Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:55:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10110.46 | 891.16 | 891.16 |
Net Site Energy | 9940.28 | 876.16 | 876.16 |
Total Source Energy | 19711.99 | 1737.46 | 1737.46 |
Net Source Energy | 19173.05 | 1689.96 | 1689.96 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1273.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 661.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 454.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 390.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 571.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 70.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 120.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2846.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4201.75 | 5908.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1273.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 661.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 454.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 150.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 366.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 571.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 70.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 120.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2846.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1273.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 661.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 454.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 150.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 390.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 571.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 70.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 120.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2846.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 53.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 122.81 | 363.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 194.24 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 370.35 | 520.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 53.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 122.81 | 363.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 194.24 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 370.35 | 520.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 178.152 | 4.24 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.98 | -0.2 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 170.174 | 4.05 |
Electricity Coming From Utility | 4031.580 | 95.95 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4031.580 | 95.95 |
Total On-Site and Utility Electric Sources | 4201.754 | 100.00 |
Total Electricity End Uses | 4201.754 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 139.51 | 6.11 |
Air to Air Heat Recovery for Heating | 2145.36 | 93.89 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2284.87 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.67 |
Time Setpoint Not Met During Occupied Cooling | 44.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8056.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.2037 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 7.5557 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 7.5557 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 7.2603 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.7794 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.2151 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 7.7715 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.1806 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4993 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.7715 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.7715 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 12.1686 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4993 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.5793 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.5793 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.2037 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 7.5557 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 7.5557 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 7.2603 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.7794 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.2151 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 7.7715 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.1806 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4993 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 7.7715 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 7.7715 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 12.1686 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4993 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.5793 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.5793 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.4264 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-19:40 | 02-FEB-19:19 | - | - | - | - | - | - | - | - | - | - | 17-APR-20:30 |
Heating | 0.00 | 654480.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 138660.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 37630.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 19290.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27767.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3812.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4060.51 | 228490.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1683.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 336874.67 | 970590.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 654480.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 138660.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 37630.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1220.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 17944.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27767.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3812.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4060.51 | 228490.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 771.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 671.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1380.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2093.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1439.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 475.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1236.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1809.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 221.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 382.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 3085.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 13306.96 | 6405.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 121.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 126.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 33.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 271.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1172.91 | 564.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 121.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 126.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 33.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 271.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1172.91 | 564.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.18 | 0.690264 | 0.587000 | 1.28 | 1.00 | 0.500000 | 0.000552 | 0.000175 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.327988 | 0.155824 | 0.362000 | 0.118732 | 0.431651 | 0.500000 | 0.002445 | 0.000091 | 0.152321 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.208620 | 0.283692 | 0.660000 | 0.137689 | 0.756512 | 0.500000 | 0.001343 | 0.000041 | 0.137689 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.206716 | 0.605435 | 0.010000 | 0.002067 | 1.00 | 0.500000 | 0.000629 | 0.000059 | 0.098374 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.096373 | 0.749241 | 0.899000 | 0.086639 | 1.00 | 0.500000 | 0.000509 | 0.000042 | 0.086639 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.41 | 0.017456 | 0.010000 | 0.034067 | 0.300000 | 0.500000 | 0.021827 | 0.000078 | 0.130168 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.47 | 0.097886 | 0.690000 | 1.01 | 0.690000 | 0.500000 | 0.003892 | 0.000297 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.68 | 0.213194 | 0.608000 | 2.84 | 0.608000 | 0.500000 | 0.001787 | 0.000756 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.18 | 1.00 | 0.601000 | 0.711960 | 1.00 | 0.500000 | 0.000380 | 0.000319 | 0.711960 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.15 | 0.117645 | 0.829000 | 1.78 | 0.829000 | 0.500000 | 0.003239 | 0.000362 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.26 | 0.111919 | 0.789000 | 1.78 | 0.789000 | 0.500000 | 0.003404 | 0.000365 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.26 | 0.062530 | 0.243000 | 0.550215 | 0.300000 | 0.500000 | 0.010959 | 0.000138 | 0.550215 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.667229 | 0.470662 | 0.282000 | 0.188159 | 1.00 | 0.500000 | 0.000809 | 0.000215 | 0.359516 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7985.21 | 0.000175 | 235.17 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4155.90 | 0.000091 | 172.20 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1858.53 | 0.000041 | 62.23 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2683.83 | 0.000059 | 111.20 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1932.20 | 0.000042 | 73.07 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 3551.21 | 0.000078 | 147.14 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 13560.20 | 0.000297 | 453.36 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 34542.36 | 0.000756 | 1131.31 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 7128.22 | 0.000156 | 321.92 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 7137.30 | 0.000156 | 322.33 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 40202.79 | 0.000879 | 1815.59 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 40385.43 | 0.000883 | 1823.83 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 7109.27 | 0.000156 | 321.06 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 7118.36 | 0.000156 | 321.47 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14563.91 | 0.000319 | 534.80 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2201.10 | 0.000048 | 99.39 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2204.38 | 0.000048 | 99.54 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10541.83 | 0.000231 | 476.03 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 16528.33 | 0.000362 | 513.27 |
DINING_FLR_6 VAV BOX REHEAT COIL | 16675.51 | 0.000365 | 518.57 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6286.36 | 0.000138 | 203.06 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9809.82 | 0.000215 | 406.50 |
VAV WITH REHEAT HEATING COIL | 311825.83 | 0.006821 | 5547.05 |
FLR_3_DOAS HEATING COIL | 30469.72 | 0.000667 | 542.02 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.958806 | 0.000156 | 0.000305 |
ROOM_2_FLR_3 FAN COIL | 0.932465 | 0.000156 | 0.000297 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.73 | 0.000879 | 0.001776 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.18 | 0.000883 | 0.001732 |
ROOM_5_FLR_3 FAN COIL | 0.871540 | 0.000156 | 0.000279 |
ROOM_6_FLR_3 FAN COIL | 0.848710 | 0.000156 | 0.000272 |
ROOM_1_FLR_6 FAN COIL | 0.249212 | 0.000048 | 0.000079 |
ROOM_2_FLR_6 FAN COIL | 0.241817 | 0.000048 | 0.000077 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.18 | 0.000231 | 0.000382 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.958806 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.932465 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.73 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.18 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.871540 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.848710 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.249212 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.241817 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.18 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008729 | 12.80 | 0.008500 | 0.000305 | 0.958806 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008735 | 12.80 | 0.008500 | 0.000297 | 0.932465 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008633 | 12.80 | 0.008500 | 0.001776 | 5.73 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008927 | 12.80 | 0.008500 | 0.001732 | 5.18 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008754 | 12.80 | 0.008500 | 0.000279 | 0.871540 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008761 | 12.80 | 0.008500 | 0.000272 | 0.848710 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008721 | 12.80 | 0.008500 | 0.000079 | 0.249212 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008727 | 12.80 | 0.008500 | 0.000077 | 0.241817 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008784 | 12.80 | 0.008500 | 0.000382 | 1.18 | |
VAV WITH REHEAT COOLING COIL | 27.19 | 6.70 | 0.012273 | 10.90 | 0.008500 | 0.018104 | 20.99 | 633025.69 |
FLR_3_DOAS COOLING COIL | 31.20 | 6.70 | 0.015365 | 11.90 | 0.008500 | 0.002511 | 2.05 | 87803.64 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.07 | 10.53 | 21.10 | 10.53 | 20.99 | 20.99 | 0.300000 | 0.501669 | 20.99 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.99 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 20.99 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.018104 | 0.000026 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.006821 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002511 | 0.000190 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000667 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.025813 | 4172.80 | |
HEATSYS1 PUMP | 0.013135 | 3916.53 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.013135 | 1.58 |
COOLSYS1 | 0.025813 | 3.10 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 600457.60 | 600457.60 | 0.013135 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.025813 | 2888.97 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.025813 | 902567.75 | 903156.85 | 102.96 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.204 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.584 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 7.556 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 18.316 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 7.556 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 18.316 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 7.260 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.640 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.779 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.469 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.215 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.745 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 7.772 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.152 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.181 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.251 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.499 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.499 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.772 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.592 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.772 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.592 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.169 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.672 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.499 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.499 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 12276.143 | 6.204 | 115.270 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 12276.143 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 506.769 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 506.769 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 586.840 | 7.556 | 46.797 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 586.840 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1192.447 | 7.260 | 449.641 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1192.447 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 358.135 | 3.779 | 175.557 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 358.135 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 406.984 | 5.215 | 48.451 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 406.984 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1467.746 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1467.746 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10701.700 | 8.181 | 25.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10701.700 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1752.054 | 4.499 | 83.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1752.054 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2577.487 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2577.487 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2577.487 | 7.772 | 10.314 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2577.487 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1257.069 | 12.169 | 56.528 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1257.069 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1854.278 | 4.499 | 83.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1854.278 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.5896 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.7104 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.6552 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.6484 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.529 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.227 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.240 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.359 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.375 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | 0.30567884E-15 | -0.30896332E-15 | -0.16551672E-09 | -0.91785058E-17 |
29 | 8 | 0.24090447E-07 | 0.80347003E-13 | 0.40068996E-03 | -0.27391669E-09 |
30 | 7 | -0.12923526E-01 | 0.40885911E-08 | -0.24067338E-01 | 0.14694521E-03 |
31 | 6 | 0.42387903 | 0.14117012E-05 | 0.48784025 | -0.49661715E-02 |
32 | 5 | -5.3713598 | 0.52370355E-04 | -4.5620847 | 0.65425660E-01 |
33 | 4 | 33.802432 | 0.42589821E-03 | 21.912301 | -0.43273925 |
34 | 3 | -112.92705 | 0.92336011E-03 | -56.556947 | 1.5397679 |
35 | 2 | 198.81648 | 0.51696486E-03 | 78.731005 | -2.9274807 |
36 | 1 | -171.78690 | 0.54949437E-04 | -55.504664 | 2.7564953 |
37 | 0 | 57.057407 | 0.31123336E-06 | 15.518192 | |
38 | 9 | -0.29803454E-14 | 0.26315664E-16 | -0.15962191E-09 | 0.69155213E-16 |
39 | 8 | 0.23264542E-07 | 0.97548145E-13 | 0.39224253E-03 | -0.26452581E-09 |
40 | 7 | -0.12672225E-01 | 0.49915742E-08 | -0.23705744E-01 | 0.14408782E-03 |
41 | 6 | 0.41705177 | 0.17291566E-05 | 0.48204435 | -0.48856940E-02 |
42 | 5 | -5.3047469 | 0.64329124E-04 | -4.5176529 | 0.64599678E-01 |
43 | 4 | 33.507866 | 0.52449971E-03 | 21.738817 | -0.42882811 |
44 | 3 | -112.30056 | 0.11397552E-02 | -56.214058 | 1.5307162 |
45 | 2 | 198.19584 | 0.63943657E-03 | 78.416197 | -2.9176244 |
46 | 1 | -171.55775 | 0.68097144E-04 | -55.412505 | 2.7524792 |
47 | 0 | 57.057407 | 0.38656276E-06 | 15.532909 | |
48 | 9 | -0.33614258E-14 | 0.27986632E-16 | -0.15994383E-09 | 0.68043394E-16 |
49 | 8 | 0.23309699E-07 | 0.96633735E-13 | 0.39270698E-03 | -0.26503927E-09 |
50 | 7 | -0.12686050E-01 | 0.49423205E-08 | -0.23725640E-01 | 0.14424502E-03 |
51 | 6 | 0.41742739 | 0.17117811E-05 | 0.48236343 | -0.48901217E-02 |
52 | 5 | -5.3084120 | 0.63672673E-04 | -4.5201000 | 0.64645123E-01 |
53 | 4 | 33.524074 | 0.51907321E-03 | 21.748373 | -0.42904331 |
54 | 3 | -112.33503 | 0.11278190E-02 | -56.232948 | 1.5312143 |
55 | 2 | 198.22999 | 0.63266761E-03 | 78.433537 | -2.9181668 |
56 | 1 | -171.57036 | 0.67369156E-04 | -55.417574 | 2.7527002 |
57 | 0 | 57.057407 | 0.38238191E-06 | 15.532094 | |
58 | 9 | -0.22411641E-14 | 0.24573241E-16 | -0.16250403E-09 | 0.37356930E-16 |
59 | 8 | 0.23667237E-07 | 0.89315092E-13 | 0.39637369E-03 | -0.26910463E-09 |
60 | 7 | -0.12795163E-01 | 0.45518602E-08 | -0.23882652E-01 | 0.14548568E-03 |
61 | 6 | 0.42039178 | 0.15742828E-05 | 0.48488081 | -0.49250650E-02 |
62 | 5 | -5.3373358 | 0.58485808E-04 | -4.5394020 | 0.65003771E-01 |
63 | 4 | 33.651980 | 0.47625396E-03 | 21.823746 | -0.43074160 |
64 | 3 | -112.60707 | 0.10337438E-02 | -56.381925 | 1.5351448 |
65 | 2 | 198.49951 | 0.57937351E-03 | 78.570299 | -2.9224469 |
66 | 1 | -171.66987 | 0.61642904E-04 | -55.457584 | 2.7544443 |
67 | 0 | 57.057407 | 0.34952873E-06 | 15.525683 | |
68 | 9 | 0.10166766E-14 | -0.33686902E-15 | -0.16281809E-09 | -0.12528342E-16 |
69 | 8 | 0.23711425E-07 | 0.88181450E-13 | 0.39682556E-03 | -0.26960706E-09 |
70 | 7 | -0.12808606E-01 | 0.45035469E-08 | -0.23901994E-01 | 0.14563852E-03 |
71 | 6 | 0.42075698 | 0.15572985E-05 | 0.48519083 | -0.49293698E-02 |
72 | 5 | -5.3408990 | 0.57846068E-04 | -4.5417786 | 0.65047954E-01 |
73 | 4 | 33.667737 | 0.47097969E-03 | 21.833026 | -0.43095081 |
74 | 3 | -112.64059 | 0.10221697E-02 | -56.400266 | 1.5356290 |
75 | 2 | 198.53271 | 0.57282338E-03 | 78.587138 | -2.9229742 |
76 | 1 | -171.68213 | 0.60939838E-04 | -55.462514 | 2.7546591 |
77 | 0 | 57.057407 | 0.34548081E-06 | 15.524896 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
103 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
104 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
105 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
106 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
107 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
108 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
109 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
110 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
111 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
112 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
113 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
114 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
115 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
116 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
117 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
118 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
119 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
120 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
121 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
122 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
123 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
124 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
125 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
126 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
127 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
128 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
129 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
130 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
131 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
132 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
133 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.24_SHGC_0.29 | 37 | 1 | VerySmooth | 1.362 | 1.362 | 1.000 | 0.291 | ||
2 | RESWINDOW_U_0.24_SHGC_0.29 | 38 | 1 | VerySmooth | 1.362 | 1.362 | 1.000 | 0.291 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.63425E-002 | 0.20180 | 0.60061 | 0.60061 | 0.50000 | 0.13060 | 0.16021 | 0.00000 | 0.84000 | 0.84000 | 8.30626E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.63425E-002 | 0.20180 | 0.60061 | 0.60061 | 0.50000 | 0.13060 | 0.16021 | 0.00000 | 0.84000 | 0.84000 | 8.30626E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.680 | 0.5995 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.312 | 3.5001E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1809 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.5915E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.2051 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1094 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1252 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 5.0060E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.0207E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.6868E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2056 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1149 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2339 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1307 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1383 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 6.2219E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.6231E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.2845E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.3336E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.5380E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.3281E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.9139E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.1843E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2895E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.9325E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7679E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.3336E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.5380E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.3281E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.9139E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.1843E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2895E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.9325E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7679E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 28676.82356 | 28676.82356 | 2.18448 | 2.18448 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 26.09433 | 1.53557E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1527.82479 | 1527.82479 | 6.86579E-002 | 0.85446 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4304.95805 | 4304.95805 | 0.32799 | 0.32799 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3389.90185 | 3389.90185 | 0.15232 | 0.15232 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2738.27569 | 2738.27569 | 0.20862 | 0.20862 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 30.67000 | 1.53641E-002 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1165.98849 | 1165.98849 | 5.23955E-002 | 9.17335E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2713.88774 | 2713.88774 | 0.20672 | 0.20672 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 30.67000 | 1.53641E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2189.18113 | 2189.18113 | 9.83737E-002 | 9.83737E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1265.22741 | 1265.22741 | 9.63730E-002 | 9.63730E-002 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1496.46253 | 1496.46253 | 6.72455E-002 | 6.72455E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44719.23017 | 44719.23017 | 3.40668 | 3.40668 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2896.90469 | 2896.90469 | 0.13017 | 0.13017 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19281.19413 | 19281.19413 | 1.47021 | 1.47021 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8457.73133 | 8457.73133 | 0.38004 | 0.67638 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61355.02990 | 61355.02990 | 4.67573 | 4.67573 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 20242.86690 | 20242.86690 | 0.90964 | 1.89399 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9340.10459 | 9340.10459 | 0.95881 | 0.95881 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7128.22308 | 7128.22308 | 0.32217 | 0.32217 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9083.49260 | 9083.49260 | 0.93246 | 0.93246 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7137.30447 | 7137.30447 | 0.32258 | 0.32258 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 55838.28693 | 55838.28693 | 5.73154 | 5.73154 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 40202.78882 | 40202.78882 | 1.81716 | 1.81716 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 50444.89251 | 50444.89251 | 5.17836 | 5.17836 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.06600 | 1.53574E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 40385.42905 | 40385.42905 | 1.82541 | 1.82541 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8489.99029 | 8489.99029 | 0.87154 | 0.87154 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.57133 | 1.53565E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7109.27490 | 7109.27490 | 0.32132 | 0.32132 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8267.58319 | 8267.58319 | 0.84871 | 0.84871 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7118.35892 | 7118.35892 | 0.32173 | 0.32173 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15551.39011 | 15551.39011 | 1.18463 | 1.18463 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53651E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10981.77581 | 10981.77581 | 0.49349 | 0.49349 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2427.67150 | 2427.67150 | 0.24921 | 0.24921 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2201.10062 | 2201.10062 | 9.94833E-002 | 9.94833E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2355.63361 | 2355.63361 | 0.24182 | 0.24182 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2204.38030 | 2204.38030 | 9.96316E-002 | 9.96316E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11536.86323 | 11536.86323 | 1.18433 | 1.18433 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 10541.83020 | 10541.83020 | 0.47647 | 0.47647 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28164.64089 | 28164.64089 | 2.14819 | 2.14819 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7567.16069 | 7567.16069 | 0.34004 | 1.18780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29605.99210 | 29605.99210 | 2.25808 | 2.25808 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7710.30811 | 7710.30811 | 0.34647 | 1.18780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29644.92789 | 29644.92789 | 2.26426 | 2.26426 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30.24600 | 1.53633E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3522.25529 | 3522.25529 | 0.15826 | 0.36735 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8759.19617 | 8759.19617 | 0.66723 | 0.66723 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53651E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8000.44497 | 8000.44497 | 0.35952 | 0.35952 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -26.20000 | 3.61342E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 348684.96 | 20.99310 | 20.99310 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 374345.00 | 7.56062 | 7.56062 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 43560.46 | 15.14542 | 2.05125 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 101562.16 | 5.60596 | 2.05125 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18448 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69026 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28229 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.51963E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74677E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28229 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7985.20715 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74677E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 235.17219 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.32799 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15582 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36200 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11873 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43165 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44506E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.09104E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15232 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4155.89969 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.09104E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 172.20294 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20862 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28369 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.66000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13769 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75651 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34301E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.06553E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13769 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1858.52660 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.06553E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 62.22732 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20672 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60543 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.06716E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.29300E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.87089E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.83737E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2683.83413 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.87089E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 111.20256 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.63730E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.74924 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.89900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66393E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.08515E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.22669E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66393E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1932.19777 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.22669E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 73.06998 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.40668 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.74557E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.40668E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18267E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.76828E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13017 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3551.21003 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.76828E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 147.14102 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47021 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.78855E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.69000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01445 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.89230E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.96630E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01445 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13560.19730 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.96630E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 453.36318 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.67573 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21319 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60800 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84285 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60800 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78711E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.55615E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84285 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34542.36118 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.55615E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1131.31351 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.95881 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.95881 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.55930E-004 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.04742E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70989 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72908E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.04742E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.95881 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7128.22308 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55930E-004 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 321.91624 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.93246 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.93246 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.56129E-004 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.96862E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70989 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73540E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.96862E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.93246 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7137.30447 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56129E-004 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 322.32616 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.73154 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.73154 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.79437E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.77605E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71075 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63334E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.77605E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.73154 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 40202.78882 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.79437E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1815.58566 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.17836 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.17836 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.83432E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.73155E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70975 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.92735E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.73155E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.17836 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 40385.42905 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.83432E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1823.83051 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.87154 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.87154 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.55516E-004 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.78789E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70985 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75360E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.78789E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.87154 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7109.27490 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55516E-004 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 321.06090 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84871 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.84871 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.55714E-004 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.71987E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70983 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.76067E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.71987E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.84871 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7118.35892 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55714E-004 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 321.47095 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18463 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60100 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71196 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.80268E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.18586E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71196 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14563.91269 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18586E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 534.80210 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24921 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24921 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.81491E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.90320E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70991 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72060E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.90320E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24921 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2201.10062 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.81491E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 99.39491 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24182 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24182 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.82209E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.68149E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70990 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72694E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.68149E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24182 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2204.38030 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.82209E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 99.54295 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.18433 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.18433 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.30603E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.81873E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70975 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78429E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.81873E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.18433 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 10541.83020 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.30603E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 476.03385 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14819 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11764 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.82900 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78085 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82900 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23856E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.61558E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78085 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16528.32691 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.61558E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 513.26982 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25808 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11192 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.78900 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78163 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78900 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40424E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.64777E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78163 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16675.50661 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.64777E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 518.57269 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26426 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.25300E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24300 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55022 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09592E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37514E-004 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55022 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6286.35963 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37514E-004 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 203.06416 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66723 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.47066 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28200 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18816 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.09499E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14590E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35952 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9809.81787 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14590E-004 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 406.49619 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.07478 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.53158 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.09919 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.53158 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.99310 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.99310 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50167 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.99310 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.99310 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.19349 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90167 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.22726E-002 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 633025.69331 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.81045E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.99310 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 311825.82980 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.82120E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5547.05362 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.99310 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.81045E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.63024E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.82120E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.20000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89847 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.53651E-002 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 87803.63747 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.51117E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 30469.71807 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.66526E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 542.02424 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.51117E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.89629E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.66526E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.58133E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4172.79897 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.31350E-002 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.57620 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.31350E-002 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3916.52791 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 600457.59577 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 600457.60000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31350E-002 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.58133E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.09760 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.58133E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2888.96946 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.58133E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 902567.75354 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 903156.85000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 102.95988 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 12125.65 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 6308.59 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2825.29 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 4074.02 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2934.46 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 5390.68 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 20614.16 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 52414.46 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 12058.55 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 12073.91 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 68010.59 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 68319.49 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 12026.50 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 12041.87 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 22123.03 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 3723.34 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 3728.89 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 17832.40 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 25088.97 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 25312.19 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9539.65 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 14891.15 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 238402.27 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 23295.22 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 16117.32 | 13435.23 | 2682.09 | 0.83 | 3720.48 | 37.74 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15692.05 | 13071.89 | 2620.17 | 0.83 | 3613.52 | 36.65 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 94681.01 | 79763.30 | 14917.71 | 0.84 | 22683.44 | 230.07 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 90072.15 | 73581.11 | 16491.04 | 0.82 | 19480.90 | 197.59 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 14713.77 | 12233.30 | 2480.47 | 0.83 | 3365.05 | 34.13 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 14347.83 | 11919.79 | 2428.04 | 0.83 | 3275.96 | 33.23 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4182.91 | 3490.01 | 692.90 | 0.83 | 968.75 | 9.83 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4063.36 | 3387.95 | 675.41 | 0.83 | 938.75 | 9.52 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 20103.89 | 16660.63 | 3443.25 | 0.83 | 4550.74 | 46.16 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 610048.48 | 395690.33 | 214358.14 | 0.65 | 95453.64 | 968.14 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64803.99 | 40877.16 | 23926.83 | 0.63 | 9107.44 | 92.37 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.12 | 14.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.590 | 0.542 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.655 | 0.597 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.717 | 0.648 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.717 | 0.648 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.717 | 0.648 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.717 | 0.648 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.648 | 0.591 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.710 | 0.642 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.710 | 0.642 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.710 | 0.642 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.710 | 0.642 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.710 | 0.642 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.710 | 0.642 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.710 | 0.642 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.710 | 0.642 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.24_SHGC_0.29 | N/A | 1.362 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6096720157E-002 | 2.2181253393E-002 | Pass | Pass | 5.0704941593E-003 | 1.4557981796E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2479975367E-003 | 9.0599488600E-004 | Pass | Pass | 0.1054208097 | 0.2746721187 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.2244765632E-003 | 1.3110685534E-002 | Pass | Pass | 2.7676675758E-002 | 7.2205754850E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1624771326E-002 | 1.6840454756E-002 | Pass | Pass | 0.1686729673 | 0.8888341267 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.0050488499E-004 | 5.5168742062E-004 | Pass | Pass | 4.4211778746E-002 | 7.5541606226E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.6634059376E-005 | 7.6629825538E-005 | Pass | Pass | 2.1531509945E-002 | 6.2506226380E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5451913659E-003 | 2.6077410828E-003 | Pass | Pass | 4.5402576655E-002 | 0.1232271159 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1378371302E-002 | 3.6956926415E-002 | Pass | Pass | 1.6752226040E-002 | 4.8157879641E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2481125508E-002 | 0.3186227355 | Pass | Pass | 9.2599354061E-002 | 0.2637478306 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2628135286E-002 | 0.3224891502 | Pass | Pass | 8.9394590801E-002 | 0.2648527982 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.5781674142E-002 | 2.8406335333E-002 | Pass | Pass | 5.2818671602E-002 | 0.1817782266 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.9772376580E-002 | 0.1021401162 | Pass | Pass | 0.3444674514 | 1.0863721745 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2280339346E-002 | 0.3144470796 | Pass | Pass | 9.4666472553E-002 | 0.2743264498 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2512358642E-002 | 0.3180321936 | Pass | Pass | 9.5423784247E-002 | 0.2793623950 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3514042156E-004 | 3.3210515002E-004 | Pass | Pass | 0.8372302506 | 6.5546973313 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2626069481E-002 | 0.3412805164 | Pass | Pass | 0.1549098981 | 0.7640578437 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2665281310E-002 | 0.3451731717 | Pass | Pass | 0.1954698900 | 0.7491769595 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.3622782786E-002 | 0.2830691815 | Pass | Pass | 7.2488165782E-002 | 0.1819851080 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7950254589E-002 | 9.2216807443E-002 | Pass | Pass | 1.0887090077E-002 | 2.8521743496E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8730690610E-002 | 9.5886082662E-002 | Pass | Pass | 1.0392895535E-002 | 2.2212035202E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1362294676E-003 | 2.1822607438E-003 | Pass | Pass | 2.4120489441E-002 | 4.6159975056E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.1249207944E-004 | 3.0066089926E-004 | Pass | Pass | 0.1976196670 | 0.7533808982 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4301.71 | 170.10 | 2128.84 | 6099.68 | 3148.99 | 15849.33 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.542 | 0.590 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.597 | 0.655 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.591 | 0.648 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.591 | 0.648 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.591 | 0.648 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.591 | 0.648 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.591 | 0.648 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.362 | 0.291 | 0.500 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.362 | 0.291 | 0.500 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.362 | 0.291 | 0.500 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.362 | 0.291 | 0.500 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.362 | 0.291 | 0.500 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.362 | 0.291 | 0.500 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.362 | 0.291 | 0.500 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.362 | 0.291 | 0.500 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.362 | 0.291 | 0.500 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.362 | 0.291 | 0.500 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.362 | 0.291 | 0.500 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.362 | 0.291 | 0.500 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.362 | 0.291 | 0.500 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.362 | 0.291 | 0.500 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.362 | 0.291 | 0.500 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.362 | 0.291 | 0.500 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.362 | 0.291 | 0.500 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.362 | 0.291 | 0.500 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.362 | 0.291 | 0.500 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.362 | 0.291 | 0.500 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.362 | 0.291 | 0.500 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.24_SHGC_0.29 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.362 | 0.291 | 0.500 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.362 | 0.291 | 0.500 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.362 | 0.291 | 0.500 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.362 | 0.291 | 0.500 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.362 | 0.291 | 0.500 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.362 | 0.291 | 0.500 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.362 | 0.291 | 0.500 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.362 | 0.291 | 0.500 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.24_SHGC_0.29 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.362 | 0.291 | 0.500 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.362 | 0.291 | 0.500 | |||||||||||||||||
North Total or Average | 432.95 | 1.362 | 0.291 | 0.500 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.362 | 0.291 | 0.500 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.2037 | 1978.83 | 12276.14 | LightsWired | LTG_SCH_BASEMENT | 40.17 | 168.00 | 40.12 | 0.0000 | Y | 92.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 7.5557 | 67.07 | 506.77 | LightsWired | LTG_SCH_RETAIL | 44.04 | 168.00 | 43.99 | 0.0000 | Y | 4.18 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 7.5557 | 77.67 | 586.84 | LightsWired | LTG_SCH_RETAIL | 44.04 | 168.00 | 43.99 | 0.0000 | Y | 4.85 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 7.2603 | 164.24 | 1192.45 | LightsWired | LTG_SCH_MECHANIC | 38.78 | 168.00 | 38.73 | 0.0000 | Y | 8.67 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.7794 | 94.76 | 358.14 | LightsWired | LTG_SCH_STORAGE | 29.59 | 168.00 | 29.56 | 0.0000 | Y | 1.99 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.2151 | 78.04 | 406.98 | LightsWired | LTG_SCH_LAUNDRY | 48.47 | 168.00 | 48.41 | 0.0000 | Y | 3.70 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 7.7715 | 188.86 | 1467.75 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 23.68 | 0.0000 | Y | 6.52 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.1806 | 1308.19 | 10701.70 | LightsWired | LTG_SCH_LOBBY | 41.54 | 168.00 | 39.05 | 0.0000 | Y | 78.45 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4993 | 1557.62 | 7008.22 | LightsWired | LTG_SCH_CORRIDOR | 41.54 | 168.00 | 41.50 | 0.0000 | Y | 54.59 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 7.7715 | 331.66 | 2577.49 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 29.81 | 0.0000 | Y | 14.43 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 7.7715 | 331.66 | 2577.49 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 29.81 | 0.0000 | Y | 14.43 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 12.1686 | 103.30 | 1257.07 | LightsWired | LTG_SCH_KITCHEN | 38.78 | 168.00 | 38.73 | 0.0000 | Y | 9.14 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4993 | 412.12 | 1854.28 | LightsWired | LTG_SCH_CORRIDOR | 41.54 | 168.00 | 41.50 | 0.0000 | Y | 14.44 |
Interior Lighting Total | 5.5793 | 11345.29 | 63298.26 | 276.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10701.70 | 749.12 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10701.70 | 749.12 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1467.75 | 572.42 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1467.75 | 572.42 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2577.49 | 515.50 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 9571.94 | AstronomicalClock | - | 83.63 | 83.63 | 150.26 | |
Exterior Lighting Total | 9571.94 | 150.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 600457.60 | 0.94 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 903156.85 | 3.11 | 903315.60 | 3.11 | 4.12 | 14.07 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10655.57 | 16117.32 | 13435.23 | 2682.09 | 0.83 | - | 3720.48 | 37.74 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10380.04 | 15692.05 | 13071.89 | 2620.17 | 0.83 | - | 3613.52 | 36.65 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62100.92 | 94681.01 | 79763.30 | 14917.71 | 0.84 | - | 22683.44 | 230.07 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 60545.13 | 90072.15 | 73581.11 | 16491.04 | 0.82 | - | 19480.90 | 197.59 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9748.08 | 14713.77 | 12233.30 | 2480.47 | 0.83 | - | 3365.05 | 34.13 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9510.24 | 14347.83 | 11919.79 | 2428.04 | 0.83 | - | 3275.96 | 33.23 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2763.42 | 4182.91 | 3490.01 | 692.90 | 0.83 | - | 968.75 | 9.83 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2685.90 | 4063.36 | 3387.95 | 675.41 | 0.83 | - | 938.75 | 9.52 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13352.51 | 20103.89 | 16660.63 | 3443.25 | 0.83 | - | 4550.74 | 46.16 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 633025.69 | 610048.48 | 395690.33 | 214358.14 | 0.65 | - | 95453.64 | 968.14 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 87803.64 | 64803.99 | 40877.16 | 23926.83 | 0.63 | - | 9107.44 | 92.37 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7985.21 | 12125.65 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4155.90 | 6308.59 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1858.53 | 2825.29 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2683.83 | 4074.02 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1932.20 | 2934.46 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3551.21 | 5390.68 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13560.20 | 20614.16 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34542.36 | 52414.46 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7128.22 | 12058.55 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7137.30 | 12073.91 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 40202.79 | 68010.59 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 40385.43 | 68319.49 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7109.27 | 12026.50 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7118.36 | 12041.87 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14563.91 | 22123.03 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2201.10 | 3723.34 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2204.38 | 3728.89 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 10541.83 | 17832.40 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 16528.33 | 25088.97 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 16675.51 | 25312.19 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6286.36 | 9539.65 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9809.82 | 14891.15 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 311825.83 | 238402.27 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 30469.72 | 23295.22 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.96 | 674.65 | 703.64 | 1.00 | 1.21 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 656.12 | 703.64 | 1.00 | 1.21 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.73 | 4032.92 | 703.64 | 1.00 | 0.96 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.18 | 3643.68 | 703.64 | 1.00 | 0.97 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.87 | 613.25 | 703.64 | 1.00 | 1.23 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.85 | 597.18 | 703.64 | 1.00 | 1.24 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 175.35 | 703.64 | 1.00 | 1.85 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.24 | 170.15 | 703.64 | 1.00 | 1.88 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.18 | 833.34 | 703.64 | 1.00 | 1.16 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.99 | 47037.94 | 2240.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.025813 | 4172.80 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.013135 | 3916.53 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.025813 | 2888.97 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.95 | 0.68 | 0.60 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.95 | 0.31 | 0.04 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 28676.82 | 28676.82 | 14.49 | 2.184 | 2.184 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 24.00 | 24.00 | 0.00934 | 26.09 | 0.01536 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4304.96 | 4304.96 | 64.18 | 0.328 | 0.328 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00924 | 30.93 | 0.01536 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2738.28 | 2738.28 | 35.26 | 0.209 | 0.209 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00964 | 30.67 | 0.01536 | 0.092 | 0.00 |
MECH_FLR_1 | 2713.89 | 2713.89 | 16.52 | 0.207 | 0.207 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00898 | 30.67 | 0.01536 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1265.23 | 1265.23 | 13.35 | 0.096 | 0.096 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00918 | 31.09 | 0.01536 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44719.23 | 44719.23 | 573.03 | 3.407 | 3.407 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00857 | 31.20 | 0.01537 | 0.000 | 0.00 |
CAFE_FLR_1 | 19281.19 | 19281.19 | 102.09 | 1.470 | 1.470 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01024 | 30.93 | 0.01536 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61355.03 | 61355.03 | 46.90 | 4.676 | 4.676 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.01012 | 31.02 | 0.01536 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9340.10 | 9340.10 | 239.35 | 0.959 | 0.959 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00873 | 29.54 | 0.01536 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9083.49 | 9083.49 | 232.81 | 0.932 | 0.932 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00874 | 29.36 | 0.01536 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 55838.29 | 55838.29 | 2276.90 | 5.732 | 5.732 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00863 | 31.02 | 0.01536 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 50444.89 | 50444.89 | 2056.41 | 5.178 | 5.178 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 21.11 | 21.11 | 0.00893 | 27.07 | 0.01536 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8489.99 | 8489.99 | 217.57 | 0.872 | 0.872 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00875 | 26.57 | 0.01536 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8267.58 | 8267.58 | 211.89 | 0.849 | 0.849 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00876 | 25.67 | 0.01535 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15551.39 | 15551.39 | 39.94 | 1.185 | 1.185 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00986 | 31.20 | 0.01537 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2427.67 | 2427.67 | 62.21 | 0.249 | 0.249 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00872 | 29.72 | 0.01536 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2355.63 | 2355.63 | 60.37 | 0.242 | 0.242 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00873 | 29.54 | 0.01536 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11536.86 | 11536.86 | 470.31 | 1.184 | 1.184 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00878 | 31.02 | 0.01536 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28164.64 | 28164.64 | 84.92 | 2.148 | 2.148 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01053 | 31.20 | 0.01537 | 1.188 | 0.00 |
DINING_FLR_6 | 29605.99 | 29605.99 | 89.27 | 2.258 | 2.258 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01044 | 31.20 | 0.01537 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29644.93 | 29644.93 | 286.97 | 2.264 | 2.264 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01016 | 30.25 | 0.01536 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8759.20 | 8759.20 | 21.25 | 0.667 | 0.667 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00918 | 31.20 | 0.01537 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1527.82 | 1527.82 | 0.77 | 0.069 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3389.90 | 3389.90 | 50.54 | 0.152 | 0.152 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00746 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1165.99 | 1165.99 | 15.01 | 0.052 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -26.20 | 0.00036 | 0.092 | 0.00 |
MECH_FLR_1 | 2189.18 | 2189.18 | 13.33 | 0.098 | 0.098 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00726 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1496.46 | 1496.46 | 15.79 | 0.067 | 0.067 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00736 | -26.20 | 0.00036 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2896.90 | 2896.90 | 37.12 | 0.130 | 0.130 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00724 | -26.20 | 0.00036 | 0.000 | 0.00 |
CAFE_FLR_1 | 8457.73 | 8457.73 | 44.78 | 0.380 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00752 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 20242.87 | 20242.87 | 15.47 | 0.910 | 1.894 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00743 | -26.20 | 0.00036 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 7128.22 | 7128.22 | 182.67 | 0.322 | 0.322 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00741 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7137.30 | 7137.30 | 182.93 | 0.323 | 0.323 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00741 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 40202.79 | 40202.79 | 1639.33 | 1.817 | 1.817 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00744 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 40385.43 | 40385.43 | 1646.33 | 1.825 | 1.825 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00744 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7109.27 | 7109.27 | 182.19 | 0.321 | 0.321 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00741 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7118.36 | 7118.36 | 182.44 | 0.322 | 0.322 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00741 | -26.20 | 0.00036 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10981.78 | 10981.78 | 28.20 | 0.493 | 0.493 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00753 | -26.20 | 0.00036 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2201.10 | 2201.10 | 56.41 | 0.099 | 0.099 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00751 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2204.38 | 2204.38 | 56.50 | 0.100 | 0.100 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10541.83 | 10541.83 | 429.74 | 0.476 | 0.476 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00753 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7567.16 | 7567.16 | 22.82 | 0.340 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 1.188 | 0.00 |
DINING_FLR_6 | 7710.31 | 7710.31 | 23.25 | 0.346 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3522.26 | 3522.26 | 34.10 | 0.158 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00705 | -26.20 | 0.00036 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8000.44 | 8000.44 | 19.41 | 0.360 | 0.360 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00770 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.99 | 20.99 | 7.56 | 7.56 | 20.9931 | 10.5316 | 20.9931 | 0.5017 | 0.3000 |
FLR_3_DOAS | 15.15 | 2.05 | 5.61 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7985.207 | 7985.207 | 1.282290 | 0.00017468 | 235.172 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7985.21 | 7985.21 | 1.282290 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00796560 | 49.1196 | 1527.82 | 0.00 | 8020.69 | 8020.69 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4155.900 | 4155.900 | 0.152321 | 0.00009091 | 172.203 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4155.90 | 4155.90 | 0.152321 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00745816 | 46.0331 | 3389.90 | 0.00 | 4175.78 | 4175.78 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1858.527 | 1858.527 | 0.137689 | 0.00004066 | 62.227 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1858.53 | 1858.53 | 0.137689 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00739720 | 45.6578 | 1165.99 | 0.00 | 1868.57 | 1868.57 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2683.834 | 2683.834 | 0.098374 | 0.00005871 | 111.203 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2683.83 | 2683.83 | 0.098374 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00725638 | 44.7990 | 2189.18 | 0.00 | 2696.67 | 2696.67 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1932.198 | 1932.198 | 0.086639 | 0.00004227 | 73.070 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1932.20 | 1932.20 | 0.086639 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00736270 | 45.4476 | 1496.46 | 0.00 | 1941.77 | 1941.77 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 3551.210 | 3551.210 | 0.130168 | 0.00007768 | 147.141 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3551.21 | 3551.21 | 0.130168 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00723502 | 44.6720 | 2896.90 | 0.00 | 3568.19 | 3568.19 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 13560.197 | 13560.197 | 1.014448 | 0.00029663 | 453.363 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13560.20 | 13560.20 | 1.014448 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00751603 | 46.3850 | 8457.73 | 0.00 | 13633.53 | 13633.53 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 34542.361 | 34542.361 | 2.842846 | 0.00075562 | 1131.314 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 34542.36 | 34542.36 | 2.842846 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00742927 | 45.8535 | 20242.87 | 0.00 | 34683.17 | 34683.17 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10655.571 | -999.000 | 0.958806 | 0.00030474 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 10655.57 | 10122.18 | 0.958806 | 21.71 | 15.29 | 0.00872908 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00872908 | 53.4005 | 9340.10 | 0.00 | 11163.99 | 10925.65 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7128.223 | 7128.223 | 0.322174 | 0.00015593 | 321.916 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7128.22 | 7128.22 | 0.322174 | 21.11 | 13.89 | 0.00740931 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00740931 | 45.4251 | 7128.22 | 0.00 | 7977.52 | 7977.52 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10380.038 | -999.000 | 0.932465 | 0.00029686 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 10380.04 | 9846.83 | 0.932465 | 21.71 | 15.30 | 0.00873540 | 12.80 | 11.68 | 0.00850000 | 29.36 | 0.01536168 | 22.63 | 0.0000 | 21.11 | 0.00873540 | 53.4386 | 9083.49 | 0.00 | 10874.75 | 10625.32 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7137.304 | 7137.304 | 0.322584 | 0.00015613 | 322.326 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7137.30 | 7137.30 | 0.322584 | 21.11 | 13.89 | 0.00741005 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00741005 | 45.4296 | 7137.30 | 0.00 | 7987.68 | 7987.68 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 62100.921 | -999.000 | 5.731545 | 0.00177605 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 62100.92 | 60252.98 | 5.731545 | 21.71 | 15.21 | 0.00863334 | 12.80 | 11.68 | 0.00850000 | 31.02 | 0.01536476 | 23.08 | 0.0000 | 21.11 | 0.00863334 | 52.8204 | 55838.29 | 0.00 | 65098.88 | 65098.88 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 40202.789 | 40202.789 | 1.817158 | 0.00087944 | 1815.586 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40202.79 | 40202.79 | 1.817158 | 21.11 | 13.92 | 0.00744223 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00744223 | 45.6212 | 40202.79 | 0.00 | 44994.14 | 44994.14 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 60545.133 | -999.000 | 5.178362 | 0.00173155 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | unknown | 7/21 19:00:00 | 60545.13 | 55125.90 | 5.178362 | 21.71 | 15.46 | 0.00892735 | 12.80 | 11.68 | 0.00850000 | 27.07 | 0.01535744 | 22.00 | 0.0000 | 21.11 | 0.00892735 | 54.5960 | 50444.89 | 0.00 | 63363.20 | 59010.68 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 40385.429 | 40385.429 | 1.825414 | 0.00088343 | 1823.831 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40385.43 | 40385.43 | 1.825414 | 21.11 | 13.93 | 0.00744443 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00744443 | 45.6345 | 40385.43 | 0.00 | 45198.55 | 45198.55 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9748.084 | -999.000 | 0.871540 | 0.00027879 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 9748.08 | 9210.77 | 0.871540 | 21.71 | 15.31 | 0.00875360 | 12.80 | 11.68 | 0.00850000 | 26.57 | 0.01535653 | 21.86 | 0.0000 | 21.11 | 0.00875360 | 53.5485 | 8489.99 | 0.00 | 10211.18 | 9930.68 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7109.275 | 7109.275 | 0.321318 | 0.00015552 | 321.061 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7109.27 | 7109.27 | 0.321318 | 21.11 | 13.89 | 0.00740786 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00740786 | 45.4163 | 7109.27 | 0.00 | 7956.31 | 7956.31 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9510.239 | -999.000 | 0.848710 | 0.00027199 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 9510.24 | 8972.23 | 0.848710 | 21.71 | 15.32 | 0.00876067 | 12.80 | 11.68 | 0.00850000 | 25.67 | 0.01535487 | 21.60 | 0.0000 | 21.11 | 0.00876067 | 53.5912 | 8267.58 | 0.00 | 9962.85 | 9671.33 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7118.359 | 7118.359 | 0.321728 | 0.00015571 | 321.471 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7118.36 | 7118.36 | 0.321728 | 21.11 | 13.89 | 0.00740860 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00740860 | 45.4208 | 7118.36 | 0.00 | 7966.48 | 7966.48 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14563.913 | 14563.913 | 0.711960 | 0.00031859 | 534.802 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14563.91 | 14563.91 | 0.711960 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00752598 | 46.4421 | 10981.78 | 0.00 | 14637.48 | 14637.48 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2763.420 | -999.000 | 0.249212 | 0.00007903 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 2763.42 | 2629.97 | 0.249212 | 21.71 | 15.28 | 0.00872060 | 12.80 | 11.68 | 0.00850000 | 29.72 | 0.01536233 | 22.73 | 0.0000 | 21.11 | 0.00872060 | 53.3493 | 2427.67 | 0.00 | 2895.47 | 2839.84 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2201.101 | 2201.101 | 0.099483 | 0.00004815 | 99.395 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2201.10 | 2201.10 | 0.099483 | 21.11 | 13.99 | 0.00751452 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00751452 | 46.0622 | 2201.10 | 0.00 | 2463.35 | 2463.35 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2685.897 | -999.000 | 0.241817 | 0.00007681 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2685.90 | 2552.64 | 0.241817 | 21.71 | 15.29 | 0.00872694 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00872694 | 53.3876 | 2355.63 | 0.00 | 2814.10 | 2755.53 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2204.380 | 2204.380 | 0.099632 | 0.00004822 | 99.543 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2204.38 | 2204.38 | 0.099632 | 21.11 | 13.99 | 0.00751523 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00751523 | 46.0665 | 2204.38 | 0.00 | 2467.03 | 2467.03 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13352.514 | -999.000 | 1.184326 | 0.00038187 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 13352.51 | 12532.91 | 1.184326 | 21.71 | 15.34 | 0.00878429 | 12.80 | 11.68 | 0.00850000 | 31.02 | 0.01536476 | 23.08 | 0.0000 | 21.11 | 0.00878429 | 53.7338 | 11536.86 | 0.00 | 13985.33 | 13495.08 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 10541.830 | 10541.830 | 0.476471 | 0.00023060 | 476.034 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10541.83 | 10541.83 | 0.476471 | 21.11 | 14.01 | 0.00753209 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00753209 | 46.1675 | 10541.83 | 0.00 | 11797.99 | 11797.99 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 16528.327 | 16528.327 | 1.780846 | 0.00036156 | 513.270 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16528.33 | 16528.33 | 1.780846 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764678 | 47.1797 | 7567.16 | 0.00 | 16598.58 | 16598.58 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 16675.507 | 16675.507 | 1.781626 | 0.00036478 | 518.573 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 16675.51 | 16675.51 | 1.781626 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765304 | 47.2178 | 7710.31 | 0.00 | 16746.34 | 16746.34 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6286.360 | 6286.360 | 0.550215 | 0.00013751 | 203.064 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 6286.36 | 6286.36 | 0.550215 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00704887 | 43.5384 | 3522.26 | 0.00 | 6312.19 | 6312.19 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9809.818 | 9809.818 | 0.359516 | 0.00021459 | 406.496 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 9809.82 | 9809.82 | 0.359516 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00770493 | 47.5334 | 8000.44 | 0.00 | 9856.74 | 9856.74 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 633025.693 | -999.000 | 20.993095 | 0.01810445 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 633025.69 | 401076.23 | 20.993095 | 27.19 | 19.90 | 0.01227259 | 10.90 | 10.89 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 44.4394 | 23.99 | 0.00980727 | 50.2762 | 275349.78 | 0.00 | 650660.61 | 400091.66 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 311825.830 | 311825.830 | 6.297929 | 0.00682120 | 5547.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 311825.83 | 311825.83 | 6.297929 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.75 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 148.1312 | 21.00 | 0.00751172 | 46.3524 | 78196.98 | 0.00 | 207182.54 | 207182.54 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87803.637 | -999.000 | 2.051317 | 0.00251117 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 87803.64 | 47531.07 | 2.051317 | 31.20 | 23.13 | 0.01536508 | 11.90 | 11.31 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 99.9965 | 21.11 | 0.00877662 | 53.6859 | 147542.58 | 0.00 | 89691.54 | 48118.14 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30469.718 | 30469.718 | 0.615395 | 0.00066653 | 542.024 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 30469.72 | 30469.72 | 0.615395 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.75 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3216 | 21.11 | 0.00744410 | 45.6326 | 124028.69 | 0.00 | 20244.61 | 20244.61 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7985.207 | 7985.207 | 1.282290 | 0.00017468 | 235.172 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 1.3036 | 1.329854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7985.21 | 7985.21 | 1.0000 | 1.47278150 | 1.282290 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.17465881 | 60.00 | 48.89 | 11.11 | 0.000 | 7985.21 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00796560 | 21.00 | 0.00796560 | 49.1196 | 1527.82 | 0.00 | 8020.69 | 8020.69 | 1.47278150 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.94 | 15.20 | 0.00800000 | 42380.7 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4155.900 | 4155.900 | 0.152321 | 0.00009091 | 172.203 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 0.6785 | 0.692122 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4155.90 | 4155.90 | 1.0000 | 0.17494878 | 0.152321 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09090115 | 60.00 | 48.89 | 11.11 | 0.000 | 4155.90 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00745816 | 21.00 | 0.00745816 | 46.0331 | 3389.90 | 0.00 | 4175.78 | 4175.78 | 0.17494878 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60803.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1858.527 | 1858.527 | 0.137689 | 0.00004066 | 62.227 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 0.3034 | 0.309518 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1858.53 | 1858.53 | 1.0000 | 0.15814346 | 0.137689 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.04065117 | 60.00 | 48.89 | 11.11 | 0.000 | 1858.53 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00739720 | 21.00 | 0.00739720 | 45.6578 | 1165.99 | 0.00 | 1868.57 | 1868.57 | 0.15814346 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.19 | 17.43 | 0.00800000 | 48750.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2683.834 | 2683.834 | 0.098374 | 0.00005871 | 111.203 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 0.4381 | 0.446965 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2683.83 | 2683.83 | 1.0000 | 0.11298767 | 0.098374 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.05870296 | 60.00 | 48.89 | 11.11 | 0.000 | 2683.83 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00725638 | 21.00 | 0.00725638 | 44.7990 | 2189.18 | 0.00 | 2696.67 | 2696.67 | 0.11298767 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60801.7 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1932.198 | 1932.198 | 0.086639 | 0.00004227 | 73.070 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 0.3154 | 0.321788 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1932.20 | 1932.20 | 1.0000 | 0.09951011 | 0.086639 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.04226257 | 60.00 | 48.89 | 11.11 | 0.000 | 1932.20 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00736270 | 21.00 | 0.00736270 | 45.4476 | 1496.46 | 0.00 | 1941.77 | 1941.77 | 0.09951011 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.74 | 19.89 | 0.00800000 | 56448.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3551.210 | 3551.210 | 0.130168 | 0.00007768 | 147.141 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 0.5797 | 0.591417 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3551.21 | 3551.21 | 1.0000 | 0.14950469 | 0.130168 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07767489 | 60.00 | 48.89 | 11.11 | 0.000 | 3551.21 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00723502 | 21.00 | 0.00723502 | 44.6720 | 2896.90 | 0.00 | 3568.19 | 3568.19 | 0.14950469 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60801.5 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13560.197 | 13560.197 | 1.014448 | 0.00029663 | 453.363 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 2.2138 | 2.258311 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13560.20 | 13560.20 | 1.0000 | 1.16515049 | 1.014448 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.29659943 | 60.00 | 48.89 | 11.11 | 0.000 | 13560.20 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00751603 | 21.00 | 0.00751603 | 46.3850 | 8457.73 | 0.00 | 13633.53 | 13633.53 | 1.16515049 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.07 | 17.39 | 0.00800000 | 48635.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34542.361 | 34542.361 | 2.842846 | 0.00075562 | 1131.314 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 5.6392 | 5.752673 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 34542.36 | 34542.36 | 1.0000 | 3.26516732 | 2.842846 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.75553803 | 60.00 | 48.89 | 11.11 | 0.000 | 34542.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00742927 | 21.00 | 0.00742927 | 45.8535 | 20242.87 | 0.00 | 34683.17 | 34683.17 | 3.26516732 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.02 | 17.02 | 0.00800000 | 47556.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10655.571 | -999.000 | 0.958806 | 0.00030474 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0669 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.958806 | 1.10124251 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 1.1806 | 1.180562 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 10655.57 | 10122.18 | 1.0000 | 1.10124251 | 0.958806 | 21.71 | 15.29 | 0.00872908 | 43998.1 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.30471119 | 6.70 | 15.03 | 8.33 | 0.000 | 10655.57 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00872908 | 21.11 | 0.00872908 | 53.4005 | 9340.10 | 0.00 | 11163.99 | 10925.65 | 1.10124251 | 21.71 | 15.77 | 0.00872908 | 43998.1 | 11.99 | 11.91 | 0.00864330 | 33860.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7128.223 | 7128.223 | 0.322174 | 0.00015593 | 321.916 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.958806 | 1.10124251 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 1.1637 | 1.187132 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7128.22 | 7128.22 | 1.0000 | 0.37003476 | 0.322174 | 21.11 | 13.89 | 0.00740931 | 40031.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15591417 | 60.00 | 48.89 | 11.11 | 0.000 | 7128.22 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00740931 | 21.11 | 0.00740931 | 45.4251 | 7128.22 | 0.00 | 7977.52 | 7977.52 | 0.37003476 | 16.60 | 12.57 | 0.00740931 | 35439.2 | 37.76 | 20.07 | 0.00740931 | 56998.1 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10380.038 | -999.000 | 0.932465 | 0.00029686 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0787 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.932465 | 1.07098766 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 1.1501 | 1.150035 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 10380.04 | 9846.83 | 1.0000 | 1.07098766 | 0.932465 | 21.71 | 15.30 | 0.00873540 | 44014.2 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.29683194 | 6.70 | 15.03 | 8.33 | 0.000 | 10380.04 | 29.36 | 0.01536168 | 22.63 | 0.00000000 | 0.0000 | 21.11 | 0.00873540 | 21.11 | 0.00873540 | 53.4386 | 9083.49 | 0.00 | 10874.75 | 10625.32 | 1.07098766 | 21.71 | 15.77 | 0.00873540 | 44014.2 | 11.99 | 11.91 | 0.00864310 | 33860.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7137.304 | 7137.304 | 0.322584 | 0.00015613 | 322.326 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.932465 | 1.07098766 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 1.1652 | 1.188644 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7137.30 | 7137.30 | 1.0000 | 0.37050618 | 0.322584 | 21.11 | 13.89 | 0.00741005 | 40033.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15611281 | 60.00 | 48.89 | 11.11 | 0.000 | 7137.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00741005 | 21.11 | 0.00741005 | 45.4296 | 7137.30 | 0.00 | 7987.68 | 7987.68 | 0.37050618 | 16.60 | 12.57 | 0.00741005 | 35441.1 | 37.76 | 20.07 | 0.00741005 | 56999.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62100.921 | -999.000 | 5.731545 | 0.00177605 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8889 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.731545 | 6.58299903 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 6.8805 | 6.880343 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 62100.92 | 60252.98 | 1.0000 | 6.58299903 | 5.731545 | 21.71 | 15.21 | 0.00863334 | 43755.7 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 1.77586413 | 6.70 | 15.03 | 8.33 | 0.000 | 62100.92 | 31.02 | 0.01536476 | 23.08 | 0.00000000 | 0.0000 | 21.11 | 0.00863334 | 21.11 | 0.00863334 | 52.8204 | 55838.29 | 0.00 | 65098.88 | 65098.88 | 6.58299903 | 21.71 | 15.68 | 0.00863334 | 43755.7 | 12.02 | 11.91 | 0.00863334 | 33866.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40202.789 | 40202.789 | 1.817158 | 0.00087944 | 1815.586 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.731545 | 6.58299903 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 6.5633 | 6.695359 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40202.79 | 40202.79 | 1.0000 | 2.08710787 | 1.817158 | 21.11 | 13.92 | 0.00744223 | 40116.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.87934741 | 60.00 | 48.89 | 11.11 | 0.000 | 40202.79 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00744223 | 21.11 | 0.00744223 | 45.6212 | 40202.79 | 0.00 | 44994.14 | 44994.14 | 2.08710787 | 16.60 | 12.61 | 0.00744223 | 35522.6 | 37.76 | 20.09 | 0.00744223 | 57080.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 60545.133 | -999.000 | 5.178362 | 0.00173155 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4355 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.178362 | 5.94763842 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 6.7081 | 6.707973 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | unknown | unknown | unknown | 7/21 19:00:00 | Sensible | 60545.13 | 55125.90 | 1.0000 | 5.94763842 | 5.178362 | 21.71 | 15.46 | 0.00892735 | 44501.9 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 1.73137418 | 6.70 | 15.03 | 8.33 | 0.000 | 60545.13 | 27.07 | 0.01535744 | 22.00 | 0.00000000 | 0.0000 | 21.11 | 0.00892735 | 21.11 | 0.00892735 | 54.5960 | 50444.89 | 0.00 | 63363.20 | 59010.68 | 5.94763842 | 21.71 | 15.94 | 0.00892735 | 44501.9 | 12.00 | 11.90 | 0.00863733 | 33848.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40385.429 | 40385.429 | 1.825414 | 0.00088343 | 1823.831 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.178362 | 5.94763842 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 6.5931 | 6.725775 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40385.43 | 40385.43 | 1.0000 | 2.09658957 | 1.825414 | 21.11 | 13.93 | 0.00744443 | 40122.3 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.88334226 | 60.00 | 48.89 | 11.11 | 0.000 | 40385.43 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00744443 | 21.11 | 0.00744443 | 45.6345 | 40385.43 | 0.00 | 45198.55 | 45198.55 | 2.09658957 | 16.60 | 12.61 | 0.00744443 | 35528.1 | 37.76 | 20.10 | 0.00744443 | 57086.3 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9748.084 | -999.000 | 0.871540 | 0.00027879 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1125 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.871540 | 1.00101275 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 1.0800 | 1.080019 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 9748.08 | 9210.77 | 1.0000 | 1.00101275 | 0.871540 | 21.71 | 15.31 | 0.00875360 | 44060.4 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.27876033 | 6.70 | 15.03 | 8.33 | 0.000 | 9748.08 | 26.57 | 0.01535653 | 21.86 | 0.00000000 | 0.0000 | 21.11 | 0.00875360 | 21.11 | 0.00875360 | 53.5485 | 8489.99 | 0.00 | 10211.18 | 9930.68 | 1.00101275 | 21.71 | 15.79 | 0.00875360 | 44060.4 | 11.99 | 11.91 | 0.00864254 | 33859.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7109.275 | 7109.275 | 0.321318 | 0.00015552 | 321.061 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.871540 | 1.00101275 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 1.1606 | 1.183976 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7109.27 | 7109.27 | 1.0000 | 0.36905113 | 0.321318 | 21.11 | 13.89 | 0.00740786 | 40028.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15549972 | 60.00 | 48.89 | 11.11 | 0.000 | 7109.27 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00740786 | 21.11 | 0.00740786 | 45.4163 | 7109.27 | 0.00 | 7956.31 | 7956.31 | 0.36905113 | 16.60 | 12.57 | 0.00740786 | 35435.6 | 37.76 | 20.07 | 0.00740786 | 56994.4 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9510.239 | -999.000 | 0.848710 | 0.00027199 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1257 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.848710 | 0.97479059 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 1.0537 | 1.053667 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 9510.24 | 8972.23 | 1.0000 | 0.97479059 | 0.848710 | 21.71 | 15.32 | 0.00876067 | 44078.4 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.27195880 | 6.70 | 15.03 | 8.33 | 0.000 | 9510.24 | 25.67 | 0.01535487 | 21.60 | 0.00000000 | 0.0000 | 21.11 | 0.00876067 | 21.11 | 0.00876067 | 53.5912 | 8267.58 | 0.00 | 9962.85 | 9671.33 | 0.97479059 | 21.71 | 15.79 | 0.00876067 | 44078.4 | 11.99 | 11.91 | 0.00864215 | 33857.9 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7118.359 | 7118.359 | 0.321728 | 0.00015571 | 321.471 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.848710 | 0.97479059 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 1.1621 | 1.185489 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7118.36 | 7118.36 | 1.0000 | 0.36952269 | 0.321728 | 21.11 | 13.89 | 0.00740860 | 40030.1 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15569841 | 60.00 | 48.89 | 11.11 | 0.000 | 7118.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00740860 | 21.11 | 0.00740860 | 45.4208 | 7118.36 | 0.00 | 7966.48 | 7966.48 | 0.36952269 | 16.60 | 12.57 | 0.00740860 | 35437.4 | 37.76 | 20.07 | 0.00740860 | 56996.3 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14563.913 | 14563.913 | 0.711960 | 0.00031859 | 534.802 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 2.3776 | 2.425469 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14563.91 | 14563.91 | 1.0000 | 0.81772588 | 0.711960 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.31855350 | 60.00 | 48.89 | 11.11 | 0.000 | 14563.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00752598 | 21.00 | 0.00752598 | 46.4421 | 10981.78 | 0.00 | 14637.48 | 14637.48 | 0.81772588 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.15 | 19.39 | 0.00800000 | 54835.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2763.420 | -999.000 | 0.249212 | 0.00007903 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0512 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.249212 | 0.28623378 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 0.3062 | 0.306167 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 2763.42 | 2629.97 | 1.0000 | 0.28623378 | 0.249212 | 21.71 | 15.28 | 0.00872060 | 43976.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.07902393 | 6.70 | 15.03 | 8.33 | 0.000 | 2763.42 | 29.72 | 0.01536233 | 22.73 | 0.00000000 | 0.0000 | 21.11 | 0.00872060 | 21.11 | 0.00872060 | 53.3493 | 2427.67 | 0.00 | 2895.47 | 2839.84 | 0.28623378 | 21.71 | 15.76 | 0.00872060 | 43976.6 | 11.99 | 11.91 | 0.00864357 | 33860.8 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2201.101 | 2201.101 | 0.099483 | 0.00004815 | 99.395 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.249212 | 0.28623378 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 0.3593 | 0.366571 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2201.10 | 2201.10 | 1.0000 | 0.11426218 | 0.099483 | 21.11 | 13.99 | 0.00751452 | 40299.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.04814423 | 60.00 | 48.89 | 11.11 | 0.000 | 2201.10 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00751452 | 21.11 | 0.00751452 | 46.0622 | 2201.10 | 0.00 | 2463.35 | 2463.35 | 0.11426218 | 16.60 | 12.68 | 0.00751452 | 35705.6 | 37.76 | 20.15 | 0.00751452 | 57264.4 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2685.897 | -999.000 | 0.241817 | 0.00007681 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0629 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.241817 | 0.27774049 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 0.2976 | 0.297578 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2685.90 | 2552.64 | 1.0000 | 0.27774049 | 0.241817 | 21.71 | 15.29 | 0.00872694 | 43992.7 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.07680705 | 6.70 | 15.03 | 8.33 | 0.000 | 2685.90 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00872694 | 21.11 | 0.00872694 | 53.3876 | 2355.63 | 0.00 | 2814.10 | 2755.53 | 0.27774049 | 21.71 | 15.76 | 0.00872694 | 43992.7 | 11.99 | 11.91 | 0.00864337 | 33860.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2204.380 | 2204.380 | 0.099632 | 0.00004822 | 99.543 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.241817 | 0.27774049 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 0.3599 | 0.367117 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2204.38 | 2204.38 | 1.0000 | 0.11443243 | 0.099632 | 21.11 | 13.99 | 0.00751523 | 40301.0 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.04821596 | 60.00 | 48.89 | 11.11 | 0.000 | 2204.38 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00751523 | 21.11 | 0.00751523 | 46.0665 | 2204.38 | 0.00 | 2467.03 | 2467.03 | 0.11443243 | 16.60 | 12.68 | 0.00751523 | 35707.4 | 37.76 | 20.15 | 0.00751523 | 57266.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13352.514 | -999.000 | 1.184326 | 0.00038187 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1695 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.184326 | 1.36026503 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 1.4794 | 1.479364 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 13352.51 | 12532.91 | 1.0000 | 1.36026503 | 1.184326 | 21.71 | 15.34 | 0.00878429 | 44138.3 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.38183412 | 6.70 | 15.03 | 8.33 | 0.000 | 13352.51 | 31.02 | 0.01536476 | 23.08 | 0.00000000 | 0.0000 | 21.11 | 0.00878429 | 21.11 | 0.00878429 | 53.7338 | 11536.86 | 0.00 | 13985.33 | 13495.08 | 1.36026503 | 21.71 | 15.81 | 0.00878429 | 44138.3 | 11.99 | 11.91 | 0.00864145 | 33857.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10541.830 | 10541.830 | 0.476471 | 0.00023060 | 476.034 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.184326 | 1.36026503 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 1.7210 | 1.755633 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10541.83 | 10541.83 | 1.0000 | 0.54725343 | 0.476471 | 21.11 | 14.01 | 0.00753209 | 40344.3 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.23057930 | 60.00 | 48.89 | 11.11 | 0.000 | 10541.83 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00753209 | 21.11 | 0.00753209 | 46.1675 | 10541.83 | 0.00 | 11797.99 | 11797.99 | 0.54725343 | 16.60 | 12.69 | 0.00753209 | 35750.1 | 37.76 | 20.16 | 0.00753209 | 57308.6 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16528.327 | 16528.327 | 1.780846 | 0.00036156 | 513.270 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 2.6983 | 2.752622 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 16528.33 | 16528.33 | 1.0000 | 2.04540057 | 1.780846 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.36152073 | 60.00 | 48.89 | 11.11 | 0.000 | 16528.33 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00764678 | 21.00 | 0.00764678 | 47.1797 | 7567.16 | 0.00 | 16598.58 | 16598.58 | 2.04540057 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.56 | 16.16 | 0.00800000 | 45049.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16675.507 | 16675.507 | 1.781626 | 0.00036478 | 518.573 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 2.7223 | 2.777133 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 16675.51 | 16675.51 | 1.0000 | 2.04629683 | 1.781626 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.36473996 | 60.00 | 48.89 | 11.11 | 0.000 | 16675.51 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00765304 | 21.00 | 0.00765304 | 47.2178 | 7710.31 | 0.00 | 16746.34 | 16746.34 | 2.04629683 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.63 | 16.18 | 0.00800000 | 45118.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6286.360 | 6286.360 | 0.550215 | 0.00013751 | 203.064 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 1.0263 | 1.046928 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 6286.36 | 6286.36 | 1.0000 | 0.63195269 | 0.550215 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.13750026 | 60.00 | 48.89 | 11.11 | 0.000 | 6286.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.71 | 0.00704887 | 21.00 | 0.00704887 | 43.5384 | 3522.26 | 0.00 | 6312.19 | 6312.19 | 0.63195269 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.40 | 16.81 | 0.00800000 | 46923.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9809.818 | 9809.818 | 0.359516 | 0.00021459 | 406.496 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 1.6015 | 1.633724 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 9809.82 | 9809.82 | 1.0000 | 0.41292462 | 0.359516 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.21456815 | 60.00 | 48.89 | 11.11 | 0.000 | 9809.82 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00770493 | 21.00 | 0.00770493 | 47.5334 | 8000.44 | 0.00 | 9856.74 | 9856.74 | 0.41292462 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60805.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 633025.693 | -999.000 | 20.993095 | 0.01810445 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.6541 | 1004.8586 | 1.1486 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.993095 | 24.11174215 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 70.1361 | 70.136086 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 633025.69 | 401076.23 | 1.0000 | 24.11174215 | 20.993095 | 27.19 | 19.90 | 0.01227259 | 58638.5 | 10.90 | 10.89 | 0.00850000 | 32384.7 | 18.10260785 | 6.70 | 15.03 | 8.33 | 47037.940 | 585987.75 | 31.20 | 0.01536508 | 23.13 | 9.32920000 | 44.4394 | 23.99 | 0.00979842 | 23.99 | 0.00980727 | 50.2762 | 275349.78 | 0.00 | 650660.61 | 400091.66 | 24.11174215 | 27.19 | 20.44 | 0.01227259 | 58638.5 | 11.05 | 11.01 | 0.00815120 | 31653.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 311825.830 | 311825.830 | 6.297929 | 0.00682120 | 5547.054 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.993095 | 24.11174215 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 50.9068 | 51.931366 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 311825.83 | 311825.83 | 1.0000 | 7.23352264 | 6.297929 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 6.82050286 | 60.00 | 48.89 | 11.11 | 0.000 | 311825.83 | -26.20 | 0.00036134 | -26.20 | 9.32920000 | 148.1312 | 20.98 | 0.00755705 | 21.00 | 0.00751172 | 46.3524 | 78196.98 | 0.00 | 207182.54 | 207182.54 | 7.23352264 | 2.80 | -3.86 | 0.00036134 | 3719.1 | 31.28 | 11.47 | 0.00036134 | 32361.1 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87803.637 | -999.000 | 2.051317 | 0.00251117 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.4029 | 1004.8586 | 1.1486 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.35596953 | 4197.9300 | 999.8980 | 25.81069027 | 15.03 | 6.70 | 8.33 | 902567.75 | 9.7282 | 9.728205 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 87803.64 | 47531.07 | 1.0000 | 2.35605237 | 2.051317 | 31.20 | 23.13 | 0.01536508 | 70669.3 | 11.90 | 11.31 | 0.00850000 | 33402.1 | 2.51091675 | 6.70 | 15.03 | 8.33 | 2195.006 | 85608.63 | 31.20 | 0.01536508 | 23.13 | 2.05124512 | 99.9965 | 21.11 | 0.00878274 | 21.11 | 0.00877662 | 53.6859 | 147542.58 | 0.00 | 89691.54 | 48118.14 | 2.35605237 | 31.20 | 23.70 | 0.01536508 | 70669.3 | 11.44 | 11.40 | 0.00836907 | 32600.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30469.718 | 30469.718 | 0.615395 | 0.00066653 | 542.024 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.35596953 | 4197.9300 | 999.8980 | 13.13368668 | 48.89 | 60.00 | 11.11 | 612542.04 | 4.9743 | 5.074416 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 30469.72 | 30469.72 | 1.0000 | 0.70681571 | 0.615395 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 0.66645794 | 60.00 | 48.89 | 11.11 | 0.000 | 30469.72 | -26.20 | 0.00036134 | -26.20 | 2.05124512 | 333.3216 | 21.11 | 0.00744552 | 21.11 | 0.00744410 | 45.6326 | 124028.69 | 0.00 | 20244.61 | 20244.61 | 0.70681571 | 2.80 | -3.86 | 0.00036134 | 3719.1 | 31.28 | 11.47 | 0.00036134 | 32361.1 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 20.99 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 233.33 | 8611.67 | 232.67 |
RETAIL_1_FLR_1 | 4094.83 | 6862.50 | 2673.00 |
RETAIL_2_FLR_1 | 1176.83 | 8239.33 | 991.50 |
MECH_FLR_1 | 2930.17 | 5903.33 | 1387.83 |
STORAGE_FLR_1 | 2095.33 | 8760.00 | 2095.33 |
LAUNDRY_FLR_1 | 8718.50 | 3700.33 | 3700.33 |
CAFE_FLR_1 | 1800.33 | 7983.00 | 1441.67 |
LOBBY_FLR_1 | 1336.83 | 7851.67 | 976.17 |
ROOM_1_FLR_3 | 3018.67 | 8391.00 | 3014.83 |
ROOM_2_FLR_3 | 3843.17 | 8182.17 | 3646.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2564.83 | 8736.50 | 2561.67 |
ROOM_5_FLR_3 | 3006.67 | 8372.50 | 2999.00 |
ROOM_6_FLR_3 | 3678.33 | 8273.50 | 3559.67 |
CORRIDOR_FLR_3 | 1792.67 | 8747.67 | 1792.67 |
ROOM_1_FLR_6 | 3579.33 | 8287.00 | 3536.67 |
ROOM_2_FLR_6 | 4416.33 | 8078.00 | 4176.00 |
ROOM_3_MULT9_FLR_6 | 2529.17 | 8367.00 | 2517.83 |
BANQUET_FLR_6 | 1671.17 | 7236.17 | 910.50 |
DINING_FLR_6 | 2226.33 | 6318.50 | 794.50 |
KITCHEN_FLR_6 | 8679.67 | 6166.17 | 6156.17 |
CORRIDOR_FLR_6 | 3886.00 | 6519.17 | 2197.00 |
Facility | 8760.00 | 8760.00 | 8056.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 3.00 | 0.00 | 3.00 |
ROOM_2_FLR_3 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3.67 | 19.83 | 3.67 | 19.83 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 17.67 | 0.00 | 17.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 9.33 | 0.00 | 9.33 |
ROOM_2_FLR_6 | 0.00 | 10.00 | 0.00 | 10.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 5.00 | 0.00 | 5.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3.67 | 44.33 | 3.67 | 44.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.704 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.236 | 0.141 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.183 | 0.047 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.098 | 0.053 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.608 | 0.052 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.386 | 0.151 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.50 | 142.30 | 748.35 | 3.584 | 0.110 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.92 | 422.44 | 5183.56 | 1.456 | 0.046 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.342 | 0.182 | 0.000 | 0.056 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.182 | 0.000 | 0.051 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.081 | 0.000 | 0.084 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.342 | 0.182 | 0.000 | 0.056 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.182 | 0.000 | 0.054 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.396 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.342 | 0.182 | 0.000 | 0.067 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.342 | 0.182 | 0.000 | 0.057 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.388 | 0.148 | 0.000 | 0.107 |
BANQUET_FLR_6 | 144.89 | 249.90 | 1010.89 | 4.675 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.89 | 249.90 | 1010.89 | 4.694 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 15.448 | 0.152 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.444 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.529 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.925 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.907 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.007 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.460 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 3.878 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.50 | 142.30 | 748.35 | 2.718 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.92 | 422.44 | 5183.56 | 1.137 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.300 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.89 | 249.90 | 1010.89 | 3.650 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.89 | 249.90 | 1010.89 | 3.655 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 4.122 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.310 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.75 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.047 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.50 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.173 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.92 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.89 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.89 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.69 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.036 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 29222300.35 | 0.00 | 29222300.35 | 0.00 | 29222300.35 | 26946214.98 | 5635.41 | 71.71 | 3052.88 | 0.00 |
RETAIL_1_FLR_1 | 2827542.13 | 0.00 | 2827542.13 | 322448.37 | 3149990.50 | 2498216.28 | 5057.05 | 89.33 | 3613.62 | 0.00 |
RETAIL_2_FLR_1 | 3137564.55 | 0.00 | 3137564.55 | 124465.48 | 3262030.03 | 2294951.32 | 560.38 | 638.94 | 7560.69 | 0.00 |
MECH_FLR_1 | 544997.01 | 0.00 | 544997.01 | 294162.45 | 839159.46 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1973999.14 | 0.00 | 1973999.14 | 169715.53 | 2143714.67 | 1821682.01 | 5637.33 | 72.07 | 3050.60 | 0.00 |
LAUNDRY_FLR_1 | 40760830.98 | 0.00 | 40760830.98 | 401663.80 | 41162494.78 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23113818.35 | 0.00 | 23113818.35 | 712790.38 | 23826608.73 | 14544917.54 | 211.67 | 130.17 | 8418.17 | 0.00 |
LOBBY_FLR_1 | 64869268.47 | 0.00 | 64869268.47 | 2036604.93 | 66905873.40 | 59728886.00 | 5633.66 | 74.30 | 3052.04 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 56821.79 | 1462898.63 | 187159.47 | 1650058.09 | 1946875.62 | 2433.17 | 5799.67 | 527.17 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 51423.64 | 1457335.74 | 187145.19 | 1644480.92 | 1946647.51 | 2433.17 | 5845.73 | 481.10 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 574.59 | 1100486.56 | 52219.59 | 1152706.15 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 369.17 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 54110.93 | 19124465.07 | 52233.87 | 19176698.94 | 26405105.73 | 2433.33 | 5810.67 | 515.99 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 56932.41 | 1463009.25 | 187159.47 | 1650168.71 | 1946875.62 | 2433.17 | 5799.67 | 527.17 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 54432.44 | 1460344.54 | 187145.19 | 1647489.72 | 1946647.51 | 2433.17 | 5799.69 | 527.14 | 0.00 |
CORRIDOR_FLR_3 | 16221368.47 | 0.00 | 16221368.47 | 226313.45 | 16447681.92 | 14972100.18 | 5637.74 | 72.12 | 3050.14 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 68604.13 | 420123.34 | 187199.47 | 607322.81 | 486718.90 | 2252.43 | 5800.47 | 707.10 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 57858.17 | 409336.19 | 187185.19 | 596521.38 | 486661.88 | 2275.66 | 5876.09 | 608.25 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 68546.92 | 2326878.33 | 95777.80 | 2422656.13 | 3126920.42 | 2433.33 | 5798.83 | 527.83 | 0.00 |
BANQUET_FLR_6 | 40645595.16 | 0.00 | 40645595.16 | 457094.06 | 41102689.22 | 37458366.31 | 5637.62 | 72.95 | 3049.43 | 0.00 |
DINING_FLR_6 | 40771661.11 | 0.00 | 40771661.11 | 457094.06 | 41228755.17 | 37458366.31 | 5614.66 | 78.91 | 3066.43 | 0.00 |
KITCHEN_FLR_6 | 41585669.74 | 0.00 | 41585669.74 | 409205.16 | 41994874.89 | 11584760.86 | 0.89 | 13.17 | 8745.94 | 0.00 |
CORRIDOR_FLR_6 | 4792904.86 | 0.00 | 4792904.86 | 400507.17 | 5193412.03 | 3961413.96 | 4796.50 | 60.20 | 3903.30 | 0.00 |
Total Facility | 0.19E+10 | 5777925.79 | 0.19E+10 | 18860290.15 | 0.20E+10 | 0.43E+10 | 8760.00 | 6279.61 | 8760.00 | 369.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9266 | 0.0000 | 0.9266 | 0.0000 | 0.9266 | 0.8545 | 5635.41 | 71.71 | 3052.88 |
RETAIL_1_FLR_1 | 0.0897 | 0.0000 | 0.0897 | 0.0102 | 0.0999 | 0.0792 | 5057.05 | 89.33 | 3613.62 |
RETAIL_2_FLR_1 | 0.0995 | 0.0000 | 0.0995 | 0.0039 | 0.1034 | 0.0728 | 560.38 | 638.94 | 7560.69 |
MECH_FLR_1 | 0.0173 | 0.0000 | 0.0173 | 0.0093 | 0.0266 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0626 | 0.0000 | 0.0626 | 0.0054 | 0.0680 | 0.0578 | 5637.33 | 72.07 | 3050.60 |
LAUNDRY_FLR_1 | 1.2925 | 0.0000 | 1.2925 | 0.0127 | 1.3053 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7329 | 0.0000 | 0.7329 | 0.0226 | 0.7555 | 0.4612 | 211.67 | 130.17 | 8418.17 |
LOBBY_FLR_1 | 2.0570 | 0.0000 | 2.0570 | 0.0646 | 2.1216 | 1.8940 | 5633.66 | 74.30 | 3052.04 |
ROOM_1_FLR_3 | 0.0446 | 0.0018 | 0.0464 | 0.0059 | 0.0523 | 0.0617 | 2433.17 | 5799.67 | 527.17 |
ROOM_2_FLR_3 | 0.0446 | 0.0016 | 0.0462 | 0.0059 | 0.0521 | 0.0617 | 2433.17 | 5845.73 | 481.10 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0017 | 0.6064 | 0.0017 | 0.6081 | 0.8373 | 2433.33 | 5810.67 | 515.99 |
ROOM_5_FLR_3 | 0.0446 | 0.0018 | 0.0464 | 0.0059 | 0.0523 | 0.0617 | 2433.17 | 5799.67 | 527.17 |
ROOM_6_FLR_3 | 0.0446 | 0.0017 | 0.0463 | 0.0059 | 0.0522 | 0.0617 | 2433.17 | 5799.69 | 527.14 |
CORRIDOR_FLR_3 | 0.5144 | 0.0000 | 0.5144 | 0.0072 | 0.5216 | 0.4748 | 5637.74 | 72.12 | 3050.14 |
ROOM_1_FLR_6 | 0.0111 | 0.0022 | 0.0133 | 0.0059 | 0.0193 | 0.0154 | 2252.43 | 5800.47 | 707.10 |
ROOM_2_FLR_6 | 0.0111 | 0.0018 | 0.0130 | 0.0059 | 0.0189 | 0.0154 | 2275.66 | 5876.09 | 608.25 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0022 | 0.0738 | 0.0030 | 0.0768 | 0.0992 | 2433.33 | 5798.83 | 527.83 |
BANQUET_FLR_6 | 1.2889 | 0.0000 | 1.2889 | 0.0145 | 1.3034 | 1.1878 | 5637.62 | 72.95 | 3049.43 |
DINING_FLR_6 | 1.2929 | 0.0000 | 1.2929 | 0.0145 | 1.3074 | 1.1878 | 5614.66 | 78.91 | 3066.43 |
KITCHEN_FLR_6 | 1.3187 | 0.0000 | 1.3187 | 0.0130 | 1.3316 | 0.3674 | 0.89 | 13.17 | 8745.94 |
CORRIDOR_FLR_6 | 0.1520 | 0.0000 | 0.1520 | 0.0127 | 0.1647 | 0.1256 | 4796.50 | 60.20 | 3903.30 |
Total Facility | 58.7266 | 0.1818 | 58.9084 | 0.4722 | 59.3807 | 73.7328 | 8760.00 | 6279.61 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.41E+09 | 0.00 | 0.41E+09 | 0.21E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 37933790.35 | 469305.03 | 38403095.38 | 64690340.46 | 8755.83 | 1.17 | 3.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 12.9871 | 0.0000 | 12.9871 | 6.7627 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2029 | 0.0149 | 1.2178 | 2.0513 | 8755.83 | 1.17 | 3.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 23.78 | 4633.17 | 0.00 | 0.00 | 0.00 | 4103.05 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 12.7029 | 14.9553 | 0.0000 | 0.0000 | 0.0000 | 10.7695 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.5748 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1344 |
Defaulted Fields | 1183 |
Fields with Defaults | 4016 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4201.75 | 59849.36 | 20-MAY-05:00 | 336874.67 | 26-JUL-19:40 |
Electricity:Building | 2110.08 | 27943.62 | 17-JUN-05:00 | 124003.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 235.57 | 2868.06 | 02-JAN-02:10 | 17194.07 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2102.99 | 27802.47 | 17-JUN-05:00 | 123762.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 454.53 | 3908.80 | 17-JUN-05:00 | 37630.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 92.46 | 840.16 | 02-JAN-02:10 | 7561.54 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 454.53 | 3908.80 | 17-JUN-05:00 | 37630.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 454.53 | 3908.80 | 17-JUN-05:00 | 37630.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 92.46 | 840.16 | 02-JAN-02:10 | 7561.54 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 454.53 | 3908.80 | 17-JUN-05:00 | 37630.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 14.37 | 182.36 | 02-JAN-02:10 | 1027.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 4.18 | 38.02 | 02-JAN-02:10 | 342.20 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 4.18 | 38.02 | 02-JAN-02:10 | 342.20 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 16.64 | 211.17 | 02-JAN-02:10 | 1190.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 4.85 | 44.03 | 02-JAN-02:10 | 396.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 4.85 | 44.03 | 02-JAN-02:10 | 396.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 21.14 | 255.50 | 02-JAN-02:10 | 1548.43 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.67 | 78.78 | 02-JAN-02:10 | 708.98 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.67 | 78.78 | 02-JAN-02:10 | 708.98 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.58 | 69.04 | 02-JAN-02:10 | 404.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.99 | 18.06 | 02-JAN-02:10 | 162.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.99 | 18.06 | 02-JAN-02:10 | 162.52 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.63 | 996.30 | 02-JAN-02:10 | 4875.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.70 | 33.61 | 02-JAN-02:10 | 302.47 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.70 | 33.61 | 02-JAN-02:10 | 302.47 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 20.86 | 234.94 | 17-JUN-05:00 | 1775.61 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 6.52 | 31.72 | 17-JUN-05:00 | 810.33 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 6.52 | 31.72 | 17-JUN-05:00 | 810.33 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 227.45 | 2793.88 | 17-JUN-05:00 | 16846.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 78.45 | 682.47 | 17-JUN-05:00 | 6817.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 78.45 | 682.47 | 17-JUN-05:00 | 6817.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 54.59 | 496.05 | 02-JAN-02:10 | 4464.45 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 54.59 | 496.05 | 02-JAN-02:10 | 4464.45 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 54.59 | 496.05 | 02-JAN-02:10 | 4464.45 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 190.28 | 2344.17 | 03-JUN-05:00 | 8170.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 14.43 | 94.87 | 03-JUN-05:00 | 1423.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 14.43 | 94.87 | 03-JUN-05:00 | 1423.01 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 190.28 | 2344.17 | 03-JUN-05:00 | 8170.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 14.43 | 94.87 | 03-JUN-05:00 | 1423.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 14.43 | 94.87 | 03-JUN-05:00 | 1423.01 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 440.25 | 5906.67 | 02-JAN-02:10 | 18521.62 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 9.14 | 83.05 | 02-JAN-02:10 | 747.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 9.14 | 83.05 | 02-JAN-02:10 | 747.41 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 14.44 | 131.25 | 02-JAN-02:10 | 1181.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 14.44 | 131.25 | 02-JAN-02:10 | 1181.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 14.44 | 131.25 | 02-JAN-02:10 | 1181.23 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.00 | 732.83 | 02-FEB-23:30 | 2790.03 | 09-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 858.86 | 2119.08 | 27-APR-01:10 | 184857.19 | 04-AUG-15:30 |
LowTempRefrigeration:Refrigeration:Electricity | 15.83 | 0.00 | 01-JAN-11:10 | 1306.51 | 31-JAN-08:10 |
MedTempRefrigeration:Refrigeration:Electricity | 21.07 | 614.95 | 02-FEB-04:10 | 716.15 | 31-AUG-13:40 |
Fans:Electricity | 571.32 | 12698.84 | 30-OCT-03:00 | 32399.09 | 26-JUN-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityProduced:Facility | 170.17 | -0.00 | 03-SEP-18:40 | 33462.85 | 25-APR-12:20 |
ElectricityProduced:Plant | 170.17 | -0.00 | 03-SEP-18:40 | 33462.85 | 25-APR-12:20 |
Photovoltaic:ElectricityProduced | 178.15 | 0.00 | 01-JAN-00:10 | 34845.48 | 25-APR-12:20 |
PowerConversion:ElectricityProduced | -7.98 | -1382.63 | 25-APR-12:20 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 713.45 | 13692.81 | 09-NOV-05:00 | 41482.83 | 26-JUN-21:20 |
ExteriorEquipment:Electricity | 390.56 | 5777.98 | 02-JAN-02:20 | 23858.54 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.47 | 378.87 | 17-JUN-05:00 | 1270.25 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 4031.58 | 50304.44 | 25-APR-11:10 | 336874.67 | 26-JUL-19:40 |
ElectricityPurchased:Plant | 4031.58 | 50304.44 | 25-APR-11:10 | 336874.67 | 26-JUL-19:40 |
Cogeneration:ElectricityPurchased | 4031.58 | 50304.44 | 25-APR-11:10 | 336874.67 | 26-JUL-19:40 |
General:Cogeneration:ElectricityPurchased | 4031.58 | 50304.44 | 25-APR-11:10 | 336874.67 | 26-JUL-19:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4031.58 | 50304.44 | 25-APR-11:10 | 336874.67 | 26-JUL-19:40 |
ElectricityNet:Plant | 4031.58 | 50304.44 | 25-APR-11:10 | 336874.67 | 26-JUL-19:40 |
Cogeneration:ElectricityNet | 4031.58 | 50304.44 | 25-APR-11:10 | 336874.67 | 26-JUL-19:40 |
General:Cogeneration:ElectricityNet | 4031.58 | 50304.44 | 25-APR-11:10 | 336874.67 | 26-JUL-19:40 |
General:Fans:Electricity | 571.32 | 12698.84 | 30-OCT-03:00 | 32399.09 | 26-JUN-21:20 |
ExteriorLights:Electricity | 150.26 | 0.00 | 01-JAN-08:00 | 9571.94 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 150.26 | 0.00 | 01-JAN-08:00 | 9571.94 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 366.65 | 5383.28 | 01-JAN-00:10 | 22430.31 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.45 | 15.80 | 01-JAN-00:10 | 157.97 | 01-JAN-07:10 |
HeatRecovery:Electricity | 120.66 | 0.00 | 12-JAN-11:30 | 8265.52 | 25-JUN-09:00 |
General:HeatRecovery:Electricity | 120.66 | 0.00 | 12-JAN-11:30 | 8265.52 | 25-JUN-09:00 |
WaterSystems:Electricity | 90.74 | 1086.56 | 11-APR-01:30 | 4738.76 | 13-JUL-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 11-APR-01:30 | 4738.76 | 13-JUL-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 661.15 | 0.00 | 01-JAN-00:30 | 177783.01 | 04-AUG-15:30 |
General:Cooling:Electricity | 661.15 | 0.00 | 01-JAN-00:30 | 177783.01 | 04-AUG-15:30 |
Pumps:Electricity | 70.07 | 47.91 | 10-MAY-15:10 | 4038.20 | 26-JUL-18:20 |
General:Pumps:Electricity | 70.07 | 47.91 | 10-MAY-15:10 | 4038.20 | 26-JUL-18:20 |
WIRED_LTG_ELECTRICITY | 16.00 | 0.00 | 01-JAN-00:10 | 1324.60 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5908.70 | 26805.16 | 20-MAR-02:30 | 970590.16 | 02-FEB-19:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4119.86 | 13443.27 | 10-JUN-15:20 | 882970.38 | 02-FEB-19:20 |
WaterSystems:NaturalGas | 2846.55 | 13443.27 | 06-JAN-16:20 | 258530.71 | 23-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 2846.55 | 13443.27 | 06-JAN-16:20 | 258530.71 | 23-FEB-21:40 |
Heating:NaturalGas | 1273.32 | 0.00 | 01-JAN-08:20 | 712937.83 | 02-FEB-09:10 |
Boiler:Heating:NaturalGas | 1273.32 | 0.00 | 01-JAN-08:20 | 712937.83 | 02-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2154.38 | 0.00 | 01-JAN-00:30 | 587623.58 | 26-JUL-18:20 |
PlantLoopCoolingDemand:HVAC | 2154.38 | 0.00 | 01-JAN-00:30 | 587623.58 | 26-JUL-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 2154.38 | 0.00 | 01-JAN-00:30 | 587623.58 | 26-JUL-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-APR-20:30 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-APR-20:30 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-APR-20:30 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-APR-20:30 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-APR-20:30 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-APR-20:30 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 17332.70 | 125181.89 | 29-SEP-13:50 | 2440227.49 | 26-JUL-18:20 |
EnergyTransfer:Building | 4561.73 | 72495.00 | 06-FEB-11:10 | 311911.53 | 29-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 678.89 | 7572.07 | 01-FEB-04:00 | 34750.36 | 29-JUL-10:40 |
Refrigeration:EnergyTransfer | 183.32 | 4016.70 | 02-FEB-23:10 | 10366.97 | 12-SEP-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.66 | 2008.35 | 02-FEB-23:10 | 5183.48 | 12-SEP-06:20 |
General:Refrigeration:EnergyTransfer | 91.66 | 2008.35 | 02-FEB-23:10 | 5183.48 | 12-SEP-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.66 | 2008.35 | 02-FEB-23:10 | 5183.48 | 12-SEP-06:20 |
EnergyTransfer:Plant | 7178.74 | 12794.02 | 30-SEP-00:20 | 1375971.17 | 26-JUL-18:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.60 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.06 | 1849.34 | 02-FEB-04:10 | 2555.74 | 31-AUG-13:40 |
EnergyTransfer:Zone:BASEMENT | 334.10 | 5163.52 | 09-APR-15:00 | 14982.47 | 17-SEP-10:40 |
Heating:EnergyTransfer | 296.07 | 0.00 | 13-JAN-18:20 | 120528.02 | 12-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 296.07 | 0.00 | 13-JAN-18:20 | 120528.02 | 12-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4174.00 | 50206.64 | 03-FEB-11:10 | 308301.53 | 29-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 334.10 | 5163.52 | 09-APR-15:00 | 14982.47 | 17-SEP-10:40 |
General:Cooling:EnergyTransfer | 4174.00 | 50206.64 | 03-FEB-11:10 | 308301.53 | 29-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 334.10 | 5163.52 | 09-APR-15:00 | 14982.47 | 17-SEP-10:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 28.34 | 0.01 | 18-MAR-05:20 | 3525.45 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 4.62 | 0.00 | 01-JAN-10:30 | 2422.48 | 02-FEB-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 4.62 | 0.00 | 01-JAN-10:30 | 2422.48 | 02-FEB-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 23.72 | 0.00 | 01-JAN-00:10 | 3525.45 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 23.72 | 0.00 | 01-JAN-00:10 | 3525.45 | 07-SEP-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.51 | 0.61 | 25-JAN-10:10 | 1609.32 | 26-JUN-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 197.28 | 03-FEB-10:50 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 197.28 | 03-FEB-10:50 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.50 | 0.00 | 06-JAN-10:10 | 1609.32 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.50 | 0.00 | 06-JAN-10:10 | 1609.32 | 26-JUN-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 8.30 | 0.08 | 14-FEB-13:20 | 1472.21 | 03-FEB-05:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 2.40 | 0.00 | 01-JAN-00:10 | 1472.21 | 03-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 2.40 | 0.00 | 01-JAN-00:10 | 1472.21 | 03-FEB-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 5.90 | 0.00 | 01-JAN-04:10 | 1422.58 | 26-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 5.90 | 0.00 | 01-JAN-04:10 | 1422.58 | 26-JUN-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 14.91 | 0.02 | 13-NOV-01:10 | 1128.05 | 03-FEB-04:50 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.21 | 0.00 | 12-JAN-19:10 | 1128.05 | 03-FEB-04:50 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.21 | 0.00 | 12-JAN-19:10 | 1128.05 | 03-FEB-04:50 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.70 | 0.00 | 01-JAN-00:10 | 952.89 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.70 | 0.00 | 01-JAN-00:10 | 952.89 | 02-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 574.22 | 6568.31 | 04-FEB-06:00 | 39016.13 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 574.22 | 6568.31 | 04-FEB-06:00 | 39016.13 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 574.22 | 6568.31 | 04-FEB-06:00 | 39016.13 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 214.76 | 1.79 | 27-NOV-14:50 | 11749.72 | 09-SEP-10:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.24 | 0.00 | 01-JAN-00:10 | 2067.45 | 12-DEC-15:00 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.24 | 0.00 | 01-JAN-00:10 | 2067.45 | 12-DEC-15:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 214.52 | 0.00 | 06-JAN-07:10 | 11749.72 | 09-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 214.52 | 0.00 | 06-JAN-07:10 | 11749.72 | 09-SEP-10:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 716.26 | 1694.56 | 12-DEC-15:00 | 35037.72 | 07-SEP-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 716.26 | 1694.56 | 12-DEC-15:00 | 35037.72 | 07-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 716.26 | 1694.56 | 12-DEC-15:00 | 35037.72 | 07-SEP-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 57.94 | 0.00 | 01-JAN-08:00 | 9877.14 | 06-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 26.56 | 0.00 | 01-JAN-08:00 | 7863.56 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 26.56 | 0.00 | 01-JAN-08:00 | 7863.56 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 31.38 | 0.00 | 01-JAN-00:10 | 9877.14 | 06-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 31.38 | 0.00 | 01-JAN-00:10 | 9877.14 | 06-SEP-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 54.59 | 0.00 | 01-JAN-08:00 | 9810.42 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 31.36 | 0.00 | 01-JAN-08:00 | 8820.06 | 02-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 31.36 | 0.00 | 01-JAN-08:00 | 8820.06 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 23.23 | 0.00 | 01-JAN-00:10 | 9810.42 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 23.23 | 0.00 | 01-JAN-00:10 | 9810.42 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 189.64 | 0.00 | 01-JAN-07:20 | 40210.70 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 18.48 | 0.00 | 01-JAN-07:20 | 22881.94 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 18.48 | 0.00 | 01-JAN-07:20 | 22881.94 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 171.17 | 0.00 | 01-JAN-00:10 | 40210.70 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 171.17 | 0.00 | 01-JAN-00:10 | 40210.70 | 07-SEP-13:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 326.70 | 0.00 | 01-JAN-08:00 | 61824.65 | 29-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 82.93 | 0.00 | 01-JAN-08:00 | 55433.97 | 04-FEB-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 82.93 | 0.00 | 01-JAN-08:00 | 55433.97 | 04-FEB-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 0.00 | 01-JAN-00:10 | 61824.65 | 29-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 0.00 | 01-JAN-00:10 | 61824.65 | 29-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 57.23 | 0.00 | 01-JAN-08:00 | 8966.72 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 26.62 | 0.00 | 01-JAN-08:00 | 8024.60 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 26.62 | 0.00 | 01-JAN-08:00 | 8024.60 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 30.61 | 0.00 | 01-JAN-00:10 | 8966.72 | 02-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 30.61 | 0.00 | 01-JAN-00:10 | 8966.72 | 02-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 54.38 | 0.00 | 01-JAN-08:00 | 9853.73 | 01-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 31.48 | 0.00 | 01-JAN-08:00 | 8769.61 | 02-FEB-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 31.48 | 0.00 | 01-JAN-08:00 | 8769.61 | 02-FEB-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 22.89 | 0.00 | 01-JAN-00:10 | 9853.73 | 01-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 22.89 | 0.00 | 01-JAN-00:10 | 9853.73 | 01-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 133.05 | 0.42 | 19-NOV-17:10 | 8634.90 | 02-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 7.58 | 0.00 | 01-JAN-00:10 | 5985.55 | 02-FEB-07:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 7.58 | 0.00 | 01-JAN-00:10 | 5985.55 | 02-FEB-07:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 125.47 | 0.00 | 01-JAN-08:10 | 8634.90 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 125.47 | 0.00 | 01-JAN-08:10 | 8634.90 | 02-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.75 | 0.00 | 01-JAN-08:00 | 2744.39 | 04-AUG-15:30 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.86 | 0.00 | 01-JAN-08:00 | 2504.61 | 02-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.86 | 0.00 | 01-JAN-08:00 | 2504.61 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 7.88 | 0.00 | 01-JAN-00:10 | 2744.39 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 7.88 | 0.00 | 01-JAN-00:10 | 2744.39 | 04-AUG-15:30 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.33 | 0.00 | 01-JAN-08:00 | 2794.33 | 02-FEB-09:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.36 | 0.00 | 01-JAN-08:00 | 2794.33 | 02-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.36 | 0.00 | 01-JAN-08:00 | 2794.33 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.97 | 0.00 | 01-JAN-00:10 | 2684.98 | 05-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.97 | 0.00 | 01-JAN-00:10 | 2684.98 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.13 | 0.00 | 01-JAN-08:00 | 13877.07 | 07-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 28.33 | 0.00 | 01-JAN-08:00 | 11878.88 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 28.33 | 0.00 | 01-JAN-08:00 | 11878.88 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 48.80 | 0.00 | 01-JAN-00:10 | 13877.07 | 07-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 48.80 | 0.00 | 01-JAN-00:10 | 13877.07 | 07-SEP-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 447.16 | 3793.23 | 02-FEB-09:20 | 20423.50 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 447.16 | 3793.23 | 02-FEB-09:20 | 20423.50 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 447.16 | 3793.23 | 02-FEB-09:20 | 20423.50 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 472.98 | 5014.36 | 02-FEB-09:30 | 21787.32 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 472.98 | 5014.36 | 02-FEB-09:30 | 21787.32 | 26-JUN-22:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 472.98 | 5014.36 | 02-FEB-09:30 | 21787.32 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 587.23 | 5330.71 | 01-FEB-04:00 | 29668.70 | 29-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 587.23 | 5330.71 | 01-FEB-04:00 | 29668.70 | 29-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 55.57 | 0.05 | 16-MAR-09:40 | 5972.50 | 02-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 11.04 | 0.00 | 01-JAN-10:30 | 5972.50 | 02-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 11.04 | 0.00 | 01-JAN-10:30 | 5972.50 | 02-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 44.54 | 0.00 | 01-JAN-00:10 | 5800.41 | 07-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 44.54 | 0.00 | 01-JAN-00:10 | 5800.41 | 07-SEP-13:30 |
PlantLoopHeatingDemand:Facility | 2000.49 | 9887.90 | 22-AUG-01:50 | 688405.49 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 847.52 | 9887.90 | 22-AUG-01:50 | 63734.36 | 22-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 847.52 | 9887.90 | 22-AUG-01:50 | 63734.36 | 22-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 847.52 | 9887.90 | 22-AUG-01:50 | 63734.36 | 22-FEB-07:10 |
EnergyTransfer:HVAC | 5592.22 | 0.00 | 10-MAY-15:10 | 777780.64 | 26-JUL-18:20 |
HeatingCoils:EnergyTransfer | 1152.97 | 0.00 | 19-MAR-20:50 | 638570.66 | 02-FEB-09:10 |
PlantLoopHeatingDemand:HVAC | 1152.97 | 0.00 | 19-MAR-20:50 | 638570.66 | 02-FEB-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 1152.97 | 0.00 | 19-MAR-20:50 | 638570.66 | 02-FEB-09:10 |
CoolingCoils:EnergyTransfer | 2154.38 | 0.00 | 01-JAN-00:30 | 587623.58 | 26-JUL-18:20 |
HeatRecoveryForHeating:EnergyTransfer | 2145.36 | 0.00 | 05-JAN-08:00 | 407512.44 | 05-JAN-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 139.51 | 0.00 | 01-JAN-00:10 | 190157.06 | 26-JUL-18:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 847.52 | 9887.90 | 22-AUG-01:50 | 63734.36 | 22-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 847.52 | 9887.90 | 22-AUG-01:50 | 63734.36 | 22-FEB-07:10 |
Boilers:EnergyTransfer | 1150.64 | 0.00 | 01-JAN-08:20 | 631029.54 | 02-FEB-09:10 |
Chillers:EnergyTransfer | 2213.89 | 0.00 | 01-JAN-00:30 | 589843.75 | 26-JUL-18:20 |
HeatRejection:EnergyTransfer | 2875.04 | 0.00 | 01-JAN-00:30 | 750317.30 | 26-JUL-18:20 |
General:HeatRejection:EnergyTransfer | 2875.04 | 0.00 | 01-JAN-00:30 | 750317.30 | 26-JUL-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -334.096 | 0.000 | 0.000 | 146.648 | 92.464 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -48.121 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 4.625 | -23.718 | 0.000 | 0.000 | 15.321 | 4.184 | 10.186 | 18.281 | 0.000 | 0.076 | 0.000 | 0.000 | -9.970 | 0.000 | -6.188 | -12.796 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.013 | -30.498 | 0.000 | 0.000 | 17.740 | 4.846 | 11.795 | 0.000 | 0.000 | 0.045 | 0.000 | 0.000 | 0.000 | 0.000 | -2.379 | -1.563 |
MECH_FLR_1 | 0.000 | 0.000 | 2.400 | -5.900 | 0.000 | 0.000 | 3.578 | 8.670 | 12.471 | 0.000 | 0.000 | 0.068 | 0.000 | 0.000 | 0.000 | 0.000 | -5.886 | -15.402 |
STORAGE_FLR_1 | 0.000 | 0.000 | 3.207 | -11.704 | 0.000 | 0.000 | 2.989 | 1.987 | 3.598 | 0.000 | 0.000 | 0.075 | 3.000 | 0.000 | 0.000 | 0.000 | -3.151 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -574.224 | 0.000 | 0.000 | 10.551 | 3.699 | 658.131 | 0.000 | 0.000 | 0.093 | 0.000 | 0.000 | 0.000 | 0.000 | -8.623 | -89.628 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.235 | -214.526 | 0.000 | 0.000 | 203.299 | 6.523 | 14.341 | 52.025 | 0.000 | 0.289 | 0.000 | 0.000 | -27.477 | 0.000 | -13.512 | -21.198 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -716.261 | 0.000 | 0.000 | 580.837 | 78.454 | 148.998 | 67.822 | 0.000 | 0.720 | 0.000 | 0.000 | -37.951 | 0.000 | -39.873 | -82.747 |
ROOM_1_FLR_3 | 31.607 | -25.922 | 0.000 | -10.506 | 0.000 | 0.000 | 9.753 | 4.922 | 10.478 | 34.747 | 0.000 | 0.385 | 0.000 | 0.000 | -22.680 | 0.000 | -14.491 | -18.295 |
ROOM_2_FLR_3 | 36.646 | -17.616 | 0.000 | -10.904 | 0.000 | 0.000 | 9.654 | 4.922 | 10.477 | 24.547 | 0.000 | 0.295 | 0.000 | 0.000 | -24.029 | 0.000 | -14.861 | -19.131 |
ROOM_3_MULT19_FLR_3 | 18.469 | -159.615 | 0.011 | -11.553 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 209.800 | 0.000 | 0.286 | 0.000 | 0.000 | -132.663 | 0.000 | -81.682 | -96.827 |
ROOM_4_MULT19_FLR_3 | 134.073 | -148.797 | 0.000 | -146.104 | 0.000 | 0.000 | 183.738 | 58.793 | 195.050 | 61.811 | 0.000 | 1.893 | 0.000 | 0.000 | -136.196 | 0.000 | -89.748 | -114.512 |
ROOM_5_FLR_3 | 31.632 | -25.107 | 0.000 | -10.513 | 0.000 | 0.000 | 9.748 | 4.922 | 10.478 | 33.860 | 0.000 | 0.386 | 0.000 | 0.000 | -22.327 | 0.000 | -14.524 | -18.554 |
ROOM_6_FLR_3 | 36.787 | -17.323 | 0.000 | -10.870 | 0.000 | 0.000 | 9.672 | 4.922 | 10.477 | 23.535 | 0.000 | 0.294 | 0.000 | 0.000 | -23.516 | 0.000 | -14.860 | -19.118 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 7.580 | -125.468 | 0.000 | 0.000 | 120.566 | 54.592 | 0.000 | 30.854 | 0.000 | 0.306 | 0.000 | 0.000 | -28.916 | 0.000 | -17.105 | -42.407 |
ROOM_1_FLR_6 | 11.220 | -6.620 | 0.000 | -2.624 | 0.000 | 0.000 | 2.442 | 1.231 | 2.620 | 8.653 | 0.000 | 0.099 | 0.000 | 0.000 | -5.627 | 0.000 | -3.655 | -7.738 |
ROOM_2_FLR_6 | 12.755 | -4.634 | 0.000 | -2.733 | 0.000 | 0.000 | 2.413 | 1.230 | 2.619 | 6.109 | 0.000 | 0.073 | 0.000 | 0.000 | -5.974 | 0.000 | -3.748 | -8.111 |
ROOM_3_MULT9_FLR_6 | 35.324 | -38.800 | 0.000 | -16.989 | 0.000 | 0.000 | 21.868 | 6.962 | 23.098 | 47.552 | 0.000 | 0.558 | 0.000 | 0.000 | -26.075 | 0.000 | -17.920 | -35.578 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -447.160 | 0.000 | 0.000 | 343.801 | 14.425 | 175.857 | 7.178 | 0.000 | 0.176 | 0.000 | 0.000 | -15.876 | 0.000 | -8.985 | -69.417 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -472.986 | 0.000 | 0.000 | 337.958 | 14.425 | 175.857 | 6.990 | 0.000 | 0.161 | 0.000 | 0.000 | -16.349 | 0.000 | -9.125 | -36.933 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -587.222 | 0.000 | 0.000 | 27.951 | 9.139 | 540.650 | 19.395 | 0.000 | 0.092 | 8.194 | 0.000 | -9.374 | 0.000 | -8.826 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 11.037 | -44.536 | 0.000 | 0.000 | 30.812 | 14.444 | 0.000 | 14.963 | 0.000 | 0.090 | 0.000 | 0.000 | -13.162 | 0.000 | -7.840 | -5.808 |
Total Facility | 348.512 | -444.435 | 29.109 | -3811.097 | 0.000 | 0.000 | 2091.341 | 454.534 | 2355.282 | 668.121 | 0.000 | 6.462 | 11.195 | 0.000 | -558.161 | 0.000 | -386.980 | -763.884 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-SEP-10:35 | 0.00 | 0.00 | 0.00 | -15032.34 | 0.00 | 0.00 | 2347.43 | 2520.47 | 4055.80 | 0.00 | 0.00 | 0.00 | 6108.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | -3524.74 | 0.00 | 0.00 | 150.60 | 95.05 | 252.59 | 4145.37 | 0.00 | 84.39 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1203.26 |
RETAIL_2_FLR_1 | 26-JUN-18:10 | 0.00 | 0.00 | 0.00 | -1624.35 | 0.00 | 0.00 | 651.60 | 352.23 | 752.15 | 0.00 | 0.00 | 27.77 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -159.41 |
MECH_FLR_1 | 26-JUN-21:00 | 0.00 | 0.00 | 0.00 | -1422.64 | 0.00 | 0.00 | 147.52 | 630.21 | 795.27 | 0.00 | 0.00 | 16.39 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -166.75 |
STORAGE_FLR_1 | 02-JUL-10:35 | 0.00 | 0.00 | 0.00 | -955.74 | 0.00 | 0.00 | 47.34 | 54.17 | 101.96 | 0.00 | 0.00 | 32.29 | 719.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39017.47 | 0.00 | 0.00 | 408.87 | 302.47 | 44299.38 | 0.00 | 0.00 | 37.66 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6030.91 |
CAFE_FLR_1 | 09-SEP-10:35 | 0.00 | 0.00 | 0.00 | -11858.94 | 0.00 | 0.00 | 3141.77 | 49.52 | 355.63 | 10259.39 | 0.00 | 63.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2011.11 |
LOBBY_FLR_1 | 07-SEP-21:10 | 0.00 | 0.00 | 0.00 | -35037.55 | 0.00 | 0.00 | 26440.22 | 4544.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -422.14 | 0.00 | -111.87 | -2803.47 |
ROOM_1_FLR_3 | 21-MAY-18:01 | 0.00 | -12581.43 | 0.00 | -555.18 | 0.00 | 0.00 | 283.20 | 378.87 | 484.65 | 4886.10 | 0.00 | 0.00 | 7800.62 | 0.00 | -0.00 | 0.00 | -696.83 | 0.00 |
ROOM_2_FLR_3 | 20-MAY-18:41 | 0.00 | -13426.38 | 0.00 | -608.31 | 0.00 | 0.00 | 257.59 | 378.82 | 484.60 | 2133.08 | 0.00 | 0.00 | 11059.14 | 0.00 | -0.00 | 0.00 | -278.54 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-SEP-13:00 | 0.00 | -40208.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 49410.12 | 0.00 | 672.91 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13494.16 |
ROOM_4_MULT19_FLR_3 | 06-MAY-19:31 | 0.00 | -70790.08 | 0.00 | -7118.84 | 0.00 | 0.00 | 5451.81 | 4525.19 | 12159.85 | 0.00 | 0.00 | 0.00 | 61034.80 | 0.00 | -3883.47 | 0.00 | -1379.26 | 0.00 |
ROOM_5_FLR_3 | 26-APR-08:61 | 0.00 | -11398.61 | 0.00 | -500.75 | 0.00 | 0.00 | 87.14 | 166.70 | 453.05 | 7454.99 | 0.00 | 0.00 | 4304.84 | 0.00 | -0.00 | 0.00 | -567.36 | 0.00 |
ROOM_6_FLR_3 | 09-AUG-08:51 | 0.00 | -11471.02 | 0.00 | -899.04 | 0.00 | 0.00 | 72.67 | 166.68 | 452.99 | 7007.90 | 0.00 | 0.00 | 4720.41 | 0.00 | -0.00 | 0.00 | -50.60 | 0.00 |
CORRIDOR_FLR_3 | 02-JUL-10:35 | 0.00 | 0.00 | 0.00 | -8648.38 | 0.00 | 0.00 | 1843.78 | 1488.15 | 0.00 | 4209.77 | 0.00 | 141.91 | 964.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 21-MAY-18:01 | 0.00 | -3274.03 | 0.00 | -139.12 | 0.00 | 0.00 | 70.80 | 94.72 | 121.16 | 1213.47 | 0.00 | 0.00 | 2102.59 | 0.00 | -0.00 | 0.00 | -189.59 | 0.00 |
ROOM_2_FLR_6 | 21-MAY-19:41 | 0.00 | -3626.07 | 0.00 | -164.94 | 0.00 | 0.00 | 61.11 | 94.71 | 163.29 | 0.00 | 0.00 | 0.00 | 3798.04 | 0.00 | -245.16 | 0.00 | -80.98 | 0.00 |
ROOM_3_MULT9_FLR_6 | 23-OCT-15:11 | 0.00 | -15780.34 | 0.00 | -826.14 | 0.00 | 0.00 | 529.39 | 150.05 | 441.28 | 5628.04 | 0.00 | 0.00 | 10338.47 | 0.00 | -0.00 | 0.00 | -480.75 | 0.00 |
BANQUET_FLR_6 | 27-JUN-21:05 | 0.00 | 0.00 | 0.00 | -21007.31 | 0.00 | 0.00 | 15835.96 | 948.68 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19.76 | 0.00 | -7.73 | -2497.74 |
DINING_FLR_6 | 26-JUN-22:00 | 0.00 | 0.00 | 0.00 | -21787.08 | 0.00 | 0.00 | 15644.49 | 948.68 | 6747.90 | 0.00 | 0.00 | 4.82 | 0.00 | 0.00 | -14.21 | 0.00 | 0.00 | -1544.59 |
KITCHEN_FLR_6 | 29-JUL-10:35 | 0.00 | 0.00 | 0.00 | -29667.66 | 0.00 | 0.00 | 464.20 | 207.61 | 23951.61 | 3129.48 | 0.00 | 26.08 | 1888.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-SEP-13:30 | 0.00 | 0.00 | 0.00 | -5799.74 | 0.00 | 0.00 | 308.46 | 328.12 | 0.00 | 3331.33 | 0.00 | 106.74 | 1725.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-18:02 | 0.00 | -144614.57 | 0.00 | -192620.08 | 0.00 | 0.00 | 79309.62 | 31039.82 | 120174.13 | 46169.28 | 0.00 | 3849.17 | 56692.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 02-FEB-07:30 | 0.00 | 0.00 | 2422.14 | 0.00 | 0.00 | 0.00 | 357.99 | 190.11 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1571.98 | 0.00 | -824.18 | -1007.10 |
RETAIL_2_FLR_1 | 03-FEB-10:53 | 0.00 | 0.00 | 203.73 | 0.00 | 0.00 | 0.00 | 207.29 | 110.07 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -270.11 | -543.49 |
MECH_FLR_1 | 03-FEB-05:00 | 0.00 | 0.00 | 1472.21 | 0.00 | 0.00 | 0.00 | 197.28 | 78.78 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -707.01 | -1217.98 |
STORAGE_FLR_1 | 02-FEB-09:03 | 0.00 | 0.00 | 1133.27 | 0.00 | 0.00 | 0.00 | 33.72 | 72.23 | 127.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -420.42 | -946.25 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 19-JAN-09:03 | 0.00 | 0.00 | 2078.21 | 0.00 | 0.00 | 0.00 | 2351.85 | 79.23 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -663.81 | 0.00 | -1474.29 | -2879.23 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 11-DEC-16:11 | 12023.21 | 289.50 | 0.00 | -289.50 | 0.00 | 0.00 | 293.99 | 106.08 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2488.01 | 0.00 | -1226.83 | -8908.63 |
ROOM_2_FLR_3 | 11-DEC-16:11 | 11939.02 | 287.43 | 0.00 | -287.43 | 0.00 | 0.00 | 293.99 | 106.07 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2483.84 | 0.00 | -1225.86 | -8829.54 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:10 | 22881.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.27 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15455.63 | 0.00 | -7114.85 | -4639.48 |
ROOM_4_MULT19_FLR_3 | 04-FEB-16:11 | 66617.28 | 3639.54 | 0.00 | -3639.54 | 0.00 | 0.00 | 3103.16 | 1493.31 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11655.25 | 0.00 | -6342.50 | -57334.67 |
ROOM_5_FLR_3 | 11-DEC-16:11 | 11592.20 | 287.72 | 0.00 | -287.72 | 0.00 | 0.00 | 293.99 | 106.08 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2494.48 | 0.00 | -1226.06 | -8471.91 |
ROOM_6_FLR_3 | 19-JAN-16:11 | 11507.84 | 285.22 | 0.00 | -285.22 | 0.00 | 0.00 | 293.99 | 106.07 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2477.17 | 0.00 | -1315.76 | -8315.13 |
CORRIDOR_FLR_3 | 02-FEB-07:20 | 0.00 | 0.00 | 5984.98 | 0.00 | 0.00 | 0.00 | 2771.55 | 2480.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4572.76 | 0.00 | -2315.56 | -4348.46 |
ROOM_1_FLR_6 | 11-DEC-16:11 | 3480.20 | 72.53 | 0.00 | -72.53 | 0.00 | 0.00 | 73.50 | 26.52 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -619.10 | 0.00 | -307.30 | -2703.86 |
ROOM_2_FLR_6 | 11-DEC-16:11 | 3448.65 | 71.94 | 0.00 | -71.94 | 0.00 | 0.00 | 73.50 | 26.52 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -619.04 | 0.00 | -307.03 | -2672.64 |
ROOM_3_MULT9_FLR_6 | 11-DEC-16:11 | 16525.43 | 464.03 | 0.00 | -464.03 | 0.00 | 0.00 | 661.48 | 150.05 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2892.51 | 0.00 | -1414.33 | -13471.40 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 02-FEB-07:10 | 0.00 | 0.00 | 5971.99 | 0.00 | 0.00 | 0.00 | 733.30 | 656.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2022.81 | 0.00 | -1025.58 | -4313.14 |
Total Facility | 12-DEC-16:12 | 78519.27 | 79271.41 | 10916.41 | -79271.41 | 0.00 | 0.00 | 62149.97 | 10421.93 | 73604.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50931.65 | 0.00 | -26690.96 | -157989.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.0992 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.9931 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.0748 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5316 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.003540 | 12.5400 | 0.000610 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.003540 | 142.3000 | 0.000914 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.000963 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1845 | 2.1845 | 1.2823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3280 | 0.3280 | 0.1187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2086 | 0.2086 | 0.1377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2067 | 0.2067 | 0.0021 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0964 | 0.0964 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4067 | 3.4067 | 0.0341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4702 | 1.4702 | 1.0144 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6757 | 4.6757 | 2.8428 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1846 | 1.1846 | 0.7120 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1482 | 2.1482 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2581 | 2.2581 | 1.7816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2643 | 2.2643 | 0.5502 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6672 | 0.6672 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.0992 | 20.9931 | 21.0992 | 10.5316 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2823 | 1.2823 | 1.2823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1640 | 0.1640 | 0.1187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1377 | 0.1377 | 0.1377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1034 | 0.1034 | 0.0021 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7033 | 1.7033 | 0.0341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0144 | 1.0144 | 1.0144 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8428 | 2.8428 | 2.8428 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7120 | 0.7120 | 0.7120 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7808 | 1.7808 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7816 | 1.7816 | 1.7816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1321 | 1.1321 | 0.5502 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3336 | 0.3336 | 0.1882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.0748 | 10.5316 | 10.5316 | 10.5316 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 3.67 |
Number of hours cooling loads not met | 44.33 |
Number of hours not met | 48.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1273.32 | 712937.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 661.15 | 177783.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 454.53 | 37630.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 150.26 | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.47 | 1270.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 366.65 | 22430.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.45 | 157.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 571.32 | 32399.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 70.07 | 4038.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 120.66 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.76 | 2846.55 | 258530.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.83 | 1306.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.07 | 716.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.45 | 4201.75 |
Natural Gas | 1788.84 | 5908.70 |
Additional | 0.00 | 0.00 |
Total | 3481.29 | 10110.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 178.15 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 40.06 |
Space Heating | 0.00 |
Space Cooling | 58.27 |
Fans (All) | 50.36 |
Service Water Heating | 8.00 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 370.35 |
Subtotal | 370.35 |
Natural Gas [MJ/m2] | |
Space Heating | 112.23 |
Service Water Heating | 250.90 |
Miscellaneous (All) | 520.81 |
Subtotal | 520.81 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.50 |
Space Heating | 12.59 |
Space Cooling | 6.54 |
Fans (All) | 5.65 |
Service Water Heating | 29.05 |
Receptacle Equipment | 34.00 |
Miscellaneous | 7.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_KITCHEN | 2022. | 8760. |
LTG_SCH_DINING | 1877. | 8760. |
LTG_SCH_BASEMENT | 2095. | 8760. |
LTG_SCH_LOBBY | 2166. | 8760. |
LTG_SCH_STORAGE | 1543. | 8760. |
LTG_SCH_MECHANIC | 2022. | 8760. |
LTG_SCH_LAUNDRY | 2527. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2166. | 8760. |
LTG_SCH_RETAIL | 2296. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8091.67 | 668.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8707.83 | 52.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8091.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 668.33 | 0.00 | 0.00 | 0.00 |
Average | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
Sum | 191957.33 | 762.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4148.67 | 5.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4135.17 | 18.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 18.83 | 0.00 | 0.00 | 0.00 |
Average | 288885.95 | 1.10 | 0.00 | 0.00 | 0.00 |
Sum | 6355490.83 | 24.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8719.00 | 41.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8351.17 | 408.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8614.17 | 145.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7692.50 | 1067.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8716.50 | 43.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8629.50 | 130.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8547.67 | 212.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8384.33 | 375.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8326.33 | 433.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8725.67 | 34.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8618.17 | 141.83 | 0.00 | 0.00 | 0.00 |
Min | 7692.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1067.50 | 0.00 | 0.00 | 0.00 |
Average | 8620.36 | 139.64 | 0.00 | 0.00 | 0.00 |
Sum | 189647.83 | 3072.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 49980.33 | 198.67 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 705169.00 | 5248.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1963346.00 | 152083.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4103.33 | 50.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4144.50 | 9.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4137.33 | 16.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4060.00 | 94.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1162469.83 | 83245.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1151315.33 | 94399.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108027.50 | 241.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 103382.17 | 2563.83 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1963346.00 | 152083.00 | 0.00 | 0.00 | 0.00 |
Average | 273516.56 | 15370.48 | 0.00 | 0.00 | 0.00 |
Sum | 6017364.33 | 338150.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:32
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274781E+11 | 12249.76 | 13-JAN-21:00 | -0.6 | -1.3 | 0.714757E+10 | 4436.64 | 06-JAN-22:10 | -0.6 | -1.3 |
February | 0.234378E+11 | 14448.11 | 02-FEB-07:00 | -36.7 | -36.8 | 0.612890E+10 | 4321.13 | 01-FEB-22:10 | -36.7 | -36.8 |
March | 0.238578E+11 | 11031.47 | 01-MAR-21:00 | -4.4 | -5.1 | 0.648040E+10 | 4135.23 | 01-MAR-22:10 | -4.4 | -5.1 |
April | 0.214986E+11 | 11355.52 | 15-APR-18:10 | 27.85 | 18.48 | 0.611615E+10 | 3918.04 | 20-APR-22:10 | 7.20 | 2.93 |
May | 0.243955E+11 | 12007.36 | 31-MAY-18:10 | 27.02 | 19.01 | 0.641378E+10 | 3976.18 | 19-MAY-22:10 | 27.02 | 19.01 |
June | 0.264543E+11 | 13083.58 | 25-JUN-10:35 | 28.87 | 21.94 | 0.654028E+10 | 4204.95 | 15-JUN-22:10 | 28.87 | 21.94 |
July | 0.295341E+11 | 13877.41 | 30-JUL-10:35 | 24.63 | 19.89 | 0.707893E+10 | 4412.68 | 21-JUL-22:10 | 24.63 | 19.89 |
August | 0.316651E+11 | 14509.32 | 27-AUG-10:35 | 25.53 | 19.86 | 0.752782E+10 | 4662.95 | 25-AUG-22:10 | 25.53 | 19.86 |
September | 0.318108E+11 | 15031.78 | 17-SEP-10:35 | 25.20 | 17.72 | 0.756773E+10 | 4836.99 | 22-SEP-22:10 | 7.43 | 5.43 |
October | 0.327451E+11 | 14604.75 | 25-OCT-21:00 | 4.40 | 1.66 | 0.794166E+10 | 4837.03 | 16-OCT-21:19 | 4.40 | 1.66 |
November | 0.309917E+11 | 14462.29 | 01-NOV-21:00 | 6.70 | 5.15 | 0.764018E+10 | 4837.04 | 16-NOV-22:19 | -0.4 | -1.4 |
December | 0.302265E+11 | 13460.91 | 01-DEC-21:00 | -5.0 | -5.8 | 0.762964E+10 | 4793.68 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.334096E+12 | 0.842130E+11 | ||||||||
Minimum of Months | 0.214986E+11 | 11031.47 | -36.7 | -36.8 | 0.611615E+10 | 3918.04 | -36.7 | -36.8 | ||
Maximum of Months | 0.327451E+11 | 15031.78 | 28.87 | 21.94 | 0.794166E+10 | 4837.04 | 28.87 | 21.94 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304038E+09 | 1167.92 | 13-JAN-11:50 | 3.62 | 1.34 | 0.621869E+09 | 366.14 | 13-JAN-22:30 | 1.65 | 0.58 |
February | 0.586853E+09 | 1812.62 | 08-FEB-13:30 | 2.50 | 1.29 | 0.565712E+09 | 391.84 | 24-FEB-22:19 | 1.67 | 1.15 |
March | 0.114078E+10 | 1624.94 | 24-MAR-13:20 | 12.57 | 6.49 | 0.639121E+09 | 421.34 | 23-MAR-21:30 | 12.57 | 6.49 |
April | 0.183564E+10 | 2749.95 | 15-APR-13:30 | 28.85 | 20.45 | 0.650776E+09 | 491.81 | 18-APR-21:30 | 15.55 | 12.91 |
May | 0.272099E+10 | 2172.57 | 31-MAY-13:30 | 29.70 | 19.57 | 0.711518E+09 | 491.84 | 30-MAY-22:10 | 29.70 | 19.57 |
June | 0.317770E+10 | 2530.64 | 30-JUN-13:00 | 29.40 | 21.96 | 0.745118E+09 | 491.84 | 20-JUN-22:10 | 29.40 | 21.96 |
July | 0.357275E+10 | 2634.61 | 30-JUL-12:00 | 26.70 | 21.51 | 0.798445E+09 | 491.84 | 07-JUL-22:10 | 26.70 | 21.51 |
August | 0.359000E+10 | 2780.02 | 04-AUG-14:10 | 33.40 | 25.74 | 0.798688E+09 | 491.84 | 11-AUG-22:10 | 17.12 | 15.39 |
September | 0.315690E+10 | 3525.45 | 07-SEP-13:00 | 31.70 | 18.06 | 0.719129E+09 | 491.84 | 07-SEP-22:10 | 20.32 | 16.01 |
October | 0.221452E+10 | 2907.33 | 20-OCT-13:00 | 21.80 | 12.61 | 0.666613E+09 | 475.37 | 20-OCT-21:30 | 13.90 | 9.49 |
November | 0.100831E+10 | 2691.96 | 04-NOV-13:00 | 13.90 | 6.81 | 0.612367E+09 | 424.22 | 03-NOV-21:19 | 13.90 | 6.81 |
December | 0.409607E+09 | 1861.27 | 03-DEC-13:00 | 5.60 | 2.41 | 0.624088E+09 | 364.12 | 12-DEC-04:19 | -20.0 | -20.3 |
Annual Sum or Average | 0.237181E+11 | 0.815344E+10 | ||||||||
Minimum of Months | 0.304038E+09 | 1167.92 | 2.50 | 1.29 | 0.565712E+09 | 364.12 | -20.0 | -20.3 | ||
Maximum of Months | 0.359000E+10 | 3525.45 | 33.40 | 25.74 | 0.798688E+09 | 491.84 | 29.70 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139534E+10 | 1124.37 | 13-JAN-21:00 | -0.6 | -1.3 | 0.722023E+09 | 470.92 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.159408E+10 | 1184.80 | 24-FEB-21:00 | 2.20 | 1.50 | 0.662359E+09 | 484.02 | 24-FEB-23:10 | 0.60 | 0.07 |
March | 0.223538E+10 | 1260.36 | 24-MAR-20:00 | 3.90 | 2.01 | 0.753931E+09 | 501.57 | 24-MAR-21:49 | 0.97 | -0.3 |
April | 0.256720E+10 | 1484.74 | 16-APR-10:35 | 23.33 | 18.86 | 0.763472E+09 | 554.52 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.302350E+10 | 1559.85 | 31-MAY-18:10 | 27.02 | 19.01 | 0.829333E+09 | 564.38 | 31-MAY-22:10 | 19.42 | 14.32 |
June | 0.319354E+10 | 1624.33 | 26-JUN-18:10 | 29.72 | 22.36 | 0.844610E+09 | 569.55 | 30-JUN-22:10 | 21.02 | 16.54 |
July | 0.343705E+10 | 1621.28 | 03-JUL-18:10 | 29.22 | 24.10 | 0.891791E+09 | 569.55 | 05-JUL-22:10 | 20.60 | 19.73 |
August | 0.340965E+10 | 1587.76 | 03-AUG-18:10 | 29.03 | 24.34 | 0.895039E+09 | 569.55 | 22-AUG-22:10 | 21.10 | 19.85 |
September | 0.308088E+10 | 1604.61 | 07-SEP-18:10 | 28.95 | 19.12 | 0.830246E+09 | 569.55 | 06-SEP-22:10 | 28.95 | 19.12 |
October | 0.275455E+10 | 1377.08 | 20-OCT-20:00 | 15.00 | 9.90 | 0.794626E+09 | 534.86 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.212348E+10 | 1300.61 | 03-NOV-20:00 | 7.80 | 4.59 | 0.729650E+09 | 512.86 | 03-NOV-22:10 | 4.82 | 2.56 |
December | 0.168299E+10 | 1096.64 | 01-DEC-21:00 | -5.0 | -5.8 | 0.726347E+09 | 464.24 | 01-DEC-23:10 | -3.3 | -4.2 |
Annual Sum or Average | 0.304976E+11 | 0.944343E+10 | ||||||||
Minimum of Months | 0.139534E+10 | 1096.64 | -5.0 | -5.8 | 0.662359E+09 | 464.24 | -3.3 | -4.2 | ||
Maximum of Months | 0.343705E+10 | 1624.33 | 29.72 | 24.34 | 0.895039E+09 | 569.55 | 28.95 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8112934.48 | 18.27 | 13-JAN-21:00 | -0.6 | -1.3 | 0.153198E+09 | 103.42 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 20044535.53 | 19.51 | 24-FEB-21:00 | 2.20 | 1.50 | 0.142700E+09 | 107.61 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 34310263.17 | 22.24 | 28-MAR-20:00 | 11.70 | 8.27 | 0.168867E+09 | 118.83 | 29-MAR-21:10 | 7.70 | 7.14 |
April | 0.181028E+09 | 951.10 | 18-APR-20:00 | 18.30 | 15.20 | 0.179386E+09 | 120.45 | 18-APR-04:00 | 18.30 | 15.20 |
May | 0.455687E+09 | 1174.75 | 31-MAY-21:00 | 22.20 | 17.24 | 0.202955E+09 | 120.45 | 31-MAY-21:19 | 21.40 | 16.40 |
June | 0.117312E+10 | 1422.58 | 26-JUN-21:00 | 25.60 | 21.31 | 0.198573E+09 | 120.46 | 19-JUN-21:10 | 25.60 | 21.31 |
July | 0.153181E+10 | 1372.09 | 03-JUL-21:00 | 24.40 | 22.86 | 0.205008E+09 | 120.45 | 27-JUL-21:30 | 20.55 | 17.79 |
August | 0.147007E+10 | 1368.61 | 04-AUG-20:00 | 18.90 | 18.12 | 0.205875E+09 | 120.45 | 11-AUG-21:30 | 18.05 | 15.93 |
September | 0.867406E+09 | 1287.89 | 07-SEP-20:00 | 23.90 | 17.04 | 0.196862E+09 | 120.46 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 91887088.97 | 463.89 | 11-OCT-20:00 | 12.60 | 7.23 | 0.193543E+09 | 120.45 | 20-OCT-23:00 | 13.90 | 9.77 |
November | 51544876.75 | 400.61 | 08-NOV-22:00 | 14.40 | 12.79 | 0.168575E+09 | 120.45 | 02-NOV-22:10 | 14.40 | 12.79 |
December | 15219958.25 | 18.01 | 04-DEC-21:00 | 1.70 | 0.04 | 0.154848E+09 | 102.75 | 04-DEC-22:10 | 1.78 | 0.09 |
Annual Sum or Average | 0.590025E+10 | 0.217039E+10 | ||||||||
Minimum of Months | 8112934.48 | 18.01 | -0.6 | -1.3 | 0.142700E+09 | 102.75 | 1.78 | 0.09 | ||
Maximum of Months | 0.153181E+10 | 1422.58 | 25.60 | 22.86 | 0.205875E+09 | 120.46 | 25.60 | 21.31 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5517360.68 | 224.94 | 13-JAN-22:00 | 2.20 | 0.77 | 0.116689E+09 | 68.58 | 07-JAN-03:00 | 2.20 | 0.77 |
February | 41594244.89 | 331.94 | 24-FEB-22:00 | 2.20 | 1.69 | 0.105500E+09 | 68.58 | 01-FEB-00:10 | 2.20 | 1.69 |
March | 0.330150E+09 | 617.59 | 28-MAR-21:00 | 10.00 | 7.70 | 0.117243E+09 | 69.16 | 28-MAR-22:10 | 8.80 | 7.21 |
April | 0.833786E+09 | 865.09 | 16-APR-10:35 | 23.33 | 18.86 | 0.114709E+09 | 77.09 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.160608E+10 | 895.36 | 31-MAY-10:35 | 27.93 | 19.39 | 0.121488E+09 | 79.60 | 31-MAY-22:10 | 19.42 | 14.32 |
June | 0.178352E+10 | 946.20 | 30-JUN-10:35 | 27.93 | 22.99 | 0.124859E+09 | 83.08 | 30-JUN-22:10 | 21.02 | 16.54 |
July | 0.193443E+10 | 955.67 | 02-JUL-10:35 | 27.77 | 21.90 | 0.131804E+09 | 82.60 | 03-JUL-22:10 | 23.12 | 22.36 |
August | 0.190840E+10 | 934.02 | 04-AUG-10:35 | 29.27 | 25.47 | 0.131770E+09 | 82.46 | 03-AUG-22:10 | 29.27 | 25.47 |
September | 0.164474E+10 | 926.51 | 08-SEP-10:35 | 28.33 | 18.78 | 0.121754E+09 | 81.19 | 11-SEP-22:10 | 19.60 | 18.05 |
October | 0.113929E+10 | 719.74 | 21-OCT-10:35 | 17.17 | 11.84 | 0.117362E+09 | 72.66 | 20-OCT-22:10 | 17.17 | 11.84 |
November | 0.466951E+09 | 669.32 | 03-NOV-20:00 | 7.80 | 4.59 | 0.113099E+09 | 71.51 | 08-NOV-23:10 | 14.40 | 12.79 |
December | 9886561.53 | 174.30 | 04-DEC-22:00 | 1.70 | 0.04 | 0.116689E+09 | 68.57 | 05-DEC-03:20 | 2.40 | 0.08 |
Annual Sum or Average | 0.117044E+11 | 0.143297E+10 | ||||||||
Minimum of Months | 5517360.68 | 174.30 | 1.70 | 0.04 | 0.105500E+09 | 68.57 | 2.20 | 0.08 | ||
Maximum of Months | 0.193443E+10 | 955.67 | 29.27 | 25.47 | 0.131804E+09 | 83.08 | 29.27 | 25.47 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449164E+11 | 36741.42 | 13-JAN-21:00 | -0.6 | -1.3 | 0.649339E+09 | 381.57 | 12-JAN-22:00 | -0.6 | -1.3 |
February | 0.414148E+11 | 37074.51 | 24-FEB-21:00 | 2.20 | 1.50 | 0.587075E+09 | 381.57 | 24-FEB-00:40 | 2.20 | 1.50 |
March | 0.475263E+11 | 37554.05 | 28-MAR-20:00 | 11.70 | 8.27 | 0.652391E+09 | 381.57 | 13-MAR-23:10 | 11.70 | 8.27 |
April | 0.471638E+11 | 38480.61 | 18-APR-20:00 | 18.30 | 15.20 | 0.629498E+09 | 381.58 | 18-APR-04:00 | 18.30 | 15.20 |
May | 0.504507E+11 | 38810.07 | 31-MAY-20:00 | 24.40 | 17.91 | 0.650706E+09 | 381.59 | 31-MAY-21:19 | 21.40 | 16.40 |
June | 0.498447E+11 | 39016.13 | 26-JUN-20:00 | 26.70 | 21.52 | 0.630869E+09 | 381.65 | 01-JUN-00:40 | 26.70 | 21.52 |
July | 0.517459E+11 | 38865.55 | 03-JUL-20:00 | 26.70 | 23.80 | 0.649333E+09 | 381.67 | 26-JUL-21:19 | 25.20 | 22.95 |
August | 0.517978E+11 | 38885.55 | 03-AUG-20:00 | 25.00 | 23.44 | 0.652079E+09 | 381.65 | 02-AUG-21:19 | 25.00 | 23.44 |
September | 0.490381E+11 | 38912.18 | 07-SEP-20:00 | 23.90 | 17.04 | 0.629192E+09 | 381.65 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.489305E+11 | 37992.04 | 20-OCT-20:00 | 15.00 | 9.90 | 0.649644E+09 | 381.60 | 31-OCT-21:10 | -0.9 | -2.7 |
November | 0.457951E+11 | 37618.12 | 03-NOV-20:00 | 7.80 | 4.59 | 0.628128E+09 | 381.57 | 16-NOV-05:40 | 0.20 | -0.8 |
December | 0.455966E+11 | 36509.33 | 04-DEC-21:00 | 1.70 | 0.04 | 0.649342E+09 | 381.55 | 11-DEC-00:30 | -21.7 | -22.1 |
Annual Sum or Average | 0.574221E+12 | 0.765760E+10 | ||||||||
Minimum of Months | 0.414148E+11 | 36509.33 | -0.6 | -1.3 | 0.587075E+09 | 381.55 | -21.7 | -22.1 | ||
Maximum of Months | 0.517978E+11 | 39016.13 | 26.70 | 23.80 | 0.652391E+09 | 381.67 | 26.70 | 23.44 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110310E+11 | 8536.42 | 13-JAN-11:35 | 3.33 | 1.18 | 0.820643E+10 | 5394.00 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.122946E+11 | 9626.20 | 08-FEB-11:40 | 2.40 | 1.36 | 0.754761E+10 | 5544.50 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.161451E+11 | 9347.43 | 19-MAR-10:35 | 13.87 | 10.01 | 0.856853E+10 | 5723.78 | 23-MAR-21:40 | 9.07 | 5.85 |
April | 0.177904E+11 | 10936.87 | 16-APR-10:35 | 23.33 | 18.86 | 0.859403E+10 | 6129.00 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.208916E+11 | 10677.19 | 31-MAY-18:10 | 27.02 | 19.01 | 0.914406E+10 | 6196.49 | 31-MAY-21:40 | 20.60 | 15.57 |
June | 0.217877E+11 | 11156.41 | 26-JUN-18:10 | 29.72 | 22.36 | 0.918663E+10 | 6349.59 | 26-JUN-21:40 | 24.80 | 21.08 |
July | 0.234014E+11 | 11285.04 | 30-JUL-10:35 | 24.63 | 19.89 | 0.960448E+10 | 6300.24 | 25-JUL-21:40 | 24.63 | 19.89 |
August | 0.234504E+11 | 11074.56 | 27-AUG-10:35 | 25.53 | 19.86 | 0.969493E+10 | 6325.65 | 02-AUG-21:40 | 25.53 | 19.86 |
September | 0.214898E+11 | 11856.45 | 09-SEP-10:35 | 25.53 | 16.73 | 0.914278E+10 | 6443.39 | 07-SEP-21:40 | 25.53 | 16.73 |
October | 0.194141E+11 | 10857.99 | 20-OCT-15:23 | 22.30 | 13.06 | 0.895661E+10 | 6129.47 | 20-OCT-21:40 | 13.90 | 9.51 |
November | 0.146701E+11 | 10795.40 | 04-NOV-10:35 | 10.20 | 5.24 | 0.826079E+10 | 5761.88 | 03-NOV-21:40 | 10.20 | 5.24 |
December | 0.121577E+11 | 9954.92 | 03-DEC-11:35 | 4.80 | 2.32 | 0.826278E+10 | 5277.82 | 01-DEC-22:40 | 4.80 | 2.32 |
Annual Sum or Average | 0.214524E+12 | 0.105170E+12 | ||||||||
Minimum of Months | 0.110310E+11 | 8536.42 | 2.40 | 1.18 | 0.754761E+10 | 5277.82 | 1.13 | 0.51 | ||
Maximum of Months | 0.234504E+11 | 11856.45 | 29.72 | 22.36 | 0.969493E+10 | 6443.39 | 25.53 | 21.08 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448706E+11 | 25373.43 | 13-JAN-22:00 | 2.20 | 0.77 | 0.254996E+11 | 17391.30 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.448102E+11 | 26350.50 | 24-FEB-21:00 | 2.20 | 1.50 | 0.236402E+11 | 17699.41 | 24-FEB-22:49 | 0.87 | 0.34 |
March | 0.555277E+11 | 27580.83 | 24-MAR-20:00 | 3.90 | 2.01 | 0.272629E+11 | 18180.61 | 28-MAR-22:10 | 8.80 | 7.21 |
April | 0.589920E+11 | 31513.27 | 16-APR-10:35 | 23.33 | 18.86 | 0.273753E+11 | 19185.87 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.665097E+11 | 32393.21 | 31-MAY-18:10 | 27.02 | 19.01 | 0.294616E+11 | 19186.10 | 30-MAY-22:10 | 27.02 | 19.01 |
June | 0.686516E+11 | 34353.91 | 30-JUN-21:52 | 21.20 | 16.66 | 0.294774E+11 | 19186.24 | 19-JUN-22:10 | 21.20 | 16.66 |
July | 0.729231E+11 | 33562.00 | 03-JUL-22:00 | 23.30 | 22.56 | 0.307925E+11 | 19186.18 | 24-JUL-22:10 | 19.32 | 15.83 |
August | 0.728111E+11 | 33837.47 | 04-AUG-21:10 | 18.30 | 17.90 | 0.310262E+11 | 19186.18 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.673149E+11 | 35037.72 | 07-SEP-21:10 | 22.43 | 16.38 | 0.292634E+11 | 19186.32 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.627251E+11 | 29853.69 | 20-OCT-20:00 | 15.00 | 9.90 | 0.287544E+11 | 19176.79 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.532915E+11 | 28681.22 | 04-NOV-10:35 | 10.20 | 5.24 | 0.263481E+11 | 18584.63 | 03-NOV-21:49 | 10.20 | 5.24 |
December | 0.478296E+11 | 25617.36 | 03-DEC-11:35 | 4.80 | 2.32 | 0.259872E+11 | 17143.87 | 04-DEC-23:10 | 2.30 | 0.33 |
Annual Sum or Average | 0.716257E+12 | 0.334889E+12 | ||||||||
Minimum of Months | 0.448102E+11 | 25373.43 | 2.20 | 0.77 | 0.236402E+11 | 17143.87 | 0.82 | 0.04 | ||
Maximum of Months | 0.729231E+11 | 35037.72 | 27.02 | 22.56 | 0.310262E+11 | 19186.32 | 27.02 | 19.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5096463.33 | 2792.22 | 12-JAN-16:11 | 2.43 | 0.93 | 92291261.17 | 56.69 | 16-JAN-00:30 | -4.2 | -4.6 |
February | 24812972.11 | 3235.05 | 24-FEB-16:11 | 7.93 | 5.63 | 84240104.68 | 56.69 | 28-FEB-00:20 | -15.2 | -15.8 |
March | 90109658.96 | 3232.53 | 22-MAR-15:11 | 6.70 | 3.37 | 95022517.80 | 56.69 | 23-MAR-21:19 | 9.23 | 6.00 |
April | 0.478438E+09 | 3258.05 | 26-APR-15:11 | 10.20 | 3.44 | 93544248.73 | 56.69 | 18-APR-21:19 | 10.20 | 3.44 |
May | 0.879117E+09 | 3284.19 | 21-MAY-18:01 | 16.93 | 9.12 | 98625585.93 | 56.69 | 30-MAY-21:00 | 18.90 | 16.37 |
June | 0.148825E+10 | 2943.27 | 07-JUN-18:01 | 19.32 | 15.83 | 95872573.50 | 56.69 | 27-JUN-01:10 | 22.70 | 19.79 |
July | 0.184376E+10 | 2909.09 | 24-JUL-18:01 | 21.98 | 17.37 | 99317596.79 | 56.69 | 25-JUL-23:10 | 25.00 | 20.31 |
August | 0.165076E+10 | 2937.34 | 27-AUG-18:01 | 24.22 | 20.82 | 99347269.64 | 56.69 | 03-AUG-00:30 | 24.22 | 20.82 |
September | 0.108024E+10 | 3246.35 | 20-SEP-18:01 | 17.23 | 10.71 | 95236168.64 | 56.69 | 06-SEP-22:40 | 17.23 | 10.71 |
October | 0.240865E+09 | 3263.06 | 19-OCT-15:11 | 18.17 | 10.51 | 96671986.69 | 56.69 | 10-OCT-21:19 | 18.17 | 10.51 |
November | 54769806.56 | 3269.49 | 04-NOV-15:11 | 13.87 | 6.62 | 91048311.40 | 56.69 | 11-NOV-00:20 | -4.4 | -5.6 |
December | 8862529.37 | 2187.02 | 02-DEC-16:11 | 4.30 | 2.45 | 92653325.84 | 56.69 | 10-DEC-05:19 | -22.4 | -22.8 |
Annual Sum or Average | 0.784509E+10 | 0.113387E+10 | ||||||||
Minimum of Months | 5096463.33 | 2187.02 | 2.43 | 0.93 | 84240104.68 | 56.69 | -22.4 | -22.8 | ||
Maximum of Months | 0.184376E+10 | 3284.19 | 24.22 | 20.82 | 99347269.64 | 56.69 | 25.00 | 20.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1644828.10 | 949.17 | 12-JAN-16:13 | 2.43 | 0.93 | 91994640.22 | 56.69 | 07-JAN-00:20 | 2.43 | 0.93 |
February | 9336880.89 | 2980.25 | 24-FEB-16:11 | 7.93 | 5.63 | 83584512.84 | 56.69 | 05-FEB-00:20 | 7.93 | 5.63 |
March | 40496870.74 | 3072.79 | 24-MAR-15:11 | 12.07 | 6.17 | 94110564.60 | 56.69 | 01-MAR-04:19 | 12.07 | 6.17 |
April | 0.317721E+09 | 3153.21 | 26-APR-15:11 | 10.20 | 3.44 | 94166145.58 | 72.92 | 17-APR-18:10 | 10.20 | 3.44 |
May | 0.641562E+09 | 3508.67 | 20-MAY-18:41 | 13.68 | 7.74 | 0.101963E+09 | 73.25 | 30-MAY-21:40 | 19.27 | 16.63 |
June | 0.122559E+10 | 3058.19 | 16-JUN-16:51 | 24.40 | 16.64 | 0.102034E+09 | 82.79 | 08-JUN-18:10 | 24.40 | 16.64 |
July | 0.146600E+10 | 3025.17 | 23-JUL-21:51 | 13.90 | 11.92 | 0.107472E+09 | 82.62 | 24-JUL-18:10 | 21.98 | 17.37 |
August | 0.123557E+10 | 3329.02 | 11-AUG-18:11 | 23.70 | 17.82 | 0.106762E+09 | 80.43 | 16-AUG-18:10 | 21.83 | 15.21 |
September | 0.742843E+09 | 3407.75 | 24-SEP-16:11 | 14.63 | 7.59 | 98325442.39 | 76.30 | 12-SEP-21:10 | 14.63 | 7.59 |
October | 0.100714E+09 | 3066.81 | 29-OCT-15:11 | 14.63 | 8.10 | 95899279.99 | 56.69 | 20-OCT-21:30 | 14.63 | 8.10 |
November | 23101646.47 | 3145.04 | 04-NOV-15:11 | 13.87 | 6.62 | 90372810.99 | 56.69 | 23-NOV-00:20 | -1.7 | -2.6 |
December | 3960548.58 | 949.58 | 17-DEC-19:04 | -3.0 | -4.0 | 92027559.83 | 56.69 | 10-DEC-04:40 | -3.0 | -4.0 |
Annual Sum or Average | 0.580853E+10 | 0.115871E+10 | ||||||||
Minimum of Months | 1644828.10 | 949.17 | -3.0 | -4.0 | 83584512.84 | 56.69 | -3.0 | -4.0 | ||
Maximum of Months | 0.146600E+10 | 3508.67 | 24.40 | 17.82 | 0.107472E+09 | 82.79 | 24.40 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2027991.33 | 76.39 | 30-JAN-15:10 | -24.0 | -24.3 | 0.00 | 0.00 | 01-JAN-00:10 | -24.0 | -24.3 |
February | 5637307.03 | 108.34 | 02-FEB-15:10 | -28.9 | -29.2 | 0.00 | 0.00 | 01-FEB-00:10 | -28.9 | -29.2 |
March | 21270679.60 | 209.19 | 28-MAR-13:25 | 16.15 | 10.05 | 0.00 | 0.00 | 01-MAR-00:10 | 16.15 | 10.05 |
April | 0.117970E+09 | 445.80 | 15-APR-13:30 | 28.85 | 20.45 | 0.00 | 0.00 | 01-APR-00:10 | 28.85 | 20.45 |
May | 0.245055E+09 | 330.60 | 06-MAY-13:00 | 22.20 | 11.68 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 11.68 |
June | 0.358079E+09 | 350.89 | 26-JUN-12:50 | 31.02 | 21.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.02 | 21.46 |
July | 0.444281E+09 | 376.39 | 30-JUL-13:30 | 26.95 | 19.99 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 19.99 |
August | 0.454473E+09 | 424.82 | 29-AUG-13:30 | 23.60 | 16.39 | 0.00 | 0.00 | 01-AUG-00:10 | 23.60 | 16.39 |
September | 0.372419E+09 | 529.09 | 07-SEP-13:00 | 31.70 | 18.06 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.06 |
October | 0.174168E+09 | 507.71 | 20-OCT-13:00 | 21.80 | 12.61 | 0.00 | 0.00 | 01-OCT-00:10 | 21.80 | 12.61 |
November | 53752879.69 | 479.89 | 04-NOV-13:00 | 13.90 | 6.81 | 0.00 | 0.00 | 01-NOV-00:10 | 13.90 | 6.81 |
December | 3061829.30 | 97.83 | 07-DEC-15:20 | -3.9 | -7.6 | 0.00 | 0.00 | 01-DEC-00:10 | -3.9 | -7.6 |
Annual Sum or Average | 0.225220E+10 | 0.00 | ||||||||
Minimum of Months | 2027991.33 | 76.39 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.454473E+09 | 529.09 | 31.70 | 21.46 | 0.00 | 0.00 | 31.70 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5396212.13 | 466.72 | 14-JAN-09:02 | -3.8 | -4.0 | 93267683.78 | 56.69 | 16-JAN-00:30 | -4.2 | -4.6 |
February | 15552917.87 | 908.34 | 26-FEB-09:01 | -2.0 | -3.2 | 84914671.97 | 56.69 | 22-FEB-22:19 | -2.0 | -3.2 |
March | 85808926.18 | 948.86 | 24-MAR-18:01 | 8.35 | 4.47 | 95440709.45 | 56.69 | 19-MAR-23:19 | 8.35 | 4.47 |
April | 0.217502E+09 | 988.55 | 30-APR-18:01 | 15.22 | 9.05 | 94062171.17 | 70.53 | 18-APR-21:49 | 15.22 | 9.05 |
May | 0.426946E+09 | 1025.12 | 06-MAY-19:31 | 13.13 | 8.89 | 0.100182E+09 | 71.53 | 12-MAY-21:00 | 16.70 | 15.64 |
June | 0.579557E+09 | 980.29 | 21-JUN-21:01 | 14.40 | 12.13 | 99495424.34 | 75.43 | 21-JUN-21:10 | 14.40 | 12.13 |
July | 0.616023E+09 | 963.56 | 13-JUL-18:02 | 24.72 | 19.30 | 0.104248E+09 | 74.08 | 07-JUL-21:49 | 24.72 | 19.30 |
August | 0.557686E+09 | 972.84 | 11-AUG-18:11 | 23.70 | 17.82 | 0.103849E+09 | 73.28 | 16-AUG-21:30 | 15.30 | 12.85 |
September | 0.413074E+09 | 988.38 | 19-SEP-18:02 | 12.65 | 8.22 | 97019092.88 | 74.25 | 12-SEP-21:10 | 12.65 | 8.22 |
October | 0.196433E+09 | 941.27 | 19-OCT-18:01 | 11.92 | 7.44 | 96573404.51 | 56.86 | 20-OCT-20:19 | 14.63 | 9.75 |
November | 86003090.90 | 927.31 | 04-NOV-18:01 | 5.50 | 2.14 | 91995753.30 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 7540444.82 | 666.40 | 03-DEC-09:01 | -1.5 | -1.7 | 93577606.30 | 56.69 | 17-DEC-00:20 | -5.0 | -5.5 |
Annual Sum or Average | 0.320752E+10 | 0.115463E+10 | ||||||||
Minimum of Months | 5396212.13 | 466.72 | -3.8 | -4.0 | 84914671.97 | 56.69 | -5.0 | -5.5 | ||
Maximum of Months | 0.616023E+09 | 1025.12 | 24.72 | 19.30 | 0.104248E+09 | 75.43 | 24.72 | 19.30 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4264827.71 | 942.37 | 17-JAN-19:04 | 1.28 | 0.72 | 92258159.48 | 56.69 | 29-JAN-00:20 | -4.4 | -5.0 |
February | 20096358.18 | 2796.84 | 24-FEB-09:01 | 3.07 | 0.61 | 84209429.64 | 56.69 | 22-FEB-04:49 | 3.07 | 0.61 |
March | 84663975.02 | 2950.54 | 24-MAR-15:11 | 12.07 | 6.17 | 95163596.01 | 56.69 | 28-MAR-21:19 | 9.63 | 7.55 |
April | 0.406644E+09 | 2974.91 | 26-APR-08:61 | 2.48 | -1.4 | 93596445.08 | 56.69 | 18-APR-21:40 | 2.48 | -1.4 |
May | 0.923303E+09 | 2935.57 | 02-MAY-15:11 | 11.30 | 5.85 | 98989300.85 | 56.69 | 30-MAY-21:49 | 19.08 | 16.50 |
June | 0.150398E+10 | 2767.32 | 28-JUN-08:61 | 24.27 | 19.17 | 96056669.57 | 56.69 | 26-JUN-00:40 | 24.27 | 19.17 |
July | 0.179099E+10 | 2767.08 | 28-JUL-08:61 | 22.48 | 18.57 | 99469489.48 | 56.69 | 03-JUL-00:00 | 22.48 | 18.57 |
August | 0.158361E+10 | 2715.80 | 10-AUG-08:62 | 19.97 | 16.51 | 99531249.68 | 56.69 | 01-AUG-22:40 | 19.97 | 16.51 |
September | 0.107643E+10 | 2920.44 | 30-SEP-15:11 | 10.73 | 3.83 | 95505142.53 | 56.69 | 07-SEP-23:30 | 10.73 | 3.83 |
October | 0.201629E+09 | 2950.47 | 24-OCT-15:11 | 15.23 | 8.69 | 96838810.01 | 56.69 | 20-OCT-21:19 | 15.23 | 8.69 |
November | 46973570.38 | 2966.72 | 04-NOV-15:11 | 13.87 | 6.62 | 91016708.27 | 56.69 | 23-NOV-00:20 | -1.7 | -2.6 |
December | 10099991.23 | 1697.83 | 03-DEC-09:01 | -1.5 | -1.7 | 92547695.60 | 56.69 | 10-DEC-00:20 | -19.4 | -20.0 |
Annual Sum or Average | 0.765270E+10 | 0.113518E+10 | ||||||||
Minimum of Months | 4264827.71 | 942.37 | -1.5 | -1.7 | 84209429.64 | 56.69 | -19.4 | -20.0 | ||
Maximum of Months | 0.179099E+10 | 2974.91 | 24.27 | 19.17 | 99531249.68 | 56.69 | 24.27 | 19.17 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1531989.75 | 956.99 | 17-JAN-19:04 | 1.28 | 0.72 | 91998591.80 | 56.69 | 28-JAN-00:20 | -22.8 | -23.0 |
February | 7172858.03 | 2214.40 | 24-FEB-09:01 | 3.07 | 0.61 | 83547003.29 | 56.69 | 05-FEB-00:20 | 3.07 | 0.61 |
March | 38913044.75 | 2443.38 | 24-MAR-15:11 | 12.07 | 6.17 | 94152383.62 | 56.69 | 01-MAR-05:40 | 12.07 | 6.17 |
April | 0.268071E+09 | 2901.72 | 26-APR-08:61 | 2.48 | -1.4 | 93733982.56 | 70.63 | 18-APR-21:40 | 2.48 | -1.4 |
May | 0.711890E+09 | 2882.91 | 21-MAY-19:41 | 12.77 | 7.03 | 0.101464E+09 | 72.16 | 31-MAY-21:00 | 19.80 | 14.74 |
June | 0.124794E+10 | 3081.94 | 20-JUN-08:51 | 21.70 | 14.94 | 0.101135E+09 | 74.42 | 30-JUN-21:10 | 22.03 | 17.04 |
July | 0.141321E+10 | 3083.74 | 19-JUL-08:51 | 21.10 | 16.85 | 0.106580E+09 | 74.95 | 05-JUL-21:10 | 21.10 | 16.85 |
August | 0.119287E+10 | 3092.54 | 09-AUG-08:51 | 23.30 | 16.39 | 0.105599E+09 | 73.87 | 04-AUG-21:40 | 23.30 | 16.39 |
September | 0.744835E+09 | 3049.51 | 06-SEP-08:51 | 22.80 | 17.04 | 97985269.12 | 72.73 | 07-SEP-21:19 | 22.07 | 16.32 |
October | 79231038.61 | 2238.78 | 01-OCT-08:61 | 10.72 | 8.45 | 95621960.73 | 56.69 | 20-OCT-21:19 | 13.90 | 9.47 |
November | 14985958.00 | 1684.90 | 04-NOV-08:62 | 2.77 | 0.71 | 90294011.78 | 56.69 | 23-NOV-00:20 | -1.7 | -2.6 |
December | 2593589.95 | 1090.59 | 05-DEC-09:03 | -6.6 | -8.5 | 92019098.28 | 56.69 | 09-DEC-00:20 | -22.8 | -23.0 |
Annual Sum or Average | 0.572325E+10 | 0.115413E+10 | ||||||||
Minimum of Months | 1531989.75 | 956.99 | -6.6 | -8.5 | 83547003.29 | 56.69 | -22.8 | -23.0 | ||
Maximum of Months | 0.141321E+10 | 3092.54 | 23.30 | 17.04 | 0.106580E+09 | 74.95 | 23.30 | 17.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294130E+09 | 1127.23 | 13-JAN-22:20 | 1.83 | 0.65 | 0.119883E+10 | 705.97 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.833930E+09 | 1298.96 | 24-FEB-20:30 | 2.75 | 2.03 | 0.108402E+10 | 715.30 | 24-FEB-22:49 | 0.87 | 0.34 |
March | 0.185368E+10 | 1502.02 | 20-MAR-10:35 | 9.43 | 6.43 | 0.121142E+10 | 739.66 | 24-MAR-21:40 | 1.33 | 0.09 |
April | 0.279110E+10 | 1904.47 | 18-APR-10:35 | 26.33 | 20.75 | 0.121198E+10 | 848.54 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.376304E+10 | 1971.04 | 31-MAY-10:35 | 27.93 | 19.39 | 0.133097E+10 | 863.00 | 31-MAY-21:49 | 20.20 | 15.15 |
June | 0.408703E+10 | 2112.09 | 29-JUN-18:10 | 28.62 | 20.23 | 0.138200E+10 | 918.59 | 30-JUN-22:10 | 21.02 | 16.54 |
July | 0.444848E+10 | 2161.92 | 02-JUL-10:35 | 27.77 | 21.90 | 0.147156E+10 | 912.70 | 03-JUL-21:49 | 23.48 | 22.61 |
August | 0.435883E+10 | 2062.41 | 02-AUG-10:35 | 26.33 | 21.24 | 0.146307E+10 | 903.33 | 04-AUG-22:10 | 18.22 | 17.52 |
September | 0.385584E+10 | 2087.10 | 09-SEP-10:35 | 25.53 | 16.73 | 0.134173E+10 | 895.53 | 08-SEP-22:10 | 25.53 | 16.73 |
October | 0.299662E+10 | 1571.67 | 20-OCT-10:35 | 17.13 | 11.05 | 0.122555E+10 | 769.14 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.152191E+10 | 1552.75 | 04-NOV-10:35 | 10.20 | 5.24 | 0.116785E+10 | 742.91 | 03-NOV-21:49 | 10.20 | 5.24 |
December | 0.562322E+09 | 1152.44 | 03-DEC-11:00 | 4.40 | 2.26 | 0.119881E+10 | 704.42 | 12-DEC-04:30 | -20.0 | -20.3 |
Annual Sum or Average | 0.313669E+11 | 0.152878E+11 | ||||||||
Minimum of Months | 0.294130E+09 | 1127.23 | 1.83 | 0.65 | 0.108402E+10 | 704.42 | -20.0 | -20.3 | ||
Maximum of Months | 0.444848E+10 | 2161.92 | 28.62 | 21.90 | 0.147156E+10 | 918.59 | 25.53 | 22.61 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3356275.47 | 1903.71 | 12-JAN-16:11 | 2.43 | 0.93 | 92064158.13 | 56.69 | 28-JAN-05:30 | -20.2 | -20.6 |
February | 21914877.50 | 3348.96 | 24-FEB-16:11 | 7.93 | 5.63 | 83849796.92 | 56.69 | 05-FEB-00:20 | 7.93 | 5.63 |
March | 73880054.65 | 3339.68 | 24-MAR-15:11 | 12.07 | 6.17 | 94445555.53 | 56.69 | 23-MAR-21:19 | 12.07 | 6.17 |
April | 0.485743E+09 | 3386.68 | 26-APR-15:11 | 10.20 | 3.44 | 93215319.17 | 56.69 | 16-APR-04:10 | 10.20 | 3.44 |
May | 0.880875E+09 | 3413.19 | 21-MAY-18:01 | 16.93 | 9.12 | 98538192.55 | 56.69 | 21-MAY-00:10 | 16.93 | 9.12 |
June | 0.154411E+10 | 3013.90 | 07-JUN-18:01 | 19.32 | 15.83 | 95789531.24 | 56.69 | 29-JUN-23:40 | 23.30 | 19.08 |
July | 0.190255E+10 | 3043.69 | 14-JUL-15:12 | 24.60 | 20.59 | 99254665.31 | 56.69 | 02-JUL-23:00 | 24.60 | 20.59 |
August | 0.166133E+10 | 3019.89 | 30-AUG-15:11 | 18.33 | 15.20 | 99253292.53 | 56.69 | 11-AUG-21:40 | 18.33 | 15.20 |
September | 0.104508E+10 | 3363.21 | 20-SEP-18:01 | 17.23 | 10.71 | 94995137.16 | 56.69 | 12-SEP-21:10 | 17.23 | 10.71 |
October | 0.215645E+09 | 3357.56 | 31-OCT-15:11 | 9.43 | 3.99 | 96229946.95 | 56.69 | 21-OCT-02:09 | 9.43 | 3.99 |
November | 43945630.60 | 3388.73 | 04-NOV-15:11 | 13.87 | 6.62 | 90537577.41 | 56.69 | 23-NOV-00:20 | -1.7 | -2.6 |
December | 6206586.17 | 1110.59 | 02-DEC-16:11 | 4.30 | 2.45 | 92258171.17 | 56.69 | 29-DEC-00:20 | -8.5 | -9.0 |
Annual Sum or Average | 0.788463E+10 | 0.113043E+10 | ||||||||
Minimum of Months | 3356275.47 | 1110.59 | 2.43 | 0.93 | 83849796.92 | 56.69 | -20.2 | -20.6 | ||
Maximum of Months | 0.190255E+10 | 3413.19 | 24.60 | 20.59 | 99254665.31 | 56.69 | 24.60 | 20.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1193489.27 | 963.29 | 09-JAN-16:14 | -3.2 | -4.2 | 91908558.04 | 56.69 | 08-JAN-04:19 | -3.2 | -4.2 |
February | 6131754.72 | 3005.32 | 24-FEB-16:11 | 7.93 | 5.63 | 83298696.91 | 56.69 | 06-FEB-04:40 | 7.93 | 5.63 |
March | 29557752.78 | 3127.43 | 24-MAR-15:11 | 12.07 | 6.17 | 93596533.06 | 56.69 | 03-MAR-00:20 | 12.07 | 6.17 |
April | 0.320314E+09 | 3264.23 | 26-APR-15:11 | 10.20 | 3.44 | 93973149.50 | 78.71 | 17-APR-18:10 | 10.20 | 3.44 |
May | 0.642007E+09 | 3791.01 | 21-MAY-19:41 | 12.77 | 7.03 | 0.102516E+09 | 74.67 | 30-MAY-21:40 | 19.27 | 16.63 |
June | 0.130812E+10 | 3205.59 | 22-JUN-21:41 | 15.60 | 12.07 | 0.102872E+09 | 91.59 | 08-JUN-21:10 | 15.60 | 12.07 |
July | 0.156726E+10 | 3292.42 | 23-JUL-21:51 | 13.90 | 11.92 | 0.108185E+09 | 89.37 | 24-JUL-21:10 | 19.40 | 16.16 |
August | 0.127724E+10 | 3489.71 | 11-AUG-18:11 | 23.70 | 17.82 | 0.107306E+09 | 86.40 | 16-AUG-18:10 | 21.83 | 15.21 |
September | 0.718566E+09 | 3524.74 | 24-SEP-16:11 | 14.63 | 7.59 | 98274322.15 | 79.79 | 12-SEP-18:10 | 14.63 | 7.59 |
October | 78465168.12 | 3080.23 | 24-OCT-15:11 | 15.23 | 8.69 | 95368233.16 | 56.69 | 20-OCT-23:19 | 15.23 | 8.69 |
November | 17368090.95 | 3212.91 | 04-NOV-15:11 | 13.87 | 6.62 | 89942427.36 | 56.69 | 23-NOV-00:20 | -1.7 | -2.6 |
December | 2588834.93 | 1050.37 | 02-DEC-16:13 | 4.30 | 2.45 | 91858088.14 | 56.69 | 10-DEC-05:00 | -22.8 | -23.1 |
Annual Sum or Average | 0.596881E+10 | 0.115910E+10 | ||||||||
Minimum of Months | 1193489.27 | 963.29 | -3.2 | -4.2 | 83298696.91 | 56.69 | -22.8 | -23.1 | ||
Maximum of Months | 0.156726E+10 | 3791.01 | 23.70 | 17.82 | 0.108185E+09 | 91.59 | 21.83 | 16.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27118308.57 | 1816.18 | 12-JAN-16:11 | 2.43 | 0.93 | 93745202.86 | 56.69 | 13-JAN-22:19 | 1.83 | 0.65 |
February | 69265356.31 | 1787.23 | 17-FEB-16:11 | -6.9 | -8.9 | 85655376.30 | 56.69 | 24-FEB-22:19 | 1.67 | 1.15 |
March | 0.140928E+09 | 1834.81 | 22-MAR-15:11 | 6.70 | 3.37 | 96285005.00 | 56.69 | 20-MAR-00:10 | 6.70 | 3.37 |
April | 0.353971E+09 | 1831.21 | 26-APR-15:11 | 10.20 | 3.44 | 93833622.11 | 56.69 | 18-APR-21:00 | 10.20 | 3.44 |
May | 0.580793E+09 | 1770.09 | 21-MAY-18:01 | 16.93 | 9.12 | 98709704.07 | 56.69 | 04-MAY-21:40 | 16.93 | 9.12 |
June | 0.852773E+09 | 1661.25 | 07-JUN-15:11 | 20.37 | 16.41 | 95889262.60 | 56.69 | 27-JUN-00:30 | 23.05 | 19.84 |
July | 0.102556E+10 | 1667.24 | 12-JUL-18:01 | 23.12 | 17.49 | 99209929.86 | 56.69 | 12-JUL-21:00 | 18.90 | 16.01 |
August | 0.100244E+10 | 1671.98 | 20-AUG-18:01 | 23.43 | 17.47 | 99257172.13 | 56.69 | 14-AUG-21:49 | 23.43 | 17.47 |
September | 0.796549E+09 | 1833.60 | 30-SEP-15:11 | 10.73 | 3.83 | 95466349.01 | 56.69 | 05-SEP-22:49 | 10.73 | 3.83 |
October | 0.390839E+09 | 1845.18 | 23-OCT-15:11 | 7.73 | 3.39 | 97799587.06 | 56.69 | 20-OCT-22:10 | 7.73 | 3.39 |
November | 0.128053E+09 | 1818.83 | 12-NOV-16:11 | 0.00 | -2.8 | 92411322.76 | 56.69 | 07-NOV-22:19 | 0.00 | -2.8 |
December | 53811860.80 | 1808.16 | 01-DEC-16:11 | -2.4 | -4.5 | 94248570.95 | 56.69 | 10-DEC-00:20 | -19.4 | -20.0 |
Annual Sum or Average | 0.542210E+10 | 0.114251E+10 | ||||||||
Minimum of Months | 27118308.57 | 1661.25 | -6.9 | -8.9 | 85655376.30 | 56.69 | -19.4 | -20.0 | ||
Maximum of Months | 0.102556E+10 | 1845.18 | 23.43 | 17.49 | 99257172.13 | 56.69 | 23.43 | 19.84 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302715E+11 | 15982.74 | 13-JAN-23:10 | 0.82 | 0.04 | 0.154764E+11 | 10538.54 | 17-JAN-23:49 | 6.10 | 4.30 |
February | 0.289458E+11 | 16163.83 | 24-FEB-23:10 | 0.60 | 0.07 | 0.141990E+11 | 10620.59 | 24-FEB-23:49 | 0.60 | 0.07 |
March | 0.352533E+11 | 16954.73 | 28-MAR-22:10 | 8.80 | 7.21 | 0.163299E+11 | 10980.47 | 28-MAR-22:49 | 8.40 | 7.17 |
April | 0.370074E+11 | 18735.25 | 18-APR-21:10 | 16.32 | 13.39 | 0.162736E+11 | 11348.72 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.416604E+11 | 20108.46 | 30-MAY-21:10 | 19.82 | 17.01 | 0.174961E+11 | 11348.93 | 30-MAY-22:10 | 18.90 | 16.33 |
June | 0.425223E+11 | 21003.71 | 27-JUN-21:05 | 23.62 | 18.90 | 0.173394E+11 | 11349.20 | 21-JUN-21:19 | 23.62 | 18.90 |
July | 0.445775E+11 | 20510.03 | 05-JUL-21:10 | 22.43 | 20.32 | 0.179315E+11 | 11349.13 | 24-JUL-22:10 | 19.32 | 15.83 |
August | 0.439319E+11 | 20527.85 | 03-AUG-21:10 | 24.32 | 23.15 | 0.179409E+11 | 11349.12 | 16-AUG-21:00 | 15.00 | 12.41 |
September | 0.402414E+11 | 19694.10 | 11-SEP-21:10 | 19.40 | 17.91 | 0.168846E+11 | 11349.20 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.376581E+11 | 17345.07 | 20-OCT-21:00 | 13.90 | 9.43 | 0.166950E+11 | 11156.01 | 20-OCT-22:49 | 13.90 | 9.64 |
November | 0.334690E+11 | 17347.78 | 08-NOV-23:10 | 14.40 | 12.79 | 0.156579E+11 | 11143.08 | 08-NOV-23:49 | 14.40 | 12.79 |
December | 0.316183E+11 | 15909.09 | 04-DEC-23:10 | 2.30 | 0.33 | 0.156824E+11 | 10516.68 | 04-DEC-23:00 | 2.80 | 0.44 |
Annual Sum or Average | 0.447157E+12 | 0.197907E+12 | ||||||||
Minimum of Months | 0.289458E+11 | 15909.09 | 0.60 | 0.04 | 0.141990E+11 | 10516.68 | 0.60 | 0.07 | ||
Maximum of Months | 0.445775E+11 | 21003.71 | 24.32 | 23.15 | 0.179409E+11 | 11349.20 | 23.62 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329963E+11 | 16782.82 | 13-JAN-23:10 | 0.82 | 0.04 | 0.159553E+11 | 10926.39 | 17-JAN-23:49 | 6.10 | 4.30 |
February | 0.313871E+11 | 16979.17 | 24-FEB-23:10 | 0.60 | 0.07 | 0.146525E+11 | 11017.46 | 24-FEB-23:49 | 0.60 | 0.07 |
March | 0.378165E+11 | 17758.83 | 28-MAR-21:00 | 10.00 | 7.70 | 0.169381E+11 | 11343.99 | 28-MAR-23:10 | 8.30 | 7.15 |
April | 0.391763E+11 | 20377.10 | 18-APR-21:10 | 16.32 | 13.39 | 0.168391E+11 | 11348.73 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.435009E+11 | 21102.08 | 31-MAY-21:53 | 19.80 | 14.74 | 0.179543E+11 | 11348.94 | 30-MAY-22:10 | 19.80 | 14.74 |
June | 0.441970E+11 | 21787.32 | 26-JUN-22:00 | 24.40 | 20.95 | 0.177290E+11 | 11349.17 | 16-JUN-22:10 | 24.40 | 20.95 |
July | 0.462286E+11 | 21575.51 | 03-JUL-22:00 | 23.30 | 22.56 | 0.183150E+11 | 11349.14 | 24-JUL-22:10 | 19.32 | 15.83 |
August | 0.455592E+11 | 21383.88 | 03-AUG-22:00 | 23.90 | 22.63 | 0.183216E+11 | 11349.13 | 16-AUG-21:00 | 15.00 | 12.41 |
September | 0.419309E+11 | 20723.90 | 07-SEP-21:53 | 20.60 | 15.99 | 0.173188E+11 | 11349.18 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.399121E+11 | 18346.40 | 20-OCT-23:00 | 13.90 | 9.66 | 0.173166E+11 | 11344.20 | 11-OCT-22:30 | 13.90 | 9.66 |
November | 0.359360E+11 | 18504.63 | 08-NOV-24:00 | 14.40 | 12.79 | 0.162143E+11 | 11343.97 | 07-NOV-23:30 | 14.40 | 12.79 |
December | 0.343426E+11 | 16701.91 | 04-DEC-23:10 | 2.30 | 0.33 | 0.161945E+11 | 10901.85 | 04-DEC-23:49 | 2.70 | 0.42 |
Annual Sum or Average | 0.472983E+12 | 0.203749E+12 | ||||||||
Minimum of Months | 0.313871E+11 | 16701.91 | 0.60 | 0.04 | 0.146525E+11 | 10901.85 | 0.60 | 0.07 | ||
Maximum of Months | 0.462286E+11 | 21787.32 | 24.40 | 22.63 | 0.183216E+11 | 11349.18 | 24.40 | 20.95 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432747E+11 | 25104.29 | 13-JAN-11:50 | 3.62 | 1.34 | 0.188678E+11 | 11319.69 | 07-JAN-18:10 | 3.62 | 1.34 |
February | 0.406107E+11 | 25958.96 | 24-FEB-11:40 | 5.93 | 2.90 | 0.170408E+11 | 11319.68 | 04-FEB-18:10 | 5.93 | 2.90 |
March | 0.476804E+11 | 27229.42 | 19-MAR-10:50 | 14.13 | 10.21 | 0.188760E+11 | 11321.43 | 25-MAR-17:19 | 16.13 | 10.21 |
April | 0.485154E+11 | 28836.09 | 15-APR-10:40 | 24.67 | 19.18 | 0.182622E+11 | 11319.68 | 15-APR-17:10 | 29.72 | 18.80 |
May | 0.530868E+11 | 29262.31 | 31-MAY-10:40 | 27.93 | 19.39 | 0.188716E+11 | 11319.61 | 20-MAY-17:10 | 27.93 | 19.39 |
June | 0.531491E+11 | 29608.68 | 11-JUN-10:50 | 30.13 | 22.31 | 0.182660E+11 | 11319.68 | 10-JUN-17:10 | 30.13 | 22.31 |
July | 0.554980E+11 | 29678.06 | 29-JUL-10:40 | 25.93 | 19.88 | 0.188681E+11 | 11319.68 | 15-JUL-17:10 | 25.93 | 19.88 |
August | 0.548988E+11 | 29176.41 | 01-AUG-10:40 | 26.83 | 21.26 | 0.188753E+11 | 11319.68 | 05-AUG-17:10 | 25.32 | 17.94 |
September | 0.512801E+11 | 29286.58 | 08-SEP-10:50 | 28.62 | 18.93 | 0.182615E+11 | 11319.66 | 09-SEP-17:10 | 26.73 | 16.46 |
October | 0.496624E+11 | 27378.33 | 01-OCT-10:35 | 16.07 | 11.42 | 0.188688E+11 | 11319.37 | 21-OCT-17:19 | 15.03 | 11.77 |
November | 0.452577E+11 | 26959.63 | 04-NOV-10:40 | 10.20 | 5.24 | 0.182586E+11 | 11319.68 | 25-NOV-18:10 | -20.8 | -21.1 |
December | 0.443168E+11 | 25556.75 | 03-DEC-11:50 | 4.90 | 2.33 | 0.188679E+11 | 11319.71 | 09-DEC-18:10 | -19.5 | -19.9 |
Annual Sum or Average | 0.587231E+12 | 0.222185E+12 | ||||||||
Minimum of Months | 0.406107E+11 | 25104.29 | 3.62 | 1.34 | 0.170408E+11 | 11319.37 | -20.8 | -21.1 | ||
Maximum of Months | 0.554980E+11 | 29678.06 | 30.13 | 22.31 | 0.188760E+11 | 11321.43 | 30.13 | 22.31 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146605E+09 | 1436.85 | 13-JAN-11:35 | 3.33 | 1.18 | 0.126888E+10 | 746.59 | 13-JAN-22:49 | 1.28 | 0.44 |
February | 0.673079E+09 | 1594.23 | 24-FEB-11:40 | 5.93 | 2.90 | 0.114924E+10 | 775.01 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.198885E+10 | 1798.00 | 20-MAR-10:35 | 9.43 | 6.43 | 0.131169E+10 | 851.23 | 19-MAR-23:30 | 9.43 | 6.43 |
April | 0.359361E+10 | 3743.90 | 18-APR-15:10 | 27.75 | 20.46 | 0.137960E+10 | 1007.39 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.511516E+10 | 4633.35 | 31-MAY-15:10 | 29.72 | 19.55 | 0.161526E+10 | 1007.40 | 30-MAY-22:10 | 29.72 | 19.55 |
June | 0.688742E+10 | 5396.61 | 30-JUN-14:10 | 29.40 | 21.90 | 0.163085E+10 | 1007.42 | 01-JUN-01:10 | 29.40 | 21.90 |
July | 0.773857E+10 | 5347.45 | 29-JUL-13:30 | 27.80 | 20.45 | 0.170779E+10 | 1007.40 | 12-JUL-22:10 | 27.80 | 20.45 |
August | 0.706628E+10 | 5609.15 | 04-AUG-15:10 | 33.90 | 25.49 | 0.171264E+10 | 1007.40 | 11-AUG-22:10 | 17.12 | 15.39 |
September | 0.558314E+10 | 5800.41 | 07-SEP-13:30 | 31.95 | 18.23 | 0.156234E+10 | 1007.42 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.377704E+10 | 1908.70 | 20-OCT-17:20 | 18.53 | 11.43 | 0.138978E+10 | 907.02 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.171847E+10 | 1881.70 | 04-NOV-10:35 | 10.20 | 5.24 | 0.127162E+10 | 874.10 | 08-NOV-23:10 | 14.40 | 12.79 |
December | 0.247825E+09 | 1532.78 | 03-DEC-11:50 | 4.90 | 2.33 | 0.126901E+10 | 745.59 | 12-DEC-05:40 | -20.0 | -20.3 |
Annual Sum or Average | 0.445360E+11 | 0.172687E+11 | ||||||||
Minimum of Months | 0.146605E+09 | 1436.85 | 3.33 | 1.18 | 0.114924E+10 | 745.59 | -20.0 | -20.3 | ||
Maximum of Months | 0.773857E+10 | 5800.41 | 33.90 | 25.49 | 0.171264E+10 | 1007.42 | 29.72 | 21.90 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167334E+10 | 2103.04 | 19-JAN-07:40 | -28.1 |
February | 0.822162E+09 | 2422.48 | 02-FEB-07:30 | -36.7 |
March | 0.293020E+09 | 886.52 | 06-MAR-07:05 | -12.7 |
April | 73289551.87 | 667.39 | 03-APR-06:10 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 347212.18 | 123.38 | 30-SEP-06:30 | 0.60 |
October | 1816780.78 | 134.21 | 23-OCT-06:10 | -3.0 |
November | 0.476329E+09 | 1738.34 | 26-NOV-07:00 | -28.9 |
December | 0.128462E+10 | 1946.36 | 09-DEC-17:00 | -19.4 |
Annual Sum or Average | 0.462493E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.7 | |
Maximum of Months | 0.167334E+10 | 2422.48 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3107184.17 | 118.31 | 19-JAN-10:10 | -26.9 |
February | 6001748.92 | 203.74 | 03-FEB-10:53 | -29.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 377649.37 | 54.68 | 26-NOV-16:00 | -13.9 |
December | 3898899.31 | 116.17 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 13385481.77 | |||
Minimum of Months | 0.00 | 0.00 | -29.4 | |
Maximum of Months | 6001748.92 | 203.74 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102293E+10 | 1227.64 | 31-JAN-05:00 | -30.6 |
February | 0.598462E+09 | 1472.21 | 03-FEB-05:00 | -33.9 |
March | 87801469.15 | 485.33 | 06-MAR-05:00 | -15.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.181203E+09 | 825.43 | 26-NOV-06:00 | -26.1 |
December | 0.509968E+09 | 948.34 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.240036E+10 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.102293E+10 | 1472.21 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118278E+10 | 975.70 | 31-JAN-05:00 | -30.6 |
February | 0.701860E+09 | 1133.28 | 02-FEB-09:03 | -35.2 |
March | 0.242156E+09 | 484.73 | 06-MAR-04:50 | -15.7 |
April | 32038029.69 | 244.45 | 03-APR-11:30 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.283340E+09 | 790.03 | 26-NOV-07:00 | -28.9 |
December | 0.764588E+09 | 812.17 | 11-DEC-16:00 | -20.0 |
Annual Sum or Average | 0.320676E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.118278E+10 | 1133.28 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89246441.28 | 2078.37 | 19-JAN-09:03 | -28.1 |
February | 22527219.62 | 1854.64 | 02-FEB-07:30 | -36.7 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 7598843.16 | 1040.93 | 26-NOV-16:00 | -13.9 |
December | 0.116129E+09 | 2067.45 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 0.235501E+09 | |||
Minimum of Months | 0.00 | 0.00 | -36.7 | |
Maximum of Months | 0.116129E+09 | 2078.37 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187517E+10 | 2993.43 | 19-JAN-19:01 | -23.3 |
February | 0.118150E+10 | 2977.29 | 04-FEB-19:01 | -20.0 |
March | 0.667109E+09 | 2951.33 | 01-MAR-16:11 | -3.9 |
April | 0.252840E+09 | 2942.94 | 03-APR-08:61 | -5.9 |
May | 12173881.09 | 1293.58 | 02-MAY-08:62 | 4.08 |
June | 2904112.69 | 1143.12 | 04-JUN-15:14 | 15.00 |
July | 880300.25 | 793.02 | 20-JUL-08:05 | 20.68 |
August | 1094624.66 | 1095.22 | 06-AUG-08:04 | 12.80 |
September | 38691060.02 | 1631.73 | 29-SEP-08:62 | 5.05 |
October | 0.186230E+09 | 2858.69 | 26-OCT-08:61 | 1.28 |
November | 0.840882E+09 | 2985.63 | 26-NOV-16:11 | -13.9 |
December | 0.158021E+10 | 3005.83 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.663968E+10 | |||
Minimum of Months | 880300.25 | 793.02 | -23.3 | |
Maximum of Months | 0.187517E+10 | 3005.83 | 20.68 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217835E+10 | 2977.49 | 19-JAN-16:11 | -23.0 |
February | 0.143744E+10 | 2967.50 | 04-FEB-19:01 | -20.0 |
March | 0.791674E+09 | 2928.23 | 06-MAR-09:01 | -9.5 |
April | 0.289942E+09 | 2918.41 | 03-APR-08:61 | -5.9 |
May | 14512331.42 | 1634.06 | 02-MAY-08:62 | 4.08 |
June | 2854859.94 | 1128.33 | 22-JUN-08:04 | 15.18 |
July | 403572.78 | 699.64 | 12-JUL-08:53 | 20.00 |
August | 902923.38 | 1079.18 | 06-AUG-08:04 | 12.80 |
September | 48468194.86 | 2242.28 | 29-SEP-08:62 | 5.05 |
October | 0.278527E+09 | 2857.54 | 27-OCT-08:61 | 3.15 |
November | 0.992525E+09 | 2965.27 | 26-NOV-16:11 | -13.9 |
December | 0.180409E+10 | 2984.78 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.783969E+10 | |||
Minimum of Months | 403572.78 | 699.64 | -23.0 | |
Maximum of Months | 0.217835E+10 | 2984.78 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124209E+09 | 301.08 | 19-JAN-05:10 | -27.3 |
February | 35433424.21 | 276.71 | 04-FEB-06:00 | -30.6 |
March | 1624712.31 | 80.02 | 05-MAR-06:00 | -8.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 4416708.20 | 173.29 | 28-NOV-05:00 | -21.7 |
December | 77441804.65 | 242.29 | 12-DEC-05:00 | -20.0 |
Annual Sum or Average | 0.243126E+09 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.124209E+09 | 301.08 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386077E+09 | 875.19 | 31-JAN-16:11 | -20.2 |
February | 0.235003E+09 | 876.55 | 04-FEB-16:11 | -19.6 |
March | 70233888.14 | 849.80 | 05-MAR-16:11 | -9.8 |
April | 9853565.45 | 824.87 | 03-APR-15:11 | -3.1 |
May | 148613.84 | 188.04 | 02-MAY-15:14 | 11.30 |
June | 93051.57 | 221.84 | 06-JUN-08:06 | 12.30 |
July | 28283.00 | 134.97 | 22-JUL-21:37 | 14.27 |
August | 59175.35 | 185.97 | 18-AUG-08:54 | 21.10 |
September | 387737.90 | 341.29 | 24-SEP-16:13 | 14.63 |
October | 2092614.50 | 416.22 | 29-OCT-15:13 | 14.63 |
November | 0.111592E+09 | 873.54 | 25-NOV-16:11 | -18.3 |
December | 0.275580E+09 | 874.66 | 10-DEC-16:11 | -18.0 |
Annual Sum or Average | 0.109115E+10 | |||
Minimum of Months | 28283.00 | 134.97 | -20.2 | |
Maximum of Months | 0.386077E+09 | 876.55 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186015E+10 | 2890.99 | 19-JAN-16:11 | -23.0 |
February | 0.120042E+10 | 2880.07 | 04-FEB-19:01 | -20.0 |
March | 0.654153E+09 | 2850.30 | 01-MAR-16:11 | -3.9 |
April | 0.280549E+09 | 2838.69 | 03-APR-08:61 | -5.9 |
May | 9722351.16 | 1188.21 | 24-MAY-18:04 | 12.80 |
June | 2118364.76 | 948.15 | 03-JUN-18:04 | 14.22 |
July | 207091.70 | 547.32 | 08-JUL-08:05 | 16.70 |
August | 511905.55 | 752.35 | 23-AUG-08:05 | 18.98 |
September | 32816858.61 | 1217.44 | 13-SEP-15:14 | 19.03 |
October | 0.186836E+09 | 2747.08 | 26-OCT-08:61 | 1.28 |
November | 0.844906E+09 | 2881.77 | 26-NOV-16:11 | -13.9 |
December | 0.158277E+10 | 2898.07 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.665516E+10 | |||
Minimum of Months | 207091.70 | 547.32 | -23.0 | |
Maximum of Months | 0.186015E+10 | 2898.07 | 19.03 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216511E+10 | 2876.98 | 19-JAN-16:11 | -23.0 |
February | 0.146340E+10 | 2875.33 | 04-FEB-16:11 | -19.6 |
March | 0.776533E+09 | 2830.06 | 05-MAR-19:01 | -14.0 |
April | 0.323977E+09 | 2814.44 | 03-APR-15:11 | -3.1 |
May | 11665977.96 | 1052.68 | 20-MAY-18:43 | 13.68 |
June | 2133917.15 | 1099.84 | 03-JUN-15:14 | 14.40 |
July | 313294.95 | 754.91 | 10-JUL-21:54 | 15.00 |
August | 403773.12 | 594.21 | 25-AUG-08:05 | 14.68 |
September | 40229480.70 | 1068.53 | 24-SEP-18:03 | 11.52 |
October | 0.277271E+09 | 2737.76 | 26-OCT-08:61 | 1.28 |
November | 0.996117E+09 | 2861.29 | 26-NOV-16:11 | -13.9 |
December | 0.181387E+10 | 2876.85 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.787102E+10 | |||
Minimum of Months | 313294.95 | 594.21 | -23.0 | |
Maximum of Months | 0.216511E+10 | 2876.98 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.746984E+09 | 1405.01 | 19-JAN-09:03 | -28.1 |
February | 0.377458E+09 | 1496.39 | 02-FEB-07:20 | -36.7 |
March | 53041287.67 | 581.96 | 01-MAR-15:00 | -3.9 |
April | 6974791.77 | 330.10 | 03-APR-08:03 | -5.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.170087E+09 | 1188.81 | 26-NOV-16:00 | -13.9 |
December | 0.540475E+09 | 1457.59 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 0.189502E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.7 | |
Maximum of Months | 0.746984E+09 | 1496.39 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264091E+10 | 3467.69 | 19-JAN-19:01 | -23.3 |
February | 0.172843E+10 | 3446.40 | 04-FEB-19:01 | -20.0 |
March | 0.103258E+10 | 3411.37 | 01-MAR-16:11 | -3.9 |
April | 0.433158E+09 | 3388.17 | 03-APR-08:61 | -5.9 |
May | 34455683.81 | 2447.23 | 02-MAY-08:62 | 4.08 |
June | 14094377.68 | 1132.84 | 04-JUN-15:14 | 15.00 |
July | 883301.71 | 963.10 | 31-JUL-08:04 | 18.42 |
August | 1039814.56 | 856.41 | 06-AUG-08:04 | 12.80 |
September | 91215234.22 | 2760.75 | 29-SEP-08:62 | 5.05 |
October | 0.372709E+09 | 3347.48 | 26-OCT-08:61 | 1.28 |
November | 0.126920E+10 | 3456.19 | 26-NOV-16:11 | -13.9 |
December | 0.224236E+10 | 3480.22 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.986103E+10 | |||
Minimum of Months | 883301.71 | 856.41 | -23.3 | |
Maximum of Months | 0.264091E+10 | 3480.22 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298761E+10 | 3441.03 | 19-JAN-16:11 | -23.0 |
February | 0.203133E+10 | 3427.79 | 04-FEB-19:01 | -20.0 |
March | 0.120231E+10 | 3377.78 | 01-MAR-16:11 | -3.9 |
April | 0.484869E+09 | 3353.55 | 03-APR-08:61 | -5.9 |
May | 36659301.10 | 2728.08 | 02-MAY-08:62 | 4.08 |
June | 14455551.70 | 1081.01 | 04-JUN-08:03 | 11.38 |
July | 459066.01 | 505.34 | 11-JUL-21:55 | 15.00 |
August | 835725.15 | 1005.73 | 06-AUG-08:04 | 12.80 |
September | 0.108872E+09 | 3176.63 | 30-SEP-08:62 | 3.35 |
October | 0.507329E+09 | 3334.73 | 27-OCT-08:61 | 3.15 |
November | 0.146397E+10 | 3425.77 | 26-NOV-16:11 | -13.9 |
December | 0.251804E+10 | 3448.67 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.113567E+11 | |||
Minimum of Months | 459066.01 | 505.34 | -23.0 | |
Maximum of Months | 0.298761E+10 | 3448.67 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.929239E+09 | 1830.26 | 26-JAN-16:11 | -11.5 |
February | 0.541110E+09 | 1807.83 | 28-FEB-19:01 | -15.7 |
March | 0.305590E+09 | 1808.10 | 01-MAR-16:11 | -3.9 |
April | 0.135024E+09 | 1798.69 | 02-APR-15:11 | 0.60 |
May | 4240597.82 | 556.77 | 26-MAY-18:04 | 19.32 |
June | 1212208.94 | 573.37 | 01-JUN-15:14 | 11.97 |
July | 293239.21 | 435.54 | 10-JUL-15:14 | 18.30 |
August | 660271.84 | 344.56 | 23-AUG-08:05 | 18.98 |
September | 13081003.84 | 578.64 | 13-SEP-15:14 | 19.03 |
October | 50181602.48 | 1604.79 | 26-OCT-08:61 | 1.28 |
November | 0.384139E+09 | 1825.26 | 26-NOV-16:11 | -13.9 |
December | 0.783222E+09 | 1836.18 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.314799E+10 | |||
Minimum of Months | 293239.21 | 344.56 | -20.2 | |
Maximum of Months | 0.929239E+09 | 1836.18 | 19.32 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432445E+10 | 5003.51 | 31-JAN-07:30 | -30.3 |
February | 0.229748E+10 | 5972.50 | 02-FEB-07:10 | -36.7 |
March | 0.493778E+09 | 2170.73 | 06-MAR-07:05 | -12.7 |
April | 41048859.15 | 986.54 | 03-APR-06:10 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.105209E+10 | 4172.58 | 26-NOV-07:00 | -28.9 |
December | 0.282809E+10 | 4100.29 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.110369E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.7 | |
Maximum of Months | 0.432445E+10 | 5972.50 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785035E+10 | 7561.54 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.708815E+10 | 7561.54 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.787455E+10 | 7561.54 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.758419E+10 | 7561.54 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.786396E+10 | 7561.54 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.761897E+10 | 7561.54 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.782918E+10 | 7561.54 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.787758E+10 | 7561.54 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.758721E+10 | 7561.54 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.784733E+10 | 7561.54 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.761292E+10 | 7561.54 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.782918E+10 | 7561.54 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.924636E+11 | 0.143105E+12 | ||||
Minimum of Months | 0.708815E+10 | 7561.54 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.787758E+10 | 7561.54 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.355268E+09 | 342.20 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.320774E+09 | 342.20 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.356363E+09 | 342.20 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.343222E+09 | 342.20 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.355884E+09 | 342.20 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.344797E+09 | 342.20 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.354310E+09 | 342.20 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.356500E+09 | 342.20 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.343359E+09 | 342.20 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.355131E+09 | 342.20 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.344523E+09 | 342.20 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.354310E+09 | 342.20 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.418444E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.320774E+09 | 342.20 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.356500E+09 | 342.20 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411401E+09 | 396.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.371458E+09 | 396.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.412669E+09 | 396.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.397453E+09 | 396.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.412115E+09 | 396.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.399276E+09 | 396.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.410292E+09 | 396.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.412828E+09 | 396.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.397611E+09 | 396.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.411243E+09 | 396.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.398959E+09 | 396.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.410292E+09 | 396.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.484560E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.371458E+09 | 396.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.412828E+09 | 396.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.736067E+09 | 708.98 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.664602E+09 | 708.98 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.738336E+09 | 708.98 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.711111E+09 | 708.98 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.737344E+09 | 708.98 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.714372E+09 | 708.98 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.734082E+09 | 708.98 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.738620E+09 | 708.98 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.711395E+09 | 708.98 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.735784E+09 | 708.98 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.713805E+09 | 708.98 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.734082E+09 | 708.98 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.866960E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.664602E+09 | 708.98 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.738620E+09 | 708.98 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.168723E+09 | 162.52 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.152342E+09 | 162.52 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.169243E+09 | 162.52 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.163003E+09 | 162.52 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.169016E+09 | 162.52 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.163750E+09 | 162.52 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.168268E+09 | 162.52 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.169308E+09 | 162.52 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.163068E+09 | 162.52 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.168658E+09 | 162.52 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.163620E+09 | 162.52 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.168268E+09 | 162.52 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.198727E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.152342E+09 | 162.52 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.169308E+09 | 162.52 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314027E+09 | 302.47 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.283537E+09 | 302.47 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.314994E+09 | 302.47 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.303380E+09 | 302.47 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.314571E+09 | 302.47 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.304771E+09 | 302.47 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.313180E+09 | 302.47 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.315115E+09 | 302.47 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.303501E+09 | 302.47 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.313906E+09 | 302.47 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.304529E+09 | 302.47 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.313180E+09 | 302.47 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.369869E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.283537E+09 | 302.47 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.315115E+09 | 302.47 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.647197E+09 | 810.33 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.559594E+09 | 810.33 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.571063E+09 | 810.33 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.504089E+09 | 810.33 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.461716E+09 | 810.33 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.431255E+09 | 810.33 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.449496E+09 | 810.33 | 03-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.488373E+09 | 810.33 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.533364E+09 | 810.33 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.604041E+09 | 810.33 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.616252E+09 | 810.33 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.656893E+09 | 810.33 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.652333E+10 | 0.143405E+11 | ||||
Minimum of Months | 0.431255E+09 | 810.33 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.656893E+09 | 810.33 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.679431E+10 | 6817.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.609647E+10 | 6817.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.670357E+10 | 6817.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.639280E+10 | 6817.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.654273E+10 | 6817.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.631293E+10 | 6817.32 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.649389E+10 | 6817.32 | 03-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.658796E+10 | 6817.32 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.643346E+10 | 6817.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.672794E+10 | 6817.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.657186E+10 | 6817.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.679642E+10 | 6817.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.784543E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.609647E+10 | 6817.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.679642E+10 | 6817.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.115875E+10 | 1116.11 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.104624E+10 | 1116.11 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.116232E+10 | 1116.11 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.111946E+10 | 1116.11 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.116076E+10 | 1116.11 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.112460E+10 | 1116.11 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.115562E+10 | 1116.11 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.116277E+10 | 1116.11 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.111991E+10 | 1116.11 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.115830E+10 | 1116.11 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.112370E+10 | 1116.11 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.115562E+10 | 1116.11 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136481E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.104624E+10 | 1116.11 | 0.00 | 0.00 | |
Maximum of Months | 0.116277E+10 | 1116.11 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131779E+10 | 1423.01 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.116701E+10 | 1423.01 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.124462E+10 | 1423.01 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.115169E+10 | 1423.01 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.113206E+10 | 1423.01 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.107858E+10 | 1423.01 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.111717E+10 | 1423.01 | 03-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.116057E+10 | 1423.01 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.118148E+10 | 1423.01 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.127574E+10 | 1423.01 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.126732E+10 | 1423.01 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.133141E+10 | 1423.01 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.144254E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.107858E+10 | 1423.01 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.133141E+10 | 1423.01 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131779E+10 | 1423.01 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.116701E+10 | 1423.01 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.124462E+10 | 1423.01 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.115169E+10 | 1423.01 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.113206E+10 | 1423.01 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.107858E+10 | 1423.01 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.111717E+10 | 1423.01 | 03-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.116057E+10 | 1423.01 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.118148E+10 | 1423.01 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.127574E+10 | 1423.01 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.126732E+10 | 1423.01 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.133141E+10 | 1423.01 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.144254E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.107858E+10 | 1423.01 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.133141E+10 | 1423.01 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.775957E+09 | 747.41 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.700619E+09 | 747.41 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.778349E+09 | 747.41 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.749649E+09 | 747.41 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.777303E+09 | 747.41 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.753087E+09 | 747.41 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.773865E+09 | 747.41 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.778648E+09 | 747.41 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.749948E+09 | 747.41 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.775658E+09 | 747.41 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.752489E+09 | 747.41 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.773865E+09 | 747.41 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.913943E+10 | 0.424019E+12 | ||||
Minimum of Months | 0.700619E+09 | 747.41 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.778648E+09 | 747.41 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.122636E+10 | 1181.23 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.110729E+10 | 1181.23 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.123014E+10 | 1181.23 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.118478E+10 | 1181.23 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.122848E+10 | 1181.23 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.119021E+10 | 1181.23 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.122305E+10 | 1181.23 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.123061E+10 | 1181.23 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.118525E+10 | 1181.23 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.122588E+10 | 1181.23 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.118927E+10 | 1181.23 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.122305E+10 | 1181.23 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.144444E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.110729E+10 | 1181.23 | 0.00 | 0.00 | |
Maximum of Months | 0.123061E+10 | 1181.23 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.785035E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.708815E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.787455E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.758419E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.786396E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.761897E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.782918E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.787758E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.758721E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.784733E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.761292E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.782918E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.924636E+11 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.708815E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.787758E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.355268E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116232E+10 |
February | 0.179968E+10 | 0.320774E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889565E+09 |
March | 0.199990E+10 | 0.356363E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688420E+09 |
April | 0.192973E+10 | 0.343222E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3357914.72 | 0.466503E+09 |
May | 0.199475E+10 | 0.355884E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266822.99 | 0.260247E+09 |
June | 0.193394E+10 | 0.344797E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22451870.35 | 0.142110E+09 |
July | 0.199054E+10 | 0.354310E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17211348.04 | 98286644.13 |
August | 0.199896E+10 | 0.356500E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17338588.40 | 0.124724E+09 |
September | 0.192879E+10 | 0.343359E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12307768.66 | 0.239025E+09 |
October | 0.199148E+10 | 0.355131E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460646E+09 |
November | 0.192552E+10 | 0.344523E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682445E+09 |
December | 0.199054E+10 | 0.354310E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973418E+09 |
Annual Sum or Average | 0.234744E+11 | 0.418444E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75934313.16 | 0.618771E+10 |
Minimum of Months | 0.179968E+10 | 0.320774E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98286644.13 |
Maximum of Months | 0.199990E+10 | 0.356500E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22451870.35 | 0.116232E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.411401E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448073E+09 |
February | 0.208403E+10 | 0.371458E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342951E+09 |
March | 0.231589E+10 | 0.412669E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265409E+09 |
April | 0.223463E+10 | 0.397453E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1999890.55 | 0.179634E+09 |
May | 0.230993E+10 | 0.412115E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2321857.89 | 99343852.71 |
June | 0.223950E+10 | 0.399276E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12300179.31 | 53612476.01 |
July | 0.230505E+10 | 0.410292E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11055162.81 | 35477106.85 |
August | 0.231480E+10 | 0.412828E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10790979.63 | 45659347.05 |
September | 0.223354E+10 | 0.397611E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6874292.38 | 91419739.82 |
October | 0.230614E+10 | 0.411243E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20318.85 | 0.177720E+09 |
November | 0.222975E+10 | 0.398959E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264600E+09 |
December | 0.230505E+10 | 0.410292E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374840E+09 |
Annual Sum or Average | 0.271834E+11 | 0.484560E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45362681.43 | 0.237874E+10 |
Minimum of Months | 0.208403E+10 | 0.371458E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35477106.85 |
Maximum of Months | 0.231589E+10 | 0.412828E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12300179.31 | 0.448073E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.736067E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105984E+10 |
February | 0.440737E+09 | 0.664602E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815304E+09 |
March | 0.489771E+09 | 0.738336E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643766E+09 |
April | 0.472586E+09 | 0.711111E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3057358.12 | 0.454364E+09 |
May | 0.488511E+09 | 0.737344E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2950420.32 | 0.279438E+09 |
June | 0.473617E+09 | 0.714372E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20247112.11 | 0.152873E+09 |
July | 0.487480E+09 | 0.734082E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15419783.77 | 0.102611E+09 |
August | 0.489542E+09 | 0.738620E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15570505.01 | 0.127688E+09 |
September | 0.472357E+09 | 0.711395E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11216977.41 | 0.247972E+09 |
October | 0.487709E+09 | 0.735784E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464109E+09 |
November | 0.471555E+09 | 0.713805E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650007E+09 |
December | 0.487480E+09 | 0.734082E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888141E+09 |
Annual Sum or Average | 0.574883E+10 | 0.866960E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68462156.73 | 0.588612E+10 |
Minimum of Months | 0.440737E+09 | 0.664602E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102611E+09 |
Maximum of Months | 0.489771E+09 | 0.738620E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20247112.11 | 0.105984E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.168723E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610252E+09 |
February | 0.339028E+09 | 0.152342E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465471E+09 |
March | 0.376747E+09 | 0.169243E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356571E+09 |
April | 0.363528E+09 | 0.163003E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3328326.01 | 0.235882E+09 |
May | 0.375778E+09 | 0.169016E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3949137.74 | 0.122132E+09 |
June | 0.364321E+09 | 0.163750E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19560678.91 | 63373533.07 |
July | 0.374985E+09 | 0.168268E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18517108.98 | 38586029.91 |
August | 0.376571E+09 | 0.169308E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17875724.43 | 51600148.51 |
September | 0.363352E+09 | 0.163068E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11212894.97 | 0.112588E+09 |
October | 0.375161E+09 | 0.168658E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94413.73 | 0.229696E+09 |
November | 0.362735E+09 | 0.163620E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355079E+09 |
December | 0.374985E+09 | 0.168268E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509683E+09 |
Annual Sum or Average | 0.442217E+10 | 0.198727E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74538284.77 | 0.315091E+10 |
Minimum of Months | 0.339028E+09 | 0.152342E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38586029.91 |
Maximum of Months | 0.376747E+09 | 0.169308E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19560678.91 | 0.610252E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.314027E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157209E+10 |
February | 0.139600E+10 | 0.283537E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121476E+10 |
March | 0.155131E+10 | 0.314994E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965092E+09 |
April | 0.149688E+10 | 0.303380E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 4174854.27 | 0.665458E+09 |
May | 0.154732E+10 | 0.314571E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 3989937.17 | 0.387424E+09 |
June | 0.150015E+10 | 0.304771E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 27646346.09 | 0.210259E+09 |
July | 0.154405E+10 | 0.313180E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 21056164.60 | 0.140105E+09 |
August | 0.155059E+10 | 0.315115E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 21261925.43 | 0.174345E+09 |
September | 0.149615E+10 | 0.303501E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 15316587.74 | 0.342799E+09 |
October | 0.154478E+10 | 0.313906E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660756E+09 |
November | 0.149361E+10 | 0.304529E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957844E+09 |
December | 0.154405E+10 | 0.313180E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133209E+10 |
Annual Sum or Average | 0.182090E+11 | 0.369869E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 93445815.30 | 0.862302E+10 |
Minimum of Months | 0.139600E+10 | 0.283537E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140105E+09 |
Maximum of Months | 0.155131E+10 | 0.315115E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 27646346.09 | 0.157209E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.647197E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256812E+10 |
February | 0.236489E+11 | 0.559594E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196803E+10 |
March | 0.262800E+11 | 0.571063E+09 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152286E+10 |
April | 0.253579E+11 | 0.504089E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10930399.33 | 0.102479E+10 |
May | 0.262123E+11 | 0.461716E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14268387.68 | 0.547561E+09 |
June | 0.254132E+11 | 0.431255E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80467605.59 | 0.285370E+09 |
July | 0.261570E+11 | 0.449496E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76176257.76 | 0.176538E+09 |
August | 0.262677E+11 | 0.488373E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69197928.66 | 0.233826E+09 |
September | 0.253456E+11 | 0.533364E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37762109.00 | 0.503180E+09 |
October | 0.261693E+11 | 0.604041E+09 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101612E+10 |
November | 0.253025E+11 | 0.616252E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151487E+10 |
December | 0.261570E+11 | 0.656893E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215056E+10 |
Annual Sum or Average | 0.308468E+12 | 0.652333E+10 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288803E+09 | 0.135118E+11 |
Minimum of Months | 0.236489E+11 | 0.431255E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176538E+09 |
Maximum of Months | 0.262800E+11 | 0.656893E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80467605.59 | 0.256812E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.679431E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739859E+10 |
February | 0.702046E+11 | 0.609647E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568947E+10 |
March | 0.780153E+11 | 0.670357E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445322E+10 |
April | 0.752779E+11 | 0.639280E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30758359.83 | 0.303678E+10 |
May | 0.778146E+11 | 0.654273E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35394682.59 | 0.171072E+10 |
June | 0.754422E+11 | 0.631293E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198347E+09 | 0.927597E+09 |
July | 0.776503E+11 | 0.649389E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178857E+09 | 0.613798E+09 |
August | 0.779788E+11 | 0.658796E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170428E+09 | 0.784597E+09 |
September | 0.752414E+11 | 0.643346E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106434E+09 | 0.156572E+10 |
October | 0.776868E+11 | 0.672794E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47691.74 | 0.303433E+10 |
November | 0.751137E+11 | 0.657186E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443524E+10 |
December | 0.776503E+11 | 0.679642E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622257E+10 |
Annual Sum or Average | 0.915726E+12 | 0.784543E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720267E+09 | 0.398726E+11 |
Minimum of Months | 0.702046E+11 | 0.609647E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613798E+09 |
Maximum of Months | 0.780153E+11 | 0.679642E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198347E+09 | 0.739859E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664035E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508507E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393429E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3055157.44 | 0.263075E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3309478.94 | 0.140046E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21092598.84 | 67444833.78 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19601280.51 | 36405352.39 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18200147.93 | 50568179.09 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11205953.82 | 0.122902E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13741.04 | 0.259148E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389092E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555058E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76478358.51 | 0.344971E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36405352.39 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21092598.84 | 0.664035E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662575E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505764E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389715E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2892450.84 | 0.262561E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3016556.57 | 0.144725E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19615493.54 | 74957079.56 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17627488.87 | 46807482.45 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16669231.67 | 59836427.14 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10523598.89 | 0.126314E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2991.24 | 0.255471E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386347E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552286E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70347811.62 | 0.346736E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46807482.45 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19615493.54 | 0.662575E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162080E+09 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132345E+09 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111402E+09 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171612.91 | 92420341.78 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 132064.69 | 63169863.84 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446300.43 | 37950482.23 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 543936.49 | 29341727.85 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 769263.75 | 34028069.58 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 705114.42 | 55816958.75 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97929628.59 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118480E+09 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136480E+09 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3768292.68 | 0.107144E+10 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29341727.85 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446300.43 | 0.162080E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186091E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142416E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110143E+09 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 837877.28 | 73625774.09 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 883096.21 | 39516333.61 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5596848.43 | 20002807.26 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081553.44 | 11813390.27 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4850287.60 | 15588115.48 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3072618.27 | 34832156.08 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13396.54 | 72055314.61 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109322E+09 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155561E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20335677.76 | 0.970968E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11813390.27 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5596848.43 | 0.186091E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663969E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508552E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394647E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057394.36 | 0.263739E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3310233.01 | 0.141365E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21073855.68 | 68018188.24 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19609361.03 | 36795708.78 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18190861.41 | 51025674.24 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11215399.22 | 0.123823E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14491.13 | 0.260126E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388961E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554630E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76471595.85 | 0.345565E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36795708.78 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21073855.68 | 0.663969E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662643E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505756E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390728E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2886625.21 | 0.262629E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2980059.65 | 0.145137E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19446085.98 | 74935652.54 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17510596.86 | 47003108.38 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16581574.54 | 59343048.49 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10463448.34 | 0.126880E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5402.49 | 0.255626E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386125E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552231E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69873793.08 | 0.346904E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47003108.38 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19446085.98 | 0.662643E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.115875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814807E+09 |
February | 0.348285E+10 | 0.104624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621639E+09 |
March | 0.387034E+10 | 0.116232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477380E+09 |
April | 0.373454E+10 | 0.111946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3787492.21 | 0.319831E+09 |
May | 0.386038E+10 | 0.116076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4117392.24 | 0.175692E+09 |
June | 0.374269E+10 | 0.112460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21069703.37 | 95478698.59 |
July | 0.385223E+10 | 0.115562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17715197.31 | 63172434.45 |
August | 0.386853E+10 | 0.116277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17942870.40 | 80298910.90 |
September | 0.373273E+10 | 0.111991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11742066.50 | 0.161906E+09 |
October | 0.385404E+10 | 0.115830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71116.52 | 0.310064E+09 |
November | 0.372639E+10 | 0.112370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475268E+09 |
December | 0.385223E+10 | 0.115562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680679E+09 |
Annual Sum or Average | 0.454292E+11 | 0.136481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76445838.54 | 0.427622E+10 |
Minimum of Months | 0.348285E+10 | 0.104624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63172434.45 |
Maximum of Months | 0.387034E+10 | 0.116277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21069703.37 | 0.814807E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664346E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508187E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392474E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2998773.77 | 0.262977E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3235169.43 | 0.140872E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20741601.47 | 67918674.12 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19152887.61 | 36886808.16 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17824132.97 | 51045394.75 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10998798.13 | 0.123037E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12353.94 | 0.258749E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388413E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554742E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74963717.32 | 0.344965E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36886808.16 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20741601.47 | 0.664346E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663544E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505920E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389137E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2842457.41 | 0.262624E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2944189.68 | 0.146567E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19300632.29 | 76526964.37 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17233580.63 | 48202237.30 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16348114.98 | 61050457.18 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10344819.47 | 0.126627E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3592.92 | 0.254707E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385993E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552940E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69017387.38 | 0.347384E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48202237.30 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19300632.29 | 0.663544E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343760E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263682E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204421E+09 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1534130.14 | 0.135894E+09 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1659881.42 | 72454253.45 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10637767.33 | 34933670.90 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9836518.45 | 18823917.84 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9128056.03 | 26118176.18 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621230.91 | 63755265.31 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3520.72 | 0.135118E+09 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202237E+09 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287798E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38421104.99 | 0.178900E+10 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18823917.84 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10637767.33 | 0.343760E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.131779E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167379E+10 |
February | 0.415303E+11 | 0.116701E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128508E+10 |
March | 0.461508E+11 | 0.124462E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100686E+10 |
April | 0.445315E+11 | 0.115169E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7621531.98 | 0.686547E+09 |
May | 0.460320E+11 | 0.113206E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8206469.95 | 0.388555E+09 |
June | 0.446286E+11 | 0.107858E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46100734.12 | 0.210042E+09 |
July | 0.459349E+11 | 0.111717E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42962364.79 | 0.136177E+09 |
August | 0.461292E+11 | 0.116057E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42466472.25 | 0.171976E+09 |
September | 0.445099E+11 | 0.118148E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28046463.90 | 0.345721E+09 |
October | 0.459565E+11 | 0.127574E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135821.94 | 0.673476E+09 |
November | 0.444343E+11 | 0.126732E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999340E+09 |
December | 0.459349E+11 | 0.133141E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140726E+10 |
Annual Sum or Average | 0.541708E+12 | 0.144254E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175540E+09 | 0.898484E+10 |
Minimum of Months | 0.415303E+11 | 0.107858E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136177E+09 |
Maximum of Months | 0.461508E+11 | 0.133141E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46100734.12 | 0.167379E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.131779E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168526E+10 |
February | 0.415303E+11 | 0.116701E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129626E+10 |
March | 0.461508E+11 | 0.124462E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102262E+10 |
April | 0.445315E+11 | 0.115169E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7097480.85 | 0.701519E+09 |
May | 0.460320E+11 | 0.113206E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7341698.43 | 0.400402E+09 |
June | 0.446286E+11 | 0.107858E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42866053.34 | 0.217537E+09 |
July | 0.459349E+11 | 0.111717E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38860376.03 | 0.142568E+09 |
August | 0.461292E+11 | 0.116057E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38804020.13 | 0.178744E+09 |
September | 0.445099E+11 | 0.118148E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26126411.44 | 0.355707E+09 |
October | 0.459565E+11 | 0.127574E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74927.97 | 0.690566E+09 |
November | 0.444343E+11 | 0.126732E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101372E+10 |
December | 0.459349E+11 | 0.133141E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141968E+10 |
Annual Sum or Average | 0.541708E+12 | 0.144254E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161171E+09 | 0.912459E+10 |
Minimum of Months | 0.415303E+11 | 0.107858E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142568E+09 |
Maximum of Months | 0.461508E+11 | 0.133141E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42866053.34 | 0.168526E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.775957E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160567E+10 |
February | 0.369574E+10 | 0.700619E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124063E+10 |
March | 0.410691E+10 | 0.778349E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987052E+09 |
April | 0.396281E+10 | 0.749649E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4132432.13 | 0.681477E+09 |
May | 0.409635E+10 | 0.777303E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3921048.29 | 0.398233E+09 |
June | 0.397146E+10 | 0.753087E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 27426786.99 | 0.216987E+09 |
July | 0.408770E+10 | 0.773865E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 20598662.33 | 0.145510E+09 |
August | 0.410499E+10 | 0.778648E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 20901620.35 | 0.180489E+09 |
September | 0.396089E+10 | 0.749948E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 15179235.90 | 0.352361E+09 |
October | 0.408962E+10 | 0.775658E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676918E+09 |
November | 0.395417E+10 | 0.752489E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979571E+09 |
December | 0.408770E+10 | 0.773865E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136111E+10 |
Annual Sum or Average | 0.482060E+11 | 0.913943E+10 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 92159786.00 | 0.882600E+10 |
Minimum of Months | 0.369574E+10 | 0.700619E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145510E+09 |
Maximum of Months | 0.410691E+10 | 0.778648E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27426786.99 | 0.160567E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.122636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144457E+10 |
February | 0.368610E+10 | 0.110729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110326E+10 |
March | 0.409620E+10 | 0.123014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855874E+09 |
April | 0.395248E+10 | 0.118478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4053715.99 | 0.592358E+09 |
May | 0.408566E+10 | 0.122848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3877170.71 | 0.364931E+09 |
June | 0.396110E+10 | 0.119021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26761472.96 | 0.203959E+09 |
July | 0.407704E+10 | 0.122305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20064029.88 | 0.141052E+09 |
August | 0.409429E+10 | 0.123061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20371669.72 | 0.174688E+09 |
September | 0.395056E+10 | 0.118525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14806905.28 | 0.320294E+09 |
October | 0.407896E+10 | 0.122588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.85 | 0.577890E+09 |
November | 0.394385E+10 | 0.118927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853462E+09 |
December | 0.407704E+10 | 0.122305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120725E+10 |
Annual Sum or Average | 0.480803E+11 | 0.144444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89935185.39 | 0.783959E+10 |
Minimum of Months | 0.368610E+10 | 0.110729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141052E+09 |
Maximum of Months | 0.409620E+10 | 0.123061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26761472.96 | 0.144457E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 7561.54 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 7561.54 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 7561.54 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 7561.54 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 7561.54 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 7561.54 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 7561.54 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 7561.54 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 7561.54 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 7561.54 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 7561.54 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 7561.54 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 7561.54 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 7561.54 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 342.20 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 721.14 | 31-JAN-04:00 |
February | 1169.53 | 01-FEB-00:10 | 342.20 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 824.24 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 342.20 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 499.55 | 06-MAR-01:00 |
April | 1169.53 | 01-APR-00:10 | 342.20 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.14 | 15-APR-15:10 | 356.10 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 342.20 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 | 31-MAY-13:00 | 251.15 | 03-MAY-03:00 |
June | 1169.53 | 01-JUN-00:10 | 342.20 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.26 | 11-JUN-15:00 | 206.97 | 01-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 342.20 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.04 | 26-JUL-15:10 | 147.75 | 24-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 342.20 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.43 | 04-AUG-15:00 | 163.82 | 07-AUG-04:00 |
September | 1169.53 | 01-SEP-00:10 | 342.20 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.71 | 06-SEP-14:20 | 272.34 | 30-SEP-01:00 |
October | 1169.53 | 01-OCT-23:10 | 342.20 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 304.04 | 23-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 342.20 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 679.54 | 26-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 342.20 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 587.35 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 342.20 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.75 | |||||
Maximum of Months | 1169.53 | 342.20 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 106.43 | 824.24 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 396.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 278.34 | 31-JAN-04:00 |
February | 1354.32 | 01-FEB-00:10 | 396.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 318.14 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 396.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 192.82 | 06-MAR-01:00 |
April | 1354.32 | 01-APR-00:10 | 396.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 | 15-APR-16:00 | 137.46 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 396.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.45 | 31-MAY-13:00 | 101.07 | 03-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 396.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.88 | 11-JUN-15:00 | 82.68 | 01-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 396.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 | 26-JUL-15:00 | 58.94 | 24-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 396.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.48 | 04-AUG-15:00 | 66.73 | 07-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 396.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.92 | 06-SEP-14:00 | 108.66 | 30-SEP-01:00 |
October | 1354.32 | 01-OCT-23:10 | 396.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 | 20-OCT-15:00 | 120.69 | 23-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 396.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 262.29 | 26-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 396.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 226.72 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 396.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.94 | |||||
Maximum of Months | 1354.32 | 396.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 45.48 | 318.14 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 708.98 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 657.81 | 31-JAN-04:00 |
February | 286.42 | 01-FEB-00:10 | 708.98 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 751.87 | 02-FEB-07:10 |
March | 286.42 | 01-MAR-00:10 | 708.98 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 455.71 | 06-MAR-01:00 |
April | 286.42 | 01-APR-00:10 | 708.98 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.42 | 15-APR-15:00 | 330.04 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 708.98 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.80 | 31-MAY-13:00 | 249.68 | 03-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 708.98 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.46 | 11-JUN-15:00 | 205.84 | 01-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 708.98 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.24 | 26-JUL-15:00 | 151.09 | 23-JUL-04:00 |
August | 286.42 | 01-AUG-00:10 | 708.98 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.09 | 04-AUG-15:00 | 170.24 | 07-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 708.98 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.85 | 07-SEP-14:00 | 272.20 | 30-SEP-01:00 |
October | 286.42 | 01-OCT-23:10 | 708.98 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 302.60 | 23-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 708.98 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 619.89 | 26-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 708.98 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 535.80 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.09 | |||||
Maximum of Months | 286.42 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 97.09 | 751.87 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 162.52 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 379.52 | 31-JAN-04:00 |
February | 220.32 | 01-FEB-00:10 | 162.52 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 433.79 | 02-FEB-06:20 |
March | 220.32 | 01-MAR-00:10 | 162.52 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 262.92 | 06-MAR-01:00 |
April | 220.32 | 01-APR-00:10 | 162.52 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.84 | 15-APR-17:00 | 187.43 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 162.52 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 31-MAY-13:00 | 132.19 | 03-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 162.52 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.37 | 11-JUN-15:00 | 105.49 | 01-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 162.52 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.41 | 26-JUL-16:00 | 72.96 | 24-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 162.52 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.66 | 04-AUG-16:00 | 84.56 | 07-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 162.52 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.23 | 06-SEP-14:30 | 143.33 | 30-SEP-01:00 |
October | 220.32 | 01-OCT-23:10 | 162.52 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 | 20-OCT-15:00 | 160.01 | 23-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 162.52 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 357.64 | 26-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 162.52 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 309.13 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 162.52 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.96 | |||||
Maximum of Months | 220.32 | 162.52 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 64.66 | 433.79 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 302.47 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 949.90 | 31-JAN-04:00 |
February | 907.20 | 01-FEB-00:10 | 302.47 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1079.99 | 02-FEB-08:00 |
March | 907.20 | 01-MAR-00:10 | 302.47 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 671.12 | 06-MAR-01:00 |
April | 907.20 | 01-APR-00:10 | 302.47 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 81.15 | 15-APR-15:10 | 490.74 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 302.47 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 81.65 | 31-MAY-13:00 | 358.87 | 03-MAY-03:00 |
June | 907.20 | 01-JUN-00:10 | 302.47 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 124.89 | 11-JUN-15:00 | 282.52 | 03-JUN-04:00 |
July | 907.20 | 01-JUL-00:10 | 302.47 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 82.28 | 26-JUL-15:10 | 206.30 | 23-JUL-04:00 |
August | 907.20 | 01-AUG-00:10 | 302.47 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 132.58 | 04-AUG-15:10 | 232.44 | 07-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 302.47 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 111.77 | 07-SEP-14:00 | 385.26 | 30-SEP-01:00 |
October | 907.20 | 01-OCT-23:10 | 302.47 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 425.43 | 23-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 302.47 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 897.30 | 26-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 302.47 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 781.72 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 206.30 | ||||||
Maximum of Months | 907.20 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 132.58 | 1079.99 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 810.33 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1594.04 | 31-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 810.33 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1822.13 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 810.33 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1104.42 | 06-MAR-01:00 |
April | 15368.40 | 01-APR-00:10 | 810.33 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.38 | 15-APR-17:00 | 787.37 | 03-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 810.33 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.61 | 31-MAY-13:00 | 581.72 | 03-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 810.33 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.55 | 11-JUN-15:00 | 465.17 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 810.33 | 03-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.30 | 26-JUL-18:00 | 331.29 | 24-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 810.33 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.76 | 04-AUG-16:00 | 374.07 | 07-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 810.33 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.89 | 06-SEP-15:00 | 623.15 | 30-SEP-01:00 |
October | 15368.40 | 01-OCT-23:10 | 810.33 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 673.01 | 23-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 810.33 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1502.20 | 26-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 810.33 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1298.43 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 810.33 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.29 | |||||
Maximum of Months | 15368.40 | 810.33 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 261.76 | 1822.13 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 6817.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4554.42 | 31-JAN-04:00 |
February | 45622.98 | 01-FEB-00:10 | 6817.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5205.73 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 6817.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 3222.35 | 06-MAR-01:00 |
April | 45622.98 | 01-APR-00:10 | 6817.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.31 | 15-APR-16:00 | 2326.28 | 03-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 6817.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 523.52 | 31-MAY-13:00 | 1723.85 | 03-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 6817.32 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 737.06 | 11-JUN-15:00 | 1394.92 | 01-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 6817.32 | 03-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.89 | 26-JUL-15:00 | 1007.90 | 24-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 6817.32 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 738.84 | 04-AUG-15:00 | 1134.12 | 07-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 6817.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.64 | 06-SEP-14:00 | 1857.18 | 30-SEP-01:00 |
October | 45622.98 | 01-OCT-23:10 | 6817.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 | 20-OCT-15:00 | 2035.45 | 23-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 6817.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4291.95 | 26-NOV-07:00 |
December | 45622.98 | 01-DEC-00:10 | 6817.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3743.84 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 6817.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.90 | |||||
Maximum of Months | 45622.98 | 6817.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 738.84 | 5205.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 419.75 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 479.64 | 02-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 291.11 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.74 | 15-APR-15:20 | 207.81 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | 31-MAY-15:20 | 146.87 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 11-JUN-15:20 | 111.92 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 | 26-JUL-15:20 | 76.59 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 04-AUG-15:20 | 88.68 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 06-SEP-15:20 | 159.16 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 20-OCT-15:20 | 177.57 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.61 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 342.10 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 479.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 419.72 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 479.61 | 02-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 291.09 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.74 | 15-APR-15:20 | 207.79 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | 31-MAY-15:20 | 146.86 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.94 | 11-JUN-15:20 | 111.91 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 | 26-JUL-15:20 | 76.58 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.51 | 04-AUG-15:20 | 88.67 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.87 | 06-SEP-15:20 | 159.15 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 20-OCT-12:50 | 177.55 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.58 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 342.08 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.58 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.51 | 479.61 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 104.67 | 31-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 120.98 | 02-FEB-07:54 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 70.98 | 06-MAR-01:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 15-APR-15:00 | 62.60 | 01-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 31-MAY-13:00 | 49.96 | 03-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 11-JUN-15:00 | 41.68 | 01-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 26-JUL-15:00 | 31.98 | 24-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 04-AUG-15:00 | 35.43 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | 07-SEP-14:00 | 52.28 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 58.25 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 100.73 | 26-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 90.02 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.98 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 120.98 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 117.15 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 133.86 | 02-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 81.25 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 15-APR-15:20 | 58.00 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 31-MAY-15:20 | 40.99 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 11-JUN-15:20 | 31.24 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 26-JUL-15:20 | 21.37 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.19 | 04-AUG-15:20 | 24.75 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 06-SEP-15:20 | 44.42 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 20-OCT-15:00 | 49.56 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 110.41 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 95.48 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.19 | 133.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 419.75 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 479.64 | 02-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 291.11 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.75 | 15-APR-15:17 | 207.81 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | 31-MAY-15:20 | 146.87 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 11-JUN-15:20 | 111.92 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 | 26-JUL-15:18 | 76.59 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 04-AUG-15:20 | 88.68 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.87 | 06-SEP-15:20 | 159.16 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 20-OCT-15:19 | 177.57 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.61 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 342.09 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 479.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 419.72 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 479.60 | 02-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 291.08 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.74 | 15-APR-15:17 | 207.79 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | 31-MAY-15:20 | 146.86 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.94 | 11-JUN-15:20 | 111.91 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 | 26-JUL-15:18 | 76.58 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.51 | 04-AUG-15:20 | 88.67 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.87 | 06-SEP-15:18 | 159.15 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 20-OCT-15:00 | 177.55 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.58 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 342.07 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.58 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.51 | 479.60 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1116.11 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 506.51 | 31-JAN-04:00 |
February | 2263.36 | 01-FEB-00:10 | 1116.11 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 578.90 | 02-FEB-06:40 |
March | 2263.36 | 01-MAR-00:10 | 1116.11 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 351.00 | 06-MAR-01:00 |
April | 2263.36 | 01-APR-00:10 | 1116.11 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.58 | 15-APR-16:00 | 250.31 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1116.11 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.71 | 31-MAY-13:00 | 178.98 | 03-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1116.11 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.59 | 11-JUN-15:00 | 147.07 | 01-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1116.11 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.68 | 26-JUL-16:00 | 106.03 | 24-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1116.11 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.81 | 04-AUG-16:00 | 120.87 | 07-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1116.11 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.61 | 06-SEP-14:00 | 191.96 | 30-SEP-01:00 |
October | 2263.36 | 01-OCT-23:10 | 1116.11 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 20-OCT-15:00 | 213.75 | 23-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1116.11 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 477.33 | 26-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1116.11 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 412.63 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1116.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.03 | ||||
Maximum of Months | 2263.36 | 1116.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.81 | 578.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 420.34 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 480.25 | 02-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 291.62 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 15-APR-16:40 | 208.29 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.18 | 31-MAY-15:20 | 147.33 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 | 11-JUN-15:20 | 112.36 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.15 | 26-JUL-15:20 | 77.01 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 04-AUG-15:20 | 89.10 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.37 | 06-SEP-15:20 | 159.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | 20-OCT-15:20 | 178.04 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 396.17 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 342.65 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.01 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 480.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 420.30 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 480.22 | 02-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 291.60 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 15-APR-15:20 | 208.28 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 | 31-MAY-15:20 | 147.31 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.57 | 11-JUN-15:20 | 112.35 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 | 26-JUL-15:20 | 77.01 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.12 | 04-AUG-16:00 | 89.10 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 06-SEP-15:20 | 159.61 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 | 20-OCT-12:50 | 178.03 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 396.15 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 342.62 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.01 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.12 | 480.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 215.05 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 245.71 | 02-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 149.21 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 15-APR-16:10 | 106.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.70 | 31-MAY-15:20 | 75.38 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.16 | 11-JUN-15:20 | 57.49 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 | 26-JUL-15:20 | 39.40 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 04-AUG-15:20 | 45.59 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.53 | 06-SEP-15:20 | 81.67 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 | 20-OCT-15:20 | 91.09 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 202.70 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 175.31 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.40 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 245.71 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1423.01 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1027.85 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 1423.01 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1170.65 | 02-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 1423.01 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 729.02 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 1423.01 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.95 | 15-APR-16:00 | 529.16 | 03-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 1423.01 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.62 | 31-MAY-13:00 | 389.93 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 1423.01 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.71 | 11-JUN-15:00 | 312.49 | 01-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 1423.01 | 03-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.46 | 26-JUL-15:00 | 225.76 | 24-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 1423.01 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.99 | 04-AUG-15:00 | 253.99 | 07-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 1423.01 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.09 | 06-SEP-14:00 | 418.03 | 30-SEP-01:00 |
October | 26988.77 | 01-OCT-23:10 | 1423.01 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.08 | 20-OCT-15:00 | 459.85 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 1423.01 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 969.79 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 1423.01 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 857.12 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1423.01 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.76 | |||||
Maximum of Months | 26988.77 | 1423.01 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 170.99 | 1170.65 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1423.01 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1033.28 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 1423.01 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1170.59 | 02-FEB-06:50 |
March | 26988.77 | 01-MAR-00:10 | 1423.01 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 735.25 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 1423.01 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.72 | 15-APR-16:00 | 535.20 | 03-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 1423.01 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.22 | 31-MAY-13:00 | 395.32 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 1423.01 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.22 | 11-JUN-15:00 | 315.83 | 01-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 1423.01 | 03-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.17 | 26-JUL-15:00 | 229.16 | 24-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 1423.01 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.84 | 04-AUG-15:00 | 257.43 | 07-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 1423.01 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.06 | 06-SEP-14:00 | 424.11 | 30-SEP-01:00 |
October | 26988.77 | 01-OCT-23:10 | 1423.01 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 20-OCT-15:00 | 466.05 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 1423.01 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 975.19 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 1423.01 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 863.69 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1423.01 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.16 | |||||
Maximum of Months | 26988.77 | 1423.01 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 166.84 | 1170.59 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 747.41 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 965.61 | 31-JAN-04:10 |
February | 2401.70 | 01-FEB-00:10 | 747.41 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1102.12 | 02-FEB-08:00 |
March | 2401.70 | 01-MAR-00:10 | 747.41 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 685.36 | 06-MAR-01:00 |
April | 2401.70 | 01-APR-00:10 | 747.41 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 81.45 | 15-APR-16:50 | 501.46 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 747.41 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 81.92 | 31-MAY-13:00 | 367.13 | 03-MAY-03:00 |
June | 2401.70 | 01-JUN-00:10 | 747.41 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 125.98 | 11-JUN-15:00 | 289.31 | 03-JUN-04:00 |
July | 2401.70 | 01-JUL-00:10 | 747.41 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 82.60 | 26-JUL-15:50 | 211.65 | 23-JUL-04:00 |
August | 2401.70 | 01-AUG-00:10 | 747.41 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 133.83 | 04-AUG-15:50 | 238.22 | 07-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 747.41 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 112.57 | 06-SEP-14:30 | 394.03 | 30-SEP-01:00 |
October | 2401.70 | 01-OCT-23:10 | 747.41 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 434.91 | 23-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 747.41 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 915.80 | 26-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 747.41 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 798.07 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 747.41 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 211.65 | ||||||
Maximum of Months | 2401.70 | 747.41 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 133.83 | 1102.12 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1181.23 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 897.44 | 31-JAN-04:00 |
February | 2395.44 | 01-FEB-00:10 | 1181.23 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1025.59 | 02-FEB-06:40 |
March | 2395.44 | 01-MAR-00:10 | 1181.23 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 622.14 | 06-MAR-01:00 |
April | 2395.44 | 01-APR-00:10 | 1181.23 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 15-APR-15:00 | 443.91 | 03-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1181.23 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 31-MAY-13:00 | 326.12 | 03-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1181.23 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.16 | 11-JUN-15:00 | 276.92 | 01-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1181.23 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.62 | 26-JUL-15:10 | 202.41 | 24-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1181.23 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.82 | 04-AUG-15:00 | 225.07 | 07-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1181.23 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.05 | 07-SEP-14:00 | 345.62 | 30-SEP-01:00 |
October | 2395.44 | 01-OCT-23:10 | 1181.23 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 20-OCT-15:00 | 382.72 | 23-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1181.23 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 845.79 | 26-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1181.23 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 731.27 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1181.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.41 | ||||
Maximum of Months | 2395.44 | 1181.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.82 | 1025.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12249.76 | 13-JAN-21:00 | 8945.92 | 7561.54 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14448.11 | 02-FEB-07:00 | 8945.92 | 3360.63 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11031.47 | 01-MAR-21:00 | 8945.92 | 7561.54 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11355.52 | 15-APR-18:10 | 53675.50 | 41168.55 | 56781.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12007.36 | 31-MAY-18:10 | 53675.50 | 40328.28 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13083.58 | 25-JUN-10:35 | 7667.93 | 5040.95 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13877.41 | 30-JUL-10:35 | 7667.93 | 5040.95 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14509.32 | 27-AUG-10:35 | 7667.93 | 5040.95 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15031.78 | 17-SEP-10:35 | 7667.93 | 5040.95 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14604.75 | 25-OCT-21:00 | 10223.90 | 6721.38 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14462.29 | 01-NOV-21:00 | 10223.90 | 6721.38 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13460.91 | 01-DEC-21:00 | 8945.92 | 7561.54 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11031.47 | 7667.93 | 3360.63 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15031.78 | 53675.50 | 41168.55 | 56781.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1167.92 | 13-JAN-11:50 | 259.90 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.84 |
February | 1812.62 | 08-FEB-13:30 | 259.90 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.98 |
March | 1624.94 | 24-MAR-13:20 | 519.79 | 190.11 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.68 |
April | 2749.95 | 15-APR-13:30 | 389.84 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 52.87 | 0.00 |
May | 2172.57 | 31-MAY-13:30 | 259.90 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 0.00 |
June | 2530.64 | 30-JUN-13:00 | 259.90 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 | 0.00 |
July | 2634.61 | 30-JUL-12:00 | 389.84 | 114.07 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 29.96 | 0.00 |
August | 2780.02 | 04-AUG-14:10 | 389.84 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 101.24 | 0.00 |
September | 3525.45 | 07-SEP-13:00 | 259.90 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 84.39 | 0.00 |
October | 2907.33 | 20-OCT-13:00 | 259.90 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.74 |
November | 2691.96 | 04-NOV-13:00 | 389.84 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.71 |
December | 1861.27 | 03-DEC-13:00 | 389.84 | 114.07 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1167.92 | 259.90 | 95.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3525.45 | 519.79 | 190.11 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 101.24 | 256.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1124.37 | 13-JAN-21:00 | 1053.36 | 396.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.88 |
February | 1184.80 | 24-FEB-21:00 | 1053.36 | 396.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.18 |
March | 1260.36 | 24-MAR-20:00 | 1053.36 | 396.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.25 |
April | 1484.74 | 16-APR-10:35 | 902.88 | 264.18 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 0.00 |
May | 1559.85 | 31-MAY-18:10 | 6320.16 | 2113.41 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 0.00 |
June | 1624.33 | 26-JUN-18:10 | 6320.16 | 2113.41 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 0.00 |
July | 1621.28 | 03-JUL-18:10 | 6320.16 | 2113.41 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 | 0.00 |
August | 1587.76 | 03-AUG-18:10 | 6320.16 | 2113.41 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 0.00 |
September | 1604.61 | 07-SEP-18:10 | 6320.16 | 2113.41 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 |
October | 1377.08 | 20-OCT-20:00 | 1053.36 | 396.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.36 |
November | 1300.61 | 03-NOV-20:00 | 1053.36 | 396.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.25 |
December | 1096.64 | 01-DEC-21:00 | 1053.36 | 396.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1096.64 | 902.88 | 264.18 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1624.33 | 6320.16 | 2113.41 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 127.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18.27 | 13-JAN-21:00 | 222.77 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.88 |
February | 19.51 | 24-FEB-21:00 | 222.77 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.75 |
March | 22.24 | 28-MAR-20:00 | 222.77 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.52 |
April | 951.10 | 18-APR-20:00 | 222.77 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.08 |
May | 1174.75 | 31-MAY-21:00 | 254.59 | 630.21 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 |
June | 1422.58 | 26-JUN-21:00 | 254.59 | 630.21 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 | 0.00 |
July | 1372.09 | 03-JUL-21:00 | 254.59 | 630.21 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 0.00 |
August | 1368.61 | 04-AUG-20:00 | 222.77 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 |
September | 1287.89 | 07-SEP-20:00 | 222.77 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
October | 463.89 | 11-OCT-20:00 | 222.77 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.82 |
November | 400.61 | 08-NOV-22:00 | 254.59 | 630.21 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.07 |
December | 18.01 | 04-DEC-21:00 | 222.77 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18.01 | 222.77 | 630.21 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1422.58 | 254.59 | 708.98 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 | 251.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 224.94 | 13-JAN-22:00 | 195.84 | 144.46 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.03 |
February | 331.94 | 24-FEB-22:00 | 195.84 | 144.46 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.16 |
March | 617.59 | 28-MAR-21:00 | 195.84 | 144.46 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.63 |
April | 865.09 | 16-APR-10:35 | 146.88 | 108.35 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 9.71 | 0.00 |
May | 895.36 | 31-MAY-10:35 | 97.92 | 90.28 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 | 0.00 |
June | 946.20 | 30-JUN-10:35 | 97.92 | 90.28 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 | 0.00 |
July | 955.67 | 02-JUL-10:35 | 146.88 | 108.35 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 32.29 | 0.00 |
August | 934.02 | 04-AUG-10:35 | 97.92 | 90.28 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 | 0.00 |
September | 926.51 | 08-SEP-10:35 | 97.92 | 90.28 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 36.45 | 0.00 |
October | 719.74 | 21-OCT-10:35 | 146.88 | 90.28 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 |
November | 669.32 | 03-NOV-20:00 | 171.36 | 162.52 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.85 |
December | 174.30 | 04-DEC-22:00 | 195.84 | 144.46 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 174.30 | 97.92 | 90.28 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 955.67 | 195.84 | 162.52 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 | 121.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36741.42 | 13-JAN-21:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 369.22 |
February | 37074.51 | 24-FEB-21:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 326.98 |
March | 37554.05 | 28-MAR-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 177.49 |
April | 38480.61 | 18-APR-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.67 |
May | 38810.07 | 31-MAY-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.49 | 0.00 |
June | 39016.13 | 26-JUN-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 37.66 | 0.00 |
July | 38865.55 | 03-JUL-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 37.19 | 0.00 |
August | 38885.55 | 03-AUG-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 13.76 | 0.00 |
September | 38912.18 | 07-SEP-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
October | 37992.04 | 20-OCT-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 128.41 |
November | 37618.12 | 03-NOV-20:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 240.86 |
December | 36509.33 | 04-DEC-21:00 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 332.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36509.33 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39016.13 | 705.60 | 302.47 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 37.66 | 369.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8536.42 | 13-JAN-11:35 | 6830.40 | 99.04 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.03 |
February | 9626.20 | 08-FEB-11:40 | 3415.20 | 49.52 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.19 |
March | 9347.43 | 19-MAR-10:35 | 10245.60 | 118.85 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.46 |
April | 10936.87 | 16-APR-10:35 | 10245.60 | 118.85 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 | 0.00 |
May | 10677.19 | 31-MAY-18:10 | 71719.20 | 950.79 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 115.13 | 0.00 |
June | 11156.41 | 26-JUN-18:10 | 71719.20 | 950.79 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 175.82 | 0.00 |
July | 11285.04 | 30-JUL-10:35 | 10245.60 | 118.85 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 57.20 | 0.00 |
August | 11074.56 | 27-AUG-10:35 | 10245.60 | 118.85 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 78.91 | 0.00 |
September | 11856.45 | 09-SEP-10:35 | 10245.60 | 99.04 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 0.00 |
October | 10857.99 | 20-OCT-15:23 | 25614.00 | 148.56 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 |
November | 10795.40 | 04-NOV-10:35 | 10245.60 | 99.04 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.81 |
December | 9954.92 | 03-DEC-11:35 | 10245.60 | 118.85 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8536.42 | 3415.20 | 49.52 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11856.45 | 71719.20 | 950.79 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 175.82 | 529.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25373.43 | 13-JAN-22:00 | 40553.76 | 6059.84 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1545.19 |
February | 26350.50 | 24-FEB-21:00 | 35484.54 | 6817.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1550.83 |
March | 27580.83 | 24-MAR-20:00 | 35484.54 | 6817.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.59 |
April | 31513.27 | 16-APR-10:35 | 30415.32 | 3908.60 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 51.31 | 0.00 |
May | 32393.21 | 31-MAY-18:10 | 212907.24 | 31268.76 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 277.69 | 0.00 |
June | 34353.91 | 30-JUN-21:52 | 410606.82 | 40903.90 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.71 |
July | 33562.00 | 03-JUL-22:00 | 45622.98 | 4544.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.56 |
August | 33837.47 | 04-AUG-21:10 | 91245.96 | 9089.76 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.00 |
September | 35037.72 | 07-SEP-21:10 | 45622.98 | 4544.88 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.87 |
October | 29853.69 | 20-OCT-20:00 | 35484.54 | 6817.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.75 |
November | 28681.22 | 04-NOV-10:35 | 30415.32 | 3257.16 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.85 |
December | 25617.36 | 03-DEC-11:35 | 30415.32 | 3908.60 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25373.43 | 30415.32 | 3257.16 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35037.72 | 410606.82 | 40903.90 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 277.69 | 1550.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2792.22 | 12-JAN-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.63 |
February | 3235.05 | 24-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.06 |
March | 3232.53 | 22-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.21 |
April | 3258.05 | 26-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 |
May | 3284.19 | 21-MAY-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 |
June | 2943.27 | 07-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 |
July | 2909.09 | 24-JUL-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
August | 2937.34 | 27-AUG-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 0.00 |
September | 3246.35 | 20-SEP-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 |
October | 3263.06 | 19-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 |
November | 3269.49 | 04-NOV-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 |
December | 2187.02 | 02-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2187.02 | 378.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3284.19 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 130.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 949.17 | 12-JAN-16:13 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.02 |
February | 2980.25 | 24-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.76 |
March | 3072.79 | 24-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.15 |
April | 3153.21 | 26-APR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.27 |
May | 3508.67 | 20-MAY-18:41 | 1170.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 |
June | 3058.19 | 16-JUN-16:51 | 777.60 | 212.14 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
July | 3025.17 | 23-JUL-21:51 | 1386.00 | 805.00 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.53 |
August | 3329.02 | 11-AUG-18:11 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
September | 3407.75 | 24-SEP-16:11 | 858.60 | 281.28 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.61 |
October | 3066.81 | 29-OCT-15:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.85 |
November | 3145.04 | 04-NOV-15:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 |
December | 949.58 | 17-DEC-19:04 | 819.00 | 662.94 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 949.17 | 378.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 | |
Maximum of Months | 3508.67 | 1386.00 | 947.05 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 76.39 | 30-JAN-15:10 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.46 |
February | 108.34 | 02-FEB-15:10 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.98 |
March | 209.19 | 28-MAR-13:25 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 |
April | 445.80 | 15-APR-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
May | 330.60 | 06-MAY-13:00 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 |
June | 350.89 | 26-JUN-12:50 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 0.00 |
July | 376.39 | 30-JUL-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
August | 424.82 | 29-AUG-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
September | 529.09 | 07-SEP-13:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 0.00 |
October | 507.71 | 20-OCT-13:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 |
November | 479.89 | 04-NOV-13:00 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.38 |
December | 97.83 | 07-DEC-15:20 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 76.39 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 529.09 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 102.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 466.72 | 14-JAN-09:02 | 324.00 | 200.06 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 |
February | 908.34 | 26-FEB-09:01 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.10 |
March | 948.86 | 24-MAR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 |
April | 988.55 | 30-APR-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 |
May | 1025.12 | 06-MAY-19:31 | 1170.00 | 595.42 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 |
June | 980.29 | 21-JUN-21:01 | 1800.00 | 398.93 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 |
July | 963.56 | 13-JUL-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
August | 972.84 | 11-AUG-18:11 | 1386.00 | 529.92 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
September | 988.38 | 19-SEP-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
October | 941.27 | 19-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 |
November | 927.31 | 04-NOV-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.39 |
December | 666.40 | 03-DEC-09:01 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 466.72 | 324.00 | 200.06 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1025.12 | 1800.00 | 595.42 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 49.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 942.37 | 17-JAN-19:04 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.67 |
February | 2796.84 | 24-FEB-09:01 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.09 |
March | 2950.54 | 24-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.27 |
April | 2974.91 | 26-APR-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.84 |
May | 2935.57 | 02-MAY-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.82 |
June | 2767.32 | 28-JUN-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 0.00 |
July | 2767.08 | 28-JUL-08:61 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 |
August | 2715.80 | 10-AUG-08:62 | 216.00 | 250.05 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
September | 2920.44 | 30-SEP-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 |
October | 2950.47 | 24-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.40 |
November | 2966.72 | 04-NOV-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.62 |
December | 1697.83 | 03-DEC-09:01 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 942.37 | 216.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2974.91 | 970.20 | 590.08 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 160.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 956.99 | 17-JAN-19:04 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.66 |
February | 2214.40 | 24-FEB-09:01 | 252.00 | 291.69 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 |
March | 2443.38 | 24-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.33 |
April | 2901.72 | 26-APR-08:61 | 252.00 | 291.69 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.82 |
May | 2882.91 | 21-MAY-19:41 | 1170.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.56 |
June | 3081.94 | 20-JUN-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 |
July | 3083.74 | 19-JUL-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 |
August | 3092.54 | 09-AUG-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 |
September | 3049.51 | 06-SEP-08:51 | 360.00 | 416.70 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 |
October | 2238.78 | 01-OCT-08:61 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.21 |
November | 1684.90 | 04-NOV-08:62 | 270.00 | 265.18 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.15 |
December | 1090.59 | 05-DEC-09:03 | 252.00 | 291.69 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 956.99 | 252.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | |
Maximum of Months | 3092.54 | 1170.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1127.23 | 13-JAN-22:20 | 2263.36 | 744.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.19 |
February | 1298.96 | 24-FEB-20:30 | 1760.39 | 1116.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.23 |
March | 1502.02 | 20-MAR-10:35 | 1005.94 | 620.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.12 |
April | 1904.47 | 18-APR-10:35 | 1005.94 | 620.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 | 0.00 |
May | 1971.04 | 31-MAY-10:35 | 1005.94 | 620.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 0.00 |
June | 2112.09 | 29-JUN-18:10 | 10562.33 | 5952.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.56 | 0.00 |
July | 2161.92 | 02-JUL-10:35 | 1508.90 | 744.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.48 | 0.00 |
August | 2062.41 | 02-AUG-10:35 | 1005.94 | 620.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 | 0.00 |
September | 2087.10 | 09-SEP-10:35 | 1508.90 | 620.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 0.00 |
October | 1571.67 | 20-OCT-10:35 | 1005.94 | 620.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.43 |
November | 1552.75 | 04-NOV-10:35 | 1508.90 | 620.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.89 |
December | 1152.44 | 03-DEC-11:00 | 6287.10 | 1860.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1127.23 | 1005.94 | 620.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2161.92 | 10562.33 | 5952.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 161.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1903.71 | 12-JAN-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.72 |
February | 3348.96 | 24-FEB-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.30 |
March | 3339.68 | 24-MAR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.43 |
April | 3386.68 | 26-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.30 |
May | 3413.19 | 21-MAY-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 |
June | 3013.90 | 07-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
July | 3043.69 | 14-JUL-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 0.00 |
August | 3019.89 | 30-AUG-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 |
September | 3363.21 | 20-SEP-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 |
October | 3357.56 | 31-OCT-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.47 |
November | 3388.73 | 04-NOV-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.46 |
December | 1110.59 | 02-DEC-16:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1110.59 | 378.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3413.19 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 130.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 963.29 | 09-JAN-16:14 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.49 |
February | 3005.32 | 24-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.77 |
March | 3127.43 | 24-MAR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 |
April | 3264.23 | 26-APR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.68 |
May | 3791.01 | 21-MAY-19:41 | 1170.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.98 |
June | 3205.59 | 22-JUN-21:41 | 1800.00 | 634.53 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.27 |
July | 3292.42 | 23-JUL-21:51 | 1386.00 | 805.00 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.82 |
August | 3489.71 | 11-AUG-18:11 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 |
September | 3524.74 | 24-SEP-16:11 | 858.60 | 281.28 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.99 |
October | 3080.23 | 24-OCT-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.72 |
November | 3212.91 | 04-NOV-15:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 |
December | 1050.37 | 02-DEC-16:13 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 963.29 | 378.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 | |
Maximum of Months | 3791.01 | 1800.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1816.18 | 12-JAN-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.57 |
February | 1787.23 | 17-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.38 |
March | 1834.81 | 22-MAR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.80 |
April | 1831.21 | 26-APR-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.90 |
May | 1770.09 | 21-MAY-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
June | 1661.25 | 07-JUN-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
July | 1667.24 | 12-JUL-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 0.00 |
August | 1671.98 | 20-AUG-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 0.00 |
September | 1833.60 | 30-SEP-15:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 |
October | 1845.18 | 23-OCT-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 |
November | 1818.83 | 12-NOV-16:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.84 |
December | 1808.16 | 01-DEC-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1661.25 | 378.00 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1845.18 | 970.20 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 108.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15982.74 | 13-JAN-23:10 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.59 |
February | 16163.83 | 24-FEB-23:10 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.64 |
March | 16954.73 | 28-MAR-22:10 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.53 |
April | 18735.25 | 18-APR-21:10 | 53977.54 | 1897.35 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.65 |
May | 20108.46 | 30-MAY-21:10 | 53977.54 | 1897.35 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.67 |
June | 21003.71 | 27-JUN-21:05 | 107955.07 | 3794.70 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 |
July | 20510.03 | 05-JUL-21:10 | 53977.54 | 1897.35 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
August | 20527.85 | 03-AUG-21:10 | 53977.54 | 1897.35 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 0.00 |
September | 19694.10 | 11-SEP-21:10 | 53977.54 | 1897.35 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.24 |
October | 17345.07 | 20-OCT-21:00 | 23990.02 | 1264.90 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.84 |
November | 17347.78 | 08-NOV-23:10 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.82 |
December | 15909.09 | 04-DEC-23:10 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15909.09 | 23990.02 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21003.71 | 107955.07 | 3794.70 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 390.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16782.82 | 13-JAN-23:10 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.05 |
February | 16979.17 | 24-FEB-23:10 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.29 |
March | 17758.83 | 28-MAR-21:00 | 23990.02 | 1264.90 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.60 |
April | 20377.10 | 18-APR-21:10 | 53977.54 | 1897.35 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.16 |
May | 21102.08 | 31-MAY-21:53 | 188921.38 | 6640.73 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 |
June | 21787.32 | 26-JUN-22:00 | 26988.77 | 948.68 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 | 0.00 |
July | 21575.51 | 03-JUL-22:00 | 26988.77 | 948.68 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.69 |
August | 21383.88 | 03-AUG-22:00 | 26988.77 | 948.68 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
September | 20723.90 | 07-SEP-21:53 | 188921.38 | 6640.73 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 |
October | 18346.40 | 20-OCT-23:00 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.19 |
November | 18504.63 | 08-NOV-24:00 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.73 |
December | 16701.91 | 04-DEC-23:10 | 26988.77 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16701.91 | 23990.02 | 474.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21787.32 | 188921.38 | 6640.73 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 | 397.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25104.29 | 13-JAN-11:50 | 533.71 | 207.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 309.32 |
February | 25958.96 | 24-FEB-11:40 | 533.71 | 207.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 273.40 |
March | 27229.42 | 19-MAR-10:50 | 800.57 | 249.14 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 143.54 |
April | 28836.09 | 15-APR-10:40 | 1601.14 | 415.23 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 8.05 | 0.00 |
May | 29262.31 | 31-MAY-10:40 | 1067.42 | 415.23 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 53.69 | 0.00 |
June | 29608.68 | 11-JUN-10:50 | 800.57 | 249.14 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 83.77 | 0.00 |
July | 29678.06 | 29-JUL-10:40 | 1601.14 | 415.23 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 26.13 | 0.00 |
August | 29176.41 | 01-AUG-10:40 | 1067.42 | 415.23 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 38.88 | 0.00 |
September | 29286.58 | 08-SEP-10:50 | 533.71 | 207.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 63.64 | 0.00 |
October | 27378.33 | 01-OCT-10:35 | 1601.14 | 498.27 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 117.56 |
November | 26959.63 | 04-NOV-10:40 | 1601.14 | 415.23 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 210.12 |
December | 25556.75 | 03-DEC-11:50 | 800.57 | 249.14 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 291.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25104.29 | 533.71 | 207.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29678.06 | 1601.14 | 498.27 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 83.77 | 309.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1436.85 | 13-JAN-11:35 | 1064.64 | 656.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 |
February | 1594.23 | 24-FEB-11:40 | 532.32 | 328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.53 |
March | 1798.00 | 20-MAR-10:35 | 1064.64 | 656.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.09 |
April | 3743.90 | 18-APR-15:10 | 1330.80 | 328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.57 | 0.00 |
May | 4633.35 | 31-MAY-15:10 | 1330.80 | 328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.18 | 0.00 |
June | 5396.61 | 30-JUN-14:10 | 798.48 | 328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.53 | 0.00 |
July | 5347.45 | 29-JUL-13:30 | 798.48 | 328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 0.00 |
August | 5609.15 | 04-AUG-15:10 | 1330.80 | 328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 | 0.00 |
September | 5800.41 | 07-SEP-13:30 | 532.32 | 328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.74 | 0.00 |
October | 1908.70 | 20-OCT-17:20 | 1330.80 | 787.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.27 |
November | 1881.70 | 04-NOV-10:35 | 1596.96 | 656.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.50 |
December | 1532.78 | 03-DEC-11:50 | 798.48 | 393.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1436.85 | 532.32 | 328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5800.41 | 1596.96 | 787.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 | 263.50 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.310495E+12 | 194523.02 | 09-JAN-20:30 | 0.779804E+12 | 918180.44 | 30-JAN-19:10 |
February | 0.277036E+12 | 194661.68 | 06-FEB-20:30 | 0.676340E+12 | 970590.16 | 02-FEB-19:19 |
March | 0.304319E+12 | 194561.85 | 06-MAR-20:10 | 0.515963E+12 | 457163.20 | 15-MAR-18:10 |
April | 0.311623E+12 | 289395.20 | 16-APR-19:40 | 0.459658E+12 | 444962.80 | 21-APR-16:40 |
May | 0.352304E+12 | 295674.07 | 31-MAY-19:40 | 0.414100E+12 | 369553.53 | 01-MAY-20:00 |
June | 0.423410E+12 | 319299.74 | 26-JUN-19:00 | 0.376456E+12 | 338030.34 | 01-JUN-17:19 |
July | 0.479272E+12 | 336874.67 | 26-JUL-19:40 | 0.377064E+12 | 313627.81 | 05-JUL-17:19 |
August | 0.459820E+12 | 326938.79 | 03-AUG-19:30 | 0.373471E+12 | 312720.19 | 01-AUG-17:10 |
September | 0.366562E+12 | 299086.57 | 07-SEP-19:10 | 0.380026E+12 | 342452.67 | 29-SEP-21:00 |
October | 0.308199E+12 | 207855.36 | 20-OCT-19:10 | 0.453239E+12 | 410686.08 | 31-OCT-17:00 |
November | 0.296653E+12 | 196902.05 | 08-NOV-20:49 | 0.517149E+12 | 805301.83 | 25-NOV-21:00 |
December | 0.312061E+12 | 194814.83 | 13-DEC-20:40 | 0.585432E+12 | 539055.00 | 11-DEC-17:30 |
Annual Sum or Average | 0.420175E+13 | 0.590870E+13 | ||||
Minimum of Months | 0.277036E+12 | 194523.02 | 0.373471E+12 | 312720.19 | ||
Maximum of Months | 0.479272E+12 | 336874.67 | 0.779804E+12 | 970590.16 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.718691E+10 | 21557.64 | 29-JAN-12:30 | 0.00 | 0.00 |
February | 0.880889E+10 | 22173.14 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.139863E+11 | 30437.31 | 16-MAR-12:30 | 0.00 | 0.00 |
April | 0.175129E+11 | 33462.85 | 25-APR-12:20 | 0.00 | 0.00 |
May | 0.207931E+11 | 32565.88 | 18-MAY-11:30 | 0.00 | 0.00 |
June | 0.223299E+11 | 32117.67 | 22-JUN-11:00 | 0.00 | 0.00 |
July | 0.230995E+11 | 31313.46 | 15-JUL-12:30 | 0.00 | 0.00 |
August | 0.195028E+11 | 31093.28 | 07-AUG-12:30 | 0.00 | 0.00 |
September | 0.150604E+11 | 27302.61 | 04-SEP-11:00 | 0.00 | 0.00 |
October | 0.106537E+11 | 22252.27 | 01-OCT-12:39 | 0.00 | 0.00 |
November | 0.643420E+10 | 17743.83 | 04-NOV-11:50 | 0.00 | 0.00 |
December | 0.480568E+10 | 14360.15 | 01-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170174E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.480568E+10 | 14360.15 | 0.00 | 0.00 | |
Maximum of Months | 0.230995E+11 | 33462.85 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.390281E+11 | 0.158741E+11 | 0.140003E+12 | 0.331709E+11 | 0.475128E+11 | 0.257792E+10 | 0.00 | 0.670124E+09 | 0.00 | 0.00 | 0.202494E+11 | 0.770429E+10 | 0.00 |
February | 0.351326E+11 | 0.132265E+11 | 0.126445E+12 | 0.299608E+11 | 0.424276E+11 | 0.327790E+10 | 0.00 | 0.101881E+10 | 0.00 | 0.00 | 0.152373E+11 | 0.696188E+10 | 0.00 |
March | 0.386666E+11 | 0.131059E+11 | 0.140056E+12 | 0.331732E+11 | 0.463995E+11 | 0.463702E+10 | 0.00 | 0.406452E+10 | 0.00 | 0.00 | 0.127953E+11 | 0.770285E+10 | 0.00 |
April | 0.372047E+11 | 0.111073E+11 | 0.135446E+12 | 0.321003E+11 | 0.456234E+11 | 0.578470E+10 | 0.00 | 0.256351E+11 | 0.00 | 0.00 | 0.765359E+10 | 0.746489E+10 | 0.00 |
May | 0.381986E+11 | 0.101022E+11 | 0.140035E+12 | 0.331716E+11 | 0.486639E+11 | 0.778991E+10 | 0.00 | 0.598272E+11 | 0.00 | 0.00 | 0.305502E+10 | 0.770425E+10 | 0.00 |
June | 0.368828E+11 | 0.908569E+10 | 0.135537E+12 | 0.321025E+11 | 0.497116E+11 | 0.787166E+10 | 0.00 | 0.134722E+12 | 0.00 | 0.00 | 0.638548E+10 | 0.745688E+10 | 0.00 |
July | 0.381323E+11 | 0.968297E+10 | 0.139944E+12 | 0.331692E+11 | 0.521218E+11 | 0.839443E+10 | 0.00 | 0.179368E+12 | 0.00 | 0.00 | 0.698101E+10 | 0.771240E+10 | 0.00 |
August | 0.383065E+11 | 0.108718E+11 | 0.140067E+12 | 0.331730E+11 | 0.516118E+11 | 0.830656E+10 | 0.00 | 0.159322E+12 | 0.00 | 0.00 | 0.667760E+10 | 0.770437E+10 | 0.00 |
September | 0.373438E+11 | 0.119802E+11 | 0.135457E+12 | 0.321005E+11 | 0.481517E+11 | 0.739384E+10 | 0.00 | 0.782505E+11 | 0.00 | 0.00 | 0.478407E+10 | 0.746622E+10 | 0.00 |
October | 0.388266E+11 | 0.140076E+11 | 0.139992E+12 | 0.331707E+11 | 0.469600E+11 | 0.600287E+10 | 0.00 | 0.132477E+11 | 0.00 | 0.00 | 0.456271E+10 | 0.770292E+10 | 0.00 |
November | 0.377395E+11 | 0.149609E+11 | 0.135531E+12 | 0.321015E+11 | 0.451459E+11 | 0.429327E+10 | 0.00 | 0.378688E+10 | 0.00 | 0.00 | 0.120503E+11 | 0.744870E+10 | 0.00 |
December | 0.390724E+11 | 0.162589E+11 | 0.139944E+12 | 0.331698E+11 | 0.469896E+11 | 0.373772E+10 | 0.00 | 0.123283E+10 | 0.00 | 0.00 | 0.202332E+11 | 0.771243E+10 | 0.00 |
Annual Sum or Average | 0.454534E+12 | 0.150264E+12 | 0.164846E+13 | 0.390564E+12 | 0.571319E+12 | 0.700678E+11 | 0.00 | 0.661145E+12 | 0.00 | 0.00 | 0.120665E+12 | 0.907421E+11 | 0.00 |
Minimum of Months | 0.351326E+11 | 0.908569E+10 | 0.126445E+12 | 0.299608E+11 | 0.424276E+11 | 0.257792E+10 | 0.00 | 0.670124E+09 | 0.00 | 0.00 | 0.305502E+10 | 0.696188E+10 | 0.00 |
Maximum of Months | 0.390724E+11 | 0.162589E+11 | 0.140067E+12 | 0.331732E+11 | 0.521218E+11 | 0.839443E+10 | 0.00 | 0.179368E+12 | 0.00 | 0.00 | 0.202494E+11 | 0.771243E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.370405E+12 | 0.00 | 0.257481E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.304815E+12 | 0.00 | 0.234321E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.105354E+12 | 0.00 | 0.258585E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.660323E+11 | 0.00 | 0.246670E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.168680E+11 | 0.00 | 0.245253E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.293154E+10 | 0.00 | 0.226411E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 92795251.29 | 0.00 | 0.225151E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.243784E+09 | 0.00 | 0.221189E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.171937E+11 | 0.00 | 0.215862E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.710342E+11 | 0.00 | 0.230302E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.136846E+12 | 0.00 | 0.233211E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.181500E+12 | 0.00 | 0.252111E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.127332E+13 | 0.00 | 0.284655E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 92795251.29 | 0.00 | 0.215862E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.370405E+12 | 0.00 | 0.258585E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 37630.57 | 02-JAN-20:10 | 9571.94 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 23858.54 | 02-JAN-07:19 | 27682.10 | 30-JAN-19:10 | 3019.55 | 31-JAN-16:40 | 0.00 | 01-JAN-00:10 |
February | 37630.57 | 01-FEB-20:10 | 9571.94 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 23858.54 | 01-FEB-07:19 | 27815.64 | 01-FEB-19:19 | 2995.02 | 13-FEB-16:49 | 0.00 | 01-FEB-00:10 |
March | 37630.57 | 01-MAR-20:10 | 9571.94 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 23858.54 | 13-MAR-06:19 | 25335.47 | 03-MAR-19:10 | 2984.09 | 21-MAR-15:39 | 0.00 | 01-MAR-00:10 |
April | 37630.57 | 03-APR-19:10 | 9571.94 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 23858.24 | 14-APR-06:19 | 28257.90 | 17-APR-20:19 | 3447.08 | 16-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 37630.57 | 01-MAY-19:10 | 9571.94 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 23857.56 | 10-MAY-06:19 | 29600.61 | 31-MAY-21:00 | 3509.50 | 31-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 37630.57 | 01-JUN-19:40 | 9571.94 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 23857.67 | 13-JUN-06:19 | 32399.09 | 26-JUN-21:19 | 3788.88 | 26-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 37630.57 | 03-JUL-19:00 | 9571.94 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 23857.54 | 20-JUL-06:19 | 31310.79 | 03-JUL-21:19 | 4038.20 | 26-JUL-18:19 | 0.00 | 01-JUL-00:10 |
August | 37630.57 | 01-AUG-19:40 | 9571.94 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 23857.64 | 31-AUG-06:19 | 31253.49 | 04-AUG-21:00 | 3885.83 | 03-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 37630.57 | 01-SEP-19:10 | 9571.94 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 23858.54 | 21-SEP-06:19 | 30768.44 | 07-SEP-21:00 | 3535.57 | 06-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 37630.57 | 02-OCT-19:10 | 9571.94 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 23858.54 | 02-OCT-06:19 | 26502.01 | 20-OCT-20:19 | 3139.92 | 20-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 37630.57 | 01-NOV-19:10 | 9571.94 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 23858.54 | 01-NOV-06:19 | 26029.39 | 28-NOV-19:10 | 2993.64 | 05-NOV-15:20 | 0.00 | 01-NOV-00:10 |
December | 37630.57 | 01-DEC-20:10 | 9571.94 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 23858.54 | 01-DEC-07:19 | 27064.43 | 11-DEC-19:10 | 3003.18 | 13-DEC-02:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 37630.57 | 9571.94 | 88863.15 | 23857.54 | 25335.47 | 2984.09 | 0.00 | |||||||
Maximum of Months | 37630.57 | 9571.94 | 88863.15 | 23858.54 | 32399.09 | 4038.20 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 4277.69 | 12-JAN-16:19 | 0.00 | 0.00 | 8265.52 | 01-JAN-00:10 | 4738.14 | 02-JAN-07:00 | 0.00 | 01-JAN-00:10 |
February | 6668.43 | 24-FEB-16:19 | 0.00 | 0.00 | 8265.52 | 01-FEB-00:10 | 4738.57 | 16-FEB-19:10 | 0.00 | 01-FEB-00:10 |
March | 37050.81 | 25-MAR-15:20 | 0.00 | 0.00 | 8265.52 | 01-MAR-00:10 | 4738.15 | 20-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 114011.44 | 16-APR-15:30 | 0.00 | 0.00 | 8265.52 | 01-APR-00:10 | 4738.54 | 27-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 112981.60 | 31-MAY-15:30 | 0.00 | 0.00 | 8265.52 | 02-MAY-05:49 | 4738.48 | 25-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 154670.45 | 11-JUN-15:30 | 0.00 | 0.00 | 8265.52 | 25-JUN-08:00 | 4738.72 | 01-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 161038.10 | 26-JUL-18:10 | 0.00 | 0.00 | 8265.52 | 02-JUL-08:00 | 4738.76 | 13-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 177783.01 | 04-AUG-15:30 | 0.00 | 0.00 | 8265.52 | 22-AUG-08:00 | 4738.48 | 03-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 131470.37 | 06-SEP-15:30 | 0.00 | 0.00 | 8265.52 | 01-SEP-12:09 | 4738.61 | 07-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 69259.24 | 20-OCT-15:20 | 0.00 | 0.00 | 8265.52 | 07-OCT-23:10 | 4738.59 | 26-OCT-18:10 | 0.00 | 01-OCT-00:10 |
November | 26938.44 | 05-NOV-15:20 | 0.00 | 0.00 | 8265.52 | 04-NOV-05:30 | 4738.69 | 15-NOV-19:10 | 0.00 | 01-NOV-00:10 |
December | 4452.19 | 03-DEC-09:09 | 0.00 | 0.00 | 8265.52 | 01-DEC-00:10 | 4738.27 | 20-DEC-07:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 4277.69 | 0.00 | 0.00 | 8265.52 | 4738.14 | 0.00 | ||||
Maximum of Months | 177783.01 | 0.00 | 0.00 | 8265.52 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 194523.02 | 09-JAN-20:30 | 37630.57 | 86131.51 | 9571.94 | 19290.81 | 24122.58 | 2960.07 | 0.00 | 809.87 | 0.00 |
February | 194661.68 | 06-FEB-20:30 | 37630.57 | 86131.51 | 9571.94 | 19290.81 | 24248.84 | 2961.08 | 0.00 | 826.21 | 0.00 |
March | 194561.85 | 06-MAR-20:10 | 37630.57 | 86131.51 | 9571.94 | 19287.45 | 24186.33 | 2949.40 | 0.00 | 833.12 | 0.00 |
April | 289395.20 | 16-APR-19:40 | 34703.83 | 84670.41 | 9571.94 | 19255.35 | 27618.54 | 3393.67 | 0.00 | 97172.59 | 0.00 |
May | 295674.07 | 31-MAY-19:40 | 37630.57 | 86131.51 | 9571.94 | 19290.40 | 27689.30 | 3396.86 | 0.00 | 98048.96 | 0.00 |
June | 319299.74 | 26-JUN-19:00 | 37630.57 | 86131.51 | 9571.94 | 19290.67 | 28326.97 | 3625.94 | 0.00 | 121032.99 | 0.00 |
July | 336874.67 | 26-JUL-19:40 | 37630.57 | 86131.51 | 9571.94 | 19290.75 | 27767.22 | 3812.53 | 0.00 | 138660.24 | 0.00 |
August | 326938.79 | 03-AUG-19:30 | 37630.57 | 86131.51 | 9571.94 | 19290.12 | 27750.56 | 3739.18 | 0.00 | 128931.67 | 0.00 |
September | 299086.57 | 07-SEP-19:10 | 37630.57 | 86131.51 | 9571.94 | 19287.45 | 27599.70 | 3405.03 | 0.00 | 101693.92 | 0.00 |
October | 207855.36 | 20-OCT-19:10 | 37630.57 | 86131.51 | 9571.94 | 19287.45 | 24118.42 | 2962.38 | 0.00 | 23260.50 | 0.00 |
November | 196902.05 | 08-NOV-20:49 | 37630.57 | 86131.51 | 9571.94 | 19290.81 | 24175.09 | 2948.85 | 0.00 | 9877.90 | 0.00 |
December | 194814.83 | 13-DEC-20:40 | 37630.57 | 86131.51 | 9571.94 | 19290.81 | 24393.59 | 2964.45 | 0.00 | 835.22 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 194523.02 | 34703.83 | 84670.41 | 9571.94 | 19255.35 | 24118.42 | 2948.85 | 0.00 | 809.87 | 0.00 | |
Maximum of Months | 336874.67 | 37630.57 | 86131.51 | 9571.94 | 19290.81 | 28326.97 | 3812.53 | 0.00 | 138660.24 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 637930.15 | 19-JAN-09:09 | 0.00 | 257777.78 | 31-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 712937.83 | 02-FEB-09:09 | 0.00 | 258530.71 | 23-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 159950.75 | 17-MAR-15:20 | 0.00 | 258379.93 | 02-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 149541.54 | 27-APR-15:20 | 0.00 | 254975.00 | 04-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 99089.47 | 03-MAY-02:49 | 0.00 | 249391.57 | 01-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 54635.82 | 03-JUN-03:00 | 0.00 | 239332.79 | 02-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4612.20 | 02-JUL-21:00 | 0.00 | 214177.15 | 01-JUL-21:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 12849.89 | 07-AUG-03:00 | 0.00 | 209069.90 | 02-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 151061.05 | 29-SEP-02:49 | 0.00 | 209660.35 | 29-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 141917.78 | 26-OCT-08:09 | 0.00 | 235516.69 | 24-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 569948.03 | 26-NOV-06:00 | 0.00 | 246392.85 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 257538.36 | 11-DEC-09:09 | 0.00 | 253066.64 | 28-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 4612.20 | 0.00 | 209069.90 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 712937.83 | 0.00 | 258530.71 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.68 | 0.83 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 21.73 | 3.00 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.72 | 1.17 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.05 | 0.17 | 22.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.74 | 3.17 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.05 | 1.50 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.50 | 1.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 1.83 | 20.33 | 1.83 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.78 | 5.67 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.75 | 7.50 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.75 | 4.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Annual Sum or Average | 3.67 | 20.42 | 3.67 | 20.42 | 19.83 | 21.40 | 19.83 | 21.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.54 | 1.83 | 20.54 | 7.50 | 21.81 | 7.50 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.09 | 0.33 | 22.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 22.21 | 0.83 | 22.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.29 | 4.83 | 22.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 22.33 | 6.33 | 22.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 22.12 | 3.83 | 22.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.25 | 1.50 | 22.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.67 | 22.26 | 17.67 | 22.26 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 22.33 | 6.33 | 22.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.76 | 2.00 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.75 | 2.50 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.77 | 1.67 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.83 | 2.00 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.33 | 21.77 | 9.33 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.83 | 2.50 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.80 | 3.67 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.78 | 3.67 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.00 | 21.79 | 10.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.81 | 3.67 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.78 | 2.17 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.79 | 1.00 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.90 | 0.33 | 21.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 21.77 | 5.00 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.90 | 2.17 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.43 | 0.00 | 22.43 | 0.00 | 22.43 |
February | 672.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
March | 744.00 | 21.43 | 5.00 | 21.42 | 5.00 | 21.42 |
April | 720.00 | 21.24 | 22.33 | 21.24 | 22.33 | 21.23 |
May | 744.00 | 21.36 | 3.83 | 21.36 | 3.83 | 21.36 |
June | 720.00 | 21.83 | 29.83 | 21.84 | 29.83 | 21.84 |
July | 744.00 | 22.33 | 71.67 | 22.34 | 71.67 | 22.35 |
August | 737.33 | 22.90 | 83.67 | 22.91 | 83.67 | 22.92 |
September | 632.83 | 23.30 | 17.00 | 23.31 | 16.33 | 23.31 |
October | 726.17 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
November | 683.33 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
December | 744.00 | 23.10 | 0.00 | 23.10 | 0.00 | 23.10 |
Annual Sum or Average | 8611.67 | 22.39 | 233.33 | 22.39 | 232.67 | 22.39 |
Minimum of Months | 632.83 | 21.24 | 0.00 | 21.24 | 0.00 | 21.23 |
Maximum of Months | 744.00 | 23.51 | 83.67 | 23.51 | 83.67 | 23.51 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.50 | 21.08 | 607.67 | 21.05 | 607.67 | 21.03 |
February | 660.17 | 21.13 | 408.33 | 21.08 | 408.33 | 21.06 |
March | 726.00 | 21.28 | 276.17 | 21.22 | 273.00 | 21.17 |
April | 629.33 | 21.53 | 145.17 | 21.66 | 86.17 | 21.60 |
May | 617.67 | 22.10 | 85.33 | 22.29 | 18.17 | 22.30 |
June | 370.67 | 22.44 | 374.17 | 23.11 | 88.50 | 23.15 |
July | 290.33 | 23.08 | 539.83 | 23.54 | 144.83 | 23.53 |
August | 286.00 | 23.03 | 486.83 | 23.50 | 118.67 | 23.49 |
September | 431.33 | 22.10 | 236.50 | 22.74 | 19.67 | 22.76 |
October | 669.00 | 21.58 | 24.33 | 21.64 | 4.67 | 21.64 |
November | 701.00 | 21.19 | 325.67 | 21.15 | 318.50 | 21.12 |
December | 737.50 | 21.13 | 584.83 | 21.07 | 584.83 | 21.05 |
Annual Sum or Average | 6862.50 | 21.61 | 4094.83 | 21.84 | 2673.00 | 21.75 |
Minimum of Months | 286.00 | 21.08 | 24.33 | 21.05 | 4.67 | 21.03 |
Maximum of Months | 743.50 | 23.08 | 607.67 | 23.54 | 607.67 | 23.53 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.04 | 275.50 | 21.03 | 275.50 | 21.02 |
February | 672.00 | 21.14 | 158.17 | 21.11 | 158.17 | 21.10 |
March | 744.00 | 21.32 | 5.83 | 21.31 | 5.83 | 21.31 |
April | 709.50 | 21.69 | 2.83 | 21.70 | 1.67 | 21.70 |
May | 734.50 | 22.16 | 22.50 | 22.19 | 18.83 | 22.20 |
June | 622.00 | 22.53 | 115.83 | 22.67 | 82.67 | 22.74 |
July | 582.83 | 22.78 | 203.33 | 22.96 | 136.83 | 23.02 |
August | 595.50 | 22.78 | 165.50 | 22.93 | 116.00 | 22.98 |
September | 627.00 | 22.40 | 51.00 | 22.49 | 19.67 | 22.51 |
October | 744.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
November | 720.00 | 21.36 | 57.67 | 21.34 | 57.67 | 21.31 |
December | 744.00 | 21.08 | 118.67 | 21.07 | 118.67 | 21.06 |
Annual Sum or Average | 8239.33 | 21.80 | 1176.83 | 21.84 | 991.50 | 21.85 |
Minimum of Months | 582.83 | 21.04 | 0.00 | 21.03 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 22.78 | 275.50 | 22.96 | 275.50 | 23.02 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.07 | 517.83 | 21.04 | 517.83 | 21.03 |
February | 672.00 | 21.32 | 252.00 | 21.23 | 252.00 | 21.18 |
March | 744.00 | 21.89 | 86.33 | 21.79 | 86.33 | 21.72 |
April | 639.50 | 22.70 | 28.50 | 22.76 | 0.00 | 22.76 |
May | 377.67 | 23.71 | 104.50 | 23.77 | 6.00 | 23.78 |
June | 142.17 | 23.80 | 320.33 | 23.94 | 8.33 | 23.94 |
July | 14.33 | 24.00 | 570.17 | 24.00 | 14.33 | 24.00 |
August | 46.67 | 24.00 | 454.67 | 24.00 | 22.17 | 24.00 |
September | 336.50 | 23.77 | 115.00 | 23.83 | 0.00 | 23.83 |
October | 738.50 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
November | 704.00 | 22.20 | 125.00 | 22.02 | 125.00 | 21.89 |
December | 744.00 | 21.16 | 355.83 | 21.11 | 355.83 | 21.08 |
Annual Sum or Average | 5903.33 | 22.22 | 2930.17 | 22.36 | 1387.83 | 22.19 |
Minimum of Months | 14.33 | 21.07 | 0.00 | 21.04 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 24.00 | 570.17 | 24.00 | 517.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 612.67 | 21.00 | 612.67 | 21.00 |
February | 672.00 | 21.00 | 385.83 | 21.00 | 385.83 | 21.00 |
March | 744.00 | 21.00 | 265.50 | 21.00 | 265.50 | 21.00 |
April | 720.00 | 21.12 | 55.83 | 21.11 | 55.83 | 21.10 |
May | 744.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
June | 720.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
July | 744.00 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
August | 744.00 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
September | 720.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
October | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
November | 720.00 | 21.01 | 217.33 | 21.01 | 217.33 | 21.01 |
December | 744.00 | 21.00 | 558.17 | 21.00 | 558.17 | 21.00 |
Annual Sum or Average | 8760.00 | 21.35 | 2095.33 | 21.28 | 2095.33 | 21.24 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.11 | 612.67 | 22.11 | 612.67 | 22.11 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 129.67 | 24.00 | 720.33 | 24.00 | 129.67 | 24.00 |
February | 130.33 | 24.00 | 654.17 | 24.00 | 130.33 | 24.00 |
March | 175.00 | 24.00 | 744.00 | 24.00 | 175.00 | 24.00 |
April | 238.00 | 24.00 | 720.00 | 24.00 | 238.00 | 24.00 |
May | 392.83 | 24.00 | 744.00 | 24.00 | 392.83 | 24.00 |
June | 511.50 | 24.00 | 720.00 | 24.00 | 511.50 | 24.00 |
July | 603.50 | 24.00 | 744.00 | 24.00 | 603.50 | 24.00 |
August | 595.83 | 24.00 | 744.00 | 24.00 | 595.83 | 24.00 |
September | 390.50 | 24.00 | 720.00 | 24.00 | 390.50 | 24.00 |
October | 217.50 | 24.00 | 744.00 | 24.00 | 217.50 | 24.00 |
November | 181.33 | 24.00 | 720.00 | 24.00 | 181.33 | 24.00 |
December | 134.33 | 24.00 | 744.00 | 24.00 | 134.33 | 24.00 |
Annual Sum or Average | 3700.33 | 24.00 | 8718.50 | 24.00 | 3700.33 | 24.00 |
Minimum of Months | 129.67 | 24.00 | 654.17 | 24.00 | 129.67 | 24.00 |
Maximum of Months | 603.50 | 24.00 | 744.00 | 24.00 | 603.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.07 | 343.17 | 21.05 | 343.17 | 21.04 |
February | 665.83 | 21.19 | 139.83 | 21.15 | 139.83 | 21.13 |
March | 740.50 | 21.35 | 26.67 | 21.34 | 26.67 | 21.33 |
April | 675.17 | 21.59 | 37.00 | 21.65 | 13.33 | 21.66 |
May | 712.83 | 21.82 | 55.67 | 21.89 | 43.33 | 21.93 |
June | 615.83 | 22.10 | 174.33 | 22.29 | 132.00 | 22.40 |
July | 595.67 | 22.28 | 280.50 | 22.50 | 218.33 | 22.60 |
August | 551.67 | 22.28 | 269.83 | 22.51 | 174.00 | 22.60 |
September | 540.00 | 21.99 | 158.17 | 22.27 | 49.67 | 22.33 |
October | 694.67 | 21.69 | 8.17 | 21.71 | 0.00 | 21.71 |
November | 706.00 | 21.32 | 85.50 | 21.30 | 79.83 | 21.28 |
December | 740.83 | 21.13 | 221.50 | 21.10 | 221.50 | 21.08 |
Annual Sum or Average | 7983.00 | 21.61 | 1800.33 | 21.70 | 1441.67 | 21.73 |
Minimum of Months | 540.00 | 21.07 | 8.17 | 21.05 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 22.28 | 343.17 | 22.51 | 343.17 | 22.60 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.35 | 102.00 | 21.31 | 102.00 | 21.28 |
February | 672.00 | 21.56 | 79.17 | 21.50 | 79.17 | 21.45 |
March | 744.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
April | 681.67 | 22.15 | 25.00 | 22.20 | 15.00 | 22.23 |
May | 681.83 | 22.55 | 64.67 | 22.63 | 54.83 | 22.68 |
June | 539.50 | 22.78 | 222.00 | 23.04 | 154.17 | 23.15 |
July | 566.83 | 23.04 | 333.67 | 23.28 | 256.50 | 23.38 |
August | 507.50 | 23.01 | 323.33 | 23.28 | 200.33 | 23.36 |
September | 515.33 | 22.73 | 134.33 | 22.95 | 61.50 | 23.02 |
October | 736.33 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
November | 718.67 | 21.89 | 17.83 | 21.87 | 17.83 | 21.85 |
December | 744.00 | 21.50 | 34.83 | 21.48 | 34.83 | 21.46 |
Annual Sum or Average | 7851.67 | 22.17 | 1336.83 | 22.32 | 976.17 | 22.39 |
Minimum of Months | 507.50 | 21.35 | 0.00 | 21.31 | 0.00 | 21.28 |
Maximum of Months | 744.00 | 23.04 | 333.67 | 23.28 | 256.50 | 23.38 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.51 | 717.00 | 20.50 | 717.00 | 20.49 |
February | 672.00 | 20.69 | 537.17 | 20.63 | 537.17 | 20.60 |
March | 744.00 | 20.98 | 402.67 | 20.87 | 402.67 | 20.81 |
April | 704.33 | 21.23 | 140.00 | 21.12 | 140.00 | 21.04 |
May | 722.17 | 21.59 | 1.17 | 21.59 | 1.17 | 21.59 |
June | 644.00 | 21.51 | 6.33 | 21.53 | 6.00 | 21.54 |
July | 637.17 | 21.51 | 9.33 | 21.53 | 7.00 | 21.54 |
August | 649.83 | 21.53 | 16.17 | 21.56 | 15.00 | 21.59 |
September | 668.17 | 21.48 | 8.67 | 21.47 | 8.67 | 21.47 |
October | 741.33 | 21.31 | 52.00 | 21.28 | 52.00 | 21.25 |
November | 720.00 | 20.84 | 428.00 | 20.75 | 428.00 | 20.70 |
December | 744.00 | 20.60 | 700.17 | 20.58 | 700.17 | 20.57 |
Annual Sum or Average | 8391.00 | 21.14 | 3018.67 | 20.99 | 3014.83 | 20.91 |
Minimum of Months | 637.17 | 20.51 | 1.17 | 20.50 | 1.17 | 20.49 |
Maximum of Months | 744.00 | 21.59 | 717.00 | 21.59 | 717.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 743.17 | 20.43 | 743.17 | 20.43 |
February | 672.00 | 20.53 | 629.83 | 20.51 | 629.83 | 20.50 |
March | 744.00 | 20.78 | 469.00 | 20.68 | 469.00 | 20.64 |
April | 699.50 | 21.18 | 185.00 | 21.08 | 178.67 | 20.99 |
May | 686.00 | 21.72 | 43.00 | 21.87 | 17.83 | 21.89 |
June | 592.83 | 21.84 | 94.33 | 22.22 | 49.50 | 22.34 |
July | 574.83 | 22.04 | 141.17 | 22.50 | 78.17 | 22.65 |
August | 597.83 | 22.00 | 130.50 | 22.35 | 86.00 | 22.46 |
September | 663.17 | 21.67 | 29.83 | 21.73 | 17.00 | 21.71 |
October | 744.00 | 21.12 | 156.00 | 21.04 | 156.00 | 20.98 |
November | 720.00 | 20.69 | 478.33 | 20.61 | 478.33 | 20.58 |
December | 744.00 | 20.46 | 743.00 | 20.46 | 743.00 | 20.46 |
Annual Sum or Average | 8182.17 | 21.16 | 3843.17 | 21.08 | 3646.50 | 20.99 |
Minimum of Months | 574.83 | 20.43 | 29.83 | 20.43 | 17.00 | 20.43 |
Maximum of Months | 744.00 | 22.04 | 743.17 | 22.50 | 743.17 | 22.65 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.65 | 642.50 | 20.61 | 642.50 | 20.60 |
February | 672.00 | 20.79 | 440.17 | 20.73 | 440.17 | 20.70 |
March | 744.00 | 21.04 | 308.17 | 20.97 | 308.17 | 20.93 |
April | 720.00 | 21.32 | 51.83 | 21.28 | 51.83 | 21.25 |
May | 742.17 | 21.73 | 9.33 | 21.74 | 9.00 | 21.76 |
June | 712.50 | 21.99 | 39.00 | 22.06 | 38.83 | 22.12 |
July | 730.33 | 22.15 | 61.50 | 22.24 | 58.83 | 22.31 |
August | 743.50 | 22.10 | 74.67 | 22.19 | 74.67 | 22.26 |
September | 720.00 | 21.73 | 1.00 | 21.74 | 1.00 | 21.74 |
October | 744.00 | 21.26 | 1.50 | 21.26 | 1.50 | 21.26 |
November | 720.00 | 20.98 | 295.83 | 20.90 | 295.83 | 20.85 |
December | 744.00 | 20.72 | 639.33 | 20.69 | 639.33 | 20.68 |
Annual Sum or Average | 8736.50 | 21.37 | 2564.83 | 21.25 | 2561.67 | 21.17 |
Minimum of Months | 672.00 | 20.65 | 1.00 | 20.61 | 1.00 | 20.60 |
Maximum of Months | 744.00 | 22.15 | 642.50 | 22.24 | 642.50 | 22.31 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 715.67 | 20.49 | 715.67 | 20.49 |
February | 672.00 | 20.69 | 543.00 | 20.63 | 543.00 | 20.61 |
March | 744.00 | 21.04 | 375.00 | 20.93 | 375.00 | 20.88 |
April | 704.00 | 21.27 | 160.50 | 21.15 | 160.17 | 21.06 |
May | 729.17 | 21.68 | 1.00 | 21.68 | 1.00 | 21.68 |
June | 641.00 | 21.54 | 6.17 | 21.56 | 3.50 | 21.56 |
July | 624.33 | 21.50 | 8.33 | 21.52 | 5.00 | 21.53 |
August | 642.17 | 21.54 | 13.50 | 21.57 | 12.17 | 21.59 |
September | 663.83 | 21.52 | 3.83 | 21.52 | 3.83 | 21.52 |
October | 744.00 | 21.37 | 44.17 | 21.35 | 44.17 | 21.32 |
November | 720.00 | 20.83 | 436.67 | 20.74 | 436.67 | 20.69 |
December | 744.00 | 20.58 | 698.83 | 20.56 | 698.83 | 20.55 |
Annual Sum or Average | 8372.50 | 21.16 | 3006.67 | 21.01 | 2999.00 | 20.92 |
Minimum of Months | 624.33 | 20.50 | 1.00 | 20.49 | 1.00 | 20.49 |
Maximum of Months | 744.00 | 21.68 | 715.67 | 21.68 | 715.67 | 21.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.44 | 740.67 | 20.44 | 740.67 | 20.44 |
February | 672.00 | 20.53 | 630.50 | 20.51 | 630.50 | 20.51 |
March | 744.00 | 20.83 | 453.50 | 20.75 | 453.50 | 20.71 |
April | 710.67 | 21.24 | 188.83 | 21.12 | 186.83 | 21.03 |
May | 717.50 | 21.88 | 25.33 | 21.94 | 16.67 | 21.98 |
June | 586.83 | 21.89 | 75.00 | 22.19 | 45.50 | 22.32 |
July | 550.00 | 22.05 | 120.33 | 22.47 | 73.17 | 22.64 |
August | 649.00 | 22.15 | 106.00 | 22.37 | 86.50 | 22.49 |
September | 691.50 | 21.80 | 18.83 | 21.86 | 7.00 | 21.86 |
October | 744.00 | 21.13 | 108.83 | 21.09 | 108.83 | 21.06 |
November | 720.00 | 20.68 | 473.67 | 20.60 | 473.67 | 20.56 |
December | 744.00 | 20.45 | 736.83 | 20.45 | 736.83 | 20.45 |
Annual Sum or Average | 8273.50 | 21.22 | 3678.33 | 21.10 | 3559.67 | 21.01 |
Minimum of Months | 550.00 | 20.44 | 18.83 | 20.44 | 7.00 | 20.44 |
Maximum of Months | 744.00 | 22.15 | 740.67 | 22.47 | 740.67 | 22.64 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 476.17 | 21.00 | 476.17 | 21.00 |
February | 672.00 | 21.00 | 240.00 | 21.00 | 240.00 | 21.00 |
March | 744.00 | 21.04 | 98.33 | 21.04 | 98.33 | 21.03 |
April | 720.00 | 21.35 | 16.83 | 21.35 | 16.83 | 21.34 |
May | 744.00 | 21.92 | 23.83 | 21.93 | 23.83 | 21.94 |
June | 712.67 | 22.58 | 107.67 | 22.62 | 107.67 | 22.66 |
July | 739.00 | 22.94 | 176.50 | 22.96 | 176.50 | 22.98 |
August | 744.00 | 22.84 | 143.00 | 22.85 | 143.00 | 22.86 |
September | 720.00 | 22.33 | 23.50 | 22.35 | 23.50 | 22.37 |
October | 744.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
November | 720.00 | 21.05 | 153.67 | 21.04 | 153.67 | 21.04 |
December | 744.00 | 21.00 | 333.17 | 21.00 | 333.17 | 21.00 |
Annual Sum or Average | 8747.67 | 21.69 | 1792.67 | 21.66 | 1792.67 | 21.64 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.94 | 476.17 | 22.96 | 476.17 | 22.98 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.45 | 736.33 | 20.45 | 736.33 | 20.45 |
February | 672.00 | 20.60 | 604.50 | 20.57 | 604.50 | 20.55 |
March | 744.00 | 20.86 | 485.83 | 20.76 | 485.83 | 20.72 |
April | 699.33 | 21.15 | 221.83 | 21.02 | 220.50 | 20.94 |
May | 706.67 | 21.54 | 13.50 | 21.53 | 13.50 | 21.53 |
June | 619.50 | 21.43 | 23.17 | 21.48 | 11.83 | 21.50 |
July | 614.17 | 21.43 | 34.00 | 21.52 | 15.83 | 21.54 |
August | 625.83 | 21.45 | 35.33 | 21.51 | 27.17 | 21.54 |
September | 657.00 | 21.41 | 32.17 | 21.39 | 28.50 | 21.37 |
October | 740.50 | 21.23 | 173.33 | 21.15 | 173.33 | 21.10 |
November | 720.00 | 20.74 | 490.83 | 20.65 | 490.83 | 20.62 |
December | 744.00 | 20.52 | 728.50 | 20.51 | 728.50 | 20.51 |
Annual Sum or Average | 8287.00 | 21.05 | 3579.33 | 20.91 | 3536.67 | 20.84 |
Minimum of Months | 614.17 | 20.45 | 13.50 | 20.45 | 11.83 | 20.45 |
Maximum of Months | 744.00 | 21.54 | 736.33 | 21.53 | 736.33 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.42 | 744.00 | 20.42 | 744.00 | 20.42 |
February | 672.00 | 20.47 | 651.50 | 20.46 | 651.50 | 20.46 |
March | 744.00 | 20.68 | 542.00 | 20.61 | 542.00 | 20.58 |
April | 692.67 | 21.10 | 275.83 | 20.99 | 267.33 | 20.91 |
May | 667.67 | 21.70 | 71.67 | 21.92 | 36.17 | 21.97 |
June | 571.67 | 21.85 | 123.00 | 22.35 | 63.83 | 22.54 |
July | 556.67 | 22.07 | 168.83 | 22.61 | 103.50 | 22.81 |
August | 574.17 | 21.98 | 161.67 | 22.41 | 107.00 | 22.55 |
September | 647.17 | 21.58 | 72.33 | 21.64 | 55.17 | 21.60 |
October | 744.00 | 21.02 | 317.17 | 20.92 | 317.17 | 20.86 |
November | 720.00 | 20.61 | 544.33 | 20.54 | 544.33 | 20.52 |
December | 744.00 | 20.42 | 744.00 | 20.42 | 744.00 | 20.42 |
Annual Sum or Average | 8078.00 | 21.10 | 4416.33 | 21.05 | 4176.00 | 20.97 |
Minimum of Months | 556.67 | 20.42 | 71.67 | 20.42 | 36.17 | 20.42 |
Maximum of Months | 744.00 | 22.07 | 744.00 | 22.61 | 744.00 | 22.81 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 631.50 | 20.76 | 631.50 | 20.73 |
February | 669.67 | 21.01 | 434.50 | 20.89 | 434.50 | 20.85 |
March | 741.67 | 21.23 | 295.50 | 21.10 | 295.50 | 21.03 |
April | 699.50 | 21.30 | 140.17 | 21.19 | 140.17 | 21.12 |
May | 720.00 | 21.61 | 1.00 | 21.61 | 1.00 | 21.61 |
June | 660.50 | 21.57 | 11.67 | 21.58 | 11.67 | 21.60 |
July | 650.67 | 21.53 | 14.67 | 21.55 | 14.67 | 21.58 |
August | 652.33 | 21.53 | 25.67 | 21.55 | 25.67 | 21.58 |
September | 654.17 | 21.49 | 15.17 | 21.53 | 3.83 | 21.52 |
October | 721.33 | 21.47 | 18.17 | 21.46 | 18.17 | 21.45 |
November | 710.33 | 21.08 | 343.00 | 20.96 | 343.00 | 20.90 |
December | 742.83 | 20.91 | 598.17 | 20.80 | 598.17 | 20.76 |
Annual Sum or Average | 8367.00 | 21.29 | 2529.17 | 21.16 | 2517.83 | 21.08 |
Minimum of Months | 650.67 | 20.84 | 1.00 | 20.76 | 1.00 | 20.73 |
Maximum of Months | 744.00 | 21.61 | 631.50 | 21.61 | 631.50 | 21.61 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.52 | 95.17 | 21.47 | 95.17 | 21.42 |
February | 672.00 | 21.64 | 81.33 | 21.57 | 81.33 | 21.52 |
March | 738.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
April | 652.00 | 22.10 | 38.67 | 22.17 | 14.00 | 22.19 |
May | 519.83 | 22.34 | 146.00 | 22.60 | 52.33 | 22.67 |
June | 393.83 | 22.65 | 331.33 | 23.03 | 145.00 | 23.13 |
July | 419.17 | 22.92 | 414.83 | 23.18 | 235.17 | 23.28 |
August | 420.33 | 22.71 | 363.00 | 23.06 | 183.50 | 23.16 |
September | 516.67 | 22.34 | 144.00 | 22.60 | 55.83 | 22.68 |
October | 720.50 | 22.11 | 3.50 | 22.12 | 0.00 | 22.12 |
November | 695.83 | 21.83 | 21.67 | 21.82 | 16.50 | 21.81 |
December | 744.00 | 21.62 | 31.67 | 21.60 | 31.67 | 21.57 |
Annual Sum or Average | 7236.17 | 22.05 | 1671.17 | 22.26 | 910.50 | 22.32 |
Minimum of Months | 393.83 | 21.52 | 0.00 | 21.47 | 0.00 | 21.42 |
Maximum of Months | 744.00 | 22.92 | 414.83 | 23.18 | 235.17 | 23.28 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.76 | 31.50 | 21.73 | 31.50 | 21.70 |
February | 671.00 | 21.90 | 59.33 | 21.83 | 59.33 | 21.77 |
March | 700.83 | 22.18 | 7.50 | 22.19 | 0.00 | 22.19 |
April | 570.50 | 22.35 | 73.83 | 22.49 | 14.33 | 22.51 |
May | 365.00 | 22.54 | 257.17 | 22.95 | 51.83 | 23.01 |
June | 272.50 | 23.06 | 460.17 | 23.33 | 148.67 | 23.41 |
July | 299.33 | 23.46 | 553.50 | 23.45 | 240.50 | 23.52 |
August | 285.00 | 23.20 | 497.83 | 23.37 | 188.17 | 23.45 |
September | 378.33 | 22.53 | 232.00 | 22.92 | 56.17 | 22.99 |
October | 633.83 | 22.35 | 23.83 | 22.40 | 0.00 | 22.40 |
November | 654.17 | 22.07 | 26.67 | 22.13 | 1.00 | 22.13 |
December | 744.00 | 21.88 | 3.00 | 21.88 | 3.00 | 21.88 |
Annual Sum or Average | 6318.50 | 22.27 | 2226.33 | 22.56 | 794.50 | 22.64 |
Minimum of Months | 272.50 | 21.76 | 3.00 | 21.73 | 0.00 | 21.70 |
Maximum of Months | 744.00 | 23.46 | 553.50 | 23.45 | 240.50 | 23.52 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 425.67 | 23.99 | 707.83 | 23.99 | 424.50 | 23.99 |
February | 422.33 | 23.97 | 644.33 | 23.98 | 413.50 | 23.98 |
March | 497.17 | 23.99 | 744.00 | 23.99 | 497.17 | 23.99 |
April | 508.50 | 23.99 | 720.00 | 23.99 | 508.50 | 23.99 |
May | 556.83 | 23.99 | 744.00 | 23.99 | 556.83 | 23.99 |
June | 574.83 | 23.99 | 720.00 | 23.99 | 574.83 | 23.99 |
July | 602.00 | 23.99 | 744.00 | 23.99 | 602.00 | 23.99 |
August | 596.83 | 23.99 | 744.00 | 23.99 | 596.83 | 23.99 |
September | 535.67 | 23.99 | 720.00 | 23.99 | 535.67 | 23.99 |
October | 519.50 | 23.99 | 744.00 | 23.99 | 519.50 | 23.99 |
November | 476.00 | 23.99 | 713.67 | 23.99 | 476.00 | 23.99 |
December | 450.83 | 23.99 | 733.83 | 23.99 | 450.83 | 23.99 |
Annual Sum or Average | 6166.17 | 23.99 | 8679.67 | 23.99 | 6156.17 | 23.99 |
Minimum of Months | 422.33 | 23.97 | 644.33 | 23.98 | 413.50 | 23.98 |
Maximum of Months | 602.00 | 23.99 | 744.00 | 23.99 | 602.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 577.50 | 21.00 | 577.50 | 21.00 |
February | 672.00 | 21.03 | 316.50 | 21.02 | 316.50 | 21.01 |
March | 744.00 | 21.27 | 153.00 | 21.22 | 153.00 | 21.19 |
April | 646.83 | 21.85 | 58.33 | 22.00 | 11.50 | 22.01 |
May | 538.33 | 23.18 | 131.67 | 23.32 | 30.67 | 23.34 |
June | 245.67 | 23.39 | 446.33 | 23.78 | 88.50 | 23.80 |
July | 159.50 | 23.94 | 668.50 | 23.97 | 150.50 | 23.97 |
August | 164.00 | 23.89 | 609.17 | 23.96 | 139.83 | 23.96 |
September | 396.83 | 22.86 | 220.67 | 23.26 | 24.67 | 23.29 |
October | 744.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
November | 720.00 | 21.32 | 204.17 | 21.25 | 204.17 | 21.20 |
December | 744.00 | 21.00 | 500.17 | 21.00 | 500.17 | 21.00 |
Annual Sum or Average | 6519.17 | 21.78 | 3886.00 | 22.10 | 2197.00 | 22.01 |
Minimum of Months | 159.50 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.94 | 668.50 | 23.97 | 577.50 | 23.97 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.43421 | 22.12191 | -0.1824 | 5.83691 |
February | 672.00000 | 21.91087 | 24.86109 | -0.2954 | 6.96089 |
March | 744.00000 | 21.42763 | 30.97926 | -0.3810 | 8.16926 |
April | 720.00000 | 21.24380 | 37.84444 | -0.3914 | 8.38759 |
May | 744.00000 | 21.35600 | 51.55087 | -1.4542 | 48.47825 |
June | 720.00000 | 21.83029 | 59.19781 | -1.2319 | 36.97922 |
July | 744.00000 | 22.32827 | 61.82270 | -1.0322 | 27.67275 |
August | 744.00000 | 22.90923 | 58.51805 | -0.8401 | 20.10823 |
September | 720.00000 | 23.34222 | 45.02799 | -0.7713 | 17.79379 |
October | 744.00000 | 23.52223 | 32.20409 | 0.16380 | 5.66033 |
November | 720.00000 | 23.46726 | 29.45874 | 0.12981 | 5.54439 |
December | 744.00000 | 23.10268 | 24.64784 | 0.00371 | 5.13349 |
Annual Sum or Average | 8760.00000 | 22.40959 | 39.94292 | -0.5250 | 16.46271 |
Minimum of Months | 672.00000 | 21.24380 | 22.12191 | -1.4542 | 5.13349 |
Maximum of Months | 744.00000 | 23.52223 | 61.82270 | 0.16380 | 48.47825 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08595 | 22.52639 | -0.6190 | 13.59180 |
February | 672.00000 | 21.17836 | 24.93543 | -0.5330 | 11.90192 |
March | 744.00000 | 21.34824 | 30.43129 | -0.4155 | 9.76811 |
April | 720.00000 | 21.82664 | 36.04642 | -0.2203 | 8.60318 |
May | 744.00000 | 22.37608 | 48.67088 | -1.0125 | 28.77705 |
June | 720.00000 | 23.10339 | 55.44045 | -0.6846 | 17.81730 |
July | 744.00000 | 23.52827 | 58.52422 | -0.4982 | 11.24785 |
August | 744.00000 | 23.49682 | 57.14686 | -0.5176 | 11.70539 |
September | 720.00000 | 22.81248 | 45.59913 | -0.8486 | 24.56741 |
October | 744.00000 | 21.81616 | 34.69179 | -0.2109 | 7.58929 |
November | 720.00000 | 21.26519 | 32.14883 | -0.4412 | 10.25491 |
December | 744.00000 | 21.15335 | 25.96778 | -0.5689 | 12.56836 |
Annual Sum or Average | 8760.00000 | 22.08815 | 39.43006 | -0.5476 | 14.03622 |
Minimum of Months | 672.00000 | 21.08595 | 22.52639 | -1.0125 | 7.58929 |
Maximum of Months | 744.00000 | 23.52827 | 58.52422 | -0.2109 | 28.77705 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04157 | 23.37336 | -0.5178 | 10.73811 |
February | 672.00000 | 21.13995 | 25.66894 | -0.4649 | 9.76337 |
March | 744.00000 | 21.31695 | 31.09519 | -0.3712 | 8.21507 |
April | 720.00000 | 21.71715 | 36.86302 | -0.2221 | 6.97248 |
May | 744.00000 | 22.18136 | 49.52563 | -1.0873 | 30.61023 |
June | 720.00000 | 22.66374 | 56.96455 | -0.8586 | 21.67343 |
July | 744.00000 | 22.93508 | 60.37144 | -0.7340 | 16.91730 |
August | 744.00000 | 22.92773 | 58.97397 | -0.7470 | 17.25244 |
September | 720.00000 | 22.53995 | 46.83094 | -0.9682 | 26.28839 |
October | 744.00000 | 21.79666 | 35.15414 | -0.2080 | 6.25926 |
November | 720.00000 | 21.36480 | 32.49921 | -0.3526 | 8.17788 |
December | 744.00000 | 21.08175 | 26.88969 | -0.4770 | 9.86140 |
Annual Sum or Average | 8760.00000 | 21.89644 | 40.43931 | -0.5849 | 14.41701 |
Minimum of Months | 672.00000 | 21.04157 | 23.37336 | -1.0873 | 6.25926 |
Maximum of Months | 744.00000 | 22.93508 | 60.37144 | -0.2080 | 30.61023 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99979 | 16.64066 | 0.71344 | 16.55097 |
February | 672.00000 | 23.99979 | 18.65799 | 0.74659 | 17.62284 |
March | 744.00000 | 23.99979 | 23.43473 | 0.81244 | 19.73087 |
April | 720.00000 | 23.99978 | 29.02304 | 0.87702 | 22.11172 |
May | 744.00000 | 23.99975 | 40.95495 | 0.35709 | 9.44392 |
June | 720.00000 | 23.99975 | 48.83764 | 0.44143 | 10.76557 |
July | 744.00000 | 23.99972 | 52.62716 | 0.47811 | 11.30684 |
August | 744.00000 | 23.99972 | 51.33640 | 0.46756 | 11.19433 |
September | 720.00000 | 23.99977 | 39.51467 | 0.35649 | 9.42986 |
October | 744.00000 | 23.99979 | 27.48012 | 0.87119 | 21.75858 |
November | 720.00000 | 23.99980 | 24.75110 | 0.81728 | 19.96449 |
December | 744.00000 | 23.99981 | 19.61156 | 0.74760 | 17.53446 |
Annual Sum or Average | 8760.00000 | 23.99977 | 32.82430 | 0.63984 | 15.60194 |
Minimum of Months | 672.00000 | 23.99972 | 16.64066 | 0.35649 | 9.42986 |
Maximum of Months | 744.00000 | 23.99981 | 52.62716 | 0.87702 | 22.11172 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.07024 | 25.57530 | -0.5111 | 10.86684 |
February | 672.00000 | 21.20275 | 27.82213 | -0.4178 | 9.32669 |
March | 744.00000 | 21.35879 | 33.30010 | -0.3074 | 7.63480 |
April | 720.00000 | 21.66828 | 39.23091 | -0.1573 | 6.89202 |
May | 744.00000 | 21.85564 | 52.72382 | -1.0507 | 29.18646 |
June | 720.00000 | 22.17763 | 60.73487 | -0.8523 | 21.63844 |
July | 744.00000 | 22.34715 | 64.54377 | -0.7477 | 17.62473 |
August | 744.00000 | 22.40835 | 62.91743 | -0.7358 | 17.31983 |
September | 720.00000 | 22.25968 | 49.85997 | -0.8965 | 24.59641 |
October | 744.00000 | 21.77773 | 37.49475 | -0.1217 | 6.17803 |
November | 720.00000 | 21.35753 | 34.80374 | -0.3166 | 8.13772 |
December | 744.00000 | 21.13592 | 29.08425 | -0.4625 | 9.99317 |
Annual Sum or Average | 8760.00000 | 21.72093 | 43.26774 | -0.5491 | 14.14248 |
Minimum of Months | 672.00000 | 21.07024 | 25.57530 | -1.0507 | 6.17803 |
Maximum of Months | 744.00000 | 22.40835 | 64.54377 | -0.1217 | 29.18646 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35468 | 25.67627 | -0.4049 | 8.78719 |
February | 672.00000 | 21.55522 | 27.78781 | -0.3295 | 7.87315 |
March | 744.00000 | 21.85570 | 33.00828 | -0.2096 | 6.52635 |
April | 720.00000 | 22.22592 | 38.71879 | -0.0672 | 6.12693 |
May | 744.00000 | 22.62630 | 51.17935 | -0.8930 | 22.76296 |
June | 720.00000 | 22.94547 | 58.85990 | -0.7136 | 16.84122 |
July | 744.00000 | 23.11734 | 62.47064 | -0.6204 | 13.81364 |
August | 744.00000 | 23.15266 | 60.97291 | -0.6181 | 13.68752 |
September | 720.00000 | 22.93748 | 48.71677 | -0.7843 | 19.40076 |
October | 744.00000 | 22.42530 | 36.86915 | -0.0229 | 5.46432 |
November | 720.00000 | 21.89697 | 34.34058 | -0.1915 | 6.74092 |
December | 744.00000 | 21.50331 | 29.05135 | -0.3429 | 7.85739 |
Annual Sum or Average | 8760.00000 | 22.30360 | 42.39235 | -0.4339 | 11.34143 |
Minimum of Months | 672.00000 | 21.35468 | 25.67627 | -0.8930 | 5.46432 |
Maximum of Months | 744.00000 | 23.15266 | 62.47064 | -0.0229 | 22.76296 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50726 | 25.27776 | -0.7854 | 18.59775 |
February | 672.00000 | 20.69133 | 29.29191 | -0.6787 | 15.56510 |
March | 744.00000 | 20.97634 | 35.36177 | -0.5301 | 11.76901 |
April | 720.00000 | 21.27885 | 41.40028 | -0.3567 | 9.01623 |
May | 744.00000 | 21.63699 | 51.63663 | -1.2832 | 40.48447 |
June | 720.00000 | 21.70675 | 54.59494 | -1.1733 | 35.42583 |
July | 744.00000 | 21.77030 | 55.79032 | -1.1084 | 32.45174 |
August | 744.00000 | 21.76081 | 55.94142 | -1.1297 | 33.40581 |
September | 720.00000 | 21.61328 | 48.76525 | -1.2894 | 41.12763 |
October | 744.00000 | 21.32129 | 41.88896 | -0.3615 | 8.38207 |
November | 720.00000 | 20.84115 | 37.38522 | -0.5727 | 12.90981 |
December | 744.00000 | 20.59941 | 28.83367 | -0.7321 | 16.90531 |
Annual Sum or Average | 8760.00000 | 21.22823 | 42.24984 | -0.8346 | 23.04682 |
Minimum of Months | 672.00000 | 20.50726 | 25.27776 | -1.2894 | 8.38207 |
Maximum of Months | 744.00000 | 21.77030 | 55.94142 | -0.3567 | 41.12763 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43432 | 25.42631 | -0.8279 | 20.09622 |
February | 672.00000 | 20.53184 | 29.61473 | -0.7420 | 17.35120 |
March | 744.00000 | 20.77903 | 35.75200 | -0.5933 | 13.15573 |
April | 720.00000 | 21.26510 | 41.72973 | -0.3767 | 9.55577 |
May | 744.00000 | 21.91889 | 51.66763 | -1.2132 | 37.93344 |
June | 720.00000 | 22.23299 | 54.51576 | -1.0236 | 30.62951 |
July | 744.00000 | 22.47150 | 56.21757 | -0.9063 | 25.71576 |
August | 744.00000 | 22.37186 | 56.56200 | -0.9608 | 27.34293 |
September | 720.00000 | 21.85419 | 49.17476 | -1.2467 | 39.66636 |
October | 744.00000 | 21.12297 | 42.42741 | -0.4316 | 9.41554 |
November | 720.00000 | 20.69134 | 37.72403 | -0.6255 | 14.16008 |
December | 744.00000 | 20.45679 | 29.08040 | -0.7846 | 18.55941 |
Annual Sum or Average | 8760.00000 | 21.34909 | 42.56075 | -0.8115 | 21.98623 |
Minimum of Months | 672.00000 | 20.43432 | 25.42631 | -1.2467 | 9.41554 |
Maximum of Months | 744.00000 | 22.47150 | 56.56200 | -0.3767 | 39.66636 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64742 | 24.26312 | -0.6993 | 15.84243 |
February | 672.00000 | 20.79195 | 28.32986 | -0.6282 | 13.81823 |
March | 744.00000 | 21.03773 | 34.44973 | -0.5028 | 10.60529 |
April | 720.00000 | 21.32122 | 40.61773 | -0.3696 | 8.44106 |
May | 744.00000 | 21.73204 | 49.87077 | -1.3180 | 41.91277 |
June | 720.00000 | 22.01426 | 54.70271 | -1.1644 | 34.82633 |
July | 744.00000 | 22.18415 | 57.84739 | -1.0824 | 31.05709 |
August | 744.00000 | 22.10541 | 57.25116 | -1.1227 | 32.73018 |
September | 720.00000 | 21.73468 | 48.43344 | -1.3302 | 42.53699 |
October | 744.00000 | 21.26388 | 40.75804 | -0.3860 | 8.25983 |
November | 720.00000 | 20.98376 | 36.00400 | -0.5125 | 11.07601 |
December | 744.00000 | 20.71819 | 28.07149 | -0.6528 | 14.34880 |
Annual Sum or Average | 8760.00000 | 21.38122 | 41.79133 | -0.8153 | 22.16649 |
Minimum of Months | 672.00000 | 20.64742 | 24.26312 | -1.3302 | 8.25983 |
Maximum of Months | 744.00000 | 22.18415 | 57.84739 | -0.3696 | 42.53699 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50371 | 25.26681 | -0.7846 | 18.57995 |
February | 672.00000 | 20.69322 | 29.28034 | -0.6802 | 15.55781 |
March | 744.00000 | 21.04098 | 35.23101 | -0.5140 | 11.41937 |
April | 720.00000 | 21.31563 | 41.27423 | -0.3575 | 9.07990 |
May | 744.00000 | 21.70938 | 50.78763 | -1.2546 | 39.14516 |
June | 720.00000 | 21.74085 | 53.91257 | -1.1611 | 34.91476 |
July | 744.00000 | 21.79174 | 55.27803 | -1.1068 | 32.42250 |
August | 744.00000 | 21.78689 | 55.49922 | -1.1281 | 33.35436 |
September | 720.00000 | 21.66484 | 48.38281 | -1.2713 | 40.25529 |
October | 744.00000 | 21.37378 | 41.81205 | -0.3522 | 8.23991 |
November | 720.00000 | 20.83387 | 37.40338 | -0.5752 | 12.98459 |
December | 744.00000 | 20.57688 | 28.84811 | -0.7369 | 17.04477 |
Annual Sum or Average | 8760.00000 | 21.25575 | 41.98205 | -0.8279 | 22.79189 |
Minimum of Months | 672.00000 | 20.50371 | 25.26681 | -1.2713 | 8.23991 |
Maximum of Months | 744.00000 | 21.79174 | 55.49922 | -0.3522 | 40.25529 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43763 | 25.40801 | -0.8264 | 20.06790 |
February | 672.00000 | 20.53081 | 29.59764 | -0.7447 | 17.42395 |
March | 744.00000 | 20.83212 | 35.62297 | -0.5796 | 12.72891 |
April | 720.00000 | 21.26773 | 41.68169 | -0.3848 | 9.55305 |
May | 744.00000 | 21.94226 | 50.97196 | -1.1991 | 36.87857 |
June | 720.00000 | 22.24152 | 54.11097 | -1.0177 | 30.13623 |
July | 744.00000 | 22.48890 | 55.94583 | -0.9048 | 25.67006 |
August | 744.00000 | 22.34855 | 56.31087 | -0.9734 | 27.44151 |
September | 720.00000 | 21.88903 | 48.73015 | -1.2342 | 38.86833 |
October | 744.00000 | 21.12922 | 42.41056 | -0.4323 | 9.19864 |
November | 720.00000 | 20.67854 | 37.74760 | -0.6298 | 14.26544 |
December | 744.00000 | 20.45363 | 29.07435 | -0.7866 | 18.66086 |
Annual Sum or Average | 8760.00000 | 21.35827 | 42.36966 | -0.8099 | 21.76055 |
Minimum of Months | 672.00000 | 20.43763 | 25.40801 | -1.2342 | 9.19864 |
Maximum of Months | 744.00000 | 22.48890 | 56.31087 | -0.3848 | 38.86833 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.45490 | 25.69903 | -0.8533 | 20.98474 |
February | 672.00000 | 20.60480 | 29.88416 | -0.7451 | 17.65857 |
March | 744.00000 | 20.86144 | 36.12849 | -0.5880 | 13.30750 |
April | 720.00000 | 21.21473 | 42.13462 | -0.3871 | 9.83515 |
May | 744.00000 | 21.62617 | 52.52429 | -1.2884 | 40.95402 |
June | 720.00000 | 21.69514 | 55.37407 | -1.1705 | 35.54881 |
July | 744.00000 | 21.76351 | 56.68933 | -1.1001 | 32.29307 |
August | 744.00000 | 21.74940 | 57.19314 | -1.1266 | 33.45699 |
September | 720.00000 | 21.57265 | 49.76800 | -1.3145 | 42.59741 |
October | 744.00000 | 21.23724 | 42.78596 | -0.4011 | 9.16337 |
November | 720.00000 | 20.73910 | 38.27220 | -0.6320 | 14.57637 |
December | 744.00000 | 20.51617 | 29.35068 | -0.8007 | 19.15058 |
Annual Sum or Average | 8760.00000 | 21.17276 | 43.05403 | -0.8682 | 24.16381 |
Minimum of Months | 672.00000 | 20.45490 | 25.69903 | -1.3145 | 9.16337 |
Maximum of Months | 744.00000 | 21.76351 | 57.19314 | -0.3871 | 42.59741 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.41534 | 25.81520 | -0.8894 | 22.36256 |
February | 672.00000 | 20.47268 | 30.18377 | -0.8040 | 19.44219 |
March | 744.00000 | 20.68320 | 36.52143 | -0.6493 | 14.72930 |
April | 720.00000 | 21.21017 | 42.41211 | -0.4061 | 10.48127 |
May | 744.00000 | 21.96523 | 52.21253 | -1.1993 | 38.01612 |
June | 720.00000 | 22.28307 | 54.82058 | -0.9982 | 30.71988 |
July | 744.00000 | 22.51317 | 56.46056 | -0.8788 | 25.59997 |
August | 744.00000 | 22.39882 | 57.14343 | -0.9425 | 27.30406 |
September | 720.00000 | 21.82244 | 49.99613 | -1.2682 | 41.15992 |
October | 744.00000 | 21.01890 | 43.39662 | -0.4775 | 10.44955 |
November | 720.00000 | 20.60617 | 38.61139 | -0.6827 | 15.86738 |
December | 744.00000 | 20.42367 | 29.54478 | -0.8445 | 20.65952 |
Annual Sum or Average | 8760.00000 | 21.32290 | 43.16242 | -0.8370 | 23.07942 |
Minimum of Months | 672.00000 | 20.41534 | 25.81520 | -1.2682 | 10.44955 |
Maximum of Months | 744.00000 | 22.51317 | 57.14343 | -0.4061 | 41.15992 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.83501 | 26.83616 | -0.6787 | 15.74095 |
February | 672.00000 | 21.01640 | 30.63125 | -0.5726 | 13.11415 |
March | 744.00000 | 21.23731 | 36.27102 | -0.4516 | 10.54413 |
April | 720.00000 | 21.36031 | 42.01631 | -0.3428 | 8.93872 |
May | 744.00000 | 21.66607 | 51.58922 | -1.2953 | 41.19909 |
June | 720.00000 | 21.71257 | 55.28514 | -1.2099 | 37.16236 |
July | 744.00000 | 21.75392 | 57.14477 | -1.1566 | 34.67787 |
August | 744.00000 | 21.74853 | 56.63490 | -1.1640 | 35.05999 |
September | 720.00000 | 21.66269 | 48.90939 | -1.2780 | 40.77102 |
October | 744.00000 | 21.52740 | 42.25855 | -0.2856 | 7.76515 |
November | 720.00000 | 21.11375 | 38.12618 | -0.4853 | 11.30898 |
December | 744.00000 | 20.91834 | 30.28033 | -0.6274 | 14.71230 |
Annual Sum or Average | 8760.00000 | 21.38143 | 43.06644 | -0.7971 | 22.63921 |
Minimum of Months | 672.00000 | 20.83501 | 26.83616 | -1.2953 | 7.76515 |
Maximum of Months | 744.00000 | 21.75392 | 57.14477 | -0.2856 | 41.19909 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.52473 | 25.37344 | -0.3561 | 8.25952 |
February | 672.00000 | 21.64089 | 27.53716 | -0.2923 | 7.63847 |
March | 744.00000 | 21.91088 | 32.77150 | -0.1549 | 6.21839 |
April | 720.00000 | 22.21699 | 38.56680 | -0.0069 | 6.02800 |
May | 744.00000 | 22.62181 | 50.90808 | -0.7711 | 18.70460 |
June | 720.00000 | 22.84777 | 58.76907 | -0.6058 | 13.83543 |
July | 744.00000 | 22.91222 | 62.63159 | -0.5473 | 12.11432 |
August | 744.00000 | 22.85627 | 61.45972 | -0.5860 | 13.09876 |
September | 720.00000 | 22.59859 | 49.31384 | -0.7905 | 19.67771 |
October | 744.00000 | 22.15090 | 37.05397 | -0.0389 | 5.69328 |
November | 720.00000 | 21.87830 | 34.20876 | -0.1616 | 6.60056 |
December | 744.00000 | 21.62267 | 28.77608 | -0.2958 | 7.39089 |
Annual Sum or Average | 8760.00000 | 22.23501 | 42.36986 | -0.3846 | 10.44932 |
Minimum of Months | 672.00000 | 21.52473 | 25.37344 | -0.7905 | 5.69328 |
Maximum of Months | 744.00000 | 22.91222 | 62.63159 | -0.0069 | 19.67771 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.76240 | 25.14545 | -0.2623 | 7.21271 |
February | 672.00000 | 21.90490 | 27.23591 | -0.1940 | 6.86056 |
March | 744.00000 | 22.25472 | 32.30299 | -0.0405 | 5.84748 |
April | 720.00000 | 22.57138 | 37.97005 | 0.10476 | 6.17440 |
May | 744.00000 | 22.91077 | 50.17217 | -0.6447 | 14.77919 |
June | 720.00000 | 23.10398 | 57.97005 | -0.4929 | 11.06832 |
July | 744.00000 | 23.15623 | 61.81071 | -0.4399 | 9.77172 |
August | 744.00000 | 23.09835 | 60.66108 | -0.4795 | 10.59523 |
September | 720.00000 | 22.87881 | 48.65290 | -0.6682 | 15.72692 |
October | 744.00000 | 22.53145 | 36.44549 | 0.07935 | 5.76697 |
November | 720.00000 | 22.20115 | 33.72569 | -0.0520 | 6.23541 |
December | 744.00000 | 21.88347 | 28.48241 | -0.1973 | 6.53476 |
Annual Sum or Average | 8760.00000 | 22.52470 | 41.80218 | -0.2746 | 8.88766 |
Minimum of Months | 672.00000 | 21.76240 | 25.14545 | -0.6682 | 5.76697 |
Maximum of Months | 744.00000 | 23.15623 | 61.81071 | 0.10476 | 15.72692 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99039 | 25.15086 | 0.88217 | 22.85277 |
February | 672.00000 | 23.97830 | 26.92547 | 0.92505 | 24.64888 |
March | 744.00000 | 23.99081 | 30.98103 | 1.00904 | 27.88911 |
April | 720.00000 | 23.99093 | 36.23070 | 1.09179 | 31.63147 |
May | 744.00000 | 23.99122 | 47.63137 | 0.66809 | 18.06184 |
June | 720.00000 | 23.99158 | 55.24887 | 0.76745 | 20.86924 |
July | 744.00000 | 23.99180 | 58.94204 | 0.80914 | 22.09823 |
August | 744.00000 | 23.99163 | 57.68374 | 0.78203 | 21.22326 |
September | 720.00000 | 23.99129 | 46.25899 | 0.65516 | 17.61174 |
October | 744.00000 | 23.99085 | 34.69097 | 1.07218 | 30.61060 |
November | 720.00000 | 23.99087 | 32.41990 | 0.99989 | 27.51398 |
December | 744.00000 | 23.99084 | 27.84457 | 0.92019 | 24.16476 |
Annual Sum or Average | 8760.00000 | 23.99013 | 40.08035 | 0.88153 | 24.09008 |
Minimum of Months | 672.00000 | 23.97830 | 25.15086 | 0.65516 | 17.61174 |
Maximum of Months | 744.00000 | 23.99180 | 58.94204 | 1.09179 | 31.63147 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00009 | 20.10467 | -0.6112 | 12.92559 |
February | 672.00000 | 21.00008 | 22.60200 | -0.5772 | 12.11567 |
March | 744.00000 | 21.00036 | 28.37978 | -0.5112 | 10.55684 |
April | 720.00000 | 21.11557 | 34.93813 | -0.4138 | 9.01369 |
May | 744.00000 | 21.31906 | 48.71737 | -1.4131 | 46.37284 |
June | 720.00000 | 21.86125 | 56.52653 | -1.1705 | 34.30288 |
July | 744.00000 | 22.10972 | 60.34130 | -1.0576 | 28.77467 |
August | 744.00000 | 22.06881 | 58.89175 | -1.0816 | 29.82279 |
September | 720.00000 | 21.65840 | 45.96666 | -1.3070 | 41.17199 |
October | 744.00000 | 21.03740 | 33.38776 | -0.4261 | 8.87874 |
November | 720.00000 | 21.01324 | 29.96225 | -0.4922 | 10.28713 |
December | 744.00000 | 21.00005 | 23.62252 | -0.5748 | 11.97009 |
Annual Sum or Average | 8760.00000 | 21.35084 | 38.71634 | -0.8044 | 21.39961 |
Minimum of Months | 672.00000 | 21.00005 | 20.10467 | -1.4131 | 8.87874 |
Maximum of Months | 744.00000 | 22.10972 | 60.34130 | -0.4138 | 46.37284 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00056 | 24.48602 | -0.5657 | 11.76639 |
February | 672.00000 | 21.00146 | 26.91027 | -0.5375 | 11.13015 |
March | 744.00000 | 21.04254 | 32.57477 | -0.4782 | 9.86914 |
April | 720.00000 | 21.35176 | 38.66042 | -0.3547 | 8.25788 |
May | 744.00000 | 21.91911 | 51.26197 | -1.2516 | 38.09966 |
June | 720.00000 | 22.58953 | 58.44755 | -0.9690 | 25.51472 |
July | 744.00000 | 22.94425 | 61.68569 | -0.8214 | 19.39118 |
August | 744.00000 | 22.83961 | 60.54989 | -0.8668 | 20.98250 |
September | 720.00000 | 22.33245 | 48.51183 | -1.1200 | 32.55303 |
October | 744.00000 | 21.16730 | 37.34733 | -0.4045 | 8.53033 |
November | 720.00000 | 21.05162 | 34.15280 | -0.4732 | 9.86311 |
December | 744.00000 | 21.00051 | 28.02164 | -0.5403 | 11.14804 |
Annual Sum or Average | 8760.00000 | 21.69077 | 41.97373 | -0.6996 | 17.28962 |
Minimum of Months | 672.00000 | 21.00051 | 24.48602 | -1.2516 | 8.25788 |
Maximum of Months | 744.00000 | 22.94425 | 61.68569 | -0.3547 | 38.09966 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00204 | 24.05453 | -0.5992 | 12.62676 |
February | 672.00000 | 21.02641 | 26.45992 | -0.5544 | 11.61764 |
March | 744.00000 | 21.26509 | 31.84577 | -0.4323 | 9.30475 |
April | 720.00000 | 22.06518 | 36.86754 | -0.1834 | 7.51937 |
May | 744.00000 | 23.35480 | 47.34222 | -0.7629 | 18.38378 |
June | 720.00000 | 23.77024 | 53.95648 | -0.5466 | 11.97934 |
July | 744.00000 | 23.95904 | 57.26011 | -0.4491 | 9.28618 |
August | 744.00000 | 23.94314 | 56.22951 | -0.4716 | 9.75261 |
September | 720.00000 | 23.34610 | 45.53658 | -0.7673 | 19.57349 |
October | 744.00000 | 21.85585 | 35.87959 | -0.2403 | 6.63217 |
November | 720.00000 | 21.31756 | 33.24704 | -0.4197 | 9.45729 |
December | 744.00000 | 21.00427 | 27.57513 | -0.5647 | 11.73853 |
Annual Sum or Average | 8760.00000 | 22.33321 | 39.76685 | -0.4991 | 11.48122 |
Minimum of Months | 672.00000 | 21.00204 | 24.05453 | -0.7673 | 6.63217 |
Maximum of Months | 744.00000 | 23.95904 | 57.26011 | -0.1834 | 19.57349 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.07100 | 20.29729 | -0.5725 | 12.02661 |
February | 672.00000 | 21.31869 | 24.05024 | -0.4841 | 10.34730 |
March | 744.00000 | 21.88688 | 30.35609 | -0.3018 | 7.94887 |
April | 720.00000 | 22.84517 | 36.66951 | -0.0316 | 6.25676 |
May | 744.00000 | 23.85018 | 46.64490 | -0.6726 | 14.97293 |
June | 720.00000 | 23.95949 | 52.79398 | -0.5562 | 11.63446 |
July | 744.00000 | 23.99989 | 56.15576 | -0.5027 | 10.30728 |
August | 744.00000 | 23.99990 | 54.54578 | -0.5159 | 10.61076 |
September | 720.00000 | 23.89014 | 44.33968 | -0.6475 | 14.23638 |
October | 744.00000 | 23.32060 | 36.11541 | 0.07566 | 5.39037 |
November | 720.00000 | 22.24061 | 31.74166 | -0.2078 | 7.72110 |
December | 744.00000 | 21.15680 | 23.75483 | -0.5199 | 10.80320 |
Annual Sum or Average | 8760.00000 | 22.80227 | 38.20198 | -0.4114 | 10.18917 |
Minimum of Months | 672.00000 | 21.07100 | 20.29729 | -0.6726 | 5.39037 |
Maximum of Months | 744.00000 | 23.99990 | 56.15576 | 0.07566 | 14.97293 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.670124E+09 | 14719.55 | 16-JAN-16:14 | 189.48 | 0.219246E+10 | 0.00 | 0.286259E+10 | 0.83 | 3.27 | 01-JAN-04:40 | 0.00 | 0.00 |
February | 0.101881E+10 | 17989.24 | 22-FEB-16:14 | 252.48 | 0.333327E+10 | 0.00 | 0.435209E+10 | 1.23 | 3.27 | 03-FEB-16:14 | 0.00 | 0.00 |
March | 0.406452E+10 | 44870.59 | 25-MAR-15:11 | 430.47 | 0.129664E+11 | 0.00 | 0.170310E+11 | 1.89 | 3.27 | 01-MAR-03:30 | 0.00 | 0.00 |
April | 0.256351E+11 | 120090.97 | 16-APR-15:13 | 537.78 | 0.819624E+11 | 0.00 | 0.107598E+12 | 2.42 | 3.87 | 16-APR-21:53 | 0.00 | 0.00 |
May | 0.598272E+11 | 119979.49 | 31-MAY-18:03 | 725.82 | 0.189586E+12 | 0.00 | 0.249414E+12 | 3.11 | 4.01 | 29-MAY-18:03 | 0.00 | 0.00 |
June | 0.134722E+12 | 160486.30 | 11-JUN-15:13 | 709.19 | 0.449733E+12 | 0.00 | 0.584455E+12 | 3.22 | 4.27 | 11-JUN-21:53 | 0.00 | 0.00 |
July | 0.179368E+12 | 172307.58 | 26-JUL-18:03 | 744.00 | 0.625185E+12 | 0.00 | 0.804553E+12 | 3.38 | 4.38 | 05-JUL-21:52 | 0.00 | 0.00 |
August | 0.159322E+12 | 181173.07 | 04-AUG-15:13 | 744.00 | 0.545785E+12 | 0.00 | 0.705107E+12 | 3.32 | 4.39 | 28-AUG-21:53 | 0.00 | 0.00 |
September | 0.782505E+11 | 139106.12 | 06-SEP-15:13 | 681.61 | 0.245058E+12 | 0.00 | 0.323309E+12 | 3.00 | 4.13 | 11-SEP-21:53 | 0.00 | 0.00 |
October | 0.132477E+11 | 70499.72 | 20-OCT-15:11 | 562.00 | 0.417690E+11 | 0.00 | 0.550167E+11 | 2.45 | 3.30 | 20-OCT-15:11 | 0.00 | 0.00 |
November | 0.378688E+10 | 38884.25 | 05-NOV-15:11 | 392.45 | 0.122848E+11 | 0.00 | 0.160717E+11 | 1.78 | 3.27 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 0.123283E+10 | 16159.13 | 20-DEC-19:04 | 339.65 | 0.403349E+10 | 0.00 | 0.526632E+10 | 1.49 | 3.27 | 01-DEC-04:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.661145E+12 | 6308.94 | 0.221389E+13 | 0.00 | 0.287504E+13 | 2.35 | 0.00 | 0.00 | ||||
Minimum of Months | 0.670124E+09 | 14719.55 | 189.48 | 0.219246E+10 | 0.00 | 0.286259E+10 | 0.83 | 3.27 | 0.00 | 0.00 | ||
Maximum of Months | 0.179368E+12 | 181173.07 | 744.00 | 0.625185E+12 | 0.00 | 0.804553E+12 | 3.38 | 4.39 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.332795E+12 | 0.00 | 739.54 | 589193.59 | 19-JAN-09:03 | 0.00 | 46.06 | 58.94 | 2.25 | 0.00 | 0.21 | 0.98 | 19-JAN-09:03 |
February | 0.273325E+12 | 0.00 | 658.82 | 647695.93 | 02-FEB-09:03 | 0.00 | 45.46 | 58.46 | 2.04 | 0.00 | 0.19 | 1.08 | 02-FEB-09:03 |
March | 0.959919E+11 | 0.00 | 721.08 | 256966.96 | 09-MAR-16:11 | 0.00 | 44.89 | 58.58 | 0.65 | 0.00 | 0.06 | 0.43 | 09-MAR-16:11 |
April | 0.607405E+11 | 0.00 | 611.23 | 246568.29 | 27-APR-15:11 | 0.00 | 41.35 | 56.43 | 0.36 | 0.00 | 0.04 | 0.41 | 27-APR-15:11 |
May | 0.156767E+11 | 0.00 | 389.88 | 109375.62 | 02-MAY-08:05 | 0.00 | 39.57 | 50.52 | 0.07 | 0.00 | 0.01 | 0.18 | 02-MAY-08:05 |
June | 0.270149E+10 | 0.00 | 122.84 | 59249.29 | 01-JUN-15:14 | 0.00 | 45.41 | 48.32 | 0.01 | 0.00 | 0.00 | 0.10 | 01-JUN-15:14 |
July | 84027772.42 | 0.00 | 21.59 | 25757.49 | 02-JUL-21:56 | 0.00 | 46.51 | 46.92 | 0.00 | 0.00 | 0.00 | 0.04 | 02-JUL-21:56 |
August | 0.224155E+09 | 0.00 | 17.92 | 40385.02 | 07-AUG-08:07 | 0.00 | 46.22 | 46.55 | 0.00 | 0.00 | 0.00 | 0.07 | 07-AUG-08:07 |
September | 0.158431E+11 | 0.00 | 242.72 | 139501.30 | 29-SEP-02:50 | 0.00 | 41.92 | 47.64 | 0.08 | 0.00 | 0.01 | 0.23 | 29-SEP-02:50 |
October | 0.653131E+11 | 0.00 | 624.09 | 172787.83 | 26-OCT-08:03 | 0.00 | 44.12 | 57.74 | 0.35 | 0.00 | 0.04 | 0.29 | 26-OCT-08:03 |
November | 0.124175E+12 | 0.00 | 660.95 | 505999.58 | 26-NOV-07:00 | 0.00 | 45.51 | 57.95 | 0.86 | 0.00 | 0.08 | 0.84 | 26-NOV-07:00 |
December | 0.163766E+12 | 0.00 | 739.64 | 267621.96 | 11-DEC-09:03 | 0.00 | 46.59 | 58.75 | 1.21 | 0.00 | 0.10 | 0.45 | 11-DEC-09:03 |
Annual Sum or Average | 0.115064E+13 | 0.00 | 5550.30 | 0.00 | 44.47 | 53.88 | 0.65 | 0.00 | 0.06 | ||||
Minimum of Months | 84027772.42 | 0.00 | 17.92 | 25757.49 | 0.00 | 39.57 | 46.55 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.332795E+12 | 0.00 | 739.64 | 647695.93 | 0.00 | 46.59 | 58.94 | 2.25 | 0.00 | 0.21 | 1.08 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.167911E+09 | 0.00 | 159.19 | 0.167911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4813.70 | 13-JAN-06:10 | 4813.70 | 13-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.206656E+09 | 0.00 | 192.32 | 0.206656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4819.11 | 14-FEB-06:10 | 4819.11 | 14-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.370370E+10 | 0.00 | 253.96 | 0.370370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79436.07 | 19-MAR-16:20 | 79436.07 | 19-MAR-16:20 | 0.00 | 0.00 | 0.00 |
April | 0.465049E+11 | 0.00 | 245.59 | 0.395683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 282128.29 | 18-APR-10:35 | 205684.95 | 15-APR-17:15 | 0.00 | 0.00 | 0.00 |
May | 0.112684E+12 | 0.00 | 369.34 | 0.917133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 280476.30 | 29-MAY-18:03 | 213101.26 | 31-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.315828E+12 | 0.00 | 545.17 | 0.222640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 385838.66 | 26-JUN-06:53 | 231979.65 | 26-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.458684E+12 | 0.00 | 692.17 | 0.285396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 456131.63 | 17-JUL-19:10 | 229340.42 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.395247E+12 | 0.00 | 646.48 | 0.251928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 461107.01 | 28-AUG-19:40 | 225935.48 | 03-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.151987E+12 | 0.00 | 393.58 | 0.138791E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286203.10 | 11-SEP-10:35 | 225826.96 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.116608E+11 | 0.00 | 129.74 | 0.116608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144121.90 | 20-OCT-15:13 | 144121.90 | 20-OCT-15:13 | 0.00 | 0.00 | 0.00 |
November | 0.841698E+09 | 0.00 | 207.18 | 0.841698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26609.74 | 03-NOV-15:13 | 26609.74 | 03-NOV-15:13 | 0.00 | 0.00 | 0.00 |
December | 0.304193E+09 | 0.00 | 290.25 | 0.304193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4799.15 | 01-DEC-06:10 | 4799.15 | 01-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149782E+13 | 0.00 | 4124.98 | 0.104692E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.167911E+09 | 0.00 | 129.74 | 0.167911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4799.15 | 4799.15 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.458684E+12 | 0.00 | 692.17 | 0.285396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 461107.01 | 231979.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.189758E+09 | 0.00 | 16.00 | 0.189758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8515.76 | 19-MAR-16:00 | 8515.76 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.309722E+10 | 0.00 | 77.17 | 0.243844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26824.05 | 18-APR-12:15 | 18721.18 | 15-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.701504E+10 | 0.00 | 235.33 | 0.526282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29139.22 | 29-MAY-15:13 | 18523.62 | 31-MAY-15:12 | 0.00 | 0.00 | 0.00 |
June | 0.232110E+11 | 0.00 | 394.67 | 0.149667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39170.75 | 26-JUN-08:62 | 20066.40 | 11-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.350577E+11 | 0.00 | 518.17 | 0.197621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39681.85 | 17-JUL-19:00 | 18987.55 | 26-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.286108E+11 | 0.00 | 475.17 | 0.164955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43067.55 | 04-AUG-08:61 | 20410.24 | 04-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.103796E+11 | 0.00 | 268.33 | 0.886000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29549.17 | 11-SEP-08:15 | 19411.86 | 06-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.596936E+09 | 0.00 | 38.00 | 0.596936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15153.02 | 20-OCT-15:11 | 15153.02 | 20-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 22232930.82 | 0.00 | 6.67 | 22232930.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1791.45 | 03-NOV-15:11 | 1791.45 | 03-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108180E+12 | 0.00 | 2029.50 | 0.685945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.350577E+11 | 0.00 | 518.17 | 0.197621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43067.55 | 20410.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8107022.96 | 0.00 | 1.35 | 8107022.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12376.52 | 12-JAN-16:11 | 12376.52 | 12-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 68410179.82 | 0.00 | 13.92 | 67779777.53 | 0.00 | 0.00 | 0.00 | 0.00 | 14186.49 | 24-FEB-16:11 | 14186.49 | 24-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.238088E+09 | 0.00 | 58.01 | 0.180384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14186.25 | 24-MAR-15:11 | 14186.25 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.177502E+10 | 0.00 | 245.46 | 0.110865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14573.06 | 16-APR-08:61 | 14186.03 | 09-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.338258E+10 | 0.00 | 511.70 | 0.167299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15033.37 | 29-MAY-08:61 | 14185.66 | 02-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.645678E+10 | 0.00 | 589.86 | 0.334590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15595.87 | 25-JUN-08:61 | 12623.99 | 07-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.834084E+10 | 0.00 | 687.40 | 0.428627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16293.54 | 20-JUL-08:62 | 12499.11 | 10-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.740242E+10 | 0.00 | 678.74 | 0.357957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17449.30 | 31-AUG-08:62 | 12661.92 | 27-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.429472E+10 | 0.00 | 482.64 | 0.233545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15238.62 | 11-SEP-08:61 | 14186.28 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.735946E+09 | 0.00 | 156.75 | 0.478651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14186.83 | 19-OCT-15:11 | 14186.83 | 19-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.137263E+09 | 0.00 | 27.36 | 97877948.83 | 0.00 | 0.00 | 0.00 | 0.00 | 14181.11 | 04-NOV-15:11 | 14181.11 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 15055313.01 | 0.00 | 1.68 | 14878961.02 | 0.00 | 0.00 | 0.00 | 0.00 | 9272.54 | 02-DEC-16:11 | 9272.54 | 02-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328552E+11 | 0.00 | 3454.86 | 0.171765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8107022.96 | 0.00 | 1.35 | 8107022.96 | 0.00 | 0.00 | 0.00 | 0.00 | 9272.54 | 9272.54 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.834084E+10 | 0.00 | 687.40 | 0.428627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17449.30 | 14186.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4184636.13 | 0.00 | 0.67 | 4184636.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3538.60 | 12-JAN-16:13 | 3538.60 | 12-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 20588112.82 | 0.00 | 5.26 | 19784612.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13163.27 | 24-FEB-16:11 | 13163.27 | 24-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 78626823.90 | 0.00 | 25.59 | 61016035.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13571.38 | 24-MAR-15:11 | 13571.38 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.107264E+10 | 0.00 | 164.94 | 0.632243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14191.35 | 16-APR-21:51 | 13799.12 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.217761E+10 | 0.00 | 388.22 | 0.952953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14926.21 | 20-MAY-18:41 | 14926.21 | 20-MAY-18:41 | 0.00 | 0.00 | 0.00 |
June | 0.505256E+10 | 0.00 | 449.38 | 0.267344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17554.20 | 26-JUN-08:11 | 13681.98 | 16-JUN-16:51 | 0.00 | 0.00 | 0.00 |
July | 0.627102E+10 | 0.00 | 494.46 | 0.330714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16166.99 | 02-JUL-08:51 | 12868.45 | 23-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.516133E+10 | 0.00 | 488.49 | 0.242410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18154.08 | 03-AUG-07:51 | 13885.30 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.272400E+10 | 0.00 | 355.61 | 0.132549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14764.40 | 11-SEP-08:51 | 14611.06 | 24-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 0.207853E+09 | 0.00 | 66.67 | 0.124678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13510.89 | 29-OCT-15:11 | 13510.89 | 29-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 45303084.42 | 0.00 | 8.13 | 34556605.27 | 0.00 | 0.00 | 0.00 | 0.00 | 13795.15 | 04-NOV-15:11 | 13795.15 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 10801810.91 | 0.00 | 1.45 | 10630634.75 | 0.00 | 0.00 | 0.00 | 0.00 | 3521.72 | 17-DEC-19:04 | 3521.72 | 17-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228265E+11 | 0.00 | 2448.87 | 0.115702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4184636.13 | 0.00 | 0.67 | 4184636.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3521.72 | 3521.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.627102E+10 | 0.00 | 494.46 | 0.330714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18154.08 | 14926.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.979773E+09 | 0.00 | 50.97 | 0.933885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16467.18 | 28-MAR-13:25 | 16467.18 | 28-MAR-13:25 | 0.00 | 0.00 | 0.00 |
April | 0.855996E+10 | 0.00 | 221.46 | 0.467966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37740.06 | 15-APR-13:15 | 29808.51 | 15-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.189143E+11 | 0.00 | 562.56 | 0.834618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27467.81 | 31-MAY-13:30 | 21231.66 | 06-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.294654E+11 | 0.00 | 631.06 | 0.111319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30912.92 | 26-JUN-12:30 | 18928.11 | 26-JUN-12:50 | 0.00 | 0.00 | 0.00 |
July | 0.376281E+11 | 0.00 | 729.45 | 0.143159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32566.61 | 30-JUL-13:30 | 21605.76 | 30-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.379572E+11 | 0.00 | 733.08 | 0.153701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36282.75 | 22-AUG-13:30 | 27101.31 | 29-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.290639E+11 | 0.00 | 557.01 | 0.165293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43425.29 | 08-SEP-12:50 | 41292.99 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.125311E+11 | 0.00 | 346.64 | 0.106119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39816.39 | 20-OCT-13:00 | 39816.39 | 20-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.346745E+10 | 0.00 | 112.20 | 0.278502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37641.83 | 04-NOV-13:00 | 37641.83 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178567E+12 | 0.00 | 3944.43 | 0.847037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.379572E+11 | 0.00 | 733.08 | 0.165293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43425.29 | 41292.99 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 44630628.91 | 0.00 | 1.77 | 44630628.91 | 0.00 | 0.00 | 0.00 | 0.00 | 32388.77 | 14-JAN-09:02 | 32388.77 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.111073E+09 | 0.00 | 10.10 | 92814280.23 | 0.00 | 0.00 | 0.00 | 0.00 | 69982.67 | 26-FEB-09:01 | 69982.67 | 26-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.242101E+10 | 0.00 | 115.95 | 0.137139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72458.10 | 24-MAR-18:01 | 72458.10 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.986766E+10 | 0.00 | 263.98 | 0.601211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79136.49 | 16-APR-21:51 | 75052.14 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.260386E+11 | 0.00 | 419.65 | 0.146365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83700.79 | 11-MAY-21:42 | 76490.02 | 06-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.401033E+11 | 0.00 | 445.62 | 0.242005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97515.32 | 26-JUN-08:11 | 72144.22 | 21-JUN-21:01 | 0.00 | 0.00 | 0.00 |
July | 0.438893E+11 | 0.00 | 433.18 | 0.258417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88516.67 | 02-JUL-08:51 | 69900.49 | 13-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.390342E+11 | 0.00 | 416.55 | 0.220814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102557.12 | 03-AUG-07:51 | 69672.87 | 10-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.243098E+11 | 0.00 | 406.37 | 0.139120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81346.62 | 11-SEP-21:51 | 75396.91 | 19-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.686074E+10 | 0.00 | 303.34 | 0.402674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72514.66 | 12-OCT-18:03 | 72514.66 | 12-OCT-18:03 | 0.00 | 0.00 | 0.00 |
November | 0.303977E+10 | 0.00 | 128.85 | 0.123179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71026.33 | 04-NOV-18:01 | 71026.33 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 78645295.89 | 0.00 | 1.44 | 78645295.89 | 0.00 | 0.00 | 0.00 | 0.00 | 48763.20 | 03-DEC-09:01 | 48763.20 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195799E+12 | 0.00 | 2946.81 | 0.113530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 44630628.91 | 0.00 | 1.44 | 44630628.91 | 0.00 | 0.00 | 0.00 | 0.00 | 32388.77 | 32388.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.438893E+11 | 0.00 | 445.62 | 0.258417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102557.12 | 76490.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5533385.63 | 0.00 | 0.91 | 5533385.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3492.19 | 17-JAN-19:04 | 3492.19 | 17-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 46494672.83 | 0.00 | 10.20 | 36564572.79 | 0.00 | 0.00 | 0.00 | 0.00 | 12256.01 | 24-FEB-09:01 | 12256.01 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.202082E+09 | 0.00 | 70.59 | 0.130887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12911.02 | 24-MAR-15:11 | 12911.02 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.148922E+10 | 0.00 | 239.07 | 0.845911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12905.59 | 26-APR-08:61 | 12905.59 | 26-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.359694E+10 | 0.00 | 559.72 | 0.174593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13484.06 | 11-MAY-15:12 | 12822.42 | 02-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.656167E+10 | 0.00 | 616.54 | 0.343273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14270.64 | 14-JUN-18:02 | 11506.37 | 28-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.815833E+10 | 0.00 | 703.35 | 0.413801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14860.32 | 20-JUL-08:62 | 11538.56 | 28-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.715103E+10 | 0.00 | 695.33 | 0.339693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15905.57 | 31-AUG-08:62 | 11538.47 | 24-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.429816E+10 | 0.00 | 505.42 | 0.230241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13236.78 | 10-SEP-08:61 | 12772.37 | 30-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.563198E+09 | 0.00 | 157.48 | 0.329560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12911.61 | 24-OCT-15:11 | 12911.61 | 24-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 98710366.71 | 0.00 | 34.26 | 67803251.73 | 0.00 | 0.00 | 0.00 | 0.00 | 12906.61 | 04-NOV-15:11 | 12906.61 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 16569518.88 | 0.00 | 4.71 | 16433351.38 | 0.00 | 0.00 | 0.00 | 0.00 | 7011.63 | 03-DEC-09:01 | 7011.63 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321879E+11 | 0.00 | 3597.59 | 0.164487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5533385.63 | 0.00 | 0.91 | 5533385.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3492.19 | 3492.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.815833E+10 | 0.00 | 703.35 | 0.413801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15905.57 | 12911.61 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3643118.96 | 0.00 | 0.56 | 3643118.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3552.31 | 17-JAN-19:04 | 3552.31 | 17-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 13419777.30 | 0.00 | 3.56 | 12620181.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9554.93 | 24-FEB-09:01 | 9554.93 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 65946591.40 | 0.00 | 23.07 | 40015708.87 | 0.00 | 0.00 | 0.00 | 0.00 | 10659.40 | 24-MAR-15:11 | 10659.40 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.886680E+09 | 0.00 | 148.96 | 0.481915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14151.50 | 18-APR-08:51 | 12574.59 | 26-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.252152E+10 | 0.00 | 433.85 | 0.119593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14544.65 | 29-MAY-08:51 | 12261.87 | 21-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.517431E+10 | 0.00 | 476.59 | 0.274919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17209.85 | 26-JUN-07:52 | 12641.83 | 20-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.607266E+10 | 0.00 | 507.60 | 0.308323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15247.31 | 27-JUL-08:51 | 12706.67 | 24-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.500792E+10 | 0.00 | 504.14 | 0.233879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17164.25 | 03-AUG-07:51 | 12714.27 | 09-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.276211E+10 | 0.00 | 376.74 | 0.135867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14476.37 | 11-SEP-08:51 | 12538.75 | 06-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.133157E+09 | 0.00 | 51.01 | 65982614.96 | 0.00 | 0.00 | 0.00 | 0.00 | 11392.41 | 02-OCT-18:02 | 9786.90 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 19403252.42 | 0.00 | 5.22 | 13120753.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7558.35 | 04-NOV-08:62 | 7066.73 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 6959789.75 | 0.00 | 1.08 | 6805890.17 | 0.00 | 0.00 | 0.00 | 0.00 | 4109.32 | 05-DEC-09:03 | 4109.32 | 05-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226677E+11 | 0.00 | 2532.38 | 0.113499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3643118.96 | 0.00 | 0.56 | 3643118.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3552.31 | 3552.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.607266E+10 | 0.00 | 507.60 | 0.308323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17209.85 | 12714.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1696305.13 | 0.00 | 1.21 | 1580505.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1991.91 | 12-JAN-16:11 | 1991.91 | 12-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 16073696.48 | 0.00 | 11.41 | 15846020.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3685.89 | 24-FEB-16:11 | 3685.89 | 24-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 51630144.50 | 0.00 | 45.88 | 39762020.94 | 0.00 | 0.00 | 0.00 | 0.00 | 3685.93 | 23-MAR-18:01 | 3685.93 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.463918E+09 | 0.00 | 221.09 | 0.304992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3806.59 | 16-APR-08:61 | 3685.44 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.867955E+09 | 0.00 | 465.51 | 0.461201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4028.83 | 29-MAY-08:61 | 3685.60 | 02-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.168557E+10 | 0.00 | 572.10 | 0.920811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4186.79 | 25-JUN-08:61 | 3253.84 | 04-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.214665E+10 | 0.00 | 684.55 | 0.115581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4373.69 | 20-JUL-08:62 | 3286.28 | 14-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.185886E+10 | 0.00 | 673.36 | 0.934935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4640.44 | 31-AUG-08:62 | 3262.16 | 30-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.104988E+10 | 0.00 | 434.56 | 0.603404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4064.82 | 11-SEP-08:61 | 3685.45 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.176791E+09 | 0.00 | 120.85 | 0.121295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3685.95 | 24-OCT-15:11 | 3685.95 | 24-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 33928164.18 | 0.00 | 20.11 | 25372344.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3684.65 | 04-NOV-15:11 | 3684.65 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 2663574.44 | 0.00 | 1.54 | 2550821.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.20 | 02-DEC-16:11 | 1083.20 | 02-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835561E+10 | 0.00 | 3252.17 | 0.458756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1696305.13 | 0.00 | 1.21 | 1580505.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.20 | 1083.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.214665E+10 | 0.00 | 684.55 | 0.115581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4640.44 | 3685.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 936354.80 | 0.00 | 0.73 | 877110.70 | 0.00 | 0.00 | 0.00 | 0.00 | 894.30 | 09-JAN-16:14 | 894.30 | 09-JAN-16:14 | 0.00 | 0.00 | 0.00 |
February | 3685287.45 | 0.00 | 3.21 | 3437974.18 | 0.00 | 0.00 | 0.00 | 0.00 | 3338.67 | 24-FEB-16:11 | 3338.67 | 24-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 14111664.97 | 0.00 | 15.98 | 11268760.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3472.78 | 24-MAR-15:11 | 3472.78 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.281559E+09 | 0.00 | 148.57 | 0.175113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3763.30 | 16-APR-21:51 | 3577.11 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.563608E+09 | 0.00 | 353.97 | 0.269712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4032.06 | 21-MAY-19:41 | 4032.06 | 21-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.136580E+10 | 0.00 | 440.01 | 0.755803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4660.44 | 26-JUN-08:11 | 3544.43 | 16-JUN-16:51 | 0.00 | 0.00 | 0.00 |
July | 0.168063E+10 | 0.00 | 499.21 | 0.916420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4266.08 | 02-JUL-08:51 | 3501.06 | 23-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.133705E+10 | 0.00 | 492.36 | 0.649335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4862.23 | 03-AUG-07:51 | 3651.59 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.669276E+09 | 0.00 | 315.82 | 0.346404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4001.71 | 19-SEP-17:41 | 4001.71 | 19-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 43348079.02 | 0.00 | 48.22 | 25933513.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3417.66 | 24-OCT-15:11 | 3417.66 | 24-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 11592869.54 | 0.00 | 6.14 | 8352622.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3546.68 | 04-NOV-15:11 | 3546.68 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 1943908.69 | 0.00 | 1.41 | 1836002.45 | 0.00 | 0.00 | 0.00 | 0.00 | 978.55 | 02-DEC-16:13 | 978.55 | 02-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.597355E+10 | 0.00 | 2325.65 | 0.316449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 936354.80 | 0.00 | 0.73 | 877110.70 | 0.00 | 0.00 | 0.00 | 0.00 | 894.30 | 894.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.168063E+10 | 0.00 | 499.21 | 0.916420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4862.23 | 4032.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.159081E+09 | 0.00 | 30.77 | 0.157006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17575.19 | 12-JAN-16:11 | 17575.19 | 12-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.460721E+09 | 0.00 | 63.72 | 0.344682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17390.38 | 17-FEB-16:11 | 17390.38 | 17-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.942673E+09 | 0.00 | 156.63 | 0.623663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17575.28 | 27-MAR-15:11 | 17575.28 | 27-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.287565E+10 | 0.00 | 296.00 | 0.175988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17984.36 | 16-APR-08:61 | 17573.54 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.495906E+10 | 0.00 | 545.70 | 0.230011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18664.11 | 29-MAY-08:61 | 17153.68 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.816388E+10 | 0.00 | 599.05 | 0.403137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20129.59 | 26-JUN-08:62 | 15676.46 | 24-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.103061E+11 | 0.00 | 674.76 | 0.504051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21127.84 | 20-JUL-08:62 | 15728.51 | 13-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.100424E+11 | 0.00 | 670.71 | 0.493669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22193.10 | 31-AUG-08:62 | 15733.96 | 20-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.704826E+10 | 0.00 | 531.72 | 0.421737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19288.09 | 11-SEP-08:61 | 17569.81 | 30-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.293886E+10 | 0.00 | 337.94 | 0.204696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17575.26 | 16-OCT-15:11 | 17575.26 | 16-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.866785E+09 | 0.00 | 122.91 | 0.604954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17563.12 | 12-NOV-16:11 | 17563.12 | 12-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.385060E+09 | 0.00 | 60.59 | 0.362643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17564.20 | 01-DEC-16:11 | 17564.20 | 01-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491486E+11 | 0.00 | 4090.51 | 0.264258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.159081E+09 | 0.00 | 30.77 | 0.157006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17390.38 | 15676.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.103061E+11 | 0.00 | 674.76 | 0.504051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22193.10 | 17575.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 535.18 | 370.78 | 164.40 | 554.90 | 665.35 | 0.00 | 0.00 | 0.00 |
February | 571.01 | 390.01 | 180.99 | 620.11 | 534.83 | 0.00 | 0.00 | 0.00 |
March | 478.77 | 249.00 | 229.76 | 553.17 | 378.05 | 0.00 | 0.00 | 0.00 |
April | 415.42 | 182.57 | 232.85 | 546.86 | 273.38 | 0.00 | 0.00 | 0.00 |
May | 352.34 | 88.29 | 264.05 | 508.61 | 154.85 | 0.00 | 0.00 | 0.00 |
June | 336.34 | 56.27 | 280.08 | 535.03 | 100.37 | 0.00 | 0.00 | 0.00 |
July | 355.72 | 77.21 | 278.51 | 590.15 | 86.45 | 0.00 | 0.00 | 0.00 |
August | 396.30 | 127.27 | 269.03 | 658.78 | 105.72 | 0.00 | 0.00 | 0.00 |
September | 485.56 | 245.07 | 240.49 | 743.89 | 181.96 | 0.00 | 0.00 | 0.00 |
October | 539.53 | 341.65 | 197.88 | 709.20 | 282.96 | 0.00 | 0.00 | 0.00 |
November | 408.83 | 258.97 | 149.86 | 452.76 | 424.32 | 0.00 | 0.00 | 0.00 |
December | 439.77 | 336.21 | 103.56 | 485.30 | 617.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 442.19 | 226.05 | 216.13 | 579.68 | 316.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 336.34 | 56.27 | 103.56 | 452.76 | 86.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 571.01 | 390.01 | 280.08 | 743.89 | 665.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1507.04 | 1044.10 | 462.94 | 1557.65 | 1861.74 | 0.00 | 0.00 | 0.00 |
February | 1607.91 | 1098.25 | 509.66 | 1742.24 | 1498.42 | 0.00 | 0.00 | 0.00 |
March | 1348.17 | 701.18 | 646.99 | 1557.08 | 1058.21 | 0.00 | 0.00 | 0.00 |
April | 1169.80 | 514.10 | 655.70 | 1549.74 | 758.34 | 0.00 | 0.00 | 0.00 |
May | 992.18 | 248.63 | 743.55 | 1459.90 | 413.82 | 0.00 | 0.00 | 0.00 |
June | 947.12 | 158.45 | 788.68 | 1554.91 | 250.83 | 0.00 | 0.00 | 0.00 |
July | 1001.68 | 217.43 | 784.26 | 1719.72 | 202.38 | 0.00 | 0.00 | 0.00 |
August | 1115.96 | 358.38 | 757.57 | 1904.91 | 255.68 | 0.00 | 0.00 | 0.00 |
September | 1367.31 | 690.10 | 677.21 | 2117.58 | 482.49 | 0.00 | 0.00 | 0.00 |
October | 1519.28 | 962.06 | 557.22 | 2002.20 | 788.54 | 0.00 | 0.00 | 0.00 |
November | 1151.23 | 729.24 | 421.99 | 1271.25 | 1190.56 | 0.00 | 0.00 | 0.00 |
December | 1238.35 | 946.73 | 291.62 | 1364.89 | 1729.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1245.17 | 636.55 | 608.62 | 1649.71 | 871.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 947.12 | 158.45 | 291.62 | 1271.25 | 202.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1607.91 | 1098.25 | 788.68 | 2117.58 | 1861.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1957.73 | 1356.34 | 601.39 | 2035.03 | 2516.53 | 0.00 | 0.00 | 0.00 |
February | 2088.77 | 1426.69 | 662.08 | 2279.08 | 2031.88 | 0.00 | 0.00 | 0.00 |
March | 1751.35 | 910.87 | 840.48 | 2036.57 | 1456.64 | 0.00 | 0.00 | 0.00 |
April | 1519.63 | 667.84 | 851.79 | 2027.52 | 1058.19 | 0.00 | 0.00 | 0.00 |
May | 1288.89 | 322.98 | 965.91 | 1893.41 | 595.24 | 0.00 | 0.00 | 0.00 |
June | 1230.37 | 205.83 | 1024.54 | 2014.57 | 372.16 | 0.00 | 0.00 | 0.00 |
July | 1301.24 | 282.45 | 1018.79 | 2229.91 | 304.48 | 0.00 | 0.00 | 0.00 |
August | 1449.69 | 465.56 | 984.13 | 2477.01 | 377.45 | 0.00 | 0.00 | 0.00 |
September | 1776.22 | 896.49 | 879.73 | 2765.28 | 686.52 | 0.00 | 0.00 | 0.00 |
October | 1973.63 | 1249.77 | 723.87 | 2615.27 | 1098.88 | 0.00 | 0.00 | 0.00 |
November | 1495.51 | 947.32 | 548.19 | 1657.40 | 1638.54 | 0.00 | 0.00 | 0.00 |
December | 1608.69 | 1229.86 | 378.83 | 1784.42 | 2350.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1617.55 | 826.92 | 790.63 | 2150.62 | 1203.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1230.37 | 205.83 | 378.83 | 1657.40 | 304.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2088.77 | 1426.69 | 1024.54 | 2765.28 | 2516.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.81 | 73.31 | 32.50 | 109.77 | 134.84 | 0.00 | 0.00 | 0.00 |
February | 112.90 | 77.11 | 35.79 | 122.54 | 108.23 | 0.00 | 0.00 | 0.00 |
March | 94.66 | 49.23 | 45.43 | 109.23 | 76.51 | 0.00 | 0.00 | 0.00 |
April | 82.14 | 36.10 | 46.04 | 108.41 | 54.34 | 0.00 | 0.00 | 0.00 |
May | 69.66 | 17.46 | 52.21 | 101.04 | 29.16 | 0.00 | 0.00 | 0.00 |
June | 66.50 | 11.13 | 55.38 | 108.58 | 16.71 | 0.00 | 0.00 | 0.00 |
July | 70.33 | 15.27 | 55.07 | 120.20 | 12.96 | 0.00 | 0.00 | 0.00 |
August | 78.36 | 25.16 | 53.19 | 133.24 | 16.44 | 0.00 | 0.00 | 0.00 |
September | 96.00 | 48.45 | 47.55 | 149.07 | 32.70 | 0.00 | 0.00 | 0.00 |
October | 106.67 | 67.55 | 39.13 | 140.90 | 55.42 | 0.00 | 0.00 | 0.00 |
November | 80.83 | 51.20 | 29.63 | 89.78 | 85.24 | 0.00 | 0.00 | 0.00 |
December | 86.95 | 66.47 | 20.48 | 96.36 | 124.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.43 | 44.69 | 42.73 | 115.72 | 62.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.50 | 11.13 | 20.48 | 89.78 | 12.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.90 | 77.11 | 55.38 | 149.07 | 134.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.30 | 26.16 | 39.14 | 34.39 | 284.26 | 0.00 | 0.00 | 0.00 |
February | 96.11 | 47.23 | 48.88 | 72.59 | 226.49 | 0.00 | 0.00 | 0.00 |
March | 115.09 | 42.93 | 72.17 | 102.96 | 146.95 | 0.00 | 0.00 | 0.00 |
April | 169.20 | 84.32 | 84.88 | 206.11 | 98.87 | 0.00 | 0.00 | 0.00 |
May | 169.22 | 68.26 | 100.96 | 231.31 | 52.95 | 0.00 | 0.00 | 0.00 |
June | 198.28 | 86.48 | 111.80 | 302.67 | 30.77 | 0.00 | 0.00 | 0.00 |
July | 213.15 | 101.96 | 111.19 | 334.85 | 24.03 | 0.00 | 0.00 | 0.00 |
August | 186.17 | 85.97 | 100.19 | 291.81 | 30.55 | 0.00 | 0.00 | 0.00 |
September | 151.00 | 72.14 | 78.86 | 215.87 | 60.70 | 0.00 | 0.00 | 0.00 |
October | 105.11 | 46.98 | 58.13 | 117.33 | 107.65 | 0.00 | 0.00 | 0.00 |
November | 62.25 | 22.84 | 39.41 | 45.60 | 173.44 | 0.00 | 0.00 | 0.00 |
December | 47.43 | 22.01 | 25.42 | 30.04 | 256.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.67 | 58.95 | 72.71 | 165.93 | 123.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.43 | 22.01 | 25.42 | 30.04 | 24.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.15 | 101.96 | 111.80 | 334.85 | 284.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 0.00 | 16.55 | 0.08 | 163.15 | 0.00 | 0.00 | 0.00 |
February | 20.98 | 0.00 | 20.98 | 1.39 | 131.14 | 0.00 | 0.00 | 0.00 |
March | 31.45 | 0.00 | 31.45 | 12.48 | 82.70 | 0.00 | 0.00 | 0.00 |
April | 36.34 | 0.19 | 36.15 | 25.43 | 54.06 | 0.00 | 0.00 | 0.00 |
May | 46.99 | 1.40 | 45.59 | 52.89 | 27.44 | 0.00 | 0.00 | 0.00 |
June | 54.60 | 4.29 | 50.31 | 79.48 | 16.54 | 0.00 | 0.00 | 0.00 |
July | 51.27 | 2.84 | 48.42 | 77.88 | 13.68 | 0.00 | 0.00 | 0.00 |
August | 43.33 | 0.63 | 42.70 | 64.81 | 17.07 | 0.00 | 0.00 | 0.00 |
September | 33.33 | 0.02 | 33.32 | 39.96 | 33.76 | 0.00 | 0.00 | 0.00 |
October | 24.76 | 0.00 | 24.76 | 15.10 | 59.02 | 0.00 | 0.00 | 0.00 |
November | 17.32 | 0.00 | 17.32 | 3.76 | 96.95 | 0.00 | 0.00 | 0.00 |
December | 11.24 | 0.00 | 11.24 | 0.02 | 143.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.41 | 0.78 | 31.62 | 31.28 | 69.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.24 | 0.00 | 11.24 | 0.02 | 13.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.60 | 4.29 | 50.31 | 79.48 | 163.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.30 | 26.16 | 39.14 | 35.41 | 282.92 | 0.00 | 0.00 | 0.00 |
February | 96.11 | 47.23 | 48.88 | 74.47 | 224.75 | 0.00 | 0.00 | 0.00 |
March | 115.09 | 42.93 | 72.17 | 105.27 | 145.63 | 0.00 | 0.00 | 0.00 |
April | 169.20 | 84.32 | 84.88 | 207.47 | 98.58 | 0.00 | 0.00 | 0.00 |
May | 169.22 | 68.26 | 100.96 | 230.56 | 53.76 | 0.00 | 0.00 | 0.00 |
June | 198.28 | 86.48 | 111.80 | 300.37 | 32.39 | 0.00 | 0.00 | 0.00 |
July | 213.15 | 101.96 | 111.19 | 332.22 | 26.53 | 0.00 | 0.00 | 0.00 |
August | 186.17 | 85.97 | 100.19 | 290.20 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 151.00 | 72.14 | 78.86 | 216.52 | 61.59 | 0.00 | 0.00 | 0.00 |
October | 105.11 | 46.98 | 58.13 | 120.01 | 106.32 | 0.00 | 0.00 | 0.00 |
November | 62.25 | 22.84 | 39.41 | 47.13 | 172.08 | 0.00 | 0.00 | 0.00 |
December | 47.43 | 22.01 | 25.42 | 31.29 | 254.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.67 | 58.95 | 72.71 | 166.37 | 123.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.43 | 22.01 | 25.42 | 31.29 | 26.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.15 | 101.96 | 111.80 | 332.22 | 282.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.64 | 58.64 | 26.00 | 90.62 | 94.70 | 0.00 | 0.00 | 0.00 |
February | 90.30 | 61.68 | 28.62 | 99.38 | 82.06 | 0.00 | 0.00 | 0.00 |
March | 75.71 | 39.38 | 36.34 | 85.58 | 62.91 | 0.00 | 0.00 | 0.00 |
April | 65.70 | 28.87 | 36.82 | 81.16 | 56.61 | 0.00 | 0.00 | 0.00 |
May | 55.72 | 13.96 | 41.76 | 71.68 | 35.82 | 0.00 | 0.00 | 0.00 |
June | 53.19 | 8.90 | 44.29 | 77.05 | 24.04 | 0.00 | 0.00 | 0.00 |
July | 56.25 | 12.21 | 44.04 | 86.45 | 20.28 | 0.00 | 0.00 | 0.00 |
August | 62.67 | 20.13 | 42.55 | 97.47 | 24.30 | 0.00 | 0.00 | 0.00 |
September | 76.79 | 38.76 | 38.03 | 111.10 | 39.83 | 0.00 | 0.00 | 0.00 |
October | 85.32 | 54.03 | 31.29 | 104.31 | 60.24 | 0.00 | 0.00 | 0.00 |
November | 64.65 | 40.95 | 23.70 | 67.77 | 76.35 | 0.00 | 0.00 | 0.00 |
December | 69.55 | 53.17 | 16.38 | 78.58 | 88.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.93 | 35.75 | 34.18 | 87.54 | 55.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.19 | 8.90 | 16.38 | 67.77 | 20.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.30 | 61.68 | 44.29 | 111.10 | 94.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.24 | 0.00 | 13.24 | 0.04 | 134.42 | 0.00 | 0.00 | 0.00 |
February | 16.79 | 0.00 | 16.79 | 0.90 | 108.05 | 0.00 | 0.00 | 0.00 |
March | 25.16 | 0.00 | 25.16 | 9.50 | 67.96 | 0.00 | 0.00 | 0.00 |
April | 29.08 | 0.15 | 28.92 | 20.89 | 43.79 | 0.00 | 0.00 | 0.00 |
May | 37.59 | 1.12 | 36.48 | 43.84 | 21.60 | 0.00 | 0.00 | 0.00 |
June | 43.69 | 3.43 | 40.26 | 65.81 | 12.59 | 0.00 | 0.00 | 0.00 |
July | 41.02 | 2.28 | 38.75 | 64.93 | 9.90 | 0.00 | 0.00 | 0.00 |
August | 34.67 | 0.51 | 34.16 | 54.19 | 12.67 | 0.00 | 0.00 | 0.00 |
September | 26.67 | 0.01 | 26.66 | 33.15 | 26.45 | 0.00 | 0.00 | 0.00 |
October | 19.81 | 0.00 | 19.81 | 11.73 | 48.22 | 0.00 | 0.00 | 0.00 |
November | 13.86 | 0.00 | 13.86 | 2.71 | 80.43 | 0.00 | 0.00 | 0.00 |
December | 8.99 | 0.00 | 8.99 | 0.01 | 118.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.93 | 0.63 | 25.30 | 25.79 | 56.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.99 | 0.00 | 8.99 | 0.01 | 9.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.69 | 3.43 | 40.26 | 65.81 | 134.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.09 | 26.12 | 38.97 | 31.56 | 279.60 | 0.00 | 0.00 | 0.00 |
February | 87.61 | 38.39 | 49.22 | 57.12 | 222.30 | 0.00 | 0.00 | 0.00 |
March | 119.65 | 47.62 | 72.03 | 107.08 | 143.29 | 0.00 | 0.00 | 0.00 |
April | 146.70 | 64.49 | 82.22 | 168.27 | 96.63 | 0.00 | 0.00 | 0.00 |
May | 185.33 | 81.74 | 103.60 | 252.96 | 50.09 | 0.00 | 0.00 | 0.00 |
June | 203.40 | 89.19 | 114.20 | 310.08 | 29.23 | 0.00 | 0.00 | 0.00 |
July | 206.12 | 95.98 | 110.14 | 321.47 | 22.62 | 0.00 | 0.00 | 0.00 |
August | 173.74 | 75.60 | 98.15 | 270.28 | 28.68 | 0.00 | 0.00 | 0.00 |
September | 155.54 | 74.30 | 81.24 | 222.15 | 59.32 | 0.00 | 0.00 | 0.00 |
October | 97.67 | 40.55 | 57.12 | 102.85 | 104.37 | 0.00 | 0.00 | 0.00 |
November | 57.34 | 18.24 | 39.10 | 35.27 | 169.86 | 0.00 | 0.00 | 0.00 |
December | 43.78 | 18.23 | 25.54 | 21.59 | 252.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.70 | 55.95 | 72.75 | 158.94 | 121.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.78 | 18.23 | 25.54 | 21.59 | 22.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 206.12 | 95.98 | 114.20 | 321.47 | 279.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.81 | 73.31 | 32.50 | 109.63 | 134.76 | 0.00 | 0.00 | 0.00 |
February | 112.90 | 77.11 | 35.79 | 122.38 | 107.99 | 0.00 | 0.00 | 0.00 |
March | 94.66 | 49.23 | 45.43 | 108.61 | 76.33 | 0.00 | 0.00 | 0.00 |
April | 82.14 | 36.10 | 46.04 | 108.05 | 53.80 | 0.00 | 0.00 | 0.00 |
May | 69.66 | 17.46 | 52.21 | 100.26 | 29.05 | 0.00 | 0.00 | 0.00 |
June | 66.50 | 11.13 | 55.38 | 108.03 | 16.49 | 0.00 | 0.00 | 0.00 |
July | 70.33 | 15.27 | 55.07 | 119.83 | 12.64 | 0.00 | 0.00 | 0.00 |
August | 78.36 | 25.16 | 53.19 | 132.99 | 16.18 | 0.00 | 0.00 | 0.00 |
September | 96.00 | 48.45 | 47.55 | 148.52 | 32.50 | 0.00 | 0.00 | 0.00 |
October | 106.67 | 67.55 | 39.13 | 140.49 | 55.19 | 0.00 | 0.00 | 0.00 |
November | 80.83 | 51.20 | 29.63 | 89.71 | 85.08 | 0.00 | 0.00 | 0.00 |
December | 86.95 | 66.47 | 20.48 | 96.34 | 124.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.43 | 44.69 | 42.73 | 115.37 | 61.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.50 | 11.13 | 20.48 | 89.71 | 12.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.90 | 77.11 | 55.38 | 148.52 | 134.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 0.00 | 16.55 | 0.07 | 163.19 | 0.00 | 0.00 | 0.00 |
February | 20.98 | 0.00 | 20.98 | 1.27 | 131.02 | 0.00 | 0.00 | 0.00 |
March | 31.45 | 0.00 | 31.45 | 12.10 | 82.74 | 0.00 | 0.00 | 0.00 |
April | 36.34 | 0.19 | 36.15 | 25.18 | 53.45 | 0.00 | 0.00 | 0.00 |
May | 46.99 | 1.40 | 45.59 | 52.21 | 27.22 | 0.00 | 0.00 | 0.00 |
June | 54.60 | 4.29 | 50.31 | 78.93 | 16.20 | 0.00 | 0.00 | 0.00 |
July | 51.27 | 2.84 | 48.42 | 77.33 | 13.13 | 0.00 | 0.00 | 0.00 |
August | 43.33 | 0.63 | 42.70 | 64.51 | 16.51 | 0.00 | 0.00 | 0.00 |
September | 33.33 | 0.02 | 33.32 | 39.30 | 33.39 | 0.00 | 0.00 | 0.00 |
October | 24.76 | 0.00 | 24.76 | 14.75 | 58.65 | 0.00 | 0.00 | 0.00 |
November | 17.32 | 0.00 | 17.32 | 3.69 | 96.81 | 0.00 | 0.00 | 0.00 |
December | 11.24 | 0.00 | 11.24 | 0.01 | 143.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.41 | 0.78 | 31.62 | 30.96 | 69.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.24 | 0.00 | 11.24 | 0.01 | 13.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.60 | 4.29 | 50.31 | 78.93 | 163.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.09 | 26.12 | 38.97 | 32.13 | 277.78 | 0.00 | 0.00 | 0.00 |
February | 87.61 | 38.39 | 49.22 | 58.32 | 219.92 | 0.00 | 0.00 | 0.00 |
March | 119.65 | 47.62 | 72.03 | 109.15 | 141.64 | 0.00 | 0.00 | 0.00 |
April | 146.70 | 64.49 | 82.22 | 169.73 | 96.04 | 0.00 | 0.00 | 0.00 |
May | 185.33 | 81.74 | 103.60 | 252.62 | 50.76 | 0.00 | 0.00 | 0.00 |
June | 203.40 | 89.19 | 114.20 | 307.85 | 30.62 | 0.00 | 0.00 | 0.00 |
July | 206.12 | 95.98 | 110.14 | 318.50 | 24.71 | 0.00 | 0.00 | 0.00 |
August | 173.74 | 75.60 | 98.15 | 268.74 | 30.67 | 0.00 | 0.00 | 0.00 |
September | 155.54 | 74.30 | 81.24 | 222.66 | 59.87 | 0.00 | 0.00 | 0.00 |
October | 97.67 | 40.55 | 57.12 | 105.55 | 102.63 | 0.00 | 0.00 | 0.00 |
November | 57.34 | 18.24 | 39.10 | 36.33 | 167.98 | 0.00 | 0.00 | 0.00 |
December | 43.78 | 18.23 | 25.54 | 22.03 | 250.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.70 | 55.95 | 72.75 | 159.18 | 120.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.78 | 18.23 | 25.54 | 22.03 | 24.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 206.12 | 95.98 | 114.20 | 318.50 | 277.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.96 | 0.00 | 20.96 | 0.04 | 218.26 | 0.00 | 0.00 | 0.00 |
February | 26.57 | 0.00 | 26.57 | 1.22 | 175.34 | 0.00 | 0.00 | 0.00 |
March | 39.82 | 0.00 | 39.82 | 14.69 | 109.60 | 0.00 | 0.00 | 0.00 |
April | 46.02 | 0.24 | 45.78 | 32.87 | 70.99 | 0.00 | 0.00 | 0.00 |
May | 59.51 | 1.77 | 57.74 | 69.30 | 36.07 | 0.00 | 0.00 | 0.00 |
June | 69.15 | 5.43 | 63.72 | 102.55 | 22.44 | 0.00 | 0.00 | 0.00 |
July | 64.93 | 3.60 | 61.33 | 100.31 | 18.68 | 0.00 | 0.00 | 0.00 |
August | 54.87 | 0.80 | 54.07 | 83.43 | 23.32 | 0.00 | 0.00 | 0.00 |
September | 42.22 | 0.02 | 42.20 | 50.89 | 45.68 | 0.00 | 0.00 | 0.00 |
October | 31.36 | 0.00 | 31.36 | 18.53 | 77.55 | 0.00 | 0.00 | 0.00 |
November | 21.94 | 0.00 | 21.94 | 4.24 | 130.08 | 0.00 | 0.00 | 0.00 |
December | 14.23 | 0.00 | 14.23 | 0.00 | 192.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.04 | 0.99 | 40.05 | 40.07 | 93.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.23 | 0.00 | 14.23 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.15 | 5.43 | 63.72 | 102.55 | 218.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.73 | 0.00 | 7.73 | 0.02 | 80.46 | 0.00 | 0.00 | 0.00 |
February | 9.79 | 0.00 | 9.79 | 0.45 | 64.64 | 0.00 | 0.00 | 0.00 |
March | 14.68 | 0.00 | 14.68 | 5.42 | 40.40 | 0.00 | 0.00 | 0.00 |
April | 16.97 | 0.09 | 16.88 | 12.12 | 26.17 | 0.00 | 0.00 | 0.00 |
May | 21.94 | 0.65 | 21.28 | 25.55 | 13.30 | 0.00 | 0.00 | 0.00 |
June | 25.49 | 2.00 | 23.49 | 37.80 | 8.27 | 0.00 | 0.00 | 0.00 |
July | 23.94 | 1.33 | 22.61 | 36.98 | 6.89 | 0.00 | 0.00 | 0.00 |
August | 20.23 | 0.29 | 19.93 | 30.76 | 8.60 | 0.00 | 0.00 | 0.00 |
September | 15.56 | 0.01 | 15.56 | 18.76 | 16.84 | 0.00 | 0.00 | 0.00 |
October | 11.56 | 0.00 | 11.56 | 6.83 | 28.59 | 0.00 | 0.00 | 0.00 |
November | 8.09 | 0.00 | 8.09 | 1.56 | 47.95 | 0.00 | 0.00 | 0.00 |
December | 5.25 | 0.00 | 5.25 | 0.00 | 71.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.13 | 0.37 | 14.76 | 14.77 | 34.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.25 | 0.00 | 5.25 | 0.00 | 6.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.49 | 2.00 | 23.49 | 37.80 | 80.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.37 | 34.21 | 15.17 | 50.41 | 65.51 | 0.00 | 0.00 | 0.00 |
February | 52.68 | 35.98 | 16.70 | 56.63 | 52.39 | 0.00 | 0.00 | 0.00 |
March | 44.17 | 22.97 | 21.20 | 50.87 | 36.87 | 0.00 | 0.00 | 0.00 |
April | 38.32 | 16.84 | 21.48 | 51.10 | 26.16 | 0.00 | 0.00 | 0.00 |
May | 32.51 | 8.15 | 24.36 | 47.84 | 14.35 | 0.00 | 0.00 | 0.00 |
June | 31.03 | 5.19 | 25.84 | 50.83 | 8.86 | 0.00 | 0.00 | 0.00 |
July | 32.82 | 7.12 | 25.69 | 56.09 | 7.27 | 0.00 | 0.00 | 0.00 |
August | 36.56 | 11.74 | 24.82 | 62.32 | 9.00 | 0.00 | 0.00 | 0.00 |
September | 44.80 | 22.61 | 22.19 | 69.80 | 16.56 | 0.00 | 0.00 | 0.00 |
October | 49.77 | 31.52 | 18.26 | 66.23 | 26.44 | 0.00 | 0.00 | 0.00 |
November | 37.72 | 23.89 | 13.83 | 41.61 | 41.46 | 0.00 | 0.00 | 0.00 |
December | 40.57 | 31.02 | 9.55 | 44.55 | 60.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.79 | 20.85 | 19.94 | 54.01 | 30.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.03 | 5.19 | 9.55 | 41.61 | 7.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.68 | 35.98 | 25.84 | 69.80 | 65.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.01 | 92.84 | 41.17 | 136.82 | 177.80 | 0.00 | 0.00 | 0.00 |
February | 142.98 | 97.66 | 45.32 | 153.71 | 142.19 | 0.00 | 0.00 | 0.00 |
March | 119.88 | 62.35 | 57.53 | 138.08 | 100.06 | 0.00 | 0.00 | 0.00 |
April | 104.02 | 45.71 | 58.31 | 138.69 | 71.02 | 0.00 | 0.00 | 0.00 |
May | 88.23 | 22.11 | 66.12 | 129.84 | 38.94 | 0.00 | 0.00 | 0.00 |
June | 84.22 | 14.09 | 70.13 | 137.95 | 24.05 | 0.00 | 0.00 | 0.00 |
July | 89.07 | 19.33 | 69.74 | 152.25 | 19.73 | 0.00 | 0.00 | 0.00 |
August | 99.23 | 31.87 | 67.36 | 169.15 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 121.58 | 61.36 | 60.22 | 189.45 | 44.95 | 0.00 | 0.00 | 0.00 |
October | 135.10 | 85.55 | 49.55 | 179.76 | 71.77 | 0.00 | 0.00 | 0.00 |
November | 102.37 | 64.84 | 37.52 | 112.93 | 112.52 | 0.00 | 0.00 | 0.00 |
December | 110.12 | 84.18 | 25.93 | 120.93 | 164.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 110.72 | 56.60 | 54.12 | 146.59 | 82.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.22 | 14.09 | 25.93 | 112.93 | 19.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.98 | 97.66 | 70.13 | 189.45 | 177.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.81 | 73.31 | 32.50 | 109.47 | 134.35 | 0.00 | 0.00 | 0.00 |
February | 112.90 | 77.11 | 35.79 | 122.26 | 107.65 | 0.00 | 0.00 | 0.00 |
March | 94.66 | 49.23 | 45.43 | 109.05 | 75.97 | 0.00 | 0.00 | 0.00 |
April | 82.14 | 36.10 | 46.04 | 107.89 | 53.87 | 0.00 | 0.00 | 0.00 |
May | 69.66 | 17.46 | 52.21 | 100.26 | 28.92 | 0.00 | 0.00 | 0.00 |
June | 66.50 | 11.13 | 55.38 | 107.91 | 16.41 | 0.00 | 0.00 | 0.00 |
July | 70.33 | 15.27 | 55.07 | 119.48 | 12.65 | 0.00 | 0.00 | 0.00 |
August | 78.36 | 25.16 | 53.19 | 132.48 | 16.13 | 0.00 | 0.00 | 0.00 |
September | 96.00 | 48.45 | 47.55 | 148.56 | 32.11 | 0.00 | 0.00 | 0.00 |
October | 106.67 | 67.55 | 39.13 | 140.56 | 54.85 | 0.00 | 0.00 | 0.00 |
November | 80.83 | 51.20 | 29.63 | 89.73 | 84.57 | 0.00 | 0.00 | 0.00 |
December | 86.95 | 66.47 | 20.48 | 96.30 | 123.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.43 | 44.69 | 42.73 | 115.29 | 61.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.50 | 11.13 | 20.48 | 89.73 | 12.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.90 | 77.11 | 55.38 | 148.56 | 134.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.30 | 26.16 | 39.14 | 34.35 | 283.41 | 0.00 | 0.00 | 0.00 |
February | 96.11 | 47.23 | 48.88 | 72.42 | 225.50 | 0.00 | 0.00 | 0.00 |
March | 115.09 | 42.93 | 72.17 | 102.88 | 145.84 | 0.00 | 0.00 | 0.00 |
April | 169.20 | 84.32 | 84.88 | 205.08 | 97.93 | 0.00 | 0.00 | 0.00 |
May | 169.22 | 68.26 | 100.96 | 229.79 | 52.45 | 0.00 | 0.00 | 0.00 |
June | 198.28 | 86.48 | 111.80 | 301.12 | 30.20 | 0.00 | 0.00 | 0.00 |
July | 213.15 | 101.96 | 111.19 | 333.20 | 23.43 | 0.00 | 0.00 | 0.00 |
August | 186.17 | 85.97 | 100.19 | 290.33 | 29.96 | 0.00 | 0.00 | 0.00 |
September | 151.00 | 72.14 | 78.86 | 215.21 | 59.60 | 0.00 | 0.00 | 0.00 |
October | 105.11 | 46.98 | 58.13 | 117.08 | 106.41 | 0.00 | 0.00 | 0.00 |
November | 62.25 | 22.84 | 39.41 | 45.83 | 171.93 | 0.00 | 0.00 | 0.00 |
December | 47.43 | 22.01 | 25.42 | 30.18 | 255.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.67 | 58.95 | 72.71 | 165.25 | 123.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.43 | 22.01 | 25.42 | 30.18 | 23.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.15 | 101.96 | 111.80 | 333.20 | 283.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 0.00 | 16.55 | 0.09 | 162.72 | 0.00 | 0.00 | 0.00 |
February | 20.98 | 0.00 | 20.98 | 1.45 | 130.52 | 0.00 | 0.00 | 0.00 |
March | 31.45 | 0.00 | 31.45 | 12.68 | 82.06 | 0.00 | 0.00 | 0.00 |
April | 36.34 | 0.19 | 36.15 | 25.32 | 53.66 | 0.00 | 0.00 | 0.00 |
May | 46.99 | 1.40 | 45.59 | 52.17 | 27.43 | 0.00 | 0.00 | 0.00 |
June | 54.60 | 4.29 | 50.31 | 78.72 | 16.57 | 0.00 | 0.00 | 0.00 |
July | 51.27 | 2.84 | 48.42 | 77.21 | 13.74 | 0.00 | 0.00 | 0.00 |
August | 43.33 | 0.63 | 42.70 | 64.31 | 17.12 | 0.00 | 0.00 | 0.00 |
September | 33.33 | 0.02 | 33.32 | 39.95 | 33.32 | 0.00 | 0.00 | 0.00 |
October | 24.76 | 0.00 | 24.76 | 15.38 | 58.27 | 0.00 | 0.00 | 0.00 |
November | 17.32 | 0.00 | 17.32 | 3.91 | 96.03 | 0.00 | 0.00 | 0.00 |
December | 11.24 | 0.00 | 11.24 | 0.02 | 142.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.41 | 0.78 | 31.62 | 31.11 | 69.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.24 | 0.00 | 11.24 | 0.02 | 13.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.60 | 4.29 | 50.31 | 78.72 | 162.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.30 | 26.16 | 39.14 | 35.31 | 282.21 | 0.00 | 0.00 | 0.00 |
February | 96.11 | 47.23 | 48.88 | 74.31 | 223.87 | 0.00 | 0.00 | 0.00 |
March | 115.09 | 42.93 | 72.17 | 105.27 | 144.56 | 0.00 | 0.00 | 0.00 |
April | 169.20 | 84.32 | 84.88 | 206.50 | 97.71 | 0.00 | 0.00 | 0.00 |
May | 169.22 | 68.26 | 100.96 | 228.64 | 53.62 | 0.00 | 0.00 | 0.00 |
June | 198.28 | 86.48 | 111.80 | 298.40 | 32.36 | 0.00 | 0.00 | 0.00 |
July | 213.15 | 101.96 | 111.19 | 330.23 | 26.57 | 0.00 | 0.00 | 0.00 |
August | 186.17 | 85.97 | 100.19 | 288.47 | 32.98 | 0.00 | 0.00 | 0.00 |
September | 151.00 | 72.14 | 78.86 | 215.88 | 60.72 | 0.00 | 0.00 | 0.00 |
October | 105.11 | 46.98 | 58.13 | 120.06 | 104.97 | 0.00 | 0.00 | 0.00 |
November | 62.25 | 22.84 | 39.41 | 47.41 | 170.64 | 0.00 | 0.00 | 0.00 |
December | 47.43 | 22.01 | 25.42 | 31.34 | 253.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.67 | 58.95 | 72.71 | 165.60 | 123.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.43 | 22.01 | 25.42 | 31.34 | 26.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.15 | 101.96 | 111.80 | 330.23 | 282.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 155.19 | 107.52 | 47.67 | 156.44 | 201.22 | 0.00 | 0.00 | 0.00 |
February | 165.58 | 113.09 | 52.48 | 175.18 | 161.79 | 0.00 | 0.00 | 0.00 |
March | 138.83 | 72.20 | 66.62 | 156.43 | 114.06 | 0.00 | 0.00 | 0.00 |
April | 120.46 | 52.94 | 67.52 | 157.25 | 79.70 | 0.00 | 0.00 | 0.00 |
May | 102.17 | 25.60 | 76.57 | 147.27 | 42.10 | 0.00 | 0.00 | 0.00 |
June | 97.53 | 16.32 | 81.21 | 159.60 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 103.15 | 22.39 | 80.76 | 177.05 | 17.52 | 0.00 | 0.00 | 0.00 |
August | 114.92 | 36.90 | 78.01 | 195.44 | 22.87 | 0.00 | 0.00 | 0.00 |
September | 140.80 | 71.06 | 69.74 | 217.17 | 47.26 | 0.00 | 0.00 | 0.00 |
October | 156.45 | 99.07 | 57.38 | 203.06 | 82.65 | 0.00 | 0.00 | 0.00 |
November | 118.55 | 75.09 | 43.45 | 128.38 | 127.63 | 0.00 | 0.00 | 0.00 |
December | 127.52 | 97.49 | 30.03 | 137.68 | 186.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.22 | 65.55 | 62.67 | 167.54 | 91.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.53 | 16.32 | 30.03 | 128.38 | 17.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.58 | 113.09 | 81.21 | 217.17 | 201.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.83 | 0.00 | 115.83 | 0.30 | 1178.89 | 0.00 | 0.00 | 0.00 |
February | 146.85 | 0.00 | 146.85 | 7.19 | 947.63 | 0.00 | 0.00 | 0.00 |
March | 220.11 | 0.00 | 220.11 | 81.85 | 599.10 | 0.00 | 0.00 | 0.00 |
April | 254.38 | 1.33 | 253.05 | 183.24 | 390.94 | 0.00 | 0.00 | 0.00 |
May | 328.90 | 9.77 | 319.13 | 385.89 | 199.17 | 0.00 | 0.00 | 0.00 |
June | 382.21 | 30.03 | 352.18 | 580.50 | 119.58 | 0.00 | 0.00 | 0.00 |
July | 358.87 | 19.91 | 338.96 | 575.10 | 93.75 | 0.00 | 0.00 | 0.00 |
August | 303.29 | 4.42 | 298.87 | 480.41 | 119.01 | 0.00 | 0.00 | 0.00 |
September | 233.34 | 0.11 | 233.23 | 294.43 | 240.72 | 0.00 | 0.00 | 0.00 |
October | 173.34 | 0.00 | 173.34 | 103.17 | 427.03 | 0.00 | 0.00 | 0.00 |
November | 121.25 | 0.00 | 121.25 | 23.55 | 707.66 | 0.00 | 0.00 | 0.00 |
December | 78.65 | 0.00 | 78.65 | 0.04 | 1042.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 226.84 | 5.48 | 221.36 | 227.62 | 503.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 78.65 | 0.00 | 78.65 | 0.04 | 93.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.21 | 30.03 | 352.18 | 580.50 | 1178.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.83 | 0.00 | 115.83 | 0.22 | 1200.45 | 0.00 | 0.00 | 0.00 |
February | 146.85 | 0.00 | 146.85 | 6.14 | 969.03 | 0.00 | 0.00 | 0.00 |
March | 220.11 | 0.00 | 220.11 | 76.73 | 619.40 | 0.00 | 0.00 | 0.00 |
April | 254.38 | 1.33 | 253.05 | 175.87 | 407.69 | 0.00 | 0.00 | 0.00 |
May | 328.90 | 9.77 | 319.13 | 375.43 | 207.72 | 0.00 | 0.00 | 0.00 |
June | 382.21 | 30.03 | 352.18 | 569.96 | 125.92 | 0.00 | 0.00 | 0.00 |
July | 358.87 | 19.91 | 338.96 | 564.97 | 99.54 | 0.00 | 0.00 | 0.00 |
August | 303.29 | 4.42 | 298.87 | 470.97 | 125.51 | 0.00 | 0.00 | 0.00 |
September | 233.34 | 0.11 | 233.23 | 286.59 | 251.25 | 0.00 | 0.00 | 0.00 |
October | 173.34 | 0.00 | 173.34 | 96.21 | 445.43 | 0.00 | 0.00 | 0.00 |
November | 121.25 | 0.00 | 121.25 | 21.15 | 729.54 | 0.00 | 0.00 | 0.00 |
December | 78.65 | 0.00 | 78.65 | 0.02 | 1065.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 226.84 | 5.48 | 221.36 | 221.64 | 518.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 78.65 | 0.00 | 78.65 | 0.02 | 99.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.21 | 30.03 | 352.18 | 569.96 | 1200.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 0.00 | 16.55 | 1.45 | 135.65 | 0.00 | 0.00 | 0.00 |
February | 20.98 | 0.00 | 20.98 | 6.70 | 106.48 | 0.00 | 0.00 | 0.00 |
March | 31.45 | 0.00 | 31.45 | 28.95 | 66.77 | 0.00 | 0.00 | 0.00 |
April | 36.34 | 0.19 | 36.15 | 52.06 | 42.56 | 0.00 | 0.00 | 0.00 |
May | 46.99 | 1.40 | 45.59 | 93.23 | 23.30 | 0.00 | 0.00 | 0.00 |
June | 54.60 | 4.29 | 50.31 | 125.36 | 14.17 | 0.00 | 0.00 | 0.00 |
July | 51.27 | 2.84 | 48.42 | 125.96 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 43.33 | 0.63 | 42.70 | 110.31 | 13.26 | 0.00 | 0.00 | 0.00 |
September | 33.33 | 0.02 | 33.32 | 75.90 | 25.31 | 0.00 | 0.00 | 0.00 |
October | 24.76 | 0.00 | 24.76 | 36.92 | 44.28 | 0.00 | 0.00 | 0.00 |
November | 17.32 | 0.00 | 17.32 | 14.09 | 75.07 | 0.00 | 0.00 | 0.00 |
December | 11.24 | 0.00 | 11.24 | 0.97 | 115.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.41 | 0.78 | 31.62 | 56.28 | 55.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.24 | 0.00 | 11.24 | 0.97 | 11.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.60 | 4.29 | 50.31 | 125.96 | 135.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.16 | 52.24 | 77.93 | 87.71 | 469.02 | 0.00 | 0.00 | 0.00 |
February | 175.21 | 76.77 | 98.43 | 156.73 | 364.32 | 0.00 | 0.00 | 0.00 |
March | 239.28 | 95.24 | 144.05 | 297.13 | 236.69 | 0.00 | 0.00 | 0.00 |
April | 293.39 | 128.97 | 164.42 | 446.40 | 156.66 | 0.00 | 0.00 | 0.00 |
May | 370.64 | 163.46 | 207.18 | 658.54 | 86.35 | 0.00 | 0.00 | 0.00 |
June | 406.77 | 178.38 | 228.39 | 788.49 | 52.89 | 0.00 | 0.00 | 0.00 |
July | 412.21 | 191.94 | 220.27 | 818.83 | 41.18 | 0.00 | 0.00 | 0.00 |
August | 347.46 | 151.18 | 196.28 | 709.39 | 49.77 | 0.00 | 0.00 | 0.00 |
September | 311.06 | 148.60 | 162.46 | 587.79 | 93.62 | 0.00 | 0.00 | 0.00 |
October | 195.33 | 81.09 | 114.24 | 307.35 | 162.03 | 0.00 | 0.00 | 0.00 |
November | 114.67 | 36.49 | 78.19 | 123.94 | 266.60 | 0.00 | 0.00 | 0.00 |
December | 87.54 | 36.46 | 51.08 | 62.44 | 406.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.38 | 111.90 | 145.48 | 421.84 | 198.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.54 | 36.46 | 51.08 | 62.44 | 41.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.21 | 191.94 | 228.39 | 818.83 | 469.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.81 | 73.31 | 32.50 | 123.04 | 116.39 | 0.00 | 0.00 | 0.00 |
February | 112.90 | 77.11 | 35.79 | 140.14 | 92.07 | 0.00 | 0.00 | 0.00 |
March | 94.66 | 49.23 | 45.43 | 132.28 | 63.94 | 0.00 | 0.00 | 0.00 |
April | 82.14 | 36.10 | 46.04 | 136.75 | 42.87 | 0.00 | 0.00 | 0.00 |
May | 69.66 | 17.46 | 52.21 | 140.01 | 24.10 | 0.00 | 0.00 | 0.00 |
June | 66.50 | 11.13 | 55.38 | 152.65 | 14.70 | 0.00 | 0.00 | 0.00 |
July | 70.33 | 15.27 | 55.07 | 166.54 | 11.22 | 0.00 | 0.00 | 0.00 |
August | 78.36 | 25.16 | 53.19 | 177.42 | 13.40 | 0.00 | 0.00 | 0.00 |
September | 96.00 | 48.45 | 47.55 | 186.48 | 25.20 | 0.00 | 0.00 | 0.00 |
October | 106.67 | 67.55 | 39.13 | 169.03 | 43.51 | 0.00 | 0.00 | 0.00 |
November | 80.83 | 51.20 | 29.63 | 108.07 | 68.94 | 0.00 | 0.00 | 0.00 |
December | 86.95 | 66.47 | 20.48 | 107.94 | 103.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.43 | 44.69 | 42.73 | 145.06 | 51.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.50 | 11.13 | 20.48 | 107.94 | 11.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.90 | 77.11 | 55.38 | 186.48 | 116.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.96 | 0.00 | 20.96 | 0.03 | 219.38 | 0.00 | 0.00 | 0.00 |
February | 26.57 | 0.00 | 26.57 | 1.03 | 176.63 | 0.00 | 0.00 | 0.00 |
March | 39.82 | 0.00 | 39.82 | 13.54 | 111.61 | 0.00 | 0.00 | 0.00 |
April | 46.02 | 0.24 | 45.78 | 29.76 | 74.77 | 0.00 | 0.00 | 0.00 |
May | 59.51 | 1.77 | 57.74 | 62.26 | 41.14 | 0.00 | 0.00 | 0.00 |
June | 69.15 | 5.43 | 63.72 | 95.65 | 26.28 | 0.00 | 0.00 | 0.00 |
July | 64.93 | 3.60 | 61.33 | 94.06 | 21.88 | 0.00 | 0.00 | 0.00 |
August | 54.87 | 0.80 | 54.07 | 77.45 | 27.28 | 0.00 | 0.00 | 0.00 |
September | 42.22 | 0.02 | 42.20 | 46.64 | 50.22 | 0.00 | 0.00 | 0.00 |
October | 31.36 | 0.00 | 31.36 | 16.23 | 81.65 | 0.00 | 0.00 | 0.00 |
November | 21.94 | 0.00 | 21.94 | 3.54 | 132.55 | 0.00 | 0.00 | 0.00 |
December | 14.23 | 0.00 | 14.23 | 0.00 | 193.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.04 | 0.99 | 40.05 | 36.90 | 96.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.23 | 0.00 | 14.23 | 0.00 | 21.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.15 | 5.43 | 63.72 | 95.65 | 219.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.75 | 0.00 | 18.75 | 0.03 | 196.28 | 0.00 | 0.00 | 0.00 |
February | 23.77 | 0.00 | 23.77 | 0.92 | 158.03 | 0.00 | 0.00 | 0.00 |
March | 35.63 | 0.00 | 35.63 | 12.11 | 99.85 | 0.00 | 0.00 | 0.00 |
April | 41.18 | 0.22 | 40.96 | 26.63 | 66.90 | 0.00 | 0.00 | 0.00 |
May | 53.24 | 1.58 | 51.66 | 55.70 | 36.81 | 0.00 | 0.00 | 0.00 |
June | 61.87 | 4.86 | 57.01 | 85.58 | 23.52 | 0.00 | 0.00 | 0.00 |
July | 58.09 | 3.22 | 54.87 | 84.15 | 19.57 | 0.00 | 0.00 | 0.00 |
August | 49.10 | 0.72 | 48.38 | 69.29 | 24.41 | 0.00 | 0.00 | 0.00 |
September | 37.77 | 0.02 | 37.75 | 41.73 | 44.93 | 0.00 | 0.00 | 0.00 |
October | 28.06 | 0.00 | 28.06 | 14.52 | 73.05 | 0.00 | 0.00 | 0.00 |
November | 19.63 | 0.00 | 19.63 | 3.17 | 118.59 | 0.00 | 0.00 | 0.00 |
December | 12.73 | 0.00 | 12.73 | 0.00 | 173.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.72 | 0.89 | 35.83 | 33.01 | 85.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.73 | 0.00 | 12.73 | 0.00 | 19.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.87 | 4.86 | 57.01 | 85.58 | 196.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 395.04 | 273.69 | 121.35 | 399.83 | 525.90 | 0.00 | 0.00 | 0.00 |
February | 421.48 | 287.88 | 133.60 | 448.75 | 421.23 | 0.00 | 0.00 | 0.00 |
March | 353.40 | 183.80 | 169.60 | 400.67 | 300.07 | 0.00 | 0.00 | 0.00 |
April | 306.64 | 134.76 | 171.88 | 397.97 | 220.43 | 0.00 | 0.00 | 0.00 |
May | 260.08 | 65.17 | 194.91 | 362.44 | 131.31 | 0.00 | 0.00 | 0.00 |
June | 248.27 | 41.53 | 206.74 | 387.02 | 83.48 | 0.00 | 0.00 | 0.00 |
July | 262.57 | 56.99 | 205.58 | 430.54 | 68.52 | 0.00 | 0.00 | 0.00 |
August | 292.53 | 93.94 | 198.58 | 480.44 | 84.56 | 0.00 | 0.00 | 0.00 |
September | 358.41 | 180.90 | 177.52 | 543.80 | 145.59 | 0.00 | 0.00 | 0.00 |
October | 398.25 | 252.18 | 146.07 | 519.24 | 222.23 | 0.00 | 0.00 | 0.00 |
November | 301.77 | 191.15 | 110.62 | 327.59 | 337.97 | 0.00 | 0.00 | 0.00 |
December | 324.61 | 248.17 | 76.44 | 353.77 | 488.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.40 | 166.86 | 159.54 | 420.85 | 251.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 248.27 | 41.53 | 76.44 | 327.59 | 68.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.48 | 287.88 | 206.74 | 543.80 | 525.90 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143343E+10 | 0.993101E+09 | 0.440330E+09 | 0.148625E+10 | 0.178208E+10 |
February | 0.138138E+10 | 0.943518E+09 | 0.437857E+09 | 0.150017E+10 | 0.129386E+10 |
March | 0.128232E+10 | 0.666933E+09 | 0.615391E+09 | 0.148161E+10 | 0.101256E+10 |
April | 0.107677E+10 | 0.473213E+09 | 0.603555E+09 | 0.141746E+10 | 0.708600E+09 |
May | 0.943718E+09 | 0.236485E+09 | 0.707234E+09 | 0.136226E+10 | 0.414761E+09 |
June | 0.871803E+09 | 0.145845E+09 | 0.725958E+09 | 0.138680E+10 | 0.260150E+09 |
July | 0.952760E+09 | 0.206809E+09 | 0.745951E+09 | 0.158065E+10 | 0.231538E+09 |
August | 0.106145E+10 | 0.340881E+09 | 0.720570E+09 | 0.176447E+10 | 0.283169E+09 |
September | 0.125858E+10 | 0.635225E+09 | 0.623353E+09 | 0.192816E+10 | 0.471642E+09 |
October | 0.144508E+10 | 0.915069E+09 | 0.530009E+09 | 0.189952E+10 | 0.757872E+09 |
November | 0.105968E+10 | 0.671248E+09 | 0.388430E+09 | 0.117356E+10 | 0.109985E+10 |
December | 0.117787E+10 | 0.900495E+09 | 0.277376E+09 | 0.129982E+10 | 0.165414E+10 |
Annual Sum or Average | 0.139448E+11 | 0.712882E+10 | 0.681601E+10 | 0.182807E+11 | 0.997022E+10 |
Minimum of Months | 0.871803E+09 | 0.145845E+09 | 0.277376E+09 | 0.117356E+10 | 0.231538E+09 |
Maximum of Months | 0.144508E+10 | 0.993101E+09 | 0.745951E+09 | 0.192816E+10 | 0.178208E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.403645E+10 | 0.279651E+10 | 0.123994E+10 | 0.417201E+10 | 0.498648E+10 |
February | 0.388986E+10 | 0.265689E+10 | 0.123298E+10 | 0.421483E+10 | 0.362498E+10 |
March | 0.361094E+10 | 0.187804E+10 | 0.173290E+10 | 0.417048E+10 | 0.283431E+10 |
April | 0.303211E+10 | 0.133254E+10 | 0.169957E+10 | 0.401693E+10 | 0.196563E+10 |
May | 0.265745E+10 | 0.665925E+09 | 0.199152E+10 | 0.391019E+10 | 0.110839E+10 |
June | 0.245494E+10 | 0.410691E+09 | 0.204425E+10 | 0.403033E+10 | 0.650150E+09 |
July | 0.268291E+10 | 0.582360E+09 | 0.210055E+10 | 0.460611E+10 | 0.542060E+09 |
August | 0.298897E+10 | 0.959898E+09 | 0.202908E+10 | 0.510210E+10 | 0.684809E+09 |
September | 0.354407E+10 | 0.178875E+10 | 0.175532E+10 | 0.548878E+10 | 0.125062E+10 |
October | 0.406924E+10 | 0.257677E+10 | 0.149247E+10 | 0.536268E+10 | 0.211203E+10 |
November | 0.298398E+10 | 0.189019E+10 | 0.109379E+10 | 0.329507E+10 | 0.308594E+10 |
December | 0.331681E+10 | 0.253573E+10 | 0.781074E+09 | 0.365571E+10 | 0.463134E+10 |
Annual Sum or Average | 0.392677E+11 | 0.200743E+11 | 0.191934E+11 | 0.520252E+11 | 0.274767E+11 |
Minimum of Months | 0.245494E+10 | 0.410691E+09 | 0.781074E+09 | 0.329507E+10 | 0.542060E+09 |
Maximum of Months | 0.406924E+10 | 0.279651E+10 | 0.210055E+10 | 0.548878E+10 | 0.498648E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.524358E+10 | 0.363282E+10 | 0.161075E+10 | 0.545062E+10 | 0.674026E+10 |
February | 0.505315E+10 | 0.345145E+10 | 0.160171E+10 | 0.551355E+10 | 0.491553E+10 |
March | 0.469082E+10 | 0.243968E+10 | 0.225114E+10 | 0.545476E+10 | 0.390146E+10 |
April | 0.393888E+10 | 0.173104E+10 | 0.220784E+10 | 0.525532E+10 | 0.274283E+10 |
May | 0.345218E+10 | 0.865074E+09 | 0.258710E+10 | 0.507130E+10 | 0.159428E+10 |
June | 0.318911E+10 | 0.533511E+09 | 0.265560E+10 | 0.522176E+10 | 0.964639E+09 |
July | 0.348525E+10 | 0.756519E+09 | 0.272873E+10 | 0.597258E+10 | 0.815516E+09 |
August | 0.388285E+10 | 0.124696E+10 | 0.263589E+10 | 0.663444E+10 | 0.101096E+10 |
September | 0.460395E+10 | 0.232369E+10 | 0.228026E+10 | 0.716761E+10 | 0.177946E+10 |
October | 0.528618E+10 | 0.334738E+10 | 0.193880E+10 | 0.700474E+10 | 0.294325E+10 |
November | 0.387637E+10 | 0.245547E+10 | 0.142090E+10 | 0.429598E+10 | 0.424708E+10 |
December | 0.430872E+10 | 0.329406E+10 | 0.101466E+10 | 0.477940E+10 | 0.629558E+10 |
Annual Sum or Average | 0.510110E+11 | 0.260777E+11 | 0.249334E+11 | 0.678221E+11 | 0.379508E+11 |
Minimum of Months | 0.318911E+10 | 0.533511E+09 | 0.101466E+10 | 0.429598E+10 | 0.815516E+09 |
Maximum of Months | 0.528618E+10 | 0.363282E+10 | 0.272873E+10 | 0.716761E+10 | 0.674026E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283414E+09 | 0.196353E+09 | 87061280.21 | 0.294000E+09 | 0.361147E+09 |
February | 0.273122E+09 | 0.186550E+09 | 86572449.12 | 0.296459E+09 | 0.261830E+09 |
March | 0.253538E+09 | 0.131864E+09 | 0.121674E+09 | 0.292571E+09 | 0.204933E+09 |
April | 0.212897E+09 | 93562390.41 | 0.119334E+09 | 0.280991E+09 | 0.140859E+09 |
May | 0.186591E+09 | 46757062.89 | 0.139834E+09 | 0.270613E+09 | 78100619.11 |
June | 0.172372E+09 | 28836144.59 | 0.143536E+09 | 0.281441E+09 | 43302650.40 |
July | 0.188379E+09 | 40889674.29 | 0.147489E+09 | 0.321935E+09 | 34712514.47 |
August | 0.209868E+09 | 67397982.69 | 0.142470E+09 | 0.356875E+09 | 44043526.03 |
September | 0.248843E+09 | 0.125595E+09 | 0.123249E+09 | 0.386385E+09 | 84752624.27 |
October | 0.285717E+09 | 0.180925E+09 | 0.104793E+09 | 0.377379E+09 | 0.148441E+09 |
November | 0.209517E+09 | 0.132717E+09 | 76799662.75 | 0.232721E+09 | 0.220938E+09 |
December | 0.232886E+09 | 0.178043E+09 | 54842386.97 | 0.258096E+09 | 0.333536E+09 |
Annual Sum or Average | 0.275714E+10 | 0.140949E+10 | 0.134765E+10 | 0.364947E+10 | 0.195660E+10 |
Minimum of Months | 0.172372E+09 | 28836144.59 | 54842386.97 | 0.232721E+09 | 34712514.47 |
Maximum of Months | 0.285717E+09 | 0.196353E+09 | 0.147489E+09 | 0.386385E+09 | 0.361147E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174899E+09 | 70056597.41 | 0.104843E+09 | 92119156.04 | 0.761363E+09 |
February | 0.232515E+09 | 0.114263E+09 | 0.118252E+09 | 0.175618E+09 | 0.547930E+09 |
March | 0.308268E+09 | 0.114971E+09 | 0.193297E+09 | 0.275764E+09 | 0.393587E+09 |
April | 0.438571E+09 | 0.218557E+09 | 0.220014E+09 | 0.534237E+09 | 0.256276E+09 |
May | 0.453232E+09 | 0.182820E+09 | 0.270412E+09 | 0.619554E+09 | 0.141814E+09 |
June | 0.513942E+09 | 0.224152E+09 | 0.289790E+09 | 0.784517E+09 | 79748811.41 |
July | 0.570900E+09 | 0.273083E+09 | 0.297817E+09 | 0.896874E+09 | 64349667.38 |
August | 0.498629E+09 | 0.230271E+09 | 0.268358E+09 | 0.781596E+09 | 81831038.27 |
September | 0.391398E+09 | 0.186985E+09 | 0.204413E+09 | 0.559536E+09 | 0.157337E+09 |
October | 0.281514E+09 | 0.125818E+09 | 0.155695E+09 | 0.314253E+09 | 0.288335E+09 |
November | 0.161364E+09 | 59208257.16 | 0.102156E+09 | 0.118189E+09 | 0.449549E+09 |
December | 0.127043E+09 | 58958369.16 | 68084650.81 | 80449605.79 | 0.686757E+09 |
Annual Sum or Average | 0.415228E+10 | 0.185915E+10 | 0.229313E+10 | 0.523271E+10 | 0.390888E+10 |
Minimum of Months | 0.127043E+09 | 58958369.16 | 68084650.81 | 80449605.79 | 64349667.38 |
Maximum of Months | 0.570900E+09 | 0.273083E+09 | 0.297817E+09 | 0.896874E+09 | 0.761363E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44321728.10 | 0.00 | 44321728.10 | 224068.83 | 0.436980E+09 |
February | 50753451.83 | 0.00 | 50753451.83 | 3363469.68 | 0.317265E+09 |
March | 84224438.77 | 221.66 | 84224217.11 | 33418414.09 | 0.221511E+09 |
April | 94196232.63 | 492911.10 | 93703321.54 | 65923377.77 | 0.140128E+09 |
May | 0.125849E+09 | 3736812.86 | 0.122113E+09 | 0.141656E+09 | 73499398.65 |
June | 0.141532E+09 | 11119765.68 | 0.130412E+09 | 0.206012E+09 | 42873826.48 |
July | 0.137319E+09 | 7618002.50 | 0.129701E+09 | 0.208589E+09 | 36652806.91 |
August | 0.116053E+09 | 1691101.26 | 0.114362E+09 | 0.173594E+09 | 45721766.95 |
September | 86403966.90 | 40416.61 | 86363550.29 | 0.103580E+09 | 87508466.64 |
October | 66327849.77 | 0.00 | 66327849.77 | 40435844.10 | 0.158075E+09 |
November | 44900279.42 | 0.00 | 44900279.42 | 9738061.26 | 0.251294E+09 |
December | 30095880.21 | 0.00 | 30095880.21 | 48234.71 | 0.384522E+09 |
Annual Sum or Average | 0.102198E+10 | 24699231.67 | 0.997278E+09 | 0.986583E+09 | 0.219603E+10 |
Minimum of Months | 30095880.21 | 0.00 | 30095880.21 | 48234.71 | 36652806.91 |
Maximum of Months | 0.141532E+09 | 11119765.68 | 0.130412E+09 | 0.208589E+09 | 0.436980E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174899E+09 | 70056597.41 | 0.104843E+09 | 94843579.28 | 0.757776E+09 |
February | 0.232515E+09 | 0.114263E+09 | 0.118252E+09 | 0.180151E+09 | 0.543710E+09 |
March | 0.308268E+09 | 0.114971E+09 | 0.193297E+09 | 0.281968E+09 | 0.390062E+09 |
April | 0.438571E+09 | 0.218557E+09 | 0.220014E+09 | 0.537771E+09 | 0.255513E+09 |
May | 0.453232E+09 | 0.182820E+09 | 0.270412E+09 | 0.617533E+09 | 0.143989E+09 |
June | 0.513942E+09 | 0.224152E+09 | 0.289790E+09 | 0.778551E+09 | 83947868.04 |
July | 0.570900E+09 | 0.273083E+09 | 0.297817E+09 | 0.889807E+09 | 71050076.45 |
August | 0.498629E+09 | 0.230271E+09 | 0.268358E+09 | 0.777270E+09 | 88347194.20 |
September | 0.391398E+09 | 0.186985E+09 | 0.204413E+09 | 0.561221E+09 | 0.159644E+09 |
October | 0.281514E+09 | 0.125818E+09 | 0.155695E+09 | 0.321429E+09 | 0.284780E+09 |
November | 0.161364E+09 | 59208257.16 | 0.102156E+09 | 0.122171E+09 | 0.446037E+09 |
December | 0.127043E+09 | 58958369.16 | 68084650.81 | 83795527.86 | 0.682676E+09 |
Annual Sum or Average | 0.415228E+10 | 0.185915E+10 | 0.229313E+10 | 0.524651E+10 | 0.390753E+10 |
Minimum of Months | 0.127043E+09 | 58958369.16 | 68084650.81 | 83795527.86 | 71050076.45 |
Maximum of Months | 0.570900E+09 | 0.273083E+09 | 0.297817E+09 | 0.889807E+09 | 0.757776E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226686E+09 | 0.157051E+09 | 69635175.61 | 0.242721E+09 | 0.253636E+09 |
February | 0.218454E+09 | 0.149210E+09 | 69244188.50 | 0.240420E+09 | 0.198523E+09 |
March | 0.202790E+09 | 0.105470E+09 | 97320046.63 | 0.229207E+09 | 0.168492E+09 |
April | 0.170284E+09 | 74835029.66 | 95448506.50 | 0.210359E+09 | 0.146746E+09 |
May | 0.149243E+09 | 37398212.82 | 0.111845E+09 | 0.191975E+09 | 95936521.24 |
June | 0.137870E+09 | 23064328.80 | 0.114806E+09 | 0.199706E+09 | 62304357.31 |
July | 0.150673E+09 | 32705235.25 | 0.117968E+09 | 0.231559E+09 | 54319826.07 |
August | 0.167861E+09 | 53907665.37 | 0.113954E+09 | 0.261075E+09 | 65096238.76 |
September | 0.199035E+09 | 0.100456E+09 | 98579302.31 | 0.287979E+09 | 0.103246E+09 |
October | 0.228528E+09 | 0.144711E+09 | 83817345.33 | 0.279380E+09 | 0.161353E+09 |
November | 0.167580E+09 | 0.106153E+09 | 61427513.93 | 0.175670E+09 | 0.197897E+09 |
December | 0.186271E+09 | 0.142406E+09 | 43865185.97 | 0.210471E+09 | 0.238015E+09 |
Annual Sum or Average | 0.220528E+10 | 0.112737E+10 | 0.107791E+10 | 0.276052E+10 | 0.174556E+10 |
Minimum of Months | 0.137870E+09 | 23064328.80 | 43865185.97 | 0.175670E+09 | 54319826.07 |
Maximum of Months | 0.228528E+09 | 0.157051E+09 | 0.117968E+09 | 0.287979E+09 | 0.253636E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35462082.56 | 0.00 | 35462082.56 | 111502.28 | 0.360037E+09 |
February | 40608143.59 | 0.00 | 40608143.59 | 2184865.64 | 0.261390E+09 |
March | 67388482.56 | 177.35 | 67388305.21 | 25445296.77 | 0.182034E+09 |
April | 75366975.10 | 394381.15 | 74972593.95 | 54149126.10 | 0.113505E+09 |
May | 0.100693E+09 | 2989846.56 | 97703050.50 | 0.117412E+09 | 57857074.10 |
June | 0.113241E+09 | 8896991.73 | 0.104344E+09 | 0.170592E+09 | 32643898.61 |
July | 0.109870E+09 | 6095209.85 | 0.103775E+09 | 0.173905E+09 | 26507841.32 |
August | 92854919.86 | 1353060.34 | 91501859.52 | 0.145133E+09 | 33940706.02 |
September | 69132336.19 | 32337.57 | 69099998.61 | 85919244.02 | 68565435.64 |
October | 53069313.52 | 0.00 | 53069313.52 | 31420386.10 | 0.129141E+09 |
November | 35924984.97 | 0.00 | 35924984.97 | 7013934.27 | 0.208466E+09 |
December | 24079895.67 | 0.00 | 24079895.67 | 14193.06 | 0.317961E+09 |
Annual Sum or Average | 0.817690E+09 | 19762004.55 | 0.797928E+09 | 0.813301E+09 | 0.179205E+10 |
Minimum of Months | 24079895.67 | 0.00 | 24079895.67 | 14193.06 | 26507841.32 |
Maximum of Months | 0.113241E+09 | 8896991.73 | 0.104344E+09 | 0.173905E+09 | 0.360037E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174328E+09 | 69959765.08 | 0.104368E+09 | 84531038.91 | 0.748881E+09 |
February | 0.211943E+09 | 92870063.64 | 0.119073E+09 | 0.138195E+09 | 0.537798E+09 |
March | 0.320471E+09 | 0.127549E+09 | 0.192922E+09 | 0.286812E+09 | 0.383799E+09 |
April | 0.380259E+09 | 0.167154E+09 | 0.213105E+09 | 0.436159E+09 | 0.250464E+09 |
May | 0.496401E+09 | 0.218920E+09 | 0.277481E+09 | 0.677528E+09 | 0.134157E+09 |
June | 0.527209E+09 | 0.231191E+09 | 0.296018E+09 | 0.803733E+09 | 75758948.20 |
July | 0.552072E+09 | 0.257063E+09 | 0.295009E+09 | 0.861030E+09 | 60585404.50 |
August | 0.465355E+09 | 0.202481E+09 | 0.262874E+09 | 0.723925E+09 | 76816270.80 |
September | 0.403159E+09 | 0.192595E+09 | 0.210563E+09 | 0.575816E+09 | 0.153758E+09 |
October | 0.261599E+09 | 0.108600E+09 | 0.153000E+09 | 0.275467E+09 | 0.279542E+09 |
November | 0.148625E+09 | 47288807.92 | 0.101336E+09 | 91411277.64 | 0.440284E+09 |
December | 0.117248E+09 | 48832671.50 | 68415165.44 | 57829915.38 | 0.675999E+09 |
Annual Sum or Average | 0.405867E+10 | 0.176450E+10 | 0.229416E+10 | 0.501244E+10 | 0.381784E+10 |
Minimum of Months | 0.117248E+09 | 47288807.92 | 68415165.44 | 57829915.38 | 60585404.50 |
Maximum of Months | 0.552072E+09 | 0.257063E+09 | 0.296018E+09 | 0.861030E+09 | 0.748881E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283414E+09 | 0.196353E+09 | 87061280.21 | 0.293625E+09 | 0.360931E+09 |
February | 0.273122E+09 | 0.186550E+09 | 86572449.12 | 0.296053E+09 | 0.261255E+09 |
March | 0.253538E+09 | 0.131864E+09 | 0.121674E+09 | 0.290893E+09 | 0.204451E+09 |
April | 0.212897E+09 | 93562390.41 | 0.119334E+09 | 0.280074E+09 | 0.139449E+09 |
May | 0.186591E+09 | 46757062.89 | 0.139834E+09 | 0.268542E+09 | 77807418.20 |
June | 0.172372E+09 | 28836144.59 | 0.143536E+09 | 0.280018E+09 | 42753122.32 |
July | 0.188379E+09 | 40889674.29 | 0.147489E+09 | 0.320953E+09 | 33849104.98 |
August | 0.209868E+09 | 67397982.69 | 0.142470E+09 | 0.356206E+09 | 43331488.85 |
September | 0.248843E+09 | 0.125595E+09 | 0.123249E+09 | 0.384954E+09 | 84231380.64 |
October | 0.285717E+09 | 0.180925E+09 | 0.104793E+09 | 0.376301E+09 | 0.147823E+09 |
November | 0.209517E+09 | 0.132717E+09 | 76799662.75 | 0.232528E+09 | 0.220533E+09 |
December | 0.232886E+09 | 0.178043E+09 | 54842386.97 | 0.258045E+09 | 0.333184E+09 |
Annual Sum or Average | 0.275714E+10 | 0.140949E+10 | 0.134765E+10 | 0.363819E+10 | 0.194960E+10 |
Minimum of Months | 0.172372E+09 | 28836144.59 | 54842386.97 | 0.232528E+09 | 33849104.98 |
Maximum of Months | 0.285717E+09 | 0.196353E+09 | 0.147489E+09 | 0.384954E+09 | 0.360931E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44321728.10 | 0.00 | 44321728.10 | 196533.89 | 0.437081E+09 |
February | 50753451.83 | 0.00 | 50753451.83 | 3077172.45 | 0.316967E+09 |
March | 84224438.77 | 221.66 | 84224217.11 | 32420002.20 | 0.221614E+09 |
April | 94196232.63 | 492911.10 | 93703321.54 | 65271814.20 | 0.138549E+09 |
May | 0.125849E+09 | 3736812.86 | 0.122113E+09 | 0.139828E+09 | 72908588.65 |
June | 0.141532E+09 | 11119765.68 | 0.130412E+09 | 0.204580E+09 | 41978093.53 |
July | 0.137319E+09 | 7618002.50 | 0.129701E+09 | 0.207115E+09 | 35178301.14 |
August | 0.116053E+09 | 1691101.26 | 0.114362E+09 | 0.172783E+09 | 44233489.39 |
September | 86403966.90 | 40416.61 | 86363550.29 | 0.101856E+09 | 86543018.71 |
October | 66327849.77 | 0.00 | 66327849.77 | 39511905.39 | 0.157082E+09 |
November | 44900279.42 | 0.00 | 44900279.42 | 9555901.07 | 0.250929E+09 |
December | 30095880.21 | 0.00 | 30095880.21 | 36729.26 | 0.384602E+09 |
Annual Sum or Average | 0.102198E+10 | 24699231.67 | 0.997278E+09 | 0.976231E+09 | 0.218767E+10 |
Minimum of Months | 30095880.21 | 0.00 | 30095880.21 | 36729.26 | 35178301.14 |
Maximum of Months | 0.141532E+09 | 11119765.68 | 0.130412E+09 | 0.207115E+09 | 0.437081E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174328E+09 | 69959765.08 | 0.104368E+09 | 86049604.36 | 0.744017E+09 |
February | 0.211943E+09 | 92870063.64 | 0.119073E+09 | 0.141079E+09 | 0.532035E+09 |
March | 0.320471E+09 | 0.127549E+09 | 0.192922E+09 | 0.292346E+09 | 0.379373E+09 |
April | 0.380259E+09 | 0.167154E+09 | 0.213105E+09 | 0.439945E+09 | 0.248933E+09 |
May | 0.496401E+09 | 0.218920E+09 | 0.277481E+09 | 0.676628E+09 | 0.135947E+09 |
June | 0.527209E+09 | 0.231191E+09 | 0.296018E+09 | 0.797958E+09 | 79367806.25 |
July | 0.552072E+09 | 0.257063E+09 | 0.295009E+09 | 0.853077E+09 | 66172062.28 |
August | 0.465355E+09 | 0.202481E+09 | 0.262874E+09 | 0.719789E+09 | 82136029.37 |
September | 0.403159E+09 | 0.192595E+09 | 0.210563E+09 | 0.577146E+09 | 0.155195E+09 |
October | 0.261599E+09 | 0.108600E+09 | 0.153000E+09 | 0.282716E+09 | 0.274887E+09 |
November | 0.148625E+09 | 47288807.92 | 0.101336E+09 | 94167817.99 | 0.435391E+09 |
December | 0.117248E+09 | 48832671.50 | 68415165.44 | 58995127.09 | 0.670223E+09 |
Annual Sum or Average | 0.405867E+10 | 0.176450E+10 | 0.229416E+10 | 0.501990E+10 | 0.380368E+10 |
Minimum of Months | 0.117248E+09 | 47288807.92 | 68415165.44 | 58995127.09 | 66172062.28 |
Maximum of Months | 0.552072E+09 | 0.257063E+09 | 0.296018E+09 | 0.853077E+09 | 0.744017E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56130672.10 | 0.00 | 56130672.10 | 110895.33 | 0.584594E+09 |
February | 64276044.38 | 0.00 | 64276044.38 | 2939615.61 | 0.424192E+09 |
March | 0.106665E+09 | 280.72 | 0.106665E+09 | 39352850.28 | 0.293548E+09 |
April | 0.119294E+09 | 624240.80 | 0.118669E+09 | 85186689.24 | 0.184003E+09 |
May | 0.159380E+09 | 4732437.71 | 0.154648E+09 | 0.185625E+09 | 96619194.62 |
June | 0.179241E+09 | 14082481.62 | 0.165159E+09 | 0.265800E+09 | 58162539.71 |
July | 0.173906E+09 | 9647719.50 | 0.164258E+09 | 0.268673E+09 | 50040197.08 |
August | 0.146974E+09 | 2141673.04 | 0.144832E+09 | 0.223470E+09 | 62448407.15 |
September | 0.109425E+09 | 51185.09 | 0.109374E+09 | 0.131911E+09 | 0.118393E+09 |
October | 84000036.67 | 0.00 | 84000036.67 | 49625286.71 | 0.207714E+09 |
November | 56863370.83 | 0.00 | 56863370.83 | 10977994.08 | 0.337169E+09 |
December | 38114533.34 | 0.00 | 38114533.34 | 9344.61 | 0.516375E+09 |
Annual Sum or Average | 0.129427E+10 | 31280018.47 | 0.126299E+10 | 0.126368E+10 | 0.293326E+10 |
Minimum of Months | 38114533.34 | 0.00 | 38114533.34 | 9344.61 | 50040197.08 |
Maximum of Months | 0.179241E+09 | 14082481.62 | 0.165159E+09 | 0.268673E+09 | 0.584594E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 20692089.92 | 0.00 | 20692089.92 | 40880.61 | 0.215506E+09 |
February | 23694811.42 | 0.00 | 23694811.42 | 1083664.04 | 0.156375E+09 |
March | 39321112.59 | 103.48 | 39321009.10 | 14507090.09 | 0.108214E+09 |
April | 43976555.05 | 230121.01 | 43746434.05 | 31403340.96 | 67831204.44 |
May | 58754205.34 | 1744572.49 | 57009632.85 | 68428986.60 | 35617835.82 |
June | 66075739.62 | 5191385.83 | 60884353.79 | 97984838.77 | 21441120.46 |
July | 64108967.03 | 3556548.89 | 60552418.14 | 99043925.81 | 18446888.65 |
August | 54180753.44 | 789509.36 | 53391244.08 | 82380459.60 | 23021068.66 |
September | 40338649.44 | 18868.94 | 40319780.50 | 48628024.87 | 43644665.82 |
October | 30965891.69 | 0.00 | 30965891.69 | 18293935.50 | 76571981.15 |
November | 20962193.02 | 0.00 | 20962193.02 | 4046943.18 | 0.124295E+09 |
December | 14050595.19 | 0.00 | 14050595.19 | 3444.81 | 0.190357E+09 |
Annual Sum or Average | 0.477122E+09 | 11531110.01 | 0.465590E+09 | 0.465846E+09 | 0.108132E+10 |
Minimum of Months | 14050595.19 | 0.00 | 14050595.19 | 3444.81 | 18446888.65 |
Maximum of Months | 66075739.62 | 5191385.83 | 60884353.79 | 99043925.81 | 0.215506E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132240E+09 | 91617610.47 | 40622442.52 | 0.135016E+09 | 0.175456E+09 |
February | 0.127438E+09 | 87043382.57 | 40394355.90 | 0.137000E+09 | 0.126733E+09 |
March | 0.118300E+09 | 61527280.27 | 56772715.30 | 0.136261E+09 | 98742853.27 |
April | 99336766.20 | 43655834.34 | 55680931.86 | 0.132442E+09 | 67819365.61 |
May | 87062444.15 | 21816657.13 | 65245787.02 | 0.128131E+09 | 38427537.61 |
June | 80428064.97 | 13454828.87 | 66973236.10 | 0.131743E+09 | 22963207.12 |
July | 87896712.53 | 19078957.25 | 68817755.28 | 0.150242E+09 | 19466457.76 |
August | 97923687.67 | 31447627.13 | 66476060.54 | 0.166919E+09 | 24098124.88 |
September | 0.116109E+09 | 58602044.79 | 57507315.90 | 0.180918E+09 | 42926706.77 |
October | 0.133315E+09 | 84418810.94 | 48895766.58 | 0.177387E+09 | 70826354.79 |
November | 97759785.70 | 61925372.53 | 35834413.16 | 0.107841E+09 | 0.107456E+09 |
December | 0.108663E+09 | 83074262.66 | 25589236.76 | 0.119335E+09 | 0.162719E+09 |
Annual Sum or Average | 0.128647E+10 | 0.657663E+09 | 0.628810E+09 | 0.170324E+10 | 0.957635E+09 |
Minimum of Months | 80428064.97 | 13454828.87 | 25589236.76 | 0.107841E+09 | 19466457.76 |
Maximum of Months | 0.133315E+09 | 91617610.47 | 68817755.28 | 0.180918E+09 | 0.175456E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358927E+09 | 0.248669E+09 | 0.110258E+09 | 0.366461E+09 | 0.476224E+09 |
February | 0.345892E+09 | 0.236254E+09 | 0.109639E+09 | 0.371845E+09 | 0.343980E+09 |
March | 0.321090E+09 | 0.166998E+09 | 0.154093E+09 | 0.369840E+09 | 0.268008E+09 |
April | 0.269620E+09 | 0.118491E+09 | 0.151129E+09 | 0.359476E+09 | 0.184076E+09 |
May | 0.236305E+09 | 59214869.95 | 0.177090E+09 | 0.347774E+09 | 0.104300E+09 |
June | 0.218298E+09 | 36519157.67 | 0.181779E+09 | 0.357578E+09 | 62326841.15 |
July | 0.238570E+09 | 51784192.50 | 0.186785E+09 | 0.407788E+09 | 52835948.14 |
August | 0.265785E+09 | 85355292.50 | 0.180430E+09 | 0.453052E+09 | 65407240.08 |
September | 0.315145E+09 | 0.159058E+09 | 0.156087E+09 | 0.491049E+09 | 0.116512E+09 |
October | 0.361843E+09 | 0.229130E+09 | 0.132713E+09 | 0.481465E+09 | 0.192237E+09 |
November | 0.265340E+09 | 0.168078E+09 | 97261927.09 | 0.292703E+09 | 0.291657E+09 |
December | 0.294935E+09 | 0.225481E+09 | 69454422.74 | 0.323899E+09 | 0.441654E+09 |
Annual Sum or Average | 0.349175E+10 | 0.178503E+10 | 0.170672E+10 | 0.462293E+10 | 0.259922E+10 |
Minimum of Months | 0.218298E+09 | 36519157.67 | 69454422.74 | 0.292703E+09 | 52835948.14 |
Maximum of Months | 0.361843E+09 | 0.248669E+09 | 0.186785E+09 | 0.491049E+09 | 0.476224E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283414E+09 | 0.196353E+09 | 87061280.21 | 0.293211E+09 | 0.359853E+09 |
February | 0.273122E+09 | 0.186550E+09 | 86572449.12 | 0.295772E+09 | 0.260422E+09 |
March | 0.253538E+09 | 0.131864E+09 | 0.121674E+09 | 0.292090E+09 | 0.203486E+09 |
April | 0.212897E+09 | 93562390.41 | 0.119334E+09 | 0.279660E+09 | 0.139627E+09 |
May | 0.186591E+09 | 46757062.89 | 0.139834E+09 | 0.268523E+09 | 77469877.90 |
June | 0.172372E+09 | 28836144.59 | 0.143536E+09 | 0.279696E+09 | 42527799.38 |
July | 0.188379E+09 | 40889674.29 | 0.147489E+09 | 0.320022E+09 | 33871602.12 |
August | 0.209868E+09 | 67397982.69 | 0.142470E+09 | 0.354838E+09 | 43209488.84 |
September | 0.248843E+09 | 0.125595E+09 | 0.123249E+09 | 0.385070E+09 | 83237266.24 |
October | 0.285717E+09 | 0.180925E+09 | 0.104793E+09 | 0.376481E+09 | 0.146918E+09 |
November | 0.209517E+09 | 0.132717E+09 | 76799662.75 | 0.232568E+09 | 0.219196E+09 |
December | 0.232886E+09 | 0.178043E+09 | 54842386.97 | 0.257930E+09 | 0.331730E+09 |
Annual Sum or Average | 0.275714E+10 | 0.140949E+10 | 0.134765E+10 | 0.363586E+10 | 0.194155E+10 |
Minimum of Months | 0.172372E+09 | 28836144.59 | 54842386.97 | 0.232568E+09 | 33871602.12 |
Maximum of Months | 0.285717E+09 | 0.196353E+09 | 0.147489E+09 | 0.385070E+09 | 0.359853E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174899E+09 | 70056597.41 | 0.104843E+09 | 92008955.68 | 0.759094E+09 |
February | 0.232515E+09 | 0.114263E+09 | 0.118252E+09 | 0.175195E+09 | 0.545528E+09 |
March | 0.308268E+09 | 0.114971E+09 | 0.193297E+09 | 0.275561E+09 | 0.390625E+09 |
April | 0.438571E+09 | 0.218557E+09 | 0.220014E+09 | 0.531567E+09 | 0.253827E+09 |
May | 0.453232E+09 | 0.182820E+09 | 0.270412E+09 | 0.615481E+09 | 0.140479E+09 |
June | 0.513942E+09 | 0.224152E+09 | 0.289790E+09 | 0.780505E+09 | 78282704.06 |
July | 0.570900E+09 | 0.273083E+09 | 0.297817E+09 | 0.892439E+09 | 62752709.87 |
August | 0.498629E+09 | 0.230271E+09 | 0.268358E+09 | 0.777610E+09 | 80254231.15 |
September | 0.391398E+09 | 0.186985E+09 | 0.204413E+09 | 0.557820E+09 | 0.154476E+09 |
October | 0.281514E+09 | 0.125818E+09 | 0.155695E+09 | 0.313582E+09 | 0.285014E+09 |
November | 0.161364E+09 | 59208257.16 | 0.102156E+09 | 0.118779E+09 | 0.445651E+09 |
December | 0.127043E+09 | 58958369.16 | 68084650.81 | 80831034.23 | 0.683093E+09 |
Annual Sum or Average | 0.415228E+10 | 0.185915E+10 | 0.229313E+10 | 0.521138E+10 | 0.387908E+10 |
Minimum of Months | 0.127043E+09 | 58958369.16 | 68084650.81 | 80831034.23 | 62752709.87 |
Maximum of Months | 0.570900E+09 | 0.273083E+09 | 0.297817E+09 | 0.892439E+09 | 0.759094E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44321728.10 | 0.00 | 44321728.10 | 250678.72 | 0.435839E+09 |
February | 50753451.83 | 0.00 | 50753451.83 | 3509732.12 | 0.315754E+09 |
March | 84224438.77 | 221.66 | 84224217.11 | 33957182.04 | 0.219794E+09 |
April | 94196232.63 | 492911.10 | 93703321.54 | 65638801.93 | 0.139075E+09 |
May | 0.125849E+09 | 3736812.86 | 0.122113E+09 | 0.139729E+09 | 73467530.90 |
June | 0.141532E+09 | 11119765.68 | 0.130412E+09 | 0.204055E+09 | 42955927.96 |
July | 0.137319E+09 | 7618002.50 | 0.129701E+09 | 0.206793E+09 | 36813056.68 |
August | 0.116053E+09 | 1691101.26 | 0.114362E+09 | 0.172252E+09 | 45853031.67 |
September | 86403966.90 | 40416.61 | 86363550.29 | 0.103550E+09 | 86370538.50 |
October | 66327849.77 | 0.00 | 66327849.77 | 41187500.10 | 0.156063E+09 |
November | 44900279.42 | 0.00 | 44900279.42 | 10123162.49 | 0.248900E+09 |
December | 30095880.21 | 0.00 | 30095880.21 | 60150.35 | 0.382569E+09 |
Annual Sum or Average | 0.102198E+10 | 24699231.67 | 0.997278E+09 | 0.981107E+09 | 0.218345E+10 |
Minimum of Months | 30095880.21 | 0.00 | 30095880.21 | 60150.35 | 36813056.68 |
Maximum of Months | 0.141532E+09 | 11119765.68 | 0.130412E+09 | 0.206793E+09 | 0.435839E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174899E+09 | 70056597.41 | 0.104843E+09 | 94572218.50 | 0.755883E+09 |
February | 0.232515E+09 | 0.114263E+09 | 0.118252E+09 | 0.179779E+09 | 0.541598E+09 |
March | 0.308268E+09 | 0.114971E+09 | 0.193297E+09 | 0.281956E+09 | 0.387198E+09 |
April | 0.438571E+09 | 0.218557E+09 | 0.220014E+09 | 0.535241E+09 | 0.253256E+09 |
May | 0.453232E+09 | 0.182820E+09 | 0.270412E+09 | 0.612401E+09 | 0.143616E+09 |
June | 0.513942E+09 | 0.224152E+09 | 0.289790E+09 | 0.773450E+09 | 83879047.31 |
July | 0.570900E+09 | 0.273083E+09 | 0.297817E+09 | 0.884494E+09 | 71156341.58 |
August | 0.498629E+09 | 0.230271E+09 | 0.268358E+09 | 0.772627E+09 | 88334052.12 |
September | 0.391398E+09 | 0.186985E+09 | 0.204413E+09 | 0.559549E+09 | 0.157377E+09 |
October | 0.281514E+09 | 0.125818E+09 | 0.155695E+09 | 0.321579E+09 | 0.281164E+09 |
November | 0.161364E+09 | 59208257.16 | 0.102156E+09 | 0.122893E+09 | 0.442289E+09 |
December | 0.127043E+09 | 58958369.16 | 68084650.81 | 83928392.09 | 0.679557E+09 |
Annual Sum or Average | 0.415228E+10 | 0.185915E+10 | 0.229313E+10 | 0.522247E+10 | 0.388531E+10 |
Minimum of Months | 0.127043E+09 | 58958369.16 | 68084650.81 | 83928392.09 | 71156341.58 |
Maximum of Months | 0.570900E+09 | 0.273083E+09 | 0.297817E+09 | 0.884494E+09 | 0.755883E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415655E+09 | 0.287971E+09 | 0.127684E+09 | 0.419020E+09 | 0.538954E+09 |
February | 0.400560E+09 | 0.273593E+09 | 0.126967E+09 | 0.423800E+09 | 0.391396E+09 |
March | 0.371838E+09 | 0.193391E+09 | 0.178447E+09 | 0.418970E+09 | 0.305485E+09 |
April | 0.312234E+09 | 0.137218E+09 | 0.175015E+09 | 0.407591E+09 | 0.206589E+09 |
May | 0.273653E+09 | 68573720.02 | 0.205079E+09 | 0.394460E+09 | 0.112761E+09 |
June | 0.252800E+09 | 42290973.46 | 0.210509E+09 | 0.413688E+09 | 60706380.79 |
July | 0.276275E+09 | 59968631.55 | 0.216307E+09 | 0.474205E+09 | 46916174.59 |
August | 0.307792E+09 | 98845609.82 | 0.208946E+09 | 0.523460E+09 | 61254960.49 |
September | 0.364953E+09 | 0.184197E+09 | 0.180756E+09 | 0.562917E+09 | 0.122498E+09 |
October | 0.419032E+09 | 0.265344E+09 | 0.153688E+09 | 0.543874E+09 | 0.221376E+09 |
November | 0.307277E+09 | 0.194643E+09 | 0.112634E+09 | 0.332774E+09 | 0.330812E+09 |
December | 0.341549E+09 | 0.261118E+09 | 80431623.74 | 0.368751E+09 | 0.498453E+09 |
Annual Sum or Average | 0.404362E+10 | 0.206715E+10 | 0.197646E+10 | 0.528351E+10 | 0.289720E+10 |
Minimum of Months | 0.252800E+09 | 42290973.46 | 80431623.74 | 0.332774E+09 | 46916174.59 |
Maximum of Months | 0.419032E+09 | 0.287971E+09 | 0.216307E+09 | 0.562917E+09 | 0.538954E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.310240E+09 | 0.00 | 0.310240E+09 | 794274.46 | 0.315754E+10 |
February | 0.355261E+09 | 0.00 | 0.355261E+09 | 17396864.51 | 0.229252E+10 |
March | 0.589549E+09 | 1551.56 | 0.589547E+09 | 0.219218E+09 | 0.160463E+10 |
April | 0.659349E+09 | 3450246.99 | 0.655898E+09 | 0.474949E+09 | 0.101332E+10 |
May | 0.880913E+09 | 26156699.35 | 0.854756E+09 | 0.103356E+10 | 0.533451E+09 |
June | 0.990686E+09 | 77835411.79 | 0.912850E+09 | 0.150465E+10 | 0.309944E+09 |
July | 0.961198E+09 | 53323997.91 | 0.907874E+09 | 0.154033E+10 | 0.251089E+09 |
August | 0.812342E+09 | 11837260.47 | 0.800505E+09 | 0.128674E+10 | 0.318769E+09 |
September | 0.604805E+09 | 282905.55 | 0.604522E+09 | 0.763151E+09 | 0.623938E+09 |
October | 0.464277E+09 | 0.00 | 0.464277E+09 | 0.276326E+09 | 0.114377E+10 |
November | 0.314290E+09 | 0.00 | 0.314290E+09 | 61043651.13 | 0.183424E+10 |
December | 0.210663E+09 | 0.00 | 0.210663E+09 | 116277.10 | 0.279235E+10 |
Annual Sum or Average | 0.715357E+10 | 0.172888E+09 | 0.698068E+10 | 0.717828E+10 | 0.158756E+11 |
Minimum of Months | 0.210663E+09 | 0.00 | 0.210663E+09 | 116277.10 | 0.251089E+09 |
Maximum of Months | 0.990686E+09 | 77835411.79 | 0.912850E+09 | 0.154033E+10 | 0.315754E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.310240E+09 | 0.00 | 0.310240E+09 | 593605.46 | 0.321529E+10 |
February | 0.355261E+09 | 0.00 | 0.355261E+09 | 14860227.26 | 0.234427E+10 |
March | 0.589549E+09 | 1551.56 | 0.589547E+09 | 0.205525E+09 | 0.165900E+10 |
April | 0.659349E+09 | 3450246.99 | 0.655898E+09 | 0.455849E+09 | 0.105672E+10 |
May | 0.880913E+09 | 26156699.35 | 0.854756E+09 | 0.100554E+10 | 0.556356E+09 |
June | 0.990686E+09 | 77835411.79 | 0.912850E+09 | 0.147733E+10 | 0.326376E+09 |
July | 0.961198E+09 | 53323997.91 | 0.907874E+09 | 0.151322E+10 | 0.266620E+09 |
August | 0.812342E+09 | 11837260.47 | 0.800505E+09 | 0.126145E+10 | 0.336155E+09 |
September | 0.604805E+09 | 282905.55 | 0.604522E+09 | 0.742843E+09 | 0.651245E+09 |
October | 0.464277E+09 | 0.00 | 0.464277E+09 | 0.257676E+09 | 0.119303E+10 |
November | 0.314290E+09 | 0.00 | 0.314290E+09 | 54810950.60 | 0.189098E+10 |
December | 0.210663E+09 | 0.00 | 0.210663E+09 | 46548.68 | 0.285250E+10 |
Annual Sum or Average | 0.715357E+10 | 0.172888E+09 | 0.698068E+10 | 0.698975E+10 | 0.163485E+11 |
Minimum of Months | 0.210663E+09 | 0.00 | 0.210663E+09 | 46548.68 | 0.266620E+09 |
Maximum of Months | 0.990686E+09 | 77835411.79 | 0.912850E+09 | 0.151322E+10 | 0.321529E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44321728.10 | 0.00 | 44321728.10 | 3873836.44 | 0.363321E+09 |
February | 50753451.83 | 0.00 | 50753451.83 | 16213468.65 | 0.257589E+09 |
March | 84224438.77 | 221.66 | 84224217.11 | 77536626.36 | 0.178829E+09 |
April | 94196232.63 | 492911.10 | 93703321.54 | 0.134952E+09 | 0.110321E+09 |
May | 0.125849E+09 | 3736812.86 | 0.122113E+09 | 0.249717E+09 | 62393799.90 |
June | 0.141532E+09 | 11119765.68 | 0.130412E+09 | 0.324921E+09 | 36720385.57 |
July | 0.137319E+09 | 7618002.50 | 0.129701E+09 | 0.337367E+09 | 29453678.73 |
August | 0.116053E+09 | 1691101.26 | 0.114362E+09 | 0.295443E+09 | 35526522.55 |
September | 86403966.90 | 40416.61 | 86363550.29 | 0.196739E+09 | 65605559.17 |
October | 66327849.77 | 0.00 | 66327849.77 | 98884434.58 | 0.118595E+09 |
November | 44900279.42 | 0.00 | 44900279.42 | 36517457.41 | 0.194582E+09 |
December | 30095880.21 | 0.00 | 30095880.21 | 2588362.56 | 0.308396E+09 |
Annual Sum or Average | 0.102198E+10 | 24699231.67 | 0.997278E+09 | 0.177475E+10 | 0.176133E+10 |
Minimum of Months | 30095880.21 | 0.00 | 30095880.21 | 2588362.56 | 29453678.73 |
Maximum of Months | 0.141532E+09 | 11119765.68 | 0.130412E+09 | 0.337367E+09 | 0.363321E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348631E+09 | 0.139910E+09 | 0.208722E+09 | 0.234918E+09 | 0.125624E+10 |
February | 0.423856E+09 | 0.185727E+09 | 0.238129E+09 | 0.379150E+09 | 0.881368E+09 |
March | 0.640897E+09 | 0.255080E+09 | 0.385816E+09 | 0.795846E+09 | 0.633962E+09 |
April | 0.760463E+09 | 0.334284E+09 | 0.426179E+09 | 0.115707E+10 | 0.406069E+09 |
May | 0.992732E+09 | 0.437809E+09 | 0.554923E+09 | 0.176383E+10 | 0.231272E+09 |
June | 0.105434E+10 | 0.462349E+09 | 0.591993E+09 | 0.204377E+10 | 0.137103E+09 |
July | 0.110407E+10 | 0.514090E+09 | 0.589976E+09 | 0.219314E+10 | 0.110290E+09 |
August | 0.930643E+09 | 0.404934E+09 | 0.525710E+09 | 0.190003E+10 | 0.133311E+09 |
September | 0.806260E+09 | 0.385163E+09 | 0.421097E+09 | 0.152356E+10 | 0.242652E+09 |
October | 0.523161E+09 | 0.217184E+09 | 0.305977E+09 | 0.823199E+09 | 0.433984E+09 |
November | 0.297229E+09 | 94570899.63 | 0.202658E+09 | 0.321245E+09 | 0.691034E+09 |
December | 0.234479E+09 | 97658407.53 | 0.136821E+09 | 0.167248E+09 | 0.108920E+10 |
Annual Sum or Average | 0.811676E+10 | 0.352876E+10 | 0.458800E+10 | 0.133030E+11 | 0.624648E+10 |
Minimum of Months | 0.234479E+09 | 94570899.63 | 0.136821E+09 | 0.167248E+09 | 0.110290E+09 |
Maximum of Months | 0.110407E+10 | 0.514090E+09 | 0.591993E+09 | 0.219314E+10 | 0.125624E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283414E+09 | 0.196353E+09 | 87061280.21 | 0.329539E+09 | 0.311727E+09 |
February | 0.273122E+09 | 0.186550E+09 | 86572449.12 | 0.339024E+09 | 0.222734E+09 |
March | 0.253538E+09 | 0.131864E+09 | 0.121674E+09 | 0.354294E+09 | 0.171257E+09 |
April | 0.212897E+09 | 93562390.41 | 0.119334E+09 | 0.354458E+09 | 0.111107E+09 |
May | 0.186591E+09 | 46757062.89 | 0.139834E+09 | 0.375006E+09 | 64551002.45 |
June | 0.172372E+09 | 28836144.59 | 0.143536E+09 | 0.395678E+09 | 38106321.51 |
July | 0.188379E+09 | 40889674.29 | 0.147489E+09 | 0.446072E+09 | 30062583.85 |
August | 0.209868E+09 | 67397982.69 | 0.142470E+09 | 0.475193E+09 | 35878612.77 |
September | 0.248843E+09 | 0.125595E+09 | 0.123249E+09 | 0.483350E+09 | 65318224.31 |
October | 0.285717E+09 | 0.180925E+09 | 0.104793E+09 | 0.452741E+09 | 0.116545E+09 |
November | 0.209517E+09 | 0.132717E+09 | 76799662.75 | 0.280106E+09 | 0.178703E+09 |
December | 0.232886E+09 | 0.178043E+09 | 54842386.97 | 0.289114E+09 | 0.277245E+09 |
Annual Sum or Average | 0.275714E+10 | 0.140949E+10 | 0.134765E+10 | 0.457457E+10 | 0.162324E+10 |
Minimum of Months | 0.172372E+09 | 28836144.59 | 54842386.97 | 0.280106E+09 | 30062583.85 |
Maximum of Months | 0.285717E+09 | 0.196353E+09 | 0.147489E+09 | 0.483350E+09 | 0.311727E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56130672.10 | 0.00 | 56130672.10 | 77913.39 | 0.587601E+09 |
February | 64276044.38 | 0.00 | 64276044.38 | 2495694.78 | 0.427297E+09 |
March | 0.106665E+09 | 280.72 | 0.106665E+09 | 36261177.84 | 0.298926E+09 |
April | 0.119294E+09 | 624240.80 | 0.118669E+09 | 77147336.75 | 0.193805E+09 |
May | 0.159380E+09 | 4732437.71 | 0.154648E+09 | 0.166746E+09 | 0.110189E+09 |
June | 0.179241E+09 | 14082481.62 | 0.165159E+09 | 0.247923E+09 | 68125855.94 |
July | 0.173906E+09 | 9647719.50 | 0.164258E+09 | 0.251926E+09 | 58591280.52 |
August | 0.146974E+09 | 2141673.04 | 0.144832E+09 | 0.207441E+09 | 73075733.62 |
September | 0.109425E+09 | 51185.09 | 0.109374E+09 | 0.120887E+09 | 0.130158E+09 |
October | 84000036.67 | 0.00 | 84000036.67 | 43470743.88 | 0.218696E+09 |
November | 56863370.83 | 0.00 | 56863370.83 | 9182202.07 | 0.343564E+09 |
December | 38114533.34 | 0.00 | 38114533.34 | 2982.00 | 0.519207E+09 |
Annual Sum or Average | 0.129427E+10 | 31280018.47 | 0.126299E+10 | 0.116356E+10 | 0.302924E+10 |
Minimum of Months | 38114533.34 | 0.00 | 38114533.34 | 2982.00 | 58591280.52 |
Maximum of Months | 0.179241E+09 | 14082481.62 | 0.165159E+09 | 0.251926E+09 | 0.587601E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50220325.01 | 0.00 | 50220325.01 | 69709.40 | 0.525706E+09 |
February | 57508020.45 | 0.00 | 57508020.45 | 2232907.57 | 0.382304E+09 |
March | 95433523.67 | 251.16 | 95433272.52 | 32443013.21 | 0.267451E+09 |
April | 0.106732E+09 | 558510.61 | 0.106174E+09 | 69024014.50 | 0.173398E+09 |
May | 0.142598E+09 | 4234129.95 | 0.138364E+09 | 0.149188E+09 | 98586879.16 |
June | 0.160368E+09 | 12599649.66 | 0.147768E+09 | 0.221818E+09 | 60952461.44 |
July | 0.155594E+09 | 8631851.19 | 0.146963E+09 | 0.225399E+09 | 52421840.68 |
August | 0.131498E+09 | 1916162.98 | 0.129582E+09 | 0.185599E+09 | 65381135.75 |
September | 97903116.26 | 45795.49 | 97857320.76 | 0.108158E+09 | 0.116453E+09 |
October | 75155151.09 | 0.00 | 75155151.09 | 38893439.26 | 0.195668E+09 |
November | 50875873.34 | 0.00 | 50875873.34 | 8215350.98 | 0.307381E+09 |
December | 34101217.39 | 0.00 | 34101217.39 | 2668.00 | 0.464513E+09 |
Annual Sum or Average | 0.115799E+10 | 27986351.04 | 0.113000E+10 | 0.104104E+10 | 0.271022E+10 |
Minimum of Months | 34101217.39 | 0.00 | 34101217.39 | 2668.00 | 52421840.68 |
Maximum of Months | 0.160368E+09 | 12599649.66 | 0.147768E+09 | 0.225399E+09 | 0.525706E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105807E+10 | 0.733045E+09 | 0.325026E+09 | 0.107092E+10 | 0.140856E+10 |
February | 0.101965E+10 | 0.696446E+09 | 0.323201E+09 | 0.108561E+10 | 0.101903E+10 |
March | 0.946534E+09 | 0.492288E+09 | 0.454246E+09 | 0.107314E+10 | 0.803714E+09 |
April | 0.794807E+09 | 0.349296E+09 | 0.445511E+09 | 0.103154E+10 | 0.571355E+09 |
May | 0.696598E+09 | 0.174558E+09 | 0.522040E+09 | 0.970747E+09 | 0.351696E+09 |
June | 0.643516E+09 | 0.107654E+09 | 0.535862E+09 | 0.100315E+10 | 0.216389E+09 |
July | 0.703274E+09 | 0.152653E+09 | 0.550620E+09 | 0.115316E+10 | 0.183513E+09 |
August | 0.783501E+09 | 0.251617E+09 | 0.531884E+09 | 0.128682E+10 | 0.226481E+09 |
September | 0.929007E+09 | 0.468883E+09 | 0.460124E+09 | 0.140953E+10 | 0.377372E+09 |
October | 0.106667E+10 | 0.675446E+09 | 0.391222E+09 | 0.139074E+10 | 0.595232E+09 |
November | 0.782189E+09 | 0.495473E+09 | 0.286716E+09 | 0.849123E+09 | 0.876021E+09 |
December | 0.869431E+09 | 0.664689E+09 | 0.204743E+09 | 0.947540E+09 | 0.130721E+10 |
Annual Sum or Average | 0.102932E+11 | 0.526205E+10 | 0.503119E+10 | 0.132720E+11 | 0.793657E+10 |
Minimum of Months | 0.643516E+09 | 0.107654E+09 | 0.204743E+09 | 0.849123E+09 | 0.183513E+09 |
Maximum of Months | 0.106667E+10 | 0.733045E+09 | 0.550620E+09 | 0.140953E+10 | 0.140856E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 554.90 | 665.35 | 535.18 | 370.78 | 164.40 | 0.00 | 0.00 |
February | 620.11 | 534.83 | 571.01 | 390.01 | 180.99 | 0.00 | 0.00 |
March | 553.17 | 378.05 | 478.77 | 249.00 | 229.76 | 0.00 | 0.00 |
April | 546.86 | 273.38 | 415.42 | 182.57 | 232.85 | 0.00 | 0.00 |
May | 508.61 | 154.85 | 352.34 | 88.29 | 264.05 | 0.00 | 0.00 |
June | 535.03 | 100.37 | 336.34 | 56.27 | 280.08 | 0.00 | 0.00 |
July | 590.15 | 86.45 | 355.72 | 77.21 | 278.51 | 0.00 | 0.00 |
August | 658.78 | 105.72 | 396.30 | 127.27 | 269.03 | 0.00 | 0.00 |
September | 743.89 | 181.96 | 485.56 | 245.07 | 240.49 | 0.00 | 0.00 |
October | 709.20 | 282.96 | 539.53 | 341.65 | 197.88 | 0.00 | 0.00 |
November | 452.76 | 424.32 | 408.83 | 258.97 | 149.86 | 0.00 | 0.00 |
December | 485.30 | 617.59 | 439.77 | 336.21 | 103.56 | 0.00 | 0.00 |
Annual Sum or Average | 579.68 | 316.15 | 442.19 | 226.05 | 216.13 | 0.00 | 0.00 |
Minimum of Months | 452.76 | 86.45 | 336.34 | 56.27 | 103.56 | 0.00 | 0.00 |
Maximum of Months | 743.89 | 665.35 | 571.01 | 390.01 | 280.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1557.65 | 1861.74 | 1507.04 | 1044.10 | 462.94 | 0.00 | 0.00 |
February | 1742.24 | 1498.42 | 1607.91 | 1098.25 | 509.66 | 0.00 | 0.00 |
March | 1557.08 | 1058.21 | 1348.17 | 701.18 | 646.99 | 0.00 | 0.00 |
April | 1549.74 | 758.34 | 1169.80 | 514.10 | 655.70 | 0.00 | 0.00 |
May | 1459.90 | 413.82 | 992.18 | 248.63 | 743.55 | 0.00 | 0.00 |
June | 1554.91 | 250.83 | 947.12 | 158.45 | 788.68 | 0.00 | 0.00 |
July | 1719.72 | 202.38 | 1001.68 | 217.43 | 784.26 | 0.00 | 0.00 |
August | 1904.91 | 255.68 | 1115.96 | 358.38 | 757.57 | 0.00 | 0.00 |
September | 2117.58 | 482.49 | 1367.31 | 690.10 | 677.21 | 0.00 | 0.00 |
October | 2002.20 | 788.54 | 1519.28 | 962.06 | 557.22 | 0.00 | 0.00 |
November | 1271.25 | 1190.56 | 1151.23 | 729.24 | 421.99 | 0.00 | 0.00 |
December | 1364.89 | 1729.15 | 1238.35 | 946.73 | 291.62 | 0.00 | 0.00 |
Annual Sum or Average | 1649.71 | 871.28 | 1245.17 | 636.55 | 608.62 | 0.00 | 0.00 |
Minimum of Months | 1271.25 | 202.38 | 947.12 | 158.45 | 291.62 | 0.00 | 0.00 |
Maximum of Months | 2117.58 | 1861.74 | 1607.91 | 1098.25 | 788.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2035.03 | 2516.53 | 1957.73 | 1356.34 | 601.39 | 0.00 | 0.00 |
February | 2279.08 | 2031.88 | 2088.77 | 1426.69 | 662.08 | 0.00 | 0.00 |
March | 2036.57 | 1456.64 | 1751.35 | 910.87 | 840.48 | 0.00 | 0.00 |
April | 2027.52 | 1058.19 | 1519.63 | 667.84 | 851.79 | 0.00 | 0.00 |
May | 1893.41 | 595.24 | 1288.89 | 322.98 | 965.91 | 0.00 | 0.00 |
June | 2014.57 | 372.16 | 1230.37 | 205.83 | 1024.54 | 0.00 | 0.00 |
July | 2229.91 | 304.48 | 1301.24 | 282.45 | 1018.79 | 0.00 | 0.00 |
August | 2477.01 | 377.45 | 1449.69 | 465.56 | 984.13 | 0.00 | 0.00 |
September | 2765.28 | 686.52 | 1776.22 | 896.49 | 879.73 | 0.00 | 0.00 |
October | 2615.27 | 1098.88 | 1973.63 | 1249.77 | 723.87 | 0.00 | 0.00 |
November | 1657.40 | 1638.54 | 1495.51 | 947.32 | 548.19 | 0.00 | 0.00 |
December | 1784.42 | 2350.50 | 1608.69 | 1229.86 | 378.83 | 0.00 | 0.00 |
Annual Sum or Average | 2150.62 | 1203.41 | 1617.55 | 826.92 | 790.63 | 0.00 | 0.00 |
Minimum of Months | 1657.40 | 304.48 | 1230.37 | 205.83 | 378.83 | 0.00 | 0.00 |
Maximum of Months | 2765.28 | 2516.53 | 2088.77 | 1426.69 | 1024.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.36 | 396.30 | 171.11 | 99.47 | 71.65 | 0.00 | 0.00 |
February | 177.66 | 317.24 | 209.01 | 124.34 | 84.67 | 0.00 | 0.00 |
March | 207.26 | 218.53 | 209.75 | 92.16 | 117.60 | 0.00 | 0.00 |
April | 312.51 | 151.21 | 251.34 | 120.42 | 130.92 | 0.00 | 0.00 |
May | 331.74 | 81.50 | 238.88 | 85.71 | 153.17 | 0.00 | 0.00 |
June | 411.08 | 47.30 | 264.78 | 97.60 | 167.18 | 0.00 | 0.00 |
July | 454.99 | 36.92 | 283.48 | 117.22 | 166.26 | 0.00 | 0.00 |
August | 424.95 | 46.89 | 264.52 | 111.14 | 153.39 | 0.00 | 0.00 |
September | 364.13 | 92.59 | 247.01 | 120.59 | 126.41 | 0.00 | 0.00 |
October | 255.45 | 160.30 | 211.78 | 114.52 | 97.25 | 0.00 | 0.00 |
November | 127.11 | 250.40 | 143.09 | 74.05 | 69.04 | 0.00 | 0.00 |
December | 111.39 | 365.93 | 134.38 | 88.49 | 45.90 | 0.00 | 0.00 |
Annual Sum or Average | 275.45 | 179.79 | 219.10 | 103.65 | 115.45 | 0.00 | 0.00 |
Minimum of Months | 111.39 | 36.92 | 134.38 | 74.05 | 45.90 | 0.00 | 0.00 |
Maximum of Months | 454.99 | 396.30 | 283.48 | 124.34 | 167.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.19 | 437.76 | 81.85 | 26.16 | 55.69 | 0.00 | 0.00 |
February | 66.76 | 346.79 | 117.09 | 47.23 | 69.86 | 0.00 | 0.00 |
March | 113.96 | 224.54 | 146.54 | 42.93 | 103.61 | 0.00 | 0.00 |
April | 231.33 | 151.06 | 205.54 | 84.51 | 121.03 | 0.00 | 0.00 |
May | 282.60 | 80.35 | 216.20 | 69.65 | 146.55 | 0.00 | 0.00 |
June | 378.94 | 48.02 | 252.88 | 90.77 | 162.12 | 0.00 | 0.00 |
July | 409.61 | 39.72 | 264.42 | 104.80 | 159.62 | 0.00 | 0.00 |
August | 354.67 | 49.71 | 229.50 | 86.60 | 142.89 | 0.00 | 0.00 |
September | 255.75 | 94.62 | 184.34 | 72.16 | 112.18 | 0.00 | 0.00 |
October | 133.36 | 163.60 | 129.87 | 46.98 | 82.89 | 0.00 | 0.00 |
November | 47.43 | 265.57 | 79.58 | 22.84 | 56.73 | 0.00 | 0.00 |
December | 25.57 | 392.72 | 58.67 | 22.01 | 36.66 | 0.00 | 0.00 |
Annual Sum or Average | 194.60 | 190.49 | 164.07 | 59.74 | 104.34 | 0.00 | 0.00 |
Minimum of Months | 25.57 | 39.72 | 58.67 | 22.01 | 36.66 | 0.00 | 0.00 |
Maximum of Months | 409.61 | 437.76 | 264.42 | 104.80 | 162.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 90.62 | 94.70 | 84.64 | 58.64 | 26.00 | 0.00 | 0.00 |
February | 99.38 | 82.06 | 90.30 | 61.68 | 28.62 | 0.00 | 0.00 |
March | 85.58 | 62.91 | 75.71 | 39.38 | 36.34 | 0.00 | 0.00 |
April | 81.16 | 56.61 | 65.70 | 28.87 | 36.82 | 0.00 | 0.00 |
May | 71.68 | 35.82 | 55.72 | 13.96 | 41.76 | 0.00 | 0.00 |
June | 77.05 | 24.04 | 53.19 | 8.90 | 44.29 | 0.00 | 0.00 |
July | 86.45 | 20.28 | 56.25 | 12.21 | 44.04 | 0.00 | 0.00 |
August | 97.47 | 24.30 | 62.67 | 20.13 | 42.55 | 0.00 | 0.00 |
September | 111.10 | 39.83 | 76.79 | 38.76 | 38.03 | 0.00 | 0.00 |
October | 104.31 | 60.24 | 85.32 | 54.03 | 31.29 | 0.00 | 0.00 |
November | 67.77 | 76.35 | 64.65 | 40.95 | 23.70 | 0.00 | 0.00 |
December | 78.58 | 88.86 | 69.55 | 53.17 | 16.38 | 0.00 | 0.00 |
Annual Sum or Average | 87.54 | 55.35 | 69.93 | 35.75 | 34.18 | 0.00 | 0.00 |
Minimum of Months | 67.77 | 20.28 | 53.19 | 8.90 | 16.38 | 0.00 | 0.00 |
Maximum of Months | 111.10 | 94.70 | 90.30 | 61.68 | 44.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.04 | 134.42 | 13.24 | 0.00 | 13.24 | 0.00 | 0.00 |
February | 0.90 | 108.05 | 16.79 | 0.00 | 16.79 | 0.00 | 0.00 |
March | 9.50 | 67.96 | 25.16 | 0.00 | 25.16 | 0.00 | 0.00 |
April | 20.89 | 43.79 | 29.08 | 0.15 | 28.92 | 0.00 | 0.00 |
May | 43.84 | 21.60 | 37.59 | 1.12 | 36.48 | 0.00 | 0.00 |
June | 65.81 | 12.59 | 43.69 | 3.43 | 40.26 | 0.00 | 0.00 |
July | 64.93 | 9.90 | 41.02 | 2.28 | 38.75 | 0.00 | 0.00 |
August | 54.19 | 12.67 | 34.67 | 0.51 | 34.16 | 0.00 | 0.00 |
September | 33.15 | 26.45 | 26.67 | 0.01 | 26.66 | 0.00 | 0.00 |
October | 11.73 | 48.22 | 19.81 | 0.00 | 19.81 | 0.00 | 0.00 |
November | 2.71 | 80.43 | 13.86 | 0.00 | 13.86 | 0.00 | 0.00 |
December | 0.01 | 118.71 | 8.99 | 0.00 | 8.99 | 0.00 | 0.00 |
Annual Sum or Average | 25.79 | 56.83 | 25.93 | 0.63 | 25.30 | 0.00 | 0.00 |
Minimum of Months | 0.01 | 9.90 | 8.99 | 0.00 | 8.99 | 0.00 | 0.00 |
Maximum of Months | 65.81 | 134.42 | 43.69 | 3.43 | 40.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.47 | 394.63 | 170.90 | 99.43 | 71.47 | 0.00 | 0.00 |
February | 162.69 | 313.49 | 200.51 | 115.50 | 85.01 | 0.00 | 0.00 |
March | 211.50 | 215.44 | 214.31 | 96.85 | 117.46 | 0.00 | 0.00 |
April | 274.14 | 148.25 | 228.84 | 100.58 | 128.26 | 0.00 | 0.00 |
May | 351.39 | 77.30 | 255.00 | 99.19 | 155.81 | 0.00 | 0.00 |
June | 417.31 | 44.92 | 269.90 | 100.32 | 169.58 | 0.00 | 0.00 |
July | 440.79 | 34.74 | 276.45 | 111.24 | 165.21 | 0.00 | 0.00 |
August | 402.51 | 44.09 | 252.10 | 100.76 | 151.34 | 0.00 | 0.00 |
September | 369.67 | 90.82 | 251.54 | 122.76 | 128.79 | 0.00 | 0.00 |
October | 241.37 | 157.59 | 204.34 | 108.10 | 96.25 | 0.00 | 0.00 |
November | 117.77 | 247.74 | 138.17 | 69.45 | 68.73 | 0.00 | 0.00 |
December | 103.63 | 362.48 | 130.72 | 84.71 | 46.02 | 0.00 | 0.00 |
Annual Sum or Average | 268.42 | 177.00 | 216.13 | 100.65 | 115.48 | 0.00 | 0.00 |
Minimum of Months | 103.63 | 34.74 | 130.72 | 69.45 | 46.02 | 0.00 | 0.00 |
Maximum of Months | 440.79 | 394.63 | 276.45 | 122.76 | 169.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.96 | 430.73 | 81.63 | 26.12 | 55.51 | 0.00 | 0.00 |
February | 49.83 | 341.19 | 108.59 | 38.39 | 70.20 | 0.00 | 0.00 |
March | 116.31 | 219.44 | 151.10 | 47.62 | 103.47 | 0.00 | 0.00 |
April | 193.00 | 147.58 | 183.05 | 64.68 | 118.37 | 0.00 | 0.00 |
May | 304.05 | 77.20 | 232.32 | 83.13 | 149.19 | 0.00 | 0.00 |
June | 386.44 | 46.48 | 258.00 | 93.48 | 164.52 | 0.00 | 0.00 |
July | 395.66 | 37.67 | 257.39 | 98.82 | 158.57 | 0.00 | 0.00 |
August | 332.96 | 46.89 | 217.07 | 76.23 | 140.84 | 0.00 | 0.00 |
September | 260.72 | 92.02 | 188.87 | 74.32 | 114.56 | 0.00 | 0.00 |
October | 117.38 | 158.36 | 122.43 | 40.55 | 81.89 | 0.00 | 0.00 |
November | 35.50 | 260.27 | 74.66 | 18.24 | 56.42 | 0.00 | 0.00 |
December | 16.01 | 387.80 | 55.01 | 18.23 | 36.78 | 0.00 | 0.00 |
Annual Sum or Average | 186.57 | 186.42 | 161.11 | 56.74 | 104.37 | 0.00 | 0.00 |
Minimum of Months | 16.01 | 37.67 | 55.01 | 18.23 | 36.78 | 0.00 | 0.00 |
Maximum of Months | 395.66 | 430.73 | 258.00 | 98.82 | 164.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 147.09 | 501.83 | 212.06 | 127.05 | 85.01 | 0.00 | 0.00 |
February | 179.89 | 402.45 | 232.02 | 133.64 | 98.38 | 0.00 | 0.00 |
March | 202.39 | 280.26 | 218.55 | 85.32 | 133.23 | 0.00 | 0.00 |
April | 234.06 | 193.63 | 205.33 | 62.89 | 142.45 | 0.00 | 0.00 |
May | 271.14 | 101.26 | 202.17 | 32.67 | 169.50 | 0.00 | 0.00 |
June | 327.67 | 62.16 | 209.89 | 26.72 | 183.18 | 0.00 | 0.00 |
July | 344.79 | 51.72 | 210.75 | 31.39 | 179.37 | 0.00 | 0.00 |
August | 345.12 | 64.79 | 210.90 | 44.70 | 166.19 | 0.00 | 0.00 |
September | 328.45 | 123.58 | 224.16 | 84.00 | 140.16 | 0.00 | 0.00 |
October | 267.07 | 200.08 | 227.79 | 117.07 | 110.73 | 0.00 | 0.00 |
November | 145.06 | 316.75 | 170.11 | 88.74 | 81.37 | 0.00 | 0.00 |
December | 137.91 | 461.94 | 170.16 | 115.20 | 54.96 | 0.00 | 0.00 |
Annual Sum or Average | 244.59 | 229.23 | 207.69 | 78.81 | 128.87 | 0.00 | 0.00 |
Minimum of Months | 137.91 | 51.72 | 170.11 | 26.72 | 54.96 | 0.00 | 0.00 |
Maximum of Months | 345.12 | 501.83 | 232.02 | 133.64 | 183.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.12 | 395.06 | 171.11 | 99.47 | 71.65 | 0.00 | 0.00 |
February | 177.26 | 315.73 | 209.01 | 124.34 | 84.67 | 0.00 | 0.00 |
March | 207.10 | 216.98 | 209.75 | 92.16 | 117.60 | 0.00 | 0.00 |
April | 310.95 | 149.78 | 251.34 | 120.42 | 130.92 | 0.00 | 0.00 |
May | 329.42 | 80.74 | 238.88 | 85.71 | 153.17 | 0.00 | 0.00 |
June | 408.85 | 46.43 | 264.78 | 97.60 | 167.18 | 0.00 | 0.00 |
July | 452.62 | 36.01 | 283.48 | 117.22 | 166.26 | 0.00 | 0.00 |
August | 422.69 | 45.98 | 264.52 | 111.14 | 153.39 | 0.00 | 0.00 |
September | 362.98 | 90.92 | 247.01 | 120.59 | 126.41 | 0.00 | 0.00 |
October | 254.96 | 158.59 | 211.78 | 114.52 | 97.25 | 0.00 | 0.00 |
November | 127.40 | 248.35 | 143.09 | 74.05 | 69.04 | 0.00 | 0.00 |
December | 111.69 | 364.11 | 134.38 | 88.49 | 45.90 | 0.00 | 0.00 |
Annual Sum or Average | 274.40 | 178.43 | 219.10 | 103.65 | 115.45 | 0.00 | 0.00 |
Minimum of Months | 111.69 | 36.01 | 134.38 | 74.05 | 45.90 | 0.00 | 0.00 |
Maximum of Months | 452.62 | 395.06 | 283.48 | 124.34 | 167.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.19 | 436.72 | 81.85 | 26.16 | 55.69 | 0.00 | 0.00 |
February | 66.79 | 345.42 | 117.09 | 47.23 | 69.86 | 0.00 | 0.00 |
March | 114.22 | 222.90 | 146.54 | 42.93 | 103.61 | 0.00 | 0.00 |
April | 230.21 | 149.75 | 205.54 | 84.51 | 121.03 | 0.00 | 0.00 |
May | 279.97 | 80.20 | 216.20 | 69.65 | 146.55 | 0.00 | 0.00 |
June | 376.23 | 48.04 | 252.88 | 90.77 | 162.12 | 0.00 | 0.00 |
July | 406.97 | 39.85 | 264.42 | 104.80 | 159.62 | 0.00 | 0.00 |
August | 352.42 | 49.74 | 229.50 | 86.60 | 142.89 | 0.00 | 0.00 |
September | 255.07 | 93.28 | 184.34 | 72.16 | 112.18 | 0.00 | 0.00 |
October | 133.71 | 161.51 | 129.87 | 46.98 | 82.89 | 0.00 | 0.00 |
November | 47.96 | 263.30 | 79.58 | 22.84 | 56.73 | 0.00 | 0.00 |
December | 25.75 | 390.94 | 58.67 | 22.01 | 36.66 | 0.00 | 0.00 |
Annual Sum or Average | 193.70 | 189.43 | 164.07 | 59.74 | 104.34 | 0.00 | 0.00 |
Minimum of Months | 25.75 | 39.85 | 58.67 | 22.01 | 36.66 | 0.00 | 0.00 |
Maximum of Months | 406.97 | 436.72 | 264.42 | 104.80 | 162.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 156.44 | 201.22 | 155.19 | 107.52 | 47.67 | 0.00 | 0.00 |
February | 175.18 | 161.79 | 165.58 | 113.09 | 52.48 | 0.00 | 0.00 |
March | 156.43 | 114.06 | 138.83 | 72.20 | 66.62 | 0.00 | 0.00 |
April | 157.25 | 79.70 | 120.46 | 52.94 | 67.52 | 0.00 | 0.00 |
May | 147.27 | 42.10 | 102.17 | 25.60 | 76.57 | 0.00 | 0.00 |
June | 159.60 | 23.42 | 97.53 | 16.32 | 81.21 | 0.00 | 0.00 |
July | 177.05 | 17.52 | 103.15 | 22.39 | 80.76 | 0.00 | 0.00 |
August | 195.44 | 22.87 | 114.92 | 36.90 | 78.01 | 0.00 | 0.00 |
September | 217.17 | 47.26 | 140.80 | 71.06 | 69.74 | 0.00 | 0.00 |
October | 203.06 | 82.65 | 156.45 | 99.07 | 57.38 | 0.00 | 0.00 |
November | 128.38 | 127.63 | 118.55 | 75.09 | 43.45 | 0.00 | 0.00 |
December | 137.68 | 186.10 | 127.52 | 97.49 | 30.03 | 0.00 | 0.00 |
Annual Sum or Average | 167.54 | 91.87 | 128.22 | 65.55 | 62.67 | 0.00 | 0.00 |
Minimum of Months | 128.38 | 17.52 | 97.53 | 16.32 | 30.03 | 0.00 | 0.00 |
Maximum of Months | 217.17 | 201.22 | 165.58 | 113.09 | 81.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.30 | 1178.89 | 115.83 | 0.00 | 115.83 | 0.00 | 0.00 |
February | 7.19 | 947.63 | 146.85 | 0.00 | 146.85 | 0.00 | 0.00 |
March | 81.85 | 599.10 | 220.11 | 0.00 | 220.11 | 0.00 | 0.00 |
April | 183.24 | 390.94 | 254.38 | 1.33 | 253.05 | 0.00 | 0.00 |
May | 385.89 | 199.17 | 328.90 | 9.77 | 319.13 | 0.00 | 0.00 |
June | 580.50 | 119.58 | 382.21 | 30.03 | 352.18 | 0.00 | 0.00 |
July | 575.10 | 93.75 | 358.87 | 19.91 | 338.96 | 0.00 | 0.00 |
August | 480.41 | 119.01 | 303.29 | 4.42 | 298.87 | 0.00 | 0.00 |
September | 294.43 | 240.72 | 233.34 | 0.11 | 233.23 | 0.00 | 0.00 |
October | 103.17 | 427.03 | 173.34 | 0.00 | 173.34 | 0.00 | 0.00 |
November | 23.55 | 707.66 | 121.25 | 0.00 | 121.25 | 0.00 | 0.00 |
December | 0.04 | 1042.55 | 78.65 | 0.00 | 78.65 | 0.00 | 0.00 |
Annual Sum or Average | 227.62 | 503.41 | 226.84 | 5.48 | 221.36 | 0.00 | 0.00 |
Minimum of Months | 0.04 | 93.75 | 78.65 | 0.00 | 78.65 | 0.00 | 0.00 |
Maximum of Months | 580.50 | 1178.89 | 382.21 | 30.03 | 352.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.22 | 1200.45 | 115.83 | 0.00 | 115.83 | 0.00 | 0.00 |
February | 6.14 | 969.03 | 146.85 | 0.00 | 146.85 | 0.00 | 0.00 |
March | 76.73 | 619.40 | 220.11 | 0.00 | 220.11 | 0.00 | 0.00 |
April | 175.87 | 407.69 | 254.38 | 1.33 | 253.05 | 0.00 | 0.00 |
May | 375.43 | 207.72 | 328.90 | 9.77 | 319.13 | 0.00 | 0.00 |
June | 569.96 | 125.92 | 382.21 | 30.03 | 352.18 | 0.00 | 0.00 |
July | 564.97 | 99.54 | 358.87 | 19.91 | 338.96 | 0.00 | 0.00 |
August | 470.97 | 125.51 | 303.29 | 4.42 | 298.87 | 0.00 | 0.00 |
September | 286.59 | 251.25 | 233.34 | 0.11 | 233.23 | 0.00 | 0.00 |
October | 96.21 | 445.43 | 173.34 | 0.00 | 173.34 | 0.00 | 0.00 |
November | 21.15 | 729.54 | 121.25 | 0.00 | 121.25 | 0.00 | 0.00 |
December | 0.02 | 1065.00 | 78.65 | 0.00 | 78.65 | 0.00 | 0.00 |
Annual Sum or Average | 221.64 | 518.41 | 226.84 | 5.48 | 221.36 | 0.00 | 0.00 |
Minimum of Months | 0.02 | 99.54 | 78.65 | 0.00 | 78.65 | 0.00 | 0.00 |
Maximum of Months | 569.96 | 1200.45 | 382.21 | 30.03 | 352.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 178.52 | 687.39 | 252.53 | 125.55 | 126.98 | 0.00 | 0.00 |
February | 276.45 | 535.75 | 309.08 | 153.88 | 155.20 | 0.00 | 0.00 |
March | 453.64 | 362.68 | 365.39 | 144.47 | 220.92 | 0.00 | 0.00 |
April | 633.57 | 240.45 | 411.87 | 165.25 | 246.61 | 0.00 | 0.00 |
May | 890.82 | 132.78 | 487.30 | 182.31 | 304.98 | 0.00 | 0.00 |
June | 1065.93 | 81.19 | 527.87 | 193.79 | 334.08 | 0.00 | 0.00 |
July | 1111.08 | 63.15 | 533.81 | 210.05 | 323.76 | 0.00 | 0.00 |
August | 996.97 | 76.30 | 469.15 | 176.98 | 292.17 | 0.00 | 0.00 |
September | 849.68 | 143.64 | 440.40 | 197.07 | 243.33 | 0.00 | 0.00 |
October | 512.19 | 248.71 | 326.76 | 148.64 | 178.13 | 0.00 | 0.00 |
November | 236.88 | 401.40 | 212.83 | 87.69 | 125.14 | 0.00 | 0.00 |
December | 152.08 | 606.04 | 185.73 | 102.94 | 82.80 | 0.00 | 0.00 |
Annual Sum or Average | 615.00 | 297.23 | 377.22 | 157.37 | 219.84 | 0.00 | 0.00 |
Minimum of Months | 152.08 | 63.15 | 185.73 | 87.69 | 82.80 | 0.00 | 0.00 |
Maximum of Months | 1111.08 | 687.39 | 533.81 | 210.05 | 334.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 341.20 | 882.87 | 434.75 | 273.69 | 161.06 | 0.00 | 0.00 |
February | 403.40 | 708.59 | 471.82 | 287.88 | 183.94 | 0.00 | 0.00 |
March | 416.03 | 501.24 | 428.85 | 183.80 | 245.05 | 0.00 | 0.00 |
April | 453.18 | 360.91 | 393.84 | 135.22 | 258.62 | 0.00 | 0.00 |
May | 477.83 | 206.70 | 372.83 | 68.52 | 304.31 | 0.00 | 0.00 |
June | 564.84 | 129.88 | 379.29 | 51.83 | 327.46 | 0.00 | 0.00 |
July | 606.69 | 107.90 | 385.59 | 63.82 | 321.77 | 0.00 | 0.00 |
August | 626.20 | 135.27 | 396.50 | 95.46 | 301.04 | 0.00 | 0.00 |
September | 631.35 | 239.92 | 438.40 | 180.93 | 257.47 | 0.00 | 0.00 |
October | 543.00 | 369.95 | 457.67 | 252.18 | 205.49 | 0.00 | 0.00 |
November | 311.46 | 566.27 | 343.34 | 191.15 | 152.18 | 0.00 | 0.00 |
December | 313.63 | 815.19 | 351.57 | 248.17 | 103.40 | 0.00 | 0.00 |
Annual Sum or Average | 474.47 | 417.38 | 404.16 | 168.74 | 235.42 | 0.00 | 0.00 |
Minimum of Months | 311.46 | 107.90 | 343.34 | 51.83 | 103.40 | 0.00 | 0.00 |
Maximum of Months | 631.35 | 882.87 | 471.82 | 287.88 | 327.46 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148625E+10 | 0.178208E+10 | 0.143343E+10 | 0.993101E+09 | 0.440330E+09 | 0.00 | 0.00 |
February | 0.150017E+10 | 0.129386E+10 | 0.138138E+10 | 0.943518E+09 | 0.437857E+09 | 0.00 | 0.00 |
March | 0.148161E+10 | 0.101256E+10 | 0.128232E+10 | 0.666933E+09 | 0.615391E+09 | 0.00 | 0.00 |
April | 0.141746E+10 | 0.708600E+09 | 0.107677E+10 | 0.473213E+09 | 0.603555E+09 | 0.00 | 0.00 |
May | 0.136226E+10 | 0.414761E+09 | 0.943718E+09 | 0.236485E+09 | 0.707234E+09 | 0.00 | 0.00 |
June | 0.138680E+10 | 0.260150E+09 | 0.871803E+09 | 0.145845E+09 | 0.725958E+09 | 0.00 | 0.00 |
July | 0.158065E+10 | 0.231538E+09 | 0.952760E+09 | 0.206809E+09 | 0.745951E+09 | 0.00 | 0.00 |
August | 0.176447E+10 | 0.283169E+09 | 0.106145E+10 | 0.340881E+09 | 0.720570E+09 | 0.00 | 0.00 |
September | 0.192816E+10 | 0.471642E+09 | 0.125858E+10 | 0.635225E+09 | 0.623353E+09 | 0.00 | 0.00 |
October | 0.189952E+10 | 0.757872E+09 | 0.144508E+10 | 0.915069E+09 | 0.530009E+09 | 0.00 | 0.00 |
November | 0.117356E+10 | 0.109985E+10 | 0.105968E+10 | 0.671248E+09 | 0.388430E+09 | 0.00 | 0.00 |
December | 0.129982E+10 | 0.165414E+10 | 0.117787E+10 | 0.900495E+09 | 0.277376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182807E+11 | 0.997022E+10 | 0.139448E+11 | 0.712882E+10 | 0.681601E+10 | 0.00 | 0.00 |
Minimum of Months | 0.117356E+10 | 0.231538E+09 | 0.871803E+09 | 0.145845E+09 | 0.277376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192816E+10 | 0.178208E+10 | 0.144508E+10 | 0.993101E+09 | 0.745951E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.417201E+10 | 0.498648E+10 | 0.403645E+10 | 0.279651E+10 | 0.123994E+10 | 0.00 | 0.00 |
February | 0.421483E+10 | 0.362498E+10 | 0.388986E+10 | 0.265689E+10 | 0.123298E+10 | 0.00 | 0.00 |
March | 0.417048E+10 | 0.283431E+10 | 0.361094E+10 | 0.187804E+10 | 0.173290E+10 | 0.00 | 0.00 |
April | 0.401693E+10 | 0.196563E+10 | 0.303211E+10 | 0.133254E+10 | 0.169957E+10 | 0.00 | 0.00 |
May | 0.391019E+10 | 0.110839E+10 | 0.265745E+10 | 0.665925E+09 | 0.199152E+10 | 0.00 | 0.00 |
June | 0.403033E+10 | 0.650150E+09 | 0.245494E+10 | 0.410691E+09 | 0.204425E+10 | 0.00 | 0.00 |
July | 0.460611E+10 | 0.542060E+09 | 0.268291E+10 | 0.582360E+09 | 0.210055E+10 | 0.00 | 0.00 |
August | 0.510210E+10 | 0.684809E+09 | 0.298897E+10 | 0.959898E+09 | 0.202908E+10 | 0.00 | 0.00 |
September | 0.548878E+10 | 0.125062E+10 | 0.354407E+10 | 0.178875E+10 | 0.175532E+10 | 0.00 | 0.00 |
October | 0.536268E+10 | 0.211203E+10 | 0.406924E+10 | 0.257677E+10 | 0.149247E+10 | 0.00 | 0.00 |
November | 0.329507E+10 | 0.308594E+10 | 0.298398E+10 | 0.189019E+10 | 0.109379E+10 | 0.00 | 0.00 |
December | 0.365571E+10 | 0.463134E+10 | 0.331681E+10 | 0.253573E+10 | 0.781074E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.520252E+11 | 0.274767E+11 | 0.392677E+11 | 0.200743E+11 | 0.191934E+11 | 0.00 | 0.00 |
Minimum of Months | 0.329507E+10 | 0.542060E+09 | 0.245494E+10 | 0.410691E+09 | 0.781074E+09 | 0.00 | 0.00 |
Maximum of Months | 0.548878E+10 | 0.498648E+10 | 0.406924E+10 | 0.279651E+10 | 0.210055E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.545062E+10 | 0.674026E+10 | 0.524358E+10 | 0.363282E+10 | 0.161075E+10 | 0.00 | 0.00 |
February | 0.551355E+10 | 0.491553E+10 | 0.505315E+10 | 0.345145E+10 | 0.160171E+10 | 0.00 | 0.00 |
March | 0.545476E+10 | 0.390146E+10 | 0.469082E+10 | 0.243968E+10 | 0.225114E+10 | 0.00 | 0.00 |
April | 0.525532E+10 | 0.274283E+10 | 0.393888E+10 | 0.173104E+10 | 0.220784E+10 | 0.00 | 0.00 |
May | 0.507130E+10 | 0.159428E+10 | 0.345218E+10 | 0.865074E+09 | 0.258710E+10 | 0.00 | 0.00 |
June | 0.522176E+10 | 0.964639E+09 | 0.318911E+10 | 0.533511E+09 | 0.265560E+10 | 0.00 | 0.00 |
July | 0.597258E+10 | 0.815516E+09 | 0.348525E+10 | 0.756519E+09 | 0.272873E+10 | 0.00 | 0.00 |
August | 0.663444E+10 | 0.101096E+10 | 0.388285E+10 | 0.124696E+10 | 0.263589E+10 | 0.00 | 0.00 |
September | 0.716761E+10 | 0.177946E+10 | 0.460395E+10 | 0.232369E+10 | 0.228026E+10 | 0.00 | 0.00 |
October | 0.700474E+10 | 0.294325E+10 | 0.528618E+10 | 0.334738E+10 | 0.193880E+10 | 0.00 | 0.00 |
November | 0.429598E+10 | 0.424708E+10 | 0.387637E+10 | 0.245547E+10 | 0.142090E+10 | 0.00 | 0.00 |
December | 0.477940E+10 | 0.629558E+10 | 0.430872E+10 | 0.329406E+10 | 0.101466E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.678221E+11 | 0.379508E+11 | 0.510110E+11 | 0.260777E+11 | 0.249334E+11 | 0.00 | 0.00 |
Minimum of Months | 0.429598E+10 | 0.815516E+09 | 0.318911E+10 | 0.533511E+09 | 0.101466E+10 | 0.00 | 0.00 |
Maximum of Months | 0.716761E+10 | 0.674026E+10 | 0.528618E+10 | 0.363282E+10 | 0.272873E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325060E+09 | 0.106145E+10 | 0.458314E+09 | 0.266410E+09 | 0.191904E+09 | 0.00 | 0.00 |
February | 0.429789E+09 | 0.767472E+09 | 0.505637E+09 | 0.300812E+09 | 0.204825E+09 | 0.00 | 0.00 |
March | 0.555125E+09 | 0.585311E+09 | 0.561806E+09 | 0.246836E+09 | 0.314971E+09 | 0.00 | 0.00 |
April | 0.810024E+09 | 0.391931E+09 | 0.651468E+09 | 0.312120E+09 | 0.339348E+09 | 0.00 | 0.00 |
May | 0.888529E+09 | 0.218277E+09 | 0.639823E+09 | 0.229577E+09 | 0.410246E+09 | 0.00 | 0.00 |
June | 0.106551E+10 | 0.122608E+09 | 0.686314E+09 | 0.252989E+09 | 0.433326E+09 | 0.00 | 0.00 |
July | 0.121864E+10 | 98895430.13 | 0.759279E+09 | 0.313973E+09 | 0.445306E+09 | 0.00 | 0.00 |
August | 0.113817E+10 | 0.125578E+09 | 0.708498E+09 | 0.297669E+09 | 0.410828E+09 | 0.00 | 0.00 |
September | 0.943814E+09 | 0.239982E+09 | 0.640242E+09 | 0.312580E+09 | 0.327661E+09 | 0.00 | 0.00 |
October | 0.684194E+09 | 0.429338E+09 | 0.567231E+09 | 0.306743E+09 | 0.260488E+09 | 0.00 | 0.00 |
November | 0.329471E+09 | 0.649048E+09 | 0.370881E+09 | 0.191926E+09 | 0.178956E+09 | 0.00 | 0.00 |
December | 0.298349E+09 | 0.980097E+09 | 0.359929E+09 | 0.237002E+09 | 0.122927E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.868669E+10 | 0.566999E+10 | 0.690942E+10 | 0.326864E+10 | 0.364079E+10 | 0.00 | 0.00 |
Minimum of Months | 0.298349E+09 | 98895430.13 | 0.359929E+09 | 0.191926E+09 | 0.122927E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121864E+10 | 0.106145E+10 | 0.759279E+09 | 0.313973E+09 | 0.445306E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 72817996.10 | 0.117251E+10 | 0.219221E+09 | 70056597.41 | 0.149164E+09 | 0.00 | 0.00 |
February | 0.161500E+09 | 0.838960E+09 | 0.283268E+09 | 0.114263E+09 | 0.169006E+09 | 0.00 | 0.00 |
March | 0.305229E+09 | 0.601417E+09 | 0.392492E+09 | 0.114972E+09 | 0.277521E+09 | 0.00 | 0.00 |
April | 0.599605E+09 | 0.391550E+09 | 0.532768E+09 | 0.219050E+09 | 0.313717E+09 | 0.00 | 0.00 |
May | 0.756916E+09 | 0.215214E+09 | 0.579082E+09 | 0.186557E+09 | 0.392525E+09 | 0.00 | 0.00 |
June | 0.982206E+09 | 0.124465E+09 | 0.655474E+09 | 0.235272E+09 | 0.420202E+09 | 0.00 | 0.00 |
July | 0.109709E+10 | 0.106395E+09 | 0.708220E+09 | 0.280701E+09 | 0.427519E+09 | 0.00 | 0.00 |
August | 0.949937E+09 | 0.133141E+09 | 0.614683E+09 | 0.231962E+09 | 0.382720E+09 | 0.00 | 0.00 |
September | 0.662895E+09 | 0.245246E+09 | 0.477802E+09 | 0.187026E+09 | 0.290776E+09 | 0.00 | 0.00 |
October | 0.357198E+09 | 0.438188E+09 | 0.347841E+09 | 0.125818E+09 | 0.222023E+09 | 0.00 | 0.00 |
November | 0.122948E+09 | 0.688370E+09 | 0.206265E+09 | 59208257.16 | 0.147057E+09 | 0.00 | 0.00 |
December | 68499355.22 | 0.105185E+10 | 0.157139E+09 | 58958369.16 | 98180531.02 | 0.00 | 0.00 |
Annual Sum or Average | 0.613684E+10 | 0.600731E+10 | 0.517425E+10 | 0.188384E+10 | 0.329041E+10 | 0.00 | 0.00 |
Minimum of Months | 68499355.22 | 0.106395E+09 | 0.157139E+09 | 58958369.16 | 98180531.02 | 0.00 | 0.00 |
Maximum of Months | 0.109709E+10 | 0.117251E+10 | 0.708220E+09 | 0.280701E+09 | 0.427519E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.242721E+09 | 0.253636E+09 | 0.226686E+09 | 0.157051E+09 | 69635175.61 | 0.00 | 0.00 |
February | 0.240420E+09 | 0.198523E+09 | 0.218454E+09 | 0.149210E+09 | 69244188.50 | 0.00 | 0.00 |
March | 0.229207E+09 | 0.168492E+09 | 0.202790E+09 | 0.105470E+09 | 97320046.63 | 0.00 | 0.00 |
April | 0.210359E+09 | 0.146746E+09 | 0.170284E+09 | 74835029.66 | 95448506.50 | 0.00 | 0.00 |
May | 0.191975E+09 | 95936521.24 | 0.149243E+09 | 37398212.82 | 0.111845E+09 | 0.00 | 0.00 |
June | 0.199706E+09 | 62304357.31 | 0.137870E+09 | 23064328.80 | 0.114806E+09 | 0.00 | 0.00 |
July | 0.231559E+09 | 54319826.07 | 0.150673E+09 | 32705235.25 | 0.117968E+09 | 0.00 | 0.00 |
August | 0.261075E+09 | 65096238.76 | 0.167861E+09 | 53907665.37 | 0.113954E+09 | 0.00 | 0.00 |
September | 0.287979E+09 | 0.103246E+09 | 0.199035E+09 | 0.100456E+09 | 98579302.31 | 0.00 | 0.00 |
October | 0.279380E+09 | 0.161353E+09 | 0.228528E+09 | 0.144711E+09 | 83817345.33 | 0.00 | 0.00 |
November | 0.175670E+09 | 0.197897E+09 | 0.167580E+09 | 0.106153E+09 | 61427513.93 | 0.00 | 0.00 |
December | 0.210471E+09 | 0.238015E+09 | 0.186271E+09 | 0.142406E+09 | 43865185.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.276052E+10 | 0.174556E+10 | 0.220528E+10 | 0.112737E+10 | 0.107791E+10 | 0.00 | 0.00 |
Minimum of Months | 0.175670E+09 | 54319826.07 | 0.137870E+09 | 23064328.80 | 43865185.97 | 0.00 | 0.00 |
Maximum of Months | 0.287979E+09 | 0.253636E+09 | 0.228528E+09 | 0.157051E+09 | 0.117968E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 111502.28 | 0.360037E+09 | 35462082.56 | 0.00 | 35462082.56 | 0.00 | 0.00 |
February | 2184865.64 | 0.261390E+09 | 40608143.59 | 0.00 | 40608143.59 | 0.00 | 0.00 |
March | 25445296.77 | 0.182034E+09 | 67388482.56 | 177.35 | 67388305.21 | 0.00 | 0.00 |
April | 54149126.10 | 0.113505E+09 | 75366975.10 | 394381.15 | 74972593.95 | 0.00 | 0.00 |
May | 0.117412E+09 | 57857074.10 | 0.100693E+09 | 2989846.56 | 97703050.50 | 0.00 | 0.00 |
June | 0.170592E+09 | 32643898.61 | 0.113241E+09 | 8896991.73 | 0.104344E+09 | 0.00 | 0.00 |
July | 0.173905E+09 | 26507841.32 | 0.109870E+09 | 6095209.85 | 0.103775E+09 | 0.00 | 0.00 |
August | 0.145133E+09 | 33940706.02 | 92854919.86 | 1353060.34 | 91501859.52 | 0.00 | 0.00 |
September | 85919244.02 | 68565435.64 | 69132336.19 | 32337.57 | 69099998.61 | 0.00 | 0.00 |
October | 31420386.10 | 0.129141E+09 | 53069313.52 | 0.00 | 53069313.52 | 0.00 | 0.00 |
November | 7013934.27 | 0.208466E+09 | 35924984.97 | 0.00 | 35924984.97 | 0.00 | 0.00 |
December | 14193.06 | 0.317961E+09 | 24079895.67 | 0.00 | 24079895.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.813301E+09 | 0.179205E+10 | 0.817690E+09 | 19762004.55 | 0.797928E+09 | 0.00 | 0.00 |
Minimum of Months | 14193.06 | 26507841.32 | 24079895.67 | 0.00 | 24079895.67 | 0.00 | 0.00 |
Maximum of Months | 0.173905E+09 | 0.360037E+09 | 0.113241E+09 | 8896991.73 | 0.104344E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325333E+09 | 0.105699E+10 | 0.457742E+09 | 0.266313E+09 | 0.191430E+09 | 0.00 | 0.00 |
February | 0.393591E+09 | 0.758395E+09 | 0.485065E+09 | 0.279420E+09 | 0.205645E+09 | 0.00 | 0.00 |
March | 0.566490E+09 | 0.577035E+09 | 0.574009E+09 | 0.259413E+09 | 0.314596E+09 | 0.00 | 0.00 |
April | 0.710578E+09 | 0.384259E+09 | 0.593155E+09 | 0.260716E+09 | 0.332439E+09 | 0.00 | 0.00 |
May | 0.941157E+09 | 0.207052E+09 | 0.682992E+09 | 0.265677E+09 | 0.417315E+09 | 0.00 | 0.00 |
June | 0.108166E+10 | 0.116422E+09 | 0.699581E+09 | 0.260027E+09 | 0.439553E+09 | 0.00 | 0.00 |
July | 0.118060E+10 | 93051494.57 | 0.740451E+09 | 0.297953E+09 | 0.442498E+09 | 0.00 | 0.00 |
August | 0.107808E+10 | 0.118097E+09 | 0.675223E+09 | 0.269879E+09 | 0.405344E+09 | 0.00 | 0.00 |
September | 0.958195E+09 | 0.235414E+09 | 0.652002E+09 | 0.318190E+09 | 0.333812E+09 | 0.00 | 0.00 |
October | 0.646479E+09 | 0.422076E+09 | 0.547317E+09 | 0.289524E+09 | 0.257792E+09 | 0.00 | 0.00 |
November | 0.305266E+09 | 0.642144E+09 | 0.358142E+09 | 0.180006E+09 | 0.178136E+09 | 0.00 | 0.00 |
December | 0.277571E+09 | 0.970879E+09 | 0.350133E+09 | 0.226876E+09 | 0.123258E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.846500E+10 | 0.558181E+10 | 0.681581E+10 | 0.317400E+10 | 0.364182E+10 | 0.00 | 0.00 |
Minimum of Months | 0.277571E+09 | 93051494.57 | 0.350133E+09 | 0.180006E+09 | 0.123258E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118060E+10 | 0.105699E+10 | 0.740451E+09 | 0.318190E+09 | 0.442498E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 58820500.06 | 0.115367E+10 | 0.218650E+09 | 69959765.08 | 0.148690E+09 | 0.00 | 0.00 |
February | 0.120556E+09 | 0.825402E+09 | 0.262697E+09 | 92870063.64 | 0.169826E+09 | 0.00 | 0.00 |
March | 0.311517E+09 | 0.587738E+09 | 0.404696E+09 | 0.127549E+09 | 0.277146E+09 | 0.00 | 0.00 |
April | 0.500262E+09 | 0.382527E+09 | 0.474455E+09 | 0.167647E+09 | 0.306808E+09 | 0.00 | 0.00 |
May | 0.814362E+09 | 0.206761E+09 | 0.622251E+09 | 0.222657E+09 | 0.399594E+09 | 0.00 | 0.00 |
June | 0.100166E+10 | 0.120468E+09 | 0.668740E+09 | 0.242311E+09 | 0.426430E+09 | 0.00 | 0.00 |
July | 0.105973E+10 | 0.100887E+09 | 0.689391E+09 | 0.264681E+09 | 0.424710E+09 | 0.00 | 0.00 |
August | 0.891787E+09 | 0.125586E+09 | 0.581408E+09 | 0.204172E+09 | 0.377236E+09 | 0.00 | 0.00 |
September | 0.675783E+09 | 0.238519E+09 | 0.489563E+09 | 0.192636E+09 | 0.296927E+09 | 0.00 | 0.00 |
October | 0.314399E+09 | 0.424141E+09 | 0.327927E+09 | 0.108600E+09 | 0.219327E+09 | 0.00 | 0.00 |
November | 92021493.06 | 0.674618E+09 | 0.193525E+09 | 47288807.92 | 0.146236E+09 | 0.00 | 0.00 |
December | 42893465.39 | 0.103869E+10 | 0.147344E+09 | 48832671.50 | 98511045.65 | 0.00 | 0.00 |
Annual Sum or Average | 0.588379E+10 | 0.587901E+10 | 0.508065E+10 | 0.178920E+10 | 0.329144E+10 | 0.00 | 0.00 |
Minimum of Months | 42893465.39 | 0.100887E+09 | 0.147344E+09 | 47288807.92 | 98511045.65 | 0.00 | 0.00 |
Maximum of Months | 0.105973E+10 | 0.115367E+10 | 0.689391E+09 | 0.264681E+09 | 0.426430E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.393960E+09 | 0.134411E+10 | 0.567989E+09 | 0.340287E+09 | 0.227703E+09 | 0.00 | 0.00 |
February | 0.435190E+09 | 0.973602E+09 | 0.561301E+09 | 0.323297E+09 | 0.238004E+09 | 0.00 | 0.00 |
March | 0.542094E+09 | 0.750646E+09 | 0.585376E+09 | 0.228525E+09 | 0.356851E+09 | 0.00 | 0.00 |
April | 0.606679E+09 | 0.501900E+09 | 0.532227E+09 | 0.163001E+09 | 0.369226E+09 | 0.00 | 0.00 |
May | 0.726212E+09 | 0.271217E+09 | 0.541502E+09 | 87508537.28 | 0.453994E+09 | 0.00 | 0.00 |
June | 0.849319E+09 | 0.161107E+09 | 0.544043E+09 | 69247853.99 | 0.474795E+09 | 0.00 | 0.00 |
July | 0.923491E+09 | 0.138533E+09 | 0.564481E+09 | 84067418.14 | 0.480414E+09 | 0.00 | 0.00 |
August | 0.924377E+09 | 0.173531E+09 | 0.564863E+09 | 0.119734E+09 | 0.445129E+09 | 0.00 | 0.00 |
September | 0.851348E+09 | 0.320318E+09 | 0.581018E+09 | 0.217730E+09 | 0.363288E+09 | 0.00 | 0.00 |
October | 0.715319E+09 | 0.535896E+09 | 0.610124E+09 | 0.313549E+09 | 0.296575E+09 | 0.00 | 0.00 |
November | 0.376008E+09 | 0.821015E+09 | 0.440925E+09 | 0.230004E+09 | 0.210922E+09 | 0.00 | 0.00 |
December | 0.369388E+09 | 0.123725E+10 | 0.455764E+09 | 0.308555E+09 | 0.147209E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.771338E+10 | 0.722912E+10 | 0.654961E+10 | 0.248550E+10 | 0.406411E+10 | 0.00 | 0.00 |
Minimum of Months | 0.369388E+09 | 0.138533E+09 | 0.440925E+09 | 69247853.99 | 0.147209E+09 | 0.00 | 0.00 |
Maximum of Months | 0.924377E+09 | 0.134411E+10 | 0.610124E+09 | 0.340287E+09 | 0.480414E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.324405E+09 | 0.105813E+10 | 0.458314E+09 | 0.266410E+09 | 0.191904E+09 | 0.00 | 0.00 |
February | 0.428836E+09 | 0.763819E+09 | 0.505637E+09 | 0.300812E+09 | 0.204825E+09 | 0.00 | 0.00 |
March | 0.554691E+09 | 0.581150E+09 | 0.561806E+09 | 0.246836E+09 | 0.314971E+09 | 0.00 | 0.00 |
April | 0.805991E+09 | 0.388218E+09 | 0.651468E+09 | 0.312120E+09 | 0.339348E+09 | 0.00 | 0.00 |
May | 0.882316E+09 | 0.216261E+09 | 0.639823E+09 | 0.229577E+09 | 0.410246E+09 | 0.00 | 0.00 |
June | 0.105973E+10 | 0.120340E+09 | 0.686314E+09 | 0.252989E+09 | 0.433326E+09 | 0.00 | 0.00 |
July | 0.121228E+10 | 96447671.75 | 0.759279E+09 | 0.313973E+09 | 0.445306E+09 | 0.00 | 0.00 |
August | 0.113213E+10 | 0.123142E+09 | 0.708498E+09 | 0.297669E+09 | 0.410828E+09 | 0.00 | 0.00 |
September | 0.940833E+09 | 0.235657E+09 | 0.640242E+09 | 0.312580E+09 | 0.327661E+09 | 0.00 | 0.00 |
October | 0.682894E+09 | 0.424764E+09 | 0.567231E+09 | 0.306743E+09 | 0.260488E+09 | 0.00 | 0.00 |
November | 0.330226E+09 | 0.643725E+09 | 0.370881E+09 | 0.191926E+09 | 0.178956E+09 | 0.00 | 0.00 |
December | 0.299163E+09 | 0.975226E+09 | 0.359929E+09 | 0.237002E+09 | 0.122927E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.865350E+10 | 0.562688E+10 | 0.690942E+10 | 0.326864E+10 | 0.364079E+10 | 0.00 | 0.00 |
Minimum of Months | 0.299163E+09 | 96447671.75 | 0.359929E+09 | 0.191926E+09 | 0.122927E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121228E+10 | 0.105813E+10 | 0.759279E+09 | 0.313973E+09 | 0.445306E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 72819774.57 | 0.116972E+10 | 0.219221E+09 | 70056597.41 | 0.149164E+09 | 0.00 | 0.00 |
February | 0.161577E+09 | 0.835640E+09 | 0.283268E+09 | 0.114263E+09 | 0.169006E+09 | 0.00 | 0.00 |
March | 0.305926E+09 | 0.597005E+09 | 0.392492E+09 | 0.114972E+09 | 0.277521E+09 | 0.00 | 0.00 |
April | 0.596711E+09 | 0.388162E+09 | 0.532768E+09 | 0.219050E+09 | 0.313717E+09 | 0.00 | 0.00 |
May | 0.749859E+09 | 0.214812E+09 | 0.579082E+09 | 0.186557E+09 | 0.392525E+09 | 0.00 | 0.00 |
June | 0.975190E+09 | 0.124520E+09 | 0.655474E+09 | 0.235272E+09 | 0.420202E+09 | 0.00 | 0.00 |
July | 0.109004E+10 | 0.106723E+09 | 0.708220E+09 | 0.280701E+09 | 0.427519E+09 | 0.00 | 0.00 |
August | 0.943929E+09 | 0.133236E+09 | 0.614683E+09 | 0.231962E+09 | 0.382720E+09 | 0.00 | 0.00 |
September | 0.661139E+09 | 0.241787E+09 | 0.477802E+09 | 0.187026E+09 | 0.290776E+09 | 0.00 | 0.00 |
October | 0.358140E+09 | 0.432601E+09 | 0.347841E+09 | 0.125818E+09 | 0.222023E+09 | 0.00 | 0.00 |
November | 0.124309E+09 | 0.682482E+09 | 0.206265E+09 | 59208257.16 | 0.147057E+09 | 0.00 | 0.00 |
December | 68964189.44 | 0.104710E+10 | 0.157139E+09 | 58958369.16 | 98180531.02 | 0.00 | 0.00 |
Annual Sum or Average | 0.610860E+10 | 0.597379E+10 | 0.517425E+10 | 0.188384E+10 | 0.329041E+10 | 0.00 | 0.00 |
Minimum of Months | 68964189.44 | 0.106723E+09 | 0.157139E+09 | 58958369.16 | 98180531.02 | 0.00 | 0.00 |
Maximum of Months | 0.109004E+10 | 0.116972E+10 | 0.708220E+09 | 0.280701E+09 | 0.427519E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.419020E+09 | 0.538954E+09 | 0.415655E+09 | 0.287971E+09 | 0.127684E+09 | 0.00 | 0.00 |
February | 0.423800E+09 | 0.391396E+09 | 0.400560E+09 | 0.273593E+09 | 0.126967E+09 | 0.00 | 0.00 |
March | 0.418970E+09 | 0.305485E+09 | 0.371838E+09 | 0.193391E+09 | 0.178447E+09 | 0.00 | 0.00 |
April | 0.407591E+09 | 0.206589E+09 | 0.312234E+09 | 0.137218E+09 | 0.175015E+09 | 0.00 | 0.00 |
May | 0.394460E+09 | 0.112761E+09 | 0.273653E+09 | 68573720.02 | 0.205079E+09 | 0.00 | 0.00 |
June | 0.413688E+09 | 60706380.79 | 0.252800E+09 | 42290973.46 | 0.210509E+09 | 0.00 | 0.00 |
July | 0.474205E+09 | 46916174.59 | 0.276275E+09 | 59968631.55 | 0.216307E+09 | 0.00 | 0.00 |
August | 0.523460E+09 | 61254960.49 | 0.307792E+09 | 98845609.82 | 0.208946E+09 | 0.00 | 0.00 |
September | 0.562917E+09 | 0.122498E+09 | 0.364953E+09 | 0.184197E+09 | 0.180756E+09 | 0.00 | 0.00 |
October | 0.543874E+09 | 0.221376E+09 | 0.419032E+09 | 0.265344E+09 | 0.153688E+09 | 0.00 | 0.00 |
November | 0.332774E+09 | 0.330812E+09 | 0.307277E+09 | 0.194643E+09 | 0.112634E+09 | 0.00 | 0.00 |
December | 0.368751E+09 | 0.498453E+09 | 0.341549E+09 | 0.261118E+09 | 80431623.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.528351E+10 | 0.289720E+10 | 0.404362E+10 | 0.206715E+10 | 0.197646E+10 | 0.00 | 0.00 |
Minimum of Months | 0.332774E+09 | 46916174.59 | 0.252800E+09 | 42290973.46 | 80431623.74 | 0.00 | 0.00 |
Maximum of Months | 0.562917E+09 | 0.538954E+09 | 0.419032E+09 | 0.287971E+09 | 0.216307E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 794274.46 | 0.315754E+10 | 0.310240E+09 | 0.00 | 0.310240E+09 | 0.00 | 0.00 |
February | 17396864.51 | 0.229252E+10 | 0.355261E+09 | 0.00 | 0.355261E+09 | 0.00 | 0.00 |
March | 0.219218E+09 | 0.160463E+10 | 0.589549E+09 | 1551.56 | 0.589547E+09 | 0.00 | 0.00 |
April | 0.474949E+09 | 0.101332E+10 | 0.659349E+09 | 3450246.99 | 0.655898E+09 | 0.00 | 0.00 |
May | 0.103356E+10 | 0.533451E+09 | 0.880913E+09 | 26156699.35 | 0.854756E+09 | 0.00 | 0.00 |
June | 0.150465E+10 | 0.309944E+09 | 0.990686E+09 | 77835411.79 | 0.912850E+09 | 0.00 | 0.00 |
July | 0.154033E+10 | 0.251089E+09 | 0.961198E+09 | 53323997.91 | 0.907874E+09 | 0.00 | 0.00 |
August | 0.128674E+10 | 0.318769E+09 | 0.812342E+09 | 11837260.47 | 0.800505E+09 | 0.00 | 0.00 |
September | 0.763151E+09 | 0.623938E+09 | 0.604805E+09 | 282905.55 | 0.604522E+09 | 0.00 | 0.00 |
October | 0.276326E+09 | 0.114377E+10 | 0.464277E+09 | 0.00 | 0.464277E+09 | 0.00 | 0.00 |
November | 61043651.13 | 0.183424E+10 | 0.314290E+09 | 0.00 | 0.314290E+09 | 0.00 | 0.00 |
December | 116277.10 | 0.279235E+10 | 0.210663E+09 | 0.00 | 0.210663E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.717828E+10 | 0.158756E+11 | 0.715357E+10 | 0.172888E+09 | 0.698068E+10 | 0.00 | 0.00 |
Minimum of Months | 116277.10 | 0.251089E+09 | 0.210663E+09 | 0.00 | 0.210663E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154033E+10 | 0.315754E+10 | 0.990686E+09 | 77835411.79 | 0.912850E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 593605.46 | 0.321529E+10 | 0.310240E+09 | 0.00 | 0.310240E+09 | 0.00 | 0.00 |
February | 14860227.26 | 0.234427E+10 | 0.355261E+09 | 0.00 | 0.355261E+09 | 0.00 | 0.00 |
March | 0.205525E+09 | 0.165900E+10 | 0.589549E+09 | 1551.56 | 0.589547E+09 | 0.00 | 0.00 |
April | 0.455849E+09 | 0.105672E+10 | 0.659349E+09 | 3450246.99 | 0.655898E+09 | 0.00 | 0.00 |
May | 0.100554E+10 | 0.556356E+09 | 0.880913E+09 | 26156699.35 | 0.854756E+09 | 0.00 | 0.00 |
June | 0.147733E+10 | 0.326376E+09 | 0.990686E+09 | 77835411.79 | 0.912850E+09 | 0.00 | 0.00 |
July | 0.151322E+10 | 0.266620E+09 | 0.961198E+09 | 53323997.91 | 0.907874E+09 | 0.00 | 0.00 |
August | 0.126145E+10 | 0.336155E+09 | 0.812342E+09 | 11837260.47 | 0.800505E+09 | 0.00 | 0.00 |
September | 0.742843E+09 | 0.651245E+09 | 0.604805E+09 | 282905.55 | 0.604522E+09 | 0.00 | 0.00 |
October | 0.257676E+09 | 0.119303E+10 | 0.464277E+09 | 0.00 | 0.464277E+09 | 0.00 | 0.00 |
November | 54810950.60 | 0.189098E+10 | 0.314290E+09 | 0.00 | 0.314290E+09 | 0.00 | 0.00 |
December | 46548.68 | 0.285250E+10 | 0.210663E+09 | 0.00 | 0.210663E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.698975E+10 | 0.163485E+11 | 0.715357E+10 | 0.172888E+09 | 0.698068E+10 | 0.00 | 0.00 |
Minimum of Months | 46548.68 | 0.266620E+09 | 0.210663E+09 | 0.00 | 0.210663E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151322E+10 | 0.321529E+10 | 0.990686E+09 | 77835411.79 | 0.912850E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.478143E+09 | 0.184110E+10 | 0.676367E+09 | 0.336263E+09 | 0.340105E+09 | 0.00 | 0.00 |
February | 0.668789E+09 | 0.129609E+10 | 0.747732E+09 | 0.372277E+09 | 0.375455E+09 | 0.00 | 0.00 |
March | 0.121503E+10 | 0.971403E+09 | 0.978659E+09 | 0.386945E+09 | 0.591715E+09 | 0.00 | 0.00 |
April | 0.164222E+10 | 0.623239E+09 | 0.106756E+10 | 0.428339E+09 | 0.639217E+09 | 0.00 | 0.00 |
May | 0.238598E+10 | 0.355641E+09 | 0.130517E+10 | 0.488303E+09 | 0.816869E+09 | 0.00 | 0.00 |
June | 0.276288E+10 | 0.210440E+09 | 0.136825E+10 | 0.502305E+09 | 0.865941E+09 | 0.00 | 0.00 |
July | 0.297591E+10 | 0.169131E+09 | 0.142976E+10 | 0.562597E+09 | 0.867166E+09 | 0.00 | 0.00 |
August | 0.267030E+10 | 0.204350E+09 | 0.125657E+10 | 0.474023E+09 | 0.782542E+09 | 0.00 | 0.00 |
September | 0.220238E+10 | 0.372304E+09 | 0.114151E+10 | 0.510799E+09 | 0.630709E+09 | 0.00 | 0.00 |
October | 0.137185E+10 | 0.666151E+09 | 0.875206E+09 | 0.398109E+09 | 0.477098E+09 | 0.00 | 0.00 |
November | 0.613985E+09 | 0.104044E+10 | 0.551646E+09 | 0.227288E+09 | 0.324358E+09 | 0.00 | 0.00 |
December | 0.407327E+09 | 0.162322E+10 | 0.497461E+09 | 0.275702E+09 | 0.221759E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193948E+11 | 0.937351E+10 | 0.118959E+11 | 0.496295E+10 | 0.693293E+10 | 0.00 | 0.00 |
Minimum of Months | 0.407327E+09 | 0.169131E+09 | 0.497461E+09 | 0.227288E+09 | 0.221759E+09 | 0.00 | 0.00 |
Maximum of Months | 0.297591E+10 | 0.184110E+10 | 0.142976E+10 | 0.562597E+09 | 0.867166E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.913873E+09 | 0.236467E+10 | 0.116442E+10 | 0.733045E+09 | 0.431377E+09 | 0.00 | 0.00 |
February | 0.975911E+09 | 0.171421E+10 | 0.114143E+10 | 0.696446E+09 | 0.444985E+09 | 0.00 | 0.00 |
March | 0.111428E+10 | 0.134253E+10 | 0.114863E+10 | 0.492289E+09 | 0.656344E+09 | 0.00 | 0.00 |
April | 0.117463E+10 | 0.935480E+09 | 0.102083E+10 | 0.350479E+09 | 0.670354E+09 | 0.00 | 0.00 |
May | 0.127983E+10 | 0.553617E+09 | 0.998577E+09 | 0.183525E+09 | 0.815052E+09 | 0.00 | 0.00 |
June | 0.146407E+10 | 0.336646E+09 | 0.983125E+09 | 0.134336E+09 | 0.848789E+09 | 0.00 | 0.00 |
July | 0.162496E+10 | 0.288999E+09 | 0.103277E+10 | 0.170933E+09 | 0.861841E+09 | 0.00 | 0.00 |
August | 0.167723E+10 | 0.362307E+09 | 0.106197E+10 | 0.255675E+09 | 0.806299E+09 | 0.00 | 0.00 |
September | 0.163645E+10 | 0.621864E+09 | 0.113634E+10 | 0.468980E+09 | 0.667355E+09 | 0.00 | 0.00 |
October | 0.145438E+10 | 0.990867E+09 | 0.122582E+10 | 0.675446E+09 | 0.550377E+09 | 0.00 | 0.00 |
November | 0.807316E+09 | 0.146776E+10 | 0.889929E+09 | 0.495473E+09 | 0.394455E+09 | 0.00 | 0.00 |
December | 0.840019E+09 | 0.218340E+10 | 0.941647E+09 | 0.664689E+09 | 0.276959E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.149629E+11 | 0.131624E+11 | 0.127455E+11 | 0.532132E+10 | 0.742419E+10 | 0.00 | 0.00 |
Minimum of Months | 0.807316E+09 | 0.288999E+09 | 0.889929E+09 | 0.134336E+09 | 0.276959E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167723E+10 | 0.236467E+10 | 0.122582E+10 | 0.733045E+09 | 0.861841E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770419E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161415625.6 | 81.21 | 0.00 | 0.00 |
February | 0.696179E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145824092.9 | 81.21 | 0.00 | 0.00 |
March | 0.770288E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161414369.2 | 81.21 | 0.00 | 0.00 |
April | 0.746480E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156207190.5 | 81.21 | 0.00 | 0.00 |
May | 0.770420E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413218.4 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156205534.4 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411662.8 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412175.7 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206187.1 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161414266.3 | 81.21 | 0.00 | 0.00 |
November | 0.744863E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156207191.0 | 81.21 | 0.00 | 0.00 |
December | 0.771227E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161414404.3 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907410E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190055E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696179E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161415625.6 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771227E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145824092.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.128966E+12 | -0.127208E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175735E+10 | 80.74 | 0.00 | 0.00 |
February | 0.116639E+12 | -0.115045E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.159360E+10 | 80.44 | 0.00 | 0.00 |
March | 0.129066E+12 | -0.127282E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178337E+10 | 80.59 | 0.00 | 0.00 |
April | 0.124582E+12 | -0.122835E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174746E+10 | 81.15 | 0.00 | 0.00 |
May | 0.124214E+12 | -0.122407E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180666E+10 | 81.29 | 0.00 | 0.00 |
June | 0.114565E+12 | -0.112831E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173381E+10 | 81.27 | 0.00 | 0.00 |
July | 0.113908E+12 | -0.112132E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177632E+10 | 81.26 | 0.00 | 0.00 |
August | 0.111859E+12 | -0.110100E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175879E+10 | 81.26 | 0.00 | 0.00 |
September | 0.109203E+12 | -0.107514E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168928E+10 | 81.25 | 0.00 | 0.00 |
October | 0.116561E+12 | -0.114820E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174035E+10 | 81.26 | 0.00 | 0.00 |
November | 0.118093E+12 | -0.116407E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168612E+10 | 81.27 | 0.00 | 0.00 |
December | 0.127720E+12 | -0.125967E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175358E+10 | 81.28 | 0.00 | 0.00 |
Annual Sum or Average | 0.143537E+13 | -0.141455E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208267E+11 | 81.09 | 0.00 | 0.00 |
Minimum of Months | 0.109203E+12 | -0.127282E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.180666E+10 | 80.44 | 0.00 | 0.00 |
Maximum of Months | 0.129066E+12 | -0.107514E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159360E+10 | 81.29 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.814452E+11 | -0.799180E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152727E+10 | 58.99 | 0.00 | 0.00 |
February | 0.750633E+11 | -0.736640E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139923E+10 | 58.99 | 0.00 | 0.00 |
March | 0.823620E+11 | -0.807927E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156934E+10 | 58.99 | 0.00 | 0.00 |
April | 0.766421E+11 | -0.751160E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152614E+10 | 58.98 | 0.00 | 0.00 |
May | 0.745622E+11 | -0.729899E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157229E+10 | 58.98 | 0.00 | 0.00 |
June | 0.674234E+11 | -0.659210E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150237E+10 | 58.98 | 0.00 | 0.00 |
July | 0.657566E+11 | -0.642250E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153162E+10 | 58.98 | 0.00 | 0.00 |
August | 0.640500E+11 | -0.625427E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150732E+10 | 58.98 | 0.00 | 0.00 |
September | 0.627630E+11 | -0.613218E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144119E+10 | 58.98 | 0.00 | 0.00 |
October | 0.680160E+11 | -0.665343E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148170E+10 | 58.98 | 0.00 | 0.00 |
November | 0.703373E+11 | -0.689011E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143617E+10 | 58.98 | 0.00 | 0.00 |
December | 0.775753E+11 | -0.760760E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149931E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.865996E+12 | -0.848002E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179940E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.627630E+11 | -0.807927E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157229E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.823620E+11 | -0.613218E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139923E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.86 | 0.86 | 01-JAN-09:39 | 7241.32 | 38.28 | 207.17 | 254.33 | 4873.74 | 37.74 | 209.33 | 223.50 |
February | 226.83 | 0.87 | 0.86 | 01-FEB-07:49 | 8685.62 | 38.01 | 221.50 | 260.00 | 1815.66 | 29.08 | 209.50 | 237.83 |
March | 334.33 | 0.87 | 0.86 | 01-MAR-07:49 | 4754.52 | 25.94 | 188.17 | 334.83 | 835.36 | 22.23 | 234.83 | 291.83 |
April | 285.17 | 0.87 | 0.86 | 01-APR-07:10 | 1767.26 | 20.32 | 66.17 | 354.67 | 726.32 | 22.45 | 220.50 | 295.00 |
May | 428.67 | 0.87 | 0.86 | 01-MAY-06:40 | 1454.68 | 19.42 | 21.33 | 404.83 | 574.41 | 21.56 | 276.17 | 345.00 |
June | 400.67 | 0.87 | 0.86 | 01-JUN-05:40 | 1480.56 | 19.77 | 46.17 | 407.00 | 598.55 | 21.93 | 280.33 | 348.67 |
July | 414.00 | 0.87 | 0.86 | 01-JUL-05:49 | 1521.88 | 20.12 | 55.00 | 416.83 | 619.52 | 22.26 | 306.50 | 359.33 |
August | 410.83 | 0.87 | 0.86 | 01-AUG-06:10 | 1709.31 | 19.88 | 73.83 | 386.67 | 676.42 | 22.00 | 301.67 | 341.17 |
September | 326.50 | 0.87 | 0.86 | 01-SEP-06:19 | 2867.31 | 22.66 | 132.50 | 340.50 | 804.10 | 22.61 | 246.83 | 299.83 |
October | 325.17 | 0.87 | 0.86 | 01-OCT-06:00 | 7473.21 | 33.87 | 296.33 | 311.83 | 1011.98 | 23.68 | 241.67 | 283.33 |
November | 254.83 | 0.86 | 0.86 | 01-NOV-07:40 | 5156.05 | 33.54 | 239.83 | 255.33 | 2479.66 | 30.93 | 227.33 | 227.33 |
December | 186.17 | 0.87 | 0.86 | 01-DEC-07:00 | 6300.03 | 38.40 | 180.50 | 229.83 | 5612.96 | 39.39 | 180.83 | 184.00 |
Annual Sum or Average | 3807.33 | 0.87 | 3681.50 | 25.78 | 1728.50 | 3956.67 | 1373.91 | 24.98 | 2935.50 | 3436.83 | ||
Minimum of Months | 186.17 | 0.86 | 0.86 | 1454.68 | 19.42 | 21.33 | 229.83 | 574.41 | 21.56 | 180.83 | 184.00 | |
Maximum of Months | 428.67 | 0.87 | 0.86 | 8685.62 | 38.40 | 296.33 | 416.83 | 5612.96 | 39.39 | 306.50 | 359.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.23 | 0.22 | 01-JAN-09:39 | 7820.98 | 38.37 | 207.17 | 261.50 | 5452.29 | 37.72 | 204.50 | 241.17 |
February | 226.83 | 0.24 | 0.22 | 01-FEB-07:49 | 9250.27 | 38.08 | 221.67 | 267.33 | 2375.33 | 28.82 | 205.33 | 251.33 |
March | 334.33 | 0.23 | 0.22 | 01-MAR-07:40 | 5157.20 | 26.20 | 189.33 | 344.33 | 1234.49 | 22.43 | 241.50 | 317.67 |
April | 285.17 | 0.24 | 0.22 | 01-APR-06:49 | 2145.12 | 20.62 | 90.67 | 365.00 | 1102.86 | 22.62 | 235.00 | 336.83 |
May | 428.67 | 0.24 | 0.22 | 01-MAY-05:00 | 1703.38 | 20.11 | 77.00 | 418.67 | 822.07 | 22.04 | 307.83 | 384.33 |
June | 400.67 | 0.25 | 0.22 | 01-JUN-05:10 | 1728.10 | 20.44 | 116.83 | 418.17 | 845.06 | 22.40 | 310.67 | 387.67 |
July | 414.00 | 0.24 | 0.22 | 01-JUL-05:40 | 1786.17 | 20.73 | 129.33 | 429.50 | 882.73 | 22.68 | 331.67 | 397.50 |
August | 410.83 | 0.25 | 0.22 | 01-AUG-05:00 | 2002.55 | 20.43 | 116.83 | 398.33 | 968.41 | 22.37 | 322.83 | 371.33 |
September | 326.50 | 0.24 | 0.22 | 01-SEP-06:10 | 3268.58 | 22.90 | 143.83 | 347.83 | 1203.72 | 22.76 | 267.00 | 324.83 |
October | 325.17 | 0.24 | 0.22 | 01-OCT-06:49 | 7918.37 | 34.04 | 297.67 | 318.83 | 1457.24 | 23.75 | 238.50 | 301.17 |
November | 254.83 | 0.24 | 0.22 | 01-NOV-07:40 | 5545.43 | 33.66 | 241.67 | 263.00 | 2869.11 | 30.98 | 229.17 | 243.67 |
December | 186.17 | 0.24 | 0.22 | 01-DEC-07:00 | 6842.48 | 38.50 | 180.83 | 241.00 | 6150.72 | 39.47 | 180.83 | 213.67 |
Annual Sum or Average | 3807.33 | 0.24 | 4050.85 | 26.15 | 2012.83 | 4073.50 | 1741.66 | 25.21 | 3074.83 | 3771.17 | ||
Minimum of Months | 186.17 | 0.23 | 0.22 | 1703.38 | 20.11 | 77.00 | 241.00 | 822.07 | 22.04 | 180.83 | 213.67 | |
Maximum of Months | 428.67 | 0.25 | 0.22 | 9250.27 | 38.50 | 297.67 | 429.50 | 6150.72 | 39.47 | 331.67 | 397.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.63 | 0.60 | 01-JAN-09:50 | 507.48 | 15.13 | 0.00 | 237.33 | 250.94 | 19.11 | 0.50 | 155.00 |
February | 226.83 | 0.63 | 0.60 | 01-FEB-08:39 | 520.50 | 15.34 | 0.00 | 248.50 | 259.69 | 19.29 | 0.33 | 180.33 |
March | 334.33 | 0.62 | 0.60 | 01-MAR-07:00 | 731.53 | 16.69 | 0.00 | 334.83 | 332.17 | 20.33 | 26.33 | 281.50 |
April | 285.17 | 0.61 | 0.60 | 01-APR-06:00 | 824.37 | 17.80 | 0.00 | 363.83 | 399.70 | 21.45 | 136.33 | 316.33 |
May | 428.67 | 0.61 | 0.60 | 01-MAY-05:00 | 970.12 | 17.96 | 4.17 | 425.33 | 432.35 | 22.34 | 228.17 | 391.50 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1170.34 | 20.99 | 66.83 | 426.33 | 551.42 | 24.40 | 303.50 | 401.50 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 1093.47 | 20.51 | 54.00 | 434.50 | 515.45 | 23.54 | 300.67 | 408.83 |
August | 410.83 | 0.61 | 0.60 | 01-AUG-05:49 | 907.93 | 17.99 | 4.50 | 401.67 | 419.52 | 21.78 | 224.33 | 373.50 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:10 | 732.65 | 17.32 | 0.00 | 342.00 | 357.16 | 20.97 | 84.17 | 303.83 |
October | 325.17 | 0.62 | 0.60 | 01-OCT-07:10 | 595.92 | 15.86 | 0.00 | 303.00 | 278.82 | 19.64 | 0.00 | 240.83 |
November | 254.83 | 0.63 | 0.60 | 01-NOV-08:09 | 522.67 | 14.97 | 0.00 | 243.50 | 234.44 | 18.74 | 0.00 | 167.33 |
December | 186.17 | 0.65 | 0.60 | 01-DEC-08:39 | 360.06 | 13.68 | 0.00 | 210.50 | 185.16 | 17.84 | 0.00 | 68.50 |
Annual Sum or Average | 3807.33 | 0.62 | 801.11 | 17.48 | 129.50 | 3971.33 | 375.91 | 21.21 | 1304.33 | 3289.00 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 360.06 | 13.68 | 0.00 | 210.50 | 185.16 | 17.84 | 0.00 | 68.50 | |
Maximum of Months | 428.67 | 0.65 | 0.60 | 1170.34 | 20.99 | 66.83 | 434.50 | 551.42 | 24.40 | 303.50 | 408.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.63 | 0.60 | 01-JAN-09:50 | 507.48 | 15.13 | 0.00 | 237.33 | 250.94 | 19.11 | 0.50 | 155.00 |
February | 226.83 | 0.63 | 0.60 | 01-FEB-08:39 | 520.50 | 15.34 | 0.00 | 248.50 | 259.69 | 19.29 | 0.33 | 180.33 |
March | 334.33 | 0.62 | 0.60 | 01-MAR-07:00 | 731.53 | 16.69 | 0.00 | 334.83 | 332.17 | 20.33 | 26.33 | 281.50 |
April | 285.17 | 0.61 | 0.60 | 01-APR-06:00 | 824.37 | 17.80 | 0.00 | 363.83 | 399.70 | 21.45 | 136.33 | 316.33 |
May | 428.67 | 0.61 | 0.60 | 01-MAY-05:00 | 970.12 | 17.96 | 4.17 | 425.33 | 432.35 | 22.34 | 228.17 | 391.50 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1170.34 | 20.99 | 66.83 | 426.33 | 551.42 | 24.40 | 303.50 | 401.50 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 1093.47 | 20.51 | 54.00 | 434.50 | 515.45 | 23.54 | 300.67 | 408.83 |
August | 410.83 | 0.61 | 0.60 | 01-AUG-05:49 | 907.93 | 17.99 | 4.50 | 401.67 | 419.52 | 21.78 | 224.33 | 373.50 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:10 | 732.65 | 17.32 | 0.00 | 342.00 | 357.16 | 20.97 | 84.17 | 303.83 |
October | 325.17 | 0.62 | 0.60 | 01-OCT-07:10 | 595.92 | 15.86 | 0.00 | 303.00 | 278.82 | 19.64 | 0.00 | 240.83 |
November | 254.83 | 0.63 | 0.60 | 01-NOV-08:09 | 522.67 | 14.97 | 0.00 | 243.50 | 234.44 | 18.74 | 0.00 | 167.33 |
December | 186.17 | 0.65 | 0.60 | 01-DEC-08:39 | 360.06 | 13.68 | 0.00 | 210.50 | 185.16 | 17.84 | 0.00 | 68.50 |
Annual Sum or Average | 3807.33 | 0.62 | 801.11 | 17.48 | 129.50 | 3971.33 | 375.91 | 21.21 | 1304.33 | 3289.00 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 360.06 | 13.68 | 0.00 | 210.50 | 185.16 | 17.84 | 0.00 | 68.50 | |
Maximum of Months | 428.67 | 0.65 | 0.60 | 1170.34 | 20.99 | 66.83 | 434.50 | 551.42 | 24.40 | 303.50 | 408.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168783E+12 | 381814.82 | 30-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164754E+12 | 394963.04 | 02-FEB-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.478168E+11 | 91253.71 | 21-MAR-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.409542E+11 | 89889.88 | 04-APR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140034E+11 | 86336.27 | 03-MAY-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.208692E+10 | 45984.41 | 03-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156632E+09 | 14898.51 | 07-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133748E+11 | 89730.42 | 29-SEP-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.532422E+11 | 95971.78 | 16-OCT-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623054E+11 | 359952.94 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422056E+11 | 91464.57 | 01-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168783E+12 | 394963.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107677E+09 | 2771.20 | 20-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147047E+10 | 4804.39 | 17-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.442600E+09 | 3854.75 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2475344.67 | 2793.73 | 01-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147047E+10 | 4804.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.341084E+10 | 2841.83 | 19-JAN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216900E+10 | 3620.23 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134669E+10 | 1630.63 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672492E+09 | 1412.17 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22729495.48 | 547.80 | 02-MAY-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13170348.77 | 438.43 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74283741.98 | 868.36 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295389E+09 | 880.45 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157974E+10 | 2477.60 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295292E+10 | 2688.10 | 09-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.341084E+10 | 3620.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.959831E+09 | 982.57 | 19-JAN-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.629118E+09 | 1435.21 | 02-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.290343E+09 | 753.30 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97331668.46 | 704.01 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1310631.88 | 303.08 | 02-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403892.02 | 187.15 | 05-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1020894.19 | 261.96 | 30-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9824416.60 | 297.75 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326742E+09 | 915.14 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.697833E+09 | 977.11 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.959831E+09 | 1435.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131510E+10 | 1598.24 | 31-JAN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.784852E+09 | 2047.26 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113675E+09 | 624.55 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232969E+09 | 1058.62 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655851E+09 | 1220.05 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.310245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131510E+10 | 2047.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264483E+10 | 1565.44 | 31-JAN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201995E+10 | 1997.53 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141397E+10 | 1029.17 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715274E+09 | 839.21 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60845067.90 | 491.28 | 02-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10982439.19 | 264.91 | 05-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59912239.47 | 422.58 | 30-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.392795E+09 | 486.55 | 27-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126421E+10 | 1330.47 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222696E+10 | 1353.71 | 11-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.264483E+10 | 1997.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.648669E+10 | 8407.06 | 19-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425246E+10 | 12110.94 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260787E+10 | 6250.97 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170350E+10 | 5799.05 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.370694E+09 | 3475.88 | 25-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239741E+09 | 4230.83 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47276591.34 | 2993.57 | 10-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20378324.58 | 2163.30 | 31-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363796E+09 | 4213.49 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.907181E+09 | 4096.11 | 26-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337733E+10 | 7377.69 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.565099E+10 | 8408.85 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20378324.58 | 2163.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648669E+10 | 12110.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.652575E+10 | 14684.66 | 26-JAN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.434870E+10 | 23208.47 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146416E+10 | 10808.51 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468586E+09 | 9262.10 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1268466.19 | 2114.11 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192510E+10 | 14905.09 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.504234E+10 | 16085.25 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.652575E+10 | 23208.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138707E+11 | 10052.29 | 19-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.935333E+10 | 13166.86 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.524341E+10 | 6791.30 | 01-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185419E+10 | 5868.96 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6500573.07 | 1083.24 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64312182.92 | 2354.55 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.908033E+09 | 3739.98 | 26-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.658033E+10 | 9202.32 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120126E+11 | 10277.74 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138707E+11 | 13166.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.736426E+10 | 6499.35 | 31-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.462449E+10 | 8697.30 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192422E+10 | 3347.06 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.417048E+09 | 2165.99 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 368602.21 | 164.67 | 30-SEP-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36396858.71 | 941.19 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265229E+10 | 5345.98 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577686E+10 | 5275.16 | 10-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.736426E+10 | 8697.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.287234E+10 | 6340.72 | 31-JAN-09:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228010E+10 | 12501.06 | 02-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755191E+09 | 4572.58 | 06-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192523E+09 | 3681.56 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10551953.22 | 2704.95 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1365927.39 | 1190.98 | 05-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 112830.79 | 188.05 | 07-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15267131.69 | 2767.61 | 29-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104204E+09 | 3515.31 | 27-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101858E+10 | 5269.98 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216870E+10 | 5761.29 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.941894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.287234E+10 | 12501.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148654E+10 | 4930.27 | 31-JAN-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118227E+10 | 11327.08 | 02-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126073E+09 | 2891.12 | 06-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13636294.02 | 1855.43 | 06-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76303.96 | 127.17 | 02-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93616.52 | 156.03 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10167817.23 | 1714.39 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320826E+09 | 3882.54 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.913274E+09 | 4385.61 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148654E+10 | 11327.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186607E+11 | 44038.28 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135465E+11 | 46111.64 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231282E+10 | 6981.13 | 06-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426893E+09 | 3898.50 | 03-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8656.04 | 0.27 | 12-MAY-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14051.61 | 0.28 | 18-JUN-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13109.94 | 0.28 | 09-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14202.02 | 0.28 | 15-AUG-18:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 295126.54 | 189.12 | 30-SEP-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21127479.67 | 1120.65 | 23-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.419542E+10 | 43198.56 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672913E+10 | 11603.85 | 09-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8656.04 | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186607E+11 | 46111.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.811798E+10 | 12380.09 | 18-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.537346E+10 | 12380.06 | 22-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315355E+10 | 12376.12 | 02-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134130E+10 | 12377.73 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120277E+09 | 5533.19 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49376122.54 | 4787.04 | 04-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4761652.19 | 3593.33 | 20-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5659501.09 | 4590.53 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.273705E+09 | 6965.38 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116779E+10 | 12122.71 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.387095E+10 | 12379.38 | 17-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.679006E+10 | 12379.74 | 31-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4761652.19 | 3593.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.811798E+10 | 12380.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.929776E+10 | 12261.60 | 18-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.637065E+10 | 12263.19 | 22-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367834E+10 | 12257.51 | 02-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151381E+10 | 12259.20 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130981E+09 | 6930.86 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50608158.71 | 4719.89 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2633128.25 | 3212.10 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5012028.50 | 4529.58 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328981E+09 | 9610.14 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159374E+10 | 12093.71 | 27-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449464E+10 | 12261.90 | 17-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.767113E+10 | 12261.22 | 31-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2633128.25 | 3212.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.929776E+10 | 12263.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.897413E+10 | 22064.18 | 19-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256873E+10 | 20255.63 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113706E+09 | 5717.51 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315768E+09 | 12597.31 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.557312E+10 | 17704.10 | 12-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.897413E+10 | 22064.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.401329E+11 | 68833.82 | 18-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279176E+11 | 68818.90 | 05-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109731E+11 | 67830.36 | 01-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309252E+10 | 66609.39 | 03-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67679160.83 | 19009.91 | 02-MAY-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22980762.48 | 21408.45 | 06-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9829040.56 | 15090.58 | 22-JUL-21:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18650011.83 | 21468.53 | 18-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239350E+09 | 30352.06 | 24-SEP-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192512E+10 | 35909.18 | 29-OCT-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143203E+11 | 68823.08 | 25-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295736E+11 | 68842.39 | 08-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9829040.56 | 15090.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401329E+11 | 68842.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.807116E+10 | 11918.65 | 16-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.545289E+10 | 11917.66 | 22-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310333E+10 | 11913.56 | 02-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146479E+10 | 11915.36 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96256957.29 | 4955.31 | 24-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38400947.10 | 4039.01 | 03-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1197824.69 | 2525.40 | 08-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2633266.19 | 3390.51 | 23-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247489E+09 | 5202.47 | 13-SEP-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117556E+10 | 11625.09 | 26-OCT-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.389163E+10 | 11916.96 | 17-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.681088E+10 | 11917.34 | 31-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1197824.69 | 2525.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.807116E+10 | 11918.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.925420E+10 | 11803.09 | 16-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.648863E+10 | 11803.67 | 22-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362528E+10 | 11797.88 | 02-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166883E+10 | 11799.74 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108098E+09 | 4434.59 | 20-MAY-18:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39326573.24 | 4625.13 | 03-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1866933.91 | 3285.22 | 10-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2556059.24 | 2669.33 | 25-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.294893E+09 | 4487.80 | 24-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160805E+10 | 11575.18 | 26-OCT-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452408E+10 | 11802.43 | 17-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.772473E+10 | 11803.04 | 02-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1866933.91 | 2669.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.925420E+10 | 11803.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.277425E+10 | 3573.75 | 16-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187616E+10 | 3575.35 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115216E+10 | 3574.07 | 12-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520337E+09 | 3572.75 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69643057.46 | 2596.30 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31201649.34 | 1187.75 | 04-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1214138.69 | 1046.38 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1972148.38 | 918.35 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135042E+09 | 3010.75 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.489328E+09 | 3555.70 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139362E+10 | 3574.76 | 17-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234517E+10 | 3573.35 | 31-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1214138.69 | 918.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.277425E+10 | 3575.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311216E+10 | 3532.39 | 13-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217377E+10 | 3534.18 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132449E+10 | 3532.62 | 12-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.576242E+09 | 3531.26 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69449157.81 | 2921.18 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31537909.12 | 1138.18 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 698661.09 | 598.62 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1148506.81 | 1089.91 | 18-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155019E+09 | 3480.61 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633585E+09 | 3533.20 | 27-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158740E+10 | 3535.42 | 15-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261581E+10 | 3532.37 | 02-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 698661.09 | 598.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.311216E+10 | 3535.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.946242E+10 | 17060.35 | 17-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.592686E+10 | 17053.15 | 27-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346527E+10 | 17054.40 | 02-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169954E+10 | 17057.02 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128575E+09 | 5629.32 | 26-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50025107.22 | 5596.54 | 01-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4607738.39 | 4535.90 | 10-JUL-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11669306.74 | 3791.89 | 23-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248014E+09 | 5813.10 | 13-SEP-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.873352E+09 | 15336.99 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418221E+10 | 17057.90 | 23-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.787639E+10 | 17060.07 | 31-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4607738.39 | 3791.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.946242E+10 | 17060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167911E+09 | 0.167911E+09 | 4813.70 | 13-JAN-06:10 | 4813.70 | 0.00 |
February | 0.00 | 0.00 | 0.206656E+09 | 0.206656E+09 | 4819.11 | 14-FEB-06:10 | 4819.11 | 0.00 |
March | 0.00 | 0.00 | 0.370370E+10 | 0.370370E+10 | 79436.07 | 19-MAR-16:20 | 79436.07 | 0.02 |
April | 0.00 | 0.00 | 0.465049E+11 | 0.395683E+11 | 282128.29 | 18-APR-10:35 | 180891.47 | 0.14 |
May | 0.00 | 0.00 | 0.112684E+12 | 0.917133E+11 | 280476.30 | 29-MAY-18:03 | 154151.35 | 0.41 |
June | 0.00 | 0.00 | 0.315828E+12 | 0.222640E+12 | 385838.66 | 26-JUN-06:53 | 157527.98 | 0.76 |
July | 0.00 | 0.00 | 0.458684E+12 | 0.285396E+12 | 456131.63 | 17-JUL-19:10 | 180317.01 | 0.93 |
August | 0.00 | 0.00 | 0.395247E+12 | 0.251928E+12 | 461107.01 | 28-AUG-19:40 | 181123.60 | 0.86 |
September | 0.00 | 0.00 | 0.151987E+12 | 0.138791E+12 | 286203.10 | 11-SEP-10:35 | 188269.26 | 0.46 |
October | 0.00 | 0.00 | 0.116608E+11 | 0.116608E+11 | 144121.90 | 20-OCT-15:13 | 144121.90 | 0.05 |
November | 0.00 | 0.00 | 0.841698E+09 | 0.841698E+09 | 26609.74 | 03-NOV-15:13 | 26609.74 | 0.01 |
December | 0.00 | 0.00 | 0.304193E+09 | 0.304193E+09 | 4799.15 | 01-DEC-06:10 | 4799.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149782E+13 | 0.104692E+13 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.167911E+09 | 0.167911E+09 | 4799.15 | 4799.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.458684E+12 | 0.285396E+12 | 461107.01 | 188269.26 | 0.93 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.189758E+09 | 0.189758E+09 | 8515.76 | 19-MAR-16:00 | 8515.76 | 0.01 |
April | 0.00 | 0.00 | 0.309722E+10 | 0.243844E+10 | 26824.05 | 18-APR-12:15 | 17721.41 | 0.09 |
May | 0.00 | 0.00 | 0.701504E+10 | 0.526282E+10 | 29139.22 | 29-MAY-15:13 | 14564.20 | 0.28 |
June | 0.00 | 0.00 | 0.232110E+11 | 0.149667E+11 | 39170.75 | 26-JUN-08:62 | 18088.17 | 0.55 |
July | 0.00 | 0.00 | 0.350577E+11 | 0.197621E+11 | 39681.85 | 17-JUL-19:00 | 15739.70 | 0.70 |
August | 0.00 | 0.00 | 0.286108E+11 | 0.164955E+11 | 43067.55 | 04-AUG-08:61 | 17491.42 | 0.63 |
September | 0.00 | 0.00 | 0.103796E+11 | 0.886000E+10 | 29549.17 | 11-SEP-08:15 | 15611.99 | 0.33 |
October | 0.00 | 0.00 | 0.596936E+09 | 0.596936E+09 | 15153.02 | 20-OCT-15:11 | 15153.02 | 0.02 |
November | 0.00 | 0.00 | 22232930.82 | 22232930.82 | 1791.45 | 03-NOV-15:11 | 1791.45 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108180E+12 | 0.685945E+11 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.350577E+11 | 0.197621E+11 | 43067.55 | 18088.17 | 0.70 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8107022.96 | 8107022.96 | 12376.52 | 12-JAN-16:11 | 12376.52 | 0.00 |
February | 0.00 | 0.00 | 68410179.82 | 67779777.53 | 14186.49 | 24-FEB-16:11 | 14186.49 | 0.00 |
March | 0.00 | 0.00 | 0.238088E+09 | 0.180384E+09 | 14186.25 | 24-MAR-15:11 | 14186.25 | 0.04 |
April | 0.00 | 0.00 | 0.177502E+10 | 0.110865E+10 | 14573.06 | 16-APR-08:61 | 11111.30 | 0.26 |
May | 0.00 | 0.00 | 0.338258E+10 | 0.167299E+10 | 15033.37 | 29-MAY-08:61 | 10786.19 | 0.64 |
June | 0.00 | 0.00 | 0.645678E+10 | 0.334590E+10 | 15595.87 | 25-JUN-08:61 | 10350.98 | 0.82 |
July | 0.00 | 0.00 | 0.834084E+10 | 0.428627E+10 | 16293.54 | 20-JUL-08:62 | 9614.04 | 0.92 |
August | 0.00 | 0.00 | 0.740242E+10 | 0.357957E+10 | 17449.30 | 31-AUG-08:62 | 8611.03 | 0.91 |
September | 0.00 | 0.00 | 0.429472E+10 | 0.233545E+10 | 15238.62 | 11-SEP-08:61 | 10621.65 | 0.64 |
October | 0.00 | 0.00 | 0.735946E+09 | 0.478651E+09 | 14186.83 | 19-OCT-15:11 | 14186.83 | 0.16 |
November | 0.00 | 0.00 | 0.137263E+09 | 97877948.83 | 14181.11 | 04-NOV-15:11 | 14181.11 | 0.03 |
December | 0.00 | 0.00 | 15055313.01 | 14878961.02 | 9272.54 | 02-DEC-16:11 | 9272.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.328552E+11 | 0.171765E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 8107022.96 | 8107022.96 | 9272.54 | 8611.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.834084E+10 | 0.428627E+10 | 17449.30 | 14186.83 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4184636.13 | 4184636.13 | 3538.60 | 12-JAN-16:13 | 3538.60 | 0.00 |
February | 0.00 | 0.00 | 20588112.82 | 19784612.24 | 13163.27 | 24-FEB-16:11 | 13163.27 | 0.00 |
March | 0.00 | 0.00 | 78626823.90 | 61016035.63 | 13571.38 | 24-MAR-15:11 | 13571.38 | 0.02 |
April | 0.00 | 0.00 | 0.107264E+10 | 0.632243E+09 | 14191.35 | 16-APR-21:51 | 10966.94 | 0.18 |
May | 0.00 | 0.00 | 0.217761E+10 | 0.952953E+09 | 14926.21 | 20-MAY-18:41 | 14926.21 | 0.49 |
June | 0.00 | 0.00 | 0.505256E+10 | 0.267344E+10 | 17554.20 | 26-JUN-08:11 | 9661.51 | 0.62 |
July | 0.00 | 0.00 | 0.627102E+10 | 0.330714E+10 | 16166.99 | 02-JUL-08:51 | 10340.58 | 0.66 |
August | 0.00 | 0.00 | 0.516133E+10 | 0.242410E+10 | 18154.08 | 03-AUG-07:51 | 9137.66 | 0.66 |
September | 0.00 | 0.00 | 0.272400E+10 | 0.132549E+10 | 14764.40 | 11-SEP-08:51 | 10367.64 | 0.48 |
October | 0.00 | 0.00 | 0.207853E+09 | 0.124678E+09 | 13510.89 | 29-OCT-15:11 | 13510.89 | 0.07 |
November | 0.00 | 0.00 | 45303084.42 | 34556605.27 | 13795.15 | 04-NOV-15:11 | 13795.15 | 0.01 |
December | 0.00 | 0.00 | 10801810.91 | 10630634.75 | 3521.72 | 17-DEC-19:04 | 3521.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.228265E+11 | 0.115702E+11 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 4184636.13 | 4184636.13 | 3521.72 | 3521.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.627102E+10 | 0.330714E+10 | 18154.08 | 14926.21 | 0.66 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.979773E+09 | 0.933885E+09 | 16467.18 | 28-MAR-13:25 | 16467.18 | 0.01 |
April | 0.00 | 0.00 | 0.855996E+10 | 0.467966E+10 | 37740.06 | 15-APR-13:15 | 29726.15 | 0.22 |
May | 0.00 | 0.00 | 0.189143E+11 | 0.834618E+10 | 27467.81 | 31-MAY-13:30 | 16136.72 | 0.61 |
June | 0.00 | 0.00 | 0.294654E+11 | 0.111319E+11 | 30912.92 | 26-JUN-12:30 | 18762.84 | 0.88 |
July | 0.00 | 0.00 | 0.376281E+11 | 0.143159E+11 | 32566.61 | 30-JUL-13:30 | 21605.76 | 0.98 |
August | 0.00 | 0.00 | 0.379572E+11 | 0.153701E+11 | 36282.75 | 22-AUG-13:30 | 24680.30 | 0.99 |
September | 0.00 | 0.00 | 0.290639E+11 | 0.165293E+11 | 43425.29 | 08-SEP-12:50 | 41047.20 | 0.66 |
October | 0.00 | 0.00 | 0.125311E+11 | 0.106119E+11 | 39816.39 | 20-OCT-13:00 | 39816.39 | 0.15 |
November | 0.00 | 0.00 | 0.346745E+10 | 0.278502E+10 | 37641.83 | 04-NOV-13:00 | 37641.83 | 0.07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.178567E+12 | 0.847037E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.379572E+11 | 0.165293E+11 | 43425.29 | 41047.20 | 0.99 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 44630628.91 | 44630628.91 | 32388.77 | 14-JAN-09:02 | 32388.77 | 0.00 |
February | 0.00 | 0.00 | 0.111073E+09 | 92814280.23 | 69982.67 | 26-FEB-09:01 | 69982.67 | 0.01 |
March | 0.00 | 0.00 | 0.242101E+10 | 0.137139E+10 | 72458.10 | 24-MAR-18:01 | 72458.10 | 0.11 |
April | 0.00 | 0.00 | 0.986766E+10 | 0.601211E+10 | 79136.49 | 16-APR-21:51 | 60515.44 | 0.25 |
May | 0.00 | 0.00 | 0.260386E+11 | 0.146365E+11 | 83700.79 | 11-MAY-21:42 | 57152.38 | 0.53 |
June | 0.00 | 0.00 | 0.401033E+11 | 0.242005E+11 | 97515.32 | 26-JUN-08:11 | 52487.97 | 0.62 |
July | 0.00 | 0.00 | 0.438893E+11 | 0.258417E+11 | 88516.67 | 02-JUL-08:51 | 57768.04 | 0.58 |
August | 0.00 | 0.00 | 0.390342E+11 | 0.220814E+11 | 102557.12 | 03-AUG-07:51 | 48814.93 | 0.56 |
September | 0.00 | 0.00 | 0.243098E+11 | 0.139120E+11 | 81346.62 | 11-SEP-21:51 | 60687.31 | 0.52 |
October | 0.00 | 0.00 | 0.686074E+10 | 0.402674E+10 | 72514.66 | 12-OCT-18:03 | 72514.66 | 0.26 |
November | 0.00 | 0.00 | 0.303977E+10 | 0.123179E+10 | 71026.33 | 04-NOV-18:01 | 71026.33 | 0.15 |
December | 0.00 | 0.00 | 78645295.89 | 78645295.89 | 48763.20 | 03-DEC-09:01 | 48763.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.195799E+12 | 0.113530E+12 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 44630628.91 | 44630628.91 | 32388.77 | 32388.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.438893E+11 | 0.258417E+11 | 102557.12 | 72514.66 | 0.62 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5533385.63 | 5533385.63 | 3492.19 | 17-JAN-19:04 | 3492.19 | 0.00 |
February | 0.00 | 0.00 | 46494672.83 | 36564572.79 | 12256.01 | 24-FEB-09:01 | 12256.01 | 0.01 |
March | 0.00 | 0.00 | 0.202082E+09 | 0.130887E+09 | 12911.02 | 24-MAR-15:11 | 12911.02 | 0.06 |
April | 0.00 | 0.00 | 0.148922E+10 | 0.845911E+09 | 12905.59 | 26-APR-08:61 | 12905.59 | 0.27 |
May | 0.00 | 0.00 | 0.359694E+10 | 0.174593E+10 | 13484.06 | 11-MAY-15:12 | 9561.45 | 0.71 |
June | 0.00 | 0.00 | 0.656167E+10 | 0.343273E+10 | 14270.64 | 14-JUN-18:02 | 9058.59 | 0.86 |
July | 0.00 | 0.00 | 0.815833E+10 | 0.413801E+10 | 14860.32 | 20-JUL-08:62 | 8742.44 | 0.95 |
August | 0.00 | 0.00 | 0.715103E+10 | 0.339693E+10 | 15905.57 | 31-AUG-08:62 | 7720.08 | 0.93 |
September | 0.00 | 0.00 | 0.429816E+10 | 0.230241E+10 | 13236.78 | 10-SEP-08:61 | 10192.55 | 0.68 |
October | 0.00 | 0.00 | 0.563198E+09 | 0.329560E+09 | 12911.61 | 24-OCT-15:11 | 12911.61 | 0.16 |
November | 0.00 | 0.00 | 98710366.71 | 67803251.73 | 12906.61 | 04-NOV-15:11 | 12906.61 | 0.03 |
December | 0.00 | 0.00 | 16569518.88 | 16433351.38 | 7011.63 | 03-DEC-09:01 | 7011.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.321879E+11 | 0.164487E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 5533385.63 | 5533385.63 | 3492.19 | 3492.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.815833E+10 | 0.413801E+10 | 15905.57 | 12911.61 | 0.95 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3643118.96 | 3643118.96 | 3552.31 | 17-JAN-19:04 | 3552.31 | 0.00 |
February | 0.00 | 0.00 | 13419777.30 | 12620181.46 | 9554.93 | 24-FEB-09:01 | 9554.93 | 0.00 |
March | 0.00 | 0.00 | 65946591.40 | 40015708.87 | 10659.40 | 24-MAR-15:11 | 10659.40 | 0.02 |
April | 0.00 | 0.00 | 0.886680E+09 | 0.481915E+09 | 14151.50 | 18-APR-08:51 | 11702.32 | 0.17 |
May | 0.00 | 0.00 | 0.252152E+10 | 0.119593E+10 | 14544.65 | 29-MAY-08:51 | 11007.05 | 0.56 |
June | 0.00 | 0.00 | 0.517431E+10 | 0.274919E+10 | 17209.85 | 26-JUN-07:52 | 11152.27 | 0.66 |
July | 0.00 | 0.00 | 0.607266E+10 | 0.308323E+10 | 15247.31 | 27-JUL-08:51 | 10856.83 | 0.68 |
August | 0.00 | 0.00 | 0.500792E+10 | 0.233879E+10 | 17164.25 | 03-AUG-07:51 | 9517.49 | 0.68 |
September | 0.00 | 0.00 | 0.276211E+10 | 0.135867E+10 | 14476.37 | 11-SEP-08:51 | 11066.07 | 0.51 |
October | 0.00 | 0.00 | 0.133157E+09 | 65982614.96 | 11392.41 | 02-OCT-18:02 | 9627.43 | 0.06 |
November | 0.00 | 0.00 | 19403252.42 | 13120753.60 | 7558.35 | 04-NOV-08:62 | 7066.73 | 0.01 |
December | 0.00 | 0.00 | 6959789.75 | 6805890.17 | 4109.32 | 05-DEC-09:03 | 4109.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.226677E+11 | 0.113499E+11 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 3643118.96 | 3643118.96 | 3552.31 | 3552.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.607266E+10 | 0.308323E+10 | 17209.85 | 11702.32 | 0.68 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1696305.13 | 1580505.56 | 1991.91 | 12-JAN-16:11 | 1991.91 | 0.00 |
February | 0.00 | 0.00 | 16073696.48 | 15846020.14 | 3685.89 | 24-FEB-16:11 | 3685.89 | 0.00 |
March | 0.00 | 0.00 | 51630144.50 | 39762020.94 | 3685.93 | 23-MAR-18:01 | 3685.93 | 0.04 |
April | 0.00 | 0.00 | 0.463918E+09 | 0.304992E+09 | 3806.59 | 16-APR-08:61 | 2803.43 | 0.24 |
May | 0.00 | 0.00 | 0.867955E+09 | 0.461201E+09 | 4028.83 | 29-MAY-08:61 | 2702.45 | 0.58 |
June | 0.00 | 0.00 | 0.168557E+10 | 0.920811E+09 | 4186.79 | 25-JUN-08:61 | 2577.84 | 0.79 |
July | 0.00 | 0.00 | 0.214665E+10 | 0.115581E+10 | 4373.69 | 20-JUL-08:62 | 2297.11 | 0.92 |
August | 0.00 | 0.00 | 0.185886E+10 | 0.934935E+09 | 4640.44 | 31-AUG-08:62 | 2055.23 | 0.91 |
September | 0.00 | 0.00 | 0.104988E+10 | 0.603404E+09 | 4064.82 | 11-SEP-08:61 | 2672.25 | 0.58 |
October | 0.00 | 0.00 | 0.176791E+09 | 0.121295E+09 | 3685.95 | 24-OCT-15:11 | 3685.95 | 0.12 |
November | 0.00 | 0.00 | 33928164.18 | 25372344.63 | 3684.65 | 04-NOV-15:11 | 3684.65 | 0.02 |
December | 0.00 | 0.00 | 2663574.44 | 2550821.43 | 1083.20 | 02-DEC-16:11 | 1083.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.835561E+10 | 0.458756E+10 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 1696305.13 | 1580505.56 | 1083.20 | 1083.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.214665E+10 | 0.115581E+10 | 4640.44 | 3685.95 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 936354.80 | 877110.70 | 894.30 | 09-JAN-16:14 | 894.30 | 0.00 |
February | 0.00 | 0.00 | 3685287.45 | 3437974.18 | 3338.67 | 24-FEB-16:11 | 3338.67 | 0.00 |
March | 0.00 | 0.00 | 14111664.97 | 11268760.15 | 3472.78 | 24-MAR-15:11 | 3472.78 | 0.01 |
April | 0.00 | 0.00 | 0.281559E+09 | 0.175113E+09 | 3763.30 | 16-APR-21:51 | 2813.06 | 0.16 |
May | 0.00 | 0.00 | 0.563608E+09 | 0.269712E+09 | 4032.06 | 21-MAY-19:41 | 4032.06 | 0.45 |
June | 0.00 | 0.00 | 0.136580E+10 | 0.755803E+09 | 4660.44 | 26-JUN-08:11 | 2423.95 | 0.61 |
July | 0.00 | 0.00 | 0.168063E+10 | 0.916420E+09 | 4266.08 | 02-JUL-08:51 | 2640.72 | 0.67 |
August | 0.00 | 0.00 | 0.133705E+10 | 0.649335E+09 | 4862.23 | 03-AUG-07:51 | 2215.26 | 0.66 |
September | 0.00 | 0.00 | 0.669276E+09 | 0.346404E+09 | 4001.71 | 19-SEP-17:41 | 4001.71 | 0.43 |
October | 0.00 | 0.00 | 43348079.02 | 25933513.35 | 3417.66 | 24-OCT-15:11 | 3417.66 | 0.05 |
November | 0.00 | 0.00 | 11592869.54 | 8352622.32 | 3546.68 | 04-NOV-15:11 | 3546.68 | 0.01 |
December | 0.00 | 0.00 | 1943908.69 | 1836002.45 | 978.55 | 02-DEC-16:13 | 978.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.597355E+10 | 0.316449E+10 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 936354.80 | 877110.70 | 894.30 | 894.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168063E+10 | 0.916420E+09 | 4862.23 | 4032.06 | 0.67 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.159081E+09 | 0.157006E+09 | 17575.19 | 12-JAN-16:11 | 17575.19 | 0.00 |
February | 0.00 | 0.00 | 0.460721E+09 | 0.344682E+09 | 17390.38 | 17-FEB-16:11 | 17390.38 | 0.05 |
March | 0.00 | 0.00 | 0.942673E+09 | 0.623663E+09 | 17575.28 | 27-MAR-15:11 | 17575.28 | 0.13 |
April | 0.00 | 0.00 | 0.287565E+10 | 0.175988E+10 | 17984.36 | 16-APR-08:61 | 13630.87 | 0.32 |
May | 0.00 | 0.00 | 0.495906E+10 | 0.230011E+10 | 18664.11 | 29-MAY-08:61 | 13454.46 | 0.70 |
June | 0.00 | 0.00 | 0.816388E+10 | 0.403137E+10 | 20129.59 | 26-JUN-08:62 | 12338.14 | 0.83 |
July | 0.00 | 0.00 | 0.103061E+11 | 0.504051E+10 | 21127.84 | 20-JUL-08:62 | 10829.47 | 0.91 |
August | 0.00 | 0.00 | 0.100424E+11 | 0.493669E+10 | 22193.10 | 31-AUG-08:62 | 9839.45 | 0.90 |
September | 0.00 | 0.00 | 0.704826E+10 | 0.421737E+10 | 19288.09 | 11-SEP-08:61 | 12971.72 | 0.70 |
October | 0.00 | 0.00 | 0.293886E+10 | 0.204696E+10 | 17575.26 | 16-OCT-15:11 | 17575.26 | 0.34 |
November | 0.00 | 0.00 | 0.866785E+09 | 0.604954E+09 | 17563.12 | 12-NOV-16:11 | 17563.12 | 0.12 |
December | 0.00 | 0.00 | 0.385060E+09 | 0.362643E+09 | 17564.20 | 01-DEC-16:11 | 17564.20 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.491486E+11 | 0.264258E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 0.159081E+09 | 0.157006E+09 | 17390.38 | 9839.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103061E+11 | 0.504051E+10 | 22193.10 | 17575.28 | 0.91 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4.52 | 2772.17 | 14-JAN-08:30 | 124251.34 | 589193.59 | 19-JAN-09:03 |
February | 33.82 | 7891.47 | 08-FEB-23:10 | 112981.64 | 647695.93 | 02-FEB-09:03 |
March | 46.46 | 8973.50 | 21-MAR-15:11 | 35839.28 | 256966.96 | 09-MAR-16:11 |
April | 48.40 | 6640.64 | 25-APR-23:05 | 23433.82 | 246568.29 | 27-APR-15:11 |
May | 4.23 | 1659.25 | 26-MAY-04:10 | 5853.02 | 109375.62 | 02-MAY-08:05 |
June | 8.78 | 2148.33 | 06-JUN-00:30 | 1042.24 | 59249.29 | 01-JUN-15:14 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.37 | 25757.49 | 02-JUL-21:56 |
August | 0.06 | 68.89 | 31-AUG-10:35 | 83.69 | 40385.02 | 07-AUG-08:07 |
September | 33.74 | 6646.64 | 30-SEP-00:20 | 6112.30 | 139501.30 | 29-SEP-02:50 |
October | 105.87 | 7572.23 | 29-OCT-18:04 | 24385.13 | 172787.83 | 26-OCT-08:03 |
November | 66.68 | 3202.68 | 10-NOV-02:40 | 47906.88 | 505999.58 | 26-NOV-07:00 |
December | 7.14 | 4630.03 | 01-DEC-22:10 | 61143.30 | 267621.96 | 11-DEC-09:03 |
Annual Sum or Average | 29.84 | 36486.42 | ||||
Minimum of Months | 0.00 | 0.00 | 31.37 | 25757.49 | ||
Maximum of Months | 105.87 | 8973.50 | 124251.34 | 647695.93 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 818.57 | 48158.35 | 16-JAN-16:14 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1377.84 | 58855.88 | 22-FEB-16:14 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 4841.12 | 132794.92 | 25-MAR-15:11 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 31621.30 | 438696.75 | 16-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 70783.44 | 441837.05 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 173508.26 | 527063.62 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 233417.29 | 633079.56 | 26-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 203772.83 | 585012.21 | 03-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 94544.08 | 463519.03 | 06-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 15594.77 | 232882.90 | 20-OCT-15:11 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4739.52 | 122117.46 | 05-NOV-15:11 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1505.93 | 52868.26 | 20-DEC-19:04 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 70201.99 | 0.00 | ||||
Minimum of Months | 818.57 | 48158.35 | 0.00 | 0.00 | ||
Maximum of Months | 233417.29 | 633079.56 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31396.90 | 64917.43 | 31-JAN-07:54 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 32007.71 | 65291.78 | 16-FEB-07:57 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 31722.92 | 65156.66 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30540.62 | 63294.21 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28815.39 | 60304.64 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 27000.51 | 56403.26 | 01-JUN-06:52 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25550.06 | 52682.97 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24922.88 | 50656.60 | 01-AUG-06:53 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25229.19 | 51768.28 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26410.29 | 55067.57 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28147.40 | 58917.49 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 29965.07 | 62374.00 | 29-DEC-07:58 |
Annual Sum or Average | 0.00 | 28454.89 | ||||
Minimum of Months | 0.00 | 0.00 | 24922.88 | 50656.60 | ||
Maximum of Months | 0.00 | 0.00 | 32007.71 | 65291.78 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.70 | 1299.30 | 02-JAN-16:11 | 0.92 |
February | 0.236042E+10 | 0.70 | 1299.30 | 01-FEB-09:04 | 0.93 |
March | 0.261333E+10 | 0.70 | 1299.30 | 05-MAR-19:03 | 0.92 |
April | 0.252903E+10 | 0.70 | 1299.30 | 15-APR-21:51 | 0.91 |
May | 0.261333E+10 | 0.70 | 1299.30 | 03-MAY-19:01 | 0.92 |
June | 0.252903E+10 | 0.70 | 1299.30 | 06-JUN-20:01 | 0.91 |
July | 0.261333E+10 | 0.70 | 1299.30 | 01-JUL-18:07 | 0.91 |
August | 0.261333E+10 | 0.70 | 1299.30 | 01-AUG-21:54 | 0.91 |
September | 0.252903E+10 | 0.70 | 1299.30 | 02-SEP-21:51 | 0.91 |
October | 0.261333E+10 | 0.70 | 1299.30 | 15-OCT-18:02 | 0.92 |
November | 0.252903E+10 | 0.70 | 1299.30 | 03-NOV-16:12 | 0.92 |
December | 0.261333E+10 | 0.70 | 1299.30 | 01-DEC-16:11 | 0.92 |
Annual Sum or Average | 0.307698E+11 | 0.70 | |||
Minimum of Months | 0.236042E+10 | 0.70 | 1299.30 | 0.91 | |
Maximum of Months | 0.261333E+10 | 0.70 | 1299.30 | 0.93 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.393878E+11 | 0.94 | 21331.95 | 02-JAN-19:50 | 1.18 |
February | 0.358700E+11 | 0.95 | 21372.10 | 07-FEB-19:40 | 1.18 |
March | 0.406371E+11 | 0.96 | 21369.90 | 29-MAR-19:10 | 1.17 |
April | 0.399182E+11 | 0.96 | 23414.83 | 18-APR-21:10 | 1.23 |
May | 0.420523E+11 | 0.97 | 24864.07 | 31-MAY-21:20 | 1.28 |
June | 0.418160E+11 | 0.98 | 27136.30 | 26-JUN-21:20 | 1.35 |
July | 0.435037E+11 | 0.99 | 26211.01 | 03-JUL-21:20 | 1.32 |
August | 0.433941E+11 | 0.99 | 26089.64 | 04-AUG-21:10 | 1.31 |
September | 0.411501E+11 | 0.98 | 26081.13 | 08-SEP-21:10 | 1.32 |
October | 0.412988E+11 | 0.97 | 21428.52 | 04-OCT-19:10 | 1.17 |
November | 0.391768E+11 | 0.96 | 21430.00 | 03-NOV-19:00 | 1.18 |
December | 0.396943E+11 | 0.95 | 21372.34 | 28-DEC-20:00 | 1.18 |
Annual Sum or Average | 0.487899E+12 | 0.97 | |||
Minimum of Months | 0.358700E+11 | 0.94 | 21331.95 | 1.17 | |
Maximum of Months | 0.435037E+11 | 0.99 | 27136.30 | 1.35 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:05 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:10 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:10 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:10 | 0.28 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:10 | 0.28 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:05 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.28 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:10 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:10 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:10 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.20 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.20 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.20 | 612.92 | 01-AUG-06:05 | 0.28 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.28 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.20 | 612.92 | 0.28 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.330112E+09 | 0.53 | 674.65 | 01-JAN-09:02 | 0.60 |
February | 0.249099E+09 | 0.48 | 674.65 | 01-FEB-09:01 | 0.61 |
March | 0.173073E+09 | 0.43 | 674.65 | 01-MAR-09:01 | 0.60 |
April | 0.160359E+09 | 0.46 | 674.65 | 01-APR-08:61 | 0.60 |
May | 0.159681E+09 | 0.48 | 674.65 | 01-MAY-15:12 | 0.60 |
June | 0.268800E+09 | 0.53 | 674.65 | 01-JUN-08:62 | 0.60 |
July | 0.330937E+09 | 0.55 | 674.65 | 01-JUL-08:62 | 0.60 |
August | 0.294764E+09 | 0.55 | 674.65 | 01-AUG-08:61 | 0.60 |
September | 0.207932E+09 | 0.50 | 674.65 | 01-SEP-08:62 | 0.60 |
October | 0.115914E+09 | 0.43 | 674.65 | 01-OCT-15:11 | 0.60 |
November | 0.191448E+09 | 0.45 | 674.65 | 03-NOV-15:11 | 0.60 |
December | 0.291424E+09 | 0.50 | 674.65 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.277354E+10 | 0.49 | |||
Minimum of Months | 0.115914E+09 | 0.43 | 674.65 | 0.60 | |
Maximum of Months | 0.330937E+09 | 0.55 | 674.65 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.371634E+09 | 0.57 | 656.12 | 01-JAN-09:02 | 0.60 |
February | 0.287312E+09 | 0.51 | 656.12 | 01-FEB-09:01 | 0.61 |
March | 0.183140E+09 | 0.44 | 656.12 | 01-MAR-09:01 | 0.60 |
April | 0.134971E+09 | 0.42 | 656.12 | 01-APR-08:61 | 0.60 |
May | 0.107610E+09 | 0.38 | 656.12 | 01-MAY-15:12 | 0.60 |
June | 0.209856E+09 | 0.41 | 656.12 | 01-JUN-08:62 | 0.60 |
July | 0.247784E+09 | 0.40 | 656.12 | 01-JUL-08:51 | 0.60 |
August | 0.203809E+09 | 0.39 | 656.12 | 01-AUG-08:51 | 0.59 |
September | 0.140706E+09 | 0.40 | 656.12 | 01-SEP-08:51 | 0.60 |
October | 0.109489E+09 | 0.40 | 656.12 | 02-OCT-18:02 | 0.60 |
November | 0.208101E+09 | 0.47 | 656.12 | 03-NOV-16:12 | 0.60 |
December | 0.317500E+09 | 0.55 | 656.12 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.252191E+10 | 0.44 | |||
Minimum of Months | 0.107610E+09 | 0.38 | 656.12 | 0.59 | |
Maximum of Months | 0.371634E+09 | 0.57 | 656.12 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.462209E+09 | 0.25 | 817.76 | 19-JAN-05:10 | 0.61 |
February | 0.124164E+09 | 0.07 | 774.13 | 04-FEB-06:00 | 0.61 |
March | 51959213.15 | 0.05 | 569.53 | 28-MAR-13:25 | 0.60 |
April | 0.307201E+09 | 0.19 | 1133.02 | 15-APR-13:30 | 0.60 |
May | 0.689797E+09 | 0.45 | 889.34 | 06-MAY-13:00 | 0.60 |
June | 0.973464E+09 | 0.53 | 913.33 | 26-JUN-12:50 | 0.60 |
July | 0.120294E+10 | 0.59 | 972.15 | 30-JUL-13:30 | 0.60 |
August | 0.122777E+10 | 0.59 | 1080.94 | 29-AUG-13:30 | 0.60 |
September | 0.992012E+09 | 0.47 | 1323.14 | 07-SEP-13:00 | 0.60 |
October | 0.466699E+09 | 0.28 | 1230.80 | 20-OCT-13:00 | 0.60 |
November | 0.151206E+09 | 0.11 | 1170.14 | 04-NOV-13:00 | 0.60 |
December | 0.308445E+09 | 0.18 | 710.25 | 12-DEC-05:00 | 0.61 |
Annual Sum or Average | 0.695786E+10 | 0.31 | |||
Minimum of Months | 51959213.15 | 0.05 | 569.53 | 0.60 | |
Maximum of Months | 0.122777E+10 | 0.59 | 1323.14 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171654E+10 | 0.46 | 3643.68 | 01-JAN-16:11 | 0.60 |
February | 0.134435E+10 | 0.43 | 3643.68 | 01-FEB-09:01 | 0.61 |
March | 0.722374E+09 | 0.40 | 3643.68 | 01-MAR-09:01 | 0.60 |
April | 0.669465E+09 | 0.39 | 3643.68 | 01-APR-08:61 | 0.60 |
May | 0.109720E+10 | 0.35 | 3643.68 | 01-MAY-08:62 | 0.60 |
June | 0.165300E+10 | 0.37 | 3643.68 | 01-JUN-08:62 | 0.60 |
July | 0.175245E+10 | 0.35 | 3643.68 | 01-JUL-08:51 | 0.60 |
August | 0.152219E+10 | 0.34 | 3643.68 | 01-AUG-08:51 | 0.60 |
September | 0.105381E+10 | 0.36 | 3643.68 | 01-SEP-08:51 | 0.60 |
October | 0.511245E+09 | 0.40 | 3643.68 | 01-OCT-08:61 | 0.60 |
November | 0.834853E+09 | 0.42 | 3643.68 | 01-NOV-08:62 | 0.60 |
December | 0.130023E+10 | 0.43 | 3643.68 | 01-DEC-16:11 | 0.60 |
Annual Sum or Average | 0.141777E+11 | 0.39 | |||
Minimum of Months | 0.511245E+09 | 0.34 | 3643.68 | 0.60 | |
Maximum of Months | 0.175245E+10 | 0.46 | 3643.68 | 0.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.316283E+09 | 0.53 | 613.25 | 01-JAN-09:02 | 0.60 |
February | 0.241963E+09 | 0.48 | 613.25 | 01-FEB-09:01 | 0.61 |
March | 0.159597E+09 | 0.44 | 613.25 | 01-MAR-09:01 | 0.60 |
April | 0.145968E+09 | 0.47 | 613.25 | 01-APR-08:61 | 0.60 |
May | 0.163648E+09 | 0.51 | 613.25 | 01-MAY-08:62 | 0.60 |
June | 0.266780E+09 | 0.55 | 613.25 | 01-JUN-08:62 | 0.60 |
July | 0.316033E+09 | 0.57 | 613.25 | 01-JUL-08:62 | 0.60 |
August | 0.277309E+09 | 0.56 | 613.25 | 01-AUG-08:61 | 0.60 |
September | 0.201969E+09 | 0.52 | 613.25 | 01-SEP-08:62 | 0.60 |
October | 0.103810E+09 | 0.43 | 613.25 | 01-OCT-08:61 | 0.60 |
November | 0.179946E+09 | 0.46 | 613.25 | 03-NOV-15:11 | 0.60 |
December | 0.275322E+09 | 0.51 | 613.25 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.264863E+10 | 0.50 | |||
Minimum of Months | 0.103810E+09 | 0.43 | 613.25 | 0.60 | |
Maximum of Months | 0.316283E+09 | 0.57 | 613.25 | 0.61 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.360974E+09 | 0.57 | 597.18 | 01-JAN-09:02 | 0.60 |
February | 0.274519E+09 | 0.51 | 597.18 | 01-FEB-09:01 | 0.61 |
March | 0.169756E+09 | 0.43 | 597.18 | 01-MAR-09:01 | 0.60 |
April | 0.127042E+09 | 0.41 | 597.18 | 01-APR-08:61 | 0.60 |
May | 0.119188E+09 | 0.41 | 597.18 | 01-MAY-08:62 | 0.60 |
June | 0.214662E+09 | 0.43 | 597.18 | 01-JUN-08:62 | 0.60 |
July | 0.238989E+09 | 0.41 | 597.18 | 01-JUL-08:51 | 0.60 |
August | 0.196051E+09 | 0.41 | 597.18 | 01-AUG-08:51 | 0.60 |
September | 0.138017E+09 | 0.42 | 597.18 | 01-SEP-08:51 | 0.60 |
October | 0.101137E+09 | 0.40 | 597.18 | 01-OCT-08:61 | 0.60 |
November | 0.198914E+09 | 0.47 | 597.18 | 09-NOV-16:12 | 0.60 |
December | 0.303223E+09 | 0.55 | 597.18 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.244247E+10 | 0.45 | |||
Minimum of Months | 0.101137E+09 | 0.40 | 597.18 | 0.60 | |
Maximum of Months | 0.360974E+09 | 0.57 | 597.18 | 0.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105086E+09 | 0.56 | 175.35 | 01-JAN-09:02 | 0.60 |
February | 78330049.06 | 0.51 | 175.35 | 01-FEB-09:01 | 0.61 |
March | 53176757.33 | 0.45 | 175.35 | 01-MAR-09:01 | 0.60 |
April | 47541047.45 | 0.47 | 175.35 | 01-APR-08:61 | 0.60 |
May | 43582956.33 | 0.49 | 175.35 | 01-MAY-15:12 | 0.60 |
June | 72653517.74 | 0.53 | 175.35 | 01-JUN-08:62 | 0.60 |
July | 87200105.87 | 0.55 | 175.35 | 01-JUL-08:62 | 0.60 |
August | 75512470.25 | 0.55 | 175.35 | 01-AUG-08:61 | 0.59 |
September | 55018760.58 | 0.50 | 175.35 | 01-SEP-15:11 | 0.60 |
October | 35966464.02 | 0.43 | 175.35 | 01-OCT-15:11 | 0.60 |
November | 60387935.49 | 0.48 | 175.35 | 03-NOV-15:11 | 0.60 |
December | 88561458.93 | 0.53 | 175.35 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.803018E+09 | 0.50 | |||
Minimum of Months | 35966464.02 | 0.43 | 175.35 | 0.59 | |
Maximum of Months | 0.105086E+09 | 0.56 | 175.35 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115183E+09 | 0.58 | 170.15 | 01-JAN-09:02 | 0.60 |
February | 86686341.07 | 0.54 | 170.15 | 01-FEB-09:01 | 0.61 |
March | 56809831.97 | 0.47 | 170.15 | 01-MAR-09:01 | 0.60 |
April | 40552110.21 | 0.42 | 170.15 | 01-APR-08:61 | 0.60 |
May | 29640147.74 | 0.39 | 170.15 | 01-MAY-15:12 | 0.60 |
June | 59072484.61 | 0.42 | 170.15 | 01-JUN-08:62 | 0.60 |
July | 68626529.10 | 0.40 | 170.15 | 01-JUL-08:51 | 0.60 |
August | 53548074.33 | 0.40 | 170.15 | 01-AUG-08:51 | 0.59 |
September | 38098041.66 | 0.41 | 170.15 | 01-SEP-08:51 | 0.60 |
October | 34717494.77 | 0.40 | 170.15 | 02-OCT-18:02 | 0.60 |
November | 65622094.88 | 0.50 | 170.15 | 03-NOV-16:12 | 0.60 |
December | 96257136.62 | 0.58 | 170.15 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.744813E+09 | 0.46 | |||
Minimum of Months | 29640147.74 | 0.39 | 170.15 | 0.59 | |
Maximum of Months | 0.115183E+09 | 0.58 | 170.15 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.365603E+09 | 0.48 | 833.34 | 01-JAN-09:02 | 0.60 |
February | 0.275068E+09 | 0.46 | 833.34 | 01-FEB-09:01 | 0.61 |
March | 0.211154E+09 | 0.46 | 833.34 | 01-MAR-09:01 | 0.60 |
April | 0.219130E+09 | 0.48 | 833.34 | 01-APR-15:11 | 0.60 |
May | 0.219880E+09 | 0.50 | 833.34 | 01-MAY-08:62 | 0.60 |
June | 0.324335E+09 | 0.53 | 833.34 | 01-JUN-08:62 | 0.60 |
July | 0.391764E+09 | 0.54 | 833.34 | 01-JUL-08:62 | 0.60 |
August | 0.385378E+09 | 0.54 | 833.34 | 01-AUG-08:61 | 0.59 |
September | 0.321066E+09 | 0.52 | 833.34 | 01-SEP-08:62 | 0.60 |
October | 0.200803E+09 | 0.48 | 833.34 | 01-OCT-08:61 | 0.60 |
November | 0.225676E+09 | 0.45 | 833.34 | 01-NOV-15:12 | 0.60 |
December | 0.332887E+09 | 0.50 | 833.34 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.347274E+10 | 0.49 | |||
Minimum of Months | 0.200803E+09 | 0.45 | 833.34 | 0.59 | |
Maximum of Months | 0.391764E+09 | 0.54 | 833.34 | 0.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.478914E+09 | 0.435332E+09 | 1999.40 | 31-JAN-07:40 | 1817.45 | 1817.45 | 46.74 | 9.92 |
February | 0.535936E+09 | 0.487166E+09 | 2366.43 | 02-FEB-07:10 | 2151.08 | 2151.08 | 45.98 | 10.62 |
March | 28725641.92 | 26111608.51 | 94.57 | 17-MAR-15:11 | 85.96 | 85.96 | 36.31 | 2.56 |
April | 13523369.79 | 12292743.13 | 92.06 | 27-APR-15:11 | 83.69 | 83.69 | 36.65 | 2.53 |
May | 2239125.74 | 2035365.30 | 26.02 | 03-MAY-03:10 | 23.65 | 23.65 | 44.54 | 1.29 |
June | 368073.89 | 334579.17 | 8.90 | 06-JUN-08:06 | 8.09 | 8.09 | 47.80 | 0.68 |
July | 10990.47 | 9990.34 | 5.08 | 22-JUL-21:37 | 4.62 | 4.62 | 46.91 | 0.47 |
August | 26231.02 | 23844.00 | 7.11 | 18-AUG-08:54 | 6.46 | 6.46 | 44.70 | 0.59 |
September | 2881730.88 | 2619493.37 | 50.95 | 29-SEP-02:40 | 46.31 | 46.31 | 40.37 | 1.86 |
October | 13711631.48 | 12463873.01 | 61.30 | 23-OCT-08:03 | 55.72 | 55.72 | 46.10 | 2.05 |
November | 84241200.76 | 76575251.50 | 1626.90 | 26-NOV-07:10 | 1478.85 | 1478.85 | 46.83 | 9.12 |
December | 76744239.68 | 69760513.87 | 174.12 | 11-DEC-09:03 | 158.27 | 158.27 | 41.36 | 3.43 |
Annual Sum or Average | 0.123732E+10 | 0.112473E+10 | ||||||
Minimum of Months | 10990.47 | 9990.34 | 5.08 | 4.62 | 4.62 | 36.31 | 0.47 | |
Maximum of Months | 0.535936E+09 | 0.487166E+09 | 2366.43 | 2151.08 | 2151.08 | 47.80 | 10.62 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 82876.80 | 75335.01 | 19.68 | 02-JAN-19:04 | 17.88 | 17.88 | 6.72 | 2.11 |
February | 242335.40 | 220282.88 | 28.01 | 22-FEB-16:14 | 25.46 | 25.46 | 6.72 | 2.58 |
March | 2998104.45 | 2725276.94 | 58.79 | 24-MAR-15:11 | 53.44 | 53.44 | 6.72 | 3.85 |
April | 53919546.56 | 49012867.82 | 584.04 | 16-APR-18:03 | 530.89 | 530.89 | 6.72 | 11.45 |
May | 0.110620E+09 | 0.100553E+09 | 632.53 | 31-MAY-18:03 | 574.97 | 574.97 | 6.72 | 11.85 |
June | 0.371285E+09 | 0.337498E+09 | 908.60 | 26-JUN-18:03 | 825.92 | 825.92 | 6.72 | 13.84 |
July | 0.528290E+09 | 0.480215E+09 | 1217.15 | 26-JUL-18:03 | 1106.39 | 1106.39 | 6.72 | 15.65 |
August | 0.440402E+09 | 0.400325E+09 | 1053.12 | 03-AUG-18:03 | 957.29 | 957.29 | 6.72 | 14.73 |
September | 0.177828E+09 | 0.161646E+09 | 674.48 | 06-SEP-18:03 | 613.10 | 613.10 | 6.72 | 12.19 |
October | 15836849.83 | 14395696.50 | 203.04 | 20-OCT-15:00 | 184.57 | 184.57 | 6.72 | 7.10 |
November | 3215182.85 | 2922601.21 | 114.34 | 05-NOV-15:11 | 103.94 | 103.94 | 6.72 | 5.39 |
December | 179515.50 | 163179.59 | 22.65 | 07-DEC-19:04 | 20.59 | 20.59 | 6.72 | 2.29 |
Annual Sum or Average | 0.170490E+10 | 0.154975E+10 | ||||||
Minimum of Months | 82876.80 | 75335.01 | 19.68 | 17.88 | 17.88 | 6.72 | 2.11 | |
Maximum of Months | 0.528290E+09 | 0.480215E+09 | 1217.15 | 1106.39 | 1106.39 | 6.72 | 15.65 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.197061E+10 | 0.179128E+10 | 2888.97 | 01-JAN-00:05 | 2626.07 | 2626.07 | 6.73 | 25.81 |
February | 0.262583E+10 | 0.238688E+10 | 2888.97 | 01-FEB-16:13 | 2626.07 | 2626.07 | 6.72 | 25.81 |
March | 0.447699E+10 | 0.406958E+10 | 2888.97 | 01-MAR-00:05 | 2626.07 | 2626.07 | 6.73 | 25.81 |
April | 0.559309E+10 | 0.508412E+10 | 2888.97 | 01-APR-00:30 | 2626.07 | 2626.07 | 6.72 | 25.81 |
May | 0.754873E+10 | 0.686180E+10 | 2888.97 | 01-MAY-00:10 | 2626.07 | 2626.07 | 6.78 | 25.81 |
June | 0.737583E+10 | 0.670463E+10 | 2888.97 | 01-JUN-00:10 | 2626.07 | 2626.07 | 7.13 | 25.81 |
July | 0.773782E+10 | 0.703367E+10 | 2888.97 | 01-JUL-00:10 | 2626.07 | 2626.07 | 7.96 | 25.81 |
August | 0.773782E+10 | 0.703367E+10 | 2888.97 | 01-AUG-00:10 | 2626.07 | 2626.07 | 8.66 | 25.81 |
September | 0.708895E+10 | 0.644386E+10 | 2888.97 | 01-SEP-00:10 | 2626.07 | 2626.07 | 7.60 | 25.81 |
October | 0.584501E+10 | 0.531311E+10 | 2888.97 | 01-OCT-06:10 | 2626.07 | 2626.07 | 6.73 | 25.81 |
November | 0.408164E+10 | 0.371021E+10 | 2888.97 | 01-NOV-05:10 | 2626.07 | 2626.07 | 6.74 | 25.81 |
December | 0.353249E+10 | 0.321103E+10 | 2888.97 | 01-DEC-00:05 | 2626.07 | 2626.07 | 6.73 | 25.81 |
Annual Sum or Average | 0.656148E+11 | 0.596438E+11 | ||||||
Minimum of Months | 0.197061E+10 | 0.179128E+10 | 2888.97 | 2626.07 | 2626.07 | 6.72 | 25.81 | |
Maximum of Months | 0.773782E+10 | 0.703367E+10 | 2888.97 | 2626.07 | 2626.07 | 8.66 | 25.81 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 46.87 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 47.54 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 47.50 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.67 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 51.21 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 51.67 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.90 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.45 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.61 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 50.93 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 51.85 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 48.55 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.87 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.61 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4.52 | 2772.17 | 14-JAN-08:30 | 50.20 | 50.20 | 124251.34 | 589193.59 | 19-JAN-09:03 |
February | 33.82 | 7891.47 | 08-FEB-23:10 | 51.63 | 51.63 | 112981.64 | 647695.93 | 02-FEB-09:03 |
March | 46.46 | 8973.50 | 21-MAR-15:11 | 50.91 | 50.91 | 35839.28 | 256966.96 | 09-MAR-16:11 |
April | 48.40 | 6640.64 | 25-APR-23:05 | 52.20 | 52.20 | 23433.82 | 246568.29 | 27-APR-15:11 |
May | 4.23 | 1659.25 | 26-MAY-04:10 | 52.76 | 52.76 | 5853.02 | 109375.62 | 02-MAY-08:05 |
June | 8.78 | 2148.33 | 06-JUN-00:30 | 52.18 | 52.18 | 1042.24 | 59249.29 | 01-JUN-15:14 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 45.71 | 45.71 | 31.37 | 25757.49 | 02-JUL-21:56 |
August | 0.06 | 68.89 | 31-AUG-10:35 | 50.01 | 50.01 | 83.69 | 40385.02 | 07-AUG-08:07 |
September | 33.74 | 6646.64 | 30-SEP-00:20 | 51.71 | 51.71 | 6112.30 | 139501.30 | 29-SEP-02:50 |
October | 105.87 | 7572.23 | 29-OCT-18:04 | 51.43 | 51.43 | 24385.13 | 172787.83 | 26-OCT-08:03 |
November | 66.68 | 3202.68 | 10-NOV-02:40 | 49.98 | 49.98 | 47906.88 | 505999.58 | 26-NOV-07:00 |
December | 7.14 | 4630.03 | 01-DEC-22:10 | 50.28 | 50.28 | 61143.30 | 267621.96 | 11-DEC-09:03 |
Annual Sum or Average | 29.84 | 36486.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.71 | 45.71 | 31.37 | 25757.49 | ||
Maximum of Months | 105.87 | 8973.50 | 52.76 | 52.76 | 124251.34 | 647695.93 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 818.57 | 48158.35 | 16-JAN-16:14 | 7.14 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1377.84 | 58855.88 | 22-FEB-16:14 | 7.24 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 4841.12 | 132794.92 | 25-MAR-15:11 | 7.93 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 31621.30 | 438696.75 | 16-APR-18:03 | 10.76 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 70783.44 | 441837.05 | 31-MAY-18:03 | 10.79 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 173508.26 | 527063.62 | 26-JUN-18:03 | 11.57 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 233417.29 | 633079.56 | 26-JUL-18:03 | 12.56 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 203772.83 | 585012.21 | 03-AUG-18:03 | 12.11 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 94544.08 | 463519.03 | 06-SEP-18:03 | 10.99 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 15594.77 | 232882.90 | 20-OCT-15:11 | 8.85 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4739.52 | 122117.46 | 05-NOV-15:11 | 7.83 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1505.93 | 52868.26 | 20-DEC-19:04 | 7.19 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 70201.99 | 0.00 | ||||||
Minimum of Months | 818.57 | 48158.35 | 7.14 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 233417.29 | 633079.56 | 12.56 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 46.87 | 59.67 | 31396.90 | 64917.43 | 31-JAN-07:54 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 47.54 | 59.51 | 32007.71 | 65291.78 | 16-FEB-07:57 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 47.50 | 59.54 | 31722.92 | 65156.66 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.67 | 59.16 | 30540.62 | 63294.21 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 51.21 | 59.35 | 28815.39 | 60304.64 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 51.67 | 59.19 | 27000.51 | 56403.26 | 01-JUN-06:52 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.90 | 58.87 | 25550.06 | 52682.97 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.45 | 59.16 | 24922.88 | 50656.60 | 01-AUG-06:53 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.61 | 59.38 | 25229.19 | 51768.28 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 50.93 | 58.36 | 26410.29 | 55067.57 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 51.85 | 59.29 | 28147.40 | 58917.49 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 48.55 | 59.33 | 29965.07 | 62374.00 | 29-DEC-07:58 |
Annual Sum or Average | 0.00 | 28454.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.87 | 58.36 | 24922.88 | 50656.60 | ||
Maximum of Months | 0.00 | 0.00 | 52.61 | 59.67 | 32007.71 | 65291.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.215720E+12 | 0.00 | 0.167911E+09 | 0.393878E+11 | 0.00 | 0.00 |
February | 0.196398E+12 | 0.00 | 0.206656E+09 | 0.358700E+11 | 0.00 | 0.00 |
March | 0.632100E+11 | 0.00 | 0.370370E+10 | 0.406371E+11 | 0.00 | 0.00 |
April | 0.485592E+11 | 0.00 | 0.465049E+11 | 0.399182E+11 | 0.00 | 0.00 |
May | 0.149187E+11 | 0.00 | 0.112684E+12 | 0.420523E+11 | 0.00 | 0.00 |
June | 0.235506E+10 | 0.00 | 0.315828E+12 | 0.418160E+11 | 0.00 | 0.00 |
July | 47276591.34 | 0.00 | 0.458684E+12 | 0.435037E+11 | 0.00 | 0.00 |
August | 0.177123E+09 | 0.00 | 0.395247E+12 | 0.433941E+11 | 0.00 | 0.00 |
September | 0.139539E+11 | 0.00 | 0.151987E+12 | 0.411501E+11 | 0.00 | 0.00 |
October | 0.559075E+11 | 0.00 | 0.116608E+11 | 0.412988E+11 | 0.00 | 0.00 |
November | 0.815835E+11 | 0.00 | 0.841698E+09 | 0.391768E+11 | 0.00 | 0.00 |
December | 0.803040E+11 | 0.00 | 0.304193E+09 | 0.396943E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.773134E+12 | 0.00 | 0.149782E+13 | 0.487899E+12 | 0.00 | 0.00 |
Minimum of Months | 47276591.34 | 0.00 | 0.167911E+09 | 0.358700E+11 | 0.00 | 0.00 |
Maximum of Months | 0.215720E+12 | 0.00 | 0.458684E+12 | 0.435037E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.186607E+11 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
February | 0.135465E+11 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
March | 0.231282E+10 | 0.00 | 0.189758E+09 | 0.261333E+10 | 0.00 | 0.00 |
April | 0.426893E+09 | 0.00 | 0.309722E+10 | 0.252903E+10 | 0.00 | 0.00 |
May | 8656.04 | 0.00 | 0.701504E+10 | 0.261333E+10 | 0.00 | 0.00 |
June | 14051.61 | 0.00 | 0.232110E+11 | 0.252903E+10 | 0.00 | 0.00 |
July | 13109.94 | 0.00 | 0.350577E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 14202.02 | 0.00 | 0.286108E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 295126.54 | 0.00 | 0.103796E+11 | 0.252903E+10 | 0.00 | 0.00 |
October | 21127479.67 | 0.00 | 0.596936E+09 | 0.261333E+10 | 0.00 | 0.00 |
November | 0.419542E+10 | 0.00 | 22232930.82 | 0.252903E+10 | 0.00 | 0.00 |
December | 0.672913E+10 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.458929E+11 | 0.00 | 0.108180E+12 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 8656.04 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.186607E+11 | 0.00 | 0.350577E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.393878E+11 | 0.167911E+09 | 0.215720E+12 | 0.461604E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358700E+11 | 0.206656E+09 | 0.196398E+12 | 0.268650E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.406371E+11 | 0.370370E+10 | 0.632100E+11 | 0.234994E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399182E+11 | 0.465049E+11 | 0.485592E+11 | 0.874771E+11 | 0.371437E+10 | 0.00 | 0.00 | 0.00 |
May | 0.420523E+11 | 0.112684E+12 | 0.149187E+11 | 0.684843E+09 | 0.321408E+10 | 0.00 | 0.00 | 0.00 |
June | 0.418160E+11 | 0.315828E+12 | 0.235506E+10 | 0.908355E+09 | 0.323920E+11 | 0.00 | 0.00 | 0.00 |
July | 0.435037E+11 | 0.458684E+12 | 47276591.34 | 0.492711E+09 | 0.387859E+11 | 0.00 | 0.00 | 0.00 |
August | 0.433941E+11 | 0.395247E+12 | 0.177123E+09 | 0.937171E+09 | 0.340526E+11 | 0.00 | 0.00 | 0.00 |
September | 0.411501E+11 | 0.151987E+12 | 0.139539E+11 | 0.548555E+10 | 0.553276E+10 | 0.00 | 0.00 | 0.00 |
October | 0.412988E+11 | 0.116608E+11 | 0.559075E+11 | 0.303381E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.391768E+11 | 0.841698E+09 | 0.815835E+11 | 0.220056E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396943E+11 | 0.304193E+09 | 0.803040E+11 | 0.471611E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487899E+12 | 0.149782E+13 | 0.773134E+12 | 0.178324E+13 | 0.117692E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358700E+11 | 0.167911E+09 | 47276591.34 | 0.492711E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.435037E+11 | 0.458684E+12 | 0.215720E+12 | 0.471611E+12 | 0.387859E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.00 | 0.186607E+11 | 0.647634E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.00 | 0.135465E+11 | 0.482798E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.189758E+09 | 0.231282E+10 | 0.495162E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.309722E+10 | 0.426893E+09 | 0.307317E+11 | 0.620970E+09 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.701504E+10 | 8656.04 | 0.100652E+11 | 0.553551E+09 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.232110E+11 | 14051.61 | 0.332436E+10 | 0.593425E+10 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.350577E+11 | 13109.94 | 0.466310E+09 | 0.710450E+10 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.286108E+11 | 14202.02 | 0.115040E+10 | 0.619463E+10 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.103796E+11 | 295126.54 | 0.105810E+11 | 0.140911E+10 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.596936E+09 | 21127479.67 | 0.299997E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 22232930.82 | 0.419542E+10 | 0.451184E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.00 | 0.672913E+10 | 0.681238E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.108180E+12 | 0.458929E+11 | 0.362120E+12 | 0.218170E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.00 | 8656.04 | 0.466310E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.350577E+11 | 0.186607E+11 | 0.681238E+11 | 0.710450E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.393878E+11 | 0.215720E+12 | 0.167911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358700E+11 | 0.196398E+12 | 0.206656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.406371E+11 | 0.632100E+11 | 0.370370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399182E+11 | 0.485592E+11 | 0.465049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420523E+11 | 0.149187E+11 | 0.112684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.418160E+11 | 0.235506E+10 | 0.315828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.435037E+11 | 47276591.34 | 0.458684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.433941E+11 | 0.177123E+09 | 0.395247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.411501E+11 | 0.139539E+11 | 0.151987E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.412988E+11 | 0.559075E+11 | 0.116608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.391768E+11 | 0.815835E+11 | 0.841698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396943E+11 | 0.803040E+11 | 0.304193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487899E+12 | 0.773134E+12 | 0.149782E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358700E+11 | 47276591.34 | 0.167911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.435037E+11 | 0.215720E+12 | 0.458684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.186607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.135465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.231282E+10 | 0.189758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.426893E+09 | 0.309722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 8656.04 | 0.701504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 14051.61 | 0.232110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 13109.94 | 0.350577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 14202.02 | 0.286108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 295126.54 | 0.103796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 21127479.67 | 0.596936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.419542E+10 | 22232930.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.672913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.458929E+11 | 0.108180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 8656.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.186607E+11 | 0.350577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.562801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
February | 0.528465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
March | 0.453259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.414129E+11 | 0.00 | 0.00 | 0.00 | 0.359714E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
May | 0.364151E+11 | 0.00 | 0.00 | 0.00 | 0.528752E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
June | 0.209060E+11 | 0.00 | 0.00 | 0.00 | 0.407337E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
July | 0.131672E+11 | 0.00 | 0.00 | 0.00 | 0.694472E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
August | 0.172867E+11 | 28152686.61 | 0.00 | 101034.71 | 0.593339E+10 | 0.00 | 0.653786E+09 | 0.00 | 0.83 |
September | 0.214829E+11 | 11020284.98 | 0.00 | 5670133.68 | 0.391427E+09 | 0.00 | 0.114112E+11 | 0.00 | 0.79 |
October | 0.201257E+11 | 0.00 | 0.00 | 12983167.46 | 0.00 | 0.00 | 0.277916E+11 | 0.00 | 0.67 |
November | 0.271274E+11 | 0.00 | 0.00 | 9487759.06 | 0.00 | 0.00 | 0.194723E+11 | 0.00 | 0.63 |
December | 0.396740E+11 | 0.00 | 0.00 | 1291539.94 | 0.00 | 0.00 | 0.478852E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.392050E+12 | 39172971.59 | 0.00 | 29533634.84 | 0.182314E+11 | 0.00 | 0.641174E+11 | 0.00 | 0.70 |
Minimum of Months | 0.131672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.562801E+11 | 28152686.61 | 0.00 | 12983167.46 | 0.694472E+10 | 0.00 | 0.277916E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103529E+10 | 0.00 | 0.00 | 5885.99 | 0.00 | 0.415867E+10 | 17199330.29 | 0.00 | 0.99 |
February | 0.192264E+10 | 0.00 | 0.00 | 113547.88 | 0.00 | 0.287139E+10 | 0.114533E+09 | 0.00 | 0.99 |
March | 0.287388E+10 | 0.00 | 0.00 | 162718.67 | 0.00 | 0.120321E+10 | 0.126285E+09 | 0.00 | 1.04 |
April | 0.304649E+10 | 50788044.08 | 0.00 | 546106.26 | 534481.95 | 0.484818E+09 | 0.326330E+09 | 0.00 | 1.16 |
May | 0.314685E+10 | 44376536.65 | 0.00 | 532850.74 | 11340409.61 | 0.00 | 0.230551E+09 | 0.00 | 1.40 |
June | 0.155875E+10 | 0.436644E+09 | 0.00 | 1116281.37 | 33795465.72 | 0.00 | 0.386040E+09 | 0.00 | 1.45 |
July | 0.836586E+09 | 0.708976E+09 | 0.00 | 1323806.61 | 60896212.12 | 0.00 | 0.391899E+09 | 0.00 | 1.53 |
August | 0.102629E+10 | 0.579756E+09 | 0.00 | 2137198.12 | 94325582.76 | 0.00 | 0.664171E+09 | 0.00 | 1.54 |
September | 0.236124E+10 | 64895817.14 | 0.00 | 2754495.68 | 279201.55 | 11753488.04 | 0.735857E+09 | 0.00 | 1.48 |
October | 0.396693E+10 | 0.00 | 0.00 | 965064.95 | 0.00 | 50868624.24 | 0.506807E+09 | 0.00 | 1.17 |
November | 0.252555E+10 | 0.00 | 0.00 | 266886.66 | 0.00 | 0.165262E+10 | 0.177408E+09 | 0.00 | 1.07 |
December | 0.108348E+10 | 0.00 | 0.00 | 71353.26 | 0.00 | 0.296131E+10 | 78618377.86 | 0.00 | 0.99 |
Annual Sum or Average | 0.253840E+11 | 0.188544E+10 | 0.00 | 9996196.18 | 0.201171E+09 | 0.133946E+11 | 0.375570E+10 | 0.00 | 1.24 |
Minimum of Months | 0.836586E+09 | 0.00 | 0.00 | 5885.99 | 0.00 | 0.00 | 17199330.29 | 0.00 | 0.99 |
Maximum of Months | 0.396693E+10 | 0.708976E+09 | 0.00 | 2754495.68 | 94325582.76 | 0.415867E+10 | 0.735857E+09 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.577233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270879E+09 | 0.00 | 0.00 | 0.99 |
February | 0.531855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355972E+09 | 0.00 | 0.00 | 0.99 |
March | 0.486697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
April | 0.437610E+10 | 609383.85 | 0.00 | 27597.90 | 38015727.76 | 0.00 | 70690503.14 | 0.00 | 1.12 |
May | 0.384563E+10 | 1294415.75 | 0.00 | 38368.24 | 55481646.83 | 0.00 | 64497341.51 | 0.00 | 1.38 |
June | 0.194963E+10 | 83129232.75 | 0.00 | 259153.26 | 0.354459E+09 | 0.00 | 0.295472E+09 | 0.00 | 1.36 |
July | 0.101151E+10 | 0.236079E+09 | 0.00 | 359917.72 | 0.510232E+09 | 0.00 | 0.402106E+09 | 0.00 | 1.41 |
August | 0.127908E+10 | 0.148805E+09 | 0.00 | 452678.15 | 0.491578E+09 | 0.00 | 0.646951E+09 | 0.00 | 1.41 |
September | 0.302904E+10 | 2656294.31 | 0.00 | 376661.85 | 40557446.23 | 0.00 | 0.504067E+09 | 0.00 | 1.32 |
October | 0.512292E+10 | 0.00 | 0.00 | 865.94 | 0.00 | 0.00 | 9557612.84 | 0.00 | 1.12 |
November | 0.498024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20898391.83 | 0.00 | 0.00 | 1.06 |
December | 0.463000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144410E+09 | 0.00 | 0.00 | 0.99 |
Annual Sum or Average | 0.461820E+11 | 0.472573E+09 | 0.00 | 1515243.07 | 0.149032E+10 | 0.792160E+09 | 0.199334E+10 | 0.00 | 1.18 |
Minimum of Months | 0.101151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
Maximum of Months | 0.577233E+10 | 0.236079E+09 | 0.00 | 452678.15 | 0.510232E+09 | 0.355972E+09 | 0.646951E+09 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16311084.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938860E+09 | 0.00 | 0.00 | 0.06 |
February | 39381856.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799826E+09 | 0.00 | 0.00 | 0.04 |
March | 59629800.89 | 0.00 | 0.00 | 0.00 | 0.00 | 47547507.31 | 0.00 | 0.00 | 0.01 |
April | 59242247.64 | 7759210.95 | 0.00 | 259046.43 | 0.00 | 0.00 | 0.106440E+09 | 0.00 | 0.03 |
May | 26628755.63 | 12972695.07 | 0.00 | 877414.21 | 0.00 | 0.00 | 0.373713E+09 | 0.00 | 0.08 |
June | 9020435.02 | 0.185425E+09 | 0.00 | 1544959.53 | 0.00 | 0.00 | 0.464224E+09 | 0.00 | 0.20 |
July | 0.00 | 0.343611E+09 | 0.00 | 1753339.26 | 0.00 | 0.00 | 0.480226E+09 | 0.00 | 0.26 |
August | 0.00 | 0.275536E+09 | 0.00 | 2126269.42 | 0.00 | 0.00 | 0.690313E+09 | 0.00 | 0.26 |
September | 18838193.74 | 16846506.84 | 0.00 | 1832507.48 | 0.00 | 0.00 | 0.620856E+09 | 0.00 | 0.15 |
October | 70527217.33 | 0.00 | 0.00 | 87345.66 | 0.00 | 0.00 | 60868587.65 | 0.00 | 0.01 |
November | 56187668.64 | 0.00 | 0.00 | 32391.26 | 0.00 | 0.139111E+09 | 24605577.69 | 0.00 | 0.02 |
December | 28988650.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319062E+09 | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.384756E+09 | 0.842151E+09 | 0.00 | 8513273.24 | 0.00 | 0.224441E+10 | 0.282125E+10 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 70527217.33 | 0.343611E+09 | 0.00 | 2126269.42 | 0.00 | 0.938860E+09 | 0.690313E+09 | 0.00 | 0.26 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 98029861.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370460E+10 | 0.00 | 0.00 | 0.51 |
February | 0.592195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297844E+10 | 0.00 | 0.00 | 0.51 |
March | 0.156337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149912E+10 | 0.00 | 0.00 | 0.53 |
April | 0.244469E+10 | 0.00 | 0.00 | 0.00 | 24304445.73 | 0.353426E+09 | 0.00 | 0.00 | 0.58 |
May | 0.246043E+10 | 0.00 | 0.00 | 0.00 | 35725740.96 | 0.00 | 0.00 | 0.00 | 0.71 |
June | 0.141254E+10 | 0.00 | 0.00 | 0.00 | 0.275222E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.889657E+09 | 0.00 | 0.00 | 0.00 | 0.469227E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.121218E+10 | 0.00 | 0.00 | 0.00 | 0.402798E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 0.222290E+10 | 0.00 | 0.00 | 0.00 | 27191792.28 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.322956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.181132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133560E+10 | 0.00 | 0.00 | 0.54 |
December | 0.194132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281012E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.181310E+11 | 0.00 | 0.00 | 0.00 | 0.123447E+10 | 0.126813E+11 | 0.00 | 0.00 | 0.61 |
Minimum of Months | 98029861.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.322956E+10 | 0.00 | 0.00 | 0.00 | 0.469227E+09 | 0.370460E+10 | 0.00 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.102613E+09 | 0.00 | 0.00 | 0.737459E+11 | 0.00 | 12.16 |
February | 0.00 | 0.00 | 0.00 | 92794662.96 | 0.00 | 0.00 | 0.684660E+11 | 0.00 | 12.23 |
March | 0.00 | 0.00 | 0.00 | 0.101820E+09 | 0.00 | 0.00 | 0.631785E+11 | 0.00 | 13.24 |
April | 0.00 | 0.436997E+09 | 0.00 | 99405939.48 | 0.00 | 0.00 | 0.575384E+11 | 0.00 | 14.59 |
May | 0.00 | 0.684892E+09 | 0.00 | 0.110325E+09 | 0.00 | 0.00 | 0.512998E+11 | 0.00 | 18.38 |
June | 0.00 | 0.569961E+10 | 0.00 | 82217329.02 | 0.00 | 0.00 | 0.286054E+11 | 0.00 | 18.05 |
July | 0.00 | 0.107532E+11 | 0.00 | 66135595.43 | 0.00 | 0.00 | 0.172745E+11 | 0.00 | 18.76 |
August | 0.00 | 0.877932E+10 | 0.00 | 80184936.86 | 0.00 | 0.00 | 0.247330E+11 | 0.00 | 18.95 |
September | 0.00 | 0.526513E+09 | 0.00 | 0.108448E+09 | 0.00 | 0.00 | 0.468164E+11 | 0.00 | 17.60 |
October | 0.00 | 0.00 | 0.00 | 0.101869E+09 | 0.00 | 0.00 | 0.679858E+11 | 0.00 | 14.61 |
November | 0.00 | 0.00 | 0.00 | 98777733.54 | 0.00 | 0.00 | 0.643575E+11 | 0.00 | 13.53 |
December | 0.00 | 0.00 | 0.00 | 0.103381E+09 | 0.00 | 0.00 | 0.602098E+11 | 0.00 | 12.29 |
Annual Sum or Average | 0.00 | 0.268805E+11 | 0.00 | 0.114797E+10 | 0.00 | 0.00 | 0.624211E+12 | 0.00 | 15.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 66135595.43 | 0.00 | 0.00 | 0.172745E+11 | 0.00 | 12.16 |
Maximum of Months | 0.00 | 0.107532E+11 | 0.00 | 0.110325E+09 | 0.00 | 0.00 | 0.737459E+11 | 0.00 | 18.95 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.420037E+11 | 0.00 | 0.00 | 6256.60 | 0.00 | 0.236037E+10 | 0.160335E+09 | 0.00 | 3.00 |
February | 0.395587E+11 | 0.00 | 0.00 | 232521.70 | 0.00 | 0.109024E+10 | 0.115887E+10 | 0.00 | 3.00 |
March | 0.329266E+11 | 0.00 | 0.00 | 507902.35 | 0.00 | 0.00 | 0.293118E+10 | 0.00 | 3.14 |
April | 0.247092E+11 | 0.205672E+09 | 0.00 | 2225830.43 | 78905882.53 | 0.00 | 0.805130E+10 | 0.00 | 3.40 |
May | 0.166593E+11 | 0.114157E+09 | 0.00 | 3687849.20 | 0.304151E+09 | 0.00 | 0.121458E+11 | 0.00 | 4.19 |
June | 0.721451E+10 | 0.163556E+10 | 0.00 | 5046587.12 | 0.158698E+10 | 0.00 | 0.931966E+10 | 0.00 | 4.12 |
July | 0.287429E+10 | 0.297143E+10 | 0.00 | 5376339.82 | 0.252269E+10 | 0.00 | 0.753721E+10 | 0.00 | 4.26 |
August | 0.352786E+10 | 0.229005E+10 | 0.00 | 7537891.58 | 0.242626E+10 | 0.00 | 0.106578E+11 | 0.00 | 4.25 |
September | 0.127015E+11 | 0.234352E+09 | 0.00 | 7803808.55 | 84233620.79 | 0.00 | 0.133184E+11 | 0.00 | 4.00 |
October | 0.256439E+11 | 0.00 | 0.00 | 3457626.65 | 0.00 | 0.00 | 0.121673E+11 | 0.00 | 3.39 |
November | 0.316474E+11 | 0.00 | 0.00 | 1216081.01 | 0.00 | 0.233481E+09 | 0.496784E+10 | 0.00 | 3.21 |
December | 0.327612E+11 | 0.00 | 0.00 | 123186.34 | 0.00 | 0.195469E+10 | 0.460376E+09 | 0.00 | 3.00 |
Annual Sum or Average | 0.272228E+12 | 0.745121E+10 | 0.00 | 37221881.35 | 0.700323E+10 | 0.563878E+10 | 0.828761E+11 | 0.00 | 3.58 |
Minimum of Months | 0.287429E+10 | 0.00 | 0.00 | 6256.60 | 0.00 | 0.00 | 0.160335E+09 | 0.00 | 3.00 |
Maximum of Months | 0.420037E+11 | 0.297143E+10 | 0.00 | 7803808.55 | 0.252269E+10 | 0.236037E+10 | 0.133184E+11 | 0.00 | 4.26 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124773E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
February | 0.116799E+12 | 0.00 | 0.00 | 30060.35 | 0.00 | 0.00 | 0.362556E+09 | 0.00 | 1.22 |
March | 0.969950E+11 | 0.00 | 0.00 | 539433.08 | 0.00 | 0.00 | 0.349219E+10 | 0.00 | 1.27 |
April | 0.772780E+11 | 49741093.38 | 0.00 | 7061284.34 | 0.747747E+09 | 0.00 | 0.145394E+11 | 0.00 | 1.38 |
May | 0.453907E+11 | 47157949.57 | 0.00 | 15303187.78 | 0.112509E+10 | 0.00 | 0.353401E+11 | 0.00 | 1.70 |
June | 0.199777E+11 | 0.245186E+10 | 0.00 | 27891886.92 | 0.660204E+10 | 0.00 | 0.264123E+11 | 0.00 | 1.68 |
July | 0.634655E+10 | 0.584378E+10 | 0.00 | 30167373.56 | 0.963962E+10 | 0.00 | 0.228754E+11 | 0.00 | 1.74 |
August | 0.800137E+10 | 0.427426E+10 | 0.00 | 39483214.15 | 0.903173E+10 | 0.00 | 0.318971E+11 | 0.00 | 1.73 |
September | 0.353732E+11 | 0.284860E+09 | 0.00 | 31351181.03 | 0.607369E+09 | 0.00 | 0.376995E+11 | 0.00 | 1.63 |
October | 0.825196E+11 | 0.00 | 0.00 | 6011978.51 | 0.00 | 0.00 | 0.234440E+11 | 0.00 | 1.38 |
November | 0.930778E+11 | 0.00 | 0.00 | 1917212.95 | 0.00 | 0.00 | 0.101782E+11 | 0.00 | 1.30 |
December | 0.985766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
Annual Sum or Average | 0.805109E+12 | 0.129516E+11 | 0.00 | 0.159757E+09 | 0.277536E+11 | 0.00 | 0.206241E+12 | 0.00 | 1.46 |
Minimum of Months | 0.634655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
Maximum of Months | 0.124773E+12 | 0.584378E+10 | 0.00 | 39483214.15 | 0.963962E+10 | 0.00 | 0.376995E+11 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29848584.14 | 0.00 | 0.00 | 111453.97 | 0.00 | 0.235209E+10 | 5515184.10 | 0.00 | 0.34 |
February | 38091452.85 | 0.00 | 0.00 | 455554.79 | 0.00 | 0.198706E+10 | 33114692.07 | 0.00 | 0.34 |
March | 67325736.45 | 0.00 | 0.00 | 1301574.35 | 0.00 | 0.112895E+10 | 0.209230E+09 | 0.00 | 0.34 |
April | 48785513.02 | 19703709.28 | 0.00 | 4266489.08 | 0.00 | 0.645057E+09 | 0.486930E+09 | 0.00 | 0.34 |
May | 36450710.60 | 23153291.61 | 1897.14 | 8174533.34 | 0.00 | 84549429.42 | 0.841180E+09 | 1619.01 | 0.34 |
June | 14192051.63 | 0.278024E+09 | 30421.85 | 6412115.47 | 780536.80 | 35647585.64 | 0.419604E+09 | 1710.88 | 0.34 |
July | 1879081.66 | 0.458458E+09 | 127199.39 | 5105365.78 | 0.00 | 457929.87 | 0.204210E+09 | 9304.13 | 0.34 |
August | 31906.01 | 0.316241E+09 | 109861.54 | 6730101.49 | 898327.63 | 517866.46 | 0.337642E+09 | 4722.34 | 0.34 |
September | 28430520.43 | 51462288.26 | 13880.68 | 6784977.11 | 41310.73 | 0.178558E+09 | 0.625985E+09 | 2853.89 | 0.34 |
October | 67166197.93 | 0.00 | 0.00 | 2945434.68 | 0.00 | 0.742466E+09 | 0.501168E+09 | 0.00 | 0.34 |
November | 57179486.30 | 0.00 | 0.00 | 705969.16 | 0.00 | 0.125532E+10 | 0.174077E+09 | 0.00 | 0.34 |
December | 39111101.31 | 0.00 | 0.00 | 197070.76 | 0.00 | 0.155004E+10 | 6701367.64 | 0.00 | 0.34 |
Annual Sum or Average | 0.428492E+09 | 0.114704E+10 | 283260.59 | 43190640.01 | 1720175.15 | 0.996071E+10 | 0.384536E+10 | 20210.25 | 0.34 |
Minimum of Months | 31906.01 | 0.00 | 0.00 | 111453.97 | 0.00 | 457929.87 | 5515184.10 | 0.00 | 0.34 |
Maximum of Months | 67325736.45 | 0.458458E+09 | 127199.39 | 8174533.34 | 898327.63 | 0.235209E+10 | 0.841180E+09 | 9304.13 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3887197.83 | 0.00 | 0.00 | 58151.24 | 0.00 | 0.238106E+10 | 2284666.70 | 0.00 | 0.34 |
February | 20489401.34 | 0.00 | 0.00 | 204547.67 | 0.00 | 0.201904E+10 | 18744570.15 | 0.00 | 0.34 |
March | 64563011.39 | 0.00 | 0.00 | 611599.96 | 0.00 | 0.122070E+10 | 0.120768E+09 | 0.00 | 0.34 |
April | 96616478.35 | 18142391.91 | 13091.38 | 2574476.96 | 1542454.01 | 0.711369E+09 | 0.374340E+09 | 3463.40 | 0.34 |
May | 0.158962E+09 | 16374872.98 | 26377.61 | 5494698.24 | 6749043.44 | 91841781.50 | 0.713942E+09 | 3800.58 | 0.34 |
June | 89001409.49 | 0.246270E+09 | 215490.85 | 4242053.52 | 32312360.19 | 37538901.67 | 0.345017E+09 | 6593.81 | 0.34 |
July | 78522348.72 | 0.379425E+09 | 203573.69 | 3497381.07 | 78899155.92 | 243255.95 | 0.129365E+09 | 13167.68 | 0.34 |
August | 0.108878E+09 | 0.266460E+09 | 333354.13 | 4121830.59 | 50403508.79 | 635909.37 | 0.231246E+09 | 20187.72 | 0.34 |
September | 0.130490E+09 | 46134631.76 | 17543.69 | 3808663.65 | 5356615.70 | 0.212768E+09 | 0.492594E+09 | 5506.05 | 0.34 |
October | 96264501.45 | 0.00 | 0.00 | 1143369.74 | 0.00 | 0.893041E+09 | 0.323142E+09 | 0.00 | 0.34 |
November | 48761282.70 | 0.00 | 0.00 | 397633.41 | 0.00 | 0.135485E+10 | 83098468.18 | 0.00 | 0.34 |
December | 8475889.31 | 0.00 | 0.00 | 144608.65 | 0.00 | 0.158322E+10 | 4020555.33 | 0.00 | 0.34 |
Annual Sum or Average | 0.904912E+09 | 0.972806E+09 | 809431.36 | 26299014.70 | 0.175263E+09 | 0.105063E+11 | 0.283856E+10 | 52719.25 | 0.34 |
Minimum of Months | 3887197.83 | 0.00 | 0.00 | 58151.24 | 0.00 | 243255.95 | 2284666.70 | 0.00 | 0.34 |
Maximum of Months | 0.158962E+09 | 0.379425E+09 | 333354.13 | 5494698.24 | 78899155.92 | 0.238106E+10 | 0.713942E+09 | 20187.72 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.797634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246396E+09 | 0.00 | 0.00 | 0.02 |
February | 0.114415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.766519E+09 | 0.00 | 0.00 | 254532.57 | 0.00 | 0.00 | 0.132754E+09 | 0.00 | 0.02 |
April | 0.666456E+09 | 49923220.82 | 0.00 | 564195.99 | 0.00 | 0.00 | 0.320545E+09 | 0.00 | 0.02 |
May | 0.259102E+09 | 98457967.61 | 0.00 | 1082306.73 | 0.00 | 0.00 | 0.516519E+09 | 0.00 | 0.02 |
June | 0.212405E+09 | 0.372265E+09 | 0.00 | 779726.33 | 0.00 | 0.00 | 0.161676E+09 | 0.00 | 0.02 |
July | 12669287.73 | 0.597432E+09 | 0.00 | 419782.60 | 0.00 | 0.00 | 74735435.01 | 0.00 | 0.02 |
August | 0.00 | 0.504764E+09 | 0.00 | 655460.89 | 0.00 | 0.00 | 88358946.06 | 0.00 | 0.02 |
September | 0.250031E+09 | 83970805.92 | 0.00 | 1577662.71 | 0.00 | 0.00 | 0.475819E+09 | 0.00 | 0.02 |
October | 0.527451E+09 | 0.00 | 0.00 | 2207760.84 | 0.00 | 0.00 | 0.718902E+09 | 0.00 | 0.02 |
November | 0.896987E+09 | 0.00 | 0.00 | 557533.24 | 0.00 | 8034236.63 | 0.185151E+09 | 0.00 | 0.02 |
December | 0.622596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196456E+09 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.615600E+10 | 0.170681E+10 | 0.00 | 8098961.91 | 0.00 | 0.450886E+09 | 0.267446E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.114415E+10 | 0.597432E+09 | 0.00 | 2207760.84 | 0.00 | 0.246396E+09 | 0.718902E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.691102E+09 | 0.00 | 0.00 | 932935.79 | 0.00 | 0.310707E+11 | 0.619407E+09 | 0.00 | 0.39 |
February | 0.722557E+09 | 0.00 | 0.00 | 2558723.40 | 0.00 | 0.247129E+11 | 0.248404E+10 | 0.00 | 0.39 |
March | 0.113634E+10 | 0.00 | 0.00 | 14826683.46 | 0.00 | 0.947848E+10 | 0.845061E+10 | 0.00 | 0.39 |
April | 0.139981E+10 | 0.208233E+09 | 201040.75 | 36589671.13 | 58792765.79 | 0.222136E+10 | 0.124147E+11 | 10971.12 | 0.39 |
May | 0.217953E+10 | 0.175113E+09 | 0.00 | 85133147.41 | 0.138959E+09 | 19883666.74 | 0.108762E+11 | 0.00 | 0.39 |
June | 0.125288E+10 | 0.322354E+10 | 394694.29 | 62220067.31 | 0.557882E+09 | 9024449.84 | 0.512981E+10 | 644.51 | 0.39 |
July | 0.108961E+10 | 0.486317E+10 | 1994094.68 | 45166768.59 | 0.135465E+10 | 746009.34 | 0.173508E+10 | 15062.11 | 0.39 |
August | 0.153339E+10 | 0.330856E+10 | 1703750.80 | 52740262.11 | 0.992562E+09 | 1996279.71 | 0.308998E+10 | 27793.66 | 0.39 |
September | 0.180639E+10 | 0.572997E+09 | 541346.38 | 60243908.60 | 0.125192E+09 | 59865116.13 | 0.946298E+10 | 30204.06 | 0.39 |
October | 0.130577E+10 | 0.00 | 0.00 | 34982484.47 | 0.00 | 0.613493E+09 | 0.158638E+11 | 0.00 | 0.39 |
November | 0.990597E+09 | 0.00 | 0.00 | 15025135.19 | 0.00 | 0.113946E+11 | 0.777157E+10 | 0.00 | 0.39 |
December | 0.875890E+09 | 0.00 | 0.00 | 1440712.90 | 0.00 | 0.200763E+11 | 0.693283E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.149839E+11 | 0.123516E+11 | 4834926.89 | 0.411861E+09 | 0.322804E+10 | 0.996592E+11 | 0.785915E+11 | 84675.46 | 0.39 |
Minimum of Months | 0.691102E+09 | 0.00 | 0.00 | 932935.79 | 0.00 | 746009.34 | 0.619407E+09 | 0.00 | 0.38 |
Maximum of Months | 0.217953E+10 | 0.486317E+10 | 1994094.68 | 85133147.41 | 0.135465E+10 | 0.310707E+11 | 0.158638E+11 | 30204.06 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25036027.73 | 0.00 | 0.00 | 79457.66 | 0.00 | 0.235466E+10 | 7792317.55 | 0.00 | 0.34 |
February | 35573016.18 | 0.00 | 0.00 | 292104.91 | 0.00 | 0.198677E+10 | 36082488.14 | 0.00 | 0.34 |
March | 66652145.85 | 0.00 | 0.00 | 992341.79 | 0.00 | 0.110958E+10 | 0.229584E+09 | 0.00 | 0.34 |
April | 46603139.18 | 19703709.28 | 0.00 | 3615229.87 | 0.00 | 0.676745E+09 | 0.458076E+09 | 0.00 | 0.34 |
May | 20742992.67 | 23156807.76 | 0.00 | 8695104.55 | 0.00 | 66511761.53 | 0.874405E+09 | 0.00 | 0.34 |
June | 11333258.22 | 0.277891E+09 | 0.00 | 6753232.19 | 945839.02 | 22205891.34 | 0.435563E+09 | 0.00 | 0.34 |
July | 1879081.66 | 0.458588E+09 | 5074.54 | 5468924.57 | 0.00 | 212188.56 | 0.204093E+09 | 1429.06 | 0.34 |
August | 0.00 | 0.313803E+09 | 83629.02 | 6602291.67 | 3365659.40 | 279648.40 | 0.338040E+09 | 1097.33 | 0.34 |
September | 23572189.08 | 51520333.56 | 0.00 | 6974300.81 | 0.00 | 0.176186E+09 | 0.633026E+09 | 0.00 | 0.34 |
October | 63481569.37 | 0.00 | 0.00 | 2462231.97 | 0.00 | 0.757755E+09 | 0.490047E+09 | 0.00 | 0.34 |
November | 54897783.49 | 0.00 | 0.00 | 604199.15 | 0.00 | 0.124886E+10 | 0.182920E+09 | 0.00 | 0.34 |
December | 35252081.98 | 0.00 | 0.00 | 165758.58 | 0.00 | 0.154003E+10 | 20595720.82 | 0.00 | 0.34 |
Annual Sum or Average | 0.385023E+09 | 0.114466E+10 | 88703.57 | 42705177.71 | 4311498.42 | 0.993980E+10 | 0.391022E+10 | 2526.40 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 79457.66 | 0.00 | 212188.56 | 7792317.55 | 0.00 | 0.34 |
Maximum of Months | 66652145.85 | 0.458588E+09 | 83629.02 | 8695104.55 | 3365659.40 | 0.235466E+10 | 0.874405E+09 | 1429.06 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3887197.83 | 0.00 | 0.00 | 49989.87 | 0.00 | 0.238151E+10 | 1842797.85 | 0.00 | 0.34 |
February | 20642877.55 | 0.00 | 0.00 | 147115.92 | 0.00 | 0.201991E+10 | 17777629.65 | 0.00 | 0.34 |
March | 67300398.51 | 0.00 | 0.00 | 419954.27 | 0.00 | 0.121620E+10 | 0.122727E+09 | 0.00 | 0.34 |
April | 94198779.53 | 18288601.22 | 10319.24 | 2076467.07 | 1400506.13 | 0.742348E+09 | 0.346277E+09 | 1974.13 | 0.34 |
May | 0.151013E+09 | 17737427.34 | 0.00 | 6160901.01 | 5416667.26 | 76455796.22 | 0.736611E+09 | 0.00 | 0.34 |
June | 86284170.70 | 0.246500E+09 | 228450.44 | 4470545.60 | 32071163.89 | 26609328.24 | 0.358436E+09 | 4387.00 | 0.34 |
July | 77189989.32 | 0.382127E+09 | 124942.02 | 3563234.49 | 76284582.63 | 266634.85 | 0.130608E+09 | 4116.95 | 0.34 |
August | 0.108308E+09 | 0.265835E+09 | 206436.51 | 3840368.40 | 51167710.55 | 386903.97 | 0.232347E+09 | 7717.33 | 0.34 |
September | 0.126526E+09 | 46403117.30 | 4371.07 | 4076755.52 | 5105182.95 | 0.201811E+09 | 0.507246E+09 | 1625.88 | 0.34 |
October | 96264501.45 | 0.00 | 0.00 | 747175.57 | 0.00 | 0.903190E+09 | 0.313389E+09 | 0.00 | 0.34 |
November | 45839569.41 | 0.00 | 0.00 | 196914.67 | 0.00 | 0.136213E+10 | 78947657.51 | 0.00 | 0.34 |
December | 4300948.67 | 0.00 | 0.00 | 95845.61 | 0.00 | 0.158654E+10 | 4926558.25 | 0.00 | 0.34 |
Annual Sum or Average | 0.881756E+09 | 0.976891E+09 | 574519.27 | 25845267.99 | 0.171446E+09 | 0.105173E+11 | 0.285114E+10 | 19821.29 | 0.34 |
Minimum of Months | 3887197.83 | 0.00 | 0.00 | 49989.87 | 0.00 | 266634.85 | 1842797.85 | 0.00 | 0.34 |
Maximum of Months | 0.151013E+09 | 0.382127E+09 | 228450.44 | 6160901.01 | 76284582.63 | 0.238151E+10 | 0.736611E+09 | 7717.33 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.881635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224318E+11 | 0.00 | 0.00 | 0.33 |
February | 0.155017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138400E+11 | 0.00 | 0.00 | 0.33 |
March | 0.233278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183823E+10 | 0.00 | 0.00 | 0.35 |
April | 0.225879E+11 | 0.00 | 0.00 | 0.00 | 0.199722E+09 | 0.405585E+09 | 0.00 | 0.00 | 0.38 |
May | 0.202186E+11 | 0.00 | 0.00 | 0.00 | 0.293577E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.116076E+11 | 0.00 | 0.00 | 0.00 | 0.226164E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.731077E+10 | 0.00 | 0.00 | 0.00 | 0.385588E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.996108E+10 | 0.00 | 0.00 | 0.00 | 0.331000E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.182667E+11 | 0.00 | 0.00 | 0.00 | 0.223449E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.265390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
November | 0.203593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550052E+10 | 0.00 | 0.00 | 0.35 |
December | 0.135897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110977E+11 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.198087E+12 | 0.00 | 0.00 | 0.00 | 0.101443E+11 | 0.551139E+11 | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.731077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.265390E+11 | 0.00 | 0.00 | 0.00 | 0.385588E+10 | 0.224318E+11 | 0.00 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3409664.05 | 0.00 | 0.00 | 23762.20 | 0.00 | 0.592395E+09 | 1063850.66 | 0.00 | 0.34 |
February | 6180480.02 | 0.00 | 0.00 | 107304.23 | 0.00 | 0.501943E+09 | 6449145.22 | 0.00 | 0.34 |
March | 16103179.05 | 0.00 | 0.00 | 277858.80 | 0.00 | 0.304021E+09 | 31299273.35 | 0.00 | 0.34 |
April | 10647040.59 | 4925927.32 | 0.00 | 1057987.72 | 0.00 | 0.185476E+09 | 99078550.90 | 0.00 | 0.34 |
May | 8022083.39 | 5788322.90 | 524.89 | 1983170.04 | 0.00 | 49595812.66 | 0.182988E+09 | 354.15 | 0.34 |
June | 3439275.79 | 69544814.16 | 8459.09 | 1564420.73 | 155462.92 | 25134199.67 | 88825929.84 | 542.93 | 0.34 |
July | 469770.42 | 0.114623E+09 | 23486.07 | 1202824.18 | 0.00 | 129282.55 | 51111313.39 | 2352.94 | 0.34 |
August | 7976.50 | 79059510.42 | 28133.93 | 1571124.34 | 224581.91 | 238394.74 | 84413040.74 | 1225.47 | 0.34 |
September | 7209131.28 | 12877002.09 | 2330.54 | 1549482.73 | 0.00 | 77013147.86 | 0.124168E+09 | 750.76 | 0.34 |
October | 17120924.08 | 0.00 | 0.00 | 690327.24 | 0.00 | 0.228346E+09 | 82278716.48 | 0.00 | 0.34 |
November | 11618818.48 | 0.00 | 0.00 | 161826.44 | 0.00 | 0.343804E+09 | 16236478.08 | 0.00 | 0.34 |
December | 7375506.43 | 0.00 | 0.00 | 36121.63 | 0.00 | 0.390463E+09 | 1137357.47 | 0.00 | 0.34 |
Annual Sum or Average | 91603850.08 | 0.286818E+09 | 62934.51 | 10226210.29 | 380044.82 | 0.269856E+10 | 0.769049E+09 | 5226.26 | 0.34 |
Minimum of Months | 7976.50 | 0.00 | 0.00 | 23762.20 | 0.00 | 129282.55 | 1063850.66 | 0.00 | 0.34 |
Maximum of Months | 17120924.08 | 0.114623E+09 | 28133.93 | 1983170.04 | 224581.91 | 0.592395E+09 | 0.182988E+09 | 2352.94 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 164355.25 | 0.00 | 0.00 | 13152.95 | 0.00 | 0.596132E+09 | 512944.07 | 0.00 | 0.34 |
February | 2608533.90 | 0.00 | 0.00 | 39893.53 | 0.00 | 0.508341E+09 | 3629735.51 | 0.00 | 0.34 |
March | 12510336.80 | 0.00 | 0.00 | 117928.71 | 0.00 | 0.322249E+09 | 16783053.10 | 0.00 | 0.34 |
April | 23621224.99 | 4535597.98 | 3709.95 | 633892.44 | 385613.50 | 0.195221E+09 | 76749136.00 | 428.74 | 0.34 |
May | 38391675.43 | 4364546.41 | 2820.33 | 1359381.41 | 1420675.07 | 47317943.61 | 0.155491E+09 | 481.83 | 0.34 |
June | 22016633.80 | 61577548.00 | 43799.38 | 1092220.40 | 8078090.05 | 25644819.21 | 70196214.28 | 1674.21 | 0.34 |
July | 19630587.18 | 94859091.34 | 52218.76 | 896361.90 | 19720646.78 | 51394.72 | 32328647.18 | 3172.06 | 0.34 |
August | 26964524.65 | 66629855.66 | 69375.95 | 1015481.17 | 12599110.43 | 89226.64 | 58151200.69 | 5816.97 | 0.34 |
September | 32475760.50 | 11539217.47 | 8540.70 | 837137.74 | 1328827.45 | 82727540.29 | 93874592.69 | 1988.67 | 0.34 |
October | 24174908.29 | 0.00 | 0.00 | 229924.60 | 0.00 | 0.256005E+09 | 47988185.18 | 0.00 | 0.34 |
November | 9603141.64 | 0.00 | 0.00 | 89420.45 | 0.00 | 0.355126E+09 | 6958958.89 | 0.00 | 0.34 |
December | 568980.02 | 0.00 | 0.00 | 27456.89 | 0.00 | 0.397399E+09 | 969336.29 | 0.00 | 0.34 |
Annual Sum or Average | 0.212731E+09 | 0.243506E+09 | 180465.07 | 6352252.21 | 43532963.28 | 0.278630E+10 | 0.563633E+09 | 13562.48 | 0.34 |
Minimum of Months | 164355.25 | 0.00 | 0.00 | 13152.95 | 0.00 | 51394.72 | 512944.07 | 0.00 | 0.34 |
Maximum of Months | 38391675.43 | 94859091.34 | 69375.95 | 1359381.41 | 19720646.78 | 0.596132E+09 | 0.155491E+09 | 5816.97 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 99169541.65 | 0.00 | 0.00 | 696760.79 | 0.00 | 0.362767E+10 | 0.107193E+09 | 0.00 | 0.39 |
February | 0.127821E+09 | 0.00 | 0.00 | 1629324.60 | 0.00 | 0.293241E+10 | 0.244689E+09 | 0.00 | 0.39 |
March | 72082896.10 | 0.00 | 0.00 | 3285206.47 | 0.00 | 0.156572E+10 | 0.618411E+09 | 0.00 | 0.39 |
April | 40431016.52 | 31646567.57 | 0.00 | 6347411.77 | 0.00 | 0.872017E+09 | 0.984523E+09 | 0.00 | 0.39 |
May | 33090988.22 | 37192666.16 | 0.00 | 11659198.11 | 0.00 | 90939186.42 | 0.142282E+10 | 0.00 | 0.39 |
June | 18620488.36 | 0.446301E+09 | 26090.37 | 8199669.65 | 1519133.17 | 21967110.86 | 0.715495E+09 | 792.64 | 0.39 |
July | 3018035.03 | 0.736439E+09 | 117765.09 | 6086130.30 | 0.00 | 703662.23 | 0.330132E+09 | 2084.74 | 0.39 |
August | 0.00 | 0.502875E+09 | 232293.36 | 8698186.35 | 6439576.82 | 3499855.33 | 0.541789E+09 | 1808.86 | 0.39 |
September | 23950571.43 | 82737520.74 | 10393.17 | 10908981.60 | 0.00 | 0.177713E+09 | 0.113618E+10 | 44.57 | 0.39 |
October | 50254235.99 | 0.00 | 0.00 | 8481358.16 | 0.00 | 0.642270E+09 | 0.140903E+10 | 0.00 | 0.39 |
November | 72619383.91 | 0.00 | 0.00 | 2877481.25 | 0.00 | 0.169150E+10 | 0.621761E+09 | 0.00 | 0.39 |
December | 42299380.82 | 0.00 | 0.00 | 1322537.35 | 0.00 | 0.234497E+10 | 0.174851E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.583358E+09 | 0.183719E+10 | 386541.98 | 70192246.42 | 7958710.00 | 0.139714E+11 | 0.830688E+10 | 4730.80 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 696760.79 | 0.00 | 703662.23 | 0.107193E+09 | 0.00 | 0.39 |
Maximum of Months | 0.127821E+09 | 0.736439E+09 | 232293.36 | 11659198.11 | 6439576.82 | 0.362767E+10 | 0.142282E+10 | 2084.74 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.521734E+11 | 0.00 | 0.00 | 6213428.25 | 0.00 | 0.00 | 0.259822E+11 | 0.00 | 3.91 |
February | 0.480243E+11 | 0.00 | 0.00 | 8304993.91 | 0.00 | 0.00 | 0.253606E+11 | 0.00 | 3.91 |
March | 0.269019E+11 | 0.00 | 0.00 | 14739003.23 | 0.00 | 0.00 | 0.360320E+11 | 0.00 | 4.09 |
April | 0.198377E+11 | 0.319554E+09 | 0.00 | 20769171.79 | 0.180016E+09 | 0.00 | 0.376689E+11 | 0.00 | 4.43 |
May | 0.997307E+10 | 0.534283E+09 | 0.00 | 31787521.18 | 0.200049E+09 | 0.00 | 0.406165E+11 | 0.00 | 5.46 |
June | 0.414011E+10 | 0.463139E+10 | 0.00 | 31037631.85 | 0.103951E+10 | 0.00 | 0.249855E+11 | 0.00 | 5.39 |
July | 0.126732E+10 | 0.813581E+10 | 0.00 | 28120356.34 | 0.157055E+10 | 0.00 | 0.170715E+11 | 0.00 | 5.58 |
August | 0.166161E+10 | 0.662576E+10 | 0.00 | 32000720.67 | 0.169544E+10 | 0.00 | 0.233561E+11 | 0.00 | 5.56 |
September | 0.964726E+10 | 0.395097E+09 | 0.00 | 30599010.61 | 0.163822E+09 | 0.00 | 0.360658E+11 | 0.00 | 5.21 |
October | 0.222992E+11 | 0.00 | 0.00 | 19903545.04 | 0.00 | 0.00 | 0.440635E+11 | 0.00 | 4.41 |
November | 0.315036E+11 | 0.00 | 0.00 | 13612588.06 | 0.00 | 0.00 | 0.331667E+11 | 0.00 | 4.18 |
December | 0.348117E+11 | 0.00 | 0.00 | 8288306.57 | 0.00 | 0.00 | 0.269315E+11 | 0.00 | 3.90 |
Annual Sum or Average | 0.262241E+12 | 0.206419E+11 | 0.00 | 0.245376E+09 | 0.484939E+10 | 0.00 | 0.371301E+12 | 0.00 | 4.67 |
Minimum of Months | 0.126732E+10 | 0.00 | 0.00 | 6213428.25 | 0.00 | 0.00 | 0.170715E+11 | 0.00 | 3.90 |
Maximum of Months | 0.521734E+11 | 0.813581E+10 | 0.00 | 32000720.67 | 0.169544E+10 | 0.00 | 0.440635E+11 | 0.00 | 5.58 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.407694E+11 | 0.00 | 0.00 | 10625256.29 | 0.00 | 0.00 | 0.374160E+11 | 0.00 | 3.92 |
February | 0.410705E+11 | 0.00 | 0.00 | 13022825.16 | 0.00 | 0.00 | 0.323419E+11 | 0.00 | 3.92 |
March | 0.208971E+11 | 0.00 | 0.00 | 22091385.67 | 0.00 | 0.00 | 0.420576E+11 | 0.00 | 4.10 |
April | 0.141694E+11 | 0.395293E+09 | 0.00 | 29058257.36 | 0.104497E+09 | 0.00 | 0.434323E+11 | 0.00 | 4.45 |
May | 0.506845E+10 | 0.595119E+09 | 0.00 | 41192395.79 | 0.139535E+09 | 0.00 | 0.457772E+11 | 0.00 | 5.50 |
June | 0.235340E+10 | 0.496456E+10 | 0.00 | 38165408.62 | 0.729291E+09 | 0.00 | 0.269579E+11 | 0.00 | 5.43 |
July | 0.697501E+09 | 0.869723E+10 | 0.00 | 34211152.41 | 0.107326E+10 | 0.00 | 0.177548E+11 | 0.00 | 5.62 |
August | 0.997769E+09 | 0.718766E+10 | 0.00 | 38559911.88 | 0.117206E+10 | 0.00 | 0.242140E+11 | 0.00 | 5.60 |
September | 0.641997E+10 | 0.453590E+09 | 0.00 | 39077603.82 | 0.105574E+09 | 0.00 | 0.394564E+11 | 0.00 | 5.24 |
October | 0.169457E+11 | 0.00 | 0.00 | 28512633.46 | 0.00 | 0.00 | 0.494662E+11 | 0.00 | 4.42 |
November | 0.253856E+11 | 0.00 | 0.00 | 20218775.15 | 0.00 | 0.00 | 0.393210E+11 | 0.00 | 4.18 |
December | 0.303527E+11 | 0.00 | 0.00 | 13328397.16 | 0.00 | 0.00 | 0.314124E+11 | 0.00 | 3.91 |
Annual Sum or Average | 0.205128E+12 | 0.222935E+11 | 0.00 | 0.328064E+09 | 0.332421E+10 | 0.00 | 0.429608E+12 | 0.00 | 4.69 |
Minimum of Months | 0.697501E+09 | 0.00 | 0.00 | 10625256.29 | 0.00 | 0.00 | 0.177548E+11 | 0.00 | 3.91 |
Maximum of Months | 0.410705E+11 | 0.869723E+10 | 0.00 | 41192395.79 | 0.117206E+10 | 0.00 | 0.494662E+11 | 0.00 | 5.62 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.101880E+09 | 0.00 | 0.00 | 0.697723E+11 | 0.00 | 11.56 |
February | 0.00 | 0.00 | 0.00 | 93380784.01 | 0.00 | 0.00 | 0.660658E+11 | 0.00 | 11.85 |
March | 0.00 | 0.00 | 0.00 | 0.104048E+09 | 0.00 | 0.00 | 0.617848E+11 | 0.00 | 13.19 |
April | 0.00 | 0.634244E+09 | 0.00 | 0.102739E+09 | 0.00 | 0.00 | 0.569607E+11 | 0.00 | 14.83 |
May | 0.00 | 0.931849E+09 | 0.00 | 0.114921E+09 | 0.00 | 0.00 | 0.499978E+11 | 0.00 | 19.11 |
June | 0.00 | 0.694108E+10 | 0.00 | 84561521.72 | 0.00 | 0.00 | 0.279318E+11 | 0.00 | 18.53 |
July | 0.00 | 0.115997E+11 | 0.00 | 67714019.00 | 0.00 | 0.00 | 0.162939E+11 | 0.00 | 19.10 |
August | 0.00 | 0.100665E+11 | 0.00 | 80162968.73 | 0.00 | 0.00 | 0.227162E+11 | 0.00 | 19.10 |
September | 0.00 | 0.709233E+09 | 0.00 | 0.111807E+09 | 0.00 | 0.00 | 0.447654E+11 | 0.00 | 17.91 |
October | 0.00 | 0.00 | 0.00 | 0.105549E+09 | 0.00 | 0.00 | 0.662465E+11 | 0.00 | 14.84 |
November | 0.00 | 0.00 | 0.00 | 99743406.56 | 0.00 | 0.00 | 0.622793E+11 | 0.00 | 13.29 |
December | 0.00 | 0.00 | 0.00 | 0.103363E+09 | 0.00 | 0.00 | 0.578302E+11 | 0.00 | 11.79 |
Annual Sum or Average | 0.00 | 0.308826E+11 | 0.00 | 0.116987E+10 | 0.00 | 0.00 | 0.602645E+12 | 0.00 | 15.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 67714019.00 | 0.00 | 0.00 | 0.162939E+11 | 0.00 | 11.56 |
Maximum of Months | 0.00 | 0.115997E+11 | 0.00 | 0.114921E+09 | 0.00 | 0.00 | 0.697723E+11 | 0.00 | 19.11 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.685269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759542E+10 | 0.00 | 0.00 | 0.33 |
February | 0.271343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522807E+10 | 0.00 | 0.00 | 0.33 |
March | 0.489718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175377E+10 | 0.00 | 0.00 | 0.35 |
April | 0.546094E+10 | 71554890.59 | 0.00 | 768459.20 | 2205414.96 | 0.297330E+09 | 0.354834E+09 | 0.00 | 0.39 |
May | 0.468753E+10 | 0.117423E+09 | 0.00 | 1596425.02 | 233595.26 | 0.00 | 0.699443E+09 | 0.00 | 0.49 |
June | 0.152038E+10 | 0.105523E+10 | 0.00 | 6421201.25 | 1596301.33 | 0.00 | 0.181185E+10 | 0.00 | 0.60 |
July | 0.375425E+09 | 0.171452E+10 | 0.00 | 6521896.76 | 1370912.81 | 0.00 | 0.178124E+10 | 0.00 | 0.66 |
August | 0.547391E+09 | 0.136017E+10 | 0.00 | 7328846.46 | 13387054.04 | 0.00 | 0.235874E+10 | 0.00 | 0.61 |
September | 0.344397E+10 | 0.110310E+09 | 0.00 | 5405390.30 | 0.00 | 0.00 | 0.156301E+10 | 0.00 | 0.51 |
October | 0.701378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
November | 0.434681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248751E+10 | 0.00 | 0.00 | 0.35 |
December | 0.120805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531640E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.369002E+11 | 0.442921E+10 | 0.00 | 28042218.99 | 18793278.40 | 0.226785E+11 | 0.856911E+10 | 0.00 | 0.44 |
Minimum of Months | 0.375425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.701378E+10 | 0.171452E+10 | 0.00 | 7328846.46 | 13387054.04 | 0.759542E+10 | 0.235874E+10 | 0.00 | 0.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:55:32
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.200318E+12 | 0.317179E+11 | 0.396159E+12 | 0.101526E+13 | 0.526786E+11 |
February | 0.231748E+12 | 0.245585E+11 | 0.309170E+12 | 0.796572E+12 | 0.467167E+11 |
March | 0.397011E+12 | 0.203468E+11 | 0.261153E+12 | 0.700648E+12 | 0.379642E+11 |
April | 0.472361E+12 | 0.140213E+11 | 0.178291E+12 | 0.510782E+12 | 0.124574E+12 |
May | 0.544273E+12 | 0.827710E+10 | 0.100443E+12 | 0.372040E+12 | 0.263721E+12 |
June | 0.569803E+12 | 0.217277E+10 | 0.219969E+11 | 0.136228E+12 | 0.598671E+12 |
July | 0.553723E+12 | -812022352.8 | -0.180153E+11 | 0.130539E+11 | 0.819900E+12 |
August | 0.499330E+12 | 0.648497E+09 | -0.126585E+10 | 0.814224E+11 | 0.719772E+12 |
September | 0.341164E+12 | 0.746327E+10 | 0.916689E+11 | 0.336248E+12 | 0.337634E+12 |
October | 0.248016E+12 | 0.141397E+11 | 0.180536E+12 | 0.532292E+12 | 0.721356E+11 |
November | 0.146601E+12 | 0.199083E+11 | 0.257538E+12 | 0.694294E+12 | 0.400537E+11 |
December | 0.973674E+11 | 0.276538E+11 | 0.351167E+12 | 0.910735E+12 | 0.351701E+11 |
Annual Sum or Average | 0.430171E+13 | 0.170096E+12 | 0.212884E+13 | 0.609957E+13 | 0.314899E+13 |
Minimum of Months | 0.973674E+11 | -812022352.8 | -0.180153E+11 | 0.130539E+11 | 0.351701E+11 |