178609E+09 0.853650E+09 0.315991E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 48314924.98 0.00 48314924.98 21951753.34 0.223193E+09
February 53288200.83 0.00 53288200.83 41188179.67 0.176123E+09
March 77222731.45 788.60 77221942.86 86275536.82 0.160562E+09
April 86336384.78 659437.31 85676947.47 0.143067E+09 80331960.39
May 0.103673E+09 5548652.34 98124040.68 0.225780E+09 42780857.77
June 0.105615E+09 10184218.31 95430717.23 0.281494E+09 18643635.57
July 0.101511E+09 7648194.22 93863191.48 0.270515E+09 13017605.97
August 87296260.75 1371229.21 85925031.54 0.214633E+09 21690980.39
September 74056152.20 43375.64 74012776.56 0.157746E+09 54278802.28
October 63475310.37 0.00 63475310.37 96235082.76 0.100906E+09
November 49590290.55 0.00 49590290.55 33106384.39 0.183127E+09
December 47940735.65 0.00 47940735.65 16660248.60 0.245684E+09
           
Annual Sum or Average 0.898320E+09 25455895.63 0.872864E+09 0.158865E+10 0.132034E+10
Minimum of Months 47940735.65 0.00 47940735.65 16660248.60 13017605.97
Maximum of Months 0.105615E+09 10184218.31 98124040.68 0.281494E+09 0.245684E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 17810881.91 0.00 17810881.91 8092325.23 82278130.65
February 19644237.32 0.00 19644237.32 15183668.49 64926048.81
March 28467496.36 290.71 28467205.65 31804735.26 59189794.56
April 31827166.34 243095.90 31584070.44 52740558.82 29613686.89
May 38218047.40 2045463.01 36172584.39 83231728.01 15770795.59
June 38934038.41 3754324.56 35179713.85 0.103770E+09 6872816.04
July 37421300.03 2819441.08 34601858.95 99723193.55 4798828.58
August 32181016.37 505491.87 31675524.50 79122464.71 7996193.53
September 27300164.13 15990.06 27284174.07 58151851.54 20009414.03
October 23399627.71 0.00 23399627.71 35476236.29 37198058.21
November 18281034.47 0.00 18281034.47 12204384.11 67508367.73
December 17672940.23 0.00 17672940.23 6141657.48 90569220.39
           
Annual Sum or Average 0.331158E+09 9384097.17 0.321774E+09 0.585643E+09 0.486731E+09
Minimum of Months 17672940.23 0.00 17672940.23 6141657.48 4798828.58
Maximum of Months 38934038.41 3754324.56 36172584.39 0.103770E+09 90569220.39



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.123483E+09 93965136.81 29518186.46 0.208062E+09 74208256.76
February 0.102741E+09 72631544.99 30109854.47 0.179280E+09 58787684.08
March 85586035.36 46716101.92 38869933.44 0.159584E+09 56726255.41
April 56345263.62 18574789.27 37770474.34 0.120809E+09 30581664.99
May 42201391.86 4362075.54 37839316.32 99068520.49 16773713.69
June 35631565.53 1237078.98 34394486.55 97135853.06 7105074.66
July 37175240.79 2073900.35 35101340.44 0.101959E+09 4969042.18
August 45672653.29 9405124.47 36267528.82 0.119897E+09 8265459.94
September 69995848.78 34196218.84 35799629.94 0.164349E+09 19842402.80
October 0.103226E+09 69343086.93 33883020.42 0.204220E+09 35470175.32
November 0.123615E+09 94672755.62 28942118.60 0.216737E+09 60687445.81
December 0.127362E+09 96251569.08 31110217.91 0.211414E+09 80527161.09
           
Annual Sum or Average 0.953035E+09 0.543429E+09 0.409606E+09 0.188252E+10 0.453944E+09
Minimum of Months 35631565.53 1237078.98 28942118.60 97135853.06 4969042.18
Maximum of Months 0.127362E+09 96251569.08 38869933.44 0.216737E+09 80527161.09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.335159E+09 0.255041E+09 80118395.85 0.564722E+09 0.201416E+09
February 0.278861E+09 0.197137E+09 81724303.88 0.486603E+09 0.159562E+09
March 0.232298E+09 0.126797E+09 0.105501E+09 0.433143E+09 0.153967E+09
April 0.152933E+09 50415777.47 0.102517E+09 0.327900E+09 83004985.72
May 0.114543E+09 11839565.27 0.102704E+09 0.268892E+09 45527289.95
June 96711357.13 3357685.40 93353671.73 0.263647E+09 19284625.94
July 0.100901E+09 5628989.76 95272217.78 0.276739E+09 13486996.88
August 0.123965E+09 25527431.58 98437491.58 0.325426E+09 22434148.93
September 0.189983E+09 92815532.61 97167518.31 0.446076E+09 53856339.88
October 0.280177E+09 0.188211E+09 91965448.03 0.554293E+09 96273311.07
November 0.335516E+09 0.256961E+09 78554829.85 0.588269E+09 0.164718E+09
December 0.345686E+09 0.261246E+09 84439494.85 0.573822E+09 0.218567E+09
           
Annual Sum or Average 0.258673E+10 0.147498E+10 0.111175E+10 0.510953E+10 0.123210E+10
Minimum of Months 96711357.13 3357685.40 78554829.85 0.263647E+09 13486996.88
Maximum of Months 0.345686E+09 0.261246E+09 0.105501E+09 0.588269E+09 0.218567E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.264647E+09 0.201384E+09 63262840.52 0.442693E+09 0.151163E+09
February 0.220193E+09 0.155663E+09 64530892.66 0.381245E+09 0.118857E+09
March 0.183426E+09 0.100121E+09 83305334.62 0.338079E+09 0.113987E+09
April 0.120758E+09 39809150.64 80948993.88 0.255849E+09 56998641.92
May 90445255.74 9348720.99 81096534.75 0.213449E+09 27163104.91
June 76364923.40 2651285.19 73713638.21 0.214921E+09 8807899.78
July 79673300.15 4444745.52 75228554.63 0.225452E+09 4883649.59
August 97884800.12 20156891.76 77727908.36 0.261874E+09 10180111.94
September 0.150014E+09 73288714.47 76725115.99 0.352416E+09 31699326.13
October 0.221232E+09 0.148615E+09 72617473.30 0.436206E+09 65281632.02
November 0.264929E+09 0.202901E+09 62028222.36 0.462754E+09 0.119931E+09
December 0.272959E+09 0.206285E+09 66674853.38 0.450728E+09 0.165415E+09
           
Annual Sum or Average 0.204253E+10 0.116467E+10 0.877860E+09 0.403567E+10 0.874368E+09
Minimum of Months 76364923.40 2651285.19 62028222.36 0.213449E+09 4883649.59
Maximum of Months 0.272959E+09 0.206285E+09 83305334.62 0.462754E+09 0.165415E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.199569E+09 0.111916E+09 87652226.75 0.282537E+09 0.302166E+09
February 0.203701E+09 0.107840E+09 95860252.20 0.305651E+09 0.238689E+09
March 0.310729E+09 0.167634E+09 0.143095E+09 0.505374E+09 0.217391E+09
April 0.345384E+09 0.187569E+09 0.157815E+09 0.638279E+09 0.104813E+09
May 0.384974E+09 0.207370E+09 0.177604E+09 0.782566E+09 50094629.74
June 0.361256E+09 0.194651E+09 0.166604E+09 0.819920E+09 16422445.05
July 0.331644E+09 0.165525E+09 0.166119E+09 0.762765E+09 8948190.94
August 0.321462E+09 0.164640E+09 0.156821E+09 0.710512E+09 18898015.75
September 0.320234E+09 0.179923E+09 0.140311E+09 0.659659E+09 59673680.19
October 0.284129E+09 0.166893E+09 0.117236E+09 0.524638E+09 0.125972E+09
November 0.227771E+09 0.138362E+09 89409581.84 0.355900E+09 0.240953E+09
December 0.188677E+09 0.101695E+09 86982465.69 0.255067E+09 0.334277E+09
           
Annual Sum or Average 0.347953E+10 0.189402E+10 0.158551E+10 0.660287E+10 0.171830E+10
Minimum of Months 0.188677E+09 0.101695E+09 86982465.69 0.255067E+09 8948190.94
Maximum of Months 0.384974E+09 0.207370E+09 0.177604E+09 0.819920E+09 0.334277E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38150281.98 0.00 38150281.98 20952185.86 0.161559E+09
February 42077264.71 0.00 42077264.71 35053767.24 0.128062E+09
March 60976374.93 622.69 60975752.24 68155986.87 0.118891E+09
April 68172669.75 520702.85 67651966.90 0.110988E+09 56871233.80
May 81861711.97 4381309.74 77480402.23 0.178216E+09 26777611.55
June 83395339.51 8041631.04 75353708.48 0.226318E+09 8991743.41
July 80155107.15 6039143.52 74115963.63 0.218093E+09 5159155.51
August 68930604.05 1082745.78 67847858.27 0.173791E+09 10683800.28
September 58475990.39 34250.14 58441740.25 0.125840E+09 33484938.82
October 50121178.72 0.00 50121178.72 77757371.77 70581695.06
November 39157332.20 0.00 39157332.20 29945365.84 0.129730E+09
December 37854815.76 0.00 37854815.76 16913177.42 0.179195E+09
           
Annual Sum or Average 0.709329E+09 20100405.76 0.689228E+09 0.128202E+10 0.929987E+09
Minimum of Months 37854815.76 0.00 37854815.76 16913177.42 5159155.51
Maximum of Months 83395339.51 8041631.04 77480402.23 0.226318E+09 0.179195E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.199569E+09 0.111916E+09 87652226.75 0.293967E+09 0.293690E+09
February 0.203701E+09 0.107840E+09 95860252.20 0.314416E+09 0.233746E+09
March 0.310729E+09 0.167634E+09 0.143095E+09 0.510115E+09 0.217290E+09
April 0.345384E+09 0.187569E+09 0.157815E+09 0.638311E+09 0.107979E+09
May 0.384974E+09 0.207370E+09 0.177604E+09 0.779469E+09 52517272.16
June 0.361256E+09 0.194651E+09 0.166604E+09 0.815402E+09 17199976.10
July 0.331644E+09 0.165525E+09 0.166119E+09 0.758345E+09 9727244.87
August 0.321462E+09 0.164640E+09 0.156821E+09 0.708347E+09 20360428.94
September 0.320234E+09 0.179923E+09 0.140311E+09 0.660699E+09 62364018.11
October 0.284129E+09 0.166893E+09 0.117236E+09 0.528027E+09 0.129560E+09
November 0.227771E+09 0.138362E+09 89409581.84 0.365028E+09 0.235889E+09
December 0.188677E+09 0.101695E+09 86982465.69 0.266779E+09 0.325587E+09
           
Annual Sum or Average 0.347953E+10 0.189402E+10 0.158551E+10 0.663891E+10 0.170591E+10
Minimum of Months 0.188677E+09 0.101695E+09 86982465.69 0.266779E+09 9727244.87
Maximum of Months 0.384974E+09 0.207370E+09 0.177604E+09 0.815402E+09 0.325587E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.388131E+09 0.295350E+09 92781026.97 0.639061E+09 0.230497E+09
February 0.322935E+09 0.228294E+09 94640747.13 0.551540E+09 0.179961E+09
March 0.269012E+09 0.146837E+09 0.122175E+09 0.491587E+09 0.168667E+09
April 0.177103E+09 58383939.91 0.118719E+09 0.377706E+09 81451176.35
May 0.132647E+09 13710796.54 0.118936E+09 0.321122E+09 37242599.53
June 0.111996E+09 3888364.17 0.108108E+09 0.325717E+09 11342579.04
July 0.116849E+09 6518645.87 0.110330E+09 0.340427E+09 5987443.32
August 0.143557E+09 29562016.22 0.113995E+09 0.391607E+09 13507017.71
September 0.220010E+09 0.107485E+09 0.112525E+09 0.519977E+09 44497020.39
October 0.324458E+09 0.217958E+09 0.106500E+09 0.637775E+09 95889671.15
November 0.388544E+09 0.297574E+09 90970340.96 0.671810E+09 0.181013E+09
December 0.400321E+09 0.302536E+09 97785071.28 0.649340E+09 0.252232E+09
           
Annual Sum or Average 0.299556E+10 0.170810E+10 0.128747E+10 0.591767E+10 0.130229E+10
Minimum of Months 0.111996E+09 3888364.17 90970340.96 0.321122E+09 5987443.32
Maximum of Months 0.400321E+09 0.302536E+09 0.122175E+09 0.671810E+09 0.252232E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.267042E+09 0.00 0.267042E+09 0.124070E+09 0.122357E+10
February 0.294530E+09 0.00 0.294530E+09 0.231711E+09 0.963955E+09
March 0.426818E+09 4358.67 0.426814E+09 0.481857E+09 0.880880E+09
April 0.477191E+09 3644781.91 0.473546E+09 0.810103E+09 0.433751E+09
May 0.573010E+09 30668006.66 0.542342E+09 0.129329E+10 0.220586E+09
June 0.583745E+09 56289285.32 0.527456E+09 0.163177E+10 88130964.84
July 0.561065E+09 42272403.62 0.518792E+09 0.156493E+10 59227900.93
August 0.482496E+09 7578933.41 0.474917E+09 0.125703E+10 0.102581E+09
September 0.409316E+09 239741.89 0.409077E+09 0.929887E+09 0.261022E+09
October 0.350835E+09 0.00 0.350835E+09 0.567186E+09 0.519487E+09
November 0.274091E+09 0.00 0.274091E+09 0.197429E+09 0.972434E+09
December 0.264974E+09 0.00 0.264974E+09 93518163.12 0.134228E+10
           
Annual Sum or Average 0.496511E+10 0.140698E+09 0.482442E+10 0.918278E+10 0.706791E+10
Minimum of Months 0.264974E+09 0.00 0.264974E+09 93518163.12 59227900.93
Maximum of Months 0.583745E+09 56289285.32 0.542342E+09 0.163177E+10 0.134228E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.267042E+09 0.00 0.267042E+09 0.109983E+09 0.127917E+10
February 0.294530E+09 0.00 0.294530E+09 0.215823E+09 0.100595E+10
March 0.426818E+09 4358.67 0.426814E+09 0.459187E+09 0.917191E+09
April 0.477191E+09 3644781.91 0.473546E+09 0.785673E+09 0.452764E+09
May 0.573010E+09 30668006.66 0.542342E+09 0.126506E+10 0.231378E+09
June 0.583745E+09 56289285.32 0.527456E+09 0.160240E+10 93874021.16
July 0.561065E+09 42272403.62 0.518792E+09 0.153435E+10 65092510.40
August 0.482496E+09 7578933.41 0.474917E+09 0.122808E+10 0.110078E+09
September 0.409316E+09 239741.89 0.409077E+09 0.906937E+09 0.274710E+09
October 0.350835E+09 0.00 0.350835E+09 0.547288E+09 0.543581E+09
November 0.274091E+09 0.00 0.274091E+09 0.182845E+09 0.101295E+10
December 0.264974E+09 0.00 0.264974E+09 80340805.53 0.140226E+10
           
Annual Sum or Average 0.496511E+10 0.140698E+09 0.482442E+10 0.891797E+10 0.738900E+10
Minimum of Months 0.264974E+09 0.00 0.264974E+09 80340805.53 65092510.40
Maximum of Months 0.583745E+09 56289285.32 0.542342E+09 0.160240E+10 0.140226E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38150281.98 0.00 38150281.98 69556459.78 0.119501E+09
February 42077264.71 0.00 42077264.71 92067126.99 97208561.27
March 60976374.93 622.69 60975752.24 0.147610E+09 92109646.58
April 68172669.75 520702.85 67651966.90 0.218697E+09 47692703.52
May 81861711.97 4381309.74 77480402.23 0.305274E+09 26579198.59
June 83395339.51 8041631.04 75353708.48 0.357333E+09 11218361.64
July 80155107.15 6039143.52 74115963.63 0.352843E+09 7261810.15
August 68930604.05 1082745.78 67847858.27 0.305753E+09 11826748.43
September 58475990.39 34250.14 58441740.25 0.246081E+09 26689879.32
October 50121178.72 0.00 50121178.72 0.176959E+09 49075754.96
November 39157332.20 0.00 39157332.20 92057339.90 93918584.37
December 37854815.76 0.00 37854815.76 62026031.34 0.133256E+09
           
Annual Sum or Average 0.709329E+09 20100405.76 0.689228E+09 0.242626E+10 0.716338E+09
Minimum of Months 37854815.76 0.00 37854815.76 62026031.34 7261810.15
Maximum of Months 83395339.51 8041631.04 77480402.23 0.357333E+09 0.133256E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.376034E+09 0.201754E+09 0.174280E+09 0.744753E+09 0.435834E+09
February 0.462070E+09 0.263879E+09 0.198192E+09 0.959328E+09 0.350882E+09
March 0.633399E+09 0.350602E+09 0.282796E+09 0.136396E+10 0.334373E+09
April 0.741245E+09 0.414284E+09 0.326961E+09 0.178877E+10 0.177236E+09
May 0.788425E+09 0.431233E+09 0.357192E+09 0.207971E+10 99892791.00
June 0.761397E+09 0.425273E+09 0.336125E+09 0.220356E+10 41917233.32
July 0.707099E+09 0.372081E+09 0.335019E+09 0.210932E+10 27291253.19
August 0.673259E+09 0.346949E+09 0.326309E+09 0.197950E+10 44352514.57
September 0.648144E+09 0.372705E+09 0.275439E+09 0.179185E+10 99865590.47
October 0.508635E+09 0.274337E+09 0.234297E+09 0.132065E+10 0.183185E+09
November 0.438528E+09 0.254067E+09 0.184461E+09 0.939891E+09 0.340112E+09
December 0.375937E+09 0.196979E+09 0.178958E+09 0.718645E+09 0.484567E+09
           
Annual Sum or Average 0.711417E+10 0.390414E+10 0.321003E+10 0.179999E+11 0.261951E+10
Minimum of Months 0.375937E+09 0.196979E+09 0.174280E+09 0.718645E+09 27291253.19
Maximum of Months 0.788425E+09 0.431233E+09 0.357192E+09 0.220356E+10 0.484567E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.264647E+09 0.201384E+09 63262840.52 0.515995E+09 0.116184E+09
February 0.220193E+09 0.155663E+09 64530892.66 0.456683E+09 94015908.15
March 0.183426E+09 0.100121E+09 83305334.62 0.428754E+09 91000176.35
April 0.120758E+09 39809150.64 80948993.88 0.363829E+09 48264705.40
May 90445255.74 9348720.99 81096534.75 0.336921E+09 26872402.07
June 76364923.40 2651285.19 73713638.21 0.342217E+09 11129625.18
July 79673300.15 4444745.52 75228554.63 0.357056E+09 7222881.91
August 97884800.12 20156891.76 77727908.36 0.393139E+09 11777905.11
September 0.150014E+09 73288714.47 76725115.99 0.475513E+09 26658431.84
October 0.221232E+09 0.148615E+09 72617473.30 0.544647E+09 48689733.27
November 0.264929E+09 0.202901E+09 62028222.36 0.545800E+09 90645905.37
December 0.272959E+09 0.206285E+09 66674853.38 0.523175E+09 0.129042E+09
           
Annual Sum or Average 0.204253E+10 0.116467E+10 0.877860E+09 0.528373E+10 0.701503E+09
Minimum of Months 76364923.40 2651285.19 62028222.36 0.336921E+09 7222881.91
Maximum of Months 0.272959E+09 0.206285E+09 83305334.62 0.545800E+09 0.129042E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 48314924.98 0.00 48314924.98 17994718.00 0.232864E+09
February 53288200.83 0.00 53288200.83 35274041.92 0.186604E+09
March 77222731.45 788.60 77221942.86 76185116.06 0.173002E+09
April 86336384.78 659437.31 85676947.47 0.128841E+09 91856248.00
May 0.103673E+09 5548652.34 98124040.68 0.211767E+09 49487008.12
June 0.105615E+09 10184218.31 95430717.23 0.270962E+09 21384159.19
July 0.101511E+09 7648194.22 93863191.48 0.257977E+09 16500447.74
August 87296260.75 1371229.21 85925031.54 0.202864E+09 26021603.86
September 74056152.20 43375.64 74012776.56 0.148395E+09 60453492.83
October 63475310.37 0.00 63475310.37 86042900.58 0.112395E+09
November 49590290.55 0.00 49590290.55 27186129.16 0.193725E+09
December 47940735.65 0.00 47940735.65 13585677.43 0.252963E+09
           
Annual Sum or Average 0.898320E+09 25455895.63 0.872864E+09 0.147707E+10 0.141726E+10
Minimum of Months 47940735.65 0.00 47940735.65 13585677.43 16500447.74
Maximum of Months 0.105615E+09 10184218.31 98124040.68 0.270962E+09 0.252963E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43227546.45 0.00 43227546.45 16099942.38 0.208345E+09
February 47677155.19 0.00 47677155.19 31559818.95 0.166956E+09
March 69091470.43 705.56 69090764.87 68163112.00 0.154786E+09
April 77245490.59 590001.06 76655489.53 0.115275E+09 82184133.12
May 92756351.27 4964400.28 87791950.99 0.189469E+09 44276213.67
June 94494083.00 9111858.71 85382224.29 0.242431E+09 19132488.26
July 90822621.41 6842868.35 83979753.06 0.230813E+09 14763013.11
August 78104295.26 1226843.97 76877451.28 0.181503E+09 23281627.57
September 66258319.97 38808.35 66219511.62 0.132769E+09 54087969.10
October 56791600.70 0.00 56791600.70 76982909.17 0.100561E+09
November 44368620.85 0.00 44368620.85 24323532.77 0.173326E+09
December 42892757.84 0.00 42892757.84 12155157.07 0.226317E+09
           
Annual Sum or Average 0.803730E+09 22775486.27 0.780955E+09 0.132154E+10 0.126801E+10
Minimum of Months 42892757.84 0.00 42892757.84 12155157.07 14763013.11
Maximum of Months 94494083.00 9111858.71 87791950.99 0.242431E+09 0.226317E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.988007E+09 0.751828E+09 0.236179E+09 0.163874E+10 0.616175E+09
February 0.822048E+09 0.581135E+09 0.240913E+09 0.140507E+10 0.496498E+09
March 0.684786E+09 0.373782E+09 0.311004E+09 0.123706E+10 0.487831E+09
April 0.450826E+09 0.148619E+09 0.302207E+09 0.921223E+09 0.279405E+09
May 0.337659E+09 34901561.25 0.302758E+09 0.751793E+09 0.155552E+09
June 0.285093E+09 9898037.65 0.275195E+09 0.747290E+09 65302551.06
July 0.297444E+09 16593559.50 0.280851E+09 0.779404E+09 50714345.29
August 0.365433E+09 75251683.38 0.290181E+09 0.923412E+09 79649473.57
September 0.560046E+09 0.273609E+09 0.286438E+09 0.128350E+10 0.176763E+09
October 0.825926E+09 0.554823E+09 0.271103E+09 0.159501E+10 0.315249E+09
November 0.989059E+09 0.757490E+09 0.231570E+09 0.170332E+10 0.510629E+09
December 0.101904E+10 0.770122E+09 0.248917E+09 0.166919E+10 0.659543E+09
           
Annual Sum or Average 0.762537E+10 0.434805E+10 0.327731E+10 0.146550E+11 0.389331E+10
Minimum of Months 0.285093E+09 9898037.65 0.231570E+09 0.747290E+09 50714345.29
Maximum of Months 0.101904E+10 0.770122E+09 0.311004E+09 0.170332E+10 0.659543E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 828.68 301.73 499.74 380.28 119.46 0.00 0.00
February 789.56 266.40 460.35 325.44 134.91 0.00 0.00
March 635.05 232.36 346.37 189.06 157.31 0.00 0.00
April 488.14 137.98 235.63 77.68 157.95 0.00 0.00
May 379.42 78.23 170.79 17.65 153.14 0.00 0.00
June 381.51 36.02 149.01 5.17 143.83 0.00 0.00
July 388.40 26.76 150.45 8.39 142.06 0.00 0.00
August 463.14 41.08 184.84 38.06 146.77 0.00 0.00
September 669.39 92.84 292.72 143.01 149.71 0.00 0.00
October 810.68 153.95 417.76 280.64 137.13 0.00 0.00
November 892.33 258.28 516.95 395.92 121.03 0.00 0.00
December 840.09 326.68 515.44 389.54 125.90 0.00 0.00
               
Annual Sum or Average 629.47 162.18 327.58 186.79 140.79 0.00 0.00
Minimum of Months 379.42 26.76 149.01 5.17 119.46 0.00 0.00
Maximum of Months 892.33 326.68 516.95 395.92 157.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2337.81 843.90 1407.24 1070.85 336.39 0.00 0.00
February 2230.40 738.34 1296.31 916.41 379.90 0.00 0.00
March 1805.34 634.76 975.35 532.39 442.97 0.00 0.00
April 1413.60 352.84 663.52 218.74 444.78 0.00 0.00
May 1129.48 184.36 480.93 49.71 431.22 0.00 0.00
June 1146.15 78.02 419.60 14.57 405.03 0.00 0.00
July 1163.27 51.84 423.65 23.63 400.02 0.00 0.00
August 1362.03 90.45 520.49 107.18 413.31 0.00 0.00
September 1918.53 226.03 824.27 402.70 421.58 0.00 0.00
October 2302.65 400.77 1176.39 790.25 386.14 0.00 0.00
November 2515.81 707.89 1455.70 1114.88 340.82 0.00 0.00
December 2368.19 915.66 1451.44 1096.91 354.54 0.00 0.00
               
Annual Sum or Average 1804.95 433.95 922.44 525.99 396.45 0.00 0.00
Minimum of Months 1129.48 51.84 419.60 14.57 336.39 0.00 0.00
Maximum of Months 2515.81 915.66 1455.70 1114.88 444.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3060.71 1164.22 1828.09 1391.09 436.99 0.00 0.00
February 2919.45 1021.20 1683.98 1190.47 493.51 0.00 0.00
March 2354.62 887.49 1267.04 691.60 575.44 0.00 0.00
April 1834.08 508.47 861.95 284.15 577.80 0.00 0.00
May 1448.73 275.84 624.76 64.58 560.18 0.00 0.00
June 1470.74 119.42 545.08 18.92 526.15 0.00 0.00
July 1492.47 85.09 550.35 30.70 519.65 0.00 0.00
August 1761.35 137.08 676.15 139.24 536.91 0.00 0.00
September 2508.37 320.35 1070.78 523.13 547.65 0.00 0.00
October 3012.61 559.90 1528.19 1026.58 501.61 0.00 0.00
November 3295.78 977.73 1891.04 1448.29 442.75 0.00 0.00
December 3096.77 1261.76 1885.51 1424.94 460.56 0.00 0.00
               
Annual Sum or Average 2350.85 607.91 1198.30 683.28 515.02 0.00 0.00
Minimum of Months 1448.73 85.09 545.08 18.92 436.99 0.00 0.00
Maximum of Months 3295.78 1261.76 1891.04 1448.29 577.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 265.56 167.25 173.32 116.97 56.35 0.00 0.00
February 279.79 146.37 175.22 108.92 66.30 0.00 0.00
March 314.51 124.95 184.50 99.97 84.53 0.00 0.00
April 346.23 63.94 179.84 87.72 92.12 0.00 0.00
May 373.44 30.25 177.50 80.91 96.59 0.00 0.00
June 400.78 10.44 168.84 76.12 92.72 0.00 0.00
July 370.69 5.59 153.57 63.46 90.11 0.00 0.00
August 364.67 11.57 156.57 69.00 87.57 0.00 0.00
September 392.29 36.55 181.42 97.69 83.73 0.00 0.00
October 359.10 72.54 188.68 117.80 70.88 0.00 0.00
November 311.85 138.26 190.09 131.66 58.43 0.00 0.00
December 256.46 183.39 172.36 114.99 57.37 0.00 0.00
               
Annual Sum or Average 336.45 82.29 175.10 96.99 78.11 0.00 0.00
Minimum of Months 256.46 5.59 153.57 63.46 56.35 0.00 0.00
Maximum of Months 400.78 183.39 190.09 131.66 96.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 115.04 172.52 88.75 41.78 46.97 0.00 0.00
February 142.62 152.07 101.59 44.58 57.02 0.00 0.00
March 215.18 127.31 138.78 62.59 76.19 0.00 0.00
April 289.95 64.85 159.55 72.57 86.99 0.00 0.00
May 358.53 30.49 174.30 79.06 95.24 0.00 0.00
June 403.31 10.62 171.55 78.20 93.35 0.00 0.00
July 366.22 5.90 153.75 64.05 89.69 0.00 0.00
August 330.58 12.21 145.76 61.87 83.88 0.00 0.00
September 304.68 38.41 146.11 69.43 76.68 0.00 0.00
October 226.24 76.29 124.79 62.31 62.48 0.00 0.00
November 150.21 143.92 102.98 53.38 49.60 0.00 0.00
December 102.98 190.95 84.58 37.97 46.61 0.00 0.00
               
Annual Sum or Average 250.95 85.14 132.83 60.70 72.13 0.00 0.00
Minimum of Months 102.98 5.90 84.58 37.97 46.61 0.00 0.00
Maximum of Months 403.31 190.95 174.30 79.06 95.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 124.19 62.68 79.03 60.14 18.89 0.00 0.00
February 117.74 55.90 72.80 51.47 21.34 0.00 0.00
March 92.65 49.03 54.78 29.90 24.88 0.00 0.00
April 70.80 30.39 37.26 12.28 24.98 0.00 0.00
May 54.07 18.13 27.01 2.79 24.22 0.00 0.00
June 54.49 9.48 23.56 0.82 22.75 0.00 0.00
July 55.27 8.07 23.79 1.33 22.47 0.00 0.00
August 67.35 11.14 29.23 6.02 23.21 0.00 0.00
September 100.84 20.98 46.29 22.62 23.68 0.00 0.00
October 122.33 32.90 66.07 44.38 21.69 0.00 0.00
November 134.66 52.78 81.75 62.61 19.14 0.00 0.00
December 125.81 66.50 81.51 61.60 19.91 0.00 0.00
               
Annual Sum or Average 93.18 34.73 51.80 29.54 22.26 0.00 0.00
Minimum of Months 54.07 8.07 23.56 0.82 18.89 0.00 0.00
Maximum of Months 134.66 66.50 81.75 62.61 24.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.73 50.42 11.40 0.00 11.40 0.00 0.00
February 11.45 43.64 13.92 0.00 13.92 0.00 0.00
March 21.07 35.67 18.22 0.00 18.22 0.00 0.00
April 36.40 16.92 21.04 0.16 20.88 0.00 0.00
May 56.19 7.45 24.45 1.31 23.15 0.00 0.00
June 73.64 2.39 25.74 2.48 23.26 0.00 0.00
July 68.81 1.22 23.94 1.80 22.14 0.00 0.00
August 55.21 2.76 20.59 0.32 20.27 0.00 0.00
September 41.51 9.45 18.05 0.01 18.04 0.00 0.00
October 24.71 20.23 14.97 0.00 14.97 0.00 0.00
November 9.29 40.78 12.09 0.00 12.09 0.00 0.00
December 4.35 56.07 11.31 0.00 11.31 0.00 0.00
               
Annual Sum or Average 34.15 23.82 18.00 0.51 17.49 0.00 0.00
Minimum of Months 4.35 1.22 11.31 0.00 11.31 0.00 0.00
Maximum of Months 73.64 56.07 25.74 2.48 23.26 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 255.36 164.74 169.01 112.85 56.16 0.00 0.00
February 297.40 143.43 186.53 118.89 67.64 0.00 0.00
March 313.07 118.79 186.73 102.84 83.90 0.00 0.00
April 360.46 59.56 189.59 95.28 94.31 0.00 0.00
May 378.77 28.06 180.96 84.00 96.96 0.00 0.00
June 415.06 9.87 176.35 83.06 93.28 0.00 0.00
July 385.99 5.37 161.76 71.12 90.63 0.00 0.00
August 376.03 11.05 162.24 72.30 89.94 0.00 0.00
September 392.69 34.24 182.91 100.18 82.74 0.00 0.00
October 335.71 70.29 177.56 106.70 70.85 0.00 0.00
November 301.74 134.85 186.81 127.29 59.52 0.00 0.00
December 253.58 180.48 172.10 113.79 58.30 0.00 0.00
               
Annual Sum or Average 338.85 79.76 177.57 98.84 78.74 0.00 0.00
Minimum of Months 253.58 5.37 161.76 71.12 56.16 0.00 0.00
Maximum of Months 415.06 180.48 189.59 127.29 96.96 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 100.00 164.68 84.45 37.67 46.78 0.00 0.00
February 154.65 142.95 112.90 54.54 58.36 0.00 0.00
March 212.25 118.82 141.02 65.45 75.56 0.00 0.00
April 304.15 60.82 169.30 80.12 89.18 0.00 0.00
May 362.79 29.25 177.76 82.14 95.61 0.00 0.00
June 415.97 10.33 179.06 85.14 93.92 0.00 0.00
July 380.05 5.79 161.94 71.72 90.22 0.00 0.00
August 340.35 11.79 151.43 65.18 86.25 0.00 0.00
September 302.79 35.76 147.60 71.91 75.68 0.00 0.00
October 201.40 71.75 113.67 51.22 62.45 0.00 0.00
November 135.62 135.06 99.71 49.01 50.69 0.00 0.00
December 93.86 181.64 84.32 36.77 47.54 0.00 0.00
               
Annual Sum or Average 250.68 80.43 135.30 62.54 72.75 0.00 0.00
Minimum of Months 93.86 5.79 84.32 36.77 46.78 0.00 0.00
Maximum of Months 415.97 181.64 179.06 85.14 95.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 291.08 208.30 195.93 130.30 65.62 0.00 0.00
February 291.98 183.32 187.89 111.51 76.38 0.00 0.00
March 263.83 159.15 158.14 64.78 93.36 0.00 0.00
April 248.40 85.98 126.33 26.96 99.36 0.00 0.00
May 252.09 44.46 111.50 8.88 102.61 0.00 0.00
June 287.55 19.75 106.83 7.15 99.68 0.00 0.00
July 279.40 13.32 103.42 6.78 96.64 0.00 0.00
August 275.79 22.39 107.94 13.74 94.20 0.00 0.00
September 318.65 56.95 139.40 49.02 90.38 0.00 0.00
October 331.10 99.47 175.58 96.16 79.42 0.00 0.00
November 320.95 176.56 203.32 135.66 67.66 0.00 0.00
December 290.61 226.14 201.11 133.47 67.64 0.00 0.00
               
Annual Sum or Average 287.51 107.62 151.23 65.11 86.12 0.00 0.00
Minimum of Months 248.40 13.32 103.42 6.78 65.62 0.00 0.00
Maximum of Months 331.10 226.14 203.32 135.66 102.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 265.56 164.04 173.32 116.97 56.35 0.00 0.00
February 279.48 143.34 175.22 108.92 66.30 0.00 0.00
March 313.52 122.33 184.50 99.97 84.53 0.00 0.00
April 344.59 62.06 179.84 87.72 92.12 0.00 0.00
May 371.84 28.81 177.50 80.91 96.59 0.00 0.00
June 399.24 9.73 168.84 76.12 92.72 0.00 0.00
July 368.94 5.15 153.57 63.46 90.11 0.00 0.00
August 363.03 10.84 156.57 69.00 87.57 0.00 0.00
September 390.37 35.16 181.42 97.69 83.73 0.00 0.00
October 357.92 70.58 188.68 117.80 70.88 0.00 0.00
November 311.71 135.10 190.09 131.66 58.43 0.00 0.00
December 256.98 180.03 172.36 114.99 57.37 0.00 0.00
               
Annual Sum or Average 335.44 80.30 175.10 96.99 78.11 0.00 0.00
Minimum of Months 256.98 5.15 153.57 63.46 56.35 0.00 0.00
Maximum of Months 399.24 180.03 190.09 131.66 96.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 115.99 168.38 88.75 41.78 46.97 0.00 0.00
February 143.26 148.36 101.59 44.58 57.02 0.00 0.00
March 214.98 124.59 138.78 62.59 76.19 0.00 0.00
April 288.70 63.22 159.55 72.57 86.99 0.00 0.00
May 357.13 29.18 174.30 79.06 95.24 0.00 0.00
June 401.75 9.96 171.55 78.20 93.35 0.00 0.00
July 364.48 5.48 153.75 64.05 89.69 0.00 0.00
August 329.27 11.50 145.76 61.87 83.88 0.00 0.00
September 303.42 36.95 146.11 69.43 76.68 0.00 0.00
October 225.80 74.35 124.79 62.31 62.48 0.00 0.00
November 151.13 139.81 102.98 53.38 49.60 0.00 0.00
December 104.16 186.71 84.58 37.97 46.61 0.00 0.00
               
Annual Sum or Average 250.48 82.90 132.83 60.70 72.13 0.00 0.00
Minimum of Months 104.16 5.48 84.58 37.97 46.61 0.00 0.00
Maximum of Months 401.75 186.71 174.30 79.06 95.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 238.60 86.06 144.91 110.27 34.64 0.00 0.00
February 227.98 74.39 133.49 94.37 39.12 0.00 0.00
March 183.54 62.97 100.44 54.82 45.62 0.00 0.00
April 145.72 31.42 68.33 22.52 45.80 0.00 0.00
May 119.89 13.90 49.52 5.12 44.41 0.00 0.00
June 125.66 4.38 43.21 1.50 41.71 0.00 0.00
July 127.10 2.24 43.63 2.43 41.19 0.00 0.00
August 146.21 5.04 53.60 11.04 42.56 0.00 0.00
September 200.61 17.17 84.88 41.47 43.41 0.00 0.00
October 238.12 35.80 121.14 81.38 39.76 0.00 0.00
November 259.19 69.84 149.90 114.80 35.10 0.00 0.00
December 242.44 94.17 149.46 112.95 36.51 0.00 0.00
               
Annual Sum or Average 187.65 41.30 94.99 54.16 40.83 0.00 0.00
Minimum of Months 119.89 2.24 43.21 1.50 34.64 0.00 0.00
Maximum of Months 259.19 94.17 149.90 114.80 45.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 46.32 456.83 99.70 0.00 99.70 0.00 0.00
February 95.78 398.46 121.75 0.00 121.75 0.00 0.00
March 179.90 328.88 159.36 0.00 159.35 0.00 0.00
April 312.54 167.34 184.10 1.41 182.70 0.00 0.00
May 482.86 82.36 213.94 11.45 202.49 0.00 0.00
June 629.54 34.00 225.21 21.72 203.49 0.00 0.00
July 584.28 22.11 209.48 15.78 193.69 0.00 0.00
August 469.32 38.30 180.14 2.83 177.31 0.00 0.00
September 358.75 100.70 157.92 0.09 157.82 0.00 0.00
October 211.76 193.95 130.99 0.00 130.99 0.00 0.00
November 76.17 375.17 105.74 0.00 105.74 0.00 0.00
December 34.92 501.15 98.93 0.00 98.93 0.00 0.00
               
Annual Sum or Average 291.18 224.12 157.44 4.46 152.98 0.00 0.00
Minimum of Months 34.92 22.11 98.93 0.00 98.93 0.00 0.00
Maximum of Months 629.54 501.15 225.21 21.72 203.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 41.06 477.59 99.70 0.00 99.70 0.00 0.00
February 89.21 415.82 121.75 0.00 121.75 0.00 0.00
March 171.44 342.44 159.36 0.00 159.35 0.00 0.00
April 303.11 174.68 184.10 1.41 182.70 0.00 0.00
May 472.32 86.39 213.94 11.45 202.49 0.00 0.00
June 618.21 36.22 225.21 21.72 203.49 0.00 0.00
July 572.86 24.30 209.48 15.78 193.69 0.00 0.00
August 458.51 41.10 180.14 2.83 177.31 0.00 0.00
September 349.90 105.98 157.92 0.09 157.82 0.00 0.00
October 204.33 202.95 130.99 0.00 130.99 0.00 0.00
November 70.54 390.80 105.74 0.00 105.74 0.00 0.00
December 30.00 523.54 98.93 0.00 98.93 0.00 0.00
               
Annual Sum or Average 282.79 234.30 157.44 4.46 152.98 0.00 0.00
Minimum of Months 30.00 24.30 98.93 0.00 98.93 0.00 0.00
Maximum of Months 618.21 523.54 225.21 21.72 203.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 495.47 249.51 253.45 150.51 102.93 0.00 0.00
February 621.77 222.47 299.41 173.42 125.99 0.00 0.00
March 722.83 191.60 327.73 168.28 159.45 0.00 0.00
April 914.28 104.82 358.86 175.39 183.47 0.00 0.00
May 1016.10 57.10 358.70 166.13 192.57 0.00 0.00
June 1120.02 24.79 355.38 168.20 187.19 0.00 0.00
July 1052.57 15.60 323.67 142.83 180.84 0.00 0.00
August 1000.00 25.37 313.65 137.47 176.18 0.00 0.00
September 969.66 59.08 330.49 172.08 158.41 0.00 0.00
October 762.38 104.78 291.21 157.91 133.30 0.00 0.00
November 607.43 201.15 286.50 176.30 110.20 0.00 0.00
December 485.34 277.39 256.40 150.56 105.84 0.00 0.00
               
Annual Sum or Average 814.59 127.36 312.85 161.37 151.48 0.00 0.00
Minimum of Months 485.34 15.60 253.45 137.47 102.93 0.00 0.00
Maximum of Months 1120.02 277.39 358.86 176.30 192.57 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 610.79 381.00 403.06 280.70 122.36 0.00 0.00
February 597.85 340.80 381.54 240.22 141.32 0.00 0.00
March 512.97 301.72 310.30 139.55 170.74 0.00 0.00
April 449.14 174.49 237.04 57.82 179.22 0.00 0.00
May 429.19 91.78 199.41 16.96 182.45 0.00 0.00
June 485.75 40.20 187.19 11.26 175.93 0.00 0.00
July 472.91 30.02 182.86 11.61 171.26 0.00 0.00
August 487.93 47.81 198.19 29.07 169.12 0.00 0.00
September 603.40 112.14 270.20 105.59 164.61 0.00 0.00
October 654.02 194.85 353.27 207.15 146.12 0.00 0.00
November 665.38 326.97 417.83 292.24 125.59 0.00 0.00
December 615.48 407.85 414.38 287.53 126.85 0.00 0.00
               
Annual Sum or Average 548.31 203.46 295.77 139.41 156.37 0.00 0.00
Minimum of Months 429.19 30.02 182.86 11.26 122.36 0.00 0.00
Maximum of Months 665.38 407.85 417.83 292.24 182.45 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.221953E+10 0.808166E+09 0.133851E+10 0.101855E+10 0.319964E+09 0.00 0.00
February 0.191011E+10 0.644466E+09 0.111368E+10 0.787299E+09 0.326377E+09 0.00 0.00
March 0.170093E+10 0.622351E+09 0.927717E+09 0.506385E+09 0.421331E+09 0.00 0.00
April 0.126525E+10 0.357649E+09 0.610757E+09 0.201344E+09 0.409413E+09 0.00 0.00
May 0.101623E+10 0.209540E+09 0.457442E+09 47283302.53 0.410158E+09 0.00 0.00
June 0.988886E+09 93364697.82 0.386227E+09 13409483.47 0.372818E+09 0.00 0.00
July 0.104030E+10 71669863.83 0.402961E+09 22480320.82 0.380480E+09 0.00 0.00
August 0.124049E+10 0.110026E+09 0.495070E+09 0.101948E+09 0.393122E+09 0.00 0.00
September 0.173506E+10 0.240639E+09 0.758725E+09 0.370674E+09 0.388050E+09 0.00 0.00
October 0.217132E+10 0.412347E+09 0.111893E+10 0.751654E+09 0.367276E+09 0.00 0.00
November 0.231292E+10 0.669464E+09 0.133994E+10 0.102622E+10 0.313719E+09 0.00 0.00
December 0.225010E+10 0.874982E+09 0.138055E+10 0.104333E+10 0.337221E+09 0.00 0.00
               
Annual Sum or Average 0.198511E+11 0.511466E+10 0.103305E+11 0.589058E+10 0.443993E+10 0.00 0.00
Minimum of Months 0.988886E+09 71669863.83 0.386227E+09 13409483.47 0.313719E+09 0.00 0.00
Maximum of Months 0.231292E+10 0.874982E+09 0.138055E+10 0.104333E+10 0.421331E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.626160E+10 0.226029E+10 0.376916E+10 0.286816E+10 0.900997E+09 0.00 0.00
February 0.539578E+10 0.178618E+10 0.313604E+10 0.221698E+10 0.919056E+09 0.00 0.00
March 0.483543E+10 0.170015E+10 0.261239E+10 0.142595E+10 0.118644E+10 0.00 0.00
April 0.366405E+10 0.914551E+09 0.171985E+10 0.566971E+09 0.115288E+10 0.00 0.00
May 0.302519E+10 0.493786E+09 0.128813E+10 0.133147E+09 0.115498E+10 0.00 0.00
June 0.297082E+10 0.202228E+09 0.108759E+10 37760221.31 0.104983E+10 0.00 0.00
July 0.311570E+10 0.138843E+09 0.113471E+10 63303101.21 0.107141E+10 0.00 0.00
August 0.364806E+10 0.242261E+09 0.139408E+10 0.287079E+09 0.110700E+10 0.00 0.00
September 0.497284E+10 0.585882E+09 0.213652E+10 0.104379E+10 0.109272E+10 0.00 0.00
October 0.616741E+10 0.107342E+10 0.315083E+10 0.211661E+10 0.103422E+10 0.00 0.00
November 0.652097E+10 0.183486E+10 0.377317E+10 0.288976E+10 0.883412E+09 0.00 0.00
December 0.634295E+10 0.245251E+10 0.388755E+10 0.293795E+10 0.949592E+09 0.00 0.00
               
Annual Sum or Average 0.569208E+11 0.136850E+11 0.290900E+11 0.165875E+11 0.125025E+11 0.00 0.00
Minimum of Months 0.297082E+10 0.138843E+09 0.108759E+10 37760221.31 0.883412E+09 0.00 0.00
Maximum of Months 0.652097E+10 0.245251E+10 0.388755E+10 0.293795E+10 0.118644E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.819780E+10 0.311826E+10 0.489635E+10 0.372591E+10 0.117045E+10 0.00 0.00
February 0.706274E+10 0.247049E+10 0.407389E+10 0.287999E+10 0.119391E+10 0.00 0.00
March 0.630661E+10 0.237705E+10 0.339364E+10 0.185239E+10 0.154126E+10 0.00 0.00
April 0.475394E+10 0.131797E+10 0.223418E+10 0.736528E+09 0.149766E+10 0.00 0.00
May 0.388029E+10 0.738798E+09 0.167335E+10 0.172965E+09 0.150038E+10 0.00 0.00
June 0.381216E+10 0.309549E+09 0.141284E+10 49052676.43 0.136379E+10 0.00 0.00
July 0.399742E+10 0.227910E+09 0.147405E+10 82234331.09 0.139182E+10 0.00 0.00
August 0.471761E+10 0.367158E+09 0.181099E+10 0.372932E+09 0.143806E+10 0.00 0.00
September 0.650169E+10 0.830339E+09 0.277546E+10 0.135595E+10 0.141951E+10 0.00 0.00
October 0.806897E+10 0.149962E+10 0.409311E+10 0.274959E+10 0.134352E+10 0.00 0.00
November 0.854266E+10 0.253428E+10 0.490157E+10 0.375397E+10 0.114760E+10 0.00 0.00
December 0.829438E+10 0.337949E+10 0.505014E+10 0.381657E+10 0.123357E+10 0.00 0.00
               
Annual Sum or Average 0.741363E+11 0.191709E+11 0.377896E+11 0.215481E+11 0.162415E+11 0.00 0.00
Minimum of Months 0.381216E+10 0.227910E+09 0.141284E+10 49052676.43 0.114760E+10 0.00 0.00
Maximum of Months 0.854266E+10 0.337949E+10 0.505014E+10 0.381657E+10 0.154126E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.711284E+09 0.447952E+09 0.464216E+09 0.313301E+09 0.150915E+09 0.00 0.00
February 0.676865E+09 0.354090E+09 0.423894E+09 0.263503E+09 0.160391E+09 0.00 0.00
March 0.842385E+09 0.334664E+09 0.494156E+09 0.267755E+09 0.226400E+09 0.00 0.00
April 0.897429E+09 0.165733E+09 0.466142E+09 0.227379E+09 0.238764E+09 0.00 0.00
May 0.100021E+10 81013819.03 0.475420E+09 0.216719E+09 0.258701E+09 0.00 0.00
June 0.103881E+10 27056684.40 0.437621E+09 0.197303E+09 0.240318E+09 0.00 0.00
July 0.992848E+09 14974856.10 0.411317E+09 0.169970E+09 0.241347E+09 0.00 0.00
August 0.976734E+09 30991131.24 0.419346E+09 0.184797E+09 0.234549E+09 0.00 0.00
September 0.101681E+10 94748689.24 0.470248E+09 0.253211E+09 0.217036E+09 0.00 0.00
October 0.961824E+09 0.194283E+09 0.505361E+09 0.315508E+09 0.189854E+09 0.00 0.00
November 0.808327E+09 0.358377E+09 0.492701E+09 0.341263E+09 0.151438E+09 0.00 0.00
December 0.686895E+09 0.491182E+09 0.461637E+09 0.307979E+09 0.153657E+09 0.00 0.00
               
Annual Sum or Average 0.106104E+11 0.259506E+10 0.552206E+10 0.305869E+10 0.246337E+10 0.00 0.00
Minimum of Months 0.676865E+09 14974856.10 0.411317E+09 0.169970E+09 0.150915E+09 0.00 0.00
Maximum of Months 0.103881E+10 0.491182E+09 0.505361E+09 0.341263E+09 0.258701E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.308116E+09 0.462082E+09 0.237719E+09 0.111916E+09 0.125803E+09 0.00 0.00
February 0.345031E+09 0.367878E+09 0.245778E+09 0.107840E+09 0.137938E+09 0.00 0.00
March 0.576334E+09 0.341000E+09 0.371706E+09 0.167635E+09 0.204071E+09 0.00 0.00
April 0.751561E+09 0.168088E+09 0.413557E+09 0.188090E+09 0.225467E+09 0.00 0.00
May 0.960280E+09 81671285.11 0.466836E+09 0.211751E+09 0.255085E+09 0.00 0.00
June 0.104538E+10 27533182.40 0.444651E+09 0.202693E+09 0.241958E+09 0.00 0.00
July 0.980885E+09 15798939.10 0.411799E+09 0.171564E+09 0.240235E+09 0.00 0.00
August 0.885434E+09 32695236.63 0.390392E+09 0.165723E+09 0.224669E+09 0.00 0.00
September 0.789720E+09 99564865.10 0.378710E+09 0.179957E+09 0.198753E+09 0.00 0.00
October 0.605956E+09 0.204341E+09 0.334250E+09 0.166893E+09 0.167358E+09 0.00 0.00
November 0.389333E+09 0.373037E+09 0.266929E+09 0.138362E+09 0.128567E+09 0.00 0.00
December 0.275811E+09 0.511430E+09 0.226532E+09 0.101695E+09 0.124837E+09 0.00 0.00
               
Annual Sum or Average 0.791384E+10 0.268512E+10 0.418886E+10 0.191412E+10 0.227474E+10 0.00 0.00
Minimum of Months 0.275811E+09 15798939.10 0.226532E+09 0.101695E+09 0.124837E+09 0.00 0.00
Maximum of Months 0.104538E+10 0.511430E+09 0.466836E+09 0.211751E+09 0.255085E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.332628E+09 0.167872E+09 0.211676E+09 0.161075E+09 50600209.40 0.00 0.00
February 0.284843E+09 0.135226E+09 0.176120E+09 0.124505E+09 51614449.40 0.00 0.00
March 0.248160E+09 0.131315E+09 0.146712E+09 80080954.26 66631016.58 0.00 0.00
April 0.183503E+09 78783562.79 96587307.00 31840988.20 64746318.81 0.00 0.00
May 0.144819E+09 48556494.73 72341817.76 7477489.72 64864328.03 0.00 0.00
June 0.141231E+09 24561803.36 61079791.60 2120606.42 58959185.18 0.00 0.00
July 0.148037E+09 21605282.19 63725966.74 3555089.41 60170877.34 0.00 0.00
August 0.180400E+09 29847440.57 78292269.87 16122307.11 62169962.76 0.00 0.00
September 0.261378E+09 54375008.18 0.119987E+09 58619313.77 61367888.37 0.00 0.00
October 0.327642E+09 88112614.27 0.176951E+09 0.118868E+09 58082427.61 0.00 0.00
November 0.349028E+09 0.136804E+09 0.211901E+09 0.162288E+09 49612711.26 0.00 0.00
December 0.336982E+09 0.178118E+09 0.218324E+09 0.164995E+09 53329276.94 0.00 0.00
               
Annual Sum or Average 0.293865E+10 0.109518E+10 0.163370E+10 0.931549E+09 0.702149E+09 0.00 0.00
Minimum of Months 0.141231E+09 21605282.19 61079791.60 2120606.42 49612711.26 0.00 0.00
Maximum of Months 0.349028E+09 0.178118E+09 0.218324E+09 0.164995E+09 66631016.58 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 15338857.48 0.135043E+09 30524271.22 0.00 30524271.22 0.00 0.00
February 27688880.95 0.105565E+09 33666273.83 0.00 33666273.83 0.00 0.00
March 56423928.54 95527990.29 48787566.16 498.22 48787067.94 0.00 0.00
April 94340445.90 43854293.75 54545365.14 416617.50 54128747.64 0.00 0.00
May 0.150491E+09 19957755.66 65498050.57 3505512.41 61992538.16 0.00 0.00
June 0.190873E+09 6183156.33 66725115.23 6434157.60 60290957.63 0.00 0.00
July 0.184310E+09 3257287.05 64132585.73 4831955.24 59300630.50 0.00 0.00
August 0.147877E+09 7388149.73 55151792.95 866311.44 54285481.51 0.00 0.00
September 0.107600E+09 24488404.01 46786993.37 27403.74 46759589.63 0.00 0.00
October 66180254.43 54175749.27 40102258.05 0.00 40102258.05 0.00 0.00
November 24084530.18 0.105714E+09 31330018.18 0.00 31330018.18 0.00 0.00
December 11643693.77 0.150182E+09 30287866.91 0.00 30287866.91 0.00 0.00
               
Annual Sum or Average 0.107685E+10 0.751336E+09 0.567538E+09 16082456.15 0.551456E+09 0.00 0.00
Minimum of Months 11643693.77 3257287.05 30287866.91 0.00 30287866.91 0.00 0.00
Maximum of Months 0.190873E+09 0.150182E+09 66725115.23 6434157.60 61992538.16 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.683955E+09 0.441227E+09 0.452678E+09 0.302269E+09 0.150409E+09 0.00 0.00
February 0.719470E+09 0.346987E+09 0.451245E+09 0.287611E+09 0.163634E+09 0.00 0.00
March 0.838525E+09 0.318177E+09 0.500148E+09 0.275435E+09 0.224713E+09 0.00 0.00
April 0.934310E+09 0.154368E+09 0.491407E+09 0.246966E+09 0.244441E+09 0.00 0.00
May 0.101449E+10 75151400.21 0.484686E+09 0.224980E+09 0.259705E+09 0.00 0.00
June 0.107584E+10 25588574.48 0.457091E+09 0.215303E+09 0.241788E+09 0.00 0.00
July 0.103384E+10 14377301.89 0.433248E+09 0.190498E+09 0.242750E+09 0.00 0.00
August 0.100717E+10 29600248.18 0.434538E+09 0.193644E+09 0.240894E+09 0.00 0.00
September 0.101785E+10 88759493.33 0.474109E+09 0.259654E+09 0.214454E+09 0.00 0.00
October 0.899156E+09 0.188256E+09 0.475568E+09 0.285793E+09 0.189774E+09 0.00 0.00
November 0.782098E+09 0.349523E+09 0.484209E+09 0.329943E+09 0.154265E+09 0.00 0.00
December 0.679181E+09 0.483409E+09 0.460941E+09 0.304781E+09 0.156160E+09 0.00 0.00
               
Annual Sum or Average 0.106859E+11 0.251543E+10 0.559987E+10 0.311688E+10 0.248299E+10 0.00 0.00
Minimum of Months 0.679181E+09 14377301.89 0.433248E+09 0.190498E+09 0.150409E+09 0.00 0.00
Maximum of Months 0.107584E+10 0.483409E+09 0.500148E+09 0.329943E+09 0.259705E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.267827E+09 0.441085E+09 0.226181E+09 0.100884E+09 0.125296E+09 0.00 0.00
February 0.374121E+09 0.345831E+09 0.273129E+09 0.131949E+09 0.141180E+09 0.00 0.00
March 0.568484E+09 0.318246E+09 0.377698E+09 0.175314E+09 0.202384E+09 0.00 0.00
April 0.788368E+09 0.157635E+09 0.438822E+09 0.207677E+09 0.231144E+09 0.00 0.00
May 0.971710E+09 78353585.28 0.476102E+09 0.220013E+09 0.256089E+09 0.00 0.00
June 0.107819E+10 26763449.31 0.464121E+09 0.220693E+09 0.243428E+09 0.00 0.00
July 0.101793E+10 15496909.02 0.433730E+09 0.192093E+09 0.241637E+09 0.00 0.00
August 0.911597E+09 31582415.66 0.405584E+09 0.174570E+09 0.231014E+09 0.00 0.00
September 0.784844E+09 92682202.91 0.382571E+09 0.186400E+09 0.196171E+09 0.00 0.00
October 0.539423E+09 0.192181E+09 0.304457E+09 0.137178E+09 0.167278E+09 0.00 0.00
November 0.351530E+09 0.350076E+09 0.258437E+09 0.127042E+09 0.131394E+09 0.00 0.00
December 0.251407E+09 0.486501E+09 0.225837E+09 98496300.25 0.127340E+09 0.00 0.00
               
Annual Sum or Average 0.790543E+10 0.253643E+10 0.426667E+10 0.197231E+10 0.229436E+10 0.00 0.00
Minimum of Months 0.251407E+09 15496909.02 0.225837E+09 98496300.25 0.125296E+09 0.00 0.00
Maximum of Months 0.107819E+10 0.486501E+09 0.476102E+09 0.220693E+09 0.256089E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.779640E+09 0.557908E+09 0.524768E+09 0.349006E+09 0.175762E+09 0.00 0.00
February 0.706349E+09 0.443492E+09 0.454535E+09 0.269768E+09 0.184767E+09 0.00 0.00
March 0.706631E+09 0.426269E+09 0.423574E+09 0.173514E+09 0.250060E+09 0.00 0.00
April 0.643849E+09 0.222864E+09 0.327441E+09 69893099.94 0.257548E+09 0.00 0.00
May 0.675211E+09 0.119091E+09 0.298635E+09 23795756.16 0.274840E+09 0.00 0.00
June 0.745324E+09 51183507.99 0.276892E+09 18533307.26 0.258359E+09 0.00 0.00
July 0.748339E+09 35674881.95 0.277009E+09 18170525.41 0.258839E+09 0.00 0.00
August 0.738667E+09 59975741.94 0.289115E+09 36809277.13 0.252306E+09 0.00 0.00
September 0.825945E+09 0.147609E+09 0.361335E+09 0.127071E+09 0.234264E+09 0.00 0.00
October 0.886807E+09 0.266430E+09 0.470278E+09 0.257554E+09 0.212723E+09 0.00 0.00
November 0.831911E+09 0.457635E+09 0.527002E+09 0.351634E+09 0.175368E+09 0.00 0.00
December 0.778378E+09 0.605687E+09 0.538661E+09 0.357498E+09 0.181163E+09 0.00 0.00
               
Annual Sum or Average 0.906705E+10 0.339382E+10 0.476925E+10 0.205325E+10 0.271600E+10 0.00 0.00
Minimum of Months 0.643849E+09 35674881.95 0.276892E+09 18170525.41 0.175368E+09 0.00 0.00
Maximum of Months 0.886807E+09 0.605687E+09 0.538661E+09 0.357498E+09 0.274840E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.711272E+09 0.439372E+09 0.464216E+09 0.313301E+09 0.150915E+09 0.00 0.00
February 0.676127E+09 0.346778E+09 0.423894E+09 0.263503E+09 0.160391E+09 0.00 0.00
March 0.839736E+09 0.327661E+09 0.494156E+09 0.267755E+09 0.226400E+09 0.00 0.00
April 0.893188E+09 0.160872E+09 0.466142E+09 0.227379E+09 0.238764E+09 0.00 0.00
May 0.995933E+09 77175055.11 0.475420E+09 0.216719E+09 0.258701E+09 0.00 0.00
June 0.103484E+10 25226742.02 0.437621E+09 0.197303E+09 0.240318E+09 0.00 0.00
July 0.988179E+09 13793739.15 0.411317E+09 0.169970E+09 0.241347E+09 0.00 0.00
August 0.972334E+09 29025543.36 0.419346E+09 0.184797E+09 0.234549E+09 0.00 0.00
September 0.101183E+10 91130506.59 0.470248E+09 0.253211E+09 0.217036E+09 0.00 0.00
October 0.958642E+09 0.189051E+09 0.505361E+09 0.315508E+09 0.189854E+09 0.00 0.00
November 0.807955E+09 0.350185E+09 0.492701E+09 0.341263E+09 0.151438E+09 0.00 0.00
December 0.688291E+09 0.482188E+09 0.461637E+09 0.307979E+09 0.153657E+09 0.00 0.00
               
Annual Sum or Average 0.105783E+11 0.253246E+10 0.552206E+10 0.305869E+10 0.246337E+10 0.00 0.00
Minimum of Months 0.676127E+09 13793739.15 0.411317E+09 0.169970E+09 0.150915E+09 0.00 0.00
Maximum of Months 0.103484E+10 0.482188E+09 0.505361E+09 0.341263E+09 0.258701E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.310656E+09 0.450987E+09 0.237719E+09 0.111916E+09 0.125803E+09 0.00 0.00
February 0.346571E+09 0.358909E+09 0.245778E+09 0.107840E+09 0.137938E+09 0.00 0.00
March 0.575796E+09 0.333705E+09 0.371706E+09 0.167635E+09 0.204071E+09 0.00 0.00
April 0.748308E+09 0.163860E+09 0.413557E+09 0.188090E+09 0.225467E+09 0.00 0.00
May 0.956536E+09 78145351.01 0.466836E+09 0.211751E+09 0.255085E+09 0.00 0.00
June 0.104133E+10 25805681.65 0.444651E+09 0.202693E+09 0.241958E+09 0.00 0.00
July 0.976221E+09 14668567.79 0.411799E+09 0.171564E+09 0.240235E+09 0.00 0.00
August 0.881904E+09 30810726.17 0.390392E+09 0.165723E+09 0.224669E+09 0.00 0.00
September 0.786463E+09 95773534.35 0.378710E+09 0.179957E+09 0.198753E+09 0.00 0.00
October 0.604781E+09 0.199139E+09 0.334250E+09 0.166893E+09 0.167358E+09 0.00 0.00
November 0.391732E+09 0.362378E+09 0.266929E+09 0.138362E+09 0.128567E+09 0.00 0.00
December 0.278987E+09 0.500076E+09 0.226532E+09 0.101695E+09 0.124837E+09 0.00 0.00
               
Annual Sum or Average 0.789929E+10 0.261426E+10 0.418886E+10 0.191412E+10 0.227474E+10 0.00 0.00
Minimum of Months 0.278987E+09 14668567.79 0.226532E+09 0.101695E+09 0.124837E+09 0.00 0.00
Maximum of Months 0.104133E+10 0.500076E+09 0.466836E+09 0.211751E+09 0.255085E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.639061E+09 0.230497E+09 0.388131E+09 0.295350E+09 92781026.97 0.00 0.00
February 0.551540E+09 0.179961E+09 0.322935E+09 0.228294E+09 94640747.13 0.00 0.00
March 0.491587E+09 0.168667E+09 0.269012E+09 0.146837E+09 0.122175E+09 0.00 0.00
April 0.377706E+09 81451176.35 0.177103E+09 58383939.91 0.118719E+09 0.00 0.00
May 0.321122E+09 37242599.53 0.132647E+09 13710796.54 0.118936E+09 0.00 0.00
June 0.325717E+09 11342579.04 0.111996E+09 3888364.17 0.108108E+09 0.00 0.00
July 0.340427E+09 5987443.32 0.116849E+09 6518645.87 0.110330E+09 0.00 0.00
August 0.391607E+09 13507017.71 0.143557E+09 29562016.22 0.113995E+09 0.00 0.00
September 0.519977E+09 44497020.39 0.220010E+09 0.107485E+09 0.112525E+09 0.00 0.00
October 0.637775E+09 95889671.15 0.324458E+09 0.217958E+09 0.106500E+09 0.00 0.00
November 0.671810E+09 0.181013E+09 0.388544E+09 0.297574E+09 90970340.96 0.00 0.00
December 0.649340E+09 0.252232E+09 0.400321E+09 0.302536E+09 97785071.28 0.00 0.00
               
Annual Sum or Average 0.591767E+10 0.130229E+10 0.299556E+10 0.170810E+10 0.128747E+10 0.00 0.00
Minimum of Months 0.321122E+09 5987443.32 0.111996E+09 3888364.17 90970340.96 0.00 0.00
Maximum of Months 0.671810E+09 0.252232E+09 0.400321E+09 0.302536E+09 0.122175E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.124070E+09 0.122357E+10 0.267042E+09 0.00 0.267042E+09 0.00 0.00
February 0.231711E+09 0.963955E+09 0.294530E+09 0.00 0.294530E+09 0.00 0.00
March 0.481857E+09 0.880880E+09 0.426818E+09 4358.67 0.426814E+09 0.00 0.00
April 0.810103E+09 0.433751E+09 0.477191E+09 3644781.91 0.473546E+09 0.00 0.00
May 0.129329E+10 0.220586E+09 0.573010E+09 30668006.66 0.542342E+09 0.00 0.00
June 0.163177E+10 88130964.84 0.583745E+09 56289285.32 0.527456E+09 0.00 0.00
July 0.156493E+10 59227900.93 0.561065E+09 42272403.62 0.518792E+09 0.00 0.00
August 0.125703E+10 0.102581E+09 0.482496E+09 7578933.41 0.474917E+09 0.00 0.00
September 0.929887E+09 0.261022E+09 0.409316E+09 239741.89 0.409077E+09 0.00 0.00
October 0.567186E+09 0.519487E+09 0.350835E+09 0.00 0.350835E+09 0.00 0.00
November 0.197429E+09 0.972434E+09 0.274091E+09 0.00 0.274091E+09 0.00 0.00
December 93518163.12 0.134228E+10 0.264974E+09 0.00 0.264974E+09 0.00 0.00
               
Annual Sum or Average 0.918278E+10 0.706791E+10 0.496511E+10 0.140698E+09 0.482442E+10 0.00 0.00
Minimum of Months 93518163.12 59227900.93 0.264974E+09 0.00 0.264974E+09 0.00 0.00
Maximum of Months 0.163177E+10 0.134228E+10 0.583745E+09 56289285.32 0.542342E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.109983E+09 0.127917E+10 0.267042E+09 0.00 0.267042E+09 0.00 0.00
February 0.215823E+09 0.100595E+10 0.294530E+09 0.00 0.294530E+09 0.00 0.00
March 0.459187E+09 0.917191E+09 0.426818E+09 4358.67 0.426814E+09 0.00 0.00
April 0.785673E+09 0.452764E+09 0.477191E+09 3644781.91 0.473546E+09 0.00 0.00
May 0.126506E+10 0.231378E+09 0.573010E+09 30668006.66 0.542342E+09 0.00 0.00
June 0.160240E+10 93874021.16 0.583745E+09 56289285.32 0.527456E+09 0.00 0.00
July 0.153435E+10 65092510.40 0.561065E+09 42272403.62 0.518792E+09 0.00 0.00
August 0.122808E+10 0.110078E+09 0.482496E+09 7578933.41 0.474917E+09 0.00 0.00
September 0.906937E+09 0.274710E+09 0.409316E+09 239741.89 0.409077E+09 0.00 0.00
October 0.547288E+09 0.543581E+09 0.350835E+09 0.00 0.350835E+09 0.00 0.00
November 0.182845E+09 0.101295E+10 0.274091E+09 0.00 0.274091E+09 0.00 0.00
December 80340805.53 0.140226E+10 0.264974E+09 0.00 0.264974E+09 0.00 0.00
               
Annual Sum or Average 0.891797E+10 0.738900E+10 0.496511E+10 0.140698E+09 0.482442E+10 0.00 0.00
Minimum of Months 80340805.53 65092510.40 0.264974E+09 0.00 0.264974E+09 0.00 0.00
Maximum of Months 0.160240E+10 0.140226E+10 0.583745E+09 56289285.32 0.542342E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.132706E+10 0.668275E+09 0.678831E+09 0.403138E+09 0.275693E+09 0.00 0.00
February 0.150418E+10 0.538208E+09 0.724341E+09 0.419541E+09 0.304800E+09 0.00 0.00
March 0.193603E+10 0.513191E+09 0.877801E+09 0.450724E+09 0.427077E+09 0.00 0.00
April 0.236981E+10 0.271705E+09 0.930176E+09 0.454614E+09 0.475562E+09 0.00 0.00
May 0.272151E+10 0.152949E+09 0.960731E+09 0.444963E+09 0.515769E+09 0.00 0.00
June 0.290309E+10 64251048.54 0.921158E+09 0.435966E+09 0.485192E+09 0.00 0.00
July 0.281922E+10 41772198.47 0.866928E+09 0.382564E+09 0.484363E+09 0.00 0.00
August 0.267839E+10 67957115.57 0.840074E+09 0.368189E+09 0.471885E+09 0.00 0.00
September 0.251335E+10 0.153127E+09 0.856634E+09 0.446028E+09 0.410606E+09 0.00 0.00
October 0.204196E+10 0.280655E+09 0.779988E+09 0.422952E+09 0.357036E+09 0.00 0.00
November 0.157445E+10 0.521380E+09 0.742615E+09 0.456968E+09 0.285647E+09 0.00 0.00
December 0.129995E+10 0.742964E+09 0.686751E+09 0.403263E+09 0.283488E+09 0.00 0.00
               
Annual Sum or Average 0.256890E+11 0.401644E+10 0.986603E+10 0.508891E+10 0.477712E+10 0.00 0.00
Minimum of Months 0.129995E+10 41772198.47 0.678831E+09 0.368189E+09 0.275693E+09 0.00 0.00
Maximum of Months 0.290309E+10 0.742964E+09 0.960731E+09 0.456968E+09 0.515769E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.163593E+10 0.102047E+10 0.107955E+10 0.751828E+09 0.327722E+09 0.00 0.00
February 0.144631E+10 0.824456E+09 0.923013E+09 0.581135E+09 0.341878E+09 0.00 0.00
March 0.137393E+10 0.808140E+09 0.831100E+09 0.373783E+09 0.457316E+09 0.00 0.00
April 0.116418E+10 0.452287E+09 0.614408E+09 0.149869E+09 0.464539E+09 0.00 0.00
May 0.114953E+10 0.245817E+09 0.534088E+09 45414613.87 0.488674E+09 0.00 0.00
June 0.125907E+10 0.104202E+09 0.485202E+09 29194114.66 0.456008E+09 0.00 0.00
July 0.126663E+10 80416198.54 0.489778E+09 31084622.08 0.458694E+09 0.00 0.00
August 0.130688E+10 0.128054E+09 0.530834E+09 77849756.57 0.452984E+09 0.00 0.00
September 0.156402E+10 0.290663E+09 0.700361E+09 0.273691E+09 0.426670E+09 0.00 0.00
October 0.175173E+10 0.521894E+09 0.946193E+09 0.554823E+09 0.391370E+09 0.00 0.00
November 0.172466E+10 0.847508E+09 0.108302E+10 0.757490E+09 0.325529E+09 0.00 0.00
December 0.164850E+10 0.109238E+10 0.110987E+10 0.770122E+09 0.339751E+09 0.00 0.00
               
Annual Sum or Average 0.172913E+11 0.641629E+10 0.932742E+10 0.439628E+10 0.493113E+10 0.00 0.00
Minimum of Months 0.114953E+10 80416198.54 0.485202E+09 29194114.66 0.325529E+09 0.00 0.00
Maximum of Months 0.175173E+10 0.109238E+10 0.110987E+10 0.770122E+09 0.488674E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 8.14 3.28 -3.0 3.49 -5.4 41.12 223.64 0.00
February 10.27 3.71 -4.6 3.82 -5.0 51.61 245.22 0.00
March 12.55 4.68 -5.5 4.62 -3.1 72.41 273.25 0.00
April 19.23 8.50 -2.7 4.72 3.38 79.21 314.56 0.00
May 23.84 12.23 2.64 5.25 8.38 86.83 326.20 0.00
June 27.86 15.03 5.88 4.15 14.09 80.19 344.14 0.01
July 27.54 18.92 14.64 3.53 17.44 86.25 283.04 0.01
August 26.28 17.11 12.00 3.28 15.48 80.55 269.68 0.02
September 23.38 15.82 11.20 2.23 11.29 66.71 294.09 0.00
October 18.30 12.02 7.27 3.24 6.21 54.59 257.93 0.01
November 11.18 5.22 -1.5 3.40 -3.3 40.23 258.80 0.00
December 6.79 1.84 -4.8 2.82 -8.9 42.65 217.21 0.00
                 
Annual Sum or Average 17.98 9.90 2.67 3.71 4.26 65.29 275.60 0.00
Minimum of Months 6.79 1.84 -5.5 2.23 -8.9 40.23 217.21 0.00
Maximum of Months 27.86 18.92 14.64 5.25 17.44 86.83 344.14 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 20.60 03-JAN-14:00 8.39 -5.0 9.80 2.22 118.50 530.50
February 23.30 20-FEB-14:00 8.88 -7.8 4.10 4.10 55.00 955.00
March 25.00 21-MAR-15:00 9.53 -8.3 6.20 5.54 50.00 873.00
April 32.20 21-APR-13:00 15.21 2.80 13.90 18.28 265.50 638.50
May 35.00 19-MAY-13:00 17.23 6.10 10.30 21.78 145.00 874.50
June 38.90 02-JUN-15:00 16.22 -1.1 4.60 20.40 234.50 284.00
July 38.30 01-JUL-16:00 19.19 8.90 3.60 26.81 165.50 256.50
August 37.20 07-AUG-15:00 17.89 6.70 5.70 24.66 143.50 615.00
September 33.90 19-SEP-13:00 16.85 6.70 3.10 17.75 113.00 912.00
October 32.80 01-OCT-14:00 15.90 4.40 5.70 16.12 127.50 736.50
November 23.90 03-NOV-15:00 13.45 6.10 5.70 12.22 48.50 648.50
December 18.30 10-DEC-14:00 7.97 -2.8 7.20 4.10 123.00 52.50
                 
Annual Sum or Average                
Minimum of Months 18.30   7.97 -8.3 3.10 2.22 48.50 52.50
Maximum of Months 38.90   19.19 8.90 13.90 26.81 265.50 955.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 27-JAN-06:00 -7.5 -15.0 3.60 -23.6 0.00 0.00
February -5.6 03-FEB-06:00 -7.5 -11.7 1.50 -23.9 0.00 0.00
March -3.9 02-MAR-04:00 -6.5 -12.8 1.50 -21.3 0.00 0.00
April 3.30 12-APR-05:00 -1.8 -9.4 2.10 -14.9 37.00 217.50
May 9.40 02-MAY-05:00 3.98 -2.2 3.60 -7.6 51.00 277.50
June 15.00 13-JUN-04:00 4.43 -10.6 2.10 -4.3 0.00 0.00
July 17.80 05-JUL-05:00 15.98 15.00 4.10 4.31 39.00 249.00
August 16.70 31-AUG-05:00 13.89 12.20 4.10 2.64 36.00 126.50
September 8.30 30-SEP-05:00 5.77 3.30 1.50 -7.3 0.00 0.00
October 6.70 11-OCT-05:00 5.82 5.00 1.50 -5.5 0.00 0.00
November -0.6 17-NOV-03:00 -3.1 -6.7 1.50 -18.1 0.00 0.00
December -4.4 27-DEC-06:00 -5.1 -6.1 2.10 -18.6 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -7.5 -15.0 1.50 -23.9 0.00 0.00
Maximum of Months 17.80   15.98 15.00 4.10 4.31 51.00 277.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.18 12-JAN-15:00 18.90 2.80 3.60 6.15 70.50 491.50
February 11.42 13-FEB-16:00 12.80 10.60 4.10 6.55 34.00 18.50
March 10.75 10-MAR-18:00 13.30 8.90 1.50 8.54 0.00 0.00
April 15.74 29-APR-13:00 30.00 6.70 4.10 18.28 336.50 432.50
May 19.12 24-MAY-12:00 27.80 15.00 5.20 17.57 188.50 862.00
June 20.21 03-JUN-14:00 33.90 13.90 8.80 23.66 264.50 316.00
July 22.88 20-JUL-15:39 25.53 21.87 2.93 18.99 184.00 15.83
August 21.18 02-AUG-11:00 30.60 17.20 3.60 20.75 154.50 850.00
September 20.65 14-SEP-09:00 25.00 18.90 2.10 14.47 126.50 835.50
October 19.64 03-OCT-13:00 32.80 13.30 2.60 21.44 224.50 577.50
November 13.57 03-NOV-14:00 23.30 7.20 0.00 10.88 72.50 802.00
December 8.30 10-DEC-12:00 17.20 -0.6 5.70 1.58 198.50 507.50
                 
Annual Sum or Average                
Minimum of Months 8.30   12.80 -0.6 0.00 1.58 0.00 0.00
Maximum of Months 22.88   33.90 21.87 8.80 23.66 336.50 862.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.00 16-JAN-01:00 9.00 9.00 2.10 4.51 0.00 0.00
February 10.60 13-FEB-13:09 12.20 11.24 5.53 5.71 147.33 0.00
March 10.00 11-MAR-00:00 10.60 10.24 2.10 6.15 0.00 0.00
April 10.60 17-APR-01:00 17.80 13.38 7.20 3.48 0.00 0.00
May 15.00 24-MAY-10:00 25.60 18.41 7.20 15.39 171.00 872.50
June 17.20 19-JUN-17:00 23.90 19.20 3.60 15.39 86.00 324.00
July 22.20 20-JUL-14:00 24.40 22.82 4.60 17.93 283.00 59.50
August 18.90 01-AUG-20:00 22.20 19.91 4.60 17.75 0.00 0.00
September 19.40 22-SEP-01:00 20.60 19.76 1.50 16.30 0.00 0.00
October 17.20 03-OCT-19:00 23.30 19.11 4.60 18.46 0.00 0.00
November 10.00 01-NOV-09:00 13.30 11.28 3.10 8.94 123.50 0.00
December 6.10 13-DEC-00:00 8.30 7.10 7.70 3.06 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   8.30 7.10 1.50 3.06 0.00 0.00
Maximum of Months 22.20   25.60 22.82 7.70 18.46 283.00 872.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 15.16 28.38 0.00
February 18.00 13.00 16.00 15.21 35.58 0.00
March 18.00 13.00 16.00 16.80 47.71 0.00
April 18.00 13.00 16.00 19.62 58.45 0.00
May 18.00 13.00 16.00 22.88 63.58 0.00
June 18.00 13.00 16.00 25.71 66.73 0.00
July 18.00 13.00 16.00 27.35 58.19 0.00
August 18.00 13.00 16.00 27.33 54.44 0.00
September 18.00 13.00 16.00 25.68 50.89 0.00
October 18.00 13.00 16.00 22.83 39.37 0.00
November 18.00 13.00 16.00 19.57 32.11 0.00
December 18.00 13.00 16.00 16.77 26.90 0.00
             
Annual Sum or Average 18.00 13.00 16.00 21.28 46.90 0.00
Minimum of Months 18.00 13.00 16.00 15.16 26.90 0.00
Maximum of Months 18.00 13.00 16.00 27.35 66.73 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770419E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -161415843.6 81.21 0.00 0.00
February 0.696176E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -145795190.8 81.21 0.00 0.00
March 0.770288E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161416581.0 81.21 0.00 0.00
April 0.746480E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156208768.8 81.21 0.00 0.00
May 0.770421E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161413673.4 81.21 0.00 0.00
June 0.745674E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156204580.7 81.21 0.00 0.00
July 0.771226E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161410476.1 81.21 0.00 0.00
August 0.770422E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -161410116.7 81.21 0.00 0.00
September 0.746614E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -156203980.4 81.21 0.00 0.00
October 0.770285E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161413238.0 81.21 0.00 0.00
November 0.744863E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156208426.5 81.21 0.00 0.00
December 0.771227E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -161415816.5 81.21 0.00 0.00
                     
Annual Sum or Average 0.907410E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190052E+10 81.21 0.00 0.00
Minimum of Months 0.696176E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -161416581.0 81.21 0.00 0.00
Maximum of Months 0.771227E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -145795190.8 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.113639E+12 -0.111892E+12 0.00 0.00 744.00 0.00 -0.174680E+10 81.26 0.00 0.00
February 0.102602E+12 -0.100997E+12 0.00 0.00 672.00 0.00 -0.160495E+10 81.26 0.00 0.00
March 0.110906E+12 -0.109106E+12 0.00 0.00 744.00 0.00 -0.180034E+10 81.26 0.00 0.00
April 0.102702E+12 -0.100964E+12 0.00 0.00 720.00 0.00 -0.173855E+10 81.26 0.00 0.00
May 0.100583E+12 -0.987969E+11 0.00 0.00 744.00 0.00 -0.178634E+10 81.25 0.00 0.00
June 0.926828E+11 -0.909639E+11 0.00 0.00 720.00 0.00 -0.171889E+10 81.25 0.00 0.00
July 0.929765E+11 -0.912300E+11 0.00 0.00 744.00 0.00 -0.174649E+10 81.25 0.00 0.00
August 0.929840E+11 -0.912534E+11 0.00 0.00 744.00 0.00 -0.173055E+10 81.24 0.00 0.00
September 0.926960E+11 -0.910247E+11 0.00 0.00 720.00 0.00 -0.167126E+10 81.24 0.00 0.00
October 0.100609E+12 -0.988824E+11 0.00 0.00 744.00 0.00 -0.172672E+10 81.24 0.00 0.00
November 0.102718E+12 -0.101046E+12 0.00 0.00 720.00 0.00 -0.167145E+10 81.25 0.00 0.00
December 0.110898E+12 -0.109168E+12 0.00 0.00 744.00 0.00 -0.172982E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.121600E+13 -0.119532E+13 0.00 0.00 8760.00 0.00 -0.206722E+11 81.25 0.00 0.00
Minimum of Months 0.926828E+11 -0.111892E+12 0.00 0.00 672.00 0.00 -0.180034E+10 81.24 0.00 0.00
Maximum of Months 0.113639E+12 -0.909639E+11 0.00 0.00 744.00 0.00 -0.160495E+10 81.26 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.655148E+11 -0.640241E+11 0.00 0.00 744.00 0.00 -0.149074E+10 58.98 0.00 0.00
February 0.591664E+11 -0.577823E+11 0.00 0.00 672.00 0.00 -0.138411E+10 58.98 0.00 0.00
March 0.632447E+11 -0.616799E+11 0.00 0.00 744.00 0.00 -0.156480E+10 58.98 0.00 0.00
April 0.571816E+11 -0.556723E+11 0.00 0.00 720.00 0.00 -0.150925E+10 58.98 0.00 0.00
May 0.543088E+11 -0.527631E+11 0.00 0.00 744.00 0.00 -0.154570E+10 58.98 0.00 0.00
June 0.485504E+11 -0.470681E+11 0.00 0.00 720.00 0.00 -0.148232E+10 58.98 0.00 0.00
July 0.476945E+11 -0.462039E+11 0.00 0.00 744.00 0.00 -0.149053E+10 58.98 0.00 0.00
August 0.477402E+11 -0.462716E+11 0.00 0.00 744.00 0.00 -0.146857E+10 58.98 0.00 0.00
September 0.485152E+11 -0.470988E+11 0.00 0.00 720.00 0.00 -0.141648E+10 58.98 0.00 0.00
October 0.542698E+11 -0.528064E+11 0.00 0.00 744.00 0.00 -0.146334E+10 58.98 0.00 0.00
November 0.571370E+11 -0.557204E+11 0.00 0.00 720.00 0.00 -0.141660E+10 58.98 0.00 0.00
December 0.631403E+11 -0.616728E+11 0.00 0.00 744.00 0.00 -0.146757E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.666464E+12 -0.648764E+12 0.00 0.00 8760.00 0.00 -0.177000E+11 58.98 0.00 0.00
Minimum of Months 0.476945E+11 -0.640241E+11 0.00 0.00 672.00 0.00 -0.156480E+10 58.98 0.00 0.00
Maximum of Months 0.655148E+11 -0.462039E+11 0.00 0.00 744.00 0.00 -0.138411E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.86 0.86 01-JAN-08:09 7948.75 38.46 274.17 279.33 1030.27 26.81 163.00 259.00
February 268.33 0.87 0.86 01-FEB-07:49 6285.70 33.56 210.83 271.50 644.32 23.56 138.17 240.50
March 351.83 0.87 0.86 01-MAR-07:10 1112.17 18.82 11.83 322.00 437.68 20.62 110.33 254.83
April 373.83 0.87 0.86 01-APR-06:00 810.96 18.24 0.00 339.17 347.36 20.52 103.00 259.83
May 408.83 0.87 0.86 01-MAY-06:40 679.00 17.83 0.00 363.50 296.36 20.14 41.67 266.50
June 398.00 0.87 0.86 01-JUN-07:10 595.84 17.74 0.00 355.33 267.59 20.12 13.17 224.17
July 400.17 0.87 0.86 01-JUL-07:10 653.40 17.62 0.00 361.83 283.59 19.96 33.50 217.50
August 377.83 0.87 0.86 01-AUG-06:00 764.02 17.99 0.00 350.67 326.50 20.27 79.00 258.00
September 365.83 0.87 0.86 01-SEP-08:30 877.94 18.13 0.00 319.33 374.36 20.44 109.50 238.17
October 318.83 0.87 0.86 01-OCT-07:19 3063.96 25.60 124.83 312.83 507.42 21.58 101.00 277.67
November 295.83 0.87 0.86 01-NOV-12:39 8150.33 37.56 288.17 289.17 780.57 25.61 133.17 269.83
December 289.50 0.86 0.86 01-DEC-07:19 7211.62 38.01 284.33 278.33 1158.69 27.48 182.00 268.67
                         
Annual Sum or Average 4125.67 0.87     2773.72 23.80 1194.17 3843.00 502.11 21.92 1207.50 3034.67
Minimum of Months 268.33 0.86 0.86   595.84 17.62 0.00 271.50 267.59 19.96 13.17 217.50
Maximum of Months 408.83 0.87 0.86   8150.33 38.46 288.17 363.50 1158.69 27.48 182.00 277.67



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.23 0.22 01-JAN-07:00 8390.32 38.52 274.33 286.33 1470.70 26.41 153.50 273.17
February 268.33 0.24 0.22 01-FEB-07:40 6674.18 33.56 210.83 280.33 1032.16 23.36 133.50 260.00
March 351.83 0.25 0.22 01-MAR-06:00 1375.01 19.29 12.17 336.00 699.83 20.93 137.17 306.83
April 373.83 0.26 0.22 01-APR-06:49 988.16 19.07 0.00 354.00 524.05 21.10 158.83 320.33
May 408.83 0.27 0.22 01-MAY-06:10 811.46 18.87 0.00 377.50 428.39 20.90 172.50 348.50
June 398.00 0.25 0.22 01-JUN-06:10 716.26 18.87 0.00 372.67 387.63 20.95 109.50 339.17
July 400.17 0.26 0.22 01-JUL-06:19 775.03 18.73 0.00 380.67 404.79 20.77 142.67 337.17
August 377.83 0.26 0.22 01-AUG-06:19 912.91 18.96 0.00 364.83 474.90 20.97 164.83 327.50
September 365.83 0.26 0.22 01-SEP-06:00 1093.54 18.80 0.00 336.33 589.40 20.88 138.33 302.67
October 318.83 0.25 0.22 01-OCT-06:00 3401.33 25.71 124.83 317.83 843.68 21.61 121.50 301.83
November 295.83 0.24 0.22 01-NOV-12:39 8559.29 37.64 288.33 295.00 1189.81 25.25 127.00 282.33
December 289.50 0.24 0.22 01-DEC-07:10 7640.39 38.07 284.67 283.67 1589.31 27.16 165.50 276.33
                         
Annual Sum or Average 4125.67 0.25     3021.87 24.41 1195.17 3985.17 749.88 22.25 1724.83 3675.83
Minimum of Months 268.33 0.23 0.22   716.26 18.73 0.00 280.33 387.63 20.77 109.50 260.00
Maximum of Months 408.83 0.27 0.22   8559.29 38.52 288.33 380.67 1589.31 27.16 172.50 348.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.66 0.60 01-JAN-08:00 307.44 13.31 0.00 235.83 164.65 17.58 0.00 63.17
February 268.33 0.65 0.60 01-FEB-09:39 347.62 14.01 0.00 242.33 184.25 18.14 0.00 98.33
March 351.83 0.64 0.60 01-MAR-07:49 416.52 14.84 0.00 309.67 207.63 18.74 0.00 155.50
April 373.83 0.62 0.60 01-APR-06:00 494.31 16.00 0.00 355.50 243.44 19.80 2.17 258.83
May 408.83 0.62 0.60 01-MAY-05:00 630.87 16.79 5.33 388.83 281.88 20.39 59.67 359.17
June 398.00 0.61 0.60 01-JUN-05:00 680.81 19.93 82.33 385.33 298.88 20.85 69.33 360.33
July 400.17 0.61 0.60 01-JUL-05:49 654.25 18.09 38.50 397.17 314.45 21.36 69.83 345.00
August 377.83 0.62 0.60 01-AUG-05:00 544.70 16.23 0.00 369.83 265.45 20.01 18.33 306.17
September 365.83 0.64 0.60 01-SEP-08:30 408.81 15.14 0.00 323.83 210.08 19.03 0.00 157.67
October 318.83 0.64 0.60 01-OCT-07:30 366.74 14.36 0.00 289.17 191.32 18.39 0.00 110.17
November 295.83 0.67 0.60 01-NOV-12:39 293.66 13.32 0.00 248.50 158.52 17.57 0.00 50.33
December 289.50 0.66 0.60 01-DEC-08:30 315.54 13.36 0.00 239.17 166.84 17.58 0.00 64.00
                         
Annual Sum or Average 4125.67 0.63     472.88 15.69 126.17 3785.17 230.86 19.29 219.33 2328.67
Minimum of Months 268.33 0.61 0.60   293.66 13.31 0.00 235.83 158.52 17.57 0.00 50.33
Maximum of Months 408.83 0.67 0.60   680.81 19.93 82.33 397.17 314.45 21.36 69.83 360.33



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.66 0.60 01-JAN-08:00 307.44 13.31 0.00 235.83 164.65 17.58 0.00 63.17
February 268.33 0.65 0.60 01-FEB-09:39 347.62 14.01 0.00 242.33 184.25 18.14 0.00 98.33
March 351.83 0.64 0.60 01-MAR-07:49 416.52 14.84 0.00 309.67 207.63 18.74 0.00 155.50
April 373.83 0.62 0.60 01-APR-06:00 494.31 16.00 0.00 355.50 243.44 19.80 2.17 258.83
May 408.83 0.62 0.60 01-MAY-05:00 630.87 16.79 5.33 388.83 281.88 20.39 59.67 359.17
June 398.00 0.61 0.60 01-JUN-05:00 680.81 19.93 82.33 385.33 298.88 20.85 69.33 360.33
July 400.17 0.61 0.60 01-JUL-05:49 654.25 18.09 38.50 397.17 314.45 21.36 69.83 345.00
August 377.83 0.62 0.60 01-AUG-05:00 544.70 16.23 0.00 369.83 265.45 20.01 18.33 306.17
September 365.83 0.64 0.60 01-SEP-08:30 408.81 15.14 0.00 323.83 210.08 19.03 0.00 157.67
October 318.83 0.64 0.60 01-OCT-07:30 366.74 14.36 0.00 289.17 191.32 18.39 0.00 110.17
November 295.83 0.67 0.60 01-NOV-12:39 293.66 13.32 0.00 248.50 158.52 17.57 0.00 50.33
December 289.50 0.66 0.60 01-DEC-08:30 315.54 13.36 0.00 239.17 166.84 17.58 0.00 64.00
                         
Annual Sum or Average 4125.67 0.63     472.88 15.69 126.17 3785.17 230.86 19.29 219.33 2328.67
Minimum of Months 268.33 0.61 0.60   293.66 13.31 0.00 235.83 158.52 17.57 0.00 50.33
Maximum of Months 408.83 0.67 0.60   680.81 19.93 82.33 397.17 314.45 21.36 69.83 360.33



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.498177E+11 100015.36 28-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.323163E+11 98321.80 10-FEB-03:20 0.00 0.00 0.00 0.00 0.00
March 0.233341E+11 95867.60 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.295157E+10 49377.07 12-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 1852810.05 1681.29 30-SEP-06:00 0.00 0.00 0.00 0.00 0.00
October 0.320821E+09 20440.95 25-OCT-03:00 0.00 0.00 0.00 0.00 0.00
November 0.292532E+11 89040.72 28-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.651053E+11 99868.36 30-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.203101E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.651053E+11 100015.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 14648124.33 1343.08 27-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 2109486.00 547.06 01-APR-16:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 16757610.32     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 14648124.33 1343.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128763E+09 769.10 27-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 53818438.04 716.30 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 37239277.42 691.46 02-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 8754.41 15.80 12-APR-06:20 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 70109733.52 682.16 28-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.209420E+09 1189.84 27-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.499360E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.209420E+09 1189.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 821485.35 141.91 17-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 15558.61 25.93 02-MAR-11:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 418814.09 116.91 28-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 3424059.03 216.89 27-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4679917.09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 3424059.03 216.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.284421E+09 462.98 27-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.174355E+09 436.82 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 81726022.92 467.84 02-MAR-11:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 57548640.88 390.14 28-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.398838E+09 537.02 27-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.996889E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.398838E+09 537.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.256860E+09 3293.63 17-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.124702E+09 3002.33 13-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 0.103764E+09 2857.30 24-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 14390443.54 1492.64 12-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 1746041.64 1130.17 03-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 164292.66 273.82 29-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 279099.08 390.54 19-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 1669045.18 1378.87 16-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 9794239.77 1436.36 14-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.210500E+09 3696.67 27-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.229826E+09 3793.64 26-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.953694E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.256860E+09 3793.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.298786E+09 3043.08 17-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 21311578.27 1950.05 03-FEB-07:15 0.00 0.00 0.00 0.00 0.00
March 17785914.26 1519.64 02-MAR-09:04 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.100542E+09 2102.71 29-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.623850E+09 3926.01 27-DEC-07:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.106228E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.623850E+09 3926.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 26109251.75 1262.14 27-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 20203411.23 1367.06 03-FEB-07:30 0.00 0.00 0.00 0.00 0.00
March 2035671.18 414.67 02-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 9605529.41 640.47 28-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.218635E+09 2080.03 27-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.276589E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.218635E+09 2080.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 11792581.23 1688.20 27-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 5005707.53 1435.52 03-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 1143930.02 1043.32 02-MAR-11:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2317344.48 1119.59 28-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 25651406.93 1794.55 28-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 45910970.19     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 25651406.93 1794.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 27541937.75 1320.30 27-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 48532045.49 1782.57 03-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 15146356.32 1128.52 02-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 22180.29 0.38 06-APR-03:20 0.00 0.00 0.00 0.00 0.00
May 32501.55 0.38 19-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 17191.28 0.38 03-JUN-15:18 0.00 0.00 0.00 0.00 0.00
July 18610.63 0.38 14-JUL-04:10 0.00 0.00 0.00 0.00 0.00
August 19710.65 0.38 16-AUG-15:17 0.00 0.00 0.00 0.00 0.00
September 18880.63 0.38 26-SEP-22:03 0.00 0.00 0.00 0.00 0.00
October 19252.76 0.37 01-OCT-05:20 0.00 0.00 0.00 0.00 0.00
November 6704.97 0.36 08-NOV-13:15 0.00 0.00 0.00 0.00 0.00
December 89262066.40 1325.82 27-DEC-07:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180637E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6704.97 0.36   0.00 0.00 0.00 0.00 0.00
Maximum of Months 89262066.40 1782.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.882137E+09 8658.54 14-JAN-16:11 0.00 0.00 0.00 0.00 0.00
February 0.511698E+09 7946.15 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.235153E+09 8674.92 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 11645655.71 2449.34 12-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 1413206.54 2336.72 02-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 124846.68 503.16 30-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 324888.48 1037.39 19-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 582907.81 706.84 18-AUG-08:07 0.00 0.00 0.00 0.00 0.00
September 1353717.50 1677.74 27-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 2767616.64 2277.52 14-OCT-18:06 0.00 0.00 0.00 0.00 0.00
November 0.379641E+09 8697.06 28-NOV-16:11 0.00 0.00 0.00 0.00 0.00
December 0.124597E+10 8857.69 26-DEC-16:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.327281E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 124846.68 503.16   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124597E+10 8857.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.162259E+10 8801.06 27-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.924545E+09 8792.74 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.365424E+09 8743.55 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 13701260.01 2363.36 12-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 1038196.20 2271.95 02-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 77195.67 1029.28 01-JUN-08:36 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 107590.83 327.48 12-AUG-08:57 0.00 0.00 0.00 0.00 0.00
September 438052.78 2147.78 29-SEP-06:25 0.00 0.00 0.00 0.00 0.00
October 4508701.72 2402.36 23-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 0.663261E+09 8755.39 28-NOV-16:11 0.00 0.00 0.00 0.00 0.00
December 0.219395E+10 8907.23 27-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.578965E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.219395E+10 8907.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.272753E+10 50723.15 27-JAN-16:12 0.00 0.00 0.00 0.00 0.00
February 0.149751E+10 47719.35 02-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.364731E+09 19817.84 28-MAR-08:05 0.00 0.00 0.00 0.00 0.00
April 12823400.38 12923.03 12-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 965956.43 5228.00 01-MAY-08:55 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 202412.96 2024.13 21-JUL-21:58 0.00 0.00 0.00 0.00 0.00
August 75346.30 1004.62 28-AUG-08:58 0.00 0.00 0.00 0.00 0.00
September 1915706.30 5427.53 27-SEP-08:56 0.00 0.00 0.00 0.00 0.00
October 8072748.91 7042.53 31-OCT-08:07 0.00 0.00 0.00 0.00 0.00
November 0.865511E+09 28333.34 28-NOV-16:11 0.00 0.00 0.00 0.00 0.00
December 0.468193E+10 50983.76 27-DEC-16:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101613E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.468193E+10 50983.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.962213E+09 8357.71 14-JAN-16:11 0.00 0.00 0.00 0.00 0.00
February 0.493296E+09 2730.40 27-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.252278E+09 6435.23 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 10067926.27 1344.23 11-APR-18:05 0.00 0.00 0.00 0.00 0.00
May 198406.50 955.24 03-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 66873.87 668.74 29-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 378035.88 865.65 16-AUG-18:07 0.00 0.00 0.00 0.00 0.00
September 69313.41 693.13 28-SEP-08:07 0.00 0.00 0.00 0.00 0.00
October 3613438.69 2263.68 15-OCT-18:05 0.00 0.00 0.00 0.00 0.00
November 0.428645E+09 8379.82 28-NOV-16:11 0.00 0.00 0.00 0.00 0.00
December 0.128894E+10 8555.20 26-DEC-16:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.343977E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128894E+10 8555.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.169137E+10 8402.29 14-JAN-16:11 0.00 0.00 0.00 0.00 0.00
February 0.837340E+09 8328.27 02-FEB-16:12 0.00 0.00 0.00 0.00 0.00
March 0.392366E+09 8337.29 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 12779422.84 1248.11 01-APR-21:56 0.00 0.00 0.00 0.00 0.00
May 93558.76 359.87 04-MAY-21:57 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 220.44 2.20 19-JUL-21:57 0.00 0.00 0.00 0.00 0.00
August 118059.40 415.95 16-AUG-21:57 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 9363780.08 2225.40 13-OCT-15:15 0.00 0.00 0.00 0.00 0.00
November 0.718470E+09 8443.40 27-NOV-16:12 0.00 0.00 0.00 0.00 0.00
December 0.218767E+10 8588.76 26-DEC-16:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.584958E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.218767E+10 8588.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.455957E+09 2671.34 14-JAN-16:11 0.00 0.00 0.00 0.00 0.00
February 0.291653E+09 2656.24 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.171538E+09 2672.55 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 21543845.23 1211.78 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 664798.22 573.81 10-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 24664.15 167.13 29-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 113481.71 188.69 18-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 157788.51 376.45 14-AUG-08:06 0.00 0.00 0.00 0.00 0.00
September 313595.91 389.06 28-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 8618327.74 571.55 11-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.239099E+09 2676.98 28-NOV-16:11 0.00 0.00 0.00 0.00 0.00
December 0.594558E+09 2697.78 26-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178424E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 24664.15 167.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.594558E+09 2697.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.731793E+09 2690.25 26-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.454141E+09 2689.28 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.226645E+09 2689.26 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 21550435.36 1336.25 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 316672.32 463.44 05-MAY-08:54 0.00 0.00 0.00 0.00 0.00
June 16382.11 120.52 01-JUN-08:36 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 29640.71 224.83 30-AUG-08:55 0.00 0.00 0.00 0.00 0.00
September 204707.10 305.96 27-SEP-08:54 0.00 0.00 0.00 0.00 0.00
October 11555976.06 587.85 10-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.377815E+09 2689.81 28-NOV-16:11 0.00 0.00 0.00 0.00 0.00
December 0.925707E+09 2691.11 04-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.274978E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.925707E+09 2691.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.584951E+09 12212.46 15-JAN-16:11 0.00 0.00 0.00 0.00 0.00
February 0.370165E+09 4124.47 26-FEB-16:15 0.00 0.00 0.00 0.00 0.00
March 0.264262E+09 8474.27 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 36013065.22 2859.63 12-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 4187812.26 1978.49 02-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 861019.77 835.82 22-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 2085.43 20.85 11-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 493218.48 900.49 24-AUG-08:07 0.00 0.00 0.00 0.00 0.00
September 171427.96 1428.57 25-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 2030494.67 3002.82 07-OCT-18:05 0.00 0.00 0.00 0.00 0.00
November 0.339393E+09 10439.07 27-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.879240E+09 12453.40 26-DEC-16:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.248177E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2085.43 20.85   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.879240E+09 12453.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.735597E+10 0.735597E+10 97826.64 03-JAN-17:00 97826.64 0.00
February 0.00 0.00 0.357677E+11 0.357677E+11 130386.03 20-FEB-16:15 130386.03 0.00
March 0.00 0.00 0.720688E+11 0.720688E+11 164116.31 14-MAR-18:10 164116.31 0.00
April 0.00 0.00 0.210249E+12 0.210249E+12 211174.27 19-APR-18:10 211174.27 0.11
May 0.00 0.00 0.341748E+12 0.339650E+12 238014.13 28-MAY-10:35 181583.16 0.44
June 0.00 0.00 0.434809E+12 0.428348E+12 274802.82 19-JUN-18:10 196134.06 0.75
July 0.00 0.00 0.575268E+12 0.450319E+12 390180.42 21-JUL-21:00 200690.84 1.00
August 0.00 0.00 0.474622E+12 0.420981E+12 359285.98 11-AUG-20:00 182707.10 0.99
September 0.00 0.00 0.392229E+12 0.336047E+12 322920.33 09-SEP-20:00 177797.14 0.86
October 0.00 0.00 0.198647E+12 0.189666E+12 310491.35 03-OCT-19:55 199749.69 0.45
November 0.00 0.00 0.434875E+11 0.434875E+11 150611.77 03-NOV-16:00 150611.77 0.03
December 0.00 0.00 0.433284E+10 0.433284E+10 54499.31 09-DEC-13:00 54499.31 0.00
                 
Annual Sum or Average 0.00 0.00 0.279059E+13 0.253827E+13       0.39
Minimum of Months 0.00 0.00 0.433284E+10 0.433284E+10 54499.31   54499.31 0.00
Maximum of Months 0.00 0.00 0.575268E+12 0.450319E+12 390180.42   211174.27 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.389195E+09 0.389195E+09 11015.35 03-JAN-17:00 11015.35 0.00
February 0.00 0.00 0.196624E+10 0.196624E+10 14147.22 20-FEB-16:12 14147.22 0.00
March 0.00 0.00 0.406941E+10 0.406941E+10 14783.01 22-MAR-15:12 14783.01 0.00
April 0.00 0.00 0.138040E+11 0.138040E+11 17603.89 21-APR-15:12 17603.89 0.08
May 0.00 0.00 0.229551E+11 0.223895E+11 21921.47 24-MAY-13:00 16129.57 0.28
June 0.00 0.00 0.287850E+11 0.274840E+11 24534.76 27-JUN-24:00 12151.89 0.54
July 0.00 0.00 0.409763E+11 0.289621E+11 39037.79 21-JUL-08:03 13821.47 0.76
August 0.00 0.00 0.334889E+11 0.272298E+11 33349.38 03-AUG-06:25 14361.93 0.76
September 0.00 0.00 0.280526E+11 0.211888E+11 31964.14 22-SEP-08:03 14826.78 0.65
October 0.00 0.00 0.130966E+11 0.117143E+11 27787.51 03-OCT-20:20 14079.20 0.33
November 0.00 0.00 0.249625E+10 0.249625E+10 14436.71 09-NOV-16:12 14436.71 0.01
December 0.00 0.00 0.199728E+09 0.199728E+09 5697.71 10-DEC-14:00 5697.71 0.00
                 
Annual Sum or Average 0.00 0.00 0.190279E+12 0.161893E+12       0.29
Minimum of Months 0.00 0.00 0.199728E+09 0.199728E+09 5697.71   5697.71 0.00
Maximum of Months 0.00 0.00 0.409763E+11 0.289621E+11 39037.79   17603.89 0.76



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.827957E+09 0.759643E+09 7986.47 12-JAN-16:12 7986.47 0.07
February 0.00 0.00 0.125200E+10 0.123677E+10 7984.36 18-FEB-16:12 7984.36 0.02
March 0.00 0.00 0.231627E+10 0.229052E+10 7985.93 12-MAR-15:12 7985.93 0.03
April 0.00 0.00 0.500494E+10 0.472549E+10 7986.10 20-APR-18:02 7986.10 0.23
May 0.00 0.00 0.752204E+10 0.671793E+10 8847.76 28-MAY-08:62 7425.34 0.53
June 0.00 0.00 0.937067E+10 0.802955E+10 8918.67 29-JUN-08:62 7225.67 0.76
July 0.00 0.00 0.999817E+10 0.745651E+10 10494.04 19-JUL-08:62 6329.90 0.96
August 0.00 0.00 0.919799E+10 0.696184E+10 9540.51 14-AUG-08:62 6732.27 0.94
September 0.00 0.00 0.854472E+10 0.650396E+10 9704.79 23-SEP-18:02 6860.99 0.93
October 0.00 0.00 0.575921E+10 0.440234E+10 9259.93 04-OCT-08:62 7154.25 0.76
November 0.00 0.00 0.226482E+10 0.209455E+10 7986.39 25-NOV-16:12 7986.39 0.15
December 0.00 0.00 0.504217E+09 0.487247E+09 7985.44 13-DEC-16:12 7985.44 0.02
                 
Annual Sum or Average 0.00 0.00 0.625630E+11 0.516663E+11       0.45
Minimum of Months 0.00 0.00 0.504217E+09 0.487247E+09 7984.36   6329.90 0.02
Maximum of Months 0.00 0.00 0.999817E+10 0.802955E+10 10494.04   7986.47 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.137719E+09 0.129997E+09 7825.63 30-JAN-16:12 7825.63 0.01
February 0.00 0.00 0.238587E+09 0.233757E+09 7924.44 24-FEB-16:12 7924.44 0.01
March 0.00 0.00 0.843632E+09 0.825271E+09 7928.45 27-MAR-18:02 7928.45 0.02
April 0.00 0.00 0.372084E+10 0.349884E+10 8745.06 06-APR-18:11 8745.06 0.19
May 0.00 0.00 0.677868E+10 0.610279E+10 9222.45 28-MAY-08:51 7479.41 0.47
June 0.00 0.00 0.896919E+10 0.777796E+10 9335.11 04-JUN-08:51 7628.47 0.68
July 0.00 0.00 0.943781E+10 0.717499E+10 10942.18 21-JUL-08:51 6097.98 0.85
August 0.00 0.00 0.814379E+10 0.623361E+10 10517.89 03-AUG-08:61 7227.33 0.81
September 0.00 0.00 0.653825E+10 0.494636E+10 10098.32 03-SEP-08:51 7019.88 0.74
October 0.00 0.00 0.315143E+10 0.217868E+10 9534.93 03-OCT-21:52 7077.86 0.54
November 0.00 0.00 0.580811E+09 0.490307E+09 7928.99 12-NOV-16:12 7928.99 0.08
December 0.00 0.00 55445921.03 53835635.55 7890.03 16-DEC-16:12 7890.03 0.00
                 
Annual Sum or Average 0.00 0.00 0.485962E+11 0.396464E+11       0.37
Minimum of Months 0.00 0.00 55445921.03 53835635.55 7825.63   6097.98 0.00
Maximum of Months 0.00 0.00 0.943781E+10 0.777796E+10 10942.18   8745.06 0.85



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.204228E+11 0.204219E+11 34961.56 12-JAN-14:25 34961.56 0.00
February 0.00 0.00 0.203562E+11 0.201152E+11 33121.84 07-FEB-13:40 33121.84 0.03
March 0.00 0.00 0.192018E+11 0.190216E+11 25972.04 07-MAR-13:10 25972.04 0.02
April 0.00 0.00 0.253771E+11 0.243412E+11 23649.73 03-APR-13:30 23649.73 0.10
May 0.00 0.00 0.304047E+11 0.258544E+11 23035.89 19-MAY-20:20 20334.45 0.35
June 0.00 0.00 0.370388E+11 0.283622E+11 25886.40 07-JUN-20:20 20321.52 0.67
July 0.00 0.00 0.409057E+11 0.243096E+11 27810.86 15-JUL-07:40 17701.06 1.00
August 0.00 0.00 0.415682E+11 0.269093E+11 28364.51 05-AUG-08:00 21595.22 1.00
September 0.00 0.00 0.460845E+11 0.329229E+11 34361.11 19-SEP-13:30 29397.65 0.98
October 0.00 0.00 0.414235E+11 0.340681E+11 40442.42 22-OCT-13:15 37252.13 0.60
November 0.00 0.00 0.299880E+11 0.289329E+11 38645.35 10-NOV-12:00 35083.49 0.11
December 0.00 0.00 0.178172E+11 0.178172E+11 30776.10 07-DEC-14:00 30776.10 0.00
                 
Annual Sum or Average 0.00 0.00 0.370589E+12 0.303076E+12       0.41
Minimum of Months 0.00 0.00 0.178172E+11 0.178172E+11 23035.89   17701.06 0.00
Maximum of Months 0.00 0.00 0.460845E+11 0.340681E+11 40442.42   37252.13 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.383048E+10 0.332584E+10 50602.48 16-JAN-09:02 49424.25 0.08
February 0.00 0.00 0.642231E+10 0.591347E+10 51913.19 21-FEB-21:32 51913.19 0.07
March 0.00 0.00 0.123305E+11 0.119309E+11 52776.74 22-MAR-20:22 52776.74 0.04
April 0.00 0.00 0.272475E+11 0.260851E+11 53787.32 05-APR-21:52 53787.32 0.15
May 0.00 0.00 0.435612E+11 0.395448E+11 58312.81 23-MAY-21:51 51759.48 0.40
June 0.00 0.00 0.562394E+11 0.487453E+11 58345.92 19-JUN-18:51 53405.32 0.63
July 0.00 0.00 0.613447E+11 0.469682E+11 69833.08 21-JUL-08:51 41898.60 0.78
August 0.00 0.00 0.523016E+11 0.399651E+11 64874.91 03-AUG-08:61 49465.16 0.73
September 0.00 0.00 0.407100E+11 0.305085E+11 64963.46 23-SEP-21:52 47162.38 0.63
October 0.00 0.00 0.258010E+11 0.192838E+11 63234.48 03-OCT-21:52 47436.84 0.46
November 0.00 0.00 0.817925E+10 0.709468E+10 51496.49 08-NOV-22:52 51496.49 0.13
December 0.00 0.00 0.275223E+10 0.256114E+10 50403.98 09-DEC-09:02 50403.98 0.03
                 
Annual Sum or Average 0.00 0.00 0.340720E+12 0.281927E+12       0.35
Minimum of Months 0.00 0.00 0.275223E+10 0.256114E+10 50403.98   41898.60 0.03
Maximum of Months 0.00 0.00 0.613447E+11 0.487453E+11 69833.08   53787.32 0.78



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.743881E+09 0.682936E+09 7102.99 31-JAN-09:02 7102.99 0.08
February 0.00 0.00 0.141938E+10 0.139213E+10 7103.15 05-FEB-09:02 7103.15 0.03
March 0.00 0.00 0.236087E+10 0.233555E+10 7103.25 28-MAR-08:62 7103.25 0.03
April 0.00 0.00 0.526739E+10 0.500164E+10 7103.05 20-APR-18:02 7103.05 0.24
May 0.00 0.00 0.770845E+10 0.697268E+10 7513.65 28-MAY-08:62 6833.82 0.54
June 0.00 0.00 0.965528E+10 0.848216E+10 7910.48 29-JUN-08:62 6437.19 0.77
July 0.00 0.00 0.102672E+11 0.796673E+10 9355.28 19-JUL-08:62 5615.04 0.98
August 0.00 0.00 0.944003E+10 0.747625E+10 8488.33 14-AUG-08:62 5977.69 0.97
September 0.00 0.00 0.863597E+10 0.676969E+10 8544.71 23-SEP-18:02 6159.80 0.95
October 0.00 0.00 0.538345E+10 0.416478E+10 8397.51 15-OCT-08:62 6257.79 0.77
November 0.00 0.00 0.216367E+10 0.201480E+10 7332.74 03-NOV-08:62 6948.11 0.15
December 0.00 0.00 0.540091E+09 0.516509E+09 7102.93 10-DEC-09:02 7102.93 0.03
                 
Annual Sum or Average 0.00 0.00 0.635857E+11 0.537758E+11       0.46
Minimum of Months 0.00 0.00 0.540091E+09 0.516509E+09 7102.93   5615.04 0.03
Maximum of Months 0.00 0.00 0.102672E+11 0.848216E+10 9355.28   7103.25 0.98



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.104959E+09 81848200.31 6830.64 31-JAN-09:02 6830.64 0.02
February 0.00 0.00 0.420071E+09 0.402433E+09 7055.07 20-FEB-09:02 7055.07 0.02
March 0.00 0.00 0.106237E+10 0.104234E+10 7056.00 28-MAR-08:62 7056.00 0.02
April 0.00 0.00 0.394513E+10 0.372504E+10 8048.33 27-APR-08:51 8048.33 0.20
May 0.00 0.00 0.672810E+10 0.611144E+10 8845.44 28-MAY-08:51 7703.99 0.49
June 0.00 0.00 0.905252E+10 0.800038E+10 9233.85 20-JUN-08:62 8389.70 0.69
July 0.00 0.00 0.951992E+10 0.745790E+10 10136.13 21-JUL-08:51 6331.55 0.87
August 0.00 0.00 0.819866E+10 0.648115E+10 9696.19 02-AUG-08:51 7160.34 0.83
September 0.00 0.00 0.641476E+10 0.485441E+10 9656.55 09-SEP-08:51 7188.91 0.77
October 0.00 0.00 0.294889E+10 0.206299E+10 8781.12 05-OCT-08:51 7717.60 0.57
November 0.00 0.00 0.611975E+09 0.542804E+09 7378.82 09-NOV-09:51 7378.82 0.07
December 0.00 0.00 73611596.83 64084423.52 6898.52 16-DEC-09:02 6898.52 0.01
                 
Annual Sum or Average 0.00 0.00 0.490810E+11 0.408268E+11       0.38
Minimum of Months 0.00 0.00 73611596.83 64084423.52 6830.64   6331.55 0.01
Maximum of Months 0.00 0.00 0.951992E+10 0.800038E+10 10136.13   8389.70 0.87



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.156443E+09 0.146933E+09 2131.04 18-JAN-16:12 2131.04 0.04
February 0.00 0.00 0.258809E+09 0.256997E+09 2130.52 18-FEB-16:12 2130.52 0.01
March 0.00 0.00 0.507184E+09 0.503682E+09 2130.90 12-MAR-15:12 2130.90 0.01
April 0.00 0.00 0.122509E+10 0.115527E+10 2130.91 20-APR-18:02 2130.91 0.22
May 0.00 0.00 0.190157E+10 0.168624E+10 2414.24 28-MAY-08:62 1946.65 0.53
June 0.00 0.00 0.244947E+10 0.208714E+10 2457.51 29-JUN-08:62 1824.18 0.76
July 0.00 0.00 0.262878E+10 0.195146E+10 2928.79 19-JUL-08:62 1567.18 0.96
August 0.00 0.00 0.237502E+10 0.178249E+10 2638.85 18-AUG-08:62 1786.17 0.95
September 0.00 0.00 0.212982E+10 0.158594E+10 2684.80 09-SEP-08:62 1767.07 0.92
October 0.00 0.00 0.131694E+10 0.995989E+09 2564.37 09-OCT-08:62 1738.90 0.70
November 0.00 0.00 0.452523E+09 0.420814E+09 2131.03 25-NOV-16:12 2131.03 0.11
December 0.00 0.00 93436782.33 91275825.96 2130.77 13-DEC-16:12 2130.77 0.01
                 
Annual Sum or Average 0.00 0.00 0.154951E+11 0.126642E+11       0.44
Minimum of Months 0.00 0.00 93436782.33 91275825.96 2130.52   1567.18 0.01
Maximum of Months 0.00 0.00 0.262878E+10 0.208714E+10 2928.79   2131.04 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 21685294.63 20592681.82 2046.80 30-JAN-16:12 2046.80 0.00
February 0.00 0.00 35252445.00 34865904.12 2079.56 24-FEB-16:12 2079.56 0.00
March 0.00 0.00 0.152566E+09 0.150211E+09 2113.08 27-MAR-18:02 2113.08 0.01
April 0.00 0.00 0.917559E+09 0.859334E+09 2336.90 06-APR-18:11 2336.90 0.19
May 0.00 0.00 0.174768E+10 0.156221E+10 2469.31 28-MAY-08:51 1973.51 0.47
June 0.00 0.00 0.238106E+10 0.205865E+10 2519.77 04-JUN-08:51 2020.87 0.69
July 0.00 0.00 0.251746E+10 0.191580E+10 2982.86 21-JUL-08:51 1594.32 0.85
August 0.00 0.00 0.213977E+10 0.162976E+10 2857.77 03-AUG-08:61 1864.42 0.82
September 0.00 0.00 0.165644E+10 0.122868E+10 2753.46 03-SEP-08:51 1824.42 0.75
October 0.00 0.00 0.677361E+09 0.463733E+09 2592.14 03-OCT-21:52 1830.06 0.49
November 0.00 0.00 78503404.92 64967015.29 2113.24 12-NOV-16:12 2113.24 0.05
December 0.00 0.00 9279821.12 8905495.42 2074.86 16-DEC-16:12 2074.86 0.00
                 
Annual Sum or Average 0.00 0.00 0.123346E+11 0.999771E+10       0.36
Minimum of Months 0.00 0.00 9279821.12 8905495.42 2046.80   1594.32 0.00
Maximum of Months 0.00 0.00 0.251746E+10 0.205865E+10 2982.86   2336.90 0.85



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.434229E+10 0.409506E+10 9863.21 08-JAN-16:12 9863.21 0.21
February 0.00 0.00 0.432018E+10 0.423633E+10 9863.70 18-FEB-16:12 9863.70 0.07
March 0.00 0.00 0.431828E+10 0.425711E+10 9863.49 27-MAR-15:12 9863.49 0.05
April 0.00 0.00 0.639478E+10 0.600858E+10 10032.52 18-APR-18:02 9727.65 0.25
May 0.00 0.00 0.837581E+10 0.716032E+10 10901.82 28-MAY-08:62 9175.81 0.61
June 0.00 0.00 0.107895E+11 0.897371E+10 10818.09 29-JUN-08:62 8591.31 0.81
July 0.00 0.00 0.122344E+11 0.892935E+10 13521.45 19-JUL-08:62 7222.09 0.95
August 0.00 0.00 0.119002E+11 0.895427E+10 11949.65 02-AUG-08:62 8494.29 0.94
September 0.00 0.00 0.121217E+11 0.942916E+10 12375.49 23-SEP-18:02 8212.07 0.93
October 0.00 0.00 0.996985E+10 0.823516E+10 11460.33 04-OCT-08:62 8755.91 0.79
November 0.00 0.00 0.638060E+10 0.607773E+10 9939.71 03-NOV-08:62 9450.26 0.22
December 0.00 0.00 0.390340E+10 0.378614E+10 9863.16 10-DEC-09:02 9863.16 0.10
                 
Annual Sum or Average 0.00 0.00 0.950509E+11 0.801429E+11       0.50
Minimum of Months 0.00 0.00 0.390340E+10 0.378614E+10 9863.16   7222.09 0.05
Maximum of Months 0.00 0.00 0.122344E+11 0.942916E+10 13521.45   9863.70 0.95



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 52.02 6374.61 05-JAN-19:03 22329.61 128252.46 28-JAN-07:40
February 38.50 2646.33 02-FEB-19:03 15589.56 131171.62 02-FEB-03:30
March 12.64 2398.29 04-MAR-09:20 9565.46 132990.71 02-MAR-09:01
April 0.75 784.85 01-APR-05:50 1184.57 48795.33 12-APR-06:00
May 0.00 0.00 01-MAY-00:10 9.62 15609.73 02-MAY-08:05
June 0.00 0.00 01-JUN-00:10 1.16 2615.57 30-JUN-08:07
July 0.00 0.00 01-JUL-00:10 0.53 4524.06 21-JUL-21:58
August 0.00 0.00 01-AUG-00:10 1.82 3620.14 17-AUG-08:07
September 0.00 0.00 01-SEP-00:10 2.68 7187.44 11-SEP-08:57
October 2.08 480.92 08-OCT-06:00 135.60 20394.73 13-OCT-08:06
November 18.69 2208.42 05-NOV-08:20 12859.70 128514.13 28-NOV-16:11
December 34.68 4687.27 29-DEC-16:12 29865.05 182040.25 26-DEC-16:11
             
Annual Sum or Average 13.16     7608.46    
Minimum of Months 0.00 0.00   0.53 2615.57  
Maximum of Months 52.02 6374.61   29865.05 182040.25  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 15842.41 145854.21 03-JAN-16:13 0.00 0.00 01-JAN-00:05
February 31723.47 197296.12 20-FEB-16:15 0.00 0.00 01-FEB-00:05
March 46451.71 283105.34 14-MAR-15:12 0.00 0.00 01-MAR-00:05
April 119004.07 336629.29 28-APR-21:51 0.00 0.00 01-APR-00:10
May 181095.88 370461.86 24-MAY-18:03 0.00 0.00 01-MAY-00:10
June 237279.66 417244.15 19-JUN-18:51 0.00 0.00 01-JUN-00:10
July 291442.37 511025.55 21-JUL-21:00 0.00 0.00 01-JUL-00:10
August 246037.73 466083.33 01-AUG-21:51 0.00 0.00 01-AUG-00:10
September 215484.09 418333.08 03-SEP-21:51 0.00 0.00 01-SEP-00:10
October 117126.54 416898.34 04-OCT-18:03 0.00 0.00 01-OCT-00:10
November 39027.17 216893.28 03-NOV-15:40 0.00 0.00 01-NOV-00:10
December 12768.18 112679.87 15-DEC-19:02 0.00 0.00 01-DEC-00:05
             
Annual Sum or Average 129988.54     0.00    
Minimum of Months 12768.18 112679.87   0.00 0.00  
Maximum of Months 291442.37 511025.55   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 25475.07 51785.00 30-JAN-07:53
February 0.00 0.00 01-FEB-00:05 25456.05 51781.88 02-FEB-07:57
March 0.00 0.00 01-MAR-00:05 24602.03 50773.65 01-MAR-08:00
April 0.00 0.00 01-APR-00:10 23055.55 47957.60 03-APR-06:58
May 0.00 0.00 01-MAY-00:10 21280.82 44614.85 01-MAY-07:00
June 0.00 0.00 01-JUN-00:10 19743.82 40902.66 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 18839.03 38180.40 03-JUL-07:00
August 0.00 0.00 01-AUG-00:10 18864.45 38383.47 31-AUG-07:00
September 0.00 0.00 01-SEP-00:10 19756.27 40891.61 29-SEP-06:25
October 0.00 0.00 01-OCT-00:10 21296.51 44591.64 31-OCT-06:20
November 0.00 0.00 01-NOV-00:10 23074.08 48129.41 30-NOV-08:00
December 0.00 0.00 01-DEC-00:05 24599.80 50742.00 29-DEC-07:55
             
Annual Sum or Average 0.00     22151.64    
Minimum of Months 0.00 0.00   18839.03 38180.40  
Maximum of Months 0.00 0.00   25475.07 51785.00  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.261333E+10 0.77 1299.30 01-JAN-16:17 1.01
February 0.236042E+10 0.77 1299.30 02-FEB-16:15 1.02
March 0.261333E+10 0.77 1299.30 01-MAR-16:40 1.01
April 0.252903E+10 0.77 1299.30 01-APR-15:30 1.01
May 0.261333E+10 0.77 1299.30 02-MAY-15:20 1.01
June 0.252903E+10 0.77 1299.30 01-JUN-08:38 1.01
July 0.261333E+10 0.77 1299.30 01-JUL-01:00 1.00
August 0.261333E+10 0.77 1299.30 01-AUG-00:10 1.00
September 0.252903E+10 0.77 1299.30 01-SEP-21:20 1.00
October 0.261333E+10 0.77 1299.30 01-OCT-16:30 1.01
November 0.252903E+10 0.77 1299.30 04-NOV-15:20 1.01
December 0.261333E+10 0.77 1299.30 01-DEC-16:13 1.01
           
Annual Sum or Average 0.307698E+11 0.77      
Minimum of Months 0.236042E+10 0.77 1299.30   1.00
Maximum of Months 0.261333E+10 0.77 1299.30   1.02



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.384496E+11 0.97 20863.33 03-JAN-22:10 1.20
February 0.350332E+11 0.97 22243.36 06-FEB-22:10 1.25
March 0.391339E+11 0.98 23661.20 16-MAR-21:10 1.30
April 0.395443E+11 1.00 28102.86 19-APR-21:20 1.43
May 0.430588E+11 1.02 31686.79 31-MAY-21:20 1.54
June 0.443439E+11 1.06 34218.76 16-JUN-21:20 1.62
July 0.455324E+11 1.05 33927.34 26-JUL-21:20 1.60
August 0.459472E+11 1.05 37376.05 07-AUG-21:20 1.70
September 0.444109E+11 1.06 35279.76 22-SEP-21:10 1.64
October 0.433742E+11 1.03 34753.08 05-OCT-21:10 1.62
November 0.394372E+11 1.00 29594.02 09-NOV-22:10 1.48
December 0.388592E+11 0.97 21752.82 01-DEC-19:50 1.23
           
Annual Sum or Average 0.497125E+12 1.01      
Minimum of Months 0.350332E+11 0.97 20863.33   1.20
Maximum of Months 0.459472E+11 1.06 37376.05   1.70



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.31 76.61 01-JAN-00:05 0.31
February 0.185347E+09 0.31 76.61 01-FEB-00:05 0.31
March 0.205205E+09 0.31 76.61 01-MAR-00:05 0.31
April 0.198586E+09 0.31 76.61 01-APR-00:10 0.31
May 0.205205E+09 0.31 76.61 01-MAY-00:10 0.31
June 0.198586E+09 0.30 76.61 01-JUN-00:10 0.30
July 0.205205E+09 0.30 76.61 01-JUL-00:10 0.30
August 0.205205E+09 0.30 76.61 01-AUG-00:10 0.30
September 0.198586E+09 0.30 76.61 01-SEP-00:10 0.30
October 0.205205E+09 0.30 76.61 01-OCT-00:10 0.31
November 0.198586E+09 0.31 76.61 01-NOV-00:10 0.31
December 0.205205E+09 0.31 76.61 01-DEC-00:05 0.31
           
Annual Sum or Average 0.241613E+10 0.31      
Minimum of Months 0.185347E+09 0.30 76.61   0.30
Maximum of Months 0.205205E+09 0.31 76.61   0.31



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 -0.0
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 -0.0
April 0.00 -0.0 0.00 01-APR-00:10 -0.0
May 0.00 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:05 -0.0
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.22 612.92 01-JAN-07:10 0.31
February 0.105030E+10 0.22 612.92 01-FEB-07:05 0.31
March 0.116283E+10 0.22 612.92 01-MAR-07:05 0.31
April 0.112532E+10 0.22 612.92 01-APR-06:05 0.31
May 0.116283E+10 0.22 612.92 01-MAY-06:05 0.31
June 0.112532E+10 0.22 612.92 01-JUN-06:05 0.31
July 0.116283E+10 0.21 612.92 01-JUL-06:05 0.30
August 0.116283E+10 0.21 612.92 01-AUG-06:05 0.30
September 0.112532E+10 0.21 612.92 01-SEP-06:05 0.30
October 0.116283E+10 0.22 612.92 01-OCT-06:10 0.31
November 0.112532E+10 0.22 612.92 01-NOV-06:05 0.30
December 0.116283E+10 0.22 612.92 01-DEC-07:05 0.31
           
Annual Sum or Average 0.136914E+11 0.22      
Minimum of Months 0.105030E+10 0.21 612.92   0.30
Maximum of Months 0.116283E+10 0.22 612.92   0.31



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.155541E+09 0.49 684.84 01-JAN-16:12 0.66
February 0.161648E+09 0.51 684.84 01-FEB-16:12 0.67
March 0.234707E+09 0.53 684.84 01-MAR-16:12 0.66
April 0.442484E+09 0.58 684.84 01-APR-08:62 0.66
May 0.654092E+09 0.62 684.84 01-MAY-08:62 0.66
June 0.797346E+09 0.63 684.84 01-JUN-08:62 0.66
July 0.771750E+09 0.63 684.84 01-JUL-08:62 0.66
August 0.719499E+09 0.62 684.84 01-AUG-08:62 0.66
September 0.663474E+09 0.62 684.84 01-SEP-08:62 0.66
October 0.478603E+09 0.59 684.84 01-OCT-08:62 0.66
November 0.233412E+09 0.54 684.84 01-NOV-08:62 0.66
December 0.147449E+09 0.48 684.84 01-DEC-16:12 0.66
           
Annual Sum or Average 0.546000E+10 0.57      
Minimum of Months 0.147449E+09 0.48 684.84   0.66
Maximum of Months 0.797346E+09 0.63 684.84   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.137391E+09 0.44 679.91 01-JAN-16:12 0.66
February 0.100103E+09 0.42 679.91 01-FEB-09:01 0.66
March 0.118220E+09 0.41 679.91 01-MAR-09:02 0.66
April 0.333638E+09 0.46 679.91 01-APR-08:51 0.66
May 0.597602E+09 0.52 679.91 01-MAY-08:51 0.66
June 0.775625E+09 0.57 679.91 01-JUN-08:31 0.66
July 0.740174E+09 0.56 679.91 01-JUL-08:62 0.66
August 0.643734E+09 0.54 679.91 01-AUG-07:52 0.66
September 0.506605E+09 0.50 679.91 01-SEP-08:51 0.65
October 0.261269E+09 0.41 679.91 01-OCT-08:52 0.66
November 0.115632E+09 0.43 679.91 01-NOV-15:12 0.66
December 0.157835E+09 0.44 679.91 02-DEC-16:11 0.66
           
Annual Sum or Average 0.448783E+10 0.47      
Minimum of Months 0.100103E+09 0.41 679.91   0.65
Maximum of Months 0.775625E+09 0.57 679.91   0.66



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.113536E+10 0.39 2068.81 12-JAN-14:25 0.66
February 0.114255E+10 0.46 1991.83 07-FEB-13:40 0.67
March 0.112422E+10 0.48 1190.04 07-MAR-13:10 0.66
April 0.146416E+10 0.60 1145.19 19-APR-17:15 0.66
May 0.171898E+10 0.65 1151.43 19-MAY-21:00 0.66
June 0.197339E+10 0.66 2044.60 07-JUN-20:20 0.66
July 0.196417E+10 0.66 1170.32 02-JUL-20:40 0.66
August 0.206110E+10 0.66 1282.82 27-AUG-13:50 0.66
September 0.233910E+10 0.66 2388.71 30-SEP-13:20 0.66
October 0.230297E+10 0.63 3634.91 22-OCT-13:15 0.66
November 0.168645E+10 0.48 3582.79 10-NOV-12:10 0.66
December 0.999272E+09 0.38 1891.97 07-DEC-14:00 0.67
           
Annual Sum or Average 0.199117E+11 0.56      
Minimum of Months 0.999272E+09 0.38 1145.19   0.66
Maximum of Months 0.233910E+10 0.66 3634.91   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.685646E+09 0.44 4420.77 01-JAN-09:02 0.66
February 0.756577E+09 0.40 4420.77 04-FEB-09:02 0.66
March 0.111736E+10 0.37 4420.77 01-MAR-09:02 0.66
April 0.232018E+10 0.39 4420.77 01-APR-08:51 0.67
May 0.385587E+10 0.46 4420.77 01-MAY-08:51 0.67
June 0.493641E+10 0.52 4420.77 01-JUN-08:31 0.66
July 0.491358E+10 0.51 4420.77 01-JUL-08:62 0.66
August 0.420053E+10 0.48 4420.77 01-AUG-07:52 0.66
September 0.316478E+10 0.42 4420.77 01-SEP-08:51 0.66
October 0.198726E+10 0.35 4420.77 01-OCT-08:52 0.66
November 0.854058E+09 0.40 4420.77 01-NOV-08:62 0.66
December 0.727454E+09 0.44 4420.77 01-DEC-09:02 0.66
           
Annual Sum or Average 0.295197E+11 0.43      
Minimum of Months 0.685646E+09 0.35 4420.77   0.66
Maximum of Months 0.493641E+10 0.52 4420.77   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144553E+09 0.47 608.38 01-JAN-09:02 0.66
February 0.170519E+09 0.52 608.38 01-FEB-09:01 0.66
March 0.235095E+09 0.56 608.38 01-MAR-09:02 0.66
April 0.464558E+09 0.62 608.38 01-APR-08:62 0.66
May 0.668823E+09 0.64 608.38 01-MAY-08:62 0.66
June 0.828224E+09 0.65 608.38 01-JUN-08:62 0.66
July 0.804495E+09 0.64 608.38 01-JUL-08:62 0.66
August 0.748739E+09 0.64 608.38 01-AUG-08:62 0.66
September 0.676103E+09 0.64 608.38 01-SEP-08:62 0.66
October 0.452295E+09 0.60 608.38 01-OCT-08:62 0.66
November 0.234071E+09 0.56 608.38 01-NOV-08:62 0.66
December 0.141478E+09 0.46 608.38 01-DEC-09:02 0.66
           
Annual Sum or Average 0.556895E+10 0.58      
Minimum of Months 0.141478E+09 0.46 608.38   0.66
Maximum of Months 0.828224E+09 0.65 608.38   0.66



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.127656E+09 0.44 604.30 02-JAN-09:02 0.66
February 0.103113E+09 0.41 604.30 02-FEB-16:12 0.67
March 0.133672E+09 0.41 604.30 01-MAR-09:02 0.66
April 0.353203E+09 0.51 604.30 01-APR-08:51 0.66
May 0.587027E+09 0.54 604.30 01-MAY-08:51 0.66
June 0.783639E+09 0.58 604.30 01-JUN-08:31 0.66
July 0.750639E+09 0.57 604.30 01-JUL-08:62 0.66
August 0.647892E+09 0.55 604.30 01-AUG-07:52 0.66
September 0.489981E+09 0.51 604.30 01-SEP-08:51 0.65
October 0.250169E+09 0.44 604.30 01-OCT-08:52 0.66
November 0.113469E+09 0.41 604.30 01-NOV-15:12 0.66
December 0.145979E+09 0.44 604.30 01-DEC-09:02 0.66
           
Annual Sum or Average 0.448644E+10 0.49      
Minimum of Months 0.103113E+09 0.41 604.30   0.65
Maximum of Months 0.783639E+09 0.58 604.30   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 45526714.93 0.48 182.86 01-JAN-16:12 0.66
February 44179629.10 0.50 182.86 01-FEB-09:01 0.66
March 59484875.17 0.52 182.86 01-MAR-16:12 0.66
April 0.111769E+09 0.58 182.86 01-APR-15:12 0.66
May 0.166896E+09 0.62 182.86 01-MAY-08:62 0.66
June 0.206714E+09 0.63 182.86 01-JUN-08:62 0.66
July 0.200994E+09 0.63 182.86 01-JUL-08:62 0.66
August 0.184636E+09 0.62 182.86 01-AUG-08:62 0.66
September 0.166643E+09 0.62 182.86 01-SEP-08:62 0.65
October 0.112310E+09 0.58 182.86 01-OCT-08:62 0.66
November 57211737.57 0.53 182.86 02-NOV-15:12 0.66
December 46182267.73 0.48 182.86 01-DEC-16:12 0.66
           
Annual Sum or Average 0.140255E+10 0.57      
Minimum of Months 44179629.10 0.48 182.86   0.65
Maximum of Months 0.206714E+09 0.63 182.86   0.66



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 46485665.80 0.44 181.33 01-JAN-16:12 0.66
February 32882540.11 0.42 181.33 01-FEB-09:01 0.66
March 31850867.02 0.40 181.33 01-MAR-09:02 0.66
April 85485278.90 0.47 181.33 01-APR-15:12 0.66
May 0.155293E+09 0.52 181.33 01-MAY-08:51 0.66
June 0.204331E+09 0.57 181.33 01-JUN-08:31 0.66
July 0.195343E+09 0.56 181.33 01-JUL-08:62 0.66
August 0.168021E+09 0.54 181.33 01-AUG-07:52 0.65
September 0.129863E+09 0.50 181.33 01-SEP-08:51 0.65
October 58925636.94 0.41 181.33 01-OCT-08:52 0.66
November 33425137.61 0.43 181.33 03-NOV-18:42 0.66
December 53401498.25 0.45 181.33 02-DEC-16:11 0.66
           
Annual Sum or Average 0.119531E+10 0.48      
Minimum of Months 31850867.02 0.40 181.33   0.65
Maximum of Months 0.204331E+09 0.57 181.33   0.66



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.425699E+09 0.57 832.33 01-JAN-09:02 0.66
February 0.388775E+09 0.57 832.33 01-FEB-09:01 0.66
March 0.386439E+09 0.57 832.33 01-MAR-09:02 0.66
April 0.552295E+09 0.60 832.33 01-APR-08:62 0.66
May 0.727180E+09 0.61 832.33 01-MAY-08:62 0.67
June 0.901249E+09 0.63 832.33 01-JUN-08:62 0.66
July 0.915801E+09 0.62 832.33 01-JUL-08:62 0.66
August 0.914278E+09 0.62 832.33 01-AUG-08:62 0.66
September 0.945969E+09 0.62 832.33 01-SEP-08:62 0.66
October 0.841181E+09 0.60 832.33 01-OCT-08:62 0.66
November 0.582873E+09 0.58 832.33 01-NOV-08:62 0.66
December 0.387480E+09 0.56 832.33 01-DEC-09:02 0.66
           
Annual Sum or Average 0.796922E+10 0.60      
Minimum of Months 0.386439E+09 0.56 832.33   0.66
Maximum of Months 0.945969E+09 0.63 832.33   0.67



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.708510E+09 0.644035E+09 1257.08 07-JAN-07:10 1142.69 1142.69 42.31 1.85
February 0.439292E+09 0.399316E+09 1303.33 02-FEB-03:20 1184.73 1184.73 43.16 1.97
March 0.273478E+09 0.248591E+09 1181.41 02-MAR-07:10 1073.90 1073.90 41.17 1.68
April 29924984.82 27201811.20 487.11 12-APR-05:00 442.78 442.78 39.58 0.56
May 379216.61 344707.90 183.32 02-MAY-08:05 166.64 166.64 40.83 0.19
June 61327.15 55746.38 54.52 30-JUN-08:07 49.56 49.56 48.88 0.06
July 30115.45 27374.94 95.47 21-JUL-21:58 86.78 86.78 49.10 0.10
August 107912.74 98092.68 78.54 17-AUG-08:07 71.40 71.40 49.16 0.08
September 183695.33 166979.06 170.42 27-SEP-08:56 154.91 154.91 50.71 0.18
October 5268752.64 4789296.15 223.40 13-OCT-08:06 203.07 203.07 39.63 0.24
November 0.371455E+09 0.337653E+09 1109.44 28-NOV-05:00 1008.48 1008.48 43.00 1.53
December 0.924229E+09 0.840124E+09 1313.07 27-DEC-09:01 1193.58 1193.58 40.12 1.99
                 
Annual Sum or Average 0.275292E+10 0.250240E+10            
Minimum of Months 30115.45 27374.94 54.52   49.56 49.56 39.58 0.06
Maximum of Months 0.924229E+09 0.840124E+09 1313.07   1193.58 1193.58 50.71 1.99



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 24580098.50 22343309.54 128.19 01-JAN-16:12 116.53 116.53 6.72 5.00
February 45389766.96 41259298.17 135.50 22-FEB-20:32 123.17 123.17 6.72 5.13
March 75516686.26 68644667.81 298.18 14-MAR-15:12 271.04 271.04 6.72 7.38
April 0.287608E+09 0.261435E+09 908.87 28-APR-18:04 826.16 826.16 6.72 11.95
May 0.634057E+09 0.576358E+09 1103.86 25-MAY-18:06 1003.41 1003.41 6.72 12.95
June 0.917255E+09 0.833785E+09 1330.87 16-JUN-20:30 1209.76 1209.76 6.72 13.99
July 0.106520E+10 0.968269E+09 1102.38 21-JUL-21:00 1002.06 1002.06 6.72 12.95
August 0.925490E+09 0.841270E+09 1100.83 22-AUG-20:10 1000.66 1000.66 6.72 12.94
September 0.748107E+09 0.680029E+09 1295.11 18-SEP-18:08 1177.25 1177.25 6.72 13.83
October 0.335626E+09 0.305084E+09 1085.02 01-OCT-18:04 986.29 986.29 6.72 12.86
November 69910330.06 63548490.02 453.18 03-NOV-15:10 411.94 411.94 6.72 8.88
December 18788327.65 17078589.84 108.72 16-DEC-16:12 98.83 98.83 6.72 4.62
                 
Annual Sum or Average 0.514753E+10 0.467910E+10            
Minimum of Months 18788327.65 17078589.84 108.72   98.83 98.83 6.72 4.62
Maximum of Months 0.106520E+10 0.968269E+09 1330.87   1209.76 1209.76 6.72 13.99



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.449086E+10 0.408219E+10 2239.97 01-JAN-00:05 2036.13 2036.13 6.80 20.01
February 0.470159E+10 0.427374E+10 2239.97 01-FEB-00:05 2036.13 2036.13 6.75 20.01
March 0.568349E+10 0.516630E+10 2239.97 01-MAR-00:05 2036.13 2036.13 6.77 20.01
April 0.579861E+10 0.527094E+10 2239.97 01-APR-00:10 2036.13 2036.13 6.84 20.01
May 0.599954E+10 0.545358E+10 2239.97 01-MAY-00:10 2036.13 2036.13 8.28 20.01
June 0.580600E+10 0.527766E+10 2239.97 01-JUN-00:10 2036.13 2036.13 9.23 20.01
July 0.599954E+10 0.545358E+10 2239.97 01-JUL-00:10 2036.13 2036.13 9.59 20.01
August 0.599954E+10 0.545358E+10 2239.97 01-AUG-00:10 2036.13 2036.13 9.95 20.01
September 0.580600E+10 0.527766E+10 2239.97 01-SEP-00:10 2036.13 2036.13 9.01 20.01
October 0.599954E+10 0.545358E+10 2239.97 01-OCT-00:10 2036.13 2036.13 7.47 20.01
November 0.488893E+10 0.444404E+10 2239.97 01-NOV-00:10 2036.13 2036.13 6.98 20.01
December 0.429535E+10 0.390448E+10 2239.97 01-DEC-00:05 2036.13 2036.13 6.76 20.01
                 
Annual Sum or Average 0.654690E+11 0.595113E+11            
Minimum of Months 0.429535E+10 0.390448E+10 2239.97   2036.13 2036.13 6.75 20.01
Maximum of Months 0.599954E+10 0.545358E+10 2239.97   2036.13 2036.13 9.95 20.01



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 49.27 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:05 14.37 14.37 49.83 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:05 14.37 14.37 50.11 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.00 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 52.99 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 53.86 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 53.68 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 53.61 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 54.39 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.35 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 53.16 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:05 14.37 14.37 50.47 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 49.27 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.39 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 52.02 6374.61 05-JAN-19:03 51.97 51.97 22329.61 128252.46 28-JAN-07:40
February 38.50 2646.33 02-FEB-19:03 50.30 50.30 15589.56 131171.62 02-FEB-03:30
March 12.64 2398.29 04-MAR-09:20 51.02 51.02 9565.46 132990.71 02-MAR-09:01
April 0.75 784.85 01-APR-05:50 52.02 52.02 1184.57 48795.33 12-APR-06:00
May 0.00 0.00 01-MAY-00:10 40.09 40.09 9.62 15609.73 02-MAY-08:05
June 0.00 0.00 01-JUN-00:10 48.03 48.03 1.16 2615.57 30-JUN-08:07
July 0.00 0.00 01-JUL-00:10 48.91 48.91 0.53 4524.06 21-JUL-21:58
August 0.00 0.00 01-AUG-00:10 49.17 49.17 1.82 3620.14 17-AUG-08:07
September 0.00 0.00 01-SEP-00:10 49.89 49.89 2.68 7187.44 11-SEP-08:57
October 2.08 480.92 08-OCT-06:00 52.50 52.50 135.60 20394.73 13-OCT-08:06
November 18.69 2208.42 05-NOV-08:20 51.47 51.47 12859.70 128514.13 28-NOV-16:11
December 34.68 4687.27 29-DEC-16:12 50.58 50.58 29865.05 182040.25 26-DEC-16:11
                 
Annual Sum or Average 13.16         7608.46    
Minimum of Months 0.00 0.00   40.09 40.09 0.53 2615.57  
Maximum of Months 52.02 6374.61   52.50 52.50 29865.05 182040.25  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 15842.41 145854.21 03-JAN-16:13 8.44 6.70 0.00 0.00 01-JAN-00:05
February 31723.47 197296.12 20-FEB-16:15 9.05 6.70 0.00 0.00 01-FEB-00:05
March 46451.71 283105.34 14-MAR-15:12 10.08 6.70 0.00 0.00 01-MAR-00:05
April 119004.07 336629.29 28-APR-21:51 10.71 6.70 0.00 0.00 01-APR-00:10
May 181095.88 370461.86 24-MAY-18:03 11.12 6.70 0.00 0.00 01-MAY-00:10
June 237279.66 417244.15 19-JUN-18:51 11.68 6.70 0.00 0.00 01-JUN-00:10
July 291442.37 511025.55 21-JUL-21:00 12.80 6.70 0.00 0.00 01-JUL-00:10
August 246037.73 466083.33 01-AUG-21:51 12.26 6.70 0.00 0.00 01-AUG-00:10
September 215484.09 418333.08 03-SEP-21:51 11.69 6.70 0.00 0.00 01-SEP-00:10
October 117126.54 416898.34 04-OCT-18:03 11.67 6.70 0.00 0.00 01-OCT-00:10
November 39027.17 216893.28 03-NOV-15:40 9.29 6.70 0.00 0.00 01-NOV-00:10
December 12768.18 112679.87 15-DEC-19:02 8.04 6.70 0.00 0.00 01-DEC-00:05
                 
Annual Sum or Average 129988.54         0.00    
Minimum of Months 12768.18 112679.87   8.04 6.70 0.00 0.00  
Maximum of Months 291442.37 511025.55   12.80 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 49.27 59.73 25475.07 51785.00 30-JAN-07:53
February 0.00 0.00 01-FEB-00:05 49.83 59.35 25456.05 51781.88 02-FEB-07:57
March 0.00 0.00 01-MAR-00:05 50.11 59.60 24602.03 50773.65 01-MAR-08:00
April 0.00 0.00 01-APR-00:10 53.00 59.56 23055.55 47957.60 03-APR-06:58
May 0.00 0.00 01-MAY-00:10 52.99 58.82 21280.82 44614.85 01-MAY-07:00
June 0.00 0.00 01-JUN-00:10 53.86 59.25 19743.82 40902.66 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 53.68 58.49 18839.03 38180.40 03-JUL-07:00
August 0.00 0.00 01-AUG-00:10 53.61 58.27 18864.45 38383.47 31-AUG-07:00
September 0.00 0.00 01-SEP-00:10 54.39 59.67 19756.27 40891.61 29-SEP-06:25
October 0.00 0.00 01-OCT-00:10 53.35 59.63 21296.51 44591.64 31-OCT-06:20
November 0.00 0.00 01-NOV-00:10 53.16 59.13 23074.08 48129.41 30-NOV-08:00
December 0.00 0.00 01-DEC-00:05 50.47 58.94 24599.80 50742.00 29-DEC-07:55
                 
Annual Sum or Average 0.00         22151.64    
Minimum of Months 0.00 0.00   49.27 58.27 18839.03 38180.40  
Maximum of Months 0.00 0.00   54.39 59.73 25475.07 51785.00  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.508252E+11 0.00 0.735597E+10 0.384496E+11 0.00 0.00
February 0.327157E+11 0.00 0.357677E+11 0.350332E+11 0.00 0.00
March 0.235925E+11 0.00 0.720688E+11 0.391339E+11 0.00 0.00
April 0.296808E+10 0.00 0.210249E+12 0.395443E+11 0.00 0.00
May 1746041.64 0.00 0.341748E+12 0.430588E+11 0.00 0.00
June 164292.66 0.00 0.434809E+12 0.443439E+11 0.00 0.00
July 279099.08 0.00 0.575268E+12 0.455324E+11 0.00 0.00
August 1669045.18 0.00 0.474622E+12 0.459472E+11 0.00 0.00
September 1852810.05 0.00 0.392229E+12 0.444109E+11 0.00 0.00
October 0.330615E+09 0.00 0.198647E+12 0.433742E+11 0.00 0.00
November 0.297042E+11 0.00 0.434875E+11 0.394372E+11 0.00 0.00
December 0.668149E+11 0.00 0.433284E+10 0.388592E+11 0.00 0.00
             
Annual Sum or Average 0.206957E+12 0.00 0.279059E+13 0.497125E+12 0.00 0.00
Minimum of Months 164292.66 0.00 0.433284E+10 0.350332E+11 0.00 0.00
Maximum of Months 0.668149E+11 0.00 0.575268E+12 0.459472E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 27541937.75 0.00 0.389195E+09 0.261333E+10 0.00 0.00
February 48532045.49 0.00 0.196624E+10 0.236042E+10 0.00 0.00
March 15146356.32 0.00 0.406941E+10 0.261333E+10 0.00 0.00
April 22180.29 0.00 0.138040E+11 0.252903E+10 0.00 0.00
May 32501.55 0.00 0.229551E+11 0.261333E+10 0.00 0.00
June 17191.28 0.00 0.287850E+11 0.252903E+10 0.00 0.00
July 18610.63 0.00 0.409763E+11 0.261333E+10 0.00 0.00
August 19710.65 0.00 0.334889E+11 0.261333E+10 0.00 0.00
September 18880.63 0.00 0.280526E+11 0.252903E+10 0.00 0.00
October 19252.76 0.00 0.130966E+11 0.261333E+10 0.00 0.00
November 6704.97 0.00 0.249625E+10 0.252903E+10 0.00 0.00
December 89262066.40 0.00 0.199728E+09 0.261333E+10 0.00 0.00
             
Annual Sum or Average 0.180637E+09 0.00 0.190279E+12 0.307698E+11 0.00 0.00
Minimum of Months 6704.97 0.00 0.199728E+09 0.236042E+10 0.00 0.00
Maximum of Months 89262066.40 0.00 0.409763E+11 0.261333E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.384496E+11 0.735597E+10 0.508252E+11 0.505456E+10 0.00 0.00 0.00 0.00
February 0.350332E+11 0.357677E+11 0.327157E+11 0.878946E+10 0.00 0.00 0.00 0.00
March 0.391339E+11 0.720688E+11 0.235925E+11 0.433452E+10 0.00 0.00 0.00 0.00
April 0.395443E+11 0.210249E+12 0.296808E+10 0.664347E+10 0.234786E+10 0.00 0.00 0.00
May 0.430588E+11 0.341748E+12 1746041.64 0.164116E+11 0.110664E+11 0.00 0.00 0.00
June 0.443439E+11 0.434809E+12 164292.66 0.223959E+11 0.275206E+11 0.00 0.00 0.00
July 0.455324E+11 0.575268E+12 279099.08 0.749787E+10 0.538319E+11 0.00 0.00 0.00
August 0.459472E+11 0.474622E+12 1669045.18 0.984133E+10 0.244246E+11 0.00 0.00 0.00
September 0.444109E+11 0.392229E+12 1852810.05 0.545175E+10 0.140054E+11 0.00 0.00 0.00
October 0.433742E+11 0.198647E+12 0.330615E+09 0.440432E+10 0.241539E+10 0.00 0.00 0.00
November 0.394372E+11 0.434875E+11 0.297042E+11 94618210.09 0.00 0.00 0.00 0.00
December 0.388592E+11 0.433284E+10 0.668149E+11 0.171809E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.497125E+12 0.279059E+13 0.206957E+12 0.108100E+12 0.135612E+12 0.00 0.00 0.00
Minimum of Months 0.350332E+11 0.433284E+10 164292.66 94618210.09 0.00 0.00 0.00 0.00
Maximum of Months 0.459472E+11 0.575268E+12 0.668149E+11 0.223959E+11 0.538319E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.261333E+10 0.389195E+09 27541937.75 0.255732E+11 0.00 0.00 0.00 0.00
February 0.236042E+10 0.196624E+10 48532045.49 0.182962E+11 0.00 0.00 0.00 0.00
March 0.261333E+10 0.406941E+10 15146356.32 0.146036E+11 0.00 0.00 0.00 0.00
April 0.252903E+10 0.138040E+11 22180.29 0.463508E+10 0.321574E+09 0.00 0.00 0.00
May 0.261333E+10 0.229551E+11 32501.55 0.200566E+10 0.202348E+10 0.00 0.00 0.00
June 0.252903E+10 0.287850E+11 17191.28 0.829091E+09 0.510583E+10 0.00 0.00 0.00
July 0.261333E+10 0.409763E+11 18610.63 697652.41 0.149972E+11 0.00 0.00 0.00
August 0.261333E+10 0.334889E+11 19710.65 0.202629E+09 0.813353E+10 0.00 0.00 0.00
September 0.252903E+10 0.280526E+11 18880.63 0.847442E+09 0.400215E+10 0.00 0.00 0.00
October 0.261333E+10 0.130966E+11 19252.76 0.324233E+10 0.836227E+09 0.00 0.00 0.00
November 0.252903E+10 0.249625E+10 6704.97 0.170438E+11 2632512.27 0.00 0.00 0.00
December 0.261333E+10 0.199728E+09 89262066.40 0.299077E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.307698E+11 0.190279E+12 0.180637E+09 0.117187E+12 0.354226E+11 0.00 0.00 0.00
Minimum of Months 0.236042E+10 0.199728E+09 6704.97 697652.41 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 0.409763E+11 89262066.40 0.299077E+11 0.149972E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.384496E+11 0.508252E+11 0.735597E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.350332E+11 0.327157E+11 0.357677E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.391339E+11 0.235925E+11 0.720688E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.395443E+11 0.296808E+10 0.210249E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.430588E+11 1746041.64 0.341748E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.443439E+11 164292.66 0.434809E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455324E+11 279099.08 0.575268E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.459472E+11 1669045.18 0.474622E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.444109E+11 1852810.05 0.392229E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.433742E+11 0.330615E+09 0.198647E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.394372E+11 0.297042E+11 0.434875E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.388592E+11 0.668149E+11 0.433284E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.497125E+12 0.206957E+12 0.279059E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.350332E+11 164292.66 0.433284E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.459472E+11 0.668149E+11 0.575268E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.261333E+10 27541937.75 0.389195E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.236042E+10 48532045.49 0.196624E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.261333E+10 15146356.32 0.406941E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.252903E+10 22180.29 0.138040E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.261333E+10 32501.55 0.229551E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.252903E+10 17191.28 0.287850E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.261333E+10 18610.63 0.409763E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.261333E+10 19710.65 0.334889E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.252903E+10 18880.63 0.280526E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.261333E+10 19252.76 0.130966E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.252903E+10 6704.97 0.249625E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.261333E+10 89262066.40 0.199728E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.307698E+11 0.180637E+09 0.190279E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.236042E+10 6704.97 0.199728E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 89262066.40 0.409763E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.367722E+11 0.00 0.00 4211321.55 0.00 0.00 0.881805E+10 0.00 0.67
February 0.372148E+11 0.00 0.00 28109.23 0.00 0.00 0.204795E+09 0.00 0.73
March 0.375494E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.77
April 0.239010E+11 0.00 0.00 0.00 59948580.54 0.00 0.00 0.00 0.79
May 0.151396E+11 0.00 0.00 0.00 0.355224E+09 0.00 0.00 0.00 0.74
June 0.796231E+10 0.00 0.00 0.00 0.106009E+10 0.00 0.00 0.00 0.66
July 0.146541E+10 0.148816E+10 0.00 1993065.06 0.387046E+10 0.00 0.577636E+09 0.00 0.64
August 0.148253E+09 0.106706E+10 0.00 38589296.86 0.504905E+09 0.00 0.739315E+10 0.00 0.74
September 29416772.70 0.111226E+10 0.00 63152783.77 33112402.64 0.00 0.153137E+11 0.00 0.91
October 60101403.15 0.164930E+09 0.00 75777704.51 3840273.90 0.00 0.342976E+11 0.00 1.01
November 0.253172E+09 0.00 0.00 64648217.74 0.00 0.00 0.474788E+11 0.00 0.88
December 0.341191E+10 0.00 0.00 43152961.44 0.00 0.00 0.465314E+11 0.00 0.70
                   
Annual Sum or Average 0.163908E+12 0.383242E+10 0.00 0.291553E+09 0.588758E+10 0.00 0.160615E+12 0.00 0.77
Minimum of Months 29416772.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
Maximum of Months 0.375494E+11 0.148816E+10 0.00 75777704.51 0.387046E+10 0.00 0.474788E+11 0.00 1.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.348841E+10 0.00 0.00 1478912.10 0.00 9639345.46 0.914672E+09 0.00 1.22
February 0.284606E+10 0.00 0.00 1546408.17 0.00 5049193.81 0.733763E+09 0.00 1.35
March 0.292432E+10 0.00 0.00 1353363.62 0.00 1495064.02 0.591868E+09 0.00 1.35
April 0.140485E+10 8218338.78 0.00 3385964.58 0.00 0.00 0.844627E+09 0.00 1.42
May 0.484261E+09 44474269.60 0.00 4577642.45 203251.07 0.00 0.980542E+09 0.00 1.39
June 28811933.67 0.150062E+09 0.00 5386074.58 33580.77 0.00 0.800173E+09 0.00 1.42
July 5687267.74 0.626779E+09 0.00 2326272.91 15464689.56 0.00 0.212021E+09 0.00 1.39
August 69805291.96 0.205224E+09 0.00 5227513.65 873946.44 0.00 0.659682E+09 0.00 1.51
September 0.180832E+09 0.155920E+09 0.00 5994506.00 270847.14 0.00 0.107293E+10 0.00 1.70
October 0.114367E+10 26522297.02 0.00 6252549.41 168504.95 0.00 0.171320E+10 0.00 1.82
November 0.247996E+10 0.00 0.00 3555387.70 0.00 1451081.76 0.169005E+10 0.00 1.57
December 0.365101E+10 0.00 0.00 1119203.91 0.00 0.100867E+09 0.759065E+09 0.00 1.17
                   
Annual Sum or Average 0.187077E+11 0.121720E+10 0.00 42203799.08 17014819.93 0.118501E+09 0.109726E+11 0.00 1.44
Minimum of Months 5687267.74 0.00 0.00 1119203.91 0.00 0.00 0.212021E+09 0.00 1.17
Maximum of Months 0.365101E+10 0.626779E+09 0.00 6252549.41 15464689.56 0.100867E+09 0.171320E+10 0.00 1.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.476279E+10 0.00 0.00 24977.87 0.00 0.00 0.129972E+09 0.00 1.13
February 0.383737E+10 0.00 0.00 60779.38 0.00 0.00 0.178113E+09 0.00 1.24
March 0.364921E+10 0.00 0.00 149221.29 0.00 0.00 0.380099E+09 0.00 1.30
April 0.142195E+10 0.00 0.00 1242770.36 6433147.20 0.00 0.114815E+10 0.00 1.34
May 0.303728E+09 3343492.40 0.00 2697753.36 34775982.04 0.00 0.134432E+10 0.00 1.27
June 50707052.09 60948157.51 0.00 3476653.98 53369778.61 0.00 0.838006E+09 0.00 1.16
July 2947102.66 0.376958E+09 0.00 2073486.01 0.215140E+09 0.00 0.225796E+09 0.00 1.13
August 69183043.85 0.104799E+09 0.00 3219465.17 64363633.96 0.00 0.720368E+09 0.00 1.22
September 0.124097E+09 57841438.23 0.00 3352691.72 57324664.40 0.00 0.122346E+10 0.00 1.32
October 0.124595E+10 6797684.47 0.00 1953207.16 10120028.62 0.00 0.175885E+10 0.00 1.43
November 0.349840E+10 0.00 0.00 421023.29 0.00 0.00 0.841788E+09 0.00 1.28
December 0.503459E+10 0.00 0.00 1832.07 0.00 0.00 22187016.60 0.00 1.11
                   
Annual Sum or Average 0.240009E+11 0.610688E+09 0.00 18673861.66 0.441527E+09 0.00 0.881111E+10 0.00 1.24
Minimum of Months 2947102.66 0.00 0.00 1832.07 0.00 0.00 22187016.60 0.00 1.11
Maximum of Months 0.503459E+10 0.376958E+09 0.00 3476653.98 0.215140E+09 0.00 0.175885E+10 0.00 1.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 89884038.19 0.00 0.00 22373.83 0.00 0.00 17141101.14 0.00 0.01
February 68790314.14 0.00 0.00 111250.85 0.00 0.00 62138074.70 0.00 0.02
March 57990096.77 0.00 0.00 330459.87 0.00 0.00 0.169024E+09 0.00 0.04
April 7732329.23 1983378.25 0.00 2340135.26 1019.93 0.00 0.641786E+09 0.00 0.18
May 0.00 17843001.95 0.00 4294375.66 0.00 0.00 0.845911E+09 0.00 0.32
June 0.00 80506296.78 0.00 4604707.62 0.00 0.00 0.645024E+09 0.00 0.40
July 0.00 0.419930E+09 0.00 1988385.16 0.00 0.00 0.177572E+09 0.00 0.41
August 0.00 0.119313E+09 0.00 4129023.48 0.00 0.00 0.530632E+09 0.00 0.40
September 0.00 69517355.90 0.00 3954045.53 0.00 0.00 0.774696E+09 0.00 0.38
October 14270.73 9867568.13 0.00 2963096.25 0.00 0.00 0.102485E+10 0.00 0.25
November 52385125.79 0.00 0.00 611017.70 0.00 0.00 0.332448E+09 0.00 0.06
December 93682060.65 0.00 0.00 7389.32 0.00 0.00 6043366.03 0.00 0.01
                   
Annual Sum or Average 0.370478E+09 0.718961E+09 0.00 25356260.54 1019.93 0.00 0.522726E+10 0.00 0.21
Minimum of Months 0.00 0.00 0.00 7389.32 0.00 0.00 6043366.03 0.00 0.01
Maximum of Months 93682060.65 0.419930E+09 0.00 4604707.62 1019.93 0.00 0.102485E+10 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.308016E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
February 0.252791E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.63
March 0.253667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.67
April 0.161465E+10 0.00 0.00 0.00 4049861.98 0.00 0.00 0.00 0.69
May 0.102276E+10 0.00 0.00 0.00 23997369.49 0.00 0.00 0.00 0.64
June 0.528709E+09 111710.75 0.00 22770.31 71503165.85 0.00 9166842.00 0.00 0.57
July 0.134656E+09 3906165.88 0.00 8795.34 0.357946E+09 0.00 3483482.19 0.00 0.55
August 0.478209E+09 538846.17 0.00 8906.45 0.102457E+09 0.00 1548776.70 0.00 0.60
September 0.821526E+09 0.00 0.00 0.00 71487895.09 0.00 0.00 0.00 0.65
October 0.187600E+10 0.00 0.00 0.00 10404202.26 0.00 0.00 0.00 0.73
November 0.273115E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.65
December 0.318340E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
                   
Annual Sum or Average 0.205358E+11 4556722.80 0.00 40472.10 0.641846E+09 0.00 14199100.89 0.00 0.63
Minimum of Months 0.134656E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
Maximum of Months 0.318340E+10 3906165.88 0.00 22770.31 0.357946E+09 0.00 9166842.00 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.104197E+09 0.00 0.00 0.690498E+11 0.00 16.10
February 0.00 0.00 0.00 96578001.47 0.00 0.00 0.576192E+11 0.00 17.89
March 0.00 0.00 0.00 0.112909E+09 0.00 0.00 0.584867E+11 0.00 19.18
April 0.00 76892116.94 0.00 0.124713E+09 0.00 0.00 0.366256E+11 0.00 19.53
May 0.00 0.446392E+09 0.00 0.121295E+09 0.00 0.00 0.225687E+11 0.00 18.09
June 0.00 0.147952E+10 0.00 91492076.05 0.00 0.00 0.112804E+11 0.00 15.99
July 0.00 0.842578E+10 0.00 33494482.46 0.00 0.00 0.275380E+10 0.00 15.41
August 0.00 0.242313E+10 0.00 85394499.11 0.00 0.00 0.100961E+11 0.00 16.86
September 0.00 0.157572E+10 0.00 97505992.98 0.00 0.00 0.182131E+11 0.00 18.38
October 0.00 0.248242E+09 0.00 0.118634E+09 0.00 0.00 0.432262E+11 0.00 20.91
November 0.00 0.00 0.00 0.107208E+09 0.00 0.00 0.628482E+11 0.00 18.48
December 0.00 0.00 0.00 0.103356E+09 0.00 0.00 0.712530E+11 0.00 15.62
                   
Annual Sum or Average 0.00 0.146757E+11 0.00 0.119678E+10 0.00 0.00 0.464021E+12 0.00 17.70
Minimum of Months 0.00 0.00 0.00 33494482.46 0.00 0.00 0.275380E+10 0.00 15.41
Maximum of Months 0.00 0.842578E+10 0.00 0.124713E+09 0.00 0.00 0.712530E+11 0.00 20.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.147665E+11 0.00 0.00 7459912.89 0.00 0.00 0.212957E+11 0.00 3.43
February 0.113128E+11 0.00 0.00 7426734.78 0.00 0.00 0.182823E+11 0.00 3.75
March 0.126302E+11 0.00 0.00 6997611.84 0.00 0.00 0.170680E+11 0.00 3.95
April 0.614265E+10 30916018.21 0.00 10842252.65 16509060.04 0.00 0.127550E+11 0.00 4.04
May 0.249475E+10 0.152511E+09 0.00 13464012.20 0.128505E+09 0.00 0.947138E+10 0.00 3.78
June 0.840700E+09 0.591321E+09 0.00 16089964.13 0.247310E+09 0.00 0.546445E+10 0.00 3.37
July 91435691.89 0.282201E+10 0.00 9990782.38 0.141690E+10 0.00 0.152670E+10 0.00 3.26
August 0.830251E+09 0.865846E+09 0.00 16119335.63 0.341495E+09 0.00 0.478994E+10 0.00 3.55
September 0.134650E+10 0.625667E+09 0.00 19341112.41 0.212060E+09 0.00 0.828007E+10 0.00 3.86
October 0.497278E+10 98557017.97 0.00 22202242.71 23389168.62 0.00 0.170057E+11 0.00 4.31
November 0.949730E+10 0.00 0.00 15218711.21 0.00 0.00 0.224829E+11 0.00 3.87
December 0.181978E+11 0.00 0.00 5781167.16 0.00 0.00 0.190750E+11 0.00 3.37
                   
Annual Sum or Average 0.831236E+11 0.518683E+10 0.00 0.150934E+09 0.238617E+10 0.00 0.157497E+12 0.00 3.71
Minimum of Months 91435691.89 0.00 0.00 5781167.16 0.00 0.00 0.152670E+10 0.00 3.26
Maximum of Months 0.181978E+11 0.282201E+10 0.00 22202242.71 0.141690E+10 0.00 0.224829E+11 0.00 4.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.559040E+11 0.00 0.00 17765982.11 0.00 0.00 0.450347E+11 0.00 1.39
February 0.413732E+11 0.00 0.00 19579942.86 0.00 0.00 0.415063E+11 0.00 1.52
March 0.378537E+11 0.00 0.00 26797177.76 0.00 0.00 0.453636E+11 0.00 1.60
April 0.149428E+11 4426265.17 0.00 51792399.67 0.128255E+09 0.00 0.385869E+11 0.00 1.66
May 0.463636E+10 99888332.42 0.00 71361170.60 0.686313E+09 0.00 0.304184E+11 0.00 1.59
June 0.104436E+10 0.113990E+10 0.00 75742147.99 0.121164E+10 0.00 0.184907E+11 0.00 1.47
July 62848502.72 0.809994E+10 0.00 45064020.66 0.431916E+10 0.00 0.505572E+10 0.00 1.42
August 0.127102E+10 0.227914E+10 0.00 72278810.67 0.125165E+10 0.00 0.161066E+11 0.00 1.55
September 0.190114E+10 0.158496E+10 0.00 79391248.48 0.810665E+09 0.00 0.274013E+11 0.00 1.67
October 0.128933E+11 0.264279E+09 0.00 70713972.29 86279755.75 0.00 0.509295E+11 0.00 1.81
November 0.349527E+11 0.00 0.00 37702758.99 0.00 0.00 0.551751E+11 0.00 1.58
December 0.642495E+11 0.00 0.00 13828422.44 0.00 0.00 0.400363E+11 0.00 1.36
                   
Annual Sum or Average 0.271085E+12 0.134725E+11 0.00 0.582018E+09 0.849397E+10 0.00 0.414105E+12 0.00 1.55
Minimum of Months 62848502.72 0.00 0.00 13828422.44 0.00 0.00 0.505572E+10 0.00 1.36
Maximum of Months 0.642495E+11 0.809994E+10 0.00 79391248.48 0.431916E+10 0.00 0.551751E+11 0.00 1.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 64876750.41 0.00 0.00 3443722.93 0.00 0.626540E+09 0.582430E+09 0.00 0.34
February 41556246.92 0.00 0.00 4443782.91 0.00 0.371739E+09 0.675526E+09 0.00 0.34
March 44091698.80 0.00 0.00 7572702.91 0.00 0.166786E+09 0.936771E+09 0.00 0.34
April 13742024.27 3256967.37 0.00 14040258.64 0.00 5281425.91 0.763528E+09 0.00 0.34
May 191157.84 21112975.40 0.00 13558630.94 0.00 417349.23 0.464571E+09 0.00 0.34
June 0.00 48443298.21 0.00 10418151.47 0.00 32925.72 0.135621E+09 0.00 0.34
July 0.00 0.467918E+09 56959.42 614623.89 0.00 1058.68 1544900.16 955.29 0.34
August 0.00 0.201445E+09 488.30 5528033.41 0.00 61734.49 59319738.38 217.92 0.34
September 0.00 0.198634E+09 10503.20 9339879.30 0.00 394370.76 0.246691E+09 288.09 0.34
October 7879172.04 25209099.52 0.00 12739387.59 0.00 1141794.35 0.764065E+09 0.00 0.34
November 16775057.71 45811.46 0.00 7094587.07 0.00 0.264265E+09 0.881146E+09 0.00 0.34
December 69005777.50 0.00 0.00 2492273.01 0.00 0.748604E+09 0.460856E+09 0.00 0.34
                   
Annual Sum or Average 0.258118E+09 0.966065E+09 67950.91 91286034.06 0.00 0.218527E+10 0.597207E+10 1461.29 0.34
Minimum of Months 0.00 0.00 0.00 614623.89 0.00 1058.68 1544900.16 0.00 0.34
Maximum of Months 69005777.50 0.467918E+09 56959.42 14040258.64 0.00 0.748604E+09 0.936771E+09 955.29 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 95807182.36 0.00 0.00 1009872.19 0.00 0.961120E+09 0.219204E+09 0.00 0.34
February 0.138446E+09 0.00 0.00 1039010.73 0.00 0.577941E+09 0.375712E+09 0.00 0.34
March 0.179469E+09 0.00 0.00 2892055.71 0.00 0.264234E+09 0.708490E+09 0.00 0.34
April 0.139096E+09 3076321.41 0.00 11038985.65 180264.36 5635115.45 0.640728E+09 0.00 0.34
May 88108736.09 20211696.65 3363.49 11456710.83 894774.61 296769.86 0.378820E+09 666.96 0.34
June 33142695.07 47036462.77 0.00 8328380.36 1401159.60 6033.76 0.104578E+09 0.00 0.34
July 663715.24 0.401614E+09 0.00 510935.94 66307748.42 0.00 985678.40 0.00 0.34
August 25501030.31 0.176523E+09 0.00 4080790.96 24898819.09 0.00 35320079.91 0.00 0.34
September 78811120.38 0.172899E+09 0.00 6704436.86 25722333.19 107175.18 0.170773E+09 0.00 0.34
October 0.165045E+09 22295621.45 11899.99 6669819.10 2898479.00 1832963.57 0.612186E+09 145.46 0.34
November 0.139057E+09 43106.03 0.00 2060181.49 2700.05 0.454366E+09 0.573661E+09 0.00 0.34
December 95890996.33 0.00 0.00 544965.08 0.00 0.105904E+10 0.125333E+09 0.00 0.34
                   
Annual Sum or Average 0.117904E+10 0.843699E+09 15263.48 56336144.91 0.122306E+09 0.332458E+10 0.394579E+10 812.43 0.34
Minimum of Months 663715.24 0.00 0.00 510935.94 0.00 0.00 985678.40 0.00 0.34
Maximum of Months 0.179469E+09 0.401614E+09 11899.99 11456710.83 66307748.42 0.105904E+10 0.708490E+09 666.96 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.236574E+09 0.00 0.00 2977234.85 0.00 0.00 0.107062E+10 0.00 0.02
February 0.152227E+09 0.00 0.00 2546837.92 0.00 0.00 0.889808E+09 0.00 0.02
March 67812630.22 0.00 0.00 2595754.39 0.00 0.00 0.898269E+09 0.00 0.02
April 0.00 7965344.05 0.00 2305902.38 0.00 0.00 0.391934E+09 0.00 0.02
May 0.00 55455323.78 0.00 1165752.18 0.00 0.00 0.109427E+09 0.00 0.02
June 0.00 73628535.95 0.00 1129837.63 0.00 0.00 37271533.22 0.00 0.02
July 0.00 0.294177E+09 0.00 179564.42 0.00 0.00 6714043.89 0.00 0.02
August 0.00 0.116121E+09 0.00 917462.74 0.00 0.00 32832431.95 0.00 0.02
September 0.00 0.108750E+09 0.00 1789653.60 0.00 0.00 82199817.74 0.00 0.02
October 21600120.46 29625664.58 0.00 3386260.29 0.00 0.00 0.547057E+09 0.00 0.02
November 0.191846E+09 0.00 0.00 3638231.06 0.00 0.00 0.804778E+09 0.00 0.02
December 0.236758E+09 0.00 0.00 2442275.82 0.00 0.00 0.110239E+10 0.00 0.02
                   
Annual Sum or Average 0.906818E+09 0.685723E+09 0.00 25074767.29 0.00 0.00 0.597330E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 179564.42 0.00 0.00 6714043.89 0.00 0.02
Maximum of Months 0.236758E+09 0.294177E+09 0.00 3638231.06 0.00 0.00 0.110239E+10 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.129957E+10 0.00 0.00 23781588.45 0.00 0.172951E+10 0.142708E+11 0.00 0.39
February 0.187268E+10 0.00 0.00 29775085.28 0.00 0.111702E+10 0.118083E+11 0.00 0.39
March 0.243439E+10 0.00 0.00 50335719.52 0.00 0.216403E+09 0.129669E+11 0.00 0.39
April 0.194300E+10 33556009.20 0.00 0.111548E+09 10617623.13 3966162.27 0.874551E+10 0.00 0.39
May 0.124426E+10 0.249190E+09 0.00 0.108808E+09 37160878.46 0.00 0.513997E+10 0.00 0.39
June 0.453399E+09 0.634556E+09 0.00 77294348.64 22471331.67 0.00 0.145045E+10 0.00 0.39
July 10959021.21 0.538901E+10 0.00 4232590.08 0.958061E+09 0.00 14111963.55 0.00 0.39
August 0.352706E+09 0.231689E+10 0.00 38320531.14 0.415277E+09 0.00 0.489329E+09 0.00 0.39
September 0.112658E+10 0.226161E+10 0.00 61060973.93 0.432571E+09 0.00 0.229021E+10 0.00 0.39
October 0.227762E+10 0.283245E+09 0.00 78915071.64 58661142.64 3607207.26 0.829786E+10 0.00 0.39
November 0.190604E+10 0.00 0.00 37188960.23 621332.10 0.369344E+09 0.135462E+11 0.00 0.39
December 0.129567E+10 0.00 0.00 18577193.89 0.00 0.391513E+10 0.121440E+11 0.00 0.39
                   
Annual Sum or Average 0.162169E+11 0.111681E+11 0.00 0.639838E+09 0.193544E+10 0.735498E+10 0.911636E+11 0.00 0.39
Minimum of Months 10959021.21 0.00 0.00 4232590.08 0.00 0.00 14111963.55 0.00 0.39
Maximum of Months 0.243439E+10 0.538901E+10 0.00 0.111548E+09 0.958061E+09 0.391513E+10 0.142708E+11 0.00 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 64668753.66 0.00 0.00 3462271.38 0.00 0.657786E+09 0.551373E+09 0.00 0.34
February 36651409.81 0.00 0.00 5280032.22 0.00 0.353164E+09 0.698170E+09 0.00 0.34
March 24982434.73 0.00 0.00 7909176.00 0.00 0.194069E+09 0.928261E+09 0.00 0.34
April 2510423.96 3256967.37 0.00 15304931.89 0.00 4135972.86 0.774640E+09 0.00 0.34
May 0.00 21112474.89 408.99 15244162.83 0.00 28826.62 0.463465E+09 91.52 0.34
June 0.00 48443298.21 0.00 11691459.25 0.00 29039.30 0.134351E+09 0.00 0.34
July 0.00 0.467976E+09 0.00 585466.19 0.00 0.00 1575116.54 0.00 0.34
August 0.00 0.201446E+09 0.00 6082756.27 0.00 78304.47 58748445.55 0.00 0.34
September 0.00 0.198644E+09 0.00 9955738.43 0.00 38700.46 0.246431E+09 0.00 0.34
October 8004361.36 25191823.14 0.00 12470025.94 17276.37 817663.91 0.764533E+09 0.00 0.34
November 17756072.96 45811.46 0.00 7430772.79 0.00 0.304447E+09 0.839647E+09 0.00 0.34
December 71994136.14 0.00 0.00 2697534.77 0.00 0.729262E+09 0.477005E+09 0.00 0.34
                   
Annual Sum or Average 0.226568E+09 0.966117E+09 408.99 98114327.95 17276.37 0.224386E+10 0.593820E+10 91.52 0.34
Minimum of Months 0.00 0.00 0.00 585466.19 0.00 0.00 1575116.54 0.00 0.34
Maximum of Months 71994136.14 0.467976E+09 408.99 15304931.89 17276.37 0.729262E+09 0.928261E+09 91.52 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 95899296.82 0.00 0.00 684279.44 0.00 0.964062E+09 0.216495E+09 0.00 0.34
February 0.138058E+09 0.00 0.00 1937636.69 0.00 0.515670E+09 0.437471E+09 0.00 0.34
March 0.177103E+09 0.00 0.00 3881750.05 0.00 0.303664E+09 0.670438E+09 0.00 0.34
April 0.128649E+09 3076321.41 0.00 12444944.49 180264.36 8607009.33 0.646798E+09 0.00 0.34
May 85273339.91 20272102.62 0.00 12418457.36 838399.09 0.00 0.380990E+09 0.00 0.34
June 32509366.41 47048786.89 0.00 8779376.53 1388835.48 0.00 0.104766E+09 0.00 0.34
July 663715.24 0.402544E+09 0.00 461238.30 65377034.29 0.00 1035376.04 0.00 0.34
August 25136609.08 0.177074E+09 0.00 4111768.43 24347795.70 15371.12 35638152.55 0.00 0.34
September 78323904.06 0.173902E+09 0.00 6712216.22 24719594.40 0.00 0.171359E+09 0.00 0.34
October 0.160901E+09 22404721.83 0.00 7178123.20 2801424.07 6700440.31 0.610953E+09 0.00 0.34
November 0.140105E+09 3269.52 0.00 2868877.27 42536.56 0.463129E+09 0.563040E+09 0.00 0.34
December 95519956.41 0.00 0.00 545334.04 0.00 0.101515E+10 0.169593E+09 0.00 0.34
                   
Annual Sum or Average 0.115814E+10 0.846325E+09 0.00 62024002.03 0.119696E+09 0.327700E+10 0.400858E+10 0.00 0.34
Minimum of Months 663715.24 0.00 0.00 461238.30 0.00 0.00 1035376.04 0.00 0.34
Maximum of Months 0.177103E+09 0.402544E+09 0.00 12444944.49 65377034.29 0.101515E+10 0.670438E+09 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.253272E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.38
February 0.207862E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
March 0.208583E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.44
April 0.132768E+11 0.00 0.00 0.00 33300802.85 0.00 0.00 0.00 0.45
May 0.837421E+10 0.00 0.00 33689.13 0.197323E+09 0.00 35635439.64 0.00 0.42
June 0.254810E+10 0.177052E+09 0.00 5857830.48 0.412151E+09 0.00 0.188414E+10 0.00 0.37
July 0.712856E+09 0.281164E+09 0.00 1993670.59 0.269432E+10 0.00 0.421444E+09 0.00 0.36
August 0.325508E+10 0.182430E+09 0.00 2300936.71 0.664587E+09 0.00 0.688927E+09 0.00 0.39
September 0.641092E+10 38034829.44 0.00 708216.60 0.549789E+09 0.00 0.343583E+09 0.00 0.43
October 0.154068E+11 0.00 0.00 13419.06 85550640.94 0.00 18943336.06 0.00 0.47
November 0.224574E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
December 0.261761E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.37
                   
Annual Sum or Average 0.165590E+12 0.678681E+09 0.00 10907762.56 0.463702E+10 0.00 0.339268E+10 0.00 0.41
Minimum of Months 0.712856E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Maximum of Months 0.261761E+11 0.281164E+09 0.00 5857830.48 0.269432E+10 0.00 0.188414E+10 0.00 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 16921651.12 0.00 0.00 676107.83 0.00 0.215871E+09 85854161.74 0.00 0.34
February 11365707.35 0.00 0.00 903135.80 0.00 0.150137E+09 0.110911E+09 0.00 0.34
March 11041433.31 0.00 0.00 1656397.54 0.00 0.111001E+09 0.165107E+09 0.00 0.34
April 3311531.57 814241.84 0.00 3376804.53 0.00 18820156.04 0.173639E+09 0.00 0.34
May 25109.29 5278243.85 0.00 3257076.25 0.00 244752.35 0.116158E+09 0.00 0.34
June 0.00 12110824.55 0.00 2539139.40 0.00 7546.02 33971303.00 0.00 0.34
July 0.00 0.116987E+09 7291.91 156335.82 0.00 0.00 383809.86 111.36 0.34
August 0.00 50357262.11 4119.74 1338910.93 0.00 16629.93 14871835.72 22.72 0.34
September 0.00 49657444.66 3661.32 2221906.50 0.00 62628.52 61821818.52 16.85 0.34
October 2358804.19 6302274.88 0.00 2851564.19 0.00 5713977.72 0.185532E+09 0.00 0.34
November 5683655.34 11452.86 0.00 1420087.44 0.00 0.125680E+09 0.159536E+09 0.00 0.34
December 18411031.26 0.00 0.00 486586.32 0.00 0.236101E+09 65241295.39 0.00 0.34
                   
Annual Sum or Average 69118923.43 0.241518E+09 15072.96 20884052.55 0.00 0.863655E+09 0.117303E+10 150.94 0.34
Minimum of Months 0.00 0.00 0.00 156335.82 0.00 0.00 383809.86 0.00 0.34
Maximum of Months 18411031.26 0.116987E+09 7291.91 3376804.53 0.00 0.236101E+09 0.185532E+09 111.36 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 24051813.13 0.00 0.00 166342.75 0.00 0.269529E+09 25538080.93 0.00 0.34
February 34599185.20 0.00 0.00 147587.84 0.00 0.196897E+09 41640203.64 0.00 0.34
March 44867350.22 0.00 0.00 533454.56 0.00 0.133041E+09 0.110329E+09 0.00 0.34
April 34672312.41 769080.35 0.00 2680016.64 45066.09 18141903.65 0.143630E+09 0.00 0.34
May 21956165.99 5053931.77 0.00 2796042.03 223693.65 81032.62 94837320.52 0.00 0.34
June 8285673.77 11785904.95 0.00 2090444.23 323500.65 0.00 26137591.81 0.00 0.34
July 165928.81 0.100403E+09 0.00 133583.02 16576937.10 0.00 240570.56 0.00 0.34
August 6374428.75 44130799.22 0.00 1016271.14 6224704.77 688.31 8834087.09 0.00 0.34
September 19668137.37 43221804.14 2885.78 1598444.83 6430583.30 58743.93 42773516.41 31.08 0.34
October 41330205.82 5589733.72 0.00 1358113.58 711802.75 8347225.33 0.145398E+09 0.00 0.34
November 35040270.13 8241.76 0.00 308313.28 3209.76 0.181506E+09 75430996.20 0.00 0.34
December 23314135.32 0.00 0.00 92032.37 0.00 0.284376E+09 12419595.85 0.00 0.34
                   
Annual Sum or Average 0.294326E+09 0.210963E+09 2885.78 12920646.27 30539498.07 0.109198E+10 0.727210E+09 31.08 0.34
Minimum of Months 165928.81 0.00 0.00 92032.37 0.00 0.00 240570.56 0.00 0.34
Maximum of Months 44867350.22 0.100403E+09 2885.78 2796042.03 16576937.10 0.284376E+09 0.145398E+09 31.08 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 26609112.35 0.00 0.00 12601566.39 0.00 0.494086E+09 0.151819E+10 0.00 0.39
February 15475434.46 0.00 0.00 12038659.15 0.00 0.325019E+09 0.140338E+10 0.00 0.39
March 17755941.04 0.00 0.00 12960390.82 0.00 0.211559E+09 0.161315E+10 0.00 0.39
April 4807715.64 5231088.04 0.00 18366546.36 0.00 22114066.97 0.123414E+10 0.00 0.39
May 0.00 33910021.36 0.00 16459316.03 0.00 3500781.23 0.748952E+09 0.00 0.39
June 0.00 77805863.26 0.00 13267098.83 0.00 17607.74 0.221325E+09 0.00 0.39
July 0.00 0.751627E+09 0.00 771212.71 0.00 0.00 2698947.47 0.00 0.39
August 11550.68 0.323533E+09 13002.10 7644582.03 0.00 0.00 96596475.13 85.78 0.39
September 0.00 0.319047E+09 0.00 13483223.47 0.00 147248.21 0.398220E+09 0.00 0.39
October 9037103.06 40488897.79 0.00 21620390.72 0.00 645096.80 0.123083E+10 0.00 0.39
November 20850662.24 73578.80 0.00 17261900.93 0.00 0.226154E+09 0.161374E+10 0.00 0.39
December 24416041.16 0.00 0.00 11394733.71 0.00 0.648028E+09 0.137354E+10 0.00 0.39
                   
Annual Sum or Average 0.118964E+09 0.155172E+10 13002.10 0.157870E+09 0.00 0.193127E+10 0.114548E+11 85.78 0.39
Minimum of Months 0.00 0.00 0.00 771212.71 0.00 0.00 2698947.47 0.00 0.39
Maximum of Months 26609112.35 0.751627E+09 13002.10 21620390.72 0.00 0.648028E+09 0.161374E+10 85.78 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.187570E+11 0.00 0.00 23934955.09 0.00 0.00 0.445778E+11 0.00 4.47
February 0.118965E+11 0.00 0.00 25345960.86 0.00 0.00 0.401493E+11 0.00 4.89
March 0.900278E+10 0.00 0.00 33707873.26 0.00 0.00 0.433972E+11 0.00 5.17
April 0.270445E+10 79058741.39 0.00 48155484.70 4228215.52 0.00 0.309745E+11 0.00 5.35
May 0.758867E+09 0.463103E+09 0.00 57401332.02 30411933.03 0.00 0.209565E+11 0.00 5.07
June 0.150209E+09 0.143114E+10 0.00 53701758.73 42394262.61 0.00 0.115605E+11 0.00 4.58
July 3839071.71 0.722710E+10 0.00 27399231.18 0.401183E+09 0.00 0.299826E+10 0.00 4.41
August 0.245099E+09 0.203442E+10 0.00 47135346.64 0.127697E+09 0.00 0.998756E+10 0.00 4.77
September 0.557220E+09 0.129485E+10 0.00 47212441.12 0.185696E+09 0.00 0.166558E+11 0.00 5.12
October 0.306892E+10 0.185116E+09 0.00 44662552.82 29616896.82 0.00 0.359213E+11 0.00 5.65
November 0.117735E+11 0.00 0.00 28684860.56 0.00 0.00 0.445216E+11 0.00 5.04
December 0.202436E+11 0.00 0.00 21496155.07 0.00 0.00 0.452071E+11 0.00 4.38
                   
Annual Sum or Average 0.791620E+11 0.127148E+11 0.00 0.458838E+09 0.821227E+09 0.00 0.346908E+12 0.00 4.91
Minimum of Months 3839071.71 0.00 0.00 21496155.07 0.00 0.00 0.299826E+10 0.00 4.38
Maximum of Months 0.202436E+11 0.722710E+10 0.00 57401332.02 0.401183E+09 0.00 0.452071E+11 0.00 5.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.112617E+11 0.00 0.00 33413343.36 0.00 0.00 0.523268E+11 0.00 4.49
February 0.643510E+10 0.00 0.00 34819372.13 0.00 0.00 0.459062E+11 0.00 4.92
March 0.371124E+10 0.00 0.00 45264742.19 0.00 0.00 0.491277E+11 0.00 5.22
April 0.121598E+10 83016760.58 0.00 60964993.64 232215.37 0.00 0.331273E+11 0.00 5.46
May 0.392990E+09 0.482327E+09 0.00 69820596.40 10963292.38 0.00 0.221040E+11 0.00 5.21
June 81116286.88 0.145660E+10 0.00 62845464.35 18544532.93 0.00 0.121157E+11 0.00 4.71
July 1244787.92 0.755926E+10 0.00 30311721.02 0.206257E+09 0.00 0.313585E+10 0.00 4.53
August 0.116389E+09 0.212408E+10 0.00 55916604.97 68386475.55 0.00 0.105189E+11 0.00 4.91
September 0.321342E+09 0.139360E+10 0.00 56389741.90 97579568.25 0.00 0.174202E+11 0.00 5.24
October 0.154168E+10 0.200953E+09 0.00 55930774.80 14919194.80 0.00 0.379729E+11 0.00 5.73
November 0.553209E+10 0.00 0.00 38163117.08 0.00 0.00 0.510902E+11 0.00 5.07
December 0.131273E+11 0.00 0.00 30995765.01 0.00 0.00 0.524529E+11 0.00 4.39
                   
Annual Sum or Average 0.437382E+11 0.132998E+11 0.00 0.574836E+09 0.416882E+09 0.00 0.387299E+12 0.00 4.99
Minimum of Months 1244787.92 0.00 0.00 30311721.02 0.00 0.00 0.313585E+10 0.00 4.39
Maximum of Months 0.131273E+11 0.755926E+10 0.00 69820596.40 0.206257E+09 0.00 0.524529E+11 0.00 5.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.107614E+09 0.00 0.00 0.671126E+11 0.00 16.38
February 0.00 0.00 0.00 0.100434E+09 0.00 0.00 0.553731E+11 0.00 18.32
March 0.00 0.00 0.00 0.117325E+09 0.00 0.00 0.556169E+11 0.00 19.58
April 0.00 0.115795E+09 0.00 0.130549E+09 0.00 0.00 0.345548E+11 0.00 19.75
May 0.00 0.687395E+09 0.00 0.122446E+09 0.00 0.00 0.207625E+11 0.00 18.35
June 0.00 0.205267E+10 0.00 91239677.92 0.00 0.00 0.106391E+11 0.00 16.53
July 0.00 0.954108E+10 0.00 31127818.43 0.00 0.00 0.257766E+10 0.00 16.01
August 0.00 0.281573E+10 0.00 86584684.22 0.00 0.00 0.957064E+10 0.00 17.31
September 0.00 0.198265E+10 0.00 96690691.31 0.00 0.00 0.166964E+11 0.00 18.54
October 0.00 0.296294E+09 0.00 0.124277E+09 0.00 0.00 0.408559E+11 0.00 21.04
November 0.00 0.00 0.00 0.111598E+09 0.00 0.00 0.601899E+11 0.00 18.91
December 0.00 0.00 0.00 0.106364E+09 0.00 0.00 0.690133E+11 0.00 15.91
                   
Annual Sum or Average 0.00 0.174916E+11 0.00 0.122625E+10 0.00 0.00 0.442963E+12 0.00 18.05
Minimum of Months 0.00 0.00 0.00 31127818.43 0.00 0.00 0.257766E+10 0.00 15.91
Maximum of Months 0.00 0.954108E+10 0.00 0.130549E+09 0.00 0.00 0.690133E+11 0.00 21.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.667589E+10 0.00 0.00 0.00 0.00 14166940.25 0.00 0.00 0.38
February 0.547319E+10 0.00 0.00 24429.08 0.00 7879858.18 9475432.91 0.00 0.41
March 0.527302E+10 0.00 0.00 429411.49 0.00 0.00 0.239895E+09 0.00 0.44
April 0.160885E+10 17274217.19 0.00 9669938.75 5883.48 0.00 0.222371E+10 0.00 0.55
May 0.203449E+09 0.116230E+09 0.00 15259366.12 0.00 0.00 0.272483E+10 0.00 0.66
June 0.00 0.396408E+09 0.00 15132902.16 0.00 0.00 0.197761E+10 0.00 0.75
July 0.00 0.160869E+10 0.00 5860721.51 0.00 0.00 0.523260E+09 0.00 0.73
August 3491291.92 0.495031E+09 0.00 13450157.53 0.00 0.00 0.159356E+10 0.00 0.73
September 0.170305E+09 0.326075E+09 0.00 12775069.76 0.00 0.00 0.216040E+10 0.00 0.71
October 0.190762E+10 48686512.28 0.00 9496132.78 0.00 0.00 0.259060E+10 0.00 0.60
November 0.551445E+10 0.00 0.00 993727.33 0.00 0.00 0.459368E+09 0.00 0.44
December 0.678215E+10 0.00 0.00 0.00 0.00 0.132138E+09 0.00 0.00 0.37
                   
Annual Sum or Average 0.336124E+11 0.300839E+10 0.00 83091856.49 5883.48 0.154185E+09 0.145027E+11 0.00 0.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.37
Maximum of Months 0.678215E+10 0.160869E+10 0.00 15259366.12 5883.48 0.132138E+09 0.272483E+10 0.00 0.75



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:54:28

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.180765E+12 0.126967E+11 0.157568E+12 0.496045E+12 0.759269E+11
February 0.189905E+12 0.102902E+11 0.121728E+12 0.415273E+12 0.117318E+12
March 0.309871E+12 0.995927E+10 0.114379E+12 0.414434E+12 0.180023E+12
April 0.325791E+12 0.565425E+10 0.642576E+11 0.265735E+12 0.418569E+12
May 0.360124E+12 0.316015E+10 0.356789E+11 0.165369E+12 0.650695E+12
June 0.344693E+12 0.103896E+10 0.790331E+10 0.670123E+11 0.823974E+12
July 0.333677E+12 -0.294725E+10 -0.387457E+11 -0.993923E+11 0.102199E+13
August 0.302843E+12 51795071.13 0.256759E+10 0.326577E+11 0.871100E+12
September 0.258042E+12 0.156636E+10 0.190087E+11 0.105541E+12 0.735507E+12
October 0.239268E+12 0.580311E+10 0.673787E+11 0.307736E+12 0.422354E+12
November 0.179851E+12 0.104348E+11 0.124378E+12 0.446291E+12 0.149716E+12
December 0.144381E+12 0.136962E+11 0.169082E+12 0.526610E+12 0.679369E+11
           
Annual Sum or Average 0.316921E+13 0.714045E+11 0.845184E+12 0.314331E+13 0.553512E+13
Minimum of Months 0.144381E+12 -0.294725E+10 -0.387457E+11 -0.993923E+11 0.679369E+11
Maximum of Months 0.360124E+12 0.136962E+11 0.169082E+12 0.526610E+12 0.102199E+13