Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:55:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9066.09 | 799.11 | 799.11 |
Net Site Energy | 8910.50 | 785.39 | 785.39 |
Total Source Energy | 17512.12 | 1543.56 | 1543.56 |
Net Source Energy | 17019.36 | 1500.13 | 1500.13 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 840.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 232.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 439.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 390.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 578.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 60.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2747.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3689.14 | 5376.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 840.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 232.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 439.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 150.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 366.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 578.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 60.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 53.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2747.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 840.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 232.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 439.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 150.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 390.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 578.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 60.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 53.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2747.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 84.91 | 316.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 188.28 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 325.17 | 473.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 84.91 | 316.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 188.28 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 325.17 | 473.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 163.080 | 4.42 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.49 | -0.2 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 155.590 | 4.22 |
Electricity Coming From Utility | 3533.548 | 95.78 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 3533.548 | 95.78 |
Total On-Site and Utility Electric Sources | 3689.139 | 100.00 |
Total Electricity End Uses | 3689.139 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.70 | 0.11 |
Air to Air Heat Recovery for Heating | 623.86 | 99.89 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 624.56 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 19.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7249.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 5.8772 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 7.1580 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 7.1580 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 6.8781 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.5805 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.9406 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 7.3625 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 7.7500 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.2625 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.3625 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.3625 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.5281 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.2625 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.3808 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.3808 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8772 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 7.1580 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 7.1580 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 6.8781 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.5805 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.9406 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 7.3625 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 7.7500 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.2625 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 7.3625 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 7.3625 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.5281 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.2625 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.3808 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.3808 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.2523 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-18:19 | 27-DEC-19:10 | - | - | - | - | - | - | - | - | - | - | 23-MAY-20:10 |
Heating | 0.00 | 128035.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 104521.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28764.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 74342.86 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 19038.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28396.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4008.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3884.25 | 226844.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1671.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 272893.55 | 442499.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 128035.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 104521.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28764.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 44668.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 968.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 17944.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28396.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4008.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3884.25 | 226844.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 216.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 789.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 665.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 911.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 737.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1391.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 475.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1236.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1832.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 192.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 168.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 2978.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 11683.50 | 5828.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 80.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 14.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 262.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1029.81 | 513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 80.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 14.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 262.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1029.81 | 513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.07 | 0.728652 | 0.619000 | 1.28 | 1.00 | 0.500000 | 0.000523 | 0.000178 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.318462 | 0.160485 | 0.373000 | 0.118786 | 0.444562 | 0.500000 | 0.002374 | 0.000056 | 0.118786 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.195454 | 0.302801 | 0.704000 | 0.137600 | 0.807468 | 0.500000 | 0.001258 | 0.000031 | 0.137600 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.180393 | 0.693783 | 0.010000 | 0.001804 | 1.00 | 0.500000 | 0.000549 | 0.000035 | 0.055739 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.081763 | 0.883121 | 1.00 | 0.081763 | 1.00 | 0.500000 | 0.000431 | 0.000028 | 0.081763 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.27 | 0.018201 | 0.010000 | 0.032671 | 0.300000 | 0.500000 | 0.020933 | 0.000045 | 0.072724 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.43 | 0.100629 | 0.709000 | 1.01 | 0.709000 | 0.500000 | 0.003786 | 0.000222 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.43 | 0.225183 | 0.642000 | 2.84 | 0.642000 | 0.500000 | 0.001692 | 0.000584 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.05 | 1.00 | 0.679000 | 0.712199 | 1.00 | 0.500000 | 0.000337 | 0.000219 | 0.712199 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.02 | 0.125172 | 0.882000 | 1.78 | 0.882000 | 0.500000 | 0.003044 | 0.000302 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.12 | 0.119083 | 0.840000 | 1.78 | 0.840000 | 0.500000 | 0.003199 | 0.000304 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.14 | 0.066053 | 0.257000 | 0.550882 | 0.300000 | 0.500000 | 0.010375 | 0.000095 | 0.550882 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.636969 | 0.493021 | 0.296000 | 0.188543 | 1.00 | 0.500000 | 0.000773 | 0.000130 | 0.209820 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8120.82 | 0.000178 | 238.70 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2567.87 | 0.000056 | 94.86 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1408.26 | 0.000031 | 44.20 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1577.34 | 0.000035 | 65.36 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1283.53 | 0.000028 | 43.80 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2057.97 | 0.000045 | 85.27 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10162.96 | 0.000222 | 317.78 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 26677.54 | 0.000584 | 825.01 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3978.95 | 0.000087 | 179.71 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3979.72 | 0.000087 | 179.74 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 22717.99 | 0.000497 | 1026.03 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 22746.23 | 0.000498 | 1027.31 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3976.86 | 0.000087 | 179.62 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3977.63 | 0.000087 | 179.65 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 10027.36 | 0.000219 | 336.02 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1261.92 | 0.000028 | 56.99 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1262.08 | 0.000028 | 57.00 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6096.35 | 0.000133 | 275.31 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 13788.25 | 0.000302 | 414.69 |
DINING_FLR_6 VAV BOX REHEAT COIL | 13889.52 | 0.000304 | 418.08 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 4339.48 | 0.000095 | 130.81 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5938.60 | 0.000130 | 246.08 |
VAV WITH REHEAT HEATING COIL | 149658.94 | 0.003274 | 3236.99 |
FLR_3_DOAS HEATING COIL | 15471.26 | 0.000338 | 334.63 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.780941 | 0.000087 | 0.000248 |
ROOM_2_FLR_3 FAN COIL | 0.707046 | 0.000087 | 0.000225 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.68 | 0.000497 | 0.001757 |
ROOM_4_MULT19_FLR_3 FAN COIL | 4.28 | 0.000498 | 0.001442 |
ROOM_5_FLR_3 FAN COIL | 0.707497 | 0.000087 | 0.000225 |
ROOM_6_FLR_3 FAN COIL | 0.641467 | 0.000087 | 0.000204 |
ROOM_1_FLR_6 FAN COIL | 0.205659 | 0.000028 | 0.000065 |
ROOM_2_FLR_6 FAN COIL | 0.184874 | 0.000028 | 0.000059 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.19 | 0.000133 | 0.000383 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.780941 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.707046 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.68 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 4.28 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.707497 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.641467 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.205659 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.184874 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.19 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008591 | 12.80 | 0.008500 | 0.000248 | 0.780941 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008600 | 12.80 | 0.008500 | 0.000225 | 0.707046 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008498 | 12.80 | 0.008498 | 0.001757 | 5.68 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008821 | 12.80 | 0.008500 | 0.001442 | 4.28 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008600 | 12.80 | 0.008500 | 0.000225 | 0.707497 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008609 | 12.80 | 0.008500 | 0.000204 | 0.641467 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008586 | 12.80 | 0.008500 | 0.000065 | 0.205659 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008595 | 12.80 | 0.008500 | 0.000059 | 0.184874 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008636 | 12.80 | 0.008500 | 0.000383 | 1.19 | |
VAV WITH REHEAT COOLING COIL | 25.12 | 6.70 | 0.009124 | 10.96 | 0.008500 | 0.010848 | 19.84 | 379290.41 |
FLR_3_DOAS COOLING COIL | 26.40 | 6.70 | 0.008407 | 11.92 | 0.008407 | 0.001033 | 2.05 | 36112.10 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.91 | 10.52 | 19.94 | 10.52 | 19.84 | 19.84 | 0.300000 | 0.530391 | 19.84 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 19.84 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 19.84 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.010848 | 0.000044 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003274 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001033 | 0.000461 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000338 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.016488 | 2665.27 | |
HEATSYS1 PUMP | 0.007371 | 2197.89 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.007371 | 0.884541 |
COOLSYS1 | 0.016488 | 1.98 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 336967.44 | 336967.44 | 0.007371 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.016488 | 1845.25 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.016488 | 576491.35 | 577062.63 | 65.79 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 5.877 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.257 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 7.158 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 17.918 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 7.158 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 17.918 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 6.878 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.258 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.581 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.271 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.941 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.471 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 7.363 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.743 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 7.750 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.820 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.263 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.263 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.363 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.183 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.363 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.183 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.528 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.031 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.263 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.263 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 11630.030 | 5.877 | 109.203 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11630.030 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 480.097 | 7.158 | 44.334 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 480.097 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 555.954 | 7.158 | 44.334 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 555.954 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1129.686 | 6.878 | 425.975 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1129.686 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 339.286 | 3.581 | 166.317 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 339.286 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 385.564 | 4.941 | 45.901 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 385.564 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1390.496 | 7.363 | 9.772 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1390.496 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10138.453 | 7.750 | 24.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10138.453 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1659.841 | 4.263 | 79.202 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1659.841 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2441.829 | 7.363 | 9.771 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2441.829 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2441.829 | 7.363 | 9.771 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2441.829 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1190.908 | 11.528 | 53.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1190.908 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1756.685 | 4.263 | 79.201 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1756.685 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.6574 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.7876 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.7805 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7104 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.354 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.102 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.114 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.227 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.240 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.16971219E-14 | 0.26892915E-16 | -0.16240059E-09 | 0.37056643E-16 |
29 | 8 | 0.23652772E-07 | 0.89616755E-13 | 0.39622571E-03 | -0.26894014E-09 |
30 | 7 | -0.12790761E-01 | 0.45676733E-08 | -0.23876317E-01 | 0.14543562E-03 |
31 | 6 | 0.42027218 | 0.15798428E-05 | 0.48477927 | -0.49236552E-02 |
32 | 5 | -5.3361689 | 0.58695281E-04 | -4.5386236 | 0.64989301E-01 |
33 | 4 | 33.646820 | 0.47798126E-03 | 21.820707 | -0.43067309 |
34 | 3 | -112.59610 | 0.10375350E-02 | -56.375918 | 1.5349863 |
35 | 2 | 198.48864 | 0.58151931E-03 | 78.564784 | -2.9222743 |
36 | 1 | -171.66586 | 0.61873281E-04 | -55.455970 | 2.7543739 |
37 | 0 | 57.057407 | 0.35084782E-06 | 15.525941 | |
38 | 9 | -0.42844289E-14 | 0.28320545E-16 | -0.15636867E-09 | 0.85480581E-16 |
39 | 8 | 0.22806714E-07 | 0.10679199E-12 | 0.38751646E-03 | -0.25932016E-09 |
40 | 7 | -0.12531483E-01 | 0.54901366E-08 | -0.23503188E-01 | 0.14248753E-03 |
41 | 6 | 0.41322793 | 0.19054371E-05 | 0.47879461 | -0.48406201E-02 |
42 | 5 | -5.2674357 | 0.71001872E-04 | -4.4927242 | 0.64137031E-01 |
43 | 4 | 33.342859 | 0.57975360E-03 | 21.641446 | -0.42663722 |
44 | 3 | -111.94957 | 0.12614747E-02 | -56.021588 | 1.5256452 |
45 | 2 | 197.84807 | 0.70855353E-03 | 78.239553 | -2.9121017 |
46 | 1 | -171.42933 | 0.75539563E-04 | -55.360912 | 2.7502285 |
47 | 0 | 57.057407 | 0.42933555E-06 | 15.541245 | |
48 | 9 | -0.42353945E-14 | 0.27136288E-16 | -0.15669806E-09 | 0.83928570E-16 |
49 | 8 | 0.22852977E-07 | 0.10586107E-12 | 0.38799547E-03 | -0.25984619E-09 |
50 | 7 | -0.12545752E-01 | 0.54398248E-08 | -0.23523727E-01 | 0.14264978E-03 |
51 | 6 | 0.41361563 | 0.18876143E-05 | 0.47912423 | -0.48451901E-02 |
52 | 5 | -5.2712188 | 0.70326153E-04 | -4.4952532 | 0.64183940E-01 |
53 | 4 | 33.359590 | 0.57415042E-03 | 21.651325 | -0.42685937 |
54 | 3 | -111.98516 | 0.12491162E-02 | -56.041117 | 1.5261594 |
55 | 2 | 197.88333 | 0.70152833E-03 | 78.257474 | -2.9126617 |
56 | 1 | -171.44235 | 0.74782356E-04 | -55.366142 | 2.7504567 |
57 | 0 | 57.057407 | 0.42497884E-06 | 15.540397 | |
58 | 9 | -0.29803454E-14 | 0.26315664E-16 | -0.15962191E-09 | 0.69155213E-16 |
59 | 8 | 0.23264542E-07 | 0.97548145E-13 | 0.39224253E-03 | -0.26452581E-09 |
60 | 7 | -0.12672225E-01 | 0.49915742E-08 | -0.23705744E-01 | 0.14408782E-03 |
61 | 6 | 0.41705177 | 0.17291566E-05 | 0.48204435 | -0.48856940E-02 |
62 | 5 | -5.3047469 | 0.64329124E-04 | -4.5176529 | 0.64599678E-01 |
63 | 4 | 33.507866 | 0.52449971E-03 | 21.738817 | -0.42882811 |
64 | 3 | -112.30056 | 0.11397552E-02 | -56.214058 | 1.5307162 |
65 | 2 | 198.19584 | 0.63943657E-03 | 78.416197 | -2.9176244 |
66 | 1 | -171.55775 | 0.68097144E-04 | -55.412505 | 2.7524792 |
67 | 0 | 57.057407 | 0.38656276E-06 | 15.532909 | |
68 | 9 | -0.33614258E-14 | 0.27986632E-16 | -0.15994383E-09 | 0.68043394E-16 |
69 | 8 | 0.23309699E-07 | 0.96633735E-13 | 0.39270698E-03 | -0.26503927E-09 |
70 | 7 | -0.12686050E-01 | 0.49423205E-08 | -0.23725640E-01 | 0.14424502E-03 |
71 | 6 | 0.41742739 | 0.17117811E-05 | 0.48236343 | -0.48901217E-02 |
72 | 5 | -5.3084120 | 0.63672673E-04 | -4.5201000 | 0.64645123E-01 |
73 | 4 | 33.524074 | 0.51907321E-03 | 21.748373 | -0.42904331 |
74 | 3 | -112.33503 | 0.11278190E-02 | -56.232948 | 1.5312143 |
75 | 2 | 198.22999 | 0.63266761E-03 | 78.433537 | -2.9181668 |
76 | 1 | -171.57036 | 0.67369156E-04 | -55.417574 | 2.7527002 |
77 | 0 | 57.057407 | 0.38238191E-06 | 15.532094 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 37 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 | ||
2 | RESWINDOW_U_0.248_SHGC_0.21 | 38 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.680 | 0.5995 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.312 | 3.5001E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1075 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 6.2155E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1230 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.2440E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1009E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.9162E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9121E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.7843E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1224 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 7.4050E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1406 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.5983E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.8482E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.6175E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2628E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3264E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6516E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5545E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.0408E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1760E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.9357E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 7.8225E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8610E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0256E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6516E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5545E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.0408E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1760E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.9357E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 7.8225E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8610E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0256E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 28178.81374 | 28178.81374 | 2.06939 | 2.06939 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 22.51733 | 8.40102E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1429.80268 | 1429.80268 | 6.19438E-002 | 0.85446 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4336.10885 | 4336.10885 | 0.31846 | 0.31846 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1948.11038 | 1948.11038 | 8.43949E-002 | 8.43949E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2661.19826 | 2661.19826 | 0.19545 | 0.19545 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 25.73267 | 8.40603E-003 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 690.33573 | 690.33573 | 2.99071E-002 | 9.17335E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2456.66586 | 2456.66586 | 0.18039 | 0.18039 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 25.94500 | 8.40636E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1286.60232 | 1286.60232 | 5.57387E-002 | 5.57387E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1113.47400 | 1113.47400 | 8.17630E-002 | 8.17630E-002 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.30900 | 8.40693E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 856.98053 | 856.98053 | 3.71265E-002 | 5.77652E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44489.06885 | 44489.06885 | 3.26713 | 3.26713 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1678.70324 | 1678.70324 | 7.27237E-002 | 7.27237E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19456.38190 | 19456.38190 | 1.43013 | 1.43013 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 4871.93075 | 4871.93075 | 0.21106 | 0.67638 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 60256.23256 | 60256.23256 | 4.42679 | 4.42679 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 11848.69594 | 11848.69594 | 0.51332 | 1.89399 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 7891.73648 | 7891.73648 | 0.78094 | 0.78094 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 25.36867 | 8.40546E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3978.99569 | 3978.99569 | 0.17339 | 0.17339 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 7144.99186 | 7144.99186 | 0.70705 | 0.70705 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3979.76854 | 3979.76854 | 0.17342 | 0.17342 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 57445.07654 | 57445.07654 | 5.68432 | 5.68432 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 22718.10929 | 22718.10929 | 0.98998 | 0.98998 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 43245.13877 | 43245.13877 | 4.27955 | 4.27955 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.30900 | 8.40693E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 22746.34973 | 22746.34973 | 0.99121 | 0.99121 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 7149.55201 | 7149.55201 | 0.70750 | 0.70750 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3976.90208 | 3976.90208 | 0.17330 | 0.17330 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 6482.28862 | 6482.28862 | 0.64147 | 0.64147 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.91067 | 8.40008E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3977.67487 | 3977.67487 | 0.17333 | 0.17333 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 14283.06230 | 14283.06230 | 1.04889 | 1.04889 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 26.40000 | 8.40708E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 6310.57258 | 6310.57258 | 0.27339 | 0.47476 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2078.27518 | 2078.27518 | 0.20566 | 0.20566 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49000 | 8.40565E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1261.92998 | 1261.92998 | 5.49894E-002 | 5.49894E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 1868.22420 | 1868.22420 | 0.18487 | 0.18487 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1262.09682 | 1262.09682 | 5.49967E-002 | 5.49967E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12051.45697 | 12051.45697 | 1.19260 | 1.19260 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 26.32417 | 8.40696E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 6096.39802 | 6096.39802 | 0.26566 | 0.26566 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 27459.09110 | 27459.09110 | 2.01900 | 2.01900 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4492.82932 | 4492.82932 | 0.19464 | 1.18780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 28863.74429 | 28863.74429 | 2.12225 | 2.12225 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4583.95958 | 4583.95958 | 0.19859 | 1.18780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -4.30000 | 2.65759E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29113.00750 | 29113.00750 | 2.14351 | 2.14351 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 25.58100 | 8.40579E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1475.17788 | 1475.17788 | 6.38987E-002 | 0.36735 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -4.30000 | 2.65759E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8673.87396 | 8673.87396 | 0.63697 | 0.63697 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 26.40000 | 8.40708E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 4843.19820 | 4843.19820 | 0.20982 | 0.20982 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -4.30000 | 2.65759E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 292713.13 | 19.84311 | 19.84311 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 181380.03 | 7.21469 | 7.21469 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 33397.10 | 13.67481 | 2.05125 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 51569.06 | 3.05027 | 2.05125 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.06939 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.72865 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28096 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.22883E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77643E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28096 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8120.82043 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77643E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 238.70196 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31846 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16049 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37300 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11879 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44456 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37405E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.61722E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11879 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2567.86742 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.61722E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 94.85994 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.19545 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30280 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.70400 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13760 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80747 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25825E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.08058E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13760 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1408.26305 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08058E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 44.19800 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18039 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69378 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.80393E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.49163E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.45043E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.57387E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1577.33954 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.45043E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 65.35551 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.17630E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.88312 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.17630E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.31425E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.80773E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.17630E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1283.53366 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80773E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 43.80081 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.26713 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.82013E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.26713E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09325E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.50182E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.27237E-002 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2057.97447 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.50182E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 85.26969 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43013 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10063 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.70900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01397 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.78619E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.22315E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01397 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10162.95553 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.22315E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 317.78194 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.42679 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22518 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.64200 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64200 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69196E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.83572E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84200 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26677.54294 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.83572E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 825.00975 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.78094 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.78094 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.70397E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.47531E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68920 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59050E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.47531E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.78094 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3978.95132 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.70397E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 179.70958 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.70705 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.70705 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.70566E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.24665E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68919 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59960E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.24665E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.70705 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3979.72416 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.70566E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 179.74446 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.68432 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.68432 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.96957E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.75727E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68967 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49812E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49812E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.75727E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.68432 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 22717.98694 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.96957E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1026.03223 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.27955 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 4.27955 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.97574E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.44195E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68867 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82140E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.44195E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.27955 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 22746.22722 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.97574E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1027.30722 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.70750 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.70750 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.69939E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.24809E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68919 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59960E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.24809E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.70750 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3976.85773 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.69939E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 179.61507 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.64147 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.64147 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.70108E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.04370E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68918 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60937E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.04370E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.64147 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3977.63051 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.70108E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 179.64995 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04889 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.67900 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71220 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36698E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.19349E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71220 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10027.36327 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.19349E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 336.02029 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.20566 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.20566 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.76045E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.51077E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68921 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58606E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.51077E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.20566 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1261.91633 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.76045E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 56.98854 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.18487 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.18487 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.76081E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.86774E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68920 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59543E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.86774E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.18487 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1262.08316 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.76081E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 56.99606 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.19260 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.19260 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.33358E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.82739E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68895 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63637E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.82739E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.19260 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6096.34538 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33358E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 275.30847 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.01900 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12517 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.88200 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78076 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88200 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04381E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01618E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78076 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13788.24612 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01618E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 414.69483 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12225 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11908 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.84000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78269 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19946E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.03834E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78269 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13889.52252 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.03834E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 418.07792 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14351 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.60525E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25700 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55088 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03747E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.49263E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55088 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4339.48161 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.49263E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 130.80689 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63697 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.49302 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18854 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.72786E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29907E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20982 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5938.60126 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29907E-004 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 246.08177 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.90516 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.52462 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 19.94014 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.52462 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 19.84311 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 19.84311 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53039 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 19.84311 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 19.84311 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.12232 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95940 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.12364E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 379290.41144 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.08477E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 19.84311 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 149658.94404 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.27379E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3236.98685 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 19.84311 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.08477E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.38980E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.27379E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.40000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91985 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 36112.10278 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.03280E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15471.26131 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.38434E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 334.62931 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.03280E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.61067E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.38434E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.64876E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 2665.26531 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 7.37117E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.88454 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 7.37117E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2197.89439 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 336967.43994 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 336967.44000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 7.37117E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.64876E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 1.97851 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.64876E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 1845.25307 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.64876E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 576491.35292 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 577062.63000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 65.78514 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 12331.29 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3900.23 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2137.42 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2394.08 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1950.66 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 3123.58 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15425.32 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 40493.72 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6730.83 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6732.14 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 38429.59 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 38477.35 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6727.29 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6728.60 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15242.55 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2134.54 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2134.82 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10311.94 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 20932.69 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 21086.34 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6587.91 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9013.57 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 153189.26 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 15836.21 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 12786.92 | 11028.70 | 1758.23 | 0.86 | 2472.94 | 25.08 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 11596.52 | 9991.93 | 1604.59 | 0.86 | 2237.57 | 22.69 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 91495.41 | 79731.14 | 11764.27 | 0.87 | 18123.81 | 183.82 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 73031.08 | 61497.13 | 11533.96 | 0.84 | 13429.42 | 136.21 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 11603.91 | 9998.30 | 1605.61 | 0.86 | 2239.00 | 22.71 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 10539.93 | 9071.80 | 1468.14 | 0.86 | 2028.74 | 20.58 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3364.63 | 2903.42 | 461.21 | 0.86 | 651.44 | 6.61 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3029.84 | 2611.81 | 418.03 | 0.86 | 585.23 | 5.94 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 19692.68 | 16900.10 | 2792.58 | 0.86 | 3765.60 | 38.19 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 468468.54 | 338586.35 | 129882.19 | 0.72 | 78201.40 | 793.16 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 44891.31 | 33390.37 | 11500.94 | 0.74 | 6895.25 | 69.94 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.657 | 0.599 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.717 | 0.648 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.788 | 0.705 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.788 | 0.705 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.788 | 0.705 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.788 | 0.705 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.710 | 0.642 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.710 | 0.642 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.710 | 0.642 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.710 | 0.642 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.710 | 0.642 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.781 | 0.699 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.781 | 0.699 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.781 | 0.699 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.781 | 0.699 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.781 | 0.699 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.781 | 0.699 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.781 | 0.699 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.781 | 0.699 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6595589955E-002 | 2.1387422240E-002 | Pass | Pass | 6.8255720099E-003 | 2.0276356013E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5866325292E-002 | 3.1149676315E-002 | Pass | Pass | 7.7295404906E-002 | 0.1346281549 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2633651804E-002 | 1.8783221014E-002 | Pass | Pass | 1.3739424106E-002 | 3.6691361897E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5262765787E-002 | 1.6660394278E-002 | Pass | Pass | 7.3117979308E-003 | 2.1137469000E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.6507181147E-004 | 4.2635300025E-004 | Pass | Pass | 0.4490107121 | 3.0569520378 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2670969330E-004 | 1.9821065754E-004 | Pass | Pass | 2.1019409660E-002 | 6.1220705632E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1693491006E-002 | 4.6326141381E-002 | Pass | Pass | 2.2113331840E-002 | 4.8101520513E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8242243848E-002 | 4.5588355796E-002 | Pass | Pass | 1.2654172331E-002 | 2.8005153416E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5548406845E-002 | 0.1412707481 | Pass | Pass | 0.2239705440 | 1.3568746455 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.2654603455E-002 | 0.2241862184 | Pass | Pass | 0.1094015457 | 0.4722052567 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0049578643E-002 | 5.6183077511E-002 | Pass | Pass | 7.4100308660E-003 | 8.5231726765E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5213560119E-002 | 8.0993903377E-002 | Pass | Pass | 0.2916972716 | 1.2690127855 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.4876712778E-002 | 0.1418230472 | Pass | Pass | 0.1270196768 | 0.6052795242 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.6254695366E-002 | 0.2179287493 | Pass | Pass | 0.3050020921 | 2.1782220123 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.6905589829E-004 | 2.6072224529E-004 | Pass | Pass | 4.1785954850E-002 | 8.4987948611E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.9873485704E-002 | 0.2243864306 | Pass | Pass | 8.8956599236E-002 | 0.3242875558 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.6624552944E-002 | 0.2941911671 | Pass | Pass | 0.1077110845 | 0.2737677807 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8814834689E-002 | 0.1413441154 | Pass | Pass | 1.6877792221 | 18.0273145525 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7873201762E-002 | 8.8260472734E-002 | Pass | Pass | 1.1221174207E-002 | 2.6871378977E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0837691088E-002 | 9.6274922567E-002 | Pass | Pass | 1.0305647981E-002 | 2.2481886119E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1214876216E-003 | 2.0515291282E-003 | Pass | Pass | 2.2686098155E-002 | 4.4417556837E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7273548518E-003 | 8.5774389377E-003 | Pass | Pass | 4.3163280292E-002 | 6.6873112839E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3368.55 | 149.69 | 1965.08 | 5910.17 | 1202.95 | 12596.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.599 | 0.657 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.648 | 0.717 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.642 | 0.710 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.408 | 0.210 | 0.290 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.408 | 0.210 | 0.290 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.408 | 0.210 | 0.290 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.408 | 0.210 | 0.290 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.408 | 0.210 | 0.290 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.408 | 0.210 | 0.290 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.408 | 0.210 | 0.290 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.408 | 0.210 | 0.290 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 432.95 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8772 | 1978.83 | 11630.03 | LightsWired | LTG_SCH_BASEMENT | 40.17 | 168.00 | 40.12 | 0.0000 | Y | 87.60 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 7.1580 | 67.07 | 480.10 | LightsWired | LTG_SCH_RETAIL | 44.04 | 168.00 | 43.99 | 0.0000 | Y | 3.96 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 7.1580 | 77.67 | 555.95 | LightsWired | LTG_SCH_RETAIL | 44.04 | 168.00 | 43.99 | 0.0000 | Y | 4.59 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 6.8781 | 164.24 | 1129.69 | LightsWired | LTG_SCH_MECHANIC | 38.78 | 168.00 | 38.73 | 0.0000 | Y | 8.21 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.5805 | 94.76 | 339.29 | LightsWired | LTG_SCH_STORAGE | 29.59 | 168.00 | 29.56 | 0.0000 | Y | 1.88 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.9406 | 78.04 | 385.56 | LightsWired | LTG_SCH_LAUNDRY | 48.47 | 168.00 | 48.41 | 0.0000 | Y | 3.50 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 7.3625 | 188.86 | 1390.50 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 24.47 | 0.0000 | Y | 6.39 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 7.7500 | 1308.19 | 10138.45 | LightsWired | LTG_SCH_LOBBY | 41.54 | 168.00 | 39.27 | 0.0000 | Y | 74.74 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.2625 | 1557.62 | 6639.36 | LightsWired | LTG_SCH_CORRIDOR | 41.54 | 168.00 | 41.50 | 0.0000 | Y | 51.72 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 7.3625 | 331.66 | 2441.83 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 30.44 | 0.0000 | Y | 13.95 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 7.3625 | 331.66 | 2441.83 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 30.44 | 0.0000 | Y | 13.95 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.5281 | 103.30 | 1190.91 | LightsWired | LTG_SCH_KITCHEN | 38.78 | 168.00 | 38.73 | 0.0000 | Y | 8.66 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.2625 | 412.12 | 1756.68 | LightsWired | LTG_SCH_CORRIDOR | 41.54 | 168.00 | 41.50 | 0.0000 | Y | 13.68 |
Interior Lighting Total | 5.3808 | 11345.29 | 61047.14 | 263.76 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10138.45 | 709.69 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10138.45 | 709.69 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1390.50 | 542.29 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1390.50 | 542.29 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2441.83 | 488.37 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2441.83 | 488.37 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2441.83 | 488.37 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2441.83 | 488.37 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 9571.94 | AstronomicalClock | - | 83.54 | 83.54 | 150.10 | |
Exterior Lighting Total | 9571.94 | 150.10 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 336967.44 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 577062.63 | 2.96 | 577164.06 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 8655.13 | 12786.92 | 11028.70 | 1758.23 | 0.86 | - | 2472.94 | 25.08 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 7855.61 | 11596.52 | 9991.93 | 1604.59 | 0.86 | - | 2237.57 | 22.69 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 61444.58 | 91495.41 | 79731.14 | 11764.27 | 0.87 | - | 18123.81 | 183.82 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 50418.89 | 73031.08 | 61497.13 | 11533.96 | 0.84 | - | 13429.42 | 136.21 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 7860.62 | 11603.91 | 9998.30 | 1605.61 | 0.86 | - | 2239.00 | 22.71 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 7145.97 | 10539.93 | 9071.80 | 1468.14 | 0.86 | - | 2028.74 | 20.58 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2276.55 | 3364.63 | 2903.42 | 461.21 | 0.86 | - | 651.44 | 6.61 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2051.70 | 3029.84 | 2611.81 | 418.03 | 0.86 | - | 585.23 | 5.94 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13382.80 | 19692.68 | 16900.10 | 2792.58 | 0.86 | - | 3765.60 | 38.19 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 379290.41 | 468468.54 | 338586.35 | 129882.19 | 0.72 | - | 78201.40 | 793.16 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 36112.10 | 44891.31 | 33390.37 | 11500.94 | 0.74 | - | 6895.25 | 69.94 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8120.82 | 12331.29 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2567.87 | 3900.23 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1408.26 | 2137.42 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1577.34 | 2394.08 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1283.53 | 1950.66 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2057.97 | 3123.58 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10162.96 | 15425.32 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26677.54 | 40493.72 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3978.95 | 6730.83 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3979.72 | 6732.14 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 22717.99 | 38429.59 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 22746.23 | 38477.35 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3976.86 | 6727.29 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3977.63 | 6728.60 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10027.36 | 15242.55 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1261.92 | 2134.54 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1262.08 | 2134.82 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 6096.35 | 10311.94 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13788.25 | 20932.69 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13889.52 | 21086.34 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 4339.48 | 6587.91 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5938.60 | 9013.57 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 149658.94 | 153189.26 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15471.26 | 15836.21 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.78 | 549.50 | 703.64 | 1.00 | 1.26 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.71 | 497.50 | 703.64 | 1.00 | 1.30 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.68 | 3999.70 | 703.64 | 1.00 | 0.96 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 4.28 | 3011.25 | 703.64 | 1.00 | 0.98 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.71 | 497.82 | 703.64 | 1.00 | 1.30 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.64 | 451.36 | 703.64 | 1.00 | 1.33 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.21 | 144.71 | 703.64 | 1.00 | 2.03 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.18 | 130.08 | 703.64 | 1.00 | 2.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.19 | 839.16 | 703.64 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 19.84 | 44461.24 | 2240.64 | 1.00 | 1.11 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.016488 | 2665.27 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.007371 | 2197.89 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.016488 | 1845.25 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.95 | 0.68 | 0.60 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.95 | 0.31 | 0.04 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 28178.81 | 28178.81 | 14.24 | 2.069 | 2.069 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 24.00 | 24.00 | 0.00936 | 22.52 | 0.00840 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4336.11 | 4336.11 | 64.65 | 0.318 | 0.318 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00905 | 26.17 | 0.00841 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2661.20 | 2661.20 | 34.26 | 0.195 | 0.195 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 24.00 | 24.00 | 0.00955 | 25.73 | 0.00841 | 0.092 | 0.00 |
MECH_FLR_1 | 2456.67 | 2456.67 | 14.96 | 0.180 | 0.180 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 24.00 | 24.00 | 0.00873 | 25.95 | 0.00841 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1113.47 | 1113.47 | 11.75 | 0.082 | 0.082 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00889 | 26.31 | 0.00841 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44489.07 | 44489.07 | 570.08 | 3.267 | 3.267 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00854 | 26.40 | 0.00841 | 0.000 | 0.00 |
CAFE_FLR_1 | 19456.38 | 19456.38 | 103.02 | 1.430 | 1.430 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.01013 | 26.17 | 0.00841 | 0.676 | 0.00 |
LOBBY_FLR_1 | 60256.23 | 60256.23 | 46.06 | 4.427 | 4.427 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.01006 | 26.25 | 0.00841 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 7891.74 | 7891.74 | 202.24 | 0.781 | 0.781 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 21.11 | 21.11 | 0.00859 | 25.37 | 0.00841 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7144.99 | 7144.99 | 183.12 | 0.707 | 0.707 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00860 | 25.13 | 0.00841 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 57445.08 | 57445.08 | 2342.42 | 5.684 | 5.684 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00850 | 26.25 | 0.00841 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 43245.14 | 43245.14 | 1762.91 | 4.280 | 4.280 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 21.11 | 21.11 | 0.00882 | 26.31 | 0.00841 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7149.55 | 7149.55 | 183.22 | 0.707 | 0.707 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00860 | 22.94 | 0.00840 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6482.29 | 6482.29 | 166.14 | 0.641 | 0.641 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.11 | 21.11 | 0.00861 | 21.91 | 0.00840 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 14283.06 | 14283.06 | 36.68 | 1.049 | 1.049 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00982 | 26.40 | 0.00841 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2078.28 | 2078.28 | 53.26 | 0.206 | 0.206 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00859 | 25.49 | 0.00841 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1868.22 | 1868.22 | 47.88 | 0.185 | 0.185 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00860 | 25.13 | 0.00841 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12051.46 | 12051.46 | 491.28 | 1.193 | 1.193 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 21.11 | 21.11 | 0.00864 | 26.32 | 0.00841 | 0.099 | 0.00 |
BANQUET_FLR_6 | 27459.09 | 27459.09 | 82.79 | 2.019 | 2.019 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01054 | 26.40 | 0.00841 | 1.188 | 0.00 |
DINING_FLR_6 | 28863.74 | 28863.74 | 87.03 | 2.122 | 2.122 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.99 | 0.01044 | 26.40 | 0.00841 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29113.01 | 29113.01 | 281.82 | 2.144 | 2.144 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01015 | 25.58 | 0.00841 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8673.87 | 8673.87 | 21.05 | 0.637 | 0.637 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00907 | 26.40 | 0.00841 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1429.80 | 1429.80 | 0.72 | 0.062 | 0.854 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -4.30 | 0.00266 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 1948.11 | 1948.11 | 29.05 | 0.084 | 0.084 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00740 | -4.30 | 0.00266 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 690.34 | 690.34 | 8.89 | 0.030 | 0.092 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00735 | -4.30 | 0.00266 | 0.092 | 0.00 |
MECH_FLR_1 | 1286.60 | 1286.60 | 7.83 | 0.056 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00721 | -4.30 | 0.00266 | 0.000 | 0.00 |
STORAGE_FLR_1 | 856.98 | 856.98 | 9.04 | 0.037 | 0.058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00730 | -4.30 | 0.00266 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1678.70 | 1678.70 | 21.51 | 0.073 | 0.073 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00718 | -4.30 | 0.00266 | 0.000 | 0.00 |
CAFE_FLR_1 | 4871.93 | 4871.93 | 25.80 | 0.211 | 0.676 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00746 | -4.30 | 0.00266 | 0.676 | 0.00 |
LOBBY_FLR_1 | 11848.70 | 11848.70 | 9.06 | 0.513 | 1.894 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00738 | -4.30 | 0.00266 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3979.00 | 3979.00 | 101.97 | 0.173 | 0.173 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00733 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3979.77 | 3979.77 | 102.00 | 0.173 | 0.173 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00733 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22718.11 | 22718.11 | 926.37 | 0.990 | 0.990 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00738 | -4.30 | 0.00266 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 22746.35 | 22746.35 | 927.27 | 0.991 | 0.991 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00738 | -4.30 | 0.00266 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3976.90 | 3976.90 | 101.91 | 0.173 | 0.173 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00733 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3977.67 | 3977.67 | 101.95 | 0.173 | 0.173 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00733 | -4.30 | 0.00266 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 6310.57 | 6310.57 | 16.21 | 0.273 | 0.475 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00747 | -4.30 | 0.00266 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1261.93 | 1261.93 | 32.34 | 0.055 | 0.055 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00746 | -4.30 | 0.00266 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1262.10 | 1262.10 | 32.35 | 0.055 | 0.055 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00746 | -4.30 | 0.00266 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 6096.40 | 6096.40 | 248.52 | 0.266 | 0.266 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00748 | -4.30 | 0.00266 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4492.83 | 4492.83 | 13.55 | 0.195 | 1.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00762 | -4.30 | 0.00266 | 1.188 | 0.00 |
DINING_FLR_6 | 4583.96 | 4583.96 | 13.82 | 0.199 | 1.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00762 | -4.30 | 0.00266 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1475.18 | 1475.18 | 14.28 | 0.064 | 0.367 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00588 | -4.30 | 0.00266 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 4843.20 | 4843.20 | 11.75 | 0.210 | 0.210 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00768 | -4.30 | 0.00266 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 19.84 | 19.84 | 7.21 | 7.21 | 19.8431 | 10.5246 | 19.8431 | 0.5304 | 0.3000 |
FLR_3_DOAS | 13.67 | 2.05 | 3.05 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8120.820 | 8120.820 | 1.280955 | 0.00017764 | 238.702 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8120.82 | 8120.82 | 1.280955 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00795599 | 50.8899 | 1429.80 | 0.00 | 8156.93 | 8156.93 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2567.867 | 2567.867 | 0.118786 | 0.00005617 | 94.860 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2567.87 | 2567.87 | 0.118786 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00740166 | 47.3877 | 1948.11 | 0.00 | 2580.83 | 2580.83 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1408.263 | 1408.263 | 0.137600 | 0.00003081 | 44.198 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1408.26 | 1408.26 | 0.137600 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00735468 | 47.0892 | 690.34 | 0.00 | 1414.22 | 1414.22 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1577.340 | 1577.340 | 0.055739 | 0.00003450 | 65.356 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1577.34 | 1577.34 | 0.055739 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00720732 | 46.1565 | 1286.60 | 0.00 | 1584.88 | 1584.88 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1283.534 | 1283.534 | 0.081763 | 0.00002808 | 43.801 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1283.53 | 1283.53 | 0.081763 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00729950 | 46.7401 | 856.98 | 0.00 | 1290.30 | 1290.30 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 2057.974 | 2057.974 | 0.072724 | 0.00004502 | 85.270 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2057.97 | 2057.97 | 0.072724 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00717612 | 45.9603 | 1678.70 | 0.00 | 2067.82 | 2067.82 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10162.956 | 10162.956 | 1.013965 | 0.00022231 | 317.782 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 10162.96 | 10162.96 | 1.013965 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00746416 | 47.7827 | 4871.93 | 0.00 | 10206.02 | 10206.02 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26677.543 | 26677.543 | 2.841998 | 0.00058357 | 825.010 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 26677.54 | 26677.54 | 2.841998 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00738131 | 47.2577 | 11848.70 | 0.00 | 26791.16 | 26791.16 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 8655.125 | -999.000 | 0.780941 | 0.00024753 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | 8/21 16:40:00 | 8655.13 | 8468.98 | 0.780941 | 21.69 | 15.53 | 0.00859050 | 12.80 | 12.00 | 0.00850000 | 25.37 | 0.00840546 | 16.68 | 0.0000 | 21.11 | 0.00859050 | 54.5214 | 7891.74 | 0.00 | 8751.78 | 8751.78 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3978.951 | 3978.951 | 0.173387 | 0.00008704 | 179.710 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3978.95 | 3978.95 | 0.173387 | 21.11 | 14.18 | 0.00733353 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00733353 | 46.6379 | 3979.00 | 0.00 | 4453.20 | 4453.20 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7855.615 | -999.000 | 0.707046 | 0.00022467 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 7855.61 | 7670.09 | 0.707046 | 21.69 | 15.54 | 0.00859960 | 12.80 | 12.00 | 0.00850000 | 25.13 | 0.00840508 | 16.59 | 0.0000 | 21.11 | 0.00859960 | 54.5783 | 7144.99 | 0.00 | 7943.11 | 7943.11 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3979.724 | 3979.724 | 0.173421 | 0.00008706 | 179.744 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3979.72 | 3979.72 | 0.173421 | 21.11 | 14.18 | 0.00733369 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00733369 | 46.6389 | 3979.77 | 0.00 | 4454.06 | 4454.06 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 61444.577 | -999.000 | 5.684324 | 0.00175727 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 61444.58 | 61444.58 | 5.684324 | 21.69 | 15.45 | 0.00849812 | 12.80 | 12.00 | 0.00849812 | 26.25 | 0.00840684 | 16.99 | 0.0000 | 21.11 | 0.00849812 | 53.9417 | 57445.08 | 0.00 | 62136.61 | 62136.61 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 22717.987 | 22717.987 | 0.989983 | 0.00049696 | 1026.032 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 22717.99 | 22717.99 | 0.989983 | 21.11 | 14.22 | 0.00737561 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00737561 | 46.9012 | 22718.11 | 0.00 | 25425.99 | 25425.99 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 50418.894 | -999.000 | 4.279551 | 0.00144195 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | unknown | 8/21 15:10:00 | 50418.89 | 46768.17 | 4.279551 | 21.69 | 15.73 | 0.00882140 | 12.80 | 12.00 | 0.00850000 | 26.31 | 0.00840693 | 17.01 | 0.0000 | 21.11 | 0.00882140 | 55.9673 | 43245.14 | 0.00 | 50965.26 | 49124.33 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 22746.227 | 22746.227 | 0.991214 | 0.00049757 | 1027.307 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 22746.23 | 22746.23 | 0.991214 | 21.11 | 14.22 | 0.00737615 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00737615 | 46.9045 | 22746.35 | 0.00 | 25457.59 | 25457.59 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7860.622 | -999.000 | 0.707497 | 0.00022481 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 7860.62 | 7674.98 | 0.707497 | 21.69 | 15.54 | 0.00859960 | 12.80 | 12.00 | 0.00850000 | 22.94 | 0.00840167 | 15.82 | 0.0000 | 21.11 | 0.00859960 | 54.5783 | 7149.55 | 0.00 | 7948.17 | 7948.17 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3976.858 | 3976.858 | 0.173296 | 0.00008699 | 179.615 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3976.86 | 3976.86 | 0.173296 | 21.11 | 14.18 | 0.00733323 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00733323 | 46.6359 | 3976.90 | 0.00 | 4450.85 | 4450.85 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7145.965 | -999.000 | 0.641467 | 0.00020437 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | unknown | 8/21 09:20:00 | 7145.97 | 6961.07 | 0.641467 | 21.69 | 15.55 | 0.00860937 | 12.80 | 12.00 | 0.00850000 | 21.91 | 0.00840008 | 15.44 | 0.0000 | 21.11 | 0.00860937 | 54.6395 | 6482.29 | 0.00 | 7225.33 | 7225.33 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3977.631 | 3977.631 | 0.173330 | 0.00008701 | 179.650 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3977.63 | 3977.63 | 0.173330 | 21.11 | 14.18 | 0.00733338 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00733338 | 46.6369 | 3977.67 | 0.00 | 4451.72 | 4451.72 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 10027.363 | 10027.363 | 0.712199 | 0.00021935 | 336.020 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10027.36 | 10027.36 | 0.712199 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00747358 | 47.8411 | 6310.57 | 0.00 | 10081.50 | 10081.50 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2276.546 | -999.000 | 0.205659 | 0.00006511 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 2276.55 | 2229.94 | 0.205659 | 21.69 | 15.53 | 0.00858606 | 12.80 | 12.00 | 0.00850000 | 25.49 | 0.00840565 | 16.72 | 0.0000 | 21.11 | 0.00858606 | 54.4935 | 2078.28 | 0.00 | 2302.00 | 2302.00 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1261.916 | 1261.916 | 0.054989 | 0.00002760 | 56.989 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1261.92 | 1261.92 | 0.054989 | 21.11 | 14.29 | 0.00746030 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00746030 | 47.4345 | 1261.93 | 0.00 | 1412.32 | 1412.32 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2051.703 | -999.000 | 0.184874 | 0.00005868 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 2051.70 | 2005.23 | 0.184874 | 21.69 | 15.53 | 0.00859543 | 12.80 | 12.00 | 0.00850000 | 25.13 | 0.00840508 | 16.59 | 0.0000 | 21.11 | 0.00859543 | 54.5522 | 1868.22 | 0.00 | 2074.58 | 2074.58 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1262.083 | 1262.083 | 0.054997 | 0.00002761 | 56.996 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1262.08 | 1262.08 | 0.054997 | 21.11 | 14.29 | 0.00746040 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00746040 | 47.4351 | 1262.10 | 0.00 | 1412.51 | 1412.51 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13382.800 | -999.000 | 1.192604 | 0.00038274 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | unknown | 8/21 13:50:00 | 13382.80 | 12953.78 | 1.192604 | 21.69 | 15.57 | 0.00863637 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00840696 | 17.01 | 0.0000 | 21.11 | 0.00863637 | 54.8092 | 12051.46 | 0.00 | 13530.33 | 13530.33 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 6096.345 | 6096.345 | 0.265657 | 0.00013336 | 275.308 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6096.35 | 6096.35 | 0.265657 | 21.11 | 14.31 | 0.00748313 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00748313 | 47.5775 | 6096.40 | 0.00 | 6822.99 | 6822.99 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13788.246 | 13788.246 | 1.780761 | 0.00030162 | 414.695 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 13788.25 | 13788.25 | 1.780761 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00761565 | 48.7400 | 4492.83 | 0.00 | 13847.85 | 13847.85 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13889.523 | 13889.523 | 1.782689 | 0.00030383 | 418.078 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 13889.52 | 13889.52 | 1.782689 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00762276 | 48.7850 | 4583.96 | 0.00 | 13949.54 | 13949.54 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 4339.482 | 4339.482 | 0.550882 | 0.00009493 | 130.807 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 4339.48 | 4339.48 | 0.550882 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00588258 | 37.7599 | 1475.18 | 0.00 | 4358.22 | 4358.22 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 5938.601 | 5938.601 | 0.209820 | 0.00012991 | 246.082 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 5938.60 | 5938.60 | 0.209820 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00768334 | 49.1677 | 4843.20 | 0.00 | 5967.00 | 5967.00 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 379290.411 | -999.000 | 19.843112 | 0.01084766 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 379290.41 | 340552.80 | 19.843112 | 25.12 | 17.20 | 0.00912364 | 10.96 | 10.96 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 47.0148 | 23.99 | 0.00976786 | 51.9427 | 270015.35 | 0.00 | 382711.35 | 331797.81 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 149658.944 | 149658.944 | 5.952934 | 0.00327379 | 3236.987 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 149658.94 | 149658.94 | 5.952934 | -4.30 | -4.30 | 0.00265759 | 16.70 | 13.09 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 156.7160 | 21.02 | 0.00746016 | 47.6978 | 45820.96 | 0.00 | 133389.33 | 133389.33 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 36112.103 | -999.000 | 2.051317 | 0.00103280 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 36112.10 | 36112.10 | 2.051317 | 26.40 | 17.04 | 0.00840708 | 11.92 | 11.55 | 0.00840708 | 26.40 | 0.00840708 | 17.04 | 99.9965 | 21.11 | 0.00863788 | 54.8177 | 138190.33 | 0.00 | 36442.34 | 36442.34 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15471.261 | 15471.261 | 0.615395 | 0.00033843 | 334.629 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 15471.26 | 15471.26 | 0.615395 | -4.30 | -4.30 | 0.00265759 | 16.70 | 13.09 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 333.3216 | 21.11 | 0.00737683 | 46.9088 | 69998.23 | 0.00 | 13789.36 | 13789.36 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8120.820 | 8120.820 | 1.280955 | 0.00017764 | 238.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 2.3624 | 2.409972 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8120.82 | 8120.82 | 1.0000 | 1.52609437 | 1.280955 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.17762505 | 60.00 | 48.89 | 11.11 | 0.000 | 8120.82 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00795599 | 21.00 | 0.00795599 | 50.8899 | 1429.80 | 0.00 | 8156.93 | 8156.93 | 1.52609437 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.84 | 15.17 | 0.00800000 | 42279.7 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2567.867 | 2567.867 | 0.118786 | 0.00005617 | 94.860 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 0.7470 | 0.762052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 2567.87 | 2567.87 | 1.0000 | 0.14151866 | 0.118786 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.05616644 | 60.00 | 48.89 | 11.11 | 0.000 | 2567.87 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00740166 | 21.00 | 0.00740166 | 47.3877 | 1948.11 | 0.00 | 2580.83 | 2580.83 | 0.14151866 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.48 | 19.49 | 0.00800000 | 55171.4 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1408.263 | 1408.263 | 0.137600 | 0.00003081 | 44.198 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 0.4097 | 0.417923 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1408.26 | 1408.26 | 1.0000 | 0.16393262 | 0.137600 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.03080265 | 60.00 | 48.89 | 11.11 | 0.000 | 1408.26 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00735468 | 21.00 | 0.00735468 | 47.0892 | 690.34 | 0.00 | 1414.22 | 1414.22 | 0.16393262 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.06 | 16.33 | 0.00800000 | 45561.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1577.340 | 1577.340 | 0.055739 | 0.00003450 | 65.356 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 0.4589 | 0.468099 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1577.34 | 1577.34 | 1.0000 | 0.06640554 | 0.055739 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.03450083 | 60.00 | 48.89 | 11.11 | 0.000 | 1577.34 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00720732 | 21.00 | 0.00720732 | 46.1565 | 1286.60 | 0.00 | 1584.88 | 1584.88 | 0.06640554 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60801.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1283.534 | 1283.534 | 0.081763 | 0.00002808 | 43.801 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 0.3734 | 0.380907 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1283.53 | 1283.53 | 1.0000 | 0.09741009 | 0.081763 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.02807447 | 60.00 | 48.89 | 11.11 | 0.000 | 1283.53 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00729950 | 21.00 | 0.00729950 | 46.7401 | 856.98 | 0.00 | 1290.30 | 1290.30 | 0.09741009 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.59 | 17.90 | 0.00800000 | 50180.8 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2057.974 | 2057.974 | 0.072724 | 0.00004502 | 85.270 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 0.5987 | 0.610734 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 2057.97 | 2057.97 | 1.0000 | 0.08664097 | 0.072724 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04501366 | 60.00 | 48.89 | 11.11 | 0.000 | 2057.97 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00717612 | 21.00 | 0.00717612 | 45.9603 | 1678.70 | 0.00 | 2067.82 | 2067.82 | 0.08664097 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60801.2 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10162.956 | 10162.956 | 1.013965 | 0.00022231 | 317.782 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 2.9565 | 3.016005 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 10162.96 | 10162.96 | 1.0000 | 1.20800952 | 1.013965 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.22229226 | 60.00 | 48.89 | 11.11 | 0.000 | 10162.96 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00746416 | 21.00 | 0.00746416 | 47.7827 | 4871.93 | 0.00 | 10206.02 | 10206.02 | 1.20800952 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.89 | 16.27 | 0.00800000 | 45383.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26677.543 | 26677.543 | 2.841998 | 0.00058357 | 825.010 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 7.7608 | 7.916950 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 26677.54 | 26677.54 | 1.0000 | 3.38587692 | 2.841998 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.58351246 | 60.00 | 48.89 | 11.11 | 0.000 | 26677.54 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00738131 | 21.00 | 0.00738131 | 47.2577 | 11848.70 | 0.00 | 26791.16 | 26791.16 | 3.38587692 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.36 | 16.08 | 0.00800000 | 44847.4 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8655.125 | -999.000 | 0.780941 | 0.00024753 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8093 | 1004.8586 | 1.1914 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.780941 | 0.93039141 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 1.5013 | 1.501317 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | unknown | unknown | 8/21 16:40:00 | Sensible | 8655.13 | 8468.98 | 1.0000 | 0.93039141 | 0.780941 | 21.69 | 15.53 | 0.00859050 | 43624.9 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.24750561 | 6.70 | 15.03 | 8.33 | 0.000 | 8655.13 | 25.37 | 0.00840546 | 16.68 | 0.00000000 | 0.0000 | 21.11 | 0.00859050 | 21.11 | 0.00859050 | 54.5214 | 7891.74 | 0.00 | 8751.78 | 8751.78 | 0.93039141 | 21.69 | 15.64 | 0.00859050 | 43624.9 | 12.47 | 12.06 | 0.00859050 | 34218.3 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3978.951 | 3978.951 | 0.173387 | 0.00008704 | 179.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.780941 | 0.93039141 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 1.1575 | 1.180812 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3978.95 | 3978.95 | 1.0000 | 0.20656878 | 0.173387 | 21.11 | 14.18 | 0.00733353 | 39840.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.08703079 | 60.00 | 48.89 | 11.11 | 0.000 | 3978.95 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00733353 | 21.11 | 0.00733353 | 46.6379 | 3979.00 | 0.00 | 4453.20 | 4453.20 | 0.20656878 | 16.60 | 12.50 | 0.00733353 | 35247.4 | 37.77 | 20.01 | 0.00733353 | 56805.3 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7855.615 | -999.000 | 0.707046 | 0.00022467 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8262 | 1004.8586 | 1.1914 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.707046 | 0.84235511 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 1.3627 | 1.362634 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 7855.61 | 7670.09 | 1.0000 | 0.84235511 | 0.707046 | 21.69 | 15.54 | 0.00859960 | 43648.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.22464248 | 6.70 | 15.03 | 8.33 | 0.000 | 7855.61 | 25.13 | 0.00840508 | 16.59 | 0.00000000 | 0.0000 | 21.11 | 0.00859960 | 21.11 | 0.00859960 | 54.5783 | 7144.99 | 0.00 | 7943.11 | 7943.11 | 0.84235511 | 21.69 | 15.64 | 0.00859960 | 43648.0 | 12.45 | 12.06 | 0.00859960 | 34218.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3979.724 | 3979.724 | 0.173421 | 0.00008706 | 179.744 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.707046 | 0.84235511 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 1.1577 | 1.181041 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3979.72 | 3979.72 | 1.0000 | 0.20660890 | 0.173421 | 21.11 | 14.18 | 0.00733369 | 39841.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.08704770 | 60.00 | 48.89 | 11.11 | 0.000 | 3979.72 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00733369 | 21.11 | 0.00733369 | 46.6389 | 3979.77 | 0.00 | 4454.06 | 4454.06 | 0.20660890 | 16.60 | 12.50 | 0.00733369 | 35247.8 | 37.77 | 20.01 | 0.00733369 | 56805.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 61444.577 | -999.000 | 5.684324 | 0.00175727 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6376 | 1004.8586 | 1.1914 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.684324 | 6.77214472 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 10.6584 | 10.658170 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 61444.58 | 61444.58 | 1.0000 | 6.77214472 | 5.684324 | 21.69 | 15.45 | 0.00849812 | 43390.6 | 12.80 | 12.00 | 0.00849812 | 34317.5 | 1.75709503 | 6.70 | 15.03 | 8.33 | 0.000 | 61444.58 | 26.25 | 0.00840684 | 16.99 | 0.00000000 | 0.0000 | 21.11 | 0.00849812 | 21.11 | 0.00849812 | 53.9417 | 57445.08 | 0.00 | 62136.61 | 62136.61 | 6.77214472 | 21.69 | 15.55 | 0.00849812 | 43390.6 | 12.70 | 12.06 | 0.00849812 | 34215.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22717.987 | 22717.987 | 0.989983 | 0.00049696 | 1026.032 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.684324 | 6.77214472 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 6.6089 | 6.741894 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 22717.99 | 22717.99 | 1.0000 | 1.17943859 | 0.989983 | 21.11 | 14.22 | 0.00737561 | 39948.2 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.49690590 | 60.00 | 48.89 | 11.11 | 0.000 | 22717.99 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00737561 | 21.11 | 0.00737561 | 46.9012 | 22718.11 | 0.00 | 25425.99 | 25425.99 | 1.17943859 | 16.60 | 12.54 | 0.00737561 | 35353.9 | 37.77 | 20.04 | 0.00737561 | 56911.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 50418.894 | -999.000 | 4.279551 | 0.00144195 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2385 | 1004.8586 | 1.1914 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.279551 | 5.09853735 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 8.7458 | 8.745656 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | unknown | unknown | unknown | 8/21 15:10:00 | Sensible | 50418.89 | 46768.17 | 1.0000 | 5.09853735 | 4.279551 | 21.69 | 15.73 | 0.00882140 | 44211.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 1.44179998 | 6.70 | 15.03 | 8.33 | 0.000 | 50418.89 | 26.31 | 0.00840693 | 17.01 | 0.00000000 | 0.0000 | 21.11 | 0.00882140 | 21.11 | 0.00882140 | 55.9673 | 43245.14 | 0.00 | 50965.26 | 49124.33 | 5.09853735 | 21.69 | 15.84 | 0.00882140 | 44211.1 | 12.25 | 12.05 | 0.00867833 | 34215.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22746.227 | 22746.227 | 0.991214 | 0.00049757 | 1027.307 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.279551 | 5.09853735 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 6.6171 | 6.750275 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 22746.23 | 22746.23 | 1.0000 | 1.18090473 | 0.991214 | 21.11 | 14.22 | 0.00737615 | 39949.6 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.49752359 | 60.00 | 48.89 | 11.11 | 0.000 | 22746.23 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00737615 | 21.11 | 0.00737615 | 46.9045 | 22746.35 | 0.00 | 25457.59 | 25457.59 | 1.18090473 | 16.60 | 12.54 | 0.00737615 | 35355.3 | 37.77 | 20.05 | 0.00737615 | 56913.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7860.622 | -999.000 | 0.707497 | 0.00022481 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8262 | 1004.8586 | 1.1914 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.707497 | 0.84289216 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 1.3635 | 1.363503 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 7860.62 | 7674.98 | 1.0000 | 0.84289216 | 0.707497 | 21.69 | 15.54 | 0.00859960 | 43648.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.22478566 | 6.70 | 15.03 | 8.33 | 0.000 | 7860.62 | 22.94 | 0.00840167 | 15.82 | 0.00000000 | 0.0000 | 21.11 | 0.00859960 | 21.11 | 0.00859960 | 54.5783 | 7149.55 | 0.00 | 7948.17 | 7948.17 | 0.84289216 | 21.69 | 15.64 | 0.00859960 | 43648.0 | 12.45 | 12.06 | 0.00859960 | 34218.3 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3976.858 | 3976.858 | 0.173296 | 0.00008699 | 179.615 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.707497 | 0.84289216 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 1.1569 | 1.180191 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3976.86 | 3976.86 | 1.0000 | 0.20646009 | 0.173296 | 21.11 | 14.18 | 0.00733323 | 39840.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.08698500 | 60.00 | 48.89 | 11.11 | 0.000 | 3976.86 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00733323 | 21.11 | 0.00733323 | 46.6359 | 3976.90 | 0.00 | 4450.85 | 4450.85 | 0.20646009 | 16.60 | 12.50 | 0.00733323 | 35246.6 | 37.77 | 20.01 | 0.00733323 | 56804.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7145.965 | -999.000 | 0.641467 | 0.00020437 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8444 | 1004.8586 | 1.1914 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.641467 | 0.76422594 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 1.2396 | 1.239538 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | unknown | unknown | unknown | 8/21 09:20:00 | Sensible | 7145.97 | 6961.07 | 1.0000 | 0.76422594 | 0.641467 | 21.69 | 15.55 | 0.00860937 | 43672.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.20434903 | 6.70 | 15.03 | 8.33 | 0.000 | 7145.97 | 21.91 | 0.00840008 | 15.44 | 0.00000000 | 0.0000 | 21.11 | 0.00860937 | 21.11 | 0.00860937 | 54.6395 | 6482.29 | 0.00 | 7225.33 | 7225.33 | 0.76422594 | 21.69 | 15.65 | 0.00860937 | 43672.8 | 12.43 | 12.06 | 0.00860937 | 34218.3 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3977.631 | 3977.631 | 0.173330 | 0.00008701 | 179.650 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.641467 | 0.76422594 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 1.1571 | 1.180420 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3977.63 | 3977.63 | 1.0000 | 0.20650021 | 0.173330 | 21.11 | 14.18 | 0.00733338 | 39840.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.08700190 | 60.00 | 48.89 | 11.11 | 0.000 | 3977.63 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00733338 | 21.11 | 0.00733338 | 46.6369 | 3977.67 | 0.00 | 4451.72 | 4451.72 | 0.20650021 | 16.60 | 12.50 | 0.00733338 | 35247.0 | 37.77 | 20.01 | 0.00733338 | 56804.9 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10027.363 | 10027.363 | 0.712199 | 0.00021935 | 336.020 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 2.9171 | 2.975766 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10027.36 | 10027.36 | 1.0000 | 0.84849377 | 0.712199 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.21932647 | 60.00 | 48.89 | 11.11 | 0.000 | 10027.36 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00747358 | 21.00 | 0.00747358 | 47.8411 | 6310.57 | 0.00 | 10081.50 | 10081.50 | 0.84849377 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.25 | 17.45 | 0.00800000 | 48816.4 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2276.546 | -999.000 | 0.205659 | 0.00006511 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8010 | 1004.8586 | 1.1914 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.205659 | 0.24501691 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 0.3949 | 0.394889 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 2276.55 | 2229.94 | 1.0000 | 0.24501691 | 0.205659 | 21.69 | 15.53 | 0.00858606 | 43613.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.06510107 | 6.70 | 15.03 | 8.33 | 0.000 | 2276.55 | 25.49 | 0.00840565 | 16.72 | 0.00000000 | 0.0000 | 21.11 | 0.00858606 | 21.11 | 0.00858606 | 54.4935 | 2078.28 | 0.00 | 2302.00 | 2302.00 | 0.24501691 | 21.69 | 15.63 | 0.00858606 | 43613.6 | 12.49 | 12.06 | 0.00858606 | 34218.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1261.916 | 1261.916 | 0.054989 | 0.00002760 | 56.989 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.205659 | 0.24501691 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 0.3671 | 0.374492 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1261.92 | 1261.92 | 1.0000 | 0.06551286 | 0.054989 | 21.11 | 14.29 | 0.00746030 | 40162.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.02760164 | 60.00 | 48.89 | 11.11 | 0.000 | 1261.92 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00746030 | 21.11 | 0.00746030 | 47.4345 | 1261.93 | 0.00 | 1412.32 | 1412.32 | 0.06551286 | 16.60 | 12.62 | 0.00746030 | 35568.3 | 37.76 | 20.11 | 0.00746030 | 57126.3 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2051.703 | -999.000 | 0.184874 | 0.00005868 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8185 | 1004.8586 | 1.1914 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.184874 | 0.22025322 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 0.3559 | 0.355888 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 2051.70 | 2005.23 | 1.0000 | 0.22025322 | 0.184874 | 21.69 | 15.53 | 0.00859543 | 43637.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.05867137 | 6.70 | 15.03 | 8.33 | 0.000 | 2051.70 | 25.13 | 0.00840508 | 16.59 | 0.00000000 | 0.0000 | 21.11 | 0.00859543 | 21.11 | 0.00859543 | 54.5522 | 1868.22 | 0.00 | 2074.58 | 2074.58 | 0.22025322 | 21.69 | 15.64 | 0.00859543 | 43637.4 | 12.46 | 12.06 | 0.00859543 | 34218.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1262.083 | 1262.083 | 0.054997 | 0.00002761 | 56.996 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.184874 | 0.22025322 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 0.3672 | 0.374542 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1262.08 | 1262.08 | 1.0000 | 0.06552152 | 0.054997 | 21.11 | 14.29 | 0.00746040 | 40163.2 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.02760529 | 60.00 | 48.89 | 11.11 | 0.000 | 1262.08 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00746040 | 21.11 | 0.00746040 | 47.4351 | 1262.10 | 0.00 | 1412.51 | 1412.51 | 0.06552152 | 16.60 | 12.62 | 0.00746040 | 35568.6 | 37.76 | 20.11 | 0.00746040 | 57126.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13382.800 | -999.000 | 1.192604 | 0.00038274 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8946 | 1004.8586 | 1.1914 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.192604 | 1.42083448 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 2.3214 | 2.321379 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | unknown | unknown | unknown | 8/21 13:50:00 | Sensible | 13382.80 | 12953.78 | 1.0000 | 1.42083448 | 1.192604 | 21.69 | 15.57 | 0.00863637 | 43741.2 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.38270018 | 6.70 | 15.03 | 8.33 | 0.000 | 13382.80 | 26.32 | 0.00840696 | 17.01 | 0.00000000 | 0.0000 | 21.11 | 0.00863637 | 21.11 | 0.00863637 | 54.8092 | 12051.46 | 0.00 | 13530.33 | 13530.33 | 1.42083448 | 21.69 | 15.68 | 0.00863637 | 43741.2 | 12.36 | 12.06 | 0.00863637 | 34218.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6096.345 | 6096.345 | 0.265657 | 0.00013336 | 275.308 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.192604 | 1.42083448 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 1.7735 | 1.809179 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6096.35 | 6096.35 | 1.0000 | 0.31649646 | 0.265657 | 21.11 | 14.31 | 0.00748313 | 40221.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.13334412 | 60.00 | 48.89 | 11.11 | 0.000 | 6096.35 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00748313 | 21.11 | 0.00748313 | 47.5775 | 6096.40 | 0.00 | 6822.99 | 6822.99 | 0.31649646 | 16.60 | 12.65 | 0.00748313 | 35626.1 | 37.76 | 20.12 | 0.00748313 | 57184.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13788.246 | 13788.246 | 1.780761 | 0.00030162 | 414.695 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 4.0111 | 4.091863 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 13788.25 | 13788.25 | 1.0000 | 2.12154870 | 1.780761 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.30158750 | 60.00 | 48.89 | 11.11 | 0.000 | 13788.25 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00761565 | 21.00 | 0.00761565 | 48.7400 | 4492.83 | 0.00 | 13847.85 | 13847.85 | 2.12154870 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.00 | 15.59 | 0.00800000 | 43462.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13889.523 | 13889.523 | 1.782689 | 0.00030383 | 418.078 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 4.0406 | 4.121918 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 13889.52 | 13889.52 | 1.0000 | 2.12384555 | 1.782689 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.30380270 | 60.00 | 48.89 | 11.11 | 0.000 | 13889.52 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00762276 | 21.00 | 0.00762276 | 48.7850 | 4583.96 | 0.00 | 13949.54 | 13949.54 | 2.12384555 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.04 | 15.61 | 0.00800000 | 43502.8 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4339.482 | 4339.482 | 0.550882 | 0.00009493 | 130.807 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 1.2624 | 1.287804 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 4339.48 | 4339.48 | 1.0000 | 0.65630559 | 0.550882 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09491660 | 60.00 | 48.89 | 11.11 | 0.000 | 4339.48 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.30 | 0.00588258 | 21.00 | 0.00588258 | 37.7599 | 1475.18 | 0.00 | 4358.22 | 4358.22 | 0.65630559 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.11 | 15.63 | 0.00800000 | 43575.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5938.601 | 5938.601 | 0.209820 | 0.00012991 | 246.082 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 1.7276 | 1.762366 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 5938.60 | 5938.60 | 1.0000 | 0.24997378 | 0.209820 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12989382 | 60.00 | 48.89 | 11.11 | 0.000 | 5938.60 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00768334 | 21.00 | 0.00768334 | 49.1677 | 4843.20 | 0.00 | 5967.00 | 5967.00 | 0.24997378 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60805.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 379290.411 | -999.000 | 19.843112 | 0.01084766 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8004 | 1004.8586 | 1.1914 | VAV WITH REHEAT FAN | Fan:VariableVolume | 19.843112 | 23.64052832 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 65.7929 | 65.792906 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 379290.41 | 340552.80 | 1.0000 | 23.64052832 | 19.843112 | 25.12 | 17.20 | 0.00912364 | 48487.7 | 10.96 | 10.96 | 0.00850000 | 32443.6 | 10.84655118 | 6.70 | 15.03 | 8.33 | 44461.243 | 334829.17 | 26.40 | 0.00840708 | 17.04 | 9.32920000 | 47.0148 | 23.99 | 0.00975950 | 23.99 | 0.00976786 | 51.9427 | 270015.35 | 0.00 | 382711.35 | 331797.81 | 23.64052832 | 25.12 | 17.31 | 0.00912364 | 48487.7 | 11.39 | 11.27 | 0.00826973 | 32298.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 149658.944 | 149658.944 | 5.952934 | 0.00327379 | 3236.987 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV WITH REHEAT FAN | Fan:VariableVolume | 19.843112 | 23.64052832 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 43.5373 | 44.413473 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 149658.94 | 149658.94 | 1.0000 | 7.09215850 | 5.952934 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 3.27345960 | 60.00 | 48.89 | 11.11 | 0.000 | 149658.94 | -4.30 | 0.00265759 | -4.30 | 9.32920000 | 156.7160 | 20.96 | 0.00746970 | 21.02 | 0.00746016 | 47.6978 | 45820.96 | 0.00 | 133389.33 | 133389.33 | 7.09215850 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 21.43 | 9.66 | 0.00265759 | 28281.9 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 36112.103 | -999.000 | 2.051317 | 0.00103280 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4683 | 1004.8586 | 1.1914 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.44379602 | 4197.9300 | 999.8980 | 16.48589781 | 15.03 | 6.70 | 8.33 | 576491.35 | 6.2641 | 6.264119 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 36112.10 | 36112.10 | 1.0000 | 2.44388195 | 2.051317 | 26.40 | 17.04 | 0.00840708 | 47966.0 | 11.92 | 11.55 | 0.00840708 | 33189.4 | 1.03269621 | 6.70 | 15.03 | 8.33 | 2195.006 | 33917.10 | 26.40 | 0.00840708 | 17.04 | 2.05124512 | 99.9965 | 21.11 | 0.00863481 | 21.11 | 0.00863788 | 54.8177 | 138190.33 | 0.00 | 36442.34 | 36442.34 | 2.44388195 | 26.40 | 17.15 | 0.00840708 | 47966.0 | 11.79 | 11.58 | 0.00840708 | 33054.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15471.261 | 15471.261 | 0.615395 | 0.00033843 | 334.629 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.44379602 | 4197.9300 | 999.8980 | 7.37042018 | 48.89 | 60.00 | 11.11 | 343749.04 | 4.5007 | 4.591322 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 15471.26 | 15471.26 | 1.0000 | 0.73316458 | 0.615395 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 0.33839975 | 60.00 | 48.89 | 11.11 | 0.000 | 15471.26 | -4.30 | 0.00265759 | -4.30 | 2.05124512 | 333.3216 | 21.11 | 0.00737862 | 21.11 | 0.00737683 | 46.9088 | 69998.23 | 0.00 | 13789.36 | 13789.36 | 0.73316458 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 21.43 | 9.66 | 0.00265759 | 28281.9 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 19.84 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 798.50 | 8168.33 | 511.67 |
RETAIL_2_FLR_1 | 0.00 | 8752.50 | 0.00 |
MECH_FLR_1 | 1.33 | 7229.50 | 0.17 |
STORAGE_FLR_1 | 94.17 | 8760.00 | 94.17 |
LAUNDRY_FLR_1 | 8760.00 | 3040.83 | 3040.83 |
CAFE_FLR_1 | 20.17 | 8689.83 | 9.83 |
LOBBY_FLR_1 | 23.50 | 8530.67 | 9.33 |
ROOM_1_FLR_3 | 1437.50 | 8728.17 | 1437.50 |
ROOM_2_FLR_3 | 2072.00 | 8557.00 | 1966.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 277.83 | 8760.00 | 277.83 |
ROOM_5_FLR_3 | 1382.17 | 8759.67 | 1382.17 |
ROOM_6_FLR_3 | 1941.17 | 8715.83 | 1922.83 |
CORRIDOR_FLR_3 | 48.67 | 8760.00 | 48.67 |
ROOM_1_FLR_6 | 2427.83 | 8613.00 | 2427.83 |
ROOM_2_FLR_6 | 3138.17 | 8432.00 | 2944.83 |
ROOM_3_MULT9_FLR_6 | 748.17 | 8610.33 | 748.17 |
BANQUET_FLR_6 | 248.67 | 7882.33 | 9.83 |
DINING_FLR_6 | 698.33 | 6971.50 | 8.83 |
KITCHEN_FLR_6 | 8760.00 | 6277.33 | 6277.33 |
CORRIDOR_FLR_6 | 258.33 | 7772.50 | 63.00 |
Facility | 8760.00 | 8760.00 | 7249.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.83 | 0.00 | 0.83 |
ROOM_2_FLR_3 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 7.67 | 0.00 | 7.67 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 5.17 | 0.00 | 5.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_2_FLR_6 | 0.00 | 8.50 | 0.00 | 8.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.67 | 0.00 | 0.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 19.17 | 0.00 | 19.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.713 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.208 | 0.139 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.199 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.030 | 0.052 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.583 | 0.052 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.018 | 0.150 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.634 | 0.109 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.474 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.180 | 0.000 | 0.027 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.341 | 0.180 | 0.000 | 0.030 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.080 | 0.000 | 0.045 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.341 | 0.180 | 0.000 | 0.027 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.341 | 0.180 | 0.000 | 0.030 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.402 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.341 | 0.180 | 0.000 | 0.031 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.341 | 0.180 | 0.000 | 0.031 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.388 | 0.147 | 0.000 | 0.049 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.736 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.749 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 15.346 | 0.150 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.410 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.575 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.965 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.967 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.006 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.470 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 6.375 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 2.928 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.190 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.324 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.824 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.834 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 5.702 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.324 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.047 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.173 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.036 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 29734026.29 | 0.00 | 29734026.29 | 0.00 | 29734026.29 | 26946214.98 | 4087.17 | 1125.55 | 3547.29 | 0.00 |
RETAIL_1_FLR_1 | 2777181.82 | 0.00 | 2777181.82 | 319403.00 | 3096584.82 | 2498216.28 | 4043.62 | 1133.27 | 3583.11 | 0.00 |
RETAIL_2_FLR_1 | 3194020.58 | 0.00 | 3194020.58 | 123289.96 | 3317310.55 | 2294951.32 | 156.17 | 149.42 | 8454.42 | 0.00 |
MECH_FLR_1 | 165704.40 | 0.00 | 165704.40 | 291384.23 | 457088.63 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1897912.91 | 0.00 | 1897912.91 | 168112.65 | 2066025.56 | 1821682.01 | 5627.10 | 103.90 | 3029.00 | 0.00 |
LAUNDRY_FLR_1 | 39906617.81 | 0.00 | 39906617.81 | 397870.28 | 40304488.10 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23536543.82 | 0.00 | 23536543.82 | 706058.42 | 24242602.24 | 14544917.54 | 8.17 | 108.08 | 8643.75 | 0.00 |
LOBBY_FLR_1 | 65969546.58 | 0.00 | 65969546.58 | 2017370.18 | 67986916.76 | 59728886.00 | 4028.74 | 1155.69 | 3575.57 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 28189.89 | 1434266.73 | 185391.43 | 1619658.16 | 1946875.62 | 2433.33 | 6029.00 | 297.67 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 31030.57 | 1436942.66 | 185377.29 | 1622319.95 | 1946647.51 | 2433.33 | 6033.93 | 292.74 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 12.43 | 1099924.40 | 51726.29 | 1151650.69 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.17 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 29283.78 | 19099637.92 | 51740.43 | 19151378.35 | 26405105.73 | 2433.33 | 6034.10 | 292.57 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 28108.98 | 1434185.82 | 185391.43 | 1619577.25 | 1946875.62 | 2433.33 | 6029.00 | 297.67 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 30302.14 | 1436214.24 | 185377.29 | 1621591.52 | 1946647.51 | 2433.33 | 6029.00 | 297.67 | 0.00 |
CORRIDOR_FLR_3 | 16531832.28 | 0.00 | 16531832.28 | 224175.54 | 16756007.82 | 14972100.18 | 4046.21 | 1148.97 | 3564.82 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 31951.83 | 383471.04 | 185430.49 | 568901.53 | 486718.90 | 2300.33 | 6031.52 | 428.15 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 31613.89 | 383091.92 | 185416.35 | 568508.26 | 486661.88 | 2312.51 | 6057.92 | 389.57 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 31850.31 | 2290181.72 | 94872.73 | 2385054.45 | 3126920.42 | 2433.33 | 6029.17 | 297.50 | 0.00 |
BANQUET_FLR_6 | 41335836.74 | 0.00 | 41335836.74 | 452774.66 | 41788611.40 | 37458366.31 | 4084.83 | 1127.05 | 3548.12 | 0.00 |
DINING_FLR_6 | 41401875.15 | 0.00 | 41401875.15 | 452774.66 | 41854649.81 | 37458366.31 | 4015.85 | 1159.37 | 3584.78 | 0.00 |
KITCHEN_FLR_6 | 41438643.43 | 0.00 | 41438643.43 | 405338.30 | 41843981.72 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 4439839.05 | 0.00 | 4439839.05 | 396722.51 | 4836561.56 | 3961413.96 | 3942.55 | 1163.17 | 3654.28 | 0.00 |
Total Facility | 0.19E+10 | 3047256.76 | 0.19E+10 | 18682123.06 | 0.20E+10 | 0.43E+10 | 8760.00 | 6495.42 | 8760.00 | 365.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9429 | 0.0000 | 0.9429 | 0.0000 | 0.9429 | 0.8545 | 4087.17 | 1125.55 | 3547.29 |
RETAIL_1_FLR_1 | 0.0881 | 0.0000 | 0.0881 | 0.0101 | 0.0982 | 0.0792 | 4043.62 | 1133.27 | 3583.11 |
RETAIL_2_FLR_1 | 0.1013 | 0.0000 | 0.1013 | 0.0039 | 0.1052 | 0.0728 | 156.17 | 149.42 | 8454.42 |
MECH_FLR_1 | 0.0053 | 0.0000 | 0.0053 | 0.0092 | 0.0145 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0602 | 0.0000 | 0.0602 | 0.0053 | 0.0655 | 0.0578 | 5627.10 | 103.90 | 3029.00 |
LAUNDRY_FLR_1 | 1.2654 | 0.0000 | 1.2654 | 0.0126 | 1.2780 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7463 | 0.0000 | 0.7463 | 0.0224 | 0.7687 | 0.4612 | 8.17 | 108.08 | 8643.75 |
LOBBY_FLR_1 | 2.0919 | 0.0000 | 2.0919 | 0.0640 | 2.1559 | 1.8940 | 4028.74 | 1155.69 | 3575.57 |
ROOM_1_FLR_3 | 0.0446 | 0.0009 | 0.0455 | 0.0059 | 0.0514 | 0.0617 | 2433.33 | 6029.00 | 297.67 |
ROOM_2_FLR_3 | 0.0446 | 0.0010 | 0.0456 | 0.0059 | 0.0514 | 0.0617 | 2433.33 | 6033.93 | 292.74 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0009 | 0.6056 | 0.0016 | 0.6073 | 0.8373 | 2433.33 | 6034.10 | 292.57 |
ROOM_5_FLR_3 | 0.0446 | 0.0009 | 0.0455 | 0.0059 | 0.0514 | 0.0617 | 2433.33 | 6029.00 | 297.67 |
ROOM_6_FLR_3 | 0.0446 | 0.0010 | 0.0455 | 0.0059 | 0.0514 | 0.0617 | 2433.33 | 6029.00 | 297.67 |
CORRIDOR_FLR_3 | 0.5242 | 0.0000 | 0.5242 | 0.0071 | 0.5313 | 0.4748 | 4046.21 | 1148.97 | 3564.82 |
ROOM_1_FLR_6 | 0.0111 | 0.0010 | 0.0122 | 0.0059 | 0.0180 | 0.0154 | 2300.33 | 6031.52 | 428.15 |
ROOM_2_FLR_6 | 0.0111 | 0.0010 | 0.0121 | 0.0059 | 0.0180 | 0.0154 | 2312.51 | 6057.92 | 389.57 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0010 | 0.0726 | 0.0030 | 0.0756 | 0.0992 | 2433.33 | 6029.17 | 297.50 |
BANQUET_FLR_6 | 1.3108 | 0.0000 | 1.3108 | 0.0144 | 1.3251 | 1.1878 | 4084.83 | 1127.05 | 3548.12 |
DINING_FLR_6 | 1.3128 | 0.0000 | 1.3128 | 0.0144 | 1.3272 | 1.1878 | 4015.85 | 1159.37 | 3584.78 |
KITCHEN_FLR_6 | 1.3140 | 0.0000 | 1.3140 | 0.0129 | 1.3269 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.1408 | 0.0000 | 0.1408 | 0.0126 | 0.1534 | 0.1256 | 3942.55 | 1163.17 | 3654.28 |
Total Facility | 58.8152 | 0.0966 | 58.9118 | 0.4677 | 59.3795 | 73.7328 | 8760.00 | 6495.42 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.44E+09 | 0.00 | 0.44E+09 | 0.21E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 40814718.56 | 242343.83 | 41057062.39 | 64690340.46 | 8759.98 | 0.02 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 14.0573 | 0.0000 | 14.0573 | 6.7627 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2942 | 0.0077 | 1.3019 | 2.0513 | 8759.98 | 0.02 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 108.63 | 7289.88 | 0.00 | 0.00 | 0.00 | 1361.50 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 13.1304 | 14.4679 | 0.0000 | 0.0000 | 0.0000 | 11.9521 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6944 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1344 |
Defaulted Fields | 1183 |
Fields with Defaults | 4016 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 3689.14 | 56741.12 | 20-MAY-04:40 | 272893.55 | 22-JUL-18:20 |
Electricity:Building | 2095.08 | 27857.55 | 10-JUN-05:00 | 122617.06 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 230.70 | 2823.84 | 02-JAN-02:10 | 16796.09 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2087.98 | 27716.41 | 10-JUN-05:00 | 122375.73 | 02-JAN-20:10 |
InteriorLights:Electricity | 439.53 | 3822.73 | 10-JUN-05:00 | 36244.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 87.60 | 795.94 | 02-JAN-02:10 | 7163.56 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 439.53 | 3822.73 | 10-JUN-05:00 | 36244.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 439.53 | 3822.73 | 10-JUN-05:00 | 36244.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 87.60 | 795.94 | 02-JAN-02:10 | 7163.56 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 439.53 | 3822.73 | 10-JUN-05:00 | 36244.21 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 14.15 | 180.36 | 02-JAN-02:10 | 1009.79 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 3.96 | 36.02 | 02-JAN-02:10 | 324.19 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 3.96 | 36.02 | 02-JAN-02:10 | 324.19 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 16.39 | 208.86 | 02-JAN-02:10 | 1169.34 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 4.59 | 41.71 | 02-JAN-02:10 | 375.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 4.59 | 41.71 | 02-JAN-02:10 | 375.41 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.68 | 251.36 | 02-JAN-02:10 | 1511.12 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.21 | 74.63 | 02-JAN-02:10 | 671.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.21 | 74.63 | 02-JAN-02:10 | 671.67 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.48 | 68.09 | 02-JAN-02:10 | 396.12 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.88 | 17.11 | 02-JAN-02:10 | 153.96 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.88 | 17.11 | 02-JAN-02:10 | 153.96 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.44 | 994.53 | 02-JAN-02:10 | 4859.35 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.50 | 31.84 | 02-JAN-02:10 | 286.55 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.50 | 31.84 | 02-JAN-02:10 | 286.55 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 20.73 | 252.99 | 10-JUN-05:00 | 1732.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 6.39 | 37.53 | 01-JAN-13:10 | 767.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 6.39 | 37.53 | 01-JAN-13:10 | 767.68 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 223.74 | 2792.53 | 10-JUN-05:00 | 16487.72 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 74.74 | 681.12 | 10-JUN-05:00 | 6458.51 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 74.74 | 681.12 | 10-JUN-05:00 | 6458.51 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 51.72 | 469.94 | 02-JAN-02:10 | 4229.48 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.72 | 469.94 | 02-JAN-02:10 | 4229.48 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.72 | 469.94 | 02-JAN-02:10 | 4229.48 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 189.81 | 2339.18 | 20-MAY-05:00 | 8096.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 13.95 | 89.87 | 20-MAY-05:00 | 1348.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 13.95 | 89.87 | 20-MAY-05:00 | 1348.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 189.81 | 2339.18 | 20-MAY-05:00 | 8096.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 13.95 | 89.87 | 20-MAY-05:00 | 1348.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 13.95 | 89.87 | 20-MAY-05:00 | 1348.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 439.77 | 5902.30 | 02-JAN-02:10 | 18508.51 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 8.66 | 78.67 | 02-JAN-02:10 | 708.07 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 8.66 | 78.67 | 02-JAN-02:10 | 708.07 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 13.68 | 124.34 | 02-JAN-02:10 | 1119.06 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.68 | 124.34 | 02-JAN-02:10 | 1119.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.68 | 124.34 | 02-JAN-02:10 | 1119.06 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.06 | 735.82 | 10-JAN-23:30 | 2787.88 | 23-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 421.57 | 2305.42 | 08-APR-00:10 | 114628.21 | 22-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.84 | 0.00 | 01-JAN-11:10 | 1306.51 | 29-AUG-04:00 |
MedTempRefrigeration:Refrigeration:Electricity | 21.13 | 639.20 | 10-JAN-16:10 | 716.18 | 08-AUG-13:10 |
Fans:Electricity | 578.77 | 13280.10 | 17-APR-03:00 | 29339.33 | 24-JUL-20:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityProduced:Facility | 155.59 | -0.00 | 06-JAN-08:20 | 32579.09 | 18-JUN-12:30 |
ElectricityProduced:Plant | 155.59 | -0.00 | 06-JAN-08:20 | 32579.09 | 18-JUN-12:30 |
Photovoltaic:ElectricityProduced | 163.08 | 0.00 | 01-JAN-00:10 | 33916.36 | 18-JUN-12:30 |
PowerConversion:ElectricityProduced | -7.49 | -1337.27 | 18-JUN-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 653.29 | 14355.57 | 09-AUG-02:20 | 37630.16 | 22-JUL-18:20 |
ExteriorEquipment:Electricity | 390.56 | 5777.95 | 02-JAN-02:20 | 23857.89 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.46 | 378.85 | 01-JUL-05:00 | 1269.61 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 3533.55 | 50997.56 | 19-MAY-11:50 | 268345.05 | 22-JUL-20:00 |
ElectricityPurchased:Plant | 3533.55 | 50997.56 | 19-MAY-11:50 | 268345.05 | 22-JUL-20:00 |
Cogeneration:ElectricityPurchased | 3533.55 | 50997.56 | 19-MAY-11:50 | 268345.05 | 22-JUL-20:00 |
General:Cogeneration:ElectricityPurchased | 3533.55 | 50997.56 | 19-MAY-11:50 | 268345.05 | 22-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 3533.55 | 50997.56 | 19-MAY-11:50 | 268345.05 | 22-JUL-20:00 |
ElectricityNet:Plant | 3533.55 | 50997.56 | 19-MAY-11:50 | 268345.05 | 22-JUL-20:00 |
Cogeneration:ElectricityNet | 3533.55 | 50997.56 | 19-MAY-11:50 | 268345.05 | 22-JUL-20:00 |
General:Cogeneration:ElectricityNet | 3533.55 | 50997.56 | 19-MAY-11:50 | 268345.05 | 22-JUL-20:00 |
General:Fans:Electricity | 578.77 | 13280.10 | 17-APR-03:00 | 29339.33 | 24-JUL-20:20 |
ExteriorLights:Electricity | 150.10 | 0.00 | 01-JAN-08:20 | 9571.94 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 150.10 | 0.00 | 01-JAN-08:20 | 9571.94 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 366.65 | 5383.28 | 01-JAN-00:10 | 22430.31 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.45 | 15.80 | 01-JAN-00:10 | 157.97 | 01-JAN-07:10 |
HeatRecovery:Electricity | 53.07 | 0.00 | 01-JAN-08:00 | 8265.52 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 53.07 | 0.00 | 01-JAN-08:00 | 8265.52 | 01-JAN-00:10 |
WaterSystems:Electricity | 90.74 | 1086.56 | 08-NOV-02:40 | 4738.76 | 23-FEB-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 08-NOV-02:40 | 4738.76 | 23-FEB-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 232.95 | 0.00 | 01-JAN-00:30 | 104717.87 | 22-JUL-18:10 |
General:Cooling:Electricity | 232.95 | 0.00 | 01-JAN-00:30 | 104717.87 | 22-JUL-18:10 |
Pumps:Electricity | 60.91 | 47.91 | 28-JUN-15:10 | 4088.86 | 30-APR-18:10 |
General:Pumps:Electricity | 60.91 | 47.91 | 28-JUN-15:10 | 4088.86 | 30-APR-18:10 |
WIRED_LTG_ELECTRICITY | 15.47 | 0.00 | 01-JAN-00:10 | 1275.80 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5376.95 | 26805.16 | 08-APR-01:10 | 442499.49 | 27-DEC-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3588.11 | 13443.27 | 26-JUN-15:20 | 354879.72 | 27-DEC-19:10 |
WaterSystems:NaturalGas | 2747.69 | 13443.27 | 16-JAN-16:20 | 242986.29 | 10-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2747.69 | 13443.27 | 16-JAN-16:20 | 242986.29 | 10-FEB-21:20 |
Heating:NaturalGas | 840.42 | 0.00 | 01-JAN-21:20 | 162316.77 | 28-DEC-16:20 |
Boiler:Heating:NaturalGas | 840.42 | 0.00 | 01-JAN-21:20 | 162316.77 | 28-DEC-16:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 680.49 | 0.00 | 01-JAN-00:30 | 425787.93 | 25-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 680.49 | 0.00 | 01-JAN-00:30 | 425787.93 | 25-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 680.49 | 0.00 | 01-JAN-00:30 | 425787.93 | 25-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-MAY-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-MAY-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-MAY-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-MAY-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-MAY-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-MAY-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 9606.36 | 125778.60 | 23-APR-14:00 | 1628429.21 | 25-JUN-18:10 |
EnergyTransfer:Building | 4237.43 | 79328.46 | 10-DEC-14:50 | 291971.38 | 22-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 682.69 | 9757.33 | 11-JAN-04:00 | 34025.00 | 23-JUL-10:40 |
Refrigeration:EnergyTransfer | 184.11 | 4054.28 | 10-JAN-23:20 | 10364.70 | 27-JUN-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.06 | 2027.14 | 10-JAN-23:20 | 5182.35 | 27-JUN-06:20 |
General:Refrigeration:EnergyTransfer | 92.06 | 2027.14 | 10-JAN-23:20 | 5182.35 | 27-JUN-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.06 | 2027.14 | 10-JAN-23:20 | 5182.35 | 27-JUN-06:20 |
EnergyTransfer:Plant | 3316.33 | 13540.07 | 08-APR-01:10 | 988456.42 | 25-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.62 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.43 | 2018.64 | 10-JAN-16:10 | 2555.91 | 08-AUG-13:10 |
EnergyTransfer:Zone:BASEMENT | 337.62 | 8846.30 | 20-MAR-14:00 | 13882.02 | 10-SEP-10:40 |
Heating:EnergyTransfer | 84.62 | 0.00 | 01-JAN-08:00 | 52214.57 | 12-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 84.62 | 0.00 | 01-JAN-08:00 | 52214.57 | 12-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4060.76 | 71395.84 | 12-JAN-15:00 | 288383.90 | 22-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 337.62 | 8846.30 | 20-MAR-14:00 | 13882.02 | 10-SEP-10:40 |
General:Cooling:EnergyTransfer | 4060.76 | 71395.84 | 12-JAN-15:00 | 288383.90 | 22-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 337.62 | 8846.30 | 20-MAR-14:00 | 13882.02 | 10-SEP-10:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 21.80 | 0.00 | 22-DEC-17:30 | 2172.94 | 27-SEP-13:20 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.37 | 0.00 | 01-JAN-00:10 | 588.11 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.37 | 0.00 | 01-JAN-00:10 | 588.11 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 21.43 | 0.00 | 02-JAN-07:10 | 2172.94 | 27-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 21.43 | 0.00 | 02-JAN-07:10 | 2172.94 | 27-SEP-13:20 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.75 | 298.12 | 12-JAN-14:30 | 1596.61 | 22-JUL-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.75 | 298.12 | 12-JAN-14:30 | 1596.61 | 22-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.75 | 298.12 | 12-JAN-14:30 | 1596.61 | 22-JUL-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 2.05 | 0.28 | 11-JAN-12:10 | 937.87 | 22-JUL-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 139.18 | 12-JAN-15:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 139.18 | 12-JAN-15:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 2.04 | 0.00 | 11-JAN-11:40 | 937.87 | 22-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 2.04 | 0.00 | 11-JAN-11:40 | 937.87 | 22-JUL-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.82 | 0.04 | 09-DEC-10:10 | 883.11 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 242.04 | 12-JAN-15:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 242.04 | 12-JAN-15:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.71 | 0.00 | 01-JAN-14:00 | 883.11 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.71 | 0.00 | 01-JAN-14:00 | 883.11 | 23-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 575.83 | 8218.95 | 30-DEC-06:00 | 38477.80 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 575.83 | 8218.95 | 30-DEC-06:00 | 38477.80 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 575.83 | 8218.95 | 30-DEC-06:00 | 38477.80 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 215.33 | 952.27 | 10-DEC-15:50 | 10832.87 | 22-JUL-18:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 215.33 | 952.27 | 10-DEC-15:50 | 10832.87 | 22-JUL-18:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 215.33 | 952.27 | 10-DEC-15:50 | 10832.87 | 22-JUL-18:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 731.11 | 10064.05 | 10-DEC-15:50 | 32932.82 | 22-JUL-18:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 731.11 | 10064.05 | 10-DEC-15:50 | 32932.82 | 22-JUL-18:00 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 731.11 | 10064.05 | 10-DEC-15:50 | 32932.82 | 22-JUL-18:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 29.57 | 0.00 | 01-JAN-08:00 | 7857.62 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 12.70 | 0.00 | 01-JAN-08:00 | 4388.56 | 12-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 12.70 | 0.00 | 01-JAN-08:00 | 4388.56 | 12-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 16.88 | 0.00 | 01-JAN-00:10 | 7857.62 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 16.88 | 0.00 | 01-JAN-00:10 | 7857.62 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 26.27 | 0.00 | 01-JAN-08:00 | 7572.85 | 22-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 15.27 | 0.00 | 01-JAN-08:00 | 4546.82 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 15.27 | 0.00 | 01-JAN-08:00 | 4546.82 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 10.99 | 0.00 | 01-JAN-00:10 | 7572.85 | 22-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 10.99 | 0.00 | 01-JAN-00:10 | 7572.85 | 22-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 110.38 | 0.00 | 01-JAN-00:10 | 29569.61 | 25-SEP-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 110.38 | 0.00 | 01-JAN-00:10 | 29569.61 | 25-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 110.38 | 0.00 | 01-JAN-00:10 | 29569.61 | 25-SEP-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 221.01 | 0.00 | 01-JAN-08:00 | 54383.82 | 22-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 6.27 | 0.00 | 01-JAN-00:10 | 26302.17 | 11-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 6.27 | 0.00 | 01-JAN-00:10 | 26302.17 | 11-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 214.75 | 0.00 | 01-JAN-08:00 | 54383.82 | 22-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 214.75 | 0.00 | 01-JAN-08:00 | 54383.82 | 22-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 29.41 | 0.00 | 01-JAN-08:00 | 7091.12 | 23-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 12.63 | 0.00 | 01-JAN-08:00 | 4366.09 | 12-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 12.63 | 0.00 | 01-JAN-08:00 | 4366.09 | 12-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 16.78 | 0.00 | 01-JAN-00:10 | 7091.12 | 23-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 16.78 | 0.00 | 01-JAN-00:10 | 7091.12 | 23-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 26.59 | 0.00 | 01-JAN-08:00 | 7861.16 | 22-JUL-08:50 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 15.16 | 0.00 | 01-JAN-08:00 | 4636.89 | 12-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 15.16 | 0.00 | 01-JAN-08:00 | 4636.89 | 12-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 11.44 | 0.00 | 01-JAN-00:10 | 7861.16 | 22-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 11.44 | 0.00 | 01-JAN-00:10 | 7861.16 | 22-JUL-08:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 130.01 | 0.56 | 31-DEC-14:50 | 8074.00 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.24 | 0.00 | 01-JAN-00:10 | 1305.46 | 10-DEC-16:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.24 | 0.00 | 01-JAN-00:10 | 1305.46 | 10-DEC-16:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 129.77 | 0.00 | 03-JAN-09:30 | 8074.00 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 129.77 | 0.00 | 03-JAN-09:30 | 8074.00 | 23-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.66 | 0.00 | 01-JAN-08:00 | 2185.37 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.32 | 0.00 | 01-JAN-08:00 | 1406.99 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.32 | 0.00 | 01-JAN-08:00 | 1406.99 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.34 | 0.00 | 01-JAN-00:10 | 2185.37 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.34 | 0.00 | 01-JAN-00:10 | 2185.37 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.96 | 0.00 | 01-JAN-08:00 | 2036.96 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.16 | 0.00 | 01-JAN-08:00 | 1459.91 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.16 | 0.00 | 01-JAN-08:00 | 1459.91 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.80 | 0.00 | 01-JAN-00:10 | 2036.96 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.80 | 0.00 | 01-JAN-00:10 | 2036.96 | 15-JUN-18:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 44.32 | 0.00 | 01-JAN-08:00 | 11849.50 | 12-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 10.19 | 0.00 | 01-JAN-08:00 | 6107.85 | 30-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 10.19 | 0.00 | 01-JAN-08:00 | 6107.85 | 30-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 34.12 | 0.00 | 01-JAN-00:10 | 11849.50 | 12-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 34.12 | 0.00 | 01-JAN-00:10 | 11849.50 | 12-SEP-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 460.05 | 8497.60 | 12-JAN-15:00 | 20085.07 | 22-JUL-18:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 460.05 | 8497.60 | 12-JAN-15:00 | 20085.07 | 22-JUL-18:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 460.05 | 8497.60 | 12-JAN-15:00 | 20085.07 | 22-JUL-18:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 486.10 | 10033.03 | 12-JAN-15:00 | 20718.28 | 22-JUL-18:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 486.10 | 10033.03 | 12-JAN-15:00 | 20718.28 | 22-JUL-18:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 486.10 | 10033.03 | 12-JAN-15:00 | 20718.28 | 22-JUL-18:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 590.64 | 7457.48 | 12-JAN-04:00 | 28945.01 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 590.64 | 7457.48 | 12-JAN-04:00 | 28945.01 | 23-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 45.11 | 0.11 | 11-JAN-17:00 | 4439.50 | 22-JUL-14:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.20 | 0.00 | 01-JAN-00:10 | 1065.81 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.20 | 0.00 | 01-JAN-00:10 | 1065.81 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 44.91 | 0.00 | 02-JAN-07:10 | 4439.50 | 22-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 44.91 | 0.00 | 02-JAN-07:10 | 4439.50 | 22-JUL-14:10 |
PlantLoopHeatingDemand:Facility | 1545.92 | 10164.42 | 18-AUG-03:00 | 154376.60 | 28-DEC-16:20 |
PlantLoopHeatingDemand:Plant | 798.36 | 10164.42 | 18-AUG-03:00 | 55874.51 | 10-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 798.36 | 10164.42 | 18-AUG-03:00 | 55874.51 | 10-FEB-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 798.36 | 10164.42 | 18-AUG-03:00 | 55874.51 | 10-FEB-07:30 |
EnergyTransfer:HVAC | 2052.60 | 0.00 | 28-JUN-15:10 | 425878.10 | 25-JUN-18:10 |
HeatingCoils:EnergyTransfer | 747.55 | 0.00 | 15-APR-20:20 | 136332.56 | 28-DEC-16:20 |
PlantLoopHeatingDemand:HVAC | 747.55 | 0.00 | 15-APR-20:20 | 136332.56 | 28-DEC-16:20 |
HeatingCoils:PlantLoopHeatingDemand | 747.55 | 0.00 | 15-APR-20:20 | 136332.56 | 28-DEC-16:20 |
CoolingCoils:EnergyTransfer | 680.49 | 0.00 | 01-JAN-00:30 | 425787.93 | 25-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 623.86 | 0.00 | 01-JAN-08:00 | 235897.49 | 12-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 0.70 | 0.00 | 01-JAN-00:10 | 19392.31 | 12-JUN-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 798.36 | 10164.42 | 18-AUG-03:00 | 55874.51 | 10-FEB-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 798.36 | 10164.42 | 18-AUG-03:00 | 55874.51 | 10-FEB-07:30 |
Boilers:EnergyTransfer | 739.36 | 0.00 | 01-JAN-21:20 | 143100.12 | 28-DEC-16:20 |
Chillers:EnergyTransfer | 726.80 | 0.00 | 01-JAN-00:30 | 426710.27 | 25-JUN-18:10 |
HeatRejection:EnergyTransfer | 959.75 | 0.00 | 01-JAN-00:30 | 527001.65 | 25-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 959.75 | 0.00 | 01-JAN-00:30 | 527001.65 | 25-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -337.619 | 0.000 | 0.000 | 148.659 | 87.597 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -41.742 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.369 | -21.432 | 0.000 | 0.000 | 15.699 | 3.964 | 10.186 | 11.685 | 0.000 | 0.004 | 0.000 | 0.000 | -8.139 | 0.000 | -4.823 | -7.512 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -31.747 | 0.000 | 0.000 | 17.995 | 4.591 | 11.795 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -1.864 | -0.773 |
MECH_FLR_1 | 0.000 | 0.000 | 0.004 | -2.043 | 0.000 | 0.000 | 3.526 | 8.213 | 12.471 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -4.899 | -17.276 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.107 | -11.710 | 0.000 | 0.000 | 3.026 | 1.883 | 3.598 | 0.000 | 0.000 | 0.006 | 5.531 | 0.000 | 0.000 | 0.000 | -2.440 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -575.833 | 0.000 | 0.000 | 10.551 | 3.504 | 658.131 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -7.152 | -89.206 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -215.326 | 0.000 | 0.000 | 205.816 | 6.388 | 14.341 | 33.259 | 0.000 | 0.022 | 0.000 | 0.000 | -22.545 | 0.000 | -10.541 | -11.413 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -731.109 | 0.000 | 0.000 | 587.223 | 74.740 | 148.998 | 43.237 | 0.000 | 0.053 | 0.000 | 0.000 | -31.631 | 0.000 | -31.622 | -59.889 |
ROOM_1_FLR_3 | 17.969 | -12.374 | 0.000 | -9.772 | 0.000 | 0.000 | 9.758 | 4.922 | 10.478 | 21.766 | 0.000 | 0.024 | 0.000 | 0.000 | -18.267 | 0.000 | -11.420 | -13.084 |
ROOM_2_FLR_3 | 20.854 | -6.627 | 0.000 | -9.948 | 0.000 | 0.000 | 9.725 | 4.922 | 10.477 | 14.722 | 0.000 | 0.016 | 0.000 | 0.000 | -18.636 | 0.000 | -11.703 | -13.802 |
ROOM_3_MULT19_FLR_3 | 0.000 | -97.820 | 0.000 | -12.560 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 127.886 | 0.000 | 0.009 | 0.008 | 0.000 | -123.893 | 0.000 | -74.260 | -73.136 |
ROOM_4_MULT19_FLR_3 | 33.123 | -107.405 | 0.000 | -134.194 | 0.000 | 0.000 | 184.450 | 58.793 | 195.050 | 31.592 | 0.000 | 0.116 | 0.000 | 0.000 | -103.970 | 0.000 | -70.180 | -87.374 |
ROOM_5_FLR_3 | 17.792 | -12.150 | 0.000 | -9.792 | 0.000 | 0.000 | 9.749 | 4.922 | 10.478 | 21.889 | 0.000 | 0.024 | 0.000 | 0.000 | -17.919 | 0.000 | -11.454 | -13.540 |
ROOM_6_FLR_3 | 20.639 | -7.004 | 0.000 | -9.916 | 0.000 | 0.000 | 9.735 | 4.922 | 10.477 | 14.733 | 0.000 | 0.016 | 0.000 | 0.000 | -18.126 | 0.000 | -11.603 | -13.872 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.241 | -129.773 | 0.000 | 0.000 | 123.065 | 51.719 | 0.000 | 19.331 | 0.000 | 0.025 | 0.000 | 0.000 | -23.064 | 0.000 | -13.253 | -28.291 |
ROOM_1_FLR_6 | 6.770 | -3.348 | 0.000 | -2.442 | 0.000 | 0.000 | 2.443 | 1.231 | 2.620 | 5.400 | 0.000 | 0.006 | 0.000 | 0.000 | -4.505 | 0.000 | -2.876 | -5.298 |
ROOM_2_FLR_6 | 7.672 | -1.807 | 0.000 | -2.499 | 0.000 | 0.000 | 2.430 | 1.230 | 2.619 | 3.634 | 0.000 | 0.004 | 0.000 | 0.000 | -4.600 | 0.000 | -2.950 | -5.734 |
ROOM_3_MULT9_FLR_6 | 16.937 | -25.038 | 0.000 | -15.828 | 0.000 | 0.000 | 21.857 | 6.962 | 23.098 | 30.213 | 0.000 | 0.035 | 0.000 | 0.000 | -21.290 | 0.000 | -14.148 | -22.799 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -460.048 | 0.000 | 0.000 | 346.228 | 13.953 | 175.857 | 3.677 | 0.000 | 0.012 | 0.000 | 0.000 | -12.001 | 0.000 | -7.162 | -60.518 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -486.104 | 0.000 | 0.000 | 339.982 | 13.953 | 175.857 | 3.507 | 0.000 | 0.011 | 0.000 | 0.000 | -12.515 | 0.000 | -7.332 | -27.358 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -590.626 | 0.000 | 0.000 | 27.948 | 8.658 | 540.650 | 14.021 | 0.000 | 0.004 | 13.400 | 0.000 | -6.724 | 0.000 | -7.332 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.203 | -44.907 | 0.000 | 0.000 | 31.165 | 13.684 | 0.000 | 9.204 | 0.000 | 0.004 | 7.695 | 0.000 | -10.766 | 0.000 | -6.282 | -0.000 |
Total Facility | 141.755 | -273.573 | 0.924 | -3845.229 | 0.000 | 0.000 | 2111.029 | 439.529 | 2355.282 | 409.757 | 0.000 | 0.403 | 26.635 | 0.000 | -458.591 | 0.000 | -315.296 | -592.617 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-SEP-10:35 | 0.00 | 0.00 | 0.00 | -13941.43 | 0.00 | 0.00 | 2471.05 | 2387.82 | 4055.80 | 0.00 | 0.00 | 0.00 | 5026.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 27-SEP-13:30 | 0.00 | 0.00 | 0.00 | -2173.06 | 0.00 | 0.00 | 150.60 | 90.05 | 252.59 | 3277.66 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -29.30 | -1568.55 |
RETAIL_2_FLR_1 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 | -1602.21 | 0.00 | 0.00 | 569.24 | 291.98 | 668.57 | 0.00 | 0.00 | 31.07 | 41.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 22-JUL-20:53 | 0.00 | 0.00 | 0.00 | -938.25 | 0.00 | 0.00 | 129.08 | 522.41 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -21.29 | -398.85 |
STORAGE_FLR_1 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -885.94 | 0.00 | 0.00 | 48.44 | 51.32 | 101.96 | 0.00 | 0.00 | 0.00 | 689.20 | 0.00 | -0.00 | 0.00 | -4.97 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -38477.36 | 0.00 | 0.00 | 408.86 | 286.55 | 44299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -43.99 | -6473.43 |
CAFE_FLR_1 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -10839.33 | 0.00 | 0.00 | 3374.49 | 56.30 | 406.43 | 5631.19 | 0.00 | 0.00 | 1388.52 | 0.00 | -0.00 | 0.00 | -17.59 | 0.00 |
LOBBY_FLR_1 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 | -33011.74 | 0.00 | 0.00 | 19190.85 | 4320.03 | 8445.65 | 1602.52 | 0.00 | 510.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1057.95 |
ROOM_1_FLR_3 | 14-APR-15:11 | 0.00 | -9970.07 | 0.00 | -533.24 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 5807.57 | 0.00 | 0.00 | 4446.90 | 0.00 | -0.00 | 0.00 | -292.71 | 0.00 |
ROOM_2_FLR_3 | 14-JUL-18:01 | 0.00 | -8938.72 | 0.00 | -692.48 | 0.00 | 0.00 | 293.56 | 337.15 | 484.60 | 3185.59 | 0.00 | 0.00 | 5619.65 | 0.00 | -0.00 | 0.00 | -289.37 | 0.00 |
ROOM_3_MULT19_FLR_3 | 25-SEP-13:30 | 0.00 | -29570.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 38975.37 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -754.76 | -12269.64 |
ROOM_4_MULT19_FLR_3 | 21-JUL-15:12 | 0.00 | -52377.32 | 0.00 | -10294.96 | 0.00 | 0.00 | 4470.40 | 1267.05 | 3726.41 | 7308.13 | 0.00 | 622.87 | 45277.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-APR-15:11 | 0.00 | -9012.90 | 0.00 | -530.92 | 0.00 | 0.00 | 235.28 | 106.08 | 200.18 | 1564.09 | 0.00 | 0.00 | 7730.00 | 0.00 | -0.00 | 0.00 | -291.81 | 0.00 |
ROOM_6_FLR_3 | 22-JUL-08:41 | 0.00 | -8822.90 | 0.00 | -936.58 | 0.00 | 0.00 | 109.97 | 212.14 | 653.15 | 5056.87 | 0.00 | 0.00 | 3762.09 | 0.00 | -0.00 | 0.00 | -34.74 | 0.00 |
CORRIDOR_FLR_3 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -8088.99 | 0.00 | 0.00 | 1947.05 | 1409.83 | 0.00 | 3469.67 | 0.00 | 0.00 | 1304.23 | 0.00 | -0.00 | 0.00 | -41.79 | 0.00 |
ROOM_1_FLR_6 | 14-APR-15:11 | 0.00 | -2630.56 | 0.00 | -133.76 | 0.00 | 0.00 | 58.82 | 26.52 | 50.05 | 1441.21 | 0.00 | 0.00 | 1261.51 | 0.00 | -0.00 | 0.00 | -73.78 | 0.00 |
ROOM_2_FLR_6 | 28-JUL-18:11 | 0.00 | -2407.70 | 0.00 | -176.99 | 0.00 | 0.00 | 73.18 | 84.29 | 121.15 | 528.04 | 0.00 | 0.00 | 1857.95 | 0.00 | -0.00 | 0.00 | -79.91 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11-MAY-18:01 | 0.00 | -14716.67 | 0.00 | -864.41 | 0.00 | 0.00 | 771.86 | 476.93 | 1068.37 | 0.00 | 0.00 | 0.00 | 14705.82 | 0.00 | -14.92 | 0.00 | -1426.98 | 0.00 |
BANQUET_FLR_6 | 22-JUL-18:00 | 0.00 | 0.00 | 0.00 | -20085.06 | 0.00 | 0.00 | 11520.81 | 539.25 | 6747.90 | 1036.55 | 0.00 | 120.67 | 119.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 22-JUL-18:00 | 0.00 | 0.00 | 0.00 | -20718.27 | 0.00 | 0.00 | 11337.34 | 539.25 | 6747.90 | 1020.14 | 0.00 | 116.16 | 957.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -28944.29 | 0.00 | 0.00 | 464.19 | 236.02 | 23951.61 | 2399.39 | 0.00 | 0.00 | 1939.21 | 0.00 | -0.00 | 0.00 | -46.13 | 0.00 |
CORRIDOR_FLR_6 | 22-JUL-14:10 | 0.00 | 0.00 | 0.00 | -4439.07 | 0.00 | 0.00 | 462.69 | 310.85 | 0.00 | 1755.04 | 0.00 | 57.67 | 1852.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-18:02 | 0.00 | -116545.54 | 0.00 | -189602.86 | 0.00 | 0.00 | 68411.86 | 28691.00 | 113070.18 | 35843.31 | 0.00 | 4054.28 | 56077.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 10-JAN-07:55 | 0.00 | 0.00 | 594.91 | 0.00 | 0.00 | 0.00 | 357.98 | 180.10 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -769.77 | 0.00 | -346.71 | -449.53 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 12-JAN-15:00 | 0.00 | 0.00 | 139.18 | 0.00 | 0.00 | 0.00 | 43.84 | 186.57 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -254.85 | -424.02 |
STORAGE_FLR_1 | 12-JAN-15:00 | 0.00 | 0.00 | 242.04 | 0.00 | 0.00 | 0.00 | 33.72 | 42.77 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -147.03 | -260.72 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 30-DEC-16:11 | 7656.29 | 292.88 | 0.00 | -292.88 | 0.00 | 0.00 | 163.32 | 125.03 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1094.84 | 0.00 | -516.45 | -6554.60 |
ROOM_2_FLR_3 | 30-DEC-16:11 | 7447.93 | 291.30 | 0.00 | -291.30 | 0.00 | 0.00 | 163.32 | 125.01 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1090.27 | 0.00 | -515.81 | -6351.41 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 12-JAN-16:12 | 40715.73 | 4534.99 | 0.00 | -4534.99 | 0.00 | 0.00 | 5400.20 | 1267.05 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6951.22 | 0.00 | -3287.26 | -40870.91 |
ROOM_5_FLR_3 | 30-DEC-16:11 | 7445.73 | 291.32 | 0.00 | -291.32 | 0.00 | 0.00 | 163.32 | 125.03 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1091.13 | 0.00 | -515.85 | -6348.36 |
ROOM_6_FLR_3 | 30-DEC-16:11 | 7232.58 | 289.43 | 0.00 | -289.43 | 0.00 | 0.00 | 163.32 | 125.01 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1086.71 | 0.00 | -515.09 | -6140.35 |
CORRIDOR_FLR_3 | 10-DEC-16:00 | 0.00 | 0.00 | 1305.44 | 0.00 | 0.00 | 0.00 | 1385.81 | 939.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1356.41 | 0.00 | -593.25 | -1681.48 |
ROOM_1_FLR_6 | 30-DEC-16:11 | 2296.53 | 74.15 | 0.00 | -74.15 | 0.00 | 0.00 | 40.83 | 31.26 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -267.57 | 0.00 | -129.93 | -2026.43 |
ROOM_2_FLR_6 | 28-DEC-16:11 | 2223.86 | 73.56 | 0.00 | -73.56 | 0.00 | 0.00 | 73.50 | 26.52 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -266.10 | 0.00 | -122.88 | -1984.94 |
ROOM_3_MULT9_FLR_6 | 30-DEC-16:11 | 11609.28 | 477.32 | 0.00 | -477.32 | 0.00 | 0.00 | 367.48 | 176.84 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1260.13 | 0.00 | -598.51 | -10782.68 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-JAN-07:55 | 0.00 | 0.00 | 1076.34 | 0.00 | 0.00 | 0.00 | 733.30 | 621.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -972.58 | 0.00 | -432.27 | -1026.49 |
Total Facility | 30-DEC-16:11 | 3882.69 | 88922.40 | 2102.04 | -88922.40 | 0.00 | 0.00 | 36841.97 | 10599.20 | 74529.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25725.86 | 0.00 | -13485.24 | -88744.75 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 19.9401 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 19.8431 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.9052 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5246 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.003540 | 12.5400 | 0.000610 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.003540 | 142.3000 | 0.000914 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.000963 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0694 | 2.0694 | 1.2810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3185 | 0.3185 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1955 | 0.1955 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1804 | 0.1804 | 0.0018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0818 | 0.0818 | 0.0818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2671 | 3.2671 | 0.0327 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4301 | 1.4301 | 1.0140 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4268 | 4.4268 | 2.8420 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0489 | 1.0489 | 0.7122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0190 | 2.0190 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1222 | 2.1222 | 1.7827 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1435 | 2.1435 | 0.5509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6370 | 0.6370 | 0.1885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 19.9401 | 19.8431 | 19.9401 | 10.5246 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2810 | 1.2810 | 1.2810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1592 | 0.1592 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1376 | 0.1376 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0902 | 0.0902 | 0.0018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0818 | 0.0818 | 0.0818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6336 | 1.6336 | 0.0327 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0140 | 1.0140 | 1.0140 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8420 | 2.8420 | 2.8420 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7122 | 0.7122 | 0.7122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7808 | 1.7808 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7827 | 1.7827 | 1.7827 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0718 | 1.0718 | 0.5509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3185 | 0.3185 | 0.1885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.9052 | 10.5246 | 10.5246 | 10.5246 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 19.17 |
Number of hours not met | 19.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 840.42 | 162316.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 232.95 | 104717.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 439.53 | 36244.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 150.10 | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.46 | 1269.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 366.65 | 22430.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.45 | 157.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 578.77 | 29339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 60.91 | 4088.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 53.07 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.76 | 2747.69 | 242986.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.84 | 1306.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.13 | 716.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.52 | 3689.14 |
Natural Gas | 1788.84 | 5376.95 |
Additional | 0.00 | 0.00 |
Total | 3481.35 | 9066.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 163.08 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 38.74 |
Space Heating | 0.00 |
Space Cooling | 20.53 |
Fans (All) | 51.01 |
Service Water Heating | 8.00 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 325.17 |
Subtotal | 325.17 |
Natural Gas [MJ/m2] | |
Space Heating | 74.08 |
Service Water Heating | 242.19 |
Miscellaneous (All) | 473.94 |
Subtotal | 473.94 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.85 |
Space Heating | 9.27 |
Space Cooling | 2.57 |
Fans (All) | 6.38 |
Service Water Heating | 31.31 |
Receptacle Equipment | 37.91 |
Miscellaneous | 7.71 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_KITCHEN | 2022. | 8760. |
LTG_SCH_DINING | 1877. | 8760. |
LTG_SCH_BASEMENT | 2095. | 8760. |
LTG_SCH_LOBBY | 2166. | 8760. |
LTG_SCH_STORAGE | 1543. | 8760. |
LTG_SCH_MECHANIC | 2022. | 8760. |
LTG_SCH_LAUNDRY | 2527. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2166. | 8760. |
LTG_SCH_RETAIL | 2296. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8596.50 | 163.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8596.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 163.50 | 0.00 | 0.00 | 0.00 |
Average | 8751.95 | 8.05 | 0.00 | 0.00 | 0.00 |
Sum | 192543.00 | 177.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4150.83 | 3.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 3.17 | 0.00 | 0.00 | 0.00 |
Average | 288886.90 | 0.14 | 0.00 | 0.00 | 0.00 |
Sum | 6355511.83 | 3.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8323.50 | 436.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8722.67 | 37.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8323.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 436.50 | 0.00 | 0.00 | 0.00 |
Average | 8737.64 | 22.36 | 0.00 | 0.00 | 0.00 |
Sum | 192228.17 | 491.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.67 | 2.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4136.50 | 17.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1244968.33 | 746.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1244931.00 | 784.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108262.83 | 6.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 784.00 | 0.00 | 0.00 | 0.00 |
Average | 288816.29 | 70.76 | 0.00 | 0.00 | 0.00 |
Sum | 6353958.33 | 1556.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280101E+11 | 12371.71 | 20-JAN-21:00 | 1.00 | 0.17 | 0.696830E+10 | 4302.40 | 27-JAN-23:10 | 5.10 | 4.59 |
February | 0.246982E+11 | 12206.03 | 01-FEB-21:00 | 6.00 | 5.05 | 0.618884E+10 | 4267.31 | 01-FEB-23:10 | 5.00 | 4.51 |
March | 0.265539E+11 | 11914.64 | 25-MAR-10:35 | 11.33 | 8.27 | 0.672258E+10 | 4181.29 | 01-MAR-23:10 | 11.33 | 8.27 |
April | 0.262612E+11 | 12957.88 | 30-APR-10:35 | 19.33 | 11.65 | 0.647097E+10 | 4130.24 | 14-APR-22:10 | 19.33 | 11.65 |
May | 0.271720E+11 | 12731.93 | 22-MAY-18:10 | 19.00 | 14.26 | 0.668756E+10 | 4137.18 | 04-MAY-22:10 | 19.00 | 14.26 |
June | 0.271287E+11 | 13235.07 | 25-JUN-10:35 | 20.00 | 13.96 | 0.656343E+10 | 4196.71 | 16-JUN-22:10 | 20.00 | 13.96 |
July | 0.291983E+11 | 13884.04 | 23-JUL-10:35 | 21.00 | 15.99 | 0.692145E+10 | 4305.83 | 28-JUL-22:10 | 12.00 | 11.46 |
August | 0.297318E+11 | 13678.43 | 19-AUG-10:35 | 18.00 | 14.38 | 0.704244E+10 | 4340.58 | 25-AUG-22:10 | 14.83 | 13.13 |
September | 0.295521E+11 | 13941.40 | 10-SEP-10:35 | 18.67 | 14.65 | 0.697963E+10 | 4479.62 | 29-SEP-22:10 | 12.00 | 8.00 |
October | 0.305118E+11 | 13805.79 | 07-OCT-10:35 | 14.67 | 10.10 | 0.732036E+10 | 4525.31 | 06-OCT-22:10 | 14.67 | 10.10 |
November | 0.293942E+11 | 13323.98 | 08-NOV-19:10 | 11.00 | 11.00 | 0.711538E+10 | 4534.38 | 17-NOV-23:10 | 6.00 | 5.49 |
December | 0.294063E+11 | 13030.30 | 01-DEC-21:00 | 4.00 | 3.53 | 0.722164E+10 | 4502.48 | 01-DEC-23:10 | 5.00 | 4.16 |
Annual Sum or Average | 0.337619E+12 | 0.822026E+11 | ||||||||
Minimum of Months | 0.246982E+11 | 11914.64 | 1.00 | 0.17 | 0.618884E+10 | 4130.24 | 5.00 | 4.16 | ||
Maximum of Months | 0.305118E+11 | 13941.40 | 21.00 | 15.99 | 0.732036E+10 | 4534.38 | 20.00 | 14.26 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.782185E+09 | 1220.50 | 21-JAN-11:35 | 6.33 | 5.22 | 0.621874E+09 | 370.82 | 23-JAN-22:40 | 8.00 | 7.45 |
February | 0.887422E+09 | 1241.45 | 04-FEB-11:50 | 7.83 | 5.15 | 0.563539E+09 | 372.14 | 27-FEB-22:30 | 4.50 | 4.50 |
March | 0.926285E+09 | 1079.06 | 25-MAR-10:35 | 11.33 | 8.27 | 0.623041E+09 | 372.53 | 20-MAR-21:30 | 11.33 | 8.27 |
April | 0.217017E+10 | 1842.94 | 30-APR-13:10 | 22.17 | 13.02 | 0.638663E+09 | 454.38 | 28-APR-21:30 | 22.17 | 13.02 |
May | 0.226862E+10 | 1437.31 | 23-MAY-10:35 | 20.00 | 14.59 | 0.660602E+09 | 461.26 | 22-MAY-21:30 | 20.00 | 14.59 |
June | 0.257780E+10 | 1638.77 | 13-JUN-14:10 | 25.25 | 17.52 | 0.670368E+09 | 479.90 | 13-JUN-21:19 | 14.00 | 12.84 |
July | 0.285079E+10 | 2103.54 | 22-JUL-13:30 | 28.00 | 16.51 | 0.716103E+09 | 486.72 | 21-JUL-21:30 | 28.00 | 16.51 |
August | 0.298127E+10 | 1922.76 | 19-AUG-13:00 | 21.00 | 15.44 | 0.732433E+09 | 482.75 | 14-AUG-21:30 | 21.00 | 15.44 |
September | 0.278545E+10 | 2173.16 | 27-SEP-13:20 | 21.33 | 13.25 | 0.685759E+09 | 476.99 | 12-SEP-21:40 | 21.33 | 13.25 |
October | 0.178460E+10 | 1729.61 | 07-OCT-13:20 | 17.00 | 9.43 | 0.641307E+09 | 425.60 | 03-OCT-21:40 | 17.00 | 9.43 |
November | 0.987400E+09 | 1243.57 | 11-NOV-11:35 | 9.00 | 6.87 | 0.601598E+09 | 373.28 | 08-NOV-23:10 | 9.00 | 6.87 |
December | 0.430039E+09 | 1102.71 | 08-DEC-11:40 | 6.67 | 4.51 | 0.620251E+09 | 364.13 | 29-DEC-04:19 | 3.00 | 0.77 |
Annual Sum or Average | 0.214320E+11 | 0.777554E+10 | ||||||||
Minimum of Months | 0.430039E+09 | 1079.06 | 6.33 | 4.51 | 0.563539E+09 | 364.13 | 3.00 | 0.77 | ||
Maximum of Months | 0.298127E+10 | 2173.16 | 28.00 | 17.52 | 0.732433E+09 | 486.72 | 28.00 | 16.51 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225588E+10 | 1183.35 | 19-JAN-21:00 | 3.00 | 2.16 | 0.739905E+09 | 472.74 | 18-JAN-23:10 | 3.00 | 2.16 |
February | 0.210348E+10 | 1182.90 | 27-FEB-21:00 | 6.00 | 6.00 | 0.671918E+09 | 472.99 | 27-FEB-23:10 | 3.83 | 3.83 |
March | 0.235890E+10 | 1204.78 | 20-MAR-20:00 | 7.00 | 4.68 | 0.750709E+09 | 476.92 | 20-MAR-22:10 | 4.30 | 3.44 |
April | 0.272957E+10 | 1457.62 | 29-APR-18:10 | 19.67 | 12.19 | 0.758256E+09 | 523.57 | 28-APR-22:10 | 19.67 | 12.19 |
May | 0.286560E+10 | 1463.91 | 22-MAY-18:10 | 19.00 | 14.26 | 0.790264E+09 | 529.97 | 23-MAY-22:10 | 11.83 | 9.72 |
June | 0.296840E+10 | 1509.62 | 13-JUN-18:00 | 23.90 | 16.48 | 0.790189E+09 | 543.40 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.316224E+10 | 1602.20 | 22-JUL-18:10 | 29.83 | 16.84 | 0.827228E+09 | 546.69 | 21-JUL-22:10 | 29.83 | 16.84 |
August | 0.319897E+10 | 1523.93 | 14-AUG-18:10 | 26.48 | 13.67 | 0.837079E+09 | 538.70 | 14-AUG-22:10 | 15.83 | 11.49 |
September | 0.298493E+10 | 1495.25 | 13-SEP-18:10 | 17.50 | 14.11 | 0.792557E+09 | 537.23 | 13-SEP-22:10 | 11.83 | 10.27 |
October | 0.266811E+10 | 1333.71 | 01-OCT-10:35 | 13.67 | 9.65 | 0.771149E+09 | 508.64 | 03-OCT-22:10 | 7.67 | 6.26 |
November | 0.231362E+10 | 1202.53 | 10-NOV-21:00 | 4.00 | 4.00 | 0.724230E+09 | 476.62 | 08-NOV-23:10 | 4.00 | 4.00 |
December | 0.213737E+10 | 1150.15 | 20-DEC-21:00 | 7.00 | 6.47 | 0.734697E+09 | 464.99 | 21-DEC-23:10 | 3.17 | 3.09 |
Annual Sum or Average | 0.317470E+11 | 0.918818E+10 | ||||||||
Minimum of Months | 0.210348E+10 | 1150.15 | 3.00 | 2.16 | 0.671918E+09 | 464.99 | 3.00 | 2.16 | ||
Maximum of Months | 0.319897E+10 | 1602.20 | 29.83 | 16.84 | 0.837079E+09 | 546.69 | 29.83 | 16.84 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37948112.07 | 18.72 | 19-JAN-21:00 | 3.00 | 2.16 | 0.170511E+09 | 112.23 | 25-JAN-22:10 | 8.00 | 7.45 |
February | 35424055.27 | 18.47 | 08-FEB-21:00 | 5.00 | 4.08 | 0.155544E+09 | 111.32 | 08-FEB-22:10 | 5.67 | 3.99 |
March | 41317933.33 | 19.40 | 20-MAR-20:00 | 7.00 | 4.68 | 0.178636E+09 | 114.97 | 20-MAR-21:10 | 4.90 | 3.99 |
April | 75569021.79 | 530.64 | 30-APR-19:15 | 21.67 | 13.25 | 0.185737E+09 | 120.45 | 28-APR-23:10 | 21.67 | 13.25 |
May | 0.105364E+09 | 575.65 | 23-MAY-20:00 | 14.00 | 10.69 | 0.196161E+09 | 120.45 | 26-MAY-23:19 | 10.67 | 9.21 |
June | 0.319438E+09 | 854.66 | 13-JUN-20:00 | 17.00 | 13.95 | 0.197154E+09 | 120.45 | 26-JUN-21:49 | 14.00 | 14.00 |
July | 0.520434E+09 | 938.25 | 22-JUL-20:53 | 22.00 | 15.84 | 0.204179E+09 | 120.45 | 11-JUL-00:10 | 22.00 | 15.84 |
August | 0.512462E+09 | 788.11 | 17-AUG-21:00 | 15.00 | 13.19 | 0.205753E+09 | 120.45 | 25-AUG-21:10 | 15.83 | 13.97 |
September | 0.262646E+09 | 702.42 | 13-SEP-20:00 | 15.00 | 12.66 | 0.196393E+09 | 120.45 | 28-SEP-23:10 | 11.83 | 11.83 |
October | 53685328.42 | 255.12 | 02-OCT-20:00 | 9.00 | 7.43 | 0.190472E+09 | 120.45 | 10-OCT-21:19 | 8.67 | 8.67 |
November | 40383007.96 | 19.65 | 10-NOV-21:00 | 4.00 | 4.00 | 0.173566E+09 | 116.67 | 09-NOV-22:10 | 4.00 | 4.00 |
December | 37899683.84 | 17.91 | 05-DEC-21:00 | 7.00 | 6.46 | 0.168721E+09 | 108.75 | 05-DEC-22:10 | 4.00 | 3.52 |
Annual Sum or Average | 0.204257E+10 | 0.222283E+10 | ||||||||
Minimum of Months | 35424055.27 | 17.91 | 3.00 | 2.16 | 0.155544E+09 | 108.75 | 4.00 | 3.52 | ||
Maximum of Months | 0.520434E+09 | 938.25 | 22.00 | 15.84 | 0.205753E+09 | 120.45 | 22.00 | 15.84 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311146E+09 | 454.62 | 18-JAN-22:00 | 8.00 | 7.45 | 0.116690E+09 | 68.57 | 14-JAN-05:49 | 8.00 | 7.45 |
February | 0.282561E+09 | 403.36 | 07-FEB-22:00 | 7.00 | 7.00 | 0.105501E+09 | 68.57 | 09-FEB-05:10 | 2.83 | 2.46 |
March | 0.535589E+09 | 482.63 | 20-MAR-21:00 | 5.00 | 4.09 | 0.117239E+09 | 68.57 | 07-MAR-03:00 | 5.00 | 4.09 |
April | 0.108896E+10 | 800.43 | 30-APR-10:35 | 19.33 | 11.65 | 0.113500E+09 | 72.44 | 30-APR-23:10 | 11.87 | 8.94 |
May | 0.127432E+10 | 785.83 | 23-MAY-10:35 | 20.00 | 14.59 | 0.117788E+09 | 73.49 | 23-MAY-22:10 | 11.83 | 9.72 |
June | 0.154527E+10 | 821.92 | 13-JUN-10:35 | 22.00 | 15.85 | 0.117071E+09 | 76.15 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.167126E+10 | 885.91 | 23-JUL-10:35 | 21.00 | 15.99 | 0.122752E+09 | 76.73 | 21-JUL-22:10 | 21.00 | 15.99 |
August | 0.168460E+10 | 821.54 | 19-AUG-10:35 | 18.00 | 14.38 | 0.123422E+09 | 75.69 | 17-AUG-22:10 | 18.00 | 14.38 |
September | 0.152506E+10 | 787.58 | 13-SEP-10:35 | 19.67 | 15.19 | 0.116133E+09 | 74.51 | 13-SEP-22:10 | 11.83 | 10.27 |
October | 0.102819E+10 | 646.93 | 02-OCT-20:00 | 9.00 | 7.43 | 0.116840E+09 | 70.22 | 02-OCT-22:10 | 8.00 | 6.98 |
November | 0.562697E+09 | 561.45 | 08-NOV-22:00 | 11.00 | 11.00 | 0.112879E+09 | 68.71 | 08-NOV-23:10 | 11.00 | 11.00 |
December | 0.200753E+09 | 326.30 | 05-DEC-21:00 | 7.00 | 6.46 | 0.116690E+09 | 68.57 | 29-DEC-04:49 | 3.00 | 0.60 |
Annual Sum or Average | 0.117104E+11 | 0.139650E+10 | ||||||||
Minimum of Months | 0.200753E+09 | 326.30 | 5.00 | 4.09 | 0.105501E+09 | 68.57 | 2.83 | 0.60 | ||
Maximum of Months | 0.168460E+10 | 885.91 | 22.00 | 15.99 | 0.123422E+09 | 76.73 | 21.00 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474439E+11 | 37029.20 | 23-JAN-21:00 | 9.00 | 7.43 | 0.649337E+09 | 381.56 | 13-JAN-22:10 | 9.00 | 7.43 |
February | 0.429508E+11 | 36994.89 | 22-FEB-21:00 | 5.00 | 4.08 | 0.587073E+09 | 381.56 | 09-FEB-22:19 | 5.00 | 4.08 |
March | 0.480473E+11 | 37135.51 | 30-MAR-20:00 | 7.00 | 4.67 | 0.652386E+09 | 381.56 | 22-MAR-04:40 | 7.00 | 4.67 |
April | 0.476477E+11 | 38042.98 | 28-APR-20:00 | 13.00 | 9.28 | 0.629495E+09 | 381.56 | 11-APR-23:30 | 13.00 | 9.28 |
May | 0.494462E+11 | 38179.14 | 22-MAY-19:57 | 17.00 | 12.89 | 0.650708E+09 | 381.58 | 11-MAY-21:10 | 17.00 | 12.89 |
June | 0.486155E+11 | 38462.77 | 13-JUN-20:00 | 17.00 | 13.95 | 0.630868E+09 | 381.59 | 08-JUN-21:10 | 17.00 | 13.95 |
July | 0.503764E+11 | 38477.80 | 21-JUL-20:00 | 21.00 | 15.02 | 0.649332E+09 | 381.54 | 10-JUL-23:49 | 21.00 | 15.02 |
August | 0.507042E+11 | 38349.07 | 14-AUG-20:00 | 20.70 | 12.26 | 0.652080E+09 | 381.60 | 09-AUG-21:10 | 20.70 | 12.26 |
September | 0.484251E+11 | 38171.32 | 13-SEP-20:00 | 15.00 | 12.66 | 0.629187E+09 | 381.55 | 01-SEP-01:10 | 15.00 | 12.66 |
October | 0.486748E+11 | 37536.19 | 06-OCT-20:00 | 8.00 | 6.07 | 0.649636E+09 | 381.55 | 07-OCT-04:10 | 2.33 | 2.26 |
November | 0.463807E+11 | 37162.61 | 08-NOV-21:00 | 11.00 | 11.00 | 0.628122E+09 | 381.57 | 01-NOV-22:10 | 11.00 | 11.00 |
December | 0.471197E+11 | 36863.87 | 20-DEC-21:00 | 7.00 | 6.47 | 0.649338E+09 | 381.56 | 27-DEC-00:20 | 1.67 | 1.38 |
Annual Sum or Average | 0.575832E+12 | 0.765756E+10 | ||||||||
Minimum of Months | 0.429508E+11 | 36863.87 | 5.00 | 4.08 | 0.587073E+09 | 381.54 | 1.67 | 1.38 | ||
Maximum of Months | 0.507042E+11 | 38477.80 | 21.00 | 15.02 | 0.652386E+09 | 381.60 | 21.00 | 15.02 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152979E+11 | 9282.22 | 15-JAN-11:35 | 8.67 | 6.43 | 0.840727E+10 | 5393.12 | 23-JAN-23:10 | 7.83 | 7.29 |
February | 0.144482E+11 | 9368.96 | 04-FEB-11:35 | 7.67 | 5.05 | 0.763031E+10 | 5361.38 | 27-FEB-22:40 | 4.33 | 4.33 |
March | 0.155646E+11 | 8228.61 | 20-MAR-18:05 | 7.83 | 5.10 | 0.850049E+10 | 5370.53 | 20-MAR-21:40 | 4.60 | 3.70 |
April | 0.189581E+11 | 10560.37 | 30-APR-10:35 | 19.33 | 11.65 | 0.848483E+10 | 5790.85 | 28-APR-21:40 | 19.33 | 11.65 |
May | 0.193620E+11 | 10013.33 | 22-MAY-18:10 | 19.00 | 14.26 | 0.876482E+10 | 5805.69 | 22-MAY-21:40 | 14.33 | 12.38 |
June | 0.198802E+11 | 10369.76 | 12-JUN-18:10 | 25.67 | 17.63 | 0.865906E+10 | 5864.28 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.213565E+11 | 10836.84 | 23-JUL-10:35 | 21.00 | 15.99 | 0.901127E+10 | 5933.30 | 21-JUL-21:40 | 21.00 | 15.99 |
August | 0.219916E+11 | 10510.33 | 14-AUG-18:10 | 26.48 | 13.67 | 0.915740E+10 | 5942.80 | 14-AUG-21:40 | 16.73 | 11.70 |
September | 0.209121E+11 | 10600.63 | 23-SEP-10:35 | 18.00 | 14.39 | 0.878289E+10 | 5955.89 | 12-SEP-22:10 | 18.00 | 14.39 |
October | 0.180417E+11 | 10125.09 | 07-OCT-10:35 | 14.67 | 10.10 | 0.868318E+10 | 5657.72 | 03-OCT-21:40 | 14.67 | 10.10 |
November | 0.153773E+11 | 9415.59 | 11-NOV-11:35 | 9.00 | 6.87 | 0.821130E+10 | 5414.95 | 08-NOV-23:10 | 9.00 | 6.87 |
December | 0.141355E+11 | 8404.20 | 03-DEC-11:35 | 6.67 | 4.17 | 0.835921E+10 | 5254.17 | 21-DEC-22:40 | 3.00 | 3.00 |
Annual Sum or Average | 0.215326E+12 | 0.102652E+12 | ||||||||
Minimum of Months | 0.141355E+11 | 8228.61 | 6.67 | 4.17 | 0.763031E+10 | 5254.17 | 3.00 | 3.00 | ||
Maximum of Months | 0.219916E+11 | 10836.84 | 26.48 | 17.63 | 0.915740E+10 | 5955.89 | 21.00 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.559328E+11 | 26409.95 | 18-JAN-22:00 | 8.00 | 7.45 | 0.267349E+11 | 17351.96 | 25-JAN-23:10 | 8.00 | 7.43 |
February | 0.514516E+11 | 26275.15 | 27-FEB-21:00 | 6.00 | 6.00 | 0.242682E+11 | 17255.54 | 27-FEB-23:10 | 3.83 | 3.83 |
March | 0.573795E+11 | 26724.48 | 20-MAR-20:00 | 7.00 | 4.68 | 0.271145E+11 | 17412.23 | 20-MAR-22:10 | 4.30 | 3.44 |
April | 0.616838E+11 | 30832.92 | 30-APR-10:35 | 19.33 | 11.65 | 0.271368E+11 | 18449.52 | 28-APR-22:10 | 19.33 | 11.65 |
May | 0.641355E+11 | 30648.97 | 22-MAY-18:10 | 19.00 | 14.26 | 0.281785E+11 | 18542.40 | 23-MAY-22:10 | 11.83 | 9.72 |
June | 0.648693E+11 | 31560.87 | 12-JUN-18:10 | 25.67 | 17.63 | 0.279323E+11 | 18841.36 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.685361E+11 | 33011.48 | 22-JUL-18:10 | 29.83 | 16.84 | 0.290563E+11 | 18986.61 | 21-JUL-22:10 | 29.83 | 16.84 |
August | 0.693134E+11 | 31863.04 | 14-AUG-18:10 | 26.48 | 13.67 | 0.294172E+11 | 18869.52 | 18-AUG-21:49 | 13.50 | 12.10 |
September | 0.656528E+11 | 31245.25 | 13-SEP-18:10 | 17.50 | 14.11 | 0.281026E+11 | 18878.87 | 12-SEP-22:10 | 17.50 | 14.11 |
October | 0.617955E+11 | 29190.48 | 01-OCT-10:35 | 13.67 | 9.65 | 0.278019E+11 | 18217.55 | 03-OCT-22:10 | 7.67 | 6.26 |
November | 0.560275E+11 | 26964.97 | 11-NOV-11:35 | 9.00 | 6.87 | 0.262237E+11 | 17514.15 | 08-NOV-23:10 | 9.00 | 6.87 |
December | 0.543296E+11 | 25814.06 | 20-DEC-21:00 | 7.00 | 6.47 | 0.265361E+11 | 17112.59 | 21-DEC-23:10 | 3.17 | 3.09 |
Annual Sum or Average | 0.731107E+12 | 0.328503E+12 | ||||||||
Minimum of Months | 0.514516E+11 | 25814.06 | 6.00 | 4.68 | 0.242682E+11 | 17112.59 | 3.17 | 3.09 | ||
Maximum of Months | 0.693134E+11 | 33011.48 | 29.83 | 17.63 | 0.294172E+11 | 18986.61 | 29.83 | 16.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12078720.15 | 1881.93 | 19-JAN-16:11 | 7.33 | 6.98 | 93783665.85 | 56.69 | 29-JAN-05:10 | 13.17 | 11.98 |
February | 23011441.70 | 2440.43 | 17-FEB-16:12 | 5.67 | 3.21 | 85241316.47 | 56.69 | 22-FEB-00:20 | 6.00 | 6.00 |
March | 21077893.66 | 1767.52 | 23-MAR-18:03 | 7.67 | 5.83 | 94414049.91 | 56.69 | 03-MAR-00:20 | 7.67 | 5.83 |
April | 0.349344E+09 | 2625.84 | 14-APR-15:11 | 12.33 | 8.16 | 94205772.70 | 56.69 | 29-APR-23:19 | 10.77 | 8.97 |
May | 0.440361E+09 | 2561.48 | 11-MAY-18:01 | 16.67 | 9.33 | 97468911.31 | 56.69 | 23-MAY-21:10 | 12.00 | 9.78 |
June | 0.734235E+09 | 2386.76 | 11-JUN-15:11 | 16.67 | 13.84 | 95249828.21 | 56.69 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.946141E+09 | 2469.79 | 09-JUL-15:11 | 21.00 | 15.31 | 98555489.71 | 56.69 | 10-JUL-21:40 | 17.00 | 13.49 |
August | 0.910611E+09 | 2435.66 | 12-AUG-15:11 | 18.33 | 14.20 | 98835582.82 | 56.69 | 21-AUG-21:10 | 14.17 | 12.31 |
September | 0.633264E+09 | 2397.97 | 09-SEP-15:11 | 19.67 | 14.05 | 95087027.82 | 56.69 | 14-SEP-22:49 | 13.00 | 12.44 |
October | 0.126441E+09 | 2459.34 | 06-OCT-18:02 | 11.33 | 7.72 | 95762192.49 | 56.69 | 07-OCT-23:19 | 10.67 | 9.24 |
November | 14453039.51 | 1960.73 | 10-NOV-16:11 | 9.67 | 7.83 | 91138369.75 | 56.69 | 23-NOV-00:20 | 8.00 | 8.00 |
December | 7849520.53 | 794.00 | 05-DEC-19:04 | 6.17 | 5.65 | 92963387.97 | 56.69 | 27-DEC-00:20 | 1.67 | 1.38 |
Annual Sum or Average | 0.421887E+10 | 0.113271E+10 | ||||||||
Minimum of Months | 7849520.53 | 794.00 | 5.67 | 3.21 | 85241316.47 | 56.69 | 1.67 | 1.38 | ||
Maximum of Months | 0.946141E+09 | 2625.84 | 21.00 | 15.31 | 98835582.82 | 56.69 | 17.00 | 13.49 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7765152.22 | 756.43 | 21-JAN-16:13 | 5.40 | 4.62 | 93100166.60 | 56.69 | 13-JAN-04:49 | 5.40 | 4.62 |
February | 11087865.27 | 1753.49 | 27-FEB-16:11 | 8.00 | 6.64 | 84458008.05 | 56.69 | 01-FEB-01:10 | 8.00 | 6.64 |
March | 15802773.14 | 1597.26 | 23-MAR-18:03 | 7.67 | 5.83 | 94065073.45 | 56.69 | 05-MAR-00:20 | 7.67 | 5.83 |
April | 0.204126E+09 | 2378.40 | 14-APR-15:11 | 12.33 | 8.16 | 93986433.35 | 60.54 | 27-APR-18:10 | 17.83 | 10.48 |
May | 0.308697E+09 | 2246.19 | 11-MAY-19:32 | 13.67 | 8.80 | 98139647.55 | 72.95 | 22-MAY-21:10 | 14.83 | 12.59 |
June | 0.578718E+09 | 2324.36 | 22-JUN-19:01 | 13.67 | 11.71 | 97322166.96 | 76.33 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.662110E+09 | 2407.82 | 14-JUL-18:01 | 14.42 | 11.60 | 0.103034E+09 | 73.31 | 10-JUL-21:40 | 14.42 | 11.60 |
August | 0.563313E+09 | 2221.66 | 28-AUG-15:11 | 24.00 | 15.59 | 0.102761E+09 | 72.58 | 17-AUG-21:10 | 24.00 | 15.59 |
September | 0.328513E+09 | 2261.46 | 14-SEP-18:01 | 14.00 | 12.84 | 96095532.55 | 68.67 | 11-SEP-21:10 | 14.00 | 12.84 |
October | 52159866.99 | 2174.07 | 06-OCT-18:02 | 11.33 | 7.72 | 95016130.75 | 56.69 | 07-OCT-23:19 | 10.67 | 9.24 |
November | 10466655.44 | 805.93 | 24-NOV-16:14 | 11.67 | 11.31 | 90536817.34 | 56.69 | 18-NOV-00:20 | 11.67 | 11.31 |
December | 5599700.39 | 710.60 | 05-DEC-19:04 | 6.17 | 5.65 | 92555167.45 | 56.69 | 05-DEC-00:20 | 6.17 | 5.65 |
Annual Sum or Average | 0.274836E+10 | 0.114107E+10 | ||||||||
Minimum of Months | 5599700.39 | 710.60 | 5.40 | 4.62 | 84458008.05 | 56.69 | 5.40 | 4.62 | ||
Maximum of Months | 0.662110E+09 | 2407.82 | 24.00 | 15.59 | 0.103034E+09 | 76.33 | 24.00 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10891691.34 | 134.89 | 01-JAN-15:05 | 3.17 | 2.13 | 0.00 | 0.00 | 01-JAN-00:10 | 3.17 | 2.13 |
February | 10127195.26 | 123.35 | 19-FEB-15:15 | 5.67 | 4.13 | 0.00 | 0.00 | 01-FEB-00:10 | 5.67 | 4.13 |
March | 9333950.54 | 100.99 | 25-MAR-14:15 | 11.67 | 9.34 | 0.00 | 0.00 | 01-MAR-00:10 | 11.67 | 9.34 |
April | 0.133292E+09 | 317.95 | 30-APR-13:05 | 22.17 | 13.02 | 0.00 | 0.00 | 01-APR-00:10 | 22.17 | 13.02 |
May | 0.115840E+09 | 226.87 | 23-MAY-13:30 | 18.50 | 14.58 | 0.00 | 0.00 | 01-MAY-00:10 | 18.50 | 14.58 |
June | 0.180362E+09 | 253.90 | 13-JUN-13:30 | 24.55 | 17.26 | 0.00 | 0.00 | 01-JUN-00:10 | 24.55 | 17.26 |
July | 0.252545E+09 | 306.26 | 22-JUL-13:30 | 28.00 | 16.51 | 0.00 | 0.00 | 01-JUL-00:10 | 28.00 | 16.51 |
August | 0.317346E+09 | 311.12 | 20-AUG-13:00 | 23.00 | 14.82 | 0.00 | 0.00 | 01-AUG-00:10 | 23.00 | 14.82 |
September | 0.307496E+09 | 389.09 | 25-SEP-13:30 | 21.50 | 13.34 | 0.00 | 0.00 | 01-SEP-00:10 | 21.50 | 13.34 |
October | 97615902.19 | 334.78 | 07-OCT-13:15 | 17.00 | 9.43 | 0.00 | 0.00 | 01-OCT-00:10 | 17.00 | 9.43 |
November | 11670106.98 | 144.29 | 11-NOV-15:05 | 9.00 | 7.01 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.01 |
December | 5846988.91 | 82.00 | 26-DEC-15:15 | 5.00 | 2.88 | 0.00 | 0.00 | 01-DEC-00:10 | 5.00 | 2.88 |
Annual Sum or Average | 0.145237E+10 | 0.00 | ||||||||
Minimum of Months | 5846988.91 | 82.00 | 3.17 | 2.13 | 0.00 | 0.00 | 3.17 | 2.13 | ||
Maximum of Months | 0.317346E+09 | 389.09 | 28.00 | 17.26 | 0.00 | 0.00 | 28.00 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78739745.31 | 692.12 | 29-JAN-19:02 | 9.00 | 8.43 | 95283084.08 | 56.69 | 18-JAN-22:19 | 9.00 | 8.43 |
February | 72681444.64 | 668.07 | 01-FEB-09:02 | 7.00 | 7.00 | 86198528.08 | 56.69 | 13-FEB-22:19 | 3.00 | 2.70 |
March | 0.147889E+09 | 759.42 | 04-MAR-09:02 | 4.33 | 1.77 | 96138891.04 | 56.69 | 10-MAR-22:19 | 3.00 | 2.98 |
April | 0.259919E+09 | 817.11 | 20-APR-18:01 | 13.67 | 8.59 | 94117580.09 | 58.50 | 27-APR-20:10 | 11.50 | 8.67 |
May | 0.321546E+09 | 802.67 | 11-MAY-19:32 | 13.67 | 8.80 | 97771195.23 | 69.90 | 22-MAY-21:10 | 14.83 | 12.59 |
June | 0.410996E+09 | 814.69 | 12-JUN-18:01 | 25.67 | 17.63 | 95884991.21 | 73.96 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.432777E+09 | 824.65 | 21-JUL-15:12 | 27.33 | 15.92 | 0.100314E+09 | 71.89 | 19-JUL-21:10 | 27.33 | 15.92 |
August | 0.390388E+09 | 791.32 | 28-AUG-15:11 | 24.00 | 15.59 | 0.100366E+09 | 71.92 | 17-AUG-21:10 | 24.00 | 15.59 |
September | 0.326920E+09 | 763.69 | 13-SEP-19:31 | 15.00 | 12.66 | 95055490.26 | 70.06 | 11-SEP-21:10 | 15.00 | 12.66 |
October | 0.210281E+09 | 783.80 | 07-OCT-18:02 | 10.67 | 8.16 | 96480817.27 | 56.69 | 02-OCT-21:10 | 10.67 | 8.16 |
November | 0.118821E+09 | 693.31 | 23-NOV-09:02 | 8.00 | 7.45 | 92644917.61 | 56.69 | 24-NOV-22:19 | 11.00 | 11.00 |
December | 54692190.95 | 660.37 | 30-DEC-09:01 | 0.00 | -1.6 | 95009261.41 | 56.69 | 04-DEC-22:19 | 0.00 | -1.6 |
Annual Sum or Average | 0.282565E+10 | 0.114526E+10 | ||||||||
Minimum of Months | 54692190.95 | 660.37 | 0.00 | -1.6 | 86198528.08 | 56.69 | 0.00 | -1.6 | ||
Maximum of Months | 0.432777E+09 | 824.65 | 27.33 | 17.63 | 0.100366E+09 | 73.96 | 27.33 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15636816.86 | 756.34 | 06-JAN-09:04 | 2.17 | 1.73 | 93764103.94 | 56.69 | 13-JAN-00:20 | 0.13 | -0.8 |
February | 18925375.05 | 1573.85 | 20-FEB-09:02 | 3.33 | 2.81 | 85130815.95 | 56.69 | 01-FEB-01:10 | 3.33 | 2.81 |
March | 17814264.25 | 702.09 | 10-MAR-09:02 | 7.17 | 4.01 | 94459773.48 | 56.69 | 05-MAR-00:20 | 7.17 | 4.01 |
April | 0.389976E+09 | 2385.97 | 14-APR-15:11 | 12.33 | 8.16 | 94706834.74 | 56.69 | 29-APR-23:19 | 10.77 | 8.97 |
May | 0.424525E+09 | 2304.12 | 11-MAY-18:01 | 16.67 | 9.33 | 97927635.30 | 56.69 | 22-MAY-21:10 | 14.83 | 12.59 |
June | 0.673900E+09 | 2223.90 | 12-JUN-15:11 | 24.00 | 16.89 | 95449081.45 | 56.69 | 21-JUN-21:10 | 13.83 | 12.18 |
July | 0.874100E+09 | 2243.34 | 23-JUL-18:02 | 20.67 | 16.44 | 98858485.69 | 56.69 | 21-JUL-21:00 | 20.67 | 16.44 |
August | 0.934702E+09 | 2224.70 | 27-AUG-15:11 | 18.33 | 14.52 | 99051192.79 | 56.69 | 17-AUG-21:10 | 18.33 | 14.52 |
September | 0.687908E+09 | 2226.78 | 10-SEP-15:11 | 21.67 | 16.48 | 95543399.33 | 56.69 | 14-SEP-22:40 | 13.00 | 12.44 |
October | 0.131883E+09 | 2226.66 | 06-OCT-18:02 | 11.33 | 7.72 | 95959441.44 | 56.69 | 07-OCT-23:19 | 10.67 | 9.24 |
November | 16988996.11 | 1670.23 | 11-NOV-09:02 | 6.50 | 5.33 | 91124398.34 | 56.69 | 21-NOV-22:19 | 8.67 | 7.78 |
December | 8462746.27 | 795.65 | 19-DEC-09:04 | 2.67 | 2.53 | 93033640.00 | 56.69 | 30-DEC-00:20 | -2.7 | -4.2 |
Annual Sum or Average | 0.419482E+10 | 0.113501E+10 | ||||||||
Minimum of Months | 8462746.27 | 702.09 | 2.17 | 1.73 | 85130815.95 | 56.69 | -2.7 | -4.2 | ||
Maximum of Months | 0.934702E+09 | 2385.97 | 24.00 | 16.89 | 99051192.79 | 56.69 | 20.67 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8100379.20 | 724.90 | 23-JAN-09:03 | 8.17 | 7.61 | 93099535.60 | 56.69 | 29-JAN-00:20 | 7.20 | 6.95 |
February | 10095586.26 | 765.92 | 27-FEB-16:14 | 8.00 | 6.64 | 84349673.80 | 56.69 | 17-FEB-00:20 | 8.00 | 6.64 |
March | 13871344.61 | 660.98 | 07-MAR-09:04 | 6.42 | 4.73 | 94110415.70 | 56.69 | 10-MAR-22:19 | 3.00 | 2.98 |
April | 0.239684E+09 | 2059.65 | 30-APR-08:51 | 18.00 | 11.96 | 94326376.31 | 56.94 | 27-APR-20:10 | 18.00 | 11.96 |
May | 0.313973E+09 | 2178.79 | 23-MAY-08:51 | 19.00 | 14.78 | 98059480.25 | 68.78 | 22-MAY-21:10 | 19.00 | 14.78 |
June | 0.542052E+09 | 2256.56 | 13-JUN-08:51 | 21.60 | 15.95 | 96691475.07 | 71.97 | 13-JUN-21:10 | 14.00 | 12.84 |
July | 0.648603E+09 | 2439.87 | 22-JUL-08:41 | 24.00 | 16.56 | 0.101631E+09 | 70.58 | 10-JUL-21:40 | 24.00 | 16.56 |
August | 0.614323E+09 | 2232.32 | 14-AUG-08:51 | 21.00 | 15.45 | 0.101972E+09 | 69.70 | 17-AUG-21:10 | 14.83 | 13.13 |
September | 0.393049E+09 | 2131.15 | 12-SEP-08:51 | 18.00 | 14.38 | 96070373.81 | 67.36 | 11-SEP-21:10 | 18.00 | 14.38 |
October | 59290759.60 | 1863.05 | 01-OCT-08:61 | 9.50 | 8.06 | 95104707.33 | 56.69 | 07-OCT-23:19 | 10.67 | 9.24 |
November | 10477468.76 | 703.00 | 20-NOV-19:05 | 6.00 | 4.61 | 90518414.57 | 56.69 | 11-NOV-00:20 | 6.00 | 4.61 |
December | 5932355.68 | 737.96 | 20-DEC-09:04 | 5.50 | 5.00 | 92628023.35 | 56.69 | 31-DEC-00:20 | 1.00 | 0.58 |
Annual Sum or Average | 0.285945E+10 | 0.113856E+10 | ||||||||
Minimum of Months | 5932355.68 | 660.98 | 5.50 | 4.61 | 84349673.80 | 56.69 | 1.00 | 0.58 | ||
Maximum of Months | 0.648603E+09 | 2439.87 | 24.00 | 16.56 | 0.101972E+09 | 71.97 | 24.00 | 16.56 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157241E+10 | 1300.01 | 23-JAN-22:00 | 8.00 | 7.45 | 0.119905E+10 | 712.60 | 23-JAN-23:10 | 7.83 | 7.29 |
February | 0.159632E+10 | 1291.84 | 27-FEB-22:00 | 5.00 | 5.00 | 0.108401E+10 | 710.61 | 27-FEB-22:49 | 4.17 | 4.17 |
March | 0.192020E+10 | 1344.59 | 20-MAR-18:03 | 7.83 | 5.10 | 0.120505E+10 | 715.69 | 20-MAR-21:49 | 4.50 | 3.61 |
April | 0.312516E+10 | 1848.87 | 30-APR-10:35 | 19.33 | 11.65 | 0.119071E+10 | 783.13 | 30-APR-23:40 | 11.17 | 8.45 |
May | 0.340296E+10 | 1781.17 | 23-MAY-10:35 | 20.00 | 14.59 | 0.124618E+10 | 784.69 | 23-MAY-21:49 | 12.00 | 9.78 |
June | 0.362990E+10 | 1876.03 | 26-JUN-18:10 | 18.00 | 16.13 | 0.125219E+10 | 811.69 | 26-JUN-22:10 | 14.17 | 14.07 |
July | 0.390443E+10 | 2022.18 | 23-JUL-10:35 | 21.00 | 15.99 | 0.131898E+10 | 829.42 | 24-JUL-21:49 | 13.17 | 13.07 |
August | 0.395477E+10 | 1911.59 | 19-AUG-10:35 | 18.00 | 14.38 | 0.133570E+10 | 817.28 | 21-AUG-22:10 | 15.17 | 12.72 |
September | 0.363746E+10 | 1818.98 | 13-SEP-18:10 | 17.50 | 14.11 | 0.125382E+10 | 802.05 | 13-SEP-21:49 | 12.00 | 10.35 |
October | 0.271458E+10 | 1713.88 | 01-OCT-10:35 | 13.67 | 9.65 | 0.121834E+10 | 760.24 | 02-OCT-22:10 | 8.00 | 6.98 |
November | 0.178717E+10 | 1311.23 | 08-NOV-22:00 | 11.00 | 11.00 | 0.116018E+10 | 714.89 | 08-NOV-23:10 | 11.00 | 11.00 |
December | 0.119772E+10 | 1164.25 | 21-DEC-22:10 | 3.00 | 3.00 | 0.119881E+10 | 704.45 | 04-DEC-05:30 | 3.00 | 3.00 |
Annual Sum or Average | 0.324431E+11 | 0.146630E+11 | ||||||||
Minimum of Months | 0.119772E+10 | 1164.25 | 3.00 | 3.00 | 0.108401E+10 | 704.45 | 3.00 | 3.00 | ||
Maximum of Months | 0.395477E+10 | 2022.18 | 21.00 | 16.13 | 0.133570E+10 | 829.42 | 15.17 | 14.07 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8350402.31 | 1967.37 | 19-JAN-16:11 | 7.33 | 6.98 | 93121534.44 | 56.69 | 29-JAN-04:40 | 12.63 | 12.05 |
February | 18441573.38 | 2523.28 | 17-FEB-16:12 | 5.67 | 3.21 | 84664322.26 | 56.69 | 04-FEB-00:20 | 5.67 | 3.21 |
March | 18285146.39 | 1854.02 | 23-MAR-18:03 | 7.67 | 5.83 | 93876750.10 | 56.69 | 09-MAR-00:20 | 7.67 | 5.83 |
April | 0.385569E+09 | 2764.34 | 14-APR-15:11 | 12.33 | 8.16 | 94189629.34 | 56.69 | 29-APR-23:19 | 10.77 | 8.97 |
May | 0.469348E+09 | 2731.09 | 11-MAY-18:01 | 16.67 | 9.33 | 97473360.83 | 56.69 | 25-MAY-01:19 | 7.67 | 7.67 |
June | 0.773620E+09 | 2507.12 | 26-JUN-18:01 | 18.00 | 16.13 | 95326592.37 | 56.69 | 13-JUN-21:00 | 18.00 | 16.13 |
July | 0.100758E+10 | 2524.03 | 16-JUL-18:01 | 18.67 | 15.16 | 98621529.31 | 56.69 | 16-JUL-04:19 | 18.67 | 15.16 |
August | 0.927708E+09 | 2531.86 | 18-AUG-18:01 | 17.83 | 14.23 | 98842796.97 | 56.69 | 17-AUG-21:10 | 17.83 | 14.23 |
September | 0.601839E+09 | 2519.25 | 14-SEP-18:01 | 14.00 | 12.84 | 95023443.95 | 56.70 | 25-SEP-00:49 | 9.83 | 8.92 |
October | 0.111563E+09 | 2572.30 | 06-OCT-18:02 | 11.33 | 7.72 | 95312301.30 | 56.70 | 03-OCT-21:49 | 11.33 | 7.72 |
November | 12163526.30 | 2058.30 | 10-NOV-16:11 | 9.67 | 7.83 | 90489721.38 | 56.69 | 29-NOV-00:20 | -1.0 | -1.4 |
December | 4264432.61 | 803.34 | 21-DEC-16:14 | 6.67 | 6.15 | 92387996.48 | 56.69 | 31-DEC-00:20 | 1.00 | 0.58 |
Annual Sum or Average | 0.433873E+10 | 0.112933E+10 | ||||||||
Minimum of Months | 4264432.61 | 803.34 | 5.67 | 3.21 | 84664322.26 | 56.69 | -1.0 | -1.4 | ||
Maximum of Months | 0.100758E+10 | 2764.34 | 18.67 | 16.13 | 98842796.97 | 56.70 | 18.67 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5372717.48 | 794.67 | 25-JAN-16:14 | 9.00 | 8.43 | 92540861.73 | 56.69 | 29-JAN-04:00 | 13.00 | 12.44 |
February | 8855720.05 | 1796.71 | 27-FEB-16:11 | 8.00 | 6.64 | 83861950.73 | 56.69 | 17-FEB-00:20 | 8.00 | 6.64 |
March | 14345996.36 | 1610.35 | 23-MAR-18:03 | 7.67 | 5.83 | 93506398.10 | 56.69 | 11-MAR-00:20 | 7.67 | 5.83 |
April | 0.225981E+09 | 2492.01 | 14-APR-15:11 | 12.33 | 8.16 | 94190310.05 | 64.89 | 27-APR-18:10 | 17.83 | 10.48 |
May | 0.327458E+09 | 2471.92 | 23-MAY-20:01 | 13.67 | 10.55 | 98645707.04 | 79.39 | 22-MAY-21:10 | 13.67 | 10.55 |
June | 0.609058E+09 | 2497.05 | 22-JUN-19:01 | 13.67 | 11.71 | 98176835.66 | 82.05 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.713844E+09 | 2584.73 | 28-JUL-18:11 | 13.67 | 12.72 | 0.104531E+09 | 78.55 | 10-JUL-18:10 | 13.67 | 12.72 |
August | 0.560873E+09 | 2394.90 | 04-AUG-20:01 | 13.83 | 12.08 | 0.103803E+09 | 76.05 | 17-AUG-21:10 | 14.83 | 13.13 |
September | 0.281394E+09 | 2423.51 | 14-SEP-18:01 | 14.00 | 12.84 | 96400433.50 | 70.53 | 11-SEP-21:10 | 14.00 | 12.84 |
October | 42425965.68 | 2254.20 | 06-OCT-18:02 | 11.33 | 7.72 | 94522311.08 | 56.69 | 07-OCT-23:19 | 10.67 | 9.24 |
November | 7615701.03 | 959.42 | 05-NOV-15:13 | 11.00 | 7.92 | 89895934.48 | 56.69 | 23-NOV-00:20 | 8.00 | 8.00 |
December | 1186816.47 | 717.52 | 16-DEC-09:05 | 6.17 | 5.65 | 92113673.58 | 56.69 | 27-DEC-00:20 | 1.67 | 1.38 |
Annual Sum or Average | 0.279841E+10 | 0.114219E+10 | ||||||||
Minimum of Months | 1186816.47 | 717.52 | 6.17 | 5.65 | 83861950.73 | 56.69 | 1.67 | 1.38 | ||
Maximum of Months | 0.713844E+09 | 2584.73 | 14.00 | 12.84 | 0.104531E+09 | 82.05 | 17.83 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56430045.71 | 1687.24 | 11-JAN-16:12 | -2.3 | -4.4 | 95473372.77 | 56.69 | 23-JAN-22:19 | 8.00 | 7.45 |
February | 71802421.02 | 1484.75 | 27-FEB-16:11 | 8.00 | 6.64 | 86689837.74 | 56.69 | 13-FEB-22:19 | 8.00 | 6.64 |
March | 37062533.32 | 1403.38 | 25-MAR-15:12 | 11.00 | 9.41 | 95460988.88 | 56.69 | 20-MAR-21:19 | 11.00 | 9.41 |
April | 0.405331E+09 | 1502.73 | 30-APR-18:01 | 24.00 | 13.14 | 95160408.25 | 56.69 | 28-APR-21:10 | 24.00 | 13.14 |
May | 0.365531E+09 | 1731.24 | 11-MAY-18:01 | 16.67 | 9.33 | 98155133.96 | 56.69 | 22-MAY-21:10 | 14.83 | 12.59 |
June | 0.508215E+09 | 1642.06 | 13-JUN-18:01 | 23.37 | 16.34 | 95531055.47 | 56.69 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.639723E+09 | 1652.26 | 22-JUL-08:61 | 24.00 | 16.56 | 98763359.37 | 56.69 | 21-JUL-21:10 | 24.00 | 16.56 |
August | 0.718579E+09 | 1633.16 | 01-AUG-15:11 | 18.00 | 13.90 | 98916713.23 | 56.69 | 30-AUG-21:10 | 15.00 | 12.67 |
September | 0.672221E+09 | 1641.77 | 11-SEP-18:01 | 21.50 | 15.69 | 95648425.33 | 56.69 | 14-SEP-21:10 | 12.92 | 12.36 |
October | 0.248027E+09 | 1596.06 | 10-OCT-15:11 | 12.67 | 11.55 | 97030158.91 | 56.69 | 04-OCT-21:10 | 12.67 | 11.55 |
November | 53136034.43 | 1501.35 | 10-NOV-16:11 | 9.67 | 7.83 | 92583690.11 | 56.69 | 03-NOV-21:19 | 9.67 | 7.83 |
December | 15362440.04 | 1619.01 | 26-DEC-16:11 | 2.33 | 1.24 | 94238622.87 | 56.69 | 24-DEC-00:20 | 2.33 | 1.24 |
Annual Sum or Average | 0.379142E+10 | 0.114365E+10 | ||||||||
Minimum of Months | 15362440.04 | 1403.38 | -2.3 | -4.4 | 86689837.74 | 56.69 | 2.33 | 1.24 | ||
Maximum of Months | 0.718579E+09 | 1731.24 | 24.00 | 16.56 | 98916713.23 | 56.69 | 24.00 | 16.56 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357301E+11 | 16835.81 | 18-JAN-23:10 | 7.80 | 7.23 | 0.160304E+11 | 10629.94 | 18-JAN-23:49 | 7.80 | 7.13 |
February | 0.326824E+11 | 16769.53 | 07-FEB-23:10 | 6.83 | 6.83 | 0.145248E+11 | 10592.18 | 07-FEB-23:49 | 6.17 | 6.17 |
March | 0.371415E+11 | 16872.98 | 30-MAR-22:10 | 5.43 | 3.80 | 0.163285E+11 | 10667.61 | 30-MAR-22:49 | 5.17 | 3.64 |
April | 0.385690E+11 | 18766.58 | 29-APR-17:50 | 20.00 | 12.40 | 0.161172E+11 | 11097.06 | 28-APR-22:49 | 20.00 | 12.40 |
May | 0.405649E+11 | 19260.47 | 22-MAY-18:10 | 19.00 | 14.26 | 0.168470E+11 | 11225.76 | 23-MAY-22:49 | 11.17 | 9.47 |
June | 0.409178E+11 | 19909.28 | 12-JUN-18:10 | 25.67 | 17.63 | 0.166645E+11 | 11343.80 | 13-JUN-22:00 | 13.00 | 12.44 |
July | 0.428332E+11 | 20085.07 | 22-JUL-18:00 | 30.00 | 16.80 | 0.172230E+11 | 11348.97 | 10-JUL-22:10 | 30.00 | 16.80 |
August | 0.426438E+11 | 19518.93 | 14-AUG-18:10 | 26.48 | 13.67 | 0.172766E+11 | 11282.92 | 16-AUG-22:49 | 15.17 | 14.47 |
September | 0.398063E+11 | 18766.58 | 13-SEP-18:10 | 17.50 | 14.11 | 0.163695E+11 | 11176.80 | 12-SEP-22:49 | 17.50 | 14.11 |
October | 0.382891E+11 | 17285.99 | 02-OCT-22:10 | 8.00 | 6.98 | 0.164309E+11 | 10843.93 | 02-OCT-22:49 | 8.00 | 6.98 |
November | 0.354242E+11 | 17096.51 | 08-NOV-23:10 | 11.00 | 11.00 | 0.156608E+11 | 10727.72 | 08-NOV-23:49 | 11.00 | 11.00 |
December | 0.354450E+11 | 16604.44 | 04-DEC-23:10 | 7.00 | 7.00 | 0.160062E+11 | 10522.33 | 04-DEC-23:49 | 7.00 | 7.00 |
Annual Sum or Average | 0.460047E+12 | 0.195479E+12 | ||||||||
Minimum of Months | 0.326824E+11 | 16604.44 | 5.43 | 3.80 | 0.145248E+11 | 10522.33 | 5.17 | 3.64 | ||
Maximum of Months | 0.428332E+11 | 20085.07 | 30.00 | 17.63 | 0.172766E+11 | 11348.97 | 30.00 | 16.80 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384386E+11 | 17690.98 | 18-JAN-23:10 | 7.80 | 7.23 | 0.166096E+11 | 11024.53 | 18-JAN-23:49 | 7.80 | 7.13 |
February | 0.350869E+11 | 17622.64 | 07-FEB-23:10 | 6.83 | 6.83 | 0.150624E+11 | 10985.30 | 07-FEB-23:49 | 6.17 | 6.17 |
March | 0.397707E+11 | 17738.77 | 30-MAR-22:10 | 5.43 | 3.80 | 0.169601E+11 | 11068.97 | 30-MAR-22:49 | 5.17 | 3.64 |
April | 0.405963E+11 | 19446.04 | 29-APR-17:50 | 20.00 | 12.40 | 0.166530E+11 | 11344.59 | 28-APR-22:00 | 20.00 | 12.40 |
May | 0.425123E+11 | 19962.24 | 22-MAY-18:10 | 19.00 | 14.26 | 0.173622E+11 | 11348.98 | 22-MAY-21:49 | 14.17 | 12.31 |
June | 0.426029E+11 | 20563.37 | 12-JUN-18:10 | 25.67 | 17.63 | 0.170992E+11 | 11349.21 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.444988E+11 | 20718.28 | 22-JUL-18:00 | 30.00 | 16.80 | 0.176383E+11 | 11349.06 | 19-JUL-21:19 | 30.00 | 16.80 |
August | 0.442682E+11 | 20143.53 | 14-AUG-18:10 | 26.48 | 13.67 | 0.176860E+11 | 11349.02 | 17-AUG-21:30 | 14.50 | 13.02 |
September | 0.415101E+11 | 19420.85 | 11-SEP-18:10 | 21.50 | 15.69 | 0.168213E+11 | 11344.20 | 15-SEP-23:10 | 13.00 | 12.54 |
October | 0.406087E+11 | 18069.70 | 17-OCT-22:10 | 11.17 | 11.17 | 0.170150E+11 | 11188.69 | 12-OCT-22:49 | 11.17 | 11.17 |
November | 0.380003E+11 | 17971.30 | 08-NOV-23:10 | 11.00 | 11.00 | 0.162442E+11 | 11131.44 | 08-NOV-23:49 | 11.00 | 11.00 |
December | 0.382099E+11 | 17441.23 | 04-DEC-23:10 | 7.00 | 7.00 | 0.165750E+11 | 10909.28 | 05-DEC-23:49 | 4.08 | 3.43 |
Annual Sum or Average | 0.486104E+12 | 0.201726E+12 | ||||||||
Minimum of Months | 0.350869E+11 | 17441.23 | 5.43 | 3.80 | 0.150624E+11 | 10909.28 | 4.08 | 3.43 | ||
Maximum of Months | 0.444988E+11 | 20718.28 | 30.00 | 17.63 | 0.176860E+11 | 11349.21 | 30.00 | 16.80 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475135E+11 | 25885.61 | 15-JAN-11:50 | 8.83 | 6.51 | 0.188680E+11 | 11319.44 | 14-JAN-18:10 | 8.83 | 6.51 |
February | 0.432108E+11 | 25929.03 | 22-FEB-11:40 | 10.00 | 8.60 | 0.170436E+11 | 11319.43 | 11-FEB-18:10 | 10.00 | 8.60 |
March | 0.484591E+11 | 26537.78 | 25-MAR-10:50 | 11.42 | 8.36 | 0.188760E+11 | 11319.44 | 04-MAR-18:10 | 11.42 | 8.36 |
April | 0.493576E+11 | 28351.42 | 30-APR-10:50 | 19.17 | 11.38 | 0.182622E+11 | 11319.61 | 29-APR-17:10 | 19.17 | 11.38 |
May | 0.513439E+11 | 28128.59 | 23-MAY-10:50 | 20.00 | 14.59 | 0.188716E+11 | 11319.57 | 20-MAY-17:10 | 20.00 | 14.59 |
June | 0.509285E+11 | 28535.52 | 25-JUN-10:50 | 20.50 | 14.20 | 0.182659E+11 | 11319.57 | 10-JUN-17:10 | 20.50 | 14.20 |
July | 0.531047E+11 | 28952.47 | 23-JUL-10:40 | 21.00 | 15.99 | 0.188680E+11 | 11319.65 | 22-JUL-17:10 | 21.00 | 15.99 |
August | 0.531516E+11 | 28320.72 | 19-AUG-10:50 | 18.00 | 14.38 | 0.188753E+11 | 11319.62 | 19-AUG-17:10 | 18.00 | 14.38 |
September | 0.504319E+11 | 28022.94 | 10-SEP-10:50 | 18.83 | 14.72 | 0.182615E+11 | 11319.58 | 09-SEP-17:10 | 18.83 | 14.72 |
October | 0.495783E+11 | 27218.17 | 07-OCT-10:50 | 14.83 | 10.17 | 0.188688E+11 | 11319.50 | 07-OCT-17:10 | 14.33 | 8.93 |
November | 0.465205E+11 | 25894.79 | 11-NOV-11:50 | 9.00 | 6.94 | 0.182586E+11 | 11319.43 | 18-NOV-18:10 | 8.67 | 5.99 |
December | 0.470361E+11 | 25265.20 | 03-DEC-11:50 | 6.83 | 4.26 | 0.188680E+11 | 11319.54 | 30-DEC-18:10 | 0.00 | -0.9 |
Annual Sum or Average | 0.590637E+12 | 0.222188E+12 | ||||||||
Minimum of Months | 0.432108E+11 | 25265.20 | 6.83 | 4.26 | 0.170436E+11 | 11319.43 | 0.00 | -0.9 | ||
Maximum of Months | 0.531516E+11 | 28952.47 | 21.00 | 15.99 | 0.188760E+11 | 11319.65 | 21.00 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199769E+10 | 1664.38 | 21-JAN-11:35 | 6.33 | 5.22 | 0.127474E+10 | 784.09 | 23-JAN-23:10 | 7.83 | 7.29 |
February | 0.223875E+10 | 1707.91 | 22-FEB-11:40 | 10.00 | 8.60 | 0.115365E+10 | 781.16 | 27-FEB-22:40 | 4.33 | 4.33 |
March | 0.304717E+10 | 1747.11 | 25-MAR-10:50 | 11.42 | 8.36 | 0.129590E+10 | 800.99 | 20-MAR-21:40 | 11.42 | 8.36 |
April | 0.423117E+10 | 3095.06 | 30-APR-15:10 | 24.00 | 13.13 | 0.141144E+10 | 982.09 | 30-APR-23:10 | 11.87 | 8.94 |
May | 0.458513E+10 | 2839.23 | 23-MAY-15:10 | 18.00 | 14.38 | 0.151215E+10 | 996.33 | 23-MAY-21:40 | 12.00 | 9.78 |
June | 0.502764E+10 | 3857.44 | 13-JUN-15:10 | 26.08 | 17.81 | 0.156216E+10 | 1007.40 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.556498E+10 | 4439.50 | 22-JUL-14:10 | 28.17 | 16.59 | 0.164265E+10 | 1007.40 | 19-JUL-21:19 | 28.17 | 16.59 |
August | 0.542254E+10 | 3481.90 | 19-AUG-13:40 | 19.67 | 15.02 | 0.165497E+10 | 1007.40 | 14-AUG-22:10 | 19.67 | 15.02 |
September | 0.471621E+10 | 2901.20 | 13-SEP-15:10 | 23.00 | 16.22 | 0.152015E+10 | 990.90 | 12-SEP-22:10 | 23.00 | 16.22 |
October | 0.389261E+10 | 2126.19 | 01-OCT-10:35 | 13.67 | 9.65 | 0.137393E+10 | 894.37 | 02-OCT-21:40 | 8.00 | 6.98 |
November | 0.274531E+10 | 1720.94 | 11-NOV-11:35 | 9.00 | 6.87 | 0.124424E+10 | 799.28 | 08-NOV-23:10 | 9.00 | 6.87 |
December | 0.143804E+10 | 1555.03 | 03-DEC-11:50 | 6.83 | 4.26 | 0.126929E+10 | 754.98 | 04-DEC-23:10 | 7.00 | 7.00 |
Annual Sum or Average | 0.449072E+11 | 0.169153E+11 | ||||||||
Minimum of Months | 0.143804E+10 | 1555.03 | 6.33 | 4.26 | 0.115365E+10 | 754.98 | 4.33 | 4.33 | ||
Maximum of Months | 0.556498E+10 | 4439.50 | 28.17 | 17.81 | 0.165497E+10 | 1007.40 | 28.17 | 16.59 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98515784.90 | 594.95 | 10-JAN-07:55 | -6.0 |
February | 35969727.47 | 440.92 | 17-FEB-07:20 | -3.7 |
March | 19099451.09 | 296.22 | 15-MAR-09:20 | 2.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 4647.75 | 7.41 | 28-OCT-06:50 | 4.50 |
November | 27301260.30 | 377.23 | 29-NOV-09:10 | 1.17 |
December | 0.187897E+09 | 508.82 | 30-DEC-17:00 | 1.00 |
Annual Sum or Average | 0.368787E+09 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 0.187897E+09 | 594.95 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3555744.97 | 139.18 | 12-JAN-15:00 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 3555744.97 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 3555744.97 | 139.18 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59139008.40 | 242.04 | 12-JAN-15:00 | -1.0 |
February | 5875392.14 | 62.09 | 19-FEB-18:00 | 3.00 |
March | 610742.29 | 39.37 | 15-MAR-12:00 | 1.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 3830465.33 | 94.01 | 29-NOV-15:50 | 4.17 |
December | 37407714.42 | 175.08 | 30-DEC-17:00 | 1.00 |
Annual Sum or Average | 0.106863E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 59139008.40 | 242.04 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.632358E+09 | 1910.94 | 03-JAN-16:11 | 3.67 |
February | 0.468623E+09 | 1891.40 | 25-FEB-16:11 | 5.00 |
March | 0.439171E+09 | 1904.53 | 15-MAR-15:11 | 3.00 |
April | 81012259.62 | 1811.89 | 10-APR-15:12 | 7.33 |
May | 50929153.39 | 1413.32 | 05-MAY-08:62 | 8.17 |
June | 3754118.31 | 1101.12 | 23-JUN-15:14 | 14.67 |
July | 3607263.95 | 863.47 | 05-JUL-08:03 | 13.00 |
August | 1824490.86 | 868.02 | 08-AUG-18:05 | 17.83 |
September | 8138874.21 | 951.73 | 18-SEP-18:04 | 14.67 |
October | 0.190459E+09 | 1859.42 | 19-OCT-15:11 | 9.00 |
November | 0.469790E+09 | 1911.26 | 29-NOV-16:11 | 3.67 |
December | 0.824720E+09 | 1914.09 | 30-DEC-16:11 | 1.67 |
Annual Sum or Average | 0.317439E+10 | |||
Minimum of Months | 1824490.86 | 863.47 | 1.67 | |
Maximum of Months | 0.824720E+09 | 1914.09 | 17.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.775099E+09 | 1859.67 | 03-JAN-16:11 | 3.67 |
February | 0.591515E+09 | 1852.59 | 25-FEB-16:11 | 5.00 |
March | 0.496762E+09 | 1853.30 | 15-MAR-15:11 | 3.00 |
April | 0.120186E+09 | 1772.29 | 10-APR-15:12 | 7.33 |
May | 61533758.77 | 1552.17 | 05-MAY-08:62 | 8.17 |
June | 3996075.58 | 848.56 | 30-JUN-15:14 | 13.67 |
July | 3444645.61 | 894.67 | 05-JUL-08:03 | 13.00 |
August | 1517905.85 | 700.58 | 18-AUG-08:53 | 19.00 |
September | 13435794.53 | 906.17 | 30-SEP-18:04 | 10.33 |
October | 0.261014E+09 | 1810.39 | 19-OCT-15:11 | 9.00 |
November | 0.572202E+09 | 1859.87 | 29-NOV-16:11 | 3.67 |
December | 0.917363E+09 | 1862.00 | 30-DEC-16:11 | 1.67 |
Annual Sum or Average | 0.381807E+10 | |||
Minimum of Months | 1517905.85 | 700.58 | 1.67 | |
Maximum of Months | 0.917363E+09 | 1862.00 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29860918.41 | 535.73 | 12-JAN-16:12 | -1.0 |
February | 11903029.30 | 514.73 | 25-FEB-16:11 | 5.00 |
March | 2308617.80 | 513.71 | 15-MAR-15:11 | 3.00 |
April | 561153.76 | 316.71 | 14-APR-15:14 | 12.33 |
May | 506016.70 | 190.11 | 13-MAY-15:16 | 11.80 |
June | 66397.96 | 178.97 | 05-JUN-15:16 | 14.00 |
July | 18126.73 | 64.68 | 07-JUL-16:17 | 15.33 |
August | 54784.19 | 134.12 | 18-AUG-08:54 | 19.00 |
September | 270285.48 | 163.07 | 15-SEP-08:06 | 14.33 |
October | 1113680.45 | 268.01 | 03-OCT-15:14 | 14.00 |
November | 7132801.32 | 526.01 | 29-NOV-16:11 | 3.67 |
December | 28643257.21 | 529.63 | 30-DEC-16:11 | 1.67 |
Annual Sum or Average | 82439069.31 | |||
Minimum of Months | 18126.73 | 64.68 | -1.0 | |
Maximum of Months | 29860918.41 | 535.73 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631057E+09 | 1857.17 | 03-JAN-16:11 | 3.67 |
February | 0.492639E+09 | 1839.32 | 15-FEB-16:11 | 6.00 |
March | 0.442382E+09 | 1851.24 | 15-MAR-15:11 | 3.00 |
April | 73798094.23 | 1754.42 | 10-APR-15:12 | 7.33 |
May | 49220433.26 | 869.43 | 28-MAY-18:04 | 11.83 |
June | 5777498.06 | 982.68 | 16-JUN-15:14 | 14.00 |
July | 2671147.24 | 941.39 | 04-JUL-15:14 | 13.67 |
August | 1210251.68 | 835.30 | 09-AUG-18:04 | 18.00 |
September | 5064286.58 | 962.83 | 28-SEP-18:04 | 11.00 |
October | 0.188162E+09 | 1806.72 | 19-OCT-15:11 | 9.00 |
November | 0.469929E+09 | 1857.56 | 29-NOV-16:11 | 3.67 |
December | 0.795322E+09 | 1861.45 | 30-DEC-16:11 | 1.67 |
Annual Sum or Average | 0.315723E+10 | |||
Minimum of Months | 1210251.68 | 835.30 | 1.67 | |
Maximum of Months | 0.795322E+09 | 1861.45 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.770625E+09 | 1803.88 | 03-JAN-16:11 | 3.67 |
February | 0.622576E+09 | 1797.39 | 25-FEB-16:11 | 5.00 |
March | 0.500962E+09 | 1798.31 | 15-MAR-15:11 | 3.00 |
April | 0.106174E+09 | 1712.52 | 10-APR-15:12 | 7.33 |
May | 60960437.27 | 826.55 | 20-MAY-15:14 | 14.67 |
June | 6147769.67 | 861.68 | 16-JUN-15:14 | 14.00 |
July | 1860239.61 | 859.58 | 04-JUL-15:14 | 13.67 |
August | 895728.84 | 598.54 | 28-AUG-21:15 | 14.67 |
September | 8912885.36 | 788.25 | 07-SEP-18:04 | 13.00 |
October | 0.255934E+09 | 1755.82 | 19-OCT-15:11 | 9.00 |
November | 0.569354E+09 | 1804.72 | 29-NOV-16:11 | 3.67 |
December | 0.884487E+09 | 1808.16 | 30-DEC-16:11 | 1.67 |
Annual Sum or Average | 0.378889E+10 | |||
Minimum of Months | 895728.84 | 598.54 | 1.67 | |
Maximum of Months | 0.884487E+09 | 1808.16 | 14.67 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15477764.97 | 305.11 | 12-JAN-13:50 | -1.0 |
February | 1077416.53 | 73.80 | 16-FEB-12:30 | 5.05 |
March | 768143.04 | 88.45 | 15-MAR-13:50 | 2.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 6160643.88 | 215.53 | 30-NOV-15:00 | 6.00 |
December | 36746477.17 | 326.37 | 10-DEC-16:00 | 4.00 |
Annual Sum or Average | 60230445.59 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 36746477.17 | 326.37 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102220E+10 | 2293.30 | 03-JAN-16:11 | 3.67 |
February | 0.768408E+09 | 2277.77 | 25-FEB-16:11 | 5.00 |
March | 0.732185E+09 | 2278.18 | 15-MAR-15:11 | 3.00 |
April | 0.181240E+09 | 2197.37 | 10-APR-15:12 | 7.33 |
May | 0.121874E+09 | 2152.49 | 05-MAY-08:62 | 8.17 |
June | 11655708.89 | 838.75 | 09-JUN-08:03 | 13.33 |
July | 13108927.12 | 1006.26 | 01-JUL-15:14 | 14.00 |
August | 2382643.99 | 912.19 | 23-AUG-08:03 | 15.17 |
September | 35216300.66 | 1021.43 | 05-SEP-15:14 | 14.00 |
October | 0.389762E+09 | 2261.85 | 19-OCT-15:11 | 9.00 |
November | 0.785638E+09 | 2294.41 | 29-NOV-16:11 | 3.67 |
December | 0.125522E+10 | 2296.55 | 30-DEC-16:11 | 1.67 |
Annual Sum or Average | 0.531889E+10 | |||
Minimum of Months | 2382643.99 | 838.75 | 1.67 | |
Maximum of Months | 0.125522E+10 | 2296.55 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120032E+10 | 2220.29 | 03-JAN-16:11 | 3.67 |
February | 0.923901E+09 | 2208.13 | 17-FEB-09:01 | 1.33 |
March | 0.804050E+09 | 2206.03 | 15-MAR-15:11 | 3.00 |
April | 0.242334E+09 | 2140.18 | 10-APR-15:12 | 7.33 |
May | 0.141191E+09 | 2088.25 | 05-MAY-08:62 | 8.17 |
June | 11784247.72 | 844.15 | 24-JUN-08:04 | 14.00 |
July | 12373342.30 | 844.12 | 03-JUL-08:03 | 14.00 |
August | 1826560.73 | 752.71 | 23-AUG-08:03 | 15.17 |
September | 52966600.90 | 1572.44 | 20-SEP-08:61 | 11.50 |
October | 0.494267E+09 | 2191.61 | 19-OCT-15:11 | 9.00 |
November | 0.910775E+09 | 2221.80 | 29-NOV-16:11 | 3.67 |
December | 0.136871E+10 | 2223.88 | 28-DEC-16:11 | 2.67 |
Annual Sum or Average | 0.616449E+10 | |||
Minimum of Months | 1826560.73 | 752.71 | 1.33 | |
Maximum of Months | 0.136871E+10 | 2223.88 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225531E+09 | 1287.19 | 03-JAN-16:11 | 3.67 |
February | 0.157099E+09 | 1253.96 | 15-FEB-16:11 | 6.00 |
March | 0.167933E+09 | 1273.29 | 15-MAR-15:11 | 3.00 |
April | 17487844.69 | 884.56 | 10-APR-15:12 | 7.33 |
May | 13886953.49 | 505.55 | 02-MAY-08:03 | 9.00 |
June | 2138795.69 | 559.97 | 08-JUN-18:03 | 15.83 |
July | 1371258.01 | 529.20 | 08-JUL-18:03 | 15.83 |
August | 1141366.54 | 529.92 | 09-AUG-18:04 | 18.00 |
September | 1229751.64 | 540.13 | 06-SEP-15:15 | 13.67 |
October | 44165524.82 | 1239.60 | 19-OCT-15:11 | 9.00 |
November | 0.142549E+09 | 1286.99 | 30-NOV-16:11 | 6.00 |
December | 0.357968E+09 | 1289.94 | 30-DEC-16:11 | 1.67 |
Annual Sum or Average | 0.113250E+10 | |||
Minimum of Months | 1141366.54 | 505.55 | 1.67 | |
Maximum of Months | 0.357968E+09 | 1289.94 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97632650.50 | 1076.39 | 10-JAN-07:55 | -6.0 |
February | 11473581.28 | 809.00 | 17-FEB-07:15 | -3.7 |
March | 479691.64 | 104.81 | 16-MAR-06:10 | 1.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 10486707.95 | 542.16 | 29-NOV-09:03 | 1.17 |
December | 83332528.08 | 820.82 | 27-DEC-09:03 | -0.7 |
Annual Sum or Average | 0.203405E+09 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 97632650.50 | 1076.39 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743717E+10 | 7163.56 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.671509E+10 | 7163.56 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.746010E+10 | 7163.56 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.718502E+10 | 7163.56 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.745007E+10 | 7163.56 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.721797E+10 | 7163.56 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.741712E+10 | 7163.56 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.746297E+10 | 7163.56 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.718788E+10 | 7163.56 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.743431E+10 | 7163.56 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.721224E+10 | 7163.56 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.741712E+10 | 7163.56 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.875971E+11 | 0.143105E+12 | ||||
Minimum of Months | 0.671509E+10 | 7163.56 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.746297E+10 | 7163.56 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.336569E+09 | 324.19 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.303891E+09 | 324.19 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.337607E+09 | 324.19 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.325158E+09 | 324.19 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.337153E+09 | 324.19 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.326649E+09 | 324.19 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.335662E+09 | 324.19 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.337736E+09 | 324.19 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.325288E+09 | 324.19 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.336440E+09 | 324.19 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.326390E+09 | 324.19 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.335662E+09 | 324.19 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.396421E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.303891E+09 | 324.19 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.337736E+09 | 324.19 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.389749E+09 | 375.41 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.351908E+09 | 375.41 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.390950E+09 | 375.41 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.376534E+09 | 375.41 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.390424E+09 | 375.41 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.378261E+09 | 375.41 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.388697E+09 | 375.41 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.391100E+09 | 375.41 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.376684E+09 | 375.41 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.389598E+09 | 375.41 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.377961E+09 | 375.41 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.388697E+09 | 375.41 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.459056E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.351908E+09 | 375.41 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.391100E+09 | 375.41 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.697327E+09 | 671.67 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.629623E+09 | 671.67 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.699476E+09 | 671.67 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.673684E+09 | 671.67 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.698536E+09 | 671.67 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.676774E+09 | 671.67 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.695446E+09 | 671.67 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.699745E+09 | 671.67 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.673953E+09 | 671.67 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.697058E+09 | 671.67 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.676237E+09 | 671.67 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.695446E+09 | 671.67 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.821331E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.629623E+09 | 671.67 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.699745E+09 | 671.67 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159843E+09 | 153.96 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.144324E+09 | 153.96 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.160336E+09 | 153.96 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.154423E+09 | 153.96 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.160120E+09 | 153.96 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.155132E+09 | 153.96 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.159412E+09 | 153.96 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.160397E+09 | 153.96 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.154485E+09 | 153.96 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.159781E+09 | 153.96 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.155009E+09 | 153.96 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.159412E+09 | 153.96 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.188267E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.144324E+09 | 153.96 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.160397E+09 | 153.96 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.297499E+09 | 286.55 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.268614E+09 | 286.55 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.298416E+09 | 286.55 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.287412E+09 | 286.55 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.298015E+09 | 286.55 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.288730E+09 | 286.55 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.296696E+09 | 286.55 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.298530E+09 | 286.55 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.287527E+09 | 286.55 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.297384E+09 | 286.55 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.288501E+09 | 286.55 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.296696E+09 | 286.55 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.350402E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.268614E+09 | 286.55 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.298530E+09 | 286.55 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.641441E+09 | 767.68 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.546719E+09 | 767.68 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.569592E+09 | 767.68 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.484571E+09 | 767.68 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.440187E+09 | 767.68 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.397020E+09 | 767.68 | 01-JUN-19:30 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.418488E+09 | 767.68 | 17-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.480656E+09 | 767.68 | 01-AUG-19:49 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.522535E+09 | 767.68 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.603964E+09 | 767.68 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.617868E+09 | 767.68 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.664619E+09 | 767.68 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.638766E+10 | 0.143405E+11 | ||||
Minimum of Months | 0.397020E+09 | 767.68 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.664619E+09 | 767.68 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648383E+10 | 6458.51 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.580574E+10 | 6458.51 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.640505E+10 | 6458.51 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.607100E+10 | 6458.51 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.621413E+10 | 6458.51 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.597911E+10 | 6458.51 | 01-JUN-19:30 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.615634E+10 | 6458.51 | 17-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.627770E+10 | 6458.51 | 01-AUG-19:49 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.612680E+10 | 6458.51 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.642812E+10 | 6458.51 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.628498E+10 | 6458.51 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.650756E+10 | 6458.51 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.747404E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.580574E+10 | 6458.51 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.650756E+10 | 6458.51 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.109776E+10 | 1057.37 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.991179E+09 | 1057.37 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.110115E+10 | 1057.37 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.106054E+10 | 1057.37 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.109967E+10 | 1057.37 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.106541E+10 | 1057.37 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.109480E+10 | 1057.37 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.110157E+10 | 1057.37 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.106097E+10 | 1057.37 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.109734E+10 | 1057.37 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.106456E+10 | 1057.37 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.109480E+10 | 1057.37 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.129297E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.991179E+09 | 1057.37 | 0.00 | 0.00 | |
Maximum of Months | 0.110157E+10 | 1057.37 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129804E+10 | 1348.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.113544E+10 | 1348.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.121881E+10 | 1348.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.109943E+10 | 1348.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.107098E+10 | 1348.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.101033E+10 | 1348.12 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.104629E+10 | 1348.12 | 17-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.111629E+10 | 1348.12 | 01-AUG-19:49 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.114250E+10 | 1348.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.125000E+10 | 1348.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.125114E+10 | 1348.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.131406E+10 | 1348.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.139533E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.101033E+10 | 1348.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.131406E+10 | 1348.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129804E+10 | 1348.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.113544E+10 | 1348.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.121881E+10 | 1348.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.109943E+10 | 1348.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.107098E+10 | 1348.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.101033E+10 | 1348.12 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.104629E+10 | 1348.12 | 17-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.111629E+10 | 1348.12 | 01-AUG-19:49 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.114250E+10 | 1348.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.125000E+10 | 1348.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.125114E+10 | 1348.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.131406E+10 | 1348.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.139533E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.101033E+10 | 1348.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.131406E+10 | 1348.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.735117E+09 | 708.07 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.663744E+09 | 708.07 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.737383E+09 | 708.07 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.710193E+09 | 708.07 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.736392E+09 | 708.07 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.713450E+09 | 708.07 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.733135E+09 | 708.07 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.737666E+09 | 708.07 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.710477E+09 | 708.07 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.734834E+09 | 708.07 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.712884E+09 | 708.07 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.733135E+09 | 708.07 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.865841E+10 | 0.424019E+12 | ||||
Minimum of Months | 0.663744E+09 | 708.07 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.737666E+09 | 708.07 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.116181E+10 | 1119.06 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.104901E+10 | 1119.06 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.116539E+10 | 1119.06 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.112242E+10 | 1119.06 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.116383E+10 | 1119.06 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.112757E+10 | 1119.06 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.115868E+10 | 1119.06 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.116584E+10 | 1119.06 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.112287E+10 | 1119.06 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.116136E+10 | 1119.06 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.112667E+10 | 1119.06 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.115868E+10 | 1119.06 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136841E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.104901E+10 | 1119.06 | 0.00 | 0.00 | |
Maximum of Months | 0.116584E+10 | 1119.06 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.743717E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.671509E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.746010E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.718502E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.745007E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.721797E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.741712E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.746297E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.718788E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.743431E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.721224E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.741712E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.875971E+11 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.671509E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.746297E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.336569E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566930E+09 |
February | 0.179968E+10 | 0.303891E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508399E+09 |
March | 0.199990E+10 | 0.337607E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503500E+09 |
April | 0.192973E+10 | 0.325158E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59278.04 | 0.405748E+09 |
May | 0.199475E+10 | 0.337153E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.96 | 0.384279E+09 |
June | 0.193394E+10 | 0.326649E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 698071.23 | 0.276314E+09 |
July | 0.199054E+10 | 0.335662E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2736721.74 | 0.243442E+09 |
August | 0.199896E+10 | 0.337736E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 397674.45 | 0.226758E+09 |
September | 0.192879E+10 | 0.325288E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281783E+09 |
October | 0.199148E+10 | 0.336440E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396794E+09 |
November | 0.192552E+10 | 0.326390E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465370E+09 |
December | 0.199054E+10 | 0.335662E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564021E+09 |
Annual Sum or Average | 0.234744E+11 | 0.396421E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3891857.42 | 0.482334E+10 |
Minimum of Months | 0.179968E+10 | 0.303891E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226758E+09 |
Maximum of Months | 0.199990E+10 | 0.337736E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2736721.74 | 0.566930E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.389749E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220481E+09 |
February | 0.208403E+10 | 0.351908E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197574E+09 |
March | 0.231589E+10 | 0.390950E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197581E+09 |
April | 0.223463E+10 | 0.376534E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 173440.63 | 0.156433E+09 |
May | 0.230993E+10 | 0.390424E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76132.52 | 0.149333E+09 |
June | 0.223950E+10 | 0.378261E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 796091.70 | 0.106541E+09 |
July | 0.230505E+10 | 0.388697E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1751939.84 | 91496253.87 |
August | 0.231480E+10 | 0.391100E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 556487.03 | 82916463.72 |
September | 0.223354E+10 | 0.376684E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79020.26 | 0.105058E+09 |
October | 0.230614E+10 | 0.389598E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154769E+09 |
November | 0.222975E+10 | 0.377961E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182240E+09 |
December | 0.230505E+10 | 0.388697E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219313E+09 |
Annual Sum or Average | 0.271834E+11 | 0.459056E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3433111.99 | 0.186374E+10 |
Minimum of Months | 0.208403E+10 | 0.351908E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82916463.72 |
Maximum of Months | 0.231589E+10 | 0.391100E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1751939.84 | 0.220481E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.697327E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546412E+09 |
February | 0.440737E+09 | 0.629623E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491367E+09 |
March | 0.489771E+09 | 0.699476E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502561E+09 |
April | 0.472586E+09 | 0.673684E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 691.39 | 0.414723E+09 |
May | 0.488511E+09 | 0.698536E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1968.34 | 0.404625E+09 |
June | 0.473617E+09 | 0.676774E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 461570.28 | 0.303758E+09 |
July | 0.487480E+09 | 0.695446E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2304195.68 | 0.266649E+09 |
August | 0.489542E+09 | 0.699745E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339247.16 | 0.246081E+09 |
September | 0.472357E+09 | 0.673953E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298957E+09 |
October | 0.487709E+09 | 0.697058E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414252E+09 |
November | 0.471555E+09 | 0.676237E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467449E+09 |
December | 0.487480E+09 | 0.695446E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542001E+09 |
Annual Sum or Average | 0.574883E+10 | 0.821331E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3107672.86 | 0.489884E+10 |
Minimum of Months | 0.440737E+09 | 0.629623E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246081E+09 |
Maximum of Months | 0.489771E+09 | 0.699745E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2304195.68 | 0.546412E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.159843E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297068E+09 |
February | 0.339028E+09 | 0.144324E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265730E+09 |
March | 0.376747E+09 | 0.160336E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264705E+09 |
April | 0.363528E+09 | 0.154423E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 349455.35 | 0.203011E+09 |
May | 0.375778E+09 | 0.160120E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 154618.57 | 0.192246E+09 |
June | 0.364321E+09 | 0.155132E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1403308.73 | 0.133388E+09 |
July | 0.374985E+09 | 0.159412E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2761460.21 | 0.112561E+09 |
August | 0.376571E+09 | 0.160397E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1028695.89 | 99672500.70 |
September | 0.363352E+09 | 0.154485E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 386495.87 | 0.129343E+09 |
October | 0.375161E+09 | 0.159781E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202033E+09 |
November | 0.362735E+09 | 0.155009E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243655E+09 |
December | 0.374985E+09 | 0.159412E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296358E+09 |
Annual Sum or Average | 0.442217E+10 | 0.188267E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6084034.63 | 0.243977E+10 |
Minimum of Months | 0.339028E+09 | 0.144324E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99672500.70 |
Maximum of Months | 0.376747E+09 | 0.160397E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2761460.21 | 0.297068E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.297499E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828133E+09 |
February | 0.139600E+10 | 0.268614E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741251E+09 |
March | 0.155131E+10 | 0.298416E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750642E+09 |
April | 0.149688E+10 | 0.287412E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597325E+09 |
May | 0.154732E+10 | 0.298015E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575181E+09 |
June | 0.150015E+10 | 0.288730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 630390.32 | 0.419953E+09 |
July | 0.154405E+10 | 0.296696E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 3146307.30 | 0.366214E+09 |
August | 0.155059E+10 | 0.298530E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 463377.23 | 0.336301E+09 |
September | 0.149615E+10 | 0.287527E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413798E+09 |
October | 0.154478E+10 | 0.297384E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600392E+09 |
November | 0.149361E+10 | 0.288501E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696955E+09 |
December | 0.154405E+10 | 0.296696E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825664E+09 |
Annual Sum or Average | 0.182090E+11 | 0.350402E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 4240074.85 | 0.715181E+10 |
Minimum of Months | 0.139600E+10 | 0.268614E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336301E+09 |
Maximum of Months | 0.155131E+10 | 0.298530E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 3146307.30 | 0.828133E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.641441E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126283E+10 |
February | 0.236489E+11 | 0.546719E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113190E+10 |
March | 0.262800E+11 | 0.569592E+09 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112908E+10 |
April | 0.253579E+11 | 0.484571E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080685.70 | 0.887503E+09 |
May | 0.262123E+11 | 0.440187E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356581.57 | 0.838782E+09 |
June | 0.254132E+11 | 0.397020E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5336694.56 | 0.584848E+09 |
July | 0.261570E+11 | 0.418488E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11396426.11 | 0.494213E+09 |
August | 0.262677E+11 | 0.480656E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3093782.42 | 0.446722E+09 |
September | 0.253456E+11 | 0.522535E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 318474.03 | 0.585640E+09 |
October | 0.261693E+11 | 0.603964E+09 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881045E+09 |
November | 0.253025E+11 | 0.617868E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104214E+10 |
December | 0.261570E+11 | 0.664619E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125656E+10 |
Annual Sum or Average | 0.308468E+12 | 0.638766E+10 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21582644.38 | 0.105413E+11 |
Minimum of Months | 0.236489E+11 | 0.397020E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446722E+09 |
Maximum of Months | 0.262800E+11 | 0.664619E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11396426.11 | 0.126283E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.648383E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371408E+10 |
February | 0.702046E+11 | 0.580574E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333009E+10 |
March | 0.780153E+11 | 0.640505E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333792E+10 |
April | 0.752779E+11 | 0.607100E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2675512.92 | 0.265936E+10 |
May | 0.778146E+11 | 0.621413E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1027764.16 | 0.253864E+10 |
June | 0.754422E+11 | 0.597911E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12216866.78 | 0.181944E+10 |
July | 0.776503E+11 | 0.615634E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27934273.75 | 0.156557E+10 |
August | 0.779788E+11 | 0.627770E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8077273.18 | 0.142560E+10 |
September | 0.752414E+11 | 0.612680E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 792993.88 | 0.180543E+10 |
October | 0.776868E+11 | 0.642812E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264392E+10 |
November | 0.751137E+11 | 0.628498E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309098E+10 |
December | 0.776503E+11 | 0.650756E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369083E+10 |
Annual Sum or Average | 0.915726E+12 | 0.747404E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 52724684.67 | 0.316219E+11 |
Minimum of Months | 0.702046E+11 | 0.580574E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142560E+10 |
Maximum of Months | 0.780153E+11 | 0.650756E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27934273.75 | 0.371408E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324166E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291901E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290033E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 216061.35 | 0.231453E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56375.30 | 0.219583E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 915456.30 | 0.153012E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2495891.88 | 0.128189E+09 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 678792.95 | 0.114391E+09 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 210228.78 | 0.149968E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226206E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266619E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320645E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4572806.57 | 0.271617E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114391E+09 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2495891.88 | 0.324166E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321302E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288766E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288590E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 214831.55 | 0.229368E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7965.35 | 0.219544E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 836649.47 | 0.155819E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2292936.44 | 0.134869E+09 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 555424.07 | 0.120112E+09 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.68 | 0.150180E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223182E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264135E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318788E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3908644.57 | 0.271465E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120112E+09 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2292936.44 | 0.321302E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103132E+09 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92424770.71 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88496354.27 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88107525.45 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87448857.44 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 725.02 | 67790942.83 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121473.06 | 61189203.02 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2385.11 | 57680654.06 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67262647.14 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87415187.61 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90796025.23 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85232535.26 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124583.19 | 0.976977E+09 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57680654.06 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121473.06 | 0.103132E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91813887.36 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82285184.38 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82586257.80 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65051.38 | 64414669.26 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9894.05 | 61360394.25 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 257958.63 | 42833205.63 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 674773.53 | 36351923.68 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 185317.24 | 32249790.20 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14429.51 | 41396362.22 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63698973.96 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75764013.61 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91388593.58 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1207424.36 | 0.766143E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32249790.20 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 674773.53 | 91813887.36 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324162E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291622E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290438E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 222443.96 | 0.233795E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57162.99 | 0.221642E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 926864.15 | 0.154067E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2479824.75 | 0.129422E+09 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 684773.19 | 0.115355E+09 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 216163.47 | 0.151716E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227131E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266583E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320920E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4587232.50 | 0.272685E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115355E+09 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2479824.75 | 0.324162E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321364E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288463E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289004E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 222446.67 | 0.231765E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9485.53 | 0.220899E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 834985.55 | 0.155910E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2245156.87 | 0.133880E+09 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 558197.37 | 0.120364E+09 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1953.47 | 0.151811E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223938E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264076E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319084E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3872225.45 | 0.272056E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120364E+09 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2245156.87 | 0.321364E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.109776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397171E+09 |
February | 0.348285E+10 | 0.991179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355270E+09 |
March | 0.387034E+10 | 0.110115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354050E+09 |
April | 0.373454E+10 | 0.106054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340898.45 | 0.275165E+09 |
May | 0.386038E+10 | 0.109967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156276.86 | 0.262758E+09 |
June | 0.374269E+10 | 0.106541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1479452.55 | 0.186273E+09 |
July | 0.385223E+10 | 0.109480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3236178.14 | 0.159912E+09 |
August | 0.386853E+10 | 0.110157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967705.21 | 0.144411E+09 |
September | 0.373273E+10 | 0.106097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182147.03 | 0.183068E+09 |
October | 0.385404E+10 | 0.109734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273158E+09 |
November | 0.372639E+10 | 0.106456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325939E+09 |
December | 0.385223E+10 | 0.109480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396192E+09 |
Annual Sum or Average | 0.454292E+11 | 0.129297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6362658.23 | 0.331337E+10 |
Minimum of Months | 0.348285E+10 | 0.991179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144411E+09 |
Maximum of Months | 0.387034E+10 | 0.110157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3236178.14 | 0.397171E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322987E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290922E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289278E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 204039.83 | 0.232688E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51704.48 | 0.220901E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 876610.36 | 0.154488E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2427695.74 | 0.129640E+09 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 654237.02 | 0.115644E+09 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 193684.36 | 0.150940E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225826E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265447E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319808E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4407971.79 | 0.271857E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115644E+09 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2427695.74 | 0.322987E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320541E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287694E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287738E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 203186.02 | 0.230981E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6651.58 | 0.221673E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 788206.98 | 0.158583E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2213396.14 | 0.138561E+09 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 524969.62 | 0.123226E+09 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151833E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222607E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262962E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318498E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3736410.34 | 0.272490E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123226E+09 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2213396.14 | 0.320541E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169700E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152605E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150998E+09 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 108192.07 | 0.120922E+09 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27563.36 | 0.114357E+09 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 456779.15 | 79481626.11 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248832.41 | 66641782.44 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 337676.10 | 59396384.35 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98855.97 | 78293598.80 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118580E+09 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139720E+09 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167188E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2277899.07 | 0.141788E+10 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59396384.35 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248832.41 | 0.169700E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.129804E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842518E+09 |
February | 0.415303E+11 | 0.113544E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754601E+09 |
March | 0.461508E+11 | 0.121881E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760324E+09 |
April | 0.445315E+11 | 0.109943E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 660314.84 | 0.601304E+09 |
May | 0.460320E+11 | 0.107098E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209290.62 | 0.577709E+09 |
June | 0.446286E+11 | 0.101033E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2638986.38 | 0.415173E+09 |
July | 0.459349E+11 | 0.104629E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6444098.82 | 0.355538E+09 |
August | 0.461292E+11 | 0.111629E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2065223.44 | 0.318996E+09 |
September | 0.445099E+11 | 0.114250E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 410778.34 | 0.399961E+09 |
October | 0.459565E+11 | 0.125000E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595259E+09 |
November | 0.444343E+11 | 0.125114E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700545E+09 |
December | 0.459349E+11 | 0.131406E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839803E+09 |
Annual Sum or Average | 0.541708E+12 | 0.139533E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 12428692.44 | 0.716173E+10 |
Minimum of Months | 0.415303E+11 | 0.101033E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318996E+09 |
Maximum of Months | 0.461508E+11 | 0.131406E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6444098.82 | 0.842518E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.129804E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857733E+09 |
February | 0.415303E+11 | 0.113544E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769002E+09 |
March | 0.461508E+11 | 0.121881E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777683E+09 |
April | 0.445315E+11 | 0.109943E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 536417.55 | 0.616456E+09 |
May | 0.460320E+11 | 0.107098E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147468.74 | 0.592382E+09 |
June | 0.446286E+11 | 0.101033E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2260640.01 | 0.427082E+09 |
July | 0.459349E+11 | 0.104629E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5961536.28 | 0.366897E+09 |
August | 0.461292E+11 | 0.111629E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1747870.67 | 0.330195E+09 |
September | 0.445099E+11 | 0.114250E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 219457.47 | 0.412455E+09 |
October | 0.459565E+11 | 0.125000E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611556E+09 |
November | 0.444343E+11 | 0.125114E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716233E+09 |
December | 0.459349E+11 | 0.131406E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854333E+09 |
Annual Sum or Average | 0.541708E+12 | 0.139533E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 10873390.73 | 0.733201E+10 |
Minimum of Months | 0.415303E+11 | 0.101033E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330195E+09 |
Maximum of Months | 0.461508E+11 | 0.131406E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5961536.28 | 0.857733E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.735117E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847647E+09 |
February | 0.369574E+10 | 0.663744E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758730E+09 |
March | 0.410691E+10 | 0.737383E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768667E+09 |
April | 0.396281E+10 | 0.710193E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612295E+09 |
May | 0.409635E+10 | 0.736392E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589868E+09 |
June | 0.397146E+10 | 0.713450E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 599957.17 | 0.431515E+09 |
July | 0.408770E+10 | 0.733135E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3110484.92 | 0.376827E+09 |
August | 0.410499E+10 | 0.737666E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 449044.11 | 0.346411E+09 |
September | 0.396089E+10 | 0.710477E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425282E+09 |
October | 0.408962E+10 | 0.734834E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615548E+09 |
November | 0.395417E+10 | 0.712884E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713856E+09 |
December | 0.408770E+10 | 0.733135E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845103E+09 |
Annual Sum or Average | 0.482060E+11 | 0.865841E+10 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 4159486.20 | 0.733175E+10 |
Minimum of Months | 0.369574E+10 | 0.663744E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346411E+09 |
Maximum of Months | 0.410691E+10 | 0.737666E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3110484.92 | 0.847647E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.116181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707137E+09 |
February | 0.368610E+10 | 0.104901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633257E+09 |
March | 0.409620E+10 | 0.116539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634685E+09 |
April | 0.395248E+10 | 0.112242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533836E+09 |
May | 0.408566E+10 | 0.116383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523766E+09 |
June | 0.396110E+10 | 0.112757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581857.42 | 0.396558E+09 |
July | 0.407704E+10 | 0.115868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3037910.50 | 0.351151E+09 |
August | 0.409429E+10 | 0.116584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436417.68 | 0.323101E+09 |
September | 0.395056E+10 | 0.112287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381091E+09 |
October | 0.407896E+10 | 0.116136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510271E+09 |
November | 0.394385E+10 | 0.112667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583515E+09 |
December | 0.407704E+10 | 0.115868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703801E+09 |
Annual Sum or Average | 0.480803E+11 | 0.136841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4056185.61 | 0.628217E+10 |
Minimum of Months | 0.368610E+10 | 0.104901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323101E+09 |
Maximum of Months | 0.409620E+10 | 0.116584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3037910.50 | 0.707137E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 7163.56 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 7163.56 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 7163.56 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 7163.56 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 7163.56 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 7163.56 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 7163.56 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 7163.56 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 7163.56 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 7163.56 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 7163.56 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 7163.56 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 324.19 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 348.07 | 11-JAN-24:00 |
February | 1169.53 | 01-FEB-00:10 | 324.19 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 322.57 | 17-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 324.19 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 279.63 | 08-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 324.19 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 30-APR-18:00 | 265.41 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 324.19 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 22-MAY-15:00 | 240.83 | 06-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 324.19 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 13-JUN-17:00 | 186.87 | 07-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 324.19 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 | 22-JUL-18:00 | 177.33 | 31-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 324.19 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.63 | 14-AUG-18:00 | 168.36 | 23-AUG-04:00 |
September | 1169.53 | 01-SEP-00:10 | 324.19 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 208.78 | 20-SEP-24:00 |
October | 1169.53 | 01-OCT-23:10 | 324.19 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 239.19 | 15-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 324.19 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 297.51 | 29-NOV-02:00 |
December | 1169.53 | 01-DEC-00:10 | 324.19 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 306.93 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 324.19 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.36 | |||||
Maximum of Months | 1169.53 | 324.19 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 | 348.07 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 375.41 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 136.20 | 11-JAN-24:00 |
February | 1354.32 | 01-FEB-00:10 | 375.41 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 125.14 | 17-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 375.41 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 109.40 | 08-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 375.41 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 30-APR-17:00 | 105.51 | 08-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 375.41 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 22-MAY-15:00 | 95.80 | 06-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 375.41 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 13-JUN-17:00 | 77.03 | 07-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 375.41 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.14 | 22-JUL-18:00 | 72.93 | 31-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 375.41 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 | 14-AUG-17:00 | 68.61 | 23-AUG-04:00 |
September | 1354.32 | 01-SEP-00:10 | 375.41 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.78 | 11-SEP-17:00 | 83.77 | 20-SEP-24:00 |
October | 1354.32 | 01-OCT-23:10 | 375.41 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 96.60 | 07-OCT-04:00 |
November | 1354.32 | 01-NOV-00:10 | 375.41 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 116.10 | 29-NOV-02:00 |
December | 1354.32 | 01-DEC-00:10 | 375.41 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 121.66 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.61 | |||||
Maximum of Months | 1354.32 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 32.14 | 136.20 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 671.67 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 322.37 | 11-JAN-24:00 |
February | 286.42 | 01-FEB-00:10 | 671.67 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 303.46 | 17-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 671.67 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 269.67 | 08-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 671.67 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 | 30-APR-15:00 | 262.83 | 08-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 671.67 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 22-MAY-15:00 | 240.57 | 07-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 671.67 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 | 13-JUN-16:52 | 198.39 | 07-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 671.67 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 | 22-JUL-18:00 | 190.07 | 31-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 671.67 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 14-AUG-17:00 | 180.24 | 24-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 671.67 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 214.05 | 20-SEP-24:00 |
October | 286.42 | 01-OCT-23:10 | 671.67 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 241.52 | 07-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 671.67 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 282.07 | 29-NOV-02:00 |
December | 286.42 | 01-DEC-00:10 | 671.67 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 294.26 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 | |||||
Maximum of Months | 286.42 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 | 322.37 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 153.96 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 183.20 | 11-JAN-24:00 |
February | 220.32 | 01-FEB-00:10 | 153.96 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 169.77 | 17-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 153.96 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 147.18 | 08-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 153.96 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 30-APR-17:00 | 139.69 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 153.96 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.25 | 22-MAY-15:00 | 126.75 | 06-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 153.96 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 13-JUN-16:51 | 98.35 | 07-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 153.96 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 | 22-JUL-18:00 | 92.69 | 31-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 153.96 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 14-AUG-17:00 | 86.73 | 20-AUG-05:00 |
September | 220.32 | 01-SEP-00:10 | 153.96 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.15 | 11-SEP-17:00 | 105.96 | 20-SEP-24:00 |
October | 220.32 | 01-OCT-23:10 | 153.96 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 125.89 | 15-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 153.96 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 156.58 | 29-NOV-02:00 |
December | 220.32 | 01-DEC-00:10 | 153.96 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 161.55 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 153.96 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 | |||||
Maximum of Months | 220.32 | 153.96 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 | 183.20 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 286.55 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 481.73 | 11-JAN-24:00 |
February | 907.20 | 01-FEB-00:10 | 286.55 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 449.96 | 17-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 286.55 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 395.81 | 08-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 286.55 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 377.81 | 08-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 286.55 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 347.33 | 06-MAY-05:00 |
June | 907.20 | 01-JUN-00:10 | 286.55 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 42.90 | 13-JUN-16:51 | 279.30 | 07-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 286.55 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 84.71 | 22-JUL-18:00 | 262.87 | 31-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 286.55 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 43.01 | 14-AUG-18:00 | 246.13 | 20-AUG-05:00 |
September | 907.20 | 01-SEP-00:10 | 286.55 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 296.80 | 21-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 286.55 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 344.96 | 15-OCT-04:00 |
November | 907.20 | 01-NOV-00:10 | 286.55 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 418.90 | 29-NOV-02:00 |
December | 907.20 | 01-DEC-00:10 | 286.55 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 430.09 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 246.13 | ||||||
Maximum of Months | 907.20 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 84.71 | 481.73 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 767.68 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 782.12 | 11-JAN-24:00 |
February | 15368.40 | 01-FEB-00:10 | 767.68 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 713.07 | 17-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 767.68 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 618.20 | 08-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 767.68 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 30-APR-18:00 | 605.83 | 08-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 767.68 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.40 | 22-MAY-15:00 | 552.78 | 06-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 767.68 | 01-JUN-19:30 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.78 | 13-JUN-17:00 | 441.77 | 07-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 767.68 | 17-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.95 | 22-JUL-18:00 | 416.39 | 31-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 767.68 | 01-AUG-19:49 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.51 | 14-AUG-18:00 | 389.36 | 23-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 767.68 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 | 11-SEP-17:00 | 478.87 | 20-SEP-24:00 |
October | 15368.40 | 01-OCT-23:10 | 767.68 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 554.79 | 07-OCT-04:00 |
November | 15368.40 | 01-NOV-00:10 | 767.68 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 670.43 | 29-NOV-02:00 |
December | 15368.40 | 01-DEC-00:10 | 767.68 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 691.10 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 767.68 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.36 | |||||
Maximum of Months | 15368.40 | 767.68 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 202.95 | 782.12 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 6458.51 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2300.82 | 11-JAN-24:00 |
February | 45622.98 | 01-FEB-00:10 | 6458.51 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2109.12 | 17-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 6458.51 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1853.26 | 08-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 6458.51 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.83 | 30-APR-17:00 | 1798.36 | 08-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 6458.51 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.64 | 22-MAY-15:00 | 1643.75 | 06-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 6458.51 | 01-JUN-19:30 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.69 | 13-JUN-17:00 | 1328.06 | 07-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 6458.51 | 17-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 526.76 | 22-JUL-18:00 | 1254.43 | 31-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 6458.51 | 01-AUG-19:49 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.51 | 14-AUG-17:00 | 1174.97 | 23-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 6458.51 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.16 | 11-SEP-17:00 | 1428.08 | 20-SEP-24:00 |
October | 45622.98 | 01-OCT-23:10 | 6458.51 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1648.32 | 07-OCT-04:00 |
November | 45622.98 | 01-NOV-00:10 | 6458.51 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1981.24 | 29-NOV-02:00 |
December | 45622.98 | 01-DEC-00:10 | 6458.51 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2060.24 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.97 | |||||
Maximum of Months | 45622.98 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 526.76 | 2300.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.17 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 188.36 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 163.44 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.17 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 22-MAY-15:20 | 140.90 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 | 13-JUN-16:50 | 109.57 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 22-JUL-18:10 | 101.98 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.98 | 14-AUG-16:50 | 94.29 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 13-SEP-15:20 | 117.58 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.94 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.82 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 179.28 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 203.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.16 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 188.34 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 163.42 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.16 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 22-MAY-15:00 | 140.89 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 | 13-JUN-16:50 | 109.56 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.19 | 22-JUL-18:10 | 101.97 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.98 | 14-AUG-16:50 | 94.28 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22-SEP-13:00 | 117.57 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.93 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.81 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 179.27 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 56.19 | 203.16 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 59.12 | 11-JAN-24:00 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 55.81 | 17-FEB-21:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 46.66 | 02-MAR-21:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 51.04 | 08-APR-05:40 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 48.15 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 13-JUN-17:00 | 40.24 | 01-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 22-JUL-18:00 | 38.70 | 31-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 14-AUG-16:53 | 37.41 | 24-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 44.09 | 21-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 49.09 | 07-OCT-04:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 51.02 | 28-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 47.78 | 26-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.41 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 59.12 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 56.70 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 52.57 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 45.61 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 30-APR-19:00 | 43.31 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 22-MAY-15:00 | 39.32 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 | 13-JUN-16:50 | 30.58 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 22-JUL-18:10 | 28.46 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 14-AUG-16:50 | 26.31 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 27-SEP-16:00 | 32.82 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 39.06 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 48.51 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 50.04 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.31 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 56.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.17 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 188.36 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 163.44 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.17 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 22-MAY-15:20 | 140.90 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 | 13-JUN-16:50 | 109.57 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 22-JUL-18:10 | 101.98 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.98 | 14-AUG-16:50 | 94.29 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 13-SEP-15:18 | 117.58 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.94 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.82 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 179.28 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 203.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.16 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 188.34 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 163.42 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.16 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 22-MAY-15:00 | 140.89 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 | 13-JUN-16:50 | 109.56 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 22-JUL-18:10 | 101.97 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.98 | 14-AUG-16:50 | 94.28 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 27-SEP-16:00 | 117.57 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.93 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.81 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 179.26 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 203.16 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1057.37 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 244.68 | 11-JAN-24:00 |
February | 2263.36 | 01-FEB-00:10 | 1057.37 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 226.77 | 17-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1057.37 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 196.65 | 08-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1057.37 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 | 30-APR-17:00 | 186.90 | 08-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1057.37 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 22-MAY-15:00 | 169.99 | 06-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1057.37 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.91 | 13-JUN-17:00 | 135.05 | 07-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1057.37 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.60 | 22-JUL-18:00 | 129.30 | 31-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1057.37 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.82 | 14-AUG-17:00 | 121.71 | 23-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1057.37 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 | 11-SEP-17:00 | 146.44 | 20-SEP-24:00 |
October | 2263.36 | 01-OCT-23:10 | 1057.37 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 170.80 | 07-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1057.37 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 209.19 | 29-NOV-02:00 |
December | 2263.36 | 01-DEC-00:10 | 1057.37 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 215.80 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1057.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.71 | ||||
Maximum of Months | 2263.36 | 1057.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.60 | 244.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.66 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 188.84 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 163.91 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | 30-APR-19:00 | 155.64 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 | 22-MAY-15:20 | 141.37 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 13-JUN-16:50 | 110.02 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.62 | 22-JUL-18:10 | 102.43 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.59 | 14-AUG-16:50 | 94.73 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 13-SEP-15:20 | 118.04 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 140.41 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 174.31 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 179.76 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 55.62 | 203.66 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.65 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 188.82 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 163.90 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | 30-APR-19:00 | 155.62 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 22-MAY-15:00 | 141.36 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 13-JUN-16:50 | 110.01 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 | 22-JUL-18:10 | 102.42 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.59 | 14-AUG-16:50 | 94.73 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 118.03 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 140.40 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 174.29 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 179.75 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 | 203.65 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 104.20 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 96.62 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 83.86 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 30-APR-19:00 | 79.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 22-MAY-15:20 | 72.33 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 13-JUN-16:50 | 56.29 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 | 22-JUL-18:08 | 52.41 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 14-AUG-16:50 | 48.47 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 13-SEP-15:20 | 60.39 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 71.84 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 89.18 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 91.97 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 | 104.20 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1348.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 528.69 | 11-JAN-24:00 |
February | 26988.77 | 01-FEB-00:10 | 1348.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 479.71 | 17-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 1348.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 421.50 | 08-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 1348.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.61 | 30-APR-18:00 | 405.98 | 08-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 1348.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 | 22-MAY-15:00 | 373.24 | 06-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 1348.12 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.17 | 13-JUN-17:00 | 300.34 | 07-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 1348.12 | 17-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.67 | 22-JUL-18:00 | 283.15 | 31-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 1348.12 | 01-AUG-19:49 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 14-AUG-18:00 | 264.57 | 23-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 1348.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 | 13-SEP-14:00 | 319.21 | 20-SEP-24:00 |
October | 26988.77 | 01-OCT-23:10 | 1348.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 369.25 | 07-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 1348.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 448.41 | 29-NOV-02:00 |
December | 26988.77 | 01-DEC-00:10 | 1348.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 471.93 | 29-DEC-23:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1348.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.57 | |||||
Maximum of Months | 26988.77 | 1348.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.67 | 528.69 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1348.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 535.07 | 11-JAN-24:00 |
February | 26988.77 | 01-FEB-00:10 | 1348.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 486.24 | 17-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 1348.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 428.26 | 08-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 1348.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.69 | 30-APR-16:00 | 411.27 | 08-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 1348.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 | 22-MAY-15:00 | 378.37 | 06-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 1348.12 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.54 | 13-JUN-17:00 | 304.79 | 07-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 1348.12 | 17-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.16 | 22-JUL-18:00 | 287.00 | 31-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 1348.12 | 01-AUG-19:49 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 | 14-AUG-18:00 | 268.09 | 23-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 1348.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 | 13-SEP-14:00 | 324.18 | 20-SEP-24:00 |
October | 26988.77 | 01-OCT-23:10 | 1348.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 374.03 | 07-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 1348.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 454.54 | 29-NOV-02:00 |
December | 26988.77 | 01-DEC-00:10 | 1348.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 478.49 | 29-DEC-23:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1348.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.09 | |||||
Maximum of Months | 26988.77 | 1348.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 116.16 | 535.07 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 708.07 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 492.34 | 11-JAN-24:00 |
February | 2401.70 | 01-FEB-00:10 | 708.07 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 459.95 | 17-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 708.07 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 404.76 | 08-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 708.07 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 386.41 | 08-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 708.07 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 355.42 | 06-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 708.07 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 42.31 | 13-JUN-16:51 | 286.08 | 07-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 708.07 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 85.06 | 22-JUL-18:00 | 269.33 | 31-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 708.07 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 42.56 | 14-AUG-18:00 | 252.28 | 20-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 708.07 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 303.87 | 21-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 708.07 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 353.01 | 15-OCT-04:00 |
November | 2401.70 | 01-NOV-00:10 | 708.07 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 428.38 | 29-NOV-02:00 |
December | 2401.70 | 01-DEC-00:10 | 708.07 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 439.63 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 708.07 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 252.28 | ||||||
Maximum of Months | 2401.70 | 708.07 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 85.06 | 492.34 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1119.06 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 433.98 | 11-JAN-24:00 |
February | 2395.44 | 01-FEB-00:10 | 1119.06 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 402.26 | 17-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1119.06 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 348.95 | 08-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1119.06 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 337.95 | 08-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1119.06 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 311.27 | 06-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1119.06 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 | 13-JUN-16:51 | 257.53 | 01-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1119.06 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.02 | 22-JUL-18:00 | 246.67 | 31-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1119.06 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.41 | 14-AUG-17:40 | 233.14 | 23-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1119.06 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 275.54 | 20-SEP-24:00 |
October | 2395.44 | 01-OCT-23:10 | 1119.06 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 310.78 | 07-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1119.06 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 371.15 | 29-NOV-02:00 |
December | 2395.44 | 01-DEC-00:10 | 1119.06 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 382.85 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1119.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.14 | ||||
Maximum of Months | 2395.44 | 1119.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.02 | 433.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12371.71 | 20-JAN-21:00 | 8945.92 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12206.03 | 01-FEB-21:00 | 8945.92 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11914.64 | 25-MAR-10:35 | 7667.93 | 3979.81 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12957.88 | 30-APR-10:35 | 7667.93 | 4775.64 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12731.93 | 22-MAY-18:10 | 62621.41 | 44573.36 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13235.07 | 25-JUN-10:35 | 7667.93 | 4775.64 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13884.04 | 23-JUL-10:35 | 7667.93 | 4775.64 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13678.43 | 19-AUG-10:35 | 7667.93 | 3979.81 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13941.40 | 10-SEP-10:35 | 7667.93 | 4775.64 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13805.79 | 07-OCT-10:35 | 7667.93 | 3979.81 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13323.98 | 08-NOV-19:10 | 35783.66 | 25470.49 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13030.30 | 01-DEC-21:00 | 8945.92 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11914.64 | 7667.93 | 3979.81 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13941.40 | 62621.41 | 44573.36 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1220.50 | 21-JAN-11:35 | 779.69 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.12 |
February | 1241.45 | 04-FEB-11:50 | 389.84 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.66 |
March | 1079.06 | 25-MAR-10:35 | 779.69 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.71 |
April | 1842.94 | 30-APR-13:10 | 519.79 | 144.08 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 |
May | 1437.31 | 23-MAY-10:35 | 519.79 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 |
June | 1638.77 | 13-JUN-14:10 | 389.84 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 0.00 |
July | 2103.54 | 22-JUL-13:30 | 389.84 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 | 0.00 |
August | 1922.76 | 19-AUG-13:00 | 389.84 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 |
September | 2173.16 | 27-SEP-13:20 | 519.79 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 |
October | 1729.61 | 07-OCT-13:20 | 779.69 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.30 |
November | 1243.57 | 11-NOV-11:35 | 779.69 | 216.12 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.76 |
December | 1102.71 | 08-DEC-11:40 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1079.06 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2173.16 | 779.69 | 216.12 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 | 201.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1183.35 | 19-JAN-21:00 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.03 |
February | 1182.90 | 27-FEB-21:00 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.79 |
March | 1204.78 | 20-MAR-20:00 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.15 |
April | 1457.62 | 29-APR-18:10 | 6320.16 | 2043.89 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
May | 1463.91 | 22-MAY-18:10 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 |
June | 1509.62 | 13-JUN-18:00 | 752.40 | 250.27 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
July | 1602.20 | 22-JUL-18:10 | 5417.28 | 1751.90 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 31.07 | 0.00 |
August | 1523.93 | 14-AUG-18:10 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 17.87 | 0.00 |
September | 1495.25 | 13-SEP-18:10 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
October | 1333.71 | 01-OCT-10:35 | 902.88 | 250.27 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.94 |
November | 1202.53 | 10-NOV-21:00 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.31 |
December | 1150.15 | 20-DEC-21:00 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1150.15 | 752.40 | 250.27 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1602.20 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 31.07 | 91.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18.72 | 19-JAN-21:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.68 |
February | 18.47 | 08-FEB-21:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.73 |
March | 19.40 | 20-MAR-20:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.53 |
April | 530.64 | 30-APR-19:15 | 763.78 | 2388.16 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 |
May | 575.65 | 23-MAY-20:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.79 |
June | 854.66 | 13-JUN-20:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.88 |
July | 938.25 | 22-JUL-20:53 | 668.30 | 1567.23 | 2120.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
August | 788.11 | 17-AUG-21:00 | 254.59 | 597.04 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.81 |
September | 702.42 | 13-SEP-20:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 |
October | 255.12 | 02-OCT-20:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.71 |
November | 19.65 | 10-NOV-21:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.95 |
December | 17.91 | 05-DEC-21:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17.91 | 222.77 | 597.04 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | |
Maximum of Months | 938.25 | 763.78 | 2388.16 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 454.62 | 18-JAN-22:00 | 195.84 | 136.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 |
February | 403.36 | 07-FEB-22:00 | 195.84 | 136.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.33 |
March | 482.63 | 20-MAR-21:00 | 195.84 | 136.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.50 |
April | 800.43 | 30-APR-10:35 | 146.88 | 102.64 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 |
May | 785.83 | 23-MAY-10:35 | 97.92 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
June | 821.92 | 13-JUN-10:35 | 97.92 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
July | 885.91 | 23-JUL-10:35 | 146.88 | 102.64 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
August | 821.54 | 19-AUG-10:35 | 146.88 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.34 |
September | 787.58 | 13-SEP-10:35 | 97.92 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 |
October | 646.93 | 02-OCT-20:00 | 171.36 | 153.96 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.26 |
November | 561.45 | 08-NOV-22:00 | 195.84 | 136.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.91 |
December | 326.30 | 05-DEC-21:00 | 171.36 | 153.96 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 326.30 | 97.92 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 885.91 | 195.84 | 153.96 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 105.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37029.20 | 23-JAN-21:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 227.86 |
February | 36994.89 | 22-FEB-21:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 291.52 |
March | 37135.51 | 30-MAR-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 262.33 |
April | 38042.98 | 28-APR-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 165.09 |
May | 38179.14 | 22-MAY-19:57 | 2116.80 | 859.66 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 0.00 | 103.67 |
June | 38462.77 | 13-JUN-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.60 |
July | 38477.80 | 21-JUL-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 |
August | 38349.07 | 14-AUG-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 |
September | 38171.32 | 13-SEP-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 133.97 |
October | 37536.19 | 06-OCT-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 244.61 |
November | 37162.61 | 08-NOV-21:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 196.61 |
December | 36863.87 | 20-DEC-21:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 261.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36863.87 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 | |
Maximum of Months | 38477.80 | 2116.80 | 859.66 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 0.00 | 291.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9282.22 | 15-JAN-11:35 | 10245.60 | 112.59 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.60 |
February | 9368.96 | 04-FEB-11:35 | 10245.60 | 93.83 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.58 |
March | 8228.61 | 20-MAR-18:05 | 47812.80 | 1785.32 | 3657.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.67 |
April | 10560.37 | 30-APR-10:35 | 10245.60 | 112.59 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 |
May | 10013.33 | 22-MAY-18:10 | 83672.40 | 1050.87 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.30 |
June | 10369.76 | 12-JUN-18:10 | 83672.40 | 1050.87 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 101.72 | 0.00 |
July | 10836.84 | 23-JUL-10:35 | 10245.60 | 112.59 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
August | 10510.33 | 14-AUG-18:10 | 83672.40 | 1050.87 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 117.20 | 0.00 |
September | 10600.63 | 23-SEP-10:35 | 10245.60 | 93.83 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.89 |
October | 10125.09 | 07-OCT-10:35 | 10245.60 | 93.83 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.60 |
November | 9415.59 | 11-NOV-11:35 | 10245.60 | 112.59 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.34 |
December | 8404.20 | 03-DEC-11:35 | 10245.60 | 112.59 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8228.61 | 10245.60 | 93.83 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10836.84 | 83672.40 | 1785.32 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 117.20 | 399.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26409.95 | 18-JAN-22:00 | 40553.76 | 5740.90 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1142.21 |
February | 26275.15 | 27-FEB-21:00 | 35484.54 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1264.54 |
March | 26724.48 | 20-MAR-20:00 | 35484.54 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.49 |
April | 30832.92 | 30-APR-10:35 | 30415.32 | 3702.88 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.84 |
May | 30648.97 | 22-MAY-18:10 | 248391.78 | 35128.55 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.85 |
June | 31560.87 | 12-JUN-18:10 | 248391.78 | 34560.21 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 238.11 | 0.00 |
July | 33011.48 | 22-JUL-18:10 | 182491.92 | 25920.16 | 50673.90 | 0.00 | 0.00 | 0.00 | 0.00 | 510.65 | 0.00 |
August | 31863.04 | 14-AUG-18:10 | 248391.78 | 35836.63 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 284.58 | 0.00 |
September | 31245.25 | 13-SEP-18:10 | 248391.78 | 38403.93 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.87 |
October | 29190.48 | 01-OCT-10:35 | 30415.32 | 3702.88 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.36 |
November | 26964.97 | 11-NOV-11:35 | 30415.32 | 3702.88 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.41 |
December | 25814.06 | 20-DEC-21:00 | 35484.54 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1181.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25814.06 | 30415.32 | 3702.88 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33011.48 | 248391.78 | 38403.93 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 510.65 | 1264.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1881.93 | 19-JAN-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 |
February | 2440.43 | 17-FEB-16:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 |
March | 1767.52 | 23-MAR-18:03 | 554.40 | 337.19 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.12 |
April | 2625.84 | 14-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.18 |
May | 2561.48 | 11-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 |
June | 2386.76 | 11-JUN-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 |
July | 2469.79 | 09-JUL-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 |
August | 2435.66 | 12-AUG-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 |
September | 2397.97 | 09-SEP-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 |
October | 2459.34 | 06-OCT-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.00 |
November | 1960.73 | 10-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.79 |
December | 794.00 | 05-DEC-19:04 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 794.00 | 378.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | |
Maximum of Months | 2625.84 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 756.43 | 21-JAN-16:13 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.19 |
February | 1753.49 | 27-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.13 |
March | 1597.26 | 23-MAR-18:03 | 554.40 | 337.15 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.77 |
April | 2378.40 | 14-APR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.66 |
May | 2246.19 | 11-MAY-19:32 | 831.60 | 568.23 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.95 |
June | 2324.36 | 22-JUN-19:01 | 1386.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.73 |
July | 2407.82 | 14-JUL-18:01 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.34 |
August | 2221.66 | 28-AUG-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
September | 2261.46 | 14-SEP-18:01 | 1247.40 | 758.59 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.89 |
October | 2174.07 | 06-OCT-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.98 |
November | 805.93 | 24-NOV-16:14 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 |
December | 710.60 | 05-DEC-19:04 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 710.60 | 378.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2407.82 | 1386.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 114.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 134.89 | 01-JAN-15:05 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.05 |
February | 123.35 | 19-FEB-15:15 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 |
March | 100.99 | 25-MAR-14:15 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 |
April | 317.95 | 30-APR-13:05 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 |
May | 226.87 | 23-MAY-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 |
June | 253.90 | 13-JUN-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
July | 306.26 | 22-JUL-13:30 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
August | 311.12 | 20-AUG-13:00 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 |
September | 389.09 | 25-SEP-13:30 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.93 |
October | 334.78 | 07-OCT-13:15 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 |
November | 144.29 | 11-NOV-15:05 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 |
December | 82.00 | 26-DEC-15:15 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 82.00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 389.09 | 0.00 | 39.29 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 46.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 692.12 | 29-JAN-19:02 | 585.00 | 297.71 | 593.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.97 |
February | 668.07 | 01-FEB-09:02 | 216.00 | 157.19 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.09 |
March | 759.42 | 04-MAR-09:02 | 270.00 | 166.72 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 |
April | 817.11 | 20-APR-18:01 | 1108.80 | 423.94 | 949.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 |
May | 802.67 | 11-MAY-19:32 | 831.60 | 357.25 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 |
June | 814.69 | 12-JUN-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 0.00 |
July | 824.65 | 21-JUL-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 |
August | 791.32 | 28-AUG-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 0.00 |
September | 763.69 | 13-SEP-19:31 | 1108.80 | 476.34 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 |
October | 783.80 | 07-OCT-18:02 | 702.00 | 357.25 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.05 |
November | 693.31 | 23-NOV-09:02 | 216.00 | 133.37 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 |
December | 660.37 | 30-DEC-09:01 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 660.37 | 216.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 824.65 | 1108.80 | 476.34 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 43.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 756.34 | 06-JAN-09:04 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.59 |
February | 1573.85 | 20-FEB-09:02 | 324.00 | 318.25 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.90 |
March | 702.09 | 10-MAR-09:02 | 180.00 | 208.38 | 566.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.06 |
April | 2385.97 | 14-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.95 |
May | 2304.12 | 11-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.43 |
June | 2223.90 | 12-JUN-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 0.00 |
July | 2243.34 | 23-JUL-18:02 | 702.00 | 568.30 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 |
August | 2224.70 | 27-AUG-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 |
September | 2226.78 | 10-SEP-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 |
October | 2226.66 | 06-OCT-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.20 |
November | 1670.23 | 11-NOV-09:02 | 270.00 | 265.21 | 816.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 |
December | 795.65 | 19-DEC-09:04 | 252.00 | 291.73 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 702.09 | 180.00 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2385.97 | 970.20 | 590.08 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 139.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 724.90 | 23-JAN-09:03 | 216.00 | 250.02 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.28 |
February | 765.92 | 27-FEB-16:14 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.99 |
March | 660.98 | 07-MAR-09:04 | 180.00 | 208.35 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.04 |
April | 2059.65 | 30-APR-08:51 | 432.00 | 424.28 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.34 |
May | 2178.79 | 23-MAY-08:51 | 288.00 | 333.36 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.27 |
June | 2256.56 | 13-JUN-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 |
July | 2439.87 | 22-JUL-08:41 | 540.00 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 |
August | 2232.32 | 14-AUG-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.43 |
September | 2131.15 | 12-SEP-08:51 | 288.00 | 333.36 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.44 |
October | 1863.05 | 01-OCT-08:61 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.13 |
November | 703.00 | 20-NOV-19:05 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.53 |
December | 737.96 | 20-DEC-09:04 | 252.00 | 291.69 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 660.98 | 180.00 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | |
Maximum of Months | 2439.87 | 831.60 | 530.35 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1300.01 | 23-JAN-22:00 | 2011.87 | 939.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.13 |
February | 1291.84 | 27-FEB-22:00 | 2011.87 | 939.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.87 |
March | 1344.59 | 20-MAR-18:03 | 7041.55 | 3759.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.87 |
April | 1848.87 | 30-APR-10:35 | 1508.90 | 704.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 |
May | 1781.17 | 23-MAY-10:35 | 1005.94 | 587.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 |
June | 1876.03 | 26-JUN-18:10 | 12322.72 | 6579.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 |
July | 2022.18 | 23-JUL-10:35 | 1508.90 | 704.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 |
August | 1911.59 | 19-AUG-10:35 | 1508.90 | 587.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.46 |
September | 1818.98 | 13-SEP-18:10 | 12322.72 | 6579.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.95 |
October | 1713.88 | 01-OCT-10:35 | 1508.90 | 704.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.01 |
November | 1311.23 | 08-NOV-22:00 | 2011.87 | 939.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.83 |
December | 1164.25 | 21-DEC-22:10 | 4526.71 | 1409.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1164.25 | 1005.94 | 587.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | |
Maximum of Months | 2022.18 | 12322.72 | 6579.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1967.37 | 19-JAN-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.09 |
February | 2523.28 | 17-FEB-16:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.45 |
March | 1854.02 | 23-MAR-18:03 | 554.40 | 337.19 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.00 |
April | 2764.34 | 14-APR-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.78 |
May | 2731.09 | 11-MAY-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.93 |
June | 2507.12 | 26-JUN-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.78 |
July | 2524.03 | 16-JUL-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 |
August | 2531.86 | 18-AUG-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 |
September | 2519.25 | 14-SEP-18:01 | 1247.40 | 758.68 | 1090.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.89 |
October | 2572.30 | 06-OCT-18:02 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 |
November | 2058.30 | 10-NOV-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.47 |
December | 803.34 | 21-DEC-16:14 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 803.34 | 554.40 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | |
Maximum of Months | 2764.34 | 1247.40 | 758.68 | 1090.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 794.67 | 25-JAN-16:14 | 486.00 | 132.59 | 250.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.81 |
February | 1796.71 | 27-FEB-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.72 |
March | 1610.35 | 23-MAR-18:03 | 554.40 | 337.15 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.43 |
April | 2492.01 | 14-APR-15:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 |
May | 2471.92 | 23-MAY-20:01 | 1602.00 | 842.88 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.96 |
June | 2497.05 | 22-JUN-19:01 | 1386.00 | 947.05 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.96 |
July | 2584.73 | 28-JUL-18:11 | 1386.00 | 842.88 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.91 |
August | 2394.90 | 04-AUG-20:01 | 1281.60 | 674.30 | 1453.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.14 |
September | 2423.51 | 14-SEP-18:01 | 1247.40 | 758.59 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.75 |
October | 2254.20 | 06-OCT-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.92 |
November | 959.42 | 05-NOV-15:13 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 |
December | 717.52 | 16-DEC-09:05 | 324.00 | 318.21 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 717.52 | 324.00 | 132.59 | 250.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.14 | |
Maximum of Months | 2584.73 | 1602.00 | 947.05 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1687.24 | 11-JAN-16:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.62 |
February | 1484.75 | 27-FEB-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.32 |
March | 1403.38 | 25-MAR-15:12 | 270.00 | 98.24 | 270.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 |
April | 1502.73 | 30-APR-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 0.00 |
May | 1731.24 | 11-MAY-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 |
June | 1642.06 | 13-JUN-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
July | 1652.26 | 22-JUL-08:61 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 0.00 |
August | 1633.16 | 01-AUG-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 |
September | 1641.77 | 11-SEP-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
October | 1596.06 | 10-OCT-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.89 |
November | 1501.35 | 10-NOV-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 |
December | 1619.01 | 26-DEC-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1403.38 | 270.00 | 98.24 | 270.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1731.24 | 970.20 | 416.79 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 91.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16835.81 | 18-JAN-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.54 |
February | 16769.53 | 07-FEB-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.58 |
March | 16872.98 | 30-MAR-22:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.16 |
April | 18766.58 | 29-APR-17:50 | 17992.51 | 539.25 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 |
May | 19260.47 | 22-MAY-18:10 | 146938.85 | 5032.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.75 |
June | 19909.28 | 12-JUN-18:10 | 146938.85 | 5032.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 50.75 | 0.00 |
July | 20085.07 | 22-JUL-18:00 | 17992.51 | 539.25 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.67 | 0.00 |
August | 19518.93 | 14-AUG-18:10 | 146938.85 | 5032.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 0.00 |
September | 18766.58 | 13-SEP-18:10 | 146938.85 | 7084.49 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.05 |
October | 17285.99 | 02-OCT-22:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.25 |
November | 17096.51 | 08-NOV-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.27 |
December | 16604.44 | 04-DEC-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16604.44 | 17992.51 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20085.07 | 146938.85 | 7084.49 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 120.67 | 317.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17690.98 | 18-JAN-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.28 |
February | 17622.64 | 07-FEB-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.32 |
March | 17738.77 | 30-MAR-22:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.06 |
April | 19446.04 | 29-APR-17:50 | 17992.51 | 539.25 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.46 |
May | 19962.24 | 22-MAY-18:10 | 146938.85 | 5032.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.99 |
June | 20563.37 | 12-JUN-18:10 | 146938.85 | 5032.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 | 0.00 |
July | 20718.28 | 22-JUL-18:00 | 17992.51 | 539.25 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 116.16 | 0.00 |
August | 20143.53 | 14-AUG-18:10 | 146938.85 | 5032.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 60.95 | 0.00 |
September | 19420.85 | 11-SEP-18:10 | 146938.85 | 6895.84 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.74 |
October | 18069.70 | 17-OCT-22:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.14 |
November | 17971.30 | 08-NOV-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.02 |
December | 17441.23 | 04-DEC-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17441.23 | 17992.51 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20718.28 | 146938.85 | 6895.84 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 116.16 | 324.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25885.61 | 15-JAN-11:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 241.19 |
February | 25929.03 | 22-FEB-11:40 | 533.71 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 215.27 |
March | 26537.78 | 25-MAR-10:50 | 800.57 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 194.62 |
April | 28351.42 | 30-APR-10:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 73.29 |
May | 28128.59 | 23-MAY-10:50 | 533.71 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 61.22 |
June | 28535.52 | 25-JUN-10:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 53.80 |
July | 28952.47 | 23-JUL-10:40 | 1601.14 | 472.05 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 |
August | 28320.72 | 19-AUG-10:50 | 800.57 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 91.96 |
September | 28022.94 | 10-SEP-10:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.24 |
October | 27218.17 | 07-OCT-10:50 | 800.57 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 141.06 |
November | 25894.79 | 11-NOV-11:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 236.07 |
December | 25265.20 | 03-DEC-11:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 273.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25265.20 | 533.71 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 | |
Maximum of Months | 28952.47 | 1601.14 | 472.05 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 273.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1664.38 | 21-JAN-11:35 | 1596.96 | 621.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.91 |
February | 1707.91 | 22-FEB-11:40 | 532.32 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.07 |
March | 1747.11 | 25-MAR-10:50 | 798.48 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.96 |
April | 3095.06 | 30-APR-15:10 | 798.48 | 248.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 |
May | 2839.23 | 23-MAY-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.94 |
June | 3857.44 | 13-JUN-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 0.00 |
July | 4439.50 | 22-JUL-14:10 | 798.48 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 0.00 |
August | 3481.90 | 19-AUG-13:40 | 798.48 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.20 |
September | 2901.20 | 13-SEP-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 |
October | 2126.19 | 01-OCT-10:35 | 1596.96 | 746.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.85 |
November | 1720.94 | 11-NOV-11:35 | 1596.96 | 746.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.18 |
December | 1555.03 | 03-DEC-11:50 | 798.48 | 373.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1555.03 | 532.32 | 248.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4439.50 | 1596.96 | 746.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 232.91 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.300560E+12 | 193437.48 | 12-JAN-20:10 | 0.524112E+12 | 435795.38 | 03-JAN-17:49 |
February | 0.269120E+12 | 193189.64 | 23-FEB-20:10 | 0.476846E+12 | 428050.41 | 16-FEB-18:00 |
March | 0.294170E+12 | 192869.84 | 02-MAR-20:00 | 0.515007E+12 | 417974.95 | 15-MAR-18:10 |
April | 0.297370E+12 | 245191.02 | 30-APR-18:10 | 0.436269E+12 | 362897.10 | 11-APR-21:10 |
May | 0.306596E+12 | 222458.67 | 22-MAY-19:49 | 0.428945E+12 | 336138.42 | 03-MAY-17:19 |
June | 0.316720E+12 | 269330.77 | 12-JUN-18:10 | 0.377501E+12 | 329749.26 | 05-JUN-17:00 |
July | 0.344562E+12 | 272893.55 | 22-JUL-18:19 | 0.382020E+12 | 314474.94 | 03-JUL-17:10 |
August | 0.352647E+12 | 262078.73 | 14-AUG-18:10 | 0.378642E+12 | 313982.90 | 08-AUG-17:00 |
September | 0.322239E+12 | 228808.09 | 11-SEP-19:10 | 0.376147E+12 | 314597.66 | 08-SEP-17:49 |
October | 0.299967E+12 | 195725.12 | 02-OCT-19:10 | 0.439759E+12 | 336073.71 | 30-OCT-19:19 |
November | 0.286434E+12 | 192811.61 | 27-NOV-20:10 | 0.482761E+12 | 434832.40 | 27-NOV-19:10 |
December | 0.298753E+12 | 193076.63 | 18-DEC-20:10 | 0.558943E+12 | 442499.49 | 27-DEC-19:10 |
Annual Sum or Average | 0.368914E+13 | 0.537695E+13 | ||||
Minimum of Months | 0.269120E+12 | 192811.61 | 0.376147E+12 | 313982.90 | ||
Maximum of Months | 0.352647E+12 | 272893.55 | 0.558943E+12 | 442499.49 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.401829E+10 | 11187.55 | 11-JAN-12:30 | 0.00 | 0.00 |
February | 0.624620E+10 | 18552.39 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.820078E+10 | 22626.96 | 28-MAR-11:30 | 0.00 | 0.00 |
April | 0.183493E+11 | 29160.02 | 26-APR-12:30 | 0.00 | 0.00 |
May | 0.222777E+11 | 32155.12 | 19-MAY-12:09 | 0.00 | 0.00 |
June | 0.227403E+11 | 32579.09 | 18-JUN-12:30 | 0.00 | 0.00 |
July | 0.235676E+11 | 31702.86 | 01-JUL-11:00 | 0.00 | 0.00 |
August | 0.202633E+11 | 28665.48 | 05-AUG-12:30 | 0.00 | 0.00 |
September | 0.149826E+11 | 24629.34 | 09-SEP-12:09 | 0.00 | 0.00 |
October | 0.809338E+10 | 20152.39 | 03-OCT-12:09 | 0.00 | 0.00 |
November | 0.409935E+10 | 13720.16 | 03-NOV-12:20 | 0.00 | 0.00 |
December | 0.275156E+10 | 10656.13 | 03-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.155590E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.275156E+10 | 10656.13 | 0.00 | 0.00 | |
Maximum of Months | 0.235676E+11 | 32579.09 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.378054E+11 | 0.164082E+11 | 0.140003E+12 | 0.331702E+11 | 0.482746E+11 | 0.364147E+10 | 0.00 | 0.117814E+10 | 0.00 | 0.00 | 0.864396E+10 | 0.770428E+10 | 0.00 |
February | 0.339830E+11 | 0.135022E+11 | 0.126445E+12 | 0.299602E+11 | 0.435274E+11 | 0.324737E+10 | 0.00 | 0.109910E+10 | 0.00 | 0.00 | 0.702376E+10 | 0.696183E+10 | 0.00 |
March | 0.374453E+11 | 0.131404E+11 | 0.140056E+12 | 0.331725E+11 | 0.482051E+11 | 0.335206E+10 | 0.00 | 0.183167E+10 | 0.00 | 0.00 | 0.553328E+10 | 0.770285E+10 | 0.00 |
April | 0.359212E+11 | 0.108890E+11 | 0.135446E+12 | 0.320996E+11 | 0.475245E+11 | 0.550921E+10 | 0.00 | 0.152301E+11 | 0.00 | 0.00 | 0.368110E+10 | 0.746489E+10 | 0.00 |
May | 0.368578E+11 | 0.964852E+10 | 0.140035E+12 | 0.331709E+11 | 0.492234E+11 | 0.592244E+10 | 0.00 | 0.172612E+11 | 0.00 | 0.00 | 0.302947E+10 | 0.770425E+10 | 0.00 |
June | 0.355368E+11 | 0.848265E+10 | 0.135537E+12 | 0.321017E+11 | 0.486075E+11 | 0.665642E+10 | 0.00 | 0.358288E+11 | 0.00 | 0.00 | 0.287059E+10 | 0.745688E+10 | 0.00 |
July | 0.367573E+11 | 0.914312E+10 | 0.139944E+12 | 0.331684E+11 | 0.506963E+11 | 0.747304E+10 | 0.00 | 0.532729E+11 | 0.00 | 0.00 | 0.264658E+10 | 0.771238E+10 | 0.00 |
August | 0.370299E+11 | 0.105387E+11 | 0.140067E+12 | 0.331723E+11 | 0.507016E+11 | 0.773408E+10 | 0.00 | 0.598984E+11 | 0.00 | 0.00 | 0.203603E+10 | 0.770438E+10 | 0.00 |
September | 0.361104E+11 | 0.119228E+11 | 0.135457E+12 | 0.320998E+11 | 0.485221E+11 | 0.686554E+10 | 0.00 | 0.378019E+11 | 0.00 | 0.00 | 0.235595E+10 | 0.746620E+10 | 0.00 |
October | 0.376085E+11 | 0.141971E+11 | 0.139992E+12 | 0.331700E+11 | 0.485519E+11 | 0.434132E+10 | 0.00 | 0.742273E+10 | 0.00 | 0.00 | 0.323377E+10 | 0.770293E+10 | 0.00 |
November | 0.365811E+11 | 0.153802E+11 | 0.135531E+12 | 0.321009E+11 | 0.466378E+11 | 0.302414E+10 | 0.00 | 0.146628E+10 | 0.00 | 0.00 | 0.465192E+10 | 0.744869E+10 | 0.00 |
December | 0.378919E+11 | 0.168504E+11 | 0.139944E+12 | 0.331691E+11 | 0.482966E+11 | 0.314397E+10 | 0.00 | 0.656747E+09 | 0.00 | 0.00 | 0.735899E+10 | 0.771243E+10 | 0.00 |
Annual Sum or Average | 0.439529E+12 | 0.150103E+12 | 0.164846E+13 | 0.390556E+12 | 0.578769E+12 | 0.609111E+11 | 0.00 | 0.232948E+12 | 0.00 | 0.00 | 0.530654E+11 | 0.907420E+11 | 0.00 |
Minimum of Months | 0.339830E+11 | 0.848265E+10 | 0.126445E+12 | 0.299602E+11 | 0.435274E+11 | 0.302414E+10 | 0.00 | 0.656747E+09 | 0.00 | 0.00 | 0.203603E+10 | 0.696183E+10 | 0.00 |
Maximum of Months | 0.378919E+11 | 0.168504E+11 | 0.140067E+12 | 0.331725E+11 | 0.507016E+11 | 0.773408E+10 | 0.00 | 0.598984E+11 | 0.00 | 0.00 | 0.864396E+10 | 0.771243E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.131396E+12 | 0.00 | 0.240798E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.121102E+12 | 0.00 | 0.218539E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.122086E+12 | 0.00 | 0.240897E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.592232E+11 | 0.00 | 0.230090E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.434767E+11 | 0.00 | 0.233489E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.854648E+10 | 0.00 | 0.221841E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.420374E+10 | 0.00 | 0.225996E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.171756E+10 | 0.00 | 0.224886E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.105027E+11 | 0.00 | 0.218673E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.588138E+11 | 0.00 | 0.229042E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.109858E+12 | 0.00 | 0.225812E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.169496E+12 | 0.00 | 0.237627E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.840422E+12 | 0.00 | 0.274769E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.171756E+10 | 0.00 | 0.218539E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.169496E+12 | 0.00 | 0.240897E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36244.21 | 02-JAN-20:10 | 9571.94 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 23857.89 | 02-JAN-07:19 | 26249.95 | 10-JAN-19:10 | 3028.61 | 01-JAN-16:19 | 0.00 | 01-JAN-00:10 |
February | 36244.21 | 01-FEB-20:10 | 9571.94 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 23857.89 | 01-FEB-07:19 | 25023.84 | 14-FEB-19:49 | 3075.78 | 12-FEB-09:09 | 0.00 | 01-FEB-00:10 |
March | 36244.21 | 01-MAR-20:10 | 9571.94 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 23857.89 | 13-MAR-06:19 | 25130.55 | 28-MAR-18:10 | 3086.36 | 12-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 36244.21 | 03-APR-19:10 | 9571.94 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 23857.76 | 10-APR-06:19 | 28132.55 | 28-APR-19:10 | 4088.86 | 30-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 36244.21 | 01-MAY-19:19 | 9571.94 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 23857.39 | 01-MAY-06:19 | 28583.40 | 23-MAY-20:19 | 3787.05 | 21-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 36244.21 | 01-JUN-19:30 | 9571.94 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 23857.11 | 15-JUN-06:19 | 28507.41 | 26-JUN-21:10 | 4056.29 | 25-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 36244.21 | 17-JUL-19:30 | 9571.94 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 23857.15 | 25-JUL-06:19 | 29339.33 | 24-JUL-20:19 | 4008.27 | 22-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 36244.21 | 01-AUG-19:49 | 9571.94 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 23857.69 | 15-AUG-06:19 | 28328.25 | 24-AUG-20:40 | 4062.10 | 14-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 36244.21 | 01-SEP-19:10 | 9571.94 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 23857.89 | 27-SEP-06:19 | 28395.20 | 13-SEP-19:40 | 3912.90 | 27-SEP-16:10 | 0.00 | 01-SEP-00:10 |
October | 36244.21 | 02-OCT-19:10 | 9571.94 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 23857.89 | 02-OCT-06:19 | 26104.95 | 03-OCT-18:10 | 3283.49 | 07-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 36244.21 | 01-NOV-19:10 | 9571.94 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 23857.89 | 01-NOV-06:19 | 25157.51 | 28-NOV-19:40 | 3049.50 | 05-NOV-08:09 | 0.00 | 01-NOV-00:10 |
December | 36244.21 | 01-DEC-20:10 | 9571.94 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 23857.89 | 01-DEC-07:19 | 25750.73 | 29-DEC-19:10 | 2999.35 | 03-DEC-09:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 36244.21 | 9571.94 | 88863.15 | 23857.11 | 25023.84 | 2999.35 | 0.00 | |||||||
Maximum of Months | 36244.21 | 9571.94 | 88863.15 | 23857.89 | 29339.33 | 4088.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 6878.62 | 29-JAN-09:09 | 0.00 | 0.00 | 8265.52 | 01-JAN-00:10 | 4738.63 | 26-JAN-19:10 | 0.00 | 01-JAN-00:10 |
February | 6207.17 | 20-FEB-09:09 | 0.00 | 0.00 | 8265.52 | 02-FEB-06:19 | 4738.76 | 23-FEB-19:10 | 0.00 | 01-FEB-00:10 |
March | 9253.35 | 20-MAR-18:10 | 0.00 | 0.00 | 8265.52 | 02-MAR-06:49 | 4738.35 | 30-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 78368.27 | 30-APR-18:10 | 0.00 | 0.00 | 8265.52 | 01-APR-04:10 | 4738.46 | 27-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 60830.83 | 22-MAY-15:20 | 0.00 | 0.00 | 8265.52 | 03-MAY-04:00 | 4738.16 | 24-MAY-06:19 | 0.00 | 01-MAY-00:10 |
June | 100291.38 | 25-JUN-18:10 | 0.00 | 0.00 | 8265.52 | 12-JUN-12:50 | 4738.55 | 15-JUN-18:40 | 0.00 | 01-JUN-00:10 |
July | 104717.87 | 22-JUL-18:10 | 0.00 | 0.00 | 8265.52 | 06-JUL-16:49 | 4738.70 | 13-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 89433.44 | 14-AUG-18:10 | 0.00 | 0.00 | 8265.52 | 14-AUG-12:30 | 4738.45 | 24-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 65778.12 | 13-SEP-15:39 | 0.00 | 0.00 | 8265.52 | 11-SEP-16:40 | 4738.51 | 21-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 41555.62 | 07-OCT-15:20 | 0.00 | 0.00 | 8265.52 | 04-OCT-05:19 | 4738.41 | 05-OCT-18:10 | 0.00 | 01-OCT-00:10 |
November | 12478.86 | 24-NOV-11:50 | 0.00 | 0.00 | 8265.52 | 03-NOV-05:49 | 4738.30 | 17-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 4660.57 | 25-DEC-09:09 | 0.00 | 0.00 | 8265.52 | 03-DEC-01:30 | 4737.65 | 04-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 4660.57 | 0.00 | 0.00 | 8265.52 | 4737.65 | 0.00 | ||||
Maximum of Months | 104717.87 | 0.00 | 0.00 | 8265.52 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 193437.48 | 12-JAN-20:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 25293.99 | 2467.26 | 0.00 | 703.23 | 0.00 |
February | 193189.64 | 23-FEB-20:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 24762.26 | 2200.87 | 0.00 | 1268.06 | 0.00 |
March | 192869.84 | 02-MAR-20:00 | 36244.21 | 86131.51 | 9571.94 | 19289.69 | 24520.08 | 2264.89 | 0.00 | 1390.81 | 0.00 |
April | 245191.02 | 30-APR-18:10 | 28790.91 | 74342.86 | 0.00 | 19034.30 | 26842.61 | 4088.86 | 0.00 | 78368.27 | 0.00 |
May | 222458.67 | 22-MAY-19:49 | 36244.21 | 86131.51 | 9571.94 | 19289.52 | 25204.35 | 3407.50 | 0.00 | 37009.56 | 0.00 |
June | 269330.77 | 12-JUN-18:10 | 29934.98 | 77265.07 | 0.00 | 19090.65 | 27502.04 | 4013.42 | 0.00 | 96888.81 | 0.00 |
July | 272893.55 | 22-JUL-18:19 | 28764.49 | 74342.86 | 0.00 | 19038.66 | 28396.61 | 4008.04 | 0.00 | 104521.89 | 0.00 |
August | 262078.73 | 14-AUG-18:10 | 30117.33 | 77265.07 | 0.00 | 19090.73 | 27480.06 | 4062.10 | 0.00 | 89433.44 | 0.00 |
September | 228808.09 | 11-SEP-19:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 25071.55 | 3517.70 | 0.00 | 43255.37 | 0.00 |
October | 195725.12 | 02-OCT-19:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 25368.23 | 2645.91 | 0.00 | 9218.63 | 0.00 |
November | 192811.61 | 27-NOV-20:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 24828.68 | 2204.70 | 0.00 | 664.97 | 0.00 |
December | 193076.63 | 18-DEC-20:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 24927.51 | 2252.03 | 0.00 | 671.06 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 192811.61 | 28764.49 | 74342.86 | 0.00 | 19034.30 | 24520.08 | 2200.87 | 0.00 | 664.97 | 0.00 | |
Maximum of Months | 272893.55 | 36244.21 | 86131.51 | 9571.94 | 19289.69 | 28396.61 | 4088.86 | 0.00 | 104521.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 161939.57 | 08-JAN-16:19 | 0.00 | 242702.50 | 27-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 137194.37 | 16-FEB-09:09 | 0.00 | 242986.29 | 10-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 146578.92 | 15-MAR-15:20 | 0.00 | 242834.71 | 01-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 102925.74 | 09-APR-06:49 | 0.00 | 240778.44 | 04-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 99470.19 | 06-MAY-04:10 | 0.00 | 235675.73 | 01-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 58804.40 | 08-JUN-03:00 | 0.00 | 228411.89 | 08-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 43095.58 | 06-JUL-03:00 | 0.00 | 211919.84 | 05-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 30970.23 | 23-AUG-03:00 | 0.00 | 210131.18 | 02-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 68266.06 | 20-SEP-03:00 | 0.00 | 210911.22 | 15-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 101098.45 | 23-OCT-03:00 | 0.00 | 225667.64 | 30-OCT-17:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 148421.29 | 29-NOV-16:19 | 0.00 | 237810.59 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 162316.77 | 28-DEC-16:19 | 0.00 | 240786.31 | 28-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 30970.23 | 0.00 | 210131.18 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 162316.77 | 0.00 | 242986.29 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 21.71 | 0.83 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.06 | 0.67 | 22.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.82 | 2.00 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.86 | 3.17 | 21.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 22.06 | 2.00 | 22.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.79 | 2.33 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.79 | 3.17 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 21.78 | 7.67 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.79 | 3.17 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.93 | 0.33 | 21.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.02 | 0.33 | 22.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.97 | 1.00 | 21.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.27 | 1.17 | 22.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.91 | 1.67 | 21.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 21.99 | 5.17 | 21.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.27 | 1.67 | 22.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.89 | 0.67 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.78 | 3.17 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.89 | 0.83 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.85 | 0.67 | 21.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.83 | 0.67 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.95 | 2.67 | 21.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.93 | 3.67 | 21.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.85 | 0.17 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 21.91 | 8.50 | 21.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.95 | 3.67 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
February | 672.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
March | 744.00 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
April | 720.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
May | 744.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
June | 720.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
July | 744.00 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
August | 744.00 | 22.24 | 0.00 | 22.24 | 0.00 | 22.24 |
September | 720.00 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
October | 744.00 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
November | 720.00 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
December | 744.00 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
Annual Sum or Average | 8760.00 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
Minimum of Months | 672.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
Maximum of Months | 744.00 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.08 | 149.67 | 21.06 | 149.67 | 21.05 |
February | 670.67 | 21.11 | 30.67 | 21.11 | 30.67 | 21.10 |
March | 744.00 | 21.02 | 37.00 | 21.02 | 37.00 | 21.02 |
April | 687.00 | 21.58 | 9.83 | 21.61 | 0.00 | 21.61 |
May | 722.00 | 21.59 | 7.50 | 21.61 | 0.00 | 21.61 |
June | 657.67 | 21.92 | 20.83 | 21.98 | 0.00 | 21.98 |
July | 608.33 | 22.16 | 72.67 | 22.34 | 0.00 | 22.34 |
August | 578.17 | 22.35 | 95.83 | 22.57 | 0.00 | 22.57 |
September | 575.50 | 22.04 | 80.17 | 22.28 | 0.00 | 22.28 |
October | 717.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
November | 720.00 | 21.08 | 36.33 | 21.07 | 36.33 | 21.07 |
December | 744.00 | 21.03 | 258.00 | 21.02 | 258.00 | 21.02 |
Annual Sum or Average | 8168.33 | 21.48 | 798.50 | 21.53 | 511.67 | 21.51 |
Minimum of Months | 575.50 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 22.35 | 258.00 | 22.57 | 258.00 | 22.57 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
February | 672.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
March | 744.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
April | 720.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
May | 744.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
June | 718.33 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
July | 738.67 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
August | 744.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
September | 719.50 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
October | 744.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
November | 720.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
December | 744.00 | 21.15 | 0.00 | 21.15 | 0.00 | 21.15 |
Annual Sum or Average | 8752.50 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
Minimum of Months | 672.00 | 21.15 | 0.00 | 21.15 | 0.00 | 21.15 |
Maximum of Months | 744.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.03 | 0.17 | 22.03 | 0.17 | 22.03 |
February | 672.00 | 22.12 | 0.00 | 22.12 | 0.00 | 22.12 |
March | 744.00 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
April | 720.00 | 23.22 | 0.00 | 23.22 | 0.00 | 23.22 |
May | 731.00 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
June | 448.17 | 23.79 | 1.17 | 23.79 | 0.00 | 23.79 |
July | 244.50 | 23.84 | 0.00 | 23.84 | 0.00 | 23.84 |
August | 215.67 | 23.98 | 0.00 | 23.98 | 0.00 | 23.98 |
September | 502.17 | 23.80 | 0.00 | 23.80 | 0.00 | 23.80 |
October | 744.00 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
November | 720.00 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
December | 744.00 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
Annual Sum or Average | 7229.50 | 22.85 | 1.33 | 22.85 | 0.17 | 22.85 |
Minimum of Months | 215.67 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
Maximum of Months | 744.00 | 23.98 | 1.17 | 23.98 | 0.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 69.67 | 21.00 | 69.67 | 21.00 |
February | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
March | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
April | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
May | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
June | 720.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
July | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
August | 744.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
September | 720.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
October | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
November | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
December | 744.00 | 21.00 | 24.50 | 21.00 | 24.50 | 21.00 |
Annual Sum or Average | 8760.00 | 21.12 | 94.17 | 21.12 | 94.17 | 21.12 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.44 | 69.67 | 21.44 | 69.67 | 21.44 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 185.50 | 24.00 | 744.00 | 24.00 | 185.50 | 24.00 |
February | 173.33 | 24.00 | 672.00 | 24.00 | 173.33 | 24.00 |
March | 197.50 | 24.00 | 744.00 | 24.00 | 197.50 | 24.00 |
April | 219.00 | 24.00 | 720.00 | 24.00 | 219.00 | 24.00 |
May | 266.67 | 24.00 | 744.00 | 24.00 | 266.67 | 24.00 |
June | 330.67 | 24.00 | 720.00 | 24.00 | 330.67 | 24.00 |
July | 354.33 | 24.00 | 744.00 | 24.00 | 354.33 | 24.00 |
August | 365.83 | 24.00 | 744.00 | 24.00 | 365.83 | 24.00 |
September | 311.33 | 24.00 | 720.00 | 24.00 | 311.33 | 24.00 |
October | 259.00 | 24.00 | 744.00 | 24.00 | 259.00 | 24.00 |
November | 206.00 | 24.00 | 720.00 | 24.00 | 206.00 | 24.00 |
December | 171.67 | 24.00 | 744.00 | 24.00 | 171.67 | 24.00 |
Annual Sum or Average | 3040.83 | 24.00 | 8760.00 | 24.00 | 3040.83 | 24.00 |
Minimum of Months | 171.67 | 24.00 | 672.00 | 24.00 | 171.67 | 24.00 |
Maximum of Months | 365.83 | 24.00 | 744.00 | 24.00 | 365.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
February | 672.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
March | 744.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
April | 718.50 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
May | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
June | 719.83 | 21.62 | 4.00 | 21.63 | 4.00 | 21.63 |
July | 738.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
August | 727.83 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
September | 675.33 | 21.80 | 10.33 | 21.81 | 0.00 | 21.81 |
October | 742.33 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
November | 720.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
December | 744.00 | 21.16 | 5.83 | 21.16 | 5.83 | 21.16 |
Annual Sum or Average | 8689.83 | 21.46 | 20.17 | 21.46 | 9.83 | 21.46 |
Minimum of Months | 672.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 21.84 | 10.33 | 21.84 | 5.83 | 21.84 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
February | 672.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
March | 744.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
April | 720.00 | 22.14 | 0.00 | 22.14 | 0.00 | 22.14 |
May | 741.83 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
June | 698.17 | 22.35 | 10.00 | 22.37 | 8.17 | 22.38 |
July | 651.67 | 22.38 | 6.00 | 22.39 | 0.00 | 22.39 |
August | 673.17 | 22.50 | 4.83 | 22.51 | 1.17 | 22.51 |
September | 677.83 | 22.45 | 2.67 | 22.46 | 0.00 | 22.46 |
October | 744.00 | 22.06 | 0.00 | 22.06 | 0.00 | 22.06 |
November | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
December | 744.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
Annual Sum or Average | 8530.67 | 22.05 | 23.50 | 22.06 | 9.33 | 22.06 |
Minimum of Months | 651.67 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
Maximum of Months | 744.00 | 22.50 | 10.00 | 22.51 | 8.17 | 22.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.78 | 328.33 | 20.67 | 328.33 | 20.61 |
February | 672.00 | 20.89 | 189.50 | 20.77 | 189.50 | 20.69 |
March | 744.00 | 20.86 | 196.50 | 20.75 | 196.50 | 20.67 |
April | 719.67 | 21.41 | 5.33 | 21.40 | 5.33 | 21.39 |
May | 743.33 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
June | 713.17 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
July | 731.33 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
August | 737.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
September | 715.67 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
October | 744.00 | 21.14 | 26.83 | 21.10 | 26.83 | 21.06 |
November | 720.00 | 20.85 | 195.83 | 20.73 | 195.83 | 20.65 |
December | 744.00 | 20.64 | 495.17 | 20.55 | 495.17 | 20.51 |
Annual Sum or Average | 8728.17 | 21.20 | 1437.50 | 21.08 | 1437.50 | 20.99 |
Minimum of Months | 672.00 | 20.64 | 0.00 | 20.55 | 0.00 | 20.51 |
Maximum of Months | 744.00 | 21.65 | 495.17 | 21.65 | 495.17 | 21.65 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.63 | 441.83 | 20.52 | 441.83 | 20.47 |
February | 672.00 | 20.71 | 316.17 | 20.58 | 316.17 | 20.51 |
March | 744.00 | 20.78 | 268.00 | 20.65 | 268.00 | 20.57 |
April | 713.67 | 21.27 | 9.00 | 21.26 | 8.33 | 21.24 |
May | 726.17 | 21.35 | 8.33 | 21.39 | 0.00 | 21.39 |
June | 680.83 | 21.59 | 21.67 | 21.69 | 0.00 | 21.69 |
July | 665.17 | 21.73 | 47.33 | 21.93 | 0.00 | 21.93 |
August | 697.83 | 21.84 | 20.67 | 21.92 | 0.00 | 21.92 |
September | 705.33 | 21.56 | 6.50 | 21.59 | 0.00 | 21.59 |
October | 744.00 | 20.98 | 60.50 | 20.91 | 60.50 | 20.84 |
November | 720.00 | 20.71 | 301.00 | 20.58 | 301.00 | 20.50 |
December | 744.00 | 20.54 | 571.00 | 20.47 | 571.00 | 20.44 |
Annual Sum or Average | 8557.00 | 21.13 | 2072.00 | 21.01 | 1966.83 | 20.90 |
Minimum of Months | 665.17 | 20.54 | 6.50 | 20.47 | 0.00 | 20.44 |
Maximum of Months | 744.00 | 21.84 | 571.00 | 21.93 | 571.00 | 21.93 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.03 | 113.67 | 20.97 | 113.67 | 20.92 |
February | 672.00 | 21.06 | 26.50 | 21.04 | 26.50 | 21.02 |
March | 744.00 | 21.17 | 6.00 | 21.16 | 6.00 | 21.15 |
April | 720.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
May | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
June | 720.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
July | 744.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
August | 744.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
September | 720.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
October | 744.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
November | 720.00 | 21.11 | 24.67 | 21.08 | 24.67 | 21.06 |
December | 744.00 | 20.99 | 107.00 | 20.92 | 107.00 | 20.86 |
Annual Sum or Average | 8760.00 | 21.34 | 277.83 | 21.31 | 277.83 | 21.28 |
Minimum of Months | 672.00 | 20.99 | 0.00 | 20.92 | 0.00 | 20.86 |
Maximum of Months | 744.00 | 21.75 | 113.67 | 21.75 | 113.67 | 21.75 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.78 | 321.00 | 20.66 | 321.00 | 20.60 |
February | 672.00 | 20.87 | 192.50 | 20.77 | 192.50 | 20.70 |
March | 744.00 | 20.88 | 178.33 | 20.77 | 178.33 | 20.70 |
April | 720.00 | 21.53 | 3.17 | 21.53 | 3.17 | 21.52 |
May | 744.00 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
June | 720.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
July | 743.67 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
August | 744.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
September | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
October | 744.00 | 21.19 | 21.67 | 21.15 | 21.67 | 21.12 |
November | 720.00 | 20.84 | 197.00 | 20.73 | 197.00 | 20.65 |
December | 744.00 | 20.65 | 468.50 | 20.55 | 468.50 | 20.51 |
Annual Sum or Average | 8759.67 | 21.25 | 1382.17 | 21.13 | 1382.17 | 21.04 |
Minimum of Months | 672.00 | 20.65 | 0.00 | 20.55 | 0.00 | 20.51 |
Maximum of Months | 744.00 | 21.72 | 468.50 | 21.72 | 468.50 | 21.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 438.00 | 20.52 | 438.00 | 20.47 |
February | 672.00 | 20.69 | 346.50 | 20.57 | 346.50 | 20.51 |
March | 744.00 | 20.81 | 244.50 | 20.68 | 244.50 | 20.61 |
April | 718.50 | 21.42 | 7.83 | 21.41 | 7.00 | 21.40 |
May | 742.00 | 21.48 | 0.67 | 21.49 | 0.00 | 21.49 |
June | 706.50 | 21.70 | 4.83 | 21.72 | 0.00 | 21.72 |
July | 727.50 | 21.90 | 9.17 | 21.94 | 0.00 | 21.94 |
August | 735.33 | 21.97 | 2.83 | 21.98 | 0.00 | 21.98 |
September | 718.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
October | 744.00 | 21.02 | 43.17 | 20.96 | 43.17 | 20.91 |
November | 720.00 | 20.71 | 295.67 | 20.57 | 295.67 | 20.49 |
December | 744.00 | 20.56 | 548.00 | 20.47 | 548.00 | 20.44 |
Annual Sum or Average | 8715.83 | 21.22 | 1941.17 | 21.06 | 1922.83 | 20.94 |
Minimum of Months | 672.00 | 20.56 | 0.00 | 20.47 | 0.00 | 20.44 |
Maximum of Months | 744.00 | 21.97 | 548.00 | 21.98 | 548.00 | 21.98 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 26.83 | 21.00 | 26.83 | 21.00 |
February | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
March | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
April | 720.00 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
May | 744.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
June | 720.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
July | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
August | 744.00 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
September | 720.00 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
October | 744.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
November | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
December | 744.00 | 21.00 | 21.83 | 21.00 | 21.83 | 21.00 |
Annual Sum or Average | 8760.00 | 21.31 | 48.67 | 21.31 | 48.67 | 21.30 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.93 | 26.83 | 21.93 | 26.83 | 21.93 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.66 | 502.50 | 20.58 | 502.50 | 20.54 |
February | 672.00 | 20.77 | 373.50 | 20.67 | 373.50 | 20.63 |
March | 744.00 | 20.76 | 413.67 | 20.67 | 413.67 | 20.63 |
April | 713.83 | 21.40 | 28.50 | 21.37 | 28.50 | 21.34 |
May | 733.50 | 21.40 | 1.67 | 21.40 | 1.67 | 21.39 |
June | 695.17 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
July | 698.83 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
August | 704.83 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
September | 698.83 | 21.53 | 0.33 | 21.53 | 0.33 | 21.53 |
October | 744.00 | 21.06 | 68.83 | 20.96 | 68.83 | 20.87 |
November | 720.00 | 20.72 | 363.33 | 20.60 | 363.33 | 20.54 |
December | 744.00 | 20.53 | 675.50 | 20.50 | 675.50 | 20.49 |
Annual Sum or Average | 8613.00 | 21.12 | 2427.83 | 20.97 | 2427.83 | 20.88 |
Minimum of Months | 672.00 | 20.53 | 0.00 | 20.50 | 0.00 | 20.49 |
Maximum of Months | 744.00 | 21.59 | 675.50 | 21.59 | 675.50 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 592.33 | 20.47 | 592.33 | 20.44 |
February | 672.00 | 20.59 | 520.67 | 20.52 | 520.67 | 20.50 |
March | 744.00 | 20.68 | 483.67 | 20.60 | 483.67 | 20.56 |
April | 707.33 | 21.26 | 51.50 | 21.26 | 43.83 | 21.23 |
May | 715.83 | 21.34 | 21.33 | 21.45 | 2.50 | 21.45 |
June | 662.33 | 21.61 | 37.00 | 21.80 | 3.50 | 21.83 |
July | 622.83 | 21.69 | 78.50 | 22.07 | 1.50 | 22.09 |
August | 666.00 | 21.83 | 44.17 | 22.02 | 0.00 | 22.02 |
September | 689.67 | 21.53 | 13.83 | 21.59 | 1.67 | 21.59 |
October | 744.00 | 20.89 | 127.50 | 20.75 | 127.50 | 20.64 |
November | 720.00 | 20.59 | 459.17 | 20.48 | 459.17 | 20.43 |
December | 744.00 | 20.46 | 708.50 | 20.45 | 708.50 | 20.44 |
Annual Sum or Average | 8432.00 | 21.06 | 3138.17 | 20.96 | 2944.83 | 20.85 |
Minimum of Months | 622.83 | 20.46 | 13.83 | 20.45 | 0.00 | 20.43 |
Maximum of Months | 744.00 | 21.83 | 708.50 | 22.07 | 708.50 | 22.09 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.11 | 207.17 | 20.99 | 207.17 | 20.91 |
February | 672.00 | 21.20 | 72.67 | 21.11 | 72.67 | 21.05 |
March | 744.00 | 21.06 | 90.17 | 21.00 | 90.17 | 20.95 |
April | 707.50 | 21.58 | 0.67 | 21.58 | 0.67 | 21.58 |
May | 739.67 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
June | 711.50 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
July | 723.50 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
August | 693.67 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
September | 671.33 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
October | 739.17 | 21.36 | 10.67 | 21.34 | 10.67 | 21.32 |
November | 720.00 | 21.13 | 71.67 | 21.04 | 71.67 | 20.97 |
December | 744.00 | 20.89 | 295.17 | 20.76 | 295.17 | 20.69 |
Annual Sum or Average | 8610.33 | 21.36 | 748.17 | 21.28 | 748.17 | 21.22 |
Minimum of Months | 671.33 | 20.89 | 0.00 | 20.76 | 0.00 | 20.69 |
Maximum of Months | 744.00 | 21.64 | 295.17 | 21.64 | 295.17 | 21.64 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
February | 672.00 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
March | 744.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
April | 703.33 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
May | 689.83 | 22.14 | 10.00 | 22.17 | 0.00 | 22.17 |
June | 529.33 | 22.13 | 56.83 | 22.28 | 8.00 | 22.29 |
July | 489.83 | 22.08 | 99.17 | 22.33 | 0.17 | 22.33 |
August | 502.00 | 22.06 | 61.50 | 22.23 | 1.67 | 22.24 |
September | 616.50 | 22.11 | 21.17 | 22.16 | 0.00 | 22.16 |
October | 731.67 | 21.98 | 0.00 | 21.98 | 0.00 | 21.98 |
November | 715.83 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
December | 744.00 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
Annual Sum or Average | 7882.33 | 21.97 | 248.67 | 22.02 | 9.83 | 22.02 |
Minimum of Months | 489.83 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
Maximum of Months | 744.00 | 22.14 | 99.17 | 22.33 | 8.00 | 22.33 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.17 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
February | 655.83 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
March | 708.17 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
April | 640.33 | 22.34 | 12.00 | 22.37 | 0.00 | 22.37 |
May | 575.00 | 22.30 | 35.67 | 22.39 | 0.00 | 22.39 |
June | 383.67 | 22.20 | 146.67 | 22.58 | 8.00 | 22.60 |
July | 358.67 | 22.17 | 211.50 | 22.68 | 0.00 | 22.68 |
August | 375.83 | 22.11 | 180.17 | 22.58 | 0.83 | 22.58 |
September | 479.67 | 22.17 | 87.33 | 22.40 | 0.00 | 22.40 |
October | 651.67 | 22.20 | 18.00 | 22.24 | 0.00 | 22.24 |
November | 676.83 | 22.13 | 7.00 | 22.15 | 0.00 | 22.15 |
December | 736.67 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
Annual Sum or Average | 6971.50 | 22.17 | 698.33 | 22.30 | 8.83 | 22.30 |
Minimum of Months | 358.67 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
Maximum of Months | 736.67 | 22.34 | 211.50 | 22.68 | 8.00 | 22.68 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 514.17 | 23.99 | 744.00 | 23.99 | 514.17 | 23.99 |
February | 470.17 | 23.99 | 672.00 | 23.99 | 470.17 | 23.99 |
March | 523.67 | 23.99 | 744.00 | 23.99 | 523.67 | 23.99 |
April | 511.67 | 23.99 | 720.00 | 23.99 | 511.67 | 23.99 |
May | 536.83 | 23.99 | 744.00 | 23.99 | 536.83 | 23.99 |
June | 536.50 | 23.99 | 720.00 | 23.99 | 536.50 | 23.99 |
July | 558.17 | 23.99 | 744.00 | 23.99 | 558.17 | 23.99 |
August | 554.50 | 23.99 | 744.00 | 23.99 | 554.50 | 23.99 |
September | 522.83 | 23.99 | 720.00 | 23.99 | 522.83 | 23.99 |
October | 530.17 | 23.99 | 744.00 | 23.99 | 530.17 | 23.99 |
November | 505.33 | 23.99 | 720.00 | 23.99 | 505.33 | 23.99 |
December | 513.33 | 23.99 | 744.00 | 23.99 | 513.33 | 23.99 |
Annual Sum or Average | 6277.33 | 23.99 | 8760.00 | 23.99 | 6277.33 | 23.99 |
Minimum of Months | 470.17 | 23.99 | 672.00 | 23.99 | 470.17 | 23.99 |
Maximum of Months | 558.17 | 23.99 | 744.00 | 23.99 | 558.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 40.33 | 21.04 | 40.33 | 21.04 |
February | 672.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
March | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
April | 700.67 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
May | 701.67 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
June | 550.17 | 23.16 | 39.33 | 23.22 | 0.00 | 23.22 |
July | 380.00 | 23.23 | 107.67 | 23.40 | 0.00 | 23.40 |
August | 425.67 | 23.38 | 40.83 | 23.44 | 0.00 | 23.44 |
September | 646.33 | 23.01 | 7.50 | 23.02 | 0.00 | 23.02 |
October | 744.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
November | 720.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
December | 744.00 | 21.01 | 22.67 | 21.01 | 22.67 | 21.01 |
Annual Sum or Average | 7772.50 | 21.93 | 258.33 | 21.97 | 63.00 | 21.96 |
Minimum of Months | 380.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.38 | 107.67 | 23.44 | 40.33 | 23.44 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.18364 | 36.33741 | -0.1519 | 5.57750 |
February | 672.00000 | 22.00757 | 37.34829 | -0.1909 | 5.85193 |
March | 744.00000 | 21.78323 | 36.98711 | -0.2504 | 6.40761 |
April | 720.00000 | 21.75720 | 37.07554 | -0.2555 | 6.49505 |
May | 744.00000 | 21.75403 | 43.48594 | -1.3541 | 43.15807 |
June | 720.00000 | 21.87052 | 51.81622 | -1.2598 | 38.31917 |
July | 744.00000 | 22.11023 | 53.20262 | -1.1629 | 33.59283 |
August | 744.00000 | 22.23627 | 53.03354 | -1.1182 | 31.47911 |
September | 720.00000 | 22.50887 | 48.51125 | -1.0470 | 28.32198 |
October | 744.00000 | 22.67276 | 42.97101 | 0.01859 | 5.11126 |
November | 720.00000 | 22.72795 | 38.80103 | 0.00507 | 5.11206 |
December | 744.00000 | 22.54200 | 34.54753 | -0.0709 | 5.20098 |
Annual Sum or Average | 8760.00000 | 22.18053 | 42.87505 | -0.5722 | 17.96617 |
Minimum of Months | 672.00000 | 21.75403 | 34.54753 | -1.3541 | 5.11126 |
Maximum of Months | 744.00000 | 22.72795 | 53.20262 | 0.01859 | 43.15807 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.07595 | 37.99017 | -0.4564 | 9.62229 |
February | 672.00000 | 21.11858 | 38.67766 | -0.4260 | 9.12527 |
March | 744.00000 | 21.01773 | 38.10379 | -0.4582 | 9.46123 |
April | 720.00000 | 21.68408 | 37.01064 | -0.2270 | 7.23875 |
May | 744.00000 | 21.64734 | 43.53280 | -1.3222 | 42.49170 |
June | 720.00000 | 22.06023 | 51.15890 | -1.1078 | 32.24137 |
July | 744.00000 | 22.43426 | 52.14962 | -0.9613 | 26.49666 |
August | 744.00000 | 22.65962 | 51.80898 | -0.8797 | 23.01533 |
September | 720.00000 | 22.39757 | 48.64042 | -0.9949 | 28.36598 |
October | 744.00000 | 21.40260 | 45.84397 | -0.2731 | 7.37278 |
November | 720.00000 | 21.07654 | 41.93627 | -0.4193 | 8.89911 |
December | 744.00000 | 21.02902 | 36.87544 | -0.5031 | 10.41726 |
Annual Sum or Average | 8760.00000 | 21.63599 | 43.67345 | -0.6709 | 17.95358 |
Minimum of Months | 672.00000 | 21.01773 | 36.87544 | -1.3222 | 7.23875 |
Maximum of Months | 744.00000 | 22.65962 | 52.14962 | -0.2270 | 42.49170 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.20248 | 38.24490 | -0.3584 | 7.80895 |
February | 672.00000 | 21.23126 | 38.93719 | -0.3436 | 7.56912 |
March | 744.00000 | 21.26805 | 38.07311 | -0.3392 | 7.53935 |
April | 720.00000 | 21.64648 | 37.44412 | -0.2289 | 6.43350 |
May | 744.00000 | 21.71280 | 43.75056 | -1.2915 | 40.20124 |
June | 720.00000 | 21.99867 | 51.67395 | -1.1336 | 32.55149 |
July | 744.00000 | 22.17025 | 53.23458 | -1.0592 | 29.33181 |
August | 744.00000 | 22.24714 | 53.28030 | -1.0311 | 27.82610 |
September | 720.00000 | 22.07338 | 49.84638 | -1.1168 | 31.77228 |
October | 744.00000 | 21.52479 | 45.84109 | -0.2163 | 6.18680 |
November | 720.00000 | 21.28550 | 41.88814 | -0.3113 | 7.18676 |
December | 744.00000 | 21.15319 | 37.11578 | -0.3834 | 8.15453 |
Annual Sum or Average | 8760.00000 | 21.62804 | 44.14128 | -0.6531 | 17.77745 |
Minimum of Months | 672.00000 | 21.15319 | 37.11578 | -1.2915 | 6.18680 |
Maximum of Months | 744.00000 | 22.24714 | 53.28030 | -0.2163 | 40.20124 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99978 | 29.22548 | 0.84917 | 20.93475 |
February | 672.00000 | 23.99977 | 29.85771 | 0.85637 | 21.18279 |
March | 744.00000 | 23.99974 | 29.13132 | 0.86039 | 21.37334 |
April | 720.00000 | 23.99975 | 29.25740 | 0.89001 | 22.48994 |
May | 744.00000 | 23.99976 | 34.82780 | 0.28532 | 8.36439 |
June | 720.00000 | 23.99975 | 42.37814 | 0.36019 | 9.37060 |
July | 744.00000 | 23.99973 | 44.22345 | 0.37981 | 9.62012 |
August | 744.00000 | 23.99975 | 44.37806 | 0.38703 | 9.75975 |
September | 720.00000 | 23.99972 | 40.93184 | 0.34712 | 9.15715 |
October | 744.00000 | 23.99972 | 36.22137 | 0.92385 | 23.73509 |
November | 720.00000 | 23.99976 | 32.43185 | 0.88003 | 22.09184 |
December | 744.00000 | 23.99980 | 28.20110 | 0.83495 | 20.42653 |
Annual Sum or Average | 8760.00000 | 23.99975 | 35.11906 | 0.65325 | 16.51243 |
Minimum of Months | 672.00000 | 23.99972 | 28.20110 | 0.28532 | 8.36439 |
Maximum of Months | 744.00000 | 23.99980 | 44.37806 | 0.92385 | 23.73509 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.20502 | 40.47540 | -0.3218 | 7.38335 |
February | 672.00000 | 21.23831 | 41.15044 | -0.2956 | 7.01908 |
March | 744.00000 | 21.23478 | 40.37569 | -0.3090 | 7.13735 |
April | 720.00000 | 21.52655 | 39.96555 | -0.1668 | 5.94346 |
May | 744.00000 | 21.48723 | 46.54839 | -1.2518 | 38.16361 |
June | 720.00000 | 21.62161 | 55.01591 | -1.1274 | 32.21397 |
July | 744.00000 | 21.73283 | 56.80085 | -1.0588 | 29.25840 |
August | 744.00000 | 21.85290 | 56.71113 | -1.0054 | 26.90674 |
September | 720.00000 | 21.84524 | 52.74309 | -1.0394 | 28.69288 |
October | 744.00000 | 21.45284 | 48.26854 | -0.1652 | 5.88111 |
November | 720.00000 | 21.26464 | 44.17428 | -0.2750 | 6.82660 |
December | 744.00000 | 21.16122 | 39.31138 | -0.3641 | 7.92583 |
Annual Sum or Average | 8760.00000 | 21.46944 | 46.82852 | -0.6172 | 17.01148 |
Minimum of Months | 672.00000 | 21.16122 | 39.31138 | -1.2518 | 5.88111 |
Maximum of Months | 744.00000 | 21.85290 | 56.80085 | -0.1652 | 38.16361 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70455 | 40.01042 | -0.2059 | 6.28307 |
February | 672.00000 | 21.74127 | 40.65960 | -0.1892 | 6.09763 |
March | 744.00000 | 21.76586 | 39.86927 | -0.1872 | 6.15774 |
April | 720.00000 | 22.14183 | 39.28632 | -0.0764 | 5.56988 |
May | 744.00000 | 22.17061 | 45.49896 | -1.0971 | 31.04715 |
June | 720.00000 | 22.38535 | 53.41035 | -0.9609 | 25.23805 |
July | 744.00000 | 22.50758 | 55.07791 | -0.9009 | 22.92318 |
August | 744.00000 | 22.58979 | 55.10248 | -0.8699 | 21.58252 |
September | 720.00000 | 22.51114 | 51.48896 | -0.9246 | 23.70903 |
October | 744.00000 | 22.06191 | 47.32732 | -0.0538 | 5.47182 |
November | 720.00000 | 21.82054 | 43.50055 | -0.1501 | 5.91714 |
December | 744.00000 | 21.63836 | 38.91404 | -0.2353 | 6.52407 |
Annual Sum or Average | 8760.00000 | 22.08800 | 45.87635 | -0.4896 | 13.92721 |
Minimum of Months | 672.00000 | 21.63836 | 38.91404 | -1.0971 | 5.47182 |
Maximum of Months | 744.00000 | 22.58979 | 55.10248 | -0.0538 | 31.04715 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.77992 | 45.06062 | -0.5414 | 11.48595 |
February | 672.00000 | 20.89104 | 45.81837 | -0.4984 | 10.44975 |
March | 744.00000 | 20.85924 | 45.62042 | -0.5041 | 10.48465 |
April | 720.00000 | 21.40771 | 44.28046 | -0.3075 | 7.59033 |
May | 744.00000 | 21.41739 | 49.59921 | -1.4308 | 47.67577 |
June | 720.00000 | 21.58213 | 54.31144 | -1.3007 | 41.10689 |
July | 744.00000 | 21.63921 | 54.57086 | -1.2581 | 39.13385 |
August | 744.00000 | 21.66988 | 54.88583 | -1.2469 | 38.61600 |
September | 720.00000 | 21.59265 | 53.52025 | -1.3157 | 41.96961 |
October | 744.00000 | 21.14272 | 52.68148 | -0.3624 | 8.11289 |
November | 720.00000 | 20.84577 | 49.32134 | -0.4932 | 10.33813 |
December | 744.00000 | 20.63515 | 44.94665 | -0.5956 | 12.78975 |
Annual Sum or Average | 8760.00000 | 21.20615 | 49.57325 | -0.8235 | 23.39728 |
Minimum of Months | 672.00000 | 20.63515 | 44.28046 | -1.4308 | 7.59033 |
Maximum of Months | 744.00000 | 21.66988 | 54.88583 | -0.3075 | 47.67577 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63295 | 45.44707 | -0.5887 | 12.68257 |
February | 672.00000 | 20.71123 | 46.28173 | -0.5544 | 11.67331 |
March | 744.00000 | 20.78486 | 45.80545 | -0.5278 | 11.02714 |
April | 720.00000 | 21.29583 | 44.58172 | -0.3526 | 8.18024 |
May | 744.00000 | 21.42117 | 49.72353 | -1.4469 | 48.79148 |
June | 720.00000 | 21.74455 | 54.21381 | -1.2639 | 39.93986 |
July | 744.00000 | 22.01196 | 54.22804 | -1.1637 | 35.77350 |
August | 744.00000 | 21.98588 | 55.19174 | -1.1772 | 35.75861 |
September | 720.00000 | 21.61783 | 54.56655 | -1.3425 | 43.42563 |
October | 744.00000 | 20.98348 | 53.18899 | -0.4150 | 8.79193 |
November | 720.00000 | 20.71337 | 49.68401 | -0.5343 | 11.26704 |
December | 744.00000 | 20.53991 | 45.19870 | -0.6255 | 13.64569 |
Annual Sum or Average | 8760.00000 | 21.20611 | 49.86181 | -0.8346 | 23.48448 |
Minimum of Months | 672.00000 | 20.53991 | 44.58172 | -1.4469 | 8.18024 |
Maximum of Months | 744.00000 | 22.01196 | 55.19174 | -0.3526 | 48.79148 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02848 | 43.58059 | -0.4537 | 9.46830 |
February | 672.00000 | 21.05972 | 44.56686 | -0.4379 | 9.05773 |
March | 744.00000 | 21.16560 | 43.83476 | -0.4010 | 8.41883 |
April | 720.00000 | 21.36990 | 43.19441 | -0.3361 | 7.52521 |
May | 744.00000 | 21.43277 | 47.99943 | -1.4558 | 48.62875 |
June | 720.00000 | 21.60739 | 52.02331 | -1.3517 | 43.32578 |
July | 744.00000 | 21.75439 | 52.88002 | -1.2924 | 40.39224 |
August | 744.00000 | 21.73247 | 53.23628 | -1.3035 | 40.81672 |
September | 720.00000 | 21.50940 | 52.13540 | -1.4022 | 45.83320 |
October | 744.00000 | 21.24940 | 50.76116 | -0.3306 | 7.33707 |
November | 720.00000 | 21.10611 | 47.51161 | -0.4018 | 8.46401 |
December | 744.00000 | 20.98972 | 43.22273 | -0.4706 | 9.72436 |
Annual Sum or Average | 8760.00000 | 21.33533 | 47.93090 | -0.8053 | 23.33270 |
Minimum of Months | 672.00000 | 20.98972 | 43.19441 | -1.4558 | 7.33707 |
Maximum of Months | 744.00000 | 21.75439 | 53.23628 | -0.3306 | 48.62875 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.77962 | 45.05096 | -0.5406 | 11.47357 |
February | 672.00000 | 20.87489 | 45.85048 | -0.5048 | 10.53311 |
March | 744.00000 | 20.88049 | 45.55095 | -0.4998 | 10.39444 |
April | 720.00000 | 21.53490 | 43.92846 | -0.2717 | 7.27014 |
May | 744.00000 | 21.52585 | 49.01322 | -1.3968 | 45.98539 |
June | 720.00000 | 21.63969 | 53.86648 | -1.2899 | 40.64926 |
July | 744.00000 | 21.70578 | 54.07848 | -1.2433 | 38.46463 |
August | 744.00000 | 21.72128 | 54.00737 | -1.2288 | 37.84182 |
September | 720.00000 | 21.68877 | 52.53004 | -1.2782 | 40.22621 |
October | 744.00000 | 21.19156 | 52.47219 | -0.3503 | 8.00471 |
November | 720.00000 | 20.84356 | 49.32237 | -0.4932 | 10.32461 |
December | 744.00000 | 20.64943 | 44.89536 | -0.5894 | 12.63967 |
Annual Sum or Average | 8760.00000 | 21.25419 | 49.23386 | -0.8094 | 22.89853 |
Minimum of Months | 672.00000 | 20.64943 | 43.92846 | -1.3968 | 7.27014 |
Maximum of Months | 744.00000 | 21.72128 | 54.07848 | -0.2717 | 45.98539 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63603 | 45.43169 | -0.5875 | 12.65344 |
February | 672.00000 | 20.69371 | 46.32266 | -0.5612 | 11.85208 |
March | 744.00000 | 20.80663 | 45.73584 | -0.5234 | 10.91775 |
April | 720.00000 | 21.42592 | 44.19981 | -0.3161 | 7.65594 |
May | 744.00000 | 21.49168 | 49.29972 | -1.4233 | 47.27557 |
June | 720.00000 | 21.74918 | 54.03446 | -1.2683 | 39.75024 |
July | 744.00000 | 21.96047 | 54.31404 | -1.1822 | 35.77681 |
August | 744.00000 | 21.99897 | 54.55481 | -1.1703 | 35.02758 |
September | 720.00000 | 21.70759 | 53.60548 | -1.3074 | 41.44090 |
October | 744.00000 | 21.02322 | 53.04573 | -0.4042 | 8.60124 |
November | 720.00000 | 20.70993 | 49.69126 | -0.5346 | 11.27703 |
December | 744.00000 | 20.55524 | 45.14491 | -0.6191 | 13.47830 |
Annual Sum or Average | 8760.00000 | 21.23244 | 49.63368 | -0.8266 | 23.04447 |
Minimum of Months | 672.00000 | 20.55524 | 44.19981 | -1.4233 | 7.65594 |
Maximum of Months | 744.00000 | 21.99897 | 54.55481 | -0.3161 | 47.27557 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.65566 | 46.24166 | -0.5998 | 13.01490 |
February | 672.00000 | 20.77127 | 46.99124 | -0.5519 | 11.73509 |
March | 744.00000 | 20.75697 | 46.76152 | -0.5500 | 11.59219 |
April | 720.00000 | 21.41367 | 44.94938 | -0.3117 | 7.90246 |
May | 744.00000 | 21.42531 | 50.34325 | -1.4340 | 48.05422 |
June | 720.00000 | 21.60448 | 54.94866 | -1.2885 | 40.78134 |
July | 744.00000 | 21.65977 | 55.23124 | -1.2428 | 38.66689 |
August | 744.00000 | 21.67783 | 55.67754 | -1.2394 | 38.53101 |
September | 720.00000 | 21.58608 | 54.55520 | -1.3250 | 42.66309 |
October | 744.00000 | 21.06050 | 54.12563 | -0.3980 | 8.82178 |
November | 720.00000 | 20.72008 | 50.72119 | -0.5465 | 11.61938 |
December | 744.00000 | 20.52831 | 46.03097 | -0.6526 | 14.40203 |
Annual Sum or Average | 8760.00000 | 21.15622 | 50.56919 | -0.8472 | 24.06341 |
Minimum of Months | 672.00000 | 20.52831 | 44.94938 | -1.4340 | 7.90246 |
Maximum of Months | 744.00000 | 21.67783 | 55.67754 | -0.3117 | 48.05422 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53004 | 46.60669 | -0.6441 | 14.22313 |
February | 672.00000 | 20.58612 | 47.50027 | -0.6101 | 13.15419 |
March | 744.00000 | 20.67756 | 46.97052 | -0.5752 | 12.22359 |
April | 720.00000 | 21.32315 | 45.22217 | -0.3541 | 8.52120 |
May | 744.00000 | 21.47275 | 50.39179 | -1.4376 | 48.90982 |
June | 720.00000 | 21.83932 | 54.57280 | -1.2289 | 39.12733 |
July | 744.00000 | 22.15397 | 54.30380 | -1.1097 | 34.58512 |
August | 744.00000 | 22.09469 | 55.52995 | -1.1373 | 34.72607 |
September | 720.00000 | 21.64858 | 55.48818 | -1.3426 | 43.83321 |
October | 744.00000 | 20.89097 | 54.69528 | -0.4543 | 9.61766 |
November | 720.00000 | 20.58753 | 51.11560 | -0.5883 | 12.67791 |
December | 744.00000 | 20.46151 | 46.22421 | -0.6778 | 15.18540 |
Annual Sum or Average | 8760.00000 | 21.19204 | 50.73523 | -0.8483 | 23.96356 |
Minimum of Months | 672.00000 | 20.46151 | 45.22217 | -1.4376 | 8.52120 |
Maximum of Months | 744.00000 | 22.15397 | 55.52995 | -0.3541 | 48.90982 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.10513 | 45.32152 | -0.4445 | 9.84717 |
February | 672.00000 | 21.19517 | 46.08694 | -0.4069 | 9.06108 |
March | 744.00000 | 21.06237 | 45.94906 | -0.4502 | 9.45433 |
April | 720.00000 | 21.61223 | 44.66068 | -0.2433 | 7.21328 |
May | 744.00000 | 21.56247 | 49.65293 | -1.3890 | 45.78131 |
June | 720.00000 | 21.65074 | 54.04980 | -1.2984 | 41.22180 |
July | 744.00000 | 21.69145 | 54.31238 | -1.2587 | 39.38288 |
August | 744.00000 | 21.70149 | 53.88237 | -1.2398 | 38.58974 |
September | 720.00000 | 21.70131 | 52.00846 | -1.2617 | 39.75880 |
October | 744.00000 | 21.37433 | 52.35796 | -0.2888 | 7.47488 |
November | 720.00000 | 21.13011 | 49.39834 | -0.4092 | 8.99994 |
December | 744.00000 | 20.89041 | 45.29647 | -0.5237 | 11.23896 |
Annual Sum or Average | 8760.00000 | 21.38990 | 49.43536 | -0.7704 | 22.42294 |
Minimum of Months | 672.00000 | 20.89041 | 44.66068 | -1.3890 | 7.21328 |
Maximum of Months | 744.00000 | 21.70149 | 54.31238 | -0.2433 | 45.78131 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.79050 | 39.64739 | -0.1389 | 5.92805 |
February | 672.00000 | 21.80788 | 40.31604 | -0.1248 | 5.79664 |
March | 744.00000 | 21.90062 | 39.39000 | -0.0954 | 5.70310 |
April | 720.00000 | 22.13611 | 39.06269 | -0.0060 | 5.51425 |
May | 744.00000 | 22.23919 | 45.10961 | -0.9608 | 25.36798 |
June | 720.00000 | 22.43876 | 53.01548 | -0.8141 | 19.85112 |
July | 744.00000 | 22.49191 | 54.87004 | -0.7744 | 18.51134 |
August | 744.00000 | 22.46034 | 55.19466 | -0.7887 | 18.93382 |
September | 720.00000 | 22.28389 | 51.79845 | -0.8953 | 22.81064 |
October | 744.00000 | 21.99981 | 47.19349 | -0.0089 | 5.52182 |
November | 720.00000 | 21.86764 | 43.16420 | -0.0871 | 5.74503 |
December | 744.00000 | 21.77860 | 38.45270 | -0.1531 | 5.98698 |
Annual Sum or Average | 8760.00000 | 22.10110 | 45.63197 | -0.4057 | 12.17666 |
Minimum of Months | 672.00000 | 21.77860 | 38.45270 | -0.9608 | 5.51425 |
Maximum of Months | 744.00000 | 22.49191 | 55.19466 | -0.0060 | 25.36798 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.11122 | 39.08338 | -0.0288 | 5.64266 |
February | 672.00000 | 22.14549 | 39.71624 | -0.0114 | 5.53901 |
March | 744.00000 | 22.26923 | 38.75144 | 0.02474 | 5.56586 |
April | 720.00000 | 22.47548 | 38.47964 | 0.09948 | 5.69025 |
May | 744.00000 | 22.55579 | 44.44607 | -0.8226 | 20.15001 |
June | 720.00000 | 22.71541 | 52.29117 | -0.6934 | 15.94268 |
July | 744.00000 | 22.75112 | 54.15213 | -0.6611 | 14.98841 |
August | 744.00000 | 22.71333 | 54.48705 | -0.6781 | 15.45557 |
September | 720.00000 | 22.56999 | 51.07880 | -0.7707 | 18.40864 |
October | 744.00000 | 22.35074 | 46.41333 | 0.10265 | 5.74795 |
November | 720.00000 | 22.21140 | 42.49178 | 0.02759 | 5.67220 |
December | 744.00000 | 22.08652 | 37.93864 | -0.0452 | 5.64730 |
Annual Sum or Average | 8760.00000 | 22.41430 | 44.97460 | -0.2898 | 10.39900 |
Minimum of Months | 672.00000 | 22.08652 | 37.93864 | -0.8226 | 5.53901 |
Maximum of Months | 744.00000 | 22.75112 | 54.48705 | 0.10265 | 20.15001 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99108 | 36.95308 | 1.04400 | 29.25956 |
February | 672.00000 | 23.99108 | 37.47684 | 1.05430 | 29.71327 |
March | 744.00000 | 23.99096 | 36.70038 | 1.06160 | 30.04314 |
April | 720.00000 | 23.99094 | 36.66558 | 1.11256 | 32.49826 |
May | 744.00000 | 23.99110 | 42.07561 | 0.58420 | 15.57036 |
June | 720.00000 | 23.99134 | 49.35841 | 0.66683 | 17.79057 |
July | 744.00000 | 23.99146 | 51.15865 | 0.69315 | 18.57266 |
August | 744.00000 | 23.99143 | 51.30237 | 0.69251 | 18.59091 |
September | 720.00000 | 23.99131 | 47.97082 | 0.64208 | 17.15306 |
October | 744.00000 | 23.99115 | 43.48567 | 1.12782 | 33.03819 |
November | 720.00000 | 23.99116 | 40.00621 | 1.07525 | 30.62278 |
December | 744.00000 | 23.99102 | 35.97957 | 1.02713 | 28.49339 |
Annual Sum or Average | 8760.00000 | 23.99117 | 42.45671 | 0.89744 | 25.08089 |
Minimum of Months | 672.00000 | 23.99094 | 35.97957 | 0.58420 | 15.57036 |
Maximum of Months | 744.00000 | 23.99146 | 51.30237 | 1.12782 | 33.03819 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00009 | 35.51429 | -0.4626 | 9.51442 |
February | 672.00000 | 21.00011 | 36.27678 | -0.4549 | 9.33574 |
March | 744.00000 | 21.00010 | 35.49191 | -0.4497 | 9.24885 |
April | 720.00000 | 21.02516 | 35.56419 | -0.4193 | 8.73432 |
May | 744.00000 | 21.05276 | 42.20185 | -1.5588 | 54.10540 |
June | 720.00000 | 21.26062 | 50.66376 | -1.4212 | 46.70396 |
July | 744.00000 | 21.43098 | 52.32004 | -1.3501 | 42.97946 |
August | 744.00000 | 21.44212 | 52.51589 | -1.3455 | 42.66619 |
September | 720.00000 | 21.21405 | 49.09753 | -1.4470 | 48.09673 |
October | 744.00000 | 21.00505 | 44.00754 | -0.3790 | 8.02325 |
November | 720.00000 | 21.00011 | 39.42696 | -0.4254 | 8.82144 |
December | 744.00000 | 21.00010 | 34.31811 | -0.4736 | 9.70521 |
Annual Sum or Average | 8760.00000 | 21.12019 | 42.31721 | -0.8513 | 24.91951 |
Minimum of Months | 672.00000 | 21.00009 | 34.31811 | -1.5588 | 8.02325 |
Maximum of Months | 744.00000 | 21.44212 | 52.51589 | -0.3790 | 54.10540 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00158 | 39.70243 | -0.4522 | 9.30378 |
February | 672.00000 | 21.00122 | 40.44907 | -0.4441 | 9.13101 |
March | 744.00000 | 21.00335 | 39.66854 | -0.4464 | 9.18529 |
April | 720.00000 | 21.18877 | 39.36585 | -0.3863 | 8.23326 |
May | 744.00000 | 21.29037 | 45.78393 | -1.5041 | 51.16100 |
June | 720.00000 | 21.61806 | 53.79777 | -1.3397 | 42.43581 |
July | 744.00000 | 21.84200 | 55.28389 | -1.2516 | 38.01159 |
August | 744.00000 | 21.92729 | 55.28161 | -1.2222 | 36.39014 |
September | 720.00000 | 21.66913 | 52.02635 | -1.3315 | 42.01686 |
October | 744.00000 | 21.12519 | 47.85034 | -0.3588 | 7.73601 |
November | 720.00000 | 21.00307 | 43.57150 | -0.4256 | 8.81822 |
December | 744.00000 | 21.00044 | 38.48213 | -0.4672 | 9.57691 |
Annual Sum or Average | 8760.00000 | 21.30768 | 45.97002 | -0.8047 | 22.74822 |
Minimum of Months | 672.00000 | 21.00044 | 38.48213 | -1.5041 | 7.73601 |
Maximum of Months | 744.00000 | 21.92729 | 55.28389 | -0.3588 | 51.16100 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04509 | 39.34213 | -0.4399 | 9.11314 |
February | 672.00000 | 21.06377 | 40.06548 | -0.4233 | 8.77613 |
March | 744.00000 | 21.14151 | 39.16684 | -0.4029 | 8.45994 |
April | 720.00000 | 22.33914 | 37.06568 | -0.1089 | 5.85452 |
May | 744.00000 | 22.68313 | 42.55134 | -1.0329 | 28.33652 |
June | 720.00000 | 23.33332 | 49.08432 | -0.7570 | 17.66365 |
July | 744.00000 | 23.55441 | 50.35539 | -0.6666 | 14.92995 |
August | 744.00000 | 23.59415 | 50.54506 | -0.6550 | 14.29809 |
September | 720.00000 | 23.09106 | 48.22553 | -0.8523 | 20.88976 |
October | 744.00000 | 21.72695 | 46.28669 | -0.2091 | 6.25853 |
November | 720.00000 | 21.11212 | 43.09856 | -0.3910 | 8.28427 |
December | 744.00000 | 21.00537 | 38.21837 | -0.4636 | 9.51115 |
Annual Sum or Average | 8760.00000 | 22.14609 | 43.68903 | -0.5345 | 12.72500 |
Minimum of Months | 672.00000 | 21.00537 | 37.06568 | -1.0329 | 5.85452 |
Maximum of Months | 744.00000 | 23.59415 | 50.54506 | -0.1089 | 28.33652 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.03455 | 39.51054 | -0.2117 | 6.34533 |
February | 672.00000 | 22.12225 | 40.37284 | -0.1858 | 5.86437 |
March | 744.00000 | 22.44362 | 40.19057 | -0.1120 | 5.42942 |
April | 720.00000 | 23.21704 | 39.37818 | 0.06681 | 5.32928 |
May | 744.00000 | 23.44666 | 44.56975 | -0.8390 | 20.16459 |
June | 720.00000 | 23.86763 | 49.26893 | -0.6556 | 14.15705 |
July | 744.00000 | 23.94749 | 49.86569 | -0.6141 | 12.99224 |
August | 744.00000 | 23.99253 | 49.26378 | -0.6041 | 12.67953 |
September | 720.00000 | 23.85685 | 48.52437 | -0.6660 | 14.45144 |
October | 744.00000 | 23.14784 | 47.42408 | 0.10321 | 5.36841 |
November | 720.00000 | 22.53873 | 43.83601 | -0.0653 | 5.33899 |
December | 744.00000 | 21.93455 | 39.27635 | -0.2374 | 6.31532 |
Annual Sum or Average | 8760.00000 | 23.04985 | 44.31175 | -0.3364 | 9.56341 |
Minimum of Months | 672.00000 | 21.93455 | 39.27635 | -0.8390 | 5.32928 |
Maximum of Months | 744.00000 | 23.99253 | 49.86569 | 0.10321 | 20.16459 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.117814E+10 | 13914.33 | 21-JAN-09:02 | 317.06 | 0.367084E+10 | 0.00 | 0.484898E+10 | 1.33 | 3.12 | 02-JAN-04:20 | 0.00 | 0.00 |
February | 0.109910E+10 | 17341.47 | 20-FEB-09:02 | 285.90 | 0.342471E+10 | 0.00 | 0.452381E+10 | 1.33 | 3.12 | 04-FEB-07:50 | 0.00 | 0.00 |
March | 0.183167E+10 | 13970.68 | 20-MAR-18:03 | 290.68 | 0.570735E+10 | 0.00 | 0.753902E+10 | 1.22 | 3.12 | 02-MAR-19:02 | 0.00 | 0.00 |
April | 0.152301E+11 | 82477.89 | 30-APR-18:03 | 591.19 | 0.478119E+11 | 0.00 | 0.630420E+11 | 2.55 | 3.87 | 30-APR-18:03 | 0.00 | 0.00 |
May | 0.172612E+11 | 62186.18 | 22-MAY-15:13 | 653.64 | 0.534607E+11 | 0.00 | 0.707219E+11 | 2.73 | 3.64 | 22-MAY-18:03 | 0.00 | 0.00 |
June | 0.358288E+11 | 103214.40 | 25-JUN-18:03 | 701.58 | 0.113856E+12 | 0.00 | 0.149685E+12 | 3.02 | 4.27 | 25-JUN-18:03 | 0.00 | 0.00 |
July | 0.532729E+11 | 109861.76 | 22-JUL-18:03 | 739.50 | 0.166551E+12 | 0.00 | 0.219824E+12 | 3.06 | 4.03 | 23-JUL-18:03 | 0.00 | 0.00 |
August | 0.598984E+11 | 94745.45 | 14-AUG-18:03 | 744.00 | 0.184499E+12 | 0.00 | 0.244398E+12 | 3.06 | 3.92 | 17-AUG-18:03 | 0.00 | 0.00 |
September | 0.378019E+11 | 66494.80 | 13-SEP-15:25 | 711.25 | 0.118399E+12 | 0.00 | 0.156201E+12 | 3.06 | 3.90 | 10-SEP-18:03 | 0.00 | 0.00 |
October | 0.742273E+10 | 42732.10 | 07-OCT-15:13 | 466.16 | 0.228069E+11 | 0.00 | 0.302296E+11 | 1.94 | 3.32 | 07-OCT-15:13 | 0.00 | 0.00 |
November | 0.146628E+10 | 15511.85 | 11-NOV-09:02 | 260.00 | 0.456538E+10 | 0.00 | 0.603166E+10 | 1.12 | 3.12 | 04-NOV-15:15 | 0.00 | 0.00 |
December | 0.656747E+09 | 14295.38 | 31-DEC-09:01 | 211.94 | 0.204638E+10 | 0.00 | 0.270312E+10 | 0.89 | 3.12 | 01-DEC-07:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.232948E+12 | 5972.91 | 0.726800E+12 | 0.00 | 0.959748E+12 | 2.11 | 0.00 | 0.00 | ||||
Minimum of Months | 0.656747E+09 | 13914.33 | 211.94 | 0.204638E+10 | 0.00 | 0.270312E+10 | 0.89 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.598984E+11 | 109861.76 | 744.00 | 0.184499E+12 | 0.00 | 0.244398E+12 | 3.06 | 4.27 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.115172E+12 | 0.00 | 739.08 | 186171.62 | 08-JAN-16:11 | 0.00 | 41.95 | 59.38 | 0.60 | 0.00 | 0.13 | 0.55 | 08-JAN-16:11 |
February | 0.106594E+12 | 0.00 | 672.00 | 169850.52 | 25-FEB-16:11 | 0.00 | 40.70 | 59.66 | 0.57 | 0.00 | 0.13 | 0.50 | 25-FEB-16:11 |
March | 0.107534E+12 | 0.00 | 741.17 | 175708.95 | 15-MAR-15:11 | 0.00 | 40.42 | 59.65 | 0.50 | 0.00 | 0.12 | 0.52 | 15-MAR-15:11 |
April | 0.523788E+11 | 0.00 | 620.28 | 95974.06 | 01-APR-08:07 | 0.00 | 40.45 | 57.14 | 0.24 | 0.00 | 0.06 | 0.28 | 01-APR-08:07 |
May | 0.385542E+11 | 0.00 | 646.34 | 86881.31 | 06-MAY-04:10 | 0.00 | 37.42 | 56.74 | 0.16 | 0.00 | 0.04 | 0.26 | 06-MAY-04:10 |
June | 0.761961E+10 | 0.00 | 382.96 | 51847.54 | 08-JUN-04:00 | 0.00 | 37.79 | 49.34 | 0.03 | 0.00 | 0.01 | 0.15 | 08-JUN-04:00 |
July | 0.371699E+10 | 0.00 | 244.59 | 38318.42 | 06-JUL-04:00 | 0.00 | 39.16 | 45.81 | 0.02 | 0.00 | 0.00 | 0.11 | 06-JUL-04:00 |
August | 0.153658E+10 | 0.00 | 168.67 | 34191.19 | 30-AUG-08:06 | 0.00 | 38.53 | 43.57 | 0.01 | 0.00 | 0.00 | 0.10 | 30-AUG-08:06 |
September | 0.928815E+10 | 0.00 | 373.79 | 60239.51 | 20-SEP-04:00 | 0.00 | 41.34 | 50.76 | 0.04 | 0.00 | 0.01 | 0.18 | 20-SEP-04:00 |
October | 0.516669E+11 | 0.00 | 722.92 | 109757.12 | 19-OCT-15:13 | 0.00 | 42.30 | 59.34 | 0.25 | 0.00 | 0.06 | 0.33 | 19-OCT-15:13 |
November | 0.965394E+11 | 0.00 | 716.83 | 165117.91 | 29-NOV-16:13 | 0.00 | 40.81 | 59.63 | 0.48 | 0.00 | 0.11 | 0.49 | 29-NOV-16:13 |
December | 0.148763E+12 | 0.00 | 744.00 | 174129.22 | 28-DEC-16:13 | 0.00 | 41.05 | 59.87 | 0.72 | 0.00 | 0.16 | 0.52 | 28-DEC-16:13 |
Annual Sum or Average | 0.739363E+12 | 0.00 | 6772.63 | 0.00 | 40.16 | 55.05 | 0.30 | 0.00 | 0.07 | ||||
Minimum of Months | 0.153658E+10 | 0.00 | 168.67 | 34191.19 | 0.00 | 37.42 | 43.57 | 0.01 | 0.00 | 0.00 | 0.10 | ||
Maximum of Months | 0.148763E+12 | 0.00 | 744.00 | 186171.62 | 0.00 | 42.30 | 59.87 | 0.72 | 0.00 | 0.16 | 0.55 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.175670E+09 | 0.00 | 178.38 | 0.175670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4446.03 | 13-JAN-06:10 | 4446.03 | 13-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.147843E+09 | 0.00 | 135.08 | 0.147843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4475.40 | 24-FEB-06:10 | 4475.40 | 24-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.104172E+09 | 0.00 | 82.26 | 0.104172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6254.01 | 26-MAR-10:35 | 6254.01 | 26-MAR-10:35 | 0.00 | 0.00 | 0.00 |
April | 0.162524E+11 | 0.00 | 95.75 | 0.162365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186952.32 | 30-APR-18:10 | 186952.32 | 30-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.168952E+11 | 0.00 | 94.33 | 0.168952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156471.28 | 22-MAY-15:35 | 156471.28 | 22-MAY-15:35 | 0.00 | 0.00 | 0.00 |
June | 0.535301E+11 | 0.00 | 243.25 | 0.505388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 369371.70 | 25-JUN-18:00 | 206142.36 | 12-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.916536E+11 | 0.00 | 384.17 | 0.898927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 234610.91 | 22-JUL-10:35 | 227493.83 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.108037E+12 | 0.00 | 442.83 | 0.106329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 209569.43 | 14-AUG-18:10 | 209569.43 | 14-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.567209E+11 | 0.00 | 292.83 | 0.560071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191846.07 | 11-SEP-17:10 | 175066.89 | 11-SEP-17:15 | 0.00 | 0.00 | 0.00 |
October | 0.327669E+10 | 0.00 | 46.83 | 0.327669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79748.30 | 07-OCT-15:13 | 79748.30 | 07-OCT-15:13 | 0.00 | 0.00 | 0.00 |
November | 0.162437E+09 | 0.00 | 58.37 | 0.162437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35443.04 | 24-NOV-11:50 | 35443.04 | 24-NOV-11:50 | 0.00 | 0.00 | 0.00 |
December | 0.153516E+09 | 0.00 | 139.74 | 0.153516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4506.94 | 12-DEC-06:10 | 4506.94 | 12-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347109E+12 | 0.00 | 2193.84 | 0.339920E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.104172E+09 | 0.00 | 46.83 | 0.104172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4446.03 | 4446.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108037E+12 | 0.00 | 442.83 | 0.106329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 369371.70 | 227493.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 |
April | 0.799630E+09 | 0.00 | 34.67 | 0.799630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17041.18 | 30-APR-18:01 | 17041.18 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.835620E+09 | 0.00 | 45.17 | 0.835620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16769.99 | 22-MAY-15:12 | 16769.99 | 22-MAY-15:12 | 0.00 | 0.00 | 0.00 |
June | 0.269652E+10 | 0.00 | 121.67 | 0.248173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31376.35 | 25-JUN-18:04 | 17925.20 | 13-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.488968E+10 | 0.00 | 222.00 | 0.470524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20042.47 | 23-JUL-16:00 | 19227.74 | 22-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.564050E+10 | 0.00 | 268.50 | 0.542979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18985.85 | 14-AUG-12:15 | 17963.27 | 14-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.283360E+10 | 0.00 | 142.33 | 0.274466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18738.57 | 13-SEP-15:13 | 16368.18 | 13-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.140689E+09 | 0.00 | 15.00 | 0.140689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8213.74 | 07-OCT-15:11 | 8213.74 | 07-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178362E+11 | 0.00 | 849.33 | 0.171374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.564050E+10 | 0.00 | 268.50 | 0.542979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31376.35 | 19227.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 12484579.56 | 0.00 | 2.39 | 7015578.43 | 0.00 | 0.00 | 0.00 | 0.00 | 8197.29 | 19-JAN-16:11 | 8197.29 | 19-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 40483466.15 | 0.00 | 10.58 | 24207588.94 | 0.00 | 0.00 | 0.00 | 0.00 | 10668.87 | 17-FEB-16:12 | 10668.87 | 17-FEB-16:12 | 0.00 | 0.00 | 0.00 |
March | 31496504.19 | 0.00 | 8.18 | 16734555.17 | 0.00 | 0.00 | 0.00 | 0.00 | 8043.53 | 23-MAR-18:03 | 8043.53 | 23-MAR-18:03 | 0.00 | 0.00 | 0.00 |
April | 0.107671E+10 | 0.00 | 210.95 | 0.673555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11176.95 | 12-APR-15:11 | 11176.95 | 12-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.141709E+10 | 0.00 | 280.71 | 0.798557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10995.91 | 11-MAY-18:01 | 10995.91 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.261921E+10 | 0.00 | 462.91 | 0.133965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11171.90 | 27-JUN-15:11 | 10198.97 | 18-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.362958E+10 | 0.00 | 525.60 | 0.185273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11186.40 | 18-JUL-15:11 | 10265.06 | 09-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.336565E+10 | 0.00 | 581.82 | 0.158941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11344.28 | 09-AUG-15:11 | 10296.72 | 18-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.217471E+10 | 0.00 | 435.60 | 0.104877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11105.19 | 16-SEP-08:62 | 10058.99 | 14-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.339433E+09 | 0.00 | 87.23 | 0.192934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10748.74 | 06-OCT-18:02 | 10748.74 | 06-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 17561448.23 | 0.00 | 3.78 | 8885635.48 | 0.00 | 0.00 | 0.00 | 0.00 | 8546.65 | 10-NOV-16:11 | 8546.65 | 10-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 6231214.78 | 0.00 | 1.52 | 3024596.75 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.91 | 05-DEC-19:04 | 2096.63 | 05-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147307E+11 | 0.00 | 2611.26 | 0.755547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6231214.78 | 0.00 | 1.52 | 3024596.75 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.91 | 2096.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.362958E+10 | 0.00 | 581.82 | 0.185273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11344.28 | 11176.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6936950.71 | 0.00 | 1.61 | 2862805.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3149.70 | 18-JAN-19:04 | 2031.53 | 21-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 10655226.17 | 0.00 | 3.16 | 4968390.84 | 0.00 | 0.00 | 0.00 | 0.00 | 7538.90 | 27-FEB-16:11 | 7538.90 | 27-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 19017624.15 | 0.00 | 5.65 | 8648887.36 | 0.00 | 0.00 | 0.00 | 0.00 | 7163.94 | 23-MAR-18:03 | 7163.94 | 23-MAR-18:03 | 0.00 | 0.00 | 0.00 |
April | 0.547857E+09 | 0.00 | 127.28 | 0.341008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10095.20 | 14-APR-15:11 | 10095.20 | 14-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.866411E+09 | 0.00 | 207.47 | 0.452345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9919.07 | 25-MAY-17:21 | 9919.07 | 25-MAY-17:21 | 0.00 | 0.00 | 0.00 |
June | 0.187921E+10 | 0.00 | 382.79 | 0.919135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11120.37 | 26-JUN-21:01 | 10044.19 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 |
July | 0.223271E+10 | 0.00 | 383.62 | 0.103278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10571.27 | 23-JUL-21:31 | 9889.86 | 14-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.163538E+10 | 0.00 | 395.27 | 0.625259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10504.79 | 11-AUG-19:12 | 9241.41 | 20-AUG-20:11 | 0.00 | 0.00 | 0.00 |
September | 0.794692E+09 | 0.00 | 267.28 | 0.291814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10150.64 | 10-SEP-20:32 | 9410.28 | 14-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 97299989.30 | 0.00 | 28.95 | 51604494.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9419.20 | 06-OCT-18:02 | 9419.20 | 06-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 10727891.39 | 0.00 | 1.98 | 4448203.11 | 0.00 | 0.00 | 0.00 | 0.00 | 4330.27 | 24-NOV-16:14 | 2458.17 | 24-NOV-16:14 | 0.00 | 0.00 | 0.00 |
December | 4427852.70 | 0.00 | 1.49 | 1972170.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2923.48 | 05-DEC-19:04 | 1785.23 | 05-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.810533E+10 | 0.00 | 1806.54 | 0.373684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4427852.70 | 0.00 | 1.49 | 1972170.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2923.48 | 1785.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.223271E+10 | 0.00 | 395.27 | 0.103278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11120.37 | 10095.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 |
April | 0.936060E+10 | 0.00 | 315.45 | 0.691507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25009.44 | 30-APR-13:05 | 20114.28 | 15-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.795991E+10 | 0.00 | 350.53 | 0.389986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18877.27 | 23-MAY-13:15 | 13407.49 | 11-MAY-16:10 | 0.00 | 0.00 | 0.00 |
June | 0.131546E+11 | 0.00 | 494.42 | 0.381744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21366.92 | 13-JUN-13:15 | 10433.24 | 13-JUN-13:15 | 0.00 | 0.00 | 0.00 |
July | 0.190979E+11 | 0.00 | 601.38 | 0.624485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24948.39 | 22-JUL-13:15 | 14679.41 | 22-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.242785E+11 | 0.00 | 655.01 | 0.894841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25778.47 | 19-AUG-13:00 | 15187.09 | 20-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.233518E+11 | 0.00 | 588.49 | 0.101724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31616.88 | 12-SEP-12:30 | 23062.49 | 25-SEP-13:25 | 0.00 | 0.00 | 0.00 |
October | 0.656621E+10 | 0.00 | 192.73 | 0.391058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26304.36 | 07-OCT-13:15 | 26304.36 | 07-OCT-13:15 | 0.00 | 0.00 | 0.00 |
November | 6736107.43 | 0.00 | 1.50 | 6736107.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.14 | 11-NOV-13:30 | 1938.14 | 11-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103776E+12 | 0.00 | 3199.52 | 0.439153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.242785E+11 | 0.00 | 655.01 | 0.101724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31616.88 | 26304.36 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.120189E+10 | 0.00 | 98.99 | 0.437697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51875.79 | 29-JAN-19:02 | 51875.79 | 29-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.101185E+10 | 0.00 | 98.79 | 0.382451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50058.66 | 01-FEB-09:02 | 50058.66 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.350617E+10 | 0.00 | 214.95 | 0.157712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57727.27 | 30-MAR-18:03 | 57727.27 | 30-MAR-18:03 | 0.00 | 0.00 | 0.00 |
April | 0.101060E+11 | 0.00 | 382.22 | 0.577360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59936.87 | 20-APR-18:01 | 59936.87 | 20-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.151123E+11 | 0.00 | 451.66 | 0.831269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59425.47 | 11-MAY-19:32 | 59425.47 | 11-MAY-19:32 | 0.00 | 0.00 | 0.00 |
June | 0.247211E+11 | 0.00 | 438.99 | 0.144697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66991.52 | 26-JUN-21:01 | 59630.55 | 08-JUN-19:12 | 0.00 | 0.00 | 0.00 |
July | 0.259828E+11 | 0.00 | 402.45 | 0.154883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64499.96 | 17-JUL-21:52 | 58010.54 | 10-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.218931E+11 | 0.00 | 363.70 | 0.122612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64707.10 | 16-AUG-21:52 | 57443.90 | 06-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.166722E+11 | 0.00 | 418.24 | 0.841066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63297.59 | 10-SEP-20:32 | 56345.60 | 29-SEP-16:02 | 0.00 | 0.00 | 0.00 |
October | 0.684817E+10 | 0.00 | 335.30 | 0.281351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59290.62 | 09-OCT-08:62 | 58412.34 | 07-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.242346E+10 | 0.00 | 164.97 | 0.858801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56765.32 | 24-NOV-19:02 | 52486.10 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.522130E+09 | 0.00 | 63.38 | 0.204039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48800.04 | 30-DEC-09:01 | 48800.04 | 30-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130001E+12 | 0.00 | 3433.64 | 0.709897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.522130E+09 | 0.00 | 63.38 | 0.204039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48800.04 | 48800.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.259828E+11 | 0.00 | 451.66 | 0.154883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66991.52 | 59936.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 14763974.59 | 0.00 | 6.95 | 5485385.62 | 0.00 | 0.00 | 0.00 | 0.00 | 3231.12 | 18-JAN-19:04 | 2030.43 | 06-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 20930340.47 | 0.00 | 10.85 | 7861060.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6838.53 | 20-FEB-09:02 | 6838.53 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 17024384.79 | 0.00 | 6.06 | 6794042.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2810.29 | 26-MAR-08:62 | 2078.62 | 14-MAR-15:14 | 0.00 | 0.00 | 0.00 |
April | 0.120052E+10 | 0.00 | 269.92 | 0.710663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10133.05 | 14-APR-15:11 | 10133.05 | 14-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.134378E+10 | 0.00 | 297.37 | 0.716633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9788.95 | 11-MAY-18:01 | 9788.95 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.239744E+10 | 0.00 | 452.56 | 0.116958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10231.61 | 26-JUN-18:01 | 9297.94 | 10-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.330832E+10 | 0.00 | 561.71 | 0.162684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10129.55 | 18-JUL-15:11 | 9338.41 | 23-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.351120E+10 | 0.00 | 629.07 | 0.169872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10176.94 | 09-AUG-15:11 | 9323.39 | 15-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.243611E+10 | 0.00 | 485.43 | 0.121805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10161.30 | 16-SEP-08:62 | 9332.80 | 13-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.355224E+09 | 0.00 | 100.96 | 0.188945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9629.93 | 06-OCT-18:02 | 9629.93 | 06-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 19843870.70 | 0.00 | 6.74 | 8278858.14 | 0.00 | 0.00 | 0.00 | 0.00 | 7358.01 | 11-NOV-09:02 | 7358.01 | 11-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 6999510.30 | 0.00 | 1.71 | 3712059.19 | 0.00 | 0.00 | 0.00 | 0.00 | 3378.70 | 05-DEC-19:04 | 2291.31 | 05-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146322E+11 | 0.00 | 2829.33 | 0.736156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6999510.30 | 0.00 | 1.71 | 3712059.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2810.29 | 2030.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.351120E+10 | 0.00 | 629.07 | 0.169872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10231.61 | 10133.05 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7119087.13 | 0.00 | 1.50 | 3671523.36 | 0.00 | 0.00 | 0.00 | 0.00 | 3332.60 | 23-JAN-09:03 | 2069.99 | 23-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 8678951.47 | 0.00 | 1.72 | 4557071.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3170.52 | 27-FEB-16:14 | 2300.13 | 27-FEB-16:14 | 0.00 | 0.00 | 0.00 |
March | 12879459.56 | 0.00 | 4.59 | 6058028.69 | 0.00 | 0.00 | 0.00 | 0.00 | 2991.82 | 19-MAR-15:15 | 1967.58 | 10-MAR-16:14 | 0.00 | 0.00 | 0.00 |
April | 0.633206E+09 | 0.00 | 161.65 | 0.370064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8657.47 | 14-APR-15:11 | 8657.47 | 14-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.875408E+09 | 0.00 | 219.34 | 0.457112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8813.66 | 23-MAY-08:51 | 8813.66 | 23-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.176286E+10 | 0.00 | 367.07 | 0.857554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9820.27 | 26-JUN-21:01 | 8974.32 | 13-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.216297E+10 | 0.00 | 412.20 | 0.104636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9737.27 | 23-JUL-08:51 | 9654.52 | 22-JUL-08:41 | 0.00 | 0.00 | 0.00 |
August | 0.190200E+10 | 0.00 | 439.74 | 0.881274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9475.42 | 17-AUG-08:51 | 9010.63 | 19-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.110218E+10 | 0.00 | 294.87 | 0.521080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9174.43 | 10-SEP-20:32 | 8685.11 | 12-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.112229E+09 | 0.00 | 35.26 | 51172957.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7842.26 | 01-OCT-08:61 | 7842.26 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 9717608.73 | 0.00 | 1.91 | 4507463.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3055.07 | 08-NOV-09:04 | 1856.87 | 20-NOV-19:05 | 0.00 | 0.00 | 0.00 |
December | 4898542.12 | 0.00 | 1.30 | 2408623.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3136.76 | 20-DEC-09:04 | 2127.01 | 20-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.859413E+10 | 0.00 | 1941.14 | 0.420582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4898542.12 | 0.00 | 1.30 | 2408623.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2991.82 | 1856.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.216297E+10 | 0.00 | 439.74 | 0.104636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9820.27 | 9654.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2367838.17 | 0.00 | 1.64 | 1259245.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2158.05 | 19-JAN-16:11 | 2158.05 | 19-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 8329052.62 | 0.00 | 8.45 | 4791107.62 | 0.00 | 0.00 | 0.00 | 0.00 | 2778.19 | 17-FEB-16:12 | 2778.19 | 17-FEB-16:12 | 0.00 | 0.00 | 0.00 |
March | 7510949.28 | 0.00 | 7.46 | 3655635.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2125.36 | 23-MAR-18:03 | 2125.36 | 23-MAR-18:03 | 0.00 | 0.00 | 0.00 |
April | 0.327458E+09 | 0.00 | 200.92 | 0.220046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2942.49 | 12-APR-15:11 | 2942.49 | 12-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.407239E+09 | 0.00 | 252.55 | 0.249540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2942.35 | 11-MAY-18:01 | 2942.35 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.726287E+09 | 0.00 | 408.94 | 0.404405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3065.79 | 27-JUN-08:62 | 2681.53 | 14-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.986897E+09 | 0.00 | 520.34 | 0.542834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3007.45 | 25-JUL-08:62 | 2675.72 | 25-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.871325E+09 | 0.00 | 548.61 | 0.449963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3007.90 | 17-AUG-08:62 | 2706.24 | 18-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.538283E+09 | 0.00 | 360.27 | 0.282875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979.15 | 02-SEP-08:62 | 2685.83 | 18-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 83376375.99 | 0.00 | 64.67 | 51492782.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2846.88 | 10-OCT-15:11 | 2829.06 | 06-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 4046757.37 | 0.00 | 2.94 | 2072215.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2257.50 | 10-NOV-16:11 | 2257.50 | 10-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 601609.88 | 0.00 | 0.32 | 307445.27 | 0.00 | 0.00 | 0.00 | 0.00 | 894.01 | 20-DEC-19:05 | 505.35 | 21-DEC-16:14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396372E+10 | 0.00 | 2377.11 | 0.221324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 601609.88 | 0.00 | 0.32 | 307445.27 | 0.00 | 0.00 | 0.00 | 0.00 | 894.01 | 505.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.986897E+09 | 0.00 | 548.61 | 0.542834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3065.79 | 2942.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1711631.00 | 0.00 | 1.11 | 817489.37 | 0.00 | 0.00 | 0.00 | 0.00 | 841.50 | 25-JAN-16:14 | 552.18 | 25-JAN-16:14 | 0.00 | 0.00 | 0.00 |
February | 3171741.26 | 0.00 | 2.82 | 1812145.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1939.35 | 27-FEB-16:11 | 1908.86 | 27-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 5233336.72 | 0.00 | 5.05 | 2527126.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1809.48 | 23-MAR-18:03 | 1754.16 | 23-MAR-18:03 | 0.00 | 0.00 | 0.00 |
April | 0.171201E+09 | 0.00 | 120.43 | 0.113245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2646.91 | 14-APR-15:11 | 2646.91 | 14-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.255012E+09 | 0.00 | 189.38 | 0.145669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2646.43 | 25-MAY-17:21 | 2646.43 | 25-MAY-17:21 | 0.00 | 0.00 | 0.00 |
June | 0.531198E+09 | 0.00 | 342.29 | 0.284699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3062.92 | 26-JUN-21:01 | 2665.34 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 |
July | 0.631335E+09 | 0.00 | 381.95 | 0.312678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.56 | 24-JUL-20:01 | 2660.01 | 28-JUL-18:11 | 0.00 | 0.00 | 0.00 |
August | 0.416843E+09 | 0.00 | 369.05 | 0.174139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2791.13 | 11-AUG-19:12 | 2514.87 | 04-AUG-20:01 | 0.00 | 0.00 | 0.00 |
September | 0.179834E+09 | 0.00 | 199.33 | 71237261.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2692.01 | 10-SEP-20:32 | 2528.52 | 14-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 23757343.17 | 0.00 | 17.53 | 13087266.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2455.05 | 06-OCT-18:02 | 2455.05 | 06-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 2543147.89 | 0.00 | 1.68 | 1276861.72 | 0.00 | 0.00 | 0.00 | 0.00 | 950.89 | 05-NOV-15:13 | 817.90 | 05-NOV-15:13 | 0.00 | 0.00 | 0.00 |
December | 347522.08 | 0.00 | 0.33 | 156998.43 | 0.00 | 0.00 | 0.00 | 0.00 | 802.32 | 16-DEC-09:05 | 445.16 | 16-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222219E+10 | 0.00 | 1630.95 | 0.112135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 347522.08 | 0.00 | 0.33 | 156998.43 | 0.00 | 0.00 | 0.00 | 0.00 | 802.32 | 445.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.631335E+09 | 0.00 | 381.95 | 0.312678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3062.92 | 2665.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.274572E+09 | 0.00 | 78.64 | 0.115696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16673.45 | 11-JAN-16:12 | 16673.45 | 11-JAN-16:12 | 0.00 | 0.00 | 0.00 |
February | 0.388693E+09 | 0.00 | 85.74 | 0.175731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14354.66 | 27-FEB-16:11 | 14354.66 | 27-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.117225E+09 | 0.00 | 36.93 | 52221664.53 | 0.00 | 0.00 | 0.00 | 0.00 | 14128.72 | 25-MAR-15:12 | 14128.72 | 25-MAR-15:12 | 0.00 | 0.00 | 0.00 |
April | 0.295655E+10 | 0.00 | 378.89 | 0.166643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14599.74 | 23-APR-08:62 | 14599.74 | 23-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.259304E+10 | 0.00 | 384.41 | 0.125746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16760.83 | 11-MAY-18:01 | 16760.83 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.402969E+10 | 0.00 | 520.04 | 0.181145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17724.15 | 26-JUN-18:01 | 15674.70 | 18-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.542355E+10 | 0.00 | 579.31 | 0.249729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16757.24 | 08-JUL-08:62 | 15732.18 | 28-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.613585E+10 | 0.00 | 635.02 | 0.290420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17427.17 | 09-AUG-15:11 | 15629.45 | 01-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.561310E+10 | 0.00 | 568.53 | 0.293937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17035.93 | 16-SEP-15:13 | 15580.36 | 13-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.168805E+10 | 0.00 | 248.57 | 0.863378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16302.19 | 09-OCT-08:62 | 15391.86 | 10-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.244236E+09 | 0.00 | 65.47 | 95460824.87 | 0.00 | 0.00 | 0.00 | 0.00 | 14581.52 | 10-NOV-16:11 | 14581.52 | 10-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 49396800.09 | 0.00 | 13.92 | 23881788.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15878.10 | 26-DEC-16:11 | 15878.10 | 26-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295140E+11 | 0.00 | 3595.47 | 0.144026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 49396800.09 | 0.00 | 13.92 | 23881788.90 | 0.00 | 0.00 | 0.00 | 0.00 | 14128.72 | 14128.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.613585E+10 | 0.00 | 635.02 | 0.293937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17724.15 | 16760.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.21 | 137.34 | 71.87 | 277.00 | 358.34 | 0.00 | 0.00 | 0.00 |
February | 251.00 | 154.37 | 96.63 | 345.72 | 345.89 | 0.00 | 0.00 | 0.00 |
March | 152.46 | 43.89 | 108.57 | 162.90 | 292.23 | 0.00 | 0.00 | 0.00 |
April | 305.93 | 131.59 | 174.34 | 495.36 | 242.63 | 0.00 | 0.00 | 0.00 |
May | 253.31 | 75.88 | 177.43 | 379.91 | 207.80 | 0.00 | 0.00 | 0.00 |
June | 233.74 | 50.07 | 183.68 | 370.74 | 156.56 | 0.00 | 0.00 | 0.00 |
July | 251.00 | 70.65 | 180.35 | 433.38 | 145.25 | 0.00 | 0.00 | 0.00 |
August | 297.20 | 127.91 | 169.29 | 540.10 | 159.84 | 0.00 | 0.00 | 0.00 |
September | 363.67 | 213.05 | 150.62 | 641.56 | 204.07 | 0.00 | 0.00 | 0.00 |
October | 247.06 | 143.20 | 103.86 | 377.32 | 265.14 | 0.00 | 0.00 | 0.00 |
November | 181.10 | 111.69 | 69.41 | 243.96 | 323.18 | 0.00 | 0.00 | 0.00 |
December | 144.57 | 94.14 | 50.42 | 184.87 | 401.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.44 | 112.32 | 128.12 | 370.54 | 258.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.57 | 43.89 | 50.42 | 162.90 | 145.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.67 | 213.05 | 183.68 | 641.56 | 401.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 589.11 | 386.74 | 202.37 | 776.70 | 1007.67 | 0.00 | 0.00 | 0.00 |
February | 706.81 | 434.70 | 272.10 | 970.91 | 972.34 | 0.00 | 0.00 | 0.00 |
March | 429.33 | 123.59 | 305.73 | 451.53 | 823.33 | 0.00 | 0.00 | 0.00 |
April | 861.48 | 370.54 | 490.94 | 1406.89 | 670.25 | 0.00 | 0.00 | 0.00 |
May | 713.30 | 213.66 | 499.63 | 1082.01 | 571.86 | 0.00 | 0.00 | 0.00 |
June | 658.21 | 140.99 | 517.22 | 1069.33 | 418.64 | 0.00 | 0.00 | 0.00 |
July | 706.79 | 198.94 | 507.85 | 1256.45 | 379.28 | 0.00 | 0.00 | 0.00 |
August | 836.90 | 360.20 | 476.71 | 1558.70 | 414.67 | 0.00 | 0.00 | 0.00 |
September | 1024.07 | 599.93 | 424.14 | 1832.24 | 545.95 | 0.00 | 0.00 | 0.00 |
October | 695.71 | 403.25 | 292.46 | 1066.94 | 743.39 | 0.00 | 0.00 | 0.00 |
November | 509.97 | 314.53 | 195.44 | 684.24 | 914.00 | 0.00 | 0.00 | 0.00 |
December | 407.09 | 265.10 | 141.99 | 516.58 | 1132.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 677.06 | 316.29 | 360.77 | 1054.64 | 714.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 407.09 | 123.59 | 141.99 | 451.53 | 379.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1024.07 | 599.93 | 517.22 | 1832.24 | 1132.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 765.28 | 502.40 | 262.89 | 1011.53 | 1397.16 | 0.00 | 0.00 | 0.00 |
February | 918.18 | 564.71 | 353.47 | 1265.39 | 1345.83 | 0.00 | 0.00 | 0.00 |
March | 557.72 | 160.56 | 397.16 | 584.81 | 1154.08 | 0.00 | 0.00 | 0.00 |
April | 1119.11 | 481.35 | 637.76 | 1836.39 | 938.32 | 0.00 | 0.00 | 0.00 |
May | 926.61 | 277.56 | 649.05 | 1405.41 | 811.03 | 0.00 | 0.00 | 0.00 |
June | 855.05 | 183.16 | 671.90 | 1380.65 | 603.92 | 0.00 | 0.00 | 0.00 |
July | 918.16 | 258.43 | 659.73 | 1624.88 | 549.45 | 0.00 | 0.00 | 0.00 |
August | 1087.19 | 467.92 | 619.27 | 2025.99 | 596.13 | 0.00 | 0.00 | 0.00 |
September | 1330.33 | 779.34 | 550.98 | 2389.88 | 770.56 | 0.00 | 0.00 | 0.00 |
October | 903.76 | 523.84 | 379.92 | 1389.73 | 1045.21 | 0.00 | 0.00 | 0.00 |
November | 662.47 | 408.59 | 253.89 | 889.19 | 1276.35 | 0.00 | 0.00 | 0.00 |
December | 528.83 | 344.38 | 184.45 | 671.03 | 1567.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 879.54 | 410.88 | 468.66 | 1371.04 | 1003.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 528.83 | 160.56 | 184.45 | 584.81 | 549.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.33 | 779.34 | 671.90 | 2389.88 | 1567.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.36 | 27.15 | 14.21 | 55.54 | 71.23 | 0.00 | 0.00 | 0.00 |
February | 49.63 | 30.52 | 19.11 | 68.98 | 69.15 | 0.00 | 0.00 | 0.00 |
March | 30.14 | 8.68 | 21.47 | 32.59 | 58.49 | 0.00 | 0.00 | 0.00 |
April | 60.49 | 26.02 | 34.47 | 98.58 | 48.15 | 0.00 | 0.00 | 0.00 |
May | 50.08 | 15.00 | 35.08 | 75.09 | 41.36 | 0.00 | 0.00 | 0.00 |
June | 46.22 | 9.90 | 36.32 | 73.48 | 30.03 | 0.00 | 0.00 | 0.00 |
July | 49.63 | 13.97 | 35.66 | 86.71 | 26.82 | 0.00 | 0.00 | 0.00 |
August | 58.76 | 25.29 | 33.47 | 108.43 | 28.84 | 0.00 | 0.00 | 0.00 |
September | 71.90 | 42.12 | 29.78 | 128.47 | 38.26 | 0.00 | 0.00 | 0.00 |
October | 48.85 | 28.31 | 20.53 | 75.45 | 52.28 | 0.00 | 0.00 | 0.00 |
November | 35.81 | 22.08 | 13.72 | 48.71 | 64.06 | 0.00 | 0.00 | 0.00 |
December | 28.58 | 18.61 | 9.97 | 37.01 | 79.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.54 | 22.21 | 25.33 | 73.98 | 50.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.58 | 8.68 | 9.97 | 32.59 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.90 | 42.12 | 36.32 | 128.47 | 79.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.17 | 8.41 | 17.77 | 19.61 | 145.24 | 0.00 | 0.00 | 0.00 |
February | 46.62 | 19.77 | 26.85 | 47.81 | 137.06 | 0.00 | 0.00 | 0.00 |
March | 42.20 | 8.23 | 33.97 | 31.92 | 110.20 | 0.00 | 0.00 | 0.00 |
April | 99.62 | 39.84 | 59.78 | 141.84 | 87.67 | 0.00 | 0.00 | 0.00 |
May | 116.93 | 47.97 | 68.96 | 165.55 | 72.82 | 0.00 | 0.00 | 0.00 |
June | 126.27 | 52.45 | 73.83 | 198.09 | 53.46 | 0.00 | 0.00 | 0.00 |
July | 128.56 | 57.10 | 71.46 | 212.81 | 47.94 | 0.00 | 0.00 | 0.00 |
August | 108.09 | 47.17 | 60.92 | 180.47 | 52.53 | 0.00 | 0.00 | 0.00 |
September | 87.16 | 39.57 | 47.59 | 137.10 | 71.61 | 0.00 | 0.00 | 0.00 |
October | 46.27 | 16.79 | 29.48 | 54.37 | 100.48 | 0.00 | 0.00 | 0.00 |
November | 24.73 | 7.12 | 17.61 | 19.04 | 127.30 | 0.00 | 0.00 | 0.00 |
December | 13.68 | 2.58 | 11.09 | 5.51 | 160.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.27 | 28.93 | 43.34 | 101.37 | 97.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.68 | 2.58 | 11.09 | 5.51 | 47.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.56 | 57.10 | 73.83 | 212.81 | 160.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.06 | 0.00 | 7.06 | 0.35 | 80.87 | 0.00 | 0.00 | 0.00 |
February | 11.03 | 0.00 | 11.03 | 1.04 | 75.87 | 0.00 | 0.00 | 0.00 |
March | 15.27 | 0.00 | 15.27 | 5.49 | 61.21 | 0.00 | 0.00 | 0.00 |
April | 24.89 | 0.11 | 24.78 | 20.87 | 47.41 | 0.00 | 0.00 | 0.00 |
May | 30.88 | 1.29 | 29.60 | 25.63 | 37.17 | 0.00 | 0.00 | 0.00 |
June | 33.96 | 1.75 | 32.21 | 39.26 | 27.36 | 0.00 | 0.00 | 0.00 |
July | 32.30 | 1.55 | 30.75 | 40.46 | 24.77 | 0.00 | 0.00 | 0.00 |
August | 25.60 | 0.36 | 25.24 | 31.61 | 27.94 | 0.00 | 0.00 | 0.00 |
September | 19.50 | 0.01 | 19.50 | 20.28 | 39.10 | 0.00 | 0.00 | 0.00 |
October | 12.49 | 0.00 | 12.49 | 6.32 | 54.52 | 0.00 | 0.00 | 0.00 |
November | 7.51 | 0.00 | 7.51 | 0.59 | 69.45 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 0.00 | 86.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.83 | 0.42 | 18.41 | 16.07 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 0.00 | 24.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.96 | 1.75 | 32.21 | 40.46 | 86.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.17 | 8.41 | 17.77 | 20.57 | 143.89 | 0.00 | 0.00 | 0.00 |
February | 46.62 | 19.77 | 26.85 | 49.25 | 135.59 | 0.00 | 0.00 | 0.00 |
March | 42.20 | 8.23 | 33.97 | 32.65 | 109.65 | 0.00 | 0.00 | 0.00 |
April | 99.62 | 39.84 | 59.78 | 143.82 | 86.95 | 0.00 | 0.00 | 0.00 |
May | 116.93 | 47.97 | 68.96 | 166.34 | 72.67 | 0.00 | 0.00 | 0.00 |
June | 126.27 | 52.45 | 73.83 | 197.66 | 53.83 | 0.00 | 0.00 | 0.00 |
July | 128.56 | 57.10 | 71.46 | 211.27 | 48.84 | 0.00 | 0.00 | 0.00 |
August | 108.09 | 47.17 | 60.92 | 180.08 | 53.44 | 0.00 | 0.00 | 0.00 |
September | 87.16 | 39.57 | 47.59 | 138.62 | 71.19 | 0.00 | 0.00 | 0.00 |
October | 46.27 | 16.79 | 29.48 | 56.12 | 99.35 | 0.00 | 0.00 | 0.00 |
November | 24.73 | 7.12 | 17.61 | 19.95 | 126.10 | 0.00 | 0.00 | 0.00 |
December | 13.68 | 2.58 | 11.09 | 5.89 | 159.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.27 | 28.93 | 43.34 | 102.03 | 96.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.68 | 2.58 | 11.09 | 5.89 | 48.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.56 | 57.10 | 73.83 | 211.27 | 159.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.08 | 21.72 | 11.37 | 41.33 | 66.78 | 0.00 | 0.00 | 0.00 |
February | 39.69 | 24.41 | 15.28 | 52.01 | 64.36 | 0.00 | 0.00 | 0.00 |
March | 24.11 | 6.94 | 17.17 | 23.76 | 52.43 | 0.00 | 0.00 | 0.00 |
April | 48.38 | 20.81 | 27.57 | 71.23 | 52.00 | 0.00 | 0.00 | 0.00 |
May | 40.06 | 12.00 | 28.06 | 51.68 | 47.57 | 0.00 | 0.00 | 0.00 |
June | 36.97 | 7.92 | 29.05 | 49.55 | 37.01 | 0.00 | 0.00 | 0.00 |
July | 39.69 | 11.17 | 28.52 | 60.04 | 34.04 | 0.00 | 0.00 | 0.00 |
August | 47.00 | 20.23 | 26.77 | 77.98 | 36.47 | 0.00 | 0.00 | 0.00 |
September | 57.51 | 33.69 | 23.82 | 94.31 | 45.36 | 0.00 | 0.00 | 0.00 |
October | 39.07 | 22.65 | 16.42 | 54.38 | 58.22 | 0.00 | 0.00 | 0.00 |
November | 28.64 | 17.66 | 10.98 | 35.60 | 64.50 | 0.00 | 0.00 | 0.00 |
December | 22.86 | 14.89 | 7.97 | 29.50 | 62.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.02 | 17.76 | 20.26 | 53.36 | 51.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.86 | 6.94 | 7.97 | 23.76 | 34.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.51 | 33.69 | 29.05 | 94.31 | 66.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.65 | 0.00 | 5.65 | 0.16 | 67.93 | 0.00 | 0.00 | 0.00 |
February | 8.83 | 0.00 | 8.83 | 0.55 | 63.34 | 0.00 | 0.00 | 0.00 |
March | 12.21 | 0.00 | 12.21 | 3.63 | 51.22 | 0.00 | 0.00 | 0.00 |
April | 19.91 | 0.09 | 19.83 | 16.79 | 38.34 | 0.00 | 0.00 | 0.00 |
May | 24.71 | 1.03 | 23.68 | 20.95 | 29.93 | 0.00 | 0.00 | 0.00 |
June | 27.17 | 1.40 | 25.77 | 32.68 | 21.59 | 0.00 | 0.00 | 0.00 |
July | 25.84 | 1.24 | 24.60 | 34.10 | 19.31 | 0.00 | 0.00 | 0.00 |
August | 20.48 | 0.29 | 20.19 | 26.75 | 21.70 | 0.00 | 0.00 | 0.00 |
September | 15.60 | 0.00 | 15.60 | 16.85 | 30.99 | 0.00 | 0.00 | 0.00 |
October | 9.99 | 0.00 | 9.99 | 4.64 | 45.36 | 0.00 | 0.00 | 0.00 |
November | 6.01 | 0.00 | 6.01 | 0.28 | 58.69 | 0.00 | 0.00 | 0.00 |
December | 4.09 | 0.00 | 4.09 | 0.00 | 73.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.07 | 0.34 | 14.73 | 13.18 | 43.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.09 | 0.00 | 4.09 | 0.00 | 19.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.17 | 1.40 | 25.77 | 34.10 | 73.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.44 | 10.31 | 16.13 | 18.32 | 142.91 | 0.00 | 0.00 | 0.00 |
February | 40.46 | 15.06 | 25.40 | 32.43 | 134.28 | 0.00 | 0.00 | 0.00 |
March | 42.07 | 8.31 | 33.76 | 30.83 | 108.87 | 0.00 | 0.00 | 0.00 |
April | 113.64 | 53.80 | 59.85 | 163.45 | 83.38 | 0.00 | 0.00 | 0.00 |
May | 119.51 | 52.61 | 66.89 | 167.26 | 70.42 | 0.00 | 0.00 | 0.00 |
June | 118.09 | 47.59 | 70.50 | 180.79 | 51.70 | 0.00 | 0.00 | 0.00 |
July | 120.49 | 51.56 | 68.92 | 195.10 | 46.10 | 0.00 | 0.00 | 0.00 |
August | 114.57 | 55.24 | 59.33 | 190.67 | 49.82 | 0.00 | 0.00 | 0.00 |
September | 103.03 | 55.14 | 47.89 | 163.07 | 68.31 | 0.00 | 0.00 | 0.00 |
October | 49.73 | 20.81 | 28.92 | 58.80 | 98.31 | 0.00 | 0.00 | 0.00 |
November | 25.52 | 8.55 | 16.97 | 17.52 | 124.37 | 0.00 | 0.00 | 0.00 |
December | 18.83 | 6.86 | 11.97 | 10.82 | 155.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 74.47 | 32.19 | 42.28 | 102.68 | 94.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.83 | 6.86 | 11.97 | 10.82 | 46.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.49 | 55.24 | 70.50 | 195.10 | 155.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.36 | 27.15 | 14.21 | 55.43 | 71.16 | 0.00 | 0.00 | 0.00 |
February | 49.63 | 30.52 | 19.11 | 68.98 | 68.95 | 0.00 | 0.00 | 0.00 |
March | 30.14 | 8.68 | 21.47 | 32.41 | 58.41 | 0.00 | 0.00 | 0.00 |
April | 60.49 | 26.02 | 34.47 | 97.55 | 48.12 | 0.00 | 0.00 | 0.00 |
May | 50.08 | 15.00 | 35.08 | 74.26 | 41.16 | 0.00 | 0.00 | 0.00 |
June | 46.22 | 9.90 | 36.32 | 73.02 | 29.67 | 0.00 | 0.00 | 0.00 |
July | 49.63 | 13.97 | 35.66 | 86.21 | 26.53 | 0.00 | 0.00 | 0.00 |
August | 58.76 | 25.29 | 33.47 | 107.84 | 28.68 | 0.00 | 0.00 | 0.00 |
September | 71.90 | 42.12 | 29.78 | 127.59 | 38.24 | 0.00 | 0.00 | 0.00 |
October | 48.85 | 28.31 | 20.53 | 75.07 | 52.22 | 0.00 | 0.00 | 0.00 |
November | 35.81 | 22.08 | 13.72 | 48.63 | 63.99 | 0.00 | 0.00 | 0.00 |
December | 28.58 | 18.61 | 9.97 | 36.88 | 79.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.54 | 22.21 | 25.33 | 73.55 | 50.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.58 | 8.68 | 9.97 | 32.41 | 26.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.90 | 42.12 | 36.32 | 127.59 | 79.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.06 | 0.00 | 7.06 | 0.32 | 80.83 | 0.00 | 0.00 | 0.00 |
February | 11.03 | 0.00 | 11.03 | 0.96 | 75.62 | 0.00 | 0.00 | 0.00 |
March | 15.27 | 0.00 | 15.27 | 5.34 | 61.15 | 0.00 | 0.00 | 0.00 |
April | 24.89 | 0.11 | 24.78 | 19.88 | 47.47 | 0.00 | 0.00 | 0.00 |
May | 30.88 | 1.29 | 29.60 | 24.99 | 37.02 | 0.00 | 0.00 | 0.00 |
June | 33.96 | 1.75 | 32.21 | 39.03 | 26.99 | 0.00 | 0.00 | 0.00 |
July | 32.30 | 1.55 | 30.75 | 40.33 | 24.30 | 0.00 | 0.00 | 0.00 |
August | 25.60 | 0.36 | 25.24 | 31.01 | 27.60 | 0.00 | 0.00 | 0.00 |
September | 19.50 | 0.01 | 19.50 | 19.40 | 39.05 | 0.00 | 0.00 | 0.00 |
October | 12.49 | 0.00 | 12.49 | 6.00 | 54.47 | 0.00 | 0.00 | 0.00 |
November | 7.51 | 0.00 | 7.51 | 0.55 | 69.38 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 0.00 | 86.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.83 | 0.42 | 18.41 | 15.73 | 52.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 0.00 | 24.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.96 | 1.75 | 32.21 | 40.33 | 86.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.44 | 10.31 | 16.13 | 18.85 | 141.07 | 0.00 | 0.00 | 0.00 |
February | 40.46 | 15.06 | 25.40 | 33.22 | 132.19 | 0.00 | 0.00 | 0.00 |
March | 42.07 | 8.31 | 33.76 | 31.49 | 108.25 | 0.00 | 0.00 | 0.00 |
April | 113.64 | 53.80 | 59.85 | 165.32 | 82.56 | 0.00 | 0.00 | 0.00 |
May | 119.51 | 52.61 | 66.89 | 168.31 | 70.13 | 0.00 | 0.00 | 0.00 |
June | 118.09 | 47.59 | 70.50 | 180.83 | 51.96 | 0.00 | 0.00 | 0.00 |
July | 120.49 | 51.56 | 68.92 | 194.63 | 46.82 | 0.00 | 0.00 | 0.00 |
August | 114.57 | 55.24 | 59.33 | 190.66 | 50.56 | 0.00 | 0.00 | 0.00 |
September | 103.03 | 55.14 | 47.89 | 164.63 | 67.72 | 0.00 | 0.00 | 0.00 |
October | 49.73 | 20.81 | 28.92 | 60.47 | 97.00 | 0.00 | 0.00 | 0.00 |
November | 25.52 | 8.55 | 16.97 | 18.04 | 122.73 | 0.00 | 0.00 | 0.00 |
December | 18.83 | 6.86 | 11.97 | 11.04 | 153.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 74.47 | 32.19 | 42.28 | 103.38 | 93.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.83 | 6.86 | 11.97 | 11.04 | 46.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.49 | 55.24 | 70.50 | 194.63 | 153.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.95 | 0.00 | 8.95 | 0.24 | 109.49 | 0.00 | 0.00 | 0.00 |
February | 13.97 | 0.00 | 13.97 | 0.77 | 101.99 | 0.00 | 0.00 | 0.00 |
March | 19.33 | 0.00 | 19.33 | 5.82 | 81.56 | 0.00 | 0.00 | 0.00 |
April | 31.52 | 0.14 | 31.38 | 26.96 | 61.38 | 0.00 | 0.00 | 0.00 |
May | 39.11 | 1.63 | 37.48 | 33.76 | 48.23 | 0.00 | 0.00 | 0.00 |
June | 43.01 | 2.22 | 40.79 | 52.23 | 35.56 | 0.00 | 0.00 | 0.00 |
July | 40.91 | 1.97 | 38.94 | 54.16 | 32.20 | 0.00 | 0.00 | 0.00 |
August | 32.42 | 0.46 | 31.96 | 42.12 | 36.56 | 0.00 | 0.00 | 0.00 |
September | 24.70 | 0.01 | 24.69 | 26.34 | 51.42 | 0.00 | 0.00 | 0.00 |
October | 15.82 | 0.00 | 15.82 | 7.28 | 72.58 | 0.00 | 0.00 | 0.00 |
November | 9.51 | 0.00 | 9.51 | 0.43 | 94.03 | 0.00 | 0.00 | 0.00 |
December | 6.47 | 0.00 | 6.47 | 0.00 | 118.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.85 | 0.54 | 23.31 | 20.94 | 70.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.47 | 0.00 | 6.47 | 0.00 | 32.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.01 | 2.22 | 40.79 | 54.16 | 118.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.30 | 0.00 | 3.30 | 0.09 | 40.36 | 0.00 | 0.00 | 0.00 |
February | 5.15 | 0.00 | 5.15 | 0.28 | 37.60 | 0.00 | 0.00 | 0.00 |
March | 7.13 | 0.00 | 7.13 | 2.14 | 30.07 | 0.00 | 0.00 | 0.00 |
April | 11.62 | 0.05 | 11.57 | 9.94 | 22.63 | 0.00 | 0.00 | 0.00 |
May | 14.42 | 0.60 | 13.82 | 12.44 | 17.78 | 0.00 | 0.00 | 0.00 |
June | 15.85 | 0.82 | 15.04 | 19.25 | 13.11 | 0.00 | 0.00 | 0.00 |
July | 15.08 | 0.73 | 14.35 | 19.96 | 11.87 | 0.00 | 0.00 | 0.00 |
August | 11.95 | 0.17 | 11.78 | 15.53 | 13.48 | 0.00 | 0.00 | 0.00 |
September | 9.11 | 0.00 | 9.10 | 9.71 | 18.95 | 0.00 | 0.00 | 0.00 |
October | 5.83 | 0.00 | 5.83 | 2.68 | 26.75 | 0.00 | 0.00 | 0.00 |
November | 3.50 | 0.00 | 3.50 | 0.16 | 34.66 | 0.00 | 0.00 | 0.00 |
December | 2.39 | 0.00 | 2.39 | 0.00 | 43.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.79 | 0.20 | 8.59 | 7.72 | 25.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2.39 | 0.00 | 2.39 | 0.00 | 11.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.85 | 0.82 | 15.04 | 19.96 | 43.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.30 | 12.67 | 6.63 | 25.56 | 34.84 | 0.00 | 0.00 | 0.00 |
February | 23.16 | 14.24 | 8.91 | 31.94 | 33.57 | 0.00 | 0.00 | 0.00 |
March | 14.07 | 4.05 | 10.02 | 14.80 | 28.48 | 0.00 | 0.00 | 0.00 |
April | 28.22 | 12.14 | 16.08 | 46.63 | 22.76 | 0.00 | 0.00 | 0.00 |
May | 23.37 | 7.00 | 16.37 | 35.65 | 19.65 | 0.00 | 0.00 | 0.00 |
June | 21.56 | 4.62 | 16.94 | 35.11 | 14.46 | 0.00 | 0.00 | 0.00 |
July | 23.16 | 6.52 | 16.64 | 41.23 | 13.13 | 0.00 | 0.00 | 0.00 |
August | 27.42 | 11.80 | 15.62 | 51.32 | 14.19 | 0.00 | 0.00 | 0.00 |
September | 33.55 | 19.65 | 13.90 | 60.58 | 18.47 | 0.00 | 0.00 | 0.00 |
October | 22.79 | 13.21 | 9.58 | 35.30 | 25.30 | 0.00 | 0.00 | 0.00 |
November | 16.71 | 10.30 | 6.40 | 22.50 | 31.43 | 0.00 | 0.00 | 0.00 |
December | 13.34 | 8.69 | 4.65 | 16.92 | 39.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.18 | 10.36 | 11.82 | 34.75 | 24.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.34 | 4.05 | 4.65 | 14.80 | 13.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.55 | 19.65 | 16.94 | 60.58 | 39.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.38 | 34.39 | 18.00 | 69.37 | 94.57 | 0.00 | 0.00 | 0.00 |
February | 62.85 | 38.65 | 24.20 | 86.70 | 91.12 | 0.00 | 0.00 | 0.00 |
March | 38.18 | 10.99 | 27.19 | 40.17 | 77.30 | 0.00 | 0.00 | 0.00 |
April | 76.60 | 32.95 | 43.66 | 126.58 | 61.77 | 0.00 | 0.00 | 0.00 |
May | 63.43 | 19.00 | 44.43 | 96.76 | 53.34 | 0.00 | 0.00 | 0.00 |
June | 58.53 | 12.54 | 45.99 | 95.29 | 39.24 | 0.00 | 0.00 | 0.00 |
July | 62.85 | 17.69 | 45.16 | 111.90 | 35.63 | 0.00 | 0.00 | 0.00 |
August | 74.42 | 32.03 | 42.39 | 139.30 | 38.50 | 0.00 | 0.00 | 0.00 |
September | 91.06 | 53.35 | 37.72 | 164.44 | 50.13 | 0.00 | 0.00 | 0.00 |
October | 61.86 | 35.86 | 26.01 | 95.82 | 68.68 | 0.00 | 0.00 | 0.00 |
November | 45.35 | 27.97 | 17.38 | 61.08 | 85.30 | 0.00 | 0.00 | 0.00 |
December | 36.20 | 23.57 | 12.63 | 45.93 | 107.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.21 | 28.13 | 32.08 | 94.32 | 66.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.20 | 10.99 | 12.63 | 40.17 | 35.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 91.06 | 53.35 | 45.99 | 164.44 | 107.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.36 | 27.15 | 14.21 | 55.73 | 70.07 | 0.00 | 0.00 | 0.00 |
February | 49.63 | 30.52 | 19.11 | 69.06 | 68.25 | 0.00 | 0.00 | 0.00 |
March | 30.14 | 8.68 | 21.47 | 32.72 | 57.59 | 0.00 | 0.00 | 0.00 |
April | 60.49 | 26.02 | 34.47 | 97.71 | 47.82 | 0.00 | 0.00 | 0.00 |
May | 50.08 | 15.00 | 35.08 | 74.21 | 41.17 | 0.00 | 0.00 | 0.00 |
June | 46.22 | 9.90 | 36.32 | 72.46 | 29.92 | 0.00 | 0.00 | 0.00 |
July | 49.63 | 13.97 | 35.66 | 85.65 | 26.69 | 0.00 | 0.00 | 0.00 |
August | 58.76 | 25.29 | 33.47 | 107.49 | 28.55 | 0.00 | 0.00 | 0.00 |
September | 71.90 | 42.12 | 29.78 | 127.71 | 37.85 | 0.00 | 0.00 | 0.00 |
October | 48.85 | 28.31 | 20.53 | 75.34 | 51.44 | 0.00 | 0.00 | 0.00 |
November | 35.81 | 22.08 | 13.72 | 48.82 | 62.94 | 0.00 | 0.00 | 0.00 |
December | 28.58 | 18.61 | 9.97 | 37.13 | 78.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.54 | 22.21 | 25.33 | 73.57 | 49.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.58 | 8.68 | 9.97 | 32.72 | 26.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.90 | 42.12 | 36.32 | 127.71 | 78.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.17 | 8.41 | 17.77 | 19.88 | 142.66 | 0.00 | 0.00 | 0.00 |
February | 46.62 | 19.77 | 26.85 | 47.98 | 135.00 | 0.00 | 0.00 | 0.00 |
March | 42.20 | 8.23 | 33.97 | 32.16 | 108.42 | 0.00 | 0.00 | 0.00 |
April | 99.62 | 39.84 | 59.78 | 140.09 | 86.89 | 0.00 | 0.00 | 0.00 |
May | 116.93 | 47.97 | 68.96 | 163.46 | 72.36 | 0.00 | 0.00 | 0.00 |
June | 126.27 | 52.45 | 73.83 | 195.51 | 53.16 | 0.00 | 0.00 | 0.00 |
July | 128.56 | 57.10 | 71.46 | 210.29 | 47.59 | 0.00 | 0.00 | 0.00 |
August | 108.09 | 47.17 | 60.92 | 178.49 | 51.89 | 0.00 | 0.00 | 0.00 |
September | 87.16 | 39.57 | 47.59 | 135.90 | 70.67 | 0.00 | 0.00 | 0.00 |
October | 46.27 | 16.79 | 29.48 | 54.28 | 98.70 | 0.00 | 0.00 | 0.00 |
November | 24.73 | 7.12 | 17.61 | 19.27 | 124.89 | 0.00 | 0.00 | 0.00 |
December | 13.68 | 2.58 | 11.09 | 5.66 | 157.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.27 | 28.93 | 43.34 | 100.43 | 95.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.68 | 2.58 | 11.09 | 5.66 | 47.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.56 | 57.10 | 73.83 | 210.29 | 157.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.06 | 0.00 | 7.06 | 0.40 | 79.41 | 0.00 | 0.00 | 0.00 |
February | 11.03 | 0.00 | 11.03 | 1.13 | 74.60 | 0.00 | 0.00 | 0.00 |
March | 15.27 | 0.00 | 15.27 | 5.67 | 60.18 | 0.00 | 0.00 | 0.00 |
April | 24.89 | 0.11 | 24.78 | 20.23 | 47.07 | 0.00 | 0.00 | 0.00 |
May | 30.88 | 1.29 | 29.60 | 24.77 | 37.03 | 0.00 | 0.00 | 0.00 |
June | 33.96 | 1.75 | 32.21 | 38.04 | 27.40 | 0.00 | 0.00 | 0.00 |
July | 32.30 | 1.55 | 30.75 | 39.12 | 24.97 | 0.00 | 0.00 | 0.00 |
August | 25.60 | 0.36 | 25.24 | 30.68 | 28.00 | 0.00 | 0.00 | 0.00 |
September | 19.50 | 0.01 | 19.50 | 19.96 | 38.77 | 0.00 | 0.00 | 0.00 |
October | 12.49 | 0.00 | 12.49 | 6.47 | 53.50 | 0.00 | 0.00 | 0.00 |
November | 7.51 | 0.00 | 7.51 | 0.67 | 68.01 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 0.00 | 85.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.83 | 0.42 | 18.41 | 15.67 | 51.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 0.00 | 24.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.96 | 1.75 | 32.21 | 39.12 | 85.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.17 | 8.41 | 17.77 | 20.88 | 141.42 | 0.00 | 0.00 | 0.00 |
February | 46.62 | 19.77 | 26.85 | 49.56 | 133.51 | 0.00 | 0.00 | 0.00 |
March | 42.20 | 8.23 | 33.97 | 32.96 | 107.86 | 0.00 | 0.00 | 0.00 |
April | 99.62 | 39.84 | 59.78 | 142.07 | 86.20 | 0.00 | 0.00 | 0.00 |
May | 116.93 | 47.97 | 68.96 | 164.01 | 72.35 | 0.00 | 0.00 | 0.00 |
June | 126.27 | 52.45 | 73.83 | 194.56 | 53.86 | 0.00 | 0.00 | 0.00 |
July | 128.56 | 57.10 | 71.46 | 207.86 | 49.06 | 0.00 | 0.00 | 0.00 |
August | 108.09 | 47.17 | 60.92 | 177.46 | 53.36 | 0.00 | 0.00 | 0.00 |
September | 87.16 | 39.57 | 47.59 | 137.36 | 70.44 | 0.00 | 0.00 | 0.00 |
October | 46.27 | 16.79 | 29.48 | 56.20 | 97.49 | 0.00 | 0.00 | 0.00 |
November | 24.73 | 7.12 | 17.61 | 20.27 | 123.71 | 0.00 | 0.00 | 0.00 |
December | 13.68 | 2.58 | 11.09 | 6.03 | 156.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.27 | 28.93 | 43.34 | 100.94 | 95.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.68 | 2.58 | 11.09 | 6.03 | 49.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.56 | 57.10 | 73.83 | 207.86 | 156.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.66 | 39.82 | 20.84 | 78.87 | 106.55 | 0.00 | 0.00 | 0.00 |
February | 72.78 | 44.76 | 28.02 | 98.55 | 103.61 | 0.00 | 0.00 | 0.00 |
March | 44.21 | 12.73 | 31.48 | 46.05 | 86.75 | 0.00 | 0.00 | 0.00 |
April | 88.71 | 38.16 | 50.56 | 141.50 | 71.04 | 0.00 | 0.00 | 0.00 |
May | 73.45 | 22.00 | 51.45 | 107.93 | 60.60 | 0.00 | 0.00 | 0.00 |
June | 67.78 | 14.52 | 53.26 | 106.56 | 43.39 | 0.00 | 0.00 | 0.00 |
July | 72.78 | 20.49 | 52.30 | 126.06 | 38.59 | 0.00 | 0.00 | 0.00 |
August | 86.18 | 37.09 | 49.09 | 157.50 | 41.58 | 0.00 | 0.00 | 0.00 |
September | 105.45 | 61.78 | 43.68 | 185.80 | 56.26 | 0.00 | 0.00 | 0.00 |
October | 71.64 | 41.52 | 30.12 | 108.18 | 78.09 | 0.00 | 0.00 | 0.00 |
November | 52.51 | 32.39 | 20.13 | 69.38 | 96.15 | 0.00 | 0.00 | 0.00 |
December | 41.92 | 27.30 | 14.62 | 52.74 | 119.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.72 | 32.57 | 37.15 | 106.45 | 75.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.92 | 12.73 | 14.62 | 46.05 | 38.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 105.45 | 61.78 | 53.26 | 185.80 | 119.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.45 | 0.00 | 49.45 | 1.43 | 586.56 | 0.00 | 0.00 | 0.00 |
February | 77.21 | 0.00 | 77.21 | 4.51 | 549.31 | 0.00 | 0.00 | 0.00 |
March | 106.86 | 0.00 | 106.86 | 32.46 | 441.79 | 0.00 | 0.00 | 0.00 |
April | 174.20 | 0.75 | 173.45 | 147.54 | 336.33 | 0.00 | 0.00 | 0.00 |
May | 216.17 | 9.00 | 207.17 | 183.15 | 269.65 | 0.00 | 0.00 | 0.00 |
June | 237.70 | 12.25 | 225.46 | 286.92 | 198.84 | 0.00 | 0.00 | 0.00 |
July | 226.09 | 10.87 | 215.22 | 302.29 | 177.99 | 0.00 | 0.00 | 0.00 |
August | 179.19 | 2.53 | 176.67 | 239.24 | 197.28 | 0.00 | 0.00 | 0.00 |
September | 136.52 | 0.04 | 136.48 | 150.69 | 276.22 | 0.00 | 0.00 | 0.00 |
October | 87.44 | 0.00 | 87.44 | 41.68 | 394.77 | 0.00 | 0.00 | 0.00 |
November | 52.54 | 0.00 | 52.54 | 2.51 | 509.15 | 0.00 | 0.00 | 0.00 |
December | 35.78 | 0.00 | 35.78 | 0.00 | 638.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.84 | 2.97 | 128.86 | 116.61 | 380.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.78 | 0.00 | 35.78 | 0.00 | 177.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.70 | 12.25 | 225.46 | 302.29 | 638.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.45 | 0.00 | 49.45 | 1.02 | 609.91 | 0.00 | 0.00 | 0.00 |
February | 77.21 | 0.00 | 77.21 | 3.47 | 572.98 | 0.00 | 0.00 | 0.00 |
March | 106.86 | 0.00 | 106.86 | 28.17 | 463.02 | 0.00 | 0.00 | 0.00 |
April | 174.20 | 0.75 | 173.45 | 139.42 | 350.20 | 0.00 | 0.00 | 0.00 |
May | 216.17 | 9.00 | 207.17 | 173.08 | 280.63 | 0.00 | 0.00 | 0.00 |
June | 237.70 | 12.25 | 225.46 | 276.65 | 206.82 | 0.00 | 0.00 | 0.00 |
July | 226.09 | 10.87 | 215.22 | 292.28 | 185.10 | 0.00 | 0.00 | 0.00 |
August | 179.19 | 2.53 | 176.67 | 230.96 | 205.64 | 0.00 | 0.00 | 0.00 |
September | 136.52 | 0.04 | 136.48 | 143.68 | 287.88 | 0.00 | 0.00 | 0.00 |
October | 87.44 | 0.00 | 87.44 | 37.23 | 414.15 | 0.00 | 0.00 | 0.00 |
November | 52.54 | 0.00 | 52.54 | 1.76 | 533.51 | 0.00 | 0.00 | 0.00 |
December | 35.78 | 0.00 | 35.78 | 0.00 | 662.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.84 | 2.97 | 128.86 | 111.20 | 396.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.78 | 0.00 | 35.78 | 0.00 | 185.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.70 | 12.25 | 225.46 | 292.28 | 662.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.06 | 0.00 | 7.06 | 7.60 | 52.97 | 0.00 | 0.00 | 0.00 |
February | 11.03 | 0.00 | 11.03 | 12.37 | 52.54 | 0.00 | 0.00 | 0.00 |
March | 15.27 | 0.00 | 15.27 | 24.20 | 43.54 | 0.00 | 0.00 | 0.00 |
April | 24.89 | 0.11 | 24.78 | 50.69 | 37.00 | 0.00 | 0.00 | 0.00 |
May | 30.88 | 1.29 | 29.60 | 60.41 | 32.65 | 0.00 | 0.00 | 0.00 |
June | 33.96 | 1.75 | 32.21 | 78.97 | 24.31 | 0.00 | 0.00 | 0.00 |
July | 32.30 | 1.55 | 30.75 | 82.23 | 21.83 | 0.00 | 0.00 | 0.00 |
August | 25.60 | 0.36 | 25.24 | 70.23 | 21.90 | 0.00 | 0.00 | 0.00 |
September | 19.50 | 0.01 | 19.50 | 51.27 | 28.27 | 0.00 | 0.00 | 0.00 |
October | 12.49 | 0.00 | 12.49 | 26.15 | 37.53 | 0.00 | 0.00 | 0.00 |
November | 7.51 | 0.00 | 7.51 | 10.25 | 44.78 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 3.80 | 58.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.83 | 0.42 | 18.41 | 39.99 | 37.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 3.80 | 21.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.96 | 1.75 | 32.21 | 82.23 | 58.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.87 | 20.61 | 32.26 | 79.66 | 192.25 | 0.00 | 0.00 | 0.00 |
February | 80.91 | 30.11 | 50.79 | 122.71 | 191.03 | 0.00 | 0.00 | 0.00 |
March | 84.14 | 16.61 | 67.52 | 142.91 | 159.92 | 0.00 | 0.00 | 0.00 |
April | 227.27 | 107.58 | 119.69 | 457.48 | 135.72 | 0.00 | 0.00 | 0.00 |
May | 239.00 | 105.22 | 133.77 | 468.76 | 121.35 | 0.00 | 0.00 | 0.00 |
June | 236.16 | 95.17 | 140.99 | 509.35 | 90.49 | 0.00 | 0.00 | 0.00 |
July | 240.95 | 103.12 | 137.84 | 544.24 | 81.05 | 0.00 | 0.00 | 0.00 |
August | 229.13 | 110.47 | 118.65 | 531.38 | 81.60 | 0.00 | 0.00 | 0.00 |
September | 206.05 | 110.28 | 95.77 | 459.69 | 104.50 | 0.00 | 0.00 | 0.00 |
October | 99.45 | 41.62 | 57.83 | 205.51 | 138.98 | 0.00 | 0.00 | 0.00 |
November | 51.03 | 17.09 | 33.94 | 83.10 | 163.96 | 0.00 | 0.00 | 0.00 |
December | 37.66 | 13.71 | 23.94 | 49.30 | 213.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 148.93 | 64.38 | 84.55 | 305.20 | 139.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.66 | 13.71 | 23.94 | 49.30 | 81.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 240.95 | 110.47 | 140.99 | 544.24 | 213.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.36 | 27.15 | 14.21 | 71.85 | 50.24 | 0.00 | 0.00 | 0.00 |
February | 49.63 | 30.52 | 19.11 | 88.22 | 51.12 | 0.00 | 0.00 | 0.00 |
March | 30.14 | 8.68 | 21.47 | 54.78 | 43.22 | 0.00 | 0.00 | 0.00 |
April | 60.49 | 26.02 | 34.47 | 130.62 | 37.59 | 0.00 | 0.00 | 0.00 |
May | 50.08 | 15.00 | 35.08 | 108.55 | 34.20 | 0.00 | 0.00 | 0.00 |
June | 46.22 | 9.90 | 36.32 | 111.62 | 25.25 | 0.00 | 0.00 | 0.00 |
July | 49.63 | 13.97 | 35.66 | 126.45 | 22.51 | 0.00 | 0.00 | 0.00 |
August | 58.76 | 25.29 | 33.47 | 146.72 | 22.33 | 0.00 | 0.00 | 0.00 |
September | 71.90 | 42.12 | 29.78 | 162.42 | 28.27 | 0.00 | 0.00 | 0.00 |
October | 48.85 | 28.31 | 20.53 | 99.59 | 37.21 | 0.00 | 0.00 | 0.00 |
November | 35.81 | 22.08 | 13.72 | 64.38 | 43.71 | 0.00 | 0.00 | 0.00 |
December | 28.58 | 18.61 | 9.97 | 47.22 | 56.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.54 | 22.21 | 25.33 | 100.96 | 37.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.58 | 8.68 | 9.97 | 47.22 | 22.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.90 | 42.12 | 36.32 | 162.42 | 56.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.95 | 0.00 | 8.95 | 0.17 | 110.58 | 0.00 | 0.00 | 0.00 |
February | 13.97 | 0.00 | 13.97 | 0.60 | 103.50 | 0.00 | 0.00 | 0.00 |
March | 19.33 | 0.00 | 19.33 | 5.08 | 83.14 | 0.00 | 0.00 | 0.00 |
April | 31.52 | 0.14 | 31.38 | 22.27 | 66.47 | 0.00 | 0.00 | 0.00 |
May | 39.11 | 1.63 | 37.48 | 27.18 | 53.79 | 0.00 | 0.00 | 0.00 |
June | 43.01 | 2.22 | 40.79 | 43.47 | 41.36 | 0.00 | 0.00 | 0.00 |
July | 40.91 | 1.97 | 38.94 | 45.28 | 37.78 | 0.00 | 0.00 | 0.00 |
August | 32.42 | 0.46 | 31.96 | 34.79 | 42.88 | 0.00 | 0.00 | 0.00 |
September | 24.70 | 0.01 | 24.69 | 21.35 | 57.92 | 0.00 | 0.00 | 0.00 |
October | 15.82 | 0.00 | 15.82 | 5.66 | 76.52 | 0.00 | 0.00 | 0.00 |
November | 9.51 | 0.00 | 9.51 | 0.31 | 95.88 | 0.00 | 0.00 | 0.00 |
December | 6.47 | 0.00 | 6.47 | 0.00 | 119.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.85 | 0.54 | 23.31 | 17.26 | 73.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.47 | 0.00 | 6.47 | 0.00 | 37.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.01 | 2.22 | 40.79 | 45.28 | 119.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.00 | 0.00 | 8.00 | 0.15 | 98.92 | 0.00 | 0.00 | 0.00 |
February | 12.50 | 0.00 | 12.50 | 0.53 | 92.60 | 0.00 | 0.00 | 0.00 |
March | 17.30 | 0.00 | 17.30 | 4.55 | 74.39 | 0.00 | 0.00 | 0.00 |
April | 28.20 | 0.12 | 28.08 | 19.92 | 59.47 | 0.00 | 0.00 | 0.00 |
May | 34.99 | 1.46 | 33.54 | 24.32 | 48.13 | 0.00 | 0.00 | 0.00 |
June | 38.48 | 1.98 | 36.50 | 38.89 | 37.00 | 0.00 | 0.00 | 0.00 |
July | 36.60 | 1.76 | 34.84 | 40.51 | 33.80 | 0.00 | 0.00 | 0.00 |
August | 29.01 | 0.41 | 28.60 | 31.13 | 38.37 | 0.00 | 0.00 | 0.00 |
September | 22.10 | 0.01 | 22.09 | 19.10 | 51.82 | 0.00 | 0.00 | 0.00 |
October | 14.15 | 0.00 | 14.15 | 5.06 | 68.47 | 0.00 | 0.00 | 0.00 |
November | 8.50 | 0.00 | 8.50 | 0.27 | 85.78 | 0.00 | 0.00 | 0.00 |
December | 5.79 | 0.00 | 5.79 | 0.00 | 106.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.34 | 0.48 | 20.86 | 15.45 | 66.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.79 | 0.00 | 5.79 | 0.00 | 33.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.48 | 1.98 | 36.50 | 40.51 | 106.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 154.42 | 101.38 | 53.05 | 202.23 | 281.13 | 0.00 | 0.00 | 0.00 |
February | 185.27 | 113.95 | 71.33 | 252.32 | 271.80 | 0.00 | 0.00 | 0.00 |
March | 112.54 | 32.40 | 80.14 | 115.00 | 232.24 | 0.00 | 0.00 | 0.00 |
April | 225.82 | 97.13 | 128.69 | 357.64 | 196.69 | 0.00 | 0.00 | 0.00 |
May | 186.98 | 56.01 | 130.97 | 267.16 | 175.88 | 0.00 | 0.00 | 0.00 |
June | 172.54 | 36.96 | 135.58 | 257.49 | 135.71 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 52.15 | 133.12 | 305.92 | 124.43 | 0.00 | 0.00 | 0.00 |
August | 219.38 | 94.42 | 124.96 | 388.79 | 133.16 | 0.00 | 0.00 | 0.00 |
September | 268.44 | 157.26 | 111.18 | 466.92 | 165.84 | 0.00 | 0.00 | 0.00 |
October | 182.37 | 105.70 | 76.66 | 275.19 | 213.08 | 0.00 | 0.00 | 0.00 |
November | 133.68 | 82.45 | 51.23 | 177.50 | 256.14 | 0.00 | 0.00 | 0.00 |
December | 106.71 | 69.49 | 37.22 | 133.99 | 318.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.48 | 82.91 | 94.57 | 266.27 | 208.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.71 | 32.40 | 37.22 | 115.00 | 124.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 268.44 | 157.26 | 135.58 | 466.92 | 318.53 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.560335E+09 | 0.367850E+09 | 0.192485E+09 | 0.741925E+09 | 0.959775E+09 |
February | 0.607224E+09 | 0.373459E+09 | 0.233765E+09 | 0.836360E+09 | 0.836772E+09 |
March | 0.408358E+09 | 0.117558E+09 | 0.290800E+09 | 0.436321E+09 | 0.782705E+09 |
April | 0.792971E+09 | 0.341069E+09 | 0.451901E+09 | 0.128398E+10 | 0.628905E+09 |
May | 0.678458E+09 | 0.203228E+09 | 0.475230E+09 | 0.101754E+10 | 0.556563E+09 |
June | 0.605866E+09 | 0.129779E+09 | 0.476087E+09 | 0.960959E+09 | 0.405811E+09 |
July | 0.672267E+09 | 0.189220E+09 | 0.483046E+09 | 0.116076E+10 | 0.389027E+09 |
August | 0.796028E+09 | 0.342606E+09 | 0.453423E+09 | 0.144659E+10 | 0.428128E+09 |
September | 0.942633E+09 | 0.552222E+09 | 0.390411E+09 | 0.166293E+10 | 0.528948E+09 |
October | 0.661728E+09 | 0.383553E+09 | 0.278176E+09 | 0.101062E+10 | 0.710160E+09 |
November | 0.469411E+09 | 0.289513E+09 | 0.179898E+09 | 0.632340E+09 | 0.837686E+09 |
December | 0.387206E+09 | 0.252152E+09 | 0.135054E+09 | 0.495149E+09 | 0.107492E+10 |
Annual Sum or Average | 0.758249E+10 | 0.354221E+10 | 0.404028E+10 | 0.116855E+11 | 0.813940E+10 |
Minimum of Months | 0.387206E+09 | 0.117558E+09 | 0.135054E+09 | 0.436321E+09 | 0.389027E+09 |
Maximum of Months | 0.942633E+09 | 0.552222E+09 | 0.483046E+09 | 0.166293E+10 | 0.107492E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157787E+10 | 0.103584E+10 | 0.542026E+09 | 0.208031E+10 | 0.269895E+10 |
February | 0.170990E+10 | 0.105164E+10 | 0.658267E+09 | 0.234882E+10 | 0.235228E+10 |
March | 0.114991E+10 | 0.331035E+09 | 0.818874E+09 | 0.120938E+10 | 0.220519E+10 |
April | 0.223295E+10 | 0.960429E+09 | 0.127252E+10 | 0.364666E+10 | 0.173730E+10 |
May | 0.191049E+10 | 0.572275E+09 | 0.133822E+10 | 0.289804E+10 | 0.153168E+10 |
June | 0.170608E+10 | 0.365449E+09 | 0.134063E+10 | 0.277171E+10 | 0.108513E+10 |
July | 0.189306E+10 | 0.532832E+09 | 0.136023E+10 | 0.336528E+10 | 0.101585E+10 |
August | 0.224156E+10 | 0.964755E+09 | 0.127681E+10 | 0.417481E+10 | 0.111065E+10 |
September | 0.265439E+10 | 0.155502E+10 | 0.109937E+10 | 0.474917E+10 | 0.141509E+10 |
October | 0.186338E+10 | 0.108006E+10 | 0.783324E+09 | 0.285770E+10 | 0.199110E+10 |
November | 0.132183E+10 | 0.815249E+09 | 0.506582E+09 | 0.177355E+10 | 0.236908E+10 |
December | 0.109035E+10 | 0.710044E+09 | 0.380302E+09 | 0.138361E+10 | 0.303251E+10 |
Annual Sum or Average | 0.213518E+11 | 0.997463E+10 | 0.113772E+11 | 0.332590E+11 | 0.225448E+11 |
Minimum of Months | 0.109035E+10 | 0.331035E+09 | 0.380302E+09 | 0.120938E+10 | 0.101585E+10 |
Maximum of Months | 0.265439E+10 | 0.155502E+10 | 0.136023E+10 | 0.474917E+10 | 0.303251E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204974E+10 | 0.134562E+10 | 0.704123E+09 | 0.270929E+10 | 0.374215E+10 |
February | 0.222126E+10 | 0.136613E+10 | 0.855126E+09 | 0.306122E+10 | 0.325583E+10 |
March | 0.149380E+10 | 0.430034E+09 | 0.106376E+10 | 0.156635E+10 | 0.309108E+10 |
April | 0.290073E+10 | 0.124765E+10 | 0.165308E+10 | 0.475993E+10 | 0.243213E+10 |
May | 0.248184E+10 | 0.743418E+09 | 0.173842E+10 | 0.376424E+10 | 0.217225E+10 |
June | 0.221629E+10 | 0.474739E+09 | 0.174156E+10 | 0.357865E+10 | 0.156535E+10 |
July | 0.245919E+10 | 0.692179E+09 | 0.176701E+10 | 0.435207E+10 | 0.147165E+10 |
August | 0.291192E+10 | 0.125327E+10 | 0.165865E+10 | 0.542642E+10 | 0.159667E+10 |
September | 0.344821E+10 | 0.202006E+10 | 0.142815E+10 | 0.619456E+10 | 0.199730E+10 |
October | 0.242064E+10 | 0.140306E+10 | 0.101758E+10 | 0.372225E+10 | 0.279948E+10 |
November | 0.171713E+10 | 0.105906E+10 | 0.658079E+09 | 0.230477E+10 | 0.330830E+10 |
December | 0.141642E+10 | 0.922388E+09 | 0.494034E+09 | 0.179728E+10 | 0.419910E+10 |
Annual Sum or Average | 0.277372E+11 | 0.129576E+11 | 0.147796E+11 | 0.432370E+11 | 0.316313E+11 |
Minimum of Months | 0.141642E+10 | 0.430034E+09 | 0.494034E+09 | 0.156635E+10 | 0.147165E+10 |
Maximum of Months | 0.344821E+10 | 0.202006E+10 | 0.176701E+10 | 0.619456E+10 | 0.419910E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110788E+09 | 72730218.65 | 38057817.66 | 0.148746E+09 | 0.190775E+09 |
February | 0.120059E+09 | 73839255.87 | 46219601.72 | 0.166882E+09 | 0.167300E+09 |
March | 80739717.45 | 23243215.37 | 57496502.08 | 87283141.85 | 0.156657E+09 |
April | 0.156785E+09 | 67435285.57 | 89349352.43 | 0.255514E+09 | 0.124809E+09 |
May | 0.134144E+09 | 40181567.79 | 93962043.07 | 0.201127E+09 | 0.110790E+09 |
June | 0.119791E+09 | 25659533.30 | 94131539.98 | 0.190465E+09 | 77836448.77 |
July | 0.132920E+09 | 37412079.40 | 95507512.87 | 0.232235E+09 | 71840537.94 |
August | 0.157389E+09 | 67739007.31 | 89650286.20 | 0.290422E+09 | 77237340.92 |
September | 0.186375E+09 | 0.109184E+09 | 77191609.42 | 0.332992E+09 | 99182814.50 |
October | 0.130835E+09 | 75834943.47 | 55000400.68 | 0.202094E+09 | 0.140019E+09 |
November | 92810845.86 | 57241680.33 | 35569165.54 | 0.126268E+09 | 0.166051E+09 |
December | 76557382.06 | 49854844.58 | 26702537.48 | 99124288.41 | 0.213451E+09 |
Annual Sum or Average | 0.149919E+10 | 0.700355E+09 | 0.798838E+09 | 0.233315E+10 | 0.159595E+10 |
Minimum of Months | 76557382.06 | 23243215.37 | 26702537.48 | 87283141.85 | 71840537.94 |
Maximum of Months | 0.186375E+09 | 0.109184E+09 | 95507512.87 | 0.332992E+09 | 0.213451E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70103377.43 | 22516648.95 | 47586728.48 | 52511934.72 | 0.389002E+09 |
February | 0.112780E+09 | 47823668.68 | 64956185.94 | 0.115664E+09 | 0.331573E+09 |
March | 0.113023E+09 | 22039037.34 | 90984377.97 | 85494956.98 | 0.295165E+09 |
April | 0.258212E+09 | 0.103264E+09 | 0.154948E+09 | 0.367660E+09 | 0.227233E+09 |
May | 0.313194E+09 | 0.128480E+09 | 0.184714E+09 | 0.443419E+09 | 0.195051E+09 |
June | 0.327302E+09 | 0.135943E+09 | 0.191358E+09 | 0.513462E+09 | 0.138557E+09 |
July | 0.344336E+09 | 0.152930E+09 | 0.191406E+09 | 0.570000E+09 | 0.128401E+09 |
August | 0.289519E+09 | 0.126350E+09 | 0.163168E+09 | 0.483382E+09 | 0.140703E+09 |
September | 0.225929E+09 | 0.102563E+09 | 0.123366E+09 | 0.355367E+09 | 0.185609E+09 |
October | 0.123937E+09 | 44968258.80 | 78968371.89 | 0.145631E+09 | 0.269125E+09 |
November | 64103227.46 | 18461449.30 | 45641778.16 | 49361486.49 | 0.329961E+09 |
December | 36632118.50 | 6915842.16 | 29716276.33 | 14755692.10 | 0.428829E+09 |
Annual Sum or Average | 0.227907E+10 | 0.912255E+09 | 0.136681E+10 | 0.319671E+10 | 0.305921E+10 |
Minimum of Months | 36632118.50 | 6915842.16 | 29716276.33 | 14755692.10 | 0.128401E+09 |
Maximum of Months | 0.344336E+09 | 0.152930E+09 | 0.191406E+09 | 0.570000E+09 | 0.428829E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18920192.73 | 0.00 | 18920192.73 | 941162.24 | 0.216600E+09 |
February | 26685522.77 | 0.00 | 26685522.77 | 2512571.38 | 0.183534E+09 |
March | 40888395.66 | 94.99 | 40888300.66 | 14709198.28 | 0.163938E+09 |
April | 64506832.14 | 278270.09 | 64228562.06 | 54105764.82 | 0.122888E+09 |
May | 82717830.29 | 3444156.17 | 79273674.12 | 68644266.65 | 99545927.41 |
June | 88020373.33 | 4534392.98 | 83485980.34 | 0.101757E+09 | 70909534.90 |
July | 86511862.95 | 4159765.81 | 82352097.14 | 0.108355E+09 | 66352891.87 |
August | 68567347.80 | 966214.74 | 67601133.05 | 84660154.07 | 74837556.64 |
September | 50551966.39 | 15085.32 | 50536881.07 | 52570372.22 | 0.101355E+09 |
October | 33456625.06 | 0.00 | 33456625.06 | 16939376.65 | 0.146017E+09 |
November | 19453978.92 | 0.00 | 19453978.92 | 1526740.99 | 0.180016E+09 |
December | 13689710.98 | 0.00 | 13689710.98 | 0.00 | 0.232705E+09 |
Annual Sum or Average | 0.593971E+09 | 13397980.11 | 0.580573E+09 | 0.506722E+09 | 0.165870E+10 |
Minimum of Months | 13689710.98 | 0.00 | 13689710.98 | 0.00 | 66352891.87 |
Maximum of Months | 88020373.33 | 4534392.98 | 83485980.34 | 0.108355E+09 | 0.232705E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70103377.43 | 22516648.95 | 47586728.48 | 55106877.83 | 0.385393E+09 |
February | 0.112780E+09 | 47823668.68 | 64956185.94 | 0.119154E+09 | 0.328012E+09 |
March | 0.113023E+09 | 22039037.34 | 90984377.97 | 87461317.80 | 0.293697E+09 |
April | 0.258212E+09 | 0.103264E+09 | 0.154948E+09 | 0.372786E+09 | 0.225367E+09 |
May | 0.313194E+09 | 0.128480E+09 | 0.184714E+09 | 0.445530E+09 | 0.194627E+09 |
June | 0.327302E+09 | 0.135943E+09 | 0.191358E+09 | 0.512326E+09 | 0.139536E+09 |
July | 0.344336E+09 | 0.152930E+09 | 0.191406E+09 | 0.565859E+09 | 0.130809E+09 |
August | 0.289519E+09 | 0.126350E+09 | 0.163168E+09 | 0.482329E+09 | 0.143138E+09 |
September | 0.225929E+09 | 0.102563E+09 | 0.123366E+09 | 0.359310E+09 | 0.184535E+09 |
October | 0.123937E+09 | 44968258.80 | 78968371.89 | 0.150306E+09 | 0.266091E+09 |
November | 64103227.46 | 18461449.30 | 45641778.16 | 51705069.63 | 0.326853E+09 |
December | 36632118.50 | 6915842.16 | 29716276.33 | 15780401.71 | 0.426062E+09 |
Annual Sum or Average | 0.227907E+10 | 0.912255E+09 | 0.136681E+10 | 0.321765E+10 | 0.304412E+10 |
Minimum of Months | 36632118.50 | 6915842.16 | 29716276.33 | 15780401.71 | 0.130809E+09 |
Maximum of Months | 0.344336E+09 | 0.152930E+09 | 0.191406E+09 | 0.565859E+09 | 0.426062E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88612806.35 | 58172605.95 | 30440200.40 | 0.110710E+09 | 0.178859E+09 |
February | 96027988.69 | 59059659.32 | 36968329.37 | 0.125819E+09 | 0.155694E+09 |
March | 64578930.95 | 18590875.07 | 45988055.88 | 63636713.09 | 0.140427E+09 |
April | 0.125403E+09 | 53937501.74 | 71465269.43 | 0.184633E+09 | 0.134785E+09 |
May | 0.107294E+09 | 32138862.68 | 75154688.22 | 0.138425E+09 | 0.127405E+09 |
June | 95813803.84 | 20523545.06 | 75290258.78 | 0.128430E+09 | 95929205.24 |
July | 0.106315E+09 | 29923712.50 | 76390818.22 | 0.160813E+09 | 91182275.45 |
August | 0.125886E+09 | 54180430.82 | 71705968.57 | 0.208863E+09 | 97686615.85 |
September | 0.149071E+09 | 87329671.17 | 61741008.91 | 0.244445E+09 | 0.117585E+09 |
October | 0.104647E+09 | 60655891.96 | 43991571.81 | 0.145654E+09 | 0.155937E+09 |
November | 74233913.57 | 45784239.01 | 28449674.56 | 92267903.52 | 0.167172E+09 |
December | 61233727.91 | 39875945.41 | 21357782.49 | 79012887.29 | 0.167506E+09 |
Annual Sum or Average | 0.119912E+10 | 0.560173E+09 | 0.638944E+09 | 0.168271E+10 | 0.163017E+10 |
Minimum of Months | 61233727.91 | 18590875.07 | 21357782.49 | 63636713.09 | 91182275.45 |
Maximum of Months | 0.149071E+09 | 87329671.17 | 76390818.22 | 0.244445E+09 | 0.178859E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 15138160.56 | 0.00 | 15138160.56 | 441624.43 | 0.181939E+09 |
February | 21351248.07 | 0.00 | 21351248.07 | 1334023.94 | 0.153241E+09 |
March | 32715052.52 | 76.01 | 32714976.51 | 9729535.44 | 0.137188E+09 |
April | 51612306.31 | 222645.58 | 51389660.73 | 43521432.29 | 99378315.32 |
May | 66183036.00 | 2755690.17 | 63427345.83 | 56106273.77 | 80158015.68 |
June | 70425632.74 | 3627995.24 | 66797637.51 | 84713167.03 | 55949375.61 |
July | 69218664.47 | 3328253.77 | 65890410.71 | 91346119.58 | 51732693.66 |
August | 54861149.43 | 773074.26 | 54088075.17 | 71650383.64 | 58121390.88 |
September | 40446933.88 | 12069.86 | 40434864.02 | 43687288.81 | 80321756.06 |
October | 26768847.94 | 0.00 | 26768847.94 | 12435928.07 | 0.121489E+09 |
November | 15565246.12 | 0.00 | 15565246.12 | 722848.32 | 0.152123E+09 |
December | 10953220.50 | 0.00 | 10953220.50 | 0.00 | 0.196385E+09 |
Annual Sum or Average | 0.475239E+09 | 10719804.87 | 0.464520E+09 | 0.415689E+09 | 0.136803E+10 |
Minimum of Months | 10953220.50 | 0.00 | 10953220.50 | 0.00 | 51732693.66 |
Maximum of Months | 70425632.74 | 3627995.24 | 66797637.51 | 91346119.58 | 0.196385E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70813818.73 | 27608988.36 | 43204830.37 | 49058790.83 | 0.382774E+09 |
February | 97872440.35 | 36429077.93 | 61443362.42 | 78462125.14 | 0.324853E+09 |
March | 0.112683E+09 | 22248080.11 | 90434959.81 | 82571086.55 | 0.291602E+09 |
April | 0.294563E+09 | 0.139438E+09 | 0.155125E+09 | 0.423659E+09 | 0.216120E+09 |
May | 0.320086E+09 | 0.140923E+09 | 0.179162E+09 | 0.447980E+09 | 0.188605E+09 |
June | 0.306080E+09 | 0.123344E+09 | 0.182735E+09 | 0.468616E+09 | 0.134019E+09 |
July | 0.322710E+09 | 0.138108E+09 | 0.184602E+09 | 0.522550E+09 | 0.123485E+09 |
August | 0.306866E+09 | 0.147954E+09 | 0.158912E+09 | 0.510700E+09 | 0.133446E+09 |
September | 0.267062E+09 | 0.142934E+09 | 0.124129E+09 | 0.422667E+09 | 0.177047E+09 |
October | 0.133190E+09 | 55737192.40 | 77453082.75 | 0.157495E+09 | 0.263301E+09 |
November | 66137150.63 | 22150671.32 | 43986479.31 | 45410831.80 | 0.322377E+09 |
December | 50436718.89 | 18367374.03 | 32069344.86 | 28972588.35 | 0.415382E+09 |
Annual Sum or Average | 0.234850E+10 | 0.101524E+10 | 0.133326E+10 | 0.323814E+10 | 0.297301E+10 |
Minimum of Months | 50436718.89 | 18367374.03 | 32069344.86 | 28972588.35 | 0.123485E+09 |
Maximum of Months | 0.322710E+09 | 0.147954E+09 | 0.184602E+09 | 0.522550E+09 | 0.415382E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110788E+09 | 72730218.65 | 38057817.66 | 0.148471E+09 | 0.190604E+09 |
February | 0.120059E+09 | 73839255.87 | 46219601.72 | 0.166865E+09 | 0.166794E+09 |
March | 80739717.45 | 23243215.37 | 57496502.08 | 86802416.35 | 0.156454E+09 |
April | 0.156785E+09 | 67435285.57 | 89349352.43 | 0.252838E+09 | 0.124735E+09 |
May | 0.134144E+09 | 40181567.79 | 93962043.07 | 0.198891E+09 | 0.110255E+09 |
June | 0.119791E+09 | 25659533.30 | 94131539.98 | 0.189263E+09 | 76899351.67 |
July | 0.132920E+09 | 37412079.40 | 95507512.87 | 0.230902E+09 | 71068779.20 |
August | 0.157389E+09 | 67739007.31 | 89650286.20 | 0.288832E+09 | 76810143.41 |
September | 0.186375E+09 | 0.109184E+09 | 77191609.42 | 0.330715E+09 | 99111775.52 |
October | 0.130835E+09 | 75834943.47 | 55000400.68 | 0.201055E+09 | 0.139874E+09 |
November | 92810845.86 | 57241680.33 | 35569165.54 | 0.126044E+09 | 0.165863E+09 |
December | 76557382.06 | 49854844.58 | 26702537.48 | 98780707.89 | 0.213664E+09 |
Annual Sum or Average | 0.149919E+10 | 0.700355E+09 | 0.798838E+09 | 0.231946E+10 | 0.159213E+10 |
Minimum of Months | 76557382.06 | 23243215.37 | 26702537.48 | 86802416.35 | 71068779.20 |
Maximum of Months | 0.186375E+09 | 0.109184E+09 | 95507512.87 | 0.330715E+09 | 0.213664E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18920192.73 | 0.00 | 18920192.73 | 857485.12 | 0.216506E+09 |
February | 26685522.77 | 0.00 | 26685522.77 | 2315148.32 | 0.182951E+09 |
March | 40888395.66 | 94.99 | 40888300.66 | 14290967.65 | 0.163792E+09 |
April | 64506832.14 | 278270.09 | 64228562.06 | 51527532.09 | 0.123050E+09 |
May | 82717830.29 | 3444156.17 | 79273674.12 | 66935723.09 | 99150970.42 |
June | 88020373.33 | 4534392.98 | 83485980.34 | 0.101153E+09 | 69961221.28 |
July | 86511862.95 | 4159765.81 | 82352097.14 | 0.108009E+09 | 65082411.30 |
August | 68567347.80 | 966214.74 | 67601133.05 | 83048161.38 | 73910786.20 |
September | 50551966.39 | 15085.32 | 50536881.07 | 50280581.19 | 0.101210E+09 |
October | 33456625.06 | 0.00 | 33456625.06 | 16069011.22 | 0.145898E+09 |
November | 19453978.92 | 0.00 | 19453978.92 | 1425769.42 | 0.179834E+09 |
December | 13689710.98 | 0.00 | 13689710.98 | 0.00 | 0.232910E+09 |
Annual Sum or Average | 0.593971E+09 | 13397980.11 | 0.580573E+09 | 0.495913E+09 | 0.165426E+10 |
Minimum of Months | 13689710.98 | 0.00 | 13689710.98 | 0.00 | 65082411.30 |
Maximum of Months | 88020373.33 | 4534392.98 | 83485980.34 | 0.108009E+09 | 0.232910E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70813818.73 | 27608988.36 | 43204830.37 | 50490355.21 | 0.377838E+09 |
February | 97872440.35 | 36429077.93 | 61443362.42 | 80373433.96 | 0.319798E+09 |
March | 0.112683E+09 | 22248080.11 | 90434959.81 | 84340820.62 | 0.289930E+09 |
April | 0.294563E+09 | 0.139438E+09 | 0.155125E+09 | 0.428499E+09 | 0.214003E+09 |
May | 0.320086E+09 | 0.140923E+09 | 0.179162E+09 | 0.450797E+09 | 0.187824E+09 |
June | 0.306080E+09 | 0.123344E+09 | 0.182735E+09 | 0.468723E+09 | 0.134691E+09 |
July | 0.322710E+09 | 0.138108E+09 | 0.184602E+09 | 0.521305E+09 | 0.125392E+09 |
August | 0.306866E+09 | 0.147954E+09 | 0.158912E+09 | 0.510669E+09 | 0.135428E+09 |
September | 0.267062E+09 | 0.142934E+09 | 0.124129E+09 | 0.426724E+09 | 0.175532E+09 |
October | 0.133190E+09 | 55737192.40 | 77453082.75 | 0.161958E+09 | 0.259818E+09 |
November | 66137150.63 | 22150671.32 | 43986479.31 | 46757048.44 | 0.318117E+09 |
December | 50436718.89 | 18367374.03 | 32069344.86 | 29566284.18 | 0.411771E+09 |
Annual Sum or Average | 0.234850E+10 | 0.101524E+10 | 0.133326E+10 | 0.326020E+10 | 0.295014E+10 |
Minimum of Months | 50436718.89 | 18367374.03 | 32069344.86 | 29566284.18 | 0.125392E+09 |
Maximum of Months | 0.322710E+09 | 0.147954E+09 | 0.184602E+09 | 0.521305E+09 | 0.411771E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 23961230.29 | 0.00 | 23961230.29 | 633839.53 | 0.293253E+09 |
February | 33795530.83 | 0.00 | 33795530.83 | 1869920.20 | 0.246738E+09 |
March | 51782573.18 | 120.30 | 51782452.88 | 15579579.64 | 0.218462E+09 |
April | 81693832.76 | 352411.51 | 81341421.25 | 69876932.97 | 0.159106E+09 |
May | 0.104757E+09 | 4361806.47 | 0.100395E+09 | 90415394.91 | 0.129175E+09 |
June | 0.111472E+09 | 5742522.61 | 0.105730E+09 | 0.135373E+09 | 92164863.40 |
July | 0.109562E+09 | 5268080.93 | 0.104294E+09 | 0.145053E+09 | 86231320.95 |
August | 86836219.63 | 1223650.01 | 85612569.62 | 0.112813E+09 | 97935047.30 |
September | 64020875.79 | 19104.61 | 64001771.17 | 68284692.91 | 0.133269E+09 |
October | 42370704.64 | 0.00 | 42370704.64 | 19488087.21 | 0.194389E+09 |
November | 24637236.82 | 0.00 | 24637236.82 | 1110127.86 | 0.243730E+09 |
December | 17337155.18 | 0.00 | 17337155.18 | 0.00 | 0.316562E+09 |
Annual Sum or Average | 0.752226E+09 | 16967696.44 | 0.735259E+09 | 0.660498E+09 | 0.221101E+10 |
Minimum of Months | 17337155.18 | 0.00 | 17337155.18 | 0.00 | 86231320.95 |
Maximum of Months | 0.111472E+09 | 5742522.61 | 0.105730E+09 | 0.145053E+09 | 0.316562E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 8833101.64 | 0.00 | 8833101.64 | 233659.50 | 0.108105E+09 |
February | 12458432.03 | 0.00 | 12458432.03 | 689330.01 | 90957886.88 |
March | 19089200.62 | 44.35 | 19089156.27 | 5743278.16 | 80534015.53 |
April | 30115729.43 | 129913.47 | 29985815.95 | 25759530.87 | 58653041.57 |
May | 38617735.72 | 1607942.47 | 37009793.25 | 33330858.37 | 47619230.63 |
June | 41093286.70 | 2116931.61 | 38976355.09 | 49904162.23 | 33975784.90 |
July | 40389021.91 | 1942032.76 | 38446989.15 | 53472538.16 | 31788435.46 |
August | 32011426.16 | 451088.06 | 31560338.10 | 41587666.09 | 36102913.60 |
September | 23600745.71 | 7042.75 | 23593702.96 | 25172565.25 | 49128459.24 |
October | 15619596.16 | 0.00 | 15619596.16 | 7184115.89 | 71659870.73 |
November | 9082305.64 | 0.00 | 9082305.64 | 409239.10 | 89848895.09 |
December | 6391193.27 | 0.00 | 6391193.27 | 0.00 | 0.116698E+09 |
Annual Sum or Average | 0.277302E+09 | 6254995.49 | 0.271047E+09 | 0.243487E+09 | 0.815072E+09 |
Minimum of Months | 6391193.27 | 0.00 | 6391193.27 | 0.00 | 31788435.46 |
Maximum of Months | 41093286.70 | 2116931.61 | 38976355.09 | 53472538.16 | 0.116698E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51693251.30 | 33935626.94 | 17757624.36 | 68453910.96 | 93326017.76 |
February | 56018979.15 | 34453099.24 | 21565879.91 | 77276209.47 | 81213901.96 |
March | 37672826.81 | 10845190.63 | 26827636.18 | 39639307.73 | 76281826.38 |
April | 73155080.29 | 31465032.50 | 41690047.79 | 0.120877E+09 | 58984731.25 |
May | 62590868.27 | 18748557.61 | 43842310.66 | 95487212.88 | 52635317.11 |
June | 55894032.07 | 11972634.84 | 43921397.23 | 91001535.32 | 37471642.28 |
July | 62019746.13 | 17456325.49 | 44563420.64 | 0.110427E+09 | 35157741.67 |
August | 73437210.12 | 31606747.84 | 41830462.28 | 0.137459E+09 | 37995362.38 |
September | 86962014.23 | 50944720.34 | 36017293.90 | 0.157035E+09 | 47869659.80 |
October | 61047244.36 | 35384279.03 | 25662965.32 | 94553058.61 | 67771718.35 |
November | 43305166.68 | 26708737.37 | 16596429.31 | 58329733.96 | 81459505.44 |
December | 35721365.97 | 23262069.58 | 12459296.38 | 45325970.56 | 0.105598E+09 |
Annual Sum or Average | 0.699518E+09 | 0.326783E+09 | 0.372735E+09 | 0.109586E+10 | 0.775765E+09 |
Minimum of Months | 35721365.97 | 10845190.63 | 12459296.38 | 39639307.73 | 35157741.67 |
Maximum of Months | 86962014.23 | 50944720.34 | 44563420.64 | 0.157035E+09 | 0.105598E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140306E+09 | 92108232.89 | 48197824.76 | 0.185798E+09 | 0.253306E+09 |
February | 0.152047E+09 | 93512758.56 | 58534209.29 | 0.209743E+09 | 0.220431E+09 |
March | 0.102252E+09 | 29436065.71 | 72815692.05 | 0.107589E+09 | 0.207044E+09 |
April | 0.198558E+09 | 85402534.24 | 0.113155E+09 | 0.328084E+09 | 0.160097E+09 |
May | 0.169884E+09 | 50887420.29 | 0.118997E+09 | 0.259172E+09 | 0.142863E+09 |
June | 0.151708E+09 | 32496179.90 | 0.119212E+09 | 0.246997E+09 | 0.101706E+09 |
July | 0.168334E+09 | 47380037.99 | 0.120954E+09 | 0.299722E+09 | 95425302.25 |
August | 0.199324E+09 | 85787178.67 | 0.113536E+09 | 0.373091E+09 | 0.103127E+09 |
September | 0.236033E+09 | 0.138274E+09 | 97758302.81 | 0.426226E+09 | 0.129928E+09 |
October | 0.165695E+09 | 96040170.99 | 69654537.13 | 0.256636E+09 | 0.183946E+09 |
November | 0.117539E+09 | 72492976.38 | 45046103.86 | 0.158319E+09 | 0.221098E+09 |
December | 96955093.87 | 63138015.00 | 33817078.88 | 0.123024E+09 | 0.286614E+09 |
Annual Sum or Average | 0.189863E+10 | 0.886956E+09 | 0.101168E+10 | 0.297440E+10 | 0.210559E+10 |
Minimum of Months | 96955093.87 | 29436065.71 | 33817078.88 | 0.107589E+09 | 95425302.25 |
Maximum of Months | 0.236033E+09 | 0.138274E+09 | 0.120954E+09 | 0.426226E+09 | 0.286614E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110788E+09 | 72730218.65 | 38057817.66 | 0.149275E+09 | 0.187663E+09 |
February | 0.120059E+09 | 73839255.87 | 46219601.72 | 0.167071E+09 | 0.165100E+09 |
March | 80739717.45 | 23243215.37 | 57496502.08 | 87631151.01 | 0.154253E+09 |
April | 0.156785E+09 | 67435285.57 | 89349352.43 | 0.253270E+09 | 0.123961E+09 |
May | 0.134144E+09 | 40181567.79 | 93962043.07 | 0.198772E+09 | 0.110281E+09 |
June | 0.119791E+09 | 25659533.30 | 94131539.98 | 0.187825E+09 | 77560047.26 |
July | 0.132920E+09 | 37412079.40 | 95507512.87 | 0.229413E+09 | 71474142.87 |
August | 0.157389E+09 | 67739007.31 | 89650286.20 | 0.287906E+09 | 76458336.13 |
September | 0.186375E+09 | 0.109184E+09 | 77191609.42 | 0.331013E+09 | 98100035.51 |
October | 0.130835E+09 | 75834943.47 | 55000400.68 | 0.201796E+09 | 0.137767E+09 |
November | 92810845.86 | 57241680.33 | 35569165.54 | 0.126530E+09 | 0.163143E+09 |
December | 76557382.06 | 49854844.58 | 26702537.48 | 99448005.60 | 0.210397E+09 |
Annual Sum or Average | 0.149919E+10 | 0.700355E+09 | 0.798838E+09 | 0.231995E+10 | 0.157616E+10 |
Minimum of Months | 76557382.06 | 23243215.37 | 26702537.48 | 87631151.01 | 71474142.87 |
Maximum of Months | 0.186375E+09 | 0.109184E+09 | 95507512.87 | 0.331013E+09 | 0.210397E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70103377.43 | 22516648.95 | 47586728.48 | 53250334.70 | 0.382088E+09 |
February | 0.112780E+09 | 47823668.68 | 64956185.94 | 0.116072E+09 | 0.326599E+09 |
March | 0.113023E+09 | 22039037.34 | 90984377.97 | 86127679.41 | 0.290397E+09 |
April | 0.258212E+09 | 0.103264E+09 | 0.154948E+09 | 0.363118E+09 | 0.225216E+09 |
May | 0.313194E+09 | 0.128480E+09 | 0.184714E+09 | 0.437816E+09 | 0.193804E+09 |
June | 0.327302E+09 | 0.135943E+09 | 0.191358E+09 | 0.506763E+09 | 0.137785E+09 |
July | 0.344336E+09 | 0.152930E+09 | 0.191406E+09 | 0.563236E+09 | 0.127458E+09 |
August | 0.289519E+09 | 0.126350E+09 | 0.163168E+09 | 0.478059E+09 | 0.138977E+09 |
September | 0.225929E+09 | 0.102563E+09 | 0.123366E+09 | 0.352252E+09 | 0.183188E+09 |
October | 0.123937E+09 | 44968258.80 | 78968371.89 | 0.145378E+09 | 0.264352E+09 |
November | 64103227.46 | 18461449.30 | 45641778.16 | 49945498.54 | 0.323714E+09 |
December | 36632118.50 | 6915842.16 | 29716276.33 | 15163538.90 | 0.422041E+09 |
Annual Sum or Average | 0.227907E+10 | 0.912255E+09 | 0.136681E+10 | 0.316718E+10 | 0.301562E+10 |
Minimum of Months | 36632118.50 | 6915842.16 | 29716276.33 | 15163538.90 | 0.127458E+09 |
Maximum of Months | 0.344336E+09 | 0.152930E+09 | 0.191406E+09 | 0.563236E+09 | 0.422041E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18920192.73 | 0.00 | 18920192.73 | 1075943.77 | 0.212680E+09 |
February | 26685522.77 | 0.00 | 26685522.77 | 2745259.86 | 0.180463E+09 |
March | 40888395.66 | 94.99 | 40888300.66 | 15188081.15 | 0.161197E+09 |
April | 64506832.14 | 278270.09 | 64228562.06 | 52433452.96 | 0.122007E+09 |
May | 82717830.29 | 3444156.17 | 79273674.12 | 66351078.28 | 99170278.38 |
June | 88020373.33 | 4534392.98 | 83485980.34 | 98593238.95 | 71031600.20 |
July | 86511862.95 | 4159765.81 | 82352097.14 | 0.104768E+09 | 66866586.56 |
August | 68567347.80 | 966214.74 | 67601133.05 | 82174383.80 | 74992103.66 |
September | 50551966.39 | 15085.32 | 50536881.07 | 51727903.83 | 0.100492E+09 |
October | 33456625.06 | 0.00 | 33456625.06 | 17318105.72 | 0.143284E+09 |
November | 19453978.92 | 0.00 | 19453978.92 | 1743075.48 | 0.176283E+09 |
December | 13689710.98 | 0.00 | 13689710.98 | 0.00 | 0.228899E+09 |
Annual Sum or Average | 0.593971E+09 | 13397980.11 | 0.580573E+09 | 0.494119E+09 | 0.163736E+10 |
Minimum of Months | 13689710.98 | 0.00 | 13689710.98 | 0.00 | 66866586.56 |
Maximum of Months | 88020373.33 | 4534392.98 | 83485980.34 | 0.104768E+09 | 0.228899E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70103377.43 | 22516648.95 | 47586728.48 | 55931065.54 | 0.378781E+09 |
February | 0.112780E+09 | 47823668.68 | 64956185.94 | 0.119901E+09 | 0.322990E+09 |
March | 0.113023E+09 | 22039037.34 | 90984377.97 | 88288838.65 | 0.288893E+09 |
April | 0.258212E+09 | 0.103264E+09 | 0.154948E+09 | 0.368243E+09 | 0.223440E+09 |
May | 0.313194E+09 | 0.128480E+09 | 0.184714E+09 | 0.439293E+09 | 0.193776E+09 |
June | 0.327302E+09 | 0.135943E+09 | 0.191358E+09 | 0.504310E+09 | 0.139599E+09 |
July | 0.344336E+09 | 0.152930E+09 | 0.191406E+09 | 0.556724E+09 | 0.131392E+09 |
August | 0.289519E+09 | 0.126350E+09 | 0.163168E+09 | 0.475303E+09 | 0.142931E+09 |
September | 0.225929E+09 | 0.102563E+09 | 0.123366E+09 | 0.356026E+09 | 0.182572E+09 |
October | 0.123937E+09 | 44968258.80 | 78968371.89 | 0.150519E+09 | 0.261106E+09 |
November | 64103227.46 | 18461449.30 | 45641778.16 | 52537009.51 | 0.320648E+09 |
December | 36632118.50 | 6915842.16 | 29716276.33 | 16159279.93 | 0.419653E+09 |
Annual Sum or Average | 0.227907E+10 | 0.912255E+09 | 0.136681E+10 | 0.318323E+10 | 0.300578E+10 |
Minimum of Months | 36632118.50 | 6915842.16 | 29716276.33 | 16159279.93 | 0.131392E+09 |
Maximum of Months | 0.344336E+09 | 0.152930E+09 | 0.191406E+09 | 0.556724E+09 | 0.419653E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162481E+09 | 0.106666E+09 | 55815442.02 | 0.211254E+09 | 0.285377E+09 |
February | 0.176078E+09 | 0.108292E+09 | 67785481.64 | 0.238418E+09 | 0.250663E+09 |
March | 0.118413E+09 | 34088406.00 | 84324138.25 | 0.123350E+09 | 0.232346E+09 |
April | 0.229940E+09 | 98900318.07 | 0.131039E+09 | 0.366763E+09 | 0.184138E+09 |
May | 0.196734E+09 | 58930125.40 | 0.137804E+09 | 0.289075E+09 | 0.162311E+09 |
June | 0.175685E+09 | 37632168.13 | 0.138053E+09 | 0.276208E+09 | 0.112474E+09 |
July | 0.194939E+09 | 54868404.89 | 0.140071E+09 | 0.337631E+09 | 0.103353E+09 |
August | 0.230827E+09 | 99345755.16 | 0.131481E+09 | 0.421851E+09 | 0.111358E+09 |
September | 0.273337E+09 | 0.160129E+09 | 0.113209E+09 | 0.481606E+09 | 0.145816E+09 |
October | 0.191883E+09 | 0.111219E+09 | 80663366.01 | 0.289759E+09 | 0.209147E+09 |
November | 0.136116E+09 | 83950417.70 | 52165594.85 | 0.179831E+09 | 0.249227E+09 |
December | 0.112279E+09 | 73116914.16 | 39161833.86 | 0.141265E+09 | 0.319323E+09 |
Annual Sum or Average | 0.219871E+10 | 0.102714E+10 | 0.117157E+10 | 0.335701E+10 | 0.236553E+10 |
Minimum of Months | 0.112279E+09 | 34088406.00 | 39161833.86 | 0.123350E+09 | 0.103353E+09 |
Maximum of Months | 0.273337E+09 | 0.160129E+09 | 0.140071E+09 | 0.481606E+09 | 0.319323E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132436E+09 | 0.00 | 0.132436E+09 | 3830775.08 | 0.157103E+10 |
February | 0.186792E+09 | 0.00 | 0.186792E+09 | 10899859.42 | 0.132889E+10 |
March | 0.286208E+09 | 664.93 | 0.286207E+09 | 86937816.22 | 0.118329E+10 |
April | 0.451531E+09 | 1947816.84 | 0.449583E+09 | 0.382426E+09 | 0.871761E+09 |
May | 0.579003E+09 | 24108180.09 | 0.554895E+09 | 0.490545E+09 | 0.722229E+09 |
June | 0.616119E+09 | 31739548.78 | 0.584380E+09 | 0.743695E+09 | 0.515381E+09 |
July | 0.605560E+09 | 29117257.85 | 0.576443E+09 | 0.809656E+09 | 0.476740E+09 |
August | 0.479953E+09 | 6763247.05 | 0.473190E+09 | 0.640778E+09 | 0.528394E+09 |
September | 0.353850E+09 | 105593.27 | 0.353745E+09 | 0.390577E+09 | 0.715968E+09 |
October | 0.234188E+09 | 0.00 | 0.234188E+09 | 0.111633E+09 | 0.105735E+10 |
November | 0.136173E+09 | 0.00 | 0.136173E+09 | 6508380.81 | 0.131973E+10 |
December | 95824347.54 | 0.00 | 95824347.54 | 0.00 | 0.171024E+10 |
Annual Sum or Average | 0.415764E+10 | 93782308.81 | 0.406385E+10 | 0.367749E+10 | 0.120010E+11 |
Minimum of Months | 95824347.54 | 0.00 | 95824347.54 | 0.00 | 0.476740E+09 |
Maximum of Months | 0.616119E+09 | 31739548.78 | 0.584380E+09 | 0.809656E+09 | 0.171024E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132436E+09 | 0.00 | 0.132436E+09 | 2733771.91 | 0.163357E+10 |
February | 0.186792E+09 | 0.00 | 0.186792E+09 | 8384992.30 | 0.138614E+10 |
March | 0.286208E+09 | 664.93 | 0.286207E+09 | 75438044.09 | 0.124014E+10 |
April | 0.451531E+09 | 1947816.84 | 0.449583E+09 | 0.361375E+09 | 0.907729E+09 |
May | 0.579003E+09 | 24108180.09 | 0.554895E+09 | 0.463572E+09 | 0.751635E+09 |
June | 0.616119E+09 | 31739548.78 | 0.584380E+09 | 0.717087E+09 | 0.536084E+09 |
July | 0.605560E+09 | 29117257.85 | 0.576443E+09 | 0.782852E+09 | 0.495775E+09 |
August | 0.479953E+09 | 6763247.05 | 0.473190E+09 | 0.618591E+09 | 0.550785E+09 |
September | 0.353850E+09 | 105593.27 | 0.353745E+09 | 0.372426E+09 | 0.746176E+09 |
October | 0.234188E+09 | 0.00 | 0.234188E+09 | 99720756.11 | 0.110926E+10 |
November | 0.136173E+09 | 0.00 | 0.136173E+09 | 4550065.06 | 0.138286E+10 |
December | 95824347.54 | 0.00 | 95824347.54 | 0.00 | 0.177472E+10 |
Annual Sum or Average | 0.415764E+10 | 93782308.81 | 0.406385E+10 | 0.350673E+10 | 0.125149E+11 |
Minimum of Months | 95824347.54 | 0.00 | 95824347.54 | 0.00 | 0.495775E+09 |
Maximum of Months | 0.616119E+09 | 31739548.78 | 0.584380E+09 | 0.782852E+09 | 0.177472E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18920192.73 | 0.00 | 18920192.73 | 20346467.54 | 0.141865E+09 |
February | 26685522.77 | 0.00 | 26685522.77 | 29917390.89 | 0.127094E+09 |
March | 40888395.66 | 94.99 | 40888300.66 | 64828210.03 | 0.116610E+09 |
April | 64506832.14 | 278270.09 | 64228562.06 | 0.131379E+09 | 95915958.62 |
May | 82717830.29 | 3444156.17 | 79273674.12 | 0.161815E+09 | 87438648.29 |
June | 88020373.33 | 4534392.98 | 83485980.34 | 0.204703E+09 | 63008646.29 |
July | 86511862.95 | 4159765.81 | 82352097.14 | 0.220244E+09 | 58463589.82 |
August | 68567347.80 | 966214.74 | 67601133.05 | 0.188092E+09 | 58668435.12 |
September | 50551966.39 | 15085.32 | 50536881.07 | 0.132903E+09 | 73277752.81 |
October | 33456625.06 | 0.00 | 33456625.06 | 70038959.93 | 0.100526E+09 |
November | 19453978.92 | 0.00 | 19453978.92 | 26563352.05 | 0.116065E+09 |
December | 13689710.98 | 0.00 | 13689710.98 | 10166208.47 | 0.156041E+09 |
Annual Sum or Average | 0.593971E+09 | 13397980.11 | 0.580573E+09 | 0.126100E+10 | 0.119497E+10 |
Minimum of Months | 13689710.98 | 0.00 | 13689710.98 | 10166208.47 | 58463589.82 |
Maximum of Months | 88020373.33 | 4534392.98 | 83485980.34 | 0.220244E+09 | 0.156041E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141618E+09 | 55214055.55 | 86403524.55 | 0.213373E+09 | 0.514931E+09 |
February | 0.195731E+09 | 72852982.01 | 0.122878E+09 | 0.296855E+09 | 0.462144E+09 |
March | 0.225350E+09 | 44493000.44 | 0.180857E+09 | 0.382775E+09 | 0.428333E+09 |
April | 0.589085E+09 | 0.278856E+09 | 0.310228E+09 | 0.118579E+10 | 0.351794E+09 |
May | 0.640126E+09 | 0.281827E+09 | 0.358299E+09 | 0.125553E+10 | 0.325030E+09 |
June | 0.612116E+09 | 0.246671E+09 | 0.365444E+09 | 0.132023E+10 | 0.234550E+09 |
July | 0.645373E+09 | 0.276195E+09 | 0.369178E+09 | 0.145769E+10 | 0.217094E+09 |
August | 0.613689E+09 | 0.295888E+09 | 0.317801E+09 | 0.142324E+10 | 0.218549E+09 |
September | 0.534087E+09 | 0.285847E+09 | 0.248240E+09 | 0.119151E+10 | 0.270865E+09 |
October | 0.266362E+09 | 0.111466E+09 | 0.154895E+09 | 0.550451E+09 | 0.372243E+09 |
November | 0.132265E+09 | 44298196.69 | 87966711.43 | 0.215386E+09 | 0.424982E+09 |
December | 0.100866E+09 | 36732139.42 | 64134135.07 | 0.132045E+09 | 0.571205E+09 |
Annual Sum or Average | 0.469667E+10 | 0.203034E+10 | 0.266632E+10 | 0.962487E+10 | 0.439172E+10 |
Minimum of Months | 0.100866E+09 | 36732139.42 | 64134135.07 | 0.132045E+09 | 0.217094E+09 |
Maximum of Months | 0.645373E+09 | 0.295888E+09 | 0.369178E+09 | 0.145769E+10 | 0.571205E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110788E+09 | 72730218.65 | 38057817.66 | 0.192436E+09 | 0.134575E+09 |
February | 0.120059E+09 | 73839255.87 | 46219601.72 | 0.213419E+09 | 0.123664E+09 |
March | 80739717.45 | 23243215.37 | 57496502.08 | 0.146723E+09 | 0.115750E+09 |
April | 0.156785E+09 | 67435285.57 | 89349352.43 | 0.338572E+09 | 97439359.36 |
May | 0.134144E+09 | 40181567.79 | 93962043.07 | 0.290752E+09 | 91604898.79 |
June | 0.119791E+09 | 25659533.30 | 94131539.98 | 0.289321E+09 | 65448833.96 |
July | 0.132920E+09 | 37412079.40 | 95507512.87 | 0.338685E+09 | 60296044.16 |
August | 0.157389E+09 | 67739007.31 | 89650286.20 | 0.392982E+09 | 59814249.15 |
September | 0.186375E+09 | 0.109184E+09 | 77191609.42 | 0.421003E+09 | 73272712.04 |
October | 0.130835E+09 | 75834943.47 | 55000400.68 | 0.266731E+09 | 99670956.57 |
November | 92810845.86 | 57241680.33 | 35569165.54 | 0.166864E+09 | 0.113295E+09 |
December | 76557382.06 | 49854844.58 | 26702537.48 | 0.126466E+09 | 0.151043E+09 |
Annual Sum or Average | 0.149919E+10 | 0.700355E+09 | 0.798838E+09 | 0.318395E+10 | 0.118587E+10 |
Minimum of Months | 76557382.06 | 23243215.37 | 26702537.48 | 0.126466E+09 | 59814249.15 |
Maximum of Months | 0.186375E+09 | 0.109184E+09 | 95507512.87 | 0.421003E+09 | 0.151043E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 23961230.29 | 0.00 | 23961230.29 | 450036.42 | 0.296169E+09 |
February | 33795530.83 | 0.00 | 33795530.83 | 1444482.00 | 0.250381E+09 |
March | 51782573.18 | 120.30 | 51782452.88 | 13607314.58 | 0.222693E+09 |
April | 81693832.76 | 352411.51 | 81341421.25 | 57719929.36 | 0.172297E+09 |
May | 0.104757E+09 | 4361806.47 | 0.100395E+09 | 72790150.28 | 0.144071E+09 |
June | 0.111472E+09 | 5742522.61 | 0.105730E+09 | 0.112668E+09 | 0.107201E+09 |
July | 0.109562E+09 | 5268080.93 | 0.104294E+09 | 0.121265E+09 | 0.101180E+09 |
August | 86836219.63 | 1223650.01 | 85612569.62 | 93187258.40 | 0.114850E+09 |
September | 64020875.79 | 19104.61 | 64001771.17 | 55342437.88 | 0.150138E+09 |
October | 42370704.64 | 0.00 | 42370704.64 | 15160819.95 | 0.204960E+09 |
November | 24637236.82 | 0.00 | 24637236.82 | 791518.44 | 0.248519E+09 |
December | 17337155.18 | 0.00 | 17337155.18 | 0.00 | 0.319314E+09 |
Annual Sum or Average | 0.752226E+09 | 16967696.44 | 0.735259E+09 | 0.544426E+09 | 0.233177E+10 |
Minimum of Months | 17337155.18 | 0.00 | 17337155.18 | 0.00 | 0.101180E+09 |
Maximum of Months | 0.111472E+09 | 5742522.61 | 0.105730E+09 | 0.121265E+09 | 0.319314E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21438203.53 | 0.00 | 21438203.53 | 402649.29 | 0.264959E+09 |
February | 30236989.48 | 0.00 | 30236989.48 | 1292383.52 | 0.224016E+09 |
March | 46330064.43 | 107.64 | 46329956.80 | 12174515.91 | 0.199244E+09 |
April | 73091781.70 | 315303.91 | 72776477.79 | 51642239.50 | 0.154155E+09 |
May | 93726406.85 | 3902524.78 | 89823882.07 | 65125623.25 | 0.128901E+09 |
June | 99734643.58 | 5137856.74 | 94596786.85 | 0.100804E+09 | 95912841.29 |
July | 98025371.75 | 4713371.97 | 93311999.79 | 0.108496E+09 | 90526005.92 |
August | 77692694.72 | 1094804.30 | 76597890.42 | 83374993.18 | 0.102757E+09 |
September | 57279720.14 | 17092.97 | 57262627.17 | 49515088.87 | 0.134329E+09 |
October | 37909229.98 | 0.00 | 37909229.98 | 13564443.05 | 0.183378E+09 |
November | 22043029.13 | 0.00 | 22043029.13 | 708174.55 | 0.222344E+09 |
December | 15511618.43 | 0.00 | 15511618.43 | 0.00 | 0.285675E+09 |
Annual Sum or Average | 0.673020E+09 | 15181062.30 | 0.657839E+09 | 0.487100E+09 | 0.208620E+10 |
Minimum of Months | 15511618.43 | 0.00 | 15511618.43 | 0.00 | 90526005.92 |
Maximum of Months | 99734643.58 | 5137856.74 | 94596786.85 | 0.108496E+09 | 0.285675E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.413605E+09 | 0.271524E+09 | 0.142081E+09 | 0.541649E+09 | 0.752975E+09 |
February | 0.448215E+09 | 0.275664E+09 | 0.172552E+09 | 0.610412E+09 | 0.657532E+09 |
March | 0.301425E+09 | 86773849.12 | 0.214652E+09 | 0.308009E+09 | 0.622028E+09 |
April | 0.585324E+09 | 0.251756E+09 | 0.333568E+09 | 0.927002E+09 | 0.509813E+09 |
May | 0.500798E+09 | 0.150010E+09 | 0.350788E+09 | 0.715559E+09 | 0.471089E+09 |
June | 0.447216E+09 | 95794683.96 | 0.351421E+09 | 0.667404E+09 | 0.351748E+09 |
July | 0.496228E+09 | 0.139670E+09 | 0.356558E+09 | 0.819388E+09 | 0.333280E+09 |
August | 0.587581E+09 | 0.252890E+09 | 0.334691E+09 | 0.104133E+10 | 0.356668E+09 |
September | 0.695795E+09 | 0.407616E+09 | 0.288179E+09 | 0.121025E+10 | 0.429850E+09 |
October | 0.488447E+09 | 0.283114E+09 | 0.205333E+09 | 0.737065E+09 | 0.570705E+09 |
November | 0.346491E+09 | 0.213700E+09 | 0.132790E+09 | 0.460091E+09 | 0.663926E+09 |
December | 0.285812E+09 | 0.186123E+09 | 99688529.36 | 0.358876E+09 | 0.853146E+09 |
Annual Sum or Average | 0.559694E+10 | 0.261464E+10 | 0.298230E+10 | 0.839704E+10 | 0.657276E+10 |
Minimum of Months | 0.285812E+09 | 86773849.12 | 99688529.36 | 0.308009E+09 | 0.333280E+09 |
Maximum of Months | 0.695795E+09 | 0.407616E+09 | 0.356558E+09 | 0.121025E+10 | 0.853146E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.00 | 358.34 | 209.21 | 137.34 | 71.87 | 0.00 | 0.00 |
February | 345.72 | 345.89 | 251.00 | 154.37 | 96.63 | 0.00 | 0.00 |
March | 162.90 | 292.23 | 152.46 | 43.89 | 108.57 | 0.00 | 0.00 |
April | 495.36 | 242.63 | 305.93 | 131.59 | 174.34 | 0.00 | 0.00 |
May | 379.91 | 207.80 | 253.31 | 75.88 | 177.43 | 0.00 | 0.00 |
June | 370.74 | 156.56 | 233.74 | 50.07 | 183.68 | 0.00 | 0.00 |
July | 433.38 | 145.25 | 251.00 | 70.65 | 180.35 | 0.00 | 0.00 |
August | 540.10 | 159.84 | 297.20 | 127.91 | 169.29 | 0.00 | 0.00 |
September | 641.56 | 204.07 | 363.67 | 213.05 | 150.62 | 0.00 | 0.00 |
October | 377.32 | 265.14 | 247.06 | 143.20 | 103.86 | 0.00 | 0.00 |
November | 243.96 | 323.18 | 181.10 | 111.69 | 69.41 | 0.00 | 0.00 |
December | 184.87 | 401.33 | 144.57 | 94.14 | 50.42 | 0.00 | 0.00 |
Annual Sum or Average | 370.54 | 258.10 | 240.44 | 112.32 | 128.12 | 0.00 | 0.00 |
Minimum of Months | 162.90 | 145.25 | 144.57 | 43.89 | 50.42 | 0.00 | 0.00 |
Maximum of Months | 641.56 | 401.33 | 363.67 | 213.05 | 183.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 776.70 | 1007.67 | 589.11 | 386.74 | 202.37 | 0.00 | 0.00 |
February | 970.91 | 972.34 | 706.81 | 434.70 | 272.10 | 0.00 | 0.00 |
March | 451.53 | 823.33 | 429.33 | 123.59 | 305.73 | 0.00 | 0.00 |
April | 1406.89 | 670.25 | 861.48 | 370.54 | 490.94 | 0.00 | 0.00 |
May | 1082.01 | 571.86 | 713.30 | 213.66 | 499.63 | 0.00 | 0.00 |
June | 1069.33 | 418.64 | 658.21 | 140.99 | 517.22 | 0.00 | 0.00 |
July | 1256.45 | 379.28 | 706.79 | 198.94 | 507.85 | 0.00 | 0.00 |
August | 1558.70 | 414.67 | 836.90 | 360.20 | 476.71 | 0.00 | 0.00 |
September | 1832.24 | 545.95 | 1024.07 | 599.93 | 424.14 | 0.00 | 0.00 |
October | 1066.94 | 743.39 | 695.71 | 403.25 | 292.46 | 0.00 | 0.00 |
November | 684.24 | 914.00 | 509.97 | 314.53 | 195.44 | 0.00 | 0.00 |
December | 516.58 | 1132.21 | 407.09 | 265.10 | 141.99 | 0.00 | 0.00 |
Annual Sum or Average | 1054.64 | 714.89 | 677.06 | 316.29 | 360.77 | 0.00 | 0.00 |
Minimum of Months | 451.53 | 379.28 | 407.09 | 123.59 | 141.99 | 0.00 | 0.00 |
Maximum of Months | 1832.24 | 1132.21 | 1024.07 | 599.93 | 517.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1011.53 | 1397.16 | 765.28 | 502.40 | 262.89 | 0.00 | 0.00 |
February | 1265.39 | 1345.83 | 918.18 | 564.71 | 353.47 | 0.00 | 0.00 |
March | 584.81 | 1154.08 | 557.72 | 160.56 | 397.16 | 0.00 | 0.00 |
April | 1836.39 | 938.32 | 1119.11 | 481.35 | 637.76 | 0.00 | 0.00 |
May | 1405.41 | 811.03 | 926.61 | 277.56 | 649.05 | 0.00 | 0.00 |
June | 1380.65 | 603.92 | 855.05 | 183.16 | 671.90 | 0.00 | 0.00 |
July | 1624.88 | 549.45 | 918.16 | 258.43 | 659.73 | 0.00 | 0.00 |
August | 2025.99 | 596.13 | 1087.19 | 467.92 | 619.27 | 0.00 | 0.00 |
September | 2389.88 | 770.56 | 1330.33 | 779.34 | 550.98 | 0.00 | 0.00 |
October | 1389.73 | 1045.21 | 903.76 | 523.84 | 379.92 | 0.00 | 0.00 |
November | 889.19 | 1276.35 | 662.47 | 408.59 | 253.89 | 0.00 | 0.00 |
December | 671.03 | 1567.76 | 528.83 | 344.38 | 184.45 | 0.00 | 0.00 |
Annual Sum or Average | 1371.04 | 1003.02 | 879.54 | 410.88 | 468.66 | 0.00 | 0.00 |
Minimum of Months | 584.81 | 549.45 | 528.83 | 160.56 | 184.45 | 0.00 | 0.00 |
Maximum of Months | 2389.88 | 1567.76 | 1330.33 | 779.34 | 671.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.65 | 208.98 | 67.54 | 35.56 | 31.98 | 0.00 | 0.00 |
February | 112.50 | 201.92 | 96.25 | 50.29 | 45.96 | 0.00 | 0.00 |
March | 62.95 | 167.13 | 72.34 | 16.91 | 55.44 | 0.00 | 0.00 |
April | 238.81 | 134.21 | 160.11 | 65.86 | 94.25 | 0.00 | 0.00 |
May | 238.70 | 112.24 | 167.02 | 62.97 | 104.05 | 0.00 | 0.00 |
June | 270.64 | 82.55 | 172.49 | 62.35 | 110.14 | 0.00 | 0.00 |
July | 298.59 | 73.84 | 178.19 | 71.07 | 107.12 | 0.00 | 0.00 |
August | 288.25 | 80.72 | 166.86 | 72.46 | 94.39 | 0.00 | 0.00 |
September | 264.41 | 108.71 | 159.07 | 81.69 | 77.38 | 0.00 | 0.00 |
October | 127.92 | 150.85 | 95.12 | 45.10 | 50.02 | 0.00 | 0.00 |
November | 63.34 | 186.95 | 60.54 | 29.21 | 31.33 | 0.00 | 0.00 |
December | 35.75 | 233.03 | 42.26 | 21.20 | 21.06 | 0.00 | 0.00 |
Annual Sum or Average | 172.55 | 144.81 | 119.81 | 51.14 | 68.67 | 0.00 | 0.00 |
Minimum of Months | 35.75 | 73.84 | 42.26 | 16.91 | 21.06 | 0.00 | 0.00 |
Maximum of Months | 298.59 | 233.03 | 178.19 | 81.69 | 110.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.00 | 221.83 | 33.24 | 8.41 | 24.83 | 0.00 | 0.00 |
February | 47.67 | 208.83 | 57.65 | 19.77 | 37.88 | 0.00 | 0.00 |
March | 36.63 | 169.34 | 57.46 | 8.23 | 49.24 | 0.00 | 0.00 |
April | 163.44 | 133.10 | 124.51 | 39.95 | 84.56 | 0.00 | 0.00 |
May | 190.96 | 108.83 | 147.82 | 49.25 | 98.56 | 0.00 | 0.00 |
June | 235.67 | 79.95 | 160.23 | 54.20 | 106.04 | 0.00 | 0.00 |
July | 250.60 | 72.49 | 160.86 | 58.65 | 102.21 | 0.00 | 0.00 |
August | 211.13 | 80.82 | 133.69 | 47.53 | 86.16 | 0.00 | 0.00 |
September | 158.05 | 109.44 | 106.67 | 39.57 | 67.09 | 0.00 | 0.00 |
October | 61.47 | 152.89 | 58.76 | 16.79 | 41.97 | 0.00 | 0.00 |
November | 19.06 | 194.08 | 32.24 | 7.12 | 25.11 | 0.00 | 0.00 |
December | 4.71 | 244.77 | 18.79 | 2.58 | 16.21 | 0.00 | 0.00 |
Annual Sum or Average | 116.71 | 147.74 | 91.10 | 29.35 | 61.75 | 0.00 | 0.00 |
Minimum of Months | 4.71 | 72.49 | 18.79 | 2.58 | 16.21 | 0.00 | 0.00 |
Maximum of Months | 250.60 | 244.77 | 160.86 | 58.65 | 106.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.33 | 66.78 | 33.08 | 21.72 | 11.37 | 0.00 | 0.00 |
February | 52.01 | 64.36 | 39.69 | 24.41 | 15.28 | 0.00 | 0.00 |
March | 23.76 | 52.43 | 24.11 | 6.94 | 17.17 | 0.00 | 0.00 |
April | 71.23 | 52.00 | 48.38 | 20.81 | 27.57 | 0.00 | 0.00 |
May | 51.68 | 47.57 | 40.06 | 12.00 | 28.06 | 0.00 | 0.00 |
June | 49.55 | 37.01 | 36.97 | 7.92 | 29.05 | 0.00 | 0.00 |
July | 60.04 | 34.04 | 39.69 | 11.17 | 28.52 | 0.00 | 0.00 |
August | 77.98 | 36.47 | 47.00 | 20.23 | 26.77 | 0.00 | 0.00 |
September | 94.31 | 45.36 | 57.51 | 33.69 | 23.82 | 0.00 | 0.00 |
October | 54.38 | 58.22 | 39.07 | 22.65 | 16.42 | 0.00 | 0.00 |
November | 35.60 | 64.50 | 28.64 | 17.66 | 10.98 | 0.00 | 0.00 |
December | 29.50 | 62.54 | 22.86 | 14.89 | 7.97 | 0.00 | 0.00 |
Annual Sum or Average | 53.36 | 51.69 | 38.02 | 17.76 | 20.26 | 0.00 | 0.00 |
Minimum of Months | 23.76 | 34.04 | 22.86 | 6.94 | 7.97 | 0.00 | 0.00 |
Maximum of Months | 94.31 | 66.78 | 57.51 | 33.69 | 29.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.16 | 67.93 | 5.65 | 0.00 | 5.65 | 0.00 | 0.00 |
February | 0.55 | 63.34 | 8.83 | 0.00 | 8.83 | 0.00 | 0.00 |
March | 3.63 | 51.22 | 12.21 | 0.00 | 12.21 | 0.00 | 0.00 |
April | 16.79 | 38.34 | 19.91 | 0.09 | 19.83 | 0.00 | 0.00 |
May | 20.95 | 29.93 | 24.71 | 1.03 | 23.68 | 0.00 | 0.00 |
June | 32.68 | 21.59 | 27.17 | 1.40 | 25.77 | 0.00 | 0.00 |
July | 34.10 | 19.31 | 25.84 | 1.24 | 24.60 | 0.00 | 0.00 |
August | 26.75 | 21.70 | 20.48 | 0.29 | 20.19 | 0.00 | 0.00 |
September | 16.85 | 30.99 | 15.60 | 0.00 | 15.60 | 0.00 | 0.00 |
October | 4.64 | 45.36 | 9.99 | 0.00 | 9.99 | 0.00 | 0.00 |
November | 0.28 | 58.69 | 6.01 | 0.00 | 6.01 | 0.00 | 0.00 |
December | 0.00 | 73.32 | 4.09 | 0.00 | 4.09 | 0.00 | 0.00 |
Annual Sum or Average | 13.18 | 43.38 | 15.07 | 0.34 | 14.73 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 19.31 | 4.09 | 0.00 | 4.09 | 0.00 | 0.00 |
Maximum of Months | 34.10 | 73.32 | 27.17 | 1.40 | 25.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.44 | 207.77 | 67.80 | 37.46 | 30.34 | 0.00 | 0.00 |
February | 97.10 | 198.92 | 90.08 | 45.58 | 44.50 | 0.00 | 0.00 |
March | 61.94 | 165.99 | 72.22 | 16.98 | 55.23 | 0.00 | 0.00 |
April | 257.83 | 128.34 | 174.13 | 79.81 | 94.32 | 0.00 | 0.00 |
May | 238.63 | 108.70 | 169.59 | 67.62 | 101.97 | 0.00 | 0.00 |
June | 252.26 | 79.82 | 164.30 | 57.49 | 106.82 | 0.00 | 0.00 |
July | 279.82 | 71.15 | 170.11 | 65.53 | 104.58 | 0.00 | 0.00 |
August | 296.79 | 76.78 | 173.33 | 80.53 | 92.80 | 0.00 | 0.00 |
September | 288.64 | 104.53 | 174.94 | 97.27 | 77.67 | 0.00 | 0.00 |
October | 132.67 | 149.33 | 98.58 | 49.12 | 49.45 | 0.00 | 0.00 |
November | 63.25 | 185.46 | 61.32 | 30.63 | 30.69 | 0.00 | 0.00 |
December | 43.90 | 231.06 | 47.41 | 25.47 | 21.94 | 0.00 | 0.00 |
Annual Sum or Average | 173.52 | 142.05 | 122.01 | 54.40 | 67.61 | 0.00 | 0.00 |
Minimum of Months | 43.90 | 71.15 | 47.41 | 16.98 | 21.94 | 0.00 | 0.00 |
Maximum of Months | 296.79 | 231.06 | 174.94 | 97.27 | 106.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.24 | 217.98 | 33.50 | 10.31 | 23.19 | 0.00 | 0.00 |
February | 30.52 | 204.15 | 51.49 | 15.06 | 36.43 | 0.00 | 0.00 |
March | 35.13 | 167.70 | 57.34 | 8.31 | 49.03 | 0.00 | 0.00 |
April | 182.16 | 127.00 | 138.53 | 53.90 | 84.63 | 0.00 | 0.00 |
May | 191.65 | 105.50 | 150.39 | 53.90 | 96.49 | 0.00 | 0.00 |
June | 218.95 | 78.04 | 152.04 | 49.34 | 102.71 | 0.00 | 0.00 |
July | 234.16 | 70.32 | 152.79 | 53.12 | 99.67 | 0.00 | 0.00 |
August | 220.77 | 77.26 | 140.17 | 55.60 | 84.57 | 0.00 | 0.00 |
September | 181.27 | 104.01 | 122.54 | 55.15 | 67.39 | 0.00 | 0.00 |
October | 64.26 | 149.27 | 62.22 | 20.81 | 41.41 | 0.00 | 0.00 |
November | 15.72 | 189.25 | 33.02 | 8.55 | 24.48 | 0.00 | 0.00 |
December | 7.58 | 237.24 | 23.94 | 6.86 | 17.08 | 0.00 | 0.00 |
Annual Sum or Average | 116.80 | 143.69 | 93.31 | 32.62 | 60.69 | 0.00 | 0.00 |
Minimum of Months | 7.58 | 70.32 | 23.94 | 6.86 | 17.08 | 0.00 | 0.00 |
Maximum of Months | 234.16 | 237.24 | 152.79 | 55.60 | 102.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.31 | 265.33 | 83.93 | 47.06 | 36.87 | 0.00 | 0.00 |
February | 110.88 | 255.46 | 105.13 | 52.90 | 52.23 | 0.00 | 0.00 |
March | 60.77 | 215.26 | 78.70 | 15.04 | 63.66 | 0.00 | 0.00 |
April | 209.67 | 168.10 | 147.96 | 45.27 | 102.69 | 0.00 | 0.00 |
May | 176.67 | 137.06 | 140.33 | 28.23 | 112.10 | 0.00 | 0.00 |
June | 199.48 | 99.96 | 138.95 | 20.19 | 118.77 | 0.00 | 0.00 |
July | 225.18 | 90.74 | 141.99 | 26.90 | 115.09 | 0.00 | 0.00 |
August | 247.76 | 102.23 | 146.21 | 44.46 | 101.75 | 0.00 | 0.00 |
September | 260.30 | 138.18 | 158.42 | 73.01 | 85.41 | 0.00 | 0.00 |
October | 138.45 | 190.68 | 106.31 | 49.07 | 57.24 | 0.00 | 0.00 |
November | 76.49 | 237.74 | 75.06 | 38.27 | 36.79 | 0.00 | 0.00 |
December | 52.16 | 297.50 | 58.39 | 32.26 | 26.14 | 0.00 | 0.00 |
Annual Sum or Average | 153.24 | 182.84 | 115.03 | 39.22 | 75.81 | 0.00 | 0.00 |
Minimum of Months | 52.16 | 90.74 | 58.39 | 15.04 | 26.14 | 0.00 | 0.00 |
Maximum of Months | 260.30 | 297.50 | 158.42 | 73.01 | 118.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 68.31 | 205.41 | 67.54 | 35.56 | 31.98 | 0.00 | 0.00 |
February | 112.90 | 199.11 | 96.25 | 50.29 | 45.96 | 0.00 | 0.00 |
March | 63.35 | 164.49 | 72.34 | 16.91 | 55.44 | 0.00 | 0.00 |
April | 236.18 | 133.08 | 160.11 | 65.86 | 94.25 | 0.00 | 0.00 |
May | 235.68 | 111.54 | 167.02 | 62.97 | 104.05 | 0.00 | 0.00 |
June | 266.99 | 82.10 | 172.49 | 62.35 | 110.14 | 0.00 | 0.00 |
July | 294.97 | 73.31 | 178.19 | 71.07 | 107.12 | 0.00 | 0.00 |
August | 285.30 | 79.75 | 166.86 | 72.46 | 94.39 | 0.00 | 0.00 |
September | 262.48 | 107.39 | 159.07 | 81.69 | 77.38 | 0.00 | 0.00 |
October | 127.79 | 148.30 | 95.12 | 45.10 | 50.02 | 0.00 | 0.00 |
November | 63.83 | 183.57 | 60.54 | 29.21 | 31.33 | 0.00 | 0.00 |
December | 36.19 | 229.53 | 42.26 | 21.20 | 21.06 | 0.00 | 0.00 |
Annual Sum or Average | 171.25 | 142.85 | 119.81 | 51.14 | 68.67 | 0.00 | 0.00 |
Minimum of Months | 36.19 | 73.31 | 42.26 | 16.91 | 21.06 | 0.00 | 0.00 |
Maximum of Months | 294.97 | 229.53 | 178.19 | 81.69 | 110.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.45 | 217.99 | 33.24 | 8.41 | 24.83 | 0.00 | 0.00 |
February | 48.20 | 205.61 | 57.65 | 19.77 | 37.88 | 0.00 | 0.00 |
March | 37.15 | 166.56 | 57.46 | 8.23 | 49.24 | 0.00 | 0.00 |
April | 160.99 | 131.97 | 124.51 | 39.95 | 84.56 | 0.00 | 0.00 |
May | 187.76 | 108.34 | 147.82 | 49.25 | 98.56 | 0.00 | 0.00 |
June | 231.36 | 80.02 | 160.23 | 54.20 | 106.04 | 0.00 | 0.00 |
July | 245.84 | 72.89 | 160.86 | 58.65 | 102.21 | 0.00 | 0.00 |
August | 207.52 | 80.74 | 133.69 | 47.53 | 86.16 | 0.00 | 0.00 |
September | 156.41 | 108.30 | 106.67 | 39.57 | 67.09 | 0.00 | 0.00 |
October | 61.70 | 150.02 | 58.76 | 16.79 | 41.97 | 0.00 | 0.00 |
November | 19.57 | 190.35 | 32.24 | 7.12 | 25.11 | 0.00 | 0.00 |
December | 4.90 | 241.00 | 18.79 | 2.58 | 16.21 | 0.00 | 0.00 |
Annual Sum or Average | 115.24 | 145.86 | 91.10 | 29.35 | 61.75 | 0.00 | 0.00 |
Minimum of Months | 4.90 | 72.89 | 18.79 | 2.58 | 16.21 | 0.00 | 0.00 |
Maximum of Months | 245.84 | 241.00 | 160.86 | 58.65 | 106.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 78.87 | 106.55 | 60.66 | 39.82 | 20.84 | 0.00 | 0.00 |
February | 98.55 | 103.61 | 72.78 | 44.76 | 28.02 | 0.00 | 0.00 |
March | 46.05 | 86.75 | 44.21 | 12.73 | 31.48 | 0.00 | 0.00 |
April | 141.50 | 71.04 | 88.71 | 38.16 | 50.56 | 0.00 | 0.00 |
May | 107.93 | 60.60 | 73.45 | 22.00 | 51.45 | 0.00 | 0.00 |
June | 106.56 | 43.39 | 67.78 | 14.52 | 53.26 | 0.00 | 0.00 |
July | 126.06 | 38.59 | 72.78 | 20.49 | 52.30 | 0.00 | 0.00 |
August | 157.50 | 41.58 | 86.18 | 37.09 | 49.09 | 0.00 | 0.00 |
September | 185.80 | 56.26 | 105.45 | 61.78 | 43.68 | 0.00 | 0.00 |
October | 108.18 | 78.09 | 71.64 | 41.52 | 30.12 | 0.00 | 0.00 |
November | 69.38 | 96.15 | 52.51 | 32.39 | 20.13 | 0.00 | 0.00 |
December | 52.74 | 119.22 | 41.92 | 27.30 | 14.62 | 0.00 | 0.00 |
Annual Sum or Average | 106.45 | 75.01 | 69.72 | 32.57 | 37.15 | 0.00 | 0.00 |
Minimum of Months | 46.05 | 38.59 | 41.92 | 12.73 | 14.62 | 0.00 | 0.00 |
Maximum of Months | 185.80 | 119.22 | 105.45 | 61.78 | 53.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.43 | 586.56 | 49.45 | 0.00 | 49.45 | 0.00 | 0.00 |
February | 4.51 | 549.31 | 77.21 | 0.00 | 77.21 | 0.00 | 0.00 |
March | 32.46 | 441.79 | 106.86 | 0.00 | 106.86 | 0.00 | 0.00 |
April | 147.54 | 336.33 | 174.20 | 0.75 | 173.45 | 0.00 | 0.00 |
May | 183.15 | 269.65 | 216.17 | 9.00 | 207.17 | 0.00 | 0.00 |
June | 286.92 | 198.84 | 237.70 | 12.25 | 225.46 | 0.00 | 0.00 |
July | 302.29 | 177.99 | 226.09 | 10.87 | 215.22 | 0.00 | 0.00 |
August | 239.24 | 197.28 | 179.19 | 2.53 | 176.67 | 0.00 | 0.00 |
September | 150.69 | 276.22 | 136.52 | 0.04 | 136.48 | 0.00 | 0.00 |
October | 41.68 | 394.77 | 87.44 | 0.00 | 87.44 | 0.00 | 0.00 |
November | 2.51 | 509.15 | 52.54 | 0.00 | 52.54 | 0.00 | 0.00 |
December | 0.00 | 638.53 | 35.78 | 0.00 | 35.78 | 0.00 | 0.00 |
Annual Sum or Average | 116.61 | 380.55 | 131.84 | 2.97 | 128.86 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 177.99 | 35.78 | 0.00 | 35.78 | 0.00 | 0.00 |
Maximum of Months | 302.29 | 638.53 | 237.70 | 12.25 | 225.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.02 | 609.91 | 49.45 | 0.00 | 49.45 | 0.00 | 0.00 |
February | 3.47 | 572.98 | 77.21 | 0.00 | 77.21 | 0.00 | 0.00 |
March | 28.17 | 463.02 | 106.86 | 0.00 | 106.86 | 0.00 | 0.00 |
April | 139.42 | 350.20 | 174.20 | 0.75 | 173.45 | 0.00 | 0.00 |
May | 173.08 | 280.63 | 216.17 | 9.00 | 207.17 | 0.00 | 0.00 |
June | 276.65 | 206.82 | 237.70 | 12.25 | 225.46 | 0.00 | 0.00 |
July | 292.28 | 185.10 | 226.09 | 10.87 | 215.22 | 0.00 | 0.00 |
August | 230.96 | 205.64 | 179.19 | 2.53 | 176.67 | 0.00 | 0.00 |
September | 143.68 | 287.88 | 136.52 | 0.04 | 136.48 | 0.00 | 0.00 |
October | 37.23 | 414.15 | 87.44 | 0.00 | 87.44 | 0.00 | 0.00 |
November | 1.76 | 533.51 | 52.54 | 0.00 | 52.54 | 0.00 | 0.00 |
December | 0.00 | 662.61 | 35.78 | 0.00 | 35.78 | 0.00 | 0.00 |
Annual Sum or Average | 111.20 | 396.84 | 131.84 | 2.97 | 128.86 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 185.10 | 35.78 | 0.00 | 35.78 | 0.00 | 0.00 |
Maximum of Months | 292.28 | 662.61 | 237.70 | 12.25 | 225.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 154.43 | 290.79 | 101.30 | 47.77 | 53.53 | 0.00 | 0.00 |
February | 221.61 | 293.00 | 141.57 | 60.64 | 80.93 | 0.00 | 0.00 |
March | 221.06 | 245.84 | 129.55 | 25.29 | 104.26 | 0.00 | 0.00 |
April | 636.73 | 208.27 | 312.65 | 133.71 | 178.94 | 0.00 | 0.00 |
May | 635.88 | 186.35 | 319.96 | 121.51 | 198.45 | 0.00 | 0.00 |
June | 699.06 | 139.16 | 316.33 | 106.82 | 209.51 | 0.00 | 0.00 |
July | 752.26 | 124.73 | 322.88 | 118.64 | 204.24 | 0.00 | 0.00 |
August | 747.69 | 125.20 | 313.49 | 136.12 | 177.36 | 0.00 | 0.00 |
September | 672.62 | 160.27 | 297.46 | 152.41 | 145.05 | 0.00 | 0.00 |
October | 330.62 | 213.10 | 160.79 | 69.93 | 90.86 | 0.00 | 0.00 |
November | 156.36 | 251.09 | 94.34 | 39.17 | 55.17 | 0.00 | 0.00 |
December | 97.82 | 325.42 | 71.35 | 32.33 | 39.03 | 0.00 | 0.00 |
Annual Sum or Average | 444.60 | 213.21 | 215.30 | 87.01 | 128.29 | 0.00 | 0.00 |
Minimum of Months | 97.82 | 124.73 | 71.35 | 25.29 | 39.03 | 0.00 | 0.00 |
Maximum of Months | 752.26 | 325.42 | 322.88 | 152.41 | 209.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.71 | 469.79 | 171.37 | 101.38 | 70.00 | 0.00 | 0.00 |
February | 239.65 | 454.09 | 211.74 | 113.95 | 97.79 | 0.00 | 0.00 |
March | 121.13 | 386.28 | 149.17 | 32.40 | 116.77 | 0.00 | 0.00 |
April | 398.95 | 321.75 | 285.54 | 97.39 | 188.15 | 0.00 | 0.00 |
May | 315.47 | 274.62 | 261.08 | 59.09 | 201.99 | 0.00 | 0.00 |
June | 334.94 | 209.17 | 254.02 | 41.16 | 212.87 | 0.00 | 0.00 |
July | 387.60 | 191.90 | 262.77 | 55.87 | 206.90 | 0.00 | 0.00 |
August | 453.96 | 213.66 | 280.81 | 95.28 | 185.52 | 0.00 | 0.00 |
September | 505.75 | 273.96 | 315.24 | 157.27 | 157.96 | 0.00 | 0.00 |
October | 281.42 | 353.58 | 212.34 | 105.70 | 106.64 | 0.00 | 0.00 |
November | 166.19 | 425.91 | 151.69 | 82.45 | 69.24 | 0.00 | 0.00 |
December | 118.03 | 528.45 | 118.97 | 69.49 | 49.48 | 0.00 | 0.00 |
Annual Sum or Average | 291.85 | 341.38 | 222.67 | 83.93 | 138.74 | 0.00 | 0.00 |
Minimum of Months | 118.03 | 191.90 | 118.97 | 32.40 | 49.48 | 0.00 | 0.00 |
Maximum of Months | 505.75 | 528.45 | 315.24 | 157.27 | 212.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.741925E+09 | 0.959775E+09 | 0.560335E+09 | 0.367850E+09 | 0.192485E+09 | 0.00 | 0.00 |
February | 0.836360E+09 | 0.836772E+09 | 0.607224E+09 | 0.373459E+09 | 0.233765E+09 | 0.00 | 0.00 |
March | 0.436321E+09 | 0.782705E+09 | 0.408358E+09 | 0.117558E+09 | 0.290800E+09 | 0.00 | 0.00 |
April | 0.128398E+10 | 0.628905E+09 | 0.792971E+09 | 0.341069E+09 | 0.451901E+09 | 0.00 | 0.00 |
May | 0.101754E+10 | 0.556563E+09 | 0.678458E+09 | 0.203228E+09 | 0.475230E+09 | 0.00 | 0.00 |
June | 0.960959E+09 | 0.405811E+09 | 0.605866E+09 | 0.129779E+09 | 0.476087E+09 | 0.00 | 0.00 |
July | 0.116076E+10 | 0.389027E+09 | 0.672267E+09 | 0.189220E+09 | 0.483046E+09 | 0.00 | 0.00 |
August | 0.144659E+10 | 0.428128E+09 | 0.796028E+09 | 0.342606E+09 | 0.453423E+09 | 0.00 | 0.00 |
September | 0.166293E+10 | 0.528948E+09 | 0.942633E+09 | 0.552222E+09 | 0.390411E+09 | 0.00 | 0.00 |
October | 0.101062E+10 | 0.710160E+09 | 0.661728E+09 | 0.383553E+09 | 0.278176E+09 | 0.00 | 0.00 |
November | 0.632340E+09 | 0.837686E+09 | 0.469411E+09 | 0.289513E+09 | 0.179898E+09 | 0.00 | 0.00 |
December | 0.495149E+09 | 0.107492E+10 | 0.387206E+09 | 0.252152E+09 | 0.135054E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116855E+11 | 0.813940E+10 | 0.758249E+10 | 0.354221E+10 | 0.404028E+10 | 0.00 | 0.00 |
Minimum of Months | 0.436321E+09 | 0.389027E+09 | 0.387206E+09 | 0.117558E+09 | 0.135054E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166293E+10 | 0.107492E+10 | 0.942633E+09 | 0.552222E+09 | 0.483046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.208031E+10 | 0.269895E+10 | 0.157787E+10 | 0.103584E+10 | 0.542026E+09 | 0.00 | 0.00 |
February | 0.234882E+10 | 0.235228E+10 | 0.170990E+10 | 0.105164E+10 | 0.658267E+09 | 0.00 | 0.00 |
March | 0.120938E+10 | 0.220519E+10 | 0.114991E+10 | 0.331035E+09 | 0.818874E+09 | 0.00 | 0.00 |
April | 0.364666E+10 | 0.173730E+10 | 0.223295E+10 | 0.960429E+09 | 0.127252E+10 | 0.00 | 0.00 |
May | 0.289804E+10 | 0.153168E+10 | 0.191049E+10 | 0.572275E+09 | 0.133822E+10 | 0.00 | 0.00 |
June | 0.277171E+10 | 0.108513E+10 | 0.170608E+10 | 0.365449E+09 | 0.134063E+10 | 0.00 | 0.00 |
July | 0.336528E+10 | 0.101585E+10 | 0.189306E+10 | 0.532832E+09 | 0.136023E+10 | 0.00 | 0.00 |
August | 0.417481E+10 | 0.111065E+10 | 0.224156E+10 | 0.964755E+09 | 0.127681E+10 | 0.00 | 0.00 |
September | 0.474917E+10 | 0.141509E+10 | 0.265439E+10 | 0.155502E+10 | 0.109937E+10 | 0.00 | 0.00 |
October | 0.285770E+10 | 0.199110E+10 | 0.186338E+10 | 0.108006E+10 | 0.783324E+09 | 0.00 | 0.00 |
November | 0.177355E+10 | 0.236908E+10 | 0.132183E+10 | 0.815249E+09 | 0.506582E+09 | 0.00 | 0.00 |
December | 0.138361E+10 | 0.303251E+10 | 0.109035E+10 | 0.710044E+09 | 0.380302E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.332590E+11 | 0.225448E+11 | 0.213518E+11 | 0.997463E+10 | 0.113772E+11 | 0.00 | 0.00 |
Minimum of Months | 0.120938E+10 | 0.101585E+10 | 0.109035E+10 | 0.331035E+09 | 0.380302E+09 | 0.00 | 0.00 |
Maximum of Months | 0.474917E+10 | 0.303251E+10 | 0.265439E+10 | 0.155502E+10 | 0.136023E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.270929E+10 | 0.374215E+10 | 0.204974E+10 | 0.134562E+10 | 0.704123E+09 | 0.00 | 0.00 |
February | 0.306122E+10 | 0.325583E+10 | 0.222126E+10 | 0.136613E+10 | 0.855126E+09 | 0.00 | 0.00 |
March | 0.156635E+10 | 0.309108E+10 | 0.149380E+10 | 0.430034E+09 | 0.106376E+10 | 0.00 | 0.00 |
April | 0.475993E+10 | 0.243213E+10 | 0.290073E+10 | 0.124765E+10 | 0.165308E+10 | 0.00 | 0.00 |
May | 0.376424E+10 | 0.217225E+10 | 0.248184E+10 | 0.743418E+09 | 0.173842E+10 | 0.00 | 0.00 |
June | 0.357865E+10 | 0.156535E+10 | 0.221629E+10 | 0.474739E+09 | 0.174156E+10 | 0.00 | 0.00 |
July | 0.435207E+10 | 0.147165E+10 | 0.245919E+10 | 0.692179E+09 | 0.176701E+10 | 0.00 | 0.00 |
August | 0.542642E+10 | 0.159667E+10 | 0.291192E+10 | 0.125327E+10 | 0.165865E+10 | 0.00 | 0.00 |
September | 0.619456E+10 | 0.199730E+10 | 0.344821E+10 | 0.202006E+10 | 0.142815E+10 | 0.00 | 0.00 |
October | 0.372225E+10 | 0.279948E+10 | 0.242064E+10 | 0.140306E+10 | 0.101758E+10 | 0.00 | 0.00 |
November | 0.230477E+10 | 0.330830E+10 | 0.171713E+10 | 0.105906E+10 | 0.658079E+09 | 0.00 | 0.00 |
December | 0.179728E+10 | 0.419910E+10 | 0.141642E+10 | 0.922388E+09 | 0.494034E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.432370E+11 | 0.316313E+11 | 0.277372E+11 | 0.129576E+11 | 0.147796E+11 | 0.00 | 0.00 |
Minimum of Months | 0.156635E+10 | 0.147165E+10 | 0.141642E+10 | 0.430034E+09 | 0.494034E+09 | 0.00 | 0.00 |
Maximum of Months | 0.619456E+10 | 0.419910E+10 | 0.344821E+10 | 0.202006E+10 | 0.176701E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181204E+09 | 0.559723E+09 | 0.180891E+09 | 95246867.60 | 85644546.14 | 0.00 | 0.00 |
February | 0.272163E+09 | 0.488490E+09 | 0.232839E+09 | 0.121663E+09 | 0.111176E+09 | 0.00 | 0.00 |
March | 0.168593E+09 | 0.447637E+09 | 0.193763E+09 | 45282252.72 | 0.148481E+09 | 0.00 | 0.00 |
April | 0.619005E+09 | 0.347872E+09 | 0.414996E+09 | 0.170699E+09 | 0.244297E+09 | 0.00 | 0.00 |
May | 0.639335E+09 | 0.300631E+09 | 0.447338E+09 | 0.168661E+09 | 0.278677E+09 | 0.00 | 0.00 |
June | 0.701501E+09 | 0.213968E+09 | 0.447093E+09 | 0.161603E+09 | 0.285490E+09 | 0.00 | 0.00 |
July | 0.799753E+09 | 0.197760E+09 | 0.477255E+09 | 0.190342E+09 | 0.286913E+09 | 0.00 | 0.00 |
August | 0.772060E+09 | 0.216196E+09 | 0.446908E+09 | 0.194089E+09 | 0.252818E+09 | 0.00 | 0.00 |
September | 0.685339E+09 | 0.281773E+09 | 0.412304E+09 | 0.211746E+09 | 0.200558E+09 | 0.00 | 0.00 |
October | 0.342626E+09 | 0.404044E+09 | 0.254772E+09 | 0.120803E+09 | 0.133969E+09 | 0.00 | 0.00 |
November | 0.164188E+09 | 0.484569E+09 | 0.156914E+09 | 75703129.62 | 81210943.70 | 0.00 | 0.00 |
December | 95749200.48 | 0.624149E+09 | 0.113190E+09 | 56770686.75 | 56418813.81 | 0.00 | 0.00 |
Annual Sum or Average | 0.544152E+10 | 0.456681E+10 | 0.377826E+10 | 0.161261E+10 | 0.216565E+10 | 0.00 | 0.00 |
Minimum of Months | 95749200.48 | 0.197760E+09 | 0.113190E+09 | 45282252.72 | 56418813.81 | 0.00 | 0.00 |
Maximum of Months | 0.799753E+09 | 0.624149E+09 | 0.477255E+09 | 0.211746E+09 | 0.286913E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 48198341.67 | 0.594143E+09 | 89023570.16 | 22516648.95 | 66506921.21 | 0.00 | 0.00 |
February | 0.115325E+09 | 0.505204E+09 | 0.139465E+09 | 47823668.68 | 91641708.71 | 0.00 | 0.00 |
March | 98101242.55 | 0.453566E+09 | 0.153912E+09 | 22039132.34 | 0.131873E+09 | 0.00 | 0.00 |
April | 0.423640E+09 | 0.345004E+09 | 0.322718E+09 | 0.103542E+09 | 0.219176E+09 | 0.00 | 0.00 |
May | 0.511479E+09 | 0.291477E+09 | 0.395912E+09 | 0.131924E+09 | 0.263988E+09 | 0.00 | 0.00 |
June | 0.610864E+09 | 0.207228E+09 | 0.415322E+09 | 0.140478E+09 | 0.274844E+09 | 0.00 | 0.00 |
July | 0.671207E+09 | 0.194155E+09 | 0.430847E+09 | 0.157090E+09 | 0.273758E+09 | 0.00 | 0.00 |
August | 0.565480E+09 | 0.216466E+09 | 0.358086E+09 | 0.127317E+09 | 0.230769E+09 | 0.00 | 0.00 |
September | 0.409662E+09 | 0.283672E+09 | 0.276481E+09 | 0.102578E+09 | 0.173903E+09 | 0.00 | 0.00 |
October | 0.164631E+09 | 0.409494E+09 | 0.157393E+09 | 44968258.80 | 0.112425E+09 | 0.00 | 0.00 |
November | 49413914.26 | 0.503051E+09 | 83557206.37 | 18461449.30 | 65095757.07 | 0.00 | 0.00 |
December | 12601923.93 | 0.655589E+09 | 50321829.47 | 6915842.16 | 43405987.31 | 0.00 | 0.00 |
Annual Sum or Average | 0.368060E+10 | 0.465905E+10 | 0.287304E+10 | 0.925652E+09 | 0.194739E+10 | 0.00 | 0.00 |
Minimum of Months | 12601923.93 | 0.194155E+09 | 50321829.47 | 6915842.16 | 43405987.31 | 0.00 | 0.00 |
Maximum of Months | 0.671207E+09 | 0.655589E+09 | 0.430847E+09 | 0.157090E+09 | 0.274844E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110710E+09 | 0.178859E+09 | 88612806.35 | 58172605.95 | 30440200.40 | 0.00 | 0.00 |
February | 0.125819E+09 | 0.155694E+09 | 96027988.69 | 59059659.32 | 36968329.37 | 0.00 | 0.00 |
March | 63636713.09 | 0.140427E+09 | 64578930.95 | 18590875.07 | 45988055.88 | 0.00 | 0.00 |
April | 0.184633E+09 | 0.134785E+09 | 0.125403E+09 | 53937501.74 | 71465269.43 | 0.00 | 0.00 |
May | 0.138425E+09 | 0.127405E+09 | 0.107294E+09 | 32138862.68 | 75154688.22 | 0.00 | 0.00 |
June | 0.128430E+09 | 95929205.24 | 95813803.84 | 20523545.06 | 75290258.78 | 0.00 | 0.00 |
July | 0.160813E+09 | 91182275.45 | 0.106315E+09 | 29923712.50 | 76390818.22 | 0.00 | 0.00 |
August | 0.208863E+09 | 97686615.85 | 0.125886E+09 | 54180430.82 | 71705968.57 | 0.00 | 0.00 |
September | 0.244445E+09 | 0.117585E+09 | 0.149071E+09 | 87329671.17 | 61741008.91 | 0.00 | 0.00 |
October | 0.145654E+09 | 0.155937E+09 | 0.104647E+09 | 60655891.96 | 43991571.81 | 0.00 | 0.00 |
November | 92267903.52 | 0.167172E+09 | 74233913.57 | 45784239.01 | 28449674.56 | 0.00 | 0.00 |
December | 79012887.29 | 0.167506E+09 | 61233727.91 | 39875945.41 | 21357782.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.168271E+10 | 0.163017E+10 | 0.119912E+10 | 0.560173E+09 | 0.638944E+09 | 0.00 | 0.00 |
Minimum of Months | 63636713.09 | 91182275.45 | 61233727.91 | 18590875.07 | 21357782.49 | 0.00 | 0.00 |
Maximum of Months | 0.244445E+09 | 0.178859E+09 | 0.149071E+09 | 87329671.17 | 76390818.22 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 441624.43 | 0.181939E+09 | 15138160.56 | 0.00 | 15138160.56 | 0.00 | 0.00 |
February | 1334023.94 | 0.153241E+09 | 21351248.07 | 0.00 | 21351248.07 | 0.00 | 0.00 |
March | 9729535.44 | 0.137188E+09 | 32715052.52 | 76.01 | 32714976.51 | 0.00 | 0.00 |
April | 43521432.29 | 99378315.32 | 51612306.31 | 222645.58 | 51389660.73 | 0.00 | 0.00 |
May | 56106273.77 | 80158015.68 | 66183036.00 | 2755690.17 | 63427345.83 | 0.00 | 0.00 |
June | 84713167.03 | 55949375.61 | 70425632.74 | 3627995.24 | 66797637.51 | 0.00 | 0.00 |
July | 91346119.58 | 51732693.66 | 69218664.47 | 3328253.77 | 65890410.71 | 0.00 | 0.00 |
August | 71650383.64 | 58121390.88 | 54861149.43 | 773074.26 | 54088075.17 | 0.00 | 0.00 |
September | 43687288.81 | 80321756.06 | 40446933.88 | 12069.86 | 40434864.02 | 0.00 | 0.00 |
October | 12435928.07 | 0.121489E+09 | 26768847.94 | 0.00 | 26768847.94 | 0.00 | 0.00 |
November | 722848.32 | 0.152123E+09 | 15565246.12 | 0.00 | 15565246.12 | 0.00 | 0.00 |
December | 0.00 | 0.196385E+09 | 10953220.50 | 0.00 | 10953220.50 | 0.00 | 0.00 |
Annual Sum or Average | 0.415689E+09 | 0.136803E+10 | 0.475239E+09 | 10719804.87 | 0.464520E+09 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 51732693.66 | 10953220.50 | 0.00 | 10953220.50 | 0.00 | 0.00 |
Maximum of Months | 91346119.58 | 0.196385E+09 | 70425632.74 | 3627995.24 | 66797637.51 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180634E+09 | 0.556483E+09 | 0.181602E+09 | 0.100339E+09 | 81262648.03 | 0.00 | 0.00 |
February | 0.234910E+09 | 0.481230E+09 | 0.217931E+09 | 0.110268E+09 | 0.107663E+09 | 0.00 | 0.00 |
March | 0.165898E+09 | 0.444580E+09 | 0.193423E+09 | 45491295.49 | 0.147931E+09 | 0.00 | 0.00 |
April | 0.668304E+09 | 0.332662E+09 | 0.451348E+09 | 0.206873E+09 | 0.244475E+09 | 0.00 | 0.00 |
May | 0.639151E+09 | 0.291140E+09 | 0.454229E+09 | 0.181105E+09 | 0.273124E+09 | 0.00 | 0.00 |
June | 0.653850E+09 | 0.206889E+09 | 0.425871E+09 | 0.149004E+09 | 0.276867E+09 | 0.00 | 0.00 |
July | 0.749468E+09 | 0.190570E+09 | 0.455629E+09 | 0.175520E+09 | 0.280110E+09 | 0.00 | 0.00 |
August | 0.794919E+09 | 0.205643E+09 | 0.464255E+09 | 0.215693E+09 | 0.248562E+09 | 0.00 | 0.00 |
September | 0.748162E+09 | 0.270939E+09 | 0.453438E+09 | 0.252118E+09 | 0.201320E+09 | 0.00 | 0.00 |
October | 0.355350E+09 | 0.399976E+09 | 0.264026E+09 | 0.131572E+09 | 0.132453E+09 | 0.00 | 0.00 |
November | 0.163932E+09 | 0.480718E+09 | 0.158948E+09 | 79392351.65 | 79555644.85 | 0.00 | 0.00 |
December | 0.117570E+09 | 0.618862E+09 | 0.126994E+09 | 68222218.61 | 58771882.34 | 0.00 | 0.00 |
Annual Sum or Average | 0.547215E+10 | 0.447969E+10 | 0.384769E+10 | 0.171560E+10 | 0.213210E+10 | 0.00 | 0.00 |
Minimum of Months | 0.117570E+09 | 0.190570E+09 | 0.126994E+09 | 45491295.49 | 58771882.34 | 0.00 | 0.00 |
Maximum of Months | 0.794919E+09 | 0.618862E+09 | 0.464255E+09 | 0.252118E+09 | 0.280110E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 40829321.37 | 0.583826E+09 | 89734011.46 | 27608988.36 | 62125023.09 | 0.00 | 0.00 |
February | 73825292.73 | 0.493886E+09 | 0.124558E+09 | 36429077.93 | 88128885.19 | 0.00 | 0.00 |
March | 94082008.39 | 0.449173E+09 | 0.153571E+09 | 22248175.11 | 0.131323E+09 | 0.00 | 0.00 |
April | 0.472163E+09 | 0.329190E+09 | 0.359070E+09 | 0.139716E+09 | 0.219354E+09 | 0.00 | 0.00 |
May | 0.513326E+09 | 0.282569E+09 | 0.402803E+09 | 0.144368E+09 | 0.258436E+09 | 0.00 | 0.00 |
June | 0.567514E+09 | 0.202291E+09 | 0.394100E+09 | 0.127879E+09 | 0.266221E+09 | 0.00 | 0.00 |
July | 0.627173E+09 | 0.188333E+09 | 0.409221E+09 | 0.142267E+09 | 0.266954E+09 | 0.00 | 0.00 |
August | 0.591321E+09 | 0.206942E+09 | 0.375433E+09 | 0.148921E+09 | 0.226513E+09 | 0.00 | 0.00 |
September | 0.469856E+09 | 0.269594E+09 | 0.317614E+09 | 0.142949E+09 | 0.174665E+09 | 0.00 | 0.00 |
October | 0.172119E+09 | 0.399808E+09 | 0.166647E+09 | 55737192.40 | 0.110910E+09 | 0.00 | 0.00 |
November | 40757642.78 | 0.490526E+09 | 85591129.55 | 22150671.32 | 63440458.23 | 0.00 | 0.00 |
December | 20301776.74 | 0.635416E+09 | 64126429.87 | 18367374.03 | 45759055.84 | 0.00 | 0.00 |
Annual Sum or Average | 0.368327E+10 | 0.453155E+10 | 0.294247E+10 | 0.102864E+10 | 0.191383E+10 | 0.00 | 0.00 |
Minimum of Months | 20301776.74 | 0.188333E+09 | 64126429.87 | 18367374.03 | 45759055.84 | 0.00 | 0.00 |
Maximum of Months | 0.627173E+09 | 0.635416E+09 | 0.409221E+09 | 0.148921E+09 | 0.266954E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217784E+09 | 0.710655E+09 | 0.224794E+09 | 0.126044E+09 | 98749781.05 | 0.00 | 0.00 |
February | 0.268250E+09 | 0.618012E+09 | 0.254320E+09 | 0.127966E+09 | 0.126354E+09 | 0.00 | 0.00 |
March | 0.162769E+09 | 0.576540E+09 | 0.210796E+09 | 40281420.99 | 0.170515E+09 | 0.00 | 0.00 |
April | 0.543470E+09 | 0.435713E+09 | 0.383522E+09 | 0.117350E+09 | 0.266173E+09 | 0.00 | 0.00 |
May | 0.473205E+09 | 0.367092E+09 | 0.375850E+09 | 75605726.84 | 0.300244E+09 | 0.00 | 0.00 |
June | 0.517054E+09 | 0.259096E+09 | 0.360167E+09 | 52328268.96 | 0.307839E+09 | 0.00 | 0.00 |
July | 0.603117E+09 | 0.243045E+09 | 0.380305E+09 | 72046477.18 | 0.308258E+09 | 0.00 | 0.00 |
August | 0.663605E+09 | 0.273815E+09 | 0.391608E+09 | 0.119069E+09 | 0.272540E+09 | 0.00 | 0.00 |
September | 0.674685E+09 | 0.358162E+09 | 0.410616E+09 | 0.189245E+09 | 0.221371E+09 | 0.00 | 0.00 |
October | 0.370822E+09 | 0.510727E+09 | 0.284732E+09 | 0.131424E+09 | 0.153308E+09 | 0.00 | 0.00 |
November | 0.198253E+09 | 0.616221E+09 | 0.194564E+09 | 99201713.76 | 95362075.63 | 0.00 | 0.00 |
December | 0.139702E+09 | 0.796824E+09 | 0.156405E+09 | 86400084.58 | 70004723.71 | 0.00 | 0.00 |
Annual Sum or Average | 0.483272E+10 | 0.576590E+10 | 0.362768E+10 | 0.123696E+10 | 0.239072E+10 | 0.00 | 0.00 |
Minimum of Months | 0.139702E+09 | 0.243045E+09 | 0.156405E+09 | 40281420.99 | 70004723.71 | 0.00 | 0.00 |
Maximum of Months | 0.674685E+09 | 0.796824E+09 | 0.410616E+09 | 0.189245E+09 | 0.308258E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.182958E+09 | 0.550183E+09 | 0.180891E+09 | 95246867.60 | 85644546.14 | 0.00 | 0.00 |
February | 0.273127E+09 | 0.481683E+09 | 0.232839E+09 | 0.121663E+09 | 0.111176E+09 | 0.00 | 0.00 |
March | 0.169666E+09 | 0.440558E+09 | 0.193763E+09 | 45282252.72 | 0.148481E+09 | 0.00 | 0.00 |
April | 0.612168E+09 | 0.344956E+09 | 0.414996E+09 | 0.170699E+09 | 0.244297E+09 | 0.00 | 0.00 |
May | 0.631241E+09 | 0.298739E+09 | 0.447338E+09 | 0.168661E+09 | 0.278677E+09 | 0.00 | 0.00 |
June | 0.692041E+09 | 0.212798E+09 | 0.447093E+09 | 0.161603E+09 | 0.285490E+09 | 0.00 | 0.00 |
July | 0.790059E+09 | 0.196342E+09 | 0.477255E+09 | 0.190342E+09 | 0.286913E+09 | 0.00 | 0.00 |
August | 0.764138E+09 | 0.213607E+09 | 0.446908E+09 | 0.194089E+09 | 0.252818E+09 | 0.00 | 0.00 |
September | 0.680343E+09 | 0.278366E+09 | 0.412304E+09 | 0.211746E+09 | 0.200558E+09 | 0.00 | 0.00 |
October | 0.342273E+09 | 0.397217E+09 | 0.254772E+09 | 0.120803E+09 | 0.133969E+09 | 0.00 | 0.00 |
November | 0.165443E+09 | 0.475825E+09 | 0.156914E+09 | 75703129.62 | 81210943.70 | 0.00 | 0.00 |
December | 96941485.36 | 0.614768E+09 | 0.113190E+09 | 56770686.75 | 56418813.81 | 0.00 | 0.00 |
Annual Sum or Average | 0.540040E+10 | 0.450504E+10 | 0.377826E+10 | 0.161261E+10 | 0.216565E+10 | 0.00 | 0.00 |
Minimum of Months | 96941485.36 | 0.196342E+09 | 0.113190E+09 | 45282252.72 | 56418813.81 | 0.00 | 0.00 |
Maximum of Months | 0.790059E+09 | 0.614768E+09 | 0.477255E+09 | 0.211746E+09 | 0.286913E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 49420686.71 | 0.583874E+09 | 89023570.16 | 22516648.95 | 66506921.21 | 0.00 | 0.00 |
February | 0.116603E+09 | 0.497409E+09 | 0.139465E+09 | 47823668.68 | 91641708.71 | 0.00 | 0.00 |
March | 99491894.50 | 0.446104E+09 | 0.153912E+09 | 22039132.34 | 0.131873E+09 | 0.00 | 0.00 |
April | 0.417290E+09 | 0.342061E+09 | 0.322718E+09 | 0.103542E+09 | 0.219176E+09 | 0.00 | 0.00 |
May | 0.502886E+09 | 0.290188E+09 | 0.395912E+09 | 0.131924E+09 | 0.263988E+09 | 0.00 | 0.00 |
June | 0.599687E+09 | 0.207414E+09 | 0.415322E+09 | 0.140478E+09 | 0.274844E+09 | 0.00 | 0.00 |
July | 0.658462E+09 | 0.195229E+09 | 0.430847E+09 | 0.157090E+09 | 0.273758E+09 | 0.00 | 0.00 |
August | 0.555809E+09 | 0.216255E+09 | 0.358086E+09 | 0.127317E+09 | 0.230769E+09 | 0.00 | 0.00 |
September | 0.405403E+09 | 0.280713E+09 | 0.276481E+09 | 0.102578E+09 | 0.173903E+09 | 0.00 | 0.00 |
October | 0.165262E+09 | 0.401815E+09 | 0.157393E+09 | 44968258.80 | 0.112425E+09 | 0.00 | 0.00 |
November | 50738024.32 | 0.493389E+09 | 83557206.37 | 18461449.30 | 65095757.07 | 0.00 | 0.00 |
December | 13112859.59 | 0.645505E+09 | 50321829.47 | 6915842.16 | 43405987.31 | 0.00 | 0.00 |
Annual Sum or Average | 0.363416E+10 | 0.459996E+10 | 0.287304E+10 | 0.925652E+09 | 0.194739E+10 | 0.00 | 0.00 |
Minimum of Months | 13112859.59 | 0.195229E+09 | 50321829.47 | 6915842.16 | 43405987.31 | 0.00 | 0.00 |
Maximum of Months | 0.658462E+09 | 0.645505E+09 | 0.430847E+09 | 0.157090E+09 | 0.274844E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.211254E+09 | 0.285377E+09 | 0.162481E+09 | 0.106666E+09 | 55815442.02 | 0.00 | 0.00 |
February | 0.238418E+09 | 0.250663E+09 | 0.176078E+09 | 0.108292E+09 | 67785481.64 | 0.00 | 0.00 |
March | 0.123350E+09 | 0.232346E+09 | 0.118413E+09 | 34088406.00 | 84324138.25 | 0.00 | 0.00 |
April | 0.366763E+09 | 0.184138E+09 | 0.229940E+09 | 98900318.07 | 0.131039E+09 | 0.00 | 0.00 |
May | 0.289075E+09 | 0.162311E+09 | 0.196734E+09 | 58930125.40 | 0.137804E+09 | 0.00 | 0.00 |
June | 0.276208E+09 | 0.112474E+09 | 0.175685E+09 | 37632168.13 | 0.138053E+09 | 0.00 | 0.00 |
July | 0.337631E+09 | 0.103353E+09 | 0.194939E+09 | 54868404.89 | 0.140071E+09 | 0.00 | 0.00 |
August | 0.421851E+09 | 0.111358E+09 | 0.230827E+09 | 99345755.16 | 0.131481E+09 | 0.00 | 0.00 |
September | 0.481606E+09 | 0.145816E+09 | 0.273337E+09 | 0.160129E+09 | 0.113209E+09 | 0.00 | 0.00 |
October | 0.289759E+09 | 0.209147E+09 | 0.191883E+09 | 0.111219E+09 | 80663366.01 | 0.00 | 0.00 |
November | 0.179831E+09 | 0.249227E+09 | 0.136116E+09 | 83950417.70 | 52165594.85 | 0.00 | 0.00 |
December | 0.141265E+09 | 0.319323E+09 | 0.112279E+09 | 73116914.16 | 39161833.86 | 0.00 | 0.00 |
Annual Sum or Average | 0.335701E+10 | 0.236553E+10 | 0.219871E+10 | 0.102714E+10 | 0.117157E+10 | 0.00 | 0.00 |
Minimum of Months | 0.123350E+09 | 0.103353E+09 | 0.112279E+09 | 34088406.00 | 39161833.86 | 0.00 | 0.00 |
Maximum of Months | 0.481606E+09 | 0.319323E+09 | 0.273337E+09 | 0.160129E+09 | 0.140071E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3830775.08 | 0.157103E+10 | 0.132436E+09 | 0.00 | 0.132436E+09 | 0.00 | 0.00 |
February | 10899859.42 | 0.132889E+10 | 0.186792E+09 | 0.00 | 0.186792E+09 | 0.00 | 0.00 |
March | 86937816.22 | 0.118329E+10 | 0.286208E+09 | 664.93 | 0.286207E+09 | 0.00 | 0.00 |
April | 0.382426E+09 | 0.871761E+09 | 0.451531E+09 | 1947816.84 | 0.449583E+09 | 0.00 | 0.00 |
May | 0.490545E+09 | 0.722229E+09 | 0.579003E+09 | 24108180.09 | 0.554895E+09 | 0.00 | 0.00 |
June | 0.743695E+09 | 0.515381E+09 | 0.616119E+09 | 31739548.78 | 0.584380E+09 | 0.00 | 0.00 |
July | 0.809656E+09 | 0.476740E+09 | 0.605560E+09 | 29117257.85 | 0.576443E+09 | 0.00 | 0.00 |
August | 0.640778E+09 | 0.528394E+09 | 0.479953E+09 | 6763247.05 | 0.473190E+09 | 0.00 | 0.00 |
September | 0.390577E+09 | 0.715968E+09 | 0.353850E+09 | 105593.27 | 0.353745E+09 | 0.00 | 0.00 |
October | 0.111633E+09 | 0.105735E+10 | 0.234188E+09 | 0.00 | 0.234188E+09 | 0.00 | 0.00 |
November | 6508380.81 | 0.131973E+10 | 0.136173E+09 | 0.00 | 0.136173E+09 | 0.00 | 0.00 |
December | 0.00 | 0.171024E+10 | 95824347.54 | 0.00 | 95824347.54 | 0.00 | 0.00 |
Annual Sum or Average | 0.367749E+10 | 0.120010E+11 | 0.415764E+10 | 93782308.81 | 0.406385E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.476740E+09 | 95824347.54 | 0.00 | 95824347.54 | 0.00 | 0.00 |
Maximum of Months | 0.809656E+09 | 0.171024E+10 | 0.616119E+09 | 31739548.78 | 0.584380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2733771.91 | 0.163357E+10 | 0.132436E+09 | 0.00 | 0.132436E+09 | 0.00 | 0.00 |
February | 8384992.30 | 0.138614E+10 | 0.186792E+09 | 0.00 | 0.186792E+09 | 0.00 | 0.00 |
March | 75438044.09 | 0.124014E+10 | 0.286208E+09 | 664.93 | 0.286207E+09 | 0.00 | 0.00 |
April | 0.361375E+09 | 0.907729E+09 | 0.451531E+09 | 1947816.84 | 0.449583E+09 | 0.00 | 0.00 |
May | 0.463572E+09 | 0.751635E+09 | 0.579003E+09 | 24108180.09 | 0.554895E+09 | 0.00 | 0.00 |
June | 0.717087E+09 | 0.536084E+09 | 0.616119E+09 | 31739548.78 | 0.584380E+09 | 0.00 | 0.00 |
July | 0.782852E+09 | 0.495775E+09 | 0.605560E+09 | 29117257.85 | 0.576443E+09 | 0.00 | 0.00 |
August | 0.618591E+09 | 0.550785E+09 | 0.479953E+09 | 6763247.05 | 0.473190E+09 | 0.00 | 0.00 |
September | 0.372426E+09 | 0.746176E+09 | 0.353850E+09 | 105593.27 | 0.353745E+09 | 0.00 | 0.00 |
October | 99720756.11 | 0.110926E+10 | 0.234188E+09 | 0.00 | 0.234188E+09 | 0.00 | 0.00 |
November | 4550065.06 | 0.138286E+10 | 0.136173E+09 | 0.00 | 0.136173E+09 | 0.00 | 0.00 |
December | 0.00 | 0.177472E+10 | 95824347.54 | 0.00 | 95824347.54 | 0.00 | 0.00 |
Annual Sum or Average | 0.350673E+10 | 0.125149E+11 | 0.415764E+10 | 93782308.81 | 0.406385E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.495775E+09 | 95824347.54 | 0.00 | 95824347.54 | 0.00 | 0.00 |
Maximum of Months | 0.782852E+09 | 0.177472E+10 | 0.616119E+09 | 31739548.78 | 0.584380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.413637E+09 | 0.778852E+09 | 0.271326E+09 | 0.127944E+09 | 0.143382E+09 | 0.00 | 0.00 |
February | 0.536113E+09 | 0.708823E+09 | 0.342475E+09 | 0.146692E+09 | 0.195783E+09 | 0.00 | 0.00 |
March | 0.592088E+09 | 0.658456E+09 | 0.346978E+09 | 67736310.81 | 0.279242E+09 | 0.00 | 0.00 |
April | 0.165042E+10 | 0.539825E+09 | 0.810376E+09 | 0.346570E+09 | 0.463806E+09 | 0.00 | 0.00 |
May | 0.170313E+10 | 0.499111E+09 | 0.856987E+09 | 0.325452E+09 | 0.531535E+09 | 0.00 | 0.00 |
June | 0.181195E+10 | 0.360703E+09 | 0.819927E+09 | 0.276865E+09 | 0.543062E+09 | 0.00 | 0.00 |
July | 0.201485E+10 | 0.334086E+09 | 0.864805E+09 | 0.317767E+09 | 0.547037E+09 | 0.00 | 0.00 |
August | 0.200262E+10 | 0.335339E+09 | 0.839645E+09 | 0.364593E+09 | 0.475052E+09 | 0.00 | 0.00 |
September | 0.174342E+10 | 0.415419E+09 | 0.771014E+09 | 0.395046E+09 | 0.375968E+09 | 0.00 | 0.00 |
October | 0.885537E+09 | 0.570756E+09 | 0.430654E+09 | 0.187301E+09 | 0.243352E+09 | 0.00 | 0.00 |
November | 0.405289E+09 | 0.650819E+09 | 0.244530E+09 | 0.101540E+09 | 0.142990E+09 | 0.00 | 0.00 |
December | 0.262002E+09 | 0.871613E+09 | 0.191113E+09 | 86586984.01 | 0.104526E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140211E+11 | 0.672380E+10 | 0.678983E+10 | 0.274410E+10 | 0.404574E+10 | 0.00 | 0.00 |
Minimum of Months | 0.262002E+09 | 0.334086E+09 | 0.191113E+09 | 67736310.81 | 0.104526E+09 | 0.00 | 0.00 |
Maximum of Months | 0.201485E+10 | 0.871613E+09 | 0.864805E+09 | 0.395046E+09 | 0.547037E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.486680E+09 | 0.125828E+10 | 0.459004E+09 | 0.271524E+09 | 0.187481E+09 | 0.00 | 0.00 |
February | 0.579761E+09 | 0.109854E+10 | 0.512248E+09 | 0.275664E+09 | 0.236584E+09 | 0.00 | 0.00 |
March | 0.324444E+09 | 0.103462E+10 | 0.399538E+09 | 86774077.06 | 0.312764E+09 | 0.00 | 0.00 |
April | 0.103408E+10 | 0.833985E+09 | 0.740109E+09 | 0.252424E+09 | 0.487686E+09 | 0.00 | 0.00 |
May | 0.844950E+09 | 0.735535E+09 | 0.699281E+09 | 0.158274E+09 | 0.541007E+09 | 0.00 | 0.00 |
June | 0.868175E+09 | 0.542160E+09 | 0.658423E+09 | 0.106675E+09 | 0.551748E+09 | 0.00 | 0.00 |
July | 0.103814E+10 | 0.513978E+09 | 0.703816E+09 | 0.149652E+09 | 0.554164E+09 | 0.00 | 0.00 |
August | 0.121588E+10 | 0.572272E+09 | 0.752110E+09 | 0.255208E+09 | 0.496902E+09 | 0.00 | 0.00 |
September | 0.131089E+10 | 0.710098E+09 | 0.817096E+09 | 0.407652E+09 | 0.409444E+09 | 0.00 | 0.00 |
October | 0.753765E+09 | 0.947018E+09 | 0.568727E+09 | 0.283114E+09 | 0.285613E+09 | 0.00 | 0.00 |
November | 0.430771E+09 | 0.110397E+10 | 0.393171E+09 | 0.213700E+09 | 0.179471E+09 | 0.00 | 0.00 |
December | 0.316137E+09 | 0.141540E+10 | 0.318660E+09 | 0.186123E+09 | 0.132537E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.920369E+10 | 0.107658E+11 | 0.702218E+10 | 0.264678E+10 | 0.437540E+10 | 0.00 | 0.00 |
Minimum of Months | 0.316137E+09 | 0.513978E+09 | 0.318660E+09 | 86774077.06 | 0.132537E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131089E+10 | 0.141540E+10 | 0.817096E+09 | 0.407652E+09 | 0.554164E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770419E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413541.0 | 81.21 | 0.00 | 0.00 |
February | 0.696176E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145792850.6 | 81.21 | 0.00 | 0.00 |
March | 0.770288E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413965.9 | 81.21 | 0.00 | 0.00 |
April | 0.746480E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156207206.7 | 81.21 | 0.00 | 0.00 |
May | 0.770421E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413544.8 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206151.4 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412632.7 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412710.6 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206117.7 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413454.5 | 81.21 | 0.00 | 0.00 |
November | 0.744863E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206329.1 | 81.21 | 0.00 | 0.00 |
December | 0.771227E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413843.3 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907409E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190051E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696176E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161413965.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771227E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145792850.6 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121928E+12 | -0.120147E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178115E+10 | 81.27 | 0.00 | 0.00 |
February | 0.110649E+12 | -0.109035E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.161358E+10 | 81.27 | 0.00 | 0.00 |
March | 0.121932E+12 | -0.120138E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179326E+10 | 81.28 | 0.00 | 0.00 |
April | 0.116462E+12 | -0.114726E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173602E+10 | 81.27 | 0.00 | 0.00 |
May | 0.118158E+12 | -0.116364E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179383E+10 | 81.27 | 0.00 | 0.00 |
June | 0.112221E+12 | -0.110488E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173244E+10 | 81.26 | 0.00 | 0.00 |
July | 0.114344E+12 | -0.112561E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178285E+10 | 81.26 | 0.00 | 0.00 |
August | 0.113737E+12 | -0.111958E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177917E+10 | 81.26 | 0.00 | 0.00 |
September | 0.110627E+12 | -0.108914E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171358E+10 | 81.25 | 0.00 | 0.00 |
October | 0.115915E+12 | -0.114149E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176599E+10 | 81.26 | 0.00 | 0.00 |
November | 0.114291E+12 | -0.112583E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170747E+10 | 81.26 | 0.00 | 0.00 |
December | 0.120294E+12 | -0.118524E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177009E+10 | 81.27 | 0.00 | 0.00 |
Annual Sum or Average | 0.139056E+13 | -0.136959E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209694E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.110627E+12 | -0.120147E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.179383E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.121932E+12 | -0.108914E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161358E+10 | 81.28 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.726304E+11 | -0.710928E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153767E+10 | 58.98 | 0.00 | 0.00 |
February | 0.660509E+11 | -0.646554E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139553E+10 | 58.98 | 0.00 | 0.00 |
March | 0.727032E+11 | -0.711488E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155440E+10 | 58.98 | 0.00 | 0.00 |
April | 0.690117E+11 | -0.675063E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150532E+10 | 58.98 | 0.00 | 0.00 |
May | 0.694521E+11 | -0.678965E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155561E+10 | 58.98 | 0.00 | 0.00 |
June | 0.654118E+11 | -0.639111E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150071E+10 | 58.98 | 0.00 | 0.00 |
July | 0.661351E+11 | -0.645944E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154069E+10 | 58.98 | 0.00 | 0.00 |
August | 0.656783E+11 | -0.641429E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153541E+10 | 58.98 | 0.00 | 0.00 |
September | 0.640016E+11 | -0.625267E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147489E+10 | 58.98 | 0.00 | 0.00 |
October | 0.674754E+11 | -0.659582E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151721E+10 | 58.98 | 0.00 | 0.00 |
November | 0.671134E+11 | -0.656473E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146604E+10 | 58.98 | 0.00 | 0.00 |
December | 0.712287E+11 | -0.697060E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152268E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.816893E+12 | -0.798786E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181061E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.640016E+11 | -0.711488E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.155561E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.727032E+11 | -0.625267E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139553E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.87 | 0.86 | 01-JAN-08:39 | 2273.13 | 35.46 | 190.33 | 211.67 | 1841.72 | 36.40 | 191.17 | 161.17 |
February | 217.00 | 0.87 | 0.86 | 01-FEB-11:39 | 3311.36 | 34.69 | 210.17 | 233.67 | 1449.33 | 30.49 | 169.83 | 185.33 |
March | 215.50 | 0.88 | 0.86 | 01-MAR-11:39 | 2113.57 | 27.89 | 152.67 | 294.00 | 447.13 | 19.60 | 47.00 | 202.83 |
April | 359.67 | 0.87 | 0.86 | 01-APR-07:40 | 1232.08 | 18.36 | 0.00 | 344.00 | 490.37 | 20.57 | 179.00 | 269.17 |
May | 417.17 | 0.87 | 0.86 | 01-MAY-07:19 | 986.96 | 17.79 | 0.00 | 392.17 | 391.70 | 20.02 | 126.83 | 292.83 |
June | 410.67 | 0.87 | 0.86 | 01-JUN-06:00 | 966.96 | 18.05 | 0.00 | 391.17 | 382.32 | 20.25 | 127.83 | 291.17 |
July | 429.00 | 0.87 | 0.86 | 01-JUL-07:10 | 944.63 | 17.88 | 0.00 | 403.83 | 380.35 | 20.11 | 128.50 | 303.17 |
August | 396.33 | 0.87 | 0.86 | 01-AUG-07:19 | 1076.21 | 18.03 | 0.00 | 365.00 | 435.87 | 20.26 | 181.67 | 287.33 |
September | 337.67 | 0.87 | 0.86 | 01-SEP-08:20 | 3668.23 | 25.14 | 128.17 | 318.33 | 524.27 | 20.72 | 182.00 | 255.67 |
October | 234.00 | 0.87 | 0.86 | 01-OCT-06:00 | 4183.33 | 33.80 | 215.33 | 267.67 | 728.50 | 23.62 | 141.00 | 202.00 |
November | 171.33 | 0.87 | 0.86 | 01-NOV-11:00 | 2644.75 | 35.14 | 166.00 | 198.67 | 1939.06 | 35.36 | 161.00 | 140.17 |
December | 131.67 | 0.87 | 0.86 | 02-DEC-08:00 | 2184.77 | 36.26 | 128.17 | 159.50 | 1768.02 | 37.22 | 128.33 | 109.00 |
Annual Sum or Average | 3515.67 | 0.87 | 1894.63 | 23.87 | 1190.83 | 3579.67 | 715.78 | 23.37 | 1764.17 | 2699.83 | ||
Minimum of Months | 131.67 | 0.87 | 0.86 | 944.63 | 17.79 | 0.00 | 159.50 | 380.35 | 19.60 | 47.00 | 109.00 | |
Maximum of Months | 429.00 | 0.88 | 0.86 | 4183.33 | 36.26 | 215.33 | 403.83 | 1939.06 | 37.22 | 191.17 | 303.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.27 | 0.22 | 01-JAN-08:39 | 2496.51 | 35.52 | 190.33 | 223.83 | 2064.62 | 36.46 | 191.33 | 191.50 |
February | 217.00 | 0.26 | 0.22 | 01-FEB-11:39 | 3562.49 | 34.78 | 210.67 | 246.00 | 1697.57 | 30.64 | 165.67 | 215.50 |
March | 215.50 | 0.27 | 0.22 | 01-MAR-11:39 | 2276.90 | 28.27 | 153.17 | 310.00 | 609.68 | 20.38 | 84.50 | 258.67 |
April | 359.67 | 0.27 | 0.22 | 01-APR-06:00 | 1459.93 | 19.04 | 0.00 | 357.17 | 717.35 | 21.04 | 198.50 | 323.33 |
May | 417.17 | 0.27 | 0.22 | 01-MAY-06:00 | 1159.68 | 18.70 | 0.00 | 409.67 | 563.70 | 20.68 | 195.00 | 362.00 |
June | 410.67 | 0.25 | 0.22 | 01-JUN-05:49 | 1127.03 | 19.01 | 0.00 | 412.17 | 541.71 | 20.96 | 202.00 | 362.33 |
July | 429.00 | 0.26 | 0.22 | 01-JUL-05:00 | 1112.78 | 18.79 | 0.00 | 420.50 | 547.82 | 20.77 | 203.00 | 371.17 |
August | 396.33 | 0.27 | 0.22 | 01-AUG-06:19 | 1286.06 | 18.77 | 0.00 | 382.17 | 644.94 | 20.78 | 200.50 | 339.83 |
September | 337.67 | 0.27 | 0.22 | 01-SEP-07:49 | 3944.52 | 25.62 | 128.17 | 329.50 | 799.84 | 21.04 | 173.67 | 295.33 |
October | 234.00 | 0.26 | 0.22 | 01-OCT-06:00 | 4446.29 | 33.96 | 215.50 | 279.67 | 991.33 | 23.92 | 137.33 | 235.00 |
November | 171.33 | 0.26 | 0.22 | 01-NOV-11:39 | 2873.96 | 35.22 | 166.17 | 217.00 | 2167.54 | 35.43 | 159.67 | 168.50 |
December | 131.67 | 0.26 | 0.22 | 02-DEC-08:50 | 2409.72 | 36.33 | 128.17 | 181.83 | 1991.88 | 37.27 | 128.33 | 128.00 |
Annual Sum or Average | 3515.67 | 0.26 | 2102.89 | 24.45 | 1192.17 | 3769.50 | 923.20 | 23.84 | 2039.50 | 3251.17 | ||
Minimum of Months | 131.67 | 0.25 | 0.22 | 1112.78 | 18.70 | 0.00 | 181.83 | 541.71 | 20.38 | 84.50 | 128.00 | |
Maximum of Months | 429.00 | 0.27 | 0.22 | 4446.29 | 36.33 | 215.50 | 420.50 | 2167.54 | 37.27 | 203.00 | 371.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.72 | 0.60 | 06-JAN-11:09 | 242.56 | 11.40 | 0.00 | 162.67 | 114.40 | 15.37 | 0.00 | 0.00 |
February | 217.00 | 0.67 | 0.60 | 01-FEB-13:09 | 316.01 | 13.02 | 0.00 | 210.17 | 148.19 | 16.89 | 0.00 | 19.33 |
March | 215.50 | 0.66 | 0.60 | 01-MAR-12:20 | 405.12 | 13.70 | 0.00 | 288.67 | 171.61 | 17.30 | 0.00 | 70.83 |
April | 359.67 | 0.63 | 0.60 | 01-APR-07:49 | 503.31 | 15.76 | 0.00 | 356.83 | 236.96 | 19.49 | 1.17 | 269.17 |
May | 417.17 | 0.62 | 0.60 | 01-MAY-07:10 | 605.22 | 17.39 | 29.33 | 420.00 | 279.76 | 21.82 | 67.50 | 367.33 |
June | 410.67 | 0.61 | 0.60 | 01-JUN-04:00 | 691.49 | 18.40 | 48.83 | 422.67 | 320.51 | 22.31 | 100.50 | 377.00 |
July | 429.00 | 0.61 | 0.60 | 01-JUL-04:00 | 636.11 | 18.52 | 59.50 | 433.17 | 299.80 | 21.93 | 84.17 | 389.50 |
August | 396.33 | 0.62 | 0.60 | 01-AUG-05:49 | 505.18 | 16.07 | 6.33 | 387.67 | 242.83 | 19.80 | 7.00 | 304.50 |
September | 337.67 | 0.64 | 0.60 | 01-SEP-08:09 | 397.76 | 14.85 | 0.00 | 316.33 | 199.94 | 18.68 | 0.00 | 173.17 |
October | 234.00 | 0.66 | 0.60 | 01-OCT-08:30 | 350.62 | 13.76 | 0.00 | 245.17 | 167.85 | 17.59 | 0.00 | 51.83 |
November | 171.33 | 0.70 | 0.60 | 02-NOV-12:30 | 266.03 | 12.06 | 0.00 | 156.67 | 125.86 | 15.99 | 0.00 | 0.33 |
December | 131.67 | 0.73 | 0.60 | 03-DEC-11:39 | 224.05 | 11.17 | 0.00 | 99.50 | 108.01 | 15.22 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.64 | 479.38 | 15.52 | 144.00 | 3499.50 | 225.42 | 19.37 | 260.33 | 2023.00 | ||
Minimum of Months | 131.67 | 0.61 | 0.60 | 224.05 | 11.17 | 0.00 | 99.50 | 108.01 | 15.22 | 0.00 | 0.00 | |
Maximum of Months | 429.00 | 0.73 | 0.60 | 691.49 | 18.52 | 59.50 | 433.17 | 320.51 | 22.31 | 100.50 | 389.50 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.72 | 0.60 | 06-JAN-11:09 | 242.56 | 11.40 | 0.00 | 162.67 | 114.40 | 15.37 | 0.00 | 0.00 |
February | 217.00 | 0.67 | 0.60 | 01-FEB-13:09 | 316.01 | 13.02 | 0.00 | 210.17 | 148.19 | 16.89 | 0.00 | 19.33 |
March | 215.50 | 0.66 | 0.60 | 01-MAR-12:20 | 405.12 | 13.70 | 0.00 | 288.67 | 171.61 | 17.30 | 0.00 | 70.83 |
April | 359.67 | 0.63 | 0.60 | 01-APR-07:49 | 503.31 | 15.76 | 0.00 | 356.83 | 236.96 | 19.49 | 1.17 | 269.17 |
May | 417.17 | 0.62 | 0.60 | 01-MAY-07:10 | 605.22 | 17.39 | 29.33 | 420.00 | 279.76 | 21.82 | 67.50 | 367.33 |
June | 410.67 | 0.61 | 0.60 | 01-JUN-04:00 | 691.49 | 18.40 | 48.83 | 422.67 | 320.51 | 22.31 | 100.50 | 377.00 |
July | 429.00 | 0.61 | 0.60 | 01-JUL-04:00 | 636.11 | 18.52 | 59.50 | 433.17 | 299.80 | 21.93 | 84.17 | 389.50 |
August | 396.33 | 0.62 | 0.60 | 01-AUG-05:49 | 505.18 | 16.07 | 6.33 | 387.67 | 242.83 | 19.80 | 7.00 | 304.50 |
September | 337.67 | 0.64 | 0.60 | 01-SEP-08:09 | 397.76 | 14.85 | 0.00 | 316.33 | 199.94 | 18.68 | 0.00 | 173.17 |
October | 234.00 | 0.66 | 0.60 | 01-OCT-08:30 | 350.62 | 13.76 | 0.00 | 245.17 | 167.85 | 17.59 | 0.00 | 51.83 |
November | 171.33 | 0.70 | 0.60 | 02-NOV-12:30 | 266.03 | 12.06 | 0.00 | 156.67 | 125.86 | 15.99 | 0.00 | 0.33 |
December | 131.67 | 0.73 | 0.60 | 03-DEC-11:39 | 224.05 | 11.17 | 0.00 | 99.50 | 108.01 | 15.22 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.64 | 479.38 | 15.52 | 144.00 | 3499.50 | 225.42 | 19.37 | 260.33 | 2023.00 | ||
Minimum of Months | 131.67 | 0.61 | 0.60 | 224.05 | 11.17 | 0.00 | 99.50 | 108.01 | 15.22 | 0.00 | 0.00 | |
Maximum of Months | 429.00 | 0.73 | 0.60 | 691.49 | 18.52 | 59.50 | 433.17 | 320.51 | 22.31 | 100.50 | 389.50 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.716059E+11 | 83123.08 | 19-JAN-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736738E+11 | 81457.14 | 03-FEB-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.777609E+11 | 78570.09 | 12-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.455470E+11 | 79853.30 | 09-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.334386E+11 | 77792.57 | 06-MAY-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623742E+10 | 46983.28 | 08-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281408E+10 | 36325.01 | 06-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110619E+10 | 26175.23 | 23-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.791008E+10 | 56294.55 | 20-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370553E+11 | 77450.54 | 07-OCT-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655164E+11 | 85345.93 | 19-NOV-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.961030E+11 | 85653.96 | 06-DEC-23:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518769E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.110619E+10 | 26175.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.961030E+11 | 85653.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148506E+10 | 1367.45 | 10-JAN-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112782E+10 | 1215.27 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125867E+10 | 1141.02 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.253088E+09 | 841.49 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211089E+09 | 621.95 | 05-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13535557.40 | 505.29 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12184321.74 | 227.85 | 04-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22659053.03 | 421.76 | 08-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560852E+09 | 846.61 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114764E+10 | 1198.67 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189964E+10 | 1292.08 | 30-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.799224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189964E+10 | 1367.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.314832E+09 | 677.45 | 12-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236407E+09 | 615.35 | 27-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263499E+09 | 622.68 | 16-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43846846.08 | 451.83 | 11-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35093275.40 | 440.47 | 05-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1764648.88 | 312.24 | 08-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1627518.69 | 289.75 | 03-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 947518.86 | 279.26 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95711834.80 | 457.06 | 19-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220015E+09 | 626.60 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401364E+09 | 670.38 | 29-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401364E+09 | 677.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4756614.78 | 178.69 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4756614.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4756614.78 | 178.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122034E+10 | 829.23 | 11-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105693E+10 | 675.69 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.950696E+09 | 643.43 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397998E+09 | 494.68 | 01-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272336E+09 | 461.19 | 05-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27802625.84 | 303.55 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9983815.24 | 229.25 | 05-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26214420.79 | 266.07 | 08-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474477E+09 | 458.84 | 23-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.871843E+09 | 692.01 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130312E+10 | 740.23 | 30-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.661174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130312E+10 | 829.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.366413E+10 | 6423.69 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.282482E+10 | 6072.31 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366075E+10 | 6076.61 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110977E+10 | 5490.27 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128265E+10 | 4823.43 | 17-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.814480E+09 | 4852.17 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.525724E+09 | 3331.39 | 13-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.293369E+09 | 4045.02 | 08-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.375770E+09 | 4476.98 | 08-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209972E+10 | 5488.49 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323681E+10 | 6118.98 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.460814E+10 | 6252.74 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.293369E+09 | 3331.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.460814E+10 | 6423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184799E+10 | 9730.55 | 12-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117586E+10 | 8662.12 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143112E+10 | 8354.61 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76508828.60 | 6047.49 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64993842.30 | 6156.57 | 16-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3214022.17 | 2725.62 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1019942.23 | 1699.90 | 08-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.311853E+09 | 5983.35 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113654E+10 | 8764.12 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263365E+10 | 9140.74 | 27-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.263365E+10 | 9730.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.660985E+10 | 6051.71 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.524688E+10 | 5670.19 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.528156E+10 | 5489.85 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.832692E+09 | 4160.95 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.426909E+09 | 3391.94 | 17-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2682024.65 | 1592.25 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 982263.86 | 1086.10 | 08-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252247E+10 | 4631.56 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.535487E+10 | 5796.94 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813785E+10 | 5964.11 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.813785E+10 | 6051.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152500E+10 | 2300.79 | 10-JAN-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.885806E+09 | 2037.56 | 17-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469381E+09 | 1336.45 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3119975.46 | 528.53 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19286404.57 | 560.86 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.634094E+09 | 1769.74 | 29-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203190E+10 | 2048.99 | 27-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203190E+10 | 2300.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.970779E+09 | 4820.92 | 11-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.640682E+09 | 4310.86 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486882E+09 | 3742.68 | 13-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95391739.42 | 3296.61 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57885743.26 | 3293.66 | 05-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28533366.55 | 2853.32 | 06-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17007177.18 | 2588.75 | 05-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31249170.19 | 2666.74 | 28-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51551625.79 | 3112.11 | 21-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265699E+09 | 3818.74 | 23-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.656911E+09 | 4037.73 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105796E+10 | 4243.76 | 18-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17007177.18 | 2588.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105796E+10 | 4820.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161259E+09 | 3140.78 | 11-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40032230.47 | 2640.51 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34444825.60 | 1935.60 | 13-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13464804.18 | 1498.92 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5907429.93 | 1614.42 | 05-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 416557.78 | 396.30 | 06-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32567.50 | 54.28 | 31-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 277046.46 | 255.48 | 28-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7969586.37 | 1422.34 | 21-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25981442.73 | 2717.26 | 23-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50007342.21 | 2286.31 | 28-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117350E+09 | 2497.58 | 18-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 32567.50 | 54.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161259E+09 | 3140.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247181E+09 | 3001.70 | 12-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82552832.48 | 1519.81 | 17-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2022015.40 | 1519.18 | 15-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4614.87 | 0.64 | 28-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4260.84 | 0.64 | 27-MAY-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10556.79 | 0.67 | 24-JUN-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21994.85 | 0.69 | 12-JUL-19:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20770.16 | 0.67 | 25-AUG-18:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10377.06 | 0.68 | 17-SEP-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1975.54 | 0.64 | 05-OCT-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6686203.90 | 640.92 | 29-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 58332806.54 | 1669.91 | 30-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1975.54 | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247181E+09 | 3001.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.312854E+10 | 7907.93 | 04-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241202E+10 | 7869.37 | 25-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236685E+10 | 7906.76 | 15-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.668100E+09 | 7695.75 | 10-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.490993E+09 | 6020.21 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69425819.68 | 4627.34 | 23-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68886122.91 | 3713.39 | 05-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13722010.89 | 3808.59 | 08-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139445E+09 | 3909.01 | 06-SEP-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128704E+10 | 7777.34 | 19-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247481E+10 | 7909.20 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388198E+10 | 7910.96 | 16-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13722010.89 | 3713.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388198E+10 | 7910.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369944E+10 | 7685.82 | 22-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291107E+10 | 7685.86 | 25-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260545E+10 | 7684.56 | 15-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.907744E+09 | 7506.59 | 10-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573326E+09 | 6593.24 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74667956.89 | 3654.55 | 30-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67043022.03 | 3844.72 | 05-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12240805.74 | 3216.85 | 18-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218567E+09 | 3884.44 | 30-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163067E+10 | 7565.37 | 19-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288599E+10 | 7685.89 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.425705E+10 | 7687.74 | 16-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12240805.74 | 3216.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425705E+10 | 7687.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.781422E+10 | 43811.98 | 12-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579278E+10 | 42921.43 | 17-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285602E+10 | 42836.69 | 15-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.467484E+09 | 27998.49 | 14-APR-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192066E+09 | 19261.30 | 13-MAY-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33627288.40 | 18496.82 | 05-JUN-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27573240.15 | 10746.18 | 22-JUL-15:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22450546.04 | 16916.90 | 18-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83241958.15 | 17372.27 | 11-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.927260E+09 | 25093.95 | 03-OCT-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393489E+10 | 43318.60 | 29-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.885207E+10 | 43484.22 | 27-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.310037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22450546.04 | 10746.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.885207E+10 | 43811.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.312332E+10 | 7682.15 | 04-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251241E+10 | 7644.63 | 15-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238873E+10 | 7679.94 | 15-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599606E+09 | 7451.26 | 10-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.468063E+09 | 3741.15 | 28-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99960778.94 | 4183.50 | 16-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 54200959.62 | 4011.24 | 04-JUL-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12470352.95 | 3704.17 | 09-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110416E+09 | 4105.27 | 28-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127485E+10 | 7554.05 | 27-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247695E+10 | 7683.47 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377829E+10 | 7685.33 | 16-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12470352.95 | 3704.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.377829E+10 | 7685.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369149E+10 | 7454.93 | 14-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304333E+10 | 7454.18 | 25-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263328E+10 | 7453.29 | 15-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.797100E+09 | 7255.95 | 10-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.548138E+09 | 3586.06 | 20-MAY-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113821E+09 | 3727.03 | 16-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 53075283.53 | 3705.47 | 04-JUL-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11077838.14 | 2696.20 | 28-AUG-21:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185120E+09 | 3430.90 | 07-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160399E+10 | 7338.25 | 27-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288290E+10 | 7454.68 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413946E+10 | 7456.62 | 16-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11077838.14 | 2696.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413946E+10 | 7456.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116416E+10 | 2373.79 | 28-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.897344E+09 | 2373.69 | 01-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.878901E+09 | 2373.20 | 16-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280620E+09 | 2337.35 | 10-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208941E+09 | 2298.71 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47471738.97 | 897.35 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36236066.92 | 1064.05 | 01-JUL-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13985270.43 | 975.44 | 23-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86221469.56 | 1081.05 | 05-SEP-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.526803E+09 | 2367.92 | 27-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.927577E+09 | 2373.77 | 23-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139209E+10 | 2373.66 | 02-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13985270.43 | 897.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139209E+10 | 2373.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134159E+10 | 2292.07 | 28-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105470E+10 | 2291.96 | 01-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.952752E+09 | 2291.46 | 16-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.355011E+09 | 2266.60 | 10-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234477E+09 | 2222.83 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45940155.14 | 912.83 | 24-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33758322.67 | 913.84 | 03-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10733653.43 | 821.04 | 23-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120229E+09 | 1663.96 | 20-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.642716E+09 | 2289.38 | 27-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105410E+10 | 2292.05 | 23-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150770E+10 | 2291.92 | 02-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.735371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10733653.43 | 821.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150770E+10 | 2292.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290248E+10 | 12104.48 | 04-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216939E+10 | 11891.18 | 15-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242420E+10 | 12021.05 | 15-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.497695E+09 | 8572.04 | 10-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.436216E+09 | 4995.85 | 02-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73417509.51 | 5476.62 | 08-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 52521339.62 | 5214.76 | 08-JUL-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15791375.07 | 5354.43 | 09-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63157560.05 | 5279.07 | 06-SEP-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.940544E+09 | 11807.89 | 19-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214879E+10 | 12106.21 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419422E+10 | 12108.74 | 16-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15791375.07 | 4995.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419422E+10 | 12108.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.175670E+09 | 0.175670E+09 | 4446.03 | 13-JAN-06:10 | 4446.03 | 0.00 |
February | 0.00 | 0.00 | 0.147843E+09 | 0.147843E+09 | 4475.40 | 24-FEB-06:10 | 4475.40 | 0.02 |
March | 0.00 | 0.00 | 0.104172E+09 | 0.104172E+09 | 6254.01 | 26-MAR-10:35 | 6254.01 | 0.00 |
April | 0.00 | 0.00 | 0.162524E+11 | 0.162365E+11 | 186952.32 | 30-APR-18:10 | 186952.32 | 0.04 |
May | 0.00 | 0.00 | 0.168952E+11 | 0.168952E+11 | 156471.28 | 22-MAY-15:35 | 156471.28 | 0.09 |
June | 0.00 | 0.00 | 0.535301E+11 | 0.505388E+11 | 369371.70 | 25-JUN-18:00 | 163828.88 | 0.33 |
July | 0.00 | 0.00 | 0.916536E+11 | 0.898927E+11 | 234610.91 | 22-JUL-10:35 | 190110.60 | 0.51 |
August | 0.00 | 0.00 | 0.108037E+12 | 0.106329E+12 | 209569.43 | 14-AUG-18:10 | 209569.43 | 0.57 |
September | 0.00 | 0.00 | 0.567209E+11 | 0.560071E+11 | 191846.07 | 11-SEP-17:10 | 171608.08 | 0.38 |
October | 0.00 | 0.00 | 0.327669E+10 | 0.327669E+10 | 79748.30 | 07-OCT-15:13 | 79748.30 | 0.01 |
November | 0.00 | 0.00 | 0.162437E+09 | 0.162437E+09 | 35443.04 | 24-NOV-11:50 | 35443.04 | 0.00 |
December | 0.00 | 0.00 | 0.153516E+09 | 0.153516E+09 | 4506.94 | 12-DEC-06:10 | 4506.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347109E+12 | 0.339920E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.104172E+09 | 0.104172E+09 | 4446.03 | 4446.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108037E+12 | 0.106329E+12 | 369371.70 | 209569.43 | 0.57 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.799630E+09 | 0.799630E+09 | 17041.18 | 30-APR-18:01 | 17041.18 | 0.02 |
May | 0.00 | 0.00 | 0.835620E+09 | 0.835620E+09 | 16769.99 | 22-MAY-15:12 | 16769.99 | 0.05 |
June | 0.00 | 0.00 | 0.269652E+10 | 0.248173E+10 | 31376.35 | 25-JUN-18:04 | 14441.62 | 0.16 |
July | 0.00 | 0.00 | 0.488968E+10 | 0.470524E+10 | 20042.47 | 23-JUL-16:00 | 14923.03 | 0.29 |
August | 0.00 | 0.00 | 0.564050E+10 | 0.542979E+10 | 18985.85 | 14-AUG-12:15 | 15893.51 | 0.35 |
September | 0.00 | 0.00 | 0.283360E+10 | 0.274466E+10 | 18738.57 | 13-SEP-15:13 | 16297.82 | 0.19 |
October | 0.00 | 0.00 | 0.140689E+09 | 0.140689E+09 | 8213.74 | 07-OCT-15:11 | 8213.74 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.178362E+11 | 0.171374E+11 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.564050E+10 | 0.542979E+10 | 31376.35 | 17041.18 | 0.35 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12484579.56 | 7015578.43 | 8197.29 | 19-JAN-16:11 | 8197.29 | 0.00 |
February | 0.00 | 0.00 | 40483466.15 | 24207588.94 | 10668.87 | 17-FEB-16:12 | 10668.87 | 0.01 |
March | 0.00 | 0.00 | 31496504.19 | 16734555.17 | 8043.53 | 23-MAR-18:03 | 8043.53 | 0.01 |
April | 0.00 | 0.00 | 0.107671E+10 | 0.673555E+09 | 11176.95 | 12-APR-15:11 | 11176.95 | 0.28 |
May | 0.00 | 0.00 | 0.141709E+10 | 0.798557E+09 | 10995.91 | 11-MAY-18:01 | 10995.91 | 0.37 |
June | 0.00 | 0.00 | 0.261921E+10 | 0.133965E+10 | 11171.90 | 27-JUN-15:11 | 9408.30 | 0.64 |
July | 0.00 | 0.00 | 0.362958E+10 | 0.185273E+10 | 11186.40 | 18-JUL-15:11 | 9271.19 | 0.71 |
August | 0.00 | 0.00 | 0.336565E+10 | 0.158941E+10 | 11344.28 | 09-AUG-15:11 | 9224.16 | 0.78 |
September | 0.00 | 0.00 | 0.217471E+10 | 0.104877E+10 | 11105.19 | 16-SEP-08:62 | 7852.48 | 0.60 |
October | 0.00 | 0.00 | 0.339433E+09 | 0.192934E+09 | 10748.74 | 06-OCT-18:02 | 10748.74 | 0.11 |
November | 0.00 | 0.00 | 17561448.23 | 8885635.48 | 8546.65 | 10-NOV-16:11 | 8546.65 | 0.01 |
December | 0.00 | 0.00 | 6231214.78 | 3024596.75 | 3349.91 | 05-DEC-19:04 | 2096.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147307E+11 | 0.755547E+10 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 6231214.78 | 3024596.75 | 3349.91 | 2096.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.362958E+10 | 0.185273E+10 | 11344.28 | 11176.95 | 0.78 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6936950.71 | 2862805.46 | 3149.70 | 18-JAN-19:04 | 1730.45 | 0.00 |
February | 0.00 | 0.00 | 10655226.17 | 4968390.84 | 7538.90 | 27-FEB-16:11 | 7538.90 | 0.00 |
March | 0.00 | 0.00 | 19017624.15 | 8648887.36 | 7163.94 | 23-MAR-18:03 | 7163.94 | 0.01 |
April | 0.00 | 0.00 | 0.547857E+09 | 0.341008E+09 | 10095.20 | 14-APR-15:11 | 10095.20 | 0.17 |
May | 0.00 | 0.00 | 0.866411E+09 | 0.452345E+09 | 9919.07 | 25-MAY-17:21 | 9919.07 | 0.28 |
June | 0.00 | 0.00 | 0.187921E+10 | 0.919135E+09 | 11120.37 | 26-JUN-21:01 | 8459.90 | 0.53 |
July | 0.00 | 0.00 | 0.223271E+10 | 0.103278E+10 | 10571.27 | 23-JUL-21:31 | 8641.60 | 0.52 |
August | 0.00 | 0.00 | 0.163538E+10 | 0.625259E+09 | 10504.79 | 11-AUG-19:12 | 7876.20 | 0.53 |
September | 0.00 | 0.00 | 0.794692E+09 | 0.291814E+09 | 10150.64 | 10-SEP-20:32 | 7738.92 | 0.37 |
October | 0.00 | 0.00 | 97299989.30 | 51604494.43 | 9419.20 | 06-OCT-18:02 | 9419.20 | 0.04 |
November | 0.00 | 0.00 | 10727891.39 | 4448203.11 | 4330.27 | 24-NOV-16:14 | 2458.17 | 0.00 |
December | 0.00 | 0.00 | 4427852.70 | 1972170.80 | 2923.48 | 05-DEC-19:04 | 1785.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.810533E+10 | 0.373684E+10 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 4427852.70 | 1972170.80 | 2923.48 | 1730.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223271E+10 | 0.103278E+10 | 11120.37 | 10095.20 | 0.53 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.936060E+10 | 0.691507E+10 | 25009.44 | 30-APR-13:05 | 16013.34 | 0.16 |
May | 0.00 | 0.00 | 0.795991E+10 | 0.389986E+10 | 18877.27 | 23-MAY-13:15 | 8431.76 | 0.32 |
June | 0.00 | 0.00 | 0.131546E+11 | 0.381744E+10 | 21366.92 | 13-JUN-13:15 | 10433.24 | 0.68 |
July | 0.00 | 0.00 | 0.190979E+11 | 0.624485E+10 | 24948.39 | 22-JUL-13:15 | 14641.88 | 0.81 |
August | 0.00 | 0.00 | 0.242785E+11 | 0.894841E+10 | 25778.47 | 19-AUG-13:00 | 14747.46 | 0.88 |
September | 0.00 | 0.00 | 0.233518E+11 | 0.101724E+11 | 31616.88 | 12-SEP-12:30 | 22057.26 | 0.80 |
October | 0.00 | 0.00 | 0.656621E+10 | 0.391058E+10 | 26304.36 | 07-OCT-13:15 | 26304.36 | 0.19 |
November | 0.00 | 0.00 | 6736107.43 | 6736107.43 | 1938.14 | 11-NOV-13:30 | 1938.14 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103776E+12 | 0.439153E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.242785E+11 | 0.101724E+11 | 31616.88 | 26304.36 | 0.88 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.120189E+10 | 0.437697E+09 | 51875.79 | 29-JAN-19:02 | 51875.79 | 0.13 |
February | 0.00 | 0.00 | 0.101185E+10 | 0.382451E+09 | 50058.66 | 01-FEB-09:02 | 50058.66 | 0.15 |
March | 0.00 | 0.00 | 0.350617E+10 | 0.157712E+10 | 57727.27 | 30-MAR-18:03 | 57727.27 | 0.27 |
April | 0.00 | 0.00 | 0.101060E+11 | 0.577360E+10 | 59936.87 | 20-APR-18:01 | 59936.87 | 0.50 |
May | 0.00 | 0.00 | 0.151123E+11 | 0.831269E+10 | 59425.47 | 11-MAY-19:32 | 59425.47 | 0.61 |
June | 0.00 | 0.00 | 0.247211E+11 | 0.144697E+11 | 66991.52 | 26-JUN-21:01 | 52555.45 | 0.61 |
July | 0.00 | 0.00 | 0.259828E+11 | 0.154883E+11 | 64499.96 | 17-JUL-21:52 | 50058.17 | 0.54 |
August | 0.00 | 0.00 | 0.218931E+11 | 0.122612E+11 | 64707.10 | 16-AUG-21:52 | 49721.27 | 0.49 |
September | 0.00 | 0.00 | 0.166722E+11 | 0.841066E+10 | 63297.59 | 10-SEP-20:32 | 49832.37 | 0.58 |
October | 0.00 | 0.00 | 0.684817E+10 | 0.281351E+10 | 59290.62 | 09-OCT-08:62 | 51781.03 | 0.45 |
November | 0.00 | 0.00 | 0.242346E+10 | 0.858801E+09 | 56765.32 | 24-NOV-19:02 | 49299.63 | 0.23 |
December | 0.00 | 0.00 | 0.522130E+09 | 0.204039E+09 | 48800.04 | 30-DEC-09:01 | 48800.04 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.130001E+12 | 0.709897E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.522130E+09 | 0.204039E+09 | 48800.04 | 48800.04 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.259828E+11 | 0.154883E+11 | 66991.52 | 59936.87 | 0.61 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 14763974.59 | 5485385.62 | 3231.12 | 18-JAN-19:04 | 1804.69 | 0.01 |
February | 0.00 | 0.00 | 20930340.47 | 7861060.10 | 6838.53 | 20-FEB-09:02 | 6838.53 | 0.02 |
March | 0.00 | 0.00 | 17024384.79 | 6794042.07 | 2810.29 | 26-MAR-08:62 | 1593.00 | 0.01 |
April | 0.00 | 0.00 | 0.120052E+10 | 0.710663E+09 | 10133.05 | 14-APR-15:11 | 10133.05 | 0.36 |
May | 0.00 | 0.00 | 0.134378E+10 | 0.716633E+09 | 9788.95 | 11-MAY-18:01 | 9788.95 | 0.39 |
June | 0.00 | 0.00 | 0.239744E+10 | 0.116958E+10 | 10231.61 | 26-JUN-18:01 | 8456.63 | 0.63 |
July | 0.00 | 0.00 | 0.330832E+10 | 0.162684E+10 | 10129.55 | 18-JUL-15:11 | 8393.96 | 0.75 |
August | 0.00 | 0.00 | 0.351120E+10 | 0.169872E+10 | 10176.94 | 09-AUG-15:11 | 8138.27 | 0.85 |
September | 0.00 | 0.00 | 0.243611E+10 | 0.121805E+10 | 10161.30 | 16-SEP-08:62 | 7658.11 | 0.67 |
October | 0.00 | 0.00 | 0.355224E+09 | 0.188945E+09 | 9629.93 | 06-OCT-18:02 | 9629.93 | 0.13 |
November | 0.00 | 0.00 | 19843870.70 | 8278858.14 | 7358.01 | 11-NOV-09:02 | 7358.01 | 0.01 |
December | 0.00 | 0.00 | 6999510.30 | 3712059.19 | 3378.70 | 05-DEC-19:04 | 2291.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.146322E+11 | 0.736156E+10 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 6999510.30 | 3712059.19 | 2810.29 | 1593.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.351120E+10 | 0.169872E+10 | 10231.61 | 10133.05 | 0.85 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7119087.13 | 3671523.36 | 3332.60 | 23-JAN-09:03 | 2069.99 | 0.00 |
February | 0.00 | 0.00 | 8678951.47 | 4557071.55 | 3170.52 | 27-FEB-16:14 | 2300.13 | 0.00 |
March | 0.00 | 0.00 | 12879459.56 | 6058028.69 | 2991.82 | 19-MAR-15:15 | 1291.66 | 0.01 |
April | 0.00 | 0.00 | 0.633206E+09 | 0.370064E+09 | 8657.47 | 14-APR-15:11 | 8657.47 | 0.21 |
May | 0.00 | 0.00 | 0.875408E+09 | 0.457112E+09 | 8813.66 | 23-MAY-08:51 | 8813.66 | 0.29 |
June | 0.00 | 0.00 | 0.176286E+10 | 0.857554E+09 | 9820.27 | 26-JUN-21:01 | 7360.02 | 0.51 |
July | 0.00 | 0.00 | 0.216297E+10 | 0.104636E+10 | 9737.27 | 23-JUL-08:51 | 9195.42 | 0.55 |
August | 0.00 | 0.00 | 0.190200E+10 | 0.881274E+09 | 9475.42 | 17-AUG-08:51 | 8347.98 | 0.59 |
September | 0.00 | 0.00 | 0.110218E+10 | 0.521080E+09 | 9174.43 | 10-SEP-20:32 | 6957.75 | 0.41 |
October | 0.00 | 0.00 | 0.112229E+09 | 51172957.06 | 7842.26 | 01-OCT-08:61 | 7842.26 | 0.05 |
November | 0.00 | 0.00 | 9717608.73 | 4507463.10 | 3055.07 | 08-NOV-09:04 | 1635.31 | 0.00 |
December | 0.00 | 0.00 | 4898542.12 | 2408623.90 | 3136.76 | 20-DEC-09:04 | 2127.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.859413E+10 | 0.420582E+10 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 4898542.12 | 2408623.90 | 2991.82 | 1291.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216297E+10 | 0.104636E+10 | 9820.27 | 9195.42 | 0.59 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2367838.17 | 1259245.35 | 2158.05 | 19-JAN-16:11 | 2158.05 | 0.00 |
February | 0.00 | 0.00 | 8329052.62 | 4791107.62 | 2778.19 | 17-FEB-16:12 | 2778.19 | 0.01 |
March | 0.00 | 0.00 | 7510949.28 | 3655635.77 | 2125.36 | 23-MAR-18:03 | 2125.36 | 0.01 |
April | 0.00 | 0.00 | 0.327458E+09 | 0.220046E+09 | 2942.49 | 12-APR-15:11 | 2942.49 | 0.26 |
May | 0.00 | 0.00 | 0.407239E+09 | 0.249540E+09 | 2942.35 | 11-MAY-18:01 | 2942.35 | 0.33 |
June | 0.00 | 0.00 | 0.726287E+09 | 0.404405E+09 | 3065.79 | 27-JUN-08:62 | 2214.87 | 0.57 |
July | 0.00 | 0.00 | 0.986897E+09 | 0.542834E+09 | 3007.45 | 25-JUL-08:62 | 2172.84 | 0.70 |
August | 0.00 | 0.00 | 0.871325E+09 | 0.449963E+09 | 3007.90 | 17-AUG-08:62 | 2006.47 | 0.74 |
September | 0.00 | 0.00 | 0.538283E+09 | 0.282875E+09 | 2979.15 | 02-SEP-08:62 | 2171.18 | 0.50 |
October | 0.00 | 0.00 | 83376375.99 | 51492782.03 | 2846.88 | 10-OCT-15:11 | 2546.85 | 0.08 |
November | 0.00 | 0.00 | 4046757.37 | 2072215.80 | 2257.50 | 10-NOV-16:11 | 2257.50 | 0.00 |
December | 0.00 | 0.00 | 601609.88 | 307445.27 | 894.01 | 20-DEC-19:05 | 490.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.396372E+10 | 0.221324E+10 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 601609.88 | 307445.27 | 894.01 | 490.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.986897E+09 | 0.542834E+09 | 3065.79 | 2942.49 | 0.74 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1711631.00 | 817489.37 | 841.50 | 25-JAN-16:14 | 552.18 | 0.00 |
February | 0.00 | 0.00 | 3171741.26 | 1812145.68 | 1939.35 | 27-FEB-16:11 | 1908.86 | 0.00 |
March | 0.00 | 0.00 | 5233336.72 | 2527126.64 | 1809.48 | 23-MAR-18:03 | 1754.16 | 0.01 |
April | 0.00 | 0.00 | 0.171201E+09 | 0.113245E+09 | 2646.91 | 14-APR-15:11 | 2646.91 | 0.16 |
May | 0.00 | 0.00 | 0.255012E+09 | 0.145669E+09 | 2646.43 | 25-MAY-17:21 | 2646.43 | 0.25 |
June | 0.00 | 0.00 | 0.531198E+09 | 0.284699E+09 | 3062.92 | 26-JUN-21:01 | 2281.17 | 0.48 |
July | 0.00 | 0.00 | 0.631335E+09 | 0.312678E+09 | 2945.56 | 24-JUL-20:01 | 2410.48 | 0.51 |
August | 0.00 | 0.00 | 0.416843E+09 | 0.174139E+09 | 2791.13 | 11-AUG-19:12 | 2102.31 | 0.50 |
September | 0.00 | 0.00 | 0.179834E+09 | 71237261.81 | 2692.01 | 10-SEP-20:32 | 2040.61 | 0.28 |
October | 0.00 | 0.00 | 23757343.17 | 13087266.20 | 2455.05 | 06-OCT-18:02 | 2455.05 | 0.02 |
November | 0.00 | 0.00 | 2543147.89 | 1276861.72 | 950.89 | 05-NOV-15:13 | 817.90 | 0.00 |
December | 0.00 | 0.00 | 347522.08 | 156998.43 | 802.32 | 16-DEC-09:05 | 445.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222219E+10 | 0.112135E+10 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 347522.08 | 156998.43 | 802.32 | 445.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.631335E+09 | 0.312678E+09 | 3062.92 | 2646.91 | 0.51 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.274572E+09 | 0.115696E+09 | 16673.45 | 11-JAN-16:12 | 16673.45 | 0.10 |
February | 0.00 | 0.00 | 0.388693E+09 | 0.175731E+09 | 14354.66 | 27-FEB-16:11 | 14354.66 | 0.13 |
March | 0.00 | 0.00 | 0.117225E+09 | 52221664.53 | 14128.72 | 25-MAR-15:12 | 14128.72 | 0.05 |
April | 0.00 | 0.00 | 0.295655E+10 | 0.166643E+10 | 14599.74 | 23-APR-08:62 | 14599.74 | 0.51 |
May | 0.00 | 0.00 | 0.259304E+10 | 0.125746E+10 | 16760.83 | 11-MAY-18:01 | 16760.83 | 0.51 |
June | 0.00 | 0.00 | 0.402969E+10 | 0.181145E+10 | 17724.15 | 26-JUN-18:01 | 14020.19 | 0.72 |
July | 0.00 | 0.00 | 0.542355E+10 | 0.249729E+10 | 16757.24 | 08-JUL-08:62 | 14103.19 | 0.78 |
August | 0.00 | 0.00 | 0.613585E+10 | 0.290420E+10 | 17427.17 | 09-AUG-15:11 | 14110.54 | 0.85 |
September | 0.00 | 0.00 | 0.561310E+10 | 0.293937E+10 | 17035.93 | 16-SEP-15:13 | 12546.44 | 0.79 |
October | 0.00 | 0.00 | 0.168805E+10 | 0.863378E+09 | 16302.19 | 09-OCT-08:62 | 13164.09 | 0.33 |
November | 0.00 | 0.00 | 0.244236E+09 | 95460824.87 | 14581.52 | 10-NOV-16:11 | 14581.52 | 0.09 |
December | 0.00 | 0.00 | 49396800.09 | 23881788.90 | 15878.10 | 26-DEC-16:11 | 15878.10 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.295140E+11 | 0.144026E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 49396800.09 | 23881788.90 | 14128.72 | 12546.44 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.613585E+10 | 0.293937E+10 | 17724.15 | 16760.83 | 0.85 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5.16 | 3634.59 | 02-JAN-22:10 | 43000.25 | 186171.62 | 08-JAN-16:11 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 44061.64 | 169850.52 | 25-FEB-16:11 |
March | 2.86 | 1202.21 | 19-MAR-20:30 | 40148.65 | 175708.95 | 15-MAR-15:11 |
April | 11.04 | 7371.90 | 19-APR-15:15 | 20207.88 | 95974.06 | 01-APR-08:07 |
May | 1.04 | 1175.48 | 06-MAY-05:40 | 14394.49 | 86881.31 | 06-MAY-04:10 |
June | 16.55 | 3892.86 | 17-JUN-08:20 | 2939.67 | 51847.54 | 08-JUN-04:00 |
July | 2.96 | 1235.84 | 01-JUL-03:20 | 1387.77 | 38318.42 | 06-JUL-04:00 |
August | 0.02 | 24.24 | 13-AUG-18:00 | 573.70 | 34191.19 | 30-AUG-08:06 |
September | 13.44 | 2444.81 | 18-SEP-08:05 | 3583.39 | 60239.51 | 20-SEP-04:00 |
October | 21.58 | 1666.16 | 13-OCT-04:50 | 19290.21 | 109757.12 | 19-OCT-15:13 |
November | 2.35 | 1012.32 | 08-NOV-21:20 | 37245.15 | 165117.91 | 29-NOV-16:13 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 55541.65 | 174129.22 | 28-DEC-16:13 |
Annual Sum or Average | 6.42 | 23445.06 | ||||
Minimum of Months | 0.00 | 0.00 | 573.70 | 34191.19 | ||
Maximum of Months | 21.58 | 7371.90 | 55541.65 | 186171.62 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1370.53 | 43356.08 | 21-JAN-09:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1415.64 | 54034.83 | 20-FEB-09:02 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 2130.88 | 43531.68 | 20-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 18445.93 | 319064.52 | 30-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 19959.94 | 221983.74 | 22-MAY-15:13 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 43926.05 | 440330.61 | 25-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 62183.11 | 374410.63 | 22-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 68884.18 | 349856.31 | 14-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 45678.66 | 248976.34 | 13-SEP-15:25 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8515.11 | 141792.65 | 07-OCT-15:13 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1761.34 | 48333.84 | 11-NOV-09:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 764.03 | 44543.43 | 31-DEC-09:01 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 23046.68 | 0.00 | ||||
Minimum of Months | 764.03 | 43356.08 | 0.00 | 0.00 | ||
Maximum of Months | 68884.18 | 440330.61 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 28108.32 | 57272.08 | 30-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 28289.99 | 57365.02 | 10-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 28129.74 | 57288.42 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27610.33 | 56423.70 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26917.38 | 55213.75 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26226.31 | 53670.44 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25687.72 | 52304.04 | 03-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25519.67 | 51623.24 | 02-AUG-06:53 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25693.25 | 52285.16 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26195.41 | 53660.95 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26894.59 | 55196.87 | 30-NOV-07:53 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 27591.56 | 56451.87 | 28-DEC-07:53 |
Annual Sum or Average | 0.00 | 26897.26 | ||||
Minimum of Months | 0.00 | 0.00 | 25519.67 | 51623.24 | ||
Maximum of Months | 0.00 | 0.00 | 28289.99 | 57365.02 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.68 | 1299.30 | 01-JAN-16:14 | 0.89 |
February | 0.236042E+10 | 0.68 | 1299.30 | 03-FEB-19:03 | 0.88 |
March | 0.261333E+10 | 0.68 | 1299.30 | 11-MAR-09:10 | 0.88 |
April | 0.252903E+10 | 0.68 | 1299.30 | 02-APR-08:10 | 0.88 |
May | 0.261333E+10 | 0.67 | 1299.30 | 01-MAY-18:40 | 0.88 |
June | 0.252903E+10 | 0.67 | 1299.30 | 01-JUN-19:00 | 0.88 |
July | 0.261333E+10 | 0.67 | 1299.30 | 01-JUL-08:10 | 0.88 |
August | 0.261333E+10 | 0.67 | 1299.30 | 01-AUG-06:05 | 0.88 |
September | 0.252903E+10 | 0.67 | 1299.30 | 01-SEP-06:15 | 0.88 |
October | 0.261333E+10 | 0.67 | 1299.30 | 01-OCT-18:07 | 0.88 |
November | 0.252903E+10 | 0.67 | 1299.30 | 14-NOV-19:15 | 0.88 |
December | 0.261333E+10 | 0.68 | 1299.30 | 01-DEC-19:03 | 0.88 |
Annual Sum or Average | 0.307698E+11 | 0.67 | |||
Minimum of Months | 0.236042E+10 | 0.67 | 1299.30 | 0.88 | |
Maximum of Months | 0.261333E+10 | 0.68 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.427262E+11 | 0.98 | 22326.57 | 19-JAN-20:10 | 1.20 |
February | 0.386535E+11 | 0.98 | 22330.24 | 06-FEB-20:10 | 1.20 |
March | 0.429757E+11 | 0.98 | 22330.24 | 01-MAR-20:10 | 1.20 |
April | 0.420400E+11 | 0.99 | 22407.23 | 28-APR-19:02 | 1.20 |
May | 0.435409E+11 | 0.99 | 22477.98 | 23-MAY-19:10 | 1.21 |
June | 0.424793E+11 | 0.99 | 22886.69 | 13-JUN-19:20 | 1.21 |
July | 0.440447E+11 | 0.99 | 22848.96 | 21-JUL-19:20 | 1.21 |
August | 0.441141E+11 | 0.99 | 22625.76 | 14-AUG-20:20 | 1.21 |
September | 0.423893E+11 | 0.99 | 22529.24 | 13-SEP-19:31 | 1.20 |
October | 0.432248E+11 | 0.99 | 22324.16 | 02-OCT-19:20 | 1.20 |
November | 0.415297E+11 | 0.98 | 22330.24 | 16-NOV-20:10 | 1.20 |
December | 0.425848E+11 | 0.98 | 22330.24 | 04-DEC-20:10 | 1.20 |
Annual Sum or Average | 0.510303E+12 | 0.99 | |||
Minimum of Months | 0.386535E+11 | 0.98 | 22324.16 | 1.20 | |
Maximum of Months | 0.441141E+11 | 0.99 | 22886.69 | 1.21 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:05 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:05 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:10 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:05 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:10 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173321E+09 | 0.41 | 549.50 | 01-JAN-16:11 | 0.58 |
February | 0.140239E+09 | 0.39 | 549.50 | 01-FEB-09:02 | 0.58 |
March | 0.143380E+09 | 0.40 | 549.50 | 01-MAR-09:02 | 0.58 |
April | 0.109755E+09 | 0.42 | 549.50 | 01-APR-15:11 | 0.58 |
May | 0.111353E+09 | 0.42 | 549.50 | 01-MAY-15:11 | 0.58 |
June | 0.128928E+09 | 0.44 | 549.50 | 01-JUN-08:61 | 0.58 |
July | 0.170302E+09 | 0.46 | 549.50 | 01-JUL-08:62 | 0.58 |
August | 0.154309E+09 | 0.46 | 549.50 | 01-AUG-08:62 | 0.58 |
September | 0.116952E+09 | 0.45 | 549.50 | 01-SEP-15:11 | 0.58 |
October | 0.108394E+09 | 0.40 | 549.50 | 01-OCT-08:61 | 0.58 |
November | 0.146139E+09 | 0.40 | 549.50 | 01-NOV-08:62 | 0.58 |
December | 0.201109E+09 | 0.43 | 549.50 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.170418E+10 | 0.42 | |||
Minimum of Months | 0.108394E+09 | 0.39 | 549.50 | 0.58 | |
Maximum of Months | 0.201109E+09 | 0.46 | 549.50 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182855E+09 | 0.42 | 497.50 | 01-JAN-09:02 | 0.58 |
February | 0.147325E+09 | 0.40 | 497.50 | 01-FEB-09:02 | 0.58 |
March | 0.142099E+09 | 0.40 | 497.50 | 01-MAR-09:02 | 0.58 |
April | 91510261.73 | 0.39 | 497.50 | 01-APR-18:02 | 0.58 |
May | 85926061.09 | 0.39 | 497.50 | 01-MAY-15:11 | 0.58 |
June | 93012587.15 | 0.38 | 497.50 | 01-JUN-08:61 | 0.58 |
July | 0.103131E+09 | 0.35 | 497.50 | 01-JUL-08:62 | 0.58 |
August | 75378140.77 | 0.32 | 497.50 | 01-AUG-08:51 | 0.58 |
September | 58311269.56 | 0.36 | 497.50 | 01-SEP-19:12 | 0.58 |
October | 0.106543E+09 | 0.39 | 497.50 | 01-OCT-15:11 | 0.58 |
November | 0.150966E+09 | 0.40 | 497.50 | 01-NOV-08:62 | 0.58 |
December | 0.201603E+09 | 0.44 | 497.50 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.143866E+10 | 0.39 | |||
Minimum of Months | 58311269.56 | 0.32 | 497.50 | 0.58 | |
Maximum of Months | 0.201603E+09 | 0.44 | 497.50 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.393635E+09 | 0.25 | 845.48 | 30-APR-13:20 | 0.58 |
May | 0.355182E+09 | 0.27 | 624.00 | 23-MAY-13:30 | 0.58 |
June | 0.535473E+09 | 0.40 | 689.10 | 13-JUN-13:15 | 0.58 |
July | 0.731357E+09 | 0.47 | 804.62 | 22-JUL-13:30 | 0.58 |
August | 0.901512E+09 | 0.51 | 819.38 | 20-AUG-13:00 | 0.58 |
September | 0.877946E+09 | 0.47 | 995.91 | 25-SEP-13:25 | 0.58 |
October | 0.270594E+09 | 0.15 | 861.14 | 07-OCT-13:15 | 0.58 |
November | 525032.46 | 0.00 | 130.57 | 11-NOV-13:30 | 0.58 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.406622E+10 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.901512E+09 | 0.51 | 995.91 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.572178E+09 | 0.39 | 3011.25 | 01-JAN-09:02 | 0.58 |
February | 0.463769E+09 | 0.39 | 3011.25 | 01-FEB-09:02 | 0.58 |
March | 0.439528E+09 | 0.39 | 3011.25 | 01-MAR-09:02 | 0.58 |
April | 0.586164E+09 | 0.38 | 3011.25 | 01-APR-08:62 | 0.58 |
May | 0.740196E+09 | 0.37 | 3011.25 | 01-MAY-08:62 | 0.58 |
June | 0.105592E+10 | 0.36 | 3011.25 | 01-JUN-08:61 | 0.58 |
July | 0.109633E+10 | 0.31 | 3011.25 | 01-JUL-08:62 | 0.58 |
August | 0.903512E+09 | 0.28 | 3011.25 | 01-AUG-08:51 | 0.58 |
September | 0.731016E+09 | 0.34 | 3011.25 | 01-SEP-08:53 | 0.58 |
October | 0.431697E+09 | 0.39 | 3011.25 | 01-OCT-08:61 | 0.58 |
November | 0.427827E+09 | 0.39 | 3011.25 | 01-NOV-08:62 | 0.58 |
December | 0.594033E+09 | 0.39 | 3011.25 | 01-DEC-16:11 | 0.58 |
Annual Sum or Average | 0.804217E+10 | 0.37 | |||
Minimum of Months | 0.427827E+09 | 0.28 | 3011.25 | 0.58 | |
Maximum of Months | 0.109633E+10 | 0.39 | 3011.25 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160931E+09 | 0.40 | 497.82 | 01-JAN-16:11 | 0.58 |
February | 0.133122E+09 | 0.39 | 497.82 | 01-FEB-09:02 | 0.58 |
March | 0.133609E+09 | 0.40 | 497.82 | 01-MAR-09:02 | 0.58 |
April | 0.105990E+09 | 0.44 | 497.82 | 01-APR-15:11 | 0.58 |
May | 0.100982E+09 | 0.43 | 497.82 | 01-MAY-08:62 | 0.58 |
June | 0.117828E+09 | 0.45 | 497.82 | 01-JUN-08:61 | 0.58 |
July | 0.149676E+09 | 0.48 | 497.82 | 01-JUL-08:62 | 0.58 |
August | 0.156486E+09 | 0.50 | 497.82 | 01-AUG-08:62 | 0.58 |
September | 0.122179E+09 | 0.48 | 497.82 | 01-SEP-15:11 | 0.58 |
October | 0.101624E+09 | 0.41 | 497.82 | 01-OCT-08:61 | 0.58 |
November | 0.135986E+09 | 0.40 | 497.82 | 01-NOV-08:62 | 0.58 |
December | 0.183869E+09 | 0.43 | 497.82 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.160228E+10 | 0.43 | |||
Minimum of Months | 0.100982E+09 | 0.39 | 497.82 | 0.58 | |
Maximum of Months | 0.183869E+09 | 0.50 | 497.82 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171340E+09 | 0.43 | 451.36 | 01-JAN-16:11 | 0.58 |
February | 0.142164E+09 | 0.40 | 451.36 | 01-FEB-09:02 | 0.58 |
March | 0.133565E+09 | 0.40 | 451.36 | 01-MAR-09:02 | 0.58 |
April | 84927163.48 | 0.39 | 451.36 | 03-APR-08:62 | 0.58 |
May | 80818910.93 | 0.38 | 451.36 | 01-MAY-08:62 | 0.58 |
June | 89889412.78 | 0.39 | 451.36 | 01-JUN-08:61 | 0.58 |
July | 0.100482E+09 | 0.37 | 451.36 | 01-JUL-08:62 | 0.58 |
August | 87138749.36 | 0.36 | 451.36 | 01-AUG-08:51 | 0.58 |
September | 67122669.76 | 0.36 | 451.36 | 01-SEP-19:12 | 0.58 |
October | 98960824.38 | 0.39 | 451.36 | 01-OCT-08:61 | 0.58 |
November | 0.141106E+09 | 0.40 | 451.36 | 01-NOV-08:62 | 0.58 |
December | 0.184905E+09 | 0.44 | 451.36 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.138242E+10 | 0.39 | |||
Minimum of Months | 67122669.76 | 0.36 | 451.36 | 0.58 | |
Maximum of Months | 0.184905E+09 | 0.44 | 451.36 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 54418551.54 | 0.44 | 144.71 | 01-JAN-09:02 | 0.58 |
February | 43461722.04 | 0.41 | 144.71 | 01-FEB-09:02 | 0.58 |
March | 44302784.85 | 0.40 | 144.71 | 01-MAR-09:02 | 0.58 |
April | 35189219.87 | 0.43 | 144.71 | 01-APR-15:11 | 0.58 |
May | 34272427.47 | 0.43 | 144.71 | 01-MAY-15:11 | 0.58 |
June | 38105794.81 | 0.46 | 144.71 | 01-JUN-08:61 | 0.58 |
July | 48131084.04 | 0.48 | 144.71 | 01-JUL-15:11 | 0.58 |
August | 41155364.76 | 0.48 | 144.71 | 01-AUG-15:11 | 0.58 |
September | 32353421.46 | 0.45 | 144.71 | 01-SEP-15:11 | 0.58 |
October | 34398786.47 | 0.40 | 144.71 | 01-OCT-15:11 | 0.58 |
November | 45692505.04 | 0.41 | 144.71 | 01-NOV-08:62 | 0.58 |
December | 62207303.86 | 0.47 | 144.71 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.513689E+09 | 0.44 | |||
Minimum of Months | 32353421.46 | 0.40 | 144.71 | 0.58 | |
Maximum of Months | 62207303.86 | 0.48 | 144.71 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 56910437.85 | 0.47 | 130.08 | 01-JAN-09:02 | 0.58 |
February | 45400607.90 | 0.42 | 130.08 | 01-FEB-09:02 | 0.58 |
March | 43517838.60 | 0.40 | 130.08 | 01-MAR-09:02 | 0.58 |
April | 28953227.66 | 0.40 | 130.08 | 01-APR-15:11 | 0.58 |
May | 26596242.06 | 0.39 | 130.08 | 01-MAY-15:11 | 0.58 |
June | 27944190.78 | 0.39 | 130.08 | 01-JUN-08:61 | 0.58 |
July | 30157304.80 | 0.36 | 130.08 | 01-JUL-08:62 | 0.58 |
August | 19601562.69 | 0.33 | 130.08 | 01-AUG-08:51 | 0.58 |
September | 17040171.01 | 0.36 | 130.08 | 01-SEP-19:12 | 0.58 |
October | 33929464.04 | 0.39 | 130.08 | 01-OCT-15:11 | 0.58 |
November | 46795405.92 | 0.43 | 130.08 | 01-NOV-08:62 | 0.58 |
December | 62263412.32 | 0.51 | 130.08 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.439110E+09 | 0.41 | |||
Minimum of Months | 17040171.01 | 0.33 | 130.08 | 0.58 | |
Maximum of Months | 62263412.32 | 0.51 | 130.08 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.195061E+09 | 0.42 | 839.16 | 01-JAN-16:11 | 0.58 |
February | 0.162426E+09 | 0.42 | 839.16 | 01-FEB-09:02 | 0.58 |
March | 0.168059E+09 | 0.39 | 839.16 | 01-MAR-09:02 | 0.58 |
April | 0.195477E+09 | 0.47 | 839.16 | 01-APR-15:11 | 0.58 |
May | 0.165796E+09 | 0.46 | 839.16 | 01-MAY-15:11 | 0.58 |
June | 0.188199E+09 | 0.47 | 839.16 | 01-JUN-08:61 | 0.58 |
July | 0.240646E+09 | 0.49 | 839.16 | 01-JUL-08:62 | 0.58 |
August | 0.267037E+09 | 0.50 | 839.16 | 01-AUG-15:11 | 0.58 |
September | 0.256939E+09 | 0.50 | 839.16 | 01-SEP-15:11 | 0.58 |
October | 0.159536E+09 | 0.44 | 839.16 | 01-OCT-08:61 | 0.58 |
November | 0.160076E+09 | 0.41 | 839.16 | 01-NOV-15:11 | 0.58 |
December | 0.240438E+09 | 0.42 | 839.16 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.239969E+10 | 0.45 | |||
Minimum of Months | 0.159536E+09 | 0.39 | 839.16 | 0.58 | |
Maximum of Months | 0.267037E+09 | 0.50 | 839.16 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.134339E+10 | 0.122114E+10 | 1251.35 | 08-JAN-16:11 | 1137.48 | 1137.48 | 36.67 | 1.91 |
February | 0.116890E+10 | 0.106253E+10 | 1174.22 | 16-FEB-09:03 | 1067.37 | 1067.37 | 36.85 | 1.72 |
March | 0.114802E+10 | 0.104355E+10 | 1212.74 | 15-MAR-15:11 | 1102.38 | 1102.38 | 36.81 | 1.81 |
April | 0.545686E+09 | 0.496029E+09 | 922.10 | 09-APR-06:40 | 838.19 | 838.19 | 42.60 | 1.21 |
May | 0.388073E+09 | 0.352758E+09 | 875.06 | 06-MAY-04:10 | 795.43 | 795.43 | 41.60 | 1.13 |
June | 80689832.83 | 73347058.04 | 527.22 | 08-JUN-04:00 | 479.25 | 479.25 | 39.71 | 0.61 |
July | 42704364.58 | 38818267.41 | 382.63 | 05-JUL-05:00 | 347.81 | 347.81 | 39.17 | 0.43 |
August | 15210657.99 | 13826488.11 | 326.19 | 18-AUG-08:54 | 296.50 | 296.50 | 41.58 | 0.36 |
September | 0.107716E+09 | 97913397.56 | 592.26 | 20-SEP-04:00 | 538.36 | 538.36 | 39.40 | 0.70 |
October | 0.607297E+09 | 0.552033E+09 | 895.03 | 23-OCT-04:00 | 813.58 | 813.58 | 41.87 | 1.16 |
November | 0.106817E+10 | 0.970967E+09 | 1189.20 | 29-NOV-16:13 | 1080.98 | 1080.98 | 37.50 | 1.76 |
December | 0.157841E+10 | 0.143477E+10 | 1240.39 | 28-DEC-16:13 | 1127.52 | 1127.52 | 37.85 | 1.88 |
Annual Sum or Average | 0.809426E+10 | 0.735768E+10 | ||||||
Minimum of Months | 15210657.99 | 13826488.11 | 326.19 | 296.50 | 296.50 | 36.67 | 0.36 | |
Maximum of Months | 0.157841E+10 | 0.143477E+10 | 1251.35 | 1137.48 | 1137.48 | 42.60 | 1.91 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 63549637.49 | 57766620.48 | 863.16 | 21-JAN-09:02 | 784.61 | 784.61 | 6.72 | 1.96 |
February | 63351462.30 | 57586479.23 | 949.35 | 20-FEB-09:02 | 862.96 | 862.96 | 6.72 | 2.21 |
March | 0.144776E+09 | 0.131601E+09 | 1015.11 | 20-MAR-18:03 | 922.74 | 922.74 | 6.72 | 2.41 |
April | 0.912094E+09 | 0.829093E+09 | 2213.48 | 30-APR-18:03 | 2012.05 | 2012.05 | 6.72 | 12.18 |
May | 0.106399E+10 | 0.967162E+09 | 1907.12 | 21-MAY-18:03 | 1733.57 | 1733.57 | 6.72 | 6.94 |
June | 0.179100E+10 | 0.162802E+10 | 2170.25 | 25-JUN-18:03 | 1972.76 | 1972.76 | 6.72 | 11.41 |
July | 0.238959E+10 | 0.217214E+10 | 2128.60 | 22-JUL-18:03 | 1934.90 | 1934.90 | 6.72 | 10.54 |
August | 0.264823E+10 | 0.240724E+10 | 2181.51 | 14-AUG-18:03 | 1982.99 | 1982.99 | 6.72 | 11.62 |
September | 0.190888E+10 | 0.173517E+10 | 2019.74 | 27-SEP-16:10 | 1835.95 | 1835.95 | 6.72 | 8.39 |
October | 0.509069E+09 | 0.462744E+09 | 1545.36 | 05-OCT-15:12 | 1404.73 | 1404.73 | 6.72 | 4.43 |
November | 0.104637E+09 | 95114838.54 | 940.48 | 10-NOV-16:11 | 854.90 | 854.90 | 6.72 | 2.18 |
December | 29351891.73 | 26680869.59 | 679.92 | 17-DEC-09:03 | 618.05 | 618.05 | 6.72 | 1.48 |
Annual Sum or Average | 0.116285E+11 | 0.105703E+11 | ||||||
Minimum of Months | 29351891.73 | 26680869.59 | 679.92 | 618.05 | 618.05 | 6.72 | 1.48 | |
Maximum of Months | 0.264823E+10 | 0.240724E+10 | 2213.48 | 2012.05 | 2012.05 | 6.72 | 12.18 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.210622E+10 | 0.191456E+10 | 1845.25 | 01-JAN-00:05 | 1677.34 | 1677.34 | 6.73 | 16.49 |
February | 0.189922E+10 | 0.172639E+10 | 1845.25 | 01-FEB-06:10 | 1677.34 | 1677.34 | 6.74 | 16.49 |
March | 0.193095E+10 | 0.175524E+10 | 1845.25 | 01-MAR-06:20 | 1677.34 | 1677.34 | 6.74 | 16.49 |
April | 0.392725E+10 | 0.356987E+10 | 1845.25 | 01-APR-04:10 | 1677.34 | 1677.34 | 6.73 | 16.49 |
May | 0.434206E+10 | 0.394694E+10 | 1845.25 | 01-MAY-00:10 | 1677.34 | 1677.34 | 7.06 | 16.49 |
June | 0.466056E+10 | 0.423645E+10 | 1845.25 | 01-JUN-00:10 | 1677.34 | 1677.34 | 6.89 | 16.49 |
July | 0.491243E+10 | 0.446540E+10 | 1845.25 | 01-JUL-00:10 | 1677.34 | 1677.34 | 6.86 | 16.49 |
August | 0.494233E+10 | 0.449257E+10 | 1845.25 | 01-AUG-00:10 | 1677.34 | 1677.34 | 6.97 | 16.49 |
September | 0.472477E+10 | 0.429482E+10 | 1845.25 | 01-SEP-00:10 | 1677.34 | 1677.34 | 6.96 | 16.49 |
October | 0.309664E+10 | 0.281484E+10 | 1845.25 | 01-OCT-00:10 | 1677.34 | 1677.34 | 6.78 | 16.49 |
November | 0.172716E+10 | 0.156999E+10 | 1845.25 | 01-NOV-05:10 | 1677.34 | 1677.34 | 6.75 | 16.49 |
December | 0.140790E+10 | 0.127978E+10 | 1845.25 | 01-DEC-07:05 | 1677.34 | 1677.34 | 6.74 | 16.49 |
Annual Sum or Average | 0.396775E+11 | 0.360668E+11 | ||||||
Minimum of Months | 0.140790E+10 | 0.127978E+10 | 1845.25 | 1677.34 | 1677.34 | 6.73 | 16.49 | |
Maximum of Months | 0.494233E+10 | 0.449257E+10 | 1845.25 | 1677.34 | 1677.34 | 7.06 | 16.49 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 47.98 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 48.66 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 48.95 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.60 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 51.79 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 51.78 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.73 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.33 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.48 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.42 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.18 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 48.82 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.98 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.48 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5.16 | 3634.59 | 02-JAN-22:10 | 51.15 | 51.15 | 43000.25 | 186171.62 | 08-JAN-16:11 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 43.24 | 60.00 | 44061.64 | 169850.52 | 25-FEB-16:11 |
March | 2.86 | 1202.21 | 19-MAR-20:30 | 51.07 | 51.07 | 40148.65 | 175708.95 | 15-MAR-15:11 |
April | 11.04 | 7371.90 | 19-APR-15:15 | 52.06 | 52.06 | 20207.88 | 95974.06 | 01-APR-08:07 |
May | 1.04 | 1175.48 | 06-MAY-05:40 | 50.58 | 50.58 | 14394.49 | 86881.31 | 06-MAY-04:10 |
June | 16.55 | 3892.86 | 17-JUN-08:20 | 51.63 | 51.63 | 2939.67 | 51847.54 | 08-JUN-04:00 |
July | 2.96 | 1235.84 | 01-JUL-03:20 | 51.50 | 51.50 | 1387.77 | 38318.42 | 06-JUL-04:00 |
August | 0.02 | 24.24 | 13-AUG-18:00 | 50.23 | 50.23 | 573.70 | 34191.19 | 30-AUG-08:06 |
September | 13.44 | 2444.81 | 18-SEP-08:05 | 50.42 | 50.42 | 3583.39 | 60239.51 | 20-SEP-04:00 |
October | 21.58 | 1666.16 | 13-OCT-04:50 | 51.35 | 51.35 | 19290.21 | 109757.12 | 19-OCT-15:13 |
November | 2.35 | 1012.32 | 08-NOV-21:20 | 51.15 | 51.15 | 37245.15 | 165117.91 | 29-NOV-16:13 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 42.19 | 60.00 | 55541.65 | 174129.22 | 28-DEC-16:13 |
Annual Sum or Average | 6.42 | 23445.06 | ||||||
Minimum of Months | 0.00 | 0.00 | 42.19 | 50.23 | 573.70 | 34191.19 | ||
Maximum of Months | 21.58 | 7371.90 | 52.06 | 60.00 | 55541.65 | 186171.62 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1370.53 | 43356.08 | 21-JAN-09:02 | 7.33 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1415.64 | 54034.83 | 20-FEB-09:02 | 7.48 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 2130.88 | 43531.68 | 20-MAR-18:03 | 7.33 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 18445.93 | 319064.52 | 30-APR-18:03 | 11.32 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 19959.94 | 221983.74 | 22-MAY-15:13 | 9.91 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 43926.05 | 440330.61 | 25-JUN-18:03 | 13.08 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 62183.11 | 374410.63 | 22-JUL-18:03 | 12.12 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 68884.18 | 349856.31 | 14-AUG-18:03 | 11.77 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 45678.66 | 248976.34 | 13-SEP-15:25 | 10.30 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8515.11 | 141792.65 | 07-OCT-15:13 | 8.75 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1761.34 | 48333.84 | 11-NOV-09:02 | 7.40 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 764.03 | 44543.43 | 31-DEC-09:01 | 7.34 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 23046.68 | 0.00 | ||||||
Minimum of Months | 764.03 | 43356.08 | 7.33 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 68884.18 | 440330.61 | 13.08 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 47.98 | 59.69 | 28108.32 | 57272.08 | 30-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 48.66 | 58.68 | 28289.99 | 57365.02 | 10-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 48.95 | 59.57 | 28129.74 | 57288.42 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.60 | 59.10 | 27610.33 | 56423.70 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 51.79 | 59.11 | 26917.38 | 55213.75 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 51.78 | 58.84 | 26226.31 | 53670.44 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.73 | 58.42 | 25687.72 | 52304.04 | 03-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.33 | 59.18 | 25519.67 | 51623.24 | 02-AUG-06:53 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.48 | 59.49 | 25693.25 | 52285.16 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.42 | 59.28 | 26195.41 | 53660.95 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.18 | 59.49 | 26894.59 | 55196.87 | 30-NOV-07:53 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 48.82 | 58.33 | 27591.56 | 56451.87 | 28-DEC-07:53 |
Annual Sum or Average | 0.00 | 26897.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.98 | 58.33 | 25519.67 | 51623.24 | ||
Maximum of Months | 0.00 | 0.00 | 52.48 | 59.69 | 28289.99 | 57365.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.894099E+11 | 0.00 | 0.175670E+09 | 0.427262E+11 | 0.00 | 0.00 |
February | 0.869090E+11 | 0.00 | 0.147843E+09 | 0.386535E+11 | 0.00 | 0.00 |
March | 0.915979E+11 | 0.00 | 0.104172E+09 | 0.429757E+11 | 0.00 | 0.00 |
April | 0.483729E+11 | 0.00 | 0.162524E+11 | 0.420400E+11 | 0.00 | 0.00 |
May | 0.357954E+11 | 0.00 | 0.168952E+11 | 0.435409E+11 | 0.00 | 0.00 |
June | 0.712985E+10 | 0.00 | 0.535301E+11 | 0.424793E+11 | 0.00 | 0.00 |
July | 0.338064E+10 | 0.00 | 0.916536E+11 | 0.440447E+11 | 0.00 | 0.00 |
August | 0.143108E+10 | 0.00 | 0.108037E+12 | 0.441141E+11 | 0.00 | 0.00 |
September | 0.839719E+10 | 0.00 | 0.567209E+11 | 0.423893E+11 | 0.00 | 0.00 |
October | 0.434313E+11 | 0.00 | 0.327669E+10 | 0.432248E+11 | 0.00 | 0.00 |
November | 0.788251E+11 | 0.00 | 0.162437E+09 | 0.415297E+11 | 0.00 | 0.00 |
December | 0.118294E+12 | 0.00 | 0.153516E+09 | 0.425848E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.612974E+12 | 0.00 | 0.347109E+12 | 0.510303E+12 | 0.00 | 0.00 |
Minimum of Months | 0.143108E+10 | 0.00 | 0.104172E+09 | 0.386535E+11 | 0.00 | 0.00 |
Maximum of Months | 0.118294E+12 | 0.00 | 0.108037E+12 | 0.441141E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.247181E+09 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
February | 82552832.48 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
March | 2022015.40 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
April | 4614.87 | 0.00 | 0.799630E+09 | 0.252903E+10 | 0.00 | 0.00 |
May | 4260.84 | 0.00 | 0.835620E+09 | 0.261333E+10 | 0.00 | 0.00 |
June | 10556.79 | 0.00 | 0.269652E+10 | 0.252903E+10 | 0.00 | 0.00 |
July | 21994.85 | 0.00 | 0.488968E+10 | 0.261333E+10 | 0.00 | 0.00 |
August | 20770.16 | 0.00 | 0.564050E+10 | 0.261333E+10 | 0.00 | 0.00 |
September | 10377.06 | 0.00 | 0.283360E+10 | 0.252903E+10 | 0.00 | 0.00 |
October | 1975.54 | 0.00 | 0.140689E+09 | 0.261333E+10 | 0.00 | 0.00 |
November | 6686203.90 | 0.00 | 0.00 | 0.252903E+10 | 0.00 | 0.00 |
December | 58332806.54 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.396849E+09 | 0.00 | 0.178362E+11 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 1975.54 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.247181E+09 | 0.00 | 0.564050E+10 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.427262E+11 | 0.175670E+09 | 0.894099E+11 | 0.103589E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.386535E+11 | 0.147843E+09 | 0.869090E+11 | 0.771356E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429757E+11 | 0.104172E+09 | 0.915979E+11 | 0.393938E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.420400E+11 | 0.162524E+11 | 0.483729E+11 | 0.118378E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.435409E+11 | 0.168952E+11 | 0.357954E+11 | 0.144569E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.424793E+11 | 0.535301E+11 | 0.712985E+10 | 0.292650E+09 | 0.156377E+09 | 0.00 | 0.00 | 0.00 |
July | 0.440447E+11 | 0.916536E+11 | 0.338064E+10 | 0.290479E+09 | 0.302271E+09 | 0.00 | 0.00 | 0.00 |
August | 0.441141E+11 | 0.108037E+12 | 0.143108E+10 | 0.746256E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.423893E+11 | 0.567209E+11 | 0.839719E+10 | 0.200481E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.432248E+11 | 0.327669E+10 | 0.434313E+11 | 0.285580E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.415297E+11 | 0.162437E+09 | 0.788251E+11 | 0.281393E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.425848E+11 | 0.153516E+09 | 0.118294E+12 | 0.716873E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510303E+12 | 0.347109E+12 | 0.612974E+12 | 0.337614E+12 | 0.458648E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.386535E+11 | 0.104172E+09 | 0.143108E+10 | 0.200481E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.441141E+11 | 0.108037E+12 | 0.118294E+12 | 0.103589E+12 | 0.302271E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.00 | 0.247181E+09 | 0.407791E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.00 | 82552832.48 | 0.373823E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.00 | 2022015.40 | 0.356495E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.799630E+09 | 4614.87 | 0.254787E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.835620E+09 | 4260.84 | 0.213468E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.269652E+10 | 10556.79 | 0.955077E+10 | 88983128.24 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.488968E+10 | 21994.85 | 0.583373E+10 | 0.142435E+09 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.564050E+10 | 20770.16 | 0.422411E+10 | 14671851.71 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.283360E+10 | 10377.06 | 0.102649E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.140689E+09 | 1975.54 | 0.231580E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.00 | 6686203.90 | 0.310696E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.00 | 58332806.54 | 0.415034E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.178362E+11 | 0.396849E+09 | 0.286241E+12 | 0.246090E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.00 | 1975.54 | 0.422411E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.564050E+10 | 0.247181E+09 | 0.415034E+11 | 0.142435E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.427262E+11 | 0.894099E+11 | 0.175670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.386535E+11 | 0.869090E+11 | 0.147843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429757E+11 | 0.915979E+11 | 0.104172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.420400E+11 | 0.483729E+11 | 0.162524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.435409E+11 | 0.357954E+11 | 0.168952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.424793E+11 | 0.712985E+10 | 0.535301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.440447E+11 | 0.338064E+10 | 0.916536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.441141E+11 | 0.143108E+10 | 0.108037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.423893E+11 | 0.839719E+10 | 0.567209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.432248E+11 | 0.434313E+11 | 0.327669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.415297E+11 | 0.788251E+11 | 0.162437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.425848E+11 | 0.118294E+12 | 0.153516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510303E+12 | 0.612974E+12 | 0.347109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.386535E+11 | 0.143108E+10 | 0.104172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.441141E+11 | 0.118294E+12 | 0.108037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.247181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 82552832.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 2022015.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 4614.87 | 0.799630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 4260.84 | 0.835620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 10556.79 | 0.269652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 21994.85 | 0.488968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 20770.16 | 0.564050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 10377.06 | 0.283360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 1975.54 | 0.140689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 6686203.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 58332806.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.396849E+09 | 0.178362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 1975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.247181E+09 | 0.564050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.492977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
February | 0.454231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
March | 0.502808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.460472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
May | 0.464822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
June | 0.400976E+11 | 0.00 | 0.00 | 0.00 | 52286293.85 | 0.00 | 0.00 | 0.00 | 0.81 |
July | 0.382652E+11 | 0.00 | 0.00 | 0.00 | 178213.63 | 0.00 | 0.00 | 0.00 | 0.86 |
August | 0.368242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
September | 0.401105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
October | 0.474793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
November | 0.480631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 0.517128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.540084E+12 | 0.00 | 0.00 | 0.00 | 52464507.48 | 0.00 | 0.00 | 0.00 | 0.71 |
Minimum of Months | 0.368242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.517128E+11 | 0.00 | 0.00 | 0.00 | 52286293.85 | 0.00 | 0.00 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.354750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102401E+10 | 0.00 | 0.00 | 1.03 |
February | 0.363868E+10 | 0.00 | 0.00 | 8915.83 | 0.00 | 0.559181E+09 | 14324880.00 | 0.00 | 1.03 |
March | 0.431718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345492E+09 | 0.00 | 0.00 | 1.04 |
April | 0.409254E+10 | 0.00 | 0.00 | 322309.97 | 0.00 | 0.00 | 0.183992E+09 | 0.00 | 1.17 |
May | 0.421323E+10 | 0.00 | 0.00 | 113898.76 | 0.00 | 0.00 | 97625285.13 | 0.00 | 1.18 |
June | 0.359609E+10 | 499501.54 | 0.00 | 247324.76 | 4349141.10 | 0.00 | 0.122236E+09 | 0.00 | 1.37 |
July | 0.318780E+10 | 20604.36 | 0.00 | 810489.92 | 0.00 | 0.00 | 0.365571E+09 | 0.00 | 1.47 |
August | 0.294880E+10 | 0.00 | 0.00 | 1176978.27 | 0.00 | 0.00 | 0.486739E+09 | 0.00 | 1.53 |
September | 0.321671E+10 | 0.00 | 0.00 | 1291309.03 | 0.00 | 0.00 | 0.551962E+09 | 0.00 | 1.45 |
October | 0.423161E+10 | 0.00 | 0.00 | 212215.67 | 0.00 | 1235896.39 | 0.177662E+09 | 0.00 | 1.15 |
November | 0.411546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341557E+09 | 0.00 | 0.00 | 1.04 |
December | 0.291584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187962E+10 | 0.00 | 0.00 | 1.03 |
Annual Sum or Average | 0.440214E+11 | 520105.89 | 0.00 | 4183442.21 | 4349141.10 | 0.415110E+10 | 0.200011E+10 | 0.00 | 1.21 |
Minimum of Months | 0.291584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.431718E+10 | 499501.54 | 0.00 | 1291309.03 | 4349141.10 | 0.187962E+10 | 0.551962E+09 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.529555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
February | 0.487933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
March | 0.540115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
April | 0.494638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
May | 0.499070E+10 | 0.00 | 0.00 | 27.88 | 0.00 | 0.00 | 2405825.43 | 0.00 | 1.18 |
June | 0.427644E+10 | 0.00 | 0.00 | 3804.75 | 5616578.70 | 0.00 | 30821796.90 | 0.00 | 1.37 |
July | 0.403179E+10 | 0.00 | 0.00 | 15693.43 | 19143.66 | 0.00 | 78626009.98 | 0.00 | 1.45 |
August | 0.391133E+10 | 0.00 | 0.00 | 6018.34 | 0.00 | 0.00 | 44304770.13 | 0.00 | 1.50 |
September | 0.426683E+10 | 0.00 | 0.00 | 4058.72 | 0.00 | 0.00 | 41827501.66 | 0.00 | 1.39 |
October | 0.510021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
November | 0.516292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
December | 0.555498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Annual Sum or Average | 0.578176E+11 | 0.00 | 0.00 | 29603.12 | 5635722.36 | 0.00 | 0.197986E+09 | 0.00 | 1.20 |
Minimum of Months | 0.391133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.555498E+10 | 0.00 | 0.00 | 15693.43 | 5616578.70 | 0.00 | 78626009.98 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68385942.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1897756.50 | 0.00 | 0.00 | 0.01 |
February | 63967803.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
March | 70808755.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
April | 60912090.55 | 0.00 | 0.00 | 83490.91 | 0.00 | 0.00 | 36536623.27 | 0.00 | 0.01 |
May | 57720260.23 | 0.00 | 0.00 | 148767.26 | 0.00 | 0.00 | 77693065.98 | 0.00 | 0.02 |
June | 29666430.77 | 1200472.50 | 0.00 | 704463.00 | 0.00 | 0.00 | 0.321956E+09 | 0.00 | 0.06 |
July | 14700389.57 | 4245.61 | 0.00 | 1314844.93 | 0.00 | 0.00 | 0.514182E+09 | 0.00 | 0.09 |
August | 6911916.06 | 0.00 | 0.00 | 1270252.46 | 0.00 | 0.00 | 0.539124E+09 | 0.00 | 0.09 |
September | 31442987.86 | 0.00 | 0.00 | 543634.27 | 0.00 | 0.00 | 0.281171E+09 | 0.00 | 0.05 |
October | 64510508.55 | 0.00 | 0.00 | 16331.28 | 0.00 | 0.00 | 12822464.76 | 0.00 | 0.01 |
November | 67685653.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
December | 72825436.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.609538E+09 | 1204718.10 | 0.00 | 4081784.10 | 0.00 | 1897756.50 | 0.178349E+10 | 0.00 | 0.03 |
Minimum of Months | 6911916.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 72825436.55 | 1200472.50 | 0.00 | 1314844.93 | 0.00 | 1897756.50 | 0.539124E+09 | 0.00 | 0.09 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692295E+09 | 0.00 | 0.00 | 0.50 |
February | 0.263796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261384E+09 | 0.00 | 0.00 | 0.50 |
March | 0.317802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31382129.32 | 0.00 | 0.00 | 0.51 |
April | 0.293918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.296694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.255942E+10 | 0.00 | 0.00 | 0.00 | 3337416.57 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.244245E+10 | 0.00 | 0.00 | 0.00 | 11375.32 | 0.00 | 0.00 | 0.00 | 0.71 |
August | 0.235047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.256024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.303058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
November | 0.296607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101784E+09 | 0.00 | 0.00 | 0.51 |
December | 0.249450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806312E+09 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.325802E+11 | 0.00 | 0.00 | 0.00 | 3348791.89 | 0.189316E+10 | 0.00 | 0.00 | 0.58 |
Minimum of Months | 0.235047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.317802E+10 | 0.00 | 0.00 | 0.00 | 3337416.57 | 0.806312E+09 | 0.00 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.101163E+09 | 0.00 | 0.00 | 0.657244E+11 | 0.00 | 12.68 |
February | 0.00 | 0.00 | 0.00 | 90023010.08 | 0.00 | 0.00 | 0.606309E+11 | 0.00 | 12.62 |
March | 0.00 | 0.00 | 0.00 | 95558365.29 | 0.00 | 0.00 | 0.673890E+11 | 0.00 | 12.87 |
April | 0.00 | 0.00 | 0.00 | 0.103427E+09 | 0.00 | 0.00 | 0.615480E+11 | 0.00 | 14.45 |
May | 0.00 | 0.00 | 0.00 | 0.108567E+09 | 0.00 | 0.00 | 0.622251E+11 | 0.00 | 14.85 |
June | 0.00 | 84030321.16 | 0.00 | 0.113298E+09 | 0.00 | 0.00 | 0.546175E+11 | 0.00 | 17.36 |
July | 0.00 | 186160.13 | 0.00 | 0.124564E+09 | 0.00 | 0.00 | 0.521548E+11 | 0.00 | 18.49 |
August | 0.00 | 0.00 | 0.00 | 0.124654E+09 | 0.00 | 0.00 | 0.508949E+11 | 0.00 | 19.28 |
September | 0.00 | 0.00 | 0.00 | 0.111819E+09 | 0.00 | 0.00 | 0.552689E+11 | 0.00 | 17.66 |
October | 0.00 | 0.00 | 0.00 | 97936285.11 | 0.00 | 0.00 | 0.636278E+11 | 0.00 | 14.27 |
November | 0.00 | 0.00 | 0.00 | 96236833.72 | 0.00 | 0.00 | 0.642627E+11 | 0.00 | 12.97 |
December | 0.00 | 0.00 | 0.00 | 0.103224E+09 | 0.00 | 0.00 | 0.683382E+11 | 0.00 | 12.56 |
Annual Sum or Average | 0.00 | 84216481.29 | 0.00 | 0.127047E+10 | 0.00 | 0.00 | 0.726682E+12 | 0.00 | 15.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 90023010.08 | 0.00 | 0.00 | 0.508949E+11 | 0.00 | 12.56 |
Maximum of Months | 0.00 | 84030321.16 | 0.00 | 0.124654E+09 | 0.00 | 0.00 | 0.683382E+11 | 0.00 | 19.28 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.387794E+11 | 0.00 | 0.00 | 5687.59 | 0.00 | 0.00 | 0.243206E+09 | 0.00 | 3.13 |
February | 0.357983E+11 | 0.00 | 0.00 | 9987.94 | 0.00 | 0.00 | 0.157212E+09 | 0.00 | 3.11 |
March | 0.397280E+11 | 0.00 | 0.00 | 655.27 | 0.00 | 0.00 | 72774655.24 | 0.00 | 3.16 |
April | 0.309071E+11 | 0.00 | 0.00 | 666985.18 | 0.00 | 0.00 | 0.554185E+10 | 0.00 | 3.51 |
May | 0.302092E+11 | 0.00 | 0.00 | 814318.25 | 0.00 | 0.00 | 0.658387E+10 | 0.00 | 3.59 |
June | 0.208537E+11 | 0.00 | 0.00 | 1878665.08 | 41388227.56 | 0.00 | 0.108845E+11 | 0.00 | 4.13 |
July | 0.186138E+11 | 87910.71 | 0.00 | 2875138.27 | 53157.74 | 0.00 | 0.116728E+11 | 0.00 | 4.40 |
August | 0.155260E+11 | 0.00 | 0.00 | 3569134.38 | 0.00 | 0.00 | 0.136193E+11 | 0.00 | 4.55 |
September | 0.183041E+11 | 0.00 | 0.00 | 3390084.65 | 0.00 | 0.00 | 0.134428E+11 | 0.00 | 4.22 |
October | 0.326237E+11 | 0.00 | 0.00 | 419330.87 | 0.00 | 0.00 | 0.495897E+10 | 0.00 | 3.49 |
November | 0.375873E+11 | 0.00 | 0.00 | 11831.58 | 0.00 | 0.00 | 0.457965E+09 | 0.00 | 3.17 |
December | 0.409343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
Annual Sum or Average | 0.359865E+12 | 87910.71 | 0.00 | 13641819.05 | 41441385.30 | 0.00 | 0.676352E+11 | 0.00 | 3.63 |
Minimum of Months | 0.155260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
Maximum of Months | 0.409343E+11 | 87910.71 | 0.00 | 3569134.38 | 41388227.56 | 0.00 | 0.136193E+11 | 0.00 | 4.55 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109375E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 |
February | 0.100778E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
March | 0.111556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 |
April | 0.947811E+11 | 0.00 | 0.00 | 1296024.35 | 0.00 | 0.00 | 0.738046E+10 | 0.00 | 1.42 |
May | 0.918584E+11 | 0.00 | 0.00 | 2074906.92 | 0.00 | 0.00 | 0.112676E+11 | 0.00 | 1.45 |
June | 0.662967E+11 | 0.00 | 0.00 | 5807568.83 | 0.116005E+09 | 0.00 | 0.226602E+11 | 0.00 | 1.68 |
July | 0.525485E+11 | 0.00 | 0.00 | 10560588.89 | 395394.56 | 0.00 | 0.323382E+11 | 0.00 | 1.79 |
August | 0.423522E+11 | 0.00 | 0.00 | 12242528.73 | 0.00 | 0.00 | 0.393358E+11 | 0.00 | 1.85 |
September | 0.596852E+11 | 0.00 | 0.00 | 8374417.86 | 0.00 | 0.00 | 0.292978E+11 | 0.00 | 1.71 |
October | 0.100109E+12 | 0.00 | 0.00 | 780317.59 | 0.00 | 0.00 | 0.523051E+10 | 0.00 | 1.42 |
November | 0.106274E+12 | 0.00 | 0.00 | 10179.21 | 0.00 | 0.00 | 0.361635E+09 | 0.00 | 1.29 |
December | 0.114733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
Annual Sum or Average | 0.105035E+13 | 0.00 | 0.00 | 41146532.38 | 0.116401E+09 | 0.00 | 0.147872E+12 | 0.00 | 1.47 |
Minimum of Months | 0.423522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
Maximum of Months | 0.114733E+12 | 0.00 | 0.00 | 12242528.73 | 0.116005E+09 | 0.00 | 0.393358E+11 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60007645.70 | 0.00 | 0.00 | 153566.41 | 0.00 | 0.128030E+10 | 14247125.90 | 0.00 | 0.34 |
February | 60647386.14 | 0.00 | 0.00 | 400492.22 | 0.00 | 0.110807E+10 | 48107104.86 | 0.00 | 0.34 |
March | 68472616.72 | 0.00 | 0.00 | 216366.07 | 0.00 | 0.122445E+10 | 63412157.91 | 0.00 | 0.34 |
April | 70589011.26 | 0.00 | 0.00 | 5004409.07 | 0.00 | 0.537473E+09 | 0.701075E+09 | 0.00 | 0.34 |
May | 75700878.21 | 0.00 | 0.00 | 5896620.12 | 0.00 | 0.412555E+09 | 0.827520E+09 | 0.00 | 0.34 |
June | 55912597.02 | 3410069.85 | 0.00 | 8476255.64 | 0.00 | 31268168.89 | 0.101430E+10 | 0.00 | 0.34 |
July | 41924957.37 | 1513518.95 | 0.00 | 10815616.67 | 0.00 | 47419805.59 | 0.938004E+09 | 0.00 | 0.34 |
August | 22907546.02 | 215015.57 | 0.00 | 10719202.46 | 23927.35 | 2538439.41 | 0.994357E+09 | 0.00 | 0.34 |
September | 41422421.67 | 7098.95 | 0.00 | 7619199.35 | 0.00 | 0.105810E+09 | 0.999996E+09 | 0.00 | 0.34 |
October | 77675947.48 | 0.00 | 0.00 | 1775837.11 | 0.00 | 0.929516E+09 | 0.348519E+09 | 0.00 | 0.34 |
November | 61770672.99 | 0.00 | 0.00 | 190772.46 | 0.00 | 0.122377E+10 | 24098266.01 | 0.00 | 0.34 |
December | 49337242.15 | 0.00 | 0.00 | 92710.74 | 0.00 | 0.128825E+10 | 4351271.95 | 0.00 | 0.34 |
Annual Sum or Average | 0.686369E+09 | 5145703.32 | 0.00 | 51361048.32 | 23927.35 | 0.819142E+10 | 0.597799E+10 | 0.00 | 0.34 |
Minimum of Months | 22907546.02 | 0.00 | 0.00 | 92710.74 | 0.00 | 2538439.41 | 4351271.95 | 0.00 | 0.34 |
Maximum of Months | 77675947.48 | 3410069.85 | 0.00 | 10815616.67 | 23927.35 | 0.128825E+10 | 0.101430E+10 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50083510.87 | 0.00 | 0.00 | 82535.41 | 0.00 | 0.129914E+10 | 5240820.76 | 0.00 | 0.34 |
February | 60640280.41 | 0.00 | 0.00 | 129733.53 | 0.00 | 0.113966E+10 | 16653642.00 | 0.00 | 0.34 |
March | 67166190.02 | 0.00 | 0.00 | 153109.00 | 0.00 | 0.125448E+10 | 34596350.27 | 0.00 | 0.34 |
April | 0.108452E+09 | 0.00 | 0.00 | 3182050.54 | 0.00 | 0.702601E+09 | 0.499752E+09 | 0.00 | 0.34 |
May | 0.123480E+09 | 0.00 | 0.00 | 4210857.16 | 0.00 | 0.490842E+09 | 0.702984E+09 | 0.00 | 0.34 |
June | 0.145305E+09 | 1452845.58 | 0.00 | 7128642.95 | 1956824.73 | 34444460.67 | 0.922950E+09 | 0.00 | 0.34 |
July | 0.220789E+09 | 1268192.53 | 572.12 | 7240737.74 | 243426.70 | 49546827.88 | 0.760467E+09 | 1150.27 | 0.34 |
August | 0.267406E+09 | 105297.96 | 0.00 | 5298859.05 | 133616.96 | 3406986.44 | 0.754290E+09 | 0.00 | 0.34 |
September | 0.158620E+09 | 0.00 | 0.00 | 3434658.94 | 7098.12 | 0.174602E+09 | 0.818055E+09 | 0.00 | 0.34 |
October | 89714419.09 | 0.00 | 0.00 | 757335.79 | 0.00 | 0.108776E+10 | 0.179091E+09 | 0.00 | 0.34 |
November | 61176152.28 | 0.00 | 0.00 | 112020.11 | 0.00 | 0.124069E+10 | 7702521.61 | 0.00 | 0.34 |
December | 40251962.65 | 0.00 | 0.00 | 72423.49 | 0.00 | 0.129733E+10 | 4224637.30 | 0.00 | 0.34 |
Annual Sum or Average | 0.139308E+10 | 2826336.07 | 572.12 | 31802963.71 | 2340966.51 | 0.877450E+10 | 0.470601E+10 | 1150.27 | 0.34 |
Minimum of Months | 40251962.65 | 0.00 | 0.00 | 72423.49 | 0.00 | 3406986.44 | 4224637.30 | 0.00 | 0.34 |
Maximum of Months | 0.267406E+09 | 1452845.58 | 572.12 | 7240737.74 | 1956824.73 | 0.129914E+10 | 0.922950E+09 | 1150.27 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.989956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 0.933533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.893142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
April | 0.565861E+09 | 0.00 | 0.00 | 1261938.18 | 0.00 | 0.00 | 0.718289E+09 | 0.00 | 0.02 |
May | 0.695222E+09 | 0.00 | 0.00 | 833988.87 | 0.00 | 0.00 | 0.647386E+09 | 0.00 | 0.02 |
June | 0.473581E+09 | 6761420.58 | 0.00 | 1064530.18 | 0.00 | 0.00 | 0.608301E+09 | 0.00 | 0.02 |
July | 0.254156E+09 | 217891.50 | 0.00 | 1917703.15 | 0.00 | 0.00 | 0.639918E+09 | 0.00 | 0.02 |
August | 0.117998E+09 | 0.00 | 0.00 | 2680550.02 | 0.00 | 0.00 | 0.638064E+09 | 0.00 | 0.02 |
September | 0.288196E+09 | 0.00 | 0.00 | 2801862.46 | 0.00 | 0.00 | 0.686807E+09 | 0.00 | 0.02 |
October | 0.829227E+09 | 0.00 | 0.00 | 968574.86 | 0.00 | 0.00 | 0.482707E+09 | 0.00 | 0.02 |
November | 0.106479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
December | 0.601464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.770713E+10 | 6979312.07 | 0.00 | 11529147.72 | 0.00 | 0.00 | 0.442147E+10 | 0.00 | 0.02 |
Minimum of Months | 0.117998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.106479E+10 | 6761420.58 | 0.00 | 2801862.46 | 0.00 | 0.00 | 0.718289E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.893404E+09 | 0.00 | 0.00 | 13463092.43 | 0.00 | 0.579412E+10 | 0.116726E+11 | 0.00 | 0.39 |
February | 0.822549E+09 | 0.00 | 0.00 | 12530346.53 | 0.00 | 0.409798E+10 | 0.115760E+11 | 0.00 | 0.39 |
March | 0.928681E+09 | 0.00 | 0.00 | 25110156.81 | 0.00 | 0.657806E+09 | 0.167871E+11 | 0.00 | 0.39 |
April | 0.147108E+10 | 0.00 | 0.00 | 60661137.57 | 0.00 | 97684000.93 | 0.161940E+11 | 0.00 | 0.39 |
May | 0.167494E+10 | 0.00 | 0.00 | 75213236.18 | 0.00 | 81280355.87 | 0.160942E+11 | 0.00 | 0.39 |
June | 0.197294E+10 | 18881059.76 | 0.00 | 0.103890E+09 | 27369072.52 | 19900375.22 | 0.129574E+11 | 0.00 | 0.39 |
July | 0.300334E+10 | 16641045.29 | 24576.49 | 0.104313E+09 | 3859137.27 | 7521499.86 | 0.109653E+11 | 2812.23 | 0.39 |
August | 0.362720E+10 | 1428303.70 | 0.00 | 80795035.13 | 1812433.91 | 5963923.40 | 0.102628E+11 | 0.00 | 0.39 |
September | 0.215159E+10 | 0.00 | 0.00 | 68214490.68 | 96281.72 | 56508396.48 | 0.133867E+11 | 0.00 | 0.39 |
October | 0.121177E+10 | 0.00 | 0.00 | 38187028.22 | 0.00 | 0.248171E+09 | 0.169132E+11 | 0.00 | 0.39 |
November | 0.879290E+09 | 0.00 | 0.00 | 20141617.36 | 0.00 | 0.204780E+10 | 0.148178E+11 | 0.00 | 0.39 |
December | 0.853777E+09 | 0.00 | 0.00 | 9460398.92 | 0.00 | 0.752016E+10 | 0.981832E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.194906E+11 | 36950408.75 | 24576.49 | 0.611980E+09 | 33136925.42 | 0.206349E+11 | 0.161445E+12 | 2812.23 | 0.39 |
Minimum of Months | 0.822549E+09 | 0.00 | 0.00 | 9460398.92 | 0.00 | 5963923.40 | 0.981832E+10 | 0.00 | 0.39 |
Maximum of Months | 0.362720E+10 | 18881059.76 | 24576.49 | 0.104313E+09 | 27369072.52 | 0.752016E+10 | 0.169132E+11 | 2812.23 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60007645.70 | 0.00 | 0.00 | 148783.56 | 0.00 | 0.125405E+10 | 40493069.34 | 0.00 | 0.34 |
February | 60647386.14 | 0.00 | 0.00 | 180946.43 | 0.00 | 0.110676E+10 | 49643455.42 | 0.00 | 0.34 |
March | 68472616.72 | 0.00 | 0.00 | 159505.62 | 0.00 | 0.122393E+10 | 63990892.42 | 0.00 | 0.34 |
April | 60686729.54 | 0.00 | 0.00 | 5406053.36 | 0.00 | 0.488005E+09 | 0.760043E+09 | 0.00 | 0.34 |
May | 62442783.49 | 0.00 | 0.00 | 5870298.31 | 0.00 | 0.389061E+09 | 0.864298E+09 | 0.00 | 0.34 |
June | 44327682.29 | 3352942.71 | 56920.41 | 8061081.63 | 0.00 | 55325223.28 | 0.100224E+10 | 206.73 | 0.34 |
July | 27145120.31 | 1513518.95 | 0.00 | 10141076.66 | 0.00 | 22526083.00 | 0.978352E+09 | 0.00 | 0.34 |
August | 8506890.89 | 215015.57 | 0.00 | 11089960.91 | 23927.35 | 2183340.63 | 0.100874E+10 | 0.00 | 0.34 |
September | 21800026.60 | 7098.95 | 0.00 | 8701593.50 | 0.00 | 67369282.17 | 0.105698E+10 | 0.00 | 0.34 |
October | 71560443.10 | 0.00 | 0.00 | 1738461.50 | 0.00 | 0.910325E+09 | 0.373863E+09 | 0.00 | 0.34 |
November | 61770672.99 | 0.00 | 0.00 | 182090.73 | 0.00 | 0.120820E+10 | 39681204.41 | 0.00 | 0.34 |
December | 48481148.28 | 0.00 | 0.00 | 106419.04 | 0.00 | 0.128124E+10 | 12205753.95 | 0.00 | 0.34 |
Annual Sum or Average | 0.595849E+09 | 5088576.18 | 56920.41 | 51786271.23 | 23927.35 | 0.800897E+10 | 0.625053E+10 | 206.73 | 0.34 |
Minimum of Months | 8506890.89 | 0.00 | 0.00 | 106419.04 | 0.00 | 2183340.63 | 12205753.95 | 0.00 | 0.34 |
Maximum of Months | 71560443.10 | 3352942.71 | 56920.41 | 11089960.91 | 23927.35 | 0.128124E+10 | 0.105698E+10 | 206.73 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50130256.28 | 0.00 | 0.00 | 88268.59 | 0.00 | 0.129614E+10 | 8190037.30 | 0.00 | 0.34 |
February | 59331155.30 | 0.00 | 0.00 | 111308.68 | 0.00 | 0.114278E+10 | 14865577.37 | 0.00 | 0.34 |
March | 67492411.00 | 0.00 | 0.00 | 128088.70 | 0.00 | 0.125641E+10 | 32359559.13 | 0.00 | 0.34 |
April | 0.106433E+09 | 0.00 | 0.00 | 3577448.14 | 0.00 | 0.593621E+09 | 0.610355E+09 | 0.00 | 0.34 |
May | 0.122052E+09 | 0.00 | 0.00 | 4315087.21 | 0.00 | 0.454742E+09 | 0.740408E+09 | 0.00 | 0.34 |
June | 0.141653E+09 | 1715608.09 | 8453.91 | 6647003.23 | 1685007.45 | 61962994.02 | 0.899564E+09 | 600.86 | 0.34 |
July | 0.217389E+09 | 1274176.68 | 0.00 | 6800911.21 | 239164.94 | 23805322.34 | 0.790048E+09 | 0.00 | 0.34 |
August | 0.258952E+09 | 214990.38 | 0.00 | 6508031.43 | 23924.55 | 2127582.03 | 0.762814E+09 | 0.00 | 0.34 |
September | 0.157430E+09 | 0.00 | 0.00 | 4825031.93 | 7098.12 | 0.140217E+09 | 0.852240E+09 | 0.00 | 0.34 |
October | 89334787.71 | 0.00 | 0.00 | 662098.09 | 0.00 | 0.104966E+10 | 0.217671E+09 | 0.00 | 0.34 |
November | 61176152.28 | 0.00 | 0.00 | 107837.62 | 0.00 | 0.123634E+10 | 12051234.53 | 0.00 | 0.34 |
December | 42172483.21 | 0.00 | 0.00 | 74018.59 | 0.00 | 0.129529E+10 | 4341136.78 | 0.00 | 0.34 |
Annual Sum or Average | 0.137355E+10 | 3204775.15 | 8453.91 | 33845133.41 | 1955195.06 | 0.855309E+10 | 0.494491E+10 | 600.86 | 0.34 |
Minimum of Months | 42172483.21 | 0.00 | 0.00 | 74018.59 | 0.00 | 2127582.03 | 4341136.78 | 0.00 | 0.34 |
Maximum of Months | 0.258952E+09 | 1715608.09 | 8453.91 | 6800911.21 | 1685007.45 | 0.129614E+10 | 0.899564E+09 | 600.86 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.260936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131547E+10 | 0.00 | 0.00 | 0.35 |
February | 0.248978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356969E+09 | 0.00 | 0.00 | 0.34 |
March | 0.278082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147447E+09 | 0.00 | 0.00 | 0.35 |
April | 0.256018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
May | 0.258437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 0.222939E+11 | 0.00 | 0.00 | 0.00 | 29070675.87 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.212751E+11 | 0.00 | 0.00 | 0.00 | 99085.06 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.204739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.223011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.263980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
November | 0.261853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537360E+09 | 0.00 | 0.00 | 0.35 |
December | 0.257197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303211E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.294892E+12 | 0.00 | 0.00 | 0.00 | 29169760.93 | 0.538935E+10 | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.204739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.278082E+11 | 0.00 | 0.00 | 0.00 | 29070675.87 | 0.303211E+10 | 0.00 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11568835.71 | 0.00 | 0.00 | 26791.70 | 0.00 | 0.325762E+09 | 1318526.71 | 0.00 | 0.34 |
February | 13541287.75 | 0.00 | 0.00 | 80309.25 | 0.00 | 0.282494E+09 | 8191501.28 | 0.00 | 0.34 |
March | 16330175.13 | 0.00 | 0.00 | 50413.49 | 0.00 | 0.314389E+09 | 8368302.41 | 0.00 | 0.34 |
April | 16443771.61 | 0.00 | 0.00 | 1362388.18 | 0.00 | 0.176601E+09 | 0.134128E+09 | 0.00 | 0.34 |
May | 17362597.92 | 0.00 | 0.00 | 1557336.28 | 0.00 | 0.147723E+09 | 0.163775E+09 | 0.00 | 0.34 |
June | 11805061.28 | 852517.46 | 0.00 | 2203457.77 | 0.00 | 33768042.41 | 0.229713E+09 | 0.00 | 0.34 |
July | 5943117.79 | 378379.74 | 0.00 | 2833574.18 | 0.00 | 30796039.85 | 0.219968E+09 | 0.00 | 0.34 |
August | 2507495.60 | 53753.89 | 0.00 | 2718822.52 | 5981.84 | 6092723.66 | 0.246312E+09 | 0.00 | 0.34 |
September | 9406354.71 | 1774.74 | 0.00 | 1827352.03 | 0.00 | 69644910.29 | 0.207833E+09 | 0.00 | 0.34 |
October | 19188361.44 | 0.00 | 0.00 | 414277.88 | 0.00 | 0.267455E+09 | 52313573.00 | 0.00 | 0.34 |
November | 15138586.73 | 0.00 | 0.00 | 40630.14 | 0.00 | 0.309127E+09 | 3152312.87 | 0.00 | 0.34 |
December | 8114115.39 | 0.00 | 0.00 | 6694.70 | 0.00 | 0.327135E+09 | 251630.34 | 0.00 | 0.34 |
Annual Sum or Average | 0.147350E+09 | 1286425.83 | 0.00 | 13122048.10 | 5981.84 | 0.229099E+10 | 0.127533E+10 | 0.00 | 0.34 |
Minimum of Months | 2507495.60 | 0.00 | 0.00 | 6694.70 | 0.00 | 6092723.66 | 251630.34 | 0.00 | 0.34 |
Maximum of Months | 19188361.44 | 852517.46 | 0.00 | 2833574.18 | 5981.84 | 0.327135E+09 | 0.246312E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8322250.11 | 0.00 | 0.00 | 18872.90 | 0.00 | 0.328925E+09 | 1370427.53 | 0.00 | 0.34 |
February | 11730822.97 | 0.00 | 0.00 | 34815.14 | 0.00 | 0.289778E+09 | 2727717.88 | 0.00 | 0.34 |
March | 16146114.40 | 0.00 | 0.00 | 41174.53 | 0.00 | 0.317232E+09 | 5678662.41 | 0.00 | 0.34 |
April | 26910515.75 | 0.00 | 0.00 | 901027.11 | 0.00 | 0.209777E+09 | 90908539.10 | 0.00 | 0.34 |
May | 30447877.79 | 0.00 | 0.00 | 1143379.27 | 0.00 | 0.158257E+09 | 0.140531E+09 | 0.00 | 0.34 |
June | 35819384.73 | 431165.71 | 0.00 | 1954366.33 | 421251.86 | 34882372.47 | 0.204801E+09 | 0.00 | 0.34 |
July | 53775151.56 | 318096.10 | 280.31 | 2016732.19 | 59808.70 | 28001320.25 | 0.175717E+09 | 150.29 | 0.34 |
August | 66080304.40 | 52750.26 | 0.00 | 1351940.86 | 6978.47 | 4632881.70 | 0.185535E+09 | 0.00 | 0.34 |
September | 39732390.66 | 0.00 | 0.00 | 763457.08 | 1774.53 | 95093637.27 | 0.153089E+09 | 0.00 | 0.34 |
October | 22333696.93 | 0.00 | 0.00 | 166828.55 | 0.00 | 0.293582E+09 | 23249224.54 | 0.00 | 0.34 |
November | 12493368.29 | 0.00 | 0.00 | 26160.67 | 0.00 | 0.313348E+09 | 1552544.12 | 0.00 | 0.34 |
December | 2401851.52 | 0.00 | 0.00 | 6713.08 | 0.00 | 0.332007E+09 | 1052833.54 | 0.00 | 0.34 |
Annual Sum or Average | 0.326194E+09 | 802012.07 | 280.31 | 8425467.73 | 489813.57 | 0.240552E+10 | 0.986213E+09 | 150.29 | 0.34 |
Minimum of Months | 2401851.52 | 0.00 | 0.00 | 6713.08 | 0.00 | 4632881.70 | 1052833.54 | 0.00 | 0.34 |
Maximum of Months | 66080304.40 | 431165.71 | 280.31 | 2016732.19 | 421251.86 | 0.332007E+09 | 0.204801E+09 | 150.29 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 83208977.97 | 0.00 | 0.00 | 1542194.64 | 0.00 | 0.165911E+10 | 0.431960E+09 | 0.00 | 0.39 |
February | 77574831.27 | 0.00 | 0.00 | 1964035.64 | 0.00 | 0.136085E+10 | 0.514632E+09 | 0.00 | 0.39 |
March | 0.109975E+09 | 0.00 | 0.00 | 828268.07 | 0.00 | 0.163438E+10 | 0.433604E+09 | 0.00 | 0.39 |
April | 46421286.00 | 0.00 | 0.00 | 10380688.68 | 0.00 | 0.426169E+09 | 0.162770E+10 | 0.00 | 0.39 |
May | 57399097.02 | 0.00 | 0.00 | 9647041.49 | 0.00 | 0.374345E+09 | 0.168138E+10 | 0.00 | 0.39 |
June | 47995606.52 | 5476989.35 | 0.00 | 12323686.32 | 0.00 | 40530879.14 | 0.168188E+10 | 0.00 | 0.39 |
July | 22614281.92 | 2430896.60 | 0.00 | 15324014.32 | 0.00 | 5867840.58 | 0.162361E+10 | 0.00 | 0.39 |
August | 4743699.18 | 345341.31 | 0.00 | 16862667.29 | 38430.25 | 3984076.55 | 0.162955E+10 | 0.00 | 0.39 |
September | 17335534.16 | 11401.78 | 0.00 | 15417284.10 | 0.00 | 22509608.16 | 0.179956E+10 | 0.00 | 0.39 |
October | 67630772.85 | 0.00 | 0.00 | 5618128.67 | 0.00 | 0.794288E+09 | 0.131275E+10 | 0.00 | 0.39 |
November | 79888104.32 | 0.00 | 0.00 | 1367397.27 | 0.00 | 0.150843E+10 | 0.514065E+09 | 0.00 | 0.39 |
December | 89647382.63 | 0.00 | 0.00 | 386154.40 | 0.00 | 0.196664E+10 | 98788972.33 | 0.00 | 0.39 |
Annual Sum or Average | 0.704435E+09 | 8264629.04 | 0.00 | 91661560.89 | 38430.25 | 0.979711E+10 | 0.133495E+11 | 0.00 | 0.39 |
Minimum of Months | 4743699.18 | 0.00 | 0.00 | 386154.40 | 0.00 | 3984076.55 | 98788972.33 | 0.00 | 0.39 |
Maximum of Months | 0.109975E+09 | 5476989.35 | 0.00 | 16862667.29 | 38430.25 | 0.196664E+10 | 0.179956E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.326733E+11 | 0.00 | 0.00 | 12464807.56 | 0.00 | 0.00 | 0.358471E+11 | 0.00 | 4.08 |
February | 0.308105E+11 | 0.00 | 0.00 | 11667558.93 | 0.00 | 0.00 | 0.323242E+11 | 0.00 | 4.06 |
March | 0.295311E+11 | 0.00 | 0.00 | 15236029.63 | 0.00 | 0.00 | 0.403531E+11 | 0.00 | 4.11 |
April | 0.204508E+11 | 0.00 | 0.00 | 19239824.56 | 0.00 | 0.00 | 0.435440E+11 | 0.00 | 4.58 |
May | 0.193663E+11 | 0.00 | 0.00 | 22469981.50 | 0.00 | 0.00 | 0.452300E+11 | 0.00 | 4.67 |
June | 0.138396E+11 | 43438785.94 | 0.00 | 27225694.34 | 29248671.29 | 0.00 | 0.418766E+11 | 0.00 | 5.39 |
July | 0.125945E+11 | 247749.35 | 0.00 | 29654719.64 | 0.00 | 0.00 | 0.405726E+11 | 0.00 | 5.74 |
August | 0.107384E+11 | 0.00 | 0.00 | 29279175.68 | 0.00 | 0.00 | 0.404246E+11 | 0.00 | 5.93 |
September | 0.154739E+11 | 0.00 | 0.00 | 22766504.04 | 0.00 | 0.00 | 0.402642E+11 | 0.00 | 5.49 |
October | 0.243915E+11 | 0.00 | 0.00 | 17403012.32 | 0.00 | 0.00 | 0.415959E+11 | 0.00 | 4.55 |
November | 0.288249E+11 | 0.00 | 0.00 | 13896141.42 | 0.00 | 0.00 | 0.379776E+11 | 0.00 | 4.13 |
December | 0.349803E+11 | 0.00 | 0.00 | 12209006.38 | 0.00 | 0.00 | 0.368977E+11 | 0.00 | 4.06 |
Annual Sum or Average | 0.273675E+12 | 43686535.29 | 0.00 | 0.233512E+09 | 29248671.29 | 0.00 | 0.476908E+12 | 0.00 | 4.74 |
Minimum of Months | 0.107384E+11 | 0.00 | 0.00 | 11667558.93 | 0.00 | 0.00 | 0.323242E+11 | 0.00 | 4.06 |
Maximum of Months | 0.349803E+11 | 43438785.94 | 0.00 | 29654719.64 | 29248671.29 | 0.00 | 0.452300E+11 | 0.00 | 5.93 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248799E+11 | 0.00 | 0.00 | 19377271.40 | 0.00 | 0.00 | 0.437078E+11 | 0.00 | 4.09 |
February | 0.218700E+11 | 0.00 | 0.00 | 18095605.64 | 0.00 | 0.00 | 0.413266E+11 | 0.00 | 4.06 |
March | 0.213377E+11 | 0.00 | 0.00 | 23294252.10 | 0.00 | 0.00 | 0.486142E+11 | 0.00 | 4.12 |
April | 0.152152E+11 | 0.00 | 0.00 | 27245137.06 | 0.00 | 0.00 | 0.488421E+11 | 0.00 | 4.59 |
May | 0.139218E+11 | 0.00 | 0.00 | 30750456.20 | 0.00 | 0.00 | 0.507560E+11 | 0.00 | 4.69 |
June | 0.935394E+10 | 48773807.91 | 0.00 | 35447803.72 | 23992342.77 | 0.00 | 0.464912E+11 | 0.00 | 5.41 |
July | 0.665628E+10 | 248017.57 | 0.00 | 38644037.47 | 0.00 | 0.00 | 0.466886E+11 | 0.00 | 5.76 |
August | 0.694176E+10 | 0.00 | 0.00 | 37399744.91 | 0.00 | 0.00 | 0.443715E+11 | 0.00 | 5.95 |
September | 0.113671E+11 | 0.00 | 0.00 | 30017341.70 | 0.00 | 0.00 | 0.444335E+11 | 0.00 | 5.50 |
October | 0.180979E+11 | 0.00 | 0.00 | 25312724.55 | 0.00 | 0.00 | 0.479530E+11 | 0.00 | 4.56 |
November | 0.218463E+11 | 0.00 | 0.00 | 21267104.60 | 0.00 | 0.00 | 0.450212E+11 | 0.00 | 4.14 |
December | 0.263720E+11 | 0.00 | 0.00 | 18911696.35 | 0.00 | 0.00 | 0.455772E+11 | 0.00 | 4.06 |
Annual Sum or Average | 0.197860E+12 | 49021825.48 | 0.00 | 0.325763E+09 | 23992342.77 | 0.00 | 0.553783E+12 | 0.00 | 4.75 |
Minimum of Months | 0.665628E+10 | 0.00 | 0.00 | 18095605.64 | 0.00 | 0.00 | 0.413266E+11 | 0.00 | 4.06 |
Maximum of Months | 0.263720E+11 | 48773807.91 | 0.00 | 38644037.47 | 23992342.77 | 0.00 | 0.507560E+11 | 0.00 | 5.95 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.103003E+09 | 0.00 | 0.00 | 0.645863E+11 | 0.00 | 12.54 |
February | 0.00 | 0.00 | 0.00 | 91939062.88 | 0.00 | 0.00 | 0.600908E+11 | 0.00 | 12.51 |
March | 0.00 | 0.00 | 0.00 | 97126585.17 | 0.00 | 0.00 | 0.660107E+11 | 0.00 | 12.84 |
April | 0.00 | 0.00 | 0.00 | 0.109269E+09 | 0.00 | 0.00 | 0.609475E+11 | 0.00 | 14.98 |
May | 0.00 | 0.00 | 0.00 | 0.114574E+09 | 0.00 | 0.00 | 0.620190E+11 | 0.00 | 15.40 |
June | 0.00 | 87358309.90 | 0.00 | 0.119635E+09 | 0.00 | 0.00 | 0.541771E+11 | 0.00 | 18.12 |
July | 0.00 | 297889.45 | 0.00 | 0.131295E+09 | 0.00 | 0.00 | 0.512434E+11 | 0.00 | 19.28 |
August | 0.00 | 0.00 | 0.00 | 0.131122E+09 | 0.00 | 0.00 | 0.488308E+11 | 0.00 | 19.94 |
September | 0.00 | 0.00 | 0.00 | 0.118474E+09 | 0.00 | 0.00 | 0.536796E+11 | 0.00 | 18.49 |
October | 0.00 | 0.00 | 0.00 | 0.101352E+09 | 0.00 | 0.00 | 0.625635E+11 | 0.00 | 14.65 |
November | 0.00 | 0.00 | 0.00 | 97975522.98 | 0.00 | 0.00 | 0.628772E+11 | 0.00 | 12.84 |
December | 0.00 | 0.00 | 0.00 | 0.104760E+09 | 0.00 | 0.00 | 0.671450E+11 | 0.00 | 12.37 |
Annual Sum or Average | 0.00 | 87656199.35 | 0.00 | 0.132053E+10 | 0.00 | 0.00 | 0.714171E+12 | 0.00 | 15.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 91939062.88 | 0.00 | 0.00 | 0.488308E+11 | 0.00 | 12.37 |
Maximum of Months | 0.00 | 87358309.90 | 0.00 | 0.131295E+09 | 0.00 | 0.00 | 0.671450E+11 | 0.00 | 19.94 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.643798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818111E+09 | 0.00 | 0.00 | 0.35 |
February | 0.650189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183895E+09 | 0.00 | 0.00 | 0.34 |
March | 0.737617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24618621.84 | 0.00 | 0.00 | 0.35 |
April | 0.665710E+10 | 0.00 | 0.00 | 498077.18 | 0.00 | 0.00 | 0.125375E+09 | 0.00 | 0.39 |
May | 0.656487E+10 | 0.00 | 0.00 | 575116.01 | 0.00 | 0.00 | 0.285619E+09 | 0.00 | 0.40 |
June | 0.509058E+10 | 9920342.88 | 0.00 | 2366262.08 | 0.00 | 0.00 | 0.852557E+09 | 0.00 | 0.47 |
July | 0.371381E+10 | 48505.56 | 0.00 | 5499065.69 | 0.00 | 0.00 | 0.206831E+10 | 0.00 | 0.52 |
August | 0.383364E+10 | 0.00 | 0.00 | 3914684.44 | 0.00 | 0.00 | 0.167179E+10 | 0.00 | 0.53 |
September | 0.566550E+10 | 0.00 | 0.00 | 563228.83 | 0.00 | 0.00 | 0.242733E+09 | 0.00 | 0.47 |
October | 0.698843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
November | 0.692199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152374E+09 | 0.00 | 0.00 | 0.35 |
December | 0.660339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100818E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.723554E+11 | 9968848.45 | 0.00 | 13416434.23 | 0.00 | 0.218718E+10 | 0.524639E+10 | 0.00 | 0.41 |
Minimum of Months | 0.371381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.737617E+10 | 9920342.88 | 0.00 | 5499065.69 | 0.00 | 0.100818E+10 | 0.206831E+10 | 0.00 | 0.53 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:55:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.719611E+11 | 0.169470E+11 | 0.227579E+12 | 0.607609E+12 | 0.327188E+11 |
February | 0.121049E+12 | 0.151943E+11 | 0.201646E+12 | 0.544711E+12 | 0.293955E+11 |
March | 0.159127E+12 | 0.153315E+11 | 0.203652E+12 | 0.558543E+12 | 0.330154E+11 |
April | 0.414610E+12 | 0.125875E+11 | 0.160290E+12 | 0.493089E+12 | 0.812843E+11 |
May | 0.539653E+12 | 0.121465E+11 | 0.157486E+12 | 0.484915E+12 | 0.876652E+11 |
June | 0.548981E+12 | 0.902810E+10 | 0.117587E+12 | 0.414014E+12 | 0.163186E+12 |
July | 0.550987E+12 | 0.817096E+10 | 0.103219E+12 | 0.394130E+12 | 0.233675E+12 |
August | 0.441080E+12 | 0.784142E+10 | 0.946013E+11 | 0.380664E+12 | 0.257967E+12 |
September | 0.319813E+12 | 0.906790E+10 | 0.113760E+12 | 0.416921E+12 | 0.169763E+12 |
October | 0.140445E+12 | 0.124273E+11 | 0.165917E+12 | 0.493832E+12 | 0.485746E+11 |
November | 0.504974E+11 | 0.142049E+11 | 0.192397E+12 | 0.521731E+12 | 0.303864E+11 |
December | 0.103498E+11 | 0.167412E+11 | 0.226947E+12 | 0.599921E+12 | 0.353172E+11 |
Annual Sum or Average | 0.336855E+13 | 0.149689E+12 | 0.196508E+13 | 0.591008E+13 | 0.120295E+13 |
Minimum of Months | 0.103498E+11 | 0.784142E+10 | 0.946013E+11 | 0.380664E+12 | 0.293955E+11 |