Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:54

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2023-10-16 08:54:51


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 11615.61 1023.83 1023.83
Net Site Energy 11500.96 1013.72 1013.72
Total Source Energy 20521.71 1808.83 1808.83
Net Source Energy 20158.62 1776.83 1776.83


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 2950.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 282.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 438.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 149.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 390.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 566.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 51.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 144.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 3068.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 43.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 3807.20 7808.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 2950.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 282.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 438.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 149.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 21.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 366.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 566.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 51.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 144.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 3068.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 20.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 2950.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 282.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 438.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 149.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1648.46 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 390.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 566.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 51.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 144.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 3068.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 43.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 51.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 87.42 530.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 196.35 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 335.58 688.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 51.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 87.42 530.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 196.35 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 335.58 688.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 120.765 3.17
Wind Power 0.000 0.00
Power Conversion -6.12 -0.2
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 114.650 3.01
     
Electricity Coming From Utility 3692.547 96.99
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 3692.547 96.99
     
Total On-Site and Utility Electric Sources 3807.197 100.00
Total Electricity End Uses 3807.197 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 0.96 0.03
Air to Air Heat Recovery for Heating 3381.96 99.97
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3382.91 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 3.33
Time Setpoint Not Met During Occupied Cooling 31.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 7928.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionElectricityGeneratedPropaneMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:54
RunPeriod RUNPERIOD 1
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [m] 133.00
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 5.8772 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 7.1580 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 7.1580 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 6.8781 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 3.5805 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 4.9406 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 7.3625 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 7.7500 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 4.2625 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.4132 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 7.3625 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 7.3625 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.5281 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 4.2625 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.3808 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.3808 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.8772 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 7.1580 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 7.1580 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 6.8781 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 3.5805 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 4.9406 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 7.3625 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 7.7500 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.4132 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.4132 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.4132 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.4132 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 4.2625 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.4132 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.4132 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.4132 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 7.3625 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 7.3625 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.5281 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 4.2625 18.58 0.0000  
Total 11345.29             5.3808 3.54 41.0437  
Conditioned Total 11345.29             5.3808 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.2523 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-JUN-19:10 12-JAN-19:10 - - - - - - - - - - 09-MAY-20:10
Heating 0.00 793652.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 91411.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 33662.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 86131.51 87619.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 19284.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27622.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 4151.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3837.47 241624.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1682.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 276049.69 1122896.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 793652.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 91411.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 33662.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56456.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 37635.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1213.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 17944.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 126.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 27622.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 4151.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3837.47 241624.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 771.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 670.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 3198.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 895.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1388.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 472.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5220.66 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1236.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1794.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 164.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 458.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.38 3326.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 138.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 12057.39 8464.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 281.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 78.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 122.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 41.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 109.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 158.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 14.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 40.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 293.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1062.77 746.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 281.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 78.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 122.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 41.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 460.16 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 109.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 158.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 14.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 40.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 293.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1062.77 746.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.07 0.729835 0.620000 1.28 1.00 0.500000 0.000522 0.000199 1.28 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.404776 0.126263 0.294000 0.119004 0.349765 0.500000 0.003018 0.000108 0.175143 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.204732 0.289080 0.672000 0.137580 0.770879 0.500000 0.001318 0.000043 0.137580 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.193417 0.647064 0.010000 0.001934 1.00 0.500000 0.000589 0.000062 0.100581 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.089582 0.806037 0.967000 0.086626 1.00 0.500000 0.000473 0.000047 0.086626 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.30 0.017995 0.010000 0.033046 0.300000 0.500000 0.021172 0.000083 0.135101 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.68 0.085672 0.604000 1.01 0.604000 0.500000 0.004447 0.000339 1.01 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.82 0.206611 0.589000 2.84 0.589000 0.500000 0.001844 0.000826 2.84 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.24 0.957824 0.575000 0.712522 1.00 0.500000 0.000398 0.000357 0.712522 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.04 0.123898 0.873000 1.78 0.873000 0.500000 0.003075 0.000401 1.78 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.14 0.117915 0.831000 1.78 0.831000 0.500000 0.003231 0.000404 1.78 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.22 0.063714 0.248000 0.551101 0.300000 0.500000 0.010755 0.000158 0.551101 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.682108 0.460395 0.276000 0.188262 1.00 0.500000 0.000828 0.000259 0.419652 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 9085.03 0.000199 270.48
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4932.07 0.000108 204.36
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1985.95 0.000043 66.86
MECH_FLR_1 VAV BOX REHEAT COIL 2832.11 0.000062 117.34
STORAGE_FLR_1 VAV BOX REHEAT COIL 2126.79 0.000047 82.49
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 3804.09 0.000083 157.62
CAFE_FLR_1 VAV BOX REHEAT COIL 15480.80 0.000339 526.10
LOBBY_FLR_1 VAV BOX REHEAT COIL 37777.42 0.000826 1254.88
ROOM_1_FLR_3 FAN COIL HEATING COIL 8566.47 0.000187 386.86
ROOM_2_FLR_3 FAN COIL HEATING COIL 8560.51 0.000187 386.59
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 48093.19 0.001052 2171.88
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 48011.57 0.001050 2168.19
ROOM_5_FLR_3 FAN COIL HEATING COIL 8555.67 0.000187 386.37
ROOM_6_FLR_3 FAN COIL HEATING COIL 8549.71 0.000187 386.10
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 16304.08 0.000357 615.23
ROOM_1_FLR_6 FAN COIL HEATING COIL 2655.62 0.000058 119.92
ROOM_2_FLR_6 FAN COIL HEATING COIL 2653.69 0.000058 119.83
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 12759.67 0.000279 576.17
BANQUET_FLR_6 VAV BOX REHEAT COIL 18311.33 0.000401 575.71
DINING_FLR_6 VAV BOX REHEAT COIL 18464.30 0.000404 581.38
KITCHEN_FLR_6 VAV BOX REHEAT COIL 7237.82 0.000158 239.70
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 11818.46 0.000259 489.73
VAV WITH REHEAT HEATING COIL 439349.95 0.009611 7011.35
FLR_3_DOAS HEATING COIL 42957.20 0.000940 685.53
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.947171 0.000187 0.000295
ROOM_2_FLR_3 FAN COIL 0.860127 0.000187 0.000268
ROOM_3_MULT19_FLR_3 FAN COIL 7.22 0.001052 0.002222
ROOM_4_MULT19_FLR_3 FAN COIL 4.99 0.001050 0.001640
ROOM_5_FLR_3 FAN COIL 0.893830 0.000187 0.000279
ROOM_6_FLR_3 FAN COIL 0.813327 0.000187 0.000254
ROOM_1_FLR_6 FAN COIL 0.245587 0.000058 0.000076
ROOM_2_FLR_6 FAN COIL 0.220882 0.000058 0.000069
ROOM_3_MULT9_FLR_6 FAN COIL 1.50 0.000279 0.000473
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 0.947171
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 0.860127
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 7.22
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 4.99
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.893830
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.813327
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.245587
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.220882
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008544 12.80 0.008500 0.000295 0.947171  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008548 12.80 0.008500 0.000268 0.860127  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008476 12.80 0.008476 0.002222 7.22  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008745 12.80 0.008500 0.001640 4.99  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008546 12.80 0.008500 0.000279 0.893830  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008550 12.80 0.008500 0.000254 0.813327  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008542 12.80 0.008500 0.000076 0.245587  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008546 12.80 0.008500 0.000069 0.220882  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008586 12.80 0.008500 0.000473 1.50  
VAV WITH REHEAT COOLING COIL 25.51 6.70 0.008494 10.95 0.008494 0.010568 20.98 369526.96
FLR_3_DOAS COOLING COIL 27.40 6.70 0.007007 11.91 0.007007 0.001096 2.05 38332.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 13.04 10.53 21.09 10.53 20.98 20.98 0.300000 0.501864 20.98
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 20.98  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 9.33
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 20.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.010568 0.000045
VAV WITH REHEAT_HEATC_CONTROLLER 0.009611  
FLR_3_DOAS_COOLC_CONTROLLER 0.001096 0.000434
FLR_3_DOAS_HEATC_CONTROLLER 0.000940  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.017240 2786.91  
HEATSYS1 PUMP 0.017082 5093.30 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.017082 2.05
COOLSYS1 0.017240 2.07
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 780873.52 780873.52 0.017082
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.017240 1929.47
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.017240 602802.62 603396.53 68.79
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 -3.10 -17.70 -19.30 -17.60 -15.40 -10.30 0.70 10.60 16.00 16.90 14.20 6.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 64.82 -147.85 -9.00 133.00 99737 1.1854


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA -1.53 36.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 5.877 5.380 0.000 0.000 0.000 0.000 11.257 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 7.158 10.760 0.000 0.000 0.000 0.000 17.918 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 7.158 10.760 0.000 0.000 0.000 0.000 17.918 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 6.878 5.380 0.000 0.000 0.000 0.000 12.258 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 3.581 2.690 0.000 0.000 0.000 0.000 6.271 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 4.941 61.680 535.850 0.000 0.000 0.000 602.471 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 7.363 5.380 0.000 0.000 0.000 0.000 12.743 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 7.750 8.070 0.000 0.000 0.000 0.000 15.820 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 4.263 0.000 0.000 0.000 0.000 0.000 4.263 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 7.363 67.820 0.000 0.000 0.000 0.000 75.183 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 7.363 67.820 0.000 0.000 0.000 0.000 75.183 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.528 512.243 2419.260 0.000 0.000 0.000 2943.031 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 4.263 0.000 0.000 0.000 0.000 0.000 4.263 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 11630.030 5.877 109.203 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11630.030
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 480.097 7.158 44.334 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 480.097
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 555.954 7.158 44.334 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 555.954
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1129.686 6.878 425.975 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1129.686
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 339.286 3.581 166.317 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 339.286
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 385.564 4.941 45.901 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 385.564
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1390.496 7.363 9.772 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1390.496
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 10138.453 7.750 24.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10138.453
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 108.229 4.413 72.152 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.229
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1659.841 4.263 79.202 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1659.841
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 2441.829 7.363 9.771 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2441.829
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 2441.829 7.363 9.771 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2441.829
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1190.908 11.528 53.553 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1190.908
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1756.685 4.263 79.201 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1756.685


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1625 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1625 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.3806 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 0.5010 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 0.4945 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 0.5010 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 0.4945 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1901 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1901 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 2.460
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.829
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.855
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.829
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.855
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 5.000
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 5.000
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.628
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 3.628
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.628
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.628
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
21 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
22 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
23 0 21.355302 0.61958938E-01 5.3791822  
24 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
25 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
26 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
27 0 21.355302 0.61958938E-01 5.3791822  
28 9 0.53036138E-14 -0.20687407E-15 -0.17503135E-09 -0.73745978E-16
29 8 0.25422872E-07 0.52195338E-13 0.41411666E-03 -0.28906677E-09
30 7 -0.13322280E-01 0.26229343E-08 -0.24640905E-01 0.15147920E-03
31 6 0.43471134 0.90107042E-06 0.49702005 -0.50938594E-02
32 5 -5.4770380 0.33281735E-04 -4.6323844 0.66736051E-01
33 4 34.269675 0.26958746E-03 22.186619 -0.43894326
34 3 -113.92059 0.58238925E-03 -57.099055 1.5541232
35 2 199.80052 0.32502050E-03 79.228999 -2.9431085
36 1 -172.15012 0.34444859E-04 -55.650987 2.7628612
37 0 57.057407 0.19438024E-06 15.495260  
38 9 0.33348593E-14 -0.26668477E-15 -0.16956947E-09 -0.43976091E-16
39 8 0.24657676E-07 0.68482217E-13 0.40643545E-03 -0.28036624E-09
40 7 -0.13094258E-01 0.34659102E-08 -0.24312948E-01 0.14888650E-03
41 6 0.42851718 0.11940890E-05 0.49177321 -0.50208446E-02
42 5 -5.4166105 0.44213948E-04 -4.5922145 0.65986760E-01
43 4 34.002513 0.35894970E-03 22.029896 -0.43539589
44 3 -113.35253 0.77701435E-03 -56.789351 1.5459154
45 2 199.23793 0.43442884E-03 78.944455 -2.9341738
46 1 -171.94247 0.46117265E-04 -55.567301 2.7592219
47 0 57.057407 0.26085733E-06 15.508311  
48 9 0.29092175E-14 -0.26257275E-15 -0.16986428E-09 -0.43070080E-16
49 8 0.24699499E-07 0.67600753E-13 0.40685731E-03 -0.28084178E-09
50 7 -0.13106789E-01 0.34199218E-08 -0.24330972E-01 0.14902898E-03
51 6 0.42885758 0.11780574E-05 0.49206171 -0.50248570E-02
52 5 -5.4199314 0.43614346E-04 -4.5944240 0.66027937E-01
53 4 34.017196 0.35403754E-03 22.038518 -0.43559085
54 3 -113.38375 0.76629489E-03 -56.806390 1.5463665
55 2 199.26885 0.42839238E-03 78.960107 -2.9346649
56 1 -171.95389 0.45472200E-04 -55.571899 2.7594220
57 0 57.057407 0.25718270E-06 15.507590  
58 9 0.33348593E-14 -0.26668477E-15 -0.16956947E-09 -0.43976091E-16
59 8 0.24657676E-07 0.68482217E-13 0.40643545E-03 -0.28036624E-09
60 7 -0.13094258E-01 0.34659102E-08 -0.24312948E-01 0.14888650E-03
61 6 0.42851718 0.11940890E-05 0.49177321 -0.50208446E-02
62 5 -5.4166105 0.44213948E-04 -4.5922145 0.65986760E-01
63 4 34.002513 0.35894970E-03 22.029896 -0.43539589
64 3 -113.35253 0.77701435E-03 -56.789351 1.5459154
65 2 199.23793 0.43442884E-03 78.944455 -2.9341738
66 1 -171.94247 0.46117265E-04 -55.567301 2.7592219
67 0 57.057407 0.26085733E-06 15.508311  
68 9 0.29092175E-14 -0.26257275E-15 -0.16986428E-09 -0.43070080E-16
69 8 0.24699499E-07 0.67600753E-13 0.40685731E-03 -0.28084178E-09
70 7 -0.13106789E-01 0.34199218E-08 -0.24330972E-01 0.14902898E-03
71 6 0.42885758 0.11780574E-05 0.49206171 -0.50248570E-02
72 5 -5.4199314 0.43614346E-04 -4.5944240 0.66027937E-01
73 4 34.017196 0.35403754E-03 22.038518 -0.43559085
74 3 -113.38375 0.76629489E-03 -56.806390 1.5463665
75 2 199.26885 0.42839238E-03 78.960107 -2.9346649
76 1 -171.95389 0.45472200E-04 -55.571899 2.7594220
77 0 57.057407 0.25718270E-06 15.507590  
78 7 -0.16359629E-14 -0.14530353E-16 -0.22331004E-13 0.54056000E-15
79 6 0.18262352E-10 0.22801053E-11 0.52333849E-09 -0.18642118E-10
80 5 -0.59540244E-07 0.11129510E-07 -0.21928235E-05 0.17164558E-06
81 4 0.60861605E-04 0.41961443E-05 0.17683552E-02 -0.28248824E-03
82 3 -0.87523238E-02 0.14809838E-03 -0.21562890 0.43346081E-01
83 2 0.12409989 0.64146884E-03 2.9009744 -0.61915653
84 1 -0.31397648 0.40472017E-03 -7.1381115 1.5697592
85 0 0.19977219 0.56546383E-05 4.4522022  
86 7 -0.22331004E-13 -0.14530353E-16 -0.16359629E-14 0.54056000E-15
87 6 0.52333849E-09 0.22801053E-11 0.18262352E-10 -0.18642118E-10
88 5 -0.21928235E-05 0.11129510E-07 -0.59540244E-07 0.17164558E-06
89 4 0.17683552E-02 0.41961443E-05 0.60861605E-04 -0.28248824E-03
90 3 -0.21562890 0.14809838E-03 -0.87523238E-02 0.43346081E-01
91 2 2.9009744 0.64146884E-03 0.12409989 -0.61915653
92 1 -7.1381115 0.40472017E-03 -0.31397648 1.5697592
93 0 4.4522022 0.56546383E-05 0.19977219  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
103 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
104 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
105 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
106 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
107 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
108 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
109 0 0.27512533 0.13606908E-04 60.838472  
110 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
111 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
112 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
113 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
114 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
115 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
116 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
117 0 0.27512533 0.13606908E-04 60.838472  
118 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
119 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
120 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
121 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
122 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
123 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
124 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
125 0 0.27512533 0.13606908E-04 60.838472  
126 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
127 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
128 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
129 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
130 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
131 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
132 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
133 0 0.27512533 0.13606908E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.24_SHGC_0.29 37 1 VerySmooth 1.362 1.362 1.000 0.291    
2 RESWINDOW_U_0.24_SHGC_0.29 38 1 VerySmooth 1.362 1.362 1.000 0.291    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   4.63425E-002 0.20180 0.60061 0.60061 0.50000 0.13060 0.16021 0.00000 0.84000 0.84000 8.30626E-002 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   4.63425E-002 0.20180 0.60061 0.60061 0.50000 0.13060 0.16021 0.00000 0.84000 0.84000 8.30626E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.680 0.5995
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.312 3.5001E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1794
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 0.1110
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.2125
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 0.1352
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.7586E-002
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.0450E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 5.0207E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.6868E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.2002
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1324
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.2370
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1606
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1078
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.0611E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 5.6231E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 2.2845E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 5.8241E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 3.3731E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.6416E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.6574E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.9690E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.5783E-002
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.9325E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.7679E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 5.8241E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 3.3731E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.6416E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.6574E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.9690E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.5783E-002
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.9325E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.7679E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 27993.02781 27993.02781 2.06604 2.06604 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 23.04800 7.00058E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 2426.87469 2426.87469 0.10567 0.85446 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 5484.01023 5484.01023 0.40478 0.40478 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40000 7.00714E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 4023.04222 4023.04222 0.17514 0.17514 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 2773.64769 2773.64769 0.20473 0.20473 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 26.89000 7.00637E-003 77.66889 12.54000 9.17335E-002 0.00000
6 RETAIL_2_FLR_1 Heating 1271.79745 1271.79745 5.53718E-002 9.17335E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 77.66889 12.54000 9.17335E-002 0.00000
7 MECH_FLR_1 Cooling 2620.94135 2620.94135 0.19342 0.19342 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 27.19600 7.00683E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 2310.18781 2310.18781 0.10058 0.10058 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1213.89267 1213.89267 8.95822E-002 8.95822E-002 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 27.29800 7.00699E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1677.15909 1677.15909 7.30201E-002 7.30201E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44775.56275 44775.56275 3.30458 3.30458 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 27.40000 7.00714E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 3103.28907 3103.28907 0.13510 0.13510 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 22740.08870 22740.08870 1.67981 1.67981 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40000 7.00714E-003 188.86188 142.30000 0.67638 0.00000
14 CAFE_FLR_1 Heating 10213.68707 10213.68707 0.44466 0.67638 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 188.86188 142.30000 0.67638 0.00000
15 LOBBY_FLR_1 Cooling 65346.28852 65346.28852 4.82471 4.82471 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 23024.84899 23024.84899 1.00246 1.89399 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 9524.08444 9524.08444 0.94717 0.94717 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 25.46200 7.00420E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 8566.47276 8566.47276 0.37513 0.37513 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 8648.83012 8648.83012 0.86013 0.86013 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 24.69700 7.00305E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 8560.51115 8560.51115 0.37487 0.37487 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 72611.10271 72611.10271 7.22094 7.22094 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 48093.18549 48093.18549 2.10615 2.10615 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 50148.99497 50148.99497 4.98755 4.98755 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 21.07600 6.99765E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 48011.56595 48011.56595 2.10258 2.10258 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 8987.71973 8987.71973 0.89383 0.89383 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 24.54400 7.00282E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 8555.67486 8555.67486 0.37465 0.37465 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 8178.24528 8178.24528 0.81333 0.81333 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 22.65700 7.00000E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 8549.71381 8549.71381 0.37439 0.37439 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 16790.13882 16790.13882 1.23917 1.23917 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40000 7.00714E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 12604.03077 12604.03077 0.54877 0.54877 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2469.44652 2469.44652 0.24559 0.24559 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 25.46200 7.00420E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 2655.62213 2655.62213 0.11629 0.11629 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2221.03707 2221.03707 0.22088 0.22088 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.95200 7.00344E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 2653.68717 2653.68717 0.11621 0.11621 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 15084.30282 15084.30282 1.50018 1.50018 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 12759.66517 12759.66517 0.55876 0.55876 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 27603.42725 27603.42725 2.03976 2.03976 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40000 7.00714E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 9063.02799 9063.02799 0.39459 1.18780 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 29004.54341 29004.54341 2.14327 2.14327 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40000 7.00714E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 9214.14788 9214.14788 0.40117 1.18780 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30032.05152 30032.05152 2.22218 2.22218 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 26.48200 7.00575E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 4379.94070 4379.94070 0.19067 0.36735 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -41.90000 6.45023E-005 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 9242.34575 9242.34575 0.68211 0.68211 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40000 7.00714E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 9638.58935 9638.58935 0.41965 0.41965 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 317534.28 20.98009 20.98009 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 538314.69 7.71177 7.71177 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00
3 FLR_3_DOAS Cooling Sensible 35674.24 16.40050 2.05125 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 143185.63 6.49903 2.05125 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.06604
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.72983
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.62000
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.28095
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.22036E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.98735E-004
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.28095
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9085.03224
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.98735E-004
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 270.47616
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.40478
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12626
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29400
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11900
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34976
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.01750E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07889E-004
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17514
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4932.07365
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07889E-004
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 204.36493
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.20473
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28908
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.67200
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13758
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.77088
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.31798E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.34428E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13758
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1985.95310
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.34428E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 66.86204
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.19342
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.64706
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.93417E-003
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.88813E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.19525E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10058
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2832.10950
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.19525E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 117.34492
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.95822E-002
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.80604
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.96700
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.66260E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.72683E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.65237E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.66260E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2126.79460
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.65237E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 82.49021
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.30458
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.79951E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.30458E-002
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.11725E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.32146E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13510
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3804.08939
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.32146E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 157.61734
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.67981
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.56721E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.60400
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.01460
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60400
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.44719E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.38643E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.01460
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15480.80180
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.38643E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 526.10170
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.82471
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20661
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58900
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.84176
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58900
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.84405E-003
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.26382E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.84176
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 37777.41580
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.26382E-004
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1254.87888
113 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
114 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.94717
115 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.94717
116 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.87392E-004
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.94999E-004
118 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69231
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54359E-003
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.94999E-004
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.94717
125 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8566.47276
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.87392E-004
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 386.85885
128 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
129 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.86013
130 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.86013
131 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.87261E-004
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.68199E-004
133 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69230
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54778E-003
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.68199E-004
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.86013
140 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8560.51115
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.87261E-004
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 386.58973
143 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
144 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 7.22094
145 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 7.22094
146 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.05204E-003
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.22185E-003
148 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69266
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47633E-003
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47633E-003
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.22185E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 7.22094
155 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 48093.18549
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.05204E-003
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 2171.87856
158 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
159 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 4.98755
160 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 4.98755
161 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.05025E-003
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.63997E-003
163 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69173
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.74532E-003
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.63997E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 4.98755
170 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 48011.56595
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.05025E-003
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 2168.19441
173 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
174 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.89383
175 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.89383
176 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.87156E-004
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.78559E-004
178 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69231
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54584E-003
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.78559E-004
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.89383
185 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8555.67486
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.87156E-004
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 386.37143
188 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
189 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.81333
190 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.81333
191 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.87025E-004
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.53756E-004
193 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69230
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54993E-003
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.53756E-004
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.81333
200 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8549.71381
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.87025E-004
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 386.10234
203 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23917
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.95782
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.57500
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.71252
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.97777E-004
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.56652E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71252
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
214 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16304.08033
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.56652E-004
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 615.23353
217 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
218 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.24559
219 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.24559
220 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.80918E-005
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.64564E-005
222 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69231
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54207E-003
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.64564E-005
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.24559
229 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2655.62213
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.80918E-005
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 119.91689
232 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
233 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.22088
234 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.22088
235 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.80495E-005
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 6.88489E-005
237 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69230
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54646E-003
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.88489E-005
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.22088
244 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2653.68717
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.80495E-005
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 119.82954
247 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
248 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.50018
249 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.50018
250 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.79118E-004
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.72718E-004
252 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69203
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58613E-003
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.72718E-004
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.50018
259 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 12759.66517
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.79118E-004
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 576.17064
262 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.03976
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12390
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.87300
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78071
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.87300
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.07511E-003
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.00561E-004
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78071
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
273 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18311.33109
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.00561E-004
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 575.70953
276 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.14327
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11791
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.83100
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78105
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.83100
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.23114E-003
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.03907E-004
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78105
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
287 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18464.30419
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.03907E-004
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 581.38259
290 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.22218
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.37141E-002
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24800
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.55110
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.07555E-002
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58328E-004
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.55110
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
301 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7237.82383
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58328E-004
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 239.69630
304 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.68211
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.46039
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27600
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18826
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.27551E-004
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.58529E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41965
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
315 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11818.46044
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.58529E-004
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 489.73094
318 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 13.03933
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 10.52915
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.09413
321 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 10.52915
322 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 20.98009
323 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 20.98009
324 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
325 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.50186
326 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
333 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
334 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 20.98009
335 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
336 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 20.98009
337 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 9.32920
338 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.50571
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94807
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49425E-003
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49425E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 369526.95725
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.05684E-002
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 20.98009
346 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 439349.94847
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.61079E-003
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 7011.35191
349 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 20.98009
350 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.05684E-002
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.50579E-005
352 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.61079E-003
353 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
355 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
356 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 27.40000
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91318
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00714E-003
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00714E-003
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 38332.29647
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.09630E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
364 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 42957.20027
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.39690E-004
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 685.53109
367 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
368 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.09630E-003
369 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 4.34362E-004
370 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.39690E-004
371 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 1.72401E-002
372 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 2786.90893
373 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.70816E-002
374 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.04980
375 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.70816E-002
376 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 5093.30375
377 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
378 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 780873.51718
379 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 780873.52000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.70816E-002
381 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 1.72401E-002
382 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.06881
383 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 1.72401E-002
384 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 1929.47105
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 1.72401E-002
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 602802.61643
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 603396.53000
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 68.78720
389 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
390 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
391 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
392 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
393 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 13793.46
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 7485.99
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 3018.73
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 4298.63
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 3229.16
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 5773.92
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 23529.64
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 57382.05
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 14489.97
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 14479.89
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 81350.09
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 81212.06
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 14471.71
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 14461.63
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 24759.52
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 4491.71
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 4488.43
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 21581.72
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 27792.28
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 28024.23
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 10983.21
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 17938.28
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 284263.13
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 27793.67


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 15374.99 13301.12 2073.87 0.87 3091.10 31.35
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 13973.08 12082.50 1890.58 0.86 2805.87 28.46
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 116471.83 101254.01 15217.82 0.87 24036.00 243.79
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 84012.22 71106.59 12905.64 0.85 16062.99 162.92
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 14515.29 12554.13 1961.16 0.86 2916.36 29.58
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 13218.16 11426.90 1791.26 0.86 2652.64 26.90
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 3984.75 3447.92 536.83 0.87 800.70 8.12
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 3587.42 3102.51 484.91 0.86 720.65 7.31
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 24546.33 21133.28 3413.05 0.86 4876.45 49.46
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 474587.44 348270.87 126316.57 0.73 81921.79 830.90
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 51661.93 36376.38 15285.55 0.70 12474.20 126.52


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.270 0.259   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.270 0.259   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.270 0.259   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.270 0.259   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.381 0.360   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.501 0.466   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.501 0.466   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.501 0.466   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.501 0.466   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.501 0.466   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.190 0.184   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.494 0.460   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.494 0.460   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.494 0.460   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.494 0.460   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.494 0.460   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.494 0.460   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.494 0.460   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.494 0.460   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.494 0.460   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.494 0.460   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.494 0.460   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.494 0.460   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.494 0.460   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.24_SHGC_0.29 N/A 1.362 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.190 0.182   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.5009055800E-002 2.2051191286E-002 Pass Pass 3.3027997534E-003 5.6955865621E-003 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.4419433456E-003 1.0997192196E-003 Pass Pass 1.4662579862E-002 3.0390996893E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 9.9278279445E-004 7.9445616373E-004 Pass Pass 0.2637323529 1.3637620824 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 6.5501789921E-004 2.8195074910E-003 Pass Pass 9.3084420438E-002 0.3782366864 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 8.3705555525E-004 5.9338579881E-004 Pass Pass 1.3114589979E-002 1.9760123526E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 1.0343580725E-004 1.8947926065E-004 Pass Pass 2.1961134749E-002 6.3662627033E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 2.5230140344E-003 1.7758666061E-003 Pass Pass 0.3355655483 1.9880792124 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 1.0385165560E-002 2.4485311623E-002 Pass Pass 3.5214817021E-002 0.1183284625 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.2640738916E-002 0.3578078005 Pass Pass 9.0025156345E-002 0.2652387410 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 9.2644452321E-002 0.3563441760 Pass Pass 8.8779814278E-002 0.2639564647 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.4991568489E-005 6.9962936357E-005 Pass Pass 3.4314062909E-002 8.9430847205E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 5.9353747971E-002 0.2075337299 Pass Pass 0.1228175404 0.3945403364 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2638463848E-002 0.3568549736 Pass Pass 9.0628161995E-002 0.2661684423 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 9.2634171404E-002 0.3551106130 Pass Pass 8.9196156918E-002 0.2645178729 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 4.6507418309E-004 3.1174282695E-004 Pass Pass 5.1177404957E-002 0.1594140013 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2652291477E-002 0.3737110863 Pass Pass 8.7388162909E-002 0.3103493507 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2641478537E-002 0.3721442307 Pass Pass 8.6649000412E-002 0.3112248577 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2642869094E-002 0.3549391369 Pass Pass 9.7861748132E-002 0.3266008691 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 2.9692378351E-002 8.2614570749E-002 Pass Pass 1.4525290529E-002 4.6821817316E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 3.4620060882E-002 8.9741914163E-002 Pass Pass 1.2517437497E-002 3.6776781433E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 1.1540620218E-003 2.1116799479E-003 Pass Pass 2.5433220462E-002 4.9456308779E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 5.8909911753E-004 4.1589900022E-004 Pass Pass 1.2435235924E-002 2.2473215871E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2378.40 266.52 3307.89 9066.64 1634.63 16654.07



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -41.90 0.00 -41.90 Wetbulb [C] 0.30 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 27.40 10.20 16.10 Wetbulb [C] 3.10 180.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.261 0.270 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.261 0.270 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.261 0.270 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.261 0.270 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.360 0.381 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.360 0.381 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.159 0.163 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.360 0.381 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.360 0.381 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.360 0.381 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.360 0.381 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.360 0.381 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.360 0.381 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.360 0.381 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.159 0.163 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.360 0.381 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.360 0.381 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.360 0.381 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.360 0.381 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.159 0.163 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.466 0.501 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.466 0.501 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.466 0.501 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.466 0.501 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.466 0.501 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.466 0.501 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.466 0.501 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.466 0.501 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.466 0.501 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.466 0.501 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.466 0.501 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.466 0.501 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.466 0.501 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.466 0.501 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.460 0.494 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.460 0.494 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.460 0.494 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.460 0.494 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.460 0.494 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.460 0.494 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.460 0.494 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.460 0.494 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.460 0.494 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.460 0.494 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.460 0.494 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.460 0.494 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.460 0.494 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.159 0.163 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.159 0.163 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.181 0.190 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.181 0.190 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.181 0.190 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.181 0.190 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.181 0.190 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.181 0.190 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.181 0.190 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.181 0.190 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.181 0.190 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.181 0.190 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.181 0.190 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.183 0.190 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.179 0.190 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.183 0.190 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.179 0.190 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.179 0.190 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.179 0.190 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.183 0.190 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.183 0.190 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.183 0.190 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.179 0.190 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   23.26 0.00 0.00 23.26 23.26 1.362 0.291 0.500             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   65.50 0.00 0.00 65.50 65.50 1.362 0.291 0.500             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   85.08 0.00 0.00 85.08 85.08 1.362 0.291 0.500             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   4.60 0.00 0.00 4.60 18.40 1.362 0.291 0.500             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.24_SHGC_0.29   8.58 0.00 0.00 8.58 34.34 1.362 0.291 0.500             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   4.60 0.00 0.00 4.60 18.40 1.362 0.291 0.500             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.24_SHGC_0.29   8.58 0.00 0.00 8.58 34.34 1.362 0.291 0.500             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   3.68 0.00 0.00 3.68 279.56 1.362 0.291 0.500             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   3.68 0.00 0.00 3.68 279.65 1.362 0.291 0.500             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.24_SHGC_0.29   8.58 0.00 0.00 8.58 34.34 1.362 0.291 0.500             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   4.60 0.00 0.00 4.60 18.40 1.362 0.291 0.500             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   4.60 0.00 0.00 4.60 18.40 1.362 0.291 0.500             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.24_SHGC_0.29   8.58 0.00 0.00 8.58 34.34 1.362 0.291 0.500             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   5.82 0.00 0.00 5.82 23.30 1.362 0.291 0.500             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   2.15 0.00 0.00 2.15 8.59 1.362 0.291 0.500             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   2.15 0.00 0.00 2.15 8.58 1.362 0.291 0.500             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   5.82 0.00 0.00 5.82 23.30 1.362 0.291 0.500             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   4.60 0.00 0.00 4.60 4.60 1.362 0.291 0.500             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.24_SHGC_0.29   8.58 0.00 0.00 8.58 8.58 1.362 0.291 0.500             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   4.60 0.00 0.00 4.60 4.60 1.362 0.291 0.500             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.24_SHGC_0.29   8.58 0.00 0.00 8.58 8.58 1.362 0.291 0.500             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.24_SHGC_0.29   6.74 0.00 0.00 6.74 60.70 1.362 0.291 0.500             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   32.19 0.00 0.00 32.19 32.19 1.362 0.291 0.500             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   32.19 0.00 0.00 32.19 32.19 1.362 0.291 0.500             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   4.60 0.00 0.00 4.60 4.60 1.362 0.291 0.500             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   17.17 0.00 0.00 17.17 17.17 1.362 0.291 0.500             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   4.60 0.00 0.00 4.60 4.60 1.362 0.291 0.500             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   5.82 0.00 0.00 5.82 5.82 1.362 0.291 0.500             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   5.21 0.00 0.00 5.21 5.21 1.362 0.291 0.500             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.24_SHGC_0.29   17.17 0.00 0.00 17.17 17.17 1.362 0.291 0.500             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 1.362 0.291 0.500                      
North Total or Average             432.95 1.362 0.291 0.500                      
Non-North Total or Average             780.84 1.362 0.291 0.500                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.8772 1978.83 11630.03 LightsWired LTG_SCH_BASEMENT 40.17 168.00 40.12 0.0000 Y 87.60
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 7.1580 67.07 480.10 LightsWired LTG_SCH_RETAIL 44.04 168.00 43.99 0.0000 Y 3.96
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 7.1580 77.67 555.95 LightsWired LTG_SCH_RETAIL 44.04 168.00 43.99 0.0000 Y 4.59
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 6.8781 164.24 1129.69 LightsWired LTG_SCH_MECHANIC 38.78 168.00 38.73 0.0000 Y 8.21
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 3.5805 94.76 339.29 LightsWired LTG_SCH_STORAGE 29.59 168.00 29.56 0.0000 Y 1.88
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 4.9406 78.04 385.56 LightsWired LTG_SCH_LAUNDRY 48.47 168.00 48.41 0.0000 Y 3.50
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 7.3625 188.86 1390.50 LightsWired LTG_SCH_DINING 36.01 168.00 23.82 0.0000 Y 6.22
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 7.7500 1308.19 10138.45 LightsWired LTG_SCH_LOBBY 41.54 168.00 39.13 0.0000 Y 74.46
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.4132 1863.81 8225.38 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.78
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.4132 1864.32 8227.62 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 58.79
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 4.92
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 4.2625 1557.62 6639.36 LightsWired LTG_SCH_CORRIDOR 41.54 168.00 41.50 0.0000 Y 51.72
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.4132 39.02 172.21 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.4132 39.02 172.19 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 1.23
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.4132 220.77 974.32 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 6.96
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 7.3625 331.66 2441.83 LightsWired LTG_SCH_DINING 36.01 168.00 29.90 0.0000 Y 13.70
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 7.3625 331.66 2441.83 LightsWired LTG_SCH_DINING 36.01 168.00 29.90 0.0000 Y 13.70
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.5281 103.30 1190.91 LightsWired LTG_SCH_KITCHEN 38.78 168.00 38.73 0.0000 Y 8.66
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 4.2625 412.12 1756.68 LightsWired LTG_SCH_CORRIDOR 41.54 168.00 41.50 0.0000 Y 13.68
Interior Lighting Total       5.3808 11345.29 61047.14               262.81


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10138.45 709.69
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10138.45 709.69
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1390.50 542.29
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1390.50 542.29
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2441.83 488.37
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2441.83 488.37
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2441.83 488.37
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2441.83 488.37


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 9571.94 AstronomicalClock -   83.06 83.06 149.24
Exterior Lighting Total 9571.94           149.24



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 780873.52 0.94        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 603396.53 2.96 603502.59 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10314.89 15374.99 13301.12 2073.87 0.87 - 3091.10 31.35
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9377.80 13973.08 12082.50 1890.58 0.86 - 2805.87 28.46
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 77688.88 116471.83 101254.01 15217.82 0.87 - 24036.00 243.79
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 57342.90 84012.22 71106.59 12905.64 0.85 - 16062.99 162.92
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9740.04 14515.29 12554.13 1961.16 0.86 - 2916.36 29.58
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8872.81 13218.16 11426.90 1791.26 0.86 - 2652.64 26.90
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2673.36 3984.75 3447.92 536.83 0.87 - 800.70 8.12
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2407.36 3587.42 3102.51 484.91 0.86 - 720.65 7.31
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 16528.98 24546.33 21133.28 3413.05 0.86 - 4876.45 49.46
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 369526.96 474587.44 348270.87 126316.57 0.73 - 81921.79 830.90
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 38332.30 51661.93 36376.38 15285.55 0.70 - 12474.20 126.52
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 9085.03 13793.46 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4932.07 7485.99 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1985.95 3018.73 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2832.11 4298.63 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2126.79 3229.16 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3804.09 5773.92 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 15480.80 23529.64 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 37777.42 57382.05 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 8566.47 14489.97 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 8560.51 14479.89 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 48093.19 81350.09 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 48011.57 81212.06 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 8555.67 14471.71 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 8549.71 14461.63 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 16304.08 24759.52 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2655.62 4491.71 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2653.69 4488.43 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 12759.67 21581.72 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 18311.33 27792.28 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 18464.30 28024.23 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7237.82 10983.21 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11818.46 17938.28 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 439349.95 284263.13 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 42957.20 27793.67 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.24 0.00 0.00 1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.95 666.46 703.64 1.00 1.21 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.86 605.22 703.64 1.00 1.24 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 7.22 5080.91 703.64 1.00 0.95 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 4.99 3509.42 703.64 1.00 0.97 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.89 628.93 703.64 1.00 1.23 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.81 572.29 703.64 1.00 1.25 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.25 172.80 703.64 1.00 1.87 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.22 155.42 703.64 1.00 1.96 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.50 1055.58 703.64 1.00 1.11 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 20.98 47008.81 2240.64 1.00 1.11 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.017240 2786.91 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.017082 5093.30 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.017240 1929.47 111917.77 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.95 0.68 0.60
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.95 0.31 0.04



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 27993.03 27993.03 14.15 2.066 2.066 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 24.00 24.00 0.00936 23.05 0.00700 0.854 0.00
RETAIL_1_FLR_1 5484.01 5484.01 81.76 0.405 0.405 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00890 27.40 0.00701 0.079 0.00
RETAIL_2_FLR_1 2773.65 2773.65 35.71 0.205 0.205 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 24.00 24.00 0.00948 26.89 0.00701 0.092 0.00
MECH_FLR_1 2620.94 2620.94 15.96 0.193 0.193 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00866 27.20 0.00701 0.000 0.00
STORAGE_FLR_1 1213.89 1213.89 12.81 0.090 0.090 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00878 27.30 0.00701 0.058 0.00
LAUNDRY_FLR_1 44775.56 44775.56 573.76 3.305 3.305 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00854 27.40 0.00701 0.000 0.00
CAFE_FLR_1 22740.09 22740.09 120.41 1.680 1.680 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 23.99 0.00988 27.40 0.00701 0.676 0.00
LOBBY_FLR_1 65346.29 65346.29 49.95 4.825 4.825 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.00993 27.40 0.00701 1.894 0.00
ROOM_1_FLR_3 9524.08 9524.08 244.07 0.947 0.947 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 21.11 21.11 0.00854 25.46 0.00700 0.062 0.00
ROOM_2_FLR_3 8648.83 8648.83 221.67 0.860 0.860 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 21.11 21.11 0.00855 24.70 0.00700 0.062 0.00
ROOM_3_MULT19_FLR_3 72611.10 72611.10 2960.84 7.221 7.221 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00848 27.40 0.00701 0.837 0.00
ROOM_4_MULT19_FLR_3 50148.99 50148.99 2044.35 4.988 4.988 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 21.11 21.11 0.00875 21.08 0.00700 0.837 0.00
ROOM_5_FLR_3 8987.72 8987.72 230.32 0.894 0.894 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 21.11 21.11 0.00855 24.54 0.00700 0.062 0.00
ROOM_6_FLR_3 8178.25 8178.25 209.60 0.813 0.813 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 21.11 21.11 0.00855 22.66 0.00700 0.062 0.00
CORRIDOR_FLR_3 16790.14 16790.14 43.12 1.239 1.239 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00959 27.40 0.00701 0.475 0.00
ROOM_1_FLR_6 2469.45 2469.45 63.28 0.246 0.246 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 21.11 21.11 0.00854 25.46 0.00700 0.015 0.00
ROOM_2_FLR_6 2221.04 2221.04 56.92 0.221 0.221 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 21.11 21.11 0.00855 24.95 0.00700 0.015 0.00
ROOM_3_MULT9_FLR_6 15084.30 15084.30 614.92 1.500 1.500 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00859 27.40 0.00701 0.099 0.00
BANQUET_FLR_6 27603.43 27603.43 83.23 2.040 2.040 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 23.98 0.01052 27.40 0.00701 1.188 0.00
DINING_FLR_6 29004.54 29004.54 87.45 2.143 2.143 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 23.99 0.01043 27.40 0.00701 1.188 0.00
KITCHEN_FLR_6 30032.05 30032.05 290.71 2.222 2.222 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01010 26.48 0.00701 0.367 0.00
CORRIDOR_FLR_6 9242.35 9242.35 22.43 0.682 0.682 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00901 27.40 0.00701 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 2426.87 2426.87 1.23 0.106 0.854 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00800 -41.90 0.00006 0.854 0.00
RETAIL_1_FLR_1 4023.04 4023.04 59.98 0.175 0.175 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00747 -41.90 0.00006 0.079 0.00
RETAIL_2_FLR_1 1271.80 1271.80 16.37 0.055 0.092 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00737 -41.90 0.00006 0.092 0.00
MECH_FLR_1 2310.19 2310.19 14.07 0.101 0.101 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00720 -41.90 0.00006 0.000 0.00
STORAGE_FLR_1 1677.16 1677.16 17.70 0.073 0.073 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00735 -41.90 0.00006 0.058 0.00
LAUNDRY_FLR_1 3103.29 3103.29 39.77 0.135 0.135 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00718 -41.90 0.00006 0.000 0.00
CAFE_FLR_1 10213.69 10213.69 54.08 0.445 0.676 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00754 -41.90 0.00006 0.676 0.00
LOBBY_FLR_1 23024.85 23024.85 17.60 1.002 1.894 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00742 -41.90 0.00006 1.894 0.00
ROOM_1_FLR_3 8566.47 8566.47 219.53 0.375 0.375 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00743 -41.90 0.00006 0.062 0.00
ROOM_2_FLR_3 8560.51 8560.51 219.40 0.375 0.375 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00743 -41.90 0.00006 0.062 0.00
ROOM_3_MULT19_FLR_3 48093.19 48093.19 1961.08 2.106 2.106 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00746 -41.90 0.00006 0.837 0.00
ROOM_4_MULT19_FLR_3 48011.57 48011.57 1957.22 2.103 2.103 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00746 -41.90 0.00006 0.837 0.00
ROOM_5_FLR_3 8555.67 8555.67 219.25 0.375 0.375 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00743 -41.90 0.00006 0.062 0.00
ROOM_6_FLR_3 8549.71 8549.71 219.13 0.374 0.374 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00743 -41.90 0.00006 0.062 0.00
CORRIDOR_FLR_3 12604.03 12604.03 32.37 0.549 0.549 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00753 -41.90 0.00006 0.475 0.00
ROOM_1_FLR_6 2655.62 2655.62 68.05 0.116 0.116 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00754 -41.90 0.00006 0.015 0.00
ROOM_2_FLR_6 2653.69 2653.69 68.01 0.116 0.116 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00754 -41.90 0.00006 0.015 0.00
ROOM_3_MULT9_FLR_6 12759.67 12759.67 520.15 0.559 0.559 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00755 -41.90 0.00006 0.099 0.00
BANQUET_FLR_6 9063.03 9063.03 27.33 0.395 1.188 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00766 -41.90 0.00006 1.188 0.00
DINING_FLR_6 9214.15 9214.15 27.78 0.401 1.188 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00767 -41.90 0.00006 1.188 0.00
KITCHEN_FLR_6 4379.94 4379.94 42.40 0.191 0.367 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00715 -41.90 0.00006 0.367 0.00
CORRIDOR_FLR_6 9638.59 9638.59 23.39 0.420 0.420 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00772 -41.90 0.00006 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 20.98 20.98 7.71 7.71 20.9801 10.5291 20.9801 0.5019 0.3000
FLR_3_DOAS 16.40 2.05 6.50 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 9085.032 9085.032 1.280945 0.00019874 270.476 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9085.03 9085.03 1.280945 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00799799 50.9004 2426.87 0.00 9124.54 9124.54
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 4932.074 4932.074 0.175143 0.00010789 204.365 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4932.07 4932.07 0.175143 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00747433 47.6138 4023.04 0.00 4955.66 4955.66
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1985.953 1985.953 0.137580 0.00004344 66.862 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1985.95 1985.95 0.137580 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00736745 46.9370 1271.80 0.00 1996.64 1996.64
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2832.109 2832.109 0.100581 0.00006195 117.345 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2832.11 2832.11 0.100581 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00719627 45.8592 2310.19 0.00 2845.66 2845.66
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 2126.795 2126.795 0.086626 0.00004652 82.490 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2126.79 2126.79 0.086626 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00734771 46.8130 1677.16 0.00 2137.16 2137.16
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 3804.089 3804.089 0.135101 0.00008321 157.617 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3804.09 3804.09 0.135101 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00718434 45.7881 3103.29 0.00 3822.28 3822.28
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 15480.802 15480.802 1.014604 0.00033864 526.102 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 15480.80 15480.80 1.014604 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00753835 48.0156 10213.69 0.00 15563.71 15563.71
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 37777.416 37777.416 2.841755 0.00082638 1254.879 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 37777.42 37777.42 2.841755 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00742387 47.2923 23024.85 0.00 37950.88 37950.88
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 10314.885 -999.000 0.947171 0.00029500 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown 7/21 17:30:00 10314.89 10207.64 0.947171 21.69 15.44 0.00854359 12.80 11.96 0.00850000 25.46 0.00700420 15.45 0.0000 21.11 0.00854359 53.9571 9524.08 0.00 10482.06 10482.06
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 8566.473 8566.473 0.375126 0.00018739 386.859 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8566.47 8566.47 0.375126 21.11 14.22 0.00743332 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00743332 47.0347 8566.47 0.00 9587.06 9587.06
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 9377.795 -999.000 0.860127 0.00026820 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown 7/21 18:10:00 9377.80 9271.04 0.860127 21.69 15.44 0.00854778 12.80 11.96 0.00850000 24.70 0.00700305 15.17 0.0000 21.11 0.00854778 53.9832 8648.83 0.00 9529.61 9529.61
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 8560.511 8560.511 0.374865 0.00018726 386.590 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8560.51 8560.51 0.374865 21.11 14.22 0.00743299 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00743299 47.0327 8560.51 0.00 9580.39 9580.39
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 77688.879 -999.000 7.220935 0.00222185 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 77688.88 77688.88 7.220935 21.69 15.38 0.00847633 12.80 11.94 0.00847633 27.40 0.00700714 16.15 0.0000 21.11 0.00847633 53.5371 72611.10 0.00 78957.50 78957.50
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 48093.185 48093.185 2.106153 0.00105204 2171.879 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 48093.19 48093.19 2.106153 21.11 14.25 0.00746280 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00746280 47.2152 48093.19 0.00 53824.74 53824.74
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 57342.902 -999.000 4.987546 0.00163997 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 unknown 7/21 21:20:00 57342.90 54141.45 4.987546 21.69 15.62 0.00874532 12.80 11.96 0.00850000 21.08 0.00699765 13.80 0.0000 21.11 0.00874532 55.2147 50148.99 0.00 58248.03 57191.74
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 48011.566 48011.566 2.102579 0.00105025 2168.194 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 48011.57 48011.57 2.102579 21.11 14.25 0.00746181 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00746181 47.2090 48011.57 0.00 53733.39 53733.39
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 9740.038 -999.000 0.893830 0.00027856 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown 7/21 10:40:00 9740.04 9633.60 0.893830 21.69 15.44 0.00854584 12.80 11.96 0.00850000 24.54 0.00700282 15.11 0.0000 21.11 0.00854584 53.9711 8987.72 0.00 9897.80 9897.80
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 8555.675 8555.675 0.374654 0.00018716 386.371 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8555.67 8555.67 0.374654 21.11 14.22 0.00743265 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00743265 47.0306 8555.67 0.00 9574.97 9574.97
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 8872.806 -999.000 0.813327 0.00025376 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 unknown 7/21 09:30:00 8872.81 8767.31 0.813327 21.69 15.44 0.00854993 12.80 11.96 0.00850000 22.66 0.00700000 14.41 0.0000 21.11 0.00854993 53.9966 8178.25 0.00 9016.37 9016.37
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 8549.714 8549.714 0.374393 0.00018703 386.102 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8549.71 8549.71 0.374393 21.11 14.22 0.00743232 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00743232 47.0285 8549.71 0.00 9568.30 9568.30
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 16304.080 16304.080 0.712522 0.00035665 615.234 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 16304.08 16304.08 0.712522 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00752571 47.9319 12604.03 0.00 16384.88 16384.88
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2673.363 -999.000 0.245587 0.00007646 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown 7/21 17:30:00 2673.36 2646.53 0.245587 21.69 15.44 0.00854207 12.80 11.96 0.00850000 25.46 0.00700420 15.45 0.0000 21.11 0.00854207 53.9476 2469.45 0.00 2716.26 2716.26
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2655.622 2655.622 0.116290 0.00005809 119.917 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2655.62 2655.62 0.116290 21.11 14.32 0.00753648 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00753648 47.6795 2655.62 0.00 2972.01 2972.01
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2407.359 -999.000 0.220882 0.00006885 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 2407.36 2380.70 0.220882 21.69 15.44 0.00854646 12.80 11.96 0.00850000 24.95 0.00700344 15.26 0.0000 21.11 0.00854646 53.9750 2221.04 0.00 2446.35 2446.35
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2653.687 2653.687 0.116206 0.00005805 119.830 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2653.69 2653.69 0.116206 21.11 14.31 0.00753620 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00753620 47.6777 2653.69 0.00 2969.85 2969.85
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 16528.978 -999.000 1.500178 0.00047272 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 16528.98 16192.82 1.500178 21.69 15.48 0.00858613 12.80 11.96 0.00850000 27.40 0.00700714 16.15 0.0000 21.11 0.00858613 54.2229 15084.30 0.00 16793.99 16793.99
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 12759.665 12759.665 0.558763 0.00027912 576.171 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 12759.67 12759.67 0.558763 21.11 14.33 0.00755471 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00755471 47.7920 12759.67 0.00 14280.02 14280.02
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 18311.331 18311.331 1.780714 0.00040056 575.710 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 18311.33 18311.33 1.780714 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00766089 48.7838 9063.03 0.00 18388.74 18388.74
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 18464.304 18464.304 1.781053 0.00040391 581.383 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 18464.30 18464.30 1.781053 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00766622 48.8173 9214.15 0.00 18542.31 18542.31
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7237.824 7237.824 0.551101 0.00015833 239.696 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 7237.82 7237.82 0.551101 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00715181 45.5858 4379.94 0.00 7267.16 7267.16
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 11818.460 11818.460 0.419652 0.00025853 489.731 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 11818.46 11818.46 0.419652 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00771850 49.1453 9638.59 0.00 11874.99 11874.99
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 369526.957 -999.000 20.980095 0.01056842 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 369526.96 369526.95 20.980095 25.51 16.75 0.00849425 10.95 10.95 0.00849425 27.40 0.00700714 16.15 44.4669 23.99 0.00967152 51.1812 284078.94 0.00 374449.63 358856.50
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 439349.948 439349.948 6.294028 0.00961079 7011.352 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 439349.95 439349.95 6.294028 -41.90 -41.90 0.00006450 16.70 13.04 0.00800000 -41.90 0.00006450 -41.90 148.2230 21.00 0.00751511 47.8664 91998.45 0.00 246862.33 246862.33
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 38332.296 -999.000 2.051317 0.00109630 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38332.30 38332.30 2.051317 27.40 16.15 0.00700714 11.91 10.04 0.00700714 27.40 0.00700714 16.15 99.9965 21.11 0.00858862 54.2375 164911.70 0.00 38875.86 38875.86
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 42957.200 42957.200 0.615395 0.00093969 685.531 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 42957.20 42957.20 0.615395 -41.90 -41.90 0.00006450 16.70 13.04 0.00800000 -41.90 0.00006450 -41.90 333.3216 21.11 0.00746322 47.2180 148406.10 0.00 24136.83 24136.83



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 9085.032 9085.032 1.280945 0.00019874 270.476 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 1.1405 1.163445 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9085.03 9085.03 1.0000 1.51848280 1.280945 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.19871506 60.00 48.89 11.11 0.000 9085.03 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00799799 21.00 0.00799799 50.9004 2426.87 0.00 9124.54 9124.54 1.51848280 16.60 13.15 0.00800000 36934.7 22.49 15.41 0.00800000 42943.7
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4932.074 4932.074 0.175143 0.00010789 204.365 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 0.6191 0.631610 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4932.07 4932.07 1.0000 0.20762184 0.175143 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.10787824 60.00 48.89 11.11 0.000 4932.07 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00747433 21.00 0.00747433 47.6138 4023.04 0.00 4955.66 4955.66 0.20762184 16.60 13.15 0.00800000 36934.7 40.01 21.18 0.00800000 60803.4
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1985.953 1985.953 0.137580 0.00004344 66.862 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 0.2493 0.254325 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1985.95 1985.95 1.0000 0.16309223 0.137580 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.04343835 60.00 48.89 11.11 0.000 1985.95 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00736745 21.00 0.00736745 46.9370 1271.80 0.00 1996.64 1996.64 0.16309223 16.60 13.15 0.00800000 36934.7 28.61 17.57 0.00800000 49177.1
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2832.109 2832.109 0.100581 0.00006195 117.345 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 0.3555 0.362685 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2832.11 2832.11 1.0000 0.11923237 0.100581 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.06194615 60.00 48.89 11.11 0.000 2832.11 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00719627 21.00 0.00719627 45.8592 2310.19 0.00 2845.66 2845.66 0.11923237 16.60 13.15 0.00800000 36934.7 40.01 21.18 0.00800000 60801.2
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 2126.795 2126.795 0.086626 0.00004652 82.490 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 0.2670 0.272361 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2126.79 2126.79 1.0000 0.10268985 0.086626 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.04651895 60.00 48.89 11.11 0.000 2126.79 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00734771 21.00 0.00734771 46.8130 1677.16 0.00 2137.16 2137.16 0.10268985 16.60 13.15 0.00800000 36934.7 37.01 20.28 0.00800000 57746.6
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 3804.089 3804.089 0.135101 0.00008321 157.617 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 0.4775 0.487158 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3804.09 3804.09 1.0000 0.16015355 0.135101 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.08320607 60.00 48.89 11.11 0.000 3804.09 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00718434 21.00 0.00718434 45.7881 3103.29 0.00 3822.28 3822.28 0.16015355 16.60 13.15 0.00800000 36934.7 40.01 21.18 0.00800000 60801.1
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 15480.802 15480.802 1.014604 0.00033864 526.102 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 1.9434 1.982498 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 15480.80 15480.80 1.0000 1.20275152 1.014604 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.33860842 60.00 48.89 11.11 0.000 15480.80 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00753835 21.00 0.00753835 48.0156 10213.69 0.00 15563.71 15563.71 1.20275152 16.60 13.15 0.00800000 36934.7 29.29 17.80 0.00800000 49874.8
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 37777.416 37777.416 2.841755 0.00082638 1254.879 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 4.7424 4.837841 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 37777.42 37777.42 1.0000 3.36872849 2.841755 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.82629772 60.00 48.89 11.11 0.000 37777.42 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00742387 21.00 0.00742387 47.2923 23024.85 0.00 37950.88 37950.88 3.36872849 16.60 13.15 0.00800000 36934.7 27.65 17.24 0.00800000 48200.4
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 10314.885 -999.000 0.947171 0.00029500 -999.000 -999.0000 1.00000 1.00000 1020.7221 1004.8586 1.1854 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.947171 1.12281412   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 1.7112 1.711123 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown unknown unknown 7/21 17:30:00 Sensible 10314.89 10207.64 1.0000 1.12281412 0.947171 21.69 15.44 0.00854359 43508.8 12.80 11.96 0.00850000 34322.2 0.29496880 6.70 15.03 8.33 0.000 10314.89 25.46 0.00700420 15.45 0.00000000 0.0000 21.11 0.00854359 21.11 0.00854359 53.9571 9524.08 0.00 10482.06 10482.06 1.12281412 21.69 15.60 0.00854359 43508.8 12.55 12.04 0.00854359 34173.3
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 8566.473 8566.473 0.375126 0.00018739 386.859 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.947171 1.12281412   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 1.0754 1.097037 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8566.47 8566.47 1.0000 0.44468967 0.375126 21.11 14.22 0.00743332 40092.6 40.00 21.00 0.00800000 60796.0 0.18737271 60.00 48.89 11.11 0.000 8566.47 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00743332 21.11 0.00743332 47.0347 8566.47 0.00 9587.06 9587.06 0.44468967 16.60 12.60 0.00743332 35500.0 37.76 20.09 0.00743332 57059.0
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 9377.795 -999.000 0.860127 0.00026820 -999.000 -999.0000 1.00000 1.00000 1020.7299 1004.8586 1.1854 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.860127 1.01962887   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 1.5557 1.555670 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown unknown unknown 7/21 18:10:00 Sensible 9377.80 9271.04 1.0000 1.01962887 0.860127 21.69 15.44 0.00854778 43519.5 12.80 11.96 0.00850000 34322.2 0.26817138 6.70 15.03 8.33 0.000 9377.80 24.70 0.00700305 15.17 0.00000000 0.0000 21.11 0.00854778 21.11 0.00854778 53.9832 8648.83 0.00 9529.61 9529.61 1.01962887 21.69 15.60 0.00854778 43519.5 12.54 12.04 0.00854778 34173.3
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 8560.511 8560.511 0.374865 0.00018726 386.590 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.860127 1.01962887   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 1.0746 1.096274 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8560.51 8560.51 1.0000 0.44438020 0.374865 21.11 14.22 0.00743299 40091.7 40.00 21.00 0.00800000 60796.0 0.18724232 60.00 48.89 11.11 0.000 8560.51 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00743299 21.11 0.00743299 47.0327 8560.51 0.00 9580.39 9580.39 0.44438020 16.60 12.60 0.00743299 35499.2 37.76 20.09 0.00743299 57058.2
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 77688.879 -999.000 7.220935 0.00222185 -999.000 -999.0000 1.00000 1.00000 1020.5971 1004.8586 1.1854 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.220935 8.55998046   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 12.8879 12.887706 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 77688.88 77688.88 1.0000 8.55998046 7.220935 21.69 15.38 0.00847633 43338.3 12.80 11.94 0.00847633 34262.4 2.22162395 6.70 15.03 8.33 0.000 77688.88 27.40 0.00700714 16.15 0.00000000 0.0000 21.11 0.00847633 21.11 0.00847633 53.5371 72611.10 0.00 78957.50 78957.50 8.55998046 21.69 15.54 0.00847633 43338.3 12.65 12.02 0.00847633 34114.2
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 48093.185 48093.185 2.106153 0.00105204 2171.879 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.220935 8.55998046   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 6.0374 6.158896 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 48093.19 48093.19 1.0000 2.49671689 2.106153 21.11 14.25 0.00746280 40168.8 40.00 21.00 0.00800000 60796.0 1.05193245 60.00 48.89 11.11 0.000 48093.19 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00746280 21.11 0.00746280 47.2152 48093.19 0.00 53824.74 53824.74 2.49671689 16.60 12.63 0.00746280 35574.6 37.76 20.11 0.00746280 57132.8
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 57342.902 -999.000 4.987546 0.00163997 -999.000 -999.0000 1.00000 1.00000 1021.0971 1004.8586 1.1854 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 4.987546 5.91243269   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 9.5127 9.512538 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 unknown unknown unknown 7/21 21:20:00 Sensible 57342.90 54141.45 1.0000 5.91243269 4.987546 21.69 15.62 0.00874532 44020.9 12.80 11.96 0.00850000 34322.2 1.63980181 6.70 15.03 8.33 0.000 57342.90 21.08 0.00699765 13.80 0.00000000 0.0000 21.11 0.00874532 21.11 0.00874532 55.2147 50148.99 0.00 58248.03 57191.74 5.91243269 21.69 15.77 0.00874532 44020.9 12.22 12.03 0.00867453 34169.1
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 48011.566 48011.566 2.102579 0.00105025 2168.194 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 4.987546 5.91243269   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 6.0271 6.148443 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 48011.57 48011.57 1.0000 2.49247965 2.102579 21.11 14.25 0.00746181 40166.3 40.00 21.00 0.00800000 60796.0 1.05014720 60.00 48.89 11.11 0.000 48011.57 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00746181 21.11 0.00746181 47.2090 48011.57 0.00 53733.39 53733.39 2.49247965 16.60 12.62 0.00746181 35572.1 37.76 20.11 0.00746181 57130.3
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 9740.038 -999.000 0.893830 0.00027856 -999.000 -999.0000 1.00000 1.00000 1020.7263 1004.8586 1.1854 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.893830 1.05958079   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 1.6158 1.615762 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown unknown unknown 7/21 10:40:00 Sensible 9740.04 9633.60 1.0000 1.05958079 0.893830 21.69 15.44 0.00854584 43514.5 12.80 11.96 0.00850000 34322.2 0.27853022 6.70 15.03 8.33 0.000 9740.04 24.54 0.00700282 15.11 0.00000000 0.0000 21.11 0.00854584 21.11 0.00854584 53.9711 8987.72 0.00 9897.80 9897.80 1.05958079 21.69 15.60 0.00854584 43514.5 12.54 12.04 0.00854584 34173.3
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 8555.675 8555.675 0.374654 0.00018716 386.371 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.893830 1.05958079   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 1.0740 1.095654 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8555.67 8555.67 1.0000 0.44412914 0.374654 21.11 14.22 0.00743265 40090.9 40.00 21.00 0.00800000 60796.0 0.18713653 60.00 48.89 11.11 0.000 8555.67 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00743265 21.11 0.00743265 47.0306 8555.67 0.00 9574.97 9574.97 0.44412914 16.60 12.60 0.00743265 35498.3 37.76 20.09 0.00743265 57057.3
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 8872.806 -999.000 0.813327 0.00025376 -999.000 -999.0000 1.00000 1.00000 1020.7339 1004.8586 1.1854 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.813327 0.96415026   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 1.4719 1.471898 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 unknown unknown unknown 7/21 09:30:00 Sensible 8872.81 8767.31 1.0000 0.96415026 0.813327 21.69 15.44 0.00854993 43524.9 12.80 11.96 0.00850000 34322.2 0.25373050 6.70 15.03 8.33 0.000 8872.81 22.66 0.00700000 14.41 0.00000000 0.0000 21.11 0.00854993 21.11 0.00854993 53.9966 8178.25 0.00 9016.37 9016.37 0.96415026 21.69 15.60 0.00854993 43524.9 12.53 12.04 0.00854993 34173.3
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 8549.714 8549.714 0.374393 0.00018703 386.102 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.813327 0.96415026   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 1.0733 1.094891 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8549.71 8549.71 1.0000 0.44381970 0.374393 21.11 14.22 0.00743232 40090.1 40.00 21.00 0.00800000 60796.0 0.18700615 60.00 48.89 11.11 0.000 8549.71 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00743232 21.11 0.00743232 47.0285 8549.71 0.00 9568.30 9568.30 0.44381970 16.60 12.60 0.00743232 35497.5 37.76 20.09 0.00743232 57056.5
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 16304.080 16304.080 0.712522 0.00035665 615.234 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 2.0467 2.087928 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 16304.08 16304.08 1.0000 0.84465153 0.712522 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.35661583 60.00 48.89 11.11 0.000 16304.08 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00752571 21.00 0.00752571 47.9319 12604.03 0.00 16384.88 16384.88 0.84465153 16.60 13.15 0.00800000 36934.7 35.62 19.85 0.00800000 56333.1
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2673.363 -999.000 0.245587 0.00007646 -999.000 -999.0000 1.00000 1.00000 1020.7193 1004.8586 1.1854 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.245587 0.29112814   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 0.4435 0.443481 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown unknown unknown 7/21 17:30:00 Sensible 2673.36 2646.53 1.0000 0.29112814 0.245587 21.69 15.44 0.00854207 43505.0 12.80 11.96 0.00850000 34322.2 0.07644861 6.70 15.03 8.33 0.000 2673.36 25.46 0.00700420 15.45 0.00000000 0.0000 21.11 0.00854207 21.11 0.00854207 53.9476 2469.45 0.00 2716.26 2716.26 0.29112814 21.69 15.59 0.00854207 43505.0 12.55 12.04 0.00854207 34174.8
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2655.622 2655.622 0.116290 0.00005809 119.917 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.245587 0.29112814   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 0.3334 0.340084 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2655.62 2655.62 1.0000 0.13785517 0.116290 21.11 14.32 0.00753648 40354.7 40.00 21.00 0.00800000 60796.0 0.05808588 60.00 48.89 11.11 0.000 2655.62 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00753648 21.11 0.00753648 47.6795 2655.62 0.00 2972.01 2972.01 0.13785517 16.60 12.70 0.00753648 35761.2 37.76 20.16 0.00753648 57320.1
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2407.359 -999.000 0.220882 0.00006885 -999.000 -999.0000 1.00000 1.00000 1020.7274 1004.8586 1.1854 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.220882 0.26184277   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 0.3994 0.399354 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 2407.36 2380.70 1.0000 0.26184277 0.220882 21.69 15.44 0.00854646 43516.1 12.80 11.96 0.00850000 34322.2 0.06884185 6.70 15.03 8.33 0.000 2407.36 24.95 0.00700344 15.26 0.00000000 0.0000 21.11 0.00854646 21.11 0.00854646 53.9750 2221.04 0.00 2446.35 2446.35 0.26184277 21.69 15.60 0.00854646 43516.1 12.54 12.04 0.00854646 34173.3
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2653.687 2653.687 0.116206 0.00005805 119.830 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.220882 0.26184277   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 0.3331 0.339836 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2653.69 2653.69 1.0000 0.13775473 0.116206 21.11 14.31 0.00753620 40354.0 40.00 21.00 0.00800000 60796.0 0.05804356 60.00 48.89 11.11 0.000 2653.69 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00753620 21.11 0.00753620 47.6777 2653.69 0.00 2969.85 2969.85 0.13775473 16.60 12.70 0.00753620 35760.5 37.76 20.16 0.00753620 57319.4
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 16528.978 -999.000 1.500178 0.00047272 -999.000 -999.0000 1.00000 1.00000 1020.8012 1004.8586 1.1854 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.500178 1.77837007   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 2.7420 2.741970 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 16528.98 16192.82 1.0000 1.77837007 1.500178 21.69 15.48 0.00858613 43616.6 12.80 11.96 0.00850000 34322.2 0.47266962 6.70 15.03 8.33 0.000 16528.98 27.40 0.00700714 16.15 0.00000000 0.0000 21.11 0.00858613 21.11 0.00858613 54.2229 15084.30 0.00 16793.99 16793.99 1.77837007 21.69 15.63 0.00858613 43616.6 12.44 12.04 0.00858613 34173.2
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 12759.665 12759.665 0.558763 0.00027912 576.171 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.500178 1.77837007   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 1.6018 1.634025 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 12759.67 12759.67 1.0000 0.66237982 0.558763 21.11 14.33 0.00755471 40401.5 40.00 21.00 0.00800000 60796.0 0.27908956 60.00 48.89 11.11 0.000 12759.67 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00755471 21.11 0.00755471 47.7920 12759.67 0.00 14280.02 14280.02 0.66237982 16.60 12.72 0.00755471 35807.4 37.76 20.18 0.00755471 57366.0
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 18311.331 18311.331 1.780714 0.00040056 575.710 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 2.2987 2.344980 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 18311.33 18311.33 1.0000 2.11092883 1.780714 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.40052001 60.00 48.89 11.11 0.000 18311.33 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00766089 21.00 0.00766089 48.7838 9063.03 0.00 18388.74 18388.74 2.11092883 16.60 13.15 0.00800000 36934.7 25.14 16.36 0.00800000 45645.9
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 18464.304 18464.304 1.781053 0.00040391 581.383 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 2.3179 2.364570 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 18464.30 18464.30 1.0000 2.11133047 1.781053 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.40386596 60.00 48.89 11.11 0.000 18464.30 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00766622 21.00 0.00766622 48.8173 9214.15 0.00 18542.31 18542.31 2.11133047 16.60 13.15 0.00800000 36934.7 25.21 16.39 0.00800000 45717.0
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 7237.824 7237.824 0.551101 0.00015833 239.696 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 0.9086 0.926888 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 7237.82 7237.82 1.0000 0.65329635 0.551101 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.15831145 60.00 48.89 11.11 0.000 7237.82 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.77 0.00715181 21.00 0.00715181 45.5858 4379.94 0.00 7267.16 7267.16 0.65329635 16.60 13.15 0.00800000 36934.7 27.51 17.19 0.00800000 48058.6
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 11818.460 11818.460 0.419652 0.00025853 489.731 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 1.4836 1.513492 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 11818.46 11818.46 1.0000 0.49747213 0.419652 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.25850278 60.00 48.89 11.11 0.000 11818.46 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00771850 21.00 0.00771850 49.1453 9638.59 0.00 11874.99 11874.99 0.49747213 16.60 13.15 0.00800000 36934.7 40.01 21.18 0.00800000 60805.4
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 369526.957 -999.000 20.980095 0.01056842 -999.000 -999.0000 1.00000 1.00000 1020.6304 1004.8586 1.1854 VAV WITH REHEAT FAN Fan:VariableVolume 20.980095 24.87062847   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 61.3015 61.301485 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 369526.96 369526.95 1.0000 24.87062847 20.980095 25.51 16.75 0.00849425 47275.5 10.95 10.95 0.00849425 32417.5 10.56734611 6.70 15.03 8.33 47008.810 322518.15 27.40 0.00700714 16.15 9.32920000 44.4669 23.99 0.00968501 23.99 0.00967152 51.1812 284078.94 0.00 374449.63 358856.50 24.87062847 25.51 16.91 0.00849425 47275.5 11.37 11.24 0.00824565 32219.6
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 439349.948 439349.948 6.294028 0.00961079 7011.352 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV WITH REHEAT FAN Fan:VariableVolume 20.980095 24.87062847   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 55.1539 56.263907 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 439349.95 439349.95 1.0000 7.46118854 6.294028 -41.90 -41.90 0.00006450 -41946.5 16.70 13.04 0.00800000 37036.7 9.60981193 60.00 48.89 11.11 0.000 439349.95 -41.90 0.00006450 -41.90 9.32920000 148.2230 20.98 0.00756209 21.00 0.00751511 47.8664 91998.45 0.00 246862.33 246862.33 7.46118854 2.80 -4.37 0.00006450 2975.2 35.72 12.99 0.00006450 36061.4
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 38332.296 -999.000 2.051317 0.00109630 -999.000 -999.0000 1.00000 1.00000 1017.8659 1004.8586 1.1854 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43162656   4197.9300 999.8980 17.23831986 15.03 6.70 8.33 602802.62 6.3590 6.359013 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 38332.30 38332.30 1.0000 2.43171206 2.051317 27.40 16.15 0.00700714 45414.0 11.91 10.04 0.00700714 29650.5 1.09618699 6.70 15.03 8.33 2195.006 36137.29 27.40 0.00700714 16.15 2.05124512 99.9965 21.11 0.00858355 21.11 0.00858862 54.2375 164911.70 0.00 38875.86 38875.86 2.43171206 27.40 16.31 0.00700714 45414.0 11.69 10.08 0.00700714 29426.9
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 42957.200 42957.200 0.615395 0.00093969 685.531 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43162656   4197.9300 999.8980 17.07988738 48.89 60.00 11.11 796588.91 5.3926 5.501173 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 42957.20 42957.20 1.0000 0.72951362 0.615395 -41.90 -41.90 0.00006450 -41946.5 16.70 13.04 0.00800000 37036.7 0.93959409 60.00 48.89 11.11 0.000 42957.20 -41.90 0.00006450 -41.90 2.05124512 333.3216 21.11 0.00746610 21.11 0.00746322 47.2180 148406.10 0.00 24136.83 24136.83 0.72951362 2.80 -4.37 0.00006450 2975.2 35.72 12.99 0.00006450 36061.4



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 20.98 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000914 0.000000 0.000000 Sum   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 505.33 8760.00 505.33
RETAIL_1_FLR_1 4345.67 7561.33 3818.00
RETAIL_2_FLR_1 1862.50 8691.50 1862.50
MECH_FLR_1 3036.67 7640.83 3034.33
STORAGE_FLR_1 3806.50 8760.00 3806.50
LAUNDRY_FLR_1 8665.83 2575.67 2575.67
CAFE_FLR_1 2836.83 8183.83 2646.17
LOBBY_FLR_1 1179.00 8166.17 1028.50
ROOM_1_FLR_3 4506.83 8685.33 4506.83
ROOM_2_FLR_3 4962.83 8468.33 4805.17
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4133.67 8752.83 4133.67
ROOM_5_FLR_3 4309.83 8570.33 4309.00
ROOM_6_FLR_3 4661.33 8557.83 4611.83
CORRIDOR_FLR_3 3240.00 8760.00 3240.00
ROOM_1_FLR_6 4806.33 8622.50 4806.33
ROOM_2_FLR_6 5296.67 8414.50 5096.17
ROOM_3_MULT9_FLR_6 4030.50 8484.17 4025.33
BANQUET_FLR_6 1132.00 7786.17 737.67
DINING_FLR_6 1044.00 7245.83 275.00
KITCHEN_FLR_6 8540.17 5667.50 5667.00
CORRIDOR_FLR_6 3924.50 7289.17 3663.50
Facility 8760.00 8760.00 7928.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 2.17 0.00 2.17
ROOM_2_FLR_3 0.00 4.00 0.00 4.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 3.33 18.00 3.33 18.00
ROOM_5_FLR_3 0.00 3.33 0.00 3.33
ROOM_6_FLR_3 0.00 10.33 0.00 10.33
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 3.67 0.00 3.67
ROOM_2_FLR_6 0.00 8.00 0.00 8.00
ROOM_3_MULT9_FLR_6 0.00 2.67 0.00 2.67
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 3.33 31.33 3.33 31.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.678 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.205 0.145 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.140 0.048 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.073 0.054 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.587 0.054 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 14.432 0.156 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 3.460 0.114 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.402 0.047 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.343 0.188 0.000 0.031
ROOM_2_FLR_3 0.95 1.50 118.93 0.343 0.188 0.000 0.033
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.390 0.083 0.000 0.054
ROOM_5_FLR_3 0.95 1.50 118.94 0.343 0.188 0.000 0.031
ROOM_6_FLR_3 0.95 1.50 118.93 0.343 0.188 0.000 0.035
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.383 0.023 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.343 0.188 0.000 0.037
ROOM_2_FLR_6 0.95 1.50 118.93 0.343 0.188 0.000 0.035
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.390 0.153 0.000 0.058
BANQUET_FLR_6 144.99 249.90 1010.89 4.504 0.054 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 4.516 0.054 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 14.377 0.157 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.411 0.038 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.551 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 0.932 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.931 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.006 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.478 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 5.392 0.002 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 2.818 0.002 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.142 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.312 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.002 0.000 0.000
BANQUET_FLR_6 144.99 249.90 1010.89 3.665 0.001 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 3.669 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 4.190 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.312 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.79 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.047
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.56 142.30 748.35 188.86 0.0000 0.173
LOBBY_FLR_1 VAV WITH REHEAT 245.09 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.25 1604.23 35184.81 11345.29 0.0000 137.036


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 28116156.84 0.00 28116156.84 0.00 28116156.84 26946214.98 6267.24 69.61 2423.15 0.00
RETAIL_1_FLR_1 2751252.28 0.00 2751252.28 331381.90 3082634.18 2498216.28 6061.89 78.19 2619.92 0.00
RETAIL_2_FLR_1 3019808.21 0.00 3019808.21 127913.83 3147722.04 2294951.32 732.17 937.40 7090.43 0.00
MECH_FLR_1 405284.20 0.00 405284.20 302312.31 707596.51 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1901400.51 0.00 1901400.51 174417.55 2075818.06 1821682.01 6264.93 70.60 2424.47 0.00
LAUNDRY_FLR_1 38137701.78 0.00 38137701.78 412792.02 38550493.80 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 22271529.77 0.00 22271529.77 732538.45 23004068.22 14544917.54 263.83 144.01 8352.15 0.00
LOBBY_FLR_1 62397297.66 0.00 62397297.66 2093029.67 64490327.33 59728886.00 6261.62 72.71 2425.67 0.00
ROOM_1_FLR_3 1406076.84 32059.06 1438135.90 192345.67 1630481.56 1946875.62 2433.33 5953.83 372.83 0.00
ROOM_2_FLR_3 1405912.09 33199.74 1439111.84 192330.99 1631442.83 1946647.51 2433.33 5989.21 337.45 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 53666.60 1153578.57 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19070354.14 34663.80 19105017.94 53681.27 19158699.21 26405105.73 2433.33 5962.83 363.84 0.00
ROOM_5_FLR_3 1406076.84 32060.62 1438137.46 192345.67 1630483.13 1946875.62 2433.33 5953.83 372.83 0.00
ROOM_6_FLR_3 1405912.09 35666.44 1441578.54 192330.99 1633909.53 1946647.51 2433.33 5953.89 372.78 0.00
CORRIDOR_FLR_3 15639528.46 0.00 15639528.46 232584.61 15872113.07 14972100.18 6260.09 73.94 2425.97 0.00
ROOM_1_FLR_6 351519.21 37557.60 389076.80 192388.03 581464.83 486718.90 2323.66 5955.81 480.53 0.00
ROOM_2_FLR_6 351478.02 35191.97 386670.00 192373.35 579043.34 486661.88 2338.27 6018.78 402.95 0.00
ROOM_3_MULT9_FLR_6 2258331.41 37528.36 2295859.77 98432.45 2394292.22 3126920.42 2433.33 5953.50 373.17 0.00
BANQUET_FLR_6 39106198.53 0.00 39106198.53 469763.21 39575961.74 37458366.31 6266.87 69.78 2423.35 0.00
DINING_FLR_6 39171133.89 0.00 39171133.89 469763.21 39640897.10 37458366.31 6263.77 69.33 2426.90 0.00
KITCHEN_FLR_6 38606020.46 0.00 38606020.46 420546.99 39026567.45 11584760.86 6.83 3.17 8750.00 0.00
CORRIDOR_FLR_6 4427929.89 0.00 4427929.89 411607.93 4839537.81 3961413.96 6009.74 85.44 2664.82 0.00
Total Facility 0.19E+10 3576897.44 0.19E+10 19382910.50 0.19E+10 0.43E+10 8760.00 6423.10 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 0.8916 0.0000 0.8916 0.0000 0.8916 0.8545 6267.24 69.61 2423.15
RETAIL_1_FLR_1 0.0872 0.0000 0.0872 0.0105 0.0977 0.0792 6061.89 78.19 2619.92
RETAIL_2_FLR_1 0.0958 0.0000 0.0958 0.0041 0.0998 0.0728 732.17 937.40 7090.43
MECH_FLR_1 0.0129 0.0000 0.0129 0.0096 0.0224 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0603 0.0000 0.0603 0.0055 0.0658 0.0578 6264.93 70.60 2424.47
LAUNDRY_FLR_1 1.2093 0.0000 1.2093 0.0131 1.2224 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7062 0.0000 0.7062 0.0232 0.7295 0.4612 263.83 144.01 8352.15
LOBBY_FLR_1 1.9786 0.0000 1.9786 0.0664 2.0450 1.8940 6261.62 72.71 2425.67
ROOM_1_FLR_3 0.0446 0.0010 0.0456 0.0061 0.0517 0.0617 2433.33 5953.83 372.83
ROOM_2_FLR_3 0.0446 0.0011 0.0456 0.0061 0.0517 0.0617 2433.33 5989.21 337.45
ROOM_4_MULT19_FLR_3 0.6047 0.0011 0.6058 0.0017 0.6075 0.8373 2433.33 5962.83 363.84
ROOM_5_FLR_3 0.0446 0.0010 0.0456 0.0061 0.0517 0.0617 2433.33 5953.83 372.83
ROOM_6_FLR_3 0.0446 0.0011 0.0457 0.0061 0.0518 0.0617 2433.33 5953.89 372.78
CORRIDOR_FLR_3 0.4959 0.0000 0.4959 0.0074 0.5033 0.4748 6260.09 73.94 2425.97
ROOM_1_FLR_6 0.0111 0.0012 0.0123 0.0061 0.0184 0.0154 2323.66 5955.81 480.53
ROOM_2_FLR_6 0.0111 0.0011 0.0123 0.0061 0.0184 0.0154 2338.27 6018.78 402.95
ROOM_3_MULT9_FLR_6 0.0716 0.0012 0.0728 0.0031 0.0759 0.0992 2433.33 5953.50 373.17
BANQUET_FLR_6 1.2400 0.0000 1.2400 0.0149 1.2549 1.1878 6266.87 69.78 2423.35
DINING_FLR_6 1.2421 0.0000 1.2421 0.0149 1.2570 1.1878 6263.77 69.33 2426.90
KITCHEN_FLR_6 1.2242 0.0000 1.2242 0.0133 1.2375 0.3674 6.83 3.17 8750.00
CORRIDOR_FLR_6 0.1404 0.0000 0.1404 0.0131 0.1535 0.1256 6009.74 85.44 2664.82
Total Facility 58.2110 0.1134 58.3244 0.4853 58.8097 73.7328 8760.00 6423.10 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.42E+09 0.00 0.42E+09 0.21E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 40409237.68 277927.61 40687165.28 64690340.46 8756.33 3.50 0.17 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 13.1878 0.0000 13.1878 6.7627 0.00 0.00 8760.00
FLR_3_DOAS 1.2814 0.0088 1.2902 2.0513 8756.33 3.50 0.17


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 7.77 3900.28 0.00 0.00 0.00 4851.96 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6691.67 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 14.5695 15.5400 0.0000 0.0000 0.0000 11.3002 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.6776 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1344
Defaulted Fields 1183
Fields with Defaults 4016
Autosized Fields 349
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 3807.20 51261.62 27-MAY-03:10 276049.69 29-JUN-19:10
Electricity:Building 2094.13 27762.57 10-JUN-04:50 122617.06 02-JAN-20:10
Electricity:Zone:BASEMENT 230.70 2823.84 02-JAN-02:10 16796.09 02-JAN-20:10
Electricity:SpaceType:GENERAL 2087.04 27621.42 10-JUN-04:50 122375.73 02-JAN-20:10
InteriorLights:Electricity 438.58 3727.75 10-JUN-04:50 36244.21 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 87.60 795.94 02-JAN-02:10 7163.56 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 438.58 3727.75 10-JUN-04:50 36244.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity 438.58 3727.75 10-JUN-04:50 36244.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 87.60 795.94 02-JAN-02:10 7163.56 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 438.58 3727.75 10-JUN-04:50 36244.21 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 14.15 180.36 02-JAN-02:10 1009.79 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 3.96 36.02 02-JAN-02:10 324.19 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 3.96 36.02 02-JAN-02:10 324.19 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 16.39 208.86 02-JAN-02:10 1169.34 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 4.59 41.71 02-JAN-02:10 375.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 4.59 41.71 02-JAN-02:10 375.41 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.68 251.36 02-JAN-02:10 1511.12 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.21 74.63 02-JAN-02:10 671.67 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.21 74.63 02-JAN-02:10 671.67 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.48 68.09 02-JAN-02:10 396.12 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.88 17.11 02-JAN-02:10 153.96 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.88 17.11 02-JAN-02:10 153.96 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 71.44 994.53 02-JAN-02:10 4859.35 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.50 31.84 02-JAN-02:10 286.55 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.50 31.84 02-JAN-02:10 286.55 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 20.56 221.98 06-MAY-05:00 1732.96 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 6.22 18.77 06-MAY-05:00 767.68 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 6.22 18.77 06-MAY-05:00 767.68 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 223.46 2728.56 10-JUN-04:50 16487.72 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 74.46 617.15 10-JUN-04:50 6458.51 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 74.46 617.15 10-JUN-04:50 6458.51 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 253.77 3619.58 02-JAN-10:10 20179.99 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 58.78 497.64 01-JAN-02:10 4523.96 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 253.84 3620.57 02-JAN-10:10 20185.51 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 58.79 497.77 01-JAN-02:10 4525.19 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 15.40 220.79 01-JAN-02:10 1160.40 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 4.92 41.68 01-JAN-02:10 378.87 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 15.40 220.76 01-JAN-02:10 1160.26 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 4.92 41.67 01-JAN-02:10 378.82 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 51.72 469.94 02-JAN-02:10 4229.48 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 51.72 469.94 02-JAN-02:10 4229.48 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 51.72 469.94 02-JAN-02:10 4229.48 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 3.85 55.20 01-JAN-02:10 290.10 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.23 10.42 01-JAN-02:10 94.72 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 3.85 55.19 01-JAN-02:10 290.07 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.23 10.42 01-JAN-02:10 94.71 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 30.06 428.75 02-JAN-10:10 2390.39 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 6.96 58.95 01-JAN-02:10 535.88 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 189.56 2339.18 06-MAY-04:50 8096.02 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 13.70 89.87 06-MAY-04:50 1348.12 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 13.70 89.87 06-MAY-04:50 1348.12 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 189.56 2339.18 06-MAY-04:50 8096.02 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 13.70 89.87 06-MAY-04:50 1348.12 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 13.70 89.87 06-MAY-04:50 1348.12 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 439.77 5902.30 02-JAN-02:10 18508.51 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 8.66 78.67 02-JAN-02:10 708.07 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 8.66 78.67 02-JAN-02:10 708.07 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 13.68 124.34 02-JAN-02:10 1119.06 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 13.68 124.34 02-JAN-02:10 1119.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 13.68 124.34 02-JAN-02:10 1119.06 02-JAN-20:10
InteriorEquipment:Electricity 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1648.46 23893.67 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 43.75 732.84 16-NOV-23:30 2786.43 16-JUL-10:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 461.96 2115.10 31-AUG-01:10 115311.82 29-JUL-18:10
LowTempRefrigeration:Refrigeration:Electricity 15.80 0.00 01-JAN-11:10 1306.63 22-JUL-10:50
MedTempRefrigeration:Refrigeration:Electricity 20.86 631.07 12-JAN-04:10 714.13 25-JUL-13:10
Fans:Electricity 566.47 12659.07 08-SEP-03:00 30214.39 22-JUN-22:00
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityProduced:Facility 114.65 -0.00 16-MAR-18:10 25313.99 01-JUN-12:30
ElectricityProduced:Plant 114.65 -0.00 16-MAR-18:10 25313.99 01-JUN-12:30
Photovoltaic:ElectricityProduced 120.77 0.00 01-JAN-00:10 26309.03 01-JUN-12:30
PowerConversion:ElectricityProduced -6.12 -995.04 01-JUN-12:30 0.00 01-JAN-00:10
Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
DCtoACInverter Ancillary:Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 732.78 14402.34 27-JUN-03:00 38738.46 11-JUL-20:00
ExteriorEquipment:Electricity 390.55 5777.91 17-JUN-03:00 23857.89 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 21.46 378.83 10-JUN-05:00 1269.61 02-JAN-07:20
ElectricityPurchased:Facility 3692.55 51001.25 27-MAY-03:10 270879.15 29-JUN-19:50
ElectricityPurchased:Plant 3692.55 51001.25 27-MAY-03:10 270879.15 29-JUN-19:50
Cogeneration:ElectricityPurchased 3692.55 51001.25 27-MAY-03:10 270879.15 29-JUN-19:50
General:Cogeneration:ElectricityPurchased 3692.55 51001.25 27-MAY-03:10 270879.15 29-JUN-19:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 3692.55 51001.25 27-MAY-03:10 270879.15 29-JUN-19:50
ElectricityNet:Plant 3692.55 51001.25 27-MAY-03:10 270879.15 29-JUN-19:50
Cogeneration:ElectricityNet 3692.55 51001.25 27-MAY-03:10 270879.15 29-JUN-19:50
General:Cogeneration:ElectricityNet 3692.55 51001.25 27-MAY-03:10 270879.15 29-JUN-19:50
General:Fans:Electricity 566.47 12659.07 08-SEP-03:00 30214.39 22-JUN-22:00
ExteriorLights:Electricity 149.24 0.00 01-JAN-11:20 9571.94 01-JAN-00:10
General:ExteriorLights:Electricity 149.24 0.00 01-JAN-11:20 9571.94 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 366.65 5383.28 01-JAN-00:10 22430.31 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.45 15.80 01-JAN-00:10 157.97 01-JAN-07:10
HeatRecovery:Electricity 144.85 0.00 07-FEB-11:00 8265.52 01-JAN-00:10
General:HeatRecovery:Electricity 144.85 0.00 07-FEB-11:00 8265.52 01-JAN-00:10
WaterSystems:Electricity 90.74 1086.56 20-NOV-04:00 4738.76 01-JUN-18:10
Water Heater:WaterSystems:Electricity 90.74 1086.56 20-NOV-04:00 4738.76 01-JUN-18:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 282.70 0.00 01-JAN-00:30 105233.14 29-JUL-18:10
General:Cooling:Electricity 282.70 0.00 01-JAN-00:30 105233.14 29-JUL-18:10
Pumps:Electricity 51.86 47.91 05-JUL-15:10 4248.43 20-JUL-18:10
General:Pumps:Electricity 51.86 47.91 05-JUL-15:10 4248.43 20-JUL-18:10
WIRED_LTG_ELECTRICITY 15.44 0.00 01-JAN-00:10 1275.80 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 7808.42 26805.16 06-APR-02:40 1122896.64 12-JAN-19:10
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 6019.58 13443.27 23-JUN-15:20 1035276.86 12-JAN-19:10
WaterSystems:NaturalGas 3068.63 13443.27 27-FEB-16:20 264413.01 06-MAR-21:40
Water Heater:WaterSystems:NaturalGas 3068.63 13443.27 27-FEB-16:20 264413.01 06-MAR-21:40
Heating:NaturalGas 2950.95 0.00 21-JAN-18:20 832360.75 12-JAN-09:10
Boiler:Heating:NaturalGas 2950.95 0.00 21-JAN-18:20 832360.75 12-JAN-09:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 867.61 0.00 01-JAN-00:30 381886.75 29-JUL-18:10
PlantLoopCoolingDemand:HVAC 867.61 0.00 01-JAN-00:30 381886.75 29-JUL-18:10
CoolingCoils:PlantLoopCoolingDemand 867.61 0.00 01-JAN-00:30 381886.75 29-JUL-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 09-MAY-20:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-08:00
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-08:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 17359.29 129409.03 04-SEP-14:00 1734220.83 12-JAN-09:10
EnergyTransfer:Building 4628.89 73375.13 05-MAR-15:00 305144.94 12-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 660.55 7491.54 12-JAN-04:00 35320.32 22-JUL-10:40
Refrigeration:EnergyTransfer 180.18 4016.66 16-NOV-23:10 10323.75 25-JUL-07:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 90.09 2008.33 16-NOV-23:10 5161.87 25-JUL-07:20
General:Refrigeration:EnergyTransfer 90.09 2008.33 16-NOV-23:10 5161.87 25-JUL-07:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 90.09 2008.33 16-NOV-23:10 5161.87 25-JUL-07:20
EnergyTransfer:Plant 5819.34 14688.34 29-SEP-00:10 916151.17 29-JUL-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.52 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 68.57 1961.84 12-JAN-04:10 2541.64 25-JUL-13:10
EnergyTransfer:Zone:BASEMENT 320.91 5164.26 05-MAR-16:00 14419.73 10-SEP-10:40
Heating:EnergyTransfer 689.61 0.00 18-MAR-17:10 168215.66 12-JAN-16:20
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 689.61 0.00 18-MAR-17:10 168215.66 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 3849.19 43821.77 12-JAN-15:00 301581.56 12-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 320.91 5164.26 05-MAR-16:00 14419.73 10-SEP-10:40
General:Cooling:EnergyTransfer 3849.19 43821.77 12-JAN-15:00 301581.56 12-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 320.91 5164.26 05-MAR-16:00 14419.73 10-SEP-10:40
EnergyTransfer:Zone:RETAIL_1_FLR_1 32.30 0.08 24-MAR-14:10 3529.05 25-AUG-13:30
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 13.18 0.00 23-JAN-12:40 2913.24 12-JAN-10:50
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 13.18 0.00 23-JAN-12:40 2913.24 12-JAN-10:50
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 19.12 0.00 01-JAN-00:10 3529.05 25-AUG-13:30
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 19.12 0.00 01-JAN-00:10 3529.05 25-AUG-13:30
EnergyTransfer:Zone:RETAIL_2_FLR_1 26.98 0.27 19-DEC-11:40 1568.98 22-JUL-10:40
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.05 0.00 01-JAN-00:10 292.20 12-JAN-10:40
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.05 0.00 01-JAN-00:10 292.20 12-JAN-10:40
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 26.93 0.00 01-JAN-13:50 1568.98 22-JUL-10:40
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 26.93 0.00 01-JAN-13:50 1568.98 22-JUL-10:40
EnergyTransfer:Zone:MECH_FLR_1 7.69 0.02 25-OCT-11:50 1171.69 21-JUL-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 4.06 0.00 01-JAN-20:10 1147.48 12-JAN-15:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 4.06 0.00 01-JAN-20:10 1147.48 12-JAN-15:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 3.63 0.00 01-JAN-00:10 1171.69 21-JUL-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 3.63 0.00 01-JAN-00:10 1171.69 21-JUL-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 15.32 0.02 21-MAR-11:10 1074.82 12-JAN-15:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 5.96 0.00 07-FEB-20:20 1074.82 12-JAN-15:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 5.96 0.00 07-FEB-20:20 1074.82 12-JAN-15:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 9.37 0.00 01-JAN-00:10 947.37 22-JUL-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 9.37 0.00 01-JAN-00:10 947.37 22-JUL-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 569.29 7025.04 12-JAN-05:00 38934.44 21-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 569.29 7025.04 12-JAN-05:00 38934.44 21-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 569.29 7025.04 12-JAN-05:00 38934.44 21-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 187.24 0.04 10-JAN-16:40 12016.30 10-AUG-15:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 3.18 0.00 01-JAN-00:10 5056.37 12-JAN-10:50
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 3.18 0.00 01-JAN-00:10 5056.37 12-JAN-10:50
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 184.06 0.00 01-JAN-11:10 12016.30 10-AUG-15:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 184.06 0.00 01-JAN-11:10 12016.30 10-AUG-15:10
EnergyTransfer:Zone:LOBBY_FLR_1 662.57 44.15 13-JAN-09:30 33596.18 23-JUL-10:40
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.06 0.00 01-JAN-00:10 2432.12 12-JAN-10:50
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.06 0.00 01-JAN-00:10 2432.12 12-JAN-10:50
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 662.51 0.00 11-JAN-10:30 33596.18 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 662.51 0.00 11-JAN-10:30 33596.18 23-JUL-10:40
EnergyTransfer:Zone:ROOM_1_FLR_3 72.69 0.00 01-JAN-08:00 9953.82 12-JAN-16:20
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 50.97 0.00 01-JAN-08:00 9953.82 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 50.97 0.00 01-JAN-08:00 9953.82 12-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 21.72 0.00 01-JAN-00:10 9371.05 16-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 21.72 0.00 01-JAN-00:10 9371.05 16-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 69.68 0.00 01-JAN-08:00 10131.73 06-JUL-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 55.55 0.00 01-JAN-08:00 10049.35 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 55.55 0.00 01-JAN-08:00 10049.35 12-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 14.13 0.00 01-JAN-00:10 10131.73 06-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 14.13 0.00 01-JAN-00:10 10131.73 06-JUL-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 289.51 0.00 07-JAN-08:40 45314.20 25-AUG-13:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 127.92 0.00 07-JAN-08:40 31450.73 12-JAN-04:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 127.92 0.00 07-JAN-08:40 31450.73 12-JAN-04:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 161.59 0.00 01-JAN-00:10 45314.20 25-AUG-13:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 161.59 0.00 01-JAN-00:10 45314.20 25-AUG-13:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 353.90 0.00 01-JAN-08:00 61258.32 10-JUL-22:10
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 172.32 0.00 01-JAN-08:00 59800.44 15-DEC-16:30
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 172.32 0.00 01-JAN-08:00 59800.44 15-DEC-16:30
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 181.58 0.00 01-JAN-00:10 61258.32 10-JUL-22:10
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 181.58 0.00 01-JAN-00:10 61258.32 10-JUL-22:10
EnergyTransfer:Zone:ROOM_5_FLR_3 74.88 0.00 01-JAN-08:00 9901.55 12-JAN-16:20
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 49.10 0.00 01-JAN-08:00 9901.55 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 49.10 0.00 01-JAN-08:00 9901.55 12-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 25.78 0.00 01-JAN-00:10 9564.98 22-JUL-08:20
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 25.78 0.00 01-JAN-00:10 9564.98 22-JUL-08:20
EnergyTransfer:Zone:ROOM_6_FLR_3 71.64 0.00 01-JAN-08:00 10338.47 11-JUL-09:00
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 53.34 0.00 01-JAN-08:00 9973.03 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 53.34 0.00 01-JAN-08:00 9973.03 12-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 18.31 0.00 01-JAN-00:10 10338.47 11-JUL-09:00
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 18.31 0.00 01-JAN-00:10 10338.47 11-JUL-09:00
EnergyTransfer:Zone:CORRIDOR_FLR_3 124.46 0.08 24-JAN-02:50 8668.20 22-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 25.24 0.00 04-JAN-21:10 8292.24 12-JAN-15:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 25.24 0.00 04-JAN-21:10 8292.24 12-JAN-15:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 99.21 0.00 01-JAN-00:10 8668.20 22-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 99.21 0.00 01-JAN-00:10 8668.20 22-JUL-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 23.06 0.00 07-JAN-08:00 3135.83 12-JAN-16:20
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 17.78 0.00 07-JAN-08:00 3135.83 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 17.78 0.00 07-JAN-08:00 3135.83 12-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 5.28 0.00 01-JAN-00:10 2549.94 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 5.28 0.00 01-JAN-00:10 2549.94 10-AUG-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 22.60 0.00 07-JAN-08:00 3140.42 12-JAN-16:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 19.20 0.00 07-JAN-08:00 3140.42 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 19.20 0.00 07-JAN-08:00 3140.42 12-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 3.41 0.00 01-JAN-00:10 2657.99 06-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 3.41 0.00 01-JAN-00:10 2657.99 06-JUL-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 104.43 0.00 01-JAN-08:00 15210.85 20-APR-15:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 62.52 0.00 01-JAN-08:00 14857.30 12-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 62.52 0.00 01-JAN-08:00 14857.30 12-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 41.91 0.00 01-JAN-00:10 15210.85 20-APR-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 41.91 0.00 01-JAN-00:10 15210.85 20-APR-15:20
EnergyTransfer:Zone:BANQUET_FLR_6 424.56 3465.14 12-JAN-14:50 20165.33 11-JUL-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 424.56 3465.14 12-JAN-14:50 20165.33 11-JUL-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 424.56 3465.14 12-JAN-14:50 20165.33 11-JUL-21:20
EnergyTransfer:Zone:DINING_FLR_6 452.19 4744.01 12-JAN-15:00 21326.61 11-JUL-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 452.19 4744.01 12-JAN-15:00 21326.61 11-JUL-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 452.19 4744.01 12-JAN-15:00 21326.61 11-JUL-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 570.47 5281.61 12-JAN-04:00 30237.51 22-JUL-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 570.47 5281.61 12-JAN-04:00 30237.51 22-JUL-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 62.42 0.07 10-FEB-20:50 6309.68 12-JAN-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 29.18 0.00 02-FEB-22:20 6309.68 12-JAN-10:40
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 29.18 0.00 02-FEB-22:20 6309.68 12-JAN-10:40
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 33.24 0.00 01-JAN-00:10 5213.60 23-JUL-13:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 33.24 0.00 01-JAN-00:10 5213.60 23-JUL-13:30
PlantLoopHeatingDemand:Facility 3632.52 12255.47 28-AUG-00:50 783679.79 12-JAN-09:10
PlantLoopHeatingDemand:Plant 971.99 12245.31 07-SEP-01:10 67263.10 01-MAR-07:10
WaterSystems:PlantLoopHeatingDemand 971.99 12245.31 07-SEP-01:10 67263.10 01-MAR-07:10
General:WaterSystems:PlantLoopHeatingDemand 971.99 12245.31 07-SEP-01:10 67263.10 01-MAR-07:10
EnergyTransfer:HVAC 6911.06 0.00 05-JUL-15:10 744914.13 12-JAN-09:10
HeatingCoils:EnergyTransfer 2660.54 0.00 19-APR-19:10 744914.13 12-JAN-09:10
PlantLoopHeatingDemand:HVAC 2660.54 0.00 19-APR-19:10 744914.13 12-JAN-09:10
HeatingCoils:PlantLoopHeatingDemand 2660.54 0.00 19-APR-19:10 744914.13 12-JAN-09:10
CoolingCoils:EnergyTransfer 867.61 0.00 01-JAN-00:30 381886.75 29-JUL-18:10
HeatRecoveryForHeating:EnergyTransfer 3381.96 0.00 03-JAN-07:40 422065.91 07-NOV-06:20
HeatRecoveryForCooling:EnergyTransfer 0.96 0.00 01-JAN-00:10 32333.42 29-JUL-16:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 971.99 12245.31 07-SEP-01:10 67263.10 01-MAR-07:10
WaterUse:WaterSystems:EnergyTransfer 971.99 12245.31 07-SEP-01:10 67263.10 01-MAR-07:10
Boilers:EnergyTransfer 2654.71 0.00 21-JAN-18:20 737002.54 12-JAN-09:10
Chillers:EnergyTransfer 909.93 0.00 01-JAN-00:30 384493.48 29-JUL-18:10
HeatRejection:EnergyTransfer 1192.63 0.00 01-JAN-00:30 489726.62 29-JUL-18:10
General:HeatRejection:EnergyTransfer 1192.63 0.00 01-JAN-00:30 489726.62 29-JUL-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -320.907 0.000 0.000 149.595 87.597 143.105 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -59.390
RETAIL_1_FLR_1 0.000 0.000 13.178 -19.119 0.000 0.000 15.527 3.964 10.186 16.378 0.000 0.006 0.000 0.000 -15.277 0.000 -9.549 -15.295
RETAIL_2_FLR_1 0.000 0.000 0.054 -26.927 0.000 0.000 18.028 4.591 11.795 0.000 0.000 0.006 0.000 0.000 0.000 0.000 -3.661 -3.887
MECH_FLR_1 0.000 0.000 4.064 -3.630 0.000 0.000 3.645 8.213 12.471 0.000 0.000 0.006 0.000 0.000 0.000 0.000 -8.941 -15.829
STORAGE_FLR_1 0.000 0.000 5.956 -9.367 0.000 0.000 3.014 1.883 3.598 0.000 0.000 0.012 0.000 0.000 0.000 0.000 -4.908 -0.187
LAUNDRY_FLR_1 0.000 0.000 0.000 -569.288 0.000 0.000 10.551 3.504 658.131 0.000 0.000 0.008 0.000 0.000 0.000 0.000 -12.989 -89.918
CAFE_FLR_1 0.000 0.000 3.177 -184.066 0.000 0.000 205.614 6.216 14.341 46.544 0.000 0.029 0.000 0.000 -42.365 0.000 -20.893 -28.597
LOBBY_FLR_1 0.000 0.000 0.056 -662.520 0.000 0.000 591.879 74.463 148.998 60.737 0.000 0.081 0.000 0.000 -57.707 0.000 -60.814 -95.175
ROOM_1_FLR_3 57.423 -17.639 0.000 -10.529 0.000 0.000 9.803 4.922 10.478 24.985 0.000 0.077 0.000 0.000 -35.420 0.000 -21.979 -22.121
ROOM_2_FLR_3 62.243 -10.003 0.000 -10.827 0.000 0.000 9.726 4.922 10.477 15.494 0.000 0.035 0.000 0.000 -37.430 0.000 -22.357 -22.281
ROOM_3_MULT19_FLR_3 127.924 -152.611 0.054 -9.034 0.000 0.000 0.000 58.777 194.997 189.463 0.000 0.008 0.000 0.000 -184.809 0.000 -116.463 -108.306
ROOM_4_MULT19_FLR_3 247.123 -111.144 0.000 -145.238 0.000 0.000 184.966 58.793 195.050 45.042 0.000 0.294 0.000 0.000 -207.702 0.000 -126.730 -140.454
ROOM_5_FLR_3 55.386 -21.503 0.000 -10.555 0.000 0.000 9.787 4.922 10.478 30.918 0.000 0.078 0.000 0.000 -34.675 0.000 -22.046 -22.791
ROOM_6_FLR_3 59.876 -14.047 0.000 -10.801 0.000 0.000 9.733 4.922 10.477 21.194 0.000 0.036 0.000 0.000 -36.407 0.000 -22.368 -22.614
CORRIDOR_FLR_3 0.000 0.000 25.244 -99.214 0.000 0.000 121.666 51.719 0.000 25.729 0.000 0.036 0.000 0.000 -44.173 0.000 -26.553 -54.454
ROOM_1_FLR_6 19.483 -4.350 0.000 -2.630 0.000 0.000 2.453 1.231 2.620 6.227 0.000 0.020 0.000 0.000 -8.788 0.000 -5.519 -10.747
ROOM_2_FLR_6 20.936 -2.434 0.000 -2.716 0.000 0.000 2.430 1.230 2.619 3.851 0.000 0.009 0.000 0.000 -9.294 0.000 -5.620 -11.012
ROOM_3_MULT9_FLR_6 72.002 -34.370 0.000 -17.020 0.000 0.000 21.983 6.962 23.098 42.744 0.000 0.136 0.000 0.000 -40.121 0.000 -26.196 -49.218
BANQUET_FLR_6 0.000 0.000 0.000 -424.561 0.000 0.000 349.935 13.704 175.857 5.252 0.000 0.024 0.000 0.000 -23.824 0.000 -13.687 -82.699
DINING_FLR_6 0.000 0.000 0.000 -452.197 0.000 0.000 344.423 13.704 175.857 5.104 0.000 0.021 0.000 0.000 -24.293 0.000 -13.829 -48.790
KITCHEN_FLR_6 0.000 0.000 0.000 -570.456 0.000 0.000 27.949 8.658 540.650 17.267 0.000 0.008 3.930 0.000 -14.726 0.000 -13.279 -0.002
CORRIDOR_FLR_6 0.000 0.000 29.183 -33.241 0.000 0.000 31.297 13.684 0.000 12.715 0.000 0.007 0.000 0.000 -19.669 0.000 -12.014 -21.962
Total Facility 722.397 -368.102 80.967 -3594.843 0.000 0.000 2124.005 438.581 2355.282 569.645 0.000 0.937 3.930 0.000 -836.678 0.000 -570.394 -925.729


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 10-SEP-10:35 0.00 0.00 0.00 -14469.77 0.00 0.00 2390.56 2387.82 4055.80 0.00 0.00 0.00 5635.59 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 25-AUG-13:30 0.00 0.00 0.00 -3529.43 0.00 0.00 150.60 90.05 252.59 5238.34 0.00 0.00 0.00 0.00 -0.00 0.00 -26.97 -2175.18
RETAIL_2_FLR_1 12-JUL-18:10 0.00 0.00 0.00 -1582.71 0.00 0.00 659.31 333.70 752.15 0.00 0.00 4.99 0.00 0.00 -0.00 0.00 0.00 -167.44
MECH_FLR_1 21-JUL-20:00 0.00 0.00 0.00 -1171.96 0.00 0.00 129.08 671.67 839.45 0.00 0.00 10.31 0.00 0.00 -0.00 0.00 0.00 -478.54
STORAGE_FLR_1 22-JUL-10:35 0.00 0.00 0.00 -950.25 0.00 0.00 48.30 42.77 89.22 0.00 0.00 10.88 759.08 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 21-JUL-20:00 0.00 0.00 0.00 -38939.36 0.00 0.00 408.82 286.55 44299.38 0.00 0.00 14.06 0.00 0.00 -0.00 0.00 0.00 -6069.46
CAFE_FLR_1 10-AUG-15:10 0.00 0.00 0.00 -12019.09 0.00 0.00 4949.69 46.91 355.63 10416.80 0.00 0.00 0.00 0.00 -0.00 0.00 -43.88 -3706.06
LOBBY_FLR_1 21-JUN-21:06 0.00 0.00 0.00 -33905.20 0.00 0.00 26569.58 4055.77 7389.94 36.01 0.00 0.00 0.00 0.00 -0.00 0.00 -34.22 -4111.90
ROOM_1_FLR_3 10-JUN-18:01 0.00 -12138.30 0.00 -734.40 0.00 0.00 283.21 378.87 484.65 6365.33 0.00 0.00 5446.96 0.00 -0.00 0.00 -86.32 0.00
ROOM_2_FLR_3 09-MAY-20:01 0.00 -12217.57 0.00 -656.30 0.00 0.00 344.42 337.15 726.90 1968.56 0.00 0.00 9800.96 0.00 -0.00 0.00 -304.11 0.00
ROOM_3_MULT19_FLR_3 25-AUG-13:30 0.00 -45313.24 0.00 0.00 0.00 0.00 0.00 1266.71 2352.88 62446.38 0.00 0.00 0.00 0.00 -0.00 0.00 -722.33 -20030.40
ROOM_4_MULT19_FLR_3 10-JUN-21:51 0.00 -68190.76 0.00 -9790.90 0.00 0.00 6244.77 3846.41 6668.31 0.00 0.00 0.00 62091.90 0.00 -306.94 0.00 -562.79 0.00
ROOM_5_FLR_3 22-JUN-18:01 0.00 -11330.91 0.00 -725.91 0.00 0.00 335.49 337.19 484.65 852.67 0.00 84.75 9962.06 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 22-JUL-08:32 0.00 -10987.48 0.00 -993.80 0.00 0.00 92.81 212.14 653.15 8180.30 0.00 0.00 3005.53 0.00 -0.00 0.00 -162.66 0.00
CORRIDOR_FLR_3 22-JUL-10:35 0.00 0.00 0.00 -8679.64 0.00 0.00 1879.30 1174.86 0.00 5796.31 0.00 24.82 0.00 0.00 -0.00 0.00 0.00 -195.65
ROOM_1_FLR_6 10-AUG-18:01 0.00 -3156.44 0.00 -184.36 0.00 0.00 83.87 84.30 121.16 1533.86 0.00 0.00 1524.70 0.00 -0.00 0.00 -7.09 0.00
ROOM_2_FLR_6 09-MAY-20:01 0.00 -3259.86 0.00 -176.61 0.00 0.00 81.27 84.29 181.72 478.02 0.00 0.00 2692.28 0.00 -0.00 0.00 -81.11 0.00
ROOM_3_MULT9_FLR_6 20-APR-15:11 0.00 -19291.91 0.00 -857.27 0.00 0.00 529.39 150.05 441.28 9849.68 0.00 0.00 9467.88 0.00 -0.00 0.00 -289.11 0.00
BANQUET_FLR_6 21-JUN-21:06 0.00 0.00 0.00 -21008.90 0.00 0.00 15972.03 539.25 6747.90 667.91 0.00 0.00 0.00 0.00 -0.00 0.00 -9.37 -2908.82
DINING_FLR_6 21-JUN-21:04 0.00 0.00 0.00 -21567.92 0.00 0.00 15684.24 539.25 6747.90 650.33 0.00 0.00 0.00 0.00 -0.00 0.00 -9.32 -2044.49
KITCHEN_FLR_6 22-JUL-10:35 0.00 0.00 0.00 -30238.31 0.00 0.00 464.20 196.69 23951.61 3886.03 0.00 0.00 1746.14 0.00 -0.00 0.00 -6.34 0.00
CORRIDOR_FLR_6 23-JUL-13:30 0.00 0.00 0.00 -5213.01 0.00 0.00 308.46 248.68 0.00 3806.05 0.00 12.74 837.08 0.00 -0.00 0.00 0.00 0.00
Total Facility 29-JUL-18:02 0.00 -142289.68 0.00 -187885.65 0.00 0.00 67555.90 28691.00 113070.18 27233.80 0.00 2244.87 91379.58 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 12-JAN-10:50 0.00 0.00 2913.18 0.00 0.00 0.00 179.01 90.05 252.59 0.00 0.00 0.00 0.00 0.00 -1549.40 0.00 -852.49 -1032.95
RETAIL_2_FLR_1 12-JAN-10:51 0.00 0.00 296.96 0.00 0.00 0.00 207.32 104.28 292.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -327.77 -573.28
MECH_FLR_1 12-JAN-15:00 0.00 0.00 1147.46 0.00 0.00 0.00 43.84 186.57 309.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -755.74 -931.41
STORAGE_FLR_1 12-JAN-15:00 0.00 0.00 1074.81 0.00 0.00 0.00 33.72 42.77 89.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -436.01 -804.51
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 12-JAN-10:50 0.00 0.00 5056.34 0.00 0.00 0.00 2351.82 213.25 355.63 0.00 0.00 0.00 0.00 0.00 -4371.02 0.00 -1884.51 -1721.50
LOBBY_FLR_1 12-JAN-10:50 0.00 0.00 2432.06 0.00 0.00 0.00 6983.06 1794.03 3694.97 0.00 0.00 0.00 0.00 0.00 -5807.59 0.00 -5384.19 -3712.35
ROOM_1_FLR_3 28-DEC-16:11 13492.38 302.81 0.00 -302.81 0.00 0.00 293.99 106.08 200.18 0.00 0.00 0.00 0.00 0.00 -2537.06 0.00 -1315.12 -10240.45
ROOM_2_FLR_3 28-DEC-16:11 12986.61 299.81 0.00 -299.81 0.00 0.00 293.99 106.07 200.16 0.00 0.00 0.00 0.00 0.00 -2529.69 0.00 -1313.73 -9743.40
ROOM_3_MULT19_FLR_3 12-JAN-04:10 31450.66 0.00 0.00 0.00 0.00 0.00 0.00 497.64 3333.24 0.00 0.00 0.00 0.00 0.00 -17844.35 0.00 -9512.96 -7924.23
ROOM_4_MULT19_FLR_3 26-NOV-16:11 73387.53 3798.83 0.00 -3798.83 0.00 0.00 3103.18 1493.31 4118.66 0.00 0.00 0.00 0.00 0.00 -14126.25 0.00 -7163.68 -60812.76
ROOM_5_FLR_3 28-DEC-16:11 13180.79 301.22 0.00 -301.22 0.00 0.00 293.99 106.08 200.18 0.00 0.00 0.00 0.00 0.00 -2525.34 0.00 -1314.43 -9941.27
ROOM_6_FLR_3 28-DEC-16:11 12677.13 298.24 0.00 -298.24 0.00 0.00 293.99 106.07 200.16 0.00 0.00 0.00 0.00 0.00 -2518.04 0.00 -1313.05 -9446.26
CORRIDOR_FLR_3 12-JAN-15:00 0.00 0.00 8292.14 0.00 0.00 0.00 1385.76 1174.86 0.00 0.00 0.00 0.00 0.00 0.00 -4225.65 0.00 -2327.49 -4299.62
ROOM_1_FLR_6 28-DEC-16:11 3883.07 75.84 0.00 -75.84 0.00 0.00 73.50 26.52 50.05 0.00 0.00 0.00 0.00 0.00 -628.70 0.00 -329.39 -3075.04
ROOM_2_FLR_6 28-DEC-16:11 3706.00 74.82 0.00 -74.82 0.00 0.00 73.50 26.52 50.04 0.00 0.00 0.00 0.00 0.00 -626.84 0.00 -328.93 -2900.29
ROOM_3_MULT9_FLR_6 28-DEC-16:11 20492.88 491.51 0.00 -491.51 0.00 0.00 661.48 150.05 441.28 0.00 0.00 0.00 0.00 0.00 -2923.76 0.00 -1517.98 -17303.95
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 12-JAN-10:40 0.00 0.00 6309.36 0.00 0.00 0.00 366.66 310.85 0.00 0.00 0.00 0.00 0.00 0.00 -1937.86 0.00 -1064.92 -3984.08
Total Facility 13-JAN-16:12 110959.52 72633.07 15299.25 -72633.07 0.00 0.00 62451.14 10092.95 73604.29 0.00 0.00 0.00 0.00 0.00 -58825.40 0.00 -34401.39 -179180.37



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 21.0941 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 20.9801 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 13.0393 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.5291 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.003540 12.5400 0.000610 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.003540 142.3000 0.000914 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.000963 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0660 2.0660 1.2809 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4048 0.4048 0.1190 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2047 0.2047 0.1376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1934 0.1934 0.0019 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0896 0.0896 0.0866 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3046 3.3046 0.0330 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6798 1.6798 1.0146 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.8247 4.8247 2.8418 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2392 1.2392 0.7125 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0398 2.0398 1.7807 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1433 2.1433 1.7811 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2222 2.2222 0.5511 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6821 0.6821 0.1883 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 21.0941 20.9801 21.0941 10.5291 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2809 1.2809 1.2809 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2024 0.2024 0.1190 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1376 0.1376 0.1376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0967 0.0967 0.0019 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0866 0.0866 0.0866 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6523 1.6523 0.0330 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0146 1.0146 1.0146 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8418 2.8418 2.8418 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7125 0.7125 0.7125 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7807 1.7807 1.7807 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7811 1.7811 1.7811 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1111 1.1111 0.5511 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3411 0.3411 0.1883 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 13.0393 10.5291 10.5291 10.5291 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 3.33
Number of hours cooling loads not met 31.33
Number of hours not met 34.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 2950.95 832360.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 282.70 105233.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 438.58 36244.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 149.24 9571.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 21.46 1269.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 366.65 22430.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.45 157.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 566.47 30214.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 51.86 4248.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 144.85 8265.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.76 3068.63 264413.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.80 1306.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 20.86 714.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1692.21 3807.20
Natural Gas 1788.84 7808.42
Additional 0.00 0.00
Total 3481.04 11615.61


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 120.77
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 38.66
Space Heating 0.00
Space Cooling 24.92
Fans (All) 49.93
Service Water Heating 8.00
Receptacle Equipment 145.30
Miscellaneous (All) 335.58
Subtotal 335.58


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 260.10
Service Water Heating 270.48
Miscellaneous (All) 688.25
Subtotal 688.25


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 3.78
Space Heating 25.41
Space Cooling 2.43
Fans (All) 4.88
Service Water Heating 27.20
Receptacle Equipment 29.59
Miscellaneous 6.72


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
PV_SCH 8760. 8760.
LTG_SCH_KITCHEN 2022. 8760.
LTG_SCH_DINING 1877. 8760.
LTG_SCH_BASEMENT 2095. 8760.
LTG_SCH_LOBBY 2166. 8760.
LTG_SCH_STORAGE 1543. 8760.
LTG_SCH_MECHANIC 2022. 8760.
LTG_SCH_LAUNDRY 2527. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2166. 8760.
LTG_SCH_RETAIL 2296. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8756.83 3.17 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8704.50 55.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8755.33 4.67 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8739.33 20.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8704.50 0.00 0.00 0.00 0.00
Max 8760.00 55.50 0.00 0.00 0.00
Average 8756.18 3.82 0.00 0.00 0.00
Sum 192636.00 84.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4153.50 0.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4142.17 11.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 11.83 0.00 0.00 0.00
Average 288886.48 0.56 0.00 0.00 0.00
Sum 6355502.67 12.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8759.33 0.67 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8746.00 14.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8612.17 147.83 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8754.50 5.50 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8738.17 21.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8754.00 6.00 0.00 0.00 0.00
DINING_FLR_6 8756.00 4.00 0.00 0.00 0.00
KITCHEN_FLR_6 8759.67 0.33 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8612.17 0.00 0.00 0.00 0.00
Max 8760.00 147.83 0.00 0.00 0.00
Average 8750.90 9.10 0.00 0.00 0.00
Sum 192519.83 200.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115175.67 253.33 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4145.50 8.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4139.50 14.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1244371.00 1344.00 0.00 0.00 0.00
DINING_FLR_6 1244819.00 896.00 0.00 0.00 0.00
KITCHEN_FLR_6 108265.33 3.67 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115175.67 1344.00 0.00 0.00 0.00
Average 288772.50 114.55 0.00 0.00 0.00
Sum 6352995.00 2520.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:54:51

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258107E+11 11476.48 06-JAN-21:00 -6.1 -6.7 0.673184E+10 4174.30 12-JAN-22:10 -36.5 -36.6
February 0.203726E+11 11135.73 01-FEB-21:00 -13.3 -13.6 0.573215E+10 4080.61 01-FEB-22:10 -12.8 -13.0
March 0.221423E+11 10816.66 22-MAR-20:00 2.80 0.30 0.632575E+10 3889.45 31-MAR-22:10 -12.6 -14.3
April 0.226749E+11 11268.54 27-APR-18:10 12.52 4.94 0.613979E+10 3924.45 21-APR-22:10 12.52 4.94
May 0.246279E+11 11799.71 31-MAY-18:10 21.13 10.92 0.638567E+10 3947.96 18-MAY-22:10 21.13 10.92
June 0.255662E+11 12484.35 29-JUN-10:35 21.83 15.68 0.631397E+10 4038.04 15-JUN-22:10 21.83 15.68
July 0.289058E+11 13867.39 23-JUL-10:35 22.23 15.22 0.688451E+10 4297.64 28-JUL-22:10 17.02 13.67
August 0.311266E+11 14355.10 26-AUG-10:35 15.93 12.30 0.736710E+10 4561.72 31-AUG-22:10 8.20 4.96
September 0.307807E+11 14469.17 10-SEP-10:35 13.87 7.59 0.735474E+10 4687.32 22-SEP-22:10 2.02 1.12
October 0.314069E+11 13895.48 06-OCT-20:00 7.80 3.77 0.763082E+10 4700.30 06-OCT-22:10 7.12 3.42
November 0.291952E+11 13358.31 01-NOV-20:00 -8.9 -9.5 0.723730E+10 4649.67 01-NOV-21:10 -8.9 -9.5
December 0.282960E+11 12689.18 01-DEC-21:00 -21.7 -22.0 0.716290E+10 4552.20 01-DEC-22:10 -21.7 -22.0
                     
Annual Sum or Average 0.320906E+12         0.812665E+11        
Minimum of Months 0.203726E+11 10816.66   -21.7 -22.0 0.573215E+10 3889.45   -36.5 -36.6
Maximum of Months 0.314069E+11 14469.17   22.23 15.68 0.763082E+10 4700.30   21.83 15.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 572176.28 163.70 23-JAN-13:30 -9.8 -10.3 0.619530E+09 364.21 26-JAN-01:10 -23.9 -24.2
February 0.111743E+09 949.70 09-FEB-11:50 -2.0 -2.3 0.560496E+09 364.24 18-FEB-05:10 -23.9 -24.3
March 0.679688E+09 1385.26 27-MAR-14:10 -5.0 -8.3 0.631484E+09 380.27 22-MAR-21:30 -5.0 -8.3
April 0.216007E+10 3067.35 22-APR-13:30 15.30 6.96 0.654141E+09 471.81 21-APR-21:19 15.30 6.96
May 0.304186E+10 3102.51 12-MAY-13:30 20.60 9.86 0.720792E+09 491.82 31-MAY-21:19 16.23 9.72
June 0.340904E+10 3047.75 30-JUN-12:30 26.15 17.75 0.753439E+09 491.85 16-JUN-21:10 26.15 17.75
July 0.359527E+10 3485.11 23-JUL-13:30 25.00 15.26 0.771796E+09 491.85 21-JUL-23:10 25.00 15.26
August 0.336559E+10 3529.05 25-AUG-13:30 21.70 14.78 0.751404E+09 491.84 01-AUG-22:10 21.70 14.78
September 0.204470E+10 2687.92 09-SEP-13:30 13.35 8.71 0.640866E+09 443.65 08-SEP-21:30 13.35 8.71
October 0.699202E+09 1777.14 03-OCT-13:30 10.85 6.24 0.624780E+09 408.20 03-OCT-21:40 7.20 3.00
November 11318184.02 793.40 08-NOV-13:30 -13.6 -14.4 0.599295E+09 364.20 08-NOV-02:39 -13.6 -14.4
December 0.00 0.00 01-DEC-00:05 -25.8 -26.0 0.619536E+09 364.26 19-DEC-01:19 -24.1 -24.3
                     
Annual Sum or Average 0.191190E+11         0.794756E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.560496E+09 364.20   -24.1 -24.3
Maximum of Months 0.359527E+10 3529.05   26.15 17.75 0.771796E+09 491.85   26.15 17.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.113922E+10 1030.82 19-JAN-21:00 -10.0 -10.4 0.718187E+09 437.58 06-JAN-23:10 -10.0 -10.4
February 0.128551E+10 1103.51 09-FEB-21:00 -8.9 -9.2 0.651687E+09 452.34 09-FEB-23:10 -10.3 -10.6
March 0.192238E+10 1202.31 22-MAR-20:00 2.80 0.30 0.733173E+09 476.47 22-MAR-22:10 1.42 -0.3
April 0.260473E+10 1422.68 21-APR-20:00 12.20 5.22 0.756707E+09 530.31 21-APR-22:10 6.83 2.10
May 0.307910E+10 1490.37 31-MAY-18:10 21.13 10.92 0.824676E+09 541.73 31-MAY-22:10 15.05 9.19
June 0.321539E+10 1577.16 21-JUN-18:10 25.40 14.16 0.836596E+09 561.93 21-JUN-22:10 21.32 13.04
July 0.333890E+10 1582.66 12-JUL-18:10 24.13 13.81 0.860687E+09 560.20 12-JUL-22:10 17.70 10.91
August 0.323044E+10 1551.81 02-AUG-18:10 22.70 14.49 0.853011E+09 558.55 11-AUG-22:10 19.90 13.18
September 0.270245E+10 1387.47 10-SEP-10:35 13.87 7.59 0.764784E+09 517.95 01-SEP-22:10 13.87 7.59
October 0.218489E+10 1265.34 03-OCT-20:00 6.10 2.72 0.742722E+09 493.78 03-OCT-22:10 7.30 3.10
November 0.122182E+10 1057.78 01-NOV-20:00 -8.9 -9.5 0.695223E+09 443.69 01-NOV-22:10 -9.0 -9.5
December 0.100205E+10 997.13 19-DEC-21:00 -6.1 -7.0 0.717624E+09 431.59 19-DEC-23:10 -8.7 -9.2
                     
Annual Sum or Average 0.269269E+11         0.915508E+10        
Minimum of Months 0.100205E+10 997.13   -10.0 -10.4 0.651687E+09 431.59   -10.3 -10.6
Maximum of Months 0.333890E+10 1582.66   25.40 14.49 0.860687E+09 561.93   21.32 13.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4782624.97 15.62 19-JAN-21:00 -10.0 -10.4 0.152309E+09 95.22 19-JAN-22:10 -9.9 -10.2
February 9273052.10 17.31 09-FEB-21:00 -8.9 -9.2 0.139107E+09 101.41 09-FEB-22:10 -9.6 -9.9
March 22249342.62 19.78 22-MAR-20:00 2.80 0.30 0.158906E+09 110.86 22-MAR-21:10 2.12 0.08
April 60779612.82 386.64 21-APR-20:00 12.20 5.22 0.176457E+09 120.45 26-APR-21:19 2.23 -0.9
May 0.363876E+09 821.87 31-MAY-21:00 16.70 9.87 0.203146E+09 120.45 16-MAY-21:10 16.70 9.87
June 0.100039E+10 1143.27 21-JUN-21:00 23.90 13.75 0.199164E+09 120.46 02-JUN-22:10 23.90 13.75
July 0.114060E+10 1171.69 21-JUL-20:00 25.00 16.11 0.204962E+09 120.46 21-JUL-23:10 19.72 15.53
August 0.836912E+09 1091.58 11-AUG-20:00 24.40 14.81 0.205587E+09 120.45 03-AUG-21:00 24.40 14.81
September 0.144754E+09 527.28 01-SEP-21:00 11.10 8.75 0.191129E+09 120.45 01-SEP-23:10 9.32 8.15
October 37956643.48 145.45 06-OCT-21:00 7.80 3.59 0.173204E+09 120.45 06-OCT-21:19 7.60 3.54
November 5833764.88 16.15 03-NOV-20:00 -6.1 -7.8 0.147503E+09 97.36 03-NOV-21:10 -6.6 -8.2
December 2941373.84 15.11 19-DEC-21:00 -6.1 -7.0 0.152024E+09 93.14 19-DEC-22:10 -8.3 -8.9
                     
Annual Sum or Average 0.363034E+10         0.210350E+10        
Minimum of Months 2941373.84 15.11   -10.0 -10.4 0.139107E+09 93.14   -9.9 -10.2
Maximum of Months 0.114060E+10 1171.69   25.00 16.11 0.205587E+09 120.46   24.40 15.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 0.116689E+09 68.58 26-JAN-01:19 -23.9 -24.2
February 2000187.97 119.12 08-FEB-22:00 1.10 -1.7 0.105501E+09 68.58 21-FEB-00:30 -24.1 -24.4
March 39888195.80 383.59 22-MAR-21:00 2.20 0.09 0.117238E+09 68.59 16-MAR-03:20 2.20 0.09
April 0.702829E+09 737.03 22-APR-17:15 13.87 6.05 0.113244E+09 71.09 21-APR-21:49 13.87 6.05
May 0.160749E+10 857.73 14-MAY-10:35 16.83 8.94 0.119876E+09 75.29 31-MAY-22:10 15.05 9.19
June 0.179290E+10 901.92 22-JUN-10:35 21.33 12.72 0.123132E+09 79.50 22-JUN-22:10 19.22 11.60
July 0.187903E+10 950.18 22-JUL-10:35 23.67 16.46 0.127535E+09 79.84 11-JUL-21:49 23.67 16.46
August 0.178014E+10 881.75 05-AUG-10:35 19.40 13.45 0.125087E+09 78.38 11-AUG-22:10 19.90 13.18
September 0.120293E+10 747.40 03-SEP-10:35 9.63 7.11 0.113709E+09 71.88 01-SEP-22:10 9.63 7.11
October 0.360252E+09 627.58 06-OCT-21:00 7.80 3.59 0.116749E+09 69.08 03-OCT-22:10 7.80 3.59
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 0.112878E+09 68.58 16-NOV-23:40 -23.9 -24.1
December 0.00 0.00 01-DEC-00:05 -25.8 -26.0 0.116689E+09 68.58 19-DEC-01:19 -24.1 -24.3
                     
Annual Sum or Average 0.936746E+10         0.140832E+10        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.105501E+09 68.58   -24.1 -24.4
Maximum of Months 0.187903E+10 950.18   23.67 16.46 0.127535E+09 79.84   23.67 16.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.452485E+11 36393.54 19-JAN-21:00 -10.0 -10.4 0.649340E+09 381.60 03-JAN-22:19 -10.0 -10.4
February 0.413905E+11 36832.66 08-FEB-21:00 -1.1 -2.8 0.587075E+09 381.59 18-FEB-05:40 -22.6 -23.0
March 0.471234E+11 37443.56 22-MAR-20:00 2.80 0.30 0.652393E+09 381.56 21-MAR-21:19 2.80 0.30
April 0.473176E+11 38134.55 21-APR-20:00 12.20 5.22 0.629503E+09 381.60 06-APR-21:00 12.20 5.22
May 0.507152E+11 38583.10 31-MAY-20:00 17.20 10.12 0.650708E+09 381.58 17-MAY-21:10 17.20 10.12
June 0.499636E+11 38852.32 29-JUN-20:00 25.00 16.66 0.630874E+09 381.71 30-JUN-23:00 15.10 14.10
July 0.515431E+11 38934.44 21-JUL-20:00 25.00 16.11 0.649335E+09 381.71 01-JUL-00:10 25.00 16.11
August 0.512746E+11 38798.72 11-AUG-20:00 24.40 14.81 0.652084E+09 381.61 01-AUG-00:49 24.40 14.81
September 0.480131E+11 38059.17 01-SEP-20:00 12.20 9.06 0.629194E+09 381.58 28-SEP-22:10 -0.7 -2.1
October 0.478364E+11 37660.11 03-OCT-20:00 6.10 2.72 0.649645E+09 381.58 15-OCT-23:10 -0.7 -1.1
November 0.440225E+11 36500.66 01-NOV-20:00 -8.9 -9.5 0.628127E+09 381.57 07-NOV-23:49 -23.0 -23.3
December 0.448374E+11 36219.38 19-DEC-21:00 -6.1 -7.0 0.649340E+09 381.59 07-DEC-22:19 -6.1 -7.0
                     
Annual Sum or Average 0.569286E+12         0.765762E+10        
Minimum of Months 0.413905E+11 36219.38   -10.0 -10.4 0.587075E+09 381.56   -23.0 -23.3
Maximum of Months 0.515431E+11 38934.44   25.00 16.66 0.652393E+09 381.71   25.00 16.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.643815E+10 6807.70 06-JAN-23:10 -3.0 -4.1 0.814387E+10 4851.99 06-JAN-23:10 -3.0 -4.1
February 0.833612E+10 7289.75 08-FEB-22:00 1.10 -1.7 0.737964E+10 5060.18 08-FEB-22:40 -0.4 -2.4
March 0.142435E+11 8977.71 27-MAR-15:40 -4.6 -8.0 0.833570E+10 5444.61 22-MAR-21:40 -4.6 -8.0
April 0.190605E+11 11339.79 21-APR-15:25 14.15 5.54 0.860812E+10 5998.34 21-APR-21:40 8.13 2.71
May 0.220779E+11 11264.24 09-MAY-15:30 17.50 8.02 0.920866E+10 6122.78 31-MAY-21:40 15.77 9.56
June 0.226833E+11 11366.72 20-JUN-15:23 25.30 14.65 0.924606E+10 6250.25 29-JUN-21:40 22.97 16.37
July 0.235471E+11 11941.31 23-JUL-10:35 22.23 15.22 0.950229E+10 6316.10 21-JUL-21:40 22.23 15.22
August 0.227996E+11 12016.30 10-AUG-15:10 22.30 12.06 0.945876E+10 6327.84 11-AUG-21:40 20.93 13.61
September 0.184695E+11 10995.80 10-SEP-10:35 13.87 7.59 0.857313E+10 5822.63 07-SEP-21:40 13.87 7.59
October 0.141444E+11 9010.88 03-OCT-15:12 12.43 6.74 0.837610E+10 5642.30 03-OCT-22:10 7.30 3.10
November 0.676491E+10 6886.47 01-NOV-22:10 -9.0 -9.5 0.787859E+10 4889.02 01-NOV-22:10 -9.0 -9.5
December 0.549864E+10 6389.25 19-DEC-22:30 -8.3 -8.9 0.814375E+10 4788.31 19-DEC-01:39 -8.3 -8.9
                     
Annual Sum or Average 0.184064E+12         0.102855E+12        
Minimum of Months 0.549864E+10 6389.25   -9.0 -9.5 0.737964E+10 4788.31   -9.0 -9.5
Maximum of Months 0.235471E+11 12016.30   25.30 15.22 0.950229E+10 6327.84   22.97 16.37



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.380788E+11 23244.23 06-JAN-22:00 -3.9 -4.8 0.249891E+11 16195.29 06-JAN-23:10 -3.0 -4.1
February 0.396866E+11 24674.11 08-FEB-22:00 1.10 -1.7 0.228741E+11 16665.13 08-FEB-23:10 -0.6 -2.4
March 0.521475E+11 26836.98 22-MAR-20:00 2.80 0.30 0.262214E+11 17500.20 22-MAR-22:10 1.42 -0.3
April 0.602591E+11 30300.48 22-APR-10:35 11.87 5.55 0.271810E+11 18817.40 21-APR-21:49 11.87 5.55
May 0.682120E+11 31749.98 14-MAY-10:35 16.83 8.94 0.293759E+11 19186.03 31-MAY-22:10 15.05 9.19
June 0.696950E+11 33907.65 21-JUN-21:06 23.53 13.66 0.293785E+11 19186.31 07-JUN-22:10 23.53 13.66
July 0.724713E+11 33790.14 23-JUL-10:35 22.23 15.22 0.302445E+11 19186.30 10-JUL-22:10 22.23 15.22
August 0.707507E+11 33285.06 25-AUG-21:10 18.25 13.61 0.301659E+11 19186.23 01-AUG-22:10 18.25 13.61
September 0.616857E+11 30626.89 10-SEP-10:35 13.87 7.59 0.275833E+11 18600.17 01-SEP-22:10 13.87 7.59
October 0.547485E+11 28120.70 03-OCT-20:00 6.10 2.72 0.267911E+11 18074.50 03-OCT-22:10 7.30 3.10
November 0.390201E+11 23797.29 01-NOV-21:00 -8.9 -9.5 0.242865E+11 16366.39 01-NOV-22:10 -9.0 -9.5
December 0.357594E+11 22767.23 19-DEC-21:00 -6.1 -7.0 0.247555E+11 15943.09 19-DEC-23:10 -8.7 -9.2
                     
Annual Sum or Average 0.662515E+12         0.323847E+12        
Minimum of Months 0.357594E+11 22767.23   -8.9 -9.5 0.228741E+11 15943.09   -9.0 -9.5
Maximum of Months 0.724713E+11 33907.65   23.53 15.22 0.302445E+11 19186.31   23.53 15.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1455456.21 882.30 19-JAN-09:04 -5.5 -6.1 91899297.32 56.69 19-JAN-00:20 -5.5 -6.1
February 4057676.04 1019.48 10-FEB-19:04 -3.1 -4.0 83088731.16 56.69 05-FEB-00:20 -3.1 -4.0
March 22031618.46 2818.56 22-MAR-15:12 5.60 2.35 93213778.72 56.69 23-MAR-23:19 -4.8 -6.2
April 0.397697E+09 3156.33 21-APR-18:01 14.22 5.92 93636784.30 56.69 21-APR-22:10 6.83 2.10
May 0.873428E+09 3176.17 10-MAY-18:01 18.30 8.81 98630259.52 56.69 30-MAY-21:30 17.50 9.63
June 0.144183E+10 3218.21 10-JUN-18:01 21.60 11.25 95998389.96 56.69 30-JUN-21:49 17.82 14.24
July 0.141571E+10 2821.46 22-JUL-08:61 19.27 14.68 99073432.17 56.69 19-JUL-21:49 19.27 14.68
August 0.104077E+10 3120.90 31-AUG-15:11 14.27 5.23 98781413.20 56.69 01-AUG-21:00 14.27 5.23
September 0.215307E+09 3111.86 07-SEP-15:11 16.47 8.91 93182721.04 56.69 01-SEP-01:10 16.47 8.91
October 14526795.72 1992.71 03-OCT-15:12 12.43 6.74 93102165.90 56.69 01-OCT-03:09 12.43 6.74
November 2114048.17 836.21 04-NOV-08:04 -8.3 -9.8 88979024.99 56.69 18-NOV-03:49 -4.8 -6.3
December 733758.25 785.40 26-DEC-09:04 -7.9 -8.5 91820708.14 56.69 23-DEC-04:00 -7.9 -8.5
                     
Annual Sum or Average 0.542967E+10         0.112141E+10        
Minimum of Months 733758.25 785.40   -8.3 -9.8 83088731.16 56.69   -7.9 -8.5
Maximum of Months 0.144183E+10 3218.21   21.60 14.68 99073432.17 56.69   19.27 14.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 726281.68 751.56 23-JAN-09:04 -11.7 -12.3 91897058.00 56.69 19-JAN-00:20 -11.7 -12.3
February 2040810.25 1046.34 08-FEB-19:04 0.22 -1.6 83027639.61 56.69 14-FEB-00:20 -13.7 -14.0
March 6417463.50 1167.03 20-MAR-15:13 6.33 2.12 92454394.29 56.69 05-MAR-00:20 6.33 2.12
April 0.211264E+09 2877.93 21-APR-18:01 14.22 5.92 92161244.43 56.69 21-APR-21:19 9.07 3.11
May 0.543257E+09 3218.46 09-MAY-20:01 13.35 5.95 0.101083E+09 79.89 10-MAY-21:10 14.13 6.05
June 0.102229E+10 2898.28 28-JUN-21:51 18.30 14.88 0.104575E+09 92.13 19-JUN-21:10 18.30 14.88
July 0.100796E+10 2825.03 06-JUL-21:51 18.90 13.76 0.106047E+09 83.10 11-JUL-21:30 21.10 13.07
August 0.630604E+09 2839.55 30-AUG-18:01 8.80 3.00 0.103691E+09 80.13 10-AUG-21:30 8.80 3.00
September 98463853.84 2825.76 07-SEP-18:01 14.13 7.59 92331782.47 56.69 02-SEP-23:19 14.13 7.59
October 8930943.08 1262.32 02-OCT-15:13 8.30 6.09 92598421.15 56.69 31-OCT-23:19 -10.3 -11.2
November 1028257.10 825.23 04-NOV-08:04 -8.3 -9.8 88976503.96 56.69 07-NOV-00:20 -13.9 -14.2
December 467207.47 878.10 26-DEC-09:04 -7.9 -8.5 91820849.24 56.69 16-DEC-00:20 -7.9 -8.5
                     
Annual Sum or Average 0.353344E+10         0.114066E+10        
Minimum of Months 467207.47 751.56   -11.7 -12.3 83027639.61 56.69   -13.9 -14.2
Maximum of Months 0.102229E+10 3218.46   18.90 14.88 0.106047E+09 92.13   21.10 14.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 0.00 0.00 01-JAN-00:10 -14.9 -15.4
February 801433.43 40.19 15-FEB-15:20 -7.2 -8.6 0.00 0.00 01-FEB-00:10 -7.2 -8.6
March 5638261.17 106.92 31-MAR-14:20 -10.7 -12.8 0.00 0.00 01-MAR-00:10 -10.7 -12.8
April 0.199897E+09 534.86 22-APR-13:30 15.30 6.96 0.00 0.00 01-APR-00:10 15.30 6.96
May 0.366747E+09 526.16 12-MAY-13:30 20.60 9.86 0.00 0.00 01-MAY-00:10 20.60 9.86
June 0.456972E+09 478.69 30-JUN-12:30 26.15 17.75 0.00 0.00 01-JUN-00:10 26.15 17.75
July 0.483605E+09 568.56 23-JUL-13:30 25.00 15.26 0.00 0.00 01-JUL-00:10 25.00 15.26
August 0.431328E+09 596.24 25-AUG-13:30 21.70 14.78 0.00 0.00 01-AUG-00:10 21.70 14.78
September 0.164730E+09 490.77 09-SEP-13:20 13.17 8.67 0.00 0.00 01-SEP-00:10 13.17 8.67
October 16401096.37 268.62 03-OCT-13:30 10.85 6.24 0.00 0.00 01-OCT-00:10 10.85 6.24
November 65399.39 20.98 08-NOV-15:20 -14.6 -15.2 0.00 0.00 01-NOV-00:10 -14.6 -15.2
December 0.00 0.00 01-DEC-00:05 -25.8 -26.0 0.00 0.00 01-DEC-00:10 -25.8 -26.0
                     
Annual Sum or Average 0.212619E+10         0.00        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.00 0.00   -25.8 -26.0
Maximum of Months 0.483605E+09 596.24   26.15 17.75 0.00 0.00   26.15 17.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1969878.04 477.97 20-JAN-19:04 -13.1 -13.2 92855531.02 56.69 16-JAN-00:30 -13.1 -13.2
February 4110073.84 476.34 08-FEB-16:14 1.67 -1.0 84107827.70 56.69 20-FEB-00:30 -18.3 -18.9
March 15259744.04 813.70 18-MAR-08:61 -1.7 -3.2 94027169.72 56.69 22-MAR-21:19 2.03 0.07
April 0.131957E+09 925.71 30-APR-18:01 9.72 3.97 92722753.45 56.69 28-APR-21:00 9.72 3.97
May 0.399518E+09 985.14 14-MAY-20:41 13.68 7.57 99087926.64 71.69 31-MAY-21:00 15.30 9.39
June 0.559806E+09 1026.07 10-JUN-21:51 19.40 11.22 0.100134E+09 76.72 19-JUN-21:10 21.23 12.32
July 0.575243E+09 953.71 19-JUL-21:51 19.40 14.19 0.103439E+09 75.92 10-JUL-21:40 19.40 14.19
August 0.436444E+09 989.88 10-AUG-21:51 16.10 9.68 0.101510E+09 73.79 04-AUG-21:10 16.10 9.68
September 0.208127E+09 916.92 10-SEP-18:01 15.32 9.12 93385965.64 56.69 19-SEP-21:10 11.60 7.66
October 53426015.99 868.51 09-OCT-08:61 -1.6 -2.1 94603402.98 56.69 04-OCT-21:19 -1.6 -2.1
November 1966741.04 463.57 06-NOV-19:04 -10.6 -11.3 89908083.27 56.69 11-NOV-00:20 -20.0 -20.3
December 1369439.55 446.62 24-DEC-09:01 0.18 -1.3 92693895.63 56.69 07-DEC-22:30 0.18 -1.3
                     
Annual Sum or Average 0.238920E+10         0.113848E+10        
Minimum of Months 1369439.55 446.62   -13.1 -13.2 84107827.70 56.69   -20.0 -20.3
Maximum of Months 0.575243E+09 1026.07   19.40 14.19 0.103439E+09 76.72   21.23 14.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1090860.54 736.67 19-JAN-09:04 -5.5 -6.1 91902651.81 56.69 19-JAN-00:20 -5.5 -6.1
February 4919949.31 995.02 08-FEB-19:04 0.22 -1.6 83166839.44 56.69 02-FEB-04:30 0.22 -1.6
March 29956000.26 2732.66 22-MAR-15:12 5.60 2.35 94053347.13 56.69 07-MAR-00:20 5.60 2.35
April 0.355212E+09 2968.26 22-APR-08:61 5.55 1.86 94178920.22 56.69 27-APR-21:19 7.07 3.28
May 0.119742E+10 3009.14 13-MAY-15:11 20.00 9.32 99174142.76 56.69 31-MAY-21:10 16.47 9.79
June 0.161502E+10 3014.22 22-JUN-18:01 23.22 12.45 96200056.72 56.69 30-JUN-21:49 17.82 14.24
July 0.170128E+10 2667.03 24-JUL-18:02 21.60 16.12 99316251.03 56.69 24-JUL-21:00 18.90 14.80
August 0.122413E+10 3012.66 10-AUG-18:01 22.62 12.07 99187070.98 56.69 25-AUG-21:49 15.65 12.71
September 0.287065E+09 2939.37 07-SEP-15:11 16.47 8.91 93878579.81 56.69 01-SEP-01:10 16.47 8.91
October 25708171.73 2674.74 04-OCT-08:62 7.88 2.97 93506421.92 56.69 18-OCT-23:19 -3.9 -4.1
November 1604708.98 789.43 04-NOV-08:04 -8.3 -9.8 88982657.59 56.69 18-NOV-04:19 -4.3 -5.8
December 581581.70 835.97 26-DEC-09:04 -7.9 -8.5 91821219.04 56.69 16-DEC-00:20 -7.9 -8.5
                     
Annual Sum or Average 0.644399E+10         0.112537E+10        
Minimum of Months 581581.70 736.67   -8.3 -9.8 83166839.44 56.69   -7.9 -8.5
Maximum of Months 0.170128E+10 3014.22   23.22 16.12 99316251.03 56.69   18.90 14.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 452383.36 796.88 23-JAN-09:04 -11.7 -12.3 91898987.32 56.69 14-JAN-00:20 -11.7 -12.3
February 2219866.54 1104.82 08-FEB-19:04 0.22 -1.6 83050224.79 56.69 09-FEB-00:20 1.70 0.15
March 12017016.37 1267.38 18-MAR-08:03 -1.7 -3.2 92929003.17 56.69 05-MAR-00:20 -1.7 -3.2
April 0.162828E+09 2722.54 22-APR-08:61 5.55 1.86 92730776.91 56.69 28-APR-21:19 3.17 1.58
May 0.868925E+09 2794.77 14-MAY-20:41 13.68 7.57 0.100929E+09 73.10 12-MAY-21:10 13.68 7.57
June 0.125129E+10 2780.25 29-JUN-08:51 18.90 14.54 0.102053E+09 76.99 22-JUN-21:30 18.90 14.54
July 0.128514E+10 2995.31 22-JUL-08:32 20.37 15.09 0.105720E+09 78.59 07-JUL-21:19 20.37 15.09
August 0.829177E+09 2722.74 31-AUG-08:61 2.48 -0.9 0.103017E+09 75.19 02-AUG-21:19 2.48 -0.9
September 0.152082E+09 2603.95 10-SEP-15:11 15.40 8.69 93053921.70 56.69 01-SEP-01:10 15.40 8.69
October 11943867.49 1845.64 04-OCT-08:62 7.88 2.97 92924900.65 56.69 31-OCT-23:19 -10.3 -11.2
November 703564.43 880.54 04-NOV-08:04 -8.3 -9.8 88978238.59 56.69 04-NOV-23:19 -12.1 -13.1
December 321458.45 863.23 26-DEC-09:04 -7.9 -8.5 91821171.73 56.69 01-DEC-03:09 -7.9 -8.5
                     
Annual Sum or Average 0.457710E+10         0.113911E+10        
Minimum of Months 321458.45 796.88   -11.7 -12.3 83050224.79 56.69   -12.1 -13.1
Maximum of Months 0.128514E+10 2995.31   20.37 15.09 0.105720E+09 78.59   20.37 15.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 50584390.89 419.58 06-JAN-23:00 -2.8 -3.9 0.119882E+10 704.47 12-JAN-04:10 -37.3 -37.4
February 0.191039E+09 772.84 08-FEB-22:05 0.73 -1.8 0.108387E+10 704.50 18-FEB-05:19 -23.5 -23.8
March 0.911985E+09 1313.32 22-MAR-21:00 2.20 0.09 0.120454E+10 714.47 22-MAR-21:49 1.78 0.04
April 0.274228E+10 1790.75 22-APR-10:35 11.87 5.55 0.119909E+10 786.23 21-APR-21:40 11.87 5.55
May 0.392989E+10 1992.70 14-MAY-10:35 16.83 8.94 0.134449E+10 845.51 12-MAY-21:40 16.83 8.94
June 0.423379E+10 2085.86 13-JUN-10:35 21.83 12.30 0.139617E+10 899.39 22-JUN-21:49 19.60 11.77
July 0.439013E+10 2169.81 22-JUL-10:35 23.67 16.46 0.143540E+10 896.90 12-JUL-21:49 23.67 16.46
August 0.411755E+10 2025.45 02-AUG-18:10 22.70 14.49 0.139013E+10 881.32 02-AUG-21:49 19.60 14.29
September 0.294827E+10 1755.88 10-SEP-10:35 13.87 7.59 0.120123E+10 793.79 01-SEP-21:49 13.87 7.59
October 0.121849E+10 1404.56 03-OCT-20:00 6.10 2.72 0.120046E+10 724.63 03-OCT-22:10 7.30 3.10
November 52925550.73 497.26 01-NOV-21:05 -8.9 -9.5 0.115966E+10 704.48 08-NOV-03:09 -24.3 -24.6
December 16409456.34 408.21 24-DEC-23:00 -3.3 -3.7 0.119883E+10 704.48 22-DEC-00:40 -3.3 -3.7
                     
Annual Sum or Average 0.248033E+11         0.150127E+11        
Minimum of Months 16409456.34 408.21   -8.9 -9.5 0.108387E+10 704.47   -37.3 -37.4
Maximum of Months 0.439013E+10 2169.81   23.67 16.46 0.143540E+10 899.39   23.67 16.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 219902.48 497.43 22-JAN-09:04 -6.2 -6.5 91879557.06 56.69 04-JAN-00:20 -6.2 -6.5
February 1466222.28 799.17 09-FEB-09:04 -2.2 -2.5 83006794.38 56.69 23-FEB-00:20 -22.8 -23.0
March 12951074.66 2443.51 22-MAR-15:12 5.60 2.35 92734634.57 56.69 05-MAR-00:20 5.60 2.35
April 0.395940E+09 3274.04 21-APR-18:01 14.22 5.92 93196990.51 56.69 27-APR-21:10 7.43 3.48
May 0.834665E+09 3291.70 30-MAY-15:11 19.47 10.27 98460396.33 56.70 12-MAY-01:49 19.47 10.27
June 0.143464E+10 3332.60 10-JUN-18:01 21.60 11.25 95906915.08 56.70 19-JUN-04:19 7.07 6.43
July 0.140844E+10 2875.39 15-JUL-18:01 18.72 15.22 98983927.05 56.69 07-JUL-21:30 18.72 15.22
August 0.993106E+09 3340.84 10-AUG-18:01 22.62 12.07 98606585.12 56.70 23-AUG-04:19 11.50 10.88
September 0.186165E+09 3219.70 07-SEP-15:11 16.47 8.91 92701906.64 56.69 07-SEP-22:40 9.60 6.04
October 10449155.39 2024.28 03-OCT-15:12 12.43 6.74 92644490.39 56.69 27-OCT-23:19 -11.1 -12.1
November 223561.41 363.11 04-NOV-08:04 -8.3 -9.8 88965249.69 56.69 03-NOV-23:19 -8.3 -9.8
December 197422.29 788.76 24-DEC-09:04 0.18 -1.3 91805332.27 56.69 01-DEC-03:49 0.18 -1.3
                     
Annual Sum or Average 0.527846E+10         0.111889E+10        
Minimum of Months 197422.29 363.11   -8.3 -9.8 83006794.38 56.69   -22.8 -23.0
Maximum of Months 0.143464E+10 3340.84   22.62 15.22 98983927.05 56.70   19.47 15.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 200720.77 371.72 21-JAN-09:04 -6.9 -7.3 91880070.13 56.69 04-JAN-04:10 -6.9 -7.3
February 910399.48 809.41 09-FEB-09:04 -2.2 -2.5 82997335.16 56.69 18-FEB-05:49 -22.1 -22.6
March 4383216.42 1264.04 20-MAR-15:13 6.33 2.12 92255287.81 56.69 03-MAR-00:20 6.33 2.12
April 0.202319E+09 2957.04 21-APR-18:01 14.22 5.92 91754937.13 56.69 21-APR-21:19 9.07 3.11
May 0.486019E+09 3436.47 09-MAY-20:01 13.35 5.95 0.101401E+09 86.29 10-MAY-21:10 14.13 6.05
June 0.103631E+10 3092.20 26-JUN-21:51 19.40 13.93 0.105779E+09 100.48 28-JUN-21:10 19.72 14.76
July 0.101430E+10 3013.47 06-JUL-21:51 18.90 13.76 0.106876E+09 86.34 06-JUL-21:10 18.90 13.76
August 0.582577E+09 2908.56 30-AUG-18:01 8.80 3.00 0.104303E+09 90.23 10-AUG-21:10 8.80 3.00
September 74573942.43 2896.74 07-SEP-18:01 14.13 7.59 91795243.98 56.69 07-SEP-21:19 10.40 5.70
October 7142656.66 1424.32 04-OCT-15:13 10.73 4.73 92259588.04 56.69 24-OCT-04:10 -4.4 -4.6
November 266054.19 475.06 04-NOV-08:04 -8.3 -9.8 88965337.65 56.69 11-NOV-00:20 -20.0 -20.3
December 173378.92 431.07 24-DEC-09:04 0.18 -1.3 91804317.21 56.69 16-DEC-00:20 0.18 -1.3
                     
Annual Sum or Average 0.340918E+10         0.114207E+10        
Minimum of Months 173378.92 371.72   -8.3 -9.8 82997335.16 56.69   -22.1 -22.6
Maximum of Months 0.103631E+10 3436.47   19.40 13.93 0.106876E+09 100.48   19.72 14.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1735097.62 580.61 22-JAN-19:04 -6.7 -7.0 91960881.58 56.69 16-JAN-00:30 -6.7 -7.0
February 7710302.30 2049.76 15-FEB-16:11 -7.4 -8.8 84057113.59 56.69 23-FEB-00:20 -22.8 -23.0
March 0.105946E+09 2189.60 27-MAR-15:11 -4.8 -8.1 95608505.36 56.69 22-MAR-21:19 -4.8 -8.1
April 0.479267E+09 2238.85 20-APR-15:11 13.70 6.18 94867215.75 56.69 19-APR-22:10 13.70 6.18
May 0.750259E+09 2238.65 13-MAY-15:11 20.00 9.32 98936870.29 56.69 31-MAY-21:19 16.23 9.72
June 0.963268E+09 2222.85 22-JUN-18:01 23.22 12.45 96006304.65 56.70 30-JUN-21:10 18.68 15.18
July 0.103086E+10 1992.53 24-JUL-18:02 21.60 16.12 99127192.30 56.69 06-JUL-21:30 21.60 16.12
August 0.888657E+09 2229.39 10-AUG-18:01 22.62 12.07 99040570.15 56.70 25-AUG-21:00 15.00 12.45
September 0.354683E+09 2172.53 30-SEP-15:12 2.97 -0.7 94432433.96 56.69 07-SEP-21:49 2.97 -0.7
October 70721089.76 2181.25 13-OCT-15:11 1.70 -2.0 94616704.87 56.69 04-OCT-21:19 1.70 -2.0
November 2892500.31 505.08 01-NOV-18:04 -8.9 -9.7 89137004.72 56.69 11-NOV-00:20 -20.0 -20.3
December 682067.27 601.22 24-DEC-19:04 -4.0 -4.2 91846250.08 56.69 17-DEC-00:20 -4.0 -4.2
                     
Annual Sum or Average 0.465668E+10         0.112964E+10        
Minimum of Months 682067.27 505.08   -8.9 -9.7 84057113.59 56.69   -22.8 -23.0
Maximum of Months 0.103086E+10 2238.85   23.22 16.12 99127192.30 56.70   21.60 16.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.292404E+11 15660.92 06-JAN-23:10 -3.0 -4.1 0.152274E+11 10162.38 06-JAN-23:49 -3.7 -4.7
February 0.274014E+11 16114.81 08-FEB-23:10 -0.6 -2.4 0.138624E+11 10400.28 08-FEB-23:00 1.70 -0.3
March 0.328190E+11 16604.15 22-MAR-22:10 1.42 -0.3 0.157104E+11 10599.38 22-MAR-22:49 0.28 -1.2
April 0.360034E+11 17730.03 21-APR-20:30 11.10 4.35 0.157953E+11 10990.92 21-APR-21:40 8.13 2.71
May 0.414804E+11 19123.63 31-MAY-18:10 21.13 10.92 0.171615E+11 11348.81 31-MAY-22:10 15.05 9.19
June 0.425927E+11 21013.58 21-JUN-21:06 23.53 13.66 0.171576E+11 11349.24 28-JUN-22:10 18.12 14.78
July 0.439964E+11 20165.33 11-JUL-21:20 21.47 13.22 0.175844E+11 11349.18 11-JUL-22:10 19.27 12.35
August 0.423547E+11 19536.95 02-AUG-18:10 22.70 14.49 0.174118E+11 11349.13 01-AUG-22:10 22.70 14.49
September 0.372666E+11 17714.11 01-SEP-21:00 11.10 8.75 0.160705E+11 11044.48 01-SEP-22:49 9.50 8.24
October 0.343886E+11 16925.76 06-OCT-22:10 7.12 3.42 0.159407E+11 10755.09 06-OCT-22:49 6.78 3.36
November 0.283982E+11 15667.35 03-NOV-22:10 -6.3 -8.0 0.147266E+11 10171.19 03-NOV-22:49 -7.0 -8.6
December 0.286164E+11 15360.57 19-DEC-23:10 -8.7 -9.2 0.151241E+11 10017.21 19-DEC-23:49 -10.2 -10.3
                     
Annual Sum or Average 0.424558E+12         0.191773E+12        
Minimum of Months 0.274014E+11 15360.57   -8.7 -9.2 0.138624E+11 10017.21   -10.2 -10.3
Maximum of Months 0.439964E+11 21013.58   23.53 14.49 0.175844E+11 11349.24   22.70 14.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.320851E+11 16452.17 06-JAN-23:10 -3.0 -4.1 0.156600E+11 10531.22 06-JAN-23:49 -3.7 -4.7
February 0.299526E+11 16930.98 08-FEB-23:10 -0.6 -2.4 0.142718E+11 10784.85 09-FEB-00:10 1.70 -0.1
March 0.355852E+11 17425.35 22-MAR-22:10 1.42 -0.3 0.162271E+11 10989.59 22-MAR-22:49 0.28 -1.2
April 0.382629E+11 18420.96 21-APR-20:30 11.10 4.35 0.163345E+11 11310.06 21-APR-22:10 6.83 2.10
May 0.432827E+11 20487.04 31-MAY-21:10 16.47 9.79 0.176342E+11 11349.19 10-MAY-21:40 16.47 9.79
June 0.441908E+11 21573.25 21-JUN-21:04 23.53 13.66 0.175335E+11 11349.24 28-JUN-22:10 18.12 14.78
July 0.456213E+11 21326.61 11-JUL-21:20 21.47 13.22 0.179738E+11 11349.18 11-JUL-22:10 19.27 12.35
August 0.440324E+11 20983.52 02-AUG-21:10 20.40 14.60 0.178262E+11 11349.13 01-AUG-22:10 20.40 14.60
September 0.394242E+11 18416.49 01-SEP-21:00 11.10 8.75 0.166307E+11 11344.22 01-SEP-23:10 9.32 8.15
October 0.371473E+11 17814.62 06-OCT-21:00 7.80 3.59 0.165072E+11 11169.44 06-OCT-22:49 6.78 3.36
November 0.311416E+11 16465.70 03-NOV-22:10 -6.3 -8.0 0.151506E+11 10543.77 03-NOV-22:49 -7.0 -8.6
December 0.314677E+11 16130.05 19-DEC-23:10 -8.7 -9.2 0.155351E+11 10372.91 19-DEC-23:49 -10.2 -10.3
                     
Annual Sum or Average 0.452194E+12         0.197285E+12        
Minimum of Months 0.299526E+11 16130.05   -8.7 -9.2 0.142718E+11 10372.91   -10.2 -10.3
Maximum of Months 0.456213E+11 21573.25   23.53 14.60 0.179738E+11 11349.24   20.40 14.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.423270E+11 24019.82 22-JAN-11:50 -6.6 -6.9 0.188677E+11 11319.72 14-JAN-18:10 -6.6 -6.9
February 0.394123E+11 25061.13 09-FEB-11:50 -2.0 -2.3 0.170435E+11 11319.71 25-FEB-18:10 -23.0 -23.5
March 0.462391E+11 26789.66 22-MAR-10:50 2.62 0.57 0.188760E+11 11319.66 04-MAR-18:10 2.62 0.57
April 0.481922E+11 28630.30 22-APR-10:50 12.33 5.78 0.182622E+11 11319.65 22-APR-17:10 14.13 6.18
May 0.533551E+11 29079.75 14-MAY-10:50 17.02 9.05 0.188716E+11 11319.57 20-MAY-17:10 13.30 6.40
June 0.532819E+11 29543.66 29-JUN-10:40 21.83 15.68 0.182659E+11 11319.67 10-JUN-17:10 21.83 15.68
July 0.551647E+11 30247.17 22-JUL-10:40 23.67 16.46 0.188681E+11 11319.66 29-JUL-17:10 29.53 18.36
August 0.537882E+11 29255.19 26-AUG-10:50 16.32 12.46 0.188753E+11 11319.66 26-AUG-17:10 21.02 13.58
September 0.489105E+11 28323.43 10-SEP-10:50 14.13 7.69 0.182614E+11 11319.58 02-SEP-17:10 14.13 7.69
October 0.469828E+11 26704.87 03-OCT-10:35 5.37 3.67 0.188688E+11 11319.61 28-OCT-17:10 -8.9 -9.3
November 0.411067E+11 23757.87 01-NOV-18:03 -8.9 -9.7 0.182586E+11 11319.69 25-NOV-18:10 -21.0 -21.2
December 0.417057E+11 24230.01 24-DEC-11:50 1.60 -0.2 0.188679E+11 11319.71 02-DEC-18:10 1.60 -0.2
                     
Annual Sum or Average 0.570466E+12         0.222187E+12        
Minimum of Months 0.394123E+11 23757.87   -8.9 -9.7 0.170435E+11 11319.57   -23.0 -23.5
Maximum of Months 0.551647E+11 30247.17   23.67 16.46 0.188760E+11 11319.72   29.53 18.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9 -15.4 0.126882E+10 745.70 26-JAN-01:49 -23.9 -24.2
February 40448338.18 1001.65 09-FEB-13:30 -0.3 -1.5 0.114715E+10 745.67 21-FEB-00:30 -24.1 -24.4
March 0.706052E+09 1618.59 22-MAR-10:40 2.43 0.50 0.127705E+10 786.03 22-MAR-22:10 1.42 -0.3
April 0.320726E+10 2189.31 22-APR-10:50 12.33 5.78 0.133788E+10 934.96 21-APR-21:30 12.33 5.78
May 0.505135E+10 3865.68 13-MAY-13:20 19.07 8.91 0.159925E+10 1007.40 11-MAY-21:40 19.07 8.91
June 0.657637E+10 4948.57 20-JUN-15:13 25.20 14.61 0.164953E+10 1007.43 02-JUN-22:10 25.20 14.61
July 0.685945E+10 5213.60 23-JUL-13:30 25.00 15.26 0.169581E+10 1007.43 01-JUL-00:10 25.00 15.26
August 0.568959E+10 4217.72 02-AUG-15:10 22.38 14.56 0.165721E+10 1007.41 01-AUG-01:10 22.38 14.56
September 0.377330E+10 2152.25 10-SEP-10:35 13.87 7.59 0.137387E+10 926.51 01-SEP-21:49 13.87 7.59
October 0.133681E+10 1624.80 03-OCT-10:50 5.73 3.91 0.128072E+10 809.91 03-OCT-22:10 7.30 3.10
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 0.122737E+10 745.68 08-NOV-02:39 -24.2 -24.5
December 0.00 0.00 01-DEC-00:05 -25.8 -26.0 0.126883E+10 745.68 19-DEC-03:20 -24.8 -25.0
                     
Annual Sum or Average 0.332406E+11         0.167835E+11        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.114715E+10 745.67   -24.8 -25.0
Maximum of Months 0.685945E+10 5213.60   25.20 15.26 0.169581E+10 1007.43   25.20 15.26



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:05 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.328642E+10 2913.24 12-JAN-10:50 -37.4
February 0.184067E+10 2196.93 27-FEB-08:63 -34.3
March 0.743299E+09 1944.84 01-MAR-08:10 -28.1
April 76367690.95 913.03 03-APR-06:05 -21.5
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 4444274.30 305.89 30-SEP-06:55 -5.0
October 0.524016E+09 1373.14 27-OCT-08:20 -18.5
November 0.283113E+10 2393.35 29-NOV-10:20 -29.4
December 0.387204E+10 2676.20 15-DEC-10:53 -33.3
         
Annual Sum or Average 0.131784E+11      
Minimum of Months 0.00 0.00   -37.4
Maximum of Months 0.387204E+10 2913.24   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 18911087.78 296.96 12-JAN-10:51 -37.2
February 2128605.26 115.24 27-FEB-10:51 -33.3
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 4794959.88 143.30 29-NOV-10:30 -29.1
December 28625122.61 235.78 15-DEC-10:53 -33.3
         
Annual Sum or Average 54459775.52      
Minimum of Months 0.00 0.00   -37.2
Maximum of Months 28625122.61 296.96   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100641E+10 1147.48 12-JAN-15:00 -36.1
February 0.699161E+09 986.82 27-FEB-05:00 -36.1
March 0.285412E+09 851.91 01-MAR-05:00 -28.3
April 10514251.09 243.78 03-APR-04:00 -21.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 49384895.21 337.32 31-OCT-09:53 -16.7
November 0.816508E+09 888.91 30-NOV-11:10 -28.6
December 0.119685E+10 1014.02 15-DEC-14:00 -32.2
         
Annual Sum or Average 0.406425E+10      
Minimum of Months 0.00 0.00   -36.1
Maximum of Months 0.119685E+10 1147.48   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134568E+10 1074.82 12-JAN-15:00 -36.1
February 0.100381E+10 899.66 27-FEB-05:00 -36.1
March 0.616470E+09 774.69 01-MAR-08:10 -28.1
April 76287883.20 392.54 03-APR-07:03 -20.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.228523E+09 469.80 27-OCT-09:10 -19.5
November 0.119400E+10 873.54 30-NOV-10:53 -28.9
December 0.149170E+10 979.27 15-DEC-12:30 -33.0
         
Annual Sum or Average 0.595648E+10      
Minimum of Months 0.00 0.00   -36.1
Maximum of Months 0.149170E+10 1074.82   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:05 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.985628E+09 5056.37 12-JAN-10:50 -37.4
February 0.107496E+09 1976.94 27-FEB-15:00 -28.3
March 4187862.61 879.92 01-MAR-08:63 -28.1
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 6331088.92 1082.67 30-OCT-08:40 -16.7
November 0.548132E+09 3676.60 29-NOV-10:10 -29.7
December 0.152519E+10 4502.68 15-DEC-11:02 -33.3
         
Annual Sum or Average 0.317697E+10      
Minimum of Months 0.00 0.00   -37.4
Maximum of Months 0.152519E+10 5056.37   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 38927277.84 2432.12 12-JAN-10:50 -37.4
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 17570790.29 1532.27 15-DEC-15:00 -30.6
         
Annual Sum or Average 56498068.13      
Minimum of Months 0.00 0.00   -37.4
Maximum of Months 38927277.84 2432.12   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.263327E+10 3367.82 29-JAN-16:11 -22.2
February 0.191636E+10 3353.03 25-FEB-16:11 -21.9
March 0.130816E+10 3327.18 01-MAR-19:01 -19.7
April 0.314991E+09 3311.96 03-APR-08:61 -17.1
May 17567026.01 1146.50 10-MAY-08:03 10.87
June 2352038.61 1079.13 21-JUN-08:04 14.78
July 2500797.08 1188.53 26-JUL-18:04 18.85
August 8632051.27 1143.53 31-AUG-18:04 14.22
September 0.196104E+09 3229.56 27-SEP-15:11 3.50
October 0.105959E+10 3332.88 30-OCT-08:61 -16.7
November 0.240723E+10 3367.78 26-NOV-16:11 -22.6
December 0.287657E+10 3373.11 28-DEC-16:11 -21.3
         
Annual Sum or Average 0.127433E+11      
Minimum of Months 2352038.61 1079.13   -22.6
Maximum of Months 0.287657E+10 3373.11   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.270561E+10 3243.58 29-JAN-16:11 -22.2
February 0.213731E+10 3232.97 25-FEB-16:11 -21.9
March 0.163243E+10 3221.15 03-MAR-09:01 -21.0
April 0.447573E+09 3195.88 03-APR-08:61 -17.1
May 23373023.66 1242.43 19-MAY-15:14 13.50
June 1157251.96 1018.05 06-JUN-08:04 11.28
July 1615801.64 1012.73 04-JUL-18:04 12.12
August 11877892.87 1695.68 31-AUG-08:61 2.48
September 0.265038E+09 3142.40 29-SEP-15:11 2.40
October 0.123291E+10 3213.26 31-OCT-15:11 -11.5
November 0.252834E+10 3245.67 26-NOV-16:11 -22.6
December 0.289956E+10 3246.67 28-DEC-16:11 -21.3
         
Annual Sum or Average 0.138868E+11      
Minimum of Months 1157251.96 1012.73   -22.6
Maximum of Months 0.289956E+10 3246.67   13.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.476878E+09 413.83 12-JAN-04:10 -37.3
February 0.196247E+09 321.63 27-FEB-05:00 -36.1
March 24456182.33 291.18 01-MAR-05:00 -28.3
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 12009.17 20.02 30-SEP-17:50 2.30
October 14512735.28 161.91 30-OCT-04:00 -14.4
November 0.385137E+09 331.64 29-NOV-05:00 -28.9
December 0.585939E+09 384.88 15-DEC-05:00 -33.3
         
Annual Sum or Average 0.168318E+10      
Minimum of Months 0.00 0.00   -37.3
Maximum of Months 0.585939E+09 413.83   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.483947E+09 964.62 14-JAN-16:11 -18.7
February 0.370687E+09 964.08 28-FEB-16:11 -22.6
March 0.249111E+09 962.31 04-MAR-16:11 -12.4
April 42375720.19 934.40 02-APR-15:11 -6.9
May 560088.21 380.59 02-MAY-15:14 11.87
June 35209.01 102.44 25-JUN-15:16 12.77
July 58320.54 153.89 16-JUL-16:36 15.73
August 176806.05 159.22 30-AUG-08:05 2.07
September 4147553.65 900.83 29-SEP-15:11 2.40
October 0.125414E+09 960.81 31-OCT-15:11 -11.5
November 0.452014E+09 965.63 26-NOV-16:11 -22.6
December 0.538803E+09 965.03 28-DEC-16:11 -21.3
         
Annual Sum or Average 0.226733E+10      
Minimum of Months 35209.01 102.44   -22.6
Maximum of Months 0.538803E+09 965.63   15.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.260926E+10 3289.70 29-JAN-16:11 -22.2
February 0.182452E+10 3277.67 25-FEB-16:11 -21.9
March 0.112058E+10 3248.69 01-MAR-19:01 -19.7
April 0.308660E+09 3210.47 04-APR-08:61 -8.0
May 11753881.49 1118.92 03-MAY-15:14 12.97
June 1202207.97 1025.36 24-JUN-15:14 12.60
July 1238230.66 1092.78 01-JUL-18:04 13.80
August 6169932.25 1170.04 30-AUG-18:04 8.80
September 0.159881E+09 3155.61 27-SEP-15:11 3.50
October 0.958231E+09 3256.51 30-OCT-08:61 -16.7
November 0.240264E+10 3290.84 26-NOV-16:11 -22.6
December 0.287172E+10 3295.21 28-DEC-16:11 -21.3
         
Annual Sum or Average 0.122759E+11      
Minimum of Months 1202207.97 1025.36   -22.6
Maximum of Months 0.287172E+10 3295.21   13.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.267908E+10 3165.96 29-JAN-16:11 -22.2
February 0.203477E+10 3159.21 25-FEB-16:11 -21.9
March 0.140276E+10 3139.88 01-MAR-19:01 -19.7
April 0.444476E+09 3102.76 03-APR-08:61 -17.1
May 16056993.13 1172.15 17-MAY-18:04 14.82
June 737381.12 881.38 28-JUN-08:05 11.97
July 872321.39 939.20 04-JUL-18:04 12.12
August 7979460.03 994.13 29-AUG-15:14 15.40
September 0.215861E+09 3063.98 27-SEP-15:11 3.50
October 0.111316E+10 3136.21 27-OCT-08:61 -18.2
November 0.252407E+10 3168.99 26-NOV-16:11 -22.6
December 0.289410E+10 3169.30 28-DEC-16:11 -21.3
         
Annual Sum or Average 0.133339E+11      
Minimum of Months 737381.12 881.38   -22.6
Maximum of Months 0.289410E+10 3169.30   15.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.167788E+10 2073.06 12-JAN-15:00 -36.1
February 0.835652E+09 1478.68 27-FEB-15:00 -28.3
March 0.174022E+09 1107.35 01-MAR-08:63 -28.1
April 8180318.66 438.17 03-APR-08:03 -17.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.173637E+09 942.00 27-OCT-08:20 -18.5
November 0.138450E+10 1661.21 29-NOV-10:20 -29.4
December 0.205721E+10 2012.10 15-DEC-14:50 -30.9
         
Annual Sum or Average 0.631108E+10      
Minimum of Months 0.00 0.00   -36.1
Maximum of Months 0.205721E+10 2073.06   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355217E+10 3874.85 10-JAN-16:11 -23.5
February 0.265514E+10 3855.61 25-FEB-16:11 -21.9
March 0.188587E+10 3826.84 01-MAR-19:01 -19.7
April 0.525214E+09 3800.09 03-APR-08:61 -17.1
May 53525580.34 1837.81 27-MAY-08:62 0.68
June 2472873.17 1121.93 21-JUN-08:04 14.78
July 3127039.18 1131.44 26-JUL-18:04 18.85
August 24446251.45 2652.97 30-AUG-08:62 2.07
September 0.373215E+09 3752.36 27-SEP-15:11 3.50
October 0.157131E+10 3831.08 27-OCT-08:61 -18.2
November 0.329076E+10 3876.55 26-NOV-16:11 -22.6
December 0.384348E+10 3883.09 28-DEC-16:11 -21.3
         
Annual Sum or Average 0.177807E+11      
Minimum of Months 2472873.17 1121.93   -23.5
Maximum of Months 0.384348E+10 3883.09   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.363226E+10 3700.32 29-JAN-16:11 -22.2
February 0.290404E+10 3687.98 25-FEB-16:11 -21.9
March 0.228092E+10 3673.21 03-MAR-09:01 -21.0
April 0.714732E+09 3639.59 03-APR-08:61 -17.1
May 65900794.39 1983.06 27-MAY-08:62 0.68
June 1423521.68 938.35 19-JUN-08:04 14.18
July 1873644.90 940.19 04-JUL-18:04 12.12
August 30459267.47 3451.63 31-AUG-08:61 2.48
September 0.485812E+09 3592.89 29-SEP-18:01 1.02
October 0.178232E+10 3663.22 31-OCT-15:11 -11.5
November 0.342723E+10 3704.47 26-NOV-16:11 -22.6
December 0.386838E+10 3706.02 28-DEC-16:11 -21.3
         
Annual Sum or Average 0.191954E+11      
Minimum of Months 1423521.68 938.35   -22.6
Maximum of Months 0.386838E+10 3706.02   14.18



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158110E+10 2270.80 14-JAN-16:11 -18.7
February 0.977595E+09 2250.59 01-FEB-16:11 -12.2
March 0.545718E+09 2226.76 13-MAR-08:61 -23.0
April 0.107021E+09 2218.54 03-APR-08:61 -17.1
May 5822466.31 781.14 27-MAY-18:03 7.52
June 1431814.43 645.94 24-JUN-15:14 12.60
July 1495358.50 723.92 04-JUL-15:14 12.80
August 2811944.69 594.12 29-AUG-15:14 15.40
September 53570518.73 2081.25 27-SEP-15:11 3.50
October 0.469818E+09 2235.66 25-OCT-15:11 -10.0
November 0.140082E+10 2265.82 26-NOV-16:11 -22.6
December 0.179971E+10 2277.01 28-DEC-16:11 -21.3
         
Annual Sum or Average 0.694692E+10      
Minimum of Months 1431814.43 594.12   -23.0
Maximum of Months 0.179971E+10 2277.01   15.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:05 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:05 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:05 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:05 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.702493E+10 6309.68 12-JAN-10:40 -37.6
February 0.442937E+10 5068.67 27-FEB-07:10 -34.9
March 0.184103E+10 4438.90 01-MAR-08:10 -28.1
April 0.186089E+09 2325.96 03-APR-06:10 -21.5
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:10 16.35
September 2139288.14 272.74 30-SEP-06:57 -5.0
October 0.105609E+10 2873.91 27-OCT-08:20 -18.5
November 0.650711E+10 5237.08 29-NOV-10:20 -29.4
December 0.813610E+10 5670.21 15-DEC-10:53 -33.3
         
Annual Sum or Average 0.291829E+11      
Minimum of Months 0.00 0.00   -37.6
Maximum of Months 0.813610E+10 6309.68   16.35



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.743717E+10 7163.56 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.671509E+10 7163.56 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.746010E+10 7163.56 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.718502E+10 7163.56 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.745007E+10 7163.56 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.721797E+10 7163.56 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.741712E+10 7163.56 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.746297E+10 7163.56 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.718788E+10 7163.56 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.743431E+10 7163.56 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.721224E+10 7163.56 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.741712E+10 7163.56 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.875971E+11     0.143105E+12    
Minimum of Months 0.671509E+10 7163.56   0.109726E+11 9632.53  
Maximum of Months 0.746297E+10 7163.56   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.336569E+09 324.19 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.303891E+09 324.19 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.337607E+09 324.19 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.325158E+09 324.19 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.337153E+09 324.19 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.326649E+09 324.19 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.335662E+09 324.19 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.337736E+09 324.19 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.325288E+09 324.19 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.336440E+09 324.19 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.326390E+09 324.19 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.335662E+09 324.19 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.396421E+10     0.101856E+11    
Minimum of Months 0.303891E+09 324.19   0.780982E+09 685.60  
Maximum of Months 0.337736E+09 324.19   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.389749E+09 375.41 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.351908E+09 375.41 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.390950E+09 375.41 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.376534E+09 375.41 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.390424E+09 375.41 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.378261E+09 375.41 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.388697E+09 375.41 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.391100E+09 375.41 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.376684E+09 375.41 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.389598E+09 375.41 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.377961E+09 375.41 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.388697E+09 375.41 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.459056E+10     0.117950E+11    
Minimum of Months 0.351908E+09 375.41   0.904380E+09 793.93  
Maximum of Months 0.391100E+09 375.41   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.697327E+09 671.67 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.629623E+09 671.67 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.699476E+09 671.67 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.673684E+09 671.67 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.698536E+09 671.67 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.676774E+09 671.67 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.695446E+09 671.67 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.699745E+09 671.67 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.673953E+09 671.67 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.697058E+09 671.67 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.676237E+09 671.67 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.695446E+09 671.67 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.821331E+10     0.124712E+11    
Minimum of Months 0.629623E+09 671.67   0.956227E+09 839.45  
Maximum of Months 0.699745E+09 671.67   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.159843E+09 153.96 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.144324E+09 153.96 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.160336E+09 153.96 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.154423E+09 153.96 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.160120E+09 153.96 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.155132E+09 153.96 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.159412E+09 153.96 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.160397E+09 153.96 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.154485E+09 153.96 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.159781E+09 153.96 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.155009E+09 153.96 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.159412E+09 153.96 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.188267E+10     0.359760E+10    
Minimum of Months 0.144324E+09 153.96   0.275845E+09 242.16  
Maximum of Months 0.160397E+09 153.96   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.297499E+09 286.55 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.268614E+09 286.55 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.298416E+09 286.55 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.287412E+09 286.55 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.298015E+09 286.55 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.288730E+09 286.55 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.296696E+09 286.55 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.298530E+09 286.55 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.287527E+09 286.55 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.297384E+09 286.55 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.288501E+09 286.55 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.296696E+09 286.55 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.350402E+10     0.679355E+11    
Minimum of Months 0.268614E+09 286.55   0.520895E+10 4572.80  
Maximum of Months 0.298530E+09 286.55   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.733909E+09 767.68 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.592371E+09 767.68 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.566253E+09 767.68 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.394419E+09 767.68 03-APR-19:40 0.117692E+10 965.27 03-APR-19:10
May 0.346296E+09 682.39 04-MAY-20:30 0.121917E+10 965.27 01-MAY-19:10
June 0.282446E+09 584.00 02-JUN-20:00 0.118076E+10 965.27 01-JUN-19:10
July 0.314422E+09 610.24 28-JUL-20:00 0.121533E+10 965.27 03-JUL-19:10
August 0.402831E+09 767.68 29-AUG-19:30 0.122063E+10 965.27 01-AUG-19:10
September 0.508925E+09 767.68 01-SEP-19:30 0.117729E+10 965.27 01-SEP-19:10
October 0.629968E+09 767.68 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.679016E+09 767.68 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.765509E+09 767.68 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.621637E+10     0.143405E+11    
Minimum of Months 0.282446E+09 584.00   0.109956E+10 965.27  
Maximum of Months 0.765509E+09 767.68   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.661997E+10 6458.51 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.586846E+10 6458.51 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.638632E+10 6458.51 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.594212E+10 6458.51 03-APR-19:40 0.122282E+11 10029.21 03-APR-19:10
May 0.607441E+10 6303.31 02-MAY-19:00 0.126672E+11 10029.21 01-MAY-19:10
June 0.580802E+10 6176.68 02-JUN-19:00 0.122682E+11 10029.21 01-JUN-19:10
July 0.600741E+10 6140.00 28-JUL-19:00 0.126273E+11 10029.21 03-JUL-19:10
August 0.616691E+10 6458.51 29-AUG-19:30 0.126824E+11 10029.21 01-AUG-19:10
September 0.610638E+10 6458.51 01-SEP-19:30 0.122320E+11 10029.21 01-SEP-19:10
October 0.645976E+10 6458.51 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.637059E+10 6458.51 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.665283E+10 6458.51 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.744632E+11     0.148998E+12    
Minimum of Months 0.580802E+10 6140.00   0.114244E+11 10029.21  
Maximum of Months 0.665283E+10 6458.51   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65789991.58 59.53 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 59414784.75 59.53 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 65267117.48 59.53 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 63743496.62 59.53 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 65528554.53 59.53 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 63237765.93 59.53 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 66042856.93 59.53 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 65267117.48 59.53 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 63760640.03 59.53 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 65781419.88 59.53 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 63490631.27 59.53 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 66051428.64 59.53 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.773376E+09     0.256575E+10    
Minimum of Months 59414784.75 59.53   0.196843E+09 232.19  
Maximum of Months 66051428.64 59.53   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.109776E+10 1057.37 02-JAN-20:10 0.00 0.00
February 0.991179E+09 1057.37 01-FEB-20:10 0.00 0.00
March 0.110115E+10 1057.37 01-MAR-20:10 0.00 0.00
April 0.106054E+10 1057.37 03-APR-19:10 0.00 0.00
May 0.109967E+10 1057.37 01-MAY-19:10 0.00 0.00
June 0.106541E+10 1057.37 01-JUN-19:10 0.00 0.00
July 0.109480E+10 1057.37 03-JUL-19:10 0.00 0.00
August 0.110157E+10 1057.37 01-AUG-19:10 0.00 0.00
September 0.106097E+10 1057.37 01-SEP-19:10 0.00 0.00
October 0.109734E+10 1057.37 02-OCT-19:10 0.00 0.00
November 0.106456E+10 1057.37 01-NOV-19:10 0.00 0.00
December 0.109480E+10 1057.37 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.129297E+11     0.00 0.00
Minimum of Months 0.991179E+09 1057.37   0.00 0.00
Maximum of Months 0.110157E+10 1057.37   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104684E+09 94.72 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 94540036.54 94.72 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.103852E+09 94.72 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.101428E+09 94.72 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.104268E+09 94.72 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.100623E+09 94.72 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.105087E+09 94.72 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.103852E+09 94.72 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.101455E+09 94.72 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.104671E+09 94.72 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.101025E+09 94.72 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.105100E+09 94.72 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.123059E+10     0.261953E+10    
Minimum of Months 94540036.54 94.72   0.200969E+09 237.06  
Maximum of Months 0.105100E+09 94.72   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104672E+09 94.71 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 94528959.80 94.71 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.103840E+09 94.71 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.101416E+09 94.71 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.104256E+09 94.71 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.100611E+09 94.71 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.105074E+09 94.71 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.103840E+09 94.71 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.101443E+09 94.71 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.104658E+09 94.71 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.101014E+09 94.71 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.105088E+09 94.71 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.123044E+10     0.261922E+10    
Minimum of Months 94528959.80 94.71   0.200945E+09 237.03  
Maximum of Months 0.105088E+09 94.71   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 65807981.74 59.54 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 59431031.62 59.54 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 65284964.65 59.54 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 63760927.16 59.54 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 65546473.20 59.54 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 63255058.18 59.54 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 66060916.23 59.54 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 65284964.65 59.54 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 63778075.26 59.54 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 65799407.69 59.54 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 63507992.67 59.54 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 66069490.28 59.54 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.773587E+09     0.256645E+10    
Minimum of Months 59431031.62 59.54   0.196897E+09 232.26  
Maximum of Months 66069490.28 59.54   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.136884E+10 1348.12 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.117196E+10 1348.12 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.120959E+10 1348.12 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.101116E+10 1348.12 03-APR-19:40 0.144540E+11 6747.90 01-APR-06:10
May 0.971794E+09 1198.33 04-MAY-20:30 0.149358E+11 6747.90 01-MAY-06:10
June 0.893470E+09 1117.45 02-JUN-19:00 0.144540E+11 6747.90 01-JUN-06:10
July 0.944222E+09 1136.84 26-JUL-20:00 0.149358E+11 6747.90 01-JUL-06:10
August 0.104142E+10 1348.12 29-AUG-19:30 0.149358E+11 6747.90 01-AUG-06:10
September 0.113200E+10 1348.12 01-SEP-19:30 0.144540E+11 6747.90 01-SEP-06:10
October 0.126798E+10 1348.12 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.130480E+10 1348.12 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.138639E+10 1348.12 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.137036E+11     0.175857E+12    
Minimum of Months 0.893470E+09 1117.45   0.134904E+11 6747.90  
Maximum of Months 0.138639E+10 1348.12   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.136884E+10 1348.12 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.117196E+10 1348.12 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.120959E+10 1348.12 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.101116E+10 1348.12 03-APR-19:40 0.144540E+11 6747.90 01-APR-06:10
May 0.971794E+09 1198.33 04-MAY-20:30 0.149358E+11 6747.90 01-MAY-06:10
June 0.893470E+09 1117.45 02-JUN-19:00 0.144540E+11 6747.90 01-JUN-06:10
July 0.944222E+09 1136.84 26-JUL-20:00 0.149358E+11 6747.90 01-JUL-06:10
August 0.104142E+10 1348.12 29-AUG-19:30 0.149358E+11 6747.90 01-AUG-06:10
September 0.113200E+10 1348.12 01-SEP-19:30 0.144540E+11 6747.90 01-SEP-06:10
October 0.126798E+10 1348.12 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.130480E+10 1348.12 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.138639E+10 1348.12 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.137036E+11     0.175857E+12    
Minimum of Months 0.893470E+09 1117.45   0.134904E+11 6747.90  
Maximum of Months 0.138639E+10 1348.12   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.735117E+09 708.07 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.663744E+09 708.07 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.737383E+09 708.07 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.710193E+09 708.07 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.736392E+09 708.07 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.713450E+09 708.07 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.733135E+09 708.07 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.737666E+09 708.07 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.710477E+09 708.07 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.734834E+09 708.07 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.712884E+09 708.07 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.733135E+09 708.07 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.865841E+10     0.424019E+12    
Minimum of Months 0.663744E+09 708.07   0.325275E+11 16179.04  
Maximum of Months 0.737666E+09 708.07   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.116181E+10 1119.06 02-JAN-20:10 0.00 0.00
February 0.104901E+10 1119.06 01-FEB-20:10 0.00 0.00
March 0.116539E+10 1119.06 01-MAR-20:10 0.00 0.00
April 0.112242E+10 1119.06 03-APR-19:10 0.00 0.00
May 0.116383E+10 1119.06 01-MAY-19:10 0.00 0.00
June 0.112757E+10 1119.06 01-JUN-19:10 0.00 0.00
July 0.115868E+10 1119.06 03-JUL-19:10 0.00 0.00
August 0.116584E+10 1119.06 01-AUG-19:10 0.00 0.00
September 0.112287E+10 1119.06 01-SEP-19:10 0.00 0.00
October 0.116136E+10 1119.06 02-OCT-19:10 0.00 0.00
November 0.112667E+10 1119.06 01-NOV-19:10 0.00 0.00
December 0.115868E+10 1119.06 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.136841E+11     0.00 0.00
Minimum of Months 0.104901E+10 1119.06   0.00 0.00
Maximum of Months 0.116584E+10 1119.06   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.743717E+10 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.671509E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.746010E+10 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.718502E+10 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.745007E+10 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.721797E+10 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.741712E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.746297E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.718788E+10 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.743431E+10 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.721224E+10 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.741712E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.875971E+11 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.671509E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.746297E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.336569E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.137922E+10
February 0.179968E+10 0.303891E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.117872E+10
March 0.199990E+10 0.337607E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.110720E+10
April 0.192973E+10 0.325158E+09 0.835931E+09 0.00 0.00 0.00 0.00 0.00 0.689517E+09
May 0.199475E+10 0.337153E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.00 0.388055E+09
June 0.193394E+10 0.326649E+09 0.838659E+09 0.00 0.00 0.00 0.00 1755311.54 0.227433E+09
July 0.199054E+10 0.335662E+09 0.863211E+09 0.00 0.00 0.00 0.00 4088246.55 0.206397E+09
August 0.199896E+10 0.337736E+09 0.866978E+09 0.00 0.00 0.00 0.00 439968.87 0.280686E+09
September 0.192879E+10 0.325288E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.00 0.475786E+09
October 0.199148E+10 0.336440E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.826247E+09
November 0.192552E+10 0.326390E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.133943E+10
December 0.199054E+10 0.335662E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.144987E+10
                   
Annual Sum or Average 0.234744E+11 0.396421E+10 0.101856E+11 0.00 0.00 0.00 0.00 6283526.96 0.954856E+10
Minimum of Months 0.179968E+10 0.303891E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.206397E+09
Maximum of Months 0.199990E+10 0.337736E+09 0.866978E+09 0.00 0.00 0.00 0.00 4088246.55 0.144987E+10



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.389749E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.532469E+09
February 0.208403E+10 0.351908E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.455149E+09
March 0.231589E+10 0.390950E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.425622E+09
April 0.223463E+10 0.376534E+09 0.968011E+09 0.00 0.00 0.00 0.00 0.00 0.262275E+09
May 0.230993E+10 0.390424E+09 0.100276E+10 0.00 0.00 0.00 0.00 0.00 0.144567E+09
June 0.223950E+10 0.378261E+09 0.971170E+09 0.00 0.00 0.00 0.00 1573266.06 80895356.86
July 0.230505E+10 0.388697E+09 0.999601E+09 0.00 0.00 0.00 0.00 3650161.38 74390455.15
August 0.231480E+10 0.391100E+09 0.100396E+10 0.00 0.00 0.00 0.00 675927.05 0.103608E+09
September 0.223354E+10 0.376684E+09 0.968312E+09 0.00 0.00 0.00 0.00 0.00 0.184308E+09
October 0.230614E+10 0.389598E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 0.320411E+09
November 0.222975E+10 0.377961E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.517160E+09
December 0.230505E+10 0.388697E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.559673E+09
                   
Annual Sum or Average 0.271834E+11 0.459056E+10 0.117950E+11 0.00 0.00 0.00 0.00 5899354.48 0.366053E+10
Minimum of Months 0.208403E+10 0.351908E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 74390455.15
Maximum of Months 0.231589E+10 0.391100E+09 0.100396E+10 0.00 0.00 0.00 0.00 3650161.38 0.559673E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.697327E+09 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.125905E+10
February 0.440737E+09 0.629623E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.107779E+10
March 0.489771E+09 0.699476E+09 0.106120E+10 0.00 0.00 0.00 0.00 0.00 0.101273E+10
April 0.472586E+09 0.673684E+09 0.102351E+10 0.00 0.00 0.00 0.00 0.00 0.649744E+09
May 0.488511E+09 0.698536E+09 0.106025E+10 0.00 0.00 0.00 0.00 0.00 0.392687E+09
June 0.473617E+09 0.676774E+09 0.102685E+10 0.00 0.00 0.00 0.00 1600980.36 0.228979E+09
July 0.487480E+09 0.695446E+09 0.105691E+10 0.00 0.00 0.00 0.00 3727242.37 0.211736E+09
August 0.489542E+09 0.699745E+09 0.106152E+10 0.00 0.00 0.00 0.00 401232.58 0.288913E+09
September 0.472357E+09 0.673953E+09 0.102382E+10 0.00 0.00 0.00 0.00 0.00 0.487365E+09
October 0.487709E+09 0.697058E+09 0.105866E+10 0.00 0.00 0.00 0.00 0.00 0.785713E+09
November 0.471555E+09 0.676237E+09 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.122294E+10
December 0.487480E+09 0.695446E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.132313E+10
                   
Annual Sum or Average 0.574883E+10 0.821331E+10 0.124712E+11 0.00 0.00 0.00 0.00 5729455.30 0.894078E+10
Minimum of Months 0.440737E+09 0.629623E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.211736E+09
Maximum of Months 0.489771E+09 0.699745E+09 0.106152E+10 0.00 0.00 0.00 0.00 3727242.37 0.132313E+10



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.159843E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.725907E+09
February 0.339028E+09 0.144324E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.620114E+09
March 0.376747E+09 0.160336E+09 0.306128E+09 0.00 0.00 0.00 0.00 0.00 0.578346E+09
April 0.363528E+09 0.154423E+09 0.295253E+09 0.00 0.00 0.00 0.00 0.00 0.346977E+09
May 0.375778E+09 0.160120E+09 0.305852E+09 0.00 0.00 0.00 0.00 24394.96 0.181332E+09
June 0.364321E+09 0.155132E+09 0.296217E+09 0.00 0.00 0.00 0.00 3088604.57 97543938.99
July 0.374985E+09 0.159412E+09 0.304889E+09 0.00 0.00 0.00 0.00 6696745.11 90063697.86
August 0.376571E+09 0.160397E+09 0.306219E+09 0.00 0.00 0.00 0.00 1718160.82 0.127245E+09
September 0.363352E+09 0.154485E+09 0.295345E+09 0.00 0.00 0.00 0.00 0.00 0.239696E+09
October 0.375161E+09 0.159781E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.00 0.432824E+09
November 0.362735E+09 0.155009E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.704961E+09
December 0.374985E+09 0.159412E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.763089E+09
                   
Annual Sum or Average 0.442217E+10 0.188267E+10 0.359760E+10 0.00 0.00 0.00 0.00 11527905.46 0.490810E+10
Minimum of Months 0.339028E+09 0.144324E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 90063697.86
Maximum of Months 0.376747E+09 0.160397E+09 0.306219E+09 0.00 0.00 0.00 0.00 6696745.11 0.763089E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.297499E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.185049E+10
February 0.139600E+10 0.268614E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.158760E+10
March 0.155131E+10 0.298416E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.149894E+10
April 0.149688E+10 0.287412E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 0.00 0.941209E+09
May 0.154732E+10 0.298015E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.00 0.541520E+09
June 0.150015E+10 0.288730E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 2186036.95 0.312708E+09
July 0.154405E+10 0.296696E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 5089349.85 0.289239E+09
August 0.155059E+10 0.298530E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 547598.74 0.395269E+09
September 0.149615E+10 0.287527E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.00 0.683902E+09
October 0.154478E+10 0.297384E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.115064E+10
November 0.149361E+10 0.288501E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.179738E+10
December 0.154405E+10 0.296696E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.193988E+10
                   
Annual Sum or Average 0.182090E+11 0.350402E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 7822985.54 0.129888E+11
Minimum of Months 0.139600E+10 0.268614E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.289239E+09
Maximum of Months 0.155131E+10 0.298530E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 5089349.85 0.193988E+10



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.733909E+09 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.304907E+10
February 0.236489E+11 0.592371E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.260566E+10
March 0.262800E+11 0.566253E+09 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.244236E+10
April 0.253579E+11 0.394419E+09 0.117692E+10 0.00 0.00 0.00 0.00 0.00 0.150965E+10
May 0.262123E+11 0.346296E+09 0.121917E+10 0.00 0.00 0.00 0.00 0.00 0.818836E+09
June 0.254132E+11 0.282446E+09 0.118076E+10 0.00 0.00 0.00 0.00 8462076.59 0.442794E+09
July 0.261570E+11 0.314422E+09 0.121533E+10 0.00 0.00 0.00 0.00 18315075.13 0.402500E+09
August 0.262677E+11 0.402831E+09 0.122063E+10 0.00 0.00 0.00 0.00 2528714.34 0.574790E+09
September 0.253456E+11 0.508925E+09 0.117729E+10 0.00 0.00 0.00 0.00 0.00 0.104843E+10
October 0.261693E+11 0.629968E+09 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.183208E+10
November 0.253025E+11 0.679016E+09 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.296112E+10
December 0.261570E+11 0.765509E+09 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.320523E+10
                   
Annual Sum or Average 0.308468E+12 0.621637E+10 0.143405E+11 0.00 0.00 0.00 0.00 29305866.05 0.208925E+11
Minimum of Months 0.236489E+11 0.282446E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.402500E+09
Maximum of Months 0.262800E+11 0.765509E+09 0.122063E+10 0.00 0.00 0.00 0.00 18315075.13 0.320523E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.661997E+10 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.875760E+10
February 0.702046E+11 0.586846E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.749999E+10
March 0.780153E+11 0.638632E+10 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.705560E+10
April 0.752779E+11 0.594212E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.00 0.440319E+10
May 0.778146E+11 0.607441E+10 0.126672E+11 0.00 0.00 0.00 0.00 0.00 0.246667E+10
June 0.754422E+11 0.580802E+10 0.122682E+11 0.00 0.00 0.00 0.00 22406894.69 0.138906E+10
July 0.776503E+11 0.600741E+10 0.126273E+11 0.00 0.00 0.00 0.00 51112856.18 0.128119E+10
August 0.779788E+11 0.616691E+10 0.126824E+11 0.00 0.00 0.00 0.00 7936262.70 0.177846E+10
September 0.752414E+11 0.610638E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.00 0.313025E+10
October 0.776868E+11 0.645976E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.534899E+10
November 0.751137E+11 0.637059E+10 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.851152E+10
December 0.776503E+11 0.665283E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.919151E+10
                   
Annual Sum or Average 0.915726E+12 0.744632E+11 0.148998E+12 0.00 0.00 0.00 0.00 81456013.58 0.608140E+11
Minimum of Months 0.702046E+11 0.580802E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.128119E+10
Maximum of Months 0.780153E+11 0.665283E+10 0.126824E+11 0.00 0.00 0.00 0.00 51112856.18 0.919151E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.789413E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.674299E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.631429E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.388629E+09
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 28834.97 0.208862E+09
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 3096403.90 0.108100E+09
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 6278130.53 97757570.53
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 1557481.66 0.142523E+09
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.268415E+09
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.471174E+09
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.766667E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.830267E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 10960851.05 0.537753E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 97757570.53
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 6278130.53 0.830267E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.789320E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.673904E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.628202E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.382661E+09
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 0.00 0.211003E+09
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 2387993.69 0.119344E+09
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 4673152.63 0.106332E+09
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 972468.02 0.148011E+09
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.264805E+09
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.469064E+09
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.766563E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.830193E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 8033614.35 0.538940E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.106332E+09
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4673152.63 0.830193E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 65789991.58 0.217935E+09 0.00 0.00 0.00 0.00 0.00 0.192356E+09
February 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 0.00 0.164064E+09
March 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 0.00 0.164460E+09
April 0.00 63743496.62 0.210923E+09 0.00 0.00 0.00 0.00 0.00 0.130161E+09
May 0.00 65528554.53 0.217879E+09 0.00 0.00 0.00 0.00 0.00 84152058.58
June 0.00 63237765.93 0.210812E+09 0.00 0.00 0.00 0.00 10041.13 53822679.92
July 0.00 66042856.93 0.217991E+09 0.00 0.00 0.00 0.00 100488.13 50862190.64
August 0.00 65267117.48 0.217824E+09 0.00 0.00 0.00 0.00 0.00 65290569.60
September 0.00 63760640.03 0.210923E+09 0.00 0.00 0.00 0.00 0.00 99989234.58
October 0.00 65781419.88 0.217935E+09 0.00 0.00 0.00 0.00 0.00 0.136975E+09
November 0.00 63490631.27 0.210867E+09 0.00 0.00 0.00 0.00 0.00 0.186820E+09
December 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 0.00 0.203457E+09
                   
Annual Sum or Average 0.00 0.773376E+09 0.256575E+10 0.00 0.00 0.00 0.00 110529.26 0.153241E+10
Minimum of Months 0.00 59414784.75 0.196843E+09 0.00 0.00 0.00 0.00 0.00 50862190.64
Maximum of Months 0.00 66051428.64 0.217991E+09 0.00 0.00 0.00 0.00 100488.13 0.203457E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.221143E+09
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 0.189094E+09
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 0.00 0.176919E+09
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 0.00 0.107590E+09
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 0.00 58026071.78
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 693266.65 31469936.67
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 1399867.08 28606285.59
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 311255.77 40394428.87
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 0.00 75058802.07
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.132843E+09
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 0.00 0.214773E+09
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 0.00 0.232471E+09
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 2404389.50 0.150839E+10
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 28606285.59
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 1399867.08 0.232471E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.789435E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.674741E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.635628E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.391497E+09
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 28857.12 0.210771E+09
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 3116608.36 0.108758E+09
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 6299018.12 98550758.43
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 1574931.68 0.143970E+09
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.271196E+09
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.472954E+09
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.766692E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.830265E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 11019415.28 0.539446E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 98550758.43
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 6299018.12 0.830265E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.789334E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.674050E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.630632E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.386265E+09
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 0.00 0.213102E+09
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 2412177.76 0.116891E+09
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 4692362.19 0.107341E+09
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 985281.10 0.148677E+09
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.268179E+09
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.470532E+09
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.766577E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.830189E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 8089821.05 0.540177E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.107341E+09
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4692362.19 0.830189E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.109776E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.969075E+09
February 0.348285E+10 0.991179E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.827895E+09
March 0.387034E+10 0.110115E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.772286E+09
April 0.373454E+10 0.106054E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.469358E+09
May 0.386038E+10 0.109967E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.261439E+09
June 0.374269E+10 0.106541E+10 0.00 0.00 0.00 0.00 0.00 2340669.51 0.150128E+09
July 0.385223E+10 0.109480E+10 0.00 0.00 0.00 0.00 0.00 5405905.52 0.137445E+09
August 0.386853E+10 0.110157E+10 0.00 0.00 0.00 0.00 0.00 1170712.52 0.186647E+09
September 0.373273E+10 0.106097E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.325789E+09
October 0.385404E+10 0.109734E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.578312E+09
November 0.372639E+10 0.106456E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.941113E+09
December 0.385223E+10 0.109480E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.101867E+10
                   
Annual Sum or Average 0.454292E+11 0.129297E+11 0.00 0.00 0.00 0.00 0.00 8917287.55 0.663816E+10
Minimum of Months 0.348285E+10 0.991179E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.137445E+09
Maximum of Months 0.387034E+10 0.110157E+10 0.00 0.00 0.00 0.00 0.00 5405905.52 0.101867E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104684E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.790657E+09
February 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.675140E+09
March 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.630758E+09
April 0.293479E+09 0.101428E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.388159E+09
May 0.303504E+09 0.104268E+09 0.222446E+09 0.00 0.00 0.00 0.00 26102.45 0.209507E+09
June 0.293842E+09 0.100623E+09 0.215230E+09 0.00 0.00 0.00 0.00 2994243.17 0.108840E+09
July 0.303141E+09 0.105087E+09 0.222560E+09 0.00 0.00 0.00 0.00 6097111.26 98468213.84
August 0.303685E+09 0.103852E+09 0.222390E+09 0.00 0.00 0.00 0.00 1495933.60 0.143048E+09
September 0.293479E+09 0.101455E+09 0.215344E+09 0.00 0.00 0.00 0.00 0.00 0.267812E+09
October 0.303322E+09 0.104671E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.470754E+09
November 0.293661E+09 0.101025E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.767874E+09
December 0.303141E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.831556E+09
                   
Annual Sum or Average 0.357224E+10 0.123059E+10 0.261953E+10 0.00 0.00 0.00 0.00 10613390.47 0.538257E+10
Minimum of Months 0.273974E+09 94540036.54 0.200969E+09 0.00 0.00 0.00 0.00 0.00 98468213.84
Maximum of Months 0.303685E+09 0.105100E+09 0.222560E+09 0.00 0.00 0.00 0.00 6097111.26 0.831556E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.104672E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.790574E+09
February 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.674987E+09
March 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.628847E+09
April 0.293479E+09 0.101416E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.382397E+09
May 0.303504E+09 0.104256E+09 0.222420E+09 0.00 0.00 0.00 0.00 0.00 0.212331E+09
June 0.293842E+09 0.100611E+09 0.215205E+09 0.00 0.00 0.00 0.00 2326258.22 0.121834E+09
July 0.303141E+09 0.105074E+09 0.222534E+09 0.00 0.00 0.00 0.00 4546497.85 0.108356E+09
August 0.303685E+09 0.103840E+09 0.222364E+09 0.00 0.00 0.00 0.00 937965.54 0.149629E+09
September 0.293479E+09 0.101443E+09 0.215319E+09 0.00 0.00 0.00 0.00 0.00 0.264045E+09
October 0.303322E+09 0.104658E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.469148E+09
November 0.293661E+09 0.101014E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.767788E+09
December 0.303141E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.831478E+09
                   
Annual Sum or Average 0.357224E+10 0.123044E+10 0.261922E+10 0.00 0.00 0.00 0.00 7810721.61 0.540141E+10
Minimum of Months 0.273974E+09 94528959.80 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.108356E+09
Maximum of Months 0.303685E+09 0.105088E+09 0.222534E+09 0.00 0.00 0.00 0.00 4546497.85 0.831478E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 65807981.74 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.404774E+09
February 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 0.347894E+09
March 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 0.00 0.328898E+09
April 0.293479E+09 63760927.16 0.210981E+09 0.00 0.00 0.00 0.00 0.00 0.201941E+09
May 0.303504E+09 65546473.20 0.217939E+09 0.00 0.00 0.00 0.00 12460.40 0.108042E+09
June 0.293842E+09 63255058.18 0.210869E+09 0.00 0.00 0.00 0.00 1545308.82 55857426.50
July 0.303141E+09 66060916.23 0.218051E+09 0.00 0.00 0.00 0.00 3129581.01 50613487.10
August 0.303685E+09 65284964.65 0.217883E+09 0.00 0.00 0.00 0.00 765613.01 73960328.13
September 0.293479E+09 63778075.26 0.210981E+09 0.00 0.00 0.00 0.00 0.00 0.140198E+09
October 0.303322E+09 65799407.69 0.217995E+09 0.00 0.00 0.00 0.00 0.00 0.244703E+09
November 0.293661E+09 63507992.67 0.210925E+09 0.00 0.00 0.00 0.00 0.00 0.393376E+09
December 0.303141E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 0.00 0.425581E+09
                   
Annual Sum or Average 0.357224E+10 0.773587E+09 0.256645E+10 0.00 0.00 0.00 0.00 5452963.22 0.277584E+10
Minimum of Months 0.273974E+09 59431031.62 0.196897E+09 0.00 0.00 0.00 0.00 0.00 50613487.10
Maximum of Months 0.303685E+09 66069490.28 0.218051E+09 0.00 0.00 0.00 0.00 3129581.01 0.425581E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.136884E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.198057E+10
February 0.415303E+11 0.117196E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.169540E+10
March 0.461508E+11 0.120959E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.159223E+10
April 0.445315E+11 0.101116E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.981762E+09
May 0.460320E+11 0.971794E+09 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.548701E+09
June 0.446286E+11 0.893470E+09 0.144540E+11 0.00 0.00 0.00 0.00 6070352.69 0.308480E+09
July 0.459349E+11 0.944222E+09 0.149358E+11 0.00 0.00 0.00 0.00 14582639.19 0.284306E+09
August 0.461292E+11 0.104142E+10 0.149358E+11 0.00 0.00 0.00 0.00 3133496.73 0.390083E+09
September 0.445099E+11 0.113200E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.697516E+09
October 0.459565E+11 0.126798E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.120610E+10
November 0.444343E+11 0.130480E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.192334E+10
December 0.459349E+11 0.138639E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.207896E+10
                   
Annual Sum or Average 0.541708E+12 0.137036E+11 0.175857E+12 0.00 0.00 0.00 0.00 23786488.62 0.136874E+11
Minimum of Months 0.415303E+11 0.893470E+09 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.284306E+09
Maximum of Months 0.461508E+11 0.138639E+10 0.149358E+11 0.00 0.00 0.00 0.00 14582639.19 0.207896E+10



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.136884E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.199087E+10
February 0.415303E+11 0.117196E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.170539E+10
March 0.461508E+11 0.120959E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.160523E+10
April 0.445315E+11 0.101116E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.996525E+09
May 0.460320E+11 0.971794E+09 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.562062E+09
June 0.446286E+11 0.893470E+09 0.144540E+11 0.00 0.00 0.00 0.00 5249646.32 0.318365E+09
July 0.459349E+11 0.944222E+09 0.149358E+11 0.00 0.00 0.00 0.00 12779155.80 0.293512E+09
August 0.461292E+11 0.104142E+10 0.149358E+11 0.00 0.00 0.00 0.00 2548403.22 0.401302E+09
September 0.445099E+11 0.113200E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.713050E+09
October 0.459565E+11 0.126798E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.122056E+10
November 0.444343E+11 0.130480E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.193353E+10
December 0.459349E+11 0.138639E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.208875E+10
                   
Annual Sum or Average 0.541708E+12 0.137036E+11 0.175857E+12 0.00 0.00 0.00 0.00 20577205.35 0.138291E+11
Minimum of Months 0.415303E+11 0.893470E+09 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.293512E+09
Maximum of Months 0.461508E+11 0.138639E+10 0.149358E+11 0.00 0.00 0.00 0.00 12779155.80 0.208875E+10



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.735117E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.188944E+10
February 0.369574E+10 0.663744E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.162125E+10
March 0.410691E+10 0.737383E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.153123E+10
April 0.396281E+10 0.710193E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.962689E+09
May 0.409635E+10 0.736392E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.555489E+09
June 0.397146E+10 0.713450E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 2085106.30 0.322076E+09
July 0.408770E+10 0.733135E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 4923734.46 0.298165E+09
August 0.410499E+10 0.737666E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 497279.46 0.406442E+09
September 0.396089E+10 0.710477E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.700482E+09
October 0.408962E+10 0.734834E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.117625E+10
November 0.395417E+10 0.712884E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.183526E+10
December 0.408770E+10 0.733135E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.198059E+10
                   
Annual Sum or Average 0.482060E+11 0.865841E+10 0.382987E+12 0.359593E+12 0.00 0.00 0.00 7506120.23 0.132794E+11
Minimum of Months 0.369574E+10 0.663744E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.298165E+09
Maximum of Months 0.410691E+10 0.737666E+09 0.325276E+11 0.305408E+11 0.00 0.00 0.00 4923734.46 0.198059E+10



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.116181E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.171764E+10
February 0.368610E+10 0.104901E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.146753E+10
March 0.409620E+10 0.116539E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.137009E+10
April 0.395248E+10 0.112242E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.853697E+09
May 0.408566E+10 0.116383E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.514277E+09
June 0.396110E+10 0.112757E+10 0.00 0.00 0.00 0.00 0.00 2023975.11 0.311519E+09
July 0.407704E+10 0.115868E+10 0.00 0.00 0.00 0.00 0.00 4788129.36 0.287556E+09
August 0.409429E+10 0.116584E+10 0.00 0.00 0.00 0.00 0.00 479184.84 0.381243E+09
September 0.395056E+10 0.112287E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.608370E+09
October 0.407896E+10 0.116136E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.102871E+10
November 0.394385E+10 0.112667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.166808E+10
December 0.407704E+10 0.115868E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.180544E+10
                   
Annual Sum or Average 0.480803E+11 0.136841E+11 0.00 0.00 0.00 0.00 0.00 7291289.32 0.120141E+11
Minimum of Months 0.368610E+10 0.104901E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.287556E+09
Maximum of Months 0.409620E+10 0.116584E+10 0.00 0.00 0.00 0.00 0.00 4788129.36 0.180544E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 7163.56 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 7163.56 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 7163.56 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 7163.56 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 7163.56 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 7163.56 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 7163.56 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 7163.56 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 7163.56 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 7163.56 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 7163.56 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 7163.56 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   7163.56   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   7163.56   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 324.19 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 870.19 12-JAN-06:20
February 1169.53 01-FEB-00:10 324.19 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 817.71 27-FEB-05:50
March 1169.53 01-MAR-00:10 324.19 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 705.46 01-MAR-07:00
April 1169.53 01-APR-00:10 324.19 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 580.60 03-APR-06:00
May 1169.53 01-MAY-00:10 324.19 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 262.45 28-MAY-02:00
June 1169.53 01-JUN-00:10 324.19 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 48.62 30-JUN-15:00 231.30 02-JUN-04:00
July 1169.53 01-JUL-00:10 324.19 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 67.83 29-JUL-16:50 187.56 31-JUL-03:00
August 1169.53 01-AUG-00:10 324.19 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 18.24 11-AUG-16:00 290.10 31-AUG-06:00
September 1169.53 01-SEP-00:10 324.19 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 334.64 30-SEP-09:00
October 1169.53 01-OCT-23:10 324.19 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 567.74 22-OCT-06:50
November 1169.53 01-NOV-00:10 324.19 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 717.09 29-NOV-10:00
December 1169.53 01-DEC-00:10 324.19 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 790.75 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   324.19   685.60   0.00 0.00 0.00 0.00 0.00   187.56  
Maximum of Months 1169.53   324.19   685.60   0.00 0.00 0.00 0.00 67.83   870.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 375.41 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 335.88 12-JAN-06:00
February 1354.32 01-FEB-00:10 375.41 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 315.64 27-FEB-06:00
March 1354.32 01-MAR-00:10 375.41 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 272.31 01-MAR-07:00
April 1354.32 01-APR-00:10 375.41 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 224.10 03-APR-06:00
May 1354.32 01-MAY-00:10 375.41 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 104.45 27-MAY-04:00
June 1354.32 01-JUN-00:10 375.41 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 25.10 30-JUN-15:00 92.69 02-JUN-04:00
July 1354.32 01-JUL-00:10 375.41 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 33.30 29-JUL-16:00 74.54 31-JUL-04:40
August 1354.32 01-AUG-00:10 375.41 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 13.61 11-AUG-17:00 117.66 31-AUG-06:00
September 1354.32 01-SEP-00:10 375.41 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 130.56 29-SEP-06:53
October 1354.32 01-OCT-23:10 375.41 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 219.14 22-OCT-06:50
November 1354.32 01-NOV-00:10 375.41 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 276.78 29-NOV-10:00
December 1354.32 01-DEC-00:10 375.41 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 305.23 15-DEC-07:59
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   375.41   793.93   0.00 0.00 0.00 0.00 0.00   74.54  
Maximum of Months 1354.32   375.41   793.93   0.00 0.00 0.00 0.00 33.30   335.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 671.67 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 793.79 12-JAN-07:50
February 286.42 01-FEB-00:10 671.67 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 745.93 27-FEB-05:00
March 286.42 01-MAR-00:10 671.67 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 643.55 01-MAR-07:00
April 286.42 01-APR-00:10 671.67 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 529.63 03-APR-06:00
May 286.42 01-MAY-00:10 671.67 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 265.29 27-MAY-06:55
June 286.42 01-JUN-00:10 671.67 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 44.36 30-JUN-15:00 236.17 02-JUN-04:00
July 286.42 01-JUL-00:10 671.67 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 61.88 29-JUL-17:00 190.17 31-JUL-04:00
August 286.42 01-AUG-00:10 671.67 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 16.64 11-AUG-16:00 296.43 31-AUG-06:00
September 286.42 01-SEP-00:10 671.67 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 325.79 29-SEP-06:53
October 286.42 01-OCT-23:10 671.67 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 521.84 22-OCT-07:00
November 286.42 01-NOV-00:10 671.67 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 654.15 29-NOV-10:00
December 286.42 01-DEC-00:10 671.67 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 721.37 15-DEC-07:54
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   671.67   839.45   0.00 0.00 0.00 0.00 0.00   190.17  
Maximum of Months 286.42   671.67   839.45   0.00 0.00 0.00 0.00 61.88   793.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 153.96 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 457.98 12-JAN-06:20
February 220.32 01-FEB-00:10 153.96 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 430.37 27-FEB-05:20
March 220.32 01-MAR-00:10 153.96 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 371.29 01-MAR-07:00
April 220.32 01-APR-00:10 153.96 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 305.57 03-APR-06:00
May 220.32 01-MAY-00:10 153.96 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 4.69 31-MAY-16:00 138.14 28-MAY-02:00
June 220.32 01-JUN-00:10 153.96 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 37.35 30-JUN-15:00 119.59 02-JUN-04:00
July 220.32 01-JUL-00:10 153.96 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 48.46 29-JUL-17:00 95.17 31-JUL-05:00
August 220.32 01-AUG-00:10 153.96 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 23.25 11-AUG-17:00 152.69 31-AUG-06:00
September 220.32 01-SEP-00:10 153.96 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 176.14 30-SEP-09:00
October 220.32 01-OCT-23:10 153.96 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 298.80 22-OCT-06:10
November 220.32 01-NOV-00:10 153.96 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 377.40 29-NOV-10:00
December 220.32 01-DEC-00:10 153.96 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 416.19 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   153.96   242.16   0.00 0.00 0.00 0.00 0.00   95.17  
Maximum of Months 220.32   153.96   242.16   0.00 0.00 0.00 0.00 48.46   457.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 286.55 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 1138.69 12-JAN-08:00
February 907.20 01-FEB-00:10 286.55 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:05 1072.02 27-FEB-05:50
March 907.20 01-MAR-00:10 286.55 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:05 931.53 01-MAR-07:00
April 907.20 01-APR-00:10 286.55 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 0.00 01-APR-00:10 773.97 03-APR-06:00
May 907.20 01-MAY-00:10 286.55 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 0.00 01-MAY-00:10 373.63 28-MAY-02:00
June 907.20 01-JUN-00:10 286.55 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 60.57 30-JUN-15:00 323.35 02-JUN-04:00
July 907.20 01-JUL-00:10 286.55 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 84.50 29-JUL-16:20 259.66 31-JUL-04:00
August 907.20 01-AUG-00:10 286.55 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 22.72 11-AUG-16:00 409.09 31-AUG-06:00
September 907.20 01-SEP-00:10 286.55 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 0.00 01-SEP-00:10 464.94 30-SEP-09:00
October 907.20 01-OCT-23:10 286.55 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 758.14 22-OCT-07:00
November 907.20 01-NOV-00:10 286.55 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:10 945.72 29-NOV-10:00
December 907.20 01-DEC-00:10 286.55 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:05 1038.82 15-DEC-08:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   286.55   4572.80   39726.58   0.00 0.00 0.00 0.00   259.66  
Maximum of Months 907.20   286.55   4572.80   39726.58   0.00 0.00 0.00 84.50   1138.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 767.68 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1923.77 12-JAN-06:40
February 15368.40 01-FEB-00:10 767.68 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1807.67 27-FEB-05:30
March 15368.40 01-MAR-00:10 767.68 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 1559.51 01-MAR-07:00
April 15368.40 01-APR-00:10 767.68 03-APR-19:40 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1283.54 03-APR-06:00
May 15368.40 01-MAY-00:10 682.39 04-MAY-20:30 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 600.73 27-MAY-05:00
June 15368.40 01-JUN-00:10 584.00 02-JUN-20:00 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 131.52 30-JUN-15:00 529.50 02-JUN-04:00
July 15368.40 01-JUL-00:10 610.24 28-JUL-20:00 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 182.44 29-JUL-17:00 423.18 31-JUL-05:00
August 15368.40 01-AUG-00:10 767.68 29-AUG-19:30 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 81.43 11-AUG-18:00 657.71 31-AUG-06:00
September 15368.40 01-SEP-00:10 767.68 01-SEP-19:30 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 739.81 30-SEP-09:00
October 15368.40 01-OCT-23:10 767.68 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1255.18 22-OCT-06:20
November 15368.40 01-NOV-00:10 767.68 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1584.96 29-NOV-10:00
December 15368.40 01-DEC-00:10 767.68 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 1748.02 15-DEC-07:56
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   584.00   965.27   0.00 0.00 0.00 0.00 0.00   423.18  
Maximum of Months 15368.40   767.68   965.27   0.00 0.00 0.00 0.00 182.44   1923.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 6458.51 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5496.05 12-JAN-07:40
February 45622.98 01-FEB-00:10 6458.51 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 5164.67 27-FEB-05:30
March 45622.98 01-MAR-00:10 6458.51 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 4487.86 01-MAR-00:05
April 45622.98 01-APR-00:10 6458.51 03-APR-19:40 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3713.98 03-APR-06:00
May 45622.98 01-MAY-00:10 6303.31 02-MAY-19:00 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1786.73 27-MAY-04:00
June 45622.98 01-JUN-00:10 6176.68 02-JUN-19:00 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 393.57 30-JUN-15:00 1576.66 02-JUN-04:00
July 45622.98 01-JUL-00:10 6140.00 28-JUL-19:00 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 525.72 29-JUL-16:00 1272.72 31-JUL-05:00
August 45622.98 01-AUG-00:10 6458.51 29-AUG-19:30 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 200.38 11-AUG-17:00 1977.72 31-AUG-06:00
September 45622.98 01-SEP-00:10 6458.51 01-SEP-19:30 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 2199.01 30-SEP-06:00
October 45622.98 01-OCT-23:10 6458.51 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3617.05 22-OCT-07:00
November 45622.98 01-NOV-00:10 6458.51 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4529.13 29-NOV-10:00
December 45622.98 01-DEC-00:10 6458.51 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 4994.41 15-DEC-07:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   6140.00   10029.21   0.00 0.00 0.00 0.00 0.00   1272.72  
Maximum of Months 45622.98   6458.51   10029.21   0.00 0.00 0.00 0.00 525.72   5496.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 506.34 12-JAN-06:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 475.87 27-FEB-05:00
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 410.71 01-MAR-07:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.18 03-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 7.00 31-MAY-16:00 153.45 28-MAY-02:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.59 20-JUN-19:00 129.96 02-JUN-04:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 58.05 29-JUL-16:00 100.50 31-JUL-03:30
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 29.46 11-AUG-16:00 169.51 31-AUG-06:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 195.38 30-SEP-09:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 330.72 22-OCT-06:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 417.44 29-NOV-10:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 459.30 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   100.50  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 58.05   506.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 506.31 12-JAN-06:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 475.83 27-FEB-05:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 410.67 01-MAR-07:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.16 03-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 153.44 28-MAY-02:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.58 20-JUN-19:00 129.95 02-JUN-04:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 58.05 29-JUL-16:10 100.49 31-JUL-03:00
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 29.46 11-AUG-16:00 169.50 31-AUG-06:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 195.37 30-SEP-09:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 330.69 22-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 417.41 29-NOV-10:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 459.27 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   100.49  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 58.05   506.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 59.53 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 128.08 12-JAN-07:54
February 0.00 01-FEB-00:10 59.53 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 119.89 27-FEB-05:00
March 0.00 01-MAR-00:10 59.53 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 103.88 31-MAR-06:00
April 0.00 01-APR-00:10 59.53 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 95.00 03-APR-06:00
May 0.00 01-MAY-00:10 59.53 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 53.06 27-MAY-07:20
June 0.00 01-JUN-00:10 59.53 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 2.91 30-JUN-15:00 47.06 02-JUN-04:00
July 0.00 01-JUL-00:10 59.53 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 6.02 29-JUL-16:53 39.20 31-JUL-03:00
August 0.00 01-AUG-00:10 59.53 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:10 58.45 31-AUG-06:00
September 0.00 01-SEP-00:10 59.53 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 62.94 30-SEP-09:00
October 0.00 01-OCT-00:10 59.53 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 85.64 22-OCT-09:00
November 0.00 01-NOV-00:10 59.53 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 103.83 29-NOV-10:00
December 0.00 01-DEC-00:10 59.53 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 115.46 15-DEC-07:54
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 0.00   39.20  
Maximum of Months 0.00   59.53   232.19   0.00 0.00 0.00 0.00 6.02   128.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 141.32 12-JAN-07:50
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 132.81 27-FEB-05:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 114.62 01-MAR-07:00
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 94.38 03-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 44.60 27-MAY-07:20
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 10.21 20-JUN-18:50 36.27 02-JUN-04:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 16.20 29-JUL-16:00 28.05 31-JUL-03:00
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 8.22 11-AUG-16:00 47.31 31-AUG-06:00
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 55.47 30-SEP-08:00
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 92.30 22-OCT-06:50
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 116.50 29-NOV-10:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 128.21 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 0.00   28.05  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 16.20   141.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 506.35 12-JAN-06:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 475.87 27-FEB-05:30
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 410.71 01-MAR-07:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.19 03-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 7.00 31-MAY-16:00 153.45 28-MAY-02:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.59 20-JUN-18:40 129.96 02-JUN-04:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 58.05 29-JUL-16:10 100.50 31-JUL-03:10
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 29.46 11-AUG-16:00 173.33 31-AUG-07:10
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 199.14 30-SEP-08:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 330.72 22-OCT-06:30
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 417.45 29-NOV-10:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 459.30 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   100.50  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 58.05   506.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 506.31 12-JAN-06:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 475.83 27-FEB-05:00
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 410.67 01-MAR-07:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.15 03-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 153.44 28-MAY-02:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.58 20-JUN-18:40 129.95 02-JUN-04:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 58.05 29-JUL-16:10 100.49 31-JUL-03:20
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 29.46 11-AUG-16:00 172.81 31-AUG-07:10
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 196.51 30-SEP-08:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 330.69 22-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 417.41 29-NOV-10:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 459.26 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   100.49  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 58.05   506.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1057.37 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 611.16 12-JAN-07:20
February 2263.36 01-FEB-00:10 1057.37 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 574.33 27-FEB-05:00
March 2263.36 01-MAR-00:10 1057.37 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 495.54 01-MAR-07:00
April 2263.36 01-APR-00:10 1057.37 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 407.89 03-APR-06:00
May 2263.36 01-MAY-00:10 1057.37 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 189.25 27-MAY-04:00
June 2263.36 01-JUN-00:10 1057.37 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 42.34 30-JUN-15:00 167.40 02-JUN-04:00
July 2263.36 01-JUL-00:10 1057.37 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 56.38 29-JUL-17:00 135.62 31-JUL-05:00
August 2263.36 01-AUG-00:10 1057.37 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 22.57 11-AUG-18:00 211.69 31-AUG-06:00
September 2263.36 01-SEP-00:10 1057.37 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 235.27 30-SEP-09:00
October 2263.36 01-OCT-23:10 1057.37 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 398.86 22-OCT-06:00
November 2263.36 01-NOV-00:10 1057.37 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 503.71 29-NOV-10:00
December 2263.36 01-DEC-00:10 1057.37 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 555.43 15-DEC-07:51
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1057.37   0.00 0.00 0.00 0.00 0.00 0.00   135.62  
Maximum of Months 2263.36   1057.37   0.00 0.00 0.00 0.00 0.00 56.38   611.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.72 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 506.98 12-JAN-06:00
February 180.00 01-FEB-00:10 94.72 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 476.48 27-FEB-05:10
March 180.00 01-MAR-00:10 94.72 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 411.29 01-MAR-07:00
April 180.00 01-APR-00:10 94.72 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.74 03-APR-06:00
May 180.00 01-MAY-00:10 94.72 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 6.60 31-MAY-16:00 153.91 28-MAY-02:00
June 180.00 01-JUN-00:10 94.72 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.20 20-JUN-18:50 130.42 02-JUN-04:00
July 180.00 01-JUL-00:10 94.72 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 57.68 29-JUL-16:05 100.95 31-JUL-03:10
August 180.00 01-AUG-00:10 94.72 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 29.07 11-AUG-16:00 169.99 31-AUG-06:00
September 180.00 01-SEP-00:10 94.72 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 195.87 30-SEP-09:00
October 180.00 01-OCT-00:10 94.72 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 331.27 22-OCT-06:00
November 180.00 01-NOV-00:10 94.72 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 418.03 29-NOV-10:00
December 180.00 01-DEC-00:10 94.72 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 459.91 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 0.00   100.95  
Maximum of Months 180.00   94.72   237.06   0.00 0.00 0.00 0.00 57.68   506.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 94.71 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 506.94 12-JAN-06:00
February 180.00 01-FEB-00:10 94.71 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 476.45 27-FEB-05:10
March 180.00 01-MAR-00:10 94.71 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 411.26 01-MAR-07:00
April 180.00 01-APR-00:10 94.71 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 338.71 03-APR-06:00
May 180.00 01-MAY-00:10 94.71 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 153.90 28-MAY-02:00
June 180.00 01-JUN-00:10 94.71 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.20 20-JUN-19:00 130.41 02-JUN-04:00
July 180.00 01-JUL-00:10 94.71 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 57.67 29-JUL-16:10 100.94 31-JUL-03:30
August 180.00 01-AUG-00:10 94.71 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 29.07 11-AUG-16:00 169.98 31-AUG-06:00
September 180.00 01-SEP-00:10 94.71 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 195.85 30-SEP-09:00
October 180.00 01-OCT-00:10 94.71 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 331.25 22-OCT-06:00
November 180.00 01-NOV-00:10 94.71 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 418.00 29-NOV-10:00
December 180.00 01-DEC-00:10 94.71 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 459.88 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 0.00   100.94  
Maximum of Months 180.00   94.71   237.03   0.00 0.00 0.00 0.00 57.67   506.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 59.54 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 259.39 12-JAN-06:10
February 180.00 01-FEB-00:10 59.54 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 243.78 27-FEB-05:00
March 180.00 01-MAR-00:10 59.54 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 210.43 01-MAR-07:00
April 180.00 01-APR-00:10 59.54 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 173.31 03-APR-06:00
May 180.00 01-MAY-00:10 59.54 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 3.37 31-MAY-16:00 78.75 28-MAY-02:00
June 180.00 01-JUN-00:10 59.54 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 18.52 20-JUN-18:50 66.72 02-JUN-04:00
July 180.00 01-JUL-00:10 59.54 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 29.51 29-JUL-16:40 51.65 31-JUL-03:00
August 180.00 01-AUG-00:10 59.54 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 14.87 11-AUG-16:00 86.97 31-AUG-06:00
September 180.00 01-SEP-00:10 59.54 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 100.21 30-SEP-09:00
October 180.00 01-OCT-00:10 59.54 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 169.49 22-OCT-06:00
November 180.00 01-NOV-00:10 59.54 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 213.88 29-NOV-10:00
December 180.00 01-DEC-00:10 59.54 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 235.31 15-DEC-07:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 0.00   51.65  
Maximum of Months 180.00   59.54   232.26   0.00 0.00 0.00 0.00 29.51   259.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 1348.12 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1240.56 12-JAN-06:00
February 26988.77 01-FEB-00:10 1348.12 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1167.80 27-FEB-05:20
March 26988.77 01-MAR-00:10 1348.12 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 1021.35 01-MAR-00:05
April 26988.77 01-APR-00:10 1348.12 03-APR-19:40 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 838.62 03-APR-06:00
May 26988.77 01-MAY-00:10 1198.33 04-MAY-20:30 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 404.57 27-MAY-05:00
June 26988.77 01-JUN-00:10 1117.45 02-JUN-19:00 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 94.99 30-JUN-15:00 357.39 02-JUN-04:00
July 26988.77 01-JUL-00:10 1136.84 26-JUL-20:00 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 130.18 29-JUL-16:00 286.89 31-JUL-05:00
August 26988.77 01-AUG-00:10 1348.12 29-AUG-19:30 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 56.67 11-AUG-18:00 444.07 31-AUG-06:00
September 26988.77 01-SEP-00:10 1348.12 01-SEP-19:30 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 498.14 30-SEP-06:00
October 26988.77 01-OCT-23:10 1348.12 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 822.82 22-OCT-07:00
November 26988.77 01-NOV-00:10 1348.12 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1018.68 29-NOV-10:00
December 26988.77 01-DEC-00:10 1348.12 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 1123.10 15-DEC-07:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   1117.45   6747.90   0.00 0.00 0.00 0.00 0.00   286.89  
Maximum of Months 26988.77   1348.12   6747.90   0.00 0.00 0.00 0.00 130.18   1240.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 1348.12 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1246.30 12-JAN-06:00
February 26988.77 01-FEB-00:10 1348.12 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1173.32 27-FEB-05:20
March 26988.77 01-MAR-00:10 1348.12 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 1027.92 01-MAR-00:05
April 26988.77 01-APR-00:10 1348.12 03-APR-19:40 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 845.10 03-APR-06:00
May 26988.77 01-MAY-00:10 1198.33 04-MAY-20:30 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 409.25 27-MAY-05:00
June 26988.77 01-JUN-00:10 1117.45 02-JUN-19:00 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 90.81 30-JUN-15:00 361.27 02-JUN-04:00
July 26988.77 01-JUL-00:10 1136.84 26-JUL-20:00 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 125.67 29-JUL-16:00 290.68 31-JUL-05:00
August 26988.77 01-AUG-00:10 1348.12 29-AUG-19:30 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 52.06 11-AUG-18:00 449.17 31-AUG-06:00
September 26988.77 01-SEP-00:10 1348.12 01-SEP-19:30 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 504.86 30-SEP-06:00
October 26988.77 01-OCT-23:10 1348.12 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 829.85 22-OCT-07:00
November 26988.77 01-NOV-00:10 1348.12 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1021.62 28-NOV-23:40
December 26988.77 01-DEC-00:10 1348.12 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 1123.79 15-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   1117.45   6747.90   0.00 0.00 0.00 0.00 0.00   290.68  
Maximum of Months 26988.77   1348.12   6747.90   0.00 0.00 0.00 0.00 125.67   1246.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 708.07 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 1162.00 12-JAN-08:00
February 2401.70 01-FEB-00:10 708.07 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:05 1093.99 27-FEB-05:00
March 2401.70 01-MAR-00:10 708.07 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:05 950.74 01-MAR-07:00
April 2401.70 01-APR-00:10 708.07 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 0.00 01-APR-00:10 790.15 03-APR-06:00
May 2401.70 01-MAY-00:10 708.07 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:10 382.20 28-MAY-02:00
June 2401.70 01-JUN-00:10 708.07 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 60.39 30-JUN-15:00 330.98 02-JUN-04:00
July 2401.70 01-JUL-00:10 708.07 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 84.83 29-JUL-16:00 266.09 31-JUL-03:50
August 2401.70 01-AUG-00:10 708.07 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 21.90 11-AUG-16:00 418.30 31-AUG-06:00
September 2401.70 01-SEP-00:10 708.07 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 0.00 01-SEP-00:10 475.18 30-SEP-09:00
October 2401.70 01-OCT-23:10 708.07 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 774.12 22-OCT-07:00
November 2401.70 01-NOV-00:10 708.07 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:10 965.16 29-NOV-10:00
December 2401.70 01-DEC-00:10 708.07 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:05 1060.21 15-DEC-08:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   708.07   14604.56   22492.83   0.00 0.00 0.00 0.00   266.09  
Maximum of Months 2401.70   708.07   14604.56   22492.83   0.00 0.00 0.00 84.83   1162.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1119.06 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1082.73 12-JAN-07:20
February 2395.44 01-FEB-00:10 1119.06 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1017.52 27-FEB-05:00
March 2395.44 01-MAR-00:10 1119.06 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 878.06 01-MAR-07:00
April 2395.44 01-APR-00:10 1119.06 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 722.86 03-APR-06:00
May 2395.44 01-MAY-00:10 1119.06 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 345.29 27-MAY-04:00
June 2395.44 01-JUN-00:10 1119.06 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 58.96 30-JUN-15:00 314.26 02-JUN-04:00
July 2395.44 01-JUL-00:10 1119.06 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 82.81 29-JUL-16:50 255.22 31-JUL-05:00
August 2395.44 01-AUG-00:10 1119.06 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 21.21 11-AUG-16:00 382.06 31-AUG-06:00
September 2395.44 01-SEP-00:10 1119.06 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 417.30 30-SEP-09:00
October 2395.44 01-OCT-23:10 1119.06 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 706.91 22-OCT-06:30
November 2395.44 01-NOV-00:10 1119.06 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 892.47 29-NOV-10:00
December 2395.44 01-DEC-00:10 1119.06 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 984.05 15-DEC-07:52
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1119.06   0.00 0.00 0.00 0.00 0.00 0.00   255.22  
Maximum of Months 2395.44   1119.06   0.00 0.00 0.00 0.00 0.00 82.81   1082.73  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11476.48 06-JAN-21:00 8945.92 7163.56 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
February 11135.73 01-FEB-21:00 8945.92 7163.56 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
March 10816.66 22-MAR-20:00 8945.92 7163.56 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
April 11268.54 27-APR-18:10 62621.41 44573.36 63878.88 0.00 0.00 0.00 0.00 0.00 0.00
May 11799.71 31-MAY-18:10 62621.41 44573.36 63878.88 0.00 0.00 0.00 0.00 0.00 0.00
June 12484.35 29-JUN-10:35 5111.95 3979.81 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
July 13867.39 23-JUL-10:35 7667.93 4775.64 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
August 14355.10 26-AUG-10:35 7667.93 3979.81 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
September 14469.17 10-SEP-10:35 7667.93 4775.64 8111.60 0.00 0.00 0.00 0.00 0.00 0.00
October 13895.48 06-OCT-20:00 8945.92 7163.56 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
November 13358.31 01-NOV-20:00 8945.92 7163.56 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
December 12689.18 01-DEC-21:00 8945.92 7163.56 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 10816.66   5111.95 3979.81 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14469.17   62621.41 44573.36 63878.88 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 163.70 23-JAN-13:30 259.90 90.05 252.59 0.00 0.00 0.00 0.00 0.00 390.02
February 949.70 09-FEB-11:50 259.90 90.05 252.59 0.00 0.00 0.00 0.00 0.00 295.80
March 1385.26 27-MAR-14:10 389.84 90.05 252.59 0.00 0.00 0.00 0.00 0.00 368.23
April 3067.35 22-APR-13:30 389.84 90.05 252.59 0.00 0.00 0.00 0.00 0.00 102.01
May 3102.51 12-MAY-13:30 259.90 90.05 252.59 0.00 0.00 0.00 0.00 0.00 39.23
June 3047.75 30-JUN-12:30 259.90 90.05 252.59 0.00 0.00 0.00 0.00 24.49 0.00
July 3485.11 23-JUL-13:30 259.90 72.04 216.51 0.00 0.00 0.00 0.00 11.43 0.00
August 3529.05 25-AUG-13:30 259.90 90.05 252.59 0.00 0.00 0.00 0.00 0.00 26.97
September 2687.92 09-SEP-13:30 389.84 90.05 252.59 0.00 0.00 0.00 0.00 0.00 127.32
October 1777.14 03-OCT-13:30 259.90 90.05 252.59 0.00 0.00 0.00 0.00 0.00 157.91
November 793.40 08-NOV-13:30 259.90 90.05 252.59 0.00 0.00 0.00 0.00 0.00 454.45
December 0.00 01-DEC-00:05 2339.06 144.08 433.01 0.00 0.00 0.00 0.00 0.00 639.31
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   259.90 72.04 216.51 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3529.05   2339.06 144.08 433.01 0.00 0.00 0.00 0.00 24.49 639.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1030.82 19-JAN-21:00 1053.36 375.41 793.93 0.00 0.00 0.00 0.00 0.00 153.90
February 1103.51 09-FEB-21:00 1053.36 375.41 793.93 0.00 0.00 0.00 0.00 0.00 153.01
March 1202.31 22-MAR-20:00 1053.36 375.41 793.93 0.00 0.00 0.00 0.00 0.00 91.43
April 1422.68 21-APR-20:00 1053.36 375.41 793.93 0.00 0.00 0.00 0.00 0.00 49.62
May 1490.37 31-MAY-18:10 7373.52 2335.87 5265.02 0.00 0.00 0.00 0.00 0.00 6.69
June 1577.16 21-JUN-18:10 6320.16 2002.18 4512.87 0.00 0.00 0.00 0.00 10.76 0.00
July 1582.66 12-JUL-18:10 6320.16 2002.18 4512.87 0.00 0.00 0.00 0.00 4.99 0.00
August 1551.81 02-AUG-18:10 6320.16 2002.18 4512.87 0.00 0.00 0.00 0.00 0.00 0.74
September 1387.47 10-SEP-10:35 902.88 250.27 668.57 0.00 0.00 0.00 0.00 0.00 35.97
October 1265.34 03-OCT-20:00 1053.36 375.41 793.93 0.00 0.00 0.00 0.00 0.00 75.41
November 1057.78 01-NOV-20:00 1053.36 375.41 793.93 0.00 0.00 0.00 0.00 0.00 146.24
December 997.13 19-DEC-21:00 1053.36 375.41 793.93 0.00 0.00 0.00 0.00 0.00 129.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 997.13   902.88 250.27 668.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1582.66   7373.52 2335.87 5265.02 0.00 0.00 0.00 0.00 10.76 153.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15.62 19-JAN-21:00 222.77 671.67 839.45 0.00 0.00 0.00 0.00 0.00 369.52
February 17.31 09-FEB-21:00 222.77 671.67 839.45 0.00 0.00 0.00 0.00 0.00 370.86
March 19.78 22-MAR-20:00 222.77 671.67 839.45 0.00 0.00 0.00 0.00 0.00 230.06
April 386.64 21-APR-20:00 222.77 671.67 839.45 0.00 0.00 0.00 0.00 0.00 128.29
May 821.87 31-MAY-21:00 254.59 597.04 795.27 0.00 0.00 0.00 0.00 0.00 78.35
June 1143.27 21-JUN-21:00 254.59 597.04 795.27 0.00 0.00 0.00 0.00 0.00 1.09
July 1171.69 21-JUL-20:00 222.77 671.67 839.45 0.00 0.00 0.00 0.00 10.31 0.00
August 1091.58 11-AUG-20:00 222.77 671.67 839.45 0.00 0.00 0.00 0.00 4.15 0.00
September 527.28 01-SEP-21:00 254.59 597.04 795.27 0.00 0.00 0.00 0.00 0.00 141.34
October 145.45 06-OCT-21:00 254.59 597.04 795.27 0.00 0.00 0.00 0.00 0.00 173.85
November 16.15 03-NOV-20:00 222.77 671.67 839.45 0.00 0.00 0.00 0.00 0.00 320.55
December 15.11 19-DEC-21:00 222.77 671.67 839.45 0.00 0.00 0.00 0.00 0.00 311.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15.11   222.77 597.04 795.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1171.69   254.59 671.67 839.45 0.00 0.00 0.00 0.00 10.31 370.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 342.72 102.64 203.92 0.00 0.00 0.00 0.00 0.00 244.18
February 119.12 08-FEB-22:00 195.84 136.85 229.41 0.00 0.00 0.00 0.00 0.00 130.13
March 383.59 22-MAR-21:00 195.84 136.85 229.41 0.00 0.00 0.00 0.00 0.00 123.57
April 737.03 22-APR-17:15 293.76 205.28 356.86 0.00 0.00 0.00 0.00 0.00 44.16
May 857.73 14-MAY-10:35 146.88 102.64 203.92 0.00 0.00 0.00 0.00 0.00 27.94
June 901.92 22-JUN-10:35 97.92 85.53 178.43 0.00 0.00 0.00 0.00 0.00 3.43
July 950.18 22-JUL-10:35 146.88 85.53 178.43 0.00 0.00 0.00 0.00 10.88 0.00
August 881.75 05-AUG-10:35 146.88 85.53 178.43 0.00 0.00 0.00 0.00 0.00 14.52
September 747.40 03-SEP-10:35 146.88 102.64 203.92 0.00 0.00 0.00 0.00 0.00 73.04
October 627.58 06-OCT-21:00 195.84 136.85 229.41 0.00 0.00 0.00 0.00 0.00 81.73
November 0.00 01-NOV-00:10 220.32 25.66 63.73 0.00 0.00 0.00 0.00 0.00 210.90
December 0.00 01-DEC-00:05 440.64 68.43 152.94 0.00 0.00 0.00 0.00 0.00 336.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   97.92 25.66 63.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 950.18   440.64 205.28 356.86 0.00 0.00 0.00 0.00 10.88 336.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36393.54 19-JAN-21:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 543.76
February 36832.66 08-FEB-21:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 391.15
March 37443.56 22-MAR-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 328.72
April 38134.55 21-APR-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 175.18
May 38583.10 31-MAY-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 99.49
June 38852.32 29-JUN-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 14.18 0.00
July 38934.44 21-JUL-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 14.06 0.00
August 38798.72 11-AUG-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 5.64 0.00
September 38059.17 01-SEP-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 175.50
October 37660.11 03-OCT-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 271.29
November 36500.66 01-NOV-20:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 516.00
December 36219.38 19-DEC-21:00 705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 465.24
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 36219.38   705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38934.44   705.60 286.55 4572.80 39726.58 0.00 0.00 0.00 14.18 543.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6807.70 06-JAN-23:10 15368.40 255.89 406.43 0.00 0.00 0.00 0.00 0.00 652.24
February 7289.75 08-FEB-22:00 13660.80 682.39 914.47 0.00 0.00 0.00 0.00 0.00 546.66
March 8977.71 27-MAR-15:40 8538.00 46.91 355.63 0.00 0.00 0.00 0.00 0.00 766.30
April 11339.79 21-APR-15:25 17076.00 93.83 711.25 0.00 0.00 0.00 0.00 0.00 257.07
May 11264.24 09-MAY-15:30 8538.00 46.91 355.63 0.00 0.00 0.00 0.00 0.00 160.17
June 11366.72 20-JUN-15:23 25614.00 140.74 1066.88 0.00 0.00 0.00 0.00 45.55 0.00
July 11941.31 23-JUL-10:35 10245.60 112.59 812.86 0.00 0.00 0.00 0.00 0.00 8.22
August 12016.30 10-AUG-15:10 8538.00 46.91 355.63 0.00 0.00 0.00 0.00 0.00 43.88
September 10995.80 10-SEP-10:35 10245.60 112.59 812.86 0.00 0.00 0.00 0.00 0.00 222.29
October 9010.88 03-OCT-15:12 51228.00 281.48 2133.76 0.00 0.00 0.00 0.00 0.00 269.18
November 6886.47 01-NOV-22:10 15368.40 255.89 406.43 0.00 0.00 0.00 0.00 0.00 839.52
December 6389.25 19-DEC-22:30 15368.40 511.79 711.25 0.00 0.00 0.00 0.00 0.00 810.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6389.25   8538.00 46.91 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12016.30   51228.00 682.39 2133.76 0.00 0.00 0.00 0.00 45.55 839.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 23244.23 06-JAN-22:00 40553.76 5740.90 9501.36 0.00 0.00 0.00 0.00 0.00 2010.46
February 24674.11 08-FEB-22:00 40553.76 5740.90 9501.36 0.00 0.00 0.00 0.00 0.00 1659.37
March 26836.98 22-MAR-20:00 35484.54 6458.51 10029.21 0.00 0.00 0.00 0.00 0.00 1541.41
April 30300.48 22-APR-10:35 30415.32 3085.73 7389.94 0.00 0.00 0.00 0.00 0.00 773.26
May 31749.98 14-MAY-10:35 30415.32 3702.88 8445.65 0.00 0.00 0.00 0.00 0.00 412.82
June 33907.65 21-JUN-21:06 228114.90 20278.87 36949.72 0.00 0.00 0.00 0.00 0.00 34.22
July 33790.14 23-JUL-10:35 30415.32 3702.88 8445.65 0.00 0.00 0.00 0.00 0.00 30.51
August 33285.06 25-AUG-21:10 91245.96 8611.35 14779.89 0.00 0.00 0.00 0.00 0.00 429.05
September 30626.89 10-SEP-10:35 30415.32 3702.88 8445.65 0.00 0.00 0.00 0.00 0.00 631.12
October 28120.70 03-OCT-20:00 35484.54 6458.51 10029.21 0.00 0.00 0.00 0.00 0.00 1277.82
November 23797.29 01-NOV-21:00 40553.76 5740.90 9501.36 0.00 0.00 0.00 0.00 0.00 2464.68
December 22767.23 19-DEC-21:00 35484.54 6458.51 10029.21 0.00 0.00 0.00 0.00 0.00 2165.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22767.23   30415.32 3085.73 7389.94 0.00 0.00 0.00 0.00 0.00 30.51
Maximum of Months 33907.65   228114.90 20278.87 36949.72 0.00 0.00 0.00 0.00 0.00 2464.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 882.30 19-JAN-09:04 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 194.01
February 1019.48 10-FEB-19:04 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 179.47
March 2818.56 22-MAR-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 111.79
April 3156.33 21-APR-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 58.29
May 3176.17 10-MAY-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 29.54
June 3218.21 10-JUN-18:01 819.00 663.02 848.14 0.00 0.00 0.00 0.00 0.00 7.55
July 2821.46 22-JUL-08:61 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 21.81
August 3120.90 31-AUG-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 57.76
September 3111.86 07-SEP-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 41.42
October 1992.71 03-OCT-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 69.64
November 836.21 04-NOV-08:04 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 219.42
December 785.40 26-DEC-09:04 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 216.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 785.40   252.00 159.12 300.27 0.00 0.00 0.00 0.00 0.00 7.55
Maximum of Months 3218.21   970.20 663.02 1143.15 0.00 0.00 0.00 0.00 0.00 219.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 751.56 23-JAN-09:04 252.00 291.69 792.74 0.00 0.00 0.00 0.00 0.00 243.16
February 1046.34 08-FEB-19:04 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 151.01
March 1167.03 20-MAR-15:13 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 104.86
April 2877.93 21-APR-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 58.25
May 3218.46 09-MAY-20:01 1602.00 842.88 1817.24 0.00 0.00 0.00 0.00 0.00 76.03
June 2898.28 28-JUN-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 44.98
July 2825.03 06-JUL-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 34.27
August 2839.55 30-AUG-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 98.38
September 2825.76 07-SEP-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 57.77
October 1262.32 02-OCT-15:13 583.20 159.11 300.24 0.00 0.00 0.00 0.00 0.00 90.70
November 825.23 04-NOV-08:04 378.00 371.25 1143.02 0.00 0.00 0.00 0.00 0.00 219.40
December 878.10 26-DEC-09:04 252.00 291.69 792.74 0.00 0.00 0.00 0.00 0.00 216.85
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 751.56   252.00 159.11 300.24 0.00 0.00 0.00 0.00 0.00 34.27
Maximum of Months 3218.46   1800.00 842.88 1817.24 0.00 0.00 0.00 0.00 0.00 243.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 0.00 30.95 87.72 0.00 0.00 0.00 0.00 0.00 63.83
February 40.19 15-FEB-15:20 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 54.10
March 106.92 31-MAR-14:20 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 72.82
April 534.86 22-APR-13:30 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 21.66
May 526.16 12-MAY-13:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 11.41
June 478.69 30-JUN-12:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 1.04
July 568.56 23-JUL-13:30 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 3.18
August 596.24 25-AUG-13:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 9.50
September 490.77 09-SEP-13:20 0.00 19.64 33.54 0.00 0.00 0.00 0.00 0.00 26.24
October 268.62 03-OCT-13:30 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 30.84
November 20.98 08-NOV-15:20 0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 67.44
December 0.00 01-DEC-00:05 0.00 26.19 87.72 0.00 0.00 0.00 0.00 0.00 91.57
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 16.67 30.96 0.00 0.00 0.00 0.00 0.00 1.04
Maximum of Months 596.24   0.00 30.95 87.72 0.00 0.00 0.00 0.00 0.00 91.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 477.97 20-JAN-19:04 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 72.86
February 476.34 08-FEB-16:14 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 39.00
March 813.70 18-MAR-08:61 378.00 233.40 1119.99 0.00 0.00 0.00 0.00 0.00 46.13
April 925.71 30-APR-18:01 819.00 416.79 830.96 0.00 0.00 0.00 0.00 0.00 24.86
May 985.14 14-MAY-20:41 1386.00 595.42 1780.62 0.00 0.00 0.00 0.00 0.00 18.05
June 1026.07 10-JUN-21:51 1247.40 455.50 789.67 0.00 0.00 0.00 0.00 0.00 7.41
July 953.71 19-JUL-21:51 1620.00 359.04 789.67 0.00 0.00 0.00 0.00 0.00 7.67
August 989.88 10-AUG-21:51 1620.00 359.04 789.67 0.00 0.00 0.00 0.00 0.00 13.53
September 916.92 10-SEP-18:01 819.00 416.79 830.96 0.00 0.00 0.00 0.00 0.00 12.95
October 868.51 09-OCT-08:61 378.00 233.40 1119.99 0.00 0.00 0.00 0.00 0.00 46.79
November 463.57 06-NOV-19:04 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 67.40
December 446.62 24-DEC-09:01 378.00 233.40 1119.99 0.00 0.00 0.00 0.00 0.00 41.51
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 446.62   378.00 116.70 343.22 0.00 0.00 0.00 0.00 0.00 7.41
Maximum of Months 1026.07   1620.00 595.42 1780.62 0.00 0.00 0.00 0.00 0.00 72.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 736.67 19-JAN-09:04 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 194.00
February 995.02 08-FEB-19:04 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 151.02
March 2732.66 22-MAR-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 114.00
April 2968.26 22-APR-08:61 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 120.76
May 3009.14 13-MAY-15:11 378.00 218.80 387.20 0.00 0.00 0.00 0.00 0.00 17.70
June 3014.22 22-JUN-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 4.07 0.00
July 2667.03 24-JUL-18:02 831.60 505.79 726.98 0.00 0.00 0.00 0.00 0.00 6.67
August 3012.66 10-AUG-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.08 0.00
September 2939.37 07-SEP-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 41.29
October 2674.74 04-OCT-08:62 180.00 208.38 566.31 0.00 0.00 0.00 0.00 0.00 94.12
November 789.43 04-NOV-08:04 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 219.42
December 835.97 26-DEC-09:04 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 216.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 736.67   180.00 159.12 300.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3014.22   970.20 590.08 1143.15 0.00 0.00 0.00 0.00 4.07 219.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 796.88 23-JAN-09:04 252.00 291.69 792.74 0.00 0.00 0.00 0.00 0.00 243.16
February 1104.82 08-FEB-19:04 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 151.01
March 1267.38 18-MAR-08:03 378.00 371.25 1143.02 0.00 0.00 0.00 0.00 0.00 165.11
April 2722.54 22-APR-08:61 378.00 371.25 1143.02 0.00 0.00 0.00 0.00 0.00 120.99
May 2794.77 14-MAY-20:41 1386.00 947.05 1817.24 0.00 0.00 0.00 0.00 0.00 63.86
June 2780.25 29-JUN-08:51 360.00 416.70 1132.48 0.00 0.00 0.00 0.00 0.00 44.73
July 2995.31 22-JUL-08:32 270.00 265.18 816.44 0.00 0.00 0.00 0.00 0.00 40.66
August 2722.74 31-AUG-08:61 252.00 291.69 792.74 0.00 0.00 0.00 0.00 0.00 147.18
September 2603.95 10-SEP-15:11 378.00 218.77 387.15 0.00 0.00 0.00 0.00 0.00 45.30
October 1845.64 04-OCT-08:62 180.00 208.35 566.24 0.00 0.00 0.00 0.00 0.00 93.04
November 880.54 04-NOV-08:04 378.00 371.25 1143.02 0.00 0.00 0.00 0.00 0.00 219.40
December 863.23 26-DEC-09:04 252.00 291.69 792.74 0.00 0.00 0.00 0.00 0.00 216.85
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 796.88   180.00 208.35 387.15 0.00 0.00 0.00 0.00 0.00 40.66
Maximum of Months 2995.31   1386.00 947.05 1817.24 0.00 0.00 0.00 0.00 0.00 243.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 419.58 06-JAN-23:00 2263.36 704.91 0.00 0.00 0.00 0.00 0.00 0.00 205.15
February 772.84 08-FEB-22:05 4526.71 1409.83 0.00 0.00 0.00 0.00 0.00 0.00 177.35
March 1313.32 22-MAR-21:00 2011.87 939.88 0.00 0.00 0.00 0.00 0.00 0.00 165.47
April 1790.75 22-APR-10:35 1508.90 587.43 0.00 0.00 0.00 0.00 0.00 0.00 82.02
May 1992.70 14-MAY-10:35 1508.90 704.91 0.00 0.00 0.00 0.00 0.00 0.00 46.32
June 2085.86 13-JUN-10:35 1005.94 587.43 0.00 0.00 0.00 0.00 0.00 0.00 7.72
July 2169.81 22-JUL-10:35 1508.90 587.43 0.00 0.00 0.00 0.00 0.00 6.21 0.00
August 2025.45 02-AUG-18:10 10562.33 5639.31 0.00 0.00 0.00 0.00 0.00 0.00 2.29
September 1755.88 10-SEP-10:35 1508.90 704.91 0.00 0.00 0.00 0.00 0.00 0.00 64.15
October 1404.56 03-OCT-20:00 1760.39 1057.37 0.00 0.00 0.00 0.00 0.00 0.00 128.15
November 497.26 01-NOV-21:05 4526.71 1409.83 0.00 0.00 0.00 0.00 0.00 0.00 264.65
December 408.21 24-DEC-23:00 2011.87 587.43 0.00 0.00 0.00 0.00 0.00 0.00 212.24
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 408.21   1005.94 587.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2169.81   10562.33 5639.31 0.00 0.00 0.00 0.00 0.00 6.21 264.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 497.43 22-JAN-09:04 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 199.56
February 799.17 09-FEB-09:04 252.00 291.73 792.83 0.00 0.00 0.00 0.00 0.00 172.62
March 2443.51 22-MAR-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 112.00
April 3274.04 21-APR-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 58.86
May 3291.70 30-MAY-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 22.16
June 3332.60 10-JUN-18:01 819.00 663.02 848.14 0.00 0.00 0.00 0.00 0.00 8.02
July 2875.39 15-JUL-18:01 819.00 663.02 848.14 0.00 0.00 0.00 0.00 0.00 26.22
August 3340.84 10-AUG-18:01 970.20 590.08 848.14 0.00 0.00 0.00 0.00 0.00 1.39
September 3219.70 07-SEP-15:11 680.40 185.64 350.32 0.00 0.00 0.00 0.00 0.00 41.81
October 2024.28 03-OCT-15:12 583.20 159.12 300.27 0.00 0.00 0.00 0.00 0.00 68.16
November 363.11 04-NOV-08:04 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 219.92
December 788.76 24-DEC-09:04 378.00 371.29 1143.15 0.00 0.00 0.00 0.00 0.00 149.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 363.11   252.00 159.12 300.27 0.00 0.00 0.00 0.00 0.00 1.39
Maximum of Months 3340.84   970.20 663.02 1143.15 0.00 0.00 0.00 0.00 0.00 219.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 371.72 21-JAN-09:04 378.00 371.25 1143.02 0.00 0.00 0.00 0.00 0.00 207.57
February 809.41 09-FEB-09:04 252.00 291.69 792.74 0.00 0.00 0.00 0.00 0.00 172.61
March 1264.04 20-MAR-15:13 680.40 185.62 350.28 0.00 0.00 0.00 0.00 0.00 105.27
April 2957.04 21-APR-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 58.79
May 3436.47 09-MAY-20:01 1602.00 842.88 1817.24 0.00 0.00 0.00 0.00 0.00 81.11
June 3092.20 26-JUN-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 39.28
July 3013.47 06-JUL-21:51 1800.00 634.53 895.45 0.00 0.00 0.00 0.00 0.00 38.24
August 2908.56 30-AUG-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 98.72
September 2896.74 07-SEP-18:01 970.20 590.02 848.04 0.00 0.00 0.00 0.00 0.00 58.14
October 1424.32 04-OCT-15:13 583.20 159.11 300.24 0.00 0.00 0.00 0.00 0.00 72.21
November 475.06 04-NOV-08:04 378.00 371.25 1143.02 0.00 0.00 0.00 0.00 0.00 219.90
December 431.07 24-DEC-09:04 378.00 371.25 1143.02 0.00 0.00 0.00 0.00 0.00 149.10
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 371.72   252.00 159.11 300.24 0.00 0.00 0.00 0.00 0.00 38.24
Maximum of Months 3436.47   1800.00 842.88 1817.24 0.00 0.00 0.00 0.00 0.00 219.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 580.61 22-JAN-19:04 819.00 416.79 830.96 0.00 0.00 0.00 0.00 0.00 103.96
February 2049.76 15-FEB-16:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 112.02
March 2189.60 27-MAR-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 103.06
April 2238.85 20-APR-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 32.12
May 2238.65 13-MAY-15:11 378.00 137.54 379.35 0.00 0.00 0.00 0.00 0.00 9.12
June 2222.85 22-JUN-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 2.30 0.00
July 1992.53 24-JUL-18:02 831.60 317.95 712.25 0.00 0.00 0.00 0.00 0.00 3.14
August 2229.39 10-AUG-18:01 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.14 0.00
September 2172.53 30-SEP-15:12 324.00 117.89 325.16 0.00 0.00 0.00 0.00 0.00 72.55
October 2181.25 13-OCT-15:11 680.40 116.70 343.22 0.00 0.00 0.00 0.00 0.00 77.17
November 505.08 01-NOV-18:04 970.20 370.95 830.96 0.00 0.00 0.00 0.00 0.00 112.50
December 601.22 24-DEC-19:04 819.00 416.79 830.96 0.00 0.00 0.00 0.00 0.00 93.20
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 505.08   324.00 116.70 325.16 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2238.85   970.20 416.79 830.96 0.00 0.00 0.00 0.00 2.30 112.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15660.92 06-JAN-23:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 450.08
February 16114.81 08-FEB-23:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 421.40
March 16604.15 22-MAR-22:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 390.02
April 17730.03 21-APR-20:30 23990.02 1115.61 6747.90 0.00 0.00 0.00 0.00 0.00 203.95
May 19123.63 31-MAY-18:10 146938.85 5032.98 47235.32 0.00 0.00 0.00 0.00 0.00 24.79
June 21013.58 21-JUN-21:06 134943.84 2696.24 33739.51 0.00 0.00 0.00 0.00 0.00 9.37
July 20165.33 11-JUL-21:20 26988.77 539.25 6747.90 0.00 0.00 0.00 0.00 0.00 42.87
August 19536.95 02-AUG-18:10 125947.58 4313.98 40487.42 0.00 0.00 0.00 0.00 0.00 0.20
September 17714.11 01-SEP-21:00 23990.02 1198.33 6747.90 0.00 0.00 0.00 0.00 0.00 204.69
October 16925.76 06-OCT-22:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 273.55
November 15667.35 03-NOV-22:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 522.88
December 15360.57 19-DEC-23:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 557.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15360.57   23990.02 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 0.20
Maximum of Months 21013.58   146938.85 5032.98 47235.32 0.00 0.00 0.00 0.00 0.00 557.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16452.17 06-JAN-23:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 456.45
February 16930.98 08-FEB-23:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 428.11
March 17425.35 22-MAR-22:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 396.79
April 18420.96 21-APR-20:30 23990.02 1115.61 6747.90 0.00 0.00 0.00 0.00 0.00 209.38
May 20487.04 31-MAY-21:10 53977.54 1603.99 13495.81 0.00 0.00 0.00 0.00 0.00 127.06
June 21573.25 21-JUN-21:04 134943.84 2696.24 33739.51 0.00 0.00 0.00 0.00 0.00 9.32
July 21326.61 11-JUL-21:20 26988.77 539.25 6747.90 0.00 0.00 0.00 0.00 0.00 43.21
August 20983.52 02-AUG-21:10 53977.54 1745.51 13495.81 0.00 0.00 0.00 0.00 0.00 61.42
September 18416.49 01-SEP-21:00 23990.02 1198.33 6747.90 0.00 0.00 0.00 0.00 0.00 210.20
October 17814.62 06-OCT-21:00 23990.02 1198.33 6747.90 0.00 0.00 0.00 0.00 0.00 258.07
November 16465.70 03-NOV-22:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 529.51
December 16130.05 19-DEC-23:10 26988.77 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 564.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16130.05   23990.02 449.37 6747.90 0.00 0.00 0.00 0.00 0.00 9.32
Maximum of Months 21573.25   134943.84 2696.24 33739.51 0.00 0.00 0.00 0.00 0.00 564.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 24019.82 22-JAN-11:50 800.57 236.02 14604.56 18744.03 0.00 0.00 0.00 0.00 488.69
February 25061.13 09-FEB-11:50 533.71 196.69 14604.56 18744.03 0.00 0.00 0.00 0.00 421.24
March 26789.66 22-MAR-10:50 533.71 196.69 14604.56 18744.03 0.00 0.00 0.00 0.00 338.39
April 28630.30 22-APR-10:50 800.57 196.69 14604.56 18744.03 0.00 0.00 0.00 0.00 177.20
May 29079.75 14-MAY-10:50 800.57 236.02 14604.56 18744.03 0.00 0.00 0.00 0.00 105.13
June 29543.66 29-JUN-10:40 1067.42 393.37 29209.11 37488.05 0.00 0.00 0.00 0.00 33.20
July 30247.17 22-JUL-10:40 1601.14 393.37 29209.11 37488.05 0.00 0.00 0.00 0.00 6.39
August 29255.19 26-AUG-10:50 800.57 196.69 14604.56 18744.03 0.00 0.00 0.00 0.00 117.31
September 28323.43 10-SEP-10:50 800.57 236.02 14604.56 18744.03 0.00 0.00 0.00 0.00 148.57
October 26704.87 03-OCT-10:35 1067.42 393.37 29209.11 37488.05 0.00 0.00 0.00 0.00 291.40
November 23757.87 01-NOV-18:03 13075.94 4405.76 102231.89 104966.55 0.00 0.00 0.00 0.00 526.70
December 24230.01 24-DEC-11:50 800.57 236.02 14604.56 18744.03 0.00 0.00 0.00 0.00 346.45
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 23757.87   533.71 196.69 14604.56 18744.03 0.00 0.00 0.00 0.00 6.39
Maximum of Months 30247.17   13075.94 4405.76 102231.89 104966.55 0.00 0.00 0.00 0.00 526.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 3726.24 746.04 0.00 0.00 0.00 0.00 0.00 0.00 577.91
February 1001.65 09-FEB-13:30 532.32 310.85 0.00 0.00 0.00 0.00 0.00 0.00 336.67
March 1618.59 22-MAR-10:40 532.32 310.85 0.00 0.00 0.00 0.00 0.00 0.00 289.59
April 2189.31 22-APR-10:50 798.48 310.85 0.00 0.00 0.00 0.00 0.00 0.00 158.02
May 3865.68 13-MAY-13:20 1596.96 621.70 0.00 0.00 0.00 0.00 0.00 0.00 72.82
June 4948.57 20-JUN-15:13 9315.60 2175.96 0.00 0.00 0.00 0.00 0.00 15.56 0.00
July 5213.60 23-JUL-13:30 532.32 248.68 0.00 0.00 0.00 0.00 0.00 12.74 0.00
August 4217.72 02-AUG-15:10 1330.80 310.85 0.00 0.00 0.00 0.00 0.00 0.00 24.99
September 2152.25 10-SEP-10:35 1596.96 746.04 0.00 0.00 0.00 0.00 0.00 0.00 133.53
October 1624.80 03-OCT-10:50 532.32 310.85 0.00 0.00 0.00 0.00 0.00 0.00 236.55
November 0.00 01-NOV-00:10 2395.44 186.51 0.00 0.00 0.00 0.00 0.00 0.00 499.33
December 0.00 01-DEC-00:05 4790.88 497.36 0.00 0.00 0.00 0.00 0.00 0.00 795.85
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   532.32 186.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5213.60   9315.60 2175.96 0.00 0.00 0.00 0.00 0.00 15.56 795.85



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.314546E+12 194163.91 12-JAN-20:10 0.102053E+13 1122896.64 12-JAN-19:10
February 0.279545E+12 191715.03 06-FEB-20:30 0.849566E+12 956745.50 28-FEB-21:19
March 0.304669E+12 191333.45 06-MAR-20:30 0.677043E+12 817845.12 01-MAR-21:00
April 0.295486E+12 198166.78 21-APR-18:10 0.483291E+12 422120.50 10-APR-20:49
May 0.321206E+12 218920.02 30-MAY-19:49 0.458448E+12 387296.16 26-MAY-17:49
June 0.352677E+12 276049.69 29-JUN-19:10 0.402477E+12 359842.10 01-JUN-17:00
July 0.376749E+12 273050.46 11-JUL-19:10 0.410107E+12 354926.26 05-JUL-17:40
August 0.348904E+12 265636.27 11-AUG-19:10 0.416810E+12 351049.97 02-AUG-17:19
September 0.291518E+12 196838.89 07-SEP-19:49 0.473395E+12 444464.68 29-SEP-18:10
October 0.303404E+12 191286.75 23-OCT-19:30 0.547719E+12 479154.14 16-OCT-18:10
November 0.302346E+12 191524.38 02-NOV-19:49 0.948013E+12 974362.38 30-NOV-19:10
December 0.316149E+12 191233.49 14-DEC-20:10 0.112101E+13 987542.36 15-DEC-17:19
             
Annual Sum or Average 0.380720E+13     0.780842E+13    
Minimum of Months 0.279545E+12 191233.49   0.402477E+12 351049.97  
Maximum of Months 0.376749E+12 276049.69   0.112101E+13 1122896.64  



Table of Contents

Report: EnergyConsumptionElectricityGeneratedPropaneMonthly

For: Meter

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ELECTRICITYPRODUCED:FACILITY [J] ELECTRICITYPRODUCED:FACILITY {Maximum} [W] ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} PROPANE:FACILITY [] PROPANE:FACILITY []
January 0.432868E+09 3831.66 31-JAN-11:30 0.00 0.00
February 0.244049E+10 9058.33 26-FEB-13:09 0.00 0.00
March 0.875017E+10 20419.30 30-MAR-12:30 0.00 0.00
April 0.161455E+11 23663.63 30-APR-13:30 0.00 0.00
May 0.200890E+11 25225.27 21-MAY-12:00 0.00 0.00
June 0.206319E+11 25313.99 01-JUN-12:30 0.00 0.00
July 0.190070E+11 25088.08 06-JUL-12:50 0.00 0.00
August 0.146314E+11 22084.49 10-AUG-12:30 0.00 0.00
September 0.800524E+10 16346.08 09-SEP-12:30 0.00 0.00
October 0.359702E+10 10816.38 03-OCT-12:30 0.00 0.00
November 0.836293E+09 4602.59 06-NOV-13:30 0.00 0.00
December 83123413.30 1220.88 02-DEC-11:30 0.00 0.00
           
Annual Sum or Average 0.114650E+12     0.00 0.00
Minimum of Months 83123413.30 1220.88   0.00 0.00
Maximum of Months 0.206319E+11 25313.99   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY [J]
January 0.381756E+11 0.205950E+11 0.140003E+12 0.331704E+11 0.484072E+11 0.142472E+10 0.00 0.189109E+09 0.00 0.00 0.211760E+11 0.770429E+10 0.00
February 0.341645E+11 0.154089E+11 0.126445E+12 0.299603E+11 0.427355E+11 0.143021E+10 0.00 0.289370E+09 0.00 0.00 0.188070E+11 0.696185E+10 0.00
March 0.374047E+11 0.134447E+11 0.140056E+12 0.331725E+11 0.462951E+11 0.218085E+10 0.00 0.950542E+09 0.00 0.00 0.197581E+11 0.770285E+10 0.00
April 0.355257E+11 0.946473E+10 0.135446E+12 0.320993E+11 0.451721E+11 0.476040E+10 0.00 0.103339E+11 0.00 0.00 0.116400E+11 0.746489E+10 0.00
May 0.364258E+11 0.618539E+10 0.140035E+12 0.331706E+11 0.484666E+11 0.719291E+10 0.00 0.356190E+11 0.00 0.00 0.269491E+10 0.770425E+10 0.00
June 0.350174E+11 0.344590E+10 0.135537E+12 0.321014E+11 0.492700E+11 0.824349E+10 0.00 0.754625E+11 0.00 0.00 0.251858E+10 0.745689E+10 0.00
July 0.363002E+11 0.478980E+10 0.139944E+12 0.331681E+11 0.507344E+11 0.876776E+10 0.00 0.877156E+11 0.00 0.00 0.387163E+10 0.771238E+10 0.00
August 0.366916E+11 0.826441E+10 0.140067E+12 0.331720E+11 0.492417E+11 0.798358E+10 0.00 0.593413E+11 0.00 0.00 0.268764E+10 0.770437E+10 0.00
September 0.360553E+11 0.114921E+11 0.135457E+12 0.320998E+11 0.450054E+11 0.472844E+10 0.00 0.110158E+11 0.00 0.00 0.458994E+10 0.746624E+10 0.00
October 0.377021E+11 0.155008E+11 0.139992E+12 0.331701E+11 0.460400E+11 0.259373E+10 0.00 0.148204E+10 0.00 0.00 0.155072E+11 0.770290E+10 0.00
November 0.368352E+11 0.185906E+11 0.135531E+12 0.321010E+11 0.464712E+11 0.114678E+10 0.00 0.153916E+09 0.00 0.00 0.204929E+11 0.744869E+10 0.00
December 0.382827E+11 0.220537E+11 0.139944E+12 0.331693E+11 0.486294E+11 0.140690E+10 0.00 0.144565E+09 0.00 0.00 0.211072E+11 0.771243E+10 0.00
                           
Annual Sum or Average 0.438581E+12 0.149236E+12 0.164846E+13 0.390555E+12 0.566469E+12 0.518598E+11 0.00 0.282698E+12 0.00 0.00 0.144851E+12 0.907420E+11 0.00
Minimum of Months 0.341645E+11 0.344590E+10 0.126445E+12 0.299603E+11 0.427355E+11 0.114678E+10 0.00 0.144565E+09 0.00 0.00 0.251858E+10 0.696185E+10 0.00
Maximum of Months 0.382827E+11 0.220537E+11 0.140067E+12 0.331725E+11 0.507344E+11 0.876776E+10 0.00 0.877156E+11 0.00 0.00 0.211760E+11 0.771243E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.603863E+12 0.00 0.264750E+12 0.00 0.00
February 0.137204E+12 0.00 0.473130E+12 0.00 0.239233E+12 0.00 0.00
March 0.152024E+12 0.00 0.260072E+12 0.00 0.264948E+12 0.00 0.00
April 0.146956E+12 0.00 0.800144E+11 0.00 0.256321E+12 0.00 0.00
May 0.151978E+12 0.00 0.423458E+11 0.00 0.264124E+12 0.00 0.00
June 0.147114E+12 0.00 0.329193E+10 0.00 0.252071E+12 0.00 0.00
July 0.151820E+12 0.00 0.151723E+10 0.00 0.256770E+12 0.00 0.00
August 0.152039E+12 0.00 0.102208E+11 0.00 0.254551E+12 0.00 0.00
September 0.146971E+12 0.00 0.804311E+11 0.00 0.245993E+12 0.00 0.00
October 0.151903E+12 0.00 0.139914E+12 0.00 0.255903E+12 0.00 0.00
November 0.147091E+12 0.00 0.550111E+12 0.00 0.250810E+12 0.00 0.00
December 0.151820E+12 0.00 0.706039E+12 0.00 0.263154E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.295095E+13 0.00 0.306863E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.151723E+10 0.00 0.239233E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.706039E+12 0.00 0.264948E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 36244.21 02-JAN-20:10 9571.94 01-JAN-00:10 88863.15 02-JAN-07:10 23857.89 02-JAN-07:19 28464.74 12-JAN-19:19 2644.83 12-JAN-09:30 0.00 01-JAN-00:10
February 36244.21 01-FEB-20:10 9571.94 01-FEB-00:10 88863.15 01-FEB-07:10 23857.89 01-FEB-07:19 27245.31 27-FEB-19:10 2187.51 10-FEB-19:10 0.00 01-FEB-00:10
March 36244.21 01-MAR-20:10 9571.94 01-MAR-00:10 88863.15 01-MAR-07:10 23857.89 01-MAR-07:19 25665.87 01-MAR-19:10 2355.92 22-MAR-18:10 0.00 01-MAR-00:10
April 36244.21 03-APR-19:40 9571.94 01-APR-00:10 88863.15 03-APR-06:10 23857.89 03-APR-06:19 26045.89 21-APR-18:10 3530.33 22-APR-16:10 0.00 01-APR-00:10
May 35563.96 02-MAY-19:00 9571.94 01-MAY-00:10 88863.15 01-MAY-06:10 23856.76 16-MAY-06:19 26904.23 19-MAY-18:10 3739.57 31-MAY-18:10 0.00 01-MAY-00:10
June 35226.05 02-JUN-19:00 9571.94 01-JUN-00:10 88863.15 01-JUN-06:10 23856.74 27-JUN-06:19 30214.39 22-JUN-21:00 4214.73 21-JUN-18:10 0.00 01-JUN-00:10
July 35013.71 26-JUL-19:00 9571.94 01-JUL-00:10 88863.15 03-JUL-06:10 23856.79 25-JUL-06:19 30008.74 11-JUL-21:00 4248.43 20-JUL-18:10 0.00 01-JUL-00:10
August 36244.21 29-AUG-19:30 9571.94 01-AUG-00:10 88863.15 01-AUG-06:10 23856.79 31-AUG-06:19 28355.16 11-AUG-18:10 4196.44 11-AUG-16:19 0.00 01-AUG-00:10
September 36244.21 01-SEP-19:30 9571.94 01-SEP-00:10 88863.15 01-SEP-06:10 23857.89 13-SEP-06:19 25794.30 08-SEP-18:10 3563.18 01-SEP-16:10 0.00 01-SEP-00:10
October 36244.21 02-OCT-19:10 9571.94 01-OCT-00:10 88863.15 02-OCT-06:10 23857.89 02-OCT-06:19 25681.72 31-OCT-18:10 2705.56 03-OCT-15:20 0.00 01-OCT-00:10
November 36244.21 01-NOV-19:10 9571.94 01-NOV-00:10 88863.15 01-NOV-06:10 23857.89 01-NOV-06:19 27532.76 30-NOV-19:10 2152.83 01-NOV-18:10 0.00 01-NOV-00:10
December 36244.21 01-DEC-20:10 9571.94 01-DEC-00:10 88863.15 01-DEC-07:10 23857.89 01-DEC-07:19 27505.16 13-DEC-19:10 2132.83 23-DEC-19:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 35013.71   9571.94   88863.15   23856.74   25665.87   2132.83   0.00  
Maximum of Months 36244.21   9571.94   88863.15   23857.89   30214.39   4248.43   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY {Maximum} [W] COGENERATION:ELECTRICITY {TIMESTAMP}
January 2199.71 20-JAN-19:10 0.00 0.00 8265.52 01-JAN-00:10 4738.66 12-JAN-19:10 0.00 01-JAN-00:10
February 3525.91 09-FEB-16:19 0.00 0.00 8265.52 01-FEB-00:10 4738.25 08-FEB-07:19 0.00 01-FEB-00:10
March 5254.92 22-MAR-18:10 0.00 0.00 8265.52 01-MAR-00:10 4738.68 16-MAR-06:00 0.00 01-MAR-00:10
April 36449.44 22-APR-15:20 0.00 0.00 8265.52 01-APR-00:10 4738.62 06-APR-18:10 0.00 01-APR-00:10
May 60703.66 31-MAY-16:10 0.00 0.00 8265.52 27-MAY-03:30 4738.26 24-MAY-06:19 0.00 01-MAY-00:10
June 94037.44 20-JUN-18:10 0.00 0.00 8265.52 03-JUN-15:39 4738.76 01-JUN-18:10 0.00 01-JUN-00:10
July 105233.14 29-JUL-18:10 0.00 0.00 8265.52 06-JUL-15:50 4738.71 13-JUL-18:10 0.00 01-JUL-00:10
August 90004.99 11-AUG-18:10 0.00 0.00 8265.52 02-AUG-15:00 4738.46 17-AUG-18:10 0.00 01-AUG-00:10
September 37019.23 09-SEP-18:10 0.00 0.00 8265.52 08-SEP-05:30 4738.10 28-SEP-18:10 0.00 01-SEP-00:10
October 11369.71 03-OCT-15:20 0.00 0.00 8265.52 01-OCT-00:10 4738.31 25-OCT-06:19 0.00 01-OCT-00:10
November 2703.51 01-NOV-18:10 0.00 0.00 8265.52 01-NOV-00:10 4738.40 17-NOV-19:10 0.00 01-NOV-00:10
December 2512.22 24-DEC-09:09 0.00 0.00 8265.52 01-DEC-00:10 4738.17 14-DEC-07:00 0.00 01-DEC-00:10
                     
Annual Sum or Average     0.00 0.00            
Minimum of Months 2199.71   0.00 0.00 8265.52   4738.10   0.00  
Maximum of Months 105233.14   0.00 0.00 8265.52   4738.76   0.00  



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 194163.91 12-JAN-20:10 36244.21 86131.51 9571.94 19286.46 27082.64 2121.82 0.00 0.00 0.00
February 191715.03 06-FEB-20:30 36244.21 86131.51 9571.94 19289.69 23923.86 2016.23 0.00 566.39 0.00
March 191333.45 06-MAR-20:30 36244.21 86131.51 9571.94 19289.69 23563.74 2003.24 0.00 565.77 0.00
April 198166.78 21-APR-18:10 29934.98 77265.07 0.00 19090.65 26045.89 3456.31 0.00 35074.50 0.00
May 218920.02 30-MAY-19:49 33842.38 86131.51 0.00 19287.73 23920.29 3532.12 0.00 47006.04 0.00
June 276049.69 29-JUN-19:10 33662.73 86131.51 0.00 19284.61 27622.31 4151.21 0.00 91411.67 0.00
July 273050.46 11-JUL-19:10 33662.73 86131.51 0.00 19284.61 28598.57 4156.43 0.00 87950.81 0.00
August 265636.27 11-AUG-19:10 33982.15 86131.51 0.00 19284.73 27476.57 4145.10 0.00 81421.75 0.00
September 196838.89 07-SEP-19:49 36244.21 86131.51 9571.94 19289.69 24183.58 2878.30 0.00 11340.67 0.00
October 191286.75 23-OCT-19:30 36244.21 86131.51 9571.94 19289.69 23499.10 1996.15 0.00 571.48 0.00
November 191524.38 02-NOV-19:49 36244.21 86131.51 9571.94 19289.69 23710.50 2007.60 0.00 599.23 0.00
December 191233.49 14-DEC-20:10 36244.21 86131.51 9571.94 19286.46 25078.38 1170.82 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 191233.49   29934.98 77265.07 0.00 19090.65 23499.10 1170.82 0.00 0.00 0.00
Maximum of Months 276049.69   36244.21 86131.51 9571.94 19289.69 28598.57 4156.43 0.00 91411.67 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 832360.75 12-JAN-09:09 0.00 264387.79 23-JAN-21:40 0.00
February 104248.32 01-FEB-18:10 0.00 723380.51 27-FEB-09:09 0.00 264410.49 28-FEB-21:19 0.00
March 104248.32 01-MAR-18:10 0.00 625459.18 01-MAR-09:09 0.00 264413.01 06-MAR-21:40 0.00
April 104248.32 01-APR-17:10 0.00 211870.32 03-APR-08:09 0.00 264409.05 10-APR-20:49 0.00
May 104248.32 01-MAY-17:10 0.00 142001.61 27-MAY-06:40 0.00 264404.78 01-MAY-20:19 0.00
June 104248.32 01-JUN-17:10 0.00 68716.03 02-JUN-03:00 0.00 261540.59 02-JUN-20:00 0.00
July 104248.32 01-JUL-17:10 0.00 28040.48 31-JUL-03:00 0.00 256874.49 03-JUL-20:00 0.00
August 104248.32 01-AUG-17:10 0.00 104517.56 30-AUG-03:30 0.00 253358.66 01-AUG-20:49 0.00
September 104248.32 01-SEP-17:10 0.00 159302.11 27-SEP-08:09 0.00 252476.39 29-SEP-20:40 0.00
October 104248.32 02-OCT-17:10 0.00 220249.30 27-OCT-08:09 0.00 255924.93 31-OCT-20:19 0.00
November 104248.32 01-NOV-17:10 0.00 695515.99 29-NOV-09:09 0.00 260344.48 30-NOV-21:19 0.00
December 104248.32 01-DEC-18:10 0.00 761680.55 15-DEC-09:09 0.00 264179.58 27-DEC-21:49 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 28040.48   0.00 252476.39   0.00
Maximum of Months 104248.32   0.00 832360.75   0.00 264413.01   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.72 0.17 21.72
June 0.00 0.00 0.00 0.00 0.83 21.75 0.83 21.75
July 0.00 0.00 0.00 0.00 0.50 21.73 0.50 21.73
August 0.00 0.00 0.00 0.00 0.67 21.77 0.67 21.77
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.17 21.75 2.17 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 21.77 0.83 21.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 21.77 0.33 21.77
June 0.00 0.00 0.00 0.00 2.33 21.95 2.33 21.95
July 0.00 0.00 0.00 0.00 1.17 21.91 1.17 21.91
August 0.00 0.00 0.00 0.00 0.17 21.82 0.17 21.82
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.00 21.92 4.00 21.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.33 21.95 2.33 21.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.33 20.45 1.33 20.45 0.00 20.45 0.00 20.45
February 0.17 20.52 0.17 20.52 0.00 20.52 0.00 20.52
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.67 21.72 0.67 21.72
June 0.00 0.00 0.00 0.00 7.83 21.84 7.83 21.84
July 0.00 0.00 0.00 0.00 6.83 21.81 6.83 21.81
August 0.00 0.00 0.00 0.00 2.67 21.73 2.67 21.73
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 20.51 0.67 20.51 0.00 20.51 0.00 20.51
December 1.17 20.51 1.17 20.51 0.00 20.51 0.00 20.51
                 
Annual Sum or Average 3.33 20.49 3.33 20.49 18.00 21.45 18.00 21.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.33 20.52 1.33 20.52 7.83 21.84 7.83 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74
June 0.00 0.00 0.00 0.00 0.67 21.76 0.67 21.76
July 0.00 0.00 0.00 0.00 0.83 21.82 0.83 21.82
August 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.33 21.76 3.33 21.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.82 1.33 21.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.50 21.82 1.50 21.82
June 0.00 0.00 0.00 0.00 3.67 22.01 3.67 22.01
July 0.00 0.00 0.00 0.00 4.83 22.30 4.83 22.30
August 0.00 0.00 0.00 0.00 0.33 21.84 0.33 21.84
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   10.33 22.12 10.33 22.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.83 22.30 4.83 22.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.87 0.17 21.87
June 0.00 0.00 0.00 0.00 1.50 21.79 1.50 21.79
July 0.00 0.00 0.00 0.00 1.50 21.74 1.50 21.74
August 0.00 0.00 0.00 0.00 0.50 21.79 0.50 21.79
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.67 21.77 3.67 21.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 21.87 1.50 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.67 21.86 0.67 21.86
June 0.00 0.00 0.00 0.00 3.50 22.06 3.50 22.06
July 0.00 0.00 0.00 0.00 3.17 21.88 3.17 21.88
August 0.00 0.00 0.00 0.00 0.67 21.82 0.67 21.82
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.00 21.95 8.00 21.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.50 22.06 3.50 22.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.82 0.17 21.82
June 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
July 0.00 0.00 0.00 0.00 0.83 21.74 0.83 21.74
August 0.00 0.00 0.00 0.00 1.33 21.77 1.33 21.77
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.67 21.75 2.67 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.82 1.33 21.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.84 0.00 21.84 0.00 21.84
February 672.00 21.29 208.67 21.23 208.67 21.20
March 744.00 21.23 201.83 21.19 201.83 21.16
April 720.00 21.27 94.83 21.24 94.83 21.22
May 744.00 21.32 0.00 21.32 0.00 21.32
June 720.00 21.49 0.00 21.49 0.00 21.49
July 744.00 22.05 0.00 22.05 0.00 22.05
August 744.00 22.69 0.00 22.69 0.00 22.69
September 720.00 23.05 0.00 23.05 0.00 23.05
October 744.00 23.10 0.00 23.10 0.00 23.10
November 720.00 22.90 0.00 22.90 0.00 22.90
December 744.00 22.46 0.00 22.46 0.00 22.46
             
Annual Sum or Average 8760.00 22.06 505.33 22.01 505.33 21.96
Minimum of Months 672.00 21.23 0.00 21.19 0.00 21.16
Maximum of Months 744.00 23.10 208.67 23.10 208.67 23.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 744.00 21.00 744.00 21.00
February 672.00 21.02 627.33 21.01 627.33 21.01
March 737.50 21.22 505.00 21.13 505.00 21.09
April 632.50 21.69 101.00 21.61 96.17 21.54
May 608.50 22.25 15.17 22.30 0.00 22.30
June 407.50 22.73 122.00 23.02 0.00 23.02
July 386.67 22.60 242.83 23.13 0.00 23.13
August 501.00 22.39 134.00 22.73 0.00 22.73
September 670.00 21.52 19.67 21.55 10.83 21.54
October 737.67 21.09 375.67 21.06 375.67 21.05
November 720.00 21.00 715.00 21.00 715.00 21.00
December 744.00 21.00 744.00 21.00 744.00 21.00
             
Annual Sum or Average 7561.33 21.50 4345.67 21.45 3818.00 21.34
Minimum of Months 386.67 21.00 15.17 21.00 0.00 21.00
Maximum of Months 744.00 22.73 744.00 23.13 744.00 23.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 416.33 21.01 416.33 21.00
February 672.00 21.03 314.50 21.02 314.50 21.02
March 744.00 21.11 159.33 21.09 159.33 21.08
April 720.00 21.64 9.67 21.63 9.67 21.62
May 744.00 22.13 0.00 22.13 0.00 22.13
June 706.00 22.55 0.00 22.55 0.00 22.55
July 705.33 22.53 0.00 22.53 0.00 22.53
August 728.17 22.42 0.00 22.42 0.00 22.42
September 720.00 21.74 0.00 21.74 0.00 21.74
October 744.00 21.23 45.00 21.22 45.00 21.21
November 720.00 21.01 400.17 21.01 400.17 21.01
December 744.00 21.00 517.50 21.00 517.50 21.00
             
Annual Sum or Average 8691.50 21.61 1862.50 21.51 1862.50 21.43
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.55 517.50 22.55 517.50 22.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.03 657.83 21.02 657.83 21.01
February 672.00 21.10 491.17 21.06 491.17 21.04
March 744.00 21.33 361.83 21.23 361.83 21.17
April 720.00 22.67 63.83 22.53 63.83 22.42
May 744.00 23.87 0.00 23.87 0.00 23.87
June 549.00 24.00 1.17 24.00 0.00 24.00
July 166.00 23.99 1.17 23.99 0.00 23.99
August 373.83 23.96 0.00 23.96 0.00 23.96
September 720.00 23.54 0.00 23.54 0.00 23.54
October 744.00 22.18 115.00 22.02 115.00 21.90
November 720.00 21.03 659.33 21.02 659.33 21.02
December 744.00 21.02 685.33 21.01 685.33 21.01
             
Annual Sum or Average 7640.83 22.26 3036.67 21.91 3034.33 21.71
Minimum of Months 166.00 21.02 0.00 21.01 0.00 21.01
Maximum of Months 744.00 24.00 685.33 24.00 685.33 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 715.00 21.00 715.00 21.00
February 672.00 21.00 602.83 21.00 602.83 21.00
March 744.00 21.00 581.33 21.00 581.33 21.00
April 720.00 21.01 210.33 21.01 210.33 21.00
May 744.00 21.20 0.00 21.20 0.00 21.20
June 720.00 21.73 0.00 21.73 0.00 21.73
July 744.00 21.79 0.00 21.79 0.00 21.79
August 744.00 21.56 0.00 21.56 0.00 21.56
September 720.00 21.04 0.00 21.04 0.00 21.04
October 744.00 21.00 254.17 21.00 254.17 21.00
November 720.00 21.00 707.67 21.00 707.67 21.00
December 744.00 21.00 735.17 21.00 735.17 21.00
             
Annual Sum or Average 8760.00 21.20 3806.50 21.14 3806.50 21.10
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.79 735.17 21.79 735.17 21.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 128.17 24.00 724.83 24.00 128.17 24.00
February 122.67 24.00 656.00 24.00 122.67 24.00
March 149.50 24.00 732.17 24.00 149.50 24.00
April 169.50 24.00 720.00 24.00 169.50 24.00
May 232.17 24.00 744.00 24.00 232.17 24.00
June 330.33 24.00 720.00 24.00 330.33 24.00
July 443.50 24.00 744.00 24.00 443.50 24.00
August 342.50 24.00 744.00 24.00 342.50 24.00
September 235.00 24.00 720.00 24.00 235.00 24.00
October 172.33 24.00 744.00 24.00 172.33 24.00
November 124.17 24.00 702.00 24.00 124.17 24.00
December 125.83 24.00 714.83 24.00 125.83 24.00
             
Annual Sum or Average 2575.67 24.00 8665.83 24.00 2575.67 24.00
Minimum of Months 122.67 24.00 656.00 24.00 122.67 24.00
Maximum of Months 443.50 24.00 744.00 24.00 443.50 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 661.67 21.00 661.67 21.00
February 672.00 21.02 402.33 21.01 402.33 21.01
March 744.00 21.18 144.50 21.15 144.50 21.13
April 681.00 21.66 16.33 21.68 7.83 21.67
May 702.67 21.93 9.83 21.96 0.00 21.96
June 602.00 22.13 24.50 22.18 0.00 22.18
July 536.83 21.99 80.83 22.16 1.00 22.16
August 596.33 21.95 67.17 22.10 2.50 22.10
September 699.00 21.59 3.33 21.60 0.00 21.60
October 742.00 21.19 95.17 21.17 95.17 21.15
November 720.00 21.00 630.17 21.00 630.17 21.00
December 744.00 21.00 701.00 21.00 701.00 21.00
             
Annual Sum or Average 8183.83 21.44 2836.83 21.37 2646.17 21.30
Minimum of Months 536.83 21.00 3.33 21.00 0.00 21.00
Maximum of Months 744.00 22.13 701.00 22.18 701.00 22.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.21 277.17 21.16 277.17 21.12
February 672.00 21.29 159.50 21.24 159.50 21.20
March 744.00 21.53 18.83 21.51 18.83 21.50
April 720.00 22.19 0.00 22.19 0.00 22.19
May 741.67 22.62 0.00 22.62 0.00 22.62
June 565.83 22.72 23.17 22.76 0.00 22.76
July 478.00 22.59 100.50 22.79 10.33 22.81
August 573.17 22.64 42.00 22.72 4.83 22.72
September 719.50 22.31 0.00 22.31 0.00 22.31
October 744.00 21.73 0.33 21.73 0.33 21.73
November 720.00 21.24 226.50 21.19 226.50 21.15
December 744.00 21.15 331.00 21.11 331.00 21.09
             
Annual Sum or Average 8166.17 21.89 1179.00 21.83 1028.50 21.75
Minimum of Months 478.00 21.15 0.00 21.11 0.00 21.09
Maximum of Months 744.00 22.72 331.00 22.79 331.00 22.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.42 744.00 20.42 744.00 20.42
February 672.00 20.44 672.00 20.44 672.00 20.44
March 744.00 20.64 692.50 20.62 692.50 20.61
April 720.00 21.29 236.50 21.17 236.50 21.10
May 743.50 21.64 2.83 21.63 2.83 21.63
June 698.17 21.68 0.00 21.68 0.00 21.68
July 711.33 21.66 0.00 21.66 0.00 21.66
August 724.33 21.61 0.00 21.61 0.00 21.61
September 720.00 21.22 112.67 21.14 112.67 21.08
October 744.00 20.65 582.33 20.59 582.33 20.57
November 720.00 20.42 720.00 20.42 720.00 20.42
December 744.00 20.41 744.00 20.41 744.00 20.41
             
Annual Sum or Average 8685.33 21.01 4506.83 20.83 4506.83 20.74
Minimum of Months 672.00 20.41 0.00 20.41 0.00 20.41
Maximum of Months 744.00 21.68 744.00 21.68 744.00 21.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.42 744.00 20.42 744.00 20.42
February 672.00 20.42 672.00 20.42 672.00 20.42
March 744.00 20.48 739.67 20.48 739.67 20.48
April 720.00 20.97 359.50 20.86 359.50 20.80
May 716.50 21.64 10.00 21.67 4.50 21.66
June 613.83 21.96 62.67 22.31 0.33 22.31
July 639.00 21.93 59.50 22.19 0.00 22.19
August 691.00 21.78 32.17 21.92 1.83 21.92
September 720.00 21.03 164.83 20.93 164.83 20.86
October 744.00 20.54 654.50 20.50 654.50 20.49
November 720.00 20.42 720.00 20.42 720.00 20.42
December 744.00 20.41 744.00 20.41 744.00 20.41
             
Annual Sum or Average 8468.33 20.97 4962.83 20.84 4805.17 20.74
Minimum of Months 613.83 20.41 10.00 20.41 0.00 20.41
Maximum of Months 744.00 21.96 744.00 22.31 744.00 22.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.56 743.00 20.56 743.00 20.56
February 672.00 20.62 654.33 20.61 654.33 20.61
March 744.00 20.76 632.17 20.74 632.17 20.72
April 720.00 21.12 233.67 21.06 233.67 21.02
May 744.00 21.59 0.00 21.59 0.00 21.59
June 719.50 22.03 0.00 22.03 0.00 22.03
July 737.33 22.04 0.00 22.04 0.00 22.04
August 744.00 21.81 0.00 21.81 0.00 21.81
September 720.00 21.25 25.83 21.23 25.83 21.21
October 744.00 20.90 384.00 20.82 384.00 20.78
November 720.00 20.56 720.00 20.56 720.00 20.56
December 744.00 20.55 740.67 20.55 740.67 20.54
             
Annual Sum or Average 8752.83 21.15 4133.67 20.98 4133.67 20.89
Minimum of Months 672.00 20.55 0.00 20.55 0.00 20.54
Maximum of Months 744.00 22.04 743.00 22.04 743.00 22.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.42 744.00 20.42 744.00 20.42
February 672.00 20.46 669.50 20.46 669.50 20.46
March 744.00 20.85 609.50 20.80 609.50 20.78
April 720.00 21.45 215.33 21.33 215.33 21.25
May 738.00 21.73 1.50 21.73 1.50 21.73
June 676.00 21.67 0.00 21.67 0.00 21.67
July 656.00 21.56 0.83 21.57 0.00 21.57
August 692.33 21.62 0.00 21.62 0.00 21.62
September 720.00 21.37 76.67 21.31 76.67 21.26
October 744.00 20.74 528.50 20.66 528.50 20.63
November 720.00 20.42 720.00 20.42 720.00 20.42
December 744.00 20.41 744.00 20.41 744.00 20.41
             
Annual Sum or Average 8570.33 21.05 4309.83 20.87 4309.00 20.78
Minimum of Months 656.00 20.41 0.00 20.41 0.00 20.41
Maximum of Months 744.00 21.73 744.00 21.73 744.00 21.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.42 744.00 20.42 744.00 20.42
February 672.00 20.43 672.00 20.43 672.00 20.43
March 744.00 20.60 693.33 20.59 693.33 20.58
April 720.00 21.17 310.17 21.05 310.17 20.99
May 741.50 21.87 2.33 21.86 2.33 21.86
June 666.00 22.12 8.83 22.16 0.00 22.16
July 618.67 21.99 42.17 22.19 3.33 22.22
August 723.67 21.97 1.83 21.98 0.00 21.98
September 720.00 21.21 133.83 21.13 133.83 21.06
October 744.00 20.62 588.83 20.56 588.83 20.54
November 720.00 20.42 720.00 20.42 720.00 20.42
December 744.00 20.41 744.00 20.41 744.00 20.41
             
Annual Sum or Average 8557.83 21.08 4661.33 20.89 4611.83 20.79
Minimum of Months 618.67 20.41 1.83 20.41 0.00 20.41
Maximum of Months 744.00 22.12 744.00 22.19 744.00 22.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 635.83 21.00 635.83 21.00
February 672.00 21.00 518.67 21.00 518.67 21.00
March 744.00 21.00 450.83 21.00 450.83 21.00
April 720.00 21.26 93.67 21.23 93.67 21.21
May 744.00 22.03 0.00 22.03 0.00 22.03
June 720.00 22.70 0.00 22.70 0.00 22.70
July 744.00 22.69 0.00 22.69 0.00 22.69
August 744.00 22.32 0.00 22.32 0.00 22.32
September 720.00 21.28 2.33 21.28 2.33 21.27
October 744.00 21.01 217.33 21.00 217.33 21.00
November 720.00 21.00 636.00 21.00 636.00 21.00
December 744.00 21.00 685.33 21.00 685.33 21.00
             
Annual Sum or Average 8760.00 21.53 3240.00 21.39 3240.00 21.30
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.70 685.33 22.70 685.33 22.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.41 744.00 20.41 744.00 20.41
February 672.00 20.42 672.00 20.42 672.00 20.42
March 744.00 20.54 713.17 20.53 713.17 20.52
April 719.50 21.20 319.00 21.06 319.00 20.99
May 741.50 21.61 18.50 21.59 18.50 21.57
June 682.00 21.63 0.00 21.63 0.00 21.63
July 684.17 21.58 0.00 21.58 0.00 21.58
August 707.33 21.54 8.83 21.53 8.83 21.53
September 720.00 21.13 192.50 21.02 192.50 20.95
October 744.00 20.56 674.33 20.53 674.33 20.52
November 720.00 20.41 720.00 20.41 720.00 20.41
December 744.00 20.41 744.00 20.41 744.00 20.41
             
Annual Sum or Average 8622.50 20.95 4806.33 20.78 4806.33 20.70
Minimum of Months 672.00 20.41 0.00 20.41 0.00 20.41
Maximum of Months 744.00 21.63 744.00 21.63 744.00 21.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.41 744.00 20.41 744.00 20.41
February 672.00 20.41 672.00 20.41 672.00 20.41
March 744.00 20.44 742.50 20.44 742.50 20.44
April 720.00 20.89 434.17 20.79 434.17 20.74
May 705.50 21.59 45.33 21.66 28.17 21.63
June 606.00 22.04 81.33 22.51 15.33 22.62
July 618.17 21.89 75.50 22.26 1.50 22.27
August 676.83 21.73 65.50 21.94 22.17 21.92
September 720.00 20.92 246.83 20.81 246.83 20.75
October 744.00 20.48 725.50 20.47 725.50 20.47
November 720.00 20.41 720.00 20.41 720.00 20.41
December 744.00 20.41 744.00 20.41 744.00 20.41
             
Annual Sum or Average 8414.50 20.94 5296.67 20.83 5096.17 20.73
Minimum of Months 606.00 20.41 45.33 20.41 1.50 20.41
Maximum of Months 744.00 22.04 744.00 22.51 744.00 22.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.43 744.00 20.43 744.00 20.43
February 672.00 20.68 629.67 20.64 629.67 20.63
March 744.00 21.14 535.83 21.01 535.83 20.95
April 703.00 21.51 153.00 21.41 153.00 21.34
May 710.50 21.62 1.00 21.62 1.00 21.62
June 654.33 21.58 0.00 21.58 0.00 21.58
July 662.83 21.55 2.50 21.55 0.00 21.55
August 684.67 21.57 2.67 21.58 0.00 21.58
September 702.83 21.42 41.00 21.38 41.00 21.35
October 742.00 20.94 460.33 20.83 460.33 20.78
November 720.00 20.46 716.50 20.46 716.50 20.46
December 744.00 20.42 744.00 20.42 744.00 20.42
             
Annual Sum or Average 8484.17 21.10 4030.50 20.93 4025.33 20.84
Minimum of Months 654.33 20.42 0.00 20.42 0.00 20.42
Maximum of Months 744.00 21.62 744.00 21.62 744.00 21.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.41 193.67 21.33 193.67 21.27
February 672.00 21.45 124.83 21.38 124.83 21.33
March 744.00 21.60 31.17 21.57 31.17 21.55
April 720.00 21.94 0.00 21.94 0.00 21.94
May 702.00 22.33 0.00 22.33 0.00 22.33
June 411.33 22.16 113.83 22.49 0.00 22.49
July 387.50 22.10 211.33 22.61 9.00 22.63
August 495.00 22.11 82.50 22.33 4.33 22.34
September 702.33 22.06 0.00 22.06 0.00 22.06
October 744.00 21.74 0.00 21.74 0.00 21.74
November 720.00 21.40 156.67 21.33 156.67 21.28
December 744.00 21.36 218.00 21.28 218.00 21.23
             
Annual Sum or Average 7786.17 21.77 1132.00 21.79 737.67 21.73
Minimum of Months 387.50 21.36 0.00 21.28 0.00 21.23
Maximum of Months 744.00 22.33 218.00 22.61 218.00 22.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.61 73.17 21.56 73.17 21.51
February 672.00 21.67 32.50 21.64 32.50 21.61
March 744.00 21.86 3.00 21.86 3.00 21.86
April 702.00 22.22 0.00 22.22 0.00 22.22
May 596.17 22.47 8.67 22.49 0.00 22.49
June 309.67 22.27 237.17 22.91 0.00 22.91
July 260.83 22.21 324.50 22.98 8.50 22.99
August 388.00 22.21 199.00 22.69 4.33 22.69
September 630.33 22.29 12.50 22.32 0.00 22.32
October 734.83 22.03 0.00 22.03 0.00 22.03
November 720.00 21.61 60.33 21.56 60.33 21.52
December 744.00 21.56 93.17 21.50 93.17 21.45
             
Annual Sum or Average 7245.83 21.95 1044.00 22.08 275.00 22.05
Minimum of Months 260.83 21.56 0.00 21.50 0.00 21.45
Maximum of Months 744.00 22.47 324.50 22.98 93.17 22.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 383.17 23.99 700.50 23.99 382.67 23.99
February 377.83 23.99 626.83 23.99 377.83 23.99
March 468.00 23.99 718.50 23.99 468.00 23.99
April 488.83 23.99 720.00 23.99 488.83 23.99
May 540.33 23.99 744.00 23.99 540.33 23.99
June 543.00 23.99 720.00 23.99 543.00 23.99
July 569.50 23.99 744.00 23.99 569.50 23.99
August 557.83 23.99 744.00 23.99 557.83 23.99
September 509.00 23.99 720.00 23.99 509.00 23.99
October 493.83 23.99 744.00 23.99 493.83 23.99
November 377.50 23.99 680.50 23.99 377.50 23.99
December 358.67 23.99 677.83 23.99 358.67 23.99
             
Annual Sum or Average 5667.50 23.99 8540.17 23.99 5667.00 23.99
Minimum of Months 358.67 23.99 626.83 23.99 358.67 23.99
Maximum of Months 569.50 23.99 744.00 23.99 569.50 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 721.00 21.00 721.00 21.00
February 672.00 21.00 602.33 21.00 602.33 21.00
March 744.00 21.02 520.33 21.01 520.33 21.01
April 720.00 21.79 107.17 21.69 107.17 21.61
May 739.83 23.26 0.00 23.26 0.00 23.26
June 215.00 23.73 47.67 23.78 0.00 23.78
July 100.17 23.47 189.00 23.81 0.00 23.81
August 426.17 23.32 24.33 23.35 0.00 23.35
September 720.00 22.03 0.00 22.03 0.00 22.03
October 744.00 21.08 259.00 21.06 259.00 21.04
November 720.00 21.00 716.50 21.00 716.50 21.00
December 744.00 21.00 737.17 21.00 737.17 21.00
             
Annual Sum or Average 7289.17 21.67 3924.50 21.51 3663.50 21.38
Minimum of Months 100.17 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.73 737.17 23.81 737.17 23.81



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.84321 19.42334 -0.3451 7.62181
February 672.00000 21.28645 20.41343 -0.4812 9.99804
March 744.00000 21.22756 22.33145 -0.4851 10.02370
April 720.00000 21.27402 24.37588 -0.4589 9.53253
May 744.00000 21.31936 28.38733 -1.6016 56.41833
June 720.00000 21.49423 43.81127 -1.4435 47.89972
July 744.00000 22.05489 52.17024 -1.1895 34.91402
August 744.00000 22.69293 45.13986 -1.0039 26.48091
September 720.00000 23.05125 33.13593 -0.9540 24.41092
October 744.00000 23.10272 26.27269 0.01861 5.12491
November 720.00000 22.90074 18.12042 -0.0871 5.30290
December 744.00000 22.45747 17.37946 -0.2037 5.99807
           
Annual Sum or Average 8760.00000 22.06375 29.31265 -0.6874 20.37907
Minimum of Months 672.00000 21.22756 17.37946 -1.6016 5.12491
Maximum of Months 744.00000 23.10272 52.17024 0.01861 56.41833



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00138 19.17566 -0.7464 16.85452
February 672.00000 21.01725 19.74647 -0.6743 14.80451
March 744.00000 21.24425 21.46383 -0.5215 11.66128
April 720.00000 21.96691 23.09844 -0.2387 8.20766
May 744.00000 22.56619 26.63189 -1.0607 31.15043
June 720.00000 23.24088 39.97668 -0.7191 17.47206
July 744.00000 23.19279 48.93132 -0.6734 16.41479
August 744.00000 22.87267 44.47889 -0.8268 21.90170
September 720.00000 21.69242 35.15602 -1.3656 45.22648
October 744.00000 21.11818 28.06645 -0.5162 11.09744
November 720.00000 21.00161 18.57080 -0.7319 16.37599
December 744.00000 21.00144 17.50106 -0.7787 17.87915
           
Annual Sum or Average 8760.00000 21.83135 28.63200 -0.7380 19.09241
Minimum of Months 672.00000 21.00138 17.50106 -1.3656 8.20766
Maximum of Months 744.00000 23.24088 48.93132 -0.2387 45.22648



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00797 19.98882 -0.5584 11.62031
February 672.00000 21.03078 20.53213 -0.5330 11.05742
March 744.00000 21.11119 22.34009 -0.4799 9.94700
April 720.00000 21.64024 23.98338 -0.3128 7.47622
May 744.00000 22.13125 27.54774 -1.2342 37.28217
June 720.00000 22.57372 41.70289 -0.9832 25.92703
July 744.00000 22.57885 50.97503 -0.9217 23.49930
August 744.00000 22.43899 45.89741 -1.0074 27.07108
September 720.00000 21.73859 35.44767 -1.3337 42.33815
October 744.00000 21.23382 28.59970 -0.4055 8.63591
November 720.00000 21.01226 19.40827 -0.5517 11.44497
December 744.00000 21.00315 18.29053 -0.5770 12.05143
           
Annual Sum or Average 8760.00000 21.62868 29.62736 -0.7427 19.06444
Minimum of Months 672.00000 21.00315 18.29053 -1.3337 7.47622
Maximum of Months 744.00000 22.57885 50.97503 -0.3128 42.33815



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.99980 13.82422 0.71043 16.43438
February 672.00000 23.99978 14.24254 0.72653 16.93805
March 744.00000 23.99983 15.85067 0.76314 18.08956
April 720.00000 23.99981 17.61065 0.80935 19.55483
May 744.00000 23.99975 21.14261 0.23482 7.76017
June 720.00000 23.99978 34.60629 0.35203 9.22085
July 744.00000 23.99976 43.18910 0.41129 10.18850
August 744.00000 23.99978 38.20696 0.36650 9.48831
September 720.00000 23.99979 27.67521 0.24945 7.93048
October 744.00000 23.99980 21.21165 0.81178 19.64910
November 720.00000 23.99980 13.31470 0.71232 16.47405
December 744.00000 23.99980 12.39144 0.69326 15.91394
           
Annual Sum or Average 8760.00000 23.99979 22.83647 0.56922 13.95319
Minimum of Months 672.00000 23.99975 12.39144 0.23482 7.76017
Maximum of Months 744.00000 23.99983 43.18910 0.81178 19.64910



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00415 22.19849 -0.6517 14.10612
February 672.00000 21.01802 22.76693 -0.5701 12.05233
March 744.00000 21.17611 24.56597 -0.4267 9.31399
April 720.00000 21.75232 26.17664 -0.1869 6.76149
May 744.00000 22.00651 30.02900 -1.1074 31.88768
June 720.00000 22.28205 44.68747 -0.8913 22.74002
July 744.00000 22.28170 54.13163 -0.8308 20.88156
August 744.00000 22.19877 48.87526 -0.9104 24.23301
September 720.00000 21.63779 37.91414 -1.2554 38.86039
October 744.00000 21.19538 30.88469 -0.3941 8.66075
November 720.00000 21.00467 21.62200 -0.6341 13.58537
December 744.00000 21.00413 20.51165 -0.6879 15.10527
           
Annual Sum or Average 8760.00000 21.54981 32.10022 -0.7131 18.20746
Minimum of Months 672.00000 21.00413 20.51165 -1.2554 6.76149
Maximum of Months 744.00000 22.28205 54.13163 -0.1869 38.86039



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.21136 22.39997 -0.4812 10.12034
February 672.00000 21.29153 22.91886 -0.4370 9.33406
March 744.00000 21.52622 24.61557 -0.3441 7.85057
April 720.00000 22.18803 26.14299 -0.1459 5.99283
May 744.00000 22.62613 29.70379 -1.0191 27.48672
June 720.00000 22.92670 43.74085 -0.8108 19.56715
July 744.00000 22.94119 52.77134 -0.7453 17.44293
August 744.00000 22.86224 47.71881 -0.8125 19.76041
September 720.00000 22.31027 37.20629 -1.0975 31.15353
October 744.00000 21.73339 30.60784 -0.2533 6.87996
November 720.00000 21.24067 21.83400 -0.4680 9.84082
December 744.00000 21.15317 20.78904 -0.5123 10.69215
           
Annual Sum or Average 8760.00000 22.00493 31.77054 -0.5948 14.69920
Minimum of Months 672.00000 21.15317 20.78904 -1.0975 5.99283
Maximum of Months 744.00000 22.94119 52.77134 -0.1459 31.15353



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.41734 21.26859 -0.8821 22.05914
February 672.00000 20.43999 22.12512 -0.8342 20.23744
March 744.00000 20.64061 24.02370 -0.7174 16.31606
April 720.00000 21.29480 28.50434 -0.4296 9.92594
May 744.00000 21.63921 34.30979 -1.3794 45.26046
June 720.00000 21.73483 45.90008 -1.2102 36.97211
July 744.00000 21.73040 52.13932 -1.1851 35.79159
August 744.00000 21.65994 49.82462 -1.2645 39.55614
September 720.00000 21.22381 42.61824 -1.5805 55.40413
October 744.00000 20.64907 32.53227 -0.6646 14.90657
November 720.00000 20.41794 20.42408 -0.8753 21.74008
December 744.00000 20.41486 19.68086 -0.9061 22.96973
           
Annual Sum or Average 8760.00000 21.02508 32.84948 -0.9951 28.46730
Minimum of Months 672.00000 20.41486 19.68086 -1.5805 9.92594
Maximum of Months 744.00000 21.73483 52.13932 -0.4296 55.40413



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.41576 21.26952 -0.8882 22.31904
February 672.00000 20.42113 22.16650 -0.8595 21.23063
March 744.00000 20.48035 24.23261 -0.7848 18.57206
April 720.00000 20.97274 28.95888 -0.5360 11.85454
May 744.00000 21.76123 34.14577 -1.3788 45.61532
June 720.00000 22.41555 44.59467 -1.0335 30.96355
July 744.00000 22.29266 51.38459 -1.0416 30.54810
August 744.00000 21.99455 49.47179 -1.2008 37.36334
September 720.00000 21.02697 43.05391 -1.6739 60.12395
October 744.00000 20.54083 32.74934 -0.7066 16.14266
November 720.00000 20.41564 20.43598 -0.8861 22.18504
December 744.00000 20.41432 19.68164 -0.9079 23.04998
           
Annual Sum or Average 8760.00000 21.10030 32.74783 -0.9921 28.35670
Minimum of Months 672.00000 20.41432 19.68164 -1.6739 11.85454
Maximum of Months 744.00000 22.41555 51.38459 -0.5360 60.12395



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.56344 20.06630 -0.7518 17.49309
February 672.00000 20.61662 20.83444 -0.7269 16.67094
March 744.00000 20.76489 22.95069 -0.6623 14.62614
April 720.00000 21.12141 27.96222 -0.5086 10.68741
May 744.00000 21.58935 32.92095 -1.4721 49.54410
June 720.00000 22.03482 43.56627 -1.2234 37.16007
July 744.00000 22.06118 50.31066 -1.1764 35.11879
August 744.00000 21.80570 47.36985 -1.3079 41.26870
September 720.00000 21.24967 41.41783 -1.5780 55.15461
October 744.00000 20.89556 31.40122 -0.5659 12.10344
November 720.00000 20.56291 19.26237 -0.7543 17.52978
December 744.00000 20.54666 18.39731 -0.7705 18.09414
           
Annual Sum or Average 8760.00000 21.15441 31.43987 -0.9594 27.17382
Minimum of Months 672.00000 20.54666 18.39731 -1.5780 10.68741
Maximum of Months 744.00000 22.06118 50.31066 -0.5086 55.15461



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.41843 21.26205 -0.8799 21.97282
February 672.00000 20.46376 22.07792 -0.8202 19.74989
March 744.00000 20.85005 23.75828 -0.6497 14.45067
April 720.00000 21.44817 28.31794 -0.3947 9.46694
May 744.00000 21.74109 34.20473 -1.3032 41.76027
June 720.00000 21.77027 45.39796 -1.1776 35.62874
July 744.00000 21.77236 50.89843 -1.1444 34.12610
August 744.00000 21.73539 48.78179 -1.2203 37.60677
September 720.00000 21.37476 42.24208 -1.5130 52.06144
October 744.00000 20.74117 32.34162 -0.6316 14.11300
November 720.00000 20.41915 20.41791 -0.8748 21.72449
December 744.00000 20.41473 19.67855 -0.9057 22.95640
           
Annual Sum or Average 8760.00000 21.09925 32.51547 -0.9604 27.16716
Minimum of Months 672.00000 20.41473 19.67855 -1.5130 9.46694
Maximum of Months 744.00000 21.77236 50.89843 -0.3947 52.06144



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.41643 21.26459 -0.8860 22.22921
February 672.00000 20.42902 22.13483 -0.8486 20.82470
March 744.00000 20.60244 24.02439 -0.7343 16.90419
April 720.00000 21.16740 28.64688 -0.4943 11.00674
May 744.00000 21.87239 33.94743 -1.3004 41.43389
June 720.00000 22.27358 44.52492 -1.0534 30.28758
July 744.00000 22.34620 50.38619 -0.9965 28.78415
August 744.00000 22.02653 48.57611 -1.1688 35.22741
September 720.00000 21.21048 42.59853 -1.5967 56.18200
October 744.00000 20.61750 32.56713 -0.6768 15.28701
November 720.00000 20.41633 20.43037 -0.8856 22.17083
December 744.00000 20.41416 19.68409 -0.9075 23.03384
           
Annual Sum or Average 8760.00000 21.15400 32.46505 -0.9628 26.96547
Minimum of Months 672.00000 20.41416 19.68409 -1.5967 11.00674
Maximum of Months 744.00000 22.34620 50.38619 -0.4943 56.18200



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.40923 21.56369 -0.9451 24.51736
February 672.00000 20.41678 22.44744 -0.8988 22.63339
March 744.00000 20.53945 24.42419 -0.7867 18.59798
April 720.00000 21.20614 28.99737 -0.4716 11.01303
May 744.00000 21.61229 34.70488 -1.4012 46.50189
June 720.00000 21.72170 46.41792 -1.2145 37.35024
July 744.00000 21.71877 53.11633 -1.1865 36.02741
August 744.00000 21.63075 50.81372 -1.2811 40.53098
September 720.00000 21.12867 43.55024 -1.6417 58.50912
October 744.00000 20.56106 33.19030 -0.7261 16.77478
November 720.00000 20.40974 20.70040 -0.9398 24.23140
December 744.00000 20.40785 19.95131 -0.9701 25.51891
           
Annual Sum or Average 8760.00000 20.98334 33.39508 -1.0394 30.21753
Minimum of Months 672.00000 20.40785 19.95131 -1.6417 11.01303
Maximum of Months 744.00000 21.72170 53.11633 -0.4716 58.50912



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.40813 21.57790 -0.9506 24.76458
February 672.00000 20.41125 22.48254 -0.9207 23.54909
March 744.00000 20.44472 24.57412 -0.8430 20.60770
April 720.00000 20.89427 29.46979 -0.5806 13.08903
May 744.00000 21.77169 34.53347 -1.3905 46.66883
June 720.00000 22.49936 44.88101 -1.0015 30.85206
July 744.00000 22.35044 51.93117 -1.0177 30.33017
August 744.00000 22.02359 50.29203 -1.1974 37.98446
September 720.00000 20.92271 44.04081 -1.7425 63.53648
October 744.00000 20.47845 33.37735 -0.7637 17.97917
November 720.00000 20.40835 20.71109 -0.9497 24.66723
December 744.00000 20.40714 19.96428 -0.9717 25.59455
           
Annual Sum or Average 8760.00000 21.08949 33.22288 -1.0279 29.98776
Minimum of Months 672.00000 20.40714 19.96428 -1.7425 13.08903
Maximum of Months 744.00000 22.49936 51.93117 -0.5806 63.53648



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.43289 23.06266 -0.8695 21.56569
February 672.00000 20.67876 23.78678 -0.7514 17.68301
March 744.00000 21.14181 25.58150 -0.5590 12.83482
April 720.00000 21.55546 30.11686 -0.3366 8.89008
May 744.00000 21.70116 35.39238 -1.3464 44.05754
June 720.00000 21.73861 46.15310 -1.2268 38.08720
July 744.00000 21.74233 51.95162 -1.1892 36.30988
August 744.00000 21.71084 49.31542 -1.2400 38.78830
September 720.00000 21.46710 43.01504 -1.4650 49.84596
October 744.00000 20.94745 33.66154 -0.5675 12.74970
November 720.00000 20.45927 22.26783 -0.8527 20.89118
December 744.00000 20.42015 21.51251 -0.9024 22.83909
           
Annual Sum or Average 8760.00000 21.16881 33.88335 -0.9435 27.09603
Minimum of Months 672.00000 20.42015 21.51251 -1.4650 8.89008
Maximum of Months 744.00000 21.74233 51.95162 -0.3366 49.84596



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.40741 22.11269 -0.4167 9.15051
February 672.00000 21.45415 22.64690 -0.3873 8.70081
March 744.00000 21.59827 24.41263 -0.3097 7.57182
April 720.00000 21.93977 26.14041 -0.1629 6.22978
May 744.00000 22.41328 29.67194 -0.9805 26.21225
June 720.00000 22.72325 43.82187 -0.7431 17.74359
July 744.00000 22.69438 53.12627 -0.6943 16.15186
August 744.00000 22.52934 48.17476 -0.8107 20.07715
September 720.00000 22.09401 37.29902 -1.0917 31.09972
October 744.00000 21.74462 30.42017 -0.2190 6.66062
November 720.00000 21.40330 21.57550 -0.4197 9.15231
December 744.00000 21.36471 20.52773 -0.4451 9.54161
           
Annual Sum or Average 8760.00000 21.95024 31.72890 -0.5576 14.04582
Minimum of Months 672.00000 21.36471 20.52773 -1.0917 6.22978
Maximum of Months 744.00000 22.72325 53.12627 -0.1629 31.09972



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.61372 21.95355 -0.3280 7.92839
February 672.00000 21.67403 22.47623 -0.2964 7.56298
March 744.00000 21.86206 24.18323 -0.2109 6.64999
April 720.00000 22.26363 25.83856 -0.0573 5.77949
May 744.00000 22.70589 29.31922 -0.8533 21.27335
June 720.00000 22.96943 43.28151 -0.6351 14.49583
July 744.00000 22.94066 52.45209 -0.5865 13.14222
August 744.00000 22.78845 47.56081 -0.6973 16.37340
September 720.00000 22.44068 36.74376 -0.9377 24.67244
October 744.00000 22.04781 30.05272 -0.1116 6.06232
November 720.00000 21.61217 21.42679 -0.3306 7.90280
December 744.00000 21.55817 20.40392 -0.3591 8.23786
           
Annual Sum or Average 8760.00000 22.20951 31.37464 -0.4511 11.69034
Minimum of Months 672.00000 21.55817 20.40392 -0.9377 5.77949
Maximum of Months 744.00000 22.96943 52.45209 -0.0573 24.67244



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.98978 22.70438 0.85107 21.58225
February 672.00000 23.99069 22.98266 0.88063 22.80690
March 744.00000 23.99086 24.09732 0.94085 25.19101
April 720.00000 23.99076 25.27726 1.01655 28.27391
May 744.00000 23.99077 28.43586 0.55567 14.93728
June 720.00000 23.99125 41.48829 0.68684 18.12027
July 744.00000 23.99157 49.86471 0.74462 20.04692
August 744.00000 23.99130 45.08731 0.67287 17.87350
September 720.00000 23.99097 34.94602 0.51717 13.79418
October 744.00000 23.99095 29.09569 0.98581 26.78832
November 720.00000 23.99076 22.23399 0.85242 21.61737
December 744.00000 23.99057 21.47955 0.83032 20.85655
           
Annual Sum or Average 8760.00000 23.99085 30.70025 0.79415 20.98169
Minimum of Months 672.00000 23.98978 21.47955 0.51717 13.79418
Maximum of Months 744.00000 23.99157 49.86471 1.01655 28.27391



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00007 16.70811 -0.6356 13.55219
February 672.00000 21.00010 17.25876 -0.6218 13.19905
March 744.00000 21.00006 19.09710 -0.5880 12.31309
April 720.00000 21.00721 21.44568 -0.5216 10.77201
May 744.00000 21.19980 25.62875 -1.5854 55.54614
June 720.00000 21.72625 40.38807 -1.3112 40.93862
July 744.00000 21.79235 50.00797 -1.2297 36.83467
August 744.00000 21.56354 44.86204 -1.3421 42.59077
September 720.00000 21.03899 33.61571 -1.6102 56.90934
October 744.00000 21.00031 25.67032 -0.5188 10.69510
November 720.00000 21.00009 16.11391 -0.6327 13.45545
December 744.00000 21.00009 14.99444 -0.6507 13.94996
           
Annual Sum or Average 8760.00000 21.19568 27.22240 -0.9390 26.79939
Minimum of Months 672.00000 21.00006 14.99444 -1.6102 10.69510
Maximum of Months 744.00000 21.79235 50.00797 -0.5188 56.90934



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00058 21.01464 -0.6013 12.64539
February 672.00000 21.00053 21.61091 -0.5857 12.25304
March 744.00000 21.00091 23.45257 -0.5528 11.44110
April 720.00000 21.26396 25.46823 -0.4525 9.46005
May 744.00000 22.02837 28.79616 -1.3484 42.90336
June 720.00000 22.69800 42.62531 -1.0292 27.53214
July 744.00000 22.69253 51.84191 -0.9719 25.17878
August 744.00000 22.32400 47.34775 -1.1310 32.27401
September 720.00000 21.27591 37.35525 -1.5623 54.32235
October 744.00000 21.00617 29.95480 -0.5132 10.55304
November 720.00000 21.00057 20.47274 -0.6012 12.62882
December 744.00000 21.00060 19.29701 -0.6157 13.00590
           
Annual Sum or Average 8760.00000 21.52826 30.83726 -0.8316 22.05325
Minimum of Months 672.00000 21.00053 19.29701 -1.5623 9.46005
Maximum of Months 744.00000 22.69800 51.84191 -0.4525 54.32235



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00079 20.54915 -0.6465 13.86546
February 672.00000 21.00071 21.19882 -0.6223 13.21686
March 744.00000 21.01992 23.01473 -0.5677 11.83437
April 720.00000 21.79172 24.63751 -0.3297 8.03491
May 744.00000 23.26316 27.10923 -0.9293 23.83307
June 720.00000 23.89636 39.32717 -0.6060 12.83851
July 744.00000 23.88567 48.01533 -0.5493 11.48812
August 744.00000 23.58349 44.03459 -0.6978 15.88152
September 720.00000 22.03317 35.79549 -1.3058 41.12529
October 744.00000 21.07513 29.49403 -0.5055 10.47261
November 720.00000 21.00078 20.03083 -0.6467 13.84490
December 744.00000 21.00085 18.87143 -0.6655 14.38117
           
Annual Sum or Average 8760.00000 22.05310 29.40011 -0.6726 15.88994
Minimum of Months 672.00000 21.00071 18.87143 -1.3058 8.03491
Maximum of Months 744.00000 23.89636 48.01533 -0.3297 41.12529



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.02768 16.34268 -0.6009 12.63646
February 672.00000 21.10466 17.36540 -0.5703 11.98286
March 744.00000 21.33175 19.15932 -0.4945 10.46781
April 720.00000 22.66783 23.36875 -0.1578 6.48233
May 744.00000 23.86858 27.27539 -0.7981 18.51773
June 720.00000 23.99856 37.55828 -0.6504 13.93285
July 744.00000 23.99669 46.07618 -0.5876 12.27646
August 744.00000 23.98105 42.17343 -0.6331 13.50678
September 720.00000 23.53650 35.54681 -0.8567 20.99715
October 744.00000 22.17656 27.15935 -0.2456 7.25413
November 720.00000 21.03450 15.68655 -0.5957 12.48705
December 744.00000 21.01581 14.88103 -0.6170 13.03907
           
Annual Sum or Average 8760.00000 22.48601 26.94831 -0.5673 12.79768
Minimum of Months 672.00000 21.01581 14.88103 -0.8567 6.48233
Maximum of Months 744.00000 23.99856 46.07618 -0.1578 20.99715



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.189109E+09 15397.96 20-JAN-19:04 70.33 0.589249E+09 0.00 0.778358E+09 0.29 3.12 02-JAN-06:50 0.00 0.00
February 0.289370E+09 20985.79 08-FEB-16:14 105.60 0.901657E+09 0.00 0.119103E+10 0.49 3.12 02-FEB-04:50 0.00 0.00
March 0.950542E+09 19266.21 17-MAR-15:14 258.27 0.296182E+10 0.00 0.391236E+10 1.08 3.12 03-MAR-16:16 0.00 0.00
April 0.103339E+11 45904.37 22-APR-15:13 564.65 0.321327E+11 0.00 0.424667E+11 2.44 3.78 22-APR-15:13 0.00 0.00
May 0.356190E+11 62993.23 31-MAY-18:03 733.50 0.110146E+12 0.00 0.145765E+12 3.05 3.84 17-MAY-18:03 0.00 0.00
June 0.754625E+11 101155.30 20-JUN-18:03 717.67 0.244164E+12 0.00 0.319626E+12 3.13 4.13 30-JUN-18:03 0.00 0.00
July 0.877156E+11 115112.99 29-JUL-18:03 742.50 0.288975E+12 0.00 0.376691E+12 3.17 3.94 22-JUL-08:53 0.00 0.00
August 0.593413E+11 96068.09 11-AUG-18:03 739.79 0.190717E+12 0.00 0.250059E+12 3.11 3.85 24-AUG-15:13 0.00 0.00
September 0.110158E+11 45133.91 09-SEP-18:03 551.91 0.337945E+11 0.00 0.448102E+11 2.38 3.67 09-SEP-18:03 0.00 0.00
October 0.148204E+10 18591.24 19-OCT-15:14 337.27 0.461760E+10 0.00 0.609964E+10 1.41 3.12 03-OCT-07:07 0.00 0.00
November 0.153916E+09 17168.25 03-NOV-08:04 55.71 0.479593E+09 0.00 0.633509E+09 0.24 3.12 01-NOV-03:20 0.00 0.00
December 0.144565E+09 17002.31 25-DEC-19:04 55.26 0.450454E+09 0.00 0.595019E+09 0.23 3.12 12-DEC-09:06 0.00 0.00
                         
Annual Sum or Average 0.282698E+12     4932.45 0.909930E+12 0.00 0.119263E+13 1.76     0.00 0.00
Minimum of Months 0.144565E+09 15397.96   55.26 0.450454E+09 0.00 0.595019E+09 0.23 3.12   0.00 0.00
Maximum of Months 0.877156E+11 115112.99   742.50 0.288975E+12 0.00 0.376691E+12 3.17 4.13   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.541046E+12 0.00 743.46 756987.75 12-JAN-09:03 0.00 46.79 59.20 3.72 0.00 0.26 0.97 12-JAN-09:03
February 0.424835E+12 0.00 670.12 677595.23 27-FEB-09:03 0.00 46.08 59.15 3.16 0.00 0.22 0.87 27-FEB-09:03
March 0.234350E+12 0.00 731.18 602535.65 01-MAR-09:03 0.00 45.99 58.45 1.68 0.00 0.11 0.77 01-MAR-09:03
April 0.732842E+11 0.00 644.20 272102.60 03-APR-08:61 0.00 44.22 57.53 0.53 0.00 0.04 0.35 03-APR-08:61
May 0.395136E+11 0.00 520.23 155472.30 27-MAY-08:06 0.00 36.60 52.72 0.16 0.00 0.02 0.20 27-MAY-08:06
June 0.311106E+10 0.00 107.81 64575.28 24-JUN-15:14 0.00 36.20 39.66 0.01 0.00 0.00 0.08 24-JUN-15:14
July 0.141295E+10 0.00 88.76 68811.29 05-JUL-08:04 0.00 40.48 42.87 0.01 0.00 0.00 0.09 05-JUL-08:04
August 0.949900E+10 0.00 212.95 143093.54 30-AUG-08:05 0.00 41.04 46.25 0.04 0.00 0.00 0.18 30-AUG-08:05
September 0.739326E+11 0.00 643.98 264079.69 27-SEP-15:11 0.00 42.71 57.99 0.41 0.00 0.04 0.34 27-SEP-15:11
October 0.126940E+12 0.00 720.92 278021.64 11-OCT-15:11 0.00 45.59 58.22 0.93 0.00 0.06 0.36 11-OCT-15:11
November 0.493647E+12 0.00 720.00 654349.61 29-NOV-09:03 0.00 46.47 59.42 3.45 0.00 0.24 0.84 29-NOV-09:03
December 0.633136E+12 0.00 743.36 704255.43 15-DEC-09:03 0.00 46.54 59.45 4.22 0.00 0.30 0.90 15-DEC-09:03
                           
Annual Sum or Average 0.265471E+13 0.00 6546.99     0.00 43.21 54.21 1.52 0.00 0.11    
Minimum of Months 0.141295E+10 0.00 88.76 64575.28   0.00 36.20 39.66 0.01 0.00 0.00 0.08  
Maximum of Months 0.633136E+12 0.00 743.46 756987.75   0.00 46.79 59.45 4.22 0.00 0.30 0.97  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 87351700.33 0.00 68.68 87351700.33 0.00 0.00 0.00 0.00 4696.23 20-JAN-06:10 4696.23 20-JAN-06:10 0.00 0.00 0.00
February 0.103383E+09 0.00 100.75 0.103383E+09 0.00 0.00 0.00 0.00 4750.14 07-FEB-06:10 4750.14 07-FEB-06:10 0.00 0.00 0.00
March 0.185438E+09 0.00 162.92 0.185438E+09 0.00 0.00 0.00 0.00 4816.58 21-MAR-05:10 4816.58 21-MAR-05:10 0.00 0.00 0.00
April 0.834694E+09 0.00 220.51 0.834694E+09 0.00 0.00 0.00 0.00 25396.29 21-APR-17:40 25396.29 21-APR-17:40 0.00 0.00 0.00
May 0.358649E+11 0.00 213.67 0.358649E+11 0.00 0.00 0.00 0.00 157757.01 31-MAY-18:00 157757.01 31-MAY-18:00 0.00 0.00 0.00
June 0.130877E+12 0.00 442.83 0.129765E+12 0.00 0.00 0.00 0.00 223897.91 29-JUN-20:00 208383.66 29-JUN-19:10 0.00 0.00 0.00
July 0.165079E+12 0.00 484.33 0.162140E+12 0.00 0.00 0.00 0.00 248848.44 29-JUL-17:15 215391.05 29-JUL-17:15 0.00 0.00 0.00
August 0.981671E+11 0.00 366.58 0.979905E+11 0.00 0.00 0.00 0.00 201476.93 11-AUG-18:10 201476.93 11-AUG-18:10 0.00 0.00 0.00
September 0.540210E+10 0.00 113.77 0.540210E+10 0.00 0.00 0.00 0.00 64660.01 02-SEP-18:00 64660.01 02-SEP-18:00 0.00 0.00 0.00
October 0.250005E+09 0.00 235.93 0.250005E+09 0.00 0.00 0.00 0.00 4934.60 17-OCT-05:10 4934.60 17-OCT-05:10 0.00 0.00 0.00
November 62665274.76 0.00 53.95 62665274.76 0.00 0.00 0.00 0.00 4717.66 14-NOV-06:10 4717.66 14-NOV-06:10 0.00 0.00 0.00
December 63520886.61 0.00 54.23 63520886.61 0.00 0.00 0.00 0.00 4668.10 26-DEC-06:10 4668.10 26-DEC-06:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.436978E+12 0.00 2518.16 0.432750E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 62665274.76 0.00 53.95 62665274.76 0.00 0.00 0.00 0.00 4668.10   4668.10   0.00 0.00 0.00
Maximum of Months 0.165079E+12 0.00 484.33 0.162140E+12 0.00 0.00 0.00 0.00 248848.44   215391.05   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 0.00 0.00
April 2616970.02 0.00 2.17 2616970.02 0.00 0.00 0.00 0.00 594.90 22-APR-14:20 594.90 22-APR-14:20 0.00 0.00 0.00
May 0.174643E+10 0.00 109.67 0.174643E+10 0.00 0.00 0.00 0.00 14983.87 31-MAY-16:00 14983.87 31-MAY-16:00 0.00 0.00 0.00
June 0.830878E+10 0.00 304.50 0.823241E+10 0.00 0.00 0.00 0.00 19908.50 30-JUN-12:15 17979.45 20-JUN-18:02 0.00 0.00 0.00
July 0.101060E+11 0.00 335.83 0.992615E+10 0.00 0.00 0.00 0.00 19631.44 29-JUL-18:02 19080.36 29-JUL-15:12 0.00 0.00 0.00
August 0.608464E+10 0.00 240.33 0.604499E+10 0.00 0.00 0.00 0.00 17533.26 11-AUG-18:02 17533.26 11-AUG-18:02 0.00 0.00 0.00
September 0.172724E+09 0.00 27.67 0.172724E+09 0.00 0.00 0.00 0.00 4990.84 07-SEP-16:00 4990.84 07-SEP-16:00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.264212E+11 0.00 1020.17 0.261253E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.101060E+11 0.00 335.83 0.992615E+10 0.00 0.00 0.00 0.00 19908.50   19080.36   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 4608682.80 0.00 0.91 4608682.80 0.00 0.00 0.00 0.00 3229.51 19-JAN-09:04 3229.51 19-JAN-09:04 0.00 0.00 0.00
February 11000270.97 0.00 1.40 10921488.36 0.00 0.00 0.00 0.00 3808.31 10-FEB-19:04 3808.31 10-FEB-19:04 0.00 0.00 0.00
March 46684737.04 0.00 12.88 46684737.04 0.00 0.00 0.00 0.00 12677.59 22-MAR-15:12 12677.59 22-MAR-15:12 0.00 0.00 0.00
April 0.136255E+10 0.00 188.64 0.136022E+10 0.00 0.00 0.00 0.00 13545.52 30-APR-18:01 13545.52 30-APR-18:01 0.00 0.00 0.00
May 0.294534E+10 0.00 494.71 0.272686E+10 0.00 0.00 0.00 0.00 13548.44 20-MAY-18:01 13548.44 20-MAY-18:01 0.00 0.00 0.00
June 0.535892E+10 0.00 631.83 0.343469E+10 0.00 0.00 0.00 0.00 13548.75 08-JUN-18:01 13548.75 08-JUN-18:01 0.00 0.00 0.00
July 0.555078E+10 0.00 641.27 0.295453E+10 0.00 0.00 0.00 0.00 13722.13 26-JUL-15:11 12344.23 26-JUL-18:01 0.00 0.00 0.00
August 0.377087E+10 0.00 565.39 0.200908E+10 0.00 0.00 0.00 0.00 13537.49 30-AUG-18:01 13537.49 30-AUG-18:01 0.00 0.00 0.00
September 0.615544E+09 0.00 142.85 0.398093E+09 0.00 0.00 0.00 0.00 13547.59 07-SEP-15:11 13547.59 07-SEP-15:11 0.00 0.00 0.00
October 28437538.84 0.00 5.32 26462600.31 0.00 0.00 0.00 0.00 8959.01 03-OCT-15:12 8959.01 03-OCT-15:12 0.00 0.00 0.00
November 6830437.85 0.00 1.21 6830437.85 0.00 0.00 0.00 0.00 3050.36 04-NOV-08:04 3050.36 04-NOV-08:04 0.00 0.00 0.00
December 2385848.86 0.00 0.40 2385848.86 0.00 0.00 0.00 0.00 2833.82 26-DEC-09:04 2833.82 26-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.197040E+11 0.00 2686.82 0.129814E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2385848.86 0.00 0.40 2385848.86 0.00 0.00 0.00 0.00 2833.82   2833.82   0.00 0.00 0.00
Maximum of Months 0.555078E+10 0.00 641.27 0.343469E+10 0.00 0.00 0.00 0.00 13722.13   13548.75   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2211751.28 0.00 0.43 2211751.28 0.00 0.00 0.00 0.00 2692.71 23-JAN-09:04 2692.71 23-JAN-09:04 0.00 0.00 0.00
February 7175758.99 0.00 0.81 7113023.63 0.00 0.00 0.00 0.00 3919.77 08-FEB-19:04 3919.77 08-FEB-19:04 0.00 0.00 0.00
March 17421241.36 0.00 1.91 17421241.36 0.00 0.00 0.00 0.00 4427.53 20-MAR-15:13 4427.53 20-MAR-15:13 0.00 0.00 0.00
April 0.680671E+09 0.00 108.53 0.680445E+09 0.00 0.00 0.00 0.00 12304.20 30-APR-18:01 12304.20 30-APR-18:01 0.00 0.00 0.00
May 0.153731E+10 0.00 344.68 0.137298E+10 0.00 0.00 0.00 0.00 13538.98 09-MAY-20:01 13538.98 09-MAY-20:01 0.00 0.00 0.00
June 0.345310E+10 0.00 453.47 0.194445E+10 0.00 0.00 0.00 0.00 13100.82 28-JUN-21:51 12431.28 01-JUN-18:41 0.00 0.00 0.00
July 0.360760E+10 0.00 461.58 0.183157E+10 0.00 0.00 0.00 0.00 12901.88 15-JUL-20:41 11957.26 06-JUL-17:51 0.00 0.00 0.00
August 0.190353E+10 0.00 378.71 0.842898E+09 0.00 0.00 0.00 0.00 12479.88 12-AUG-21:52 12297.21 30-AUG-18:01 0.00 0.00 0.00
September 0.205590E+09 0.00 71.80 0.114094E+09 0.00 0.00 0.00 0.00 12303.44 07-SEP-18:01 12303.44 07-SEP-18:01 0.00 0.00 0.00
October 21977729.50 0.00 2.47 20503974.40 0.00 0.00 0.00 0.00 4872.85 02-OCT-15:13 4436.24 07-OCT-18:03 0.00 0.00 0.00
November 3253402.82 0.00 0.57 3253402.82 0.00 0.00 0.00 0.00 2998.17 04-NOV-08:04 2998.17 04-NOV-08:04 0.00 0.00 0.00
December 1449015.91 0.00 0.29 1449015.91 0.00 0.00 0.00 0.00 3214.94 26-DEC-09:04 3214.94 26-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.114413E+11 0.00 1825.24 0.683838E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1449015.91 0.00 0.29 1449015.91 0.00 0.00 0.00 0.00 2692.71   2692.71   0.00 0.00 0.00
Maximum of Months 0.360760E+10 0.00 461.58 0.194445E+10 0.00 0.00 0.00 0.00 13538.98   13538.98   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 0.00 0.00
April 0.146325E+11 0.00 286.57 0.146325E+11 0.00 0.00 0.00 0.00 41975.69 22-APR-13:30 41975.69 22-APR-13:30 0.00 0.00 0.00
May 0.276434E+11 0.00 581.64 0.276434E+11 0.00 0.00 0.00 0.00 41295.22 12-MAY-13:30 41295.22 12-MAY-13:30 0.00 0.00 0.00
June 0.348803E+11 0.00 695.43 0.209544E+11 0.00 0.00 0.00 0.00 40645.71 30-JUN-12:30 35572.13 08-JUN-12:30 0.00 0.00 0.00
July 0.373348E+11 0.00 712.83 0.157987E+11 0.00 0.00 0.00 0.00 45877.64 23-JUL-13:15 38144.71 23-JUL-13:30 0.00 0.00 0.00
August 0.328931E+11 0.00 669.76 0.162646E+11 0.00 0.00 0.00 0.00 47818.28 25-AUG-13:30 41902.38 25-AUG-13:30 0.00 0.00 0.00
September 0.118772E+11 0.00 330.49 0.100059E+11 0.00 0.00 0.00 0.00 38527.63 09-SEP-13:20 38527.63 09-SEP-13:20 0.00 0.00 0.00
October 0.577217E+09 0.00 34.17 0.577217E+09 0.00 0.00 0.00 0.00 21163.58 03-OCT-13:30 21163.58 03-OCT-13:30 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.159839E+12 0.00 3310.88 0.105877E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.373348E+11 0.00 712.83 0.276434E+11 0.00 0.00 0.00 0.00 47818.28   41975.69   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 36161717.16 0.00 0.79 36161717.16 0.00 0.00 0.00 0.00 32280.28 20-JAN-19:04 32280.28 20-JAN-19:04 0.00 0.00 0.00
February 57867562.47 0.00 1.00 57521397.08 0.00 0.00 0.00 0.00 32028.52 08-FEB-16:14 32028.52 08-FEB-16:14 0.00 0.00 0.00
March 0.149822E+09 0.00 13.06 0.149822E+09 0.00 0.00 0.00 0.00 61997.67 18-MAR-08:61 61997.67 18-MAR-08:61 0.00 0.00 0.00
April 0.446122E+10 0.00 178.88 0.444555E+10 0.00 0.00 0.00 0.00 69726.35 30-APR-18:01 69726.35 30-APR-18:01 0.00 0.00 0.00
May 0.199647E+11 0.00 437.55 0.188851E+11 0.00 0.00 0.00 0.00 72864.55 31-MAY-21:51 72864.55 31-MAY-21:51 0.00 0.00 0.00
June 0.333085E+11 0.00 399.18 0.250834E+11 0.00 0.00 0.00 0.00 74731.98 30-JUN-21:51 74534.35 07-JUN-21:51 0.00 0.00 0.00
July 0.365626E+11 0.00 418.50 0.245736E+11 0.00 0.00 0.00 0.00 76913.26 18-JUL-21:52 67986.82 19-JUL-21:51 0.00 0.00 0.00
August 0.246505E+11 0.00 387.70 0.152509E+11 0.00 0.00 0.00 0.00 74521.90 12-AUG-21:52 72898.03 10-AUG-21:51 0.00 0.00 0.00
September 0.739206E+10 0.00 320.87 0.425039E+10 0.00 0.00 0.00 0.00 69207.21 10-SEP-18:01 69207.21 10-SEP-18:01 0.00 0.00 0.00
October 0.999519E+09 0.00 63.52 0.854260E+09 0.00 0.00 0.00 0.00 66526.12 04-OCT-18:03 66526.12 04-OCT-18:03 0.00 0.00 0.00
November 33170728.57 0.00 0.67 33170728.57 0.00 0.00 0.00 0.00 31165.12 06-NOV-19:04 31165.12 06-NOV-19:04 0.00 0.00 0.00
December 25713656.01 0.00 0.74 25713656.01 0.00 0.00 0.00 0.00 30510.57 24-DEC-09:01 30510.57 24-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.127642E+12 0.00 2222.46 0.936455E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 25713656.01 0.00 0.67 25713656.01 0.00 0.00 0.00 0.00 30510.57   30510.57   0.00 0.00 0.00
Maximum of Months 0.365626E+11 0.00 437.55 0.250834E+11 0.00 0.00 0.00 0.00 76913.26   74534.35   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3325109.40 0.00 0.69 3325109.40 0.00 0.00 0.00 0.00 2619.00 19-JAN-09:04 2619.00 19-JAN-09:04 0.00 0.00 0.00
February 12320205.61 0.00 1.38 12245938.93 0.00 0.00 0.00 0.00 3708.11 08-FEB-19:04 3708.11 08-FEB-19:04 0.00 0.00 0.00
March 57982453.18 0.00 17.78 57982453.18 0.00 0.00 0.00 0.00 12180.81 22-MAR-15:12 12180.81 22-MAR-15:12 0.00 0.00 0.00
April 0.116430E+10 0.00 228.65 0.114764E+10 0.00 0.00 0.00 0.00 12787.89 22-APR-08:61 12787.89 22-APR-08:61 0.00 0.00 0.00
May 0.427297E+10 0.00 579.23 0.395459E+10 0.00 0.00 0.00 0.00 12788.13 12-MAY-08:62 12788.13 12-MAY-08:62 0.00 0.00 0.00
June 0.611175E+10 0.00 660.81 0.401220E+10 0.00 0.00 0.00 0.00 12788.06 08-JUN-18:01 12788.06 08-JUN-18:01 0.00 0.00 0.00
July 0.683809E+10 0.00 676.46 0.399349E+10 0.00 0.00 0.00 0.00 12764.18 26-JUL-15:11 11639.13 27-JUL-08:62 0.00 0.00 0.00
August 0.459829E+10 0.00 613.88 0.258945E+10 0.00 0.00 0.00 0.00 12787.71 10-AUG-18:01 12787.71 10-AUG-18:01 0.00 0.00 0.00
September 0.851609E+09 0.00 207.58 0.499310E+09 0.00 0.00 0.00 0.00 12788.74 10-SEP-15:11 12788.74 10-SEP-15:11 0.00 0.00 0.00
October 47846380.83 0.00 15.91 38657787.80 0.00 0.00 0.00 0.00 12156.77 04-OCT-08:62 12156.77 04-OCT-08:62 0.00 0.00 0.00
November 5040917.11 0.00 0.98 5040917.11 0.00 0.00 0.00 0.00 2851.07 04-NOV-08:04 2851.07 04-NOV-08:04 0.00 0.00 0.00
December 1855226.38 0.00 0.33 1855226.38 0.00 0.00 0.00 0.00 3041.50 26-DEC-09:04 3041.50 26-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.239654E+11 0.00 3003.68 0.163158E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1855226.38 0.00 0.33 1855226.38 0.00 0.00 0.00 0.00 2619.00   2619.00   0.00 0.00 0.00
Maximum of Months 0.683809E+10 0.00 676.46 0.401220E+10 0.00 0.00 0.00 0.00 12788.74   12788.74   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1356905.63 0.00 0.33 1356905.63 0.00 0.00 0.00 0.00 2878.93 23-JAN-09:04 2878.93 23-JAN-09:04 0.00 0.00 0.00
February 7624026.57 0.00 0.86 7581763.16 0.00 0.00 0.00 0.00 4160.73 08-FEB-19:04 4160.73 08-FEB-19:04 0.00 0.00 0.00
March 20400110.58 0.00 6.03 20400110.58 0.00 0.00 0.00 0.00 4879.69 18-MAR-08:03 4879.69 18-MAR-08:03 0.00 0.00 0.00
April 0.453030E+09 0.00 109.33 0.442225E+09 0.00 0.00 0.00 0.00 11639.93 22-APR-08:61 11639.93 22-APR-08:61 0.00 0.00 0.00
May 0.288717E+10 0.00 461.11 0.264366E+10 0.00 0.00 0.00 0.00 11780.93 14-MAY-20:41 11780.93 14-MAY-20:41 0.00 0.00 0.00
June 0.445524E+10 0.00 505.69 0.283304E+10 0.00 0.00 0.00 0.00 11968.70 30-JUN-21:51 11648.29 01-JUN-18:41 0.00 0.00 0.00
July 0.485034E+10 0.00 516.38 0.283365E+10 0.00 0.00 0.00 0.00 12705.35 22-JUL-08:32 12705.35 22-JUL-08:32 0.00 0.00 0.00
August 0.280024E+10 0.00 449.63 0.148935E+10 0.00 0.00 0.00 0.00 11821.49 12-AUG-21:52 11637.77 31-AUG-08:61 0.00 0.00 0.00
September 0.358164E+09 0.00 106.66 0.200411E+09 0.00 0.00 0.00 0.00 11321.36 10-SEP-15:11 11321.36 10-SEP-15:11 0.00 0.00 0.00
October 23536400.53 0.00 4.35 19298119.83 0.00 0.00 0.00 0.00 7825.17 04-OCT-08:62 7825.17 04-OCT-08:62 0.00 0.00 0.00
November 2327448.28 0.00 0.36 2327448.28 0.00 0.00 0.00 0.00 3225.75 04-NOV-08:04 3225.75 04-NOV-08:04 0.00 0.00 0.00
December 1036699.80 0.00 0.14 1036699.80 0.00 0.00 0.00 0.00 3149.25 26-DEC-09:04 3149.25 26-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.158605E+11 0.00 2160.87 0.104943E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1036699.80 0.00 0.14 1036699.80 0.00 0.00 0.00 0.00 2878.93   2878.93   0.00 0.00 0.00
Maximum of Months 0.485034E+10 0.00 516.38 0.283365E+10 0.00 0.00 0.00 0.00 12705.35   12705.35   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 153631.71 0.00 0.17 153631.71 0.00 0.00 0.00 0.00 408.93 22-JAN-09:04 408.93 22-JAN-09:04 0.00 0.00 0.00
February 924077.94 0.00 0.81 899351.65 0.00 0.00 0.00 0.00 726.84 09-FEB-09:04 658.63 09-FEB-19:04 0.00 0.00 0.00
March 5863595.27 0.00 9.44 5841398.94 0.00 0.00 0.00 0.00 2710.74 22-MAR-15:12 2710.74 22-MAR-15:12 0.00 0.00 0.00
April 0.351833E+09 0.00 167.98 0.351631E+09 0.00 0.00 0.00 0.00 3510.83 30-APR-18:01 3510.83 30-APR-18:01 0.00 0.00 0.00
May 0.724865E+09 0.00 414.79 0.673018E+09 0.00 0.00 0.00 0.00 3511.60 20-MAY-18:01 3511.60 20-MAY-18:01 0.00 0.00 0.00
June 0.133925E+10 0.00 608.12 0.889633E+09 0.00 0.00 0.00 0.00 3511.55 08-JUN-18:01 3511.55 08-JUN-18:01 0.00 0.00 0.00
July 0.137928E+10 0.00 619.60 0.767782E+09 0.00 0.00 0.00 0.00 3547.69 26-JUL-15:11 3147.03 15-JUL-18:01 0.00 0.00 0.00
August 0.904295E+09 0.00 510.65 0.512826E+09 0.00 0.00 0.00 0.00 3642.58 13-AUG-08:61 3511.36 10-AUG-18:01 0.00 0.00 0.00
September 0.143862E+09 0.00 112.17 98333415.46 0.00 0.00 0.00 0.00 3511.48 07-SEP-15:11 3511.48 07-SEP-15:11 0.00 0.00 0.00
October 5664839.81 0.00 4.17 4962917.24 0.00 0.00 0.00 0.00 2290.86 03-OCT-15:12 2290.86 03-OCT-15:12 0.00 0.00 0.00
November 84460.09 0.00 0.26 84460.09 0.00 0.00 0.00 0.00 273.00 04-NOV-08:04 273.00 04-NOV-08:04 0.00 0.00 0.00
December 131491.93 0.00 0.17 131491.93 0.00 0.00 0.00 0.00 709.58 24-DEC-09:04 709.58 24-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.485621E+10 0.00 2448.33 0.330530E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 84460.09 0.00 0.17 84460.09 0.00 0.00 0.00 0.00 273.00   273.00   0.00 0.00 0.00
Maximum of Months 0.137928E+10 0.00 619.60 0.889633E+09 0.00 0.00 0.00 0.00 3642.58   3511.60   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 92742.39 0.00 0.17 92742.39 0.00 0.00 0.00 0.00 279.46 21-JAN-09:04 279.46 21-JAN-09:04 0.00 0.00 0.00
February 702723.05 0.00 0.62 681542.18 0.00 0.00 0.00 0.00 735.65 09-FEB-09:04 581.35 09-FEB-16:14 0.00 0.00 0.00
March 3472623.81 0.00 1.82 3453693.01 0.00 0.00 0.00 0.00 1194.51 20-MAR-15:13 1194.51 20-MAR-15:13 0.00 0.00 0.00
April 0.169823E+09 0.00 94.54 0.169706E+09 0.00 0.00 0.00 0.00 3159.44 30-APR-18:01 3159.44 30-APR-18:01 0.00 0.00 0.00
May 0.348061E+09 0.00 275.33 0.310783E+09 0.00 0.00 0.00 0.00 3611.90 09-MAY-20:01 3611.90 09-MAY-20:01 0.00 0.00 0.00
June 0.880305E+09 0.00 445.74 0.506363E+09 0.00 0.00 0.00 0.00 3364.72 28-JUN-21:51 3219.31 01-JUN-18:41 0.00 0.00 0.00
July 0.909230E+09 0.00 462.64 0.473258E+09 0.00 0.00 0.00 0.00 3492.93 08-JUL-21:51 3237.88 06-JUL-17:32 0.00 0.00 0.00
August 0.434077E+09 0.00 338.18 0.199133E+09 0.00 0.00 0.00 0.00 3267.34 12-AUG-21:52 3157.66 30-AUG-18:01 0.00 0.00 0.00
September 41229499.93 0.00 45.07 24534039.70 0.00 0.00 0.00 0.00 3159.20 07-SEP-18:01 3159.20 07-SEP-18:01 0.00 0.00 0.00
October 4823781.87 0.00 2.38 4411337.59 0.00 0.00 0.00 0.00 1378.76 04-OCT-15:13 1378.76 04-OCT-15:13 0.00 0.00 0.00
November 138625.65 0.00 0.31 138625.65 0.00 0.00 0.00 0.00 388.65 04-NOV-08:04 388.65 04-NOV-08:04 0.00 0.00 0.00
December 111678.42 0.00 0.14 111678.42 0.00 0.00 0.00 0.00 337.62 24-DEC-09:04 337.62 24-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.279207E+10 0.00 1666.93 0.169267E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 92742.39 0.00 0.14 92742.39 0.00 0.00 0.00 0.00 279.46   279.46   0.00 0.00 0.00
Maximum of Months 0.909230E+09 0.00 462.64 0.506363E+09 0.00 0.00 0.00 0.00 3611.90   3611.90   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 7969595.64 0.00 1.31 7969595.64 0.00 0.00 0.00 0.00 4726.94 22-JAN-19:04 4726.94 22-JAN-19:04 0.00 0.00 0.00
February 26674228.27 0.00 4.70 26593858.60 0.00 0.00 0.00 0.00 20601.20 15-FEB-16:11 20601.20 15-FEB-16:11 0.00 0.00 0.00
March 0.807917E+09 0.00 88.46 0.806602E+09 0.00 0.00 0.00 0.00 21526.37 22-MAR-15:12 21526.37 22-MAR-15:12 0.00 0.00 0.00
April 0.382566E+10 0.00 326.62 0.378391E+10 0.00 0.00 0.00 0.00 21529.23 19-APR-18:01 21529.23 19-APR-18:01 0.00 0.00 0.00
May 0.583251E+10 0.00 567.92 0.517224E+10 0.00 0.00 0.00 0.00 21531.45 01-MAY-15:11 21531.45 01-MAY-15:11 0.00 0.00 0.00
June 0.796903E+10 0.00 636.40 0.488927E+10 0.00 0.00 0.00 0.00 21529.98 15-JUN-18:01 21529.98 15-JUN-18:01 0.00 0.00 0.00
July 0.911836E+10 0.00 654.48 0.484881E+10 0.00 0.00 0.00 0.00 21237.41 01-JUL-15:11 19621.17 26-JUL-18:01 0.00 0.00 0.00
August 0.747775E+10 0.00 612.76 0.431753E+10 0.00 0.00 0.00 0.00 21525.08 21-AUG-18:01 21525.08 21-AUG-18:01 0.00 0.00 0.00
September 0.256834E+10 0.00 310.45 0.159088E+10 0.00 0.00 0.00 0.00 21524.00 28-SEP-15:12 21524.00 28-SEP-15:12 0.00 0.00 0.00
October 0.459080E+09 0.00 63.27 0.400411E+09 0.00 0.00 0.00 0.00 21515.60 14-OCT-15:11 21515.60 14-OCT-15:11 0.00 0.00 0.00
November 11502907.80 0.00 1.55 11502907.80 0.00 0.00 0.00 0.00 4054.00 01-NOV-18:04 4054.00 01-NOV-18:04 0.00 0.00 0.00
December 4164008.29 0.00 0.79 4164008.29 0.00 0.00 0.00 0.00 4918.37 24-DEC-19:04 4918.37 24-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.381090E+11 0.00 3268.71 0.258599E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 4164008.29 0.00 0.79 4164008.29 0.00 0.00 0.00 0.00 4054.00   4054.00   0.00 0.00 0.00
Maximum of Months 0.911836E+10 0.00 654.48 0.517224E+10 0.00 0.00 0.00 0.00 21531.45   21531.45   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.62 75.47 36.15 60.82 932.85 0.00 0.00 0.00
February 370.84 260.41 110.43 328.82 747.55 0.00 0.00 0.00
March 620.54 422.70 197.84 680.53 572.22 0.00 0.00 0.00
April 751.50 468.45 283.05 961.14 369.68 0.00 0.00 0.00
May 612.63 315.03 297.60 828.07 190.68 0.00 0.00 0.00
June 554.57 221.80 332.77 779.52 97.92 0.00 0.00 0.00
July 534.97 228.28 306.69 775.78 100.52 0.00 0.00 0.00
August 562.99 310.41 252.58 791.13 151.60 0.00 0.00 0.00
September 453.30 272.37 180.94 559.67 275.26 0.00 0.00 0.00
October 339.98 218.18 121.79 337.97 484.80 0.00 0.00 0.00
November 186.56 133.23 53.33 117.08 870.36 0.00 0.00 0.00
December 33.12 23.70 9.43 4.17 1034.55 0.00 0.00 0.00
                 
Annual Sum or Average 427.54 245.41 182.13 519.35 484.42 0.00 0.00 0.00
Minimum of Months 33.12 23.70 9.43 4.17 97.92 0.00 0.00 0.00
Maximum of Months 751.50 468.45 332.77 961.14 1034.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 314.30 212.52 101.78 169.77 2604.97 0.00 0.00 0.00
February 1044.25 733.30 310.96 921.27 2087.04 0.00 0.00 0.00
March 1747.40 1190.30 557.10 1915.52 1596.60 0.00 0.00 0.00
April 2116.17 1319.11 797.05 2718.29 1025.72 0.00 0.00 0.00
May 1725.12 887.11 838.01 2359.53 512.83 0.00 0.00 0.00
June 1561.63 624.56 937.07 2244.66 245.23 0.00 0.00 0.00
July 1506.45 642.81 863.63 2230.86 252.64 0.00 0.00 0.00
August 1585.35 874.11 711.25 2258.62 397.24 0.00 0.00 0.00
September 1276.48 766.96 509.51 1582.84 764.39 0.00 0.00 0.00
October 957.35 614.39 342.96 948.40 1357.32 0.00 0.00 0.00
November 525.33 375.16 150.17 327.02 2429.91 0.00 0.00 0.00
December 93.28 66.73 26.55 11.58 2889.33 0.00 0.00 0.00
                 
Annual Sum or Average 1203.93 691.05 512.88 1475.90 1343.38 0.00 0.00 0.00
Minimum of Months 93.28 66.73 26.55 11.58 245.23 0.00 0.00 0.00
Maximum of Months 2116.17 1319.11 937.07 2718.29 2889.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 408.29 276.07 132.22 217.92 3518.53 0.00 0.00 0.00
February 1356.54 952.59 403.95 1197.62 2818.40 0.00 0.00 0.00
March 2269.98 1546.27 723.70 2507.73 2160.07 0.00 0.00 0.00
April 2749.02 1713.60 1035.42 3565.48 1397.34 0.00 0.00 0.00
May 2241.03 1152.41 1088.63 3083.68 719.81 0.00 0.00 0.00
June 2028.65 811.34 1217.31 2924.58 355.23 0.00 0.00 0.00
July 1956.96 835.05 1121.91 2906.21 366.79 0.00 0.00 0.00
August 2059.46 1135.51 923.95 2946.24 565.72 0.00 0.00 0.00
September 1658.21 996.33 661.88 2063.56 1069.59 0.00 0.00 0.00
October 1243.65 798.13 445.53 1233.38 1862.56 0.00 0.00 0.00
November 682.44 487.36 195.08 421.23 3284.53 0.00 0.00 0.00
December 121.17 86.68 34.49 14.40 3896.49 0.00 0.00 0.00
                 
Annual Sum or Average 1563.97 897.71 666.26 1925.96 1829.88 0.00 0.00 0.00
Minimum of Months 121.17 86.68 34.49 14.40 355.23 0.00 0.00 0.00
Maximum of Months 2749.02 1713.60 1217.31 3565.48 3896.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.07 14.92 7.15 12.28 186.48 0.00 0.00 0.00
February 73.32 51.49 21.83 66.24 149.51 0.00 0.00 0.00
March 122.69 83.58 39.12 136.54 114.88 0.00 0.00 0.00
April 148.58 92.62 55.96 191.57 73.39 0.00 0.00 0.00
May 121.13 62.29 58.84 165.09 36.01 0.00 0.00 0.00
June 109.65 43.85 65.80 157.03 16.35 0.00 0.00 0.00
July 105.77 45.13 60.64 156.59 16.81 0.00 0.00 0.00
August 111.31 61.37 49.94 158.73 26.97 0.00 0.00 0.00
September 89.63 53.85 35.77 112.14 53.90 0.00 0.00 0.00
October 67.22 43.14 24.08 67.85 96.80 0.00 0.00 0.00
November 36.89 26.34 10.54 23.92 173.15 0.00 0.00 0.00
December 6.55 4.69 1.86 0.87 206.58 0.00 0.00 0.00
                 
Annual Sum or Average 84.53 48.52 36.01 104.19 95.65 0.00 0.00 0.00
Minimum of Months 6.55 4.69 1.86 0.87 16.35 0.00 0.00 0.00
Maximum of Months 148.58 92.62 65.80 191.57 206.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4.29 0.64 3.65 0.00 382.51 0.00 0.00 0.00
February 25.73 8.64 17.09 3.86 331.19 0.00 0.00 0.00
March 78.57 33.75 44.82 46.30 244.50 0.00 0.00 0.00
April 188.46 98.57 89.89 204.53 135.11 0.00 0.00 0.00
May 182.79 84.17 98.62 218.43 61.71 0.00 0.00 0.00
June 199.89 86.05 113.84 269.29 28.23 0.00 0.00 0.00
July 166.74 63.50 103.24 229.48 29.73 0.00 0.00 0.00
August 137.62 58.92 78.70 175.08 48.76 0.00 0.00 0.00
September 82.50 34.46 48.04 76.53 105.34 0.00 0.00 0.00
October 31.91 9.28 22.63 11.22 210.75 0.00 0.00 0.00
November 12.70 4.43 8.27 0.84 365.16 0.00 0.00 0.00
December 1.13 0.09 1.04 0.00 401.55 0.00 0.00 0.00
                 
Annual Sum or Average 92.94 40.30 52.64 103.40 194.67 0.00 0.00 0.00
Minimum of Months 1.13 0.09 1.04 0.00 28.23 0.00 0.00 0.00
Maximum of Months 199.89 98.57 113.84 269.29 401.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1.71 0.00 1.71 0.00 205.63 0.00 0.00 0.00
February 7.57 0.00 7.57 0.00 185.55 0.00 0.00 0.00
March 20.27 0.00 20.27 0.92 141.53 0.00 0.00 0.00
April 36.84 0.88 35.97 13.37 75.24 0.00 0.00 0.00
May 55.99 8.46 47.53 48.32 28.24 0.00 0.00 0.00
June 72.83 15.80 57.03 85.41 11.53 0.00 0.00 0.00
July 61.52 9.91 51.61 75.98 13.75 0.00 0.00 0.00
August 39.66 2.11 37.55 38.15 24.92 0.00 0.00 0.00
September 22.00 0.05 21.95 8.40 58.30 0.00 0.00 0.00
October 10.66 0.00 10.66 0.49 117.31 0.00 0.00 0.00
November 3.31 0.00 3.31 0.00 200.90 0.00 0.00 0.00
December 0.52 0.00 0.52 0.00 214.68 0.00 0.00 0.00
                 
Annual Sum or Average 27.84 3.11 24.73 22.73 106.03 0.00 0.00 0.00
Minimum of Months 0.52 0.00 0.52 0.00 11.53 0.00 0.00 0.00
Maximum of Months 72.83 15.80 57.03 85.41 214.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4.29 0.64 3.65 0.00 382.52 0.00 0.00 0.00
February 25.73 8.64 17.09 4.09 330.70 0.00 0.00 0.00
March 78.57 33.75 44.82 47.83 242.67 0.00 0.00 0.00
April 188.46 98.57 89.89 208.57 133.35 0.00 0.00 0.00
May 182.79 84.17 98.62 219.33 61.46 0.00 0.00 0.00
June 199.89 86.05 113.84 265.62 28.74 0.00 0.00 0.00
July 166.74 63.50 103.24 227.05 30.48 0.00 0.00 0.00
August 137.62 58.92 78.70 174.96 49.59 0.00 0.00 0.00
September 82.50 34.46 48.04 78.67 104.04 0.00 0.00 0.00
October 31.91 9.28 22.63 11.95 209.62 0.00 0.00 0.00
November 12.70 4.43 8.27 0.88 364.99 0.00 0.00 0.00
December 1.13 0.09 1.04 0.00 401.53 0.00 0.00 0.00
                 
Annual Sum or Average 92.94 40.30 52.64 103.67 194.26 0.00 0.00 0.00
Minimum of Months 1.13 0.09 1.04 0.00 28.74 0.00 0.00 0.00
Maximum of Months 199.89 98.57 113.84 265.62 401.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 17.65 11.93 5.72 10.82 131.55 0.00 0.00 0.00
February 58.65 41.18 17.46 55.82 105.18 0.00 0.00 0.00
March 98.13 66.85 31.29 110.24 86.57 0.00 0.00 0.00
April 118.84 74.08 44.76 145.66 71.16 0.00 0.00 0.00
May 96.88 49.82 47.06 122.91 41.78 0.00 0.00 0.00
June 87.70 35.08 52.63 114.93 23.01 0.00 0.00 0.00
July 84.60 36.10 48.50 114.75 23.65 0.00 0.00 0.00
August 89.03 49.09 39.94 117.80 34.13 0.00 0.00 0.00
September 71.69 43.07 28.61 82.06 58.64 0.00 0.00 0.00
October 53.76 34.50 19.26 51.25 82.57 0.00 0.00 0.00
November 29.50 21.07 8.43 20.80 121.89 0.00 0.00 0.00
December 5.24 3.75 1.49 0.84 146.80 0.00 0.00 0.00
                 
Annual Sum or Average 67.61 38.81 28.80 79.05 77.11 0.00 0.00 0.00
Minimum of Months 5.24 3.75 1.49 0.84 23.01 0.00 0.00 0.00
Maximum of Months 118.84 74.08 52.63 145.66 146.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1.37 0.00 1.37 0.00 168.30 0.00 0.00 0.00
February 6.06 0.00 6.06 0.00 152.21 0.00 0.00 0.00
March 16.22 0.00 16.22 0.57 116.38 0.00 0.00 0.00
April 29.48 0.70 28.78 10.80 60.77 0.00 0.00 0.00
May 44.80 6.77 38.03 40.10 22.29 0.00 0.00 0.00
June 58.27 12.64 45.63 71.24 8.82 0.00 0.00 0.00
July 49.22 7.93 41.29 62.87 10.60 0.00 0.00 0.00
August 31.73 1.69 30.04 31.83 19.44 0.00 0.00 0.00
September 17.60 0.04 17.56 6.46 47.98 0.00 0.00 0.00
October 8.53 0.00 8.53 0.26 97.30 0.00 0.00 0.00
November 2.65 0.00 2.65 0.00 164.53 0.00 0.00 0.00
December 0.42 0.00 0.42 0.00 175.56 0.00 0.00 0.00
                 
Annual Sum or Average 22.27 2.49 19.78 18.79 86.66 0.00 0.00 0.00
Minimum of Months 0.42 0.00 0.42 0.00 8.82 0.00 0.00 0.00
Maximum of Months 58.27 12.64 45.63 71.24 175.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.19 3.23 5.96 0.76 374.81 0.00 0.00 0.00
February 48.67 23.10 25.57 23.83 313.49 0.00 0.00 0.00
March 138.57 70.56 68.00 128.09 233.25 0.00 0.00 0.00
April 184.69 94.26 90.43 189.88 126.10 0.00 0.00 0.00
May 270.29 154.05 116.23 349.39 55.93 0.00 0.00 0.00
June 246.35 116.09 130.26 339.10 23.39 0.00 0.00 0.00
July 234.95 115.36 119.59 334.45 26.32 0.00 0.00 0.00
August 188.98 93.59 95.38 252.02 44.94 0.00 0.00 0.00
September 117.90 53.78 64.12 125.93 100.24 0.00 0.00 0.00
October 63.32 25.61 37.72 48.76 198.85 0.00 0.00 0.00
November 12.78 4.41 8.37 0.54 364.43 0.00 0.00 0.00
December 1.79 0.37 1.43 0.00 400.08 0.00 0.00 0.00
                 
Annual Sum or Average 126.94 63.15 63.80 150.27 187.84 0.00 0.00 0.00
Minimum of Months 1.79 0.37 1.43 0.00 23.39 0.00 0.00 0.00
Maximum of Months 270.29 154.05 130.26 349.39 400.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.07 14.92 7.15 12.24 186.52 0.00 0.00 0.00
February 73.32 51.49 21.83 65.90 149.65 0.00 0.00 0.00
March 122.69 83.58 39.12 135.01 115.35 0.00 0.00 0.00
April 148.58 92.62 55.96 190.53 73.15 0.00 0.00 0.00
May 121.13 62.29 58.84 163.62 35.85 0.00 0.00 0.00
June 109.65 43.85 65.80 156.26 15.81 0.00 0.00 0.00
July 105.77 45.13 60.64 155.55 16.53 0.00 0.00 0.00
August 111.31 61.37 49.94 157.81 27.00 0.00 0.00 0.00
September 89.63 53.85 35.77 111.08 54.21 0.00 0.00 0.00
October 67.22 43.14 24.08 67.15 97.11 0.00 0.00 0.00
November 36.89 26.34 10.54 23.89 173.15 0.00 0.00 0.00
December 6.55 4.69 1.86 0.87 206.59 0.00 0.00 0.00
                 
Annual Sum or Average 84.53 48.52 36.01 103.45 95.65 0.00 0.00 0.00
Minimum of Months 6.55 4.69 1.86 0.87 15.81 0.00 0.00 0.00
Maximum of Months 148.58 92.62 65.80 190.53 206.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1.71 0.00 1.71 0.00 205.52 0.00 0.00 0.00
February 7.57 0.00 7.57 0.00 185.41 0.00 0.00 0.00
March 20.27 0.00 20.27 0.73 142.54 0.00 0.00 0.00
April 36.84 0.88 35.97 12.50 75.33 0.00 0.00 0.00
May 55.99 8.46 47.53 46.42 28.26 0.00 0.00 0.00
June 72.83 15.80 57.03 85.23 11.35 0.00 0.00 0.00
July 61.52 9.91 51.61 74.69 13.69 0.00 0.00 0.00
August 39.66 2.11 37.55 37.20 24.93 0.00 0.00 0.00
September 22.00 0.05 21.95 7.57 58.97 0.00 0.00 0.00
October 10.66 0.00 10.66 0.38 117.76 0.00 0.00 0.00
November 3.31 0.00 3.31 0.00 200.92 0.00 0.00 0.00
December 0.52 0.00 0.52 0.00 214.67 0.00 0.00 0.00
                 
Annual Sum or Average 27.84 3.11 24.73 22.20 106.18 0.00 0.00 0.00
Minimum of Months 0.52 0.00 0.52 0.00 11.35 0.00 0.00 0.00
Maximum of Months 72.83 15.80 57.03 85.23 214.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.19 3.23 5.96 0.77 374.51 0.00 0.00 0.00
February 48.67 23.10 25.57 24.14 312.38 0.00 0.00 0.00
March 138.57 70.56 68.00 129.46 230.23 0.00 0.00 0.00
April 184.69 94.26 90.43 193.06 123.64 0.00 0.00 0.00
May 270.29 154.05 116.23 350.43 56.06 0.00 0.00 0.00
June 246.35 116.09 130.26 337.42 24.63 0.00 0.00 0.00
July 234.95 115.36 119.59 332.26 27.64 0.00 0.00 0.00
August 188.98 93.59 95.38 252.41 45.81 0.00 0.00 0.00
September 117.90 53.78 64.12 127.65 98.72 0.00 0.00 0.00
October 63.32 25.61 37.72 49.46 197.21 0.00 0.00 0.00
November 12.78 4.41 8.37 0.55 364.23 0.00 0.00 0.00
December 1.79 0.37 1.43 0.00 399.98 0.00 0.00 0.00
                 
Annual Sum or Average 126.94 63.15 63.80 150.67 187.28 0.00 0.00 0.00
Minimum of Months 1.79 0.37 1.43 0.00 24.63 0.00 0.00 0.00
Maximum of Months 270.29 154.05 130.26 350.43 399.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.17 0.00 2.17 0.00 271.97 0.00 0.00 0.00
February 9.59 0.00 9.59 0.00 246.35 0.00 0.00 0.00
March 25.68 0.00 25.67 0.81 188.81 0.00 0.00 0.00
April 46.66 1.11 45.55 16.25 98.92 0.00 0.00 0.00
May 70.91 10.71 60.20 61.52 37.43 0.00 0.00 0.00
June 92.23 20.01 72.22 109.85 15.81 0.00 0.00 0.00
July 77.91 12.55 65.36 97.01 18.95 0.00 0.00 0.00
August 50.22 2.67 47.55 48.50 33.50 0.00 0.00 0.00
September 27.86 0.06 27.80 9.97 77.73 0.00 0.00 0.00
October 13.50 0.00 13.50 0.39 157.12 0.00 0.00 0.00
November 4.19 0.00 4.19 0.00 266.00 0.00 0.00 0.00
December 0.66 0.00 0.66 0.00 283.58 0.00 0.00 0.00
                 
Annual Sum or Average 35.26 3.94 31.31 28.87 140.78 0.00 0.00 0.00
Minimum of Months 0.66 0.00 0.66 0.00 15.81 0.00 0.00 0.00
Maximum of Months 92.23 20.01 72.22 109.85 283.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 0.80 0.00 0.80 0.00 100.25 0.00 0.00 0.00
February 3.53 0.00 3.53 0.00 90.82 0.00 0.00 0.00
March 9.47 0.00 9.46 0.30 69.60 0.00 0.00 0.00
April 17.20 0.41 16.79 5.99 36.47 0.00 0.00 0.00
May 26.14 3.95 22.19 22.68 13.80 0.00 0.00 0.00
June 34.00 7.38 26.62 40.50 5.83 0.00 0.00 0.00
July 28.72 4.63 24.10 35.76 6.99 0.00 0.00 0.00
August 18.51 0.99 17.53 17.88 12.35 0.00 0.00 0.00
September 10.27 0.02 10.25 3.68 28.66 0.00 0.00 0.00
October 4.97 0.00 4.97 0.14 57.92 0.00 0.00 0.00
November 1.54 0.00 1.54 0.00 98.06 0.00 0.00 0.00
December 0.24 0.00 0.24 0.00 104.52 0.00 0.00 0.00
                 
Annual Sum or Average 13.00 1.45 11.54 10.64 51.89 0.00 0.00 0.00
Minimum of Months 0.24 0.00 0.24 0.00 5.83 0.00 0.00 0.00
Maximum of Months 34.00 7.38 26.62 40.50 104.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.30 6.96 3.33 5.41 90.82 0.00 0.00 0.00
February 34.21 24.02 10.19 30.05 72.55 0.00 0.00 0.00
March 57.25 39.00 18.25 62.94 55.37 0.00 0.00 0.00
April 69.33 43.22 26.11 89.91 34.86 0.00 0.00 0.00
May 56.52 29.06 27.45 77.61 17.74 0.00 0.00 0.00
June 51.16 20.46 30.70 73.30 8.77 0.00 0.00 0.00
July 49.35 21.06 28.29 73.01 9.02 0.00 0.00 0.00
August 51.94 28.64 23.30 74.34 13.76 0.00 0.00 0.00
September 41.82 25.13 16.69 52.46 25.98 0.00 0.00 0.00
October 31.36 20.13 11.24 31.07 47.12 0.00 0.00 0.00
November 17.21 12.29 4.92 10.59 84.16 0.00 0.00 0.00
December 3.06 2.19 0.87 0.35 100.63 0.00 0.00 0.00
                 
Annual Sum or Average 39.44 22.64 16.80 48.48 46.61 0.00 0.00 0.00
Minimum of Months 3.06 2.19 0.87 0.35 8.77 0.00 0.00 0.00
Maximum of Months 69.33 43.22 30.70 89.91 100.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 27.95 18.90 9.05 14.67 246.51 0.00 0.00 0.00
February 92.86 65.21 27.65 81.56 196.90 0.00 0.00 0.00
March 155.38 105.84 49.54 170.83 150.28 0.00 0.00 0.00
April 188.17 117.30 70.88 244.03 94.63 0.00 0.00 0.00
May 153.40 78.88 74.52 210.65 48.15 0.00 0.00 0.00
June 138.86 55.54 83.33 198.96 23.80 0.00 0.00 0.00
July 133.96 57.16 76.80 198.17 24.50 0.00 0.00 0.00
August 140.97 77.73 63.25 201.78 37.34 0.00 0.00 0.00
September 113.51 68.20 45.31 142.38 70.53 0.00 0.00 0.00
October 85.13 54.63 30.50 84.34 127.90 0.00 0.00 0.00
November 46.71 33.36 13.35 28.73 228.44 0.00 0.00 0.00
December 8.29 5.93 2.36 0.96 273.13 0.00 0.00 0.00
                 
Annual Sum or Average 107.06 61.45 45.61 131.59 126.51 0.00 0.00 0.00
Minimum of Months 8.29 5.93 2.36 0.96 23.80 0.00 0.00 0.00
Maximum of Months 188.17 117.30 83.33 244.03 273.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.07 14.92 7.15 12.35 185.30 0.00 0.00 0.00
February 73.32 51.49 21.83 66.48 148.52 0.00 0.00 0.00
March 122.69 83.58 39.12 136.64 114.29 0.00 0.00 0.00
April 148.58 92.62 55.96 191.06 73.03 0.00 0.00 0.00
May 121.13 62.29 58.84 164.28 35.72 0.00 0.00 0.00
June 109.65 43.85 65.80 156.12 16.14 0.00 0.00 0.00
July 105.77 45.13 60.64 155.77 16.59 0.00 0.00 0.00
August 111.31 61.37 49.94 158.15 26.66 0.00 0.00 0.00
September 89.63 53.85 35.77 112.15 53.30 0.00 0.00 0.00
October 67.22 43.14 24.08 68.03 96.09 0.00 0.00 0.00
November 36.89 26.34 10.54 24.15 171.56 0.00 0.00 0.00
December 6.55 4.69 1.86 0.89 205.31 0.00 0.00 0.00
                 
Annual Sum or Average 84.53 48.52 36.01 103.96 94.96 0.00 0.00 0.00
Minimum of Months 6.55 4.69 1.86 0.89 16.14 0.00 0.00 0.00
Maximum of Months 148.58 92.62 65.80 191.06 205.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4.29 0.64 3.65 0.00 380.10 0.00 0.00 0.00
February 25.73 8.64 17.09 3.95 328.85 0.00 0.00 0.00
March 78.57 33.75 44.82 46.48 242.94 0.00 0.00 0.00
April 188.46 98.57 89.89 203.53 134.21 0.00 0.00 0.00
May 182.79 84.17 98.62 217.24 61.12 0.00 0.00 0.00
June 199.89 86.05 113.84 267.73 27.83 0.00 0.00 0.00
July 166.74 63.50 103.24 228.17 29.30 0.00 0.00 0.00
August 137.62 58.92 78.70 174.20 48.10 0.00 0.00 0.00
September 82.50 34.46 48.04 76.61 103.93 0.00 0.00 0.00
October 31.91 9.28 22.63 11.49 209.03 0.00 0.00 0.00
November 12.70 4.43 8.27 0.87 361.71 0.00 0.00 0.00
December 1.13 0.09 1.04 0.00 399.08 0.00 0.00 0.00
                 
Annual Sum or Average 92.94 40.30 52.64 102.95 193.14 0.00 0.00 0.00
Minimum of Months 1.13 0.09 1.04 0.00 27.83 0.00 0.00 0.00
Maximum of Months 199.89 98.57 113.84 267.73 399.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1.71 0.00 1.71 0.00 204.45 0.00 0.00 0.00
February 7.57 0.00 7.57 0.00 184.40 0.00 0.00 0.00
March 20.27 0.00 20.27 0.98 140.80 0.00 0.00 0.00
April 36.84 0.88 35.97 13.46 74.80 0.00 0.00 0.00
May 55.99 8.46 47.53 47.98 28.13 0.00 0.00 0.00
June 72.83 15.80 57.03 84.36 11.59 0.00 0.00 0.00
July 61.52 9.91 51.61 75.19 13.79 0.00 0.00 0.00
August 39.66 2.11 37.55 37.85 24.87 0.00 0.00 0.00
September 22.00 0.05 21.95 8.62 57.41 0.00 0.00 0.00
October 10.66 0.00 10.66 0.58 116.42 0.00 0.00 0.00
November 3.31 0.00 3.31 0.00 199.16 0.00 0.00 0.00
December 0.52 0.00 0.52 0.00 213.40 0.00 0.00 0.00
                 
Annual Sum or Average 27.84 3.11 24.73 22.56 105.34 0.00 0.00 0.00
Minimum of Months 0.52 0.00 0.52 0.00 11.59 0.00 0.00 0.00
Maximum of Months 72.83 15.80 57.03 84.36 213.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4.29 0.64 3.65 0.00 380.14 0.00 0.00 0.00
February 25.73 8.64 17.09 4.17 328.49 0.00 0.00 0.00
March 78.57 33.75 44.82 47.93 241.42 0.00 0.00 0.00
April 188.46 98.57 89.89 207.90 132.46 0.00 0.00 0.00
May 182.79 84.17 98.62 217.99 60.99 0.00 0.00 0.00
June 199.89 86.05 113.84 263.09 28.78 0.00 0.00 0.00
July 166.74 63.50 103.24 225.08 30.42 0.00 0.00 0.00
August 137.62 58.92 78.70 173.73 49.29 0.00 0.00 0.00
September 82.50 34.46 48.04 79.03 102.53 0.00 0.00 0.00
October 31.91 9.28 22.63 12.23 208.05 0.00 0.00 0.00
November 12.70 4.43 8.27 0.91 361.59 0.00 0.00 0.00
December 1.13 0.09 1.04 0.00 399.06 0.00 0.00 0.00
                 
Annual Sum or Average 92.94 40.30 52.64 103.10 192.90 0.00 0.00 0.00
Minimum of Months 1.13 0.09 1.04 0.00 28.78 0.00 0.00 0.00
Maximum of Months 199.89 98.57 113.84 263.09 399.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.37 21.88 10.48 17.57 275.11 0.00 0.00 0.00
February 107.53 75.51 32.02 94.58 221.65 0.00 0.00 0.00
March 179.94 122.57 57.37 194.75 171.71 0.00 0.00 0.00
April 217.91 135.84 82.08 276.36 108.83 0.00 0.00 0.00
May 177.65 91.35 86.30 239.65 52.54 0.00 0.00 0.00
June 160.81 64.31 96.50 229.35 23.34 0.00 0.00 0.00
July 155.13 66.19 88.93 228.47 24.13 0.00 0.00 0.00
August 163.25 90.01 73.24 230.85 39.27 0.00 0.00 0.00
September 131.45 78.98 52.47 161.35 80.39 0.00 0.00 0.00
October 98.58 63.27 35.32 96.43 144.58 0.00 0.00 0.00
November 54.10 38.63 15.46 34.37 254.88 0.00 0.00 0.00
December 9.61 6.87 2.73 1.25 304.50 0.00 0.00 0.00
                 
Annual Sum or Average 123.98 71.16 52.81 150.60 141.36 0.00 0.00 0.00
Minimum of Months 9.61 6.87 2.73 1.25 23.34 0.00 0.00 0.00
Maximum of Months 217.91 135.84 96.50 276.36 304.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.99 0.00 11.99 0.00 1459.89 0.00 0.00 0.00
February 52.98 0.00 52.98 0.00 1320.94 0.00 0.00 0.00
March 141.92 0.01 141.90 4.97 1015.30 0.00 0.00 0.00
April 257.90 6.13 251.77 94.82 535.97 0.00 0.00 0.00
May 391.92 59.19 332.73 351.96 201.55 0.00 0.00 0.00
June 509.78 110.59 399.19 630.00 82.51 0.00 0.00 0.00
July 430.63 69.36 361.26 559.54 97.83 0.00 0.00 0.00
August 277.58 14.78 262.81 284.43 175.22 0.00 0.00 0.00
September 153.99 0.36 153.63 58.14 420.97 0.00 0.00 0.00
October 74.59 0.00 74.59 2.33 850.20 0.00 0.00 0.00
November 23.15 0.00 23.15 0.00 1421.37 0.00 0.00 0.00
December 3.64 0.00 3.64 0.00 1520.30 0.00 0.00 0.00
                 
Annual Sum or Average 194.87 21.80 173.07 166.54 755.45 0.00 0.00 0.00
Minimum of Months 3.64 0.00 3.64 0.00 82.51 0.00 0.00 0.00
Maximum of Months 509.78 110.59 399.19 630.00 1520.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.99 0.00 11.99 0.00 1479.50 0.00 0.00 0.00
February 52.98 0.00 52.98 0.00 1340.84 0.00 0.00 0.00
March 141.92 0.01 141.90 4.33 1036.19 0.00 0.00 0.00
April 257.90 6.13 251.77 89.07 552.83 0.00 0.00 0.00
May 391.92 59.19 332.73 340.19 208.65 0.00 0.00 0.00
June 509.78 110.59 399.19 617.78 86.11 0.00 0.00 0.00
July 430.63 69.36 361.26 548.28 102.26 0.00 0.00 0.00
August 277.58 14.78 262.81 275.20 182.57 0.00 0.00 0.00
September 153.99 0.36 153.63 53.53 438.98 0.00 0.00 0.00
October 74.59 0.00 74.59 1.67 872.80 0.00 0.00 0.00
November 23.15 0.00 23.15 0.00 1440.78 0.00 0.00 0.00
December 3.64 0.00 3.64 0.00 1539.34 0.00 0.00 0.00
                 
Annual Sum or Average 194.87 21.80 173.07 161.84 770.31 0.00 0.00 0.00
Minimum of Months 3.64 0.00 3.64 0.00 86.11 0.00 0.00 0.00
Maximum of Months 509.78 110.59 399.19 617.78 1539.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1.71 0.00 1.71 0.00 171.59 0.00 0.00 0.00
February 7.57 0.00 7.57 0.01 151.44 0.00 0.00 0.00
March 20.27 0.00 20.27 5.36 113.18 0.00 0.00 0.00
April 36.84 0.88 35.97 37.26 62.33 0.00 0.00 0.00
May 55.99 8.46 47.53 89.16 26.03 0.00 0.00 0.00
June 72.83 15.80 57.03 134.78 11.30 0.00 0.00 0.00
July 61.52 9.91 51.61 124.17 12.92 0.00 0.00 0.00
August 39.66 2.11 37.55 80.44 21.02 0.00 0.00 0.00
September 22.00 0.05 21.95 30.82 42.09 0.00 0.00 0.00
October 10.66 0.00 10.66 4.98 88.64 0.00 0.00 0.00
November 3.31 0.00 3.31 0.00 165.42 0.00 0.00 0.00
December 0.52 0.00 0.52 0.00 180.12 0.00 0.00 0.00
                 
Annual Sum or Average 27.84 3.11 24.73 42.50 86.83 0.00 0.00 0.00
Minimum of Months 0.52 0.00 0.52 0.00 11.30 0.00 0.00 0.00
Maximum of Months 72.83 15.80 57.03 134.78 180.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.38 6.46 11.92 3.81 625.08 0.00 0.00 0.00
February 97.32 46.19 51.13 69.58 518.25 0.00 0.00 0.00
March 277.11 141.12 136.00 315.00 386.07 0.00 0.00 0.00
April 369.36 188.50 180.85 501.53 218.16 0.00 0.00 0.00
May 540.54 308.09 232.45 858.06 99.36 0.00 0.00 0.00
June 492.67 232.16 260.51 855.71 44.30 0.00 0.00 0.00
July 469.87 230.70 239.17 847.17 49.45 0.00 0.00 0.00
August 377.93 187.18 190.75 669.66 78.51 0.00 0.00 0.00
September 235.78 107.56 128.22 363.87 153.77 0.00 0.00 0.00
October 126.64 51.21 75.43 142.68 310.40 0.00 0.00 0.00
November 25.56 8.82 16.74 3.45 598.23 0.00 0.00 0.00
December 3.59 0.73 2.86 0.00 671.82 0.00 0.00 0.00
                 
Annual Sum or Average 253.87 126.29 127.58 387.98 311.74 0.00 0.00 0.00
Minimum of Months 3.59 0.73 2.86 0.00 44.30 0.00 0.00 0.00
Maximum of Months 540.54 308.09 260.51 858.06 671.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.07 14.92 7.15 16.41 156.38 0.00 0.00 0.00
February 73.32 51.49 21.83 78.69 126.72 0.00 0.00 0.00
March 122.69 83.58 39.12 157.24 99.47 0.00 0.00 0.00
April 148.58 92.62 55.96 222.91 62.78 0.00 0.00 0.00
May 121.13 62.29 58.84 204.58 30.69 0.00 0.00 0.00
June 109.65 43.85 65.80 203.53 15.33 0.00 0.00 0.00
July 105.77 45.13 60.64 202.92 15.56 0.00 0.00 0.00
August 111.31 61.37 49.94 200.24 22.17 0.00 0.00 0.00
September 89.63 53.85 35.77 141.53 41.70 0.00 0.00 0.00
October 67.22 43.14 24.08 84.75 78.62 0.00 0.00 0.00
November 36.89 26.34 10.54 31.10 144.26 0.00 0.00 0.00
December 6.55 4.69 1.86 1.64 172.85 0.00 0.00 0.00
                 
Annual Sum or Average 84.53 48.52 36.01 128.98 80.32 0.00 0.00 0.00
Minimum of Months 6.55 4.69 1.86 1.64 15.33 0.00 0.00 0.00
Maximum of Months 148.58 92.62 65.80 222.91 172.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.17 0.00 2.17 0.00 271.50 0.00 0.00 0.00
February 9.59 0.00 9.59 0.00 246.23 0.00 0.00 0.00
March 25.68 0.00 25.67 0.71 189.86 0.00 0.00 0.00
April 46.66 1.11 45.55 13.95 102.06 0.00 0.00 0.00
May 70.91 10.71 60.20 54.57 41.07 0.00 0.00 0.00
June 92.23 20.01 72.22 101.45 18.16 0.00 0.00 0.00
July 77.91 12.55 65.36 89.38 21.86 0.00 0.00 0.00
August 50.22 2.67 47.55 42.47 37.97 0.00 0.00 0.00
September 27.86 0.06 27.80 8.02 82.40 0.00 0.00 0.00
October 13.50 0.00 13.50 0.28 158.74 0.00 0.00 0.00
November 4.19 0.00 4.19 0.00 264.82 0.00 0.00 0.00
December 0.66 0.00 0.66 0.00 282.84 0.00 0.00 0.00
                 
Annual Sum or Average 35.26 3.94 31.31 26.06 142.57 0.00 0.00 0.00
Minimum of Months 0.66 0.00 0.66 0.00 18.16 0.00 0.00 0.00
Maximum of Months 92.23 20.01 72.22 101.45 282.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1.94 0.00 1.94 0.00 242.91 0.00 0.00 0.00
February 8.58 0.00 8.58 0.00 220.27 0.00 0.00 0.00
March 22.97 0.00 22.97 0.64 169.87 0.00 0.00 0.00
April 41.75 0.99 40.75 12.48 91.31 0.00 0.00 0.00
May 63.44 9.58 53.86 48.82 36.74 0.00 0.00 0.00
June 82.52 17.90 64.62 90.77 16.25 0.00 0.00 0.00
July 69.71 11.23 58.48 79.97 19.56 0.00 0.00 0.00
August 44.93 2.39 42.54 38.00 33.97 0.00 0.00 0.00
September 24.93 0.06 24.87 7.17 73.73 0.00 0.00 0.00
October 12.07 0.00 12.07 0.25 142.01 0.00 0.00 0.00
November 3.75 0.00 3.75 0.00 236.93 0.00 0.00 0.00
December 0.59 0.00 0.59 0.00 253.06 0.00 0.00 0.00
                 
Annual Sum or Average 31.54 3.53 28.02 23.32 127.55 0.00 0.00 0.00
Minimum of Months 0.59 0.00 0.59 0.00 16.25 0.00 0.00 0.00
Maximum of Months 82.52 17.90 64.62 90.77 253.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 82.39 55.71 26.68 43.15 725.57 0.00 0.00 0.00
February 273.73 192.22 81.51 239.74 579.98 0.00 0.00 0.00
March 458.05 312.01 146.03 500.25 444.67 0.00 0.00 0.00
April 554.71 345.78 208.93 708.65 286.41 0.00 0.00 0.00
May 452.21 232.54 219.67 602.35 156.26 0.00 0.00 0.00
June 409.35 163.72 245.63 564.94 81.72 0.00 0.00 0.00
July 394.88 168.50 226.38 563.56 84.01 0.00 0.00 0.00
August 415.57 229.13 186.44 576.92 124.81 0.00 0.00 0.00
September 334.60 201.04 133.56 410.37 219.55 0.00 0.00 0.00
October 250.95 161.05 89.90 246.00 380.57 0.00 0.00 0.00
November 137.71 98.34 39.36 84.85 670.43 0.00 0.00 0.00
December 24.45 17.49 6.96 2.86 803.46 0.00 0.00 0.00
                 
Annual Sum or Average 315.59 181.14 134.44 379.08 378.86 0.00 0.00 0.00
Minimum of Months 24.45 17.49 6.96 2.86 81.72 0.00 0.00 0.00
Maximum of Months 554.71 345.78 245.63 708.65 803.46 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298950E+09 0.202137E+09 96812571.55 0.162890E+09 0.249855E+10
February 0.897129E+09 0.629983E+09 0.267146E+09 0.795492E+09 0.180847E+10
March 0.166206E+10 0.113217E+10 0.529890E+09 0.182273E+10 0.153262E+10
April 0.194788E+10 0.121421E+10 0.733670E+09 0.249127E+10 0.958209E+09
May 0.164087E+10 0.843784E+09 0.797082E+09 0.221789E+10 0.510720E+09
June 0.143744E+10 0.574893E+09 0.862549E+09 0.202051E+10 0.253798E+09
July 0.143287E+10 0.611419E+09 0.821450E+09 0.207784E+10 0.269225E+09
August 0.150792E+10 0.831413E+09 0.676509E+09 0.211895E+10 0.406045E+09
September 0.117497E+10 0.705972E+09 0.468993E+09 0.145068E+10 0.713463E+09
October 0.910593E+09 0.584381E+09 0.326212E+09 0.905210E+09 0.129850E+10
November 0.483558E+09 0.345330E+09 0.138228E+09 0.303465E+09 0.225599E+10
December 88721138.45 63468308.89 25252829.55 11175695.43 0.277094E+10
           
Annual Sum or Average 0.134830E+11 0.773916E+10 0.574380E+10 0.163781E+11 0.152765E+11
Minimum of Months 88721138.45 63468308.89 25252829.55 11175695.43 0.253798E+09
Maximum of Months 0.194788E+10 0.121421E+10 0.862549E+09 0.249127E+10 0.277094E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.841824E+09 0.569206E+09 0.272618E+09 0.454708E+09 0.697716E+10
February 0.252626E+10 0.177399E+10 0.752267E+09 0.222874E+10 0.504897E+10
March 0.468024E+10 0.318811E+10 0.149214E+10 0.513053E+10 0.427632E+10
April 0.548510E+10 0.341914E+10 0.206597E+10 0.704580E+10 0.265867E+10
May 0.462057E+10 0.237604E+10 0.224453E+10 0.631977E+10 0.137355E+10
June 0.404774E+10 0.161886E+10 0.242888E+10 0.581816E+10 0.635632E+09
July 0.403486E+10 0.172171E+10 0.231315E+10 0.597513E+10 0.676683E+09
August 0.424621E+10 0.234120E+10 0.190500E+10 0.604948E+10 0.106397E+10
September 0.330862E+10 0.198797E+10 0.132065E+10 0.410272E+10 0.198130E+10
October 0.256417E+10 0.164558E+10 0.918591E+09 0.254020E+10 0.363545E+10
November 0.136167E+10 0.972426E+09 0.389241E+09 0.847637E+09 0.629832E+10
December 0.249833E+09 0.178723E+09 71110303.00 31020756.16 0.773877E+10
           
Annual Sum or Average 0.379671E+11 0.217930E+11 0.161741E+11 0.465439E+11 0.423648E+11
Minimum of Months 0.249833E+09 0.178723E+09 71110303.00 31020756.16 0.635632E+09
Maximum of Months 0.548510E+10 0.341914E+10 0.242888E+10 0.704580E+10 0.773877E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109358E+10 0.739431E+09 0.354146E+09 0.583685E+09 0.942402E+10
February 0.328175E+10 0.230451E+10 0.977237E+09 0.289729E+10 0.681828E+10
March 0.607990E+10 0.414153E+10 0.193837E+10 0.671671E+10 0.578553E+10
April 0.712546E+10 0.444166E+10 0.268381E+10 0.924173E+10 0.362192E+10
May 0.600238E+10 0.308661E+10 0.291577E+10 0.825932E+10 0.192793E+10
June 0.525825E+10 0.210299E+10 0.315526E+10 0.758051E+10 0.920758E+09
July 0.524152E+10 0.223660E+10 0.300491E+10 0.778399E+10 0.982414E+09
August 0.551607E+10 0.304136E+10 0.247471E+10 0.789121E+10 0.151523E+10
September 0.429809E+10 0.258249E+10 0.171561E+10 0.534875E+10 0.277238E+10
October 0.333100E+10 0.213770E+10 0.119330E+10 0.330349E+10 0.498868E+10
November 0.176888E+10 0.126324E+10 0.505646E+09 0.109183E+10 0.851349E+10
December 0.324547E+09 0.232171E+09 92376330.53 38566041.44 0.104364E+11
           
Annual Sum or Average 0.493214E+11 0.283103E+11 0.210111E+11 0.607371E+11 0.577070E+11
Minimum of Months 0.324547E+09 0.232171E+09 92376330.53 38566041.44 0.920758E+09
Maximum of Months 0.712546E+10 0.444166E+10 0.315526E+10 0.924173E+10 0.104364E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59107587.39 39966046.04 19141541.35 32882025.46 0.499463E+09
February 0.177378E+09 0.124558E+09 52819601.66 0.160257E+09 0.361705E+09
March 0.328618E+09 0.223849E+09 0.104769E+09 0.365702E+09 0.307703E+09
April 0.385131E+09 0.240070E+09 0.145060E+09 0.496559E+09 0.190227E+09
May 0.324429E+09 0.166831E+09 0.157598E+09 0.442178E+09 96452282.25
June 0.284208E+09 0.113666E+09 0.170542E+09 0.407031E+09 42373668.30
July 0.283304E+09 0.120888E+09 0.162416E+09 0.419402E+09 45013725.80
August 0.298143E+09 0.164385E+09 0.133758E+09 0.425144E+09 72242081.00
September 0.232311E+09 0.139583E+09 92728585.28 0.290662E+09 0.139720E+09
October 0.180040E+09 0.115542E+09 64497936.25 0.181727E+09 0.259279E+09
November 95607751.59 68277645.44 27330106.14 61989713.61 0.448802E+09
December 17541701.43 12548774.73 4992926.70 2338710.01 0.553297E+09
           
Annual Sum or Average 0.266582E+10 0.153016E+10 0.113565E+10 0.328587E+10 0.301628E+10
Minimum of Months 17541701.43 12548774.73 4992926.70 2338710.01 42373668.30
Maximum of Months 0.385131E+09 0.240070E+09 0.170542E+09 0.496559E+09 0.553297E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 11486556.15 1705645.82 9780910.33 0.00 0.102452E+10
February 62244458.89 20902337.51 41342121.38 9327793.30 0.801208E+09
March 0.210447E+09 90391204.81 0.120056E+09 0.124017E+09 0.654858E+09
April 0.488484E+09 0.255487E+09 0.232997E+09 0.530134E+09 0.350204E+09
May 0.489583E+09 0.225450E+09 0.264133E+09 0.585038E+09 0.165279E+09
June 0.518108E+09 0.223038E+09 0.295070E+09 0.697998E+09 73167897.28
July 0.446602E+09 0.170086E+09 0.276515E+09 0.614646E+09 79625869.68
August 0.368613E+09 0.157822E+09 0.210790E+09 0.468931E+09 0.130608E+09
September 0.213831E+09 89323781.97 0.124507E+09 0.198358E+09 0.273049E+09
October 85460959.51 24858392.30 60602567.21 30060903.80 0.564481E+09
November 32925659.96 11493277.30 21432382.66 2172681.35 0.946503E+09
December 3027357.30 242591.52 2784765.78 0.00 0.107552E+10
           
Annual Sum or Average 0.293081E+10 0.127080E+10 0.166001E+10 0.326068E+10 0.613902E+10
Minimum of Months 3027357.30 242591.52 2784765.78 0.00 73167897.28
Maximum of Months 0.518108E+09 0.255487E+09 0.295070E+09 0.697998E+09 0.107552E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 4586409.53 0.00 4586409.53 0.00 0.550766E+09
February 18312140.33 0.00 18312140.33 0.00 0.448884E+09
March 54303148.56 4230.74 54298917.82 2461345.73 0.379080E+09
April 95500032.05 2271094.42 93228937.64 34651245.94 0.195021E+09
May 0.149964E+09 22649144.62 0.127315E+09 0.129418E+09 75629789.59
June 0.188770E+09 40950738.73 0.147819E+09 0.221389E+09 29887503.94
July 0.164776E+09 26541033.82 0.138235E+09 0.203509E+09 36826101.03
August 0.106215E+09 5653698.97 0.100561E+09 0.102171E+09 66753314.69
September 57022242.83 132701.96 56889540.87 21765150.13 0.151117E+09
October 28541372.39 0.00 28541372.39 1319304.84 0.314191E+09
November 8571672.55 0.00 8571672.55 0.00 0.520723E+09
December 1391275.71 0.00 1391275.71 0.00 0.574997E+09
           
Annual Sum or Average 0.877953E+09 98202643.25 0.779751E+09 0.716684E+09 0.334387E+10
Minimum of Months 1391275.71 0.00 1391275.71 0.00 29887503.94
Maximum of Months 0.188770E+09 40950738.73 0.147819E+09 0.221389E+09 0.574997E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 11486556.15 1705645.82 9780910.33 0.00 0.102454E+10
February 62244458.89 20902337.51 41342121.38 9893415.50 0.800027E+09
March 0.210447E+09 90391204.81 0.120056E+09 0.128106E+09 0.649979E+09
April 0.488484E+09 0.255487E+09 0.232997E+09 0.540602E+09 0.345631E+09
May 0.489583E+09 0.225450E+09 0.264133E+09 0.587456E+09 0.164603E+09
June 0.518108E+09 0.223038E+09 0.295070E+09 0.688483E+09 74501307.89
July 0.446602E+09 0.170086E+09 0.276515E+09 0.608141E+09 81629852.71
August 0.368613E+09 0.157822E+09 0.210790E+09 0.468600E+09 0.132813E+09
September 0.213831E+09 89323781.97 0.124507E+09 0.203909E+09 0.269661E+09
October 85460959.51 24858392.30 60602567.21 32016475.20 0.561444E+09
November 32925659.96 11493277.30 21432382.66 2279466.25 0.946061E+09
December 3027357.30 242591.52 2784765.78 0.00 0.107545E+10
           
Annual Sum or Average 0.293081E+10 0.127080E+10 0.166001E+10 0.326949E+10 0.612634E+10
Minimum of Months 3027357.30 242591.52 2784765.78 0.00 74501307.89
Maximum of Months 0.518108E+09 0.255487E+09 0.295070E+09 0.688483E+09 0.107545E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 47276667.86 31966479.56 15310188.30 28989861.54 0.352341E+09
February 0.141874E+09 99626911.10 42247279.48 0.135037E+09 0.254445E+09
March 0.262842E+09 0.179044E+09 83798449.73 0.295277E+09 0.231871E+09
April 0.308043E+09 0.192018E+09 0.116025E+09 0.377546E+09 0.184459E+09
May 0.259491E+09 0.133438E+09 0.126053E+09 0.329196E+09 0.111904E+09
June 0.227322E+09 90914864.02 0.136407E+09 0.297900E+09 59653020.76
July 0.226598E+09 96691123.43 0.129907E+09 0.307343E+09 63342382.82
August 0.238467E+09 0.131482E+09 0.106985E+09 0.315511E+09 91411132.20
September 0.185812E+09 0.111644E+09 74168118.18 0.212701E+09 0.152005E+09
October 0.144003E+09 92415349.65 51588089.52 0.137269E+09 0.221153E+09
November 76470993.25 54611255.65 21859737.60 53919967.42 0.315930E+09
December 14030570.84 10037023.69 3993547.15 2249051.53 0.393182E+09
           
Annual Sum or Average 0.213223E+10 0.122389E+10 0.908343E+09 0.249294E+10 0.243170E+10
Minimum of Months 14030570.84 10037023.69 3993547.15 2249051.53 59653020.76
Maximum of Months 0.308043E+09 0.192018E+09 0.136407E+09 0.377546E+09 0.393182E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 3669613.99 0.00 3669613.99 0.00 0.450762E+09
February 14651654.16 0.00 14651654.16 0.00 0.368224E+09
March 43448277.40 3385.04 43444892.36 1536978.83 0.311717E+09
April 76410152.90 1817116.37 74593036.53 27999774.95 0.157519E+09
May 0.119987E+09 18121717.51 0.101865E+09 0.107399E+09 59688391.87
June 0.151036E+09 32764933.58 0.118271E+09 0.184646E+09 22860141.16
July 0.131838E+09 21235641.59 0.110603E+09 0.168390E+09 28397646.68
August 84983063.64 4523558.72 80459504.93 85251864.80 52073101.43
September 45623841.16 106175.64 45517665.52 16746025.46 0.124377E+09
October 22836124.56 0.00 22836124.56 691320.40 0.260620E+09
November 6858247.02 0.00 6858247.02 0.00 0.426454E+09
December 1113168.11 0.00 1113168.11 0.00 0.470226E+09
           
Annual Sum or Average 0.702456E+09 78572528.46 0.623883E+09 0.592662E+09 0.273292E+10
Minimum of Months 1113168.11 0.00 1113168.11 0.00 22860141.16
Maximum of Months 0.151036E+09 32764933.58 0.118271E+09 0.184646E+09 0.470226E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 24619726.97 8651486.50 15968240.47 2022368.89 0.100389E+10
February 0.117732E+09 55878597.63 61853691.56 57637946.07 0.758401E+09
March 0.371138E+09 0.188997E+09 0.182140E+09 0.343068E+09 0.624739E+09
April 0.478719E+09 0.244319E+09 0.234400E+09 0.492173E+09 0.326864E+09
May 0.723939E+09 0.412617E+09 0.311321E+09 0.935794E+09 0.149801E+09
June 0.638542E+09 0.300896E+09 0.337645E+09 0.878935E+09 60635386.91
July 0.629293E+09 0.308980E+09 0.320313E+09 0.895784E+09 70486659.59
August 0.506156E+09 0.250683E+09 0.255474E+09 0.674997E+09 0.120381E+09
September 0.305595E+09 0.139404E+09 0.166191E+09 0.326416E+09 0.259814E+09
October 0.169609E+09 68583779.27 0.101025E+09 0.130610E+09 0.532611E+09
November 33130464.40 11435613.74 21694850.67 1392225.74 0.944593E+09
December 4802634.85 977787.07 3824847.77 0.00 0.107157E+10
           
Annual Sum or Average 0.400328E+10 0.199142E+10 0.201185E+10 0.473883E+10 0.592379E+10
Minimum of Months 4802634.85 977787.07 3824847.77 0.00 60635386.91
Maximum of Months 0.723939E+09 0.412617E+09 0.337645E+09 0.935794E+09 0.107157E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59107587.39 39966046.04 19141541.35 32772629.68 0.499567E+09
February 0.177378E+09 0.124558E+09 52819601.66 0.159432E+09 0.362030E+09
March 0.328618E+09 0.223849E+09 0.104769E+09 0.361611E+09 0.308944E+09
April 0.385131E+09 0.240070E+09 0.145060E+09 0.493851E+09 0.189609E+09
May 0.324429E+09 0.166831E+09 0.157598E+09 0.438235E+09 96009955.76
June 0.284208E+09 0.113666E+09 0.170542E+09 0.405015E+09 40968562.18
July 0.283304E+09 0.120888E+09 0.162416E+09 0.416634E+09 44263933.02
August 0.298143E+09 0.164385E+09 0.133758E+09 0.422690E+09 72317085.27
September 0.232311E+09 0.139583E+09 92728585.28 0.287911E+09 0.140523E+09
October 0.180040E+09 0.115542E+09 64497936.25 0.179843E+09 0.260110E+09
November 95607751.59 68277645.44 27330106.14 61929804.59 0.448792E+09
December 17541701.43 12548774.73 4992926.70 2334267.35 0.553327E+09
           
Annual Sum or Average 0.266582E+10 0.153016E+10 0.113565E+10 0.326226E+10 0.301646E+10
Minimum of Months 17541701.43 12548774.73 4992926.70 2334267.35 40968562.18
Maximum of Months 0.385131E+09 0.240070E+09 0.170542E+09 0.493851E+09 0.553327E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 4586409.53 0.00 4586409.53 0.00 0.550469E+09
February 18312140.33 0.00 18312140.33 0.00 0.448539E+09
March 54303148.56 4230.74 54298917.82 1966578.20 0.381768E+09
April 95500032.05 2271094.42 93228937.64 32412305.87 0.195265E+09
May 0.149964E+09 22649144.62 0.127315E+09 0.124339E+09 75690128.12
June 0.188770E+09 40950738.73 0.147819E+09 0.220907E+09 29417148.23
July 0.164776E+09 26541033.82 0.138235E+09 0.200039E+09 36661485.03
August 0.106215E+09 5653698.97 0.100561E+09 99646730.85 66770026.84
September 57022242.83 132701.96 56889540.87 19627541.36 0.152848E+09
October 28541372.39 0.00 28541372.39 1017746.83 0.315413E+09
November 8571672.55 0.00 8571672.55 0.00 0.520778E+09
December 1391275.71 0.00 1391275.71 0.00 0.574967E+09
           
Annual Sum or Average 0.877953E+09 98202643.25 0.779751E+09 0.699957E+09 0.334859E+10
Minimum of Months 1391275.71 0.00 1391275.71 0.00 29417148.23
Maximum of Months 0.188770E+09 40950738.73 0.147819E+09 0.220907E+09 0.574967E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 24619726.97 8651486.50 15968240.47 2060452.22 0.100309E+10
February 0.117732E+09 55878597.63 61853691.56 58406147.63 0.755714E+09
March 0.371138E+09 0.188997E+09 0.182140E+09 0.346753E+09 0.616661E+09
April 0.478719E+09 0.244319E+09 0.234400E+09 0.500411E+09 0.320474E+09
May 0.723939E+09 0.412617E+09 0.311321E+09 0.938580E+09 0.150138E+09
June 0.638542E+09 0.300896E+09 0.337645E+09 0.874586E+09 63835726.84
July 0.629293E+09 0.308980E+09 0.320313E+09 0.889938E+09 74028580.89
August 0.506156E+09 0.250683E+09 0.255474E+09 0.676064E+09 0.122696E+09
September 0.305595E+09 0.139404E+09 0.166191E+09 0.330857E+09 0.255887E+09
October 0.169609E+09 68583779.27 0.101025E+09 0.132464E+09 0.528199E+09
November 33130464.40 11435613.74 21694850.67 1428075.08 0.944083E+09
December 4802634.85 977787.07 3824847.77 0.00 0.107131E+10
           
Annual Sum or Average 0.400328E+10 0.199142E+10 0.201185E+10 0.475155E+10 0.590612E+10
Minimum of Months 4802634.85 977787.07 3824847.77 0.00 63835726.84
Maximum of Months 0.723939E+09 0.412617E+09 0.337645E+09 0.938580E+09 0.107131E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 5808398.29 0.00 5808398.29 0.00 0.728442E+09
February 23191170.29 0.00 23191170.29 0.00 0.595982E+09
March 68771511.32 5357.97 68766153.35 2159725.57 0.505702E+09
April 0.120945E+09 2876197.78 0.118069E+09 42114705.56 0.256402E+09
May 0.189920E+09 28683712.58 0.161236E+09 0.164777E+09 0.100251E+09
June 0.239066E+09 51861526.75 0.187204E+09 0.284734E+09 40989891.43
July 0.208679E+09 33612544.69 0.175066E+09 0.259834E+09 50763051.93
August 0.134514E+09 7160053.01 0.127354E+09 0.129900E+09 89735960.70
September 72215072.64 168058.66 72047013.98 25841638.89 0.201482E+09
October 36145847.27 0.00 36145847.27 1034406.02 0.420820E+09
November 10855482.44 0.00 10855482.44 0.00 0.689484E+09
December 1761962.91 0.00 1761962.91 0.00 0.759530E+09
           
Annual Sum or Average 0.111187E+10 0.124367E+09 0.987505E+09 0.910396E+09 0.443958E+10
Minimum of Months 1761962.91 0.00 1761962.91 0.00 40989891.43
Maximum of Months 0.239066E+09 51861526.75 0.187204E+09 0.284734E+09 0.759530E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 2141216.12 0.00 2141216.12 0.00 0.268514E+09
February 8549225.64 0.00 8549225.64 0.00 0.219703E+09
March 25352026.67 1975.17 25350051.51 796164.27 0.186423E+09
April 44585248.26 1060285.60 43524962.67 15525224.30 94520336.68
May 70012394.14 10574004.16 59438389.98 60743667.04 36956573.14
June 88129453.66 19118306.18 69011147.49 0.104965E+09 15110571.24
July 76927538.78 12390975.76 64536563.02 95785597.44 18713362.87
August 49587533.16 2639492.02 46948041.15 47886580.85 33080390.79
September 26621465.97 61953.38 26559512.59 9526298.11 74274751.43
October 13324855.98 0.00 13324855.98 381324.89 0.155132E+09
November 4001780.32 0.00 4001780.32 0.00 0.254160E+09
December 649532.48 0.00 649532.48 0.00 0.279935E+09
           
Annual Sum or Average 0.409882E+09 45846992.25 0.364035E+09 0.335610E+09 0.163652E+10
Minimum of Months 649532.48 0.00 649532.48 0.00 15110571.24
Maximum of Months 88129453.66 19118306.18 69011147.49 0.104965E+09 0.279935E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27579362.09 18647996.03 8931366.06 14478911.78 0.243255E+09
February 82763863.25 58118449.96 24645413.29 72693937.35 0.175503E+09
March 0.153332E+09 0.104447E+09 48884743.63 0.168578E+09 0.148298E+09
April 0.179700E+09 0.112016E+09 67684468.30 0.233047E+09 90369802.71
May 0.151377E+09 77842478.07 73534660.14 0.207868E+09 47515759.97
June 0.132610E+09 53036181.86 79574308.82 0.189997E+09 22724857.66
July 0.132189E+09 56405826.06 75782681.75 0.195555E+09 24172323.92
August 0.139112E+09 76701226.84 62411142.81 0.199122E+09 36845657.52
September 0.108396E+09 65128735.68 43266784.22 0.135969E+09 67349824.56
October 84005983.74 53911506.59 30094477.15 83225052.87 0.126209E+09
November 44610191.62 31858074.23 12752117.39 27439107.12 0.218155E+09
December 8184887.20 5855207.72 2329679.48 948432.48 0.269526E+09
           
Annual Sum or Average 0.124386E+10 0.713969E+09 0.529892E+09 0.152892E+10 0.146992E+10
Minimum of Months 8184887.20 5855207.72 2329679.48 948432.48 22724857.66
Maximum of Months 0.179700E+09 0.112016E+09 79574308.82 0.233047E+09 0.269526E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 74856029.95 50614475.59 24241554.36 39298728.18 0.660243E+09
February 0.224638E+09 0.157745E+09 66892692.77 0.197306E+09 0.476351E+09
March 0.416174E+09 0.283491E+09 0.132683E+09 0.457556E+09 0.402511E+09
April 0.487743E+09 0.304034E+09 0.183709E+09 0.632538E+09 0.245282E+09
May 0.410869E+09 0.211280E+09 0.199588E+09 0.564195E+09 0.128967E+09
June 0.359932E+09 0.143951E+09 0.215981E+09 0.515692E+09 61679911.96
July 0.358787E+09 0.153097E+09 0.205690E+09 0.530776E+09 65608631.47
August 0.377579E+09 0.208183E+09 0.169397E+09 0.540459E+09 0.100007E+09
September 0.294208E+09 0.176773E+09 0.117435E+09 0.369048E+09 0.182801E+09
October 0.228009E+09 0.146327E+09 81682566.67 0.225890E+09 0.342557E+09
November 0.121081E+09 86469329.87 34611855.00 74475349.28 0.592118E+09
December 22215458.04 15892231.41 6323226.63 2574239.74 0.731548E+09
           
Annual Sum or Average 0.337609E+10 0.193786E+10 0.143823E+10 0.414981E+10 0.398967E+10
Minimum of Months 22215458.04 15892231.41 6323226.63 2574239.74 61679911.96
Maximum of Months 0.487743E+09 0.304034E+09 0.215981E+09 0.632538E+09 0.731548E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59107587.39 39966046.04 19141541.35 33076709.05 0.496309E+09
February 0.177378E+09 0.124558E+09 52819601.66 0.160826E+09 0.359289E+09
March 0.328618E+09 0.223849E+09 0.104769E+09 0.365965E+09 0.306120E+09
April 0.385131E+09 0.240070E+09 0.145060E+09 0.495218E+09 0.189303E+09
May 0.324429E+09 0.166831E+09 0.157598E+09 0.439997E+09 95683570.43
June 0.284208E+09 0.113666E+09 0.170542E+09 0.404659E+09 41841297.80
July 0.283304E+09 0.120888E+09 0.162416E+09 0.417206E+09 44439230.54
August 0.298143E+09 0.164385E+09 0.133758E+09 0.423577E+09 71404326.54
September 0.232311E+09 0.139583E+09 92728585.28 0.290681E+09 0.138144E+09
October 0.180040E+09 0.115542E+09 64497936.25 0.182215E+09 0.257367E+09
November 95607751.59 68277645.44 27330106.14 62601627.27 0.444696E+09
December 17541701.43 12548774.73 4992926.70 2385720.18 0.549905E+09
           
Annual Sum or Average 0.266582E+10 0.153016E+10 0.113565E+10 0.327841E+10 0.299450E+10
Minimum of Months 17541701.43 12548774.73 4992926.70 2385720.18 41841297.80
Maximum of Months 0.385131E+09 0.240070E+09 0.170542E+09 0.495218E+09 0.549905E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 11486556.15 1705645.82 9780910.33 0.00 0.101805E+10
February 62244458.89 20902337.51 41342121.38 9564633.05 0.795549E+09
March 0.210447E+09 90391204.81 0.120056E+09 0.124482E+09 0.650690E+09
April 0.488484E+09 0.255487E+09 0.232997E+09 0.527541E+09 0.347870E+09
May 0.489583E+09 0.225450E+09 0.264133E+09 0.581869E+09 0.163707E+09
June 0.518108E+09 0.223038E+09 0.295070E+09 0.693968E+09 72142524.08
July 0.446602E+09 0.170086E+09 0.276515E+09 0.611135E+09 78466626.97
August 0.368613E+09 0.157822E+09 0.210790E+09 0.466576E+09 0.128833E+09
September 0.213831E+09 89323781.97 0.124507E+09 0.198563E+09 0.269392E+09
October 85460959.51 24858392.30 60602567.21 30762611.15 0.559859E+09
November 32925659.96 11493277.30 21432382.66 2252089.09 0.937560E+09
December 3027357.30 242591.52 2784765.78 0.00 0.106890E+10
           
Annual Sum or Average 0.293081E+10 0.127080E+10 0.166001E+10 0.324671E+10 0.609102E+10
Minimum of Months 3027357.30 242591.52 2784765.78 0.00 72142524.08
Maximum of Months 0.518108E+09 0.255487E+09 0.295070E+09 0.693968E+09 0.106890E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 4586409.53 0.00 4586409.53 0.00 0.547588E+09
February 18312140.33 0.00 18312140.33 0.00 0.446109E+09
March 54303148.56 4230.74 54298917.82 2615202.94 0.377123E+09
April 95500032.05 2271094.42 93228937.64 34883737.46 0.193891E+09
May 0.149964E+09 22649144.62 0.127315E+09 0.128497E+09 75350804.07
June 0.188770E+09 40950738.73 0.147819E+09 0.218670E+09 30052249.07
July 0.164776E+09 26541033.82 0.138235E+09 0.201395E+09 36924817.78
August 0.106215E+09 5653698.97 0.100561E+09 0.101382E+09 66605389.69
September 57022242.83 132701.96 56889540.87 22346156.14 0.148808E+09
October 28541372.39 0.00 28541372.39 1546465.70 0.311829E+09
November 8571672.55 0.00 8571672.55 0.00 0.516223E+09
December 1391275.71 0.00 1391275.71 0.00 0.571577E+09
           
Annual Sum or Average 0.877953E+09 98202643.25 0.779751E+09 0.711335E+09 0.332208E+10
Minimum of Months 1391275.71 0.00 1391275.71 0.00 30052249.07
Maximum of Months 0.188770E+09 40950738.73 0.147819E+09 0.218670E+09 0.571577E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 11486556.15 1705645.82 9780910.33 0.00 0.101817E+10
February 62244458.89 20902337.51 41342121.38 10096983.79 0.794690E+09
March 0.210447E+09 90391204.81 0.120056E+09 0.128386E+09 0.646620E+09
April 0.488484E+09 0.255487E+09 0.232997E+09 0.538883E+09 0.343345E+09
May 0.489583E+09 0.225450E+09 0.264133E+09 0.583870E+09 0.163359E+09
June 0.518108E+09 0.223038E+09 0.295070E+09 0.681940E+09 74584928.82
July 0.446602E+09 0.170086E+09 0.276515E+09 0.602844E+09 81489213.35
August 0.368613E+09 0.157822E+09 0.210790E+09 0.465316E+09 0.132028E+09
September 0.213831E+09 89323781.97 0.124507E+09 0.204837E+09 0.265753E+09
October 85460959.51 24858392.30 60602567.21 32750272.95 0.557238E+09
November 32925659.96 11493277.30 21432382.66 2360220.03 0.937252E+09
December 3027357.30 242591.52 2784765.78 0.00 0.106885E+10
           
Annual Sum or Average 0.293081E+10 0.127080E+10 0.166001E+10 0.325128E+10 0.608338E+10
Minimum of Months 3027357.30 242591.52 2784765.78 0.00 74584928.82
Maximum of Months 0.518108E+09 0.255487E+09 0.295070E+09 0.681940E+09 0.106885E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86686949.48 58614042.07 28072907.41 47069805.05 0.736852E+09
February 0.260142E+09 0.182677E+09 77465014.95 0.228816E+09 0.536227E+09
March 0.481950E+09 0.328296E+09 0.153654E+09 0.521616E+09 0.459908E+09
April 0.564831E+09 0.352086E+09 0.212745E+09 0.716330E+09 0.282077E+09
May 0.475806E+09 0.244673E+09 0.231133E+09 0.641869E+09 0.140719E+09
June 0.416819E+09 0.166702E+09 0.250117E+09 0.594480E+09 60489455.40
July 0.415493E+09 0.177294E+09 0.238199E+09 0.611925E+09 64641338.59
August 0.437255E+09 0.241086E+09 0.196170E+09 0.618300E+09 0.105180E+09
September 0.340707E+09 0.204711E+09 0.135995E+09 0.418217E+09 0.208372E+09
October 0.264046E+09 0.169454E+09 94592413.40 0.258268E+09 0.387248E+09
November 0.140218E+09 0.100136E+09 40082223.54 89078010.15 0.660638E+09
December 25726588.63 18403982.45 7322606.18 3344740.45 0.815571E+09
           
Annual Sum or Average 0.390968E+10 0.224413E+10 0.166555E+10 0.474931E+10 0.445792E+10
Minimum of Months 25726588.63 18403982.45 7322606.18 3344740.45 60489455.40
Maximum of Months 0.564831E+09 0.352086E+09 0.250117E+09 0.716330E+09 0.815571E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32103650.82 0.00 32103650.82 0.00 0.391016E+10
February 0.128180E+09 0.00 0.128180E+09 0.00 0.319563E+10
March 0.380108E+09 29614.08 0.380078E+09 13322064.38 0.271937E+10
April 0.668475E+09 15897058.81 0.652578E+09 0.245764E+09 0.138924E+10
May 0.104971E+10 0.158538E+09 0.891171E+09 0.942682E+09 0.539835E+09
June 0.132134E+10 0.286644E+09 0.103470E+10 0.163295E+10 0.213859E+09
July 0.115339E+10 0.185780E+09 0.967609E+09 0.149866E+10 0.262040E+09
August 0.743475E+09 39574393.91 0.703901E+09 0.761828E+09 0.469300E+09
September 0.399141E+09 928878.53 0.398212E+09 0.150705E+09 0.109117E+10
October 0.199782E+09 0.00 0.199782E+09 6245265.41 0.227717E+10
November 59999435.41 0.00 59999435.41 0.00 0.368420E+10
December 9738561.15 0.00 9738561.15 0.00 0.407197E+10
           
Annual Sum or Average 0.614544E+10 0.687392E+09 0.545805E+10 0.525216E+10 0.238239E+11
Minimum of Months 9738561.15 0.00 9738561.15 0.00 0.213859E+09
Maximum of Months 0.132134E+10 0.286644E+09 0.103470E+10 0.163295E+10 0.407197E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32103650.82 0.00 32103650.82 0.00 0.396270E+10
February 0.128180E+09 0.00 0.128180E+09 0.00 0.324375E+10
March 0.380108E+09 29614.08 0.380078E+09 11604139.96 0.277534E+10
April 0.668475E+09 15897058.81 0.652578E+09 0.230865E+09 0.143292E+10
May 0.104971E+10 0.158538E+09 0.891171E+09 0.911154E+09 0.558852E+09
June 0.132134E+10 0.286644E+09 0.103470E+10 0.160128E+10 0.223192E+09
July 0.115339E+10 0.185780E+09 0.967609E+09 0.146853E+10 0.273898E+09
August 0.743475E+09 39574393.91 0.703901E+09 0.737098E+09 0.488998E+09
September 0.399141E+09 928878.53 0.398212E+09 0.138763E+09 0.113783E+10
October 0.199782E+09 0.00 0.199782E+09 4477594.47 0.233771E+10
November 59999435.41 0.00 59999435.41 0.00 0.373449E+10
December 9738561.15 0.00 9738561.15 0.00 0.412296E+10
           
Annual Sum or Average 0.614544E+10 0.687392E+09 0.545805E+10 0.510377E+10 0.242926E+11
Minimum of Months 9738561.15 0.00 9738561.15 0.00 0.223192E+09
Maximum of Months 0.132134E+10 0.286644E+09 0.103470E+10 0.160128E+10 0.412296E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 4586409.53 0.00 4586409.53 0.00 0.459577E+09
February 18312140.33 0.00 18312140.33 21970.11 0.366374E+09
March 54303148.56 4230.74 54298917.82 14352264.05 0.303138E+09
April 95500032.05 2271094.42 93228937.64 96573284.78 0.161565E+09
May 0.149964E+09 22649144.62 0.127315E+09 0.238807E+09 69730404.21
June 0.188770E+09 40950738.73 0.147819E+09 0.349345E+09 29290683.75
July 0.164776E+09 26541033.82 0.138235E+09 0.332580E+09 34602415.36
August 0.106215E+09 5653698.97 0.100561E+09 0.215460E+09 56286708.05
September 57022242.83 132701.96 56889540.87 79889774.29 0.109092E+09
October 28541372.39 0.00 28541372.39 13335136.13 0.237401E+09
November 8571672.55 0.00 8571672.55 0.00 0.428757E+09
December 1391275.71 0.00 1391275.71 0.00 0.482437E+09
           
Annual Sum or Average 0.877953E+09 98202643.25 0.779751E+09 0.134036E+10 0.273825E+10
Minimum of Months 1391275.71 0.00 1391275.71 0.00 29290683.75
Maximum of Months 0.188770E+09 40950738.73 0.147819E+09 0.349345E+09 0.482437E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49235957.32 17301744.28 31934213.04 10209781.80 0.167422E+10
February 0.235448E+09 0.111749E+09 0.123699E+09 0.168330E+09 0.125374E+10
March 0.742223E+09 0.377968E+09 0.364254E+09 0.843696E+09 0.103405E+10
April 0.957370E+09 0.488603E+09 0.468767E+09 0.129997E+10 0.565472E+09
May 0.144777E+10 0.825176E+09 0.622598E+09 0.229823E+10 0.266123E+09
June 0.127699E+10 0.601750E+09 0.675243E+09 0.221799E+10 0.114815E+09
July 0.125850E+10 0.617916E+09 0.640581E+09 0.226906E+10 0.132436E+09
August 0.101224E+10 0.501330E+09 0.510911E+09 0.179362E+10 0.210289E+09
September 0.611146E+09 0.278788E+09 0.332358E+09 0.943142E+09 0.398563E+09
October 0.339193E+09 0.137158E+09 0.202035E+09 0.382149E+09 0.831365E+09
November 66256223.44 22869603.33 43386620.11 8933192.82 0.155060E+10
December 9604587.60 1955435.28 7649152.32 0.00 0.179941E+10
           
Annual Sum or Average 0.800598E+10 0.398256E+10 0.402342E+10 0.122353E+11 0.983108E+10
Minimum of Months 9604587.60 1955435.28 7649152.32 0.00 0.114815E+09
Maximum of Months 0.144777E+10 0.825176E+09 0.675243E+09 0.229823E+10 0.179941E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59107587.39 39966046.04 19141541.35 43950162.76 0.418859E+09
February 0.177378E+09 0.124558E+09 52819601.66 0.190370E+09 0.306568E+09
March 0.328618E+09 0.223849E+09 0.104769E+09 0.421150E+09 0.266410E+09
April 0.385131E+09 0.240070E+09 0.145060E+09 0.577787E+09 0.162726E+09
May 0.324429E+09 0.166831E+09 0.157598E+09 0.547935E+09 82190650.01
June 0.284208E+09 0.113666E+09 0.170542E+09 0.527538E+09 39736902.01
July 0.283304E+09 0.120888E+09 0.162416E+09 0.543493E+09 41683080.56
August 0.298143E+09 0.164385E+09 0.133758E+09 0.536314E+09 59383410.68
September 0.232311E+09 0.139583E+09 92728585.28 0.366858E+09 0.108079E+09
October 0.180040E+09 0.115542E+09 64497936.25 0.226991E+09 0.210572E+09
November 95607751.59 68277645.44 27330106.14 80603782.36 0.373917E+09
December 17541701.43 12548774.73 4992926.70 4392346.58 0.462973E+09
           
Annual Sum or Average 0.266582E+10 0.153016E+10 0.113565E+10 0.406738E+10 0.253310E+10
Minimum of Months 17541701.43 12548774.73 4992926.70 4392346.58 39736902.01
Maximum of Months 0.385131E+09 0.240070E+09 0.170542E+09 0.577787E+09 0.462973E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 5808398.29 0.00 5808398.29 0.00 0.727184E+09
February 23191170.29 0.00 23191170.29 0.00 0.595680E+09
March 68771511.32 5357.97 68766153.35 1907423.19 0.508527E+09
April 0.120945E+09 2876197.78 0.118069E+09 36161020.55 0.264541E+09
May 0.189920E+09 28683712.58 0.161236E+09 0.146153E+09 0.110000E+09
June 0.239066E+09 51861526.75 0.187204E+09 0.262958E+09 47065567.65
July 0.208679E+09 33612544.69 0.175066E+09 0.239404E+09 58548073.93
August 0.134514E+09 7160053.01 0.127354E+09 0.113764E+09 0.101694E+09
September 72215072.64 168058.66 72047013.98 20781420.91 0.213587E+09
October 36145847.27 0.00 36145847.27 756674.70 0.425170E+09
November 10855482.44 0.00 10855482.44 0.00 0.686403E+09
December 1761962.91 0.00 1761962.91 0.00 0.757551E+09
           
Annual Sum or Average 0.111187E+10 0.124367E+09 0.987505E+09 0.821887E+09 0.449595E+10
Minimum of Months 1761962.91 0.00 1761962.91 0.00 47065567.65
Maximum of Months 0.239066E+09 51861526.75 0.187204E+09 0.262958E+09 0.757551E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 5196795.96 0.00 5196795.96 0.00 0.650614E+09
February 20749227.93 0.00 20749227.93 0.00 0.532870E+09
March 61530131.75 4793.80 61525337.95 1706578.76 0.454981E+09
April 0.108210E+09 2573345.05 0.105636E+09 32353402.10 0.236686E+09
May 0.169922E+09 25663426.33 0.144259E+09 0.130764E+09 98417071.40
June 0.213893E+09 46400704.49 0.167492E+09 0.235270E+09 42109741.70
July 0.186705E+09 30073271.09 0.156632E+09 0.214196E+09 52383183.58
August 0.120350E+09 6406126.56 0.113944E+09 0.101785E+09 90986103.52
September 64611099.11 150362.72 64460736.40 18593216.03 0.191097E+09
October 32339826.50 0.00 32339826.50 676999.72 0.380354E+09
November 9712441.27 0.00 9712441.27 0.00 0.614127E+09
December 1576434.89 0.00 1576434.89 0.00 0.677784E+09
           
Annual Sum or Average 0.994797E+09 0.111272E+09 0.883525E+09 0.735345E+09 0.402241E+10
Minimum of Months 1576434.89 0.00 1576434.89 0.00 42109741.70
Maximum of Months 0.213893E+09 46400704.49 0.167492E+09 0.235270E+09 0.677784E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.220666E+09 0.149205E+09 71461077.76 0.115565E+09 0.194336E+10
February 0.662205E+09 0.465014E+09 0.197191E+09 0.579977E+09 0.140310E+10
March 0.122683E+10 0.835695E+09 0.391133E+09 0.133987E+10 0.119100E+10
April 0.143781E+10 0.896254E+09 0.541553E+09 0.183682E+10 0.742371E+09
May 0.121119E+10 0.622828E+09 0.588361E+09 0.161335E+10 0.418532E+09
June 0.106103E+10 0.424350E+09 0.636685E+09 0.146433E+10 0.211824E+09
July 0.105766E+10 0.451311E+09 0.606348E+09 0.150944E+10 0.225011E+09
August 0.111306E+10 0.613697E+09 0.499360E+09 0.154521E+10 0.334297E+09
September 0.867287E+09 0.521104E+09 0.346183E+09 0.106368E+10 0.569078E+09
October 0.672143E+09 0.431353E+09 0.240790E+09 0.658878E+09 0.101931E+10
November 0.356932E+09 0.254901E+09 0.102031E+09 0.219935E+09 0.173776E+10
December 65488398.61 46848315.40 18640083.20 7659981.42 0.215198E+10
           
Annual Sum or Average 0.995230E+10 0.571256E+10 0.423974E+10 0.119547E+11 0.119476E+11
Minimum of Months 65488398.61 46848315.40 18640083.20 7659981.42 0.211824E+09
Maximum of Months 0.143781E+10 0.896254E+09 0.636685E+09 0.183682E+10 0.215198E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 60.82 932.85 111.62 75.47 36.15 0.00 0.00
February 328.82 747.55 370.84 260.41 110.43 0.00 0.00
March 680.53 572.22 620.54 422.70 197.84 0.00 0.00
April 961.14 369.68 751.50 468.45 283.05 0.00 0.00
May 828.07 190.68 612.63 315.03 297.60 0.00 0.00
June 779.52 97.92 554.57 221.80 332.77 0.00 0.00
July 775.78 100.52 534.97 228.28 306.69 0.00 0.00
August 791.13 151.60 562.99 310.41 252.58 0.00 0.00
September 559.67 275.26 453.30 272.37 180.94 0.00 0.00
October 337.97 484.80 339.98 218.18 121.79 0.00 0.00
November 117.08 870.36 186.56 133.23 53.33 0.00 0.00
December 4.17 1034.55 33.12 23.70 9.43 0.00 0.00
               
Annual Sum or Average 519.35 484.42 427.54 245.41 182.13 0.00 0.00
Minimum of Months 4.17 97.92 33.12 23.70 9.43 0.00 0.00
Maximum of Months 961.14 1034.55 751.50 468.45 332.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 169.77 2604.97 314.30 212.52 101.78 0.00 0.00
February 921.27 2087.04 1044.25 733.30 310.96 0.00 0.00
March 1915.52 1596.60 1747.40 1190.30 557.10 0.00 0.00
April 2718.29 1025.72 2116.17 1319.11 797.05 0.00 0.00
May 2359.53 512.83 1725.12 887.11 838.01 0.00 0.00
June 2244.66 245.23 1561.63 624.56 937.07 0.00 0.00
July 2230.86 252.64 1506.45 642.81 863.63 0.00 0.00
August 2258.62 397.24 1585.35 874.11 711.25 0.00 0.00
September 1582.84 764.39 1276.48 766.96 509.51 0.00 0.00
October 948.40 1357.32 957.35 614.39 342.96 0.00 0.00
November 327.02 2429.91 525.33 375.16 150.17 0.00 0.00
December 11.58 2889.33 93.28 66.73 26.55 0.00 0.00
               
Annual Sum or Average 1475.90 1343.38 1203.93 691.05 512.88 0.00 0.00
Minimum of Months 11.58 245.23 93.28 66.73 26.55 0.00 0.00
Maximum of Months 2718.29 2889.33 2116.17 1319.11 937.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 217.92 3518.53 408.29 276.07 132.22 0.00 0.00
February 1197.62 2818.40 1356.54 952.59 403.95 0.00 0.00
March 2507.73 2160.07 2269.98 1546.27 723.70 0.00 0.00
April 3565.48 1397.34 2749.02 1713.60 1035.42 0.00 0.00
May 3083.68 719.81 2241.03 1152.41 1088.63 0.00 0.00
June 2924.58 355.23 2028.65 811.34 1217.31 0.00 0.00
July 2906.21 366.79 1956.96 835.05 1121.91 0.00 0.00
August 2946.24 565.72 2059.46 1135.51 923.95 0.00 0.00
September 2063.56 1069.59 1658.21 996.33 661.88 0.00 0.00
October 1233.38 1862.56 1243.65 798.13 445.53 0.00 0.00
November 421.23 3284.53 682.44 487.36 195.08 0.00 0.00
December 14.40 3896.49 121.17 86.68 34.49 0.00 0.00
               
Annual Sum or Average 1925.96 1829.88 1563.97 897.71 666.26 0.00 0.00
Minimum of Months 14.40 355.23 121.17 86.68 34.49 0.00 0.00
Maximum of Months 3565.48 3896.49 2749.02 1713.60 1217.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.47 558.18 26.36 15.56 10.80 0.00 0.00
February 39.06 449.66 99.05 60.13 38.92 0.00 0.00
March 159.47 336.01 201.26 117.32 83.94 0.00 0.00
April 387.13 199.53 337.04 191.19 145.86 0.00 0.00
May 381.54 95.74 303.92 146.46 157.46 0.00 0.00
June 425.59 43.85 309.54 129.90 179.63 0.00 0.00
July 385.62 46.09 272.52 108.64 163.88 0.00 0.00
August 332.71 74.64 248.94 120.30 128.64 0.00 0.00
September 184.64 155.22 172.12 88.31 83.81 0.00 0.00
October 61.72 290.21 99.13 52.42 46.71 0.00 0.00
November 9.35 522.90 49.59 30.78 18.81 0.00 0.00
December 0.00 607.26 7.68 4.78 2.90 0.00 0.00
               
Annual Sum or Average 198.06 280.79 177.47 88.82 88.65 0.00 0.00
Minimum of Months 0.00 43.85 7.68 4.78 2.90 0.00 0.00
Maximum of Months 425.59 607.26 337.04 191.19 179.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 588.15 6.00 0.64 5.36 0.00 0.00
February 1.07 513.23 33.30 8.64 24.66 0.00 0.00
March 40.48 375.94 98.85 33.75 65.10 0.00 0.00
April 216.76 203.41 225.30 99.44 125.86 0.00 0.00
May 259.42 81.46 238.78 92.63 146.15 0.00 0.00
June 345.26 34.51 272.72 101.85 170.87 0.00 0.00
July 299.38 40.57 228.26 73.41 154.85 0.00 0.00
August 209.89 71.30 177.28 61.03 116.25 0.00 0.00
September 84.70 159.98 104.50 34.51 69.98 0.00 0.00
October 9.90 324.37 42.56 9.28 33.28 0.00 0.00
November 0.27 565.28 16.01 4.43 11.58 0.00 0.00
December 0.00 616.21 1.65 0.09 1.56 0.00 0.00
               
Annual Sum or Average 122.82 296.72 120.78 43.41 77.36 0.00 0.00
Minimum of Months 0.00 34.51 1.65 0.09 1.56 0.00 0.00
Maximum of Months 345.26 616.21 272.72 101.85 170.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 10.82 131.55 17.65 11.93 5.72 0.00 0.00
February 55.82 105.18 58.65 41.18 17.46 0.00 0.00
March 110.24 86.57 98.13 66.85 31.29 0.00 0.00
April 145.66 71.16 118.84 74.08 44.76 0.00 0.00
May 122.91 41.78 96.88 49.82 47.06 0.00 0.00
June 114.93 23.01 87.70 35.08 52.63 0.00 0.00
July 114.75 23.65 84.60 36.10 48.50 0.00 0.00
August 117.80 34.13 89.03 49.09 39.94 0.00 0.00
September 82.06 58.64 71.69 43.07 28.61 0.00 0.00
October 51.25 82.57 53.76 34.50 19.26 0.00 0.00
November 20.80 121.89 29.50 21.07 8.43 0.00 0.00
December 0.84 146.80 5.24 3.75 1.49 0.00 0.00
               
Annual Sum or Average 79.05 77.11 67.61 38.81 28.80 0.00 0.00
Minimum of Months 0.84 23.01 5.24 3.75 1.49 0.00 0.00
Maximum of Months 145.66 146.80 118.84 74.08 52.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 168.30 1.37 0.00 1.37 0.00 0.00
February 0.00 152.21 6.06 0.00 6.06 0.00 0.00
March 0.57 116.38 16.22 0.00 16.22 0.00 0.00
April 10.80 60.77 29.48 0.70 28.78 0.00 0.00
May 40.10 22.29 44.80 6.77 38.03 0.00 0.00
June 71.24 8.82 58.27 12.64 45.63 0.00 0.00
July 62.87 10.60 49.22 7.93 41.29 0.00 0.00
August 31.83 19.44 31.73 1.69 30.04 0.00 0.00
September 6.46 47.98 17.60 0.04 17.56 0.00 0.00
October 0.26 97.30 8.53 0.00 8.53 0.00 0.00
November 0.00 164.53 2.65 0.00 2.65 0.00 0.00
December 0.00 175.56 0.42 0.00 0.42 0.00 0.00
               
Annual Sum or Average 18.79 86.66 22.27 2.49 19.78 0.00 0.00
Minimum of Months 0.00 8.82 0.42 0.00 0.42 0.00 0.00
Maximum of Months 71.24 175.56 58.27 12.64 45.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.13 553.46 31.26 18.15 13.11 0.00 0.00
February 68.38 441.80 121.99 74.59 47.40 0.00 0.00
March 243.53 329.03 261.26 154.14 107.12 0.00 0.00
April 370.56 189.40 333.28 186.88 146.40 0.00 0.00
May 507.53 86.30 391.42 216.34 175.07 0.00 0.00
June 492.66 36.51 356.00 159.94 196.06 0.00 0.00
July 488.08 40.93 340.72 160.49 180.23 0.00 0.00
August 406.75 68.86 300.29 154.97 145.32 0.00 0.00
September 231.45 148.90 207.53 107.63 99.89 0.00 0.00
October 105.46 285.52 130.54 68.74 61.80 0.00 0.00
November 8.59 521.73 49.67 30.75 18.91 0.00 0.00
December 0.00 605.80 8.34 5.05 3.29 0.00 0.00
               
Annual Sum or Average 245.10 274.88 211.48 111.67 99.81 0.00 0.00
Minimum of Months 0.00 36.51 8.34 5.05 3.29 0.00 0.00
Maximum of Months 507.53 605.80 391.42 216.34 196.06 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.11 579.38 10.90 3.23 7.67 0.00 0.00
February 13.05 486.69 56.24 23.10 33.14 0.00 0.00
March 112.01 354.58 158.84 70.57 88.28 0.00 0.00
April 196.49 189.90 221.54 95.14 126.40 0.00 0.00
May 395.39 82.86 326.28 162.51 163.77 0.00 0.00
June 421.37 34.71 319.18 131.89 187.29 0.00 0.00
July 406.32 40.70 296.47 125.27 171.20 0.00 0.00
August 288.61 69.73 228.63 95.71 132.93 0.00 0.00
September 129.37 151.84 139.90 53.83 86.06 0.00 0.00
October 40.81 305.94 73.98 25.61 48.37 0.00 0.00
November 0.06 564.66 16.09 4.41 11.68 0.00 0.00
December 0.00 614.65 2.31 0.37 1.95 0.00 0.00
               
Annual Sum or Average 168.01 288.61 154.78 66.26 88.52 0.00 0.00
Minimum of Months 0.00 34.71 2.31 0.37 1.95 0.00 0.00
Maximum of Months 421.37 614.65 326.28 162.51 187.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 6.55 696.02 41.21 25.86 15.35 0.00 0.00
February 66.30 561.32 140.19 89.23 50.96 0.00 0.00
March 197.20 426.39 247.77 144.84 102.93 0.00 0.00
April 347.51 256.21 321.36 162.03 159.33 0.00 0.00
May 362.10 106.77 306.97 122.60 184.36 0.00 0.00
June 414.23 45.84 316.26 103.38 212.87 0.00 0.00
July 398.84 54.35 289.94 95.40 194.55 0.00 0.00
August 338.66 93.10 261.65 110.02 151.62 0.00 0.00
September 202.18 196.59 193.46 93.41 100.04 0.00 0.00
October 89.96 364.07 134.96 74.76 60.20 0.00 0.00
November 16.03 653.37 69.66 45.65 24.01 0.00 0.00
December 0.00 760.54 12.25 8.12 4.13 0.00 0.00
               
Annual Sum or Average 203.97 350.18 194.75 89.49 105.27 0.00 0.00
Minimum of Months 0.00 45.84 12.25 8.12 4.13 0.00 0.00
Maximum of Months 414.23 760.54 321.36 162.03 212.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.53 554.57 26.36 15.56 10.80 0.00 0.00
February 39.59 446.52 99.05 60.13 38.92 0.00 0.00
March 160.12 334.24 201.26 117.32 83.94 0.00 0.00
April 385.73 198.39 337.04 191.19 145.86 0.00 0.00
May 379.52 94.84 303.92 146.46 157.46 0.00 0.00
June 423.12 43.24 309.54 129.90 179.63 0.00 0.00
July 383.48 45.43 272.52 108.64 163.88 0.00 0.00
August 331.26 73.67 248.94 120.30 128.64 0.00 0.00
September 184.83 153.31 172.12 88.31 83.81 0.00 0.00
October 62.42 288.02 99.13 52.42 46.71 0.00 0.00
November 9.65 517.90 49.59 30.78 18.81 0.00 0.00
December 0.00 603.50 7.68 4.78 2.90 0.00 0.00
               
Annual Sum or Average 197.47 278.66 177.47 88.82 88.65 0.00 0.00
Minimum of Months 0.00 43.24 7.68 4.78 2.90 0.00 0.00
Maximum of Months 423.12 603.50 337.04 191.19 179.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 584.59 6.00 0.64 5.36 0.00 0.00
February 1.13 509.85 33.30 8.64 24.66 0.00 0.00
March 40.73 374.04 98.85 33.75 65.10 0.00 0.00
April 216.21 202.12 225.30 99.44 125.86 0.00 0.00
May 257.84 80.99 238.78 92.63 146.15 0.00 0.00
June 341.77 34.69 272.72 101.85 170.87 0.00 0.00
July 296.69 40.63 228.26 73.41 154.85 0.00 0.00
August 208.35 70.93 177.28 61.03 116.25 0.00 0.00
September 85.35 157.64 104.50 34.51 69.98 0.00 0.00
October 10.30 321.97 42.56 9.28 33.28 0.00 0.00
November 0.28 560.13 16.01 4.43 11.58 0.00 0.00
December 0.00 612.47 1.65 0.09 1.56 0.00 0.00
               
Annual Sum or Average 122.11 294.70 120.78 43.41 77.36 0.00 0.00
Minimum of Months 0.00 34.69 1.65 0.09 1.56 0.00 0.00
Maximum of Months 341.77 612.47 272.72 101.85 170.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 17.57 275.11 32.37 21.88 10.48 0.00 0.00
February 94.58 221.65 107.53 75.51 32.02 0.00 0.00
March 194.75 171.71 179.94 122.57 57.37 0.00 0.00
April 276.36 108.83 217.91 135.84 82.08 0.00 0.00
May 239.65 52.54 177.65 91.35 86.30 0.00 0.00
June 229.35 23.34 160.81 64.31 96.50 0.00 0.00
July 228.47 24.13 155.13 66.19 88.93 0.00 0.00
August 230.85 39.27 163.25 90.01 73.24 0.00 0.00
September 161.35 80.39 131.45 78.98 52.47 0.00 0.00
October 96.43 144.58 98.58 63.27 35.32 0.00 0.00
November 34.37 254.88 54.10 38.63 15.46 0.00 0.00
December 1.25 304.50 9.61 6.87 2.73 0.00 0.00
               
Annual Sum or Average 150.60 141.36 123.98 71.16 52.81 0.00 0.00
Minimum of Months 1.25 23.34 9.61 6.87 2.73 0.00 0.00
Maximum of Months 276.36 304.50 217.91 135.84 96.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 1459.89 11.99 0.00 11.99 0.00 0.00
February 0.00 1320.94 52.98 0.00 52.98 0.00 0.00
March 4.97 1015.30 141.92 0.01 141.90 0.00 0.00
April 94.82 535.97 257.90 6.13 251.77 0.00 0.00
May 351.96 201.55 391.92 59.19 332.73 0.00 0.00
June 630.00 82.51 509.78 110.59 399.19 0.00 0.00
July 559.54 97.83 430.63 69.36 361.26 0.00 0.00
August 284.43 175.22 277.58 14.78 262.81 0.00 0.00
September 58.14 420.97 153.99 0.36 153.63 0.00 0.00
October 2.33 850.20 74.59 0.00 74.59 0.00 0.00
November 0.00 1421.37 23.15 0.00 23.15 0.00 0.00
December 0.00 1520.30 3.64 0.00 3.64 0.00 0.00
               
Annual Sum or Average 166.54 755.45 194.87 21.80 173.07 0.00 0.00
Minimum of Months 0.00 82.51 3.64 0.00 3.64 0.00 0.00
Maximum of Months 630.00 1520.30 509.78 110.59 399.19 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 1479.50 11.99 0.00 11.99 0.00 0.00
February 0.00 1340.84 52.98 0.00 52.98 0.00 0.00
March 4.33 1036.19 141.92 0.01 141.90 0.00 0.00
April 89.07 552.83 257.90 6.13 251.77 0.00 0.00
May 340.19 208.65 391.92 59.19 332.73 0.00 0.00
June 617.78 86.11 509.78 110.59 399.19 0.00 0.00
July 548.28 102.26 430.63 69.36 361.26 0.00 0.00
August 275.20 182.57 277.58 14.78 262.81 0.00 0.00
September 53.53 438.98 153.99 0.36 153.63 0.00 0.00
October 1.67 872.80 74.59 0.00 74.59 0.00 0.00
November 0.00 1440.78 23.15 0.00 23.15 0.00 0.00
December 0.00 1539.34 3.64 0.00 3.64 0.00 0.00
               
Annual Sum or Average 161.84 770.31 194.87 21.80 173.07 0.00 0.00
Minimum of Months 0.00 86.11 3.64 0.00 3.64 0.00 0.00
Maximum of Months 617.78 1539.34 509.78 110.59 399.19 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.44 940.27 42.16 21.38 20.78 0.00 0.00
February 108.85 756.99 178.22 97.68 80.54 0.00 0.00
March 449.61 570.73 420.08 224.69 195.39 0.00 0.00
April 753.13 334.71 554.78 282.00 272.78 0.00 0.00
May 1147.51 151.79 717.66 378.83 338.83 0.00 0.00
June 1190.45 67.37 675.14 291.81 383.34 0.00 0.00
July 1172.22 75.89 637.16 285.75 351.42 0.00 0.00
August 949.10 120.46 528.90 250.66 278.24 0.00 0.00
September 534.33 235.66 347.41 161.46 185.95 0.00 0.00
October 215.68 460.93 204.52 94.35 110.17 0.00 0.00
November 9.18 882.53 65.75 35.16 30.59 0.00 0.00
December 0.00 1023.16 10.65 5.42 5.24 0.00 0.00
               
Annual Sum or Average 547.53 466.97 366.24 177.92 188.32 0.00 0.00
Minimum of Months 0.00 67.37 10.65 5.42 5.24 0.00 0.00
Maximum of Months 1190.45 1023.16 717.66 378.83 383.34 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 22.14 1218.97 86.50 55.71 30.79 0.00 0.00
February 172.74 979.49 291.89 192.22 99.67 0.00 0.00
March 446.18 748.99 506.69 312.02 194.68 0.00 0.00
April 721.89 466.58 643.12 347.88 295.24 0.00 0.00
May 684.28 212.61 586.56 252.83 333.73 0.00 0.00
June 737.13 96.10 584.10 201.62 382.48 0.00 0.00
July 720.33 112.84 542.50 192.28 350.23 0.00 0.00
August 650.06 189.42 510.72 234.19 276.53 0.00 0.00
September 415.32 365.44 387.39 201.17 186.22 0.00 0.00
October 207.50 642.28 276.52 161.05 115.47 0.00 0.00
November 48.39 1135.72 145.64 98.34 47.30 0.00 0.00
December 0.11 1336.60 25.70 17.49 8.21 0.00 0.00
               
Annual Sum or Average 403.20 623.71 382.39 188.62 193.77 0.00 0.00
Minimum of Months 0.11 96.10 25.70 17.49 8.21 0.00 0.00
Maximum of Months 737.13 1336.60 643.12 347.88 382.48 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.162890E+09 0.249855E+10 0.298950E+09 0.202137E+09 96812571.55 0.00 0.00
February 0.795492E+09 0.180847E+10 0.897129E+09 0.629983E+09 0.267146E+09 0.00 0.00
March 0.182273E+10 0.153262E+10 0.166206E+10 0.113217E+10 0.529890E+09 0.00 0.00
April 0.249127E+10 0.958209E+09 0.194788E+10 0.121421E+10 0.733670E+09 0.00 0.00
May 0.221789E+10 0.510720E+09 0.164087E+10 0.843784E+09 0.797082E+09 0.00 0.00
June 0.202051E+10 0.253798E+09 0.143744E+10 0.574893E+09 0.862549E+09 0.00 0.00
July 0.207784E+10 0.269225E+09 0.143287E+10 0.611419E+09 0.821450E+09 0.00 0.00
August 0.211895E+10 0.406045E+09 0.150792E+10 0.831413E+09 0.676509E+09 0.00 0.00
September 0.145068E+10 0.713463E+09 0.117497E+10 0.705972E+09 0.468993E+09 0.00 0.00
October 0.905210E+09 0.129850E+10 0.910593E+09 0.584381E+09 0.326212E+09 0.00 0.00
November 0.303465E+09 0.225599E+10 0.483558E+09 0.345330E+09 0.138228E+09 0.00 0.00
December 11175695.43 0.277094E+10 88721138.45 63468308.89 25252829.55 0.00 0.00
               
Annual Sum or Average 0.163781E+11 0.152765E+11 0.134830E+11 0.773916E+10 0.574380E+10 0.00 0.00
Minimum of Months 11175695.43 0.253798E+09 88721138.45 63468308.89 25252829.55 0.00 0.00
Maximum of Months 0.249127E+10 0.277094E+10 0.194788E+10 0.121421E+10 0.862549E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.454708E+09 0.697716E+10 0.841824E+09 0.569206E+09 0.272618E+09 0.00 0.00
February 0.222874E+10 0.504897E+10 0.252626E+10 0.177399E+10 0.752267E+09 0.00 0.00
March 0.513053E+10 0.427632E+10 0.468024E+10 0.318811E+10 0.149214E+10 0.00 0.00
April 0.704580E+10 0.265867E+10 0.548510E+10 0.341914E+10 0.206597E+10 0.00 0.00
May 0.631977E+10 0.137355E+10 0.462057E+10 0.237604E+10 0.224453E+10 0.00 0.00
June 0.581816E+10 0.635632E+09 0.404774E+10 0.161886E+10 0.242888E+10 0.00 0.00
July 0.597513E+10 0.676683E+09 0.403486E+10 0.172171E+10 0.231315E+10 0.00 0.00
August 0.604948E+10 0.106397E+10 0.424621E+10 0.234120E+10 0.190500E+10 0.00 0.00
September 0.410272E+10 0.198130E+10 0.330862E+10 0.198797E+10 0.132065E+10 0.00 0.00
October 0.254020E+10 0.363545E+10 0.256417E+10 0.164558E+10 0.918591E+09 0.00 0.00
November 0.847637E+09 0.629832E+10 0.136167E+10 0.972426E+09 0.389241E+09 0.00 0.00
December 31020756.16 0.773877E+10 0.249833E+09 0.178723E+09 71110303.00 0.00 0.00
               
Annual Sum or Average 0.465439E+11 0.423648E+11 0.379671E+11 0.217930E+11 0.161741E+11 0.00 0.00
Minimum of Months 31020756.16 0.635632E+09 0.249833E+09 0.178723E+09 71110303.00 0.00 0.00
Maximum of Months 0.704580E+10 0.773877E+10 0.548510E+10 0.341914E+10 0.242888E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.583685E+09 0.942402E+10 0.109358E+10 0.739431E+09 0.354146E+09 0.00 0.00
February 0.289729E+10 0.681828E+10 0.328175E+10 0.230451E+10 0.977237E+09 0.00 0.00
March 0.671671E+10 0.578553E+10 0.607990E+10 0.414153E+10 0.193837E+10 0.00 0.00
April 0.924173E+10 0.362192E+10 0.712546E+10 0.444166E+10 0.268381E+10 0.00 0.00
May 0.825932E+10 0.192793E+10 0.600238E+10 0.308661E+10 0.291577E+10 0.00 0.00
June 0.758051E+10 0.920758E+09 0.525825E+10 0.210299E+10 0.315526E+10 0.00 0.00
July 0.778399E+10 0.982414E+09 0.524152E+10 0.223660E+10 0.300491E+10 0.00 0.00
August 0.789121E+10 0.151523E+10 0.551607E+10 0.304136E+10 0.247471E+10 0.00 0.00
September 0.534875E+10 0.277238E+10 0.429809E+10 0.258249E+10 0.171561E+10 0.00 0.00
October 0.330349E+10 0.498868E+10 0.333100E+10 0.213770E+10 0.119330E+10 0.00 0.00
November 0.109183E+10 0.851349E+10 0.176888E+10 0.126324E+10 0.505646E+09 0.00 0.00
December 38566041.44 0.104364E+11 0.324547E+09 0.232171E+09 92376330.53 0.00 0.00
               
Annual Sum or Average 0.607371E+11 0.577070E+11 0.493214E+11 0.283103E+11 0.210111E+11 0.00 0.00
Minimum of Months 38566041.44 0.920758E+09 0.324547E+09 0.232171E+09 92376330.53 0.00 0.00
Maximum of Months 0.924173E+10 0.104364E+11 0.712546E+10 0.444166E+10 0.315526E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 3939501.86 0.149504E+10 70594143.54 41671691.87 28922451.68 0.00 0.00
February 94495356.96 0.108782E+10 0.239622E+09 0.145461E+09 94161723.04 0.00 0.00
March 0.427132E+09 0.899976E+09 0.539065E+09 0.314240E+09 0.224825E+09 0.00 0.00
April 0.100344E+10 0.517182E+09 0.873614E+09 0.495557E+09 0.378057E+09 0.00 0.00
May 0.102191E+10 0.256430E+09 0.814011E+09 0.392281E+09 0.421731E+09 0.00 0.00
June 0.110314E+10 0.113648E+09 0.802317E+09 0.336704E+09 0.465613E+09 0.00 0.00
July 0.103285E+10 0.123438E+09 0.729906E+09 0.290974E+09 0.438932E+09 0.00 0.00
August 0.891131E+09 0.199907E+09 0.666756E+09 0.322207E+09 0.344549E+09 0.00 0.00
September 0.478582E+09 0.402331E+09 0.446142E+09 0.228907E+09 0.217236E+09 0.00 0.00
October 0.165318E+09 0.777290E+09 0.265501E+09 0.140401E+09 0.125101E+09 0.00 0.00
November 24222374.77 0.135537E+10 0.128533E+09 79770922.75 48762488.80 0.00 0.00
December 0.00 0.162648E+10 20569058.73 12791366.25 7777692.48 0.00 0.00
               
Annual Sum or Average 0.624616E+10 0.885491E+10 0.559663E+10 0.280097E+10 0.279567E+10 0.00 0.00
Minimum of Months 0.00 0.113648E+09 20569058.73 12791366.25 7777692.48 0.00 0.00
Maximum of Months 0.110314E+10 0.162648E+10 0.873614E+09 0.495557E+09 0.465613E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.157530E+10 16072965.68 1705645.82 14367319.86 0.00 0.00
February 2576665.96 0.124159E+10 80556599.21 20902337.51 59654261.70 0.00 0.00
March 0.108425E+09 0.100692E+10 0.264750E+09 90395435.55 0.174355E+09 0.00 0.00
April 0.561836E+09 0.527235E+09 0.583984E+09 0.257758E+09 0.326226E+09 0.00 0.00
May 0.694837E+09 0.218195E+09 0.639547E+09 0.248099E+09 0.391448E+09 0.00 0.00
June 0.894921E+09 89437631.95 0.706878E+09 0.263989E+09 0.442890E+09 0.00 0.00
July 0.801865E+09 0.108671E+09 0.611378E+09 0.196627E+09 0.414751E+09 0.00 0.00
August 0.562182E+09 0.190978E+09 0.474827E+09 0.163476E+09 0.311351E+09 0.00 0.00
September 0.219552E+09 0.414656E+09 0.270853E+09 89456483.93 0.181397E+09 0.00 0.00
October 26502988.71 0.868802E+09 0.114002E+09 24858392.30 89143939.60 0.00 0.00
November 709844.77 0.146521E+10 41497332.51 11493277.30 30004055.21 0.00 0.00
December 0.00 0.165045E+10 4418633.01 242591.52 4176041.49 0.00 0.00
               
Annual Sum or Average 0.387341E+10 0.935745E+10 0.380877E+10 0.136900E+10 0.243976E+10 0.00 0.00
Minimum of Months 0.00 89437631.95 4418633.01 242591.52 4176041.49 0.00 0.00
Maximum of Months 0.894921E+09 0.165045E+10 0.706878E+09 0.263989E+09 0.442890E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 28989861.54 0.352341E+09 47276667.86 31966479.56 15310188.30 0.00 0.00
February 0.135037E+09 0.254445E+09 0.141874E+09 99626911.10 42247279.48 0.00 0.00
March 0.295277E+09 0.231871E+09 0.262842E+09 0.179044E+09 83798449.73 0.00 0.00
April 0.377546E+09 0.184459E+09 0.308043E+09 0.192018E+09 0.116025E+09 0.00 0.00
May 0.329196E+09 0.111904E+09 0.259491E+09 0.133438E+09 0.126053E+09 0.00 0.00
June 0.297900E+09 59653020.76 0.227322E+09 90914864.02 0.136407E+09 0.00 0.00
July 0.307343E+09 63342382.82 0.226598E+09 96691123.43 0.129907E+09 0.00 0.00
August 0.315511E+09 91411132.20 0.238467E+09 0.131482E+09 0.106985E+09 0.00 0.00
September 0.212701E+09 0.152005E+09 0.185812E+09 0.111644E+09 74168118.18 0.00 0.00
October 0.137269E+09 0.221153E+09 0.144003E+09 92415349.65 51588089.52 0.00 0.00
November 53919967.42 0.315930E+09 76470993.25 54611255.65 21859737.60 0.00 0.00
December 2249051.53 0.393182E+09 14030570.84 10037023.69 3993547.15 0.00 0.00
               
Annual Sum or Average 0.249294E+10 0.243170E+10 0.213223E+10 0.122389E+10 0.908343E+09 0.00 0.00
Minimum of Months 2249051.53 59653020.76 14030570.84 10037023.69 3993547.15 0.00 0.00
Maximum of Months 0.377546E+09 0.393182E+09 0.308043E+09 0.192018E+09 0.136407E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.450762E+09 3669613.99 0.00 3669613.99 0.00 0.00
February 0.00 0.368224E+09 14651654.16 0.00 14651654.16 0.00 0.00
March 1536978.83 0.311717E+09 43448277.40 3385.04 43444892.36 0.00 0.00
April 27999774.95 0.157519E+09 76410152.90 1817116.37 74593036.53 0.00 0.00
May 0.107399E+09 59688391.87 0.119987E+09 18121717.51 0.101865E+09 0.00 0.00
June 0.184646E+09 22860141.16 0.151036E+09 32764933.58 0.118271E+09 0.00 0.00
July 0.168390E+09 28397646.68 0.131838E+09 21235641.59 0.110603E+09 0.00 0.00
August 85251864.80 52073101.43 84983063.64 4523558.72 80459504.93 0.00 0.00
September 16746025.46 0.124377E+09 45623841.16 106175.64 45517665.52 0.00 0.00
October 691320.40 0.260620E+09 22836124.56 0.00 22836124.56 0.00 0.00
November 0.00 0.426454E+09 6858247.02 0.00 6858247.02 0.00 0.00
December 0.00 0.470226E+09 1113168.11 0.00 1113168.11 0.00 0.00
               
Annual Sum or Average 0.592662E+09 0.273292E+10 0.702456E+09 78572528.46 0.623883E+09 0.00 0.00
Minimum of Months 0.00 22860141.16 1113168.11 0.00 1113168.11 0.00 0.00
Maximum of Months 0.184646E+09 0.470226E+09 0.151036E+09 32764933.58 0.118271E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 13727985.08 0.148239E+10 83727314.36 48617532.54 35109781.82 0.00 0.00
February 0.165433E+09 0.106879E+10 0.295110E+09 0.180437E+09 0.114673E+09 0.00 0.00
March 0.652258E+09 0.881261E+09 0.699755E+09 0.412846E+09 0.286909E+09 0.00 0.00
April 0.960480E+09 0.490929E+09 0.863850E+09 0.484389E+09 0.379460E+09 0.00 0.00
May 0.135936E+10 0.231139E+09 0.104837E+10 0.579448E+09 0.468919E+09 0.00 0.00
June 0.127698E+10 94633540.02 0.922750E+09 0.414563E+09 0.508188E+09 0.00 0.00
July 0.130729E+10 0.109618E+09 0.912597E+09 0.429868E+09 0.482729E+09 0.00 0.00
August 0.108943E+10 0.184436E+09 0.804299E+09 0.415067E+09 0.389232E+09 0.00 0.00
September 0.599926E+09 0.385937E+09 0.537906E+09 0.278986E+09 0.258919E+09 0.00 0.00
October 0.282467E+09 0.764735E+09 0.349649E+09 0.184126E+09 0.165523E+09 0.00 0.00
November 22257405.22 0.135232E+10 0.128738E+09 79713259.18 49024956.81 0.00 0.00
December 0.00 0.162256E+10 22344336.28 13526561.80 8817774.48 0.00 0.00
               
Annual Sum or Average 0.772960E+10 0.866876E+10 0.666909E+10 0.352159E+10 0.314751E+10 0.00 0.00
Minimum of Months 0.00 94633540.02 22344336.28 13526561.80 8817774.48 0.00 0.00
Maximum of Months 0.135936E+10 0.162256E+10 0.104837E+10 0.579448E+09 0.508188E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 305264.15 0.155180E+10 29206136.50 8651486.50 20554650.00 0.00 0.00
February 31564858.34 0.117741E+10 0.136044E+09 55878597.63 80165831.89 0.00 0.00
March 0.299994E+09 0.949704E+09 0.425441E+09 0.189002E+09 0.236439E+09 0.00 0.00
April 0.509295E+09 0.492210E+09 0.574219E+09 0.246590E+09 0.327629E+09 0.00 0.00
May 0.105902E+10 0.221929E+09 0.873903E+09 0.435267E+09 0.438636E+09 0.00 0.00
June 0.109220E+10 89957550.53 0.827312E+09 0.341847E+09 0.485465E+09 0.00 0.00
July 0.108829E+10 0.109003E+09 0.794069E+09 0.335521E+09 0.458548E+09 0.00 0.00
August 0.773022E+09 0.186777E+09 0.612371E+09 0.256336E+09 0.356035E+09 0.00 0.00
September 0.335314E+09 0.393564E+09 0.362617E+09 0.139536E+09 0.223080E+09 0.00 0.00
October 0.109299E+09 0.819429E+09 0.198150E+09 68583779.27 0.129566E+09 0.00 0.00
November 163975.52 0.146360E+10 41702136.95 11435613.74 30266523.22 0.00 0.00
December 0.00 0.164628E+10 6193910.56 977787.07 5216123.49 0.00 0.00
               
Annual Sum or Average 0.529846E+10 0.910166E+10 0.488123E+10 0.208963E+10 0.279160E+10 0.00 0.00
Minimum of Months 0.00 89957550.53 6193910.56 977787.07 5216123.49 0.00 0.00
Maximum of Months 0.109220E+10 0.164628E+10 0.873903E+09 0.435267E+09 0.485465E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 17534393.70 0.186421E+10 0.110385E+09 69262471.62 41122534.82 0.00 0.00
February 0.160395E+09 0.135793E+10 0.339142E+09 0.215864E+09 0.123279E+09 0.00 0.00
March 0.528191E+09 0.114203E+10 0.663629E+09 0.387945E+09 0.275684E+09 0.00 0.00
April 0.900756E+09 0.664105E+09 0.832974E+09 0.419986E+09 0.412987E+09 0.00 0.00
May 0.969853E+09 0.285960E+09 0.822178E+09 0.328381E+09 0.493797E+09 0.00 0.00
June 0.107369E+10 0.118810E+09 0.819737E+09 0.267967E+09 0.551770E+09 0.00 0.00
July 0.106827E+10 0.145572E+09 0.776581E+09 0.255506E+09 0.521075E+09 0.00 0.00
August 0.907070E+09 0.249371E+09 0.700794E+09 0.294684E+09 0.406110E+09 0.00 0.00
September 0.524047E+09 0.509570E+09 0.501440E+09 0.242131E+09 0.259308E+09 0.00 0.00
October 0.240944E+09 0.975132E+09 0.361486E+09 0.200238E+09 0.161248E+09 0.00 0.00
November 41538453.59 0.169354E+10 0.180549E+09 0.118327E+09 62221235.15 0.00 0.00
December 0.00 0.203702E+10 32811840.63 21747439.13 11064401.50 0.00 0.00
               
Annual Sum or Average 0.643229E+10 0.110433E+11 0.614171E+10 0.282204E+10 0.331967E+10 0.00 0.00
Minimum of Months 0.00 0.118810E+09 32811840.63 21747439.13 11064401.50 0.00 0.00
Maximum of Months 0.107369E+10 0.203702E+10 0.832974E+09 0.419986E+09 0.551770E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 4087063.13 0.148537E+10 70594143.54 41671691.87 28922451.68 0.00 0.00
February 95783317.91 0.108023E+10 0.239622E+09 0.145461E+09 94161723.04 0.00 0.00
March 0.428873E+09 0.895236E+09 0.539065E+09 0.314240E+09 0.224825E+09 0.00 0.00
April 0.999808E+09 0.514222E+09 0.873614E+09 0.495557E+09 0.378057E+09 0.00 0.00
May 0.101650E+10 0.254029E+09 0.814011E+09 0.392281E+09 0.421731E+09 0.00 0.00
June 0.109672E+10 0.112081E+09 0.802317E+09 0.336704E+09 0.465613E+09 0.00 0.00
July 0.102712E+10 0.121684E+09 0.729906E+09 0.290974E+09 0.438932E+09 0.00 0.00
August 0.887244E+09 0.197328E+09 0.666756E+09 0.322207E+09 0.344549E+09 0.00 0.00
September 0.479090E+09 0.397382E+09 0.446142E+09 0.228907E+09 0.217236E+09 0.00 0.00
October 0.167196E+09 0.771445E+09 0.265501E+09 0.140401E+09 0.125101E+09 0.00 0.00
November 25003895.96 0.134241E+10 0.128533E+09 79770922.75 48762488.80 0.00 0.00
December 0.00 0.161642E+10 20569058.73 12791366.25 7777692.48 0.00 0.00
               
Annual Sum or Average 0.622743E+10 0.878783E+10 0.559663E+10 0.280097E+10 0.279567E+10 0.00 0.00
Minimum of Months 0.00 0.112081E+09 20569058.73 12791366.25 7777692.48 0.00 0.00
Maximum of Months 0.109672E+10 0.161642E+10 0.873614E+09 0.495557E+09 0.465613E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.156575E+10 16072965.68 1705645.82 14367319.86 0.00 0.00
February 2737421.37 0.123344E+10 80556599.21 20902337.51 59654261.70 0.00 0.00
March 0.109086E+09 0.100183E+10 0.264750E+09 90395435.55 0.174355E+09 0.00 0.00
April 0.560423E+09 0.523892E+09 0.583984E+09 0.257758E+09 0.326226E+09 0.00 0.00
May 0.690586E+09 0.216930E+09 0.639547E+09 0.248099E+09 0.391448E+09 0.00 0.00
June 0.885880E+09 89907776.65 0.706878E+09 0.263989E+09 0.442890E+09 0.00 0.00
July 0.794651E+09 0.108826E+09 0.611378E+09 0.196627E+09 0.414751E+09 0.00 0.00
August 0.558045E+09 0.189981E+09 0.474827E+09 0.163476E+09 0.311351E+09 0.00 0.00
September 0.221226E+09 0.408604E+09 0.270853E+09 89456483.93 0.181397E+09 0.00 0.00
October 27581041.29 0.862352E+09 0.114002E+09 24858392.30 89143939.60 0.00 0.00
November 729310.78 0.145184E+10 41497332.51 11493277.30 30004055.21 0.00 0.00
December 0.00 0.164043E+10 4418633.01 242591.52 4176041.49 0.00 0.00
               
Annual Sum or Average 0.385095E+10 0.929379E+10 0.380877E+10 0.136900E+10 0.243976E+10 0.00 0.00
Minimum of Months 0.00 89907776.65 4418633.01 242591.52 4176041.49 0.00 0.00
Maximum of Months 0.885880E+09 0.164043E+10 0.706878E+09 0.263989E+09 0.442890E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 47069805.05 0.736852E+09 86686949.48 58614042.07 28072907.41 0.00 0.00
February 0.228816E+09 0.536227E+09 0.260142E+09 0.182677E+09 77465014.95 0.00 0.00
March 0.521616E+09 0.459908E+09 0.481950E+09 0.328296E+09 0.153654E+09 0.00 0.00
April 0.716330E+09 0.282077E+09 0.564831E+09 0.352086E+09 0.212745E+09 0.00 0.00
May 0.641869E+09 0.140719E+09 0.475806E+09 0.244673E+09 0.231133E+09 0.00 0.00
June 0.594480E+09 60489455.40 0.416819E+09 0.166702E+09 0.250117E+09 0.00 0.00
July 0.611925E+09 64641338.59 0.415493E+09 0.177294E+09 0.238199E+09 0.00 0.00
August 0.618300E+09 0.105180E+09 0.437255E+09 0.241086E+09 0.196170E+09 0.00 0.00
September 0.418217E+09 0.208372E+09 0.340707E+09 0.204711E+09 0.135995E+09 0.00 0.00
October 0.258268E+09 0.387248E+09 0.264046E+09 0.169454E+09 94592413.40 0.00 0.00
November 89078010.15 0.660638E+09 0.140218E+09 0.100136E+09 40082223.54 0.00 0.00
December 3344740.45 0.815571E+09 25726588.63 18403982.45 7322606.18 0.00 0.00
               
Annual Sum or Average 0.474931E+10 0.445792E+10 0.390968E+10 0.224413E+10 0.166555E+10 0.00 0.00
Minimum of Months 3344740.45 60489455.40 25726588.63 18403982.45 7322606.18 0.00 0.00
Maximum of Months 0.716330E+09 0.815571E+09 0.564831E+09 0.352086E+09 0.250117E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.391016E+10 32103650.82 0.00 32103650.82 0.00 0.00
February 0.00 0.319563E+10 0.128180E+09 0.00 0.128180E+09 0.00 0.00
March 13322064.38 0.271937E+10 0.380108E+09 29614.08 0.380078E+09 0.00 0.00
April 0.245764E+09 0.138924E+10 0.668475E+09 15897058.81 0.652578E+09 0.00 0.00
May 0.942682E+09 0.539835E+09 0.104971E+10 0.158538E+09 0.891171E+09 0.00 0.00
June 0.163295E+10 0.213859E+09 0.132134E+10 0.286644E+09 0.103470E+10 0.00 0.00
July 0.149866E+10 0.262040E+09 0.115339E+10 0.185780E+09 0.967609E+09 0.00 0.00
August 0.761828E+09 0.469300E+09 0.743475E+09 39574393.91 0.703901E+09 0.00 0.00
September 0.150705E+09 0.109117E+10 0.399141E+09 928878.53 0.398212E+09 0.00 0.00
October 6245265.41 0.227717E+10 0.199782E+09 0.00 0.199782E+09 0.00 0.00
November 0.00 0.368420E+10 59999435.41 0.00 59999435.41 0.00 0.00
December 0.00 0.407197E+10 9738561.15 0.00 9738561.15 0.00 0.00
               
Annual Sum or Average 0.525216E+10 0.238239E+11 0.614544E+10 0.687392E+09 0.545805E+10 0.00 0.00
Minimum of Months 0.00 0.213859E+09 9738561.15 0.00 9738561.15 0.00 0.00
Maximum of Months 0.163295E+10 0.407197E+10 0.132134E+10 0.286644E+09 0.103470E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.396270E+10 32103650.82 0.00 32103650.82 0.00 0.00
February 0.00 0.324375E+10 0.128180E+09 0.00 0.128180E+09 0.00 0.00
March 11604139.96 0.277534E+10 0.380108E+09 29614.08 0.380078E+09 0.00 0.00
April 0.230865E+09 0.143292E+10 0.668475E+09 15897058.81 0.652578E+09 0.00 0.00
May 0.911154E+09 0.558852E+09 0.104971E+10 0.158538E+09 0.891171E+09 0.00 0.00
June 0.160128E+10 0.223192E+09 0.132134E+10 0.286644E+09 0.103470E+10 0.00 0.00
July 0.146853E+10 0.273898E+09 0.115339E+10 0.185780E+09 0.967609E+09 0.00 0.00
August 0.737098E+09 0.488998E+09 0.743475E+09 39574393.91 0.703901E+09 0.00 0.00
September 0.138763E+09 0.113783E+10 0.399141E+09 928878.53 0.398212E+09 0.00 0.00
October 4477594.47 0.233771E+10 0.199782E+09 0.00 0.199782E+09 0.00 0.00
November 0.00 0.373449E+10 59999435.41 0.00 59999435.41 0.00 0.00
December 0.00 0.412296E+10 9738561.15 0.00 9738561.15 0.00 0.00
               
Annual Sum or Average 0.510377E+10 0.242926E+11 0.614544E+10 0.687392E+09 0.545805E+10 0.00 0.00
Minimum of Months 0.00 0.223192E+09 9738561.15 0.00 9738561.15 0.00 0.00
Maximum of Months 0.160128E+10 0.412296E+10 0.132134E+10 0.286644E+09 0.103470E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 19935200.78 0.251843E+10 0.112930E+09 57267790.32 55662163.92 0.00 0.00
February 0.263340E+09 0.183130E+10 0.431138E+09 0.236308E+09 0.194830E+09 0.00 0.00
March 0.120424E+10 0.152865E+10 0.112514E+10 0.601821E+09 0.523322E+09 0.00 0.00
April 0.195212E+10 0.867557E+09 0.143800E+10 0.730945E+09 0.707056E+09 0.00 0.00
May 0.307349E+10 0.406557E+09 0.192217E+10 0.101466E+10 0.907511E+09 0.00 0.00
June 0.308566E+10 0.174623E+09 0.174997E+10 0.756367E+09 0.993605E+09 0.00 0.00
July 0.313967E+10 0.203265E+09 0.170658E+10 0.765345E+09 0.941232E+09 0.00 0.00
August 0.254206E+10 0.322627E+09 0.141660E+10 0.671368E+09 0.745230E+09 0.00 0.00
September 0.138498E+10 0.610822E+09 0.900479E+09 0.418503E+09 0.481976E+09 0.00 0.00
October 0.577685E+09 0.123455E+10 0.547775E+09 0.252700E+09 0.295075E+09 0.00 0.00
November 23793991.09 0.228753E+10 0.170436E+09 91147248.77 79288398.81 0.00 0.00
December 4323.44 0.274043E+10 28537564.74 14504210.00 14033354.74 0.00 0.00
               
Annual Sum or Average 0.172670E+11 0.147263E+11 0.115498E+11 0.561093E+10 0.593882E+10 0.00 0.00
Minimum of Months 4323.44 0.174623E+09 28537564.74 14504210.00 14033354.74 0.00 0.00
Maximum of Months 0.313967E+10 0.274043E+10 0.192217E+10 0.101466E+10 0.993605E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 59304073.85 0.326489E+10 0.231671E+09 0.149205E+09 82466272.00 0.00 0.00
February 0.417903E+09 0.236957E+10 0.706145E+09 0.465014E+09 0.241132E+09 0.00 0.00
March 0.119506E+10 0.200609E+10 0.135713E+10 0.835705E+09 0.521425E+09 0.00 0.00
April 0.187113E+10 0.120939E+10 0.166696E+10 0.901704E+09 0.765258E+09 0.00 0.00
May 0.183276E+10 0.569448E+09 0.157103E+10 0.677175E+09 0.893856E+09 0.00 0.00
June 0.191064E+10 0.249080E+09 0.151399E+10 0.522612E+09 0.991381E+09 0.00 0.00
July 0.192934E+10 0.302242E+09 0.145304E+10 0.514997E+09 0.938046E+09 0.00 0.00
August 0.174113E+10 0.507339E+09 0.136792E+10 0.627263E+09 0.740659E+09 0.00 0.00
September 0.107652E+10 0.947227E+09 0.100411E+10 0.521422E+09 0.482691E+09 0.00 0.00
October 0.555769E+09 0.172029E+10 0.740629E+09 0.431353E+09 0.309276E+09 0.00 0.00
November 0.125432E+09 0.294379E+10 0.377500E+09 0.254901E+09 0.122599E+09 0.00 0.00
December 283279.19 0.357994E+10 68826796.40 46848315.40 21978481.00 0.00 0.00
               
Annual Sum or Average 0.127153E+11 0.196693E+11 0.120590E+11 0.594820E+10 0.611077E+10 0.00 0.00
Minimum of Months 283279.19 0.249080E+09 68826796.40 46848315.40 21978481.00 0.00 0.00
Maximum of Months 0.192934E+10 0.357994E+10 0.166696E+10 0.901704E+09 0.991381E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -17.6 -17.9 -19.9 1.62 -32.2 4.20 17.57 0.00
February -15.4 -16.0 -18.9 1.58 -31.2 17.68 68.90 0.00
March -10.3 -11.6 -17.1 2.46 -25.4 47.11 147.56 0.00
April 0.73 -2.7 -8.8 3.74 -14.2 75.81 230.75 0.00
May 10.60 5.25 -1.5 3.99 -2.1 92.54 252.99 0.00
June 15.96 10.88 6.41 3.45 5.66 116.77 222.76 0.00
July 16.86 12.85 9.90 2.85 7.58 107.92 197.90 0.00
August 14.24 10.70 7.59 2.94 4.33 81.01 176.65 0.00
September 6.72 4.45 1.76 2.11 -4.1 51.38 110.92 0.00
October -3.1 -4.4 -7.1 2.79 -14.3 26.50 62.95 0.00
November -17.6 -18.1 -20.3 0.70 -32.8 8.03 31.72 0.00
December -19.3 -19.6 -21.9 1.25 -33.6 1.27 5.23 0.00
                 
Annual Sum or Average -1.4 -3.8 -7.4 2.46 -14.3 52.69 127.40 0.00
Minimum of Months -19.3 -19.6 -21.9 0.70 -33.6 1.27 5.23 0.00
Maximum of Months 16.86 12.85 9.90 3.99 7.58 116.77 252.99 0.00



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 21-JAN-20:00 -2.7 -5.6 0.00 -9.0 0.00 0.00
February 2.80 08-FEB-15:09 -0.7 -6.5 2.68 -7.9 21.67 32.33
March 6.70 20-MAR-14:09 2.60 -3.5 1.37 -7.5 138.33 487.67
April 15.60 22-APR-13:00 7.03 -3.3 4.10 -0.8 117.50 760.50
May 22.20 31-MAY-15:00 10.79 -1.1 3.10 7.75 143.50 516.50
June 28.30 30-JUN-14:00 17.30 10.60 6.20 17.57 223.50 277.50
July 30.00 29-JUL-16:19 18.34 11.70 4.67 18.88 163.67 322.83
August 25.60 11-AUG-15:00 14.77 6.70 6.20 12.22 99.50 604.00
September 17.20 07-SEP-15:00 8.91 0.00 1.50 2.64 77.00 480.50
October 13.90 01-OCT-14:00 8.01 1.70 2.60 1.58 78.50 227.50
November -3.9 18-NOV-03:00 -5.6 -8.9 1.50 -12.4 0.00 0.00
December 1.70 24-DEC-11:00 -0.1 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -3.9   -5.6 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 30.00   18.34 11.70 6.20 18.88 223.50 760.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -38.3 12-JAN-05:00 -38.4 -40.4 0.00 -60.9 0.00 0.00
February -36.1 27-FEB-04:00 -36.2 -39.4 0.00 -58.7 0.00 0.00
March -28.9 01-MAR-00:10 -29.2 -34.0 0.65 -51.0 0.00 0.00
April -21.7 03-APR-05:00 -22.3 -27.2 2.60 -42.7 0.00 0.00
May 0.00 27-MAY-03:00 -1.1 -2.8 6.20 -7.1 29.00 14.00
June 3.30 02-JUN-03:00 2.38 1.10 1.50 -11.2 45.50 266.00
July 7.20 31-JUL-03:49 6.67 6.10 2.18 -7.6 0.00 0.00
August -1.7 31-AUG-05:00 -2.9 -5.0 2.60 -18.6 25.00 538.50
September -5.6 29-SEP-06:00 -6.1 -7.2 2.60 -21.6 0.00 0.00
October -20.6 22-OCT-05:00 -20.8 -22.2 2.60 -40.2 0.00 0.00
November -30.0 29-NOV-09:00 -30.2 -33.3 0.00 -51.8 0.00 0.00
December -33.9 15-DEC-07:00 -34.0 -37.8 0.00 -56.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -38.3   -38.4 -40.4 0.00 -60.9 0.00 0.00
Maximum of Months 7.20   6.67 6.10 6.20 -7.1 45.50 538.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -2.7 21-JAN-20:00 -1.1 -5.6 0.00 -9.0 0.00 0.00
February 1.24 09-FEB-01:00 2.80 -1.1 8.80 -4.1 0.00 0.00
March 2.65 20-MAR-13:00 6.70 -3.3 0.00 -7.6 139.00 515.00
April 7.03 22-APR-13:00 15.60 -3.3 4.10 -0.8 117.50 760.50
May 10.97 31-MAY-17:00 21.70 0.00 2.60 11.07 73.50 187.00
June 18.33 30-JUN-11:00 25.60 14.40 1.50 15.21 221.00 616.00
July 18.36 29-JUL-17:19 29.07 12.23 3.10 19.29 141.00 225.33
August 16.14 04-AUG-19:00 21.70 12.80 3.10 14.28 25.50 28.50
September 10.82 01-SEP-15:00 15.60 6.70 2.60 4.31 145.50 176.00
October 8.01 01-OCT-14:00 13.90 1.70 2.60 1.58 78.50 227.50
November -5.6 18-NOV-03:00 -3.9 -8.9 1.50 -12.4 0.00 0.00
December -0.1 24-DEC-11:00 1.70 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -5.6   -3.9 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 18.36   29.07 14.40 8.80 19.29 221.00 760.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 06-JAN-19:00 -1.7 -2.7 2.60 -12.4 0.00 0.00
February -0.6 09-FEB-00:00 1.70 0.78 3.60 -5.0 0.00 0.00
March 0.00 21-MAR-15:00 1.10 0.62 2.10 -5.5 70.50 4.00
April 0.00 30-APR-07:00 3.30 1.91 2.60 -8.3 198.00 170.00
May 6.10 16-MAY-19:00 8.90 7.49 5.20 3.69 16.00 15.00
June 15.60 30-JUN-17:00 18.90 16.75 3.60 12.22 99.50 223.00
July 17.80 03-JUL-14:00 19.40 18.27 1.50 10.11 223.00 401.50
August 15.00 12-AUG-22:00 16.10 15.38 0.00 12.79 0.00 0.00
September 8.90 04-SEP-11:00 10.00 9.41 2.60 5.33 238.50 0.50
October 5.60 02-OCT-11:09 7.30 6.41 4.95 0.30 123.67 16.00
November -8.3 18-NOV-04:00 -5.0 -6.1 1.50 -13.4 0.00 0.00
December -2.8 24-DEC-09:00 1.10 -0.5 3.10 -6.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -8.3   -5.0 -6.1 0.00 -13.4 0.00 0.00
Maximum of Months 17.80   19.40 18.27 5.20 12.79 238.50 401.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 0.00 1.10 0.00
February 18.00 13.00 16.00 0.00 5.89 0.00
March 18.00 13.00 16.00 0.00 18.25 0.00
April 18.00 13.00 16.00 0.00 35.02 0.00
May 18.00 13.00 16.00 0.44 43.39 0.00
June 18.00 13.00 16.00 2.62 46.67 0.00
July 18.00 13.00 16.00 4.74 42.09 0.00
August 18.00 13.00 16.00 6.08 32.30 0.00
September 18.00 13.00 16.00 6.25 18.21 0.00
October 18.00 13.00 16.00 5.21 8.04 0.00
November 18.00 13.00 16.00 3.27 2.12 0.00
December 18.00 13.00 16.00 0.94 0.28 0.00
             
Annual Sum or Average 18.00 13.00 16.00 2.48 21.19 0.00
Minimum of Months 18.00 13.00 16.00 0.00 0.28 0.00
Maximum of Months 18.00 13.00 16.00 6.25 46.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770420E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -161417322.4 81.21 0.00 0.00
February 0.696176E+10 -0.681596E+10 0.00 0.00 672.00 0.00 -145793971.8 81.21 0.00 0.00
March 0.770288E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161414242.1 81.21 0.00 0.00
April 0.746479E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156207603.9 81.21 0.00 0.00
May 0.770421E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161414559.7 81.21 0.00 0.00
June 0.745674E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156206421.7 81.21 0.00 0.00
July 0.771226E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161412271.2 81.21 0.00 0.00
August 0.770422E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -161413146.8 81.21 0.00 0.00
September 0.746614E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -156206979.0 81.21 0.00 0.00
October 0.770285E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161413969.3 81.21 0.00 0.00
November 0.744863E+10 -0.729242E+10 0.00 0.00 720.00 0.00 -156207555.7 81.21 0.00 0.00
December 0.771227E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161415155.1 81.21 0.00 0.00
                     
Annual Sum or Average 0.907410E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190052E+10 81.21 0.00 0.00
Minimum of Months 0.696176E+10 -0.755085E+10 0.00 0.00 672.00 0.00 -161417322.4 81.21 0.00 0.00
Maximum of Months 0.771227E+10 -0.681596E+10 0.00 0.00 744.00 0.00 -145793971.8 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.129593E+12 -0.127852E+12 0.00 0.00 744.00 0.00 -0.174111E+10 79.61 0.00 0.00
February 0.117062E+12 -0.115474E+12 0.00 0.00 672.00 0.00 -0.158777E+10 79.61 0.00 0.00
March 0.129606E+12 -0.127846E+12 0.00 0.00 744.00 0.00 -0.175968E+10 79.61 0.00 0.00
April 0.125423E+12 -0.123722E+12 0.00 0.00 720.00 0.00 -0.170155E+10 79.61 0.00 0.00
May 0.129540E+12 -0.127780E+12 0.00 0.00 744.00 0.00 -0.176042E+10 79.72 0.00 0.00
June 0.125056E+12 -0.123341E+12 0.00 0.00 720.00 0.00 -0.171528E+10 80.30 0.00 0.00
July 0.128910E+12 -0.127137E+12 0.00 0.00 744.00 0.00 -0.177233E+10 80.85 0.00 0.00
August 0.128703E+12 -0.126939E+12 0.00 0.00 744.00 0.00 -0.176370E+10 81.20 0.00 0.00
September 0.124521E+12 -0.122823E+12 0.00 0.00 720.00 0.00 -0.169759E+10 81.25 0.00 0.00
October 0.128819E+12 -0.127075E+12 0.00 0.00 744.00 0.00 -0.174442E+10 80.97 0.00 0.00
November 0.124938E+12 -0.123259E+12 0.00 0.00 720.00 0.00 -0.167912E+10 80.46 0.00 0.00
December 0.129446E+12 -0.127716E+12 0.00 0.00 744.00 0.00 -0.173003E+10 79.85 0.00 0.00
                     
Annual Sum or Average 0.152162E+13 -0.150096E+13 0.00 0.00 8760.00 0.00 -0.206530E+11 80.26 0.00 0.00
Minimum of Months 0.117062E+12 -0.127852E+12 0.00 0.00 672.00 0.00 -0.177233E+10 79.61 0.00 0.00
Maximum of Months 0.129606E+12 -0.115474E+12 0.00 0.00 744.00 0.00 -0.158777E+10 81.25 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.877489E+11 -0.861969E+11 0.00 0.00 744.00 0.00 -0.155201E+10 58.99 0.00 0.00
February 0.792938E+11 -0.778710E+11 0.00 0.00 672.00 0.00 -0.142283E+10 58.99 0.00 0.00
March 0.878524E+11 -0.862746E+11 0.00 0.00 744.00 0.00 -0.157775E+10 58.99 0.00 0.00
April 0.849701E+11 -0.834451E+11 0.00 0.00 720.00 0.00 -0.152499E+10 58.99 0.00 0.00
May 0.871672E+11 -0.855933E+11 0.00 0.00 744.00 0.00 -0.157391E+10 58.99 0.00 0.00
June 0.812974E+11 -0.797813E+11 0.00 0.00 720.00 0.00 -0.151607E+10 58.99 0.00 0.00
July 0.808100E+11 -0.792668E+11 0.00 0.00 744.00 0.00 -0.154318E+10 58.99 0.00 0.00
August 0.788999E+11 -0.773834E+11 0.00 0.00 744.00 0.00 -0.151648E+10 58.98 0.00 0.00
September 0.760624E+11 -0.746093E+11 0.00 0.00 720.00 0.00 -0.145305E+10 58.98 0.00 0.00
October 0.800705E+11 -0.785711E+11 0.00 0.00 744.00 0.00 -0.149933E+10 58.98 0.00 0.00
November 0.802491E+11 -0.787899E+11 0.00 0.00 720.00 0.00 -0.145915E+10 58.99 0.00 0.00
December 0.863450E+11 -0.848186E+11 0.00 0.00 744.00 0.00 -0.152634E+10 58.99 0.00 0.00
                     
Annual Sum or Average 0.990766E+12 -0.972601E+12 0.00 0.00 8760.00 0.00 -0.181651E+11 58.99 0.00 0.00
Minimum of Months 0.760624E+11 -0.862746E+11 0.00 0.00 672.00 0.00 -0.157775E+10 58.98 0.00 0.00
Maximum of Months 0.878524E+11 -0.746093E+11 0.00 0.00 744.00 0.00 -0.142283E+10 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.89 0.86 10-JAN-10:00 641.77 26.49 72.50 78.00 460.94 28.18 72.67 46.17
February 205.83 0.87 0.86 01-FEB-11:39 2399.03 35.42 190.33 184.17 1938.44 36.46 191.83 159.83
March 329.50 0.87 0.86 01-MAR-08:39 5603.77 33.37 281.83 308.83 3032.50 31.28 281.50 277.33
April 421.83 0.87 0.86 01-APR-07:40 7804.10 30.17 260.83 391.83 872.36 21.82 300.83 329.00
May 545.00 0.88 0.86 01-MAY-05:30 3509.30 21.08 133.17 462.67 642.30 20.47 316.83 377.17
June 583.50 0.88 0.86 01-JUN-05:30 1552.54 17.89 93.00 489.33 613.84 20.07 304.00 386.83
July 562.83 0.88 0.86 01-JUL-04:00 1928.52 18.57 105.50 485.83 625.96 20.19 309.00 381.83
August 467.17 0.87 0.86 01-AUG-05:00 5361.35 25.76 226.17 415.17 694.96 20.77 265.83 341.17
September 356.33 0.87 0.86 01-SEP-06:30 4562.56 30.90 274.83 326.50 1248.07 23.33 218.83 275.33
October 265.50 0.87 0.86 01-OCT-07:49 2513.13 33.10 241.50 241.00 1985.09 34.11 244.83 212.83
November 135.83 0.88 0.86 01-NOV-09:50 944.03 32.77 117.50 128.83 696.34 34.09 117.67 96.50
December 71.17 0.94 0.86 04-DEC-11:30 151.56 5.40 0.00 14.67 90.75 8.89 0.00 2.00
                         
Annual Sum or Average 4053.17 0.88     3587.96 25.40 1997.17 3526.83 1054.56 23.84 2623.83 2886.00
Minimum of Months 71.17 0.87 0.86   151.56 5.40 0.00 14.67 90.75 8.89 0.00 2.00
Maximum of Months 583.50 0.94 0.86   7804.10 35.42 281.83 489.33 3032.50 36.46 316.83 386.83



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.36 0.22 03-JAN-11:39 754.80 27.01 72.67 89.00 572.06 28.66 72.83 65.33
February 205.83 0.27 0.22 01-FEB-10:50 2701.37 35.55 190.50 191.33 2239.70 36.57 192.50 177.33
March 329.50 0.26 0.22 01-MAR-08:30 6050.82 33.59 285.00 314.83 3480.40 31.35 275.83 298.50
April 421.83 0.26 0.22 01-APR-07:10 8267.09 30.66 277.67 404.67 1333.53 21.92 299.00 369.50
May 545.00 0.29 0.22 01-MAY-04:00 3829.83 21.70 163.83 485.00 961.46 20.81 334.17 436.17
June 583.50 0.29 0.22 01-JUN-04:40 1823.07 18.56 103.83 519.00 883.09 20.57 341.83 455.17
July 562.83 0.29 0.22 01-JUL-04:19 2206.70 19.25 120.17 511.67 903.26 20.65 324.17 445.50
August 467.17 0.27 0.22 01-AUG-04:00 5698.55 26.39 243.33 432.67 1031.42 21.11 282.00 390.83
September 356.33 0.27 0.22 01-SEP-05:00 4884.27 31.21 279.50 337.67 1566.88 23.66 235.00 304.83
October 265.50 0.27 0.22 01-OCT-07:40 2778.67 33.23 242.33 249.67 2248.34 34.23 246.17 231.00
November 135.83 0.29 0.22 01-NOV-09:30 1111.53 33.02 117.67 141.00 863.15 34.32 117.67 115.83
December 71.17 0.58 0.22 04-DEC-10:00 171.21 6.96 0.00 28.33 109.02 10.37 0.00 11.33
                         
Annual Sum or Average 4053.17 0.28     3902.05 25.90 2096.50 3704.83 1367.39 24.17 2721.17 3301.33
Minimum of Months 71.17 0.26 0.22   171.21 6.96 0.00 28.33 109.02 10.37 0.00 11.33
Maximum of Months 583.50 0.58 0.22   8267.09 35.55 285.00 519.00 3480.40 36.57 341.83 455.17



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.82 0.65 31-JAN-11:30 130.82 7.60 0.00 20.00 64.11 11.59 0.00 0.00
February 205.83 0.70 0.60 04-FEB-11:30 288.96 11.97 0.00 147.67 139.76 15.97 0.00 29.17
March 329.50 0.64 0.60 01-MAR-09:20 513.79 15.01 0.00 294.17 244.61 18.83 2.83 216.83
April 421.83 0.62 0.60 01-APR-07:30 646.42 17.17 10.17 408.83 324.89 20.90 74.00 359.50
May 545.00 0.62 0.60 01-MAY-04:49 802.40 19.34 89.00 506.83 394.37 23.24 216.50 478.50
June 583.50 0.62 0.60 01-JUN-03:30 1002.81 20.98 149.17 550.50 482.14 23.58 298.33 511.17
July 562.83 0.62 0.60 01-JUL-03:30 908.73 20.20 125.00 538.50 417.34 22.80 232.67 484.83
August 467.17 0.62 0.60 01-AUG-04:40 687.73 17.52 35.00 440.17 330.02 21.46 104.50 381.17
September 356.33 0.64 0.60 01-SEP-05:00 503.76 14.91 0.00 321.50 232.18 18.58 5.17 224.83
October 265.50 0.67 0.60 01-OCT-07:00 359.94 13.01 0.00 218.17 159.54 16.76 0.00 49.00
November 135.83 0.78 0.60 01-NOV-13:09 177.22 9.50 0.00 51.50 84.66 13.79 0.00 0.00
December 71.17 0.93 0.80 04-DEC-11:30 48.16 2.94 0.00 0.00 24.36 6.42 0.00 0.00
                         
Annual Sum or Average 4053.17 0.65     659.59 16.80 408.33 3497.83 315.07 20.29 934.00 2735.00
Minimum of Months 71.17 0.62 0.60   48.16 2.94 0.00 0.00 24.36 6.42 0.00 0.00
Maximum of Months 583.50 0.93 0.80   1002.81 20.98 149.17 550.50 482.14 23.58 298.33 511.17



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.82 0.65 31-JAN-11:30 130.82 7.60 0.00 20.00 64.11 11.59 0.00 0.00
February 205.83 0.70 0.60 04-FEB-11:30 288.96 11.97 0.00 147.67 139.76 15.97 0.00 29.17
March 329.50 0.64 0.60 01-MAR-09:20 513.79 15.01 0.00 294.17 244.61 18.83 2.83 216.83
April 421.83 0.62 0.60 01-APR-07:30 646.42 17.17 10.17 408.83 324.89 20.90 74.00 359.50
May 545.00 0.62 0.60 01-MAY-04:49 802.40 19.34 89.00 506.83 394.37 23.24 216.50 478.50
June 583.50 0.62 0.60 01-JUN-03:30 1002.81 20.98 149.17 550.50 482.14 23.58 298.33 511.17
July 562.83 0.62 0.60 01-JUL-03:30 908.73 20.20 125.00 538.50 417.34 22.80 232.67 484.83
August 467.17 0.62 0.60 01-AUG-04:40 687.73 17.52 35.00 440.17 330.02 21.46 104.67 381.17
September 356.33 0.64 0.60 01-SEP-05:00 503.76 14.91 0.00 321.50 232.18 18.58 5.17 224.83
October 265.50 0.67 0.60 01-OCT-07:00 359.94 13.01 0.00 218.17 159.54 16.76 0.00 49.00
November 135.83 0.78 0.60 01-NOV-13:09 177.22 9.50 0.00 51.50 84.66 13.79 0.00 0.00
December 71.17 0.93 0.80 04-DEC-11:30 48.16 2.94 0.00 0.00 24.36 6.42 0.00 0.00
                         
Annual Sum or Average 4053.17 0.65     659.59 16.80 408.33 3497.83 315.07 20.29 934.17 2735.00
Minimum of Months 71.17 0.62 0.60   48.16 2.94 0.00 0.00 24.36 6.42 0.00 0.00
Maximum of Months 583.50 0.93 0.80   1002.81 20.98 149.17 550.50 482.14 23.58 298.33 511.17



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.285969E+12 485118.06 12-JAN-21:10 0.00 0.00 0.00 0.00 0.00
February 0.243284E+12 434984.98 27-FEB-06:20 0.00 0.00 0.00 0.00 0.00
March 0.122636E+12 379433.74 01-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 0.454593E+11 96826.63 23-APR-22:30 0.00 0.00 0.00 0.00 0.00
May 0.373137E+11 89863.28 27-MAY-06:40 0.00 0.00 0.00 0.00 0.00
June 0.284555E+10 63824.45 02-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.124513E+10 27922.28 31-JUL-03:00 0.00 0.00 0.00 0.00 0.00
August 0.858843E+10 90423.35 30-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.608925E+11 97405.08 28-SEP-22:40 0.00 0.00 0.00 0.00 0.00
October 0.527326E+11 95711.41 16-OCT-22:40 0.00 0.00 0.00 0.00 0.00
November 0.262631E+12 389786.94 29-NOV-20:00 0.00 0.00 0.00 0.00 0.00
December 0.345540E+12 433381.19 15-DEC-07:52 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.146914E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124513E+10 27922.28   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.345540E+12 485118.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.941818E+09 3028.70 13-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 0.145593E+10 4343.97 27-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.958912E+09 4101.53 17-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.696656E+09 4377.74 30-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 39008438.25 2568.45 01-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.409233E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145593E+10 4377.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.535715E+10 3739.64 12-JAN-10:50 0.00 0.00 0.00 0.00 0.00
February 0.361226E+10 2961.55 27-FEB-08:10 0.00 0.00 0.00 0.00 0.00
March 0.226028E+10 2709.88 01-MAR-08:10 0.00 0.00 0.00 0.00 0.00
April 0.546419E+09 1682.10 03-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 36008852.53 627.76 27-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 7676276.74 341.33 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.379634E+09 1077.08 30-SEP-06:55 0.00 0.00 0.00 0.00 0.00
October 0.198440E+10 2141.57 27-OCT-08:20 0.00 0.00 0.00 0.00 0.00
November 0.482494E+10 3158.01 29-NOV-10:20 0.00 0.00 0.00 0.00 0.00
December 0.593906E+10 3441.35 15-DEC-11:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.249478E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.593906E+10 3739.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128146E+10 1182.70 12-JAN-10:51 0.00 0.00 0.00 0.00 0.00
February 0.902944E+09 1001.15 27-FEB-10:51 0.00 0.00 0.00 0.00 0.00
March 0.560285E+09 858.19 01-MAR-10:10 0.00 0.00 0.00 0.00 0.00
April 90567021.40 686.20 03-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 856587.43 190.46 27-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 39687896.02 435.26 25-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.360003E+09 713.73 26-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.110995E+10 1029.23 29-NOV-10:10 0.00 0.00 0.00 0.00 0.00
December 0.142190E+10 1121.21 15-DEC-14:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.576766E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142190E+10 1182.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.129282E+10 1472.70 12-JAN-15:00 0.00 0.00 0.00 0.00 0.00
February 0.898210E+09 1266.23 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.367665E+09 1092.63 01-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 13738353.89 313.99 03-APR-04:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 63887636.77 432.25 31-OCT-09:53 0.00 0.00 0.00 0.00 0.00
November 0.104877E+10 1140.43 30-NOV-11:10 0.00 0.00 0.00 0.00 0.00
December 0.153744E+10 1301.89 15-DEC-14:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.522253E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153744E+10 1472.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.285468E+10 1632.29 12-JAN-15:00 0.00 0.00 0.00 0.00 0.00
February 0.236956E+10 1457.44 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.210737E+10 1332.50 01-MAR-04:50 0.00 0.00 0.00 0.00 0.00
April 0.898225E+09 985.46 03-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 70323026.67 399.92 27-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 1269.60 4.23 25-JUN-17:00 0.00 0.00 0.00 0.00 0.00
July 270554.98 65.49 06-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 6499165.07 322.04 31-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.332775E+09 632.45 30-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.140397E+10 1052.80 30-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.265477E+10 1430.99 30-NOV-10:59 0.00 0.00 0.00 0.00 0.00
December 0.299808E+10 1536.90 15-DEC-13:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.156965E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1269.60 4.23   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.299808E+10 1632.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122507E+11 11586.67 12-JAN-10:50 0.00 0.00 0.00 0.00 0.00
February 0.786242E+10 8516.93 27-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 0.429049E+10 7415.69 01-MAR-08:07 0.00 0.00 0.00 0.00 0.00
April 0.118624E+10 6182.90 03-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 0.243512E+09 3963.83 27-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.119005E+09 2970.63 27-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.116143E+09 3800.53 05-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.260957E+09 3541.70 07-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.144555E+10 5289.83 27-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.451306E+10 7642.39 30-OCT-08:40 0.00 0.00 0.00 0.00 0.00
November 0.109234E+11 10247.66 29-NOV-10:10 0.00 0.00 0.00 0.00 0.00
December 0.136968E+11 11033.47 15-DEC-10:51 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.569083E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.116143E+09 2970.63   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.136968E+11 11586.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.134807E+11 20719.02 12-JAN-10:50 0.00 0.00 0.00 0.00 0.00
February 0.767443E+10 17101.08 27-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 0.298265E+10 12661.63 01-MAR-09:03 0.00 0.00 0.00 0.00 0.00
April 0.317345E+09 8796.74 04-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 87854714.49 5099.02 27-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.244737E+10 11466.78 29-OCT-15:00 0.00 0.00 0.00 0.00 0.00
November 0.111150E+11 18028.38 29-NOV-10:10 0.00 0.00 0.00 0.00 0.00
December 0.151562E+11 19828.29 15-DEC-14:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.532615E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.151562E+11 20719.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.189150E+11 12874.23 12-JAN-15:00 0.00 0.00 0.00 0.00 0.00
February 0.138272E+11 10500.91 27-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 0.964501E+10 9009.80 01-MAR-08:10 0.00 0.00 0.00 0.00 0.00
April 0.218809E+10 6349.41 03-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.138041E+10 4924.23 27-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.847112E+10 8367.61 27-OCT-08:20 0.00 0.00 0.00 0.00 0.00
November 0.173367E+11 11222.86 29-NOV-10:20 0.00 0.00 0.00 0.00 0.00
December 0.205456E+11 12631.09 15-DEC-14:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.923091E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.205456E+11 12874.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.103475E+11 8096.94 12-JAN-10:40 0.00 0.00 0.00 0.00 0.00
February 0.735817E+10 6494.90 27-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.447164E+10 5687.70 01-MAR-08:10 0.00 0.00 0.00 0.00 0.00
April 0.755315E+09 3538.02 03-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.155207E+09 1492.82 30-SEP-06:57 0.00 0.00 0.00 0.00 0.00
October 0.310229E+10 4084.19 27-OCT-08:20 0.00 0.00 0.00 0.00 0.00
November 0.968397E+10 6716.27 29-NOV-10:20 0.00 0.00 0.00 0.00 0.00
December 0.114277E+11 7275.56 15-DEC-10:53 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.473018E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114277E+11 8096.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.417325E+10 8011.21 12-JAN-14:50 0.00 0.00 0.00 0.00 0.00
February 0.312021E+10 6680.83 27-FEB-10:10 0.00 0.00 0.00 0.00 0.00
March 0.214063E+10 6580.04 15-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.577175E+09 5477.64 03-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 40796390.65 2990.12 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 4213414.29 1370.31 02-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 5426794.60 1542.95 31-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 37647946.95 3680.29 31-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.236224E+09 4642.19 28-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.151595E+10 5885.63 30-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.392350E+10 6995.54 29-NOV-10:53 0.00 0.00 0.00 0.00 0.00
December 0.449570E+10 7430.41 15-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.202707E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4213414.29 1370.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.449570E+10 8011.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.252049E+10 6736.15 12-JAN-14:50 0.00 0.00 0.00 0.00 0.00
February 0.171572E+10 5266.70 27-FEB-10:10 0.00 0.00 0.00 0.00 0.00
March 0.896136E+09 4947.44 01-MAR-11:50 0.00 0.00 0.00 0.00 0.00
April 0.123399E+09 3810.08 03-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 2251875.73 1086.52 02-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 4449438.80 2244.35 31-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 17682739.46 2977.69 28-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.507820E+09 4219.52 30-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.234722E+10 5560.14 29-NOV-15:00 0.00 0.00 0.00 0.00 0.00
December 0.276193E+10 6060.89 15-DEC-14:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.108971E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.276193E+10 6736.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.334004E+11 57391.21 12-JAN-07:50 0.00 0.00 0.00 0.00 0.00
February 0.300976E+11 56405.38 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.164610E+11 53071.28 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.211547E+10 9202.22 03-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 10444.39 0.61 14-MAY-15:40 0.00 0.00 0.00 0.00 0.00
June 25277.82 0.65 28-JUN-23:40 0.00 0.00 0.00 0.00 0.00
July 29959.91 0.66 21-JUL-20:00 0.00 0.00 0.00 0.00 0.00
August 2765097.98 497.08 31-AUG-06:00 0.00 0.00 0.00 0.00 0.00
September 0.118353E+09 2114.78 29-SEP-06:50 0.00 0.00 0.00 0.00 0.00
October 0.417402E+10 9266.40 27-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.320821E+11 53579.22 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.403366E+11 55355.43 15-DEC-07:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.158788E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10444.39 0.61   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.403366E+11 57391.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111284E+11 13954.20 23-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.824557E+10 13954.39 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.580950E+10 13951.82 08-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.164985E+10 13948.15 05-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.180109E+09 4805.11 10-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 11092537.06 4548.82 08-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 15773554.81 5099.69 26-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 79810153.61 4808.13 31-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 0.120746E+10 13754.53 27-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.479688E+10 13954.41 19-OCT-15:11 0.00 0.00 0.00 0.00 0.00
November 0.101883E+11 13953.70 18-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.120943E+11 13953.30 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.554070E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 11092537.06 4548.82   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120943E+11 13954.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.114296E+11 13391.27 23-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.912172E+10 13391.60 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.710916E+10 13391.90 21-MAR-15:11 0.00 0.00 0.00 0.00 0.00
April 0.225033E+10 13385.73 02-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.223804E+09 5199.24 19-MAY-15:14 0.00 0.00 0.00 0.00 0.00
June 5951435.68 4336.54 06-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 10093764.16 4307.07 04-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 0.100531E+09 7156.12 31-AUG-08:61 0.00 0.00 0.00 0.00 0.00
September 0.155372E+10 13305.17 29-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.549328E+10 13395.86 09-OCT-15:11 0.00 0.00 0.00 0.00 0.00
November 0.106770E+11 13390.86 18-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.122009E+11 13390.47 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.601761E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5951435.68 4307.07   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122009E+11 13395.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.345913E+11 32362.40 12-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.141203E+11 23514.04 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.175498E+10 21257.31 01-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.102679E+10 11683.08 30-OCT-04:00 0.00 0.00 0.00 0.00 0.00
November 0.278302E+11 24255.61 29-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.426000E+11 28774.53 15-DEC-15:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121924E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.426000E+11 32362.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.482868E+11 76152.32 17-JAN-16:11 0.00 0.00 0.00 0.00 0.00
February 0.384223E+11 76135.69 04-FEB-16:11 0.00 0.00 0.00 0.00 0.00
March 0.283114E+11 76115.14 04-MAR-16:11 0.00 0.00 0.00 0.00 0.00
April 0.749803E+10 74816.93 02-APR-15:11 0.00 0.00 0.00 0.00 0.00
May 0.107589E+09 33524.01 02-MAY-15:14 0.00 0.00 0.00 0.00 0.00
June 9382918.84 14901.73 21-JUN-21:56 0.00 0.00 0.00 0.00 0.00
July 16011941.76 16737.58 16-JUL-16:36 0.00 0.00 0.00 0.00 0.00
August 88984608.94 17100.38 30-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.183680E+10 73452.52 30-SEP-15:12 0.00 0.00 0.00 0.00 0.00
October 0.164526E+11 76127.74 31-OCT-15:11 0.00 0.00 0.00 0.00 0.00
November 0.449910E+11 76154.37 18-NOV-16:11 0.00 0.00 0.00 0.00 0.00
December 0.524633E+11 76149.31 31-DEC-16:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.238484E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9382918.84 14901.73   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.524633E+11 76154.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.110466E+11 13610.14 23-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.789616E+10 13610.33 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.507467E+10 13602.71 05-MAR-16:11 0.00 0.00 0.00 0.00 0.00
April 0.161492E+10 13564.45 03-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.126716E+09 4714.20 03-MAY-15:14 0.00 0.00 0.00 0.00 0.00
June 5826092.10 4354.14 24-JUN-15:14 0.00 0.00 0.00 0.00 0.00
July 7988114.64 4704.14 26-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 60050896.68 4920.19 30-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 0.101057E+10 13406.87 27-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.438835E+10 13610.33 19-OCT-15:11 0.00 0.00 0.00 0.00 0.00
November 0.101812E+11 13609.74 18-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.120868E+11 13609.32 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.534999E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5826092.10 4354.14   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120868E+11 13610.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.113368E+11 13054.87 23-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.872960E+10 13055.18 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.620967E+10 13052.35 17-MAR-15:11 0.00 0.00 0.00 0.00 0.00
April 0.222839E+10 13048.55 03-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.167121E+09 4920.79 17-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 3834532.66 3799.11 28-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 6386047.85 4021.82 04-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 73924285.72 4248.19 29-AUG-15:14 0.00 0.00 0.00 0.00 0.00
September 0.130125E+10 12949.48 27-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.502643E+10 13058.72 20-OCT-15:11 0.00 0.00 0.00 0.00 0.00
November 0.106699E+11 13054.45 18-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.121872E+11 13054.06 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.579405E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3834532.66 3799.11   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121872E+11 13058.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.368300E+10 4003.49 23-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.278502E+10 4003.58 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.201977E+10 4004.76 21-MAR-18:01 0.00 0.00 0.00 0.00 0.00
April 0.628279E+09 4001.78 05-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.105964E+09 1957.01 27-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 7118292.64 1181.13 21-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 8481462.47 1221.28 26-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 48193220.01 2817.03 30-AUG-08:62 0.00 0.00 0.00 0.00 0.00
September 0.491994E+09 4004.46 27-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.170081E+10 4004.77 09-OCT-15:11 0.00 0.00 0.00 0.00 0.00
November 0.341231E+10 4003.28 18-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.396967E+10 4003.24 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.188606E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7118292.64 1181.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.396967E+10 4004.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.376476E+10 3807.28 23-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.302982E+10 3807.42 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.241310E+10 3808.63 21-MAR-18:01 0.00 0.00 0.00 0.00 0.00
April 0.830964E+09 3805.62 05-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.119926E+09 2118.10 27-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 3889176.78 1002.70 19-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 5749984.29 1009.37 04-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 54032473.28 3672.32 31-AUG-08:61 0.00 0.00 0.00 0.00 0.00
September 0.616555E+09 3808.48 27-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.191187E+10 3809.25 08-OCT-15:11 0.00 0.00 0.00 0.00 0.00
November 0.354716E+10 3807.07 18-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.399524E+10 3807.03 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.202931E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3889176.78 1002.70   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.399524E+10 3809.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.152562E+11 21305.18 23-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.980203E+10 21305.64 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.585249E+10 21298.18 25-MAR-18:01 0.00 0.00 0.00 0.00 0.00
April 0.145787E+10 21297.01 03-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.153971E+09 7389.82 27-MAY-18:03 0.00 0.00 0.00 0.00 0.00
June 16072414.02 6236.22 24-JUN-15:14 0.00 0.00 0.00 0.00 0.00
July 18555006.97 6911.78 04-JUL-15:14 0.00 0.00 0.00 0.00 0.00
August 67976451.70 5792.08 03-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 0.898327E+09 20167.78 27-SEP-15:11 0.00 0.00 0.00 0.00 0.00
October 0.507330E+10 21306.75 19-OCT-15:11 0.00 0.00 0.00 0.00 0.00
November 0.135671E+11 21305.07 18-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.171881E+11 21304.18 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.693520E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 16072414.02 5792.08   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171881E+11 21306.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 87351700.33 87351700.33 4696.23 20-JAN-06:10 4696.23 0.00
February 0.00 0.00 0.103383E+09 0.103383E+09 4750.14 07-FEB-06:10 4750.14 0.00
March 0.00 0.00 0.185438E+09 0.185438E+09 4816.58 21-MAR-05:10 4816.58 0.00
April 0.00 0.00 0.834694E+09 0.834694E+09 25396.29 21-APR-17:40 25396.29 0.00
May 0.00 0.00 0.358649E+11 0.358649E+11 157757.01 31-MAY-18:00 157757.01 0.00
June 0.00 0.00 0.130877E+12 0.129765E+12 223897.91 29-JUN-20:00 205406.40 0.25
July 0.00 0.00 0.165079E+12 0.162140E+12 248848.44 29-JUL-17:15 215391.05 0.61
August 0.00 0.00 0.981671E+11 0.979905E+11 201476.93 11-AUG-18:10 201476.93 0.40
September 0.00 0.00 0.540210E+10 0.540210E+10 64660.01 02-SEP-18:00 64660.01 0.00
October 0.00 0.00 0.250005E+09 0.250005E+09 4934.60 17-OCT-05:10 4934.60 0.00
November 0.00 0.00 62665274.76 62665274.76 4717.66 14-NOV-06:10 4717.66 0.00
December 0.00 0.00 63520886.61 63520886.61 4668.10 26-DEC-06:10 4668.10 0.00
                 
Annual Sum or Average 0.00 0.00 0.436978E+12 0.432750E+12       0.11
Minimum of Months 0.00 0.00 62665274.76 62665274.76 4668.10   4668.10 0.00
Maximum of Months 0.00 0.00 0.165079E+12 0.162140E+12 248848.44   215391.05 0.61



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 0.00
April 0.00 0.00 2616970.02 2616970.02 594.90 22-APR-14:20 594.90 0.00
May 0.00 0.00 0.174643E+10 0.174643E+10 14983.87 31-MAY-16:00 14983.87 0.00
June 0.00 0.00 0.830878E+10 0.823241E+10 19908.50 30-JUN-12:15 17598.54 0.18
July 0.00 0.00 0.101060E+11 0.992615E+10 19631.44 29-JUL-18:02 18190.56 0.42
August 0.00 0.00 0.608464E+10 0.604499E+10 17533.26 11-AUG-18:02 17533.26 0.27
September 0.00 0.00 0.172724E+09 0.172724E+09 4990.84 07-SEP-16:00 4990.84 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.264212E+11 0.261253E+11       0.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.101060E+11 0.992615E+10 19908.50   18190.56 0.42



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 4608682.80 4608682.80 3229.51 19-JAN-09:04 3229.51 0.00
February 0.00 0.00 11000270.97 10921488.36 3808.31 10-FEB-19:04 3808.31 0.00
March 0.00 0.00 46684737.04 46684737.04 12677.59 22-MAR-15:12 12677.59 0.00
April 0.00 0.00 0.136255E+10 0.136022E+10 13545.52 30-APR-18:01 13545.52 0.00
May 0.00 0.00 0.294534E+10 0.272686E+10 13548.44 20-MAY-18:01 13548.44 0.12
June 0.00 0.00 0.535892E+10 0.343469E+10 13548.75 08-JUN-18:01 13548.75 0.77
July 0.00 0.00 0.555078E+10 0.295453E+10 13722.13 26-JUL-15:11 11093.95 0.86
August 0.00 0.00 0.377087E+10 0.200908E+10 13537.49 30-AUG-18:01 13537.49 0.73
September 0.00 0.00 0.615544E+09 0.398093E+09 13547.59 07-SEP-15:11 13547.59 0.16
October 0.00 0.00 28437538.84 26462600.31 8959.01 03-OCT-15:12 8959.01 0.00
November 0.00 0.00 6830437.85 6830437.85 3050.36 04-NOV-08:04 3050.36 0.00
December 0.00 0.00 2385848.86 2385848.86 2833.82 26-DEC-09:04 2833.82 0.00
                 
Annual Sum or Average 0.00 0.00 0.197040E+11 0.129814E+11       0.22
Minimum of Months 0.00 0.00 2385848.86 2385848.86 2833.82   2833.82 0.00
Maximum of Months 0.00 0.00 0.555078E+10 0.343469E+10 13722.13   13548.75 0.86



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2211751.28 2211751.28 2692.71 23-JAN-09:04 2692.71 0.00
February 0.00 0.00 7175758.99 7113023.63 3919.77 08-FEB-19:04 3919.77 0.00
March 0.00 0.00 17421241.36 17421241.36 4427.53 20-MAR-15:13 4427.53 0.00
April 0.00 0.00 0.680671E+09 0.680445E+09 12304.20 30-APR-18:01 12304.20 0.00
May 0.00 0.00 0.153731E+10 0.137298E+10 13538.98 09-MAY-20:01 13538.98 0.10
June 0.00 0.00 0.345310E+10 0.194445E+10 13100.82 28-JUN-21:51 12035.43 0.62
July 0.00 0.00 0.360760E+10 0.183157E+10 12901.88 15-JUL-20:41 10055.99 0.62
August 0.00 0.00 0.190353E+10 0.842898E+09 12479.88 12-AUG-21:52 9562.81 0.49
September 0.00 0.00 0.205590E+09 0.114094E+09 12303.44 07-SEP-18:01 12303.44 0.08
October 0.00 0.00 21977729.50 20503974.40 4872.85 02-OCT-15:13 3537.65 0.00
November 0.00 0.00 3253402.82 3253402.82 2998.17 04-NOV-08:04 2998.17 0.00
December 0.00 0.00 1449015.91 1449015.91 3214.94 26-DEC-09:04 3214.94 0.00
                 
Annual Sum or Average 0.00 0.00 0.114413E+11 0.683838E+10       0.16
Minimum of Months 0.00 0.00 1449015.91 1449015.91 2692.71   2692.71 0.00
Maximum of Months 0.00 0.00 0.360760E+10 0.194445E+10 13538.98   13538.98 0.62



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 0.00
April 0.00 0.00 0.146325E+11 0.146325E+11 41975.69 22-APR-13:30 41975.69 0.00
May 0.00 0.00 0.276434E+11 0.276434E+11 41295.22 12-MAY-13:30 41295.22 0.00
June 0.00 0.00 0.348803E+11 0.209544E+11 40645.71 30-JUN-12:30 27697.86 0.68
July 0.00 0.00 0.373348E+11 0.157987E+11 45877.64 23-JUL-13:15 37947.57 0.96
August 0.00 0.00 0.328931E+11 0.162646E+11 47818.28 25-AUG-13:30 41902.38 0.82
September 0.00 0.00 0.118772E+11 0.100059E+11 38527.63 09-SEP-13:20 38527.63 0.14
October 0.00 0.00 0.577217E+09 0.577217E+09 21163.58 03-OCT-13:30 21163.58 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.159839E+12 0.105877E+12       0.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.373348E+11 0.276434E+11 47818.28   41975.69 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 36161717.16 36161717.16 32280.28 20-JAN-19:04 32280.28 0.00
February 0.00 0.00 57867562.47 57521397.08 32028.52 08-FEB-16:14 32028.52 0.00
March 0.00 0.00 0.149822E+09 0.149822E+09 61997.67 18-MAR-08:61 61997.67 0.00
April 0.00 0.00 0.446122E+10 0.444555E+10 69726.35 30-APR-18:01 69726.35 0.00
May 0.00 0.00 0.199647E+11 0.188851E+11 72864.55 31-MAY-21:51 72864.55 0.10
June 0.00 0.00 0.333085E+11 0.250834E+11 74731.98 30-JUN-21:51 61778.81 0.53
July 0.00 0.00 0.365626E+11 0.245736E+11 76913.26 18-JUL-21:52 58023.29 0.56
August 0.00 0.00 0.246505E+11 0.152509E+11 74521.90 12-AUG-21:52 58405.05 0.49
September 0.00 0.00 0.739206E+10 0.425039E+10 69207.21 10-SEP-18:01 69207.21 0.35
October 0.00 0.00 0.999519E+09 0.854260E+09 66526.12 04-OCT-18:03 66526.12 0.02
November 0.00 0.00 33170728.57 33170728.57 31165.12 06-NOV-19:04 31165.12 0.00
December 0.00 0.00 25713656.01 25713656.01 30510.57 24-DEC-09:01 30510.57 0.00
                 
Annual Sum or Average 0.00 0.00 0.127642E+12 0.936455E+11       0.17
Minimum of Months 0.00 0.00 25713656.01 25713656.01 30510.57   30510.57 0.00
Maximum of Months 0.00 0.00 0.365626E+11 0.250834E+11 76913.26   72864.55 0.56



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3325109.40 3325109.40 2619.00 19-JAN-09:04 2619.00 0.00
February 0.00 0.00 12320205.61 12245938.93 3708.11 08-FEB-19:04 3708.11 0.00
March 0.00 0.00 57982453.18 57982453.18 12180.81 22-MAR-15:12 12180.81 0.00
April 0.00 0.00 0.116430E+10 0.114764E+10 12787.89 22-APR-08:61 12787.89 0.01
May 0.00 0.00 0.427297E+10 0.395459E+10 12788.13 12-MAY-08:62 12788.13 0.16
June 0.00 0.00 0.611175E+10 0.401220E+10 12788.06 08-JUN-18:01 12788.06 0.82
July 0.00 0.00 0.683809E+10 0.399349E+10 12764.18 26-JUL-15:11 10625.80 0.91
August 0.00 0.00 0.459829E+10 0.258945E+10 12787.71 10-AUG-18:01 12787.71 0.78
September 0.00 0.00 0.851609E+09 0.499310E+09 12788.74 10-SEP-15:11 12788.74 0.24
October 0.00 0.00 47846380.83 38657787.80 12156.77 04-OCT-08:62 12156.77 0.01
November 0.00 0.00 5040917.11 5040917.11 2851.07 04-NOV-08:04 2851.07 0.00
December 0.00 0.00 1855226.38 1855226.38 3041.50 26-DEC-09:04 3041.50 0.00
                 
Annual Sum or Average 0.00 0.00 0.239654E+11 0.163158E+11       0.25
Minimum of Months 0.00 0.00 1855226.38 1855226.38 2619.00   2619.00 0.00
Maximum of Months 0.00 0.00 0.683809E+10 0.401220E+10 12788.74   12788.74 0.91



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1356905.63 1356905.63 2878.93 23-JAN-09:04 2878.93 0.00
February 0.00 0.00 7624026.57 7581763.16 4160.73 08-FEB-19:04 4160.73 0.00
March 0.00 0.00 20400110.58 20400110.58 4879.69 18-MAR-08:03 4879.69 0.00
April 0.00 0.00 0.453030E+09 0.442225E+09 11639.93 22-APR-08:61 11639.93 0.01
May 0.00 0.00 0.288717E+10 0.264366E+10 11780.93 14-MAY-20:41 11780.93 0.14
June 0.00 0.00 0.445524E+10 0.283304E+10 11968.70 30-JUN-21:51 9815.86 0.69
July 0.00 0.00 0.485034E+10 0.283365E+10 12705.35 22-JUL-08:32 12705.35 0.69
August 0.00 0.00 0.280024E+10 0.148935E+10 11821.49 12-AUG-21:52 9066.96 0.57
September 0.00 0.00 0.358164E+09 0.200411E+09 11321.36 10-SEP-15:11 11321.36 0.13
October 0.00 0.00 23536400.53 19298119.83 7825.17 04-OCT-08:62 7825.17 0.00
November 0.00 0.00 2327448.28 2327448.28 3225.75 04-NOV-08:04 3225.75 0.00
December 0.00 0.00 1036699.80 1036699.80 3149.25 26-DEC-09:04 3149.25 0.00
                 
Annual Sum or Average 0.00 0.00 0.158605E+11 0.104943E+11       0.19
Minimum of Months 0.00 0.00 1036699.80 1036699.80 2878.93   2878.93 0.00
Maximum of Months 0.00 0.00 0.485034E+10 0.283365E+10 12705.35   12705.35 0.69



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 153631.71 153631.71 408.93 22-JAN-09:04 408.93 0.00
February 0.00 0.00 924077.94 899351.65 726.84 09-FEB-09:04 438.37 0.00
March 0.00 0.00 5863595.27 5841398.94 2710.74 22-MAR-15:12 2710.74 0.00
April 0.00 0.00 0.351833E+09 0.351631E+09 3510.83 30-APR-18:01 3510.83 0.00
May 0.00 0.00 0.724865E+09 0.673018E+09 3511.60 20-MAY-18:01 3511.60 0.12
June 0.00 0.00 0.133925E+10 0.889633E+09 3511.55 08-JUN-18:01 3511.55 0.74
July 0.00 0.00 0.137928E+10 0.767782E+09 3547.69 26-JUL-15:11 2883.33 0.83
August 0.00 0.00 0.904295E+09 0.512826E+09 3642.58 13-AUG-08:61 2669.68 0.66
September 0.00 0.00 0.143862E+09 98333415.46 3511.48 07-SEP-15:11 3511.48 0.12
October 0.00 0.00 5664839.81 4962917.24 2290.86 03-OCT-15:12 2290.86 0.00
November 0.00 0.00 84460.09 84460.09 273.00 04-NOV-08:04 273.00 0.00
December 0.00 0.00 131491.93 131491.93 709.58 24-DEC-09:04 709.58 0.00
                 
Annual Sum or Average 0.00 0.00 0.485621E+10 0.330530E+10       0.21
Minimum of Months 0.00 0.00 84460.09 84460.09 273.00   273.00 0.00
Maximum of Months 0.00 0.00 0.137928E+10 0.889633E+09 3642.58   3511.60 0.83



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 92742.39 92742.39 279.46 21-JAN-09:04 279.46 0.00
February 0.00 0.00 702723.05 681542.18 735.65 09-FEB-09:04 488.54 0.00
March 0.00 0.00 3472623.81 3453693.01 1194.51 20-MAR-15:13 1194.51 0.00
April 0.00 0.00 0.169823E+09 0.169706E+09 3159.44 30-APR-18:01 3159.44 0.00
May 0.00 0.00 0.348061E+09 0.310783E+09 3611.90 09-MAY-20:01 3611.90 0.09
June 0.00 0.00 0.880305E+09 0.506363E+09 3364.72 28-JUN-21:51 3172.67 0.61
July 0.00 0.00 0.909230E+09 0.473258E+09 3492.93 08-JUL-21:51 2986.41 0.62
August 0.00 0.00 0.434077E+09 0.199133E+09 3267.34 12-AUG-21:52 2393.31 0.44
September 0.00 0.00 41229499.93 24534039.70 3159.20 07-SEP-18:01 3159.20 0.05
October 0.00 0.00 4823781.87 4411337.59 1378.76 04-OCT-15:13 1378.76 0.00
November 0.00 0.00 138625.65 138625.65 388.65 04-NOV-08:04 388.65 0.00
December 0.00 0.00 111678.42 111678.42 337.62 24-DEC-09:04 337.62 0.00
                 
Annual Sum or Average 0.00 0.00 0.279207E+10 0.169267E+10       0.15
Minimum of Months 0.00 0.00 92742.39 92742.39 279.46   279.46 0.00
Maximum of Months 0.00 0.00 0.909230E+09 0.506363E+09 3611.90   3611.90 0.62



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 7969595.64 7969595.64 4726.94 22-JAN-19:04 4726.94 0.00
February 0.00 0.00 26674228.27 26593858.60 20601.20 15-FEB-16:11 20601.20 0.00
March 0.00 0.00 0.807917E+09 0.806602E+09 21526.37 22-MAR-15:12 21526.37 0.00
April 0.00 0.00 0.382566E+10 0.378391E+10 21529.23 19-APR-18:01 21529.23 0.02
May 0.00 0.00 0.583251E+10 0.517224E+10 21531.45 01-MAY-15:11 21531.45 0.21
June 0.00 0.00 0.796903E+10 0.488927E+10 21529.98 15-JUN-18:01 21529.98 0.77
July 0.00 0.00 0.911836E+10 0.484881E+10 21237.41 01-JUL-15:11 18158.21 0.88
August 0.00 0.00 0.747775E+10 0.431753E+10 21525.08 21-AUG-18:01 21525.08 0.77
September 0.00 0.00 0.256834E+10 0.159088E+10 21524.00 28-SEP-15:12 21524.00 0.37
October 0.00 0.00 0.459080E+09 0.400411E+09 21515.60 14-OCT-15:11 21515.60 0.02
November 0.00 0.00 11502907.80 11502907.80 4054.00 01-NOV-18:04 4054.00 0.00
December 0.00 0.00 4164008.29 4164008.29 4918.37 24-DEC-19:04 4918.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.381090E+11 0.258599E+11       0.25
Minimum of Months 0.00 0.00 4164008.29 4164008.29 4054.00   4054.00 0.00
Maximum of Months 0.00 0.00 0.911836E+10 0.517224E+10 21531.45   21531.45 0.88



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.92 2152.83 21-JAN-18:25 202003.42 756987.75 12-JAN-09:03
February 6.14 10038.65 07-FEB-22:05 175609.71 677595.23 27-FEB-09:03
March 37.61 10101.52 22-MAR-24:00 87496.34 602535.65 01-MAR-09:03
April 273.45 15056.33 03-APR-18:01 28273.21 272102.60 03-APR-08:61
May 14.47 7486.97 28-MAY-01:40 14752.69 155472.30 27-MAY-08:06
June 0.00 0.00 01-JUN-00:10 1200.26 64575.28 24-JUN-15:14
July 0.00 0.00 01-JUL-00:10 527.54 68811.29 05-JUL-08:04
August 20.54 7965.64 31-AUG-02:40 3546.52 143093.54 30-AUG-08:05
September 74.15 9307.83 26-SEP-04:50 28523.37 264079.69 27-SEP-15:11
October 62.44 9671.42 05-OCT-03:00 47393.89 278021.64 11-OCT-15:11
November 0.00 0.00 01-NOV-00:10 190450.09 654349.61 29-NOV-09:03
December 0.88 1931.59 23-DEC-18:25 236385.82 704255.43 15-DEC-09:03
             
Annual Sum or Average 40.66     84180.20    
Minimum of Months 0.00 0.00   527.54 64575.28  
Maximum of Months 273.45 15056.33   236385.82 756987.75  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 220.00 47978.98 20-JAN-19:04 0.00 0.00 01-JAN-00:05
February 372.71 65390.26 08-FEB-16:14 0.00 0.00 01-FEB-00:05
March 1105.82 60032.16 17-MAR-15:14 0.00 0.00 01-MAR-00:05
April 12396.89 173720.41 22-APR-15:13 0.00 0.00 01-APR-00:10
May 41123.91 239884.35 31-MAY-18:03 0.00 0.00 01-MAY-00:10
June 94198.94 373581.85 29-JUN-18:03 0.00 0.00 01-JUN-00:10
July 107890.99 425435.42 29-JUL-18:03 0.00 0.00 01-JUL-00:10
August 71205.74 367425.76 23-AUG-18:03 0.00 0.00 01-AUG-00:10
September 13037.99 165526.97 09-SEP-18:03 0.00 0.00 01-SEP-00:10
October 1724.02 57929.03 19-OCT-15:14 0.00 0.00 01-OCT-00:10
November 185.03 53495.09 03-NOV-08:04 0.00 0.00 01-NOV-00:10
December 168.18 52978.04 25-DEC-19:04 0.00 0.00 01-DEC-00:05
             
Annual Sum or Average 28853.70     0.00    
Minimum of Months 168.18 47978.98   0.00 0.00  
Maximum of Months 107890.99 425435.42   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 33737.61 68895.68 12-JAN-07:54
February 0.00 0.00 01-FEB-00:05 33744.12 68881.56 27-FEB-07:59
March 0.00 0.00 01-MAR-00:05 33766.59 68871.32 02-MAR-07:53
April 0.00 0.00 01-APR-00:10 33748.43 68823.10 03-APR-06:56
May 0.00 0.00 01-MAY-00:10 33512.64 68853.79 12-MAY-06:57
June 0.00 0.00 01-JUN-00:10 32337.52 67146.50 01-JUN-06:53
July 0.00 0.00 01-JUL-00:10 31153.91 64346.30 03-JUL-06:54
August 0.00 0.00 01-AUG-00:10 30452.21 62381.68 02-AUG-06:58
September 0.00 0.00 01-SEP-00:10 30345.28 61921.40 29-SEP-06:50
October 0.00 0.00 01-OCT-00:10 30895.11 63838.65 31-OCT-06:53
November 0.00 0.00 01-NOV-00:10 31955.63 66381.13 30-NOV-08:00
December 0.00 0.00 01-DEC-00:05 33223.29 68851.84 28-DEC-07:57
             
Annual Sum or Average 0.00     32398.42    
Minimum of Months 0.00 0.00   30345.28 61921.40  
Maximum of Months 0.00 0.00   33766.59 68895.68  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.261333E+10 0.68 1299.30 01-JAN-00:20 0.89
February 0.236042E+10 0.68 1299.30 01-FEB-00:20 0.89
March 0.261333E+10 0.68 1299.30 01-MAR-00:20 0.90
April 0.252903E+10 0.68 1299.30 01-APR-00:50 0.89
May 0.261333E+10 0.68 1299.30 01-MAY-00:40 0.89
June 0.252903E+10 0.68 1299.30 01-JUN-00:40 0.89
July 0.261333E+10 0.68 1299.30 01-JUL-00:30 0.88
August 0.261333E+10 0.68 1299.30 01-AUG-00:30 0.89
September 0.252903E+10 0.68 1299.30 01-SEP-02:40 0.89
October 0.261333E+10 0.68 1299.30 01-OCT-00:30 0.89
November 0.252903E+10 0.68 1299.30 01-NOV-01:30 0.89
December 0.261333E+10 0.68 1299.30 01-DEC-00:30 0.90
           
Annual Sum or Average 0.307698E+11 0.68      
Minimum of Months 0.236042E+10 0.68 1299.30   0.88
Maximum of Months 0.261333E+10 0.68 1299.30   0.90



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.385814E+11 0.90 20882.34 19-JAN-19:50 1.13
February 0.351717E+11 0.91 20884.43 09-FEB-20:00 1.13
March 0.396693E+11 0.92 20875.41 17-MAR-18:30 1.13
April 0.391936E+11 0.93 20936.01 23-APR-19:30 1.13
May 0.414159E+11 0.94 21532.34 31-MAY-21:10 1.14
June 0.410188E+11 0.95 24828.09 21-JUN-21:06 1.24
July 0.423026E+11 0.94 24599.15 11-JUL-21:20 1.24
August 0.418617E+11 0.94 23855.14 11-AUG-21:10 1.21
September 0.394688E+11 0.93 21002.05 11-SEP-19:10 1.12
October 0.399085E+11 0.92 20889.46 30-OCT-18:40 1.13
November 0.373936E+11 0.91 20876.92 22-NOV-19:40 1.13
December 0.383750E+11 0.90 20896.33 24-DEC-20:10 1.13
           
Annual Sum or Average 0.474361E+12 0.92      
Minimum of Months 0.351717E+11 0.90 20875.41   1.12
Maximum of Months 0.423026E+11 0.95 24828.09   1.24



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:05 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:05 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:05 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:10 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:10 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:10 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:10 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:10 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:05 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 -0.0
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:05 -0.0
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 -0.0
July 0.00 -0.0 0.00 01-JUL-00:10 -0.0
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 -0.0 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 -0.0
December 0.00 -0.0 0.00 01-DEC-00:05 -0.0
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:10 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:10 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.404813E+09 0.57 666.46 01-JAN-09:01 0.59
February 0.303040E+09 0.54 666.46 01-FEB-09:01 0.59
March 0.239400E+09 0.45 666.46 01-MAR-09:01 0.59
April 0.157199E+09 0.44 666.46 01-APR-08:61 0.59
May 0.165969E+09 0.48 666.46 01-MAY-15:11 0.58
June 0.265780E+09 0.51 666.46 01-JUN-08:62 0.58
July 0.254338E+09 0.51 666.46 01-JUL-08:61 0.58
August 0.189282E+09 0.48 666.46 01-AUG-08:61 0.58
September 0.107322E+09 0.41 666.46 01-SEP-15:11 0.58
October 0.213590E+09 0.46 666.46 03-OCT-08:61 0.58
November 0.364408E+09 0.57 666.46 01-NOV-08:61 0.59
December 0.415721E+09 0.57 666.46 01-DEC-09:01 0.59
           
Annual Sum or Average 0.308086E+10 0.50      
Minimum of Months 0.107322E+09 0.41 666.46   0.58
Maximum of Months 0.415721E+09 0.57 666.46   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.391366E+09 0.57 605.22 01-JAN-09:01 0.59
February 0.313309E+09 0.56 605.22 01-FEB-09:01 0.59
March 0.267602E+09 0.52 605.22 01-MAR-09:01 0.59
April 0.143228E+09 0.43 605.22 01-APR-08:61 0.59
May 99021249.82 0.37 605.22 01-MAY-15:11 0.58
June 0.164811E+09 0.37 605.22 01-JUN-08:62 0.58
July 0.162106E+09 0.37 605.22 01-JUL-08:61 0.58
August 97565388.53 0.34 605.22 01-AUG-08:61 0.58
September 95938925.25 0.39 605.22 01-SEP-15:11 0.58
October 0.224156E+09 0.49 605.22 03-OCT-08:61 0.58
November 0.358879E+09 0.57 605.22 01-NOV-08:61 0.59
December 0.399275E+09 0.57 605.22 01-DEC-09:01 0.59
           
Annual Sum or Average 0.271726E+10 0.46      
Minimum of Months 95938925.25 0.34 605.22   0.58
Maximum of Months 0.399275E+09 0.57 605.22   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.167449E+10 0.58 1142.64 12-JAN-16:00 0.59
February 0.788913E+09 0.40 930.13 27-FEB-05:00 0.59
March 0.102960E+09 0.05 872.31 01-MAR-05:00 0.59
April 0.550819E+09 0.23 1326.52 22-APR-13:30 0.59
May 0.105777E+10 0.46 1307.13 12-MAY-13:30 0.59
June 0.135762E+10 0.56 1248.37 10-JUN-14:00 0.58
July 0.137786E+10 0.56 1432.64 23-JUL-13:30 0.58
August 0.124751E+10 0.52 1500.76 25-AUG-13:30 0.58
September 0.493759E+09 0.27 1676.70 30-SEP-17:50 0.59
October 0.103484E+09 0.08 748.42 03-OCT-13:30 0.59
November 0.143105E+10 0.57 948.74 29-NOV-05:00 0.59
December 0.192666E+10 0.59 1058.78 15-DEC-15:10 0.59
           
Annual Sum or Average 0.121129E+11 0.41      
Minimum of Months 0.102960E+09 0.05 748.42   0.58
Maximum of Months 0.192666E+10 0.59 1676.70   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.179516E+10 0.48 3509.42 01-JAN-09:01 0.59
February 0.140955E+10 0.45 3509.42 01-FEB-09:01 0.59
March 0.113501E+10 0.41 3509.42 01-MAR-09:01 0.59
April 0.638017E+09 0.40 3509.42 01-APR-15:11 0.59
May 0.985724E+09 0.35 3509.42 01-MAY-08:61 0.58
June 0.161253E+10 0.32 3509.42 01-JUN-08:62 0.58
July 0.162017E+10 0.33 3509.42 01-JUL-08:61 0.58
August 0.108738E+10 0.31 3509.42 01-AUG-08:61 0.58
September 0.530273E+09 0.39 3509.42 01-SEP-08:61 0.58
October 0.809052E+09 0.40 3509.42 01-OCT-08:62 0.58
November 0.163610E+10 0.47 3509.42 01-NOV-08:61 0.59
December 0.186799E+10 0.49 3509.42 01-DEC-09:01 0.59
           
Annual Sum or Average 0.151270E+11 0.40      
Minimum of Months 0.530273E+09 0.31 3509.42   0.58
Maximum of Months 0.186799E+10 0.49 3509.42   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.389565E+09 0.57 628.93 01-JAN-09:01 0.59
February 0.282813E+09 0.53 628.93 01-FEB-09:01 0.59
March 0.207302E+09 0.43 628.93 01-MAR-09:01 0.59
April 0.143726E+09 0.46 628.93 01-APR-08:61 0.59
May 0.224310E+09 0.52 628.93 01-MAY-08:61 0.58
June 0.291219E+09 0.54 628.93 01-JUN-08:62 0.58
July 0.306382E+09 0.53 628.93 01-JUL-08:61 0.58
August 0.218027E+09 0.51 628.93 01-AUG-08:61 0.58
September 0.106918E+09 0.43 628.93 01-SEP-08:61 0.58
October 0.192451E+09 0.45 628.93 03-OCT-15:12 0.58
November 0.352295E+09 0.57 628.93 01-NOV-08:61 0.59
December 0.402730E+09 0.57 628.93 01-DEC-09:01 0.59
           
Annual Sum or Average 0.311774E+10 0.51      
Minimum of Months 0.106918E+09 0.43 628.93   0.58
Maximum of Months 0.402730E+09 0.57 628.93   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.377360E+09 0.57 572.29 01-JAN-09:01 0.59
February 0.294355E+09 0.56 572.29 01-FEB-09:01 0.59
March 0.229669E+09 0.47 572.29 01-MAR-09:01 0.59
April 0.127871E+09 0.41 572.29 01-APR-08:61 0.59
May 0.163464E+09 0.44 572.29 01-MAY-08:61 0.58
June 0.216986E+09 0.41 572.29 01-JUN-08:62 0.58
July 0.217828E+09 0.41 572.29 01-JUL-08:61 0.58
August 0.136332E+09 0.39 572.29 01-AUG-08:61 0.58
September 89628113.38 0.39 572.29 01-SEP-08:61 0.58
October 0.201798E+09 0.47 572.29 08-OCT-15:11 0.58
November 0.348291E+09 0.57 572.29 01-NOV-08:61 0.59
December 0.390379E+09 0.57 572.29 01-DEC-09:01 0.59
           
Annual Sum or Average 0.279396E+10 0.47      
Minimum of Months 89628113.38 0.39 572.29   0.58
Maximum of Months 0.390379E+09 0.57 572.29   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.119739E+09 0.58 172.80 01-JAN-09:01 0.59
February 91733158.72 0.57 172.80 01-FEB-09:01 0.59
March 72977421.60 0.50 172.80 01-MAR-09:01 0.59
April 46497796.77 0.44 172.80 01-APR-08:61 0.59
May 43860361.62 0.48 172.80 01-MAY-15:11 0.58
June 67768513.16 0.51 172.80 01-JUN-08:62 0.58
July 64690365.93 0.51 172.80 01-JUL-08:61 0.58
August 47491432.38 0.48 172.80 01-AUG-08:61 0.58
September 32696298.08 0.42 172.80 01-SEP-15:11 0.58
October 66017622.33 0.50 172.80 02-OCT-15:12 0.58
November 0.109857E+09 0.58 172.80 01-NOV-08:61 0.59
December 0.125201E+09 0.58 172.80 01-DEC-09:01 0.59
           
Annual Sum or Average 0.888530E+09 0.51      
Minimum of Months 32696298.08 0.42 172.80   0.58
Maximum of Months 0.125201E+09 0.58 172.80   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.117513E+09 0.58 155.42 01-JAN-09:01 0.59
February 95882740.93 0.57 155.42 01-FEB-09:01 0.59
March 80837004.02 0.55 155.42 01-MAR-09:01 0.59
April 43243050.11 0.44 155.42 01-APR-08:61 0.59
May 25702563.51 0.37 155.42 01-MAY-15:11 0.58
June 42796334.60 0.37 155.42 01-JUN-08:62 0.58
July 41815783.18 0.37 155.42 01-JUL-08:61 0.58
August 23955104.03 0.34 155.42 01-AUG-08:61 0.58
September 30326778.19 0.41 155.42 01-SEP-15:11 0.58
October 68186475.21 0.52 155.42 02-OCT-15:12 0.58
November 0.111054E+09 0.58 155.42 01-NOV-08:61 0.59
December 0.124052E+09 0.58 155.42 01-DEC-09:01 0.59
           
Annual Sum or Average 0.805365E+09 0.47      
Minimum of Months 23955104.03 0.34 155.42   0.58
Maximum of Months 0.124052E+09 0.58 155.42   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.574475E+09 0.55 1055.58 01-JAN-09:01 0.59
February 0.388090E+09 0.48 1055.58 01-FEB-09:01 0.59
March 0.308669E+09 0.45 1055.58 01-MAR-09:01 0.59
April 0.274899E+09 0.49 1055.58 01-APR-15:11 0.59
May 0.303513E+09 0.51 1055.58 01-MAY-08:61 0.58
June 0.378760E+09 0.52 1055.58 01-JUN-08:62 0.58
July 0.405254E+09 0.52 1055.58 01-JUL-08:61 0.58
August 0.351084E+09 0.50 1055.58 01-AUG-08:61 0.58
September 0.196736E+09 0.45 1055.58 01-SEP-08:61 0.58
October 0.271375E+09 0.44 1055.58 01-OCT-15:12 0.58
November 0.512721E+09 0.54 1055.58 01-NOV-08:61 0.59
December 0.620984E+09 0.57 1055.58 01-DEC-09:01 0.59
           
Annual Sum or Average 0.458656E+10 0.50      
Minimum of Months 0.196736E+09 0.44 1055.58   0.58
Maximum of Months 0.620984E+09 0.57 1055.58   0.59



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.804796E+09 0.731560E+09 2626.88 12-JAN-09:13 2387.83 2387.83 46.14 12.96
February 0.575514E+09 0.523143E+09 1966.93 27-FEB-06:10 1787.94 1787.94 47.14 11.51
March 0.218737E+09 0.198832E+09 1285.32 01-MAR-07:00 1168.36 1168.36 46.67 9.65
April 19984828.41 18166209.02 108.05 03-APR-08:61 98.22 98.22 39.12 3.12
May 4831861.25 4392161.88 36.23 27-MAY-08:06 32.93 32.93 38.74 1.75
June 248107.37 225529.60 7.88 24-JUN-15:14 7.16 7.16 37.56 0.69
July 123349.39 112124.60 8.95 04-JUL-15:14 8.13 8.13 44.32 0.75
August 1285466.70 1168489.23 28.17 30-AUG-08:05 25.61 25.61 37.45 1.52
September 13922342.72 12655409.53 78.50 27-SEP-15:11 71.35 71.35 36.18 2.65
October 42306649.72 38456744.59 134.49 30-OCT-08:61 122.25 122.25 43.24 3.47
November 0.632726E+09 0.575148E+09 1524.72 29-NOV-09:03 1385.97 1385.97 44.91 10.37
December 0.892567E+09 0.811343E+09 1971.61 15-DEC-09:03 1792.19 1792.19 45.39 11.53
                 
Annual Sum or Average 0.320704E+10 0.291520E+10            
Minimum of Months 123349.39 112124.60 7.88   7.16 7.16 36.18 0.69
Maximum of Months 0.892567E+09 0.811343E+09 2626.88   2387.83 2387.83 47.14 12.96



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 3086329.96 2805473.93 906.19 17-JAN-19:04 823.73 823.73 6.72 2.06
February 5296570.38 4814582.47 1042.92 10-FEB-16:14 948.01 948.01 6.72 2.46
March 39858824.63 36231671.59 1040.16 17-MAR-15:14 945.50 945.50 6.72 2.45
April 0.694131E+09 0.630965E+09 1748.88 22-APR-15:11 1589.73 1589.73 6.72 5.36
May 0.196480E+10 0.178600E+10 1804.08 31-MAY-18:01 1639.91 1639.91 6.72 5.71
June 0.313409E+10 0.284889E+10 2261.93 21-JUN-18:03 2056.09 2056.09 6.72 11.78
July 0.348185E+10 0.316500E+10 2300.12 20-JUL-18:03 2090.81 2090.81 6.72 12.49
August 0.271532E+10 0.246822E+10 2233.37 11-AUG-15:12 2030.14 2030.14 6.72 11.18
September 0.756756E+09 0.687891E+09 1770.92 09-SEP-18:03 1609.77 1609.77 6.72 5.50
October 80432118.56 73112795.77 1166.36 03-OCT-18:02 1060.22 1060.22 6.72 2.85
November 2878407.20 2616472.15 949.78 06-NOV-09:04 863.35 863.35 6.72 2.19
December 2192577.47 1993052.92 912.27 21-DEC-09:04 829.26 829.26 6.72 2.08
                 
Annual Sum or Average 0.128807E+11 0.117085E+11            
Minimum of Months 2192577.47 1993052.92 906.19   823.73 823.73 6.72 2.06
Maximum of Months 0.348185E+10 0.316500E+10 2300.12   2090.81 2090.81 6.72 12.49



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.488528E+09 0.444072E+09 1929.47 01-JAN-00:05 1753.89 1753.89 6.73 17.24
February 0.733502E+09 0.666754E+09 1929.47 01-FEB-09:04 1753.89 1753.89 6.74 17.24
March 0.179394E+10 0.163069E+10 1929.47 01-MAR-09:04 1753.89 1753.89 6.79 17.24
April 0.392210E+10 0.356519E+10 1929.47 01-APR-00:40 1753.89 1753.89 6.72 17.24
May 0.509496E+10 0.463132E+10 1929.47 01-MAY-00:10 1753.89 1753.89 6.78 17.24
June 0.498498E+10 0.453135E+10 1929.47 01-JUN-00:10 1753.89 1753.89 7.23 17.24
July 0.515748E+10 0.468815E+10 1929.47 01-JUL-00:10 1753.89 1753.89 7.47 17.24
August 0.513866E+10 0.467105E+10 1929.47 01-AUG-00:10 1753.89 1753.89 7.70 17.24
September 0.383359E+10 0.348473E+10 1929.47 01-SEP-00:10 1753.89 1753.89 6.81 17.24
October 0.234268E+10 0.212950E+10 1929.47 01-OCT-00:10 1753.89 1753.89 6.73 17.24
November 0.386997E+09 0.351780E+09 1929.47 01-NOV-00:20 1753.89 1753.89 6.73 17.24
December 0.383827E+09 0.348899E+09 1929.47 01-DEC-09:06 1753.89 1753.89 6.84 17.24
                 
Annual Sum or Average 0.342613E+11 0.311435E+11            
Minimum of Months 0.383827E+09 0.348899E+09 1929.47   1753.89 1753.89 6.72 17.24
Maximum of Months 0.515748E+10 0.468815E+10 1929.47   1753.89 1753.89 7.70 17.24



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 45.60 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:05 14.37 14.37 46.86 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:05 14.37 14.37 46.89 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 49.81 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 49.74 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 49.85 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 50.76 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 50.71 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 50.53 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 50.09 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 50.43 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:05 14.37 14.37 46.77 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 45.60 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 50.76 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.92 2152.83 21-JAN-18:25 49.31 49.31 202003.42 756987.75 12-JAN-09:03
February 6.14 10038.65 07-FEB-22:05 51.37 51.37 175609.71 677595.23 27-FEB-09:03
March 37.61 10101.52 22-MAR-24:00 52.50 52.50 87496.34 602535.65 01-MAR-09:03
April 273.45 15056.33 03-APR-18:01 50.75 50.75 28273.21 272102.60 03-APR-08:61
May 14.47 7486.97 28-MAY-01:40 52.47 52.47 14752.69 155472.30 27-MAY-08:06
June 0.00 0.00 01-JUN-00:10 34.03 34.03 1200.26 64575.28 24-JUN-15:14
July 0.00 0.00 01-JUL-00:10 44.29 44.29 527.54 68811.29 05-JUL-08:04
August 20.54 7965.64 31-AUG-02:40 53.19 53.19 3546.52 143093.54 30-AUG-08:05
September 74.15 9307.83 26-SEP-04:50 52.06 52.06 28523.37 264079.69 27-SEP-15:11
October 62.44 9671.42 05-OCT-03:00 52.44 52.44 47393.89 278021.64 11-OCT-15:11
November 0.00 0.00 01-NOV-00:10 48.19 56.93 190450.09 654349.61 29-NOV-09:03
December 0.88 1931.59 23-DEC-18:25 49.53 49.53 236385.82 704255.43 15-DEC-09:03
                 
Annual Sum or Average 40.66         84180.20    
Minimum of Months 0.00 0.00   34.03 34.03 527.54 64575.28  
Maximum of Months 273.45 15056.33   53.19 56.93 236385.82 756987.75  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 220.00 47978.98 20-JAN-19:04 7.36 6.70 0.00 0.00 01-JAN-00:05
February 372.71 65390.26 08-FEB-16:14 7.60 6.70 0.00 0.00 01-FEB-00:05
March 1105.82 60032.16 17-MAR-15:14 7.53 6.70 0.00 0.00 01-MAR-00:05
April 12396.89 173720.41 22-APR-15:13 9.10 6.70 0.00 0.00 01-APR-00:10
May 41123.91 239884.35 31-MAY-18:03 10.02 6.70 0.00 0.00 01-MAY-00:10
June 94198.94 373581.85 29-JUN-18:03 11.87 6.70 0.00 0.00 01-JUN-00:10
July 107890.99 425435.42 29-JUL-18:03 12.59 6.70 0.00 0.00 01-JUL-00:10
August 71205.74 367425.76 23-AUG-18:03 11.79 6.70 0.00 0.00 01-AUG-00:10
September 13037.99 165526.97 09-SEP-18:03 8.99 6.70 0.00 0.00 01-SEP-00:10
October 1724.02 57929.03 19-OCT-15:14 7.50 6.70 0.00 0.00 01-OCT-00:10
November 185.03 53495.09 03-NOV-08:04 7.44 6.70 0.00 0.00 01-NOV-00:10
December 168.18 52978.04 25-DEC-19:04 7.43 6.70 0.00 0.00 01-DEC-00:05
                 
Annual Sum or Average 28853.70         0.00    
Minimum of Months 168.18 47978.98   7.36 6.70 0.00 0.00  
Maximum of Months 107890.99 425435.42   12.59 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 45.60 59.63 33737.61 68895.68 12-JAN-07:54
February 0.00 0.00 01-FEB-00:05 46.86 59.64 33744.12 68881.56 27-FEB-07:59
March 0.00 0.00 01-MAR-00:05 46.89 59.69 33766.59 68871.32 02-MAR-07:53
April 0.00 0.00 01-APR-00:10 49.81 58.91 33748.43 68823.10 03-APR-06:56
May 0.00 0.00 01-MAY-00:10 49.74 58.79 33512.64 68853.79 12-MAY-06:57
June 0.00 0.00 01-JUN-00:10 49.85 58.60 32337.52 67146.50 01-JUN-06:53
July 0.00 0.00 01-JUL-00:10 50.76 59.56 31153.91 64346.30 03-JUL-06:54
August 0.00 0.00 01-AUG-00:10 50.71 59.01 30452.21 62381.68 02-AUG-06:58
September 0.00 0.00 01-SEP-00:10 50.53 58.44 30345.28 61921.40 29-SEP-06:50
October 0.00 0.00 01-OCT-00:10 50.09 59.54 30895.11 63838.65 31-OCT-06:53
November 0.00 0.00 01-NOV-00:10 50.43 58.81 31955.63 66381.13 30-NOV-08:00
December 0.00 0.00 01-DEC-00:05 46.77 58.36 33223.29 68851.84 28-DEC-07:57
                 
Annual Sum or Average 0.00         32398.42    
Minimum of Months 0.00 0.00   45.60 58.36 30345.28 61921.40  
Maximum of Months 0.00 0.00   50.76 59.69 33766.59 68895.68  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.358443E+12 0.00 87351700.33 0.385814E+11 0.00 0.00
February 0.293567E+12 0.00 0.103383E+09 0.351717E+11 0.00 0.00
March 0.153814E+12 0.00 0.185438E+09 0.396693E+11 0.00 0.00
April 0.531148E+11 0.00 0.834694E+09 0.391936E+11 0.00 0.00
May 0.384041E+11 0.00 0.358649E+11 0.414159E+11 0.00 0.00
June 0.300778E+10 0.00 0.130877E+12 0.410188E+11 0.00 0.00
July 0.136697E+10 0.00 0.165079E+12 0.423026E+11 0.00 0.00
August 0.890566E+10 0.00 0.981671E+11 0.418617E+11 0.00 0.00
September 0.649675E+11 0.00 0.540210E+10 0.394688E+11 0.00 0.00
October 0.771024E+11 0.00 0.250005E+09 0.399085E+11 0.00 0.00
November 0.327599E+12 0.00 62665274.76 0.373936E+11 0.00 0.00
December 0.425520E+12 0.00 63520886.61 0.383750E+11 0.00 0.00
             
Annual Sum or Average 0.180581E+13 0.00 0.436978E+12 0.474361E+12 0.00 0.00
Minimum of Months 0.136697E+10 0.00 62665274.76 0.351717E+11 0.00 0.00
Maximum of Months 0.425520E+12 0.00 0.165079E+12 0.423026E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.334004E+11 0.00 0.00 0.261333E+10 0.00 0.00
February 0.300976E+11 0.00 0.00 0.236042E+10 0.00 0.00
March 0.164610E+11 0.00 0.00 0.261333E+10 0.00 0.00
April 0.211547E+10 0.00 2616970.02 0.252903E+10 0.00 0.00
May 10444.39 0.00 0.174643E+10 0.261333E+10 0.00 0.00
June 25277.82 0.00 0.830878E+10 0.252903E+10 0.00 0.00
July 29959.91 0.00 0.101060E+11 0.261333E+10 0.00 0.00
August 2765097.98 0.00 0.608464E+10 0.261333E+10 0.00 0.00
September 0.118353E+09 0.00 0.172724E+09 0.252903E+10 0.00 0.00
October 0.417402E+10 0.00 0.00 0.261333E+10 0.00 0.00
November 0.320821E+11 0.00 0.00 0.252903E+10 0.00 0.00
December 0.403366E+11 0.00 0.00 0.261333E+10 0.00 0.00
             
Annual Sum or Average 0.158788E+12 0.00 0.264212E+11 0.307698E+11 0.00 0.00
Minimum of Months 10444.39 0.00 0.00 0.236042E+10 0.00 0.00
Maximum of Months 0.403366E+11 0.00 0.101060E+11 0.261333E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.385814E+11 87351700.33 0.358443E+12 0.482946E+12 0.00 0.00 0.00 0.00
February 0.351717E+11 0.103383E+09 0.293567E+12 0.402002E+12 0.00 0.00 0.00 0.00
March 0.396693E+11 0.185438E+09 0.153814E+12 0.464533E+12 0.00 0.00 0.00 0.00
April 0.391936E+11 0.834694E+09 0.531148E+11 0.215444E+12 0.00 0.00 0.00 0.00
May 0.414159E+11 0.358649E+11 0.384041E+11 0.304861E+10 0.00 0.00 0.00 0.00
June 0.410188E+11 0.130877E+12 0.300778E+10 0.175995E+10 98664006.91 0.00 0.00 0.00
July 0.423026E+11 0.165079E+12 0.136697E+10 0.386480E+10 0.442517E+09 0.00 0.00 0.00
August 0.418617E+11 0.981671E+11 0.890566E+10 0.569513E+10 0.00 0.00 0.00 0.00
September 0.394688E+11 0.540210E+10 0.649675E+11 0.342945E+11 0.00 0.00 0.00 0.00
October 0.399085E+11 0.250005E+09 0.771024E+11 0.328167E+12 0.00 0.00 0.00 0.00
November 0.373936E+11 62665274.76 0.327599E+12 0.487364E+12 0.00 0.00 0.00 0.00
December 0.383750E+11 63520886.61 0.425520E+12 0.460525E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.474361E+12 0.436978E+12 0.180581E+13 0.288965E+13 0.541181E+09 0.00 0.00 0.00
Minimum of Months 0.351717E+11 62665274.76 0.136697E+10 0.175995E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.423026E+11 0.165079E+12 0.425520E+12 0.487364E+12 0.442517E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.261333E+10 0.00 0.334004E+11 0.651660E+11 0.00 0.00 0.00 0.00
February 0.236042E+10 0.00 0.300976E+11 0.543944E+11 0.00 0.00 0.00 0.00
March 0.261333E+10 0.00 0.164610E+11 0.670779E+11 0.00 0.00 0.00 0.00
April 0.252903E+10 2616970.02 0.211547E+10 0.490633E+11 0.00 0.00 0.00 0.00
May 0.261333E+10 0.174643E+10 10444.39 0.207764E+11 0.00 0.00 0.00 0.00
June 0.252903E+10 0.830878E+10 25277.82 0.516736E+10 0.101814E+09 0.00 0.00 0.00
July 0.261333E+10 0.101060E+11 29959.91 0.427298E+10 0.276805E+09 0.00 0.00 0.00
August 0.261333E+10 0.608464E+10 2765097.98 0.935707E+10 36350405.54 0.00 0.00 0.00
September 0.252903E+10 0.172724E+09 0.118353E+09 0.309372E+11 0.00 0.00 0.00 0.00
October 0.261333E+10 0.00 0.417402E+10 0.589020E+11 0.00 0.00 0.00 0.00
November 0.252903E+10 0.00 0.320821E+11 0.648559E+11 0.00 0.00 0.00 0.00
December 0.261333E+10 0.00 0.403366E+11 0.623433E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.307698E+11 0.264212E+11 0.158788E+12 0.492314E+12 0.414969E+09 0.00 0.00 0.00
Minimum of Months 0.236042E+10 0.00 10444.39 0.427298E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 0.101060E+11 0.403366E+11 0.670779E+11 0.276805E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.385814E+11 0.358443E+12 87351700.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.351717E+11 0.293567E+12 0.103383E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.396693E+11 0.153814E+12 0.185438E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.391936E+11 0.531148E+11 0.834694E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.414159E+11 0.384041E+11 0.358649E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.410188E+11 0.300778E+10 0.130877E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.423026E+11 0.136697E+10 0.165079E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.418617E+11 0.890566E+10 0.981671E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.394688E+11 0.649675E+11 0.540210E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.399085E+11 0.771024E+11 0.250005E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373936E+11 0.327599E+12 62665274.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.383750E+11 0.425520E+12 63520886.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.474361E+12 0.180581E+13 0.436978E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.351717E+11 0.136697E+10 62665274.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.423026E+11 0.425520E+12 0.165079E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.261333E+10 0.334004E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.236042E+10 0.300976E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.261333E+10 0.164610E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.252903E+10 0.211547E+10 2616970.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.261333E+10 10444.39 0.174643E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.252903E+10 25277.82 0.830878E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.261333E+10 29959.91 0.101060E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.261333E+10 2765097.98 0.608464E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.252903E+10 0.118353E+09 0.172724E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.261333E+10 0.417402E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.252903E+10 0.320821E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.261333E+10 0.403366E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.307698E+11 0.158788E+12 0.264212E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.236042E+10 10444.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261333E+10 0.403366E+11 0.101060E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.677363E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
February 0.597212E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
March 0.526918E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
April 0.458462E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
May 0.459718E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.76
June 0.341278E+11 0.00 0.00 0.00 4971662.82 0.00 0.00 0.00 0.86
July 0.327030E+11 0.00 0.00 0.00 22881916.42 0.00 0.00 0.00 0.85
August 0.389062E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.83
September 0.449798E+11 0.00 0.00 564777.44 0.00 0.00 0.338375E+10 0.00 0.66
October 0.425115E+11 0.00 0.00 889382.50 0.00 0.00 0.457637E+10 0.00 0.60
November 0.642551E+11 0.00 0.00 44985.57 0.00 0.00 0.412970E+09 0.00 0.59
December 0.736800E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
                   
Annual Sum or Average 0.603131E+12 0.00 0.00 1499145.51 27853579.25 0.00 0.837309E+10 0.00 0.68
Minimum of Months 0.327030E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
Maximum of Months 0.736800E+11 0.00 0.00 889382.50 22881916.42 0.00 0.457637E+10 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 15001990.95 0.00 0.00 0.00 0.00 0.627992E+10 0.00 0.00 1.00
February 0.446145E+09 0.00 0.00 0.00 0.00 0.510215E+10 0.00 0.00 0.99
March 0.180722E+10 0.00 0.00 106765.07 0.00 0.295788E+10 0.131171E+09 0.00 0.99
April 0.315214E+10 0.00 0.00 1358574.91 0.00 0.413703E+09 0.902867E+09 0.00 1.11
May 0.336045E+10 0.00 0.00 2142591.99 0.00 0.00 0.110043E+10 0.00 1.40
June 0.198798E+10 883634.30 0.00 4168335.72 0.00 0.00 0.133623E+10 0.00 1.62
July 0.216745E+10 3227877.49 0.00 4386643.64 0.00 0.00 0.969810E+09 0.00 1.61
August 0.272756E+10 0.00 0.00 3243174.25 0.00 0.00 0.107322E+10 0.00 1.57
September 0.405914E+10 0.00 0.00 610573.40 0.00 97221950.15 0.410176E+09 0.00 1.14
October 0.230317E+10 0.00 0.00 70246.56 0.00 0.199971E+10 77230789.47 0.00 1.00
November 63910073.62 0.00 0.00 0.00 0.00 0.594397E+10 0.00 0.00 1.00
December 0.00 0.00 0.00 0.00 0.00 0.684512E+10 0.00 0.00 1.00
                   
Annual Sum or Average 0.220902E+11 4111511.79 0.00 16086905.53 0.00 0.296397E+11 0.600114E+10 0.00 1.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.99
Maximum of Months 0.405914E+10 3227877.49 0.00 4386643.64 0.00 0.684512E+10 0.133623E+10 0.00 1.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.648265E+10 0.00 0.00 0.00 0.00 0.792543E+09 0.00 0.00 1.00
February 0.624046E+10 0.00 0.00 0.00 0.00 0.173875E+09 0.00 0.00 0.99
March 0.565935E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.99
April 0.491945E+10 0.00 0.00 106.19 0.00 0.00 4650254.59 0.00 1.04
May 0.489248E+10 0.00 0.00 7704.54 0.00 0.00 45098732.27 0.00 1.28
June 0.335496E+10 0.00 0.00 154022.45 533980.10 0.00 0.310374E+09 0.00 1.46
July 0.320170E+10 0.00 0.00 161848.26 2457626.03 0.00 0.310599E+09 0.00 1.43
August 0.396711E+10 0.00 0.00 95226.01 0.00 0.00 0.211505E+09 0.00 1.39
September 0.519453E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.11
October 0.505756E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.00
November 0.650795E+10 0.00 0.00 0.00 0.00 0.437713E+09 0.00 0.00 0.99
December 0.652174E+10 0.00 0.00 0.00 0.00 0.139184E+10 0.00 0.00 1.00
                   
Annual Sum or Average 0.619999E+11 0.00 0.00 418907.44 2991606.13 0.279597E+10 0.882228E+09 0.00 1.14
Minimum of Months 0.320170E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.99
Maximum of Months 0.652174E+10 0.00 0.00 161848.26 2457626.03 0.139184E+10 0.310599E+09 0.00 1.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9840179.47 0.00 0.00 0.00 0.00 0.109486E+10 0.00 0.00 0.06
February 17368810.97 0.00 0.00 0.00 0.00 0.777018E+09 0.00 0.00 0.05
March 41122073.10 0.00 0.00 0.00 0.00 0.284487E+09 0.00 0.00 0.02
April 62540174.60 0.00 0.00 38449.73 0.00 6466589.07 27798560.54 0.00 0.01
May 35210247.68 0.00 0.00 831291.51 0.00 0.00 0.385758E+09 0.00 0.06
June 739070.16 133782.44 0.00 2576780.99 0.00 0.00 0.884622E+09 0.00 0.18
July 1888428.88 759548.01 0.00 2969785.68 0.00 0.00 0.939808E+09 0.00 0.20
August 7888194.52 0.00 0.00 1985344.28 0.00 0.00 0.809734E+09 0.00 0.15
September 60511739.97 0.00 0.00 212165.74 0.00 0.00 0.134176E+09 0.00 0.02
October 61042093.53 0.00 0.00 2222.64 0.00 30773357.97 1764741.58 0.00 0.01
November 12761604.28 0.00 0.00 0.00 0.00 0.851806E+09 0.00 0.00 0.05
December 6288131.56 0.00 0.00 0.00 0.00 0.127771E+10 0.00 0.00 0.07
                   
Annual Sum or Average 0.317201E+09 893330.45 0.00 8616040.57 0.00 0.432312E+10 0.318366E+10 0.00 0.07
Minimum of Months 739070.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Maximum of Months 62540174.60 759548.01 0.00 2969785.68 0.00 0.127771E+10 0.939808E+09 0.00 0.20



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.458077E+10 0.00 0.00 0.51
February 75199538.24 0.00 0.00 0.00 0.00 0.396354E+10 0.00 0.00 0.51
March 0.444951E+09 0.00 0.00 0.00 0.00 0.311842E+10 0.00 0.00 0.51
April 0.259374E+10 0.00 0.00 0.00 0.00 0.506687E+09 0.00 0.00 0.53
May 0.310892E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.66
June 0.230795E+10 0.00 0.00 0.00 336216.73 0.00 0.00 0.00 0.75
July 0.221159E+10 0.00 0.00 0.00 1547426.55 0.00 0.00 0.00 0.74
August 0.263109E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.72
September 0.327070E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
October 0.192368E+10 0.00 0.00 0.00 0.00 0.126078E+10 0.00 0.00 0.52
November 0.00 0.00 0.00 0.00 0.00 0.437328E+10 0.00 0.00 0.51
December 0.00 0.00 0.00 0.00 0.00 0.498273E+10 0.00 0.00 0.51
                   
Annual Sum or Average 0.185678E+11 0.00 0.00 0.00 1883643.27 0.227862E+11 0.00 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.51
Maximum of Months 0.327070E+10 0.00 0.00 0.00 1547426.55 0.498273E+10 0.00 0.00 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.102721E+09 0.00 0.00 0.875799E+11 0.00 11.98
February 0.00 0.00 0.00 94563935.73 0.00 0.00 0.783547E+11 0.00 12.05
March 0.00 0.00 0.00 0.105895E+09 0.00 0.00 0.694389E+11 0.00 12.26
April 0.00 0.00 0.00 0.103248E+09 0.00 0.00 0.632843E+11 0.00 13.11
May 0.00 0.00 0.00 0.119373E+09 0.00 0.00 0.627023E+11 0.00 16.65
June 0.00 5223275.05 0.00 0.127553E+09 0.00 0.00 0.459085E+11 0.00 19.13
July 0.00 31122134.64 0.00 0.133622E+09 0.00 0.00 0.439784E+11 0.00 18.69
August 0.00 0.00 0.00 0.121405E+09 0.00 0.00 0.531609E+11 0.00 18.29
September 0.00 0.00 0.00 0.100846E+09 0.00 0.00 0.663162E+11 0.00 14.35
October 0.00 0.00 0.00 0.104713E+09 0.00 0.00 0.644346E+11 0.00 12.54
November 0.00 0.00 0.00 0.100228E+09 0.00 0.00 0.846747E+11 0.00 12.03
December 0.00 0.00 0.00 0.102068E+09 0.00 0.00 0.949327E+11 0.00 11.89
                   
Annual Sum or Average 0.00 36345409.69 0.00 0.131624E+10 0.00 0.00 0.814766E+12 0.00 14.43
Minimum of Months 0.00 0.00 0.00 94563935.73 0.00 0.00 0.439784E+11 0.00 11.89
Maximum of Months 0.00 31122134.64 0.00 0.133622E+09 0.00 0.00 0.949327E+11 0.00 19.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.380215E+11 0.00 0.00 0.00 0.00 0.156306E+11 0.00 0.00 3.02
February 0.431719E+11 0.00 0.00 0.00 0.00 0.413176E+10 0.00 0.00 3.01
March 0.405026E+11 0.00 0.00 128153.21 0.00 0.384315E+09 0.848819E+09 0.00 3.00
April 0.252229E+11 0.00 0.00 3552592.55 0.00 0.00 0.110915E+11 0.00 3.15
May 0.184531E+11 0.00 0.00 5592337.71 0.00 0.00 0.179544E+11 0.00 3.87
June 0.107587E+11 3742051.40 0.00 9252621.58 195876.01 0.00 0.162639E+11 0.00 4.41
July 0.106861E+11 16811014.48 0.00 10071620.35 1313168.31 0.00 0.152072E+11 0.00 4.35
August 0.137749E+11 0.00 0.00 10053359.76 0.00 0.00 0.170347E+11 0.00 4.22
September 0.282551E+11 0.00 0.00 2001699.50 0.00 0.00 0.100509E+11 0.00 3.37
October 0.353853E+11 0.00 0.00 189715.50 0.00 0.154800E+09 0.175758E+10 0.00 3.03
November 0.385150E+11 0.00 0.00 0.00 0.00 0.127069E+11 0.00 0.00 3.02
December 0.363853E+11 0.00 0.00 0.00 0.00 0.219748E+11 0.00 0.00 3.02
                   
Annual Sum or Average 0.339132E+12 20553065.88 0.00 40842100.17 1509044.32 0.549832E+11 0.902090E+11 0.00 3.46
Minimum of Months 0.106861E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.00
Maximum of Months 0.431719E+11 16811014.48 0.00 10071620.35 1313168.31 0.219748E+11 0.179544E+11 0.00 4.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145380E+12 0.00 0.00 0.00 0.00 0.489221E+10 0.00 0.00 1.22
February 0.132490E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.22
March 0.116771E+12 0.00 0.00 3848.47 0.00 0.00 0.124789E+09 0.00 1.22
April 0.890813E+11 0.00 0.00 2699885.49 0.00 0.00 0.126250E+11 0.00 1.27
May 0.637512E+11 0.00 0.00 12855939.49 0.00 0.00 0.382239E+11 0.00 1.57
June 0.341623E+11 0.00 0.00 35198081.44 11029550.17 0.00 0.415719E+11 0.00 1.79
July 0.305802E+11 14105079.44 0.00 34951362.83 36658066.47 0.00 0.420191E+11 0.00 1.76
August 0.409428E+11 0.00 0.00 28891910.35 0.00 0.00 0.454021E+11 0.00 1.71
September 0.888619E+11 0.00 0.00 3642702.59 0.00 0.00 0.184294E+11 0.00 1.36
October 0.103053E+12 0.00 0.00 213636.09 0.00 0.00 0.141271E+10 0.00 1.23
November 0.143465E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.22
December 0.161340E+12 0.00 0.00 0.00 0.00 0.211818E+10 0.00 0.00 1.22
                   
Annual Sum or Average 0.114988E+13 14105079.44 0.00 0.118457E+09 47687616.64 0.701039E+10 0.199809E+12 0.00 1.40
Minimum of Months 0.305802E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.22
Maximum of Months 0.161340E+12 14105079.44 0.00 35198081.44 36658066.47 0.489221E+10 0.454021E+11 0.00 1.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 66719.36 0.00 0.314435E+10 3258420.21 0.00 0.34
February 12145410.14 0.00 0.00 146795.55 0.00 0.283833E+10 4905868.47 0.00 0.34
March 56296486.51 0.00 0.00 367711.84 0.00 0.209908E+10 44004723.64 0.00 0.34
April 65759662.13 0.00 0.00 4801068.19 0.00 0.827625E+09 0.513514E+09 0.00 0.34
May 35557990.52 0.00 0.00 9937859.90 0.00 0.137318E+09 0.116660E+10 0.00 0.34
June 8890469.04 1231194.09 0.00 14956112.74 0.00 2546210.93 0.972233E+09 0.00 0.34
July 14801645.92 4647280.37 0.00 13837179.83 0.00 2424598.21 0.815844E+09 0.00 0.34
August 34032369.78 8992.76 0.00 10784658.28 0.00 54786065.78 0.962791E+09 0.00 0.34
September 75015922.65 0.00 0.00 2816453.15 0.00 0.713590E+09 0.527041E+09 0.00 0.34
October 39645574.51 0.00 0.00 317564.10 0.00 0.144730E+10 34643013.48 0.00 0.34
November 0.00 0.00 0.00 97278.65 0.00 0.298960E+10 4811343.07 0.00 0.34
December 0.00 0.00 0.00 33658.62 0.00 0.348995E+10 1519079.48 0.00 0.34
                   
Annual Sum or Average 0.342146E+09 5887467.22 0.00 58163060.21 0.00 0.177469E+11 0.505116E+10 0.00 0.34
Minimum of Months 0.00 0.00 0.00 33658.62 0.00 2424598.21 1519079.48 0.00 0.34
Maximum of Months 75015922.65 4647280.37 0.00 14956112.74 0.00 0.348995E+10 0.116660E+10 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 33211.08 0.00 0.314540E+10 1872130.83 0.00 0.34
February 0.00 0.00 0.00 94156.52 0.00 0.285265E+10 2446921.69 0.00 0.34
March 12916782.21 0.00 0.00 224894.09 0.00 0.217832E+10 8024962.22 0.00 0.34
April 64934682.55 0.00 0.00 2825932.08 0.00 0.994606E+09 0.349168E+09 0.00 0.34
May 0.197496E+09 0.00 0.00 6665370.39 0.00 0.177623E+09 0.967468E+09 0.00 0.34
June 0.233971E+09 1075434.30 156.52 11196189.23 154638.51 1879151.05 0.751463E+09 820.51 0.34
July 0.191077E+09 3951844.73 2724.86 10138099.36 690388.15 2224991.83 0.643368E+09 1778.14 0.35
August 0.215867E+09 8991.70 0.00 6032577.15 0.00 71904350.02 0.768466E+09 0.00 0.34
September 99601713.36 0.00 0.00 1358637.97 0.00 0.886323E+09 0.331025E+09 0.00 0.34
October 22967226.06 0.00 0.00 264415.30 0.00 0.148228E+10 16213181.61 0.00 0.34
November 0.00 0.00 0.00 47156.42 0.00 0.299168E+10 2437676.64 0.00 0.34
December 0.00 0.00 0.00 21395.78 0.00 0.349004E+10 1030068.11 0.00 0.34
                   
Annual Sum or Average 0.103883E+10 5036270.73 2881.37 38902035.35 845026.65 0.182749E+11 0.384298E+10 2598.65 0.34
Minimum of Months 0.00 0.00 0.00 21395.78 0.00 1879151.05 1030068.11 0.00 0.34
Maximum of Months 0.233971E+09 3951844.73 2724.86 11196189.23 690388.15 0.349004E+10 0.967468E+09 1778.14 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.161506E+10 0.00 0.00 0.02
February 0.451715E+09 0.00 0.00 0.00 0.00 0.574826E+09 0.00 0.00 0.02
March 0.880481E+09 0.00 0.00 0.00 0.00 16790647.54 0.00 0.00 0.02
April 0.376902E+09 0.00 0.00 2786076.73 0.00 0.00 0.958197E+09 0.00 0.02
May 82244984.66 0.00 0.00 3727227.74 0.00 0.00 0.127685E+10 0.00 0.02
June 71312880.15 1674308.84 0.00 3925972.83 0.00 0.00 0.956111E+09 0.00 0.02
July 39647454.55 8506442.62 0.00 3950555.05 0.00 0.00 0.675777E+09 0.00 0.02
August 91339755.43 0.00 0.00 4211705.44 0.00 0.00 0.883318E+09 0.00 0.02
September 0.655381E+09 0.00 0.00 1682954.91 0.00 0.00 0.684667E+09 0.00 0.02
October 0.976765E+09 0.00 0.00 113243.91 0.00 53747863.25 69400754.81 0.00 0.02
November 63743037.76 0.00 0.00 0.00 0.00 0.142133E+10 0.00 0.00 0.02
December 0.00 0.00 0.00 0.00 0.00 0.195716E+10 0.00 0.00 0.02
                   
Annual Sum or Average 0.368953E+10 10180751.47 0.00 20397736.61 0.00 0.563891E+10 0.550432E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 0.976765E+09 8506442.62 0.00 4211705.44 0.00 0.195716E+10 0.127685E+10 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.370546E+09 0.00 0.00 629551.06 0.00 0.422501E+11 70044884.54 0.00 0.39
February 0.510658E+09 0.00 0.00 1025203.96 0.00 0.377965E+11 0.420848E+09 0.00 0.39
March 0.994260E+09 0.00 0.00 2598351.26 0.00 0.269198E+11 0.191808E+10 0.00 0.39
April 0.105040E+10 0.00 0.00 28708646.67 0.00 0.631593E+10 0.117516E+11 0.00 0.39
May 0.268449E+10 0.00 0.00 95523243.75 0.00 45173679.22 0.154766E+11 0.00 0.39
June 0.353011E+10 12325840.74 0.00 0.147449E+09 4372611.78 2871569.67 0.986375E+10 0.00 0.39
July 0.279497E+10 51038742.97 0.00 0.142219E+09 11991441.63 4637721.26 0.854462E+10 0.00 0.39
August 0.300005E+10 121967.04 0.00 95940724.32 0.00 26563630.75 0.112865E+11 0.00 0.39
September 0.137156E+10 0.00 0.00 41258904.67 0.00 0.124906E+10 0.152202E+11 0.00 0.39
October 0.103013E+10 0.00 0.00 9478624.78 0.00 0.127887E+11 0.681303E+10 0.00 0.39
November 0.437813E+09 0.00 0.00 596529.29 0.00 0.401105E+11 65125865.73 0.00 0.39
December 0.221038E+09 0.00 0.00 490225.35 0.00 0.470682E+11 64879597.80 0.00 0.39
                   
Annual Sum or Average 0.179960E+11 63486550.75 0.00 0.565918E+09 16364053.41 0.214578E+12 0.814953E+11 0.00 0.39
Minimum of Months 0.221038E+09 0.00 0.00 490225.35 0.00 2871569.67 64879597.80 0.00 0.39
Maximum of Months 0.353011E+10 51038742.97 0.00 0.147449E+09 11991441.63 0.470682E+11 0.154766E+11 0.00 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 49886.46 0.00 0.314476E+10 2864921.02 0.00 0.34
February 14413063.09 0.00 0.00 165081.34 0.00 0.283421E+10 6737096.28 0.00 0.34
March 68615399.72 0.00 0.00 393280.57 0.00 0.205171E+10 79031860.53 0.00 0.34
April 41909761.57 0.00 0.00 4121838.44 0.00 0.806828E+09 0.558840E+09 0.00 0.34
May 10718768.38 0.00 0.00 12415837.53 0.00 85337770.43 0.124094E+10 0.00 0.34
June 6939909.13 1231194.09 0.00 16210976.66 0.00 1278334.71 0.974197E+09 0.00 0.34
July 11982228.59 4647280.37 0.00 16736134.47 0.00 1403473.86 0.816786E+09 0.00 0.34
August 15959633.70 8992.76 0.00 12174959.79 0.00 43848571.48 0.990411E+09 0.00 0.34
September 51531383.43 0.00 0.00 3433116.26 0.00 0.632038E+09 0.631461E+09 0.00 0.34
October 51061786.45 0.00 0.00 410631.11 0.00 0.138739E+10 83039310.01 0.00 0.34
November 0.00 0.00 0.00 73657.88 0.00 0.299039E+10 4054164.77 0.00 0.34
December 0.00 0.00 0.00 26670.00 0.00 0.349028E+10 1197142.14 0.00 0.34
                   
Annual Sum or Average 0.273132E+09 5887467.22 0.00 66212070.52 0.00 0.174695E+11 0.538956E+10 0.00 0.34
Minimum of Months 0.00 0.00 0.00 26670.00 0.00 1278334.71 1197142.14 0.00 0.34
Maximum of Months 68615399.72 4647280.37 0.00 16736134.47 0.00 0.349028E+10 0.124094E+10 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 20628.06 0.00 0.314614E+10 1143005.64 0.00 0.34
February 384347.34 0.00 0.00 102219.76 0.00 0.285061E+10 4102097.58 0.00 0.34
March 42762848.45 0.00 0.00 229345.39 0.00 0.212253E+10 33969438.75 0.00 0.34
April 72509135.36 0.00 0.00 2074858.11 0.00 0.952233E+09 0.384717E+09 0.00 0.34
May 0.150527E+09 0.00 0.00 9417836.61 0.00 0.129440E+09 0.105987E+10 0.00 0.34
June 0.207944E+09 1075434.30 0.00 13232490.36 154638.51 1034968.58 0.776298E+09 977.03 0.34
July 0.180287E+09 3996802.40 3066.44 12878420.16 645430.48 969129.62 0.652674E+09 1436.56 0.35
August 0.200728E+09 8991.70 0.00 7892995.91 0.00 55870484.57 0.797778E+09 0.00 0.34
September 0.100841E+09 0.00 0.00 1841064.49 0.00 0.747879E+09 0.467748E+09 0.00 0.34
October 33349092.85 0.00 0.00 255509.58 0.00 0.146262E+10 25501072.26 0.00 0.34
November 0.00 0.00 0.00 32279.74 0.00 0.299274E+10 1388796.03 0.00 0.34
December 0.00 0.00 0.00 14719.67 0.00 0.349044E+10 637000.42 0.00 0.34
                   
Annual Sum or Average 0.989332E+09 5081228.40 3066.44 47992367.84 800068.98 0.179525E+11 0.420582E+10 2413.59 0.34
Minimum of Months 0.00 0.00 0.00 14719.67 0.00 969129.62 637000.42 0.00 0.34
Maximum of Months 0.207944E+09 3996802.40 3066.44 13232490.36 645430.48 0.349044E+10 0.105987E+10 1436.56 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.320607E+10 0.00 0.00 0.00 0.00 0.344720E+11 0.00 0.00 0.33
February 0.686553E+10 0.00 0.00 0.00 0.00 0.263542E+11 0.00 0.00 0.33
March 0.192792E+11 0.00 0.00 0.00 0.00 0.100304E+11 0.00 0.00 0.33
April 0.249401E+11 0.00 0.00 0.00 0.00 0.561690E+09 0.00 0.00 0.35
May 0.255717E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
June 0.189835E+11 0.00 0.00 0.00 2765472.63 0.00 0.00 0.00 0.49
July 0.181910E+11 0.00 0.00 0.00 12727997.83 0.00 0.00 0.00 0.48
August 0.216415E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
September 0.269024E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.37
October 0.203155E+11 0.00 0.00 0.00 0.00 0.587749E+10 0.00 0.00 0.34
November 0.337741E+10 0.00 0.00 0.00 0.00 0.325940E+11 0.00 0.00 0.33
December 0.122171E+10 0.00 0.00 0.00 0.00 0.397626E+11 0.00 0.00 0.33
                   
Annual Sum or Average 0.190496E+12 0.00 0.00 0.00 15493470.46 0.149652E+12 0.00 0.00 0.38
Minimum of Months 0.122171E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.33
Maximum of Months 0.269024E+11 0.00 0.00 0.00 12727997.83 0.397626E+11 0.00 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2513.71 0.00 0.786707E+09 209400.86 0.00 0.34
February 563154.80 0.00 0.00 14294.66 0.00 0.712423E+09 881876.11 0.00 0.34
March 8368145.12 0.00 0.00 57264.70 0.00 0.533219E+09 8292221.38 0.00 0.34
April 15620893.06 0.00 0.00 1177307.04 0.00 0.234712E+09 0.101415E+09 0.00 0.34
May 8672886.01 0.00 0.00 2380890.37 0.00 73548783.83 0.252750E+09 0.00 0.34
June 2120287.82 307798.52 0.00 3683673.14 0.00 2325907.39 0.241527E+09 0.00 0.34
July 3595986.53 1161820.09 0.00 3372152.82 0.00 5978994.74 0.198780E+09 0.00 0.34
August 8416991.61 2248.19 0.00 2556914.77 0.00 30824592.28 0.223800E+09 0.00 0.34
September 18459083.40 0.00 0.00 640591.47 0.00 0.230146E+09 80370389.49 0.00 0.34
October 6550949.68 0.00 0.00 61175.60 0.00 0.369747E+09 4117002.36 0.00 0.34
November 0.00 0.00 0.00 2552.55 0.00 0.748239E+09 386391.16 0.00 0.34
December 0.00 0.00 0.00 2260.78 0.00 0.872693E+09 181411.80 0.00 0.34
                   
Annual Sum or Average 72368378.04 1471866.80 0.00 13951591.61 0.00 0.460056E+10 0.111271E+10 0.00 0.34
Minimum of Months 0.00 0.00 0.00 2260.78 0.00 2325907.39 181411.80 0.00 0.34
Maximum of Months 18459083.40 1161820.09 0.00 3683673.14 0.00 0.872693E+09 0.252750E+09 0.00 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2286.52 0.00 0.786557E+09 268034.20 0.00 0.34
February 0.00 0.00 0.00 10505.37 0.00 0.713326E+09 461759.17 0.00 0.34
March 1350168.06 0.00 0.00 45429.69 0.00 0.546983E+09 1493608.91 0.00 0.34
April 13912443.93 0.00 0.00 677319.64 0.00 0.270063E+09 68230978.29 0.00 0.34
May 48346263.84 0.00 0.00 1571245.14 0.00 81752350.96 0.205643E+09 0.00 0.34
June 53933696.29 269102.83 0.00 2936298.63 38659.63 784965.09 0.191972E+09 0.00 0.34
July 47397233.15 999200.60 682.88 2577761.70 161357.62 3524220.31 0.158203E+09 442.87 0.35
August 53523588.25 2247.93 0.00 1406867.60 0.00 31444344.03 0.179193E+09 0.00 0.34
September 22139145.78 0.00 0.00 283384.73 0.00 0.256756E+09 50398254.22 0.00 0.34
October 4091566.24 0.00 0.00 55588.52 0.00 0.374603E+09 1681566.51 0.00 0.34
November 0.00 0.00 0.00 3047.08 0.00 0.748213E+09 324596.91 0.00 0.34
December 0.00 0.00 0.00 1980.63 0.00 0.872611E+09 160949.39 0.00 0.34
                   
Annual Sum or Average 0.244694E+09 1270551.36 682.88 9571715.25 200017.25 0.468662E+10 0.858031E+09 442.87 0.34
Minimum of Months 0.00 0.00 0.00 1980.63 0.00 784965.09 160949.39 0.00 0.34
Maximum of Months 53933696.29 999200.60 682.88 2936298.63 161357.62 0.872611E+09 0.205643E+09 442.87 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 22149510.83 0.00 0.00 126809.35 0.00 0.502435E+10 8929964.21 0.00 0.39
February 86518904.12 0.00 0.00 312095.86 0.00 0.447424E+10 25254569.56 0.00 0.39
March 73591044.67 0.00 0.00 2717380.93 0.00 0.315845E+10 0.298303E+09 0.00 0.39
April 35788627.01 0.00 0.00 10049958.86 0.00 0.979066E+09 0.124246E+10 0.00 0.39
May 14433636.66 0.00 0.00 16399294.45 0.00 87880558.34 0.204861E+10 0.00 0.39
June 11146343.07 1977448.32 0.00 20740991.86 0.00 4730055.53 0.156730E+10 0.00 0.39
July 18613701.39 7464100.81 0.00 20837771.94 0.00 3982024.24 0.131680E+10 0.00 0.39
August 18361396.85 14443.47 0.00 18196318.71 0.00 43336953.83 0.162644E+10 0.00 0.39
September 56289809.54 0.00 0.00 7847631.18 0.00 0.616510E+09 0.143697E+10 0.00 0.39
October 79652031.41 0.00 0.00 1680658.74 0.00 0.200189E+10 0.361136E+09 0.00 0.39
November 35977366.26 0.00 0.00 171984.97 0.00 0.476353E+10 9878857.03 0.00 0.39
December 0.00 0.00 0.00 70444.29 0.00 0.560212E+10 5596382.50 0.00 0.39
                   
Annual Sum or Average 0.452522E+09 9455992.60 0.00 99151341.12 0.00 0.267601E+11 0.994767E+10 0.00 0.39
Minimum of Months 0.00 0.00 0.00 70444.29 0.00 3982024.24 5596382.50 0.00 0.39
Maximum of Months 86518904.12 7464100.81 0.00 20837771.94 0.00 0.560212E+10 0.204861E+10 0.00 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.694631E+11 0.00 0.00 4409006.35 0.00 0.00 0.246965E+11 0.00 3.93
February 0.562236E+11 0.00 0.00 4721668.28 0.00 0.00 0.267935E+11 0.00 3.92
March 0.435300E+11 0.00 0.00 8004852.16 0.00 0.00 0.297119E+11 0.00 3.91
April 0.277355E+11 0.00 0.00 15295293.97 0.00 0.00 0.359826E+11 0.00 4.09
May 0.171791E+11 0.00 0.00 27834676.47 0.00 0.00 0.467032E+11 0.00 5.04
June 0.892851E+10 2435405.82 0.00 39951348.34 4475983.89 0.00 0.385765E+11 0.00 5.76
July 0.715859E+10 26984156.26 0.00 39382645.86 4825290.07 0.00 0.383435E+11 0.00 5.66
August 0.133369E+11 0.00 0.00 32666541.23 0.00 0.00 0.407369E+11 0.00 5.49
September 0.240158E+11 0.00 0.00 18765867.01 0.00 0.00 0.431991E+11 0.00 4.38
October 0.324396E+11 0.00 0.00 11424265.10 0.00 0.00 0.330098E+11 0.00 3.95
November 0.644251E+11 0.00 0.00 4155863.70 0.00 0.00 0.254695E+11 0.00 3.93
December 0.796130E+11 0.00 0.00 3012111.18 0.00 0.00 0.228108E+11 0.00 3.93
                   
Annual Sum or Average 0.444049E+12 29419562.08 0.00 0.209624E+09 9301273.96 0.00 0.406034E+12 0.00 4.50
Minimum of Months 0.715859E+10 0.00 0.00 3012111.18 0.00 0.00 0.228108E+11 0.00 3.91
Maximum of Months 0.796130E+11 26984156.26 0.00 39951348.34 4825290.07 0.00 0.467032E+11 0.00 5.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.575522E+11 0.00 0.00 8238169.56 0.00 0.00 0.366215E+11 0.00 3.94
February 0.463615E+11 0.00 0.00 8527056.57 0.00 0.00 0.366676E+11 0.00 3.92
March 0.326208E+11 0.00 0.00 13370840.11 0.00 0.00 0.406296E+11 0.00 3.91
April 0.211641E+11 0.00 0.00 22235801.55 0.00 0.00 0.425591E+11 0.00 4.10
May 0.114862E+11 0.00 0.00 36613969.01 0.00 0.00 0.525036E+11 0.00 5.05
June 0.468379E+10 6296580.72 0.00 49751409.80 616124.03 0.00 0.430510E+11 0.00 5.79
July 0.376035E+10 28501254.36 0.00 50021681.32 3314244.36 0.00 0.419481E+11 0.00 5.70
August 0.860896E+10 0.00 0.00 41345497.01 0.00 0.00 0.456399E+11 0.00 5.51
September 0.185421E+11 0.00 0.00 26598075.57 0.00 0.00 0.486781E+11 0.00 4.39
October 0.268339E+11 0.00 0.00 17995033.34 0.00 0.00 0.386214E+11 0.00 3.95
November 0.528637E+11 0.00 0.00 7809615.98 0.00 0.00 0.370444E+11 0.00 3.93
December 0.569268E+11 0.00 0.00 6530030.42 0.00 0.00 0.455129E+11 0.00 3.94
                   
Annual Sum or Average 0.341404E+12 34797835.07 0.00 0.289037E+09 3930368.39 0.00 0.509477E+12 0.00 4.52
Minimum of Months 0.376035E+10 0.00 0.00 6530030.42 0.00 0.00 0.366215E+11 0.00 3.91
Maximum of Months 0.575522E+11 28501254.36 0.00 50021681.32 3314244.36 0.00 0.525036E+11 0.00 5.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 99402528.80 0.00 0.00 0.802389E+11 0.00 11.07
February 0.00 0.00 0.00 92806878.95 0.00 0.00 0.717732E+11 0.00 11.32
March 0.00 0.00 0.00 0.106312E+09 0.00 0.00 0.662746E+11 0.00 11.87
April 0.00 0.00 0.00 0.108107E+09 0.00 0.00 0.632202E+11 0.00 13.24
May 0.00 0.00 0.00 0.127489E+09 0.00 0.00 0.634573E+11 0.00 17.55
June 0.00 8616388.21 0.00 0.136625E+09 0.00 0.00 0.472458E+11 0.00 20.02
July 0.00 39636792.79 0.00 0.143928E+09 0.00 0.00 0.440091E+11 0.00 19.55
August 0.00 0.00 0.00 0.128512E+09 0.00 0.00 0.534383E+11 0.00 18.92
September 0.00 0.00 0.00 0.104796E+09 0.00 0.00 0.658554E+11 0.00 14.55
October 0.00 0.00 0.00 0.104978E+09 0.00 0.00 0.624505E+11 0.00 12.19
November 0.00 0.00 0.00 96803028.74 0.00 0.00 0.775045E+11 0.00 11.08
December 0.00 0.00 0.00 98294435.90 0.00 0.00 0.868218E+11 0.00 10.92
                   
Annual Sum or Average 0.00 48253181.00 0.00 0.134805E+10 0.00 0.00 0.782290E+12 0.00 14.38
Minimum of Months 0.00 0.00 0.00 92806878.95 0.00 0.00 0.440091E+11 0.00 10.92
Maximum of Months 0.00 39636792.79 0.00 0.143928E+09 0.00 0.00 0.868218E+11 0.00 20.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.103025E+11 0.00 0.00 0.34
February 0.323352E+09 0.00 0.00 0.00 0.00 0.846947E+10 0.00 0.00 0.33
March 0.256557E+10 0.00 0.00 0.00 0.00 0.517951E+10 0.00 0.00 0.33
April 0.607304E+10 0.00 0.00 5630.46 0.00 0.648087E+09 16933946.38 0.00 0.35
May 0.568180E+10 0.00 0.00 2445299.43 0.00 0.00 0.116906E+10 0.00 0.45
June 0.988268E+09 1485050.69 0.00 13348522.80 0.00 0.00 0.479219E+10 0.00 0.62
July 0.122808E+10 6049903.77 0.00 14002999.47 0.00 0.00 0.418071E+10 0.00 0.60
August 0.370757E+10 0.00 0.00 6002966.48 0.00 0.00 0.227695E+10 0.00 0.52
September 0.706464E+10 0.00 0.00 0.00 0.00 43484683.42 0.00 0.00 0.37
October 0.410067E+10 0.00 0.00 0.00 0.00 0.282002E+10 0.00 0.00 0.34
November 0.00 0.00 0.00 0.00 0.00 0.956394E+10 0.00 0.00 0.33
December 0.00 0.00 0.00 0.00 0.00 0.109923E+11 0.00 0.00 0.34
                   
Annual Sum or Average 0.317330E+11 7534954.46 0.00 35805418.65 0.00 0.480194E+11 0.124359E+11 0.00 0.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.33
Maximum of Months 0.706464E+10 6049903.77 0.00 14002999.47 0.00 0.109923E+11 0.479219E+10 0.00 0.62



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:54:51

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January -0.475104E+11 0.366034E+11 0.459540E+12 0.114426E+13 0.757263E+11
February 0.113664E+11 0.314513E+11 0.387620E+12 0.990709E+12 0.604741E+11
March 0.177611E+12 0.304816E+11 0.376206E+12 0.988085E+12 0.415892E+11
April 0.359684E+12 0.199847E+11 0.246227E+12 0.693795E+12 0.604635E+11
May 0.487516E+12 0.120911E+11 0.143402E+12 0.491642E+12 0.161045E+12
June 0.508753E+12 0.775485E+10 0.904317E+11 0.361370E+12 0.332988E+12
July 0.453032E+12 0.699210E+10 0.845665E+11 0.340972E+12 0.390952E+12
August 0.331169E+12 0.918159E+10 0.111146E+12 0.411845E+12 0.263625E+12
September 0.138469E+12 0.144312E+11 0.185937E+12 0.539537E+12 0.624100E+11
October 0.409935E+11 0.238692E+11 0.308985E+12 0.802576E+12 0.308580E+11
November -0.223336E+11 0.356440E+11 0.442860E+12 0.112000E+13 0.688366E+11
December -0.603486E+11 0.380314E+11 0.470964E+12 0.118171E+13 0.856506E+11
           
Annual Sum or Average 0.237840E+13 0.266516E+12 0.330789E+13 0.906650E+13 0.163462E+13
Minimum of Months -0.603486E+11 0.699210E+10 0.845665E+11 0.340972E+12 0.308580E+11
Maximum of Months 0.508753E+12 0.380314E+11 0.470964E+12 0.118171E+13 0.390952E+12