Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:54
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:54:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9623.98 | 848.28 | 848.28 |
Net Site Energy | 9421.36 | 830.42 | 830.42 |
Total Source Energy | 20899.25 | 1842.11 | 1842.11 |
Net Source Energy | 20257.56 | 1785.55 | 1785.55 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 351.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1425.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 473.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 390.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 600.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 89.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 110.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2458.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5024.90 | 4599.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 351.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1425.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 473.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 150.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 366.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 600.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 89.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 110.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2458.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 351.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1425.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 473.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 150.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 390.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 600.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 89.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 110.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2458.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 55.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 194.49 | 247.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 193.40 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 442.91 | 405.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 55.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 194.49 | 247.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 193.40 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 442.91 | 405.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 211.646 | 4.21 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -9.03 | -0.2 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 202.617 | 4.03 |
Electricity Coming From Utility | 4822.281 | 95.97 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4822.281 | 95.97 |
Total On-Site and Utility Electric Sources | 5024.898 | 100.00 |
Total Electricity End Uses | 5024.898 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 570.10 | 58.58 |
Air to Air Heat Recovery for Heating | 403.10 | 41.42 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 973.20 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 77.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7943.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:54 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.2037 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 7.5557 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 7.5557 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 7.2603 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.7794 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.2151 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 7.7715 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.1806 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4993 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.7715 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.7715 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 12.1686 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4993 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.5793 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.5793 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.2037 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 7.5557 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 7.5557 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 7.2603 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.7794 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.2151 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 7.7715 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.1806 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4993 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 7.7715 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 7.7715 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 12.1686 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4993 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.5793 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.5793 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.4264 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-19:19 | 09-JAN-17:40 | - | - | - | - | - | - | - | - | - | - | 29-MAR-20:19 |
Heating | 0.00 | 132817.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 149056.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 39200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 19291.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31164.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3668.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3959.45 | 205348.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1343.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 351653.62 | 427778.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 132817.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 149056.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 39200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1220.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 17944.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 31164.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3668.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3959.45 | 205348.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 431.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 670.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 381.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4513.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1500.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 476.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1902.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 284.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 351.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 2665.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15913.85 | 4985.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 33.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 397.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 30.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 234.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1402.68 | 439.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 33.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 397.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 30.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 234.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1402.68 | 439.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.16 | 0.698578 | 0.594000 | 1.28 | 1.00 | 0.500000 | 0.000545 | 0.000172 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.278322 | 0.183631 | 0.427000 | 0.118843 | 0.508678 | 0.500000 | 0.002075 | 0.000065 | 0.118843 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.214176 | 0.276332 | 0.642000 | 0.137501 | 0.736884 | 0.500000 | 0.001379 | 0.000035 | 0.137501 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.224467 | 0.557557 | 0.010000 | 0.002245 | 1.00 | 0.500000 | 0.000683 | 0.000046 | 0.076330 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.107150 | 0.673881 | 0.809000 | 0.086685 | 1.00 | 0.500000 | 0.000565 | 0.000033 | 0.086685 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.38 | 0.017615 | 0.010000 | 0.033758 | 0.300000 | 0.500000 | 0.021629 | 0.000060 | 0.098922 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.30 | 0.110483 | 0.779000 | 1.01 | 0.779000 | 0.500000 | 0.003449 | 0.000238 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.49 | 0.222139 | 0.633000 | 2.84 | 0.633000 | 0.500000 | 0.001715 | 0.000638 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.13 | 1.00 | 0.628000 | 0.711917 | 1.00 | 0.500000 | 0.000364 | 0.000252 | 0.711917 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.16 | 0.117155 | 0.826000 | 1.78 | 0.826000 | 0.500000 | 0.003252 | 0.000316 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.27 | 0.111535 | 0.786000 | 1.78 | 0.786000 | 0.500000 | 0.003416 | 0.000319 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.23 | 0.063451 | 0.247000 | 0.551154 | 0.300000 | 0.500000 | 0.010800 | 0.000108 | 0.551154 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.658001 | 0.477262 | 0.286000 | 0.188188 | 1.00 | 0.500000 | 0.000798 | 0.000154 | 0.256001 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7871.53 | 0.000172 | 231.23 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2952.66 | 0.000065 | 116.16 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1581.64 | 0.000035 | 51.05 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2105.04 | 0.000046 | 87.22 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1524.72 | 0.000033 | 53.57 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2728.10 | 0.000060 | 113.04 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10901.96 | 0.000238 | 346.98 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 29176.17 | 0.000638 | 920.63 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4883.91 | 0.000107 | 220.57 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4886.63 | 0.000107 | 220.69 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 27927.57 | 0.000611 | 1261.23 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 27994.59 | 0.000612 | 1264.26 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4877.74 | 0.000107 | 220.29 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4880.46 | 0.000107 | 220.41 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11511.78 | 0.000252 | 397.08 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1531.97 | 0.000034 | 69.18 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1533.03 | 0.000034 | 69.23 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7381.14 | 0.000161 | 333.31 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14464.06 | 0.000316 | 439.32 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14572.87 | 0.000319 | 443.12 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 4924.25 | 0.000108 | 151.71 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7060.89 | 0.000154 | 292.59 |
VAV WITH REHEAT HEATING COIL | 164929.62 | 0.003608 | 3492.56 |
FLR_3_DOAS HEATING COIL | 16512.40 | 0.000361 | 349.67 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.843391 | 0.000107 | 0.000271 |
ROOM_2_FLR_3 FAN COIL | 0.834203 | 0.000107 | 0.000268 |
ROOM_3_MULT19_FLR_3 FAN COIL | 4.92 | 0.000611 | 0.001540 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.38 | 0.000612 | 0.001801 |
ROOM_5_FLR_3 FAN COIL | 0.765848 | 0.000107 | 0.000248 |
ROOM_6_FLR_3 FAN COIL | 0.759822 | 0.000107 | 0.000246 |
ROOM_1_FLR_6 FAN COIL | 0.222664 | 0.000034 | 0.000071 |
ROOM_2_FLR_6 FAN COIL | 0.219857 | 0.000034 | 0.000071 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.03 | 0.000161 | 0.000336 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.843391 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.834203 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 4.92 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.38 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.765848 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.759822 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.222664 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.219857 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008735 | 12.80 | 0.008500 | 0.000271 | 0.843391 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008738 | 12.80 | 0.008500 | 0.000268 | 0.834203 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008633 | 12.80 | 0.008500 | 0.001540 | 4.92 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008888 | 12.80 | 0.008500 | 0.001801 | 5.38 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008760 | 12.80 | 0.008500 | 0.000248 | 0.765848 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008762 | 12.80 | 0.008500 | 0.000246 | 0.759822 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008723 | 12.80 | 0.008500 | 0.000071 | 0.222664 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008726 | 12.80 | 0.008500 | 0.000071 | 0.219857 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008803 | 12.80 | 0.008500 | 0.000336 | 1.03 | |
VAV WITH REHEAT COOLING COIL | 28.73 | 6.70 | 0.011932 | 10.92 | 0.008500 | 0.018329 | 20.49 | 640862.03 |
FLR_3_DOAS COOLING COIL | 34.40 | 6.70 | 0.014473 | 11.91 | 0.008500 | 0.002607 | 2.05 | 91161.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.02 | 10.53 | 20.59 | 10.53 | 20.49 | 20.49 | 0.300000 | 0.513958 | 20.49 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.49 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 20.49 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.018329 | 0.000026 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003608 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002607 | 0.000183 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000361 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.025788 | 4168.67 | |
HEATSYS1 PUMP | 0.008284 | 2470.19 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.008284 | 0.994127 |
COOLSYS1 | 0.025788 | 3.09 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 378714.75 | 378714.75 | 0.008284 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.025788 | 2886.11 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.025788 | 901675.55 | 902255.41 | 102.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.204 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.584 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 7.556 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 18.316 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 7.556 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 18.316 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 7.260 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.640 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.779 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.469 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.215 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.745 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 7.772 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.152 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.181 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.251 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.499 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.499 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.772 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.592 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.772 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.592 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.169 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.672 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.499 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.499 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 12276.143 | 6.204 | 115.270 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12276.143 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 506.769 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 506.769 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 586.840 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 586.840 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1192.447 | 7.260 | 449.641 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1192.447 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 358.135 | 3.779 | 175.557 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 358.135 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 406.984 | 5.215 | 48.451 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.984 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1467.746 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1467.746 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10701.700 | 8.181 | 25.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10701.700 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1752.054 | 4.499 | 83.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1752.054 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2577.487 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2577.487 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2577.487 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2577.487 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1257.069 | 12.169 | 56.528 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1257.069 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1854.278 | 4.499 | 83.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1854.278 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 37 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 | ||
2 | RESWINDOW_U_0.248_SHGC_0.21 | 38 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.680 | 0.5995 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.312 | 3.5001E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.9511E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.1241E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1114 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.4625E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2344E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6464E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9121E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.7843E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1090 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.0450E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1217 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.4566E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9325E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3295E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2628E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3264E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.2933E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3272E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7720E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0052E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7108E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.9454E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8610E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0256E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.2933E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3272E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7720E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0052E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7108E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.9454E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8610E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0256E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 28641.97572 | 28641.97572 | 2.15848 | 2.15848 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 28.65250 | 1.44628E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1345.42784 | 1345.42784 | 5.98144E-002 | 0.85446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 3692.60302 | 3692.60302 | 0.27832 | 0.27832 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2348.35037 | 2348.35037 | 0.10440 | 0.10440 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2841.63168 | 2841.63168 | 0.21418 | 0.21418 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 31.64500 | 1.44682E-002 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 882.42606 | 882.42606 | 3.92295E-002 | 9.17335E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2978.81346 | 2978.81346 | 0.22447 | 0.22447 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.93250 | 1.44669E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1716.96298 | 1716.96298 | 7.63298E-002 | 7.63298E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1421.93804 | 1421.93804 | 0.10715 | 0.10715 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1083.96168 | 1083.96168 | 4.81889E-002 | 5.77652E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44793.95084 | 44793.95084 | 3.37584 | 3.37584 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.92500 | 1.44724E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2225.22038 | 2225.22038 | 9.89220E-002 | 9.89220E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17267.38328 | 17267.38328 | 1.30258 | 1.30258 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5741.61386 | 5741.61386 | 0.25525 | 0.67638 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 59521.58639 | 59521.58639 | 4.48746 | 4.48746 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 14731.19277 | 14731.19277 | 0.65490 | 1.89399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 8304.72243 | 8304.72243 | 0.84339 | 0.84339 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4884.04390 | 4884.04390 | 0.21839 | 0.21839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 8214.25235 | 8214.25235 | 0.83420 | 0.83420 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4886.76749 | 4886.76749 | 0.21852 | 0.21852 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 48453.36347 | 48453.36347 | 4.92028 | 4.92028 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 27927.93877 | 27927.93877 | 1.24887 | 1.24887 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 53022.78006 | 53022.78006 | 5.38472 | 5.38472 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 27994.96465 | 27994.96465 | 1.25186 | 1.25186 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 7541.16444 | 7541.16444 | 0.76585 | 0.76585 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4877.87250 | 4877.87250 | 0.21812 | 0.21812 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 7481.81950 | 7481.81950 | 0.75982 | 0.75982 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4880.59736 | 4880.59736 | 0.21824 | 0.21824 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15042.86281 | 15042.86281 | 1.13363 | 1.13363 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 7890.75347 | 7890.75347 | 0.35080 | 0.47476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2192.53966 | 2192.53966 | 0.22266 | 0.22266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1532.01512 | 1532.01512 | 6.85054E-002 | 6.85054E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2164.89108 | 2164.89108 | 0.21986 | 0.21986 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1533.06975 | 1533.06975 | 6.85526E-002 | 6.85526E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10093.83973 | 10093.83973 | 1.02510 | 1.02510 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7381.29778 | 7381.29778 | 0.33007 | 0.33007 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28588.78189 | 28588.78189 | 2.15717 | 2.15717 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5399.60951 | 5399.60951 | 0.24005 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30029.61231 | 30029.61231 | 2.26585 | 2.26585 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5512.96061 | 5512.96061 | 0.24509 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29530.97340 | 29530.97340 | 2.23139 | 2.23139 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2127.36779 | 2127.36779 | 9.45631E-002 | 0.36735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8731.50823 | 8731.50823 | 0.65800 | 0.65800 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 34.40000 | 1.44733E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5758.43499 | 5758.43499 | 0.25600 | 0.25600 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 380746.18 | 20.48902 | 20.48902 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 196617.54 | 7.32767 | 7.32767 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 51689.19 | 14.45655 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 55039.41 | 3.84112 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15848 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69858 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28214 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.45393E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72190E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28214 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7871.53072 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72190E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 231.22628 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.27832 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18363 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11884 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50868 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.07482E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.45896E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11884 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2952.66433 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.45896E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 116.15531 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21418 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27633 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.64200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13750 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73688 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37878E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.45985E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13750 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1581.64306 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.45985E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 51.04687 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22447 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55756 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.24467E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.83338E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.60477E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.63298E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2105.03554 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.60477E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 87.22245 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10715 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67388 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.80900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66847E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.65382E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.33533E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66847E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1524.72074 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.33533E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 53.57259 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.37584 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.76152E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.37584E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16290E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.96772E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.89220E-002 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2728.09668 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.96772E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 113.03926 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30258 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11048 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.77900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01471 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44850E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.38481E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01471 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10901.96198 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.38481E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 346.98433 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.48746 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22214 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.63300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84056 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63300 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71515E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.38229E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84056 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29176.16683 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.38229E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 920.63445 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84339 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.84339 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.06836E-004 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.71209E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70355 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73516E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.71209E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.84339 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4883.91047 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06836E-004 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.56710 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.83420 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.83420 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.06895E-004 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.68459E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70354 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73806E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.68459E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.83420 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4886.63398 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06895E-004 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.69004 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.92028 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 4.92028 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.10916E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.54009E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70437 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63336E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.54009E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.92028 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 27927.56729 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.10916E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1261.23458 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.38472 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.38472 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.12382E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.80093E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70343 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.88788E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.80093E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.38472 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 27994.59232 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.12382E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1264.26039 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.76585 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.76585 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.06701E-004 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.47862E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70351 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75975E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.47862E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.76585 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4877.73922 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06701E-004 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.28852 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.75982 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.75982 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.06760E-004 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.46043E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70350 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.76179E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.46043E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.75982 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4880.46401 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06760E-004 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.41151 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13363 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.62800 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71192 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.63897E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.51820E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71192 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11511.77760 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51820E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 397.08467 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.22266 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.22266 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.35120E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.13772E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70357 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72317E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.13772E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.22266 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1531.97468 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.35120E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 69.18080 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.21986 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.21986 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.35351E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.05261E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70356 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72581E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.05261E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.21986 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1533.02928 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.35351E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 69.22840 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02510 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.02510 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.61463E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.35535E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70337 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.80337E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.35535E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02510 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7381.14113 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61463E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 333.31262 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15717 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11715 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.82600 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78183 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82600 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25211E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16402E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78183 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14464.06208 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16402E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 439.31977 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26585 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11154 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.78600 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78096 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78600 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41595E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.18782E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78096 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14572.87165 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18782E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 443.12312 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23139 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.34511E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55115 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08001E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07718E-004 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55115 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4924.25099 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07718E-004 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 151.71238 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65800 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.47726 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18819 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.98303E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54457E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25600 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7060.89016 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54457E-004 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 292.58848 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.02031 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.53049 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.59452 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.53049 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.48902 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.48902 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51396 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.48902 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.48902 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.72891 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92082 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.19317E-002 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 640862.02969 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.83286E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.48902 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 164929.61657 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.60784E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3492.55945 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.48902 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.83286E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.59808E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.60784E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 34.40000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90668 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.44733E-002 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 91161.10877 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.60720E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 16512.40431 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.61209E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 349.66766 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60720E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.82645E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.61209E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.57878E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4168.67408 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 8.28440E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.99413 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 8.28440E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2470.19420 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 378714.74562 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 378714.75000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 8.28440E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.57878E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.09454 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.57878E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2886.11367 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.57878E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 901675.54911 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 902255.41000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 102.85712 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 11953.07 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4483.08 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2400.13 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3195.29 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2316.79 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 4141.05 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 16546.10 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 44283.12 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 8261.97 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 8266.57 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 47243.87 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 47357.23 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 8251.53 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 8256.14 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17494.19 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2591.46 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2593.25 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 12485.75 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 21958.02 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 22123.05 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7474.92 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10717.92 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 163755.01 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 16394.81 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 14190.93 | 11901.37 | 2289.55 | 0.84 | 3058.63 | 31.02 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 14043.49 | 11774.12 | 2269.38 | 0.84 | 3024.01 | 30.67 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 81271.54 | 68921.74 | 12349.80 | 0.85 | 18101.25 | 183.59 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 93029.19 | 76815.43 | 16213.76 | 0.83 | 19198.54 | 194.72 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 12941.82 | 10825.78 | 2116.04 | 0.84 | 2767.60 | 28.07 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 12844.56 | 10742.13 | 2102.43 | 0.84 | 2745.04 | 27.84 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3738.14 | 3139.11 | 599.03 | 0.84 | 808.05 | 8.20 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3692.72 | 3100.11 | 592.62 | 0.84 | 797.55 | 8.09 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 17453.94 | 14534.66 | 2919.28 | 0.83 | 3683.06 | 37.36 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 597468.47 | 390161.47 | 207307.01 | 0.65 | 89983.51 | 912.66 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64827.35 | 41208.20 | 23619.15 | 0.64 | 8819.06 | 89.45 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.12 | 14.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6756783851E-002 | 2.2479927067E-002 | Pass | Pass | 5.7525573113E-003 | 1.8386960130E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0210968870E-003 | 7.4093579270E-004 | Pass | Pass | 0.2901984508 | 1.7035688736 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4259324299E-002 | 2.1580126486E-002 | Pass | Pass | 1.1926152812E-002 | 3.2495711048E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6855347589E-002 | 1.8373950646E-002 | Pass | Pass | 5.8932397160E-003 | 1.7852826219E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.1717622070E-004 | 4.3139668011E-004 | Pass | Pass | 2.9141896009E-002 | 4.1878632771E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4360019142E-004 | 2.2483296911E-004 | Pass | Pass | 2.0979651014E-002 | 6.1364869111E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2189734581E-002 | 3.7048767738E-002 | Pass | Pass | 2.1418290428E-002 | 6.2147324155E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8280888612E-002 | 4.6705132017E-002 | Pass | Pass | 1.1839420655E-002 | 2.8476620191E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.1801288849E-002 | 0.1359857284 | Pass | Pass | 0.1504835277 | 0.6526755036 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3228450308E-002 | 0.1418189622 | Pass | Pass | 0.1425160654 | 0.5985567424 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.6019680901E-002 | 4.6063597044E-002 | Pass | Pass | 7.1770477274E-003 | 7.4369079137E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5001194722E-002 | 0.1362780503 | Pass | Pass | 0.3089244295 | 2.0670440539 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0573274687E-002 | 0.1322405828 | Pass | Pass | 0.1534245599 | 0.6663572071 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.1994068524E-002 | 0.1379400319 | Pass | Pass | 0.1457500928 | 0.6145385558 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.5986260970E-004 | 2.7363449041E-004 | Pass | Pass | 3.3485714964E-002 | 7.5923641538E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.2520283912E-002 | 0.2079932684 | Pass | Pass | 9.8312565379E-002 | 0.3492480704 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.4168755816E-002 | 0.2148958143 | Pass | Pass | 9.5925152653E-002 | 0.3390898590 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9989914766E-002 | 9.0185291321E-002 | Pass | Pass | 0.1332642801 | 0.4599472533 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.7928631202E-002 | 9.5862304941E-002 | Pass | Pass | 1.0550265435E-002 | 2.3136294147E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0625038893E-002 | 9.3394799377E-002 | Pass | Pass | 9.1677572215E-003 | 2.0985390224E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2105869902E-004 | 1.8646426600E-003 | Pass | Pass | 2.2283189692E-002 | 4.4132097148E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.6628820211E-003 | 7.7617981334E-003 | Pass | Pass | 1.6049704042E-002 | 3.4984154560E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2954.92 | 48.36 | 553.00 | 2148.94 | 6442.17 | 12147.39 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.408 | 0.210 | 0.290 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.408 | 0.210 | 0.290 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.408 | 0.210 | 0.290 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.408 | 0.210 | 0.290 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.408 | 0.210 | 0.290 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.408 | 0.210 | 0.290 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.408 | 0.210 | 0.290 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.408 | 0.210 | 0.290 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 432.95 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.2037 | 1978.83 | 12276.14 | LightsWired | LTG_SCH_BASEMENT | 42.56 | 168.00 | 42.52 | 0.0000 | Y | 97.97 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 7.5557 | 67.07 | 506.77 | LightsWired | LTG_SCH_RETAIL | 46.66 | 168.00 | 46.61 | 0.0000 | Y | 4.43 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 7.5557 | 77.67 | 586.84 | LightsWired | LTG_SCH_RETAIL | 46.66 | 168.00 | 46.61 | 0.0000 | Y | 5.13 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 7.2603 | 164.24 | 1192.45 | LightsWired | LTG_SCH_MECHANIC | 41.09 | 168.00 | 41.04 | 0.0000 | Y | 9.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.7794 | 94.76 | 358.14 | LightsWired | LTG_SCH_STORAGE | 31.36 | 168.00 | 31.32 | 0.0000 | Y | 2.11 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.2151 | 78.04 | 406.98 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 3.92 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 7.7715 | 188.86 | 1467.75 | LightsWired | LTG_SCH_DINING | 38.15 | 168.00 | 25.54 | 0.0000 | Y | 7.04 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.1806 | 1308.19 | 10701.70 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.53 | 0.0000 | Y | 83.42 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4993 | 1557.62 | 7008.22 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 57.85 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 7.7715 | 331.66 | 2577.49 | LightsWired | LTG_SCH_DINING | 38.15 | 168.00 | 32.02 | 0.0000 | Y | 15.49 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 7.7715 | 331.66 | 2577.49 | LightsWired | LTG_SCH_DINING | 38.15 | 168.00 | 32.02 | 0.0000 | Y | 15.49 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 12.1686 | 103.30 | 1257.07 | LightsWired | LTG_SCH_KITCHEN | 41.09 | 168.00 | 41.04 | 0.0000 | Y | 9.68 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4993 | 412.12 | 1854.28 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.31 |
Interior Lighting Total | 5.5793 | 11345.29 | 63298.26 | 293.35 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10701.70 | 749.12 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10701.70 | 749.12 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1467.75 | 572.42 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1467.75 | 572.42 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 9571.94 | AstronomicalClock | - | 83.77 | 83.77 | 150.52 | |
Exterior Lighting Total | 9571.94 | 150.52 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 378714.75 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 902255.41 | 3.11 | 902414.00 | 3.11 | 4.12 | 14.07 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9483.07 | 14190.93 | 11901.37 | 2289.55 | 0.84 | - | 3058.63 | 31.02 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9386.89 | 14043.49 | 11774.12 | 2269.38 | 0.84 | - | 3024.01 | 30.67 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 53850.61 | 81271.54 | 68921.74 | 12349.80 | 0.85 | - | 18101.25 | 183.59 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62971.16 | 93029.19 | 76815.43 | 16213.76 | 0.83 | - | 19198.54 | 194.72 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 8666.71 | 12941.82 | 10825.78 | 2116.04 | 0.84 | - | 2767.60 | 28.07 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 8603.09 | 12844.56 | 10742.13 | 2102.43 | 0.84 | - | 2745.04 | 27.84 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2495.77 | 3738.14 | 3139.11 | 599.03 | 0.84 | - | 808.05 | 8.20 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2466.00 | 3692.72 | 3100.11 | 592.62 | 0.84 | - | 797.55 | 8.09 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 11732.27 | 17453.94 | 14534.66 | 2919.28 | 0.83 | - | 3683.06 | 37.36 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 640862.03 | 597468.47 | 390161.47 | 207307.01 | 0.65 | - | 89983.51 | 912.66 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 91161.11 | 64827.35 | 41208.20 | 23619.15 | 0.64 | - | 8819.06 | 89.45 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7871.53 | 11953.07 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2952.66 | 4483.08 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1581.64 | 2400.13 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2105.04 | 3195.29 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1524.72 | 2316.79 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2728.10 | 4141.05 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10901.96 | 16546.10 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29176.17 | 44283.12 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4883.91 | 8261.97 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4886.63 | 8266.57 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 27927.57 | 47243.87 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 27994.59 | 47357.23 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4877.74 | 8251.53 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4880.46 | 8256.14 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11511.78 | 17494.19 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1531.97 | 2591.46 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1533.03 | 2593.25 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7381.14 | 12485.75 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14464.06 | 21958.02 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14572.87 | 22123.05 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 4924.25 | 7474.92 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7060.89 | 10717.92 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 164929.62 | 163755.01 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 16512.40 | 16394.81 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.84 | 593.44 | 703.64 | 1.00 | 1.24 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.83 | 586.98 | 703.64 | 1.00 | 1.24 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 4.92 | 3462.09 | 703.64 | 1.00 | 0.97 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.38 | 3788.88 | 703.64 | 1.00 | 0.97 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.77 | 538.88 | 703.64 | 1.00 | 1.27 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.76 | 534.64 | 703.64 | 1.00 | 1.27 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.22 | 156.67 | 703.64 | 1.00 | 1.95 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.22 | 154.70 | 703.64 | 1.00 | 1.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 721.30 | 703.64 | 1.00 | 1.19 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.49 | 45908.49 | 2240.64 | 1.00 | 1.11 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.025788 | 4168.67 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.008284 | 2470.19 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.025788 | 2886.11 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.95 | 0.68 | 0.60 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.95 | 0.31 | 0.04 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 28641.98 | 28641.98 | 14.47 | 2.158 | 2.158 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 24.00 | 24.00 | 0.00934 | 28.65 | 0.01446 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3692.60 | 3692.60 | 55.05 | 0.278 | 0.278 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00933 | 34.40 | 0.01447 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2841.63 | 2841.63 | 36.59 | 0.214 | 0.214 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00958 | 31.64 | 0.01447 | 0.092 | 0.00 |
MECH_FLR_1 | 2978.81 | 2978.81 | 18.14 | 0.224 | 0.224 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 24.00 | 24.00 | 0.00891 | 30.93 | 0.01447 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1421.94 | 1421.94 | 15.01 | 0.107 | 0.107 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00907 | 31.88 | 0.01447 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44793.95 | 44793.95 | 573.99 | 3.376 | 3.376 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00856 | 33.92 | 0.01447 | 0.000 | 0.00 |
CAFE_FLR_1 | 17267.38 | 17267.38 | 91.43 | 1.303 | 1.303 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01043 | 34.40 | 0.01447 | 0.676 | 0.00 |
LOBBY_FLR_1 | 59521.59 | 59521.59 | 45.50 | 4.487 | 4.487 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01016 | 34.40 | 0.01447 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 8304.72 | 8304.72 | 212.82 | 0.843 | 0.843 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00874 | 32.91 | 0.01447 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 8214.25 | 8214.25 | 210.53 | 0.834 | 0.834 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00874 | 32.75 | 0.01447 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 48453.36 | 48453.36 | 1975.77 | 4.920 | 4.920 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00863 | 34.40 | 0.01447 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 53022.78 | 53022.78 | 2161.50 | 5.385 | 5.385 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00889 | 34.02 | 0.01447 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7541.16 | 7541.16 | 193.25 | 0.766 | 0.766 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00876 | 31.50 | 0.01447 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7481.82 | 7481.82 | 191.76 | 0.760 | 0.760 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00876 | 31.03 | 0.01447 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15042.86 | 15042.86 | 38.63 | 1.134 | 1.134 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00988 | 34.30 | 0.01447 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2192.54 | 2192.54 | 56.19 | 0.223 | 0.223 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00872 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2164.89 | 2164.89 | 55.49 | 0.220 | 0.220 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00873 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10093.84 | 10093.84 | 411.48 | 1.025 | 1.025 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00880 | 34.40 | 0.01447 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28588.78 | 28588.78 | 86.20 | 2.157 | 2.157 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01050 | 34.40 | 0.01447 | 1.188 | 0.00 |
DINING_FLR_6 | 30029.61 | 30029.61 | 90.54 | 2.266 | 2.266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01040 | 34.40 | 0.01447 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29530.97 | 29530.97 | 285.86 | 2.231 | 2.231 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01016 | 33.55 | 0.01447 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8731.51 | 8731.51 | 21.19 | 0.658 | 0.658 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00917 | 34.40 | 0.01447 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1345.43 | 1345.43 | 0.68 | 0.060 | 0.854 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | -6.30 | 0.00230 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2348.35 | 2348.35 | 35.01 | 0.104 | 0.104 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00747 | -6.30 | 0.00230 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 882.43 | 882.43 | 11.36 | 0.039 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00746 | -6.30 | 0.00230 | 0.092 | 0.00 |
MECH_FLR_1 | 1716.96 | 1716.96 | 10.45 | 0.076 | 0.076 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00735 | -6.30 | 0.00230 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1083.96 | 1083.96 | 11.44 | 0.048 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00740 | -6.30 | 0.00230 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2225.22 | 2225.22 | 28.51 | 0.099 | 0.099 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00732 | -6.30 | 0.00230 | 0.000 | 0.00 |
CAFE_FLR_1 | 5741.61 | 5741.61 | 30.40 | 0.255 | 0.676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 0.676 | 0.00 |
LOBBY_FLR_1 | 14731.19 | 14731.19 | 11.26 | 0.655 | 1.894 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00747 | -6.30 | 0.00230 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4884.04 | 4884.04 | 125.16 | 0.218 | 0.218 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00742 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4886.77 | 4886.77 | 125.25 | 0.219 | 0.219 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00742 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 27927.94 | 27927.94 | 1138.81 | 1.249 | 1.249 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00745 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 27994.96 | 27994.96 | 1141.23 | 1.252 | 1.252 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4877.87 | 4877.87 | 125.00 | 0.218 | 0.218 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00742 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4880.60 | 4880.60 | 125.09 | 0.218 | 0.218 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00742 | -6.30 | 0.00230 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 7890.75 | 7890.75 | 20.26 | 0.351 | 0.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00755 | -6.30 | 0.00230 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1532.02 | 1532.02 | 39.26 | 0.069 | 0.069 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1533.07 | 1533.07 | 39.29 | 0.069 | 0.069 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00753 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7381.30 | 7381.30 | 300.90 | 0.330 | 0.330 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00754 | -6.30 | 0.00230 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5399.61 | 5399.61 | 16.28 | 0.240 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00766 | -6.30 | 0.00230 | 1.188 | 0.00 |
DINING_FLR_6 | 5512.96 | 5512.96 | 16.62 | 0.245 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00767 | -6.30 | 0.00230 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2127.37 | 2127.37 | 20.59 | 0.095 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00666 | -6.30 | 0.00230 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5758.43 | 5758.43 | 13.97 | 0.256 | 0.256 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00772 | -6.30 | 0.00230 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.49 | 20.49 | 7.33 | 7.33 | 20.4890 | 10.5305 | 20.4890 | 0.5140 | 0.3000 |
FLR_3_DOAS | 14.46 | 2.05 | 3.84 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7871.531 | 7871.531 | 1.282138 | 0.00017219 | 231.226 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7871.53 | 7871.53 | 1.282138 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00793710 | 49.4753 | 1345.43 | 0.00 | 7906.54 | 7906.54 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2952.664 | 2952.664 | 0.118843 | 0.00006459 | 116.155 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2952.66 | 2952.66 | 0.118843 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00746885 | 46.5929 | 2348.35 | 0.00 | 2967.02 | 2967.02 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1581.643 | 1581.643 | 0.137501 | 0.00003460 | 51.047 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1581.64 | 1581.64 | 0.137501 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00745577 | 46.5115 | 882.43 | 0.00 | 1588.14 | 1588.14 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2105.036 | 2105.036 | 0.076330 | 0.00004605 | 87.222 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2105.04 | 2105.04 | 0.076330 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00735221 | 45.8731 | 1716.96 | 0.00 | 2115.10 | 2115.10 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1524.721 | 1524.721 | 0.086685 | 0.00003335 | 53.573 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1524.72 | 1524.72 | 0.086685 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00740216 | 46.1811 | 1083.96 | 0.00 | 1532.64 | 1532.64 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 2728.097 | 2728.097 | 0.098922 | 0.00005968 | 113.039 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2728.10 | 2728.10 | 0.098922 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00732161 | 45.6851 | 2225.22 | 0.00 | 2741.14 | 2741.14 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10901.962 | 10901.962 | 1.014711 | 0.00023848 | 346.984 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 10901.96 | 10901.96 | 1.014711 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751545 | 46.8797 | 5741.61 | 0.00 | 10947.84 | 10947.84 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29176.167 | 29176.167 | 2.840562 | 0.00063823 | 920.634 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 29176.17 | 29176.17 | 2.840562 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00746556 | 46.5718 | 14731.19 | 0.00 | 29299.33 | 29299.33 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9483.067 | -999.000 | 0.843391 | 0.00027121 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 9483.07 | 8989.14 | 0.843391 | 21.70 | 15.40 | 0.00873516 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00873516 | 54.0148 | 8304.72 | 0.00 | 9835.29 | 9637.87 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4883.910 | 4883.910 | 0.218394 | 0.00010684 | 220.567 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 4883.91 | 4883.91 | 0.218394 | 21.11 | 14.00 | 0.00741649 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00741649 | 45.9559 | 4884.04 | 0.00 | 5466.02 | 5466.02 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 9386.892 | -999.000 | 0.834203 | 0.00026846 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 9386.89 | 8892.27 | 0.834203 | 21.70 | 15.41 | 0.00873806 | 12.80 | 11.77 | 0.00850000 | 32.75 | 0.01447025 | 23.10 | 0.0000 | 21.11 | 0.00873806 | 54.0325 | 8214.25 | 0.00 | 9735.36 | 9532.83 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4886.634 | 4886.634 | 0.218516 | 0.00010690 | 220.690 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 4886.63 | 4886.63 | 0.218516 | 21.11 | 14.00 | 0.00741682 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00741682 | 45.9579 | 4886.77 | 0.00 | 5469.07 | 5469.07 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 53850.615 | -999.000 | 4.920282 | 0.00154009 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 53850.61 | 52223.37 | 4.920282 | 21.70 | 15.31 | 0.00863336 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00863336 | 53.3916 | 48453.36 | 0.00 | 55872.49 | 55872.49 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 27927.567 | 27927.567 | 1.248865 | 0.00061092 | 1261.235 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 27927.57 | 27927.57 | 1.248865 | 21.11 | 14.04 | 0.00745497 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00745497 | 46.1904 | 27927.94 | 0.00 | 31256.57 | 31256.57 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62971.160 | -999.000 | 5.384720 | 0.00180093 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 62971.16 | 57738.22 | 5.384720 | 21.70 | 15.54 | 0.00888788 | 12.80 | 11.77 | 0.00850000 | 34.02 | 0.01447257 | 23.44 | 0.0000 | 21.11 | 0.00888788 | 54.9456 | 53022.78 | 0.00 | 65267.55 | 61542.05 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 27994.592 | 27994.592 | 1.251863 | 0.00061238 | 1264.260 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 27994.59 | 27994.59 | 1.251863 | 21.11 | 14.04 | 0.00745601 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00745601 | 46.1968 | 27994.96 | 0.00 | 31331.58 | 31331.58 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 8666.714 | -999.000 | 0.765848 | 0.00024786 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 8666.71 | 8170.80 | 0.765848 | 21.70 | 15.42 | 0.00875975 | 12.80 | 11.77 | 0.00850000 | 31.50 | 0.01446797 | 22.76 | 0.0000 | 21.11 | 0.00875975 | 54.1648 | 7541.16 | 0.00 | 8987.15 | 8751.41 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4877.739 | 4877.739 | 0.218118 | 0.00010670 | 220.289 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 4877.74 | 4877.74 | 0.218118 | 21.11 | 14.00 | 0.00741582 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00741582 | 45.9519 | 4877.87 | 0.00 | 5459.12 | 5459.12 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 8603.093 | -999.000 | 0.759822 | 0.00024604 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 8603.09 | 8107.17 | 0.759822 | 21.70 | 15.43 | 0.00876179 | 12.80 | 11.77 | 0.00850000 | 31.03 | 0.01446710 | 22.63 | 0.0000 | 21.11 | 0.00876179 | 54.1773 | 7481.82 | 0.00 | 8921.06 | 8682.51 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4880.464 | 4880.464 | 0.218240 | 0.00010676 | 220.412 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 4880.46 | 4880.46 | 0.218240 | 21.11 | 14.00 | 0.00741616 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00741616 | 45.9539 | 4880.60 | 0.00 | 5462.17 | 5462.17 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11511.778 | 11511.778 | 0.711917 | 0.00025182 | 397.085 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 11511.78 | 11511.78 | 0.711917 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00754930 | 47.0873 | 7890.75 | 0.00 | 11572.05 | 11572.05 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2495.766 | -999.000 | 0.222664 | 0.00007138 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2495.77 | 2372.07 | 0.222664 | 21.70 | 15.39 | 0.00872317 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00872317 | 53.9417 | 2192.54 | 0.00 | 2588.28 | 2544.27 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1531.975 | 1531.975 | 0.068505 | 0.00003351 | 69.181 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1531.97 | 1531.97 | 0.068505 | 21.11 | 14.10 | 0.00752499 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00752499 | 46.6202 | 1532.02 | 0.00 | 1714.57 | 1714.57 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2466.003 | -999.000 | 0.219857 | 0.00007053 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2466.00 | 2342.41 | 0.219857 | 21.70 | 15.39 | 0.00872581 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00872581 | 53.9578 | 2164.89 | 0.00 | 2557.37 | 2512.18 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1533.029 | 1533.029 | 0.068553 | 0.00003354 | 69.228 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1533.03 | 1533.03 | 0.068553 | 21.11 | 14.10 | 0.00752532 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00752532 | 46.6223 | 1533.07 | 0.00 | 1715.75 | 1715.75 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11732.269 | -999.000 | 1.025098 | 0.00033554 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 11732.27 | 10955.66 | 1.025098 | 21.70 | 15.46 | 0.00880337 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00880337 | 54.4310 | 10093.84 | 0.00 | 12162.66 | 11713.23 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7381.141 | 7381.141 | 0.330065 | 0.00016146 | 333.313 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 7381.14 | 7381.14 | 0.330065 | 21.11 | 14.12 | 0.00754434 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00754434 | 46.7383 | 7381.30 | 0.00 | 8260.93 | 8260.93 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14464.062 | 14464.062 | 1.781825 | 0.00031640 | 439.320 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14464.06 | 14464.06 | 1.781825 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00766041 | 47.7723 | 5399.61 | 0.00 | 14526.24 | 14526.24 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14572.872 | 14572.872 | 1.780961 | 0.00031878 | 443.123 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 14572.87 | 14572.87 | 1.780961 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00766699 | 47.8132 | 5512.96 | 0.00 | 14635.48 | 14635.48 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 4924.251 | 4924.251 | 0.551154 | 0.00010772 | 151.712 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 4924.25 | 4924.25 | 0.551154 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00665544 | 41.5784 | 2127.37 | 0.00 | 4945.26 | 4945.26 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7060.890 | 7060.890 | 0.256001 | 0.00015446 | 292.588 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 7060.89 | 7060.89 | 0.256001 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00771801 | 48.1271 | 5758.43 | 0.00 | 7094.66 | 7094.66 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 640862.030 | -999.000 | 20.489019 | 0.01832857 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 640862.03 | 431343.94 | 20.489019 | 28.73 | 20.24 | 0.01193169 | 10.92 | 10.92 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 45.5327 | 23.99 | 0.00981777 | 50.8733 | 271687.38 | 0.00 | 654633.52 | 429778.92 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 164929.617 | 164929.617 | 6.146706 | 0.00360784 | 3492.559 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 164929.62 | 164929.62 | 6.146706 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 151.7756 | 21.01 | 0.00753101 | 46.9540 | 55933.35 | 0.00 | 142556.66 | 142556.66 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 91161.11 | 55491.40 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 11.91 | 11.41 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 99.9965 | 21.11 | 0.00876801 | 54.2139 | 141928.65 | 0.00 | 92683.44 | 56170.47 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 16512.404 | 16512.404 | 0.615395 | 0.00036121 | 349.668 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 16512.40 | 16512.40 | 0.615395 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 333.3216 | 21.11 | 0.00745618 | 46.1979 | 85898.57 | 0.00 | 14272.47 | 14272.47 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7871.531 | 7871.531 | 1.282138 | 0.00017219 | 231.226 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 2.0375 | 2.078485 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7871.53 | 7871.53 | 1.0000 | 1.48853239 | 1.282138 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.17217239 | 60.00 | 48.89 | 11.11 | 0.000 | 7871.53 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00793710 | 21.00 | 0.00793710 | 49.4753 | 1345.43 | 0.00 | 7906.54 | 7906.54 | 1.48853239 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.81 | 15.15 | 0.00800000 | 42246.4 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2952.664 | 2952.664 | 0.118843 | 0.00006459 | 116.155 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 0.7643 | 0.779654 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2952.66 | 2952.66 | 1.0000 | 0.13797431 | 0.118843 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.06458303 | 60.00 | 48.89 | 11.11 | 0.000 | 2952.66 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00746885 | 21.00 | 0.00746885 | 46.5929 | 2348.35 | 0.00 | 2967.02 | 2967.02 | 0.13797431 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.69 | 20.49 | 0.00800000 | 58438.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1581.643 | 1581.643 | 0.137501 | 0.00003460 | 51.047 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 0.4094 | 0.417634 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1581.64 | 1581.64 | 1.0000 | 0.15963572 | 0.137501 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.03459496 | 60.00 | 48.89 | 11.11 | 0.000 | 1581.64 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00745577 | 21.00 | 0.00745577 | 46.5115 | 882.43 | 0.00 | 1588.14 | 1588.14 | 0.15963572 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.36 | 16.79 | 0.00800000 | 46883.3 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2105.036 | 2105.036 | 0.076330 | 0.00004605 | 87.222 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 0.5449 | 0.555837 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 2105.04 | 2105.04 | 1.0000 | 0.08861705 | 0.076330 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.04604301 | 60.00 | 48.89 | 11.11 | 0.000 | 2105.04 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00735221 | 21.00 | 0.00735221 | 45.8731 | 1716.96 | 0.00 | 2115.10 | 2115.10 | 0.08861705 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60802.6 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1524.721 | 1524.721 | 0.086685 | 0.00003335 | 53.573 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 0.3947 | 0.402604 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1524.72 | 1524.72 | 1.0000 | 0.10063886 | 0.086685 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.03334991 | 60.00 | 48.89 | 11.11 | 0.000 | 1524.72 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00740216 | 21.00 | 0.00740216 | 46.1811 | 1083.96 | 0.00 | 1532.64 | 1532.64 | 0.10063886 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.53 | 18.55 | 0.00800000 | 52163.8 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2728.097 | 2728.097 | 0.098922 | 0.00005968 | 113.039 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 0.7061 | 0.720357 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2728.10 | 2728.10 | 1.0000 | 0.11484613 | 0.098922 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05967110 | 60.00 | 48.89 | 11.11 | 0.000 | 2728.10 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00732161 | 21.00 | 0.00732161 | 45.6851 | 2225.22 | 0.00 | 2741.14 | 2741.14 | 0.11484613 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60802.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10901.962 | 10901.962 | 1.014711 | 0.00023848 | 346.984 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 2.8219 | 2.878674 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 10901.96 | 10901.96 | 1.0000 | 1.17805595 | 1.014711 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.23845639 | 60.00 | 48.89 | 11.11 | 0.000 | 10901.96 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00751545 | 21.00 | 0.00751545 | 46.8797 | 5741.61 | 0.00 | 10947.84 | 10947.84 | 1.17805595 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.71 | 16.57 | 0.00800000 | 46227.9 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29176.167 | 29176.167 | 2.840562 | 0.00063823 | 920.634 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 7.5520 | 7.703995 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 29176.17 | 29176.17 | 1.0000 | 3.29782534 | 2.840562 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.63816435 | 60.00 | 48.89 | 11.11 | 0.000 | 29176.17 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00746556 | 21.00 | 0.00746556 | 46.5718 | 14731.19 | 0.00 | 29299.33 | 29299.33 | 3.29782534 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.31 | 16.42 | 0.00800000 | 45819.2 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9483.067 | -999.000 | 0.843391 | 0.00027121 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0782 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.843391 | 0.97915698 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 1.0517 | 1.051696 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 9483.07 | 8989.14 | 1.0000 | 0.97915698 | 0.843391 | 21.70 | 15.40 | 0.00873516 | 44007.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.27118179 | 6.70 | 15.03 | 8.33 | 0.000 | 9483.07 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00873516 | 21.11 | 0.00873516 | 54.0148 | 8304.72 | 0.00 | 9835.29 | 9637.87 | 0.97915698 | 21.70 | 15.77 | 0.00873516 | 44007.1 | 12.06 | 11.95 | 0.00865526 | 33962.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4883.910 | 4883.910 | 0.218394 | 0.00010684 | 220.567 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.843391 | 0.97915698 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 1.2642 | 1.289601 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 4883.91 | 4883.91 | 1.0000 | 0.25355055 | 0.218394 | 21.11 | 14.00 | 0.00741649 | 40051.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10682478 | 60.00 | 48.89 | 11.11 | 0.000 | 4883.91 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00741649 | 21.11 | 0.00741649 | 45.9559 | 4884.04 | 0.00 | 5466.02 | 5466.02 | 0.25355055 | 16.60 | 12.58 | 0.00741649 | 35457.4 | 37.76 | 20.08 | 0.00741649 | 57015.3 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9386.892 | -999.000 | 0.834203 | 0.00026846 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0836 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.834203 | 0.96849028 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 1.0410 | 1.041030 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 9386.89 | 8892.27 | 1.0000 | 0.96849028 | 0.834203 | 21.70 | 15.41 | 0.00873806 | 44014.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.26843153 | 6.70 | 15.03 | 8.33 | 0.000 | 9386.89 | 32.75 | 0.01447025 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00873806 | 21.11 | 0.00873806 | 54.0325 | 8214.25 | 0.00 | 9735.36 | 9532.83 | 0.96849028 | 21.70 | 15.77 | 0.00873806 | 44014.5 | 12.06 | 11.95 | 0.00865519 | 33962.4 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4886.634 | 4886.634 | 0.218516 | 0.00010690 | 220.690 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.834203 | 0.96849028 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 1.2649 | 1.290320 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 4886.63 | 4886.63 | 1.0000 | 0.25369194 | 0.218516 | 21.11 | 14.00 | 0.00741682 | 40052.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10688435 | 60.00 | 48.89 | 11.11 | 0.000 | 4886.63 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00741682 | 21.11 | 0.00741682 | 45.9579 | 4886.77 | 0.00 | 5469.07 | 5469.07 | 0.25369194 | 16.60 | 12.58 | 0.00741682 | 35458.2 | 37.76 | 20.08 | 0.00741682 | 57016.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53850.615 | -999.000 | 4.920282 | 0.00154009 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8890 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.920282 | 5.71233251 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 5.9723 | 5.972171 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 53850.61 | 52223.37 | 1.0000 | 5.71233251 | 4.920282 | 21.70 | 15.31 | 0.00863336 | 43749.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 1.53993490 | 6.70 | 15.03 | 8.33 | 0.000 | 53850.61 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00863336 | 21.11 | 0.00863336 | 53.3916 | 48453.36 | 0.00 | 55872.49 | 55872.49 | 5.71233251 | 21.70 | 15.68 | 0.00863336 | 43749.3 | 12.12 | 11.95 | 0.00863336 | 33968.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27927.567 | 27927.567 | 1.248865 | 0.00061092 | 1261.235 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.920282 | 5.71233251 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 7.2288 | 7.374302 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 27927.57 | 27927.57 | 1.0000 | 1.44990332 | 1.248865 | 21.11 | 14.04 | 0.00745497 | 40149.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.61085399 | 60.00 | 48.89 | 11.11 | 0.000 | 27927.57 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00745497 | 21.11 | 0.00745497 | 46.1904 | 27927.94 | 0.00 | 31256.57 | 31256.57 | 1.44990332 | 16.60 | 12.62 | 0.00745497 | 35554.8 | 37.76 | 20.10 | 0.00745497 | 57112.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62971.160 | -999.000 | 5.384720 | 0.00180093 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3621 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.384720 | 6.25153342 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 6.9838 | 6.983663 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 62971.16 | 57738.22 | 1.0000 | 6.25153342 | 5.384720 | 21.70 | 15.54 | 0.00888788 | 44395.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 1.80074985 | 6.70 | 15.03 | 8.33 | 0.000 | 62971.16 | 34.02 | 0.01447257 | 23.44 | 0.00000000 | 0.0000 | 21.11 | 0.00888788 | 21.11 | 0.00888788 | 54.9456 | 53022.78 | 0.00 | 65267.55 | 61542.05 | 6.25153342 | 21.70 | 15.90 | 0.00888788 | 44395.1 | 12.07 | 11.95 | 0.00865171 | 33954.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27994.592 | 27994.592 | 1.251863 | 0.00061238 | 1264.260 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.384720 | 6.25153342 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 7.2462 | 7.392000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 27994.59 | 27994.59 | 1.0000 | 1.45338303 | 1.251863 | 21.11 | 14.04 | 0.00745601 | 40152.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.61232002 | 60.00 | 48.89 | 11.11 | 0.000 | 27994.59 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00745601 | 21.11 | 0.00745601 | 46.1968 | 27994.96 | 0.00 | 31331.58 | 31331.58 | 1.45338303 | 16.60 | 12.62 | 0.00745601 | 35557.5 | 37.76 | 20.10 | 0.00745601 | 57115.2 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8666.714 | -999.000 | 0.765848 | 0.00024786 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1239 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.765848 | 0.88913212 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 0.9612 | 0.961161 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 8666.71 | 8170.80 | 1.0000 | 0.88913212 | 0.765848 | 21.70 | 15.42 | 0.00875975 | 44069.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.24783701 | 6.70 | 15.03 | 8.33 | 0.000 | 8666.71 | 31.50 | 0.01446797 | 22.76 | 0.00000000 | 0.0000 | 21.11 | 0.00875975 | 21.11 | 0.00875975 | 54.1648 | 7541.16 | 0.00 | 8987.15 | 8751.41 | 0.88913212 | 21.70 | 15.79 | 0.00875975 | 44069.6 | 12.06 | 11.95 | 0.00865468 | 33961.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4877.739 | 4877.739 | 0.218118 | 0.00010670 | 220.289 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.765848 | 0.88913212 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 1.2626 | 1.287972 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 4877.74 | 4877.74 | 1.0000 | 0.25323017 | 0.218118 | 21.11 | 14.00 | 0.00741582 | 40050.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10668980 | 60.00 | 48.89 | 11.11 | 0.000 | 4877.74 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00741582 | 21.11 | 0.00741582 | 45.9519 | 4877.87 | 0.00 | 5459.12 | 5459.12 | 0.25323017 | 16.60 | 12.58 | 0.00741582 | 35455.7 | 37.76 | 20.07 | 0.00741582 | 57013.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8603.093 | -999.000 | 0.759822 | 0.00024604 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1277 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.759822 | 0.88213574 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 0.9541 | 0.954105 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 8603.09 | 8107.17 | 1.0000 | 0.88213574 | 0.759822 | 21.70 | 15.43 | 0.00876179 | 44074.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.24601769 | 6.70 | 15.03 | 8.33 | 0.000 | 8603.09 | 31.03 | 0.01446710 | 22.63 | 0.00000000 | 0.0000 | 21.11 | 0.00876179 | 21.11 | 0.00876179 | 54.1773 | 7481.82 | 0.00 | 8921.06 | 8682.51 | 0.88213574 | 21.70 | 15.79 | 0.00876179 | 44074.8 | 12.06 | 11.95 | 0.00865463 | 33961.7 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4880.464 | 4880.464 | 0.218240 | 0.00010676 | 220.412 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.759822 | 0.88213574 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 1.2633 | 1.288691 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 4880.46 | 4880.46 | 1.0000 | 0.25337163 | 0.218240 | 21.11 | 14.00 | 0.00741616 | 40050.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10674940 | 60.00 | 48.89 | 11.11 | 0.000 | 4880.46 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00741616 | 21.11 | 0.00741616 | 45.9539 | 4880.60 | 0.00 | 5462.17 | 5462.17 | 0.25337163 | 16.60 | 12.58 | 0.00741616 | 35456.6 | 37.76 | 20.08 | 0.00741616 | 57014.5 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11511.778 | 11511.778 | 0.711917 | 0.00025182 | 397.085 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 2.9797 | 3.039696 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 11511.78 | 11511.78 | 1.0000 | 0.82651886 | 0.711917 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.25179477 | 60.00 | 48.89 | 11.11 | 0.000 | 11511.78 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00754930 | 21.00 | 0.00754930 | 47.0873 | 7890.75 | 0.00 | 11572.05 | 11572.05 | 0.82651886 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.33 | 18.15 | 0.00800000 | 50935.7 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2495.766 | -999.000 | 0.222664 | 0.00007138 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0559 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.222664 | 0.25850807 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 0.2768 | 0.276787 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2495.77 | 2372.07 | 1.0000 | 0.25850807 | 0.222664 | 21.70 | 15.39 | 0.00872317 | 43976.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.07136997 | 6.70 | 15.03 | 8.33 | 0.000 | 2495.77 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00872317 | 21.11 | 0.00872317 | 53.9417 | 2192.54 | 0.00 | 2588.28 | 2544.27 | 0.25850807 | 21.70 | 15.76 | 0.00872317 | 43976.7 | 12.06 | 11.95 | 0.00865571 | 33964.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1531.975 | 1531.975 | 0.068505 | 0.00003351 | 69.181 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.222664 | 0.25850807 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 0.3965 | 0.404519 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1531.97 | 1531.97 | 1.0000 | 0.07953319 | 0.068505 | 21.11 | 14.10 | 0.00752499 | 40327.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.03350857 | 60.00 | 48.89 | 11.11 | 0.000 | 1531.97 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00752499 | 21.11 | 0.00752499 | 46.6202 | 1532.02 | 0.00 | 1714.57 | 1714.57 | 0.07953319 | 16.60 | 12.69 | 0.00752499 | 35732.1 | 37.76 | 20.16 | 0.00752499 | 57290.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2466.003 | -999.000 | 0.219857 | 0.00007053 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0608 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.219857 | 0.25524835 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 0.2735 | 0.273486 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2466.00 | 2342.41 | 1.0000 | 0.25524835 | 0.219857 | 21.70 | 15.39 | 0.00872581 | 43983.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.07051887 | 6.70 | 15.03 | 8.33 | 0.000 | 2466.00 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00872581 | 21.11 | 0.00872581 | 53.9578 | 2164.89 | 0.00 | 2557.37 | 2512.18 | 0.25524835 | 21.70 | 15.76 | 0.00872581 | 43983.4 | 12.06 | 11.95 | 0.00865565 | 33964.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1533.029 | 1533.029 | 0.068553 | 0.00003354 | 69.228 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.219857 | 0.25524835 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 0.3968 | 0.404798 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1533.03 | 1533.03 | 1.0000 | 0.07958794 | 0.068553 | 21.11 | 14.10 | 0.00752532 | 40328.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.03353164 | 60.00 | 48.89 | 11.11 | 0.000 | 1533.03 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00752532 | 21.11 | 0.00752532 | 46.6223 | 1533.07 | 0.00 | 1715.75 | 1715.75 | 0.07958794 | 16.60 | 12.69 | 0.00752532 | 35732.9 | 37.76 | 20.16 | 0.00752532 | 57290.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11732.269 | -999.000 | 1.025098 | 0.00033554 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2050 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.025098 | 1.19011515 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 1.3012 | 1.301139 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 11732.27 | 10955.66 | 1.0000 | 1.19011515 | 1.025098 | 21.70 | 15.46 | 0.00880337 | 44180.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.33550090 | 6.70 | 15.03 | 8.33 | 0.000 | 11732.27 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00880337 | 21.11 | 0.00880337 | 54.4310 | 10093.84 | 0.00 | 12162.66 | 11713.23 | 1.19011515 | 21.70 | 15.83 | 0.00880337 | 44180.3 | 12.07 | 11.95 | 0.00865372 | 33960.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7381.141 | 7381.141 | 0.330065 | 0.00016146 | 333.313 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.025098 | 1.19011515 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 1.9105 | 1.948998 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 7381.14 | 7381.14 | 1.0000 | 0.38319824 | 0.330065 | 21.11 | 14.12 | 0.00754434 | 40376.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.16144620 | 60.00 | 48.89 | 11.11 | 0.000 | 7381.14 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00754434 | 21.11 | 0.00754434 | 46.7383 | 7381.30 | 0.00 | 8260.93 | 8260.93 | 0.38319824 | 16.60 | 12.71 | 0.00754434 | 35781.1 | 37.76 | 20.17 | 0.00754434 | 57338.9 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14464.062 | 14464.062 | 1.781825 | 0.00031640 | 439.320 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 3.7439 | 3.819250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 14464.06 | 14464.06 | 1.0000 | 2.06865751 | 1.781825 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.31636948 | 60.00 | 48.89 | 11.11 | 0.000 | 14464.06 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00766041 | 21.00 | 0.00766041 | 47.7723 | 5399.61 | 0.00 | 14526.24 | 14526.24 | 2.06865751 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.49 | 15.77 | 0.00800000 | 43956.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14572.872 | 14572.872 | 1.780961 | 0.00031878 | 443.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 3.7721 | 3.847981 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 14572.87 | 14572.87 | 1.0000 | 2.06765368 | 1.780961 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.31874945 | 60.00 | 48.89 | 11.11 | 0.000 | 14572.87 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00766699 | 21.00 | 0.00766699 | 47.8132 | 5512.96 | 0.00 | 14635.48 | 14635.48 | 2.06765368 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.54 | 15.79 | 0.00800000 | 44013.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4924.251 | 4924.251 | 0.551154 | 0.00010772 | 151.712 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 1.2746 | 1.300253 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 4924.25 | 4924.25 | 1.0000 | 0.63987691 | 0.551154 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10770714 | 60.00 | 48.89 | 11.11 | 0.000 | 4924.25 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.52 | 0.00665544 | 21.00 | 0.00665544 | 41.5784 | 2127.37 | 0.00 | 4945.26 | 4945.26 | 0.63987691 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.18 | 16.02 | 0.00800000 | 44663.2 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7060.890 | 7060.890 | 0.256001 | 0.00015446 | 292.588 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 1.8277 | 1.864435 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 7060.89 | 7060.89 | 1.0000 | 0.29721127 | 0.256001 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.15444141 | 60.00 | 48.89 | 11.11 | 0.000 | 7060.89 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00771801 | 21.00 | 0.00771801 | 48.1271 | 5758.43 | 0.00 | 7094.66 | 7094.66 | 0.29721127 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60805.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 640862.030 | -999.000 | 20.489019 | 0.01832857 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.0204 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.489019 | 23.78727040 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 71.0746 | 71.074571 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 640862.03 | 431343.94 | 1.0000 | 23.78727040 | 20.489019 | 28.73 | 20.24 | 0.01193169 | 59345.6 | 10.92 | 10.92 | 0.00850000 | 32404.2 | 18.32670322 | 6.70 | 15.03 | 8.33 | 45908.487 | 594953.54 | 34.40 | 0.01447326 | 23.54 | 9.32920000 | 45.5327 | 23.99 | 0.00980702 | 23.99 | 0.00981777 | 50.8733 | 271687.38 | 0.00 | 654633.52 | 429778.92 | 23.78727040 | 28.73 | 20.65 | 0.01193169 | 59345.6 | 11.14 | 11.08 | 0.00818305 | 31825.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 164929.617 | 164929.617 | 6.146706 | 0.00360784 | 3492.559 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.489019 | 23.78727040 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 42.6907 | 43.549827 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 164929.62 | 164929.62 | 1.0000 | 7.13618112 | 6.146706 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 3.60747191 | 60.00 | 48.89 | 11.11 | 0.000 | 164929.62 | -6.30 | 0.00229779 | -6.30 | 9.32920000 | 151.7756 | 20.98 | 0.00754375 | 21.01 | 0.00753101 | 46.9540 | 55933.35 | 0.00 | 142556.66 | 142556.66 | 7.13618112 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 22.60 | 9.79 | 0.00229779 | 28548.8 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.7451 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 25.78517594 | 15.03 | 6.70 | 8.33 | 901675.55 | 10.1102 | 10.110190 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 91161.11 | 55491.40 | 1.0000 | 2.38153119 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 71688.8 | 11.91 | 11.41 | 0.00850000 | 33410.4 | 2.60693021 | 6.70 | 15.03 | 8.33 | 2195.006 | 88966.10 | 34.40 | 0.01447326 | 23.54 | 2.05124512 | 99.9965 | 21.11 | 0.00877332 | 21.11 | 0.00876801 | 54.2139 | 141928.65 | 0.00 | 92683.44 | 56170.47 | 2.38153119 | 34.40 | 23.99 | 0.01447326 | 71688.8 | 11.54 | 11.47 | 0.00839502 | 32771.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16512.404 | 16512.404 | 0.615395 | 0.00036121 | 349.668 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 8.28355049 | 48.89 | 60.00 | 11.11 | 386336.53 | 4.2741 | 4.360117 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 16512.40 | 16512.40 | 1.0000 | 0.71445936 | 0.615395 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 0.36117246 | 60.00 | 48.89 | 11.11 | 0.000 | 16512.40 | -6.30 | 0.00229779 | -6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00745671 | 21.11 | 0.00745618 | 46.1979 | 85898.57 | 0.00 | 14272.47 | 14272.47 | 0.71445936 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 22.60 | 9.79 | 0.00229779 | 28548.8 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 20.49 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 708.67 | 7078.67 | 157.33 |
RETAIL_1_FLR_1 | 3611.67 | 5778.83 | 1219.17 |
RETAIL_2_FLR_1 | 1462.00 | 7458.50 | 742.83 |
MECH_FLR_1 | 3502.33 | 4401.17 | 275.00 |
STORAGE_FLR_1 | 653.50 | 8755.00 | 653.50 |
LAUNDRY_FLR_1 | 8760.00 | 4675.50 | 4675.50 |
CAFE_FLR_1 | 1619.50 | 7983.67 | 1361.67 |
LOBBY_FLR_1 | 2062.00 | 7424.33 | 1470.00 |
ROOM_1_FLR_3 | 1001.17 | 8307.50 | 1001.17 |
ROOM_2_FLR_3 | 1864.50 | 8199.17 | 1823.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1079.50 | 8757.00 | 1079.50 |
ROOM_5_FLR_3 | 941.67 | 8249.00 | 940.83 |
ROOM_6_FLR_3 | 1838.17 | 8171.17 | 1786.33 |
CORRIDOR_FLR_3 | 1288.67 | 8618.67 | 1288.17 |
ROOM_1_FLR_6 | 1688.50 | 8107.00 | 1677.67 |
ROOM_2_FLR_6 | 2531.50 | 7995.17 | 2457.50 |
ROOM_3_MULT9_FLR_6 | 622.67 | 8323.67 | 621.33 |
BANQUET_FLR_6 | 2382.00 | 6688.50 | 1379.83 |
DINING_FLR_6 | 3362.50 | 5513.83 | 1388.33 |
KITCHEN_FLR_6 | 8757.00 | 6526.33 | 6526.33 |
CORRIDOR_FLR_6 | 3943.00 | 5327.17 | 1097.67 |
Facility | 8760.00 | 8760.00 | 7943.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.33 | 0.00 | 0.33 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 2.67 | 0.00 | 2.67 |
ROOM_2_FLR_3 | 0.00 | 7.67 | 0.00 | 7.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 27.83 | 0.00 | 27.83 |
ROOM_5_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_6_FLR_3 | 0.00 | 31.33 | 0.00 | 31.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 10.17 | 0.00 | 10.17 |
ROOM_2_FLR_6 | 0.00 | 13.50 | 0.00 | 13.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 11.50 | 0.00 | 11.50 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 13.83 | 0.00 | 13.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 77.00 | 0.00 | 77.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.724 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.277 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.206 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.144 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.620 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.661 | 0.146 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.652 | 0.106 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.486 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.175 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.175 | 0.000 | 0.069 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.078 | 0.000 | 0.108 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.175 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.175 | 0.000 | 0.069 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.404 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.341 | 0.175 | 0.000 | 0.082 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.342 | 0.175 | 0.000 | 0.081 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.388 | 0.142 | 0.000 | 0.130 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.768 | 0.050 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.788 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 15.927 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.485 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.522 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.916 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.910 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.007 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.452 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 5.885 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.678 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.132 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.295 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.604 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.629 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.743 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.309 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.047 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.173 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.036 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 30101343.41 | 0.00 | 30101343.41 | 0.00 | 30101343.41 | 26946214.98 | 5089.53 | 92.32 | 3578.15 | 0.00 |
RETAIL_1_FLR_1 | 2920382.02 | 0.00 | 2920382.02 | 310220.85 | 3230602.88 | 2498216.28 | 3923.35 | 127.64 | 4709.01 | 0.00 |
RETAIL_2_FLR_1 | 3200487.75 | 0.00 | 3200487.75 | 119745.64 | 3320233.39 | 2294951.32 | 721.75 | 574.66 | 7463.59 | 0.00 |
MECH_FLR_1 | 798574.21 | 0.00 | 798574.21 | 283007.56 | 1081581.77 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2014115.25 | 0.00 | 2014115.25 | 163279.77 | 2177395.03 | 1821682.01 | 5210.95 | 64.98 | 3484.07 | 0.00 |
LAUNDRY_FLR_1 | 41569126.61 | 0.00 | 41569126.61 | 386432.37 | 41955558.98 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23576823.49 | 0.00 | 23576823.49 | 685760.76 | 24262584.25 | 14544917.54 | 259.33 | 289.83 | 8210.83 | 0.00 |
LOBBY_FLR_1 | 66280693.29 | 0.00 | 66280693.29 | 1959375.13 | 68240068.43 | 59728886.00 | 5107.27 | 120.84 | 3531.90 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 70115.73 | 1476192.57 | 180061.18 | 1656253.74 | 1946875.62 | 2433.33 | 5505.17 | 821.50 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 70975.97 | 1476888.06 | 180047.44 | 1656935.50 | 1946647.51 | 2433.33 | 5508.71 | 817.95 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 3045.33 | 1102957.30 | 50239.09 | 1153196.38 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 395.17 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 69664.57 | 19140018.71 | 50252.83 | 19190271.53 | 26405105.73 | 2433.33 | 5550.23 | 776.43 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 70133.25 | 1476210.08 | 180061.18 | 1656271.26 | 1946875.62 | 2433.33 | 5505.17 | 821.50 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 70406.51 | 1476318.60 | 180047.44 | 1656366.04 | 1946647.51 | 2433.33 | 5505.17 | 821.50 | 0.00 |
CORRIDOR_FLR_3 | 16541366.47 | 0.00 | 16541366.47 | 217730.19 | 16759096.66 | 14972100.18 | 5215.09 | 63.99 | 3480.92 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 83798.73 | 435317.94 | 180098.20 | 615416.14 | 486718.90 | 2190.83 | 5506.06 | 1063.12 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 82916.37 | 434394.40 | 180084.46 | 614478.86 | 486661.88 | 2193.42 | 5514.08 | 1052.50 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 83897.11 | 2342228.52 | 92144.54 | 2434373.06 | 3126920.42 | 2433.33 | 5502.50 | 824.17 | 0.00 |
BANQUET_FLR_6 | 41505361.61 | 0.00 | 41505361.61 | 439754.55 | 41945116.16 | 37458366.31 | 5195.37 | 80.41 | 3484.22 | 0.00 |
DINING_FLR_6 | 41632364.15 | 0.00 | 41632364.15 | 439754.55 | 42072118.69 | 37458366.31 | 5095.12 | 105.36 | 3559.52 | 0.00 |
KITCHEN_FLR_6 | 42964193.19 | 0.00 | 42964193.19 | 393682.28 | 43357875.47 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 5229053.99 | 0.00 | 5229053.99 | 385314.24 | 5614368.23 | 3961413.96 | 2655.03 | 87.28 | 6017.69 | 0.00 |
Total Facility | 0.19E+10 | 7574267.17 | 0.20E+10 | 18144986.26 | 0.20E+10 | 0.43E+10 | 8760.00 | 6039.11 | 8760.00 | 395.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9545 | 0.0000 | 0.9545 | 0.0000 | 0.9545 | 0.8545 | 5089.53 | 92.32 | 3578.15 |
RETAIL_1_FLR_1 | 0.0926 | 0.0000 | 0.0926 | 0.0098 | 0.1024 | 0.0792 | 3923.35 | 127.64 | 4709.01 |
RETAIL_2_FLR_1 | 0.1015 | 0.0000 | 0.1015 | 0.0038 | 0.1053 | 0.0728 | 721.75 | 574.66 | 7463.59 |
MECH_FLR_1 | 0.0253 | 0.0000 | 0.0253 | 0.0090 | 0.0343 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0639 | 0.0000 | 0.0639 | 0.0052 | 0.0690 | 0.0578 | 5210.95 | 64.98 | 3484.07 |
LAUNDRY_FLR_1 | 1.3181 | 0.0000 | 1.3181 | 0.0123 | 1.3304 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7476 | 0.0000 | 0.7476 | 0.0217 | 0.7694 | 0.4612 | 259.33 | 289.83 | 8210.83 |
LOBBY_FLR_1 | 2.1017 | 0.0000 | 2.1017 | 0.0621 | 2.1639 | 1.8940 | 5107.27 | 120.84 | 3531.90 |
ROOM_1_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0057 | 0.0525 | 0.0617 | 2433.33 | 5505.17 | 821.50 |
ROOM_2_FLR_3 | 0.0446 | 0.0023 | 0.0468 | 0.0057 | 0.0525 | 0.0617 | 2433.33 | 5508.71 | 817.95 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0022 | 0.6069 | 0.0016 | 0.6085 | 0.8373 | 2433.33 | 5550.23 | 776.43 |
ROOM_5_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0057 | 0.0525 | 0.0617 | 2433.33 | 5505.17 | 821.50 |
ROOM_6_FLR_3 | 0.0446 | 0.0022 | 0.0468 | 0.0057 | 0.0525 | 0.0617 | 2433.33 | 5505.17 | 821.50 |
CORRIDOR_FLR_3 | 0.5245 | 0.0000 | 0.5245 | 0.0069 | 0.5314 | 0.4748 | 5215.09 | 63.99 | 3480.92 |
ROOM_1_FLR_6 | 0.0111 | 0.0027 | 0.0138 | 0.0057 | 0.0195 | 0.0154 | 2190.83 | 5506.06 | 1063.12 |
ROOM_2_FLR_6 | 0.0111 | 0.0026 | 0.0138 | 0.0057 | 0.0195 | 0.0154 | 2193.42 | 5514.08 | 1052.50 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0027 | 0.0743 | 0.0029 | 0.0772 | 0.0992 | 2433.33 | 5502.50 | 824.17 |
BANQUET_FLR_6 | 1.3161 | 0.0000 | 1.3161 | 0.0139 | 1.3301 | 1.1878 | 5195.37 | 80.41 | 3484.22 |
DINING_FLR_6 | 1.3202 | 0.0000 | 1.3202 | 0.0139 | 1.3341 | 1.1878 | 5095.12 | 105.36 | 3559.52 |
KITCHEN_FLR_6 | 1.3624 | 0.0000 | 1.3624 | 0.0125 | 1.3749 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.1658 | 0.0000 | 0.1658 | 0.0122 | 0.1780 | 0.1256 | 2655.03 | 87.28 | 6017.69 |
Total Facility | 59.0065 | 0.2328 | 59.2393 | 0.4543 | 59.6936 | 73.7328 | 8760.00 | 6039.11 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.43E+09 | 0.00 | 0.43E+09 | 0.21E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 38758673.79 | 604953.57 | 39363627.36 | 64690340.46 | 8759.67 | 0.33 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 13.6057 | 0.0000 | 13.6057 | 6.7627 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2290 | 0.0192 | 1.2482 | 2.0513 | 8759.67 | 0.33 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 111.17 | 5050.81 | 0.00 | 0.00 | 0.00 | 3598.02 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 12.4792 | 15.3825 | 0.0000 | 0.0000 | 0.0000 | 11.1505 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6091 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1344 |
Defaulted Fields | 1183 |
Fields with Defaults | 4016 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5024.90 | 60619.48 | 31-JAN-04:00 | 351653.62 | 18-AUG-19:20 |
Electricity:Building | 2129.27 | 28377.88 | 02-JAN-02:10 | 125573.39 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 241.08 | 2918.13 | 02-JAN-02:10 | 17644.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2122.17 | 28236.73 | 02-JAN-02:10 | 125332.06 | 02-JAN-20:10 |
InteriorLights:Electricity | 473.72 | 4343.06 | 02-JAN-02:10 | 39200.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 97.97 | 890.23 | 02-JAN-02:10 | 8012.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 473.72 | 4343.06 | 02-JAN-02:10 | 39200.55 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 473.72 | 4343.06 | 02-JAN-02:10 | 39200.55 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 97.97 | 890.23 | 02-JAN-02:10 | 8012.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 473.72 | 4343.06 | 02-JAN-02:10 | 39200.55 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 14.62 | 184.63 | 02-JAN-02:10 | 1048.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 4.43 | 40.29 | 02-JAN-02:10 | 362.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 4.43 | 40.29 | 02-JAN-02:10 | 362.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 16.93 | 213.80 | 02-JAN-02:10 | 1213.81 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 5.13 | 46.65 | 02-JAN-02:10 | 419.88 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 5.13 | 46.65 | 02-JAN-02:10 | 419.88 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 21.66 | 260.20 | 02-JAN-02:10 | 1590.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 9.19 | 83.47 | 02-JAN-02:10 | 751.24 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 9.19 | 83.47 | 02-JAN-02:10 | 751.24 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.70 | 70.12 | 02-JAN-02:10 | 414.36 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.11 | 19.14 | 02-JAN-02:10 | 172.20 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.11 | 19.14 | 02-JAN-02:10 | 172.20 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.85 | 998.31 | 02-JAN-02:10 | 4893.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.92 | 35.61 | 02-JAN-02:10 | 320.50 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.92 | 35.61 | 02-JAN-02:10 | 320.50 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 21.38 | 298.62 | 02-JAN-02:10 | 1823.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 7.04 | 41.98 | 01-JAN-13:10 | 858.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 7.04 | 41.98 | 01-JAN-13:10 | 858.63 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 232.42 | 2914.04 | 02-JAN-02:10 | 17252.86 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 83.42 | 802.63 | 02-JAN-02:10 | 7223.65 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 83.42 | 802.63 | 02-JAN-02:10 | 7223.65 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 57.85 | 525.62 | 02-JAN-02:10 | 4730.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 57.85 | 525.62 | 02-JAN-02:10 | 4730.55 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 57.85 | 525.62 | 02-JAN-02:10 | 4730.55 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 191.35 | 2416.84 | 02-JAN-02:10 | 8255.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 15.49 | 167.54 | 02-JAN-02:10 | 1507.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 15.49 | 167.54 | 02-JAN-02:10 | 1507.83 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 191.35 | 2416.84 | 02-JAN-02:10 | 8255.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 15.49 | 167.54 | 02-JAN-02:10 | 1507.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 15.49 | 167.54 | 02-JAN-02:10 | 1507.83 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 440.79 | 5911.62 | 02-JAN-02:10 | 18536.47 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 9.68 | 87.99 | 02-JAN-02:10 | 791.95 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 9.68 | 87.99 | 02-JAN-02:10 | 791.95 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.31 | 139.07 | 02-JAN-02:10 | 1251.64 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.31 | 139.07 | 02-JAN-02:10 | 1251.64 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.31 | 139.07 | 02-JAN-02:10 | 1251.64 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.20 | 732.86 | 13-FEB-23:30 | 2790.41 | 23-APR-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1642.88 | 2311.19 | 31-JAN-02:40 | 176777.57 | 08-JUL-15:30 |
LowTempRefrigeration:Refrigeration:Electricity | 15.86 | 0.00 | 01-JAN-11:10 | 1317.79 | 02-JUN-10:40 |
MedTempRefrigeration:Refrigeration:Electricity | 21.25 | 636.00 | 14-FEB-04:20 | 716.60 | 28-OCT-13:10 |
Fans:Electricity | 600.73 | 12868.00 | 13-NOV-03:30 | 36246.82 | 18-AUG-21:40 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityProduced:Facility | 202.62 | -0.00 | 01-FEB-08:10 | 33884.38 | 06-APR-12:40 |
ElectricityProduced:Plant | 202.62 | -0.00 | 01-FEB-08:10 | 33884.38 | 06-APR-12:40 |
Photovoltaic:ElectricityProduced | 211.65 | 0.00 | 01-JAN-00:10 | 35288.92 | 06-APR-12:40 |
PowerConversion:ElectricityProduced | -9.03 | -1404.54 | 06-APR-12:40 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 733.14 | 13682.90 | 27-NOV-05:00 | 45331.15 | 18-AUG-21:40 |
ExteriorEquipment:Electricity | 390.57 | 5778.01 | 02-JAN-02:20 | 23859.27 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.48 | 378.94 | 02-JAN-02:20 | 1270.98 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 4822.28 | 51968.23 | 06-APR-11:20 | 351653.62 | 18-AUG-19:20 |
ElectricityPurchased:Plant | 4822.28 | 51968.23 | 06-APR-11:20 | 351653.62 | 18-AUG-19:20 |
Cogeneration:ElectricityPurchased | 4822.28 | 51968.23 | 06-APR-11:20 | 351653.62 | 18-AUG-19:20 |
General:Cogeneration:ElectricityPurchased | 4822.28 | 51968.23 | 06-APR-11:20 | 351653.62 | 18-AUG-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4822.28 | 51968.23 | 06-APR-11:20 | 351653.62 | 18-AUG-19:20 |
ElectricityNet:Plant | 4822.28 | 51968.23 | 06-APR-11:20 | 351653.62 | 18-AUG-19:20 |
Cogeneration:ElectricityNet | 4822.28 | 51968.23 | 06-APR-11:20 | 351653.62 | 18-AUG-19:20 |
General:Cogeneration:ElectricityNet | 4822.28 | 51968.23 | 06-APR-11:20 | 351653.62 | 18-AUG-19:20 |
General:Fans:Electricity | 600.73 | 12868.00 | 13-NOV-03:30 | 36246.82 | 18-AUG-21:40 |
ExteriorLights:Electricity | 150.52 | 0.00 | 01-JAN-07:50 | 9571.94 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 150.52 | 0.00 | 01-JAN-07:50 | 9571.94 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 366.65 | 5383.28 | 01-JAN-00:10 | 22430.31 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.45 | 15.80 | 01-JAN-00:10 | 157.97 | 01-JAN-07:10 |
HeatRecovery:Electricity | 110.93 | 0.00 | 01-JAN-08:00 | 8265.52 | 31-MAY-09:00 |
General:HeatRecovery:Electricity | 110.93 | 0.00 | 01-JAN-08:00 | 8265.52 | 31-MAY-09:00 |
WaterSystems:Electricity | 90.74 | 1086.56 | 04-MAY-01:40 | 4738.77 | 01-JUN-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 04-MAY-01:40 | 4738.77 | 01-JUN-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1425.14 | 0.00 | 01-JAN-00:20 | 169280.48 | 08-JUL-15:30 |
General:Cooling:Electricity | 1425.14 | 0.00 | 01-JAN-00:20 | 169280.48 | 08-JUL-15:30 |
Pumps:Electricity | 89.89 | 47.91 | 31-MAR-14:10 | 4096.88 | 17-DEC-10:50 |
General:Pumps:Electricity | 89.89 | 47.91 | 31-MAR-14:10 | 4096.88 | 17-DEC-10:50 |
WIRED_LTG_ELECTRICITY | 16.67 | 0.00 | 01-JAN-00:10 | 1379.86 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4599.08 | 26805.16 | 20-JAN-02:20 | 427778.25 | 09-JAN-17:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2810.24 | 13443.27 | 30-JUN-09:00 | 338166.04 | 09-JAN-17:40 |
WaterSystems:NaturalGas | 2458.52 | 13443.27 | 20-JUN-09:00 | 228947.46 | 24-JAN-21:20 |
Water Heater:WaterSystems:NaturalGas | 2458.52 | 13443.27 | 20-JUN-09:00 | 228947.46 | 24-JAN-21:20 |
Heating:NaturalGas | 351.72 | 0.00 | 01-JAN-08:10 | 162517.92 | 09-JAN-16:20 |
Boiler:Heating:NaturalGas | 351.72 | 0.00 | 01-JAN-08:10 | 162517.92 | 09-JAN-16:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4746.87 | 0.00 | 01-JAN-00:20 | 594045.31 | 23-AUG-22:00 |
PlantLoopCoolingDemand:HVAC | 4746.87 | 0.00 | 01-JAN-00:20 | 594045.31 | 23-AUG-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 4746.87 | 0.00 | 01-JAN-00:20 | 594045.31 | 23-AUG-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 23178.14 | 123324.10 | 23-MAR-13:20 | 2308576.45 | 06-JUL-18:20 |
EnergyTransfer:Building | 5011.68 | 75838.55 | 08-JAN-15:00 | 318465.35 | 02-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 704.56 | 8591.18 | 12-FEB-04:00 | 34722.24 | 08-JUL-10:40 |
Refrigeration:EnergyTransfer | 185.86 | 4017.19 | 13-FEB-23:10 | 10367.19 | 04-APR-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.93 | 2008.60 | 13-FEB-23:10 | 5183.60 | 04-APR-06:30 |
General:Refrigeration:EnergyTransfer | 92.93 | 2008.60 | 13-FEB-23:10 | 5183.60 | 04-APR-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.93 | 2008.60 | 13-FEB-23:10 | 5183.60 | 04-APR-06:30 |
EnergyTransfer:Plant | 12135.23 | 12869.63 | 16-FEB-03:00 | 1367893.68 | 23-AUG-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.67 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.26 | 1996.28 | 14-FEB-04:20 | 2558.85 | 28-OCT-13:10 |
EnergyTransfer:Zone:BASEMENT | 351.79 | 3935.18 | 09-APR-15:00 | 18770.21 | 08-NOV-22:00 |
Heating:EnergyTransfer | 53.72 | 0.00 | 01-JAN-08:00 | 68358.79 | 07-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 53.72 | 0.00 | 01-JAN-08:00 | 68358.79 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4865.02 | 65310.40 | 08-JAN-15:00 | 314857.11 | 02-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 351.79 | 3935.18 | 09-APR-15:00 | 18770.21 | 08-NOV-22:00 |
General:Cooling:EnergyTransfer | 4865.02 | 65310.40 | 08-JAN-15:00 | 314857.11 | 02-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 351.79 | 3935.18 | 09-APR-15:00 | 18770.21 | 08-NOV-22:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.73 | 0.05 | 22-NOV-03:40 | 2692.86 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.35 | 0.00 | 01-JAN-00:10 | 1133.07 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.35 | 0.00 | 01-JAN-00:10 | 1133.07 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.38 | 0.00 | 01-JAN-17:00 | 2692.86 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.38 | 0.00 | 01-JAN-17:00 | 2692.86 | 10-OCT-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.54 | 149.75 | 08-JAN-15:50 | 1902.52 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.54 | 149.75 | 08-JAN-15:50 | 1902.52 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.54 | 149.75 | 08-JAN-15:50 | 1902.52 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 12.32 | 0.03 | 14-FEB-13:00 | 1842.81 | 07-JUL-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 446.07 | 08-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 446.07 | 08-JAN-13:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 12.18 | 0.00 | 06-JAN-04:20 | 1842.81 | 07-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 12.18 | 0.00 | 06-JAN-04:20 | 1842.81 | 07-JUL-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 18.11 | 0.03 | 24-JAN-06:00 | 1029.52 | 08-JUL-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.33 | 0.00 | 01-JAN-00:10 | 431.17 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.33 | 0.00 | 01-JAN-00:10 | 431.17 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 17.78 | 0.00 | 03-JAN-09:50 | 1029.52 | 08-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 17.78 | 0.00 | 03-JAN-09:50 | 1029.52 | 08-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.39 | 7602.61 | 13-FEB-05:00 | 39384.68 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.39 | 7602.61 | 13-FEB-05:00 | 39384.68 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.39 | 7602.61 | 13-FEB-05:00 | 39384.68 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 248.68 | 384.74 | 09-JAN-09:20 | 11306.69 | 08-JUL-17:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 248.68 | 384.74 | 09-JAN-09:20 | 11306.69 | 08-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 248.68 | 384.74 | 09-JAN-09:20 | 11306.69 | 08-JUL-17:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 797.61 | 7601.02 | 08-JAN-16:00 | 38012.95 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 797.61 | 7601.02 | 08-JAN-16:00 | 38012.95 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 797.61 | 7601.02 | 08-JAN-16:00 | 38012.95 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 55.58 | 0.00 | 01-JAN-08:00 | 9021.00 | 18-AUG-15:30 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 6.07 | 0.00 | 01-JAN-08:00 | 4900.81 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 6.07 | 0.00 | 01-JAN-08:00 | 4900.81 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 49.52 | 0.00 | 01-JAN-00:10 | 9021.00 | 18-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 49.52 | 0.00 | 01-JAN-00:10 | 9021.00 | 18-AUG-15:30 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 48.46 | 0.00 | 01-JAN-08:00 | 9101.41 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 8.45 | 0.00 | 01-JAN-08:00 | 5196.77 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 8.45 | 0.00 | 01-JAN-08:00 | 5196.77 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 40.02 | 0.00 | 01-JAN-00:10 | 9101.41 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 40.02 | 0.00 | 01-JAN-00:10 | 9101.41 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 265.94 | 0.00 | 01-JAN-00:10 | 32280.55 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 265.94 | 0.00 | 01-JAN-00:10 | 32280.55 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 265.94 | 0.00 | 01-JAN-00:10 | 32280.55 | 10-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 403.32 | 0.00 | 01-JAN-08:00 | 63371.81 | 27-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 11.42 | 0.00 | 01-JAN-00:10 | 32442.00 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 11.42 | 0.00 | 01-JAN-00:10 | 32442.00 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 391.90 | 0.00 | 01-JAN-08:00 | 63371.81 | 27-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 391.90 | 0.00 | 01-JAN-08:00 | 63371.81 | 27-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 55.71 | 0.00 | 01-JAN-08:00 | 8225.05 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 6.06 | 0.00 | 01-JAN-08:00 | 5106.70 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 6.06 | 0.00 | 01-JAN-08:00 | 5106.70 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 49.65 | 0.00 | 01-JAN-00:10 | 8225.05 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 49.65 | 0.00 | 01-JAN-00:10 | 8225.05 | 07-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 48.73 | 0.00 | 01-JAN-08:00 | 8721.06 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 8.43 | 0.00 | 01-JAN-08:00 | 5269.62 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 8.43 | 0.00 | 01-JAN-08:00 | 5269.62 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 40.30 | 0.00 | 01-JAN-00:10 | 8721.06 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 40.30 | 0.00 | 01-JAN-00:10 | 8721.06 | 07-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 171.82 | 6.69 | 17-JAN-12:00 | 8819.29 | 19-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.24 | 0.00 | 01-JAN-00:10 | 2226.88 | 09-JAN-09:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.24 | 0.00 | 01-JAN-00:10 | 2226.88 | 09-JAN-09:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 171.58 | 0.00 | 03-JAN-09:10 | 8819.29 | 19-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 171.58 | 0.00 | 03-JAN-09:10 | 8819.29 | 19-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 15.06 | 0.00 | 01-JAN-08:00 | 2475.91 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.79 | 0.00 | 01-JAN-08:00 | 1664.87 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.79 | 0.00 | 01-JAN-08:00 | 1664.87 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.27 | 0.00 | 01-JAN-00:10 | 2475.91 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.27 | 0.00 | 01-JAN-00:10 | 2475.91 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 13.78 | 0.00 | 01-JAN-08:00 | 2498.64 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.64 | 0.00 | 01-JAN-08:00 | 1779.56 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.64 | 0.00 | 01-JAN-08:00 | 1779.56 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.13 | 0.00 | 01-JAN-00:10 | 2498.64 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.13 | 0.00 | 01-JAN-00:10 | 2498.64 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 82.15 | 0.00 | 01-JAN-08:00 | 12499.50 | 10-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.94 | 0.00 | 01-JAN-08:00 | 7383.67 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.94 | 0.00 | 01-JAN-08:00 | 7383.67 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.20 | 0.00 | 01-JAN-00:10 | 12499.50 | 10-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.20 | 0.00 | 01-JAN-00:10 | 12499.50 | 10-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 484.36 | 7987.03 | 08-JAN-16:00 | 21377.06 | 07-JUL-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 484.36 | 7987.03 | 08-JAN-16:00 | 21377.06 | 07-JUL-22:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 484.36 | 7987.03 | 08-JAN-16:00 | 21377.06 | 07-JUL-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 506.92 | 9569.09 | 08-JAN-16:00 | 22729.76 | 07-JUL-22:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 506.92 | 9569.09 | 08-JAN-16:00 | 22729.76 | 07-JUL-22:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 506.92 | 9569.09 | 08-JAN-16:00 | 22729.76 | 07-JUL-22:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 611.63 | 6297.76 | 12-FEB-04:00 | 29640.21 | 08-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 611.63 | 6297.76 | 12-FEB-04:00 | 29640.21 | 08-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 67.12 | 0.04 | 11-FEB-16:30 | 5886.25 | 08-JUL-16:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.85 | 0.00 | 01-JAN-00:10 | 2421.61 | 12-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.85 | 0.00 | 01-JAN-00:10 | 2421.61 | 12-FEB-06:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 66.28 | 0.00 | 02-JAN-09:10 | 5886.25 | 08-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 66.28 | 0.00 | 02-JAN-09:10 | 5886.25 | 08-JUL-16:10 |
PlantLoopHeatingDemand:Facility | 982.76 | 7488.14 | 04-AUG-02:00 | 147799.85 | 03-JAN-09:10 |
PlantLoopHeatingDemand:Plant | 671.59 | 7488.14 | 04-AUG-02:00 | 51953.94 | 02-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 671.59 | 7488.14 | 04-AUG-02:00 | 51953.94 | 02-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 671.59 | 7488.14 | 04-AUG-02:00 | 51953.94 | 02-FEB-07:40 |
EnergyTransfer:HVAC | 6031.23 | 0.00 | 29-OCT-10:00 | 700512.56 | 06-JUL-18:20 |
HeatingCoils:EnergyTransfer | 311.17 | 0.00 | 19-JAN-21:10 | 130108.95 | 09-JAN-16:20 |
PlantLoopHeatingDemand:HVAC | 311.17 | 0.00 | 19-JAN-21:10 | 130108.95 | 09-JAN-16:20 |
HeatingCoils:PlantLoopHeatingDemand | 311.17 | 0.00 | 19-JAN-21:10 | 130108.95 | 09-JAN-16:20 |
CoolingCoils:EnergyTransfer | 4746.87 | 0.00 | 01-JAN-00:20 | 594045.31 | 23-AUG-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 403.10 | 0.00 | 01-JAN-08:00 | 311093.31 | 12-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 570.10 | 0.00 | 01-JAN-00:10 | 156071.27 | 19-AUG-16:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 671.59 | 7488.14 | 04-AUG-02:00 | 51953.94 | 02-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 671.59 | 7488.14 | 04-AUG-02:00 | 51953.94 | 02-FEB-07:40 |
Boilers:EnergyTransfer | 307.26 | 0.00 | 01-JAN-08:10 | 143319.32 | 09-JAN-16:20 |
Chillers:EnergyTransfer | 4819.15 | 0.00 | 01-JAN-00:20 | 599460.29 | 23-AUG-22:00 |
HeatRejection:EnergyTransfer | 6244.29 | 0.00 | 01-JAN-00:20 | 742728.05 | 23-AUG-22:00 |
General:HeatRejection:EnergyTransfer | 6244.29 | 0.00 | 01-JAN-00:20 | 742728.05 | 23-AUG-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -351.787 | 0.000 | 0.000 | 145.256 | 97.975 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -34.549 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.352 | -33.379 | 0.000 | 0.000 | 14.767 | 4.434 | 10.186 | 15.836 | 0.000 | 0.324 | 0.000 | 0.000 | -5.094 | 0.000 | -2.649 | -4.775 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -36.537 | 0.000 | 0.000 | 17.176 | 5.134 | 11.795 | 0.000 | 0.000 | 0.157 | 3.292 | 0.000 | 0.000 | 0.000 | -1.017 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.144 | -12.177 | 0.000 | 0.000 | 3.441 | 9.186 | 12.471 | 0.000 | 0.000 | 0.287 | 0.000 | 0.000 | 0.000 | 0.000 | -2.664 | -10.689 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.330 | -17.781 | 0.000 | 0.000 | 2.926 | 2.106 | 3.598 | 0.000 | 0.000 | 0.243 | 9.862 | 0.000 | 0.000 | 0.000 | -1.283 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -589.393 | 0.000 | 0.000 | 10.551 | 3.919 | 658.131 | 0.000 | 0.000 | 0.391 | 0.000 | 0.000 | 0.000 | 0.000 | -3.896 | -79.703 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -248.679 | 0.000 | 0.000 | 199.212 | 7.037 | 14.341 | 45.782 | 0.000 | 1.073 | 0.388 | 0.000 | -13.500 | 0.000 | -5.655 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -797.616 | 0.000 | 0.000 | 566.073 | 83.423 | 148.998 | 59.299 | 0.000 | 2.595 | 0.000 | 0.000 | -19.292 | 0.000 | -17.352 | -26.129 |
ROOM_1_FLR_3 | 8.507 | -40.490 | 0.000 | -11.465 | 0.000 | 0.000 | 9.679 | 4.922 | 10.478 | 33.064 | 0.000 | 1.302 | 1.084 | 0.000 | -10.751 | 0.000 | -6.330 | -0.001 |
ROOM_2_FLR_3 | 11.228 | -30.899 | 0.000 | -11.897 | 0.000 | 0.000 | 9.583 | 4.922 | 10.477 | 25.256 | 0.000 | 1.143 | 0.000 | 0.000 | -11.286 | 0.000 | -6.698 | -1.828 |
ROOM_3_MULT19_FLR_3 | 0.000 | -250.031 | 0.000 | -15.906 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 174.555 | 0.000 | 1.781 | 0.003 | 0.000 | -84.950 | 0.000 | -47.469 | -31.755 |
ROOM_4_MULT19_FLR_3 | 28.717 | -249.009 | 0.000 | -160.161 | 0.000 | 0.000 | 182.293 | 58.793 | 195.050 | 75.355 | 0.000 | 6.707 | 0.000 | 0.000 | -61.977 | 0.000 | -47.307 | -28.460 |
ROOM_5_FLR_3 | 8.490 | -40.600 | 0.000 | -11.476 | 0.000 | 0.000 | 9.672 | 4.922 | 10.478 | 33.148 | 0.000 | 1.300 | 0.858 | 0.000 | -10.438 | 0.000 | -6.355 | -0.001 |
ROOM_6_FLR_3 | 11.210 | -31.181 | 0.000 | -11.896 | 0.000 | 0.000 | 9.586 | 4.922 | 10.477 | 25.056 | 0.000 | 1.141 | 0.000 | 0.000 | -10.684 | 0.000 | -6.652 | -1.979 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.240 | -171.581 | 0.000 | 0.000 | 117.568 | 57.846 | 0.000 | 30.051 | 0.000 | 1.131 | 0.000 | 0.000 | -13.958 | 0.000 | -7.122 | -14.174 |
ROOM_1_FLR_6 | 3.542 | -10.155 | 0.000 | -2.863 | 0.000 | 0.000 | 2.424 | 1.231 | 2.620 | 8.239 | 0.000 | 0.326 | 0.000 | 0.000 | -2.632 | 0.000 | -1.607 | -1.124 |
ROOM_2_FLR_6 | 4.451 | -7.970 | 0.000 | -2.967 | 0.000 | 0.000 | 2.400 | 1.230 | 2.619 | 6.296 | 0.000 | 0.284 | 0.000 | 0.000 | -2.764 | 0.000 | -1.701 | -1.879 |
ROOM_3_MULT9_FLR_6 | 7.763 | -61.517 | 0.000 | -18.501 | 0.000 | 0.000 | 21.721 | 6.962 | 23.098 | 42.050 | 0.000 | 1.663 | 0.000 | 0.000 | -12.198 | 0.000 | -8.508 | -2.533 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -484.365 | 0.000 | 0.000 | 337.943 | 15.494 | 175.857 | 8.760 | 0.000 | 0.609 | 0.000 | 0.000 | -7.374 | 0.000 | -3.870 | -43.055 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -506.922 | 0.000 | 0.000 | 332.510 | 15.494 | 175.857 | 8.516 | 0.000 | 0.574 | 0.000 | 0.000 | -7.744 | 0.000 | -3.982 | -14.301 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -611.618 | 0.000 | 0.000 | 27.943 | 9.684 | 540.650 | 21.276 | 0.000 | 0.387 | 19.895 | 0.000 | -4.214 | 0.000 | -4.004 | -0.002 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.849 | -66.276 | 0.000 | 0.000 | 29.694 | 15.305 | 0.000 | 13.986 | 0.000 | 0.381 | 16.167 | 0.000 | -6.674 | 0.000 | -3.433 | -0.001 |
Total Facility | 83.907 | -721.852 | 1.916 | -4175.244 | 0.000 | 0.000 | 2052.418 | 473.719 | 2355.282 | 626.525 | 0.000 | 23.798 | 51.551 | 0.000 | -285.529 | 0.000 | -189.554 | -296.939 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-NOV-22:00 | 0.00 | 0.00 | 0.00 | -18771.08 | 0.00 | 0.00 | 5924.42 | 7121.99 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3400.89 |
RETAIL_1_FLR_1 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 | -2693.11 | 0.00 | 0.00 | 150.60 | 100.72 | 252.59 | 3339.17 | 0.00 | 54.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1204.03 |
RETAIL_2_FLR_1 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | -1902.57 | 0.00 | 0.00 | 697.61 | 373.23 | 752.15 | 0.00 | 0.00 | 30.30 | 49.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 07-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1842.85 | 0.00 | 0.00 | 147.53 | 667.77 | 795.27 | 0.00 | 0.00 | 66.67 | 165.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 08-JUL-10:35 | 0.00 | 0.00 | 0.00 | -1032.53 | 0.00 | 0.00 | 45.72 | 47.83 | 89.22 | 0.00 | 0.00 | 60.05 | 789.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 07-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39383.80 | 0.00 | 0.00 | 408.79 | 320.50 | 44299.38 | 0.00 | 0.00 | 97.76 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5742.63 |
CAFE_FLR_1 | 12-APR-15:14 | 0.00 | 0.00 | 0.00 | -12260.08 | 0.00 | 0.00 | 5372.75 | 52.47 | 355.63 | 4138.64 | 0.00 | 139.73 | 2200.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -38019.11 | 0.00 | 0.00 | 26440.14 | 4815.77 | 7389.94 | 468.32 | 0.00 | 476.60 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1571.66 |
ROOM_1_FLR_3 | 09-APR-15:11 | 0.00 | -11081.82 | 0.00 | -713.63 | 0.00 | 0.00 | 130.71 | 125.03 | 221.25 | 5964.24 | 0.00 | 0.00 | 5432.18 | 0.00 | -0.00 | 0.00 | -77.95 | 0.00 |
ROOM_2_FLR_3 | 09-MAY-20:41 | 0.00 | -11531.12 | 0.00 | -573.92 | 0.00 | 0.00 | 368.34 | 337.15 | 726.90 | 0.00 | 0.00 | 0.00 | 11785.19 | 0.00 | -848.44 | 0.00 | -264.10 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-13:30 | 0.00 | -32278.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 39294.29 | 0.00 | 293.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10928.52 |
ROOM_4_MULT19_FLR_3 | 09-MAY-20:41 | 0.00 | -75668.19 | 0.00 | -7765.42 | 0.00 | 0.00 | 7159.84 | 4027.42 | 13532.74 | 0.00 | 0.00 | 0.00 | 64292.69 | 0.00 | -4179.90 | 0.00 | -1399.19 | 0.00 |
ROOM_5_FLR_3 | 13-MAR-15:11 | 0.00 | -10069.62 | 0.00 | -712.86 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 2277.39 | 0.00 | 37.57 | 7925.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 04-JUN-08:51 | 0.00 | -9943.75 | 0.00 | -930.44 | 0.00 | 0.00 | 107.49 | 212.14 | 653.15 | 5682.25 | 0.00 | 0.00 | 4248.43 | 0.00 | -0.00 | 0.00 | -29.28 | 0.00 |
CORRIDOR_FLR_3 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | -8832.98 | 0.00 | 0.00 | 1823.77 | 1314.04 | 0.00 | 3749.48 | 0.00 | 268.35 | 1677.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 09-APR-15:11 | 0.00 | -2926.73 | 0.00 | -178.70 | 0.00 | 0.00 | 32.68 | 31.26 | 55.31 | 1481.17 | 0.00 | 0.00 | 1528.16 | 0.00 | -0.00 | 0.00 | -23.15 | 0.00 |
ROOM_2_FLR_6 | 09-MAY-20:41 | 0.00 | -3088.74 | 0.00 | -148.88 | 0.00 | 0.00 | 89.90 | 84.29 | 181.72 | 0.00 | 0.00 | 0.00 | 3167.72 | 0.00 | -217.57 | 0.00 | -68.43 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13-MAR-15:11 | 0.00 | -13748.32 | 0.00 | -1167.74 | 0.00 | 0.00 | 529.39 | 150.05 | 441.28 | 5559.67 | 0.00 | 35.78 | 8199.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 12-APR-15:14 | 0.00 | 0.00 | 0.00 | -21424.62 | 0.00 | 0.00 | 9454.03 | 251.30 | 6747.90 | 1130.94 | 0.00 | 88.76 | 3751.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 07-JUL-22:00 | 0.00 | 0.00 | 0.00 | -22729.67 | 0.00 | 0.00 | 15644.38 | 1005.22 | 6747.90 | 193.78 | 0.00 | 83.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -945.27 |
KITCHEN_FLR_6 | 15-APR-10:36 | 0.00 | 0.00 | 0.00 | -31286.64 | 0.00 | 0.00 | 464.21 | 219.99 | 23951.61 | 2864.00 | 0.00 | 1.97 | 3784.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 08-JUL-16:10 | 0.00 | 0.00 | 0.00 | -5885.63 | 0.00 | 0.00 | 771.16 | 347.68 | 0.00 | 1147.41 | 0.00 | 165.03 | 3454.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-18:02 | 0.00 | -142579.40 | 0.00 | -197257.77 | 0.00 | 0.00 | 78488.64 | 32461.89 | 120174.13 | 25451.07 | 0.00 | 5303.54 | 77957.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 12-FEB-06:00 | 0.00 | 0.00 | 1133.09 | 0.00 | 0.00 | 0.00 | 626.56 | 80.58 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -993.37 | 0.00 | -435.92 | -627.45 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 08-JAN-13:40 | 0.00 | 0.00 | 446.07 | 0.00 | 0.00 | 0.00 | 43.84 | 166.94 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -245.91 | -676.03 |
STORAGE_FLR_1 | 12-FEB-09:03 | 0.00 | 0.00 | 432.06 | 0.00 | 0.00 | 0.00 | 84.30 | 57.40 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -214.96 | -460.77 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 07-JAN-16:11 | 8970.66 | 290.23 | 0.00 | -290.23 | 0.00 | 0.00 | 163.32 | 125.03 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -776.13 | 0.00 | -695.32 | -8008.81 |
ROOM_2_FLR_3 | 07-JAN-16:11 | 8957.15 | 289.19 | 0.00 | -289.19 | 0.00 | 0.00 | 163.33 | 125.01 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -878.14 | 0.00 | -694.86 | -7893.72 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 07-JAN-16:11 | 51481.55 | 4273.55 | 0.00 | -4273.55 | 0.00 | 0.00 | 3025.86 | 1493.31 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6309.18 | 0.00 | -3740.22 | -50069.97 |
ROOM_5_FLR_3 | 07-JAN-16:11 | 8711.68 | 287.88 | 0.00 | -287.88 | 0.00 | 0.00 | 163.33 | 125.03 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1013.10 | 0.00 | -694.37 | -7513.82 |
ROOM_6_FLR_3 | 07-JAN-16:11 | 8703.93 | 286.90 | 0.00 | -286.90 | 0.00 | 0.00 | 163.33 | 125.01 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1115.15 | 0.00 | -693.94 | -7404.41 |
CORRIDOR_FLR_3 | 09-JAN-09:10 | 0.00 | 0.00 | 2227.49 | 0.00 | 0.00 | 0.00 | 1385.76 | 2102.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1302.64 | 0.00 | -854.44 | -3558.63 |
ROOM_1_FLR_6 | 07-JAN-16:11 | 2662.90 | 73.12 | 0.00 | -73.12 | 0.00 | 0.00 | 40.83 | 31.26 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -189.86 | 0.00 | -174.53 | -2425.92 |
ROOM_2_FLR_6 | 07-JAN-16:11 | 2657.02 | 72.79 | 0.00 | -72.79 | 0.00 | 0.00 | 40.83 | 31.25 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -215.84 | 0.00 | -174.38 | -2394.19 |
ROOM_3_MULT9_FLR_6 | 07-JAN-16:11 | 12562.22 | 464.76 | 0.00 | -464.76 | 0.00 | 0.00 | 367.48 | 176.84 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -952.26 | 0.00 | -802.14 | -11839.87 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 12-FEB-06:20 | 0.00 | 0.00 | 2421.65 | 0.00 | 0.00 | 0.00 | 1283.35 | 417.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1284.71 | 0.00 | -546.97 | -2290.53 |
Total Facility | 07-JAN-16:11 | 29902.23 | 80843.29 | 4820.26 | -80843.29 | 0.00 | 0.00 | 36985.98 | 10745.47 | 74529.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22644.19 | 0.00 | -18007.99 | -116331.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.5945 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.4890 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.0203 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5305 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.003540 | 12.5400 | 0.000610 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.003540 | 142.3000 | 0.000914 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.000963 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1585 | 2.1585 | 1.2821 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2783 | 0.2783 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2142 | 0.2142 | 0.1375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2245 | 0.2245 | 0.0022 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1072 | 0.1072 | 0.0867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3758 | 3.3758 | 0.0338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3026 | 1.3026 | 1.0147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4875 | 4.4875 | 2.8406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1336 | 1.1336 | 0.7119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1572 | 2.1572 | 1.7818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2659 | 2.2659 | 1.7810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2314 | 2.2314 | 0.5512 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6580 | 0.6580 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.5945 | 20.4890 | 20.5945 | 10.5305 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2821 | 1.2821 | 1.2821 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1392 | 0.1392 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1375 | 0.1375 | 0.1375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1122 | 0.1122 | 0.0022 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0867 | 0.0867 | 0.0867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6879 | 1.6879 | 0.0338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0147 | 1.0147 | 1.0147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8406 | 2.8406 | 2.8406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7119 | 0.7119 | 0.7119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7818 | 1.7818 | 1.7818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7810 | 1.7810 | 1.7810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1157 | 1.1157 | 0.5512 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3290 | 0.3290 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.0203 | 10.5305 | 10.5305 | 10.5305 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 77.00 |
Number of hours not met | 77.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 351.72 | 162517.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1425.14 | 169280.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 473.72 | 39200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 150.52 | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.48 | 1270.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 366.65 | 22430.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.45 | 157.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 600.73 | 36246.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 89.89 | 4096.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 110.93 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.77 | 2458.52 | 228947.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.86 | 1317.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.25 | 716.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.65 | 5024.90 |
Natural Gas | 1788.84 | 4599.08 |
Additional | 0.00 | 0.00 |
Total | 3481.49 | 9623.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 211.65 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 41.75 |
Space Heating | 0.00 |
Space Cooling | 125.62 |
Fans (All) | 52.95 |
Service Water Heating | 8.00 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 442.91 |
Subtotal | 442.91 |
Natural Gas [MJ/m2] | |
Space Heating | 31.00 |
Service Water Heating | 216.70 |
Miscellaneous (All) | 405.37 |
Subtotal | 405.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.92 |
Space Heating | 3.65 |
Space Cooling | 14.81 |
Fans (All) | 6.24 |
Service Water Heating | 26.49 |
Receptacle Equipment | 35.72 |
Miscellaneous | 8.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_KITCHEN | 2142. | 8760. |
LTG_SCH_DINING | 1989. | 8760. |
LTG_SCH_BASEMENT | 2219. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1635. | 8760. |
LTG_SCH_MECHANIC | 2142. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2433. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6974.17 | 1785.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6974.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1785.83 | 0.00 | 0.00 | 0.00 |
Average | 8678.68 | 81.32 | 0.00 | 0.00 | 0.00 |
Sum | 190931.00 | 1789.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8542.00 | 218.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8509.00 | 251.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7779.33 | 980.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8551.83 | 208.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6303.17 | 2456.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8607.83 | 152.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8511.67 | 248.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8521.67 | 238.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7905.17 | 854.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7777.83 | 982.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8644.00 | 116.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8518.83 | 241.17 | 0.00 | 0.00 | 0.00 |
Min | 6303.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2456.83 | 0.00 | 0.00 | 0.00 |
Average | 8440.23 | 319.77 | 0.00 | 0.00 | 0.00 |
Sum | 185685.00 | 7035.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 48261.67 | 1917.33 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59152.33 | 3.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8958.83 | 18.17 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 678289.00 | 32128.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1756729.67 | 358699.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4115.83 | 38.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4120.50 | 33.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4115.67 | 38.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4109.00 | 45.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1056461.50 | 189253.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1031743.00 | 213972.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107482.00 | 787.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 101713.17 | 4232.83 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1756729.67 | 358699.33 | 0.00 | 0.00 | 0.00 |
Average | 252470.37 | 36416.67 | 0.00 | 0.00 | 0.00 |
Sum | 5554348.17 | 801166.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:54:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279509E+11 | 12480.23 | 31-JAN-21:00 | 17.20 | 12.43 | 0.712150E+10 | 4426.62 | 27-JAN-22:10 | 17.20 | 12.43 |
February | 0.235796E+11 | 12021.97 | 01-FEB-21:00 | 9.40 | 8.81 | 0.610825E+10 | 4346.21 | 01-FEB-22:10 | 8.72 | 8.24 |
March | 0.240993E+11 | 11745.27 | 30-MAR-18:10 | 26.02 | 17.62 | 0.643511E+10 | 4114.99 | 01-MAR-23:10 | 26.02 | 17.62 |
April | 0.202484E+11 | 12262.37 | 14-APR-18:01 | 24.45 | 15.36 | 0.603261E+10 | 3845.90 | 14-APR-22:10 | 17.12 | 12.34 |
May | 0.245557E+11 | 12876.55 | 15-MAY-18:04 | 27.70 | 16.54 | 0.638822E+10 | 3961.62 | 24-MAY-22:10 | 18.22 | 17.12 |
June | 0.279615E+11 | 13605.35 | 10-JUN-18:10 | 28.62 | 13.87 | 0.671398E+10 | 4314.82 | 16-JUN-22:10 | 23.22 | 20.55 |
July | 0.312486E+11 | 14472.14 | 20-JUL-18:10 | 32.12 | 22.73 | 0.728436E+10 | 4546.64 | 28-JUL-22:10 | 17.70 | 17.38 |
August | 0.335259E+11 | 15325.00 | 27-AUG-10:35 | 29.47 | 22.52 | 0.772736E+10 | 4778.00 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.346032E+11 | 17523.05 | 28-SEP-21:00 | 15.60 | 13.52 | 0.782915E+10 | 4837.09 | 14-SEP-22:10 | 15.60 | 13.52 |
October | 0.363971E+11 | 18656.88 | 12-OCT-21:00 | 12.20 | 9.05 | 0.815847E+10 | 4837.19 | 27-OCT-23:00 | 12.20 | 12.20 |
November | 0.350586E+11 | 18770.21 | 08-NOV-22:00 | 13.90 | 7.06 | 0.790066E+10 | 4837.15 | 30-NOV-00:10 | 8.98 | 7.61 |
December | 0.325571E+11 | 16660.36 | 01-DEC-22:00 | 3.90 | 0.00 | 0.790552E+10 | 4837.05 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.351786E+12 | 0.856052E+11 | ||||||||
Minimum of Months | 0.202484E+11 | 11745.27 | 3.90 | 0.00 | 0.603261E+10 | 3845.90 | 8.72 | 7.61 | ||
Maximum of Months | 0.363971E+11 | 18770.21 | 32.12 | 22.73 | 0.815847E+10 | 4837.19 | 26.02 | 20.55 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120526E+10 | 1534.60 | 29-JAN-13:00 | 13.90 | 6.14 | 0.633460E+09 | 421.44 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.151189E+10 | 1921.80 | 21-FEB-14:25 | 22.25 | 10.82 | 0.591120E+09 | 477.76 | 28-FEB-22:30 | 18.10 | 10.49 |
March | 0.254815E+10 | 1973.88 | 30-MAR-14:05 | 27.80 | 17.74 | 0.708945E+09 | 491.84 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.274349E+10 | 1971.88 | 15-APR-13:40 | 27.43 | 14.98 | 0.712949E+09 | 491.84 | 12-APR-22:10 | 27.43 | 14.98 |
May | 0.311012E+10 | 1831.57 | 19-MAY-18:20 | 29.03 | 18.68 | 0.776470E+09 | 491.84 | 23-MAY-22:10 | 20.50 | 16.92 |
June | 0.351903E+10 | 2079.47 | 13-JUN-18:03 | 31.93 | 21.91 | 0.793149E+09 | 491.84 | 02-JUN-22:10 | 31.93 | 21.91 |
July | 0.393517E+10 | 2375.18 | 07-JUL-18:20 | 33.70 | 23.11 | 0.822659E+09 | 491.84 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.424332E+10 | 2563.52 | 19-AUG-13:40 | 33.70 | 23.70 | 0.836024E+09 | 491.84 | 07-AUG-22:10 | 33.70 | 23.70 |
September | 0.347667E+10 | 2583.88 | 24-SEP-12:00 | 28.30 | 19.79 | 0.775056E+09 | 491.84 | 14-SEP-22:10 | 28.30 | 19.79 |
October | 0.297281E+10 | 2692.86 | 10-OCT-13:30 | 28.85 | 20.88 | 0.741542E+09 | 491.84 | 11-OCT-22:10 | 14.40 | 8.97 |
November | 0.239797E+10 | 2083.07 | 08-NOV-13:40 | 20.20 | 9.59 | 0.666289E+09 | 466.43 | 08-NOV-22:19 | 13.33 | 6.86 |
December | 0.171536E+10 | 1858.14 | 10-DEC-13:00 | 15.60 | 7.72 | 0.650139E+09 | 465.50 | 12-DEC-22:40 | 18.30 | 14.79 |
Annual Sum or Average | 0.333792E+11 | 0.870780E+10 | ||||||||
Minimum of Months | 0.120526E+10 | 1534.60 | 13.90 | 6.14 | 0.591120E+09 | 421.44 | 13.33 | 6.86 | ||
Maximum of Months | 0.424332E+10 | 2692.86 | 33.70 | 23.70 | 0.836024E+09 | 491.84 | 33.70 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223802E+10 | 1261.35 | 31-JAN-21:00 | 17.20 | 12.43 | 0.748392E+09 | 503.30 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.222786E+10 | 1396.75 | 28-FEB-21:00 | 20.60 | 11.78 | 0.697232E+09 | 539.60 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.293295E+10 | 1520.02 | 30-MAR-18:10 | 26.02 | 17.62 | 0.824572E+09 | 561.87 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.302641E+10 | 1636.46 | 12-APR-15:14 | 28.13 | 16.55 | 0.821579E+09 | 564.57 | 14-APR-22:10 | 17.12 | 12.34 |
May | 0.332841E+10 | 1610.53 | 15-MAY-18:04 | 27.70 | 16.54 | 0.876967E+09 | 569.55 | 18-MAY-22:10 | 21.78 | 16.44 |
June | 0.347014E+10 | 1675.24 | 27-JUN-21:00 | 27.20 | 20.99 | 0.887568E+09 | 569.55 | 26-JUN-22:10 | 27.20 | 20.99 |
July | 0.367908E+10 | 1857.45 | 07-JUL-21:00 | 30.60 | 22.80 | 0.922531E+09 | 569.55 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.374266E+10 | 1902.52 | 18-AUG-21:00 | 31.10 | 22.83 | 0.937265E+09 | 569.55 | 07-AUG-22:10 | 31.10 | 22.83 |
September | 0.337322E+10 | 1761.97 | 08-SEP-21:00 | 25.60 | 21.61 | 0.875438E+09 | 569.55 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.314579E+10 | 1551.09 | 11-OCT-18:10 | 21.73 | 13.14 | 0.854284E+09 | 569.55 | 10-OCT-22:10 | 21.73 | 13.14 |
November | 0.279663E+10 | 1383.66 | 06-NOV-21:00 | 12.20 | 6.19 | 0.788085E+09 | 536.81 | 06-NOV-23:10 | 10.40 | 5.30 |
December | 0.257588E+10 | 1355.36 | 12-DEC-21:00 | 18.30 | 14.62 | 0.773624E+09 | 530.79 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.365370E+11 | 0.100075E+11 | ||||||||
Minimum of Months | 0.222786E+10 | 1261.35 | 12.20 | 6.19 | 0.697232E+09 | 503.30 | 10.40 | 5.30 | ||
Maximum of Months | 0.374266E+10 | 1902.52 | 31.10 | 22.83 | 0.937265E+09 | 569.55 | 31.10 | 22.83 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35631232.76 | 24.65 | 20-JAN-21:00 | 12.80 | 8.84 | 0.165299E+09 | 119.98 | 20-JAN-22:10 | 11.52 | 8.16 |
February | 62640077.29 | 621.61 | 28-FEB-22:00 | 18.90 | 10.96 | 0.159919E+09 | 120.45 | 22-FEB-22:10 | 18.90 | 10.96 |
March | 0.236304E+09 | 1034.02 | 30-MAR-21:00 | 23.90 | 16.89 | 0.197591E+09 | 120.45 | 13-MAR-21:00 | 23.90 | 16.89 |
April | 0.571730E+09 | 1055.14 | 19-APR-20:00 | 20.60 | 16.68 | 0.196573E+09 | 120.45 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.123059E+10 | 1330.32 | 19-MAY-21:00 | 23.90 | 16.26 | 0.205419E+09 | 120.45 | 19-MAY-01:10 | 23.90 | 16.26 |
June | 0.212002E+10 | 1642.78 | 13-JUN-21:00 | 28.30 | 21.76 | 0.199177E+09 | 120.45 | 08-JUN-21:00 | 28.30 | 21.76 |
July | 0.251573E+10 | 1842.81 | 07-JUL-21:00 | 30.60 | 22.80 | 0.205007E+09 | 120.45 | 24-JUL-21:30 | 26.15 | 20.09 |
August | 0.266198E+10 | 1812.61 | 18-AUG-21:00 | 31.10 | 22.83 | 0.205873E+09 | 120.45 | 25-AUG-21:30 | 25.85 | 18.41 |
September | 0.176025E+10 | 1620.55 | 07-SEP-20:00 | 27.20 | 22.45 | 0.198648E+09 | 120.45 | 15-SEP-21:30 | 24.45 | 17.91 |
October | 0.701163E+09 | 1211.44 | 18-OCT-21:00 | 23.30 | 22.56 | 0.203420E+09 | 120.45 | 12-OCT-21:40 | 23.30 | 22.56 |
November | 0.210093E+09 | 779.29 | 03-NOV-21:00 | 18.30 | 16.18 | 0.190126E+09 | 120.45 | 20-NOV-00:10 | 20.82 | 18.45 |
December | 70544451.50 | 567.49 | 13-DEC-22:00 | 13.30 | 12.92 | 0.180671E+09 | 120.45 | 11-DEC-22:10 | 13.30 | 12.92 |
Annual Sum or Average | 0.121767E+11 | 0.230772E+10 | ||||||||
Minimum of Months | 35631232.76 | 24.65 | 12.80 | 8.84 | 0.159919E+09 | 119.98 | 11.52 | 8.16 | ||
Maximum of Months | 0.266198E+10 | 1842.81 | 31.10 | 22.83 | 0.205873E+09 | 120.45 | 28.30 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272370E+09 | 663.73 | 31-JAN-21:00 | 17.20 | 12.43 | 0.116730E+09 | 70.46 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.632222E+09 | 735.40 | 28-FEB-19:00 | 21.70 | 12.09 | 0.105911E+09 | 74.36 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.137771E+10 | 840.68 | 30-MAR-18:10 | 26.02 | 17.62 | 0.119904E+09 | 78.44 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.161517E+10 | 944.31 | 12-APR-15:14 | 28.13 | 16.55 | 0.119718E+09 | 78.76 | 18-APR-22:10 | 19.32 | 14.41 |
May | 0.187805E+10 | 926.48 | 20-MAY-10:35 | 27.23 | 18.94 | 0.129749E+09 | 81.62 | 19-MAY-22:10 | 27.23 | 18.94 |
June | 0.200602E+10 | 990.11 | 25-JUN-10:35 | 29.80 | 23.29 | 0.133656E+09 | 85.18 | 28-JUN-22:10 | 26.10 | 21.34 |
July | 0.214128E+10 | 1032.45 | 08-JUL-10:35 | 33.17 | 24.62 | 0.140309E+09 | 87.60 | 07-JUL-22:10 | 33.17 | 24.62 |
August | 0.216301E+10 | 1025.75 | 19-AUG-10:35 | 32.03 | 24.19 | 0.142085E+09 | 87.56 | 18-AUG-22:10 | 32.03 | 24.19 |
September | 0.192193E+10 | 979.51 | 09-SEP-10:35 | 30.03 | 23.84 | 0.130717E+09 | 84.99 | 07-SEP-22:10 | 30.03 | 23.84 |
October | 0.170225E+10 | 865.89 | 11-OCT-10:35 | 24.67 | 19.78 | 0.124953E+09 | 80.60 | 18-OCT-22:10 | 22.80 | 22.03 |
November | 0.133626E+10 | 779.64 | 05-NOV-10:35 | 18.33 | 17.01 | 0.115412E+09 | 75.72 | 03-NOV-22:10 | 18.33 | 17.01 |
December | 0.735169E+09 | 739.68 | 13-DEC-11:35 | 19.80 | 17.47 | 0.117117E+09 | 73.77 | 13-DEC-23:10 | 12.62 | 12.25 |
Annual Sum or Average | 0.177814E+11 | 0.149626E+10 | ||||||||
Minimum of Months | 0.272370E+09 | 663.73 | 17.20 | 12.09 | 0.105911E+09 | 70.46 | 12.22 | 9.67 | ||
Maximum of Months | 0.216301E+10 | 1032.45 | 33.17 | 24.62 | 0.142085E+09 | 87.60 | 33.17 | 24.62 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464298E+11 | 37348.67 | 31-JAN-21:00 | 17.20 | 12.43 | 0.649339E+09 | 381.58 | 11-JAN-22:10 | 17.20 | 12.43 |
February | 0.428705E+11 | 37857.47 | 28-FEB-21:00 | 20.60 | 11.78 | 0.587073E+09 | 381.57 | 08-FEB-22:40 | 20.60 | 11.78 |
March | 0.493048E+11 | 38286.63 | 30-MAR-20:00 | 24.40 | 16.98 | 0.652388E+09 | 381.57 | 28-MAR-21:19 | 24.40 | 16.98 |
April | 0.485634E+11 | 38433.35 | 17-APR-20:00 | 22.80 | 15.38 | 0.629503E+09 | 381.60 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.513390E+11 | 38791.39 | 19-MAY-20:00 | 25.60 | 17.28 | 0.650767E+09 | 381.60 | 08-MAY-21:19 | 25.60 | 17.28 |
June | 0.507842E+11 | 39160.82 | 13-JUN-20:00 | 29.40 | 21.98 | 0.630898E+09 | 381.71 | 13-JUN-21:10 | 28.12 | 21.63 |
July | 0.526567E+11 | 39384.68 | 07-JUL-20:00 | 31.10 | 23.22 | 0.649336E+09 | 381.73 | 11-JUL-21:10 | 26.52 | 20.92 |
August | 0.530001E+11 | 39296.25 | 18-AUG-20:00 | 31.70 | 22.32 | 0.652086E+09 | 381.71 | 01-AUG-21:10 | 31.70 | 22.32 |
September | 0.499092E+11 | 39033.05 | 07-SEP-20:00 | 27.20 | 22.45 | 0.629202E+09 | 381.72 | 05-SEP-21:10 | 27.20 | 22.45 |
October | 0.499261E+11 | 38404.22 | 10-OCT-20:00 | 22.20 | 19.19 | 0.649643E+09 | 381.64 | 10-OCT-21:10 | 21.10 | 18.77 |
November | 0.472367E+11 | 37771.63 | 03-NOV-20:00 | 18.90 | 16.38 | 0.628130E+09 | 381.59 | 29-NOV-23:49 | 9.37 | 7.47 |
December | 0.473672E+11 | 37606.05 | 12-DEC-21:00 | 18.30 | 14.62 | 0.649340E+09 | 381.59 | 15-DEC-22:10 | 5.50 | 3.86 |
Annual Sum or Average | 0.589388E+12 | 0.765770E+10 | ||||||||
Minimum of Months | 0.428705E+11 | 37348.67 | 17.20 | 11.78 | 0.587073E+09 | 381.57 | 5.50 | 3.86 | ||
Maximum of Months | 0.530001E+11 | 39384.68 | 31.70 | 23.22 | 0.652388E+09 | 381.73 | 31.70 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164173E+11 | 9824.69 | 29-JAN-11:35 | 12.43 | 5.39 | 0.854698E+10 | 5718.11 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.160704E+11 | 10219.68 | 26-FEB-11:35 | 22.07 | 11.70 | 0.791109E+10 | 5997.36 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.202976E+11 | 10901.99 | 30-MAR-15:11 | 27.80 | 17.21 | 0.916005E+10 | 6180.15 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.204047E+11 | 12260.34 | 12-APR-15:14 | 28.13 | 16.55 | 0.891724E+10 | 6110.86 | 17-APR-22:10 | 19.72 | 13.80 |
May | 0.221293E+11 | 10949.37 | 13-MAY-17:25 | 25.85 | 14.30 | 0.938180E+10 | 6157.72 | 19-MAY-21:00 | 22.20 | 15.66 |
June | 0.227493E+11 | 10812.21 | 12-JUN-18:10 | 31.60 | 21.71 | 0.937199E+10 | 6323.65 | 13-JUN-22:10 | 27.12 | 20.92 |
July | 0.240903E+11 | 11306.69 | 08-JUL-17:30 | 34.40 | 23.36 | 0.975830E+10 | 6423.32 | 07-JUL-22:10 | 34.40 | 23.36 |
August | 0.247504E+11 | 11343.05 | 02-AUG-18:10 | 32.80 | 23.11 | 0.998717E+10 | 6460.34 | 18-AUG-22:10 | 29.32 | 23.10 |
September | 0.225171E+11 | 11557.45 | 22-SEP-16:52 | 26.10 | 17.31 | 0.935458E+10 | 6391.25 | 07-SEP-21:40 | 26.10 | 17.31 |
October | 0.215760E+11 | 10869.32 | 10-OCT-15:40 | 29.63 | 20.59 | 0.935710E+10 | 6297.07 | 10-OCT-21:40 | 21.10 | 18.64 |
November | 0.195135E+11 | 10632.84 | 11-NOV-11:35 | 18.50 | 11.57 | 0.875530E+10 | 5985.08 | 08-NOV-22:40 | 18.50 | 11.57 |
December | 0.181607E+11 | 10172.43 | 10-DEC-11:35 | 12.93 | 6.50 | 0.875436E+10 | 5985.54 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.248676E+12 | 0.109256E+12 | ||||||||
Minimum of Months | 0.160704E+11 | 9824.69 | 12.43 | 5.39 | 0.791109E+10 | 5718.11 | 13.37 | 10.31 | ||
Maximum of Months | 0.247504E+11 | 12260.34 | 34.40 | 23.36 | 0.998717E+10 | 6460.34 | 34.40 | 23.36 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.554526E+11 | 27860.82 | 31-JAN-21:00 | 17.20 | 12.43 | 0.270236E+11 | 18253.43 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.530036E+11 | 29708.74 | 28-FEB-21:00 | 20.60 | 11.78 | 0.250532E+11 | 19046.45 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.645637E+11 | 32316.67 | 30-MAR-21:10 | 23.72 | 16.82 | 0.291965E+11 | 19185.87 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.650089E+11 | 34201.93 | 12-APR-15:14 | 28.13 | 16.55 | 0.286557E+11 | 19186.14 | 12-APR-22:10 | 17.88 | 13.25 |
May | 0.703760E+11 | 33344.19 | 15-MAY-18:04 | 27.70 | 16.54 | 0.302726E+11 | 19186.11 | 03-MAY-22:10 | 27.70 | 16.54 |
June | 0.723571E+11 | 34917.14 | 13-JUN-22:00 | 27.20 | 20.99 | 0.302085E+11 | 19186.18 | 08-JUN-22:10 | 27.20 | 20.99 |
July | 0.766228E+11 | 37109.41 | 07-JUL-21:10 | 30.40 | 22.79 | 0.312994E+11 | 19186.07 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.781716E+11 | 38012.95 | 18-AUG-21:10 | 30.82 | 22.88 | 0.317155E+11 | 19186.07 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.712757E+11 | 36164.83 | 07-SEP-21:10 | 25.40 | 21.43 | 0.300723E+11 | 19186.10 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.683993E+11 | 33057.75 | 10-OCT-21:53 | 21.10 | 18.56 | 0.300081E+11 | 19186.00 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.624231E+11 | 29553.06 | 06-NOV-21:00 | 12.20 | 6.19 | 0.281646E+11 | 19020.86 | 06-NOV-23:10 | 10.40 | 5.30 |
December | 0.599553E+11 | 29314.88 | 12-DEC-21:00 | 18.30 | 14.62 | 0.279831E+11 | 18977.78 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.797610E+12 | 0.349653E+12 | ||||||||
Minimum of Months | 0.530036E+11 | 27860.82 | 12.20 | 6.19 | 0.250532E+11 | 18253.43 | 10.40 | 5.30 | ||
Maximum of Months | 0.781716E+11 | 38012.95 | 30.82 | 22.88 | 0.317155E+11 | 19186.18 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52310702.20 | 2858.81 | 28-JAN-16:11 | 12.20 | 4.56 | 94403777.83 | 56.69 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.191607E+09 | 2948.28 | 27-FEB-16:11 | 22.60 | 11.36 | 86322797.27 | 57.28 | 16-FEB-22:49 | 22.60 | 11.36 |
March | 0.641635E+09 | 2948.06 | 13-MAR-15:11 | 24.07 | 13.32 | 97997818.06 | 60.19 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.104234E+10 | 2948.93 | 09-APR-15:11 | 21.70 | 11.19 | 95508531.52 | 56.69 | 18-APR-21:49 | 19.50 | 14.61 |
May | 0.144784E+10 | 2935.68 | 09-MAY-18:01 | 19.63 | 9.69 | 99207681.82 | 56.69 | 07-MAY-00:20 | 19.63 | 9.69 |
June | 0.187881E+10 | 2627.03 | 19-JUN-15:12 | 31.87 | 23.33 | 96321242.85 | 56.69 | 28-JUN-02:00 | 22.80 | 20.15 |
July | 0.209181E+10 | 2625.33 | 02-JUL-15:12 | 30.77 | 22.82 | 99450351.51 | 56.69 | 07-JUL-22:10 | 29.13 | 22.71 |
August | 0.219328E+10 | 2660.48 | 30-AUG-15:12 | 29.60 | 22.15 | 99620974.35 | 56.70 | 17-AUG-21:19 | 29.60 | 22.15 |
September | 0.153140E+10 | 2651.81 | 05-SEP-15:12 | 29.43 | 22.36 | 95968150.40 | 56.69 | 08-SEP-02:20 | 21.70 | 19.63 |
October | 0.857791E+09 | 2774.55 | 31-OCT-18:01 | 12.20 | 6.42 | 98185523.78 | 56.69 | 10-OCT-22:00 | 12.20 | 6.42 |
November | 0.347478E+09 | 2940.85 | 08-NOV-16:11 | 21.50 | 10.04 | 94095110.82 | 56.69 | 02-NOV-21:00 | 21.50 | 10.04 |
December | 0.102618E+09 | 2893.53 | 10-DEC-16:11 | 18.33 | 9.11 | 95410251.27 | 56.69 | 12-DEC-22:49 | 18.30 | 14.83 |
Annual Sum or Average | 0.123789E+11 | 0.115249E+10 | ||||||||
Minimum of Months | 52310702.20 | 2625.33 | 12.20 | 4.56 | 86322797.27 | 56.69 | 12.20 | 6.42 | ||
Maximum of Months | 0.219328E+10 | 2948.93 | 31.87 | 23.33 | 99620974.35 | 60.19 | 29.60 | 22.71 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16991565.91 | 857.80 | 12-JAN-16:14 | 9.63 | 3.50 | 93185069.30 | 57.54 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 78962492.56 | 2655.81 | 24-FEB-19:01 | 12.52 | 5.38 | 86005028.97 | 66.53 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.363668E+09 | 2893.59 | 13-MAR-15:11 | 24.07 | 13.32 | 99639424.71 | 71.18 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.758314E+09 | 3013.48 | 26-APR-18:41 | 14.60 | 7.53 | 99804217.59 | 74.05 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.120287E+10 | 3026.26 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104741E+09 | 74.90 | 10-MAY-21:10 | 14.72 | 7.99 |
June | 0.174570E+10 | 2615.12 | 05-JUN-21:51 | 22.20 | 17.55 | 99727128.50 | 80.44 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.194851E+10 | 2622.11 | 11-JUL-18:02 | 27.85 | 21.78 | 0.102659E+09 | 78.57 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.199423E+10 | 2626.83 | 24-AUG-15:12 | 29.60 | 23.92 | 0.101856E+09 | 74.38 | 07-AUG-21:00 | 29.60 | 23.92 |
September | 0.122089E+10 | 2859.33 | 18-SEP-16:01 | 25.40 | 17.60 | 0.100049E+09 | 74.40 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.495210E+09 | 2654.21 | 31-OCT-18:01 | 12.20 | 6.42 | 0.100886E+09 | 71.68 | 10-OCT-21:10 | 12.20 | 6.42 |
November | 0.142449E+09 | 2614.58 | 07-NOV-19:01 | 11.42 | 5.15 | 93848456.61 | 62.53 | 02-NOV-21:40 | 11.42 | 5.15 |
December | 36459629.52 | 2602.33 | 07-DEC-16:11 | 14.80 | 6.67 | 94146597.73 | 60.58 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.100042E+11 | 0.117655E+10 | ||||||||
Minimum of Months | 16991565.91 | 857.80 | 9.63 | 3.50 | 86005028.97 | 57.54 | 11.42 | 5.15 | ||
Maximum of Months | 0.199423E+10 | 3026.26 | 29.60 | 23.92 | 0.104741E+09 | 80.44 | 29.60 | 23.92 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30828254.65 | 277.41 | 29-JAN-13:30 | 14.45 | 6.22 | 0.00 | 0.00 | 01-JAN-00:10 | 14.45 | 6.22 |
February | 84443595.96 | 337.58 | 26-FEB-14:15 | 24.60 | 12.61 | 0.00 | 0.00 | 01-FEB-00:10 | 24.60 | 12.61 |
March | 0.230252E+09 | 320.44 | 13-MAR-16:20 | 24.40 | 14.34 | 0.00 | 0.00 | 01-MAR-00:10 | 24.40 | 14.34 |
April | 0.264278E+09 | 291.37 | 15-APR-14:00 | 27.80 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 27.80 | 15.01 |
May | 0.330713E+09 | 259.47 | 19-MAY-20:20 | 25.03 | 16.94 | 0.00 | 0.00 | 01-MAY-00:10 | 25.03 | 16.94 |
June | 0.419422E+09 | 290.58 | 13-JUN-20:20 | 29.03 | 21.92 | 0.00 | 0.00 | 01-JUN-00:10 | 29.03 | 21.92 |
July | 0.483872E+09 | 319.92 | 08-JUL-17:30 | 34.40 | 23.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 23.36 |
August | 0.553960E+09 | 342.63 | 18-AUG-16:20 | 34.80 | 22.88 | 0.00 | 0.00 | 01-AUG-00:10 | 34.80 | 22.88 |
September | 0.433534E+09 | 392.98 | 24-SEP-12:40 | 28.70 | 19.86 | 0.00 | 0.00 | 01-SEP-00:10 | 28.70 | 19.86 |
October | 0.333997E+09 | 424.74 | 10-OCT-13:30 | 28.85 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 28.85 | 20.88 |
November | 0.221566E+09 | 388.36 | 15-NOV-14:00 | 21.10 | 11.33 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 11.33 |
December | 0.112340E+09 | 371.90 | 10-DEC-14:30 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.349920E+10 | 0.00 | ||||||||
Minimum of Months | 30828254.65 | 259.47 | 14.45 | 6.22 | 0.00 | 0.00 | 14.45 | 6.22 | ||
Maximum of Months | 0.553960E+09 | 424.74 | 34.80 | 23.36 | 0.00 | 0.00 | 34.80 | 23.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63648180.45 | 943.22 | 22-JAN-09:01 | 1.38 | -0.9 | 95009577.25 | 64.13 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.134504E+09 | 1034.32 | 28-FEB-22:52 | 17.30 | 10.02 | 86988278.95 | 68.50 | 28-FEB-22:00 | 17.30 | 10.02 |
March | 0.306646E+09 | 1031.39 | 31-MAR-20:12 | 13.87 | 8.46 | 98652647.75 | 69.99 | 28-MAR-21:10 | 13.87 | 8.46 |
April | 0.429923E+09 | 1031.81 | 09-APR-20:11 | 13.70 | 8.28 | 98317846.86 | 72.77 | 24-APR-21:10 | 13.22 | 9.86 |
May | 0.584504E+09 | 1097.81 | 09-MAY-20:41 | 13.68 | 6.54 | 0.103259E+09 | 73.10 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.741943E+09 | 997.85 | 28-JUN-18:02 | 30.50 | 23.40 | 98779671.74 | 76.85 | 26-JUN-21:10 | 30.50 | 23.40 |
July | 0.803929E+09 | 997.03 | 19-JUL-18:02 | 31.42 | 22.87 | 0.101976E+09 | 75.74 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.800075E+09 | 995.83 | 13-AUG-18:02 | 30.92 | 21.87 | 0.101215E+09 | 74.25 | 31-AUG-21:19 | 21.67 | 19.98 |
September | 0.581147E+09 | 995.62 | 23-SEP-18:01 | 25.82 | 18.98 | 99271219.72 | 74.75 | 01-SEP-21:10 | 25.82 | 18.98 |
October | 0.365663E+09 | 1035.64 | 11-OCT-21:52 | 14.40 | 8.97 | 99988063.49 | 72.00 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.227318E+09 | 989.82 | 28-NOV-19:02 | 11.52 | 4.78 | 94407938.80 | 67.85 | 03-NOV-21:00 | 11.52 | 4.78 |
December | 0.117248E+09 | 942.05 | 10-DEC-09:02 | 8.35 | 3.66 | 95781094.92 | 65.09 | 12-DEC-22:00 | 18.30 | 14.87 |
Annual Sum or Average | 0.515655E+10 | 0.117365E+10 | ||||||||
Minimum of Months | 63648180.45 | 942.05 | 1.38 | -0.9 | 86988278.95 | 64.13 | 11.52 | 4.78 | ||
Maximum of Months | 0.803929E+09 | 1097.81 | 31.42 | 23.40 | 0.103259E+09 | 76.85 | 30.50 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44543659.87 | 2541.03 | 29-JAN-16:11 | 16.33 | 6.57 | 94494801.97 | 56.69 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.202859E+09 | 2692.15 | 27-FEB-16:11 | 22.60 | 11.36 | 86509048.87 | 56.91 | 16-FEB-22:49 | 22.60 | 11.36 |
March | 0.584246E+09 | 2695.62 | 13-MAR-15:11 | 24.07 | 13.32 | 98183258.90 | 57.58 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.101182E+10 | 2692.13 | 09-APR-15:11 | 21.70 | 11.19 | 95769158.48 | 56.69 | 20-APR-21:40 | 18.90 | 15.33 |
May | 0.147818E+10 | 2670.50 | 09-MAY-18:01 | 19.63 | 9.69 | 99413475.17 | 56.69 | 31-MAY-23:00 | 21.00 | 18.72 |
June | 0.191948E+10 | 2462.78 | 06-JUN-08:61 | 24.27 | 18.66 | 96436056.58 | 56.69 | 20-JUN-00:49 | 20.68 | 19.81 |
July | 0.216018E+10 | 2452.21 | 07-JUL-08:61 | 27.15 | 23.64 | 99510758.92 | 56.69 | 11-JUL-02:49 | 20.68 | 19.81 |
August | 0.220707E+10 | 2443.36 | 11-AUG-15:12 | 31.30 | 23.78 | 99662890.75 | 56.69 | 02-AUG-21:19 | 31.30 | 23.78 |
September | 0.153785E+10 | 2441.69 | 07-SEP-18:02 | 29.72 | 22.85 | 96057485.74 | 56.69 | 27-SEP-00:00 | 23.90 | 20.07 |
October | 0.839058E+09 | 2427.15 | 02-OCT-15:11 | 26.70 | 20.33 | 98346708.56 | 56.69 | 02-OCT-21:00 | 17.80 | 15.00 |
November | 0.327422E+09 | 2678.03 | 08-NOV-16:11 | 21.50 | 10.04 | 94289411.31 | 56.69 | 03-NOV-21:00 | 21.50 | 10.04 |
December | 99718635.57 | 2623.11 | 10-DEC-16:11 | 18.33 | 9.11 | 95529562.49 | 56.69 | 12-DEC-22:00 | 18.30 | 14.87 |
Annual Sum or Average | 0.124124E+11 | 0.115420E+10 | ||||||||
Minimum of Months | 44543659.87 | 2427.15 | 16.33 | 6.57 | 86509048.87 | 56.69 | 12.98 | 10.04 | ||
Maximum of Months | 0.220707E+10 | 2695.62 | 31.30 | 23.78 | 99662890.75 | 57.58 | 31.30 | 23.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18087580.11 | 1627.89 | 29-JAN-09:01 | 5.65 | 1.66 | 93236304.29 | 58.15 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 98478761.03 | 2454.49 | 24-FEB-09:02 | 7.57 | 2.82 | 85973270.62 | 65.90 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.343693E+09 | 2655.32 | 13-MAR-15:11 | 24.07 | 13.32 | 98973415.46 | 68.26 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.748486E+09 | 2571.35 | 14-APR-08:51 | 19.40 | 14.17 | 99309638.03 | 71.65 | 14-APR-21:30 | 18.60 | 13.02 |
May | 0.122988E+10 | 2686.78 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104610E+09 | 75.19 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.176248E+10 | 2718.70 | 04-JUN-08:51 | 24.40 | 18.28 | 0.100056E+09 | 77.52 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.198779E+10 | 2515.58 | 25-JUL-08:51 | 24.40 | 20.24 | 0.103206E+09 | 79.02 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.199272E+10 | 2598.62 | 26-AUG-08:51 | 24.40 | 19.19 | 0.102122E+09 | 75.85 | 07-AUG-21:00 | 24.40 | 19.19 |
September | 0.121566E+10 | 2608.26 | 15-SEP-08:51 | 21.70 | 14.94 | 0.100133E+09 | 73.95 | 01-SEP-21:10 | 21.70 | 14.94 |
October | 0.498034E+09 | 2362.72 | 09-OCT-18:01 | 24.13 | 18.81 | 0.100396E+09 | 71.07 | 17-OCT-21:10 | 23.22 | 20.61 |
November | 0.145706E+09 | 2284.27 | 06-NOV-09:01 | 12.57 | 11.17 | 93463750.20 | 62.92 | 03-NOV-21:40 | 12.57 | 11.17 |
December | 34708121.38 | 1512.47 | 10-DEC-09:02 | 8.35 | 3.66 | 94140006.30 | 60.07 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.100757E+11 | 0.117562E+10 | ||||||||
Minimum of Months | 18087580.11 | 1512.47 | 5.65 | 1.66 | 85973270.62 | 58.15 | 12.57 | 10.34 | ||
Maximum of Months | 0.199272E+10 | 2718.70 | 24.40 | 20.24 | 0.104610E+09 | 79.02 | 24.40 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175543E+10 | 1418.71 | 31-JAN-19:00 | 17.80 | 12.69 | 0.120180E+10 | 740.27 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.212619E+10 | 1648.25 | 27-FEB-19:10 | 19.82 | 10.52 | 0.110759E+10 | 803.90 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.354834E+10 | 1835.64 | 11-MAR-16:11 | 25.93 | 16.26 | 0.130215E+10 | 827.89 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.379406E+10 | 2100.87 | 12-APR-15:14 | 28.13 | 16.55 | 0.132297E+10 | 862.22 | 19-APR-21:49 | 17.98 | 15.78 |
May | 0.421309E+10 | 2044.14 | 15-MAY-18:04 | 27.70 | 16.54 | 0.142087E+10 | 877.43 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.440545E+10 | 2130.23 | 25-JUN-10:35 | 29.80 | 23.29 | 0.144507E+10 | 912.95 | 29-JUN-21:49 | 25.18 | 21.75 |
July | 0.469398E+10 | 2207.85 | 08-JUL-10:35 | 33.17 | 24.62 | 0.151612E+10 | 926.90 | 07-JUL-22:10 | 33.17 | 24.62 |
August | 0.471584E+10 | 2208.08 | 19-AUG-10:35 | 32.03 | 24.19 | 0.152910E+10 | 934.80 | 18-AUG-21:00 | 32.03 | 24.19 |
September | 0.423379E+10 | 2112.00 | 09-SEP-10:35 | 30.03 | 23.84 | 0.141448E+10 | 904.05 | 08-SEP-21:49 | 30.03 | 23.84 |
October | 0.380217E+10 | 1894.94 | 11-OCT-18:10 | 21.73 | 13.14 | 0.134926E+10 | 860.15 | 11-OCT-21:49 | 14.68 | 9.09 |
November | 0.317136E+10 | 1639.54 | 11-NOV-11:35 | 18.50 | 11.57 | 0.121628E+10 | 789.31 | 08-NOV-22:49 | 18.50 | 11.57 |
December | 0.243531E+10 | 1522.94 | 13-DEC-19:10 | 16.10 | 16.05 | 0.121147E+10 | 768.27 | 12-DEC-23:10 | 16.10 | 16.05 |
Annual Sum or Average | 0.428950E+11 | 0.160372E+11 | ||||||||
Minimum of Months | 0.175543E+10 | 1418.71 | 16.10 | 10.52 | 0.110759E+10 | 740.27 | 12.98 | 9.09 | ||
Maximum of Months | 0.471584E+10 | 2208.08 | 33.17 | 24.62 | 0.152910E+10 | 934.80 | 33.17 | 24.62 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36588290.93 | 2973.32 | 29-JAN-16:11 | 16.33 | 6.57 | 93637971.19 | 56.69 | 31-JAN-22:30 | 13.75 | 10.50 |
February | 0.162756E+09 | 3100.18 | 27-FEB-16:11 | 22.60 | 11.36 | 85718255.99 | 56.69 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.572563E+09 | 3096.46 | 13-MAR-15:11 | 24.07 | 13.32 | 97613686.45 | 58.53 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.100853E+10 | 3105.50 | 09-APR-15:11 | 21.70 | 11.19 | 95315822.43 | 56.69 | 17-APR-22:49 | 18.58 | 13.56 |
May | 0.147469E+10 | 3097.07 | 10-MAY-18:01 | 20.92 | 10.48 | 99119632.77 | 56.69 | 23-MAY-21:49 | 20.78 | 16.98 |
June | 0.194263E+10 | 2766.15 | 15-JUN-15:12 | 26.10 | 21.16 | 96280438.24 | 56.69 | 20-JUN-22:00 | 20.60 | 19.43 |
July | 0.217294E+10 | 2784.05 | 21-JUL-18:02 | 33.03 | 22.93 | 99409723.31 | 56.69 | 10-JUL-01:49 | 33.03 | 22.93 |
August | 0.227500E+10 | 2779.77 | 18-AUG-18:02 | 33.72 | 23.57 | 99596555.67 | 56.69 | 28-AUG-00:30 | 22.50 | 20.39 |
September | 0.150459E+10 | 2754.92 | 10-SEP-15:12 | 27.57 | 22.13 | 95840768.49 | 56.70 | 29-SEP-00:10 | 13.22 | 12.01 |
October | 0.767702E+09 | 2913.02 | 31-OCT-18:01 | 12.20 | 6.42 | 97842597.68 | 56.69 | 10-OCT-21:00 | 12.20 | 6.42 |
November | 0.276787E+09 | 3087.35 | 08-NOV-16:11 | 21.50 | 10.04 | 93625926.71 | 56.69 | 02-NOV-01:39 | 21.50 | 10.04 |
December | 75884182.99 | 3033.59 | 10-DEC-16:11 | 18.33 | 9.11 | 94643448.54 | 56.69 | 12-DEC-23:19 | 18.13 | 14.84 |
Annual Sum or Average | 0.122707E+11 | 0.114864E+10 | ||||||||
Minimum of Months | 36588290.93 | 2754.92 | 12.20 | 6.42 | 85718255.99 | 56.69 | 12.20 | 6.42 | ||
Maximum of Months | 0.227500E+10 | 3105.50 | 33.72 | 23.57 | 99596555.67 | 58.53 | 33.03 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12195711.33 | 1062.19 | 13-JAN-16:13 | 5.17 | 0.73 | 92553225.45 | 56.69 | 08-JAN-05:10 | 5.17 | 0.73 |
February | 57969371.09 | 2752.51 | 24-FEB-19:01 | 12.52 | 5.38 | 85470307.43 | 66.46 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.307513E+09 | 3028.94 | 13-MAR-15:11 | 24.07 | 13.32 | 99187759.40 | 71.40 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.733308E+09 | 3184.36 | 09-APR-20:11 | 13.70 | 8.28 | 99914748.08 | 75.50 | 14-APR-21:30 | 18.60 | 13.02 |
May | 0.126002E+10 | 3237.63 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104847E+09 | 77.08 | 10-MAY-21:10 | 14.72 | 7.99 |
June | 0.183973E+10 | 2750.83 | 05-JUN-21:51 | 22.20 | 17.55 | 99553844.33 | 81.87 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.206047E+10 | 2791.55 | 21-JUL-18:02 | 33.03 | 22.93 | 0.102408E+09 | 78.77 | 18-JUL-21:10 | 33.03 | 22.93 |
August | 0.209514E+10 | 2744.17 | 11-AUG-18:02 | 24.90 | 23.08 | 0.101649E+09 | 74.33 | 07-AUG-21:00 | 24.90 | 23.08 |
September | 0.122042E+10 | 2975.47 | 18-SEP-16:01 | 25.40 | 17.60 | 99715870.59 | 74.07 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.420836E+09 | 2832.62 | 15-OCT-16:21 | 24.15 | 17.28 | 0.100394E+09 | 71.62 | 10-OCT-21:19 | 24.15 | 17.28 |
November | 0.100107E+09 | 2706.92 | 06-NOV-19:12 | 13.87 | 6.89 | 93153059.77 | 61.80 | 02-NOV-21:40 | 13.87 | 6.89 |
December | 23883909.55 | 1573.77 | 07-DEC-16:11 | 14.80 | 6.67 | 93315662.42 | 59.12 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.101316E+11 | 0.117216E+10 | ||||||||
Minimum of Months | 12195711.33 | 1062.19 | 5.17 | 0.73 | 85470307.43 | 56.69 | 5.17 | 0.73 | ||
Maximum of Months | 0.209514E+10 | 3237.63 | 33.03 | 23.08 | 0.104847E+09 | 81.87 | 33.03 | 23.08 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153487E+09 | 1612.45 | 28-JAN-16:11 | 12.20 | 4.56 | 96247163.45 | 58.07 | 19-JAN-22:49 | 12.20 | 4.56 |
February | 0.250034E+09 | 1654.08 | 27-FEB-16:11 | 22.60 | 11.36 | 87594256.21 | 61.71 | 16-FEB-22:49 | 22.60 | 11.36 |
March | 0.535174E+09 | 1657.33 | 13-MAR-15:11 | 24.07 | 13.32 | 98352331.07 | 62.81 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.661649E+09 | 1623.98 | 09-APR-18:01 | 20.45 | 11.08 | 95514323.79 | 56.69 | 18-APR-22:49 | 18.98 | 14.30 |
May | 0.846779E+09 | 1621.99 | 10-MAY-18:01 | 20.92 | 10.48 | 99131136.86 | 56.69 | 26-MAY-21:00 | 18.30 | 17.97 |
June | 0.106729E+10 | 1487.15 | 22-JUN-18:02 | 30.40 | 22.95 | 96274831.63 | 56.69 | 06-JUN-23:49 | 30.40 | 22.95 |
July | 0.121330E+10 | 1486.93 | 31-JUL-18:02 | 29.82 | 23.24 | 99405087.58 | 56.70 | 12-JUL-21:19 | 29.82 | 23.24 |
August | 0.134178E+10 | 1488.33 | 04-AUG-18:02 | 28.80 | 23.56 | 99608045.39 | 56.69 | 02-AUG-21:00 | 28.80 | 23.56 |
September | 0.101599E+10 | 1485.54 | 26-SEP-18:01 | 26.93 | 20.31 | 95943937.05 | 56.69 | 20-SEP-22:49 | 26.93 | 20.31 |
October | 0.738835E+09 | 1603.60 | 12-OCT-18:01 | 17.23 | 10.36 | 98513080.02 | 56.69 | 02-OCT-22:49 | 17.23 | 10.36 |
November | 0.486140E+09 | 1653.83 | 08-NOV-16:11 | 21.50 | 10.04 | 95128355.97 | 56.69 | 01-NOV-21:19 | 21.50 | 10.04 |
December | 0.267730E+09 | 1631.50 | 10-DEC-16:11 | 18.33 | 9.11 | 97079659.56 | 56.69 | 12-DEC-22:00 | 18.30 | 14.87 |
Annual Sum or Average | 0.857819E+10 | 0.115879E+10 | ||||||||
Minimum of Months | 0.153487E+09 | 1485.54 | 12.20 | 4.56 | 87594256.21 | 56.69 | 12.20 | 4.56 | ||
Maximum of Months | 0.134178E+10 | 1657.33 | 30.40 | 23.56 | 99608045.39 | 62.81 | 30.40 | 23.56 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345520E+11 | 17331.12 | 19-JAN-23:10 | 18.22 | 16.49 | 0.160717E+11 | 11018.61 | 19-JAN-23:49 | 17.88 | 16.40 |
February | 0.329118E+11 | 17962.53 | 28-FEB-22:00 | 18.90 | 10.96 | 0.148516E+11 | 11341.79 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.397489E+11 | 19633.12 | 30-MAR-21:10 | 23.72 | 16.82 | 0.171580E+11 | 11348.66 | 13-MAR-22:10 | 23.72 | 16.82 |
April | 0.404850E+11 | 21425.15 | 12-APR-15:14 | 28.13 | 16.55 | 0.169101E+11 | 11348.98 | 12-APR-22:10 | 17.88 | 13.25 |
May | 0.438928E+11 | 21050.50 | 13-MAY-17:05 | 26.02 | 14.15 | 0.178292E+11 | 11348.94 | 03-MAY-22:10 | 26.02 | 14.15 |
June | 0.441825E+11 | 20899.61 | 13-JUN-22:00 | 27.20 | 20.99 | 0.175644E+11 | 11349.06 | 07-JUN-22:10 | 27.20 | 20.99 |
July | 0.461460E+11 | 21377.06 | 07-JUL-22:00 | 29.40 | 22.70 | 0.181205E+11 | 11348.94 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.461737E+11 | 21103.86 | 18-AUG-22:00 | 29.40 | 23.06 | 0.182375E+11 | 11348.93 | 07-AUG-22:10 | 29.40 | 23.06 |
September | 0.424049E+11 | 20825.39 | 22-SEP-16:52 | 26.10 | 17.31 | 0.172485E+11 | 11348.93 | 11-SEP-22:10 | 26.10 | 17.31 |
October | 0.406942E+11 | 19503.78 | 18-OCT-21:10 | 23.22 | 22.46 | 0.172272E+11 | 11348.78 | 10-OCT-22:10 | 23.22 | 22.46 |
November | 0.370722E+11 | 17846.67 | 03-NOV-21:00 | 18.30 | 16.18 | 0.162122E+11 | 11286.78 | 03-NOV-22:49 | 17.80 | 16.05 |
December | 0.360964E+11 | 17651.07 | 12-DEC-23:10 | 18.22 | 14.85 | 0.163337E+11 | 11189.29 | 12-DEC-23:49 | 17.88 | 14.79 |
Annual Sum or Average | 0.484361E+12 | 0.203765E+12 | ||||||||
Minimum of Months | 0.329118E+11 | 17331.12 | 18.22 | 10.96 | 0.148516E+11 | 11018.61 | 17.02 | 9.75 | ||
Maximum of Months | 0.461737E+11 | 21425.15 | 29.40 | 23.06 | 0.182375E+11 | 11349.06 | 29.40 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371230E+11 | 18302.85 | 19-JAN-22:15 | 18.30 | 16.51 | 0.166413E+11 | 11347.43 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.350484E+11 | 19935.22 | 28-FEB-22:10 | 18.63 | 10.80 | 0.153655E+11 | 11348.56 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.416793E+11 | 20862.05 | 30-MAR-21:07 | 23.72 | 16.82 | 0.176748E+11 | 11348.67 | 13-MAR-22:10 | 23.72 | 16.82 |
April | 0.421481E+11 | 22000.43 | 12-APR-15:14 | 28.13 | 16.55 | 0.173353E+11 | 11349.06 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.455203E+11 | 21682.90 | 13-MAY-17:05 | 26.02 | 14.15 | 0.182154E+11 | 11348.97 | 10-MAY-21:40 | 26.02 | 14.15 |
June | 0.457895E+11 | 22280.58 | 13-JUN-22:00 | 27.20 | 20.99 | 0.179223E+11 | 11349.06 | 07-JUN-22:10 | 27.20 | 20.99 |
July | 0.478355E+11 | 22729.76 | 07-JUL-22:00 | 29.40 | 22.70 | 0.184731E+11 | 11348.94 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.478464E+11 | 22451.77 | 18-AUG-22:00 | 29.40 | 23.06 | 0.185892E+11 | 11348.94 | 07-AUG-22:10 | 29.40 | 23.06 |
September | 0.439350E+11 | 21495.06 | 06-SEP-22:00 | 26.70 | 22.61 | 0.176143E+11 | 11348.94 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.424209E+11 | 20633.12 | 18-OCT-21:10 | 23.22 | 22.46 | 0.176830E+11 | 11348.79 | 10-OCT-22:10 | 23.22 | 22.46 |
November | 0.390640E+11 | 19639.63 | 03-NOV-21:10 | 18.22 | 16.16 | 0.167520E+11 | 11348.34 | 02-NOV-22:10 | 18.22 | 16.16 |
December | 0.385078E+11 | 18753.23 | 12-DEC-24:00 | 17.80 | 14.77 | 0.169315E+11 | 11347.99 | 12-DEC-23:10 | 17.80 | 14.77 |
Annual Sum or Average | 0.506918E+12 | 0.209198E+12 | ||||||||
Minimum of Months | 0.350484E+11 | 18302.85 | 17.80 | 10.80 | 0.153655E+11 | 11347.43 | 12.98 | 9.75 | ||
Maximum of Months | 0.478464E+11 | 22729.76 | 29.40 | 23.06 | 0.185892E+11 | 11349.06 | 29.40 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464143E+11 | 26072.10 | 29-JAN-11:50 | 12.62 | 5.48 | 0.188680E+11 | 11319.61 | 07-JAN-18:10 | 12.62 | 5.48 |
February | 0.433857E+11 | 27104.05 | 26-FEB-11:50 | 22.43 | 11.86 | 0.170436E+11 | 11321.60 | 18-FEB-18:19 | 22.43 | 11.86 |
March | 0.507499E+11 | 28283.00 | 11-MAR-16:11 | 25.93 | 16.26 | 0.188763E+11 | 11319.57 | 11-MAR-18:10 | 24.22 | 15.08 |
April | 0.508349E+11 | 31283.36 | 15-APR-10:36 | 24.83 | 14.24 | 0.182644E+11 | 11345.99 | 15-APR-17:49 | 25.28 | 15.39 |
May | 0.542636E+11 | 30481.33 | 13-MAY-17:05 | 26.02 | 14.15 | 0.188728E+11 | 11358.34 | 13-MAY-17:00 | 25.60 | 14.52 |
June | 0.539154E+11 | 29222.86 | 02-JUN-10:40 | 26.33 | 17.12 | 0.182665E+11 | 11334.53 | 10-JUN-17:40 | 29.07 | 13.91 |
July | 0.561438E+11 | 29649.66 | 08-JUL-10:40 | 33.17 | 24.62 | 0.188681E+11 | 11319.67 | 15-JUL-17:10 | 33.30 | 24.04 |
August | 0.562161E+11 | 29501.19 | 27-AUG-10:50 | 30.03 | 22.67 | 0.188754E+11 | 11319.68 | 12-AUG-17:10 | 30.03 | 22.67 |
September | 0.525078E+11 | 30384.45 | 22-SEP-16:52 | 26.10 | 17.31 | 0.182622E+11 | 11321.59 | 30-SEP-17:19 | 17.60 | 15.56 |
October | 0.515811E+11 | 28019.75 | 09-OCT-10:50 | 24.03 | 18.11 | 0.188689E+11 | 11321.59 | 28-OCT-17:19 | 17.03 | 17.03 |
November | 0.479309E+11 | 26801.95 | 11-NOV-11:50 | 18.95 | 11.69 | 0.182587E+11 | 11319.41 | 04-NOV-17:10 | 18.95 | 11.69 |
December | 0.476831E+11 | 26335.99 | 12-DEC-11:50 | 20.22 | 16.28 | 0.188680E+11 | 11319.43 | 02-DEC-18:10 | 20.22 | 16.28 |
Annual Sum or Average | 0.611627E+12 | 0.222193E+12 | ||||||||
Minimum of Months | 0.433857E+11 | 26072.10 | 12.62 | 5.48 | 0.170436E+11 | 11319.41 | 12.62 | 5.48 | ||
Maximum of Months | 0.562161E+11 | 31283.36 | 33.17 | 24.62 | 0.188763E+11 | 11358.34 | 33.30 | 24.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182480E+10 | 1706.96 | 31-JAN-19:00 | 17.80 | 12.69 | 0.128726E+10 | 862.12 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.251467E+10 | 2054.73 | 28-FEB-18:15 | 22.43 | 12.28 | 0.123143E+10 | 970.05 | 28-FEB-22:49 | 17.57 | 10.18 |
March | 0.443793E+10 | 3212.45 | 30-MAR-15:13 | 27.80 | 17.21 | 0.152891E+10 | 1007.40 | 29-MAR-22:10 | 27.80 | 17.21 |
April | 0.519526E+10 | 4213.69 | 17-APR-15:10 | 28.90 | 16.41 | 0.157877E+10 | 1007.40 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.666185E+10 | 4620.35 | 30-MAY-15:10 | 30.13 | 21.49 | 0.170135E+10 | 1007.40 | 23-MAY-22:10 | 30.13 | 21.49 |
June | 0.830117E+10 | 5182.75 | 13-JUN-15:40 | 32.40 | 22.24 | 0.166321E+10 | 1007.40 | 08-JUN-22:10 | 32.40 | 22.24 |
July | 0.930274E+10 | 5886.25 | 08-JUL-16:10 | 36.32 | 23.83 | 0.171363E+10 | 1007.40 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.956867E+10 | 5821.52 | 18-AUG-15:10 | 34.50 | 23.13 | 0.172178E+10 | 1007.40 | 30-AUG-22:10 | 22.80 | 20.87 |
September | 0.676508E+10 | 5067.14 | 07-SEP-15:23 | 31.70 | 23.32 | 0.164888E+10 | 1007.40 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.490414E+10 | 3827.92 | 10-OCT-15:13 | 29.27 | 20.62 | 0.159286E+10 | 1007.40 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.386295E+10 | 2079.20 | 05-NOV-17:15 | 21.10 | 17.61 | 0.139705E+10 | 950.22 | 05-NOV-23:19 | 14.43 | 14.43 |
December | 0.293610E+10 | 1904.01 | 13-DEC-11:35 | 19.80 | 17.47 | 0.132163E+10 | 918.71 | 12-DEC-23:10 | 19.80 | 17.47 |
Annual Sum or Average | 0.662753E+11 | 0.183867E+11 | ||||||||
Minimum of Months | 0.182480E+10 | 1706.96 | 17.80 | 12.28 | 0.123143E+10 | 862.12 | 13.37 | 10.18 | ||
Maximum of Months | 0.956867E+10 | 5886.25 | 36.32 | 23.83 | 0.172178E+10 | 1007.40 | 32.40 | 22.24 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222449E+09 | 937.22 | 08-JAN-05:20 | -5.4 |
February | 0.106055E+09 | 1133.07 | 12-FEB-06:00 | -12.2 |
March | 98673.14 | 37.07 | 23-MAR-08:08 | 6.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 3180322.87 | 326.65 | 21-NOV-07:10 | -2.8 |
December | 20663733.96 | 486.95 | 01-DEC-07:15 | -3.7 |
Annual Sum or Average | 0.352447E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.222449E+09 | 1133.07 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92043610.92 | 446.07 | 08-JAN-13:40 | -0.8 |
February | 52271673.12 | 374.14 | 13-FEB-10:30 | -0.3 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.144315E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 92043610.92 | 446.07 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200020E+09 | 398.60 | 08-JAN-06:00 | -5.0 |
February | 0.121087E+09 | 432.06 | 12-FEB-09:03 | -10.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 9364226.00 | 130.20 | 18-DEC-08:05 | -5.0 |
Annual Sum or Average | 0.330471E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.2 | |
Maximum of Months | 0.200020E+09 | 432.06 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.638607E+09 | 2242.69 | 07-JAN-16:11 | -4.3 |
February | 0.353934E+09 | 2229.79 | 03-FEB-09:01 | -6.8 |
March | 36605271.46 | 2127.69 | 23-MAR-08:62 | 6.97 |
April | 9026782.36 | 1544.47 | 06-APR-08:62 | 5.37 |
May | 940206.16 | 796.69 | 17-MAY-08:04 | 19.87 |
June | 216263.00 | 743.16 | 09-JUN-08:05 | 21.38 |
July | 151603.24 | 429.49 | 28-JUL-08:06 | 19.40 |
August | 12559.72 | 125.60 | 30-AUG-08:05 | 21.28 |
September | 1016673.46 | 734.97 | 01-SEP-08:05 | 20.18 |
October | 25312193.44 | 2083.65 | 31-OCT-08:62 | 7.80 |
November | 97488446.66 | 2171.80 | 30-NOV-16:11 | 7.20 |
December | 0.353014E+09 | 2192.01 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.151633E+10 | |||
Minimum of Months | 12559.72 | 125.60 | -6.8 | |
Maximum of Months | 0.638607E+09 | 2242.69 | 21.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.848422E+09 | 2239.31 | 07-JAN-16:11 | -4.3 |
February | 0.475243E+09 | 2238.40 | 03-FEB-09:01 | -6.8 |
March | 52560086.91 | 2124.75 | 23-MAR-08:62 | 6.97 |
April | 12471951.45 | 1786.33 | 06-APR-08:62 | 5.37 |
May | 774594.96 | 728.03 | 12-MAY-08:04 | 15.28 |
June | 93317.42 | 259.76 | 02-JUN-08:54 | 23.90 |
July | 76045.14 | 268.97 | 11-JUL-08:36 | 25.53 |
August | 44327.53 | 237.88 | 25-AUG-08:54 | 24.40 |
September | 690617.70 | 716.91 | 29-SEP-08:04 | 14.78 |
October | 32881396.87 | 2124.58 | 26-OCT-08:62 | 5.05 |
November | 0.165815E+09 | 2215.18 | 22-NOV-09:01 | 1.05 |
December | 0.522617E+09 | 2227.66 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.211169E+10 | |||
Minimum of Months | 44327.53 | 237.88 | -6.8 | |
Maximum of Months | 0.848422E+09 | 2239.31 | 25.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81004341.45 | 677.40 | 07-JAN-16:11 | -4.3 |
February | 43752699.44 | 672.99 | 12-FEB-16:11 | 3.50 |
March | 773761.65 | 311.08 | 31-MAR-15:16 | 15.73 |
April | 302003.35 | 376.13 | 06-APR-08:04 | 5.37 |
May | 111214.26 | 192.94 | 15-MAY-08:55 | 20.60 |
June | 7576.88 | 38.07 | 11-JUN-15:17 | 32.40 |
July | 6797.77 | 47.72 | 29-JUL-08:58 | 17.80 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 105606.70 | 175.37 | 19-SEP-08:54 | 19.40 |
October | 615416.86 | 308.75 | 26-OCT-08:03 | 5.05 |
November | 3561694.15 | 642.30 | 22-NOV-16:11 | 11.83 |
December | 19993803.29 | 656.80 | 03-DEC-16:11 | 6.33 |
Annual Sum or Average | 0.150235E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.3 | |
Maximum of Months | 81004341.45 | 677.40 | 32.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.644474E+09 | 2177.94 | 07-JAN-16:11 | -4.3 |
February | 0.347324E+09 | 2159.23 | 11-FEB-19:01 | -6.2 |
March | 41429552.21 | 2063.97 | 23-MAR-08:62 | 6.97 |
April | 9649875.73 | 962.78 | 06-APR-15:14 | 15.60 |
May | 249409.76 | 513.08 | 10-MAY-18:06 | 20.92 |
June | 4946.98 | 49.47 | 23-JUN-08:07 | 24.18 |
July | 173414.12 | 454.35 | 28-JUL-08:06 | 19.40 |
August | 8461.14 | 75.16 | 24-AUG-08:07 | 23.80 |
September | 577147.66 | 678.71 | 30-SEP-15:15 | 17.97 |
October | 26118592.36 | 2025.86 | 31-OCT-08:62 | 7.80 |
November | 97768776.13 | 2108.98 | 30-NOV-16:11 | 7.20 |
December | 0.347578E+09 | 2129.20 | 25-DEC-16:11 | 5.93 |
Annual Sum or Average | 0.151536E+10 | |||
Minimum of Months | 4946.98 | 49.47 | -6.2 | |
Maximum of Months | 0.644474E+09 | 2177.94 | 24.18 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.862162E+09 | 2176.00 | 07-JAN-16:11 | -4.3 |
February | 0.465511E+09 | 2161.74 | 12-FEB-16:11 | 3.50 |
March | 57381659.96 | 2062.67 | 23-MAR-08:62 | 6.97 |
April | 12357805.38 | 874.61 | 25-APR-19:04 | 14.13 |
May | 360813.47 | 706.72 | 10-MAY-21:24 | 14.15 |
June | 31847.89 | 172.93 | 10-JUN-21:56 | 21.10 |
July | 59683.28 | 212.82 | 28-JUL-08:56 | 19.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 361136.63 | 720.39 | 29-SEP-08:04 | 14.78 |
October | 34091522.02 | 2023.22 | 31-OCT-08:62 | 7.80 |
November | 0.162286E+09 | 2113.72 | 30-NOV-16:11 | 7.20 |
December | 0.513398E+09 | 2149.08 | 03-DEC-16:11 | 6.33 |
Annual Sum or Average | 0.210800E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.3 | |
Maximum of Months | 0.862162E+09 | 2176.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50269749.86 | 556.89 | 09-JAN-09:10 | -3.2 |
February | 9685447.10 | 241.27 | 07-FEB-14:30 | 5.85 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 59955196.95 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 50269749.86 | 556.89 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106149E+10 | 2662.93 | 07-JAN-16:11 | -4.3 |
February | 0.617171E+09 | 2644.27 | 03-FEB-09:01 | -6.8 |
March | 0.110633E+09 | 2557.34 | 23-MAR-08:62 | 6.97 |
April | 31712607.45 | 2492.78 | 06-APR-08:62 | 5.37 |
May | 1158020.57 | 793.21 | 14-MAY-08:04 | 16.15 |
June | 270333.89 | 753.45 | 08-JUN-08:03 | 17.57 |
July | 176265.89 | 538.51 | 28-JUL-18:05 | 18.90 |
August | 88538.37 | 296.99 | 07-AUG-08:04 | 25.97 |
September | 1272990.22 | 637.27 | 20-SEP-08:03 | 18.58 |
October | 75055066.96 | 2539.20 | 26-OCT-08:62 | 5.05 |
November | 0.234247E+09 | 2618.26 | 30-NOV-16:11 | 7.20 |
December | 0.661065E+09 | 2629.31 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.279434E+10 | |||
Minimum of Months | 88538.37 | 296.99 | -6.8 | |
Maximum of Months | 0.106149E+10 | 2662.93 | 25.97 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133542E+10 | 2657.05 | 07-JAN-16:11 | -4.3 |
February | 0.779717E+09 | 2654.05 | 03-FEB-09:01 | -6.8 |
March | 0.145143E+09 | 2551.91 | 23-MAR-08:62 | 6.97 |
April | 35723527.15 | 2494.72 | 06-APR-08:62 | 5.37 |
May | 1032401.44 | 890.26 | 14-MAY-08:04 | 16.15 |
June | 260542.68 | 779.28 | 07-JUN-08:53 | 18.90 |
July | 71824.25 | 340.49 | 28-JUL-21:55 | 17.80 |
August | 36388.97 | 187.84 | 25-AUG-08:54 | 24.40 |
September | 697489.04 | 667.37 | 23-SEP-08:53 | 22.20 |
October | 97853900.89 | 2565.63 | 26-OCT-08:62 | 5.05 |
November | 0.357418E+09 | 2622.07 | 22-NOV-09:01 | 1.05 |
December | 0.891177E+09 | 2637.72 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.364455E+10 | |||
Minimum of Months | 36388.97 | 187.84 | -6.8 | |
Maximum of Months | 0.133542E+10 | 2657.05 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252077E+09 | 1395.82 | 07-JAN-16:11 | -4.3 |
February | 0.131670E+09 | 1383.02 | 07-FEB-16:11 | 6.70 |
March | 15318133.62 | 1309.40 | 23-MAR-08:62 | 6.97 |
April | 6241236.67 | 860.75 | 06-APR-08:62 | 5.37 |
May | 462932.54 | 374.48 | 11-MAY-08:03 | 12.15 |
June | 156200.72 | 283.80 | 08-JUN-08:03 | 17.57 |
July | 119378.01 | 207.56 | 28-JUL-18:05 | 18.90 |
August | 119981.32 | 166.40 | 14-AUG-08:06 | 24.68 |
September | 567372.11 | 454.85 | 30-SEP-15:15 | 17.97 |
October | 8736399.55 | 924.08 | 30-OCT-15:12 | 11.50 |
November | 26453780.34 | 1340.53 | 30-NOV-16:11 | 7.20 |
December | 0.107481E+09 | 1355.07 | 25-DEC-16:11 | 5.93 |
Annual Sum or Average | 0.549403E+09 | |||
Minimum of Months | 119378.01 | 166.40 | -4.3 | |
Maximum of Months | 0.252077E+09 | 1395.82 | 24.68 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530467E+09 | 2021.65 | 08-JAN-05:20 | -5.4 |
February | 0.266015E+09 | 2421.61 | 12-FEB-06:20 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 3115036.84 | 482.32 | 22-NOV-07:05 | -3.2 |
December | 49693465.25 | 1165.19 | 18-DEC-07:40 | -5.4 |
Annual Sum or Average | 0.849290E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.530467E+09 | 2421.61 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.831825E+10 | 8012.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.751062E+10 | 8012.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.834390E+10 | 8012.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.803622E+10 | 8012.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.833268E+10 | 8012.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.807308E+10 | 8012.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.829582E+10 | 8012.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.834710E+10 | 8012.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.803943E+10 | 8012.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.831505E+10 | 8012.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.806667E+10 | 8012.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.829582E+10 | 8012.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.979746E+11 | 0.143105E+12 | ||||
Minimum of Months | 0.751062E+10 | 8012.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.834710E+10 | 8012.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.376443E+09 | 362.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.339893E+09 | 362.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.377603E+09 | 362.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.363679E+09 | 362.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.377095E+09 | 362.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.365347E+09 | 362.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.375427E+09 | 362.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.377748E+09 | 362.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.363824E+09 | 362.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.376298E+09 | 362.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.365057E+09 | 362.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.375427E+09 | 362.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.443384E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.339893E+09 | 362.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.377748E+09 | 362.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435922E+09 | 419.88 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.393598E+09 | 419.88 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.437266E+09 | 419.88 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.421142E+09 | 419.88 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.436678E+09 | 419.88 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.423074E+09 | 419.88 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.434746E+09 | 419.88 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.437434E+09 | 419.88 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.421310E+09 | 419.88 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.435754E+09 | 419.88 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.422738E+09 | 419.88 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.434746E+09 | 419.88 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.513441E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.393598E+09 | 419.88 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.437434E+09 | 419.88 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.779939E+09 | 751.24 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.704214E+09 | 751.24 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.782343E+09 | 751.24 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.753495E+09 | 751.24 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.781291E+09 | 751.24 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.756951E+09 | 751.24 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.777835E+09 | 751.24 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.782643E+09 | 751.24 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.753796E+09 | 751.24 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.779638E+09 | 751.24 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.756350E+09 | 751.24 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.777835E+09 | 751.24 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.918633E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.704214E+09 | 751.24 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.782643E+09 | 751.24 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.178779E+09 | 172.20 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.161422E+09 | 172.20 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.179330E+09 | 172.20 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.172718E+09 | 172.20 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.179089E+09 | 172.20 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.173510E+09 | 172.20 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.178297E+09 | 172.20 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.179399E+09 | 172.20 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.172787E+09 | 172.20 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.178711E+09 | 172.20 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.173372E+09 | 172.20 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.178297E+09 | 172.20 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.210571E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.161422E+09 | 172.20 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.179399E+09 | 172.20 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332743E+09 | 320.50 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.300437E+09 | 320.50 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.333769E+09 | 320.50 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.321462E+09 | 320.50 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.333320E+09 | 320.50 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.322936E+09 | 320.50 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.331846E+09 | 320.50 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.333897E+09 | 320.50 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.321590E+09 | 320.50 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.332615E+09 | 320.50 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.322680E+09 | 320.50 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.331846E+09 | 320.50 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.391914E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.300437E+09 | 320.50 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.333897E+09 | 320.50 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.671083E+09 | 858.63 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.600885E+09 | 858.63 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.611283E+09 | 858.63 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.544135E+09 | 858.63 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.524909E+09 | 858.63 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.490495E+09 | 858.63 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.514595E+09 | 858.63 | 03-JUL-19:49 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.544154E+09 | 858.63 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.579849E+09 | 858.63 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.645664E+09 | 858.63 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.640617E+09 | 858.63 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.669540E+09 | 858.63 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.703721E+10 | 0.143405E+11 | ||||
Minimum of Months | 0.490495E+09 | 858.63 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.671083E+09 | 858.63 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.717810E+10 | 7223.65 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.647888E+10 | 7223.65 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.712003E+10 | 7223.65 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.680338E+10 | 7223.65 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.699843E+10 | 7223.65 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.675416E+10 | 7223.65 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.695624E+10 | 7223.65 | 03-JUL-19:49 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.703090E+10 | 7223.65 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.684987E+10 | 7223.65 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.714961E+10 | 7223.65 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.694498E+10 | 7223.65 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.715882E+10 | 7223.65 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.834234E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.647888E+10 | 7223.65 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.717810E+10 | 7223.65 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.122781E+10 | 1182.64 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.110860E+10 | 1182.64 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.123160E+10 | 1182.64 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.118618E+10 | 1182.64 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.122994E+10 | 1182.64 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.119162E+10 | 1182.64 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.122450E+10 | 1182.64 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.123207E+10 | 1182.64 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.118666E+10 | 1182.64 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.122734E+10 | 1182.64 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.119068E+10 | 1182.64 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.122450E+10 | 1182.64 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.144615E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.110860E+10 | 1182.64 | 0.00 | 0.00 | |
Maximum of Months | 0.123207E+10 | 1182.64 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140228E+10 | 1507.83 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.126055E+10 | 1507.83 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.133538E+10 | 1507.83 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.123381E+10 | 1507.83 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.122894E+10 | 1507.83 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.116874E+10 | 1507.83 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.121522E+10 | 1507.83 | 03-JUL-19:49 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.125445E+10 | 1507.83 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.127123E+10 | 1507.83 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.138011E+10 | 1507.83 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.134522E+10 | 1507.83 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.139800E+10 | 1507.83 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.154939E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.116874E+10 | 1507.83 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.140228E+10 | 1507.83 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140228E+10 | 1507.83 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.126055E+10 | 1507.83 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.133538E+10 | 1507.83 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.123381E+10 | 1507.83 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.122894E+10 | 1507.83 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.116874E+10 | 1507.83 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.121522E+10 | 1507.83 | 03-JUL-19:49 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.125445E+10 | 1507.83 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.127123E+10 | 1507.83 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.138011E+10 | 1507.83 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.134522E+10 | 1507.83 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.139800E+10 | 1507.83 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.154939E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.116874E+10 | 1507.83 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.140228E+10 | 1507.83 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.822206E+09 | 791.95 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.742377E+09 | 791.95 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.824741E+09 | 791.95 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.794330E+09 | 791.95 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.823632E+09 | 791.95 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.797973E+09 | 791.95 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.819989E+09 | 791.95 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.825057E+09 | 791.95 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.794646E+09 | 791.95 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.821890E+09 | 791.95 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.797339E+09 | 791.95 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.819989E+09 | 791.95 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.968417E+10 | 0.424019E+12 | ||||
Minimum of Months | 0.742377E+09 | 791.95 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.825057E+09 | 791.95 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.129945E+10 | 1251.64 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.117329E+10 | 1251.64 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.130346E+10 | 1251.64 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.125539E+10 | 1251.64 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.130170E+10 | 1251.64 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.126115E+10 | 1251.64 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.129595E+10 | 1251.64 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.130396E+10 | 1251.64 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.125589E+10 | 1251.64 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.129895E+10 | 1251.64 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.126015E+10 | 1251.64 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.129595E+10 | 1251.64 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.153053E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.117329E+10 | 1251.64 | 0.00 | 0.00 | |
Maximum of Months | 0.130396E+10 | 1251.64 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.831825E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.751062E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.834390E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.803622E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.833268E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.807308E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.829582E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.834710E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.803943E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.831505E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.806667E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.829582E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.979746E+11 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.751062E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.834710E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.376443E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572915E+09 |
February | 0.179968E+10 | 0.339893E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 141537.86 | 0.404358E+09 |
March | 0.199990E+10 | 0.377603E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2118812.17 | 0.273242E+09 |
April | 0.192973E+10 | 0.363679E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10029439.32 | 0.177049E+09 |
May | 0.199475E+10 | 0.377095E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25896932.18 | 99492092.00 |
June | 0.193394E+10 | 0.365347E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70726962.95 | 41252417.22 |
July | 0.199054E+10 | 0.375427E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91139439.90 | 24650631.86 |
August | 0.199896E+10 | 0.377748E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88116936.06 | 10515838.34 |
September | 0.192879E+10 | 0.363824E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30501447.45 | 60983507.34 |
October | 0.199148E+10 | 0.376298E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4939696.28 | 0.218364E+09 |
November | 0.192552E+10 | 0.365057E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177006.45 | 0.315441E+09 |
December | 0.199054E+10 | 0.375427E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451165E+09 |
Annual Sum or Average | 0.234744E+11 | 0.443384E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323788E+09 | 0.264943E+10 |
Minimum of Months | 0.179968E+10 | 0.339893E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10515838.34 |
Maximum of Months | 0.199990E+10 | 0.377748E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91139439.90 | 0.572915E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.435922E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220868E+09 |
February | 0.208403E+10 | 0.393598E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 440233.48 | 0.155999E+09 |
March | 0.231589E+10 | 0.437266E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1764563.66 | 0.104242E+09 |
April | 0.223463E+10 | 0.421142E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6984951.60 | 68726400.91 |
May | 0.230993E+10 | 0.436678E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14709325.06 | 37983377.92 |
June | 0.223950E+10 | 0.423074E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32934783.09 | 15419988.33 |
July | 0.230505E+10 | 0.434746E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40444620.71 | 8805047.98 |
August | 0.231480E+10 | 0.437434E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39421300.99 | 3459652.45 |
September | 0.223354E+10 | 0.421310E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16156120.34 | 23081142.90 |
October | 0.230614E+10 | 0.435754E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3693104.46 | 82956204.82 |
November | 0.222975E+10 | 0.422738E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 337767.65 | 0.121304E+09 |
December | 0.230505E+10 | 0.434746E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27749.61 | 0.174031E+09 |
Annual Sum or Average | 0.271834E+11 | 0.513441E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156915E+09 | 0.101688E+10 |
Minimum of Months | 0.208403E+10 | 0.393598E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3459652.45 |
Maximum of Months | 0.231589E+10 | 0.437434E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40444620.71 | 0.220868E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.779939E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534808E+09 |
February | 0.440737E+09 | 0.704214E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 255911.82 | 0.389602E+09 |
March | 0.489771E+09 | 0.782343E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1577967.76 | 0.284175E+09 |
April | 0.472586E+09 | 0.753495E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7951625.83 | 0.193983E+09 |
May | 0.488511E+09 | 0.781291E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20991825.07 | 0.111769E+09 |
June | 0.473617E+09 | 0.756951E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62954503.67 | 43686101.10 |
July | 0.487480E+09 | 0.777835E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82228248.25 | 27152939.43 |
August | 0.489542E+09 | 0.782643E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79930868.17 | 11065185.56 |
September | 0.472357E+09 | 0.753796E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26796824.05 | 68220590.01 |
October | 0.487709E+09 | 0.779638E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3953565.91 | 0.231359E+09 |
November | 0.471555E+09 | 0.756350E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41035.02 | 0.326601E+09 |
December | 0.487480E+09 | 0.777835E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441723E+09 |
Annual Sum or Average | 0.574883E+10 | 0.918633E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286682E+09 | 0.266415E+10 |
Minimum of Months | 0.440737E+09 | 0.704214E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11065185.56 |
Maximum of Months | 0.489771E+09 | 0.782643E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82228248.25 | 0.534808E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.178779E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 399.25 | 0.296288E+09 |
February | 0.339028E+09 | 0.161422E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 959618.62 | 0.205297E+09 |
March | 0.376747E+09 | 0.179330E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3493787.93 | 0.128233E+09 |
April | 0.363528E+09 | 0.172718E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11885796.61 | 81501851.72 |
May | 0.375778E+09 | 0.179089E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23061452.23 | 41961267.74 |
June | 0.364321E+09 | 0.173510E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49218056.85 | 15363315.26 |
July | 0.374985E+09 | 0.178297E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60000096.01 | 7899086.27 |
August | 0.376571E+09 | 0.179399E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60723124.06 | 2108957.76 |
September | 0.363352E+09 | 0.172787E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26085856.34 | 24107291.00 |
October | 0.375161E+09 | 0.178711E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6532142.55 | 99805061.77 |
November | 0.362735E+09 | 0.173372E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 757504.96 | 0.151791E+09 |
December | 0.374985E+09 | 0.178297E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 107348.20 | 0.228395E+09 |
Annual Sum or Average | 0.442217E+10 | 0.210571E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242825E+09 | 0.128275E+10 |
Minimum of Months | 0.339028E+09 | 0.161422E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 399.25 | 2108957.76 |
Maximum of Months | 0.376747E+09 | 0.179399E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60723124.06 | 0.296288E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.332743E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823572E+09 |
February | 0.139600E+10 | 0.300437E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 167679.47 | 0.591597E+09 |
March | 0.155131E+10 | 0.333769E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 1991647.28 | 0.408143E+09 |
April | 0.149688E+10 | 0.321462E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 10361529.41 | 0.269831E+09 |
May | 0.154732E+10 | 0.333320E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 28638431.64 | 0.152692E+09 |
June | 0.150015E+10 | 0.322936E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 85949817.33 | 59646572.30 |
July | 0.154405E+10 | 0.331846E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.112278E+09 | 37071198.71 |
August | 0.155059E+10 | 0.333897E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.109140E+09 | 15104419.87 |
September | 0.149615E+10 | 0.321590E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 36587619.48 | 93147652.94 |
October | 0.154478E+10 | 0.332615E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 5399266.91 | 0.320175E+09 |
November | 0.149361E+10 | 0.322680E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 19730.67 | 0.465359E+09 |
December | 0.154405E+10 | 0.331846E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659764E+09 |
Annual Sum or Average | 0.182090E+11 | 0.391914E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.390534E+09 | 0.389610E+10 |
Minimum of Months | 0.139600E+10 | 0.300437E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15104419.87 |
Maximum of Months | 0.155131E+10 | 0.333897E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.112278E+09 | 0.823572E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.671083E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591.08 | 0.127022E+10 |
February | 0.236489E+11 | 0.600885E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2037818.77 | 0.893072E+09 |
March | 0.262800E+11 | 0.611283E+09 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10835964.51 | 0.581529E+09 |
April | 0.253579E+11 | 0.544135E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45939624.94 | 0.366707E+09 |
May | 0.262123E+11 | 0.524909E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103474E+09 | 0.189624E+09 |
June | 0.254132E+11 | 0.490495E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226823E+09 | 70038191.91 |
July | 0.261570E+11 | 0.514595E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273135E+09 | 34187963.26 |
August | 0.262677E+11 | 0.544154E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269659E+09 | 11184466.81 |
September | 0.253456E+11 | 0.579849E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114246E+09 | 0.107689E+09 |
October | 0.261693E+11 | 0.645664E+09 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23656440.47 | 0.452095E+09 |
November | 0.253025E+11 | 0.640617E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2694863.36 | 0.682095E+09 |
December | 0.261570E+11 | 0.669540E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 127966.88 | 0.996875E+09 |
Annual Sum or Average | 0.308468E+12 | 0.703721E+10 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107263E+10 | 0.565532E+10 |
Minimum of Months | 0.236489E+11 | 0.490495E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591.08 | 11184466.81 |
Maximum of Months | 0.262800E+11 | 0.671083E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273135E+09 | 0.127022E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.717810E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372310E+10 |
February | 0.702046E+11 | 0.647888E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5877035.47 | 0.264415E+10 |
March | 0.780153E+11 | 0.712003E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25806634.82 | 0.178529E+10 |
April | 0.752779E+11 | 0.680338E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110711E+09 | 0.117357E+10 |
May | 0.778146E+11 | 0.699843E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242003E+09 | 0.654893E+09 |
June | 0.754422E+11 | 0.675416E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550525E+09 | 0.268590E+09 |
July | 0.776503E+11 | 0.695624E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675423E+09 | 0.157609E+09 |
August | 0.779788E+11 | 0.703090E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656757E+09 | 64005676.15 |
September | 0.752414E+11 | 0.684987E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265716E+09 | 0.403593E+09 |
October | 0.776868E+11 | 0.714961E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57065692.27 | 0.142473E+10 |
November | 0.751137E+11 | 0.694498E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4360330.76 | 0.208328E+10 |
December | 0.776503E+11 | 0.715882E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 283332.69 | 0.296891E+10 |
Annual Sum or Average | 0.915726E+12 | 0.834234E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259453E+10 | 0.173517E+11 |
Minimum of Months | 0.702046E+11 | 0.647888E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64005676.15 |
Maximum of Months | 0.780153E+11 | 0.717810E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675423E+09 | 0.372310E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325701E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 418383.00 | 0.227643E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2778328.96 | 0.147051E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9462438.24 | 89869291.99 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22768813.90 | 40845789.33 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60101141.12 | 10751249.19 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77715698.00 | 4478864.67 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82364540.69 | 662818.21 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32129491.50 | 20439977.17 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5881580.45 | 0.109071E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 359892.76 | 0.171769E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14481.67 | 0.254082E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293995E+09 | 0.140236E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662818.21 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82364540.69 | 0.325701E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320948E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 345035.61 | 0.225104E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2307430.22 | 0.147822E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8664865.16 | 94839486.25 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21336527.01 | 47765026.79 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57644625.66 | 14252148.34 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75034121.91 | 7713038.41 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79405779.76 | 2059221.09 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29790904.31 | 24627567.03 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5068136.89 | 0.111218E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 258566.86 | 0.169189E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17010.77 | 0.249046E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279873E+09 | 0.141458E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2059221.09 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79405779.76 | 0.320948E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101316E+09 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81018764.01 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21168.83 | 65664793.21 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 191048.60 | 46854370.44 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1069518.76 | 30637034.92 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5544812.33 | 14990278.49 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7859323.03 | 11367806.50 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7082315.28 | 8100268.89 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1555661.23 | 21826968.62 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 116281.09 | 54176976.87 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73040605.08 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94581858.32 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23440129.15 | 0.603576E+09 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8100268.89 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7859323.03 | 0.101316E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91264593.44 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 145611.45 | 63862502.83 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 734510.74 | 40951976.13 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2658844.39 | 25996655.42 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6162884.19 | 12807710.93 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16291213.12 | 3674197.75 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21146129.92 | 1947979.75 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22442435.46 | 431323.21 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8577761.85 | 6679051.45 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1602894.94 | 30856842.95 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95227.73 | 47698248.46 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13570.46 | 70977777.01 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79871084.27 | 0.397149E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431323.21 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22442435.46 | 91264593.44 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326311E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 416733.53 | 0.228597E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2804310.79 | 0.148357E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9463520.66 | 90993554.83 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22673230.96 | 41394508.39 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59986790.14 | 10980023.86 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77570910.48 | 4552316.82 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82236352.01 | 693139.34 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32084173.29 | 20664062.52 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5883818.18 | 0.109822E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 373828.15 | 0.172541E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14458.41 | 0.254687E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293508E+09 | 0.140959E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693139.34 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82236352.01 | 0.326311E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321383E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 319211.62 | 0.225647E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2397815.17 | 0.147969E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8579640.96 | 95233914.09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21166619.49 | 48453209.86 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57207286.65 | 15277670.30 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74517649.04 | 8737340.21 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79079767.25 | 2601044.42 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29560710.51 | 25239463.70 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5047161.62 | 0.111405E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 358758.67 | 0.168846E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38337.32 | 0.249387E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278273E+09 | 0.142018E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2601044.42 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79079767.25 | 0.321383E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.122781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.42 | 0.396386E+09 |
February | 0.348285E+10 | 0.110860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873222.20 | 0.277214E+09 |
March | 0.387034E+10 | 0.123160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3572702.63 | 0.181671E+09 |
April | 0.373454E+10 | 0.118618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12157174.68 | 0.120394E+09 |
May | 0.386038E+10 | 0.122994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25565943.79 | 65084430.11 |
June | 0.374269E+10 | 0.119162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58910667.86 | 25182518.03 |
July | 0.385223E+10 | 0.122450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72369149.31 | 14712177.66 |
August | 0.386853E+10 | 0.123207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72106838.64 | 4863025.42 |
September | 0.373273E+10 | 0.118666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29285422.63 | 38176641.51 |
October | 0.385404E+10 | 0.122734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6861385.57 | 0.142413E+09 |
November | 0.372639E+10 | 0.119068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833638.62 | 0.207892E+09 |
December | 0.385223E+10 | 0.122450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99811.06 | 0.306603E+09 |
Annual Sum or Average | 0.454292E+11 | 0.144615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282636E+09 | 0.178059E+10 |
Minimum of Months | 0.348285E+10 | 0.110860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.42 | 4863025.42 |
Maximum of Months | 0.387034E+10 | 0.123207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72369149.31 | 0.396386E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324238E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 397441.47 | 0.226638E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2700956.68 | 0.146831E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9212450.65 | 90107678.79 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22309601.67 | 41266519.62 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59350510.36 | 10948764.76 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76828877.04 | 4563476.81 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81368793.03 | 671323.63 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31518060.19 | 20521242.30 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5719699.30 | 0.108905E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 334137.48 | 0.171298E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13128.85 | 0.252584E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289754E+09 | 0.139857E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671323.63 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81368793.03 | 0.324238E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320128E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 340213.38 | 0.224482E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2228344.99 | 0.147390E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8383714.91 | 95437314.66 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20918936.45 | 48336850.42 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56986305.31 | 14212395.73 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74275796.04 | 7508329.77 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78586858.07 | 1878424.79 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29267037.61 | 24347956.31 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4912474.52 | 0.110677E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 266348.49 | 0.168181E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22135.98 | 0.247448E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276188E+09 | 0.141003E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1878424.79 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78586858.07 | 0.320128E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170674E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 198574.45 | 0.119316E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1379559.28 | 76582892.91 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4711565.48 | 46537237.05 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11444900.07 | 21140874.51 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30413549.28 | 5606316.87 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39347495.21 | 2340410.55 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41633485.28 | 350320.12 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16097982.63 | 10621268.93 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2892131.55 | 56884656.71 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 162927.40 | 90159786.79 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6540.95 | 0.133517E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148289E+09 | 0.733731E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350320.12 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41633485.28 | 0.170674E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.140228E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840389E+09 |
February | 0.415303E+11 | 0.126055E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1705169.43 | 0.596680E+09 |
March | 0.461508E+11 | 0.133538E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6201780.72 | 0.399996E+09 |
April | 0.445315E+11 | 0.123381E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24892419.02 | 0.265312E+09 |
May | 0.460320E+11 | 0.122894E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53891471.76 | 0.148171E+09 |
June | 0.446286E+11 | 0.116874E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126311E+09 | 58781936.44 |
July | 0.459349E+11 | 0.121522E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156219E+09 | 33207504.25 |
August | 0.461292E+11 | 0.125445E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156336E+09 | 12309782.78 |
September | 0.445099E+11 | 0.127123E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66293398.61 | 85739724.45 |
October | 0.459565E+11 | 0.138011E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15514862.08 | 0.310270E+09 |
November | 0.444343E+11 | 0.134522E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1289480.55 | 0.456872E+09 |
December | 0.459349E+11 | 0.139800E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161014.14 | 0.662114E+09 |
Annual Sum or Average | 0.541708E+12 | 0.154939E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608815E+09 | 0.386984E+10 |
Minimum of Months | 0.415303E+11 | 0.116874E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12309782.78 |
Maximum of Months | 0.461508E+11 | 0.140228E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156336E+09 | 0.840389E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.140228E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854875E+09 |
February | 0.415303E+11 | 0.126055E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1358873.83 | 0.609792E+09 |
March | 0.461508E+11 | 0.133538E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5256844.84 | 0.413304E+09 |
April | 0.445315E+11 | 0.123381E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22237262.39 | 0.274452E+09 |
May | 0.460320E+11 | 0.122894E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49627462.03 | 0.154606E+09 |
June | 0.446286E+11 | 0.116874E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120192E+09 | 62494132.90 |
July | 0.459349E+11 | 0.121522E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149765E+09 | 36605317.24 |
August | 0.461292E+11 | 0.125445E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148772E+09 | 14484251.17 |
September | 0.445099E+11 | 0.127123E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61527767.84 | 91006334.93 |
October | 0.459565E+11 | 0.138011E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13783445.22 | 0.321099E+09 |
November | 0.444343E+11 | 0.134522E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 891860.92 | 0.471197E+09 |
December | 0.459349E+11 | 0.139800E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99155.96 | 0.677915E+09 |
Annual Sum or Average | 0.541708E+12 | 0.154939E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573511E+09 | 0.398183E+10 |
Minimum of Months | 0.415303E+11 | 0.116874E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14484251.17 |
Maximum of Months | 0.461508E+11 | 0.140228E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149765E+09 | 0.854875E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.822206E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842912E+09 |
February | 0.369574E+10 | 0.742377E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 134326.15 | 0.606123E+09 |
March | 0.410691E+10 | 0.824741E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1809917.74 | 0.419411E+09 |
April | 0.396281E+10 | 0.794330E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9364685.03 | 0.278031E+09 |
May | 0.409635E+10 | 0.823632E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27994446.34 | 0.158297E+09 |
June | 0.397146E+10 | 0.797973E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 85681359.90 | 62520723.17 |
July | 0.408770E+10 | 0.819989E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.112289E+09 | 39293714.21 |
August | 0.410499E+10 | 0.825057E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.108746E+09 | 16554951.06 |
September | 0.396089E+10 | 0.794646E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 35868496.40 | 97242926.57 |
October | 0.408962E+10 | 0.821890E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5233619.31 | 0.329642E+09 |
November | 0.395417E+10 | 0.797339E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 12474.54 | 0.477721E+09 |
December | 0.408770E+10 | 0.819989E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675965E+09 |
Annual Sum or Average | 0.482060E+11 | 0.968417E+10 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.387133E+09 | 0.400371E+10 |
Minimum of Months | 0.369574E+10 | 0.742377E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16554951.06 |
Maximum of Months | 0.410691E+10 | 0.825057E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.112289E+09 | 0.842912E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.129945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708383E+09 |
February | 0.368610E+10 | 0.117329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426464.09 | 0.507983E+09 |
March | 0.409620E+10 | 0.130346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2337523.40 | 0.360463E+09 |
April | 0.395248E+10 | 0.125539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10617847.13 | 0.251359E+09 |
May | 0.408566E+10 | 0.130170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27580239.53 | 0.150631E+09 |
June | 0.396110E+10 | 0.126115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83824446.90 | 60658503.68 |
July | 0.407704E+10 | 0.129595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109702E+09 | 38281000.72 |
August | 0.409429E+10 | 0.130396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106211E+09 | 16265163.94 |
September | 0.395056E+10 | 0.125589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35219510.54 | 91945106.80 |
October | 0.407896E+10 | 0.129895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5231777.21 | 0.291085E+09 |
November | 0.394385E+10 | 0.126015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236845.08 | 0.399932E+09 |
December | 0.407704E+10 | 0.129595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556259E+09 |
Annual Sum or Average | 0.480803E+11 | 0.153053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381388E+09 | 0.343325E+10 |
Minimum of Months | 0.368610E+10 | 0.117329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16265163.94 |
Maximum of Months | 0.409620E+10 | 0.130396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109702E+09 | 0.708383E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 8012.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 8012.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 8012.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 8012.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 8012.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 8012.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 8012.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 8012.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 8012.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 8012.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 8012.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 8012.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 8012.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 8012.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 362.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 354.83 | 27-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 362.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 28-FEB-14:40 | 445.28 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 362.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.41 | 30-MAR-14:20 | 246.23 | 19-MAR-06:53 |
April | 1169.53 | 01-APR-00:10 | 362.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.24 | 12-APR-14:00 | 259.87 | 06-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 362.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 | 19-MAY-14:00 | 165.07 | 11-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 362.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 | 06-JUN-15:00 | 134.37 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 362.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.14 | 08-JUL-15:00 | 69.55 | 28-JUL-23:00 |
August | 1169.53 | 01-AUG-00:10 | 362.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.79 | 02-AUG-16:00 | 59.87 | 25-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 362.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.81 | 07-SEP-16:00 | 124.18 | 14-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 362.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.53 | 10-OCT-16:00 | 230.87 | 26-OCT-06:55 |
November | 1169.53 | 01-NOV-00:10 | 362.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 | 19-NOV-15:40 | 303.44 | 22-NOV-06:30 |
December | 1169.53 | 01-DEC-00:10 | 362.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 338.31 | 18-DEC-07:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 362.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.87 | |||||
Maximum of Months | 1169.53 | 362.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 138.14 | 445.28 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 419.88 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 137.30 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 419.88 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 26-FEB-15:00 | 171.87 | 12-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 419.88 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 | 30-MAR-14:00 | 98.20 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 419.88 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 | 12-APR-14:00 | 104.70 | 06-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 419.88 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.05 | 30-MAY-14:00 | 68.62 | 11-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 419.88 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 06-JUN-15:00 | 54.65 | 10-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 419.88 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 08-JUL-16:00 | 27.74 | 28-JUL-23:00 |
August | 1354.32 | 01-AUG-00:10 | 419.88 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 01-AUG-15:00 | 23.65 | 25-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 419.88 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.94 | 07-SEP-15:00 | 50.33 | 14-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 419.88 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.08 | 10-OCT-16:00 | 93.81 | 26-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 419.88 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 | 19-NOV-15:00 | 119.30 | 22-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 419.88 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 12-DEC-14:00 | 130.58 | 18-DEC-07:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | |||||
Maximum of Months | 1354.32 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 171.87 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 751.24 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 325.62 | 27-JAN-07:52 |
February | 286.42 | 01-FEB-00:10 | 751.24 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 26-FEB-15:00 | 406.18 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 751.24 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 | 30-MAR-14:00 | 241.94 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 751.24 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 12-APR-14:00 | 260.61 | 06-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 751.24 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.91 | 19-MAY-14:00 | 177.34 | 11-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 751.24 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.77 | 06-JUN-15:00 | 139.63 | 10-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 751.24 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.02 | 08-JUL-15:00 | 72.47 | 28-JUL-23:20 |
August | 286.42 | 01-AUG-00:10 | 751.24 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.19 | 02-AUG-16:00 | 59.97 | 25-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 751.24 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.37 | 07-SEP-16:00 | 132.78 | 29-SEP-04:00 |
October | 286.42 | 01-OCT-23:10 | 751.24 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.68 | 10-OCT-16:00 | 236.16 | 26-OCT-06:55 |
November | 286.42 | 01-NOV-00:10 | 751.24 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 19-NOV-15:00 | 291.53 | 22-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 751.24 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 318.02 | 18-DEC-07:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.97 | |||||
Maximum of Months | 286.42 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 126.02 | 406.18 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 172.20 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 31-JAN-15:00 | 186.76 | 27-JAN-07:52 |
February | 220.32 | 01-FEB-00:10 | 172.20 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.52 | 26-FEB-15:00 | 234.35 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 172.20 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 30-MAR-16:00 | 129.60 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 172.20 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.60 | 12-APR-14:00 | 136.77 | 06-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 172.20 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.74 | 19-MAY-16:40 | 86.00 | 11-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 172.20 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.98 | 06-JUN-15:00 | 68.27 | 10-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 172.20 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.07 | 08-JUL-16:00 | 31.94 | 28-JUL-23:00 |
August | 220.32 | 01-AUG-00:10 | 172.20 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.95 | 01-AUG-16:50 | 26.83 | 25-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 172.20 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.79 | 07-SEP-16:00 | 63.41 | 29-SEP-04:00 |
October | 220.32 | 01-OCT-23:10 | 172.20 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.11 | 10-OCT-16:00 | 121.51 | 26-OCT-06:55 |
November | 220.32 | 01-NOV-00:10 | 172.20 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 | 19-NOV-15:00 | 159.70 | 22-NOV-06:30 |
December | 220.32 | 01-DEC-00:10 | 172.20 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 | 12-DEC-14:00 | 178.06 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 172.20 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 26.83 | |||||
Maximum of Months | 220.32 | 172.20 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 79.07 | 234.35 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 320.50 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 489.84 | 27-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 320.50 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 14.03 | 28-FEB-14:30 | 603.84 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 320.50 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 52.85 | 30-MAR-14:20 | 352.94 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 320.50 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 68.81 | 12-APR-14:00 | 369.94 | 06-APR-05:00 |
May | 907.20 | 01-MAY-00:10 | 320.50 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 91.37 | 19-MAY-14:00 | 242.15 | 11-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 320.50 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 140.33 | 06-JUN-15:00 | 190.66 | 10-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 320.50 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 172.08 | 08-JUL-15:00 | 98.95 | 28-JUL-23:20 |
August | 907.20 | 01-AUG-00:10 | 320.50 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 150.46 | 02-AUG-16:00 | 81.88 | 25-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 320.50 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 105.65 | 07-SEP-16:00 | 181.30 | 29-SEP-04:00 |
October | 907.20 | 01-OCT-23:10 | 320.50 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 82.87 | 10-OCT-16:00 | 333.44 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 320.50 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 5.60 | 05-NOV-16:00 | 424.58 | 22-NOV-06:00 |
December | 907.20 | 01-DEC-00:10 | 320.50 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 468.93 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 | ||||||
Maximum of Months | 907.20 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 172.08 | 603.84 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 858.63 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 31-JAN-15:00 | 789.54 | 14-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 858.63 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 28-FEB-14:40 | 984.45 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 858.63 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.40 | 30-MAR-14:00 | 545.93 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 858.63 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.10 | 17-APR-16:00 | 594.70 | 06-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 858.63 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.72 | 19-MAY-17:00 | 370.66 | 11-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 858.63 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.81 | 06-JUN-15:00 | 302.59 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 858.63 | 03-JUL-19:49 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.13 | 08-JUL-16:00 | 147.77 | 28-JUL-23:00 |
August | 15368.40 | 01-AUG-00:10 | 858.63 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.38 | 01-AUG-17:00 | 112.91 | 25-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 858.63 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.20 | 07-SEP-12:00 | 280.12 | 29-SEP-04:00 |
October | 15368.40 | 01-OCT-23:10 | 858.63 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.92 | 10-OCT-16:00 | 536.26 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 858.63 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.66 | 19-NOV-15:40 | 685.09 | 22-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 858.63 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 12-DEC-15:00 | 747.88 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 858.63 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 112.91 | |||||
Maximum of Months | 15368.40 | 858.63 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 354.13 | 984.45 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 7223.65 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2325.16 | 14-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 7223.65 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.84 | 28-FEB-14:20 | 2830.61 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 7223.65 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.04 | 30-MAR-14:00 | 1653.29 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 7223.65 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 471.22 | 12-APR-14:00 | 1779.45 | 06-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 7223.65 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.71 | 30-MAY-14:00 | 1150.69 | 11-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 7223.65 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 809.63 | 06-JUN-15:00 | 930.38 | 10-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 7223.65 | 03-JUL-19:49 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 966.19 | 08-JUL-16:00 | 489.40 | 28-JUL-23:00 |
August | 45622.98 | 01-AUG-00:10 | 7223.65 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 848.17 | 01-AUG-15:00 | 400.84 | 25-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 7223.65 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 607.04 | 07-SEP-15:00 | 872.60 | 29-SEP-04:00 |
October | 45622.98 | 01-OCT-23:10 | 7223.65 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 493.91 | 10-OCT-16:00 | 1604.19 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 7223.65 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.48 | 19-NOV-15:00 | 2033.82 | 22-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 7223.65 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.01 | 12-DEC-15:00 | 2184.72 | 18-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 7223.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.84 | |||||
Maximum of Months | 45622.98 | 7223.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 966.19 | 2830.61 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.05 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 26-FEB-16:20 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 143.22 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 17-APR-15:20 | 151.94 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.90 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.25 | 06-JUN-15:20 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 08-JUL-15:20 | 33.69 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 23.25 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.94 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.06 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.21 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 12-DEC-16:17 | 196.67 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.04 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 26-FEB-16:20 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 143.21 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 17-APR-15:20 | 151.92 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.24 | 06-JUN-15:20 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 08-JUL-15:20 | 35.54 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 28.23 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.05 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 12-DEC-14:00 | 196.66 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.23 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 259.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 65.07 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 71.43 | 12-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 30-MAR-14:10 | 49.93 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 12-APR-14:00 | 50.85 | 06-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 19-MAY-14:00 | 36.75 | 11-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 | 06-JUN-15:00 | 29.91 | 10-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 08-JUL-15:00 | 17.99 | 28-JUL-23:30 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 02-AUG-16:00 | 15.70 | 25-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 07-SEP-16:00 | 27.94 | 29-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 | 10-OCT-16:00 | 48.31 | 26-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 57.94 | 22-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 64.32 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 71.43 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 57.79 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28-FEB-14:00 | 72.45 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 30-MAR-15:40 | 40.66 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 17-APR-15:20 | 42.40 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 19-MAY-16:00 | 25.96 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 06-JUN-15:20 | 19.32 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 08-JUL-15:20 | 10.63 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 | 02-AUG-16:00 | 7.61 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.82 | 07-SEP-16:00 | 18.12 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 10-OCT-16:00 | 38.56 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-NOV-16:00 | 49.46 | 22-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 12-DEC-14:00 | 55.18 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 72.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.05 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 26-FEB-16:18 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-15:50 | 143.69 | 19-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 17-APR-15:20 | 151.93 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.25 | 06-JUN-15:20 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 | 08-JUL-15:20 | 33.54 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 24.02 | 25-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 65.51 | 14-SEP-07:10 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.06 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.21 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 12-DEC-16:17 | 196.68 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.04 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 26-FEB-16:18 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 143.35 | 19-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 17-APR-15:20 | 151.92 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.24 | 06-JUN-15:20 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 08-JUL-15:20 | 35.07 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 28.69 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 65.71 | 14-SEP-07:10 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.05 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 12-DEC-14:00 | 196.66 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 259.58 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1182.64 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 31-JAN-15:00 | 249.42 | 27-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1182.64 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.25 | 26-FEB-15:00 | 312.90 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1182.64 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 30-MAR-14:00 | 174.87 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1182.64 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.49 | 12-APR-14:00 | 188.10 | 06-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1182.64 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 | 30-MAY-14:00 | 122.48 | 11-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1182.64 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.22 | 06-JUN-15:00 | 97.60 | 10-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1182.64 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.56 | 08-JUL-16:00 | 48.31 | 28-JUL-23:00 |
August | 2263.36 | 01-AUG-00:10 | 1182.64 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.14 | 01-AUG-17:00 | 39.86 | 25-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1182.64 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.02 | 07-SEP-16:00 | 90.28 | 29-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1182.64 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.36 | 10-OCT-16:00 | 165.72 | 26-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1182.64 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 19-NOV-15:00 | 213.33 | 22-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1182.64 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 | 12-DEC-15:00 | 237.82 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1182.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 39.86 | ||||
Maximum of Months | 2263.36 | 1182.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.56 | 312.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.54 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 26-FEB-16:20 | 260.11 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 143.68 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 17-APR-15:20 | 152.40 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.44 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.89 | 06-JUN-15:20 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.66 | 08-JUL-16:00 | 31.44 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.86 | 02-AUG-16:00 | 22.24 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.36 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 10-OCT-16:00 | 135.51 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.68 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 12-DEC-16:17 | 197.16 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.24 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 97.66 | 260.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207.52 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 26-FEB-16:20 | 260.10 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 143.67 | 19-MAR-06:50 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 17-APR-15:20 | 152.38 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.44 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 | 06-JUN-15:20 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.64 | 08-JUL-16:00 | 34.69 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.86 | 02-AUG-16:00 | 26.19 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.35 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 10-OCT-16:00 | 135.51 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.67 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 | 12-DEC-14:00 | 197.14 | 18-DEC-07:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.19 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 97.64 | 260.10 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 106.18 | 27-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 | 26-FEB-16:20 | 133.08 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 30-MAR-16:00 | 73.52 | 19-MAR-06:53 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 | 17-APR-15:20 | 77.97 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 | 19-MAY-16:00 | 47.81 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 | 06-JUN-15:20 | 35.64 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 08-JUL-15:20 | 16.88 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 02-AUG-16:00 | 11.73 | 25-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 | 07-SEP-16:00 | 33.44 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.92 | 10-OCT-16:00 | 69.33 | 26-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 05-NOV-16:00 | 90.91 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 12-DEC-16:19 | 100.89 | 18-DEC-07:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 133.08 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1507.83 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 525.01 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 1507.83 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 26-FEB-15:00 | 644.48 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 1507.83 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.22 | 30-MAR-14:00 | 376.34 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 1507.83 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.52 | 12-APR-14:00 | 400.52 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 1507.83 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.61 | 19-MAY-14:00 | 261.30 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 1507.83 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.04 | 06-JUN-15:00 | 208.21 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 1507.83 | 03-JUL-19:49 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.57 | 08-JUL-16:00 | 114.20 | 28-JUL-23:00 |
August | 26988.77 | 01-AUG-00:10 | 1507.83 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.78 | 01-AUG-15:00 | 87.52 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 1507.83 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.71 | 07-SEP-12:00 | 195.16 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 1507.83 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.84 | 10-OCT-16:00 | 357.72 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 1507.83 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.21 | 19-NOV-15:00 | 455.39 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 1507.83 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 12-DEC-15:00 | 490.35 | 18-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1507.83 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.52 | |||||
Maximum of Months | 26988.77 | 1507.83 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 220.57 | 644.48 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1507.83 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 530.61 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 1507.83 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.81 | 28-FEB-14:00 | 650.76 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 1507.83 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.63 | 30-MAR-14:00 | 382.38 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 1507.83 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.99 | 12-APR-14:00 | 404.98 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 1507.83 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 | 19-MAY-14:00 | 265.38 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 1507.83 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.84 | 06-JUN-15:00 | 211.58 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 1507.83 | 03-JUL-19:49 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.90 | 08-JUL-16:00 | 114.20 | 28-JUL-23:00 |
August | 26988.77 | 01-AUG-00:10 | 1507.83 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.50 | 01-AUG-15:00 | 91.13 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 1507.83 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.25 | 07-SEP-12:00 | 198.55 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 1507.83 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.51 | 10-OCT-16:00 | 362.66 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 1507.83 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 | 19-NOV-15:00 | 460.86 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 1507.83 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 | 12-DEC-15:00 | 495.85 | 18-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1507.83 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.13 | |||||
Maximum of Months | 26988.77 | 1507.83 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 215.90 | 650.76 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 791.95 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 500.65 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 791.95 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 12.96 | 28-FEB-14:50 | 616.75 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 791.95 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 52.39 | 30-MAR-15:16 | 361.08 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 791.95 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 73.25 | 17-APR-16:00 | 378.41 | 06-APR-05:00 |
May | 2401.70 | 01-MAY-00:10 | 791.95 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 91.80 | 19-MAY-15:50 | 248.12 | 11-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 791.95 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 141.70 | 06-JUN-15:00 | 195.70 | 10-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 791.95 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 174.05 | 08-JUL-15:00 | 102.27 | 28-JUL-23:40 |
August | 2401.70 | 01-AUG-00:10 | 791.95 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 152.07 | 02-AUG-16:00 | 84.80 | 25-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 791.95 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 106.41 | 07-SEP-16:00 | 186.18 | 29-SEP-04:00 |
October | 2401.70 | 01-OCT-23:10 | 791.95 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 83.20 | 10-OCT-16:00 | 341.18 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 791.95 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 4.45 | 05-NOV-16:00 | 434.09 | 22-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 791.95 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 479.31 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 791.95 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 84.80 | ||||||
Maximum of Months | 2401.70 | 791.95 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 174.05 | 616.75 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1251.64 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 442.35 | 27-JAN-07:52 |
February | 2395.44 | 01-FEB-00:10 | 1251.64 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.45 | 26-FEB-15:00 | 554.72 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1251.64 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.25 | 30-MAR-14:20 | 308.65 | 19-MAR-06:53 |
April | 2395.44 | 01-APR-00:10 | 1251.64 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 | 12-APR-14:00 | 338.73 | 06-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1251.64 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 19-MAY-14:00 | 228.63 | 11-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1251.64 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.54 | 06-JUN-15:00 | 185.71 | 10-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1251.64 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 08-JUL-15:00 | 100.14 | 28-JUL-23:20 |
August | 2395.44 | 01-AUG-00:10 | 1251.64 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 | 02-AUG-16:00 | 83.10 | 25-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1251.64 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.94 | 07-SEP-16:00 | 172.21 | 29-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1251.64 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 | 10-OCT-16:00 | 297.12 | 26-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1251.64 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 19-NOV-15:00 | 378.45 | 22-NOV-06:30 |
December | 2395.44 | 01-DEC-00:10 | 1251.64 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 421.82 | 18-DEC-07:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1251.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.10 | ||||
Maximum of Months | 2395.44 | 1251.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 554.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12480.23 | 31-JAN-21:00 | 8945.92 | 8012.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12021.97 | 01-FEB-21:00 | 8945.92 | 8012.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11745.27 | 30-MAR-18:10 | 62621.41 | 49853.94 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12262.37 | 14-APR-18:01 | 62621.41 | 49853.94 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12876.55 | 15-MAY-18:04 | 62621.41 | 49853.94 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13605.35 | 10-JUN-18:10 | 53675.50 | 43622.31 | 56781.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14472.14 | 20-JUL-18:10 | 53675.50 | 42731.95 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15325.00 | 27-AUG-10:35 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17523.05 | 28-SEP-21:00 | 10223.90 | 7121.99 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18656.88 | 12-OCT-21:00 | 10223.90 | 7121.99 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18770.21 | 08-NOV-22:00 | 10223.90 | 7121.99 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16660.36 | 01-DEC-22:00 | 10223.90 | 7121.99 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11745.27 | 7667.93 | 5341.40 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18770.21 | 62621.41 | 49853.94 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1534.60 | 29-JAN-13:00 | 389.84 | 120.86 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.63 |
February | 1921.80 | 21-FEB-14:25 | 519.79 | 201.44 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
March | 1973.88 | 30-MAR-14:05 | 779.69 | 201.44 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 0.00 |
April | 1971.88 | 15-APR-13:40 | 389.84 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 38.48 | 0.00 |
May | 1831.57 | 19-MAY-18:20 | 1819.27 | 644.61 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 | 0.00 |
June | 2079.47 | 13-JUN-18:03 | 5457.82 | 1933.82 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 87.44 | 0.00 |
July | 2375.18 | 07-JUL-18:20 | 1819.27 | 644.61 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 0.00 |
August | 2563.52 | 19-AUG-13:40 | 389.84 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 0.00 |
September | 2583.88 | 24-SEP-12:00 | 389.84 | 120.86 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 | 0.00 |
October | 2692.86 | 10-OCT-13:30 | 259.90 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 0.00 |
November | 2083.07 | 08-NOV-13:40 | 259.90 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.78 |
December | 1858.14 | 10-DEC-13:00 | 389.84 | 120.86 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1534.60 | 259.90 | 100.72 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2692.86 | 5457.82 | 1933.82 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 120.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1261.35 | 31-JAN-21:00 | 1053.36 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 |
February | 1396.75 | 28-FEB-21:00 | 1053.36 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 |
March | 1520.02 | 30-MAR-18:10 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 0.00 |
April | 1636.46 | 12-APR-15:14 | 5266.80 | 816.44 | 2047.51 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 | 0.00 |
May | 1610.53 | 15-MAY-18:04 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 0.00 |
June | 1675.24 | 27-JUN-21:00 | 1203.84 | 373.23 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 0.00 |
July | 1857.45 | 07-JUL-21:00 | 1203.84 | 373.23 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 0.00 |
August | 1902.52 | 18-AUG-21:00 | 1203.84 | 373.23 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 0.00 |
September | 1761.97 | 08-SEP-21:00 | 1203.84 | 373.23 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 | 0.00 |
October | 1551.09 | 11-OCT-18:10 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 |
November | 1383.66 | 06-NOV-21:00 | 1053.36 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.46 |
December | 1355.36 | 12-DEC-21:00 | 1053.36 | 419.88 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1261.35 | 1053.36 | 373.23 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1902.52 | 7373.52 | 2612.60 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 49.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24.65 | 20-JAN-21:00 | 222.77 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 |
February | 621.61 | 28-FEB-22:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 |
March | 1034.02 | 30-MAR-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
April | 1055.14 | 19-APR-20:00 | 222.77 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 |
May | 1330.32 | 19-MAY-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
June | 1642.78 | 13-JUN-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 0.00 |
July | 1842.81 | 07-JUL-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 66.67 | 0.00 |
August | 1812.61 | 18-AUG-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 71.60 | 0.00 |
September | 1620.55 | 07-SEP-20:00 | 222.77 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.65 | 0.00 |
October | 1211.44 | 18-OCT-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
November | 779.29 | 03-NOV-21:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.44 |
December | 567.49 | 13-DEC-22:00 | 254.59 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24.65 | 222.77 | 667.77 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1842.81 | 254.59 | 751.24 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 71.60 | 118.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 663.73 | 31-JAN-21:00 | 171.36 | 172.20 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 |
February | 735.40 | 28-FEB-19:00 | 122.40 | 114.80 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 0.00 |
March | 840.68 | 30-MAR-18:10 | 1199.52 | 1071.47 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 | 0.00 |
April | 944.31 | 12-APR-15:14 | 856.80 | 334.83 | 624.51 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 0.00 |
May | 926.48 | 20-MAY-10:35 | 146.88 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 0.00 |
June | 990.11 | 25-JUN-10:35 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 42.27 | 0.00 |
July | 1032.45 | 08-JUL-10:35 | 146.88 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 60.05 | 0.00 |
August | 1025.75 | 19-AUG-10:35 | 146.88 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 53.29 | 0.00 |
September | 979.51 | 09-SEP-10:35 | 146.88 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 43.81 | 0.00 |
October | 865.89 | 11-OCT-10:35 | 97.92 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 0.00 |
November | 779.64 | 05-NOV-10:35 | 146.88 | 114.80 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 |
December | 739.68 | 13-DEC-11:35 | 97.92 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 663.73 | 97.92 | 95.67 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1032.45 | 1199.52 | 1071.47 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 60.05 | 24.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37348.67 | 31-JAN-21:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.23 |
February | 37857.47 | 28-FEB-21:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 |
March | 38286.63 | 30-MAR-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
April | 38433.35 | 17-APR-20:00 | 1411.20 | 641.00 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 |
May | 38791.39 | 19-MAY-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.46 | 0.00 |
June | 39160.82 | 13-JUN-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 74.92 | 0.00 |
July | 39384.68 | 07-JUL-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 97.76 | 0.00 |
August | 39296.25 | 18-AUG-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 105.80 | 0.00 |
September | 39033.05 | 07-SEP-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.59 | 0.00 |
October | 38404.22 | 10-OCT-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
November | 37771.63 | 03-NOV-20:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.70 |
December | 37606.05 | 12-DEC-21:00 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 82.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37348.67 | 705.60 | 320.50 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39384.68 | 1411.20 | 641.00 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 105.80 | 99.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9824.69 | 29-JAN-11:35 | 10245.60 | 125.93 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.01 |
February | 10219.68 | 26-FEB-11:35 | 10245.60 | 125.93 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
March | 10901.99 | 30-MAR-15:11 | 59766.00 | 367.30 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 122.09 | 0.00 |
April | 12260.34 | 12-APR-15:14 | 59766.00 | 367.30 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 139.73 | 0.00 |
May | 10949.37 | 13-MAY-17:25 | 40982.40 | 503.73 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 99.58 | 0.00 |
June | 10812.21 | 12-JUN-18:10 | 71719.20 | 1007.46 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 229.03 | 0.00 |
July | 11306.69 | 08-JUL-17:30 | 10245.60 | 125.93 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 290.38 | 0.00 |
August | 11343.05 | 02-AUG-18:10 | 71719.20 | 1007.46 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 250.93 | 0.00 |
September | 11557.45 | 22-SEP-16:52 | 51228.00 | 314.83 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 92.97 | 0.00 |
October | 10869.32 | 10-OCT-15:40 | 8538.00 | 52.47 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 156.57 | 0.00 |
November | 10632.84 | 11-NOV-11:35 | 10245.60 | 125.93 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.74 |
December | 10172.43 | 10-DEC-11:35 | 10245.60 | 125.93 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9824.69 | 8538.00 | 52.47 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12260.34 | 71719.20 | 1007.46 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 290.38 | 262.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27860.82 | 31-JAN-21:00 | 35484.54 | 7223.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.89 |
February | 29708.74 | 28-FEB-21:00 | 35484.54 | 7223.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.72 |
March | 32316.67 | 30-MAR-21:10 | 136868.94 | 14447.30 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 |
April | 34201.93 | 12-APR-15:14 | 177422.70 | 12079.54 | 25864.80 | 0.00 | 0.00 | 0.00 | 0.00 | 401.74 | 0.00 |
May | 33344.19 | 15-MAY-18:04 | 248391.78 | 39952.54 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 356.74 | 0.00 |
June | 34917.14 | 13-JUN-22:00 | 45622.98 | 4815.77 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 226.98 | 0.00 |
July | 37109.41 | 07-JUL-21:10 | 45622.98 | 4815.77 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 448.08 | 0.00 |
August | 38012.95 | 18-AUG-21:10 | 45622.98 | 4815.77 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 476.60 | 0.00 |
September | 36164.83 | 07-SEP-21:10 | 45622.98 | 4815.77 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 99.48 | 0.00 |
October | 33057.75 | 10-OCT-21:53 | 319360.86 | 33710.36 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.77 |
November | 29553.06 | 06-NOV-21:00 | 35484.54 | 7223.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.96 |
December | 29314.88 | 12-DEC-21:00 | 35484.54 | 7223.65 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27860.82 | 35484.54 | 4815.77 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38012.95 | 319360.86 | 39952.54 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 476.60 | 829.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2858.81 | 28-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.68 |
February | 2948.28 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
March | 2948.06 | 13-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 0.00 |
April | 2948.93 | 09-APR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 |
May | 2935.68 | 09-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
June | 2627.03 | 19-JUN-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 58.59 | 0.00 |
July | 2625.33 | 02-JUL-15:12 | 324.00 | 187.54 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 51.88 | 0.00 |
August | 2660.48 | 30-AUG-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 0.00 |
September | 2651.81 | 05-SEP-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 43.09 | 0.00 |
October | 2774.55 | 31-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 |
November | 2940.85 | 08-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
December | 2893.53 | 10-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2625.33 | 324.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2948.93 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 58.59 | 71.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 857.80 | 12-JAN-16:14 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 |
February | 2655.81 | 24-FEB-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.24 |
March | 2893.59 | 13-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 | 0.00 |
April | 3013.48 | 26-APR-18:41 | 1247.40 | 758.59 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.54 |
May | 3026.26 | 09-MAY-20:41 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.03 |
June | 2615.12 | 05-JUN-21:51 | 1260.00 | 444.17 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 |
July | 2622.11 | 11-JUL-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 0.00 |
August | 2626.83 | 24-AUG-15:12 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 | 0.00 |
September | 2859.33 | 18-SEP-16:01 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 0.00 |
October | 2654.21 | 31-OCT-18:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.54 |
November | 2614.58 | 07-NOV-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.59 |
December | 2602.33 | 07-DEC-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 857.80 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3026.26 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 | 80.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 277.41 | 29-JAN-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 |
February | 337.58 | 26-FEB-14:15 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 |
March | 320.44 | 13-MAR-16:20 | 0.00 | 16.67 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
April | 291.37 | 15-APR-14:00 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 0.00 |
May | 259.47 | 19-MAY-20:20 | 0.00 | 52.98 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
June | 290.58 | 13-JUN-20:20 | 0.00 | 52.98 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
July | 319.92 | 08-JUL-17:30 | 0.00 | 50.60 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 0.00 |
August | 342.63 | 18-AUG-16:20 | 0.00 | 16.67 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 0.00 |
September | 392.98 | 24-SEP-12:40 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 0.00 |
October | 424.74 | 10-OCT-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
November | 388.36 | 15-NOV-14:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 |
December | 371.90 | 10-DEC-14:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 259.47 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 424.74 | 0.00 | 52.98 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 23.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 943.22 | 22-JAN-09:01 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
February | 1034.32 | 28-FEB-22:52 | 1080.00 | 239.36 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 |
March | 1031.39 | 31-MAR-20:12 | 961.20 | 317.95 | 1068.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 |
April | 1031.81 | 09-APR-20:11 | 1247.40 | 535.88 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 |
May | 1097.81 | 09-MAY-20:41 | 1441.80 | 476.93 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 |
June | 997.85 | 28-JUN-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 | 0.00 |
July | 997.03 | 19-JUL-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 |
August | 995.83 | 13-AUG-18:02 | 702.00 | 357.25 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 0.00 |
September | 995.62 | 23-SEP-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 | 0.00 |
October | 1035.64 | 11-OCT-21:52 | 1080.00 | 239.36 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 |
November | 989.82 | 28-NOV-19:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 |
December | 942.05 | 10-DEC-09:02 | 324.00 | 200.06 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 942.05 | 324.00 | 200.06 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1097.81 | 1441.80 | 535.88 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 39.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2541.03 | 29-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.26 |
February | 2692.15 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
March | 2695.62 | 13-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 0.00 |
April | 2692.13 | 09-APR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 |
May | 2670.50 | 09-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 |
June | 2462.78 | 06-JUN-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 0.00 |
July | 2452.21 | 07-JUL-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 | 0.00 |
August | 2443.36 | 11-AUG-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 55.25 | 0.00 |
September | 2441.69 | 07-SEP-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | 0.00 |
October | 2427.15 | 02-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 | 0.00 |
November | 2678.03 | 08-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
December | 2623.11 | 10-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2427.15 | 252.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2695.62 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 55.25 | 39.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1627.89 | 29-JAN-09:01 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.91 |
February | 2454.49 | 24-FEB-09:02 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.32 |
March | 2655.32 | 13-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 | 0.00 |
April | 2571.35 | 14-APR-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.90 |
May | 2686.78 | 09-MAY-20:41 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 |
June | 2718.70 | 04-JUN-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 |
July | 2515.58 | 25-JUL-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 |
August | 2598.62 | 26-AUG-08:51 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
September | 2608.26 | 15-SEP-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 |
October | 2362.72 | 09-OCT-18:01 | 819.00 | 662.94 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 | 0.00 |
November | 2284.27 | 06-NOV-09:01 | 252.00 | 291.69 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.08 |
December | 1512.47 | 10-DEC-09:02 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1512.47 | 216.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2718.70 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 | 110.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1418.71 | 31-JAN-19:00 | 1257.42 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 |
February | 1648.25 | 27-FEB-19:10 | 12322.72 | 7358.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 |
March | 1835.64 | 11-MAR-16:11 | 5281.16 | 2299.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.57 | 0.00 |
April | 2100.87 | 12-APR-15:14 | 8801.94 | 2299.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.85 | 0.00 |
May | 2044.14 | 15-MAY-18:04 | 12322.72 | 7358.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.99 | 0.00 |
June | 2130.23 | 25-JUN-10:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 | 0.00 |
July | 2207.85 | 08-JUL-10:35 | 1508.90 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.61 | 0.00 |
August | 2208.08 | 19-AUG-10:35 | 1508.90 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.09 | 0.00 |
September | 2112.00 | 09-SEP-10:35 | 1508.90 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.45 | 0.00 |
October | 1894.94 | 11-OCT-18:10 | 12322.72 | 7358.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 |
November | 1639.54 | 11-NOV-11:35 | 1508.90 | 788.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 |
December | 1522.94 | 13-DEC-19:10 | 5281.16 | 3153.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1418.71 | 1257.42 | 657.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2208.08 | 12322.72 | 7358.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.61 | 43.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2973.32 | 29-JAN-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.44 |
February | 3100.18 | 27-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
March | 3096.46 | 13-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 0.00 |
April | 3105.50 | 09-APR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 |
May | 3097.07 | 10-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 |
June | 2766.15 | 15-JUN-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 | 0.00 |
July | 2784.05 | 21-JUL-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 | 0.00 |
August | 2779.77 | 18-AUG-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 | 0.00 |
September | 2754.92 | 10-SEP-15:12 | 324.00 | 187.54 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 0.00 |
October | 2913.02 | 31-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.08 |
November | 3087.35 | 08-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 |
December | 3033.59 | 10-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2754.92 | 324.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3105.50 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 | 68.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1062.19 | 13-JAN-16:13 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 |
February | 2752.51 | 24-FEB-19:01 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.45 |
March | 3028.94 | 13-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 0.00 |
April | 3184.36 | 09-APR-20:11 | 1247.40 | 852.35 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.58 |
May | 3237.63 | 09-MAY-20:41 | 1441.80 | 758.59 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.43 |
June | 2750.83 | 05-JUN-21:51 | 1260.00 | 444.17 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
July | 2791.55 | 21-JUL-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 | 0.00 |
August | 2744.17 | 11-AUG-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
September | 2975.47 | 18-SEP-16:01 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
October | 2832.62 | 15-OCT-16:21 | 858.60 | 281.28 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 |
November | 2706.92 | 06-NOV-19:12 | 693.00 | 421.44 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.88 |
December | 1573.77 | 07-DEC-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1062.19 | 583.20 | 159.11 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3237.63 | 1441.80 | 852.35 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 | 113.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1612.45 | 28-JAN-16:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 |
February | 1654.08 | 27-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 |
March | 1657.33 | 13-MAR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 0.00 |
April | 1623.98 | 09-APR-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 |
May | 1621.99 | 10-MAY-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 |
June | 1487.15 | 22-JUN-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 | 0.00 |
July | 1486.93 | 31-JUL-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 0.00 |
August | 1488.33 | 04-AUG-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 0.00 |
September | 1485.54 | 26-SEP-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 0.00 |
October | 1603.60 | 12-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.78 |
November | 1653.83 | 08-NOV-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 |
December | 1631.50 | 10-DEC-16:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1485.54 | 378.00 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1657.33 | 970.20 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 | 37.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17331.12 | 19-JAN-23:10 | 26988.77 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.64 |
February | 17962.53 | 28-FEB-22:00 | 23990.02 | 1340.29 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.41 |
March | 19633.12 | 30-MAR-21:10 | 80966.30 | 3015.66 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.12 |
April | 21425.15 | 12-APR-15:14 | 104956.32 | 1759.13 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 88.76 | 0.00 |
May | 21050.50 | 13-MAY-17:05 | 71970.05 | 2412.53 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 0.00 |
June | 20899.61 | 13-JUN-22:00 | 26988.77 | 1005.22 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 |
July | 21377.06 | 07-JUL-22:00 | 26988.77 | 1005.22 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.66 | 0.00 |
August | 21103.86 | 18-AUG-22:00 | 26988.77 | 1005.22 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.67 | 0.00 |
September | 20825.39 | 22-SEP-16:52 | 89962.56 | 1507.83 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 54.01 | 0.00 |
October | 19503.78 | 18-OCT-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 |
November | 17846.67 | 03-NOV-21:00 | 23990.02 | 1340.29 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.54 |
December | 17651.07 | 12-DEC-23:10 | 26988.77 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17331.12 | 23990.02 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21425.15 | 104956.32 | 3015.66 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 88.76 | 93.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18302.85 | 19-JAN-22:15 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.81 |
February | 19935.22 | 28-FEB-22:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.97 |
March | 20862.05 | 30-MAR-21:07 | 80966.30 | 3015.66 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 |
April | 22000.43 | 12-APR-15:14 | 104956.32 | 1759.13 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 | 0.00 |
May | 21682.90 | 13-MAY-17:05 | 71970.05 | 2412.53 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 | 0.00 |
June | 22280.58 | 13-JUN-22:00 | 26988.77 | 1005.22 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 |
July | 22729.76 | 07-JUL-22:00 | 26988.77 | 1005.22 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.65 | 0.00 |
August | 22451.77 | 18-AUG-22:00 | 26988.77 | 1005.22 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.66 | 0.00 |
September | 21495.06 | 06-SEP-22:00 | 26988.77 | 1005.22 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 | 0.00 |
October | 20633.12 | 18-OCT-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 |
November | 19639.63 | 03-NOV-21:10 | 53977.54 | 2010.44 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.66 |
December | 18753.23 | 12-DEC-24:00 | 26988.77 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18302.85 | 26988.77 | 502.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22729.76 | 104956.32 | 3015.66 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 | 103.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26072.10 | 29-JAN-11:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 174.86 |
February | 27104.05 | 26-FEB-11:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 |
March | 28283.00 | 11-MAR-16:11 | 5603.98 | 1539.91 | 102231.89 | 157449.82 | 0.00 | 0.00 | 0.00 | 24.09 | 0.00 |
April | 31283.36 | 15-APR-10:36 | 4002.84 | 1099.94 | 73022.78 | 93720.13 | 0.00 | 0.00 | 0.00 | 1.97 | 0.00 |
May | 30481.33 | 13-MAY-17:05 | 6404.54 | 2111.88 | 58418.22 | 89971.33 | 0.00 | 0.00 | 0.00 | 23.96 | 0.00 |
June | 29222.86 | 02-JUN-10:40 | 1067.42 | 439.97 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 27.92 | 0.00 |
July | 29649.66 | 08-JUL-10:40 | 1601.14 | 439.97 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 127.01 | 0.00 |
August | 29501.19 | 27-AUG-10:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 83.94 | 0.00 |
September | 30384.45 | 22-SEP-16:52 | 8005.68 | 1319.92 | 87627.33 | 134956.99 | 0.00 | 0.00 | 0.00 | 25.42 | 0.00 |
October | 28019.75 | 09-OCT-10:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
November | 26801.95 | 11-NOV-11:50 | 800.57 | 263.98 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 |
December | 26335.99 | 12-DEC-11:50 | 533.71 | 219.99 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 56.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26072.10 | 533.71 | 219.99 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31283.36 | 8005.68 | 2111.88 | 102231.89 | 157449.82 | 0.00 | 0.00 | 0.00 | 127.01 | 174.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1706.96 | 31-JAN-19:00 | 1330.80 | 834.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.89 |
February | 2054.73 | 28-FEB-18:15 | 2661.60 | 1668.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 |
March | 3212.45 | 30-MAR-15:13 | 9315.60 | 2433.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 | 0.00 |
April | 4213.69 | 17-APR-15:10 | 1330.80 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.48 | 0.00 |
May | 4620.35 | 30-MAY-15:10 | 1330.80 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 | 0.00 |
June | 5182.75 | 13-JUN-15:40 | 1330.80 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.54 | 0.00 |
July | 5886.25 | 08-JUL-16:10 | 1330.80 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.03 | 0.00 |
August | 5821.52 | 18-AUG-15:10 | 1330.80 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 0.00 |
September | 5067.14 | 07-SEP-15:23 | 3992.40 | 1043.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.92 | 0.00 |
October | 3827.92 | 10-OCT-15:13 | 7984.80 | 2086.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.29 | 0.00 |
November | 2079.20 | 05-NOV-17:15 | 2129.28 | 1390.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.32 |
December | 1904.01 | 13-DEC-11:35 | 1064.64 | 695.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1706.96 | 1064.64 | 347.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5886.25 | 9315.60 | 2433.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.03 | 61.89 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.308759E+12 | 239401.46 | 19-JAN-20:10 | 0.494161E+12 | 427778.25 | 09-JAN-17:40 |
February | 0.287958E+12 | 245032.36 | 28-FEB-20:49 | 0.413395E+12 | 408552.45 | 12-FEB-17:10 |
March | 0.346002E+12 | 284523.16 | 30-MAR-19:10 | 0.400740E+12 | 342841.40 | 22-MAR-18:10 |
April | 0.379584E+12 | 288584.09 | 04-APR-19:00 | 0.368629E+12 | 320777.54 | 05-APR-20:00 |
May | 0.459612E+12 | 313549.31 | 30-MAY-19:40 | 0.357717E+12 | 315847.67 | 15-MAY-17:10 |
June | 0.527070E+12 | 332189.36 | 28-JUN-19:10 | 0.335439E+12 | 301689.85 | 02-JUN-17:10 |
July | 0.591164E+12 | 349211.60 | 07-JUL-19:49 | 0.340251E+12 | 285229.14 | 03-JUL-17:49 |
August | 0.606547E+12 | 351653.62 | 18-AUG-19:19 | 0.340007E+12 | 285095.58 | 31-AUG-17:30 |
September | 0.491853E+12 | 333106.14 | 07-SEP-19:10 | 0.334238E+12 | 298236.09 | 28-SEP-17:19 |
October | 0.388820E+12 | 319291.24 | 18-OCT-19:00 | 0.362459E+12 | 311670.21 | 30-OCT-17:19 |
November | 0.327736E+12 | 270980.11 | 27-NOV-20:10 | 0.390530E+12 | 355077.09 | 21-NOV-22:00 |
December | 0.309795E+12 | 234760.23 | 12-DEC-20:10 | 0.461511E+12 | 419038.20 | 02-DEC-19:10 |
Annual Sum or Average | 0.502490E+13 | 0.459908E+13 | ||||
Minimum of Months | 0.287958E+12 | 234760.23 | 0.334238E+12 | 285095.58 | ||
Maximum of Months | 0.606547E+12 | 351653.62 | 0.494161E+12 | 427778.25 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.108316E+11 | 24178.27 | 27-JAN-12:50 | 0.00 | 0.00 |
February | 0.116839E+11 | 27923.74 | 24-FEB-12:50 | 0.00 | 0.00 |
March | 0.178232E+11 | 32993.78 | 18-MAR-12:50 | 0.00 | 0.00 |
April | 0.208508E+11 | 33884.38 | 06-APR-12:39 | 0.00 | 0.00 |
May | 0.233800E+11 | 33854.32 | 10-MAY-12:20 | 0.00 | 0.00 |
June | 0.238235E+11 | 33103.47 | 10-JUN-12:30 | 0.00 | 0.00 |
July | 0.228304E+11 | 31933.61 | 24-JUL-12:30 | 0.00 | 0.00 |
August | 0.210976E+11 | 30654.68 | 02-AUG-12:30 | 0.00 | 0.00 |
September | 0.155604E+11 | 29247.82 | 14-SEP-12:30 | 0.00 | 0.00 |
October | 0.143538E+11 | 28160.43 | 25-OCT-12:30 | 0.00 | 0.00 |
November | 0.107503E+11 | 22933.84 | 07-NOV-12:30 | 0.00 | 0.00 |
December | 0.963192E+10 | 21470.57 | 02-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.202617E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.963192E+10 | 21470.57 | 0.00 | 0.00 | |
Maximum of Months | 0.238235E+11 | 33884.38 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.405867E+11 | 0.148978E+11 | 0.140003E+12 | 0.331717E+11 | 0.471318E+11 | 0.586728E+10 | 0.00 | 0.609312E+10 | 0.00 | 0.00 | 0.958387E+10 | 0.770428E+10 | 0.00 |
February | 0.366299E+11 | 0.127154E+11 | 0.126445E+12 | 0.299617E+11 | 0.428951E+11 | 0.549963E+10 | 0.00 | 0.176482E+11 | 0.00 | 0.00 | 0.583858E+10 | 0.696185E+10 | 0.00 |
March | 0.402896E+11 | 0.130025E+11 | 0.140056E+12 | 0.331741E+11 | 0.485241E+11 | 0.748324E+10 | 0.00 | 0.494763E+11 | 0.00 | 0.00 | 0.255724E+10 | 0.770285E+10 | 0.00 |
April | 0.387681E+11 | 0.115093E+11 | 0.135446E+12 | 0.321012E+11 | 0.483259E+11 | 0.779077E+10 | 0.00 | 0.904365E+11 | 0.00 | 0.00 | 0.411171E+10 | 0.746484E+10 | 0.00 |
May | 0.398948E+11 | 0.109580E+11 | 0.140035E+12 | 0.331726E+11 | 0.518650E+11 | 0.824914E+10 | 0.00 | 0.155890E+12 | 0.00 | 0.00 | 0.806691E+10 | 0.770423E+10 | 0.00 |
June | 0.385165E+11 | 0.101941E+11 | 0.135537E+12 | 0.321034E+11 | 0.531819E+11 | 0.832316E+10 | 0.00 | 0.222804E+12 | 0.00 | 0.00 | 0.152942E+11 | 0.745688E+10 | 0.00 |
July | 0.398351E+11 | 0.106880E+11 | 0.139944E+12 | 0.331702E+11 | 0.559897E+11 | 0.882556E+10 | 0.00 | 0.271551E+12 | 0.00 | 0.00 | 0.196796E+11 | 0.771239E+10 | 0.00 |
August | 0.399782E+11 | 0.114691E+11 | 0.140067E+12 | 0.331739E+11 | 0.568016E+11 | 0.893390E+10 | 0.00 | 0.284090E+12 | 0.00 | 0.00 | 0.205442E+11 | 0.770437E+10 | 0.00 |
September | 0.389351E+11 | 0.121181E+11 | 0.135457E+12 | 0.321013E+11 | 0.514820E+11 | 0.817860E+10 | 0.00 | 0.190358E+12 | 0.00 | 0.00 | 0.120934E+11 | 0.746620E+10 | 0.00 |
October | 0.404801E+11 | 0.136343E+11 | 0.139992E+12 | 0.331716E+11 | 0.500784E+11 | 0.778998E+10 | 0.00 | 0.870331E+11 | 0.00 | 0.00 | 0.517580E+10 | 0.770293E+10 | 0.00 |
November | 0.392449E+11 | 0.141684E+11 | 0.135531E+12 | 0.321024E+11 | 0.471135E+11 | 0.715612E+10 | 0.00 | 0.381349E+11 | 0.00 | 0.00 | 0.322568E+10 | 0.744870E+10 | 0.00 |
December | 0.405598E+11 | 0.151620E+11 | 0.139944E+12 | 0.331706E+11 | 0.473436E+11 | 0.578892E+10 | 0.00 | 0.116260E+11 | 0.00 | 0.00 | 0.476166E+10 | 0.771243E+10 | 0.00 |
Annual Sum or Average | 0.473719E+12 | 0.150517E+12 | 0.164846E+13 | 0.390575E+12 | 0.600733E+12 | 0.898863E+11 | 0.00 | 0.142514E+13 | 0.00 | 0.00 | 0.110933E+12 | 0.907419E+11 | 0.00 |
Minimum of Months | 0.366299E+11 | 0.101941E+11 | 0.126445E+12 | 0.299617E+11 | 0.428951E+11 | 0.549963E+10 | 0.00 | 0.609312E+10 | 0.00 | 0.00 | 0.255724E+10 | 0.696185E+10 | 0.00 |
Maximum of Months | 0.405867E+11 | 0.151620E+11 | 0.140067E+12 | 0.331741E+11 | 0.568016E+11 | 0.893390E+10 | 0.00 | 0.284090E+12 | 0.00 | 0.00 | 0.205442E+11 | 0.771243E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.112857E+12 | 0.00 | 0.229386E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.686945E+11 | 0.00 | 0.207497E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.239309E+11 | 0.00 | 0.224785E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.132194E+11 | 0.00 | 0.208454E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.142736E+10 | 0.00 | 0.204311E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.172917E+09 | 0.00 | 0.188153E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 49354184.58 | 0.00 | 0.188381E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 20546179.03 | 0.00 | 0.187948E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.358611E+09 | 0.00 | 0.186908E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.803232E+10 | 0.00 | 0.202523E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.366853E+11 | 0.00 | 0.206753E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.862673E+11 | 0.00 | 0.223423E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.351715E+12 | 0.00 | 0.245852E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 20546179.03 | 0.00 | 0.186908E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.112857E+12 | 0.00 | 0.229386E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 39200.55 | 02-JAN-20:10 | 9571.94 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 23859.27 | 02-JAN-07:19 | 25769.97 | 06-JAN-19:10 | 4041.34 | 05-JAN-16:19 | 0.00 | 01-JAN-00:10 |
February | 39200.55 | 01-FEB-20:10 | 9571.94 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 23859.27 | 01-FEB-07:19 | 25807.23 | 19-FEB-20:49 | 4035.58 | 03-FEB-16:19 | 0.00 | 01-FEB-00:10 |
March | 39200.55 | 01-MAR-20:10 | 9571.94 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 23859.27 | 01-MAR-07:19 | 28263.57 | 30-MAR-21:00 | 3721.55 | 18-MAR-06:49 | 0.00 | 01-MAR-00:10 |
April | 39200.55 | 03-APR-19:10 | 9571.94 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 23859.27 | 03-APR-06:19 | 28786.69 | 18-APR-21:00 | 3878.78 | 06-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 39200.55 | 01-MAY-19:19 | 9571.94 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 23859.03 | 08-MAY-06:19 | 30578.54 | 19-MAY-21:00 | 3695.67 | 13-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 39200.55 | 01-JUN-19:40 | 9571.94 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 23858.91 | 23-JUN-06:19 | 33708.41 | 13-JUN-21:19 | 3863.87 | 28-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 39200.55 | 03-JUL-19:49 | 9571.94 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 23858.99 | 28-JUL-06:19 | 35879.35 | 07-JUL-21:40 | 4000.77 | 06-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 39200.55 | 01-AUG-19:40 | 9571.94 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 23859.27 | 25-AUG-06:19 | 36246.82 | 18-AUG-21:40 | 3989.51 | 10-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 39200.55 | 01-SEP-19:10 | 9571.94 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 23859.27 | 01-SEP-06:19 | 34922.00 | 07-SEP-21:19 | 3836.51 | 06-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 39200.55 | 02-OCT-19:10 | 9571.94 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 23859.27 | 02-OCT-06:19 | 31093.42 | 10-OCT-21:00 | 3713.68 | 26-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 39200.55 | 01-NOV-19:10 | 9571.94 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 23859.27 | 01-NOV-06:19 | 28242.22 | 09-NOV-21:30 | 3867.58 | 21-NOV-09:39 | 0.00 | 01-NOV-00:10 |
December | 39200.55 | 01-DEC-20:10 | 9571.94 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 23859.27 | 01-DEC-07:19 | 26827.67 | 13-DEC-21:10 | 4096.88 | 17-DEC-10:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 39200.55 | 9571.94 | 88863.15 | 23858.91 | 25769.97 | 3695.67 | 0.00 | |||||||
Maximum of Months | 39200.55 | 9571.94 | 88863.15 | 23859.27 | 36246.82 | 4096.88 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 53071.59 | 19-JAN-20:10 | 0.00 | 0.00 | 8265.52 | 05-JAN-00:10 | 4738.34 | 19-JAN-19:10 | 0.00 | 01-JAN-00:10 |
February | 77314.80 | 26-FEB-16:19 | 0.00 | 0.00 | 8265.52 | 01-FEB-04:30 | 4738.75 | 23-FEB-19:10 | 0.00 | 01-FEB-00:10 |
March | 101006.92 | 30-MAR-18:10 | 0.00 | 0.00 | 8265.52 | 04-MAR-16:00 | 4738.61 | 02-MAR-19:10 | 0.00 | 01-MAR-00:10 |
April | 103081.78 | 12-APR-15:39 | 0.00 | 0.00 | 8265.52 | 02-APR-12:50 | 4738.49 | 25-APR-06:00 | 0.00 | 01-APR-00:10 |
May | 125457.95 | 30-MAY-18:10 | 0.00 | 0.00 | 8265.52 | 31-MAY-08:00 | 4738.52 | 02-MAY-06:00 | 0.00 | 01-MAY-00:10 |
June | 150485.63 | 28-JUN-18:10 | 0.00 | 0.00 | 8265.52 | 14-JUN-08:00 | 4738.77 | 01-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 169280.48 | 08-JUL-15:30 | 0.00 | 0.00 | 8265.52 | 01-JUL-08:39 | 4738.71 | 13-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 163050.47 | 01-AUG-15:30 | 0.00 | 0.00 | 8265.52 | 05-AUG-08:00 | 4738.57 | 24-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 148441.88 | 07-SEP-15:30 | 0.00 | 0.00 | 8265.52 | 06-SEP-08:39 | 4738.70 | 07-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 123654.24 | 18-OCT-21:00 | 0.00 | 0.00 | 8265.52 | 01-OCT-12:00 | 4738.20 | 04-OCT-06:19 | 0.00 | 01-OCT-00:10 |
November | 89360.86 | 05-NOV-15:20 | 0.00 | 0.00 | 8265.52 | 05-NOV-12:00 | 4738.42 | 06-NOV-07:00 | 0.00 | 01-NOV-00:10 |
December | 62407.42 | 12-DEC-13:00 | 0.00 | 0.00 | 8265.52 | 01-DEC-00:40 | 4738.61 | 07-DEC-19:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 53071.59 | 0.00 | 0.00 | 8265.52 | 4738.20 | 0.00 | ||||
Maximum of Months | 169280.48 | 0.00 | 0.00 | 8265.52 | 4738.77 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 239401.46 | 19-JAN-20:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 23654.30 | 3002.09 | 0.00 | 53071.59 | 0.00 |
February | 245032.36 | 28-FEB-20:49 | 39200.55 | 86131.51 | 9571.94 | 19292.08 | 24628.38 | 3009.15 | 0.00 | 57979.56 | 0.00 |
March | 284523.16 | 30-MAR-19:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 27196.79 | 3308.91 | 0.00 | 92778.07 | 0.00 |
April | 288584.09 | 04-APR-19:00 | 39200.55 | 86131.51 | 9571.94 | 19292.08 | 26993.55 | 3304.37 | 0.00 | 90853.16 | 0.00 |
May | 313549.31 | 30-MAY-19:40 | 39200.55 | 86131.51 | 9571.94 | 19291.80 | 28475.99 | 3556.17 | 0.00 | 113940.99 | 0.00 |
June | 332189.36 | 28-JUN-19:10 | 37294.72 | 86131.51 | 0.00 | 19286.83 | 29062.13 | 3779.02 | 0.00 | 142986.89 | 0.00 |
July | 349211.60 | 07-JUL-19:49 | 39200.55 | 86131.51 | 9571.94 | 19291.79 | 30524.59 | 3707.85 | 0.00 | 147643.94 | 0.00 |
August | 351653.62 | 18-AUG-19:19 | 39200.55 | 86131.51 | 9571.94 | 19291.31 | 31164.13 | 3668.98 | 0.00 | 149056.57 | 0.00 |
September | 333106.14 | 07-SEP-19:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 28861.73 | 3705.42 | 0.00 | 132593.33 | 0.00 |
October | 319291.24 | 18-OCT-19:00 | 39200.55 | 86131.51 | 9571.94 | 19292.08 | 26572.63 | 3610.48 | 0.00 | 120870.89 | 0.00 |
November | 270980.11 | 27-NOV-20:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 25106.16 | 3154.29 | 0.00 | 76126.45 | 0.00 |
December | 234760.23 | 12-DEC-20:10 | 39200.55 | 86131.51 | 9571.94 | 19288.57 | 24754.70 | 3011.55 | 0.00 | 47769.51 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 234760.23 | 37294.72 | 86131.51 | 0.00 | 19286.83 | 23654.30 | 3002.09 | 0.00 | 47769.51 | 0.00 | |
Maximum of Months | 351653.62 | 39200.55 | 86131.51 | 9571.94 | 19292.08 | 31164.13 | 3779.02 | 0.00 | 149056.57 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 162517.92 | 09-JAN-16:19 | 0.00 | 228947.46 | 24-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 152500.94 | 03-FEB-16:19 | 0.00 | 226618.80 | 08-FEB-21:10 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 103204.14 | 19-MAR-06:40 | 0.00 | 212955.20 | 02-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 111394.14 | 06-APR-06:19 | 0.00 | 208771.36 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 25601.32 | 15-MAY-13:00 | 0.00 | 206940.77 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 12702.49 | 02-JUN-18:40 | 0.00 | 197256.50 | 02-JUN-17:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 6035.97 | 29-JUL-08:00 | 0.00 | 181445.12 | 03-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 2377.39 | 25-AUG-08:00 | 0.00 | 181315.49 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 11766.86 | 29-SEP-08:09 | 0.00 | 193997.81 | 30-SEP-18:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 94845.36 | 26-OCT-04:00 | 0.00 | 206561.98 | 30-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 124049.34 | 25-NOV-07:30 | 0.00 | 208534.88 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 135591.96 | 21-DEC-09:09 | 0.00 | 211343.82 | 27-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 2377.39 | 0.00 | 181315.49 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 162517.92 | 0.00 | 228947.46 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.33 | 24.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.63 | 0.33 | 24.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.33 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.67 | 21.71 | 2.67 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.76 | 1.67 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.78 | 3.67 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.75 | 1.67 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 21.77 | 7.67 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.79 | 3.67 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.76 | 2.33 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.75 | 6.17 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 21.78 | 9.67 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.75 | 6.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.83 | 21.76 | 27.83 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 21.78 | 9.67 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.67 | 0.50 | 21.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.67 | 1.00 | 21.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.67 | 0.50 | 21.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.98 | 0.83 | 21.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 22.01 | 3.83 | 22.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 22.15 | 7.67 | 22.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 22.23 | 9.17 | 22.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.12 | 6.17 | 22.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 22.09 | 3.67 | 22.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 31.33 | 22.14 | 31.33 | 22.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 22.23 | 9.17 | 22.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.71 | 1.33 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.74 | 4.00 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.79 | 2.33 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.17 | 21.74 | 10.17 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.79 | 4.00 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.74 | 3.50 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.78 | 6.00 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.76 | 3.00 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.88 | 0.33 | 21.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.50 | 21.77 | 13.50 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.88 | 6.00 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.81 | 2.33 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.83 | 2.17 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.84 | 2.67 | 21.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
Annual Sum or Average | 0.00 | 0.00 | 11.50 | 21.79 | 11.50 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.84 | 2.67 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.62 | 0.50 | 24.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.73 | 7.83 | 24.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.69 | 2.33 | 24.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.61 | 1.17 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.78 | 2.00 | 24.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.83 | 24.72 | 13.83 | 24.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.78 | 7.83 | 24.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
February | 672.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
March | 744.00 | 21.37 | 14.33 | 21.36 | 14.33 | 21.35 |
April | 720.00 | 21.14 | 2.17 | 21.14 | 2.17 | 21.14 |
May | 744.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
June | 720.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
July | 744.00 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
August | 526.50 | 23.04 | 37.67 | 23.07 | 36.67 | 23.08 |
September | 153.33 | 23.57 | 366.00 | 23.79 | 73.50 | 23.80 |
October | 182.50 | 23.70 | 189.00 | 23.82 | 26.00 | 23.83 |
November | 432.83 | 23.83 | 94.17 | 23.86 | 4.67 | 23.86 |
December | 695.50 | 23.46 | 5.33 | 23.46 | 0.00 | 23.46 |
Annual Sum or Average | 7078.67 | 22.29 | 708.67 | 22.43 | 157.33 | 22.45 |
Minimum of Months | 153.33 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
Maximum of Months | 744.00 | 23.83 | 366.00 | 23.86 | 73.50 | 23.86 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.17 | 21.29 | 217.17 | 21.23 | 217.17 | 21.19 |
February | 640.00 | 21.47 | 139.00 | 21.39 | 139.00 | 21.33 |
March | 649.17 | 22.05 | 44.00 | 22.14 | 6.67 | 22.13 |
April | 555.67 | 22.30 | 100.00 | 22.53 | 9.83 | 22.53 |
May | 406.67 | 22.72 | 303.33 | 23.12 | 65.50 | 23.11 |
June | 224.17 | 23.42 | 572.33 | 23.74 | 140.17 | 23.73 |
July | 218.83 | 23.57 | 691.83 | 23.80 | 185.17 | 23.78 |
August | 208.83 | 23.91 | 741.00 | 23.93 | 208.83 | 23.93 |
September | 281.17 | 23.02 | 508.83 | 23.53 | 130.33 | 23.53 |
October | 494.33 | 22.22 | 192.17 | 22.66 | 39.00 | 22.69 |
November | 646.67 | 21.91 | 29.67 | 21.95 | 12.33 | 21.94 |
December | 714.17 | 21.48 | 72.33 | 21.46 | 65.17 | 21.43 |
Annual Sum or Average | 5778.83 | 22.11 | 3611.67 | 22.65 | 1219.17 | 22.65 |
Minimum of Months | 208.83 | 21.29 | 29.67 | 21.23 | 6.67 | 21.19 |
Maximum of Months | 739.17 | 23.91 | 741.00 | 23.93 | 217.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.29 | 12.67 | 21.28 | 12.67 | 21.28 |
February | 672.00 | 21.54 | 26.83 | 21.52 | 26.83 | 21.50 |
March | 735.00 | 22.06 | 1.67 | 22.07 | 0.00 | 22.07 |
April | 689.83 | 22.35 | 12.67 | 22.35 | 10.50 | 22.36 |
May | 621.50 | 22.57 | 116.33 | 22.68 | 73.83 | 22.71 |
June | 484.50 | 22.96 | 257.00 | 23.21 | 126.83 | 23.27 |
July | 441.83 | 23.07 | 357.67 | 23.36 | 158.00 | 23.41 |
August | 415.50 | 23.26 | 409.17 | 23.51 | 188.67 | 23.56 |
September | 495.17 | 22.86 | 212.67 | 23.09 | 105.50 | 23.15 |
October | 695.17 | 22.42 | 51.17 | 22.48 | 35.83 | 22.51 |
November | 720.00 | 22.04 | 4.17 | 22.04 | 4.17 | 22.04 |
December | 744.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
Annual Sum or Average | 7458.50 | 22.22 | 1462.00 | 22.45 | 742.83 | 22.52 |
Minimum of Months | 415.50 | 21.29 | 0.00 | 21.28 | 0.00 | 21.28 |
Maximum of Months | 744.00 | 23.26 | 409.17 | 23.51 | 188.67 | 23.56 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.72 | 99.67 | 21.65 | 99.67 | 21.60 |
February | 670.33 | 22.37 | 100.33 | 22.24 | 100.33 | 22.14 |
March | 641.67 | 23.41 | 4.50 | 23.41 | 0.00 | 23.41 |
April | 415.83 | 23.75 | 95.00 | 23.80 | 10.00 | 23.80 |
May | 141.67 | 23.99 | 423.33 | 24.00 | 22.17 | 24.00 |
June | 75.17 | 24.00 | 540.50 | 24.00 | 0.00 | 24.00 |
July | 8.33 | 24.00 | 744.00 | 24.00 | 8.33 | 24.00 |
August | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
September | 3.00 | 24.00 | 535.67 | 24.00 | 2.00 | 24.00 |
October | 410.67 | 23.81 | 176.67 | 23.86 | 32.50 | 23.87 |
November | 582.00 | 23.38 | 34.83 | 23.42 | 0.00 | 23.42 |
December | 708.50 | 22.53 | 3.83 | 22.54 | 0.00 | 22.54 |
Annual Sum or Average | 4401.17 | 22.92 | 3502.33 | 23.33 | 275.00 | 23.28 |
Minimum of Months | 0.00 | 0.00 | 3.83 | 21.65 | 0.00 | 21.60 |
Maximum of Months | 744.00 | 24.00 | 744.00 | 24.00 | 100.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 317.83 | 21.00 | 317.83 | 21.00 |
February | 672.00 | 21.03 | 186.00 | 21.02 | 186.00 | 21.02 |
March | 744.00 | 21.18 | 25.33 | 21.17 | 25.33 | 21.17 |
April | 720.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
May | 744.00 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
June | 720.00 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
July | 741.83 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
August | 741.17 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
September | 720.00 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
October | 744.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
November | 720.00 | 21.18 | 7.17 | 21.18 | 7.17 | 21.17 |
December | 744.00 | 21.03 | 117.17 | 21.02 | 117.17 | 21.02 |
Annual Sum or Average | 8755.00 | 21.74 | 653.50 | 21.69 | 653.50 | 21.64 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.81 | 317.83 | 22.81 | 317.83 | 22.81 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 159.33 | 24.00 | 744.00 | 24.00 | 159.33 | 24.00 |
February | 168.00 | 24.00 | 672.00 | 24.00 | 168.00 | 24.00 |
March | 253.00 | 24.00 | 744.00 | 24.00 | 253.00 | 24.00 |
April | 331.83 | 24.00 | 720.00 | 24.00 | 331.83 | 24.00 |
May | 527.83 | 24.00 | 744.00 | 24.00 | 527.83 | 24.00 |
June | 567.00 | 24.00 | 720.00 | 24.00 | 567.00 | 24.00 |
July | 644.17 | 24.00 | 744.00 | 24.00 | 644.17 | 24.00 |
August | 653.17 | 24.00 | 744.00 | 24.00 | 653.17 | 24.00 |
September | 557.17 | 24.00 | 720.00 | 24.00 | 557.17 | 24.00 |
October | 385.50 | 24.00 | 744.00 | 24.00 | 385.50 | 24.00 |
November | 245.50 | 24.00 | 720.00 | 24.00 | 245.50 | 24.00 |
December | 183.00 | 24.00 | 744.00 | 24.00 | 183.00 | 24.00 |
Annual Sum or Average | 4675.50 | 24.00 | 8760.00 | 24.00 | 4675.50 | 24.00 |
Minimum of Months | 159.33 | 24.00 | 672.00 | 24.00 | 159.33 | 24.00 |
Maximum of Months | 653.17 | 24.00 | 744.00 | 24.00 | 653.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 25.83 | 21.36 | 25.83 | 21.35 |
February | 668.83 | 21.54 | 14.33 | 21.53 | 14.33 | 21.53 |
March | 717.17 | 21.81 | 16.50 | 21.83 | 11.50 | 21.85 |
April | 686.33 | 21.85 | 52.17 | 21.90 | 52.17 | 21.95 |
May | 695.83 | 21.95 | 179.00 | 22.13 | 166.50 | 22.23 |
June | 657.00 | 22.24 | 220.17 | 22.48 | 201.50 | 22.61 |
July | 633.83 | 22.39 | 314.17 | 22.65 | 284.50 | 22.77 |
August | 535.33 | 22.64 | 374.83 | 22.89 | 284.67 | 23.00 |
September | 565.00 | 22.25 | 278.67 | 22.51 | 213.17 | 22.62 |
October | 661.83 | 22.03 | 112.00 | 22.16 | 77.33 | 22.22 |
November | 686.17 | 21.79 | 27.00 | 21.82 | 26.83 | 21.85 |
December | 732.33 | 21.54 | 4.83 | 21.55 | 3.33 | 21.55 |
Annual Sum or Average | 7983.67 | 21.92 | 1619.50 | 22.11 | 1361.67 | 22.22 |
Minimum of Months | 535.33 | 21.36 | 4.83 | 21.36 | 3.33 | 21.35 |
Maximum of Months | 744.00 | 22.64 | 374.83 | 22.89 | 284.67 | 23.00 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.81 | 4.50 | 21.82 | 4.50 | 21.83 |
February | 670.17 | 22.04 | 10.67 | 22.06 | 10.67 | 22.07 |
March | 708.17 | 22.44 | 31.33 | 22.49 | 20.17 | 22.51 |
April | 628.67 | 22.54 | 91.67 | 22.65 | 66.00 | 22.71 |
May | 621.50 | 22.75 | 254.50 | 22.99 | 190.33 | 23.09 |
June | 533.50 | 23.08 | 315.83 | 23.35 | 214.50 | 23.46 |
July | 536.67 | 23.26 | 410.67 | 23.49 | 298.83 | 23.58 |
August | 458.50 | 23.46 | 431.67 | 23.64 | 300.67 | 23.71 |
September | 500.50 | 23.11 | 352.50 | 23.37 | 241.17 | 23.45 |
October | 606.83 | 22.69 | 112.00 | 22.83 | 88.00 | 22.91 |
November | 688.83 | 22.51 | 38.00 | 22.56 | 31.17 | 22.59 |
December | 727.00 | 22.12 | 8.67 | 22.14 | 4.00 | 22.14 |
Annual Sum or Average | 7424.33 | 22.58 | 2062.00 | 22.83 | 1470.00 | 22.95 |
Minimum of Months | 458.50 | 21.81 | 4.50 | 21.82 | 4.00 | 21.83 |
Maximum of Months | 744.00 | 23.46 | 431.67 | 23.64 | 300.67 | 23.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 413.17 | 20.83 | 413.17 | 20.80 |
February | 672.00 | 21.11 | 233.83 | 20.99 | 233.83 | 20.92 |
March | 739.67 | 21.49 | 11.17 | 21.48 | 11.17 | 21.46 |
April | 709.67 | 21.63 | 5.83 | 21.64 | 5.83 | 21.64 |
May | 710.00 | 21.66 | 4.50 | 21.67 | 4.50 | 21.68 |
June | 634.83 | 21.58 | 7.67 | 21.60 | 7.67 | 21.61 |
July | 630.67 | 21.51 | 20.17 | 21.56 | 20.17 | 21.60 |
August | 615.17 | 21.48 | 11.83 | 21.51 | 11.83 | 21.53 |
September | 658.67 | 21.60 | 16.00 | 21.63 | 16.00 | 21.66 |
October | 728.83 | 21.53 | 35.00 | 21.54 | 35.00 | 21.55 |
November | 720.00 | 21.41 | 42.50 | 21.39 | 42.50 | 21.37 |
December | 744.00 | 21.11 | 199.50 | 21.04 | 199.50 | 20.99 |
Annual Sum or Average | 8307.50 | 21.41 | 1001.17 | 21.36 | 1001.17 | 21.31 |
Minimum of Months | 615.17 | 20.91 | 4.50 | 20.83 | 4.50 | 20.80 |
Maximum of Months | 744.00 | 21.66 | 413.17 | 21.67 | 413.17 | 21.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.66 | 550.00 | 20.60 | 550.00 | 20.58 |
February | 672.00 | 20.96 | 295.50 | 20.81 | 295.50 | 20.73 |
March | 739.17 | 21.56 | 29.00 | 21.53 | 29.00 | 21.49 |
April | 692.33 | 21.90 | 28.33 | 21.95 | 20.17 | 21.97 |
May | 662.33 | 22.01 | 68.83 | 22.15 | 52.33 | 22.22 |
June | 609.50 | 21.89 | 64.17 | 22.07 | 57.50 | 22.20 |
July | 615.17 | 21.86 | 106.33 | 22.11 | 103.50 | 22.29 |
August | 616.33 | 21.78 | 76.00 | 21.97 | 74.83 | 22.12 |
September | 663.50 | 22.01 | 81.33 | 22.16 | 76.67 | 22.27 |
October | 720.83 | 21.66 | 64.17 | 21.70 | 63.17 | 21.73 |
November | 720.00 | 21.27 | 103.00 | 21.22 | 103.00 | 21.18 |
December | 744.00 | 20.84 | 397.83 | 20.76 | 397.83 | 20.72 |
Annual Sum or Average | 8199.17 | 21.51 | 1864.50 | 21.47 | 1823.50 | 21.43 |
Minimum of Months | 609.50 | 20.66 | 28.33 | 20.60 | 20.17 | 20.58 |
Maximum of Months | 744.00 | 22.01 | 550.00 | 22.16 | 550.00 | 22.29 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.98 | 346.00 | 20.91 | 346.00 | 20.88 |
February | 672.00 | 21.17 | 207.17 | 21.08 | 207.17 | 21.03 |
March | 744.00 | 21.49 | 6.33 | 21.49 | 6.33 | 21.48 |
April | 719.67 | 21.84 | 7.33 | 21.85 | 7.33 | 21.86 |
May | 743.17 | 22.06 | 35.17 | 22.10 | 35.17 | 22.15 |
June | 719.33 | 22.03 | 52.83 | 22.12 | 52.83 | 22.20 |
July | 743.33 | 22.04 | 91.00 | 22.17 | 91.00 | 22.28 |
August | 743.83 | 21.96 | 70.33 | 22.06 | 70.33 | 22.15 |
September | 719.67 | 22.03 | 54.50 | 22.11 | 54.50 | 22.19 |
October | 744.00 | 21.66 | 32.67 | 21.69 | 32.67 | 21.73 |
November | 720.00 | 21.36 | 18.17 | 21.35 | 18.17 | 21.35 |
December | 744.00 | 21.12 | 158.00 | 21.07 | 158.00 | 21.04 |
Annual Sum or Average | 8757.00 | 21.65 | 1079.50 | 21.64 | 1079.50 | 21.63 |
Minimum of Months | 672.00 | 20.98 | 6.33 | 20.91 | 6.33 | 20.88 |
Maximum of Months | 744.00 | 22.06 | 346.00 | 22.17 | 346.00 | 22.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 399.83 | 20.87 | 399.83 | 20.83 |
February | 672.00 | 21.16 | 221.50 | 21.05 | 221.50 | 20.98 |
March | 744.00 | 21.57 | 16.50 | 21.56 | 16.50 | 21.54 |
April | 720.00 | 21.72 | 4.33 | 21.72 | 4.33 | 21.73 |
May | 720.33 | 21.72 | 3.67 | 21.73 | 3.67 | 21.74 |
June | 619.00 | 21.56 | 4.00 | 21.57 | 4.00 | 21.58 |
July | 584.00 | 21.38 | 15.50 | 21.42 | 14.67 | 21.45 |
August | 585.00 | 21.39 | 9.00 | 21.42 | 9.00 | 21.44 |
September | 659.67 | 21.61 | 14.67 | 21.65 | 14.67 | 21.67 |
October | 737.00 | 21.59 | 33.83 | 21.60 | 33.83 | 21.61 |
November | 720.00 | 21.46 | 38.00 | 21.43 | 38.00 | 21.42 |
December | 744.00 | 21.14 | 180.83 | 21.08 | 180.83 | 21.04 |
Annual Sum or Average | 8249.00 | 21.44 | 941.67 | 21.38 | 940.83 | 21.34 |
Minimum of Months | 584.00 | 20.94 | 3.67 | 20.87 | 3.67 | 20.83 |
Maximum of Months | 744.00 | 21.72 | 399.83 | 21.73 | 399.83 | 21.74 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 541.33 | 20.62 | 541.33 | 20.60 |
February | 672.00 | 21.00 | 298.50 | 20.85 | 298.50 | 20.77 |
March | 744.00 | 21.58 | 30.17 | 21.55 | 30.17 | 21.53 |
April | 713.00 | 21.99 | 17.33 | 22.02 | 15.33 | 22.04 |
May | 683.83 | 22.12 | 69.83 | 22.26 | 52.83 | 22.34 |
June | 581.50 | 21.90 | 74.00 | 22.18 | 59.00 | 22.35 |
July | 576.00 | 21.87 | 110.33 | 22.22 | 102.67 | 22.46 |
August | 588.33 | 21.76 | 76.83 | 22.02 | 74.50 | 22.21 |
September | 661.83 | 22.05 | 82.67 | 22.23 | 75.17 | 22.36 |
October | 742.67 | 21.74 | 58.33 | 21.77 | 58.00 | 21.79 |
November | 720.00 | 21.25 | 89.67 | 21.21 | 89.67 | 21.18 |
December | 744.00 | 20.86 | 389.17 | 20.79 | 389.17 | 20.76 |
Annual Sum or Average | 8171.17 | 21.54 | 1838.17 | 21.52 | 1786.33 | 21.49 |
Minimum of Months | 576.00 | 20.68 | 17.33 | 20.62 | 15.33 | 20.60 |
Maximum of Months | 744.00 | 22.12 | 541.33 | 22.26 | 541.33 | 22.46 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 114.17 | 21.01 | 114.17 | 21.01 |
February | 672.00 | 21.18 | 108.67 | 21.15 | 108.67 | 21.13 |
March | 744.00 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
April | 720.00 | 22.17 | 16.00 | 22.17 | 16.00 | 22.18 |
May | 744.00 | 22.55 | 107.00 | 22.56 | 107.00 | 22.57 |
June | 710.83 | 23.03 | 165.50 | 23.06 | 165.50 | 23.08 |
July | 674.33 | 23.20 | 237.50 | 23.23 | 237.50 | 23.24 |
August | 681.50 | 23.26 | 259.17 | 23.28 | 258.67 | 23.30 |
September | 720.00 | 22.85 | 163.83 | 22.87 | 163.83 | 22.89 |
October | 744.00 | 22.06 | 46.67 | 22.08 | 46.67 | 22.10 |
November | 720.00 | 21.40 | 9.33 | 21.40 | 9.33 | 21.40 |
December | 744.00 | 21.08 | 60.83 | 21.07 | 60.83 | 21.07 |
Annual Sum or Average | 8618.67 | 22.11 | 1288.67 | 22.18 | 1288.17 | 22.23 |
Minimum of Months | 672.00 | 21.02 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.26 | 259.17 | 23.28 | 258.67 | 23.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.77 | 563.67 | 20.71 | 563.67 | 20.69 |
February | 672.00 | 20.99 | 330.83 | 20.86 | 330.83 | 20.80 |
March | 735.50 | 21.42 | 46.83 | 21.37 | 46.83 | 21.33 |
April | 690.67 | 21.55 | 27.33 | 21.56 | 27.33 | 21.56 |
May | 666.67 | 21.54 | 18.83 | 21.55 | 18.83 | 21.56 |
June | 598.33 | 21.47 | 17.50 | 21.51 | 17.50 | 21.54 |
July | 600.83 | 21.42 | 43.67 | 21.50 | 38.00 | 21.55 |
August | 588.83 | 21.40 | 29.67 | 21.46 | 25.17 | 21.51 |
September | 630.67 | 21.50 | 34.50 | 21.55 | 33.83 | 21.60 |
October | 717.33 | 21.44 | 62.17 | 21.43 | 62.17 | 21.42 |
November | 718.17 | 21.32 | 117.67 | 21.26 | 117.67 | 21.22 |
December | 744.00 | 20.97 | 395.83 | 20.88 | 395.83 | 20.84 |
Annual Sum or Average | 8107.00 | 21.30 | 1688.50 | 21.23 | 1677.67 | 21.18 |
Minimum of Months | 588.83 | 20.77 | 17.50 | 20.71 | 17.50 | 20.69 |
Maximum of Months | 744.00 | 21.55 | 563.67 | 21.56 | 563.67 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.55 | 630.00 | 20.51 | 630.00 | 20.50 |
February | 672.00 | 20.86 | 380.00 | 20.72 | 380.00 | 20.66 |
March | 735.17 | 21.47 | 85.17 | 21.39 | 85.17 | 21.32 |
April | 663.33 | 21.80 | 65.50 | 21.88 | 49.00 | 21.89 |
May | 613.17 | 21.87 | 98.00 | 22.09 | 70.00 | 22.16 |
June | 579.50 | 21.79 | 75.00 | 22.00 | 68.33 | 22.13 |
July | 590.67 | 21.77 | 128.33 | 22.05 | 118.83 | 22.23 |
August | 588.33 | 21.68 | 90.33 | 21.89 | 86.50 | 22.05 |
September | 632.00 | 21.88 | 102.00 | 22.06 | 96.67 | 22.17 |
October | 713.17 | 21.55 | 107.83 | 21.56 | 103.67 | 21.56 |
November | 719.83 | 21.15 | 226.67 | 21.06 | 226.67 | 21.01 |
December | 744.00 | 20.69 | 542.67 | 20.63 | 542.67 | 20.60 |
Annual Sum or Average | 7995.17 | 21.39 | 2531.50 | 21.34 | 2457.50 | 21.29 |
Minimum of Months | 579.50 | 20.55 | 65.50 | 20.51 | 49.00 | 20.50 |
Maximum of Months | 744.00 | 21.88 | 630.00 | 22.09 | 630.00 | 22.23 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.26 | 238.67 | 21.13 | 238.67 | 21.05 |
February | 669.33 | 21.36 | 134.50 | 21.26 | 134.50 | 21.19 |
March | 736.67 | 21.57 | 12.50 | 21.56 | 12.50 | 21.54 |
April | 700.50 | 21.62 | 3.33 | 21.62 | 3.33 | 21.62 |
May | 724.67 | 21.69 | 8.50 | 21.69 | 8.50 | 21.70 |
June | 666.33 | 21.65 | 18.33 | 21.68 | 18.33 | 21.71 |
July | 654.00 | 21.57 | 35.17 | 21.62 | 35.17 | 21.67 |
August | 634.50 | 21.53 | 26.00 | 21.58 | 26.00 | 21.62 |
September | 647.33 | 21.56 | 17.17 | 21.59 | 17.17 | 21.62 |
October | 701.50 | 21.53 | 28.83 | 21.54 | 27.50 | 21.55 |
November | 704.50 | 21.57 | 20.17 | 21.55 | 20.17 | 21.53 |
December | 740.33 | 21.41 | 79.50 | 21.34 | 79.50 | 21.29 |
Annual Sum or Average | 8323.67 | 21.53 | 622.67 | 21.50 | 621.33 | 21.47 |
Minimum of Months | 634.50 | 21.26 | 3.33 | 21.13 | 3.33 | 21.05 |
Maximum of Months | 744.00 | 21.69 | 238.67 | 21.69 | 238.67 | 21.71 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.17 | 21.80 | 4.50 | 21.81 | 4.50 | 21.82 |
February | 656.17 | 21.97 | 11.67 | 22.00 | 10.50 | 22.01 |
March | 648.00 | 22.21 | 47.17 | 22.30 | 13.67 | 22.33 |
April | 528.33 | 22.35 | 144.67 | 22.60 | 59.50 | 22.66 |
May | 456.83 | 22.66 | 317.00 | 22.99 | 175.50 | 23.09 |
June | 361.83 | 23.03 | 385.17 | 23.28 | 205.50 | 23.38 |
July | 406.17 | 23.20 | 478.67 | 23.34 | 287.83 | 23.43 |
August | 407.00 | 23.22 | 467.83 | 23.37 | 286.67 | 23.46 |
September | 478.17 | 22.72 | 351.00 | 23.03 | 221.67 | 23.14 |
October | 610.33 | 22.29 | 123.17 | 22.48 | 81.67 | 22.57 |
November | 672.83 | 22.12 | 39.67 | 22.19 | 29.33 | 22.23 |
December | 725.67 | 21.92 | 11.50 | 21.94 | 3.50 | 21.95 |
Annual Sum or Average | 6688.50 | 22.35 | 2382.00 | 22.65 | 1379.83 | 22.77 |
Minimum of Months | 361.83 | 21.80 | 4.50 | 21.81 | 3.50 | 21.82 |
Maximum of Months | 737.17 | 23.22 | 478.67 | 23.37 | 287.83 | 23.46 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 713.17 | 22.07 | 16.83 | 22.11 | 4.50 | 22.12 |
February | 598.50 | 22.20 | 31.50 | 22.27 | 11.17 | 22.29 |
March | 534.33 | 22.39 | 101.33 | 22.59 | 14.83 | 22.61 |
April | 382.50 | 22.53 | 226.00 | 22.92 | 60.33 | 22.99 |
May | 318.50 | 23.03 | 445.17 | 23.28 | 178.17 | 23.36 |
June | 258.50 | 23.56 | 538.33 | 23.49 | 205.50 | 23.57 |
July | 307.50 | 23.72 | 619.17 | 23.54 | 287.50 | 23.61 |
August | 306.83 | 23.76 | 614.50 | 23.56 | 286.00 | 23.64 |
September | 341.17 | 23.16 | 458.83 | 23.35 | 223.33 | 23.43 |
October | 471.17 | 22.44 | 204.17 | 22.77 | 82.50 | 22.86 |
November | 596.17 | 22.35 | 77.33 | 22.48 | 30.67 | 22.53 |
December | 685.50 | 22.20 | 29.33 | 22.26 | 3.83 | 22.26 |
Annual Sum or Average | 5513.83 | 22.60 | 3362.50 | 22.94 | 1388.33 | 23.05 |
Minimum of Months | 258.50 | 22.07 | 16.83 | 22.11 | 3.83 | 22.12 |
Maximum of Months | 713.17 | 23.76 | 619.17 | 23.56 | 287.50 | 23.64 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.50 | 23.99 | 744.00 | 23.99 | 484.50 | 23.99 |
February | 454.17 | 23.99 | 669.00 | 23.99 | 454.17 | 23.99 |
March | 531.33 | 23.99 | 744.00 | 23.99 | 531.33 | 23.99 |
April | 532.67 | 24.02 | 720.00 | 24.01 | 532.67 | 24.01 |
May | 577.83 | 24.00 | 744.00 | 24.00 | 577.83 | 24.00 |
June | 579.67 | 24.00 | 720.00 | 24.00 | 579.67 | 24.00 |
July | 614.50 | 23.99 | 744.00 | 23.99 | 614.50 | 23.99 |
August | 617.67 | 23.99 | 744.00 | 23.99 | 617.67 | 23.99 |
September | 570.17 | 24.00 | 720.00 | 24.00 | 570.17 | 24.00 |
October | 550.83 | 23.99 | 744.00 | 23.99 | 550.83 | 23.99 |
November | 511.00 | 23.99 | 720.00 | 23.99 | 511.00 | 23.99 |
December | 502.00 | 23.99 | 744.00 | 23.99 | 502.00 | 23.99 |
Annual Sum or Average | 6526.33 | 23.99 | 8757.00 | 23.99 | 6526.33 | 23.99 |
Minimum of Months | 454.17 | 23.99 | 669.00 | 23.99 | 454.17 | 23.99 |
Maximum of Months | 617.67 | 24.02 | 744.00 | 24.01 | 617.67 | 24.01 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.13 | 187.67 | 21.11 | 187.67 | 21.09 |
February | 672.00 | 21.64 | 149.50 | 21.53 | 149.50 | 21.45 |
March | 674.50 | 22.60 | 26.17 | 22.65 | 2.00 | 22.65 |
April | 431.83 | 23.11 | 131.17 | 23.30 | 31.83 | 23.32 |
May | 206.33 | 23.70 | 538.50 | 23.88 | 115.50 | 23.88 |
June | 134.67 | 23.92 | 616.33 | 23.99 | 95.83 | 23.99 |
July | 122.67 | 23.98 | 744.00 | 23.99 | 122.67 | 23.99 |
August | 130.33 | 24.00 | 744.00 | 24.00 | 130.33 | 24.00 |
September | 199.83 | 23.79 | 578.50 | 23.93 | 149.83 | 23.93 |
October | 552.67 | 22.95 | 169.00 | 23.17 | 54.33 | 23.21 |
November | 714.33 | 22.21 | 12.00 | 22.22 | 12.00 | 22.23 |
December | 744.00 | 21.37 | 46.17 | 21.35 | 46.17 | 21.33 |
Annual Sum or Average | 5327.17 | 22.31 | 3943.00 | 22.90 | 1097.67 | 22.90 |
Minimum of Months | 122.67 | 21.13 | 12.00 | 21.11 | 2.00 | 21.09 |
Maximum of Months | 744.00 | 24.00 | 744.00 | 24.00 | 187.67 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.39887 | 30.57089 | -0.1363 | 5.55971 |
February | 672.00000 | 21.87613 | 33.47576 | -0.2505 | 6.54681 |
March | 744.00000 | 21.36688 | 40.50940 | -0.3374 | 7.63487 |
April | 720.00000 | 21.14244 | 51.36476 | -0.3396 | 7.59314 |
May | 744.00000 | 21.32417 | 61.59257 | -1.4039 | 45.77676 |
June | 720.00000 | 22.09044 | 60.28566 | -1.1275 | 31.99638 |
July | 744.00000 | 22.61825 | 62.02834 | -0.9214 | 23.12555 |
August | 744.00000 | 23.18188 | 60.15608 | -0.7253 | 16.28853 |
September | 720.00000 | 23.72074 | 57.18833 | -0.5452 | 11.39196 |
October | 744.00000 | 23.83451 | 47.37277 | 0.35498 | 7.75314 |
November | 720.00000 | 23.85674 | 36.16730 | 0.28291 | 6.86508 |
December | 744.00000 | 23.47954 | 31.93963 | 0.15073 | 5.67782 |
Annual Sum or Average | 8760.00000 | 22.57855 | 47.79935 | -0.4177 | 14.75347 |
Minimum of Months | 672.00000 | 21.14244 | 30.57089 | -1.4039 | 5.55971 |
Maximum of Months | 744.00000 | 23.85674 | 62.02834 | 0.35498 | 45.77676 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.31169 | 31.81225 | -0.4171 | 9.44989 |
February | 672.00000 | 21.59203 | 33.76981 | -0.3102 | 8.40454 |
March | 744.00000 | 22.27123 | 38.48942 | -0.0636 | 6.68303 |
April | 720.00000 | 22.64436 | 47.38512 | 0.09649 | 6.56408 |
May | 744.00000 | 23.16223 | 56.08532 | -0.6741 | 15.83677 |
June | 720.00000 | 23.71895 | 55.92232 | -0.4492 | 9.93095 |
July | 744.00000 | 23.80107 | 59.43961 | -0.3791 | 8.41616 |
August | 744.00000 | 23.93061 | 59.06134 | -0.3174 | 7.23082 |
September | 720.00000 | 23.50105 | 58.68961 | -0.5090 | 11.67250 |
October | 744.00000 | 22.75814 | 50.46969 | 0.15027 | 7.19137 |
November | 720.00000 | 22.11182 | 39.56375 | -0.1006 | 6.72064 |
December | 744.00000 | 21.57567 | 34.82192 | -0.3005 | 8.21303 |
Annual Sum or Average | 8760.00000 | 22.70409 | 47.19985 | -0.2729 | 8.86473 |
Minimum of Months | 672.00000 | 21.31169 | 31.81225 | -0.6741 | 6.56408 |
Maximum of Months | 744.00000 | 23.93061 | 59.43961 | 0.15027 | 15.83677 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28719 | 32.27653 | -0.3736 | 8.22666 |
February | 672.00000 | 21.54173 | 34.10413 | -0.2913 | 7.37366 |
March | 744.00000 | 22.08028 | 39.19124 | -0.1078 | 5.94643 |
April | 720.00000 | 22.39686 | 48.30152 | 0.03378 | 5.68388 |
May | 744.00000 | 22.71961 | 57.49421 | -0.8351 | 20.43701 |
June | 720.00000 | 23.16943 | 57.48205 | -0.6643 | 14.96553 |
July | 744.00000 | 23.28478 | 60.71289 | -0.5976 | 13.08151 |
August | 744.00000 | 23.41125 | 60.39140 | -0.5517 | 11.83005 |
September | 720.00000 | 23.06905 | 59.92747 | -0.6867 | 15.57816 |
October | 744.00000 | 22.48679 | 51.32846 | 0.07762 | 5.74626 |
November | 720.00000 | 22.03820 | 40.00119 | -0.1148 | 5.86426 |
December | 744.00000 | 21.55688 | 35.14308 | -0.2759 | 7.11269 |
Annual Sum or Average | 8760.00000 | 22.42467 | 48.10673 | -0.3663 | 10.17265 |
Minimum of Months | 672.00000 | 21.28719 | 32.27653 | -0.8351 | 5.68388 |
Maximum of Months | 744.00000 | 23.41125 | 60.71289 | 0.07762 | 20.43701 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99978 | 24.30946 | 0.78817 | 18.94005 |
February | 672.00000 | 23.99976 | 26.18462 | 0.82414 | 20.24970 |
March | 744.00000 | 23.99977 | 31.51290 | 0.90078 | 23.01403 |
April | 720.00000 | 23.99983 | 40.32859 | 0.98223 | 26.14865 |
May | 744.00000 | 24.00042 | 49.39554 | 0.43880 | 10.62424 |
June | 720.00000 | 24.00006 | 50.52452 | 0.48044 | 11.42010 |
July | 744.00000 | 23.99971 | 53.75321 | 0.51136 | 11.91942 |
August | 744.00000 | 23.99974 | 53.77390 | 0.51844 | 12.11615 |
September | 720.00000 | 23.99983 | 52.55974 | 0.46965 | 11.12272 |
October | 744.00000 | 23.99977 | 43.18620 | 0.99692 | 26.67582 |
November | 720.00000 | 23.99983 | 32.16756 | 0.89510 | 22.75897 |
December | 744.00000 | 23.99981 | 27.15251 | 0.82992 | 20.40516 |
Annual Sum or Average | 8760.00000 | 23.99986 | 40.48268 | 0.71894 | 17.93163 |
Minimum of Months | 672.00000 | 23.99971 | 24.30946 | 0.43880 | 10.62424 |
Maximum of Months | 744.00000 | 24.00042 | 53.77390 | 0.99692 | 26.67582 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36128 | 34.46818 | -0.2995 | 7.37418 |
February | 672.00000 | 21.54420 | 36.41852 | -0.2185 | 6.72103 |
March | 744.00000 | 21.84869 | 42.02314 | -0.0638 | 5.84792 |
April | 720.00000 | 21.90493 | 51.92476 | 0.02255 | 5.70865 |
May | 744.00000 | 22.02494 | 61.92232 | -0.9093 | 23.34314 |
June | 720.00000 | 22.29684 | 62.44729 | -0.7793 | 18.84834 |
July | 744.00000 | 22.42114 | 65.78291 | -0.7006 | 16.30908 |
August | 744.00000 | 22.62380 | 65.20172 | -0.6176 | 13.89243 |
September | 720.00000 | 22.36149 | 64.49188 | -0.7477 | 17.95665 |
October | 744.00000 | 22.11931 | 54.63230 | 0.10208 | 6.05111 |
November | 720.00000 | 21.84284 | 42.77660 | -0.0638 | 5.87311 |
December | 744.00000 | 21.56110 | 37.51728 | -0.2010 | 6.49817 |
Annual Sum or Average | 8760.00000 | 21.99504 | 51.71758 | -0.3741 | 11.22901 |
Minimum of Months | 672.00000 | 21.36128 | 34.46818 | -0.9093 | 5.70865 |
Maximum of Months | 744.00000 | 22.62380 | 65.78291 | 0.10208 | 23.34314 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.81375 | 34.20405 | -0.2159 | 6.51978 |
February | 672.00000 | 22.04629 | 35.99534 | -0.1377 | 6.20956 |
March | 744.00000 | 22.49361 | 41.20239 | 0.02442 | 5.76820 |
April | 720.00000 | 22.67035 | 50.39576 | 0.13426 | 6.08547 |
May | 744.00000 | 22.88250 | 59.72566 | -0.7340 | 17.31018 |
June | 720.00000 | 23.19221 | 60.07035 | -0.6040 | 13.61831 |
July | 744.00000 | 23.28203 | 63.25529 | -0.5432 | 11.97424 |
August | 744.00000 | 23.38745 | 62.93130 | -0.5017 | 10.94168 |
September | 720.00000 | 23.19892 | 62.15524 | -0.5906 | 13.11117 |
October | 744.00000 | 22.84263 | 53.12422 | 0.20083 | 6.45658 |
November | 720.00000 | 22.55010 | 41.77281 | 0.04253 | 5.69494 |
December | 744.00000 | 22.15061 | 36.92833 | -0.1019 | 5.85163 |
Annual Sum or Average | 8760.00000 | 22.71253 | 50.22521 | -0.2532 | 9.14700 |
Minimum of Months | 672.00000 | 21.81375 | 34.20405 | -0.7340 | 5.69494 |
Maximum of Months | 744.00000 | 23.38745 | 63.25529 | 0.20083 | 17.31018 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90824 | 38.01843 | -0.5432 | 11.73755 |
February | 672.00000 | 21.10569 | 40.02390 | -0.4501 | 10.13147 |
March | 744.00000 | 21.50521 | 43.45672 | -0.2594 | 7.20726 |
April | 720.00000 | 21.65321 | 50.61199 | -0.1449 | 6.31935 |
May | 744.00000 | 21.73847 | 55.07209 | -1.1700 | 35.04251 |
June | 720.00000 | 21.78663 | 53.96574 | -1.1121 | 32.48088 |
July | 744.00000 | 21.79078 | 56.44771 | -1.0818 | 31.13998 |
August | 744.00000 | 21.79986 | 55.84119 | -1.0721 | 30.73844 |
September | 720.00000 | 21.74329 | 57.04006 | -1.1437 | 33.89779 |
October | 744.00000 | 21.56871 | 54.72258 | -0.1614 | 6.36903 |
November | 720.00000 | 21.41323 | 45.87944 | -0.3012 | 7.65749 |
December | 744.00000 | 21.11157 | 41.93574 | -0.4475 | 9.72400 |
Annual Sum or Average | 8760.00000 | 21.51221 | 49.46826 | -0.6588 | 18.58923 |
Minimum of Months | 672.00000 | 20.90824 | 38.01843 | -1.1700 | 6.31935 |
Maximum of Months | 744.00000 | 21.79986 | 57.04006 | -0.1449 | 35.04251 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.65731 | 38.50902 | -0.6241 | 13.79987 |
February | 672.00000 | 20.96210 | 40.32150 | -0.5077 | 11.49581 |
March | 744.00000 | 21.57688 | 43.81600 | -0.2666 | 7.45449 |
April | 720.00000 | 21.98638 | 50.64853 | -0.0867 | 6.43028 |
May | 744.00000 | 22.20645 | 55.51193 | -1.0345 | 29.47992 |
June | 720.00000 | 22.13334 | 54.52428 | -1.0068 | 28.38177 |
July | 744.00000 | 22.12272 | 57.53825 | -0.9785 | 27.20773 |
August | 744.00000 | 22.04517 | 57.07682 | -1.0036 | 28.12739 |
September | 720.00000 | 22.12286 | 58.51149 | -1.0417 | 29.68314 |
October | 744.00000 | 21.73613 | 55.74126 | -0.1466 | 6.55580 |
November | 720.00000 | 21.27429 | 46.70783 | -0.3599 | 8.48126 |
December | 744.00000 | 20.84120 | 42.66317 | -0.5334 | 11.51229 |
Annual Sum or Average | 8760.00000 | 21.64166 | 50.18443 | -0.6336 | 17.42312 |
Minimum of Months | 672.00000 | 20.65731 | 38.50902 | -1.0417 | 6.43028 |
Maximum of Months | 744.00000 | 22.20645 | 58.51149 | -0.0867 | 29.68314 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.97536 | 36.81908 | -0.5139 | 10.89756 |
February | 672.00000 | 21.16694 | 38.17635 | -0.4412 | 9.59483 |
March | 744.00000 | 21.49490 | 42.08098 | -0.3037 | 7.40225 |
April | 720.00000 | 21.83719 | 49.08975 | -0.1625 | 6.31889 |
May | 744.00000 | 22.05856 | 55.33487 | -1.1499 | 33.90085 |
June | 720.00000 | 22.02703 | 55.60325 | -1.1322 | 33.29781 |
July | 744.00000 | 22.03987 | 58.65736 | -1.1027 | 32.08751 |
August | 744.00000 | 21.95893 | 58.48063 | -1.1347 | 33.40593 |
September | 720.00000 | 22.02633 | 58.13024 | -1.1445 | 33.72312 |
October | 744.00000 | 21.65832 | 53.39194 | -0.1905 | 6.29325 |
November | 720.00000 | 21.36270 | 44.17126 | -0.3377 | 7.82044 |
December | 744.00000 | 21.12017 | 40.68362 | -0.4411 | 9.39640 |
Annual Sum or Average | 8760.00000 | 21.64592 | 49.28130 | -0.6729 | 18.73523 |
Minimum of Months | 672.00000 | 20.97536 | 36.81908 | -1.1499 | 6.29325 |
Maximum of Months | 744.00000 | 22.05856 | 58.65736 | -0.1625 | 33.90085 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.93981 | 37.94261 | -0.5367 | 11.58357 |
February | 672.00000 | 21.16168 | 39.89900 | -0.4347 | 9.88607 |
March | 744.00000 | 21.57404 | 43.22470 | -0.2486 | 7.15018 |
April | 720.00000 | 21.71669 | 50.13935 | -0.1329 | 6.30078 |
May | 744.00000 | 21.77427 | 54.20929 | -1.1562 | 34.49166 |
June | 720.00000 | 21.80657 | 53.40628 | -1.1012 | 32.07232 |
July | 744.00000 | 21.80310 | 55.76472 | -1.0726 | 30.81639 |
August | 744.00000 | 21.80884 | 55.47768 | -1.0682 | 30.62706 |
September | 720.00000 | 21.75887 | 56.52055 | -1.1387 | 33.72289 |
October | 744.00000 | 21.60963 | 54.08976 | -0.1554 | 6.36997 |
November | 720.00000 | 21.45526 | 45.74876 | -0.2934 | 7.54114 |
December | 744.00000 | 21.14331 | 41.83505 | -0.4395 | 9.54252 |
Annual Sum or Average | 8760.00000 | 21.54765 | 49.06980 | -0.6497 | 18.39437 |
Minimum of Months | 672.00000 | 20.93981 | 37.94261 | -1.1562 | 6.30078 |
Maximum of Months | 744.00000 | 21.80884 | 56.52055 | -0.1329 | 34.49166 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67967 | 38.44395 | -0.6195 | 13.66061 |
February | 672.00000 | 20.99506 | 40.23824 | -0.4967 | 11.20651 |
March | 744.00000 | 21.57777 | 43.73463 | -0.2696 | 7.32504 |
April | 720.00000 | 22.01269 | 50.25707 | -0.0825 | 6.27523 |
May | 744.00000 | 22.25402 | 54.71061 | -1.0175 | 28.92358 |
June | 720.00000 | 22.21857 | 53.95628 | -0.9773 | 27.77776 |
July | 744.00000 | 22.20968 | 56.74366 | -0.9480 | 26.76848 |
August | 744.00000 | 22.09431 | 56.66032 | -0.9883 | 27.93590 |
September | 720.00000 | 22.17181 | 57.79159 | -1.0281 | 29.36250 |
October | 744.00000 | 21.74669 | 55.16420 | -0.1472 | 6.44115 |
November | 720.00000 | 21.24694 | 46.71836 | -0.3661 | 8.39860 |
December | 744.00000 | 20.85711 | 42.59346 | -0.5284 | 11.33544 |
Annual Sum or Average | 8760.00000 | 21.67496 | 49.80259 | -0.6236 | 17.15699 |
Minimum of Months | 672.00000 | 20.67967 | 38.44395 | -1.0281 | 6.27523 |
Maximum of Months | 744.00000 | 22.25402 | 57.79159 | -0.0825 | 29.36250 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.76720 | 38.94637 | -0.6112 | 13.50011 |
February | 672.00000 | 20.98565 | 40.98961 | -0.5044 | 11.48795 |
March | 744.00000 | 21.43701 | 44.38863 | -0.2881 | 7.73849 |
April | 720.00000 | 21.62115 | 51.81053 | -0.1538 | 6.56773 |
May | 744.00000 | 21.72839 | 56.03263 | -1.1654 | 35.03337 |
June | 720.00000 | 21.78357 | 54.47265 | -1.1025 | 32.24773 |
July | 744.00000 | 21.78758 | 57.20231 | -1.0691 | 30.77305 |
August | 744.00000 | 21.79876 | 56.40449 | -1.0596 | 30.38025 |
September | 720.00000 | 21.72471 | 58.44844 | -1.1469 | 34.20796 |
October | 744.00000 | 21.50851 | 56.37771 | -0.1836 | 6.70870 |
November | 720.00000 | 21.32699 | 47.08501 | -0.3403 | 8.38421 |
December | 744.00000 | 20.96893 | 43.13314 | -0.5083 | 11.10991 |
Annual Sum or Average | 8760.00000 | 21.45528 | 50.49110 | -0.6791 | 19.05877 |
Minimum of Months | 672.00000 | 20.76720 | 38.94637 | -1.1654 | 6.56773 |
Maximum of Months | 744.00000 | 21.79876 | 58.44844 | -0.1538 | 35.03337 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54945 | 39.43123 | -0.6868 | 15.64171 |
February | 672.00000 | 20.86257 | 41.30015 | -0.5594 | 12.89105 |
March | 744.00000 | 21.49708 | 44.71771 | -0.2985 | 8.09576 |
April | 720.00000 | 21.97690 | 51.58479 | -0.0895 | 6.77858 |
May | 744.00000 | 22.20268 | 56.07037 | -1.0252 | 29.47751 |
June | 720.00000 | 22.11115 | 54.88037 | -1.0007 | 28.29651 |
July | 744.00000 | 22.09607 | 58.10835 | -0.9709 | 27.01395 |
August | 744.00000 | 22.02339 | 57.53621 | -0.9960 | 27.91608 |
September | 720.00000 | 22.07843 | 59.66941 | -1.0509 | 30.27592 |
October | 744.00000 | 21.65487 | 57.37730 | -0.1736 | 7.01770 |
November | 720.00000 | 21.15531 | 47.98557 | -0.4083 | 9.47000 |
December | 744.00000 | 20.69201 | 43.89810 | -0.5971 | 13.19646 |
Annual Sum or Average | 8760.00000 | 21.57805 | 51.09952 | -0.6557 | 18.04031 |
Minimum of Months | 672.00000 | 20.54945 | 39.43123 | -1.0509 | 6.77858 |
Maximum of Months | 744.00000 | 22.20268 | 59.66941 | -0.0895 | 30.27592 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26144 | 38.72992 | -0.4304 | 9.99066 |
February | 672.00000 | 21.37237 | 40.43104 | -0.3652 | 8.86891 |
March | 744.00000 | 21.59202 | 43.34885 | -0.2389 | 7.19239 |
April | 720.00000 | 21.66940 | 50.83000 | -0.1598 | 6.53088 |
May | 744.00000 | 21.72792 | 55.98431 | -1.2067 | 36.84668 |
June | 720.00000 | 21.77849 | 55.20713 | -1.1562 | 34.53103 |
July | 744.00000 | 21.78375 | 57.58335 | -1.1228 | 32.99658 |
August | 744.00000 | 21.79922 | 56.40527 | -1.1051 | 32.26517 |
September | 720.00000 | 21.74160 | 56.98185 | -1.1646 | 34.97739 |
October | 744.00000 | 21.63674 | 53.65646 | -0.1440 | 6.42561 |
November | 720.00000 | 21.60459 | 45.29320 | -0.2325 | 7.17105 |
December | 744.00000 | 21.41798 | 42.08058 | -0.3420 | 8.41714 |
Annual Sum or Average | 8760.00000 | 21.61655 | 49.76133 | -0.6408 | 18.91178 |
Minimum of Months | 672.00000 | 21.26144 | 38.72992 | -1.2067 | 6.42561 |
Maximum of Months | 744.00000 | 21.79922 | 57.58335 | -0.1440 | 36.84668 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.81380 | 33.93748 | -0.1833 | 6.48333 |
February | 672.00000 | 22.01027 | 35.73431 | -0.0996 | 6.24777 |
March | 744.00000 | 22.36610 | 41.14575 | 0.06357 | 6.03705 |
April | 720.00000 | 22.61170 | 50.22615 | 0.20669 | 6.71116 |
May | 744.00000 | 22.81745 | 59.49850 | -0.6135 | 13.89908 |
June | 720.00000 | 22.98776 | 60.15053 | -0.5223 | 11.66847 |
July | 744.00000 | 23.02141 | 63.46309 | -0.4805 | 10.68713 |
August | 744.00000 | 23.02777 | 63.47809 | -0.4787 | 10.69780 |
September | 720.00000 | 22.82093 | 62.85683 | -0.5914 | 13.36084 |
October | 744.00000 | 22.46328 | 53.72585 | 0.17862 | 6.48406 |
November | 720.00000 | 22.19319 | 42.10940 | 0.00901 | 5.96616 |
December | 744.00000 | 21.95329 | 36.93801 | -0.1111 | 6.12981 |
Annual Sum or Average | 8760.00000 | 22.50973 | 50.35243 | -0.2194 | 8.70987 |
Minimum of Months | 672.00000 | 21.81380 | 33.93748 | -0.6135 | 5.96616 |
Maximum of Months | 744.00000 | 23.02777 | 63.47809 | 0.20669 | 13.89908 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.12626 | 33.49314 | -0.0761 | 6.03294 |
February | 672.00000 | 22.33712 | 35.22305 | 0.00769 | 6.11571 |
March | 744.00000 | 22.68508 | 40.55352 | 0.16222 | 6.43164 |
April | 720.00000 | 22.88771 | 49.54550 | 0.29182 | 7.51821 |
May | 744.00000 | 23.06342 | 58.72442 | -0.5056 | 11.23915 |
June | 720.00000 | 23.22472 | 59.38370 | -0.4176 | 9.46888 |
July | 744.00000 | 23.25127 | 62.65684 | -0.3782 | 8.69832 |
August | 744.00000 | 23.25581 | 62.67854 | -0.3772 | 8.72976 |
September | 720.00000 | 23.06090 | 62.05320 | -0.4863 | 10.85807 |
October | 744.00000 | 22.74664 | 52.97392 | 0.26602 | 7.22595 |
November | 720.00000 | 22.53206 | 41.46511 | 0.11465 | 6.21856 |
December | 744.00000 | 22.30028 | 36.38181 | 0.00180 | 5.93095 |
Annual Sum or Average | 8760.00000 | 22.79149 | 49.67397 | -0.1173 | 7.87973 |
Minimum of Months | 672.00000 | 22.12626 | 33.49314 | -0.5056 | 5.93095 |
Maximum of Months | 744.00000 | 23.25581 | 62.67854 | 0.29182 | 11.23915 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99092 | 32.16700 | 0.98611 | 26.94432 |
February | 672.00000 | 23.99125 | 33.78364 | 1.02966 | 28.84775 |
March | 744.00000 | 23.99353 | 38.65224 | 1.11777 | 32.70538 |
April | 720.00000 | 24.01139 | 47.14844 | 1.21331 | 37.17669 |
May | 744.00000 | 23.99906 | 55.89072 | 0.75339 | 20.29607 |
June | 720.00000 | 23.99568 | 56.90323 | 0.79811 | 21.64753 |
July | 744.00000 | 23.99189 | 60.01963 | 0.83059 | 22.54944 |
August | 744.00000 | 23.99189 | 60.00651 | 0.83064 | 22.49607 |
September | 720.00000 | 23.99804 | 58.91166 | 0.77135 | 20.58188 |
October | 744.00000 | 23.99166 | 49.97371 | 1.20826 | 36.75867 |
November | 720.00000 | 23.99117 | 39.38363 | 1.09741 | 31.74060 |
December | 744.00000 | 23.99095 | 34.71198 | 1.02851 | 28.74274 |
Annual Sum or Average | 8760.00000 | 23.99477 | 47.37103 | 0.97164 | 27.52715 |
Minimum of Months | 672.00000 | 23.99092 | 32.16700 | 0.75339 | 20.29607 |
Maximum of Months | 744.00000 | 24.01139 | 60.01963 | 1.21331 | 37.17669 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00224 | 29.53920 | -0.5067 | 10.52660 |
February | 672.00000 | 21.02714 | 31.85879 | -0.4667 | 9.80374 |
March | 744.00000 | 21.17645 | 37.90533 | -0.3596 | 8.09353 |
April | 720.00000 | 21.48221 | 47.49342 | -0.2186 | 6.46363 |
May | 744.00000 | 21.92938 | 56.99460 | -1.1437 | 32.79833 |
June | 720.00000 | 22.52688 | 56.75697 | -0.9306 | 23.59363 |
July | 744.00000 | 22.72537 | 60.19423 | -0.8375 | 19.97083 |
August | 744.00000 | 22.81042 | 60.13163 | -0.8073 | 18.82626 |
September | 720.00000 | 22.33591 | 59.61306 | -0.9806 | 25.53982 |
October | 744.00000 | 21.58870 | 50.81470 | -0.1696 | 5.98650 |
November | 720.00000 | 21.17711 | 38.68147 | -0.3538 | 7.98060 |
December | 744.00000 | 21.02748 | 32.97937 | -0.4497 | 9.46477 |
Annual Sum or Average | 8760.00000 | 21.73831 | 46.99651 | -0.6029 | 14.95207 |
Minimum of Months | 672.00000 | 21.00224 | 29.53920 | -1.1437 | 5.98650 |
Maximum of Months | 744.00000 | 22.81042 | 60.19423 | -0.1696 | 32.79833 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01609 | 33.79795 | -0.4801 | 9.93874 |
February | 672.00000 | 21.17733 | 35.87410 | -0.4210 | 8.95452 |
March | 744.00000 | 21.66603 | 41.17022 | -0.2551 | 6.74254 |
April | 720.00000 | 22.16721 | 49.94364 | -0.0753 | 5.55514 |
May | 744.00000 | 22.55005 | 59.26767 | -0.9788 | 25.45348 |
June | 720.00000 | 23.03878 | 59.30985 | -0.8037 | 18.84808 |
July | 744.00000 | 23.23863 | 62.45869 | -0.7112 | 15.77691 |
August | 744.00000 | 23.28362 | 62.48069 | -0.6953 | 15.23533 |
September | 720.00000 | 22.84978 | 62.02936 | -0.8531 | 20.55741 |
October | 744.00000 | 22.05602 | 53.75427 | -0.0798 | 5.55383 |
November | 720.00000 | 21.39773 | 42.47059 | -0.3161 | 7.38513 |
December | 744.00000 | 21.07751 | 37.10683 | -0.4357 | 9.19085 |
Annual Sum or Average | 8760.00000 | 22.13177 | 50.04987 | -0.5095 | 12.45409 |
Minimum of Months | 672.00000 | 21.01609 | 33.79795 | -0.9788 | 5.55383 |
Maximum of Months | 744.00000 | 23.28362 | 62.48069 | -0.0753 | 25.45348 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.12991 | 33.27047 | -0.4611 | 9.75673 |
February | 672.00000 | 21.64300 | 34.77209 | -0.3147 | 8.07796 |
March | 744.00000 | 22.71079 | 38.86340 | -0.0065 | 5.95620 |
April | 720.00000 | 23.42600 | 46.45886 | 0.22908 | 6.85763 |
May | 744.00000 | 23.88367 | 54.52258 | -0.5103 | 10.72695 |
June | 720.00000 | 23.98251 | 54.76275 | -0.4476 | 9.31308 |
July | 744.00000 | 23.99269 | 58.02724 | -0.4118 | 8.54808 |
August | 744.00000 | 23.99952 | 57.94794 | -0.4064 | 8.44918 |
September | 720.00000 | 23.90873 | 57.76525 | -0.4747 | 9.88153 |
October | 744.00000 | 23.18687 | 50.50776 | 0.19118 | 6.64335 |
November | 720.00000 | 22.21892 | 40.48615 | -0.1221 | 6.22501 |
December | 744.00000 | 21.36811 | 36.28280 | -0.3672 | 8.43083 |
Annual Sum or Average | 8760.00000 | 22.96029 | 47.04081 | -0.2586 | 8.24206 |
Minimum of Months | 672.00000 | 21.12991 | 33.27047 | -0.5103 | 5.95620 |
Maximum of Months | 744.00000 | 23.99952 | 58.02724 | 0.22908 | 10.72695 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.72416 | 33.33362 | -0.3246 | 8.10357 |
February | 672.00000 | 22.37551 | 36.00965 | -0.1548 | 7.22286 |
March | 744.00000 | 23.48770 | 39.81531 | 0.13820 | 5.91054 |
April | 720.00000 | 23.85701 | 45.71857 | 0.27873 | 6.94219 |
May | 744.00000 | 23.99777 | 52.92021 | -0.5432 | 11.29640 |
June | 720.00000 | 23.99987 | 53.42369 | -0.4964 | 10.24699 |
July | 744.00000 | 23.99983 | 57.39639 | -0.4565 | 9.35790 |
August | 744.00000 | 23.99981 | 57.46259 | -0.4502 | 9.23575 |
September | 720.00000 | 23.99988 | 55.84124 | -0.4924 | 10.12690 |
October | 744.00000 | 23.89200 | 49.07981 | 0.31911 | 7.29675 |
November | 720.00000 | 23.49523 | 40.41248 | 0.14834 | 6.04282 |
December | 744.00000 | 22.59664 | 37.06833 | -0.0917 | 5.92186 |
Annual Sum or Average | 8760.00000 | 23.45674 | 46.60141 | -0.1777 | 8.14743 |
Minimum of Months | 672.00000 | 21.72416 | 33.33362 | -0.5432 | 5.91054 |
Maximum of Months | 744.00000 | 23.99988 | 57.46259 | 0.31911 | 11.29640 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.609312E+10 | 59537.30 | 19-JAN-22:53 | 427.92 | 0.188740E+11 | 0.00 | 0.249672E+11 | 1.87 | 3.31 | 19-JAN-22:53 | 0.00 | 0.00 |
February | 0.176482E+11 | 87955.84 | 26-FEB-16:12 | 440.69 | 0.530359E+11 | 0.00 | 0.706841E+11 | 2.09 | 3.59 | 26-FEB-16:12 | 0.00 | 0.00 |
March | 0.494763E+11 | 108311.97 | 30-MAR-18:03 | 676.27 | 0.150862E+12 | 0.00 | 0.200339E+12 | 2.86 | 3.81 | 28-MAR-18:03 | 0.00 | 0.00 |
April | 0.904365E+11 | 117188.15 | 12-APR-15:14 | 706.47 | 0.281579E+12 | 0.00 | 0.372015E+12 | 3.08 | 3.95 | 02-APR-21:52 | 0.00 | 0.00 |
May | 0.155890E+12 | 133585.11 | 30-MAY-18:03 | 744.00 | 0.506976E+12 | 0.00 | 0.662866E+12 | 3.20 | 4.23 | 30-MAY-21:51 | 0.00 | 0.00 |
June | 0.222804E+12 | 157766.27 | 28-JUN-18:03 | 720.00 | 0.757315E+12 | 0.00 | 0.980119E+12 | 3.37 | 4.36 | 22-JUN-21:52 | 0.00 | 0.00 |
July | 0.271551E+12 | 173339.55 | 08-JUL-15:13 | 744.00 | 0.947111E+12 | 0.00 | 0.121866E+13 | 3.51 | 4.36 | 27-JUL-21:54 | 0.00 | 0.00 |
August | 0.284090E+12 | 169379.74 | 18-AUG-18:05 | 744.00 | 0.100386E+13 | 0.00 | 0.128795E+13 | 3.54 | 4.32 | 07-AUG-21:54 | 0.00 | 0.00 |
September | 0.190358E+12 | 152674.04 | 07-SEP-18:03 | 720.00 | 0.658222E+12 | 0.00 | 0.848580E+12 | 3.38 | 4.27 | 27-SEP-21:53 | 0.00 | 0.00 |
October | 0.870331E+11 | 130983.95 | 18-OCT-21:52 | 707.52 | 0.287865E+12 | 0.00 | 0.374898E+12 | 3.07 | 4.26 | 18-OCT-21:52 | 0.00 | 0.00 |
November | 0.381349E+11 | 99304.24 | 05-NOV-15:13 | 632.59 | 0.117761E+12 | 0.00 | 0.155896E+12 | 2.79 | 3.97 | 27-NOV-22:53 | 0.00 | 0.00 |
December | 0.116260E+11 | 63435.07 | 12-DEC-16:13 | 451.59 | 0.356932E+11 | 0.00 | 0.473191E+11 | 1.96 | 3.45 | 13-DEC-09:53 | 0.00 | 0.00 |
Annual Sum or Average | 0.142514E+13 | 7715.05 | 0.481915E+13 | 0.00 | 0.624429E+13 | 2.90 | 0.00 | 0.00 | ||||
Minimum of Months | 0.609312E+10 | 59537.30 | 427.92 | 0.188740E+11 | 0.00 | 0.249672E+11 | 1.87 | 3.31 | 0.00 | 0.00 | ||
Maximum of Months | 0.284090E+12 | 173339.55 | 744.00 | 0.100386E+13 | 0.00 | 0.128795E+13 | 3.54 | 4.36 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.983176E+11 | 0.00 | 722.39 | 197743.24 | 09-JAN-16:11 | 0.00 | 43.54 | 59.01 | 0.57 | 0.00 | 0.10 | 0.52 | 09-JAN-16:11 |
February | 0.598622E+11 | 0.00 | 581.30 | 180186.89 | 07-FEB-09:01 | 0.00 | 44.61 | 57.86 | 0.38 | 0.00 | 0.07 | 0.48 | 07-FEB-09:01 |
March | 0.210657E+11 | 0.00 | 507.58 | 113522.27 | 22-MAR-08:62 | 0.00 | 41.78 | 54.15 | 0.10 | 0.00 | 0.02 | 0.30 | 22-MAR-08:62 |
April | 0.116939E+11 | 0.00 | 398.21 | 103510.85 | 06-APR-08:04 | 0.00 | 38.87 | 50.47 | 0.05 | 0.00 | 0.01 | 0.27 | 06-APR-08:04 |
May | 0.128719E+10 | 0.00 | 246.23 | 44565.52 | 15-MAY-08:55 | 0.00 | 33.57 | 42.26 | 0.00 | 0.00 | 0.00 | 0.12 | 15-MAY-08:55 |
June | 0.155928E+09 | 0.00 | 24.61 | 29642.17 | 11-JUN-15:17 | 0.00 | 36.29 | 37.15 | 0.00 | 0.00 | 0.00 | 0.08 | 11-JUN-15:17 |
July | 43475375.11 | 0.00 | 13.10 | 20880.24 | 29-JUL-08:58 | 0.00 | 40.52 | 40.86 | 0.00 | 0.00 | 0.00 | 0.06 | 29-JUL-08:58 |
August | 17853567.25 | 0.00 | 3.34 | 14864.53 | 25-AUG-08:56 | 0.00 | 43.83 | 43.90 | 0.00 | 0.00 | 0.00 | 0.04 | 25-AUG-08:56 |
September | 0.313023E+09 | 0.00 | 55.38 | 33152.55 | 21-SEP-08:55 | 0.00 | 44.13 | 45.38 | 0.00 | 0.00 | 0.00 | 0.09 | 21-SEP-08:55 |
October | 0.702839E+10 | 0.00 | 265.76 | 104404.64 | 26-OCT-08:03 | 0.00 | 45.57 | 50.72 | 0.04 | 0.00 | 0.01 | 0.28 | 26-OCT-08:03 |
November | 0.321390E+11 | 0.00 | 476.11 | 121864.61 | 30-NOV-16:11 | 0.00 | 45.61 | 55.47 | 0.17 | 0.00 | 0.03 | 0.32 | 30-NOV-16:11 |
December | 0.753395E+11 | 0.00 | 670.78 | 174066.02 | 25-DEC-16:11 | 0.00 | 43.71 | 58.19 | 0.41 | 0.00 | 0.07 | 0.46 | 25-DEC-16:11 |
Annual Sum or Average | 0.307264E+12 | 0.00 | 3964.79 | 0.00 | 41.82 | 49.58 | 0.14 | 0.00 | 0.03 | ||||
Minimum of Months | 17853567.25 | 0.00 | 3.34 | 14864.53 | 0.00 | 33.57 | 37.15 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.983176E+11 | 0.00 | 722.39 | 197743.24 | 0.00 | 45.61 | 59.01 | 0.57 | 0.00 | 0.10 | 0.52 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100121E+11 | 0.00 | 244.27 | 0.833602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147609.65 | 19-JAN-19:05 | 102046.30 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.332174E+11 | 0.00 | 232.68 | 0.324933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164166.36 | 28-FEB-17:00 | 164166.36 | 28-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.957897E+11 | 0.00 | 343.83 | 0.922572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 238313.42 | 30-MAR-15:19 | 238313.42 | 30-MAR-15:19 | 0.00 | 0.00 | 0.00 |
April | 0.195603E+12 | 0.00 | 501.67 | 0.172005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260385.06 | 21-APR-17:15 | 257352.35 | 13-APR-15:25 | 0.00 | 0.00 | 0.00 |
May | 0.371364E+12 | 0.00 | 686.83 | 0.278972E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 340480.70 | 30-MAY-21:08 | 279115.68 | 16-MAY-18:07 | 0.00 | 0.00 | 0.00 |
June | 0.571566E+12 | 0.00 | 702.50 | 0.389448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 398581.65 | 26-JUN-18:10 | 282760.94 | 10-JUN-18:07 | 0.00 | 0.00 | 0.00 |
July | 0.728323E+12 | 0.00 | 744.00 | 0.441507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 402359.73 | 18-JUL-20:00 | 253126.24 | 08-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.773822E+12 | 0.00 | 744.00 | 0.461850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 445917.48 | 23-AUG-21:53 | 252096.43 | 02-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.499281E+12 | 0.00 | 698.17 | 0.332986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 400097.30 | 27-SEP-18:10 | 234613.15 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.201847E+12 | 0.00 | 423.50 | 0.144752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 425022.16 | 18-OCT-19:40 | 205049.47 | 10-OCT-17:15 | 0.00 | 0.00 | 0.00 |
November | 0.742164E+11 | 0.00 | 275.79 | 0.612485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 246747.43 | 27-NOV-19:10 | 158807.45 | 27-NOV-19:10 | 0.00 | 0.00 | 0.00 |
December | 0.167323E+11 | 0.00 | 144.29 | 0.141055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190741.74 | 13-DEC-11:35 | 132816.33 | 12-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357177E+13 | 0.00 | 5741.52 | 0.242996E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100121E+11 | 0.00 | 144.29 | 0.833602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147609.65 | 102046.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.773822E+12 | 0.00 | 744.00 | 0.461850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 445917.48 | 282760.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.661162E+09 | 0.00 | 29.17 | 0.498469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13220.25 | 19-JAN-22:53 | 12205.06 | 31-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.183383E+10 | 0.00 | 83.00 | 0.181307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16173.76 | 28-FEB-16:11 | 16173.76 | 28-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.677311E+10 | 0.00 | 233.83 | 0.617131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22775.54 | 28-MAR-18:01 | 18084.25 | 30-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.136316E+11 | 0.00 | 357.67 | 0.108940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28889.99 | 30-APR-15:13 | 18441.34 | 17-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.290952E+11 | 0.00 | 515.50 | 0.191693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39091.40 | 30-MAY-21:50 | 19095.21 | 19-MAY-15:12 | 0.00 | 0.00 | 0.00 |
June | 0.433860E+11 | 0.00 | 533.67 | 0.268605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45326.50 | 29-JUN-08:03 | 20527.27 | 06-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.545047E+11 | 0.00 | 568.33 | 0.303115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 26-JUL-08:03 | 21489.75 | 08-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.560509E+11 | 0.00 | 568.33 | 0.314444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47641.65 | 11-AUG-08:03 | 20876.08 | 01-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.388569E+11 | 0.00 | 531.00 | 0.234422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45944.88 | 17-SEP-08:62 | 19670.87 | 07-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.155416E+11 | 0.00 | 294.00 | 0.952852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43943.87 | 18-OCT-21:52 | 18698.76 | 10-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.541931E+10 | 0.00 | 161.83 | 0.391187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27191.69 | 19-NOV-24:00 | 16596.50 | 05-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 0.111104E+10 | 0.00 | 48.50 | 0.885151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19299.94 | 12-DEC-13:30 | 14615.14 | 12-DEC-16:14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266865E+12 | 0.00 | 3924.83 | 0.164930E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.661162E+09 | 0.00 | 29.17 | 0.498469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13220.25 | 12205.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.560509E+11 | 0.00 | 568.33 | 0.314444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 21489.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.107381E+09 | 0.00 | 34.05 | 96310934.42 | 0.00 | 0.00 | 0.00 | 0.00 | 12391.25 | 28-JAN-16:11 | 12391.25 | 28-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.547950E+09 | 0.00 | 123.70 | 0.470338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12404.28 | 28-FEB-19:01 | 12404.28 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.218432E+10 | 0.00 | 400.14 | 0.140734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12877.33 | 28-MAR-15:11 | 12401.50 | 25-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.400273E+10 | 0.00 | 549.26 | 0.213788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13567.07 | 02-APR-15:11 | 12401.20 | 09-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.617542E+10 | 0.00 | 655.87 | 0.312365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13720.81 | 27-MAY-08:62 | 12402.32 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.830321E+10 | 0.00 | 675.41 | 0.460212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14501.11 | 29-JUN-08:62 | 11108.51 | 14-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.961915E+10 | 0.00 | 698.88 | 0.540231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15157.10 | 27-JUL-08:62 | 11029.98 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.101688E+11 | 0.00 | 708.60 | 0.575081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14580.90 | 29-AUG-08:62 | 11170.34 | 30-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.676286E+10 | 0.00 | 643.02 | 0.339140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14780.11 | 17-SEP-08:62 | 11121.30 | 05-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.331203E+10 | 0.00 | 481.68 | 0.157483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14385.92 | 01-OCT-15:12 | 12079.85 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.106488E+10 | 0.00 | 267.11 | 0.604971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13679.94 | 04-NOV-15:12 | 12405.30 | 25-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.269511E+09 | 0.00 | 83.92 | 0.167017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13017.89 | 13-DEC-16:12 | 12399.83 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.525182E+11 | 0.00 | 5321.65 | 0.287290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.107381E+09 | 0.00 | 34.05 | 96310934.42 | 0.00 | 0.00 | 0.00 | 0.00 | 12391.25 | 11029.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101688E+11 | 0.00 | 708.60 | 0.575081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15157.10 | 12405.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8936544.89 | 0.00 | 3.75 | 6933000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 4052.70 | 18-JAN-16:14 | 3151.40 | 12-JAN-16:14 | 0.00 | 0.00 | 0.00 |
February | 0.111656E+09 | 0.00 | 51.88 | 80051945.29 | 0.00 | 0.00 | 0.00 | 0.00 | 11593.95 | 24-FEB-19:01 | 11593.95 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.958665E+09 | 0.00 | 230.75 | 0.513535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12627.69 | 28-MAR-18:01 | 12268.06 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.259480E+10 | 0.00 | 394.03 | 0.126642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13607.60 | 02-APR-15:11 | 12793.22 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.481240E+10 | 0.00 | 483.96 | 0.249269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14373.29 | 07-MAY-17:42 | 12830.67 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.750250E+10 | 0.00 | 560.50 | 0.437755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15297.10 | 26-JUN-08:21 | 11063.40 | 05-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.869379E+10 | 0.00 | 585.77 | 0.510412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15350.02 | 08-JUL-07:51 | 11095.75 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.905847E+10 | 0.00 | 617.52 | 0.519861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16431.20 | 20-AUG-07:52 | 11442.53 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.508062E+10 | 0.00 | 482.06 | 0.251421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14835.83 | 17-SEP-08:52 | 11786.53 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.157299E+10 | 0.00 | 295.15 | 0.601929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14350.37 | 18-OCT-21:52 | 11579.09 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.216725E+09 | 0.00 | 106.50 | 95920364.73 | 0.00 | 0.00 | 0.00 | 0.00 | 13037.71 | 05-NOV-15:11 | 11679.51 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 37543532.41 | 0.00 | 16.78 | 22618178.99 | 0.00 | 0.00 | 0.00 | 0.00 | 11374.17 | 07-DEC-16:11 | 11374.17 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406491E+11 | 0.00 | 3828.65 | 0.222746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8936544.89 | 0.00 | 3.75 | 6933000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 4052.70 | 3151.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.905847E+10 | 0.00 | 617.52 | 0.519861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16431.20 | 12830.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.155538E+10 | 0.00 | 57.75 | 0.131057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21793.64 | 29-JAN-13:30 | 21793.64 | 29-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.562673E+10 | 0.00 | 159.29 | 0.539860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26496.81 | 26-FEB-14:15 | 26496.81 | 26-FEB-14:15 | 0.00 | 0.00 | 0.00 |
March | 0.171401E+11 | 0.00 | 513.99 | 0.118312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27289.55 | 30-MAR-13:30 | 25157.25 | 13-MAR-16:20 | 0.00 | 0.00 | 0.00 |
April | 0.202139E+11 | 0.00 | 589.97 | 0.945219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23387.88 | 12-APR-16:10 | 19382.17 | 10-APR-16:03 | 0.00 | 0.00 | 0.00 |
May | 0.270610E+11 | 0.00 | 702.25 | 0.100271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23012.41 | 30-MAY-20:20 | 12160.00 | 19-MAY-20:20 | 0.00 | 0.00 | 0.00 |
June | 0.357936E+11 | 0.00 | 707.31 | 0.144024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26393.73 | 25-JUN-08:00 | 15185.34 | 13-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.427543E+11 | 0.00 | 740.76 | 0.179690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28806.63 | 08-JUL-07:51 | 18300.37 | 08-JUL-17:30 | 0.00 | 0.00 | 0.00 |
August | 0.492840E+11 | 0.00 | 743.00 | 0.225565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31255.94 | 17-AUG-16:20 | 20864.64 | 18-AUG-16:20 | 0.00 | 0.00 | 0.00 |
September | 0.368034E+11 | 0.00 | 695.62 | 0.163723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34040.50 | 25-SEP-16:10 | 26903.28 | 24-SEP-12:40 | 0.00 | 0.00 | 0.00 |
October | 0.263357E+11 | 0.00 | 588.39 | 0.135214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36423.73 | 10-OCT-13:30 | 31273.91 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.164771E+11 | 0.00 | 478.89 | 0.126007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30580.14 | 06-NOV-13:40 | 30467.83 | 15-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.781383E+10 | 0.00 | 236.41 | 0.626940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29773.50 | 12-DEC-12:30 | 29182.28 | 10-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286859E+12 | 0.00 | 6213.64 | 0.141711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.155538E+10 | 0.00 | 57.75 | 0.131057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21793.64 | 12160.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.492840E+11 | 0.00 | 743.00 | 0.225565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36423.73 | 31273.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.137083E+10 | 0.00 | 83.22 | 0.601177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80114.20 | 19-JAN-22:53 | 72809.80 | 22-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.486348E+10 | 0.00 | 175.42 | 0.295252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80675.73 | 18-FEB-09:02 | 78171.16 | 28-FEB-22:52 | 0.00 | 0.00 | 0.00 |
March | 0.139078E+11 | 0.00 | 355.89 | 0.865159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79712.88 | 29-MAR-15:11 | 78617.90 | 31-MAR-20:12 | 0.00 | 0.00 | 0.00 |
April | 0.251447E+11 | 0.00 | 374.19 | 0.147626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87357.24 | 30-APR-21:52 | 77811.71 | 09-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.393736E+11 | 0.00 | 423.31 | 0.232624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92924.26 | 07-MAY-17:42 | 81959.94 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.534035E+11 | 0.00 | 507.75 | 0.332905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97491.82 | 26-JUN-08:21 | 72615.70 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.603048E+11 | 0.00 | 537.00 | 0.371670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98785.14 | 01-JUL-08:31 | 72651.97 | 15-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.605262E+11 | 0.00 | 557.97 | 0.359761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107893.72 | 20-AUG-07:52 | 72644.95 | 13-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.399353E+11 | 0.00 | 421.74 | 0.222292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96032.97 | 17-SEP-08:52 | 72328.64 | 23-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.200297E+11 | 0.00 | 376.01 | 0.958194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95600.12 | 18-OCT-21:52 | 79015.21 | 11-OCT-21:52 | 0.00 | 0.00 | 0.00 |
November | 0.909116E+10 | 0.00 | 300.87 | 0.526582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85811.94 | 05-NOV-21:52 | 76119.73 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 0.312839E+10 | 0.00 | 160.53 | 0.158821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83186.03 | 13-DEC-21:03 | 73128.74 | 10-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331079E+12 | 0.00 | 4273.91 | 0.195329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.137083E+10 | 0.00 | 83.22 | 0.601177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79712.88 | 72328.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.605262E+11 | 0.00 | 557.97 | 0.371670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107893.72 | 81959.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 70041150.37 | 0.00 | 31.91 | 55321197.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10940.36 | 29-JAN-16:11 | 10940.36 | 29-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.594719E+09 | 0.00 | 138.99 | 0.500568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11280.06 | 28-FEB-19:01 | 11280.06 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.194581E+10 | 0.00 | 416.13 | 0.118504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11842.97 | 30-MAR-08:62 | 11277.63 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.388566E+10 | 0.00 | 575.30 | 0.204474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12418.24 | 02-APR-15:11 | 11277.85 | 09-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.635721E+10 | 0.00 | 683.87 | 0.328557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12551.74 | 27-MAY-08:62 | 11277.40 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.851637E+10 | 0.00 | 693.39 | 0.476535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13154.65 | 23-JUN-08:62 | 10165.62 | 06-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.996097E+10 | 0.00 | 711.97 | 0.569974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13808.12 | 27-JUL-08:62 | 10161.06 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.102524E+11 | 0.00 | 718.34 | 0.586134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13205.04 | 24-AUG-08:62 | 10198.26 | 12-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.682268E+10 | 0.00 | 653.15 | 0.348589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13478.59 | 17-SEP-08:62 | 10179.91 | 07-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.327318E+10 | 0.00 | 496.77 | 0.156569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13247.04 | 01-OCT-15:12 | 10428.30 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.972205E+09 | 0.00 | 267.75 | 0.537519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12411.72 | 04-NOV-15:12 | 11279.22 | 18-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.242472E+09 | 0.00 | 83.64 | 0.136003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11803.75 | 13-DEC-16:12 | 11193.40 | 10-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528937E+11 | 0.00 | 5471.20 | 0.291228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 70041150.37 | 0.00 | 31.91 | 55321197.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10940.36 | 10161.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.102524E+11 | 0.00 | 718.34 | 0.586134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13808.12 | 11280.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 10977240.63 | 0.00 | 3.25 | 9291918.28 | 0.00 | 0.00 | 0.00 | 0.00 | 6679.63 | 29-JAN-09:01 | 6679.63 | 29-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.185832E+09 | 0.00 | 57.78 | 0.132349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10697.63 | 24-FEB-09:02 | 10697.63 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.881584E+09 | 0.00 | 227.85 | 0.453476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11508.00 | 28-MAR-18:01 | 11190.38 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.257723E+10 | 0.00 | 423.34 | 0.128803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12503.48 | 02-APR-15:11 | 10829.33 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.497160E+10 | 0.00 | 510.08 | 0.261060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13179.27 | 07-MAY-17:42 | 11316.45 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.760812E+10 | 0.00 | 573.15 | 0.441804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14404.88 | 29-JUN-08:51 | 10965.25 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.892168E+10 | 0.00 | 594.82 | 0.532415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14546.60 | 23-JUL-08:51 | 10193.88 | 25-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.909330E+10 | 0.00 | 624.09 | 0.521804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15065.20 | 20-AUG-07:52 | 10480.97 | 26-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.510132E+10 | 0.00 | 500.38 | 0.255579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14057.53 | 07-SEP-08:31 | 10681.55 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.163823E+10 | 0.00 | 311.19 | 0.683334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13135.51 | 18-OCT-21:52 | 9996.11 | 20-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.234362E+09 | 0.00 | 91.70 | 0.102642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12372.94 | 05-NOV-15:11 | 9814.97 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 30791729.48 | 0.00 | 16.39 | 15851529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 6994.77 | 13-DEC-21:03 | 6222.11 | 10-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412550E+11 | 0.00 | 3934.02 | 0.228116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10977240.63 | 0.00 | 3.25 | 9291918.28 | 0.00 | 0.00 | 0.00 | 0.00 | 6679.63 | 6222.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.909330E+10 | 0.00 | 624.09 | 0.532415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15065.20 | 11316.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 17367307.96 | 0.00 | 17.81 | 15866995.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.57 | 29-JAN-16:11 | 3245.57 | 29-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.119828E+09 | 0.00 | 94.08 | 0.105404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3271.44 | 21-FEB-16:11 | 3271.44 | 21-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.503021E+09 | 0.00 | 316.23 | 0.330136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.10 | 28-MAR-15:11 | 3271.12 | 25-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.971662E+09 | 0.00 | 498.86 | 0.544791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3607.18 | 23-APR-08:62 | 3271.04 | 09-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.156734E+10 | 0.00 | 653.76 | 0.816477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3740.85 | 27-MAY-08:62 | 3272.04 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.215055E+10 | 0.00 | 674.02 | 0.119928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3992.08 | 23-JUN-08:62 | 2951.47 | 15-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.250051E+10 | 0.00 | 695.32 | 0.141149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4190.47 | 30-JUL-08:62 | 2951.33 | 26-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.264122E+10 | 0.00 | 706.50 | 0.149397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4029.87 | 29-AUG-08:62 | 2929.62 | 11-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.165678E+10 | 0.00 | 619.82 | 0.829642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4128.27 | 17-SEP-08:62 | 2918.03 | 10-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.752221E+09 | 0.00 | 411.95 | 0.372499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3899.69 | 18-OCT-08:62 | 3189.65 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.221026E+09 | 0.00 | 194.38 | 0.131415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3646.44 | 04-NOV-15:12 | 3271.51 | 18-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 51420698.49 | 0.00 | 55.15 | 32898350.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3462.11 | 13-DEC-16:12 | 3270.73 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131529E+11 | 0.00 | 4937.88 | 0.728388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 17367307.96 | 0.00 | 17.81 | 15866995.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.57 | 2918.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.264122E+10 | 0.00 | 706.50 | 0.149397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4190.47 | 3272.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2603095.04 | 0.00 | 1.51 | 1785417.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.05 | 19-JAN-09:05 | 997.19 | 13-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 18938554.86 | 0.00 | 26.24 | 13666360.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3023.49 | 24-FEB-19:01 | 3023.49 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.208446E+09 | 0.00 | 167.66 | 0.111662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3307.70 | 30-MAR-08:52 | 3230.22 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.628314E+09 | 0.00 | 366.19 | 0.320206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3618.09 | 02-APR-15:11 | 3391.98 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.126451E+10 | 0.00 | 494.15 | 0.675117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3825.47 | 07-MAY-17:42 | 3444.59 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.198355E+10 | 0.00 | 562.90 | 0.117204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4177.84 | 26-JUN-08:21 | 2932.42 | 05-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.230361E+10 | 0.00 | 586.17 | 0.136684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4141.25 | 08-JUL-07:51 | 2905.77 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.238558E+10 | 0.00 | 618.27 | 0.137799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4491.40 | 20-AUG-07:52 | 3024.47 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.126753E+10 | 0.00 | 476.35 | 0.628268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4028.12 | 17-SEP-08:52 | 3081.44 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.334894E+09 | 0.00 | 227.06 | 0.134311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3909.79 | 18-OCT-21:52 | 3042.44 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 31045205.44 | 0.00 | 50.73 | 14457970.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3454.47 | 05-NOV-21:52 | 3049.39 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 4268287.21 | 0.00 | 5.87 | 2585025.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.70 | 07-DEC-16:11 | 1612.70 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104333E+11 | 0.00 | 3583.09 | 0.581893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2603095.04 | 0.00 | 1.51 | 1785417.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.05 | 997.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.238558E+10 | 0.00 | 618.27 | 0.137799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4491.40 | 3444.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.101590E+10 | 0.00 | 159.43 | 0.908106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15136.52 | 10-JAN-16:11 | 15136.52 | 10-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.175796E+10 | 0.00 | 219.54 | 0.149318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15650.50 | 18-FEB-09:02 | 15136.31 | 26-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.416501E+10 | 0.00 | 483.08 | 0.283059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15286.33 | 30-MAR-08:62 | 15138.73 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.564220E+10 | 0.00 | 554.78 | 0.310343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16650.46 | 21-APR-18:01 | 15138.18 | 27-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.793840E+10 | 0.00 | 653.81 | 0.395976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17033.36 | 31-MAY-08:62 | 15135.64 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.104082E+11 | 0.00 | 667.38 | 0.557059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19052.38 | 29-JUN-08:62 | 13709.81 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.123722E+11 | 0.00 | 691.25 | 0.679239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19647.00 | 27-JUL-08:62 | 13706.06 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.137427E+11 | 0.00 | 703.11 | 0.800171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18983.20 | 29-AUG-08:62 | 13698.12 | 04-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.995569E+10 | 0.00 | 635.23 | 0.544298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18829.84 | 17-SEP-08:62 | 13659.22 | 05-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.654340E+10 | 0.00 | 560.86 | 0.376486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18096.45 | 18-OCT-08:62 | 15138.92 | 26-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.384311E+10 | 0.00 | 443.43 | 0.258144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16687.90 | 04-NOV-15:12 | 15138.22 | 11-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.200346E+10 | 0.00 | 264.56 | 0.159482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16003.92 | 13-DEC-16:12 | 15136.22 | 10-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793883E+11 | 0.00 | 6036.47 | 0.460438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.101590E+10 | 0.00 | 159.43 | 0.908106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15136.52 | 13659.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137427E+11 | 0.00 | 703.11 | 0.800171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19647.00 | 15138.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 373.52 | 261.11 | 112.41 | 548.92 | 342.84 | 0.00 | 0.00 | 0.00 |
February | 340.82 | 226.67 | 114.15 | 543.62 | 285.74 | 0.00 | 0.00 | 0.00 |
March | 302.82 | 153.78 | 149.04 | 538.90 | 186.73 | 0.00 | 0.00 | 0.00 |
April | 223.52 | 66.25 | 157.27 | 444.57 | 150.48 | 0.00 | 0.00 | 0.00 |
May | 182.89 | 16.39 | 166.50 | 376.33 | 94.37 | 0.00 | 0.00 | 0.00 |
June | 170.25 | 5.77 | 164.47 | 388.80 | 56.62 | 0.00 | 0.00 | 0.00 |
July | 170.42 | 7.46 | 162.95 | 406.80 | 35.65 | 0.00 | 0.00 | 0.00 |
August | 201.93 | 30.95 | 170.98 | 491.70 | 28.29 | 0.00 | 0.00 | 0.00 |
September | 227.72 | 82.50 | 145.22 | 488.80 | 76.77 | 0.00 | 0.00 | 0.00 |
October | 326.93 | 208.88 | 118.05 | 607.89 | 171.34 | 0.00 | 0.00 | 0.00 |
November | 368.07 | 246.73 | 121.33 | 614.93 | 228.82 | 0.00 | 0.00 | 0.00 |
December | 372.99 | 264.58 | 108.41 | 576.18 | 288.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.52 | 130.47 | 141.05 | 502.15 | 161.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.25 | 5.77 | 108.41 | 376.33 | 28.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.52 | 264.58 | 170.98 | 614.93 | 342.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1051.82 | 735.28 | 316.54 | 1544.91 | 963.20 | 0.00 | 0.00 | 0.00 |
February | 959.73 | 638.28 | 321.45 | 1535.26 | 798.96 | 0.00 | 0.00 | 0.00 |
March | 852.73 | 433.04 | 419.69 | 1538.24 | 502.98 | 0.00 | 0.00 | 0.00 |
April | 629.41 | 186.54 | 442.87 | 1286.24 | 389.33 | 0.00 | 0.00 | 0.00 |
May | 515.01 | 46.16 | 468.85 | 1114.80 | 223.57 | 0.00 | 0.00 | 0.00 |
June | 479.40 | 16.26 | 463.14 | 1173.56 | 117.05 | 0.00 | 0.00 | 0.00 |
July | 479.88 | 21.02 | 458.87 | 1228.55 | 64.80 | 0.00 | 0.00 | 0.00 |
August | 568.63 | 87.15 | 481.48 | 1463.51 | 44.39 | 0.00 | 0.00 | 0.00 |
September | 641.26 | 232.32 | 408.94 | 1430.44 | 171.79 | 0.00 | 0.00 | 0.00 |
October | 920.61 | 588.19 | 332.42 | 1739.06 | 450.71 | 0.00 | 0.00 | 0.00 |
November | 1036.45 | 694.79 | 341.66 | 1743.90 | 626.12 | 0.00 | 0.00 | 0.00 |
December | 1050.30 | 745.04 | 305.27 | 1624.98 | 806.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.59 | 367.40 | 397.19 | 1451.75 | 428.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 479.40 | 16.26 | 305.27 | 1114.80 | 44.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1051.82 | 745.04 | 481.48 | 1743.90 | 963.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1366.38 | 955.17 | 411.21 | 2018.59 | 1327.91 | 0.00 | 0.00 | 0.00 |
February | 1246.75 | 829.17 | 417.58 | 2005.81 | 1108.75 | 0.00 | 0.00 | 0.00 |
March | 1107.75 | 562.55 | 545.20 | 2002.67 | 712.89 | 0.00 | 0.00 | 0.00 |
April | 817.64 | 242.33 | 575.31 | 1665.40 | 564.01 | 0.00 | 0.00 | 0.00 |
May | 669.03 | 59.96 | 609.07 | 1430.97 | 340.21 | 0.00 | 0.00 | 0.00 |
June | 622.77 | 21.12 | 601.65 | 1497.90 | 191.19 | 0.00 | 0.00 | 0.00 |
July | 623.40 | 27.30 | 596.09 | 1567.52 | 115.50 | 0.00 | 0.00 | 0.00 |
August | 738.68 | 113.22 | 625.46 | 1881.87 | 84.40 | 0.00 | 0.00 | 0.00 |
September | 833.03 | 301.80 | 531.23 | 1844.32 | 270.44 | 0.00 | 0.00 | 0.00 |
October | 1195.93 | 764.09 | 431.84 | 2263.19 | 647.93 | 0.00 | 0.00 | 0.00 |
November | 1346.40 | 902.57 | 443.84 | 2270.90 | 883.86 | 0.00 | 0.00 | 0.00 |
December | 1364.40 | 967.85 | 396.56 | 2119.47 | 1124.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 993.25 | 477.28 | 515.98 | 1880.36 | 611.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 622.77 | 21.12 | 396.56 | 1430.97 | 84.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1366.38 | 967.85 | 625.46 | 2270.90 | 1327.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.85 | 51.63 | 22.23 | 109.08 | 68.52 | 0.00 | 0.00 | 0.00 |
February | 67.39 | 44.82 | 22.57 | 108.04 | 56.35 | 0.00 | 0.00 | 0.00 |
March | 59.87 | 30.41 | 29.47 | 107.08 | 34.88 | 0.00 | 0.00 | 0.00 |
April | 44.19 | 13.10 | 31.10 | 88.82 | 27.05 | 0.00 | 0.00 | 0.00 |
May | 36.16 | 3.24 | 32.92 | 76.66 | 14.80 | 0.00 | 0.00 | 0.00 |
June | 33.66 | 1.14 | 32.52 | 81.96 | 6.78 | 0.00 | 0.00 | 0.00 |
July | 33.69 | 1.48 | 32.22 | 86.52 | 3.16 | 0.00 | 0.00 | 0.00 |
August | 39.93 | 6.12 | 33.81 | 103.97 | 1.53 | 0.00 | 0.00 | 0.00 |
September | 45.03 | 16.31 | 28.71 | 100.24 | 10.26 | 0.00 | 0.00 | 0.00 |
October | 64.64 | 41.30 | 23.34 | 122.04 | 30.28 | 0.00 | 0.00 | 0.00 |
November | 72.77 | 48.78 | 23.99 | 122.80 | 43.22 | 0.00 | 0.00 | 0.00 |
December | 73.75 | 52.31 | 21.43 | 114.77 | 56.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.69 | 25.80 | 27.89 | 101.82 | 29.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.66 | 1.14 | 21.43 | 76.66 | 1.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.85 | 52.31 | 33.81 | 122.80 | 68.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 57.61 | 26.56 | 31.05 | 63.18 | 141.21 | 0.00 | 0.00 | 0.00 |
February | 66.49 | 31.16 | 35.33 | 90.10 | 114.74 | 0.00 | 0.00 | 0.00 |
March | 98.15 | 47.65 | 50.50 | 158.06 | 66.85 | 0.00 | 0.00 | 0.00 |
April | 110.79 | 51.13 | 59.65 | 200.24 | 49.88 | 0.00 | 0.00 | 0.00 |
May | 111.09 | 42.46 | 68.63 | 218.54 | 27.47 | 0.00 | 0.00 | 0.00 |
June | 116.60 | 45.14 | 71.46 | 254.22 | 12.58 | 0.00 | 0.00 | 0.00 |
July | 109.71 | 40.78 | 68.92 | 248.85 | 5.85 | 0.00 | 0.00 | 0.00 |
August | 107.96 | 40.70 | 67.26 | 246.07 | 2.84 | 0.00 | 0.00 | 0.00 |
September | 88.42 | 37.34 | 51.08 | 179.30 | 19.19 | 0.00 | 0.00 | 0.00 |
October | 78.29 | 40.79 | 37.49 | 136.46 | 59.11 | 0.00 | 0.00 | 0.00 |
November | 61.66 | 27.37 | 34.29 | 92.13 | 87.36 | 0.00 | 0.00 | 0.00 |
December | 50.82 | 21.95 | 28.87 | 60.52 | 116.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.24 | 37.78 | 50.46 | 162.69 | 58.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.82 | 21.95 | 28.87 | 60.52 | 2.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.60 | 51.13 | 71.46 | 254.22 | 141.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.71 | 0.00 | 13.71 | 4.19 | 78.77 | 0.00 | 0.00 | 0.00 |
February | 15.20 | 0.00 | 15.20 | 10.93 | 63.15 | 0.00 | 0.00 | 0.00 |
March | 21.34 | 0.00 | 21.34 | 24.06 | 36.72 | 0.00 | 0.00 | 0.00 |
April | 25.81 | 0.09 | 25.72 | 40.42 | 27.35 | 0.00 | 0.00 | 0.00 |
May | 30.59 | 0.68 | 29.90 | 58.32 | 15.07 | 0.00 | 0.00 | 0.00 |
June | 33.40 | 1.67 | 31.73 | 78.63 | 6.87 | 0.00 | 0.00 | 0.00 |
July | 31.72 | 1.21 | 30.51 | 79.07 | 3.48 | 0.00 | 0.00 | 0.00 |
August | 28.44 | 0.22 | 28.23 | 72.39 | 1.71 | 0.00 | 0.00 | 0.00 |
September | 21.55 | 0.00 | 21.55 | 44.11 | 11.09 | 0.00 | 0.00 | 0.00 |
October | 16.38 | 0.00 | 16.38 | 22.48 | 32.33 | 0.00 | 0.00 | 0.00 |
November | 14.66 | 0.00 | 14.66 | 13.82 | 46.95 | 0.00 | 0.00 | 0.00 |
December | 12.67 | 0.00 | 12.67 | 5.78 | 63.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.16 | 0.32 | 21.84 | 38.00 | 32.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.67 | 0.00 | 12.67 | 4.19 | 1.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.40 | 1.67 | 31.73 | 79.07 | 78.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 57.61 | 26.56 | 31.05 | 65.49 | 139.04 | 0.00 | 0.00 | 0.00 |
February | 66.49 | 31.16 | 35.33 | 92.06 | 113.18 | 0.00 | 0.00 | 0.00 |
March | 98.15 | 47.65 | 50.50 | 159.29 | 66.75 | 0.00 | 0.00 | 0.00 |
April | 110.79 | 51.13 | 59.65 | 199.99 | 51.34 | 0.00 | 0.00 | 0.00 |
May | 111.09 | 42.46 | 68.63 | 217.02 | 29.43 | 0.00 | 0.00 | 0.00 |
June | 116.60 | 45.14 | 71.46 | 252.47 | 13.52 | 0.00 | 0.00 | 0.00 |
July | 109.71 | 40.78 | 68.92 | 247.15 | 6.59 | 0.00 | 0.00 | 0.00 |
August | 107.96 | 40.70 | 67.26 | 245.18 | 3.18 | 0.00 | 0.00 | 0.00 |
September | 88.42 | 37.34 | 51.08 | 178.78 | 20.56 | 0.00 | 0.00 | 0.00 |
October | 78.29 | 40.79 | 37.49 | 137.58 | 59.47 | 0.00 | 0.00 | 0.00 |
November | 61.66 | 27.37 | 34.29 | 94.53 | 85.95 | 0.00 | 0.00 | 0.00 |
December | 50.82 | 21.95 | 28.87 | 63.18 | 113.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.24 | 37.78 | 50.46 | 163.10 | 58.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.82 | 21.95 | 28.87 | 63.18 | 3.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.60 | 51.13 | 71.46 | 252.47 | 139.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.07 | 41.29 | 17.78 | 83.02 | 62.19 | 0.00 | 0.00 | 0.00 |
February | 53.90 | 35.85 | 18.05 | 80.25 | 58.25 | 0.00 | 0.00 | 0.00 |
March | 47.89 | 24.32 | 23.57 | 77.10 | 42.59 | 0.00 | 0.00 | 0.00 |
April | 35.35 | 10.48 | 24.87 | 62.55 | 34.85 | 0.00 | 0.00 | 0.00 |
May | 28.92 | 2.59 | 26.33 | 52.17 | 23.30 | 0.00 | 0.00 | 0.00 |
June | 26.92 | 0.91 | 26.01 | 55.03 | 14.67 | 0.00 | 0.00 | 0.00 |
July | 26.95 | 1.18 | 25.77 | 57.88 | 10.75 | 0.00 | 0.00 | 0.00 |
August | 31.93 | 4.89 | 27.04 | 71.65 | 9.32 | 0.00 | 0.00 | 0.00 |
September | 36.01 | 13.05 | 22.97 | 71.22 | 19.96 | 0.00 | 0.00 | 0.00 |
October | 51.70 | 33.03 | 18.67 | 89.64 | 39.21 | 0.00 | 0.00 | 0.00 |
November | 58.21 | 39.02 | 19.19 | 89.77 | 50.84 | 0.00 | 0.00 | 0.00 |
December | 58.98 | 41.84 | 17.14 | 84.00 | 60.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.94 | 20.63 | 22.31 | 72.83 | 35.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.92 | 0.91 | 17.14 | 52.17 | 9.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.07 | 41.84 | 27.04 | 89.77 | 62.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.97 | 0.00 | 10.97 | 2.92 | 65.58 | 0.00 | 0.00 | 0.00 |
February | 12.16 | 0.00 | 12.16 | 8.59 | 52.25 | 0.00 | 0.00 | 0.00 |
March | 17.07 | 0.00 | 17.07 | 19.88 | 29.12 | 0.00 | 0.00 | 0.00 |
April | 20.65 | 0.07 | 20.58 | 33.65 | 21.20 | 0.00 | 0.00 | 0.00 |
May | 24.47 | 0.55 | 23.93 | 48.36 | 11.26 | 0.00 | 0.00 | 0.00 |
June | 26.72 | 1.34 | 25.39 | 65.21 | 4.73 | 0.00 | 0.00 | 0.00 |
July | 25.38 | 0.97 | 24.41 | 65.78 | 2.22 | 0.00 | 0.00 | 0.00 |
August | 22.76 | 0.17 | 22.58 | 60.75 | 0.91 | 0.00 | 0.00 | 0.00 |
September | 17.25 | 0.00 | 17.24 | 36.92 | 8.14 | 0.00 | 0.00 | 0.00 |
October | 13.11 | 0.00 | 13.11 | 18.66 | 25.58 | 0.00 | 0.00 | 0.00 |
November | 11.73 | 0.00 | 11.73 | 10.96 | 38.34 | 0.00 | 0.00 | 0.00 |
December | 10.14 | 0.00 | 10.14 | 4.09 | 52.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.73 | 0.26 | 17.47 | 31.44 | 25.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.14 | 0.00 | 10.14 | 2.92 | 0.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.72 | 1.34 | 25.39 | 65.78 | 65.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.20 | 25.35 | 30.85 | 56.15 | 136.91 | 0.00 | 0.00 | 0.00 |
February | 71.11 | 38.29 | 32.82 | 92.84 | 108.57 | 0.00 | 0.00 | 0.00 |
March | 89.84 | 41.19 | 48.64 | 137.67 | 62.72 | 0.00 | 0.00 | 0.00 |
April | 108.73 | 49.96 | 58.77 | 193.29 | 46.40 | 0.00 | 0.00 | 0.00 |
May | 118.96 | 50.60 | 68.35 | 232.08 | 25.74 | 0.00 | 0.00 | 0.00 |
June | 122.92 | 51.73 | 71.19 | 266.12 | 11.68 | 0.00 | 0.00 | 0.00 |
July | 120.04 | 50.73 | 69.31 | 268.40 | 5.69 | 0.00 | 0.00 | 0.00 |
August | 110.00 | 43.97 | 66.03 | 250.41 | 2.71 | 0.00 | 0.00 | 0.00 |
September | 90.32 | 40.26 | 50.06 | 182.76 | 18.41 | 0.00 | 0.00 | 0.00 |
October | 76.80 | 40.01 | 36.78 | 130.16 | 55.70 | 0.00 | 0.00 | 0.00 |
November | 60.72 | 27.19 | 33.54 | 84.29 | 81.47 | 0.00 | 0.00 | 0.00 |
December | 52.39 | 23.51 | 28.88 | 57.39 | 109.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.92 | 40.23 | 49.70 | 163.00 | 55.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.39 | 23.51 | 28.88 | 56.15 | 2.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.92 | 51.73 | 71.19 | 268.40 | 136.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.85 | 51.63 | 22.23 | 108.76 | 68.35 | 0.00 | 0.00 | 0.00 |
February | 67.39 | 44.82 | 22.57 | 107.50 | 56.24 | 0.00 | 0.00 | 0.00 |
March | 59.87 | 30.41 | 29.47 | 106.60 | 34.59 | 0.00 | 0.00 | 0.00 |
April | 44.19 | 13.10 | 31.10 | 88.31 | 26.86 | 0.00 | 0.00 | 0.00 |
May | 36.16 | 3.24 | 32.92 | 76.14 | 14.68 | 0.00 | 0.00 | 0.00 |
June | 33.66 | 1.14 | 32.52 | 81.52 | 6.68 | 0.00 | 0.00 | 0.00 |
July | 33.69 | 1.48 | 32.22 | 86.16 | 3.12 | 0.00 | 0.00 | 0.00 |
August | 39.93 | 6.12 | 33.81 | 103.79 | 1.47 | 0.00 | 0.00 | 0.00 |
September | 45.03 | 16.31 | 28.71 | 99.98 | 10.15 | 0.00 | 0.00 | 0.00 |
October | 64.64 | 41.30 | 23.34 | 121.63 | 30.09 | 0.00 | 0.00 | 0.00 |
November | 72.77 | 48.78 | 23.99 | 122.46 | 43.05 | 0.00 | 0.00 | 0.00 |
December | 73.75 | 52.31 | 21.43 | 114.44 | 56.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.69 | 25.80 | 27.89 | 101.43 | 29.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.66 | 1.14 | 21.43 | 76.14 | 1.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.85 | 52.31 | 33.81 | 122.46 | 68.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.71 | 0.00 | 13.71 | 4.01 | 78.73 | 0.00 | 0.00 | 0.00 |
February | 15.20 | 0.00 | 15.20 | 10.63 | 63.19 | 0.00 | 0.00 | 0.00 |
March | 21.34 | 0.00 | 21.34 | 23.76 | 36.30 | 0.00 | 0.00 | 0.00 |
April | 25.81 | 0.09 | 25.72 | 39.94 | 27.03 | 0.00 | 0.00 | 0.00 |
May | 30.59 | 0.68 | 29.90 | 57.66 | 14.84 | 0.00 | 0.00 | 0.00 |
June | 33.40 | 1.67 | 31.73 | 77.91 | 6.75 | 0.00 | 0.00 | 0.00 |
July | 31.72 | 1.21 | 30.51 | 78.41 | 3.46 | 0.00 | 0.00 | 0.00 |
August | 28.44 | 0.22 | 28.23 | 72.03 | 1.65 | 0.00 | 0.00 | 0.00 |
September | 21.55 | 0.00 | 21.55 | 43.65 | 10.95 | 0.00 | 0.00 | 0.00 |
October | 16.38 | 0.00 | 16.38 | 22.04 | 31.98 | 0.00 | 0.00 | 0.00 |
November | 14.66 | 0.00 | 14.66 | 13.61 | 46.59 | 0.00 | 0.00 | 0.00 |
December | 12.67 | 0.00 | 12.67 | 5.58 | 63.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.16 | 0.32 | 21.84 | 37.59 | 31.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.67 | 0.00 | 12.67 | 4.01 | 1.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.40 | 1.67 | 31.73 | 78.41 | 78.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.20 | 25.35 | 30.85 | 57.79 | 134.03 | 0.00 | 0.00 | 0.00 |
February | 71.11 | 38.29 | 32.82 | 94.72 | 106.72 | 0.00 | 0.00 | 0.00 |
March | 89.84 | 41.19 | 48.64 | 139.31 | 62.30 | 0.00 | 0.00 | 0.00 |
April | 108.73 | 49.96 | 58.77 | 193.25 | 47.64 | 0.00 | 0.00 | 0.00 |
May | 118.96 | 50.60 | 68.35 | 230.32 | 27.51 | 0.00 | 0.00 | 0.00 |
June | 122.92 | 51.73 | 71.19 | 263.71 | 12.53 | 0.00 | 0.00 | 0.00 |
July | 120.04 | 50.73 | 69.31 | 266.00 | 6.43 | 0.00 | 0.00 | 0.00 |
August | 110.00 | 43.97 | 66.03 | 249.11 | 3.01 | 0.00 | 0.00 | 0.00 |
September | 90.32 | 40.26 | 50.06 | 181.81 | 19.66 | 0.00 | 0.00 | 0.00 |
October | 76.80 | 40.01 | 36.78 | 131.35 | 55.73 | 0.00 | 0.00 | 0.00 |
November | 60.72 | 27.19 | 33.54 | 86.91 | 79.64 | 0.00 | 0.00 | 0.00 |
December | 52.39 | 23.51 | 28.88 | 59.71 | 107.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.92 | 40.23 | 49.70 | 163.19 | 54.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.39 | 23.51 | 28.88 | 57.79 | 3.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.92 | 51.73 | 71.19 | 266.00 | 134.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 0.00 | 17.36 | 4.40 | 106.58 | 0.00 | 0.00 | 0.00 |
February | 19.25 | 0.00 | 19.25 | 13.35 | 84.81 | 0.00 | 0.00 | 0.00 |
March | 27.03 | 0.00 | 27.03 | 31.09 | 48.43 | 0.00 | 0.00 | 0.00 |
April | 32.69 | 0.11 | 32.58 | 52.66 | 36.26 | 0.00 | 0.00 | 0.00 |
May | 38.74 | 0.86 | 37.87 | 75.59 | 20.55 | 0.00 | 0.00 | 0.00 |
June | 42.30 | 2.12 | 40.18 | 99.76 | 10.90 | 0.00 | 0.00 | 0.00 |
July | 40.18 | 1.54 | 38.64 | 99.14 | 6.66 | 0.00 | 0.00 | 0.00 |
August | 36.02 | 0.27 | 35.75 | 89.92 | 4.38 | 0.00 | 0.00 | 0.00 |
September | 27.30 | 0.00 | 27.29 | 55.95 | 16.74 | 0.00 | 0.00 | 0.00 |
October | 20.75 | 0.00 | 20.75 | 28.52 | 43.79 | 0.00 | 0.00 | 0.00 |
November | 18.57 | 0.00 | 18.57 | 17.08 | 62.64 | 0.00 | 0.00 | 0.00 |
December | 16.05 | 0.00 | 16.05 | 6.15 | 85.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.07 | 0.41 | 27.65 | 47.99 | 43.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.05 | 0.00 | 16.05 | 4.40 | 4.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.30 | 2.12 | 40.18 | 99.76 | 106.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6.40 | 0.00 | 6.40 | 1.62 | 39.29 | 0.00 | 0.00 | 0.00 |
February | 7.09 | 0.00 | 7.09 | 4.92 | 31.26 | 0.00 | 0.00 | 0.00 |
March | 9.96 | 0.00 | 9.96 | 11.46 | 17.85 | 0.00 | 0.00 | 0.00 |
April | 12.05 | 0.04 | 12.01 | 19.41 | 13.37 | 0.00 | 0.00 | 0.00 |
May | 14.28 | 0.32 | 13.96 | 27.87 | 7.58 | 0.00 | 0.00 | 0.00 |
June | 15.59 | 0.78 | 14.81 | 36.78 | 4.02 | 0.00 | 0.00 | 0.00 |
July | 14.81 | 0.57 | 14.24 | 36.55 | 2.46 | 0.00 | 0.00 | 0.00 |
August | 13.28 | 0.10 | 13.18 | 33.15 | 1.61 | 0.00 | 0.00 | 0.00 |
September | 10.06 | 0.00 | 10.06 | 20.63 | 6.17 | 0.00 | 0.00 | 0.00 |
October | 7.65 | 0.00 | 7.65 | 10.51 | 16.14 | 0.00 | 0.00 | 0.00 |
November | 6.84 | 0.00 | 6.84 | 6.30 | 23.09 | 0.00 | 0.00 | 0.00 |
December | 5.92 | 0.00 | 5.92 | 2.27 | 31.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.35 | 0.15 | 10.19 | 17.69 | 16.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.92 | 0.00 | 5.92 | 1.62 | 1.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.59 | 0.78 | 14.81 | 36.78 | 39.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.46 | 24.09 | 10.37 | 50.60 | 33.29 | 0.00 | 0.00 | 0.00 |
February | 31.44 | 20.91 | 10.53 | 50.41 | 27.33 | 0.00 | 0.00 | 0.00 |
March | 27.94 | 14.19 | 13.75 | 50.50 | 16.98 | 0.00 | 0.00 | 0.00 |
April | 20.62 | 6.11 | 14.51 | 41.93 | 13.60 | 0.00 | 0.00 | 0.00 |
May | 16.87 | 1.51 | 15.36 | 36.08 | 8.00 | 0.00 | 0.00 | 0.00 |
June | 15.71 | 0.53 | 15.17 | 37.92 | 4.27 | 0.00 | 0.00 | 0.00 |
July | 15.72 | 0.69 | 15.03 | 39.59 | 2.53 | 0.00 | 0.00 | 0.00 |
August | 18.63 | 2.86 | 15.77 | 47.61 | 1.63 | 0.00 | 0.00 | 0.00 |
September | 21.01 | 7.61 | 13.40 | 46.64 | 6.13 | 0.00 | 0.00 | 0.00 |
October | 30.16 | 19.27 | 10.89 | 57.23 | 15.26 | 0.00 | 0.00 | 0.00 |
November | 33.96 | 22.76 | 11.19 | 57.71 | 20.86 | 0.00 | 0.00 | 0.00 |
December | 34.41 | 24.41 | 10.00 | 53.50 | 27.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.05 | 12.04 | 13.01 | 47.47 | 14.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.71 | 0.53 | 10.00 | 36.08 | 1.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.46 | 24.41 | 15.77 | 57.71 | 33.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.53 | 65.38 | 28.15 | 137.34 | 90.35 | 0.00 | 0.00 | 0.00 |
February | 85.34 | 56.76 | 28.58 | 136.82 | 74.17 | 0.00 | 0.00 | 0.00 |
March | 75.83 | 38.51 | 37.32 | 137.06 | 46.08 | 0.00 | 0.00 | 0.00 |
April | 55.97 | 16.59 | 39.38 | 113.79 | 36.92 | 0.00 | 0.00 | 0.00 |
May | 45.80 | 4.10 | 41.69 | 97.94 | 21.72 | 0.00 | 0.00 | 0.00 |
June | 42.63 | 1.45 | 41.18 | 102.93 | 11.59 | 0.00 | 0.00 | 0.00 |
July | 42.67 | 1.87 | 40.80 | 107.46 | 6.86 | 0.00 | 0.00 | 0.00 |
August | 50.56 | 7.75 | 42.81 | 129.24 | 4.41 | 0.00 | 0.00 | 0.00 |
September | 57.02 | 20.66 | 36.36 | 126.59 | 16.65 | 0.00 | 0.00 | 0.00 |
October | 81.86 | 52.30 | 29.56 | 155.33 | 41.42 | 0.00 | 0.00 | 0.00 |
November | 92.16 | 61.78 | 30.38 | 156.63 | 56.63 | 0.00 | 0.00 | 0.00 |
December | 93.39 | 66.25 | 27.14 | 145.21 | 74.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.99 | 32.67 | 35.32 | 128.84 | 39.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.63 | 1.45 | 27.14 | 97.94 | 4.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 93.53 | 66.25 | 42.81 | 156.63 | 90.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.85 | 51.63 | 22.23 | 109.13 | 67.52 | 0.00 | 0.00 | 0.00 |
February | 67.39 | 44.82 | 22.57 | 107.94 | 55.43 | 0.00 | 0.00 | 0.00 |
March | 59.87 | 30.41 | 29.47 | 106.67 | 34.17 | 0.00 | 0.00 | 0.00 |
April | 44.19 | 13.10 | 31.10 | 88.29 | 26.53 | 0.00 | 0.00 | 0.00 |
May | 36.16 | 3.24 | 32.92 | 76.04 | 14.46 | 0.00 | 0.00 | 0.00 |
June | 33.66 | 1.14 | 32.52 | 81.50 | 6.48 | 0.00 | 0.00 | 0.00 |
July | 33.69 | 1.48 | 32.22 | 86.06 | 2.93 | 0.00 | 0.00 | 0.00 |
August | 39.93 | 6.12 | 33.81 | 103.46 | 1.35 | 0.00 | 0.00 | 0.00 |
September | 45.03 | 16.31 | 28.71 | 99.79 | 9.85 | 0.00 | 0.00 | 0.00 |
October | 64.64 | 41.30 | 23.34 | 121.64 | 29.58 | 0.00 | 0.00 | 0.00 |
November | 72.77 | 48.78 | 23.99 | 122.63 | 42.38 | 0.00 | 0.00 | 0.00 |
December | 73.75 | 52.31 | 21.43 | 114.79 | 55.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.69 | 25.80 | 27.89 | 101.48 | 28.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.66 | 1.14 | 21.43 | 76.04 | 1.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.85 | 52.31 | 33.81 | 122.63 | 67.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 57.61 | 26.56 | 31.05 | 63.52 | 138.97 | 0.00 | 0.00 | 0.00 |
February | 66.49 | 31.16 | 35.33 | 90.17 | 112.64 | 0.00 | 0.00 | 0.00 |
March | 98.15 | 47.65 | 50.50 | 157.42 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 110.79 | 51.13 | 59.65 | 199.14 | 48.87 | 0.00 | 0.00 | 0.00 |
May | 111.09 | 42.46 | 68.63 | 217.07 | 26.81 | 0.00 | 0.00 | 0.00 |
June | 116.60 | 45.14 | 71.46 | 252.76 | 11.97 | 0.00 | 0.00 | 0.00 |
July | 109.71 | 40.78 | 68.92 | 247.60 | 5.42 | 0.00 | 0.00 | 0.00 |
August | 107.96 | 40.70 | 67.26 | 244.89 | 2.51 | 0.00 | 0.00 | 0.00 |
September | 88.42 | 37.34 | 51.08 | 178.51 | 18.36 | 0.00 | 0.00 | 0.00 |
October | 78.29 | 40.79 | 37.49 | 136.02 | 57.58 | 0.00 | 0.00 | 0.00 |
November | 61.66 | 27.37 | 34.29 | 92.10 | 85.45 | 0.00 | 0.00 | 0.00 |
December | 50.82 | 21.95 | 28.87 | 60.95 | 113.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.24 | 37.78 | 50.46 | 162.06 | 57.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.82 | 21.95 | 28.87 | 60.95 | 2.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.60 | 51.13 | 71.46 | 252.76 | 138.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.71 | 0.00 | 13.71 | 4.41 | 77.52 | 0.00 | 0.00 | 0.00 |
February | 15.20 | 0.00 | 15.20 | 11.16 | 61.99 | 0.00 | 0.00 | 0.00 |
March | 21.34 | 0.00 | 21.34 | 24.19 | 35.96 | 0.00 | 0.00 | 0.00 |
April | 25.81 | 0.09 | 25.72 | 40.16 | 27.03 | 0.00 | 0.00 | 0.00 |
May | 30.59 | 0.68 | 29.90 | 57.80 | 14.92 | 0.00 | 0.00 | 0.00 |
June | 33.40 | 1.67 | 31.73 | 78.22 | 6.63 | 0.00 | 0.00 | 0.00 |
July | 31.72 | 1.21 | 30.51 | 78.66 | 3.29 | 0.00 | 0.00 | 0.00 |
August | 28.44 | 0.22 | 28.23 | 72.07 | 1.52 | 0.00 | 0.00 | 0.00 |
September | 21.55 | 0.00 | 21.55 | 43.97 | 10.67 | 0.00 | 0.00 | 0.00 |
October | 16.38 | 0.00 | 16.38 | 22.65 | 31.50 | 0.00 | 0.00 | 0.00 |
November | 14.66 | 0.00 | 14.66 | 14.17 | 45.78 | 0.00 | 0.00 | 0.00 |
December | 12.67 | 0.00 | 12.67 | 6.18 | 61.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.16 | 0.32 | 21.84 | 37.95 | 31.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.67 | 0.00 | 12.67 | 4.41 | 1.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.40 | 1.67 | 31.73 | 78.66 | 77.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 57.61 | 26.56 | 31.05 | 65.87 | 136.98 | 0.00 | 0.00 | 0.00 |
February | 66.49 | 31.16 | 35.33 | 92.21 | 111.17 | 0.00 | 0.00 | 0.00 |
March | 98.15 | 47.65 | 50.50 | 158.82 | 65.29 | 0.00 | 0.00 | 0.00 |
April | 110.79 | 51.13 | 59.65 | 198.77 | 50.67 | 0.00 | 0.00 | 0.00 |
May | 111.09 | 42.46 | 68.63 | 215.41 | 29.05 | 0.00 | 0.00 | 0.00 |
June | 116.60 | 45.14 | 71.46 | 251.04 | 12.97 | 0.00 | 0.00 | 0.00 |
July | 109.71 | 40.78 | 68.92 | 245.91 | 6.18 | 0.00 | 0.00 | 0.00 |
August | 107.96 | 40.70 | 67.26 | 244.03 | 2.83 | 0.00 | 0.00 | 0.00 |
September | 88.42 | 37.34 | 51.08 | 178.02 | 19.76 | 0.00 | 0.00 | 0.00 |
October | 78.29 | 40.79 | 37.49 | 137.32 | 57.92 | 0.00 | 0.00 | 0.00 |
November | 61.66 | 27.37 | 34.29 | 94.85 | 83.85 | 0.00 | 0.00 | 0.00 |
December | 50.82 | 21.95 | 28.87 | 63.84 | 111.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.24 | 37.78 | 50.46 | 162.55 | 57.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.82 | 21.95 | 28.87 | 63.84 | 2.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.60 | 51.13 | 71.46 | 251.04 | 136.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.31 | 75.72 | 32.60 | 155.67 | 102.81 | 0.00 | 0.00 | 0.00 |
February | 98.83 | 65.73 | 33.10 | 154.94 | 84.25 | 0.00 | 0.00 | 0.00 |
March | 87.81 | 44.59 | 43.22 | 155.02 | 50.78 | 0.00 | 0.00 | 0.00 |
April | 64.81 | 19.21 | 45.60 | 129.71 | 38.35 | 0.00 | 0.00 | 0.00 |
May | 53.03 | 4.75 | 48.28 | 112.91 | 20.31 | 0.00 | 0.00 | 0.00 |
June | 49.37 | 1.67 | 47.69 | 121.79 | 8.69 | 0.00 | 0.00 | 0.00 |
July | 49.42 | 2.16 | 47.25 | 128.69 | 3.77 | 0.00 | 0.00 | 0.00 |
August | 58.56 | 8.97 | 49.58 | 154.05 | 1.63 | 0.00 | 0.00 | 0.00 |
September | 66.03 | 23.92 | 42.11 | 147.03 | 14.01 | 0.00 | 0.00 | 0.00 |
October | 94.80 | 60.57 | 34.23 | 177.08 | 44.19 | 0.00 | 0.00 | 0.00 |
November | 106.73 | 71.55 | 35.18 | 176.92 | 64.47 | 0.00 | 0.00 | 0.00 |
December | 108.16 | 76.72 | 31.43 | 164.16 | 84.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.73 | 37.83 | 40.90 | 148.16 | 42.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.37 | 1.67 | 31.43 | 112.91 | 1.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.31 | 76.72 | 49.58 | 177.08 | 102.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.97 | 0.00 | 95.97 | 25.09 | 575.36 | 0.00 | 0.00 | 0.00 |
February | 106.37 | 0.00 | 106.37 | 75.69 | 461.24 | 0.00 | 0.00 | 0.00 |
March | 149.37 | 0.00 | 149.37 | 176.73 | 263.60 | 0.00 | 0.00 | 0.00 |
April | 180.68 | 0.62 | 180.06 | 300.61 | 194.41 | 0.00 | 0.00 | 0.00 |
May | 214.10 | 4.77 | 209.32 | 430.96 | 108.88 | 0.00 | 0.00 | 0.00 |
June | 233.80 | 11.72 | 222.08 | 574.43 | 53.97 | 0.00 | 0.00 | 0.00 |
July | 222.06 | 8.50 | 213.56 | 576.90 | 30.20 | 0.00 | 0.00 | 0.00 |
August | 199.08 | 1.51 | 197.57 | 528.31 | 17.53 | 0.00 | 0.00 | 0.00 |
September | 150.88 | 0.03 | 150.85 | 330.27 | 81.11 | 0.00 | 0.00 | 0.00 |
October | 114.66 | 0.00 | 114.66 | 167.72 | 231.72 | 0.00 | 0.00 | 0.00 |
November | 102.62 | 0.00 | 102.62 | 97.97 | 339.52 | 0.00 | 0.00 | 0.00 |
December | 88.71 | 0.00 | 88.71 | 35.47 | 461.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.12 | 2.27 | 152.85 | 277.79 | 233.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.71 | 0.00 | 88.71 | 25.09 | 17.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 233.80 | 11.72 | 222.08 | 576.90 | 575.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.97 | 0.00 | 95.97 | 22.63 | 597.28 | 0.00 | 0.00 | 0.00 |
February | 106.37 | 0.00 | 106.37 | 71.45 | 481.15 | 0.00 | 0.00 | 0.00 |
March | 149.37 | 0.00 | 149.37 | 168.71 | 277.11 | 0.00 | 0.00 | 0.00 |
April | 180.68 | 0.62 | 180.06 | 291.78 | 203.89 | 0.00 | 0.00 | 0.00 |
May | 214.10 | 4.77 | 209.32 | 421.36 | 115.61 | 0.00 | 0.00 | 0.00 |
June | 233.80 | 11.72 | 222.08 | 563.50 | 58.89 | 0.00 | 0.00 | 0.00 |
July | 222.06 | 8.50 | 213.56 | 565.53 | 34.22 | 0.00 | 0.00 | 0.00 |
August | 199.08 | 1.51 | 197.57 | 516.71 | 21.21 | 0.00 | 0.00 | 0.00 |
September | 150.88 | 0.03 | 150.85 | 321.20 | 87.91 | 0.00 | 0.00 | 0.00 |
October | 114.66 | 0.00 | 114.66 | 160.96 | 243.87 | 0.00 | 0.00 | 0.00 |
November | 102.62 | 0.00 | 102.62 | 91.85 | 356.41 | 0.00 | 0.00 | 0.00 |
December | 88.71 | 0.00 | 88.71 | 31.52 | 483.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.12 | 2.27 | 152.85 | 270.03 | 245.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.71 | 0.00 | 88.71 | 22.63 | 21.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 233.80 | 11.72 | 222.08 | 565.53 | 597.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.71 | 0.00 | 13.71 | 16.20 | 59.01 | 0.00 | 0.00 | 0.00 |
February | 15.20 | 0.00 | 15.20 | 29.30 | 47.37 | 0.00 | 0.00 | 0.00 |
March | 21.34 | 0.00 | 21.34 | 55.15 | 27.32 | 0.00 | 0.00 | 0.00 |
April | 25.81 | 0.09 | 25.72 | 79.11 | 21.01 | 0.00 | 0.00 | 0.00 |
May | 30.59 | 0.68 | 29.90 | 103.65 | 12.64 | 0.00 | 0.00 | 0.00 |
June | 33.40 | 1.67 | 31.73 | 127.44 | 6.87 | 0.00 | 0.00 | 0.00 |
July | 31.72 | 1.21 | 30.51 | 128.93 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 28.44 | 0.22 | 28.23 | 122.19 | 2.37 | 0.00 | 0.00 | 0.00 |
September | 21.55 | 0.00 | 21.55 | 88.92 | 8.30 | 0.00 | 0.00 | 0.00 |
October | 16.38 | 0.00 | 16.38 | 54.49 | 22.19 | 0.00 | 0.00 | 0.00 |
November | 14.66 | 0.00 | 14.66 | 38.66 | 33.84 | 0.00 | 0.00 | 0.00 |
December | 12.67 | 0.00 | 12.67 | 22.52 | 46.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.16 | 0.32 | 21.84 | 72.44 | 24.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.67 | 0.00 | 12.67 | 16.20 | 2.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.40 | 1.67 | 31.73 | 128.93 | 59.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.40 | 50.69 | 61.70 | 178.20 | 208.96 | 0.00 | 0.00 | 0.00 |
February | 142.21 | 76.57 | 65.64 | 274.32 | 167.46 | 0.00 | 0.00 | 0.00 |
March | 179.66 | 82.38 | 97.28 | 406.46 | 100.05 | 0.00 | 0.00 | 0.00 |
April | 217.44 | 99.91 | 117.53 | 539.16 | 77.94 | 0.00 | 0.00 | 0.00 |
May | 237.90 | 101.20 | 136.70 | 633.43 | 47.38 | 0.00 | 0.00 | 0.00 |
June | 245.82 | 103.45 | 142.38 | 713.57 | 25.81 | 0.00 | 0.00 | 0.00 |
July | 240.05 | 101.45 | 138.61 | 720.84 | 14.53 | 0.00 | 0.00 | 0.00 |
August | 219.99 | 87.94 | 132.05 | 685.59 | 8.92 | 0.00 | 0.00 | 0.00 |
September | 180.62 | 80.51 | 100.11 | 535.05 | 31.15 | 0.00 | 0.00 | 0.00 |
October | 153.58 | 80.02 | 73.56 | 392.57 | 82.02 | 0.00 | 0.00 | 0.00 |
November | 121.44 | 54.37 | 67.07 | 280.22 | 122.01 | 0.00 | 0.00 | 0.00 |
December | 104.78 | 47.02 | 57.77 | 198.52 | 165.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 179.84 | 80.45 | 99.39 | 464.12 | 87.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.78 | 47.02 | 57.77 | 178.20 | 8.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 245.82 | 103.45 | 142.38 | 720.84 | 208.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.85 | 51.63 | 22.23 | 131.76 | 55.18 | 0.00 | 0.00 | 0.00 |
February | 67.39 | 44.82 | 22.57 | 133.67 | 44.51 | 0.00 | 0.00 | 0.00 |
March | 59.87 | 30.41 | 29.47 | 141.17 | 26.87 | 0.00 | 0.00 | 0.00 |
April | 44.19 | 13.10 | 31.10 | 127.46 | 21.16 | 0.00 | 0.00 | 0.00 |
May | 36.16 | 3.24 | 32.92 | 120.67 | 12.69 | 0.00 | 0.00 | 0.00 |
June | 33.66 | 1.14 | 32.52 | 129.54 | 6.92 | 0.00 | 0.00 | 0.00 |
July | 33.69 | 1.48 | 32.22 | 135.32 | 3.86 | 0.00 | 0.00 | 0.00 |
August | 39.93 | 6.12 | 33.81 | 153.35 | 2.36 | 0.00 | 0.00 | 0.00 |
September | 45.03 | 16.31 | 28.71 | 145.36 | 8.27 | 0.00 | 0.00 | 0.00 |
October | 64.64 | 41.30 | 23.34 | 157.27 | 21.88 | 0.00 | 0.00 | 0.00 |
November | 72.77 | 48.78 | 23.99 | 153.60 | 32.49 | 0.00 | 0.00 | 0.00 |
December | 73.75 | 52.31 | 21.43 | 139.93 | 44.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.69 | 25.80 | 27.89 | 139.14 | 23.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.66 | 1.14 | 21.43 | 120.67 | 2.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.85 | 52.31 | 33.81 | 157.27 | 55.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 0.00 | 17.36 | 3.97 | 107.93 | 0.00 | 0.00 | 0.00 |
February | 19.25 | 0.00 | 19.25 | 11.93 | 87.77 | 0.00 | 0.00 | 0.00 |
March | 27.03 | 0.00 | 27.03 | 27.23 | 53.41 | 0.00 | 0.00 | 0.00 |
April | 32.69 | 0.11 | 32.58 | 47.18 | 41.36 | 0.00 | 0.00 | 0.00 |
May | 38.74 | 0.86 | 37.87 | 68.66 | 25.26 | 0.00 | 0.00 | 0.00 |
June | 42.30 | 2.12 | 40.18 | 93.39 | 13.85 | 0.00 | 0.00 | 0.00 |
July | 40.18 | 1.54 | 38.64 | 93.26 | 8.93 | 0.00 | 0.00 | 0.00 |
August | 36.02 | 0.27 | 35.75 | 84.25 | 6.63 | 0.00 | 0.00 | 0.00 |
September | 27.30 | 0.00 | 27.29 | 50.78 | 20.97 | 0.00 | 0.00 | 0.00 |
October | 20.75 | 0.00 | 20.75 | 24.70 | 49.36 | 0.00 | 0.00 | 0.00 |
November | 18.57 | 0.00 | 18.57 | 14.68 | 67.18 | 0.00 | 0.00 | 0.00 |
December | 16.05 | 0.00 | 16.05 | 5.27 | 87.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.07 | 0.41 | 27.65 | 43.95 | 47.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.05 | 0.00 | 16.05 | 3.97 | 6.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.30 | 2.12 | 40.18 | 93.39 | 107.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.53 | 0.00 | 15.53 | 3.55 | 96.57 | 0.00 | 0.00 | 0.00 |
February | 17.22 | 0.00 | 17.22 | 10.67 | 78.53 | 0.00 | 0.00 | 0.00 |
March | 24.18 | 0.00 | 24.18 | 24.36 | 47.78 | 0.00 | 0.00 | 0.00 |
April | 29.25 | 0.10 | 29.15 | 42.21 | 37.01 | 0.00 | 0.00 | 0.00 |
May | 34.66 | 0.77 | 33.88 | 61.43 | 22.60 | 0.00 | 0.00 | 0.00 |
June | 37.85 | 1.90 | 35.95 | 83.56 | 12.39 | 0.00 | 0.00 | 0.00 |
July | 35.95 | 1.38 | 34.57 | 83.44 | 7.99 | 0.00 | 0.00 | 0.00 |
August | 32.23 | 0.24 | 31.98 | 75.38 | 5.93 | 0.00 | 0.00 | 0.00 |
September | 24.42 | 0.00 | 24.42 | 45.44 | 18.76 | 0.00 | 0.00 | 0.00 |
October | 18.56 | 0.00 | 18.56 | 22.10 | 44.16 | 0.00 | 0.00 | 0.00 |
November | 16.61 | 0.00 | 16.61 | 13.14 | 60.11 | 0.00 | 0.00 | 0.00 |
December | 14.36 | 0.00 | 14.36 | 4.72 | 78.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.11 | 0.37 | 24.74 | 39.32 | 42.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.36 | 0.00 | 14.36 | 3.55 | 5.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.85 | 1.90 | 35.95 | 83.56 | 96.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 275.71 | 192.74 | 82.98 | 400.15 | 269.05 | 0.00 | 0.00 | 0.00 |
February | 251.57 | 167.31 | 84.26 | 395.79 | 226.47 | 0.00 | 0.00 | 0.00 |
March | 223.53 | 113.51 | 110.01 | 389.66 | 149.63 | 0.00 | 0.00 | 0.00 |
April | 164.99 | 48.90 | 116.09 | 318.27 | 124.17 | 0.00 | 0.00 | 0.00 |
May | 135.00 | 12.10 | 122.90 | 268.88 | 79.02 | 0.00 | 0.00 | 0.00 |
June | 125.67 | 4.26 | 121.40 | 285.26 | 43.65 | 0.00 | 0.00 | 0.00 |
July | 125.79 | 5.51 | 120.28 | 299.72 | 27.32 | 0.00 | 0.00 | 0.00 |
August | 149.06 | 22.85 | 126.21 | 363.91 | 19.93 | 0.00 | 0.00 | 0.00 |
September | 168.09 | 60.90 | 107.20 | 356.90 | 61.63 | 0.00 | 0.00 | 0.00 |
October | 241.32 | 154.18 | 87.14 | 443.40 | 137.46 | 0.00 | 0.00 | 0.00 |
November | 271.68 | 182.12 | 89.56 | 450.87 | 178.69 | 0.00 | 0.00 | 0.00 |
December | 275.32 | 195.30 | 80.02 | 421.67 | 223.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.42 | 96.31 | 104.12 | 366.11 | 127.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 125.67 | 4.26 | 80.02 | 268.88 | 19.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.71 | 195.30 | 126.21 | 450.87 | 269.05 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100045E+10 | 0.699365E+09 | 0.301084E+09 | 0.147023E+10 | 0.918273E+09 |
February | 0.824519E+09 | 0.548356E+09 | 0.276163E+09 | 0.131514E+10 | 0.691263E+09 |
March | 0.811084E+09 | 0.411891E+09 | 0.399193E+09 | 0.144339E+10 | 0.500130E+09 |
April | 0.579358E+09 | 0.171710E+09 | 0.407648E+09 | 0.115233E+10 | 0.390056E+09 |
May | 0.489858E+09 | 43904413.21 | 0.445953E+09 | 0.100797E+10 | 0.252770E+09 |
June | 0.441276E+09 | 14966727.38 | 0.426309E+09 | 0.100778E+10 | 0.146748E+09 |
July | 0.456445E+09 | 19989416.40 | 0.436456E+09 | 0.108958E+10 | 95480576.97 |
August | 0.540856E+09 | 82896667.40 | 0.457960E+09 | 0.131696E+10 | 75782013.81 |
September | 0.590263E+09 | 0.213845E+09 | 0.376418E+09 | 0.126697E+10 | 0.198996E+09 |
October | 0.875649E+09 | 0.559462E+09 | 0.316186E+09 | 0.162817E+10 | 0.458910E+09 |
November | 0.954026E+09 | 0.639535E+09 | 0.314490E+09 | 0.159391E+10 | 0.593102E+09 |
December | 0.999005E+09 | 0.708649E+09 | 0.290356E+09 | 0.154325E+10 | 0.772161E+09 |
Annual Sum or Average | 0.856279E+10 | 0.411457E+10 | 0.444822E+10 | 0.158357E+11 | 0.509367E+10 |
Minimum of Months | 0.441276E+09 | 14966727.38 | 0.276163E+09 | 0.100778E+10 | 75782013.81 |
Maximum of Months | 0.100045E+10 | 0.708649E+09 | 0.457960E+09 | 0.162817E+10 | 0.918273E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281720E+10 | 0.196937E+10 | 0.847832E+09 | 0.413788E+10 | 0.257985E+10 |
February | 0.232179E+10 | 0.154413E+10 | 0.777656E+09 | 0.371410E+10 | 0.193284E+10 |
March | 0.228396E+10 | 0.115986E+10 | 0.112410E+10 | 0.412003E+10 | 0.134718E+10 |
April | 0.163143E+10 | 0.483524E+09 | 0.114791E+10 | 0.333394E+10 | 0.100914E+10 |
May | 0.137941E+10 | 0.123632E+09 | 0.125577E+10 | 0.298589E+10 | 0.598797E+09 |
June | 0.124260E+10 | 42145317.48 | 0.120046E+10 | 0.304187E+10 | 0.303398E+09 |
July | 0.128532E+10 | 56288878.59 | 0.122903E+10 | 0.329054E+10 | 0.173565E+09 |
August | 0.152302E+10 | 0.233432E+09 | 0.128958E+10 | 0.391986E+10 | 0.118890E+09 |
September | 0.166214E+10 | 0.602175E+09 | 0.105997E+10 | 0.370771E+10 | 0.445283E+09 |
October | 0.246577E+10 | 0.157541E+10 | 0.890360E+09 | 0.465789E+10 | 0.120719E+10 |
November | 0.268647E+10 | 0.180089E+10 | 0.885584E+09 | 0.452020E+10 | 0.162291E+10 |
December | 0.281313E+10 | 0.199551E+10 | 0.817622E+09 | 0.435236E+10 | 0.216049E+10 |
Annual Sum or Average | 0.241122E+11 | 0.115864E+11 | 0.125259E+11 | 0.457823E+11 | 0.134995E+11 |
Minimum of Months | 0.124260E+10 | 42145317.48 | 0.777656E+09 | 0.298589E+10 | 0.118890E+09 |
Maximum of Months | 0.281720E+10 | 0.199551E+10 | 0.128958E+10 | 0.465789E+10 | 0.257985E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365970E+10 | 0.255832E+10 | 0.110138E+10 | 0.540660E+10 | 0.355669E+10 |
February | 0.301614E+10 | 0.200592E+10 | 0.101022E+10 | 0.485245E+10 | 0.268228E+10 |
March | 0.296699E+10 | 0.150672E+10 | 0.146027E+10 | 0.536395E+10 | 0.190941E+10 |
April | 0.211933E+10 | 0.628126E+09 | 0.149120E+10 | 0.431671E+10 | 0.146192E+10 |
May | 0.179193E+10 | 0.160605E+09 | 0.163132E+10 | 0.383271E+10 | 0.911225E+09 |
June | 0.161421E+10 | 54749165.92 | 0.155946E+10 | 0.388256E+10 | 0.495567E+09 |
July | 0.166970E+10 | 73122456.72 | 0.159658E+10 | 0.419845E+10 | 0.309353E+09 |
August | 0.197848E+10 | 0.303241E+09 | 0.167524E+10 | 0.504041E+10 | 0.226067E+09 |
September | 0.215922E+10 | 0.782259E+09 | 0.137696E+10 | 0.478047E+10 | 0.700985E+09 |
October | 0.320317E+10 | 0.204655E+10 | 0.115663E+10 | 0.606172E+10 | 0.173542E+10 |
November | 0.348988E+10 | 0.233946E+10 | 0.115042E+10 | 0.588618E+10 | 0.229097E+10 |
December | 0.365442E+10 | 0.259228E+10 | 0.106214E+10 | 0.567679E+10 | 0.301174E+10 |
Annual Sum or Average | 0.313232E+11 | 0.150513E+11 | 0.162718E+11 | 0.592990E+11 | 0.192916E+11 |
Minimum of Months | 0.161421E+10 | 54749165.92 | 0.101022E+10 | 0.383271E+10 | 0.226067E+09 |
Maximum of Months | 0.365970E+10 | 0.259228E+10 | 0.167524E+10 | 0.606172E+10 | 0.355669E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197806E+09 | 0.138277E+09 | 59529819.38 | 0.292163E+09 | 0.183514E+09 |
February | 0.163022E+09 | 0.108419E+09 | 54602549.62 | 0.261382E+09 | 0.136311E+09 |
March | 0.160366E+09 | 81437980.93 | 78928037.75 | 0.286815E+09 | 93417130.46 |
April | 0.114550E+09 | 33950045.46 | 80599804.00 | 0.230228E+09 | 70106099.05 |
May | 96854215.86 | 8680656.54 | 88173559.32 | 0.205335E+09 | 39646895.65 |
June | 87248841.46 | 2959179.05 | 84289662.40 | 0.212449E+09 | 17568763.44 |
July | 90247967.30 | 3952250.94 | 86295716.36 | 0.231744E+09 | 8459692.80 |
August | 0.106937E+09 | 16390094.88 | 90547387.85 | 0.278462E+09 | 4088865.65 |
September | 0.116706E+09 | 42280927.84 | 74424881.86 | 0.259810E+09 | 26581045.68 |
October | 0.173131E+09 | 0.110615E+09 | 62516065.90 | 0.326867E+09 | 81109748.55 |
November | 0.188628E+09 | 0.126447E+09 | 62180560.59 | 0.318305E+09 | 0.112037E+09 |
December | 0.197521E+09 | 0.140112E+09 | 57408680.67 | 0.307394E+09 | 0.151446E+09 |
Annual Sum or Average | 0.169302E+10 | 0.813522E+09 | 0.879497E+09 | 0.321096E+10 | 0.924286E+09 |
Minimum of Months | 87248841.46 | 2959179.05 | 54602549.62 | 0.205335E+09 | 4088865.65 |
Maximum of Months | 0.197806E+09 | 0.140112E+09 | 90547387.85 | 0.326867E+09 | 0.183514E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154303E+09 | 71131092.33 | 83172032.11 | 0.169225E+09 | 0.378225E+09 |
February | 0.160855E+09 | 75385602.55 | 85469527.82 | 0.217963E+09 | 0.277573E+09 |
March | 0.262888E+09 | 0.127615E+09 | 0.135273E+09 | 0.423341E+09 | 0.179038E+09 |
April | 0.287156E+09 | 0.132542E+09 | 0.154615E+09 | 0.519025E+09 | 0.129293E+09 |
May | 0.297554E+09 | 0.113736E+09 | 0.183818E+09 | 0.585349E+09 | 73585188.27 |
June | 0.302238E+09 | 0.117005E+09 | 0.185233E+09 | 0.658930E+09 | 32617660.79 |
July | 0.293836E+09 | 0.109228E+09 | 0.184608E+09 | 0.666526E+09 | 15680030.78 |
August | 0.289161E+09 | 0.109019E+09 | 0.180142E+09 | 0.659078E+09 | 7612851.21 |
September | 0.229194E+09 | 96793657.69 | 0.132400E+09 | 0.464743E+09 | 49731256.09 |
October | 0.209684E+09 | 0.109264E+09 | 0.100420E+09 | 0.365482E+09 | 0.158318E+09 |
November | 0.159819E+09 | 70939221.71 | 88879409.84 | 0.238796E+09 | 0.226439E+09 |
December | 0.136128E+09 | 58802334.52 | 77325822.68 | 0.162099E+09 | 0.310844E+09 |
Annual Sum or Average | 0.278282E+10 | 0.119146E+10 | 0.159136E+10 | 0.513056E+10 | 0.183896E+10 |
Minimum of Months | 0.136128E+09 | 58802334.52 | 77325822.68 | 0.162099E+09 | 7612851.21 |
Maximum of Months | 0.302238E+09 | 0.132542E+09 | 0.185233E+09 | 0.666526E+09 | 0.378225E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36721179.13 | 0.00 | 36721179.13 | 11228716.06 | 0.210975E+09 |
February | 36762972.14 | 0.00 | 36762972.14 | 26441101.80 | 0.152765E+09 |
March | 57156296.39 | 326.84 | 57155969.56 | 64449464.71 | 98351993.18 |
April | 66904111.85 | 227889.08 | 66676222.78 | 0.104778E+09 | 70900609.95 |
May | 81922035.16 | 1826942.77 | 80095092.38 | 0.156216E+09 | 40352414.90 |
June | 86576606.12 | 4338936.35 | 82237669.77 | 0.203800E+09 | 17803892.12 |
July | 84967898.63 | 3252503.14 | 81715395.49 | 0.211779E+09 | 9316020.28 |
August | 76176873.73 | 577269.49 | 75599604.23 | 0.193882E+09 | 4571601.28 |
September | 55869174.22 | 9474.23 | 55859699.99 | 0.114331E+09 | 28747146.70 |
October | 43874948.72 | 0.00 | 43874948.72 | 60200325.90 | 86583460.36 |
November | 37999798.57 | 0.00 | 37999798.57 | 35821271.70 | 0.121694E+09 |
December | 33945997.15 | 0.00 | 33945997.15 | 15490561.87 | 0.169092E+09 |
Annual Sum or Average | 0.698878E+09 | 10233341.89 | 0.688645E+09 | 0.119842E+10 | 0.101115E+10 |
Minimum of Months | 33945997.15 | 0.00 | 33945997.15 | 11228716.06 | 4571601.28 |
Maximum of Months | 86576606.12 | 4338936.35 | 82237669.77 | 0.211779E+09 | 0.210975E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154303E+09 | 71131092.33 | 83172032.11 | 0.175408E+09 | 0.372397E+09 |
February | 0.160855E+09 | 75385602.55 | 85469527.82 | 0.222708E+09 | 0.273805E+09 |
March | 0.262888E+09 | 0.127615E+09 | 0.135273E+09 | 0.426648E+09 | 0.178783E+09 |
April | 0.287156E+09 | 0.132542E+09 | 0.154615E+09 | 0.518385E+09 | 0.133077E+09 |
May | 0.297554E+09 | 0.113736E+09 | 0.183818E+09 | 0.581273E+09 | 78813915.85 |
June | 0.302238E+09 | 0.117005E+09 | 0.185233E+09 | 0.654414E+09 | 35046374.69 |
July | 0.293836E+09 | 0.109228E+09 | 0.184608E+09 | 0.661962E+09 | 17662785.38 |
August | 0.289161E+09 | 0.109019E+09 | 0.180142E+09 | 0.656683E+09 | 8527951.35 |
September | 0.229194E+09 | 96793657.69 | 0.132400E+09 | 0.463409E+09 | 53286775.75 |
October | 0.209684E+09 | 0.109264E+09 | 0.100420E+09 | 0.368494E+09 | 0.159283E+09 |
November | 0.159819E+09 | 70939221.71 | 88879409.84 | 0.245015E+09 | 0.222779E+09 |
December | 0.136128E+09 | 58802334.52 | 77325822.68 | 0.169228E+09 | 0.305129E+09 |
Annual Sum or Average | 0.278282E+10 | 0.119146E+10 | 0.159136E+10 | 0.514363E+10 | 0.183859E+10 |
Minimum of Months | 0.136128E+09 | 58802334.52 | 77325822.68 | 0.169228E+09 | 8527951.35 |
Maximum of Months | 0.302238E+09 | 0.132542E+09 | 0.185233E+09 | 0.661962E+09 | 0.372397E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158214E+09 | 0.110599E+09 | 47614386.28 | 0.222348E+09 | 0.166571E+09 |
February | 0.130392E+09 | 86718291.19 | 43673354.25 | 0.194131E+09 | 0.140922E+09 |
March | 0.128267E+09 | 65137430.67 | 63129875.37 | 0.206501E+09 | 0.114063E+09 |
April | 91621658.49 | 27154636.04 | 64467022.44 | 0.162137E+09 | 90338779.27 |
May | 77467966.40 | 6943144.43 | 70524821.97 | 0.139737E+09 | 62410800.50 |
June | 69785194.77 | 2366872.54 | 67418322.23 | 0.142630E+09 | 38030972.36 |
July | 72184018.38 | 3161172.08 | 69022846.31 | 0.155035E+09 | 28789446.21 |
August | 85532975.98 | 13109468.79 | 72423507.20 | 0.191900E+09 | 24966568.11 |
September | 93346083.74 | 33818016.78 | 59528066.96 | 0.184596E+09 | 51745959.82 |
October | 0.138478E+09 | 88474644.40 | 50002908.49 | 0.240094E+09 | 0.105014E+09 |
November | 0.150872E+09 | 0.101138E+09 | 49734557.61 | 0.232682E+09 | 0.131775E+09 |
December | 0.157985E+09 | 0.112067E+09 | 45917812.72 | 0.224987E+09 | 0.163131E+09 |
Annual Sum or Average | 0.135415E+10 | 0.650688E+09 | 0.703457E+09 | 0.229678E+10 | 0.111776E+10 |
Minimum of Months | 69785194.77 | 2366872.54 | 43673354.25 | 0.139737E+09 | 24966568.11 |
Maximum of Months | 0.158214E+09 | 0.112067E+09 | 72423507.20 | 0.240094E+09 | 0.166571E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 29380837.38 | 0.00 | 29380837.38 | 7821669.70 | 0.175643E+09 |
February | 29414276.23 | 0.00 | 29414276.23 | 20769771.86 | 0.126402E+09 |
March | 45731098.23 | 261.50 | 45730836.72 | 53233388.24 | 78001901.90 |
April | 53530384.30 | 182335.43 | 53348048.87 | 87208669.28 | 54938690.62 |
May | 65546315.51 | 1461747.95 | 64084567.55 | 0.129539E+09 | 30163167.55 |
June | 69270465.87 | 3471609.20 | 65798856.67 | 0.169014E+09 | 12272816.46 |
July | 67983329.29 | 2602347.42 | 65380981.87 | 0.176179E+09 | 5952234.20 |
August | 60949577.12 | 461876.81 | 60487700.31 | 0.162710E+09 | 2426505.22 |
September | 44701263.99 | 7580.39 | 44693683.61 | 95699614.38 | 21102216.46 |
October | 35104611.67 | 0.00 | 35104611.67 | 49967106.93 | 68515992.00 |
November | 30403868.52 | 0.00 | 30403868.52 | 28420977.03 | 99379239.27 |
December | 27160397.50 | 0.00 | 27160397.50 | 10949229.17 | 0.140689E+09 |
Annual Sum or Average | 0.559176E+09 | 8187758.70 | 0.550989E+09 | 0.991513E+09 | 0.815487E+09 |
Minimum of Months | 27160397.50 | 0.00 | 27160397.50 | 7821669.70 | 2426505.22 |
Maximum of Months | 69270465.87 | 3471609.20 | 65798856.67 | 0.176179E+09 | 0.175643E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150531E+09 | 67895236.33 | 82635433.85 | 0.150396E+09 | 0.366713E+09 |
February | 0.172028E+09 | 92626625.78 | 79401230.66 | 0.224604E+09 | 0.262659E+09 |
March | 0.240618E+09 | 0.110334E+09 | 0.130285E+09 | 0.368738E+09 | 0.167989E+09 |
April | 0.281817E+09 | 0.129489E+09 | 0.152328E+09 | 0.501016E+09 | 0.120264E+09 |
May | 0.318616E+09 | 0.135540E+09 | 0.183076E+09 | 0.621594E+09 | 68950373.89 |
June | 0.318608E+09 | 0.134074E+09 | 0.184534E+09 | 0.689774E+09 | 30285309.08 |
July | 0.321502E+09 | 0.135868E+09 | 0.185635E+09 | 0.718886E+09 | 15242399.31 |
August | 0.294627E+09 | 0.117778E+09 | 0.176849E+09 | 0.670708E+09 | 7246992.57 |
September | 0.234100E+09 | 0.104342E+09 | 0.129758E+09 | 0.473704E+09 | 47722334.33 |
October | 0.205689E+09 | 0.107168E+09 | 98521080.51 | 0.348613E+09 | 0.149179E+09 |
November | 0.157393E+09 | 70466088.82 | 86926497.78 | 0.218487E+09 | 0.211171E+09 |
December | 0.140333E+09 | 62968254.83 | 77364746.67 | 0.153725E+09 | 0.294132E+09 |
Annual Sum or Average | 0.283586E+10 | 0.126855E+10 | 0.156731E+10 | 0.514024E+10 | 0.174155E+10 |
Minimum of Months | 0.140333E+09 | 62968254.83 | 77364746.67 | 0.150396E+09 | 7246992.57 |
Maximum of Months | 0.321502E+09 | 0.135868E+09 | 0.185635E+09 | 0.718886E+09 | 0.366713E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197806E+09 | 0.138277E+09 | 59529819.38 | 0.291315E+09 | 0.183080E+09 |
February | 0.163022E+09 | 0.108419E+09 | 54602549.62 | 0.260059E+09 | 0.136046E+09 |
March | 0.160366E+09 | 81437980.93 | 78928037.75 | 0.285524E+09 | 92656740.96 |
April | 0.114550E+09 | 33950045.46 | 80599804.00 | 0.228897E+09 | 69628280.51 |
May | 96854215.86 | 8680656.54 | 88173559.32 | 0.203939E+09 | 39327706.48 |
June | 87248841.46 | 2959179.05 | 84289662.40 | 0.211311E+09 | 17302054.79 |
July | 90247967.30 | 3952250.94 | 86295716.36 | 0.230763E+09 | 8344047.73 |
August | 0.106937E+09 | 16390094.88 | 90547387.85 | 0.277983E+09 | 3948083.02 |
September | 0.116706E+09 | 42280927.84 | 74424881.86 | 0.259138E+09 | 26309622.42 |
October | 0.173131E+09 | 0.110615E+09 | 62516065.90 | 0.325782E+09 | 80586641.29 |
November | 0.188628E+09 | 0.126447E+09 | 62180560.59 | 0.317418E+09 | 0.111580E+09 |
December | 0.197521E+09 | 0.140112E+09 | 57408680.67 | 0.306526E+09 | 0.151155E+09 |
Annual Sum or Average | 0.169302E+10 | 0.813522E+09 | 0.879497E+09 | 0.319865E+10 | 0.919964E+09 |
Minimum of Months | 87248841.46 | 2959179.05 | 54602549.62 | 0.203939E+09 | 3948083.02 |
Maximum of Months | 0.197806E+09 | 0.140112E+09 | 90547387.85 | 0.325782E+09 | 0.183080E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36721179.13 | 0.00 | 36721179.13 | 10750882.76 | 0.210882E+09 |
February | 36762972.14 | 0.00 | 36762972.14 | 25709102.37 | 0.152869E+09 |
March | 57156296.39 | 326.84 | 57155969.56 | 63648185.03 | 97219506.66 |
April | 66904111.85 | 227889.08 | 66676222.78 | 0.103530E+09 | 70065979.31 |
May | 81922035.16 | 1826942.77 | 80095092.38 | 0.154444E+09 | 39750459.75 |
June | 86576606.12 | 4338936.35 | 82237669.77 | 0.201939E+09 | 17501184.70 |
July | 84967898.63 | 3252503.14 | 81715395.49 | 0.210008E+09 | 9278110.15 |
August | 76176873.73 | 577269.49 | 75599604.23 | 0.192937E+09 | 4415076.13 |
September | 55869174.22 | 9474.23 | 55859699.99 | 0.113153E+09 | 28388474.98 |
October | 43874948.72 | 0.00 | 43874948.72 | 59034937.54 | 85661843.86 |
November | 37999798.57 | 0.00 | 37999798.57 | 35283667.63 | 0.120771E+09 |
December | 33945997.15 | 0.00 | 33945997.15 | 14944080.83 | 0.168960E+09 |
Annual Sum or Average | 0.698878E+09 | 10233341.89 | 0.688645E+09 | 0.118538E+10 | 0.100576E+10 |
Minimum of Months | 33945997.15 | 0.00 | 33945997.15 | 10750882.76 | 4415076.13 |
Maximum of Months | 86576606.12 | 4338936.35 | 82237669.77 | 0.210008E+09 | 0.210882E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150531E+09 | 67895236.33 | 82635433.85 | 0.154772E+09 | 0.358976E+09 |
February | 0.172028E+09 | 92626625.78 | 79401230.66 | 0.229156E+09 | 0.258176E+09 |
March | 0.240618E+09 | 0.110334E+09 | 0.130285E+09 | 0.373120E+09 | 0.166867E+09 |
April | 0.281817E+09 | 0.129489E+09 | 0.152328E+09 | 0.500916E+09 | 0.123478E+09 |
May | 0.318616E+09 | 0.135540E+09 | 0.183076E+09 | 0.616879E+09 | 73687037.16 |
June | 0.318608E+09 | 0.134074E+09 | 0.184534E+09 | 0.683541E+09 | 32485463.00 |
July | 0.321502E+09 | 0.135868E+09 | 0.185635E+09 | 0.712467E+09 | 17219609.33 |
August | 0.294627E+09 | 0.117778E+09 | 0.176849E+09 | 0.667208E+09 | 8063034.22 |
September | 0.234100E+09 | 0.104342E+09 | 0.129758E+09 | 0.471256E+09 | 50969410.81 |
October | 0.205689E+09 | 0.107168E+09 | 98521080.51 | 0.351796E+09 | 0.149277E+09 |
November | 0.157393E+09 | 70466088.82 | 86926497.78 | 0.225278E+09 | 0.206430E+09 |
December | 0.140333E+09 | 62968254.83 | 77364746.67 | 0.159935E+09 | 0.287196E+09 |
Annual Sum or Average | 0.283586E+10 | 0.126855E+10 | 0.156731E+10 | 0.514632E+10 | 0.173282E+10 |
Minimum of Months | 0.140333E+09 | 62968254.83 | 77364746.67 | 0.154772E+09 | 8063034.22 |
Maximum of Months | 0.321502E+09 | 0.135868E+09 | 0.185635E+09 | 0.712467E+09 | 0.358976E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46505056.39 | 0.00 | 46505056.39 | 11790361.26 | 0.285462E+09 |
February | 46557984.60 | 0.00 | 46557984.60 | 32303954.95 | 0.205175E+09 |
March | 72384843.02 | 413.92 | 72384429.10 | 83267839.67 | 0.129711E+09 |
April | 84729836.25 | 288607.13 | 84441229.11 | 0.136501E+09 | 93984749.16 |
May | 0.103749E+09 | 2313707.75 | 0.101435E+09 | 0.202457E+09 | 55045430.61 |
June | 0.109644E+09 | 5494989.11 | 0.104149E+09 | 0.258588E+09 | 28248409.38 |
July | 0.107606E+09 | 4119090.01 | 0.103487E+09 | 0.265523E+09 | 17847156.39 |
August | 96473204.08 | 731075.39 | 95742128.69 | 0.240837E+09 | 11721081.44 |
September | 70754784.00 | 11998.51 | 70742785.48 | 0.145031E+09 | 43384720.33 |
October | 55564854.19 | 0.00 | 55564854.19 | 76388385.92 | 0.117292E+09 |
November | 48124347.23 | 0.00 | 48124347.23 | 44274346.79 | 0.162369E+09 |
December | 42990463.51 | 0.00 | 42990463.51 | 16460152.45 | 0.227742E+09 |
Annual Sum or Average | 0.885085E+09 | 12959881.82 | 0.872125E+09 | 0.151342E+10 | 0.137798E+10 |
Minimum of Months | 42990463.51 | 0.00 | 42990463.51 | 11790361.26 | 11721081.44 |
Maximum of Months | 0.109644E+09 | 5494989.11 | 0.104149E+09 | 0.265523E+09 | 0.285462E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 17143689.41 | 0.00 | 17143689.41 | 4346415.36 | 0.105233E+09 |
February | 17163200.94 | 0.00 | 17163200.94 | 11908575.40 | 75635816.11 |
March | 26684050.36 | 152.59 | 26683897.77 | 30695973.55 | 47816863.19 |
April | 31234926.03 | 106392.54 | 31128533.49 | 50319940.80 | 34646670.14 |
May | 38246209.94 | 852928.48 | 37393281.47 | 74633971.05 | 20292024.98 |
June | 40419247.98 | 2025680.52 | 38393567.46 | 95326133.02 | 10413533.37 |
July | 39668205.06 | 1518467.13 | 38149737.93 | 97882951.67 | 6579200.84 |
August | 35564017.66 | 269504.66 | 35294513.01 | 88782642.88 | 4320875.95 |
September | 26083143.11 | 4423.15 | 26078719.96 | 53464565.75 | 15993404.33 |
October | 20483506.02 | 0.00 | 20483506.02 | 28159922.04 | 43238780.12 |
November | 17740627.06 | 0.00 | 17740627.06 | 16321357.48 | 59856035.21 |
December | 15848064.95 | 0.00 | 15848064.95 | 6067893.76 | 83955133.81 |
Annual Sum or Average | 0.326279E+09 | 4777549.07 | 0.321501E+09 | 0.557910E+09 | 0.507981E+09 |
Minimum of Months | 15848064.95 | 0.00 | 15848064.95 | 4346415.36 | 4320875.95 |
Maximum of Months | 40419247.98 | 2025680.52 | 38393567.46 | 97882951.67 | 0.105233E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92295642.31 | 64519268.48 | 27776373.83 | 0.135529E+09 | 89158384.57 |
February | 76065394.75 | 50588065.13 | 25477329.62 | 0.121946E+09 | 66110440.02 |
March | 74826138.09 | 37998633.73 | 36827504.36 | 0.135254E+09 | 45473864.86 |
April | 53448498.16 | 15840954.40 | 37607543.75 | 0.108671E+09 | 35254947.44 |
May | 45191786.83 | 4050359.36 | 41141427.47 | 96644627.21 | 21435252.73 |
June | 40709957.84 | 1380741.02 | 39329216.82 | 98294525.65 | 11071975.51 |
July | 42109337.87 | 1844104.36 | 40265233.51 | 0.106039E+09 | 6766241.06 |
August | 49896598.52 | 7647552.23 | 42249046.29 | 0.127531E+09 | 4356226.20 |
September | 54454460.52 | 19728110.55 | 34726349.96 | 0.120893E+09 | 15900555.19 |
October | 80782397.44 | 51612653.01 | 29169744.43 | 0.153278E+09 | 40878470.24 |
November | 88012905.91 | 58999706.90 | 29013199.00 | 0.149575E+09 | 54076217.71 |
December | 92162433.21 | 65375774.15 | 26786659.06 | 0.143293E+09 | 73153590.71 |
Annual Sum or Average | 0.789956E+09 | 0.379586E+09 | 0.410370E+09 | 0.149695E+10 | 0.463636E+09 |
Minimum of Months | 40709957.84 | 1380741.02 | 25477329.62 | 96644627.21 | 4356226.20 |
Maximum of Months | 92295642.31 | 65375774.15 | 42249046.29 | 0.153278E+09 | 89158384.57 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250509E+09 | 0.175118E+09 | 75390760.12 | 0.367854E+09 | 0.241994E+09 |
February | 0.206457E+09 | 0.137306E+09 | 69150683.87 | 0.330986E+09 | 0.179437E+09 |
March | 0.203093E+09 | 0.103136E+09 | 99957379.73 | 0.367106E+09 | 0.123425E+09 |
April | 0.145070E+09 | 42995590.45 | 0.102075E+09 | 0.294955E+09 | 95689228.81 |
May | 0.122660E+09 | 10993503.79 | 0.111666E+09 | 0.262313E+09 | 58179660.40 |
June | 0.110495E+09 | 3747613.56 | 0.106748E+09 | 0.266791E+09 | 30051606.26 |
July | 0.114293E+09 | 5005276.44 | 0.109288E+09 | 0.287810E+09 | 18364962.24 |
August | 0.135430E+09 | 20757021.01 | 0.114673E+09 | 0.346146E+09 | 11823688.96 |
September | 0.147801E+09 | 53546127.33 | 94254416.92 | 0.328128E+09 | 43157359.17 |
October | 0.219260E+09 | 0.140087E+09 | 79172652.91 | 0.416027E+09 | 0.110953E+09 |
November | 0.238885E+09 | 0.160137E+09 | 78747756.61 | 0.405976E+09 | 0.146774E+09 |
December | 0.250148E+09 | 0.177443E+09 | 72704471.78 | 0.388928E+09 | 0.198554E+09 |
Annual Sum or Average | 0.214410E+10 | 0.103027E+10 | 0.111383E+10 | 0.406302E+10 | 0.125840E+10 |
Minimum of Months | 0.110495E+09 | 3747613.56 | 69150683.87 | 0.262313E+09 | 11823688.96 |
Maximum of Months | 0.250509E+09 | 0.177443E+09 | 0.114673E+09 | 0.416027E+09 | 0.241994E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197806E+09 | 0.138277E+09 | 59529819.38 | 0.292299E+09 | 0.180838E+09 |
February | 0.163022E+09 | 0.108419E+09 | 54602549.62 | 0.261135E+09 | 0.134087E+09 |
March | 0.160366E+09 | 81437980.93 | 78928037.75 | 0.285707E+09 | 91528835.93 |
April | 0.114550E+09 | 33950045.46 | 80599804.00 | 0.228858E+09 | 68755992.35 |
May | 96854215.86 | 8680656.54 | 88173559.32 | 0.203672E+09 | 38736864.29 |
June | 87248841.46 | 2959179.05 | 84289662.40 | 0.211238E+09 | 16787019.73 |
July | 90247967.30 | 3952250.94 | 86295716.36 | 0.230498E+09 | 7842055.09 |
August | 0.106937E+09 | 16390094.88 | 90547387.85 | 0.277099E+09 | 3607733.62 |
September | 0.116706E+09 | 42280927.84 | 74424881.86 | 0.258645E+09 | 25519095.95 |
October | 0.173131E+09 | 0.110615E+09 | 62516065.90 | 0.325807E+09 | 79216591.50 |
November | 0.188628E+09 | 0.126447E+09 | 62180560.59 | 0.317867E+09 | 0.109843E+09 |
December | 0.197521E+09 | 0.140112E+09 | 57408680.67 | 0.307462E+09 | 0.148772E+09 |
Annual Sum or Average | 0.169302E+10 | 0.813522E+09 | 0.879497E+09 | 0.320029E+10 | 0.905535E+09 |
Minimum of Months | 87248841.46 | 2959179.05 | 54602549.62 | 0.203672E+09 | 3607733.62 |
Maximum of Months | 0.197806E+09 | 0.140112E+09 | 90547387.85 | 0.325807E+09 | 0.180838E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154303E+09 | 71131092.33 | 83172032.11 | 0.170128E+09 | 0.372219E+09 |
February | 0.160855E+09 | 75385602.55 | 85469527.82 | 0.218132E+09 | 0.272496E+09 |
March | 0.262888E+09 | 0.127615E+09 | 0.135273E+09 | 0.421641E+09 | 0.175076E+09 |
April | 0.287156E+09 | 0.132542E+09 | 0.154615E+09 | 0.516163E+09 | 0.126670E+09 |
May | 0.297554E+09 | 0.113736E+09 | 0.183818E+09 | 0.581394E+09 | 71819365.94 |
June | 0.302238E+09 | 0.117005E+09 | 0.185233E+09 | 0.655167E+09 | 31014768.20 |
July | 0.293836E+09 | 0.109228E+09 | 0.184608E+09 | 0.663167E+09 | 14511193.77 |
August | 0.289161E+09 | 0.109019E+09 | 0.180142E+09 | 0.655901E+09 | 6723824.49 |
September | 0.229194E+09 | 96793657.69 | 0.132400E+09 | 0.462701E+09 | 47591890.40 |
October | 0.209684E+09 | 0.109264E+09 | 0.100420E+09 | 0.364322E+09 | 0.154211E+09 |
November | 0.159819E+09 | 70939221.71 | 88879409.84 | 0.238726E+09 | 0.221497E+09 |
December | 0.136128E+09 | 58802334.52 | 77325822.68 | 0.163246E+09 | 0.304731E+09 |
Annual Sum or Average | 0.278282E+10 | 0.119146E+10 | 0.159136E+10 | 0.511069E+10 | 0.179856E+10 |
Minimum of Months | 0.136128E+09 | 58802334.52 | 77325822.68 | 0.163246E+09 | 6723824.49 |
Maximum of Months | 0.302238E+09 | 0.132542E+09 | 0.185233E+09 | 0.663167E+09 | 0.372219E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36721179.13 | 0.00 | 36721179.13 | 11810009.81 | 0.207627E+09 |
February | 36762972.14 | 0.00 | 36762972.14 | 27009883.23 | 0.149978E+09 |
March | 57156296.39 | 326.84 | 57155969.56 | 64784326.02 | 96303878.68 |
April | 66904111.85 | 227889.08 | 66676222.78 | 0.104097E+09 | 70071032.86 |
May | 81922035.16 | 1826942.77 | 80095092.38 | 0.154804E+09 | 39965559.61 |
June | 86576606.12 | 4338936.35 | 82237669.77 | 0.202743E+09 | 17179526.21 |
July | 84967898.63 | 3252503.14 | 81715395.49 | 0.210689E+09 | 8817607.32 |
August | 76176873.73 | 577269.49 | 75599604.23 | 0.193028E+09 | 4071399.29 |
September | 55869174.22 | 9474.23 | 55859699.99 | 0.113972E+09 | 27654994.83 |
October | 43874948.72 | 0.00 | 43874948.72 | 60671025.57 | 84381774.33 |
November | 37999798.57 | 0.00 | 37999798.57 | 36741088.60 | 0.118664E+09 |
December | 33945997.15 | 0.00 | 33945997.15 | 16546427.73 | 0.165451E+09 |
Annual Sum or Average | 0.698878E+09 | 10233341.89 | 0.688645E+09 | 0.119690E+10 | 0.990165E+09 |
Minimum of Months | 33945997.15 | 0.00 | 33945997.15 | 11810009.81 | 4071399.29 |
Maximum of Months | 86576606.12 | 4338936.35 | 82237669.77 | 0.210689E+09 | 0.207627E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154303E+09 | 71131092.33 | 83172032.11 | 0.176439E+09 | 0.366884E+09 |
February | 0.160855E+09 | 75385602.55 | 85469527.82 | 0.223066E+09 | 0.268949E+09 |
March | 0.262888E+09 | 0.127615E+09 | 0.135273E+09 | 0.425384E+09 | 0.174860E+09 |
April | 0.287156E+09 | 0.132542E+09 | 0.154615E+09 | 0.515224E+09 | 0.131327E+09 |
May | 0.297554E+09 | 0.113736E+09 | 0.183818E+09 | 0.576950E+09 | 77817246.27 |
June | 0.302238E+09 | 0.117005E+09 | 0.185233E+09 | 0.650684E+09 | 33618891.56 |
July | 0.293836E+09 | 0.109228E+09 | 0.184608E+09 | 0.658654E+09 | 16552889.96 |
August | 0.289161E+09 | 0.109019E+09 | 0.180142E+09 | 0.653598E+09 | 7586981.88 |
September | 0.229194E+09 | 96793657.69 | 0.132400E+09 | 0.461432E+09 | 51229751.31 |
October | 0.209684E+09 | 0.109264E+09 | 0.100420E+09 | 0.367799E+09 | 0.155137E+09 |
November | 0.159819E+09 | 70939221.71 | 88879409.84 | 0.245850E+09 | 0.217350E+09 |
December | 0.136128E+09 | 58802334.52 | 77325822.68 | 0.170983E+09 | 0.299002E+09 |
Annual Sum or Average | 0.278282E+10 | 0.119146E+10 | 0.159136E+10 | 0.512606E+10 | 0.180031E+10 |
Minimum of Months | 0.136128E+09 | 58802334.52 | 77325822.68 | 0.170983E+09 | 7586981.88 |
Maximum of Months | 0.302238E+09 | 0.132542E+09 | 0.185233E+09 | 0.658654E+09 | 0.366884E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.290102E+09 | 0.202796E+09 | 87306193.21 | 0.416950E+09 | 0.275377E+09 |
February | 0.239087E+09 | 0.159007E+09 | 80079879.25 | 0.374840E+09 | 0.203820E+09 |
March | 0.235192E+09 | 0.119437E+09 | 0.115756E+09 | 0.415200E+09 | 0.136020E+09 |
April | 0.167998E+09 | 49790999.86 | 0.118207E+09 | 0.336217E+09 | 99404764.65 |
May | 0.142046E+09 | 12731015.90 | 0.129315E+09 | 0.302415E+09 | 54401193.65 |
June | 0.127959E+09 | 4339920.08 | 0.123619E+09 | 0.315671E+09 | 22529286.28 |
July | 0.132357E+09 | 5796355.30 | 0.126561E+09 | 0.344683E+09 | 10090338.88 |
August | 0.156834E+09 | 24037647.11 | 0.132796E+09 | 0.412595E+09 | 4361481.03 |
September | 0.171160E+09 | 62009038.39 | 0.109151E+09 | 0.381105E+09 | 36307044.92 |
October | 0.253914E+09 | 0.162228E+09 | 91685810.32 | 0.474300E+09 | 0.118352E+09 |
November | 0.276641E+09 | 0.185447E+09 | 91193759.59 | 0.458584E+09 | 0.167094E+09 |
December | 0.289683E+09 | 0.205488E+09 | 84195339.72 | 0.439678E+09 | 0.227631E+09 |
Annual Sum or Average | 0.248297E+10 | 0.119311E+10 | 0.128987E+10 | 0.467224E+10 | 0.135539E+10 |
Minimum of Months | 0.127959E+09 | 4339920.08 | 80079879.25 | 0.302415E+09 | 4361481.03 |
Maximum of Months | 0.290102E+09 | 0.205488E+09 | 0.132796E+09 | 0.474300E+09 | 0.275377E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257039E+09 | 0.00 | 0.257039E+09 | 67208895.00 | 0.154104E+10 |
February | 0.257331E+09 | 0.00 | 0.257331E+09 | 0.183101E+09 | 0.111582E+10 |
March | 0.400079E+09 | 2287.77 | 0.400077E+09 | 0.473358E+09 | 0.706027E+09 |
April | 0.468311E+09 | 1595163.11 | 0.466716E+09 | 0.779179E+09 | 0.503910E+09 |
May | 0.573433E+09 | 12788115.06 | 0.560644E+09 | 0.115428E+10 | 0.291612E+09 |
June | 0.606013E+09 | 30371404.14 | 0.575642E+09 | 0.148892E+10 | 0.139892E+09 |
July | 0.594753E+09 | 22766659.71 | 0.571986E+09 | 0.154517E+10 | 80892484.90 |
August | 0.533218E+09 | 4040733.41 | 0.529177E+09 | 0.141503E+10 | 46945446.07 |
September | 0.391069E+09 | 66317.09 | 0.391003E+09 | 0.856053E+09 | 0.210229E+09 |
October | 0.307113E+09 | 0.00 | 0.307113E+09 | 0.449222E+09 | 0.620626E+09 |
November | 0.265989E+09 | 0.00 | 0.265989E+09 | 0.253935E+09 | 0.880045E+09 |
December | 0.237613E+09 | 0.00 | 0.237613E+09 | 94998372.86 | 0.123707E+10 |
Annual Sum or Average | 0.489196E+10 | 71630680.28 | 0.482033E+10 | 0.876045E+10 | 0.737410E+10 |
Minimum of Months | 0.237613E+09 | 0.00 | 0.237613E+09 | 67208895.00 | 46945446.07 |
Maximum of Months | 0.606013E+09 | 30371404.14 | 0.575642E+09 | 0.154517E+10 | 0.154104E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257039E+09 | 0.00 | 0.257039E+09 | 60606711.36 | 0.159975E+10 |
February | 0.257331E+09 | 0.00 | 0.257331E+09 | 0.172854E+09 | 0.116401E+10 |
March | 0.400079E+09 | 2287.77 | 0.400077E+09 | 0.451861E+09 | 0.742208E+09 |
April | 0.468311E+09 | 1595163.11 | 0.466716E+09 | 0.756296E+09 | 0.528478E+09 |
May | 0.573433E+09 | 12788115.06 | 0.560644E+09 | 0.112857E+10 | 0.309645E+09 |
June | 0.606013E+09 | 30371404.14 | 0.575642E+09 | 0.146058E+10 | 0.152651E+09 |
July | 0.594753E+09 | 22766659.71 | 0.571986E+09 | 0.151472E+10 | 91665660.89 |
August | 0.533218E+09 | 4040733.41 | 0.529177E+09 | 0.138395E+10 | 56798601.15 |
September | 0.391069E+09 | 66317.09 | 0.391003E+09 | 0.832554E+09 | 0.227868E+09 |
October | 0.307113E+09 | 0.00 | 0.307113E+09 | 0.431114E+09 | 0.653191E+09 |
November | 0.265989E+09 | 0.00 | 0.265989E+09 | 0.238067E+09 | 0.923820E+09 |
December | 0.237613E+09 | 0.00 | 0.237613E+09 | 84423666.46 | 0.129418E+10 |
Annual Sum or Average | 0.489196E+10 | 71630680.28 | 0.482033E+10 | 0.851560E+10 | 0.774427E+10 |
Minimum of Months | 0.237613E+09 | 0.00 | 0.237613E+09 | 60606711.36 | 56798601.15 |
Maximum of Months | 0.606013E+09 | 30371404.14 | 0.575642E+09 | 0.151472E+10 | 0.159975E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36721179.13 | 0.00 | 36721179.13 | 43382283.96 | 0.158055E+09 |
February | 36762972.14 | 0.00 | 36762972.14 | 70892801.66 | 0.114597E+09 |
March | 57156296.39 | 326.84 | 57155969.56 | 0.147711E+09 | 73168298.28 |
April | 66904111.85 | 227889.08 | 66676222.78 | 0.205054E+09 | 54459430.09 |
May | 81922035.16 | 1826942.77 | 80095092.38 | 0.277627E+09 | 33842074.00 |
June | 86576606.12 | 4338936.35 | 82237669.77 | 0.330315E+09 | 17819366.81 |
July | 84967898.63 | 3252503.14 | 81715395.49 | 0.345337E+09 | 10355268.64 |
August | 76176873.73 | 577269.49 | 75599604.23 | 0.327278E+09 | 6356985.91 |
September | 55869174.22 | 9474.23 | 55859699.99 | 0.230470E+09 | 21525573.42 |
October | 43874948.72 | 0.00 | 43874948.72 | 0.145936E+09 | 59420581.75 |
November | 37999798.57 | 0.00 | 37999798.57 | 0.100219E+09 | 87707441.90 |
December | 33945997.15 | 0.00 | 33945997.15 | 60317184.73 | 0.124613E+09 |
Annual Sum or Average | 0.698878E+09 | 10233341.89 | 0.688645E+09 | 0.228454E+10 | 0.761920E+09 |
Minimum of Months | 33945997.15 | 0.00 | 33945997.15 | 43382283.96 | 6356985.91 |
Maximum of Months | 86576606.12 | 4338936.35 | 82237669.77 | 0.345337E+09 | 0.158055E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.301040E+09 | 0.135781E+09 | 0.165259E+09 | 0.477294E+09 | 0.559666E+09 |
February | 0.344031E+09 | 0.185240E+09 | 0.158791E+09 | 0.663633E+09 | 0.405125E+09 |
March | 0.481203E+09 | 0.220652E+09 | 0.260551E+09 | 0.108867E+10 | 0.267965E+09 |
April | 0.563593E+09 | 0.258959E+09 | 0.304634E+09 | 0.139751E+10 | 0.202019E+09 |
May | 0.637187E+09 | 0.271061E+09 | 0.366126E+09 | 0.169659E+10 | 0.126901E+09 |
June | 0.637171E+09 | 0.268130E+09 | 0.369041E+09 | 0.184957E+10 | 66905598.75 |
July | 0.642959E+09 | 0.271716E+09 | 0.371243E+09 | 0.193071E+10 | 38930503.02 |
August | 0.589213E+09 | 0.235540E+09 | 0.353673E+09 | 0.183630E+10 | 23902366.76 |
September | 0.468167E+09 | 0.208670E+09 | 0.259497E+09 | 0.138686E+10 | 80752751.24 |
October | 0.411349E+09 | 0.214321E+09 | 0.197028E+09 | 0.105146E+10 | 0.219671E+09 |
November | 0.314763E+09 | 0.140922E+09 | 0.173841E+09 | 0.726338E+09 | 0.316249E+09 |
December | 0.280646E+09 | 0.125928E+09 | 0.154719E+09 | 0.531709E+09 | 0.444088E+09 |
Annual Sum or Average | 0.567132E+10 | 0.253692E+10 | 0.313440E+10 | 0.146366E+11 | 0.275217E+10 |
Minimum of Months | 0.280646E+09 | 0.125928E+09 | 0.154719E+09 | 0.477294E+09 | 23902366.76 |
Maximum of Months | 0.642959E+09 | 0.271716E+09 | 0.371243E+09 | 0.193071E+10 | 0.559666E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197806E+09 | 0.138277E+09 | 59529819.38 | 0.352901E+09 | 0.147803E+09 |
February | 0.163022E+09 | 0.108419E+09 | 54602549.62 | 0.323371E+09 | 0.107670E+09 |
March | 0.160366E+09 | 81437980.93 | 78928037.75 | 0.378121E+09 | 71961711.76 |
April | 0.114550E+09 | 33950045.46 | 80599804.00 | 0.330387E+09 | 54841097.62 |
May | 96854215.86 | 8680656.54 | 88173559.32 | 0.323211E+09 | 33982760.50 |
June | 87248841.46 | 2959179.05 | 84289662.40 | 0.335767E+09 | 17938878.80 |
July | 90247967.30 | 3952250.94 | 86295716.36 | 0.362436E+09 | 10330185.73 |
August | 0.106937E+09 | 16390094.88 | 90547387.85 | 0.410743E+09 | 6322251.11 |
September | 0.116706E+09 | 42280927.84 | 74424881.86 | 0.376772E+09 | 21448474.87 |
October | 0.173131E+09 | 0.110615E+09 | 62516065.90 | 0.421233E+09 | 58590688.25 |
November | 0.188628E+09 | 0.126447E+09 | 62180560.59 | 0.398134E+09 | 84209121.50 |
December | 0.197521E+09 | 0.140112E+09 | 57408680.67 | 0.374798E+09 | 0.117980E+09 |
Annual Sum or Average | 0.169302E+10 | 0.813522E+09 | 0.879497E+09 | 0.438787E+10 | 0.733078E+09 |
Minimum of Months | 87248841.46 | 2959179.05 | 54602549.62 | 0.323211E+09 | 6322251.11 |
Maximum of Months | 0.197806E+09 | 0.140112E+09 | 90547387.85 | 0.421233E+09 | 0.147803E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46505056.39 | 0.00 | 46505056.39 | 10624827.31 | 0.289090E+09 |
February | 46557984.60 | 0.00 | 46557984.60 | 28862922.52 | 0.212330E+09 |
March | 72384843.02 | 413.92 | 72384429.10 | 72936766.82 | 0.143044E+09 |
April | 84729836.25 | 288607.13 | 84441229.11 | 0.122279E+09 | 0.107217E+09 |
May | 0.103749E+09 | 2313707.75 | 0.101435E+09 | 0.183906E+09 | 67669548.19 |
June | 0.109644E+09 | 5494989.11 | 0.104149E+09 | 0.242072E+09 | 35905582.56 |
July | 0.107606E+09 | 4119090.01 | 0.103487E+09 | 0.249777E+09 | 23917904.28 |
August | 96473204.08 | 731075.39 | 95742128.69 | 0.225650E+09 | 17745238.11 |
September | 70754784.00 | 11998.51 | 70742785.48 | 0.131630E+09 | 54352028.31 |
October | 55564854.19 | 0.00 | 55564854.19 | 66145893.66 | 0.132213E+09 |
November | 48124347.23 | 0.00 | 48124347.23 | 38058195.60 | 0.174129E+09 |
December | 42990463.51 | 0.00 | 42990463.51 | 14118241.23 | 0.233878E+09 |
Annual Sum or Average | 0.885085E+09 | 12959881.82 | 0.872125E+09 | 0.138606E+10 | 0.149149E+10 |
Minimum of Months | 42990463.51 | 0.00 | 42990463.51 | 10624827.31 | 17745238.11 |
Maximum of Months | 0.109644E+09 | 5494989.11 | 0.104149E+09 | 0.249777E+09 | 0.289090E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41608250.16 | 0.00 | 41608250.16 | 9506073.25 | 0.258645E+09 |
February | 41655605.23 | 0.00 | 41655605.23 | 25823766.14 | 0.189973E+09 |
March | 64762993.31 | 370.33 | 64762622.98 | 65256801.63 | 0.127982E+09 |
April | 75808105.53 | 258217.90 | 75549887.63 | 0.109404E+09 | 95927644.57 |
May | 92824702.61 | 2070083.09 | 90754619.53 | 0.164541E+09 | 60544201.16 |
June | 98098731.32 | 4916387.58 | 93182343.74 | 0.216583E+09 | 32124860.76 |
July | 96275927.56 | 3685365.44 | 92590562.13 | 0.223476E+09 | 21399439.58 |
August | 86314941.23 | 654095.92 | 85660845.31 | 0.201890E+09 | 15876731.78 |
September | 63304573.33 | 10735.11 | 63293838.22 | 0.117770E+09 | 48628965.67 |
October | 49714085.58 | 0.00 | 49714085.58 | 59180981.69 | 0.118291E+09 |
November | 43057035.81 | 0.00 | 43057035.81 | 34050811.81 | 0.155792E+09 |
December | 38463730.60 | 0.00 | 38463730.60 | 12631643.92 | 0.209242E+09 |
Annual Sum or Average | 0.791889E+09 | 11595255.37 | 0.780293E+09 | 0.124011E+10 | 0.133443E+10 |
Minimum of Months | 38463730.60 | 0.00 | 38463730.60 | 9506073.25 | 15876731.78 |
Maximum of Months | 98098731.32 | 4916387.58 | 93182343.74 | 0.223476E+09 | 0.258645E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.738470E+09 | 0.516227E+09 | 0.222243E+09 | 0.107177E+10 | 0.720636E+09 |
February | 0.608610E+09 | 0.404762E+09 | 0.203848E+09 | 0.957485E+09 | 0.547872E+09 |
March | 0.598694E+09 | 0.304032E+09 | 0.294662E+09 | 0.104366E+10 | 0.400763E+09 |
April | 0.427649E+09 | 0.126746E+09 | 0.300903E+09 | 0.824950E+09 | 0.321846E+09 |
May | 0.361586E+09 | 32407477.58 | 0.329178E+09 | 0.720156E+09 | 0.211652E+09 |
June | 0.325726E+09 | 11047497.20 | 0.314678E+09 | 0.739397E+09 | 0.113133E+09 |
July | 0.336923E+09 | 14754930.46 | 0.322168E+09 | 0.802759E+09 | 73185405.61 |
August | 0.399229E+09 | 61189108.20 | 0.338040E+09 | 0.974691E+09 | 53388573.17 |
September | 0.435698E+09 | 0.157847E+09 | 0.277850E+09 | 0.925091E+09 | 0.159751E+09 |
October | 0.646351E+09 | 0.412960E+09 | 0.233391E+09 | 0.118759E+10 | 0.368186E+09 |
November | 0.704203E+09 | 0.472065E+09 | 0.232139E+09 | 0.116866E+10 | 0.463163E+09 |
December | 0.737404E+09 | 0.523080E+09 | 0.214324E+09 | 0.112941E+10 | 0.599889E+09 |
Annual Sum or Average | 0.632054E+10 | 0.303712E+10 | 0.328342E+10 | 0.115456E+11 | 0.403346E+10 |
Minimum of Months | 0.325726E+09 | 11047497.20 | 0.203848E+09 | 0.720156E+09 | 53388573.17 |
Maximum of Months | 0.738470E+09 | 0.523080E+09 | 0.338040E+09 | 0.118759E+10 | 0.720636E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 548.92 | 342.84 | 373.52 | 261.11 | 112.41 | 0.00 | 0.00 |
February | 543.62 | 285.74 | 340.82 | 226.67 | 114.15 | 0.00 | 0.00 |
March | 538.90 | 186.73 | 302.82 | 153.78 | 149.04 | 0.00 | 0.00 |
April | 444.57 | 150.48 | 223.52 | 66.25 | 157.27 | 0.00 | 0.00 |
May | 376.33 | 94.37 | 182.89 | 16.39 | 166.50 | 0.00 | 0.00 |
June | 388.80 | 56.62 | 170.25 | 5.77 | 164.47 | 0.00 | 0.00 |
July | 406.80 | 35.65 | 170.42 | 7.46 | 162.95 | 0.00 | 0.00 |
August | 491.70 | 28.29 | 201.93 | 30.95 | 170.98 | 0.00 | 0.00 |
September | 488.80 | 76.77 | 227.72 | 82.50 | 145.22 | 0.00 | 0.00 |
October | 607.89 | 171.34 | 326.93 | 208.88 | 118.05 | 0.00 | 0.00 |
November | 614.93 | 228.82 | 368.07 | 246.73 | 121.33 | 0.00 | 0.00 |
December | 576.18 | 288.29 | 372.99 | 264.58 | 108.41 | 0.00 | 0.00 |
Annual Sum or Average | 502.15 | 161.52 | 271.52 | 130.47 | 141.05 | 0.00 | 0.00 |
Minimum of Months | 376.33 | 28.29 | 170.25 | 5.77 | 108.41 | 0.00 | 0.00 |
Maximum of Months | 614.93 | 342.84 | 373.52 | 264.58 | 170.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1544.91 | 963.20 | 1051.82 | 735.28 | 316.54 | 0.00 | 0.00 |
February | 1535.26 | 798.96 | 959.73 | 638.28 | 321.45 | 0.00 | 0.00 |
March | 1538.24 | 502.98 | 852.73 | 433.04 | 419.69 | 0.00 | 0.00 |
April | 1286.24 | 389.33 | 629.41 | 186.54 | 442.87 | 0.00 | 0.00 |
May | 1114.80 | 223.57 | 515.01 | 46.16 | 468.85 | 0.00 | 0.00 |
June | 1173.56 | 117.05 | 479.40 | 16.26 | 463.14 | 0.00 | 0.00 |
July | 1228.55 | 64.80 | 479.88 | 21.02 | 458.87 | 0.00 | 0.00 |
August | 1463.51 | 44.39 | 568.63 | 87.15 | 481.48 | 0.00 | 0.00 |
September | 1430.44 | 171.79 | 641.26 | 232.32 | 408.94 | 0.00 | 0.00 |
October | 1739.06 | 450.71 | 920.61 | 588.19 | 332.42 | 0.00 | 0.00 |
November | 1743.90 | 626.12 | 1036.45 | 694.79 | 341.66 | 0.00 | 0.00 |
December | 1624.98 | 806.64 | 1050.30 | 745.04 | 305.27 | 0.00 | 0.00 |
Annual Sum or Average | 1451.75 | 428.07 | 764.59 | 367.40 | 397.19 | 0.00 | 0.00 |
Minimum of Months | 1114.80 | 44.39 | 479.40 | 16.26 | 305.27 | 0.00 | 0.00 |
Maximum of Months | 1743.90 | 963.20 | 1051.82 | 745.04 | 481.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2018.59 | 1327.91 | 1366.38 | 955.17 | 411.21 | 0.00 | 0.00 |
February | 2005.81 | 1108.75 | 1246.75 | 829.17 | 417.58 | 0.00 | 0.00 |
March | 2002.67 | 712.89 | 1107.75 | 562.55 | 545.20 | 0.00 | 0.00 |
April | 1665.40 | 564.01 | 817.64 | 242.33 | 575.31 | 0.00 | 0.00 |
May | 1430.97 | 340.21 | 669.03 | 59.96 | 609.07 | 0.00 | 0.00 |
June | 1497.90 | 191.19 | 622.77 | 21.12 | 601.65 | 0.00 | 0.00 |
July | 1567.52 | 115.50 | 623.40 | 27.30 | 596.09 | 0.00 | 0.00 |
August | 1881.87 | 84.40 | 738.68 | 113.22 | 625.46 | 0.00 | 0.00 |
September | 1844.32 | 270.44 | 833.03 | 301.80 | 531.23 | 0.00 | 0.00 |
October | 2263.19 | 647.93 | 1195.93 | 764.09 | 431.84 | 0.00 | 0.00 |
November | 2270.90 | 883.86 | 1346.40 | 902.57 | 443.84 | 0.00 | 0.00 |
December | 2119.47 | 1124.46 | 1364.40 | 967.85 | 396.56 | 0.00 | 0.00 |
Annual Sum or Average | 1880.36 | 611.73 | 993.25 | 477.28 | 515.98 | 0.00 | 0.00 |
Minimum of Months | 1430.97 | 84.40 | 622.77 | 21.12 | 396.56 | 0.00 | 0.00 |
Maximum of Months | 2270.90 | 1327.91 | 1366.38 | 967.85 | 625.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.88 | 201.35 | 131.46 | 78.18 | 53.28 | 0.00 | 0.00 |
February | 191.63 | 164.57 | 133.88 | 75.98 | 57.90 | 0.00 | 0.00 |
March | 263.72 | 100.30 | 158.02 | 78.05 | 79.97 | 0.00 | 0.00 |
April | 288.56 | 76.43 | 154.98 | 64.23 | 90.75 | 0.00 | 0.00 |
May | 295.14 | 42.21 | 147.26 | 45.71 | 101.55 | 0.00 | 0.00 |
June | 336.17 | 19.35 | 150.26 | 46.28 | 103.98 | 0.00 | 0.00 |
July | 335.37 | 9.01 | 143.40 | 42.26 | 101.14 | 0.00 | 0.00 |
August | 350.04 | 4.37 | 147.89 | 46.82 | 101.06 | 0.00 | 0.00 |
September | 279.48 | 29.39 | 133.45 | 53.66 | 79.79 | 0.00 | 0.00 |
October | 257.20 | 88.10 | 142.93 | 82.09 | 60.83 | 0.00 | 0.00 |
November | 211.19 | 126.85 | 134.43 | 76.15 | 58.28 | 0.00 | 0.00 |
December | 168.33 | 165.64 | 124.57 | 74.27 | 50.30 | 0.00 | 0.00 |
Annual Sum or Average | 262.12 | 85.23 | 141.93 | 63.58 | 78.35 | 0.00 | 0.00 |
Minimum of Months | 163.88 | 4.37 | 124.57 | 42.26 | 50.30 | 0.00 | 0.00 |
Maximum of Months | 350.04 | 201.35 | 158.02 | 82.09 | 103.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 66.17 | 214.30 | 71.32 | 26.56 | 44.76 | 0.00 | 0.00 |
February | 100.65 | 173.99 | 81.69 | 31.16 | 50.53 | 0.00 | 0.00 |
March | 182.60 | 102.71 | 119.49 | 47.65 | 71.84 | 0.00 | 0.00 |
April | 240.11 | 78.39 | 136.60 | 51.22 | 85.37 | 0.00 | 0.00 |
May | 274.95 | 44.10 | 141.68 | 43.15 | 98.53 | 0.00 | 0.00 |
June | 330.71 | 20.00 | 150.01 | 46.81 | 103.19 | 0.00 | 0.00 |
July | 326.09 | 9.94 | 141.43 | 42.00 | 99.43 | 0.00 | 0.00 |
August | 317.54 | 4.87 | 136.40 | 40.92 | 95.48 | 0.00 | 0.00 |
September | 222.84 | 31.60 | 109.98 | 37.35 | 72.63 | 0.00 | 0.00 |
October | 159.60 | 91.34 | 94.67 | 40.79 | 53.87 | 0.00 | 0.00 |
November | 107.61 | 132.16 | 76.32 | 27.37 | 48.95 | 0.00 | 0.00 |
December | 67.27 | 175.36 | 63.50 | 21.95 | 41.54 | 0.00 | 0.00 |
Annual Sum or Average | 200.21 | 89.47 | 110.40 | 38.11 | 72.30 | 0.00 | 0.00 |
Minimum of Months | 66.17 | 4.87 | 63.50 | 21.95 | 41.54 | 0.00 | 0.00 |
Maximum of Months | 330.71 | 214.30 | 150.01 | 51.22 | 103.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.02 | 62.19 | 59.07 | 41.29 | 17.78 | 0.00 | 0.00 |
February | 80.25 | 58.25 | 53.90 | 35.85 | 18.05 | 0.00 | 0.00 |
March | 77.10 | 42.59 | 47.89 | 24.32 | 23.57 | 0.00 | 0.00 |
April | 62.55 | 34.85 | 35.35 | 10.48 | 24.87 | 0.00 | 0.00 |
May | 52.17 | 23.30 | 28.92 | 2.59 | 26.33 | 0.00 | 0.00 |
June | 55.03 | 14.67 | 26.92 | 0.91 | 26.01 | 0.00 | 0.00 |
July | 57.88 | 10.75 | 26.95 | 1.18 | 25.77 | 0.00 | 0.00 |
August | 71.65 | 9.32 | 31.93 | 4.89 | 27.04 | 0.00 | 0.00 |
September | 71.22 | 19.96 | 36.01 | 13.05 | 22.97 | 0.00 | 0.00 |
October | 89.64 | 39.21 | 51.70 | 33.03 | 18.67 | 0.00 | 0.00 |
November | 89.77 | 50.84 | 58.21 | 39.02 | 19.19 | 0.00 | 0.00 |
December | 84.00 | 60.91 | 58.98 | 41.84 | 17.14 | 0.00 | 0.00 |
Annual Sum or Average | 72.83 | 35.44 | 42.94 | 20.63 | 22.31 | 0.00 | 0.00 |
Minimum of Months | 52.17 | 9.32 | 26.92 | 0.91 | 17.14 | 0.00 | 0.00 |
Maximum of Months | 89.77 | 62.19 | 59.07 | 41.84 | 27.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.92 | 65.58 | 10.97 | 0.00 | 10.97 | 0.00 | 0.00 |
February | 8.59 | 52.25 | 12.16 | 0.00 | 12.16 | 0.00 | 0.00 |
March | 19.88 | 29.12 | 17.07 | 0.00 | 17.07 | 0.00 | 0.00 |
April | 33.65 | 21.20 | 20.65 | 0.07 | 20.58 | 0.00 | 0.00 |
May | 48.36 | 11.26 | 24.47 | 0.55 | 23.93 | 0.00 | 0.00 |
June | 65.21 | 4.73 | 26.72 | 1.34 | 25.39 | 0.00 | 0.00 |
July | 65.78 | 2.22 | 25.38 | 0.97 | 24.41 | 0.00 | 0.00 |
August | 60.75 | 0.91 | 22.76 | 0.17 | 22.58 | 0.00 | 0.00 |
September | 36.92 | 8.14 | 17.25 | 0.00 | 17.24 | 0.00 | 0.00 |
October | 18.66 | 25.58 | 13.11 | 0.00 | 13.11 | 0.00 | 0.00 |
November | 10.96 | 38.34 | 11.73 | 0.00 | 11.73 | 0.00 | 0.00 |
December | 4.09 | 52.53 | 10.14 | 0.00 | 10.14 | 0.00 | 0.00 |
Annual Sum or Average | 31.44 | 25.86 | 17.73 | 0.26 | 17.47 | 0.00 | 0.00 |
Minimum of Months | 2.92 | 0.91 | 10.14 | 0.00 | 10.14 | 0.00 | 0.00 |
Maximum of Months | 65.78 | 65.58 | 26.72 | 1.34 | 25.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.50 | 198.86 | 130.05 | 76.98 | 53.08 | 0.00 | 0.00 |
February | 196.67 | 161.14 | 138.50 | 83.10 | 55.39 | 0.00 | 0.00 |
March | 242.91 | 95.95 | 149.71 | 71.60 | 78.11 | 0.00 | 0.00 |
April | 279.89 | 71.55 | 152.92 | 63.06 | 89.86 | 0.00 | 0.00 |
May | 307.41 | 39.62 | 155.12 | 53.85 | 101.27 | 0.00 | 0.00 |
June | 347.27 | 17.99 | 156.58 | 52.87 | 103.71 | 0.00 | 0.00 |
July | 354.51 | 8.76 | 153.73 | 52.20 | 101.53 | 0.00 | 0.00 |
August | 354.18 | 4.16 | 149.93 | 50.09 | 99.83 | 0.00 | 0.00 |
September | 282.47 | 28.30 | 135.34 | 56.57 | 78.77 | 0.00 | 0.00 |
October | 250.96 | 84.95 | 141.44 | 81.31 | 60.12 | 0.00 | 0.00 |
November | 205.59 | 123.36 | 133.50 | 75.97 | 57.53 | 0.00 | 0.00 |
December | 168.60 | 163.01 | 126.14 | 75.82 | 50.32 | 0.00 | 0.00 |
Annual Sum or Average | 262.78 | 82.75 | 143.61 | 66.02 | 77.59 | 0.00 | 0.00 |
Minimum of Months | 158.50 | 4.16 | 126.14 | 50.09 | 50.32 | 0.00 | 0.00 |
Maximum of Months | 354.51 | 198.86 | 156.58 | 83.10 | 103.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 56.16 | 207.12 | 69.91 | 25.35 | 44.56 | 0.00 | 0.00 |
February | 99.90 | 164.46 | 86.31 | 38.29 | 48.02 | 0.00 | 0.00 |
March | 160.49 | 96.02 | 111.18 | 41.19 | 69.98 | 0.00 | 0.00 |
April | 231.70 | 73.17 | 134.54 | 50.04 | 84.49 | 0.00 | 0.00 |
May | 287.77 | 42.14 | 149.54 | 51.29 | 98.26 | 0.00 | 0.00 |
June | 341.58 | 19.24 | 156.32 | 53.40 | 102.92 | 0.00 | 0.00 |
July | 344.41 | 9.89 | 151.76 | 51.94 | 99.82 | 0.00 | 0.00 |
August | 321.13 | 4.65 | 138.44 | 44.19 | 94.25 | 0.00 | 0.00 |
September | 225.13 | 30.28 | 111.87 | 40.26 | 71.61 | 0.00 | 0.00 |
October | 151.38 | 85.71 | 93.18 | 40.01 | 53.16 | 0.00 | 0.00 |
November | 97.20 | 122.91 | 75.38 | 27.19 | 48.20 | 0.00 | 0.00 |
December | 60.45 | 165.46 | 65.07 | 23.51 | 41.56 | 0.00 | 0.00 |
Annual Sum or Average | 198.63 | 84.70 | 112.09 | 40.55 | 71.54 | 0.00 | 0.00 |
Minimum of Months | 56.16 | 4.65 | 65.07 | 23.51 | 41.56 | 0.00 | 0.00 |
Maximum of Months | 344.41 | 207.12 | 156.32 | 53.40 | 102.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 178.87 | 254.41 | 151.75 | 89.47 | 62.28 | 0.00 | 0.00 |
February | 195.48 | 207.56 | 143.12 | 77.67 | 65.46 | 0.00 | 0.00 |
March | 228.72 | 127.95 | 140.75 | 52.69 | 88.06 | 0.00 | 0.00 |
April | 227.63 | 99.98 | 121.33 | 22.85 | 98.48 | 0.00 | 0.00 |
May | 236.94 | 57.32 | 115.68 | 6.80 | 108.88 | 0.00 | 0.00 |
June | 276.83 | 30.22 | 116.23 | 4.88 | 111.35 | 0.00 | 0.00 |
July | 282.50 | 18.28 | 113.38 | 4.66 | 108.72 | 0.00 | 0.00 |
August | 299.87 | 11.98 | 118.49 | 10.98 | 107.51 | 0.00 | 0.00 |
September | 249.78 | 45.66 | 115.39 | 28.28 | 87.12 | 0.00 | 0.00 |
October | 249.85 | 114.88 | 140.42 | 71.57 | 68.84 | 0.00 | 0.00 |
November | 232.69 | 158.20 | 151.53 | 84.54 | 66.99 | 0.00 | 0.00 |
December | 196.57 | 207.27 | 149.77 | 90.66 | 59.11 | 0.00 | 0.00 |
Annual Sum or Average | 238.23 | 110.65 | 131.45 | 45.27 | 86.18 | 0.00 | 0.00 |
Minimum of Months | 178.87 | 11.98 | 113.38 | 4.66 | 59.11 | 0.00 | 0.00 |
Maximum of Months | 299.87 | 254.41 | 151.75 | 90.66 | 111.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 164.57 | 198.41 | 131.46 | 78.18 | 53.28 | 0.00 | 0.00 |
February | 191.84 | 161.79 | 133.88 | 75.98 | 57.90 | 0.00 | 0.00 |
March | 262.74 | 98.19 | 158.02 | 78.05 | 79.97 | 0.00 | 0.00 |
April | 286.93 | 74.89 | 154.98 | 64.23 | 90.75 | 0.00 | 0.00 |
May | 293.04 | 41.21 | 147.26 | 45.71 | 101.55 | 0.00 | 0.00 |
June | 334.25 | 18.43 | 150.26 | 46.28 | 103.98 | 0.00 | 0.00 |
July | 333.65 | 8.34 | 143.40 | 42.26 | 101.14 | 0.00 | 0.00 |
August | 348.34 | 3.86 | 147.89 | 46.82 | 101.06 | 0.00 | 0.00 |
September | 278.25 | 28.16 | 133.45 | 53.66 | 79.79 | 0.00 | 0.00 |
October | 256.45 | 85.93 | 142.93 | 82.09 | 60.83 | 0.00 | 0.00 |
November | 211.20 | 124.30 | 134.43 | 76.15 | 58.28 | 0.00 | 0.00 |
December | 169.09 | 162.67 | 124.57 | 74.27 | 50.30 | 0.00 | 0.00 |
Annual Sum or Average | 261.25 | 83.45 | 141.93 | 63.58 | 78.35 | 0.00 | 0.00 |
Minimum of Months | 164.57 | 3.86 | 124.57 | 42.26 | 50.30 | 0.00 | 0.00 |
Maximum of Months | 348.34 | 198.41 | 158.02 | 82.09 | 103.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 66.97 | 211.18 | 71.32 | 26.56 | 44.76 | 0.00 | 0.00 |
February | 101.13 | 170.92 | 81.69 | 31.16 | 50.53 | 0.00 | 0.00 |
March | 182.25 | 100.49 | 119.49 | 47.65 | 71.84 | 0.00 | 0.00 |
April | 238.61 | 77.37 | 136.60 | 51.22 | 85.37 | 0.00 | 0.00 |
May | 272.83 | 43.60 | 141.68 | 43.15 | 98.53 | 0.00 | 0.00 |
June | 328.89 | 19.24 | 150.01 | 46.81 | 103.19 | 0.00 | 0.00 |
July | 324.48 | 9.37 | 141.43 | 42.00 | 99.43 | 0.00 | 0.00 |
August | 316.08 | 4.34 | 136.40 | 40.92 | 95.48 | 0.00 | 0.00 |
September | 221.94 | 30.38 | 109.98 | 37.35 | 72.63 | 0.00 | 0.00 |
October | 159.52 | 88.97 | 94.67 | 40.79 | 53.87 | 0.00 | 0.00 |
November | 108.34 | 128.95 | 76.32 | 27.37 | 48.95 | 0.00 | 0.00 |
December | 68.46 | 171.85 | 63.50 | 21.95 | 41.54 | 0.00 | 0.00 |
Annual Sum or Average | 199.65 | 87.64 | 110.40 | 38.11 | 72.30 | 0.00 | 0.00 |
Minimum of Months | 66.97 | 4.34 | 63.50 | 21.95 | 41.54 | 0.00 | 0.00 |
Maximum of Months | 328.89 | 211.18 | 150.01 | 51.22 | 103.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 155.67 | 102.81 | 108.31 | 75.72 | 32.60 | 0.00 | 0.00 |
February | 154.94 | 84.25 | 98.83 | 65.73 | 33.10 | 0.00 | 0.00 |
March | 155.02 | 50.78 | 87.81 | 44.59 | 43.22 | 0.00 | 0.00 |
April | 129.71 | 38.35 | 64.81 | 19.21 | 45.60 | 0.00 | 0.00 |
May | 112.91 | 20.31 | 53.03 | 4.75 | 48.28 | 0.00 | 0.00 |
June | 121.79 | 8.69 | 49.37 | 1.67 | 47.69 | 0.00 | 0.00 |
July | 128.69 | 3.77 | 49.42 | 2.16 | 47.25 | 0.00 | 0.00 |
August | 154.05 | 1.63 | 58.56 | 8.97 | 49.58 | 0.00 | 0.00 |
September | 147.03 | 14.01 | 66.03 | 23.92 | 42.11 | 0.00 | 0.00 |
October | 177.08 | 44.19 | 94.80 | 60.57 | 34.23 | 0.00 | 0.00 |
November | 176.92 | 64.47 | 106.73 | 71.55 | 35.18 | 0.00 | 0.00 |
December | 164.16 | 84.99 | 108.16 | 76.72 | 31.43 | 0.00 | 0.00 |
Annual Sum or Average | 148.16 | 42.98 | 78.73 | 37.83 | 40.90 | 0.00 | 0.00 |
Minimum of Months | 112.91 | 1.63 | 49.37 | 1.67 | 31.43 | 0.00 | 0.00 |
Maximum of Months | 177.08 | 102.81 | 108.31 | 76.72 | 49.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 25.09 | 575.36 | 95.97 | 0.00 | 95.97 | 0.00 | 0.00 |
February | 75.69 | 461.24 | 106.37 | 0.00 | 106.37 | 0.00 | 0.00 |
March | 176.73 | 263.60 | 149.37 | 0.00 | 149.37 | 0.00 | 0.00 |
April | 300.61 | 194.41 | 180.68 | 0.62 | 180.06 | 0.00 | 0.00 |
May | 430.96 | 108.88 | 214.10 | 4.77 | 209.32 | 0.00 | 0.00 |
June | 574.43 | 53.97 | 233.80 | 11.72 | 222.08 | 0.00 | 0.00 |
July | 576.90 | 30.20 | 222.06 | 8.50 | 213.56 | 0.00 | 0.00 |
August | 528.31 | 17.53 | 199.08 | 1.51 | 197.57 | 0.00 | 0.00 |
September | 330.27 | 81.11 | 150.88 | 0.03 | 150.85 | 0.00 | 0.00 |
October | 167.72 | 231.72 | 114.66 | 0.00 | 114.66 | 0.00 | 0.00 |
November | 97.97 | 339.52 | 102.62 | 0.00 | 102.62 | 0.00 | 0.00 |
December | 35.47 | 461.87 | 88.71 | 0.00 | 88.71 | 0.00 | 0.00 |
Annual Sum or Average | 277.79 | 233.83 | 155.12 | 2.27 | 152.85 | 0.00 | 0.00 |
Minimum of Months | 25.09 | 17.53 | 88.71 | 0.00 | 88.71 | 0.00 | 0.00 |
Maximum of Months | 576.90 | 575.36 | 233.80 | 11.72 | 222.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.63 | 597.28 | 95.97 | 0.00 | 95.97 | 0.00 | 0.00 |
February | 71.45 | 481.15 | 106.37 | 0.00 | 106.37 | 0.00 | 0.00 |
March | 168.71 | 277.11 | 149.37 | 0.00 | 149.37 | 0.00 | 0.00 |
April | 291.78 | 203.89 | 180.68 | 0.62 | 180.06 | 0.00 | 0.00 |
May | 421.36 | 115.61 | 214.10 | 4.77 | 209.32 | 0.00 | 0.00 |
June | 563.50 | 58.89 | 233.80 | 11.72 | 222.08 | 0.00 | 0.00 |
July | 565.53 | 34.22 | 222.06 | 8.50 | 213.56 | 0.00 | 0.00 |
August | 516.71 | 21.21 | 199.08 | 1.51 | 197.57 | 0.00 | 0.00 |
September | 321.20 | 87.91 | 150.88 | 0.03 | 150.85 | 0.00 | 0.00 |
October | 160.96 | 243.87 | 114.66 | 0.00 | 114.66 | 0.00 | 0.00 |
November | 91.85 | 356.41 | 102.62 | 0.00 | 102.62 | 0.00 | 0.00 |
December | 31.52 | 483.19 | 88.71 | 0.00 | 88.71 | 0.00 | 0.00 |
Annual Sum or Average | 270.03 | 245.57 | 155.12 | 2.27 | 152.85 | 0.00 | 0.00 |
Minimum of Months | 22.63 | 21.21 | 88.71 | 0.00 | 88.71 | 0.00 | 0.00 |
Maximum of Months | 565.53 | 597.28 | 233.80 | 11.72 | 222.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.27 | 319.26 | 199.96 | 102.32 | 97.64 | 0.00 | 0.00 |
February | 433.70 | 255.75 | 224.79 | 121.39 | 103.40 | 0.00 | 0.00 |
March | 601.99 | 153.43 | 260.87 | 112.79 | 148.09 | 0.00 | 0.00 |
April | 745.16 | 119.53 | 287.44 | 113.09 | 174.35 | 0.00 | 0.00 |
May | 857.66 | 72.61 | 304.65 | 105.13 | 199.52 | 0.00 | 0.00 |
June | 970.49 | 39.56 | 312.88 | 106.26 | 206.62 | 0.00 | 0.00 |
July | 985.10 | 22.26 | 305.47 | 104.14 | 201.33 | 0.00 | 0.00 |
August | 961.14 | 13.66 | 288.35 | 94.28 | 194.08 | 0.00 | 0.00 |
September | 769.32 | 47.73 | 247.20 | 96.82 | 150.38 | 0.00 | 0.00 |
October | 603.94 | 125.69 | 234.60 | 121.32 | 113.28 | 0.00 | 0.00 |
November | 471.26 | 187.10 | 208.87 | 103.15 | 105.72 | 0.00 | 0.00 |
December | 358.69 | 254.10 | 191.20 | 99.33 | 91.87 | 0.00 | 0.00 |
Annual Sum or Average | 674.64 | 133.62 | 255.68 | 106.57 | 149.12 | 0.00 | 0.00 |
Minimum of Months | 322.27 | 13.66 | 191.20 | 94.28 | 91.87 | 0.00 | 0.00 |
Maximum of Months | 985.10 | 319.26 | 312.88 | 121.39 | 206.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 385.07 | 450.95 | 308.61 | 192.74 | 115.87 | 0.00 | 0.00 |
February | 403.22 | 377.60 | 288.04 | 167.31 | 120.73 | 0.00 | 0.00 |
March | 438.85 | 248.41 | 274.73 | 113.51 | 161.22 | 0.00 | 0.00 |
April | 407.35 | 202.24 | 226.92 | 49.11 | 177.81 | 0.00 | 0.00 |
May | 397.83 | 125.75 | 208.39 | 13.74 | 194.66 | 0.00 | 0.00 |
June | 460.89 | 68.57 | 205.81 | 8.28 | 197.53 | 0.00 | 0.00 |
July | 475.79 | 43.62 | 201.91 | 8.42 | 193.49 | 0.00 | 0.00 |
August | 523.34 | 32.29 | 217.30 | 23.36 | 193.94 | 0.00 | 0.00 |
September | 453.04 | 101.29 | 219.81 | 60.91 | 158.91 | 0.00 | 0.00 |
October | 487.14 | 227.94 | 280.63 | 154.18 | 126.44 | 0.00 | 0.00 |
November | 470.58 | 297.86 | 306.86 | 182.12 | 124.74 | 0.00 | 0.00 |
December | 415.68 | 373.44 | 305.73 | 195.30 | 110.43 | 0.00 | 0.00 |
Annual Sum or Average | 443.51 | 211.63 | 253.60 | 97.09 | 156.51 | 0.00 | 0.00 |
Minimum of Months | 385.07 | 32.29 | 201.91 | 8.28 | 110.43 | 0.00 | 0.00 |
Maximum of Months | 523.34 | 450.95 | 308.61 | 195.30 | 197.53 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.147023E+10 | 0.918273E+09 | 0.100045E+10 | 0.699365E+09 | 0.301084E+09 | 0.00 | 0.00 |
February | 0.131514E+10 | 0.691263E+09 | 0.824519E+09 | 0.548356E+09 | 0.276163E+09 | 0.00 | 0.00 |
March | 0.144339E+10 | 0.500130E+09 | 0.811084E+09 | 0.411891E+09 | 0.399193E+09 | 0.00 | 0.00 |
April | 0.115233E+10 | 0.390056E+09 | 0.579358E+09 | 0.171710E+09 | 0.407648E+09 | 0.00 | 0.00 |
May | 0.100797E+10 | 0.252770E+09 | 0.489858E+09 | 43904413.21 | 0.445953E+09 | 0.00 | 0.00 |
June | 0.100778E+10 | 0.146748E+09 | 0.441276E+09 | 14966727.38 | 0.426309E+09 | 0.00 | 0.00 |
July | 0.108958E+10 | 95480576.97 | 0.456445E+09 | 19989416.40 | 0.436456E+09 | 0.00 | 0.00 |
August | 0.131696E+10 | 75782013.81 | 0.540856E+09 | 82896667.40 | 0.457960E+09 | 0.00 | 0.00 |
September | 0.126697E+10 | 0.198996E+09 | 0.590263E+09 | 0.213845E+09 | 0.376418E+09 | 0.00 | 0.00 |
October | 0.162817E+10 | 0.458910E+09 | 0.875649E+09 | 0.559462E+09 | 0.316186E+09 | 0.00 | 0.00 |
November | 0.159391E+10 | 0.593102E+09 | 0.954026E+09 | 0.639535E+09 | 0.314490E+09 | 0.00 | 0.00 |
December | 0.154325E+10 | 0.772161E+09 | 0.999005E+09 | 0.708649E+09 | 0.290356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.158357E+11 | 0.509367E+10 | 0.856279E+10 | 0.411457E+10 | 0.444822E+10 | 0.00 | 0.00 |
Minimum of Months | 0.100778E+10 | 75782013.81 | 0.441276E+09 | 14966727.38 | 0.276163E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162817E+10 | 0.918273E+09 | 0.100045E+10 | 0.708649E+09 | 0.457960E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.413788E+10 | 0.257985E+10 | 0.281720E+10 | 0.196937E+10 | 0.847832E+09 | 0.00 | 0.00 |
February | 0.371410E+10 | 0.193284E+10 | 0.232179E+10 | 0.154413E+10 | 0.777656E+09 | 0.00 | 0.00 |
March | 0.412003E+10 | 0.134718E+10 | 0.228396E+10 | 0.115986E+10 | 0.112410E+10 | 0.00 | 0.00 |
April | 0.333394E+10 | 0.100914E+10 | 0.163143E+10 | 0.483524E+09 | 0.114791E+10 | 0.00 | 0.00 |
May | 0.298589E+10 | 0.598797E+09 | 0.137941E+10 | 0.123632E+09 | 0.125577E+10 | 0.00 | 0.00 |
June | 0.304187E+10 | 0.303398E+09 | 0.124260E+10 | 42145317.48 | 0.120046E+10 | 0.00 | 0.00 |
July | 0.329054E+10 | 0.173565E+09 | 0.128532E+10 | 56288878.59 | 0.122903E+10 | 0.00 | 0.00 |
August | 0.391986E+10 | 0.118890E+09 | 0.152302E+10 | 0.233432E+09 | 0.128958E+10 | 0.00 | 0.00 |
September | 0.370771E+10 | 0.445283E+09 | 0.166214E+10 | 0.602175E+09 | 0.105997E+10 | 0.00 | 0.00 |
October | 0.465789E+10 | 0.120719E+10 | 0.246577E+10 | 0.157541E+10 | 0.890360E+09 | 0.00 | 0.00 |
November | 0.452020E+10 | 0.162291E+10 | 0.268647E+10 | 0.180089E+10 | 0.885584E+09 | 0.00 | 0.00 |
December | 0.435236E+10 | 0.216049E+10 | 0.281313E+10 | 0.199551E+10 | 0.817622E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.457823E+11 | 0.134995E+11 | 0.241122E+11 | 0.115864E+11 | 0.125259E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298589E+10 | 0.118890E+09 | 0.124260E+10 | 42145317.48 | 0.777656E+09 | 0.00 | 0.00 |
Maximum of Months | 0.465789E+10 | 0.257985E+10 | 0.281720E+10 | 0.199551E+10 | 0.128958E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.540660E+10 | 0.355669E+10 | 0.365970E+10 | 0.255832E+10 | 0.110138E+10 | 0.00 | 0.00 |
February | 0.485245E+10 | 0.268228E+10 | 0.301614E+10 | 0.200592E+10 | 0.101022E+10 | 0.00 | 0.00 |
March | 0.536395E+10 | 0.190941E+10 | 0.296699E+10 | 0.150672E+10 | 0.146027E+10 | 0.00 | 0.00 |
April | 0.431671E+10 | 0.146192E+10 | 0.211933E+10 | 0.628126E+09 | 0.149120E+10 | 0.00 | 0.00 |
May | 0.383271E+10 | 0.911225E+09 | 0.179193E+10 | 0.160605E+09 | 0.163132E+10 | 0.00 | 0.00 |
June | 0.388256E+10 | 0.495567E+09 | 0.161421E+10 | 54749165.92 | 0.155946E+10 | 0.00 | 0.00 |
July | 0.419845E+10 | 0.309353E+09 | 0.166970E+10 | 73122456.72 | 0.159658E+10 | 0.00 | 0.00 |
August | 0.504041E+10 | 0.226067E+09 | 0.197848E+10 | 0.303241E+09 | 0.167524E+10 | 0.00 | 0.00 |
September | 0.478047E+10 | 0.700985E+09 | 0.215922E+10 | 0.782259E+09 | 0.137696E+10 | 0.00 | 0.00 |
October | 0.606172E+10 | 0.173542E+10 | 0.320317E+10 | 0.204655E+10 | 0.115663E+10 | 0.00 | 0.00 |
November | 0.588618E+10 | 0.229097E+10 | 0.348988E+10 | 0.233946E+10 | 0.115042E+10 | 0.00 | 0.00 |
December | 0.567679E+10 | 0.301174E+10 | 0.365442E+10 | 0.259228E+10 | 0.106214E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.592990E+11 | 0.192916E+11 | 0.313232E+11 | 0.150513E+11 | 0.162718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.383271E+10 | 0.226067E+09 | 0.161421E+10 | 54749165.92 | 0.101022E+10 | 0.00 | 0.00 |
Maximum of Months | 0.606172E+10 | 0.355669E+10 | 0.365970E+10 | 0.259228E+10 | 0.167524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438947E+09 | 0.539297E+09 | 0.352109E+09 | 0.209408E+09 | 0.142702E+09 | 0.00 | 0.00 |
February | 0.463590E+09 | 0.398130E+09 | 0.323877E+09 | 0.183805E+09 | 0.140072E+09 | 0.00 | 0.00 |
March | 0.706354E+09 | 0.268652E+09 | 0.423254E+09 | 0.209053E+09 | 0.214201E+09 | 0.00 | 0.00 |
April | 0.747951E+09 | 0.198098E+09 | 0.401706E+09 | 0.166492E+09 | 0.235215E+09 | 0.00 | 0.00 |
May | 0.790511E+09 | 0.113058E+09 | 0.394408E+09 | 0.122417E+09 | 0.271991E+09 | 0.00 | 0.00 |
June | 0.871358E+09 | 50165236.85 | 0.389487E+09 | 0.119964E+09 | 0.269523E+09 | 0.00 | 0.00 |
July | 0.898256E+09 | 24125560.22 | 0.384084E+09 | 0.113181E+09 | 0.270903E+09 | 0.00 | 0.00 |
August | 0.937539E+09 | 11700838.45 | 0.396099E+09 | 0.125409E+09 | 0.270690E+09 | 0.00 | 0.00 |
September | 0.724423E+09 | 76181606.11 | 0.345900E+09 | 0.139075E+09 | 0.206825E+09 | 0.00 | 0.00 |
October | 0.688886E+09 | 0.235964E+09 | 0.382815E+09 | 0.219879E+09 | 0.162936E+09 | 0.00 | 0.00 |
November | 0.547416E+09 | 0.328791E+09 | 0.348446E+09 | 0.197386E+09 | 0.151060E+09 | 0.00 | 0.00 |
December | 0.450854E+09 | 0.443650E+09 | 0.333649E+09 | 0.198915E+09 | 0.134735E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.826608E+10 | 0.268781E+10 | 0.447583E+10 | 0.200498E+10 | 0.247085E+10 | 0.00 | 0.00 |
Minimum of Months | 0.438947E+09 | 11700838.45 | 0.323877E+09 | 0.113181E+09 | 0.134735E+09 | 0.00 | 0.00 |
Maximum of Months | 0.937539E+09 | 0.539297E+09 | 0.423254E+09 | 0.219879E+09 | 0.271991E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177239E+09 | 0.573975E+09 | 0.191024E+09 | 71131092.33 | 0.119893E+09 | 0.00 | 0.00 |
February | 0.243489E+09 | 0.420910E+09 | 0.197618E+09 | 75385602.55 | 0.122232E+09 | 0.00 | 0.00 |
March | 0.489066E+09 | 0.275104E+09 | 0.320044E+09 | 0.127616E+09 | 0.192429E+09 | 0.00 | 0.00 |
April | 0.622361E+09 | 0.203176E+09 | 0.354061E+09 | 0.132769E+09 | 0.221291E+09 | 0.00 | 0.00 |
May | 0.736436E+09 | 0.118113E+09 | 0.379476E+09 | 0.115563E+09 | 0.263913E+09 | 0.00 | 0.00 |
June | 0.857194E+09 | 51829851.10 | 0.388815E+09 | 0.121344E+09 | 0.267471E+09 | 0.00 | 0.00 |
July | 0.873399E+09 | 26636324.96 | 0.378804E+09 | 0.112481E+09 | 0.266323E+09 | 0.00 | 0.00 |
August | 0.850507E+09 | 13042039.24 | 0.365338E+09 | 0.109596E+09 | 0.255742E+09 | 0.00 | 0.00 |
September | 0.577605E+09 | 81898915.11 | 0.285063E+09 | 96803131.92 | 0.188260E+09 | 0.00 | 0.00 |
October | 0.427478E+09 | 0.244651E+09 | 0.253558E+09 | 0.109264E+09 | 0.144295E+09 | 0.00 | 0.00 |
November | 0.278932E+09 | 0.342569E+09 | 0.197818E+09 | 70939221.71 | 0.126879E+09 | 0.00 | 0.00 |
December | 0.180186E+09 | 0.469688E+09 | 0.170074E+09 | 58802334.52 | 0.111272E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.631389E+10 | 0.282159E+10 | 0.348169E+10 | 0.120169E+10 | 0.228000E+10 | 0.00 | 0.00 |
Minimum of Months | 0.177239E+09 | 13042039.24 | 0.170074E+09 | 58802334.52 | 0.111272E+09 | 0.00 | 0.00 |
Maximum of Months | 0.873399E+09 | 0.573975E+09 | 0.388815E+09 | 0.132769E+09 | 0.267471E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.222348E+09 | 0.166571E+09 | 0.158214E+09 | 0.110599E+09 | 47614386.28 | 0.00 | 0.00 |
February | 0.194131E+09 | 0.140922E+09 | 0.130392E+09 | 86718291.19 | 43673354.25 | 0.00 | 0.00 |
March | 0.206501E+09 | 0.114063E+09 | 0.128267E+09 | 65137430.67 | 63129875.37 | 0.00 | 0.00 |
April | 0.162137E+09 | 90338779.27 | 91621658.49 | 27154636.04 | 64467022.44 | 0.00 | 0.00 |
May | 0.139737E+09 | 62410800.50 | 77467966.40 | 6943144.43 | 70524821.97 | 0.00 | 0.00 |
June | 0.142630E+09 | 38030972.36 | 69785194.77 | 2366872.54 | 67418322.23 | 0.00 | 0.00 |
July | 0.155035E+09 | 28789446.21 | 72184018.38 | 3161172.08 | 69022846.31 | 0.00 | 0.00 |
August | 0.191900E+09 | 24966568.11 | 85532975.98 | 13109468.79 | 72423507.20 | 0.00 | 0.00 |
September | 0.184596E+09 | 51745959.82 | 93346083.74 | 33818016.78 | 59528066.96 | 0.00 | 0.00 |
October | 0.240094E+09 | 0.105014E+09 | 0.138478E+09 | 88474644.40 | 50002908.49 | 0.00 | 0.00 |
November | 0.232682E+09 | 0.131775E+09 | 0.150872E+09 | 0.101138E+09 | 49734557.61 | 0.00 | 0.00 |
December | 0.224987E+09 | 0.163131E+09 | 0.157985E+09 | 0.112067E+09 | 45917812.72 | 0.00 | 0.00 |
Annual Sum or Average | 0.229678E+10 | 0.111776E+10 | 0.135415E+10 | 0.650688E+09 | 0.703457E+09 | 0.00 | 0.00 |
Minimum of Months | 0.139737E+09 | 24966568.11 | 69785194.77 | 2366872.54 | 43673354.25 | 0.00 | 0.00 |
Maximum of Months | 0.240094E+09 | 0.166571E+09 | 0.158214E+09 | 0.112067E+09 | 72423507.20 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7821669.70 | 0.175643E+09 | 29380837.38 | 0.00 | 29380837.38 | 0.00 | 0.00 |
February | 20769771.86 | 0.126402E+09 | 29414276.23 | 0.00 | 29414276.23 | 0.00 | 0.00 |
March | 53233388.24 | 78001901.90 | 45731098.23 | 261.50 | 45730836.72 | 0.00 | 0.00 |
April | 87208669.28 | 54938690.62 | 53530384.30 | 182335.43 | 53348048.87 | 0.00 | 0.00 |
May | 0.129539E+09 | 30163167.55 | 65546315.51 | 1461747.95 | 64084567.55 | 0.00 | 0.00 |
June | 0.169014E+09 | 12272816.46 | 69270465.87 | 3471609.20 | 65798856.67 | 0.00 | 0.00 |
July | 0.176179E+09 | 5952234.20 | 67983329.29 | 2602347.42 | 65380981.87 | 0.00 | 0.00 |
August | 0.162710E+09 | 2426505.22 | 60949577.12 | 461876.81 | 60487700.31 | 0.00 | 0.00 |
September | 95699614.38 | 21102216.46 | 44701263.99 | 7580.39 | 44693683.61 | 0.00 | 0.00 |
October | 49967106.93 | 68515992.00 | 35104611.67 | 0.00 | 35104611.67 | 0.00 | 0.00 |
November | 28420977.03 | 99379239.27 | 30403868.52 | 0.00 | 30403868.52 | 0.00 | 0.00 |
December | 10949229.17 | 0.140689E+09 | 27160397.50 | 0.00 | 27160397.50 | 0.00 | 0.00 |
Annual Sum or Average | 0.991513E+09 | 0.815487E+09 | 0.559176E+09 | 8187758.70 | 0.550989E+09 | 0.00 | 0.00 |
Minimum of Months | 7821669.70 | 2426505.22 | 27160397.50 | 0.00 | 27160397.50 | 0.00 | 0.00 |
Maximum of Months | 0.176179E+09 | 0.175643E+09 | 69270465.87 | 3471609.20 | 65798856.67 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.424539E+09 | 0.532622E+09 | 0.348337E+09 | 0.206172E+09 | 0.142165E+09 | 0.00 | 0.00 |
February | 0.475779E+09 | 0.389821E+09 | 0.335050E+09 | 0.201046E+09 | 0.134004E+09 | 0.00 | 0.00 |
March | 0.650614E+09 | 0.256998E+09 | 0.400984E+09 | 0.191772E+09 | 0.209213E+09 | 0.00 | 0.00 |
April | 0.725486E+09 | 0.185464E+09 | 0.396366E+09 | 0.163439E+09 | 0.232928E+09 | 0.00 | 0.00 |
May | 0.823368E+09 | 0.106113E+09 | 0.415470E+09 | 0.144221E+09 | 0.271249E+09 | 0.00 | 0.00 |
June | 0.900135E+09 | 46637850.64 | 0.405857E+09 | 0.137034E+09 | 0.268823E+09 | 0.00 | 0.00 |
July | 0.949525E+09 | 23462270.37 | 0.411750E+09 | 0.139820E+09 | 0.271930E+09 | 0.00 | 0.00 |
August | 0.948634E+09 | 11137940.37 | 0.401565E+09 | 0.134169E+09 | 0.267396E+09 | 0.00 | 0.00 |
September | 0.732172E+09 | 73362270.07 | 0.350806E+09 | 0.146623E+09 | 0.204183E+09 | 0.00 | 0.00 |
October | 0.672166E+09 | 0.227536E+09 | 0.378821E+09 | 0.217783E+09 | 0.161037E+09 | 0.00 | 0.00 |
November | 0.532900E+09 | 0.319747E+09 | 0.346020E+09 | 0.196913E+09 | 0.149107E+09 | 0.00 | 0.00 |
December | 0.451579E+09 | 0.436614E+09 | 0.337854E+09 | 0.203080E+09 | 0.134773E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.828690E+10 | 0.260952E+10 | 0.452888E+10 | 0.208207E+10 | 0.244681E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424539E+09 | 11137940.37 | 0.335050E+09 | 0.134169E+09 | 0.134004E+09 | 0.00 | 0.00 |
Maximum of Months | 0.949525E+09 | 0.532622E+09 | 0.415470E+09 | 0.217783E+09 | 0.271930E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150417E+09 | 0.554753E+09 | 0.187252E+09 | 67895236.33 | 0.119357E+09 | 0.00 | 0.00 |
February | 0.241690E+09 | 0.397870E+09 | 0.208791E+09 | 92626625.78 | 0.116164E+09 | 0.00 | 0.00 |
March | 0.429851E+09 | 0.257170E+09 | 0.297775E+09 | 0.110334E+09 | 0.187441E+09 | 0.00 | 0.00 |
April | 0.600566E+09 | 0.189664E+09 | 0.348721E+09 | 0.129717E+09 | 0.219004E+09 | 0.00 | 0.00 |
May | 0.770758E+09 | 0.112872E+09 | 0.400538E+09 | 0.137367E+09 | 0.263171E+09 | 0.00 | 0.00 |
June | 0.885374E+09 | 49880874.00 | 0.405185E+09 | 0.138413E+09 | 0.266771E+09 | 0.00 | 0.00 |
July | 0.922467E+09 | 26489975.43 | 0.406470E+09 | 0.139120E+09 | 0.267350E+09 | 0.00 | 0.00 |
August | 0.860124E+09 | 12457745.45 | 0.370804E+09 | 0.118356E+09 | 0.252449E+09 | 0.00 | 0.00 |
September | 0.583530E+09 | 78478160.60 | 0.289970E+09 | 0.104352E+09 | 0.185618E+09 | 0.00 | 0.00 |
October | 0.405467E+09 | 0.229575E+09 | 0.249564E+09 | 0.107168E+09 | 0.142396E+09 | 0.00 | 0.00 |
November | 0.251937E+09 | 0.318577E+09 | 0.195392E+09 | 70466088.82 | 0.124926E+09 | 0.00 | 0.00 |
December | 0.161901E+09 | 0.443178E+09 | 0.174279E+09 | 62968254.83 | 0.111311E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.626408E+10 | 0.267097E+10 | 0.353474E+10 | 0.127878E+10 | 0.225596E+10 | 0.00 | 0.00 |
Minimum of Months | 0.150417E+09 | 12457745.45 | 0.174279E+09 | 62968254.83 | 0.111311E+09 | 0.00 | 0.00 |
Maximum of Months | 0.922467E+09 | 0.554753E+09 | 0.406470E+09 | 0.139120E+09 | 0.267350E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.479076E+09 | 0.681404E+09 | 0.406454E+09 | 0.239638E+09 | 0.166816E+09 | 0.00 | 0.00 |
February | 0.472913E+09 | 0.502127E+09 | 0.346244E+09 | 0.187894E+09 | 0.158349E+09 | 0.00 | 0.00 |
March | 0.612600E+09 | 0.342704E+09 | 0.376988E+09 | 0.141135E+09 | 0.235853E+09 | 0.00 | 0.00 |
April | 0.590012E+09 | 0.259141E+09 | 0.314483E+09 | 59231544.53 | 0.255252E+09 | 0.00 | 0.00 |
May | 0.634616E+09 | 0.153520E+09 | 0.309847E+09 | 18210499.38 | 0.291636E+09 | 0.00 | 0.00 |
June | 0.717540E+09 | 78325745.75 | 0.301268E+09 | 12649024.21 | 0.288619E+09 | 0.00 | 0.00 |
July | 0.756650E+09 | 48951802.86 | 0.303677E+09 | 12486937.94 | 0.291190E+09 | 0.00 | 0.00 |
August | 0.803163E+09 | 32087813.31 | 0.317363E+09 | 29405153.29 | 0.287958E+09 | 0.00 | 0.00 |
September | 0.647426E+09 | 0.118345E+09 | 0.299093E+09 | 73290659.54 | 0.225802E+09 | 0.00 | 0.00 |
October | 0.669198E+09 | 0.307706E+09 | 0.376091E+09 | 0.191700E+09 | 0.184391E+09 | 0.00 | 0.00 |
November | 0.603133E+09 | 0.410062E+09 | 0.392763E+09 | 0.219137E+09 | 0.173626E+09 | 0.00 | 0.00 |
December | 0.526495E+09 | 0.555150E+09 | 0.401149E+09 | 0.242819E+09 | 0.158330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.751282E+10 | 0.348952E+10 | 0.414542E+10 | 0.142760E+10 | 0.271782E+10 | 0.00 | 0.00 |
Minimum of Months | 0.472913E+09 | 32087813.31 | 0.299093E+09 | 12486937.94 | 0.158330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.803163E+09 | 0.681404E+09 | 0.406454E+09 | 0.242819E+09 | 0.291636E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.440795E+09 | 0.531426E+09 | 0.352109E+09 | 0.209408E+09 | 0.142702E+09 | 0.00 | 0.00 |
February | 0.464093E+09 | 0.391409E+09 | 0.323877E+09 | 0.183805E+09 | 0.140072E+09 | 0.00 | 0.00 |
March | 0.703730E+09 | 0.262987E+09 | 0.423254E+09 | 0.209053E+09 | 0.214201E+09 | 0.00 | 0.00 |
April | 0.743719E+09 | 0.194123E+09 | 0.401706E+09 | 0.166492E+09 | 0.235215E+09 | 0.00 | 0.00 |
May | 0.784883E+09 | 0.110373E+09 | 0.394408E+09 | 0.122417E+09 | 0.271991E+09 | 0.00 | 0.00 |
June | 0.866383E+09 | 47780592.71 | 0.389487E+09 | 0.119964E+09 | 0.269523E+09 | 0.00 | 0.00 |
July | 0.893651E+09 | 22339049.42 | 0.384084E+09 | 0.113181E+09 | 0.270903E+09 | 0.00 | 0.00 |
August | 0.932999E+09 | 10331059.96 | 0.396099E+09 | 0.125409E+09 | 0.270690E+09 | 0.00 | 0.00 |
September | 0.721224E+09 | 72988839.62 | 0.345900E+09 | 0.139075E+09 | 0.206825E+09 | 0.00 | 0.00 |
October | 0.686865E+09 | 0.230164E+09 | 0.382815E+09 | 0.219879E+09 | 0.162936E+09 | 0.00 | 0.00 |
November | 0.547432E+09 | 0.322179E+09 | 0.348446E+09 | 0.197386E+09 | 0.151060E+09 | 0.00 | 0.00 |
December | 0.452898E+09 | 0.435694E+09 | 0.333649E+09 | 0.198915E+09 | 0.134735E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.823867E+10 | 0.263179E+10 | 0.447583E+10 | 0.200498E+10 | 0.247085E+10 | 0.00 | 0.00 |
Minimum of Months | 0.440795E+09 | 10331059.96 | 0.323877E+09 | 0.113181E+09 | 0.134735E+09 | 0.00 | 0.00 |
Maximum of Months | 0.932999E+09 | 0.531426E+09 | 0.423254E+09 | 0.219879E+09 | 0.271991E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.179365E+09 | 0.565627E+09 | 0.191024E+09 | 71131092.33 | 0.119893E+09 | 0.00 | 0.00 |
February | 0.244646E+09 | 0.413497E+09 | 0.197618E+09 | 75385602.55 | 0.122232E+09 | 0.00 | 0.00 |
March | 0.488151E+09 | 0.269146E+09 | 0.320044E+09 | 0.127616E+09 | 0.192429E+09 | 0.00 | 0.00 |
April | 0.618473E+09 | 0.200550E+09 | 0.354061E+09 | 0.132769E+09 | 0.221291E+09 | 0.00 | 0.00 |
May | 0.730738E+09 | 0.116767E+09 | 0.379476E+09 | 0.115563E+09 | 0.263913E+09 | 0.00 | 0.00 |
June | 0.852495E+09 | 49866876.97 | 0.388815E+09 | 0.121344E+09 | 0.267471E+09 | 0.00 | 0.00 |
July | 0.869080E+09 | 25107468.98 | 0.378804E+09 | 0.112481E+09 | 0.266323E+09 | 0.00 | 0.00 |
August | 0.846580E+09 | 11611986.58 | 0.365338E+09 | 0.109596E+09 | 0.255742E+09 | 0.00 | 0.00 |
September | 0.575266E+09 | 78747294.56 | 0.285063E+09 | 96803131.92 | 0.188260E+09 | 0.00 | 0.00 |
October | 0.427253E+09 | 0.238302E+09 | 0.253558E+09 | 0.109264E+09 | 0.144295E+09 | 0.00 | 0.00 |
November | 0.280814E+09 | 0.334237E+09 | 0.197818E+09 | 70939221.71 | 0.126879E+09 | 0.00 | 0.00 |
December | 0.183369E+09 | 0.460293E+09 | 0.170074E+09 | 58802334.52 | 0.111272E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.629623E+10 | 0.276375E+10 | 0.348169E+10 | 0.120169E+10 | 0.228000E+10 | 0.00 | 0.00 |
Minimum of Months | 0.179365E+09 | 11611986.58 | 0.170074E+09 | 58802334.52 | 0.111272E+09 | 0.00 | 0.00 |
Maximum of Months | 0.869080E+09 | 0.565627E+09 | 0.388815E+09 | 0.132769E+09 | 0.267471E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.416950E+09 | 0.275377E+09 | 0.290102E+09 | 0.202796E+09 | 87306193.21 | 0.00 | 0.00 |
February | 0.374840E+09 | 0.203820E+09 | 0.239087E+09 | 0.159007E+09 | 80079879.25 | 0.00 | 0.00 |
March | 0.415200E+09 | 0.136020E+09 | 0.235192E+09 | 0.119437E+09 | 0.115756E+09 | 0.00 | 0.00 |
April | 0.336217E+09 | 99404764.65 | 0.167998E+09 | 49790999.86 | 0.118207E+09 | 0.00 | 0.00 |
May | 0.302415E+09 | 54401193.65 | 0.142046E+09 | 12731015.90 | 0.129315E+09 | 0.00 | 0.00 |
June | 0.315671E+09 | 22529286.28 | 0.127959E+09 | 4339920.08 | 0.123619E+09 | 0.00 | 0.00 |
July | 0.344683E+09 | 10090338.88 | 0.132357E+09 | 5796355.30 | 0.126561E+09 | 0.00 | 0.00 |
August | 0.412595E+09 | 4361481.03 | 0.156834E+09 | 24037647.11 | 0.132796E+09 | 0.00 | 0.00 |
September | 0.381105E+09 | 36307044.92 | 0.171160E+09 | 62009038.39 | 0.109151E+09 | 0.00 | 0.00 |
October | 0.474300E+09 | 0.118352E+09 | 0.253914E+09 | 0.162228E+09 | 91685810.32 | 0.00 | 0.00 |
November | 0.458584E+09 | 0.167094E+09 | 0.276641E+09 | 0.185447E+09 | 91193759.59 | 0.00 | 0.00 |
December | 0.439678E+09 | 0.227631E+09 | 0.289683E+09 | 0.205488E+09 | 84195339.72 | 0.00 | 0.00 |
Annual Sum or Average | 0.467224E+10 | 0.135539E+10 | 0.248297E+10 | 0.119311E+10 | 0.128987E+10 | 0.00 | 0.00 |
Minimum of Months | 0.302415E+09 | 4361481.03 | 0.127959E+09 | 4339920.08 | 80079879.25 | 0.00 | 0.00 |
Maximum of Months | 0.474300E+09 | 0.275377E+09 | 0.290102E+09 | 0.205488E+09 | 0.132796E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 67208895.00 | 0.154104E+10 | 0.257039E+09 | 0.00 | 0.257039E+09 | 0.00 | 0.00 |
February | 0.183101E+09 | 0.111582E+10 | 0.257331E+09 | 0.00 | 0.257331E+09 | 0.00 | 0.00 |
March | 0.473358E+09 | 0.706027E+09 | 0.400079E+09 | 2287.77 | 0.400077E+09 | 0.00 | 0.00 |
April | 0.779179E+09 | 0.503910E+09 | 0.468311E+09 | 1595163.11 | 0.466716E+09 | 0.00 | 0.00 |
May | 0.115428E+10 | 0.291612E+09 | 0.573433E+09 | 12788115.06 | 0.560644E+09 | 0.00 | 0.00 |
June | 0.148892E+10 | 0.139892E+09 | 0.606013E+09 | 30371404.14 | 0.575642E+09 | 0.00 | 0.00 |
July | 0.154517E+10 | 80892484.90 | 0.594753E+09 | 22766659.71 | 0.571986E+09 | 0.00 | 0.00 |
August | 0.141503E+10 | 46945446.07 | 0.533218E+09 | 4040733.41 | 0.529177E+09 | 0.00 | 0.00 |
September | 0.856053E+09 | 0.210229E+09 | 0.391069E+09 | 66317.09 | 0.391003E+09 | 0.00 | 0.00 |
October | 0.449222E+09 | 0.620626E+09 | 0.307113E+09 | 0.00 | 0.307113E+09 | 0.00 | 0.00 |
November | 0.253935E+09 | 0.880045E+09 | 0.265989E+09 | 0.00 | 0.265989E+09 | 0.00 | 0.00 |
December | 94998372.86 | 0.123707E+10 | 0.237613E+09 | 0.00 | 0.237613E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876045E+10 | 0.737410E+10 | 0.489196E+10 | 71630680.28 | 0.482033E+10 | 0.00 | 0.00 |
Minimum of Months | 67208895.00 | 46945446.07 | 0.237613E+09 | 0.00 | 0.237613E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154517E+10 | 0.154104E+10 | 0.606013E+09 | 30371404.14 | 0.575642E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 60606711.36 | 0.159975E+10 | 0.257039E+09 | 0.00 | 0.257039E+09 | 0.00 | 0.00 |
February | 0.172854E+09 | 0.116401E+10 | 0.257331E+09 | 0.00 | 0.257331E+09 | 0.00 | 0.00 |
March | 0.451861E+09 | 0.742208E+09 | 0.400079E+09 | 2287.77 | 0.400077E+09 | 0.00 | 0.00 |
April | 0.756296E+09 | 0.528478E+09 | 0.468311E+09 | 1595163.11 | 0.466716E+09 | 0.00 | 0.00 |
May | 0.112857E+10 | 0.309645E+09 | 0.573433E+09 | 12788115.06 | 0.560644E+09 | 0.00 | 0.00 |
June | 0.146058E+10 | 0.152651E+09 | 0.606013E+09 | 30371404.14 | 0.575642E+09 | 0.00 | 0.00 |
July | 0.151472E+10 | 91665660.89 | 0.594753E+09 | 22766659.71 | 0.571986E+09 | 0.00 | 0.00 |
August | 0.138395E+10 | 56798601.15 | 0.533218E+09 | 4040733.41 | 0.529177E+09 | 0.00 | 0.00 |
September | 0.832554E+09 | 0.227868E+09 | 0.391069E+09 | 66317.09 | 0.391003E+09 | 0.00 | 0.00 |
October | 0.431114E+09 | 0.653191E+09 | 0.307113E+09 | 0.00 | 0.307113E+09 | 0.00 | 0.00 |
November | 0.238067E+09 | 0.923820E+09 | 0.265989E+09 | 0.00 | 0.265989E+09 | 0.00 | 0.00 |
December | 84423666.46 | 0.129418E+10 | 0.237613E+09 | 0.00 | 0.237613E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851560E+10 | 0.774427E+10 | 0.489196E+10 | 71630680.28 | 0.482033E+10 | 0.00 | 0.00 |
Minimum of Months | 60606711.36 | 56798601.15 | 0.237613E+09 | 0.00 | 0.237613E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151472E+10 | 0.159975E+10 | 0.606013E+09 | 30371404.14 | 0.575642E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.863163E+09 | 0.855109E+09 | 0.535567E+09 | 0.274057E+09 | 0.261510E+09 | 0.00 | 0.00 |
February | 0.104921E+10 | 0.618701E+09 | 0.543816E+09 | 0.293660E+09 | 0.250157E+09 | 0.00 | 0.00 |
March | 0.161237E+10 | 0.410959E+09 | 0.698725E+09 | 0.302090E+09 | 0.396635E+09 | 0.00 | 0.00 |
April | 0.193146E+10 | 0.309824E+09 | 0.745047E+09 | 0.293137E+09 | 0.451910E+09 | 0.00 | 0.00 |
May | 0.229717E+10 | 0.194473E+09 | 0.815963E+09 | 0.281569E+09 | 0.534394E+09 | 0.00 | 0.00 |
June | 0.251551E+10 | 0.102527E+09 | 0.810996E+09 | 0.275428E+09 | 0.535568E+09 | 0.00 | 0.00 |
July | 0.263848E+10 | 59615707.90 | 0.818175E+09 | 0.278921E+09 | 0.539254E+09 | 0.00 | 0.00 |
August | 0.257432E+10 | 36580417.21 | 0.772327E+09 | 0.252507E+09 | 0.519820E+09 | 0.00 | 0.00 |
September | 0.199409E+10 | 0.123715E+09 | 0.640742E+09 | 0.250960E+09 | 0.389782E+09 | 0.00 | 0.00 |
October | 0.161760E+10 | 0.336653E+09 | 0.628356E+09 | 0.324936E+09 | 0.303419E+09 | 0.00 | 0.00 |
November | 0.122150E+10 | 0.484975E+09 | 0.541390E+09 | 0.267369E+09 | 0.274021E+09 | 0.00 | 0.00 |
December | 0.960716E+09 | 0.680574E+09 | 0.512113E+09 | 0.266040E+09 | 0.246073E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.212756E+11 | 0.421371E+10 | 0.806322E+10 | 0.336067E+10 | 0.470254E+10 | 0.00 | 0.00 |
Minimum of Months | 0.863163E+09 | 36580417.21 | 0.512113E+09 | 0.250960E+09 | 0.246073E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263848E+10 | 0.855109E+09 | 0.818175E+09 | 0.324936E+09 | 0.539254E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103136E+10 | 0.120783E+10 | 0.826583E+09 | 0.516227E+09 | 0.310356E+09 | 0.00 | 0.00 |
February | 0.975478E+09 | 0.913480E+09 | 0.696823E+09 | 0.404762E+09 | 0.292061E+09 | 0.00 | 0.00 |
March | 0.117541E+10 | 0.665341E+09 | 0.735842E+09 | 0.304033E+09 | 0.431809E+09 | 0.00 | 0.00 |
April | 0.105585E+10 | 0.524211E+09 | 0.588187E+09 | 0.127292E+09 | 0.460894E+09 | 0.00 | 0.00 |
May | 0.106555E+10 | 0.336816E+09 | 0.558159E+09 | 36791268.41 | 0.521368E+09 | 0.00 | 0.00 |
June | 0.119462E+10 | 0.177728E+09 | 0.533468E+09 | 21458873.90 | 0.512010E+09 | 0.00 | 0.00 |
July | 0.127435E+10 | 0.116836E+09 | 0.540805E+09 | 22559385.90 | 0.518246E+09 | 0.00 | 0.00 |
August | 0.140172E+10 | 86497346.06 | 0.582018E+09 | 62574279.51 | 0.519443E+09 | 0.00 | 0.00 |
September | 0.117429E+10 | 0.262532E+09 | 0.569757E+09 | 0.157870E+09 | 0.411887E+09 | 0.00 | 0.00 |
October | 0.130475E+10 | 0.610520E+09 | 0.751630E+09 | 0.412960E+09 | 0.338670E+09 | 0.00 | 0.00 |
November | 0.121973E+10 | 0.772047E+09 | 0.795385E+09 | 0.472065E+09 | 0.323320E+09 | 0.00 | 0.00 |
December | 0.111337E+10 | 0.100021E+10 | 0.818858E+09 | 0.523080E+09 | 0.295778E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.139865E+11 | 0.667405E+10 | 0.799752E+10 | 0.306167E+10 | 0.493584E+10 | 0.00 | 0.00 |
Minimum of Months | 0.975478E+09 | 86497346.06 | 0.533468E+09 | 21458873.90 | 0.292061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140172E+10 | 0.120783E+10 | 0.826583E+09 | 0.523080E+09 | 0.521368E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770419E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161414077.0 | 81.21 | 0.00 | 0.00 |
February | 0.696176E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145792519.0 | 81.21 | 0.00 | 0.00 |
March | 0.770287E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161406557.4 | 81.21 | 0.00 | 0.00 |
April | 0.746474E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156151238.5 | 81.21 | 0.00 | 0.00 |
May | 0.770418E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161389306.8 | 81.21 | 0.00 | 0.00 |
June | 0.745673E+10 | -0.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156194124.2 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411566.3 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411642.3 | 81.21 | 0.00 | 0.00 |
September | 0.746612E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156187538.0 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412059.0 | 81.21 | 0.00 | 0.00 |
November | 0.744863E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206358.4 | 81.21 | 0.00 | 0.00 |
December | 0.771227E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413882.3 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907408E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190039E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696176E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161414077.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771227E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145792519.0 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.116080E+12 | -0.114306E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177427E+10 | 81.26 | 0.00 | 0.00 |
February | 0.104999E+12 | -0.103383E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.161678E+10 | 81.26 | 0.00 | 0.00 |
March | 0.113682E+12 | -0.111877E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180536E+10 | 81.26 | 0.00 | 0.00 |
April | 0.105406E+12 | -0.103652E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175353E+10 | 81.25 | 0.00 | 0.00 |
May | 0.103254E+12 | -0.101447E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180641E+10 | 81.25 | 0.00 | 0.00 |
June | 0.950361E+11 | -0.933104E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172566E+10 | 81.25 | 0.00 | 0.00 |
July | 0.951549E+11 | -0.933877E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176714E+10 | 81.24 | 0.00 | 0.00 |
August | 0.949228E+11 | -0.931726E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175025E+10 | 81.25 | 0.00 | 0.00 |
September | 0.944256E+11 | -0.927477E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167794E+10 | 81.24 | 0.00 | 0.00 |
October | 0.102388E+12 | -0.100658E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173040E+10 | 81.24 | 0.00 | 0.00 |
November | 0.104564E+12 | -0.102890E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167407E+10 | 81.25 | 0.00 | 0.00 |
December | 0.113046E+12 | -0.111304E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174158E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.124296E+13 | -0.122214E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208234E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.944256E+11 | -0.114306E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.180641E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.116080E+12 | -0.927477E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161678E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.676267E+11 | -0.660981E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152862E+10 | 58.98 | 0.00 | 0.00 |
February | 0.612330E+11 | -0.598326E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.140044E+10 | 58.98 | 0.00 | 0.00 |
March | 0.656393E+11 | -0.640675E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157173E+10 | 58.98 | 0.00 | 0.00 |
April | 0.595206E+11 | -0.579905E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153012E+10 | 58.98 | 0.00 | 0.00 |
May | 0.566245E+11 | -0.550511E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157346E+10 | 58.98 | 0.00 | 0.00 |
June | 0.505859E+11 | -0.490942E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149168E+10 | 58.98 | 0.00 | 0.00 |
July | 0.495846E+11 | -0.480654E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151930E+10 | 58.98 | 0.00 | 0.00 |
August | 0.494248E+11 | -0.479291E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149574E+10 | 58.98 | 0.00 | 0.00 |
September | 0.500113E+11 | -0.485856E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142573E+10 | 58.98 | 0.00 | 0.00 |
October | 0.558063E+11 | -0.543378E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146853E+10 | 58.98 | 0.00 | 0.00 |
November | 0.587294E+11 | -0.573091E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142030E+10 | 58.98 | 0.00 | 0.00 |
December | 0.649957E+11 | -0.635122E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148345E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.689782E+12 | -0.671873E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179091E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.494248E+11 | -0.660981E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157346E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.676267E+11 | -0.479291E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.140044E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.87 | 0.86 | 01-JAN-09:09 | 5322.58 | 33.95 | 270.00 | 275.50 | 808.16 | 25.17 | 149.67 | 246.67 |
February | 263.00 | 0.87 | 0.86 | 01-FEB-13:39 | 4599.82 | 30.52 | 191.00 | 250.33 | 564.83 | 21.38 | 94.33 | 204.33 |
March | 351.67 | 0.87 | 0.86 | 01-MAR-08:50 | 1145.50 | 18.52 | 10.83 | 320.83 | 448.64 | 20.38 | 125.17 | 256.50 |
April | 369.33 | 0.87 | 0.86 | 01-APR-08:30 | 922.31 | 17.92 | 0.00 | 328.50 | 369.19 | 20.16 | 95.83 | 250.33 |
May | 407.00 | 0.87 | 0.86 | 01-MAY-07:49 | 874.03 | 17.86 | 0.00 | 362.17 | 350.94 | 20.11 | 107.83 | 279.83 |
June | 411.67 | 0.87 | 0.86 | 01-JUN-07:10 | 806.90 | 17.61 | 0.00 | 363.33 | 328.91 | 19.88 | 103.33 | 264.00 |
July | 411.00 | 0.87 | 0.86 | 01-JUL-08:30 | 853.86 | 17.72 | 0.00 | 368.50 | 345.05 | 19.97 | 137.33 | 277.67 |
August | 390.50 | 0.87 | 0.86 | 01-AUG-07:40 | 1057.70 | 18.43 | 0.00 | 355.00 | 418.70 | 20.63 | 186.33 | 290.50 |
September | 298.50 | 0.87 | 0.86 | 01-SEP-07:40 | 1112.35 | 18.37 | 0.00 | 312.33 | 444.06 | 20.59 | 129.17 | 241.17 |
October | 293.50 | 0.87 | 0.86 | 01-OCT-10:39 | 2635.60 | 23.97 | 104.83 | 291.50 | 456.30 | 20.46 | 89.00 | 218.67 |
November | 299.00 | 0.87 | 0.86 | 01-NOV-08:30 | 5262.57 | 34.68 | 285.17 | 275.33 | 657.24 | 24.79 | 152.33 | 246.00 |
December | 285.17 | 0.87 | 0.86 | 01-DEC-07:00 | 5008.56 | 34.49 | 270.17 | 271.50 | 910.85 | 26.38 | 158.83 | 237.00 |
Annual Sum or Average | 4071.00 | 0.87 | 2225.39 | 22.78 | 1132.00 | 3774.83 | 487.32 | 21.44 | 1529.17 | 3012.67 | ||
Minimum of Months | 263.00 | 0.87 | 0.86 | 806.90 | 17.61 | 0.00 | 250.33 | 328.91 | 19.88 | 89.00 | 204.33 | |
Maximum of Months | 411.67 | 0.87 | 0.86 | 5322.58 | 34.68 | 285.17 | 368.50 | 910.85 | 26.38 | 186.33 | 290.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.24 | 0.22 | 01-JAN-08:00 | 5641.10 | 34.08 | 271.83 | 283.17 | 1125.84 | 25.13 | 164.50 | 265.83 |
February | 263.00 | 0.26 | 0.22 | 01-FEB-10:20 | 4896.67 | 30.64 | 191.83 | 259.83 | 860.99 | 21.56 | 100.00 | 225.67 |
March | 351.67 | 0.26 | 0.22 | 01-MAR-08:20 | 1381.09 | 19.14 | 11.00 | 333.33 | 683.34 | 20.83 | 154.50 | 301.33 |
April | 369.33 | 0.26 | 0.22 | 01-APR-07:00 | 1092.93 | 18.83 | 0.00 | 344.33 | 539.16 | 20.81 | 157.33 | 305.83 |
May | 407.00 | 0.26 | 0.22 | 01-MAY-07:10 | 1013.72 | 18.93 | 0.00 | 383.00 | 490.03 | 20.90 | 210.33 | 334.83 |
June | 411.67 | 0.26 | 0.22 | 01-JUN-06:49 | 936.05 | 18.72 | 0.00 | 382.83 | 457.51 | 20.71 | 198.00 | 336.67 |
July | 411.00 | 0.26 | 0.22 | 01-JUL-06:40 | 986.82 | 18.81 | 0.00 | 386.50 | 477.42 | 20.78 | 224.50 | 338.50 |
August | 390.50 | 0.25 | 0.22 | 01-AUG-06:49 | 1219.88 | 19.39 | 0.00 | 369.17 | 580.16 | 21.33 | 245.50 | 333.17 |
September | 298.50 | 0.26 | 0.22 | 01-SEP-07:10 | 1312.73 | 19.16 | 0.00 | 325.50 | 643.67 | 21.15 | 165.33 | 291.17 |
October | 293.50 | 0.26 | 0.22 | 01-OCT-07:00 | 2922.07 | 24.18 | 106.33 | 306.17 | 740.83 | 20.67 | 98.33 | 266.83 |
November | 299.00 | 0.25 | 0.22 | 01-NOV-07:00 | 5566.36 | 34.77 | 286.33 | 282.33 | 958.83 | 24.81 | 163.67 | 266.83 |
December | 285.17 | 0.24 | 0.22 | 01-DEC-07:49 | 5333.98 | 34.60 | 271.33 | 280.17 | 1233.87 | 26.33 | 166.33 | 259.50 |
Annual Sum or Average | 4071.00 | 0.26 | 2439.60 | 23.44 | 1138.67 | 3936.33 | 700.52 | 21.91 | 2048.33 | 3526.17 | ||
Minimum of Months | 263.00 | 0.24 | 0.22 | 936.05 | 18.72 | 0.00 | 259.83 | 457.51 | 20.67 | 98.33 | 225.67 | |
Maximum of Months | 411.67 | 0.26 | 0.22 | 5641.10 | 34.77 | 286.33 | 386.50 | 1233.87 | 26.33 | 245.50 | 338.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.67 | 0.60 | 01-JAN-10:50 | 328.66 | 13.05 | 0.00 | 212.33 | 154.83 | 17.07 | 0.00 | 59.83 |
February | 263.00 | 0.68 | 0.60 | 01-FEB-13:39 | 338.66 | 13.22 | 0.00 | 200.67 | 163.15 | 17.20 | 0.00 | 78.33 |
March | 351.67 | 0.64 | 0.60 | 01-MAR-08:00 | 438.06 | 14.80 | 0.00 | 314.83 | 207.72 | 18.60 | 0.00 | 177.50 |
April | 369.33 | 0.63 | 0.60 | 01-APR-08:30 | 531.95 | 15.74 | 0.00 | 340.83 | 246.09 | 19.46 | 0.00 | 229.83 |
May | 407.00 | 0.61 | 0.60 | 01-MAY-07:19 | 675.81 | 17.35 | 17.33 | 391.50 | 311.70 | 21.31 | 57.50 | 347.00 |
June | 411.67 | 0.61 | 0.60 | 01-JUN-06:40 | 747.85 | 19.03 | 55.17 | 393.17 | 347.10 | 22.82 | 144.67 | 366.67 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-05:00 | 753.37 | 17.90 | 27.33 | 395.00 | 336.54 | 22.17 | 132.17 | 355.33 |
August | 390.50 | 0.62 | 0.60 | 01-AUG-06:40 | 671.06 | 16.70 | 0.00 | 370.67 | 308.51 | 20.35 | 21.33 | 327.00 |
September | 298.50 | 0.63 | 0.60 | 01-SEP-07:30 | 492.34 | 15.53 | 0.00 | 316.00 | 235.29 | 19.26 | 0.00 | 208.50 |
October | 293.50 | 0.67 | 0.60 | 01-OCT-10:39 | 344.06 | 13.64 | 0.00 | 229.50 | 171.37 | 17.65 | 0.00 | 103.17 |
November | 299.00 | 0.66 | 0.60 | 01-NOV-09:50 | 339.92 | 13.31 | 0.00 | 241.50 | 162.74 | 17.27 | 0.00 | 66.00 |
December | 285.17 | 0.67 | 0.60 | 01-DEC-09:50 | 318.37 | 13.09 | 0.00 | 213.50 | 152.17 | 17.15 | 0.00 | 44.50 |
Annual Sum or Average | 4071.00 | 0.64 | 523.24 | 15.58 | 99.83 | 3619.50 | 243.91 | 19.48 | 355.67 | 2363.67 | ||
Minimum of Months | 263.00 | 0.61 | 0.60 | 318.37 | 13.05 | 0.00 | 200.67 | 152.17 | 17.07 | 0.00 | 44.50 | |
Maximum of Months | 411.67 | 0.68 | 0.60 | 753.37 | 19.03 | 55.17 | 395.00 | 347.10 | 22.82 | 144.67 | 366.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.67 | 0.60 | 01-JAN-10:50 | 328.66 | 13.05 | 0.00 | 212.33 | 154.83 | 17.07 | 0.00 | 59.83 |
February | 263.00 | 0.68 | 0.60 | 01-FEB-13:39 | 338.66 | 13.22 | 0.00 | 200.67 | 163.15 | 17.20 | 0.00 | 78.33 |
March | 351.67 | 0.64 | 0.60 | 01-MAR-08:00 | 438.06 | 14.80 | 0.00 | 314.83 | 207.72 | 18.60 | 0.00 | 177.50 |
April | 369.33 | 0.63 | 0.60 | 01-APR-08:30 | 531.95 | 15.74 | 0.00 | 340.83 | 246.09 | 19.46 | 0.00 | 229.83 |
May | 407.00 | 0.61 | 0.60 | 01-MAY-07:19 | 675.81 | 17.35 | 17.33 | 391.50 | 311.70 | 21.31 | 57.50 | 347.00 |
June | 411.67 | 0.61 | 0.60 | 01-JUN-06:40 | 747.85 | 19.03 | 55.17 | 393.17 | 347.10 | 22.82 | 144.67 | 366.67 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-05:00 | 753.37 | 17.90 | 27.33 | 395.00 | 336.54 | 22.17 | 132.00 | 355.33 |
August | 390.50 | 0.62 | 0.60 | 01-AUG-06:40 | 671.06 | 16.70 | 0.00 | 370.67 | 308.51 | 20.35 | 21.33 | 327.00 |
September | 298.50 | 0.63 | 0.60 | 01-SEP-07:30 | 492.34 | 15.53 | 0.00 | 316.00 | 235.29 | 19.26 | 0.00 | 208.50 |
October | 293.50 | 0.67 | 0.60 | 01-OCT-10:39 | 344.06 | 13.64 | 0.00 | 229.50 | 171.37 | 17.65 | 0.00 | 103.17 |
November | 299.00 | 0.66 | 0.60 | 01-NOV-09:50 | 339.92 | 13.31 | 0.00 | 241.50 | 162.74 | 17.27 | 0.00 | 66.00 |
December | 285.17 | 0.67 | 0.60 | 01-DEC-09:50 | 318.37 | 13.09 | 0.00 | 213.50 | 152.17 | 17.15 | 0.00 | 44.50 |
Annual Sum or Average | 4071.00 | 0.64 | 523.24 | 15.58 | 99.83 | 3619.50 | 243.91 | 19.48 | 355.50 | 2363.67 | ||
Minimum of Months | 263.00 | 0.61 | 0.60 | 318.37 | 13.05 | 0.00 | 200.67 | 152.17 | 17.07 | 0.00 | 44.50 | |
Maximum of Months | 411.67 | 0.68 | 0.60 | 753.37 | 19.03 | 55.17 | 395.00 | 347.10 | 22.82 | 144.67 | 366.67 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.511905E+11 | 88130.65 | 15-JAN-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328019E+11 | 83577.14 | 11-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170009E+11 | 82579.59 | 19-MAR-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.756262E+10 | 81600.57 | 06-APR-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.287406E+09 | 20932.34 | 14-MAY-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74025242.42 | 8937.19 | 02-JUN-15:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9369.83 | 47.63 | 25-AUG-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147259E+09 | 10441.39 | 14-SEP-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.472914E+10 | 71882.60 | 26-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249085E+11 | 90274.49 | 21-NOV-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.510539E+11 | 84199.62 | 02-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.511905E+11 | 90274.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447576E+09 | 3434.70 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302933E+10 | 6816.08 | 16-APR-16:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.769605E+09 | 5257.75 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 783518.98 | 1305.86 | 01-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.302933E+10 | 6816.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120016E+10 | 1691.41 | 08-JAN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.702729E+09 | 1885.98 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104878E+09 | 854.68 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31464210.90 | 644.04 | 06-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66050102.99 | 760.55 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139041E+09 | 1081.27 | 21-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.619766E+09 | 1241.62 | 01-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120016E+10 | 1885.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276851E+09 | 746.50 | 09-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169816E+09 | 669.98 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10687687.81 | 461.72 | 23-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 873574.90 | 262.30 | 07-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2653236.83 | 234.26 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6608863.35 | 325.36 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 73520892.88 | 436.16 | 22-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276851E+09 | 746.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119114E+09 | 572.64 | 08-JAN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67620056.37 | 479.72 | 13-FEB-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119114E+09 | 572.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143347E+10 | 949.45 | 08-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.871647E+09 | 980.82 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228375E+09 | 556.90 | 19-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48071126.64 | 451.75 | 07-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33344316.11 | 354.02 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200739E+09 | 590.57 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797690E+09 | 717.16 | 18-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143347E+10 | 980.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.239011E+10 | 6062.08 | 09-JAN-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164167E+10 | 5672.30 | 07-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.695449E+09 | 5003.53 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.416225E+09 | 3594.21 | 06-APR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201003E+09 | 2750.22 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51536223.49 | 2528.22 | 08-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28840663.27 | 2367.28 | 28-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4680939.70 | 1712.63 | 31-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98175191.59 | 3301.21 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485827E+09 | 4839.49 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578501E+09 | 4698.25 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141517E+10 | 4660.97 | 22-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.800719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4680939.70 | 1712.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.239011E+10 | 6062.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128076E+10 | 10447.09 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674046E+09 | 8654.04 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33151208.37 | 3772.31 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4260516.14 | 2125.29 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3298772.05 | 998.01 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164726E+09 | 4549.03 | 22-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128076E+10 | 10447.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558731E+10 | 6741.99 | 09-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320669E+10 | 5522.61 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117409E+09 | 3045.00 | 23-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121193E+09 | 3066.34 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433643E+09 | 3561.43 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289654E+10 | 4651.58 | 22-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558731E+10 | 6741.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205237E+10 | 3214.43 | 08-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108690E+10 | 3609.90 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1041667.60 | 257.55 | 23-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82282382.45 | 1677.79 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.627414E+09 | 2355.46 | 18-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205237E+10 | 3609.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103602E+10 | 4540.50 | 27-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.575626E+09 | 4652.25 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59964343.16 | 3121.90 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17524331.24 | 2987.92 | 07-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1037790.93 | 651.79 | 11-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 324695.11 | 215.60 | 15-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38116840.66 | 3047.68 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134800E+09 | 3465.62 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502458E+09 | 4036.73 | 04-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103602E+10 | 4652.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212090E+09 | 2886.78 | 27-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111234E+09 | 2955.42 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2937184.87 | 1321.32 | 20-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1624434.05 | 1102.76 | 06-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2751498.11 | 1542.39 | 26-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6667625.07 | 1785.93 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40010099.71 | 2327.28 | 04-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212090E+09 | 2955.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.661344E+09 | 4007.87 | 07-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.573328E+09 | 5195.00 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6284.50 | 0.26 | 09-MAR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9390.30 | 0.26 | 29-APR-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11181.48 | 0.26 | 08-MAY-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8821.32 | 0.27 | 01-JUN-21:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10742.78 | 0.27 | 24-JUL-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9270.33 | 0.26 | 03-AUG-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12674.53 | 0.26 | 09-SEP-01:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12379.30 | 0.26 | 14-OCT-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35604725.74 | 1146.42 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118947E+09 | 2081.71 | 18-DEC-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6284.50 | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.661344E+09 | 5195.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307549E+10 | 9272.29 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179464E+10 | 9274.37 | 07-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304555E+09 | 9051.66 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78128047.91 | 6610.46 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5025008.00 | 3595.44 | 17-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1471179.67 | 3421.75 | 09-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1142979.24 | 2160.73 | 28-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 346008.58 | 1010.03 | 30-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6765351.41 | 3360.57 | 01-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213322E+09 | 9016.99 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655063E+09 | 9116.07 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191151E+10 | 9172.66 | 25-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.804745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 346008.58 | 1010.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.307549E+10 | 9274.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392577E+10 | 9244.49 | 17-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230312E+10 | 9246.22 | 07-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413489E+09 | 9033.52 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92558172.55 | 7676.03 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4618736.30 | 3201.85 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1050376.13 | 1546.27 | 02-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 571622.78 | 1591.02 | 11-JUL-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 490437.57 | 1467.32 | 25-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4350028.21 | 3261.42 | 15-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268237E+09 | 9022.88 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101944E+10 | 9230.23 | 22-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262641E+10 | 9239.94 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 490437.57 | 1467.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.392577E+10 | 9246.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124175E+11 | 54070.28 | 07-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675998E+10 | 53875.77 | 03-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424947E+09 | 28173.57 | 31-MAR-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124009E+09 | 32814.70 | 06-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28243050.01 | 21721.74 | 15-MAY-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6532224.82 | 10410.64 | 11-JUN-15:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2256907.04 | 9764.21 | 29-JUL-08:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 953291.79 | 7619.17 | 25-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23934328.42 | 19810.00 | 19-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208673E+09 | 27872.67 | 26-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141913E+10 | 52526.21 | 22-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.558351E+10 | 53151.97 | 03-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 953291.79 | 7619.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124175E+11 | 54070.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.310577E+10 | 8981.30 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177201E+10 | 8983.47 | 07-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330696E+09 | 8762.44 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79389075.71 | 4076.97 | 06-APR-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2159691.46 | 2536.83 | 10-MAY-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 201465.12 | 755.93 | 23-JUN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1198258.45 | 2260.53 | 28-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 334151.02 | 856.03 | 24-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4997213.44 | 3059.48 | 30-SEP-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220695E+09 | 8736.07 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.656151E+09 | 8836.35 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188581E+10 | 8897.73 | 25-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 201465.12 | 755.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.310577E+10 | 8983.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.398928E+10 | 8962.03 | 03-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226103E+10 | 8963.21 | 07-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.436146E+09 | 8752.20 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93493665.66 | 3754.09 | 26-APR-18:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2729441.02 | 3080.31 | 10-MAY-21:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 435063.42 | 1221.78 | 10-JUN-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 499224.93 | 1322.33 | 28-JUL-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 50012.75 | 500.13 | 23-AUG-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2747847.54 | 3150.71 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.286096E+09 | 8720.96 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100532E+10 | 8845.87 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.259910E+10 | 8938.96 | 03-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 50012.75 | 500.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.398928E+10 | 8963.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118585E+10 | 2748.73 | 04-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.715742E+09 | 2748.84 | 10-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176693E+09 | 2723.89 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53081076.27 | 2699.94 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2439350.45 | 864.11 | 14-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 419614.59 | 836.38 | 08-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362227.80 | 639.61 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 217236.60 | 423.32 | 07-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5419555.17 | 728.95 | 20-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124652E+09 | 2709.82 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324575E+09 | 2748.85 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788954E+09 | 2748.74 | 31-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 217236.60 | 423.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118585E+10 | 2748.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145965E+10 | 2738.53 | 18-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.882873E+09 | 2737.89 | 10-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218862E+09 | 2715.94 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55286498.00 | 2697.31 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1474759.20 | 956.87 | 14-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 433932.58 | 875.41 | 07-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 145449.73 | 436.82 | 28-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 110987.77 | 321.56 | 25-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2573517.50 | 786.17 | 23-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152088E+09 | 2723.91 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460631E+09 | 2737.86 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102167E+10 | 2737.75 | 31-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 110987.77 | 321.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145965E+10 | 2738.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298610E+10 | 13025.29 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167719E+10 | 13028.37 | 07-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324181E+09 | 12617.48 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136657E+09 | 8386.07 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8484357.89 | 3849.61 | 11-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3501304.01 | 3176.46 | 08-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3175842.78 | 2591.71 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3082291.57 | 2356.92 | 14-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15050637.23 | 4688.77 | 30-SEP-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195261E+09 | 9004.74 | 30-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464805E+09 | 12736.94 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155370E+10 | 12832.20 | 25-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3082291.57 | 2356.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298610E+10 | 13028.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100121E+11 | 0.833602E+10 | 147609.65 | 19-JAN-19:05 | 73754.96 | 0.05 |
February | 0.00 | 0.00 | 0.332174E+11 | 0.324933E+11 | 164166.36 | 28-FEB-17:00 | 164166.36 | 0.07 |
March | 0.00 | 0.00 | 0.957897E+11 | 0.922572E+11 | 238313.42 | 30-MAR-15:19 | 238313.42 | 0.27 |
April | 0.00 | 0.00 | 0.195603E+12 | 0.172005E+12 | 260385.06 | 21-APR-17:15 | 158615.90 | 0.58 |
May | 0.00 | 0.00 | 0.371364E+12 | 0.278972E+12 | 340480.70 | 30-MAY-21:08 | 186767.29 | 0.88 |
June | 0.00 | 0.00 | 0.571566E+12 | 0.389448E+12 | 398581.65 | 26-JUN-18:10 | 197895.93 | 0.91 |
July | 0.00 | 0.00 | 0.728323E+12 | 0.441507E+12 | 402359.73 | 18-JUL-20:00 | 191643.84 | 1.00 |
August | 0.00 | 0.00 | 0.773822E+12 | 0.461850E+12 | 445917.48 | 23-AUG-21:53 | 192750.76 | 1.00 |
September | 0.00 | 0.00 | 0.499281E+12 | 0.332986E+12 | 400097.30 | 27-SEP-18:10 | 191662.03 | 0.97 |
October | 0.00 | 0.00 | 0.201847E+12 | 0.144752E+12 | 425022.16 | 18-OCT-19:40 | 197576.30 | 0.47 |
November | 0.00 | 0.00 | 0.742164E+11 | 0.612485E+11 | 246747.43 | 27-NOV-19:10 | 158807.45 | 0.21 |
December | 0.00 | 0.00 | 0.167323E+11 | 0.141055E+11 | 190741.74 | 13-DEC-11:35 | 105413.38 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.357177E+13 | 0.242996E+13 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 0.100121E+11 | 0.833602E+10 | 147609.65 | 73754.96 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.773822E+12 | 0.461850E+12 | 445917.48 | 238313.42 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.661162E+09 | 0.498469E+09 | 13220.25 | 19-JAN-22:53 | 7342.46 | 0.03 |
February | 0.00 | 0.00 | 0.183383E+10 | 0.181307E+10 | 16173.76 | 28-FEB-16:11 | 16173.76 | 0.04 |
March | 0.00 | 0.00 | 0.677311E+10 | 0.617131E+10 | 22775.54 | 28-MAR-18:01 | 16870.58 | 0.19 |
April | 0.00 | 0.00 | 0.136316E+11 | 0.108940E+11 | 28889.99 | 30-APR-15:13 | 15803.14 | 0.44 |
May | 0.00 | 0.00 | 0.290952E+11 | 0.191693E+11 | 39091.40 | 30-MAY-21:50 | 15428.16 | 0.67 |
June | 0.00 | 0.00 | 0.433860E+11 | 0.268605E+11 | 45326.50 | 29-JUN-08:03 | 17336.41 | 0.71 |
July | 0.00 | 0.00 | 0.545047E+11 | 0.303115E+11 | 49419.14 | 26-JUL-08:03 | 16840.26 | 0.76 |
August | 0.00 | 0.00 | 0.560509E+11 | 0.314444E+11 | 47641.65 | 11-AUG-08:03 | 16944.83 | 0.76 |
September | 0.00 | 0.00 | 0.388569E+11 | 0.234422E+11 | 45944.88 | 17-SEP-08:62 | 17076.44 | 0.74 |
October | 0.00 | 0.00 | 0.155416E+11 | 0.952852E+10 | 43943.87 | 18-OCT-21:52 | 15925.77 | 0.34 |
November | 0.00 | 0.00 | 0.541931E+10 | 0.391187E+10 | 27191.69 | 19-NOV-24:00 | 13347.23 | 0.15 |
December | 0.00 | 0.00 | 0.111104E+10 | 0.885151E+09 | 19299.94 | 12-DEC-13:30 | 14321.98 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.266865E+12 | 0.164930E+12 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.661162E+09 | 0.498469E+09 | 13220.25 | 7342.46 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.560509E+11 | 0.314444E+11 | 49419.14 | 17336.41 | 0.76 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.107381E+09 | 96310934.42 | 12391.25 | 28-JAN-16:11 | 12391.25 | 0.02 |
February | 0.00 | 0.00 | 0.547950E+09 | 0.470338E+09 | 12404.28 | 28-FEB-19:01 | 12404.28 | 0.06 |
March | 0.00 | 0.00 | 0.218432E+10 | 0.140734E+10 | 12877.33 | 28-MAR-15:11 | 9820.41 | 0.33 |
April | 0.00 | 0.00 | 0.400273E+10 | 0.213788E+10 | 13567.07 | 02-APR-15:11 | 9290.64 | 0.70 |
May | 0.00 | 0.00 | 0.617542E+10 | 0.312365E+10 | 13720.81 | 27-MAY-08:62 | 8664.99 | 0.85 |
June | 0.00 | 0.00 | 0.830321E+10 | 0.460212E+10 | 14501.11 | 29-JUN-08:62 | 8560.22 | 0.94 |
July | 0.00 | 0.00 | 0.961915E+10 | 0.540231E+10 | 15157.10 | 27-JUL-08:62 | 8031.10 | 0.94 |
August | 0.00 | 0.00 | 0.101688E+11 | 0.575081E+10 | 14580.90 | 29-AUG-08:62 | 8494.47 | 0.95 |
September | 0.00 | 0.00 | 0.676286E+10 | 0.339140E+10 | 14780.11 | 17-SEP-08:62 | 8325.56 | 0.89 |
October | 0.00 | 0.00 | 0.331203E+10 | 0.157483E+10 | 14385.92 | 01-OCT-15:12 | 8640.07 | 0.64 |
November | 0.00 | 0.00 | 0.106488E+10 | 0.604971E+09 | 13679.94 | 04-NOV-15:12 | 8473.50 | 0.26 |
December | 0.00 | 0.00 | 0.269511E+09 | 0.167017E+09 | 13017.89 | 13-DEC-16:12 | 8438.83 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.525182E+11 | 0.287290E+11 | 0.56 | |||
Minimum of Months | 0.00 | 0.00 | 0.107381E+09 | 96310934.42 | 12391.25 | 8031.10 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.101688E+11 | 0.575081E+10 | 15157.10 | 12404.28 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8936544.89 | 6933000.80 | 4052.70 | 18-JAN-16:14 | 2216.18 | 0.00 |
February | 0.00 | 0.00 | 0.111656E+09 | 80051945.29 | 11593.95 | 24-FEB-19:01 | 11593.95 | 0.03 |
March | 0.00 | 0.00 | 0.958665E+09 | 0.513535E+09 | 12627.69 | 28-MAR-18:01 | 9801.83 | 0.21 |
April | 0.00 | 0.00 | 0.259480E+10 | 0.126642E+10 | 13607.60 | 02-APR-15:11 | 9050.91 | 0.51 |
May | 0.00 | 0.00 | 0.481240E+10 | 0.249269E+10 | 14373.29 | 07-MAY-17:42 | 10220.21 | 0.63 |
June | 0.00 | 0.00 | 0.750250E+10 | 0.437755E+10 | 15297.10 | 26-JUN-08:21 | 8632.84 | 0.78 |
July | 0.00 | 0.00 | 0.869379E+10 | 0.510412E+10 | 15350.02 | 08-JUL-07:51 | 9856.94 | 0.79 |
August | 0.00 | 0.00 | 0.905847E+10 | 0.519861E+10 | 16431.20 | 20-AUG-07:52 | 8344.38 | 0.83 |
September | 0.00 | 0.00 | 0.508062E+10 | 0.251421E+10 | 14835.83 | 17-SEP-08:52 | 7787.20 | 0.67 |
October | 0.00 | 0.00 | 0.157299E+10 | 0.601929E+09 | 14350.37 | 18-OCT-21:52 | 8142.31 | 0.39 |
November | 0.00 | 0.00 | 0.216725E+09 | 95920364.73 | 13037.71 | 05-NOV-15:11 | 9492.45 | 0.11 |
December | 0.00 | 0.00 | 37543532.41 | 22618178.99 | 11374.17 | 07-DEC-16:11 | 11374.17 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.406491E+11 | 0.222746E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 8936544.89 | 6933000.80 | 4052.70 | 2216.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.905847E+10 | 0.519861E+10 | 16431.20 | 11593.95 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.155538E+10 | 0.131057E+10 | 21793.64 | 29-JAN-13:30 | 21793.64 | 0.02 |
February | 0.00 | 0.00 | 0.562673E+10 | 0.539860E+10 | 26496.81 | 26-FEB-14:15 | 26496.81 | 0.02 |
March | 0.00 | 0.00 | 0.171401E+11 | 0.118312E+11 | 27289.55 | 30-MAR-13:30 | 17033.97 | 0.35 |
April | 0.00 | 0.00 | 0.202139E+11 | 0.945219E+10 | 23387.88 | 12-APR-16:10 | 14582.33 | 0.69 |
May | 0.00 | 0.00 | 0.270610E+11 | 0.100271E+11 | 23012.41 | 30-MAY-20:20 | 11936.47 | 0.91 |
June | 0.00 | 0.00 | 0.357936E+11 | 0.144024E+11 | 26393.73 | 25-JUN-08:00 | 13449.16 | 0.98 |
July | 0.00 | 0.00 | 0.427543E+11 | 0.179690E+11 | 28806.63 | 08-JUL-07:51 | 15908.90 | 1.00 |
August | 0.00 | 0.00 | 0.492840E+11 | 0.225565E+11 | 31255.94 | 17-AUG-16:20 | 20541.42 | 1.00 |
September | 0.00 | 0.00 | 0.368034E+11 | 0.163723E+11 | 34040.50 | 25-SEP-16:10 | 26553.84 | 0.97 |
October | 0.00 | 0.00 | 0.263357E+11 | 0.135214E+11 | 36423.73 | 10-OCT-13:30 | 31273.91 | 0.74 |
November | 0.00 | 0.00 | 0.164771E+11 | 0.126007E+11 | 30580.14 | 06-NOV-13:40 | 24591.75 | 0.29 |
December | 0.00 | 0.00 | 0.781383E+10 | 0.626940E+10 | 29773.50 | 12-DEC-12:30 | 19830.23 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.286859E+12 | 0.141711E+12 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.155538E+10 | 0.131057E+10 | 21793.64 | 11936.47 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.492840E+11 | 0.225565E+11 | 36423.73 | 31273.91 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137083E+10 | 0.601177E+09 | 80114.20 | 19-JAN-22:53 | 56403.45 | 0.09 |
February | 0.00 | 0.00 | 0.486348E+10 | 0.295252E+10 | 80675.73 | 18-FEB-09:02 | 61994.35 | 0.15 |
March | 0.00 | 0.00 | 0.139078E+11 | 0.865159E+10 | 79712.88 | 29-MAR-15:11 | 66823.53 | 0.29 |
April | 0.00 | 0.00 | 0.251447E+11 | 0.147626E+11 | 87357.24 | 30-APR-21:52 | 60311.92 | 0.46 |
May | 0.00 | 0.00 | 0.393736E+11 | 0.232624E+11 | 92924.26 | 07-MAY-17:42 | 64431.57 | 0.55 |
June | 0.00 | 0.00 | 0.534035E+11 | 0.332905E+11 | 97491.82 | 26-JUN-08:21 | 54700.07 | 0.71 |
July | 0.00 | 0.00 | 0.603048E+11 | 0.371670E+11 | 98785.14 | 01-JUL-08:31 | 55964.79 | 0.72 |
August | 0.00 | 0.00 | 0.605262E+11 | 0.359761E+11 | 107893.72 | 20-AUG-07:52 | 52056.47 | 0.75 |
September | 0.00 | 0.00 | 0.399353E+11 | 0.222292E+11 | 96032.97 | 17-SEP-08:52 | 52755.42 | 0.59 |
October | 0.00 | 0.00 | 0.200297E+11 | 0.958194E+10 | 95600.12 | 18-OCT-21:52 | 54601.06 | 0.50 |
November | 0.00 | 0.00 | 0.909116E+10 | 0.526582E+10 | 85811.94 | 05-NOV-21:52 | 58625.14 | 0.25 |
December | 0.00 | 0.00 | 0.312839E+10 | 0.158821E+10 | 83186.03 | 13-DEC-21:03 | 58793.34 | 0.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.331079E+12 | 0.195329E+12 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.137083E+10 | 0.601177E+09 | 79712.88 | 52056.47 | 0.09 | |
Maximum of Months | 0.00 | 0.00 | 0.605262E+11 | 0.371670E+11 | 107893.72 | 66823.53 | 0.75 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 70041150.37 | 55321197.57 | 10940.36 | 29-JAN-16:11 | 10940.36 | 0.02 |
February | 0.00 | 0.00 | 0.594719E+09 | 0.500568E+09 | 11280.06 | 28-FEB-19:01 | 11280.06 | 0.07 |
March | 0.00 | 0.00 | 0.194581E+10 | 0.118504E+10 | 11842.97 | 30-MAR-08:62 | 8528.55 | 0.36 |
April | 0.00 | 0.00 | 0.388566E+10 | 0.204474E+10 | 12418.24 | 02-APR-15:11 | 8421.01 | 0.73 |
May | 0.00 | 0.00 | 0.635721E+10 | 0.328557E+10 | 12551.74 | 27-MAY-08:62 | 7970.75 | 0.88 |
June | 0.00 | 0.00 | 0.851637E+10 | 0.476535E+10 | 13154.65 | 23-JUN-08:62 | 7855.50 | 0.96 |
July | 0.00 | 0.00 | 0.996097E+10 | 0.569974E+10 | 13808.12 | 27-JUL-08:62 | 7328.43 | 0.96 |
August | 0.00 | 0.00 | 0.102524E+11 | 0.586134E+10 | 13205.04 | 24-AUG-08:62 | 7805.81 | 0.97 |
September | 0.00 | 0.00 | 0.682268E+10 | 0.348589E+10 | 13478.59 | 17-SEP-08:62 | 7583.26 | 0.91 |
October | 0.00 | 0.00 | 0.327318E+10 | 0.156569E+10 | 13247.04 | 01-OCT-15:12 | 7766.29 | 0.66 |
November | 0.00 | 0.00 | 0.972205E+09 | 0.537519E+09 | 12411.72 | 04-NOV-15:12 | 7654.05 | 0.27 |
December | 0.00 | 0.00 | 0.242472E+09 | 0.136003E+09 | 11803.75 | 13-DEC-16:12 | 7757.81 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.528937E+11 | 0.291228E+11 | 0.57 | |||
Minimum of Months | 0.00 | 0.00 | 70041150.37 | 55321197.57 | 10940.36 | 7328.43 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.102524E+11 | 0.586134E+10 | 13808.12 | 11280.06 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10977240.63 | 9291918.28 | 6679.63 | 29-JAN-09:01 | 6679.63 | 0.00 |
February | 0.00 | 0.00 | 0.185832E+09 | 0.132349E+09 | 10697.63 | 24-FEB-09:02 | 10697.63 | 0.04 |
March | 0.00 | 0.00 | 0.881584E+09 | 0.453476E+09 | 11508.00 | 28-MAR-18:01 | 8975.53 | 0.22 |
April | 0.00 | 0.00 | 0.257723E+10 | 0.128803E+10 | 12503.48 | 02-APR-15:11 | 8218.35 | 0.55 |
May | 0.00 | 0.00 | 0.497160E+10 | 0.261060E+10 | 13179.27 | 07-MAY-17:42 | 9742.91 | 0.66 |
June | 0.00 | 0.00 | 0.760812E+10 | 0.441804E+10 | 14404.88 | 29-JUN-08:51 | 8750.24 | 0.80 |
July | 0.00 | 0.00 | 0.892168E+10 | 0.532415E+10 | 14546.60 | 23-JUL-08:51 | 9297.63 | 0.80 |
August | 0.00 | 0.00 | 0.909330E+10 | 0.521804E+10 | 15065.20 | 20-AUG-07:52 | 7684.71 | 0.84 |
September | 0.00 | 0.00 | 0.510132E+10 | 0.255579E+10 | 14057.53 | 07-SEP-08:31 | 9230.31 | 0.69 |
October | 0.00 | 0.00 | 0.163823E+10 | 0.683334E+09 | 13135.51 | 18-OCT-21:52 | 7452.29 | 0.42 |
November | 0.00 | 0.00 | 0.234362E+09 | 0.102642E+09 | 12372.94 | 05-NOV-15:11 | 8153.74 | 0.10 |
December | 0.00 | 0.00 | 30791729.48 | 15851529.41 | 6994.77 | 13-DEC-21:03 | 3802.09 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.412550E+11 | 0.228116E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 10977240.63 | 9291918.28 | 6679.63 | 3802.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.909330E+10 | 0.532415E+10 | 15065.20 | 10697.63 | 0.84 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 17367307.96 | 15866995.77 | 3245.57 | 29-JAN-16:11 | 3245.57 | 0.00 |
February | 0.00 | 0.00 | 0.119828E+09 | 0.105404E+09 | 3271.44 | 21-FEB-16:11 | 3271.44 | 0.04 |
March | 0.00 | 0.00 | 0.503021E+09 | 0.330136E+09 | 3392.10 | 28-MAR-15:11 | 2589.91 | 0.27 |
April | 0.00 | 0.00 | 0.971662E+09 | 0.544791E+09 | 3607.18 | 23-APR-08:62 | 2079.04 | 0.64 |
May | 0.00 | 0.00 | 0.156734E+10 | 0.816477E+09 | 3740.85 | 27-MAY-08:62 | 2089.93 | 0.85 |
June | 0.00 | 0.00 | 0.215055E+10 | 0.119928E+10 | 3992.08 | 23-JUN-08:62 | 2118.15 | 0.94 |
July | 0.00 | 0.00 | 0.250051E+10 | 0.141149E+10 | 4190.47 | 30-JUL-08:62 | 1922.41 | 0.93 |
August | 0.00 | 0.00 | 0.264122E+10 | 0.149397E+10 | 4029.87 | 29-AUG-08:62 | 2085.16 | 0.95 |
September | 0.00 | 0.00 | 0.165678E+10 | 0.829642E+09 | 4128.27 | 17-SEP-08:62 | 2001.15 | 0.86 |
October | 0.00 | 0.00 | 0.752221E+09 | 0.372499E+09 | 3899.69 | 18-OCT-08:62 | 1919.02 | 0.54 |
November | 0.00 | 0.00 | 0.221026E+09 | 0.131415E+09 | 3646.44 | 04-NOV-15:12 | 2191.33 | 0.19 |
December | 0.00 | 0.00 | 51420698.49 | 32898350.65 | 3462.11 | 13-DEC-16:12 | 2182.63 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.131529E+11 | 0.728388E+10 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 17367307.96 | 15866995.77 | 3245.57 | 1919.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.264122E+10 | 0.149397E+10 | 4190.47 | 3271.44 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2603095.04 | 1785417.81 | 1173.05 | 19-JAN-09:05 | 373.47 | 0.00 |
February | 0.00 | 0.00 | 18938554.86 | 13666360.16 | 3023.49 | 24-FEB-19:01 | 3023.49 | 0.02 |
March | 0.00 | 0.00 | 0.208446E+09 | 0.111662E+09 | 3307.70 | 30-MAR-08:52 | 2242.54 | 0.17 |
April | 0.00 | 0.00 | 0.628314E+09 | 0.320206E+09 | 3618.09 | 02-APR-15:11 | 2350.90 | 0.48 |
May | 0.00 | 0.00 | 0.126451E+10 | 0.675117E+09 | 3825.47 | 07-MAY-17:42 | 2744.31 | 0.64 |
June | 0.00 | 0.00 | 0.198355E+10 | 0.117204E+10 | 4177.84 | 26-JUN-08:21 | 2130.56 | 0.78 |
July | 0.00 | 0.00 | 0.230361E+10 | 0.136684E+10 | 4141.25 | 08-JUL-07:51 | 2472.91 | 0.79 |
August | 0.00 | 0.00 | 0.238558E+10 | 0.137799E+10 | 4491.40 | 20-AUG-07:52 | 2001.67 | 0.83 |
September | 0.00 | 0.00 | 0.126753E+10 | 0.628268E+09 | 4028.12 | 17-SEP-08:52 | 1917.85 | 0.66 |
October | 0.00 | 0.00 | 0.334894E+09 | 0.134311E+09 | 3909.79 | 18-OCT-21:52 | 2035.50 | 0.30 |
November | 0.00 | 0.00 | 31045205.44 | 14457970.82 | 3454.47 | 05-NOV-21:52 | 2140.33 | 0.05 |
December | 0.00 | 0.00 | 4268287.21 | 2585025.36 | 1612.70 | 07-DEC-16:11 | 1612.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104333E+11 | 0.581893E+10 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 2603095.04 | 1785417.81 | 1173.05 | 373.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.238558E+10 | 0.137799E+10 | 4491.40 | 3023.49 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101590E+10 | 0.908106E+09 | 15136.52 | 10-JAN-16:11 | 15136.52 | 0.05 |
February | 0.00 | 0.00 | 0.175796E+10 | 0.149318E+10 | 15650.50 | 18-FEB-09:02 | 10335.54 | 0.13 |
March | 0.00 | 0.00 | 0.416501E+10 | 0.283059E+10 | 15286.33 | 30-MAR-08:62 | 10700.92 | 0.41 |
April | 0.00 | 0.00 | 0.564220E+10 | 0.310343E+10 | 16650.46 | 21-APR-18:01 | 11407.91 | 0.71 |
May | 0.00 | 0.00 | 0.793840E+10 | 0.395976E+10 | 17033.36 | 31-MAY-08:62 | 10682.16 | 0.85 |
June | 0.00 | 0.00 | 0.104082E+11 | 0.557059E+10 | 19052.38 | 29-JUN-08:62 | 9517.14 | 0.93 |
July | 0.00 | 0.00 | 0.123722E+11 | 0.679239E+10 | 19647.00 | 27-JUL-08:62 | 8882.81 | 0.93 |
August | 0.00 | 0.00 | 0.137427E+11 | 0.800171E+10 | 18983.20 | 29-AUG-08:62 | 9570.82 | 0.95 |
September | 0.00 | 0.00 | 0.995569E+10 | 0.544298E+10 | 18829.84 | 17-SEP-08:62 | 9684.17 | 0.88 |
October | 0.00 | 0.00 | 0.654340E+10 | 0.376486E+10 | 18096.45 | 18-OCT-08:62 | 9286.23 | 0.74 |
November | 0.00 | 0.00 | 0.384311E+10 | 0.258144E+10 | 16687.90 | 04-NOV-15:12 | 10842.63 | 0.42 |
December | 0.00 | 0.00 | 0.200346E+10 | 0.159482E+10 | 16003.92 | 13-DEC-16:12 | 11134.43 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.793883E+11 | 0.460438E+11 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.101590E+10 | 0.908106E+09 | 15136.52 | 8882.81 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.137427E+11 | 0.800171E+10 | 19647.00 | 15136.52 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14.71 | 1973.81 | 21-JAN-00:20 | 36707.58 | 197743.24 | 09-JAN-16:11 |
February | 39.43 | 3010.83 | 01-FEB-21:03 | 24744.62 | 180186.89 | 07-FEB-09:01 |
March | 20.89 | 2027.36 | 16-MAR-23:05 | 7865.05 | 113522.27 | 22-MAR-08:62 |
April | 1.26 | 2328.94 | 06-APR-03:40 | 4511.53 | 103510.85 | 06-APR-08:04 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 480.58 | 44565.52 | 15-MAY-08:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 60.16 | 29642.17 | 11-JUN-15:17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.23 | 20880.24 | 29-JUL-08:58 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 6.67 | 14864.53 | 25-AUG-08:56 |
September | 0.02 | 25.15 | 30-SEP-09:30 | 120.77 | 33152.55 | 21-SEP-08:55 |
October | 35.93 | 2180.14 | 30-OCT-19:40 | 2624.10 | 104404.64 | 26-OCT-08:03 |
November | 48.25 | 3470.28 | 19-NOV-09:20 | 12399.32 | 121864.61 | 30-NOV-16:11 |
December | 33.22 | 3197.70 | 07-DEC-19:03 | 28128.54 | 174066.02 | 25-DEC-16:11 |
Annual Sum or Average | 15.99 | 9743.27 | ||||
Minimum of Months | 0.00 | 0.00 | 6.67 | 14864.53 | ||
Maximum of Months | 48.25 | 3470.28 | 36707.58 | 197743.24 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7046.76 | 197335.24 | 19-JAN-22:53 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 21922.91 | 315860.13 | 26-FEB-16:12 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 56325.50 | 399537.55 | 30-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 108633.79 | 413560.14 | 12-APR-15:14 | 0.00 | 0.00 | 01-APR-00:10 |
May | 189283.09 | 498155.56 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 292173.92 | 554470.03 | 26-JUN-21:52 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 353610.57 | 573416.59 | 06-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 374798.39 | 632444.02 | 23-AUG-21:53 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 253943.57 | 565780.81 | 16-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 107476.36 | 557372.41 | 18-OCT-21:52 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 45432.35 | 378085.83 | 05-NOV-15:13 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13326.31 | 213646.17 | 13-DEC-09:53 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 152814.32 | 0.00 | ||||
Minimum of Months | 7046.76 | 197335.24 | 0.00 | 0.00 | ||
Maximum of Months | 374798.39 | 632444.02 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 26247.83 | 53484.87 | 27-JAN-07:58 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26300.84 | 53507.22 | 03-FEB-07:58 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25490.80 | 52666.08 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23942.05 | 49832.10 | 03-APR-06:36 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22131.75 | 46396.93 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20522.52 | 42613.49 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19532.35 | 39745.38 | 03-JUL-06:55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 19481.56 | 39562.97 | 31-AUG-06:57 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20327.61 | 41995.97 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21867.19 | 45850.28 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23685.91 | 49453.01 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 25284.19 | 52187.48 | 28-DEC-07:53 |
Annual Sum or Average | 0.00 | 22881.84 | ||||
Minimum of Months | 0.00 | 0.00 | 19481.56 | 39562.97 | ||
Maximum of Months | 0.00 | 0.00 | 26300.84 | 53507.22 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.69 | 1299.30 | 01-JAN-00:05 | 0.91 |
February | 0.236042E+10 | 0.69 | 1299.30 | 01-FEB-00:05 | 0.91 |
March | 0.261333E+10 | 0.69 | 1299.30 | 01-MAR-00:05 | 0.91 |
April | 0.252903E+10 | 0.69 | 1299.30 | 01-APR-00:10 | 0.91 |
May | 0.261333E+10 | 0.69 | 1299.30 | 01-MAY-00:10 | 0.90 |
June | 0.252903E+10 | 0.69 | 1299.30 | 01-JUN-00:10 | 0.90 |
July | 0.261333E+10 | 0.69 | 1299.30 | 01-JUL-00:10 | 0.90 |
August | 0.261333E+10 | 0.69 | 1299.30 | 01-AUG-00:10 | 0.90 |
September | 0.252903E+10 | 0.69 | 1299.30 | 01-SEP-00:10 | 0.90 |
October | 0.261333E+10 | 0.69 | 1299.30 | 01-OCT-00:10 | 0.90 |
November | 0.252903E+10 | 0.69 | 1299.30 | 01-NOV-00:10 | 0.91 |
December | 0.261333E+10 | 0.69 | 1299.30 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.307698E+11 | 0.69 | |||
Minimum of Months | 0.236042E+10 | 0.69 | 1299.30 | 0.90 | |
Maximum of Months | 0.261333E+10 | 0.69 | 1299.30 | 0.91 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.412524E+11 | 0.97 | 21960.28 | 16-JAN-20:20 | 1.20 |
February | 0.376939E+11 | 0.98 | 22075.85 | 27-FEB-20:20 | 1.20 |
March | 0.425751E+11 | 0.98 | 24786.87 | 30-MAR-21:10 | 1.28 |
April | 0.417524E+11 | 0.99 | 23662.44 | 18-APR-21:20 | 1.25 |
May | 0.440368E+11 | 1.00 | 25953.53 | 18-MAY-21:10 | 1.32 |
June | 0.440807E+11 | 1.02 | 28262.45 | 13-JUN-21:20 | 1.39 |
July | 0.461007E+11 | 1.02 | 29997.29 | 07-JUL-21:40 | 1.44 |
August | 0.466688E+11 | 1.03 | 30400.35 | 18-AUG-21:40 | 1.45 |
September | 0.434653E+11 | 1.01 | 29662.01 | 07-SEP-21:20 | 1.43 |
October | 0.435035E+11 | 0.99 | 27191.65 | 18-OCT-21:10 | 1.35 |
November | 0.415275E+11 | 0.99 | 23541.42 | 09-NOV-21:10 | 1.25 |
December | 0.417081E+11 | 0.97 | 22767.35 | 01-DEC-19:40 | 1.23 |
Annual Sum or Average | 0.514365E+12 | 1.00 | |||
Minimum of Months | 0.376939E+11 | 0.97 | 21960.28 | 1.20 | |
Maximum of Months | 0.466688E+11 | 1.03 | 30400.35 | 1.45 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:05 | 0.27 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:05 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:10 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168171E+09 | 0.42 | 593.44 | 01-JAN-16:12 | 0.59 |
February | 0.129224E+09 | 0.42 | 593.44 | 01-FEB-09:01 | 0.60 |
March | 0.125848E+09 | 0.45 | 593.44 | 02-MAR-16:12 | 0.59 |
April | 0.183462E+09 | 0.49 | 593.44 | 01-APR-08:62 | 0.59 |
May | 0.251784E+09 | 0.52 | 593.44 | 01-MAY-15:11 | 0.59 |
June | 0.332208E+09 | 0.56 | 593.44 | 01-JUN-08:62 | 0.59 |
July | 0.375880E+09 | 0.56 | 593.44 | 01-JUL-08:62 | 0.59 |
August | 0.393252E+09 | 0.56 | 593.44 | 01-AUG-08:61 | 0.59 |
September | 0.265361E+09 | 0.53 | 593.44 | 01-SEP-08:62 | 0.59 |
October | 0.162070E+09 | 0.48 | 593.44 | 01-OCT-08:62 | 0.59 |
November | 98097757.17 | 0.44 | 593.44 | 01-NOV-15:11 | 0.59 |
December | 0.128590E+09 | 0.41 | 593.44 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.261395E+10 | 0.49 | |||
Minimum of Months | 98097757.17 | 0.41 | 593.44 | 0.59 | |
Maximum of Months | 0.393252E+09 | 0.56 | 593.44 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196217E+09 | 0.44 | 586.98 | 01-JAN-16:12 | 0.59 |
February | 0.128279E+09 | 0.39 | 586.98 | 01-FEB-09:01 | 0.60 |
March | 77121851.47 | 0.34 | 586.98 | 02-MAR-19:02 | 0.59 |
April | 0.122550E+09 | 0.36 | 586.98 | 01-APR-08:62 | 0.59 |
May | 0.196986E+09 | 0.39 | 586.98 | 01-MAY-08:53 | 0.59 |
June | 0.304788E+09 | 0.46 | 586.98 | 01-JUN-08:51 | 0.59 |
July | 0.347937E+09 | 0.47 | 586.98 | 01-JUL-08:31 | 0.59 |
August | 0.353635E+09 | 0.49 | 586.98 | 01-AUG-07:51 | 0.59 |
September | 0.198899E+09 | 0.40 | 586.98 | 01-SEP-08:51 | 0.59 |
October | 89252308.04 | 0.34 | 586.98 | 01-OCT-21:52 | 0.59 |
November | 78969467.95 | 0.35 | 586.98 | 05-NOV-08:62 | 0.59 |
December | 0.147893E+09 | 0.39 | 586.98 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.224253E+10 | 0.40 | |||
Minimum of Months | 77121851.47 | 0.34 | 586.98 | 0.59 | |
Maximum of Months | 0.353635E+09 | 0.49 | 586.98 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 61607536.31 | 0.05 | 710.69 | 29-JAN-13:30 | 0.60 |
February | 0.206954E+09 | 0.14 | 841.47 | 26-FEB-14:15 | 0.60 |
March | 0.630505E+09 | 0.41 | 806.66 | 30-MAR-16:20 | 0.59 |
April | 0.726560E+09 | 0.49 | 748.81 | 15-APR-13:40 | 0.59 |
May | 0.905602E+09 | 0.56 | 680.99 | 19-MAY-20:20 | 0.59 |
June | 0.113237E+10 | 0.58 | 759.47 | 13-JUN-20:20 | 0.59 |
July | 0.129362E+10 | 0.59 | 831.48 | 08-JUL-17:30 | 0.59 |
August | 0.146550E+10 | 0.59 | 885.32 | 18-AUG-16:20 | 0.59 |
September | 0.115428E+10 | 0.57 | 995.92 | 24-SEP-12:40 | 0.59 |
October | 0.900485E+09 | 0.47 | 1071.31 | 10-OCT-13:30 | 0.59 |
November | 0.596029E+09 | 0.40 | 952.48 | 15-NOV-14:00 | 0.60 |
December | 0.287616E+09 | 0.19 | 917.62 | 10-DEC-14:30 | 0.60 |
Annual Sum or Average | 0.936113E+10 | 0.42 | |||
Minimum of Months | 61607536.31 | 0.05 | 680.99 | 0.59 | |
Maximum of Months | 0.146550E+10 | 0.59 | 1071.31 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.817640E+09 | 0.39 | 3788.88 | 01-JAN-09:02 | 0.59 |
February | 0.642182E+09 | 0.37 | 3788.88 | 02-FEB-16:11 | 0.60 |
March | 0.678591E+09 | 0.32 | 3788.88 | 01-MAR-09:02 | 0.60 |
April | 0.106541E+10 | 0.32 | 3788.88 | 01-APR-08:62 | 0.60 |
May | 0.160174E+10 | 0.34 | 3788.88 | 01-MAY-08:53 | 0.59 |
June | 0.224381E+10 | 0.42 | 3788.88 | 01-JUN-08:51 | 0.59 |
July | 0.246861E+10 | 0.43 | 3788.88 | 01-JUL-08:31 | 0.59 |
August | 0.245093E+10 | 0.44 | 3788.88 | 01-AUG-07:51 | 0.59 |
September | 0.157551E+10 | 0.35 | 3788.88 | 01-SEP-08:51 | 0.59 |
October | 0.838814E+09 | 0.31 | 3788.88 | 01-OCT-08:53 | 0.59 |
November | 0.535995E+09 | 0.34 | 3788.88 | 01-NOV-08:62 | 0.59 |
December | 0.565071E+09 | 0.39 | 3788.88 | 01-DEC-16:11 | 0.60 |
Annual Sum or Average | 0.154843E+11 | 0.37 | |||
Minimum of Months | 0.535995E+09 | 0.31 | 3788.88 | 0.59 | |
Maximum of Months | 0.246861E+10 | 0.44 | 3788.88 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156468E+09 | 0.42 | 538.88 | 01-JAN-16:12 | 0.59 |
February | 0.122912E+09 | 0.43 | 538.88 | 01-FEB-09:01 | 0.60 |
March | 0.113995E+09 | 0.46 | 538.88 | 02-MAR-16:12 | 0.59 |
April | 0.173407E+09 | 0.51 | 538.88 | 01-APR-08:62 | 0.59 |
May | 0.254009E+09 | 0.55 | 538.88 | 01-MAY-15:11 | 0.59 |
June | 0.340853E+09 | 0.57 | 538.88 | 01-JUN-08:62 | 0.59 |
July | 0.390872E+09 | 0.57 | 538.88 | 01-JUL-08:62 | 0.59 |
August | 0.397275E+09 | 0.57 | 538.88 | 01-AUG-08:61 | 0.59 |
September | 0.264874E+09 | 0.54 | 538.88 | 01-SEP-08:62 | 0.59 |
October | 0.153940E+09 | 0.50 | 538.88 | 01-OCT-08:62 | 0.59 |
November | 90800390.54 | 0.44 | 538.88 | 01-NOV-15:11 | 0.59 |
December | 0.117963E+09 | 0.41 | 538.88 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.257737E+10 | 0.50 | |||
Minimum of Months | 90800390.54 | 0.41 | 538.88 | 0.59 | |
Maximum of Months | 0.397275E+09 | 0.57 | 538.88 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.185906E+09 | 0.43 | 534.64 | 01-JAN-16:12 | 0.59 |
February | 0.121570E+09 | 0.39 | 534.64 | 01-FEB-09:01 | 0.60 |
March | 71815396.95 | 0.34 | 534.64 | 02-MAR-19:02 | 0.59 |
April | 0.118339E+09 | 0.39 | 534.64 | 01-APR-08:62 | 0.59 |
May | 0.201906E+09 | 0.41 | 534.64 | 01-MAY-08:53 | 0.59 |
June | 0.311541E+09 | 0.47 | 534.64 | 01-JUN-08:51 | 0.59 |
July | 0.358086E+09 | 0.47 | 534.64 | 01-JUL-08:31 | 0.59 |
August | 0.358493E+09 | 0.50 | 534.64 | 01-AUG-07:51 | 0.59 |
September | 0.197540E+09 | 0.41 | 534.64 | 01-SEP-08:51 | 0.59 |
October | 89087699.76 | 0.36 | 534.64 | 01-OCT-21:52 | 0.59 |
November | 74796944.57 | 0.34 | 534.64 | 03-NOV-08:62 | 0.59 |
December | 0.137301E+09 | 0.39 | 534.64 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.222638E+10 | 0.41 | |||
Minimum of Months | 71815396.95 | 0.34 | 534.64 | 0.59 | |
Maximum of Months | 0.358493E+09 | 0.50 | 534.64 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 54038669.42 | 0.44 | 156.67 | 01-JAN-16:12 | 0.59 |
February | 40388065.84 | 0.43 | 156.67 | 01-FEB-09:01 | 0.60 |
March | 34774526.83 | 0.45 | 156.67 | 03-MAR-16:11 | 0.59 |
April | 47074524.06 | 0.49 | 156.67 | 01-APR-15:12 | 0.59 |
May | 65065184.77 | 0.53 | 156.67 | 01-MAY-15:11 | 0.59 |
June | 87310324.80 | 0.56 | 156.67 | 01-JUN-08:62 | 0.59 |
July | 99757575.85 | 0.55 | 156.67 | 01-JUL-08:62 | 0.59 |
August | 0.103715E+09 | 0.56 | 156.67 | 01-AUG-08:61 | 0.59 |
September | 66427147.47 | 0.53 | 156.67 | 01-SEP-08:62 | 0.59 |
October | 41506456.75 | 0.48 | 156.67 | 01-OCT-15:12 | 0.59 |
November | 29606918.20 | 0.43 | 156.67 | 01-NOV-15:11 | 0.59 |
December | 41965715.15 | 0.42 | 156.67 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.711630E+09 | 0.49 | |||
Minimum of Months | 29606918.20 | 0.42 | 156.67 | 0.59 | |
Maximum of Months | 0.103715E+09 | 0.56 | 156.67 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 62979018.26 | 0.48 | 154.70 | 01-JAN-16:12 | 0.59 |
February | 41624955.46 | 0.43 | 154.70 | 01-FEB-09:01 | 0.60 |
March | 23274887.94 | 0.34 | 154.70 | 03-MAR-09:02 | 0.59 |
April | 31663244.89 | 0.37 | 154.70 | 02-APR-15:11 | 0.59 |
May | 52531138.21 | 0.40 | 154.70 | 01-MAY-21:51 | 0.59 |
June | 82087570.11 | 0.46 | 154.70 | 01-JUN-08:51 | 0.59 |
July | 94227770.06 | 0.47 | 154.70 | 01-JUL-08:31 | 0.59 |
August | 94362860.45 | 0.49 | 154.70 | 01-AUG-07:51 | 0.59 |
September | 50433565.64 | 0.40 | 154.70 | 01-SEP-08:51 | 0.59 |
October | 24227564.04 | 0.34 | 154.70 | 01-OCT-21:52 | 0.59 |
November | 26800803.65 | 0.36 | 154.70 | 05-NOV-15:11 | 0.59 |
December | 48286410.53 | 0.42 | 154.70 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.632500E+09 | 0.41 | |||
Minimum of Months | 23274887.94 | 0.34 | 154.70 | 0.59 | |
Maximum of Months | 94362860.45 | 0.49 | 154.70 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.194962E+09 | 0.45 | 721.30 | 02-JAN-09:01 | 0.60 |
February | 0.171995E+09 | 0.45 | 721.30 | 01-FEB-09:01 | 0.60 |
March | 0.211780E+09 | 0.48 | 721.30 | 02-MAR-16:12 | 0.59 |
April | 0.252101E+09 | 0.50 | 721.30 | 01-APR-08:62 | 0.59 |
May | 0.317231E+09 | 0.52 | 721.30 | 01-MAY-15:11 | 0.59 |
June | 0.413253E+09 | 0.55 | 721.30 | 01-JUN-08:62 | 0.59 |
July | 0.478669E+09 | 0.55 | 721.30 | 01-JUL-08:62 | 0.59 |
August | 0.534213E+09 | 0.56 | 721.30 | 01-AUG-08:61 | 0.59 |
September | 0.390426E+09 | 0.53 | 721.30 | 01-SEP-08:62 | 0.59 |
October | 0.294242E+09 | 0.51 | 721.30 | 01-OCT-08:62 | 0.59 |
November | 0.202052E+09 | 0.49 | 721.30 | 01-NOV-15:11 | 0.59 |
December | 0.179466E+09 | 0.46 | 721.30 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.364039E+10 | 0.50 | |||
Minimum of Months | 0.171995E+09 | 0.45 | 721.30 | 0.59 | |
Maximum of Months | 0.534213E+09 | 0.56 | 721.30 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128724E+10 | 0.117010E+10 | 1376.98 | 09-JAN-16:11 | 1251.67 | 1251.67 | 37.16 | 2.07 |
February | 0.787323E+09 | 0.715676E+09 | 1309.66 | 14-FEB-09:01 | 1190.48 | 1190.48 | 38.00 | 1.91 |
March | 0.245462E+09 | 0.223125E+09 | 939.40 | 19-MAR-06:30 | 853.91 | 853.91 | 42.54 | 1.20 |
April | 0.125680E+09 | 0.114243E+09 | 969.11 | 06-APR-06:10 | 880.92 | 880.92 | 42.85 | 1.24 |
May | 11575234.22 | 10521887.91 | 452.41 | 15-MAY-08:55 | 411.24 | 411.24 | 39.01 | 0.51 |
June | 1399141.73 | 1271819.83 | 262.87 | 11-JUN-15:17 | 238.94 | 238.94 | 35.01 | 0.28 |
July | 519125.30 | 471884.90 | 253.07 | 29-JUL-08:58 | 230.04 | 230.04 | 41.63 | 0.27 |
August | 260179.75 | 236503.39 | 218.73 | 25-AUG-08:56 | 198.83 | 198.83 | 44.75 | 0.23 |
September | 4524117.97 | 4112423.23 | 416.04 | 19-SEP-08:54 | 378.18 | 378.18 | 46.79 | 0.46 |
October | 0.110607E+09 | 0.100542E+09 | 895.94 | 26-OCT-05:00 | 814.41 | 814.41 | 42.45 | 1.13 |
November | 0.409530E+09 | 0.372262E+09 | 1296.51 | 22-NOV-09:01 | 1178.53 | 1178.53 | 45.19 | 1.87 |
December | 0.956463E+09 | 0.869424E+09 | 1215.84 | 02-DEC-19:01 | 1105.19 | 1105.19 | 35.66 | 1.71 |
Annual Sum or Average | 0.394058E+10 | 0.358199E+10 | ||||||
Minimum of Months | 260179.75 | 236503.39 | 218.73 | 198.83 | 198.83 | 35.01 | 0.23 | |
Maximum of Months | 0.128724E+10 | 0.117010E+10 | 1376.98 | 1251.67 | 1251.67 | 46.79 | 2.07 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 5584038.54 | 5075891.04 | 91.63 | 19-JAN-22:53 | 83.29 | 83.29 | 6.72 | 4.83 |
February | 17590869.06 | 15990099.97 | 229.02 | 26-FEB-16:12 | 208.17 | 208.17 | 6.72 | 7.51 |
March | 82989992.16 | 75437902.88 | 513.77 | 30-MAR-18:03 | 467.02 | 467.02 | 6.72 | 10.82 |
April | 0.200719E+09 | 0.182454E+09 | 761.24 | 13-APR-16:08 | 691.97 | 691.97 | 6.72 | 12.83 |
May | 0.379083E+09 | 0.344586E+09 | 917.58 | 13-MAY-18:01 | 834.08 | 834.08 | 6.72 | 13.89 |
June | 0.716778E+09 | 0.651551E+09 | 1002.35 | 28-JUN-18:03 | 911.14 | 911.14 | 6.72 | 14.42 |
July | 0.966561E+09 | 0.878604E+09 | 1130.44 | 06-JUL-18:03 | 1027.57 | 1027.57 | 6.72 | 15.17 |
August | 0.107516E+10 | 0.977322E+09 | 1126.58 | 10-AUG-18:03 | 1024.06 | 1024.06 | 6.72 | 15.15 |
September | 0.569099E+09 | 0.517311E+09 | 975.54 | 06-SEP-18:03 | 886.77 | 886.77 | 6.72 | 14.26 |
October | 0.199951E+09 | 0.181755E+09 | 815.68 | 18-OCT-18:03 | 741.45 | 741.45 | 6.72 | 13.21 |
November | 49820228.01 | 45286587.26 | 349.17 | 05-NOV-15:11 | 317.40 | 317.40 | 6.72 | 9.11 |
December | 12149787.70 | 11044157.02 | 128.45 | 13-DEC-09:53 | 116.76 | 116.76 | 6.72 | 5.70 |
Annual Sum or Average | 0.427549E+10 | 0.388642E+10 | ||||||
Minimum of Months | 5584038.54 | 5075891.04 | 91.63 | 83.29 | 83.29 | 6.72 | 4.83 | |
Maximum of Months | 0.107516E+10 | 0.977322E+09 | 1130.44 | 1027.57 | 1027.57 | 6.72 | 15.17 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.444614E+10 | 0.404154E+10 | 2886.11 | 01-JAN-00:05 | 2623.48 | 2623.48 | 6.73 | 25.79 |
February | 0.457882E+10 | 0.416215E+10 | 2886.11 | 01-FEB-00:05 | 2623.48 | 2623.48 | 6.79 | 25.79 |
March | 0.702647E+10 | 0.638707E+10 | 2886.11 | 01-MAR-00:05 | 2623.48 | 2623.48 | 7.13 | 25.79 |
April | 0.734020E+10 | 0.667224E+10 | 2886.11 | 01-APR-00:10 | 2623.48 | 2623.48 | 6.86 | 25.79 |
May | 0.773017E+10 | 0.702672E+10 | 2886.11 | 01-MAY-00:10 | 2623.48 | 2623.48 | 7.94 | 25.79 |
June | 0.748081E+10 | 0.680005E+10 | 2886.11 | 01-JUN-00:10 | 2623.48 | 2623.48 | 9.08 | 25.79 |
July | 0.773017E+10 | 0.702672E+10 | 2886.11 | 01-JUL-00:10 | 2623.48 | 2623.48 | 10.05 | 25.79 |
August | 0.773017E+10 | 0.702672E+10 | 2886.11 | 01-AUG-00:10 | 2623.48 | 2623.48 | 9.68 | 25.79 |
September | 0.748081E+10 | 0.680005E+10 | 2886.11 | 01-SEP-00:10 | 2623.48 | 2623.48 | 8.94 | 25.79 |
October | 0.735110E+10 | 0.668215E+10 | 2886.11 | 01-OCT-00:10 | 2623.48 | 2623.48 | 7.46 | 25.79 |
November | 0.657260E+10 | 0.597449E+10 | 2886.11 | 01-NOV-00:10 | 2623.48 | 2623.48 | 6.74 | 25.79 |
December | 0.469200E+10 | 0.426502E+10 | 2886.11 | 01-DEC-01:30 | 2623.48 | 2623.48 | 6.72 | 25.79 |
Annual Sum or Average | 0.801594E+11 | 0.728649E+11 | ||||||
Minimum of Months | 0.444614E+10 | 0.404154E+10 | 2886.11 | 2623.48 | 2623.48 | 6.72 | 25.79 | |
Maximum of Months | 0.773017E+10 | 0.702672E+10 | 2886.11 | 2623.48 | 2623.48 | 10.05 | 25.79 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.85 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 49.70 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 49.44 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.78 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.03 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.73 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.71 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.21 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.77 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.18 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.49 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 50.33 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.85 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.21 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14.71 | 1973.81 | 21-JAN-00:20 | 51.99 | 51.99 | 36707.58 | 197743.24 | 09-JAN-16:11 |
February | 39.43 | 3010.83 | 01-FEB-21:03 | 49.82 | 49.82 | 24744.62 | 180186.89 | 07-FEB-09:01 |
March | 20.89 | 2027.36 | 16-MAR-23:05 | 52.30 | 52.30 | 7865.05 | 113522.27 | 22-MAR-08:62 |
April | 1.26 | 2328.94 | 06-APR-03:40 | 51.24 | 51.24 | 4511.53 | 103510.85 | 06-APR-08:04 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 38.06 | 38.06 | 480.58 | 44565.52 | 15-MAY-08:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 30.87 | 30.87 | 60.16 | 29642.17 | 11-JUN-15:17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 39.04 | 39.04 | 16.23 | 20880.24 | 29-JUL-08:58 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 41.82 | 41.82 | 6.67 | 14864.53 | 25-AUG-08:56 |
September | 0.02 | 25.15 | 30-SEP-09:30 | 49.56 | 49.56 | 120.77 | 33152.55 | 21-SEP-08:55 |
October | 35.93 | 2180.14 | 30-OCT-19:40 | 51.68 | 51.68 | 2624.10 | 104404.64 | 26-OCT-08:03 |
November | 48.25 | 3470.28 | 19-NOV-09:20 | 52.01 | 52.01 | 12399.32 | 121864.61 | 30-NOV-16:11 |
December | 33.22 | 3197.70 | 07-DEC-19:03 | 50.16 | 50.16 | 28128.54 | 174066.02 | 25-DEC-16:11 |
Annual Sum or Average | 15.99 | 9743.27 | ||||||
Minimum of Months | 0.00 | 0.00 | 30.87 | 30.87 | 6.67 | 14864.53 | ||
Maximum of Months | 48.25 | 3470.28 | 52.30 | 52.30 | 36707.58 | 197743.24 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7046.76 | 197335.24 | 19-JAN-22:53 | 8.53 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 21922.91 | 315860.13 | 26-FEB-16:12 | 9.62 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 56325.50 | 399537.55 | 30-MAR-18:03 | 10.40 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 108633.79 | 413560.14 | 12-APR-15:14 | 10.53 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 189283.09 | 498155.56 | 30-MAY-18:03 | 11.31 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 292173.92 | 554470.03 | 26-JUN-21:52 | 11.83 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 353610.57 | 573416.59 | 06-JUL-18:03 | 12.01 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 374798.39 | 632444.02 | 23-AUG-21:53 | 12.56 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 253943.57 | 565780.81 | 16-SEP-18:03 | 11.94 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 107476.36 | 557372.41 | 18-OCT-21:52 | 11.86 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 45432.35 | 378085.83 | 05-NOV-15:13 | 10.20 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13326.31 | 213646.17 | 13-DEC-09:53 | 8.68 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 152814.32 | 0.00 | ||||||
Minimum of Months | 7046.76 | 197335.24 | 8.53 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 374798.39 | 632444.02 | 12.56 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.85 | 59.71 | 26247.83 | 53484.87 | 27-JAN-07:58 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.70 | 59.70 | 26300.84 | 53507.22 | 03-FEB-07:58 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 49.44 | 58.82 | 25490.80 | 52666.08 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.78 | 59.65 | 23942.05 | 49832.10 | 03-APR-06:36 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.03 | 59.28 | 22131.75 | 46396.93 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.73 | 59.58 | 20522.52 | 42613.49 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.71 | 58.78 | 19532.35 | 39745.38 | 03-JUL-06:55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.21 | 59.35 | 19481.56 | 39562.97 | 31-AUG-06:57 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.77 | 59.00 | 20327.61 | 41995.97 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.18 | 59.67 | 21867.19 | 45850.28 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.49 | 58.29 | 23685.91 | 49453.01 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.33 | 59.39 | 25284.19 | 52187.48 | 28-DEC-07:53 |
Annual Sum or Average | 0.00 | 22881.84 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.85 | 58.29 | 19481.56 | 39562.97 | ||
Maximum of Months | 0.00 | 0.00 | 54.21 | 59.71 | 26300.84 | 53507.22 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.667787E+11 | 0.00 | 0.100121E+11 | 0.412524E+11 | 0.00 | 0.00 |
February | 0.419099E+11 | 0.00 | 0.332174E+11 | 0.376939E+11 | 0.00 | 0.00 |
March | 0.187024E+11 | 0.00 | 0.957897E+11 | 0.425751E+11 | 0.00 | 0.00 |
April | 0.111077E+11 | 0.00 | 0.195603E+12 | 0.417524E+11 | 0.00 | 0.00 |
May | 0.125905E+10 | 0.00 | 0.371364E+12 | 0.440368E+11 | 0.00 | 0.00 |
June | 0.126345E+09 | 0.00 | 0.571566E+12 | 0.440807E+11 | 0.00 | 0.00 |
July | 28840663.27 | 0.00 | 0.728323E+12 | 0.461007E+11 | 0.00 | 0.00 |
August | 4690309.52 | 0.00 | 0.773822E+12 | 0.466688E+11 | 0.00 | 0.00 |
September | 0.245759E+09 | 0.00 | 0.499281E+12 | 0.434653E+11 | 0.00 | 0.00 |
October | 0.548334E+10 | 0.00 | 0.201847E+12 | 0.435035E+11 | 0.00 | 0.00 |
November | 0.264941E+11 | 0.00 | 0.742164E+11 | 0.415275E+11 | 0.00 | 0.00 |
December | 0.581912E+11 | 0.00 | 0.167323E+11 | 0.417081E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.230332E+12 | 0.00 | 0.357177E+13 | 0.514365E+12 | 0.00 | 0.00 |
Minimum of Months | 4690309.52 | 0.00 | 0.100121E+11 | 0.376939E+11 | 0.00 | 0.00 |
Maximum of Months | 0.667787E+11 | 0.00 | 0.773822E+12 | 0.466688E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.661344E+09 | 0.00 | 0.661162E+09 | 0.261333E+10 | 0.00 | 0.00 |
February | 0.573328E+09 | 0.00 | 0.183383E+10 | 0.236042E+10 | 0.00 | 0.00 |
March | 6284.50 | 0.00 | 0.677311E+10 | 0.261333E+10 | 0.00 | 0.00 |
April | 9390.30 | 0.00 | 0.136316E+11 | 0.252903E+10 | 0.00 | 0.00 |
May | 11181.48 | 0.00 | 0.290952E+11 | 0.261333E+10 | 0.00 | 0.00 |
June | 8821.32 | 0.00 | 0.433860E+11 | 0.252903E+10 | 0.00 | 0.00 |
July | 10742.78 | 0.00 | 0.545047E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 9270.33 | 0.00 | 0.560509E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 12674.53 | 0.00 | 0.388569E+11 | 0.252903E+10 | 0.00 | 0.00 |
October | 12379.30 | 0.00 | 0.155416E+11 | 0.261333E+10 | 0.00 | 0.00 |
November | 35604725.74 | 0.00 | 0.541931E+10 | 0.252903E+10 | 0.00 | 0.00 |
December | 0.118947E+09 | 0.00 | 0.111104E+10 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.138930E+10 | 0.00 | 0.266865E+12 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 6284.50 | 0.00 | 0.661162E+09 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.661344E+09 | 0.00 | 0.560509E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.412524E+11 | 0.100121E+11 | 0.667787E+11 | 0.139129E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376939E+11 | 0.332174E+11 | 0.419099E+11 | 0.765929E+11 | 33368769.82 | 0.00 | 0.00 | 0.00 |
March | 0.425751E+11 | 0.957897E+11 | 0.187024E+11 | 0.921939E+09 | 0.529160E+09 | 0.00 | 0.00 | 0.00 |
April | 0.417524E+11 | 0.195603E+12 | 0.111077E+11 | 0.150942E+10 | 0.351041E+10 | 0.00 | 0.00 | 0.00 |
May | 0.440368E+11 | 0.371364E+12 | 0.125905E+10 | 0.00 | 0.215399E+11 | 0.00 | 0.00 | 0.00 |
June | 0.440807E+11 | 0.571566E+12 | 0.126345E+09 | 0.00 | 0.827854E+11 | 0.00 | 0.00 | 0.00 |
July | 0.461007E+11 | 0.728323E+12 | 28840663.27 | 0.00 | 0.132900E+12 | 0.00 | 0.00 | 0.00 |
August | 0.466688E+11 | 0.773822E+12 | 4690309.52 | 0.00 | 0.167230E+12 | 0.00 | 0.00 | 0.00 |
September | 0.434653E+11 | 0.499281E+12 | 0.245759E+09 | 0.00 | 0.513368E+11 | 0.00 | 0.00 | 0.00 |
October | 0.435035E+11 | 0.201847E+12 | 0.548334E+10 | 0.00 | 0.938219E+10 | 0.00 | 0.00 | 0.00 |
November | 0.415275E+11 | 0.742164E+11 | 0.264941E+11 | 0.107230E+11 | 0.199075E+09 | 0.00 | 0.00 | 0.00 |
December | 0.417081E+11 | 0.167323E+11 | 0.581912E+11 | 0.379245E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514365E+12 | 0.357177E+13 | 0.230332E+12 | 0.266801E+12 | 0.469446E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.376939E+11 | 0.100121E+11 | 4690309.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.466688E+11 | 0.773822E+12 | 0.667787E+11 | 0.139129E+12 | 0.167230E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.661162E+09 | 0.661344E+09 | 0.402254E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.183383E+10 | 0.573328E+09 | 0.252182E+11 | 1958888.70 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.677311E+10 | 6284.50 | 0.115864E+11 | 0.347272E+09 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.136316E+11 | 9390.30 | 0.538562E+10 | 0.705693E+09 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.290952E+11 | 11181.48 | 0.949427E+09 | 0.409789E+10 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.433860E+11 | 8821.32 | 0.280786E+09 | 0.168546E+11 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.545047E+11 | 10742.78 | 0.00 | 0.277517E+11 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.560509E+11 | 9270.33 | 164961.46 | 0.360488E+11 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.388569E+11 | 12674.53 | 0.180208E+09 | 0.127028E+11 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.155416E+11 | 12379.30 | 0.705528E+10 | 0.205321E+10 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.541931E+10 | 35604725.74 | 0.163468E+11 | 83159625.27 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.111104E+10 | 0.118947E+09 | 0.290714E+11 | 1597726.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.266865E+12 | 0.138930E+10 | 0.136300E+12 | 0.100649E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.661162E+09 | 6284.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.560509E+11 | 0.661344E+09 | 0.402254E+11 | 0.360488E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.412524E+11 | 0.667787E+11 | 0.100121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376939E+11 | 0.419099E+11 | 0.332174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425751E+11 | 0.187024E+11 | 0.957897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.417524E+11 | 0.111077E+11 | 0.195603E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.440368E+11 | 0.125905E+10 | 0.371364E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.440807E+11 | 0.126345E+09 | 0.571566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.461007E+11 | 28840663.27 | 0.728323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.466688E+11 | 4690309.52 | 0.773822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.434653E+11 | 0.245759E+09 | 0.499281E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.435035E+11 | 0.548334E+10 | 0.201847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.415275E+11 | 0.264941E+11 | 0.742164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417081E+11 | 0.581912E+11 | 0.167323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514365E+12 | 0.230332E+12 | 0.357177E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.376939E+11 | 4690309.52 | 0.100121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.466688E+11 | 0.667787E+11 | 0.773822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.661344E+09 | 0.661162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.573328E+09 | 0.183383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 6284.50 | 0.677311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 9390.30 | 0.136316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 11181.48 | 0.290952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 8821.32 | 0.433860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 10742.78 | 0.545047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 9270.33 | 0.560509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 12674.53 | 0.388569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 12379.30 | 0.155416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 35604725.74 | 0.541931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.118947E+09 | 0.111104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.138930E+10 | 0.266865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 6284.50 | 0.661162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.661344E+09 | 0.560509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.456706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
February | 0.385092E+11 | 0.00 | 0.00 | 0.00 | 1424017.97 | 0.00 | 0.00 | 0.00 | 0.71 |
March | 0.370552E+11 | 0.00 | 0.00 | 0.00 | 37699210.17 | 0.00 | 0.00 | 0.00 | 0.80 |
April | 0.269844E+11 | 0.00 | 0.00 | 0.00 | 0.468053E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
May | 0.153031E+11 | 0.00 | 0.00 | 0.00 | 0.263042E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 0.540542E+10 | 0.00 | 0.00 | 0.00 | 0.104980E+11 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.656157E+09 | 0.00 | 0.00 | 0.00 | 0.175650E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.271353E+09 | 0.263446E+10 | 0.00 | 55225.56 | 0.178251E+11 | 0.00 | 28942034.34 | 0.00 | 0.59 |
September | 0.574375E+09 | 0.455510E+10 | 0.00 | 16581541.73 | 0.376602E+10 | 0.00 | 0.915831E+10 | 0.00 | 0.75 |
October | 0.177026E+10 | 0.167482E+10 | 0.00 | 40799128.85 | 0.492891E+09 | 0.00 | 0.302379E+11 | 0.00 | 0.83 |
November | 0.186879E+10 | 49186481.84 | 0.00 | 45809184.16 | 18018896.10 | 0.00 | 0.393784E+11 | 0.00 | 0.81 |
December | 0.257807E+11 | 0.00 | 0.00 | 11009640.51 | 159951.20 | 0.00 | 0.209325E+11 | 0.00 | 0.68 |
Annual Sum or Average | 0.199850E+12 | 0.891356E+10 | 0.00 | 0.114255E+09 | 0.533027E+11 | 0.00 | 0.997360E+11 | 0.00 | 0.72 |
Minimum of Months | 0.271353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.456706E+11 | 0.455510E+10 | 0.00 | 45809184.16 | 0.178251E+11 | 0.00 | 0.393784E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.305261E+10 | 0.00 | 0.00 | 62993.23 | 0.00 | 0.109570E+10 | 87106162.84 | 0.00 | 1.06 |
February | 0.285871E+10 | 144156.42 | 0.00 | 367400.45 | 0.00 | 0.578409E+09 | 0.137391E+09 | 0.00 | 1.21 |
March | 0.312660E+10 | 2633650.53 | 0.00 | 604343.55 | 1345323.93 | 11904445.14 | 0.304024E+09 | 0.00 | 1.36 |
April | 0.222880E+10 | 11278173.55 | 0.00 | 860301.91 | 33796259.25 | 0.00 | 0.275653E+09 | 0.00 | 1.43 |
May | 0.111702E+10 | 0.181080E+09 | 0.00 | 744482.71 | 71281954.85 | 0.00 | 0.305374E+09 | 0.00 | 1.37 |
June | 0.295531E+09 | 0.104157E+10 | 0.00 | 559866.00 | 68105115.15 | 0.00 | 0.208670E+09 | 0.00 | 1.22 |
July | 33833027.44 | 0.178125E+10 | 0.00 | 87713.59 | 0.156261E+09 | 0.00 | 27236797.99 | 0.00 | 1.17 |
August | 2559846.63 | 0.235051E+10 | 0.00 | 71800.32 | 39943734.15 | 0.00 | 25832597.73 | 0.00 | 1.23 |
September | 0.580794E+09 | 0.728279E+09 | 0.00 | 1181701.09 | 0.156983E+09 | 0.00 | 0.307658E+09 | 0.00 | 1.37 |
October | 0.220718E+10 | 0.135582E+09 | 0.00 | 1635281.03 | 78917537.31 | 0.00 | 0.663963E+09 | 0.00 | 1.42 |
November | 0.326218E+10 | 1596669.28 | 0.00 | 838099.13 | 4699426.25 | 51920274.91 | 0.352479E+09 | 0.00 | 1.34 |
December | 0.385146E+10 | 0.00 | 0.00 | 316851.58 | 14826.12 | 0.262779E+09 | 0.222877E+09 | 0.00 | 1.14 |
Annual Sum or Average | 0.226173E+11 | 0.623393E+10 | 0.00 | 7330834.59 | 0.611348E+09 | 0.200072E+10 | 0.291826E+10 | 0.00 | 1.28 |
Minimum of Months | 2559846.63 | 0.00 | 0.00 | 62993.23 | 0.00 | 0.00 | 25832597.73 | 0.00 | 1.06 |
Maximum of Months | 0.385146E+10 | 0.235051E+10 | 0.00 | 1635281.03 | 0.156983E+09 | 0.109570E+10 | 0.663963E+09 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
February | 0.411528E+10 | 0.00 | 0.00 | 2746.73 | 152716.95 | 0.00 | 14589331.79 | 0.00 | 1.20 |
March | 0.390283E+10 | 5110.47 | 0.00 | 37501.44 | 4037892.16 | 0.00 | 71066043.56 | 0.00 | 1.34 |
April | 0.265104E+10 | 0.00 | 0.00 | 159158.71 | 50195774.27 | 0.00 | 0.242703E+09 | 0.00 | 1.40 |
May | 0.129791E+10 | 31494422.84 | 0.00 | 348737.39 | 0.250601E+09 | 0.00 | 0.343120E+09 | 0.00 | 1.35 |
June | 0.275454E+09 | 0.395716E+09 | 0.00 | 375144.25 | 0.734315E+09 | 0.00 | 0.304073E+09 | 0.00 | 1.13 |
July | 29272139.03 | 0.792468E+09 | 0.00 | 67579.02 | 0.110596E+10 | 0.00 | 41029036.93 | 0.00 | 1.01 |
August | 3258484.68 | 0.116856E+10 | 0.00 | 66847.61 | 0.104956E+10 | 0.00 | 28927292.61 | 0.00 | 1.00 |
September | 0.570960E+09 | 0.281073E+09 | 0.00 | 450601.00 | 0.602636E+09 | 0.00 | 0.445855E+09 | 0.00 | 1.24 |
October | 0.292768E+10 | 40647129.05 | 0.00 | 177898.88 | 0.181776E+09 | 0.00 | 0.342338E+09 | 0.00 | 1.33 |
November | 0.415453E+10 | 0.00 | 0.00 | 3362.72 | 7143324.41 | 0.00 | 30183179.18 | 0.00 | 1.29 |
December | 0.499900E+10 | 0.00 | 0.00 | 49.74 | 17153.76 | 0.00 | 1631733.50 | 0.00 | 1.13 |
Annual Sum or Average | 0.298251E+11 | 0.270996E+10 | 0.00 | 1689627.48 | 0.398639E+10 | 0.00 | 0.186552E+10 | 0.00 | 1.21 |
Minimum of Months | 3258484.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Maximum of Months | 0.499900E+10 | 0.116856E+10 | 0.00 | 450601.00 | 0.110596E+10 | 0.00 | 0.445855E+09 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 63359597.79 | 0.00 | 0.00 | 0.00 | 0.00 | 50898389.44 | 0.00 | 0.00 | 0.01 |
February | 55659564.19 | 0.00 | 0.00 | 54998.48 | 2493.06 | 31400659.13 | 23715582.77 | 0.00 | 0.02 |
March | 51023041.89 | 545428.84 | 0.00 | 399397.94 | 10643.28 | 0.00 | 0.148288E+09 | 0.00 | 0.04 |
April | 18615599.57 | 6320497.52 | 0.00 | 1107627.89 | 248730.77 | 0.00 | 0.362321E+09 | 0.00 | 0.11 |
May | 885017.89 | 94756607.25 | 0.00 | 1672858.87 | 0.00 | 0.00 | 0.452626E+09 | 0.00 | 0.20 |
June | 0.00 | 0.653994E+09 | 0.00 | 1010865.44 | 0.00 | 0.00 | 0.253190E+09 | 0.00 | 0.29 |
July | 0.00 | 0.117870E+10 | 0.00 | 172255.61 | 0.00 | 0.00 | 32476036.67 | 0.00 | 0.30 |
August | 0.00 | 0.146797E+10 | 0.00 | 113940.08 | 0.00 | 0.00 | 19020698.97 | 0.00 | 0.32 |
September | 0.00 | 0.454323E+09 | 0.00 | 1332400.79 | 0.00 | 0.00 | 0.387540E+09 | 0.00 | 0.26 |
October | 20178169.11 | 82757812.40 | 0.00 | 1031162.44 | 0.00 | 0.00 | 0.434945E+09 | 0.00 | 0.11 |
November | 52124145.53 | 413969.65 | 0.00 | 337795.46 | 59513.24 | 0.00 | 0.161266E+09 | 0.00 | 0.04 |
December | 79373322.91 | 0.00 | 0.00 | 45287.07 | 280.03 | 0.00 | 23173530.62 | 0.00 | 0.01 |
Annual Sum or Average | 0.341218E+09 | 0.393978E+10 | 0.00 | 7278590.07 | 321660.39 | 82299048.57 | 0.229856E+10 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 79373322.91 | 0.146797E+10 | 0.00 | 1672858.87 | 248730.77 | 50898389.44 | 0.452626E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148495E+10 | 0.00 | 0.00 | 0.55 |
February | 0.172218E+10 | 0.00 | 0.00 | 0.00 | 96277.07 | 0.881406E+09 | 0.00 | 0.00 | 0.62 |
March | 0.250528E+10 | 0.00 | 0.00 | 0.00 | 2548822.93 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 0.182440E+10 | 0.00 | 0.00 | 0.00 | 31644832.34 | 0.00 | 0.00 | 0.00 | 0.72 |
May | 0.103464E+10 | 0.00 | 0.00 | 0.00 | 0.177841E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
June | 0.365457E+09 | 0.00 | 0.00 | 0.00 | 0.709762E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 44362448.54 | 0.00 | 0.00 | 0.00 | 0.118756E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 20306534.85 | 0.00 | 0.00 | 0.00 | 0.138326E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.641029E+09 | 0.00 | 0.00 | 0.00 | 0.555057E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.206146E+10 | 0.00 | 0.00 | 0.00 | 0.140219E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
November | 0.263816E+10 | 0.00 | 0.00 | 0.00 | 4503353.25 | 0.00 | 0.00 | 0.00 | 0.67 |
December | 0.295999E+10 | 0.00 | 0.00 | 0.00 | 10814.21 | 0.192552E+09 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.174201E+11 | 0.00 | 0.00 | 0.00 | 0.419250E+10 | 0.255891E+10 | 0.00 | 0.00 | 0.62 |
Minimum of Months | 20306534.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.295999E+10 | 0.00 | 0.00 | 0.00 | 0.138326E+10 | 0.148495E+10 | 0.00 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.100266E+09 | 0.00 | 0.00 | 0.613383E+11 | 0.00 | 13.28 |
February | 0.00 | 1638064.85 | 0.00 | 92432144.67 | 0.00 | 0.00 | 0.521325E+11 | 0.00 | 15.35 |
March | 0.00 | 48781804.86 | 0.00 | 0.104819E+09 | 0.00 | 0.00 | 0.508339E+11 | 0.00 | 17.68 |
April | 0.00 | 0.595042E+09 | 0.00 | 98396201.20 | 0.00 | 0.00 | 0.367115E+11 | 0.00 | 18.48 |
May | 0.00 | 0.362435E+10 | 0.00 | 74130609.56 | 0.00 | 0.00 | 0.199579E+11 | 0.00 | 17.64 |
June | 0.00 | 0.150205E+11 | 0.00 | 29685263.32 | 0.00 | 0.00 | 0.695495E+10 | 0.00 | 14.77 |
July | 0.00 | 0.250294E+11 | 0.00 | 4246232.21 | 0.00 | 0.00 | 0.733185E+09 | 0.00 | 13.12 |
August | 0.00 | 0.293410E+11 | 0.00 | 2330708.47 | 0.00 | 0.00 | 0.346121E+09 | 0.00 | 13.04 |
September | 0.00 | 0.117817E+11 | 0.00 | 45176032.84 | 0.00 | 0.00 | 0.129399E+11 | 0.00 | 16.13 |
October | 0.00 | 0.298785E+10 | 0.00 | 91380297.61 | 0.00 | 0.00 | 0.423397E+11 | 0.00 | 17.40 |
November | 0.00 | 86177201.07 | 0.00 | 97578448.03 | 0.00 | 0.00 | 0.541314E+11 | 0.00 | 16.78 |
December | 0.00 | 175736.51 | 0.00 | 99374080.37 | 0.00 | 0.00 | 0.631806E+11 | 0.00 | 14.34 |
Annual Sum or Average | 0.00 | 0.885167E+11 | 0.00 | 0.839815E+09 | 0.00 | 0.00 | 0.401600E+12 | 0.00 | 15.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2330708.47 | 0.00 | 0.00 | 0.346121E+09 | 0.00 | 13.04 |
Maximum of Months | 0.00 | 0.293410E+11 | 0.00 | 0.104819E+09 | 0.00 | 0.00 | 0.631806E+11 | 0.00 | 18.48 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332712E+11 | 0.00 | 0.00 | 369304.12 | 0.00 | 0.00 | 0.287315E+10 | 0.00 | 3.22 |
February | 0.246593E+11 | 209506.51 | 0.00 | 1355861.35 | 917491.36 | 0.00 | 0.581628E+10 | 0.00 | 3.64 |
March | 0.173252E+11 | 7545769.74 | 0.00 | 3652259.64 | 22290180.90 | 0.00 | 0.119974E+11 | 0.00 | 4.08 |
April | 0.110732E+11 | 28102429.37 | 0.00 | 4351455.99 | 0.342325E+09 | 0.00 | 0.102784E+11 | 0.00 | 4.24 |
May | 0.374413E+10 | 0.352308E+09 | 0.00 | 5690688.83 | 0.172946E+10 | 0.00 | 0.836141E+10 | 0.00 | 4.08 |
June | 0.112604E+10 | 0.343630E+10 | 0.00 | 2701921.89 | 0.487201E+10 | 0.00 | 0.314923E+10 | 0.00 | 3.41 |
July | 62442735.56 | 0.676882E+10 | 0.00 | 725890.39 | 0.713248E+10 | 0.00 | 0.456128E+09 | 0.00 | 3.05 |
August | 33280526.66 | 0.101837E+11 | 0.00 | 491548.77 | 0.600882E+10 | 0.00 | 0.203932E+09 | 0.00 | 3.01 |
September | 0.228197E+10 | 0.314317E+10 | 0.00 | 4713350.26 | 0.335421E+10 | 0.00 | 0.521706E+10 | 0.00 | 3.74 |
October | 0.117027E+11 | 0.767499E+09 | 0.00 | 5380139.21 | 0.873879E+09 | 0.00 | 0.124229E+11 | 0.00 | 4.03 |
November | 0.190495E+11 | 2311750.75 | 0.00 | 3590982.09 | 50403494.37 | 0.00 | 0.118287E+11 | 0.00 | 3.93 |
December | 0.302286E+11 | 0.00 | 0.00 | 1305685.98 | 126588.75 | 0.00 | 0.667298E+10 | 0.00 | 3.43 |
Annual Sum or Average | 0.154558E+12 | 0.246900E+11 | 0.00 | 34329088.51 | 0.243869E+11 | 0.00 | 0.792776E+11 | 0.00 | 3.65 |
Minimum of Months | 33280526.66 | 0.00 | 0.00 | 369304.12 | 0.00 | 0.00 | 0.203932E+09 | 0.00 | 3.01 |
Maximum of Months | 0.332712E+11 | 0.101837E+11 | 0.00 | 5690688.83 | 0.713248E+10 | 0.00 | 0.124229E+11 | 0.00 | 4.24 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.996574E+11 | 0.00 | 0.00 | 355229.80 | 0.00 | 0.00 | 0.152490E+10 | 0.00 | 1.30 |
February | 0.763228E+11 | 0.00 | 0.00 | 2940057.69 | 3154894.42 | 0.00 | 0.899088E+10 | 0.00 | 1.47 |
March | 0.570591E+11 | 1097263.64 | 0.00 | 11594488.97 | 82424876.10 | 0.00 | 0.250276E+11 | 0.00 | 1.65 |
April | 0.306041E+11 | 23360068.35 | 0.00 | 19243610.22 | 0.101361E+10 | 0.00 | 0.291780E+11 | 0.00 | 1.72 |
May | 0.860753E+10 | 0.923778E+09 | 0.00 | 29875229.89 | 0.490994E+10 | 0.00 | 0.252991E+11 | 0.00 | 1.66 |
June | 0.220420E+10 | 0.922966E+10 | 0.00 | 16773671.94 | 0.142293E+11 | 0.00 | 0.979080E+10 | 0.00 | 1.39 |
July | 76543931.73 | 0.183887E+11 | 0.00 | 4230133.61 | 0.210288E+11 | 0.00 | 0.137585E+10 | 0.00 | 1.26 |
August | 44578837.34 | 0.261405E+11 | 0.00 | 2363765.35 | 0.201786E+11 | 0.00 | 0.627511E+09 | 0.00 | 1.25 |
September | 0.537372E+10 | 0.813811E+10 | 0.00 | 24959388.33 | 0.101961E+11 | 0.00 | 0.156980E+11 | 0.00 | 1.53 |
October | 0.347450E+11 | 0.171891E+10 | 0.00 | 21689180.54 | 0.288956E+10 | 0.00 | 0.328346E+11 | 0.00 | 1.63 |
November | 0.576031E+11 | 2383639.27 | 0.00 | 10515656.52 | 0.145186E+09 | 0.00 | 0.288361E+11 | 0.00 | 1.59 |
December | 0.938416E+11 | 0.00 | 0.00 | 2841696.31 | 354369.93 | 0.00 | 0.946079E+10 | 0.00 | 1.39 |
Annual Sum or Average | 0.466140E+12 | 0.645665E+11 | 0.00 | 0.147382E+09 | 0.746770E+11 | 0.00 | 0.188644E+12 | 0.00 | 1.49 |
Minimum of Months | 44578837.34 | 0.00 | 0.00 | 355229.80 | 0.00 | 0.00 | 0.627511E+09 | 0.00 | 1.25 |
Maximum of Months | 0.996574E+11 | 0.261405E+11 | 0.00 | 29875229.89 | 0.210288E+11 | 0.00 | 0.328346E+11 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 64805704.23 | 0.00 | 0.00 | 744609.16 | 0.00 | 0.113091E+10 | 0.125751E+09 | 0.00 | 0.34 |
February | 70753790.88 | 40950.25 | 710.63 | 2142116.15 | 0.00 | 0.763238E+09 | 0.320880E+09 | 1102.49 | 0.34 |
March | 62813852.60 | 9154822.24 | 0.00 | 5613938.47 | 231678.74 | 0.229430E+09 | 0.756331E+09 | 0.00 | 0.34 |
April | 22312330.03 | 39478199.22 | 42740.96 | 7844888.41 | 3252248.62 | 58897540.72 | 0.654414E+09 | 1661.53 | 0.34 |
May | 1688413.86 | 0.238052E+09 | 0.00 | 5347093.00 | 1075176.77 | 798361.44 | 0.264573E+09 | 0.00 | 0.34 |
June | 630378.54 | 0.725231E+09 | 62298.06 | 2488523.62 | 0.00 | 174211.78 | 0.116700E+09 | 1112.94 | 0.34 |
July | 0.00 | 0.103140E+10 | 49567.74 | 234842.01 | 2552376.09 | 83336.69 | 3735227.35 | 1608.83 | 0.34 |
August | 0.00 | 0.112623E+10 | 9706.30 | 82702.68 | 0.00 | 0.00 | 323136.28 | 443.04 | 0.34 |
September | 1384346.82 | 0.538085E+09 | 200949.60 | 2913520.90 | 4188431.17 | 1023028.34 | 0.154259E+09 | 2846.58 | 0.34 |
October | 31583628.68 | 0.140922E+09 | 35106.33 | 6028292.51 | 3684638.38 | 0.137151E+09 | 0.660145E+09 | 2249.17 | 0.34 |
November | 40959482.77 | 7389508.96 | 469.64 | 3655541.40 | 1615374.86 | 0.402995E+09 | 0.654101E+09 | 2201.75 | 0.34 |
December | 71668215.85 | 280523.83 | 0.00 | 1351038.25 | 348453.18 | 0.976859E+09 | 0.245660E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.368600E+09 | 0.385626E+10 | 401549.27 | 38447106.56 | 16948377.82 | 0.370156E+10 | 0.395687E+10 | 13226.33 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 82702.68 | 0.00 | 0.00 | 323136.28 | 0.00 | 0.34 |
Maximum of Months | 71668215.85 | 0.112623E+10 | 200949.60 | 7844888.41 | 4188431.17 | 0.113091E+10 | 0.756331E+09 | 2846.58 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 62759342.74 | 0.00 | 0.00 | 125079.64 | 0.00 | 0.122057E+10 | 38601093.66 | 0.00 | 0.34 |
February | 0.105012E+09 | 24552.88 | 16316.21 | 588678.76 | 0.00 | 0.852328E+09 | 0.198949E+09 | 1889.27 | 0.34 |
March | 0.200977E+09 | 7458795.76 | 5605.53 | 2139278.20 | 1915337.93 | 0.312662E+09 | 0.538288E+09 | 5661.99 | 0.34 |
April | 0.145907E+09 | 31034537.26 | 89994.16 | 5426901.49 | 11642954.28 | 63612524.23 | 0.528435E+09 | 2352.94 | 0.34 |
May | 89834383.77 | 0.202245E+09 | 190157.89 | 3071526.21 | 36653165.46 | 637720.69 | 0.178831E+09 | 11444.24 | 0.34 |
June | 24758162.56 | 0.617847E+09 | 139638.84 | 2099971.96 | 0.107220E+09 | 79690.33 | 93041029.62 | 2470.13 | 0.34 |
July | 3903114.60 | 0.886123E+09 | 89880.10 | 70189.81 | 0.147666E+09 | 3051.20 | 76575.53 | 3093.93 | 0.34 |
August | 405791.40 | 0.101578E+10 | 90053.75 | 0.00 | 0.110229E+09 | 0.00 | 0.00 | 2570.36 | 0.34 |
September | 57066592.00 | 0.432475E+09 | 209002.61 | 1793630.45 | 0.109718E+09 | 429313.97 | 0.100272E+09 | 10565.17 | 0.34 |
October | 0.146515E+09 | 0.108189E+09 | 194439.20 | 2237403.47 | 36235076.77 | 0.185851E+09 | 0.500206E+09 | 9122.26 | 0.34 |
November | 0.137504E+09 | 4869514.21 | 21840.52 | 849099.23 | 4113644.42 | 0.609067E+09 | 0.354162E+09 | 1500.70 | 0.34 |
December | 97082918.83 | 254345.30 | 0.00 | 332612.00 | 374558.02 | 0.111262E+10 | 85347440.85 | 0.00 | 0.34 |
Annual Sum or Average | 0.107172E+10 | 0.330630E+10 | 1046928.81 | 18734371.22 | 0.565769E+09 | 0.435786E+10 | 0.261621E+10 | 50670.99 | 0.34 |
Minimum of Months | 405791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.200977E+09 | 0.101578E+10 | 209002.61 | 5426901.49 | 0.147666E+09 | 0.122057E+10 | 0.538288E+09 | 11444.24 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.896957E+09 | 0.00 | 0.00 | 203903.36 | 0.00 | 0.00 | 0.117248E+09 | 0.00 | 0.02 |
February | 0.660104E+09 | 0.00 | 0.00 | 775242.26 | 0.00 | 0.00 | 0.240374E+09 | 0.00 | 0.02 |
March | 0.277664E+09 | 21194985.27 | 0.00 | 1724144.05 | 0.00 | 0.00 | 0.709976E+09 | 0.00 | 0.02 |
April | 0.120840E+09 | 75507343.60 | 0.00 | 1484663.40 | 20830372.72 | 0.00 | 0.304982E+09 | 0.00 | 0.02 |
May | 13348729.91 | 0.291574E+09 | 0.00 | 340899.04 | 4278899.64 | 0.00 | 97281093.83 | 0.00 | 0.02 |
June | 0.00 | 0.537785E+09 | 0.00 | 116027.17 | 0.00 | 0.00 | 41318862.65 | 0.00 | 0.02 |
July | 0.00 | 0.765011E+09 | 0.00 | 0.00 | 42552431.02 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.888427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 29533266.10 | 0.583650E+09 | 0.00 | 365138.69 | 21929579.30 | 0.00 | 24433889.62 | 0.00 | 0.02 |
October | 0.175769E+09 | 0.213199E+09 | 0.00 | 1863420.34 | 14164973.19 | 0.00 | 0.468422E+09 | 0.00 | 0.02 |
November | 0.294122E+09 | 39728041.76 | 0.00 | 1924328.90 | 4437126.50 | 0.00 | 0.659172E+09 | 0.00 | 0.02 |
December | 0.620959E+09 | 0.00 | 0.00 | 1190807.12 | 0.00 | 0.00 | 0.606315E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.308930E+10 | 0.341608E+10 | 0.00 | 9988574.34 | 0.108193E+09 | 0.00 | 0.326952E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.896957E+09 | 0.888427E+09 | 0.00 | 1924328.90 | 42552431.02 | 0.00 | 0.709976E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119632E+10 | 0.00 | 0.00 | 9446889.05 | 0.00 | 0.100729E+11 | 0.665422E+10 | 0.00 | 0.38 |
February | 0.158219E+10 | 579991.45 | 0.00 | 21499924.52 | 0.00 | 0.541362E+10 | 0.867504E+10 | 0.00 | 0.39 |
March | 0.272613E+10 | 97985927.41 | 262337.27 | 43787124.01 | 29039308.53 | 97676868.69 | 0.114302E+11 | 19764.04 | 0.39 |
April | 0.198880E+10 | 0.408122E+09 | 231640.63 | 72913134.38 | 0.171789E+09 | 31839513.35 | 0.798998E+10 | 5377.80 | 0.39 |
May | 0.122919E+10 | 0.257702E+10 | 1976782.25 | 39393349.77 | 0.664188E+09 | 2444550.24 | 0.242357E+10 | 57740.35 | 0.39 |
June | 0.349342E+09 | 0.819040E+10 | 1051613.64 | 21875911.19 | 0.164557E+10 | 568913.66 | 0.125565E+10 | 4779.20 | 0.39 |
July | 52943408.01 | 0.117821E+11 | 54071.53 | 1329836.32 | 0.224185E+10 | 45124.11 | 657210.99 | 3606.77 | 0.39 |
August | 5504316.95 | 0.132451E+11 | 0.00 | 0.00 | 0.202988E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.781123E+09 | 0.555280E+10 | 1336472.55 | 24382601.36 | 0.180335E+10 | 3981765.53 | 0.135487E+10 | 26334.58 | 0.39 |
October | 0.198738E+10 | 0.143032E+10 | 1771759.02 | 43759530.69 | 0.529637E+09 | 89664023.13 | 0.920288E+10 | 57080.48 | 0.39 |
November | 0.186516E+10 | 65979425.45 | 377935.89 | 34629691.98 | 55799118.80 | 0.932250E+09 | 0.121103E+11 | 11287.36 | 0.39 |
December | 0.131687E+10 | 3450041.48 | 0.00 | 18504917.31 | 5080654.82 | 0.436560E+10 | 0.118702E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.150810E+11 | 0.433538E+11 | 7062612.77 | 0.331523E+09 | 0.917618E+10 | 0.210106E+11 | 0.729675E+11 | 185970.57 | 0.39 |
Minimum of Months | 5504316.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.272613E+10 | 0.132451E+11 | 1976782.25 | 72913134.38 | 0.224185E+10 | 0.100729E+11 | 0.121103E+11 | 57740.35 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 66368606.60 | 0.00 | 0.00 | 481729.22 | 0.00 | 0.112073E+10 | 0.134631E+09 | 0.00 | 0.34 |
February | 65859363.66 | 38341.99 | 3302.00 | 2304026.73 | 0.00 | 0.763114E+09 | 0.325736E+09 | 1119.37 | 0.34 |
March | 51073136.31 | 9198226.11 | 3460.60 | 5389077.12 | 184267.77 | 0.242525E+09 | 0.755202E+09 | 546.50 | 0.34 |
April | 14695739.35 | 39942244.89 | 41999.40 | 8081766.81 | 2788794.50 | 59663504.83 | 0.661028E+09 | 1811.55 | 0.34 |
May | 47811.96 | 0.238117E+09 | 22080.03 | 5812885.82 | 987167.38 | 478884.06 | 0.266067E+09 | 1109.43 | 0.34 |
June | 0.00 | 0.725278E+09 | 15857.42 | 2731274.55 | 0.00 | 0.00 | 0.117262E+09 | 197.69 | 0.34 |
July | 0.00 | 0.103128E+10 | 171098.40 | 231818.47 | 2552376.09 | 83336.69 | 3738250.90 | 2956.06 | 0.34 |
August | 0.00 | 0.112619E+10 | 49527.08 | 100392.66 | 0.00 | 0.00 | 305446.29 | 342.43 | 0.34 |
September | 1384346.82 | 0.537522E+09 | 172583.41 | 3159302.26 | 4778859.89 | 548423.69 | 0.154488E+09 | 3669.00 | 0.34 |
October | 20337309.90 | 0.141008E+09 | 69715.76 | 5982041.00 | 3564281.12 | 0.137156E+09 | 0.671432E+09 | 2596.45 | 0.34 |
November | 39930771.76 | 7465630.88 | 6720.74 | 3678666.79 | 1532184.49 | 0.410994E+09 | 0.647107E+09 | 3019.11 | 0.34 |
December | 72128615.39 | 254375.11 | 0.00 | 1147470.80 | 374601.91 | 0.956478E+09 | 0.265785E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.331826E+09 | 0.385629E+10 | 556344.84 | 39100452.22 | 16762533.16 | 0.369177E+10 | 0.400278E+10 | 17367.59 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 100392.66 | 0.00 | 0.00 | 305446.29 | 0.00 | 0.34 |
Maximum of Months | 72128615.39 | 0.112619E+10 | 172583.41 | 8081766.81 | 4778859.89 | 0.112073E+10 | 0.755202E+09 | 3669.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69209943.48 | 0.00 | 0.00 | 132975.78 | 0.00 | 0.121356E+10 | 39154196.20 | 0.00 | 0.34 |
February | 0.109285E+09 | 24552.88 | 16368.16 | 938922.27 | 0.00 | 0.836333E+09 | 0.210320E+09 | 1837.32 | 0.34 |
March | 0.199783E+09 | 7459747.29 | 24100.35 | 2357778.27 | 1895071.60 | 0.312200E+09 | 0.539726E+09 | 6481.97 | 0.34 |
April | 0.144120E+09 | 32060852.18 | 41345.76 | 5763698.04 | 10666274.07 | 64118278.58 | 0.529380E+09 | 1366.62 | 0.34 |
May | 87946953.89 | 0.202899E+09 | 126342.61 | 3312518.36 | 36070768.97 | 512001.44 | 0.180603E+09 | 3433.97 | 0.34 |
June | 24142033.96 | 0.619040E+09 | 34353.11 | 2305463.36 | 0.106134E+09 | 43047.20 | 93488309.95 | 479.55 | 0.34 |
July | 3903114.60 | 0.888765E+09 | 92241.32 | 69808.79 | 0.145023E+09 | 3051.20 | 76956.54 | 1512.45 | 0.34 |
August | 405791.40 | 0.101678E+10 | 0.00 | 0.00 | 0.109327E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 56610984.64 | 0.432664E+09 | 189101.35 | 1896231.46 | 0.109555E+09 | 308665.99 | 0.100746E+09 | 4954.37 | 0.34 |
October | 0.145447E+09 | 0.111365E+09 | 221007.74 | 2528204.58 | 33034972.92 | 0.196040E+09 | 0.490794E+09 | 6625.73 | 0.34 |
November | 0.137923E+09 | 4869514.21 | 22115.10 | 1094284.66 | 4113644.42 | 0.594997E+09 | 0.367567E+09 | 1226.11 | 0.34 |
December | 97082918.83 | 254345.30 | 0.00 | 260212.22 | 374558.02 | 0.110653E+10 | 91514273.68 | 0.00 | 0.34 |
Annual Sum or Average | 0.107586E+10 | 0.331618E+10 | 766975.51 | 20660097.81 | 0.556195E+09 | 0.432464E+10 | 0.264337E+10 | 27918.10 | 0.34 |
Minimum of Months | 405791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.199783E+09 | 0.101678E+10 | 221007.74 | 5763698.04 | 0.145023E+09 | 0.121356E+10 | 0.539726E+09 | 6625.73 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206547E+10 | 0.00 | 0.00 | 0.36 |
February | 0.206109E+11 | 0.00 | 0.00 | 0.00 | 790696.74 | 0.771569E+09 | 0.00 | 0.00 | 0.40 |
March | 0.205752E+11 | 0.00 | 0.00 | 0.00 | 20932771.37 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.149833E+11 | 0.00 | 0.00 | 0.00 | 0.259890E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.849719E+10 | 0.00 | 0.00 | 0.00 | 0.146056E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.300140E+10 | 0.00 | 0.00 | 0.00 | 0.582908E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.364336E+09 | 3978308.38 | 0.00 | 0.00 | 0.974912E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.166772E+09 | 53703188.80 | 0.00 | 0.00 | 0.113066E+11 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.526459E+10 | 0.00 | 0.00 | 0.00 | 0.455853E+10 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.169302E+11 | 0.00 | 0.00 | 0.00 | 0.115158E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 0.216665E+11 | 0.00 | 0.00 | 0.00 | 36984783.46 | 0.00 | 0.00 | 0.00 | 0.43 |
December | 0.258909E+11 | 0.00 | 0.00 | 0.00 | 88814.11 | 0.00 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.161245E+12 | 57681497.18 | 0.00 | 0.00 | 0.343742E+11 | 0.283704E+10 | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.166772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.258909E+11 | 53703188.80 | 0.00 | 0.00 | 0.113066E+11 | 0.206547E+10 | 0.00 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15143305.39 | 0.00 | 0.00 | 132035.17 | 0.00 | 0.295145E+09 | 20132850.06 | 0.00 | 0.34 |
February | 16203075.70 | 10237.56 | 0.00 | 463484.26 | 0.00 | 0.216794E+09 | 55792667.26 | 453.28 | 0.34 |
March | 15614900.28 | 2300612.70 | 746.56 | 1223480.86 | 44778.45 | 0.105447E+09 | 0.141262E+09 | 487.54 | 0.34 |
April | 5121071.95 | 9952638.65 | 10282.92 | 1787582.98 | 729720.61 | 28319337.73 | 0.150639E+09 | 1070.41 | 0.34 |
May | 370544.15 | 59535086.27 | 0.00 | 1221913.40 | 246791.85 | 244584.83 | 66264600.12 | 0.00 | 0.34 |
June | 0.00 | 0.181307E+09 | 12694.06 | 583619.92 | 3264.54 | 52908.56 | 29361699.87 | 385.75 | 0.34 |
July | 0.00 | 0.257787E+09 | 26577.47 | 48981.30 | 685980.32 | 20834.17 | 943536.04 | 1205.44 | 0.34 |
August | 0.00 | 0.281529E+09 | 29915.25 | 19094.08 | 0.00 | 2893.55 | 79472.10 | 777.07 | 0.34 |
September | 346086.71 | 0.134411E+09 | 73028.64 | 611709.20 | 1134003.50 | 2081671.88 | 36855562.73 | 1337.12 | 0.34 |
October | 7974747.76 | 35209710.65 | 59396.28 | 1282630.86 | 891070.28 | 76081189.20 | 0.123388E+09 | 864.36 | 0.34 |
November | 10923615.86 | 1887603.01 | 122.69 | 739355.66 | 363617.95 | 0.158689E+09 | 0.105076E+09 | 545.16 | 0.34 |
December | 17338567.25 | 70130.96 | 0.00 | 264578.60 | 87113.30 | 0.271303E+09 | 34978117.79 | 0.00 | 0.34 |
Annual Sum or Average | 89035915.05 | 0.964000E+09 | 212763.87 | 8378466.27 | 4186340.79 | 0.115418E+10 | 0.764774E+09 | 7126.13 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 19094.08 | 0.00 | 2893.55 | 79472.10 | 0.00 | 0.34 |
Maximum of Months | 17338567.25 | 0.281529E+09 | 73028.64 | 1787582.98 | 1134003.50 | 0.295145E+09 | 0.150639E+09 | 1337.12 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11249603.13 | 0.00 | 0.00 | 27373.74 | 0.00 | 0.315453E+09 | 3784129.79 | 0.00 | 0.34 |
February | 23524406.08 | 6138.22 | 4063.46 | 101464.89 | 0.00 | 0.238565E+09 | 27028944.05 | 487.91 | 0.34 |
March | 50244237.19 | 1869079.21 | 1547.03 | 396301.00 | 473813.98 | 0.123878E+09 | 88998053.90 | 1910.08 | 0.34 |
April | 36427986.03 | 7942942.05 | 22329.11 | 1228707.79 | 2726441.97 | 28673241.53 | 0.119516E+09 | 746.53 | 0.34 |
May | 22112313.70 | 50749087.86 | 62132.53 | 721302.89 | 8959377.38 | 147919.33 | 45112127.46 | 4276.02 | 0.34 |
June | 6049530.72 | 0.154451E+09 | 45147.54 | 501008.08 | 26805099.79 | 24488.27 | 23419686.55 | 692.84 | 0.34 |
July | 975778.65 | 0.221531E+09 | 22744.53 | 14803.94 | 36916506.90 | 3656.18 | 18994.01 | 498.98 | 0.34 |
August | 101447.85 | 0.253938E+09 | 30912.53 | 0.00 | 27557337.39 | 0.00 | 0.00 | 487.37 | 0.34 |
September | 14214002.20 | 0.108145E+09 | 70037.53 | 370645.97 | 27384710.26 | 390888.65 | 24914819.40 | 4057.72 | 0.34 |
October | 36628646.15 | 27307013.78 | 89897.48 | 382409.97 | 8756681.73 | 87179056.74 | 84512226.73 | 3211.79 | 0.34 |
November | 33905915.47 | 1219145.46 | 3709.98 | 121140.26 | 1028411.11 | 0.195855E+09 | 45513000.57 | 358.42 | 0.34 |
December | 19497834.84 | 63586.33 | 0.00 | 44865.03 | 93639.50 | 0.295975E+09 | 8328691.13 | 0.00 | 0.34 |
Annual Sum or Average | 0.254932E+09 | 0.827221E+09 | 352521.72 | 3910023.55 | 0.140702E+09 | 0.128615E+10 | 0.471146E+09 | 16727.67 | 0.34 |
Minimum of Months | 101447.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 50244237.19 | 0.253938E+09 | 89897.48 | 1228707.79 | 36916506.90 | 0.315453E+09 | 0.119516E+09 | 4276.02 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70791387.65 | 0.00 | 0.00 | 3848789.60 | 0.00 | 0.134983E+10 | 0.699161E+09 | 0.00 | 0.38 |
February | 80744134.68 | 61581.92 | 6961.82 | 5763014.58 | 0.00 | 0.848353E+09 | 0.923445E+09 | 139.45 | 0.39 |
March | 45908671.79 | 14887265.55 | 0.00 | 9946226.63 | 188603.34 | 0.230709E+09 | 0.140659E+10 | 0.00 | 0.39 |
April | 27392254.09 | 63763273.62 | 52743.57 | 10861915.70 | 4883918.04 | 0.110540E+09 | 0.104531E+10 | 1707.30 | 0.39 |
May | 1701650.56 | 0.382407E+09 | 73961.63 | 6875670.28 | 1585511.58 | 1441320.38 | 0.427500E+09 | 1892.01 | 0.39 |
June | 138030.60 | 0.116467E+10 | 240549.41 | 2918388.50 | 0.00 | 364844.02 | 0.189302E+09 | 4918.34 | 0.39 |
July | 0.00 | 0.165557E+10 | 752539.84 | 307708.79 | 4407073.25 | 133848.91 | 6068708.29 | 6166.05 | 0.39 |
August | 0.00 | 0.180795E+10 | 915106.92 | 126282.19 | 0.00 | 0.00 | 525544.82 | 12002.87 | 0.39 |
September | 2223430.35 | 0.862004E+09 | 295302.10 | 4285484.87 | 8981021.83 | 3523976.19 | 0.246272E+09 | 4217.40 | 0.39 |
October | 16936198.65 | 0.226475E+09 | 113075.92 | 11355150.11 | 5724671.52 | 0.157260E+09 | 0.115541E+10 | 3066.34 | 0.39 |
November | 28913488.05 | 12953257.54 | 4241.09 | 10207258.12 | 1509093.49 | 0.313013E+09 | 0.141735E+10 | 643.50 | 0.39 |
December | 53194835.03 | 1010214.03 | 0.00 | 5831595.05 | 0.00 | 0.102267E+10 | 0.999094E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.327944E+09 | 0.619175E+10 | 2454482.30 | 72327484.40 | 27279893.04 | 0.403784E+10 | 0.851603E+10 | 34753.27 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 126282.19 | 0.00 | 0.00 | 525544.82 | 0.00 | 0.38 |
Maximum of Months | 80744134.68 | 0.180795E+10 | 915106.92 | 11355150.11 | 8981021.83 | 0.134983E+10 | 0.141735E+10 | 12002.87 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308328E+11 | 0.00 | 0.00 | 12677057.91 | 0.00 | 0.00 | 0.326243E+11 | 0.00 | 4.19 |
February | 0.215310E+11 | 0.00 | 0.00 | 15697951.72 | 1978999.90 | 0.00 | 0.319707E+11 | 0.00 | 4.74 |
March | 0.145407E+11 | 24128887.50 | 0.00 | 26022676.35 | 28262820.30 | 0.00 | 0.369388E+11 | 0.00 | 5.31 |
April | 0.667606E+10 | 0.345982E+09 | 0.00 | 30218825.96 | 0.304486E+09 | 0.00 | 0.308519E+11 | 0.00 | 5.54 |
May | 0.187119E+10 | 0.277752E+10 | 0.00 | 32715556.78 | 0.886086E+09 | 0.00 | 0.194532E+11 | 0.00 | 5.34 |
June | 0.420591E+09 | 0.124882E+11 | 0.00 | 13790051.82 | 0.219204E+10 | 0.00 | 0.712349E+10 | 0.00 | 4.47 |
July | 5884400.45 | 0.214425E+11 | 0.00 | 3101294.52 | 0.312286E+10 | 0.00 | 0.905970E+09 | 0.00 | 4.00 |
August | 9517939.68 | 0.251690E+11 | 0.00 | 1485289.54 | 0.348410E+10 | 0.00 | 0.408224E+09 | 0.00 | 3.94 |
September | 0.139885E+10 | 0.934714E+10 | 0.00 | 17832800.61 | 0.209872E+10 | 0.00 | 0.117933E+11 | 0.00 | 4.88 |
October | 0.104722E+11 | 0.189394E+10 | 0.00 | 23984920.48 | 0.998836E+09 | 0.00 | 0.318905E+11 | 0.00 | 5.24 |
November | 0.169669E+11 | 33903991.22 | 0.00 | 20550872.23 | 58663587.84 | 0.00 | 0.372407E+11 | 0.00 | 5.11 |
December | 0.262333E+11 | 0.00 | 0.00 | 15717794.07 | 222288.91 | 0.00 | 0.385522E+11 | 0.00 | 4.47 |
Annual Sum or Average | 0.130959E+12 | 0.735223E+11 | 0.00 | 0.213795E+09 | 0.131763E+11 | 0.00 | 0.279753E+12 | 0.00 | 4.77 |
Minimum of Months | 5884400.45 | 0.00 | 0.00 | 1485289.54 | 0.00 | 0.00 | 0.408224E+09 | 0.00 | 3.94 |
Maximum of Months | 0.308328E+11 | 0.251690E+11 | 0.00 | 32715556.78 | 0.348410E+10 | 0.00 | 0.385522E+11 | 0.00 | 5.54 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.244119E+11 | 0.00 | 0.00 | 19082835.13 | 0.00 | 0.00 | 0.390103E+11 | 0.00 | 4.20 |
February | 0.168616E+11 | 1430161.85 | 0.00 | 22409637.36 | 547877.73 | 0.00 | 0.366386E+11 | 0.00 | 4.75 |
March | 0.107550E+11 | 35432936.34 | 0.00 | 34296924.50 | 16933348.08 | 0.00 | 0.407825E+11 | 0.00 | 5.33 |
April | 0.422505E+10 | 0.505403E+09 | 0.00 | 38088284.69 | 0.144772E+09 | 0.00 | 0.334377E+11 | 0.00 | 5.56 |
May | 0.921983E+09 | 0.308505E+10 | 0.00 | 39194738.40 | 0.585144E+09 | 0.00 | 0.205263E+11 | 0.00 | 5.37 |
June | 0.292317E+09 | 0.131496E+11 | 0.00 | 16525520.26 | 0.160755E+10 | 0.00 | 0.729027E+10 | 0.00 | 4.51 |
July | 2585812.43 | 0.225397E+11 | 0.00 | 3513227.44 | 0.216742E+10 | 0.00 | 0.914580E+09 | 0.00 | 4.03 |
August | 2955091.55 | 0.264248E+11 | 0.00 | 1741413.62 | 0.241754E+10 | 0.00 | 0.415651E+09 | 0.00 | 3.98 |
September | 0.708822E+09 | 0.101498E+11 | 0.00 | 21319309.91 | 0.133106E+10 | 0.00 | 0.125642E+11 | 0.00 | 4.91 |
October | 0.769279E+10 | 0.244932E+10 | 0.00 | 30917575.44 | 0.455137E+09 | 0.00 | 0.347275E+11 | 0.00 | 5.26 |
November | 0.133942E+11 | 55290493.28 | 0.00 | 28179256.26 | 37232166.82 | 0.00 | 0.408087E+11 | 0.00 | 5.12 |
December | 0.204682E+11 | 0.00 | 0.00 | 23223644.70 | 222181.05 | 0.00 | 0.442897E+11 | 0.00 | 4.47 |
Annual Sum or Average | 0.997374E+11 | 0.783958E+11 | 0.00 | 0.278492E+09 | 0.876356E+10 | 0.00 | 0.311406E+12 | 0.00 | 4.79 |
Minimum of Months | 2585812.43 | 0.00 | 0.00 | 1741413.62 | 0.00 | 0.00 | 0.415651E+09 | 0.00 | 3.98 |
Maximum of Months | 0.244119E+11 | 0.264248E+11 | 0.00 | 39194738.40 | 0.241754E+10 | 0.00 | 0.442897E+11 | 0.00 | 5.56 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.102157E+09 | 0.00 | 0.00 | 0.603311E+11 | 0.00 | 13.17 |
February | 0.00 | 2421120.30 | 0.00 | 94930061.22 | 0.00 | 0.00 | 0.507146E+11 | 0.00 | 15.47 |
March | 0.00 | 65490699.53 | 0.00 | 0.107883E+09 | 0.00 | 0.00 | 0.496191E+11 | 0.00 | 17.99 |
April | 0.00 | 0.807922E+09 | 0.00 | 97656689.22 | 0.00 | 0.00 | 0.345487E+11 | 0.00 | 18.69 |
May | 0.00 | 0.449911E+10 | 0.00 | 70324280.54 | 0.00 | 0.00 | 0.183942E+11 | 0.00 | 17.79 |
June | 0.00 | 0.169453E+11 | 0.00 | 28453987.75 | 0.00 | 0.00 | 0.644959E+10 | 0.00 | 15.18 |
July | 0.00 | 0.277991E+11 | 0.00 | 3917399.06 | 0.00 | 0.00 | 0.689636E+09 | 0.00 | 13.68 |
August | 0.00 | 0.317777E+11 | 0.00 | 2356605.74 | 0.00 | 0.00 | 0.349032E+09 | 0.00 | 13.57 |
September | 0.00 | 0.130777E+11 | 0.00 | 44940467.25 | 0.00 | 0.00 | 0.119044E+11 | 0.00 | 16.45 |
October | 0.00 | 0.327939E+10 | 0.00 | 93413871.41 | 0.00 | 0.00 | 0.403790E+11 | 0.00 | 17.68 |
November | 0.00 | 0.114051E+09 | 0.00 | 99937568.85 | 0.00 | 0.00 | 0.516386E+11 | 0.00 | 17.09 |
December | 0.00 | 278266.73 | 0.00 | 0.101777E+09 | 0.00 | 0.00 | 0.616200E+11 | 0.00 | 14.46 |
Annual Sum or Average | 0.00 | 0.983685E+11 | 0.00 | 0.847748E+09 | 0.00 | 0.00 | 0.386638E+12 | 0.00 | 15.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2356605.74 | 0.00 | 0.00 | 0.349032E+09 | 0.00 | 13.17 |
Maximum of Months | 0.00 | 0.317777E+11 | 0.00 | 0.107883E+09 | 0.00 | 0.00 | 0.616200E+11 | 0.00 | 18.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180411E+10 | 0.00 | 0.00 | 0.36 |
February | 0.482661E+10 | 0.00 | 0.00 | 0.00 | 209013.02 | 0.825648E+09 | 0.00 | 0.00 | 0.40 |
March | 0.524891E+10 | 3490039.35 | 0.00 | 283280.89 | 2624178.73 | 0.00 | 0.195336E+09 | 0.00 | 0.45 |
April | 0.302996E+10 | 42500039.89 | 0.00 | 2799322.89 | 35150362.27 | 0.00 | 0.101651E+10 | 0.00 | 0.51 |
May | 0.800648E+09 | 0.575896E+09 | 0.00 | 4890791.40 | 6409517.31 | 0.00 | 0.160166E+10 | 0.00 | 0.55 |
June | 0.176188E+09 | 0.266927E+10 | 0.00 | 2833567.01 | 80500.09 | 0.00 | 0.732589E+09 | 0.00 | 0.58 |
July | 4150588.16 | 0.456835E+10 | 0.00 | 454292.83 | 5120385.78 | 0.00 | 0.107323E+09 | 0.00 | 0.57 |
August | 0.00 | 0.538425E+10 | 0.00 | 306156.73 | 0.00 | 0.00 | 56053051.05 | 0.00 | 0.58 |
September | 0.629741E+09 | 0.174372E+10 | 0.00 | 2983884.27 | 5683730.71 | 0.00 | 0.847852E+09 | 0.00 | 0.53 |
October | 0.394971E+10 | 0.280301E+09 | 0.00 | 1203827.37 | 69223515.95 | 0.00 | 0.548754E+09 | 0.00 | 0.46 |
November | 0.568470E+10 | 0.00 | 0.00 | 0.00 | 9776568.97 | 42630745.39 | 0.00 | 0.00 | 0.43 |
December | 0.654397E+10 | 0.00 | 0.00 | 0.00 | 23477.15 | 0.300039E+09 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.357939E+11 | 0.152678E+11 | 0.00 | 15755123.38 | 0.134301E+09 | 0.297242E+10 | 0.510607E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.654397E+10 | 0.538425E+10 | 0.00 | 4890791.40 | 69223515.95 | 0.180411E+10 | 0.160166E+10 | 0.00 | 0.58 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:54:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.168680E+12 | 0.172179E+11 | 0.222096E+12 | 0.607486E+12 | 0.512043E+11 |
February | 0.178417E+12 | 0.126282E+11 | 0.159575E+12 | 0.475054E+12 | 0.900818E+11 |
March | 0.270710E+12 | 0.925313E+10 | 0.113494E+12 | 0.386349E+12 | 0.215202E+12 |
April | 0.308744E+12 | 0.570832E+10 | 0.673205E+11 | 0.273058E+12 | 0.386539E+12 |
May | 0.341624E+12 | 0.133321E+10 | 0.113821E+11 | 0.101531E+12 | 0.677374E+12 |
June | 0.349660E+12 | -0.477950E+10 | -0.717404E+11 | -0.147814E+12 | 0.994267E+12 |
July | 0.325547E+12 | -0.917157E+10 | -0.130389E+12 | -0.324479E+12 | 0.123294E+13 |
August | 0.300443E+12 | -0.110034E+11 | -0.151576E+12 | -0.397305E+12 | 0.130212E+13 |
September | 0.223977E+12 | -0.257108E+10 | -0.392547E+11 | -0.507592E+11 | 0.862283E+12 |
October | 0.210725E+12 | 0.595163E+10 | 0.714004E+11 | 0.285091E+12 | 0.388649E+12 |
November | 0.142925E+12 | 0.997055E+10 | 0.123351E+12 | 0.419216E+12 | 0.171811E+12 |
December | 0.133463E+12 | 0.138245E+11 | 0.177344E+12 | 0.521442E+12 | 0.697004E+11 |
Annual Sum or Average | 0.295492E+13 | 0.483620E+11 | 0.553003E+12 | 0.214887E+13 | 0.644217E+13 |
Minimum of Months | 0.133463E+12 | -0.110034E+11 | -0.151576E+12 | -0.397305E+12 | 0.512043E+11 |