Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:55:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 8739.47 | 770.32 | 770.32 |
Net Site Energy | 8507.90 | 749.91 | 749.91 |
Total Source Energy | 18439.69 | 1625.32 | 1625.32 |
Net Source Energy | 17706.33 | 1560.68 | 1560.68 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 164.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 835.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 473.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 390.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 602.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 67.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2482.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4304.42 | 4435.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 164.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 835.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 473.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 150.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 366.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 602.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 67.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2482.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 164.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 835.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 473.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 150.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 390.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 602.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 67.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2482.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 55.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 140.74 | 233.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 183.63 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 379.40 | 390.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 55.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 140.74 | 233.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 183.63 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 379.40 | 390.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 241.615 | 5.61 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -10.05 | -0.2 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 231.565 | 5.38 |
Electricity Coming From Utility | 4072.858 | 94.62 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4072.858 | 94.62 |
Total On-Site and Utility Electric Sources | 4304.423 | 100.00 |
Total Electricity End Uses | 4304.423 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 62.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7279.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.2037 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 7.5557 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 7.5557 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 7.2603 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.7794 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.2151 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 7.7715 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.1806 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4993 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.7715 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.7715 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 12.1686 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4993 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.5793 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.5793 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.2037 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 7.5557 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 7.5557 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 7.2603 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.7794 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.2151 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 7.7715 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.1806 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4993 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 7.7715 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 7.7715 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 12.1686 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4993 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.5793 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.5793 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.4264 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-19:10 | 06-JAN-22:00 | - | - | - | - | - | - | - | - | - | - | 19-JAN-21:10 |
Heating | 0.00 | 68290.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 94581.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 39200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 54264.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 19288.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29256.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2543.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3590.56 | 203719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1328.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 285493.07 | 326273.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 68290.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 94581.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 39200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 24992.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1217.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 17944.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29256.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2543.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3590.56 | 203719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 428.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 658.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 177.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2646.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1500.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 476.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1909.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 213.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 2690.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 140.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 13632.11 | 4807.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 233.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 237.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1201.57 | 423.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 233.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 237.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1201.57 | 423.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.07 | 0.728712 | 0.619000 | 1.28 | 1.00 | 0.500000 | 0.000523 | 0.000058 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.277162 | 0.184399 | 0.429000 | 0.118903 | 0.510806 | 0.500000 | 0.002066 | 0.000019 | 0.118903 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.205020 | 0.288673 | 0.671000 | 0.137568 | 0.769794 | 0.500000 | 0.001320 | 0.000011 | 0.137568 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.203276 | 0.615681 | 0.010000 | 0.002033 | 1.00 | 0.500000 | 0.000619 | 0.000012 | 0.047280 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.093961 | 0.768472 | 0.922000 | 0.086632 | 1.00 | 0.500000 | 0.000496 | 0.000010 | 0.086632 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.30 | 0.018025 | 0.010000 | 0.032990 | 0.300000 | 0.500000 | 0.021137 | 0.000015 | 0.061999 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.30 | 0.110642 | 0.780000 | 1.01 | 0.780000 | 0.500000 | 0.003444 | 0.000079 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.36 | 0.228472 | 0.651000 | 2.84 | 0.651000 | 0.500000 | 0.001668 | 0.000211 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.08 | 1.00 | 0.662000 | 0.712405 | 1.00 | 0.500000 | 0.000345 | 0.000077 | 0.712405 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.06 | 0.122724 | 0.865000 | 1.78 | 0.865000 | 0.500000 | 0.003105 | 0.000112 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.16 | 0.116738 | 0.823000 | 1.78 | 0.823000 | 0.500000 | 0.003264 | 0.000113 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.16 | 0.065660 | 0.256000 | 0.552022 | 0.300000 | 0.500000 | 0.010437 | 0.000032 | 0.552022 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.610095 | 0.514738 | 0.309000 | 0.188519 | 1.00 | 0.500000 | 0.000740 | 0.000042 | 0.188519 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6637.13 | 0.000058 | 138.41 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2134.88 | 0.000019 | 51.15 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1279.13 | 0.000011 | 27.83 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1327.34 | 0.000012 | 36.22 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1133.18 | 0.000010 | 25.68 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 1740.54 | 0.000015 | 47.50 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 8987.91 | 0.000079 | 194.62 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 24130.37 | 0.000211 | 520.51 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3130.24 | 0.000027 | 89.45 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3129.91 | 0.000027 | 89.44 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 19054.10 | 0.000167 | 544.48 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 19059.31 | 0.000167 | 544.63 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3130.47 | 0.000027 | 89.46 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3130.13 | 0.000027 | 89.45 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 8828.13 | 0.000077 | 198.51 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 997.88 | 0.000009 | 28.51 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 997.87 | 0.000009 | 28.51 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 4834.36 | 0.000042 | 138.14 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12811.71 | 0.000112 | 272.66 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12886.19 | 0.000113 | 274.36 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 3620.01 | 0.000032 | 76.54 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 4848.02 | 0.000042 | 128.10 |
VAV WITH REHEAT HEATING COIL | 90884.98 | 0.000795 | 1628.96 |
FLR_3_DOAS HEATING COIL | 9427.25 | 0.000082 | 168.97 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.823397 | 0.000027 | 0.000258 |
ROOM_2_FLR_3 FAN COIL | 0.792069 | 0.000027 | 0.000249 |
ROOM_3_MULT19_FLR_3 FAN COIL | 4.98 | 0.000167 | 0.001527 |
ROOM_4_MULT19_FLR_3 FAN COIL | 4.84 | 0.000167 | 0.001602 |
ROOM_5_FLR_3 FAN COIL | 0.734486 | 0.000027 | 0.000231 |
ROOM_6_FLR_3 FAN COIL | 0.707860 | 0.000027 | 0.000223 |
ROOM_1_FLR_6 FAN COIL | 0.213839 | 0.000009 | 0.000067 |
ROOM_2_FLR_6 FAN COIL | 0.205205 | 0.000009 | 0.000064 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.02 | 0.000042 | 0.000326 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.823397 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.792069 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 4.98 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 4.84 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.734486 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.707860 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.213839 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.205205 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.02 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008582 | 12.80 | 0.008500 | 0.000258 | 0.823397 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008585 | 12.80 | 0.008500 | 0.000249 | 0.792069 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008494 | 12.80 | 0.008494 | 0.001527 | 4.98 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008784 | 12.80 | 0.008500 | 0.001602 | 4.84 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008592 | 12.80 | 0.008500 | 0.000231 | 0.734486 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008595 | 12.80 | 0.008500 | 0.000223 | 0.707860 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008579 | 12.80 | 0.008500 | 0.000067 | 0.213839 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008582 | 12.80 | 0.008500 | 0.000064 | 0.205205 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008656 | 12.80 | 0.008500 | 0.000326 | 1.02 | |
VAV WITH REHEAT COOLING COIL | 27.44 | 6.70 | 0.009046 | 10.94 | 0.008500 | 0.012184 | 19.78 | 426010.35 |
FLR_3_DOAS COOLING COIL | 31.30 | 6.70 | 0.008233 | 11.91 | 0.008233 | 0.001371 | 2.05 | 47946.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.91 | 10.53 | 19.88 | 10.53 | 19.78 | 19.78 | 0.300000 | 0.532452 | 19.78 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 19.78 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 19.78 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.012184 | 0.000039 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000795 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001371 | 0.000347 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000082 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.018104 | 2926.55 | |
HEATSYS1 PUMP | 0.002171 | 647.29 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002171 | 0.260502 |
COOLSYS1 | 0.018104 | 2.17 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 248141.04 | 248141.04 | 0.002171 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.018104 | 2026.15 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.018104 | 633006.01 | 633576.04 | 72.23 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.204 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.584 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 7.556 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 18.316 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 7.556 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 18.316 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 7.260 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.640 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.779 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.469 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.215 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.745 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 7.772 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.152 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.181 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.251 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.499 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.499 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.772 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.592 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.772 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.592 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.169 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.672 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.499 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.499 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 12276.143 | 6.204 | 115.270 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12276.143 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 506.769 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 506.769 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 586.840 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 586.840 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1192.447 | 7.260 | 449.641 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1192.447 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 358.135 | 3.779 | 175.557 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 358.135 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 406.984 | 5.215 | 48.451 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.984 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1467.746 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1467.746 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10701.700 | 8.181 | 25.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10701.700 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1752.054 | 4.499 | 83.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1752.054 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2577.487 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2577.487 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2577.487 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2577.487 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1257.069 | 12.169 | 56.528 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1257.069 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1854.278 | 4.499 | 83.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1854.278 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 37 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 | ||
2 | RESWINDOW_U_0.248_SHGC_0.21 | 38 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.680 | 0.5995 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.312 | 3.5001E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.6748E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.4057E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1077 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.8170E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2656E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.7402E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9121E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.7843E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1093 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3701E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1219 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.8659E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 8.0356E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.4381E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2628E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3264E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3125E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3455E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7798E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0152E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6972E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.8853E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8610E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0256E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3125E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3455E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7798E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0152E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6972E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.8853E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8610E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0256E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 27949.55608 | 27949.55608 | 2.06922 | 2.06922 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:50:00 | 27.01317 | 8.22670E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 3.80000 | 5.05843E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 3743.38492 | 3743.38492 | 0.27716 | 0.27716 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 67.07136 | 10.82900 | 7.92170E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1519.22666 | 1519.22666 | 6.63505E-002 | 7.92170E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 67.07136 | 10.82900 | 7.92170E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2768.96279 | 2768.96279 | 0.20502 | 0.20502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 29.75733 | 8.23104E-003 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 566.81892 | 566.81892 | 2.47556E-002 | 9.17335E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2746.01361 | 2746.01361 | 0.20328 | 0.20328 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16400 | 8.23009E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1082.56399 | 1082.56399 | 4.72805E-002 | 4.72805E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1269.29070 | 1269.29070 | 9.39612E-002 | 9.39612E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 31.12200 | 8.23321E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 684.65217 | 684.65217 | 2.99019E-002 | 5.77652E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44561.61267 | 44561.61267 | 3.29902 | 3.29902 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1419.58488 | 1419.58488 | 6.19987E-002 | 6.19987E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17552.68889 | 17552.68889 | 1.30071 | 1.30071 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 3734.40832 | 3734.40832 | 0.16310 | 0.67638 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 58910.51641 | 58910.51641 | 4.36307 | 4.36307 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 9423.23868 | 9423.23868 | 0.41156 | 1.89399 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 8253.78856 | 8253.78856 | 0.82340 | 0.82340 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3130.28324 | 3130.28324 | 0.13751 | 0.13751 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 7939.74931 | 7939.74931 | 0.79207 | 0.79207 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3129.94914 | 3129.94914 | 0.13750 | 0.13750 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 49899.05939 | 49899.05939 | 4.97771 | 4.97771 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 18058.64923 | 18058.64923 | 0.79334 | 0.83707 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 48499.79434 | 48499.79434 | 4.83851 | 4.83851 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 18062.04616 | 18062.04616 | 0.79348 | 0.83730 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 7362.53579 | 7362.53579 | 0.73449 | 0.73449 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16150 | 8.22694E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3130.50973 | 3130.50973 | 0.13752 | 0.13752 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 7095.63344 | 7095.63344 | 0.70786 | 0.70786 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3130.17557 | 3130.17557 | 0.13751 | 0.13751 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 14536.10269 | 14536.10269 | 1.07614 | 1.07614 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 5138.87546 | 5138.87546 | 0.22444 | 0.47476 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2143.54078 | 2143.54078 | 0.21384 | 0.21384 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 997.89169 | 997.89169 | 4.38377E-002 | 4.38377E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2056.99095 | 2056.99095 | 0.20521 | 0.20521 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 997.88413 | 997.88413 | 4.38374E-002 | 4.38374E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10220.59994 | 10220.59994 | 1.01963 | 1.01963 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 4834.40974 | 4834.40974 | 0.21238 | 0.21238 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 27781.34385 | 27781.34385 | 2.05929 | 2.05929 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 3585.87408 | 3585.87408 | 0.15661 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29206.23700 | 29206.23700 | 2.16487 | 2.16487 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 3658.33035 | 3658.33035 | 0.15978 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29050.92322 | 29050.92322 | 2.15633 | 2.15633 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.23222E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 774.92019 | 774.92019 | 3.38411E-002 | 0.36735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 3.80000 | 5.05843E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8241.01412 | 8241.01412 | 0.61009 | 0.61009 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 31.22583 | 8.23338E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 3871.54562 | 3871.54562 | 0.16909 | 0.16909 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 3.80000 | 5.05843E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 343710.67 | 19.77607 | 19.77607 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 109523.50 | 7.14951 | 7.14951 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 45064.07 | 13.69173 | 2.05125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 31423.05 | 2.52447 | 2.05125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.06922 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.72871 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28085 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.22840E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.80645E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28085 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6637.12553 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.80645E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 138.40581 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.27716 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18440 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11890 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51081 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06618E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86768E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11890 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2134.87734 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86768E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 51.14948 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20502 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28867 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.67100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13757 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76979 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31983E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11904E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13757 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1279.12913 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11904E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 27.82512 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20328 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61568 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03276E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.18826E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16121E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.72805E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1327.33926 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16121E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.22438 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.39612E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.76847 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.92200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66322E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.95789E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.91359E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66322E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1133.18433 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.91359E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 25.67568 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.29902 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.80254E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.29902E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11368E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52270E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.19987E-002 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1740.53557 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52270E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 47.50091 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30071 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11064 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.78000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01455 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44354E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.86302E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01455 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8987.91463 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.86302E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 194.61542 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.36307 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22847 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.65100 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84036 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65100 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66760E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.11103E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84036 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24130.37452 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11103E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 520.51361 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.82340 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.82340 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.73847E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.58436E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69393 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58224E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.58436E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.82340 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3130.24264 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73847E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 89.45042 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.79207 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.79207 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.73818E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.48815E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69392 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58535E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.48815E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.79207 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3129.90855 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73818E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 89.44088 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.97771 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 4.97771 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.66694E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.52723E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69438 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49397E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49397E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.52723E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.97771 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19054.09831 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66694E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 544.48490 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.83851 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 4.83851 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.66739E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.60226E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69342 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78364E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.60226E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.83851 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19059.30861 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66739E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 544.63380 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.73449 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.73449 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.73867E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.31132E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69391 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59178E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.31132E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.73449 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3130.46913 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73867E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 89.45690 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.70786 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.70786 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.73838E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.22955E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69391 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59510E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.22955E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.70786 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3130.13497 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73838E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 89.44735 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07614 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.66200 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71240 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45444E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.72323E-005 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71240 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8828.12917 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.72323E-005 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 198.51498 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.21384 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.21384 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.72988E-006 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.70628E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69393 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57929E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.70628E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.21384 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 997.87903 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.72988E-006 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 28.51420 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.20521 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.20521 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.72981E-006 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.44114E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69393 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58249E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.44114E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.20521 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 997.87147 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.72981E-006 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 28.51398 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01963 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.01963 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.22931E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.26492E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69362 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65617E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.26492E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.01963 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4834.36033 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.22931E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 138.13972 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05929 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12272 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.86500 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78128 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10454E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12082E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78128 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12811.70965 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12082E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 272.66058 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.16487 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11674 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.82300 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78169 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82300 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26371E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12734E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78169 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12886.19158 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12734E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.35873 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15633 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.56597E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55202 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04368E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16694E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55202 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3620.00659 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16694E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 76.54370 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61009 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51474 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18852 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.40182E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.24126E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18852 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4848.02170 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.24126E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 128.09848 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.90828 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.52980 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 19.87816 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.52980 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 19.77607 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 19.77607 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53245 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 19.77607 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 19.77607 |
337 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.43823 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94420 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.04614E-003 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 426010.35140 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.21838E-002 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 19.77607 |
345 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 90884.97859 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.95101E-004 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1628.96382 |
348 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 19.77607 |
349 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.21838E-002 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.90838E-005 |
351 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.95101E-004 |
352 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
354 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.30000 |
355 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91243 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23349E-003 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23349E-003 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 47946.24805 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.37126E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
362 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 9427.24706 |
363 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.24737E-005 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 168.96790 |
365 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
366 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37126E-003 |
367 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.47266E-004 |
368 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.24737E-005 |
369 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.81039E-002 |
370 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 2926.54688 |
371 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.17085E-003 |
372 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.26050 |
373 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.17085E-003 |
374 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 647.29059 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
376 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 248141.03768 |
377 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 248141.04000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.17085E-003 |
379 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.81039E-002 |
380 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.17247 |
381 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.81039E-002 |
382 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2026.14711 |
383 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.81039E-002 |
384 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 633006.01468 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 633576.04000 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 72.22767 |
387 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
388 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
389 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
390 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
391 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6671.45 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2144.29 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1285.50 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1332.39 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1138.53 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 1747.15 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9032.85 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 24251.41 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 3371.60 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 3371.24 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 20523.09 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 20528.70 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 3371.84 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 3371.48 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 8870.08 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1074.79 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1074.78 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5206.94 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12876.75 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12951.58 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 3638.49 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 4867.07 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 76270.44 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 7911.32 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 13463.26 | 11579.58 | 1883.68 | 0.86 | 2721.80 | 27.61 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 12958.52 | 11141.55 | 1816.97 | 0.86 | 2617.42 | 26.55 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 80164.99 | 69604.59 | 10560.39 | 0.87 | 16659.01 | 168.96 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 82060.53 | 69077.67 | 12982.87 | 0.84 | 15790.15 | 160.15 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 12032.63 | 10337.80 | 1694.83 | 0.86 | 2428.27 | 24.63 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 11603.57 | 9965.46 | 1638.11 | 0.86 | 2339.46 | 23.73 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3494.54 | 3006.61 | 487.93 | 0.86 | 707.07 | 7.17 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3355.44 | 2885.89 | 469.55 | 0.86 | 678.30 | 6.88 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 16902.14 | 14418.93 | 2483.22 | 0.85 | 3351.01 | 33.99 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 491155.39 | 345038.10 | 146117.29 | 0.70 | 77327.38 | 784.30 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51303.12 | 35829.51 | 15473.61 | 0.70 | 7298.17 | 74.02 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.12 | 14.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6562439383E-002 | 2.2169723447E-002 | Pass | Pass | 6.5336890365E-003 | 1.8860647831E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.2930536383E-002 | 5.1375616504E-002 | Pass | Pass | 3.1328175941E-002 | 4.5856991346E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.9454299908E-002 | 2.7577315616E-002 | Pass | Pass | 1.2020081215E-002 | 2.8699892941E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7421347870E-002 | 1.7886780915E-002 | Pass | Pass | 6.9279165426E-003 | 1.8593581803E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.8219010091E-004 | 3.9445829812E-004 | Pass | Pass | 1.9690016240E-002 | 2.6033054816E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.3321250058E-005 | 1.4114413716E-004 | Pass | Pass | 2.0861953545E-002 | 6.0355591592E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8248713910E-002 | 5.5628921935E-002 | Pass | Pass | 2.0214916333E-002 | 4.6290360082E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.6470923150E-002 | 4.6194006329E-002 | Pass | Pass | 9.1025073502E-003 | 2.1780556869E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4083699126E-002 | 9.6938847969E-002 | Pass | Pass | 1.1766777791 | 6.1597703399 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.1223334213E-002 | 4.7013494432E-002 | Pass | Pass | 0.1813662708 | 0.8786567927 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.9916407706E-002 | 5.8847511199E-002 | Pass | Pass | 4.5359543019E-002 | 0.1747384465 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.9115757860E-002 | 0.1473379337 | Pass | Pass | 0.3253965959 | 1.4688410483 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2342122333E-002 | 0.1855946154 | Pass | Pass | 4.5825978651 | 51.0756254364 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.5497959396E-002 | 0.1481152957 | Pass | Pass | 0.5990527984 | 3.1218244445 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3131671641E-003 | 7.8310423587E-003 | Pass | Pass | 1.7840907774E-002 | 3.9908214475E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.3945579183E-002 | 7.1530623670E-002 | Pass | Pass | 0.3614567900 | 1.8028098394 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.6833435744E-002 | 9.8625066495E-002 | Pass | Pass | 0.1153983907 | 0.4180308553 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.8630883116E-002 | 0.2277730750 | Pass | Pass | 0.6223243872 | 4.5254185473 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8724533067E-002 | 9.4936479711E-002 | Pass | Pass | 9.7646039761E-003 | 2.0182499173E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.1822090843E-002 | 9.5070518380E-002 | Pass | Pass | 9.5293296876E-003 | 2.1732794729E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2829750038E-004 | 1.7390008115E-003 | Pass | Pass | 2.2854853686E-002 | 4.2956881309E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.6879712679E-002 | 1.3387199744E-002 | Pass | Pass | 7.8767390109E-003 | 2.0878355607E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3489.72 | 78.33 | 978.04 | 3812.37 | 3933.07 | 12291.54 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.408 | 0.210 | 0.290 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.408 | 0.210 | 0.290 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.408 | 0.210 | 0.290 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.408 | 0.210 | 0.290 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.408 | 0.210 | 0.290 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.408 | 0.210 | 0.290 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.408 | 0.210 | 0.290 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.408 | 0.210 | 0.290 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 432.95 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.2037 | 1978.83 | 12276.14 | LightsWired | LTG_SCH_BASEMENT | 42.56 | 168.00 | 42.52 | 0.0000 | Y | 97.97 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 7.5557 | 67.07 | 506.77 | LightsWired | LTG_SCH_RETAIL | 46.66 | 168.00 | 46.61 | 0.0000 | Y | 4.43 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 7.5557 | 77.67 | 586.84 | LightsWired | LTG_SCH_RETAIL | 46.66 | 168.00 | 46.61 | 0.0000 | Y | 5.13 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 7.2603 | 164.24 | 1192.45 | LightsWired | LTG_SCH_MECHANIC | 41.09 | 168.00 | 41.04 | 0.0000 | Y | 9.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.7794 | 94.76 | 358.14 | LightsWired | LTG_SCH_STORAGE | 31.36 | 168.00 | 31.32 | 0.0000 | Y | 2.11 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.2151 | 78.04 | 406.98 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 3.92 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 7.7715 | 188.86 | 1467.75 | LightsWired | LTG_SCH_DINING | 38.15 | 168.00 | 25.88 | 0.0000 | Y | 7.13 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.1806 | 1308.19 | 10701.70 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.54 | 0.0000 | Y | 83.46 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4993 | 1557.62 | 7008.22 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 57.85 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 7.7715 | 331.66 | 2577.49 | LightsWired | LTG_SCH_DINING | 38.15 | 168.00 | 32.11 | 0.0000 | Y | 15.53 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 7.7715 | 331.66 | 2577.49 | LightsWired | LTG_SCH_DINING | 38.15 | 168.00 | 32.11 | 0.0000 | Y | 15.53 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 12.1686 | 103.30 | 1257.07 | LightsWired | LTG_SCH_KITCHEN | 41.09 | 168.00 | 41.04 | 0.0000 | Y | 9.68 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4993 | 412.12 | 1854.28 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.31 |
Interior Lighting Total | 5.5793 | 11345.29 | 63298.26 | 293.56 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10701.70 | 749.12 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10701.70 | 749.12 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1467.75 | 572.42 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1467.75 | 572.42 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 9571.94 | AstronomicalClock | - | 83.75 | 83.75 | 150.49 | |
Exterior Lighting Total | 9571.94 | 150.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 248141.04 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 633576.04 | 3.11 | 633687.41 | 3.11 | 4.12 | 14.07 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9036.43 | 13463.26 | 11579.58 | 1883.68 | 0.86 | - | 2721.80 | 27.61 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 8700.01 | 12958.52 | 11141.55 | 1816.97 | 0.86 | - | 2617.42 | 26.55 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 53401.01 | 80164.99 | 69604.59 | 10560.39 | 0.87 | - | 16659.01 | 168.96 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 56024.25 | 82060.53 | 69077.67 | 12982.87 | 0.84 | - | 15790.15 | 160.15 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 8081.71 | 12032.63 | 10337.80 | 1694.83 | 0.86 | - | 2428.27 | 24.63 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 7795.79 | 11603.57 | 9965.46 | 1638.11 | 0.86 | - | 2339.46 | 23.73 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2344.91 | 3494.54 | 3006.61 | 487.93 | 0.86 | - | 707.07 | 7.17 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2252.20 | 3355.44 | 2885.89 | 469.55 | 0.86 | - | 678.30 | 6.88 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 11416.07 | 16902.14 | 14418.93 | 2483.22 | 0.85 | - | 3351.01 | 33.99 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 426010.35 | 491155.39 | 345038.10 | 146117.29 | 0.70 | - | 77327.38 | 784.30 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 47946.25 | 51303.12 | 35829.51 | 15473.61 | 0.70 | - | 7298.17 | 74.02 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6637.13 | 6671.45 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2134.88 | 2144.29 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1279.13 | 1285.50 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1327.34 | 1332.39 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1133.18 | 1138.53 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1740.54 | 1747.15 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8987.91 | 9032.85 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24130.37 | 24251.41 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3130.24 | 3371.60 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3129.91 | 3371.24 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19054.10 | 20523.09 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19059.31 | 20528.70 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3130.47 | 3371.84 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3130.13 | 3371.48 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8828.13 | 8870.08 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 997.88 | 1074.79 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 997.87 | 1074.78 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 4834.36 | 5206.94 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12811.71 | 12876.75 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12886.19 | 12951.58 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 3620.01 | 3638.49 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 4848.02 | 4867.07 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 90884.98 | 76270.44 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 9427.25 | 7911.32 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.82 | 579.37 | 703.64 | 1.00 | 1.25 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.79 | 557.33 | 703.64 | 1.00 | 1.26 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 4.98 | 3502.49 | 703.64 | 1.00 | 0.97 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 4.84 | 3404.55 | 703.64 | 1.00 | 0.97 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.73 | 516.81 | 703.64 | 1.00 | 1.28 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.71 | 498.08 | 703.64 | 1.00 | 1.30 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.21 | 150.47 | 703.64 | 1.00 | 1.99 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.21 | 144.39 | 703.64 | 1.00 | 2.03 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.02 | 717.45 | 703.64 | 1.00 | 1.19 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 19.78 | 44311.03 | 2240.64 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.018104 | 2926.55 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002171 | 647.29 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.018104 | 2026.15 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.95 | 0.68 | 0.60 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.95 | 0.31 | 0.04 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 27949.56 | 27949.56 | 14.12 | 2.069 | 2.069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:50:00 | 24.00 | 24.00 | 0.00936 | 27.01 | 0.00823 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3743.38 | 3743.38 | 55.81 | 0.277 | 0.277 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00913 | 30.93 | 0.00823 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2768.96 | 2768.96 | 35.65 | 0.205 | 0.205 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 24.00 | 24.00 | 0.00950 | 29.76 | 0.00823 | 0.092 | 0.00 |
MECH_FLR_1 | 2746.01 | 2746.01 | 16.72 | 0.203 | 0.203 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00870 | 29.16 | 0.00823 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1269.29 | 1269.29 | 13.39 | 0.094 | 0.094 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00883 | 31.12 | 0.00823 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44561.61 | 44561.61 | 571.01 | 3.299 | 3.299 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00854 | 31.30 | 0.00823 | 0.000 | 0.00 |
CAFE_FLR_1 | 17552.69 | 17552.69 | 92.94 | 1.301 | 1.301 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 23.99 | 0.01030 | 30.93 | 0.00823 | 0.676 | 0.00 |
LOBBY_FLR_1 | 58910.52 | 58910.52 | 45.03 | 4.363 | 4.363 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.01010 | 31.08 | 0.00823 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 8253.79 | 8253.79 | 211.52 | 0.823 | 0.823 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00858 | 30.53 | 0.00823 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7939.75 | 7939.75 | 203.49 | 0.792 | 0.792 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00859 | 30.41 | 0.00823 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 49899.06 | 49899.06 | 2034.72 | 4.978 | 4.978 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00849 | 31.08 | 0.00823 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 48499.79 | 48499.79 | 1977.12 | 4.839 | 4.839 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 21.11 | 21.11 | 0.00878 | 31.30 | 0.00823 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7362.54 | 7362.54 | 188.68 | 0.734 | 0.734 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 21.11 | 21.11 | 0.00859 | 27.16 | 0.00823 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7095.63 | 7095.63 | 181.86 | 0.708 | 0.708 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00860 | 26.66 | 0.00823 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 14536.10 | 14536.10 | 37.33 | 1.076 | 1.076 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00978 | 31.30 | 0.00823 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2143.54 | 2143.54 | 54.93 | 0.214 | 0.214 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00858 | 30.53 | 0.00823 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2056.99 | 2056.99 | 52.72 | 0.205 | 0.205 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00858 | 30.41 | 0.00823 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10220.60 | 10220.60 | 416.65 | 1.020 | 1.020 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00866 | 31.08 | 0.00823 | 0.099 | 0.00 |
BANQUET_FLR_6 | 27781.34 | 27781.34 | 83.77 | 2.059 | 2.059 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 23.98 | 0.01052 | 31.30 | 0.00823 | 1.188 | 0.00 |
DINING_FLR_6 | 29206.24 | 29206.24 | 88.06 | 2.165 | 2.165 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 23.98 | 0.01042 | 31.30 | 0.00823 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29050.92 | 29050.92 | 281.22 | 2.156 | 2.156 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01015 | 30.50 | 0.00823 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8241.01 | 8241.01 | 20.00 | 0.610 | 0.610 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00910 | 31.23 | 0.00823 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 21.65 | 0.00506 | 3.80 | 0.00506 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1519.23 | 1519.23 | 22.65 | 0.066 | 0.079 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00760 | 3.80 | 0.00506 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 566.82 | 566.82 | 7.30 | 0.025 | 0.092 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00759 | 3.80 | 0.00506 | 0.092 | 0.00 |
MECH_FLR_1 | 1082.56 | 1082.56 | 6.59 | 0.047 | 0.047 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00751 | 3.80 | 0.00506 | 0.000 | 0.00 |
STORAGE_FLR_1 | 684.65 | 684.65 | 7.23 | 0.030 | 0.058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | 3.80 | 0.00506 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1419.58 | 1419.58 | 18.19 | 0.062 | 0.062 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00750 | 3.80 | 0.00506 | 0.000 | 0.00 |
CAFE_FLR_1 | 3734.41 | 3734.41 | 19.77 | 0.163 | 0.676 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00764 | 3.80 | 0.00506 | 0.676 | 0.00 |
LOBBY_FLR_1 | 9423.24 | 9423.24 | 7.20 | 0.412 | 1.894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00760 | 3.80 | 0.00506 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3130.28 | 3130.28 | 80.22 | 0.138 | 0.138 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00756 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3129.95 | 3129.95 | 80.22 | 0.137 | 0.137 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00756 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 18058.65 | 18058.65 | 736.37 | 0.793 | 0.837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 18062.05 | 18062.05 | 736.31 | 0.793 | 0.837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3130.51 | 3130.51 | 80.22 | 0.138 | 0.138 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00756 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3130.18 | 3130.18 | 80.23 | 0.138 | 0.138 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00756 | 3.80 | 0.00506 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 5138.88 | 5138.88 | 13.20 | 0.224 | 0.475 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00766 | 3.80 | 0.00506 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 997.89 | 997.89 | 25.57 | 0.044 | 0.044 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 997.88 | 997.88 | 25.58 | 0.044 | 0.044 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4834.41 | 4834.41 | 197.08 | 0.212 | 0.212 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 3.80 | 0.00506 | 0.099 | 0.00 |
BANQUET_FLR_6 | 3585.87 | 3585.87 | 10.81 | 0.157 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00775 | 3.80 | 0.00506 | 1.188 | 0.00 |
DINING_FLR_6 | 3658.33 | 3658.33 | 11.03 | 0.160 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00775 | 3.80 | 0.00506 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 774.92 | 774.92 | 7.50 | 0.034 | 0.367 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00539 | 3.80 | 0.00506 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 3871.55 | 3871.55 | 9.39 | 0.169 | 0.169 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00779 | 3.80 | 0.00506 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 19.78 | 19.78 | 7.15 | 7.15 | 19.7761 | 10.5298 | 19.7761 | 0.5325 | 0.3000 |
FLR_3_DOAS | 13.69 | 2.05 | 2.52 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6637.126 | 6637.126 | 1.280849 | 0.00005806 | 138.406 | 12/21 00:10:00 | 12/21 00:10:00 | 6637.13 | 6637.13 | 1.280849 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 6674.43 | 6674.43 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2134.877 | 2134.877 | 0.118903 | 0.00001868 | 51.149 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2134.88 | 2134.88 | 0.118903 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00760494 | 48.2804 | 1519.23 | 0.00 | 2146.05 | 2146.05 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1279.129 | 1279.129 | 0.137568 | 0.00001119 | 27.825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1279.13 | 1279.13 | 0.137568 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00759291 | 48.2045 | 566.82 | 0.00 | 1286.22 | 1286.22 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1327.339 | 1327.339 | 0.047280 | 0.00001161 | 36.224 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1327.34 | 1327.34 | 0.047280 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00751221 | 47.6982 | 1082.56 | 0.00 | 1333.92 | 1333.92 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1133.184 | 1133.184 | 0.086632 | 0.00000991 | 25.676 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1133.18 | 1133.18 | 0.086632 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00754849 | 47.9259 | 684.65 | 0.00 | 1139.29 | 1139.29 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 1740.536 | 1740.536 | 0.061999 | 0.00001523 | 47.501 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1740.54 | 1740.54 | 0.061999 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00749587 | 47.5962 | 1419.58 | 0.00 | 1749.17 | 1749.17 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 8987.915 | 8987.915 | 1.014551 | 0.00007863 | 194.615 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8987.91 | 8987.91 | 1.014551 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00763985 | 48.4992 | 3734.41 | 0.00 | 9037.81 | 9037.81 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 24130.375 | 24130.375 | 2.840359 | 0.00021110 | 520.514 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 24130.37 | 24130.37 | 2.840359 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00759845 | 48.2392 | 9423.24 | 0.00 | 24264.48 | 24264.48 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9036.433 | -999.000 | 0.823397 | 0.00025844 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 9036.43 | 8861.61 | 0.823397 | 21.69 | 15.44 | 0.00858224 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00858224 | 54.0309 | 8253.79 | 0.00 | 9208.42 | 9208.42 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3130.243 | 3130.243 | 0.137514 | 0.00002738 | 89.450 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3130.24 | 3130.24 | 0.137514 | 21.11 | 14.31 | 0.00756449 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00756449 | 47.7005 | 3130.28 | 0.00 | 3374.50 | 3374.50 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 8700.013 | -999.000 | 0.792069 | 0.00024881 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 8700.01 | 8525.46 | 0.792069 | 21.69 | 15.45 | 0.00858535 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00823207 | 18.16 | 0.0000 | 21.11 | 0.00858535 | 54.0503 | 7939.75 | 0.00 | 8865.48 | 8865.48 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3129.909 | 3129.909 | 0.137500 | 0.00002738 | 89.441 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3129.91 | 3129.91 | 0.137500 | 21.11 | 14.31 | 0.00756448 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00756448 | 47.7004 | 3129.95 | 0.00 | 3374.14 | 3374.14 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 53401.005 | -999.000 | 4.977705 | 0.00152723 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 53401.01 | 53401.01 | 4.977705 | 21.69 | 15.37 | 0.00849397 | 12.80 | 11.93 | 0.00849397 | 31.08 | 0.00823314 | 18.38 | 0.0000 | 21.11 | 0.00849397 | 53.4816 | 49899.06 | 0.00 | 54430.17 | 54430.17 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 19054.098 | 19054.098 | 0.837072 | 0.00016669 | 544.485 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19054.10 | 19054.10 | 0.837072 | 21.11 | 14.34 | 0.00759494 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00759494 | 47.8896 | 18058.65 | 0.00 | 20540.95 | 20540.95 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 56024.255 | -999.000 | 4.838506 | 0.00160226 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | unknown | 8/21 14:50:00 | 56024.25 | 52454.74 | 4.838506 | 21.69 | 15.62 | 0.00878364 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 0.0000 | 21.11 | 0.00878364 | 55.2823 | 48499.79 | 0.00 | 57072.48 | 55459.85 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 19059.309 | 19059.309 | 0.837300 | 0.00016674 | 544.634 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19059.31 | 19059.31 | 0.837300 | 21.11 | 14.34 | 0.00759491 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00759491 | 47.8894 | 18062.05 | 0.00 | 20546.57 | 20546.57 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 8081.712 | -999.000 | 0.734486 | 0.00023113 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | unknown | 8/21 09:30:00 | 8081.71 | 7907.60 | 0.734486 | 21.69 | 15.45 | 0.00859178 | 12.80 | 11.93 | 0.00850000 | 27.16 | 0.00822694 | 17.07 | 0.0000 | 21.11 | 0.00859178 | 54.0902 | 7362.54 | 0.00 | 8236.55 | 8236.55 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3130.469 | 3130.469 | 0.137524 | 0.00002739 | 89.457 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3130.47 | 3130.47 | 0.137524 | 21.11 | 14.31 | 0.00756452 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00756452 | 47.7006 | 3130.51 | 0.00 | 3374.74 | 3374.74 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7795.795 | -999.000 | 0.707860 | 0.00022295 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 7795.79 | 7621.91 | 0.707860 | 21.69 | 15.45 | 0.00859510 | 12.80 | 11.93 | 0.00850000 | 26.66 | 0.00822614 | 16.89 | 0.0000 | 21.11 | 0.00859510 | 54.1108 | 7095.63 | 0.00 | 7945.04 | 7945.04 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3130.135 | 3130.135 | 0.137510 | 0.00002738 | 89.447 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3130.13 | 3130.13 | 0.137510 | 21.11 | 14.31 | 0.00756451 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00756451 | 47.7006 | 3130.18 | 0.00 | 3374.38 | 3374.38 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 8828.129 | 8828.129 | 0.712405 | 0.00007723 | 198.515 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8828.13 | 8828.13 | 0.712405 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00766425 | 48.6517 | 5138.88 | 0.00 | 8875.86 | 8875.86 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2344.906 | -999.000 | 0.213839 | 0.00006706 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 2344.91 | 2301.13 | 0.213839 | 21.69 | 15.44 | 0.00857929 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00857929 | 54.0127 | 2143.54 | 0.00 | 2389.57 | 2389.57 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 997.879 | 997.879 | 0.043838 | 0.00000873 | 28.514 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 997.88 | 997.88 | 0.043838 | 21.11 | 14.39 | 0.00764714 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00764714 | 48.2153 | 997.89 | 0.00 | 1075.74 | 1075.74 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2252.197 | -999.000 | 0.205205 | 0.00006441 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 2252.20 | 2208.49 | 0.205205 | 21.69 | 15.44 | 0.00858249 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00823207 | 18.16 | 0.0000 | 21.11 | 0.00858249 | 54.0325 | 2056.99 | 0.00 | 2295.06 | 2295.06 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 997.871 | 997.871 | 0.043837 | 0.00000873 | 28.514 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 997.87 | 997.87 | 0.043837 | 21.11 | 14.39 | 0.00764716 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00764716 | 48.2154 | 997.88 | 0.00 | 1075.74 | 1075.74 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11416.069 | -999.000 | 1.019634 | 0.00032649 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 11416.07 | 11003.80 | 1.019634 | 21.69 | 15.51 | 0.00865617 | 12.80 | 11.93 | 0.00850000 | 31.08 | 0.00823314 | 18.38 | 0.0000 | 21.11 | 0.00865617 | 54.4908 | 10220.60 | 0.00 | 11631.59 | 11631.59 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 4834.360 | 4834.360 | 0.212378 | 0.00004229 | 138.140 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4834.36 | 4834.36 | 0.212378 | 21.11 | 14.40 | 0.00766261 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00766261 | 48.3115 | 4834.41 | 0.00 | 5211.59 | 5211.59 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12811.710 | 12811.710 | 1.781282 | 0.00011208 | 272.661 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12811.71 | 12811.71 | 1.781282 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00774930 | 49.1852 | 3585.87 | 0.00 | 12883.21 | 12883.21 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12886.192 | 12886.192 | 1.781687 | 0.00011273 | 274.359 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 12886.19 | 12886.19 | 1.781687 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00775379 | 49.2135 | 3658.33 | 0.00 | 12958.10 | 12958.10 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 3620.007 | 3620.007 | 0.552022 | 0.00003167 | 76.544 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 3620.01 | 3620.01 | 0.552022 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00539254 | 34.3607 | 774.92 | 0.00 | 3640.25 | 3640.25 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 4848.022 | 4848.022 | 0.188519 | 0.00004241 | 128.098 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 4848.02 | 4848.02 | 0.188519 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00779318 | 49.4603 | 3871.55 | 0.00 | 4872.28 | 4872.28 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 426010.351 | -999.000 | 19.776073 | 0.01218384 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 426010.35 | 392747.03 | 19.776073 | 27.44 | 17.83 | 0.00904614 | 10.94 | 10.94 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 47.1742 | 23.99 | 0.00977390 | 51.5559 | 266895.33 | 0.00 | 432012.69 | 384031.68 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 90884.979 | 90884.979 | 5.932822 | 0.00079510 | 1628.964 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 90884.98 | 90884.98 | 5.932822 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.02 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 157.2473 | 21.15 | 0.00694989 | 43.7633 | 35013.25 | 0.00 | 92322.69 | 92322.69 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 47946.248 | -999.000 | 2.051317 | 0.00137126 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 47946.25 | 47946.25 | 2.051317 | 31.30 | 18.45 | 0.00823349 | 11.91 | 11.29 | 0.00823349 | 31.30 | 0.00823349 | 18.45 | 99.9965 | 21.11 | 0.00863797 | 54.3769 | 137246.92 | 0.00 | 48578.76 | 48578.76 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 9427.247 | 9427.247 | 0.615395 | 0.00008247 | 168.968 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9427.25 | 9427.25 | 0.615395 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.02 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 333.3216 | 21.11 | 0.00759546 | 47.8929 | 55471.80 | 0.00 | 9576.38 | 9576.38 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6637.126 | 6637.126 | 1.280849 | 0.00005806 | 138.406 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 2.6220 | 2.674739 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 6637.13 | 6637.13 | 1.0000 | 1.51368050 | 1.280849 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05805855 | 60.00 | 32.22 | 27.78 | 0.000 | 6637.13 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 6674.43 | 6674.43 | 1.51368050 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2134.877 | 2134.877 | 0.118903 | 0.00001868 | 51.149 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 0.8434 | 0.860348 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2134.88 | 2134.88 | 1.0000 | 0.14051665 | 0.118903 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01867493 | 60.00 | 32.22 | 27.78 | 0.000 | 2134.88 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00760494 | 21.00 | 0.00760494 | 48.2804 | 1519.23 | 0.00 | 2146.05 | 2146.05 | 0.14051665 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.58 | 18.56 | 0.00800000 | 52207.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1279.129 | 1279.129 | 0.137568 | 0.00001119 | 27.825 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 0.5053 | 0.515485 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1279.13 | 1279.13 | 1.0000 | 0.16257542 | 0.137568 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01118924 | 60.00 | 32.22 | 27.78 | 0.000 | 1279.13 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00759291 | 21.00 | 0.00759291 | 48.2045 | 566.82 | 0.00 | 1286.22 | 1286.22 | 0.16257542 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.36 | 16.08 | 0.00800000 | 44846.3 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1327.339 | 1327.339 | 0.047280 | 0.00001161 | 36.224 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 0.5244 | 0.534913 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1327.34 | 1327.34 | 1.0000 | 0.05587507 | 0.047280 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01161096 | 60.00 | 32.22 | 27.78 | 0.000 | 1327.34 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00751221 | 21.00 | 0.00751221 | 47.6982 | 1082.56 | 0.00 | 1333.92 | 1333.92 | 0.05587507 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1133.184 | 1133.184 | 0.086632 | 0.00000991 | 25.676 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 0.4477 | 0.456669 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1133.18 | 1133.18 | 1.0000 | 0.10238008 | 0.086632 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.00991258 | 60.00 | 32.22 | 27.78 | 0.000 | 1133.18 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00754849 | 21.00 | 0.00754849 | 47.9259 | 684.65 | 0.00 | 1139.29 | 1139.29 | 0.10238008 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.51 | 17.19 | 0.00800000 | 48062.8 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1740.536 | 1740.536 | 0.061999 | 0.00001523 | 47.501 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 0.6876 | 0.701430 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1740.54 | 1740.54 | 1.0000 | 0.07326878 | 0.061999 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01522541 | 60.00 | 32.22 | 27.78 | 0.000 | 1740.54 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00749587 | 21.00 | 0.00749587 | 47.5962 | 1419.58 | 0.00 | 1749.17 | 1749.17 | 0.07326878 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8987.915 | 8987.915 | 1.014551 | 0.00007863 | 194.615 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 3.5506 | 3.622099 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8987.91 | 8987.91 | 1.0000 | 1.19897442 | 1.014551 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07862218 | 60.00 | 32.22 | 27.78 | 0.000 | 8987.91 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00763985 | 21.00 | 0.00763985 | 48.4992 | 3734.41 | 0.00 | 9037.81 | 9037.81 | 1.19897442 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.99 | 15.95 | 0.00800000 | 44472.7 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24130.375 | 24130.375 | 2.840359 | 0.00021110 | 520.514 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 9.5326 | 9.724459 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 24130.37 | 24130.37 | 1.0000 | 3.35667564 | 2.840359 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.21108151 | 60.00 | 32.22 | 27.78 | 0.000 | 24130.37 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00759845 | 21.00 | 0.00759845 | 48.2392 | 9423.24 | 0.00 | 24264.48 | 24264.48 | 3.35667564 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.69 | 15.84 | 0.00800000 | 44163.5 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9036.433 | -999.000 | 0.823397 | 0.00025844 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7939 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.823397 | 0.97307326 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 1.4275 | 1.427516 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 9036.43 | 8861.61 | 1.0000 | 0.97307326 | 0.823397 | 21.69 | 15.44 | 0.00858224 | 43608.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.25840965 | 6.70 | 15.03 | 8.33 | 0.000 | 9036.43 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00858224 | 21.11 | 0.00858224 | 54.0309 | 8253.79 | 0.00 | 9208.42 | 9208.42 | 0.97307326 | 21.69 | 15.63 | 0.00858224 | 43608.7 | 12.42 | 12.03 | 0.00858224 | 34145.4 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3130.243 | 3130.243 | 0.137514 | 0.00002738 | 89.450 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.823397 | 0.97307326 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 1.2366 | 1.261477 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3130.24 | 3130.24 | 1.0000 | 0.16251159 | 0.137514 | 21.11 | 14.31 | 0.00756449 | 40428.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.02738193 | 60.00 | 32.22 | 27.78 | 0.000 | 3130.24 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00756449 | 21.11 | 0.00756449 | 47.7005 | 3130.28 | 0.00 | 3374.50 | 3374.50 | 0.16251159 | 16.60 | 12.73 | 0.00756449 | 35832.1 | 36.98 | 19.94 | 0.00756449 | 56596.8 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8700.013 | -999.000 | 0.792069 | 0.00024881 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7997 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.792069 | 0.93605016 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 1.3744 | 1.374371 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 8700.01 | 8525.46 | 1.0000 | 0.93605016 | 0.792069 | 21.69 | 15.45 | 0.00858535 | 43616.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.24878923 | 6.70 | 15.03 | 8.33 | 0.000 | 8700.01 | 30.41 | 0.00823207 | 18.16 | 0.00000000 | 0.0000 | 21.11 | 0.00858535 | 21.11 | 0.00858535 | 54.0503 | 7939.75 | 0.00 | 8865.48 | 8865.48 | 0.93605016 | 21.69 | 15.63 | 0.00858535 | 43616.6 | 12.42 | 12.03 | 0.00858535 | 34145.4 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3129.909 | 3129.909 | 0.137500 | 0.00002738 | 89.441 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.792069 | 0.93605016 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 1.2365 | 1.261343 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3129.91 | 3129.91 | 1.0000 | 0.16249425 | 0.137500 | 21.11 | 14.31 | 0.00756448 | 40428.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.02737901 | 60.00 | 32.22 | 27.78 | 0.000 | 3129.91 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00756448 | 21.11 | 0.00756448 | 47.7004 | 3129.95 | 0.00 | 3374.14 | 3374.14 | 0.16249425 | 16.60 | 12.73 | 0.00756448 | 35832.1 | 36.98 | 19.94 | 0.00756448 | 56596.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53401.005 | -999.000 | 4.977705 | 0.00152723 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6299 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.977705 | 5.88254562 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 8.4361 | 8.435940 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 53401.01 | 53401.01 | 1.0000 | 5.88254562 | 4.977705 | 21.69 | 15.37 | 0.00849397 | 43384.9 | 12.80 | 11.93 | 0.00849397 | 34307.0 | 1.52707767 | 6.70 | 15.03 | 8.33 | 0.000 | 53401.01 | 31.08 | 0.00823314 | 18.38 | 0.00000000 | 0.0000 | 21.11 | 0.00849397 | 21.11 | 0.00849397 | 53.4816 | 49899.06 | 0.00 | 54430.17 | 54430.17 | 5.88254562 | 21.69 | 15.55 | 0.00849397 | 43384.9 | 12.63 | 12.02 | 0.00849397 | 34132.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19054.098 | 19054.098 | 0.837072 | 0.00016669 | 544.485 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.977705 | 5.88254562 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 7.5272 | 7.678737 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19054.10 | 19054.10 | 1.0000 | 0.98923326 | 0.837072 | 21.11 | 14.34 | 0.00759494 | 40505.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.16667656 | 60.00 | 32.22 | 27.78 | 0.000 | 19054.10 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00759494 | 21.11 | 0.00759494 | 47.8896 | 18058.65 | 0.00 | 20540.95 | 20540.95 | 0.98923326 | 16.60 | 12.76 | 0.00759494 | 35909.2 | 36.98 | 19.97 | 0.00759494 | 56673.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 56024.255 | -999.000 | 4.838506 | 0.00160226 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1684 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.838506 | 5.71804307 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 8.8505 | 8.850344 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | unknown | unknown | unknown | 8/21 14:50:00 | Sensible | 56024.25 | 52454.74 | 1.0000 | 5.71804307 | 4.838506 | 21.69 | 15.62 | 0.00878364 | 44120.0 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 1.60209322 | 6.70 | 15.03 | 8.33 | 0.000 | 56024.25 | 31.30 | 0.00823349 | 18.45 | 0.00000000 | 0.0000 | 21.11 | 0.00878364 | 21.11 | 0.00878364 | 55.2823 | 48499.79 | 0.00 | 57072.48 | 55459.85 | 5.71804307 | 21.69 | 15.81 | 0.00878364 | 44120.0 | 12.20 | 12.02 | 0.00867189 | 34138.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19059.309 | 19059.309 | 0.837300 | 0.00016674 | 544.634 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.838506 | 5.71804307 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 7.5293 | 7.680837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19059.31 | 19059.31 | 1.0000 | 0.98950376 | 0.837300 | 21.11 | 14.34 | 0.00759491 | 40505.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.16672214 | 60.00 | 32.22 | 27.78 | 0.000 | 19059.31 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00759491 | 21.11 | 0.00759491 | 47.8894 | 18062.05 | 0.00 | 20546.57 | 20546.57 | 0.98950376 | 16.60 | 12.76 | 0.00759491 | 35909.1 | 36.98 | 19.97 | 0.00759491 | 56673.6 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8081.712 | -999.000 | 0.734486 | 0.00023113 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8117 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.734486 | 0.86799983 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 1.2767 | 1.276696 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | unknown | unknown | unknown | 8/21 09:30:00 | Sensible | 8081.71 | 7907.60 | 1.0000 | 0.86799983 | 0.734486 | 21.69 | 15.45 | 0.00859178 | 43632.9 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.23110806 | 6.70 | 15.03 | 8.33 | 0.000 | 8081.71 | 27.16 | 0.00822694 | 17.07 | 0.00000000 | 0.0000 | 21.11 | 0.00859178 | 21.11 | 0.00859178 | 54.0902 | 7362.54 | 0.00 | 8236.55 | 8236.55 | 0.86799983 | 21.69 | 15.64 | 0.00859178 | 43632.9 | 12.40 | 12.03 | 0.00859178 | 34143.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3130.469 | 3130.469 | 0.137524 | 0.00002739 | 89.457 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.734486 | 0.86799983 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 1.2367 | 1.261568 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3130.47 | 3130.47 | 1.0000 | 0.16252335 | 0.137524 | 21.11 | 14.31 | 0.00756452 | 40428.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.02738392 | 60.00 | 32.22 | 27.78 | 0.000 | 3130.47 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00756452 | 21.11 | 0.00756452 | 47.7006 | 3130.51 | 0.00 | 3374.74 | 3374.74 | 0.16252335 | 16.60 | 12.73 | 0.00756452 | 35832.2 | 36.98 | 19.94 | 0.00756452 | 56596.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7795.795 | -999.000 | 0.707860 | 0.00022295 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8179 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.707860 | 0.83653374 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 1.2316 | 1.231528 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | Sensible | 7795.79 | 7621.91 | 1.0000 | 0.83653374 | 0.707860 | 21.69 | 15.45 | 0.00859510 | 43641.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.22293184 | 6.70 | 15.03 | 8.33 | 0.000 | 7795.79 | 26.66 | 0.00822614 | 16.89 | 0.00000000 | 0.0000 | 21.11 | 0.00859510 | 21.11 | 0.00859510 | 54.1108 | 7095.63 | 0.00 | 7945.04 | 7945.04 | 0.83653374 | 21.69 | 15.64 | 0.00859510 | 43641.4 | 12.39 | 12.03 | 0.00859510 | 34143.8 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3130.135 | 3130.135 | 0.137510 | 0.00002738 | 89.447 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.707860 | 0.83653374 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 1.2365 | 1.261434 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3130.13 | 3130.13 | 1.0000 | 0.16250600 | 0.137510 | 21.11 | 14.31 | 0.00756451 | 40428.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.02738099 | 60.00 | 32.22 | 27.78 | 0.000 | 3130.13 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00756451 | 21.11 | 0.00756451 | 47.7006 | 3130.18 | 0.00 | 3374.38 | 3374.38 | 0.16250600 | 16.60 | 12.73 | 0.00756451 | 35832.2 | 36.98 | 19.94 | 0.00756451 | 56596.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8828.129 | 8828.129 | 0.712405 | 0.00007723 | 198.515 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 3.4875 | 3.557706 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8828.13 | 8828.13 | 1.0000 | 0.84190486 | 0.712405 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07722445 | 60.00 | 32.22 | 27.78 | 0.000 | 8828.13 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00766425 | 21.00 | 0.00766425 | 48.6517 | 5138.88 | 0.00 | 8875.86 | 8875.86 | 0.84190486 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.94 | 17.00 | 0.00800000 | 47477.3 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2344.906 | -999.000 | 0.213839 | 0.00006706 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7885 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.213839 | 0.25271080 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 0.3704 | 0.370433 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 2344.91 | 2301.13 | 1.0000 | 0.25271080 | 0.213839 | 21.69 | 15.44 | 0.00857929 | 43601.2 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.06705593 | 6.70 | 15.03 | 8.33 | 0.000 | 2344.91 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00857929 | 21.11 | 0.00857929 | 54.0127 | 2143.54 | 0.00 | 2389.57 | 2389.57 | 0.25271080 | 21.69 | 15.63 | 0.00857929 | 43601.2 | 12.43 | 12.03 | 0.00857929 | 34145.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 997.879 | 997.879 | 0.043838 | 0.00000873 | 28.514 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.213839 | 0.25271080 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 0.3942 | 0.402142 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 997.88 | 997.88 | 1.0000 | 0.05180648 | 0.043838 | 21.11 | 14.39 | 0.00764714 | 40638.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.00872899 | 60.00 | 32.22 | 27.78 | 0.000 | 997.88 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00764714 | 21.11 | 0.00764714 | 48.2153 | 997.89 | 0.00 | 1075.74 | 1075.74 | 0.05180648 | 16.60 | 12.81 | 0.00764714 | 36041.4 | 36.98 | 20.01 | 0.00764714 | 56806.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2252.197 | -999.000 | 0.205205 | 0.00006441 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7944 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.205205 | 0.24250716 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 0.3558 | 0.355787 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 2252.20 | 2208.49 | 1.0000 | 0.24250716 | 0.205205 | 21.69 | 15.44 | 0.00858249 | 43609.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.06440478 | 6.70 | 15.03 | 8.33 | 0.000 | 2252.20 | 30.41 | 0.00823207 | 18.16 | 0.00000000 | 0.0000 | 21.11 | 0.00858249 | 21.11 | 0.00858249 | 54.0325 | 2056.99 | 0.00 | 2295.06 | 2295.06 | 0.24250716 | 21.69 | 15.63 | 0.00858249 | 43609.3 | 12.42 | 12.03 | 0.00858249 | 34145.4 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 997.871 | 997.871 | 0.043837 | 0.00000873 | 28.514 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.205205 | 0.24250716 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 0.3942 | 0.402139 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 997.87 | 997.87 | 1.0000 | 0.05180609 | 0.043837 | 21.11 | 14.39 | 0.00764716 | 40638.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.00872892 | 60.00 | 32.22 | 27.78 | 0.000 | 997.87 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00764716 | 21.11 | 0.00764716 | 48.2154 | 997.88 | 0.00 | 1075.74 | 1075.74 | 0.05180609 | 16.60 | 12.81 | 0.00764716 | 36041.4 | 36.98 | 20.01 | 0.00764716 | 56806.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11416.069 | -999.000 | 1.019634 | 0.00032649 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9314 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.019634 | 1.20498160 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 1.8035 | 1.803436 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 11416.07 | 11003.80 | 1.0000 | 1.20498160 | 1.019634 | 21.69 | 15.51 | 0.00865617 | 43796.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.32645873 | 6.70 | 15.03 | 8.33 | 0.000 | 11416.07 | 31.08 | 0.00823314 | 18.38 | 0.00000000 | 0.0000 | 21.11 | 0.00865617 | 21.11 | 0.00865617 | 54.4908 | 10220.60 | 0.00 | 11631.59 | 11631.59 | 1.20498160 | 21.69 | 15.70 | 0.00865617 | 43796.3 | 12.24 | 12.02 | 0.00865617 | 34143.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4834.360 | 4834.360 | 0.212378 | 0.00004229 | 138.140 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.019634 | 1.20498160 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 1.9098 | 1.948231 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4834.36 | 4834.36 | 1.0000 | 0.25098434 | 0.212378 | 21.11 | 14.40 | 0.00766261 | 40677.3 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04228878 | 60.00 | 32.22 | 27.78 | 0.000 | 4834.36 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00766261 | 21.11 | 0.00766261 | 48.3115 | 4834.41 | 0.00 | 5211.59 | 5211.59 | 0.25098434 | 16.60 | 12.82 | 0.00766261 | 36080.5 | 36.98 | 20.02 | 0.00766261 | 56845.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12811.710 | 12811.710 | 1.781282 | 0.00011208 | 272.661 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 5.0612 | 5.163076 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12811.71 | 12811.71 | 1.0000 | 2.10508159 | 1.781282 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.11207099 | 60.00 | 32.22 | 27.78 | 0.000 | 12811.71 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00774930 | 21.00 | 0.00774930 | 49.1852 | 3585.87 | 0.00 | 12883.21 | 12883.21 | 2.10508159 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.60 | 15.45 | 0.00800000 | 43054.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12886.192 | 12886.192 | 1.781687 | 0.00011273 | 274.359 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 5.0906 | 5.193092 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 12886.19 | 12886.19 | 1.0000 | 2.10556019 | 1.781687 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.11272253 | 60.00 | 32.22 | 27.78 | 0.000 | 12886.19 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00775379 | 21.00 | 0.00775379 | 49.2135 | 3658.33 | 0.00 | 12958.10 | 12958.10 | 2.10556019 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.64 | 15.46 | 0.00800000 | 43089.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3620.007 | 3620.007 | 0.552022 | 0.00003167 | 76.544 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 1.4301 | 1.458850 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 3620.01 | 3620.01 | 1.0000 | 0.65236752 | 0.552022 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03166617 | 60.00 | 32.22 | 27.78 | 0.000 | 3620.01 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.50 | 0.00539254 | 21.00 | 0.00539254 | 34.3607 | 774.92 | 0.00 | 3640.25 | 3640.25 | 0.65236752 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.07 | 15.25 | 0.00800000 | 42514.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4848.022 | 4848.022 | 0.188519 | 0.00004241 | 128.098 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 1.9152 | 1.953736 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 4848.02 | 4848.02 | 1.0000 | 0.22278801 | 0.188519 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04240828 | 60.00 | 32.22 | 27.78 | 0.000 | 4848.02 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00779318 | 21.00 | 0.00779318 | 49.4603 | 3871.55 | 0.00 | 4872.28 | 4872.28 | 0.22278801 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 38.05 | 20.60 | 0.00800000 | 58804.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 426010.351 | -999.000 | 19.776073 | 0.01218384 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6563 | 1004.8586 | 1.1818 | VAV WITH REHEAT FAN | Fan:VariableVolume | 19.776073 | 23.37094078 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 67.2996 | 67.299574 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 426010.35 | 392747.03 | 1.0000 | 23.37094078 | 19.776073 | 27.44 | 17.83 | 0.00904614 | 50656.3 | 10.94 | 10.94 | 0.00850000 | 32428.1 | 12.18259924 | 6.70 | 15.03 | 8.33 | 44311.032 | 381699.32 | 31.30 | 0.00823349 | 18.45 | 9.32920000 | 47.1742 | 23.99 | 0.00977209 | 23.99 | 0.00977390 | 51.5559 | 266895.33 | 0.00 | 432012.69 | 384031.68 | 23.37094078 | 27.44 | 18.03 | 0.00904614 | 50656.3 | 11.35 | 11.22 | 0.00823211 | 32171.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 90884.979 | 90884.979 | 5.932822 | 0.00079510 | 1628.964 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV WITH REHEAT FAN | Fan:VariableVolume | 19.776073 | 23.37094078 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 35.9038 | 36.626339 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 90884.98 | 90884.98 | 1.0000 | 7.01128224 | 5.932822 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 0.79502033 | 60.00 | 32.22 | 27.78 | 0.000 | 90884.98 | 3.80 | 0.00505843 | 3.80 | 9.32920000 | 157.2473 | 18.39 | 0.00725183 | 21.15 | 0.00694989 | 43.7633 | 35013.25 | 0.00 | 92322.69 | 92322.69 | 7.01128224 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 15.78 | 9.78 | 0.00505843 | 28658.4 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 47946.248 | -999.000 | 2.051317 | 0.00137126 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1456 | 1004.8586 | 1.1818 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.42411771 | 4197.9300 | 999.8980 | 18.10204511 | 15.03 | 6.70 | 8.33 | 633006.01 | 7.5744 | 7.574375 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 47946.25 | 47946.25 | 1.0000 | 2.42420295 | 2.051317 | 31.30 | 18.45 | 0.00823349 | 52522.0 | 11.91 | 11.29 | 0.00823349 | 32743.9 | 1.37111674 | 6.70 | 15.03 | 8.33 | 2195.006 | 45751.24 | 31.30 | 0.00823349 | 18.45 | 2.05124512 | 99.9965 | 21.11 | 0.00863181 | 21.11 | 0.00863797 | 54.3769 | 137246.92 | 0.00 | 48578.76 | 48578.76 | 2.42420295 | 31.30 | 18.65 | 0.00823349 | 52522.0 | 11.66 | 11.35 | 0.00823349 | 32483.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9427.247 | 9427.247 | 0.615395 | 0.00008247 | 168.968 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.42411771 | 4197.9300 | 999.8980 | 2.17062460 | 54.44 | 82.22 | 27.78 | 253134.97 | 3.7242 | 3.799149 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9427.25 | 9427.25 | 1.0000 | 0.72726088 | 0.615395 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 0.08246526 | 60.00 | 32.22 | 27.78 | 0.000 | 9427.25 | 3.80 | 0.00505843 | 3.80 | 2.05124512 | 333.3216 | 21.11 | 0.00759580 | 21.11 | 0.00759546 | 47.8929 | 55471.80 | 0.00 | 9576.38 | 9576.38 | 0.72726088 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 15.78 | 9.78 | 0.00505843 | 28658.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 19.78 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 0.00 | 8759.17 | 0.00 |
RETAIL_1_FLR_1 | 1225.83 | 6358.50 | 12.83 |
RETAIL_2_FLR_1 | 92.83 | 8242.33 | 0.00 |
MECH_FLR_1 | 1171.33 | 4093.83 | 0.67 |
STORAGE_FLR_1 | 6.00 | 8760.00 | 6.00 |
LAUNDRY_FLR_1 | 8760.00 | 4400.00 | 4400.00 |
CAFE_FLR_1 | 728.00 | 8168.33 | 555.33 |
LOBBY_FLR_1 | 959.17 | 7849.17 | 773.17 |
ROOM_1_FLR_3 | 12.83 | 8419.17 | 12.83 |
ROOM_2_FLR_3 | 765.67 | 7870.33 | 266.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 113.33 | 8737.50 | 111.67 |
ROOM_5_FLR_3 | 19.50 | 8725.33 | 19.50 |
ROOM_6_FLR_3 | 443.00 | 8362.33 | 274.17 |
CORRIDOR_FLR_3 | 229.83 | 8760.00 | 229.83 |
ROOM_1_FLR_6 | 153.17 | 8204.67 | 152.33 |
ROOM_2_FLR_6 | 1161.83 | 7692.00 | 589.50 |
ROOM_3_MULT9_FLR_6 | 9.50 | 8358.17 | 9.50 |
BANQUET_FLR_6 | 1398.50 | 7108.83 | 750.00 |
DINING_FLR_6 | 2282.83 | 5601.17 | 761.00 |
KITCHEN_FLR_6 | 8760.00 | 6498.33 | 6498.33 |
CORRIDOR_FLR_6 | 1991.83 | 5884.33 | 303.67 |
Facility | 8760.00 | 8760.00 | 7279.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_2_FLR_3 | 0.00 | 9.50 | 0.00 | 9.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 23.17 | 0.00 | 23.17 |
ROOM_5_FLR_3 | 0.00 | 2.00 | 0.00 | 2.00 |
ROOM_6_FLR_3 | 0.00 | 27.17 | 0.00 | 27.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 8.33 | 0.00 | 8.33 |
ROOM_2_FLR_6 | 0.00 | 19.00 | 0.00 | 19.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 9.33 | 0.00 | 9.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 62.33 | 0.00 | 62.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 0.862 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.519 | 0.136 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.453 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.104 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.747 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.653 | 0.146 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 4.401 | 0.106 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.01 | 422.44 | 5183.56 | 1.784 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.342 | 0.176 | 0.000 | 0.094 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.343 | 0.176 | 0.000 | 0.099 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.389 | 0.078 | 0.000 | 0.157 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.342 | 0.176 | 0.000 | 0.094 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.343 | 0.176 | 0.000 | 0.102 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.487 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.343 | 0.176 | 0.000 | 0.105 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.343 | 0.176 | 0.000 | 0.102 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.389 | 0.143 | 0.000 | 0.167 |
BANQUET_FLR_6 | 144.94 | 249.90 | 1010.89 | 5.731 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.94 | 249.90 | 1010.89 | 5.748 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 19.061 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.507 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 0.552 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.941 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.940 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.007 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.478 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 6.529 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 2.828 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.01 | 422.44 | 5183.56 | 1.153 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.312 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.94 | 249.90 | 1010.89 | 3.705 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.94 | 249.90 | 1010.89 | 3.709 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 6.018 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.316 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.77 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.041 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.047 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.53 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.173 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.01 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.94 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.94 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.97 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 136.998 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 35765745.84 | 0.00 | 35765745.84 | 0.00 | 35765745.84 | 26946214.98 | 1501.88 | 58.37 | 7199.76 | 0.00 |
RETAIL_1_FLR_1 | 3466489.33 | 0.00 | 3466489.33 | 310101.36 | 3776590.69 | 1981818.02 | 67.92 | 204.58 | 8487.50 | 0.00 |
RETAIL_2_FLR_1 | 3841476.74 | 0.00 | 3841476.74 | 119699.52 | 3961176.26 | 2294951.32 | 76.58 | 218.42 | 8465.00 | 0.00 |
MECH_FLR_1 | 575189.46 | 0.00 | 575189.46 | 282898.54 | 858088.01 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2419070.52 | 0.00 | 2419070.52 | 163216.88 | 2582287.39 | 1821682.01 | 1499.63 | 59.12 | 7201.26 | 0.00 |
LAUNDRY_FLR_1 | 49350363.95 | 0.00 | 49350363.95 | 386283.51 | 49736647.46 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 28329765.98 | 0.00 | 28329765.98 | 685496.60 | 29015262.59 | 14544917.54 | 29.25 | 24.33 | 8706.42 | 0.00 |
LOBBY_FLR_1 | 79322402.06 | 0.00 | 79322402.06 | 1958620.37 | 81281022.43 | 59728886.00 | 1499.96 | 58.79 | 7201.26 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 96045.26 | 1502122.10 | 179991.83 | 1682113.93 | 1946875.62 | 2433.33 | 5215.00 | 1111.67 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 100822.94 | 1506735.03 | 179978.09 | 1686713.13 | 1946647.51 | 2433.33 | 5250.46 | 1076.21 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 50219.74 | 1150131.71 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 100981.69 | 19171335.82 | 50233.47 | 19221569.29 | 26405105.73 | 2433.33 | 5225.92 | 1100.74 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 96190.60 | 1502267.43 | 179991.83 | 1682259.26 | 1946875.62 | 2433.33 | 5214.83 | 1111.83 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 104078.43 | 1509990.52 | 179978.09 | 1689968.62 | 1946647.51 | 2433.33 | 5214.83 | 1111.83 | 0.00 |
CORRIDOR_FLR_3 | 19892807.77 | 0.00 | 19892807.77 | 217646.33 | 20110454.11 | 14972100.18 | 1498.54 | 58.95 | 7202.51 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 107838.57 | 459357.78 | 180028.86 | 639386.63 | 486718.90 | 2033.22 | 5226.34 | 1500.44 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 103358.32 | 454836.35 | 180015.12 | 634851.47 | 486661.88 | 2086.98 | 5333.93 | 1339.09 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 107683.24 | 2366014.65 | 92109.06 | 2458123.72 | 3126920.42 | 2433.33 | 5214.83 | 1111.83 | 0.00 |
BANQUET_FLR_6 | 49746147.58 | 0.00 | 49746147.58 | 439585.22 | 50185732.80 | 37458366.31 | 1499.96 | 58.79 | 7201.26 | 0.00 |
DINING_FLR_6 | 49841914.55 | 0.00 | 49841914.55 | 439585.22 | 50281499.78 | 37458366.31 | 1498.54 | 59.62 | 7201.84 | 0.00 |
KITCHEN_FLR_6 | 51253540.38 | 0.00 | 51253540.38 | 393530.69 | 51647071.07 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 5449313.08 | 0.00 | 5449313.08 | 385165.88 | 5834478.96 | 3961413.96 | 1041.79 | 72.50 | 7645.71 | 0.00 |
Total Facility | 0.20E+10 | 10443503.24 | 0.20E+10 | 18137997.94 | 0.20E+10 | 0.43E+10 | 8760.00 | 5733.88 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1341 | 0.0000 | 1.1341 | 0.0000 | 1.1341 | 0.8545 | 1501.88 | 58.37 | 7199.76 |
RETAIL_1_FLR_1 | 0.1099 | 0.0000 | 0.1099 | 0.0098 | 0.1198 | 0.0628 | 67.92 | 204.58 | 8487.50 |
RETAIL_2_FLR_1 | 0.1218 | 0.0000 | 0.1218 | 0.0038 | 0.1256 | 0.0728 | 76.58 | 218.42 | 8465.00 |
MECH_FLR_1 | 0.0182 | 0.0000 | 0.0182 | 0.0090 | 0.0272 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0767 | 0.0000 | 0.0767 | 0.0052 | 0.0819 | 0.0578 | 1499.63 | 59.12 | 7201.26 |
LAUNDRY_FLR_1 | 1.5649 | 0.0000 | 1.5649 | 0.0122 | 1.5771 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8983 | 0.0000 | 0.8983 | 0.0217 | 0.9201 | 0.4612 | 29.25 | 24.33 | 8706.42 |
LOBBY_FLR_1 | 2.5153 | 0.0000 | 2.5153 | 0.0621 | 2.5774 | 1.8940 | 1499.96 | 58.79 | 7201.26 |
ROOM_1_FLR_3 | 0.0446 | 0.0030 | 0.0476 | 0.0057 | 0.0533 | 0.0617 | 2433.33 | 5215.00 | 1111.67 |
ROOM_2_FLR_3 | 0.0446 | 0.0032 | 0.0478 | 0.0057 | 0.0535 | 0.0617 | 2433.33 | 5250.46 | 1076.21 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0032 | 0.6079 | 0.0016 | 0.6095 | 0.8373 | 2433.33 | 5225.92 | 1100.74 |
ROOM_5_FLR_3 | 0.0446 | 0.0031 | 0.0476 | 0.0057 | 0.0533 | 0.0617 | 2433.33 | 5214.83 | 1111.83 |
ROOM_6_FLR_3 | 0.0446 | 0.0033 | 0.0479 | 0.0057 | 0.0536 | 0.0617 | 2433.33 | 5214.83 | 1111.83 |
CORRIDOR_FLR_3 | 0.6308 | 0.0000 | 0.6308 | 0.0069 | 0.6377 | 0.4748 | 1498.54 | 58.95 | 7202.51 |
ROOM_1_FLR_6 | 0.0111 | 0.0034 | 0.0146 | 0.0057 | 0.0203 | 0.0154 | 2033.22 | 5226.34 | 1500.44 |
ROOM_2_FLR_6 | 0.0111 | 0.0033 | 0.0144 | 0.0057 | 0.0201 | 0.0154 | 2086.98 | 5333.93 | 1339.09 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0034 | 0.0750 | 0.0029 | 0.0779 | 0.0992 | 2433.33 | 5214.83 | 1111.83 |
BANQUET_FLR_6 | 1.5774 | 0.0000 | 1.5774 | 0.0139 | 1.5914 | 1.1878 | 1499.96 | 58.79 | 7201.26 |
DINING_FLR_6 | 1.5805 | 0.0000 | 1.5805 | 0.0139 | 1.5944 | 1.1878 | 1498.54 | 59.62 | 7201.84 |
KITCHEN_FLR_6 | 1.6252 | 0.0000 | 1.6252 | 0.0125 | 1.6377 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.1728 | 0.0000 | 0.1728 | 0.0122 | 0.1850 | 0.1256 | 1041.79 | 72.50 | 7645.71 |
Total Facility | 61.2571 | 0.3312 | 61.5882 | 0.4541 | 62.0424 | 73.7164 | 8760.00 | 5733.88 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.53E+09 | 0.00 | 0.53E+09 | 0.21E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 40160055.99 | 816999.05 | 40977055.04 | 64690340.46 | 8758.83 | 1.17 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 16.7956 | 0.0000 | 16.7956 | 6.7464 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2735 | 0.0259 | 1.2994 | 2.0513 | 8758.83 | 1.17 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 45.26 | 8025.46 | 0.00 | 0.00 | 0.00 | 689.28 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 13.1015 | 17.2890 | 0.0000 | 0.0000 | 0.0000 | 11.3153 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6673 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1341 |
Defaulted Fields | 1182 |
Fields with Defaults | 3973 |
Autosized Fields | 347 |
Autosizable Fields | 400 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4304.42 | 59038.06 | 13-MAY-05:00 | 285493.07 | 29-SEP-19:10 |
Electricity:Building | 2129.48 | 28219.80 | 03-JUN-05:00 | 125573.39 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 241.08 | 2918.13 | 02-JAN-02:10 | 17644.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2122.38 | 28078.66 | 03-JUN-05:00 | 125332.06 | 02-JAN-20:10 |
InteriorLights:Electricity | 473.93 | 4184.99 | 03-JUN-05:00 | 39200.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 97.97 | 890.23 | 02-JAN-02:10 | 8012.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 473.93 | 4184.99 | 03-JUN-05:00 | 39200.55 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 473.93 | 4184.99 | 03-JUN-05:00 | 39200.55 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 97.97 | 890.23 | 02-JAN-02:10 | 8012.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 473.93 | 4184.99 | 03-JUN-05:00 | 39200.55 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 14.62 | 184.63 | 02-JAN-02:10 | 1048.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 4.43 | 40.29 | 02-JAN-02:10 | 362.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 4.43 | 40.29 | 02-JAN-02:10 | 362.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 16.93 | 213.80 | 02-JAN-02:10 | 1213.81 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 5.13 | 46.65 | 02-JAN-02:10 | 419.88 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 5.13 | 46.65 | 02-JAN-02:10 | 419.88 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 21.66 | 260.20 | 02-JAN-02:10 | 1590.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 9.19 | 83.47 | 02-JAN-02:10 | 751.24 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 9.19 | 83.47 | 02-JAN-02:10 | 751.24 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.70 | 70.12 | 02-JAN-02:10 | 414.36 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.11 | 19.14 | 02-JAN-02:10 | 172.20 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.11 | 19.14 | 02-JAN-02:10 | 172.20 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.85 | 998.31 | 02-JAN-02:10 | 4893.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.92 | 35.61 | 02-JAN-02:10 | 320.50 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.92 | 35.61 | 02-JAN-02:10 | 320.50 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 21.47 | 268.98 | 03-JUN-05:00 | 1823.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 7.13 | 41.98 | 01-JAN-13:10 | 858.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 7.13 | 41.98 | 01-JAN-13:10 | 858.63 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 232.46 | 2883.45 | 03-JUN-05:00 | 17252.86 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 83.46 | 772.03 | 03-JUN-05:00 | 7223.65 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 83.46 | 772.03 | 03-JUN-05:00 | 7223.65 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 57.85 | 525.62 | 02-JAN-02:10 | 4730.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 57.85 | 525.62 | 02-JAN-02:10 | 4730.55 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 57.85 | 525.62 | 02-JAN-02:10 | 4730.55 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 191.39 | 2367.92 | 03-JUN-05:00 | 8255.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 15.53 | 118.62 | 03-JUN-05:00 | 1507.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 15.53 | 118.62 | 03-JUN-05:00 | 1507.83 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 191.39 | 2367.92 | 03-JUN-05:00 | 8255.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 15.53 | 118.62 | 03-JUN-05:00 | 1507.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 15.53 | 118.62 | 03-JUN-05:00 | 1507.83 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 440.79 | 5911.62 | 02-JAN-02:10 | 18536.47 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 9.68 | 87.99 | 02-JAN-02:10 | 791.95 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 9.68 | 87.99 | 02-JAN-02:10 | 791.95 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.31 | 139.07 | 02-JAN-02:10 | 1251.64 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.31 | 139.07 | 02-JAN-02:10 | 1251.64 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.31 | 139.07 | 02-JAN-02:10 | 1251.64 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.27 | 732.85 | 27-NOV-23:30 | 2789.97 | 01-OCT-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1030.94 | 2310.62 | 02-MAR-04:00 | 134608.04 | 16-OCT-10:50 |
LowTempRefrigeration:Refrigeration:Electricity | 15.87 | 0.00 | 01-JAN-11:10 | 1306.49 | 14-APR-03:10 |
MedTempRefrigeration:Refrigeration:Electricity | 21.31 | 636.00 | 29-NOV-03:10 | 716.46 | 11-FEB-14:10 |
Fans:Electricity | 602.94 | 13404.16 | 11-MAR-03:50 | 31634.78 | 16-OCT-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityProduced:Facility | 231.56 | -0.00 | 27-FEB-06:30 | 34554.33 | 27-MAY-11:40 |
ElectricityProduced:Plant | 231.56 | -0.00 | 27-FEB-06:30 | 34554.33 | 27-MAY-11:40 |
Photovoltaic:ElectricityProduced | 241.61 | 0.00 | 01-JAN-00:10 | 36235.99 | 27-MAY-11:50 |
PowerConversion:ElectricityProduced | -10.05 | -1681.65 | 27-MAY-11:50 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 624.42 | 13783.10 | 11-MAR-03:50 | 32453.59 | 16-OCT-22:00 |
ExteriorEquipment:Electricity | 390.57 | 5778.01 | 02-JAN-02:20 | 23859.27 | 03-NOV-06:20 |
Transformer:ExteriorEquipment:Electricity | 21.48 | 378.92 | 03-JUN-05:00 | 1270.98 | 03-NOV-06:20 |
ElectricityPurchased:Facility | 4072.86 | 57238.52 | 28-MAR-13:30 | 285493.07 | 29-SEP-19:10 |
ElectricityPurchased:Plant | 4072.86 | 57238.52 | 28-MAR-13:30 | 285493.07 | 29-SEP-19:10 |
Cogeneration:ElectricityPurchased | 4072.86 | 57238.52 | 28-MAR-13:30 | 285493.07 | 29-SEP-19:10 |
General:Cogeneration:ElectricityPurchased | 4072.86 | 57238.52 | 28-MAR-13:30 | 285493.07 | 29-SEP-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4072.86 | 57238.52 | 28-MAR-13:30 | 285493.07 | 29-SEP-19:10 |
ElectricityNet:Plant | 4072.86 | 57238.52 | 28-MAR-13:30 | 285493.07 | 29-SEP-19:10 |
Cogeneration:ElectricityNet | 4072.86 | 57238.52 | 28-MAR-13:30 | 285493.07 | 29-SEP-19:10 |
General:Cogeneration:ElectricityNet | 4072.86 | 57238.52 | 28-MAR-13:30 | 285493.07 | 29-SEP-19:10 |
General:Fans:Electricity | 602.94 | 13404.16 | 11-MAR-03:50 | 31634.78 | 16-OCT-22:00 |
ExteriorLights:Electricity | 150.49 | 0.00 | 01-JAN-07:00 | 9571.94 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 150.49 | 0.00 | 01-JAN-07:00 | 9571.94 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 366.65 | 5383.28 | 01-JAN-00:10 | 22430.31 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.45 | 15.80 | 01-JAN-00:10 | 157.97 | 01-JAN-07:10 |
WaterSystems:Electricity | 90.74 | 1086.56 | 20-SEP-02:30 | 4738.75 | 19-JAN-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 20-SEP-02:30 | 4738.75 | 19-JAN-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 835.70 | 0.00 | 01-JAN-00:50 | 126718.75 | 16-OCT-12:10 |
General:Cooling:Electricity | 835.70 | 0.00 | 01-JAN-00:50 | 126718.75 | 16-OCT-12:10 |
Pumps:Electricity | 67.32 | 47.91 | 14-MAY-07:00 | 3528.86 | 17-OCT-10:50 |
General:Pumps:Electricity | 67.32 | 47.91 | 14-MAY-07:00 | 3528.86 | 17-OCT-10:50 |
WIRED_LTG_ELECTRICITY | 16.68 | 0.00 | 01-JAN-00:10 | 1379.86 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4435.04 | 26805.16 | 26-APR-01:10 | 326273.47 | 06-JAN-23:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2646.20 | 13443.27 | 07-AUG-09:00 | 283524.90 | 29-MAR-22:50 |
WaterSystems:NaturalGas | 2482.18 | 13443.27 | 18-MAY-09:00 | 208320.59 | 13-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2482.18 | 13443.27 | 18-MAY-09:00 | 208320.59 | 13-FEB-21:20 |
Heating:NaturalGas | 164.02 | 0.00 | 06-JAN-15:10 | 140553.10 | 09-JAN-06:00 |
Boiler:Heating:NaturalGas | 164.02 | 0.00 | 06-JAN-15:10 | 140553.10 | 09-JAN-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2822.88 | 0.00 | 01-JAN-00:30 | 451957.63 | 17-AUG-15:30 |
PlantLoopCoolingDemand:HVAC | 2822.88 | 0.00 | 01-JAN-00:30 | 451957.63 | 17-AUG-15:30 |
CoolingCoils:PlantLoopCoolingDemand | 2822.88 | 0.00 | 01-JAN-00:30 | 451957.63 | 17-AUG-15:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 15343.66 | 123716.94 | 28-MAR-14:00 | 1738078.77 | 17-AUG-15:30 |
EnergyTransfer:Building | 4939.99 | 93830.22 | 29-MAR-10:30 | 291485.80 | 16-OCT-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 707.33 | 10377.76 | 30-MAR-03:00 | 33945.27 | 30-SEP-10:50 |
Refrigeration:EnergyTransfer | 186.80 | 4017.01 | 03-FEB-23:20 | 10366.15 | 08-SEP-06:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.40 | 2008.51 | 03-FEB-23:20 | 5183.07 | 08-SEP-06:40 |
General:Refrigeration:EnergyTransfer | 93.40 | 2008.51 | 03-FEB-23:20 | 5183.07 | 08-SEP-06:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.40 | 2008.51 | 03-FEB-23:20 | 5183.07 | 08-SEP-06:40 |
EnergyTransfer:Plant | 7475.07 | 18877.83 | 14-MAR-14:40 | 1035273.15 | 17-AUG-15:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.69 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.71 | 1996.28 | 29-NOV-03:10 | 2557.90 | 11-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 351.53 | 9020.84 | 05-JUN-13:20 | 14899.36 | 15-OCT-10:40 |
Heating:EnergyTransfer | 3.75 | 0.00 | 01-JAN-08:00 | 9585.56 | 25-FEB-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 3.75 | 0.00 | 01-JAN-08:00 | 9585.56 | 25-FEB-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4842.85 | 91372.40 | 29-MAR-12:00 | 287928.18 | 16-OCT-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 351.53 | 9020.84 | 05-JUN-13:20 | 14899.36 | 15-OCT-10:40 |
General:Cooling:EnergyTransfer | 4842.85 | 91372.40 | 29-MAR-12:00 | 287928.18 | 16-OCT-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 351.53 | 9020.84 | 05-JUN-13:20 | 14899.36 | 15-OCT-10:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.56 | 77.40 | 30-MAR-06:10 | 3404.38 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.56 | 77.40 | 30-MAR-06:10 | 3404.38 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.56 | 77.40 | 30-MAR-06:10 | 3404.38 | 16-OCT-12:20 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.58 | 615.66 | 29-MAR-12:10 | 1616.62 | 30-SEP-10:40 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.58 | 615.66 | 29-MAR-12:10 | 1616.62 | 30-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.58 | 615.66 | 29-MAR-12:10 | 1616.62 | 30-SEP-10:40 |
EnergyTransfer:Zone:MECH_FLR_1 | 6.66 | 16.76 | 30-MAR-04:10 | 1315.62 | 16-OCT-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 6.66 | 16.76 | 30-MAR-04:10 | 1315.62 | 16-OCT-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 6.66 | 16.76 | 30-MAR-04:10 | 1315.62 | 16-OCT-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 19.94 | 134.84 | 29-MAR-12:00 | 962.37 | 30-SEP-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.94 | 134.84 | 29-MAR-12:00 | 962.37 | 30-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.94 | 134.84 | 29-MAR-12:00 | 962.37 | 30-SEP-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.39 | 8596.81 | 30-MAR-04:00 | 38719.38 | 29-SEP-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.39 | 8596.81 | 30-MAR-04:00 | 38719.38 | 29-SEP-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.39 | 8596.81 | 30-MAR-04:00 | 38719.38 | 29-SEP-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 256.70 | 2691.65 | 29-MAR-12:10 | 12546.38 | 15-OCT-10:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 256.70 | 2691.65 | 29-MAR-12:10 | 12546.38 | 15-OCT-10:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 256.70 | 2691.65 | 29-MAR-12:10 | 12546.38 | 15-OCT-10:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 808.52 | 16239.36 | 29-MAR-12:10 | 34240.03 | 15-OCT-10:40 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 808.52 | 16239.36 | 29-MAR-12:10 | 34240.03 | 15-OCT-10:40 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 808.52 | 16239.36 | 29-MAR-12:10 | 34240.03 | 15-OCT-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 47.61 | 0.00 | 01-JAN-08:00 | 8346.20 | 31-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.36 | 0.00 | 01-JAN-07:50 | 1199.20 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.36 | 0.00 | 01-JAN-07:50 | 1199.20 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 47.25 | 0.00 | 01-JAN-00:10 | 8346.20 | 31-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 47.25 | 0.00 | 01-JAN-00:10 | 8346.20 | 31-OCT-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 29.84 | 0.00 | 01-JAN-08:00 | 8138.53 | 17-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.70 | 0.00 | 01-JAN-08:00 | 1418.12 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.70 | 0.00 | 01-JAN-08:00 | 1418.12 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 29.14 | 0.00 | 01-JAN-00:10 | 8138.53 | 17-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 29.14 | 0.00 | 01-JAN-00:10 | 8138.53 | 17-AUG-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 292.89 | 0.00 | 01-JAN-00:10 | 40592.38 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 292.89 | 0.00 | 01-JAN-00:10 | 40592.38 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 292.89 | 0.00 | 01-JAN-00:10 | 40592.38 | 16-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 342.47 | 0.00 | 01-JAN-08:00 | 57026.49 | 14-OCT-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.26 | 0.00 | 01-JAN-00:10 | 5337.84 | 25-FEB-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.26 | 0.00 | 01-JAN-00:10 | 5337.84 | 25-FEB-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 342.21 | 0.00 | 01-JAN-08:00 | 57026.49 | 14-OCT-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 342.21 | 0.00 | 01-JAN-08:00 | 57026.49 | 14-OCT-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 44.11 | 0.00 | 01-JAN-08:00 | 8293.71 | 15-OCT-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.38 | 0.00 | 01-JAN-07:10 | 1329.27 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.38 | 0.00 | 01-JAN-07:10 | 1329.27 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 43.73 | 0.00 | 01-JAN-00:10 | 8293.71 | 15-OCT-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 43.73 | 0.00 | 01-JAN-00:10 | 8293.71 | 15-OCT-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 28.41 | 0.00 | 01-JAN-08:00 | 8647.56 | 17-OCT-08:40 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.81 | 0.00 | 01-JAN-07:20 | 1410.60 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.81 | 0.00 | 01-JAN-07:20 | 1410.60 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.59 | 0.00 | 01-JAN-00:10 | 8647.56 | 17-OCT-08:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.59 | 0.00 | 01-JAN-00:10 | 8647.56 | 17-OCT-08:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 185.98 | 2426.53 | 29-MAR-12:10 | 8450.15 | 30-SEP-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 185.98 | 2426.53 | 29-MAR-12:10 | 8450.15 | 30-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 185.98 | 2426.53 | 29-MAR-12:10 | 8450.15 | 30-SEP-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.46 | 0.00 | 01-JAN-08:00 | 2242.19 | 30-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.35 | 0.00 | 01-JAN-08:00 | 538.85 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.35 | 0.00 | 01-JAN-08:00 | 538.85 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.11 | 0.00 | 01-JAN-00:10 | 2242.19 | 30-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.11 | 0.00 | 01-JAN-00:10 | 2242.19 | 30-SEP-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.52 | 0.00 | 01-JAN-08:00 | 2223.30 | 17-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.66 | 0.00 | 01-JAN-08:00 | 571.72 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.66 | 0.00 | 01-JAN-08:00 | 571.72 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.86 | 0.00 | 01-JAN-00:10 | 2223.30 | 17-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.86 | 0.00 | 01-JAN-00:10 | 2223.30 | 17-AUG-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.47 | 0.00 | 01-JAN-08:00 | 12011.91 | 26-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.23 | 0.00 | 01-JAN-00:10 | 1645.18 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.23 | 0.00 | 01-JAN-00:10 | 1645.18 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.24 | 0.00 | 01-JAN-02:30 | 12011.91 | 26-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.24 | 0.00 | 01-JAN-02:30 | 12011.91 | 26-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 489.18 | 10842.38 | 29-MAR-12:30 | 19411.50 | 19-JUL-18:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 489.18 | 10842.38 | 29-MAR-12:30 | 19411.50 | 19-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 489.18 | 10842.38 | 29-MAR-12:30 | 19411.50 | 19-JUL-18:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 509.41 | 11939.52 | 29-MAR-11:00 | 20351.52 | 29-SEP-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 509.41 | 11939.52 | 29-MAR-11:00 | 20351.52 | 29-SEP-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 509.41 | 11939.52 | 29-MAR-11:00 | 20351.52 | 29-SEP-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 613.93 | 8043.01 | 30-MAR-03:00 | 28927.80 | 30-SEP-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 613.93 | 8043.01 | 30-MAR-03:00 | 28927.80 | 30-SEP-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 60.44 | 1236.82 | 03-JAN-07:20 | 5052.68 | 30-SEP-13:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 60.44 | 1236.82 | 03-JAN-07:20 | 5052.68 | 30-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 60.44 | 1236.82 | 03-JAN-07:20 | 5052.68 | 30-SEP-13:30 |
PlantLoopHeatingDemand:Facility | 787.65 | 8695.82 | 04-AUG-02:40 | 135085.84 | 08-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 681.94 | 8695.82 | 04-AUG-02:40 | 47502.56 | 03-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 681.94 | 8695.82 | 04-AUG-02:40 | 47502.56 | 03-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 681.94 | 8695.82 | 04-AUG-02:40 | 47502.56 | 03-FEB-07:10 |
EnergyTransfer:HVAC | 2928.59 | 0.00 | 14-MAY-07:00 | 451957.63 | 17-AUG-15:30 |
HeatingCoils:EnergyTransfer | 105.71 | 0.00 | 06-JAN-15:10 | 105687.77 | 08-JAN-06:50 |
PlantLoopHeatingDemand:HVAC | 105.71 | 0.00 | 06-JAN-15:10 | 105687.77 | 08-JAN-06:50 |
HeatingCoils:PlantLoopHeatingDemand | 105.71 | 0.00 | 06-JAN-15:10 | 105687.77 | 08-JAN-06:50 |
CoolingCoils:EnergyTransfer | 2822.88 | 0.00 | 01-JAN-00:30 | 451957.63 | 17-AUG-15:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 681.94 | 8695.82 | 04-AUG-02:40 | 47502.56 | 03-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 681.94 | 8695.82 | 04-AUG-02:40 | 47502.56 | 03-FEB-07:10 |
Boilers:EnergyTransfer | 104.68 | 0.00 | 06-JAN-15:10 | 105027.53 | 08-JAN-06:50 |
Chillers:EnergyTransfer | 2879.67 | 0.00 | 01-JAN-00:50 | 452985.57 | 17-AUG-15:30 |
HeatRejection:EnergyTransfer | 3715.38 | 0.00 | 01-JAN-00:50 | 565784.93 | 17-AUG-15:30 |
General:HeatRejection:EnergyTransfer | 3715.38 | 0.00 | 01-JAN-00:50 | 565784.93 | 17-AUG-15:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -351.526 | 0.000 | 0.000 | 146.759 | 97.975 | 143.105 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -36.313 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -35.562 | 0.000 | 0.000 | 14.867 | 4.434 | 10.186 | 17.962 | 0.000 | 0.034 | 0.000 | 0.000 | -5.118 | 0.000 | -2.553 | -4.250 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -37.577 | 0.000 | 0.000 | 17.245 | 5.134 | 11.795 | 0.000 | 0.000 | 0.027 | 4.332 | 0.000 | 0.000 | 0.000 | -0.956 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -6.657 | 0.000 | 0.000 | 3.362 | 9.186 | 12.471 | 0.000 | 0.000 | 0.027 | 0.000 | 0.000 | 0.000 | 0.000 | -2.725 | -15.665 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -19.944 | 0.000 | 0.000 | 2.977 | 2.106 | 3.598 | 0.000 | 0.000 | 0.049 | 12.344 | 0.000 | 0.000 | 0.000 | -1.129 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -589.393 | 0.000 | 0.000 | 10.551 | 3.919 | 658.131 | 0.000 | 0.000 | 0.036 | 0.000 | 0.000 | 0.000 | 0.000 | -3.792 | -79.452 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -256.700 | 0.000 | 0.000 | 200.475 | 7.131 | 14.341 | 51.550 | 0.000 | 0.199 | 1.356 | 0.000 | -13.191 | 0.000 | -5.160 | -0.001 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -808.522 | 0.000 | 0.000 | 568.536 | 83.459 | 148.998 | 67.047 | 0.000 | 0.442 | 0.000 | 0.000 | -18.989 | 0.000 | -16.336 | -24.636 |
ROOM_1_FLR_3 | 1.283 | -37.196 | 0.000 | -10.982 | 0.000 | 0.000 | 9.637 | 4.922 | 10.478 | 37.851 | 0.000 | 0.167 | 1.373 | 0.000 | -10.670 | 0.000 | -6.863 | -0.000 |
ROOM_2_FLR_3 | 2.281 | -18.928 | 0.000 | -11.787 | 0.000 | 0.000 | 9.444 | 4.922 | 10.477 | 27.466 | 0.000 | 0.129 | 0.000 | 0.000 | -11.023 | 0.000 | -7.978 | -5.002 |
ROOM_3_MULT19_FLR_3 | 0.000 | -276.241 | 0.000 | -16.646 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 198.706 | 0.000 | 0.142 | 0.005 | 0.000 | -88.870 | 0.000 | -49.482 | -21.382 |
ROOM_4_MULT19_FLR_3 | 3.463 | -190.671 | 0.000 | -154.733 | 0.000 | 0.000 | 181.546 | 58.793 | 195.050 | 63.027 | 0.000 | 0.849 | 0.000 | 0.000 | -57.425 | 0.000 | -67.945 | -31.954 |
ROOM_5_FLR_3 | 1.415 | -33.771 | 0.000 | -10.986 | 0.000 | 0.000 | 9.631 | 4.922 | 10.478 | 35.311 | 0.000 | 0.165 | 0.156 | 0.000 | -10.434 | 0.000 | -6.889 | -0.001 |
ROOM_6_FLR_3 | 2.479 | -17.617 | 0.000 | -11.640 | 0.000 | 0.000 | 9.498 | 4.922 | 10.477 | 24.842 | 0.000 | 0.123 | 0.000 | 0.000 | -10.538 | 0.000 | -7.766 | -4.779 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -185.977 | 0.000 | 0.000 | 118.197 | 57.846 | 0.000 | 32.038 | 0.000 | 0.183 | 0.000 | 0.000 | -13.614 | 0.000 | -6.649 | -2.024 |
ROOM_1_FLR_6 | 0.833 | -8.855 | 0.000 | -2.747 | 0.000 | 0.000 | 2.411 | 1.231 | 2.620 | 9.403 | 0.000 | 0.041 | 0.000 | 0.000 | -2.621 | 0.000 | -1.769 | -0.546 |
ROOM_2_FLR_6 | 1.325 | -4.568 | 0.000 | -2.962 | 0.000 | 0.000 | 2.357 | 1.230 | 2.619 | 6.811 | 0.000 | 0.031 | 0.000 | 0.000 | -2.721 | 0.000 | -2.033 | -2.091 |
ROOM_3_MULT9_FLR_6 | 1.020 | -60.365 | 0.000 | -17.664 | 0.000 | 0.000 | 21.667 | 6.962 | 23.098 | 47.142 | 0.000 | 0.230 | 0.268 | 0.000 | -12.130 | 0.000 | -10.227 | -0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -489.176 | 0.000 | 0.000 | 340.187 | 15.534 | 175.857 | 7.474 | 0.000 | 0.116 | 0.000 | 0.000 | -6.656 | 0.000 | -3.601 | -39.736 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -509.407 | 0.000 | 0.000 | 334.883 | 15.534 | 175.857 | 7.235 | 0.000 | 0.101 | 0.000 | 0.000 | -6.990 | 0.000 | -3.734 | -13.479 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -613.925 | 0.000 | 0.000 | 27.948 | 9.684 | 540.650 | 21.660 | 0.000 | 0.036 | 21.460 | 0.000 | -3.606 | 0.000 | -3.907 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -60.440 | 0.000 | 0.000 | 29.322 | 15.305 | 0.000 | 15.113 | 0.000 | 0.037 | 10.864 | 0.000 | -6.732 | 0.000 | -3.470 | -0.000 |
Total Facility | 14.098 | -648.212 | 0.000 | -4204.953 | 0.000 | 0.000 | 2061.499 | 473.928 | 2355.282 | 670.640 | 0.000 | 3.164 | 52.160 | 0.000 | -281.328 | 0.000 | -214.964 | -281.310 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-OCT-10:35 | 0.00 | 0.00 | 0.00 | -14949.33 | 0.00 | 0.00 | 2415.24 | 2670.70 | 4055.80 | 0.00 | 0.00 | 0.00 | 5807.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 | -3404.40 | 0.00 | 0.00 | 150.60 | 100.72 | 252.59 | 3750.64 | 0.00 | 126.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -976.21 |
RETAIL_2_FLR_1 | 16-OCT-18:10 | 0.00 | 0.00 | 0.00 | -1631.04 | 0.00 | 0.00 | 648.05 | 373.23 | 752.15 | 0.00 | 0.00 | 2.37 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -144.76 |
MECH_FLR_1 | 16-OCT-20:00 | 0.00 | 0.00 | 0.00 | -1315.58 | 0.00 | 0.00 | 129.08 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -31.85 | -372.34 |
STORAGE_FLR_1 | 30-SEP-10:35 | 0.00 | 0.00 | 0.00 | -965.24 | 0.00 | 0.00 | 47.53 | 47.83 | 89.22 | 0.00 | 0.00 | 49.78 | 730.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 29-SEP-20:00 | 0.00 | 0.00 | 0.00 | -38718.46 | 0.00 | 0.00 | 408.87 | 320.50 | 44299.38 | 0.00 | 0.00 | 14.22 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6324.51 |
CAFE_FLR_1 | 15-OCT-10:35 | 0.00 | 0.00 | 0.00 | -12668.88 | 0.00 | 0.00 | 3074.13 | 62.97 | 406.43 | 10373.59 | 0.00 | 208.61 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1456.83 |
LOBBY_FLR_1 | 15-OCT-10:35 | 0.00 | 0.00 | 0.00 | -34450.33 | 0.00 | 0.00 | 9345.46 | 2070.78 | 4222.82 | 13621.44 | 0.00 | 617.15 | 4572.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 14-OCT-08:61 | 0.00 | -10667.07 | 0.00 | -736.20 | 0.00 | 0.00 | 130.71 | 212.17 | 653.23 | 1954.63 | 0.00 | 128.89 | 8323.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 14-OCT-08:61 | 0.00 | -10571.02 | 0.00 | -771.21 | 0.00 | 0.00 | 126.46 | 212.14 | 653.15 | 990.83 | 0.00 | 116.38 | 9243.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 16-OCT-12:30 | 0.00 | -40592.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 43649.06 | 0.00 | 1139.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7815.33 |
ROOM_4_MULT19_FLR_3 | 14-OCT-08:61 | 0.00 | -66582.59 | 0.00 | -10564.61 | 0.00 | 0.00 | 2424.63 | 2534.11 | 12159.85 | 5363.52 | 0.00 | 599.57 | 54065.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-OCT-08:61 | 0.00 | -9660.52 | 0.00 | -747.51 | 0.00 | 0.00 | 130.71 | 212.17 | 653.23 | 5646.27 | 0.00 | 124.82 | 3640.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 17-OCT-08:21 | 0.00 | -10644.09 | 0.00 | -916.32 | 0.00 | 0.00 | 73.38 | 166.68 | 452.99 | 5366.41 | 0.00 | 60.36 | 5440.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 30-SEP-10:35 | 0.00 | 0.00 | 0.00 | -8463.10 | 0.00 | 0.00 | 1889.33 | 1314.04 | 0.00 | 5080.89 | 0.00 | 245.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -66.31 |
ROOM_1_FLR_6 | 13-OCT-15:11 | 0.00 | -2771.18 | 0.00 | -184.30 | 0.00 | 0.00 | 58.82 | 26.52 | 50.05 | 1290.29 | 0.00 | 29.64 | 1500.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 14-OCT-08:61 | 0.00 | -2674.74 | 0.00 | -186.09 | 0.00 | 0.00 | 32.37 | 53.04 | 163.29 | 252.90 | 0.00 | 31.11 | 2328.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14-OCT-08:61 | 0.00 | -13412.18 | 0.00 | -1193.79 | 0.00 | 0.00 | 294.10 | 300.09 | 1439.98 | 4303.78 | 0.00 | 143.60 | 8124.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 19-JUL-18:10 | 0.00 | 0.00 | 0.00 | -19745.07 | 0.00 | 0.00 | 13697.14 | 865.58 | 6747.90 | 718.18 | 0.00 | 0.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2283.81 |
DINING_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -20827.82 | 0.00 | 0.00 | 15960.27 | 1005.22 | 6747.90 | 0.00 | 0.00 | 8.04 | 0.00 | 0.00 | -51.40 | 0.00 | 0.00 | -2842.21 |
KITCHEN_FLR_6 | 30-SEP-10:50 | 0.00 | 0.00 | 0.00 | -28937.64 | 0.00 | 0.00 | 464.23 | 219.99 | 23951.61 | 2191.89 | 0.00 | 95.37 | 2014.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 30-SEP-13:30 | 0.00 | 0.00 | 0.00 | -5052.58 | 0.00 | 0.00 | 462.69 | 347.68 | 0.00 | 2298.84 | 0.00 | 109.46 | 1833.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-18:02 | 0.00 | -115270.58 | 0.00 | -188246.20 | 0.00 | 0.00 | 79838.37 | 34857.49 | 120174.13 | 296.53 | 0.00 | 1240.98 | 72232.86 | 0.00 | -4701.51 | 0.00 | -422.07 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 19-DEC-19:04 | 3540.42 | 409.35 | 0.00 | -409.35 | 0.00 | 0.00 | 335.52 | 337.19 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -830.06 | 0.00 | -196.91 | -3670.81 |
ROOM_2_FLR_3 | 04-JAN-19:03 | 3437.90 | 412.41 | 0.00 | -412.41 | 0.00 | 0.00 | 361.37 | 337.15 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -728.18 | 0.00 | -216.89 | -3675.95 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 06-FEB-09:04 | 17628.79 | 5546.13 | 0.00 | -5546.13 | 0.00 | 0.00 | 1774.38 | 1991.09 | 8433.45 | 965.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -992.93 | -29800.01 |
ROOM_5_FLR_3 | 03-JAN-16:14 | 3396.37 | 413.34 | 0.00 | -413.34 | 0.00 | 0.00 | 240.58 | 106.08 | 200.18 | 328.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -629.12 | -3642.23 |
ROOM_6_FLR_3 | 06-APR-18:04 | 3282.37 | 415.82 | 0.00 | -415.82 | 0.00 | 0.00 | 347.79 | 337.15 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.88 | 0.00 | -226.29 | -3459.73 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 09-JAN-16:14 | 1062.46 | 103.36 | 0.00 | -103.36 | 0.00 | 0.00 | 58.82 | 26.52 | 50.05 | 261.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -42.90 | -1416.57 |
ROOM_2_FLR_6 | 22-JAN-16:14 | 1042.26 | 104.50 | 0.00 | -104.50 | 0.00 | 0.00 | 33.18 | 31.25 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18.37 | 0.00 | -47.69 | -1095.94 |
ROOM_3_MULT9_FLR_6 | 12-MAY-15:14 | 4975.65 | 674.64 | 0.00 | -674.64 | 0.00 | 0.00 | 588.92 | 150.05 | 441.28 | 547.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3223.05 | -3480.70 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-MAR-15:15 | -90570.27 | 126670.40 | 0.00 | -126670.40 | 0.00 | 0.00 | 59069.63 | 10112.12 | 73604.29 | 26545.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6030.03 | -72731.06 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 19.8782 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 19.7761 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.9083 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5298 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.003540 | 10.8290 | 0.000610 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.003540 | 12.5400 | 0.000610 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.003540 | 142.3000 | 0.000914 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.000958 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0692 | 2.0692 | 1.2808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2772 | 0.2772 | 0.1189 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2050 | 0.2050 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2033 | 0.2033 | 0.0020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0940 | 0.0940 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2990 | 3.2990 | 0.0330 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3007 | 1.3007 | 1.0146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.3631 | 4.3631 | 2.8404 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0761 | 1.0761 | 0.7124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0593 | 2.0593 | 1.7813 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1649 | 2.1649 | 1.7817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1563 | 2.1563 | 0.5520 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6101 | 0.6101 | 0.1885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 19.8782 | 19.7761 | 19.8782 | 10.5298 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2808 | 1.2808 | 1.2808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1386 | 0.1386 | 0.1189 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1376 | 0.1376 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1016 | 0.1016 | 0.0020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6495 | 1.6495 | 0.0330 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0146 | 1.0146 | 1.0146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8404 | 2.8404 | 2.8404 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7124 | 0.7124 | 0.7124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7813 | 1.7813 | 1.7813 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7817 | 1.7817 | 1.7817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0782 | 1.0782 | 0.5520 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3050 | 0.3050 | 0.1885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.9083 | 10.5298 | 10.5298 | 10.5298 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 62.33 |
Number of hours not met | 62.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 164.02 | 140553.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 835.70 | 126718.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 473.93 | 39200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 150.49 | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.48 | 1270.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 366.65 | 22430.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.45 | 157.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 602.94 | 31634.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 67.32 | 3528.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.75 | 2482.18 | 208320.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.87 | 1306.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.31 | 716.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.73 | 4304.42 |
Natural Gas | 1788.84 | 4435.04 |
Additional | 0.00 | 0.00 |
Total | 3481.56 | 8739.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 241.61 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 41.77 |
Space Heating | 0.00 |
Space Cooling | 73.66 |
Fans (All) | 53.14 |
Service Water Heating | 8.00 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 379.40 |
Subtotal | 379.40 |
Natural Gas [MJ/m2] | |
Space Heating | 14.46 |
Service Water Heating | 218.79 |
Miscellaneous (All) | 390.91 |
Subtotal | 390.91 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.42 |
Space Heating | 1.88 |
Space Cooling | 9.56 |
Fans (All) | 6.90 |
Service Water Heating | 29.44 |
Receptacle Equipment | 39.33 |
Miscellaneous | 7.47 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_KITCHEN | 2142. | 8760. |
LTG_SCH_DINING | 1989. | 8760. |
LTG_SCH_BASEMENT | 2219. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1635. | 8760. |
LTG_SCH_MECHANIC | 2142. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2433. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6989.33 | 1770.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8684.67 | 75.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6989.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1770.67 | 0.00 | 0.00 | 0.00 |
Average | 8675.23 | 84.77 | 0.00 | 0.00 | 0.00 |
Sum | 190855.17 | 1864.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4153.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4142.67 | 11.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 11.33 | 0.00 | 0.00 | 0.00 |
Average | 288886.52 | 0.52 | 0.00 | 0.00 | 0.00 |
Sum | 6355503.50 | 11.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8392.67 | 367.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8542.67 | 217.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 5912.00 | 2848.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8640.17 | 119.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8391.67 | 368.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8603.17 | 156.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8332.67 | 427.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8581.50 | 178.50 | 0.00 | 0.00 | 0.00 |
Min | 5912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2848.00 | 0.00 | 0.00 | 0.00 |
Average | 8544.84 | 215.16 | 0.00 | 0.00 | 0.00 |
Sum | 187986.50 | 4733.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1976317.67 | 139111.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4063.00 | 91.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4153.17 | 0.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4145.33 | 8.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 3982.50 | 171.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1210630.17 | 35084.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1150417.33 | 95297.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107924.83 | 344.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 102638.67 | 3307.33 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1976317.67 | 139111.33 | 0.00 | 0.00 | 0.00 |
Average | 276458.98 | 12428.06 | 0.00 | 0.00 | 0.00 |
Sum | 6082097.67 | 273417.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311882E+11 | 13975.35 | 22-JAN-11:35 | 16.67 | 11.79 | 0.744461E+10 | 4601.59 | 13-JAN-23:10 | 16.67 | 11.79 |
February | 0.259349E+11 | 13598.79 | 01-FEB-19:10 | 13.00 | 12.44 | 0.634526E+10 | 4511.38 | 01-FEB-23:10 | 13.00 | 11.39 |
March | 0.279826E+11 | 12991.18 | 12-MAR-10:35 | 21.33 | 14.69 | 0.690417E+10 | 4256.34 | 01-MAR-23:10 | 21.33 | 14.69 |
April | 0.271325E+11 | 13095.04 | 30-APR-10:35 | 25.67 | 16.97 | 0.659778E+10 | 4222.38 | 14-APR-22:10 | 25.67 | 16.97 |
May | 0.279911E+11 | 12973.41 | 04-MAY-18:10 | 18.83 | 14.89 | 0.682136E+10 | 4223.23 | 26-MAY-22:10 | 11.00 | 8.46 |
June | 0.269954E+11 | 12996.09 | 25-JUN-10:35 | 23.00 | 17.26 | 0.655009E+10 | 4181.26 | 01-JUN-22:10 | 23.00 | 17.26 |
July | 0.296650E+11 | 13798.19 | 23-JUL-10:35 | 25.67 | 20.39 | 0.698489E+10 | 4345.18 | 28-JUL-22:10 | 18.00 | 17.35 |
August | 0.301211E+11 | 13802.30 | 19-AUG-10:35 | 24.67 | 20.11 | 0.709338E+10 | 4370.53 | 11-AUG-22:10 | 24.67 | 20.11 |
September | 0.300863E+11 | 14530.60 | 30-SEP-10:35 | 30.57 | 17.23 | 0.706247E+10 | 4520.63 | 28-SEP-22:10 | 30.57 | 17.23 |
October | 0.322069E+11 | 14950.15 | 15-OCT-10:35 | 31.67 | 16.43 | 0.751165E+10 | 4662.59 | 20-OCT-22:10 | 16.00 | 13.03 |
November | 0.309542E+11 | 14447.12 | 19-NOV-11:35 | 26.00 | 15.32 | 0.732200E+10 | 4682.24 | 30-NOV-23:10 | 11.03 | 5.21 |
December | 0.312674E+11 | 13857.84 | 07-DEC-19:10 | 14.83 | 13.74 | 0.746467E+10 | 4660.12 | 01-DEC-23:10 | 14.83 | 13.74 |
Annual Sum or Average | 0.351525E+12 | 0.841023E+11 | ||||||||
Minimum of Months | 0.259349E+11 | 12973.41 | 13.00 | 11.79 | 0.634526E+10 | 4181.26 | 11.00 | 5.21 | ||
Maximum of Months | 0.322069E+11 | 14950.15 | 31.67 | 20.39 | 0.751165E+10 | 4682.24 | 30.57 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303822E+10 | 2750.20 | 14-JAN-12:40 | 25.33 | 11.70 | 0.713480E+09 | 468.18 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.251393E+10 | 2440.55 | 02-FEB-12:40 | 19.33 | 12.36 | 0.632102E+09 | 468.30 | 01-FEB-22:30 | 19.33 | 12.36 |
March | 0.253272E+10 | 2146.42 | 11-MAR-13:00 | 24.00 | 13.82 | 0.684593E+09 | 466.42 | 23-MAR-21:30 | 13.50 | 12.93 |
April | 0.271053E+10 | 1555.26 | 08-APR-13:00 | 22.00 | 16.42 | 0.692530E+09 | 471.49 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.265312E+10 | 1433.75 | 04-MAY-10:35 | 22.00 | 15.73 | 0.695670E+09 | 473.20 | 04-MAY-21:40 | 17.00 | 15.07 |
June | 0.273255E+10 | 1393.94 | 29-JUN-18:10 | 21.50 | 18.39 | 0.700986E+09 | 470.16 | 28-JUN-21:49 | 21.50 | 18.39 |
July | 0.305513E+10 | 1512.22 | 30-JUL-10:35 | 24.67 | 20.10 | 0.757779E+09 | 488.00 | 31-JUL-21:40 | 18.80 | 17.92 |
August | 0.322023E+10 | 1669.96 | 20-AUG-12:00 | 25.00 | 19.59 | 0.782415E+09 | 491.84 | 17-AUG-22:10 | 25.00 | 19.59 |
September | 0.318520E+10 | 2938.87 | 30-SEP-12:00 | 32.00 | 17.11 | 0.745223E+09 | 491.83 | 29-SEP-21:19 | 32.00 | 17.11 |
October | 0.359172E+10 | 3404.38 | 16-OCT-12:20 | 35.37 | 17.35 | 0.772366E+09 | 491.84 | 18-OCT-21:30 | 14.50 | 14.21 |
November | 0.309727E+10 | 3029.30 | 19-NOV-12:30 | 26.50 | 15.22 | 0.707231E+09 | 472.04 | 27-NOV-22:30 | 16.00 | 5.61 |
December | 0.323088E+10 | 2900.27 | 19-DEC-12:50 | 25.83 | 11.54 | 0.723380E+09 | 485.95 | 05-DEC-22:40 | 25.83 | 11.54 |
Annual Sum or Average | 0.355615E+11 | 0.860776E+10 | ||||||||
Minimum of Months | 0.251393E+10 | 1393.94 | 19.33 | 11.54 | 0.632102E+09 | 466.42 | 13.50 | 5.61 | ||
Maximum of Months | 0.359172E+10 | 3404.38 | 35.37 | 20.10 | 0.782415E+09 | 491.84 | 32.00 | 19.59 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303920E+10 | 1422.75 | 18-JAN-19:10 | 18.83 | 14.20 | 0.821721E+09 | 534.22 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.270851E+10 | 1426.18 | 03-FEB-21:00 | 13.00 | 7.33 | 0.738127E+09 | 538.30 | 03-FEB-23:10 | 11.67 | 3.87 |
March | 0.294683E+10 | 1448.06 | 23-MAR-18:10 | 16.50 | 14.36 | 0.810235E+09 | 537.52 | 24-MAR-22:10 | 13.00 | 11.29 |
April | 0.304090E+10 | 1498.06 | 26-APR-18:10 | 18.67 | 15.37 | 0.807023E+09 | 546.21 | 27-APR-22:10 | 14.00 | 12.84 |
May | 0.311219E+10 | 1498.41 | 04-MAY-18:10 | 18.83 | 14.89 | 0.830187E+09 | 547.02 | 03-MAY-22:10 | 18.83 | 14.89 |
June | 0.313734E+10 | 1526.20 | 29-JUN-18:10 | 21.50 | 18.39 | 0.823103E+09 | 551.32 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.339805E+10 | 1566.69 | 19-JUL-18:10 | 22.67 | 18.90 | 0.869714E+09 | 558.47 | 31-JUL-22:10 | 18.65 | 17.88 |
August | 0.344581E+10 | 1569.53 | 17-AUG-18:10 | 20.77 | 18.28 | 0.882661E+09 | 564.10 | 18-AUG-22:10 | 19.00 | 17.66 |
September | 0.325394E+10 | 1624.79 | 30-SEP-10:35 | 30.57 | 17.23 | 0.842098E+09 | 569.51 | 29-SEP-21:49 | 30.57 | 17.23 |
October | 0.336382E+10 | 1630.94 | 16-OCT-18:10 | 23.83 | 14.43 | 0.871576E+09 | 569.55 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.304126E+10 | 1490.81 | 19-NOV-11:35 | 26.00 | 15.32 | 0.811514E+09 | 539.60 | 01-NOV-22:10 | 26.00 | 15.32 |
December | 0.308956E+10 | 1445.77 | 05-DEC-21:00 | 16.00 | 9.09 | 0.830678E+09 | 545.08 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.375774E+11 | 0.993864E+10 | ||||||||
Minimum of Months | 0.270851E+10 | 1422.75 | 13.00 | 7.33 | 0.738127E+09 | 534.22 | 11.67 | 3.87 | ||
Maximum of Months | 0.344581E+10 | 1630.94 | 30.57 | 18.90 | 0.882661E+09 | 569.55 | 30.57 | 17.88 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200559E+09 | 742.97 | 18-JAN-22:00 | 17.00 | 13.48 | 0.198095E+09 | 120.45 | 25-JAN-22:30 | 14.00 | 14.00 |
February | 0.142065E+09 | 613.89 | 03-FEB-21:00 | 13.00 | 7.33 | 0.179845E+09 | 120.45 | 09-FEB-22:19 | 9.97 | 9.97 |
March | 0.133582E+09 | 576.82 | 24-MAR-21:00 | 13.00 | 11.87 | 0.197886E+09 | 120.45 | 24-MAR-01:10 | 13.00 | 11.87 |
April | 0.303254E+09 | 766.93 | 26-APR-21:00 | 16.00 | 15.39 | 0.196275E+09 | 120.45 | 26-APR-21:30 | 16.00 | 15.39 |
May | 0.425453E+09 | 900.50 | 04-MAY-21:00 | 17.00 | 15.07 | 0.204495E+09 | 120.45 | 24-MAY-21:40 | 16.00 | 14.13 |
June | 0.789762E+09 | 993.20 | 30-JUN-21:00 | 16.00 | 14.76 | 0.199165E+09 | 120.45 | 26-JUN-21:30 | 16.00 | 14.76 |
July | 0.116183E+10 | 1109.04 | 19-JUL-21:00 | 18.00 | 18.00 | 0.205008E+09 | 120.45 | 12-JUL-21:40 | 18.00 | 18.00 |
August | 0.114059E+10 | 1090.05 | 18-AUG-21:00 | 19.00 | 17.66 | 0.205875E+09 | 120.45 | 29-AUG-22:30 | 17.65 | 15.80 |
September | 0.866094E+09 | 1249.36 | 29-SEP-21:00 | 24.60 | 13.50 | 0.198646E+09 | 120.45 | 20-SEP-21:40 | 24.60 | 13.50 |
October | 0.992311E+09 | 1315.62 | 16-OCT-20:00 | 21.00 | 13.07 | 0.205066E+09 | 120.45 | 31-OCT-21:10 | 16.88 | 14.87 |
November | 0.283783E+09 | 692.52 | 01-NOV-20:00 | 15.00 | 11.57 | 0.196184E+09 | 120.45 | 24-NOV-22:10 | 12.17 | 9.86 |
December | 0.217691E+09 | 748.15 | 05-DEC-22:00 | 17.00 | 9.46 | 0.200290E+09 | 120.45 | 20-DEC-22:10 | 9.00 | 9.00 |
Annual Sum or Average | 0.665697E+10 | 0.238683E+10 | ||||||||
Minimum of Months | 0.133582E+09 | 576.82 | 13.00 | 7.33 | 0.179845E+09 | 120.45 | 9.00 | 9.00 | ||
Maximum of Months | 0.116183E+10 | 1315.62 | 24.60 | 18.00 | 0.205875E+09 | 120.45 | 24.60 | 18.00 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148768E+10 | 816.48 | 20-JAN-11:35 | 21.67 | 15.71 | 0.118879E+09 | 74.87 | 18-JAN-23:10 | 21.67 | 15.71 |
February | 0.134959E+10 | 791.43 | 01-FEB-11:35 | 25.00 | 14.29 | 0.106864E+09 | 73.41 | 03-FEB-23:10 | 11.67 | 3.87 |
March | 0.140905E+10 | 804.52 | 19-MAR-10:35 | 19.33 | 15.06 | 0.118319E+09 | 73.14 | 24-MAR-22:10 | 13.00 | 11.29 |
April | 0.160747E+10 | 849.94 | 30-APR-10:35 | 25.67 | 16.97 | 0.116341E+09 | 74.97 | 26-APR-22:10 | 25.67 | 16.97 |
May | 0.171210E+10 | 856.02 | 04-MAY-10:35 | 22.00 | 15.73 | 0.121623E+09 | 76.48 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.176047E+10 | 888.14 | 25-JUN-10:35 | 23.00 | 17.26 | 0.121583E+09 | 77.51 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.190431E+10 | 922.93 | 23-JUL-10:35 | 25.67 | 20.39 | 0.128110E+09 | 78.75 | 19-JUL-22:10 | 25.67 | 20.39 |
August | 0.190235E+10 | 917.76 | 19-AUG-10:35 | 24.67 | 20.11 | 0.128555E+09 | 78.77 | 18-AUG-22:10 | 24.67 | 20.11 |
September | 0.177733E+10 | 965.25 | 30-SEP-10:35 | 30.57 | 17.23 | 0.122124E+09 | 80.32 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.185243E+10 | 954.92 | 15-OCT-10:35 | 31.67 | 16.43 | 0.127195E+09 | 81.13 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.160982E+10 | 847.19 | 19-NOV-11:35 | 26.00 | 15.32 | 0.116403E+09 | 74.65 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.157183E+10 | 822.50 | 19-DEC-11:35 | 25.00 | 11.16 | 0.119200E+09 | 75.28 | 05-DEC-23:10 | 25.00 | 11.16 |
Annual Sum or Average | 0.199444E+11 | 0.144520E+10 | ||||||||
Minimum of Months | 0.134959E+10 | 791.43 | 19.33 | 11.16 | 0.106864E+09 | 73.14 | 11.67 | 3.87 | ||
Maximum of Months | 0.190431E+10 | 965.25 | 31.67 | 20.39 | 0.128555E+09 | 81.13 | 30.57 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492229E+11 | 37781.99 | 24-JAN-21:00 | 17.00 | 11.91 | 0.649328E+09 | 381.55 | 04-JAN-23:49 | 17.00 | 11.91 |
February | 0.443278E+11 | 37652.00 | 03-FEB-21:00 | 13.00 | 7.33 | 0.587066E+09 | 381.56 | 24-FEB-00:10 | 13.00 | 11.87 |
March | 0.491860E+11 | 37889.22 | 23-MAR-20:00 | 14.00 | 13.42 | 0.652384E+09 | 381.57 | 10-MAR-22:10 | 14.00 | 13.42 |
April | 0.482916E+11 | 38173.57 | 26-APR-20:00 | 17.00 | 15.07 | 0.629494E+09 | 381.58 | 26-APR-21:19 | 16.00 | 15.39 |
May | 0.500352E+11 | 38181.86 | 04-MAY-20:00 | 17.00 | 15.07 | 0.650704E+09 | 381.56 | 15-MAY-21:10 | 13.83 | 12.68 |
June | 0.490313E+11 | 38202.80 | 30-JUN-20:00 | 16.00 | 15.39 | 0.630867E+09 | 381.58 | 26-JUN-21:19 | 16.00 | 15.39 |
July | 0.510764E+11 | 38446.26 | 19-JUL-20:00 | 19.00 | 18.34 | 0.649332E+09 | 381.58 | 17-JUL-21:19 | 19.00 | 18.34 |
August | 0.513523E+11 | 38408.97 | 18-AUG-20:00 | 19.00 | 17.66 | 0.652079E+09 | 381.58 | 03-AUG-21:19 | 19.00 | 17.66 |
September | 0.489678E+11 | 38719.38 | 29-SEP-20:00 | 25.00 | 13.58 | 0.629189E+09 | 381.58 | 13-SEP-21:19 | 25.00 | 13.58 |
October | 0.506582E+11 | 38627.98 | 16-OCT-20:00 | 21.00 | 13.07 | 0.649635E+09 | 381.63 | 17-OCT-21:10 | 18.00 | 14.87 |
November | 0.480136E+11 | 37658.51 | 28-NOV-21:00 | 13.00 | 6.31 | 0.628117E+09 | 381.59 | 28-NOV-22:00 | 9.00 | 4.95 |
December | 0.492294E+11 | 37898.69 | 05-DEC-21:00 | 16.00 | 9.09 | 0.649327E+09 | 381.71 | 01-DEC-01:10 | 16.00 | 9.09 |
Annual Sum or Average | 0.589393E+12 | 0.765752E+10 | ||||||||
Minimum of Months | 0.443278E+11 | 37652.00 | 13.00 | 6.31 | 0.587066E+09 | 381.55 | 9.00 | 4.95 | ||
Maximum of Months | 0.513523E+11 | 38719.38 | 25.00 | 18.34 | 0.652384E+09 | 381.71 | 25.00 | 18.34 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220957E+11 | 11903.69 | 14-JAN-11:35 | 26.00 | 11.75 | 0.920115E+10 | 5950.77 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.190045E+11 | 11169.05 | 04-FEB-11:35 | 20.67 | 8.25 | 0.820515E+10 | 5928.21 | 01-FEB-22:40 | 20.67 | 8.25 |
March | 0.202796E+11 | 11298.53 | 11-MAR-11:35 | 24.00 | 13.82 | 0.897321E+10 | 5852.60 | 23-MAR-21:40 | 13.33 | 12.77 |
April | 0.205309E+11 | 10172.57 | 08-APR-10:35 | 21.67 | 16.37 | 0.872287E+10 | 5840.98 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.202563E+11 | 9707.00 | 04-MAY-18:10 | 18.83 | 14.89 | 0.891548E+10 | 5872.16 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.202269E+11 | 9720.71 | 29-JUN-18:10 | 21.50 | 18.39 | 0.875444E+10 | 5822.59 | 27-JUN-22:10 | 21.50 | 18.39 |
July | 0.219138E+11 | 10138.32 | 30-JUL-10:35 | 24.67 | 20.10 | 0.912105E+10 | 5892.53 | 31-JUL-22:10 | 18.65 | 17.88 |
August | 0.227014E+11 | 10483.31 | 27-AUG-10:35 | 23.33 | 18.72 | 0.931123E+10 | 5949.04 | 18-AUG-22:10 | 23.33 | 18.72 |
September | 0.220071E+11 | 12022.67 | 30-SEP-10:35 | 30.57 | 17.23 | 0.903032E+10 | 6287.11 | 29-SEP-21:40 | 30.57 | 17.23 |
October | 0.234126E+11 | 12668.43 | 15-OCT-10:35 | 31.67 | 16.43 | 0.949074E+10 | 6315.27 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.217469E+11 | 12492.00 | 19-NOV-11:35 | 26.00 | 15.32 | 0.897607E+10 | 6013.94 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.225234E+11 | 11818.23 | 30-DEC-11:35 | 21.33 | 11.09 | 0.929196E+10 | 6092.57 | 05-DEC-23:10 | 21.33 | 11.09 |
Annual Sum or Average | 0.256699E+12 | 0.107994E+12 | ||||||||
Minimum of Months | 0.190045E+11 | 9707.00 | 18.83 | 8.25 | 0.820515E+10 | 5822.59 | 13.33 | 8.25 | ||
Maximum of Months | 0.234126E+11 | 12668.43 | 31.67 | 20.10 | 0.949074E+10 | 6315.27 | 30.57 | 18.72 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.672634E+11 | 31090.03 | 22-JAN-11:35 | 16.67 | 11.79 | 0.292143E+11 | 18975.03 | 20-JAN-23:10 | 16.67 | 11.79 |
February | 0.597395E+11 | 30355.51 | 04-FEB-11:35 | 20.67 | 8.25 | 0.261899E+11 | 18949.90 | 03-FEB-23:10 | 20.67 | 8.25 |
March | 0.650863E+11 | 30540.28 | 11-MAR-11:35 | 24.00 | 13.82 | 0.287655E+11 | 18761.19 | 24-MAR-22:10 | 13.00 | 11.29 |
April | 0.652016E+11 | 30667.85 | 26-APR-18:10 | 18.67 | 15.37 | 0.281329E+11 | 18824.38 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.668186E+11 | 30936.96 | 04-MAY-18:10 | 18.83 | 14.89 | 0.290075E+11 | 18967.25 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.665507E+11 | 31182.42 | 29-JUN-18:10 | 21.50 | 18.39 | 0.285358E+11 | 18960.42 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.708826E+11 | 31895.09 | 19-JUL-18:10 | 22.67 | 18.90 | 0.297642E+11 | 19157.68 | 19-JUL-22:10 | 18.00 | 17.35 |
August | 0.717776E+11 | 31846.86 | 17-AUG-18:10 | 20.77 | 18.28 | 0.301622E+11 | 19186.12 | 16-AUG-22:10 | 20.77 | 18.28 |
September | 0.687361E+11 | 33861.20 | 30-SEP-10:35 | 30.57 | 17.23 | 0.290408E+11 | 19185.81 | 28-SEP-22:10 | 30.57 | 17.23 |
October | 0.719570E+11 | 34450.61 | 15-OCT-10:35 | 31.67 | 16.43 | 0.302943E+11 | 19186.11 | 18-OCT-21:30 | 14.50 | 14.21 |
November | 0.664020E+11 | 32618.81 | 19-NOV-11:35 | 26.00 | 15.32 | 0.286181E+11 | 18986.41 | 27-NOV-23:10 | 16.00 | 5.58 |
December | 0.681042E+11 | 30915.94 | 30-DEC-11:35 | 21.33 | 11.09 | 0.294651E+11 | 19185.63 | 05-DEC-23:10 | 21.33 | 11.09 |
Annual Sum or Average | 0.808520E+12 | 0.347191E+12 | ||||||||
Minimum of Months | 0.597395E+11 | 30355.51 | 16.67 | 8.25 | 0.261899E+11 | 18761.19 | 13.00 | 5.58 | ||
Maximum of Months | 0.719570E+11 | 34450.61 | 31.67 | 18.90 | 0.302943E+11 | 19186.12 | 30.57 | 18.28 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594845E+09 | 2805.52 | 14-JAN-16:11 | 23.00 | 12.42 | 98367268.22 | 56.69 | 19-JAN-23:19 | 13.83 | 12.74 |
February | 0.531467E+09 | 2811.90 | 03-FEB-16:11 | 20.00 | 10.06 | 88563022.33 | 56.69 | 02-FEB-00:10 | 20.00 | 10.06 |
March | 0.546628E+09 | 2487.52 | 19-MAR-18:01 | 13.83 | 12.77 | 98065113.93 | 56.69 | 23-MAR-23:00 | 12.00 | 12.00 |
April | 0.953925E+09 | 2631.65 | 01-APR-18:02 | 17.83 | 8.84 | 95656229.80 | 56.69 | 26-APR-21:10 | 16.00 | 15.39 |
May | 0.919143E+09 | 2606.01 | 24-MAY-08:61 | 18.00 | 8.80 | 98779510.95 | 56.69 | 03-MAY-21:00 | 18.00 | 8.80 |
June | 0.115684E+10 | 2560.09 | 01-JUN-15:11 | 20.67 | 15.87 | 95872490.36 | 56.69 | 15-JUN-21:40 | 16.00 | 14.76 |
July | 0.152966E+10 | 2583.16 | 13-JUL-15:11 | 22.67 | 18.88 | 99262531.90 | 56.69 | 06-JUL-21:00 | 22.67 | 18.88 |
August | 0.156981E+10 | 2543.09 | 20-AUG-18:01 | 18.83 | 16.43 | 99391656.93 | 56.69 | 29-AUG-21:40 | 17.20 | 15.33 |
September | 0.129438E+10 | 2557.49 | 09-SEP-15:11 | 21.67 | 18.54 | 95961411.22 | 56.69 | 11-SEP-21:40 | 17.00 | 15.07 |
October | 0.128821E+10 | 2850.87 | 14-OCT-08:61 | 27.67 | 13.01 | 99068850.52 | 56.69 | 18-OCT-22:10 | 13.83 | 13.83 |
November | 0.751241E+09 | 2778.48 | 27-NOV-16:11 | 19.33 | 7.38 | 95513865.38 | 56.69 | 13-NOV-22:40 | 19.33 | 7.38 |
December | 0.677553E+09 | 2810.18 | 19-DEC-16:11 | 20.33 | 7.94 | 98493146.80 | 56.69 | 07-DEC-22:40 | 20.33 | 7.94 |
Annual Sum or Average | 0.118137E+11 | 0.116300E+10 | ||||||||
Minimum of Months | 0.531467E+09 | 2487.52 | 13.83 | 7.38 | 88563022.33 | 56.69 | 12.00 | 7.38 | ||
Maximum of Months | 0.156981E+10 | 2850.87 | 27.67 | 18.88 | 99391656.93 | 56.69 | 22.67 | 18.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225179E+09 | 2487.15 | 09-JAN-16:11 | 15.00 | 9.49 | 97724117.89 | 64.57 | 18-JAN-22:40 | 16.33 | 13.19 |
February | 0.261227E+09 | 2645.85 | 06-FEB-16:11 | 14.67 | 10.54 | 88209089.86 | 56.69 | 16-FEB-22:10 | 12.00 | 11.46 |
March | 0.317519E+09 | 2376.63 | 19-MAR-18:11 | 13.67 | 12.71 | 98246657.49 | 56.69 | 23-MAR-23:10 | 12.00 | 12.00 |
April | 0.643238E+09 | 2678.23 | 19-APR-18:01 | 14.00 | 12.24 | 98649699.81 | 73.98 | 26-APR-21:40 | 16.00 | 15.39 |
May | 0.710273E+09 | 2575.48 | 24-MAY-08:51 | 18.00 | 9.64 | 0.102841E+09 | 73.76 | 03-MAY-21:40 | 18.00 | 9.64 |
June | 0.833940E+09 | 2474.45 | 22-JUN-20:11 | 15.00 | 13.18 | 0.104660E+09 | 77.56 | 30-JUN-21:40 | 16.07 | 15.66 |
July | 0.109612E+10 | 2403.10 | 17-JUL-15:11 | 24.00 | 18.92 | 0.111090E+09 | 77.92 | 07-JUL-21:10 | 24.00 | 18.92 |
August | 0.104434E+10 | 2423.38 | 06-AUG-15:12 | 24.67 | 20.11 | 0.110310E+09 | 76.63 | 03-AUG-21:40 | 24.67 | 20.11 |
September | 0.816027E+09 | 2427.30 | 30-SEP-08:61 | 25.38 | 14.89 | 0.102072E+09 | 72.96 | 13-SEP-21:40 | 25.38 | 14.89 |
October | 0.749179E+09 | 2835.61 | 14-OCT-08:61 | 27.67 | 13.01 | 0.104077E+09 | 74.51 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.342909E+09 | 2531.25 | 30-NOV-19:01 | 13.67 | 6.91 | 95513166.13 | 66.04 | 10-NOV-22:10 | 13.67 | 6.91 |
December | 0.245140E+09 | 2576.18 | 19-DEC-19:01 | 14.00 | 4.98 | 97884726.01 | 65.11 | 05-DEC-22:49 | 14.00 | 4.98 |
Annual Sum or Average | 0.728508E+10 | 0.121128E+10 | ||||||||
Minimum of Months | 0.225179E+09 | 2376.63 | 13.67 | 4.98 | 88209089.86 | 56.69 | 12.00 | 4.98 | ||
Maximum of Months | 0.109612E+10 | 2835.61 | 27.67 | 20.11 | 0.111090E+09 | 77.92 | 25.38 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412848E+09 | 487.11 | 14-JAN-12:40 | 25.33 | 11.70 | 0.00 | 0.00 | 01-JAN-00:10 | 25.33 | 11.70 |
February | 0.273740E+09 | 431.21 | 02-FEB-12:40 | 19.33 | 12.36 | 0.00 | 0.00 | 01-FEB-00:10 | 19.33 | 12.36 |
March | 0.212186E+09 | 365.25 | 11-MAR-13:15 | 24.00 | 13.46 | 0.00 | 0.00 | 01-MAR-00:10 | 24.00 | 13.46 |
April | 0.236023E+09 | 255.69 | 08-APR-12:50 | 22.17 | 16.56 | 0.00 | 0.00 | 01-APR-00:10 | 22.17 | 16.56 |
May | 0.155276E+09 | 185.03 | 04-MAY-12:30 | 23.50 | 16.62 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 16.62 |
June | 0.187249E+09 | 189.41 | 24-JUN-08:00 | 19.00 | 14.76 | 0.00 | 0.00 | 01-JUN-00:10 | 19.00 | 14.76 |
July | 0.268042E+09 | 216.51 | 30-JUL-08:00 | 20.00 | 18.03 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 18.03 |
August | 0.348151E+09 | 243.06 | 30-AUG-13:00 | 24.00 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.00 | 18.12 |
September | 0.386267E+09 | 445.06 | 30-SEP-13:05 | 32.00 | 16.98 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.98 |
October | 0.492059E+09 | 534.11 | 16-OCT-12:30 | 35.05 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 35.05 | 17.21 |
November | 0.419074E+09 | 522.47 | 19-NOV-09:53 | 26.00 | 13.89 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 13.89 |
December | 0.462875E+09 | 496.46 | 19-DEC-13:00 | 26.00 | 11.60 | 0.00 | 0.00 | 01-DEC-00:10 | 26.00 | 11.60 |
Annual Sum or Average | 0.385379E+10 | 0.00 | ||||||||
Minimum of Months | 0.155276E+09 | 185.03 | 19.00 | 11.60 | 0.00 | 0.00 | 19.00 | 11.60 | ||
Maximum of Months | 0.492059E+09 | 534.11 | 35.05 | 18.12 | 0.00 | 0.00 | 35.05 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271799E+09 | 914.02 | 16-JAN-09:02 | 15.33 | 6.47 | 97684397.21 | 68.33 | 18-JAN-22:00 | 16.00 | 13.03 |
February | 0.275500E+09 | 905.76 | 05-FEB-09:01 | 13.50 | 5.78 | 87969473.40 | 58.00 | 13-FEB-21:19 | 14.67 | 14.08 |
March | 0.316049E+09 | 845.32 | 04-MAR-09:01 | 14.00 | 12.23 | 97686274.00 | 57.29 | 02-MAR-05:49 | 14.00 | 12.23 |
April | 0.375358E+09 | 901.39 | 02-APR-08:51 | 19.00 | 9.47 | 95857898.43 | 70.74 | 25-APR-21:10 | 14.83 | 14.24 |
May | 0.425880E+09 | 903.91 | 24-MAY-08:51 | 18.00 | 9.64 | 99988425.88 | 71.00 | 04-MAY-21:00 | 18.00 | 9.64 |
June | 0.443556E+09 | 879.03 | 22-JUN-20:11 | 15.00 | 13.18 | 0.100189E+09 | 73.73 | 30-JUN-21:00 | 16.10 | 16.10 |
July | 0.509730E+09 | 889.83 | 18-JUL-18:02 | 23.33 | 19.62 | 0.105709E+09 | 75.04 | 07-JUL-21:10 | 23.33 | 19.62 |
August | 0.482316E+09 | 839.89 | 17-AUG-15:12 | 26.13 | 20.58 | 0.105270E+09 | 72.98 | 16-AUG-21:00 | 26.13 | 20.58 |
September | 0.408281E+09 | 842.05 | 03-SEP-08:51 | 20.00 | 15.11 | 98865437.55 | 70.84 | 22-SEP-21:00 | 17.00 | 16.37 |
October | 0.419903E+09 | 1015.11 | 14-OCT-08:61 | 27.67 | 13.01 | 0.102173E+09 | 73.07 | 04-OCT-21:19 | 27.67 | 13.01 |
November | 0.301209E+09 | 930.42 | 19-NOV-09:41 | 25.67 | 13.67 | 94616485.33 | 67.75 | 10-NOV-22:10 | 25.67 | 13.67 |
December | 0.273248E+09 | 915.79 | 19-DEC-19:01 | 14.00 | 4.98 | 97458285.47 | 68.37 | 06-DEC-22:10 | 14.00 | 4.98 |
Annual Sum or Average | 0.450283E+10 | 0.118347E+10 | ||||||||
Minimum of Months | 0.271799E+09 | 839.89 | 13.50 | 4.98 | 87969473.40 | 57.29 | 14.00 | 4.98 | ||
Maximum of Months | 0.509730E+09 | 1015.11 | 27.67 | 20.58 | 0.105709E+09 | 75.04 | 27.67 | 20.58 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.616477E+09 | 2531.47 | 14-JAN-16:11 | 23.00 | 12.42 | 98671247.89 | 56.69 | 20-JAN-23:49 | 13.17 | 13.17 |
February | 0.495010E+09 | 2541.73 | 01-FEB-09:01 | 22.33 | 11.86 | 88647695.18 | 56.69 | 16-FEB-22:49 | 12.00 | 11.46 |
March | 0.533634E+09 | 2279.48 | 12-MAR-15:11 | 18.33 | 15.23 | 98249247.52 | 56.69 | 23-MAR-23:40 | 12.00 | 12.00 |
April | 0.871876E+09 | 2517.54 | 02-APR-08:61 | 17.33 | 8.66 | 95802819.99 | 56.69 | 26-APR-21:19 | 16.00 | 15.39 |
May | 0.805437E+09 | 2522.97 | 24-MAY-08:61 | 18.00 | 8.80 | 98866772.09 | 56.69 | 04-MAY-21:40 | 18.00 | 8.80 |
June | 0.995703E+09 | 2303.07 | 25-JUN-08:61 | 19.50 | 15.48 | 95908625.13 | 56.69 | 22-JUN-21:10 | 19.50 | 15.48 |
July | 0.139260E+10 | 2317.02 | 23-JUL-08:61 | 23.33 | 19.11 | 99428159.94 | 56.69 | 27-JUL-21:00 | 18.00 | 17.35 |
August | 0.148567E+10 | 2306.98 | 29-AUG-15:11 | 22.67 | 17.12 | 99552974.59 | 56.69 | 24-AUG-21:10 | 22.67 | 17.12 |
September | 0.113273E+10 | 2310.80 | 20-SEP-15:11 | 21.67 | 16.74 | 95862131.82 | 56.69 | 13-SEP-21:40 | 21.67 | 16.74 |
October | 0.123015E+10 | 2602.05 | 14-OCT-08:61 | 27.67 | 13.01 | 99130038.74 | 56.69 | 01-OCT-00:00 | 27.67 | 13.01 |
November | 0.700971E+09 | 2546.68 | 27-NOV-09:01 | 21.17 | 8.41 | 95644979.36 | 56.69 | 20-NOV-00:10 | 21.17 | 8.41 |
December | 0.671369E+09 | 2560.04 | 05-DEC-09:01 | 24.33 | 12.02 | 98716243.38 | 56.69 | 07-DEC-22:40 | 12.27 | 12.24 |
Annual Sum or Average | 0.109316E+11 | 0.116448E+10 | ||||||||
Minimum of Months | 0.495010E+09 | 2279.48 | 17.33 | 8.41 | 88647695.18 | 56.69 | 12.00 | 8.41 | ||
Maximum of Months | 0.148567E+10 | 2602.05 | 27.67 | 19.11 | 99552974.59 | 56.69 | 27.67 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259328E+09 | 2372.66 | 14-JAN-09:52 | 22.00 | 9.25 | 97783766.10 | 63.74 | 24-JAN-22:40 | 15.00 | 11.13 |
February | 0.246442E+09 | 2415.21 | 03-FEB-09:52 | 21.00 | 8.28 | 87962116.48 | 56.69 | 01-FEB-22:10 | 21.00 | 8.28 |
March | 0.322724E+09 | 2341.83 | 23-MAR-08:51 | 19.00 | 14.76 | 98092668.46 | 56.69 | 23-MAR-22:40 | 12.33 | 12.15 |
April | 0.611030E+09 | 2593.46 | 02-APR-08:51 | 19.00 | 9.47 | 97572406.49 | 70.45 | 26-APR-21:40 | 16.00 | 15.39 |
May | 0.646535E+09 | 2662.06 | 24-MAY-08:51 | 18.00 | 9.64 | 0.101578E+09 | 71.39 | 04-MAY-21:40 | 18.00 | 9.64 |
June | 0.759641E+09 | 2508.73 | 23-JUN-08:51 | 21.00 | 15.42 | 0.101744E+09 | 72.43 | 30-JUN-21:49 | 16.08 | 15.88 |
July | 0.103005E+10 | 2527.07 | 04-JUL-08:51 | 22.00 | 15.83 | 0.108185E+09 | 73.97 | 19-JUL-21:40 | 18.00 | 17.57 |
August | 0.101467E+10 | 2426.57 | 22-AUG-08:51 | 19.00 | 14.76 | 0.108089E+09 | 73.82 | 15-AUG-21:40 | 19.00 | 14.76 |
September | 0.715742E+09 | 2457.17 | 03-SEP-08:51 | 20.00 | 15.11 | 0.100292E+09 | 70.18 | 13-SEP-21:40 | 17.00 | 16.37 |
October | 0.712490E+09 | 2890.11 | 17-OCT-08:21 | 27.50 | 13.36 | 0.103419E+09 | 72.90 | 16-OCT-21:40 | 27.50 | 13.36 |
November | 0.325814E+09 | 2379.61 | 28-NOV-09:52 | 21.00 | 8.49 | 95100962.52 | 62.84 | 10-NOV-22:10 | 21.00 | 8.49 |
December | 0.253998E+09 | 2565.23 | 05-DEC-09:41 | 25.67 | 12.88 | 97879578.91 | 65.07 | 05-DEC-22:49 | 17.83 | 9.39 |
Annual Sum or Average | 0.689847E+10 | 0.119770E+10 | ||||||||
Minimum of Months | 0.246442E+09 | 2341.83 | 18.00 | 8.28 | 87962116.48 | 56.69 | 12.33 | 8.28 | ||
Maximum of Months | 0.103005E+10 | 2890.11 | 27.50 | 15.83 | 0.108185E+09 | 73.97 | 27.50 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366869E+10 | 1825.94 | 22-JAN-11:35 | 16.67 | 11.79 | 0.129699E+10 | 810.30 | 20-JAN-23:10 | 16.67 | 11.79 |
February | 0.330849E+10 | 1800.00 | 04-FEB-11:35 | 20.67 | 8.25 | 0.117074E+10 | 809.18 | 03-FEB-23:10 | 20.67 | 8.25 |
March | 0.357025E+10 | 1806.24 | 12-MAR-10:35 | 21.33 | 14.69 | 0.128040E+10 | 804.11 | 24-MAR-22:10 | 13.00 | 11.29 |
April | 0.371875E+10 | 1893.22 | 30-APR-10:35 | 25.67 | 16.97 | 0.127792E+10 | 816.40 | 27-APR-22:10 | 25.67 | 16.97 |
May | 0.387061E+10 | 1891.50 | 04-MAY-10:35 | 22.00 | 15.73 | 0.133016E+10 | 834.90 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.392796E+10 | 1952.76 | 25-JUN-10:35 | 23.00 | 17.26 | 0.132411E+10 | 847.67 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.429220E+10 | 2026.45 | 23-JUL-10:35 | 25.67 | 20.39 | 0.140743E+10 | 858.26 | 28-JUL-22:10 | 18.00 | 17.35 |
August | 0.434496E+10 | 2047.22 | 19-AUG-10:35 | 24.67 | 20.11 | 0.142580E+10 | 867.03 | 18-AUG-22:10 | 24.67 | 20.11 |
September | 0.404579E+10 | 2115.78 | 30-SEP-10:35 | 30.57 | 17.23 | 0.134816E+10 | 867.33 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.423452E+10 | 2097.66 | 15-OCT-10:35 | 31.67 | 16.43 | 0.140861E+10 | 890.37 | 17-OCT-22:10 | 17.67 | 13.97 |
November | 0.373017E+10 | 1895.34 | 19-NOV-11:35 | 26.00 | 15.32 | 0.129004E+10 | 838.74 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.378182E+10 | 1818.36 | 05-DEC-11:35 | 23.33 | 12.89 | 0.131966E+10 | 821.81 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.464942E+11 | 0.158800E+11 | ||||||||
Minimum of Months | 0.330849E+10 | 1800.00 | 16.67 | 8.25 | 0.117074E+10 | 804.11 | 13.00 | 8.25 | ||
Maximum of Months | 0.434496E+10 | 2115.78 | 31.67 | 20.39 | 0.142580E+10 | 890.37 | 30.57 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475564E+09 | 2908.61 | 14-JAN-16:11 | 23.00 | 12.42 | 98061308.94 | 56.70 | 25-JAN-05:10 | 16.00 | 11.06 |
February | 0.426594E+09 | 2912.21 | 03-FEB-16:11 | 20.00 | 10.06 | 88268139.39 | 56.69 | 17-FEB-02:20 | 12.00 | 11.46 |
March | 0.478267E+09 | 2544.24 | 19-MAR-18:01 | 13.83 | 12.77 | 97840535.90 | 56.69 | 20-MAR-01:10 | 9.83 | 9.34 |
April | 0.926837E+09 | 2751.13 | 01-APR-18:02 | 17.83 | 8.84 | 95603868.27 | 56.69 | 25-APR-04:30 | 11.50 | 11.23 |
May | 0.880478E+09 | 2680.34 | 24-MAY-08:61 | 18.00 | 8.80 | 98738876.34 | 56.70 | 06-MAY-03:09 | 18.00 | 8.80 |
June | 0.116588E+10 | 2678.34 | 29-JUN-18:01 | 21.50 | 18.39 | 95847529.16 | 56.69 | 30-JUN-21:40 | 16.07 | 15.66 |
July | 0.157619E+10 | 2648.50 | 31-JUL-18:02 | 22.67 | 19.46 | 99236854.04 | 56.69 | 18-JUL-21:40 | 22.67 | 19.46 |
August | 0.159461E+10 | 2628.90 | 01-AUG-18:01 | 17.83 | 15.38 | 99341203.35 | 56.69 | 09-AUG-21:00 | 18.00 | 17.36 |
September | 0.125795E+10 | 2590.21 | 09-SEP-15:11 | 21.67 | 18.54 | 95887793.30 | 56.69 | 24-SEP-00:10 | 17.00 | 15.73 |
October | 0.119146E+10 | 2955.48 | 13-OCT-15:11 | 27.33 | 14.91 | 98937897.51 | 56.69 | 17-OCT-21:00 | 18.00 | 14.37 |
November | 0.607807E+09 | 2873.77 | 27-NOV-16:11 | 19.33 | 7.38 | 95257226.25 | 56.70 | 10-NOV-03:49 | 19.33 | 7.38 |
December | 0.532923E+09 | 2913.23 | 19-DEC-16:11 | 20.33 | 7.94 | 98150621.66 | 56.69 | 26-DEC-01:10 | 13.17 | 3.76 |
Annual Sum or Average | 0.111146E+11 | 0.116117E+10 | ||||||||
Minimum of Months | 0.426594E+09 | 2544.24 | 13.83 | 7.38 | 88268139.39 | 56.69 | 9.83 | 3.76 | ||
Maximum of Months | 0.159461E+10 | 2955.48 | 27.33 | 19.46 | 99341203.35 | 56.70 | 22.67 | 19.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137386E+09 | 2529.76 | 09-JAN-16:11 | 15.00 | 9.49 | 97167296.30 | 63.24 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.170504E+09 | 2732.20 | 06-FEB-16:11 | 14.67 | 10.54 | 87821113.34 | 56.69 | 23-FEB-22:30 | 13.50 | 11.00 |
March | 0.247102E+09 | 2542.98 | 19-MAR-18:11 | 13.67 | 12.71 | 98136553.18 | 58.87 | 22-MAR-18:10 | 15.50 | 14.39 |
April | 0.604782E+09 | 2820.62 | 23-APR-18:11 | 14.67 | 13.07 | 99259824.90 | 76.69 | 26-APR-21:40 | 16.00 | 15.39 |
May | 0.681470E+09 | 2710.17 | 18-MAY-19:11 | 13.67 | 12.32 | 0.103461E+09 | 76.04 | 03-MAY-21:40 | 13.67 | 12.32 |
June | 0.878548E+09 | 2635.05 | 22-JUN-20:11 | 15.00 | 13.18 | 0.106165E+09 | 81.07 | 30-JUN-18:10 | 18.83 | 16.43 |
July | 0.119990E+10 | 2542.09 | 08-JUL-21:11 | 15.00 | 13.80 | 0.112983E+09 | 80.86 | 07-JUL-21:10 | 15.00 | 13.80 |
August | 0.111598E+10 | 2447.47 | 21-AUG-20:11 | 15.00 | 13.80 | 0.111801E+09 | 79.18 | 03-AUG-21:40 | 15.00 | 13.80 |
September | 0.798180E+09 | 2488.19 | 30-SEP-08:61 | 25.38 | 14.89 | 0.102409E+09 | 73.83 | 13-SEP-21:40 | 25.38 | 14.89 |
October | 0.672363E+09 | 2860.88 | 14-OCT-08:61 | 27.67 | 13.01 | 0.103753E+09 | 74.29 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.215763E+09 | 2547.57 | 30-NOV-19:01 | 13.67 | 6.91 | 95031671.93 | 64.11 | 10-NOV-22:10 | 13.67 | 6.91 |
December | 0.142233E+09 | 2604.37 | 19-DEC-19:01 | 14.00 | 4.98 | 97200106.04 | 63.42 | 05-DEC-22:40 | 14.00 | 4.98 |
Annual Sum or Average | 0.686421E+10 | 0.121519E+10 | ||||||||
Minimum of Months | 0.137386E+09 | 2447.47 | 13.67 | 4.98 | 87821113.34 | 56.69 | 13.50 | 4.98 | ||
Maximum of Months | 0.119990E+10 | 2860.88 | 27.67 | 14.89 | 0.112983E+09 | 81.07 | 25.38 | 16.43 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.827594E+09 | 1613.70 | 14-JAN-16:11 | 23.00 | 12.42 | 99144355.49 | 57.29 | 28-JAN-03:00 | 6.00 | 6.00 |
February | 0.581035E+09 | 1602.84 | 03-FEB-16:11 | 20.00 | 10.06 | 89110631.49 | 57.32 | 21-FEB-04:00 | 8.00 | 6.97 |
March | 0.508952E+09 | 1417.43 | 24-MAR-18:01 | 13.00 | 11.87 | 98521110.33 | 57.28 | 02-MAR-02:20 | 13.00 | 11.87 |
April | 0.589176E+09 | 1522.22 | 01-APR-18:02 | 17.83 | 8.84 | 95625844.03 | 56.69 | 07-APR-21:10 | 13.00 | 12.44 |
May | 0.437630E+09 | 1453.02 | 18-MAY-15:11 | 21.67 | 13.85 | 98407962.56 | 56.69 | 04-MAY-21:19 | 21.67 | 13.85 |
June | 0.508493E+09 | 1413.12 | 21-JUN-15:11 | 22.00 | 16.41 | 95486119.81 | 56.69 | 28-JUN-01:19 | 16.67 | 15.83 |
July | 0.701640E+09 | 1447.15 | 31-JUL-15:12 | 25.33 | 20.29 | 99058472.94 | 56.69 | 31-JUL-21:49 | 18.75 | 17.98 |
August | 0.840011E+09 | 1455.56 | 10-AUG-15:12 | 22.67 | 18.32 | 99274587.04 | 56.69 | 25-AUG-21:40 | 16.03 | 16.03 |
September | 0.838827E+09 | 1443.92 | 09-SEP-15:11 | 21.67 | 18.54 | 95800893.39 | 56.69 | 07-SEP-21:40 | 21.67 | 18.54 |
October | 0.102003E+10 | 1622.92 | 14-OCT-08:61 | 27.67 | 13.01 | 99153377.19 | 56.69 | 01-OCT-01:19 | 27.67 | 13.01 |
November | 0.830958E+09 | 1597.50 | 27-NOV-09:01 | 21.17 | 8.41 | 96042246.30 | 57.33 | 24-NOV-05:19 | 21.17 | 8.41 |
December | 0.898038E+09 | 1609.42 | 19-DEC-16:11 | 20.33 | 7.94 | 99207474.53 | 57.35 | 25-DEC-04:30 | 6.80 | 5.70 |
Annual Sum or Average | 0.858239E+10 | 0.116483E+10 | ||||||||
Minimum of Months | 0.437630E+09 | 1413.12 | 13.00 | 7.94 | 89110631.49 | 56.69 | 6.00 | 5.70 | ||
Maximum of Months | 0.102003E+10 | 1622.92 | 27.67 | 20.29 | 99274587.04 | 57.35 | 27.67 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393730E+11 | 18068.80 | 18-JAN-19:10 | 18.83 | 14.20 | 0.166669E+11 | 11137.46 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.358474E+11 | 17646.07 | 01-FEB-23:10 | 13.00 | 11.39 | 0.151570E+11 | 11051.39 | 01-FEB-23:49 | 13.00 | 11.77 |
March | 0.398949E+11 | 18195.82 | 23-MAR-18:10 | 16.50 | 14.36 | 0.168602E+11 | 11143.19 | 24-MAR-22:49 | 13.00 | 11.29 |
April | 0.402251E+11 | 18952.53 | 26-APR-18:10 | 18.67 | 15.37 | 0.165253E+11 | 11294.29 | 26-APR-22:49 | 16.00 | 14.87 |
May | 0.419299E+11 | 19120.46 | 04-MAY-18:10 | 18.83 | 14.89 | 0.172101E+11 | 11348.81 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.418109E+11 | 19529.40 | 29-JUN-18:10 | 21.50 | 18.39 | 0.169331E+11 | 11349.08 | 20-JUN-22:10 | 21.50 | 18.39 |
July | 0.440637E+11 | 19744.31 | 19-JUL-18:10 | 22.67 | 18.90 | 0.175226E+11 | 11349.08 | 03-JUL-22:10 | 22.67 | 18.90 |
August | 0.439150E+11 | 19409.21 | 17-AUG-18:10 | 20.77 | 18.28 | 0.175862E+11 | 11348.96 | 02-AUG-22:10 | 20.77 | 18.28 |
September | 0.413932E+11 | 19221.24 | 30-SEP-17:20 | 25.00 | 17.45 | 0.167787E+11 | 11344.20 | 29-SEP-22:19 | 25.00 | 17.45 |
October | 0.423758E+11 | 19319.41 | 16-OCT-18:10 | 23.83 | 14.43 | 0.172756E+11 | 11348.89 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.388260E+11 | 17864.91 | 01-NOV-18:10 | 15.83 | 12.41 | 0.162901E+11 | 11116.46 | 01-NOV-22:49 | 13.17 | 10.87 |
December | 0.395206E+11 | 17961.34 | 05-DEC-22:00 | 17.00 | 9.46 | 0.167145E+11 | 11194.57 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.489176E+12 | 0.201520E+12 | ||||||||
Minimum of Months | 0.358474E+11 | 17646.07 | 13.00 | 9.46 | 0.151570E+11 | 11051.39 | 13.00 | 9.21 | ||
Maximum of Months | 0.440637E+11 | 19744.31 | 25.00 | 18.90 | 0.175862E+11 | 11349.08 | 25.00 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412474E+11 | 18759.83 | 18-JAN-19:10 | 18.83 | 14.20 | 0.171781E+11 | 11348.36 | 24-JAN-23:10 | 14.33 | 10.84 |
February | 0.375371E+11 | 18284.75 | 13-FEB-23:10 | 14.00 | 13.42 | 0.156222E+11 | 11344.15 | 02-FEB-00:10 | 14.00 | 13.42 |
March | 0.418438E+11 | 18859.41 | 23-MAR-18:10 | 16.50 | 14.36 | 0.173944E+11 | 11344.04 | 24-MAR-22:49 | 13.00 | 11.29 |
April | 0.419291E+11 | 19604.18 | 26-APR-18:10 | 18.67 | 15.37 | 0.169849E+11 | 11348.98 | 25-APR-21:30 | 18.67 | 15.37 |
May | 0.436939E+11 | 20173.30 | 04-MAY-21:10 | 17.00 | 15.07 | 0.176758E+11 | 11348.92 | 03-MAY-22:10 | 17.00 | 15.07 |
June | 0.434342E+11 | 20647.22 | 27-JUN-21:10 | 17.00 | 16.37 | 0.173298E+11 | 11349.09 | 20-JUN-22:10 | 17.00 | 16.37 |
July | 0.456344E+11 | 20700.74 | 19-JUL-21:10 | 18.00 | 17.89 | 0.178989E+11 | 11349.11 | 07-JUL-21:30 | 18.00 | 17.89 |
August | 0.454597E+11 | 20464.85 | 02-AUG-21:10 | 17.88 | 16.64 | 0.179525E+11 | 11348.97 | 01-AUG-22:10 | 17.88 | 16.64 |
September | 0.428967E+11 | 20826.46 | 29-SEP-21:10 | 24.58 | 13.52 | 0.171604E+11 | 11348.81 | 12-SEP-22:10 | 24.58 | 13.52 |
October | 0.439251E+11 | 20719.10 | 04-OCT-21:10 | 21.00 | 18.98 | 0.176714E+11 | 11348.90 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.404968E+11 | 18489.23 | 01-NOV-18:10 | 15.83 | 12.41 | 0.167517E+11 | 11347.97 | 27-NOV-23:10 | 16.00 | 5.58 |
December | 0.413079E+11 | 18675.92 | 05-DEC-22:54 | 18.00 | 9.37 | 0.172051E+11 | 11348.28 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.509406E+12 | 0.206825E+12 | ||||||||
Minimum of Months | 0.375371E+11 | 18284.75 | 14.00 | 9.37 | 0.156222E+11 | 11344.04 | 13.00 | 5.58 | ||
Maximum of Months | 0.456344E+11 | 20826.46 | 24.58 | 18.98 | 0.179525E+11 | 11349.11 | 24.58 | 17.89 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505742E+11 | 27190.25 | 14-JAN-11:50 | 26.00 | 11.78 | 0.188680E+11 | 11319.53 | 07-JAN-18:10 | 26.00 | 11.78 |
February | 0.456644E+11 | 27056.06 | 19-FEB-11:50 | 16.00 | 13.49 | 0.170436E+11 | 11319.53 | 04-FEB-18:10 | 16.00 | 13.49 |
March | 0.507890E+11 | 27787.62 | 19-MAR-10:50 | 19.67 | 15.35 | 0.188761E+11 | 11319.50 | 11-MAR-18:10 | 19.67 | 15.35 |
April | 0.506101E+11 | 28182.43 | 30-APR-10:40 | 25.67 | 16.97 | 0.182623E+11 | 11319.58 | 08-APR-17:10 | 25.67 | 16.97 |
May | 0.522867E+11 | 27846.34 | 04-MAY-10:40 | 22.00 | 15.73 | 0.188717E+11 | 11319.57 | 27-MAY-17:10 | 17.83 | 13.11 |
June | 0.515494E+11 | 28248.89 | 25-JUN-10:40 | 23.00 | 17.26 | 0.182660E+11 | 11319.62 | 17-JUN-17:10 | 23.00 | 17.26 |
July | 0.541375E+11 | 28561.10 | 23-JUL-10:40 | 25.67 | 20.39 | 0.188681E+11 | 11319.65 | 29-JUL-17:10 | 21.83 | 19.24 |
August | 0.542070E+11 | 28464.86 | 19-AUG-10:40 | 24.67 | 20.11 | 0.188754E+11 | 11319.65 | 19-AUG-17:10 | 23.83 | 17.59 |
September | 0.514320E+11 | 28927.80 | 30-SEP-10:50 | 30.78 | 17.57 | 0.182615E+11 | 11319.61 | 30-SEP-17:10 | 25.50 | 17.63 |
October | 0.527743E+11 | 28811.47 | 15-OCT-10:50 | 31.83 | 16.40 | 0.188688E+11 | 11319.61 | 14-OCT-17:10 | 31.83 | 16.40 |
November | 0.493399E+11 | 27745.56 | 19-NOV-11:50 | 26.00 | 15.39 | 0.182586E+11 | 11319.52 | 25-NOV-18:10 | 13.00 | 11.21 |
December | 0.505696E+11 | 27063.68 | 05-DEC-11:50 | 23.17 | 12.83 | 0.188680E+11 | 11319.53 | 23-DEC-18:10 | 10.83 | 10.73 |
Annual Sum or Average | 0.613934E+12 | 0.222188E+12 | ||||||||
Minimum of Months | 0.456644E+11 | 27056.06 | 16.00 | 11.78 | 0.170436E+11 | 11319.50 | 10.83 | 10.73 | ||
Maximum of Months | 0.542070E+11 | 28927.80 | 31.83 | 20.39 | 0.188761E+11 | 11319.65 | 31.83 | 19.24 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444485E+10 | 2318.37 | 20-JAN-11:35 | 21.67 | 15.71 | 0.148985E+10 | 962.59 | 18-JAN-22:40 | 21.67 | 15.71 |
February | 0.403174E+10 | 2227.95 | 04-FEB-11:50 | 20.83 | 8.35 | 0.135533E+10 | 940.01 | 01-FEB-23:10 | 20.83 | 8.35 |
March | 0.442429E+10 | 2305.15 | 11-MAR-11:35 | 24.00 | 13.82 | 0.149232E+10 | 967.29 | 24-MAR-21:49 | 13.00 | 11.39 |
April | 0.473987E+10 | 2613.76 | 27-APR-14:10 | 20.03 | 15.47 | 0.153112E+10 | 998.54 | 27-APR-22:10 | 14.00 | 12.84 |
May | 0.494188E+10 | 3056.10 | 04-MAY-12:00 | 24.00 | 16.55 | 0.159440E+10 | 1007.40 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.524809E+10 | 3146.07 | 30-JUN-15:35 | 22.80 | 17.87 | 0.160862E+10 | 1007.40 | 29-JUN-22:10 | 22.80 | 17.87 |
July | 0.611227E+10 | 3516.34 | 30-JUL-13:30 | 24.00 | 19.60 | 0.169724E+10 | 1007.40 | 26-JUL-22:10 | 24.00 | 19.60 |
August | 0.625698E+10 | 3739.81 | 19-AUG-13:10 | 27.00 | 20.18 | 0.170712E+10 | 1007.40 | 03-AUG-22:10 | 27.00 | 20.18 |
September | 0.546219E+10 | 5052.68 | 30-SEP-13:30 | 32.00 | 17.24 | 0.161609E+10 | 1007.40 | 06-SEP-22:10 | 32.00 | 17.24 |
October | 0.570368E+10 | 4902.75 | 16-OCT-12:30 | 35.05 | 17.21 | 0.165893E+10 | 1007.40 | 18-OCT-21:30 | 14.50 | 14.21 |
November | 0.453255E+10 | 2617.43 | 19-NOV-13:00 | 27.00 | 14.96 | 0.149372E+10 | 988.07 | 01-NOV-00:10 | 27.00 | 14.96 |
December | 0.454099E+10 | 2322.96 | 19-DEC-13:10 | 25.50 | 11.30 | 0.151331E+10 | 976.78 | 05-DEC-23:10 | 25.50 | 11.30 |
Annual Sum or Average | 0.604394E+11 | 0.187580E+11 | ||||||||
Minimum of Months | 0.403174E+10 | 2227.95 | 20.03 | 8.35 | 0.135533E+10 | 940.01 | 13.00 | 8.35 | ||
Maximum of Months | 0.625698E+10 | 5052.68 | 35.05 | 20.18 | 0.170712E+10 | 1007.40 | 32.00 | 20.18 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21067940.53 | 883.35 | 09-JAN-16:14 | 15.00 |
February | 11924775.05 | 882.07 | 03-FEB-19:04 | 13.83 |
March | 28140553.89 | 864.20 | 03-MAR-19:04 | 12.00 |
April | 4902382.63 | 871.73 | 14-APR-18:04 | 12.83 |
May | 2661020.75 | 826.88 | 11-MAY-15:15 | 17.00 |
June | 1654353.90 | 831.30 | 08-JUN-15:15 | 18.00 |
July | 995288.73 | 797.74 | 03-JUL-08:05 | 19.33 |
August | 1005135.37 | 814.73 | 09-AUG-08:05 | 19.50 |
September | 1346671.49 | 723.61 | 13-SEP-08:05 | 20.33 |
October | 2146436.55 | 850.08 | 25-OCT-18:04 | 18.50 |
November | 3183426.97 | 879.29 | 30-NOV-19:04 | 13.67 |
December | 10366977.30 | 885.09 | 19-DEC-19:04 | 14.00 |
Annual Sum or Average | 89394963.15 | |||
Minimum of Months | 995288.73 | 723.61 | 12.00 | |
Maximum of Months | 28140553.89 | 885.09 | 20.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63793407.83 | 859.46 | 04-JAN-19:03 | 13.33 |
February | 19380303.81 | 853.39 | 21-FEB-19:04 | 13.00 |
March | 39333778.03 | 848.60 | 22-MAR-08:03 | 14.33 |
April | 5277525.03 | 858.60 | 28-APR-08:04 | 15.33 |
May | 2033178.19 | 819.54 | 09-MAY-08:04 | 13.83 |
June | 763642.40 | 793.32 | 02-JUN-08:53 | 19.00 |
July | 158670.85 | 395.83 | 07-JUL-08:54 | 21.00 |
August | 151082.45 | 229.03 | 11-AUG-08:55 | 21.00 |
September | 895530.03 | 785.79 | 03-SEP-08:53 | 20.00 |
October | 1151276.24 | 805.83 | 27-OCT-08:53 | 19.00 |
November | 7344608.28 | 847.55 | 15-NOV-09:03 | 14.33 |
December | 35732565.83 | 852.07 | 14-DEC-16:14 | 13.67 |
Annual Sum or Average | 0.176016E+09 | |||
Minimum of Months | 151082.45 | 229.03 | 13.00 | |
Maximum of Months | 63793407.83 | 859.46 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 742839.90 | 230.90 | 22-JAN-16:14 | 14.33 |
February | 491858.15 | 231.96 | 06-FEB-09:04 | 14.33 |
March | 470933.31 | 227.59 | 30-MAR-15:14 | 15.00 |
April | 129187.55 | 176.29 | 17-APR-16:26 | 13.00 |
May | 92584.40 | 150.31 | 07-MAY-19:07 | 14.00 |
June | 44539.40 | 167.57 | 03-JUN-08:56 | 19.00 |
July | 6455.27 | 53.96 | 09-JUL-21:57 | 17.00 |
August | 8270.44 | 120.41 | 22-AUG-08:54 | 19.00 |
September | 122848.77 | 209.43 | 19-SEP-08:54 | 17.00 |
October | 156626.81 | 197.09 | 10-OCT-08:54 | 20.00 |
November | 443888.93 | 227.97 | 26-NOV-16:14 | 13.67 |
December | 650601.28 | 229.59 | 27-DEC-09:04 | 15.67 |
Annual Sum or Average | 3360634.21 | |||
Minimum of Months | 6455.27 | 53.96 | 13.00 | |
Maximum of Months | 742839.90 | 231.96 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20519031.33 | 849.13 | 03-JAN-16:14 | 15.67 |
February | 14267682.32 | 846.12 | 23-FEB-16:14 | 14.00 |
March | 35403375.39 | 839.88 | 05-MAR-16:14 | 14.33 |
April | 4228170.92 | 834.94 | 06-APR-18:04 | 13.00 |
May | 2720757.53 | 817.97 | 13-MAY-18:04 | 13.67 |
June | 1020379.02 | 749.37 | 07-JUN-18:04 | 16.83 |
July | 244494.11 | 673.06 | 09-JUL-18:05 | 17.83 |
August | 145895.07 | 172.58 | 08-AUG-18:06 | 18.83 |
September | 1189510.93 | 762.34 | 04-SEP-18:04 | 16.83 |
October | 1342271.01 | 787.80 | 24-OCT-15:15 | 19.00 |
November | 2696005.73 | 843.39 | 28-NOV-19:04 | 12.33 |
December | 11985838.94 | 843.45 | 10-DEC-16:14 | 14.00 |
Annual Sum or Average | 95763412.31 | |||
Minimum of Months | 145895.07 | 172.58 | 12.33 | |
Maximum of Months | 35403375.39 | 849.13 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63302327.31 | 819.80 | 25-JAN-16:14 | 15.00 |
February | 25958906.92 | 813.70 | 10-FEB-16:13 | 14.93 |
March | 50478315.61 | 818.01 | 13-MAR-18:04 | 13.00 |
April | 4280399.02 | 820.61 | 06-APR-18:04 | 13.00 |
May | 1774923.12 | 816.05 | 08-MAY-18:14 | 14.67 |
June | 470558.15 | 783.94 | 12-JUN-19:34 | 14.33 |
July | 93217.52 | 328.10 | 11-JUL-21:55 | 16.00 |
August | 41744.23 | 263.01 | 21-AUG-20:15 | 15.00 |
September | 845967.03 | 495.10 | 16-SEP-19:14 | 14.67 |
October | 624640.45 | 419.56 | 06-OCT-21:55 | 17.00 |
November | 12249458.75 | 811.89 | 08-NOV-19:04 | 13.83 |
December | 43192382.44 | 812.27 | 01-DEC-16:13 | 12.67 |
Annual Sum or Average | 0.203313E+09 | |||
Minimum of Months | 41744.23 | 263.01 | 12.67 | |
Maximum of Months | 63302327.31 | 820.61 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85083928.17 | 1062.43 | 09-JAN-16:14 | 15.00 |
February | 55975439.48 | 1057.16 | 21-FEB-19:04 | 13.00 |
March | 91729967.97 | 1052.42 | 09-MAR-19:04 | 12.83 |
April | 11390548.62 | 1022.12 | 17-APR-18:04 | 12.00 |
May | 8514832.53 | 890.97 | 20-MAY-08:04 | 15.17 |
June | 1435625.83 | 790.33 | 08-JUN-15:15 | 18.00 |
July | 877787.48 | 712.09 | 05-JUL-08:05 | 20.17 |
August | 825954.66 | 682.45 | 09-AUG-08:05 | 19.50 |
September | 1158167.03 | 651.76 | 18-SEP-18:05 | 15.67 |
October | 3042568.10 | 1029.38 | 25-OCT-18:04 | 18.50 |
November | 22416000.00 | 1044.32 | 02-NOV-15:14 | 14.67 |
December | 62963485.66 | 1034.32 | 17-DEC-16:14 | 16.67 |
Annual Sum or Average | 0.345414E+09 | |||
Minimum of Months | 825954.66 | 651.76 | 12.00 | |
Maximum of Months | 91729967.97 | 1062.43 | 20.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194847E+09 | 1042.27 | 22-JAN-16:14 | 14.33 |
February | 96547308.11 | 975.01 | 16-FEB-19:04 | 13.83 |
March | 0.122719E+09 | 983.18 | 30-MAR-08:62 | 9.50 |
April | 12489536.82 | 1040.78 | 14-APR-18:04 | 12.83 |
May | 6944804.62 | 1009.72 | 24-MAY-08:53 | 18.00 |
June | 656069.02 | 584.60 | 02-JUN-08:53 | 19.00 |
July | 83648.88 | 392.19 | 06-JUL-08:54 | 20.00 |
August | 135331.90 | 368.75 | 21-AUG-08:55 | 19.00 |
September | 1087212.05 | 707.54 | 12-SEP-08:53 | 21.00 |
October | 3198736.12 | 982.55 | 18-OCT-08:53 | 25.00 |
November | 61092508.92 | 932.31 | 25-NOV-19:03 | 12.83 |
December | 0.158800E+09 | 1040.71 | 26-DEC-19:03 | 12.00 |
Annual Sum or Average | 0.658601E+09 | |||
Minimum of Months | 83648.88 | 368.75 | 9.50 | |
Maximum of Months | 0.194847E+09 | 1042.27 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1367390.98 | 403.25 | 16-JAN-09:05 | 15.33 |
February | 2569590.39 | 517.28 | 11-FEB-16:15 | 17.67 |
March | 12263227.84 | 449.98 | 17-MAR-15:15 | 16.00 |
April | 1886862.88 | 530.38 | 21-APR-15:15 | 14.67 |
May | 1711412.41 | 552.94 | 12-MAY-15:14 | 15.67 |
June | 1213584.91 | 472.85 | 08-JUN-18:03 | 15.67 |
July | 636529.26 | 377.33 | 09-JUL-18:05 | 17.83 |
August | 549434.68 | 361.14 | 30-AUG-08:05 | 19.50 |
September | 625824.15 | 395.33 | 16-SEP-18:04 | 15.83 |
October | 628766.92 | 523.22 | 24-OCT-15:15 | 19.00 |
November | 451896.88 | 505.43 | 11-NOV-16:15 | 16.67 |
December | 1561455.34 | 433.05 | 06-DEC-09:05 | 20.17 |
Annual Sum or Average | 25465976.64 | |||
Minimum of Months | 451896.88 | 361.14 | 14.67 | |
Maximum of Months | 12263227.84 | 552.94 | 20.17 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.831825E+10 | 8012.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.751062E+10 | 8012.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.834390E+10 | 8012.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.803622E+10 | 8012.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.833268E+10 | 8012.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.807308E+10 | 8012.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.829582E+10 | 8012.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.834710E+10 | 8012.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.803943E+10 | 8012.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.831505E+10 | 8012.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.806667E+10 | 8012.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.829582E+10 | 8012.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.979746E+11 | 0.143105E+12 | ||||
Minimum of Months | 0.751062E+10 | 8012.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.834710E+10 | 8012.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.376443E+09 | 362.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.339893E+09 | 362.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.377603E+09 | 362.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.363679E+09 | 362.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.377095E+09 | 362.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.365347E+09 | 362.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.375427E+09 | 362.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.377748E+09 | 362.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.363824E+09 | 362.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.376298E+09 | 362.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.365057E+09 | 362.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.375427E+09 | 362.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.443384E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.339893E+09 | 362.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.377748E+09 | 362.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435922E+09 | 419.88 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.393598E+09 | 419.88 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.437266E+09 | 419.88 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.421142E+09 | 419.88 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.436678E+09 | 419.88 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.423074E+09 | 419.88 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.434746E+09 | 419.88 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.437434E+09 | 419.88 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.421310E+09 | 419.88 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.435754E+09 | 419.88 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.422738E+09 | 419.88 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.434746E+09 | 419.88 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.513441E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.393598E+09 | 419.88 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.437434E+09 | 419.88 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.779939E+09 | 751.24 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.704214E+09 | 751.24 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.782343E+09 | 751.24 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.753495E+09 | 751.24 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.781291E+09 | 751.24 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.756951E+09 | 751.24 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.777835E+09 | 751.24 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.782643E+09 | 751.24 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.753796E+09 | 751.24 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.779638E+09 | 751.24 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.756350E+09 | 751.24 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.777835E+09 | 751.24 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.918633E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.704214E+09 | 751.24 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.782643E+09 | 751.24 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.178779E+09 | 172.20 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.161422E+09 | 172.20 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.179330E+09 | 172.20 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.172718E+09 | 172.20 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.179089E+09 | 172.20 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.173510E+09 | 172.20 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.178297E+09 | 172.20 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.179399E+09 | 172.20 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.172787E+09 | 172.20 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.178711E+09 | 172.20 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.173372E+09 | 172.20 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.178297E+09 | 172.20 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.210571E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.161422E+09 | 172.20 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.179399E+09 | 172.20 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332743E+09 | 320.50 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.300437E+09 | 320.50 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.333769E+09 | 320.50 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.321462E+09 | 320.50 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.333320E+09 | 320.50 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.322936E+09 | 320.50 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.331846E+09 | 320.50 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.333897E+09 | 320.50 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.321590E+09 | 320.50 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.332615E+09 | 320.50 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.322680E+09 | 320.50 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.331846E+09 | 320.50 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.391914E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.300437E+09 | 320.50 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.333897E+09 | 320.50 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.655111E+09 | 858.63 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.574266E+09 | 858.63 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.624344E+09 | 858.63 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.566640E+09 | 858.63 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.552569E+09 | 858.63 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.527160E+09 | 858.63 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.547482E+09 | 858.63 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.571464E+09 | 858.63 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.596750E+09 | 858.63 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.637646E+09 | 858.63 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.626704E+09 | 858.63 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.650646E+09 | 858.63 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.713078E+10 | 0.143405E+11 | ||||
Minimum of Months | 0.527160E+09 | 858.63 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.655111E+09 | 858.63 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.715035E+10 | 7223.65 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.643230E+10 | 7223.65 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.713189E+10 | 7223.65 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.682019E+10 | 7223.65 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.702725E+10 | 7223.65 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.679957E+10 | 7223.65 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.699156E+10 | 7223.65 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.706194E+10 | 7223.65 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.686790E+10 | 7223.65 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.713020E+10 | 7223.65 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.692020E+10 | 7223.65 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.712596E+10 | 7223.65 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.834593E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.643230E+10 | 7223.65 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.715035E+10 | 7223.65 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.122781E+10 | 1182.64 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.110860E+10 | 1182.64 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.123160E+10 | 1182.64 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.118618E+10 | 1182.64 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.122994E+10 | 1182.64 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.119162E+10 | 1182.64 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.122450E+10 | 1182.64 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.123207E+10 | 1182.64 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.118666E+10 | 1182.64 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.122734E+10 | 1182.64 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.119068E+10 | 1182.64 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.122450E+10 | 1182.64 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.144615E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.110860E+10 | 1182.64 | 0.00 | 0.00 | |
Maximum of Months | 0.123207E+10 | 1182.64 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138084E+10 | 1507.83 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.122350E+10 | 1507.83 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.133911E+10 | 1507.83 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.124953E+10 | 1507.83 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.125588E+10 | 1507.83 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.120407E+10 | 1507.83 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.124584E+10 | 1507.83 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.127861E+10 | 1507.83 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.128310E+10 | 1507.83 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.136375E+10 | 1507.83 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.132994E+10 | 1507.83 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.137988E+10 | 1507.83 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.155340E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.120407E+10 | 1507.83 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.138084E+10 | 1507.83 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138084E+10 | 1507.83 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.122350E+10 | 1507.83 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.133911E+10 | 1507.83 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.124953E+10 | 1507.83 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.125588E+10 | 1507.83 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.120407E+10 | 1507.83 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.124584E+10 | 1507.83 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.127861E+10 | 1507.83 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.128310E+10 | 1507.83 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.136375E+10 | 1507.83 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.132994E+10 | 1507.83 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.137988E+10 | 1507.83 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.155340E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.120407E+10 | 1507.83 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.138084E+10 | 1507.83 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.822206E+09 | 791.95 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.742377E+09 | 791.95 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.824741E+09 | 791.95 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.794330E+09 | 791.95 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.823632E+09 | 791.95 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.797973E+09 | 791.95 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.819989E+09 | 791.95 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.825057E+09 | 791.95 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.794646E+09 | 791.95 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.821890E+09 | 791.95 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.797339E+09 | 791.95 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.819989E+09 | 791.95 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.968417E+10 | 0.424019E+12 | ||||
Minimum of Months | 0.742377E+09 | 791.95 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.825057E+09 | 791.95 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.129945E+10 | 1251.64 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.117329E+10 | 1251.64 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.130346E+10 | 1251.64 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.125539E+10 | 1251.64 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.130170E+10 | 1251.64 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.126115E+10 | 1251.64 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.129595E+10 | 1251.64 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.130396E+10 | 1251.64 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.125589E+10 | 1251.64 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.129895E+10 | 1251.64 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.126015E+10 | 1251.64 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.129595E+10 | 1251.64 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.153053E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.117329E+10 | 1251.64 | 0.00 | 0.00 | |
Maximum of Months | 0.130396E+10 | 1251.64 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.831825E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.751062E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.834390E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.803622E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.833268E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.807308E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.829582E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.834710E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.803943E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.831505E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.806667E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.829582E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.979746E+11 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.751062E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.834710E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.376443E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 768505.50 | 0.304510E+09 |
February | 0.179968E+10 | 0.339893E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68599.50 | 0.261804E+09 |
March | 0.199990E+10 | 0.377603E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302297E+09 |
April | 0.192973E+10 | 0.363679E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 772927.81 | 0.222866E+09 |
May | 0.199475E+10 | 0.377095E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14888.02 | 0.209488E+09 |
June | 0.193394E+10 | 0.365347E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1018906.88 | 0.148222E+09 |
July | 0.199054E+10 | 0.375427E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5200198.91 | 0.117265E+09 |
August | 0.199896E+10 | 0.377748E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4369096.53 | 0.119258E+09 |
September | 0.192879E+10 | 0.363824E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7383122.46 | 0.152027E+09 |
October | 0.199148E+10 | 0.376298E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13485862.08 | 0.155694E+09 |
November | 0.192552E+10 | 0.365057E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624285.73 | 0.264438E+09 |
December | 0.199054E+10 | 0.375427E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 393212.11 | 0.295572E+09 |
Annual Sum or Average | 0.234744E+11 | 0.443384E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34099605.53 | 0.255344E+10 |
Minimum of Months | 0.179968E+10 | 0.339893E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117265E+09 |
Maximum of Months | 0.199990E+10 | 0.377748E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13485862.08 | 0.304510E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.435922E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1104322.86 | 0.113097E+09 |
February | 0.208403E+10 | 0.393598E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 172714.44 | 98703132.75 |
March | 0.231589E+10 | 0.437266E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256793.22 | 0.116037E+09 |
April | 0.223463E+10 | 0.421142E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156913.77 | 84292695.45 |
May | 0.230993E+10 | 0.436678E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 268474.54 | 82157354.38 |
June | 0.223950E+10 | 0.423074E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1420145.01 | 57634953.74 |
July | 0.230505E+10 | 0.434746E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4582963.31 | 44207623.22 |
August | 0.231480E+10 | 0.437434E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5203659.62 | 43281145.70 |
September | 0.223354E+10 | 0.421310E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3852156.21 | 53744984.22 |
October | 0.230614E+10 | 0.435754E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7574229.37 | 56330718.72 |
November | 0.222975E+10 | 0.422738E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 797282.93 | 97391605.61 |
December | 0.230505E+10 | 0.434746E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 968619.86 | 0.109449E+09 |
Annual Sum or Average | 0.271834E+11 | 0.513441E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27358275.13 | 0.956327E+09 |
Minimum of Months | 0.208403E+10 | 0.393598E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 172714.44 | 43281145.70 |
Maximum of Months | 0.231589E+10 | 0.437434E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7574229.37 | 0.116037E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.779939E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 596692.75 | 0.307713E+09 |
February | 0.440737E+09 | 0.704214E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67763.84 | 0.274216E+09 |
March | 0.489771E+09 | 0.782343E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42715.51 | 0.320044E+09 |
April | 0.472586E+09 | 0.753495E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519792.75 | 0.242208E+09 |
May | 0.488511E+09 | 0.781291E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244509E+09 |
June | 0.473617E+09 | 0.756951E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37553.95 | 0.177368E+09 |
July | 0.487480E+09 | 0.777835E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2836125.20 | 0.134408E+09 |
August | 0.489542E+09 | 0.782643E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3238501.73 | 0.128099E+09 |
September | 0.472357E+09 | 0.753796E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6424665.31 | 0.160935E+09 |
October | 0.487709E+09 | 0.779638E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12231128.25 | 0.164249E+09 |
November | 0.471555E+09 | 0.756350E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 583176.24 | 0.271698E+09 |
December | 0.487480E+09 | 0.777835E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425966.55 | 0.299529E+09 |
Annual Sum or Average | 0.574883E+10 | 0.918633E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27004082.07 | 0.272498E+10 |
Minimum of Months | 0.440737E+09 | 0.704214E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128099E+09 |
Maximum of Months | 0.489771E+09 | 0.782643E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12231128.25 | 0.320044E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.178779E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2092655.99 | 0.137851E+09 |
February | 0.339028E+09 | 0.161422E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 390803.88 | 0.119936E+09 |
March | 0.376747E+09 | 0.179330E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 705867.06 | 0.143904E+09 |
April | 0.363528E+09 | 0.172718E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2304503.68 | 99199975.79 |
May | 0.375778E+09 | 0.179089E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 654193.43 | 97964747.06 |
June | 0.364321E+09 | 0.173510E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2753412.26 | 66738270.08 |
July | 0.374985E+09 | 0.178297E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7956497.01 | 48214740.74 |
August | 0.376571E+09 | 0.179399E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9525322.36 | 45816385.47 |
September | 0.363352E+09 | 0.172787E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6819958.05 | 58942454.75 |
October | 0.375161E+09 | 0.178711E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12220728.65 | 63086035.31 |
November | 0.362735E+09 | 0.173372E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1662045.25 | 0.115501E+09 |
December | 0.374985E+09 | 0.178297E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2224452.66 | 0.131699E+09 |
Annual Sum or Average | 0.442217E+10 | 0.210571E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49310440.27 | 0.112886E+10 |
Minimum of Months | 0.339028E+09 | 0.161422E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 390803.88 | 45816385.47 |
Maximum of Months | 0.376747E+09 | 0.179399E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12220728.65 | 0.143904E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.332743E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 651493.86 | 0.436043E+09 |
February | 0.139600E+10 | 0.300437E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 85451.13 | 0.387466E+09 |
March | 0.155131E+10 | 0.333769E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456128E+09 |
April | 0.149688E+10 | 0.321462E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 632269.23 | 0.336467E+09 |
May | 0.154732E+10 | 0.333320E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336152E+09 |
June | 0.150015E+10 | 0.322936E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 51253.04 | 0.242220E+09 |
July | 0.154405E+10 | 0.331846E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 3872824.67 | 0.183519E+09 |
August | 0.155059E+10 | 0.333897E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 4422251.34 | 0.174905E+09 |
September | 0.149615E+10 | 0.321590E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 8772777.68 | 0.219749E+09 |
October | 0.154478E+10 | 0.332615E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 16700243.02 | 0.224320E+09 |
November | 0.149361E+10 | 0.322680E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 777532.37 | 0.375732E+09 |
December | 0.154405E+10 | 0.331846E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 489739.62 | 0.419730E+09 |
Annual Sum or Average | 0.182090E+11 | 0.391914E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 36455835.95 | 0.379243E+10 |
Minimum of Months | 0.139600E+10 | 0.300437E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174905E+09 |
Maximum of Months | 0.155131E+10 | 0.333897E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 16700243.02 | 0.456128E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.655111E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5201197.42 | 0.642724E+09 |
February | 0.236489E+11 | 0.574266E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 627336.86 | 0.553915E+09 |
March | 0.262800E+11 | 0.624344E+09 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 784527.07 | 0.647282E+09 |
April | 0.253579E+11 | 0.566640E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7808197.79 | 0.449155E+09 |
May | 0.262123E+11 | 0.552569E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3191212.81 | 0.430085E+09 |
June | 0.254132E+11 | 0.527160E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16957418.35 | 0.289903E+09 |
July | 0.261570E+11 | 0.547482E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44704994.42 | 0.210761E+09 |
August | 0.262677E+11 | 0.571464E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46050483.04 | 0.207954E+09 |
September | 0.253456E+11 | 0.596750E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25478744.81 | 0.270894E+09 |
October | 0.261693E+11 | 0.637646E+09 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42969501.08 | 0.294225E+09 |
November | 0.253025E+11 | 0.626704E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2451999.34 | 0.542332E+09 |
December | 0.261570E+11 | 0.650646E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2578488.30 | 0.620462E+09 |
Annual Sum or Average | 0.308468E+12 | 0.713078E+10 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198804E+09 | 0.515969E+10 |
Minimum of Months | 0.236489E+11 | 0.527160E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 627336.86 | 0.207954E+09 |
Maximum of Months | 0.262800E+11 | 0.655111E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46050483.04 | 0.647282E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.715035E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14898476.20 | 0.194508E+10 |
February | 0.702046E+11 | 0.643230E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2146056.22 | 0.169525E+10 |
March | 0.780153E+11 | 0.713189E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2908819.41 | 0.198534E+10 |
April | 0.752779E+11 | 0.682019E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17232595.24 | 0.142939E+10 |
May | 0.778146E+11 | 0.702725E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4537546.15 | 0.139950E+10 |
June | 0.754422E+11 | 0.679957E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25201368.64 | 0.982447E+09 |
July | 0.776503E+11 | 0.699156E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81233980.02 | 0.744037E+09 |
August | 0.779788E+11 | 0.706194E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90971883.06 | 0.726361E+09 |
September | 0.752414E+11 | 0.686790E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62032540.61 | 0.910286E+09 |
October | 0.776868E+11 | 0.713020E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118952E+09 | 0.968184E+09 |
November | 0.751137E+11 | 0.692020E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10144243.11 | 0.166909E+10 |
December | 0.776503E+11 | 0.712596E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11621617.51 | 0.188107E+10 |
Annual Sum or Average | 0.915726E+12 | 0.834593E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441881E+09 | 0.163360E+11 |
Minimum of Months | 0.702046E+11 | 0.643230E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2146056.22 | 0.726361E+09 |
Maximum of Months | 0.780153E+11 | 0.715035E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118952E+09 | 0.198534E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1024819.36 | 0.160388E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179544.45 | 0.140527E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 156150.01 | 0.167545E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 905334.49 | 0.116712E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71244.21 | 0.114229E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056037.89 | 73954490.90 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5286872.71 | 48907215.08 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6226654.46 | 45703247.69 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6257055.20 | 65417721.03 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10939434.69 | 67000135.63 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 802994.00 | 0.134492E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 886406.50 | 0.153300E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33792547.97 | 0.128818E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71244.21 | 45703247.69 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10939434.69 | 0.167545E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1221354.07 | 0.157293E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 216545.69 | 0.138765E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 213404.56 | 0.166899E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 836737.93 | 0.121536E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46911.45 | 0.121458E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 675949.01 | 88013021.68 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4384210.99 | 66932712.66 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5102343.37 | 61850009.36 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6033715.46 | 75266505.72 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10573415.00 | 74388163.19 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 969291.89 | 0.133530E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1226074.06 | 0.150732E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31499953.48 | 0.135666E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46911.45 | 61850009.36 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10573415.00 | 0.166899E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70455949.81 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62600102.94 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72361131.55 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 585.55 | 56890613.87 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57117096.49 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44665437.21 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45269.65 | 37096270.49 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30152.77 | 35927925.72 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 658366.01 | 41409195.32 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127568.88 | 41863570.80 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 451.49 | 62248645.03 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68444742.65 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1862394.35 | 0.651081E+09 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35927925.72 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127568.88 | 72361131.55 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 429516.59 | 43782868.13 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80702.91 | 38509451.96 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91571.66 | 46270829.87 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 314265.03 | 32334175.91 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34177.21 | 32300586.65 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 251171.09 | 22506005.12 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1348932.65 | 16375728.91 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630280.54 | 15133272.93 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1755160.50 | 19320724.46 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3172451.46 | 19846108.86 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 373961.01 | 36559786.27 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 462467.45 | 41703092.18 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9944658.11 | 0.364643E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34177.21 | 15133272.93 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3172451.46 | 46270829.87 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 994677.05 | 0.161232E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 174966.36 | 0.140803E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 145209.68 | 0.168324E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 850821.17 | 0.117386E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67907.13 | 0.114883E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 976568.31 | 74174679.49 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5202665.51 | 49314293.60 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6080991.73 | 46028876.60 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6227080.28 | 65361284.06 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10928287.08 | 67254945.19 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 786885.77 | 0.134888E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 870420.12 | 0.153869E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33306480.20 | 0.129352E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67907.13 | 46028876.60 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10928287.08 | 0.168324E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1133948.95 | 0.157510E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 163456.01 | 0.138381E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 147827.93 | 0.167177E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 647303.77 | 0.120484E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41439.63 | 0.120293E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 585092.94 | 84518778.34 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4206952.73 | 63906646.23 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4811192.52 | 59839933.15 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5923493.68 | 72963803.13 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10207462.72 | 73772709.11 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 910824.31 | 0.132616E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1063532.41 | 0.150684E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29842527.61 | 0.134215E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41439.63 | 59839933.15 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10207462.72 | 0.167177E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.122781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2051588.97 | 0.196657E+09 |
February | 0.348285E+10 | 0.110860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324049.11 | 0.172472E+09 |
March | 0.387034E+10 | 0.123160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478877.66 | 0.202707E+09 |
April | 0.373454E+10 | 0.118618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2050412.85 | 0.145574E+09 |
May | 0.386038E+10 | 0.122994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363416.98 | 0.143961E+09 |
June | 0.374269E+10 | 0.119162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1934918.55 | 99826914.81 |
July | 0.385223E+10 | 0.122450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7082010.33 | 75870239.68 |
August | 0.386853E+10 | 0.123207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7997525.27 | 73628251.46 |
September | 0.373273E+10 | 0.118666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6995414.37 | 92168984.52 |
October | 0.385404E+10 | 0.122734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13209510.62 | 98110836.89 |
November | 0.372639E+10 | 0.119068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1482162.53 | 0.169859E+09 |
December | 0.385223E+10 | 0.122450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1808561.19 | 0.191351E+09 |
Annual Sum or Average | 0.454292E+11 | 0.144615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45778448.41 | 0.166219E+10 |
Minimum of Months | 0.348285E+10 | 0.110860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324049.11 | 73628251.46 |
Maximum of Months | 0.387034E+10 | 0.123207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13209510.62 | 0.202707E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 976236.56 | 0.160707E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 173109.14 | 0.140717E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 142941.90 | 0.167995E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 839984.53 | 0.117662E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60641.58 | 0.115350E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 944002.07 | 74951019.19 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5035959.59 | 49759937.91 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5932965.27 | 46426543.25 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6148009.92 | 66196157.59 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10733157.21 | 67561540.82 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 772451.81 | 0.134923E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 848017.59 | 0.153542E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32607477.16 | 0.129579E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60641.58 | 46426543.25 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10733157.21 | 0.167995E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1209799.62 | 0.156945E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 224655.24 | 0.138662E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179926.98 | 0.167558E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 740121.17 | 0.123651E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38666.90 | 0.123627E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 599738.04 | 91104739.47 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4176817.72 | 70401251.82 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4845658.58 | 64668241.54 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5953047.72 | 76690913.13 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10439012.01 | 74614270.46 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 973140.86 | 0.133399E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1272717.34 | 0.150085E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30653302.19 | 0.137141E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38666.90 | 64668241.54 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10439012.01 | 0.167558E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 459829.66 | 83661376.10 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84451.98 | 73247478.02 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67243.56 | 87080514.77 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 421706.16 | 60343008.99 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31583.14 | 58718104.83 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 501401.75 | 37931905.41 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2607549.00 | 25239365.78 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3039482.74 | 23658816.12 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3138458.87 | 33838465.75 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5454319.80 | 34870589.85 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 371673.11 | 70082071.21 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 415606.61 | 79953384.08 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16593306.38 | 0.668625E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31583.14 | 23658816.12 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5454319.80 | 87080514.77 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.138084E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4811207.97 | 0.421043E+09 |
February | 0.415303E+11 | 0.122350E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 952190.04 | 0.372776E+09 |
March | 0.461508E+11 | 0.133911E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1205063.65 | 0.443926E+09 |
April | 0.445315E+11 | 0.124953E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4311996.61 | 0.320784E+09 |
May | 0.460320E+11 | 0.125588E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1057706.65 | 0.319086E+09 |
June | 0.446286E+11 | 0.120407E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5257054.48 | 0.225061E+09 |
July | 0.459349E+11 | 0.124584E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18372597.88 | 0.168569E+09 |
August | 0.461292E+11 | 0.127861E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22519945.22 | 0.161196E+09 |
September | 0.445099E+11 | 0.128310E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16275514.64 | 0.198098E+09 |
October | 0.459565E+11 | 0.136375E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32233399.72 | 0.206697E+09 |
November | 0.444343E+11 | 0.132994E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3918814.56 | 0.358940E+09 |
December | 0.459349E+11 | 0.137988E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5146433.06 | 0.404644E+09 |
Annual Sum or Average | 0.541708E+12 | 0.155340E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116062E+09 | 0.360082E+10 |
Minimum of Months | 0.415303E+11 | 0.120407E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 952190.04 | 0.161196E+09 |
Maximum of Months | 0.461508E+11 | 0.138084E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32233399.72 | 0.443926E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.138084E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4071825.90 | 0.434571E+09 |
February | 0.415303E+11 | 0.122350E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 787462.59 | 0.385513E+09 |
March | 0.461508E+11 | 0.133911E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 865045.37 | 0.458388E+09 |
April | 0.445315E+11 | 0.124953E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3410194.80 | 0.332633E+09 |
May | 0.460320E+11 | 0.125588E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 685821.56 | 0.331704E+09 |
June | 0.446286E+11 | 0.120407E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3865890.50 | 0.234828E+09 |
July | 0.459349E+11 | 0.124584E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15660338.20 | 0.176449E+09 |
August | 0.461292E+11 | 0.127861E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19344359.50 | 0.168313E+09 |
September | 0.445099E+11 | 0.128310E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14716366.78 | 0.207116E+09 |
October | 0.459565E+11 | 0.136375E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30031116.42 | 0.215457E+09 |
November | 0.444343E+11 | 0.132994E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3356887.95 | 0.371148E+09 |
December | 0.459349E+11 | 0.137988E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4284421.90 | 0.417440E+09 |
Annual Sum or Average | 0.541708E+12 | 0.155340E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101080E+09 | 0.373356E+10 |
Minimum of Months | 0.415303E+11 | 0.120407E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 685821.56 | 0.168313E+09 |
Maximum of Months | 0.461508E+11 | 0.138084E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30031116.42 | 0.458388E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.822206E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 602782.35 | 0.447989E+09 |
February | 0.369574E+10 | 0.742377E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 79978.15 | 0.398163E+09 |
March | 0.410691E+10 | 0.824741E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468497E+09 |
April | 0.396281E+10 | 0.794330E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 607345.51 | 0.346411E+09 |
May | 0.409635E+10 | 0.823632E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346242E+09 |
June | 0.397146E+10 | 0.797973E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 43419.89 | 0.250397E+09 |
July | 0.408770E+10 | 0.819989E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3741180.29 | 0.190508E+09 |
August | 0.410499E+10 | 0.825057E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4235818.29 | 0.181662E+09 |
September | 0.396089E+10 | 0.794646E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 8759331.90 | 0.227313E+09 |
October | 0.408962E+10 | 0.821890E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16669745.57 | 0.231919E+09 |
November | 0.395417E+10 | 0.797339E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 744940.56 | 0.386412E+09 |
December | 0.408770E+10 | 0.819989E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 450896.12 | 0.431365E+09 |
Annual Sum or Average | 0.482060E+11 | 0.968417E+10 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 35935438.63 | 0.390688E+10 |
Minimum of Months | 0.369574E+10 | 0.742377E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181662E+09 |
Maximum of Months | 0.410691E+10 | 0.825057E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16669745.57 | 0.468497E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.129945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168925.81 | 0.383327E+09 |
February | 0.368610E+10 | 0.117329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162799.48 | 0.341107E+09 |
March | 0.409620E+10 | 0.130346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48328.38 | 0.400496E+09 |
April | 0.395248E+10 | 0.125539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758904.24 | 0.307753E+09 |
May | 0.408566E+10 | 0.130170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308834E+09 |
June | 0.396110E+10 | 0.126115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41525.03 | 0.231682E+09 |
July | 0.407704E+10 | 0.129595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3642446.76 | 0.183009E+09 |
August | 0.409429E+10 | 0.130396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4119875.68 | 0.174790E+09 |
September | 0.395056E+10 | 0.125589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8682812.25 | 0.212393E+09 |
October | 0.407896E+10 | 0.129895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16427743.08 | 0.214158E+09 |
November | 0.394385E+10 | 0.126015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851717.33 | 0.338947E+09 |
December | 0.407704E+10 | 0.129595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799424.98 | 0.373623E+09 |
Annual Sum or Average | 0.480803E+11 | 0.153053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36704503.02 | 0.347012E+10 |
Minimum of Months | 0.368610E+10 | 0.117329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174790E+09 |
Maximum of Months | 0.409620E+10 | 0.130396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16427743.08 | 0.400496E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 8012.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 8012.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 8012.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 8012.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 8012.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 8012.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 8012.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 8012.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 8012.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 8012.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 8012.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 8012.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 8012.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 8012.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 362.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 14-JAN-11:00 | 250.88 | 08-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 362.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 01-FEB-12:00 | 205.28 | 04-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 362.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 212.13 | 08-MAR-02:00 |
April | 1169.53 | 01-APR-00:10 | 362.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | 26-APR-13:00 | 170.89 | 01-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 362.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 03-MAY-12:00 | 163.28 | 19-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 362.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 29-JUN-11:00 | 126.93 | 13-JUN-04:20 |
July | 1169.53 | 01-JUL-00:10 | 362.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.56 | 19-JUL-11:00 | 112.73 | 06-JUL-01:00 |
August | 1169.53 | 01-AUG-00:10 | 362.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 14-AUG-11:00 | 103.18 | 28-AUG-03:00 |
September | 1169.53 | 01-SEP-00:10 | 362.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 | 29-SEP-11:00 | 134.00 | 20-SEP-03:00 |
October | 1169.53 | 01-OCT-23:10 | 362.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 16-OCT-11:00 | 160.86 | 30-OCT-03:00 |
November | 1169.53 | 01-NOV-00:10 | 362.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 19-NOV-13:00 | 197.62 | 29-NOV-23:00 |
December | 1169.53 | 01-DEC-00:10 | 362.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 16-DEC-13:00 | 206.94 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 362.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.18 | |||||
Maximum of Months | 1169.53 | 362.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 250.88 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 419.88 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.66 | 18-JAN-13:00 | 100.71 | 08-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 419.88 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 01-FEB-12:00 | 83.03 | 04-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 419.88 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 11-MAR-11:50 | 86.52 | 08-MAR-02:00 |
April | 1354.32 | 01-APR-00:10 | 419.88 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.45 | 26-APR-13:00 | 68.81 | 01-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 419.88 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 03-MAY-12:00 | 67.99 | 19-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 419.88 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 29-JUN-11:00 | 53.28 | 13-JUN-04:40 |
July | 1354.32 | 01-JUL-00:10 | 419.88 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.84 | 19-JUL-11:00 | 45.96 | 06-JUL-01:00 |
August | 1354.32 | 01-AUG-00:10 | 419.88 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 | 14-AUG-11:00 | 41.04 | 24-AUG-02:00 |
September | 1354.32 | 01-SEP-00:10 | 419.88 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 29-SEP-11:00 | 54.38 | 20-SEP-03:00 |
October | 1354.32 | 01-OCT-23:10 | 419.88 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 16-OCT-11:00 | 64.39 | 27-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 419.88 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 | 19-NOV-13:00 | 77.20 | 29-NOV-23:00 |
December | 1354.32 | 01-DEC-00:10 | 419.88 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 16-DEC-13:00 | 82.82 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 41.04 | |||||
Maximum of Months | 1354.32 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 100.71 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 751.24 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 | 13-JAN-14:00 | 252.08 | 08-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 751.24 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.63 | 01-FEB-12:00 | 209.30 | 04-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 751.24 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 11-MAR-11:50 | 215.69 | 08-MAR-02:00 |
April | 286.42 | 01-APR-00:10 | 751.24 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 26-APR-13:00 | 176.11 | 01-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 751.24 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 176.60 | 19-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 751.24 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 29-JUN-11:00 | 143.66 | 13-JUN-04:50 |
July | 286.42 | 01-JUL-00:10 | 751.24 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 19-JUL-12:00 | 119.94 | 06-JUL-01:00 |
August | 286.42 | 01-AUG-00:10 | 751.24 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.56 | 18-AUG-12:00 | 108.57 | 31-AUG-04:00 |
September | 286.42 | 01-SEP-00:10 | 751.24 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.05 | 29-SEP-11:00 | 142.58 | 20-SEP-03:00 |
October | 286.42 | 01-OCT-23:10 | 751.24 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.97 | 16-OCT-11:00 | 166.35 | 12-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 751.24 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 19-NOV-13:00 | 190.11 | 23-NOV-22:00 |
December | 286.42 | 01-DEC-00:10 | 751.24 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 | 16-DEC-13:00 | 210.85 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.57 | |||||
Maximum of Months | 286.42 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 130.97 | 252.08 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 172.20 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 13-JAN-14:00 | 132.04 | 08-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 172.20 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 | 01-FEB-12:00 | 104.75 | 04-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 172.20 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 11-MAR-11:50 | 110.95 | 08-MAR-02:00 |
April | 220.32 | 01-APR-00:10 | 172.20 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 | 26-APR-13:00 | 89.93 | 01-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 172.20 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 | 03-MAY-12:00 | 85.24 | 27-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 172.20 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 | 29-JUN-11:00 | 66.30 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 172.20 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.69 | 19-JUL-11:00 | 55.41 | 06-JUL-01:00 |
August | 220.32 | 01-AUG-00:10 | 172.20 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.30 | 14-AUG-11:00 | 48.38 | 28-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 172.20 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.03 | 29-SEP-11:00 | 66.14 | 20-SEP-03:00 |
October | 220.32 | 01-OCT-23:10 | 172.20 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.62 | 16-OCT-11:00 | 79.67 | 27-OCT-04:30 |
November | 220.32 | 01-NOV-00:10 | 172.20 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 | 19-NOV-13:00 | 94.24 | 29-NOV-23:00 |
December | 220.32 | 01-DEC-00:10 | 172.20 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.12 | 16-DEC-13:00 | 104.27 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 172.20 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 | 48.38 | |||||
Maximum of Months | 220.32 | 172.20 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 86.62 | 132.04 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 320.50 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 28.61 | 14-JAN-11:00 | 359.33 | 08-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 320.50 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 28.46 | 01-FEB-12:00 | 291.33 | 04-FEB-06:00 |
March | 907.20 | 01-MAR-00:10 | 320.50 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 308.89 | 08-MAR-02:00 |
April | 907.20 | 01-APR-00:10 | 320.50 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 42.57 | 26-APR-13:00 | 258.41 | 01-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 320.50 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 243.69 | 15-MAY-05:00 |
June | 907.20 | 01-JUN-00:10 | 320.50 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 14.24 | 29-JUN-11:00 | 196.16 | 13-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 320.50 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 56.64 | 19-JUL-12:00 | 163.77 | 06-JUL-01:00 |
August | 907.20 | 01-AUG-00:10 | 320.50 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 56.75 | 18-AUG-12:00 | 148.24 | 31-AUG-04:00 |
September | 907.20 | 01-SEP-00:10 | 320.50 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 165.28 | 29-SEP-11:00 | 194.79 | 20-SEP-04:00 |
October | 907.20 | 01-OCT-23:10 | 320.50 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 178.82 | 16-OCT-11:00 | 227.36 | 30-OCT-04:00 |
November | 907.20 | 01-NOV-00:10 | 320.50 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 42.59 | 19-NOV-13:00 | 259.62 | 24-NOV-01:00 |
December | 907.20 | 01-DEC-00:10 | 320.50 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 28.68 | 16-DEC-13:00 | 292.06 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 148.24 | ||||||
Maximum of Months | 907.20 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 178.82 | 359.33 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 858.63 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.95 | 15-JAN-14:00 | 559.98 | 08-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 858.63 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.43 | 01-FEB-12:00 | 473.73 | 04-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 858.63 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.22 | 11-MAR-11:50 | 495.26 | 08-MAR-02:00 |
April | 15368.40 | 01-APR-00:10 | 858.63 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.79 | 26-APR-13:00 | 386.85 | 01-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 858.63 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.46 | 03-MAY-12:00 | 381.74 | 19-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 858.63 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.47 | 29-JUN-11:00 | 301.84 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 858.63 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.93 | 19-JUL-11:00 | 250.43 | 06-JUL-01:00 |
August | 15368.40 | 01-AUG-00:10 | 858.63 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.96 | 14-AUG-11:00 | 227.61 | 28-AUG-04:20 |
September | 15368.40 | 01-SEP-00:10 | 858.63 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.79 | 29-SEP-10:50 | 304.84 | 20-SEP-03:00 |
October | 15368.40 | 01-OCT-23:10 | 858.63 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 342.31 | 16-OCT-11:00 | 365.81 | 30-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 858.63 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.36 | 19-NOV-13:00 | 431.81 | 29-NOV-23:00 |
December | 15368.40 | 01-DEC-00:10 | 858.63 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.60 | 05-DEC-09:55 | 473.57 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 858.63 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 42.22 | 227.61 | |||||
Maximum of Months | 15368.40 | 858.63 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 342.31 | 559.98 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 7223.65 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.88 | 18-JAN-13:00 | 1693.77 | 08-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 7223.65 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.40 | 01-FEB-12:00 | 1413.27 | 04-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 7223.65 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.51 | 11-MAR-11:50 | 1473.82 | 08-MAR-02:00 |
April | 45622.98 | 01-APR-00:10 | 7223.65 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.72 | 26-APR-13:00 | 1183.92 | 01-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 7223.65 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.46 | 03-MAY-12:00 | 1160.30 | 19-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 7223.65 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.56 | 29-JUN-11:00 | 927.98 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 7223.65 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.69 | 19-JUL-11:00 | 780.45 | 06-JUL-01:00 |
August | 45622.98 | 01-AUG-00:10 | 7223.65 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 451.39 | 14-AUG-11:00 | 704.70 | 31-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 7223.65 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 963.73 | 29-SEP-11:00 | 929.28 | 20-SEP-03:00 |
October | 45622.98 | 01-OCT-23:10 | 7223.65 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.37 | 16-OCT-11:00 | 1101.86 | 27-OCT-04:40 |
November | 45622.98 | 01-NOV-00:10 | 7223.65 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.36 | 19-NOV-13:00 | 1301.46 | 29-NOV-23:00 |
December | 45622.98 | 01-DEC-00:10 | 7223.65 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.47 | 16-DEC-13:00 | 1408.03 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 7223.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 138.51 | 704.70 | |||||
Maximum of Months | 45622.98 | 7223.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.37 | 1693.77 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.64 | 14-JAN-10:52 | 146.71 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-09:52 | 115.41 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 11-MAR-10:50 | 123.45 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.21 | 30-APR-09:52 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 03-MAY-09:52 | 93.35 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 | 29-JUN-09:50 | 71.39 | 13-JUN-04:40 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 19-JUL-09:50 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.05 | 15-AUG-09:52 | 56.91 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.09 | 29-SEP-09:50 | 70.90 | 20-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 16-OCT-11:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-09:55 | 100.72 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 05-DEC-10:00 | 115.70 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 56.57 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 146.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 | 14-JAN-10:52 | 146.70 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.24 | 01-FEB-12:00 | 115.40 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 11-MAR-10:52 | 123.44 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 30-APR-09:52 | 100.24 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 03-MAY-09:52 | 93.35 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 | 29-JUN-09:50 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.61 | 19-JUL-09:50 | 64.58 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.95 | 15-AUG-09:52 | 62.09 | 21-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.48 | 29-SEP-09:52 | 70.89 | 20-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.72 | 16-OCT-09:51 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-09:58 | 100.71 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 05-DEC-10:00 | 115.69 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 62.09 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 87.72 | 146.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 51.30 | 08-JAN-07:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 42.85 | 04-FEB-06:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 44.64 | 08-MAR-02:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 26-APR-13:00 | 36.09 | 01-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 35.74 | 15-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 29.91 | 13-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 19-JUL-12:00 | 26.48 | 06-JUL-01:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 18-AUG-12:00 | 24.49 | 31-AUG-04:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 29-SEP-11:00 | 30.55 | 20-SEP-03:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 16-OCT-11:00 | 34.90 | 30-OCT-04:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 19-NOV-13:00 | 39.13 | 24-NOV-01:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 43.39 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 51.30 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 13-JAN-14:00 | 40.94 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 01-FEB-12:00 | 32.21 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 11-MAR-10:52 | 34.45 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 | 26-APR-13:00 | 27.98 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 | 03-MAY-12:50 | 26.05 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 29-JUN-09:50 | 19.93 | 13-JUN-04:40 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 19-JUL-09:50 | 17.24 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 15-AUG-09:52 | 16.41 | 21-AUG-20:10 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 29-SEP-09:52 | 19.79 | 20-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 16-OCT-09:51 | 23.96 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 19-NOV-10:00 | 28.25 | 08-NOV-05:40 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 05-DEC-10:00 | 32.29 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 | 16.41 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 40.94 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 | 14-JAN-10:52 | 146.71 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-09:52 | 115.41 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 11-MAR-10:50 | 123.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 26-APR-13:00 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 03-MAY-09:52 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 | 29-JUN-09:50 | 71.39 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 19-JUL-09:50 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 | 15-AUG-09:50 | 61.40 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.09 | 29-SEP-09:50 | 70.90 | 20-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 16-OCT-11:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-10:00 | 100.72 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 05-DEC-10:00 | 115.70 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 56.57 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 146.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 | 14-JAN-10:52 | 146.70 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-10:00 | 115.40 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 11-MAR-10:50 | 123.44 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 26-APR-13:00 | 100.24 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 03-MAY-09:52 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 | 29-JUN-09:50 | 71.39 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.61 | 19-JUL-09:50 | 59.15 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 | 15-AUG-09:50 | 61.96 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.08 | 29-SEP-09:50 | 70.89 | 20-SEP-03:50 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 16-OCT-11:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 19-NOV-10:00 | 100.71 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 05-DEC-10:00 | 115.69 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 59.15 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 146.70 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1182.64 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 | 13-JAN-14:00 | 179.36 | 08-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1182.64 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 | 01-FEB-12:00 | 147.34 | 04-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1182.64 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 11-MAR-11:50 | 151.89 | 08-MAR-02:00 |
April | 2263.36 | 01-APR-00:10 | 1182.64 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 26-APR-13:00 | 120.61 | 01-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1182.64 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 03-MAY-12:00 | 119.70 | 27-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1182.64 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.69 | 29-JUN-11:00 | 93.50 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1182.64 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.47 | 19-JUL-11:00 | 80.55 | 06-JUL-01:00 |
August | 2263.36 | 01-AUG-00:10 | 1182.64 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.80 | 14-AUG-11:00 | 72.03 | 24-AUG-02:00 |
September | 2263.36 | 01-SEP-00:10 | 1182.64 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.01 | 29-SEP-11:00 | 95.16 | 20-SEP-03:00 |
October | 2263.36 | 01-OCT-23:10 | 1182.64 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.77 | 16-OCT-11:00 | 113.86 | 30-OCT-03:00 |
November | 2263.36 | 01-NOV-00:10 | 1182.64 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.48 | 19-NOV-13:00 | 131.89 | 29-NOV-23:00 |
December | 2263.36 | 01-DEC-00:10 | 1182.64 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 | 16-DEC-13:00 | 146.77 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1182.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 72.03 | ||||
Maximum of Months | 2263.36 | 1182.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.77 | 179.36 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 14-JAN-10:52 | 147.18 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 01-FEB-09:52 | 115.86 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 11-MAR-10:50 | 123.90 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 30-APR-09:52 | 100.70 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 03-MAY-09:52 | 93.79 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 29-JUN-09:50 | 71.83 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.23 | 19-JUL-09:50 | 56.99 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.49 | 15-AUG-09:52 | 56.01 | 28-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.72 | 29-SEP-09:50 | 71.33 | 20-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 | 16-OCT-11:00 | 86.28 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 19-NOV-09:55 | 101.16 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 | 05-DEC-10:00 | 116.15 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 56.01 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 | 147.18 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 | 14-JAN-10:52 | 147.17 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 | 01-FEB-12:00 | 115.85 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 | 11-MAR-10:52 | 123.89 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 | 30-APR-09:52 | 100.68 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 | 03-MAY-09:52 | 93.79 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 29-JUN-09:50 | 71.82 | 13-JUN-04:50 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.23 | 19-JUL-09:50 | 67.82 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 15-AUG-09:52 | 65.66 | 26-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.88 | 29-SEP-09:52 | 71.32 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.24 | 16-OCT-09:51 | 86.27 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 19-NOV-09:58 | 101.15 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.92 | 05-DEC-10:00 | 116.14 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 | 65.66 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 87.24 | 147.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 14-JAN-10:52 | 75.30 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 01-FEB-09:52 | 59.28 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 | 11-MAR-10:50 | 63.39 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 26-APR-13:00 | 51.52 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | 03-MAY-09:52 | 47.99 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 29-JUN-09:50 | 36.75 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 19-JUL-09:50 | 29.16 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 15-AUG-09:52 | 29.37 | 28-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 29-SEP-09:50 | 36.49 | 20-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 16-OCT-11:00 | 44.14 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 | 19-NOV-10:30 | 52.01 | 05-NOV-02:40 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 05-DEC-10:00 | 59.43 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | 29.16 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 75.30 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1507.83 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.52 | 14-JAN-11:50 | 377.35 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 1507.83 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.59 | 01-FEB-12:00 | 313.95 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 1507.83 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 11-MAR-11:50 | 330.37 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 1507.83 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.07 | 26-APR-13:00 | 271.44 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 1507.83 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 03-MAY-12:00 | 261.29 | 27-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 1507.83 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.82 | 29-JUN-10:50 | 209.71 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 1507.83 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.03 | 19-JUL-10:50 | 175.83 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 1507.83 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.83 | 14-AUG-10:50 | 157.38 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 1507.83 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.24 | 29-SEP-10:50 | 207.12 | 20-SEP-03:10 |
October | 26988.77 | 01-OCT-23:10 | 1507.83 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.65 | 16-OCT-11:00 | 242.99 | 12-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 1507.83 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.88 | 19-NOV-13:00 | 290.03 | 29-NOV-23:00 |
December | 26988.77 | 01-DEC-00:10 | 1507.83 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.80 | 19-DEC-13:00 | 312.27 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1507.83 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 157.38 | |||||
Maximum of Months | 26988.77 | 1507.83 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 244.65 | 377.35 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1507.83 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.68 | 14-JAN-11:50 | 382.60 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 1507.83 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.46 | 01-FEB-12:00 | 317.98 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 1507.83 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.16 | 11-MAR-11:50 | 335.65 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 1507.83 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 | 26-APR-13:00 | 277.30 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 1507.83 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 | 03-MAY-12:00 | 265.26 | 27-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 1507.83 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.13 | 29-JUN-10:50 | 213.73 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 1507.83 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.37 | 19-JUL-10:50 | 179.29 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 1507.83 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.49 | 14-AUG-10:50 | 160.49 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 1507.83 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.88 | 29-SEP-10:50 | 210.84 | 20-SEP-03:00 |
October | 26988.77 | 01-OCT-23:10 | 1507.83 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.36 | 16-OCT-11:00 | 246.84 | 12-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 1507.83 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 | 19-NOV-13:00 | 294.92 | 29-NOV-23:00 |
December | 26988.77 | 01-DEC-00:10 | 1507.83 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.01 | 19-DEC-13:00 | 316.44 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1507.83 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 | 160.49 | |||||
Maximum of Months | 26988.77 | 1507.83 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 240.36 | 382.60 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 791.95 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 27.82 | 14-JAN-11:50 | 367.57 | 08-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 791.95 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 27.69 | 01-FEB-12:00 | 298.31 | 04-FEB-06:00 |
March | 2401.70 | 01-MAR-00:10 | 791.95 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 316.24 | 08-MAR-02:00 |
April | 2401.70 | 01-APR-00:10 | 791.95 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 42.05 | 26-APR-13:00 | 264.72 | 01-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 791.95 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 249.79 | 15-MAY-02:00 |
June | 2401.70 | 01-JUN-00:10 | 791.95 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 13.20 | 29-JUN-11:00 | 201.35 | 13-JUN-04:10 |
July | 2401.70 | 01-JUL-00:10 | 791.95 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 56.41 | 19-JUL-12:00 | 168.34 | 06-JUL-01:00 |
August | 2401.70 | 01-AUG-00:10 | 791.95 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 56.52 | 18-AUG-12:00 | 152.51 | 31-AUG-04:00 |
September | 2401.70 | 01-SEP-00:10 | 791.95 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 167.11 | 29-SEP-11:00 | 199.95 | 20-SEP-04:00 |
October | 2401.70 | 01-OCT-23:10 | 791.95 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 180.90 | 16-OCT-11:00 | 233.15 | 30-OCT-04:00 |
November | 2401.70 | 01-NOV-00:10 | 791.95 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 42.10 | 19-NOV-13:00 | 266.02 | 24-NOV-01:00 |
December | 2401.70 | 01-DEC-00:10 | 791.95 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 27.92 | 16-DEC-13:00 | 299.01 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 791.95 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 152.51 | ||||||
Maximum of Months | 2401.70 | 791.95 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 180.90 | 367.57 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1251.64 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.40 | 14-JAN-10:52 | 319.51 | 08-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1251.64 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.98 | 01-FEB-12:00 | 270.51 | 04-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1251.64 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 11-MAR-10:52 | 277.00 | 08-MAR-02:00 |
April | 2395.44 | 01-APR-00:10 | 1251.64 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.99 | 26-APR-13:00 | 221.60 | 01-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1251.64 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 226.51 | 27-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1251.64 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 29-JUN-11:00 | 181.22 | 13-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1251.64 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.03 | 19-JUL-12:00 | 160.03 | 06-JUL-01:00 |
August | 2395.44 | 01-AUG-00:10 | 1251.64 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.14 | 18-AUG-12:00 | 144.75 | 28-AUG-03:00 |
September | 2395.44 | 01-SEP-00:10 | 1251.64 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.41 | 29-SEP-11:00 | 181.88 | 20-SEP-03:00 |
October | 2395.44 | 01-OCT-23:10 | 1251.64 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.91 | 16-OCT-11:00 | 213.73 | 27-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1251.64 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 | 19-NOV-13:00 | 247.98 | 29-NOV-23:00 |
December | 2395.44 | 01-DEC-00:10 | 1251.64 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.72 | 16-DEC-13:00 | 268.57 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1251.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.75 | ||||
Maximum of Months | 2395.44 | 1251.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.91 | 319.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13975.35 | 22-JAN-11:35 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13598.79 | 01-FEB-19:10 | 62621.41 | 49853.94 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12991.18 | 12-MAR-10:35 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13095.04 | 30-APR-10:35 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12973.41 | 04-MAY-18:10 | 62621.41 | 49853.94 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12996.09 | 25-JUN-10:35 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13798.19 | 23-JUL-10:35 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13802.30 | 19-AUG-10:35 | 7667.93 | 4451.29 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14530.60 | 30-SEP-10:35 | 7667.93 | 4451.29 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14950.15 | 15-OCT-10:35 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14447.12 | 19-NOV-11:35 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13857.84 | 07-DEC-19:10 | 62621.41 | 49853.94 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12973.41 | 7667.93 | 4451.29 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14950.15 | 62621.41 | 49853.94 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2750.20 | 14-JAN-12:40 | 389.84 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 |
February | 2440.55 | 02-FEB-12:40 | 259.90 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 |
March | 2146.42 | 11-MAR-13:00 | 389.84 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
April | 1555.26 | 08-APR-13:00 | 389.84 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 |
May | 1433.75 | 04-MAY-10:35 | 519.79 | 201.44 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 |
June | 1393.94 | 29-JUN-18:10 | 6367.45 | 2256.13 | 4546.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 |
July | 1512.22 | 30-JUL-10:35 | 779.69 | 241.73 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
August | 1669.96 | 20-AUG-12:00 | 389.84 | 120.86 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 |
September | 2938.87 | 30-SEP-12:00 | 389.84 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 89.37 | 0.00 |
October | 3404.38 | 16-OCT-12:20 | 259.90 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 126.06 | 0.00 |
November | 3029.30 | 19-NOV-12:30 | 389.84 | 120.86 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 | 0.00 |
December | 2900.27 | 19-DEC-12:50 | 259.90 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1393.94 | 259.90 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3404.38 | 6367.45 | 2256.13 | 4546.63 | 0.00 | 0.00 | 0.00 | 0.00 | 126.06 | 54.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1422.75 | 18-JAN-19:10 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 |
February | 1426.18 | 03-FEB-21:00 | 1053.36 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.82 |
March | 1448.06 | 23-MAR-18:10 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 |
April | 1498.06 | 26-APR-18:10 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 |
May | 1498.41 | 04-MAY-18:10 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 |
June | 1526.20 | 29-JUN-18:10 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 |
July | 1566.69 | 19-JUL-18:10 | 6320.16 | 2239.37 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 1569.53 | 17-AUG-18:10 | 6320.16 | 2239.37 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 |
September | 1624.79 | 30-SEP-10:35 | 902.88 | 233.27 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.12 | 0.00 |
October | 1630.94 | 16-OCT-18:10 | 6320.16 | 2239.37 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 0.00 |
November | 1490.81 | 19-NOV-11:35 | 902.88 | 279.92 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 0.00 |
December | 1445.77 | 05-DEC-21:00 | 1053.36 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1422.75 | 902.88 | 233.27 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1630.94 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 34.12 | 46.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 742.97 | 18-JAN-22:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.87 |
February | 613.89 | 03-FEB-21:00 | 222.77 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.39 |
March | 576.82 | 24-MAR-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.90 |
April | 766.93 | 26-APR-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.45 |
May | 900.50 | 04-MAY-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.45 |
June | 993.20 | 30-JUN-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.34 |
July | 1109.04 | 19-JUL-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 |
August | 1090.05 | 18-AUG-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 |
September | 1249.36 | 29-SEP-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 0.00 |
October | 1315.62 | 16-OCT-20:00 | 222.77 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.85 |
November | 692.52 | 01-NOV-20:00 | 222.77 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.60 |
December | 748.15 | 05-DEC-22:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 576.82 | 222.77 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1315.62 | 254.59 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 120.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 816.48 | 20-JAN-11:35 | 97.92 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | 0.00 |
February | 791.43 | 01-FEB-11:35 | 97.92 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 | 0.00 |
March | 804.52 | 19-MAR-10:35 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 |
April | 849.94 | 30-APR-10:35 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 | 0.00 |
May | 856.02 | 04-MAY-10:35 | 97.92 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 0.00 |
June | 888.14 | 25-JUN-10:35 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 8.27 | 0.00 |
July | 922.93 | 23-JUL-10:35 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 0.00 |
August | 917.76 | 19-AUG-10:35 | 146.88 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 0.00 |
September | 965.25 | 30-SEP-10:35 | 146.88 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 0.00 |
October | 954.92 | 15-OCT-10:35 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 56.76 | 0.00 |
November | 847.19 | 19-NOV-11:35 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 0.00 |
December | 822.50 | 19-DEC-11:35 | 97.92 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 791.43 | 97.92 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 965.25 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 56.76 | 10.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37781.99 | 24-JAN-21:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.34 |
February | 37652.00 | 03-FEB-21:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 164.38 |
March | 37889.22 | 23-MAR-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 148.51 |
April | 38173.57 | 26-APR-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 |
May | 38181.86 | 04-MAY-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 |
June | 38202.80 | 30-JUN-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 117.91 |
July | 38446.26 | 19-JUL-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 |
August | 38408.97 | 18-AUG-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.05 |
September | 38719.38 | 29-SEP-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.22 | 0.00 |
October | 38627.98 | 16-OCT-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 |
November | 37658.51 | 28-NOV-21:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 164.66 |
December | 37898.69 | 05-DEC-21:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 118.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37652.00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38719.38 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.22 | 164.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11903.69 | 14-JAN-11:35 | 10245.60 | 104.94 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.43 | 0.00 |
February | 11169.05 | 04-FEB-11:35 | 10245.60 | 104.94 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.28 |
March | 11298.53 | 11-MAR-11:35 | 10245.60 | 104.94 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 0.00 |
April | 10172.57 | 08-APR-10:35 | 10245.60 | 104.94 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
May | 9707.00 | 04-MAY-18:10 | 83672.40 | 2467.54 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 |
June | 9720.71 | 29-JUN-18:10 | 83672.40 | 2053.61 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
July | 10138.32 | 30-JUL-10:35 | 10245.60 | 125.93 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 84.11 | 0.00 |
August | 10483.31 | 27-AUG-10:35 | 10245.60 | 125.93 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 | 0.00 |
September | 12022.67 | 30-SEP-10:35 | 10245.60 | 104.94 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 194.73 | 0.00 |
October | 12668.43 | 15-OCT-10:35 | 10245.60 | 125.93 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 208.61 | 0.00 |
November | 12492.00 | 19-NOV-11:35 | 10245.60 | 125.93 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 61.29 | 0.00 |
December | 11818.23 | 30-DEC-11:35 | 10245.60 | 104.94 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9707.00 | 10245.60 | 104.94 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12668.43 | 83672.40 | 2467.54 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 208.61 | 69.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31090.03 | 22-JAN-11:35 | 30415.32 | 4141.56 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.61 |
February | 30355.51 | 04-FEB-11:35 | 30415.32 | 3451.30 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.08 |
March | 30540.28 | 11-MAR-11:35 | 30415.32 | 3451.30 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 122.77 | 0.00 |
April | 30667.85 | 26-APR-18:10 | 248391.78 | 42811.95 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.84 |
May | 30936.96 | 04-MAY-18:10 | 248391.78 | 42347.87 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.34 |
June | 31182.42 | 29-JUN-18:10 | 248391.78 | 41376.36 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.34 |
July | 31895.09 | 19-JUL-18:10 | 212907.24 | 35652.63 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
August | 31846.86 | 17-AUG-18:10 | 212907.24 | 36677.16 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.80 |
September | 33861.20 | 30-SEP-10:35 | 30415.32 | 3451.30 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 552.11 | 0.00 |
October | 34450.61 | 15-OCT-10:35 | 30415.32 | 4141.56 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 617.15 | 0.00 |
November | 32618.81 | 19-NOV-11:35 | 30415.32 | 4141.56 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 224.74 | 0.00 |
December | 30915.94 | 30-DEC-11:35 | 30415.32 | 3451.30 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 30355.51 | 30415.32 | 3451.30 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34450.61 | 248391.78 | 42811.95 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 617.15 | 449.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2805.52 | 14-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
February | 2811.90 | 03-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 |
March | 2487.52 | 19-MAR-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.99 |
April | 2631.65 | 01-APR-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 |
May | 2606.01 | 24-MAY-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 |
June | 2560.09 | 01-JUN-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 |
July | 2583.16 | 13-JUL-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
August | 2543.09 | 20-AUG-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 |
September | 2557.49 | 09-SEP-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 |
October | 2850.87 | 14-OCT-08:61 | 540.00 | 530.41 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 0.00 |
November | 2778.48 | 27-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.27 |
December | 2810.18 | 19-DEC-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2487.52 | 252.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2850.87 | 819.00 | 663.02 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 60.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2487.15 | 09-JAN-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.56 |
February | 2645.85 | 06-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.60 |
March | 2376.63 | 19-MAR-18:11 | 1053.00 | 852.35 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.10 |
April | 2678.23 | 19-APR-18:01 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.52 |
May | 2575.48 | 24-MAY-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.36 |
June | 2474.45 | 22-JUN-20:11 | 1602.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.21 |
July | 2403.10 | 17-JUL-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | 0.00 |
August | 2423.38 | 06-AUG-15:12 | 324.00 | 187.52 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 | 0.00 |
September | 2427.30 | 30-SEP-08:61 | 486.00 | 477.32 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 | 0.00 |
October | 2835.61 | 14-OCT-08:61 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.09 | 0.00 |
November | 2531.25 | 30-NOV-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 |
December | 2576.18 | 19-DEC-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2376.63 | 324.00 | 185.62 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2835.61 | 1602.00 | 852.35 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.09 | 70.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 487.11 | 14-JAN-12:40 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 |
February | 431.21 | 02-FEB-12:40 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
March | 365.25 | 11-MAR-13:15 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
April | 255.69 | 08-APR-12:50 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 |
May | 185.03 | 04-MAY-12:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
June | 189.41 | 24-JUN-08:00 | 0.00 | 33.33 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 |
July | 216.51 | 30-JUL-08:00 | 0.00 | 33.33 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 |
August | 243.06 | 30-AUG-13:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
September | 445.06 | 30-SEP-13:05 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 | 0.00 |
October | 534.11 | 16-OCT-12:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 |
November | 522.47 | 19-NOV-09:53 | 0.00 | 133.34 | 639.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
December | 496.46 | 19-DEC-13:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 185.03 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 534.11 | 0.00 | 133.34 | 639.82 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 14.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 914.02 | 16-JAN-09:02 | 324.00 | 200.06 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 |
February | 905.76 | 05-FEB-09:01 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
March | 845.32 | 04-MAR-09:01 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 |
April | 901.39 | 02-APR-08:51 | 432.00 | 266.75 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 |
May | 903.91 | 24-MAY-08:51 | 324.00 | 235.79 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 |
June | 879.03 | 22-JUN-20:11 | 1602.00 | 529.92 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 |
July | 889.83 | 18-JUL-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
August | 839.89 | 17-AUG-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
September | 842.05 | 03-SEP-08:51 | 486.00 | 300.09 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
October | 1015.11 | 14-OCT-08:61 | 540.00 | 333.44 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 |
November | 930.42 | 19-NOV-09:41 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 | 0.00 |
December | 915.79 | 19-DEC-19:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 839.89 | 324.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1015.11 | 1602.00 | 529.92 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 17.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2531.47 | 14-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
February | 2541.73 | 01-FEB-09:01 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 |
March | 2279.48 | 12-MAR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 |
April | 2517.54 | 02-APR-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.96 |
May | 2522.97 | 24-MAY-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 |
June | 2303.07 | 25-JUN-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 |
July | 2317.02 | 23-JUL-08:61 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.00 |
August | 2306.98 | 29-AUG-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 2310.80 | 20-SEP-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 |
October | 2602.05 | 14-OCT-08:61 | 540.00 | 530.41 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 0.00 |
November | 2546.68 | 27-NOV-09:01 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 |
December | 2560.04 | 05-DEC-09:01 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2279.48 | 252.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2602.05 | 680.40 | 530.41 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 36.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2372.66 | 14-JAN-09:52 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 |
February | 2415.21 | 03-FEB-09:52 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 |
March | 2341.83 | 23-MAR-08:51 | 288.00 | 333.36 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 |
April | 2593.46 | 02-APR-08:51 | 432.00 | 424.28 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 |
May | 2662.06 | 24-MAY-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 |
June | 2508.73 | 23-JUN-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 |
July | 2527.07 | 04-JUL-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 |
August | 2426.57 | 22-AUG-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 |
September | 2457.17 | 03-SEP-08:51 | 486.00 | 477.32 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 |
October | 2890.11 | 17-OCT-08:21 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 | 0.00 |
November | 2379.61 | 28-NOV-09:52 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
December | 2565.23 | 05-DEC-09:41 | 288.00 | 333.36 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2341.83 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2890.11 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 41.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1825.94 | 22-JAN-11:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 |
February | 1800.00 | 04-FEB-11:35 | 1508.90 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
March | 1806.24 | 12-MAR-10:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 |
April | 1893.22 | 30-APR-10:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.37 | 0.00 |
May | 1891.50 | 04-MAY-10:35 | 1005.94 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
June | 1952.76 | 25-JUN-10:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 | 0.00 |
July | 2026.45 | 23-JUL-10:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 | 0.00 |
August | 2047.22 | 19-AUG-10:35 | 1508.90 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 0.00 |
September | 2115.78 | 30-SEP-10:35 | 1508.90 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.29 | 0.00 |
October | 2097.66 | 15-OCT-10:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.42 | 0.00 |
November | 1895.34 | 19-NOV-11:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.15 | 0.00 |
December | 1818.36 | 05-DEC-11:35 | 1005.94 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1800.00 | 1005.94 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2115.78 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.42 | 45.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2908.61 | 14-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 0.00 |
February | 2912.21 | 03-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 |
March | 2544.24 | 19-MAR-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.52 |
April | 2751.13 | 01-APR-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 |
May | 2680.34 | 24-MAY-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.35 |
June | 2678.34 | 29-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
July | 2648.50 | 31-JUL-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 2628.90 | 01-AUG-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
September | 2590.21 | 09-SEP-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 |
October | 2955.48 | 13-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 29.64 | 0.00 |
November | 2873.77 | 27-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 |
December | 2913.23 | 19-DEC-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2544.24 | 252.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2955.48 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 29.64 | 61.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2529.76 | 09-JAN-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.46 |
February | 2732.20 | 06-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.91 |
March | 2542.98 | 19-MAR-18:11 | 1053.00 | 852.35 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.30 |
April | 2820.62 | 23-APR-18:11 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.21 |
May | 2710.17 | 18-MAY-19:11 | 1247.40 | 852.35 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.91 |
June | 2635.05 | 22-JUN-20:11 | 1602.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.21 |
July | 2542.09 | 08-JUL-21:11 | 1247.40 | 724.50 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 |
August | 2447.47 | 21-AUG-20:11 | 1281.60 | 674.30 | 1453.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 |
September | 2488.19 | 30-SEP-08:61 | 486.00 | 477.32 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 | 0.00 |
October | 2860.88 | 14-OCT-08:61 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 0.00 |
November | 2547.57 | 30-NOV-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.48 |
December | 2604.37 | 19-DEC-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2447.47 | 486.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2860.88 | 1602.00 | 947.05 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 71.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1613.70 | 14-JAN-16:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
February | 1602.84 | 03-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 |
March | 1417.43 | 24-MAR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 |
April | 1522.22 | 01-APR-18:02 | 702.00 | 357.25 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 |
May | 1453.02 | 18-MAY-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
June | 1413.12 | 21-JUN-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 |
July | 1447.15 | 31-JUL-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 0.00 |
August | 1455.56 | 10-AUG-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 1443.92 | 09-SEP-15:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
October | 1622.92 | 14-OCT-08:61 | 540.00 | 333.44 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 0.00 |
November | 1597.50 | 27-NOV-09:01 | 252.00 | 183.39 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
December | 1609.42 | 19-DEC-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1413.12 | 252.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1622.92 | 970.20 | 370.95 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 34.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18068.80 | 18-JAN-19:10 | 146938.85 | 9382.05 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.89 |
February | 17646.07 | 01-FEB-23:10 | 26988.77 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.30 |
March | 18195.82 | 23-MAR-18:10 | 146938.85 | 9382.05 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.72 |
April | 18952.53 | 26-APR-18:10 | 146938.85 | 7318.91 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.46 |
May | 19120.46 | 04-MAY-18:10 | 146938.85 | 6714.45 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 |
June | 19529.40 | 29-JUN-18:10 | 146938.85 | 5629.23 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 |
July | 19744.31 | 19-JUL-18:10 | 125947.58 | 5193.46 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 | 0.00 |
August | 19409.21 | 17-AUG-18:10 | 125947.58 | 6224.19 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 |
September | 19221.24 | 30-SEP-17:20 | 35985.02 | 1856.36 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 41.95 | 0.00 |
October | 19319.41 | 16-OCT-18:10 | 125947.58 | 8041.76 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 0.00 |
November | 17864.91 | 01-NOV-18:10 | 104956.32 | 6701.46 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.71 |
December | 17961.34 | 05-DEC-22:00 | 23990.02 | 1340.29 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17646.07 | 23990.02 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19744.31 | 146938.85 | 9382.05 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 41.95 | 182.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18759.83 | 18-JAN-19:10 | 146938.85 | 9382.05 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.21 |
February | 18284.75 | 13-FEB-23:10 | 26988.77 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.30 |
March | 18859.41 | 23-MAR-18:10 | 146938.85 | 9382.05 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.82 |
April | 19604.18 | 26-APR-18:10 | 146938.85 | 7318.91 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.44 |
May | 20173.30 | 04-MAY-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.54 |
June | 20647.22 | 27-JUN-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.50 |
July | 20700.74 | 19-JUL-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.45 |
August | 20464.85 | 02-AUG-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.79 |
September | 20826.46 | 29-SEP-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 0.00 |
October | 20719.10 | 04-OCT-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.99 |
November | 18489.23 | 01-NOV-18:10 | 104956.32 | 6701.46 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.54 |
December | 18675.92 | 05-DEC-22:54 | 134943.84 | 5026.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18284.75 | 26988.77 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20826.46 | 146938.85 | 9382.05 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 169.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27190.25 | 14-JAN-11:50 | 800.57 | 219.99 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 27.82 | 0.00 |
February | 27056.06 | 19-FEB-11:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 122.03 |
March | 27787.62 | 19-MAR-10:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 65.77 |
April | 28182.43 | 30-APR-10:40 | 1601.14 | 527.97 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 22.92 | 0.00 |
May | 27846.34 | 04-MAY-10:40 | 1067.42 | 439.97 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
June | 28248.89 | 25-JUN-10:40 | 1601.14 | 527.97 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 |
July | 28561.10 | 23-JUL-10:40 | 1601.14 | 527.97 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 22.96 | 0.00 |
August | 28464.86 | 19-AUG-10:40 | 1601.14 | 439.97 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 8.38 | 0.00 |
September | 28927.80 | 30-SEP-10:50 | 800.57 | 219.99 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 95.37 | 0.00 |
October | 28811.47 | 15-OCT-10:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 110.49 | 0.00 |
November | 27745.56 | 19-NOV-11:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 27.74 | 0.00 |
December | 27063.68 | 05-DEC-11:50 | 533.71 | 219.99 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27056.06 | 533.71 | 219.99 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28927.80 | 1601.14 | 527.97 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 110.49 | 122.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2318.37 | 20-JAN-11:35 | 1064.64 | 695.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 |
February | 2227.95 | 04-FEB-11:50 | 798.48 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.27 |
March | 2305.15 | 11-MAR-11:35 | 1596.96 | 695.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 0.00 |
April | 2613.76 | 27-APR-14:10 | 798.48 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.03 |
May | 3056.10 | 04-MAY-12:00 | 532.32 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 |
June | 3146.07 | 30-JUN-15:35 | 2661.60 | 695.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
July | 3516.34 | 30-JUL-13:30 | 532.32 | 278.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
August | 3739.81 | 19-AUG-13:10 | 1596.96 | 695.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 0.00 |
September | 5052.68 | 30-SEP-13:30 | 798.48 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 | 0.00 |
October | 4902.75 | 16-OCT-12:30 | 532.32 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.96 | 0.00 |
November | 2617.43 | 19-NOV-13:00 | 798.48 | 417.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 | 0.00 |
December | 2322.96 | 19-DEC-13:10 | 532.32 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2227.95 | 532.32 | 278.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5052.68 | 2661.60 | 695.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.96 | 59.03 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.335495E+12 | 231134.60 | 17-JAN-20:10 | 0.407597E+12 | 326273.47 | 06-JAN-22:00 |
February | 0.293454E+12 | 211149.02 | 13-FEB-20:10 | 0.353559E+12 | 319109.20 | 27-FEB-18:10 |
March | 0.320890E+12 | 221120.35 | 23-MAR-19:19 | 0.402808E+12 | 321218.60 | 29-MAR-17:10 |
April | 0.333890E+12 | 232650.00 | 26-APR-19:10 | 0.361460E+12 | 318506.40 | 17-APR-17:19 |
May | 0.344467E+12 | 231494.98 | 04-MAY-19:10 | 0.370336E+12 | 315413.82 | 12-MAY-17:10 |
June | 0.362206E+12 | 248004.99 | 29-JUN-18:10 | 0.349046E+12 | 311722.53 | 08-JUN-17:49 |
July | 0.422084E+12 | 273276.68 | 31-JUL-19:10 | 0.356862E+12 | 309941.67 | 14-JUL-17:40 |
August | 0.434624E+12 | 267272.01 | 14-AUG-19:10 | 0.356587E+12 | 309749.13 | 28-AUG-17:40 |
September | 0.385247E+12 | 285493.07 | 29-SEP-19:10 | 0.347016E+12 | 310588.15 | 22-SEP-17:00 |
October | 0.403310E+12 | 274791.49 | 04-OCT-19:10 | 0.363541E+12 | 311125.53 | 24-OCT-17:10 |
November | 0.329258E+12 | 220578.07 | 01-NOV-19:19 | 0.367535E+12 | 317511.47 | 16-NOV-18:40 |
December | 0.339498E+12 | 228663.58 | 05-DEC-20:10 | 0.398697E+12 | 317978.46 | 12-DEC-18:10 |
Annual Sum or Average | 0.430442E+13 | 0.443504E+13 | ||||
Minimum of Months | 0.293454E+12 | 211149.02 | 0.347016E+12 | 309749.13 | ||
Maximum of Months | 0.434624E+12 | 285493.07 | 0.407597E+12 | 326273.47 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.123142E+11 | 22800.11 | 29-JAN-12:09 | 0.00 | 0.00 |
February | 0.127959E+11 | 26773.28 | 22-FEB-11:00 | 0.00 | 0.00 |
March | 0.174968E+11 | 30321.99 | 21-MAR-12:30 | 0.00 | 0.00 |
April | 0.244611E+11 | 34338.26 | 29-APR-11:39 | 0.00 | 0.00 |
May | 0.250493E+11 | 34554.33 | 27-MAY-11:39 | 0.00 | 0.00 |
June | 0.253481E+11 | 34348.42 | 13-JUN-11:50 | 0.00 | 0.00 |
July | 0.282640E+11 | 33203.99 | 02-JUL-11:00 | 0.00 | 0.00 |
August | 0.261836E+11 | 31772.09 | 01-AUG-12:09 | 0.00 | 0.00 |
September | 0.200651E+11 | 31574.60 | 02-SEP-11:00 | 0.00 | 0.00 |
October | 0.152932E+11 | 27529.10 | 03-OCT-11:39 | 0.00 | 0.00 |
November | 0.126578E+11 | 23806.47 | 02-NOV-11:30 | 0.00 | 0.00 |
December | 0.116360E+11 | 21156.13 | 02-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.231565E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.116360E+11 | 21156.13 | 0.00 | 0.00 | |
Maximum of Months | 0.282640E+11 | 34554.33 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.405001E+11 | 0.148288E+11 | 0.140003E+12 | 0.331717E+11 | 0.506946E+11 | 0.545970E+10 | 0.00 | 0.393898E+11 | 0.00 | 0.00 | 0.00 | 0.770428E+10 | 0.00 |
February | 0.364826E+11 | 0.126752E+11 | 0.126445E+12 | 0.299616E+11 | 0.453602E+11 | 0.497329E+10 | 0.00 | 0.272098E+11 | 0.00 | 0.00 | 0.00 | 0.696185E+10 | 0.00 |
March | 0.403220E+11 | 0.129910E+11 | 0.140056E+12 | 0.331741E+11 | 0.500748E+11 | 0.526114E+10 | 0.00 | 0.275505E+11 | 0.00 | 0.00 | 0.00 | 0.770286E+10 | 0.00 |
April | 0.388388E+11 | 0.115495E+11 | 0.135446E+12 | 0.321012E+11 | 0.490077E+11 | 0.550046E+10 | 0.00 | 0.503433E+11 | 0.00 | 0.00 | 0.00 | 0.746489E+10 | 0.00 |
May | 0.400052E+11 | 0.110269E+11 | 0.140035E+12 | 0.331727E+11 | 0.505453E+11 | 0.571447E+10 | 0.00 | 0.524994E+11 | 0.00 | 0.00 | 0.00 | 0.770426E+10 | 0.00 |
June | 0.386693E+11 | 0.102228E+11 | 0.135537E+12 | 0.321035E+11 | 0.496266E+11 | 0.557285E+10 | 0.00 | 0.793591E+11 | 0.00 | 0.00 | 0.00 | 0.745689E+10 | 0.00 |
July | 0.399645E+11 | 0.107627E+11 | 0.139944E+12 | 0.331703E+11 | 0.523122E+11 | 0.601286E+10 | 0.00 | 0.128438E+12 | 0.00 | 0.00 | 0.00 | 0.771239E+10 | 0.00 |
August | 0.400849E+11 | 0.115265E+11 | 0.140067E+12 | 0.331740E+11 | 0.526071E+11 | 0.608781E+10 | 0.00 | 0.139587E+12 | 0.00 | 0.00 | 0.00 | 0.770437E+10 | 0.00 |
September | 0.389938E+11 | 0.121353E+11 | 0.135457E+12 | 0.321014E+11 | 0.502468E+11 | 0.570801E+10 | 0.00 | 0.994796E+11 | 0.00 | 0.00 | 0.00 | 0.746620E+10 | 0.00 |
October | 0.404199E+11 | 0.135998E+11 | 0.139992E+12 | 0.331716E+11 | 0.523702E+11 | 0.592896E+10 | 0.00 | 0.106368E+12 | 0.00 | 0.00 | 0.00 | 0.770295E+10 | 0.00 |
November | 0.391757E+11 | 0.140880E+11 | 0.135531E+12 | 0.321023E+11 | 0.492636E+11 | 0.553558E+10 | 0.00 | 0.424926E+11 | 0.00 | 0.00 | 0.00 | 0.744868E+10 | 0.00 |
December | 0.404718E+11 | 0.150815E+11 | 0.139944E+12 | 0.331706E+11 | 0.508336E+11 | 0.556483E+10 | 0.00 | 0.429853E+11 | 0.00 | 0.00 | 0.00 | 0.771244E+10 | 0.00 |
Annual Sum or Average | 0.473928E+12 | 0.150488E+12 | 0.164846E+13 | 0.390575E+12 | 0.602943E+12 | 0.673200E+11 | 0.00 | 0.835702E+12 | 0.00 | 0.00 | 0.00 | 0.907421E+11 | 0.00 |
Minimum of Months | 0.364826E+11 | 0.102228E+11 | 0.126445E+12 | 0.299616E+11 | 0.453602E+11 | 0.497329E+10 | 0.00 | 0.272098E+11 | 0.00 | 0.00 | 0.00 | 0.696185E+10 | 0.00 |
Maximum of Months | 0.405001E+11 | 0.150815E+11 | 0.140067E+12 | 0.331741E+11 | 0.526071E+11 | 0.608781E+10 | 0.00 | 0.139587E+12 | 0.00 | 0.00 | 0.00 | 0.771244E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.385939E+11 | 0.00 | 0.217084E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.200675E+11 | 0.00 | 0.196287E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.349055E+11 | 0.00 | 0.215879E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.840688E+10 | 0.00 | 0.206097E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.879072E+10 | 0.00 | 0.209566E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.208871E+10 | 0.00 | 0.199844E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.508005E+09 | 0.00 | 0.204533E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.167407E+09 | 0.00 | 0.204381E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.788625E+09 | 0.00 | 0.199256E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.291320E+10 | 0.00 | 0.208724E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.151329E+11 | 0.00 | 0.205311E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.316571E+11 | 0.00 | 0.215220E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.164020E+12 | 0.00 | 0.248218E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.167407E+09 | 0.00 | 0.196287E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.385939E+11 | 0.00 | 0.217084E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 39200.55 | 02-JAN-20:10 | 9571.94 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 23859.15 | 18-JAN-07:19 | 28302.34 | 19-JAN-21:10 | 2537.36 | 18-JAN-12:00 | 0.00 | 01-JAN-00:10 |
February | 39200.55 | 01-FEB-20:10 | 9571.94 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 23858.89 | 10-FEB-07:19 | 27343.81 | 03-FEB-19:10 | 2409.12 | 01-FEB-13:09 | 0.00 | 01-FEB-00:10 |
March | 39200.55 | 01-MAR-20:10 | 9571.94 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 23859.24 | 16-MAR-06:19 | 28052.80 | 23-MAR-19:19 | 2630.10 | 11-MAR-11:50 | 0.00 | 01-MAR-00:10 |
April | 39200.55 | 03-APR-19:10 | 9571.94 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 23858.85 | 05-APR-06:19 | 28670.20 | 27-APR-19:19 | 2477.01 | 13-APR-08:00 | 0.00 | 01-APR-00:10 |
May | 39200.55 | 01-MAY-19:10 | 9571.94 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 23858.49 | 09-MAY-06:19 | 28864.70 | 24-MAY-19:30 | 2335.74 | 03-MAY-09:50 | 0.00 | 01-MAY-00:10 |
June | 39200.55 | 01-JUN-19:10 | 9571.94 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 23858.49 | 16-JUN-06:19 | 29778.20 | 22-JUN-20:30 | 2745.42 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 39200.55 | 03-JUL-19:10 | 9571.94 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 23858.49 | 12-JUL-06:19 | 28792.72 | 19-JUL-21:00 | 3034.07 | 18-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 39200.55 | 01-AUG-19:10 | 9571.94 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 23858.80 | 29-AUG-06:19 | 29692.96 | 21-AUG-20:30 | 2961.57 | 17-AUG-15:30 | 0.00 | 01-AUG-00:10 |
September | 39200.55 | 01-SEP-19:10 | 9571.94 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 23859.02 | 18-SEP-06:19 | 30442.09 | 29-SEP-21:19 | 3485.35 | 29-SEP-18:00 | 0.00 | 01-SEP-00:10 |
October | 39200.55 | 02-OCT-19:10 | 9571.94 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 23859.23 | 23-OCT-06:19 | 31634.78 | 16-OCT-21:00 | 3528.86 | 17-OCT-10:50 | 0.00 | 01-OCT-00:10 |
November | 39200.55 | 01-NOV-19:10 | 9571.94 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 23859.27 | 03-NOV-06:19 | 27786.11 | 19-NOV-20:19 | 2801.88 | 19-NOV-10:39 | 0.00 | 01-NOV-00:10 |
December | 39200.55 | 01-DEC-20:10 | 9571.94 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 23859.09 | 08-DEC-07:19 | 27447.36 | 19-DEC-19:10 | 2583.11 | 16-DEC-11:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 39200.55 | 9571.94 | 88863.15 | 23858.49 | 27343.81 | 2335.74 | 0.00 | |||||||
Maximum of Months | 39200.55 | 9571.94 | 88863.15 | 23859.27 | 31634.78 | 3528.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 68914.68 | 14-JAN-11:39 | 0.00 | 0.00 | 0.00 | 4738.75 | 19-JAN-19:10 | 0.00 | 01-JAN-00:10 |
February | 64537.60 | 01-FEB-11:50 | 0.00 | 0.00 | 0.00 | 4738.65 | 23-FEB-19:10 | 0.00 | 01-FEB-00:10 |
March | 62865.81 | 23-MAR-15:30 | 0.00 | 0.00 | 0.00 | 4738.23 | 16-MAR-06:00 | 0.00 | 01-MAR-00:10 |
April | 70679.16 | 26-APR-10:50 | 0.00 | 0.00 | 0.00 | 4738.46 | 13-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 56672.82 | 03-MAY-09:50 | 0.00 | 0.00 | 0.00 | 4738.40 | 16-MAY-18:00 | 0.00 | 01-MAY-00:10 |
June | 85393.04 | 29-JUN-18:10 | 0.00 | 0.00 | 0.00 | 4738.64 | 15-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 109978.82 | 19-JUL-15:30 | 0.00 | 0.00 | 0.00 | 4738.36 | 10-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 112799.37 | 17-AUG-15:30 | 0.00 | 0.00 | 0.00 | 4738.56 | 17-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 123617.51 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 4738.55 | 12-SEP-06:30 | 0.00 | 01-SEP-00:10 |
October | 126718.75 | 16-OCT-12:09 | 0.00 | 0.00 | 0.00 | 4738.15 | 04-OCT-06:19 | 0.00 | 01-OCT-00:10 |
November | 78822.13 | 19-NOV-09:50 | 0.00 | 0.00 | 0.00 | 4738.40 | 02-NOV-18:10 | 0.00 | 01-NOV-00:10 |
December | 74758.05 | 05-DEC-09:50 | 0.00 | 0.00 | 0.00 | 4738.31 | 06-DEC-07:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 56672.82 | 0.00 | 0.00 | 0.00 | 4738.15 | 0.00 | |||
Maximum of Months | 126718.75 | 0.00 | 0.00 | 0.00 | 4738.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 231134.60 | 17-JAN-20:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 25404.27 | 2192.18 | 0.00 | 44350.19 | 0.00 |
February | 211149.02 | 13-FEB-20:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 24487.44 | 2111.77 | 0.00 | 24596.74 | 0.00 |
March | 221120.35 | 23-MAR-19:19 | 39200.55 | 86131.51 | 9571.94 | 19292.08 | 28052.80 | 2156.23 | 0.00 | 31300.09 | 0.00 |
April | 232650.00 | 26-APR-19:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 25183.02 | 2231.80 | 0.00 | 45667.87 | 0.00 |
May | 231494.98 | 04-MAY-19:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 25170.32 | 2211.37 | 0.00 | 44401.21 | 0.00 |
June | 248004.99 | 29-JUN-18:10 | 32805.29 | 77265.07 | 0.00 | 19091.98 | 24275.30 | 2745.42 | 0.00 | 85393.04 | 0.00 |
July | 273276.68 | 31-JUL-19:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 25503.01 | 2756.05 | 0.00 | 85086.48 | 0.00 |
August | 267272.01 | 14-AUG-19:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 25511.24 | 2653.10 | 0.00 | 79187.94 | 0.00 |
September | 285493.07 | 29-SEP-19:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 29256.72 | 2543.37 | 0.00 | 94581.15 | 0.00 |
October | 274791.49 | 04-OCT-19:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 25395.32 | 2762.34 | 0.00 | 87104.12 | 0.00 |
November | 220578.07 | 01-NOV-19:19 | 39200.55 | 86131.51 | 9571.94 | 19292.08 | 27745.98 | 2175.11 | 0.00 | 30774.55 | 0.00 |
December | 228663.58 | 05-DEC-20:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 25865.08 | 2156.05 | 0.00 | 41446.76 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 211149.02 | 32805.29 | 77265.07 | 0.00 | 19091.98 | 24275.30 | 2111.77 | 0.00 | 24596.74 | 0.00 | |
Maximum of Months | 285493.07 | 39200.55 | 86131.51 | 9571.94 | 19292.08 | 29256.72 | 2762.34 | 0.00 | 94581.15 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 140553.10 | 09-JAN-05:00 | 0.00 | 208302.38 | 30-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 91120.56 | 05-FEB-05:00 | 0.00 | 208320.59 | 13-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 117189.85 | 30-MAR-02:00 | 0.00 | 208187.12 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 59530.41 | 01-APR-05:00 | 0.00 | 207747.13 | 03-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 50154.82 | 14-MAY-04:49 | 0.00 | 207201.81 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 9854.53 | 13-JUN-03:00 | 0.00 | 206624.59 | 02-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 6541.92 | 06-JUL-00:00 | 0.00 | 206022.18 | 11-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 3716.91 | 06-AUG-15:20 | 0.00 | 205981.46 | 22-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 9011.24 | 20-SEP-02:00 | 0.00 | 206429.36 | 28-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 29822.92 | 30-OCT-03:00 | 0.00 | 207065.55 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 62353.40 | 24-NOV-03:00 | 0.00 | 207614.79 | 28-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 94144.31 | 24-DEC-03:00 | 0.00 | 208097.14 | 29-DEC-21:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 3716.91 | 0.00 | 205981.46 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 140553.10 | 0.00 | 208320.59 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.02 | 0.67 | 22.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.98 | 2.33 | 21.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.97 | 3.17 | 21.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.02 | 2.33 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.81 | 0.50 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.96 | 0.50 | 21.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.73 | 3.00 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.72 | 2.33 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.91 | 0.50 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.87 | 1.17 | 21.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.50 | 21.77 | 9.50 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.96 | 3.00 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.84 | 3.67 | 21.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.84 | 7.00 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 21.79 | 6.50 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.77 | 2.33 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.83 | 2.33 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.17 | 21.81 | 23.17 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.84 | 7.00 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.80 | 0.67 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.00 | 21.80 | 2.00 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.83 | 1.00 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.85 | 0.33 | 21.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.95 | 1.50 | 21.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.87 | 2.50 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 22.06 | 3.67 | 22.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.21 | 7.17 | 22.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.24 | 7.17 | 22.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.99 | 3.00 | 21.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.90 | 1.67 | 21.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.05 | 0.17 | 22.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.17 | 22.10 | 27.17 | 22.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.24 | 7.17 | 22.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.93 | 1.50 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.99 | 4.00 | 21.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
Annual Sum or Average | 0.00 | 0.00 | 8.33 | 21.88 | 8.33 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.99 | 4.00 | 21.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.86 | 1.00 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.86 | 1.67 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.84 | 2.67 | 21.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.81 | 5.67 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.77 | 5.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.93 | 1.00 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.92 | 1.67 | 21.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.00 | 21.83 | 19.00 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.93 | 5.67 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.70 | 1.33 | 21.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.98 | 0.67 | 21.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.97 | 4.83 | 21.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.79 | 0.83 | 21.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
Annual Sum or Average | 0.00 | 0.00 | 9.33 | 21.88 | 9.33 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.98 | 4.83 | 21.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
February | 672.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
March | 744.00 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
April | 720.00 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
May | 744.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
June | 720.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
July | 744.00 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
August | 744.00 | 22.31 | 0.00 | 22.31 | 0.00 | 22.31 |
September | 720.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
October | 743.83 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
November | 719.33 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
December | 744.00 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
Annual Sum or Average | 8759.17 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
Minimum of Months | 672.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
Maximum of Months | 744.00 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 576.50 | 22.20 | 84.17 | 22.43 | 0.00 | 22.43 |
February | 554.17 | 21.96 | 54.50 | 22.14 | 0.00 | 22.14 |
March | 653.67 | 21.78 | 49.50 | 21.93 | 0.00 | 21.93 |
April | 602.17 | 22.24 | 53.33 | 22.37 | 0.00 | 22.37 |
May | 713.17 | 22.05 | 6.33 | 22.06 | 0.00 | 22.06 |
June | 668.83 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
July | 471.67 | 22.74 | 90.50 | 22.89 | 0.00 | 22.89 |
August | 267.33 | 22.81 | 280.00 | 23.30 | 1.33 | 23.30 |
September | 366.17 | 22.69 | 229.00 | 23.14 | 3.17 | 23.14 |
October | 386.33 | 22.70 | 211.00 | 23.12 | 8.33 | 23.12 |
November | 535.83 | 22.43 | 96.50 | 22.67 | 0.00 | 22.67 |
December | 562.67 | 22.33 | 71.00 | 22.51 | 0.00 | 22.51 |
Annual Sum or Average | 6358.50 | 22.30 | 1225.83 | 22.55 | 12.83 | 22.55 |
Minimum of Months | 267.33 | 21.78 | 0.00 | 21.93 | 0.00 | 21.93 |
Maximum of Months | 713.17 | 22.81 | 280.00 | 23.30 | 8.33 | 23.30 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.67 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
February | 672.00 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
March | 743.67 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
April | 712.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
May | 736.50 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
June | 686.50 | 22.35 | 2.33 | 22.36 | 0.00 | 22.36 |
July | 623.17 | 22.54 | 18.83 | 22.57 | 0.00 | 22.57 |
August | 558.67 | 22.58 | 42.17 | 22.65 | 0.00 | 22.65 |
September | 636.33 | 22.58 | 12.33 | 22.60 | 0.00 | 22.60 |
October | 666.50 | 22.63 | 17.17 | 22.65 | 0.00 | 22.65 |
November | 719.33 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
December | 744.00 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
Annual Sum or Average | 8242.33 | 22.31 | 92.83 | 22.32 | 0.00 | 22.32 |
Minimum of Months | 558.67 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
Maximum of Months | 744.00 | 22.63 | 42.17 | 22.65 | 0.00 | 22.65 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 623.33 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
February | 615.83 | 23.61 | 0.67 | 23.61 | 0.67 | 23.61 |
March | 642.83 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
April | 357.17 | 23.70 | 2.00 | 23.71 | 0.00 | 23.71 |
May | 311.67 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
June | 11.50 | 23.97 | 66.50 | 24.00 | 0.00 | 24.00 |
July | 0.00 | 0.00 | 343.17 | 24.00 | 0.00 | 24.00 |
August | 0.00 | 0.00 | 462.17 | 24.00 | 0.00 | 24.00 |
September | 18.67 | 24.00 | 163.67 | 24.00 | 0.00 | 24.00 |
October | 312.33 | 24.00 | 133.17 | 24.00 | 0.00 | 24.00 |
November | 515.00 | 23.83 | 0.00 | 23.83 | 0.00 | 23.83 |
December | 685.50 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
Annual Sum or Average | 4093.83 | 23.68 | 1171.33 | 23.75 | 0.67 | 23.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.45 | 0.00 | 23.45 |
Maximum of Months | 685.50 | 24.00 | 462.17 | 24.00 | 0.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.16 | 1.83 | 21.15 | 1.83 | 21.15 |
February | 672.00 | 21.10 | 2.33 | 21.10 | 2.33 | 21.10 |
March | 744.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
April | 720.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
May | 744.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
June | 720.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
July | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
August | 744.00 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
September | 720.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
October | 744.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
November | 720.00 | 21.26 | 1.83 | 21.26 | 1.83 | 21.26 |
December | 744.00 | 21.18 | 0.00 | 21.18 | 0.00 | 21.18 |
Annual Sum or Average | 8760.00 | 21.42 | 6.00 | 21.42 | 6.00 | 21.42 |
Minimum of Months | 672.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
Maximum of Months | 744.00 | 21.84 | 2.33 | 21.84 | 2.33 | 21.84 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 247.17 | 24.00 | 744.00 | 24.00 | 247.17 | 24.00 |
February | 240.33 | 24.00 | 672.00 | 24.00 | 240.33 | 24.00 |
March | 304.33 | 24.00 | 744.00 | 24.00 | 304.33 | 24.00 |
April | 334.33 | 24.00 | 720.00 | 24.00 | 334.33 | 24.00 |
May | 338.67 | 24.00 | 744.00 | 24.00 | 338.67 | 24.00 |
June | 443.83 | 24.00 | 720.00 | 24.00 | 443.83 | 24.00 |
July | 582.00 | 24.00 | 744.00 | 24.00 | 582.00 | 24.00 |
August | 597.00 | 24.00 | 744.00 | 24.00 | 597.00 | 24.00 |
September | 467.67 | 24.00 | 720.00 | 24.00 | 467.67 | 24.00 |
October | 365.17 | 24.00 | 744.00 | 24.00 | 365.17 | 24.00 |
November | 259.50 | 24.00 | 720.00 | 24.00 | 259.50 | 24.00 |
December | 220.00 | 24.00 | 744.00 | 24.00 | 220.00 | 24.00 |
Annual Sum or Average | 4400.00 | 24.00 | 8760.00 | 24.00 | 4400.00 | 24.00 |
Minimum of Months | 220.00 | 24.00 | 672.00 | 24.00 | 220.00 | 24.00 |
Maximum of Months | 597.00 | 24.00 | 744.00 | 24.00 | 597.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 649.00 | 21.99 | 34.67 | 22.04 | 4.00 | 22.04 |
February | 631.33 | 21.85 | 7.00 | 21.86 | 0.83 | 21.86 |
March | 726.33 | 21.68 | 0.17 | 21.68 | 0.00 | 21.68 |
April | 718.17 | 21.73 | 9.67 | 21.74 | 9.67 | 21.75 |
May | 742.67 | 21.58 | 2.33 | 21.58 | 2.33 | 21.59 |
June | 720.00 | 21.67 | 44.67 | 21.73 | 44.67 | 21.78 |
July | 743.50 | 21.79 | 132.33 | 21.93 | 132.33 | 22.03 |
August | 739.67 | 21.96 | 200.50 | 22.13 | 200.50 | 22.24 |
September | 655.50 | 22.02 | 112.50 | 22.13 | 104.33 | 22.21 |
October | 587.83 | 22.14 | 127.83 | 22.30 | 54.17 | 22.34 |
November | 624.17 | 22.05 | 31.67 | 22.10 | 2.50 | 22.10 |
December | 630.17 | 22.08 | 24.67 | 22.12 | 0.00 | 22.12 |
Annual Sum or Average | 8168.33 | 21.87 | 728.00 | 21.95 | 555.33 | 21.99 |
Minimum of Months | 587.83 | 21.58 | 0.17 | 21.58 | 0.00 | 21.59 |
Maximum of Months | 743.50 | 22.14 | 200.50 | 22.30 | 200.50 | 22.34 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 708.17 | 22.59 | 12.33 | 22.60 | 6.83 | 22.61 |
February | 651.00 | 22.48 | 3.67 | 22.48 | 3.00 | 22.48 |
March | 723.67 | 22.34 | 1.00 | 22.34 | 0.00 | 22.34 |
April | 651.83 | 22.41 | 15.50 | 22.43 | 9.83 | 22.44 |
May | 693.17 | 22.38 | 18.00 | 22.41 | 11.83 | 22.43 |
June | 617.67 | 22.46 | 89.83 | 22.58 | 76.33 | 22.67 |
July | 625.33 | 22.62 | 221.17 | 22.84 | 194.17 | 22.95 |
August | 654.50 | 22.76 | 293.33 | 22.98 | 258.33 | 23.09 |
September | 576.17 | 22.69 | 178.67 | 22.88 | 141.50 | 22.97 |
October | 579.50 | 22.80 | 106.00 | 22.94 | 60.67 | 23.00 |
November | 653.00 | 22.68 | 17.00 | 22.70 | 10.67 | 22.70 |
December | 715.17 | 22.70 | 2.67 | 22.70 | 0.00 | 22.70 |
Annual Sum or Average | 7849.17 | 22.57 | 959.17 | 22.67 | 773.17 | 22.73 |
Minimum of Months | 576.17 | 22.34 | 1.00 | 22.34 | 0.00 | 22.34 |
Maximum of Months | 723.67 | 22.80 | 293.33 | 22.98 | 258.33 | 23.09 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.67 | 21.63 | 2.67 | 21.63 | 2.67 | 21.63 |
February | 666.50 | 21.55 | 2.00 | 21.55 | 2.00 | 21.55 |
March | 736.17 | 21.52 | 3.17 | 21.51 | 3.17 | 21.51 |
April | 697.50 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
May | 739.33 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
June | 687.17 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
July | 669.17 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
August | 657.00 | 21.56 | 1.17 | 21.56 | 1.17 | 21.56 |
September | 664.00 | 21.61 | 0.33 | 21.61 | 0.33 | 21.61 |
October | 708.50 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
November | 709.83 | 21.66 | 2.33 | 21.65 | 2.33 | 21.65 |
December | 742.33 | 21.66 | 1.17 | 21.66 | 1.17 | 21.66 |
Annual Sum or Average | 8419.17 | 21.61 | 12.83 | 21.61 | 12.83 | 21.61 |
Minimum of Months | 657.00 | 21.52 | 0.00 | 21.51 | 0.00 | 21.51 |
Maximum of Months | 742.33 | 21.66 | 3.17 | 21.66 | 3.17 | 21.66 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.46 | 27.50 | 21.44 | 27.50 | 21.43 |
February | 672.00 | 21.46 | 10.50 | 21.46 | 10.50 | 21.45 |
March | 732.50 | 21.46 | 9.67 | 21.47 | 4.67 | 21.47 |
April | 642.83 | 21.70 | 34.83 | 21.85 | 0.00 | 21.85 |
May | 662.17 | 21.79 | 45.50 | 21.97 | 0.00 | 21.97 |
June | 561.17 | 21.98 | 110.83 | 22.46 | 6.33 | 22.48 |
July | 527.33 | 22.15 | 192.50 | 22.84 | 57.83 | 22.94 |
August | 548.83 | 22.17 | 188.00 | 22.77 | 76.00 | 22.88 |
September | 608.17 | 22.01 | 71.67 | 22.23 | 17.33 | 22.25 |
October | 707.33 | 22.08 | 41.50 | 22.15 | 32.67 | 22.20 |
November | 720.00 | 21.62 | 10.67 | 21.61 | 10.67 | 21.60 |
December | 744.00 | 21.50 | 22.50 | 21.49 | 22.50 | 21.48 |
Annual Sum or Average | 7870.33 | 21.76 | 765.67 | 21.97 | 266.00 | 22.00 |
Minimum of Months | 527.33 | 21.46 | 9.67 | 21.44 | 0.00 | 21.43 |
Maximum of Months | 744.00 | 22.17 | 192.50 | 22.84 | 76.00 | 22.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.42 | 4.33 | 21.42 | 4.33 | 21.41 |
February | 672.00 | 21.41 | 5.83 | 21.41 | 5.83 | 21.40 |
March | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
April | 720.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
May | 744.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
June | 714.17 | 22.08 | 1.00 | 22.08 | 0.00 | 22.08 |
July | 733.17 | 22.30 | 25.67 | 22.34 | 25.00 | 22.37 |
August | 738.67 | 22.24 | 31.50 | 22.28 | 31.50 | 22.32 |
September | 720.00 | 21.96 | 8.00 | 21.97 | 8.00 | 21.98 |
October | 743.50 | 21.93 | 19.83 | 21.97 | 19.83 | 22.00 |
November | 720.00 | 21.45 | 9.17 | 21.45 | 9.17 | 21.44 |
December | 744.00 | 21.41 | 8.00 | 21.40 | 8.00 | 21.40 |
Annual Sum or Average | 8737.50 | 21.75 | 113.33 | 21.76 | 111.67 | 21.78 |
Minimum of Months | 672.00 | 21.41 | 0.00 | 21.40 | 0.00 | 21.40 |
Maximum of Months | 744.00 | 22.30 | 31.50 | 22.34 | 31.50 | 22.37 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.68 | 2.67 | 21.68 | 2.67 | 21.68 |
February | 672.00 | 21.59 | 4.00 | 21.58 | 4.00 | 21.58 |
March | 744.00 | 21.58 | 2.33 | 21.58 | 2.33 | 21.58 |
April | 720.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
May | 744.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
June | 719.17 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
July | 736.17 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
August | 726.83 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
September | 713.00 | 21.73 | 0.17 | 21.73 | 0.17 | 21.73 |
October | 742.17 | 21.74 | 0.17 | 21.74 | 0.17 | 21.74 |
November | 720.00 | 21.70 | 5.17 | 21.70 | 5.17 | 21.69 |
December | 744.00 | 21.69 | 5.00 | 21.69 | 5.00 | 21.68 |
Annual Sum or Average | 8725.33 | 21.70 | 19.50 | 21.70 | 19.50 | 21.70 |
Minimum of Months | 672.00 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
Maximum of Months | 744.00 | 21.77 | 5.17 | 21.77 | 5.17 | 21.77 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.48 | 22.17 | 21.46 | 22.17 | 21.45 |
February | 672.00 | 21.44 | 10.33 | 21.44 | 10.33 | 21.43 |
March | 742.33 | 21.51 | 5.33 | 21.51 | 5.33 | 21.50 |
April | 707.17 | 21.87 | 6.33 | 21.90 | 0.00 | 21.90 |
May | 723.67 | 21.93 | 5.00 | 21.95 | 0.00 | 21.95 |
June | 645.50 | 22.12 | 39.67 | 22.26 | 3.83 | 22.27 |
July | 608.17 | 22.34 | 120.83 | 22.67 | 56.67 | 22.78 |
August | 627.17 | 22.39 | 121.00 | 22.70 | 78.83 | 22.84 |
September | 693.67 | 22.11 | 31.83 | 22.18 | 18.33 | 22.20 |
October | 735.50 | 22.12 | 35.50 | 22.17 | 33.67 | 22.21 |
November | 719.17 | 21.57 | 15.67 | 21.56 | 15.67 | 21.55 |
December | 744.00 | 21.51 | 29.33 | 21.49 | 29.33 | 21.48 |
Annual Sum or Average | 8362.33 | 21.85 | 443.00 | 21.94 | 274.17 | 21.97 |
Minimum of Months | 608.17 | 21.44 | 5.00 | 21.44 | 0.00 | 21.43 |
Maximum of Months | 744.00 | 22.39 | 121.00 | 22.70 | 78.83 | 22.84 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
February | 672.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
March | 744.00 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
April | 720.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
May | 744.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
June | 720.00 | 22.16 | 13.50 | 22.16 | 13.50 | 22.17 |
July | 744.00 | 22.48 | 70.67 | 22.50 | 70.67 | 22.51 |
August | 744.00 | 22.57 | 93.83 | 22.58 | 93.83 | 22.59 |
September | 720.00 | 22.38 | 23.83 | 22.38 | 23.83 | 22.38 |
October | 744.00 | 22.50 | 28.00 | 22.51 | 28.00 | 22.52 |
November | 720.00 | 21.98 | 0.00 | 21.98 | 0.00 | 21.98 |
December | 744.00 | 21.89 | 0.00 | 21.89 | 0.00 | 21.89 |
Annual Sum or Average | 8760.00 | 22.06 | 229.83 | 22.07 | 229.83 | 22.08 |
Minimum of Months | 672.00 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
Maximum of Months | 744.00 | 22.57 | 93.83 | 22.58 | 93.83 | 22.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.33 | 21.58 | 32.83 | 21.56 | 32.83 | 21.54 |
February | 657.50 | 21.48 | 20.50 | 21.47 | 20.50 | 21.46 |
March | 724.50 | 21.45 | 17.50 | 21.43 | 17.50 | 21.41 |
April | 672.67 | 21.57 | 1.00 | 21.57 | 1.00 | 21.57 |
May | 715.33 | 21.60 | 0.33 | 21.60 | 0.33 | 21.60 |
June | 657.33 | 21.56 | 0.50 | 21.56 | 0.50 | 21.56 |
July | 637.83 | 21.50 | 2.33 | 21.51 | 2.33 | 21.51 |
August | 630.67 | 21.48 | 8.00 | 21.50 | 8.00 | 21.51 |
September | 640.83 | 21.54 | 6.33 | 21.54 | 5.50 | 21.55 |
October | 695.17 | 21.60 | 2.00 | 21.61 | 2.00 | 21.61 |
November | 697.67 | 21.59 | 23.67 | 21.58 | 23.67 | 21.56 |
December | 738.83 | 21.60 | 38.17 | 21.58 | 38.17 | 21.56 |
Annual Sum or Average | 8204.67 | 21.55 | 153.17 | 21.54 | 152.33 | 21.54 |
Minimum of Months | 630.67 | 21.45 | 0.33 | 21.43 | 0.33 | 21.41 |
Maximum of Months | 738.83 | 21.60 | 38.17 | 21.61 | 38.17 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.38 | 91.00 | 21.34 | 91.00 | 21.30 |
February | 671.33 | 21.39 | 36.33 | 21.37 | 36.33 | 21.36 |
March | 726.33 | 21.41 | 32.83 | 21.43 | 22.67 | 21.41 |
April | 611.00 | 21.63 | 61.50 | 21.91 | 2.83 | 21.91 |
May | 625.33 | 21.71 | 67.00 | 22.01 | 0.17 | 22.01 |
June | 540.83 | 22.03 | 135.50 | 22.68 | 23.50 | 22.79 |
July | 516.67 | 22.29 | 219.00 | 23.12 | 90.00 | 23.30 |
August | 530.83 | 22.21 | 219.33 | 22.94 | 107.00 | 23.09 |
September | 567.83 | 21.90 | 107.83 | 22.24 | 37.83 | 22.28 |
October | 693.83 | 22.00 | 52.67 | 22.11 | 39.33 | 22.16 |
November | 720.00 | 21.55 | 44.67 | 21.52 | 44.67 | 21.50 |
December | 744.00 | 21.40 | 94.17 | 21.36 | 94.17 | 21.32 |
Annual Sum or Average | 7692.00 | 21.71 | 1161.83 | 21.98 | 589.50 | 22.02 |
Minimum of Months | 516.67 | 21.38 | 32.83 | 21.34 | 0.17 | 21.30 |
Maximum of Months | 744.00 | 22.29 | 219.33 | 23.12 | 107.00 | 23.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 685.83 | 21.61 | 0.17 | 21.61 | 0.17 | 21.61 |
February | 641.17 | 21.59 | 0.67 | 21.59 | 0.67 | 21.58 |
March | 716.33 | 21.56 | 2.83 | 21.55 | 2.83 | 21.55 |
April | 714.83 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 744.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
June | 720.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
July | 742.17 | 21.73 | 0.83 | 21.73 | 0.83 | 21.73 |
August | 712.83 | 21.68 | 3.67 | 21.69 | 3.67 | 21.70 |
September | 656.33 | 21.58 | 0.33 | 21.58 | 0.33 | 21.58 |
October | 666.67 | 21.57 | 1.00 | 21.57 | 1.00 | 21.57 |
November | 664.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
December | 694.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
Annual Sum or Average | 8358.17 | 21.63 | 9.50 | 21.63 | 9.50 | 21.63 |
Minimum of Months | 641.17 | 21.56 | 0.00 | 21.55 | 0.00 | 21.55 |
Maximum of Months | 744.00 | 21.73 | 3.67 | 21.73 | 3.67 | 21.73 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 688.67 | 22.06 | 15.67 | 22.10 | 6.17 | 22.11 |
February | 620.17 | 22.11 | 14.83 | 22.15 | 2.83 | 22.15 |
March | 659.83 | 22.08 | 19.17 | 22.12 | 0.00 | 22.12 |
April | 532.67 | 22.09 | 61.83 | 22.24 | 10.33 | 22.26 |
May | 546.33 | 22.16 | 83.83 | 22.34 | 11.83 | 22.37 |
June | 452.00 | 22.25 | 203.00 | 22.63 | 74.50 | 22.72 |
July | 523.17 | 22.51 | 316.50 | 22.84 | 189.33 | 22.94 |
August | 597.50 | 22.56 | 324.83 | 22.85 | 253.83 | 22.96 |
September | 539.50 | 22.32 | 209.50 | 22.61 | 135.17 | 22.72 |
October | 583.83 | 22.29 | 119.67 | 22.48 | 56.83 | 22.56 |
November | 654.67 | 22.15 | 25.50 | 22.19 | 9.17 | 22.20 |
December | 710.50 | 22.13 | 4.17 | 22.14 | 0.00 | 22.14 |
Annual Sum or Average | 7108.83 | 22.22 | 1398.50 | 22.41 | 750.00 | 22.49 |
Minimum of Months | 452.00 | 22.06 | 4.17 | 22.10 | 0.00 | 22.11 |
Maximum of Months | 710.50 | 22.56 | 324.83 | 22.85 | 253.83 | 22.96 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 599.67 | 22.24 | 54.17 | 22.36 | 6.50 | 22.37 |
February | 508.17 | 22.25 | 59.00 | 22.38 | 3.17 | 22.39 |
March | 519.17 | 22.19 | 81.83 | 22.38 | 0.00 | 22.38 |
April | 409.17 | 22.20 | 182.17 | 22.60 | 10.50 | 22.62 |
May | 395.83 | 22.23 | 190.00 | 22.66 | 11.67 | 22.68 |
June | 304.33 | 22.49 | 332.33 | 23.01 | 75.83 | 23.08 |
July | 350.67 | 22.88 | 401.00 | 23.18 | 193.00 | 23.26 |
August | 448.50 | 22.90 | 394.17 | 23.16 | 255.33 | 23.25 |
September | 423.67 | 22.54 | 304.67 | 22.93 | 137.83 | 23.02 |
October | 477.00 | 22.42 | 185.83 | 22.73 | 57.17 | 22.80 |
November | 530.50 | 22.27 | 67.50 | 22.41 | 10.00 | 22.43 |
December | 634.50 | 22.32 | 30.17 | 22.38 | 0.00 | 22.38 |
Annual Sum or Average | 5601.17 | 22.39 | 2282.83 | 22.71 | 761.00 | 22.79 |
Minimum of Months | 304.33 | 22.19 | 30.17 | 22.36 | 0.00 | 22.37 |
Maximum of Months | 634.50 | 22.90 | 401.00 | 23.18 | 255.33 | 23.26 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 531.67 | 23.99 | 744.00 | 23.99 | 531.67 | 23.99 |
February | 482.33 | 23.99 | 672.00 | 23.99 | 482.33 | 23.99 |
March | 539.50 | 23.99 | 744.00 | 23.99 | 539.50 | 23.99 |
April | 536.00 | 23.99 | 720.00 | 23.99 | 536.00 | 23.99 |
May | 555.17 | 23.99 | 744.00 | 23.99 | 555.17 | 23.99 |
June | 552.00 | 23.99 | 720.00 | 23.99 | 552.00 | 23.99 |
July | 578.33 | 23.99 | 744.00 | 23.99 | 578.33 | 23.99 |
August | 580.33 | 23.99 | 744.00 | 23.99 | 580.33 | 23.99 |
September | 551.17 | 23.99 | 720.00 | 23.99 | 551.17 | 23.99 |
October | 549.00 | 23.99 | 744.00 | 23.99 | 549.00 | 23.99 |
November | 518.17 | 23.99 | 720.00 | 23.99 | 518.17 | 23.99 |
December | 524.67 | 23.99 | 744.00 | 23.99 | 524.67 | 23.99 |
Annual Sum or Average | 6498.33 | 23.99 | 8760.00 | 23.99 | 6498.33 | 23.99 |
Minimum of Months | 482.33 | 23.99 | 672.00 | 23.99 | 482.33 | 23.99 |
Maximum of Months | 580.33 | 23.99 | 744.00 | 23.99 | 580.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.00 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
February | 672.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
March | 726.50 | 22.51 | 0.50 | 22.51 | 0.00 | 22.51 |
April | 572.67 | 23.01 | 19.83 | 23.04 | 1.83 | 23.05 |
May | 619.50 | 23.12 | 24.17 | 23.15 | 0.00 | 23.15 |
June | 290.00 | 23.34 | 219.50 | 23.61 | 17.67 | 23.62 |
July | 102.33 | 23.78 | 609.33 | 23.93 | 91.67 | 23.91 |
August | 123.83 | 23.84 | 666.00 | 23.93 | 121.33 | 23.92 |
September | 183.00 | 23.40 | 283.17 | 23.71 | 36.33 | 23.71 |
October | 419.00 | 23.48 | 169.33 | 23.62 | 34.83 | 23.64 |
November | 705.67 | 22.95 | 0.00 | 22.95 | 0.00 | 22.95 |
December | 740.83 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
Annual Sum or Average | 5884.33 | 22.92 | 1991.83 | 23.18 | 303.67 | 23.20 |
Minimum of Months | 102.33 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
Maximum of Months | 740.83 | 23.84 | 666.00 | 23.93 | 121.33 | 23.92 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.84657 | 41.29836 | 0.05288 | 5.26626 |
February | 672.00000 | 22.24963 | 45.23260 | -0.0783 | 5.30266 |
March | 744.00000 | 22.03986 | 49.76168 | -0.1046 | 5.34029 |
April | 720.00000 | 21.94393 | 54.11828 | -0.1027 | 5.37722 |
May | 744.00000 | 21.94552 | 53.50944 | -1.2236 | 36.53063 |
June | 720.00000 | 21.84920 | 60.26957 | -1.2161 | 36.15071 |
July | 744.00000 | 22.19756 | 62.47275 | -1.0733 | 29.46194 |
August | 744.00000 | 22.30558 | 62.90340 | -1.0311 | 27.60008 |
September | 720.00000 | 22.62614 | 58.71292 | -0.9393 | 23.84805 |
October | 744.00000 | 22.92974 | 47.65031 | 0.11784 | 5.50593 |
November | 720.00000 | 23.01728 | 42.24580 | 0.10374 | 5.45981 |
December | 744.00000 | 22.87468 | 36.18970 | 0.02699 | 5.26782 |
Annual Sum or Average | 8760.00000 | 22.40387 | 51.21716 | -0.4578 | 15.99373 |
Minimum of Months | 672.00000 | 21.84920 | 36.18970 | -1.2236 | 5.26626 |
Maximum of Months | 744.00000 | 23.01728 | 62.90340 | 0.11784 | 36.53063 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.58732 | 41.77567 | 0.05624 | 6.52893 |
February | 672.00000 | 22.30073 | 45.21751 | -0.0058 | 6.37265 |
March | 744.00000 | 22.01665 | 49.63316 | -0.0581 | 6.46105 |
April | 720.00000 | 22.46514 | 52.53644 | 0.08419 | 6.10354 |
May | 744.00000 | 22.10515 | 52.97078 | -1.0877 | 30.77535 |
June | 720.00000 | 22.45604 | 58.39833 | -0.9218 | 23.55331 |
July | 744.00000 | 22.97665 | 60.38046 | -0.7127 | 16.12963 |
August | 744.00000 | 23.30107 | 60.22599 | -0.5898 | 12.89731 |
September | 720.00000 | 23.19023 | 57.16162 | -0.6434 | 14.91346 |
October | 744.00000 | 23.22738 | 47.05706 | 0.27238 | 7.48288 |
November | 720.00000 | 22.80522 | 42.65455 | 0.12313 | 6.43494 |
December | 744.00000 | 22.72110 | 36.53899 | 0.06306 | 6.38119 |
Annual Sum or Average | 8760.00000 | 22.68196 | 50.39634 | -0.2867 | 12.04093 |
Minimum of Months | 672.00000 | 22.01665 | 36.53899 | -1.0877 | 6.10354 |
Maximum of Months | 744.00000 | 23.30107 | 60.38046 | 0.27238 | 30.77535 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.15301 | 43.00064 | -0.0616 | 5.45456 |
February | 672.00000 | 22.06980 | 45.93194 | -0.0668 | 5.41697 |
March | 744.00000 | 21.93395 | 50.22852 | -0.0757 | 5.50471 |
April | 720.00000 | 22.23754 | 53.46728 | 0.02760 | 5.44488 |
May | 744.00000 | 22.18234 | 53.05420 | -1.0605 | 29.26547 |
June | 720.00000 | 22.39930 | 58.78875 | -0.9424 | 24.31901 |
July | 744.00000 | 22.67080 | 61.31732 | -0.8225 | 19.75441 |
August | 744.00000 | 22.77581 | 61.79469 | -0.7800 | 18.29592 |
September | 720.00000 | 22.67692 | 58.92891 | -0.8360 | 20.21524 |
October | 744.00000 | 22.71260 | 48.52469 | 0.12497 | 5.74265 |
November | 720.00000 | 22.35731 | 43.93800 | -0.0009 | 5.32617 |
December | 744.00000 | 22.26820 | 37.63667 | -0.0651 | 5.34911 |
Annual Sum or Average | 8760.00000 | 22.37174 | 51.40285 | -0.3818 | 12.55125 |
Minimum of Months | 672.00000 | 21.93395 | 37.63667 | -1.0605 | 5.32617 |
Maximum of Months | 744.00000 | 22.77581 | 61.79469 | 0.12497 | 29.26547 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99972 | 35.04312 | 0.92573 | 23.92842 |
February | 672.00000 | 23.99971 | 37.35333 | 0.93803 | 24.37258 |
March | 744.00000 | 23.99974 | 40.97874 | 0.96455 | 25.36251 |
April | 720.00000 | 23.99974 | 44.64101 | 1.00699 | 27.09868 |
May | 744.00000 | 23.99972 | 44.07162 | 0.36253 | 9.38030 |
June | 720.00000 | 23.99974 | 49.80387 | 0.42094 | 10.30553 |
July | 744.00000 | 23.99972 | 52.80071 | 0.45807 | 10.86356 |
August | 744.00000 | 23.99972 | 53.51772 | 0.46793 | 11.09319 |
September | 720.00000 | 23.99974 | 50.66382 | 0.42762 | 10.37291 |
October | 744.00000 | 23.99973 | 41.15365 | 0.99884 | 26.83311 |
November | 720.00000 | 23.99973 | 36.21786 | 0.94158 | 24.55065 |
December | 744.00000 | 23.99970 | 30.30592 | 0.89413 | 22.71022 |
Annual Sum or Average | 8760.00000 | 23.99973 | 43.06769 | 0.73261 | 18.87007 |
Minimum of Months | 672.00000 | 23.99970 | 30.30592 | 0.36253 | 9.38030 |
Maximum of Months | 744.00000 | 23.99974 | 53.51772 | 1.00699 | 27.09868 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.10175 | 45.52819 | 0.04797 | 5.70447 |
February | 672.00000 | 21.89998 | 48.66141 | -0.0009 | 5.52660 |
March | 744.00000 | 21.70168 | 53.13055 | -0.0354 | 5.53210 |
April | 720.00000 | 21.72785 | 57.24428 | 0.01126 | 5.38278 |
May | 744.00000 | 21.58329 | 57.03167 | -1.1390 | 32.76420 |
June | 720.00000 | 21.67225 | 63.42174 | -1.0544 | 28.98493 |
July | 744.00000 | 21.79176 | 66.50821 | -0.9696 | 25.40509 |
August | 744.00000 | 21.96439 | 66.76379 | -0.8896 | 22.24881 |
September | 720.00000 | 22.07803 | 63.12206 | -0.8696 | 21.66580 |
October | 744.00000 | 22.31267 | 51.97570 | 0.16211 | 6.22530 |
November | 720.00000 | 22.16585 | 46.76092 | 0.07790 | 5.72144 |
December | 744.00000 | 22.22555 | 40.16067 | 0.05118 | 5.69203 |
Annual Sum or Average | 8760.00000 | 21.93598 | 55.04946 | -0.3863 | 14.29623 |
Minimum of Months | 672.00000 | 21.58329 | 40.16067 | -1.1390 | 5.38278 |
Maximum of Months | 744.00000 | 22.31267 | 66.76379 | 0.16211 | 32.76420 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.63185 | 44.76610 | 0.09006 | 5.58033 |
February | 672.00000 | 22.51181 | 47.64673 | 0.07394 | 5.51096 |
March | 744.00000 | 22.36620 | 51.86815 | 0.06087 | 5.54290 |
April | 720.00000 | 22.50181 | 55.49571 | 0.12466 | 5.79635 |
May | 744.00000 | 22.45414 | 55.05058 | -0.9293 | 24.03614 |
June | 720.00000 | 22.59130 | 60.94461 | -0.8356 | 20.57117 |
July | 744.00000 | 22.74198 | 63.78950 | -0.7548 | 17.79943 |
August | 744.00000 | 22.83668 | 64.29725 | -0.7147 | 16.49251 |
September | 720.00000 | 22.84200 | 61.14228 | -0.7347 | 17.03555 |
October | 744.00000 | 22.97048 | 50.66779 | 0.22726 | 6.51785 |
November | 720.00000 | 22.75713 | 45.83977 | 0.13257 | 5.74943 |
December | 744.00000 | 22.73271 | 39.58618 | 0.08399 | 5.44869 |
Annual Sum or Average | 8760.00000 | 22.66261 | 53.44540 | -0.2667 | 11.37763 |
Minimum of Months | 672.00000 | 22.36620 | 39.58618 | -0.9293 | 5.44869 |
Maximum of Months | 744.00000 | 22.97048 | 64.29725 | 0.22726 | 24.03614 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63595 | 45.93017 | -0.2153 | 6.83380 |
February | 672.00000 | 21.56873 | 49.06037 | -0.2143 | 6.68642 |
March | 744.00000 | 21.53889 | 52.44804 | -0.2062 | 6.65550 |
April | 720.00000 | 21.69086 | 53.82573 | -0.1206 | 6.15845 |
May | 744.00000 | 21.66285 | 54.10319 | -1.2544 | 38.92596 |
June | 720.00000 | 21.70935 | 56.93443 | -1.1887 | 35.82852 |
July | 744.00000 | 21.76131 | 57.47182 | -1.1321 | 33.33572 |
August | 744.00000 | 21.76563 | 57.80385 | -1.1245 | 33.04981 |
September | 720.00000 | 21.74269 | 56.74104 | -1.1602 | 34.69151 |
October | 744.00000 | 21.73359 | 49.70019 | -0.1086 | 6.14660 |
November | 720.00000 | 21.68038 | 46.55021 | -0.1807 | 6.58878 |
December | 744.00000 | 21.66048 | 40.81840 | -0.2303 | 7.00576 |
Annual Sum or Average | 8760.00000 | 21.67984 | 51.78569 | -0.5970 | 18.56380 |
Minimum of Months | 672.00000 | 21.53889 | 40.81840 | -1.2544 | 6.14660 |
Maximum of Months | 744.00000 | 21.76563 | 57.80385 | -0.1086 | 38.92596 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.45883 | 47.39237 | -0.2931 | 7.40423 |
February | 672.00000 | 21.46111 | 50.17972 | -0.2641 | 7.00027 |
March | 744.00000 | 21.50157 | 53.46414 | -0.2320 | 6.87977 |
April | 720.00000 | 21.96720 | 54.11192 | -0.0764 | 6.53066 |
May | 744.00000 | 22.05865 | 53.34205 | -1.1450 | 34.73588 |
June | 720.00000 | 22.52634 | 55.80696 | -0.9496 | 27.69446 |
July | 744.00000 | 22.80065 | 56.99617 | -0.8238 | 23.37722 |
August | 744.00000 | 22.71506 | 58.47288 | -0.8503 | 23.88317 |
September | 720.00000 | 22.31380 | 57.83781 | -1.0122 | 28.88202 |
October | 744.00000 | 22.15941 | 50.68539 | -0.0419 | 6.21954 |
November | 720.00000 | 21.61722 | 48.17042 | -0.2279 | 6.79563 |
December | 744.00000 | 21.50334 | 41.87455 | -0.3094 | 7.54296 |
Annual Sum or Average | 8760.00000 | 22.01033 | 52.36137 | -0.5204 | 15.62854 |
Minimum of Months | 672.00000 | 21.45883 | 41.87455 | -1.1450 | 6.21954 |
Maximum of Months | 744.00000 | 22.80065 | 58.47288 | -0.0419 | 34.73588 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41710 | 44.54753 | -0.3174 | 7.39771 |
February | 672.00000 | 21.40821 | 47.40119 | -0.2972 | 7.05158 |
March | 744.00000 | 21.43301 | 50.83248 | -0.2687 | 6.73363 |
April | 720.00000 | 21.62900 | 53.21887 | -0.1952 | 6.16830 |
May | 744.00000 | 21.74109 | 52.29040 | -1.3001 | 40.71772 |
June | 720.00000 | 22.09524 | 56.14299 | -1.1431 | 33.48308 |
July | 744.00000 | 22.32126 | 59.01978 | -1.0411 | 29.17125 |
August | 744.00000 | 22.25359 | 60.45946 | -1.0631 | 30.01275 |
September | 720.00000 | 21.95525 | 58.19102 | -1.1887 | 35.40386 |
October | 744.00000 | 21.93426 | 49.32611 | -0.1360 | 6.09485 |
November | 720.00000 | 21.45235 | 45.85671 | -0.2933 | 7.07451 |
December | 744.00000 | 21.40678 | 39.29873 | -0.3506 | 7.77595 |
Annual Sum or Average | 8760.00000 | 21.75645 | 51.39323 | -0.6348 | 18.15440 |
Minimum of Months | 672.00000 | 21.40678 | 39.29873 | -1.3001 | 6.09485 |
Maximum of Months | 744.00000 | 22.32126 | 60.45946 | -0.1360 | 40.71772 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.68274 | 45.69916 | -0.2026 | 6.70365 |
February | 672.00000 | 21.58549 | 49.09218 | -0.2138 | 6.66426 |
March | 744.00000 | 21.58155 | 52.11662 | -0.1989 | 6.61409 |
April | 720.00000 | 21.73185 | 53.68325 | -0.1166 | 6.14927 |
May | 744.00000 | 21.69881 | 53.93326 | -1.2558 | 38.99015 |
June | 720.00000 | 21.72644 | 57.30646 | -1.1978 | 36.25411 |
July | 744.00000 | 21.78833 | 57.56372 | -1.1345 | 33.46892 |
August | 744.00000 | 21.79156 | 57.67202 | -1.1228 | 32.98756 |
September | 720.00000 | 21.74124 | 57.49902 | -1.1748 | 35.32290 |
October | 744.00000 | 21.74802 | 49.91743 | -0.1077 | 6.11226 |
November | 720.00000 | 21.70334 | 46.70706 | -0.1790 | 6.52149 |
December | 744.00000 | 21.69194 | 40.76252 | -0.2236 | 6.89795 |
Annual Sum or Average | 8760.00000 | 21.70672 | 51.83031 | -0.5963 | 18.62752 |
Minimum of Months | 672.00000 | 21.58155 | 40.76252 | -1.2558 | 6.11226 |
Maximum of Months | 744.00000 | 21.79156 | 57.67202 | -0.1077 | 38.99015 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.47509 | 47.07844 | -0.2866 | 7.22542 |
February | 672.00000 | 21.44119 | 50.22279 | -0.2723 | 6.93228 |
March | 744.00000 | 21.52026 | 53.18166 | -0.2302 | 6.74964 |
April | 720.00000 | 21.91878 | 54.32015 | -0.0910 | 6.15012 |
May | 744.00000 | 21.99566 | 53.79556 | -1.1733 | 35.38285 |
June | 720.00000 | 22.33396 | 57.03629 | -1.0173 | 28.98973 |
July | 744.00000 | 22.64437 | 57.94123 | -0.8778 | 24.06972 |
August | 744.00000 | 22.62062 | 59.05636 | -0.8821 | 24.16639 |
September | 720.00000 | 22.18981 | 59.27216 | -1.0618 | 30.43148 |
October | 744.00000 | 22.14606 | 51.04687 | -0.0475 | 6.02825 |
November | 720.00000 | 21.56899 | 48.30946 | -0.2424 | 6.71751 |
December | 744.00000 | 21.50956 | 41.92018 | -0.3076 | 7.37693 |
Annual Sum or Average | 8760.00000 | 21.95057 | 52.76441 | -0.5423 | 15.90067 |
Minimum of Months | 672.00000 | 21.44119 | 41.92018 | -1.1733 | 6.02825 |
Maximum of Months | 744.00000 | 22.64437 | 59.27216 | -0.0475 | 35.38285 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59440 | 47.02897 | -0.2418 | 7.24436 |
February | 672.00000 | 21.51914 | 50.26707 | -0.2408 | 7.07440 |
March | 744.00000 | 21.50248 | 53.70458 | -0.2250 | 7.01364 |
April | 720.00000 | 21.68709 | 55.00232 | -0.1202 | 6.33154 |
May | 744.00000 | 21.66363 | 55.21449 | -1.2563 | 39.25973 |
June | 720.00000 | 21.71179 | 57.98571 | -1.1812 | 35.70150 |
July | 744.00000 | 21.76210 | 58.21568 | -1.1217 | 33.07815 |
August | 744.00000 | 21.76177 | 58.75205 | -1.1176 | 32.93594 |
September | 720.00000 | 21.73300 | 58.25132 | -1.1609 | 34.92427 |
October | 744.00000 | 21.71580 | 50.88086 | -0.1170 | 6.33264 |
November | 720.00000 | 21.64502 | 47.76795 | -0.2030 | 6.90761 |
December | 744.00000 | 21.61432 | 41.75528 | -0.2605 | 7.45359 |
Annual Sum or Average | 8760.00000 | 21.65998 | 52.90358 | -0.6061 | 18.75860 |
Minimum of Months | 672.00000 | 21.50248 | 41.75528 | -1.2563 | 6.33154 |
Maximum of Months | 744.00000 | 21.76210 | 58.75205 | -0.1170 | 39.25973 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37914 | 48.60753 | -0.3328 | 8.02289 |
February | 672.00000 | 21.39291 | 51.50690 | -0.2976 | 7.52110 |
March | 744.00000 | 21.47771 | 54.72672 | -0.2497 | 7.29317 |
April | 720.00000 | 22.03090 | 54.93703 | -0.0613 | 6.95005 |
May | 744.00000 | 22.11636 | 54.05423 | -1.1261 | 34.63700 |
June | 720.00000 | 22.64504 | 55.87828 | -0.9022 | 27.31770 |
July | 744.00000 | 22.94239 | 56.46166 | -0.7654 | 22.95720 |
August | 744.00000 | 22.82425 | 58.21888 | -0.8050 | 23.56389 |
September | 720.00000 | 22.33916 | 58.75952 | -0.9994 | 28.93131 |
October | 744.00000 | 22.11933 | 51.74820 | -0.0540 | 6.45705 |
November | 720.00000 | 21.54839 | 49.57220 | -0.2608 | 7.25937 |
December | 744.00000 | 21.40425 | 42.91426 | -0.3566 | 8.28409 |
Annual Sum or Average | 8760.00000 | 22.02212 | 53.11036 | -0.5190 | 15.81375 |
Minimum of Months | 672.00000 | 21.37914 | 42.91426 | -1.1261 | 6.45705 |
Maximum of Months | 744.00000 | 22.94239 | 58.75952 | -0.0540 | 34.63700 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74928 | 44.84543 | -0.1541 | 6.68424 |
February | 672.00000 | 21.66593 | 48.25757 | -0.1797 | 6.65843 |
March | 744.00000 | 21.62205 | 51.43141 | -0.1900 | 6.72529 |
April | 720.00000 | 21.70353 | 53.86257 | -0.1380 | 6.33549 |
May | 744.00000 | 21.63167 | 55.24576 | -1.3139 | 41.85592 |
June | 720.00000 | 21.66370 | 59.37315 | -1.2565 | 39.01347 |
July | 744.00000 | 21.73511 | 60.38742 | -1.1958 | 36.26588 |
August | 744.00000 | 21.75115 | 59.58860 | -1.1702 | 35.17685 |
September | 720.00000 | 21.73050 | 56.81646 | -1.1861 | 36.02996 |
October | 744.00000 | 21.75230 | 49.44439 | -0.1004 | 6.30312 |
November | 720.00000 | 21.76235 | 45.46627 | -0.1410 | 6.57921 |
December | 744.00000 | 21.76301 | 40.20165 | -0.1694 | 6.86462 |
Annual Sum or Average | 8760.00000 | 21.71121 | 52.08836 | -0.6022 | 19.62009 |
Minimum of Months | 672.00000 | 21.62205 | 40.20165 | -1.3139 | 6.30312 |
Maximum of Months | 744.00000 | 21.76301 | 60.38742 | -0.1004 | 41.85592 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.15559 | 45.47612 | 0.03140 | 5.70588 |
February | 672.00000 | 22.20904 | 47.97491 | 0.06442 | 5.67216 |
March | 744.00000 | 22.21418 | 52.00121 | 0.09273 | 5.72725 |
April | 720.00000 | 22.38832 | 55.54527 | 0.17861 | 6.19145 |
May | 744.00000 | 22.46169 | 54.74325 | -0.8026 | 19.43706 |
June | 720.00000 | 22.60393 | 60.59804 | -0.6946 | 16.01743 |
July | 744.00000 | 22.67212 | 63.60254 | -0.6371 | 14.31690 |
August | 744.00000 | 22.64563 | 64.47907 | -0.6445 | 14.60664 |
September | 720.00000 | 22.53999 | 61.72760 | -0.7168 | 16.70726 |
October | 744.00000 | 22.50356 | 51.45428 | 0.19224 | 6.44535 |
November | 720.00000 | 22.25822 | 46.58703 | 0.07353 | 5.76493 |
December | 744.00000 | 22.18609 | 40.24470 | 0.00772 | 5.58517 |
Annual Sum or Average | 8760.00000 | 22.40431 | 53.72349 | -0.2398 | 10.20768 |
Minimum of Months | 672.00000 | 22.15559 | 40.24470 | -0.8026 | 5.58517 |
Maximum of Months | 744.00000 | 22.67212 | 64.47907 | 0.19224 | 19.43706 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.46833 | 44.82304 | 0.12818 | 6.00295 |
February | 672.00000 | 22.52402 | 47.25465 | 0.16157 | 6.12999 |
March | 744.00000 | 22.53971 | 51.19110 | 0.19329 | 6.30154 |
April | 720.00000 | 22.68031 | 54.75010 | 0.26836 | 6.99215 |
May | 744.00000 | 22.74997 | 53.96090 | -0.6775 | 15.44550 |
June | 720.00000 | 22.86197 | 59.78046 | -0.5817 | 12.86870 |
July | 744.00000 | 22.91070 | 62.79835 | -0.5327 | 11.64630 |
August | 744.00000 | 22.87776 | 63.68148 | -0.5427 | 11.95582 |
September | 720.00000 | 22.78581 | 60.94039 | -0.6097 | 13.63455 |
October | 744.00000 | 22.74997 | 50.82384 | 0.26817 | 7.13473 |
November | 720.00000 | 22.54946 | 45.95134 | 0.16311 | 6.20375 |
December | 744.00000 | 22.48643 | 39.70203 | 0.10038 | 5.78845 |
Annual Sum or Average | 8760.00000 | 22.68293 | 52.99233 | -0.1403 | 9.19219 |
Minimum of Months | 672.00000 | 22.46833 | 39.70203 | -0.6775 | 5.78845 |
Maximum of Months | 744.00000 | 22.91070 | 63.68148 | 0.26836 | 15.44550 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99128 | 42.33012 | 1.13760 | 33.64106 |
February | 672.00000 | 23.99126 | 44.50614 | 1.15206 | 34.24931 |
March | 744.00000 | 23.99125 | 48.00957 | 1.18011 | 35.53118 |
April | 720.00000 | 23.99144 | 51.54703 | 1.23328 | 38.04427 |
May | 744.00000 | 23.99142 | 50.98750 | 0.66407 | 17.57281 |
June | 720.00000 | 23.99171 | 56.52184 | 0.72749 | 19.37035 |
July | 744.00000 | 23.99193 | 59.41690 | 0.77254 | 20.72636 |
August | 744.00000 | 23.99192 | 60.09119 | 0.77681 | 20.81633 |
September | 720.00000 | 23.99161 | 57.31128 | 0.72873 | 19.36391 |
October | 744.00000 | 23.99137 | 48.12281 | 1.21933 | 37.43292 |
November | 720.00000 | 23.99130 | 43.41033 | 1.15354 | 34.33958 |
December | 744.00000 | 23.99112 | 37.71105 | 1.10667 | 32.26079 |
Annual Sum or Average | 8760.00000 | 23.99147 | 50.01816 | 0.98663 | 28.57520 |
Minimum of Months | 672.00000 | 23.99112 | 37.71105 | 0.66407 | 17.57281 |
Maximum of Months | 744.00000 | 23.99193 | 60.09119 | 1.23328 | 38.04427 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15535 | 42.14626 | -0.3355 | 7.56038 |
February | 672.00000 | 21.09911 | 45.16903 | -0.3318 | 7.40487 |
March | 744.00000 | 21.06699 | 49.50685 | -0.3173 | 7.18942 |
April | 720.00000 | 21.22579 | 53.39675 | -0.2471 | 6.41601 |
May | 744.00000 | 21.32814 | 52.46704 | -1.3830 | 44.66882 |
June | 720.00000 | 21.61385 | 58.28079 | -1.2457 | 37.58162 |
July | 744.00000 | 21.83939 | 61.25530 | -1.1463 | 32.72253 |
August | 744.00000 | 21.83068 | 62.21225 | -1.1441 | 32.61281 |
September | 720.00000 | 21.68420 | 59.16723 | -1.2149 | 36.09120 |
October | 744.00000 | 21.77131 | 47.90237 | -0.1373 | 5.68389 |
November | 720.00000 | 21.26264 | 43.39990 | -0.2953 | 7.01946 |
December | 744.00000 | 21.17869 | 36.55684 | -0.3597 | 7.86325 |
Annual Sum or Average | 8760.00000 | 21.42372 | 50.97405 | -0.6819 | 19.47375 |
Minimum of Months | 672.00000 | 21.06699 | 36.55684 | -1.3830 | 5.68389 |
Maximum of Months | 744.00000 | 21.83939 | 62.21225 | -0.1373 | 44.66882 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.71397 | 45.03458 | -0.2186 | 6.26505 |
February | 672.00000 | 21.68390 | 47.99842 | -0.2092 | 6.01445 |
March | 744.00000 | 21.52580 | 52.37246 | -0.2221 | 6.21189 |
April | 720.00000 | 21.84477 | 55.70880 | -0.1212 | 5.49815 |
May | 744.00000 | 21.90526 | 54.98360 | -1.2327 | 36.99480 |
June | 720.00000 | 22.15781 | 60.69834 | -1.1079 | 31.01123 |
July | 744.00000 | 22.48301 | 63.19590 | -0.9754 | 25.16396 |
August | 744.00000 | 22.57226 | 63.77262 | -0.9399 | 23.70907 |
September | 720.00000 | 22.37659 | 61.06721 | -1.0270 | 27.38092 |
October | 744.00000 | 22.50281 | 50.21834 | 0.01396 | 5.27064 |
November | 720.00000 | 21.98293 | 45.97828 | -0.1452 | 5.60236 |
December | 744.00000 | 21.88614 | 39.42823 | -0.2099 | 6.06361 |
Annual Sum or Average | 8760.00000 | 22.05556 | 53.38825 | -0.5349 | 15.48831 |
Minimum of Months | 672.00000 | 21.52580 | 39.42823 | -1.2327 | 5.27064 |
Maximum of Months | 744.00000 | 22.57226 | 63.77262 | 0.01396 | 36.99480 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.60449 | 42.89016 | -0.0083 | 5.60892 |
February | 672.00000 | 22.63767 | 45.58631 | 0.01634 | 5.26945 |
March | 744.00000 | 22.53840 | 49.51871 | 0.01826 | 5.50314 |
April | 720.00000 | 23.17330 | 51.86770 | 0.19605 | 6.20370 |
May | 744.00000 | 23.23369 | 51.22139 | -0.7841 | 18.44196 |
June | 720.00000 | 23.64057 | 56.00086 | -0.6027 | 12.92617 |
July | 744.00000 | 23.90464 | 58.32452 | -0.4840 | 9.95575 |
August | 744.00000 | 23.91587 | 59.08078 | -0.4735 | 9.73087 |
September | 720.00000 | 23.72308 | 56.73771 | -0.5660 | 11.94183 |
October | 744.00000 | 23.66328 | 47.16235 | 0.29563 | 7.16297 |
November | 720.00000 | 22.97039 | 43.62272 | 0.08850 | 5.44962 |
December | 744.00000 | 22.76936 | 37.68122 | -0.0018 | 5.29335 |
Annual Sum or Average | 8760.00000 | 23.23451 | 49.98778 | -0.1935 | 8.64600 |
Minimum of Months | 672.00000 | 22.53840 | 37.68122 | -0.7841 | 5.26945 |
Maximum of Months | 744.00000 | 23.91587 | 59.08078 | 0.29563 | 18.44196 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60209 | 43.96441 | 0.19476 | 6.09153 |
February | 672.00000 | 23.63753 | 47.16665 | 0.22129 | 6.15390 |
March | 744.00000 | 23.52090 | 50.71735 | 0.21605 | 6.21235 |
April | 720.00000 | 23.84815 | 52.15740 | 0.30968 | 7.13030 |
May | 744.00000 | 23.94212 | 50.48671 | -0.6203 | 13.13951 |
June | 720.00000 | 23.99887 | 53.88421 | -0.5547 | 11.46346 |
July | 744.00000 | 23.99992 | 56.57372 | -0.5171 | 10.60589 |
August | 744.00000 | 23.99991 | 57.77146 | -0.5106 | 10.45905 |
September | 720.00000 | 23.99975 | 54.75887 | -0.5430 | 11.22682 |
October | 744.00000 | 23.99854 | 45.30938 | 0.32805 | 7.37887 |
November | 720.00000 | 23.87659 | 44.23366 | 0.26639 | 6.63327 |
December | 744.00000 | 23.72997 | 38.92058 | 0.19177 | 5.90888 |
Annual Sum or Average | 8760.00000 | 23.84698 | 49.66505 | -0.0868 | 8.54686 |
Minimum of Months | 672.00000 | 23.52090 | 38.92058 | -0.6203 | 5.90888 |
Maximum of Months | 744.00000 | 23.99992 | 57.77146 | 0.32805 | 13.13951 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.393898E+11 | 78243.86 | 15-JAN-09:52 | 690.39 | 0.126303E+12 | 0.00 | 0.165693E+12 | 2.98 | 3.99 | 14-JAN-09:52 | 0.00 | 0.00 |
February | 0.272098E+11 | 75607.84 | 01-FEB-09:52 | 640.58 | 0.861762E+11 | 0.00 | 0.113386E+12 | 3.06 | 3.92 | 01-FEB-09:52 | 0.00 | 0.00 |
March | 0.275505E+11 | 70925.88 | 11-MAR-09:51 | 668.08 | 0.886282E+11 | 0.00 | 0.116179E+12 | 2.90 | 3.97 | 23-MAR-15:25 | 0.00 | 0.00 |
April | 0.503433E+11 | 71424.73 | 26-APR-10:35 | 713.33 | 0.161097E+12 | 0.00 | 0.211440E+12 | 3.17 | 3.93 | 26-APR-08:52 | 0.00 | 0.00 |
May | 0.524994E+11 | 56672.82 | 03-MAY-09:50 | 743.22 | 0.163818E+12 | 0.00 | 0.216318E+12 | 3.15 | 3.85 | 04-MAY-08:53 | 0.00 | 0.00 |
June | 0.793591E+11 | 88197.68 | 29-JUN-18:03 | 720.00 | 0.262288E+12 | 0.00 | 0.341647E+12 | 3.22 | 4.37 | 29-JUN-18:03 | 0.00 | 0.00 |
July | 0.128438E+12 | 114845.80 | 19-JUL-15:13 | 744.00 | 0.471275E+12 | 0.00 | 0.599713E+12 | 3.53 | 4.53 | 31-JUL-21:54 | 0.00 | 0.00 |
August | 0.139587E+12 | 117900.07 | 17-AUG-15:13 | 744.00 | 0.524449E+12 | 0.00 | 0.664036E+12 | 3.64 | 4.51 | 24-AUG-18:03 | 0.00 | 0.00 |
September | 0.994796E+11 | 126721.29 | 29-SEP-15:13 | 720.00 | 0.345523E+12 | 0.00 | 0.445002E+12 | 3.35 | 4.46 | 22-SEP-08:52 | 0.00 | 0.00 |
October | 0.106368E+12 | 129493.41 | 14-OCT-15:13 | 744.00 | 0.374189E+12 | 0.00 | 0.480557E+12 | 3.38 | 4.53 | 05-OCT-18:03 | 0.00 | 0.00 |
November | 0.424926E+11 | 88661.32 | 19-NOV-09:41 | 715.50 | 0.135945E+12 | 0.00 | 0.178437E+12 | 3.18 | 4.00 | 28-NOV-09:52 | 0.00 | 0.00 |
December | 0.429853E+11 | 87022.75 | 05-DEC-09:41 | 709.17 | 0.139983E+12 | 0.00 | 0.182969E+12 | 3.08 | 4.08 | 16-DEC-09:52 | 0.00 | 0.00 |
Annual Sum or Average | 0.835702E+12 | 8552.28 | 0.287967E+13 | 0.00 | 0.371538E+13 | 3.22 | 0.00 | 0.00 | ||||
Minimum of Months | 0.272098E+11 | 56672.82 | 640.58 | 0.861762E+11 | 0.00 | 0.113386E+12 | 2.90 | 3.85 | 0.00 | 0.00 | ||
Maximum of Months | 0.139587E+12 | 129493.41 | 744.00 | 0.524449E+12 | 0.00 | 0.664036E+12 | 3.64 | 4.53 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.254979E+11 | 0.00 | 595.28 | 105027.53 | 08-JAN-06:50 | 0.00 | 41.78 | 56.51 | 0.10 | 0.00 | 0.04 | 0.42 | 08-JAN-06:50 |
February | 0.124267E+11 | 0.00 | 563.88 | 62931.15 | 05-FEB-06:00 | 0.00 | 43.06 | 57.27 | 0.06 | 0.00 | 0.02 | 0.25 | 05-FEB-06:00 |
March | 0.226238E+11 | 0.00 | 666.78 | 85420.26 | 30-MAR-03:00 | 0.00 | 41.89 | 58.25 | 0.10 | 0.00 | 0.03 | 0.34 | 30-MAR-03:00 |
April | 0.513014E+10 | 0.00 | 486.33 | 41150.14 | 01-APR-06:00 | 0.00 | 41.41 | 53.73 | 0.03 | 0.00 | 0.01 | 0.17 | 01-APR-06:00 |
May | 0.533986E+10 | 0.00 | 537.45 | 32398.67 | 14-MAY-04:50 | 0.00 | 37.35 | 53.19 | 0.02 | 0.00 | 0.01 | 0.13 | 14-MAY-04:50 |
June | 0.129184E+10 | 0.00 | 308.97 | 16917.20 | 23-JUN-08:55 | 0.00 | 31.55 | 43.04 | 0.01 | 0.00 | 0.00 | 0.07 | 23-JUN-08:55 |
July | 0.328708E+09 | 0.00 | 122.21 | 15753.65 | 12-JUL-08:57 | 0.00 | 27.77 | 32.99 | 0.00 | 0.00 | 0.00 | 0.06 | 12-JUL-08:57 |
August | 0.105049E+09 | 0.00 | 38.61 | 14614.37 | 22-AUG-08:54 | 0.00 | 32.51 | 33.97 | 0.00 | 0.00 | 0.00 | 0.06 | 22-AUG-08:54 |
September | 0.479272E+09 | 0.00 | 90.57 | 16351.90 | 28-SEP-08:55 | 0.00 | 35.98 | 38.82 | 0.00 | 0.00 | 0.00 | 0.07 | 28-SEP-08:55 |
October | 0.175907E+10 | 0.00 | 181.61 | 17916.22 | 30-OCT-04:00 | 0.00 | 39.57 | 44.50 | 0.01 | 0.00 | 0.00 | 0.07 | 30-OCT-04:00 |
November | 0.933371E+10 | 0.00 | 445.92 | 41857.36 | 24-NOV-04:00 | 0.00 | 42.27 | 53.36 | 0.04 | 0.00 | 0.01 | 0.17 | 24-NOV-04:00 |
December | 0.203666E+11 | 0.00 | 529.40 | 66002.70 | 24-DEC-04:00 | 0.00 | 42.50 | 55.47 | 0.08 | 0.00 | 0.03 | 0.27 | 24-DEC-04:00 |
Annual Sum or Average | 0.104683E+12 | 0.00 | 4567.02 | 0.00 | 38.10 | 48.37 | 0.04 | 0.00 | 0.01 | ||||
Minimum of Months | 0.105049E+09 | 0.00 | 38.61 | 14614.37 | 0.00 | 27.77 | 32.99 | 0.00 | 0.00 | 0.00 | 0.06 | ||
Maximum of Months | 0.254979E+11 | 0.00 | 666.78 | 105027.53 | 0.00 | 43.06 | 58.25 | 0.10 | 0.00 | 0.04 | 0.42 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.635778E+11 | 0.00 | 298.12 | 0.632546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 196865.43 | 14-JAN-11:35 | 196865.43 | 14-JAN-11:35 | 0.00 | 0.00 | 0.00 |
February | 0.370519E+11 | 0.00 | 253.19 | 0.360528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188283.77 | 01-FEB-11:50 | 188283.77 | 01-FEB-11:50 | 0.00 | 0.00 | 0.00 |
March | 0.406657E+11 | 0.00 | 227.59 | 0.397799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189283.17 | 23-MAR-10:50 | 177866.42 | 11-MAR-11:35 | 0.00 | 0.00 | 0.00 |
April | 0.938925E+11 | 0.00 | 367.24 | 0.917320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 236936.64 | 26-APR-10:35 | 198565.56 | 30-APR-10:50 | 0.00 | 0.00 | 0.00 |
May | 0.101448E+12 | 0.00 | 446.23 | 0.100046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 167489.44 | 18-MAY-10:50 | 160843.24 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 |
June | 0.181973E+12 | 0.00 | 616.33 | 0.158946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 304958.23 | 29-JUN-18:03 | 184607.44 | 29-JUN-10:50 | 0.00 | 0.00 | 0.00 |
July | 0.352194E+12 | 0.00 | 735.50 | 0.235829E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 358749.24 | 31-JUL-18:20 | 218178.56 | 19-JUL-10:50 | 0.00 | 0.00 | 0.00 |
August | 0.394523E+12 | 0.00 | 736.83 | 0.245219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 347184.11 | 14-AUG-10:35 | 217907.40 | 14-AUG-10:50 | 0.00 | 0.00 | 0.00 |
September | 0.241359E+12 | 0.00 | 676.33 | 0.184896E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345716.29 | 22-SEP-10:35 | 300691.37 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 |
October | 0.263710E+12 | 0.00 | 620.67 | 0.213006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 330575.54 | 04-OCT-18:03 | 312873.53 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 |
November | 0.671881E+11 | 0.00 | 361.75 | 0.660718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204211.28 | 19-NOV-11:35 | 204211.28 | 19-NOV-11:35 | 0.00 | 0.00 | 0.00 |
December | 0.725422E+11 | 0.00 | 311.36 | 0.725389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186801.81 | 19-DEC-11:35 | 186801.81 | 19-DEC-11:35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191012E+13 | 0.00 | 5651.15 | 0.150737E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.370519E+11 | 0.00 | 227.59 | 0.360528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167489.44 | 160843.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.394523E+12 | 0.00 | 736.83 | 0.245219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 358749.24 | 312873.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.325706E+10 | 0.00 | 159.67 | 0.323404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20570.98 | 13-JAN-14:00 | 20570.98 | 13-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.176477E+10 | 0.00 | 122.33 | 0.171146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17583.23 | 01-FEB-09:53 | 17583.23 | 01-FEB-09:53 | 0.00 | 0.00 | 0.00 |
March | 0.195362E+10 | 0.00 | 100.67 | 0.180527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22012.17 | 22-MAR-13:00 | 17611.20 | 11-MAR-13:15 | 0.00 | 0.00 | 0.00 |
April | 0.490019E+10 | 0.00 | 196.33 | 0.461280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22090.96 | 26-APR-13:00 | 22090.96 | 26-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.520930E+10 | 0.00 | 255.83 | 0.511855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18829.64 | 04-MAY-13:00 | 17662.38 | 03-MAY-12:20 | 0.00 | 0.00 | 0.00 |
June | 0.118877E+11 | 0.00 | 440.50 | 0.944832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30817.80 | 29-JUN-12:15 | 17826.82 | 29-JUN-12:15 | 0.00 | 0.00 | 0.00 |
July | 0.270221E+11 | 0.00 | 560.33 | 0.158139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40153.36 | 31-JUL-12:15 | 23766.73 | 31-JUL-12:15 | 0.00 | 0.00 | 0.00 |
August | 0.309007E+11 | 0.00 | 562.17 | 0.166894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38594.96 | 18-AUG-12:15 | 22287.37 | 18-AUG-12:15 | 0.00 | 0.00 | 0.00 |
September | 0.175428E+11 | 0.00 | 498.50 | 0.122681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39619.58 | 22-SEP-12:15 | 35123.90 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.195118E+11 | 0.00 | 442.00 | 0.143145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38111.08 | 01-OCT-12:15 | 34150.37 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 |
November | 0.327790E+10 | 0.00 | 196.50 | 0.321606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21037.50 | 19-NOV-13:15 | 21037.50 | 19-NOV-13:15 | 0.00 | 0.00 | 0.00 |
December | 0.398719E+10 | 0.00 | 167.83 | 0.398506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20480.92 | 05-DEC-09:55 | 20480.92 | 05-DEC-09:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131215E+12 | 0.00 | 3702.67 | 0.922174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.176477E+10 | 0.00 | 100.67 | 0.171146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17583.23 | 17583.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.309007E+11 | 0.00 | 562.17 | 0.166894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40153.36 | 35123.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.192029E+10 | 0.00 | 446.08 | 0.100469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12060.31 | 21-JAN-09:01 | 11832.13 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.172638E+10 | 0.00 | 373.47 | 0.937799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12046.53 | 13-FEB-16:12 | 11830.38 | 06-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.185637E+10 | 0.00 | 381.50 | 0.855215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11745.00 | 18-MAR-08:61 | 10738.72 | 19-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.368536E+10 | 0.00 | 561.55 | 0.177545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11540.51 | 08-APR-08:62 | 11498.49 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.345808E+10 | 0.00 | 561.76 | 0.158406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11975.24 | 06-MAY-08:62 | 11249.01 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.487246E+10 | 0.00 | 597.23 | 0.227038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12186.45 | 28-JUN-08:62 | 10774.59 | 14-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.688042E+10 | 0.00 | 669.21 | 0.337506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12599.05 | 31-JUL-08:62 | 10756.91 | 06-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.714508E+10 | 0.00 | 683.64 | 0.352741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12942.22 | 18-AUG-08:62 | 10726.09 | 20-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.555471E+10 | 0.00 | 640.14 | 0.264846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12777.87 | 22-SEP-08:62 | 10744.33 | 16-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.504055E+10 | 0.00 | 641.77 | 0.297268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12687.23 | 01-OCT-08:62 | 11833.67 | 18-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.258594E+10 | 0.00 | 529.88 | 0.136555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12279.05 | 12-NOV-09:02 | 11831.49 | 22-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.216098E+10 | 0.00 | 473.26 | 0.151318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11832.45 | 30-DEC-16:11 | 11832.45 | 30-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468866E+11 | 0.00 | 6559.49 | 0.238299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.172638E+10 | 0.00 | 373.47 | 0.855215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11540.51 | 10726.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.714508E+10 | 0.00 | 683.64 | 0.352741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12942.22 | 11833.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.443518E+09 | 0.00 | 199.47 | 0.189984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11583.50 | 20-JAN-19:01 | 10790.72 | 09-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.608640E+09 | 0.00 | 215.57 | 0.258812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11383.41 | 06-FEB-16:11 | 11383.41 | 06-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.858884E+09 | 0.00 | 261.77 | 0.313736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11474.12 | 22-MAR-18:51 | 10189.68 | 03-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.219092E+10 | 0.00 | 428.13 | 0.840442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12242.95 | 26-APR-21:51 | 11202.30 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.240902E+10 | 0.00 | 432.60 | 0.978037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11861.78 | 02-MAY-21:51 | 10850.53 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.312717E+10 | 0.00 | 391.91 | 0.138090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12705.83 | 28-JUN-21:51 | 10397.57 | 04-JUN-19:31 | 0.00 | 0.00 | 0.00 |
July | 0.445531E+10 | 0.00 | 413.79 | 0.222703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12892.73 | 27-JUL-21:51 | 10048.95 | 08-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.424253E+10 | 0.00 | 408.79 | 0.202801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12808.20 | 16-AUG-21:51 | 10063.60 | 06-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.303365E+10 | 0.00 | 389.25 | 0.126471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12441.86 | 30-SEP-21:51 | 10117.96 | 19-SEP-19:01 | 0.00 | 0.00 | 0.00 |
October | 0.237960E+10 | 0.00 | 392.97 | 0.126602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12757.02 | 01-OCT-08:52 | 11725.43 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.810262E+09 | 0.00 | 309.95 | 0.314452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11824.84 | 12-NOV-09:02 | 10954.57 | 30-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.471922E+09 | 0.00 | 207.82 | 0.288520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11219.70 | 07-DEC-19:01 | 11131.08 | 19-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250314E+11 | 0.00 | 4052.03 | 0.113507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.443518E+09 | 0.00 | 199.47 | 0.189984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11219.70 | 10048.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.445531E+10 | 0.00 | 432.60 | 0.222703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12892.73 | 11725.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.315282E+11 | 0.00 | 618.10 | 0.224582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38501.94 | 14-JAN-12:40 | 38501.94 | 14-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.206529E+11 | 0.00 | 482.85 | 0.134387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34350.05 | 02-FEB-12:30 | 32763.12 | 03-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.158034E+11 | 0.00 | 471.78 | 0.697469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28760.10 | 11-MAR-13:15 | 27613.00 | 11-MAR-09:51 | 0.00 | 0.00 | 0.00 |
April | 0.179010E+11 | 0.00 | 564.85 | 0.644664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21784.58 | 08-APR-12:40 | 17400.65 | 02-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.111383E+11 | 0.00 | 504.12 | 0.282208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16982.29 | 03-MAY-06:53 | 6462.78 | 04-MAY-12:30 | 0.00 | 0.00 | 0.00 |
June | 0.143037E+11 | 0.00 | 572.90 | 0.365687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18356.20 | 30-JUN-06:53 | 6837.12 | 24-JUN-08:00 | 0.00 | 0.00 | 0.00 |
July | 0.220001E+11 | 0.00 | 697.07 | 0.646532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21838.85 | 30-JUL-08:00 | 8958.96 | 30-JUL-08:00 | 0.00 | 0.00 | 0.00 |
August | 0.290813E+11 | 0.00 | 728.00 | 0.101736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22845.05 | 19-AUG-08:00 | 10776.18 | 30-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.311716E+11 | 0.00 | 706.72 | 0.135012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34929.06 | 30-SEP-13:05 | 33372.93 | 30-SEP-13:05 | 0.00 | 0.00 | 0.00 |
October | 0.385645E+11 | 0.00 | 713.96 | 0.251683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42188.26 | 16-OCT-12:30 | 42188.26 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.322505E+11 | 0.00 | 638.92 | 0.213572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41651.38 | 19-NOV-09:53 | 35832.21 | 20-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.352366E+11 | 0.00 | 644.08 | 0.282241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39237.94 | 19-DEC-13:00 | 39237.94 | 19-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299632E+12 | 0.00 | 7343.36 | 0.160687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.111383E+11 | 0.00 | 471.78 | 0.282208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16982.29 | 6462.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.385645E+11 | 0.00 | 728.00 | 0.282241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42188.26 | 42188.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.110688E+11 | 0.00 | 330.73 | 0.579614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71788.12 | 20-JAN-19:01 | 68963.11 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.127772E+11 | 0.00 | 391.22 | 0.625290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70167.14 | 13-FEB-19:12 | 68124.94 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.156193E+11 | 0.00 | 398.12 | 0.721763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68996.34 | 22-MAR-18:51 | 63076.40 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.219646E+11 | 0.00 | 397.65 | 0.111743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74836.98 | 26-APR-21:51 | 67627.96 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.253920E+11 | 0.00 | 393.96 | 0.139910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73202.94 | 04-MAY-21:51 | 66180.74 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.280553E+11 | 0.00 | 326.34 | 0.163545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77749.61 | 28-JUN-21:51 | 63713.73 | 22-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.336084E+11 | 0.00 | 349.33 | 0.199875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79271.83 | 19-JUL-21:51 | 63311.06 | 18-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.313799E+11 | 0.00 | 331.30 | 0.178975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78541.55 | 16-AUG-21:51 | 60790.60 | 21-AUG-20:11 | 0.00 | 0.00 | 0.00 |
September | 0.246680E+11 | 0.00 | 309.14 | 0.131961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78002.04 | 22-SEP-21:52 | 62310.98 | 19-SEP-19:01 | 0.00 | 0.00 | 0.00 |
October | 0.223233E+11 | 0.00 | 337.41 | 0.143753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77733.11 | 01-OCT-08:52 | 72508.42 | 15-OCT-07:41 | 0.00 | 0.00 | 0.00 |
November | 0.142046E+11 | 0.00 | 393.42 | 0.738703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71451.39 | 09-NOV-22:53 | 68336.67 | 28-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.103938E+11 | 0.00 | 350.86 | 0.651020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68582.03 | 19-DEC-19:01 | 68582.03 | 19-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251455E+12 | 0.00 | 4309.46 | 0.140140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.103938E+11 | 0.00 | 309.14 | 0.579614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68582.03 | 60790.60 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.336084E+11 | 0.00 | 398.12 | 0.199875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79271.83 | 72508.42 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.202954E+10 | 0.00 | 460.39 | 0.117197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10564.51 | 14-JAN-16:11 | 10564.51 | 14-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.160021E+10 | 0.00 | 363.06 | 0.923536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10565.90 | 01-FEB-09:01 | 10565.90 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.182263E+10 | 0.00 | 380.82 | 0.861737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10380.90 | 17-MAR-08:61 | 9582.96 | 12-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.333820E+10 | 0.00 | 576.25 | 0.161512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10560.94 | 02-APR-08:61 | 10560.94 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.296888E+10 | 0.00 | 565.25 | 0.136851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10811.60 | 06-MAY-08:62 | 10558.21 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.412215E+10 | 0.00 | 613.61 | 0.185518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10971.58 | 28-JUN-08:62 | 9599.11 | 03-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.626875E+10 | 0.00 | 694.78 | 0.299668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10967.18 | 20-JUL-08:62 | 9617.17 | 22-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.678545E+10 | 0.00 | 701.93 | 0.329214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11186.02 | 08-AUG-08:62 | 9603.78 | 23-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.479017E+10 | 0.00 | 639.63 | 0.221314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11287.62 | 22-SEP-08:62 | 9583.89 | 03-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.476427E+10 | 0.00 | 647.83 | 0.286044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11360.16 | 01-OCT-08:62 | 10566.56 | 18-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.238304E+10 | 0.00 | 518.06 | 0.136410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10980.13 | 12-NOV-09:02 | 10563.66 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.215868E+10 | 0.00 | 472.17 | 0.160981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10564.11 | 31-DEC-09:01 | 10564.11 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430320E+11 | 0.00 | 6633.79 | 0.221324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.160021E+10 | 0.00 | 363.06 | 0.861737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10380.90 | 9582.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.678545E+10 | 0.00 | 701.93 | 0.329214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11360.16 | 10566.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.578263E+09 | 0.00 | 190.46 | 0.298223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10413.47 | 20-JAN-19:01 | 9997.05 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.600783E+09 | 0.00 | 173.73 | 0.305841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10169.61 | 06-FEB-09:01 | 10169.61 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.902944E+09 | 0.00 | 258.75 | 0.387900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10069.73 | 18-MAR-08:61 | 9630.32 | 23-MAR-08:51 | 0.00 | 0.00 | 0.00 |
April | 0.205208E+10 | 0.00 | 430.94 | 0.926277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10736.39 | 26-APR-21:51 | 10707.22 | 02-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.211887E+10 | 0.00 | 440.00 | 0.926948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10949.34 | 24-MAY-08:51 | 10949.34 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.274930E+10 | 0.00 | 406.93 | 0.121986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11421.44 | 30-JUN-08:51 | 10090.45 | 23-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.413316E+10 | 0.00 | 428.00 | 0.199989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12127.48 | 23-JUL-08:51 | 10118.02 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.409417E+10 | 0.00 | 428.04 | 0.193855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12464.49 | 19-AUG-08:51 | 9912.50 | 22-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.250686E+10 | 0.00 | 404.29 | 0.108297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11429.86 | 10-SEP-08:51 | 9990.70 | 03-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.219963E+10 | 0.00 | 407.40 | 0.126077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11760.72 | 15-OCT-07:41 | 11760.72 | 15-OCT-07:41 | 0.00 | 0.00 | 0.00 |
November | 0.780002E+09 | 0.00 | 252.53 | 0.372158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10582.72 | 12-NOV-09:02 | 10013.57 | 23-NOV-09:52 | 0.00 | 0.00 | 0.00 |
December | 0.506334E+09 | 0.00 | 187.46 | 0.336017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10535.74 | 05-DEC-09:41 | 10535.74 | 05-DEC-09:41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232224E+11 | 0.00 | 4008.55 | 0.110554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.506334E+09 | 0.00 | 173.73 | 0.298223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10069.73 | 9630.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.413316E+10 | 0.00 | 440.00 | 0.199989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12464.49 | 11760.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.389986E+09 | 0.00 | 349.29 | 0.213186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3274.60 | 21-JAN-09:01 | 3072.22 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.363402E+09 | 0.00 | 265.51 | 0.206297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3132.95 | 13-FEB-16:12 | 3071.74 | 06-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.427441E+09 | 0.00 | 296.26 | 0.214568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.14 | 18-MAR-08:61 | 2752.02 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.903068E+09 | 0.00 | 524.97 | 0.467333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3179.52 | 12-APR-08:62 | 3015.75 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.831450E+09 | 0.00 | 519.98 | 0.407578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3288.90 | 06-MAY-08:62 | 2906.01 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.122325E+10 | 0.00 | 605.78 | 0.597984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3275.61 | 28-JUN-08:62 | 2796.87 | 13-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.177054E+10 | 0.00 | 685.60 | 0.895512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3360.98 | 31-JUL-08:62 | 2797.98 | 16-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.181125E+10 | 0.00 | 685.52 | 0.913643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3490.40 | 06-AUG-08:61 | 2787.79 | 01-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.133642E+10 | 0.00 | 639.82 | 0.649643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3441.15 | 22-SEP-08:62 | 2780.21 | 16-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.115747E+10 | 0.00 | 596.35 | 0.689140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3431.41 | 01-OCT-08:62 | 3072.44 | 13-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.527948E+09 | 0.00 | 410.16 | 0.285892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3328.07 | 12-NOV-09:02 | 3072.13 | 22-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.433192E+09 | 0.00 | 366.41 | 0.311793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3072.75 | 05-DEC-19:01 | 3072.75 | 05-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111754E+11 | 0.00 | 5945.65 | 0.585257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.363402E+09 | 0.00 | 265.51 | 0.206297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3072.75 | 2752.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.181125E+10 | 0.00 | 685.60 | 0.913643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3490.40 | 3072.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 61842985.62 | 0.00 | 92.35 | 29594284.84 | 0.00 | 0.00 | 0.00 | 0.00 | 3063.67 | 21-JAN-09:01 | 2758.38 | 09-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.104373E+09 | 0.00 | 127.77 | 46405520.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.58 | 06-FEB-16:11 | 2948.58 | 06-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.178833E+09 | 0.00 | 172.37 | 71722253.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.47 | 22-MAR-18:51 | 2685.13 | 19-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.522743E+09 | 0.00 | 381.71 | 0.214440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.74 | 26-APR-21:51 | 2952.78 | 23-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.580186E+09 | 0.00 | 414.86 | 0.248421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.83 | 02-MAY-21:51 | 2853.76 | 18-MAY-19:11 | 0.00 | 0.00 | 0.00 |
June | 0.834329E+09 | 0.00 | 402.56 | 0.381615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3384.91 | 28-JUN-21:51 | 2775.48 | 04-JUN-19:31 | 0.00 | 0.00 | 0.00 |
July | 0.123647E+10 | 0.00 | 424.20 | 0.631996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3423.40 | 27-JUL-21:51 | 2672.93 | 08-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.114736E+10 | 0.00 | 420.11 | 0.555535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3397.96 | 16-AUG-21:51 | 2596.83 | 21-AUG-20:11 | 0.00 | 0.00 | 0.00 |
September | 0.735986E+09 | 0.00 | 406.00 | 0.304835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3277.72 | 30-SEP-21:51 | 2660.86 | 19-SEP-19:01 | 0.00 | 0.00 | 0.00 |
October | 0.520124E+09 | 0.00 | 350.25 | 0.281390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3380.21 | 01-OCT-08:52 | 2983.68 | 14-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.114517E+09 | 0.00 | 177.90 | 44373961.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.10 | 12-NOV-09:02 | 2774.67 | 30-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 57326293.62 | 0.00 | 98.98 | 39524040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2899.53 | 07-DEC-19:01 | 2831.40 | 19-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609409E+10 | 0.00 | 3469.05 | 0.284985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 57326293.62 | 0.00 | 92.35 | 29594284.84 | 0.00 | 0.00 | 0.00 | 0.00 | 2899.53 | 2596.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.123647E+10 | 0.00 | 424.20 | 0.631996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3423.40 | 2983.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.684835E+10 | 0.00 | 592.15 | 0.488980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14738.49 | 14-JAN-16:11 | 14738.49 | 14-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.466019E+10 | 0.00 | 484.89 | 0.308167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14878.20 | 13-FEB-16:12 | 14738.95 | 06-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.409256E+10 | 0.00 | 469.36 | 0.217927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14799.60 | 18-MAR-08:61 | 13422.75 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.499748E+10 | 0.00 | 577.33 | 0.236701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14557.74 | 01-APR-18:02 | 14557.74 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.330440E+10 | 0.00 | 515.94 | 0.132134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14990.66 | 06-MAY-08:62 | 13767.42 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.436384E+10 | 0.00 | 568.33 | 0.166838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15386.10 | 27-JUN-18:01 | 13074.03 | 04-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.680447E+10 | 0.00 | 645.69 | 0.280574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16239.93 | 29-JUL-18:01 | 13353.98 | 31-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.843985E+10 | 0.00 | 672.44 | 0.374087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16427.84 | 18-AUG-08:62 | 13450.70 | 10-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.803136E+10 | 0.00 | 634.04 | 0.401191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16142.21 | 22-SEP-08:62 | 13450.35 | 24-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.909167E+10 | 0.00 | 658.31 | 0.613605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16299.84 | 05-OCT-18:01 | 14737.85 | 26-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.704917E+10 | 0.00 | 625.39 | 0.483359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15052.87 | 12-NOV-09:02 | 14737.37 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.732737E+10 | 0.00 | 617.93 | 0.589429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14738.67 | 29-DEC-19:01 | 14738.67 | 29-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.750107E+11 | 0.00 | 7061.78 | 0.429299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.330440E+10 | 0.00 | 469.36 | 0.132134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14557.74 | 13074.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.909167E+10 | 0.00 | 672.44 | 0.613605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16427.84 | 14738.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 490.43 | 361.99 | 128.44 | 866.25 | 224.55 | 0.00 | 0.00 | 0.00 |
February | 379.17 | 233.68 | 145.49 | 661.49 | 197.71 | 0.00 | 0.00 | 0.00 |
March | 294.11 | 138.00 | 156.10 | 525.23 | 201.89 | 0.00 | 0.00 | 0.00 |
April | 237.78 | 81.64 | 156.14 | 462.78 | 166.31 | 0.00 | 0.00 | 0.00 |
May | 172.45 | 14.83 | 157.61 | 291.82 | 145.79 | 0.00 | 0.00 | 0.00 |
June | 153.27 | 5.17 | 148.09 | 257.21 | 111.15 | 0.00 | 0.00 | 0.00 |
July | 159.19 | 11.01 | 148.17 | 296.88 | 99.72 | 0.00 | 0.00 | 0.00 |
August | 198.28 | 51.40 | 146.88 | 414.94 | 107.31 | 0.00 | 0.00 | 0.00 |
September | 276.63 | 129.39 | 147.25 | 562.31 | 127.02 | 0.00 | 0.00 | 0.00 |
October | 376.24 | 250.40 | 125.84 | 732.84 | 140.26 | 0.00 | 0.00 | 0.00 |
November | 469.20 | 333.54 | 135.66 | 835.42 | 202.43 | 0.00 | 0.00 | 0.00 |
December | 527.32 | 404.29 | 123.03 | 931.54 | 225.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 310.91 | 167.74 | 143.17 | 569.58 | 162.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.27 | 5.17 | 123.03 | 257.21 | 99.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 527.32 | 404.29 | 157.61 | 931.54 | 225.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1381.01 | 1019.33 | 361.68 | 2455.55 | 601.67 | 0.00 | 0.00 | 0.00 |
February | 1067.71 | 658.03 | 409.69 | 1879.13 | 530.95 | 0.00 | 0.00 | 0.00 |
March | 828.19 | 388.61 | 439.58 | 1494.76 | 547.12 | 0.00 | 0.00 | 0.00 |
April | 669.59 | 229.89 | 439.69 | 1335.76 | 430.66 | 0.00 | 0.00 | 0.00 |
May | 485.60 | 41.77 | 443.82 | 848.03 | 380.10 | 0.00 | 0.00 | 0.00 |
June | 431.59 | 14.57 | 417.03 | 761.27 | 274.70 | 0.00 | 0.00 | 0.00 |
July | 448.26 | 31.02 | 417.24 | 889.64 | 230.33 | 0.00 | 0.00 | 0.00 |
August | 558.35 | 144.75 | 413.59 | 1225.86 | 245.75 | 0.00 | 0.00 | 0.00 |
September | 778.98 | 364.34 | 414.64 | 1626.98 | 304.46 | 0.00 | 0.00 | 0.00 |
October | 1059.47 | 705.11 | 354.36 | 2095.95 | 346.93 | 0.00 | 0.00 | 0.00 |
November | 1321.24 | 939.23 | 382.01 | 2373.80 | 531.92 | 0.00 | 0.00 | 0.00 |
December | 1484.90 | 1138.44 | 346.45 | 2638.44 | 601.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 875.50 | 472.35 | 403.15 | 1634.64 | 418.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 431.59 | 14.57 | 346.45 | 761.27 | 230.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.90 | 1138.44 | 443.82 | 2638.44 | 601.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1794.01 | 1324.17 | 469.84 | 3214.54 | 837.47 | 0.00 | 0.00 | 0.00 |
February | 1387.02 | 854.81 | 532.21 | 2453.20 | 750.66 | 0.00 | 0.00 | 0.00 |
March | 1075.86 | 504.83 | 571.04 | 1946.53 | 776.29 | 0.00 | 0.00 | 0.00 |
April | 869.83 | 298.64 | 571.19 | 1733.21 | 622.44 | 0.00 | 0.00 | 0.00 |
May | 630.82 | 54.27 | 576.55 | 1084.87 | 560.65 | 0.00 | 0.00 | 0.00 |
June | 560.66 | 18.93 | 541.74 | 966.52 | 418.69 | 0.00 | 0.00 | 0.00 |
July | 582.31 | 40.29 | 542.02 | 1133.77 | 357.68 | 0.00 | 0.00 | 0.00 |
August | 725.32 | 188.04 | 537.28 | 1581.42 | 374.26 | 0.00 | 0.00 | 0.00 |
September | 1011.94 | 473.30 | 538.64 | 2115.31 | 451.03 | 0.00 | 0.00 | 0.00 |
October | 1376.31 | 915.98 | 460.33 | 2735.46 | 501.85 | 0.00 | 0.00 | 0.00 |
November | 1716.37 | 1220.11 | 496.26 | 3104.59 | 747.55 | 0.00 | 0.00 | 0.00 |
December | 1928.96 | 1478.90 | 450.06 | 3455.95 | 835.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1137.32 | 613.60 | 523.72 | 2126.05 | 602.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 560.66 | 18.93 | 450.06 | 966.52 | 357.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1928.96 | 1478.90 | 576.55 | 3455.95 | 837.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.97 | 71.57 | 25.39 | 173.41 | 41.84 | 0.00 | 0.00 | 0.00 |
February | 74.97 | 46.20 | 28.77 | 131.70 | 37.39 | 0.00 | 0.00 | 0.00 |
March | 58.15 | 27.29 | 30.86 | 104.18 | 39.29 | 0.00 | 0.00 | 0.00 |
April | 47.01 | 16.14 | 30.87 | 92.11 | 31.33 | 0.00 | 0.00 | 0.00 |
May | 34.10 | 2.93 | 31.16 | 57.29 | 28.14 | 0.00 | 0.00 | 0.00 |
June | 30.30 | 1.02 | 29.28 | 51.13 | 20.39 | 0.00 | 0.00 | 0.00 |
July | 31.47 | 2.18 | 29.30 | 60.22 | 17.00 | 0.00 | 0.00 | 0.00 |
August | 39.20 | 10.16 | 29.04 | 84.36 | 17.57 | 0.00 | 0.00 | 0.00 |
September | 54.70 | 25.58 | 29.11 | 113.29 | 21.47 | 0.00 | 0.00 | 0.00 |
October | 74.39 | 49.51 | 24.88 | 147.39 | 23.44 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 65.95 | 26.82 | 167.21 | 36.93 | 0.00 | 0.00 | 0.00 |
December | 104.26 | 79.93 | 24.33 | 186.46 | 41.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.47 | 33.17 | 28.31 | 114.01 | 29.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.30 | 1.02 | 24.33 | 51.13 | 17.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.26 | 79.93 | 31.16 | 186.46 | 41.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.49 | 34.17 | 34.31 | 111.58 | 83.49 | 0.00 | 0.00 | 0.00 |
February | 82.88 | 38.42 | 44.46 | 130.29 | 72.64 | 0.00 | 0.00 | 0.00 |
March | 95.08 | 42.31 | 52.77 | 151.72 | 74.06 | 0.00 | 0.00 | 0.00 |
April | 131.10 | 68.54 | 62.57 | 229.45 | 57.16 | 0.00 | 0.00 | 0.00 |
May | 128.76 | 59.78 | 68.97 | 222.55 | 50.61 | 0.00 | 0.00 | 0.00 |
June | 136.49 | 68.61 | 67.88 | 246.30 | 36.40 | 0.00 | 0.00 | 0.00 |
July | 144.49 | 77.67 | 66.82 | 271.43 | 30.43 | 0.00 | 0.00 | 0.00 |
August | 135.63 | 73.87 | 61.77 | 256.00 | 31.91 | 0.00 | 0.00 | 0.00 |
September | 116.18 | 62.49 | 53.69 | 213.37 | 39.19 | 0.00 | 0.00 | 0.00 |
October | 88.83 | 48.74 | 40.09 | 166.86 | 45.34 | 0.00 | 0.00 | 0.00 |
November | 79.44 | 41.41 | 38.03 | 132.25 | 72.71 | 0.00 | 0.00 | 0.00 |
December | 69.44 | 36.78 | 32.66 | 114.54 | 83.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 106.49 | 54.46 | 52.03 | 187.46 | 56.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.49 | 34.17 | 32.66 | 111.58 | 30.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.49 | 77.67 | 68.97 | 271.43 | 83.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.44 | 0.00 | 14.44 | 15.73 | 44.54 | 0.00 | 0.00 | 0.00 |
February | 18.12 | 0.00 | 18.12 | 18.95 | 39.14 | 0.00 | 0.00 | 0.00 |
March | 22.21 | 0.00 | 22.21 | 25.67 | 40.38 | 0.00 | 0.00 | 0.00 |
April | 25.64 | 0.13 | 25.52 | 33.44 | 30.89 | 0.00 | 0.00 | 0.00 |
May | 30.51 | 1.18 | 29.33 | 42.47 | 26.91 | 0.00 | 0.00 | 0.00 |
June | 32.06 | 2.50 | 29.56 | 50.48 | 20.51 | 0.00 | 0.00 | 0.00 |
July | 30.40 | 1.96 | 28.44 | 51.19 | 18.23 | 0.00 | 0.00 | 0.00 |
August | 25.64 | 0.37 | 25.26 | 41.60 | 19.03 | 0.00 | 0.00 | 0.00 |
September | 21.81 | 0.00 | 21.80 | 33.22 | 22.88 | 0.00 | 0.00 | 0.00 |
October | 17.30 | 0.00 | 17.30 | 28.57 | 25.63 | 0.00 | 0.00 | 0.00 |
November | 15.66 | 0.00 | 15.66 | 17.87 | 39.37 | 0.00 | 0.00 | 0.00 |
December | 13.44 | 0.00 | 13.44 | 14.40 | 44.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.29 | 0.51 | 21.77 | 31.20 | 30.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.44 | 0.00 | 13.44 | 14.40 | 18.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.06 | 2.50 | 29.56 | 51.19 | 44.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.49 | 34.17 | 34.31 | 114.79 | 81.65 | 0.00 | 0.00 | 0.00 |
February | 82.88 | 38.42 | 44.46 | 132.52 | 71.44 | 0.00 | 0.00 | 0.00 |
March | 95.08 | 42.31 | 52.77 | 153.18 | 73.37 | 0.00 | 0.00 | 0.00 |
April | 131.10 | 68.54 | 62.57 | 228.96 | 57.75 | 0.00 | 0.00 | 0.00 |
May | 128.76 | 59.78 | 68.97 | 220.59 | 51.87 | 0.00 | 0.00 | 0.00 |
June | 136.49 | 68.61 | 67.88 | 242.23 | 39.37 | 0.00 | 0.00 | 0.00 |
July | 144.49 | 77.67 | 66.82 | 266.75 | 34.43 | 0.00 | 0.00 | 0.00 |
August | 135.63 | 73.87 | 61.77 | 252.70 | 35.72 | 0.00 | 0.00 | 0.00 |
September | 116.18 | 62.49 | 53.69 | 212.36 | 41.29 | 0.00 | 0.00 | 0.00 |
October | 88.83 | 48.74 | 40.09 | 167.28 | 46.80 | 0.00 | 0.00 | 0.00 |
November | 79.44 | 41.41 | 38.03 | 134.82 | 71.56 | 0.00 | 0.00 | 0.00 |
December | 69.44 | 36.78 | 32.66 | 117.76 | 81.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 106.49 | 54.46 | 52.03 | 187.25 | 57.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.49 | 34.17 | 32.66 | 114.79 | 34.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.49 | 77.67 | 68.97 | 266.75 | 81.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.56 | 57.25 | 20.31 | 130.46 | 48.72 | 0.00 | 0.00 | 0.00 |
February | 59.96 | 36.95 | 23.01 | 96.93 | 45.04 | 0.00 | 0.00 | 0.00 |
March | 46.51 | 21.82 | 24.69 | 75.04 | 46.05 | 0.00 | 0.00 | 0.00 |
April | 37.60 | 12.91 | 24.69 | 65.71 | 38.36 | 0.00 | 0.00 | 0.00 |
May | 27.27 | 2.35 | 24.93 | 37.34 | 34.83 | 0.00 | 0.00 | 0.00 |
June | 24.24 | 0.82 | 23.42 | 32.27 | 27.73 | 0.00 | 0.00 | 0.00 |
July | 25.17 | 1.74 | 23.43 | 39.71 | 24.49 | 0.00 | 0.00 | 0.00 |
August | 31.36 | 8.13 | 23.23 | 59.23 | 25.63 | 0.00 | 0.00 | 0.00 |
September | 43.75 | 20.46 | 23.29 | 82.78 | 30.00 | 0.00 | 0.00 | 0.00 |
October | 59.50 | 39.60 | 19.90 | 109.70 | 32.04 | 0.00 | 0.00 | 0.00 |
November | 74.20 | 52.75 | 21.45 | 125.47 | 44.23 | 0.00 | 0.00 | 0.00 |
December | 83.39 | 63.93 | 19.46 | 140.77 | 48.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.17 | 26.53 | 22.64 | 82.91 | 37.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.24 | 0.82 | 19.46 | 32.27 | 24.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.39 | 63.93 | 24.93 | 140.77 | 48.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.55 | 0.00 | 11.55 | 12.75 | 35.69 | 0.00 | 0.00 | 0.00 |
February | 14.50 | 0.00 | 14.50 | 15.50 | 31.17 | 0.00 | 0.00 | 0.00 |
March | 17.77 | 0.00 | 17.77 | 21.04 | 32.13 | 0.00 | 0.00 | 0.00 |
April | 20.52 | 0.10 | 20.42 | 28.57 | 23.67 | 0.00 | 0.00 | 0.00 |
May | 24.41 | 0.94 | 23.47 | 35.91 | 20.73 | 0.00 | 0.00 | 0.00 |
June | 25.65 | 2.00 | 23.65 | 42.79 | 15.36 | 0.00 | 0.00 | 0.00 |
July | 24.32 | 1.57 | 22.75 | 43.63 | 13.19 | 0.00 | 0.00 | 0.00 |
August | 20.51 | 0.30 | 20.21 | 35.72 | 13.62 | 0.00 | 0.00 | 0.00 |
September | 17.45 | 0.00 | 17.45 | 28.33 | 16.75 | 0.00 | 0.00 | 0.00 |
October | 13.84 | 0.00 | 13.84 | 23.98 | 19.35 | 0.00 | 0.00 | 0.00 |
November | 12.53 | 0.00 | 12.53 | 14.84 | 30.87 | 0.00 | 0.00 | 0.00 |
December | 10.75 | 0.00 | 10.75 | 11.77 | 35.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.83 | 0.41 | 17.42 | 26.30 | 23.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.75 | 0.00 | 10.75 | 11.77 | 13.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.65 | 2.00 | 23.65 | 43.63 | 35.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.04 | 38.21 | 33.83 | 115.28 | 79.69 | 0.00 | 0.00 | 0.00 |
February | 76.57 | 34.99 | 41.58 | 116.37 | 69.85 | 0.00 | 0.00 | 0.00 |
March | 94.20 | 42.43 | 51.77 | 147.60 | 71.23 | 0.00 | 0.00 | 0.00 |
April | 119.76 | 60.34 | 59.42 | 206.88 | 54.90 | 0.00 | 0.00 | 0.00 |
May | 112.75 | 47.24 | 65.51 | 191.84 | 49.08 | 0.00 | 0.00 | 0.00 |
June | 111.74 | 48.51 | 63.24 | 200.97 | 35.87 | 0.00 | 0.00 | 0.00 |
July | 126.72 | 63.04 | 63.68 | 239.28 | 30.18 | 0.00 | 0.00 | 0.00 |
August | 125.57 | 66.97 | 58.60 | 237.97 | 31.04 | 0.00 | 0.00 | 0.00 |
September | 91.29 | 41.97 | 49.32 | 166.85 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 80.55 | 41.38 | 39.17 | 149.56 | 43.50 | 0.00 | 0.00 | 0.00 |
November | 72.80 | 36.66 | 36.14 | 117.25 | 70.23 | 0.00 | 0.00 | 0.00 |
December | 69.54 | 38.39 | 31.15 | 111.66 | 79.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.26 | 46.77 | 49.49 | 167.14 | 54.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.54 | 34.99 | 31.15 | 111.66 | 30.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 126.72 | 66.97 | 65.51 | 239.28 | 79.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.97 | 71.57 | 25.39 | 172.95 | 41.74 | 0.00 | 0.00 | 0.00 |
February | 74.97 | 46.20 | 28.77 | 131.45 | 37.07 | 0.00 | 0.00 | 0.00 |
March | 58.15 | 27.29 | 30.86 | 103.71 | 39.00 | 0.00 | 0.00 | 0.00 |
April | 47.01 | 16.14 | 30.87 | 91.65 | 30.85 | 0.00 | 0.00 | 0.00 |
May | 34.10 | 2.93 | 31.16 | 56.98 | 27.63 | 0.00 | 0.00 | 0.00 |
June | 30.30 | 1.02 | 29.28 | 50.98 | 19.84 | 0.00 | 0.00 | 0.00 |
July | 31.47 | 2.18 | 29.30 | 59.90 | 16.49 | 0.00 | 0.00 | 0.00 |
August | 39.20 | 10.16 | 29.04 | 83.98 | 17.11 | 0.00 | 0.00 | 0.00 |
September | 54.70 | 25.58 | 29.11 | 113.26 | 20.84 | 0.00 | 0.00 | 0.00 |
October | 74.39 | 49.51 | 24.88 | 147.18 | 23.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 65.95 | 26.82 | 166.98 | 36.61 | 0.00 | 0.00 | 0.00 |
December | 104.26 | 79.93 | 24.33 | 186.11 | 41.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.47 | 33.17 | 28.31 | 113.70 | 29.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.30 | 1.02 | 24.33 | 50.98 | 16.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.26 | 79.93 | 31.16 | 186.11 | 41.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.44 | 0.00 | 14.44 | 15.21 | 44.24 | 0.00 | 0.00 | 0.00 |
February | 18.12 | 0.00 | 18.12 | 18.63 | 38.58 | 0.00 | 0.00 | 0.00 |
March | 22.21 | 0.00 | 22.21 | 25.21 | 39.98 | 0.00 | 0.00 | 0.00 |
April | 25.64 | 0.13 | 25.52 | 33.17 | 30.17 | 0.00 | 0.00 | 0.00 |
May | 30.51 | 1.18 | 29.33 | 42.49 | 26.25 | 0.00 | 0.00 | 0.00 |
June | 32.06 | 2.50 | 29.56 | 50.96 | 19.55 | 0.00 | 0.00 | 0.00 |
July | 30.40 | 1.96 | 28.44 | 51.31 | 17.21 | 0.00 | 0.00 | 0.00 |
August | 25.64 | 0.37 | 25.26 | 41.32 | 18.05 | 0.00 | 0.00 | 0.00 |
September | 21.81 | 0.00 | 21.80 | 33.27 | 21.70 | 0.00 | 0.00 | 0.00 |
October | 17.30 | 0.00 | 17.30 | 28.16 | 24.96 | 0.00 | 0.00 | 0.00 |
November | 15.66 | 0.00 | 15.66 | 17.53 | 38.63 | 0.00 | 0.00 | 0.00 |
December | 13.44 | 0.00 | 13.44 | 13.87 | 44.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.29 | 0.51 | 21.77 | 31.00 | 30.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.44 | 0.00 | 13.44 | 13.87 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.06 | 2.50 | 29.56 | 51.31 | 44.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.04 | 38.21 | 33.83 | 118.32 | 77.45 | 0.00 | 0.00 | 0.00 |
February | 76.57 | 34.99 | 41.58 | 118.73 | 68.34 | 0.00 | 0.00 | 0.00 |
March | 94.20 | 42.43 | 51.77 | 149.21 | 70.37 | 0.00 | 0.00 | 0.00 |
April | 119.76 | 60.34 | 59.42 | 207.05 | 55.12 | 0.00 | 0.00 | 0.00 |
May | 112.75 | 47.24 | 65.51 | 190.62 | 50.04 | 0.00 | 0.00 | 0.00 |
June | 111.74 | 48.51 | 63.24 | 198.26 | 38.18 | 0.00 | 0.00 | 0.00 |
July | 126.72 | 63.04 | 63.68 | 235.67 | 33.45 | 0.00 | 0.00 | 0.00 |
August | 125.57 | 66.97 | 58.60 | 235.05 | 34.02 | 0.00 | 0.00 | 0.00 |
September | 91.29 | 41.97 | 49.32 | 166.34 | 39.63 | 0.00 | 0.00 | 0.00 |
October | 80.55 | 41.38 | 39.17 | 149.97 | 44.58 | 0.00 | 0.00 | 0.00 |
November | 72.80 | 36.66 | 36.14 | 119.81 | 68.38 | 0.00 | 0.00 | 0.00 |
December | 69.54 | 38.39 | 31.15 | 114.59 | 77.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.26 | 46.77 | 49.49 | 167.30 | 54.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.54 | 34.99 | 31.15 | 114.59 | 33.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 126.72 | 66.97 | 65.51 | 235.67 | 77.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.29 | 0.00 | 18.29 | 19.30 | 59.72 | 0.00 | 0.00 | 0.00 |
February | 22.95 | 0.00 | 22.95 | 23.84 | 52.37 | 0.00 | 0.00 | 0.00 |
March | 28.13 | 0.00 | 28.13 | 33.18 | 52.92 | 0.00 | 0.00 | 0.00 |
April | 32.48 | 0.16 | 32.32 | 44.99 | 39.86 | 0.00 | 0.00 | 0.00 |
May | 38.64 | 1.49 | 37.15 | 56.97 | 34.77 | 0.00 | 0.00 | 0.00 |
June | 40.61 | 3.16 | 37.44 | 68.44 | 25.74 | 0.00 | 0.00 | 0.00 |
July | 38.50 | 2.49 | 36.01 | 69.36 | 22.57 | 0.00 | 0.00 | 0.00 |
August | 32.47 | 0.47 | 31.99 | 56.05 | 23.94 | 0.00 | 0.00 | 0.00 |
September | 27.62 | 0.00 | 27.61 | 44.05 | 29.58 | 0.00 | 0.00 | 0.00 |
October | 21.91 | 0.00 | 21.91 | 36.64 | 34.55 | 0.00 | 0.00 | 0.00 |
November | 19.83 | 0.00 | 19.83 | 22.16 | 53.13 | 0.00 | 0.00 | 0.00 |
December | 17.02 | 0.00 | 17.02 | 17.33 | 60.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.23 | 0.65 | 27.57 | 41.13 | 40.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.02 | 0.00 | 17.02 | 17.33 | 22.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.61 | 3.16 | 37.44 | 69.36 | 60.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6.74 | 0.00 | 6.74 | 7.11 | 22.02 | 0.00 | 0.00 | 0.00 |
February | 8.46 | 0.00 | 8.46 | 8.79 | 19.30 | 0.00 | 0.00 | 0.00 |
March | 10.37 | 0.00 | 10.37 | 12.23 | 19.51 | 0.00 | 0.00 | 0.00 |
April | 11.97 | 0.06 | 11.91 | 16.58 | 14.70 | 0.00 | 0.00 | 0.00 |
May | 14.24 | 0.55 | 13.69 | 21.00 | 12.82 | 0.00 | 0.00 | 0.00 |
June | 14.97 | 1.17 | 13.80 | 25.23 | 9.49 | 0.00 | 0.00 | 0.00 |
July | 14.19 | 0.92 | 13.28 | 25.57 | 8.32 | 0.00 | 0.00 | 0.00 |
August | 11.97 | 0.17 | 11.79 | 20.66 | 8.83 | 0.00 | 0.00 | 0.00 |
September | 10.18 | 0.00 | 10.18 | 16.24 | 10.90 | 0.00 | 0.00 | 0.00 |
October | 8.08 | 0.00 | 8.08 | 13.51 | 12.74 | 0.00 | 0.00 | 0.00 |
November | 7.31 | 0.00 | 7.31 | 8.17 | 19.59 | 0.00 | 0.00 | 0.00 |
December | 6.28 | 0.00 | 6.28 | 6.39 | 22.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.40 | 0.24 | 10.16 | 15.16 | 15.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.28 | 0.00 | 6.28 | 6.39 | 8.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.97 | 1.17 | 13.80 | 25.57 | 22.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.24 | 33.39 | 11.85 | 81.53 | 20.20 | 0.00 | 0.00 | 0.00 |
February | 34.98 | 21.56 | 13.42 | 61.98 | 18.15 | 0.00 | 0.00 | 0.00 |
March | 27.13 | 12.73 | 14.40 | 49.23 | 18.84 | 0.00 | 0.00 | 0.00 |
April | 21.94 | 7.53 | 14.41 | 43.85 | 15.06 | 0.00 | 0.00 | 0.00 |
May | 15.91 | 1.37 | 14.54 | 27.43 | 13.70 | 0.00 | 0.00 | 0.00 |
June | 14.14 | 0.48 | 13.66 | 24.50 | 10.16 | 0.00 | 0.00 | 0.00 |
July | 14.69 | 1.02 | 13.67 | 28.63 | 8.75 | 0.00 | 0.00 | 0.00 |
August | 18.29 | 4.74 | 13.55 | 39.82 | 9.13 | 0.00 | 0.00 | 0.00 |
September | 25.52 | 11.94 | 13.58 | 53.38 | 10.86 | 0.00 | 0.00 | 0.00 |
October | 34.71 | 23.10 | 11.61 | 69.05 | 12.09 | 0.00 | 0.00 | 0.00 |
November | 43.29 | 30.77 | 12.52 | 78.55 | 18.08 | 0.00 | 0.00 | 0.00 |
December | 48.65 | 37.30 | 11.35 | 87.52 | 20.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.68 | 15.47 | 13.21 | 53.76 | 14.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.14 | 0.48 | 11.35 | 24.50 | 8.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.65 | 37.30 | 14.54 | 87.52 | 20.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.80 | 90.64 | 32.16 | 221.29 | 54.82 | 0.00 | 0.00 | 0.00 |
February | 94.94 | 58.51 | 36.43 | 168.22 | 49.27 | 0.00 | 0.00 | 0.00 |
March | 73.64 | 34.56 | 39.09 | 133.62 | 51.15 | 0.00 | 0.00 | 0.00 |
April | 59.54 | 20.44 | 39.10 | 119.01 | 40.87 | 0.00 | 0.00 | 0.00 |
May | 43.18 | 3.71 | 39.47 | 74.46 | 37.17 | 0.00 | 0.00 | 0.00 |
June | 38.38 | 1.30 | 37.08 | 66.50 | 27.57 | 0.00 | 0.00 | 0.00 |
July | 39.86 | 2.76 | 37.10 | 77.69 | 23.75 | 0.00 | 0.00 | 0.00 |
August | 49.65 | 12.87 | 36.78 | 108.08 | 24.78 | 0.00 | 0.00 | 0.00 |
September | 69.27 | 32.40 | 36.87 | 144.89 | 29.48 | 0.00 | 0.00 | 0.00 |
October | 94.21 | 62.70 | 31.51 | 187.42 | 32.82 | 0.00 | 0.00 | 0.00 |
November | 117.49 | 83.52 | 33.97 | 213.19 | 49.09 | 0.00 | 0.00 | 0.00 |
December | 132.04 | 101.23 | 30.81 | 237.56 | 54.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.85 | 42.00 | 35.85 | 145.92 | 39.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.38 | 1.30 | 30.81 | 66.50 | 23.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.04 | 101.23 | 39.47 | 237.56 | 54.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.97 | 71.57 | 25.39 | 172.99 | 41.08 | 0.00 | 0.00 | 0.00 |
February | 74.97 | 46.20 | 28.77 | 131.17 | 36.69 | 0.00 | 0.00 | 0.00 |
March | 58.15 | 27.29 | 30.86 | 103.62 | 38.76 | 0.00 | 0.00 | 0.00 |
April | 47.01 | 16.14 | 30.87 | 91.32 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 34.10 | 2.93 | 31.16 | 56.63 | 27.83 | 0.00 | 0.00 | 0.00 |
June | 30.30 | 1.02 | 29.28 | 50.49 | 20.20 | 0.00 | 0.00 | 0.00 |
July | 31.47 | 2.18 | 29.30 | 59.56 | 16.81 | 0.00 | 0.00 | 0.00 |
August | 39.20 | 10.16 | 29.04 | 83.64 | 17.31 | 0.00 | 0.00 | 0.00 |
September | 54.70 | 25.58 | 29.11 | 112.54 | 21.12 | 0.00 | 0.00 | 0.00 |
October | 74.39 | 49.51 | 24.88 | 146.76 | 22.90 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 65.95 | 26.82 | 166.64 | 36.20 | 0.00 | 0.00 | 0.00 |
December | 104.26 | 79.93 | 24.33 | 186.00 | 40.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.47 | 33.17 | 28.31 | 113.39 | 29.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.30 | 1.02 | 24.33 | 50.49 | 16.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.26 | 79.93 | 31.16 | 186.00 | 41.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.49 | 34.17 | 34.31 | 111.11 | 81.77 | 0.00 | 0.00 | 0.00 |
February | 82.88 | 38.42 | 44.46 | 129.69 | 71.15 | 0.00 | 0.00 | 0.00 |
March | 95.08 | 42.31 | 52.77 | 150.63 | 72.93 | 0.00 | 0.00 | 0.00 |
April | 131.10 | 68.54 | 62.57 | 227.48 | 56.48 | 0.00 | 0.00 | 0.00 |
May | 128.76 | 59.78 | 68.97 | 220.50 | 49.97 | 0.00 | 0.00 | 0.00 |
June | 136.49 | 68.61 | 67.88 | 244.03 | 35.98 | 0.00 | 0.00 | 0.00 |
July | 144.49 | 77.67 | 66.82 | 269.25 | 29.99 | 0.00 | 0.00 | 0.00 |
August | 135.63 | 73.87 | 61.77 | 254.00 | 31.35 | 0.00 | 0.00 | 0.00 |
September | 116.18 | 62.49 | 53.69 | 211.76 | 38.50 | 0.00 | 0.00 | 0.00 |
October | 88.83 | 48.74 | 40.09 | 165.97 | 44.23 | 0.00 | 0.00 | 0.00 |
November | 79.44 | 41.41 | 38.03 | 131.66 | 71.16 | 0.00 | 0.00 | 0.00 |
December | 69.44 | 36.78 | 32.66 | 114.24 | 81.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 106.49 | 54.46 | 52.03 | 186.12 | 55.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.49 | 34.17 | 32.66 | 111.11 | 29.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.49 | 77.67 | 68.97 | 269.25 | 81.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.44 | 0.00 | 14.44 | 16.04 | 43.42 | 0.00 | 0.00 | 0.00 |
February | 18.12 | 0.00 | 18.12 | 19.18 | 38.25 | 0.00 | 0.00 | 0.00 |
March | 22.21 | 0.00 | 22.21 | 25.56 | 39.81 | 0.00 | 0.00 | 0.00 |
April | 25.64 | 0.13 | 25.52 | 32.84 | 30.81 | 0.00 | 0.00 | 0.00 |
May | 30.51 | 1.18 | 29.33 | 41.73 | 26.87 | 0.00 | 0.00 | 0.00 |
June | 32.06 | 2.50 | 29.56 | 49.41 | 20.82 | 0.00 | 0.00 | 0.00 |
July | 30.40 | 1.96 | 28.44 | 50.14 | 18.68 | 0.00 | 0.00 | 0.00 |
August | 25.64 | 0.37 | 25.26 | 40.87 | 19.40 | 0.00 | 0.00 | 0.00 |
September | 21.81 | 0.00 | 21.80 | 32.84 | 22.84 | 0.00 | 0.00 | 0.00 |
October | 17.30 | 0.00 | 17.30 | 28.59 | 25.11 | 0.00 | 0.00 | 0.00 |
November | 15.66 | 0.00 | 15.66 | 18.15 | 38.39 | 0.00 | 0.00 | 0.00 |
December | 13.44 | 0.00 | 13.44 | 14.85 | 43.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.29 | 0.51 | 21.77 | 30.92 | 30.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.44 | 0.00 | 13.44 | 14.85 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.06 | 2.50 | 29.56 | 50.14 | 43.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.49 | 34.17 | 34.31 | 114.79 | 79.58 | 0.00 | 0.00 | 0.00 |
February | 82.88 | 38.42 | 44.46 | 132.25 | 69.77 | 0.00 | 0.00 | 0.00 |
March | 95.08 | 42.31 | 52.77 | 152.14 | 72.26 | 0.00 | 0.00 | 0.00 |
April | 131.10 | 68.54 | 62.57 | 226.62 | 57.49 | 0.00 | 0.00 | 0.00 |
May | 128.76 | 59.78 | 68.97 | 218.09 | 51.67 | 0.00 | 0.00 | 0.00 |
June | 136.49 | 68.61 | 67.88 | 239.19 | 39.90 | 0.00 | 0.00 | 0.00 |
July | 144.49 | 77.67 | 66.82 | 263.72 | 35.22 | 0.00 | 0.00 | 0.00 |
August | 135.63 | 73.87 | 61.77 | 250.07 | 36.28 | 0.00 | 0.00 | 0.00 |
September | 116.18 | 62.49 | 53.69 | 210.51 | 41.09 | 0.00 | 0.00 | 0.00 |
October | 88.83 | 48.74 | 40.09 | 166.52 | 45.81 | 0.00 | 0.00 | 0.00 |
November | 79.44 | 41.41 | 38.03 | 134.65 | 69.72 | 0.00 | 0.00 | 0.00 |
December | 69.44 | 36.78 | 32.66 | 118.05 | 78.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 106.49 | 54.46 | 52.03 | 185.80 | 56.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.49 | 34.17 | 32.66 | 114.79 | 35.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.49 | 77.67 | 68.97 | 263.72 | 79.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.21 | 104.97 | 37.24 | 251.24 | 62.33 | 0.00 | 0.00 | 0.00 |
February | 109.95 | 67.76 | 42.19 | 190.57 | 55.14 | 0.00 | 0.00 | 0.00 |
March | 85.28 | 40.02 | 45.27 | 150.80 | 57.53 | 0.00 | 0.00 | 0.00 |
April | 68.95 | 23.67 | 45.28 | 134.32 | 44.63 | 0.00 | 0.00 | 0.00 |
May | 50.01 | 4.30 | 45.70 | 84.43 | 39.51 | 0.00 | 0.00 | 0.00 |
June | 44.44 | 1.50 | 42.94 | 76.11 | 27.96 | 0.00 | 0.00 | 0.00 |
July | 46.16 | 3.19 | 42.97 | 89.59 | 22.80 | 0.00 | 0.00 | 0.00 |
August | 57.50 | 14.91 | 42.59 | 124.15 | 23.84 | 0.00 | 0.00 | 0.00 |
September | 80.22 | 37.52 | 42.70 | 165.41 | 30.05 | 0.00 | 0.00 | 0.00 |
October | 109.10 | 72.61 | 36.49 | 214.63 | 33.62 | 0.00 | 0.00 | 0.00 |
November | 136.06 | 96.72 | 39.34 | 242.50 | 54.51 | 0.00 | 0.00 | 0.00 |
December | 152.91 | 117.23 | 35.68 | 270.29 | 61.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.15 | 48.64 | 41.52 | 166.10 | 42.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.44 | 1.50 | 35.68 | 76.11 | 22.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.91 | 117.23 | 45.70 | 270.29 | 62.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.07 | 0.00 | 101.07 | 114.37 | 309.95 | 0.00 | 0.00 | 0.00 |
February | 126.87 | 0.00 | 126.87 | 137.87 | 275.71 | 0.00 | 0.00 | 0.00 |
March | 155.48 | 0.00 | 155.48 | 187.20 | 284.15 | 0.00 | 0.00 | 0.00 |
April | 179.50 | 0.88 | 178.62 | 254.83 | 211.40 | 0.00 | 0.00 | 0.00 |
May | 213.56 | 8.23 | 205.33 | 320.76 | 185.89 | 0.00 | 0.00 | 0.00 |
June | 224.43 | 17.49 | 206.94 | 386.40 | 136.54 | 0.00 | 0.00 | 0.00 |
July | 212.79 | 13.74 | 199.05 | 397.55 | 115.08 | 0.00 | 0.00 | 0.00 |
August | 179.44 | 2.61 | 176.83 | 326.15 | 119.79 | 0.00 | 0.00 | 0.00 |
September | 152.64 | 0.01 | 152.63 | 256.20 | 147.85 | 0.00 | 0.00 | 0.00 |
October | 121.08 | 0.00 | 121.08 | 218.22 | 169.62 | 0.00 | 0.00 | 0.00 |
November | 109.63 | 0.00 | 109.63 | 132.11 | 271.40 | 0.00 | 0.00 | 0.00 |
December | 94.09 | 0.00 | 94.09 | 105.44 | 308.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 156.00 | 3.60 | 152.40 | 237.00 | 211.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.09 | 0.00 | 94.09 | 105.44 | 115.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.43 | 17.49 | 206.94 | 397.55 | 309.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.07 | 0.00 | 101.07 | 108.39 | 324.32 | 0.00 | 0.00 | 0.00 |
February | 126.87 | 0.00 | 126.87 | 131.04 | 289.68 | 0.00 | 0.00 | 0.00 |
March | 155.48 | 0.00 | 155.48 | 179.35 | 297.74 | 0.00 | 0.00 | 0.00 |
April | 179.50 | 0.88 | 178.62 | 246.26 | 221.76 | 0.00 | 0.00 | 0.00 |
May | 213.56 | 8.23 | 205.33 | 310.83 | 194.73 | 0.00 | 0.00 | 0.00 |
June | 224.43 | 17.49 | 206.94 | 376.83 | 143.88 | 0.00 | 0.00 | 0.00 |
July | 212.79 | 13.74 | 199.05 | 388.69 | 121.74 | 0.00 | 0.00 | 0.00 |
August | 179.44 | 2.61 | 176.83 | 318.05 | 126.99 | 0.00 | 0.00 | 0.00 |
September | 152.64 | 0.01 | 152.63 | 249.15 | 156.74 | 0.00 | 0.00 | 0.00 |
October | 121.08 | 0.00 | 121.08 | 211.72 | 179.22 | 0.00 | 0.00 | 0.00 |
November | 109.63 | 0.00 | 109.63 | 126.10 | 284.28 | 0.00 | 0.00 | 0.00 |
December | 94.09 | 0.00 | 94.09 | 99.76 | 322.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 156.00 | 3.60 | 152.40 | 229.42 | 221.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.09 | 0.00 | 94.09 | 99.76 | 121.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.43 | 17.49 | 206.94 | 388.69 | 324.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.44 | 0.00 | 14.44 | 41.90 | 29.01 | 0.00 | 0.00 | 0.00 |
February | 18.12 | 0.00 | 18.12 | 46.33 | 25.83 | 0.00 | 0.00 | 0.00 |
March | 22.21 | 0.00 | 22.21 | 54.88 | 28.34 | 0.00 | 0.00 | 0.00 |
April | 25.64 | 0.13 | 25.52 | 69.34 | 21.10 | 0.00 | 0.00 | 0.00 |
May | 30.51 | 1.18 | 29.33 | 81.91 | 19.86 | 0.00 | 0.00 | 0.00 |
June | 32.06 | 2.50 | 29.56 | 93.66 | 13.73 | 0.00 | 0.00 | 0.00 |
July | 30.40 | 1.96 | 28.44 | 96.38 | 11.15 | 0.00 | 0.00 | 0.00 |
August | 25.64 | 0.37 | 25.26 | 84.95 | 11.21 | 0.00 | 0.00 | 0.00 |
September | 21.81 | 0.00 | 21.80 | 72.11 | 12.81 | 0.00 | 0.00 | 0.00 |
October | 17.30 | 0.00 | 17.30 | 65.93 | 15.81 | 0.00 | 0.00 | 0.00 |
November | 15.66 | 0.00 | 15.66 | 46.21 | 24.69 | 0.00 | 0.00 | 0.00 |
December | 13.44 | 0.00 | 13.44 | 40.23 | 28.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.29 | 0.51 | 21.77 | 66.27 | 20.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.44 | 0.00 | 13.44 | 40.23 | 11.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.06 | 2.50 | 29.56 | 96.38 | 29.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.06 | 76.41 | 67.65 | 346.64 | 106.49 | 0.00 | 0.00 | 0.00 |
February | 153.13 | 69.98 | 83.15 | 347.87 | 95.10 | 0.00 | 0.00 | 0.00 |
March | 188.39 | 84.86 | 103.53 | 417.21 | 104.16 | 0.00 | 0.00 | 0.00 |
April | 239.50 | 120.67 | 118.82 | 552.97 | 78.60 | 0.00 | 0.00 | 0.00 |
May | 225.49 | 94.47 | 131.02 | 527.21 | 74.21 | 0.00 | 0.00 | 0.00 |
June | 223.47 | 97.00 | 126.47 | 553.60 | 51.51 | 0.00 | 0.00 | 0.00 |
July | 253.42 | 126.07 | 127.35 | 638.30 | 41.93 | 0.00 | 0.00 | 0.00 |
August | 251.13 | 133.93 | 117.20 | 633.97 | 42.14 | 0.00 | 0.00 | 0.00 |
September | 182.56 | 83.93 | 98.63 | 480.80 | 48.05 | 0.00 | 0.00 | 0.00 |
October | 161.09 | 82.75 | 78.34 | 446.35 | 59.05 | 0.00 | 0.00 | 0.00 |
November | 145.59 | 73.32 | 72.28 | 354.13 | 90.72 | 0.00 | 0.00 | 0.00 |
December | 139.07 | 76.78 | 62.29 | 337.75 | 104.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.50 | 93.54 | 98.97 | 470.56 | 74.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.07 | 69.98 | 62.29 | 337.75 | 41.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.42 | 133.93 | 131.02 | 638.30 | 106.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.97 | 71.57 | 25.39 | 205.79 | 28.39 | 0.00 | 0.00 | 0.00 |
February | 74.97 | 46.20 | 28.77 | 163.13 | 25.45 | 0.00 | 0.00 | 0.00 |
March | 58.15 | 27.29 | 30.86 | 135.99 | 28.11 | 0.00 | 0.00 | 0.00 |
April | 47.01 | 16.14 | 30.87 | 127.80 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 34.10 | 2.93 | 31.16 | 94.22 | 20.29 | 0.00 | 0.00 | 0.00 |
June | 30.30 | 1.02 | 29.28 | 90.99 | 14.00 | 0.00 | 0.00 | 0.00 |
July | 31.47 | 2.18 | 29.30 | 102.26 | 11.25 | 0.00 | 0.00 | 0.00 |
August | 39.20 | 10.16 | 29.04 | 125.83 | 11.21 | 0.00 | 0.00 | 0.00 |
September | 54.70 | 25.58 | 29.11 | 152.62 | 12.83 | 0.00 | 0.00 | 0.00 |
October | 74.39 | 49.51 | 24.88 | 187.17 | 15.74 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 65.95 | 26.82 | 200.72 | 24.17 | 0.00 | 0.00 | 0.00 |
December | 104.26 | 79.93 | 24.33 | 218.84 | 27.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.47 | 33.17 | 28.31 | 150.42 | 20.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.30 | 1.02 | 24.33 | 90.99 | 11.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.26 | 79.93 | 31.16 | 218.84 | 28.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.29 | 0.00 | 18.29 | 16.53 | 64.03 | 0.00 | 0.00 | 0.00 |
February | 22.95 | 0.00 | 22.95 | 20.60 | 57.02 | 0.00 | 0.00 | 0.00 |
March | 28.13 | 0.00 | 28.13 | 29.30 | 57.58 | 0.00 | 0.00 | 0.00 |
April | 32.48 | 0.16 | 32.32 | 39.35 | 45.01 | 0.00 | 0.00 | 0.00 |
May | 38.64 | 1.49 | 37.15 | 50.54 | 39.35 | 0.00 | 0.00 | 0.00 |
June | 40.61 | 3.16 | 37.44 | 60.99 | 30.53 | 0.00 | 0.00 | 0.00 |
July | 38.50 | 2.49 | 36.01 | 62.17 | 27.14 | 0.00 | 0.00 | 0.00 |
August | 32.47 | 0.47 | 31.99 | 49.74 | 28.82 | 0.00 | 0.00 | 0.00 |
September | 27.62 | 0.00 | 27.61 | 38.72 | 35.18 | 0.00 | 0.00 | 0.00 |
October | 21.91 | 0.00 | 21.91 | 32.43 | 39.75 | 0.00 | 0.00 | 0.00 |
November | 19.83 | 0.00 | 19.83 | 19.05 | 57.87 | 0.00 | 0.00 | 0.00 |
December | 17.02 | 0.00 | 17.02 | 14.68 | 64.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.23 | 0.65 | 27.57 | 36.27 | 45.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.02 | 0.00 | 17.02 | 14.68 | 27.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.61 | 3.16 | 37.44 | 62.17 | 64.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.36 | 0.00 | 16.36 | 14.79 | 57.28 | 0.00 | 0.00 | 0.00 |
February | 20.54 | 0.00 | 20.54 | 18.43 | 51.02 | 0.00 | 0.00 | 0.00 |
March | 25.17 | 0.00 | 25.17 | 26.22 | 51.52 | 0.00 | 0.00 | 0.00 |
April | 29.06 | 0.14 | 28.91 | 35.21 | 40.27 | 0.00 | 0.00 | 0.00 |
May | 34.57 | 1.33 | 33.24 | 45.22 | 35.20 | 0.00 | 0.00 | 0.00 |
June | 36.33 | 2.83 | 33.50 | 54.57 | 27.31 | 0.00 | 0.00 | 0.00 |
July | 34.45 | 2.22 | 32.22 | 55.63 | 24.28 | 0.00 | 0.00 | 0.00 |
August | 29.05 | 0.42 | 28.62 | 44.50 | 25.78 | 0.00 | 0.00 | 0.00 |
September | 24.71 | 0.00 | 24.71 | 34.64 | 31.48 | 0.00 | 0.00 | 0.00 |
October | 19.60 | 0.00 | 19.60 | 29.02 | 35.56 | 0.00 | 0.00 | 0.00 |
November | 17.75 | 0.00 | 17.75 | 17.04 | 51.78 | 0.00 | 0.00 | 0.00 |
December | 15.23 | 0.00 | 15.23 | 13.14 | 57.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.25 | 0.58 | 24.67 | 32.45 | 40.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.23 | 0.00 | 15.23 | 13.14 | 24.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.33 | 2.83 | 33.50 | 55.63 | 57.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.00 | 267.20 | 94.81 | 640.16 | 172.83 | 0.00 | 0.00 | 0.00 |
February | 279.88 | 172.49 | 107.39 | 482.29 | 157.70 | 0.00 | 0.00 | 0.00 |
March | 217.09 | 101.87 | 115.23 | 379.96 | 164.06 | 0.00 | 0.00 | 0.00 |
April | 175.52 | 60.26 | 115.26 | 333.23 | 136.28 | 0.00 | 0.00 | 0.00 |
May | 127.29 | 10.95 | 116.34 | 201.44 | 124.81 | 0.00 | 0.00 | 0.00 |
June | 113.13 | 3.82 | 109.32 | 176.05 | 97.46 | 0.00 | 0.00 | 0.00 |
July | 117.50 | 8.13 | 109.37 | 209.32 | 85.29 | 0.00 | 0.00 | 0.00 |
August | 146.36 | 37.94 | 108.42 | 299.96 | 88.49 | 0.00 | 0.00 | 0.00 |
September | 204.20 | 95.50 | 108.69 | 409.61 | 103.30 | 0.00 | 0.00 | 0.00 |
October | 277.72 | 184.83 | 92.89 | 536.80 | 111.07 | 0.00 | 0.00 | 0.00 |
November | 346.34 | 246.20 | 100.14 | 614.64 | 156.87 | 0.00 | 0.00 | 0.00 |
December | 389.23 | 298.42 | 90.82 | 687.64 | 172.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 229.49 | 123.82 | 105.68 | 414.04 | 130.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.13 | 3.82 | 90.82 | 176.05 | 85.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.23 | 298.42 | 116.34 | 687.64 | 172.83 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131356E+10 | 0.969549E+09 | 0.344013E+09 | 0.232016E+10 | 0.601442E+09 |
February | 0.917283E+09 | 0.565317E+09 | 0.351966E+09 | 0.160027E+10 | 0.478301E+09 |
March | 0.787739E+09 | 0.369630E+09 | 0.418109E+09 | 0.140677E+10 | 0.540754E+09 |
April | 0.616338E+09 | 0.211611E+09 | 0.404727E+09 | 0.119953E+10 | 0.431069E+09 |
May | 0.461881E+09 | 39733814.90 | 0.422147E+09 | 0.781621E+09 | 0.390471E+09 |
June | 0.397272E+09 | 13409845.86 | 0.383862E+09 | 0.666691E+09 | 0.288092E+09 |
July | 0.426363E+09 | 29500837.39 | 0.396862E+09 | 0.795166E+09 | 0.267087E+09 |
August | 0.531075E+09 | 0.137683E+09 | 0.393392E+09 | 0.111136E+10 | 0.287429E+09 |
September | 0.717036E+09 | 0.335369E+09 | 0.381666E+09 | 0.145750E+10 | 0.329242E+09 |
October | 0.100772E+10 | 0.670671E+09 | 0.337051E+09 | 0.196285E+10 | 0.375677E+09 |
November | 0.121617E+10 | 0.864537E+09 | 0.351633E+09 | 0.216542E+10 | 0.524711E+09 |
December | 0.141237E+10 | 0.108284E+10 | 0.329532E+09 | 0.249504E+10 | 0.603413E+09 |
Annual Sum or Average | 0.980481E+10 | 0.528985E+10 | 0.451496E+10 | 0.179624E+11 | 0.511769E+10 |
Minimum of Months | 0.397272E+09 | 13409845.86 | 0.329532E+09 | 0.666691E+09 | 0.267087E+09 |
Maximum of Months | 0.141237E+10 | 0.108284E+10 | 0.422147E+09 | 0.249504E+10 | 0.603413E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369890E+10 | 0.273019E+10 | 0.968719E+09 | 0.657696E+10 | 0.161150E+10 |
February | 0.258301E+10 | 0.159190E+10 | 0.991113E+09 | 0.454599E+10 | 0.128447E+10 |
March | 0.221822E+10 | 0.104085E+10 | 0.117737E+10 | 0.400356E+10 | 0.146541E+10 |
April | 0.173557E+10 | 0.595883E+09 | 0.113968E+10 | 0.346230E+10 | 0.111626E+10 |
May | 0.130063E+10 | 0.111888E+09 | 0.118874E+10 | 0.227136E+10 | 0.101805E+10 |
June | 0.111869E+10 | 37761241.79 | 0.108093E+10 | 0.197322E+10 | 0.712017E+09 |
July | 0.120061E+10 | 83072412.98 | 0.111754E+10 | 0.238282E+10 | 0.616903E+09 |
August | 0.149547E+10 | 0.387706E+09 | 0.110777E+10 | 0.328334E+10 | 0.658213E+09 |
September | 0.201912E+10 | 0.944378E+09 | 0.107475E+10 | 0.421712E+10 | 0.789168E+09 |
October | 0.283768E+10 | 0.188857E+10 | 0.949113E+09 | 0.561379E+10 | 0.929212E+09 |
November | 0.342465E+10 | 0.243448E+10 | 0.990175E+09 | 0.615290E+10 | 0.137874E+10 |
December | 0.397715E+10 | 0.304921E+10 | 0.927941E+09 | 0.706681E+10 | 0.161108E+10 |
Annual Sum or Average | 0.276097E+11 | 0.148959E+11 | 0.127138E+11 | 0.515501E+11 | 0.131910E+11 |
Minimum of Months | 0.111869E+10 | 37761241.79 | 0.927941E+09 | 0.197322E+10 | 0.616903E+09 |
Maximum of Months | 0.397715E+10 | 0.304921E+10 | 0.118874E+10 | 0.706681E+10 | 0.161150E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.480509E+10 | 0.354667E+10 | 0.125842E+10 | 0.860983E+10 | 0.224308E+10 |
February | 0.335548E+10 | 0.206796E+10 | 0.128751E+10 | 0.593479E+10 | 0.181600E+10 |
March | 0.288160E+10 | 0.135213E+10 | 0.152947E+10 | 0.521358E+10 | 0.207921E+10 |
April | 0.225460E+10 | 0.774087E+09 | 0.148051E+10 | 0.449247E+10 | 0.161337E+10 |
May | 0.168959E+10 | 0.145349E+09 | 0.154424E+10 | 0.290571E+10 | 0.150164E+10 |
June | 0.145324E+10 | 49054002.09 | 0.140419E+10 | 0.250521E+10 | 0.108526E+10 |
July | 0.155966E+10 | 0.107916E+09 | 0.145174E+10 | 0.303668E+10 | 0.958020E+09 |
August | 0.194270E+10 | 0.503652E+09 | 0.143905E+10 | 0.423567E+10 | 0.100242E+10 |
September | 0.262296E+10 | 0.122680E+10 | 0.139616E+10 | 0.548289E+10 | 0.116907E+10 |
October | 0.368631E+10 | 0.245335E+10 | 0.123295E+10 | 0.732667E+10 | 0.134416E+10 |
November | 0.444882E+10 | 0.316253E+10 | 0.128629E+10 | 0.804710E+10 | 0.193764E+10 |
December | 0.516654E+10 | 0.396109E+10 | 0.120545E+10 | 0.925643E+10 | 0.223902E+10 |
Annual Sum or Average | 0.358666E+11 | 0.193506E+11 | 0.165160E+11 | 0.670470E+11 | 0.189889E+11 |
Minimum of Months | 0.145324E+10 | 49054002.09 | 0.120545E+10 | 0.250521E+10 | 0.958020E+09 |
Maximum of Months | 0.516654E+10 | 0.396109E+10 | 0.154424E+10 | 0.925643E+10 | 0.224308E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259714E+09 | 0.191696E+09 | 68017836.83 | 0.464466E+09 | 0.112065E+09 |
February | 0.181363E+09 | 0.111773E+09 | 69590245.24 | 0.318608E+09 | 90452409.98 |
March | 0.155750E+09 | 73082247.84 | 82668012.91 | 0.279024E+09 | 0.105244E+09 |
April | 0.121862E+09 | 41839190.35 | 80022368.62 | 0.238752E+09 | 81211267.57 |
May | 91322771.85 | 7856057.63 | 83466714.22 | 0.153445E+09 | 75362767.97 |
June | 78548484.78 | 2651356.84 | 75897127.94 | 0.132523E+09 | 52858559.07 |
July | 84300374.06 | 5832822.22 | 78467551.84 | 0.161294E+09 | 45544494.29 |
August | 0.105004E+09 | 27222272.24 | 77781517.74 | 0.225948E+09 | 47065643.57 |
September | 0.141771E+09 | 66308265.72 | 75462790.44 | 0.293636E+09 | 55647528.57 |
October | 0.199245E+09 | 0.132603E+09 | 66641376.49 | 0.394761E+09 | 62785360.74 |
November | 0.240458E+09 | 0.170934E+09 | 69524362.08 | 0.433406E+09 | 95714435.20 |
December | 0.279251E+09 | 0.214096E+09 | 65154661.93 | 0.499402E+09 | 0.111223E+09 |
Annual Sum or Average | 0.193859E+10 | 0.104589E+10 | 0.892695E+09 | 0.359526E+10 | 0.935174E+09 |
Minimum of Months | 78548484.78 | 2651356.84 | 65154661.93 | 0.132523E+09 | 45544494.29 |
Maximum of Months | 0.279251E+09 | 0.214096E+09 | 83466714.22 | 0.499402E+09 | 0.112065E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183433E+09 | 91526423.86 | 91906905.35 | 0.298854E+09 | 0.223617E+09 |
February | 0.200496E+09 | 92934228.36 | 0.107561E+09 | 0.315195E+09 | 0.175732E+09 |
March | 0.254664E+09 | 0.113326E+09 | 0.141337E+09 | 0.406355E+09 | 0.198367E+09 |
April | 0.339821E+09 | 0.177649E+09 | 0.162172E+09 | 0.594729E+09 | 0.148167E+09 |
May | 0.344861E+09 | 0.160123E+09 | 0.184738E+09 | 0.596078E+09 | 0.135556E+09 |
June | 0.353782E+09 | 0.177837E+09 | 0.175945E+09 | 0.638419E+09 | 94355532.82 |
July | 0.386997E+09 | 0.208030E+09 | 0.178968E+09 | 0.727004E+09 | 81506288.66 |
August | 0.363282E+09 | 0.197846E+09 | 0.165437E+09 | 0.685663E+09 | 85461377.85 |
September | 0.301140E+09 | 0.161965E+09 | 0.139175E+09 | 0.553065E+09 | 0.101573E+09 |
October | 0.237924E+09 | 0.130545E+09 | 0.107379E+09 | 0.446930E+09 | 0.121440E+09 |
November | 0.205898E+09 | 0.107324E+09 | 98573806.38 | 0.342782E+09 | 0.188471E+09 |
December | 0.185980E+09 | 98499410.79 | 87480405.89 | 0.306774E+09 | 0.222352E+09 |
Annual Sum or Average | 0.335828E+10 | 0.171761E+10 | 0.164067E+10 | 0.591185E+10 | 0.177660E+10 |
Minimum of Months | 0.183433E+09 | 91526423.86 | 87480405.89 | 0.298854E+09 | 81506288.66 |
Maximum of Months | 0.386997E+09 | 0.208030E+09 | 0.184738E+09 | 0.727004E+09 | 0.223617E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38673031.88 | 0.00 | 38673031.88 | 42129466.29 | 0.119292E+09 |
February | 43847041.44 | 0.00 | 43847041.44 | 45833865.77 | 94687097.17 |
March | 59493074.91 | 149.08 | 59492925.83 | 68741329.91 | 0.108150E+09 |
April | 66468798.23 | 324953.58 | 66143844.65 | 86664398.46 | 80079303.89 |
May | 81718431.75 | 3150707.44 | 78567724.31 | 0.113748E+09 | 72078288.81 |
June | 83107415.33 | 6476857.56 | 76630557.77 | 0.130851E+09 | 53156657.59 |
July | 81424075.67 | 5257166.52 | 76166909.15 | 0.137096E+09 | 48828331.05 |
August | 68663146.08 | 1000191.28 | 67662954.81 | 0.111419E+09 | 50982929.18 |
September | 56521861.11 | 4081.39 | 56517779.72 | 86118525.27 | 59301405.54 |
October | 46330312.59 | 0.00 | 46330312.59 | 76516071.36 | 68659402.77 |
November | 40595561.14 | 0.00 | 40595561.14 | 46321823.31 | 0.102049E+09 |
December | 36001305.81 | 0.00 | 36001305.81 | 38567124.21 | 0.119232E+09 |
Annual Sum or Average | 0.702844E+09 | 16214106.84 | 0.686630E+09 | 0.984006E+09 | 0.976496E+09 |
Minimum of Months | 36001305.81 | 0.00 | 36001305.81 | 38567124.21 | 48828331.05 |
Maximum of Months | 83107415.33 | 6476857.56 | 78567724.31 | 0.137096E+09 | 0.119292E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183433E+09 | 91526423.86 | 91906905.35 | 0.307448E+09 | 0.218704E+09 |
February | 0.200496E+09 | 92934228.36 | 0.107561E+09 | 0.320593E+09 | 0.172825E+09 |
March | 0.254664E+09 | 0.113326E+09 | 0.141337E+09 | 0.410266E+09 | 0.196506E+09 |
April | 0.339821E+09 | 0.177649E+09 | 0.162172E+09 | 0.593455E+09 | 0.149699E+09 |
May | 0.344861E+09 | 0.160123E+09 | 0.184738E+09 | 0.590838E+09 | 0.138918E+09 |
June | 0.353782E+09 | 0.177837E+09 | 0.175945E+09 | 0.627869E+09 | 0.102037E+09 |
July | 0.386997E+09 | 0.208030E+09 | 0.178968E+09 | 0.714468E+09 | 92228010.16 |
August | 0.363282E+09 | 0.197846E+09 | 0.165437E+09 | 0.676843E+09 | 95669812.64 |
September | 0.301140E+09 | 0.161965E+09 | 0.139175E+09 | 0.550436E+09 | 0.107013E+09 |
October | 0.237924E+09 | 0.130545E+09 | 0.107379E+09 | 0.448046E+09 | 0.125360E+09 |
November | 0.205898E+09 | 0.107324E+09 | 98573806.38 | 0.349463E+09 | 0.185478E+09 |
December | 0.185980E+09 | 98499410.79 | 87480405.89 | 0.315411E+09 | 0.217504E+09 |
Annual Sum or Average | 0.335828E+10 | 0.171761E+10 | 0.164067E+10 | 0.590514E+10 | 0.180194E+10 |
Minimum of Months | 0.183433E+09 | 91526423.86 | 87480405.89 | 0.307448E+09 | 92228010.16 |
Maximum of Months | 0.386997E+09 | 0.208030E+09 | 0.184738E+09 | 0.714468E+09 | 0.218704E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207730E+09 | 0.153327E+09 | 54403450.09 | 0.349415E+09 | 0.130488E+09 |
February | 0.145062E+09 | 89400535.50 | 55661126.70 | 0.234493E+09 | 0.108963E+09 |
March | 0.124575E+09 | 58454173.31 | 66121260.59 | 0.200989E+09 | 0.123334E+09 |
April | 97469863.05 | 33464697.05 | 64005165.99 | 0.170325E+09 | 99440056.03 |
May | 73043691.06 | 6283596.46 | 66760094.59 | 0.100018E+09 | 93282806.76 |
June | 62826293.36 | 2120663.73 | 60705629.64 | 83648187.03 | 71864333.87 |
July | 67426889.86 | 4665329.97 | 62761559.89 | 0.106366E+09 | 65605406.66 |
August | 83986329.37 | 21773487.64 | 62212841.74 | 0.158649E+09 | 68634118.67 |
September | 0.113394E+09 | 53036065.13 | 60358228.73 | 0.214566E+09 | 77759262.23 |
October | 0.159364E+09 | 0.106061E+09 | 53302500.76 | 0.293815E+09 | 85825395.34 |
November | 0.192328E+09 | 0.136720E+09 | 55608430.65 | 0.325222E+09 | 0.114639E+09 |
December | 0.223356E+09 | 0.171243E+09 | 52113365.60 | 0.377050E+09 | 0.129512E+09 |
Annual Sum or Average | 0.155056E+10 | 0.836549E+09 | 0.714014E+09 | 0.261456E+10 | 0.116935E+10 |
Minimum of Months | 62826293.36 | 2120663.73 | 52113365.60 | 83648187.03 | 65605406.66 |
Maximum of Months | 0.223356E+09 | 0.171243E+09 | 66760094.59 | 0.377050E+09 | 0.130488E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30942526.57 | 0.00 | 30942526.57 | 34152692.59 | 95579040.02 |
February | 35082282.89 | 0.00 | 35082282.89 | 37490881.12 | 75409752.81 |
March | 47600768.84 | 119.28 | 47600649.57 | 56363710.98 | 86070266.36 |
April | 53182087.23 | 259997.32 | 52922089.91 | 74044650.39 | 61349668.92 |
May | 65383411.19 | 2520900.07 | 62862511.13 | 96174004.05 | 55515706.85 |
June | 66494745.35 | 5182172.89 | 61312572.47 | 0.110900E+09 | 39807577.68 |
July | 65147895.11 | 4206290.71 | 60941604.40 | 0.116859E+09 | 35330095.32 |
August | 54937798.22 | 800259.09 | 54137539.13 | 95660594.62 | 36472179.67 |
September | 45223482.72 | 3265.55 | 45220217.18 | 73425427.50 | 43412532.10 |
October | 37069163.15 | 0.00 | 37069163.15 | 64231884.10 | 51820098.32 |
November | 32480753.85 | 0.00 | 32480753.85 | 38466230.32 | 80005877.52 |
December | 28804862.39 | 0.00 | 28804862.39 | 31531056.34 | 94824371.05 |
Annual Sum or Average | 0.562350E+09 | 12973004.89 | 0.549377E+09 | 0.829300E+09 | 0.755597E+09 |
Minimum of Months | 28804862.39 | 0.00 | 28804862.39 | 31531056.34 | 35330095.32 |
Maximum of Months | 66494745.35 | 5182172.89 | 62862511.13 | 0.116859E+09 | 95579040.02 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.192939E+09 | 0.102331E+09 | 90607881.74 | 0.308763E+09 | 0.213442E+09 |
February | 0.185235E+09 | 84648623.84 | 0.100586E+09 | 0.281528E+09 | 0.168980E+09 |
March | 0.252307E+09 | 0.113651E+09 | 0.138656E+09 | 0.395325E+09 | 0.190778E+09 |
April | 0.310408E+09 | 0.156401E+09 | 0.154007E+09 | 0.536235E+09 | 0.142310E+09 |
May | 0.302001E+09 | 0.126526E+09 | 0.175475E+09 | 0.513818E+09 | 0.131460E+09 |
June | 0.289643E+09 | 0.125727E+09 | 0.163916E+09 | 0.520904E+09 | 92964069.64 |
July | 0.339409E+09 | 0.168846E+09 | 0.170563E+09 | 0.640881E+09 | 80829256.50 |
August | 0.336333E+09 | 0.179368E+09 | 0.156965E+09 | 0.637369E+09 | 83149750.44 |
September | 0.236617E+09 | 0.108787E+09 | 0.127830E+09 | 0.432479E+09 | 99252955.45 |
October | 0.215748E+09 | 0.110824E+09 | 0.104923E+09 | 0.400579E+09 | 0.116521E+09 |
November | 0.188699E+09 | 95023132.89 | 93675494.95 | 0.303924E+09 | 0.182038E+09 |
December | 0.186260E+09 | 0.102833E+09 | 83426370.81 | 0.299070E+09 | 0.212802E+09 |
Annual Sum or Average | 0.303560E+10 | 0.147497E+10 | 0.156063E+10 | 0.527087E+10 | 0.171453E+10 |
Minimum of Months | 0.185235E+09 | 84648623.84 | 83426370.81 | 0.281528E+09 | 80829256.50 |
Maximum of Months | 0.339409E+09 | 0.179368E+09 | 0.175475E+09 | 0.640881E+09 | 0.213442E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259714E+09 | 0.191696E+09 | 68017836.83 | 0.463233E+09 | 0.111784E+09 |
February | 0.181363E+09 | 0.111773E+09 | 69590245.24 | 0.318014E+09 | 89677774.45 |
March | 0.155750E+09 | 73082247.84 | 82668012.91 | 0.277769E+09 | 0.104454E+09 |
April | 0.121862E+09 | 41839190.35 | 80022368.62 | 0.237546E+09 | 79968153.72 |
May | 91322771.85 | 7856057.63 | 83466714.22 | 0.152609E+09 | 74008572.91 |
June | 78548484.78 | 2651356.84 | 75897127.94 | 0.132147E+09 | 51429274.14 |
July | 84300374.06 | 5832822.22 | 78467551.84 | 0.160445E+09 | 44155508.48 |
August | 0.105004E+09 | 27222272.24 | 77781517.74 | 0.224931E+09 | 45814202.75 |
September | 0.141771E+09 | 66308265.72 | 75462790.44 | 0.293563E+09 | 54019383.56 |
October | 0.199245E+09 | 0.132603E+09 | 66641376.49 | 0.394206E+09 | 61915930.37 |
November | 0.240458E+09 | 0.170934E+09 | 69524362.08 | 0.432821E+09 | 94889332.05 |
December | 0.279251E+09 | 0.214096E+09 | 65154661.93 | 0.498465E+09 | 0.110655E+09 |
Annual Sum or Average | 0.193859E+10 | 0.104589E+10 | 0.892695E+09 | 0.358575E+10 | 0.922771E+09 |
Minimum of Months | 78548484.78 | 2651356.84 | 65154661.93 | 0.132147E+09 | 44155508.48 |
Maximum of Months | 0.279251E+09 | 0.214096E+09 | 83466714.22 | 0.498465E+09 | 0.111784E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38673031.88 | 0.00 | 38673031.88 | 40739899.50 | 0.118479E+09 |
February | 43847041.44 | 0.00 | 43847041.44 | 45079981.76 | 93333078.96 |
March | 59493074.91 | 149.08 | 59492925.83 | 67510537.92 | 0.107072E+09 |
April | 66468798.23 | 324953.58 | 66143844.65 | 85982175.41 | 78207269.61 |
May | 81718431.75 | 3150707.44 | 78567724.31 | 0.113805E+09 | 70303940.45 |
June | 83107415.33 | 6476857.56 | 76630557.77 | 0.132090E+09 | 50684723.21 |
July | 81424075.67 | 5257166.52 | 76166909.15 | 0.137416E+09 | 46103744.92 |
August | 68663146.08 | 1000191.28 | 67662954.81 | 0.110671E+09 | 48355758.86 |
September | 56521861.11 | 4081.39 | 56517779.72 | 86227957.80 | 56236117.69 |
October | 46330312.59 | 0.00 | 46330312.59 | 75428779.71 | 66863992.94 |
November | 40595561.14 | 0.00 | 40595561.14 | 45439332.51 | 0.100134E+09 |
December | 36001305.81 | 0.00 | 36001305.81 | 37141521.37 | 0.117906E+09 |
Annual Sum or Average | 0.702844E+09 | 16214106.84 | 0.686630E+09 | 0.977532E+09 | 0.953680E+09 |
Minimum of Months | 36001305.81 | 0.00 | 36001305.81 | 37141521.37 | 46103744.92 |
Maximum of Months | 83107415.33 | 6476857.56 | 78567724.31 | 0.137416E+09 | 0.118479E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.192939E+09 | 0.102331E+09 | 90607881.74 | 0.316909E+09 | 0.207438E+09 |
February | 0.185235E+09 | 84648623.84 | 0.100586E+09 | 0.287237E+09 | 0.165339E+09 |
March | 0.252307E+09 | 0.113651E+09 | 0.138656E+09 | 0.399632E+09 | 0.188475E+09 |
April | 0.310408E+09 | 0.156401E+09 | 0.154007E+09 | 0.536680E+09 | 0.142876E+09 |
May | 0.302001E+09 | 0.126526E+09 | 0.175475E+09 | 0.510546E+09 | 0.134039E+09 |
June | 0.289643E+09 | 0.125727E+09 | 0.163916E+09 | 0.513890E+09 | 98973545.09 |
July | 0.339409E+09 | 0.168846E+09 | 0.170563E+09 | 0.631222E+09 | 89597259.31 |
August | 0.336333E+09 | 0.179368E+09 | 0.156965E+09 | 0.629564E+09 | 91127801.57 |
September | 0.236617E+09 | 0.108787E+09 | 0.127830E+09 | 0.431150E+09 | 0.102712E+09 |
October | 0.215748E+09 | 0.110824E+09 | 0.104923E+09 | 0.401692E+09 | 0.119395E+09 |
November | 0.188699E+09 | 95023132.89 | 93675494.95 | 0.310557E+09 | 0.177246E+09 |
December | 0.186260E+09 | 0.102833E+09 | 83426370.81 | 0.306908E+09 | 0.206540E+09 |
Annual Sum or Average | 0.303560E+10 | 0.147497E+10 | 0.156063E+10 | 0.527599E+10 | 0.172376E+10 |
Minimum of Months | 0.185235E+09 | 84648623.84 | 83426370.81 | 0.287237E+09 | 89597259.31 |
Maximum of Months | 0.339409E+09 | 0.179368E+09 | 0.175475E+09 | 0.631222E+09 | 0.207438E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48976954.75 | 0.00 | 48976954.75 | 51684861.52 | 0.159953E+09 |
February | 55529511.39 | 0.00 | 55529511.39 | 57678909.71 | 0.126683E+09 |
March | 75344225.57 | 188.80 | 75344036.77 | 88873681.77 | 0.141742E+09 |
April | 84178539.01 | 411533.21 | 83767005.80 | 0.116604E+09 | 0.103326E+09 |
May | 0.103491E+09 | 3990172.17 | 99501065.49 | 0.152600E+09 | 93121018.21 |
June | 0.105250E+09 | 8202531.44 | 97047766.30 | 0.177404E+09 | 66716246.38 |
July | 0.103118E+09 | 6657869.69 | 96460584.57 | 0.185786E+09 | 60446025.12 |
August | 86957542.11 | 1266679.14 | 85690862.97 | 0.150137E+09 | 64128265.69 |
September | 71581370.76 | 5168.82 | 71576201.94 | 0.114180E+09 | 76675249.20 |
October | 58674417.61 | 0.00 | 58674417.61 | 98146190.54 | 92542410.71 |
November | 51411716.75 | 0.00 | 51411716.75 | 57449316.69 | 0.137713E+09 |
December | 45593382.25 | 0.00 | 45593382.25 | 46426778.95 | 0.161416E+09 |
Annual Sum or Average | 0.890108E+09 | 20534143.27 | 0.869574E+09 | 0.129697E+10 | 0.128446E+10 |
Minimum of Months | 45593382.25 | 0.00 | 45593382.25 | 46426778.95 | 60446025.12 |
Maximum of Months | 0.105250E+09 | 8202531.44 | 99501065.49 | 0.185786E+09 | 0.161416E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18054933.50 | 0.00 | 18054933.50 | 19053180.06 | 58965208.80 |
February | 20470477.19 | 0.00 | 20470477.19 | 21262834.42 | 46700489.41 |
March | 27775001.30 | 69.60 | 27774931.71 | 32762519.07 | 52251864.70 |
April | 31031695.04 | 151708.18 | 30879986.86 | 42984917.11 | 38090307.76 |
May | 38151155.44 | 1470942.68 | 36680212.75 | 56254769.45 | 34328263.15 |
June | 38799617.82 | 3023792.73 | 35775825.09 | 65398477.42 | 24594370.92 |
July | 38013732.04 | 2454366.45 | 35559365.59 | 68488235.90 | 22282907.73 |
August | 32056150.65 | 466950.38 | 31589200.27 | 55346828.32 | 23640334.08 |
September | 26387857.21 | 1905.44 | 26385951.77 | 42091296.95 | 28265671.73 |
October | 21629819.85 | 0.00 | 21629819.85 | 36180749.75 | 34114964.47 |
November | 18952487.59 | 0.00 | 18952487.59 | 21178196.92 | 50766824.01 |
December | 16807608.57 | 0.00 | 16807608.57 | 17114833.10 | 59504786.79 |
Annual Sum or Average | 0.328131E+09 | 7569735.46 | 0.320561E+09 | 0.478117E+09 | 0.473506E+09 |
Minimum of Months | 16807608.57 | 0.00 | 16807608.57 | 17114833.10 | 22282907.73 |
Maximum of Months | 38799617.82 | 3023792.73 | 36680212.75 | 68488235.90 | 59504786.79 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121182E+09 | 89444795.35 | 31736848.58 | 0.218373E+09 | 54092596.86 |
February | 84623309.73 | 52152781.73 | 32470528.00 | 0.149933E+09 | 43913665.68 |
March | 72672444.04 | 34099882.34 | 38572561.70 | 0.131856E+09 | 50472802.88 |
April | 56860112.35 | 19521997.62 | 37338114.73 | 0.113650E+09 | 39029066.68 |
May | 42610837.34 | 3665604.83 | 38945232.51 | 73473127.89 | 36681890.04 |
June | 36650406.47 | 1237112.42 | 35413294.05 | 63507177.69 | 26331546.47 |
July | 39334214.83 | 2721571.35 | 36612643.49 | 76669735.36 | 23435222.38 |
August | 48994345.27 | 12701802.53 | 36292542.74 | 0.106654E+09 | 24450635.99 |
September | 66149803.51 | 30939169.58 | 35210633.93 | 0.138365E+09 | 28148238.35 |
October | 92966718.38 | 61872120.66 | 31094597.73 | 0.184950E+09 | 32388317.10 |
November | 0.112197E+09 | 79757008.84 | 32439787.19 | 0.203594E+09 | 46875491.91 |
December | 0.130297E+09 | 99896337.36 | 30400902.70 | 0.234422E+09 | 54133469.84 |
Annual Sum or Average | 0.904538E+09 | 0.488010E+09 | 0.416528E+09 | 0.169545E+10 | 0.459953E+09 |
Minimum of Months | 36650406.47 | 1237112.42 | 30400902.70 | 63507177.69 | 23435222.38 |
Maximum of Months | 0.130297E+09 | 99896337.36 | 38945232.51 | 0.234422E+09 | 54133469.84 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328912E+09 | 0.242771E+09 | 86140298.66 | 0.592708E+09 | 0.146818E+09 |
February | 0.229685E+09 | 0.141553E+09 | 88131654.70 | 0.406949E+09 | 0.119191E+09 |
March | 0.197248E+09 | 92554055.65 | 0.104694E+09 | 0.357884E+09 | 0.136994E+09 |
April | 0.154330E+09 | 52986694.67 | 0.101343E+09 | 0.308470E+09 | 0.105933E+09 |
May | 0.115655E+09 | 9949201.30 | 0.105705E+09 | 0.199421E+09 | 99562152.67 |
June | 99476699.84 | 3357776.15 | 96118923.69 | 0.172371E+09 | 71469203.11 |
July | 0.106761E+09 | 7386901.32 | 99374203.37 | 0.208097E+09 | 63607987.11 |
August | 0.132981E+09 | 34475290.17 | 98505384.48 | 0.289480E+09 | 66363921.46 |
September | 0.179544E+09 | 83975234.71 | 95568862.65 | 0.375552E+09 | 76400076.48 |
October | 0.252331E+09 | 0.167934E+09 | 84397098.49 | 0.501991E+09 | 87908517.49 |
November | 0.304525E+09 | 0.216477E+09 | 88048217.83 | 0.552595E+09 | 0.127230E+09 |
December | 0.353653E+09 | 0.271139E+09 | 82514268.30 | 0.636269E+09 | 0.146929E+09 |
Annual Sum or Average | 0.245510E+10 | 0.132456E+10 | 0.113054E+10 | 0.460179E+10 | 0.124841E+10 |
Minimum of Months | 99476699.84 | 3357776.15 | 82514268.30 | 0.172371E+09 | 63607987.11 |
Maximum of Months | 0.353653E+09 | 0.271139E+09 | 0.105705E+09 | 0.636269E+09 | 0.146929E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259714E+09 | 0.191696E+09 | 68017836.83 | 0.463332E+09 | 0.110023E+09 |
February | 0.181363E+09 | 0.111773E+09 | 69590245.24 | 0.317324E+09 | 88749003.77 |
March | 0.155750E+09 | 73082247.84 | 82668012.91 | 0.277538E+09 | 0.103816E+09 |
April | 0.121862E+09 | 41839190.35 | 80022368.62 | 0.236689E+09 | 80336318.34 |
May | 91322771.85 | 7856057.63 | 83466714.22 | 0.151666E+09 | 74553144.56 |
June | 78548484.78 | 2651356.84 | 75897127.94 | 0.130873E+09 | 52365672.91 |
July | 84300374.06 | 5832822.22 | 78467551.84 | 0.159538E+09 | 45028954.73 |
August | 0.105004E+09 | 27222272.24 | 77781517.74 | 0.224018E+09 | 46362783.59 |
September | 0.141771E+09 | 66308265.72 | 75462790.44 | 0.291702E+09 | 54755534.85 |
October | 0.199245E+09 | 0.132603E+09 | 66641376.49 | 0.393072E+09 | 61327617.77 |
November | 0.240458E+09 | 0.170934E+09 | 69524362.08 | 0.431923E+09 | 93832973.22 |
December | 0.279251E+09 | 0.214096E+09 | 65154661.93 | 0.498184E+09 | 0.108921E+09 |
Annual Sum or Average | 0.193859E+10 | 0.104589E+10 | 0.892695E+09 | 0.357586E+10 | 0.920072E+09 |
Minimum of Months | 78548484.78 | 2651356.84 | 65154661.93 | 0.130873E+09 | 45028954.73 |
Maximum of Months | 0.279251E+09 | 0.214096E+09 | 83466714.22 | 0.498184E+09 | 0.110023E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183433E+09 | 91526423.86 | 91906905.35 | 0.297587E+09 | 0.219014E+09 |
February | 0.200496E+09 | 92934228.36 | 0.107561E+09 | 0.313756E+09 | 0.172136E+09 |
March | 0.254664E+09 | 0.113326E+09 | 0.141337E+09 | 0.403436E+09 | 0.195332E+09 |
April | 0.339821E+09 | 0.177649E+09 | 0.162172E+09 | 0.589617E+09 | 0.146383E+09 |
May | 0.344861E+09 | 0.160123E+09 | 0.184738E+09 | 0.590596E+09 | 0.133848E+09 |
June | 0.353782E+09 | 0.177837E+09 | 0.175945E+09 | 0.632519E+09 | 93247983.94 |
July | 0.386997E+09 | 0.208030E+09 | 0.178968E+09 | 0.721169E+09 | 80323126.76 |
August | 0.363282E+09 | 0.197846E+09 | 0.165437E+09 | 0.680313E+09 | 83961955.70 |
September | 0.301140E+09 | 0.161965E+09 | 0.139175E+09 | 0.548872E+09 | 99780116.69 |
October | 0.237924E+09 | 0.130545E+09 | 0.107379E+09 | 0.444530E+09 | 0.118462E+09 |
November | 0.205898E+09 | 0.107324E+09 | 98573806.38 | 0.341250E+09 | 0.184450E+09 |
December | 0.185980E+09 | 98499410.79 | 87480405.89 | 0.305974E+09 | 0.217221E+09 |
Annual Sum or Average | 0.335828E+10 | 0.171761E+10 | 0.164067E+10 | 0.586962E+10 | 0.174416E+10 |
Minimum of Months | 0.183433E+09 | 91526423.86 | 87480405.89 | 0.297587E+09 | 80323126.76 |
Maximum of Months | 0.386997E+09 | 0.208030E+09 | 0.184738E+09 | 0.721169E+09 | 0.219014E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38673031.88 | 0.00 | 38673031.88 | 42960743.18 | 0.116300E+09 |
February | 43847041.44 | 0.00 | 43847041.44 | 46391742.43 | 92538621.61 |
March | 59493074.91 | 149.08 | 59492925.83 | 68455225.02 | 0.106637E+09 |
April | 66468798.23 | 324953.58 | 66143844.65 | 85117573.77 | 79850624.90 |
May | 81718431.75 | 3150707.44 | 78567724.31 | 0.111757E+09 | 71957175.24 |
June | 83107415.33 | 6476857.56 | 76630557.77 | 0.128079E+09 | 53962159.03 |
July | 81424075.67 | 5257166.52 | 76166909.15 | 0.134290E+09 | 50033235.90 |
August | 68663146.08 | 1000191.28 | 67662954.81 | 0.109465E+09 | 51963218.38 |
September | 56521861.11 | 4081.39 | 56517779.72 | 85125212.28 | 59209366.12 |
October | 46330312.59 | 0.00 | 46330312.59 | 76581132.68 | 67248854.00 |
November | 40595561.14 | 0.00 | 40595561.14 | 47042851.14 | 99495048.42 |
December | 36001305.81 | 0.00 | 36001305.81 | 39767914.22 | 0.115793E+09 |
Annual Sum or Average | 0.702844E+09 | 16214106.84 | 0.686630E+09 | 0.975033E+09 | 0.964988E+09 |
Minimum of Months | 36001305.81 | 0.00 | 36001305.81 | 39767914.22 | 50033235.90 |
Maximum of Months | 83107415.33 | 6476857.56 | 78567724.31 | 0.134290E+09 | 0.116300E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183433E+09 | 91526423.86 | 91906905.35 | 0.307463E+09 | 0.213150E+09 |
February | 0.200496E+09 | 92934228.36 | 0.107561E+09 | 0.319948E+09 | 0.168794E+09 |
March | 0.254664E+09 | 0.113326E+09 | 0.141337E+09 | 0.407503E+09 | 0.193528E+09 |
April | 0.339821E+09 | 0.177649E+09 | 0.162172E+09 | 0.587398E+09 | 0.149006E+09 |
May | 0.344861E+09 | 0.160123E+09 | 0.184738E+09 | 0.584125E+09 | 0.138403E+09 |
June | 0.353782E+09 | 0.177837E+09 | 0.175945E+09 | 0.619990E+09 | 0.103428E+09 |
July | 0.386997E+09 | 0.208030E+09 | 0.178968E+09 | 0.706344E+09 | 94335273.13 |
August | 0.363282E+09 | 0.197846E+09 | 0.165437E+09 | 0.669796E+09 | 97162432.89 |
September | 0.301140E+09 | 0.161965E+09 | 0.139175E+09 | 0.545634E+09 | 0.106503E+09 |
October | 0.237924E+09 | 0.130545E+09 | 0.107379E+09 | 0.445999E+09 | 0.122690E+09 |
November | 0.205898E+09 | 0.107324E+09 | 98573806.38 | 0.349006E+09 | 0.180702E+09 |
December | 0.185980E+09 | 98499410.79 | 87480405.89 | 0.316180E+09 | 0.211200E+09 |
Annual Sum or Average | 0.335828E+10 | 0.171761E+10 | 0.164067E+10 | 0.585939E+10 | 0.177890E+10 |
Minimum of Months | 0.183433E+09 | 91526423.86 | 87480405.89 | 0.307463E+09 | 94335273.13 |
Maximum of Months | 0.386997E+09 | 0.208030E+09 | 0.184738E+09 | 0.706344E+09 | 0.213150E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380896E+09 | 0.281141E+09 | 99754685.41 | 0.672924E+09 | 0.166947E+09 |
February | 0.265986E+09 | 0.163926E+09 | 0.102061E+09 | 0.461022E+09 | 0.133397E+09 |
March | 0.228423E+09 | 0.107182E+09 | 0.121241E+09 | 0.403893E+09 | 0.154084E+09 |
April | 0.178722E+09 | 61361187.97 | 0.117360E+09 | 0.348167E+09 | 0.115674E+09 |
May | 0.133934E+09 | 11521662.46 | 0.122412E+09 | 0.226129E+09 | 0.105832E+09 |
June | 0.115199E+09 | 3888469.26 | 0.111310E+09 | 0.197279E+09 | 72469077.18 |
July | 0.123635E+09 | 8554393.57 | 0.115080E+09 | 0.239964E+09 | 61076369.25 |
August | 0.153998E+09 | 39924074.78 | 0.114074E+09 | 0.332526E+09 | 63839711.42 |
September | 0.207921E+09 | 97247435.30 | 0.110673E+09 | 0.428748E+09 | 77898697.81 |
October | 0.292211E+09 | 0.194475E+09 | 97735974.21 | 0.574862E+09 | 90054572.26 |
November | 0.352655E+09 | 0.250691E+09 | 0.101964E+09 | 0.628564E+09 | 0.141282E+09 |
December | 0.409548E+09 | 0.313992E+09 | 95555564.63 | 0.723947E+09 | 0.165229E+09 |
Annual Sum or Average | 0.284313E+10 | 0.153390E+10 | 0.130922E+10 | 0.523802E+10 | 0.134778E+10 |
Minimum of Months | 0.115199E+09 | 3888469.26 | 95555564.63 | 0.197279E+09 | 61076369.25 |
Maximum of Months | 0.409548E+09 | 0.313992E+09 | 0.122412E+09 | 0.723947E+09 | 0.166947E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270701E+09 | 0.00 | 0.270701E+09 | 0.306340E+09 | 0.830174E+09 |
February | 0.306918E+09 | 0.00 | 0.306918E+09 | 0.333540E+09 | 0.666989E+09 |
March | 0.416436E+09 | 1043.49 | 0.416435E+09 | 0.501396E+09 | 0.761077E+09 |
April | 0.465264E+09 | 2274588.92 | 0.462989E+09 | 0.660528E+09 | 0.547949E+09 |
May | 0.572007E+09 | 22054116.78 | 0.549953E+09 | 0.859116E+09 | 0.497879E+09 |
June | 0.581730E+09 | 45336285.86 | 0.536394E+09 | 0.100155E+10 | 0.353905E+09 |
July | 0.569947E+09 | 36798771.89 | 0.533148E+09 | 0.106481E+10 | 0.308228E+09 |
August | 0.480624E+09 | 7001073.78 | 0.473623E+09 | 0.873557E+09 | 0.320849E+09 |
September | 0.395638E+09 | 28568.66 | 0.395609E+09 | 0.664064E+09 | 0.383237E+09 |
October | 0.324300E+09 | 0.00 | 0.324300E+09 | 0.584470E+09 | 0.454320E+09 |
November | 0.284158E+09 | 0.00 | 0.284158E+09 | 0.342419E+09 | 0.703462E+09 |
December | 0.252000E+09 | 0.00 | 0.252000E+09 | 0.282398E+09 | 0.827592E+09 |
Annual Sum or Average | 0.491972E+10 | 0.113494E+09 | 0.480623E+10 | 0.747419E+10 | 0.665566E+10 |
Minimum of Months | 0.252000E+09 | 0.00 | 0.252000E+09 | 0.282398E+09 | 0.308228E+09 |
Maximum of Months | 0.581730E+09 | 45336285.86 | 0.549953E+09 | 0.106481E+10 | 0.830174E+09 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270701E+09 | 0.00 | 0.270701E+09 | 0.290303E+09 | 0.868659E+09 |
February | 0.306918E+09 | 0.00 | 0.306918E+09 | 0.317005E+09 | 0.700795E+09 |
March | 0.416436E+09 | 1043.49 | 0.416435E+09 | 0.480359E+09 | 0.797479E+09 |
April | 0.465264E+09 | 2274588.92 | 0.462989E+09 | 0.638309E+09 | 0.574804E+09 |
May | 0.572007E+09 | 22054116.78 | 0.549953E+09 | 0.832528E+09 | 0.521553E+09 |
June | 0.581730E+09 | 45336285.86 | 0.536394E+09 | 0.976742E+09 | 0.372946E+09 |
July | 0.569947E+09 | 36798771.89 | 0.533148E+09 | 0.104107E+10 | 0.326069E+09 |
August | 0.480624E+09 | 7001073.78 | 0.473623E+09 | 0.851868E+09 | 0.340121E+09 |
September | 0.395638E+09 | 28568.66 | 0.395609E+09 | 0.645785E+09 | 0.406264E+09 |
October | 0.324300E+09 | 0.00 | 0.324300E+09 | 0.567066E+09 | 0.480019E+09 |
November | 0.284158E+09 | 0.00 | 0.284158E+09 | 0.326856E+09 | 0.736854E+09 |
December | 0.252000E+09 | 0.00 | 0.252000E+09 | 0.267201E+09 | 0.864773E+09 |
Annual Sum or Average | 0.491972E+10 | 0.113494E+09 | 0.480623E+10 | 0.723509E+10 | 0.699034E+10 |
Minimum of Months | 0.252000E+09 | 0.00 | 0.252000E+09 | 0.267201E+09 | 0.326069E+09 |
Maximum of Months | 0.581730E+09 | 45336285.86 | 0.549953E+09 | 0.104107E+10 | 0.868659E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38673031.88 | 0.00 | 38673031.88 | 0.112223E+09 | 77695643.51 |
February | 43847041.44 | 0.00 | 43847041.44 | 0.112080E+09 | 62480158.65 |
March | 59493074.91 | 149.08 | 59492925.83 | 0.146994E+09 | 75909681.71 |
April | 66468798.23 | 324953.58 | 66143844.65 | 0.179730E+09 | 54687113.12 |
May | 81718431.75 | 3150707.44 | 78567724.31 | 0.219396E+09 | 53184086.74 |
June | 83107415.33 | 6476857.56 | 76630557.77 | 0.242761E+09 | 35579991.08 |
July | 81424075.67 | 5257166.52 | 76166909.15 | 0.258149E+09 | 29877430.55 |
August | 68663146.08 | 1000191.28 | 67662954.81 | 0.227518E+09 | 30027339.56 |
September | 56521861.11 | 4081.39 | 56517779.72 | 0.186917E+09 | 33190904.57 |
October | 46330312.59 | 0.00 | 46330312.59 | 0.176580E+09 | 42346314.89 |
November | 40595561.14 | 0.00 | 40595561.14 | 0.119770E+09 | 64006235.37 |
December | 36001305.81 | 0.00 | 36001305.81 | 0.107749E+09 | 76028081.84 |
Annual Sum or Average | 0.702844E+09 | 16214106.84 | 0.686630E+09 | 0.208987E+10 | 0.635013E+09 |
Minimum of Months | 36001305.81 | 0.00 | 36001305.81 | 0.107749E+09 | 29877430.55 |
Maximum of Months | 83107415.33 | 6476857.56 | 78567724.31 | 0.258149E+09 | 77695643.51 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385850E+09 | 0.204647E+09 | 0.181203E+09 | 0.928438E+09 | 0.285213E+09 |
February | 0.370444E+09 | 0.169285E+09 | 0.201158E+09 | 0.841570E+09 | 0.230061E+09 |
March | 0.504579E+09 | 0.227286E+09 | 0.277293E+09 | 0.111746E+10 | 0.278994E+09 |
April | 0.620773E+09 | 0.312780E+09 | 0.307993E+09 | 0.143329E+10 | 0.203724E+09 |
May | 0.603959E+09 | 0.253034E+09 | 0.350925E+09 | 0.141208E+10 | 0.198753E+09 |
June | 0.579244E+09 | 0.251435E+09 | 0.327809E+09 | 0.143492E+10 | 0.133510E+09 |
July | 0.678769E+09 | 0.337667E+09 | 0.341102E+09 | 0.170961E+10 | 0.112308E+09 |
August | 0.672619E+09 | 0.358711E+09 | 0.313909E+09 | 0.169803E+10 | 0.112857E+09 |
September | 0.473200E+09 | 0.217558E+09 | 0.255641E+09 | 0.124624E+10 | 0.124552E+09 |
October | 0.431465E+09 | 0.221633E+09 | 0.209832E+09 | 0.119550E+10 | 0.158152E+09 |
November | 0.377370E+09 | 0.190033E+09 | 0.187338E+09 | 0.917894E+09 | 0.235155E+09 |
December | 0.372493E+09 | 0.205652E+09 | 0.166841E+09 | 0.904625E+09 | 0.279132E+09 |
Annual Sum or Average | 0.607077E+10 | 0.294972E+10 | 0.312104E+10 | 0.148397E+11 | 0.235241E+10 |
Minimum of Months | 0.370444E+09 | 0.169285E+09 | 0.166841E+09 | 0.841570E+09 | 0.112308E+09 |
Maximum of Months | 0.678769E+09 | 0.358711E+09 | 0.350925E+09 | 0.170961E+10 | 0.285213E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259714E+09 | 0.191696E+09 | 68017836.83 | 0.551183E+09 | 76028222.74 |
February | 0.181363E+09 | 0.111773E+09 | 69590245.24 | 0.394638E+09 | 61561005.30 |
March | 0.155750E+09 | 73082247.84 | 82668012.91 | 0.364227E+09 | 75301729.07 |
April | 0.121862E+09 | 41839190.35 | 80022368.62 | 0.331262E+09 | 55293661.40 |
May | 91322771.85 | 7856057.63 | 83466714.22 | 0.252372E+09 | 54345007.71 |
June | 78548484.78 | 2651356.84 | 75897127.94 | 0.235851E+09 | 36277317.23 |
July | 84300374.06 | 5832822.22 | 78467551.84 | 0.273894E+09 | 30118632.89 |
August | 0.105004E+09 | 27222272.24 | 77781517.74 | 0.337029E+09 | 30023075.23 |
September | 0.141771E+09 | 66308265.72 | 75462790.44 | 0.395584E+09 | 33259794.41 |
October | 0.199245E+09 | 0.132603E+09 | 66641376.49 | 0.501306E+09 | 42152858.06 |
November | 0.240458E+09 | 0.170934E+09 | 69524362.08 | 0.520257E+09 | 62649240.12 |
December | 0.279251E+09 | 0.214096E+09 | 65154661.93 | 0.586142E+09 | 74381825.46 |
Annual Sum or Average | 0.193859E+10 | 0.104589E+10 | 0.892695E+09 | 0.474375E+10 | 0.631392E+09 |
Minimum of Months | 78548484.78 | 2651356.84 | 65154661.93 | 0.235851E+09 | 30023075.23 |
Maximum of Months | 0.279251E+09 | 0.214096E+09 | 83466714.22 | 0.586142E+09 | 76028222.74 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48976954.75 | 0.00 | 48976954.75 | 44268327.28 | 0.171487E+09 |
February | 55529511.39 | 0.00 | 55529511.39 | 49839755.74 | 0.137940E+09 |
March | 75344225.57 | 188.80 | 75344036.77 | 78484390.40 | 0.154229E+09 |
April | 84178539.01 | 411533.21 | 83767005.80 | 0.102002E+09 | 0.116657E+09 |
May | 0.103491E+09 | 3990172.17 | 99501065.49 | 0.135366E+09 | 0.105382E+09 |
June | 0.105250E+09 | 8202531.44 | 97047766.30 | 0.158082E+09 | 79130936.68 |
July | 0.103118E+09 | 6657869.69 | 96460584.57 | 0.166525E+09 | 72694973.99 |
August | 86957542.11 | 1266679.14 | 85690862.97 | 0.133217E+09 | 77181137.66 |
September | 71581370.76 | 5168.82 | 71576201.94 | 0.100363E+09 | 91191212.85 |
October | 58674417.61 | 0.00 | 58674417.61 | 86867648.77 | 0.106458E+09 |
November | 51411716.75 | 0.00 | 51411716.75 | 49374912.01 | 0.149998E+09 |
December | 45593382.25 | 0.00 | 45593382.25 | 39326049.62 | 0.172833E+09 |
Annual Sum or Average | 0.890108E+09 | 20534143.27 | 0.869574E+09 | 0.114372E+10 | 0.143518E+10 |
Minimum of Months | 45593382.25 | 0.00 | 45593382.25 | 39326049.62 | 72694973.99 |
Maximum of Months | 0.105250E+09 | 8202531.44 | 99501065.49 | 0.166525E+09 | 0.172833E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43819866.99 | 0.00 | 43819866.99 | 39607040.15 | 0.153416E+09 |
February | 49682464.24 | 0.00 | 49682464.24 | 44591818.30 | 0.123415E+09 |
March | 67410764.09 | 168.92 | 67410595.18 | 70220281.47 | 0.137989E+09 |
April | 75314857.80 | 368200.32 | 74946657.48 | 91261911.62 | 0.104373E+09 |
May | 92594002.46 | 3570022.16 | 89023980.30 | 0.121112E+09 | 94285818.20 |
June | 94167840.17 | 7338835.96 | 86829004.22 | 0.141436E+09 | 70798748.87 |
July | 92260471.74 | 5956821.23 | 86303650.50 | 0.148991E+09 | 65040468.66 |
August | 77801242.41 | 1133302.63 | 76667939.78 | 0.119190E+09 | 69054256.31 |
September | 64044123.64 | 4624.57 | 64039499.08 | 89795095.78 | 81589123.66 |
October | 52496223.75 | 0.00 | 52496223.75 | 77720814.49 | 95248108.02 |
November | 45998257.77 | 0.00 | 45998257.77 | 44175920.86 | 0.134202E+09 |
December | 40792571.85 | 0.00 | 40792571.85 | 35185165.60 | 0.154613E+09 |
Annual Sum or Average | 0.796383E+09 | 18371975.78 | 0.778011E+09 | 0.102329E+10 | 0.128403E+10 |
Minimum of Months | 40792571.85 | 0.00 | 40792571.85 | 35185165.60 | 65040468.66 |
Maximum of Months | 94167840.17 | 7338835.96 | 89023980.30 | 0.148991E+09 | 0.154613E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.969591E+09 | 0.715660E+09 | 0.253931E+09 | 0.171462E+10 | 0.462899E+09 |
February | 0.677083E+09 | 0.417282E+09 | 0.259801E+09 | 0.116676E+10 | 0.381516E+09 |
March | 0.581462E+09 | 0.272838E+09 | 0.308624E+09 | 0.101767E+10 | 0.439424E+09 |
April | 0.454946E+09 | 0.156198E+09 | 0.298747E+09 | 0.863729E+09 | 0.353231E+09 |
May | 0.340935E+09 | 29329004.12 | 0.311606E+09 | 0.539544E+09 | 0.334300E+09 |
June | 0.293245E+09 | 9898305.15 | 0.283347E+09 | 0.456329E+09 | 0.252616E+09 |
July | 0.314718E+09 | 21775663.46 | 0.292943E+09 | 0.560635E+09 | 0.228444E+09 |
August | 0.392010E+09 | 0.101629E+09 | 0.290382E+09 | 0.803422E+09 | 0.237006E+09 |
September | 0.529274E+09 | 0.247549E+09 | 0.281725E+09 | 0.106172E+10 | 0.267761E+09 |
October | 0.743839E+09 | 0.495047E+09 | 0.248792E+09 | 0.143777E+10 | 0.297495E+09 |
November | 0.897702E+09 | 0.638147E+09 | 0.259555E+09 | 0.159314E+10 | 0.406620E+09 |
December | 0.104253E+10 | 0.799284E+09 | 0.243242E+09 | 0.184178E+10 | 0.461919E+09 |
Annual Sum or Average | 0.723733E+10 | 0.390464E+10 | 0.333269E+10 | 0.130571E+11 | 0.412323E+10 |
Minimum of Months | 0.293245E+09 | 9898305.15 | 0.243242E+09 | 0.456329E+09 | 0.228444E+09 |
Maximum of Months | 0.104253E+10 | 0.799284E+09 | 0.311606E+09 | 0.184178E+10 | 0.462899E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 866.25 | 224.55 | 490.43 | 361.99 | 128.44 | 0.00 | 0.00 |
February | 661.49 | 197.71 | 379.17 | 233.68 | 145.49 | 0.00 | 0.00 |
March | 525.23 | 201.89 | 294.11 | 138.00 | 156.10 | 0.00 | 0.00 |
April | 462.78 | 166.31 | 237.78 | 81.64 | 156.14 | 0.00 | 0.00 |
May | 291.82 | 145.79 | 172.45 | 14.83 | 157.61 | 0.00 | 0.00 |
June | 257.21 | 111.15 | 153.27 | 5.17 | 148.09 | 0.00 | 0.00 |
July | 296.88 | 99.72 | 159.19 | 11.01 | 148.17 | 0.00 | 0.00 |
August | 414.94 | 107.31 | 198.28 | 51.40 | 146.88 | 0.00 | 0.00 |
September | 562.31 | 127.02 | 276.63 | 129.39 | 147.25 | 0.00 | 0.00 |
October | 732.84 | 140.26 | 376.24 | 250.40 | 125.84 | 0.00 | 0.00 |
November | 835.42 | 202.43 | 469.20 | 333.54 | 135.66 | 0.00 | 0.00 |
December | 931.54 | 225.29 | 527.32 | 404.29 | 123.03 | 0.00 | 0.00 |
Annual Sum or Average | 569.58 | 162.28 | 310.91 | 167.74 | 143.17 | 0.00 | 0.00 |
Minimum of Months | 257.21 | 99.72 | 153.27 | 5.17 | 123.03 | 0.00 | 0.00 |
Maximum of Months | 931.54 | 225.29 | 527.32 | 404.29 | 157.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2455.55 | 601.67 | 1381.01 | 1019.33 | 361.68 | 0.00 | 0.00 |
February | 1879.13 | 530.95 | 1067.71 | 658.03 | 409.69 | 0.00 | 0.00 |
March | 1494.76 | 547.12 | 828.19 | 388.61 | 439.58 | 0.00 | 0.00 |
April | 1335.76 | 430.66 | 669.59 | 229.89 | 439.69 | 0.00 | 0.00 |
May | 848.03 | 380.10 | 485.60 | 41.77 | 443.82 | 0.00 | 0.00 |
June | 761.27 | 274.70 | 431.59 | 14.57 | 417.03 | 0.00 | 0.00 |
July | 889.64 | 230.33 | 448.26 | 31.02 | 417.24 | 0.00 | 0.00 |
August | 1225.86 | 245.75 | 558.35 | 144.75 | 413.59 | 0.00 | 0.00 |
September | 1626.98 | 304.46 | 778.98 | 364.34 | 414.64 | 0.00 | 0.00 |
October | 2095.95 | 346.93 | 1059.47 | 705.11 | 354.36 | 0.00 | 0.00 |
November | 2373.80 | 531.92 | 1321.24 | 939.23 | 382.01 | 0.00 | 0.00 |
December | 2638.44 | 601.51 | 1484.90 | 1138.44 | 346.45 | 0.00 | 0.00 |
Annual Sum or Average | 1634.64 | 418.28 | 875.50 | 472.35 | 403.15 | 0.00 | 0.00 |
Minimum of Months | 761.27 | 230.33 | 431.59 | 14.57 | 346.45 | 0.00 | 0.00 |
Maximum of Months | 2638.44 | 601.67 | 1484.90 | 1138.44 | 443.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3214.54 | 837.47 | 1794.01 | 1324.17 | 469.84 | 0.00 | 0.00 |
February | 2453.20 | 750.66 | 1387.02 | 854.81 | 532.21 | 0.00 | 0.00 |
March | 1946.53 | 776.29 | 1075.86 | 504.83 | 571.04 | 0.00 | 0.00 |
April | 1733.21 | 622.44 | 869.83 | 298.64 | 571.19 | 0.00 | 0.00 |
May | 1084.87 | 560.65 | 630.82 | 54.27 | 576.55 | 0.00 | 0.00 |
June | 966.52 | 418.69 | 560.66 | 18.93 | 541.74 | 0.00 | 0.00 |
July | 1133.77 | 357.68 | 582.31 | 40.29 | 542.02 | 0.00 | 0.00 |
August | 1581.42 | 374.26 | 725.32 | 188.04 | 537.28 | 0.00 | 0.00 |
September | 2115.31 | 451.03 | 1011.94 | 473.30 | 538.64 | 0.00 | 0.00 |
October | 2735.46 | 501.85 | 1376.31 | 915.98 | 460.33 | 0.00 | 0.00 |
November | 3104.59 | 747.55 | 1716.37 | 1220.11 | 496.26 | 0.00 | 0.00 |
December | 3455.95 | 835.95 | 1928.96 | 1478.90 | 450.06 | 0.00 | 0.00 |
Annual Sum or Average | 2126.05 | 602.13 | 1137.32 | 613.60 | 523.72 | 0.00 | 0.00 |
Minimum of Months | 966.52 | 357.68 | 560.66 | 18.93 | 450.06 | 0.00 | 0.00 |
Maximum of Months | 3455.95 | 837.47 | 1928.96 | 1478.90 | 576.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 281.68 | 122.02 | 165.45 | 105.74 | 59.71 | 0.00 | 0.00 |
February | 260.39 | 108.43 | 157.85 | 84.62 | 73.23 | 0.00 | 0.00 |
March | 254.76 | 112.22 | 153.23 | 69.60 | 83.63 | 0.00 | 0.00 |
April | 320.79 | 87.73 | 178.12 | 84.68 | 93.44 | 0.00 | 0.00 |
May | 278.90 | 77.81 | 162.85 | 62.72 | 100.14 | 0.00 | 0.00 |
June | 296.58 | 55.95 | 166.79 | 69.63 | 97.16 | 0.00 | 0.00 |
July | 331.00 | 46.78 | 175.96 | 79.85 | 96.12 | 0.00 | 0.00 |
August | 339.89 | 49.01 | 174.84 | 84.03 | 90.81 | 0.00 | 0.00 |
September | 326.10 | 60.10 | 170.88 | 88.07 | 82.81 | 0.00 | 0.00 |
October | 313.46 | 67.99 | 163.22 | 98.25 | 64.97 | 0.00 | 0.00 |
November | 297.31 | 107.50 | 172.21 | 107.35 | 64.85 | 0.00 | 0.00 |
December | 297.34 | 120.89 | 173.70 | 116.71 | 56.99 | 0.00 | 0.00 |
Annual Sum or Average | 300.06 | 84.58 | 167.96 | 87.63 | 80.33 | 0.00 | 0.00 |
Minimum of Months | 254.76 | 46.78 | 153.23 | 62.72 | 56.99 | 0.00 | 0.00 |
Maximum of Months | 339.89 | 122.02 | 178.12 | 116.71 | 100.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 129.68 | 125.35 | 82.93 | 34.17 | 48.75 | 0.00 | 0.00 |
February | 150.59 | 109.70 | 101.00 | 38.42 | 62.59 | 0.00 | 0.00 |
March | 177.82 | 112.73 | 117.29 | 42.31 | 74.98 | 0.00 | 0.00 |
April | 261.94 | 88.20 | 156.75 | 68.66 | 88.08 | 0.00 | 0.00 |
May | 262.20 | 77.92 | 159.27 | 60.96 | 98.31 | 0.00 | 0.00 |
June | 292.10 | 59.26 | 168.55 | 71.11 | 97.44 | 0.00 | 0.00 |
July | 317.61 | 52.33 | 174.89 | 79.63 | 95.26 | 0.00 | 0.00 |
August | 293.95 | 54.40 | 161.27 | 74.24 | 87.03 | 0.00 | 0.00 |
September | 244.85 | 63.43 | 137.99 | 62.49 | 75.50 | 0.00 | 0.00 |
October | 195.34 | 71.93 | 106.13 | 48.74 | 57.39 | 0.00 | 0.00 |
November | 151.66 | 109.90 | 95.10 | 41.41 | 53.69 | 0.00 | 0.00 |
December | 131.14 | 124.71 | 82.88 | 36.78 | 46.10 | 0.00 | 0.00 |
Annual Sum or Average | 217.74 | 87.39 | 128.78 | 54.98 | 73.80 | 0.00 | 0.00 |
Minimum of Months | 129.68 | 52.33 | 82.88 | 34.17 | 46.10 | 0.00 | 0.00 |
Maximum of Months | 317.61 | 125.35 | 174.89 | 79.63 | 98.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.46 | 48.72 | 77.56 | 57.25 | 20.31 | 0.00 | 0.00 |
February | 96.93 | 45.04 | 59.96 | 36.95 | 23.01 | 0.00 | 0.00 |
March | 75.04 | 46.05 | 46.51 | 21.82 | 24.69 | 0.00 | 0.00 |
April | 65.71 | 38.36 | 37.60 | 12.91 | 24.69 | 0.00 | 0.00 |
May | 37.34 | 34.83 | 27.27 | 2.35 | 24.93 | 0.00 | 0.00 |
June | 32.27 | 27.73 | 24.24 | 0.82 | 23.42 | 0.00 | 0.00 |
July | 39.71 | 24.49 | 25.17 | 1.74 | 23.43 | 0.00 | 0.00 |
August | 59.23 | 25.63 | 31.36 | 8.13 | 23.23 | 0.00 | 0.00 |
September | 82.78 | 30.00 | 43.75 | 20.46 | 23.29 | 0.00 | 0.00 |
October | 109.70 | 32.04 | 59.50 | 39.60 | 19.90 | 0.00 | 0.00 |
November | 125.47 | 44.23 | 74.20 | 52.75 | 21.45 | 0.00 | 0.00 |
December | 140.77 | 48.35 | 83.39 | 63.93 | 19.46 | 0.00 | 0.00 |
Annual Sum or Average | 82.91 | 37.08 | 49.17 | 26.53 | 22.64 | 0.00 | 0.00 |
Minimum of Months | 32.27 | 24.49 | 24.24 | 0.82 | 19.46 | 0.00 | 0.00 |
Maximum of Months | 140.77 | 48.72 | 83.39 | 63.93 | 24.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.75 | 35.69 | 11.55 | 0.00 | 11.55 | 0.00 | 0.00 |
February | 15.50 | 31.17 | 14.50 | 0.00 | 14.50 | 0.00 | 0.00 |
March | 21.04 | 32.13 | 17.77 | 0.00 | 17.77 | 0.00 | 0.00 |
April | 28.57 | 23.67 | 20.52 | 0.10 | 20.42 | 0.00 | 0.00 |
May | 35.91 | 20.73 | 24.41 | 0.94 | 23.47 | 0.00 | 0.00 |
June | 42.79 | 15.36 | 25.65 | 2.00 | 23.65 | 0.00 | 0.00 |
July | 43.63 | 13.19 | 24.32 | 1.57 | 22.75 | 0.00 | 0.00 |
August | 35.72 | 13.62 | 20.51 | 0.30 | 20.21 | 0.00 | 0.00 |
September | 28.33 | 16.75 | 17.45 | 0.00 | 17.45 | 0.00 | 0.00 |
October | 23.98 | 19.35 | 13.84 | 0.00 | 13.84 | 0.00 | 0.00 |
November | 14.84 | 30.87 | 12.53 | 0.00 | 12.53 | 0.00 | 0.00 |
December | 11.77 | 35.40 | 10.75 | 0.00 | 10.75 | 0.00 | 0.00 |
Annual Sum or Average | 26.30 | 23.96 | 17.83 | 0.41 | 17.42 | 0.00 | 0.00 |
Minimum of Months | 11.77 | 13.19 | 10.75 | 0.00 | 10.75 | 0.00 | 0.00 |
Maximum of Months | 43.63 | 35.69 | 25.65 | 2.00 | 23.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.85 | 120.04 | 169.00 | 109.78 | 59.22 | 0.00 | 0.00 |
February | 246.85 | 105.94 | 151.54 | 81.19 | 70.34 | 0.00 | 0.00 |
March | 249.97 | 108.89 | 152.35 | 69.72 | 82.63 | 0.00 | 0.00 |
April | 297.32 | 84.55 | 166.77 | 76.48 | 90.29 | 0.00 | 0.00 |
May | 247.63 | 75.52 | 146.85 | 50.17 | 96.68 | 0.00 | 0.00 |
June | 251.38 | 55.14 | 142.05 | 49.53 | 92.52 | 0.00 | 0.00 |
July | 298.93 | 46.42 | 158.19 | 65.22 | 92.98 | 0.00 | 0.00 |
August | 321.54 | 47.74 | 164.78 | 77.13 | 87.64 | 0.00 | 0.00 |
September | 279.76 | 58.79 | 145.98 | 67.55 | 78.43 | 0.00 | 0.00 |
October | 296.24 | 66.13 | 154.94 | 90.89 | 64.05 | 0.00 | 0.00 |
November | 282.96 | 105.56 | 165.57 | 102.61 | 62.96 | 0.00 | 0.00 |
December | 296.22 | 119.22 | 173.80 | 118.33 | 55.47 | 0.00 | 0.00 |
Annual Sum or Average | 279.93 | 82.71 | 157.73 | 79.94 | 77.79 | 0.00 | 0.00 |
Minimum of Months | 246.85 | 46.42 | 142.05 | 49.53 | 55.47 | 0.00 | 0.00 |
Maximum of Months | 321.54 | 120.04 | 173.80 | 118.33 | 96.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.94 | 119.10 | 86.47 | 38.21 | 48.27 | 0.00 | 0.00 |
February | 135.55 | 105.11 | 94.69 | 34.99 | 59.70 | 0.00 | 0.00 |
March | 172.27 | 108.20 | 116.41 | 42.43 | 73.98 | 0.00 | 0.00 |
April | 239.27 | 84.34 | 145.40 | 60.47 | 84.93 | 0.00 | 0.00 |
May | 232.46 | 75.65 | 143.26 | 48.42 | 94.85 | 0.00 | 0.00 |
June | 248.20 | 56.71 | 143.81 | 51.00 | 92.80 | 0.00 | 0.00 |
July | 286.11 | 49.80 | 157.12 | 65.00 | 92.12 | 0.00 | 0.00 |
August | 276.02 | 51.72 | 151.21 | 67.34 | 83.87 | 0.00 | 0.00 |
September | 199.21 | 60.93 | 113.09 | 41.97 | 71.12 | 0.00 | 0.00 |
October | 177.06 | 68.46 | 97.85 | 41.38 | 56.47 | 0.00 | 0.00 |
November | 135.42 | 105.09 | 88.46 | 36.66 | 51.80 | 0.00 | 0.00 |
December | 125.86 | 118.54 | 82.98 | 38.39 | 44.59 | 0.00 | 0.00 |
Annual Sum or Average | 196.93 | 83.54 | 118.55 | 47.28 | 71.26 | 0.00 | 0.00 |
Minimum of Months | 125.86 | 49.80 | 82.98 | 34.99 | 44.59 | 0.00 | 0.00 |
Maximum of Months | 286.11 | 119.10 | 157.12 | 67.34 | 94.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.31 | 151.82 | 193.07 | 124.04 | 69.04 | 0.00 | 0.00 |
February | 260.45 | 136.71 | 161.34 | 80.07 | 81.27 | 0.00 | 0.00 |
March | 227.40 | 141.56 | 139.28 | 47.29 | 91.99 | 0.00 | 0.00 |
April | 224.16 | 110.22 | 125.93 | 28.19 | 97.73 | 0.00 | 0.00 |
May | 178.40 | 96.99 | 111.97 | 7.12 | 104.85 | 0.00 | 0.00 |
June | 182.92 | 71.20 | 108.09 | 6.10 | 101.99 | 0.00 | 0.00 |
July | 200.05 | 62.18 | 107.24 | 7.18 | 100.06 | 0.00 | 0.00 |
August | 224.19 | 66.24 | 112.38 | 18.26 | 94.12 | 0.00 | 0.00 |
September | 258.51 | 80.77 | 132.59 | 44.34 | 88.25 | 0.00 | 0.00 |
October | 305.38 | 90.96 | 158.90 | 85.80 | 73.10 | 0.00 | 0.00 |
November | 318.44 | 136.25 | 187.92 | 114.29 | 73.63 | 0.00 | 0.00 |
December | 343.19 | 151.94 | 203.98 | 138.53 | 65.46 | 0.00 | 0.00 |
Annual Sum or Average | 253.98 | 107.93 | 145.16 | 58.37 | 86.80 | 0.00 | 0.00 |
Minimum of Months | 178.40 | 62.18 | 107.24 | 6.10 | 65.46 | 0.00 | 0.00 |
Maximum of Months | 343.19 | 151.94 | 203.98 | 138.53 | 104.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 280.97 | 119.73 | 165.45 | 105.74 | 59.71 | 0.00 | 0.00 |
February | 259.35 | 106.32 | 157.85 | 84.62 | 73.23 | 0.00 | 0.00 |
March | 253.13 | 110.58 | 153.23 | 69.60 | 83.63 | 0.00 | 0.00 |
April | 318.00 | 86.68 | 178.12 | 84.68 | 93.44 | 0.00 | 0.00 |
May | 276.16 | 76.84 | 162.85 | 62.72 | 100.14 | 0.00 | 0.00 |
June | 293.63 | 55.29 | 166.79 | 69.63 | 97.16 | 0.00 | 0.00 |
July | 328.13 | 46.11 | 175.96 | 79.85 | 96.12 | 0.00 | 0.00 |
August | 337.15 | 48.17 | 174.84 | 84.03 | 90.81 | 0.00 | 0.00 |
September | 323.73 | 59.05 | 170.88 | 88.07 | 82.81 | 0.00 | 0.00 |
October | 311.99 | 66.39 | 163.22 | 98.25 | 64.97 | 0.00 | 0.00 |
November | 296.26 | 105.33 | 172.21 | 107.35 | 64.85 | 0.00 | 0.00 |
December | 296.82 | 118.35 | 173.70 | 116.71 | 56.99 | 0.00 | 0.00 |
Annual Sum or Average | 298.15 | 83.12 | 167.96 | 87.63 | 80.33 | 0.00 | 0.00 |
Minimum of Months | 253.13 | 46.11 | 153.23 | 62.72 | 56.99 | 0.00 | 0.00 |
Maximum of Months | 337.15 | 119.73 | 178.12 | 116.71 | 100.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.01 | 122.17 | 82.93 | 34.17 | 48.75 | 0.00 | 0.00 |
February | 150.55 | 107.14 | 101.00 | 38.42 | 62.59 | 0.00 | 0.00 |
March | 176.65 | 111.01 | 117.29 | 42.31 | 74.98 | 0.00 | 0.00 |
April | 258.96 | 87.80 | 156.75 | 68.66 | 88.08 | 0.00 | 0.00 |
May | 258.93 | 77.66 | 159.27 | 60.96 | 98.31 | 0.00 | 0.00 |
June | 288.00 | 60.12 | 168.55 | 71.11 | 97.44 | 0.00 | 0.00 |
July | 313.52 | 53.57 | 174.89 | 79.63 | 95.26 | 0.00 | 0.00 |
August | 290.55 | 55.29 | 161.27 | 74.24 | 87.03 | 0.00 | 0.00 |
September | 242.55 | 63.13 | 137.99 | 62.49 | 75.50 | 0.00 | 0.00 |
October | 194.59 | 70.39 | 106.13 | 48.74 | 57.39 | 0.00 | 0.00 |
November | 151.77 | 107.07 | 95.10 | 41.41 | 53.69 | 0.00 | 0.00 |
December | 131.90 | 121.09 | 82.88 | 36.78 | 46.10 | 0.00 | 0.00 |
Annual Sum or Average | 215.98 | 86.27 | 128.78 | 54.98 | 73.80 | 0.00 | 0.00 |
Minimum of Months | 130.01 | 53.57 | 82.88 | 34.17 | 46.10 | 0.00 | 0.00 |
Maximum of Months | 313.52 | 122.17 | 174.89 | 79.63 | 98.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 251.24 | 62.33 | 142.21 | 104.97 | 37.24 | 0.00 | 0.00 |
February | 190.57 | 55.14 | 109.95 | 67.76 | 42.19 | 0.00 | 0.00 |
March | 150.80 | 57.53 | 85.28 | 40.02 | 45.27 | 0.00 | 0.00 |
April | 134.32 | 44.63 | 68.95 | 23.67 | 45.28 | 0.00 | 0.00 |
May | 84.43 | 39.51 | 50.01 | 4.30 | 45.70 | 0.00 | 0.00 |
June | 76.11 | 27.96 | 44.44 | 1.50 | 42.94 | 0.00 | 0.00 |
July | 89.59 | 22.80 | 46.16 | 3.19 | 42.97 | 0.00 | 0.00 |
August | 124.15 | 23.84 | 57.50 | 14.91 | 42.59 | 0.00 | 0.00 |
September | 165.41 | 30.05 | 80.22 | 37.52 | 42.70 | 0.00 | 0.00 |
October | 214.63 | 33.62 | 109.10 | 72.61 | 36.49 | 0.00 | 0.00 |
November | 242.50 | 54.51 | 136.06 | 96.72 | 39.34 | 0.00 | 0.00 |
December | 270.29 | 61.69 | 152.91 | 117.23 | 35.68 | 0.00 | 0.00 |
Annual Sum or Average | 166.10 | 42.74 | 90.15 | 48.64 | 41.52 | 0.00 | 0.00 |
Minimum of Months | 76.11 | 22.80 | 44.44 | 1.50 | 35.68 | 0.00 | 0.00 |
Maximum of Months | 270.29 | 62.33 | 152.91 | 117.23 | 45.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 114.37 | 309.95 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
February | 137.87 | 275.71 | 126.87 | 0.00 | 126.87 | 0.00 | 0.00 |
March | 187.20 | 284.15 | 155.48 | 0.00 | 155.48 | 0.00 | 0.00 |
April | 254.83 | 211.40 | 179.50 | 0.88 | 178.62 | 0.00 | 0.00 |
May | 320.76 | 185.89 | 213.56 | 8.23 | 205.33 | 0.00 | 0.00 |
June | 386.40 | 136.54 | 224.43 | 17.49 | 206.94 | 0.00 | 0.00 |
July | 397.55 | 115.08 | 212.79 | 13.74 | 199.05 | 0.00 | 0.00 |
August | 326.15 | 119.79 | 179.44 | 2.61 | 176.83 | 0.00 | 0.00 |
September | 256.20 | 147.85 | 152.64 | 0.01 | 152.63 | 0.00 | 0.00 |
October | 218.22 | 169.62 | 121.08 | 0.00 | 121.08 | 0.00 | 0.00 |
November | 132.11 | 271.40 | 109.63 | 0.00 | 109.63 | 0.00 | 0.00 |
December | 105.44 | 308.99 | 94.09 | 0.00 | 94.09 | 0.00 | 0.00 |
Annual Sum or Average | 237.00 | 211.05 | 156.00 | 3.60 | 152.40 | 0.00 | 0.00 |
Minimum of Months | 105.44 | 115.08 | 94.09 | 0.00 | 94.09 | 0.00 | 0.00 |
Maximum of Months | 397.55 | 309.95 | 224.43 | 17.49 | 206.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 108.39 | 324.32 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
February | 131.04 | 289.68 | 126.87 | 0.00 | 126.87 | 0.00 | 0.00 |
March | 179.35 | 297.74 | 155.48 | 0.00 | 155.48 | 0.00 | 0.00 |
April | 246.26 | 221.76 | 179.50 | 0.88 | 178.62 | 0.00 | 0.00 |
May | 310.83 | 194.73 | 213.56 | 8.23 | 205.33 | 0.00 | 0.00 |
June | 376.83 | 143.88 | 224.43 | 17.49 | 206.94 | 0.00 | 0.00 |
July | 388.69 | 121.74 | 212.79 | 13.74 | 199.05 | 0.00 | 0.00 |
August | 318.05 | 126.99 | 179.44 | 2.61 | 176.83 | 0.00 | 0.00 |
September | 249.15 | 156.74 | 152.64 | 0.01 | 152.63 | 0.00 | 0.00 |
October | 211.72 | 179.22 | 121.08 | 0.00 | 121.08 | 0.00 | 0.00 |
November | 126.10 | 284.28 | 109.63 | 0.00 | 109.63 | 0.00 | 0.00 |
December | 99.76 | 322.87 | 94.09 | 0.00 | 94.09 | 0.00 | 0.00 |
Annual Sum or Average | 229.42 | 221.66 | 156.00 | 3.60 | 152.40 | 0.00 | 0.00 |
Minimum of Months | 99.76 | 121.74 | 94.09 | 0.00 | 94.09 | 0.00 | 0.00 |
Maximum of Months | 388.69 | 324.32 | 224.43 | 17.49 | 206.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 593.68 | 163.24 | 255.46 | 147.98 | 107.49 | 0.00 | 0.00 |
February | 556.70 | 145.74 | 246.22 | 116.18 | 130.04 | 0.00 | 0.00 |
March | 607.15 | 159.70 | 268.75 | 112.14 | 156.61 | 0.00 | 0.00 |
April | 749.58 | 120.50 | 312.15 | 136.94 | 175.22 | 0.00 | 0.00 |
May | 702.82 | 113.82 | 290.10 | 98.58 | 191.52 | 0.00 | 0.00 |
June | 737.99 | 78.98 | 285.84 | 100.53 | 185.31 | 0.00 | 0.00 |
July | 836.88 | 64.27 | 315.30 | 130.21 | 185.09 | 0.00 | 0.00 |
August | 844.74 | 64.55 | 315.97 | 144.46 | 171.50 | 0.00 | 0.00 |
September | 705.47 | 73.63 | 259.06 | 109.52 | 149.55 | 0.00 | 0.00 |
October | 699.35 | 90.50 | 252.78 | 132.26 | 120.52 | 0.00 | 0.00 |
November | 600.52 | 139.06 | 254.02 | 139.26 | 114.76 | 0.00 | 0.00 |
December | 596.19 | 159.74 | 256.77 | 156.72 | 100.06 | 0.00 | 0.00 |
Annual Sum or Average | 686.85 | 114.35 | 276.26 | 127.21 | 149.05 | 0.00 | 0.00 |
Minimum of Months | 556.70 | 64.27 | 246.22 | 98.58 | 100.06 | 0.00 | 0.00 |
Maximum of Months | 844.74 | 163.24 | 315.97 | 156.72 | 191.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 663.51 | 286.16 | 396.65 | 267.20 | 129.45 | 0.00 | 0.00 |
February | 517.21 | 261.62 | 323.37 | 172.49 | 150.88 | 0.00 | 0.00 |
March | 433.95 | 271.64 | 270.39 | 101.87 | 168.53 | 0.00 | 0.00 |
April | 407.33 | 221.09 | 237.05 | 60.56 | 176.49 | 0.00 | 0.00 |
May | 294.40 | 196.56 | 200.50 | 13.77 | 186.73 | 0.00 | 0.00 |
June | 287.75 | 151.44 | 190.07 | 9.81 | 180.26 | 0.00 | 0.00 |
July | 324.24 | 133.84 | 190.45 | 12.84 | 177.61 | 0.00 | 0.00 |
August | 393.29 | 142.17 | 207.87 | 38.84 | 169.03 | 0.00 | 0.00 |
September | 482.88 | 169.86 | 256.52 | 95.51 | 161.01 | 0.00 | 0.00 |
October | 595.98 | 184.11 | 319.22 | 184.83 | 134.39 | 0.00 | 0.00 |
November | 644.59 | 260.38 | 383.92 | 246.20 | 137.72 | 0.00 | 0.00 |
December | 706.36 | 285.62 | 421.49 | 298.42 | 123.07 | 0.00 | 0.00 |
Annual Sum or Average | 479.24 | 213.46 | 282.97 | 125.05 | 157.92 | 0.00 | 0.00 |
Minimum of Months | 287.75 | 133.84 | 190.07 | 9.81 | 123.07 | 0.00 | 0.00 |
Maximum of Months | 706.36 | 286.16 | 421.49 | 298.42 | 186.73 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232016E+10 | 0.601442E+09 | 0.131356E+10 | 0.969549E+09 | 0.344013E+09 | 0.00 | 0.00 |
February | 0.160027E+10 | 0.478301E+09 | 0.917283E+09 | 0.565317E+09 | 0.351966E+09 | 0.00 | 0.00 |
March | 0.140677E+10 | 0.540754E+09 | 0.787739E+09 | 0.369630E+09 | 0.418109E+09 | 0.00 | 0.00 |
April | 0.119953E+10 | 0.431069E+09 | 0.616338E+09 | 0.211611E+09 | 0.404727E+09 | 0.00 | 0.00 |
May | 0.781621E+09 | 0.390471E+09 | 0.461881E+09 | 39733814.90 | 0.422147E+09 | 0.00 | 0.00 |
June | 0.666691E+09 | 0.288092E+09 | 0.397272E+09 | 13409845.86 | 0.383862E+09 | 0.00 | 0.00 |
July | 0.795166E+09 | 0.267087E+09 | 0.426363E+09 | 29500837.39 | 0.396862E+09 | 0.00 | 0.00 |
August | 0.111136E+10 | 0.287429E+09 | 0.531075E+09 | 0.137683E+09 | 0.393392E+09 | 0.00 | 0.00 |
September | 0.145750E+10 | 0.329242E+09 | 0.717036E+09 | 0.335369E+09 | 0.381666E+09 | 0.00 | 0.00 |
October | 0.196285E+10 | 0.375677E+09 | 0.100772E+10 | 0.670671E+09 | 0.337051E+09 | 0.00 | 0.00 |
November | 0.216542E+10 | 0.524711E+09 | 0.121617E+10 | 0.864537E+09 | 0.351633E+09 | 0.00 | 0.00 |
December | 0.249504E+10 | 0.603413E+09 | 0.141237E+10 | 0.108284E+10 | 0.329532E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179624E+11 | 0.511769E+10 | 0.980481E+10 | 0.528985E+10 | 0.451496E+10 | 0.00 | 0.00 |
Minimum of Months | 0.666691E+09 | 0.267087E+09 | 0.397272E+09 | 13409845.86 | 0.329532E+09 | 0.00 | 0.00 |
Maximum of Months | 0.249504E+10 | 0.603413E+09 | 0.141237E+10 | 0.108284E+10 | 0.422147E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.657696E+10 | 0.161150E+10 | 0.369890E+10 | 0.273019E+10 | 0.968719E+09 | 0.00 | 0.00 |
February | 0.454599E+10 | 0.128447E+10 | 0.258301E+10 | 0.159190E+10 | 0.991113E+09 | 0.00 | 0.00 |
March | 0.400356E+10 | 0.146541E+10 | 0.221822E+10 | 0.104085E+10 | 0.117737E+10 | 0.00 | 0.00 |
April | 0.346230E+10 | 0.111626E+10 | 0.173557E+10 | 0.595883E+09 | 0.113968E+10 | 0.00 | 0.00 |
May | 0.227136E+10 | 0.101805E+10 | 0.130063E+10 | 0.111888E+09 | 0.118874E+10 | 0.00 | 0.00 |
June | 0.197322E+10 | 0.712017E+09 | 0.111869E+10 | 37761241.79 | 0.108093E+10 | 0.00 | 0.00 |
July | 0.238282E+10 | 0.616903E+09 | 0.120061E+10 | 83072412.98 | 0.111754E+10 | 0.00 | 0.00 |
August | 0.328334E+10 | 0.658213E+09 | 0.149547E+10 | 0.387706E+09 | 0.110777E+10 | 0.00 | 0.00 |
September | 0.421712E+10 | 0.789168E+09 | 0.201912E+10 | 0.944378E+09 | 0.107475E+10 | 0.00 | 0.00 |
October | 0.561379E+10 | 0.929212E+09 | 0.283768E+10 | 0.188857E+10 | 0.949113E+09 | 0.00 | 0.00 |
November | 0.615290E+10 | 0.137874E+10 | 0.342465E+10 | 0.243448E+10 | 0.990175E+09 | 0.00 | 0.00 |
December | 0.706681E+10 | 0.161108E+10 | 0.397715E+10 | 0.304921E+10 | 0.927941E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.515501E+11 | 0.131910E+11 | 0.276097E+11 | 0.148959E+11 | 0.127138E+11 | 0.00 | 0.00 |
Minimum of Months | 0.197322E+10 | 0.616903E+09 | 0.111869E+10 | 37761241.79 | 0.927941E+09 | 0.00 | 0.00 |
Maximum of Months | 0.706681E+10 | 0.161150E+10 | 0.397715E+10 | 0.304921E+10 | 0.118874E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.860983E+10 | 0.224308E+10 | 0.480509E+10 | 0.354667E+10 | 0.125842E+10 | 0.00 | 0.00 |
February | 0.593479E+10 | 0.181600E+10 | 0.335548E+10 | 0.206796E+10 | 0.128751E+10 | 0.00 | 0.00 |
March | 0.521358E+10 | 0.207921E+10 | 0.288160E+10 | 0.135213E+10 | 0.152947E+10 | 0.00 | 0.00 |
April | 0.449247E+10 | 0.161337E+10 | 0.225460E+10 | 0.774087E+09 | 0.148051E+10 | 0.00 | 0.00 |
May | 0.290571E+10 | 0.150164E+10 | 0.168959E+10 | 0.145349E+09 | 0.154424E+10 | 0.00 | 0.00 |
June | 0.250521E+10 | 0.108526E+10 | 0.145324E+10 | 49054002.09 | 0.140419E+10 | 0.00 | 0.00 |
July | 0.303668E+10 | 0.958020E+09 | 0.155966E+10 | 0.107916E+09 | 0.145174E+10 | 0.00 | 0.00 |
August | 0.423567E+10 | 0.100242E+10 | 0.194270E+10 | 0.503652E+09 | 0.143905E+10 | 0.00 | 0.00 |
September | 0.548289E+10 | 0.116907E+10 | 0.262296E+10 | 0.122680E+10 | 0.139616E+10 | 0.00 | 0.00 |
October | 0.732667E+10 | 0.134416E+10 | 0.368631E+10 | 0.245335E+10 | 0.123295E+10 | 0.00 | 0.00 |
November | 0.804710E+10 | 0.193764E+10 | 0.444882E+10 | 0.316253E+10 | 0.128629E+10 | 0.00 | 0.00 |
December | 0.925643E+10 | 0.223902E+10 | 0.516654E+10 | 0.396109E+10 | 0.120545E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.670470E+11 | 0.189889E+11 | 0.358666E+11 | 0.193506E+11 | 0.165160E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250521E+10 | 0.958020E+09 | 0.145324E+10 | 49054002.09 | 0.120545E+10 | 0.00 | 0.00 |
Maximum of Months | 0.925643E+10 | 0.224308E+10 | 0.516654E+10 | 0.396109E+10 | 0.154424E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.754458E+09 | 0.326820E+09 | 0.443148E+09 | 0.283223E+09 | 0.159925E+09 | 0.00 | 0.00 |
February | 0.629935E+09 | 0.262317E+09 | 0.381859E+09 | 0.204707E+09 | 0.177152E+09 | 0.00 | 0.00 |
March | 0.682338E+09 | 0.300570E+09 | 0.410414E+09 | 0.186408E+09 | 0.224005E+09 | 0.00 | 0.00 |
April | 0.831490E+09 | 0.227388E+09 | 0.461683E+09 | 0.219488E+09 | 0.242194E+09 | 0.00 | 0.00 |
May | 0.747007E+09 | 0.208404E+09 | 0.436184E+09 | 0.167979E+09 | 0.268204E+09 | 0.00 | 0.00 |
June | 0.768742E+09 | 0.145015E+09 | 0.432331E+09 | 0.180488E+09 | 0.251842E+09 | 0.00 | 0.00 |
July | 0.886544E+09 | 0.125297E+09 | 0.471298E+09 | 0.213863E+09 | 0.257435E+09 | 0.00 | 0.00 |
August | 0.910352E+09 | 0.131268E+09 | 0.468286E+09 | 0.225068E+09 | 0.243218E+09 | 0.00 | 0.00 |
September | 0.845262E+09 | 0.155782E+09 | 0.442911E+09 | 0.228273E+09 | 0.214638E+09 | 0.00 | 0.00 |
October | 0.839583E+09 | 0.182117E+09 | 0.437169E+09 | 0.263149E+09 | 0.174020E+09 | 0.00 | 0.00 |
November | 0.770633E+09 | 0.278630E+09 | 0.446356E+09 | 0.278258E+09 | 0.168098E+09 | 0.00 | 0.00 |
December | 0.796402E+09 | 0.323800E+09 | 0.465230E+09 | 0.312595E+09 | 0.152635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.946275E+10 | 0.266741E+10 | 0.529687E+10 | 0.276350E+10 | 0.253337E+10 | 0.00 | 0.00 |
Minimum of Months | 0.629935E+09 | 0.125297E+09 | 0.381859E+09 | 0.167979E+09 | 0.152635E+09 | 0.00 | 0.00 |
Maximum of Months | 0.910352E+09 | 0.326820E+09 | 0.471298E+09 | 0.312595E+09 | 0.268204E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.347328E+09 | 0.335747E+09 | 0.222106E+09 | 91526423.86 | 0.130580E+09 | 0.00 | 0.00 |
February | 0.364309E+09 | 0.265394E+09 | 0.244343E+09 | 92934228.36 | 0.151408E+09 | 0.00 | 0.00 |
March | 0.476284E+09 | 0.301933E+09 | 0.314157E+09 | 0.113326E+09 | 0.200830E+09 | 0.00 | 0.00 |
April | 0.678954E+09 | 0.228613E+09 | 0.406290E+09 | 0.177974E+09 | 0.228316E+09 | 0.00 | 0.00 |
May | 0.702277E+09 | 0.208688E+09 | 0.426579E+09 | 0.163274E+09 | 0.263305E+09 | 0.00 | 0.00 |
June | 0.757133E+09 | 0.153607E+09 | 0.436890E+09 | 0.184314E+09 | 0.252576E+09 | 0.00 | 0.00 |
July | 0.850679E+09 | 0.140172E+09 | 0.468421E+09 | 0.213287E+09 | 0.255135E+09 | 0.00 | 0.00 |
August | 0.787321E+09 | 0.145712E+09 | 0.431945E+09 | 0.198846E+09 | 0.233100E+09 | 0.00 | 0.00 |
September | 0.634654E+09 | 0.164414E+09 | 0.357662E+09 | 0.161969E+09 | 0.195693E+09 | 0.00 | 0.00 |
October | 0.523209E+09 | 0.192667E+09 | 0.284255E+09 | 0.130545E+09 | 0.153709E+09 | 0.00 | 0.00 |
November | 0.393113E+09 | 0.284855E+09 | 0.246493E+09 | 0.107324E+09 | 0.139169E+09 | 0.00 | 0.00 |
December | 0.351256E+09 | 0.334014E+09 | 0.221981E+09 | 98499410.79 | 0.123482E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.686652E+10 | 0.275581E+10 | 0.406112E+10 | 0.173382E+10 | 0.232730E+10 | 0.00 | 0.00 |
Minimum of Months | 0.347328E+09 | 0.140172E+09 | 0.221981E+09 | 91526423.86 | 0.123482E+09 | 0.00 | 0.00 |
Maximum of Months | 0.850679E+09 | 0.335747E+09 | 0.468421E+09 | 0.213287E+09 | 0.263305E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.349415E+09 | 0.130488E+09 | 0.207730E+09 | 0.153327E+09 | 54403450.09 | 0.00 | 0.00 |
February | 0.234493E+09 | 0.108963E+09 | 0.145062E+09 | 89400535.50 | 55661126.70 | 0.00 | 0.00 |
March | 0.200989E+09 | 0.123334E+09 | 0.124575E+09 | 58454173.31 | 66121260.59 | 0.00 | 0.00 |
April | 0.170325E+09 | 99440056.03 | 97469863.05 | 33464697.05 | 64005165.99 | 0.00 | 0.00 |
May | 0.100018E+09 | 93282806.76 | 73043691.06 | 6283596.46 | 66760094.59 | 0.00 | 0.00 |
June | 83648187.03 | 71864333.87 | 62826293.36 | 2120663.73 | 60705629.64 | 0.00 | 0.00 |
July | 0.106366E+09 | 65605406.66 | 67426889.86 | 4665329.97 | 62761559.89 | 0.00 | 0.00 |
August | 0.158649E+09 | 68634118.67 | 83986329.37 | 21773487.64 | 62212841.74 | 0.00 | 0.00 |
September | 0.214566E+09 | 77759262.23 | 0.113394E+09 | 53036065.13 | 60358228.73 | 0.00 | 0.00 |
October | 0.293815E+09 | 85825395.34 | 0.159364E+09 | 0.106061E+09 | 53302500.76 | 0.00 | 0.00 |
November | 0.325222E+09 | 0.114639E+09 | 0.192328E+09 | 0.136720E+09 | 55608430.65 | 0.00 | 0.00 |
December | 0.377050E+09 | 0.129512E+09 | 0.223356E+09 | 0.171243E+09 | 52113365.60 | 0.00 | 0.00 |
Annual Sum or Average | 0.261456E+10 | 0.116935E+10 | 0.155056E+10 | 0.836549E+09 | 0.714014E+09 | 0.00 | 0.00 |
Minimum of Months | 83648187.03 | 65605406.66 | 62826293.36 | 2120663.73 | 52113365.60 | 0.00 | 0.00 |
Maximum of Months | 0.377050E+09 | 0.130488E+09 | 0.223356E+09 | 0.171243E+09 | 66760094.59 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 34152692.59 | 95579040.02 | 30942526.57 | 0.00 | 30942526.57 | 0.00 | 0.00 |
February | 37490881.12 | 75409752.81 | 35082282.89 | 0.00 | 35082282.89 | 0.00 | 0.00 |
March | 56363710.98 | 86070266.36 | 47600768.84 | 119.28 | 47600649.57 | 0.00 | 0.00 |
April | 74044650.39 | 61349668.92 | 53182087.23 | 259997.32 | 52922089.91 | 0.00 | 0.00 |
May | 96174004.05 | 55515706.85 | 65383411.19 | 2520900.07 | 62862511.13 | 0.00 | 0.00 |
June | 0.110900E+09 | 39807577.68 | 66494745.35 | 5182172.89 | 61312572.47 | 0.00 | 0.00 |
July | 0.116859E+09 | 35330095.32 | 65147895.11 | 4206290.71 | 60941604.40 | 0.00 | 0.00 |
August | 95660594.62 | 36472179.67 | 54937798.22 | 800259.09 | 54137539.13 | 0.00 | 0.00 |
September | 73425427.50 | 43412532.10 | 45223482.72 | 3265.55 | 45220217.18 | 0.00 | 0.00 |
October | 64231884.10 | 51820098.32 | 37069163.15 | 0.00 | 37069163.15 | 0.00 | 0.00 |
November | 38466230.32 | 80005877.52 | 32480753.85 | 0.00 | 32480753.85 | 0.00 | 0.00 |
December | 31531056.34 | 94824371.05 | 28804862.39 | 0.00 | 28804862.39 | 0.00 | 0.00 |
Annual Sum or Average | 0.829300E+09 | 0.755597E+09 | 0.562350E+09 | 12973004.89 | 0.549377E+09 | 0.00 | 0.00 |
Minimum of Months | 31531056.34 | 35330095.32 | 28804862.39 | 0.00 | 28804862.39 | 0.00 | 0.00 |
Maximum of Months | 0.116859E+09 | 95579040.02 | 66494745.35 | 5182172.89 | 62862511.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.768298E+09 | 0.321527E+09 | 0.452653E+09 | 0.294027E+09 | 0.158626E+09 | 0.00 | 0.00 |
February | 0.597173E+09 | 0.256289E+09 | 0.366598E+09 | 0.196422E+09 | 0.170177E+09 | 0.00 | 0.00 |
March | 0.669524E+09 | 0.291662E+09 | 0.408058E+09 | 0.186733E+09 | 0.221324E+09 | 0.00 | 0.00 |
April | 0.770648E+09 | 0.219145E+09 | 0.432270E+09 | 0.198240E+09 | 0.234030E+09 | 0.00 | 0.00 |
May | 0.663240E+09 | 0.202282E+09 | 0.393324E+09 | 0.134382E+09 | 0.258942E+09 | 0.00 | 0.00 |
June | 0.651583E+09 | 0.142926E+09 | 0.368191E+09 | 0.128378E+09 | 0.239813E+09 | 0.00 | 0.00 |
July | 0.800666E+09 | 0.124325E+09 | 0.423709E+09 | 0.174678E+09 | 0.249031E+09 | 0.00 | 0.00 |
August | 0.861207E+09 | 0.127871E+09 | 0.441337E+09 | 0.206590E+09 | 0.234747E+09 | 0.00 | 0.00 |
September | 0.725141E+09 | 0.152372E+09 | 0.378388E+09 | 0.175095E+09 | 0.203293E+09 | 0.00 | 0.00 |
October | 0.793463E+09 | 0.177115E+09 | 0.414992E+09 | 0.243428E+09 | 0.171565E+09 | 0.00 | 0.00 |
November | 0.733429E+09 | 0.273610E+09 | 0.429157E+09 | 0.265957E+09 | 0.163200E+09 | 0.00 | 0.00 |
December | 0.793403E+09 | 0.319325E+09 | 0.465510E+09 | 0.316929E+09 | 0.148581E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.882778E+10 | 0.260845E+10 | 0.497419E+10 | 0.252086E+10 | 0.245333E+10 | 0.00 | 0.00 |
Minimum of Months | 0.597173E+09 | 0.124325E+09 | 0.366598E+09 | 0.128378E+09 | 0.148581E+09 | 0.00 | 0.00 |
Maximum of Months | 0.861207E+09 | 0.321527E+09 | 0.465510E+09 | 0.316929E+09 | 0.258942E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.350718E+09 | 0.318986E+09 | 0.231612E+09 | 0.102331E+09 | 0.129281E+09 | 0.00 | 0.00 |
February | 0.327926E+09 | 0.254281E+09 | 0.229082E+09 | 84648623.84 | 0.144433E+09 | 0.00 | 0.00 |
March | 0.461411E+09 | 0.289815E+09 | 0.311800E+09 | 0.113651E+09 | 0.198149E+09 | 0.00 | 0.00 |
April | 0.620182E+09 | 0.218603E+09 | 0.376877E+09 | 0.156726E+09 | 0.220151E+09 | 0.00 | 0.00 |
May | 0.622624E+09 | 0.202615E+09 | 0.383720E+09 | 0.129677E+09 | 0.254043E+09 | 0.00 | 0.00 |
June | 0.643324E+09 | 0.147002E+09 | 0.372750E+09 | 0.132203E+09 | 0.240546E+09 | 0.00 | 0.00 |
July | 0.766330E+09 | 0.133394E+09 | 0.420833E+09 | 0.174103E+09 | 0.246730E+09 | 0.00 | 0.00 |
August | 0.739287E+09 | 0.138535E+09 | 0.404997E+09 | 0.180368E+09 | 0.224628E+09 | 0.00 | 0.00 |
September | 0.516365E+09 | 0.157935E+09 | 0.293139E+09 | 0.108791E+09 | 0.184348E+09 | 0.00 | 0.00 |
October | 0.474238E+09 | 0.183376E+09 | 0.262078E+09 | 0.110824E+09 | 0.151254E+09 | 0.00 | 0.00 |
November | 0.351015E+09 | 0.272399E+09 | 0.229294E+09 | 95023132.89 | 0.134271E+09 | 0.00 | 0.00 |
December | 0.337096E+09 | 0.317493E+09 | 0.222261E+09 | 0.102833E+09 | 0.119428E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.621052E+10 | 0.263443E+10 | 0.373844E+10 | 0.149118E+10 | 0.224726E+10 | 0.00 | 0.00 |
Minimum of Months | 0.327926E+09 | 0.133394E+09 | 0.222261E+09 | 84648623.84 | 0.119428E+09 | 0.00 | 0.00 |
Maximum of Months | 0.766330E+09 | 0.318986E+09 | 0.420833E+09 | 0.180368E+09 | 0.254043E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.868630E+09 | 0.406641E+09 | 0.517125E+09 | 0.332216E+09 | 0.184909E+09 | 0.00 | 0.00 |
February | 0.630071E+09 | 0.330735E+09 | 0.390308E+09 | 0.193706E+09 | 0.196602E+09 | 0.00 | 0.00 |
March | 0.609066E+09 | 0.379150E+09 | 0.373040E+09 | 0.126654E+09 | 0.246385E+09 | 0.00 | 0.00 |
April | 0.581024E+09 | 0.285695E+09 | 0.326400E+09 | 73071933.68 | 0.253328E+09 | 0.00 | 0.00 |
May | 0.477823E+09 | 0.259767E+09 | 0.299908E+09 | 19075920.98 | 0.280832E+09 | 0.00 | 0.00 |
June | 0.474122E+09 | 0.184552E+09 | 0.280177E+09 | 15821212.73 | 0.264356E+09 | 0.00 | 0.00 |
July | 0.535803E+09 | 0.166534E+09 | 0.287228E+09 | 19220708.80 | 0.268007E+09 | 0.00 | 0.00 |
August | 0.600458E+09 | 0.177424E+09 | 0.300989E+09 | 48910722.23 | 0.252078E+09 | 0.00 | 0.00 |
September | 0.670067E+09 | 0.209369E+09 | 0.343663E+09 | 0.114921E+09 | 0.228742E+09 | 0.00 | 0.00 |
October | 0.817930E+09 | 0.243616E+09 | 0.425602E+09 | 0.229806E+09 | 0.195796E+09 | 0.00 | 0.00 |
November | 0.825395E+09 | 0.353164E+09 | 0.487086E+09 | 0.296234E+09 | 0.190852E+09 | 0.00 | 0.00 |
December | 0.919192E+09 | 0.406944E+09 | 0.546352E+09 | 0.371035E+09 | 0.175316E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.800958E+10 | 0.340359E+10 | 0.457788E+10 | 0.184067E+10 | 0.273720E+10 | 0.00 | 0.00 |
Minimum of Months | 0.474122E+09 | 0.166534E+09 | 0.280177E+09 | 15821212.73 | 0.175316E+09 | 0.00 | 0.00 |
Maximum of Months | 0.919192E+09 | 0.406944E+09 | 0.546352E+09 | 0.371035E+09 | 0.280832E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.752558E+09 | 0.320676E+09 | 0.443148E+09 | 0.283223E+09 | 0.159925E+09 | 0.00 | 0.00 |
February | 0.627409E+09 | 0.257214E+09 | 0.381859E+09 | 0.204707E+09 | 0.177152E+09 | 0.00 | 0.00 |
March | 0.677993E+09 | 0.296167E+09 | 0.410414E+09 | 0.186408E+09 | 0.224005E+09 | 0.00 | 0.00 |
April | 0.824263E+09 | 0.224677E+09 | 0.461683E+09 | 0.219488E+09 | 0.242194E+09 | 0.00 | 0.00 |
May | 0.739673E+09 | 0.205812E+09 | 0.436184E+09 | 0.167979E+09 | 0.268204E+09 | 0.00 | 0.00 |
June | 0.761092E+09 | 0.143314E+09 | 0.432331E+09 | 0.180488E+09 | 0.251842E+09 | 0.00 | 0.00 |
July | 0.878859E+09 | 0.123504E+09 | 0.471298E+09 | 0.213863E+09 | 0.257435E+09 | 0.00 | 0.00 |
August | 0.903012E+09 | 0.129006E+09 | 0.468286E+09 | 0.225068E+09 | 0.243218E+09 | 0.00 | 0.00 |
September | 0.839107E+09 | 0.153069E+09 | 0.442911E+09 | 0.228273E+09 | 0.214638E+09 | 0.00 | 0.00 |
October | 0.835629E+09 | 0.177816E+09 | 0.437169E+09 | 0.263149E+09 | 0.174020E+09 | 0.00 | 0.00 |
November | 0.767916E+09 | 0.273026E+09 | 0.446356E+09 | 0.278258E+09 | 0.168098E+09 | 0.00 | 0.00 |
December | 0.794996E+09 | 0.316979E+09 | 0.465230E+09 | 0.312595E+09 | 0.152635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.940251E+10 | 0.262126E+10 | 0.529687E+10 | 0.276350E+10 | 0.253337E+10 | 0.00 | 0.00 |
Minimum of Months | 0.627409E+09 | 0.123504E+09 | 0.381859E+09 | 0.167979E+09 | 0.152635E+09 | 0.00 | 0.00 |
Maximum of Months | 0.903012E+09 | 0.320676E+09 | 0.471298E+09 | 0.312595E+09 | 0.268204E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.348206E+09 | 0.327233E+09 | 0.222106E+09 | 91526423.86 | 0.130580E+09 | 0.00 | 0.00 |
February | 0.364211E+09 | 0.259203E+09 | 0.244343E+09 | 92934228.36 | 0.151408E+09 | 0.00 | 0.00 |
March | 0.473132E+09 | 0.297339E+09 | 0.314157E+09 | 0.113326E+09 | 0.200830E+09 | 0.00 | 0.00 |
April | 0.671229E+09 | 0.227570E+09 | 0.406290E+09 | 0.177974E+09 | 0.228316E+09 | 0.00 | 0.00 |
May | 0.693530E+09 | 0.208008E+09 | 0.426579E+09 | 0.163274E+09 | 0.263305E+09 | 0.00 | 0.00 |
June | 0.746498E+09 | 0.155819E+09 | 0.436890E+09 | 0.184314E+09 | 0.252576E+09 | 0.00 | 0.00 |
July | 0.839736E+09 | 0.143471E+09 | 0.468421E+09 | 0.213287E+09 | 0.255135E+09 | 0.00 | 0.00 |
August | 0.778219E+09 | 0.148084E+09 | 0.431945E+09 | 0.198846E+09 | 0.233100E+09 | 0.00 | 0.00 |
September | 0.628677E+09 | 0.163631E+09 | 0.357662E+09 | 0.161969E+09 | 0.195693E+09 | 0.00 | 0.00 |
October | 0.521181E+09 | 0.188540E+09 | 0.284255E+09 | 0.130545E+09 | 0.153709E+09 | 0.00 | 0.00 |
November | 0.393375E+09 | 0.277523E+09 | 0.246493E+09 | 0.107324E+09 | 0.139169E+09 | 0.00 | 0.00 |
December | 0.353290E+09 | 0.324334E+09 | 0.221981E+09 | 98499410.79 | 0.123482E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.681129E+10 | 0.272076E+10 | 0.406112E+10 | 0.173382E+10 | 0.232730E+10 | 0.00 | 0.00 |
Minimum of Months | 0.348206E+09 | 0.143471E+09 | 0.221981E+09 | 91526423.86 | 0.123482E+09 | 0.00 | 0.00 |
Maximum of Months | 0.839736E+09 | 0.327233E+09 | 0.468421E+09 | 0.213287E+09 | 0.263305E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.672924E+09 | 0.166947E+09 | 0.380896E+09 | 0.281141E+09 | 99754685.41 | 0.00 | 0.00 |
February | 0.461022E+09 | 0.133397E+09 | 0.265986E+09 | 0.163926E+09 | 0.102061E+09 | 0.00 | 0.00 |
March | 0.403893E+09 | 0.154084E+09 | 0.228423E+09 | 0.107182E+09 | 0.121241E+09 | 0.00 | 0.00 |
April | 0.348167E+09 | 0.115674E+09 | 0.178722E+09 | 61361187.97 | 0.117360E+09 | 0.00 | 0.00 |
May | 0.226129E+09 | 0.105832E+09 | 0.133934E+09 | 11521662.46 | 0.122412E+09 | 0.00 | 0.00 |
June | 0.197279E+09 | 72469077.18 | 0.115199E+09 | 3888469.26 | 0.111310E+09 | 0.00 | 0.00 |
July | 0.239964E+09 | 61076369.25 | 0.123635E+09 | 8554393.57 | 0.115080E+09 | 0.00 | 0.00 |
August | 0.332526E+09 | 63839711.42 | 0.153998E+09 | 39924074.78 | 0.114074E+09 | 0.00 | 0.00 |
September | 0.428748E+09 | 77898697.81 | 0.207921E+09 | 97247435.30 | 0.110673E+09 | 0.00 | 0.00 |
October | 0.574862E+09 | 90054572.26 | 0.292211E+09 | 0.194475E+09 | 97735974.21 | 0.00 | 0.00 |
November | 0.628564E+09 | 0.141282E+09 | 0.352655E+09 | 0.250691E+09 | 0.101964E+09 | 0.00 | 0.00 |
December | 0.723947E+09 | 0.165229E+09 | 0.409548E+09 | 0.313992E+09 | 95555564.63 | 0.00 | 0.00 |
Annual Sum or Average | 0.523802E+10 | 0.134778E+10 | 0.284313E+10 | 0.153390E+10 | 0.130922E+10 | 0.00 | 0.00 |
Minimum of Months | 0.197279E+09 | 61076369.25 | 0.115199E+09 | 3888469.26 | 95555564.63 | 0.00 | 0.00 |
Maximum of Months | 0.723947E+09 | 0.166947E+09 | 0.409548E+09 | 0.313992E+09 | 0.122412E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.306340E+09 | 0.830174E+09 | 0.270701E+09 | 0.00 | 0.270701E+09 | 0.00 | 0.00 |
February | 0.333540E+09 | 0.666989E+09 | 0.306918E+09 | 0.00 | 0.306918E+09 | 0.00 | 0.00 |
March | 0.501396E+09 | 0.761077E+09 | 0.416436E+09 | 1043.49 | 0.416435E+09 | 0.00 | 0.00 |
April | 0.660528E+09 | 0.547949E+09 | 0.465264E+09 | 2274588.92 | 0.462989E+09 | 0.00 | 0.00 |
May | 0.859116E+09 | 0.497879E+09 | 0.572007E+09 | 22054116.78 | 0.549953E+09 | 0.00 | 0.00 |
June | 0.100155E+10 | 0.353905E+09 | 0.581730E+09 | 45336285.86 | 0.536394E+09 | 0.00 | 0.00 |
July | 0.106481E+10 | 0.308228E+09 | 0.569947E+09 | 36798771.89 | 0.533148E+09 | 0.00 | 0.00 |
August | 0.873557E+09 | 0.320849E+09 | 0.480624E+09 | 7001073.78 | 0.473623E+09 | 0.00 | 0.00 |
September | 0.664064E+09 | 0.383237E+09 | 0.395638E+09 | 28568.66 | 0.395609E+09 | 0.00 | 0.00 |
October | 0.584470E+09 | 0.454320E+09 | 0.324300E+09 | 0.00 | 0.324300E+09 | 0.00 | 0.00 |
November | 0.342419E+09 | 0.703462E+09 | 0.284158E+09 | 0.00 | 0.284158E+09 | 0.00 | 0.00 |
December | 0.282398E+09 | 0.827592E+09 | 0.252000E+09 | 0.00 | 0.252000E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.747419E+10 | 0.665566E+10 | 0.491972E+10 | 0.113494E+09 | 0.480623E+10 | 0.00 | 0.00 |
Minimum of Months | 0.282398E+09 | 0.308228E+09 | 0.252000E+09 | 0.00 | 0.252000E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106481E+10 | 0.830174E+09 | 0.581730E+09 | 45336285.86 | 0.549953E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290303E+09 | 0.868659E+09 | 0.270701E+09 | 0.00 | 0.270701E+09 | 0.00 | 0.00 |
February | 0.317005E+09 | 0.700795E+09 | 0.306918E+09 | 0.00 | 0.306918E+09 | 0.00 | 0.00 |
March | 0.480359E+09 | 0.797479E+09 | 0.416436E+09 | 1043.49 | 0.416435E+09 | 0.00 | 0.00 |
April | 0.638309E+09 | 0.574804E+09 | 0.465264E+09 | 2274588.92 | 0.462989E+09 | 0.00 | 0.00 |
May | 0.832528E+09 | 0.521553E+09 | 0.572007E+09 | 22054116.78 | 0.549953E+09 | 0.00 | 0.00 |
June | 0.976742E+09 | 0.372946E+09 | 0.581730E+09 | 45336285.86 | 0.536394E+09 | 0.00 | 0.00 |
July | 0.104107E+10 | 0.326069E+09 | 0.569947E+09 | 36798771.89 | 0.533148E+09 | 0.00 | 0.00 |
August | 0.851868E+09 | 0.340121E+09 | 0.480624E+09 | 7001073.78 | 0.473623E+09 | 0.00 | 0.00 |
September | 0.645785E+09 | 0.406264E+09 | 0.395638E+09 | 28568.66 | 0.395609E+09 | 0.00 | 0.00 |
October | 0.567066E+09 | 0.480019E+09 | 0.324300E+09 | 0.00 | 0.324300E+09 | 0.00 | 0.00 |
November | 0.326856E+09 | 0.736854E+09 | 0.284158E+09 | 0.00 | 0.284158E+09 | 0.00 | 0.00 |
December | 0.267201E+09 | 0.864773E+09 | 0.252000E+09 | 0.00 | 0.252000E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.723509E+10 | 0.699034E+10 | 0.491972E+10 | 0.113494E+09 | 0.480623E+10 | 0.00 | 0.00 |
Minimum of Months | 0.267201E+09 | 0.326069E+09 | 0.252000E+09 | 0.00 | 0.252000E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104107E+10 | 0.868659E+09 | 0.581730E+09 | 45336285.86 | 0.549953E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159012E+10 | 0.437215E+09 | 0.684237E+09 | 0.396344E+09 | 0.287894E+09 | 0.00 | 0.00 |
February | 0.134676E+10 | 0.352575E+09 | 0.595654E+09 | 0.281058E+09 | 0.314596E+09 | 0.00 | 0.00 |
March | 0.162620E+10 | 0.427729E+09 | 0.719822E+09 | 0.300368E+09 | 0.419454E+09 | 0.00 | 0.00 |
April | 0.194292E+10 | 0.312347E+09 | 0.809103E+09 | 0.354944E+09 | 0.454159E+09 | 0.00 | 0.00 |
May | 0.188243E+10 | 0.304865E+09 | 0.777000E+09 | 0.264041E+09 | 0.512960E+09 | 0.00 | 0.00 |
June | 0.191288E+10 | 0.204711E+09 | 0.740900E+09 | 0.260564E+09 | 0.480336E+09 | 0.00 | 0.00 |
July | 0.224150E+10 | 0.172145E+09 | 0.844494E+09 | 0.348757E+09 | 0.495737E+09 | 0.00 | 0.00 |
August | 0.226256E+10 | 0.172893E+09 | 0.846286E+09 | 0.386933E+09 | 0.459353E+09 | 0.00 | 0.00 |
September | 0.182858E+10 | 0.190838E+09 | 0.671493E+09 | 0.283871E+09 | 0.387622E+09 | 0.00 | 0.00 |
October | 0.187313E+10 | 0.242397E+09 | 0.677040E+09 | 0.354236E+09 | 0.322804E+09 | 0.00 | 0.00 |
November | 0.155655E+10 | 0.360440E+09 | 0.658424E+09 | 0.360967E+09 | 0.297458E+09 | 0.00 | 0.00 |
December | 0.159683E+10 | 0.427853E+09 | 0.687745E+09 | 0.419748E+09 | 0.267997E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.216605E+11 | 0.360601E+10 | 0.871220E+10 | 0.401183E+10 | 0.470037E+10 | 0.00 | 0.00 |
Minimum of Months | 0.134676E+10 | 0.172145E+09 | 0.595654E+09 | 0.260564E+09 | 0.267997E+09 | 0.00 | 0.00 |
Maximum of Months | 0.226256E+10 | 0.437215E+09 | 0.846286E+09 | 0.419748E+09 | 0.512960E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177714E+10 | 0.766455E+09 | 0.106239E+10 | 0.715660E+09 | 0.346728E+09 | 0.00 | 0.00 |
February | 0.125123E+10 | 0.632912E+09 | 0.782295E+09 | 0.417282E+09 | 0.365013E+09 | 0.00 | 0.00 |
March | 0.116229E+10 | 0.727550E+09 | 0.724217E+09 | 0.272838E+09 | 0.451379E+09 | 0.00 | 0.00 |
April | 0.105580E+10 | 0.573070E+09 | 0.614439E+09 | 0.156978E+09 | 0.457461E+09 | 0.00 | 0.00 |
May | 0.788518E+09 | 0.526464E+09 | 0.537020E+09 | 36889198.45 | 0.500131E+09 | 0.00 | 0.00 |
June | 0.745837E+09 | 0.392537E+09 | 0.492663E+09 | 25439672.54 | 0.467223E+09 | 0.00 | 0.00 |
July | 0.868439E+09 | 0.358466E+09 | 0.510097E+09 | 34390354.38 | 0.475707E+09 | 0.00 | 0.00 |
August | 0.105338E+10 | 0.380792E+09 | 0.556769E+09 | 0.104029E+09 | 0.452740E+09 | 0.00 | 0.00 |
September | 0.125161E+10 | 0.440279E+09 | 0.664899E+09 | 0.247558E+09 | 0.417341E+09 | 0.00 | 0.00 |
October | 0.159627E+10 | 0.493110E+09 | 0.855010E+09 | 0.495047E+09 | 0.359963E+09 | 0.00 | 0.00 |
November | 0.167077E+10 | 0.674895E+09 | 0.995112E+09 | 0.638147E+09 | 0.356965E+09 | 0.00 | 0.00 |
December | 0.189192E+10 | 0.764994E+09 | 0.112891E+10 | 0.799284E+09 | 0.329628E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.151132E+11 | 0.673152E+10 | 0.892382E+10 | 0.394354E+10 | 0.498028E+10 | 0.00 | 0.00 |
Minimum of Months | 0.745837E+09 | 0.358466E+09 | 0.492663E+09 | 25439672.54 | 0.329628E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189192E+10 | 0.766455E+09 | 0.112891E+10 | 0.799284E+09 | 0.500131E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770419E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413088.7 | 81.21 | 0.00 | 0.00 |
February | 0.696176E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145792449.7 | 81.21 | 0.00 | 0.00 |
March | 0.770288E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413172.9 | 81.21 | 0.00 | 0.00 |
April | 0.746480E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156205854.2 | 81.21 | 0.00 | 0.00 |
May | 0.770420E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412649.8 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156205119.5 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411391.0 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411494.7 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156205292.8 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412760.4 | 81.21 | 0.00 | 0.00 |
November | 0.744863E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206041.0 | 81.21 | 0.00 | 0.00 |
December | 0.771227E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413488.1 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907409E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190050E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696176E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161413488.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771227E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145792449.7 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.109809E+12 | -0.108049E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176036E+10 | 81.25 | 0.00 | 0.00 |
February | 0.992703E+11 | -0.976639E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160640E+10 | 81.25 | 0.00 | 0.00 |
March | 0.109141E+12 | -0.107356E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178491E+10 | 81.25 | 0.00 | 0.00 |
April | 0.104213E+12 | -0.102483E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173015E+10 | 81.26 | 0.00 | 0.00 |
May | 0.105935E+12 | -0.104147E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178769E+10 | 81.25 | 0.00 | 0.00 |
June | 0.100999E+12 | -0.992664E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173287E+10 | 81.25 | 0.00 | 0.00 |
July | 0.103389E+12 | -0.101609E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178002E+10 | 81.25 | 0.00 | 0.00 |
August | 0.103286E+12 | -0.101509E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177682E+10 | 81.25 | 0.00 | 0.00 |
September | 0.100716E+12 | -0.990055E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171010E+10 | 81.25 | 0.00 | 0.00 |
October | 0.105539E+12 | -0.103781E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175788E+10 | 81.25 | 0.00 | 0.00 |
November | 0.103828E+12 | -0.102129E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169865E+10 | 81.25 | 0.00 | 0.00 |
December | 0.108851E+12 | -0.107091E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175966E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.125498E+13 | -0.123409E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208855E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.992703E+11 | -0.108049E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.178769E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.109809E+12 | -0.976639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160640E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.622222E+11 | -0.607123E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150989E+10 | 58.98 | 0.00 | 0.00 |
February | 0.562958E+11 | -0.549095E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.138629E+10 | 58.98 | 0.00 | 0.00 |
March | 0.617145E+11 | -0.601709E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154359E+10 | 58.98 | 0.00 | 0.00 |
April | 0.584792E+11 | -0.569815E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149766E+10 | 58.98 | 0.00 | 0.00 |
May | 0.589271E+11 | -0.573796E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154750E+10 | 58.98 | 0.00 | 0.00 |
June | 0.557391E+11 | -0.542376E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150148E+10 | 58.98 | 0.00 | 0.00 |
July | 0.566956E+11 | -0.551586E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153698E+10 | 58.98 | 0.00 | 0.00 |
August | 0.566614E+11 | -0.551290E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153246E+10 | 58.98 | 0.00 | 0.00 |
September | 0.554565E+11 | -0.539864E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147007E+10 | 58.98 | 0.00 | 0.00 |
October | 0.585377E+11 | -0.570313E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150639E+10 | 58.98 | 0.00 | 0.00 |
November | 0.581085E+11 | -0.566543E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145426E+10 | 58.98 | 0.00 | 0.00 |
December | 0.613938E+11 | -0.598850E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150871E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.700231E+12 | -0.682236E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179953E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.554565E+11 | -0.607123E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.154750E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.622222E+11 | -0.539864E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.138629E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.87 | 0.86 | 01-JAN-07:19 | 7090.25 | 37.45 | 285.00 | 281.17 | 1005.40 | 26.85 | 186.83 | 264.67 |
February | 279.67 | 0.87 | 0.86 | 01-FEB-07:19 | 4816.74 | 31.89 | 217.67 | 276.33 | 663.89 | 23.38 | 160.67 | 246.67 |
March | 338.17 | 0.87 | 0.86 | 01-MAR-07:30 | 1262.29 | 19.00 | 14.00 | 321.83 | 481.50 | 20.69 | 132.17 | 268.00 |
April | 358.33 | 0.87 | 0.86 | 01-APR-06:00 | 873.87 | 18.39 | 0.00 | 334.67 | 372.27 | 20.65 | 116.17 | 274.67 |
May | 393.83 | 0.87 | 0.86 | 01-MAY-06:49 | 796.23 | 17.87 | 0.00 | 367.50 | 328.42 | 20.12 | 68.00 | 281.33 |
June | 381.00 | 0.87 | 0.86 | 01-JUN-06:49 | 688.40 | 17.63 | 0.00 | 359.50 | 293.73 | 19.93 | 25.00 | 262.00 |
July | 408.67 | 0.87 | 0.86 | 01-JUL-06:49 | 677.11 | 17.74 | 0.00 | 369.83 | 299.27 | 20.06 | 39.67 | 280.33 |
August | 390.67 | 0.87 | 0.86 | 01-AUG-07:30 | 734.78 | 18.02 | 0.00 | 355.67 | 323.38 | 20.31 | 64.67 | 282.83 |
September | 328.83 | 0.87 | 0.86 | 01-SEP-06:00 | 989.89 | 18.42 | 0.00 | 310.67 | 416.02 | 20.68 | 120.50 | 260.83 |
October | 296.17 | 0.87 | 0.86 | 01-OCT-09:39 | 3269.52 | 26.66 | 135.50 | 306.33 | 489.53 | 21.24 | 88.83 | 254.67 |
November | 300.00 | 0.87 | 0.86 | 01-NOV-06:49 | 6853.55 | 37.25 | 294.67 | 281.33 | 877.63 | 26.38 | 197.50 | 269.17 |
December | 297.00 | 0.87 | 0.86 | 01-DEC-07:19 | 6975.54 | 37.88 | 289.17 | 281.33 | 1235.73 | 28.44 | 184.33 | 267.33 |
Annual Sum or Average | 4065.67 | 0.87 | 2638.72 | 23.94 | 1236.00 | 3846.17 | 535.90 | 22.12 | 1384.33 | 3212.50 | ||
Minimum of Months | 279.67 | 0.87 | 0.86 | 677.11 | 17.63 | 0.00 | 276.33 | 293.73 | 19.93 | 25.00 | 246.67 | |
Maximum of Months | 408.67 | 0.87 | 0.86 | 7090.25 | 37.88 | 294.67 | 369.83 | 1235.73 | 28.44 | 197.50 | 282.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.24 | 0.22 | 01-JAN-07:19 | 7497.68 | 37.53 | 285.00 | 287.67 | 1414.68 | 26.57 | 171.17 | 275.83 |
February | 279.67 | 0.24 | 0.22 | 01-FEB-07:19 | 5133.67 | 32.00 | 218.50 | 282.17 | 980.36 | 23.51 | 163.33 | 265.67 |
March | 338.17 | 0.26 | 0.22 | 01-MAR-06:00 | 1500.71 | 19.62 | 14.00 | 330.17 | 718.92 | 21.15 | 177.33 | 303.00 |
April | 358.33 | 0.25 | 0.22 | 01-APR-06:30 | 1060.83 | 19.20 | 0.00 | 347.67 | 558.70 | 21.22 | 184.83 | 317.33 |
May | 393.83 | 0.26 | 0.22 | 01-MAY-06:19 | 931.51 | 18.93 | 0.00 | 381.17 | 463.18 | 20.91 | 188.50 | 345.83 |
June | 381.00 | 0.26 | 0.22 | 01-JUN-06:19 | 811.43 | 18.75 | 0.00 | 371.83 | 416.31 | 20.76 | 167.83 | 336.00 |
July | 408.67 | 0.27 | 0.22 | 01-JUL-05:00 | 805.95 | 18.80 | 0.00 | 379.83 | 427.68 | 20.83 | 213.83 | 349.83 |
August | 390.67 | 0.26 | 0.22 | 01-AUG-06:49 | 890.86 | 18.94 | 0.00 | 368.17 | 479.01 | 20.97 | 192.00 | 339.33 |
September | 328.83 | 0.26 | 0.22 | 01-SEP-06:40 | 1215.38 | 19.08 | 0.00 | 323.83 | 640.89 | 21.13 | 143.33 | 295.50 |
October | 296.17 | 0.25 | 0.22 | 01-OCT-09:39 | 3589.40 | 26.76 | 135.83 | 317.67 | 808.02 | 21.31 | 96.00 | 285.00 |
November | 300.00 | 0.25 | 0.22 | 01-NOV-06:40 | 7234.45 | 37.31 | 295.00 | 286.17 | 1255.52 | 26.17 | 187.83 | 277.00 |
December | 297.00 | 0.25 | 0.22 | 01-DEC-07:10 | 7401.60 | 37.96 | 289.33 | 287.67 | 1660.94 | 28.10 | 169.67 | 277.33 |
Annual Sum or Average | 4065.67 | 0.26 | 2879.57 | 24.55 | 1237.67 | 3964.00 | 776.11 | 22.49 | 2055.67 | 3667.67 | ||
Minimum of Months | 279.67 | 0.24 | 0.22 | 805.95 | 18.75 | 0.00 | 282.17 | 416.31 | 20.76 | 96.00 | 265.67 | |
Maximum of Months | 408.67 | 0.27 | 0.22 | 7497.68 | 37.96 | 295.00 | 381.17 | 1660.94 | 28.10 | 213.83 | 349.83 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.65 | 0.60 | 01-JAN-08:50 | 327.96 | 13.64 | 0.00 | 245.17 | 172.65 | 17.82 | 0.00 | 69.17 |
February | 279.67 | 0.64 | 0.60 | 01-FEB-08:39 | 409.98 | 14.56 | 0.00 | 258.67 | 199.95 | 18.46 | 0.00 | 132.83 |
March | 338.17 | 0.63 | 0.60 | 01-MAR-08:30 | 490.70 | 15.16 | 0.00 | 316.83 | 229.10 | 18.90 | 0.00 | 231.00 |
April | 358.33 | 0.62 | 0.60 | 01-APR-06:00 | 514.08 | 16.09 | 0.00 | 346.00 | 256.31 | 19.88 | 7.67 | 297.83 |
May | 393.83 | 0.61 | 0.60 | 01-MAY-06:30 | 682.15 | 17.13 | 12.50 | 388.83 | 313.42 | 20.79 | 50.50 | 354.33 |
June | 381.00 | 0.61 | 0.60 | 01-JUN-06:19 | 719.59 | 19.21 | 58.67 | 382.83 | 338.45 | 22.01 | 101.00 | 347.50 |
July | 408.67 | 0.62 | 0.60 | 01-JUL-05:40 | 652.33 | 18.41 | 44.50 | 390.50 | 297.75 | 20.46 | 78.17 | 361.67 |
August | 390.67 | 0.62 | 0.60 | 01-AUG-06:00 | 520.43 | 16.16 | 0.00 | 372.00 | 257.82 | 19.98 | 23.83 | 330.83 |
September | 328.83 | 0.63 | 0.60 | 01-SEP-06:49 | 454.54 | 15.42 | 0.00 | 314.50 | 229.48 | 19.26 | 0.00 | 236.00 |
October | 296.17 | 0.66 | 0.60 | 01-OCT-09:39 | 339.29 | 13.98 | 0.00 | 271.00 | 175.14 | 18.04 | 0.00 | 99.00 |
November | 300.00 | 0.66 | 0.60 | 01-NOV-07:40 | 336.27 | 13.46 | 0.00 | 251.67 | 174.30 | 17.51 | 0.00 | 83.33 |
December | 297.00 | 0.66 | 0.60 | 01-DEC-08:20 | 295.89 | 13.10 | 0.00 | 238.67 | 160.22 | 17.35 | 0.00 | 47.83 |
Annual Sum or Average | 4065.67 | 0.63 | 494.99 | 15.74 | 115.67 | 3776.67 | 240.52 | 19.36 | 261.17 | 2591.33 | ||
Minimum of Months | 279.67 | 0.61 | 0.60 | 295.89 | 13.10 | 0.00 | 238.67 | 160.22 | 17.35 | 0.00 | 47.83 | |
Maximum of Months | 408.67 | 0.66 | 0.60 | 719.59 | 19.21 | 58.67 | 390.50 | 338.45 | 22.01 | 101.00 | 361.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.65 | 0.60 | 01-JAN-08:50 | 327.96 | 13.64 | 0.00 | 245.17 | 172.65 | 17.82 | 0.00 | 69.17 |
February | 279.67 | 0.64 | 0.60 | 01-FEB-08:39 | 409.98 | 14.56 | 0.00 | 258.67 | 199.95 | 18.46 | 0.00 | 132.83 |
March | 338.17 | 0.63 | 0.60 | 01-MAR-08:30 | 490.70 | 15.16 | 0.00 | 316.83 | 229.10 | 18.90 | 0.00 | 231.00 |
April | 358.33 | 0.62 | 0.60 | 01-APR-06:00 | 514.08 | 16.09 | 0.00 | 346.00 | 256.31 | 19.88 | 7.67 | 297.83 |
May | 393.83 | 0.61 | 0.60 | 01-MAY-06:30 | 682.15 | 17.13 | 12.50 | 388.83 | 313.42 | 20.79 | 50.50 | 354.33 |
June | 381.00 | 0.61 | 0.60 | 01-JUN-06:19 | 719.59 | 19.21 | 58.67 | 382.83 | 338.45 | 22.01 | 101.00 | 347.50 |
July | 408.67 | 0.62 | 0.60 | 01-JUL-05:40 | 652.33 | 18.41 | 44.50 | 390.50 | 297.75 | 20.46 | 78.17 | 361.67 |
August | 390.67 | 0.62 | 0.60 | 01-AUG-06:00 | 520.43 | 16.16 | 0.00 | 372.00 | 257.82 | 19.98 | 23.83 | 330.83 |
September | 328.83 | 0.63 | 0.60 | 01-SEP-06:49 | 454.54 | 15.42 | 0.00 | 314.50 | 229.48 | 19.26 | 0.00 | 236.00 |
October | 296.17 | 0.66 | 0.60 | 01-OCT-09:39 | 339.29 | 13.98 | 0.00 | 271.00 | 175.14 | 18.04 | 0.00 | 99.00 |
November | 300.00 | 0.66 | 0.60 | 01-NOV-07:40 | 336.27 | 13.46 | 0.00 | 251.67 | 174.30 | 17.51 | 0.00 | 83.33 |
December | 297.00 | 0.66 | 0.60 | 01-DEC-08:20 | 295.89 | 13.10 | 0.00 | 238.67 | 160.22 | 17.35 | 0.00 | 47.83 |
Annual Sum or Average | 4065.67 | 0.63 | 494.99 | 15.74 | 115.67 | 3776.67 | 240.52 | 19.36 | 261.17 | 2591.33 | ||
Minimum of Months | 279.67 | 0.61 | 0.60 | 295.89 | 13.10 | 0.00 | 238.67 | 160.22 | 17.35 | 0.00 | 47.83 | |
Maximum of Months | 408.67 | 0.66 | 0.60 | 719.59 | 19.21 | 58.67 | 390.50 | 338.45 | 22.01 | 101.00 | 361.67 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138436E+11 | 77622.72 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.383162E+10 | 47250.68 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101450E+11 | 58531.23 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464514E+09 | 25155.04 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762096E+09 | 20748.52 | 15-MAY-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142023E+09 | 9948.74 | 30-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286929E+10 | 29565.30 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100083E+11 | 47928.23 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.420664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138436E+11 | 77622.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 26072580.34 | 464.64 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51541030.36 | 510.45 | 25-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97320638.92 | 816.55 | 29-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8467422.83 | 517.96 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6732535.47 | 309.85 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8068075.39 | 389.89 | 13-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97320638.92 | 816.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3084937.27 | 213.15 | 01-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5017890.75 | 305.48 | 28-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11893369.70 | 429.32 | 29-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 242379.86 | 160.60 | 18-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14412.24 | 24.02 | 15-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20252989.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11893369.70 | 429.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147790E+09 | 418.39 | 01-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112703E+09 | 396.74 | 28-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209801E+09 | 513.08 | 29-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31496931.95 | 329.57 | 01-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6640141.68 | 205.63 | 15-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7706556.43 | 193.48 | 24-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 68319366.00 | 316.94 | 13-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.584457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209801E+09 | 513.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186806E+09 | 3667.63 | 25-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.517519E+09 | 4125.41 | 28-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.792922E+09 | 5102.61 | 29-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291848E+09 | 3331.38 | 22-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.743608E+09 | 4102.43 | 09-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610629E+09 | 3538.71 | 08-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267172E+09 | 2643.78 | 06-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 54448482.78 | 1825.44 | 02-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96961876.61 | 3623.29 | 18-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 92376742.85 | 2798.99 | 06-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89053416.40 | 2637.11 | 03-NOV-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135907E+09 | 3273.08 | 08-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 54448482.78 | 1825.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.792922E+09 | 5102.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 303822.12 | 506.37 | 01-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4156749.40 | 3324.78 | 28-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31620289.22 | 5162.69 | 29-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36080860.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31620289.22 | 5162.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 74976077.56 | 2235.22 | 01-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19976062.58 | 2159.41 | 28-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105159E+09 | 3069.51 | 29-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1129755.34 | 907.55 | 01-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105159E+09 | 3069.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 69940600.71 | 3207.52 | 03-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45363822.76 | 2872.73 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63592707.17 | 3159.54 | 30-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28122877.28 | 2744.99 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15398965.36 | 1730.84 | 15-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3991292.85 | 893.83 | 13-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 410618.64 | 316.90 | 17-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2337721.01 | 614.32 | 31-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11643446.39 | 1422.86 | 20-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15499769.93 | 2635.15 | 30-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37305271.55 | 2877.74 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49318065.33 | 3063.37 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 410618.64 | 316.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69940600.71 | 3207.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10360937.69 | 1479.66 | 03-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3123264.48 | 858.61 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3684284.10 | 1092.65 | 30-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 167967.06 | 279.95 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1052625.41 | 719.90 | 27-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5923615.01 | 1159.41 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24312693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10360937.69 | 1479.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.781976E+10 | 8943.46 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630484E+10 | 8391.78 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841655E+10 | 8532.16 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.400991E+10 | 8113.59 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.358791E+10 | 7975.38 | 19-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.637781E+09 | 5275.70 | 13-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37023292.77 | 2368.96 | 06-JUL-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16923290.42 | 904.57 | 24-AUG-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317076E+09 | 5276.32 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142155E+10 | 7833.53 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.557451E+10 | 8114.43 | 05-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.786357E+10 | 8394.05 | 03-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.460074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16923290.42 | 904.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.841655E+10 | 8943.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.282811E+09 | 3180.60 | 28-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176282E+09 | 3179.11 | 08-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323384E+09 | 3235.50 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40587634.69 | 3176.93 | 28-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30269338.84 | 3145.23 | 11-MAY-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7721194.70 | 3178.69 | 08-JUN-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4725174.75 | 3099.96 | 05-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4707913.31 | 3152.95 | 09-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6453328.03 | 2902.04 | 06-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10971446.05 | 3179.61 | 24-OCT-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54886340.99 | 3179.91 | 16-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180580E+09 | 3180.02 | 21-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4707913.31 | 2902.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323384E+09 | 3235.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.603402E+09 | 3219.61 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290145E+09 | 3163.76 | 22-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433056E+09 | 3228.21 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46151529.79 | 3160.54 | 29-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24582154.56 | 3163.00 | 28-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4212755.81 | 3130.77 | 02-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1164409.45 | 2028.82 | 07-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1274117.27 | 1402.57 | 11-AUG-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5041070.06 | 3118.93 | 03-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7665431.82 | 3161.98 | 27-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159368E+09 | 3163.86 | 06-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.445848E+09 | 3213.85 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1164409.45 | 1402.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.603402E+09 | 3228.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116373E+10 | 19283.67 | 29-JAN-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194546E+09 | 19278.25 | 28-FEB-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.605772E+09 | 19281.38 | 08-MAR-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59356329.09 | 17832.52 | 03-APR-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24206364.40 | 15024.04 | 07-MAY-19:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12131478.00 | 17851.05 | 03-JUN-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7276165.23 | 9675.09 | 09-JUL-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9705897.55 | 14584.29 | 22-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24922576.66 | 18927.56 | 20-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31266391.93 | 19277.53 | 10-OCT-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133164E+09 | 19282.87 | 25-NOV-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623063E+09 | 19284.11 | 02-DEC-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7276165.23 | 9675.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116373E+10 | 19284.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.281786E+09 | 3129.02 | 29-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215493E+09 | 3128.08 | 09-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362952E+09 | 3127.54 | 15-MAR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46134668.60 | 3129.50 | 17-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41116998.40 | 3128.89 | 13-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6925767.14 | 2961.66 | 08-JUN-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2239959.21 | 2788.70 | 09-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1455024.67 | 1123.80 | 08-AUG-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6231418.22 | 2958.56 | 04-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9248468.33 | 3129.25 | 24-OCT-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75758816.08 | 3129.27 | 12-NOV-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205685E+09 | 3129.19 | 21-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1455024.67 | 1123.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.362952E+09 | 3129.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.580458E+09 | 3140.97 | 02-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360564E+09 | 3112.22 | 19-FEB-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486027E+09 | 3163.54 | 29-MAR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54299239.61 | 3110.49 | 05-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34486525.23 | 3111.92 | 16-MAY-18:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2667089.28 | 3021.75 | 12-JUN-19:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 607829.53 | 1614.82 | 11-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 447613.72 | 1345.25 | 21-AUG-20:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4918851.31 | 2230.98 | 16-SEP-19:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8243322.87 | 1993.18 | 06-OCT-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213421E+09 | 3111.98 | 16-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476761E+09 | 3111.96 | 21-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 447613.72 | 1345.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.580458E+09 | 3163.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168160E+09 | 982.57 | 14-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124698E+09 | 1005.17 | 25-FEB-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173697E+09 | 1013.51 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30033595.89 | 957.46 | 17-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25477254.69 | 885.04 | 20-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3796852.19 | 816.61 | 08-JUN-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1134603.20 | 762.78 | 05-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1107279.05 | 737.10 | 08-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1663655.93 | 702.19 | 18-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12505002.44 | 981.51 | 25-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67390090.33 | 982.95 | 02-NOV-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138848E+09 | 982.72 | 17-DEC-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.748512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1107279.05 | 702.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173697E+09 | 1013.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.315404E+09 | 1009.54 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188301E+09 | 1002.64 | 25-FEB-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222169E+09 | 1009.97 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32364374.79 | 975.63 | 14-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19300654.10 | 975.98 | 24-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1584672.76 | 669.27 | 13-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 197256.57 | 498.19 | 06-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 248807.56 | 464.00 | 21-AUG-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1554669.25 | 768.78 | 12-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14904099.22 | 976.32 | 18-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136312E+09 | 891.93 | 25-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270670E+09 | 1007.43 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 197256.57 | 464.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315404E+09 | 1009.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137962E+09 | 3802.91 | 16-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124287E+09 | 4645.28 | 11-FEB-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348576E+09 | 4249.48 | 17-MAR-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52753139.11 | 4747.66 | 01-APR-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77992690.93 | 4744.74 | 12-MAY-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18749271.99 | 4238.77 | 15-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9962114.10 | 3731.24 | 09-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7959956.54 | 3683.67 | 30-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8982406.85 | 3780.84 | 16-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11402443.18 | 4746.01 | 24-OCT-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14435529.35 | 4506.02 | 11-NOV-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76428360.79 | 4299.62 | 06-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7959956.54 | 3683.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348576E+09 | 4747.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.635778E+11 | 0.632546E+11 | 196865.43 | 14-JAN-11:35 | 196865.43 | 0.27 |
February | 0.00 | 0.00 | 0.370519E+11 | 0.360528E+11 | 188283.77 | 01-FEB-11:50 | 188283.77 | 0.27 |
March | 0.00 | 0.00 | 0.406657E+11 | 0.397799E+11 | 189283.17 | 23-MAR-10:50 | 153660.20 | 0.27 |
April | 0.00 | 0.00 | 0.938925E+11 | 0.917320E+11 | 236936.64 | 26-APR-10:35 | 190467.55 | 0.48 |
May | 0.00 | 0.00 | 0.101448E+12 | 0.100046E+12 | 167489.44 | 18-MAY-10:50 | 150215.12 | 0.58 |
June | 0.00 | 0.00 | 0.181973E+12 | 0.158946E+12 | 304958.23 | 29-JUN-18:03 | 165439.45 | 0.85 |
July | 0.00 | 0.00 | 0.352194E+12 | 0.235829E+12 | 358749.24 | 31-JUL-18:20 | 179742.93 | 0.99 |
August | 0.00 | 0.00 | 0.394523E+12 | 0.245219E+12 | 347184.11 | 14-AUG-10:35 | 217032.89 | 0.99 |
September | 0.00 | 0.00 | 0.241359E+12 | 0.184896E+12 | 345716.29 | 22-SEP-10:35 | 149173.80 | 0.93 |
October | 0.00 | 0.00 | 0.263710E+12 | 0.213006E+12 | 330575.54 | 04-OCT-18:03 | 153348.71 | 0.62 |
November | 0.00 | 0.00 | 0.671881E+11 | 0.660718E+11 | 204211.28 | 19-NOV-11:35 | 204211.28 | 0.34 |
December | 0.00 | 0.00 | 0.725422E+11 | 0.725389E+11 | 186801.81 | 19-DEC-11:35 | 186801.81 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.191012E+13 | 0.150737E+13 | 0.56 | |||
Minimum of Months | 0.00 | 0.00 | 0.370519E+11 | 0.360528E+11 | 167489.44 | 149173.80 | 0.13 | |
Maximum of Months | 0.00 | 0.00 | 0.394523E+12 | 0.245219E+12 | 358749.24 | 217032.89 | 0.99 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.325706E+10 | 0.323404E+10 | 20570.98 | 13-JAN-14:00 | 20570.98 | 0.15 |
February | 0.00 | 0.00 | 0.176477E+10 | 0.171146E+10 | 17583.23 | 01-FEB-09:53 | 17583.23 | 0.13 |
March | 0.00 | 0.00 | 0.195362E+10 | 0.180527E+10 | 22012.17 | 22-MAR-13:00 | 14832.69 | 0.11 |
April | 0.00 | 0.00 | 0.490019E+10 | 0.461280E+10 | 22090.96 | 26-APR-13:00 | 22090.96 | 0.25 |
May | 0.00 | 0.00 | 0.520930E+10 | 0.511855E+10 | 18829.64 | 04-MAY-13:00 | 16265.15 | 0.33 |
June | 0.00 | 0.00 | 0.118877E+11 | 0.944832E+10 | 30817.80 | 29-JUN-12:15 | 17826.82 | 0.61 |
July | 0.00 | 0.00 | 0.270221E+11 | 0.158139E+11 | 40153.36 | 31-JUL-12:15 | 23766.73 | 0.75 |
August | 0.00 | 0.00 | 0.309007E+11 | 0.166894E+11 | 38594.96 | 18-AUG-12:15 | 22287.37 | 0.76 |
September | 0.00 | 0.00 | 0.175428E+11 | 0.122681E+11 | 39619.58 | 22-SEP-12:15 | 19372.88 | 0.66 |
October | 0.00 | 0.00 | 0.195118E+11 | 0.143145E+11 | 38111.08 | 01-OCT-12:15 | 20334.16 | 0.44 |
November | 0.00 | 0.00 | 0.327790E+10 | 0.321606E+10 | 21037.50 | 19-NOV-13:15 | 21037.50 | 0.18 |
December | 0.00 | 0.00 | 0.398719E+10 | 0.398506E+10 | 20480.92 | 05-DEC-09:55 | 20480.92 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.131215E+12 | 0.922174E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.176477E+10 | 0.171146E+10 | 17583.23 | 14832.69 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.309007E+11 | 0.166894E+11 | 40153.36 | 23766.73 | 0.76 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192029E+10 | 0.100469E+10 | 12060.31 | 21-JAN-09:01 | 9657.64 | 0.47 |
February | 0.00 | 0.00 | 0.172638E+10 | 0.937799E+09 | 12046.53 | 13-FEB-16:12 | 8786.76 | 0.46 |
March | 0.00 | 0.00 | 0.185637E+10 | 0.855215E+09 | 11745.00 | 18-MAR-08:61 | 9011.12 | 0.51 |
April | 0.00 | 0.00 | 0.368536E+10 | 0.177545E+10 | 11540.51 | 08-APR-08:62 | 9722.09 | 0.76 |
May | 0.00 | 0.00 | 0.345808E+10 | 0.158406E+10 | 11975.24 | 06-MAY-08:62 | 9185.93 | 0.75 |
June | 0.00 | 0.00 | 0.487246E+10 | 0.227038E+10 | 12186.45 | 28-JUN-08:62 | 8769.77 | 0.83 |
July | 0.00 | 0.00 | 0.688042E+10 | 0.337506E+10 | 12599.05 | 31-JUL-08:62 | 9222.52 | 0.90 |
August | 0.00 | 0.00 | 0.714508E+10 | 0.352741E+10 | 12942.22 | 18-AUG-08:62 | 8860.56 | 0.92 |
September | 0.00 | 0.00 | 0.555471E+10 | 0.264846E+10 | 12777.87 | 22-SEP-08:62 | 8767.34 | 0.89 |
October | 0.00 | 0.00 | 0.504055E+10 | 0.297268E+10 | 12687.23 | 01-OCT-08:62 | 9151.68 | 0.72 |
November | 0.00 | 0.00 | 0.258594E+10 | 0.136555E+10 | 12279.05 | 12-NOV-09:02 | 8418.53 | 0.59 |
December | 0.00 | 0.00 | 0.216098E+10 | 0.151318E+10 | 11832.45 | 30-DEC-16:11 | 11832.45 | 0.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.468866E+11 | 0.238299E+11 | 0.68 | |||
Minimum of Months | 0.00 | 0.00 | 0.172638E+10 | 0.855215E+09 | 11540.51 | 8418.53 | 0.34 | |
Maximum of Months | 0.00 | 0.00 | 0.714508E+10 | 0.352741E+10 | 12942.22 | 11832.45 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.443518E+09 | 0.189984E+09 | 11583.50 | 20-JAN-19:01 | 8583.58 | 0.23 |
February | 0.00 | 0.00 | 0.608640E+09 | 0.258812E+09 | 11383.41 | 06-FEB-16:11 | 11383.41 | 0.28 |
March | 0.00 | 0.00 | 0.858884E+09 | 0.313736E+09 | 11474.12 | 22-MAR-18:51 | 9152.95 | 0.35 |
April | 0.00 | 0.00 | 0.219092E+10 | 0.840442E+09 | 12242.95 | 26-APR-21:51 | 9206.92 | 0.59 |
May | 0.00 | 0.00 | 0.240902E+10 | 0.978037E+09 | 11861.78 | 02-MAY-21:51 | 9159.77 | 0.58 |
June | 0.00 | 0.00 | 0.312717E+10 | 0.138090E+10 | 12705.83 | 28-JUN-21:51 | 9253.33 | 0.54 |
July | 0.00 | 0.00 | 0.445531E+10 | 0.222703E+10 | 12892.73 | 27-JUL-21:51 | 9169.31 | 0.56 |
August | 0.00 | 0.00 | 0.424253E+10 | 0.202801E+10 | 12808.20 | 16-AUG-21:51 | 9128.93 | 0.55 |
September | 0.00 | 0.00 | 0.303365E+10 | 0.126471E+10 | 12441.86 | 30-SEP-21:51 | 9058.46 | 0.54 |
October | 0.00 | 0.00 | 0.237960E+10 | 0.126602E+10 | 12757.02 | 01-OCT-08:52 | 8240.90 | 0.43 |
November | 0.00 | 0.00 | 0.810262E+09 | 0.314452E+09 | 11824.84 | 12-NOV-09:02 | 8005.71 | 0.36 |
December | 0.00 | 0.00 | 0.471922E+09 | 0.288520E+09 | 11219.70 | 07-DEC-19:01 | 9087.70 | 0.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.250314E+11 | 0.113507E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.443518E+09 | 0.189984E+09 | 11219.70 | 8005.71 | 0.17 | |
Maximum of Months | 0.00 | 0.00 | 0.445531E+10 | 0.222703E+10 | 12892.73 | 11383.41 | 0.59 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.315282E+11 | 0.224582E+11 | 38501.94 | 14-JAN-12:40 | 38501.94 | 0.59 |
February | 0.00 | 0.00 | 0.206529E+11 | 0.134387E+11 | 34350.05 | 02-FEB-12:30 | 31584.82 | 0.55 |
March | 0.00 | 0.00 | 0.158034E+11 | 0.697469E+10 | 28760.10 | 11-MAR-13:15 | 24915.30 | 0.61 |
April | 0.00 | 0.00 | 0.179010E+11 | 0.644664E+10 | 21784.58 | 08-APR-12:40 | 11801.73 | 0.76 |
May | 0.00 | 0.00 | 0.111383E+11 | 0.282208E+10 | 16982.29 | 03-MAY-06:53 | 6356.35 | 0.68 |
June | 0.00 | 0.00 | 0.143037E+11 | 0.365687E+10 | 18356.20 | 30-JUN-06:53 | 6788.36 | 0.80 |
July | 0.00 | 0.00 | 0.220001E+11 | 0.646532E+10 | 21838.85 | 30-JUL-08:00 | 8958.96 | 0.94 |
August | 0.00 | 0.00 | 0.290813E+11 | 0.101736E+11 | 22845.05 | 19-AUG-08:00 | 9783.68 | 0.98 |
September | 0.00 | 0.00 | 0.311716E+11 | 0.135012E+11 | 34929.06 | 30-SEP-13:05 | 33372.93 | 0.98 |
October | 0.00 | 0.00 | 0.385645E+11 | 0.251683E+11 | 42188.26 | 16-OCT-12:30 | 42188.26 | 0.75 |
November | 0.00 | 0.00 | 0.322505E+11 | 0.213572E+11 | 41651.38 | 19-NOV-09:53 | 35018.32 | 0.70 |
December | 0.00 | 0.00 | 0.352366E+11 | 0.282241E+11 | 39237.94 | 19-DEC-13:00 | 39237.94 | 0.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.299632E+12 | 0.160687E+12 | 0.73 | |||
Minimum of Months | 0.00 | 0.00 | 0.111383E+11 | 0.282208E+10 | 16982.29 | 6356.35 | 0.47 | |
Maximum of Months | 0.00 | 0.00 | 0.385645E+11 | 0.282241E+11 | 42188.26 | 42188.26 | 0.98 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.110688E+11 | 0.579614E+10 | 71788.12 | 20-JAN-19:01 | 55993.54 | 0.36 |
February | 0.00 | 0.00 | 0.127772E+11 | 0.625290E+10 | 70167.14 | 13-FEB-19:12 | 54434.71 | 0.50 |
March | 0.00 | 0.00 | 0.156193E+11 | 0.721763E+10 | 68996.34 | 22-MAR-18:51 | 55606.52 | 0.53 |
April | 0.00 | 0.00 | 0.219646E+11 | 0.111743E+11 | 74836.98 | 26-APR-21:51 | 55991.27 | 0.54 |
May | 0.00 | 0.00 | 0.253920E+11 | 0.139910E+11 | 73202.94 | 04-MAY-21:51 | 57829.97 | 0.53 |
June | 0.00 | 0.00 | 0.280553E+11 | 0.163545E+11 | 77749.61 | 28-JUN-21:51 | 56362.01 | 0.45 |
July | 0.00 | 0.00 | 0.336084E+11 | 0.199875E+11 | 79271.83 | 19-JUL-21:51 | 55176.11 | 0.47 |
August | 0.00 | 0.00 | 0.313799E+11 | 0.178975E+11 | 78541.55 | 16-AUG-21:51 | 55693.70 | 0.45 |
September | 0.00 | 0.00 | 0.246680E+11 | 0.131961E+11 | 78002.04 | 22-SEP-21:52 | 54088.08 | 0.43 |
October | 0.00 | 0.00 | 0.223233E+11 | 0.143753E+11 | 77733.11 | 01-OCT-08:52 | 52223.63 | 0.35 |
November | 0.00 | 0.00 | 0.142046E+11 | 0.738703E+10 | 71451.39 | 09-NOV-22:53 | 53253.00 | 0.45 |
December | 0.00 | 0.00 | 0.103938E+11 | 0.651020E+10 | 68582.03 | 19-DEC-19:01 | 68582.03 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.251455E+12 | 0.140140E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.103938E+11 | 0.579614E+10 | 68582.03 | 52223.63 | 0.29 | |
Maximum of Months | 0.00 | 0.00 | 0.336084E+11 | 0.199875E+11 | 79271.83 | 68582.03 | 0.54 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.202954E+10 | 0.117197E+10 | 10564.51 | 14-JAN-16:11 | 10564.51 | 0.49 |
February | 0.00 | 0.00 | 0.160021E+10 | 0.923536E+09 | 10565.90 | 01-FEB-09:01 | 10565.90 | 0.44 |
March | 0.00 | 0.00 | 0.182263E+10 | 0.861737E+09 | 10380.90 | 17-MAR-08:61 | 8922.51 | 0.51 |
April | 0.00 | 0.00 | 0.333820E+10 | 0.161512E+10 | 10560.94 | 02-APR-08:61 | 10560.94 | 0.78 |
May | 0.00 | 0.00 | 0.296888E+10 | 0.136851E+10 | 10811.60 | 06-MAY-08:62 | 8427.57 | 0.75 |
June | 0.00 | 0.00 | 0.412215E+10 | 0.185518E+10 | 10971.58 | 28-JUN-08:62 | 7838.16 | 0.85 |
July | 0.00 | 0.00 | 0.626875E+10 | 0.299668E+10 | 10967.18 | 20-JUL-08:62 | 8466.81 | 0.93 |
August | 0.00 | 0.00 | 0.678545E+10 | 0.329214E+10 | 11186.02 | 08-AUG-08:62 | 8041.70 | 0.94 |
September | 0.00 | 0.00 | 0.479017E+10 | 0.221314E+10 | 11287.62 | 22-SEP-08:62 | 8152.18 | 0.89 |
October | 0.00 | 0.00 | 0.476427E+10 | 0.286044E+10 | 11360.16 | 01-OCT-08:62 | 8154.90 | 0.72 |
November | 0.00 | 0.00 | 0.238304E+10 | 0.136410E+10 | 10980.13 | 12-NOV-09:02 | 7482.35 | 0.57 |
December | 0.00 | 0.00 | 0.215868E+10 | 0.160981E+10 | 10564.11 | 31-DEC-09:01 | 10564.11 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.430320E+11 | 0.221324E+11 | 0.69 | |||
Minimum of Months | 0.00 | 0.00 | 0.160021E+10 | 0.861737E+09 | 10380.90 | 7482.35 | 0.33 | |
Maximum of Months | 0.00 | 0.00 | 0.678545E+10 | 0.329214E+10 | 11360.16 | 10565.90 | 0.94 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.578263E+09 | 0.298223E+09 | 10413.47 | 20-JAN-19:01 | 7781.46 | 0.21 |
February | 0.00 | 0.00 | 0.600783E+09 | 0.305841E+09 | 10169.61 | 06-FEB-09:01 | 10169.61 | 0.23 |
March | 0.00 | 0.00 | 0.902944E+09 | 0.387900E+09 | 10069.73 | 18-MAR-08:61 | 8559.27 | 0.35 |
April | 0.00 | 0.00 | 0.205208E+10 | 0.926277E+09 | 10736.39 | 26-APR-21:51 | 7943.58 | 0.59 |
May | 0.00 | 0.00 | 0.211887E+10 | 0.926948E+09 | 10949.34 | 24-MAY-08:51 | 10949.34 | 0.59 |
June | 0.00 | 0.00 | 0.274930E+10 | 0.121986E+10 | 11421.44 | 30-JUN-08:51 | 9370.03 | 0.57 |
July | 0.00 | 0.00 | 0.413316E+10 | 0.199989E+10 | 12127.48 | 23-JUL-08:51 | 9431.35 | 0.58 |
August | 0.00 | 0.00 | 0.409417E+10 | 0.193855E+10 | 12464.49 | 19-AUG-08:51 | 9150.08 | 0.58 |
September | 0.00 | 0.00 | 0.250686E+10 | 0.108297E+10 | 11429.86 | 10-SEP-08:51 | 9371.92 | 0.56 |
October | 0.00 | 0.00 | 0.219963E+10 | 0.126077E+10 | 11760.72 | 15-OCT-07:41 | 11760.72 | 0.44 |
November | 0.00 | 0.00 | 0.780002E+09 | 0.372158E+09 | 10582.72 | 12-NOV-09:02 | 7106.31 | 0.30 |
December | 0.00 | 0.00 | 0.506334E+09 | 0.336017E+09 | 10535.74 | 05-DEC-09:41 | 10535.74 | 0.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.232224E+11 | 0.110554E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.506334E+09 | 0.298223E+09 | 10069.73 | 7106.31 | 0.15 | |
Maximum of Months | 0.00 | 0.00 | 0.413316E+10 | 0.199989E+10 | 12464.49 | 11760.72 | 0.59 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.389986E+09 | 0.213186E+09 | 3274.60 | 21-JAN-09:01 | 2279.22 | 0.37 |
February | 0.00 | 0.00 | 0.363402E+09 | 0.206297E+09 | 3132.95 | 13-FEB-16:12 | 2223.89 | 0.33 |
March | 0.00 | 0.00 | 0.427441E+09 | 0.214568E+09 | 3130.14 | 18-MAR-08:61 | 2168.74 | 0.40 |
April | 0.00 | 0.00 | 0.903068E+09 | 0.467333E+09 | 3179.52 | 12-APR-08:62 | 2231.38 | 0.72 |
May | 0.00 | 0.00 | 0.831450E+09 | 0.407578E+09 | 3288.90 | 06-MAY-08:62 | 2123.84 | 0.69 |
June | 0.00 | 0.00 | 0.122325E+10 | 0.597984E+09 | 3275.61 | 28-JUN-08:62 | 2134.42 | 0.84 |
July | 0.00 | 0.00 | 0.177054E+10 | 0.895512E+09 | 3360.98 | 31-JUL-08:62 | 2282.12 | 0.92 |
August | 0.00 | 0.00 | 0.181125E+10 | 0.913643E+09 | 3490.40 | 06-AUG-08:61 | 2193.53 | 0.92 |
September | 0.00 | 0.00 | 0.133642E+10 | 0.649643E+09 | 3441.15 | 22-SEP-08:62 | 2126.13 | 0.89 |
October | 0.00 | 0.00 | 0.115747E+10 | 0.689140E+09 | 3431.41 | 01-OCT-08:62 | 2263.31 | 0.67 |
November | 0.00 | 0.00 | 0.527948E+09 | 0.285892E+09 | 3328.07 | 12-NOV-09:02 | 1951.73 | 0.46 |
December | 0.00 | 0.00 | 0.433192E+09 | 0.311793E+09 | 3072.75 | 05-DEC-19:01 | 3072.75 | 0.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.111754E+11 | 0.585257E+10 | 0.62 | |||
Minimum of Months | 0.00 | 0.00 | 0.363402E+09 | 0.206297E+09 | 3072.75 | 1951.73 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.181125E+10 | 0.913643E+09 | 3490.40 | 3072.75 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 61842985.62 | 29594284.84 | 3063.67 | 21-JAN-09:01 | 2008.39 | 0.10 |
February | 0.00 | 0.00 | 0.104373E+09 | 46405520.66 | 2948.58 | 06-FEB-16:11 | 2948.58 | 0.17 |
March | 0.00 | 0.00 | 0.178833E+09 | 71722253.14 | 3027.47 | 22-MAR-18:51 | 2439.18 | 0.23 |
April | 0.00 | 0.00 | 0.522743E+09 | 0.214440E+09 | 3255.74 | 26-APR-21:51 | 2410.95 | 0.53 |
May | 0.00 | 0.00 | 0.580186E+09 | 0.248421E+09 | 3139.83 | 02-MAY-21:51 | 2363.92 | 0.55 |
June | 0.00 | 0.00 | 0.834329E+09 | 0.381615E+09 | 3384.91 | 28-JUN-21:51 | 2428.62 | 0.56 |
July | 0.00 | 0.00 | 0.123647E+10 | 0.631996E+09 | 3423.40 | 27-JUL-21:51 | 2400.42 | 0.57 |
August | 0.00 | 0.00 | 0.114736E+10 | 0.555535E+09 | 3397.96 | 16-AUG-21:51 | 2374.02 | 0.56 |
September | 0.00 | 0.00 | 0.735986E+09 | 0.304835E+09 | 3277.72 | 30-SEP-21:51 | 2295.43 | 0.56 |
October | 0.00 | 0.00 | 0.520124E+09 | 0.281390E+09 | 3380.21 | 01-OCT-08:52 | 2038.22 | 0.39 |
November | 0.00 | 0.00 | 0.114517E+09 | 44373961.57 | 3181.10 | 12-NOV-09:02 | 1850.92 | 0.21 |
December | 0.00 | 0.00 | 57326293.62 | 39524040.17 | 2899.53 | 07-DEC-19:01 | 2271.47 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.609409E+10 | 0.284985E+10 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 57326293.62 | 29594284.84 | 2899.53 | 1850.92 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.123647E+10 | 0.631996E+09 | 3423.40 | 2948.58 | 0.57 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.684835E+10 | 0.488980E+10 | 14738.49 | 14-JAN-16:11 | 14738.49 | 0.63 |
February | 0.00 | 0.00 | 0.466019E+10 | 0.308167E+10 | 14878.20 | 13-FEB-16:12 | 10848.17 | 0.60 |
March | 0.00 | 0.00 | 0.409256E+10 | 0.217927E+10 | 14799.60 | 18-MAR-08:61 | 11899.93 | 0.63 |
April | 0.00 | 0.00 | 0.499748E+10 | 0.236701E+10 | 14557.74 | 01-APR-18:02 | 14557.74 | 0.78 |
May | 0.00 | 0.00 | 0.330440E+10 | 0.132134E+10 | 14990.66 | 06-MAY-08:62 | 11481.81 | 0.69 |
June | 0.00 | 0.00 | 0.436384E+10 | 0.166838E+10 | 15386.10 | 27-JUN-18:01 | 11829.42 | 0.79 |
July | 0.00 | 0.00 | 0.680447E+10 | 0.280574E+10 | 16239.93 | 29-JUL-18:01 | 11163.34 | 0.87 |
August | 0.00 | 0.00 | 0.843985E+10 | 0.374087E+10 | 16427.84 | 18-AUG-08:62 | 10517.61 | 0.90 |
September | 0.00 | 0.00 | 0.803136E+10 | 0.401191E+10 | 16142.21 | 22-SEP-08:62 | 10856.37 | 0.88 |
October | 0.00 | 0.00 | 0.909167E+10 | 0.613605E+10 | 16299.84 | 05-OCT-18:01 | 11113.31 | 0.74 |
November | 0.00 | 0.00 | 0.704917E+10 | 0.483359E+10 | 15052.87 | 12-NOV-09:02 | 11315.19 | 0.70 |
December | 0.00 | 0.00 | 0.732737E+10 | 0.589429E+10 | 14738.67 | 29-DEC-19:01 | 14738.67 | 0.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.750107E+11 | 0.429299E+11 | 0.73 | |||
Minimum of Months | 0.00 | 0.00 | 0.330440E+10 | 0.132134E+10 | 14557.74 | 10517.61 | 0.49 | |
Maximum of Months | 0.00 | 0.00 | 0.909167E+10 | 0.613605E+10 | 16427.84 | 14738.67 | 0.90 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 9519.83 | 105027.53 | 08-JAN-06:50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 5136.68 | 62931.15 | 05-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 8446.76 | 85420.26 | 30-MAR-03:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1979.22 | 41150.14 | 01-APR-06:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1993.68 | 32398.67 | 14-MAY-04:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 498.41 | 16917.20 | 23-JUN-08:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 122.74 | 15753.65 | 12-JUL-08:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 39.24 | 14614.37 | 22-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 184.92 | 16351.90 | 28-SEP-08:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 656.77 | 17916.22 | 30-OCT-04:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3600.97 | 41857.36 | 24-NOV-04:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 7604.01 | 66002.70 | 24-DEC-04:00 |
Annual Sum or Average | 0.00 | 3319.47 | ||||
Minimum of Months | 0.00 | 0.00 | 39.24 | 14614.37 | ||
Maximum of Months | 0.00 | 0.00 | 9519.83 | 105027.53 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 47156.06 | 300749.24 | 15-JAN-09:52 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 35621.77 | 296599.11 | 01-FEB-09:52 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 33089.96 | 280834.78 | 11-MAR-09:51 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 62151.44 | 273061.23 | 26-APR-08:52 | 0.00 | 0.00 | 01-APR-00:10 |
May | 61162.71 | 210204.64 | 04-MAY-08:53 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 101191.17 | 385735.94 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 175953.99 | 473618.51 | 18-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 195806.78 | 472435.42 | 18-AUG-15:13 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 133303.56 | 454374.53 | 21-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 139706.31 | 430173.18 | 14-OCT-15:13 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 52447.80 | 344850.88 | 19-NOV-09:41 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 52263.84 | 337048.92 | 05-DEC-09:41 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 91313.86 | 0.00 | ||||
Minimum of Months | 33089.96 | 210204.64 | 0.00 | 0.00 | ||
Maximum of Months | 195806.78 | 473618.51 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 24241.96 | 49048.27 | 25-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 24271.89 | 49077.36 | 02-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 24039.80 | 48799.17 | 02-MAR-07:57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23559.43 | 47939.95 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 23000.41 | 46882.44 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22503.34 | 45721.11 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22172.77 | 44821.11 | 05-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 22162.09 | 44770.79 | 31-AUG-06:56 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22407.25 | 45503.85 | 29-SEP-06:58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22870.82 | 46678.62 | 31-OCT-06:57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23433.92 | 47819.86 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23933.34 | 48625.69 | 28-DEC-08:00 |
Annual Sum or Average | 0.00 | 23210.38 | ||||
Minimum of Months | 0.00 | 0.00 | 22162.09 | 44770.79 | ||
Maximum of Months | 0.00 | 0.00 | 24271.89 | 49077.36 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.68 | 1299.30 | 01-JAN-09:04 | 0.89 |
February | 0.236042E+10 | 0.68 | 1299.30 | 01-FEB-00:40 | 0.89 |
March | 0.261333E+10 | 0.68 | 1299.30 | 01-MAR-00:40 | 0.89 |
April | 0.252903E+10 | 0.68 | 1299.30 | 01-APR-04:40 | 0.89 |
May | 0.261333E+10 | 0.68 | 1299.30 | 01-MAY-03:50 | 0.89 |
June | 0.252903E+10 | 0.68 | 1299.30 | 01-JUN-00:50 | 0.89 |
July | 0.261333E+10 | 0.68 | 1299.30 | 01-JUL-00:50 | 0.88 |
August | 0.261333E+10 | 0.68 | 1299.30 | 01-AUG-08:62 | 0.89 |
September | 0.252903E+10 | 0.68 | 1299.30 | 29-SEP-15:50 | 0.89 |
October | 0.261333E+10 | 0.68 | 1299.30 | 16-OCT-16:20 | 0.89 |
November | 0.252903E+10 | 0.68 | 1299.30 | 01-NOV-00:30 | 0.89 |
December | 0.261333E+10 | 0.68 | 1299.30 | 01-DEC-02:20 | 0.89 |
Annual Sum or Average | 0.307698E+11 | 0.68 | |||
Minimum of Months | 0.236042E+10 | 0.68 | 1299.30 | 0.88 | |
Maximum of Months | 0.261333E+10 | 0.68 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.440702E+11 | 1.01 | 22860.04 | 18-JAN-21:00 | 1.23 |
February | 0.397256E+11 | 1.00 | 22792.11 | 02-FEB-20:20 | 1.23 |
March | 0.439309E+11 | 1.00 | 22780.56 | 23-MAR-19:50 | 1.22 |
April | 0.427862E+11 | 1.01 | 22860.43 | 27-APR-20:00 | 1.23 |
May | 0.443340E+11 | 1.01 | 22983.49 | 04-MAY-20:20 | 1.23 |
June | 0.432649E+11 | 1.01 | 23069.76 | 27-JUN-21:10 | 1.23 |
July | 0.450086E+11 | 1.01 | 23143.52 | 19-JUL-20:30 | 1.23 |
August | 0.451570E+11 | 1.01 | 23129.90 | 17-AUG-20:30 | 1.23 |
September | 0.433387E+11 | 1.01 | 25857.42 | 29-SEP-21:20 | 1.33 |
October | 0.449880E+11 | 1.02 | 25431.54 | 16-OCT-21:52 | 1.32 |
November | 0.428257E+11 | 1.01 | 22825.54 | 01-NOV-19:40 | 1.23 |
December | 0.441478E+11 | 1.01 | 22820.19 | 18-DEC-20:30 | 1.24 |
Annual Sum or Average | 0.523578E+12 | 1.01 | |||
Minimum of Months | 0.397256E+11 | 1.00 | 22780.56 | 1.22 | |
Maximum of Months | 0.451570E+11 | 1.02 | 25857.42 | 1.33 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:05 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:05 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:10 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:05 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:10 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129757E+09 | 0.48 | 579.37 | 01-JAN-09:01 | 0.58 |
February | 0.110355E+09 | 0.46 | 579.37 | 01-FEB-09:01 | 0.59 |
March | 0.128985E+09 | 0.45 | 579.37 | 01-MAR-09:01 | 0.58 |
April | 0.170169E+09 | 0.48 | 579.37 | 01-APR-08:61 | 0.58 |
May | 0.160148E+09 | 0.46 | 579.37 | 01-MAY-08:62 | 0.58 |
June | 0.204224E+09 | 0.48 | 579.37 | 01-JUN-08:62 | 0.58 |
July | 0.275777E+09 | 0.52 | 579.37 | 01-JUL-08:61 | 0.58 |
August | 0.282037E+09 | 0.54 | 579.37 | 01-AUG-08:62 | 0.58 |
September | 0.229016E+09 | 0.52 | 579.37 | 01-SEP-08:62 | 0.58 |
October | 0.226063E+09 | 0.51 | 579.37 | 01-OCT-08:62 | 0.58 |
November | 0.130528E+09 | 0.49 | 579.37 | 01-NOV-08:61 | 0.58 |
December | 0.133336E+09 | 0.49 | 579.37 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.218040E+10 | 0.49 | |||
Minimum of Months | 0.110355E+09 | 0.45 | 579.37 | 0.58 | |
Maximum of Months | 0.282037E+09 | 0.54 | 579.37 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 94106557.42 | 0.38 | 557.33 | 02-JAN-16:12 | 0.59 |
February | 73009961.40 | 0.39 | 557.33 | 01-FEB-19:01 | 0.58 |
March | 94552632.72 | 0.39 | 557.33 | 01-MAR-19:01 | 0.58 |
April | 0.100178E+09 | 0.38 | 557.33 | 02-APR-19:02 | 0.58 |
May | 0.107513E+09 | 0.36 | 557.33 | 01-MAY-08:51 | 0.58 |
June | 0.122120E+09 | 0.32 | 557.33 | 01-JUN-08:51 | 0.58 |
July | 0.167740E+09 | 0.32 | 557.33 | 01-JUL-08:51 | 0.58 |
August | 0.157909E+09 | 0.32 | 557.33 | 01-AUG-08:51 | 0.58 |
September | 0.119961E+09 | 0.32 | 557.33 | 01-SEP-08:51 | 0.58 |
October | 0.108903E+09 | 0.32 | 557.33 | 01-OCT-08:52 | 0.58 |
November | 66526078.48 | 0.38 | 557.33 | 01-NOV-08:61 | 0.58 |
December | 83885814.02 | 0.37 | 557.33 | 01-DEC-16:13 | 0.58 |
Annual Sum or Average | 0.129641E+10 | 0.35 | |||
Minimum of Months | 66526078.48 | 0.32 | 557.33 | 0.58 | |
Maximum of Months | 0.167740E+09 | 0.39 | 557.33 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110113E+10 | 0.49 | 1481.70 | 14-JAN-12:40 | 0.59 |
February | 0.739708E+09 | 0.42 | 1078.50 | 02-FEB-12:30 | 0.58 |
March | 0.590115E+09 | 0.37 | 1001.38 | 11-MAR-13:10 | 0.59 |
April | 0.656308E+09 | 0.46 | 679.20 | 08-APR-12:50 | 0.58 |
May | 0.445933E+09 | 0.40 | 513.77 | 03-MAY-06:53 | 0.58 |
June | 0.531738E+09 | 0.46 | 532.38 | 30-JUN-06:53 | 0.58 |
July | 0.757660E+09 | 0.55 | 606.90 | 30-JUL-08:00 | 0.58 |
August | 0.963593E+09 | 0.57 | 651.29 | 30-AUG-13:00 | 0.58 |
September | 0.104936E+10 | 0.57 | 1104.33 | 30-SEP-13:05 | 0.58 |
October | 0.131687E+10 | 0.56 | 1786.16 | 31-OCT-12:30 | 0.58 |
November | 0.113085E+10 | 0.52 | 1943.51 | 19-NOV-09:53 | 0.59 |
December | 0.123680E+10 | 0.51 | 1835.46 | 25-DEC-13:30 | 0.59 |
Annual Sum or Average | 0.105201E+11 | 0.49 | |||
Minimum of Months | 0.445933E+09 | 0.37 | 513.77 | 0.58 | |
Maximum of Months | 0.131687E+10 | 0.57 | 1943.51 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.697005E+09 | 0.36 | 3404.55 | 01-JAN-09:01 | 0.58 |
February | 0.645789E+09 | 0.37 | 3404.55 | 01-FEB-09:52 | 0.59 |
March | 0.840910E+09 | 0.37 | 3404.55 | 01-MAR-09:01 | 0.59 |
April | 0.903916E+09 | 0.33 | 3404.55 | 01-APR-08:61 | 0.59 |
May | 0.105744E+10 | 0.31 | 3404.55 | 01-MAY-08:51 | 0.58 |
June | 0.110421E+10 | 0.26 | 3404.55 | 01-JUN-08:51 | 0.58 |
July | 0.133093E+10 | 0.27 | 3404.55 | 01-JUL-08:51 | 0.58 |
August | 0.120335E+10 | 0.26 | 3404.55 | 01-AUG-08:51 | 0.58 |
September | 0.951657E+09 | 0.25 | 3404.55 | 01-SEP-08:51 | 0.58 |
October | 0.952824E+09 | 0.27 | 3404.55 | 01-OCT-08:52 | 0.58 |
November | 0.689214E+09 | 0.34 | 3404.55 | 01-NOV-08:61 | 0.58 |
December | 0.616665E+09 | 0.35 | 3404.55 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.109939E+11 | 0.31 | |||
Minimum of Months | 0.616665E+09 | 0.25 | 3404.55 | 0.58 | |
Maximum of Months | 0.133093E+10 | 0.37 | 3404.55 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130724E+09 | 0.49 | 516.81 | 01-JAN-09:01 | 0.58 |
February | 0.106129E+09 | 0.47 | 516.81 | 01-FEB-09:01 | 0.59 |
March | 0.125736E+09 | 0.45 | 516.81 | 01-MAR-09:01 | 0.58 |
April | 0.152727E+09 | 0.51 | 516.81 | 01-APR-08:61 | 0.58 |
May | 0.136472E+09 | 0.48 | 516.81 | 01-MAY-08:62 | 0.58 |
June | 0.169793E+09 | 0.50 | 516.81 | 01-JUN-08:62 | 0.58 |
July | 0.246658E+09 | 0.54 | 516.81 | 01-JUL-08:61 | 0.58 |
August | 0.264887E+09 | 0.55 | 516.81 | 01-AUG-08:62 | 0.58 |
September | 0.196228E+09 | 0.52 | 516.81 | 01-SEP-08:62 | 0.58 |
October | 0.211619E+09 | 0.52 | 516.81 | 01-OCT-08:62 | 0.58 |
November | 0.125304E+09 | 0.49 | 516.81 | 01-NOV-08:61 | 0.58 |
December | 0.133754E+09 | 0.49 | 516.81 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.200003E+10 | 0.50 | |||
Minimum of Months | 0.106129E+09 | 0.45 | 516.81 | 0.58 | |
Maximum of Months | 0.264887E+09 | 0.55 | 516.81 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 89845768.17 | 0.36 | 498.08 | 01-JAN-09:01 | 0.58 |
February | 74991368.09 | 0.37 | 498.08 | 01-FEB-09:52 | 0.59 |
March | 95378776.81 | 0.39 | 498.08 | 01-MAR-09:01 | 0.58 |
April | 97931726.76 | 0.40 | 498.08 | 01-APR-08:61 | 0.58 |
May | 98809622.70 | 0.37 | 498.08 | 01-MAY-08:51 | 0.58 |
June | 0.113397E+09 | 0.33 | 498.08 | 01-JUN-08:51 | 0.58 |
July | 0.163674E+09 | 0.34 | 498.08 | 01-JUL-08:51 | 0.58 |
August | 0.161294E+09 | 0.34 | 498.08 | 01-AUG-08:51 | 0.58 |
September | 0.105126E+09 | 0.33 | 498.08 | 01-SEP-08:51 | 0.58 |
October | 0.102069E+09 | 0.33 | 498.08 | 01-OCT-08:52 | 0.58 |
November | 67084412.06 | 0.35 | 498.08 | 01-NOV-08:61 | 0.58 |
December | 81549819.58 | 0.35 | 498.08 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.125115E+10 | 0.35 | |||
Minimum of Months | 67084412.06 | 0.33 | 498.08 | 0.58 | |
Maximum of Months | 0.163674E+09 | 0.40 | 498.08 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 36144554.51 | 0.48 | 150.47 | 02-JAN-16:12 | 0.59 |
February | 31757042.27 | 0.46 | 150.47 | 01-FEB-09:01 | 0.59 |
March | 37854947.60 | 0.45 | 150.47 | 01-MAR-16:11 | 0.58 |
April | 44298746.75 | 0.50 | 150.47 | 01-APR-15:12 | 0.59 |
May | 41093149.79 | 0.48 | 150.47 | 01-MAY-08:62 | 0.58 |
June | 52281414.52 | 0.50 | 150.47 | 01-JUN-15:11 | 0.58 |
July | 71945444.43 | 0.54 | 150.47 | 01-JUL-08:61 | 0.58 |
August | 72543494.39 | 0.54 | 150.47 | 01-AUG-08:62 | 0.58 |
September | 56192343.97 | 0.52 | 150.47 | 01-SEP-08:62 | 0.58 |
October | 54237594.79 | 0.51 | 150.47 | 01-OCT-08:62 | 0.58 |
November | 32965655.70 | 0.48 | 150.47 | 01-NOV-08:61 | 0.58 |
December | 36655695.46 | 0.48 | 150.47 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.567970E+09 | 0.49 | |||
Minimum of Months | 31757042.27 | 0.45 | 150.47 | 0.58 | |
Maximum of Months | 72543494.39 | 0.54 | 150.47 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 32575341.91 | 0.37 | 144.39 | 01-JAN-09:01 | 0.58 |
February | 25294055.68 | 0.39 | 144.39 | 01-FEB-19:01 | 0.58 |
March | 30255097.81 | 0.40 | 144.39 | 01-MAR-09:01 | 0.58 |
April | 26016611.63 | 0.39 | 144.39 | 02-APR-19:02 | 0.58 |
May | 27394578.91 | 0.37 | 144.39 | 01-MAY-08:51 | 0.58 |
June | 32900566.30 | 0.33 | 144.39 | 01-JUN-08:51 | 0.58 |
July | 47473416.38 | 0.33 | 144.39 | 01-JUL-08:51 | 0.58 |
August | 43396051.65 | 0.33 | 144.39 | 01-AUG-08:51 | 0.58 |
September | 29385989.13 | 0.33 | 144.39 | 01-SEP-08:51 | 0.58 |
October | 25859374.26 | 0.32 | 144.39 | 01-OCT-08:52 | 0.58 |
November | 21433705.69 | 0.38 | 144.39 | 01-NOV-08:61 | 0.58 |
December | 29648740.78 | 0.37 | 144.39 | 02-DEC-16:11 | 0.58 |
Annual Sum or Average | 0.371634E+09 | 0.36 | |||
Minimum of Months | 21433705.69 | 0.32 | 144.39 | 0.58 | |
Maximum of Months | 47473416.38 | 0.40 | 144.39 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.331774E+09 | 0.52 | 717.45 | 01-JAN-09:01 | 0.58 |
February | 0.231438E+09 | 0.49 | 717.45 | 01-FEB-09:01 | 0.59 |
March | 0.218755E+09 | 0.47 | 717.45 | 01-MAR-09:01 | 0.58 |
April | 0.217091E+09 | 0.50 | 717.45 | 01-APR-08:61 | 0.59 |
May | 0.155075E+09 | 0.46 | 717.45 | 01-MAY-08:62 | 0.58 |
June | 0.178090E+09 | 0.47 | 717.45 | 01-JUN-08:62 | 0.58 |
July | 0.260381E+09 | 0.51 | 717.45 | 01-JUL-08:61 | 0.58 |
August | 0.319770E+09 | 0.53 | 717.45 | 01-AUG-08:62 | 0.58 |
September | 0.318267E+09 | 0.51 | 717.45 | 01-SEP-08:62 | 0.58 |
October | 0.402419E+09 | 0.52 | 717.45 | 01-OCT-08:62 | 0.58 |
November | 0.321027E+09 | 0.53 | 717.45 | 01-NOV-08:61 | 0.58 |
December | 0.352219E+09 | 0.53 | 717.45 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.330631E+10 | 0.50 | |||
Minimum of Months | 0.155075E+09 | 0.46 | 717.45 | 0.58 | |
Maximum of Months | 0.402419E+09 | 0.53 | 717.45 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.209213E+09 | 0.190175E+09 | 493.55 | 08-JAN-06:50 | 448.64 | 448.64 | 37.64 | 1.12 |
February | 0.136260E+09 | 0.123860E+09 | 388.36 | 05-FEB-06:00 | 353.02 | 353.02 | 35.58 | 0.62 |
March | 0.204942E+09 | 0.186292E+09 | 455.71 | 30-MAR-03:00 | 414.24 | 414.24 | 36.47 | 0.87 |
April | 64231785.33 | 58386692.86 | 294.78 | 01-APR-06:00 | 267.96 | 267.96 | 35.40 | 0.40 |
May | 60057200.91 | 54591995.62 | 235.97 | 14-MAY-04:50 | 214.50 | 214.50 | 33.98 | 0.30 |
June | 12512140.41 | 11373535.63 | 144.54 | 02-JUN-08:54 | 131.39 | 131.39 | 36.85 | 0.17 |
July | 2449158.77 | 2226285.32 | 108.92 | 09-JUL-21:57 | 99.01 | 99.01 | 29.35 | 0.12 |
August | 884400.57 | 803920.12 | 125.15 | 22-AUG-08:54 | 113.76 | 113.76 | 35.29 | 0.14 |
September | 5354029.60 | 4866812.91 | 152.03 | 20-SEP-08:54 | 138.20 | 138.20 | 42.38 | 0.18 |
October | 21019354.22 | 19106592.99 | 153.27 | 13-OCT-08:54 | 139.33 | 139.33 | 41.59 | 0.18 |
November | 99626976.01 | 90560921.19 | 291.85 | 24-NOV-04:00 | 265.30 | 265.30 | 34.63 | 0.39 |
December | 0.182058E+09 | 0.165491E+09 | 399.85 | 24-DEC-04:00 | 363.46 | 363.46 | 35.74 | 0.65 |
Annual Sum or Average | 0.998609E+09 | 0.907735E+09 | ||||||
Minimum of Months | 884400.57 | 803920.12 | 108.92 | 99.01 | 99.01 | 29.35 | 0.12 | |
Maximum of Months | 0.209213E+09 | 0.190175E+09 | 493.55 | 448.64 | 448.64 | 42.38 | 1.12 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 86388086.15 | 78526770.31 | 579.52 | 24-JAN-09:51 | 526.79 | 526.79 | 6.72 | 9.32 |
February | 48636180.86 | 44210288.40 | 335.07 | 01-FEB-13:10 | 304.58 | 304.58 | 6.72 | 7.35 |
March | 54794759.42 | 49808436.32 | 556.45 | 11-MAR-11:35 | 505.81 | 505.81 | 6.72 | 9.16 |
April | 0.108909E+09 | 98998465.50 | 496.86 | 13-APR-08:53 | 451.65 | 451.65 | 6.72 | 8.73 |
May | 0.104940E+09 | 95390299.43 | 261.08 | 03-MAY-09:50 | 237.33 | 237.33 | 6.72 | 6.58 |
June | 0.184387E+09 | 0.167608E+09 | 702.55 | 29-JUN-18:03 | 638.62 | 638.62 | 6.72 | 10.12 |
July | 0.455262E+09 | 0.413833E+09 | 1047.68 | 18-JUL-18:03 | 952.34 | 952.34 | 6.72 | 11.95 |
August | 0.531781E+09 | 0.483389E+09 | 924.99 | 17-AUG-15:23 | 840.82 | 840.82 | 6.72 | 11.35 |
September | 0.326711E+09 | 0.296980E+09 | 1499.94 | 29-SEP-15:13 | 1363.45 | 1363.45 | 6.72 | 13.84 |
October | 0.352796E+09 | 0.320692E+09 | 1454.38 | 17-OCT-10:50 | 1322.03 | 1322.03 | 6.72 | 13.67 |
November | 92831445.89 | 84383784.31 | 727.83 | 19-NOV-10:40 | 661.60 | 661.60 | 6.72 | 10.27 |
December | 81701182.76 | 74266375.13 | 504.90 | 16-DEC-11:50 | 458.96 | 458.96 | 6.72 | 8.79 |
Annual Sum or Average | 0.242914E+10 | 0.220809E+10 | ||||||
Minimum of Months | 48636180.86 | 44210288.40 | 261.08 | 237.33 | 237.33 | 6.72 | 6.58 | |
Maximum of Months | 0.531781E+09 | 0.483389E+09 | 1499.94 | 1363.45 | 1363.45 | 6.72 | 13.84 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.503579E+10 | 0.457753E+10 | 2026.15 | 01-JAN-00:05 | 1841.77 | 1841.77 | 6.76 | 18.10 |
February | 0.467250E+10 | 0.424730E+10 | 2026.15 | 01-FEB-00:05 | 1841.77 | 1841.77 | 6.87 | 18.10 |
March | 0.487309E+10 | 0.442964E+10 | 2026.15 | 01-MAR-00:05 | 1841.77 | 1841.77 | 6.72 | 18.10 |
April | 0.520315E+10 | 0.472966E+10 | 2026.15 | 01-APR-00:10 | 1841.77 | 1841.77 | 6.76 | 18.10 |
May | 0.542116E+10 | 0.492783E+10 | 2026.15 | 01-MAY-00:10 | 1841.77 | 1841.77 | 7.34 | 18.10 |
June | 0.525177E+10 | 0.477386E+10 | 2026.15 | 01-JUN-00:10 | 1841.77 | 1841.77 | 6.99 | 18.10 |
July | 0.542683E+10 | 0.493299E+10 | 2026.15 | 01-JUL-00:10 | 1841.77 | 1841.77 | 8.09 | 18.10 |
August | 0.542683E+10 | 0.493299E+10 | 2026.15 | 01-AUG-00:10 | 1841.77 | 1841.77 | 9.07 | 18.10 |
September | 0.525177E+10 | 0.477386E+10 | 2026.15 | 01-SEP-00:10 | 1841.77 | 1841.77 | 7.61 | 18.10 |
October | 0.542683E+10 | 0.493299E+10 | 2026.15 | 01-OCT-00:10 | 1841.77 | 1841.77 | 9.37 | 18.10 |
November | 0.521895E+10 | 0.474403E+10 | 2026.15 | 01-NOV-00:10 | 1841.77 | 1841.77 | 7.20 | 18.10 |
December | 0.517275E+10 | 0.470203E+10 | 2026.15 | 01-DEC-00:05 | 1841.77 | 1841.77 | 6.92 | 18.10 |
Annual Sum or Average | 0.623814E+11 | 0.567047E+11 | ||||||
Minimum of Months | 0.467250E+10 | 0.424730E+10 | 2026.15 | 1841.77 | 1841.77 | 6.72 | 18.10 | |
Maximum of Months | 0.542683E+10 | 0.493299E+10 | 2026.15 | 1841.77 | 1841.77 | 9.37 | 18.10 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 49.80 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 50.10 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 49.98 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.97 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 52.61 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.02 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.96 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.32 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.04 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.66 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.82 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 50.50 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.80 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.32 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 39.05 | 60.00 | 9519.83 | 105027.53 | 08-JAN-06:50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 43.70 | 60.00 | 5136.68 | 62931.15 | 05-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 34.58 | 60.00 | 8446.76 | 85420.26 | 30-MAR-03:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 41.28 | 60.00 | 1979.22 | 41150.14 | 01-APR-06:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 37.01 | 37.01 | 1993.68 | 32398.67 | 14-MAY-04:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 39.10 | 60.00 | 498.41 | 16917.20 | 23-JUN-08:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.07 | 29.07 | 122.74 | 15753.65 | 12-JUL-08:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.07 | 28.07 | 39.24 | 14614.37 | 22-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 37.92 | 37.92 | 184.92 | 16351.90 | 28-SEP-08:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 36.57 | 36.57 | 656.77 | 17916.22 | 30-OCT-04:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 41.10 | 41.10 | 3600.97 | 41857.36 | 24-NOV-04:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 44.40 | 60.00 | 7604.01 | 66002.70 | 24-DEC-04:00 |
Annual Sum or Average | 0.00 | 3319.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.07 | 28.07 | 39.24 | 14614.37 | ||
Maximum of Months | 0.00 | 0.00 | 44.40 | 60.00 | 9519.83 | 105027.53 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 47156.06 | 300749.24 | 15-JAN-09:52 | 10.66 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 35621.77 | 296599.11 | 01-FEB-09:52 | 10.61 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 33089.96 | 280834.78 | 11-MAR-09:51 | 10.40 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 62151.44 | 273061.23 | 26-APR-08:52 | 10.30 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 61162.71 | 210204.64 | 04-MAY-08:53 | 9.47 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 101191.17 | 385735.94 | 29-JUN-18:03 | 11.79 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 175953.99 | 473618.51 | 18-JUL-18:03 | 12.95 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 195806.78 | 472435.42 | 18-AUG-15:13 | 12.93 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 133303.56 | 454374.53 | 21-SEP-21:52 | 12.69 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 139706.31 | 430173.18 | 14-OCT-15:13 | 12.37 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 52447.80 | 344850.88 | 19-NOV-09:41 | 11.25 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 52263.84 | 337048.92 | 05-DEC-09:41 | 11.14 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 91313.86 | 0.00 | ||||||
Minimum of Months | 33089.96 | 210204.64 | 9.47 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 195806.78 | 473618.51 | 12.95 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 49.80 | 59.74 | 24241.96 | 49048.27 | 25-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 50.10 | 58.85 | 24271.89 | 49077.36 | 02-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 49.98 | 58.33 | 24039.80 | 48799.17 | 02-MAR-07:57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.97 | 59.48 | 23559.43 | 47939.95 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.61 | 58.71 | 23000.41 | 46882.44 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.02 | 58.90 | 22503.34 | 45721.11 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.96 | 58.68 | 22172.77 | 44821.11 | 05-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.32 | 59.16 | 22162.09 | 44770.79 | 31-AUG-06:56 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.04 | 58.76 | 22407.25 | 45503.85 | 29-SEP-06:58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.66 | 59.63 | 22870.82 | 46678.62 | 31-OCT-06:57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.82 | 58.81 | 23433.92 | 47819.86 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.50 | 58.80 | 23933.34 | 48625.69 | 28-DEC-08:00 |
Annual Sum or Average | 0.00 | 23210.38 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.80 | 58.33 | 22162.09 | 44770.79 | ||
Maximum of Months | 0.00 | 0.00 | 53.32 | 59.74 | 24271.89 | 49077.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.143629E+11 | 0.00 | 0.635778E+11 | 0.440702E+11 | 0.00 | 0.00 |
February | 0.459102E+10 | 0.00 | 0.370519E+11 | 0.397256E+11 | 0.00 | 0.00 |
March | 0.114610E+11 | 0.00 | 0.406657E+11 | 0.439309E+11 | 0.00 | 0.00 |
April | 0.825822E+09 | 0.00 | 0.938925E+11 | 0.427862E+11 | 0.00 | 0.00 |
May | 0.153449E+10 | 0.00 | 0.101448E+12 | 0.443340E+11 | 0.00 | 0.00 |
June | 0.614620E+09 | 0.00 | 0.181973E+12 | 0.432649E+11 | 0.00 | 0.00 |
July | 0.267583E+09 | 0.00 | 0.352194E+12 | 0.450086E+11 | 0.00 | 0.00 |
August | 56786203.80 | 0.00 | 0.394523E+12 | 0.451570E+11 | 0.00 | 0.00 |
September | 0.108605E+09 | 0.00 | 0.241359E+12 | 0.433387E+11 | 0.00 | 0.00 |
October | 0.250067E+09 | 0.00 | 0.263710E+12 | 0.449880E+11 | 0.00 | 0.00 |
November | 0.300441E+10 | 0.00 | 0.671881E+11 | 0.428257E+11 | 0.00 | 0.00 |
December | 0.102758E+11 | 0.00 | 0.725422E+11 | 0.441478E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.473531E+11 | 0.00 | 0.191012E+13 | 0.523578E+12 | 0.00 | 0.00 |
Minimum of Months | 56786203.80 | 0.00 | 0.370519E+11 | 0.397256E+11 | 0.00 | 0.00 |
Maximum of Months | 0.143629E+11 | 0.00 | 0.394523E+12 | 0.451570E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.781976E+10 | 0.00 | 0.325706E+10 | 0.261333E+10 | 0.00 | 0.00 |
February | 0.630484E+10 | 0.00 | 0.176477E+10 | 0.236042E+10 | 0.00 | 0.00 |
March | 0.841655E+10 | 0.00 | 0.195362E+10 | 0.261333E+10 | 0.00 | 0.00 |
April | 0.400991E+10 | 0.00 | 0.490019E+10 | 0.252903E+10 | 0.00 | 0.00 |
May | 0.358791E+10 | 0.00 | 0.520930E+10 | 0.261333E+10 | 0.00 | 0.00 |
June | 0.637781E+09 | 0.00 | 0.118877E+11 | 0.252903E+10 | 0.00 | 0.00 |
July | 37023292.77 | 0.00 | 0.270221E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 16923290.42 | 0.00 | 0.309007E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 0.317076E+09 | 0.00 | 0.175428E+11 | 0.252903E+10 | 0.00 | 0.00 |
October | 0.142155E+10 | 0.00 | 0.195118E+11 | 0.261333E+10 | 0.00 | 0.00 |
November | 0.557451E+10 | 0.00 | 0.327790E+10 | 0.252903E+10 | 0.00 | 0.00 |
December | 0.786357E+10 | 0.00 | 0.398719E+10 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.460074E+11 | 0.00 | 0.131215E+12 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 16923290.42 | 0.00 | 0.176477E+10 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841655E+10 | 0.00 | 0.309007E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.440702E+11 | 0.635778E+11 | 0.143629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397256E+11 | 0.370519E+11 | 0.459102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.439309E+11 | 0.406657E+11 | 0.114610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.427862E+11 | 0.938925E+11 | 0.825822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.443340E+11 | 0.101448E+12 | 0.153449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.432649E+11 | 0.181973E+12 | 0.614620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.450086E+11 | 0.352194E+12 | 0.267583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.451570E+11 | 0.394523E+12 | 56786203.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.433387E+11 | 0.241359E+12 | 0.108605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.449880E+11 | 0.263710E+12 | 0.250067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428257E+11 | 0.671881E+11 | 0.300441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.441478E+11 | 0.725422E+11 | 0.102758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.523578E+12 | 0.191012E+13 | 0.473531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.397256E+11 | 0.370519E+11 | 56786203.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.451570E+11 | 0.394523E+12 | 0.143629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.325706E+10 | 0.781976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.176477E+10 | 0.630484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.195362E+10 | 0.841655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.490019E+10 | 0.400991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.520930E+10 | 0.358791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.118877E+11 | 0.637781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.270221E+11 | 37023292.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.309007E+11 | 16923290.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.175428E+11 | 0.317076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.195118E+11 | 0.142155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.327790E+10 | 0.557451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.398719E+10 | 0.786357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.131215E+12 | 0.460074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.176477E+10 | 16923290.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.309007E+11 | 0.841655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.440702E+11 | 0.143629E+11 | 0.635778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397256E+11 | 0.459102E+10 | 0.370519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.439309E+11 | 0.114610E+11 | 0.406657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.427862E+11 | 0.825822E+09 | 0.938925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.443340E+11 | 0.153449E+10 | 0.101448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.432649E+11 | 0.614620E+09 | 0.181973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.450086E+11 | 0.267583E+09 | 0.352194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.451570E+11 | 56786203.80 | 0.394523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.433387E+11 | 0.108605E+09 | 0.241359E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.449880E+11 | 0.250067E+09 | 0.263710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428257E+11 | 0.300441E+10 | 0.671881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.441478E+11 | 0.102758E+11 | 0.725422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.523578E+12 | 0.473531E+11 | 0.191012E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.397256E+11 | 56786203.80 | 0.370519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.451570E+11 | 0.143629E+11 | 0.394523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.781976E+10 | 0.325706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.630484E+10 | 0.176477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.841655E+10 | 0.195362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.400991E+10 | 0.490019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.358791E+10 | 0.520930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.637781E+09 | 0.118877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 37023292.77 | 0.270221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 16923290.42 | 0.309007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.317076E+09 | 0.175428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.142155E+10 | 0.195118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.557451E+10 | 0.327790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.786357E+10 | 0.398719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.460074E+11 | 0.131215E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 16923290.42 | 0.176477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.841655E+10 | 0.309007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.411353E+11 | 0.00 | 0.00 | 0.00 | 35246951.88 | 0.00 | 0.00 | 0.00 | 0.80 |
February | 0.376847E+11 | 0.00 | 0.00 | 0.00 | 9852882.39 | 0.00 | 0.00 | 0.00 | 0.83 |
March | 0.420464E+11 | 0.00 | 0.00 | 0.00 | 631907.41 | 0.00 | 0.00 | 0.00 | 0.80 |
April | 0.355536E+11 | 0.00 | 0.00 | 0.00 | 40463929.76 | 0.00 | 0.00 | 0.00 | 0.86 |
May | 0.363245E+11 | 0.00 | 0.00 | 0.00 | 7820961.15 | 0.00 | 0.00 | 0.00 | 0.89 |
June | 0.285006E+11 | 0.00 | 0.00 | 0.00 | 0.452298E+09 | 0.00 | 0.00 | 0.00 | 0.92 |
July | 0.183279E+11 | 0.00 | 0.00 | 0.00 | 0.344475E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
August | 0.154921E+11 | 0.00 | 0.00 | 0.00 | 0.420833E+10 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 0.247920E+11 | 0.00 | 0.00 | 0.00 | 0.137162E+10 | 0.00 | 0.00 | 0.00 | 0.94 |
October | 0.245705E+11 | 0.00 | 0.00 | 76874.21 | 0.221781E+10 | 0.00 | 0.891468E+09 | 0.00 | 0.89 |
November | 0.361935E+11 | 0.00 | 0.00 | 373851.89 | 17412277.26 | 0.00 | 0.260894E+10 | 0.00 | 0.85 |
December | 0.400025E+11 | 0.00 | 0.00 | 26075.58 | 11594793.63 | 0.00 | 0.169740E+09 | 0.00 | 0.80 |
Annual Sum or Average | 0.380624E+12 | 0.00 | 0.00 | 476801.68 | 0.118178E+11 | 0.00 | 0.367015E+10 | 0.00 | 0.86 |
Minimum of Months | 0.154921E+11 | 0.00 | 0.00 | 0.00 | 631907.41 | 0.00 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.420464E+11 | 0.00 | 0.00 | 373851.89 | 0.420833E+10 | 0.00 | 0.260894E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.319388E+10 | 5627426.72 | 0.00 | 2020341.34 | 118885.23 | 0.00 | 0.779113E+09 | 0.00 | 1.47 |
February | 0.301527E+10 | 1504310.64 | 0.00 | 1344332.77 | 0.00 | 0.00 | 0.557919E+09 | 0.00 | 1.47 |
March | 0.366061E+10 | 58660.67 | 0.00 | 704575.11 | 0.00 | 0.00 | 0.252671E+09 | 0.00 | 1.36 |
April | 0.305327E+10 | 3054090.97 | 0.00 | 463512.26 | 716833.11 | 0.00 | 0.247956E+09 | 0.00 | 1.46 |
May | 0.331345E+10 | 210127.89 | 0.00 | 64579.53 | 515900.64 | 0.00 | 58528709.40 | 0.00 | 1.50 |
June | 0.258281E+10 | 3254457.98 | 0.00 | 20511.88 | 38732887.94 | 0.00 | 62905461.98 | 0.00 | 1.56 |
July | 0.155020E+10 | 0.178707E+09 | 0.00 | 155921.04 | 0.141210E+09 | 0.00 | 0.151043E+09 | 0.00 | 1.52 |
August | 0.105221E+10 | 0.306791E+09 | 0.00 | 615108.21 | 97761963.89 | 0.00 | 0.385658E+09 | 0.00 | 1.50 |
September | 0.170014E+10 | 0.121854E+09 | 0.00 | 1552652.36 | 41908990.92 | 0.00 | 0.620366E+09 | 0.00 | 1.65 |
October | 0.157038E+10 | 0.264346E+09 | 0.00 | 2340430.87 | 40963236.46 | 0.00 | 0.848671E+09 | 0.00 | 1.66 |
November | 0.289422E+10 | 3101319.85 | 0.00 | 2217140.10 | 0.00 | 0.00 | 0.847037E+09 | 0.00 | 1.56 |
December | 0.303057E+10 | 2044422.13 | 0.00 | 2795236.14 | 0.00 | 0.00 | 0.854353E+09 | 0.00 | 1.52 |
Annual Sum or Average | 0.306170E+11 | 0.890552E+09 | 0.00 | 14294341.60 | 0.361929E+09 | 0.00 | 0.566622E+10 | 0.00 | 1.52 |
Minimum of Months | 0.105221E+10 | 58660.67 | 0.00 | 20511.88 | 0.00 | 0.00 | 58528709.40 | 0.00 | 1.36 |
Maximum of Months | 0.366061E+10 | 0.306791E+09 | 0.00 | 2795236.14 | 0.141210E+09 | 0.00 | 0.854353E+09 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.439497E+10 | 0.00 | 0.00 | 1923.92 | 3785665.59 | 0.00 | 23132406.38 | 0.00 | 1.34 |
February | 0.400342E+10 | 0.00 | 0.00 | 4844.93 | 1058239.53 | 0.00 | 44071750.20 | 0.00 | 1.39 |
March | 0.448999E+10 | 0.00 | 0.00 | 3456.72 | 67869.42 | 0.00 | 25958233.29 | 0.00 | 1.34 |
April | 0.369488E+10 | 0.00 | 0.00 | 22721.22 | 4345990.17 | 0.00 | 0.123702E+09 | 0.00 | 1.45 |
May | 0.383966E+10 | 0.00 | 0.00 | 13467.26 | 840002.95 | 0.00 | 61721680.46 | 0.00 | 1.50 |
June | 0.290269E+10 | 0.00 | 0.00 | 53469.63 | 48578661.76 | 0.00 | 0.158331E+09 | 0.00 | 1.56 |
July | 0.170258E+10 | 5107033.83 | 0.00 | 174154.15 | 0.364873E+09 | 0.00 | 0.265735E+09 | 0.00 | 1.52 |
August | 0.124686E+10 | 3434662.78 | 0.00 | 316621.54 | 0.448557E+09 | 0.00 | 0.416735E+09 | 0.00 | 1.49 |
September | 0.228667E+10 | 4560016.16 | 0.00 | 212724.50 | 0.142757E+09 | 0.00 | 0.375953E+09 | 0.00 | 1.58 |
October | 0.220858E+10 | 8683904.72 | 0.00 | 327631.13 | 0.229518E+09 | 0.00 | 0.526650E+09 | 0.00 | 1.49 |
November | 0.405917E+10 | 0.00 | 0.00 | 12337.61 | 1870149.20 | 0.00 | 0.108398E+09 | 0.00 | 1.43 |
December | 0.422904E+10 | 0.00 | 0.00 | 12017.67 | 1245327.86 | 0.00 | 85618053.53 | 0.00 | 1.35 |
Annual Sum or Average | 0.390585E+11 | 21785617.49 | 0.00 | 1155370.27 | 0.124750E+10 | 0.00 | 0.221600E+10 | 0.00 | 1.45 |
Minimum of Months | 0.124686E+10 | 0.00 | 0.00 | 1923.92 | 67869.42 | 0.00 | 23132406.38 | 0.00 | 1.34 |
Maximum of Months | 0.448999E+10 | 8683904.72 | 0.00 | 327631.13 | 0.448557E+09 | 0.00 | 0.526650E+09 | 0.00 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46586393.22 | 77402.92 | 0.00 | 363202.48 | 42230.54 | 0.00 | 0.182914E+09 | 0.00 | 0.04 |
February | 47250227.42 | 0.00 | 0.00 | 205673.57 | 15636.93 | 0.00 | 0.133679E+09 | 0.00 | 0.03 |
March | 55252938.37 | 0.00 | 0.00 | 181956.62 | 1002.86 | 0.00 | 0.113932E+09 | 0.00 | 0.02 |
April | 28343193.97 | 207227.15 | 0.00 | 670657.25 | 19891.90 | 0.00 | 0.311946E+09 | 0.00 | 0.06 |
May | 18129300.11 | 61572.46 | 0.00 | 1034402.10 | 0.00 | 0.00 | 0.449260E+09 | 0.00 | 0.08 |
June | 1049509.49 | 8267046.06 | 0.00 | 1952312.00 | 0.00 | 0.00 | 0.676025E+09 | 0.00 | 0.15 |
July | 0.00 | 91146281.93 | 0.00 | 2238802.52 | 0.00 | 0.00 | 0.590269E+09 | 0.00 | 0.21 |
August | 0.00 | 0.100136E+09 | 0.00 | 1958366.15 | 0.00 | 0.00 | 0.497014E+09 | 0.00 | 0.21 |
September | 306474.65 | 32435459.74 | 0.00 | 1808844.62 | 0.00 | 0.00 | 0.600280E+09 | 0.00 | 0.17 |
October | 1734732.75 | 74301144.73 | 0.00 | 1746282.36 | 0.00 | 0.00 | 0.628042E+09 | 0.00 | 0.18 |
November | 33053170.27 | 174574.06 | 0.00 | 542472.30 | 2725.68 | 0.00 | 0.309450E+09 | 0.00 | 0.05 |
December | 44527501.40 | 100839.18 | 0.00 | 379768.99 | 3291.31 | 0.00 | 0.204965E+09 | 0.00 | 0.04 |
Annual Sum or Average | 0.276233E+09 | 0.306908E+09 | 0.00 | 13082740.95 | 84779.23 | 0.00 | 0.469777E+10 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 181956.62 | 0.00 | 0.00 | 0.113932E+09 | 0.00 | 0.02 |
Maximum of Months | 55252938.37 | 0.100136E+09 | 0.00 | 2238802.52 | 42230.54 | 0.00 | 0.676025E+09 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278225E+10 | 0.00 | 0.00 | 0.00 | 2383981.10 | 0.00 | 0.00 | 0.00 | 0.69 |
February | 0.254886E+10 | 0.00 | 0.00 | 0.00 | 666414.66 | 0.00 | 0.00 | 0.00 | 0.72 |
March | 0.284387E+10 | 0.00 | 0.00 | 0.00 | 42740.02 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 0.240472E+10 | 0.00 | 0.00 | 0.00 | 2736839.32 | 0.00 | 0.00 | 0.00 | 0.75 |
May | 0.245686E+10 | 0.00 | 0.00 | 0.00 | 528982.58 | 0.00 | 0.00 | 0.00 | 0.77 |
June | 0.192768E+10 | 0.00 | 0.00 | 0.00 | 30591875.80 | 0.00 | 0.00 | 0.00 | 0.80 |
July | 0.123964E+10 | 0.00 | 0.00 | 0.00 | 0.232991E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
August | 0.104783E+10 | 0.00 | 0.00 | 0.00 | 0.284637E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 0.167684E+10 | 0.00 | 0.00 | 0.00 | 92771566.39 | 0.00 | 0.00 | 0.00 | 0.81 |
October | 0.172216E+10 | 0.00 | 0.00 | 0.00 | 0.150005E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
November | 0.262449E+10 | 0.00 | 0.00 | 0.00 | 1177705.81 | 0.00 | 0.00 | 0.00 | 0.73 |
December | 0.271711E+10 | 0.00 | 0.00 | 0.00 | 784231.47 | 0.00 | 0.00 | 0.00 | 0.69 |
Annual Sum or Average | 0.259923E+11 | 0.00 | 0.00 | 0.00 | 0.799317E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
Minimum of Months | 0.104783E+10 | 0.00 | 0.00 | 0.00 | 42740.02 | 0.00 | 0.00 | 0.00 | 0.69 |
Maximum of Months | 0.284387E+10 | 0.00 | 0.00 | 0.00 | 0.284637E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 39000700.81 | 0.00 | 0.110703E+09 | 0.00 | 0.00 | 0.567515E+11 | 0.00 | 17.05 |
February | 0.00 | 10449825.25 | 0.00 | 97894440.58 | 0.00 | 0.00 | 0.521086E+11 | 0.00 | 17.66 |
March | 0.00 | 634300.65 | 0.00 | 0.107229E+09 | 0.00 | 0.00 | 0.578664E+11 | 0.00 | 16.98 |
April | 0.00 | 42571884.20 | 0.00 | 0.116013E+09 | 0.00 | 0.00 | 0.500236E+11 | 0.00 | 18.65 |
May | 0.00 | 8198684.27 | 0.00 | 0.123978E+09 | 0.00 | 0.00 | 0.510422E+11 | 0.00 | 19.30 |
June | 0.00 | 0.506987E+09 | 0.00 | 0.120391E+09 | 0.00 | 0.00 | 0.400388E+11 | 0.00 | 20.07 |
July | 0.00 | 0.420652E+10 | 0.00 | 98844951.09 | 0.00 | 0.00 | 0.247905E+11 | 0.00 | 19.61 |
August | 0.00 | 0.500102E+10 | 0.00 | 85911609.67 | 0.00 | 0.00 | 0.211284E+11 | 0.00 | 19.43 |
September | 0.00 | 0.160906E+10 | 0.00 | 0.105649E+09 | 0.00 | 0.00 | 0.344143E+11 | 0.00 | 20.17 |
October | 0.00 | 0.274255E+10 | 0.00 | 98274851.24 | 0.00 | 0.00 | 0.358701E+11 | 0.00 | 19.39 |
November | 0.00 | 19066210.61 | 0.00 | 0.108864E+09 | 0.00 | 0.00 | 0.543679E+11 | 0.00 | 18.36 |
December | 0.00 | 13096109.67 | 0.00 | 0.111620E+09 | 0.00 | 0.00 | 0.558257E+11 | 0.00 | 17.14 |
Annual Sum or Average | 0.00 | 0.141992E+11 | 0.00 | 0.128537E+10 | 0.00 | 0.00 | 0.534228E+12 | 0.00 | 18.65 |
Minimum of Months | 0.00 | 634300.65 | 0.00 | 85911609.67 | 0.00 | 0.00 | 0.211284E+11 | 0.00 | 16.98 |
Maximum of Months | 0.00 | 0.500102E+10 | 0.00 | 0.123978E+09 | 0.00 | 0.00 | 0.578664E+11 | 0.00 | 20.17 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155937E+11 | 23217606.75 | 0.00 | 5114053.25 | 4701226.62 | 0.00 | 0.169842E+11 | 0.00 | 4.08 |
February | 0.166322E+11 | 6306412.36 | 0.00 | 3391278.27 | 1497978.29 | 0.00 | 0.132142E+11 | 0.00 | 4.22 |
March | 0.227112E+11 | 0.00 | 0.00 | 2088907.78 | 500528.89 | 0.00 | 0.105913E+11 | 0.00 | 4.07 |
April | 0.166243E+11 | 0.00 | 0.00 | 2601152.39 | 32051160.52 | 0.00 | 0.115349E+11 | 0.00 | 4.40 |
May | 0.173639E+11 | 0.00 | 0.00 | 2182832.99 | 6194921.82 | 0.00 | 0.114063E+11 | 0.00 | 4.55 |
June | 0.117992E+11 | 0.00 | 0.00 | 3113919.77 | 0.358262E+09 | 0.00 | 0.107728E+11 | 0.00 | 4.71 |
July | 0.605337E+10 | 39580445.84 | 0.00 | 4019585.93 | 0.268898E+10 | 0.00 | 0.846002E+10 | 0.00 | 4.58 |
August | 0.345212E+10 | 39556674.34 | 0.00 | 5381536.50 | 0.329383E+10 | 0.00 | 0.881367E+10 | 0.00 | 4.50 |
September | 0.787806E+10 | 0.377671E+09 | 0.00 | 5277481.57 | 0.708778E+09 | 0.00 | 0.117542E+11 | 0.00 | 4.77 |
October | 0.741206E+10 | 0.910349E+09 | 0.00 | 7751195.85 | 0.846363E+09 | 0.00 | 0.127485E+11 | 0.00 | 4.52 |
November | 0.137377E+11 | 13658798.45 | 0.00 | 6013150.66 | 133329.42 | 0.00 | 0.169918E+11 | 0.00 | 4.32 |
December | 0.150283E+11 | 7492450.77 | 0.00 | 7443034.83 | 1691694.07 | 0.00 | 0.167844E+11 | 0.00 | 4.09 |
Annual Sum or Average | 0.154286E+12 | 0.141783E+10 | 0.00 | 54378129.80 | 0.794298E+10 | 0.00 | 0.150056E+12 | 0.00 | 4.40 |
Minimum of Months | 0.345212E+10 | 0.00 | 0.00 | 2088907.78 | 133329.42 | 0.00 | 0.846002E+10 | 0.00 | 4.07 |
Maximum of Months | 0.227112E+11 | 0.910349E+09 | 0.00 | 7751195.85 | 0.329383E+10 | 0.00 | 0.169918E+11 | 0.00 | 4.77 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580638E+11 | 0.00 | 0.00 | 9502447.55 | 78162191.30 | 0.00 | 0.331466E+11 | 0.00 | 1.65 |
February | 0.565661E+11 | 0.00 | 0.00 | 7330579.76 | 21849346.89 | 0.00 | 0.269947E+11 | 0.00 | 1.71 |
March | 0.721392E+11 | 0.00 | 0.00 | 4836979.46 | 1401291.90 | 0.00 | 0.210963E+11 | 0.00 | 1.65 |
April | 0.480681E+11 | 0.00 | 0.00 | 8893259.98 | 89731146.97 | 0.00 | 0.307653E+11 | 0.00 | 1.78 |
May | 0.491240E+11 | 0.00 | 0.00 | 8589427.96 | 17343441.89 | 0.00 | 0.314192E+11 | 0.00 | 1.85 |
June | 0.286881E+11 | 0.00 | 0.00 | 14606607.27 | 0.100300E+10 | 0.00 | 0.344990E+11 | 0.00 | 1.91 |
July | 0.138931E+11 | 0.185326E+09 | 0.00 | 23221934.66 | 0.745360E+10 | 0.00 | 0.267269E+11 | 0.00 | 1.86 |
August | 0.788237E+10 | 97976796.38 | 0.00 | 30455910.48 | 0.923425E+10 | 0.00 | 0.264426E+11 | 0.00 | 1.83 |
September | 0.208400E+11 | 0.304181E+09 | 0.00 | 25152334.88 | 0.273747E+10 | 0.00 | 0.341185E+11 | 0.00 | 1.93 |
October | 0.201059E+11 | 0.633700E+09 | 0.00 | 31925934.96 | 0.428481E+10 | 0.00 | 0.364160E+11 | 0.00 | 1.83 |
November | 0.450012E+11 | 3427096.23 | 0.00 | 14235136.82 | 35185653.92 | 0.00 | 0.410322E+11 | 0.00 | 1.75 |
December | 0.526234E+11 | 0.00 | 0.00 | 13140544.17 | 25712137.64 | 0.00 | 0.364489E+11 | 0.00 | 1.65 |
Annual Sum or Average | 0.472995E+12 | 0.122461E+10 | 0.00 | 0.191891E+09 | 0.249825E+11 | 0.00 | 0.379106E+12 | 0.00 | 1.78 |
Minimum of Months | 0.788237E+10 | 0.00 | 0.00 | 4836979.46 | 1401291.90 | 0.00 | 0.210963E+11 | 0.00 | 1.65 |
Maximum of Months | 0.721392E+11 | 0.633700E+09 | 0.00 | 31925934.96 | 0.923425E+10 | 0.00 | 0.410322E+11 | 0.00 | 1.93 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11138186.20 | 2530272.70 | 0.00 | 6748106.32 | 704061.75 | 0.326256E+09 | 0.140939E+10 | 0.00 | 0.34 |
February | 24354977.60 | 1527509.15 | 0.00 | 6107402.31 | 0.00 | 0.172347E+09 | 0.130736E+10 | 0.00 | 0.34 |
March | 42198856.46 | 2036627.04 | 0.00 | 6225618.57 | 0.00 | 0.374996E+09 | 0.132560E+10 | 0.00 | 0.34 |
April | 16128027.33 | 4786722.71 | 0.00 | 10618026.51 | 0.00 | 44048160.02 | 0.113349E+10 | 0.00 | 0.34 |
May | 28088253.88 | 1336453.57 | 0.00 | 11008086.43 | 486168.26 | 31014458.04 | 0.115410E+10 | 0.00 | 0.34 |
June | 11004257.80 | 29269817.76 | 0.00 | 11802483.42 | 477255.89 | 1661046.73 | 0.693572E+09 | 0.00 | 0.34 |
July | 72494.35 | 0.202244E+09 | 14415.95 | 10700808.87 | 191073.09 | 560638.91 | 0.321616E+09 | 288.17 | 0.34 |
August | 0.00 | 0.267038E+09 | 32534.84 | 8474775.34 | 0.00 | 535651.32 | 0.242196E+09 | 964.74 | 0.34 |
September | 1585877.19 | 78669232.52 | 20777.28 | 10412411.63 | 4246015.58 | 1439007.83 | 0.533549E+09 | 1460.14 | 0.34 |
October | 5378537.07 | 0.164472E+09 | 39341.39 | 8798415.03 | 1502822.69 | 2050992.89 | 0.815892E+09 | 5767.57 | 0.34 |
November | 11810974.42 | 2083442.24 | 0.00 | 8098300.52 | 309475.80 | 7721996.64 | 0.145348E+10 | 0.00 | 0.34 |
December | 12689155.09 | 3862666.60 | 0.00 | 7424351.57 | 226975.21 | 0.173952E+09 | 0.152580E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.164450E+09 | 0.759856E+09 | 107069.47 | 0.106419E+09 | 8143848.27 | 0.113658E+10 | 0.119160E+11 | 8480.63 | 0.34 |
Minimum of Months | 0.00 | 1336453.57 | 0.00 | 6107402.31 | 0.00 | 535651.32 | 0.242196E+09 | 0.00 | 0.34 |
Maximum of Months | 42198856.46 | 0.267038E+09 | 39341.39 | 11802483.42 | 4246015.58 | 0.374996E+09 | 0.152580E+10 | 5767.57 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117330E+09 | 785368.41 | 16142.75 | 2374799.25 | 2429695.69 | 0.809421E+09 | 0.824202E+09 | 2748.65 | 0.34 |
February | 0.103607E+09 | 408185.85 | 701.73 | 2897754.73 | 1116285.00 | 0.337767E+09 | 0.106572E+10 | 2157.60 | 0.34 |
March | 0.100712E+09 | 277794.19 | 0.00 | 3365643.57 | 1758594.23 | 0.537639E+09 | 0.110710E+10 | 0.00 | 0.34 |
April | 0.153461E+09 | 2740523.68 | 0.00 | 6412194.87 | 2045638.20 | 43679700.82 | 0.100059E+10 | 0.00 | 0.34 |
May | 0.219120E+09 | 1135566.39 | 0.00 | 7593853.09 | 686841.89 | 26248890.15 | 0.971104E+09 | 0.00 | 0.34 |
June | 0.290151E+09 | 24349492.15 | 47216.18 | 7260990.54 | 5341169.94 | 1186119.13 | 0.419358E+09 | 5710.08 | 0.34 |
July | 0.210444E+09 | 0.171658E+09 | 63036.71 | 6323905.66 | 30702396.99 | 166344.25 | 0.115976E+09 | 2765.42 | 0.34 |
August | 0.170013E+09 | 0.225415E+09 | 165711.46 | 4376496.39 | 41454360.06 | 163338.83 | 76624162.16 | 4446.51 | 0.35 |
September | 0.229399E+09 | 67920867.24 | 161989.07 | 5232691.96 | 14838743.99 | 1202637.51 | 0.311088E+09 | 6167.88 | 0.35 |
October | 0.229184E+09 | 0.137081E+09 | 180174.88 | 3774244.44 | 28730320.73 | 1808521.37 | 0.597256E+09 | 8942.34 | 0.34 |
November | 0.154910E+09 | 1935447.07 | 10094.28 | 3040886.26 | 445312.01 | 0.180075E+09 | 0.114291E+10 | 1784.32 | 0.34 |
December | 0.129840E+09 | 2840894.02 | 42863.38 | 2342970.68 | 1198255.74 | 0.625813E+09 | 0.961666E+09 | 7149.51 | 0.34 |
Annual Sum or Average | 0.210817E+10 | 0.636548E+09 | 687930.45 | 54996431.45 | 0.130748E+09 | 0.256517E+10 | 0.859360E+10 | 41872.30 | 0.34 |
Minimum of Months | 0.100712E+09 | 277794.19 | 0.00 | 2342970.68 | 445312.01 | 163338.83 | 76624162.16 | 0.00 | 0.34 |
Maximum of Months | 0.290151E+09 | 0.225415E+09 | 180174.88 | 7593853.09 | 41454360.06 | 0.809421E+09 | 0.114291E+10 | 8942.34 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 93991752.03 | 3925720.75 | 0.00 | 3729625.72 | 0.00 | 0.00 | 0.894129E+09 | 0.00 | 0.02 |
February | 0.365840E+09 | 0.00 | 0.00 | 2254723.87 | 0.00 | 0.00 | 0.683485E+09 | 0.00 | 0.02 |
March | 0.527991E+09 | 6283553.53 | 0.00 | 1621875.74 | 0.00 | 0.00 | 0.592658E+09 | 0.00 | 0.02 |
April | 0.137579E+09 | 1128316.02 | 0.00 | 1697844.85 | 0.00 | 0.00 | 0.617889E+09 | 0.00 | 0.02 |
May | 0.644968E+09 | 0.00 | 0.00 | 332838.18 | 0.00 | 0.00 | 0.205895E+09 | 0.00 | 0.02 |
June | 0.386933E+09 | 4998393.50 | 0.00 | 180922.53 | 9442494.88 | 0.00 | 0.124003E+09 | 0.00 | 0.02 |
July | 81592903.33 | 0.295249E+09 | 0.00 | 111154.54 | 13893540.21 | 0.00 | 52407359.88 | 0.00 | 0.02 |
August | 0.00 | 0.459224E+09 | 0.00 | 193553.81 | 0.00 | 0.00 | 25522927.94 | 0.00 | 0.02 |
September | 0.00 | 0.155818E+09 | 0.00 | 1456348.66 | 0.00 | 0.00 | 0.165738E+09 | 0.00 | 0.02 |
October | 49134557.72 | 0.207238E+09 | 0.00 | 2098264.96 | 5034465.10 | 0.00 | 0.277846E+09 | 0.00 | 0.02 |
November | 34108621.65 | 369322.45 | 0.00 | 3375098.13 | 0.00 | 0.00 | 0.878944E+09 | 0.00 | 0.02 |
December | 82124834.90 | 320708.95 | 0.00 | 3928700.36 | 0.00 | 0.00 | 0.922197E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.240426E+10 | 0.113455E+10 | 0.00 | 20980951.36 | 28370500.19 | 0.00 | 0.544071E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 111154.54 | 0.00 | 0.00 | 25522927.94 | 0.00 | 0.02 |
Maximum of Months | 0.644968E+09 | 0.459224E+09 | 0.00 | 3928700.36 | 13893540.21 | 0.00 | 0.922197E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159217E+10 | 10199236.88 | 300061.22 | 53024634.90 | 33355670.29 | 0.140370E+09 | 0.219973E+11 | 11697.93 | 0.39 |
February | 0.139897E+10 | 5575581.34 | 0.00 | 55437044.39 | 15141736.35 | 91312141.71 | 0.189364E+11 | 0.00 | 0.39 |
March | 0.137351E+10 | 3760310.97 | 0.00 | 63900735.66 | 23854275.76 | 85255216.77 | 0.221990E+11 | 7800.52 | 0.39 |
April | 0.209611E+10 | 24409546.09 | 130813.09 | 80258497.57 | 40375164.71 | 20227320.42 | 0.141369E+11 | 5890.75 | 0.39 |
May | 0.301973E+10 | 4248927.66 | 0.00 | 95535531.85 | 20470947.45 | 9932906.32 | 0.134785E+11 | 0.00 | 0.39 |
June | 0.400370E+10 | 0.222138E+09 | 0.00 | 93980051.55 | 0.181316E+09 | 3783325.02 | 0.563717E+10 | 0.00 | 0.39 |
July | 0.287441E+10 | 0.191033E+10 | 0.00 | 78394594.61 | 0.835459E+09 | 1067184.75 | 0.156186E+10 | 0.00 | 0.39 |
August | 0.230612E+10 | 0.249955E+10 | 1098944.48 | 54263489.35 | 0.112159E+10 | 180349.01 | 0.104650E+10 | 184.02 | 0.39 |
September | 0.313864E+10 | 0.736027E+09 | 1096773.20 | 61732075.48 | 0.387737E+09 | 4801195.00 | 0.421350E+10 | 4491.94 | 0.39 |
October | 0.311908E+10 | 0.155225E+10 | 233705.36 | 52137674.47 | 0.699164E+09 | 6423197.27 | 0.810825E+10 | 46406.59 | 0.39 |
November | 0.210921E+10 | 15750291.01 | 0.00 | 56991632.09 | 16704403.79 | 56523239.99 | 0.178653E+11 | 0.00 | 0.39 |
December | 0.176251E+10 | 36814920.03 | 689582.43 | 51055625.18 | 17920268.00 | 0.104888E+09 | 0.214077E+11 | 42267.88 | 0.39 |
Annual Sum or Average | 0.287942E+11 | 0.702105E+10 | 3549879.78 | 0.796712E+09 | 0.339309E+10 | 0.524764E+09 | 0.150588E+12 | 118739.63 | 0.39 |
Minimum of Months | 0.137351E+10 | 3760310.97 | 0.00 | 51055625.18 | 15141736.35 | 180349.01 | 0.104650E+10 | 0.00 | 0.39 |
Maximum of Months | 0.400370E+10 | 0.249955E+10 | 1098944.48 | 95535531.85 | 0.112159E+10 | 0.140370E+09 | 0.221990E+11 | 46406.59 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14152837.18 | 2530272.70 | 0.00 | 7760498.95 | 704061.75 | 0.351744E+09 | 0.137988E+10 | 0.00 | 0.34 |
February | 26143847.88 | 1527509.15 | 0.00 | 6022933.29 | 0.00 | 0.230272E+09 | 0.124773E+10 | 0.00 | 0.34 |
March | 41034151.43 | 2036627.04 | 0.00 | 6424089.77 | 0.00 | 0.432509E+09 | 0.126905E+10 | 0.00 | 0.34 |
April | 10808925.82 | 4786722.71 | 0.00 | 10050218.52 | 0.00 | 39907747.56 | 0.114352E+10 | 0.00 | 0.34 |
May | 23471663.55 | 1822621.83 | 0.00 | 10193226.23 | 0.00 | 32104973.56 | 0.115844E+10 | 0.00 | 0.34 |
June | 9785404.66 | 29744548.15 | 2493.15 | 10613813.61 | 0.00 | 1754148.57 | 0.695886E+09 | 32.35 | 0.34 |
July | 0.00 | 0.202334E+09 | 20827.46 | 10130276.00 | 94049.98 | 622948.59 | 0.322196E+09 | 753.66 | 0.34 |
August | 0.00 | 0.267071E+09 | 0.00 | 8395329.14 | 0.00 | 573888.10 | 0.242237E+09 | 0.00 | 0.34 |
September | 1585877.19 | 78691469.94 | 0.00 | 9375415.57 | 4246015.58 | 1691878.30 | 0.534333E+09 | 0.00 | 0.34 |
October | 5378537.07 | 0.164441E+09 | 73508.55 | 9003724.12 | 1502822.69 | 1488208.48 | 0.816250E+09 | 2491.57 | 0.34 |
November | 13534619.84 | 2082009.89 | 758.25 | 8264924.06 | 309475.80 | 40327803.43 | 0.141898E+10 | 674.10 | 0.34 |
December | 15225965.67 | 4084007.54 | 3826.27 | 8040847.33 | 0.00 | 0.214525E+09 | 0.148207E+10 | 1808.00 | 0.34 |
Annual Sum or Average | 0.161122E+09 | 0.761152E+09 | 101413.69 | 0.104275E+09 | 6856425.80 | 0.134752E+10 | 0.117106E+11 | 5759.68 | 0.34 |
Minimum of Months | 0.00 | 1527509.15 | 0.00 | 6022933.29 | 0.00 | 573888.10 | 0.242237E+09 | 0.00 | 0.34 |
Maximum of Months | 41034151.43 | 0.267071E+09 | 73508.55 | 10613813.61 | 4246015.58 | 0.432509E+09 | 0.148207E+10 | 2491.57 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117317E+09 | 774895.75 | 0.00 | 3035869.02 | 2459059.75 | 0.736396E+09 | 0.896580E+09 | 0.00 | 0.34 |
February | 0.103136E+09 | 406859.34 | 2341.91 | 2979142.65 | 1116285.00 | 0.432372E+09 | 0.971507E+09 | 1843.94 | 0.34 |
March | 0.100795E+09 | 385651.83 | 0.00 | 3712685.93 | 1650736.59 | 0.591493E+09 | 0.105281E+10 | 0.00 | 0.34 |
April | 0.150732E+09 | 3797544.64 | 0.00 | 6559449.11 | 988617.23 | 39291145.54 | 0.100756E+10 | 0.00 | 0.34 |
May | 0.214745E+09 | 1771640.69 | 0.00 | 7516562.29 | 50767.59 | 30052099.39 | 0.971753E+09 | 0.00 | 0.34 |
June | 0.290078E+09 | 24792219.06 | 0.00 | 6351990.77 | 4951369.28 | 1029529.62 | 0.420496E+09 | 0.00 | 0.34 |
July | 0.209788E+09 | 0.172614E+09 | 0.00 | 5453449.21 | 29812483.42 | 216567.31 | 0.117452E+09 | 0.00 | 0.34 |
August | 0.170013E+09 | 0.227623E+09 | 0.00 | 3842765.60 | 39417333.89 | 187352.56 | 77133879.23 | 0.00 | 0.35 |
September | 0.229521E+09 | 67575333.02 | 190905.29 | 4652388.74 | 15159070.68 | 1376800.99 | 0.311371E+09 | 2459.19 | 0.35 |
October | 0.228651E+09 | 0.136623E+09 | 171753.10 | 4125936.41 | 29201214.91 | 1376659.86 | 0.597869E+09 | 4356.15 | 0.34 |
November | 0.156292E+09 | 1358190.51 | 0.00 | 3521996.30 | 1034447.18 | 0.294349E+09 | 0.102678E+10 | 0.00 | 0.34 |
December | 0.129831E+09 | 2811489.21 | 23415.05 | 2716858.27 | 1249368.44 | 0.677211E+09 | 0.909903E+09 | 4889.95 | 0.34 |
Annual Sum or Average | 0.210090E+10 | 0.640533E+09 | 388415.35 | 54469094.29 | 0.127091E+09 | 0.280535E+10 | 0.836122E+10 | 13549.23 | 0.34 |
Minimum of Months | 0.100795E+09 | 385651.83 | 0.00 | 2716858.27 | 50767.59 | 187352.56 | 77133879.23 | 0.00 | 0.34 |
Maximum of Months | 0.290078E+09 | 0.227623E+09 | 190905.29 | 7516562.29 | 39417333.89 | 0.736396E+09 | 0.105281E+10 | 4889.95 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228793E+11 | 0.00 | 0.00 | 0.00 | 19604256.03 | 0.00 | 0.00 | 0.00 | 0.45 |
February | 0.209601E+11 | 0.00 | 0.00 | 0.00 | 5480145.62 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.233861E+11 | 0.00 | 0.00 | 0.00 | 351465.13 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.197748E+11 | 0.00 | 0.00 | 0.00 | 22505924.53 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.202036E+11 | 0.00 | 0.00 | 0.00 | 4349996.71 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.158519E+11 | 0.00 | 0.00 | 0.00 | 0.251567E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.101939E+11 | 0.00 | 0.00 | 0.00 | 0.191596E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.861666E+10 | 0.00 | 0.00 | 0.00 | 0.234066E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.137892E+11 | 0.00 | 0.00 | 0.00 | 0.762891E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.141619E+11 | 0.00 | 0.00 | 0.00 | 0.123354E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.215820E+11 | 0.00 | 0.00 | 0.00 | 9684659.90 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.223437E+11 | 0.00 | 0.00 | 0.00 | 6448991.78 | 0.00 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.213743E+12 | 0.00 | 0.00 | 0.00 | 0.657305E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
Minimum of Months | 0.861666E+10 | 0.00 | 0.00 | 0.00 | 351465.13 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.233861E+11 | 0.00 | 0.00 | 0.00 | 0.234066E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2991163.68 | 632568.18 | 0.00 | 1341911.83 | 176015.44 | 0.197919E+09 | 0.236131E+09 | 0.00 | 0.34 |
February | 6192255.26 | 381877.29 | 0.00 | 1250834.29 | 0.00 | 0.139469E+09 | 0.230630E+09 | 0.00 | 0.34 |
March | 9727474.17 | 509156.76 | 0.00 | 1380391.68 | 0.00 | 0.189446E+09 | 0.236701E+09 | 0.00 | 0.34 |
April | 3084764.48 | 1196680.68 | 0.00 | 2575912.58 | 0.00 | 29530737.94 | 0.265880E+09 | 0.00 | 0.34 |
May | 5152515.11 | 455655.46 | 0.00 | 2673215.29 | 0.00 | 25930970.78 | 0.272296E+09 | 0.00 | 0.34 |
June | 2024717.86 | 7433129.52 | 0.00 | 2912766.76 | 3638.89 | 400211.15 | 0.174172E+09 | 0.00 | 0.34 |
July | 0.00 | 50608798.15 | 3607.73 | 2659988.51 | 0.00 | 141163.30 | 80436223.47 | 68.30 | 0.34 |
August | 0.00 | 66759812.15 | 7711.82 | 2045829.10 | 0.00 | 137810.60 | 60617974.95 | 290.78 | 0.34 |
September | 396469.30 | 19729460.26 | 2758.42 | 2442477.95 | 1001571.04 | 323817.38 | 0.133584E+09 | 581.66 | 0.34 |
October | 1536541.64 | 41295778.84 | 18040.22 | 1916356.98 | 188557.15 | 9808136.43 | 0.194769E+09 | 2522.39 | 0.34 |
November | 3276105.60 | 520860.56 | 0.00 | 1636586.08 | 77368.95 | 93900127.34 | 0.271465E+09 | 0.00 | 0.34 |
December | 3827148.36 | 1022410.45 | 0.00 | 1453150.73 | 0.00 | 0.182851E+09 | 0.241834E+09 | 0.00 | 0.34 |
Annual Sum or Average | 38209155.47 | 0.190546E+09 | 32118.19 | 24289421.79 | 1447151.47 | 0.869859E+09 | 0.239852E+10 | 3463.14 | 0.34 |
Minimum of Months | 0.00 | 381877.29 | 0.00 | 1250834.29 | 0.00 | 137810.60 | 60617974.95 | 0.00 | 0.34 |
Maximum of Months | 9727474.17 | 66759812.15 | 18040.22 | 2912766.76 | 1001571.04 | 0.197919E+09 | 0.272296E+09 | 2522.39 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29643748.15 | 196342.10 | 4160.40 | 368814.96 | 607423.92 | 0.298802E+09 | 0.109518E+09 | 562.45 | 0.34 |
February | 25783903.30 | 102046.46 | 558.35 | 508416.44 | 279071.25 | 0.217040E+09 | 0.134166E+09 | 156.49 | 0.34 |
March | 25818388.33 | 69448.55 | 0.00 | 680205.40 | 439648.56 | 0.229212E+09 | 0.181492E+09 | 0.00 | 0.34 |
April | 37535967.15 | 959612.17 | 0.00 | 1543991.10 | 236928.30 | 31370589.95 | 0.230585E+09 | 0.00 | 0.34 |
May | 52771644.94 | 455602.07 | 0.00 | 1910018.87 | 0.00 | 19996607.90 | 0.231338E+09 | 0.00 | 0.34 |
June | 72093571.20 | 6189602.53 | 4287.60 | 1909500.71 | 1241480.78 | 304075.97 | 0.105182E+09 | 526.17 | 0.34 |
July | 52611119.93 | 42923226.05 | 7165.91 | 1711186.80 | 7675599.25 | 19466.27 | 28885849.81 | 552.99 | 0.35 |
August | 42503257.18 | 56434723.04 | 17872.84 | 1140576.80 | 10306626.64 | 35369.00 | 19115053.55 | 769.40 | 0.35 |
September | 56763370.25 | 17516204.32 | 37140.61 | 1229388.65 | 3177244.53 | 288484.28 | 78449203.77 | 1352.59 | 0.35 |
October | 57302807.26 | 34461890.47 | 39875.37 | 735255.67 | 6993644.91 | 16962908.23 | 0.133005E+09 | 4624.95 | 0.34 |
November | 38840558.49 | 483861.77 | 2569.47 | 449620.74 | 111328.00 | 0.168614E+09 | 0.162331E+09 | 400.18 | 0.34 |
December | 32679833.73 | 716892.59 | 4761.77 | 324048.88 | 299563.94 | 0.283971E+09 | 0.112940E+09 | 1072.37 | 0.34 |
Annual Sum or Average | 0.524348E+09 | 0.160509E+09 | 118392.31 | 12511025.02 | 31368560.08 | 0.126662E+10 | 0.152701E+10 | 10017.57 | 0.34 |
Minimum of Months | 25783903.30 | 69448.55 | 0.00 | 324048.88 | 0.00 | 19466.27 | 19115053.55 | 0.00 | 0.34 |
Maximum of Months | 72093571.20 | 56434723.04 | 39875.37 | 1910018.87 | 10306626.64 | 0.298802E+09 | 0.231338E+09 | 4624.95 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7980427.58 | 5028049.90 | 0.00 | 18271252.51 | 166686.90 | 93181306.60 | 0.269696E+10 | 0.00 | 0.39 |
February | 28529920.93 | 2453366.57 | 0.00 | 13215669.96 | 0.00 | 0.102975E+09 | 0.228080E+10 | 0.00 | 0.39 |
March | 47213505.99 | 3271072.17 | 0.00 | 12010847.00 | 0.00 | 0.376701E+09 | 0.237321E+10 | 0.00 | 0.39 |
April | 13570590.85 | 7688062.26 | 0.00 | 14243532.05 | 0.00 | 43497706.45 | 0.186292E+10 | 0.00 | 0.39 |
May | 35458571.70 | 2845805.12 | 0.00 | 11827251.11 | 81548.52 | 50866176.25 | 0.186808E+10 | 0.00 | 0.39 |
June | 16085435.69 | 47104045.26 | 4006.66 | 12059382.59 | 669337.88 | 3736735.00 | 0.112138E+10 | 49.61 | 0.39 |
July | 17785.95 | 0.325101E+09 | 55817.61 | 11539771.62 | 0.00 | 1676142.98 | 0.521524E+09 | 2460.93 | 0.39 |
August | 0.00 | 0.428895E+09 | 51413.87 | 10361085.67 | 0.00 | 1665062.65 | 0.391442E+09 | 2390.56 | 0.39 |
September | 2547112.78 | 0.126773E+09 | 0.00 | 14179779.47 | 6434582.48 | 2806029.49 | 0.858993E+09 | 0.00 | 0.39 |
October | 5140035.11 | 0.264215E+09 | 17919.40 | 14890991.17 | 2413717.09 | 4449565.74 | 0.131201E+10 | 658.43 | 0.39 |
November | 4119771.65 | 3701005.85 | 0.00 | 18081779.20 | 142313.27 | 3740620.78 | 0.235291E+10 | 0.00 | 0.39 |
December | 9062126.81 | 6568465.07 | 0.00 | 19185883.47 | 0.00 | 52623458.42 | 0.268144E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.169725E+09 | 0.122364E+10 | 129157.53 | 0.169867E+09 | 9908186.15 | 0.737919E+09 | 0.203217E+11 | 5559.53 | 0.39 |
Minimum of Months | 0.00 | 2453366.57 | 0.00 | 10361085.67 | 0.00 | 1665062.65 | 0.391442E+09 | 0.00 | 0.39 |
Maximum of Months | 47213505.99 | 0.428895E+09 | 55817.61 | 19185883.47 | 6434582.48 | 0.376701E+09 | 0.269696E+10 | 2460.93 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170663E+11 | 5170971.95 | 0.00 | 20304354.14 | 43847106.54 | 0.00 | 0.401204E+11 | 0.00 | 5.30 |
February | 0.153656E+11 | 0.00 | 0.00 | 19387922.65 | 13702443.38 | 0.00 | 0.370233E+11 | 0.00 | 5.49 |
March | 0.165376E+11 | 0.00 | 0.00 | 21840263.75 | 878796.19 | 0.00 | 0.419146E+11 | 0.00 | 5.30 |
April | 0.105389E+11 | 6526424.31 | 0.00 | 24794389.75 | 49746926.41 | 0.00 | 0.388809E+11 | 0.00 | 5.74 |
May | 0.100927E+11 | 2893915.74 | 0.00 | 27909866.26 | 7982726.56 | 0.00 | 0.403972E+11 | 0.00 | 5.94 |
June | 0.542429E+10 | 0.221420E+09 | 0.00 | 33099621.48 | 0.407593E+09 | 0.00 | 0.341901E+11 | 0.00 | 6.15 |
July | 0.168511E+10 | 0.254948E+10 | 0.00 | 35374241.57 | 0.224114E+10 | 0.00 | 0.237812E+11 | 0.00 | 5.98 |
August | 0.136710E+10 | 0.260124E+10 | 0.00 | 34094549.03 | 0.325130E+10 | 0.00 | 0.201532E+11 | 0.00 | 5.87 |
September | 0.477758E+10 | 0.783988E+09 | 0.00 | 29494992.91 | 0.112360E+10 | 0.00 | 0.296728E+11 | 0.00 | 6.21 |
October | 0.494881E+10 | 0.155099E+10 | 0.00 | 28734126.03 | 0.153362E+10 | 0.00 | 0.304378E+11 | 0.00 | 5.88 |
November | 0.141638E+11 | 3691344.69 | 0.00 | 21800600.43 | 20523979.70 | 0.00 | 0.397777E+11 | 0.00 | 5.62 |
December | 0.153490E+11 | 0.00 | 0.00 | 20801502.76 | 16124926.38 | 0.00 | 0.404979E+11 | 0.00 | 5.31 |
Annual Sum or Average | 0.117317E+12 | 0.772540E+10 | 0.00 | 0.317636E+09 | 0.871006E+10 | 0.00 | 0.416847E+12 | 0.00 | 5.73 |
Minimum of Months | 0.136710E+10 | 0.00 | 0.00 | 19387922.65 | 878796.19 | 0.00 | 0.201532E+11 | 0.00 | 5.30 |
Maximum of Months | 0.170663E+11 | 0.260124E+10 | 0.00 | 35374241.57 | 0.325130E+10 | 0.00 | 0.419146E+11 | 0.00 | 6.21 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127446E+11 | 15141538.23 | 0.00 | 27564483.64 | 33887684.73 | 0.00 | 0.444560E+11 | 0.00 | 5.31 |
February | 0.118845E+11 | 0.00 | 0.00 | 26182463.41 | 13705558.69 | 0.00 | 0.405097E+11 | 0.00 | 5.50 |
March | 0.126072E+11 | 0.00 | 0.00 | 29750436.91 | 878995.99 | 0.00 | 0.458538E+11 | 0.00 | 5.30 |
April | 0.661380E+10 | 35570787.19 | 0.00 | 32781317.93 | 20715357.53 | 0.00 | 0.428583E+11 | 0.00 | 5.75 |
May | 0.570658E+10 | 3892945.91 | 0.00 | 36859930.39 | 6986169.24 | 0.00 | 0.448847E+11 | 0.00 | 5.95 |
June | 0.290962E+10 | 0.428420E+09 | 0.00 | 42311283.03 | 0.200736E+09 | 0.00 | 0.369002E+11 | 0.00 | 6.18 |
July | 0.113325E+10 | 0.350805E+10 | 0.00 | 43796085.78 | 0.128367E+10 | 0.00 | 0.244788E+11 | 0.00 | 6.01 |
August | 0.756010E+09 | 0.401114E+10 | 0.00 | 40910910.37 | 0.184273E+10 | 0.00 | 0.209128E+11 | 0.00 | 5.90 |
September | 0.276973E+10 | 0.132692E+10 | 0.00 | 36903711.00 | 0.585396E+09 | 0.00 | 0.317792E+11 | 0.00 | 6.23 |
October | 0.318867E+10 | 0.228816E+10 | 0.00 | 35608907.51 | 0.798125E+09 | 0.00 | 0.322910E+11 | 0.00 | 5.90 |
November | 0.109088E+11 | 14787378.16 | 0.00 | 28707139.94 | 9433451.69 | 0.00 | 0.430419E+11 | 0.00 | 5.63 |
December | 0.116973E+11 | 1545253.54 | 0.00 | 27857745.47 | 14583338.92 | 0.00 | 0.441664E+11 | 0.00 | 5.32 |
Annual Sum or Average | 0.829202E+11 | 0.116336E+11 | 0.00 | 0.409234E+09 | 0.481085E+10 | 0.00 | 0.452133E+12 | 0.00 | 5.75 |
Minimum of Months | 0.756010E+09 | 0.00 | 0.00 | 26182463.41 | 878995.99 | 0.00 | 0.209128E+11 | 0.00 | 5.30 |
Maximum of Months | 0.127446E+11 | 0.401114E+10 | 0.00 | 43796085.78 | 0.184273E+10 | 0.00 | 0.458538E+11 | 0.00 | 6.23 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 59031183.65 | 0.00 | 0.115925E+09 | 0.00 | 0.00 | 0.541235E+11 | 0.00 | 17.59 |
February | 0.00 | 16564214.07 | 0.00 | 0.103136E+09 | 0.00 | 0.00 | 0.506451E+11 | 0.00 | 18.28 |
March | 0.00 | 1062985.36 | 0.00 | 0.112836E+09 | 0.00 | 0.00 | 0.560801E+11 | 0.00 | 17.70 |
April | 0.00 | 68033610.23 | 0.00 | 0.122750E+09 | 0.00 | 0.00 | 0.472138E+11 | 0.00 | 19.27 |
May | 0.00 | 13108140.65 | 0.00 | 0.129920E+09 | 0.00 | 0.00 | 0.482393E+11 | 0.00 | 19.98 |
June | 0.00 | 0.759803E+09 | 0.00 | 0.122909E+09 | 0.00 | 0.00 | 0.369748E+11 | 0.00 | 20.42 |
July | 0.00 | 0.578864E+10 | 0.00 | 97064402.78 | 0.00 | 0.00 | 0.225029E+11 | 0.00 | 19.71 |
August | 0.00 | 0.707222E+10 | 0.00 | 78074850.69 | 0.00 | 0.00 | 0.186269E+11 | 0.00 | 19.29 |
September | 0.00 | 0.227081E+10 | 0.00 | 0.107367E+09 | 0.00 | 0.00 | 0.318195E+11 | 0.00 | 20.58 |
October | 0.00 | 0.368894E+10 | 0.00 | 98145626.76 | 0.00 | 0.00 | 0.324723E+11 | 0.00 | 19.44 |
November | 0.00 | 29098163.21 | 0.00 | 0.114617E+09 | 0.00 | 0.00 | 0.517080E+11 | 0.00 | 18.80 |
December | 0.00 | 19431888.86 | 0.00 | 0.117774E+09 | 0.00 | 0.00 | 0.530009E+11 | 0.00 | 17.69 |
Annual Sum or Average | 0.00 | 0.197867E+11 | 0.00 | 0.132052E+10 | 0.00 | 0.00 | 0.503407E+12 | 0.00 | 19.06 |
Minimum of Months | 0.00 | 1062985.36 | 0.00 | 78074850.69 | 0.00 | 0.00 | 0.186269E+11 | 0.00 | 17.59 |
Maximum of Months | 0.00 | 0.707222E+10 | 0.00 | 0.129920E+09 | 0.00 | 0.00 | 0.560801E+11 | 0.00 | 20.58 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.599227E+10 | 1267022.83 | 0.00 | 59770.23 | 3920728.61 | 0.00 | 62089248.65 | 0.00 | 0.45 |
February | 0.554655E+10 | 0.00 | 0.00 | 0.00 | 1450176.60 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.615597E+10 | 0.00 | 0.00 | 46363.06 | 93006.02 | 0.00 | 32494254.71 | 0.00 | 0.45 |
April | 0.485804E+10 | 3483296.12 | 0.00 | 790747.86 | 2659341.59 | 0.00 | 0.379640E+09 | 0.00 | 0.49 |
May | 0.500084E+10 | 472437.85 | 0.00 | 936575.60 | 817956.29 | 0.00 | 0.353783E+09 | 0.00 | 0.51 |
June | 0.292015E+10 | 83805512.58 | 0.00 | 3634943.13 | 627503.41 | 0.00 | 0.131312E+10 | 0.00 | 0.54 |
July | 0.768442E+09 | 0.667632E+09 | 0.00 | 6660452.36 | 5483768.04 | 0.00 | 0.200612E+10 | 0.00 | 0.56 |
August | 0.583326E+09 | 0.832450E+09 | 0.00 | 5195152.34 | 9912461.23 | 0.00 | 0.175587E+10 | 0.00 | 0.56 |
September | 0.230130E+10 | 0.214722E+09 | 0.00 | 3587045.22 | 58549795.72 | 0.00 | 0.139109E+10 | 0.00 | 0.56 |
October | 0.269921E+10 | 0.454917E+09 | 0.00 | 2867346.74 | 9635254.05 | 0.00 | 0.110852E+10 | 0.00 | 0.54 |
November | 0.568284E+10 | 2547629.02 | 0.00 | 39349.20 | 132678.19 | 0.00 | 28243144.21 | 0.00 | 0.48 |
December | 0.589450E+10 | 808304.50 | 0.00 | 62946.76 | 930322.38 | 0.00 | 18296384.79 | 0.00 | 0.45 |
Annual Sum or Average | 0.484035E+11 | 0.226210E+10 | 0.00 | 23880692.49 | 94212992.12 | 0.00 | 0.844927E+10 | 0.00 | 0.51 |
Minimum of Months | 0.583326E+09 | 0.00 | 0.00 | 0.00 | 93006.02 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.615597E+10 | 0.832450E+09 | 0.00 | 6660452.36 | 58549795.72 | 0.00 | 0.200612E+10 | 0.00 | 0.56 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.154358E+12 | 0.951455E+10 | 0.119204E+12 | 0.424067E+12 | 0.191323E+12 |
February | 0.202915E+12 | 0.837240E+10 | 0.109956E+12 | 0.389103E+12 | 0.132112E+12 |
March | 0.291581E+12 | 0.967211E+10 | 0.126345E+12 | 0.433314E+12 | 0.140602E+12 |
April | 0.382267E+12 | 0.743437E+10 | 0.947020E+11 | 0.365485E+12 | 0.227673E+12 |
May | 0.410739E+12 | 0.766698E+10 | 0.953867E+11 | 0.374861E+12 | 0.233317E+12 |
June | 0.406431E+12 | 0.542055E+10 | 0.670779E+11 | 0.284828E+12 | 0.356438E+12 |
July | 0.431235E+12 | 0.220409E+10 | 0.260934E+11 | 0.145025E+12 | 0.615197E+12 |
August | 0.391119E+12 | 0.140953E+10 | 0.153464E+11 | 0.107219E+12 | 0.679334E+12 |
September | 0.306710E+12 | 0.423596E+10 | 0.522541E+11 | 0.234152E+12 | 0.458647E+12 |
October | 0.207211E+12 | 0.457286E+10 | 0.507730E+11 | 0.237730E+12 | 0.495167E+12 |
November | 0.170867E+12 | 0.842454E+10 | 0.104903E+12 | 0.401111E+12 | 0.196463E+12 |
December | 0.134284E+12 | 0.940188E+10 | 0.116004E+12 | 0.415413E+12 | 0.206793E+12 |
Annual Sum or Average | 0.348972E+13 | 0.783298E+11 | 0.978045E+12 | 0.381231E+13 | 0.393307E+13 |