Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:55:34
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 8906.01 | 785.00 | 785.00 |
Net Site Energy | 8753.76 | 771.58 | 771.58 |
Total Source Energy | 17597.97 | 1551.13 | 1551.13 |
Net Source Energy | 17115.79 | 1508.63 | 1508.63 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 633.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 439.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 390.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 575.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 70.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 46.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2669.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3813.66 | 5092.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 633.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 439.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 150.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 366.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 575.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 70.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 46.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2669.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 633.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 439.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 150.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1648.46 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 390.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 575.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 70.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 46.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2669.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 52.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 96.44 | 291.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 187.70 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 336.15 | 448.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 52.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 96.44 | 291.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 187.70 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 336.15 | 448.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 159.710 | 4.19 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.46 | -0.2 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 152.252 | 3.99 |
Electricity Coming From Utility | 3661.410 | 96.01 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 3661.410 | 96.01 |
Total On-Site and Utility Electric Sources | 3813.662 | 100.00 |
Total Electricity End Uses | 3813.662 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 10.10 | 2.57 |
Air to Air Heat Recovery for Heating | 383.56 | 97.43 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 393.66 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 30.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7199.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:55 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 5.8772 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 7.1580 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 7.1580 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 6.8781 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.5805 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.9406 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 7.3625 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 7.7500 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.2625 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.3625 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 7.3625 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.5281 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.2625 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.3808 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.3808 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8772 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 7.1580 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 7.1580 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 6.8781 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.5805 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.9406 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 7.3625 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 7.7500 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.2625 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 7.3625 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 7.3625 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.5281 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.2625 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.3808 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.3808 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.2523 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-19:30 | 16-JAN-19:10 | - | - | - | - | - | - | - | - | - | - | 30-MAY-20:30 |
Heating | 0.00 | 141100.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97185.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36244.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 83438.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 19289.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28535.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3936.96 | 225501.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1682.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 295220.81 | 450040.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 141100.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 97185.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36244.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 33453.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1218.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 17944.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28535.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3936.96 | 225501.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 771.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 670.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 687.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1133.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 475.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.66 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1236.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1822.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 222.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 147.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 2893.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 12077.87 | 5520.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 60.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 160.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 12.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 255.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1064.57 | 486.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 60.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 160.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 12.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 255.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1064.57 | 486.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.12 | 0.710225 | 0.604000 | 1.28 | 1.00 | 0.500000 | 0.000536 | 0.000146 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.325975 | 0.156786 | 0.365000 | 0.118981 | 0.434316 | 0.500000 | 0.002430 | 0.000057 | 0.118981 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.199594 | 0.296520 | 0.689000 | 0.137520 | 0.790720 | 0.500000 | 0.001285 | 0.000031 | 0.137520 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.188039 | 0.665569 | 0.010000 | 0.001880 | 1.00 | 0.500000 | 0.000572 | 0.000036 | 0.058203 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.086641 | 0.833396 | 1.00 | 0.086641 | 1.00 | 0.500000 | 0.000457 | 0.000029 | 0.086641 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.28 | 0.018112 | 0.010000 | 0.032832 | 0.300000 | 0.500000 | 0.021036 | 0.000048 | 0.077164 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.45 | 0.099290 | 0.700000 | 1.01 | 0.700000 | 0.500000 | 0.003837 | 0.000222 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.49 | 0.222137 | 0.633000 | 2.84 | 0.633000 | 0.500000 | 0.001715 | 0.000584 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.08 | 1.00 | 0.657000 | 0.712579 | 1.00 | 0.500000 | 0.000348 | 0.000225 | 0.712579 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.03 | 0.124602 | 0.878000 | 1.78 | 0.878000 | 0.500000 | 0.003058 | 0.000299 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.13 | 0.118547 | 0.836000 | 1.78 | 0.836000 | 0.500000 | 0.003214 | 0.000301 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.15 | 0.065775 | 0.256000 | 0.551055 | 0.300000 | 0.500000 | 0.010419 | 0.000096 | 0.551055 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.634448 | 0.494980 | 0.297000 | 0.188431 | 1.00 | 0.500000 | 0.000770 | 0.000125 | 0.203289 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6674.17 | 0.000146 | 192.71 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2587.21 | 0.000057 | 95.88 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1423.63 | 0.000031 | 44.80 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1641.04 | 0.000036 | 68.00 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1329.31 | 0.000029 | 45.21 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2175.65 | 0.000048 | 90.15 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10142.21 | 0.000222 | 317.19 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 26716.05 | 0.000584 | 826.96 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4109.40 | 0.000090 | 185.60 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4110.04 | 0.000090 | 185.63 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 23501.62 | 0.000514 | 1061.40 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 23526.49 | 0.000515 | 1062.53 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4111.24 | 0.000090 | 185.68 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4111.88 | 0.000090 | 185.71 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 10272.31 | 0.000225 | 345.70 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1270.45 | 0.000028 | 57.37 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1270.79 | 0.000028 | 57.39 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6115.24 | 0.000134 | 276.16 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 13652.22 | 0.000299 | 410.27 |
DINING_FLR_6 VAV BOX REHEAT COIL | 13754.06 | 0.000301 | 413.69 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 4370.35 | 0.000096 | 131.92 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5732.59 | 0.000125 | 237.54 |
VAV WITH REHEAT HEATING COIL | 150146.66 | 0.003284 | 3251.04 |
FLR_3_DOAS HEATING COIL | 15340.96 | 0.000336 | 332.17 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.817367 | 0.000090 | 0.000259 |
ROOM_2_FLR_3 FAN COIL | 0.748374 | 0.000090 | 0.000237 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.82 | 0.000514 | 0.001797 |
ROOM_4_MULT19_FLR_3 FAN COIL | 4.51 | 0.000515 | 0.001513 |
ROOM_5_FLR_3 FAN COIL | 0.732397 | 0.000090 | 0.000232 |
ROOM_6_FLR_3 FAN COIL | 0.670503 | 0.000090 | 0.000213 |
ROOM_1_FLR_6 FAN COIL | 0.212612 | 0.000028 | 0.000067 |
ROOM_2_FLR_6 FAN COIL | 0.193331 | 0.000028 | 0.000061 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.21 | 0.000134 | 0.000387 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.817367 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.748374 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.82 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 4.51 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.732397 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.670503 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.212612 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.193331 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.21 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008598 | 12.80 | 0.008500 | 0.000259 | 0.817367 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008606 | 12.80 | 0.008500 | 0.000237 | 0.748374 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008506 | 12.80 | 0.008500 | 0.001797 | 5.82 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008817 | 12.80 | 0.008500 | 0.001513 | 4.51 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008609 | 12.80 | 0.008500 | 0.000232 | 0.732397 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008618 | 12.80 | 0.008500 | 0.000213 | 0.670503 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008594 | 12.80 | 0.008500 | 0.000067 | 0.212612 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008603 | 12.80 | 0.008500 | 0.000061 | 0.193331 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008643 | 12.80 | 0.008500 | 0.000387 | 1.21 | |
VAV WITH REHEAT COOLING COIL | 26.50 | 6.70 | 0.009320 | 10.95 | 0.008500 | 0.012243 | 20.08 | 428086.12 |
FLR_3_DOAS COOLING COIL | 29.40 | 6.70 | 0.008822 | 11.92 | 0.008500 | 0.001300 | 2.05 | 45447.84 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.93 | 10.53 | 20.18 | 10.53 | 20.08 | 20.08 | 0.300000 | 0.524507 | 20.08 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.08 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 9.33 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 20.08 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.012243 | 0.000039 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003284 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001300 | 0.000366 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000336 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.018311 | 2960.01 | |
HEATSYS1 PUMP | 0.007396 | 2205.19 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.007396 | 0.887476 |
COOLSYS1 | 0.018311 | 2.20 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 338085.57 | 338085.57 | 0.007396 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.018311 | 2049.31 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.018311 | 640243.38 | 640818.97 | 73.05 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 5.877 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.257 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 7.158 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 17.918 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 7.158 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 17.918 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 6.878 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.258 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.581 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.271 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.941 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.471 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 7.363 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.743 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 7.750 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.820 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.263 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.263 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.363 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.183 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.363 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.183 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.528 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.031 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.263 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.263 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 11630.030 | 5.877 | 109.203 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11630.030 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 480.097 | 7.158 | 44.334 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 480.097 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 555.954 | 7.158 | 44.334 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 555.954 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1129.686 | 6.878 | 425.975 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1129.686 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 339.286 | 3.581 | 166.317 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 339.286 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 385.564 | 4.941 | 45.901 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 385.564 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1390.496 | 7.363 | 9.772 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1390.496 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10138.453 | 7.750 | 24.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10138.453 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1659.841 | 4.263 | 79.202 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1659.841 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2441.829 | 7.363 | 9.771 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2441.829 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2441.829 | 7.363 | 9.771 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2441.829 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1190.908 | 11.528 | 53.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1190.908 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1756.685 | 4.263 | 79.201 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1756.685 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7546 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.8883 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.8810 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7876 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7805 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.158 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9584 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9677 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.102 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.114 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.43711420E-14 | 0.31093217E-16 | -0.15789436E-09 | 0.78758550E-16 |
29 | 8 | 0.23022052E-07 | 0.10246757E-12 | 0.38974329E-03 | -0.26176864E-09 |
30 | 7 | -0.12597811E-01 | 0.52558284E-08 | -0.23598652E-01 | 0.14324170E-03 |
31 | 6 | 0.41503002 | 0.18224974E-05 | 0.48032647 | -0.48618624E-02 |
32 | 5 | -5.2850199 | 0.67859432E-04 | -4.5044765 | 0.64355069E-01 |
33 | 4 | 33.420626 | 0.55371102E-03 | 21.687353 | -0.42766977 |
34 | 3 | -112.11499 | 0.12040638E-02 | -56.112333 | 1.5280352 |
35 | 2 | 198.01198 | 0.67593269E-03 | 78.322831 | -2.9147046 |
36 | 1 | -171.48986 | 0.72025056E-04 | -55.385224 | 2.7512893 |
37 | 0 | 57.057407 | 0.40909525E-06 | 15.537308 | |
38 | 9 | -0.25066581E-14 | 0.33473338E-16 | -0.15165523E-09 | 0.38583792E-16 |
39 | 8 | 0.22146796E-07 | 0.11988460E-12 | 0.38064773E-03 | -0.25181670E-09 |
40 | 7 | -0.12326740E-01 | 0.62060581E-08 | -0.23208464E-01 | 0.14015953E-03 |
41 | 6 | 0.40766501 | 0.21598984E-05 | 0.47406221 | -0.47750464E-02 |
42 | 5 | -5.2131519 | 0.80676365E-04 | -4.4564008 | 0.63463932E-01 |
43 | 4 | 33.102770 | 0.66017470E-03 | 21.499520 | -0.42344947 |
44 | 3 | -111.43882 | 0.14392361E-02 | -55.741026 | 1.5182660 |
45 | 2 | 197.34194 | 0.80979329E-03 | 77.982142 | -2.9040641 |
46 | 1 | -171.24241 | 0.86470291E-04 | -55.285886 | 2.7469524 |
47 | 0 | 57.057407 | 0.49239716E-06 | 15.553494 | |
48 | 9 | -0.28459328E-14 | 0.32762126E-16 | -0.15199605E-09 | 0.43003076E-16 |
49 | 8 | 0.22194661E-07 | 0.11894586E-12 | 0.38114823E-03 | -0.25236094E-09 |
50 | 7 | -0.12341667E-01 | 0.61542415E-08 | -0.23229953E-01 | 0.14032925E-03 |
51 | 6 | 0.40807058 | 0.21414273E-05 | 0.47440742 | -0.47798271E-02 |
52 | 5 | -5.2171096 | 0.79972373E-04 | -4.4590513 | 0.63513007E-01 |
53 | 4 | 33.120275 | 0.65430996E-03 | 21.509879 | -0.42368190 |
54 | 3 | -111.47606 | 0.14262484E-02 | -55.761503 | 1.5188041 |
55 | 2 | 197.37885 | 0.80238430E-03 | 78.000927 | -2.9046503 |
56 | 1 | -171.25604 | 0.85669138E-04 | -55.291354 | 2.7471913 |
57 | 0 | 57.057407 | 0.48777329E-06 | 15.552596 | |
58 | 9 | -0.42844289E-14 | 0.28320545E-16 | -0.15636867E-09 | 0.85480581E-16 |
59 | 8 | 0.22806714E-07 | 0.10679199E-12 | 0.38751646E-03 | -0.25932016E-09 |
60 | 7 | -0.12531483E-01 | 0.54901366E-08 | -0.23503188E-01 | 0.14248753E-03 |
61 | 6 | 0.41322793 | 0.19054371E-05 | 0.47879461 | -0.48406201E-02 |
62 | 5 | -5.2674357 | 0.71001872E-04 | -4.4927242 | 0.64137031E-01 |
63 | 4 | 33.342859 | 0.57975360E-03 | 21.641446 | -0.42663722 |
64 | 3 | -111.94957 | 0.12614747E-02 | -56.021588 | 1.5256452 |
65 | 2 | 197.84807 | 0.70855353E-03 | 78.239553 | -2.9121017 |
66 | 1 | -171.42933 | 0.75539563E-04 | -55.360912 | 2.7502285 |
67 | 0 | 57.057407 | 0.42933555E-06 | 15.541245 | |
68 | 9 | -0.42353945E-14 | 0.27136288E-16 | -0.15669806E-09 | 0.83928570E-16 |
69 | 8 | 0.22852977E-07 | 0.10586107E-12 | 0.38799547E-03 | -0.25984619E-09 |
70 | 7 | -0.12545752E-01 | 0.54398248E-08 | -0.23523727E-01 | 0.14264978E-03 |
71 | 6 | 0.41361563 | 0.18876143E-05 | 0.47912423 | -0.48451901E-02 |
72 | 5 | -5.2712188 | 0.70326153E-04 | -4.4952532 | 0.64183940E-01 |
73 | 4 | 33.359590 | 0.57415042E-03 | 21.651325 | -0.42685937 |
74 | 3 | -111.98516 | 0.12491162E-02 | -56.041117 | 1.5261594 |
75 | 2 | 197.88333 | 0.70152833E-03 | 78.257474 | -2.9126617 |
76 | 1 | -171.44235 | 0.74782356E-04 | -55.366142 | 2.7504567 |
77 | 0 | 57.057407 | 0.42497884E-06 | 15.540397 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 37 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 | ||
2 | RESWINDOW_U_0.248_SHGC_0.21 | 38 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.680 | 0.5995 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.312 | 3.5001E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1055 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 6.3264E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1206 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.4052E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.9599E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.8858E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9121E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.7843E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1210 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 7.5628E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1390 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.8249E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.6990E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.5814E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2628E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3264E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.7248E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5985E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.0955E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2092E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.9803E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 7.9852E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8610E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0256E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.7248E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5985E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.0955E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2092E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.9803E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 7.9852E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8610E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0256E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 28803.59870 | 28803.59870 | 2.12308 | 2.12308 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 24.96267 | 8.81442E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4422.06305 | 4422.06305 | 0.32598 | 0.32598 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1968.69136 | 1968.69136 | 8.56007E-002 | 8.56007E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2707.56557 | 2707.56557 | 0.19959 | 0.19959 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 28.49867 | 8.82005E-003 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 708.72879 | 708.72879 | 3.08172E-002 | 9.17335E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 77.66889 | 12.54000 | 9.17335E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2551.38062 | 2551.38062 | 0.18804 | 0.18804 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 28.77600 | 8.82049E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1338.55005 | 1338.55005 | 5.82033E-002 | 5.82033E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1175.56841 | 1175.56841 | 8.66414E-002 | 8.66414E-002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 878.95527 | 878.95527 | 3.82190E-002 | 5.77652E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44543.80672 | 44543.80672 | 3.28323 | 3.28323 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1774.65922 | 1774.65922 | 7.71638E-002 | 7.71638E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19646.16363 | 19646.16363 | 1.44942 | 1.44942 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 4867.23373 | 4867.23373 | 0.21163 | 0.67638 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 60857.68562 | 60857.68562 | 4.48749 | 4.48749 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 11948.82581 | 11948.82581 | 0.51956 | 1.89399 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 8229.41814 | 8229.41814 | 0.81737 | 0.81737 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 28.22133 | 8.81961E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4109.49771 | 4109.49771 | 0.17973 | 0.17973 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 7534.77580 | 7534.77580 | 0.74837 | 0.74837 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4110.13659 | 4110.13659 | 0.17976 | 0.17976 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 58630.24985 | 58630.24985 | 5.82303 | 5.82303 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 23501.89317 | 23501.89317 | 1.02791 | 1.02791 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 45412.96440 | 45412.96440 | 4.51068 | 4.51068 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 23526.75957 | 23526.75957 | 1.02900 | 1.02900 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 7373.92251 | 7373.92251 | 0.73240 | 0.73240 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4111.33460 | 4111.33460 | 0.17981 | 0.17981 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 6750.75017 | 6750.75017 | 0.67050 | 0.67050 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 23.97467 | 8.81286E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4111.97341 | 4111.97341 | 0.17984 | 0.17984 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 14714.88498 | 14714.88498 | 1.08459 | 1.08459 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 6567.06005 | 6567.06005 | 0.28555 | 0.47476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2140.61914 | 2140.61914 | 0.21261 | 0.21261 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1270.47873 | 1270.47873 | 5.55659E-002 | 5.55659E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 1946.49248 | 1946.49248 | 0.19333 | 0.19333 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1270.82019 | 1270.82019 | 5.55808E-002 | 5.55808E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12173.37473 | 12173.37473 | 1.20912 | 1.20912 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 6115.35382 | 6115.35382 | 0.26747 | 0.26747 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 27483.11208 | 27483.11208 | 2.02824 | 2.02824 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4390.82128 | 4390.82128 | 0.19092 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 28887.41822 | 28887.41822 | 2.13184 | 2.13184 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4485.22649 | 4485.22649 | 0.19503 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29128.08781 | 29128.08781 | 2.15256 | 2.15256 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1515.23666 | 1515.23666 | 6.58762E-002 | 0.36735 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8607.76449 | 8607.76449 | 0.63445 | 0.63445 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 4675.20517 | 4675.20517 | 0.20329 | 0.20329 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 328129.86 | 20.07686 | 20.07686 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 179892.04 | 7.21628 | 7.21628 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 40614.20 | 14.21530 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 51134.75 | 3.15468 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12308 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71023 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28234 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.36449E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45998E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28234 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6674.17164 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45998E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 192.70506 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.32598 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15679 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11898 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43432 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43006E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.65952E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11898 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2587.20568 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.65952E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 95.87541 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.19959 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29652 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.68900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13752 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79072 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28490E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.11419E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13752 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1423.63005 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.11419E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 44.80300 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18804 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66557 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88039E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.72442E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.58979E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.82033E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1641.04450 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.58979E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 67.99548 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.66414E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.83340 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66414E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.57166E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.90788E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66414E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1329.31457 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.90788E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.20965 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.28323 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.81120E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.28323E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10357E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.75924E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.71638E-002 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2175.64837 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.75924E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 90.14661 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44942 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.92898E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.70000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01459 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.83725E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.21861E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01459 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10142.20503 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.21861E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 317.18980 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.48749 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22214 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.63300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84058 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63300 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71516E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.84414E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84058 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26716.05061 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.84414E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 826.95568 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81737 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.81737 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.98933E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.58689E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69129 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59767E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.58689E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.81737 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4109.40057 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.98933E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 185.59787 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.74837 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.74837 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.99072E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.37420E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69127 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60646E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.37420E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.74837 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4110.03944 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.99072E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 185.62670 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.82303 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.82303 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.14099E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.79710E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69178 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50624E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.79710E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.82303 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 23501.62268 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.14099E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1061.40386 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.51068 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 4.51068 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.14643E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.51282E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69078 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.81692E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.51282E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.51068 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 23526.48879 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.14643E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1062.52652 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.73240 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.73240 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.99334E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.32494E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69127 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60873E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.32494E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.73240 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4111.23743 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.99334E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 185.68079 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.67050 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.67050 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.99474E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.13410E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69126 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61848E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.13410E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.67050 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4111.87622 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.99474E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 185.70962 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08459 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.65700 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71258 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48158E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.24707E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71258 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10272.31378 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24707E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 345.69659 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.21261 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.21261 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.77911E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.72218E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69129 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59398E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.72218E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.21261 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1270.44955 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.77911E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 57.37360 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.19333 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.19333 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.77986E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.12795E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69128 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60320E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.12795E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.19333 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1270.79100 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.77986E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 57.38902 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.20912 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.20912 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.33771E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.87435E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69104 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64341E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.87435E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.20912 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6115.24075 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33771E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 276.16073 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.02824 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12460 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.87800 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78079 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87800 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05773E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.98643E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78079 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13652.22442 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.98643E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 410.27454 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13184 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11855 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.83600 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78222 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83600 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21392E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.00870E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78222 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13754.05639 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00870E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 413.68700 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15256 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.57749E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55105 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04185E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.56015E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55105 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4370.34906 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.56015E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 131.91974 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63445 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.49498 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18843 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.69729E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25401E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20329 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5732.58810 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25401E-004 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 237.54473 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.92940 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.53045 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.17516 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.53045 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.07686 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.07686 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.52451 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.07686 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.07686 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32920 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.50328 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95327 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.32048E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 428086.12363 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.22432E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.07686 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 150146.65854 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28446E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3251.04139 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.07686 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.22432E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.88943E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.28446E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.40000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91727 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82150E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45447.83718 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29980E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15340.96456 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.35584E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 332.16930 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.29980E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.66356E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.35584E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.83109E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 2960.00705 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 7.39563E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.88748 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 7.39563E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2205.18749 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 338085.57170 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 338085.57000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 7.39563E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.83109E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.19731 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.83109E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2049.31272 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.83109E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 640243.38008 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 640818.97000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 73.05336 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 10135.64 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3929.58 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2160.72 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2490.80 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2020.44 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 3302.23 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15393.90 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 40552.16 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6951.51 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6952.59 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 39755.19 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 39797.25 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6954.61 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6955.69 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15614.36 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2148.99 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2149.57 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10344.00 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 20726.38 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 20880.86 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6634.74 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8700.99 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 153927.43 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 15727.26 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 13401.74 | 11530.42 | 1871.32 | 0.86 | 2635.31 | 26.73 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 12292.40 | 10565.50 | 1726.90 | 0.86 | 2413.88 | 24.48 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 93832.55 | 81577.44 | 12255.11 | 0.87 | 18909.22 | 191.79 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 76932.36 | 64690.62 | 12241.74 | 0.84 | 14399.81 | 146.05 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 12035.00 | 10341.67 | 1693.32 | 0.86 | 2361.92 | 23.96 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 11037.70 | 9474.53 | 1563.17 | 0.86 | 2160.66 | 21.91 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3483.65 | 2998.45 | 485.20 | 0.86 | 685.69 | 6.95 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3173.14 | 2728.39 | 444.75 | 0.86 | 623.05 | 6.32 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 19994.98 | 17116.88 | 2878.11 | 0.86 | 3889.18 | 39.45 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 497573.19 | 351114.97 | 146458.22 | 0.71 | 79122.46 | 802.50 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 49570.73 | 35167.84 | 14402.90 | 0.71 | 6912.11 | 70.11 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.12 | 14.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.755 | 0.678 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.788 | 0.705 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.888 | 0.784 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.888 | 0.784 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.888 | 0.784 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.888 | 0.784 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.781 | 0.699 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.781 | 0.699 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.781 | 0.699 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.781 | 0.699 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.781 | 0.699 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.881 | 0.778 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.881 | 0.778 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.881 | 0.778 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.881 | 0.778 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.881 | 0.778 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.881 | 0.778 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.881 | 0.778 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.881 | 0.778 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6294040921E-002 | 2.1121707803E-002 | Pass | Pass | 5.7127693905E-003 | 1.8127707055E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0759671541E-003 | 7.9689884018E-004 | Pass | Pass | 0.2085541875 | 0.4314672473 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.1782799099E-003 | 1.7016043463E-002 | Pass | Pass | 1.8425150068E-002 | 5.1156289931E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6529733285E-002 | 1.7272834344E-002 | Pass | Pass | 6.4971385426E-003 | 1.9334741994E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.4778232888E-004 | 5.0036468960E-004 | Pass | Pass | 0.2383140957 | 1.3159051452 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.9651954966E-005 | 1.0584531548E-004 | Pass | Pass | 2.1174620206E-002 | 6.1672116693E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6491948009E-003 | 2.0881791551E-002 | Pass | Pass | 2.7300720129E-002 | 8.6473676437E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1437280400E-002 | 3.9745835264E-002 | Pass | Pass | 1.3368320821E-002 | 3.6516521332E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0740767068E-002 | 0.2357788375 | Pass | Pass | 0.1123618627 | 0.3989723023 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0551966260E-002 | 0.2360912357 | Pass | Pass | 0.1138343774 | 0.3956448383 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.5661785383E-002 | 3.6674484102E-002 | Pass | Pass | 7.3185131954E-003 | 6.4348135499E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.7910869422E-002 | 8.6594844075E-002 | Pass | Pass | 0.4848649878 | 2.9081025022 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0411212504E-002 | 0.2343679137 | Pass | Pass | 0.1139508112 | 0.4072086619 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0164464801E-002 | 0.2346854063 | Pass | Pass | 0.1161067402 | 0.4047031761 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.8646636825E-004 | 2.9852894575E-004 | Pass | Pass | 7.6398081180E-002 | 0.2096807340 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2868637919E-002 | 0.2835844619 | Pass | Pass | 7.3903843255E-002 | 0.2184541183 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2935209912E-002 | 0.2831980144 | Pass | Pass | 7.1654435605E-002 | 0.2050029522 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.5903518875E-002 | 0.1983184347 | Pass | Pass | 8.2352214184E-002 | 0.2512886378 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.0289762896E-002 | 9.0953976085E-002 | Pass | Pass | 1.0415165656E-002 | 2.5236731505E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.1069180874E-002 | 9.5390165213E-002 | Pass | Pass | 9.6450894275E-003 | 2.1223303670E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.0348923014E-003 | 1.9761119509E-003 | Pass | Pass | 2.2970823755E-002 | 4.4358115487E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5866644283E-004 | 2.7523435422E-004 | Pass | Pass | 0.1111962292 | 0.3888427821 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3446.08 | 130.33 | 1720.83 | 5264.35 | 1759.49 | 12321.08 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.755 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.705 | 0.788 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.784 | 0.888 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.784 | 0.888 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.784 | 0.888 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.784 | 0.888 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.699 | 0.781 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.778 | 0.881 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.778 | 0.881 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.778 | 0.881 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.778 | 0.881 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.778 | 0.881 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.778 | 0.881 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.778 | 0.881 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.778 | 0.881 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.408 | 0.210 | 0.290 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.408 | 0.210 | 0.290 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.408 | 0.210 | 0.290 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.408 | 0.210 | 0.290 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.408 | 0.210 | 0.290 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.408 | 0.210 | 0.290 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.408 | 0.210 | 0.290 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.408 | 0.210 | 0.290 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.408 | 0.210 | 0.290 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.248_SHGC_0.21 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.408 | 0.210 | 0.290 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.408 | 0.210 | 0.290 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.408 | 0.210 | 0.290 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.408 | 0.210 | 0.290 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.248_SHGC_0.21 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.408 | 0.210 | 0.290 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
North Total or Average | 432.95 | 1.408 | 0.210 | 0.290 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.408 | 0.210 | 0.290 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8772 | 1978.83 | 11630.03 | LightsWired | LTG_SCH_BASEMENT | 40.17 | 168.00 | 40.12 | 0.0000 | Y | 87.60 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 7.1580 | 67.07 | 480.10 | LightsWired | LTG_SCH_RETAIL | 44.04 | 168.00 | 43.99 | 0.0000 | Y | 3.96 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 7.1580 | 77.67 | 555.95 | LightsWired | LTG_SCH_RETAIL | 44.04 | 168.00 | 43.99 | 0.0000 | Y | 4.59 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 6.8781 | 164.24 | 1129.69 | LightsWired | LTG_SCH_MECHANIC | 38.78 | 168.00 | 38.73 | 0.0000 | Y | 8.21 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.5805 | 94.76 | 339.29 | LightsWired | LTG_SCH_STORAGE | 29.59 | 168.00 | 29.56 | 0.0000 | Y | 1.88 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.9406 | 78.04 | 385.56 | LightsWired | LTG_SCH_LAUNDRY | 48.47 | 168.00 | 48.41 | 0.0000 | Y | 3.50 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 7.3625 | 188.86 | 1390.50 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 24.63 | 0.0000 | Y | 6.43 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 7.7500 | 1308.19 | 10138.45 | LightsWired | LTG_SCH_LOBBY | 41.54 | 168.00 | 39.34 | 0.0000 | Y | 74.86 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.78 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 58.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 4.92 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.2625 | 1557.62 | 6639.36 | LightsWired | LTG_SCH_CORRIDOR | 41.54 | 168.00 | 41.50 | 0.0000 | Y | 51.72 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 1.23 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 6.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 7.3625 | 331.66 | 2441.83 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 30.58 | 0.0000 | Y | 14.02 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 7.3625 | 331.66 | 2441.83 | LightsWired | LTG_SCH_DINING | 36.01 | 168.00 | 30.58 | 0.0000 | Y | 14.02 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.5281 | 103.30 | 1190.91 | LightsWired | LTG_SCH_KITCHEN | 38.78 | 168.00 | 38.73 | 0.0000 | Y | 8.66 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.2625 | 412.12 | 1756.68 | LightsWired | LTG_SCH_CORRIDOR | 41.54 | 168.00 | 41.50 | 0.0000 | Y | 13.68 |
Interior Lighting Total | 5.3808 | 11345.29 | 61047.14 | 264.05 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10138.45 | 709.69 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10138.45 | 709.69 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1390.50 | 542.29 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1390.50 | 542.29 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2441.83 | 488.37 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2441.83 | 488.37 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2441.83 | 488.37 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2441.83 | 488.37 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 9571.94 | AstronomicalClock | - | 83.55 | 83.55 | 150.11 | |
Exterior Lighting Total | 9571.94 | 150.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 338085.57 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 640818.97 | 3.11 | 640931.61 | 3.11 | 4.12 | 14.07 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9045.26 | 13401.74 | 11530.42 | 1871.32 | 0.86 | - | 2635.31 | 26.73 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 8301.60 | 12292.40 | 10565.50 | 1726.90 | 0.86 | - | 2413.88 | 24.48 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62837.02 | 93832.55 | 81577.44 | 12255.11 | 0.87 | - | 18909.22 | 191.79 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 52897.07 | 76932.36 | 64690.62 | 12241.74 | 0.84 | - | 14399.81 | 146.05 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 8129.37 | 12035.00 | 10341.67 | 1693.32 | 0.86 | - | 2361.92 | 23.96 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 7462.07 | 11037.70 | 9474.53 | 1563.17 | 0.86 | - | 2160.66 | 21.91 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2350.47 | 3483.65 | 2998.45 | 485.20 | 0.86 | - | 685.69 | 6.95 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2142.69 | 3173.14 | 2728.39 | 444.75 | 0.86 | - | 623.05 | 6.32 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13546.99 | 19994.98 | 17116.88 | 2878.11 | 0.86 | - | 3889.18 | 39.45 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 428086.12 | 497573.19 | 351114.97 | 146458.22 | 0.71 | - | 79122.46 | 802.50 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45447.84 | 49570.73 | 35167.84 | 14402.90 | 0.71 | - | 6912.11 | 70.11 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6674.17 | 10135.64 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2587.21 | 3929.58 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1423.63 | 2160.72 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1641.04 | 2490.80 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1329.31 | 2020.44 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2175.65 | 3302.23 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10142.21 | 15393.90 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26716.05 | 40552.16 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4109.40 | 6951.51 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4110.04 | 6952.59 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 23501.62 | 39755.19 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 23526.49 | 39797.25 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4111.24 | 6954.61 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4111.88 | 6955.69 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10272.31 | 15614.36 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1270.45 | 2148.99 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1270.79 | 2149.57 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 6115.24 | 10344.00 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13652.22 | 20726.38 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13754.06 | 20880.86 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 4370.35 | 6634.74 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5732.59 | 8700.99 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 150146.66 | 153927.43 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15340.96 | 15727.26 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.82 | 575.13 | 703.64 | 1.00 | 1.25 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.75 | 526.58 | 703.64 | 1.00 | 1.28 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.82 | 4097.29 | 703.64 | 1.00 | 0.96 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 4.51 | 3173.88 | 703.64 | 1.00 | 0.98 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.73 | 515.34 | 703.64 | 1.00 | 1.28 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.67 | 471.79 | 703.64 | 1.00 | 1.31 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.21 | 149.60 | 703.64 | 1.00 | 2.00 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.19 | 136.03 | 703.64 | 1.00 | 2.09 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.21 | 850.78 | 703.64 | 1.00 | 1.15 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.08 | 44984.99 | 2240.64 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.018311 | 2960.01 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.007396 | 2205.19 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.018311 | 2049.31 | 111917.77 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.95 | 0.68 | 0.60 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.95 | 0.31 | 0.04 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 28803.60 | 28803.60 | 14.56 | 2.123 | 2.123 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 24.00 | 24.00 | 0.00934 | 24.96 | 0.00881 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4422.06 | 4422.06 | 65.93 | 0.326 | 0.326 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00905 | 29.14 | 0.00882 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2707.57 | 2707.57 | 34.86 | 0.200 | 0.200 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00954 | 28.50 | 0.00882 | 0.092 | 0.00 |
MECH_FLR_1 | 2551.38 | 2551.38 | 15.53 | 0.188 | 0.188 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 24.00 | 24.00 | 0.00874 | 28.78 | 0.00882 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1175.57 | 1175.57 | 12.41 | 0.087 | 0.087 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00889 | 29.30 | 0.00882 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44543.81 | 44543.81 | 570.79 | 3.283 | 3.283 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00854 | 29.40 | 0.00882 | 0.000 | 0.00 |
CAFE_FLR_1 | 19646.16 | 19646.16 | 104.02 | 1.449 | 1.449 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.01012 | 29.14 | 0.00882 | 0.676 | 0.00 |
LOBBY_FLR_1 | 60857.69 | 60857.69 | 46.52 | 4.487 | 4.487 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.01006 | 29.23 | 0.00882 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 8229.42 | 8229.42 | 210.89 | 0.817 | 0.817 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 21.11 | 21.11 | 0.00860 | 28.22 | 0.00882 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7534.78 | 7534.78 | 193.11 | 0.748 | 0.748 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00861 | 27.94 | 0.00882 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 58630.25 | 58630.25 | 2390.74 | 5.823 | 5.823 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00851 | 29.23 | 0.00882 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 45412.96 | 45412.96 | 1851.28 | 4.511 | 4.511 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 21.11 | 21.11 | 0.00882 | 29.30 | 0.00882 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7373.92 | 7373.92 | 188.97 | 0.732 | 0.732 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00861 | 25.45 | 0.00882 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6750.75 | 6750.75 | 173.02 | 0.671 | 0.671 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00862 | 23.97 | 0.00881 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 14714.88 | 14714.88 | 37.79 | 1.085 | 1.085 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00979 | 29.40 | 0.00882 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2140.62 | 2140.62 | 54.86 | 0.213 | 0.213 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00859 | 28.36 | 0.00882 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1946.49 | 1946.49 | 49.89 | 0.193 | 0.193 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00860 | 27.94 | 0.00882 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12173.37 | 12173.37 | 496.25 | 1.209 | 1.209 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00864 | 29.23 | 0.00882 | 0.099 | 0.00 |
BANQUET_FLR_6 | 27483.11 | 27483.11 | 82.87 | 2.028 | 2.028 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01054 | 29.40 | 0.00882 | 1.188 | 0.00 |
DINING_FLR_6 | 28887.42 | 28887.42 | 87.10 | 2.132 | 2.132 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01044 | 29.40 | 0.00882 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29128.09 | 29128.09 | 281.96 | 2.153 | 2.153 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01015 | 28.46 | 0.00882 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8607.76 | 8607.76 | 20.89 | 0.634 | 0.634 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00908 | 29.40 | 0.00882 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.94 | 0.00269 | -4.20 | 0.00269 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 1968.69 | 1968.69 | 29.35 | 0.086 | 0.086 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00741 | -4.20 | 0.00269 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 708.73 | 708.73 | 9.13 | 0.031 | 0.092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00738 | -4.20 | 0.00269 | 0.092 | 0.00 |
MECH_FLR_1 | 1338.55 | 1338.55 | 8.15 | 0.058 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00724 | -4.20 | 0.00269 | 0.000 | 0.00 |
STORAGE_FLR_1 | 878.96 | 878.96 | 9.28 | 0.038 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00732 | -4.20 | 0.00269 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1774.66 | 1774.66 | 22.74 | 0.077 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00722 | -4.20 | 0.00269 | 0.000 | 0.00 |
CAFE_FLR_1 | 4867.23 | 4867.23 | 25.77 | 0.212 | 0.676 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.676 | 0.00 |
LOBBY_FLR_1 | 11948.83 | 11948.83 | 9.13 | 0.520 | 1.894 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00739 | -4.20 | 0.00269 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4109.50 | 4109.50 | 105.31 | 0.180 | 0.180 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00736 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4110.14 | 4110.14 | 105.34 | 0.180 | 0.180 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00736 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 23501.89 | 23501.89 | 958.33 | 1.028 | 1.028 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00740 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 23526.76 | 23526.76 | 959.08 | 1.029 | 1.029 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00740 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4111.33 | 4111.33 | 105.36 | 0.180 | 0.180 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00736 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4111.97 | 4111.97 | 105.39 | 0.180 | 0.180 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00736 | -4.20 | 0.00269 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 6567.06 | 6567.06 | 16.86 | 0.286 | 0.475 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00750 | -4.20 | 0.00269 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1270.48 | 1270.48 | 32.56 | 0.056 | 0.056 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00747 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1270.82 | 1270.82 | 32.57 | 0.056 | 0.056 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00747 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 6115.35 | 6115.35 | 249.30 | 0.267 | 0.267 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4390.82 | 4390.82 | 13.24 | 0.191 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00761 | -4.20 | 0.00269 | 1.188 | 0.00 |
DINING_FLR_6 | 4485.23 | 4485.23 | 13.52 | 0.195 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00762 | -4.20 | 0.00269 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1515.24 | 1515.24 | 14.67 | 0.066 | 0.367 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00596 | -4.20 | 0.00269 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 4675.21 | 4675.21 | 11.34 | 0.203 | 0.203 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00768 | -4.20 | 0.00269 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.08 | 20.08 | 7.22 | 7.22 | 20.0769 | 10.5304 | 20.0769 | 0.5245 | 0.3000 |
FLR_3_DOAS | 14.22 | 2.05 | 3.15 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6674.172 | 6674.172 | 1.282343 | 0.00014600 | 192.705 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6674.17 | 6674.17 | 1.282343 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 6704.06 | 6704.06 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2587.206 | 2587.206 | 0.118981 | 0.00005660 | 95.875 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2587.21 | 2587.21 | 0.118981 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00741300 | 47.2847 | 1968.69 | 0.00 | 2600.26 | 2600.26 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1423.630 | 1423.630 | 0.137520 | 0.00003114 | 44.803 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1423.63 | 1423.63 | 0.137520 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00737534 | 47.0463 | 708.73 | 0.00 | 1429.65 | 1429.65 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1641.045 | 1641.045 | 0.058203 | 0.00003590 | 67.995 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1641.04 | 1641.04 | 0.058203 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00724068 | 46.1972 | 1338.55 | 0.00 | 1648.89 | 1648.89 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1329.315 | 1329.315 | 0.086641 | 0.00002908 | 45.210 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1329.31 | 1329.31 | 0.086641 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00732115 | 46.7046 | 878.96 | 0.00 | 1336.43 | 1336.43 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 2175.648 | 2175.648 | 0.077164 | 0.00004759 | 90.147 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2175.65 | 2175.65 | 0.077164 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00722165 | 46.0782 | 1774.66 | 0.00 | 2186.05 | 2186.05 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10142.205 | 10142.205 | 1.014595 | 0.00022186 | 317.190 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10142.21 | 10142.21 | 1.014595 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746893 | 47.6369 | 4867.23 | 0.00 | 10185.18 | 10185.18 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26716.051 | 26716.051 | 2.840580 | 0.00058441 | 826.956 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 26716.05 | 26716.05 | 2.840580 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00739164 | 47.1490 | 11948.83 | 0.00 | 26829.78 | 26829.78 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9045.263 | -999.000 | 0.817367 | 0.00025869 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | 8/21 16:40:00 | 9045.26 | 8836.82 | 0.817367 | 21.69 | 15.50 | 0.00859767 | 12.80 | 11.97 | 0.00850000 | 28.22 | 0.00881961 | 17.95 | 0.0000 | 21.11 | 0.00859767 | 54.3657 | 8229.42 | 0.00 | 9177.91 | 9177.91 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4109.401 | 4109.401 | 0.179734 | 0.00008989 | 185.598 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4109.40 | 4109.40 | 0.179734 | 21.11 | 14.16 | 0.00735843 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00735843 | 46.6220 | 4109.50 | 0.00 | 4599.21 | 4599.21 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 8301.596 | -999.000 | 0.748374 | 0.00023742 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 8301.60 | 8093.50 | 0.748374 | 21.69 | 15.51 | 0.00860646 | 12.80 | 11.97 | 0.00850000 | 27.94 | 0.00881916 | 17.86 | 0.0000 | 21.11 | 0.00860646 | 54.4206 | 7534.78 | 0.00 | 8424.52 | 8424.52 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4110.039 | 4110.039 | 0.179762 | 0.00008991 | 185.627 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4110.04 | 4110.04 | 0.179762 | 21.11 | 14.16 | 0.00735856 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00735856 | 46.6228 | 4110.14 | 0.00 | 4599.92 | 4599.92 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 62837.022 | -999.000 | 5.823029 | 0.00179710 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 62837.02 | 62742.54 | 5.823029 | 21.69 | 15.42 | 0.00850624 | 12.80 | 11.97 | 0.00850000 | 29.23 | 0.00882122 | 18.29 | 0.0000 | 21.11 | 0.00850624 | 53.7940 | 58630.25 | 0.00 | 63770.14 | 63770.14 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 23501.623 | 23501.623 | 1.027915 | 0.00051410 | 1061.404 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23501.62 | 23501.62 | 1.027915 | 21.11 | 14.20 | 0.00739998 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00739998 | 46.8811 | 23501.89 | 0.00 | 26303.06 | 26303.06 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 52897.071 | -999.000 | 4.510679 | 0.00151282 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | unknown | 8/21 15:10:00 | 52897.07 | 49136.16 | 4.510679 | 21.69 | 15.69 | 0.00881692 | 12.80 | 11.97 | 0.00850000 | 29.30 | 0.00882133 | 18.31 | 0.0000 | 21.11 | 0.00881692 | 55.7336 | 45412.96 | 0.00 | 53660.62 | 51747.91 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 23526.489 | 23526.489 | 1.029002 | 0.00051464 | 1062.527 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23526.49 | 23526.49 | 1.029002 | 21.11 | 14.20 | 0.00740039 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00740039 | 46.8837 | 23526.76 | 0.00 | 26330.89 | 26330.89 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 8129.366 | -999.000 | 0.732397 | 0.00023249 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 8129.37 | 7921.37 | 0.732397 | 21.69 | 15.51 | 0.00860873 | 12.80 | 11.97 | 0.00850000 | 25.45 | 0.00881519 | 17.01 | 0.0000 | 21.11 | 0.00860873 | 54.4347 | 7373.92 | 0.00 | 8249.66 | 8249.66 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4111.237 | 4111.237 | 0.179814 | 0.00008993 | 185.681 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4111.24 | 4111.24 | 0.179814 | 21.11 | 14.16 | 0.00735869 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00735869 | 46.6236 | 4111.33 | 0.00 | 4601.26 | 4601.26 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7462.072 | -999.000 | 0.670503 | 0.00021341 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 7462.07 | 7254.50 | 0.670503 | 21.69 | 15.52 | 0.00861848 | 12.80 | 11.97 | 0.00850000 | 23.97 | 0.00881286 | 16.50 | 0.0000 | 21.11 | 0.00861848 | 54.4955 | 6750.75 | 0.00 | 7572.22 | 7572.22 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4111.876 | 4111.876 | 0.179842 | 0.00008995 | 185.710 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4111.88 | 4111.88 | 0.179842 | 21.11 | 14.16 | 0.00735882 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00735882 | 46.6244 | 4111.97 | 0.00 | 4601.98 | 4601.98 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 10272.314 | 10272.314 | 0.712579 | 0.00022471 | 345.697 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10272.31 | 10272.31 | 0.712579 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00749678 | 47.8114 | 6567.06 | 0.00 | 10327.61 | 10327.61 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2350.468 | -999.000 | 0.212612 | 0.00006722 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 2350.47 | 2298.30 | 0.212612 | 21.69 | 15.50 | 0.00859398 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00859398 | 54.3427 | 2140.62 | 0.00 | 2384.97 | 2384.97 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1270.450 | 1270.450 | 0.055566 | 0.00002779 | 57.374 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1270.45 | 1270.45 | 0.055566 | 21.11 | 14.27 | 0.00746883 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00746883 | 47.3132 | 1270.48 | 0.00 | 1421.88 | 1421.88 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2142.688 | -999.000 | 0.193331 | 0.00006128 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 2142.69 | 2090.58 | 0.193331 | 21.69 | 15.50 | 0.00860320 | 12.80 | 11.97 | 0.00850000 | 27.94 | 0.00881916 | 17.86 | 0.0000 | 21.11 | 0.00860320 | 54.4002 | 1946.49 | 0.00 | 2174.07 | 2174.07 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1270.791 | 1270.791 | 0.055581 | 0.00002780 | 57.389 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1270.79 | 1270.79 | 0.055581 | 21.11 | 14.27 | 0.00746899 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00746899 | 47.3142 | 1270.82 | 0.00 | 1422.26 | 1422.26 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13546.988 | -999.000 | 1.209121 | 0.00038743 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 13546.99 | 13093.50 | 1.209121 | 21.69 | 15.54 | 0.00864341 | 12.80 | 11.97 | 0.00850000 | 29.23 | 0.00882122 | 18.29 | 0.0000 | 21.11 | 0.00864341 | 54.6516 | 12173.37 | 0.00 | 13745.69 | 13745.69 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 6115.241 | 6115.241 | 0.267465 | 0.00013377 | 276.161 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6115.24 | 6115.24 | 0.267465 | 21.11 | 14.29 | 0.00748964 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748964 | 47.4431 | 6115.35 | 0.00 | 6844.15 | 6844.15 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13652.224 | 13652.224 | 1.780793 | 0.00029864 | 410.275 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13652.22 | 13652.22 | 1.780793 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00761125 | 48.5330 | 4390.82 | 0.00 | 13711.27 | 13711.27 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13754.056 | 13754.056 | 1.782218 | 0.00030087 | 413.687 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 13754.06 | 13754.06 | 1.782218 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00761883 | 48.5809 | 4485.23 | 0.00 | 13813.51 | 13813.51 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 4370.349 | 4370.349 | 0.551055 | 0.00009560 | 131.920 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 4370.35 | 4370.35 | 0.551055 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00596185 | 38.1231 | 1515.24 | 0.00 | 4389.20 | 4389.20 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 5732.588 | 5732.588 | 0.203289 | 0.00012540 | 237.545 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 5732.59 | 5732.59 | 0.203289 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00767589 | 48.9400 | 4675.21 | 0.00 | 5760.01 | 5760.01 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 428086.124 | -999.000 | 20.076862 | 0.01224321 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 428086.12 | 376978.59 | 20.076862 | 26.50 | 17.79 | 0.00932048 | 10.95 | 10.95 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 46.4674 | 23.99 | 0.00975891 | 51.7050 | 272182.38 | 0.00 | 432760.94 | 368639.04 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 150146.659 | 150146.659 | 6.023059 | 0.00328446 | 3251.041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 150146.66 | 150146.66 | 6.023059 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 154.8914 | 21.22 | 0.00638915 | 40.2767 | 44587.37 | 0.00 | 134032.96 | 134032.96 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45447.837 | -999.000 | 2.051317 | 0.00129980 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 45447.84 | 43504.21 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 11.92 | 11.61 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 99.9965 | 21.11 | 0.00864290 | 54.6475 | 143123.46 | 0.00 | 45917.97 | 43441.59 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15340.965 | 15340.965 | 0.615395 | 0.00033558 | 332.169 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15340.96 | 15340.96 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 333.3216 | 21.11 | 0.00740082 | 46.8864 | 72128.25 | 0.00 | 13694.58 | 13694.58 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6674.172 | 6674.172 | 1.282343 | 0.00014600 | 192.705 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 1.9352 | 1.974107 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6674.17 | 6674.17 | 1.0000 | 1.52212934 | 1.282343 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.14598280 | 60.00 | 48.89 | 11.11 | 0.000 | 6674.17 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 6704.06 | 6704.06 | 1.52212934 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41339.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2587.206 | 2587.206 | 0.118981 | 0.00005660 | 95.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 0.7502 | 0.765252 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2587.21 | 2587.21 | 1.0000 | 0.14122922 | 0.118981 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05658942 | 60.00 | 48.89 | 11.11 | 0.000 | 2587.21 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00741300 | 21.00 | 0.00741300 | 47.2847 | 1968.69 | 0.00 | 2600.26 | 2600.26 | 0.14122922 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.66 | 19.55 | 0.00800000 | 55346.4 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1423.630 | 1423.630 | 0.137520 | 0.00003114 | 44.803 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 0.4128 | 0.421086 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1423.63 | 1423.63 | 1.0000 | 0.16323546 | 0.137520 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.03113877 | 60.00 | 48.89 | 11.11 | 0.000 | 1423.63 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00737534 | 21.00 | 0.00737534 | 47.0463 | 708.73 | 0.00 | 1429.65 | 1429.65 | 0.16323546 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.19 | 16.38 | 0.00800000 | 45692.9 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1641.045 | 1641.045 | 0.058203 | 0.00003590 | 67.995 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 0.4758 | 0.485393 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1641.04 | 1641.04 | 1.0000 | 0.06908673 | 0.058203 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.03589423 | 60.00 | 48.89 | 11.11 | 0.000 | 1641.04 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00724068 | 21.00 | 0.00724068 | 46.1972 | 1338.55 | 0.00 | 1648.89 | 1648.89 | 0.06908673 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60801.7 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1329.315 | 1329.315 | 0.086641 | 0.00002908 | 45.210 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 0.3854 | 0.393189 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1329.31 | 1329.31 | 1.0000 | 0.10284252 | 0.086641 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.02907583 | 60.00 | 48.89 | 11.11 | 0.000 | 1329.31 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00732115 | 21.00 | 0.00732115 | 46.7046 | 878.96 | 0.00 | 1336.43 | 1336.43 | 0.10284252 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.34 | 17.82 | 0.00800000 | 49929.7 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2175.648 | 2175.648 | 0.077164 | 0.00004759 | 90.147 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 0.6308 | 0.643520 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2175.65 | 2175.65 | 1.0000 | 0.09159277 | 0.077164 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04758751 | 60.00 | 48.89 | 11.11 | 0.000 | 2175.65 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00722165 | 21.00 | 0.00722165 | 46.0782 | 1774.66 | 0.00 | 2186.05 | 2186.05 | 0.09159277 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60801.8 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10142.205 | 10142.205 | 1.014595 | 0.00022186 | 317.190 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 2.9407 | 2.999893 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10142.21 | 10142.21 | 1.0000 | 1.20431437 | 1.014595 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.22183838 | 60.00 | 48.89 | 11.11 | 0.000 | 10142.21 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00746893 | 21.00 | 0.00746893 | 47.6369 | 4867.23 | 0.00 | 10185.18 | 10185.18 | 1.20431437 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.89 | 16.28 | 0.00800000 | 45392.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26716.051 | 26716.051 | 2.840580 | 0.00058441 | 826.956 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 7.7463 | 7.902156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 26716.05 | 26716.05 | 1.0000 | 3.37174241 | 2.840580 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.58435473 | 60.00 | 48.89 | 11.11 | 0.000 | 26716.05 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00739164 | 21.00 | 0.00739164 | 47.1490 | 11948.83 | 0.00 | 26829.78 | 26829.78 | 3.37174241 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.40 | 16.10 | 0.00800000 | 44892.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9045.263 | -999.000 | 0.817367 | 0.00025869 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8226 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.817367 | 0.97020748 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 1.4128 | 1.412759 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | unknown | unknown | 8/21 16:40:00 | Sensible | 9045.26 | 8836.82 | 1.0000 | 0.97020748 | 0.817367 | 21.69 | 15.50 | 0.00859767 | 43645.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.25866215 | 6.70 | 15.03 | 8.33 | 0.000 | 9045.26 | 28.22 | 0.00881961 | 17.95 | 0.00000000 | 0.0000 | 21.11 | 0.00859767 | 21.11 | 0.00859767 | 54.3657 | 8229.42 | 0.00 | 9177.91 | 9177.91 | 0.97020748 | 21.69 | 15.64 | 0.00859767 | 43645.2 | 12.42 | 12.04 | 0.00859767 | 34185.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4109.401 | 4109.401 | 0.179734 | 0.00008989 | 185.598 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.817367 | 0.97020748 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 1.1915 | 1.215491 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4109.40 | 4109.40 | 1.0000 | 0.21334218 | 0.179734 | 21.11 | 14.16 | 0.00735843 | 39904.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08988408 | 60.00 | 48.89 | 11.11 | 0.000 | 4109.40 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00735843 | 21.11 | 0.00735843 | 46.6220 | 4109.50 | 0.00 | 4599.21 | 4599.21 | 0.21334218 | 16.60 | 12.52 | 0.00735843 | 35310.4 | 37.77 | 20.03 | 0.00735843 | 56868.3 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8301.596 | -999.000 | 0.748374 | 0.00023742 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8390 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.748374 | 0.88831327 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 1.2966 | 1.296607 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 8301.60 | 8093.50 | 1.0000 | 0.88831327 | 0.748374 | 21.69 | 15.51 | 0.00860646 | 43667.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.23739593 | 6.70 | 15.03 | 8.33 | 0.000 | 8301.60 | 27.94 | 0.00881916 | 17.86 | 0.00000000 | 0.0000 | 21.11 | 0.00860646 | 21.11 | 0.00860646 | 54.4206 | 7534.78 | 0.00 | 8424.52 | 8424.52 | 0.88831327 | 21.69 | 15.65 | 0.00860646 | 43667.5 | 12.40 | 12.04 | 0.00860646 | 34183.8 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4110.039 | 4110.039 | 0.179762 | 0.00008991 | 185.627 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.748374 | 0.88831327 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 1.1917 | 1.215680 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4110.04 | 4110.04 | 1.0000 | 0.21337535 | 0.179762 | 21.11 | 14.16 | 0.00735856 | 39904.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08989806 | 60.00 | 48.89 | 11.11 | 0.000 | 4110.04 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00735856 | 21.11 | 0.00735856 | 46.6228 | 4110.14 | 0.00 | 4599.92 | 4599.92 | 0.21337535 | 16.60 | 12.52 | 0.00735856 | 35310.7 | 37.77 | 20.03 | 0.00735856 | 56868.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62837.022 | -999.000 | 5.823029 | 0.00179710 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6527 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.823029 | 6.91188149 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 9.8146 | 9.814369 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 62837.02 | 62742.54 | 1.0000 | 6.91188149 | 5.823029 | 21.69 | 15.42 | 0.00850624 | 43413.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 1.79691398 | 6.70 | 15.03 | 8.33 | 0.000 | 62837.02 | 29.23 | 0.00882122 | 18.29 | 0.00000000 | 0.0000 | 21.11 | 0.00850624 | 21.11 | 0.00850624 | 53.7940 | 58630.25 | 0.00 | 63770.14 | 63770.14 | 6.91188149 | 21.69 | 15.56 | 0.00850624 | 43413.4 | 12.65 | 12.05 | 0.00850624 | 34187.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23501.623 | 23501.623 | 1.027915 | 0.00051410 | 1061.404 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.823029 | 6.91188149 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 6.8142 | 6.951383 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23501.62 | 23501.62 | 1.0000 | 1.22012527 | 1.027915 | 21.11 | 14.20 | 0.00739998 | 40010.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.51404621 | 60.00 | 48.89 | 11.11 | 0.000 | 23501.62 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00739998 | 21.11 | 0.00739998 | 46.8811 | 23501.89 | 0.00 | 26303.06 | 26303.06 | 1.22012527 | 16.60 | 12.56 | 0.00739998 | 35415.6 | 37.76 | 20.06 | 0.00739998 | 56973.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 52897.071 | -999.000 | 4.510679 | 0.00151282 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2302 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.510679 | 5.35413397 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 8.2620 | 8.261871 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | unknown | unknown | unknown | 8/21 15:10:00 | Sensible | 52897.07 | 49136.16 | 1.0000 | 5.35413397 | 4.510679 | 21.69 | 15.69 | 0.00881692 | 44201.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 1.51266696 | 6.70 | 15.03 | 8.33 | 0.000 | 52897.07 | 29.30 | 0.00882133 | 18.31 | 0.00000000 | 0.0000 | 21.11 | 0.00881692 | 21.11 | 0.00881692 | 55.7336 | 45412.96 | 0.00 | 53660.62 | 51747.91 | 5.35413397 | 21.69 | 15.84 | 0.00881692 | 44201.9 | 12.23 | 12.04 | 0.00867536 | 34179.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23526.489 | 23526.489 | 1.029002 | 0.00051464 | 1062.527 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.510679 | 5.35413397 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 6.8215 | 6.958738 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23526.49 | 23526.49 | 1.0000 | 1.22141624 | 1.029002 | 21.11 | 14.20 | 0.00740039 | 40011.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.51459010 | 60.00 | 48.89 | 11.11 | 0.000 | 23526.49 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00740039 | 21.11 | 0.00740039 | 46.8837 | 23526.76 | 0.00 | 26330.89 | 26330.89 | 1.22141624 | 16.60 | 12.56 | 0.00740039 | 35416.7 | 37.76 | 20.06 | 0.00740039 | 56974.3 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8129.366 | -999.000 | 0.732397 | 0.00023249 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8432 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.732397 | 0.86934901 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 1.2697 | 1.269707 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 8129.37 | 7921.37 | 1.0000 | 0.86934901 | 0.732397 | 21.69 | 15.51 | 0.00860873 | 43673.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.23247077 | 6.70 | 15.03 | 8.33 | 0.000 | 8129.37 | 25.45 | 0.00881519 | 17.01 | 0.00000000 | 0.0000 | 21.11 | 0.00860873 | 21.11 | 0.00860873 | 54.4347 | 7373.92 | 0.00 | 8249.66 | 8249.66 | 0.86934901 | 21.69 | 15.65 | 0.00860873 | 43673.3 | 12.40 | 12.04 | 0.00860873 | 34183.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4111.237 | 4111.237 | 0.179814 | 0.00008993 | 185.681 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.732397 | 0.86934901 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 1.1920 | 1.216035 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4111.24 | 4111.24 | 1.0000 | 0.21343754 | 0.179814 | 21.11 | 14.16 | 0.00735869 | 39904.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08992426 | 60.00 | 48.89 | 11.11 | 0.000 | 4111.24 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00735869 | 21.11 | 0.00735869 | 46.6236 | 4111.33 | 0.00 | 4601.26 | 4601.26 | 0.21343754 | 16.60 | 12.52 | 0.00735869 | 35311.1 | 37.77 | 20.03 | 0.00735869 | 56868.9 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7462.072 | -999.000 | 0.670503 | 0.00021341 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8613 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.670503 | 0.79588062 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 1.1655 | 1.165484 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | Sensible | 7462.07 | 7254.50 | 1.0000 | 0.79588062 | 0.670503 | 21.69 | 15.52 | 0.00861848 | 43698.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.21338856 | 6.70 | 15.03 | 8.33 | 0.000 | 7462.07 | 23.97 | 0.00881286 | 16.50 | 0.00000000 | 0.0000 | 21.11 | 0.00861848 | 21.11 | 0.00861848 | 54.4955 | 6750.75 | 0.00 | 7572.22 | 7572.22 | 0.79588062 | 21.69 | 15.66 | 0.00861848 | 43698.1 | 12.37 | 12.04 | 0.00861848 | 34183.8 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4111.876 | 4111.876 | 0.179842 | 0.00008995 | 185.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.670503 | 0.79588062 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 1.1922 | 1.216224 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4111.88 | 4111.88 | 1.0000 | 0.21347071 | 0.179842 | 21.11 | 14.16 | 0.00735882 | 39905.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08993823 | 60.00 | 48.89 | 11.11 | 0.000 | 4111.88 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00735882 | 21.11 | 0.00735882 | 46.6244 | 4111.97 | 0.00 | 4601.98 | 4601.98 | 0.21347071 | 16.60 | 12.52 | 0.00735882 | 35311.4 | 37.77 | 20.03 | 0.00735882 | 56869.3 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10272.314 | 10272.314 | 0.712579 | 0.00022471 | 345.697 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 2.9784 | 3.038377 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10272.31 | 10272.31 | 1.0000 | 0.84582417 | 0.712579 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.22468423 | 60.00 | 48.89 | 11.11 | 0.000 | 10272.31 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00749678 | 21.00 | 0.00749678 | 47.8114 | 6567.06 | 0.00 | 10327.61 | 10327.61 | 0.84582417 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.57 | 17.56 | 0.00800000 | 49144.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2350.468 | -999.000 | 0.212612 | 0.00006722 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8158 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.212612 | 0.25236830 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 0.3671 | 0.367114 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 2350.47 | 2298.30 | 1.0000 | 0.25236830 | 0.212612 | 21.69 | 15.50 | 0.00859398 | 43635.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.06721497 | 6.70 | 15.03 | 8.33 | 0.000 | 2350.47 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00859398 | 21.11 | 0.00859398 | 54.3427 | 2140.62 | 0.00 | 2384.97 | 2384.97 | 0.25236830 | 21.69 | 15.64 | 0.00859398 | 43635.8 | 12.43 | 12.04 | 0.00859398 | 34185.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1270.450 | 1270.450 | 0.055566 | 0.00002779 | 57.374 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.212612 | 0.25236830 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 0.3684 | 0.375778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1270.45 | 1270.45 | 1.0000 | 0.06595619 | 0.055566 | 21.11 | 14.27 | 0.00746883 | 40184.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.02778828 | 60.00 | 48.89 | 11.11 | 0.000 | 1270.45 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746883 | 21.11 | 0.00746883 | 47.3132 | 1270.48 | 0.00 | 1421.88 | 1421.88 | 0.06595619 | 16.60 | 12.63 | 0.00746883 | 35589.9 | 37.76 | 20.11 | 0.00746883 | 57147.8 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2142.688 | -999.000 | 0.193331 | 0.00006128 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8329 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.193331 | 0.22948187 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 0.3347 | 0.334662 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 2142.69 | 2090.58 | 1.0000 | 0.22948187 | 0.193331 | 21.69 | 15.50 | 0.00860320 | 43659.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.06127322 | 6.70 | 15.03 | 8.33 | 0.000 | 2142.69 | 27.94 | 0.00881916 | 17.86 | 0.00000000 | 0.0000 | 21.11 | 0.00860320 | 21.11 | 0.00860320 | 54.4002 | 1946.49 | 0.00 | 2174.07 | 2174.07 | 0.22948187 | 21.69 | 15.65 | 0.00860320 | 43659.3 | 12.41 | 12.04 | 0.00860320 | 34185.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1270.791 | 1270.791 | 0.055581 | 0.00002780 | 57.389 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.193331 | 0.22948187 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 0.3685 | 0.375879 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1270.79 | 1270.79 | 1.0000 | 0.06597392 | 0.055581 | 21.11 | 14.27 | 0.00746899 | 40185.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.02779575 | 60.00 | 48.89 | 11.11 | 0.000 | 1270.79 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746899 | 21.11 | 0.00746899 | 47.3142 | 1270.82 | 0.00 | 1422.26 | 1422.26 | 0.06597392 | 16.60 | 12.63 | 0.00746899 | 35590.3 | 37.76 | 20.11 | 0.00746899 | 57148.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13546.988 | -999.000 | 1.209121 | 0.00038743 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9077 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.209121 | 1.43521497 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 2.1159 | 2.115873 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 13546.99 | 13093.50 | 1.0000 | 1.43521497 | 1.209121 | 21.69 | 15.54 | 0.00864341 | 43761.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.38739538 | 6.70 | 15.03 | 8.33 | 0.000 | 13546.99 | 29.23 | 0.00882122 | 18.29 | 0.00000000 | 0.0000 | 21.11 | 0.00864341 | 21.11 | 0.00864341 | 54.6516 | 12173.37 | 0.00 | 13745.69 | 13745.69 | 1.43521497 | 21.69 | 15.68 | 0.00864341 | 43761.2 | 12.31 | 12.04 | 0.00864341 | 34183.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6115.241 | 6115.241 | 0.267465 | 0.00013377 | 276.161 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.209121 | 1.43521497 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 1.7731 | 1.808785 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6115.24 | 6115.24 | 1.0000 | 0.31747872 | 0.267465 | 21.11 | 14.29 | 0.00748964 | 40237.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.13375742 | 60.00 | 48.89 | 11.11 | 0.000 | 6115.24 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748964 | 21.11 | 0.00748964 | 47.4431 | 6115.35 | 0.00 | 6844.15 | 6844.15 | 0.31747872 | 16.60 | 12.65 | 0.00748964 | 35642.6 | 37.76 | 20.13 | 0.00748964 | 57200.4 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13652.224 | 13652.224 | 1.780793 | 0.00029864 | 410.275 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 3.9584 | 4.038097 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13652.22 | 13652.22 | 1.0000 | 2.11378533 | 1.780793 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.29861232 | 60.00 | 48.89 | 11.11 | 0.000 | 13652.22 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00761125 | 21.00 | 0.00761125 | 48.5330 | 4390.82 | 0.00 | 13711.27 | 13711.27 | 2.11378533 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.96 | 15.58 | 0.00800000 | 43421.3 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13754.056 | 13754.056 | 1.782218 | 0.00030087 | 413.687 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 3.9880 | 4.068217 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 13754.06 | 13754.06 | 1.0000 | 2.11547609 | 1.782218 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.30083967 | 60.00 | 48.89 | 11.11 | 0.000 | 13754.06 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00761883 | 21.00 | 0.00761883 | 48.5809 | 4485.23 | 0.00 | 13813.51 | 13813.51 | 2.11547609 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.00 | 15.59 | 0.00800000 | 43464.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4370.349 | 4370.349 | 0.551055 | 0.00009560 | 131.920 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 1.2672 | 1.292675 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 4370.35 | 4370.35 | 1.0000 | 0.65409702 | 0.551055 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09559175 | 60.00 | 48.89 | 11.11 | 0.000 | 4370.35 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.32 | 0.00596185 | 21.00 | 0.00596185 | 38.1231 | 1515.24 | 0.00 | 4389.20 | 4389.20 | 0.65409702 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.18 | 15.66 | 0.00800000 | 43645.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5732.588 | 5732.588 | 0.203289 | 0.00012540 | 237.545 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 1.6622 | 1.695603 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 5732.59 | 5732.59 | 1.0000 | 0.24130267 | 0.203289 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12538773 | 60.00 | 48.89 | 11.11 | 0.000 | 5732.59 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00767589 | 21.00 | 0.00767589 | 48.9400 | 4675.21 | 0.00 | 5760.01 | 5760.01 | 0.24130267 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.18 | 0.00800000 | 60805.2 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 428086.124 | -999.000 | 20.076862 | 0.01224321 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1663 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.076862 | 23.83105020 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 66.8630 | 66.863030 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 428086.12 | 376978.59 | 1.0000 | 23.83105020 | 20.076862 | 26.50 | 17.79 | 0.00932048 | 50400.7 | 10.95 | 10.95 | 0.00850000 | 32437.3 | 12.24196001 | 6.70 | 15.03 | 8.33 | 44984.992 | 383101.13 | 29.40 | 0.00882150 | 18.34 | 9.32920000 | 46.4674 | 23.99 | 0.00975366 | 23.99 | 0.00975891 | 51.7050 | 272182.38 | 0.00 | 432760.94 | 368639.04 | 23.83105020 | 26.50 | 17.94 | 0.00932048 | 50400.7 | 11.37 | 11.25 | 0.00825363 | 32241.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 150146.659 | 150146.659 | 6.023059 | 0.00328446 | 3251.041 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.076862 | 23.83105020 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 43.5347 | 44.410845 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 150146.66 | 150146.66 | 1.0000 | 7.14931506 | 6.023059 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 3.28412728 | 60.00 | 48.89 | 11.11 | 0.000 | 150146.66 | -4.20 | 0.00269032 | -4.20 | 9.32920000 | 154.8914 | 18.40 | 0.00685177 | 21.22 | 0.00638915 | 40.2767 | 44587.37 | 0.00 | 134032.96 | 134032.96 | 7.14931506 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.36 | 9.67 | 0.00269032 | 28303.5 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45447.837 | -999.000 | 2.051317 | 0.00129980 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2387 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 18.30901172 | 15.03 | 6.70 | 8.33 | 640243.38 | 7.0985 | 7.098525 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 45447.84 | 43504.21 | 1.0000 | 2.43489466 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 52086.5 | 11.92 | 11.61 | 0.00850000 | 33421.2 | 1.29966980 | 6.70 | 15.03 | 8.33 | 2195.006 | 43252.83 | 29.40 | 0.00882150 | 18.34 | 2.05124512 | 99.9965 | 21.11 | 0.00864042 | 21.11 | 0.00864290 | 54.6475 | 143123.46 | 0.00 | 45917.97 | 43441.59 | 2.43489466 | 29.40 | 18.50 | 0.00882150 | 52086.5 | 11.93 | 11.66 | 0.00841841 | 33228.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15340.965 | 15340.965 | 0.615395 | 0.00033558 | 332.169 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 7.39487684 | 48.89 | 60.00 | 11.11 | 344889.68 | 4.4481 | 4.537598 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15340.96 | 15340.96 | 1.0000 | 0.73046840 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 0.33554979 | 60.00 | 48.89 | 11.11 | 0.000 | 15340.96 | -4.20 | 0.00269032 | -4.20 | 2.05124512 | 333.3216 | 21.11 | 0.00740072 | 21.11 | 0.00740082 | 46.8864 | 72128.25 | 0.00 | 13694.58 | 13694.58 | 0.73046840 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.36 | 9.67 | 0.00269032 | 28303.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 20.08 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 1203.50 | 7847.00 | 671.17 |
RETAIL_2_FLR_1 | 20.67 | 8636.67 | 5.83 |
MECH_FLR_1 | 16.50 | 6898.00 | 0.00 |
STORAGE_FLR_1 | 238.33 | 8760.00 | 238.33 |
LAUNDRY_FLR_1 | 8760.00 | 3259.50 | 3259.50 |
CAFE_FLR_1 | 111.83 | 8496.33 | 22.50 |
LOBBY_FLR_1 | 163.67 | 8260.00 | 22.33 |
ROOM_1_FLR_3 | 1390.83 | 8681.33 | 1390.83 |
ROOM_2_FLR_3 | 1954.67 | 8531.00 | 1849.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 335.67 | 8759.83 | 335.67 |
ROOM_5_FLR_3 | 1378.50 | 8746.00 | 1378.50 |
ROOM_6_FLR_3 | 1838.17 | 8700.00 | 1808.67 |
CORRIDOR_FLR_3 | 105.33 | 8760.00 | 105.33 |
ROOM_1_FLR_6 | 2188.33 | 8576.00 | 2187.67 |
ROOM_2_FLR_6 | 2808.83 | 8356.67 | 2629.17 |
ROOM_3_MULT9_FLR_6 | 823.50 | 8591.17 | 823.50 |
BANQUET_FLR_6 | 489.33 | 7476.50 | 17.83 |
DINING_FLR_6 | 1088.67 | 6322.50 | 18.17 |
KITCHEN_FLR_6 | 8760.00 | 6300.67 | 6300.67 |
CORRIDOR_FLR_6 | 589.33 | 7179.67 | 72.50 |
Facility | 8760.00 | 8760.00 | 7199.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 2.50 | 0.00 | 2.50 |
ROOM_2_FLR_3 | 0.00 | 3.00 | 0.00 | 3.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 17.83 | 0.00 | 17.83 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 6.00 | 0.00 | 6.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 8.33 | 0.00 | 8.33 |
ROOM_2_FLR_6 | 0.00 | 10.83 | 0.00 | 10.83 |
ROOM_3_MULT9_FLR_6 | 0.00 | 2.17 | 0.00 | 2.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 30.17 | 0.00 | 30.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.739 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.258 | 0.138 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.240 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.049 | 0.052 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.638 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.677 | 0.149 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.50 | 142.30 | 748.35 | 3.761 | 0.108 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.92 | 422.44 | 5183.56 | 1.524 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.342 | 0.179 | 0.000 | 0.043 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.179 | 0.000 | 0.047 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.388 | 0.079 | 0.000 | 0.074 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.342 | 0.179 | 0.000 | 0.042 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.342 | 0.179 | 0.000 | 0.047 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.416 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.342 | 0.179 | 0.000 | 0.050 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.342 | 0.179 | 0.000 | 0.052 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.388 | 0.146 | 0.000 | 0.079 |
BANQUET_FLR_6 | 144.89 | 249.90 | 1010.89 | 4.899 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.89 | 249.90 | 1010.89 | 4.914 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 15.927 | 0.149 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.431 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.554 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.933 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.931 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.006 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.480 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 6.098 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.50 | 142.30 | 748.35 | 2.824 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.92 | 422.44 | 5183.56 | 1.145 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.313 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.89 | 249.90 | 1010.89 | 3.677 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.89 | 249.90 | 1010.89 | 3.683 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 5.358 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.312 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.75 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.047 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.50 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.173 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.92 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.89 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.89 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.69 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.036 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 30702814.95 | 0.00 | 30702814.95 | 0.00 | 30702814.95 | 26946214.98 | 4246.00 | 152.56 | 4361.44 | 0.00 |
RETAIL_1_FLR_1 | 2884094.18 | 0.00 | 2884094.18 | 316459.92 | 3200554.10 | 2498216.28 | 4085.91 | 160.20 | 4513.89 | 0.00 |
RETAIL_2_FLR_1 | 3292625.55 | 0.00 | 3292625.55 | 122153.93 | 3414779.47 | 2294951.32 | 385.38 | 614.33 | 7760.29 | 0.00 |
MECH_FLR_1 | 271696.27 | 0.00 | 271696.27 | 288699.32 | 560395.58 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2074432.71 | 0.00 | 2074432.71 | 166563.60 | 2240996.32 | 1821682.01 | 4251.22 | 151.58 | 4357.20 | 0.00 |
LAUNDRY_FLR_1 | 41565338.86 | 0.00 | 41565338.86 | 394204.17 | 41959543.03 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 24292180.99 | 0.00 | 24292180.99 | 699552.56 | 24991733.55 | 14544917.54 | 148.00 | 88.46 | 8523.54 | 0.00 |
LOBBY_FLR_1 | 68016646.43 | 0.00 | 68016646.43 | 1998781.45 | 70015427.88 | 59728886.00 | 4252.30 | 151.21 | 4356.49 | 0.00 |
ROOM_1_FLR_3 | 1406076.84 | 43662.82 | 1449739.65 | 183682.98 | 1633422.64 | 1946875.62 | 2433.33 | 5817.83 | 508.83 | 0.00 |
ROOM_2_FLR_3 | 1405912.09 | 48038.18 | 1453950.27 | 183668.97 | 1637619.24 | 1946647.51 | 2433.33 | 5829.60 | 497.07 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 307.51 | 1100219.48 | 51249.61 | 1151469.09 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 369.00 |
ROOM_4_MULT19_FLR_3 | 19070354.14 | 47405.19 | 19117759.33 | 51263.63 | 19169022.95 | 26405105.73 | 2433.33 | 5827.90 | 498.76 | 0.00 |
ROOM_5_FLR_3 | 1406076.84 | 43595.57 | 1449672.41 | 183682.98 | 1633355.39 | 1946875.62 | 2433.33 | 5817.83 | 508.83 | 0.00 |
ROOM_6_FLR_3 | 1405912.09 | 47964.71 | 1453876.80 | 183668.97 | 1637545.77 | 1946647.51 | 2433.33 | 5817.83 | 508.83 | 0.00 |
CORRIDOR_FLR_3 | 17061088.20 | 0.00 | 17061088.20 | 222109.68 | 17283197.88 | 14972100.18 | 4245.00 | 152.81 | 4362.19 | 0.00 |
ROOM_1_FLR_6 | 351519.21 | 50963.26 | 402482.47 | 183721.42 | 586203.89 | 486718.90 | 2282.53 | 5819.73 | 657.75 | 0.00 |
ROOM_2_FLR_6 | 351478.02 | 52830.31 | 404308.33 | 183707.41 | 588015.74 | 486661.88 | 2289.90 | 5857.94 | 612.15 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2258331.41 | 50899.95 | 2309231.36 | 93998.31 | 2403229.67 | 3126920.42 | 2433.33 | 5817.50 | 509.17 | 0.00 |
BANQUET_FLR_6 | 42644645.52 | 0.00 | 42644645.52 | 448601.54 | 43093247.06 | 37458366.31 | 4254.88 | 151.76 | 4353.36 | 0.00 |
DINING_FLR_6 | 42733972.51 | 0.00 | 42733972.51 | 448601.54 | 43182574.05 | 37458366.31 | 4247.00 | 152.75 | 4360.24 | 0.00 |
KITCHEN_FLR_6 | 42911899.21 | 0.00 | 42911899.21 | 401602.39 | 43313501.60 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 4662872.13 | 0.00 | 4662872.13 | 393066.01 | 5055938.14 | 3961413.96 | 3947.31 | 155.82 | 4656.87 | 0.00 |
Total Facility | 0.20E+10 | 4921103.58 | 0.20E+10 | 18509960.64 | 0.20E+10 | 0.43E+10 | 8760.00 | 6278.96 | 8760.00 | 369.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9736 | 0.0000 | 0.9736 | 0.0000 | 0.9736 | 0.8545 | 4246.00 | 152.56 | 4361.44 |
RETAIL_1_FLR_1 | 0.0915 | 0.0000 | 0.0915 | 0.0100 | 0.1015 | 0.0792 | 4085.91 | 160.20 | 4513.89 |
RETAIL_2_FLR_1 | 0.1044 | 0.0000 | 0.1044 | 0.0039 | 0.1083 | 0.0728 | 385.38 | 614.33 | 7760.29 |
MECH_FLR_1 | 0.0086 | 0.0000 | 0.0086 | 0.0092 | 0.0178 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0658 | 0.0000 | 0.0658 | 0.0053 | 0.0711 | 0.0578 | 4251.22 | 151.58 | 4357.20 |
LAUNDRY_FLR_1 | 1.3180 | 0.0000 | 1.3180 | 0.0125 | 1.3305 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7703 | 0.0000 | 0.7703 | 0.0222 | 0.7925 | 0.4612 | 148.00 | 88.46 | 8523.54 |
LOBBY_FLR_1 | 2.1568 | 0.0000 | 2.1568 | 0.0634 | 2.2202 | 1.8940 | 4252.30 | 151.21 | 4356.49 |
ROOM_1_FLR_3 | 0.0446 | 0.0014 | 0.0460 | 0.0058 | 0.0518 | 0.0617 | 2433.33 | 5817.83 | 508.83 |
ROOM_2_FLR_3 | 0.0446 | 0.0015 | 0.0461 | 0.0058 | 0.0519 | 0.0617 | 2433.33 | 5829.60 | 497.07 |
ROOM_4_MULT19_FLR_3 | 0.6047 | 0.0015 | 0.6062 | 0.0016 | 0.6078 | 0.8373 | 2433.33 | 5827.90 | 498.76 |
ROOM_5_FLR_3 | 0.0446 | 0.0014 | 0.0460 | 0.0058 | 0.0518 | 0.0617 | 2433.33 | 5817.83 | 508.83 |
ROOM_6_FLR_3 | 0.0446 | 0.0015 | 0.0461 | 0.0058 | 0.0519 | 0.0617 | 2433.33 | 5817.83 | 508.83 |
CORRIDOR_FLR_3 | 0.5410 | 0.0000 | 0.5410 | 0.0070 | 0.5480 | 0.4748 | 4245.00 | 152.81 | 4362.19 |
ROOM_1_FLR_6 | 0.0111 | 0.0016 | 0.0128 | 0.0058 | 0.0186 | 0.0154 | 2282.53 | 5819.73 | 657.75 |
ROOM_2_FLR_6 | 0.0111 | 0.0017 | 0.0128 | 0.0058 | 0.0186 | 0.0154 | 2289.90 | 5857.94 | 612.15 |
ROOM_3_MULT9_FLR_6 | 0.0716 | 0.0016 | 0.0732 | 0.0030 | 0.0762 | 0.0992 | 2433.33 | 5817.50 | 509.17 |
BANQUET_FLR_6 | 1.3523 | 0.0000 | 1.3523 | 0.0142 | 1.3665 | 1.1878 | 4254.88 | 151.76 | 4353.36 |
DINING_FLR_6 | 1.3551 | 0.0000 | 1.3551 | 0.0142 | 1.3693 | 1.1878 | 4247.00 | 152.75 | 4360.24 |
KITCHEN_FLR_6 | 1.3607 | 0.0000 | 1.3607 | 0.0127 | 1.3735 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.1479 | 0.0000 | 0.1479 | 0.0125 | 0.1603 | 0.1256 | 3947.31 | 155.82 | 4656.87 |
Total Facility | 59.2075 | 0.1553 | 59.3628 | 0.4634 | 59.8263 | 73.7328 | 8760.00 | 6278.96 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.46E+09 | 0.00 | 0.46E+09 | 0.21E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 40515081.20 | 385667.50 | 40900748.70 | 64690340.46 | 8755.00 | 4.29 | 0.71 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 14.4359 | 0.0000 | 14.4359 | 6.7627 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2847 | 0.0122 | 1.2970 | 2.0513 | 8755.00 | 4.29 | 0.71 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 16.60 | 7788.41 | 0.00 | 0.00 | 0.00 | 955.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6691.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 13.6973 | 14.8024 | 0.0000 | 0.0000 | 0.0000 | 11.4867 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6820 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1344 |
Defaulted Fields | 1183 |
Fields with Defaults | 4016 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 3813.66 | 59698.95 | 20-MAY-05:00 | 295220.81 | 10-AUG-19:30 |
Electricity:Building | 2095.37 | 27845.54 | 01-JUL-05:00 | 122617.06 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 230.70 | 2823.84 | 02-JAN-02:10 | 16796.09 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2088.27 | 27704.39 | 01-JUL-05:00 | 122375.73 | 02-JAN-20:10 |
InteriorLights:Electricity | 439.82 | 3810.72 | 01-JUL-05:00 | 36244.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 87.60 | 795.94 | 02-JAN-02:10 | 7163.56 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 439.82 | 3810.72 | 01-JUL-05:00 | 36244.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 439.82 | 3810.72 | 01-JUL-05:00 | 36244.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 87.60 | 795.94 | 02-JAN-02:10 | 7163.56 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 439.82 | 3810.72 | 01-JUL-05:00 | 36244.21 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 14.15 | 180.36 | 02-JAN-02:10 | 1009.79 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 3.96 | 36.02 | 02-JAN-02:10 | 324.19 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 3.96 | 36.02 | 02-JAN-02:10 | 324.19 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 16.39 | 208.86 | 02-JAN-02:10 | 1169.34 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 4.59 | 41.71 | 02-JAN-02:10 | 375.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 4.59 | 41.71 | 02-JAN-02:10 | 375.41 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.68 | 251.36 | 02-JAN-02:10 | 1511.12 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.21 | 74.63 | 02-JAN-02:10 | 671.67 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.21 | 74.63 | 02-JAN-02:10 | 671.67 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.48 | 68.09 | 02-JAN-02:10 | 396.12 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.88 | 17.11 | 02-JAN-02:10 | 153.96 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.88 | 17.11 | 02-JAN-02:10 | 153.96 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.44 | 994.53 | 02-JAN-02:10 | 4859.35 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.50 | 31.84 | 02-JAN-02:10 | 286.55 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.50 | 31.84 | 02-JAN-02:10 | 286.55 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 20.77 | 240.13 | 01-JUL-05:00 | 1732.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 6.43 | 36.92 | 01-JUL-05:00 | 767.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 6.43 | 36.92 | 01-JUL-05:00 | 767.68 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 223.86 | 2778.84 | 01-JUL-05:00 | 16487.72 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 74.86 | 667.43 | 01-JUL-05:00 | 6458.51 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 74.86 | 667.43 | 01-JUL-05:00 | 6458.51 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 253.77 | 3619.58 | 02-JAN-10:10 | 20179.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 58.78 | 497.64 | 01-JAN-02:10 | 4523.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 253.84 | 3620.57 | 02-JAN-10:10 | 20185.51 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 58.79 | 497.77 | 01-JAN-02:10 | 4525.19 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.40 | 220.79 | 01-JAN-02:10 | 1160.40 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 4.92 | 41.68 | 01-JAN-02:10 | 378.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.40 | 220.76 | 01-JAN-02:10 | 1160.26 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 4.92 | 41.67 | 01-JAN-02:10 | 378.82 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 51.72 | 469.94 | 02-JAN-02:10 | 4229.48 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.72 | 469.94 | 02-JAN-02:10 | 4229.48 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.72 | 469.94 | 02-JAN-02:10 | 4229.48 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 3.85 | 55.20 | 01-JAN-02:10 | 290.10 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 3.85 | 55.19 | 01-JAN-02:10 | 290.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.23 | 10.42 | 01-JAN-02:10 | 94.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.06 | 428.75 | 02-JAN-10:10 | 2390.39 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 6.96 | 58.95 | 01-JAN-02:10 | 535.88 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 189.87 | 2339.18 | 10-JUN-05:00 | 8096.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 14.02 | 89.87 | 10-JUN-05:00 | 1348.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 14.02 | 89.87 | 10-JUN-05:00 | 1348.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 189.87 | 2339.18 | 10-JUN-05:00 | 8096.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 14.02 | 89.87 | 10-JUN-05:00 | 1348.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 14.02 | 89.87 | 10-JUN-05:00 | 1348.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 439.77 | 5902.30 | 02-JAN-02:10 | 18508.51 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 8.66 | 78.67 | 02-JAN-02:10 | 708.07 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 8.66 | 78.67 | 02-JAN-02:10 | 708.07 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 13.68 | 124.34 | 02-JAN-02:10 | 1119.06 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.68 | 124.34 | 02-JAN-02:10 | 1119.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.68 | 124.34 | 02-JAN-02:10 | 1119.06 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1648.46 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.08 | 732.86 | 11-FEB-23:30 | 2789.17 | 13-AUG-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 555.70 | 2369.22 | 01-NOV-02:00 | 130236.29 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.84 | 0.00 | 01-JAN-11:10 | 1306.51 | 01-AUG-03:10 |
MedTempRefrigeration:Refrigeration:Electricity | 21.15 | 636.00 | 25-MAR-05:00 | 716.11 | 15-JUL-13:40 |
Fans:Electricity | 575.46 | 13171.32 | 12-OCT-03:00 | 29774.72 | 10-AUG-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityProduced:Facility | 152.25 | -0.00 | 15-FEB-07:30 | 34554.33 | 24-MAY-12:30 |
ElectricityProduced:Plant | 152.25 | -0.00 | 15-FEB-07:30 | 34554.33 | 24-MAY-12:30 |
Photovoltaic:ElectricityProduced | 159.71 | 0.00 | 01-JAN-00:10 | 37186.56 | 18-MAY-11:30 |
PowerConversion:ElectricityProduced | -7.46 | -2632.23 | 18-MAY-11:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 643.38 | 14186.50 | 17-JUL-03:00 | 38435.11 | 10-AUG-18:20 |
ExteriorEquipment:Electricity | 390.56 | 5777.95 | 02-JAN-02:20 | 23857.89 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.46 | 378.85 | 17-JUN-05:00 | 1269.61 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 3661.41 | 48431.55 | 18-MAY-11:30 | 295220.81 | 10-AUG-19:30 |
ElectricityPurchased:Plant | 3661.41 | 48431.55 | 18-MAY-11:30 | 295220.81 | 10-AUG-19:30 |
Cogeneration:ElectricityPurchased | 3661.41 | 48431.55 | 18-MAY-11:30 | 295220.81 | 10-AUG-19:30 |
General:Cogeneration:ElectricityPurchased | 3661.41 | 48431.55 | 18-MAY-11:30 | 295220.81 | 10-AUG-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 3661.41 | 48431.55 | 18-MAY-11:30 | 295220.81 | 10-AUG-19:30 |
ElectricityNet:Plant | 3661.41 | 48431.55 | 18-MAY-11:30 | 295220.81 | 10-AUG-19:30 |
Cogeneration:ElectricityNet | 3661.41 | 48431.55 | 18-MAY-11:30 | 295220.81 | 10-AUG-19:30 |
General:Cogeneration:ElectricityNet | 3661.41 | 48431.55 | 18-MAY-11:30 | 295220.81 | 10-AUG-19:30 |
General:Fans:Electricity | 575.46 | 13171.32 | 12-OCT-03:00 | 29774.72 | 10-AUG-22:00 |
ExteriorLights:Electricity | 150.11 | 0.00 | 01-JAN-08:10 | 9571.94 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 150.11 | 0.00 | 01-JAN-08:10 | 9571.94 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 366.65 | 5383.28 | 01-JAN-00:10 | 22430.31 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.45 | 15.80 | 01-JAN-00:10 | 157.97 | 01-JAN-07:10 |
HeatRecovery:Electricity | 46.47 | 0.00 | 01-JAN-08:00 | 8265.52 | 05-JAN-00:50 |
General:HeatRecovery:Electricity | 46.47 | 0.00 | 01-JAN-08:00 | 8265.52 | 05-JAN-00:50 |
WaterSystems:Electricity | 90.74 | 1086.56 | 17-JAN-01:10 | 4738.74 | 15-NOV-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 17-JAN-01:10 | 4738.74 | 15-NOV-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 357.79 | 0.00 | 01-JAN-00:10 | 119579.94 | 10-AUG-18:10 |
General:Cooling:Electricity | 357.79 | 0.00 | 01-JAN-00:10 | 119579.94 | 10-AUG-18:10 |
Pumps:Electricity | 70.18 | 47.91 | 13-JUN-15:10 | 4456.51 | 10-AUG-18:10 |
General:Pumps:Electricity | 70.18 | 47.91 | 13-JUN-15:10 | 4456.51 | 10-AUG-18:10 |
WIRED_LTG_ELECTRICITY | 15.48 | 0.00 | 01-JAN-00:10 | 1275.80 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5092.35 | 26805.16 | 25-FEB-02:30 | 450040.63 | 16-JAN-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3303.51 | 13443.27 | 14-MAY-15:20 | 366602.60 | 16-JAN-19:10 |
WaterSystems:NaturalGas | 2669.65 | 13443.27 | 14-AUG-09:00 | 240068.89 | 13-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 2669.65 | 13443.27 | 14-AUG-09:00 | 240068.89 | 13-FEB-21:40 |
Heating:NaturalGas | 633.86 | 0.00 | 07-JAN-11:20 | 185507.66 | 16-JAN-16:20 |
Boiler:Heating:NaturalGas | 633.86 | 0.00 | 07-JAN-11:20 | 185507.66 | 16-JAN-16:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1124.85 | 0.00 | 01-JAN-00:10 | 416348.11 | 10-AUG-18:10 |
PlantLoopCoolingDemand:HVAC | 1124.85 | 0.00 | 01-JAN-00:10 | 416348.11 | 10-AUG-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 1124.85 | 0.00 | 01-JAN-00:10 | 416348.11 | 10-AUG-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 30-MAY-20:30 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 30-MAY-20:30 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 30-MAY-20:30 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 30-MAY-20:30 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 30-MAY-20:30 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 30-MAY-20:30 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 10563.41 | 125322.89 | 28-MAY-14:00 | 1764873.88 | 10-AUG-18:10 |
EnergyTransfer:Building | 4350.60 | 77108.11 | 16-JAN-15:00 | 301614.60 | 10-AUG-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 684.70 | 9571.92 | 19-FEB-04:00 | 33876.91 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 184.38 | 4017.18 | 24-MAR-22:10 | 10344.04 | 29-AUG-06:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.19 | 2008.59 | 24-MAR-22:10 | 5172.02 | 29-AUG-06:50 |
General:Refrigeration:EnergyTransfer | 92.19 | 2008.59 | 24-MAR-22:10 | 5172.02 | 29-AUG-06:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.19 | 2008.59 | 24-MAR-22:10 | 5172.02 | 29-AUG-06:50 |
EnergyTransfer:Plant | 4131.86 | 14119.26 | 01-NOV-02:30 | 993244.07 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.63 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.56 | 1996.31 | 25-MAR-05:00 | 2555.46 | 15-JUL-13:40 |
EnergyTransfer:Zone:BASEMENT | 346.27 | 8936.00 | 23-APR-15:00 | 14313.49 | 13-AUG-10:40 |
Heating:EnergyTransfer | 76.85 | 0.00 | 01-JAN-08:00 | 53210.50 | 16-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 76.85 | 0.00 | 01-JAN-08:00 | 53210.50 | 16-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4181.56 | 68402.19 | 16-JAN-15:00 | 297994.71 | 10-AUG-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 346.27 | 8936.00 | 23-APR-15:00 | 14313.49 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer | 4181.56 | 68402.19 | 16-JAN-15:00 | 297994.71 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 346.27 | 8936.00 | 23-APR-15:00 | 14313.49 | 13-AUG-10:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 23.97 | 0.01 | 20-FEB-17:50 | 2570.22 | 24-AUG-13:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.41 | 0.00 | 01-JAN-00:10 | 685.59 | 26-DEC-10:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.41 | 0.00 | 01-JAN-00:10 | 685.59 | 26-DEC-10:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 23.56 | 0.00 | 01-JAN-02:10 | 2570.22 | 24-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 23.56 | 0.00 | 01-JAN-02:10 | 2570.22 | 24-AUG-13:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.44 | 216.54 | 16-JAN-16:00 | 1641.04 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.44 | 216.54 | 16-JAN-16:00 | 1641.04 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.44 | 216.54 | 16-JAN-16:00 | 1641.04 | 10-AUG-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 3.28 | 0.18 | 17-JAN-18:00 | 1208.68 | 10-AUG-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 140.55 | 16-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 140.55 | 16-JAN-16:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 3.27 | 0.00 | 08-JAN-15:30 | 1208.68 | 10-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 3.27 | 0.00 | 08-JAN-15:30 | 1208.68 | 10-AUG-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 13.32 | 0.01 | 16-FEB-09:50 | 930.16 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.18 | 0.00 | 01-JAN-00:10 | 240.64 | 16-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.18 | 0.00 | 01-JAN-00:10 | 240.64 | 16-JAN-16:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 13.14 | 0.00 | 01-JAN-13:10 | 930.16 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 13.14 | 0.00 | 01-JAN-13:10 | 930.16 | 10-AUG-18:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 576.45 | 8124.64 | 17-JAN-05:00 | 38833.39 | 10-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 576.45 | 8124.64 | 17-JAN-05:00 | 38833.39 | 10-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 576.45 | 8124.64 | 17-JAN-05:00 | 38833.39 | 10-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 220.75 | 602.98 | 26-DEC-12:30 | 11050.17 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 220.75 | 602.98 | 26-DEC-12:30 | 11050.17 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 220.75 | 602.98 | 26-DEC-12:30 | 11050.17 | 10-AUG-18:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 740.73 | 8528.95 | 16-JAN-16:00 | 33487.95 | 10-AUG-19:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 740.73 | 8528.95 | 16-JAN-16:00 | 33487.95 | 10-AUG-19:00 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 740.73 | 8528.95 | 16-JAN-16:00 | 33487.95 | 10-AUG-19:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 32.80 | 0.00 | 01-JAN-08:00 | 8610.67 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 11.32 | 0.00 | 01-JAN-08:00 | 4620.71 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 11.32 | 0.00 | 01-JAN-08:00 | 4620.71 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 21.49 | 0.00 | 01-JAN-00:10 | 8610.67 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 21.49 | 0.00 | 01-JAN-00:10 | 8610.67 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 27.83 | 0.00 | 01-JAN-08:00 | 8322.86 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.49 | 0.00 | 01-JAN-08:00 | 4578.20 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.49 | 0.00 | 01-JAN-08:00 | 4578.20 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.34 | 0.00 | 01-JAN-00:10 | 8322.86 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.34 | 0.00 | 01-JAN-00:10 | 8322.86 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 128.68 | 0.00 | 01-JAN-00:10 | 30942.95 | 14-SEP-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 128.68 | 0.00 | 01-JAN-00:10 | 30942.95 | 14-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 128.68 | 0.00 | 01-JAN-00:10 | 30942.95 | 14-SEP-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 250.88 | 0.00 | 01-JAN-08:00 | 55363.00 | 11-JUL-20:40 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 6.76 | 0.00 | 01-JAN-00:10 | 23208.27 | 15-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 6.76 | 0.00 | 01-JAN-00:10 | 23208.27 | 15-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 244.11 | 0.00 | 01-JAN-08:00 | 55363.00 | 11-JUL-20:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 244.11 | 0.00 | 01-JAN-08:00 | 55363.00 | 11-JUL-20:40 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 31.51 | 0.00 | 01-JAN-08:00 | 7384.71 | 10-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 11.32 | 0.00 | 01-JAN-08:00 | 4541.33 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 11.32 | 0.00 | 01-JAN-08:00 | 4541.33 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 20.19 | 0.00 | 01-JAN-00:10 | 7384.71 | 10-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 20.19 | 0.00 | 01-JAN-00:10 | 7384.71 | 10-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.38 | 0.00 | 01-JAN-08:00 | 8128.83 | 24-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.45 | 0.00 | 01-JAN-08:00 | 4560.10 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.45 | 0.00 | 01-JAN-08:00 | 4560.10 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.93 | 0.00 | 01-JAN-00:10 | 8128.83 | 24-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.93 | 0.00 | 01-JAN-00:10 | 8128.83 | 24-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 136.00 | 0.20 | 02-JAN-15:20 | 8188.00 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.33 | 0.00 | 01-JAN-00:10 | 2009.37 | 26-DEC-14:50 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.33 | 0.00 | 01-JAN-00:10 | 2009.37 | 26-DEC-14:50 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 135.67 | 0.00 | 01-JAN-13:10 | 8188.00 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 135.67 | 0.00 | 01-JAN-13:10 | 8188.00 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.13 | 0.00 | 01-JAN-08:00 | 2434.77 | 10-AUG-18:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.66 | 0.00 | 01-JAN-08:00 | 1479.21 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.66 | 0.00 | 01-JAN-08:00 | 1479.21 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.47 | 0.00 | 01-JAN-00:10 | 2434.77 | 10-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.47 | 0.00 | 01-JAN-00:10 | 2434.77 | 10-AUG-18:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.03 | 0.00 | 01-JAN-08:00 | 2315.23 | 14-JUL-16:40 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.38 | 0.00 | 01-JAN-08:00 | 1485.07 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.38 | 0.00 | 01-JAN-08:00 | 1485.07 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.65 | 0.00 | 01-JAN-00:10 | 2315.23 | 14-JUL-16:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.65 | 0.00 | 01-JAN-00:10 | 2315.23 | 14-JUL-16:40 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 50.15 | 0.00 | 01-JAN-08:00 | 12444.65 | 13-SEP-15:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.35 | 0.00 | 01-JAN-08:00 | 6801.96 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.35 | 0.00 | 01-JAN-08:00 | 6801.96 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 40.80 | 0.00 | 01-JAN-00:10 | 12444.65 | 13-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 40.80 | 0.00 | 01-JAN-00:10 | 12444.65 | 13-SEP-15:30 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 465.33 | 8471.42 | 15-JAN-16:00 | 20083.31 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 465.33 | 8471.42 | 15-JAN-16:00 | 20083.31 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 465.33 | 8471.42 | 15-JAN-16:00 | 20083.31 | 10-AUG-18:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 490.43 | 10085.23 | 26-DEC-15:00 | 20737.59 | 10-AUG-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 490.43 | 10085.23 | 26-DEC-15:00 | 20737.59 | 10-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 490.43 | 10085.23 | 26-DEC-15:00 | 20737.59 | 10-AUG-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 592.51 | 7256.82 | 19-FEB-04:00 | 28788.87 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 592.51 | 7256.82 | 19-FEB-04:00 | 28788.87 | 13-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 48.57 | 0.00 | 05-JAN-10:40 | 5147.31 | 10-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.20 | 0.00 | 01-JAN-00:10 | 1045.54 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.20 | 0.00 | 01-JAN-00:10 | 1045.54 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 48.37 | 0.00 | 01-JAN-16:00 | 5147.31 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 48.37 | 0.00 | 01-JAN-16:00 | 5147.31 | 10-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 1326.68 | 9491.69 | 11-AUG-00:20 | 176270.78 | 16-JAN-16:20 |
PlantLoopHeatingDemand:Plant | 764.23 | 9491.69 | 11-AUG-00:20 | 54593.70 | 07-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 764.23 | 9491.69 | 11-AUG-00:20 | 54593.70 | 07-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 764.23 | 9491.69 | 11-AUG-00:20 | 54593.70 | 07-FEB-07:40 |
EnergyTransfer:HVAC | 2080.96 | 0.00 | 13-JUN-15:10 | 470015.21 | 10-AUG-18:10 |
HeatingCoils:EnergyTransfer | 562.45 | 0.00 | 18-MAR-20:20 | 158593.39 | 16-JAN-16:20 |
PlantLoopHeatingDemand:HVAC | 562.45 | 0.00 | 18-MAR-20:20 | 158593.39 | 16-JAN-16:20 |
HeatingCoils:PlantLoopHeatingDemand | 562.45 | 0.00 | 18-MAR-20:20 | 158593.39 | 16-JAN-16:20 |
CoolingCoils:EnergyTransfer | 1124.85 | 0.00 | 01-JAN-00:10 | 416348.11 | 10-AUG-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 383.56 | 0.00 | 01-JAN-08:00 | 224474.17 | 19-FEB-06:10 |
HeatRecoveryForCooling:EnergyTransfer | 10.10 | 0.00 | 01-JAN-00:10 | 54993.86 | 29-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 764.23 | 9491.69 | 11-AUG-00:20 | 54593.70 | 07-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 764.23 | 9491.69 | 11-AUG-00:20 | 54593.70 | 07-FEB-07:40 |
Boilers:EnergyTransfer | 556.04 | 0.00 | 07-JAN-11:20 | 163364.56 | 16-JAN-16:20 |
Chillers:EnergyTransfer | 1180.80 | 0.00 | 01-JAN-00:10 | 419751.16 | 10-AUG-18:10 |
HeatRejection:EnergyTransfer | 1538.59 | 0.00 | 01-JAN-00:10 | 539331.10 | 10-AUG-18:10 |
General:HeatRejection:EnergyTransfer | 1538.59 | 0.00 | 01-JAN-00:10 | 539331.10 | 10-AUG-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -346.270 | 0.000 | 0.000 | 147.076 | 87.597 | 143.105 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -31.509 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.410 | -23.561 | 0.000 | 0.000 | 15.545 | 3.964 | 10.186 | 11.682 | 0.000 | 0.023 | 0.000 | 0.000 | -7.084 | 0.000 | -4.096 | -7.069 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -32.436 | 0.000 | 0.000 | 17.868 | 4.591 | 11.795 | 0.000 | 0.000 | 0.017 | 0.000 | 0.000 | 0.000 | 0.000 | -1.583 | -0.252 |
MECH_FLR_1 | 0.000 | 0.000 | 0.006 | -3.272 | 0.000 | 0.000 | 3.510 | 8.213 | 12.471 | 0.000 | 0.000 | 0.019 | 0.000 | 0.000 | 0.000 | 0.000 | -4.198 | -16.750 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.180 | -13.136 | 0.000 | 0.000 | 3.016 | 1.883 | 3.598 | 0.000 | 0.000 | 0.030 | 6.481 | 0.000 | 0.000 | 0.000 | -2.052 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -576.448 | 0.000 | 0.000 | 10.551 | 3.504 | 658.131 | 0.000 | 0.000 | 0.026 | 0.000 | 0.000 | 0.000 | 0.000 | -6.156 | -89.609 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -220.754 | 0.000 | 0.000 | 204.553 | 6.430 | 14.341 | 33.328 | 0.000 | 0.109 | 0.000 | 0.000 | -19.528 | 0.000 | -8.926 | -9.553 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -740.733 | 0.000 | 0.000 | 583.536 | 74.863 | 148.998 | 43.297 | 0.000 | 0.266 | 0.000 | 0.000 | -27.595 | 0.000 | -26.976 | -55.656 |
ROOM_1_FLR_3 | 16.007 | -16.144 | 0.000 | -10.031 | 0.000 | 0.000 | 9.747 | 4.922 | 10.478 | 22.184 | 0.000 | 0.145 | 0.000 | 0.000 | -15.853 | 0.000 | -9.755 | -11.701 |
ROOM_2_FLR_3 | 18.475 | -9.000 | 0.000 | -10.330 | 0.000 | 0.000 | 9.677 | 4.922 | 10.477 | 15.324 | 0.000 | 0.091 | 0.000 | 0.000 | -16.325 | 0.000 | -10.182 | -13.128 |
ROOM_3_MULT19_FLR_3 | 0.000 | -115.481 | 0.000 | -13.197 | 0.000 | 0.000 | 0.000 | 58.777 | 194.997 | 127.244 | 0.000 | 0.066 | 0.008 | 0.000 | -111.188 | 0.000 | -65.003 | -76.214 |
ROOM_4_MULT19_FLR_3 | 30.357 | -128.640 | 0.000 | -139.061 | 0.000 | 0.000 | 183.695 | 58.793 | 195.050 | 35.119 | 0.000 | 0.736 | 0.000 | 0.000 | -91.541 | 0.000 | -64.770 | -79.738 |
ROOM_5_FLR_3 | 16.000 | -14.834 | 0.000 | -10.040 | 0.000 | 0.000 | 9.743 | 4.922 | 10.478 | 21.035 | 0.000 | 0.147 | 0.000 | 0.000 | -15.508 | 0.000 | -9.768 | -12.174 |
ROOM_6_FLR_3 | 18.492 | -8.705 | 0.000 | -10.258 | 0.000 | 0.000 | 9.702 | 4.922 | 10.477 | 14.128 | 0.000 | 0.094 | 0.000 | 0.000 | -15.853 | 0.000 | -10.031 | -12.967 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.329 | -135.672 | 0.000 | 0.000 | 122.386 | 51.719 | 0.000 | 19.738 | 0.000 | 0.125 | 0.000 | 0.000 | -20.145 | 0.000 | -11.198 | -27.282 |
ROOM_1_FLR_6 | 5.961 | -4.262 | 0.000 | -2.506 | 0.000 | 0.000 | 2.440 | 1.231 | 2.620 | 5.503 | 0.000 | 0.037 | 0.000 | 0.000 | -3.913 | 0.000 | -2.466 | -4.644 |
ROOM_2_FLR_6 | 6.727 | -2.402 | 0.000 | -2.597 | 0.000 | 0.000 | 2.418 | 1.230 | 2.619 | 3.786 | 0.000 | 0.022 | 0.000 | 0.000 | -4.037 | 0.000 | -2.595 | -5.173 |
ROOM_3_MULT9_FLR_6 | 15.090 | -30.314 | 0.000 | -16.227 | 0.000 | 0.000 | 21.844 | 6.962 | 23.098 | 30.176 | 0.000 | 0.230 | 0.000 | 0.000 | -18.379 | 0.000 | -12.358 | -20.122 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -465.330 | 0.000 | 0.000 | 344.345 | 14.016 | 175.857 | 4.115 | 0.000 | 0.064 | 0.000 | 0.000 | -10.703 | 0.000 | -6.113 | -56.251 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -490.427 | 0.000 | 0.000 | 338.292 | 14.016 | 175.857 | 3.946 | 0.000 | 0.058 | 0.000 | 0.000 | -11.212 | 0.000 | -6.272 | -24.257 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -592.505 | 0.000 | 0.000 | 27.948 | 8.658 | 540.650 | 13.759 | 0.000 | 0.026 | 13.641 | 0.000 | -5.862 | 0.000 | -6.315 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.202 | -48.366 | 0.000 | 0.000 | 30.788 | 13.684 | 0.000 | 9.302 | 0.000 | 0.025 | 9.349 | 0.000 | -9.591 | 0.000 | -5.392 | -0.000 |
Total Facility | 127.109 | -329.783 | 1.128 | -3903.156 | 0.000 | 0.000 | 2098.680 | 439.818 | 2355.282 | 413.664 | 0.000 | 2.357 | 29.481 | 0.000 | -404.316 | 0.000 | -276.205 | -554.049 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -14413.02 | 0.00 | 0.00 | 5772.94 | 6367.62 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6853.10 |
RETAIL_1_FLR_1 | 24-AUG-13:10 | 0.00 | 0.00 | 0.00 | -2570.60 | 0.00 | 0.00 | 150.60 | 90.05 | 252.59 | 2991.20 | 0.00 | 56.08 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -969.92 |
RETAIL_2_FLR_1 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -1656.17 | 0.00 | 0.00 | 656.63 | 333.70 | 752.15 | 0.00 | 0.00 | 32.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -118.78 |
MECH_FLR_1 | 10-AUG-20:00 | 0.00 | 0.00 | 0.00 | -1208.69 | 0.00 | 0.00 | 129.08 | 671.67 | 839.45 | 0.00 | 0.00 | 16.66 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -448.17 |
STORAGE_FLR_1 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -932.71 | 0.00 | 0.00 | 112.21 | 136.85 | 229.41 | 0.00 | 0.00 | 50.46 | 403.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 10-AUG-20:00 | 0.00 | 0.00 | 0.00 | -38834.45 | 0.00 | 0.00 | 408.86 | 286.55 | 44299.38 | 0.00 | 0.00 | 22.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6183.08 |
CAFE_FLR_1 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -11230.58 | 0.00 | 0.00 | 7891.19 | 248.03 | 914.47 | 864.36 | 0.00 | 206.03 | 1106.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -33899.82 | 0.00 | 0.00 | 22389.26 | 5285.99 | 9501.36 | 1112.67 | 0.00 | 538.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4927.66 |
ROOM_1_FLR_3 | 14-MAY-18:01 | 0.00 | -10508.52 | 0.00 | -735.33 | 0.00 | 0.00 | 283.21 | 378.87 | 484.65 | 3651.60 | 0.00 | 0.00 | 6525.21 | 0.00 | -0.00 | 0.00 | -79.68 | 0.00 |
ROOM_2_FLR_3 | 14-JUL-16:21 | 0.00 | -9661.94 | 0.00 | -896.89 | 0.00 | 0.00 | 204.94 | 106.07 | 505.67 | 5822.42 | 0.00 | 0.00 | 3930.99 | 0.00 | -0.00 | 0.00 | -11.26 | 0.00 |
ROOM_3_MULT19_FLR_3 | 14-SEP-13:30 | 0.00 | -30941.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.71 | 2352.88 | 36884.08 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -481.67 | -9080.30 |
ROOM_4_MULT19_FLR_3 | 14-MAY-21:51 | 0.00 | -58962.96 | 0.00 | -7692.33 | 0.00 | 0.00 | 6537.09 | 3846.41 | 6668.31 | 0.00 | 0.00 | 0.00 | 53341.67 | 0.00 | -2881.81 | 0.00 | -856.38 | 0.00 |
ROOM_5_FLR_3 | 14-MAY-18:01 | 0.00 | -9356.30 | 0.00 | -729.21 | 0.00 | 0.00 | 283.21 | 378.87 | 484.65 | 194.50 | 0.00 | 0.00 | 8816.75 | 0.00 | -0.00 | 0.00 | -72.49 | 0.00 |
ROOM_6_FLR_3 | 24-JUL-08:51 | 0.00 | -8835.49 | 0.00 | -934.75 | 0.00 | 0.00 | 72.90 | 166.68 | 452.99 | 5292.34 | 0.00 | 0.00 | 3822.94 | 0.00 | -0.00 | 0.00 | -37.63 | 0.00 |
CORRIDOR_FLR_3 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -8218.11 | 0.00 | 0.00 | 4460.10 | 3759.54 | 0.00 | 1187.08 | 0.00 | 248.26 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1436.87 |
ROOM_1_FLR_6 | 14-MAY-18:01 | 0.00 | -2738.20 | 0.00 | -184.21 | 0.00 | 0.00 | 70.80 | 94.72 | 121.16 | 904.00 | 0.00 | 0.00 | 1756.30 | 0.00 | -0.00 | 0.00 | -24.56 | 0.00 |
ROOM_2_FLR_6 | 14-JUL-16:21 | 0.00 | -2487.45 | 0.00 | -236.80 | 0.00 | 0.00 | 48.39 | 26.52 | 126.42 | 1434.45 | 0.00 | 0.00 | 1096.28 | 0.00 | -0.00 | 0.00 | -7.80 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14-MAY-18:01 | 0.00 | -15364.66 | 0.00 | -1160.42 | 0.00 | 0.00 | 637.22 | 535.88 | 1068.37 | 225.06 | 0.00 | 0.00 | 14213.22 | 0.00 | -0.00 | 0.00 | -154.67 | 0.00 |
BANQUET_FLR_6 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -20419.78 | 0.00 | 0.00 | 13659.32 | 719.00 | 6747.90 | 841.43 | 0.00 | 125.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1673.16 |
DINING_FLR_6 | 10-AUG-21:10 | 0.00 | 0.00 | 0.00 | -21187.14 | 0.00 | 0.00 | 15902.03 | 898.75 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -86.81 | 0.00 | -19.23 | -2255.50 |
KITCHEN_FLR_6 | 13-AUG-10:35 | 0.00 | 0.00 | 0.00 | -28787.66 | 0.00 | 0.00 | 464.19 | 236.02 | 23951.61 | 2448.54 | 0.00 | 1.03 | 1686.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 | -5147.04 | 0.00 | 0.00 | 771.14 | 310.85 | 0.00 | 1438.41 | 0.00 | 87.61 | 2539.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-18:02 | 0.00 | -126958.12 | 0.00 | -193335.65 | 0.00 | 0.00 | 80256.70 | 30381.70 | 120174.13 | 29933.00 | 0.00 | 4503.28 | 55044.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 26-DEC-10:20 | 0.00 | 0.00 | 685.56 | 0.00 | 0.00 | 0.00 | 179.02 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -469.07 | 0.00 | -266.76 | -471.40 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 16-JAN-16:00 | 0.00 | 0.00 | 140.55 | 0.00 | 0.00 | 0.00 | 43.84 | 149.26 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -217.14 | -381.59 |
STORAGE_FLR_1 | 16-JAN-16:00 | 0.00 | 0.00 | 240.63 | 0.00 | 0.00 | 0.00 | 33.72 | 34.21 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -125.29 | -259.75 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 26-DEC-16:11 | 7934.12 | 292.80 | 0.00 | -292.80 | 0.00 | 0.00 | 293.98 | 106.08 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1057.57 | 0.00 | -456.60 | -7020.20 |
ROOM_2_FLR_3 | 16-JAN-16:11 | 7748.04 | 290.68 | 0.00 | -290.68 | 0.00 | 0.00 | 163.33 | 125.01 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -994.62 | 0.00 | -512.35 | -6750.63 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 07-JAN-16:11 | 42172.12 | 4759.73 | 0.00 | -4759.73 | 0.00 | 0.00 | 2969.07 | 1493.31 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6249.15 | 0.00 | -2730.21 | -41773.81 |
ROOM_5_FLR_3 | 26-DEC-16:11 | 7694.27 | 291.47 | 0.00 | -291.47 | 0.00 | 0.00 | 293.98 | 106.08 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1057.64 | 0.00 | -456.08 | -6780.80 |
ROOM_6_FLR_3 | 16-JAN-16:11 | 7498.15 | 289.11 | 0.00 | -289.11 | 0.00 | 0.00 | 163.32 | 125.01 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1065.05 | 0.00 | -511.73 | -6430.93 |
CORRIDOR_FLR_3 | 26-DEC-14:50 | 0.00 | 0.00 | 2009.28 | 0.00 | 0.00 | 0.00 | 1385.82 | 1174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1256.55 | 0.00 | -671.67 | -2641.73 |
ROOM_1_FLR_6 | 26-DEC-16:11 | 2333.68 | 73.79 | 0.00 | -73.79 | 0.00 | 0.00 | 73.50 | 26.52 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -260.06 | 0.00 | -114.83 | -2108.85 |
ROOM_2_FLR_6 | 15-JAN-16:11 | 2267.58 | 73.09 | 0.00 | -73.09 | 0.00 | 0.00 | 40.83 | 31.25 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -258.36 | 0.00 | -133.17 | -2003.43 |
ROOM_3_MULT9_FLR_6 | 26-DEC-16:11 | 11710.80 | 473.44 | 0.00 | -473.44 | 0.00 | 0.00 | 661.46 | 150.05 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1222.17 | 0.00 | -528.58 | -11212.84 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 19-FEB-06:00 | 0.00 | 0.00 | 1045.53 | 0.00 | 0.00 | 0.00 | 1283.31 | 248.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1024.23 | 0.00 | -422.73 | -1130.56 |
Total Facility | 16-JAN-16:11 | 12757.64 | 83070.83 | 2701.06 | -83070.83 | 0.00 | 0.00 | 36936.60 | 9171.58 | 70977.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24405.04 | 0.00 | -13475.07 | -94664.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.1752 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.0769 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.9294 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5304 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.003540 | 12.5400 | 0.000610 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.003540 | 142.3000 | 0.000914 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.000963 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1231 | 2.1231 | 1.2823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3260 | 0.3260 | 0.1190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1996 | 0.1996 | 0.1375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1880 | 0.1880 | 0.0019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2832 | 3.2832 | 0.0328 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4494 | 1.4494 | 1.0146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4875 | 4.4875 | 2.8406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0846 | 1.0846 | 0.7126 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0282 | 2.0282 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1318 | 2.1318 | 1.7822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1526 | 2.1526 | 0.5511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6344 | 0.6344 | 0.1884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.1752 | 20.0769 | 20.1752 | 10.5304 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2823 | 1.2823 | 1.2823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1630 | 0.1630 | 0.1190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1375 | 0.1375 | 0.1375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0940 | 0.0940 | 0.0019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6416 | 1.6416 | 0.0328 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0146 | 1.0146 | 1.0146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8406 | 2.8406 | 2.8406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7126 | 0.7126 | 0.7126 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7808 | 1.7808 | 1.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7822 | 1.7822 | 1.7822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0763 | 1.0763 | 0.5511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3172 | 0.3172 | 0.1884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.9294 | 10.5304 | 10.5304 | 10.5304 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 30.17 |
Number of hours not met | 30.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 633.86 | 185507.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 357.79 | 119579.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 439.82 | 36244.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 150.11 | 9571.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.46 | 1269.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 366.65 | 22430.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.45 | 157.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 575.46 | 29774.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 70.18 | 4456.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 46.47 | 8265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.74 | 2669.65 | 240068.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.84 | 1306.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.15 | 716.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1692.54 | 3813.66 |
Natural Gas | 1788.84 | 5092.35 |
Additional | 0.00 | 0.00 |
Total | 3481.37 | 8906.01 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 159.71 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 38.77 |
Space Heating | 0.00 |
Space Cooling | 31.54 |
Fans (All) | 50.72 |
Service Water Heating | 8.00 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 336.15 |
Subtotal | 336.15 |
Natural Gas [MJ/m2] | |
Space Heating | 55.87 |
Service Water Heating | 235.31 |
Miscellaneous (All) | 448.85 |
Subtotal | 448.85 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.94 |
Space Heating | 7.12 |
Space Cooling | 4.02 |
Fans (All) | 6.46 |
Service Water Heating | 30.99 |
Receptacle Equipment | 38.60 |
Miscellaneous | 7.88 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_KITCHEN | 2022. | 8760. |
LTG_SCH_DINING | 1877. | 8760. |
LTG_SCH_BASEMENT | 2095. | 8760. |
LTG_SCH_LOBBY | 2166. | 8760. |
LTG_SCH_STORAGE | 1543. | 8760. |
LTG_SCH_MECHANIC | 2022. | 8760. |
LTG_SCH_LAUNDRY | 2527. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2166. | 8760. |
LTG_SCH_RETAIL | 2296. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8547.83 | 212.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8547.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 212.17 | 0.00 | 0.00 | 0.00 |
Average | 8749.61 | 10.39 | 0.00 | 0.00 | 0.00 |
Sum | 192491.33 | 228.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4153.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4151.00 | 3.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 3.00 | 0.00 | 0.00 | 0.00 |
Average | 288886.90 | 0.14 | 0.00 | 0.00 | 0.00 |
Sum | 6355511.83 | 3.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8273.17 | 486.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8726.83 | 33.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8273.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 486.83 | 0.00 | 0.00 | 0.00 |
Average | 8734.62 | 25.38 | 0.00 | 0.00 | 0.00 |
Sum | 192161.67 | 558.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2113909.00 | 1520.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4149.83 | 4.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4139.67 | 14.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1244445.67 | 1269.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1244744.33 | 970.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108243.83 | 25.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2113909.00 | 1520.00 | 0.00 | 0.00 | 0.00 |
Average | 288714.15 | 172.89 | 0.00 | 0.00 | 0.00 |
Sum | 6351711.33 | 3803.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:55:34
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285145E+11 | 12634.24 | 11-JAN-19:10 | 12.30 | 9.41 | 0.708692E+10 | 4381.38 | 13-JAN-22:10 | 0.60 | 0.60 |
February | 0.251223E+11 | 12458.58 | 01-FEB-21:00 | 6.70 | 5.41 | 0.627564E+10 | 4341.50 | 01-FEB-23:10 | 6.28 | 4.82 |
March | 0.272376E+11 | 12297.67 | 02-MAR-19:10 | 10.22 | 8.41 | 0.683005E+10 | 4247.81 | 01-MAR-23:10 | 10.22 | 8.41 |
April | 0.262960E+11 | 12947.16 | 27-APR-18:10 | 25.55 | 15.86 | 0.651445E+10 | 4155.30 | 06-APR-22:10 | 25.55 | 15.86 |
May | 0.278489E+11 | 13018.20 | 14-MAY-10:35 | 20.03 | 12.68 | 0.679614E+10 | 4202.91 | 18-MAY-22:10 | 8.80 | 7.20 |
June | 0.279682E+11 | 13596.62 | 28-JUN-18:10 | 25.40 | 16.48 | 0.671146E+10 | 4288.09 | 23-JUN-22:10 | 25.40 | 16.48 |
July | 0.300322E+11 | 14075.13 | 24-JUL-18:10 | 28.72 | 17.86 | 0.705980E+10 | 4379.50 | 28-JUL-22:10 | 14.90 | 12.78 |
August | 0.308856E+11 | 14413.04 | 10-AUG-18:10 | 30.57 | 19.31 | 0.722850E+10 | 4464.89 | 18-AUG-22:10 | 15.65 | 12.22 |
September | 0.303580E+11 | 14363.29 | 10-SEP-10:35 | 18.33 | 13.89 | 0.713299E+10 | 4548.45 | 15-SEP-22:10 | 14.32 | 13.32 |
October | 0.315165E+11 | 14184.00 | 07-OCT-10:35 | 14.63 | 10.97 | 0.749882E+10 | 4626.18 | 06-OCT-22:10 | 14.63 | 10.97 |
November | 0.304251E+11 | 14005.43 | 04-NOV-10:35 | 17.23 | 14.47 | 0.730337E+10 | 4656.75 | 10-NOV-23:10 | 4.40 | 3.92 |
December | 0.300642E+11 | 13347.89 | 01-DEC-21:00 | 5.00 | 5.00 | 0.734720E+10 | 4608.24 | 01-DEC-23:10 | 3.90 | 3.68 |
Annual Sum or Average | 0.346269E+12 | 0.837853E+11 | ||||||||
Minimum of Months | 0.251223E+11 | 12297.67 | 5.00 | 5.00 | 0.627564E+10 | 4155.30 | 0.60 | 0.60 | ||
Maximum of Months | 0.315165E+11 | 14413.04 | 30.57 | 19.31 | 0.749882E+10 | 4656.75 | 25.55 | 16.48 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506062E+09 | 1093.13 | 20-JAN-11:50 | 5.60 | 3.57 | 0.620319E+09 | 371.48 | 11-JAN-22:40 | 5.60 | 3.57 |
February | 0.979646E+09 | 1207.90 | 08-FEB-11:50 | 4.82 | 2.98 | 0.566189E+09 | 419.04 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.165551E+10 | 1551.56 | 02-MAR-13:30 | 12.75 | 7.74 | 0.639196E+09 | 434.58 | 14-MAR-21:30 | 12.50 | 8.53 |
April | 0.213296E+10 | 1942.62 | 27-APR-13:05 | 26.10 | 16.37 | 0.639187E+09 | 482.31 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.255258E+10 | 1844.28 | 04-MAY-13:30 | 23.05 | 15.32 | 0.684248E+09 | 480.76 | 04-MAY-22:10 | 18.43 | 12.09 |
June | 0.268527E+10 | 1572.74 | 28-JUN-14:10 | 25.18 | 15.64 | 0.689938E+09 | 488.33 | 28-JUN-21:40 | 17.77 | 13.93 |
July | 0.309014E+10 | 2124.36 | 24-JUL-13:30 | 28.85 | 18.23 | 0.751408E+09 | 491.84 | 24-JUL-22:10 | 20.40 | 15.71 |
August | 0.326591E+10 | 2570.44 | 24-AUG-13:10 | 28.93 | 19.36 | 0.760603E+09 | 491.84 | 15-AUG-22:10 | 28.93 | 19.36 |
September | 0.280673E+10 | 2524.40 | 14-SEP-13:15 | 23.17 | 17.52 | 0.693520E+09 | 491.84 | 11-SEP-22:10 | 23.17 | 17.52 |
October | 0.214134E+10 | 2278.49 | 04-OCT-13:00 | 20.60 | 11.21 | 0.657715E+09 | 473.31 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.108565E+10 | 1649.65 | 04-NOV-13:25 | 20.85 | 16.00 | 0.605244E+09 | 391.67 | 02-NOV-21:49 | 20.85 | 16.00 |
December | 0.659445E+09 | 1234.38 | 05-DEC-11:50 | 9.72 | 5.97 | 0.621709E+09 | 372.94 | 05-DEC-22:30 | 4.70 | 2.12 |
Annual Sum or Average | 0.235612E+11 | 0.792927E+10 | ||||||||
Minimum of Months | 0.506062E+09 | 1093.13 | 4.82 | 2.98 | 0.566189E+09 | 371.48 | 4.70 | 2.12 | ||
Maximum of Months | 0.326591E+10 | 2570.44 | 28.93 | 19.36 | 0.760603E+09 | 491.84 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210988E+10 | 1173.78 | 11-JAN-21:00 | 11.10 | 10.22 | 0.735819E+09 | 472.85 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.208865E+10 | 1268.23 | 27-FEB-21:00 | 12.20 | 10.06 | 0.674320E+09 | 496.72 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.257081E+10 | 1294.78 | 18-MAR-18:10 | 18.03 | 9.10 | 0.766919E+09 | 501.75 | 14-MAR-22:10 | 18.03 | 9.10 |
April | 0.270631E+10 | 1509.31 | 27-APR-18:10 | 25.55 | 15.86 | 0.759424E+09 | 538.42 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.298621E+10 | 1492.28 | 04-MAY-18:10 | 22.70 | 14.48 | 0.808359E+09 | 539.25 | 04-MAY-22:10 | 18.43 | 12.09 |
June | 0.301755E+10 | 1552.66 | 28-JUN-18:10 | 25.40 | 16.48 | 0.801227E+09 | 548.78 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.328813E+10 | 1619.47 | 24-JUL-18:10 | 28.72 | 17.86 | 0.851774E+09 | 561.12 | 31-JUL-22:10 | 20.05 | 15.96 |
August | 0.332262E+10 | 1656.15 | 10-AUG-18:10 | 30.57 | 19.31 | 0.861369E+09 | 569.54 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.301924E+10 | 1549.62 | 14-SEP-18:10 | 21.52 | 16.29 | 0.803016E+09 | 554.38 | 14-SEP-22:10 | 17.12 | 14.45 |
October | 0.278293E+10 | 1429.80 | 04-OCT-18:10 | 17.52 | 10.01 | 0.785289E+09 | 534.07 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.234017E+10 | 1302.20 | 04-NOV-18:10 | 15.00 | 13.34 | 0.728619E+09 | 488.17 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.220329E+10 | 1181.60 | 05-DEC-21:00 | 5.60 | 1.73 | 0.738768E+09 | 474.12 | 05-DEC-23:10 | 4.03 | 2.13 |
Annual Sum or Average | 0.324358E+11 | 0.931490E+10 | ||||||||
Minimum of Months | 0.208865E+10 | 1173.78 | 5.60 | 1.73 | 0.674320E+09 | 472.85 | 4.03 | 2.13 | ||
Maximum of Months | 0.332262E+10 | 1656.15 | 30.57 | 19.31 | 0.861369E+09 | 569.54 | 21.82 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37580744.10 | 18.85 | 11-JAN-21:00 | 11.10 | 10.22 | 0.166132E+09 | 110.29 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 36061176.94 | 21.40 | 27-FEB-19:10 | 15.73 | 11.89 | 0.155344E+09 | 120.04 | 28-FEB-22:10 | 8.12 | 7.00 |
March | 45032475.26 | 21.40 | 18-MAR-18:10 | 18.03 | 9.10 | 0.184509E+09 | 120.41 | 10-MAR-22:10 | 18.03 | 9.10 |
April | 83262778.99 | 581.16 | 27-APR-21:00 | 17.20 | 11.44 | 0.186429E+09 | 120.45 | 14-APR-21:19 | 17.20 | 11.44 |
May | 0.239284E+09 | 770.01 | 05-MAY-21:00 | 18.90 | 12.98 | 0.200857E+09 | 120.45 | 15-MAY-22:10 | 12.70 | 11.06 |
June | 0.464685E+09 | 932.49 | 28-JUN-20:00 | 21.70 | 15.30 | 0.198167E+09 | 120.45 | 02-JUN-21:10 | 21.70 | 15.30 |
July | 0.820555E+09 | 1151.36 | 24-JUL-21:00 | 22.80 | 16.50 | 0.204972E+09 | 120.45 | 26-JUL-21:30 | 18.65 | 15.87 |
August | 0.951354E+09 | 1208.68 | 10-AUG-20:00 | 25.60 | 17.66 | 0.205822E+09 | 120.45 | 10-AUG-23:10 | 18.07 | 15.44 |
September | 0.411654E+09 | 895.39 | 14-SEP-21:00 | 18.30 | 14.89 | 0.197143E+09 | 120.45 | 01-SEP-01:10 | 18.30 | 14.89 |
October | 97129021.43 | 541.59 | 04-OCT-20:00 | 17.20 | 10.66 | 0.194761E+09 | 120.45 | 05-OCT-00:10 | 12.93 | 9.84 |
November | 45776719.57 | 208.71 | 06-NOV-22:00 | 15.00 | 14.30 | 0.175352E+09 | 120.45 | 06-NOV-22:10 | 15.10 | 14.35 |
December | 39461806.58 | 18.94 | 29-DEC-21:00 | 9.40 | 7.72 | 0.169554E+09 | 110.48 | 29-DEC-22:10 | 8.90 | 7.55 |
Annual Sum or Average | 0.327184E+10 | 0.223904E+10 | ||||||||
Minimum of Months | 36061176.94 | 18.85 | 9.40 | 7.72 | 0.155344E+09 | 110.29 | 8.12 | 7.00 | ||
Maximum of Months | 0.951354E+09 | 1208.68 | 25.60 | 17.66 | 0.205822E+09 | 120.45 | 21.70 | 15.87 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197466E+09 | 464.23 | 11-JAN-22:00 | 11.10 | 10.49 | 0.116690E+09 | 68.57 | 14-JAN-03:09 | 2.12 | 1.67 |
February | 0.359288E+09 | 640.51 | 27-FEB-22:00 | 12.20 | 10.06 | 0.105508E+09 | 69.58 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.785476E+09 | 637.80 | 10-MAR-22:00 | 11.70 | 11.07 | 0.117249E+09 | 69.43 | 10-MAR-23:10 | 11.02 | 10.80 |
April | 0.113211E+10 | 817.82 | 27-APR-18:10 | 25.55 | 15.86 | 0.113660E+09 | 73.38 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.152827E+10 | 855.49 | 06-MAY-10:35 | 20.93 | 16.16 | 0.118938E+09 | 75.08 | 05-MAY-22:10 | 20.93 | 16.16 |
June | 0.166341E+10 | 871.61 | 28-JUN-18:10 | 25.40 | 16.48 | 0.118064E+09 | 76.64 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.182636E+10 | 918.56 | 24-JUL-18:10 | 28.72 | 17.86 | 0.124974E+09 | 79.04 | 24-JUL-22:10 | 20.40 | 15.71 |
August | 0.185397E+10 | 932.72 | 10-AUG-18:10 | 30.57 | 19.31 | 0.126696E+09 | 80.12 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.162296E+10 | 856.46 | 14-SEP-10:35 | 19.43 | 16.41 | 0.117327E+09 | 76.46 | 14-SEP-22:10 | 17.12 | 14.45 |
October | 0.123969E+10 | 761.31 | 05-OCT-10:35 | 14.63 | 9.59 | 0.117327E+09 | 72.82 | 04-OCT-22:10 | 14.63 | 9.59 |
November | 0.658919E+09 | 672.29 | 04-NOV-19:00 | 15.00 | 13.08 | 0.112934E+09 | 70.14 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.268035E+09 | 430.48 | 29-DEC-22:00 | 8.90 | 7.51 | 0.116691E+09 | 68.57 | 18-DEC-04:10 | 8.90 | 7.51 |
Annual Sum or Average | 0.131359E+11 | 0.140606E+10 | ||||||||
Minimum of Months | 0.197466E+09 | 430.48 | 8.90 | 7.51 | 0.105508E+09 | 68.57 | 2.12 | 1.67 | ||
Maximum of Months | 0.185397E+10 | 932.72 | 30.57 | 19.31 | 0.126696E+09 | 80.12 | 21.82 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469102E+11 | 36976.22 | 11-JAN-21:00 | 11.10 | 10.22 | 0.649338E+09 | 381.57 | 17-JAN-00:40 | 1.30 | -0.4 |
February | 0.428252E+11 | 37349.57 | 27-FEB-21:00 | 12.20 | 10.06 | 0.587074E+09 | 381.58 | 27-FEB-04:40 | 12.20 | 10.06 |
March | 0.483097E+11 | 37496.00 | 14-MAR-20:00 | 14.40 | 9.49 | 0.652386E+09 | 381.60 | 28-MAR-21:10 | 7.70 | 4.73 |
April | 0.474050E+11 | 38293.83 | 27-APR-20:00 | 19.40 | 13.66 | 0.629497E+09 | 381.57 | 07-APR-21:10 | 19.40 | 13.66 |
May | 0.497049E+11 | 38238.88 | 04-MAY-20:00 | 19.40 | 13.12 | 0.650707E+09 | 381.57 | 11-MAY-22:49 | 9.78 | 8.57 |
June | 0.488103E+11 | 38469.67 | 28-JUN-20:00 | 21.70 | 15.30 | 0.630868E+09 | 381.56 | 01-JUN-00:00 | 21.70 | 15.30 |
July | 0.507073E+11 | 38743.26 | 24-JUL-20:00 | 23.90 | 16.63 | 0.649331E+09 | 381.58 | 26-JUL-21:19 | 19.67 | 16.34 |
August | 0.511373E+11 | 38833.39 | 10-AUG-20:00 | 25.60 | 17.66 | 0.652081E+09 | 381.63 | 08-AUG-21:10 | 25.60 | 17.66 |
September | 0.484177E+11 | 38363.36 | 14-SEP-20:00 | 18.90 | 14.81 | 0.629190E+09 | 381.57 | 01-SEP-01:10 | 18.90 | 14.81 |
October | 0.488415E+11 | 37937.81 | 04-OCT-20:00 | 17.20 | 10.66 | 0.649641E+09 | 381.56 | 16-OCT-21:10 | 9.90 | 8.49 |
November | 0.463519E+11 | 37280.42 | 02-NOV-20:00 | 12.80 | 10.42 | 0.628122E+09 | 381.56 | 29-NOV-00:00 | 10.60 | 9.73 |
December | 0.470259E+11 | 36871.80 | 29-DEC-21:00 | 9.40 | 7.72 | 0.649337E+09 | 381.57 | 12-DEC-03:00 | 9.40 | 7.72 |
Annual Sum or Average | 0.576447E+12 | 0.765757E+10 | ||||||||
Minimum of Months | 0.428252E+11 | 36871.80 | 9.40 | 7.72 | 0.587074E+09 | 381.56 | 1.30 | -0.4 | ||
Maximum of Months | 0.511373E+11 | 38833.39 | 25.60 | 17.66 | 0.652386E+09 | 381.63 | 25.60 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143291E+11 | 8341.79 | 08-JAN-11:35 | 1.33 | 0.94 | 0.839190E+10 | 5409.97 | 11-JAN-22:40 | 9.97 | 8.97 |
February | 0.146055E+11 | 9288.13 | 12-FEB-11:35 | 5.60 | 0.67 | 0.768994E+10 | 5674.27 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.177340E+11 | 9648.30 | 14-MAR-15:40 | 16.83 | 10.74 | 0.870756E+10 | 5770.14 | 14-MAR-21:40 | 12.40 | 8.44 |
April | 0.186791E+11 | 10438.53 | 27-APR-18:10 | 25.55 | 15.86 | 0.852081E+10 | 5954.11 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.202277E+11 | 10229.23 | 04-MAY-18:10 | 22.70 | 14.48 | 0.892236E+10 | 5972.71 | 04-MAY-22:10 | 18.43 | 12.09 |
June | 0.204063E+11 | 10488.75 | 28-JUN-18:10 | 25.40 | 16.48 | 0.877363E+10 | 5953.63 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.221551E+11 | 11008.12 | 24-JUL-18:10 | 28.72 | 17.86 | 0.918958E+10 | 6114.38 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.225832E+11 | 11230.15 | 10-AUG-18:10 | 30.57 | 19.31 | 0.935447E+10 | 6209.50 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.205914E+11 | 11034.61 | 10-SEP-10:35 | 18.33 | 13.89 | 0.885230E+10 | 6093.00 | 12-SEP-21:40 | 18.67 | 14.43 |
October | 0.190324E+11 | 10400.05 | 07-OCT-10:35 | 14.63 | 10.97 | 0.882994E+10 | 5992.19 | 04-OCT-22:10 | 14.63 | 10.97 |
November | 0.155637E+11 | 9749.40 | 04-NOV-10:35 | 17.23 | 14.47 | 0.827391E+10 | 5542.36 | 02-NOV-22:10 | 17.23 | 14.47 |
December | 0.148457E+11 | 9243.87 | 02-DEC-11:35 | 11.83 | 6.03 | 0.840850E+10 | 5393.70 | 05-DEC-22:40 | 4.60 | 2.18 |
Annual Sum or Average | 0.220753E+12 | 0.103915E+12 | ||||||||
Minimum of Months | 0.143291E+11 | 8341.79 | 1.33 | 0.67 | 0.768994E+10 | 5393.70 | 4.60 | 2.18 | ||
Maximum of Months | 0.225832E+11 | 11230.15 | 30.57 | 19.31 | 0.935447E+10 | 6209.50 | 21.82 | 16.04 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.539854E+11 | 26398.17 | 11-JAN-22:00 | 11.10 | 10.49 | 0.265564E+11 | 17392.49 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.514096E+11 | 27919.18 | 27-FEB-21:00 | 12.20 | 10.06 | 0.243757E+11 | 18024.96 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.603852E+11 | 28239.92 | 14-MAR-20:00 | 14.40 | 9.49 | 0.277338E+11 | 18086.33 | 14-MAR-22:10 | 12.12 | 8.27 |
April | 0.612971E+11 | 31457.11 | 27-APR-18:10 | 25.55 | 15.86 | 0.272354E+11 | 18802.31 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.658330E+11 | 31187.83 | 04-MAY-18:10 | 22.70 | 14.48 | 0.287032E+11 | 18886.56 | 04-MAY-22:10 | 18.43 | 12.09 |
June | 0.657500E+11 | 32181.99 | 28-JUN-18:10 | 25.40 | 16.48 | 0.282778E+11 | 19059.70 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.702095E+11 | 33325.68 | 24-JUL-18:10 | 28.72 | 17.86 | 0.296082E+11 | 19186.03 | 31-JUL-22:10 | 20.05 | 15.96 |
August | 0.711374E+11 | 33898.97 | 10-AUG-18:10 | 30.57 | 19.31 | 0.300021E+11 | 19186.16 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.658553E+11 | 32182.87 | 14-SEP-18:10 | 21.52 | 16.29 | 0.283207E+11 | 19186.01 | 12-SEP-22:10 | 21.52 | 16.29 |
October | 0.633629E+11 | 30323.30 | 04-OCT-18:10 | 17.52 | 10.01 | 0.282606E+11 | 18898.35 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.564040E+11 | 28338.54 | 04-NOV-18:10 | 15.00 | 13.34 | 0.263861E+11 | 17897.03 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.551008E+11 | 26488.79 | 05-DEC-21:00 | 5.60 | 1.73 | 0.267305E+11 | 17430.34 | 05-DEC-23:10 | 4.03 | 2.13 |
Annual Sum or Average | 0.740730E+12 | 0.332191E+12 | ||||||||
Minimum of Months | 0.514096E+11 | 26398.17 | 5.60 | 1.73 | 0.243757E+11 | 17392.49 | 4.03 | 2.13 | ||
Maximum of Months | 0.711374E+11 | 33898.97 | 30.57 | 19.31 | 0.300021E+11 | 19186.16 | 21.52 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9794141.45 | 851.27 | 26-JAN-19:04 | 8.30 | 7.74 | 93187640.60 | 56.69 | 16-JAN-00:30 | 8.30 | 7.74 |
February | 27677579.04 | 2575.08 | 08-FEB-16:12 | 7.03 | 3.66 | 85262444.83 | 56.69 | 28-FEB-00:20 | 12.03 | 10.57 |
March | 96968284.07 | 2718.92 | 01-MAR-16:11 | 12.20 | 6.75 | 95669060.56 | 56.69 | 18-MAR-23:19 | 10.20 | 8.02 |
April | 0.318848E+09 | 2704.19 | 13-APR-18:01 | 16.52 | 9.25 | 93848026.63 | 56.69 | 27-APR-21:10 | 16.73 | 11.41 |
May | 0.618646E+09 | 2810.99 | 14-MAY-18:01 | 21.83 | 11.88 | 98041355.08 | 56.69 | 04-MAY-21:30 | 21.83 | 11.88 |
June | 0.791791E+09 | 2521.26 | 30-JUN-15:11 | 20.60 | 14.39 | 95390512.70 | 56.69 | 28-JUN-21:00 | 20.60 | 14.39 |
July | 0.123811E+10 | 2554.10 | 26-JUL-15:11 | 22.40 | 16.96 | 98911596.01 | 56.69 | 31-JUL-23:10 | 18.57 | 14.72 |
August | 0.123061E+10 | 2553.53 | 18-AUG-15:11 | 20.73 | 14.08 | 98968413.24 | 56.69 | 11-AUG-21:00 | 20.73 | 14.08 |
September | 0.775341E+09 | 2510.36 | 14-SEP-18:01 | 21.52 | 16.29 | 94994365.53 | 56.69 | 12-SEP-21:49 | 21.52 | 16.29 |
October | 0.218348E+09 | 2724.33 | 04-OCT-18:01 | 17.52 | 10.01 | 96370348.40 | 56.69 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 35193228.97 | 2448.27 | 04-NOV-15:11 | 20.73 | 15.94 | 91284970.93 | 56.69 | 04-NOV-23:19 | 13.30 | 12.93 |
December | 9939073.31 | 1340.59 | 05-DEC-16:11 | 6.10 | 4.53 | 93475993.47 | 56.69 | 12-DEC-04:10 | 1.52 | 1.52 |
Annual Sum or Average | 0.537126E+10 | 0.113540E+10 | ||||||||
Minimum of Months | 9794141.45 | 851.27 | 6.10 | 3.66 | 85262444.83 | 56.69 | 1.52 | 1.52 | ||
Maximum of Months | 0.123811E+10 | 2810.99 | 22.40 | 16.96 | 98968413.24 | 56.69 | 21.83 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6964973.90 | 835.27 | 03-JAN-19:04 | 6.78 | 5.87 | 92738284.14 | 56.69 | 16-JAN-00:30 | -0.6 | -1.8 |
February | 13032953.02 | 1978.30 | 26-FEB-16:12 | 14.40 | 10.21 | 84538396.45 | 56.69 | 27-FEB-22:19 | 12.20 | 10.16 |
March | 39309187.37 | 2372.23 | 01-MAR-16:11 | 12.20 | 6.75 | 94920420.13 | 56.69 | 18-MAR-23:19 | 10.20 | 8.02 |
April | 0.192913E+09 | 2502.70 | 25-APR-17:42 | 14.60 | 8.96 | 93943972.55 | 68.39 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.401969E+09 | 2540.30 | 21-MAY-17:42 | 15.60 | 9.45 | 0.100649E+09 | 73.14 | 15-MAY-21:10 | 15.60 | 9.45 |
June | 0.570120E+09 | 2482.14 | 22-JUN-16:21 | 24.40 | 15.53 | 99344160.47 | 74.31 | 22-JUN-21:40 | 16.33 | 13.15 |
July | 0.888755E+09 | 2639.70 | 14-JUL-16:21 | 24.40 | 16.40 | 0.105618E+09 | 77.91 | 26-JUL-21:10 | 20.68 | 16.76 |
August | 0.898958E+09 | 2382.98 | 10-AUG-21:51 | 22.50 | 15.63 | 0.103486E+09 | 74.87 | 08-AUG-21:10 | 22.50 | 15.63 |
September | 0.449035E+09 | 2475.93 | 22-SEP-16:11 | 24.43 | 17.44 | 98121909.27 | 71.43 | 13-SEP-21:30 | 24.43 | 17.44 |
October | 97898620.28 | 1994.14 | 07-OCT-18:01 | 13.80 | 10.77 | 95867011.18 | 65.50 | 04-OCT-21:10 | 13.80 | 10.77 |
November | 18810786.92 | 1840.33 | 05-NOV-15:11 | 14.60 | 12.80 | 90814743.98 | 56.69 | 06-NOV-22:19 | 15.20 | 14.40 |
December | 7532035.26 | 817.82 | 14-DEC-19:04 | 6.60 | 5.40 | 92915385.81 | 56.69 | 10-DEC-00:20 | 6.60 | 5.40 |
Annual Sum or Average | 0.358530E+10 | 0.115296E+10 | ||||||||
Minimum of Months | 6964973.90 | 817.82 | 6.60 | 5.40 | 84538396.45 | 56.69 | -0.6 | -1.8 | ||
Maximum of Months | 0.898958E+09 | 2639.70 | 24.43 | 17.44 | 0.105618E+09 | 77.91 | 24.43 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5649684.91 | 80.57 | 08-JAN-15:20 | 5.20 | 2.41 | 0.00 | 0.00 | 01-JAN-00:10 | 5.20 | 2.41 |
February | 9151803.09 | 158.34 | 27-FEB-15:05 | 19.90 | 12.22 | 0.00 | 0.00 | 01-FEB-00:10 | 19.90 | 12.22 |
March | 41207877.41 | 224.67 | 18-MAR-13:40 | 19.07 | 10.73 | 0.00 | 0.00 | 01-MAR-00:10 | 19.07 | 10.73 |
April | 0.114761E+09 | 322.20 | 27-APR-13:15 | 26.10 | 16.46 | 0.00 | 0.00 | 01-APR-00:10 | 26.10 | 16.46 |
May | 0.175031E+09 | 304.49 | 04-MAY-13:30 | 23.05 | 15.32 | 0.00 | 0.00 | 01-MAY-00:10 | 23.05 | 15.32 |
June | 0.216316E+09 | 237.81 | 28-JUN-13:20 | 24.60 | 15.70 | 0.00 | 0.00 | 01-JUN-00:10 | 24.60 | 15.70 |
July | 0.313093E+09 | 309.76 | 31-JUL-13:30 | 27.75 | 18.58 | 0.00 | 0.00 | 01-JUL-00:10 | 27.75 | 18.58 |
August | 0.361607E+09 | 388.30 | 24-AUG-13:20 | 28.97 | 19.35 | 0.00 | 0.00 | 01-AUG-00:10 | 28.97 | 19.35 |
September | 0.284898E+09 | 407.14 | 14-SEP-13:30 | 23.35 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 23.35 | 17.43 |
October | 0.141238E+09 | 406.82 | 04-OCT-13:00 | 20.60 | 11.21 | 0.00 | 0.00 | 01-OCT-00:10 | 20.60 | 11.21 |
November | 22208525.18 | 237.22 | 04-NOV-13:40 | 20.93 | 15.98 | 0.00 | 0.00 | 01-NOV-00:10 | 20.93 | 15.98 |
December | 7984432.76 | 136.55 | 06-DEC-15:05 | 4.72 | 4.12 | 0.00 | 0.00 | 01-DEC-00:10 | 4.72 | 4.12 |
Annual Sum or Average | 0.169315E+10 | 0.00 | ||||||||
Minimum of Months | 5649684.91 | 80.57 | 4.72 | 2.41 | 0.00 | 0.00 | 4.72 | 2.41 | ||
Maximum of Months | 0.361607E+09 | 407.14 | 28.97 | 19.35 | 0.00 | 0.00 | 28.97 | 19.35 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68294252.06 | 690.20 | 12-JAN-09:02 | 6.70 | 5.79 | 95094246.03 | 56.69 | 11-JAN-22:10 | 6.70 | 5.79 |
February | 95746484.05 | 789.55 | 12-FEB-09:01 | 1.97 | -1.0 | 86307413.70 | 56.69 | 27-FEB-22:10 | 12.20 | 10.11 |
March | 0.187016E+09 | 813.04 | 28-MAR-18:02 | 10.92 | 4.32 | 96410027.32 | 56.69 | 09-MAR-22:10 | 10.92 | 4.32 |
April | 0.274732E+09 | 847.59 | 24-APR-18:01 | 12.93 | 7.27 | 94340307.85 | 67.87 | 27-APR-21:49 | 14.87 | 11.14 |
May | 0.369551E+09 | 877.05 | 14-MAY-21:51 | 16.70 | 9.76 | 99248835.74 | 72.71 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.422099E+09 | 846.70 | 28-JUN-18:01 | 25.40 | 16.48 | 97927752.37 | 71.21 | 22-JUN-21:00 | 25.40 | 16.48 |
July | 0.483998E+09 | 866.75 | 30-JUL-18:01 | 26.32 | 17.50 | 0.102522E+09 | 73.40 | 26-JUL-21:10 | 26.32 | 17.50 |
August | 0.484088E+09 | 861.20 | 07-AUG-18:01 | 26.28 | 16.73 | 0.101945E+09 | 71.22 | 25-AUG-21:10 | 21.48 | 16.43 |
September | 0.358395E+09 | 818.65 | 12-SEP-15:12 | 24.40 | 16.82 | 96576194.63 | 69.94 | 13-SEP-21:00 | 18.30 | 14.64 |
October | 0.251383E+09 | 840.75 | 02-OCT-18:01 | 14.32 | 8.97 | 96809392.20 | 66.46 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.145811E+09 | 738.70 | 19-NOV-09:02 | 10.10 | 9.12 | 92847707.38 | 56.69 | 06-NOV-22:10 | 10.10 | 9.12 |
December | 70906404.07 | 790.94 | 03-DEC-09:02 | 7.98 | 3.60 | 95170972.53 | 56.69 | 15-DEC-22:19 | 5.77 | 5.55 |
Annual Sum or Average | 0.321202E+10 | 0.115520E+10 | ||||||||
Minimum of Months | 68294252.06 | 690.20 | 1.97 | -1.0 | 86307413.70 | 56.69 | 5.77 | 4.32 | ||
Maximum of Months | 0.484088E+09 | 877.05 | 26.32 | 17.50 | 0.102522E+09 | 73.40 | 26.32 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9650619.51 | 783.37 | 03-JAN-19:04 | 6.78 | 5.87 | 93134156.15 | 56.69 | 16-JAN-00:30 | -0.6 | -1.8 |
February | 26027209.32 | 1837.07 | 12-FEB-09:01 | 1.97 | -1.0 | 85233046.57 | 56.69 | 27-FEB-22:19 | 12.20 | 10.16 |
March | 86303288.50 | 2378.76 | 25-MAR-15:11 | 11.70 | 3.80 | 95825718.10 | 56.69 | 18-MAR-23:19 | 11.70 | 3.80 |
April | 0.320332E+09 | 2335.94 | 19-APR-15:12 | 13.13 | 6.88 | 94191869.77 | 56.69 | 28-APR-01:10 | 14.03 | 11.94 |
May | 0.532896E+09 | 2521.40 | 14-MAY-18:01 | 21.83 | 11.88 | 98088079.94 | 56.69 | 07-MAY-00:20 | 21.83 | 11.88 |
June | 0.825892E+09 | 2271.20 | 30-JUN-15:11 | 20.60 | 14.39 | 95692685.26 | 56.69 | 28-JUN-21:00 | 20.60 | 14.39 |
July | 0.108180E+10 | 2317.14 | 10-JUL-15:11 | 21.10 | 14.81 | 99016141.17 | 56.69 | 27-JUL-21:40 | 18.17 | 14.77 |
August | 0.120660E+10 | 2321.83 | 30-AUG-15:11 | 23.57 | 16.58 | 99150447.01 | 56.69 | 11-AUG-21:40 | 23.57 | 16.58 |
September | 0.701163E+09 | 2312.94 | 15-SEP-18:01 | 21.60 | 16.08 | 94950326.78 | 56.69 | 11-SEP-21:40 | 21.60 | 16.08 |
October | 0.210210E+09 | 2416.77 | 04-OCT-18:01 | 17.52 | 10.01 | 96484073.99 | 56.69 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 34652140.17 | 2109.35 | 04-NOV-15:11 | 20.73 | 15.94 | 91272821.77 | 56.69 | 04-NOV-23:19 | 13.30 | 12.93 |
December | 12664253.76 | 964.70 | 02-DEC-09:02 | 8.58 | 4.35 | 93425915.07 | 56.69 | 14-DEC-03:09 | 5.28 | 3.74 |
Annual Sum or Average | 0.504819E+10 | 0.113647E+10 | ||||||||
Minimum of Months | 9650619.51 | 783.37 | 1.97 | -1.0 | 85233046.57 | 56.69 | -0.6 | -1.8 | ||
Maximum of Months | 0.120660E+10 | 2521.40 | 23.57 | 16.58 | 99150447.01 | 56.69 | 23.57 | 16.58 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6282966.05 | 851.43 | 03-JAN-19:04 | 6.78 | 5.87 | 92715314.14 | 56.69 | 15-JAN-00:20 | -1.0 | -3.2 |
February | 12200639.14 | 974.40 | 25-FEB-09:02 | 11.88 | 10.94 | 84481338.72 | 56.69 | 18-FEB-00:20 | 11.88 | 10.94 |
March | 32771115.87 | 2049.43 | 25-MAR-08:62 | 4.78 | 0.26 | 94935152.60 | 56.69 | 18-MAR-23:19 | 4.78 | 0.26 |
April | 0.202732E+09 | 2121.53 | 25-APR-18:02 | 13.95 | 8.77 | 93978435.08 | 66.96 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.371786E+09 | 2178.42 | 06-MAY-08:51 | 19.40 | 15.38 | 99343520.55 | 70.69 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.626943E+09 | 2206.47 | 10-JUN-08:51 | 18.30 | 14.28 | 98809842.49 | 69.72 | 20-JUN-21:19 | 18.87 | 13.53 |
July | 0.797271E+09 | 2442.62 | 24-JUL-08:51 | 23.90 | 16.63 | 0.103471E+09 | 72.94 | 24-JUL-21:10 | 22.43 | 16.40 |
August | 0.883529E+09 | 2429.79 | 13-AUG-08:51 | 20.90 | 15.90 | 0.103076E+09 | 73.23 | 08-AUG-21:10 | 20.90 | 15.90 |
September | 0.422969E+09 | 2258.67 | 13-SEP-08:51 | 18.30 | 15.25 | 96719183.89 | 69.94 | 13-SEP-21:30 | 18.30 | 14.77 |
October | 99036548.28 | 2015.55 | 07-OCT-08:61 | 10.18 | 9.20 | 95687755.03 | 63.09 | 04-OCT-21:10 | 10.18 | 9.20 |
November | 18369561.36 | 1268.12 | 04-NOV-08:62 | 13.07 | 11.67 | 90750565.41 | 56.69 | 06-NOV-22:19 | 15.20 | 14.40 |
December | 7380962.87 | 793.13 | 14-DEC-19:04 | 6.60 | 5.40 | 92864452.47 | 56.69 | 15-DEC-22:19 | 5.77 | 5.55 |
Annual Sum or Average | 0.348127E+10 | 0.114683E+10 | ||||||||
Minimum of Months | 6282966.05 | 793.13 | 4.78 | 0.26 | 84481338.72 | 56.69 | -1.0 | -3.2 | ||
Maximum of Months | 0.883529E+09 | 2442.62 | 23.90 | 16.63 | 0.103471E+09 | 73.23 | 22.43 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122270E+10 | 1289.09 | 11-JAN-22:00 | 11.10 | 10.49 | 0.119886E+10 | 711.85 | 11-JAN-22:49 | 9.68 | 8.60 |
February | 0.161711E+10 | 1513.38 | 27-FEB-19:10 | 15.73 | 11.89 | 0.108552E+10 | 733.73 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.253491E+10 | 1547.52 | 18-MAR-17:50 | 18.48 | 9.34 | 0.121175E+10 | 737.12 | 14-MAR-22:10 | 18.48 | 9.34 |
April | 0.304733E+10 | 1793.65 | 27-APR-18:10 | 25.55 | 15.86 | 0.119012E+10 | 784.97 | 27-APR-21:49 | 14.87 | 11.14 |
May | 0.362123E+10 | 1841.67 | 06-MAY-10:35 | 20.93 | 16.16 | 0.127512E+10 | 801.16 | 15-MAY-22:10 | 12.70 | 11.06 |
June | 0.370680E+10 | 1920.70 | 28-JUN-18:10 | 25.40 | 16.48 | 0.127227E+10 | 824.43 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.406305E+10 | 2029.20 | 24-JUL-18:10 | 28.72 | 17.86 | 0.135690E+10 | 850.98 | 24-JUL-22:10 | 20.40 | 15.71 |
August | 0.414057E+10 | 2054.53 | 10-AUG-18:10 | 30.57 | 19.31 | 0.137961E+10 | 860.86 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.368599E+10 | 1920.65 | 15-SEP-10:35 | 18.50 | 15.07 | 0.127138E+10 | 840.65 | 14-SEP-22:10 | 18.50 | 15.07 |
October | 0.299228E+10 | 1711.33 | 07-OCT-10:35 | 14.63 | 10.97 | 0.122921E+10 | 781.77 | 04-OCT-22:10 | 14.63 | 10.97 |
November | 0.188247E+10 | 1541.17 | 04-NOV-17:20 | 17.60 | 14.26 | 0.116302E+10 | 727.05 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.140347E+10 | 1281.84 | 05-DEC-21:10 | 5.50 | 1.77 | 0.119888E+10 | 710.67 | 05-DEC-22:49 | 4.50 | 2.23 |
Annual Sum or Average | 0.339179E+11 | 0.148326E+11 | ||||||||
Minimum of Months | 0.122270E+10 | 1281.84 | 5.50 | 1.77 | 0.108552E+10 | 710.67 | 4.50 | 2.23 | ||
Maximum of Months | 0.414057E+10 | 2054.53 | 30.57 | 19.31 | 0.137961E+10 | 860.86 | 21.82 | 15.74 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5375165.26 | 837.70 | 02-JAN-19:05 | 8.80 | 6.27 | 92554455.84 | 56.69 | 17-JAN-05:10 | 1.60 | 0.13 |
February | 22289262.68 | 2643.55 | 08-FEB-16:12 | 7.03 | 3.66 | 84737686.39 | 56.69 | 18-FEB-00:20 | -1.0 | -2.0 |
March | 88485001.24 | 2822.88 | 01-MAR-16:11 | 12.20 | 6.75 | 95260267.61 | 56.69 | 18-MAR-23:19 | 10.20 | 8.02 |
April | 0.323696E+09 | 2816.69 | 13-APR-18:01 | 16.52 | 9.25 | 93708578.06 | 56.69 | 30-APR-04:00 | 11.70 | 11.70 |
May | 0.643822E+09 | 2922.44 | 14-MAY-18:01 | 21.83 | 11.88 | 98040774.21 | 56.70 | 14-MAY-03:20 | 21.83 | 11.88 |
June | 0.829401E+09 | 2590.96 | 30-JUN-15:11 | 20.60 | 14.39 | 95437157.51 | 56.70 | 03-JUN-02:39 | 20.60 | 14.39 |
July | 0.130991E+10 | 2608.83 | 12-JUL-15:11 | 18.50 | 14.04 | 98890477.53 | 56.70 | 13-JUL-04:00 | 12.80 | 11.87 |
August | 0.126187E+10 | 2613.37 | 28-AUG-18:01 | 23.87 | 16.61 | 98917752.35 | 56.69 | 24-AUG-22:00 | 23.87 | 16.61 |
September | 0.760105E+09 | 2618.17 | 03-SEP-15:11 | 18.17 | 14.24 | 94872595.63 | 56.69 | 11-SEP-21:10 | 17.70 | 14.09 |
October | 0.186462E+09 | 2828.31 | 04-OCT-18:01 | 17.52 | 10.01 | 96000438.79 | 56.69 | 07-OCT-23:30 | 11.10 | 10.04 |
November | 28625266.27 | 2598.12 | 04-NOV-15:11 | 20.73 | 15.94 | 90703822.03 | 56.70 | 04-NOV-23:10 | 13.30 | 12.93 |
December | 6207257.21 | 848.47 | 01-DEC-19:04 | 6.02 | 5.54 | 92886755.61 | 56.69 | 23-DEC-00:20 | 1.87 | 1.62 |
Annual Sum or Average | 0.546625E+10 | 0.113201E+10 | ||||||||
Minimum of Months | 5375165.26 | 837.70 | 6.02 | 3.66 | 84737686.39 | 56.69 | -1.0 | -2.0 | ||
Maximum of Months | 0.130991E+10 | 2922.44 | 23.87 | 16.61 | 98917752.35 | 56.70 | 23.87 | 16.61 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1888987.00 | 859.49 | 10-JAN-19:05 | 9.32 | 4.98 | 92268079.44 | 56.69 | 30-JAN-03:09 | 7.02 | 6.23 |
February | 9842331.99 | 1790.94 | 26-FEB-16:12 | 14.40 | 10.21 | 84039022.23 | 56.69 | 14-FEB-00:20 | 14.40 | 10.21 |
March | 33924605.69 | 2435.75 | 01-MAR-16:11 | 12.20 | 6.75 | 94474879.83 | 56.69 | 18-MAR-23:19 | 10.20 | 8.02 |
April | 0.190814E+09 | 2626.67 | 25-APR-17:42 | 14.60 | 8.96 | 93952254.04 | 69.97 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.410033E+09 | 2694.80 | 21-MAY-17:42 | 15.60 | 9.45 | 0.101515E+09 | 76.42 | 15-MAY-21:10 | 15.60 | 9.45 |
June | 0.600047E+09 | 2578.05 | 22-JUN-16:21 | 24.40 | 15.53 | 0.100432E+09 | 78.73 | 22-JUN-21:30 | 16.70 | 13.38 |
July | 0.964383E+09 | 2724.25 | 14-JUL-16:21 | 24.40 | 16.40 | 0.107111E+09 | 82.59 | 26-JUL-21:10 | 20.68 | 16.76 |
August | 0.933499E+09 | 2542.88 | 06-AUG-21:51 | 17.90 | 14.41 | 0.103930E+09 | 75.89 | 08-AUG-21:10 | 24.15 | 15.61 |
September | 0.416572E+09 | 2687.83 | 22-SEP-16:11 | 24.43 | 17.44 | 98724058.93 | 73.94 | 11-SEP-21:40 | 24.43 | 17.44 |
October | 71468875.00 | 2049.21 | 07-OCT-18:01 | 13.80 | 10.77 | 95464402.42 | 65.64 | 04-OCT-21:10 | 13.80 | 10.77 |
November | 13068514.26 | 1863.21 | 05-NOV-15:11 | 14.60 | 12.80 | 90254313.29 | 56.69 | 29-NOV-01:10 | 10.40 | 9.52 |
December | 3572916.87 | 794.23 | 01-DEC-16:14 | 7.43 | 5.87 | 92371757.98 | 56.69 | 23-DEC-00:20 | 1.87 | 1.62 |
Annual Sum or Average | 0.364911E+10 | 0.115454E+10 | ||||||||
Minimum of Months | 1888987.00 | 794.23 | 7.43 | 4.98 | 84039022.23 | 56.69 | 1.87 | 1.62 | ||
Maximum of Months | 0.964383E+09 | 2724.25 | 24.43 | 17.44 | 0.107111E+09 | 82.59 | 24.43 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19946219.76 | 1323.97 | 20-JAN-16:11 | 5.20 | 3.48 | 94458918.99 | 56.69 | 11-JAN-22:19 | 5.20 | 3.48 |
February | 98621369.48 | 1794.15 | 12-FEB-16:11 | 6.33 | 1.47 | 86698155.52 | 56.69 | 27-FEB-23:49 | 12.20 | 10.59 |
March | 0.205544E+09 | 1813.03 | 25-MAR-15:11 | 11.70 | 3.80 | 97030309.14 | 56.69 | 14-MAR-21:10 | 11.70 | 3.80 |
April | 0.355590E+09 | 1721.59 | 13-APR-18:01 | 16.52 | 9.25 | 94803823.84 | 56.69 | 27-APR-21:00 | 14.40 | 11.03 |
May | 0.482681E+09 | 1836.13 | 14-MAY-18:01 | 21.83 | 11.88 | 98448097.64 | 56.69 | 07-MAY-00:20 | 21.83 | 11.88 |
June | 0.578213E+09 | 1731.06 | 01-JUN-18:02 | 17.70 | 10.65 | 95638433.26 | 56.69 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.781433E+09 | 1708.24 | 26-JUL-15:11 | 22.40 | 16.96 | 98933370.98 | 56.69 | 20-JUL-21:40 | 22.40 | 16.96 |
August | 0.856505E+09 | 1670.62 | 11-AUG-18:01 | 20.88 | 15.38 | 99022546.77 | 56.69 | 25-AUG-21:49 | 21.02 | 16.21 |
September | 0.666983E+09 | 1692.92 | 15-SEP-18:01 | 21.60 | 16.08 | 95294897.24 | 56.69 | 15-SEP-21:49 | 14.68 | 13.58 |
October | 0.351253E+09 | 1807.64 | 04-OCT-18:01 | 17.52 | 10.01 | 97525091.80 | 56.69 | 25-OCT-22:10 | 14.32 | 12.82 |
November | 86812755.24 | 1601.05 | 04-NOV-18:01 | 15.00 | 13.34 | 92480537.41 | 56.69 | 04-NOV-23:19 | 13.30 | 12.93 |
December | 49754260.29 | 1610.99 | 03-DEC-19:02 | 8.72 | 3.46 | 94810153.57 | 56.69 | 04-DEC-22:19 | 4.70 | 3.27 |
Annual Sum or Average | 0.453334E+10 | 0.114514E+10 | ||||||||
Minimum of Months | 19946219.76 | 1323.97 | 5.20 | 1.47 | 86698155.52 | 56.69 | 4.70 | 3.27 | ||
Maximum of Months | 0.856505E+09 | 1836.13 | 22.40 | 16.96 | 99022546.77 | 56.69 | 22.40 | 16.96 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354716E+11 | 16943.34 | 11-JAN-23:10 | 9.22 | 8.15 | 0.160647E+11 | 10696.78 | 11-JAN-23:49 | 8.48 | 7.83 |
February | 0.328349E+11 | 17361.10 | 27-FEB-23:10 | 12.20 | 10.40 | 0.146244E+11 | 10902.69 | 27-FEB-23:49 | 12.20 | 10.59 |
March | 0.380336E+11 | 17387.57 | 10-MAR-23:10 | 11.02 | 10.80 | 0.165437E+11 | 10897.79 | 14-MAR-22:49 | 11.78 | 8.25 |
April | 0.384615E+11 | 19302.98 | 27-APR-18:10 | 25.55 | 15.86 | 0.162096E+11 | 11261.22 | 27-APR-22:49 | 14.40 | 10.85 |
May | 0.413950E+11 | 19245.21 | 04-MAY-18:10 | 22.70 | 14.48 | 0.170899E+11 | 11348.63 | 05-MAY-22:10 | 17.62 | 12.71 |
June | 0.412722E+11 | 19979.56 | 28-JUN-18:10 | 25.40 | 16.48 | 0.168077E+11 | 11349.01 | 27-JUN-22:10 | 25.40 | 16.48 |
July | 0.434946E+11 | 20362.82 | 24-JUL-18:10 | 28.72 | 17.86 | 0.174273E+11 | 11349.11 | 21-JUL-22:10 | 28.72 | 17.86 |
August | 0.434864E+11 | 20418.93 | 10-AUG-18:10 | 30.57 | 19.31 | 0.175134E+11 | 11348.96 | 24-AUG-22:10 | 21.62 | 17.07 |
September | 0.402716E+11 | 19090.76 | 14-SEP-18:10 | 21.52 | 16.29 | 0.165594E+11 | 11326.55 | 12-SEP-22:49 | 21.52 | 16.29 |
October | 0.390484E+11 | 17999.60 | 04-OCT-18:10 | 17.52 | 10.01 | 0.166467E+11 | 11119.15 | 04-OCT-22:49 | 14.27 | 9.79 |
November | 0.358446E+11 | 17489.27 | 06-NOV-23:10 | 15.40 | 14.28 | 0.157887E+11 | 10923.44 | 06-NOV-23:49 | 14.60 | 13.10 |
December | 0.357143E+11 | 16845.93 | 29-DEC-23:10 | 8.72 | 7.62 | 0.160876E+11 | 10658.70 | 29-DEC-23:49 | 7.98 | 7.08 |
Annual Sum or Average | 0.465329E+12 | 0.197363E+12 | ||||||||
Minimum of Months | 0.328349E+11 | 16845.93 | 8.72 | 7.62 | 0.146244E+11 | 10658.70 | 7.98 | 7.08 | ||
Maximum of Months | 0.434946E+11 | 20418.93 | 30.57 | 19.31 | 0.175134E+11 | 11349.11 | 28.72 | 17.86 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382028E+11 | 17791.60 | 11-JAN-23:10 | 9.22 | 8.15 | 0.166397E+11 | 11092.46 | 11-JAN-23:49 | 8.48 | 7.83 |
February | 0.351898E+11 | 18152.06 | 27-FEB-23:10 | 12.20 | 10.40 | 0.151589E+11 | 11273.72 | 27-FEB-23:49 | 12.20 | 10.59 |
March | 0.403877E+11 | 18204.07 | 10-MAR-23:10 | 11.02 | 10.80 | 0.171474E+11 | 11281.10 | 08-MAR-23:49 | 11.02 | 10.80 |
April | 0.404871E+11 | 19981.68 | 27-APR-18:10 | 25.55 | 15.86 | 0.167499E+11 | 11348.68 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.432096E+11 | 20199.54 | 05-MAY-21:10 | 18.72 | 12.94 | 0.175660E+11 | 11349.10 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.429123E+11 | 20626.56 | 28-JUN-21:10 | 16.97 | 13.74 | 0.172148E+11 | 11349.01 | 27-JUN-22:10 | 16.97 | 13.74 |
July | 0.450999E+11 | 21156.46 | 24-JUL-21:10 | 22.43 | 16.40 | 0.178074E+11 | 11349.12 | 21-JUL-22:10 | 22.43 | 16.40 |
August | 0.450979E+11 | 21187.78 | 10-AUG-21:10 | 22.92 | 16.74 | 0.178920E+11 | 11348.97 | 24-AUG-22:10 | 21.62 | 17.07 |
September | 0.419313E+11 | 19673.39 | 14-SEP-18:10 | 21.52 | 16.29 | 0.169898E+11 | 11348.84 | 11-SEP-22:10 | 21.52 | 16.29 |
October | 0.411697E+11 | 18680.06 | 04-OCT-18:10 | 17.52 | 10.01 | 0.172079E+11 | 11344.70 | 04-OCT-23:10 | 13.80 | 9.78 |
November | 0.383135E+11 | 18267.53 | 06-NOV-23:10 | 15.40 | 14.28 | 0.163697E+11 | 11286.65 | 06-NOV-23:49 | 14.60 | 13.10 |
December | 0.384238E+11 | 17706.25 | 29-DEC-23:10 | 8.72 | 7.62 | 0.166725E+11 | 11060.21 | 29-DEC-23:49 | 7.98 | 7.08 |
Annual Sum or Average | 0.490425E+12 | 0.203416E+12 | ||||||||
Minimum of Months | 0.351898E+11 | 17706.25 | 8.72 | 7.62 | 0.151589E+11 | 11060.21 | 7.98 | 7.08 | ||
Maximum of Months | 0.450999E+11 | 21187.78 | 25.55 | 16.74 | 0.178920E+11 | 11349.12 | 22.43 | 17.07 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.468934E+11 | 25281.46 | 11-JAN-19:05 | 12.30 | 9.41 | 0.188680E+11 | 11319.54 | 07-JAN-18:10 | 12.30 | 9.41 |
February | 0.431500E+11 | 26044.77 | 27-FEB-11:50 | 16.23 | 10.66 | 0.170436E+11 | 11319.54 | 18-FEB-18:10 | 16.23 | 10.66 |
March | 0.490886E+11 | 26684.11 | 14-MAR-10:50 | 11.42 | 8.58 | 0.188760E+11 | 11319.49 | 18-MAR-17:10 | 19.22 | 9.55 |
April | 0.489828E+11 | 27882.01 | 27-APR-10:40 | 20.37 | 13.53 | 0.182623E+11 | 11319.57 | 29-APR-17:10 | 21.13 | 14.68 |
May | 0.517366E+11 | 28110.88 | 14-MAY-10:50 | 20.32 | 12.80 | 0.188716E+11 | 11319.61 | 13-MAY-17:10 | 20.32 | 12.80 |
June | 0.511697E+11 | 28379.33 | 10-JUN-10:50 | 20.40 | 14.81 | 0.182659E+11 | 11319.57 | 24-JUN-17:10 | 19.32 | 11.84 |
July | 0.534888E+11 | 28683.66 | 30-JUL-10:50 | 23.62 | 16.21 | 0.188680E+11 | 11319.66 | 15-JUL-17:10 | 23.62 | 16.21 |
August | 0.537366E+11 | 28797.89 | 13-AUG-10:40 | 24.17 | 17.28 | 0.188753E+11 | 11319.66 | 12-AUG-17:10 | 24.17 | 17.28 |
September | 0.504893E+11 | 28217.40 | 10-SEP-10:50 | 18.62 | 13.97 | 0.182615E+11 | 11319.62 | 23-SEP-17:10 | 21.93 | 16.62 |
October | 0.499776E+11 | 27263.32 | 07-OCT-10:50 | 14.82 | 11.00 | 0.188688E+11 | 11319.41 | 07-OCT-17:10 | 15.73 | 11.80 |
November | 0.466580E+11 | 26988.10 | 04-NOV-10:50 | 17.52 | 14.63 | 0.182586E+11 | 11319.51 | 04-NOV-17:10 | 18.25 | 14.42 |
December | 0.471434E+11 | 25619.79 | 03-DEC-11:50 | 11.52 | 5.93 | 0.188680E+11 | 11319.54 | 23-DEC-18:10 | 5.60 | 4.99 |
Annual Sum or Average | 0.592515E+12 | 0.222188E+12 | ||||||||
Minimum of Months | 0.431500E+11 | 25281.46 | 11.42 | 5.93 | 0.170436E+11 | 11319.41 | 5.60 | 4.99 | ||
Maximum of Months | 0.537366E+11 | 28797.89 | 24.17 | 17.28 | 0.188760E+11 | 11319.66 | 24.17 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168227E+10 | 1559.35 | 11-JAN-19:10 | 12.30 | 9.41 | 0.127243E+10 | 791.49 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.229192E+10 | 1858.22 | 27-FEB-19:10 | 15.73 | 11.89 | 0.117164E+10 | 866.61 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.379378E+10 | 1948.21 | 18-MAR-17:15 | 19.03 | 9.50 | 0.136762E+10 | 873.74 | 14-MAR-22:10 | 19.03 | 9.50 |
April | 0.417402E+10 | 2712.44 | 27-APR-15:10 | 27.20 | 17.22 | 0.141540E+10 | 997.99 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.487071E+10 | 3381.02 | 15-MAY-15:10 | 23.40 | 12.66 | 0.157384E+10 | 1007.40 | 15-MAY-21:00 | 12.80 | 11.20 |
June | 0.520572E+10 | 3926.03 | 28-JUN-15:10 | 26.10 | 15.67 | 0.159236E+10 | 1007.40 | 27-JUN-22:10 | 26.10 | 15.67 |
July | 0.612422E+10 | 4504.73 | 24-JUL-15:10 | 30.32 | 18.75 | 0.167983E+10 | 1007.40 | 10-JUL-22:10 | 30.32 | 18.75 |
August | 0.620894E+10 | 5147.31 | 10-AUG-15:10 | 30.37 | 18.88 | 0.168451E+10 | 1007.40 | 10-AUG-23:10 | 18.07 | 15.44 |
September | 0.499221E+10 | 3896.54 | 14-SEP-15:10 | 23.98 | 16.97 | 0.155170E+10 | 1007.40 | 11-SEP-22:10 | 23.98 | 16.97 |
October | 0.416544E+10 | 2192.16 | 04-OCT-10:50 | 18.62 | 11.03 | 0.143748E+10 | 959.89 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.292855E+10 | 1962.25 | 04-NOV-17:20 | 17.60 | 14.26 | 0.127302E+10 | 869.39 | 05-NOV-23:30 | 11.10 | 9.45 |
December | 0.192800E+10 | 1657.93 | 03-DEC-11:35 | 11.33 | 5.78 | 0.127294E+10 | 777.23 | 29-DEC-23:10 | 8.72 | 7.62 |
Annual Sum or Average | 0.483658E+11 | 0.172928E+11 | ||||||||
Minimum of Months | 0.168227E+10 | 1559.35 | 11.33 | 5.78 | 0.117164E+10 | 777.23 | 8.72 | 7.62 | ||
Maximum of Months | 0.620894E+10 | 5147.31 | 30.37 | 18.88 | 0.168451E+10 | 1007.40 | 30.32 | 18.75 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166687E+09 | 566.00 | 16-JAN-17:00 | 1.70 |
February | 69391964.07 | 653.64 | 19-FEB-06:00 | -5.6 |
March | 2397221.91 | 166.94 | 05-MAR-17:00 | 5.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 27070393.88 | 345.30 | 30-NOV-15:00 | 5.00 |
December | 0.144862E+09 | 685.59 | 26-DEC-10:20 | 0.03 |
Annual Sum or Average | 0.410408E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.166687E+09 | 685.59 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3191536.72 | 140.55 | 16-JAN-16:00 | 2.20 |
February | 2440211.93 | 115.89 | 19-FEB-17:55 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 551931.53 | 48.28 | 26-DEC-15:00 | 2.20 |
Annual Sum or Average | 6183680.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3191536.72 | 140.55 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 95635478.00 | 240.64 | 16-JAN-16:00 | 2.20 |
February | 48621053.81 | 233.32 | 19-FEB-06:00 | -5.6 |
March | 51597.42 | 10.82 | 05-MAR-16:50 | 5.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 1902572.51 | 51.19 | 12-NOV-17:57 | 3.30 |
December | 34094231.48 | 220.72 | 26-DEC-12:50 | 0.53 |
Annual Sum or Average | 0.180305E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 95635478.00 | 240.64 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.768320E+09 | 1982.87 | 16-JAN-16:11 | 2.03 |
February | 0.473505E+09 | 1970.36 | 13-FEB-16:11 | 0.60 |
March | 0.241288E+09 | 1952.70 | 05-MAR-16:11 | 5.93 |
April | 88275356.95 | 1866.85 | 19-APR-08:62 | 5.87 |
May | 17903297.47 | 1102.41 | 18-MAY-08:62 | 6.28 |
June | 3215499.21 | 951.45 | 08-JUN-08:03 | 13.98 |
July | 1588198.94 | 782.98 | 03-JUL-15:15 | 16.13 |
August | 2249706.18 | 967.30 | 01-AUG-08:04 | 11.85 |
September | 7518430.38 | 841.83 | 20-SEP-08:03 | 11.47 |
October | 0.105537E+09 | 1875.20 | 31-OCT-15:12 | 10.53 |
November | 0.421748E+09 | 1973.96 | 30-NOV-16:11 | 4.60 |
December | 0.697864E+09 | 1983.54 | 26-DEC-16:11 | 3.73 |
Annual Sum or Average | 0.282901E+10 | |||
Minimum of Months | 1588198.94 | 782.98 | 0.60 | |
Maximum of Months | 0.768320E+09 | 1983.54 | 16.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.864890E+09 | 1937.03 | 16-JAN-16:11 | 2.03 |
February | 0.584478E+09 | 1928.79 | 19-FEB-09:01 | -3.1 |
March | 0.318139E+09 | 1913.90 | 05-MAR-16:11 | 5.93 |
April | 0.117430E+09 | 1837.64 | 19-APR-08:62 | 5.87 |
May | 20071691.78 | 1063.14 | 18-MAY-08:62 | 6.28 |
June | 3333195.23 | 915.21 | 12-JUN-08:04 | 15.28 |
July | 1498420.18 | 812.15 | 25-JUL-08:05 | 15.18 |
August | 1512813.21 | 911.21 | 01-AUG-08:04 | 11.85 |
September | 8947427.54 | 850.52 | 10-SEP-08:04 | 14.68 |
October | 0.153629E+09 | 1838.90 | 31-OCT-15:12 | 10.53 |
November | 0.496337E+09 | 1926.72 | 30-NOV-16:11 | 4.60 |
December | 0.801060E+09 | 1935.93 | 26-DEC-16:11 | 3.73 |
Annual Sum or Average | 0.337133E+10 | |||
Minimum of Months | 1498420.18 | 812.15 | -3.1 | |
Maximum of Months | 0.864890E+09 | 1937.03 | 15.28 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36731990.41 | 554.90 | 07-JAN-16:11 | 2.60 |
February | 20967042.73 | 551.73 | 19-FEB-16:11 | 2.43 |
March | 1566536.37 | 507.59 | 05-MAR-16:11 | 5.93 |
April | 639659.20 | 262.14 | 19-APR-18:05 | 10.82 |
May | 273933.45 | 145.22 | 18-MAY-15:16 | 12.57 |
June | 78012.64 | 154.44 | 14-JUN-15:16 | 14.40 |
July | 28817.49 | 86.50 | 23-JUL-08:56 | 18.90 |
August | 84378.07 | 159.30 | 11-AUG-08:55 | 16.90 |
September | 279515.46 | 135.70 | 06-SEP-16:46 | 15.60 |
October | 991698.32 | 239.22 | 27-OCT-15:13 | 10.53 |
November | 5883035.13 | 541.41 | 30-NOV-16:11 | 4.60 |
December | 21448113.94 | 554.45 | 26-DEC-16:11 | 3.73 |
Annual Sum or Average | 88972733.20 | |||
Minimum of Months | 28817.49 | 86.50 | 2.43 | |
Maximum of Months | 36731990.41 | 554.90 | 18.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.771859E+09 | 1923.30 | 16-JAN-16:11 | 2.03 |
February | 0.474190E+09 | 1913.73 | 13-FEB-16:11 | 0.60 |
March | 0.231900E+09 | 1890.73 | 05-MAR-16:11 | 5.93 |
April | 82678418.21 | 1795.74 | 18-APR-08:62 | 4.50 |
May | 22477993.90 | 1072.09 | 18-MAY-08:62 | 6.28 |
June | 3152809.10 | 759.33 | 12-JUN-15:15 | 16.87 |
July | 1481947.24 | 850.92 | 03-JUL-15:15 | 16.13 |
August | 1359123.75 | 966.53 | 01-AUG-18:05 | 19.42 |
September | 8736325.41 | 1049.34 | 30-SEP-15:14 | 17.60 |
October | 0.108491E+09 | 1823.34 | 31-OCT-15:12 | 10.53 |
November | 0.421584E+09 | 1914.99 | 30-NOV-16:11 | 4.60 |
December | 0.701380E+09 | 1923.58 | 26-DEC-16:11 | 3.73 |
Annual Sum or Average | 0.282929E+10 | |||
Minimum of Months | 1359123.75 | 759.33 | 0.60 | |
Maximum of Months | 0.771859E+09 | 1923.58 | 19.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.871187E+09 | 1874.56 | 16-JAN-16:11 | 2.03 |
February | 0.585361E+09 | 1866.72 | 13-FEB-16:11 | 0.60 |
March | 0.306011E+09 | 1848.93 | 05-MAR-16:11 | 5.93 |
April | 0.108567E+09 | 1768.07 | 11-APR-15:11 | 10.60 |
May | 26379064.85 | 1050.08 | 18-MAY-08:62 | 6.28 |
June | 3154791.77 | 742.07 | 13-JUN-08:04 | 11.78 |
July | 1066261.39 | 770.39 | 26-JUL-08:05 | 14.50 |
August | 946287.51 | 625.58 | 16-AUG-08:05 | 15.87 |
September | 9840879.79 | 690.90 | 07-SEP-08:04 | 13.98 |
October | 0.155018E+09 | 1783.80 | 31-OCT-15:12 | 10.53 |
November | 0.493420E+09 | 1865.42 | 12-NOV-16:11 | 4.43 |
December | 0.802358E+09 | 1873.11 | 26-DEC-16:11 | 3.73 |
Annual Sum or Average | 0.336331E+10 | |||
Minimum of Months | 946287.51 | 625.58 | 0.60 | |
Maximum of Months | 0.871187E+09 | 1874.56 | 15.87 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30058663.50 | 451.17 | 16-JAN-16:00 | 2.20 |
February | 7909731.91 | 202.12 | 17-FEB-10:20 | 0.97 |
March | 52700.54 | 33.04 | 05-MAR-16:00 | 6.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 5365261.15 | 213.60 | 30-NOV-15:00 | 5.00 |
December | 38783758.93 | 502.34 | 26-DEC-14:50 | 2.03 |
Annual Sum or Average | 82170116.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.97 | |
Maximum of Months | 38783758.93 | 502.34 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116764E+10 | 2331.13 | 16-JAN-16:11 | 2.03 |
February | 0.761358E+09 | 2312.68 | 18-FEB-19:01 | -0.8 |
March | 0.440747E+09 | 2306.91 | 05-MAR-16:11 | 5.93 |
April | 0.184129E+09 | 2211.24 | 19-APR-08:62 | 5.87 |
May | 54750605.26 | 1902.85 | 18-MAY-08:62 | 6.28 |
June | 9355857.31 | 815.16 | 08-JUN-08:03 | 13.98 |
July | 1567133.52 | 821.44 | 04-JUL-08:04 | 12.98 |
August | 2002004.03 | 896.28 | 20-AUG-18:05 | 18.83 |
September | 21387742.07 | 914.03 | 27-SEP-08:63 | 9.08 |
October | 0.233423E+09 | 2231.19 | 31-OCT-15:12 | 10.53 |
November | 0.700649E+09 | 2319.87 | 30-NOV-16:11 | 4.60 |
December | 0.108188E+10 | 2333.69 | 26-DEC-16:11 | 3.73 |
Annual Sum or Average | 0.465889E+10 | |||
Minimum of Months | 1567133.52 | 815.16 | -0.8 | |
Maximum of Months | 0.116764E+10 | 2333.69 | 18.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128820E+10 | 2267.60 | 15-JAN-16:11 | 1.50 |
February | 0.901774E+09 | 2252.28 | 19-FEB-09:01 | -3.1 |
March | 0.548337E+09 | 2242.16 | 05-MAR-16:11 | 5.93 |
April | 0.228554E+09 | 2166.34 | 19-APR-08:62 | 5.87 |
May | 58004135.28 | 1848.55 | 18-MAY-08:62 | 6.28 |
June | 9547293.21 | 856.10 | 12-JUN-08:04 | 15.28 |
July | 1340882.62 | 691.46 | 03-JUL-08:04 | 13.48 |
August | 1648031.76 | 871.76 | 01-AUG-08:04 | 11.85 |
September | 25236351.56 | 1328.03 | 28-SEP-08:62 | 10.28 |
October | 0.312803E+09 | 2179.79 | 31-OCT-15:12 | 10.53 |
November | 0.794823E+09 | 2253.82 | 30-NOV-16:11 | 4.60 |
December | 0.120804E+10 | 2266.64 | 26-DEC-16:11 | 3.73 |
Annual Sum or Average | 0.537830E+10 | |||
Minimum of Months | 1340882.62 | 691.46 | -3.1 | |
Maximum of Months | 0.128820E+10 | 2267.60 | 15.28 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324913E+09 | 1297.66 | 16-JAN-16:11 | 2.03 |
February | 0.169923E+09 | 1283.01 | 16-FEB-16:11 | 2.80 |
March | 58279743.05 | 1259.27 | 05-MAR-16:11 | 5.93 |
April | 20978853.77 | 898.43 | 18-APR-08:62 | 4.50 |
May | 4689161.76 | 668.33 | 30-MAY-15:14 | 17.20 |
June | 1548092.06 | 577.25 | 14-JUN-15:14 | 14.40 |
July | 987377.65 | 594.46 | 09-JUL-18:04 | 18.30 |
August | 1232311.87 | 576.77 | 17-AUG-15:14 | 20.17 |
September | 2806923.90 | 624.48 | 03-SEP-18:04 | 17.62 |
October | 16919339.41 | 1036.05 | 27-OCT-15:12 | 10.53 |
November | 0.143089E+09 | 1293.35 | 30-NOV-16:11 | 4.60 |
December | 0.293332E+09 | 1301.20 | 26-DEC-16:11 | 3.73 |
Annual Sum or Average | 0.103870E+10 | |||
Minimum of Months | 987377.65 | 576.77 | 2.03 | |
Maximum of Months | 0.324913E+09 | 1301.20 | 20.17 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104349E+09 | 721.53 | 16-JAN-06:00 | -2.2 |
February | 45684054.60 | 1045.54 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 986592.84 | 121.51 | 30-NOV-15:00 | 5.00 |
December | 50980959.67 | 914.17 | 26-DEC-10:10 | 0.02 |
Annual Sum or Average | 0.202000E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.104349E+09 | 1045.54 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743717E+10 | 7163.56 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.671509E+10 | 7163.56 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.746010E+10 | 7163.56 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.718502E+10 | 7163.56 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.745007E+10 | 7163.56 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.721797E+10 | 7163.56 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.741712E+10 | 7163.56 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.746297E+10 | 7163.56 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.718788E+10 | 7163.56 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.743431E+10 | 7163.56 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.721224E+10 | 7163.56 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.741712E+10 | 7163.56 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.875971E+11 | 0.143105E+12 | ||||
Minimum of Months | 0.671509E+10 | 7163.56 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.746297E+10 | 7163.56 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.336569E+09 | 324.19 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.303891E+09 | 324.19 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.337607E+09 | 324.19 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.325158E+09 | 324.19 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.337153E+09 | 324.19 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.326649E+09 | 324.19 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.335662E+09 | 324.19 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.337736E+09 | 324.19 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.325288E+09 | 324.19 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.336440E+09 | 324.19 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.326390E+09 | 324.19 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.335662E+09 | 324.19 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.396421E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.303891E+09 | 324.19 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.337736E+09 | 324.19 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.389749E+09 | 375.41 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.351908E+09 | 375.41 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.390950E+09 | 375.41 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.376534E+09 | 375.41 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.390424E+09 | 375.41 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.378261E+09 | 375.41 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.388697E+09 | 375.41 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.391100E+09 | 375.41 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.376684E+09 | 375.41 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.389598E+09 | 375.41 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.377961E+09 | 375.41 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.388697E+09 | 375.41 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.459056E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.351908E+09 | 375.41 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.391100E+09 | 375.41 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.697327E+09 | 671.67 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.629623E+09 | 671.67 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.699476E+09 | 671.67 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.673684E+09 | 671.67 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.698536E+09 | 671.67 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.676774E+09 | 671.67 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.695446E+09 | 671.67 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.699745E+09 | 671.67 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.673953E+09 | 671.67 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.697058E+09 | 671.67 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.676237E+09 | 671.67 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.695446E+09 | 671.67 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.821331E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.629623E+09 | 671.67 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.699745E+09 | 671.67 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159843E+09 | 153.96 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.144324E+09 | 153.96 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.160336E+09 | 153.96 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.154423E+09 | 153.96 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.160120E+09 | 153.96 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.155132E+09 | 153.96 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.159412E+09 | 153.96 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.160397E+09 | 153.96 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.154485E+09 | 153.96 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.159781E+09 | 153.96 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.155009E+09 | 153.96 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.159412E+09 | 153.96 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.188267E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.144324E+09 | 153.96 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.160397E+09 | 153.96 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.297499E+09 | 286.55 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.268614E+09 | 286.55 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.298416E+09 | 286.55 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.287412E+09 | 286.55 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.298015E+09 | 286.55 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.288730E+09 | 286.55 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.296696E+09 | 286.55 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.298530E+09 | 286.55 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.287527E+09 | 286.55 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.297384E+09 | 286.55 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.288501E+09 | 286.55 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.296696E+09 | 286.55 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.350402E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.268614E+09 | 286.55 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.298530E+09 | 286.55 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.640044E+09 | 767.68 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.544555E+09 | 767.68 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.565058E+09 | 767.68 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.491276E+09 | 767.68 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.468516E+09 | 767.68 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.417465E+09 | 767.68 | 01-JUN-19:00 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.445823E+09 | 767.68 | 10-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.482123E+09 | 767.68 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.529864E+09 | 767.68 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.595653E+09 | 767.68 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.606918E+09 | 767.68 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.642935E+09 | 767.68 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.643023E+10 | 0.143405E+11 | ||||
Minimum of Months | 0.417465E+09 | 767.68 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.642935E+09 | 767.68 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648396E+10 | 6458.51 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.580284E+10 | 6458.51 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.639713E+10 | 6458.51 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.608904E+10 | 6458.51 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.626007E+10 | 6458.51 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.601904E+10 | 6458.51 | 01-JUN-19:00 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.621831E+10 | 6458.51 | 10-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.629238E+10 | 6458.51 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.614038E+10 | 6458.51 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.641605E+10 | 6458.51 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.626757E+10 | 6458.51 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.647580E+10 | 6458.51 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.748626E+11 | 0.148998E+12 | ||||
Minimum of Months | 0.580284E+10 | 6458.51 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.648396E+10 | 6458.51 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65789991.58 | 59.53 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 59414784.75 | 59.53 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 65267117.48 | 59.53 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 63743496.62 | 59.53 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 65528554.53 | 59.53 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 63237765.93 | 59.53 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 66042856.93 | 59.53 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 65267117.48 | 59.53 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 63760640.03 | 59.53 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 65781419.88 | 59.53 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 63490631.27 | 59.53 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 66051428.64 | 59.53 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.773376E+09 | 0.256575E+10 | ||||
Minimum of Months | 59414784.75 | 59.53 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 66051428.64 | 59.53 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.109776E+10 | 1057.37 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.991179E+09 | 1057.37 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.110115E+10 | 1057.37 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.106054E+10 | 1057.37 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.109967E+10 | 1057.37 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.106541E+10 | 1057.37 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.109480E+10 | 1057.37 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.110157E+10 | 1057.37 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.106097E+10 | 1057.37 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.109734E+10 | 1057.37 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.106456E+10 | 1057.37 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.109480E+10 | 1057.37 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.129297E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.991179E+09 | 1057.37 | 0.00 | 0.00 | |
Maximum of Months | 0.110157E+10 | 1057.37 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104684E+09 | 94.72 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 94540036.54 | 94.72 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.103852E+09 | 94.72 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.101428E+09 | 94.72 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.104268E+09 | 94.72 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.100623E+09 | 94.72 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.105087E+09 | 94.72 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.103852E+09 | 94.72 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.101455E+09 | 94.72 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.104671E+09 | 94.72 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.101025E+09 | 94.72 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.105100E+09 | 94.72 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.123059E+10 | 0.261953E+10 | ||||
Minimum of Months | 94540036.54 | 94.72 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.105100E+09 | 94.72 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104672E+09 | 94.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 94528959.80 | 94.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.103840E+09 | 94.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.101416E+09 | 94.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.104256E+09 | 94.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.100611E+09 | 94.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.105074E+09 | 94.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.103840E+09 | 94.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.101443E+09 | 94.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.104658E+09 | 94.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.101014E+09 | 94.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.105088E+09 | 94.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.123044E+10 | 0.261922E+10 | ||||
Minimum of Months | 94528959.80 | 94.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.105088E+09 | 94.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 65807981.74 | 59.54 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 59431031.62 | 59.54 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 65284964.65 | 59.54 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 63760927.16 | 59.54 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 65546473.20 | 59.54 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 63255058.18 | 59.54 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 66060916.23 | 59.54 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 65284964.65 | 59.54 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 63778075.26 | 59.54 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 65799407.69 | 59.54 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 63507992.67 | 59.54 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 66069490.28 | 59.54 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.773587E+09 | 0.256645E+10 | ||||
Minimum of Months | 59431031.62 | 59.54 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 66069490.28 | 59.54 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129720E+10 | 1348.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.113501E+10 | 1348.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.121616E+10 | 1348.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.110922E+10 | 1348.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.110127E+10 | 1348.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.102483E+10 | 1348.12 | 01-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.106884E+10 | 1348.12 | 10-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.111985E+10 | 1348.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.115044E+10 | 1348.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.124657E+10 | 1348.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.124504E+10 | 1348.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.130135E+10 | 1348.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.140158E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.102483E+10 | 1348.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.130135E+10 | 1348.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129720E+10 | 1348.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.113501E+10 | 1348.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.121616E+10 | 1348.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.110922E+10 | 1348.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.110127E+10 | 1348.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.102483E+10 | 1348.12 | 01-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.106884E+10 | 1348.12 | 10-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.111985E+10 | 1348.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.115044E+10 | 1348.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.124657E+10 | 1348.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.124504E+10 | 1348.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.130135E+10 | 1348.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.140158E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.102483E+10 | 1348.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.130135E+10 | 1348.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.735117E+09 | 708.07 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.663744E+09 | 708.07 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.737383E+09 | 708.07 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.710193E+09 | 708.07 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.736392E+09 | 708.07 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.713450E+09 | 708.07 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.733135E+09 | 708.07 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.737666E+09 | 708.07 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.710477E+09 | 708.07 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.734834E+09 | 708.07 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.712884E+09 | 708.07 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.733135E+09 | 708.07 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.865841E+10 | 0.424019E+12 | ||||
Minimum of Months | 0.663744E+09 | 708.07 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.737666E+09 | 708.07 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.116181E+10 | 1119.06 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.104901E+10 | 1119.06 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.116539E+10 | 1119.06 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.112242E+10 | 1119.06 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.116383E+10 | 1119.06 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.112757E+10 | 1119.06 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.115868E+10 | 1119.06 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.116584E+10 | 1119.06 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.112287E+10 | 1119.06 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.116136E+10 | 1119.06 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.112667E+10 | 1119.06 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.115868E+10 | 1119.06 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136841E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.104901E+10 | 1119.06 | 0.00 | 0.00 | |
Maximum of Months | 0.116584E+10 | 1119.06 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.743717E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.671509E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.746010E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.718502E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.745007E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.721797E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.741712E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.746297E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.718788E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.743431E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.721224E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.741712E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.875971E+11 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.671509E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.746297E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.336569E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551140E+09 |
February | 0.179968E+10 | 0.303891E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457137E+09 |
March | 0.199990E+10 | 0.337607E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426599E+09 |
April | 0.192973E+10 | 0.325158E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1280534.33 | 0.342332E+09 |
May | 0.199475E+10 | 0.337153E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177931.56 | 0.291859E+09 |
June | 0.193394E+10 | 0.326649E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 881917.74 | 0.210583E+09 |
July | 0.199054E+10 | 0.335662E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6309694.84 | 0.174124E+09 |
August | 0.199896E+10 | 0.337736E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13762511.44 | 0.147152E+09 |
September | 0.192879E+10 | 0.325288E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 110147.19 | 0.227879E+09 |
October | 0.199148E+10 | 0.336440E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330734E+09 |
November | 0.192552E+10 | 0.326390E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416389E+09 |
December | 0.199054E+10 | 0.335662E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520298E+09 |
Annual Sum or Average | 0.234744E+11 | 0.396421E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22522737.10 | 0.409623E+10 |
Minimum of Months | 0.179968E+10 | 0.303891E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147152E+09 |
Maximum of Months | 0.199990E+10 | 0.337736E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13762511.44 | 0.551140E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.389749E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214459E+09 |
February | 0.208403E+10 | 0.351908E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177586E+09 |
March | 0.231589E+10 | 0.390950E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166164E+09 |
April | 0.223463E+10 | 0.376534E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1071571.25 | 0.132989E+09 |
May | 0.230993E+10 | 0.390424E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 649387.33 | 0.112773E+09 |
June | 0.223950E+10 | 0.378261E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278535.11 | 79970965.01 |
July | 0.230505E+10 | 0.388697E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4609668.83 | 64106013.11 |
August | 0.231480E+10 | 0.391100E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8701178.01 | 55009623.09 |
September | 0.223354E+10 | 0.376684E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 588230.55 | 86092075.48 |
October | 0.230614E+10 | 0.389598E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128410E+09 |
November | 0.222975E+10 | 0.377961E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163351E+09 |
December | 0.230505E+10 | 0.388697E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202395E+09 |
Annual Sum or Average | 0.271834E+11 | 0.459056E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16898571.07 | 0.158331E+10 |
Minimum of Months | 0.208403E+10 | 0.351908E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55009623.09 |
Maximum of Months | 0.231589E+10 | 0.391100E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8701178.01 | 0.214459E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.697327E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525209E+09 |
February | 0.440737E+09 | 0.629623E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442406E+09 |
March | 0.489771E+09 | 0.699476E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432432E+09 |
April | 0.472586E+09 | 0.673684E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1269733.40 | 0.358670E+09 |
May | 0.488511E+09 | 0.698536E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73088.29 | 0.317736E+09 |
June | 0.473617E+09 | 0.676774E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 553170.91 | 0.237221E+09 |
July | 0.487480E+09 | 0.695446E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5430708.44 | 0.190627E+09 |
August | 0.489542E+09 | 0.699745E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12032531.59 | 0.163968E+09 |
September | 0.472357E+09 | 0.673953E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95995.71 | 0.250443E+09 |
October | 0.487709E+09 | 0.697058E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353690E+09 |
November | 0.471555E+09 | 0.676237E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423619E+09 |
December | 0.487480E+09 | 0.695446E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502137E+09 |
Annual Sum or Average | 0.574883E+10 | 0.821331E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19455228.33 | 0.419816E+10 |
Minimum of Months | 0.440737E+09 | 0.629623E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163968E+09 |
Maximum of Months | 0.489771E+09 | 0.699745E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12032531.59 | 0.525209E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.159843E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289590E+09 |
February | 0.339028E+09 | 0.144324E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238105E+09 |
March | 0.376747E+09 | 0.160336E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219147E+09 |
April | 0.363528E+09 | 0.154423E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1810710.53 | 0.171421E+09 |
May | 0.375778E+09 | 0.160120E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1442087.17 | 0.140881E+09 |
June | 0.364321E+09 | 0.155132E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2539379.05 | 96780465.06 |
July | 0.374985E+09 | 0.159412E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8056048.76 | 74695324.03 |
August | 0.376571E+09 | 0.160397E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14400005.78 | 63516056.39 |
September | 0.363352E+09 | 0.154485E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1538670.50 | 0.103636E+09 |
October | 0.375161E+09 | 0.159781E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10108.34 | 0.164097E+09 |
November | 0.362735E+09 | 0.155009E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2329.21 | 0.217224E+09 |
December | 0.374985E+09 | 0.159412E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272622E+09 |
Annual Sum or Average | 0.442217E+10 | 0.188267E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29799339.34 | 0.205171E+10 |
Minimum of Months | 0.339028E+09 | 0.144324E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63516056.39 |
Maximum of Months | 0.376747E+09 | 0.160397E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14400005.78 | 0.289590E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.297499E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809462E+09 |
February | 0.139600E+10 | 0.268614E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674436E+09 |
March | 0.155131E+10 | 0.298416E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640989E+09 |
April | 0.149688E+10 | 0.287412E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 1327473.28 | 0.518789E+09 |
May | 0.154732E+10 | 0.298015E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 98974.38 | 0.445370E+09 |
June | 0.150015E+10 | 0.288730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 755335.64 | 0.326548E+09 |
July | 0.154405E+10 | 0.296696E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 7415700.66 | 0.260404E+09 |
August | 0.155059E+10 | 0.298530E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 16430168.76 | 0.224061E+09 |
September | 0.149615E+10 | 0.287527E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 131145.45 | 0.345998E+09 |
October | 0.154478E+10 | 0.297384E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507804E+09 |
November | 0.149361E+10 | 0.288501E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632678E+09 |
December | 0.154405E+10 | 0.296696E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769120E+09 |
Annual Sum or Average | 0.182090E+11 | 0.350402E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 26158798.17 | 0.615566E+10 |
Minimum of Months | 0.139600E+10 | 0.268614E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224061E+09 |
Maximum of Months | 0.155131E+10 | 0.298530E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 16430168.76 | 0.809462E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.640044E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122990E+10 |
February | 0.236489E+11 | 0.544555E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101913E+10 |
March | 0.262800E+11 | 0.565058E+09 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951574E+09 |
April | 0.253579E+11 | 0.491276E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5596880.53 | 0.752978E+09 |
May | 0.262123E+11 | 0.468516E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4411140.11 | 0.625909E+09 |
June | 0.254132E+11 | 0.417465E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9452315.72 | 0.432439E+09 |
July | 0.261570E+11 | 0.445823E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31586236.11 | 0.333462E+09 |
August | 0.262677E+11 | 0.482123E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55117469.83 | 0.285656E+09 |
September | 0.253456E+11 | 0.529864E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2703230.30 | 0.471785E+09 |
October | 0.261693E+11 | 0.595653E+09 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728543E+09 |
November | 0.253025E+11 | 0.606918E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934523E+09 |
December | 0.261570E+11 | 0.642935E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116017E+10 |
Annual Sum or Average | 0.308468E+12 | 0.643023E+10 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108867E+09 | 0.892607E+10 |
Minimum of Months | 0.236489E+11 | 0.417465E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285656E+09 |
Maximum of Months | 0.262800E+11 | 0.642935E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55117469.83 | 0.122990E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.648396E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360915E+10 |
February | 0.702046E+11 | 0.580284E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300401E+10 |
March | 0.780153E+11 | 0.639713E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283366E+10 |
April | 0.752779E+11 | 0.608904E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15765807.13 | 0.227617E+10 |
May | 0.778146E+11 | 0.626007E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9555198.28 | 0.193260E+10 |
June | 0.754422E+11 | 0.601904E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19327703.56 | 0.138051E+10 |
July | 0.776503E+11 | 0.621831E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74614842.06 | 0.109680E+10 |
August | 0.779788E+11 | 0.629238E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139163E+09 | 0.949002E+09 |
September | 0.752414E+11 | 0.614038E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7864363.75 | 0.148148E+10 |
October | 0.776868E+11 | 0.641605E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221209E+10 |
November | 0.751137E+11 | 0.626757E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278095E+10 |
December | 0.776503E+11 | 0.647580E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341965E+10 |
Annual Sum or Average | 0.915726E+12 | 0.748626E+11 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266291E+09 | 0.269761E+11 |
Minimum of Months | 0.702046E+11 | 0.580284E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949002E+09 |
Maximum of Months | 0.780153E+11 | 0.648396E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139163E+09 | 0.360915E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313665E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261512E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244301E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285729.72 | 0.194795E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 698043.36 | 0.162648E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1703265.36 | 0.111410E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7015694.19 | 83266928.23 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13495449.22 | 68632286.99 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 936596.29 | 0.118882E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1946.30 | 0.185856E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237819E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296279E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25136724.45 | 0.227907E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68632286.99 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13495449.22 | 0.313665E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311698E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258578E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241194E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1316105.71 | 0.193542E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 291493.70 | 0.165721E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1133538.75 | 0.116388E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5779418.78 | 91757918.27 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12333126.01 | 74071958.02 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 355631.41 | 0.122478E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183243E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235842E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293928E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21209314.36 | 0.228844E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74071958.02 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12333126.01 | 0.311698E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 65789991.58 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81789478.10 |
February | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80311551.57 |
March | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91567693.60 |
April | 0.00 | 63743496.62 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7049.40 | 79348917.28 |
May | 0.00 | 65528554.53 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71232652.09 |
June | 0.00 | 63237765.93 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55633531.49 |
July | 0.00 | 66042856.93 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187348.78 | 46957193.24 |
August | 0.00 | 65267117.48 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 670475.49 | 41441958.91 |
September | 0.00 | 63760640.03 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58232558.40 |
October | 0.00 | 65781419.88 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78147670.58 |
November | 0.00 | 63490631.27 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82952689.15 |
December | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85305786.69 |
Annual Sum or Average | 0.00 | 0.773376E+09 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 864873.67 | 0.852922E+09 |
Minimum of Months | 0.00 | 59414784.75 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41441958.91 |
Maximum of Months | 0.00 | 66051428.64 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 670475.49 | 91567693.60 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89326366.32 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73859891.05 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68800131.65 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 414968.95 | 54627217.91 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 134990.77 | 45713587.84 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 374499.27 | 31880803.65 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1758407.75 | 24287042.17 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3654685.95 | 20041341.86 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 191485.45 | 33544914.33 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52119933.30 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67768672.93 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84232988.55 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6529038.14 | 0.646203E+09 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20041341.86 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3654685.95 | 89326366.32 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313489E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261519E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245270E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1300919.36 | 0.196436E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 711457.46 | 0.163194E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1733106.22 | 0.112633E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7085382.31 | 83760153.58 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13492839.04 | 69235320.80 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 959223.79 | 0.119002E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2196.72 | 0.186493E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237786E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296083E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25285124.90 | 0.228490E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69235320.80 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13492839.04 | 0.313489E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311641E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258494E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241883E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1329069.43 | 0.194784E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 322454.00 | 0.164212E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1184950.89 | 0.116785E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5856339.21 | 89640313.70 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12215777.88 | 74508267.85 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 443919.28 | 0.120615E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183368E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235667E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293708E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21352510.69 | 0.228531E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74508267.85 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12215777.88 | 0.311641E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.109776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387170E+09 |
February | 0.348285E+10 | 0.991179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318594E+09 |
March | 0.387034E+10 | 0.110115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294095E+09 |
April | 0.373454E+10 | 0.106054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2143321.15 | 0.232452E+09 |
May | 0.386038E+10 | 0.109967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1290874.67 | 0.196445E+09 |
June | 0.374269E+10 | 0.106541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2425758.85 | 0.138478E+09 |
July | 0.385223E+10 | 0.109480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8367607.44 | 0.109835E+09 |
August | 0.386853E+10 | 0.110157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15918408.85 | 94723574.61 |
September | 0.373273E+10 | 0.106097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1112747.83 | 0.148779E+09 |
October | 0.385404E+10 | 0.109734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223379E+09 |
November | 0.372639E+10 | 0.106456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290972E+09 |
December | 0.385223E+10 | 0.109480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364543E+09 |
Annual Sum or Average | 0.454292E+11 | 0.129297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31258718.79 | 0.279947E+10 |
Minimum of Months | 0.348285E+10 | 0.991179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94723574.61 |
Maximum of Months | 0.387034E+10 | 0.110157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15918408.85 | 0.387170E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104684E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312563E+09 |
February | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260728E+09 |
March | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244027E+09 |
April | 0.293479E+09 | 0.101428E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1246788.24 | 0.195467E+09 |
May | 0.303504E+09 | 0.104268E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 652953.95 | 0.163860E+09 |
June | 0.293842E+09 | 0.100623E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632678.65 | 0.112695E+09 |
July | 0.303141E+09 | 0.105087E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6825643.86 | 84231998.77 |
August | 0.303685E+09 | 0.103852E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13168293.71 | 69310384.23 |
September | 0.293479E+09 | 0.101455E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 889653.28 | 0.119574E+09 |
October | 0.303322E+09 | 0.104671E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.32 | 0.185759E+09 |
November | 0.293661E+09 | 0.101025E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236890E+09 |
December | 0.303141E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295419E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123059E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24416965.03 | 0.228052E+10 |
Minimum of Months | 0.273974E+09 | 94540036.54 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69310384.23 |
Maximum of Months | 0.303685E+09 | 0.105100E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13168293.71 | 0.312563E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.104672E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311287E+09 |
February | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257881E+09 |
March | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240758E+09 |
April | 0.293479E+09 | 0.101416E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1237642.58 | 0.194408E+09 |
May | 0.303504E+09 | 0.104256E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 265001.80 | 0.168378E+09 |
June | 0.293842E+09 | 0.100611E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1063696.96 | 0.119370E+09 |
July | 0.303141E+09 | 0.105074E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5590043.58 | 94972972.26 |
August | 0.303685E+09 | 0.103840E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11935012.77 | 75480418.76 |
September | 0.293479E+09 | 0.101443E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 330562.70 | 0.124464E+09 |
October | 0.303322E+09 | 0.104658E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182991E+09 |
November | 0.293661E+09 | 0.101014E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234973E+09 |
December | 0.303141E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293241E+09 |
Annual Sum or Average | 0.357224E+10 | 0.123044E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20421960.39 | 0.229820E+10 |
Minimum of Months | 0.273974E+09 | 94528959.80 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75480418.76 |
Maximum of Months | 0.303685E+09 | 0.105088E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11935012.77 | 0.311287E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 65807981.74 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163561E+09 |
February | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136981E+09 |
March | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128129E+09 |
April | 0.293479E+09 | 63760927.16 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 640453.93 | 0.102049E+09 |
May | 0.303504E+09 | 65546473.20 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343110.98 | 84646911.03 |
June | 0.293842E+09 | 63255058.18 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 850219.29 | 58082593.26 |
July | 0.303141E+09 | 66060916.23 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3530524.66 | 43210046.99 |
August | 0.303685E+09 | 65284964.65 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6759398.03 | 35684190.04 |
September | 0.293479E+09 | 63778075.26 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 459061.22 | 61963621.98 |
October | 0.303322E+09 | 65799407.69 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 274.07 | 97705420.16 |
November | 0.293661E+09 | 63507992.67 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124489E+09 |
December | 0.303141E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154706E+09 |
Annual Sum or Average | 0.357224E+10 | 0.773587E+09 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12583042.18 | 0.119121E+10 |
Minimum of Months | 0.273974E+09 | 59431031.62 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35684190.04 |
Maximum of Months | 0.303685E+09 | 66069490.28 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6759398.03 | 0.163561E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.129720E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822554E+09 |
February | 0.415303E+11 | 0.113501E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682036E+09 |
March | 0.461508E+11 | 0.121616E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642074E+09 |
April | 0.445315E+11 | 0.110922E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3684636.01 | 0.516231E+09 |
May | 0.460320E+11 | 0.110127E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2191424.11 | 0.439750E+09 |
June | 0.446286E+11 | 0.102483E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4172532.16 | 0.314680E+09 |
July | 0.459349E+11 | 0.106884E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17462352.23 | 0.247388E+09 |
August | 0.461292E+11 | 0.111985E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34027411.12 | 0.211887E+09 |
September | 0.445099E+11 | 0.115044E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2656313.33 | 0.330324E+09 |
October | 0.459565E+11 | 0.124657E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496428E+09 |
November | 0.444343E+11 | 0.124504E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631720E+09 |
December | 0.459349E+11 | 0.130135E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777708E+09 |
Annual Sum or Average | 0.541708E+12 | 0.140158E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 64194668.97 | 0.611278E+10 |
Minimum of Months | 0.415303E+11 | 0.102483E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211887E+09 |
Maximum of Months | 0.461508E+11 | 0.130135E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34027411.12 | 0.822554E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.129720E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837289E+09 |
February | 0.415303E+11 | 0.113501E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696142E+09 |
March | 0.461508E+11 | 0.121616E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658835E+09 |
April | 0.445315E+11 | 0.110922E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3270455.33 | 0.531060E+09 |
May | 0.460320E+11 | 0.110127E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1707227.65 | 0.452681E+09 |
June | 0.446286E+11 | 0.102483E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3421013.59 | 0.325416E+09 |
July | 0.459349E+11 | 0.106884E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15830791.34 | 0.256587E+09 |
August | 0.461292E+11 | 0.111985E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31565795.84 | 0.220126E+09 |
September | 0.445099E+11 | 0.115044E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2063315.91 | 0.341791E+09 |
October | 0.459565E+11 | 0.124657E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512095E+09 |
November | 0.444343E+11 | 0.124504E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647317E+09 |
December | 0.459349E+11 | 0.130135E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792877E+09 |
Annual Sum or Average | 0.541708E+12 | 0.140158E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 57858599.67 | 0.627222E+10 |
Minimum of Months | 0.415303E+11 | 0.102483E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220126E+09 |
Maximum of Months | 0.461508E+11 | 0.130135E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31565795.84 | 0.837289E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.735117E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828591E+09 |
February | 0.369574E+10 | 0.663744E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690612E+09 |
March | 0.410691E+10 | 0.737383E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656896E+09 |
April | 0.396281E+10 | 0.710193E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1283604.22 | 0.532178E+09 |
May | 0.409635E+10 | 0.736392E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 77142.51 | 0.457529E+09 |
June | 0.397146E+10 | 0.713450E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 693990.44 | 0.336269E+09 |
July | 0.408770E+10 | 0.733135E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7265376.77 | 0.268782E+09 |
August | 0.410499E+10 | 0.737666E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16226066.81 | 0.231518E+09 |
September | 0.396089E+10 | 0.710477E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 106413.32 | 0.356149E+09 |
October | 0.408962E+10 | 0.734834E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521167E+09 |
November | 0.395417E+10 | 0.712884E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648322E+09 |
December | 0.408770E+10 | 0.733135E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787486E+09 |
Annual Sum or Average | 0.482060E+11 | 0.865841E+10 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 25652594.07 | 0.631550E+10 |
Minimum of Months | 0.369574E+10 | 0.663744E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231518E+09 |
Maximum of Months | 0.410691E+10 | 0.737666E+09 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16226066.81 | 0.828591E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.116181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688384E+09 |
February | 0.368610E+10 | 0.104901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572645E+09 |
March | 0.409620E+10 | 0.116539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546963E+09 |
April | 0.395248E+10 | 0.112242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1686747.50 | 0.456364E+09 |
May | 0.408566E+10 | 0.116383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73054.83 | 0.411087E+09 |
June | 0.396110E+10 | 0.112757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670150.90 | 0.310993E+09 |
July | 0.407704E+10 | 0.115868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7077090.22 | 0.254592E+09 |
August | 0.409429E+10 | 0.116584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15832076.42 | 0.217182E+09 |
September | 0.395056E+10 | 0.112287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102227.43 | 0.320415E+09 |
October | 0.407896E+10 | 0.116136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436241E+09 |
November | 0.394385E+10 | 0.112667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528686E+09 |
December | 0.407704E+10 | 0.115868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648866E+09 |
Annual Sum or Average | 0.480803E+11 | 0.136841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25441347.31 | 0.539242E+10 |
Minimum of Months | 0.368610E+10 | 0.104901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217182E+09 |
Maximum of Months | 0.409620E+10 | 0.116584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15832076.42 | 0.688384E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 7163.56 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 7163.56 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 7163.56 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 7163.56 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 7163.56 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 7163.56 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 7163.56 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 7163.56 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 7163.56 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 7163.56 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 7163.56 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 7163.56 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 324.19 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 323.32 | 15-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 324.19 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 339.05 | 19-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 324.19 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 275.50 | 01-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 324.19 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 01-APR-17:00 | 243.92 | 19-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 324.19 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 | 05-MAY-16:00 | 206.18 | 11-MAY-04:00 |
June | 1169.53 | 01-JUN-00:10 | 324.19 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 | 28-JUN-17:00 | 158.10 | 01-JUN-04:30 |
July | 1169.53 | 01-JUL-00:10 | 324.19 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.55 | 24-JUL-15:00 | 134.73 | 19-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 324.19 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.31 | 10-AUG-16:51 | 139.13 | 01-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 324.19 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 14-SEP-16:52 | 169.91 | 27-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 324.19 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 190.58 | 13-OCT-05:00 |
November | 1169.53 | 01-NOV-00:10 | 324.19 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 264.96 | 11-NOV-07:10 |
December | 1169.53 | 01-DEC-00:10 | 324.19 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 291.31 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 324.19 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.73 | |||||
Maximum of Months | 1169.53 | 324.19 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 87.31 | 339.05 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 375.41 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 124.80 | 15-JAN-07:53 |
February | 1354.32 | 01-FEB-00:10 | 375.41 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 130.87 | 19-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 375.41 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 109.37 | 01-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 375.41 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 | 01-APR-16:00 | 96.56 | 19-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 375.41 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 05-MAY-16:00 | 83.94 | 11-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 375.41 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 28-JUN-17:00 | 64.28 | 15-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 375.41 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.73 | 24-JUL-15:00 | 54.33 | 07-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 375.41 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 | 29-AUG-16:00 | 55.03 | 01-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 375.41 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 22-SEP-16:00 | 69.67 | 27-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 375.41 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 78.37 | 13-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 375.41 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 103.75 | 11-NOV-08:00 |
December | 1354.32 | 01-DEC-00:10 | 375.41 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 112.44 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.33 | |||||
Maximum of Months | 1354.32 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 | 130.87 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 671.67 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 300.24 | 15-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 671.67 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 309.52 | 19-FEB-05:00 |
March | 286.42 | 01-MAR-00:10 | 671.67 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 273.88 | 01-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 671.67 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 01-APR-16:00 | 239.86 | 19-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 671.67 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 05-MAY-16:00 | 214.76 | 11-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 671.67 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.27 | 28-JUN-16:53 | 169.40 | 15-JUN-03:00 |
July | 286.42 | 01-JUL-00:10 | 671.67 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.00 | 24-JUL-15:00 | 143.22 | 07-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 671.67 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 | 10-AUG-16:52 | 144.41 | 21-AUG-05:00 |
September | 286.42 | 01-SEP-00:10 | 671.67 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 14-SEP-16:53 | 181.61 | 27-SEP-05:00 |
October | 286.42 | 01-OCT-23:10 | 671.67 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 198.80 | 13-OCT-05:00 |
November | 286.42 | 01-NOV-00:10 | 671.67 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 258.66 | 11-NOV-08:00 |
December | 286.42 | 01-DEC-00:10 | 671.67 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 269.97 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.22 | |||||
Maximum of Months | 286.42 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 | 309.52 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 153.96 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 170.17 | 15-JAN-07:57 |
February | 220.32 | 01-FEB-00:10 | 153.96 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 178.44 | 19-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 153.96 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 144.99 | 01-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 153.96 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.19 | 01-APR-16:00 | 128.37 | 19-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 153.96 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 | 05-MAY-16:00 | 108.51 | 11-MAY-03:30 |
June | 220.32 | 01-JUN-00:10 | 153.96 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 | 28-JUN-16:51 | 81.58 | 15-JUN-03:50 |
July | 220.32 | 01-JUL-00:10 | 153.96 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.74 | 24-JUL-15:00 | 66.82 | 19-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 153.96 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 | 10-AUG-17:00 | 67.58 | 01-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 153.96 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 22-SEP-16:00 | 89.42 | 27-SEP-05:00 |
October | 220.32 | 01-OCT-23:10 | 153.96 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 04-OCT-15:00 | 100.14 | 13-OCT-05:00 |
November | 220.32 | 01-NOV-00:10 | 153.96 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 04-NOV-15:00 | 139.44 | 11-NOV-07:40 |
December | 220.32 | 01-DEC-00:10 | 153.96 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 153.31 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 153.96 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.82 | |||||
Maximum of Months | 220.32 | 153.96 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 | 178.44 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 286.55 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 451.24 | 15-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 286.55 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 469.93 | 19-FEB-06:00 |
March | 907.20 | 01-MAR-00:10 | 286.55 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 390.79 | 01-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 286.55 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 45.46 | 27-APR-15:20 | 351.06 | 19-APR-05:00 |
May | 907.20 | 01-MAY-00:10 | 286.55 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 14.34 | 05-MAY-16:00 | 303.20 | 11-MAY-03:10 |
June | 907.20 | 01-JUN-00:10 | 286.55 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 38.60 | 28-JUN-17:00 | 238.64 | 15-JUN-04:00 |
July | 907.20 | 01-JUL-00:10 | 286.55 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 92.85 | 24-JUL-15:00 | 195.55 | 07-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 286.55 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 108.76 | 10-AUG-16:51 | 197.17 | 21-AUG-05:00 |
September | 907.20 | 01-SEP-00:10 | 286.55 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 14.35 | 14-SEP-16:52 | 257.61 | 27-SEP-05:00 |
October | 907.20 | 01-OCT-23:10 | 286.55 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 283.13 | 13-OCT-05:00 |
November | 907.20 | 01-NOV-00:10 | 286.55 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 377.13 | 11-NOV-08:00 |
December | 907.20 | 01-DEC-00:10 | 286.55 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 410.78 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 195.55 | ||||||
Maximum of Months | 907.20 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 108.76 | 469.93 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 767.68 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 714.76 | 15-JAN-07:55 |
February | 15368.40 | 01-FEB-00:10 | 767.68 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 749.61 | 19-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 767.68 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 612.17 | 01-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 767.68 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.14 | 01-APR-16:00 | 558.46 | 19-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 767.68 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.42 | 05-MAY-16:00 | 481.51 | 11-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 767.68 | 01-JUN-19:00 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.69 | 28-JUN-17:00 | 370.96 | 15-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 767.68 | 10-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.99 | 24-JUL-15:00 | 308.08 | 19-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 767.68 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.66 | 10-AUG-17:00 | 306.76 | 01-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 767.68 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.77 | 14-SEP-17:00 | 401.45 | 27-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 767.68 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 452.25 | 13-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 767.68 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 585.75 | 11-NOV-07:30 |
December | 15368.40 | 01-DEC-00:10 | 767.68 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 644.06 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 767.68 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.76 | |||||
Maximum of Months | 15368.40 | 767.68 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 240.66 | 749.61 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 6458.51 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2097.59 | 15-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 6458.51 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2170.86 | 19-FEB-05:00 |
March | 45622.98 | 01-MAR-00:10 | 6458.51 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1849.05 | 01-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 6458.51 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.44 | 01-APR-16:00 | 1662.00 | 19-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 6458.51 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.83 | 05-MAY-16:00 | 1441.90 | 11-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 6458.51 | 01-JUN-19:00 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.40 | 28-JUN-17:00 | 1120.56 | 15-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 6458.51 | 10-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 586.76 | 24-JUL-15:00 | 936.78 | 19-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 6458.51 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 657.67 | 10-AUG-17:00 | 934.65 | 01-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 6458.51 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.77 | 22-SEP-16:00 | 1214.15 | 27-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 6458.51 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1352.60 | 13-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 6458.51 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1761.95 | 11-NOV-08:00 |
December | 45622.98 | 01-DEC-00:10 | 6458.51 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1900.14 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.65 | |||||
Maximum of Months | 45622.98 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 657.67 | 2170.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.99 | 15-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 197.91 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 161.03 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:20 | 142.70 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 28-JUN-16:50 | 91.04 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 | 24-JUL-15:20 | 71.02 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 | 10-AUG-16:50 | 78.07 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 22-SEP-16:00 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 04-OCT-15:20 | 111.52 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.89 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 170.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 | 197.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.97 | 15-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 197.90 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 161.01 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:19 | 142.69 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 28-JUN-16:50 | 91.03 | 15-JUN-03:50 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 | 24-JUL-15:20 | 71.02 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.55 | 10-AUG-16:50 | 78.26 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 14-SEP-16:50 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 111.51 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.87 | 11-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 170.20 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 68.55 | 197.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 59.53 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 50.09 | 15-JAN-08:10 |
February | 0.00 | 01-FEB-00:10 | 59.53 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 53.32 | 09-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 59.53 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 50.39 | 01-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 59.53 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 | 27-APR-15:13 | 47.36 | 19-APR-05:30 |
May | 0.00 | 01-MAY-00:10 | 59.53 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 43.05 | 11-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 59.53 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 34.88 | 01-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 59.53 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 | 24-JUL-15:00 | 30.59 | 19-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 59.53 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 10-AUG-17:00 | 30.64 | 06-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 59.53 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 36.52 | 27-SEP-04:30 |
October | 0.00 | 01-OCT-00:10 | 59.53 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 41.14 | 13-OCT-05:00 |
November | 0.00 | 01-NOV-00:10 | 59.53 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 50.46 | 11-NOV-23:00 |
December | 0.00 | 01-DEC-00:10 | 59.53 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 50.44 | 06-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | |||||
Maximum of Months | 0.00 | 59.53 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 53.32 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 52.66 | 15-JAN-07:53 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 55.24 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 44.94 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27-APR-15:20 | 39.83 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 05-MAY-16:00 | 33.70 | 11-MAY-03:20 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 28-JUN-16:50 | 25.41 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.28 | 24-JUL-15:20 | 20.81 | 04-JUL-07:30 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 | 10-AUG-16:50 | 22.08 | 01-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 | 14-SEP-16:50 | 27.83 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 31.38 | 29-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 43.88 | 11-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 47.50 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 | 55.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.99 | 15-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 197.91 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 161.03 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:20 | 142.70 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 28-JUN-16:50 | 91.04 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 | 24-JUL-15:20 | 71.02 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 | 10-AUG-16:50 | 81.18 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 22-SEP-16:00 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 04-OCT-15:20 | 111.52 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.89 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 170.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 | 197.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.97 | 15-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 197.90 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 161.01 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:19 | 142.68 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.75 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 28-JUN-16:50 | 91.03 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 | 24-JUL-15:20 | 71.01 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.55 | 10-AUG-16:50 | 81.30 | 01-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 14-SEP-16:50 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 111.51 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.88 | 11-NOV-07:50 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 170.20 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 68.55 | 197.90 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1057.37 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 227.31 | 15-JAN-07:55 |
February | 2263.36 | 01-FEB-00:10 | 1057.37 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 238.34 | 19-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1057.37 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 193.73 | 01-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1057.37 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.38 | 01-APR-16:00 | 171.57 | 19-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1057.37 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51 | 05-MAY-16:00 | 149.57 | 11-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1057.37 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.89 | 28-JUN-17:00 | 113.74 | 15-JUN-03:00 |
July | 2263.36 | 01-JUL-00:10 | 1057.37 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.99 | 24-JUL-15:00 | 94.12 | 19-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1057.37 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.50 | 10-AUG-17:00 | 95.60 | 01-AUG-05:00 |
September | 2263.36 | 01-SEP-00:10 | 1057.37 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.99 | 22-SEP-16:00 | 122.13 | 27-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1057.37 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 136.30 | 13-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1057.37 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 186.32 | 11-NOV-07:20 |
December | 2263.36 | 01-DEC-00:10 | 1057.37 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 204.84 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1057.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.12 | ||||
Maximum of Months | 2263.36 | 1057.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.50 | 238.34 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.72 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.47 | 15-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.72 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 198.40 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.72 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 161.50 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.72 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 27-APR-15:20 | 143.16 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.72 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 05-MAY-16:00 | 121.22 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 94.72 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 | 28-JUN-16:50 | 91.48 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.72 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.93 | 24-JUL-15:20 | 71.45 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 94.72 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.18 | 10-AUG-16:50 | 76.91 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 94.72 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 22-SEP-16:00 | 100.15 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 94.72 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 04-OCT-15:20 | 111.97 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 94.72 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 155.36 | 11-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.72 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 170.69 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | |||||
Maximum of Months | 180.00 | 94.72 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 68.18 | 198.40 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 94.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.46 | 15-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 94.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 198.38 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 94.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 161.49 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 94.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 27-APR-15:20 | 143.15 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 94.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 05-MAY-16:00 | 121.21 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 94.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 | 28-JUN-16:50 | 91.47 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 94.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.87 | 24-JUL-15:20 | 74.55 | 11-JUL-19:55 |
August | 180.00 | 01-AUG-00:10 | 94.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.18 | 10-AUG-16:50 | 77.34 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 94.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 14-SEP-16:50 | 100.14 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 94.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 111.96 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 94.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 155.34 | 11-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 94.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 170.67 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.55 | |||||
Maximum of Months | 180.00 | 94.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 68.18 | 198.38 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 59.54 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 96.43 | 15-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 59.54 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 101.51 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 59.54 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 82.63 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 59.54 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | 27-APR-15:20 | 73.25 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 59.54 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 05-MAY-16:00 | 62.02 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 59.54 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 | 28-JUN-16:50 | 46.80 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 59.54 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 | 24-JUL-15:20 | 36.58 | 04-JUL-07:30 |
August | 180.00 | 01-AUG-00:10 | 59.54 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 | 10-AUG-16:50 | 40.16 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 59.54 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 22-SEP-16:00 | 51.24 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 59.54 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 | 04-OCT-15:20 | 57.29 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 59.54 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 79.49 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 59.54 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 87.33 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | |||||
Maximum of Months | 180.00 | 59.54 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 | 101.51 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1348.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 481.34 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 1348.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 493.42 | 19-FEB-06:20 |
March | 26988.77 | 01-MAR-00:10 | 1348.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 419.00 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 1348.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.56 | 01-APR-16:00 | 376.49 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 1348.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 05-MAY-16:00 | 326.94 | 11-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 1348.12 | 01-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.74 | 28-JUN-17:00 | 255.51 | 15-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 1348.12 | 10-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.47 | 24-JUL-15:00 | 211.25 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 1348.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.65 | 10-AUG-17:00 | 210.28 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 1348.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.00 | 14-SEP-17:00 | 274.71 | 27-SEP-04:20 |
October | 26988.77 | 01-OCT-23:10 | 1348.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 302.70 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 1348.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 402.26 | 11-NOV-08:00 |
December | 26988.77 | 01-DEC-00:10 | 1348.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 435.34 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1348.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.28 | |||||
Maximum of Months | 26988.77 | 1348.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 149.65 | 493.42 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1348.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 488.20 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 1348.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 499.21 | 19-FEB-06:20 |
March | 26988.77 | 01-MAR-00:10 | 1348.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 425.10 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 1348.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 | 01-APR-16:00 | 382.05 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 1348.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.48 | 05-MAY-16:00 | 331.26 | 11-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 1348.12 | 01-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.15 | 28-JUN-17:00 | 259.75 | 15-JUN-03:00 |
July | 26988.77 | 01-JUL-00:10 | 1348.12 | 10-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.42 | 24-JUL-15:00 | 214.65 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 1348.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.31 | 10-AUG-17:00 | 214.12 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 1348.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 | 14-SEP-17:00 | 279.35 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 1348.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 307.37 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 1348.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 408.93 | 11-NOV-08:00 |
December | 26988.77 | 01-DEC-00:10 | 1348.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 441.84 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 1348.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.12 | |||||
Maximum of Months | 26988.77 | 1348.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 145.31 | 499.21 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 708.07 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 461.33 | 15-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 708.07 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 480.33 | 19-FEB-06:00 |
March | 2401.70 | 01-MAR-00:10 | 708.07 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 399.65 | 01-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 708.07 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 45.06 | 27-APR-15:50 | 359.20 | 19-APR-05:00 |
May | 2401.70 | 01-MAY-00:10 | 708.07 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 13.33 | 05-MAY-16:00 | 310.44 | 11-MAY-03:00 |
June | 2401.70 | 01-JUN-00:10 | 708.07 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 37.93 | 28-JUN-16:51 | 244.64 | 15-JUN-04:00 |
July | 2401.70 | 01-JUL-00:10 | 708.07 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 93.28 | 24-JUL-15:00 | 200.73 | 07-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 708.07 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 109.44 | 10-AUG-16:51 | 202.38 | 21-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 708.07 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 13.28 | 22-SEP-16:00 | 263.97 | 27-SEP-05:00 |
October | 2401.70 | 01-OCT-23:10 | 708.07 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 289.96 | 13-OCT-05:00 |
November | 2401.70 | 01-NOV-00:10 | 708.07 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 385.76 | 11-NOV-08:00 |
December | 2401.70 | 01-DEC-00:10 | 708.07 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 420.02 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 708.07 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 200.73 | ||||||
Maximum of Months | 2401.70 | 708.07 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 109.44 | 480.33 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1119.06 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 403.23 | 15-JAN-07:57 |
February | 2395.44 | 01-FEB-00:10 | 1119.06 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 422.73 | 19-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1119.06 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 349.27 | 01-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1119.06 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.46 | 01-APR-16:00 | 309.96 | 19-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1119.06 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 05-MAY-16:00 | 280.24 | 11-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1119.06 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.03 | 28-JUN-17:00 | 219.05 | 15-JUN-03:00 |
July | 2395.44 | 01-JUL-00:10 | 1119.06 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.16 | 24-JUL-15:00 | 189.46 | 19-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1119.06 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.02 | 10-AUG-16:51 | 188.82 | 01-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1119.06 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 22-SEP-16:00 | 230.23 | 27-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1119.06 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 254.59 | 13-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1119.06 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 330.66 | 11-NOV-07:20 |
December | 2395.44 | 01-DEC-00:10 | 1119.06 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 363.43 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1119.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.82 | ||||
Maximum of Months | 2395.44 | 1119.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.02 | 422.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12634.24 | 11-JAN-19:10 | 35783.66 | 25470.49 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12458.58 | 01-FEB-21:00 | 8945.92 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12297.67 | 02-MAR-19:10 | 62621.41 | 44573.36 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12947.16 | 27-APR-18:10 | 62621.41 | 44573.36 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13018.20 | 14-MAY-10:35 | 7667.93 | 4775.64 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13596.62 | 28-JUN-18:10 | 62621.41 | 44573.36 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14075.13 | 24-JUL-18:10 | 53675.50 | 38205.74 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14413.04 | 10-AUG-18:10 | 53675.50 | 38205.74 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14363.29 | 10-SEP-10:35 | 7667.93 | 4775.64 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14184.00 | 07-OCT-10:35 | 7667.93 | 3979.81 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14005.43 | 04-NOV-10:35 | 7667.93 | 3979.81 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13347.89 | 01-DEC-21:00 | 8945.92 | 7163.56 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12297.67 | 7667.93 | 3979.81 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14413.04 | 62621.41 | 44573.36 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1093.13 | 20-JAN-11:50 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.00 |
February | 1207.90 | 08-FEB-11:50 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.69 |
March | 1551.56 | 02-MAR-13:30 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.57 |
April | 1942.62 | 27-APR-13:05 | 519.79 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 |
May | 1844.28 | 04-MAY-13:30 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 |
June | 1572.74 | 28-JUN-14:10 | 389.84 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 | 0.00 |
July | 2124.36 | 24-JUL-13:30 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 55.12 | 0.00 |
August | 2570.44 | 24-AUG-13:10 | 519.79 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 0.00 |
September | 2524.40 | 14-SEP-13:15 | 519.79 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
October | 2278.49 | 04-OCT-13:00 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.64 |
November | 1649.65 | 04-NOV-13:25 | 779.69 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 |
December | 1234.38 | 05-DEC-11:50 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1093.13 | 259.90 | 90.05 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2570.44 | 779.69 | 180.10 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 222.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1173.78 | 11-JAN-21:00 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.60 |
February | 1268.23 | 27-FEB-21:00 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.68 |
March | 1294.78 | 18-MAR-18:10 | 5417.28 | 1751.90 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
April | 1509.31 | 27-APR-18:10 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 13.58 | 0.00 |
May | 1492.28 | 04-MAY-18:10 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 0.00 |
June | 1552.66 | 28-JUN-18:10 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 0.00 |
July | 1619.47 | 24-JUL-18:10 | 6320.16 | 2002.18 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 0.00 |
August | 1656.15 | 10-AUG-18:10 | 6320.16 | 2002.18 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 0.00 |
September | 1549.62 | 14-SEP-18:10 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 |
October | 1429.80 | 04-OCT-18:10 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 |
November | 1302.20 | 04-NOV-18:10 | 6320.16 | 2043.89 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 |
December | 1181.60 | 05-DEC-21:00 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1173.78 | 1053.36 | 375.41 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1656.15 | 7373.52 | 2335.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 76.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18.85 | 11-JAN-21:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.92 |
February | 21.40 | 27-FEB-19:10 | 445.54 | 1194.08 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.61 |
March | 21.40 | 18-MAR-18:10 | 1145.66 | 3134.46 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.71 |
April | 581.16 | 27-APR-21:00 | 254.59 | 597.04 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 |
May | 770.01 | 05-MAY-21:00 | 254.59 | 597.04 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 |
June | 932.49 | 28-JUN-20:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 |
July | 1151.36 | 24-JUL-21:00 | 254.59 | 597.04 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
August | 1208.68 | 10-AUG-20:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 0.00 |
September | 895.39 | 14-SEP-21:00 | 254.59 | 597.04 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.46 |
October | 541.59 | 04-OCT-20:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.94 |
November | 208.71 | 06-NOV-22:00 | 254.59 | 597.04 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.30 |
December | 18.94 | 29-DEC-21:00 | 222.77 | 671.67 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18.85 | 222.77 | 597.04 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1208.68 | 1145.66 | 3134.46 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 152.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 464.23 | 11-JAN-22:00 | 195.84 | 136.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.80 |
February | 640.51 | 27-FEB-22:00 | 195.84 | 136.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.31 |
March | 637.80 | 10-MAR-22:00 | 195.84 | 136.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.31 |
April | 817.82 | 27-APR-18:10 | 1199.52 | 957.98 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 26.10 | 0.00 |
May | 855.49 | 06-MAY-10:35 | 146.88 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
June | 871.61 | 28-JUN-18:10 | 1199.52 | 957.98 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 0.00 |
July | 918.56 | 24-JUL-18:10 | 1028.16 | 821.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 0.00 |
August | 932.72 | 10-AUG-18:10 | 1028.16 | 821.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 50.46 | 0.00 |
September | 856.46 | 14-SEP-10:35 | 97.92 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 |
October | 761.31 | 05-OCT-10:35 | 97.92 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.80 |
November | 672.29 | 04-NOV-19:00 | 146.88 | 119.75 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 |
December | 430.48 | 29-DEC-22:00 | 195.84 | 136.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 430.48 | 97.92 | 85.53 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 932.72 | 1199.52 | 957.98 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 50.46 | 78.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36976.22 | 11-JAN-21:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 194.05 |
February | 37349.57 | 27-FEB-21:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 177.65 |
March | 37496.00 | 14-MAR-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 143.27 |
April | 38293.83 | 27-APR-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.02 |
May | 38238.88 | 04-MAY-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 |
June | 38469.67 | 28-JUN-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
July | 38743.26 | 24-JUL-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
August | 38833.39 | 10-AUG-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.74 | 0.00 |
September | 38363.36 | 14-SEP-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.92 |
October | 37937.81 | 04-OCT-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.63 |
November | 37280.42 | 02-NOV-20:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 168.78 |
December | 36871.80 | 29-DEC-21:00 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 223.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36871.80 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38833.39 | 705.60 | 286.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.74 | 223.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8341.79 | 08-JAN-11:35 | 10245.60 | 112.59 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.44 |
February | 9288.13 | 12-FEB-11:35 | 10245.60 | 112.59 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.15 |
March | 9648.30 | 14-MAR-15:40 | 8538.00 | 46.91 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.85 |
April | 10438.53 | 27-APR-18:10 | 83672.40 | 1695.82 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 92.24 | 0.00 |
May | 10229.23 | 04-MAY-18:10 | 83672.40 | 2106.49 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 | 0.00 |
June | 10488.75 | 28-JUN-18:10 | 83672.40 | 1050.87 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 91.00 | 0.00 |
July | 11008.12 | 24-JUL-18:10 | 71719.20 | 900.75 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 166.63 | 0.00 |
August | 11230.15 | 10-AUG-18:10 | 71719.20 | 1488.17 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 206.03 | 0.00 |
September | 11034.61 | 10-SEP-10:35 | 10245.60 | 112.59 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.24 |
October | 10400.05 | 07-OCT-10:35 | 10245.60 | 93.83 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.08 |
November | 9749.40 | 04-NOV-10:35 | 10245.60 | 93.83 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.33 |
December | 9243.87 | 02-DEC-11:35 | 10245.60 | 93.83 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8341.79 | 8538.00 | 46.91 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11230.15 | 83672.40 | 2106.49 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 206.03 | 556.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26398.17 | 11-JAN-22:00 | 40553.76 | 5740.90 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882.17 |
February | 27919.18 | 27-FEB-21:00 | 35484.54 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 801.35 |
March | 28239.92 | 14-MAR-20:00 | 35484.54 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.01 |
April | 31457.11 | 27-APR-18:10 | 248391.78 | 36218.46 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 216.88 | 0.00 |
May | 31187.83 | 04-MAY-18:10 | 248391.78 | 37836.85 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 0.00 |
June | 32181.99 | 28-JUN-18:10 | 248391.78 | 35521.84 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 200.66 | 0.00 |
July | 33325.68 | 24-JUL-18:10 | 212907.24 | 30219.08 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 424.09 | 0.00 |
August | 33898.97 | 10-AUG-18:10 | 212907.24 | 31715.92 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 538.21 | 0.00 |
September | 32182.87 | 14-SEP-18:10 | 248391.78 | 38922.29 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.66 |
October | 30323.30 | 04-OCT-18:10 | 248391.78 | 40186.29 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.45 |
November | 28338.54 | 04-NOV-18:10 | 212907.24 | 35163.01 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.97 |
December | 26488.79 | 05-DEC-21:00 | 35484.54 | 6458.51 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1298.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26398.17 | 35484.54 | 5740.90 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33898.97 | 248391.78 | 40186.29 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 538.21 | 1298.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 851.27 | 26-JAN-19:04 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.13 |
February | 2575.08 | 08-FEB-16:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.00 |
March | 2718.92 | 01-MAR-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.15 |
April | 2704.19 | 13-APR-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 |
May | 2810.99 | 14-MAY-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
June | 2521.26 | 30-JUN-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 |
July | 2554.10 | 26-JUL-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
August | 2553.53 | 18-AUG-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 |
September | 2510.36 | 14-SEP-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 |
October | 2724.33 | 04-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 |
November | 2448.27 | 04-NOV-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 |
December | 1340.59 | 05-DEC-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 851.27 | 378.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | |
Maximum of Months | 2810.99 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 835.27 | 03-JAN-19:04 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 |
February | 1978.30 | 26-FEB-16:12 | 324.00 | 187.52 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 |
March | 2372.23 | 01-MAR-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.71 |
April | 2502.70 | 25-APR-17:42 | 486.00 | 317.26 | 632.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 |
May | 2540.30 | 21-MAY-17:42 | 583.20 | 483.00 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.72 |
June | 2482.14 | 22-JUN-16:21 | 874.80 | 238.66 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
July | 2639.70 | 14-JUL-16:21 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 |
August | 2382.98 | 10-AUG-21:51 | 1260.00 | 444.17 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 |
September | 2475.93 | 22-SEP-16:11 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 0.00 |
October | 1994.14 | 07-OCT-18:01 | 819.00 | 662.94 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.94 |
November | 1840.33 | 05-NOV-15:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 |
December | 817.82 | 14-DEC-19:04 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 817.82 | 324.00 | 185.62 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2639.70 | 1260.00 | 662.94 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 103.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 80.57 | 08-JAN-15:20 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.13 |
February | 158.34 | 27-FEB-15:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 |
March | 224.67 | 18-MAR-13:40 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 |
April | 322.20 | 27-APR-13:15 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
May | 304.49 | 04-MAY-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 |
June | 237.81 | 28-JUN-13:20 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
July | 309.76 | 31-JUL-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 | 0.00 |
August | 388.30 | 24-AUG-13:20 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 0.00 |
September | 407.14 | 14-SEP-13:30 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 |
October | 406.82 | 04-OCT-13:00 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.53 |
November | 237.22 | 04-NOV-13:40 | 0.00 | 19.64 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 |
December | 136.55 | 06-DEC-15:05 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 80.57 | 0.00 | 16.67 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 407.14 | 0.00 | 33.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 41.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 690.20 | 12-JAN-09:02 | 216.00 | 157.19 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 |
February | 789.55 | 12-FEB-09:01 | 378.00 | 233.40 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 |
March | 813.04 | 28-MAR-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 |
April | 847.59 | 24-APR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 |
May | 877.05 | 14-MAY-21:51 | 970.20 | 354.28 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 |
June | 846.70 | 28-JUN-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 0.00 |
July | 866.75 | 30-JUL-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 | 0.00 |
August | 861.20 | 07-AUG-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
September | 818.65 | 12-SEP-15:12 | 583.20 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 0.00 |
October | 840.75 | 02-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 |
November | 738.70 | 19-NOV-09:02 | 216.00 | 133.37 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 |
December | 790.94 | 03-DEC-09:02 | 216.00 | 133.37 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 690.20 | 216.00 | 100.03 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 877.05 | 970.20 | 416.79 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 | 38.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 783.37 | 03-JAN-19:04 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.10 |
February | 1837.07 | 12-FEB-09:01 | 378.00 | 371.29 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.18 |
March | 2378.76 | 25-MAR-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.70 |
April | 2335.94 | 19-APR-15:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.95 |
May | 2521.40 | 14-MAY-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 |
June | 2271.20 | 30-JUN-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 |
July | 2317.14 | 10-JUL-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
August | 2321.83 | 30-AUG-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 0.00 |
September | 2312.94 | 15-SEP-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 |
October | 2416.77 | 04-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 |
November | 2109.35 | 04-NOV-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 |
December | 964.70 | 02-DEC-09:02 | 270.00 | 265.21 | 816.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 783.37 | 270.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2521.40 | 970.20 | 663.02 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 138.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 851.43 | 03-JAN-19:04 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 |
February | 974.40 | 25-FEB-09:02 | 270.00 | 265.18 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.27 |
March | 2049.43 | 25-MAR-08:62 | 270.00 | 265.18 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.02 |
April | 2121.53 | 25-APR-18:02 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.10 |
May | 2178.42 | 06-MAY-08:51 | 432.00 | 424.28 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 |
June | 2206.47 | 10-JUN-08:51 | 486.00 | 477.32 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 |
July | 2442.62 | 24-JUL-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 |
August | 2429.79 | 13-AUG-08:51 | 486.00 | 477.32 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 |
September | 2258.67 | 13-SEP-08:51 | 324.00 | 375.03 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 |
October | 2015.55 | 07-OCT-08:61 | 378.00 | 371.25 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.24 |
November | 1268.12 | 04-NOV-08:62 | 270.00 | 265.18 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.92 |
December | 793.13 | 14-DEC-19:04 | 970.20 | 590.02 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 793.13 | 270.00 | 265.18 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | |
Maximum of Months | 2442.62 | 970.20 | 590.02 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1289.09 | 11-JAN-22:00 | 2011.87 | 939.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.17 |
February | 1513.38 | 27-FEB-19:10 | 3520.78 | 1879.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.81 |
March | 1547.52 | 18-MAR-17:50 | 1508.90 | 704.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 |
April | 1793.65 | 27-APR-18:10 | 12322.72 | 6579.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 0.00 |
May | 1841.67 | 06-MAY-10:35 | 1508.90 | 587.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 |
June | 1920.70 | 28-JUN-18:10 | 12322.72 | 6579.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 | 0.00 |
July | 2029.20 | 24-JUL-18:10 | 10562.33 | 5639.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.01 | 0.00 |
August | 2054.53 | 10-AUG-18:10 | 10562.33 | 5639.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 | 0.00 |
September | 1920.65 | 15-SEP-10:35 | 1005.94 | 587.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.01 |
October | 1711.33 | 07-OCT-10:35 | 1508.90 | 587.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.06 |
November | 1541.17 | 04-NOV-17:20 | 1508.90 | 704.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 |
December | 1281.84 | 05-DEC-21:10 | 2011.87 | 939.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1281.84 | 1005.94 | 587.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2054.53 | 12322.72 | 6579.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 | 133.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 837.70 | 02-JAN-19:05 | 831.60 | 505.79 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.85 |
February | 2643.55 | 08-FEB-16:12 | 583.20 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.40 |
March | 2822.88 | 01-MAR-16:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.58 |
April | 2816.69 | 13-APR-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 |
May | 2922.44 | 14-MAY-18:01 | 819.00 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 |
June | 2590.96 | 30-JUN-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
July | 2608.83 | 12-JUL-15:11 | 680.40 | 185.64 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 |
August | 2613.37 | 28-AUG-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 | 0.00 |
September | 2618.17 | 03-SEP-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 |
October | 2828.31 | 04-OCT-18:01 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.49 |
November | 2598.12 | 04-NOV-15:11 | 378.00 | 218.80 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 |
December | 848.47 | 01-DEC-19:04 | 970.20 | 590.08 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 837.70 | 378.00 | 159.12 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2922.44 | 970.20 | 663.02 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 | 108.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 859.49 | 10-JAN-19:05 | 831.60 | 505.73 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.40 |
February | 1790.94 | 26-FEB-16:12 | 324.00 | 187.52 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.88 |
March | 2435.75 | 01-MAR-16:11 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.78 |
April | 2626.67 | 25-APR-17:42 | 486.00 | 317.26 | 632.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.38 |
May | 2694.80 | 21-MAY-17:42 | 583.20 | 483.00 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 |
June | 2578.05 | 22-JUN-16:21 | 874.80 | 238.66 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
July | 2724.25 | 14-JUL-16:21 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 |
August | 2542.88 | 06-AUG-21:51 | 1247.40 | 724.50 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 |
September | 2687.83 | 22-SEP-16:11 | 972.00 | 265.18 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
October | 2049.21 | 07-OCT-18:01 | 819.00 | 662.94 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.42 |
November | 1863.21 | 05-NOV-15:11 | 378.00 | 218.77 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.19 |
December | 794.23 | 01-DEC-16:14 | 680.40 | 185.62 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 794.23 | 324.00 | 185.62 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | |
Maximum of Months | 2724.25 | 1247.40 | 724.50 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1323.97 | 20-JAN-16:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.88 |
February | 1794.15 | 12-FEB-16:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.71 |
March | 1813.03 | 25-MAR-15:11 | 378.00 | 137.54 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.74 |
April | 1721.59 | 13-APR-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 |
May | 1836.13 | 14-MAY-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
June | 1731.06 | 01-JUN-18:02 | 831.60 | 317.95 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 |
July | 1708.24 | 26-JUL-15:11 | 680.40 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
August | 1670.62 | 11-AUG-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
September | 1692.92 | 15-SEP-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 |
October | 1807.64 | 04-OCT-18:01 | 970.20 | 370.95 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 |
November | 1601.05 | 04-NOV-18:01 | 819.00 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 |
December | 1610.99 | 03-DEC-19:02 | 585.00 | 297.71 | 593.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1323.97 | 378.00 | 116.70 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | |
Maximum of Months | 1836.13 | 970.20 | 416.79 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16943.34 | 11-JAN-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.28 |
February | 17361.10 | 27-FEB-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.68 |
March | 17387.57 | 10-MAR-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.98 |
April | 19302.98 | 27-APR-18:10 | 146938.85 | 5542.38 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 50.15 | 0.00 |
May | 19245.21 | 04-MAY-18:10 | 146938.85 | 5885.70 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 | 0.00 |
June | 19979.56 | 28-JUN-18:10 | 146938.85 | 5032.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 44.86 | 0.00 |
July | 20362.82 | 24-JUL-18:10 | 125947.58 | 4313.98 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 0.00 |
August | 20418.93 | 10-AUG-18:10 | 125947.58 | 4313.98 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 125.29 | 0.00 |
September | 19090.76 | 14-SEP-18:10 | 146938.85 | 7442.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 |
October | 17999.60 | 04-OCT-18:10 | 146938.85 | 8388.29 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.70 |
November | 17489.27 | 06-NOV-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.75 |
December | 16845.93 | 29-DEC-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16845.93 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20418.93 | 146938.85 | 8388.29 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 125.29 | 255.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17791.60 | 11-JAN-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.90 |
February | 18152.06 | 27-FEB-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.82 |
March | 18204.07 | 10-MAR-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.31 |
April | 19981.68 | 27-APR-18:10 | 146938.85 | 5542.38 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 45.19 | 0.00 |
May | 20199.54 | 05-MAY-21:10 | 53977.54 | 1797.49 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.63 |
June | 20626.56 | 28-JUN-21:10 | 53977.54 | 1797.49 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.87 |
July | 21156.46 | 24-JUL-21:10 | 53977.54 | 1797.49 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 |
August | 21187.78 | 10-AUG-21:10 | 53977.54 | 1797.49 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 |
September | 19673.39 | 14-SEP-18:10 | 146938.85 | 7442.98 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 |
October | 18680.06 | 04-OCT-18:10 | 146938.85 | 8388.29 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.85 |
November | 18267.53 | 06-NOV-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.57 |
December | 17706.25 | 29-DEC-23:10 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17706.25 | 26988.77 | 449.37 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21187.78 | 146938.85 | 8388.29 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 45.19 | 262.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25281.46 | 11-JAN-19:05 | 7471.97 | 2517.58 | 58418.22 | 59980.88 | 0.00 | 0.00 | 0.00 | 0.00 | 179.92 |
February | 26044.77 | 27-FEB-11:50 | 533.71 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 118.68 |
March | 26684.11 | 14-MAR-10:50 | 533.71 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 195.63 |
April | 27882.01 | 27-APR-10:40 | 1067.42 | 393.37 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 |
May | 28110.88 | 14-MAY-10:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 56.05 |
June | 28379.33 | 10-JUN-10:50 | 800.57 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 55.10 |
July | 28683.66 | 30-JUL-10:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 |
August | 28797.89 | 13-AUG-10:40 | 1601.14 | 472.05 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
September | 28217.40 | 10-SEP-10:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 81.94 |
October | 27263.32 | 07-OCT-10:50 | 800.57 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 141.51 |
November | 26988.10 | 04-NOV-10:50 | 800.57 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.16 |
December | 25619.79 | 03-DEC-11:50 | 800.57 | 236.02 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 192.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25281.46 | 533.71 | 196.69 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28797.89 | 7471.97 | 2517.58 | 58418.22 | 59980.88 | 0.00 | 0.00 | 0.00 | 1.08 | 195.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1559.35 | 11-JAN-19:10 | 7452.48 | 3978.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.35 |
February | 1858.22 | 27-FEB-19:10 | 3726.24 | 1989.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.91 |
March | 1948.21 | 18-MAR-17:15 | 3193.92 | 1492.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.85 |
April | 2712.44 | 27-APR-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 | 0.00 |
May | 3381.02 | 15-MAY-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 |
June | 3926.03 | 28-JUN-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.52 | 0.00 |
July | 4504.73 | 24-JUL-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 | 0.00 |
August | 5147.31 | 10-AUG-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.61 | 0.00 |
September | 3896.54 | 14-SEP-15:10 | 1330.80 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
October | 2192.16 | 04-OCT-10:50 | 532.32 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.84 |
November | 1962.25 | 04-NOV-17:20 | 1596.96 | 746.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.98 |
December | 1657.93 | 03-DEC-11:35 | 1596.96 | 746.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1559.35 | 532.32 | 310.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5147.31 | 7452.48 | 3978.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.61 | 152.84 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.297613E+12 | 188539.22 | 15-JAN-20:10 | 0.532008E+12 | 450040.63 | 16-JAN-19:10 |
February | 0.268713E+12 | 200298.67 | 27-FEB-20:10 | 0.455471E+12 | 443840.83 | 19-FEB-17:30 |
March | 0.296143E+12 | 201415.52 | 14-MAR-19:10 | 0.461887E+12 | 375651.90 | 05-MAR-19:10 |
April | 0.300603E+12 | 257738.32 | 27-APR-18:10 | 0.406623E+12 | 335359.00 | 10-APR-17:00 |
May | 0.324765E+12 | 240267.22 | 04-MAY-19:19 | 0.391030E+12 | 315111.91 | 01-MAY-17:00 |
June | 0.335063E+12 | 263019.52 | 28-JUN-19:10 | 0.362062E+12 | 313847.00 | 06-JUN-17:40 |
July | 0.375095E+12 | 281272.69 | 24-JUL-19:49 | 0.368889E+12 | 312517.92 | 03-JUL-17:00 |
August | 0.393386E+12 | 295220.81 | 10-AUG-19:30 | 0.367960E+12 | 312170.46 | 02-AUG-17:00 |
September | 0.331778E+12 | 237829.81 | 14-SEP-19:10 | 0.359890E+12 | 313500.22 | 26-SEP-17:00 |
October | 0.307765E+12 | 220426.68 | 04-OCT-19:00 | 0.395577E+12 | 317986.07 | 31-OCT-18:10 |
November | 0.287422E+12 | 198868.94 | 04-NOV-19:19 | 0.457853E+12 | 391168.19 | 12-NOV-17:40 |
December | 0.295316E+12 | 188190.40 | 25-DEC-20:19 | 0.533100E+12 | 448841.53 | 25-DEC-17:49 |
Annual Sum or Average | 0.381366E+13 | 0.509235E+13 | ||||
Minimum of Months | 0.268713E+12 | 188190.40 | 0.359890E+12 | 312170.46 | ||
Maximum of Months | 0.393386E+12 | 295220.81 | 0.533100E+12 | 450040.63 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.387691E+10 | 12721.50 | 30-JAN-11:30 | 0.00 | 0.00 |
February | 0.630474E+10 | 18079.43 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.110345E+11 | 25462.46 | 24-MAR-12:30 | 0.00 | 0.00 |
April | 0.163117E+11 | 29879.44 | 25-APR-12:09 | 0.00 | 0.00 |
May | 0.210797E+11 | 34554.33 | 24-MAY-12:30 | 0.00 | 0.00 |
June | 0.218618E+11 | 32125.66 | 19-JUN-12:09 | 0.00 | 0.00 |
July | 0.232520E+11 | 32390.76 | 05-JUL-10:30 | 0.00 | 0.00 |
August | 0.188583E+11 | 29260.34 | 06-AUG-12:30 | 0.00 | 0.00 |
September | 0.134192E+11 | 25577.33 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.865385E+10 | 21788.07 | 03-OCT-11:00 | 0.00 | 0.00 |
November | 0.428126E+10 | 13263.15 | 11-NOV-12:20 | 0.00 | 0.00 |
December | 0.331799E+10 | 10585.84 | 01-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.152252E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.331799E+10 | 10585.84 | 0.00 | 0.00 | |
Maximum of Months | 0.232520E+11 | 34554.33 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.378025E+11 | 0.163221E+11 | 0.140003E+12 | 0.331702E+11 | 0.476773E+11 | 0.329776E+10 | 0.00 | 0.857424E+09 | 0.00 | 0.00 | 0.705119E+10 | 0.770428E+10 | 0.00 |
February | 0.339771E+11 | 0.134562E+11 | 0.126445E+12 | 0.299602E+11 | 0.430533E+11 | 0.355384E+10 | 0.00 | 0.240356E+10 | 0.00 | 0.00 | 0.553414E+10 | 0.696183E+10 | 0.00 |
March | 0.374275E+11 | 0.131346E+11 | 0.140056E+12 | 0.331725E+11 | 0.477707E+11 | 0.438252E+10 | 0.00 | 0.550616E+10 | 0.00 | 0.00 | 0.325923E+10 | 0.770285E+10 | 0.00 |
April | 0.359655E+11 | 0.109407E+11 | 0.135446E+12 | 0.320996E+11 | 0.468411E+11 | 0.592884E+10 | 0.00 | 0.191041E+11 | 0.00 | 0.00 | 0.319920E+10 | 0.746489E+10 | 0.00 |
May | 0.369927E+11 | 0.971743E+10 | 0.140035E+12 | 0.331710E+11 | 0.491415E+11 | 0.725956E+10 | 0.00 | 0.340033E+11 | 0.00 | 0.00 | 0.299182E+10 | 0.770425E+10 | 0.00 |
June | 0.356262E+11 | 0.855157E+10 | 0.135537E+12 | 0.321018E+11 | 0.483782E+11 | 0.792258E+10 | 0.00 | 0.531634E+11 | 0.00 | 0.00 | 0.268953E+10 | 0.745689E+10 | 0.00 |
July | 0.368918E+11 | 0.922926E+10 | 0.139944E+12 | 0.331685E+11 | 0.509875E+11 | 0.894673E+10 | 0.00 | 0.809062E+11 | 0.00 | 0.00 | 0.356234E+10 | 0.771237E+10 | 0.00 |
August | 0.370532E+11 | 0.105961E+11 | 0.140067E+12 | 0.331723E+11 | 0.514157E+11 | 0.918047E+10 | 0.00 | 0.955869E+11 | 0.00 | 0.00 | 0.483795E+10 | 0.770438E+10 | 0.00 |
September | 0.361472E+11 | 0.119400E+11 | 0.135457E+12 | 0.320998E+11 | 0.481430E+11 | 0.755019E+10 | 0.00 | 0.468856E+11 | 0.00 | 0.00 | 0.244368E+10 | 0.746620E+10 | 0.00 |
October | 0.375813E+11 | 0.141684E+11 | 0.139992E+12 | 0.331700E+11 | 0.482697E+11 | 0.568881E+10 | 0.00 | 0.146928E+11 | 0.00 | 0.00 | 0.275206E+10 | 0.770294E+10 | 0.00 |
November | 0.365405E+11 | 0.153170E+11 | 0.135531E+12 | 0.321009E+11 | 0.461505E+11 | 0.345864E+10 | 0.00 | 0.387720E+10 | 0.00 | 0.00 | 0.338198E+10 | 0.744869E+10 | 0.00 |
December | 0.378130E+11 | 0.167413E+11 | 0.139944E+12 | 0.331691E+11 | 0.476267E+11 | 0.301110E+10 | 0.00 | 0.804067E+09 | 0.00 | 0.00 | 0.476479E+10 | 0.771243E+10 | 0.00 |
Annual Sum or Average | 0.439818E+12 | 0.150115E+12 | 0.164846E+13 | 0.390556E+12 | 0.575455E+12 | 0.701811E+11 | 0.00 | 0.357791E+12 | 0.00 | 0.00 | 0.464679E+11 | 0.907420E+11 | 0.00 |
Minimum of Months | 0.339771E+11 | 0.855157E+10 | 0.126445E+12 | 0.299602E+11 | 0.430533E+11 | 0.301110E+10 | 0.00 | 0.804067E+09 | 0.00 | 0.00 | 0.244368E+10 | 0.696183E+10 | 0.00 |
Maximum of Months | 0.378130E+11 | 0.167413E+11 | 0.140067E+12 | 0.331725E+11 | 0.514157E+11 | 0.918047E+10 | 0.00 | 0.955869E+11 | 0.00 | 0.00 | 0.705119E+10 | 0.771243E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.143133E+12 | 0.00 | 0.236957E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.103212E+12 | 0.00 | 0.215054E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.734912E+11 | 0.00 | 0.236372E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.351821E+11 | 0.00 | 0.224485E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.128443E+11 | 0.00 | 0.226208E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.144750E+10 | 0.00 | 0.213501E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.439911E+09 | 0.00 | 0.216628E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.462893E+09 | 0.00 | 0.215459E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.265169E+10 | 0.00 | 0.210267E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.220238E+11 | 0.00 | 0.221650E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.906990E+11 | 0.00 | 0.220063E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.148268E+12 | 0.00 | 0.233011E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.633856E+12 | 0.00 | 0.266965E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.439911E+09 | 0.00 | 0.210267E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.148268E+12 | 0.00 | 0.236957E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36244.21 | 02-JAN-20:10 | 9571.94 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 23857.89 | 02-JAN-07:19 | 25199.87 | 06-JAN-19:10 | 3254.16 | 07-JAN-16:19 | 0.00 | 01-JAN-00:10 |
February | 36244.21 | 01-FEB-20:10 | 9571.94 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 23857.89 | 01-FEB-07:19 | 25851.93 | 27-FEB-20:10 | 3660.58 | 27-FEB-16:40 | 0.00 | 01-FEB-00:10 |
March | 36244.21 | 01-MAR-20:10 | 9571.94 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 23857.89 | 13-MAR-06:19 | 25570.86 | 14-MAR-18:49 | 3597.96 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 36244.21 | 03-APR-19:10 | 9571.94 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 23857.69 | 04-APR-06:19 | 27056.98 | 27-APR-18:10 | 4410.12 | 01-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 36244.21 | 01-MAY-19:19 | 9571.94 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 23857.65 | 01-MAY-06:19 | 27785.95 | 08-MAY-20:10 | 4300.00 | 04-MAY-15:20 | 0.00 | 01-MAY-00:10 |
June | 36244.21 | 01-JUN-19:00 | 9571.94 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 23857.19 | 22-JUN-06:19 | 28564.99 | 01-JUN-20:40 | 4371.02 | 28-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 36244.21 | 10-JUL-19:00 | 9571.94 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 23857.24 | 10-JUL-06:19 | 28904.17 | 24-JUL-18:19 | 4424.53 | 31-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 36244.21 | 01-AUG-19:40 | 9571.94 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 23857.52 | 16-AUG-06:19 | 29774.72 | 10-AUG-21:00 | 4456.51 | 10-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 36244.21 | 01-SEP-19:10 | 9571.94 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 23857.89 | 25-SEP-06:19 | 27525.88 | 07-SEP-19:49 | 4330.75 | 14-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 36244.21 | 02-OCT-19:10 | 9571.94 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 23857.89 | 02-OCT-06:19 | 26248.82 | 06-OCT-18:49 | 3940.82 | 08-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 36244.21 | 01-NOV-19:10 | 9571.94 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 23857.89 | 01-NOV-06:19 | 24909.12 | 05-NOV-19:00 | 3799.49 | 04-NOV-15:20 | 0.00 | 01-NOV-00:10 |
December | 36244.21 | 01-DEC-20:10 | 9571.94 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 23857.89 | 01-DEC-07:19 | 25084.93 | 26-DEC-19:49 | 3218.24 | 31-DEC-09:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 36244.21 | 9571.94 | 88863.15 | 23857.19 | 24909.12 | 3218.24 | 0.00 | |||||||
Maximum of Months | 36244.21 | 9571.94 | 88863.15 | 23857.89 | 29774.72 | 4456.51 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 5404.52 | 11-JAN-19:10 | 0.00 | 0.00 | 8265.52 | 05-JAN-00:49 | 4738.67 | 12-JAN-19:10 | 0.00 | 01-JAN-00:10 |
February | 38097.48 | 27-FEB-15:00 | 0.00 | 0.00 | 8265.52 | 08-FEB-01:10 | 4738.51 | 09-FEB-19:10 | 0.00 | 01-FEB-00:10 |
March | 45802.29 | 18-MAR-16:10 | 0.00 | 0.00 | 8265.52 | 01-MAR-03:00 | 4738.49 | 23-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 84873.91 | 27-APR-18:10 | 0.00 | 0.00 | 8265.52 | 01-APR-12:50 | 4738.50 | 20-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 74589.29 | 05-MAY-15:20 | 0.00 | 0.00 | 8265.52 | 04-MAY-15:20 | 4738.00 | 04-MAY-06:00 | 0.00 | 01-MAY-00:10 |
June | 88381.40 | 28-JUN-18:10 | 0.00 | 0.00 | 8265.52 | 09-JUN-15:30 | 4738.60 | 08-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 105545.37 | 24-JUL-18:10 | 0.00 | 0.00 | 8265.52 | 06-JUL-15:00 | 4738.41 | 10-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 119579.94 | 10-AUG-18:10 | 0.00 | 0.00 | 8265.52 | 06-AUG-15:20 | 4738.54 | 10-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 83381.06 | 14-SEP-15:20 | 0.00 | 0.00 | 8265.52 | 08-SEP-16:10 | 4738.43 | 28-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 54292.89 | 04-OCT-15:20 | 0.00 | 0.00 | 1521.82 | 01-OCT-00:10 | 4738.50 | 05-OCT-18:10 | 0.00 | 01-OCT-00:10 |
November | 49102.47 | 04-NOV-15:20 | 0.00 | 0.00 | 8265.52 | 11-NOV-03:00 | 4738.74 | 15-NOV-19:10 | 0.00 | 01-NOV-00:10 |
December | 5103.36 | 02-DEC-09:09 | 0.00 | 0.00 | 8265.52 | 06-DEC-01:49 | 4738.13 | 28-DEC-19:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 5103.36 | 0.00 | 0.00 | 1521.82 | 4738.00 | 0.00 | ||||
Maximum of Months | 119579.94 | 0.00 | 0.00 | 8265.52 | 4738.74 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 188539.22 | 15-JAN-20:10 | 33471.51 | 84670.41 | 9571.94 | 19252.20 | 24853.93 | 2658.26 | 0.00 | 1018.99 | 0.00 |
February | 200298.67 | 27-FEB-20:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 25851.93 | 2955.67 | 0.00 | 13003.72 | 0.00 |
March | 201415.52 | 14-MAR-19:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 25069.83 | 3148.17 | 0.00 | 17042.48 | 0.00 |
April | 257738.32 | 27-APR-18:10 | 30409.56 | 77265.07 | 0.00 | 19090.86 | 27056.98 | 4347.79 | 0.00 | 84873.91 | 0.00 |
May | 240267.22 | 04-MAY-19:19 | 36244.21 | 86131.51 | 9571.94 | 19289.69 | 25007.51 | 4188.82 | 0.00 | 54457.56 | 0.00 |
June | 263019.52 | 28-JUN-19:10 | 34332.22 | 86131.51 | 0.00 | 19284.98 | 27426.10 | 4322.27 | 0.00 | 77917.84 | 0.00 |
July | 281272.69 | 24-JUL-19:49 | 36244.21 | 86131.51 | 9571.94 | 19289.54 | 27987.47 | 4355.98 | 0.00 | 83805.14 | 0.00 |
August | 295220.81 | 10-AUG-19:30 | 36244.21 | 86131.51 | 9571.94 | 19289.40 | 28535.73 | 4377.78 | 0.00 | 97185.06 | 0.00 |
September | 237829.81 | 14-SEP-19:10 | 36244.21 | 86131.51 | 9571.94 | 19286.46 | 25101.75 | 3999.81 | 0.00 | 51984.49 | 0.00 |
October | 220426.68 | 04-OCT-19:00 | 36244.21 | 86131.51 | 9571.94 | 19289.69 | 25071.64 | 3401.83 | 0.00 | 35022.06 | 0.00 |
November | 198868.94 | 04-NOV-19:19 | 30698.82 | 81748.21 | 9571.94 | 19188.43 | 23742.70 | 3405.34 | 0.00 | 25060.85 | 0.00 |
December | 188190.40 | 25-DEC-20:19 | 33471.51 | 84670.41 | 9571.94 | 19254.38 | 24983.86 | 2589.60 | 0.00 | 740.12 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 188190.40 | 30409.56 | 77265.07 | 0.00 | 19090.86 | 23742.70 | 2589.60 | 0.00 | 740.12 | 0.00 | |
Maximum of Months | 295220.81 | 36244.21 | 86131.51 | 9571.94 | 19289.69 | 28535.73 | 4377.78 | 0.00 | 97185.06 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 185507.66 | 16-JAN-16:19 | 0.00 | 239850.33 | 31-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 162873.37 | 18-FEB-16:19 | 0.00 | 240068.89 | 13-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 117165.68 | 05-MAR-16:19 | 0.00 | 239623.26 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 104176.87 | 19-APR-04:10 | 0.00 | 236477.36 | 04-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 67559.80 | 11-MAY-03:00 | 0.00 | 221014.53 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 24122.89 | 15-JUN-03:00 | 0.00 | 209348.62 | 01-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 11571.90 | 12-JUL-08:20 | 0.00 | 208440.02 | 05-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 11428.32 | 18-AUG-08:20 | 0.00 | 208013.92 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 38143.55 | 27-SEP-03:00 | 0.00 | 208610.51 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 62418.27 | 30-OCT-08:09 | 0.00 | 209493.91 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 135903.84 | 13-NOV-09:09 | 0.00 | 223698.67 | 29-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 167998.07 | 25-DEC-16:19 | 0.00 | 236560.28 | 28-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 11428.32 | 0.00 | 208013.92 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 185507.66 | 0.00 | 240068.89 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.76 | 1.33 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 21.73 | 2.50 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.76 | 1.33 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.30 | 0.17 | 22.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.74 | 1.17 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 21.81 | 3.00 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.30 | 1.33 | 22.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.74 | 4.00 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.75 | 6.67 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.72 | 5.83 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.83 | 21.74 | 17.83 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.76 | 6.67 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.82 | 0.17 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.06 | 0.67 | 22.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 22.15 | 2.00 | 22.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.15 | 2.67 | 22.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.87 | 0.33 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 22.11 | 6.00 | 22.11 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.15 | 2.67 | 22.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.81 | 0.67 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.75 | 2.33 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.83 | 3.67 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.33 | 21.79 | 8.33 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.83 | 3.67 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.76 | 1.33 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.85 | 1.83 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.88 | 4.00 | 21.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.80 | 3.50 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.04 | 0.17 | 22.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.83 | 21.84 | 10.83 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.04 | 4.00 | 22.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 21.73 | 2.17 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
February | 672.00 | 22.14 | 0.00 | 22.14 | 0.00 | 22.14 |
March | 744.00 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
April | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
May | 744.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
June | 720.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
July | 744.00 | 22.31 | 0.00 | 22.31 | 0.00 | 22.31 |
August | 744.00 | 22.50 | 0.00 | 22.50 | 0.00 | 22.50 |
September | 720.00 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
October | 744.00 | 22.92 | 0.00 | 22.92 | 0.00 | 22.92 |
November | 720.00 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
December | 744.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
Annual Sum or Average | 8760.00 | 22.37 | 0.00 | 22.37 | 0.00 | 22.37 |
Minimum of Months | 672.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
Maximum of Months | 744.00 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.03 | 236.00 | 21.02 | 236.00 | 21.02 |
February | 669.50 | 21.15 | 163.00 | 21.12 | 163.00 | 21.10 |
March | 730.67 | 21.27 | 19.00 | 21.26 | 19.00 | 21.26 |
April | 686.33 | 21.54 | 12.17 | 21.58 | 0.00 | 21.58 |
May | 687.83 | 21.83 | 22.50 | 21.89 | 0.00 | 21.89 |
June | 646.67 | 22.17 | 29.83 | 22.25 | 0.00 | 22.25 |
July | 503.17 | 22.49 | 139.50 | 22.80 | 0.00 | 22.80 |
August | 460.33 | 22.43 | 203.50 | 22.89 | 0.00 | 22.89 |
September | 553.67 | 21.98 | 111.33 | 22.31 | 0.00 | 22.31 |
October | 706.00 | 21.51 | 9.17 | 21.54 | 0.00 | 21.54 |
November | 714.83 | 21.10 | 53.33 | 21.11 | 49.00 | 21.10 |
December | 744.00 | 21.07 | 204.17 | 21.06 | 204.17 | 21.05 |
Annual Sum or Average | 7847.00 | 21.57 | 1203.50 | 21.66 | 671.17 | 21.62 |
Minimum of Months | 460.33 | 21.03 | 9.17 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 22.49 | 236.00 | 22.89 | 236.00 | 22.89 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.16 | 5.83 | 21.16 | 5.83 | 21.16 |
February | 672.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
March | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
April | 720.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
May | 744.00 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
June | 717.17 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
July | 714.17 | 22.41 | 2.67 | 22.42 | 0.00 | 22.42 |
August | 670.33 | 22.41 | 12.17 | 22.44 | 0.00 | 22.44 |
September | 703.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
October | 744.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
November | 720.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
December | 744.00 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
Annual Sum or Average | 8636.67 | 21.72 | 20.67 | 21.73 | 5.83 | 21.73 |
Minimum of Months | 670.33 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 22.41 | 12.17 | 22.44 | 5.83 | 22.44 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
February | 672.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
March | 744.00 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
April | 699.67 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
May | 657.17 | 23.68 | 0.00 | 23.68 | 0.00 | 23.68 |
June | 544.00 | 23.91 | 0.00 | 23.91 | 0.00 | 23.91 |
July | 237.17 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
August | 68.00 | 23.97 | 16.50 | 23.97 | 0.00 | 23.97 |
September | 339.00 | 23.79 | 0.00 | 23.79 | 0.00 | 23.79 |
October | 736.17 | 23.38 | 0.00 | 23.38 | 0.00 | 23.38 |
November | 712.83 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
December | 744.00 | 21.98 | 0.00 | 21.98 | 0.00 | 21.98 |
Annual Sum or Average | 6898.00 | 22.89 | 16.50 | 22.89 | 0.00 | 22.89 |
Minimum of Months | 68.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
Maximum of Months | 744.00 | 23.99 | 16.50 | 23.99 | 0.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 93.50 | 21.00 | 93.50 | 21.00 |
February | 672.00 | 21.00 | 93.17 | 21.00 | 93.17 | 21.00 |
March | 744.00 | 21.00 | 40.67 | 21.00 | 40.67 | 21.00 |
April | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
May | 744.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
June | 720.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
July | 744.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
August | 744.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
September | 720.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
October | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
November | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
December | 744.00 | 21.00 | 11.00 | 21.00 | 11.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.18 | 238.33 | 21.17 | 238.33 | 21.17 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.68 | 93.50 | 21.68 | 93.50 | 21.68 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 169.83 | 24.00 | 744.00 | 24.00 | 169.83 | 24.00 |
February | 171.67 | 24.00 | 672.00 | 24.00 | 171.67 | 24.00 |
March | 204.33 | 24.00 | 744.00 | 24.00 | 204.33 | 24.00 |
April | 240.50 | 24.00 | 720.00 | 24.00 | 240.50 | 24.00 |
May | 294.00 | 24.00 | 744.00 | 24.00 | 294.00 | 24.00 |
June | 310.33 | 24.00 | 720.00 | 24.00 | 310.33 | 24.00 |
July | 383.50 | 24.00 | 744.00 | 24.00 | 383.50 | 24.00 |
August | 465.83 | 24.00 | 744.00 | 24.00 | 465.83 | 24.00 |
September | 361.17 | 24.00 | 720.00 | 24.00 | 361.17 | 24.00 |
October | 269.67 | 24.00 | 744.00 | 24.00 | 269.67 | 24.00 |
November | 215.00 | 24.00 | 720.00 | 24.00 | 215.00 | 24.00 |
December | 173.67 | 24.00 | 744.00 | 24.00 | 173.67 | 24.00 |
Annual Sum or Average | 3259.50 | 24.00 | 8760.00 | 24.00 | 3259.50 | 24.00 |
Minimum of Months | 169.83 | 24.00 | 672.00 | 24.00 | 169.83 | 24.00 |
Maximum of Months | 465.83 | 24.00 | 744.00 | 24.00 | 465.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.19 | 9.00 | 21.18 | 9.00 | 21.18 |
February | 672.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
March | 743.50 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
April | 715.67 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
May | 741.67 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
June | 719.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
July | 712.33 | 21.87 | 5.00 | 21.87 | 0.33 | 21.87 |
August | 610.67 | 21.84 | 60.67 | 21.94 | 9.50 | 21.96 |
September | 642.50 | 21.78 | 31.50 | 21.83 | 0.00 | 21.83 |
October | 734.83 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
November | 716.17 | 21.31 | 2.33 | 21.32 | 0.33 | 21.32 |
December | 744.00 | 21.21 | 3.33 | 21.21 | 3.33 | 21.21 |
Annual Sum or Average | 8496.33 | 21.52 | 111.83 | 21.54 | 22.50 | 21.54 |
Minimum of Months | 610.67 | 21.19 | 0.00 | 21.18 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 21.87 | 60.67 | 21.94 | 9.50 | 21.96 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
February | 672.00 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
March | 744.00 | 21.98 | 0.00 | 21.98 | 0.00 | 21.98 |
April | 716.83 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
May | 733.17 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
June | 670.17 | 22.43 | 2.00 | 22.44 | 0.00 | 22.44 |
July | 596.50 | 22.49 | 34.00 | 22.56 | 1.00 | 22.56 |
August | 549.00 | 22.50 | 99.17 | 22.69 | 20.50 | 22.72 |
September | 627.50 | 22.43 | 27.67 | 22.48 | 0.00 | 22.48 |
October | 742.83 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
November | 720.00 | 21.87 | 0.83 | 21.87 | 0.83 | 21.88 |
December | 744.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
Annual Sum or Average | 8260.00 | 22.11 | 163.67 | 22.14 | 22.33 | 22.15 |
Minimum of Months | 549.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
Maximum of Months | 744.00 | 22.50 | 99.17 | 22.69 | 20.50 | 22.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.66 | 470.50 | 20.57 | 470.50 | 20.52 |
February | 672.00 | 20.90 | 268.33 | 20.79 | 268.33 | 20.73 |
March | 744.00 | 21.10 | 75.33 | 21.03 | 75.33 | 20.97 |
April | 719.17 | 21.35 | 3.50 | 21.34 | 3.50 | 21.34 |
May | 741.17 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
June | 717.17 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
July | 719.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
August | 712.17 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
September | 704.67 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
October | 744.00 | 21.26 | 5.83 | 21.25 | 5.83 | 21.24 |
November | 720.00 | 20.87 | 184.33 | 20.74 | 184.33 | 20.65 |
December | 744.00 | 20.73 | 383.00 | 20.61 | 383.00 | 20.56 |
Annual Sum or Average | 8681.33 | 21.23 | 1390.83 | 21.11 | 1390.83 | 21.03 |
Minimum of Months | 672.00 | 20.66 | 0.00 | 20.57 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.65 | 470.50 | 21.65 | 470.50 | 21.65 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 528.00 | 20.47 | 528.00 | 20.43 |
February | 672.00 | 20.73 | 366.17 | 20.62 | 366.17 | 20.57 |
March | 744.00 | 20.93 | 157.67 | 20.82 | 157.67 | 20.75 |
April | 717.17 | 21.27 | 14.33 | 21.25 | 14.33 | 21.23 |
May | 714.67 | 21.60 | 16.83 | 21.68 | 0.00 | 21.68 |
June | 687.33 | 21.81 | 11.33 | 21.86 | 0.00 | 21.86 |
July | 657.50 | 21.94 | 47.00 | 22.15 | 0.00 | 22.15 |
August | 702.00 | 21.93 | 15.50 | 22.00 | 0.00 | 22.00 |
September | 684.33 | 21.66 | 14.33 | 21.73 | 0.00 | 21.73 |
October | 744.00 | 21.12 | 22.17 | 21.09 | 22.17 | 21.06 |
November | 720.00 | 20.76 | 246.33 | 20.63 | 246.33 | 20.54 |
December | 744.00 | 20.61 | 515.00 | 20.52 | 515.00 | 20.48 |
Annual Sum or Average | 8531.00 | 21.23 | 1954.67 | 21.11 | 1849.67 | 21.00 |
Minimum of Months | 657.50 | 20.56 | 11.33 | 20.47 | 0.00 | 20.43 |
Maximum of Months | 744.00 | 21.94 | 528.00 | 22.15 | 528.00 | 22.15 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 125.33 | 20.93 | 125.33 | 20.87 |
February | 672.00 | 21.08 | 100.50 | 21.02 | 100.50 | 20.98 |
March | 744.00 | 21.21 | 5.00 | 21.21 | 5.00 | 21.21 |
April | 720.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
May | 744.00 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
June | 720.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
July | 743.83 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
August | 744.00 | 21.89 | 0.00 | 21.89 | 0.00 | 21.89 |
September | 720.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
October | 744.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
November | 720.00 | 21.14 | 24.17 | 21.12 | 24.17 | 21.09 |
December | 744.00 | 21.02 | 80.67 | 20.95 | 80.67 | 20.90 |
Annual Sum or Average | 8759.83 | 21.42 | 335.67 | 21.39 | 335.67 | 21.36 |
Minimum of Months | 672.00 | 20.99 | 0.00 | 20.93 | 0.00 | 20.87 |
Maximum of Months | 744.00 | 21.95 | 125.33 | 21.95 | 125.33 | 21.95 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.65 | 473.50 | 20.56 | 473.50 | 20.51 |
February | 672.00 | 20.90 | 263.50 | 20.79 | 263.50 | 20.74 |
March | 744.00 | 21.15 | 57.67 | 21.09 | 57.67 | 21.03 |
April | 720.00 | 21.44 | 2.00 | 21.44 | 2.00 | 21.43 |
May | 744.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
June | 720.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
July | 741.67 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
August | 732.67 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
September | 719.67 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
October | 744.00 | 21.29 | 5.17 | 21.28 | 5.17 | 21.27 |
November | 720.00 | 20.87 | 185.00 | 20.74 | 185.00 | 20.65 |
December | 744.00 | 20.72 | 391.67 | 20.61 | 391.67 | 20.55 |
Annual Sum or Average | 8746.00 | 21.27 | 1378.50 | 21.15 | 1378.50 | 21.06 |
Minimum of Months | 672.00 | 20.65 | 0.00 | 20.56 | 0.00 | 20.51 |
Maximum of Months | 744.00 | 21.72 | 473.50 | 21.72 | 473.50 | 21.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 520.67 | 20.46 | 520.67 | 20.42 |
February | 672.00 | 20.72 | 380.17 | 20.63 | 380.17 | 20.58 |
March | 744.00 | 20.97 | 107.00 | 20.89 | 107.00 | 20.84 |
April | 719.50 | 21.35 | 6.00 | 21.34 | 6.00 | 21.33 |
May | 743.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
June | 713.00 | 21.92 | 2.17 | 21.93 | 0.00 | 21.93 |
July | 723.50 | 22.05 | 10.17 | 22.09 | 0.00 | 22.09 |
August | 717.83 | 22.00 | 16.50 | 22.06 | 0.00 | 22.06 |
September | 715.17 | 21.67 | 0.67 | 21.67 | 0.00 | 21.67 |
October | 744.00 | 21.12 | 18.17 | 21.10 | 18.17 | 21.07 |
November | 720.00 | 20.75 | 259.17 | 20.62 | 259.17 | 20.54 |
December | 744.00 | 20.60 | 517.50 | 20.51 | 517.50 | 20.47 |
Annual Sum or Average | 8700.00 | 21.28 | 1838.17 | 21.13 | 1808.67 | 21.02 |
Minimum of Months | 672.00 | 20.56 | 0.00 | 20.46 | 0.00 | 20.42 |
Maximum of Months | 744.00 | 22.05 | 520.67 | 22.09 | 520.67 | 22.09 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 33.67 | 21.00 | 33.67 | 21.00 |
February | 672.00 | 21.01 | 37.00 | 21.01 | 37.00 | 21.01 |
March | 744.00 | 21.04 | 29.50 | 21.04 | 29.50 | 21.04 |
April | 720.00 | 21.18 | 0.00 | 21.18 | 0.00 | 21.18 |
May | 744.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
June | 720.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
July | 744.00 | 22.12 | 0.00 | 22.12 | 0.00 | 22.12 |
August | 744.00 | 22.24 | 0.00 | 22.24 | 0.00 | 22.24 |
September | 720.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
October | 744.00 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
November | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
December | 744.00 | 21.00 | 5.17 | 21.00 | 5.17 | 21.00 |
Annual Sum or Average | 8760.00 | 21.41 | 105.33 | 21.40 | 105.33 | 21.40 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.24 | 37.00 | 22.24 | 37.00 | 22.24 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 655.50 | 20.51 | 655.50 | 20.50 |
February | 672.00 | 20.79 | 381.50 | 20.69 | 381.50 | 20.64 |
March | 744.00 | 21.02 | 159.83 | 20.92 | 159.83 | 20.84 |
April | 714.50 | 21.31 | 19.67 | 21.29 | 19.67 | 21.27 |
May | 726.50 | 21.49 | 0.83 | 21.49 | 0.83 | 21.49 |
June | 702.33 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
July | 689.33 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
August | 686.00 | 21.55 | 1.33 | 21.55 | 0.67 | 21.55 |
September | 689.83 | 21.46 | 1.17 | 21.46 | 1.17 | 21.46 |
October | 743.50 | 21.19 | 31.83 | 21.13 | 31.83 | 21.08 |
November | 720.00 | 20.76 | 347.67 | 20.65 | 347.67 | 20.59 |
December | 744.00 | 20.62 | 589.00 | 20.57 | 589.00 | 20.55 |
Annual Sum or Average | 8576.00 | 21.15 | 2188.33 | 21.01 | 2187.67 | 20.92 |
Minimum of Months | 672.00 | 20.54 | 0.00 | 20.51 | 0.00 | 20.50 |
Maximum of Months | 744.00 | 21.59 | 655.50 | 21.59 | 655.50 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 673.50 | 20.44 | 673.50 | 20.43 |
February | 672.00 | 20.62 | 462.50 | 20.54 | 462.50 | 20.51 |
March | 744.00 | 20.85 | 286.17 | 20.73 | 286.17 | 20.67 |
April | 713.00 | 21.25 | 41.50 | 21.21 | 39.17 | 21.17 |
May | 686.67 | 21.56 | 30.50 | 21.72 | 1.00 | 21.72 |
June | 657.00 | 21.80 | 29.00 | 21.95 | 0.00 | 21.95 |
July | 609.00 | 21.91 | 71.83 | 22.28 | 6.33 | 22.33 |
August | 666.00 | 21.87 | 25.83 | 21.99 | 2.33 | 22.00 |
September | 657.33 | 21.61 | 31.00 | 21.76 | 1.17 | 21.76 |
October | 743.67 | 21.04 | 70.00 | 20.94 | 70.00 | 20.86 |
November | 720.00 | 20.65 | 416.17 | 20.54 | 416.17 | 20.49 |
December | 744.00 | 20.51 | 670.83 | 20.48 | 670.83 | 20.47 |
Annual Sum or Average | 8356.67 | 21.15 | 2808.83 | 21.05 | 2629.17 | 20.93 |
Minimum of Months | 609.00 | 20.48 | 25.83 | 20.44 | 0.00 | 20.43 |
Maximum of Months | 744.00 | 21.91 | 673.50 | 22.28 | 673.50 | 22.33 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 321.50 | 20.80 | 321.50 | 20.73 |
February | 672.00 | 21.19 | 161.50 | 21.09 | 161.50 | 21.03 |
March | 742.00 | 21.35 | 23.83 | 21.33 | 23.83 | 21.30 |
April | 714.17 | 21.53 | 0.83 | 21.53 | 0.83 | 21.53 |
May | 732.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
June | 716.33 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
July | 714.50 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
August | 689.17 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
September | 672.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
October | 734.33 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
November | 716.67 | 21.09 | 84.00 | 21.00 | 84.00 | 20.93 |
December | 744.00 | 20.99 | 231.83 | 20.84 | 231.83 | 20.75 |
Annual Sum or Average | 8591.17 | 21.37 | 823.50 | 21.29 | 823.50 | 21.23 |
Minimum of Months | 672.00 | 20.91 | 0.00 | 20.80 | 0.00 | 20.73 |
Maximum of Months | 744.00 | 21.67 | 321.50 | 21.67 | 321.50 | 21.67 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
February | 666.33 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
March | 737.67 | 22.00 | 1.00 | 22.00 | 0.00 | 22.00 |
April | 676.83 | 22.10 | 5.50 | 22.12 | 0.00 | 22.12 |
May | 621.17 | 22.18 | 23.17 | 22.24 | 0.00 | 22.24 |
June | 488.67 | 22.12 | 65.00 | 22.31 | 0.00 | 22.31 |
July | 447.00 | 22.12 | 138.50 | 22.46 | 0.67 | 22.46 |
August | 423.33 | 22.04 | 188.00 | 22.49 | 16.17 | 22.52 |
September | 515.50 | 22.04 | 63.00 | 22.21 | 0.00 | 22.21 |
October | 704.50 | 22.04 | 1.33 | 22.05 | 0.00 | 22.05 |
November | 707.50 | 21.91 | 3.83 | 21.92 | 1.00 | 21.92 |
December | 744.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
Annual Sum or Average | 7476.50 | 21.99 | 489.33 | 22.09 | 17.83 | 22.09 |
Minimum of Months | 423.33 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
Maximum of Months | 744.00 | 22.18 | 188.00 | 22.49 | 16.17 | 22.52 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 723.67 | 22.08 | 1.83 | 22.08 | 0.00 | 22.08 |
February | 624.67 | 22.11 | 6.17 | 22.13 | 0.00 | 22.13 |
March | 665.17 | 22.24 | 8.17 | 22.26 | 0.00 | 22.26 |
April | 572.50 | 22.29 | 33.83 | 22.37 | 0.00 | 22.37 |
May | 458.17 | 22.23 | 83.33 | 22.46 | 0.00 | 22.46 |
June | 355.33 | 22.17 | 162.83 | 22.63 | 0.00 | 22.63 |
July | 297.33 | 22.18 | 246.33 | 22.81 | 0.50 | 22.82 |
August | 294.17 | 22.16 | 312.67 | 22.87 | 16.50 | 22.90 |
September | 391.17 | 22.11 | 174.33 | 22.55 | 0.00 | 22.55 |
October | 580.83 | 22.20 | 37.17 | 22.29 | 0.00 | 22.29 |
November | 628.00 | 22.13 | 21.33 | 22.18 | 1.17 | 22.18 |
December | 731.50 | 22.12 | 0.67 | 22.12 | 0.00 | 22.12 |
Annual Sum or Average | 6322.50 | 22.16 | 1088.67 | 22.37 | 18.17 | 22.38 |
Minimum of Months | 294.17 | 22.08 | 0.67 | 22.08 | 0.00 | 22.08 |
Maximum of Months | 731.50 | 22.29 | 312.67 | 22.87 | 16.50 | 22.90 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 506.50 | 23.99 | 744.00 | 23.99 | 506.50 | 23.99 |
February | 461.83 | 23.99 | 672.00 | 23.99 | 461.83 | 23.99 |
March | 524.33 | 23.99 | 744.00 | 23.99 | 524.33 | 23.99 |
April | 515.17 | 23.99 | 720.00 | 23.99 | 515.17 | 23.99 |
May | 542.67 | 23.99 | 744.00 | 23.99 | 542.67 | 23.99 |
June | 536.83 | 23.99 | 720.00 | 23.99 | 536.83 | 23.99 |
July | 559.17 | 23.99 | 744.00 | 23.99 | 559.17 | 23.99 |
August | 566.67 | 23.99 | 744.00 | 23.99 | 566.67 | 23.99 |
September | 535.83 | 23.99 | 720.00 | 23.99 | 535.83 | 23.99 |
October | 532.17 | 23.99 | 744.00 | 23.99 | 532.17 | 23.99 |
November | 507.50 | 23.99 | 720.00 | 23.99 | 507.50 | 23.99 |
December | 512.00 | 23.99 | 744.00 | 23.99 | 512.00 | 23.99 |
Annual Sum or Average | 6300.67 | 23.99 | 8760.00 | 23.99 | 6300.67 | 23.99 |
Minimum of Months | 461.83 | 23.99 | 672.00 | 23.99 | 461.83 | 23.99 |
Maximum of Months | 566.67 | 23.99 | 744.00 | 23.99 | 566.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 34.33 | 21.02 | 34.33 | 21.02 |
February | 672.00 | 21.19 | 33.33 | 21.18 | 33.33 | 21.17 |
March | 744.00 | 21.63 | 0.67 | 21.63 | 0.67 | 21.63 |
April | 698.83 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
May | 643.17 | 22.95 | 21.00 | 22.98 | 0.00 | 22.98 |
June | 479.00 | 23.33 | 11.67 | 23.34 | 0.00 | 23.34 |
July | 249.00 | 23.51 | 159.17 | 23.70 | 0.00 | 23.70 |
August | 219.50 | 23.41 | 264.67 | 23.72 | 0.00 | 23.72 |
September | 522.17 | 23.03 | 60.33 | 23.13 | 0.00 | 23.13 |
October | 744.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
November | 720.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
December | 744.00 | 21.03 | 4.17 | 21.03 | 4.17 | 21.03 |
Annual Sum or Average | 7179.67 | 22.00 | 589.33 | 22.13 | 72.50 | 22.12 |
Minimum of Months | 219.50 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 23.51 | 264.67 | 23.72 | 34.33 | 23.72 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.35158 | 34.29086 | -0.1220 | 5.41051 |
February | 672.00000 | 22.14457 | 35.89051 | -0.1649 | 5.70723 |
March | 744.00000 | 21.93727 | 36.80170 | -0.2117 | 6.07610 |
April | 720.00000 | 21.82466 | 41.37569 | -0.2129 | 6.09693 |
May | 744.00000 | 21.91095 | 46.00659 | -1.2821 | 39.44777 |
June | 720.00000 | 22.08944 | 48.28279 | -1.2020 | 35.48007 |
July | 744.00000 | 22.30686 | 51.90026 | -1.0992 | 30.62828 |
August | 744.00000 | 22.49836 | 55.72140 | -1.0051 | 26.47088 |
September | 720.00000 | 22.73199 | 51.83636 | -0.9446 | 24.04321 |
October | 744.00000 | 22.92049 | 42.88136 | 0.08282 | 5.25497 |
November | 720.00000 | 22.99693 | 39.78489 | 0.08113 | 5.25499 |
December | 744.00000 | 22.71676 | 34.82927 | -0.0243 | 5.11028 |
Annual Sum or Average | 8760.00000 | 22.37055 | 43.33891 | -0.5109 | 16.31896 |
Minimum of Months | 672.00000 | 21.82466 | 34.29086 | -1.2821 | 5.11028 |
Maximum of Months | 744.00000 | 22.99693 | 55.72140 | 0.08282 | 39.44777 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02825 | 36.21480 | -0.5017 | 10.38802 |
February | 672.00000 | 21.16159 | 37.37721 | -0.4228 | 9.26770 |
March | 744.00000 | 21.31607 | 37.82852 | -0.3472 | 8.15243 |
April | 720.00000 | 21.64338 | 41.57241 | -0.2152 | 7.07856 |
May | 744.00000 | 21.96946 | 45.73872 | -1.1824 | 35.94564 |
June | 720.00000 | 22.32958 | 47.65798 | -1.0335 | 28.88603 |
July | 744.00000 | 22.89683 | 50.19121 | -0.8009 | 20.24350 |
August | 744.00000 | 22.95575 | 54.25722 | -0.7465 | 18.80103 |
September | 720.00000 | 22.39995 | 52.69612 | -0.9701 | 27.62232 |
October | 744.00000 | 21.62622 | 45.82699 | -0.1999 | 6.84725 |
November | 720.00000 | 21.12114 | 43.49907 | -0.3955 | 8.75579 |
December | 744.00000 | 21.07185 | 37.48982 | -0.4751 | 9.96177 |
Annual Sum or Average | 8760.00000 | 21.79765 | 44.22821 | -0.6086 | 16.02823 |
Minimum of Months | 672.00000 | 21.02825 | 36.21480 | -1.1824 | 6.84725 |
Maximum of Months | 744.00000 | 22.95575 | 54.25722 | -0.1999 | 35.94564 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.16314 | 36.45822 | -0.3865 | 8.23259 |
February | 672.00000 | 21.25928 | 37.59428 | -0.3463 | 7.75476 |
March | 744.00000 | 21.43057 | 37.91897 | -0.2910 | 7.02088 |
April | 720.00000 | 21.65575 | 41.87529 | -0.2025 | 6.30090 |
May | 744.00000 | 21.92178 | 46.17215 | -1.1993 | 35.68910 |
June | 720.00000 | 22.13226 | 48.40985 | -1.1061 | 31.33103 |
July | 744.00000 | 22.45669 | 51.73708 | -0.9632 | 25.22112 |
August | 744.00000 | 22.52045 | 55.92563 | -0.9139 | 23.35032 |
September | 720.00000 | 22.18891 | 53.59475 | -1.0524 | 29.09730 |
October | 744.00000 | 21.68069 | 45.95215 | -0.1723 | 5.93688 |
November | 720.00000 | 21.33489 | 43.42577 | -0.2895 | 7.02788 |
December | 744.00000 | 21.19246 | 37.71172 | -0.3680 | 7.92442 |
Annual Sum or Average | 8760.00000 | 21.74782 | 44.76702 | -0.6091 | 16.28625 |
Minimum of Months | 672.00000 | 21.16314 | 36.45822 | -1.1993 | 5.93688 |
Maximum of Months | 744.00000 | 22.52045 | 55.92563 | -0.1723 | 35.68910 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99979 | 27.66151 | 0.82383 | 20.05538 |
February | 672.00000 | 23.99978 | 28.79968 | 0.84346 | 20.80238 |
March | 744.00000 | 23.99974 | 29.28106 | 0.86546 | 21.58065 |
April | 720.00000 | 23.99975 | 33.12411 | 0.90838 | 23.16135 |
May | 744.00000 | 23.99973 | 37.35423 | 0.30762 | 8.58872 |
June | 720.00000 | 23.99973 | 39.80486 | 0.34618 | 9.14525 |
July | 744.00000 | 23.99972 | 43.55749 | 0.38320 | 9.66733 |
August | 744.00000 | 23.99975 | 47.49800 | 0.41953 | 10.29434 |
September | 720.00000 | 23.99975 | 44.56978 | 0.36953 | 9.45960 |
October | 744.00000 | 23.99975 | 36.65594 | 0.92885 | 23.90219 |
November | 720.00000 | 23.99976 | 33.86138 | 0.88747 | 22.38932 |
December | 744.00000 | 23.99979 | 28.73340 | 0.83473 | 20.42963 |
Annual Sum or Average | 8760.00000 | 23.99975 | 35.94571 | 0.65870 | 16.59506 |
Minimum of Months | 672.00000 | 23.99972 | 27.66151 | 0.30762 | 8.58872 |
Maximum of Months | 744.00000 | 23.99979 | 47.49800 | 0.92885 | 23.90219 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.18672 | 38.63349 | -0.3573 | 7.85828 |
February | 672.00000 | 21.29166 | 39.76465 | -0.2890 | 7.13640 |
March | 744.00000 | 21.43078 | 40.18235 | -0.2232 | 6.41226 |
April | 720.00000 | 21.53934 | 44.41983 | -0.1433 | 5.87883 |
May | 744.00000 | 21.63204 | 49.15775 | -1.1672 | 34.18062 |
June | 720.00000 | 21.72655 | 51.75392 | -1.0990 | 30.98552 |
July | 744.00000 | 21.90344 | 55.59581 | -0.9890 | 26.34738 |
August | 744.00000 | 22.02503 | 59.73446 | -0.9136 | 23.70263 |
September | 720.00000 | 21.88963 | 56.73779 | -1.0074 | 27.62977 |
October | 744.00000 | 21.58532 | 48.43911 | -0.1135 | 5.71970 |
November | 720.00000 | 21.32123 | 45.69255 | -0.2492 | 6.73305 |
December | 744.00000 | 21.20754 | 39.91938 | -0.3365 | 7.55752 |
Annual Sum or Average | 8760.00000 | 21.56319 | 47.54265 | -0.5758 | 15.89525 |
Minimum of Months | 672.00000 | 21.18672 | 38.63349 | -1.1672 | 5.71970 |
Maximum of Months | 744.00000 | 22.02503 | 59.73446 | -0.1135 | 34.18062 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63930 | 38.30238 | -0.2401 | 6.61053 |
February | 672.00000 | 21.78189 | 39.31005 | -0.1883 | 6.27105 |
March | 744.00000 | 21.98392 | 39.62332 | -0.1252 | 5.82453 |
April | 720.00000 | 22.16662 | 43.55789 | -0.0464 | 5.58702 |
May | 744.00000 | 22.35341 | 47.91242 | -1.0123 | 27.38419 |
June | 720.00000 | 22.50704 | 50.23823 | -0.9355 | 24.29146 |
July | 744.00000 | 22.69723 | 53.88983 | -0.8358 | 20.50348 |
August | 744.00000 | 22.77942 | 57.94684 | -0.7783 | 18.59662 |
September | 720.00000 | 22.56805 | 55.29178 | -0.8802 | 22.26342 |
October | 744.00000 | 22.22250 | 47.40221 | -0.0081 | 5.49649 |
November | 720.00000 | 21.87297 | 44.96465 | -0.1275 | 5.92330 |
December | 744.00000 | 21.70689 | 39.48278 | -0.2131 | 6.31605 |
Annual Sum or Average | 8760.00000 | 22.19232 | 46.53044 | -0.4509 | 12.95954 |
Minimum of Months | 672.00000 | 21.63930 | 38.30238 | -1.0123 | 5.49649 |
Maximum of Months | 744.00000 | 22.77942 | 57.94684 | -0.0081 | 27.38419 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.66119 | 43.74777 | -0.5918 | 12.65686 |
February | 672.00000 | 20.89604 | 44.48564 | -0.5067 | 10.86259 |
March | 744.00000 | 21.09773 | 45.11677 | -0.4233 | 9.05014 |
April | 720.00000 | 21.35154 | 47.82773 | -0.3085 | 7.52673 |
May | 744.00000 | 21.53003 | 50.72421 | -1.3622 | 44.22064 |
June | 720.00000 | 21.61582 | 52.07835 | -1.2994 | 41.02064 |
July | 744.00000 | 21.70523 | 52.61023 | -1.2173 | 37.24041 |
August | 744.00000 | 21.69445 | 55.40239 | -1.2076 | 36.76329 |
September | 720.00000 | 21.55973 | 56.12248 | -1.2967 | 41.01978 |
October | 744.00000 | 21.25525 | 52.25021 | -0.3205 | 7.56941 |
November | 720.00000 | 20.86838 | 50.59979 | -0.4754 | 10.14585 |
December | 744.00000 | 20.73074 | 45.42542 | -0.5609 | 11.94639 |
Annual Sum or Average | 8760.00000 | 21.24895 | 49.72065 | -0.7994 | 22.57097 |
Minimum of Months | 672.00000 | 20.66119 | 43.74777 | -1.3622 | 7.52673 |
Maximum of Months | 744.00000 | 21.70523 | 56.12248 | -0.3085 | 44.22064 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.56060 | 43.99751 | -0.6233 | 13.58033 |
February | 672.00000 | 20.72651 | 44.89487 | -0.5594 | 12.04897 |
March | 744.00000 | 20.93417 | 45.49762 | -0.4764 | 9.96635 |
April | 720.00000 | 21.28276 | 48.14683 | -0.3399 | 7.95420 |
May | 744.00000 | 21.72134 | 50.52184 | -1.3244 | 42.96669 |
June | 720.00000 | 21.92926 | 51.41779 | -1.2228 | 37.78873 |
July | 744.00000 | 22.23721 | 51.92642 | -1.0781 | 32.09356 |
August | 744.00000 | 22.05627 | 55.65940 | -1.1203 | 33.02379 |
September | 720.00000 | 21.79676 | 56.76659 | -1.2529 | 39.36443 |
October | 744.00000 | 21.11639 | 52.74560 | -0.3703 | 8.15069 |
November | 720.00000 | 20.76211 | 50.98137 | -0.5089 | 10.84973 |
December | 744.00000 | 20.60856 | 45.73789 | -0.5987 | 12.88274 |
Annual Sum or Average | 8760.00000 | 21.31436 | 49.87701 | -0.7910 | 21.77719 |
Minimum of Months | 672.00000 | 20.56060 | 43.99751 | -1.3244 | 7.95420 |
Maximum of Months | 744.00000 | 22.23721 | 56.76659 | -0.3399 | 42.96669 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99481 | 42.04277 | -0.4748 | 9.83716 |
February | 672.00000 | 21.07859 | 42.91393 | -0.4406 | 9.27328 |
March | 744.00000 | 21.21380 | 43.46829 | -0.3853 | 8.18752 |
April | 720.00000 | 21.39069 | 46.10079 | -0.3123 | 7.24965 |
May | 744.00000 | 21.60318 | 48.47406 | -1.3857 | 45.06843 |
June | 720.00000 | 21.79441 | 48.98096 | -1.3041 | 40.95416 |
July | 744.00000 | 21.94859 | 51.03652 | -1.2305 | 37.48517 |
August | 744.00000 | 21.88923 | 54.24493 | -1.2330 | 37.48262 |
September | 720.00000 | 21.64678 | 54.10958 | -1.3364 | 42.51552 |
October | 744.00000 | 21.30164 | 50.20697 | -0.3143 | 7.13859 |
November | 720.00000 | 21.13976 | 48.35667 | -0.3843 | 8.24844 |
December | 744.00000 | 21.01830 | 43.74873 | -0.4577 | 9.47147 |
Annual Sum or Average | 8760.00000 | 21.42029 | 47.82992 | -0.7736 | 21.98215 |
Minimum of Months | 672.00000 | 20.99481 | 42.04277 | -1.3857 | 7.13859 |
Maximum of Months | 744.00000 | 21.94859 | 54.24493 | -0.3123 | 45.06843 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.65204 | 43.75818 | -0.5941 | 12.72013 |
February | 672.00000 | 20.89601 | 44.47133 | -0.5069 | 10.80747 |
March | 744.00000 | 21.14846 | 44.99226 | -0.4114 | 8.84259 |
April | 720.00000 | 21.44035 | 47.52570 | -0.2863 | 7.31886 |
May | 744.00000 | 21.55829 | 50.46755 | -1.3646 | 44.36587 |
June | 720.00000 | 21.68224 | 51.13120 | -1.2753 | 39.95960 |
July | 744.00000 | 21.72801 | 52.59093 | -1.2249 | 37.64023 |
August | 744.00000 | 21.72719 | 54.78886 | -1.2000 | 36.46046 |
September | 720.00000 | 21.56490 | 56.13905 | -1.3042 | 41.42177 |
October | 744.00000 | 21.28915 | 52.01818 | -0.3146 | 7.53110 |
November | 720.00000 | 20.86662 | 50.59937 | -0.4755 | 10.15435 |
December | 744.00000 | 20.72042 | 45.44290 | -0.5631 | 11.98705 |
Annual Sum or Average | 8760.00000 | 21.27464 | 49.51474 | -0.7953 | 22.50470 |
Minimum of Months | 672.00000 | 20.65204 | 43.75818 | -1.3646 | 7.31886 |
Maximum of Months | 744.00000 | 21.72801 | 56.13905 | -0.2863 | 44.36587 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55754 | 43.99740 | -0.6246 | 13.63948 |
February | 672.00000 | 20.72100 | 44.89766 | -0.5608 | 12.04689 |
March | 744.00000 | 20.96976 | 45.39194 | -0.4677 | 9.71171 |
April | 720.00000 | 21.34919 | 47.89354 | -0.3220 | 7.63755 |
May | 744.00000 | 21.63667 | 50.57458 | -1.3589 | 44.05723 |
June | 720.00000 | 21.94787 | 50.71678 | -1.2124 | 37.01041 |
July | 744.00000 | 22.11658 | 52.51022 | -1.1267 | 33.32946 |
August | 744.00000 | 22.08613 | 55.10533 | -1.1132 | 32.71199 |
September | 720.00000 | 21.68647 | 57.02211 | -1.2946 | 40.93436 |
October | 744.00000 | 21.12241 | 52.62053 | -0.3699 | 8.08804 |
November | 720.00000 | 20.75241 | 51.00276 | -0.5107 | 10.89153 |
December | 744.00000 | 20.59689 | 45.75869 | -0.6013 | 12.97515 |
Annual Sum or Average | 8760.00000 | 21.29844 | 49.81071 | -0.7984 | 21.97653 |
Minimum of Months | 672.00000 | 20.55754 | 43.99740 | -1.3589 | 7.63755 |
Maximum of Months | 744.00000 | 22.11658 | 57.02211 | -0.3220 | 44.05723 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54067 | 44.85050 | -0.6496 | 14.29498 |
February | 672.00000 | 20.78764 | 45.60299 | -0.5566 | 12.12885 |
March | 744.00000 | 21.02104 | 46.19626 | -0.4579 | 9.81853 |
April | 720.00000 | 21.32922 | 48.77154 | -0.3206 | 7.86073 |
May | 744.00000 | 21.53630 | 51.47518 | -1.3614 | 44.41749 |
June | 720.00000 | 21.63094 | 52.71896 | -1.2877 | 40.69254 |
July | 744.00000 | 21.70778 | 53.30066 | -1.2041 | 36.87029 |
August | 744.00000 | 21.68947 | 56.37051 | -1.2013 | 36.67994 |
September | 720.00000 | 21.54027 | 57.46901 | -1.3041 | 41.60788 |
October | 744.00000 | 21.18865 | 53.59164 | -0.3483 | 8.08571 |
November | 720.00000 | 20.75586 | 52.00971 | -0.5228 | 11.30232 |
December | 744.00000 | 20.62286 | 46.58314 | -0.6150 | 13.37960 |
Annual Sum or Average | 8760.00000 | 21.19795 | 50.76538 | -0.8209 | 23.16015 |
Minimum of Months | 672.00000 | 20.54067 | 44.85050 | -1.3614 | 7.86073 |
Maximum of Months | 744.00000 | 21.70778 | 57.46901 | -0.3206 | 44.41749 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47571 | 45.02810 | -0.6751 | 15.10476 |
February | 672.00000 | 20.62308 | 46.02988 | -0.6095 | 13.42920 |
March | 744.00000 | 20.84892 | 46.61210 | -0.5141 | 10.85284 |
April | 720.00000 | 21.27381 | 49.02950 | -0.3503 | 8.31120 |
May | 744.00000 | 21.80528 | 51.07352 | -1.2986 | 42.50765 |
June | 720.00000 | 22.04002 | 51.68153 | -1.1794 | 36.48984 |
July | 744.00000 | 22.36251 | 51.96217 | -1.0237 | 30.93267 |
August | 744.00000 | 22.09523 | 56.31428 | -1.0980 | 32.51458 |
September | 720.00000 | 21.84906 | 57.77974 | -1.2379 | 39.29874 |
October | 744.00000 | 21.04147 | 54.13367 | -0.4016 | 8.76878 |
November | 720.00000 | 20.65284 | 52.41893 | -0.5563 | 12.07508 |
December | 744.00000 | 20.50955 | 46.89210 | -0.6518 | 14.38942 |
Annual Sum or Average | 8760.00000 | 21.30196 | 50.76335 | -0.8009 | 22.10536 |
Minimum of Months | 672.00000 | 20.47571 | 45.02810 | -1.2986 | 8.31120 |
Maximum of Months | 744.00000 | 22.36251 | 57.77974 | -0.3503 | 42.50765 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91005 | 44.17725 | -0.5211 | 11.09269 |
February | 672.00000 | 21.19495 | 44.73222 | -0.4145 | 9.41824 |
March | 744.00000 | 21.35956 | 45.31020 | -0.3402 | 8.08383 |
April | 720.00000 | 21.54782 | 47.70592 | -0.2514 | 7.14974 |
May | 744.00000 | 21.61971 | 50.52094 | -1.3410 | 43.38577 |
June | 720.00000 | 21.67532 | 51.68215 | -1.2907 | 40.83638 |
July | 744.00000 | 21.71555 | 52.71451 | -1.2373 | 38.39543 |
August | 744.00000 | 21.71052 | 54.90332 | -1.2160 | 37.36794 |
September | 720.00000 | 21.62474 | 54.92750 | -1.2756 | 40.25376 |
October | 744.00000 | 21.46672 | 51.54127 | -0.2513 | 7.05686 |
November | 720.00000 | 21.10413 | 50.31670 | -0.4067 | 9.03713 |
December | 744.00000 | 20.98640 | 45.75432 | -0.4848 | 10.58552 |
Annual Sum or Average | 8760.00000 | 21.41053 | 49.54533 | -0.7547 | 21.96447 |
Minimum of Months | 672.00000 | 20.91005 | 44.17725 | -1.3410 | 7.05686 |
Maximum of Months | 744.00000 | 21.71555 | 54.92750 | -0.2513 | 43.38577 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.80327 | 37.80518 | -0.1501 | 6.04825 |
February | 672.00000 | 21.86575 | 38.92429 | -0.1166 | 5.97736 |
March | 744.00000 | 22.01285 | 39.29940 | -0.0568 | 5.71161 |
April | 720.00000 | 22.18059 | 43.28863 | 0.02975 | 5.63619 |
May | 744.00000 | 22.38080 | 47.59417 | -0.8827 | 22.35830 |
June | 720.00000 | 22.51890 | 49.94768 | -0.7995 | 19.44695 |
July | 744.00000 | 22.60575 | 53.87323 | -0.7305 | 17.10729 |
August | 744.00000 | 22.58860 | 58.22957 | -0.7109 | 16.58843 |
September | 720.00000 | 22.39438 | 55.50965 | -0.8245 | 20.34050 |
October | 744.00000 | 22.11840 | 47.35147 | 0.03172 | 5.64326 |
November | 720.00000 | 21.93839 | 44.60447 | -0.0553 | 5.76234 |
December | 744.00000 | 21.82104 | 39.04187 | -0.1359 | 5.89648 |
Annual Sum or Average | 8760.00000 | 22.18756 | 46.32722 | -0.3683 | 11.40523 |
Minimum of Months | 672.00000 | 21.80327 | 37.80518 | -0.8827 | 5.63619 |
Maximum of Months | 744.00000 | 22.60575 | 58.22957 | 0.03172 | 22.35830 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.11633 | 37.29696 | -0.0414 | 5.72049 |
February | 672.00000 | 22.20104 | 38.34458 | -0.0045 | 5.77728 |
March | 744.00000 | 22.37412 | 38.67611 | 0.05782 | 5.72287 |
April | 720.00000 | 22.52288 | 42.61694 | 0.13602 | 5.96144 |
May | 744.00000 | 22.67439 | 46.92671 | -0.7548 | 17.88097 |
June | 720.00000 | 22.78125 | 49.29545 | -0.6847 | 15.76122 |
July | 744.00000 | 22.84653 | 53.20095 | -0.6247 | 13.98570 |
August | 744.00000 | 22.82772 | 57.49578 | -0.6057 | 13.55772 |
September | 720.00000 | 22.66885 | 54.75041 | -0.7049 | 16.40367 |
October | 744.00000 | 22.46016 | 46.59091 | 0.13843 | 6.00270 |
November | 720.00000 | 22.28486 | 43.89042 | 0.05864 | 5.82485 |
December | 744.00000 | 22.14369 | 38.49565 | -0.0252 | 5.62035 |
Annual Sum or Average | 8760.00000 | 22.49341 | 45.66964 | -0.2561 | 9.87264 |
Minimum of Months | 672.00000 | 22.11633 | 37.29696 | -0.7548 | 5.62035 |
Maximum of Months | 744.00000 | 22.84653 | 57.49578 | 0.13843 | 17.88097 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99100 | 35.46034 | 1.02055 | 28.21752 |
February | 672.00000 | 23.99099 | 36.40533 | 1.04470 | 29.33348 |
March | 744.00000 | 23.99095 | 36.73956 | 1.07361 | 30.57162 |
April | 720.00000 | 23.99103 | 40.37700 | 1.12792 | 33.08612 |
May | 744.00000 | 23.99117 | 44.46099 | 0.60900 | 16.10167 |
June | 720.00000 | 23.99124 | 46.79257 | 0.65574 | 17.29319 |
July | 744.00000 | 23.99150 | 50.47321 | 0.69813 | 18.72279 |
August | 744.00000 | 23.99162 | 54.26044 | 0.72675 | 19.46794 |
September | 720.00000 | 23.99142 | 51.44981 | 0.66569 | 17.54478 |
October | 744.00000 | 23.99113 | 43.81293 | 1.13747 | 33.37173 |
November | 720.00000 | 23.99116 | 41.31164 | 1.08612 | 31.12380 |
December | 744.00000 | 23.99104 | 36.47770 | 1.03185 | 28.73001 |
Annual Sum or Average | 8760.00000 | 23.99119 | 43.20417 | 0.90557 | 25.26974 |
Minimum of Months | 672.00000 | 23.99095 | 35.46034 | 0.60900 | 16.10167 |
Maximum of Months | 744.00000 | 23.99162 | 54.26044 | 1.13747 | 33.37173 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00011 | 33.61182 | -0.4823 | 9.89904 |
February | 672.00000 | 21.00048 | 35.00441 | -0.4628 | 9.57219 |
March | 744.00000 | 21.00063 | 35.63577 | -0.4389 | 9.08239 |
April | 720.00000 | 21.03480 | 40.16660 | -0.3900 | 8.29431 |
May | 744.00000 | 21.13041 | 45.01493 | -1.5032 | 51.10716 |
June | 720.00000 | 21.33120 | 47.39140 | -1.4115 | 46.18297 |
July | 744.00000 | 21.59190 | 51.03677 | -1.2960 | 40.17349 |
August | 744.00000 | 21.67823 | 55.35921 | -1.2402 | 37.37429 |
September | 720.00000 | 21.30071 | 53.12714 | -1.3891 | 45.03942 |
October | 744.00000 | 21.03408 | 44.45591 | -0.3615 | 7.76341 |
November | 720.00000 | 21.00337 | 41.12906 | -0.4115 | 8.62190 |
December | 744.00000 | 21.00012 | 34.92004 | -0.4678 | 9.59927 |
Annual Sum or Average | 8760.00000 | 21.17703 | 43.11128 | -0.8233 | 23.63603 |
Minimum of Months | 672.00000 | 21.00011 | 33.61182 | -1.5032 | 7.76341 |
Maximum of Months | 744.00000 | 21.67823 | 55.35921 | -0.3615 | 51.10716 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00067 | 37.82653 | -0.4703 | 9.64928 |
February | 672.00000 | 21.00997 | 39.16489 | -0.4505 | 9.31891 |
March | 744.00000 | 21.03931 | 39.74696 | -0.4287 | 8.89818 |
April | 720.00000 | 21.18099 | 43.98422 | -0.3629 | 7.93490 |
May | 744.00000 | 21.49560 | 48.29773 | -1.4169 | 46.50673 |
June | 720.00000 | 21.76757 | 50.45608 | -1.3084 | 40.81243 |
July | 744.00000 | 22.11529 | 53.77015 | -1.1652 | 33.75558 |
August | 744.00000 | 22.23620 | 57.90796 | -1.0972 | 30.57047 |
September | 720.00000 | 21.78891 | 55.84979 | -1.2670 | 38.85808 |
October | 744.00000 | 21.19361 | 48.22108 | -0.3364 | 7.45206 |
November | 720.00000 | 21.01990 | 45.24698 | -0.4110 | 8.61012 |
December | 744.00000 | 21.00073 | 39.11659 | -0.4604 | 9.45111 |
Annual Sum or Average | 8760.00000 | 21.40691 | 46.66911 | -0.7664 | 21.04707 |
Minimum of Months | 672.00000 | 21.00067 | 37.82653 | -1.4169 | 7.45206 |
Maximum of Months | 744.00000 | 22.23620 | 57.90796 | -0.3364 | 46.50673 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01936 | 37.53231 | -0.4611 | 9.48727 |
February | 672.00000 | 21.19206 | 38.50820 | -0.4015 | 8.67362 |
March | 744.00000 | 21.63363 | 38.45416 | -0.2793 | 6.84869 |
April | 720.00000 | 22.33442 | 41.35916 | -0.0848 | 5.71734 |
May | 744.00000 | 23.08022 | 44.45457 | -0.8811 | 22.08457 |
June | 720.00000 | 23.52271 | 45.98223 | -0.7107 | 16.03884 |
July | 744.00000 | 23.77980 | 48.95540 | -0.5905 | 12.60113 |
August | 744.00000 | 23.75599 | 53.01379 | -0.5712 | 12.11882 |
September | 720.00000 | 23.26476 | 51.58146 | -0.7661 | 18.15470 |
October | 744.00000 | 22.15603 | 45.82117 | -0.1032 | 5.61710 |
November | 720.00000 | 21.31409 | 44.25529 | -0.3319 | 7.76894 |
December | 744.00000 | 21.03241 | 38.82871 | -0.4472 | 9.21393 |
Annual Sum or Average | 8760.00000 | 22.34695 | 44.08887 | -0.4696 | 11.20650 |
Minimum of Months | 672.00000 | 21.01936 | 37.53231 | -0.8811 | 5.61710 |
Maximum of Months | 744.00000 | 23.77980 | 53.01379 | -0.0848 | 22.08457 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.77333 | 38.30659 | -0.2825 | 6.98188 |
February | 672.00000 | 22.10087 | 39.38729 | -0.1981 | 6.49626 |
March | 744.00000 | 22.76168 | 40.70635 | -0.0337 | 5.25910 |
April | 720.00000 | 23.25016 | 43.38792 | 0.09934 | 5.48566 |
May | 744.00000 | 23.71422 | 45.21904 | -0.7410 | 16.76770 |
June | 720.00000 | 23.93164 | 45.78498 | -0.6518 | 13.98348 |
July | 744.00000 | 23.99692 | 47.05295 | -0.6015 | 12.63935 |
August | 744.00000 | 23.99544 | 50.84398 | -0.5704 | 11.84448 |
September | 720.00000 | 23.89597 | 50.95144 | -0.6287 | 13.43433 |
October | 744.00000 | 23.38400 | 47.21167 | 0.15923 | 5.70774 |
November | 720.00000 | 22.63574 | 45.57903 | -0.0315 | 5.61538 |
December | 744.00000 | 21.98116 | 40.01642 | -0.2231 | 6.19981 |
Annual Sum or Average | 8760.00000 | 23.12339 | 44.55894 | -0.3096 | 9.21880 |
Minimum of Months | 672.00000 | 21.77333 | 38.30659 | -0.7410 | 5.25910 |
Maximum of Months | 744.00000 | 23.99692 | 50.95144 | 0.15923 | 16.76770 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.857424E+09 | 12204.25 | 22-JAN-09:01 | 230.91 | 0.280522E+10 | 0.00 | 0.366264E+10 | 1.02 | 3.27 | 01-JAN-21:05 | 0.00 | 0.00 |
February | 0.240356E+10 | 38097.48 | 27-FEB-16:00 | 306.70 | 0.763832E+10 | 0.00 | 0.100419E+11 | 1.49 | 3.27 | 01-FEB-19:06 | 0.00 | 0.00 |
March | 0.550616E+10 | 47335.38 | 18-MAR-15:11 | 424.00 | 0.176494E+11 | 0.00 | 0.231556E+11 | 1.86 | 3.44 | 18-MAR-15:11 | 0.00 | 0.00 |
April | 0.191041E+11 | 90889.57 | 27-APR-18:03 | 598.12 | 0.621036E+11 | 0.00 | 0.812077E+11 | 2.70 | 3.91 | 27-APR-18:03 | 0.00 | 0.00 |
May | 0.340033E+11 | 83173.11 | 05-MAY-15:13 | 709.15 | 0.110786E+12 | 0.00 | 0.144790E+12 | 3.09 | 3.98 | 05-MAY-18:03 | 0.00 | 0.00 |
June | 0.531634E+11 | 93503.42 | 28-JUN-18:03 | 710.42 | 0.172227E+12 | 0.00 | 0.225390E+12 | 3.17 | 4.14 | 12-JUN-18:03 | 0.00 | 0.00 |
July | 0.809062E+11 | 110691.87 | 24-JUL-18:03 | 744.00 | 0.269462E+12 | 0.00 | 0.350368E+12 | 3.24 | 4.17 | 15-JUL-18:03 | 0.00 | 0.00 |
August | 0.955869E+11 | 124461.34 | 10-AUG-18:03 | 744.00 | 0.321610E+12 | 0.00 | 0.417197E+12 | 3.26 | 4.21 | 26-AUG-18:03 | 0.00 | 0.00 |
September | 0.468856E+11 | 88844.06 | 14-SEP-15:13 | 698.08 | 0.154826E+12 | 0.00 | 0.201712E+12 | 3.14 | 4.12 | 23-SEP-18:03 | 0.00 | 0.00 |
October | 0.146928E+11 | 54910.17 | 04-OCT-15:15 | 588.19 | 0.466515E+11 | 0.00 | 0.613443E+11 | 2.56 | 3.66 | 04-OCT-15:15 | 0.00 | 0.00 |
November | 0.387720E+10 | 51066.34 | 04-NOV-15:13 | 295.87 | 0.124104E+11 | 0.00 | 0.162876E+11 | 1.34 | 3.58 | 04-NOV-15:13 | 0.00 | 0.00 |
December | 0.804067E+09 | 11270.87 | 03-DEC-19:02 | 193.65 | 0.263069E+10 | 0.00 | 0.343476E+10 | 0.85 | 3.27 | 02-DEC-09:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.357791E+12 | 6243.09 | 0.118080E+13 | 0.00 | 0.153859E+13 | 2.31 | 0.00 | 0.00 | ||||
Minimum of Months | 0.804067E+09 | 11270.87 | 193.65 | 0.263069E+10 | 0.00 | 0.343476E+10 | 0.85 | 3.27 | 0.00 | 0.00 | ||
Maximum of Months | 0.955869E+11 | 124461.34 | 744.00 | 0.321610E+12 | 0.00 | 0.417197E+12 | 3.26 | 4.21 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.125465E+12 | 0.00 | 741.00 | 190252.74 | 16-JAN-16:13 | 0.00 | 41.81 | 59.67 | 0.63 | 0.00 | 0.14 | 0.56 | 16-JAN-16:13 |
February | 0.904959E+11 | 0.00 | 658.00 | 186238.24 | 18-FEB-16:11 | 0.00 | 42.08 | 59.38 | 0.50 | 0.00 | 0.11 | 0.55 | 18-FEB-16:11 |
March | 0.645735E+11 | 0.00 | 715.49 | 162764.18 | 05-MAR-16:11 | 0.00 | 41.38 | 59.19 | 0.31 | 0.00 | 0.07 | 0.48 | 05-MAR-16:11 |
April | 0.309356E+11 | 0.00 | 605.53 | 111050.19 | 18-APR-08:62 | 0.00 | 41.76 | 57.26 | 0.15 | 0.00 | 0.04 | 0.33 | 18-APR-08:62 |
May | 0.112920E+11 | 0.00 | 475.74 | 83173.72 | 18-MAY-08:62 | 0.00 | 41.62 | 53.47 | 0.05 | 0.00 | 0.01 | 0.25 | 18-MAY-08:62 |
June | 0.126231E+10 | 0.00 | 253.08 | 35760.12 | 06-JUN-15:15 | 0.00 | 42.05 | 48.17 | 0.01 | 0.00 | 0.00 | 0.11 | 06-JUN-15:15 |
July | 0.388015E+09 | 0.00 | 107.05 | 32041.78 | 14-JUL-08:05 | 0.00 | 40.96 | 43.79 | 0.00 | 0.00 | 0.00 | 0.09 | 14-JUL-08:05 |
August | 0.404812E+09 | 0.00 | 128.17 | 31017.15 | 18-AUG-08:04 | 0.00 | 43.98 | 47.07 | 0.00 | 0.00 | 0.00 | 0.09 | 18-AUG-08:04 |
September | 0.230252E+10 | 0.00 | 283.00 | 33826.36 | 26-SEP-15:17 | 0.00 | 45.43 | 51.36 | 0.02 | 0.00 | 0.00 | 0.10 | 26-SEP-15:17 |
October | 0.192231E+11 | 0.00 | 598.41 | 77906.16 | 31-OCT-15:13 | 0.00 | 45.28 | 57.09 | 0.11 | 0.00 | 0.02 | 0.23 | 31-OCT-15:13 |
November | 0.796457E+11 | 0.00 | 684.72 | 161924.16 | 23-NOV-16:11 | 0.00 | 42.25 | 58.88 | 0.41 | 0.00 | 0.09 | 0.48 | 23-NOV-16:11 |
December | 0.130055E+12 | 0.00 | 742.83 | 181592.94 | 25-DEC-16:13 | 0.00 | 41.08 | 59.81 | 0.63 | 0.00 | 0.14 | 0.54 | 25-DEC-16:13 |
Annual Sum or Average | 0.556043E+12 | 0.00 | 5993.02 | 0.00 | 42.47 | 54.56 | 0.24 | 0.00 | 0.05 | ||||
Minimum of Months | 0.388015E+09 | 0.00 | 107.05 | 31017.15 | 0.00 | 40.96 | 43.79 | 0.00 | 0.00 | 0.00 | 0.09 | ||
Maximum of Months | 0.130055E+12 | 0.00 | 742.83 | 190252.74 | 0.00 | 45.43 | 59.81 | 0.63 | 0.00 | 0.14 | 0.56 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.133833E+09 | 0.00 | 127.22 | 0.133833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4714.27 | 06-JAN-06:10 | 4714.27 | 06-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.217466E+10 | 0.00 | 104.50 | 0.217466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86517.71 | 27-FEB-15:00 | 86517.71 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.468935E+10 | 0.00 | 47.33 | 0.468935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112800.18 | 18-MAR-16:00 | 112800.18 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.302414E+11 | 0.00 | 129.17 | 0.301789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206925.09 | 27-APR-17:15 | 201823.33 | 27-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.593129E+11 | 0.00 | 251.50 | 0.586212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 219268.66 | 05-MAY-17:15 | 186581.66 | 04-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.104681E+12 | 0.00 | 399.33 | 0.104181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 221971.77 | 28-JUN-18:10 | 206366.12 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.174201E+12 | 0.00 | 546.83 | 0.167036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260555.84 | 15-JUL-18:03 | 226721.93 | 24-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.215343E+12 | 0.00 | 599.17 | 0.204413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 278209.08 | 10-AUG-18:10 | 237202.24 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.866994E+11 | 0.00 | 355.17 | 0.834142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 219548.82 | 14-SEP-17:15 | 185559.04 | 14-SEP-17:15 | 0.00 | 0.00 | 0.00 |
October | 0.173006E+11 | 0.00 | 127.83 | 0.172760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127248.04 | 04-OCT-15:27 | 127248.04 | 04-OCT-15:27 | 0.00 | 0.00 | 0.00 |
November | 0.397513E+10 | 0.00 | 44.89 | 0.397513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111924.20 | 04-NOV-15:13 | 111924.20 | 04-NOV-15:13 | 0.00 | 0.00 | 0.00 |
December | 65945965.06 | 0.00 | 55.66 | 65945965.06 | 0.00 | 0.00 | 0.00 | 0.00 | 4706.19 | 22-DEC-06:10 | 4706.19 | 22-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698818E+12 | 0.00 | 2788.60 | 0.676159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 65945965.06 | 0.00 | 44.89 | 65945965.06 | 0.00 | 0.00 | 0.00 | 0.00 | 4706.19 | 4706.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.215343E+12 | 0.00 | 599.17 | 0.204413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 278209.08 | 237202.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.100185E+09 | 0.00 | 4.67 | 0.100185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9453.00 | 27-FEB-16:15 | 9453.00 | 27-FEB-16:15 | 0.00 | 0.00 | 0.00 |
March | 0.213107E+09 | 0.00 | 17.00 | 0.213107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12388.66 | 18-MAR-16:00 | 12388.66 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.167058E+10 | 0.00 | 68.67 | 0.167058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17999.92 | 27-APR-15:11 | 17999.92 | 27-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.330427E+10 | 0.00 | 137.17 | 0.318830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20677.56 | 05-MAY-18:04 | 17234.28 | 05-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.589822E+10 | 0.00 | 255.17 | 0.589685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17796.86 | 28-JUN-15:12 | 17796.86 | 28-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.110614E+11 | 0.00 | 381.50 | 0.102725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23708.15 | 15-JUL-18:03 | 19276.58 | 24-JUL-15:12 | 0.00 | 0.00 | 0.00 |
August | 0.145691E+11 | 0.00 | 435.50 | 0.133624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23935.29 | 30-AUG-12:30 | 19693.29 | 29-AUG-15:12 | 0.00 | 0.00 | 0.00 |
September | 0.509662E+10 | 0.00 | 224.17 | 0.476262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22616.73 | 14-SEP-12:40 | 17100.78 | 12-SEP-15:12 | 0.00 | 0.00 | 0.00 |
October | 0.823568E+09 | 0.00 | 66.00 | 0.823568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14003.41 | 04-OCT-15:12 | 14003.41 | 04-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.200368E+09 | 0.00 | 14.67 | 0.179941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15533.96 | 04-NOV-13:00 | 12798.73 | 04-NOV-15:16 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429374E+11 | 0.00 | 1604.50 | 0.404701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.145691E+11 | 0.00 | 435.50 | 0.133624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23935.29 | 19693.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9116660.87 | 0.00 | 1.77 | 4985148.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3660.90 | 26-JAN-19:04 | 2735.46 | 09-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 41772626.10 | 0.00 | 14.25 | 22535752.30 | 0.00 | 0.00 | 0.00 | 0.00 | 11318.32 | 08-FEB-16:12 | 11318.32 | 08-FEB-16:12 | 0.00 | 0.00 | 0.00 |
March | 0.230730E+09 | 0.00 | 64.66 | 0.158864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11726.53 | 01-MAR-16:11 | 11726.53 | 01-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.970511E+09 | 0.00 | 206.43 | 0.567169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11674.06 | 13-APR-18:01 | 11674.06 | 13-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.205628E+10 | 0.00 | 382.08 | 0.110958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11729.34 | 20-MAY-18:01 | 11729.34 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.270842E+10 | 0.00 | 496.50 | 0.133764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11671.02 | 12-JUN-15:12 | 10596.18 | 30-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.480545E+10 | 0.00 | 621.69 | 0.256943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11969.19 | 16-JUL-15:12 | 10630.57 | 09-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.485684E+10 | 0.00 | 619.84 | 0.256311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12055.54 | 26-AUG-15:11 | 10798.47 | 18-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.284961E+10 | 0.00 | 480.52 | 0.137365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11907.80 | 23-SEP-08:61 | 10562.85 | 15-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.578002E+09 | 0.00 | 166.82 | 0.287544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12079.14 | 01-OCT-15:12 | 11721.08 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 70531863.41 | 0.00 | 19.37 | 27398582.47 | 0.00 | 0.00 | 0.00 | 0.00 | 11282.66 | 05-NOV-15:11 | 10309.77 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 9838585.54 | 0.00 | 1.92 | 5266177.84 | 0.00 | 0.00 | 0.00 | 0.00 | 5539.34 | 05-DEC-16:11 | 4876.50 | 05-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191871E+11 | 0.00 | 3075.84 | 0.100272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9116660.87 | 0.00 | 1.77 | 4985148.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3660.90 | 2735.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.485684E+10 | 0.00 | 621.69 | 0.256943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12079.14 | 11729.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7033570.61 | 0.00 | 1.62 | 3547952.64 | 0.00 | 0.00 | 0.00 | 0.00 | 3539.24 | 03-JAN-19:04 | 2424.94 | 03-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 10179305.77 | 0.00 | 4.61 | 5288870.66 | 0.00 | 0.00 | 0.00 | 0.00 | 8657.80 | 26-FEB-16:12 | 8657.80 | 26-FEB-16:12 | 0.00 | 0.00 | 0.00 |
March | 55177440.30 | 0.00 | 20.24 | 31268192.02 | 0.00 | 0.00 | 0.00 | 0.00 | 10204.20 | 01-MAR-16:11 | 10204.20 | 01-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.473941E+09 | 0.00 | 131.98 | 0.249844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11502.93 | 25-APR-17:42 | 11502.93 | 25-APR-17:42 | 0.00 | 0.00 | 0.00 |
May | 0.106245E+10 | 0.00 | 271.92 | 0.463118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11516.50 | 21-MAY-17:42 | 11516.50 | 21-MAY-17:42 | 0.00 | 0.00 | 0.00 |
June | 0.166957E+10 | 0.00 | 356.77 | 0.739791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11018.52 | 12-JUN-18:01 | 10061.05 | 22-JUN-16:21 | 0.00 | 0.00 | 0.00 |
July | 0.310157E+10 | 0.00 | 438.29 | 0.157482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11497.31 | 15-JUL-21:51 | 10667.15 | 14-JUL-16:21 | 0.00 | 0.00 | 0.00 |
August | 0.320575E+10 | 0.00 | 437.95 | 0.166665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11013.63 | 30-AUG-08:52 | 9928.90 | 10-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.126746E+10 | 0.00 | 310.92 | 0.464400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10981.36 | 24-SEP-18:11 | 10050.32 | 22-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 0.142120E+09 | 0.00 | 75.20 | 50584802.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10524.52 | 01-OCT-08:62 | 8587.47 | 23-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 16568471.10 | 0.00 | 4.71 | 6495312.38 | 0.00 | 0.00 | 0.00 | 0.00 | 10096.63 | 05-NOV-15:11 | 7991.97 | 05-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 7478569.27 | 0.00 | 1.69 | 3851862.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3131.89 | 14-DEC-19:04 | 2288.73 | 02-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110193E+11 | 0.00 | 2055.89 | 0.525965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7033570.61 | 0.00 | 1.62 | 3547952.64 | 0.00 | 0.00 | 0.00 | 0.00 | 3131.89 | 2288.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.320575E+10 | 0.00 | 438.29 | 0.166665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11516.50 | 11516.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.213278E+10 | 0.00 | 129.55 | 0.207397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17699.47 | 18-MAR-13:40 | 17699.47 | 18-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.786739E+10 | 0.00 | 338.09 | 0.496185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25341.33 | 27-APR-13:15 | 20130.26 | 02-APR-13:25 | 0.00 | 0.00 | 0.00 |
May | 0.126529E+11 | 0.00 | 475.94 | 0.530545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24733.78 | 04-MAY-13:15 | 18805.33 | 15-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.157937E+11 | 0.00 | 556.62 | 0.486235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19326.15 | 28-JUN-13:15 | 8947.38 | 28-JUN-13:15 | 0.00 | 0.00 | 0.00 |
July | 0.238912E+11 | 0.00 | 673.53 | 0.830467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26351.43 | 31-JUL-13:15 | 14830.44 | 31-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.281372E+11 | 0.00 | 675.72 | 0.109531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32790.68 | 24-AUG-13:00 | 22607.13 | 24-AUG-13:05 | 0.00 | 0.00 | 0.00 |
September | 0.217610E+11 | 0.00 | 571.62 | 0.892307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34086.96 | 14-SEP-13:15 | 24707.55 | 14-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.995156E+10 | 0.00 | 316.77 | 0.523788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32057.27 | 04-OCT-13:00 | 28325.19 | 04-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.861836E+09 | 0.00 | 37.60 | 0.245341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20679.02 | 04-NOV-13:25 | 9020.70 | 04-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123050E+12 | 0.00 | 3775.43 | 0.508677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.281372E+11 | 0.00 | 675.72 | 0.109531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34086.96 | 28325.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.972929E+09 | 0.00 | 88.93 | 0.409968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52003.39 | 12-JAN-09:02 | 52003.39 | 12-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.247813E+10 | 0.00 | 141.34 | 0.100100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61807.20 | 25-FEB-09:02 | 59546.41 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.552612E+10 | 0.00 | 286.68 | 0.282918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61306.40 | 18-MAR-20:42 | 61306.40 | 18-MAR-20:42 | 0.00 | 0.00 | 0.00 |
April | 0.116374E+11 | 0.00 | 402.48 | 0.639453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62998.08 | 24-APR-18:01 | 62998.08 | 24-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.189332E+11 | 0.00 | 429.26 | 0.109097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65519.80 | 06-MAY-21:52 | 64514.53 | 21-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.239658E+11 | 0.00 | 379.36 | 0.147287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67013.87 | 12-JUN-18:01 | 59688.10 | 26-JUN-21:52 | 0.00 | 0.00 | 0.00 |
July | 0.289265E+11 | 0.00 | 374.60 | 0.184814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68463.74 | 26-JUL-21:51 | 60765.06 | 30-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.298681E+11 | 0.00 | 382.19 | 0.179277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69156.72 | 26-AUG-21:52 | 60616.64 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.200664E+11 | 0.00 | 376.92 | 0.102211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66793.13 | 15-SEP-21:52 | 59543.50 | 16-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.971979E+10 | 0.00 | 412.40 | 0.421202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62750.09 | 04-OCT-21:12 | 62750.09 | 04-OCT-21:12 | 0.00 | 0.00 | 0.00 |
November | 0.446587E+10 | 0.00 | 230.16 | 0.167093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62668.75 | 05-NOV-08:62 | 56411.69 | 18-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.901958E+09 | 0.00 | 93.34 | 0.443020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60931.26 | 03-DEC-09:02 | 60931.26 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157462E+12 | 0.00 | 3597.67 | 0.892292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.901958E+09 | 0.00 | 88.93 | 0.409968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52003.39 | 52003.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.298681E+11 | 0.00 | 429.26 | 0.184814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69156.72 | 64514.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8634411.71 | 0.00 | 1.76 | 4730409.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3280.64 | 03-JAN-19:04 | 2731.74 | 09-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 29217694.47 | 0.00 | 16.09 | 15400191.04 | 0.00 | 0.00 | 0.00 | 0.00 | 7797.40 | 12-FEB-09:01 | 7797.40 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.172210E+09 | 0.00 | 61.71 | 0.116562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10200.70 | 25-MAR-15:11 | 10200.70 | 25-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.942702E+09 | 0.00 | 244.24 | 0.509126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10370.67 | 30-APR-08:62 | 10131.44 | 19-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.172576E+10 | 0.00 | 375.78 | 0.866790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10520.30 | 14-MAY-18:01 | 10520.30 | 14-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.290533E+10 | 0.00 | 541.61 | 0.147124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10451.62 | 12-JUN-15:12 | 9523.49 | 21-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.412182E+10 | 0.00 | 637.94 | 0.209667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10769.25 | 11-JUL-15:11 | 9640.07 | 10-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.479693E+10 | 0.00 | 631.23 | 0.250353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10844.24 | 30-AUG-08:62 | 9614.58 | 12-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.253638E+10 | 0.00 | 457.16 | 0.121070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10749.02 | 24-SEP-15:11 | 9622.86 | 02-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.551745E+09 | 0.00 | 166.33 | 0.277194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10541.25 | 01-OCT-15:12 | 10276.85 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 59140700.91 | 0.00 | 22.73 | 20774775.71 | 0.00 | 0.00 | 0.00 | 0.00 | 10549.83 | 04-NOV-15:11 | 8801.33 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 12514377.15 | 0.00 | 6.23 | 6352749.19 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.65 | 02-DEC-09:02 | 3494.19 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178624E+11 | 0.00 | 3162.80 | 0.909908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8634411.71 | 0.00 | 1.76 | 4730409.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3280.64 | 2731.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.479693E+10 | 0.00 | 637.94 | 0.250353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10844.24 | 10520.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6919177.14 | 0.00 | 1.78 | 3451096.01 | 0.00 | 0.00 | 0.00 | 0.00 | 3658.95 | 03-JAN-19:04 | 2793.52 | 03-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 8831195.84 | 0.00 | 2.12 | 4804634.64 | 0.00 | 0.00 | 0.00 | 0.00 | 5287.47 | 25-FEB-09:02 | 2782.74 | 25-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 34158710.77 | 0.00 | 14.62 | 21389683.34 | 0.00 | 0.00 | 0.00 | 0.00 | 8928.64 | 25-MAR-08:62 | 8928.64 | 25-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.475507E+09 | 0.00 | 146.69 | 0.240878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9507.11 | 30-APR-08:62 | 9107.47 | 25-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.986737E+09 | 0.00 | 261.06 | 0.464692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9621.63 | 06-MAY-08:51 | 9095.87 | 12-MAY-19:01 | 0.00 | 0.00 | 0.00 |
June | 0.196647E+10 | 0.00 | 400.51 | 0.990624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9971.67 | 12-JUN-18:01 | 8937.06 | 10-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.269080E+10 | 0.00 | 460.68 | 0.135003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10381.14 | 31-JUL-08:51 | 9747.98 | 24-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.317911E+10 | 0.00 | 456.83 | 0.163206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10504.39 | 10-AUG-08:51 | 9719.24 | 13-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.120404E+10 | 0.00 | 289.68 | 0.528709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9747.74 | 23-SEP-08:61 | 9186.48 | 13-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.167989E+09 | 0.00 | 58.37 | 75050738.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9341.45 | 01-OCT-08:62 | 8500.23 | 07-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 16223801.67 | 0.00 | 5.14 | 6250788.50 | 0.00 | 0.00 | 0.00 | 0.00 | 7748.56 | 05-NOV-08:62 | 4975.77 | 05-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 7358677.53 | 0.00 | 1.68 | 3781304.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3041.87 | 14-DEC-19:04 | 2452.56 | 03-DEC-16:14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107442E+11 | 0.00 | 2099.16 | 0.532173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6919177.14 | 0.00 | 1.68 | 3451096.01 | 0.00 | 0.00 | 0.00 | 0.00 | 3041.87 | 2452.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.317911E+10 | 0.00 | 460.68 | 0.163206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10504.39 | 9747.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1418694.64 | 0.00 | 0.81 | 712588.37 | 0.00 | 0.00 | 0.00 | 0.00 | 808.13 | 02-JAN-19:05 | 668.33 | 14-JAN-16:14 | 0.00 | 0.00 | 0.00 |
February | 10265027.85 | 0.00 | 11.52 | 5217639.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2919.36 | 08-FEB-16:12 | 2919.36 | 08-FEB-16:12 | 0.00 | 0.00 | 0.00 |
March | 60011746.14 | 0.00 | 49.44 | 42961368.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3049.48 | 01-MAR-16:11 | 3049.48 | 01-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.265042E+09 | 0.00 | 182.77 | 0.166794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3123.03 | 30-APR-08:62 | 3048.68 | 13-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.567999E+09 | 0.00 | 356.80 | 0.336902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3050.08 | 20-MAY-18:01 | 3050.08 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.734647E+09 | 0.00 | 471.74 | 0.397152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.36 | 12-JUN-15:12 | 2738.50 | 29-JUN-15:12 | 0.00 | 0.00 | 0.00 |
July | 0.127967E+10 | 0.00 | 623.64 | 0.734795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.06 | 16-JUL-15:12 | 2777.86 | 12-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.124791E+10 | 0.00 | 598.57 | 0.703856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3192.47 | 20-AUG-08:62 | 2783.49 | 09-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.714783E+09 | 0.00 | 424.12 | 0.378388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3252.80 | 23-SEP-08:61 | 2791.78 | 03-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.135582E+09 | 0.00 | 126.78 | 73845902.93 | 0.00 | 0.00 | 0.00 | 0.00 | 3147.23 | 01-OCT-15:12 | 3050.27 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 18261151.72 | 0.00 | 15.15 | 7716265.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2988.36 | 05-NOV-15:11 | 2741.11 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 1620101.13 | 0.00 | 0.96 | 873526.73 | 0.00 | 0.00 | 0.00 | 0.00 | 902.12 | 28-DEC-16:15 | 607.66 | 02-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503721E+10 | 0.00 | 2862.30 | 0.284921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1418694.64 | 0.00 | 0.81 | 712588.37 | 0.00 | 0.00 | 0.00 | 0.00 | 808.13 | 607.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127967E+10 | 0.00 | 623.64 | 0.734795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3252.80 | 3050.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 900553.73 | 0.00 | 0.59 | 450150.41 | 0.00 | 0.00 | 0.00 | 0.00 | 841.51 | 27-JAN-19:05 | 643.51 | 10-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 2697755.04 | 0.00 | 3.48 | 1385746.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.91 | 26-FEB-16:12 | 1706.91 | 26-FEB-16:12 | 0.00 | 0.00 | 0.00 |
March | 13757941.16 | 0.00 | 17.82 | 7773386.45 | 0.00 | 0.00 | 0.00 | 0.00 | 2628.67 | 01-MAR-16:11 | 2628.67 | 01-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.129780E+09 | 0.00 | 113.12 | 75280598.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3021.95 | 25-APR-17:42 | 3021.95 | 25-APR-17:42 | 0.00 | 0.00 | 0.00 |
May | 0.295792E+09 | 0.00 | 256.05 | 0.142642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3060.94 | 21-MAY-17:42 | 3060.94 | 21-MAY-17:42 | 0.00 | 0.00 | 0.00 |
June | 0.462660E+09 | 0.00 | 351.47 | 0.223476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2879.62 | 12-JUN-18:01 | 2611.63 | 22-JUN-16:21 | 0.00 | 0.00 | 0.00 |
July | 0.860628E+09 | 0.00 | 454.27 | 0.463563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3115.33 | 15-JUL-21:51 | 2808.55 | 25-JUL-16:52 | 0.00 | 0.00 | 0.00 |
August | 0.836275E+09 | 0.00 | 438.79 | 0.465363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2912.36 | 30-AUG-08:52 | 2637.37 | 06-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.300318E+09 | 0.00 | 266.39 | 0.118864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2941.54 | 23-SEP-08:61 | 2733.44 | 22-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 27494511.59 | 0.00 | 42.66 | 10747837.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2829.54 | 01-OCT-08:62 | 2213.74 | 07-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 4618432.42 | 0.00 | 3.02 | 1978519.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2641.99 | 05-NOV-15:11 | 2031.31 | 05-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 1008267.23 | 0.00 | 0.80 | 466523.90 | 0.00 | 0.00 | 0.00 | 0.00 | 843.52 | 28-DEC-09:05 | 523.24 | 01-DEC-16:14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293593E+10 | 0.00 | 1948.46 | 0.151199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 900553.73 | 0.00 | 0.59 | 450150.41 | 0.00 | 0.00 | 0.00 | 0.00 | 841.51 | 523.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.860628E+09 | 0.00 | 454.27 | 0.465363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3115.33 | 3060.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 71414583.27 | 0.00 | 19.11 | 34353913.18 | 0.00 | 0.00 | 0.00 | 0.00 | 12876.40 | 20-JAN-16:11 | 12876.40 | 20-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.595951E+09 | 0.00 | 116.58 | 0.315976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17411.61 | 12-FEB-16:11 | 17411.61 | 12-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.132438E+10 | 0.00 | 209.20 | 0.883219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17415.21 | 26-MAR-15:11 | 17415.21 | 26-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.250532E+10 | 0.00 | 358.88 | 0.133427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17169.57 | 30-APR-15:12 | 16722.86 | 13-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.358171E+10 | 0.00 | 476.75 | 0.176233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17412.15 | 14-MAY-18:01 | 17412.15 | 14-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.446082E+10 | 0.00 | 566.08 | 0.205871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17453.68 | 12-JUN-18:01 | 16926.34 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.669178E+10 | 0.00 | 644.73 | 0.322885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17845.21 | 16-JUL-15:12 | 16048.20 | 26-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.759347E+10 | 0.00 | 636.84 | 0.388831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17706.20 | 16-AUG-15:11 | 15937.03 | 17-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.569754E+10 | 0.00 | 548.49 | 0.295779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17474.98 | 23-SEP-08:61 | 15942.35 | 15-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.247858E+10 | 0.00 | 364.39 | 0.123640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17414.27 | 04-OCT-18:01 | 17414.27 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.522024E+09 | 0.00 | 94.82 | 0.206826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17059.14 | 05-NOV-15:11 | 15544.77 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 0.276416E+09 | 0.00 | 62.53 | 0.178501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16216.74 | 03-DEC-19:02 | 16216.74 | 03-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357994E+11 | 0.00 | 4098.40 | 0.180855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 71414583.27 | 0.00 | 19.11 | 34353913.18 | 0.00 | 0.00 | 0.00 | 0.00 | 12876.40 | 12876.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.759347E+10 | 0.00 | 644.73 | 0.388831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17845.21 | 17415.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.59 | 98.31 | 64.28 | 187.00 | 356.73 | 0.00 | 0.00 | 0.00 |
February | 248.45 | 155.78 | 92.67 | 335.70 | 311.52 | 0.00 | 0.00 | 0.00 |
March | 259.22 | 137.15 | 122.07 | 378.80 | 260.35 | 0.00 | 0.00 | 0.00 |
April | 267.66 | 111.43 | 156.22 | 427.62 | 211.70 | 0.00 | 0.00 | 0.00 |
May | 246.69 | 69.44 | 177.25 | 407.54 | 172.64 | 0.00 | 0.00 | 0.00 |
June | 221.51 | 52.55 | 168.96 | 379.23 | 131.91 | 0.00 | 0.00 | 0.00 |
July | 239.08 | 79.44 | 159.64 | 453.72 | 120.18 | 0.00 | 0.00 | 0.00 |
August | 257.61 | 113.18 | 144.43 | 500.76 | 114.71 | 0.00 | 0.00 | 0.00 |
September | 291.97 | 157.69 | 134.28 | 515.83 | 163.78 | 0.00 | 0.00 | 0.00 |
October | 270.33 | 166.37 | 103.96 | 425.00 | 219.44 | 0.00 | 0.00 | 0.00 |
November | 163.74 | 95.13 | 68.61 | 209.15 | 281.34 | 0.00 | 0.00 | 0.00 |
December | 172.51 | 113.18 | 59.33 | 223.23 | 356.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.29 | 112.21 | 121.09 | 370.44 | 224.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.59 | 52.55 | 59.33 | 187.00 | 114.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 291.97 | 166.37 | 177.25 | 515.83 | 356.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 457.84 | 276.84 | 181.00 | 521.20 | 1008.21 | 0.00 | 0.00 | 0.00 |
February | 699.62 | 438.66 | 260.96 | 941.82 | 878.12 | 0.00 | 0.00 | 0.00 |
March | 729.95 | 386.21 | 343.73 | 1067.17 | 733.27 | 0.00 | 0.00 | 0.00 |
April | 753.70 | 313.79 | 439.91 | 1212.92 | 586.18 | 0.00 | 0.00 | 0.00 |
May | 694.65 | 195.53 | 499.12 | 1166.90 | 466.62 | 0.00 | 0.00 | 0.00 |
June | 623.76 | 147.98 | 475.78 | 1099.53 | 345.72 | 0.00 | 0.00 | 0.00 |
July | 673.24 | 223.71 | 449.53 | 1324.74 | 297.94 | 0.00 | 0.00 | 0.00 |
August | 725.42 | 318.71 | 406.71 | 1453.31 | 284.02 | 0.00 | 0.00 | 0.00 |
September | 822.16 | 444.04 | 378.12 | 1474.36 | 431.19 | 0.00 | 0.00 | 0.00 |
October | 761.22 | 468.48 | 292.74 | 1203.47 | 611.28 | 0.00 | 0.00 | 0.00 |
November | 461.08 | 267.89 | 193.19 | 584.66 | 796.90 | 0.00 | 0.00 | 0.00 |
December | 485.76 | 318.70 | 167.07 | 625.30 | 1006.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 656.93 | 315.96 | 340.97 | 1056.82 | 619.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.84 | 147.98 | 167.07 | 521.20 | 284.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 822.16 | 468.48 | 499.12 | 1474.36 | 1008.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 594.76 | 359.63 | 235.13 | 677.63 | 1399.72 | 0.00 | 0.00 | 0.00 |
February | 908.84 | 569.84 | 339.00 | 1227.17 | 1219.34 | 0.00 | 0.00 | 0.00 |
March | 948.24 | 501.71 | 446.53 | 1392.62 | 1027.79 | 0.00 | 0.00 | 0.00 |
April | 979.10 | 407.63 | 571.47 | 1579.70 | 828.08 | 0.00 | 0.00 | 0.00 |
May | 902.39 | 254.00 | 648.39 | 1514.05 | 670.61 | 0.00 | 0.00 | 0.00 |
June | 810.30 | 192.23 | 618.06 | 1418.80 | 505.85 | 0.00 | 0.00 | 0.00 |
July | 874.58 | 290.61 | 583.97 | 1713.83 | 440.65 | 0.00 | 0.00 | 0.00 |
August | 942.36 | 414.02 | 528.34 | 1884.72 | 420.32 | 0.00 | 0.00 | 0.00 |
September | 1068.03 | 576.83 | 491.19 | 1920.22 | 620.85 | 0.00 | 0.00 | 0.00 |
October | 988.87 | 608.59 | 380.29 | 1566.89 | 867.09 | 0.00 | 0.00 | 0.00 |
November | 598.97 | 348.00 | 250.97 | 758.54 | 1120.45 | 0.00 | 0.00 | 0.00 |
December | 631.04 | 414.00 | 217.03 | 812.91 | 1399.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 853.39 | 410.45 | 442.94 | 1372.93 | 875.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 594.76 | 192.23 | 217.03 | 677.63 | 420.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1068.03 | 608.59 | 648.39 | 1920.22 | 1399.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.15 | 19.44 | 12.71 | 37.30 | 71.48 | 0.00 | 0.00 | 0.00 |
February | 49.12 | 30.80 | 18.32 | 66.69 | 62.39 | 0.00 | 0.00 | 0.00 |
March | 51.25 | 27.12 | 24.13 | 75.21 | 51.94 | 0.00 | 0.00 | 0.00 |
April | 52.92 | 22.03 | 30.89 | 84.58 | 41.84 | 0.00 | 0.00 | 0.00 |
May | 48.77 | 13.73 | 35.05 | 80.48 | 33.38 | 0.00 | 0.00 | 0.00 |
June | 43.80 | 10.39 | 33.41 | 75.55 | 24.13 | 0.00 | 0.00 | 0.00 |
July | 47.27 | 15.71 | 31.56 | 91.23 | 20.50 | 0.00 | 0.00 | 0.00 |
August | 50.93 | 22.38 | 28.56 | 100.93 | 18.87 | 0.00 | 0.00 | 0.00 |
September | 57.73 | 31.18 | 26.55 | 103.30 | 29.99 | 0.00 | 0.00 | 0.00 |
October | 53.45 | 32.89 | 20.55 | 84.58 | 42.60 | 0.00 | 0.00 | 0.00 |
November | 32.37 | 18.81 | 13.56 | 41.74 | 55.97 | 0.00 | 0.00 | 0.00 |
December | 34.11 | 22.38 | 11.73 | 44.54 | 70.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.13 | 22.18 | 23.94 | 73.88 | 43.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.15 | 10.39 | 11.73 | 37.30 | 18.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.73 | 32.89 | 35.05 | 103.30 | 71.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 6.43 | 15.82 | 11.29 | 145.75 | 0.00 | 0.00 | 0.00 |
February | 39.93 | 14.84 | 25.09 | 35.51 | 126.01 | 0.00 | 0.00 | 0.00 |
March | 56.28 | 19.02 | 37.25 | 62.79 | 99.31 | 0.00 | 0.00 | 0.00 |
April | 85.83 | 32.96 | 52.86 | 119.76 | 76.49 | 0.00 | 0.00 | 0.00 |
May | 110.90 | 45.53 | 65.37 | 172.62 | 60.32 | 0.00 | 0.00 | 0.00 |
June | 106.19 | 41.39 | 64.80 | 171.79 | 43.61 | 0.00 | 0.00 | 0.00 |
July | 131.90 | 69.84 | 62.06 | 234.62 | 37.15 | 0.00 | 0.00 | 0.00 |
August | 109.23 | 56.20 | 53.03 | 197.98 | 34.69 | 0.00 | 0.00 | 0.00 |
September | 89.04 | 43.14 | 45.90 | 145.95 | 56.11 | 0.00 | 0.00 | 0.00 |
October | 50.58 | 20.79 | 29.78 | 63.96 | 82.58 | 0.00 | 0.00 | 0.00 |
November | 24.87 | 6.95 | 17.93 | 17.70 | 111.83 | 0.00 | 0.00 | 0.00 |
December | 20.87 | 7.06 | 13.80 | 14.36 | 143.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.84 | 30.47 | 40.38 | 104.48 | 84.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.87 | 6.43 | 13.80 | 11.29 | 34.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.90 | 69.84 | 65.37 | 234.62 | 145.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.07 | 0.00 | 7.07 | 0.13 | 81.23 | 0.00 | 0.00 | 0.00 |
February | 11.01 | 0.00 | 11.01 | 2.08 | 70.19 | 0.00 | 0.00 | 0.00 |
March | 16.22 | 0.00 | 16.22 | 8.17 | 54.25 | 0.00 | 0.00 | 0.00 |
April | 22.99 | 0.10 | 22.89 | 20.05 | 41.32 | 0.00 | 0.00 | 0.00 |
May | 29.37 | 0.71 | 28.66 | 32.77 | 31.79 | 0.00 | 0.00 | 0.00 |
June | 30.76 | 1.74 | 29.02 | 39.60 | 22.70 | 0.00 | 0.00 | 0.00 |
July | 29.18 | 1.97 | 27.21 | 43.25 | 19.81 | 0.00 | 0.00 | 0.00 |
August | 23.80 | 0.53 | 23.27 | 37.21 | 18.42 | 0.00 | 0.00 | 0.00 |
September | 18.56 | 0.01 | 18.56 | 20.25 | 31.03 | 0.00 | 0.00 | 0.00 |
October | 12.71 | 0.00 | 12.71 | 7.57 | 44.83 | 0.00 | 0.00 | 0.00 |
November | 8.01 | 0.00 | 8.01 | 1.21 | 61.56 | 0.00 | 0.00 | 0.00 |
December | 6.01 | 0.00 | 6.01 | 0.05 | 78.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.01 | 0.42 | 17.58 | 17.79 | 46.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.01 | 0.00 | 6.01 | 0.05 | 18.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.76 | 1.97 | 29.02 | 43.25 | 81.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 6.43 | 15.82 | 11.87 | 144.70 | 0.00 | 0.00 | 0.00 |
February | 39.93 | 14.84 | 25.09 | 36.84 | 124.50 | 0.00 | 0.00 | 0.00 |
March | 56.28 | 19.02 | 37.25 | 64.60 | 98.13 | 0.00 | 0.00 | 0.00 |
April | 85.83 | 32.96 | 52.86 | 121.33 | 75.99 | 0.00 | 0.00 | 0.00 |
May | 110.90 | 45.53 | 65.37 | 172.45 | 60.86 | 0.00 | 0.00 | 0.00 |
June | 106.19 | 41.39 | 64.80 | 170.88 | 44.72 | 0.00 | 0.00 | 0.00 |
July | 131.90 | 69.84 | 62.06 | 232.77 | 39.07 | 0.00 | 0.00 | 0.00 |
August | 109.23 | 56.20 | 53.03 | 197.59 | 36.12 | 0.00 | 0.00 | 0.00 |
September | 89.04 | 43.14 | 45.90 | 146.32 | 56.85 | 0.00 | 0.00 | 0.00 |
October | 50.58 | 20.79 | 29.78 | 65.75 | 81.46 | 0.00 | 0.00 | 0.00 |
November | 24.87 | 6.95 | 17.93 | 18.45 | 110.79 | 0.00 | 0.00 | 0.00 |
December | 20.87 | 7.06 | 13.80 | 15.08 | 142.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.84 | 30.47 | 40.38 | 104.94 | 84.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.87 | 6.43 | 13.80 | 11.87 | 36.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.90 | 69.84 | 65.37 | 232.77 | 144.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.71 | 15.55 | 10.17 | 29.91 | 54.60 | 0.00 | 0.00 | 0.00 |
February | 39.29 | 24.64 | 14.66 | 50.74 | 56.28 | 0.00 | 0.00 | 0.00 |
March | 40.99 | 21.69 | 19.30 | 54.08 | 57.56 | 0.00 | 0.00 | 0.00 |
April | 42.33 | 17.62 | 24.71 | 59.44 | 49.17 | 0.00 | 0.00 | 0.00 |
May | 39.01 | 10.98 | 28.03 | 55.99 | 41.15 | 0.00 | 0.00 | 0.00 |
June | 35.03 | 8.31 | 26.72 | 51.14 | 32.51 | 0.00 | 0.00 | 0.00 |
July | 37.81 | 12.56 | 25.25 | 64.21 | 29.07 | 0.00 | 0.00 | 0.00 |
August | 40.74 | 17.90 | 22.84 | 71.87 | 27.98 | 0.00 | 0.00 | 0.00 |
September | 46.17 | 24.94 | 21.24 | 74.99 | 38.93 | 0.00 | 0.00 | 0.00 |
October | 42.75 | 26.31 | 16.44 | 60.78 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 25.89 | 15.04 | 10.85 | 29.57 | 58.14 | 0.00 | 0.00 | 0.00 |
December | 27.28 | 17.90 | 9.38 | 34.23 | 60.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.89 | 17.74 | 19.15 | 53.09 | 46.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.71 | 8.31 | 9.38 | 29.57 | 27.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.17 | 26.31 | 28.03 | 74.99 | 60.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.66 | 0.00 | 5.66 | 0.05 | 68.73 | 0.00 | 0.00 | 0.00 |
February | 8.81 | 0.00 | 8.81 | 1.40 | 59.00 | 0.00 | 0.00 | 0.00 |
March | 12.98 | 0.00 | 12.98 | 5.95 | 45.14 | 0.00 | 0.00 | 0.00 |
April | 18.39 | 0.08 | 18.31 | 15.95 | 33.71 | 0.00 | 0.00 | 0.00 |
May | 23.50 | 0.56 | 22.93 | 27.14 | 25.34 | 0.00 | 0.00 | 0.00 |
June | 24.61 | 1.39 | 23.22 | 32.84 | 17.92 | 0.00 | 0.00 | 0.00 |
July | 23.35 | 1.57 | 21.77 | 36.64 | 15.08 | 0.00 | 0.00 | 0.00 |
August | 19.05 | 0.43 | 18.62 | 31.32 | 14.08 | 0.00 | 0.00 | 0.00 |
September | 14.85 | 0.01 | 14.85 | 17.01 | 24.33 | 0.00 | 0.00 | 0.00 |
October | 10.17 | 0.00 | 10.17 | 5.73 | 37.15 | 0.00 | 0.00 | 0.00 |
November | 6.41 | 0.00 | 6.41 | 0.75 | 52.30 | 0.00 | 0.00 | 0.00 |
December | 4.81 | 0.00 | 4.81 | 0.01 | 66.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.41 | 0.34 | 14.07 | 14.65 | 38.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.81 | 0.00 | 4.81 | 0.01 | 14.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.61 | 1.57 | 23.22 | 36.64 | 68.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.91 | 5.07 | 15.84 | 7.62 | 144.48 | 0.00 | 0.00 | 0.00 |
February | 38.71 | 13.56 | 25.14 | 30.23 | 122.88 | 0.00 | 0.00 | 0.00 |
March | 58.39 | 21.20 | 37.19 | 62.95 | 95.63 | 0.00 | 0.00 | 0.00 |
April | 90.69 | 37.96 | 52.73 | 124.85 | 73.14 | 0.00 | 0.00 | 0.00 |
May | 96.19 | 33.64 | 62.55 | 143.18 | 58.27 | 0.00 | 0.00 | 0.00 |
June | 115.36 | 50.49 | 64.86 | 187.76 | 41.57 | 0.00 | 0.00 | 0.00 |
July | 107.50 | 48.54 | 58.96 | 186.06 | 34.02 | 0.00 | 0.00 | 0.00 |
August | 106.04 | 53.49 | 52.55 | 189.57 | 32.15 | 0.00 | 0.00 | 0.00 |
September | 78.41 | 36.52 | 41.89 | 122.17 | 53.44 | 0.00 | 0.00 | 0.00 |
October | 50.89 | 21.73 | 29.16 | 62.37 | 80.01 | 0.00 | 0.00 | 0.00 |
November | 24.68 | 6.82 | 17.86 | 16.03 | 110.22 | 0.00 | 0.00 | 0.00 |
December | 20.09 | 6.26 | 13.83 | 10.65 | 141.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.45 | 28.00 | 39.44 | 95.63 | 82.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.09 | 5.07 | 13.83 | 7.62 | 32.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.36 | 53.49 | 64.86 | 189.57 | 144.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.15 | 19.44 | 12.71 | 37.29 | 71.41 | 0.00 | 0.00 | 0.00 |
February | 49.12 | 30.80 | 18.32 | 66.58 | 62.27 | 0.00 | 0.00 | 0.00 |
March | 51.25 | 27.12 | 24.13 | 74.81 | 51.85 | 0.00 | 0.00 | 0.00 |
April | 52.92 | 22.03 | 30.89 | 83.89 | 41.76 | 0.00 | 0.00 | 0.00 |
May | 48.77 | 13.73 | 35.05 | 80.31 | 33.05 | 0.00 | 0.00 | 0.00 |
June | 43.80 | 10.39 | 33.41 | 74.85 | 24.03 | 0.00 | 0.00 | 0.00 |
July | 47.27 | 15.71 | 31.56 | 91.14 | 20.10 | 0.00 | 0.00 | 0.00 |
August | 50.93 | 22.38 | 28.56 | 100.56 | 18.68 | 0.00 | 0.00 | 0.00 |
September | 57.73 | 31.18 | 26.55 | 103.15 | 29.57 | 0.00 | 0.00 | 0.00 |
October | 53.45 | 32.89 | 20.55 | 84.29 | 42.46 | 0.00 | 0.00 | 0.00 |
November | 32.37 | 18.81 | 13.56 | 41.67 | 55.91 | 0.00 | 0.00 | 0.00 |
December | 34.11 | 22.38 | 11.73 | 44.51 | 70.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.13 | 22.18 | 23.94 | 73.62 | 43.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.15 | 10.39 | 11.73 | 37.29 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.73 | 32.89 | 35.05 | 103.15 | 71.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.07 | 0.00 | 7.07 | 0.12 | 81.22 | 0.00 | 0.00 | 0.00 |
February | 11.01 | 0.00 | 11.01 | 2.06 | 70.15 | 0.00 | 0.00 | 0.00 |
March | 16.22 | 0.00 | 16.22 | 7.89 | 54.19 | 0.00 | 0.00 | 0.00 |
April | 22.99 | 0.10 | 22.89 | 19.51 | 41.31 | 0.00 | 0.00 | 0.00 |
May | 29.37 | 0.71 | 28.66 | 32.98 | 31.32 | 0.00 | 0.00 | 0.00 |
June | 30.76 | 1.74 | 29.02 | 39.03 | 22.48 | 0.00 | 0.00 | 0.00 |
July | 29.18 | 1.97 | 27.21 | 43.57 | 19.07 | 0.00 | 0.00 | 0.00 |
August | 23.80 | 0.53 | 23.27 | 36.71 | 18.10 | 0.00 | 0.00 | 0.00 |
September | 18.56 | 0.01 | 18.56 | 20.32 | 30.32 | 0.00 | 0.00 | 0.00 |
October | 12.71 | 0.00 | 12.71 | 7.35 | 44.63 | 0.00 | 0.00 | 0.00 |
November | 8.01 | 0.00 | 8.01 | 1.17 | 61.48 | 0.00 | 0.00 | 0.00 |
December | 6.01 | 0.00 | 6.01 | 0.04 | 78.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.01 | 0.42 | 17.58 | 17.66 | 45.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.01 | 0.00 | 6.01 | 0.04 | 18.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.76 | 1.97 | 29.02 | 43.57 | 81.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.91 | 5.07 | 15.84 | 7.82 | 143.11 | 0.00 | 0.00 | 0.00 |
February | 38.71 | 13.56 | 25.14 | 30.98 | 120.75 | 0.00 | 0.00 | 0.00 |
March | 58.39 | 21.20 | 37.19 | 64.69 | 94.23 | 0.00 | 0.00 | 0.00 |
April | 90.69 | 37.96 | 52.73 | 126.48 | 72.50 | 0.00 | 0.00 | 0.00 |
May | 96.19 | 33.64 | 62.55 | 143.82 | 58.50 | 0.00 | 0.00 | 0.00 |
June | 115.36 | 50.49 | 64.86 | 187.41 | 42.64 | 0.00 | 0.00 | 0.00 |
July | 107.50 | 48.54 | 58.96 | 185.28 | 35.46 | 0.00 | 0.00 | 0.00 |
August | 106.04 | 53.49 | 52.55 | 189.06 | 33.38 | 0.00 | 0.00 | 0.00 |
September | 78.41 | 36.52 | 41.89 | 123.18 | 53.64 | 0.00 | 0.00 | 0.00 |
October | 50.89 | 21.73 | 29.16 | 64.19 | 78.63 | 0.00 | 0.00 | 0.00 |
November | 24.68 | 6.82 | 17.86 | 16.51 | 108.80 | 0.00 | 0.00 | 0.00 |
December | 20.09 | 6.26 | 13.83 | 10.93 | 139.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.45 | 28.00 | 39.44 | 96.20 | 81.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.09 | 5.07 | 13.83 | 7.82 | 33.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.36 | 53.49 | 64.86 | 189.06 | 143.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.96 | 0.00 | 8.96 | 0.07 | 110.83 | 0.00 | 0.00 | 0.00 |
February | 13.94 | 0.00 | 13.94 | 2.27 | 95.07 | 0.00 | 0.00 | 0.00 |
March | 20.54 | 0.00 | 20.54 | 9.47 | 71.98 | 0.00 | 0.00 | 0.00 |
April | 29.11 | 0.12 | 28.99 | 25.79 | 53.78 | 0.00 | 0.00 | 0.00 |
May | 37.19 | 0.89 | 36.30 | 43.76 | 41.20 | 0.00 | 0.00 | 0.00 |
June | 38.95 | 2.20 | 36.75 | 52.59 | 29.51 | 0.00 | 0.00 | 0.00 |
July | 36.95 | 2.49 | 34.47 | 57.88 | 25.62 | 0.00 | 0.00 | 0.00 |
August | 30.15 | 0.68 | 29.47 | 48.75 | 24.77 | 0.00 | 0.00 | 0.00 |
September | 23.51 | 0.01 | 23.50 | 26.71 | 40.60 | 0.00 | 0.00 | 0.00 |
October | 16.10 | 0.00 | 16.10 | 9.11 | 59.65 | 0.00 | 0.00 | 0.00 |
November | 10.14 | 0.00 | 10.14 | 1.27 | 83.72 | 0.00 | 0.00 | 0.00 |
December | 7.61 | 0.00 | 7.61 | 0.02 | 107.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.81 | 0.54 | 22.27 | 23.27 | 61.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 7.61 | 0.00 | 7.61 | 0.02 | 24.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.95 | 2.49 | 36.75 | 57.88 | 110.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.30 | 0.00 | 3.30 | 0.02 | 40.86 | 0.00 | 0.00 | 0.00 |
February | 5.14 | 0.00 | 5.14 | 0.84 | 35.05 | 0.00 | 0.00 | 0.00 |
March | 7.57 | 0.00 | 7.57 | 3.49 | 26.54 | 0.00 | 0.00 | 0.00 |
April | 10.73 | 0.05 | 10.69 | 9.51 | 19.83 | 0.00 | 0.00 | 0.00 |
May | 13.71 | 0.33 | 13.38 | 16.13 | 15.19 | 0.00 | 0.00 | 0.00 |
June | 14.36 | 0.81 | 13.55 | 19.39 | 10.88 | 0.00 | 0.00 | 0.00 |
July | 13.62 | 0.92 | 12.71 | 21.34 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 11.11 | 0.25 | 10.86 | 17.97 | 9.13 | 0.00 | 0.00 | 0.00 |
September | 8.67 | 0.00 | 8.66 | 9.85 | 14.97 | 0.00 | 0.00 | 0.00 |
October | 5.94 | 0.00 | 5.94 | 3.36 | 21.99 | 0.00 | 0.00 | 0.00 |
November | 3.74 | 0.00 | 3.74 | 0.47 | 30.86 | 0.00 | 0.00 | 0.00 |
December | 2.81 | 0.00 | 2.81 | 0.01 | 39.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.41 | 0.20 | 8.21 | 8.58 | 22.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2.81 | 0.00 | 2.81 | 0.01 | 9.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.36 | 0.92 | 13.55 | 21.34 | 40.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.00 | 9.07 | 5.93 | 16.95 | 35.38 | 0.00 | 0.00 | 0.00 |
February | 22.92 | 14.37 | 8.55 | 30.84 | 30.45 | 0.00 | 0.00 | 0.00 |
March | 23.91 | 12.65 | 11.26 | 35.14 | 25.06 | 0.00 | 0.00 | 0.00 |
April | 24.69 | 10.28 | 14.41 | 39.95 | 19.90 | 0.00 | 0.00 | 0.00 |
May | 22.76 | 6.41 | 16.35 | 38.33 | 16.05 | 0.00 | 0.00 | 0.00 |
June | 20.44 | 4.85 | 15.59 | 35.97 | 11.88 | 0.00 | 0.00 | 0.00 |
July | 22.06 | 7.33 | 14.73 | 43.32 | 10.33 | 0.00 | 0.00 | 0.00 |
August | 23.77 | 10.44 | 13.32 | 47.63 | 9.76 | 0.00 | 0.00 | 0.00 |
September | 26.94 | 14.55 | 12.39 | 48.72 | 14.69 | 0.00 | 0.00 | 0.00 |
October | 24.94 | 15.35 | 9.59 | 39.70 | 20.57 | 0.00 | 0.00 | 0.00 |
November | 15.11 | 8.78 | 6.33 | 19.23 | 27.58 | 0.00 | 0.00 | 0.00 |
December | 15.91 | 10.44 | 5.47 | 20.49 | 35.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.52 | 10.35 | 11.17 | 34.71 | 21.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.00 | 4.85 | 5.47 | 16.95 | 9.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.94 | 15.35 | 16.35 | 48.72 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.71 | 24.62 | 16.09 | 46.01 | 96.02 | 0.00 | 0.00 | 0.00 |
February | 62.21 | 39.01 | 23.20 | 83.69 | 82.66 | 0.00 | 0.00 | 0.00 |
March | 64.91 | 34.34 | 30.57 | 95.38 | 68.01 | 0.00 | 0.00 | 0.00 |
April | 67.02 | 27.90 | 39.12 | 108.44 | 54.02 | 0.00 | 0.00 | 0.00 |
May | 61.77 | 17.39 | 44.38 | 104.03 | 43.57 | 0.00 | 0.00 | 0.00 |
June | 55.47 | 13.16 | 42.31 | 97.62 | 32.24 | 0.00 | 0.00 | 0.00 |
July | 59.87 | 19.89 | 39.97 | 117.57 | 28.04 | 0.00 | 0.00 | 0.00 |
August | 64.51 | 28.34 | 36.17 | 129.26 | 26.49 | 0.00 | 0.00 | 0.00 |
September | 73.11 | 39.48 | 33.62 | 132.23 | 39.87 | 0.00 | 0.00 | 0.00 |
October | 67.69 | 41.66 | 26.03 | 107.75 | 55.84 | 0.00 | 0.00 | 0.00 |
November | 41.00 | 23.82 | 17.18 | 52.19 | 74.86 | 0.00 | 0.00 | 0.00 |
December | 43.19 | 28.34 | 14.86 | 55.62 | 95.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.42 | 28.10 | 30.32 | 94.20 | 57.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.71 | 13.16 | 14.86 | 46.01 | 26.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.11 | 41.66 | 44.38 | 132.23 | 96.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.15 | 19.44 | 12.71 | 37.42 | 70.57 | 0.00 | 0.00 | 0.00 |
February | 49.12 | 30.80 | 18.32 | 66.64 | 61.65 | 0.00 | 0.00 | 0.00 |
March | 51.25 | 27.12 | 24.13 | 74.90 | 51.35 | 0.00 | 0.00 | 0.00 |
April | 52.92 | 22.03 | 30.89 | 83.83 | 41.58 | 0.00 | 0.00 | 0.00 |
May | 48.77 | 13.73 | 35.05 | 79.46 | 33.22 | 0.00 | 0.00 | 0.00 |
June | 43.80 | 10.39 | 33.41 | 74.47 | 23.99 | 0.00 | 0.00 | 0.00 |
July | 47.27 | 15.71 | 31.56 | 90.15 | 20.36 | 0.00 | 0.00 | 0.00 |
August | 50.93 | 22.38 | 28.56 | 100.06 | 18.60 | 0.00 | 0.00 | 0.00 |
September | 57.73 | 31.18 | 26.55 | 102.67 | 29.65 | 0.00 | 0.00 | 0.00 |
October | 53.45 | 32.89 | 20.55 | 84.22 | 41.98 | 0.00 | 0.00 | 0.00 |
November | 32.37 | 18.81 | 13.56 | 41.78 | 55.11 | 0.00 | 0.00 | 0.00 |
December | 34.11 | 22.38 | 11.73 | 44.62 | 69.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.13 | 22.18 | 23.94 | 73.38 | 43.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.15 | 10.39 | 11.73 | 37.42 | 18.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.73 | 32.89 | 35.05 | 102.67 | 70.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 6.43 | 15.82 | 11.51 | 143.64 | 0.00 | 0.00 | 0.00 |
February | 39.93 | 14.84 | 25.09 | 35.58 | 124.24 | 0.00 | 0.00 | 0.00 |
March | 56.28 | 19.02 | 37.25 | 62.48 | 98.02 | 0.00 | 0.00 | 0.00 |
April | 85.83 | 32.96 | 52.86 | 118.44 | 75.90 | 0.00 | 0.00 | 0.00 |
May | 110.90 | 45.53 | 65.37 | 170.49 | 59.93 | 0.00 | 0.00 | 0.00 |
June | 106.19 | 41.39 | 64.80 | 169.53 | 43.27 | 0.00 | 0.00 | 0.00 |
July | 131.90 | 69.84 | 62.06 | 232.19 | 36.81 | 0.00 | 0.00 | 0.00 |
August | 109.23 | 56.20 | 53.03 | 196.24 | 34.12 | 0.00 | 0.00 | 0.00 |
September | 89.04 | 43.14 | 45.90 | 144.77 | 55.36 | 0.00 | 0.00 | 0.00 |
October | 50.58 | 20.79 | 29.78 | 63.63 | 81.21 | 0.00 | 0.00 | 0.00 |
November | 24.87 | 6.95 | 17.93 | 17.86 | 109.89 | 0.00 | 0.00 | 0.00 |
December | 20.87 | 7.06 | 13.80 | 14.52 | 141.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.84 | 30.47 | 40.38 | 103.55 | 83.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.87 | 6.43 | 13.80 | 11.51 | 34.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.90 | 69.84 | 65.37 | 232.19 | 143.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.07 | 0.00 | 7.07 | 0.15 | 80.02 | 0.00 | 0.00 | 0.00 |
February | 11.01 | 0.00 | 11.01 | 2.15 | 69.11 | 0.00 | 0.00 | 0.00 |
March | 16.22 | 0.00 | 16.22 | 8.26 | 53.51 | 0.00 | 0.00 | 0.00 |
April | 22.99 | 0.10 | 22.89 | 19.75 | 41.02 | 0.00 | 0.00 | 0.00 |
May | 29.37 | 0.71 | 28.66 | 31.86 | 31.81 | 0.00 | 0.00 | 0.00 |
June | 30.76 | 1.74 | 29.02 | 38.48 | 22.85 | 0.00 | 0.00 | 0.00 |
July | 29.18 | 1.97 | 27.21 | 42.09 | 20.08 | 0.00 | 0.00 | 0.00 |
August | 23.80 | 0.53 | 23.27 | 36.62 | 18.35 | 0.00 | 0.00 | 0.00 |
September | 18.56 | 0.01 | 18.56 | 19.82 | 30.95 | 0.00 | 0.00 | 0.00 |
October | 12.71 | 0.00 | 12.71 | 7.69 | 44.03 | 0.00 | 0.00 | 0.00 |
November | 8.01 | 0.00 | 8.01 | 1.27 | 60.40 | 0.00 | 0.00 | 0.00 |
December | 6.01 | 0.00 | 6.01 | 0.06 | 77.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.01 | 0.42 | 17.58 | 17.45 | 45.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.01 | 0.00 | 6.01 | 0.06 | 18.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.76 | 1.97 | 29.02 | 42.09 | 80.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 6.43 | 15.82 | 12.04 | 142.76 | 0.00 | 0.00 | 0.00 |
February | 39.93 | 14.84 | 25.09 | 37.02 | 122.77 | 0.00 | 0.00 | 0.00 |
March | 56.28 | 19.02 | 37.25 | 64.46 | 96.79 | 0.00 | 0.00 | 0.00 |
April | 85.83 | 32.96 | 52.86 | 120.03 | 75.46 | 0.00 | 0.00 | 0.00 |
May | 110.90 | 45.53 | 65.37 | 169.85 | 60.90 | 0.00 | 0.00 | 0.00 |
June | 106.19 | 41.39 | 64.80 | 167.96 | 44.95 | 0.00 | 0.00 | 0.00 |
July | 131.90 | 69.84 | 62.06 | 229.50 | 39.54 | 0.00 | 0.00 | 0.00 |
August | 109.23 | 56.20 | 53.03 | 195.55 | 35.96 | 0.00 | 0.00 | 0.00 |
September | 89.04 | 43.14 | 45.90 | 144.82 | 56.58 | 0.00 | 0.00 | 0.00 |
October | 50.58 | 20.79 | 29.78 | 65.60 | 80.02 | 0.00 | 0.00 | 0.00 |
November | 24.87 | 6.95 | 17.93 | 18.69 | 108.86 | 0.00 | 0.00 | 0.00 |
December | 20.87 | 7.06 | 13.80 | 15.30 | 140.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.84 | 30.47 | 40.38 | 103.84 | 83.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.87 | 6.43 | 13.80 | 12.04 | 35.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.90 | 69.84 | 65.37 | 229.50 | 142.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.15 | 28.51 | 18.64 | 52.77 | 107.19 | 0.00 | 0.00 | 0.00 |
February | 72.04 | 45.17 | 26.87 | 94.76 | 93.86 | 0.00 | 0.00 | 0.00 |
March | 75.17 | 39.77 | 35.40 | 107.26 | 78.04 | 0.00 | 0.00 | 0.00 |
April | 77.61 | 32.31 | 45.30 | 121.08 | 62.19 | 0.00 | 0.00 | 0.00 |
May | 71.53 | 20.13 | 51.40 | 116.18 | 48.73 | 0.00 | 0.00 | 0.00 |
June | 64.23 | 15.24 | 48.99 | 109.34 | 34.88 | 0.00 | 0.00 | 0.00 |
July | 69.33 | 23.04 | 46.29 | 133.08 | 29.02 | 0.00 | 0.00 | 0.00 |
August | 74.70 | 32.82 | 41.88 | 147.09 | 26.75 | 0.00 | 0.00 | 0.00 |
September | 84.66 | 45.73 | 38.94 | 149.84 | 43.65 | 0.00 | 0.00 | 0.00 |
October | 78.39 | 48.24 | 30.15 | 121.15 | 63.93 | 0.00 | 0.00 | 0.00 |
November | 47.48 | 27.59 | 19.89 | 59.28 | 84.21 | 0.00 | 0.00 | 0.00 |
December | 50.02 | 32.82 | 17.20 | 63.35 | 106.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.65 | 32.54 | 35.11 | 106.32 | 64.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.15 | 15.24 | 17.20 | 52.77 | 26.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.66 | 48.24 | 51.40 | 149.84 | 107.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.51 | 0.00 | 49.51 | 0.37 | 602.23 | 0.00 | 0.00 | 0.00 |
February | 77.05 | 0.00 | 77.05 | 12.38 | 518.15 | 0.00 | 0.00 | 0.00 |
March | 113.53 | 0.00 | 113.53 | 52.13 | 398.70 | 0.00 | 0.00 | 0.00 |
April | 160.89 | 0.68 | 160.21 | 140.98 | 301.79 | 0.00 | 0.00 | 0.00 |
May | 205.55 | 4.94 | 200.61 | 240.33 | 230.80 | 0.00 | 0.00 | 0.00 |
June | 215.28 | 12.18 | 203.10 | 291.40 | 165.73 | 0.00 | 0.00 | 0.00 |
July | 204.25 | 13.76 | 190.49 | 327.18 | 140.46 | 0.00 | 0.00 | 0.00 |
August | 166.63 | 3.73 | 162.89 | 280.98 | 132.87 | 0.00 | 0.00 | 0.00 |
September | 129.93 | 0.05 | 129.88 | 152.96 | 218.56 | 0.00 | 0.00 | 0.00 |
October | 89.00 | 0.00 | 89.00 | 51.07 | 330.67 | 0.00 | 0.00 | 0.00 |
November | 56.06 | 0.00 | 56.06 | 6.84 | 459.14 | 0.00 | 0.00 | 0.00 |
December | 42.07 | 0.00 | 42.07 | 0.12 | 584.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.05 | 2.97 | 123.09 | 130.49 | 339.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.07 | 0.00 | 42.07 | 0.12 | 132.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.28 | 13.76 | 203.10 | 327.18 | 602.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.51 | 0.00 | 49.51 | 0.22 | 626.65 | 0.00 | 0.00 | 0.00 |
February | 77.05 | 0.00 | 77.05 | 10.78 | 541.65 | 0.00 | 0.00 | 0.00 |
March | 113.53 | 0.00 | 113.53 | 46.97 | 418.68 | 0.00 | 0.00 | 0.00 |
April | 160.89 | 0.68 | 160.21 | 132.95 | 316.80 | 0.00 | 0.00 | 0.00 |
May | 205.55 | 4.94 | 200.61 | 231.27 | 241.22 | 0.00 | 0.00 | 0.00 |
June | 215.28 | 12.18 | 203.10 | 281.57 | 173.48 | 0.00 | 0.00 | 0.00 |
July | 204.25 | 13.76 | 190.49 | 318.03 | 147.44 | 0.00 | 0.00 | 0.00 |
August | 166.63 | 3.73 | 162.89 | 272.37 | 140.38 | 0.00 | 0.00 | 0.00 |
September | 129.93 | 0.05 | 129.88 | 146.34 | 229.83 | 0.00 | 0.00 | 0.00 |
October | 89.00 | 0.00 | 89.00 | 46.26 | 349.19 | 0.00 | 0.00 | 0.00 |
November | 56.06 | 0.00 | 56.06 | 5.62 | 483.15 | 0.00 | 0.00 | 0.00 |
December | 42.07 | 0.00 | 42.07 | 0.05 | 608.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.05 | 2.97 | 123.09 | 125.11 | 355.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.07 | 0.00 | 42.07 | 0.05 | 140.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.28 | 13.76 | 203.10 | 318.03 | 626.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.07 | 0.00 | 7.07 | 5.00 | 54.87 | 0.00 | 0.00 | 0.00 |
February | 11.01 | 0.00 | 11.01 | 13.54 | 49.35 | 0.00 | 0.00 | 0.00 |
March | 16.22 | 0.00 | 16.22 | 28.25 | 39.97 | 0.00 | 0.00 | 0.00 |
April | 22.99 | 0.10 | 22.89 | 48.86 | 32.58 | 0.00 | 0.00 | 0.00 |
May | 29.37 | 0.71 | 28.66 | 68.83 | 26.10 | 0.00 | 0.00 | 0.00 |
June | 30.76 | 1.74 | 29.02 | 79.95 | 19.67 | 0.00 | 0.00 | 0.00 |
July | 29.18 | 1.97 | 27.21 | 86.42 | 16.41 | 0.00 | 0.00 | 0.00 |
August | 23.80 | 0.53 | 23.27 | 79.34 | 15.29 | 0.00 | 0.00 | 0.00 |
September | 18.56 | 0.01 | 18.56 | 53.89 | 20.78 | 0.00 | 0.00 | 0.00 |
October | 12.71 | 0.00 | 12.71 | 29.25 | 30.71 | 0.00 | 0.00 | 0.00 |
November | 8.01 | 0.00 | 8.01 | 12.26 | 39.37 | 0.00 | 0.00 | 0.00 |
December | 6.01 | 0.00 | 6.01 | 5.11 | 52.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.01 | 0.42 | 17.58 | 42.73 | 33.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.01 | 0.00 | 6.01 | 5.00 | 15.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.76 | 1.97 | 29.02 | 86.42 | 54.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.82 | 10.15 | 31.68 | 45.04 | 199.73 | 0.00 | 0.00 | 0.00 |
February | 77.41 | 27.12 | 50.29 | 119.40 | 178.13 | 0.00 | 0.00 | 0.00 |
March | 116.78 | 42.40 | 74.38 | 216.78 | 146.03 | 0.00 | 0.00 | 0.00 |
April | 181.36 | 75.92 | 105.44 | 371.72 | 120.10 | 0.00 | 0.00 | 0.00 |
May | 192.36 | 67.27 | 125.09 | 421.96 | 97.09 | 0.00 | 0.00 | 0.00 |
June | 230.70 | 100.98 | 129.72 | 526.79 | 73.17 | 0.00 | 0.00 | 0.00 |
July | 214.98 | 97.08 | 117.90 | 530.94 | 60.82 | 0.00 | 0.00 | 0.00 |
August | 212.07 | 106.97 | 105.09 | 539.23 | 57.25 | 0.00 | 0.00 | 0.00 |
September | 156.81 | 73.03 | 83.78 | 378.09 | 77.44 | 0.00 | 0.00 | 0.00 |
October | 101.77 | 43.46 | 58.32 | 219.96 | 114.34 | 0.00 | 0.00 | 0.00 |
November | 49.36 | 13.64 | 35.72 | 83.79 | 145.35 | 0.00 | 0.00 | 0.00 |
December | 40.17 | 12.51 | 27.66 | 53.22 | 192.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.89 | 56.00 | 78.88 | 293.14 | 121.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.17 | 10.15 | 27.66 | 45.04 | 57.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.70 | 106.97 | 129.72 | 539.23 | 199.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.15 | 19.44 | 12.71 | 50.46 | 52.32 | 0.00 | 0.00 | 0.00 |
February | 49.12 | 30.80 | 18.32 | 86.27 | 47.35 | 0.00 | 0.00 | 0.00 |
March | 51.25 | 27.12 | 24.13 | 99.44 | 39.51 | 0.00 | 0.00 | 0.00 |
April | 52.92 | 22.03 | 30.89 | 114.90 | 33.17 | 0.00 | 0.00 | 0.00 |
May | 48.77 | 13.73 | 35.05 | 115.47 | 26.79 | 0.00 | 0.00 | 0.00 |
June | 43.80 | 10.39 | 33.41 | 114.22 | 20.47 | 0.00 | 0.00 | 0.00 |
July | 47.27 | 15.71 | 31.56 | 132.39 | 16.94 | 0.00 | 0.00 | 0.00 |
August | 50.93 | 22.38 | 28.56 | 142.21 | 15.53 | 0.00 | 0.00 | 0.00 |
September | 57.73 | 31.18 | 26.55 | 138.49 | 20.76 | 0.00 | 0.00 | 0.00 |
October | 53.45 | 32.89 | 20.55 | 110.59 | 30.60 | 0.00 | 0.00 | 0.00 |
November | 32.37 | 18.81 | 13.56 | 58.61 | 38.51 | 0.00 | 0.00 | 0.00 |
December | 34.11 | 22.38 | 11.73 | 57.32 | 50.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.13 | 22.18 | 23.94 | 101.77 | 32.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.15 | 10.39 | 11.73 | 50.46 | 15.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.73 | 32.89 | 35.05 | 142.21 | 52.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.96 | 0.00 | 8.96 | 0.05 | 112.34 | 0.00 | 0.00 | 0.00 |
February | 13.94 | 0.00 | 13.94 | 1.86 | 97.48 | 0.00 | 0.00 | 0.00 |
March | 20.54 | 0.00 | 20.54 | 7.79 | 76.37 | 0.00 | 0.00 | 0.00 |
April | 29.11 | 0.12 | 28.99 | 21.58 | 59.73 | 0.00 | 0.00 | 0.00 |
May | 37.19 | 0.89 | 36.30 | 36.85 | 47.73 | 0.00 | 0.00 | 0.00 |
June | 38.95 | 2.20 | 36.75 | 43.94 | 35.64 | 0.00 | 0.00 | 0.00 |
July | 36.95 | 2.49 | 34.47 | 49.57 | 31.47 | 0.00 | 0.00 | 0.00 |
August | 30.15 | 0.68 | 29.47 | 41.72 | 30.59 | 0.00 | 0.00 | 0.00 |
September | 23.51 | 0.01 | 23.50 | 21.74 | 47.61 | 0.00 | 0.00 | 0.00 |
October | 16.10 | 0.00 | 16.10 | 6.82 | 65.85 | 0.00 | 0.00 | 0.00 |
November | 10.14 | 0.00 | 10.14 | 0.87 | 87.00 | 0.00 | 0.00 | 0.00 |
December | 7.61 | 0.00 | 7.61 | 0.01 | 109.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.81 | 0.54 | 22.27 | 19.52 | 66.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 7.61 | 0.00 | 7.61 | 0.01 | 30.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.95 | 2.49 | 36.75 | 49.57 | 112.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.02 | 0.00 | 8.02 | 0.04 | 100.51 | 0.00 | 0.00 | 0.00 |
February | 12.47 | 0.00 | 12.47 | 1.66 | 87.21 | 0.00 | 0.00 | 0.00 |
March | 18.38 | 0.00 | 18.38 | 6.97 | 68.33 | 0.00 | 0.00 | 0.00 |
April | 26.04 | 0.11 | 25.93 | 19.30 | 53.44 | 0.00 | 0.00 | 0.00 |
May | 33.27 | 0.80 | 32.47 | 32.97 | 42.70 | 0.00 | 0.00 | 0.00 |
June | 34.85 | 1.97 | 32.88 | 39.32 | 31.89 | 0.00 | 0.00 | 0.00 |
July | 33.06 | 2.23 | 30.84 | 44.35 | 28.16 | 0.00 | 0.00 | 0.00 |
August | 26.97 | 0.60 | 26.37 | 37.32 | 27.37 | 0.00 | 0.00 | 0.00 |
September | 21.03 | 0.01 | 21.02 | 19.45 | 42.60 | 0.00 | 0.00 | 0.00 |
October | 14.41 | 0.00 | 14.41 | 6.11 | 58.91 | 0.00 | 0.00 | 0.00 |
November | 9.07 | 0.00 | 9.07 | 0.78 | 77.84 | 0.00 | 0.00 | 0.00 |
December | 6.81 | 0.00 | 6.81 | 0.01 | 97.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.40 | 0.48 | 19.92 | 17.46 | 59.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.81 | 0.00 | 6.81 | 0.01 | 27.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.85 | 2.23 | 32.88 | 44.35 | 100.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.01 | 72.57 | 47.45 | 133.67 | 287.41 | 0.00 | 0.00 | 0.00 |
February | 183.39 | 114.99 | 68.40 | 242.15 | 249.38 | 0.00 | 0.00 | 0.00 |
March | 191.34 | 101.24 | 90.10 | 273.27 | 212.54 | 0.00 | 0.00 | 0.00 |
April | 197.57 | 82.25 | 115.32 | 304.70 | 176.54 | 0.00 | 0.00 | 0.00 |
May | 182.09 | 51.25 | 130.84 | 286.12 | 149.29 | 0.00 | 0.00 | 0.00 |
June | 163.51 | 38.79 | 124.72 | 263.64 | 116.00 | 0.00 | 0.00 | 0.00 |
July | 176.48 | 58.64 | 117.84 | 323.07 | 102.49 | 0.00 | 0.00 | 0.00 |
August | 190.15 | 83.54 | 106.61 | 359.87 | 96.55 | 0.00 | 0.00 | 0.00 |
September | 215.51 | 116.40 | 99.12 | 372.86 | 137.52 | 0.00 | 0.00 | 0.00 |
October | 199.54 | 122.80 | 76.74 | 306.62 | 180.91 | 0.00 | 0.00 | 0.00 |
November | 120.86 | 70.22 | 50.64 | 149.86 | 229.20 | 0.00 | 0.00 | 0.00 |
December | 127.33 | 83.54 | 43.79 | 161.83 | 284.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.20 | 82.82 | 89.38 | 264.90 | 184.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.01 | 38.79 | 43.79 | 133.67 | 96.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.51 | 122.80 | 130.84 | 372.86 | 287.41 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.435476E+09 | 0.263316E+09 | 0.172161E+09 | 0.500855E+09 | 0.955472E+09 |
February | 0.601048E+09 | 0.376858E+09 | 0.224191E+09 | 0.812122E+09 | 0.753622E+09 |
March | 0.694294E+09 | 0.367349E+09 | 0.326945E+09 | 0.101458E+10 | 0.697324E+09 |
April | 0.693765E+09 | 0.288834E+09 | 0.404931E+09 | 0.110839E+10 | 0.548732E+09 |
May | 0.660722E+09 | 0.185979E+09 | 0.474744E+09 | 0.109155E+10 | 0.462403E+09 |
June | 0.574154E+09 | 0.136212E+09 | 0.437942E+09 | 0.982956E+09 | 0.341901E+09 |
July | 0.640358E+09 | 0.212780E+09 | 0.427578E+09 | 0.121524E+10 | 0.321887E+09 |
August | 0.689989E+09 | 0.303144E+09 | 0.386844E+09 | 0.134123E+10 | 0.307244E+09 |
September | 0.756774E+09 | 0.408728E+09 | 0.348047E+09 | 0.133703E+10 | 0.424528E+09 |
October | 0.724043E+09 | 0.445601E+09 | 0.278442E+09 | 0.113833E+10 | 0.587746E+09 |
November | 0.424413E+09 | 0.246586E+09 | 0.177827E+09 | 0.542126E+09 | 0.729239E+09 |
December | 0.462039E+09 | 0.303130E+09 | 0.158909E+09 | 0.597892E+09 | 0.953666E+09 |
Annual Sum or Average | 0.735708E+10 | 0.353852E+10 | 0.381856E+10 | 0.116823E+11 | 0.708376E+10 |
Minimum of Months | 0.424413E+09 | 0.136212E+09 | 0.158909E+09 | 0.500855E+09 | 0.307244E+09 |
Maximum of Months | 0.756774E+09 | 0.445601E+09 | 0.474744E+09 | 0.134123E+10 | 0.955472E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122627E+10 | 0.741479E+09 | 0.484794E+09 | 0.139597E+10 | 0.270038E+10 |
February | 0.169251E+10 | 0.106121E+10 | 0.631306E+09 | 0.227845E+10 | 0.212434E+10 |
March | 0.195509E+10 | 0.103443E+10 | 0.920656E+09 | 0.285830E+10 | 0.196400E+10 |
April | 0.195360E+10 | 0.813338E+09 | 0.114026E+10 | 0.314388E+10 | 0.151938E+10 |
May | 0.186055E+10 | 0.523704E+09 | 0.133685E+10 | 0.312543E+10 | 0.124979E+10 |
June | 0.161678E+10 | 0.383563E+09 | 0.123322E+10 | 0.284998E+10 | 0.896099E+09 |
July | 0.180321E+10 | 0.599175E+09 | 0.120403E+10 | 0.354818E+10 | 0.798006E+09 |
August | 0.194296E+10 | 0.853634E+09 | 0.108933E+10 | 0.389254E+10 | 0.760725E+09 |
September | 0.213103E+10 | 0.115095E+10 | 0.980076E+09 | 0.382154E+10 | 0.111764E+10 |
October | 0.203886E+10 | 0.125478E+10 | 0.784074E+09 | 0.322337E+10 | 0.163724E+10 |
November | 0.119512E+10 | 0.694369E+09 | 0.500749E+09 | 0.151543E+10 | 0.206557E+10 |
December | 0.130107E+10 | 0.853593E+09 | 0.447478E+09 | 0.167481E+10 | 0.269471E+10 |
Annual Sum or Average | 0.207170E+11 | 0.996423E+10 | 0.107528E+11 | 0.333279E+11 | 0.195279E+11 |
Minimum of Months | 0.119512E+10 | 0.383563E+09 | 0.447478E+09 | 0.139597E+10 | 0.760725E+09 |
Maximum of Months | 0.213103E+10 | 0.125478E+10 | 0.133685E+10 | 0.389254E+10 | 0.270038E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159300E+10 | 0.963224E+09 | 0.629775E+09 | 0.181496E+10 | 0.374901E+10 |
February | 0.219867E+10 | 0.137857E+10 | 0.820102E+09 | 0.296877E+10 | 0.294984E+10 |
March | 0.253977E+10 | 0.134378E+10 | 0.119598E+10 | 0.372998E+10 | 0.275284E+10 |
April | 0.253783E+10 | 0.105657E+10 | 0.148126E+10 | 0.409459E+10 | 0.214638E+10 |
May | 0.241696E+10 | 0.680321E+09 | 0.173664E+10 | 0.405524E+10 | 0.179617E+10 |
June | 0.210029E+10 | 0.498270E+09 | 0.160202E+10 | 0.367753E+10 | 0.131117E+10 |
July | 0.234247E+10 | 0.778362E+09 | 0.156410E+10 | 0.459031E+10 | 0.118024E+10 |
August | 0.252402E+10 | 0.110892E+10 | 0.141510E+10 | 0.504802E+10 | 0.112578E+10 |
September | 0.276833E+10 | 0.149515E+10 | 0.127318E+10 | 0.497720E+10 | 0.160925E+10 |
October | 0.264859E+10 | 0.163004E+10 | 0.101856E+10 | 0.419676E+10 | 0.232241E+10 |
November | 0.155253E+10 | 0.902025E+09 | 0.650501E+09 | 0.196614E+10 | 0.290420E+10 |
December | 0.169017E+10 | 0.110887E+10 | 0.581300E+09 | 0.217729E+10 | 0.374779E+10 |
Annual Sum or Average | 0.269126E+11 | 0.129441E+11 | 0.139685E+11 | 0.432968E+11 | 0.275951E+11 |
Minimum of Months | 0.155253E+10 | 0.498270E+09 | 0.581300E+09 | 0.181496E+10 | 0.112578E+10 |
Maximum of Months | 0.276833E+10 | 0.163004E+10 | 0.173664E+10 | 0.504802E+10 | 0.374901E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86101326.40 | 52062013.65 | 34039312.75 | 99916936.35 | 0.191448E+09 |
February | 0.118838E+09 | 74511221.90 | 44326573.77 | 0.161332E+09 | 0.150936E+09 |
March | 0.137274E+09 | 72631220.93 | 64643081.44 | 0.201442E+09 | 0.139110E+09 |
April | 0.137170E+09 | 57107494.18 | 80062490.27 | 0.219227E+09 | 0.108444E+09 |
May | 0.130637E+09 | 36771165.79 | 93865828.25 | 0.215553E+09 | 89394476.07 |
June | 0.113521E+09 | 26931393.53 | 86589587.35 | 0.195830E+09 | 62539117.19 |
July | 0.126611E+09 | 42070292.86 | 84540407.94 | 0.244357E+09 | 54919836.55 |
August | 0.136423E+09 | 59936826.96 | 76486541.40 | 0.270322E+09 | 50538790.68 |
September | 0.149628E+09 | 80812509.80 | 68815343.62 | 0.267746E+09 | 77724222.12 |
October | 0.143156E+09 | 88103024.63 | 55053066.57 | 0.226526E+09 | 0.114095E+09 |
November | 83913825.62 | 48754218.97 | 35159606.65 | 0.108189E+09 | 0.145085E+09 |
December | 91353169.44 | 59933916.47 | 31419252.97 | 0.119283E+09 | 0.189932E+09 |
Annual Sum or Average | 0.145463E+10 | 0.699625E+09 | 0.755001E+09 | 0.232972E+10 | 0.137417E+10 |
Minimum of Months | 83913825.62 | 26931393.53 | 31419252.97 | 99916936.35 | 50538790.68 |
Maximum of Months | 0.149628E+09 | 88103024.63 | 93865828.25 | 0.270322E+09 | 0.191448E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59599176.07 | 17222110.70 | 42377065.37 | 30238074.54 | 0.390390E+09 |
February | 96609441.26 | 35905768.34 | 60703672.92 | 85914053.77 | 0.304836E+09 |
March | 0.150729E+09 | 50954464.27 | 99774512.72 | 0.168174E+09 | 0.265985E+09 |
April | 0.222465E+09 | 85441558.77 | 0.137024E+09 | 0.310418E+09 | 0.198271E+09 |
May | 0.297040E+09 | 0.121959E+09 | 0.175081E+09 | 0.462348E+09 | 0.161558E+09 |
June | 0.275247E+09 | 0.107280E+09 | 0.167967E+09 | 0.445273E+09 | 0.113031E+09 |
July | 0.353291E+09 | 0.187056E+09 | 0.166235E+09 | 0.628408E+09 | 99509300.08 |
August | 0.292567E+09 | 0.150519E+09 | 0.142048E+09 | 0.530266E+09 | 92905855.73 |
September | 0.230784E+09 | 0.111822E+09 | 0.118962E+09 | 0.378296E+09 | 0.145442E+09 |
October | 0.135461E+09 | 55687389.65 | 79773663.80 | 0.171323E+09 | 0.221173E+09 |
November | 64475472.80 | 18010891.45 | 46464581.35 | 45868219.89 | 0.289868E+09 |
December | 55889254.90 | 18921587.65 | 36967667.25 | 38453165.06 | 0.384843E+09 |
Annual Sum or Average | 0.223416E+10 | 0.960780E+09 | 0.127338E+10 | 0.329498E+10 | 0.266781E+10 |
Minimum of Months | 55889254.90 | 17222110.70 | 36967667.25 | 30238074.54 | 92905855.73 |
Maximum of Months | 0.353291E+09 | 0.187056E+09 | 0.175081E+09 | 0.628408E+09 | 0.390390E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18946356.37 | 0.00 | 18946356.37 | 338254.20 | 0.217574E+09 |
February | 26628054.19 | 0.00 | 26628054.19 | 5022314.96 | 0.169804E+09 |
March | 43439650.42 | 41.20 | 43439609.22 | 21891011.64 | 0.145300E+09 |
April | 59577731.69 | 250168.07 | 59327563.62 | 51958361.86 | 0.107100E+09 |
May | 78652506.95 | 1889932.19 | 76762574.76 | 87770852.31 | 85134411.20 |
June | 79717193.26 | 4509218.76 | 75207974.50 | 0.102655E+09 | 58848929.99 |
July | 78156447.04 | 5265044.47 | 72891402.57 | 0.115844E+09 | 53066804.17 |
August | 63757954.73 | 1428929.28 | 62329025.45 | 99665258.30 | 49346567.07 |
September | 48114157.88 | 18742.73 | 48095415.14 | 52483569.76 | 80439794.03 |
October | 34053415.06 | 0.00 | 34053415.06 | 20273448.95 | 0.120085E+09 |
November | 20758325.30 | 0.00 | 20758325.30 | 3130803.92 | 0.159568E+09 |
December | 16099518.30 | 0.00 | 16099518.30 | 125241.69 | 0.211471E+09 |
Annual Sum or Average | 0.567901E+09 | 13362076.70 | 0.554539E+09 | 0.561157E+09 | 0.145774E+10 |
Minimum of Months | 16099518.30 | 0.00 | 16099518.30 | 125241.69 | 49346567.07 |
Maximum of Months | 79717193.26 | 5265044.47 | 76762574.76 | 0.115844E+09 | 0.217574E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59599176.07 | 17222110.70 | 42377065.37 | 31787435.73 | 0.387577E+09 |
February | 96609441.26 | 35905768.34 | 60703672.92 | 89118335.41 | 0.301195E+09 |
March | 0.150729E+09 | 50954464.27 | 99774512.72 | 0.173036E+09 | 0.262825E+09 |
April | 0.222465E+09 | 85441558.77 | 0.137024E+09 | 0.314476E+09 | 0.196972E+09 |
May | 0.297040E+09 | 0.121959E+09 | 0.175081E+09 | 0.461882E+09 | 0.163003E+09 |
June | 0.275247E+09 | 0.107280E+09 | 0.167967E+09 | 0.442913E+09 | 0.115915E+09 |
July | 0.353291E+09 | 0.187056E+09 | 0.166235E+09 | 0.623445E+09 | 0.104643E+09 |
August | 0.292567E+09 | 0.150519E+09 | 0.142048E+09 | 0.529222E+09 | 96740967.76 |
September | 0.230784E+09 | 0.111822E+09 | 0.118962E+09 | 0.379274E+09 | 0.147348E+09 |
October | 0.135461E+09 | 55687389.65 | 79773663.80 | 0.176111E+09 | 0.218174E+09 |
November | 64475472.80 | 18010891.45 | 46464581.35 | 47824549.61 | 0.287165E+09 |
December | 55889254.90 | 18921587.65 | 36967667.25 | 40381029.61 | 0.381655E+09 |
Annual Sum or Average | 0.223416E+10 | 0.960780E+09 | 0.127338E+10 | 0.330947E+10 | 0.266321E+10 |
Minimum of Months | 55889254.90 | 17222110.70 | 36967667.25 | 31787435.73 | 96740967.76 |
Maximum of Months | 0.353291E+09 | 0.187056E+09 | 0.175081E+09 | 0.623445E+09 | 0.387577E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68867365.26 | 41641329.58 | 27226035.67 | 80117782.75 | 0.146244E+09 |
February | 95051333.39 | 59597125.26 | 35454208.13 | 0.122751E+09 | 0.136152E+09 |
March | 0.109798E+09 | 58093423.53 | 51704182.58 | 0.144843E+09 | 0.154168E+09 |
April | 0.109714E+09 | 45676911.44 | 64037256.93 | 0.154077E+09 | 0.127447E+09 |
May | 0.104489E+09 | 29411083.56 | 75077731.66 | 0.149964E+09 | 0.110203E+09 |
June | 90798727.29 | 21540830.93 | 69257896.35 | 0.132545E+09 | 84265271.06 |
July | 0.101268E+09 | 33649542.30 | 67618878.78 | 0.171991E+09 | 77863300.66 |
August | 0.109117E+09 | 47939927.61 | 61177066.65 | 0.192501E+09 | 74939978.58 |
September | 0.119678E+09 | 64637153.25 | 55041328.66 | 0.194372E+09 | 0.100917E+09 |
October | 0.114502E+09 | 70468405.44 | 44033696.14 | 0.162783E+09 | 0.139209E+09 |
November | 67117712.59 | 38995620.00 | 28122092.59 | 76654346.24 | 0.150692E+09 |
December | 73068004.29 | 47937599.68 | 25130404.62 | 91669599.67 | 0.160905E+09 |
Annual Sum or Average | 0.116347E+10 | 0.559589E+09 | 0.603881E+09 | 0.167427E+10 | 0.146301E+10 |
Minimum of Months | 67117712.59 | 21540830.93 | 25130404.62 | 76654346.24 | 74939978.58 |
Maximum of Months | 0.119678E+09 | 70468405.44 | 75077731.66 | 0.194372E+09 | 0.160905E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 15159094.26 | 0.00 | 15159094.26 | 125702.64 | 0.184083E+09 |
February | 21305267.12 | 0.00 | 21305267.12 | 3393187.89 | 0.142737E+09 |
March | 34756326.87 | 32.97 | 34756293.91 | 15930382.05 | 0.120896E+09 |
April | 47668503.24 | 200160.98 | 47468342.26 | 41352435.63 | 87367807.16 |
May | 62930346.23 | 1512146.17 | 61418200.06 | 72703199.13 | 67858673.93 |
June | 63782208.18 | 3607853.18 | 60174355.00 | 85114927.58 | 46438625.45 |
July | 62533445.69 | 4212593.90 | 58320851.79 | 98147112.99 | 40394560.57 |
August | 51013124.97 | 1143294.95 | 49869830.01 | 83882209.29 | 37700371.75 |
September | 38496428.55 | 14996.18 | 38481432.37 | 44097742.12 | 63056116.58 |
October | 27246343.23 | 0.00 | 27246343.23 | 15343368.01 | 99504941.43 |
November | 16608861.54 | 0.00 | 16608861.54 | 1956266.04 | 0.135563E+09 |
December | 12881321.90 | 0.00 | 12881321.90 | 39196.09 | 0.178881E+09 |
Annual Sum or Average | 0.454381E+09 | 10691078.34 | 0.443690E+09 | 0.462086E+09 | 0.120448E+10 |
Minimum of Months | 12881321.90 | 0.00 | 12881321.90 | 39196.09 | 37700371.75 |
Maximum of Months | 63782208.18 | 4212593.90 | 61418200.06 | 98147112.99 | 0.184083E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56013126.85 | 13589135.22 | 42423991.63 | 20399411.65 | 0.386981E+09 |
February | 93642058.49 | 32812606.93 | 60829451.56 | 73122704.26 | 0.297264E+09 |
March | 0.156400E+09 | 56782413.99 | 99617975.23 | 0.168618E+09 | 0.256126E+09 |
April | 0.235061E+09 | 98394540.84 | 0.136666E+09 | 0.323599E+09 | 0.189567E+09 |
May | 0.257627E+09 | 90094480.01 | 0.167533E+09 | 0.383488E+09 | 0.156064E+09 |
June | 0.299005E+09 | 0.130876E+09 | 0.168129E+09 | 0.486685E+09 | 0.107758E+09 |
July | 0.287922E+09 | 0.130015E+09 | 0.157907E+09 | 0.498337E+09 | 91108312.15 |
August | 0.284021E+09 | 0.143270E+09 | 0.140751E+09 | 0.507733E+09 | 86098467.71 |
September | 0.203238E+09 | 94655831.95 | 0.108582E+09 | 0.316672E+09 | 0.138507E+09 |
October | 0.136306E+09 | 58202454.63 | 78103826.20 | 0.167049E+09 | 0.214288E+09 |
November | 63978982.37 | 17682872.31 | 46296110.06 | 41540247.47 | 0.285680E+09 |
December | 53803267.41 | 16756669.15 | 37046598.26 | 28518396.04 | 0.377701E+09 |
Annual Sum or Average | 0.212702E+10 | 0.883132E+09 | 0.124389E+10 | 0.301576E+10 | 0.258714E+10 |
Minimum of Months | 53803267.41 | 13589135.22 | 37046598.26 | 20399411.65 | 86098467.71 |
Maximum of Months | 0.299005E+09 | 0.143270E+09 | 0.168129E+09 | 0.507733E+09 | 0.386981E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86101326.40 | 52062013.65 | 34039312.75 | 99884748.32 | 0.191270E+09 |
February | 0.118838E+09 | 74511221.90 | 44326573.77 | 0.161063E+09 | 0.150646E+09 |
March | 0.137274E+09 | 72631220.93 | 64643081.44 | 0.200379E+09 | 0.138870E+09 |
April | 0.137170E+09 | 57107494.18 | 80062490.27 | 0.217442E+09 | 0.108242E+09 |
May | 0.130637E+09 | 36771165.79 | 93865828.25 | 0.215104E+09 | 88512872.07 |
June | 0.113521E+09 | 26931393.53 | 86589587.35 | 0.194012E+09 | 62275301.24 |
July | 0.126611E+09 | 42070292.86 | 84540407.94 | 0.244120E+09 | 53827304.72 |
August | 0.136423E+09 | 59936826.96 | 76486541.40 | 0.269349E+09 | 50030771.80 |
September | 0.149628E+09 | 80812509.80 | 68815343.62 | 0.267373E+09 | 76651598.74 |
October | 0.143156E+09 | 88103024.63 | 55053066.57 | 0.225758E+09 | 0.113713E+09 |
November | 83913825.62 | 48754218.97 | 35159606.65 | 0.108012E+09 | 0.144925E+09 |
December | 91353169.44 | 59933916.47 | 31419252.97 | 0.119218E+09 | 0.189733E+09 |
Annual Sum or Average | 0.145463E+10 | 0.699625E+09 | 0.755001E+09 | 0.232171E+10 | 0.136870E+10 |
Minimum of Months | 83913825.62 | 26931393.53 | 31419252.97 | 99884748.32 | 50030771.80 |
Maximum of Months | 0.149628E+09 | 88103024.63 | 93865828.25 | 0.269349E+09 | 0.191270E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18946356.37 | 0.00 | 18946356.37 | 328392.33 | 0.217530E+09 |
February | 26628054.19 | 0.00 | 26628054.19 | 4983591.45 | 0.169706E+09 |
March | 43439650.42 | 41.20 | 43439609.22 | 21119287.71 | 0.145146E+09 |
April | 59577731.69 | 250168.07 | 59327563.62 | 50557861.48 | 0.107088E+09 |
May | 78652506.95 | 1889932.19 | 76762574.76 | 88339000.92 | 83880907.65 |
June | 79717193.26 | 4509218.76 | 75207974.50 | 0.101164E+09 | 58278345.50 |
July | 78156447.04 | 5265044.47 | 72891402.57 | 0.116700E+09 | 51068966.64 |
August | 63757954.73 | 1428929.28 | 62329025.45 | 98326824.25 | 48476577.51 |
September | 48114157.88 | 18742.73 | 48095415.14 | 52678354.61 | 78581042.45 |
October | 34053415.06 | 0.00 | 34053415.06 | 19694724.13 | 0.119526E+09 |
November | 20758325.30 | 0.00 | 20758325.30 | 3020221.60 | 0.159364E+09 |
December | 16099518.30 | 0.00 | 16099518.30 | 120231.34 | 0.211344E+09 |
Annual Sum or Average | 0.567901E+09 | 13362076.70 | 0.554539E+09 | 0.557033E+09 | 0.144999E+10 |
Minimum of Months | 16099518.30 | 0.00 | 16099518.30 | 120231.34 | 48476577.51 |
Maximum of Months | 79717193.26 | 5265044.47 | 76762574.76 | 0.116700E+09 | 0.217530E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56013126.85 | 13589135.22 | 42423991.63 | 20952638.84 | 0.383316E+09 |
February | 93642058.49 | 32812606.93 | 60829451.56 | 74950160.36 | 0.292118E+09 |
March | 0.156400E+09 | 56782413.99 | 99617975.23 | 0.173273E+09 | 0.252383E+09 |
April | 0.235061E+09 | 98394540.84 | 0.136666E+09 | 0.327844E+09 | 0.187925E+09 |
May | 0.257627E+09 | 90094480.01 | 0.167533E+09 | 0.385220E+09 | 0.156680E+09 |
June | 0.299005E+09 | 0.130876E+09 | 0.168129E+09 | 0.485773E+09 | 0.110513E+09 |
July | 0.287922E+09 | 0.130015E+09 | 0.157907E+09 | 0.496243E+09 | 94969719.80 |
August | 0.284021E+09 | 0.143270E+09 | 0.140751E+09 | 0.506369E+09 | 89394283.09 |
September | 0.203238E+09 | 94655831.95 | 0.108582E+09 | 0.319275E+09 | 0.139024E+09 |
October | 0.136306E+09 | 58202454.63 | 78103826.20 | 0.171936E+09 | 0.210610E+09 |
November | 63978982.37 | 17682872.31 | 46296110.06 | 42784001.73 | 0.282016E+09 |
December | 53803267.41 | 16756669.15 | 37046598.26 | 29265885.26 | 0.373262E+09 |
Annual Sum or Average | 0.212702E+10 | 0.883132E+09 | 0.124389E+10 | 0.303389E+10 | 0.257221E+10 |
Minimum of Months | 53803267.41 | 13589135.22 | 37046598.26 | 20952638.84 | 89394283.09 |
Maximum of Months | 0.299005E+09 | 0.143270E+09 | 0.168129E+09 | 0.506369E+09 | 0.383316E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 23994364.90 | 0.00 | 23994364.90 | 176340.60 | 0.296860E+09 |
February | 33722750.50 | 0.00 | 33722750.50 | 5485472.00 | 0.229987E+09 |
March | 55013576.37 | 52.18 | 55013524.19 | 25372601.13 | 0.192793E+09 |
April | 75451438.04 | 316822.08 | 75134615.96 | 66858355.68 | 0.139406E+09 |
May | 99608437.36 | 2393479.87 | 97214957.48 | 0.117218E+09 | 0.110355E+09 |
June | 0.100957E+09 | 5710641.04 | 95246154.35 | 0.136303E+09 | 76482646.19 |
July | 98980208.77 | 6667846.61 | 92312362.16 | 0.155031E+09 | 68620024.08 |
August | 80745426.76 | 1809648.77 | 78935777.99 | 0.130568E+09 | 66341329.35 |
September | 60933545.12 | 23736.49 | 60909808.62 | 69236896.71 | 0.105238E+09 |
October | 43126501.53 | 0.00 | 43126501.53 | 24397393.70 | 0.159780E+09 |
November | 26289109.21 | 0.00 | 26289109.21 | 3279068.77 | 0.216992E+09 |
December | 20389024.10 | 0.00 | 20389024.10 | 53935.81 | 0.288387E+09 |
Annual Sum or Average | 0.719211E+09 | 16922227.05 | 0.702289E+09 | 0.733980E+09 | 0.195124E+10 |
Minimum of Months | 20389024.10 | 0.00 | 20389024.10 | 53935.81 | 66341329.35 |
Maximum of Months | 0.100957E+09 | 6667846.61 | 97214957.48 | 0.155031E+09 | 0.296860E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 8845316.43 | 0.00 | 8845316.43 | 65006.45 | 0.109435E+09 |
February | 12431602.18 | 0.00 | 12431602.18 | 2022172.11 | 84782617.22 |
March | 20280282.18 | 19.24 | 20280262.95 | 9353391.37 | 71071418.40 |
April | 27814524.26 | 116793.74 | 27697730.52 | 24646758.29 | 51390856.85 |
May | 36719794.47 | 882335.79 | 35837458.68 | 43211302.65 | 40681476.30 |
June | 37216855.07 | 2105178.75 | 35111676.32 | 50246941.68 | 28194670.28 |
July | 36488203.40 | 2458044.35 | 34030159.05 | 57150890.54 | 25296182.21 |
August | 29766107.71 | 667111.47 | 29098996.24 | 48132950.43 | 24456160.98 |
September | 22462627.79 | 8750.25 | 22453877.54 | 25523587.00 | 38795082.03 |
October | 15898214.19 | 0.00 | 15898214.19 | 8993889.54 | 58901394.53 |
November | 9691254.20 | 0.00 | 9691254.20 | 1208800.52 | 79992263.59 |
December | 7516238.53 | 0.00 | 7516238.53 | 19882.97 | 0.106312E+09 |
Annual Sum or Average | 0.265131E+09 | 6238233.58 | 0.258893E+09 | 0.270576E+09 | 0.719308E+09 |
Minimum of Months | 7516238.53 | 0.00 | 7516238.53 | 19882.97 | 24456160.98 |
Maximum of Months | 37216855.07 | 2458044.35 | 35837458.68 | 57150890.54 | 0.109435E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 40174531.94 | 24291925.78 | 15882606.16 | 45402161.27 | 94754839.20 |
February | 55449236.58 | 34766635.88 | 20682600.70 | 74598196.23 | 73674569.87 |
March | 64051636.31 | 33889435.00 | 30162201.31 | 94119003.77 | 67115452.64 |
April | 64002961.99 | 26646126.66 | 37356835.33 | 0.103557E+09 | 51585217.87 |
May | 60954694.99 | 17157277.78 | 43797417.21 | 0.102655E+09 | 42990335.81 |
June | 52968432.23 | 12566079.70 | 40402352.53 | 93224898.02 | 30791896.98 |
July | 59076042.79 | 19629829.12 | 39446213.67 | 0.116018E+09 | 27672567.73 |
August | 63654593.93 | 27966281.93 | 35688312.00 | 0.127559E+09 | 26139406.83 |
September | 69815753.45 | 37706791.42 | 32108962.03 | 0.126280E+09 | 38074515.44 |
October | 66796055.28 | 41108516.27 | 25687539.01 | 0.106333E+09 | 55108022.41 |
November | 39153852.89 | 22748522.11 | 16405330.78 | 49836141.49 | 71484874.62 |
December | 42625020.73 | 27964923.91 | 14660096.83 | 54881608.96 | 93902546.19 |
Annual Sum or Average | 0.678723E+09 | 0.326442E+09 | 0.352280E+09 | 0.109446E+10 | 0.673294E+09 |
Minimum of Months | 39153852.89 | 12566079.70 | 14660096.83 | 45402161.27 | 26139406.83 |
Maximum of Months | 69815753.45 | 41108516.27 | 43797417.21 | 0.127559E+09 | 94754839.20 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109042E+09 | 65933255.36 | 43108641.83 | 0.123231E+09 | 0.257184E+09 |
February | 0.150501E+09 | 94363761.14 | 56136808.83 | 0.202475E+09 | 0.199968E+09 |
March | 0.173849E+09 | 91982858.53 | 81866383.89 | 0.255458E+09 | 0.182165E+09 |
April | 0.173717E+09 | 72323038.10 | 0.101394E+09 | 0.281074E+09 | 0.140013E+09 |
May | 0.165444E+09 | 46568361.34 | 0.118875E+09 | 0.278625E+09 | 0.116685E+09 |
June | 0.143767E+09 | 34106910.63 | 0.109660E+09 | 0.253031E+09 | 83575506.74 |
July | 0.160344E+09 | 53279371.42 | 0.107065E+09 | 0.314897E+09 | 75109009.10 |
August | 0.172772E+09 | 75906209.54 | 96865378.65 | 0.346222E+09 | 70947690.48 |
September | 0.189494E+09 | 0.102344E+09 | 87150290.69 | 0.342750E+09 | 0.103342E+09 |
October | 0.181298E+09 | 0.111577E+09 | 69721235.15 | 0.288609E+09 | 0.149574E+09 |
November | 0.106272E+09 | 61744142.11 | 44527423.37 | 0.135265E+09 | 0.194025E+09 |
December | 0.115693E+09 | 75902523.58 | 39790501.44 | 0.148960E+09 | 0.254871E+09 |
Annual Sum or Average | 0.184219E+10 | 0.886031E+09 | 0.956161E+09 | 0.297060E+10 | 0.182746E+10 |
Minimum of Months | 0.106272E+09 | 34106910.63 | 39790501.44 | 0.123231E+09 | 70947690.48 |
Maximum of Months | 0.189494E+09 | 0.111577E+09 | 0.118875E+09 | 0.346222E+09 | 0.257184E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86101326.40 | 52062013.65 | 34039312.75 | 0.100227E+09 | 0.189018E+09 |
February | 0.118838E+09 | 74511221.90 | 44326573.77 | 0.161212E+09 | 0.149132E+09 |
March | 0.137274E+09 | 72631220.93 | 64643081.44 | 0.200604E+09 | 0.137538E+09 |
April | 0.137170E+09 | 57107494.18 | 80062490.27 | 0.217290E+09 | 0.107777E+09 |
May | 0.130637E+09 | 36771165.79 | 93865828.25 | 0.212833E+09 | 88982859.06 |
June | 0.113521E+09 | 26931393.53 | 86589587.35 | 0.193033E+09 | 62188583.00 |
July | 0.126611E+09 | 42070292.86 | 84540407.94 | 0.241448E+09 | 54539157.35 |
August | 0.136423E+09 | 59936826.96 | 76486541.40 | 0.267987E+09 | 49816548.53 |
September | 0.149628E+09 | 80812509.80 | 68815343.62 | 0.266116E+09 | 76854578.18 |
October | 0.143156E+09 | 88103024.63 | 55053066.57 | 0.225574E+09 | 0.112444E+09 |
November | 83913825.62 | 48754218.97 | 35159606.65 | 0.108306E+09 | 0.142850E+09 |
December | 91353169.44 | 59933916.47 | 31419252.97 | 0.119499E+09 | 0.187235E+09 |
Annual Sum or Average | 0.145463E+10 | 0.699625E+09 | 0.755001E+09 | 0.231413E+10 | 0.135837E+10 |
Minimum of Months | 83913825.62 | 26931393.53 | 31419252.97 | 0.100227E+09 | 49816548.53 |
Maximum of Months | 0.149628E+09 | 88103024.63 | 93865828.25 | 0.267987E+09 | 0.189018E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59599176.07 | 17222110.70 | 42377065.37 | 30817065.05 | 0.384738E+09 |
February | 96609441.26 | 35905768.34 | 60703672.92 | 86077232.81 | 0.300560E+09 |
March | 0.150729E+09 | 50954464.27 | 99774512.72 | 0.167338E+09 | 0.262534E+09 |
April | 0.222465E+09 | 85441558.77 | 0.137024E+09 | 0.306985E+09 | 0.196734E+09 |
May | 0.297040E+09 | 0.121959E+09 | 0.175081E+09 | 0.456646E+09 | 0.160529E+09 |
June | 0.275247E+09 | 0.107280E+09 | 0.167967E+09 | 0.439410E+09 | 0.112166E+09 |
July | 0.353291E+09 | 0.187056E+09 | 0.166235E+09 | 0.621896E+09 | 98584422.19 |
August | 0.292567E+09 | 0.150519E+09 | 0.142048E+09 | 0.525611E+09 | 91388660.20 |
September | 0.230784E+09 | 0.111822E+09 | 0.118962E+09 | 0.375238E+09 | 0.143499E+09 |
October | 0.135461E+09 | 55687389.65 | 79773663.80 | 0.170427E+09 | 0.217524E+09 |
November | 64475472.80 | 18010891.45 | 46464581.35 | 46302821.25 | 0.284825E+09 |
December | 55889254.90 | 18921587.65 | 36967667.25 | 38898692.56 | 0.378525E+09 |
Annual Sum or Average | 0.223416E+10 | 0.960780E+09 | 0.127338E+10 | 0.326565E+10 | 0.263161E+10 |
Minimum of Months | 55889254.90 | 17222110.70 | 36967667.25 | 30817065.05 | 91388660.20 |
Maximum of Months | 0.353291E+09 | 0.187056E+09 | 0.175081E+09 | 0.621896E+09 | 0.384738E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18946356.37 | 0.00 | 18946356.37 | 399443.98 | 0.214336E+09 |
February | 26628054.19 | 0.00 | 26628054.19 | 5202613.55 | 0.167201E+09 |
March | 43439650.42 | 41.20 | 43439609.22 | 22134949.28 | 0.143323E+09 |
April | 59577731.69 | 250168.07 | 59327563.62 | 51191936.39 | 0.106332E+09 |
May | 78652506.95 | 1889932.19 | 76762574.76 | 85342698.03 | 85208007.90 |
June | 79717193.26 | 4509218.76 | 75207974.50 | 99742667.78 | 59219028.27 |
July | 78156447.04 | 5265044.47 | 72891402.57 | 0.112721E+09 | 53784644.83 |
August | 63757954.73 | 1428929.28 | 62329025.45 | 98081252.80 | 49158953.79 |
September | 48114157.88 | 18742.73 | 48095415.14 | 51368366.92 | 80215497.69 |
October | 34053415.06 | 0.00 | 34053415.06 | 20601049.38 | 0.117934E+09 |
November | 20758325.30 | 0.00 | 20758325.30 | 3283193.02 | 0.156544E+09 |
December | 16099518.30 | 0.00 | 16099518.30 | 155763.28 | 0.207684E+09 |
Annual Sum or Average | 0.567901E+09 | 13362076.70 | 0.554539E+09 | 0.550225E+09 | 0.144094E+10 |
Minimum of Months | 16099518.30 | 0.00 | 16099518.30 | 155763.28 | 49158953.79 |
Maximum of Months | 79717193.26 | 5265044.47 | 76762574.76 | 0.112721E+09 | 0.214336E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59599176.07 | 17222110.70 | 42377065.37 | 32246228.97 | 0.382355E+09 |
February | 96609441.26 | 35905768.34 | 60703672.92 | 89555764.54 | 0.296998E+09 |
March | 0.150729E+09 | 50954464.27 | 99774512.72 | 0.172652E+09 | 0.259245E+09 |
April | 0.222465E+09 | 85441558.77 | 0.137024E+09 | 0.311128E+09 | 0.195604E+09 |
May | 0.297040E+09 | 0.121959E+09 | 0.175081E+09 | 0.454936E+09 | 0.163103E+09 |
June | 0.275247E+09 | 0.107280E+09 | 0.167967E+09 | 0.435345E+09 | 0.116507E+09 |
July | 0.353291E+09 | 0.187056E+09 | 0.166235E+09 | 0.614691E+09 | 0.105892E+09 |
August | 0.292567E+09 | 0.150519E+09 | 0.142048E+09 | 0.523761E+09 | 96302298.86 |
September | 0.230784E+09 | 0.111822E+09 | 0.118962E+09 | 0.375382E+09 | 0.146647E+09 |
October | 0.135461E+09 | 55687389.65 | 79773663.80 | 0.175702E+09 | 0.214335E+09 |
November | 64475472.80 | 18010891.45 | 46464581.35 | 48437740.71 | 0.282165E+09 |
December | 55889254.90 | 18921587.65 | 36967667.25 | 40982940.18 | 0.375474E+09 |
Annual Sum or Average | 0.223416E+10 | 0.960780E+09 | 0.127338E+10 | 0.327482E+10 | 0.263463E+10 |
Minimum of Months | 55889254.90 | 17222110.70 | 36967667.25 | 32246228.97 | 96302298.86 |
Maximum of Months | 0.353291E+09 | 0.187056E+09 | 0.175081E+09 | 0.614691E+09 | 0.382355E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126276E+09 | 76353939.43 | 49921918.91 | 0.141341E+09 | 0.287092E+09 |
February | 0.174287E+09 | 0.109278E+09 | 65009174.48 | 0.229246E+09 | 0.227073E+09 |
March | 0.201326E+09 | 0.106521E+09 | 94805282.74 | 0.287278E+09 | 0.209017E+09 |
April | 0.201173E+09 | 83753620.84 | 0.117419E+09 | 0.313848E+09 | 0.161193E+09 |
May | 0.191592E+09 | 53928443.57 | 0.137663E+09 | 0.311172E+09 | 0.130524E+09 |
June | 0.166489E+09 | 39497473.23 | 0.126992E+09 | 0.283418E+09 | 90398863.34 |
July | 0.185687E+09 | 61700121.98 | 0.123987E+09 | 0.356431E+09 | 77729357.20 |
August | 0.200078E+09 | 87903108.89 | 0.112175E+09 | 0.393971E+09 | 71642793.38 |
September | 0.219444E+09 | 0.118519E+09 | 0.100924E+09 | 0.388379E+09 | 0.113148E+09 |
October | 0.209952E+09 | 0.129212E+09 | 80740605.58 | 0.324478E+09 | 0.171217E+09 |
November | 0.123068E+09 | 71502741.08 | 51564937.42 | 0.153641E+09 | 0.218277E+09 |
December | 0.133978E+09 | 87898840.37 | 46079349.80 | 0.169669E+09 | 0.284851E+09 |
Annual Sum or Average | 0.213335E+10 | 0.102607E+10 | 0.110728E+10 | 0.335287E+10 | 0.204216E+10 |
Minimum of Months | 0.123068E+09 | 39497473.23 | 46079349.80 | 0.141341E+09 | 71642793.38 |
Maximum of Months | 0.219444E+09 | 0.129212E+09 | 0.137663E+09 | 0.393971E+09 | 0.287092E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132619E+09 | 0.00 | 0.132619E+09 | 983348.22 | 0.161302E+10 |
February | 0.186389E+09 | 0.00 | 0.186389E+09 | 29942473.69 | 0.125352E+10 |
March | 0.304066E+09 | 288.41 | 0.304066E+09 | 0.139616E+09 | 0.106787E+10 |
April | 0.417028E+09 | 1751110.17 | 0.415277E+09 | 0.365410E+09 | 0.782248E+09 |
May | 0.550547E+09 | 13229024.31 | 0.537318E+09 | 0.643703E+09 | 0.618174E+09 |
June | 0.557999E+09 | 31563335.86 | 0.526436E+09 | 0.755297E+09 | 0.429580E+09 |
July | 0.547074E+09 | 36853915.44 | 0.510220E+09 | 0.876320E+09 | 0.376199E+09 |
August | 0.446289E+09 | 10002126.14 | 0.436287E+09 | 0.752572E+09 | 0.355867E+09 |
September | 0.336786E+09 | 131194.17 | 0.336655E+09 | 0.396477E+09 | 0.566504E+09 |
October | 0.238365E+09 | 0.00 | 0.238365E+09 | 0.136787E+09 | 0.885676E+09 |
November | 0.145303E+09 | 0.00 | 0.145303E+09 | 17730046.69 | 0.119009E+10 |
December | 0.112692E+09 | 0.00 | 0.112692E+09 | 311678.64 | 0.156431E+10 |
Annual Sum or Average | 0.397516E+10 | 93530994.50 | 0.388163E+10 | 0.411515E+10 | 0.107031E+11 |
Minimum of Months | 0.112692E+09 | 0.00 | 0.112692E+09 | 311678.64 | 0.355867E+09 |
Maximum of Months | 0.557999E+09 | 36853915.44 | 0.537318E+09 | 0.876320E+09 | 0.161302E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132619E+09 | 0.00 | 0.132619E+09 | 591737.63 | 0.167842E+10 |
February | 0.186389E+09 | 0.00 | 0.186389E+09 | 26081716.90 | 0.131035E+10 |
March | 0.304066E+09 | 288.41 | 0.304066E+09 | 0.125804E+09 | 0.112140E+10 |
April | 0.417028E+09 | 1751110.17 | 0.415277E+09 | 0.344601E+09 | 0.821152E+09 |
May | 0.550547E+09 | 13229024.31 | 0.537318E+09 | 0.619422E+09 | 0.646080E+09 |
June | 0.557999E+09 | 31563335.86 | 0.526436E+09 | 0.729839E+09 | 0.449666E+09 |
July | 0.547074E+09 | 36853915.44 | 0.510220E+09 | 0.851808E+09 | 0.394904E+09 |
August | 0.446289E+09 | 10002126.14 | 0.436287E+09 | 0.729508E+09 | 0.375989E+09 |
September | 0.336786E+09 | 131194.17 | 0.336655E+09 | 0.379316E+09 | 0.595722E+09 |
October | 0.238365E+09 | 0.00 | 0.238365E+09 | 0.123902E+09 | 0.935270E+09 |
November | 0.145303E+09 | 0.00 | 0.145303E+09 | 14557625.00 | 0.125231E+10 |
December | 0.112692E+09 | 0.00 | 0.112692E+09 | 133211.87 | 0.163075E+10 |
Annual Sum or Average | 0.397516E+10 | 93530994.50 | 0.388163E+10 | 0.394557E+10 | 0.112120E+11 |
Minimum of Months | 0.112692E+09 | 0.00 | 0.112692E+09 | 133211.87 | 0.375989E+09 |
Maximum of Months | 0.557999E+09 | 36853915.44 | 0.537318E+09 | 0.851808E+09 | 0.167842E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 18946356.37 | 0.00 | 18946356.37 | 13395266.12 | 0.146952E+09 |
February | 26628054.19 | 0.00 | 26628054.19 | 32746624.86 | 0.119390E+09 |
March | 43439650.42 | 41.20 | 43439609.22 | 75661226.05 | 0.107047E+09 |
April | 59577731.69 | 250168.07 | 59327563.62 | 0.126636E+09 | 84448319.18 |
May | 78652506.95 | 1889932.19 | 76762574.76 | 0.184362E+09 | 69897620.75 |
June | 79717193.26 | 4509218.76 | 75207974.50 | 0.207226E+09 | 50979951.35 |
July | 78156447.04 | 5265044.47 | 72891402.57 | 0.231461E+09 | 43948951.62 |
August | 63757954.73 | 1428929.28 | 62329025.45 | 0.212507E+09 | 40958794.16 |
September | 48114157.88 | 18742.73 | 48095415.14 | 0.139674E+09 | 53874066.92 |
October | 34053415.06 | 0.00 | 34053415.06 | 78346407.48 | 82264909.52 |
November | 20758325.30 | 0.00 | 20758325.30 | 31775971.16 | 0.102046E+09 |
December | 16099518.30 | 0.00 | 16099518.30 | 13690267.78 | 0.139863E+09 |
Annual Sum or Average | 0.567901E+09 | 13362076.70 | 0.554539E+09 | 0.134748E+10 | 0.104167E+10 |
Minimum of Months | 16099518.30 | 0.00 | 16099518.30 | 13395266.12 | 40958794.16 |
Maximum of Months | 79717193.26 | 5265044.47 | 76762574.76 | 0.231461E+09 | 0.146952E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112018E+09 | 27176340.43 | 84841957.98 | 0.120639E+09 | 0.534950E+09 |
February | 0.187271E+09 | 65620553.63 | 0.121650E+09 | 0.288849E+09 | 0.430938E+09 |
March | 0.312779E+09 | 0.113557E+09 | 0.199222E+09 | 0.580622E+09 | 0.391139E+09 |
April | 0.470088E+09 | 0.196775E+09 | 0.273313E+09 | 0.963498E+09 | 0.311288E+09 |
May | 0.515218E+09 | 0.180176E+09 | 0.335042E+09 | 0.113019E+10 | 0.260057E+09 |
June | 0.597968E+09 | 0.261733E+09 | 0.336235E+09 | 0.136544E+10 | 0.189651E+09 |
July | 0.575803E+09 | 0.260012E+09 | 0.315791E+09 | 0.142206E+10 | 0.162912E+09 |
August | 0.568001E+09 | 0.286519E+09 | 0.281482E+09 | 0.144428E+10 | 0.153341E+09 |
September | 0.406447E+09 | 0.189298E+09 | 0.217149E+09 | 0.980016E+09 | 0.200732E+09 |
October | 0.272593E+09 | 0.116397E+09 | 0.156197E+09 | 0.589141E+09 | 0.306250E+09 |
November | 0.127949E+09 | 35363233.21 | 92585644.90 | 0.217187E+09 | 0.376746E+09 |
December | 0.107599E+09 | 33510958.43 | 74087934.97 | 0.142533E+09 | 0.514895E+09 |
Annual Sum or Average | 0.425373E+10 | 0.176614E+10 | 0.248760E+10 | 0.924446E+10 | 0.383290E+10 |
Minimum of Months | 0.107599E+09 | 27176340.43 | 74087934.97 | 0.120639E+09 | 0.153341E+09 |
Maximum of Months | 0.597968E+09 | 0.286519E+09 | 0.336235E+09 | 0.144428E+10 | 0.534950E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86101326.40 | 52062013.65 | 34039312.75 | 0.135149E+09 | 0.140140E+09 |
February | 0.118838E+09 | 74511221.90 | 44326573.77 | 0.208697E+09 | 0.114554E+09 |
March | 0.137274E+09 | 72631220.93 | 64643081.44 | 0.266340E+09 | 0.105836E+09 |
April | 0.137170E+09 | 57107494.18 | 80062490.27 | 0.297820E+09 | 85988841.37 |
May | 0.130637E+09 | 36771165.79 | 93865828.25 | 0.309275E+09 | 71742389.60 |
June | 0.113521E+09 | 26931393.53 | 86589587.35 | 0.296068E+09 | 53048928.05 |
July | 0.126611E+09 | 42070292.86 | 84540407.94 | 0.354599E+09 | 45374541.65 |
August | 0.136423E+09 | 59936826.96 | 76486541.40 | 0.380888E+09 | 41592581.78 |
September | 0.149628E+09 | 80812509.80 | 68815343.62 | 0.358972E+09 | 53813376.56 |
October | 0.143156E+09 | 88103024.63 | 55053066.57 | 0.296204E+09 | 81959447.02 |
November | 83913825.62 | 48754218.97 | 35159606.65 | 0.151926E+09 | 99811112.65 |
December | 91353169.44 | 59933916.47 | 31419252.97 | 0.153538E+09 | 0.135409E+09 |
Annual Sum or Average | 0.145463E+10 | 0.699625E+09 | 0.755001E+09 | 0.320948E+10 | 0.102927E+10 |
Minimum of Months | 83913825.62 | 26931393.53 | 31419252.97 | 0.135149E+09 | 41592581.78 |
Maximum of Months | 0.149628E+09 | 88103024.63 | 93865828.25 | 0.380888E+09 | 0.140140E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 23994364.90 | 0.00 | 23994364.90 | 125744.86 | 0.300902E+09 |
February | 33722750.50 | 0.00 | 33722750.50 | 4497228.31 | 0.235820E+09 |
March | 55013576.37 | 52.18 | 55013524.19 | 20865977.53 | 0.204558E+09 |
April | 75451438.04 | 316822.08 | 75134615.96 | 55924959.41 | 0.154832E+09 |
May | 99608437.36 | 2393479.87 | 97214957.48 | 98689448.30 | 0.127834E+09 |
June | 0.100957E+09 | 5710641.04 | 95246154.35 | 0.113899E+09 | 92387831.07 |
July | 98980208.77 | 6667846.61 | 92312362.16 | 0.132774E+09 | 84302189.25 |
August | 80745426.76 | 1809648.77 | 78935777.99 | 0.111733E+09 | 81939288.39 |
September | 60933545.12 | 23736.49 | 60909808.62 | 56355940.34 | 0.123417E+09 |
October | 43126501.53 | 0.00 | 43126501.53 | 18276694.35 | 0.176367E+09 |
November | 26289109.21 | 0.00 | 26289109.21 | 2254239.98 | 0.225516E+09 |
December | 20389024.10 | 0.00 | 20389024.10 | 34929.32 | 0.292197E+09 |
Annual Sum or Average | 0.719211E+09 | 16922227.05 | 0.702289E+09 | 0.615431E+09 | 0.210007E+10 |
Minimum of Months | 20389024.10 | 0.00 | 20389024.10 | 34929.32 | 81939288.39 |
Maximum of Months | 0.100957E+09 | 6667846.61 | 97214957.48 | 0.132774E+09 | 0.300902E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21467849.19 | 0.00 | 21467849.19 | 112504.40 | 0.269210E+09 |
February | 30171872.65 | 0.00 | 30171872.65 | 4023687.21 | 0.210989E+09 |
March | 49220855.22 | 46.69 | 49220808.53 | 18668869.16 | 0.183019E+09 |
April | 67506687.50 | 283461.91 | 67223225.59 | 50036273.08 | 0.138529E+09 |
May | 89120046.32 | 2141455.51 | 86978590.81 | 88297823.32 | 0.114373E+09 |
June | 90326427.36 | 5109332.18 | 85217095.18 | 0.101906E+09 | 82659742.52 |
July | 88557967.82 | 5965747.63 | 82592220.20 | 0.118793E+09 | 75425488.14 |
August | 72243239.27 | 1619099.61 | 70624139.65 | 99967929.38 | 73311391.79 |
September | 54517473.69 | 21237.13 | 54496236.56 | 50421873.35 | 0.110421E+09 |
October | 38585444.32 | 0.00 | 38585444.32 | 16352227.69 | 0.157796E+09 |
November | 23520965.62 | 0.00 | 23520965.62 | 2016877.05 | 0.201767E+09 |
December | 18242137.12 | 0.00 | 18242137.12 | 31251.39 | 0.261413E+09 |
Annual Sum or Average | 0.643481E+09 | 15140380.66 | 0.628341E+09 | 0.550628E+09 | 0.187891E+10 |
Minimum of Months | 18242137.12 | 0.00 | 18242137.12 | 31251.39 | 73311391.79 |
Maximum of Months | 90326427.36 | 5965747.63 | 86978590.81 | 0.118793E+09 | 0.269210E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321442E+09 | 0.194363E+09 | 0.127079E+09 | 0.358014E+09 | 0.769787E+09 |
February | 0.443657E+09 | 0.278173E+09 | 0.165484E+09 | 0.585816E+09 | 0.603303E+09 |
March | 0.512486E+09 | 0.271154E+09 | 0.241332E+09 | 0.731926E+09 | 0.569277E+09 |
April | 0.512096E+09 | 0.213199E+09 | 0.298897E+09 | 0.789782E+09 | 0.457593E+09 |
May | 0.487707E+09 | 0.137278E+09 | 0.350429E+09 | 0.766334E+09 | 0.399857E+09 |
June | 0.423808E+09 | 0.100543E+09 | 0.323265E+09 | 0.683343E+09 | 0.300660E+09 |
July | 0.472675E+09 | 0.157061E+09 | 0.315615E+09 | 0.865323E+09 | 0.274517E+09 |
August | 0.509309E+09 | 0.223762E+09 | 0.285547E+09 | 0.963870E+09 | 0.258612E+09 |
September | 0.558605E+09 | 0.301697E+09 | 0.256908E+09 | 0.966454E+09 | 0.356446E+09 |
October | 0.534444E+09 | 0.328915E+09 | 0.205530E+09 | 0.821242E+09 | 0.484554E+09 |
November | 0.313275E+09 | 0.182014E+09 | 0.131261E+09 | 0.388432E+09 | 0.594083E+09 |
December | 0.341049E+09 | 0.223751E+09 | 0.117297E+09 | 0.433440E+09 | 0.761764E+09 |
Annual Sum or Average | 0.543055E+10 | 0.261191E+10 | 0.281864E+10 | 0.835398E+10 | 0.583045E+10 |
Minimum of Months | 0.313275E+09 | 0.100543E+09 | 0.117297E+09 | 0.358014E+09 | 0.258612E+09 |
Maximum of Months | 0.558605E+09 | 0.328915E+09 | 0.350429E+09 | 0.966454E+09 | 0.769787E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 187.00 | 356.73 | 162.59 | 98.31 | 64.28 | 0.00 | 0.00 |
February | 335.70 | 311.52 | 248.45 | 155.78 | 92.67 | 0.00 | 0.00 |
March | 378.80 | 260.35 | 259.22 | 137.15 | 122.07 | 0.00 | 0.00 |
April | 427.62 | 211.70 | 267.66 | 111.43 | 156.22 | 0.00 | 0.00 |
May | 407.54 | 172.64 | 246.69 | 69.44 | 177.25 | 0.00 | 0.00 |
June | 379.23 | 131.91 | 221.51 | 52.55 | 168.96 | 0.00 | 0.00 |
July | 453.72 | 120.18 | 239.08 | 79.44 | 159.64 | 0.00 | 0.00 |
August | 500.76 | 114.71 | 257.61 | 113.18 | 144.43 | 0.00 | 0.00 |
September | 515.83 | 163.78 | 291.97 | 157.69 | 134.28 | 0.00 | 0.00 |
October | 425.00 | 219.44 | 270.33 | 166.37 | 103.96 | 0.00 | 0.00 |
November | 209.15 | 281.34 | 163.74 | 95.13 | 68.61 | 0.00 | 0.00 |
December | 223.23 | 356.06 | 172.51 | 113.18 | 59.33 | 0.00 | 0.00 |
Annual Sum or Average | 370.44 | 224.62 | 233.29 | 112.21 | 121.09 | 0.00 | 0.00 |
Minimum of Months | 187.00 | 114.71 | 162.59 | 52.55 | 59.33 | 0.00 | 0.00 |
Maximum of Months | 515.83 | 356.73 | 291.97 | 166.37 | 177.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 521.20 | 1008.21 | 457.84 | 276.84 | 181.00 | 0.00 | 0.00 |
February | 941.82 | 878.12 | 699.62 | 438.66 | 260.96 | 0.00 | 0.00 |
March | 1067.17 | 733.27 | 729.95 | 386.21 | 343.73 | 0.00 | 0.00 |
April | 1212.92 | 586.18 | 753.70 | 313.79 | 439.91 | 0.00 | 0.00 |
May | 1166.90 | 466.62 | 694.65 | 195.53 | 499.12 | 0.00 | 0.00 |
June | 1099.53 | 345.72 | 623.76 | 147.98 | 475.78 | 0.00 | 0.00 |
July | 1324.74 | 297.94 | 673.24 | 223.71 | 449.53 | 0.00 | 0.00 |
August | 1453.31 | 284.02 | 725.42 | 318.71 | 406.71 | 0.00 | 0.00 |
September | 1474.36 | 431.19 | 822.16 | 444.04 | 378.12 | 0.00 | 0.00 |
October | 1203.47 | 611.28 | 761.22 | 468.48 | 292.74 | 0.00 | 0.00 |
November | 584.66 | 796.90 | 461.08 | 267.89 | 193.19 | 0.00 | 0.00 |
December | 625.30 | 1006.09 | 485.76 | 318.70 | 167.07 | 0.00 | 0.00 |
Annual Sum or Average | 1056.82 | 619.23 | 656.93 | 315.96 | 340.97 | 0.00 | 0.00 |
Minimum of Months | 521.20 | 284.02 | 457.84 | 147.98 | 167.07 | 0.00 | 0.00 |
Maximum of Months | 1474.36 | 1008.21 | 822.16 | 468.48 | 499.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 677.63 | 1399.72 | 594.76 | 359.63 | 235.13 | 0.00 | 0.00 |
February | 1227.17 | 1219.34 | 908.84 | 569.84 | 339.00 | 0.00 | 0.00 |
March | 1392.62 | 1027.79 | 948.24 | 501.71 | 446.53 | 0.00 | 0.00 |
April | 1579.70 | 828.08 | 979.10 | 407.63 | 571.47 | 0.00 | 0.00 |
May | 1514.05 | 670.61 | 902.39 | 254.00 | 648.39 | 0.00 | 0.00 |
June | 1418.80 | 505.85 | 810.30 | 192.23 | 618.06 | 0.00 | 0.00 |
July | 1713.83 | 440.65 | 874.58 | 290.61 | 583.97 | 0.00 | 0.00 |
August | 1884.72 | 420.32 | 942.36 | 414.02 | 528.34 | 0.00 | 0.00 |
September | 1920.22 | 620.85 | 1068.03 | 576.83 | 491.19 | 0.00 | 0.00 |
October | 1566.89 | 867.09 | 988.87 | 608.59 | 380.29 | 0.00 | 0.00 |
November | 758.54 | 1120.45 | 598.97 | 348.00 | 250.97 | 0.00 | 0.00 |
December | 812.91 | 1399.26 | 631.04 | 414.00 | 217.03 | 0.00 | 0.00 |
Annual Sum or Average | 1372.93 | 875.03 | 853.39 | 410.45 | 442.94 | 0.00 | 0.00 |
Minimum of Months | 677.63 | 420.32 | 594.76 | 192.23 | 217.03 | 0.00 | 0.00 |
Maximum of Months | 1920.22 | 1399.72 | 1068.03 | 608.59 | 648.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.17 | 210.81 | 54.40 | 25.87 | 28.53 | 0.00 | 0.00 |
February | 96.00 | 182.20 | 89.06 | 45.64 | 43.42 | 0.00 | 0.00 |
March | 135.86 | 149.10 | 107.53 | 46.14 | 61.39 | 0.00 | 0.00 |
April | 203.12 | 117.11 | 138.75 | 55.00 | 83.75 | 0.00 | 0.00 |
May | 252.35 | 92.95 | 159.68 | 59.26 | 100.41 | 0.00 | 0.00 |
June | 246.84 | 67.24 | 149.99 | 51.78 | 98.21 | 0.00 | 0.00 |
July | 325.41 | 57.22 | 179.17 | 85.55 | 93.63 | 0.00 | 0.00 |
August | 298.66 | 53.31 | 160.17 | 78.58 | 81.59 | 0.00 | 0.00 |
September | 248.50 | 85.35 | 146.76 | 74.32 | 72.44 | 0.00 | 0.00 |
October | 146.61 | 123.24 | 104.02 | 53.69 | 50.34 | 0.00 | 0.00 |
November | 55.70 | 164.07 | 57.25 | 25.76 | 31.49 | 0.00 | 0.00 |
December | 53.01 | 208.71 | 54.97 | 29.44 | 25.53 | 0.00 | 0.00 |
Annual Sum or Average | 175.86 | 125.67 | 116.97 | 52.65 | 64.32 | 0.00 | 0.00 |
Minimum of Months | 42.17 | 53.31 | 54.40 | 25.76 | 25.53 | 0.00 | 0.00 |
Maximum of Months | 325.41 | 210.81 | 179.17 | 85.55 | 100.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.77 | 223.72 | 29.33 | 6.43 | 22.90 | 0.00 | 0.00 |
February | 36.34 | 192.12 | 50.94 | 14.84 | 36.10 | 0.00 | 0.00 |
March | 71.51 | 151.10 | 72.49 | 19.02 | 53.47 | 0.00 | 0.00 |
April | 140.65 | 116.59 | 108.81 | 33.06 | 75.75 | 0.00 | 0.00 |
May | 204.69 | 92.12 | 140.27 | 46.24 | 94.03 | 0.00 | 0.00 |
June | 209.29 | 66.23 | 136.95 | 43.13 | 93.82 | 0.00 | 0.00 |
July | 275.05 | 57.91 | 161.08 | 71.80 | 89.28 | 0.00 | 0.00 |
August | 234.38 | 54.12 | 133.04 | 56.73 | 76.31 | 0.00 | 0.00 |
September | 166.00 | 87.31 | 107.60 | 43.15 | 64.45 | 0.00 | 0.00 |
October | 72.31 | 125.28 | 63.29 | 20.79 | 42.50 | 0.00 | 0.00 |
November | 18.15 | 170.84 | 32.88 | 6.95 | 25.93 | 0.00 | 0.00 |
December | 12.92 | 219.25 | 26.88 | 7.06 | 19.81 | 0.00 | 0.00 |
Annual Sum or Average | 121.48 | 129.42 | 88.85 | 30.89 | 57.96 | 0.00 | 0.00 |
Minimum of Months | 9.77 | 54.12 | 26.88 | 6.43 | 19.81 | 0.00 | 0.00 |
Maximum of Months | 275.05 | 223.72 | 161.08 | 71.80 | 94.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 29.91 | 54.60 | 25.71 | 15.55 | 10.17 | 0.00 | 0.00 |
February | 50.74 | 56.28 | 39.29 | 24.64 | 14.66 | 0.00 | 0.00 |
March | 54.08 | 57.56 | 40.99 | 21.69 | 19.30 | 0.00 | 0.00 |
April | 59.44 | 49.17 | 42.33 | 17.62 | 24.71 | 0.00 | 0.00 |
May | 55.99 | 41.15 | 39.01 | 10.98 | 28.03 | 0.00 | 0.00 |
June | 51.14 | 32.51 | 35.03 | 8.31 | 26.72 | 0.00 | 0.00 |
July | 64.21 | 29.07 | 37.81 | 12.56 | 25.25 | 0.00 | 0.00 |
August | 71.87 | 27.98 | 40.74 | 17.90 | 22.84 | 0.00 | 0.00 |
September | 74.99 | 38.93 | 46.17 | 24.94 | 21.24 | 0.00 | 0.00 |
October | 60.78 | 51.97 | 42.75 | 26.31 | 16.44 | 0.00 | 0.00 |
November | 29.57 | 58.14 | 25.89 | 15.04 | 10.85 | 0.00 | 0.00 |
December | 34.23 | 60.08 | 27.28 | 17.90 | 9.38 | 0.00 | 0.00 |
Annual Sum or Average | 53.09 | 46.39 | 36.89 | 17.74 | 19.15 | 0.00 | 0.00 |
Minimum of Months | 29.57 | 27.98 | 25.71 | 8.31 | 9.38 | 0.00 | 0.00 |
Maximum of Months | 74.99 | 60.08 | 46.17 | 26.31 | 28.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.05 | 68.73 | 5.66 | 0.00 | 5.66 | 0.00 | 0.00 |
February | 1.40 | 59.00 | 8.81 | 0.00 | 8.81 | 0.00 | 0.00 |
March | 5.95 | 45.14 | 12.98 | 0.00 | 12.98 | 0.00 | 0.00 |
April | 15.95 | 33.71 | 18.39 | 0.08 | 18.31 | 0.00 | 0.00 |
May | 27.14 | 25.34 | 23.50 | 0.56 | 22.93 | 0.00 | 0.00 |
June | 32.84 | 17.92 | 24.61 | 1.39 | 23.22 | 0.00 | 0.00 |
July | 36.64 | 15.08 | 23.35 | 1.57 | 21.77 | 0.00 | 0.00 |
August | 31.32 | 14.08 | 19.05 | 0.43 | 18.62 | 0.00 | 0.00 |
September | 17.01 | 24.33 | 14.85 | 0.01 | 14.85 | 0.00 | 0.00 |
October | 5.73 | 37.15 | 10.17 | 0.00 | 10.17 | 0.00 | 0.00 |
November | 0.75 | 52.30 | 6.41 | 0.00 | 6.41 | 0.00 | 0.00 |
December | 0.01 | 66.79 | 4.81 | 0.00 | 4.81 | 0.00 | 0.00 |
Annual Sum or Average | 14.65 | 38.19 | 14.41 | 0.34 | 14.07 | 0.00 | 0.00 |
Minimum of Months | 0.01 | 14.08 | 4.81 | 0.00 | 4.81 | 0.00 | 0.00 |
Maximum of Months | 36.64 | 68.73 | 24.61 | 1.57 | 23.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 38.96 | 209.95 | 53.06 | 24.51 | 28.55 | 0.00 | 0.00 |
February | 92.10 | 180.44 | 87.83 | 44.36 | 43.47 | 0.00 | 0.00 |
March | 136.12 | 145.83 | 109.65 | 48.32 | 61.33 | 0.00 | 0.00 |
April | 206.65 | 112.81 | 143.61 | 59.99 | 83.61 | 0.00 | 0.00 |
May | 222.15 | 89.97 | 144.96 | 47.37 | 97.60 | 0.00 | 0.00 |
June | 261.36 | 64.34 | 159.15 | 60.88 | 98.27 | 0.00 | 0.00 |
July | 276.05 | 52.96 | 154.77 | 64.25 | 90.52 | 0.00 | 0.00 |
August | 288.84 | 49.54 | 156.98 | 75.87 | 81.11 | 0.00 | 0.00 |
September | 224.22 | 81.90 | 136.14 | 67.70 | 68.44 | 0.00 | 0.00 |
October | 145.44 | 121.24 | 104.34 | 54.62 | 49.72 | 0.00 | 0.00 |
November | 54.64 | 163.07 | 57.06 | 25.63 | 31.43 | 0.00 | 0.00 |
December | 49.82 | 206.52 | 54.20 | 28.63 | 25.56 | 0.00 | 0.00 |
Annual Sum or Average | 166.75 | 122.94 | 113.57 | 50.19 | 63.38 | 0.00 | 0.00 |
Minimum of Months | 38.96 | 49.54 | 53.06 | 24.51 | 25.56 | 0.00 | 0.00 |
Maximum of Months | 288.84 | 209.95 | 159.15 | 75.87 | 98.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.38 | 221.76 | 27.99 | 5.07 | 22.91 | 0.00 | 0.00 |
February | 29.18 | 187.04 | 49.71 | 13.56 | 36.15 | 0.00 | 0.00 |
March | 69.72 | 145.57 | 74.61 | 21.20 | 53.41 | 0.00 | 0.00 |
April | 143.76 | 111.59 | 113.67 | 38.06 | 75.61 | 0.00 | 0.00 |
May | 176.05 | 89.06 | 125.55 | 34.34 | 91.21 | 0.00 | 0.00 |
June | 225.88 | 64.55 | 146.11 | 52.23 | 93.88 | 0.00 | 0.00 |
July | 228.04 | 53.71 | 136.68 | 50.51 | 86.17 | 0.00 | 0.00 |
August | 225.29 | 51.00 | 129.85 | 54.02 | 75.82 | 0.00 | 0.00 |
September | 141.96 | 82.41 | 96.97 | 36.53 | 60.45 | 0.00 | 0.00 |
October | 69.40 | 121.12 | 63.61 | 21.73 | 41.87 | 0.00 | 0.00 |
November | 15.56 | 168.17 | 32.69 | 6.82 | 25.87 | 0.00 | 0.00 |
December | 8.30 | 215.59 | 26.10 | 6.26 | 19.84 | 0.00 | 0.00 |
Annual Sum or Average | 112.00 | 125.67 | 85.46 | 28.43 | 57.03 | 0.00 | 0.00 |
Minimum of Months | 5.38 | 51.00 | 26.10 | 5.07 | 19.84 | 0.00 | 0.00 |
Maximum of Months | 228.04 | 221.76 | 146.11 | 54.02 | 93.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 51.06 | 271.11 | 67.97 | 33.69 | 34.29 | 0.00 | 0.00 |
February | 106.91 | 232.50 | 104.21 | 53.38 | 50.83 | 0.00 | 0.00 |
March | 141.14 | 189.25 | 116.93 | 47.00 | 69.94 | 0.00 | 0.00 |
April | 183.22 | 147.06 | 131.55 | 38.35 | 93.20 | 0.00 | 0.00 |
May | 201.29 | 115.05 | 135.43 | 25.02 | 110.41 | 0.00 | 0.00 |
June | 203.80 | 82.75 | 129.21 | 21.02 | 108.19 | 0.00 | 0.00 |
July | 238.39 | 71.72 | 132.50 | 30.63 | 101.87 | 0.00 | 0.00 |
August | 243.02 | 69.56 | 129.53 | 39.71 | 89.83 | 0.00 | 0.00 |
September | 217.10 | 109.71 | 132.22 | 54.04 | 78.17 | 0.00 | 0.00 |
October | 157.21 | 155.36 | 114.67 | 57.01 | 57.66 | 0.00 | 0.00 |
November | 66.21 | 210.08 | 69.99 | 32.60 | 37.39 | 0.00 | 0.00 |
December | 64.93 | 266.38 | 69.53 | 38.78 | 30.75 | 0.00 | 0.00 |
Annual Sum or Average | 156.47 | 159.69 | 111.15 | 39.18 | 71.97 | 0.00 | 0.00 |
Minimum of Months | 51.06 | 69.56 | 67.97 | 21.02 | 30.75 | 0.00 | 0.00 |
Maximum of Months | 243.02 | 271.11 | 135.43 | 57.01 | 110.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.66 | 207.95 | 54.40 | 25.87 | 28.53 | 0.00 | 0.00 |
February | 96.20 | 179.86 | 89.06 | 45.64 | 43.42 | 0.00 | 0.00 |
March | 135.28 | 147.27 | 107.53 | 46.14 | 61.39 | 0.00 | 0.00 |
April | 201.05 | 116.26 | 138.75 | 55.00 | 83.75 | 0.00 | 0.00 |
May | 249.18 | 92.38 | 159.68 | 59.26 | 100.41 | 0.00 | 0.00 |
June | 243.47 | 66.74 | 149.99 | 51.78 | 98.21 | 0.00 | 0.00 |
July | 321.87 | 56.70 | 179.17 | 85.55 | 93.63 | 0.00 | 0.00 |
August | 296.03 | 52.46 | 160.17 | 78.58 | 81.59 | 0.00 | 0.00 |
September | 246.69 | 84.27 | 146.76 | 74.32 | 72.44 | 0.00 | 0.00 |
October | 146.00 | 121.34 | 104.02 | 53.69 | 50.34 | 0.00 | 0.00 |
November | 56.03 | 161.38 | 57.25 | 25.76 | 31.49 | 0.00 | 0.00 |
December | 53.43 | 205.52 | 54.97 | 29.44 | 25.53 | 0.00 | 0.00 |
Annual Sum or Average | 174.49 | 124.08 | 116.97 | 52.65 | 64.32 | 0.00 | 0.00 |
Minimum of Months | 42.66 | 52.46 | 54.40 | 25.76 | 25.53 | 0.00 | 0.00 |
Maximum of Months | 321.87 | 207.95 | 179.17 | 85.55 | 100.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.02 | 220.61 | 29.33 | 6.43 | 22.90 | 0.00 | 0.00 |
February | 36.73 | 189.44 | 50.94 | 14.84 | 36.10 | 0.00 | 0.00 |
March | 71.45 | 149.03 | 72.49 | 19.02 | 53.47 | 0.00 | 0.00 |
April | 139.04 | 115.75 | 108.81 | 33.06 | 75.75 | 0.00 | 0.00 |
May | 201.17 | 92.16 | 140.27 | 46.24 | 94.03 | 0.00 | 0.00 |
June | 205.25 | 66.60 | 136.95 | 43.13 | 93.82 | 0.00 | 0.00 |
July | 270.63 | 58.66 | 161.08 | 71.80 | 89.28 | 0.00 | 0.00 |
August | 231.73 | 53.87 | 133.04 | 56.73 | 76.31 | 0.00 | 0.00 |
September | 164.00 | 86.89 | 107.60 | 43.15 | 64.45 | 0.00 | 0.00 |
October | 72.29 | 123.06 | 63.29 | 20.79 | 42.50 | 0.00 | 0.00 |
November | 18.50 | 167.80 | 32.88 | 6.95 | 25.93 | 0.00 | 0.00 |
December | 13.28 | 215.65 | 26.88 | 7.06 | 19.81 | 0.00 | 0.00 |
Annual Sum or Average | 120.06 | 128.00 | 88.85 | 30.89 | 57.96 | 0.00 | 0.00 |
Minimum of Months | 10.02 | 53.87 | 26.88 | 6.43 | 19.81 | 0.00 | 0.00 |
Maximum of Months | 270.63 | 220.61 | 161.08 | 71.80 | 94.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 52.77 | 107.19 | 47.15 | 28.51 | 18.64 | 0.00 | 0.00 |
February | 94.76 | 93.86 | 72.04 | 45.17 | 26.87 | 0.00 | 0.00 |
March | 107.26 | 78.04 | 75.17 | 39.77 | 35.40 | 0.00 | 0.00 |
April | 121.08 | 62.19 | 77.61 | 32.31 | 45.30 | 0.00 | 0.00 |
May | 116.18 | 48.73 | 71.53 | 20.13 | 51.40 | 0.00 | 0.00 |
June | 109.34 | 34.88 | 64.23 | 15.24 | 48.99 | 0.00 | 0.00 |
July | 133.08 | 29.02 | 69.33 | 23.04 | 46.29 | 0.00 | 0.00 |
August | 147.09 | 26.75 | 74.70 | 32.82 | 41.88 | 0.00 | 0.00 |
September | 149.84 | 43.65 | 84.66 | 45.73 | 38.94 | 0.00 | 0.00 |
October | 121.15 | 63.93 | 78.39 | 48.24 | 30.15 | 0.00 | 0.00 |
November | 59.28 | 84.21 | 47.48 | 27.59 | 19.89 | 0.00 | 0.00 |
December | 63.35 | 106.35 | 50.02 | 32.82 | 17.20 | 0.00 | 0.00 |
Annual Sum or Average | 106.32 | 64.76 | 67.65 | 32.54 | 35.11 | 0.00 | 0.00 |
Minimum of Months | 52.77 | 26.75 | 47.15 | 15.24 | 17.20 | 0.00 | 0.00 |
Maximum of Months | 149.84 | 107.19 | 84.66 | 48.24 | 51.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.37 | 602.23 | 49.51 | 0.00 | 49.51 | 0.00 | 0.00 |
February | 12.38 | 518.15 | 77.05 | 0.00 | 77.05 | 0.00 | 0.00 |
March | 52.13 | 398.70 | 113.53 | 0.00 | 113.53 | 0.00 | 0.00 |
April | 140.98 | 301.79 | 160.89 | 0.68 | 160.21 | 0.00 | 0.00 |
May | 240.33 | 230.80 | 205.55 | 4.94 | 200.61 | 0.00 | 0.00 |
June | 291.40 | 165.73 | 215.28 | 12.18 | 203.10 | 0.00 | 0.00 |
July | 327.18 | 140.46 | 204.25 | 13.76 | 190.49 | 0.00 | 0.00 |
August | 280.98 | 132.87 | 166.63 | 3.73 | 162.89 | 0.00 | 0.00 |
September | 152.96 | 218.56 | 129.93 | 0.05 | 129.88 | 0.00 | 0.00 |
October | 51.07 | 330.67 | 89.00 | 0.00 | 89.00 | 0.00 | 0.00 |
November | 6.84 | 459.14 | 56.06 | 0.00 | 56.06 | 0.00 | 0.00 |
December | 0.12 | 584.05 | 42.07 | 0.00 | 42.07 | 0.00 | 0.00 |
Annual Sum or Average | 130.49 | 339.39 | 126.05 | 2.97 | 123.09 | 0.00 | 0.00 |
Minimum of Months | 0.12 | 132.87 | 42.07 | 0.00 | 42.07 | 0.00 | 0.00 |
Maximum of Months | 327.18 | 602.23 | 215.28 | 13.76 | 203.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.22 | 626.65 | 49.51 | 0.00 | 49.51 | 0.00 | 0.00 |
February | 10.78 | 541.65 | 77.05 | 0.00 | 77.05 | 0.00 | 0.00 |
March | 46.97 | 418.68 | 113.53 | 0.00 | 113.53 | 0.00 | 0.00 |
April | 132.95 | 316.80 | 160.89 | 0.68 | 160.21 | 0.00 | 0.00 |
May | 231.27 | 241.22 | 205.55 | 4.94 | 200.61 | 0.00 | 0.00 |
June | 281.57 | 173.48 | 215.28 | 12.18 | 203.10 | 0.00 | 0.00 |
July | 318.03 | 147.44 | 204.25 | 13.76 | 190.49 | 0.00 | 0.00 |
August | 272.37 | 140.38 | 166.63 | 3.73 | 162.89 | 0.00 | 0.00 |
September | 146.34 | 229.83 | 129.93 | 0.05 | 129.88 | 0.00 | 0.00 |
October | 46.26 | 349.19 | 89.00 | 0.00 | 89.00 | 0.00 | 0.00 |
November | 5.62 | 483.15 | 56.06 | 0.00 | 56.06 | 0.00 | 0.00 |
December | 0.05 | 608.85 | 42.07 | 0.00 | 42.07 | 0.00 | 0.00 |
Annual Sum or Average | 125.11 | 355.53 | 126.05 | 2.97 | 123.09 | 0.00 | 0.00 |
Minimum of Months | 0.05 | 140.38 | 42.07 | 0.00 | 42.07 | 0.00 | 0.00 |
Maximum of Months | 318.03 | 626.65 | 215.28 | 13.76 | 203.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 96.14 | 302.55 | 81.04 | 29.58 | 51.46 | 0.00 | 0.00 |
February | 216.94 | 272.57 | 137.54 | 57.92 | 79.62 | 0.00 | 0.00 |
March | 343.20 | 224.25 | 184.25 | 69.51 | 114.73 | 0.00 | 0.00 |
April | 534.17 | 184.55 | 257.27 | 98.05 | 159.22 | 0.00 | 0.00 |
May | 605.59 | 149.30 | 270.50 | 81.70 | 188.80 | 0.00 | 0.00 |
June | 720.37 | 112.71 | 305.25 | 113.11 | 192.14 | 0.00 | 0.00 |
July | 749.33 | 93.75 | 291.43 | 114.75 | 176.68 | 0.00 | 0.00 |
August | 760.53 | 87.82 | 286.81 | 129.89 | 156.92 | 0.00 | 0.00 |
September | 570.17 | 118.69 | 233.10 | 104.22 | 128.88 | 0.00 | 0.00 |
October | 359.44 | 175.30 | 167.94 | 76.35 | 91.59 | 0.00 | 0.00 |
November | 153.22 | 221.78 | 89.75 | 32.45 | 57.29 | 0.00 | 0.00 |
December | 112.85 | 292.21 | 80.29 | 34.89 | 45.40 | 0.00 | 0.00 |
Annual Sum or Average | 436.31 | 185.87 | 199.02 | 78.61 | 120.41 | 0.00 | 0.00 |
Minimum of Months | 96.14 | 87.82 | 80.29 | 29.58 | 45.40 | 0.00 | 0.00 |
Maximum of Months | 760.53 | 302.55 | 305.25 | 129.89 | 192.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 115.96 | 482.46 | 136.99 | 72.57 | 64.42 | 0.00 | 0.00 |
February | 229.34 | 417.74 | 209.80 | 114.99 | 94.82 | 0.00 | 0.00 |
March | 284.00 | 353.22 | 230.26 | 101.24 | 129.02 | 0.00 | 0.00 |
April | 344.62 | 288.76 | 252.72 | 82.48 | 170.24 | 0.00 | 0.00 |
May | 354.37 | 238.16 | 252.55 | 52.95 | 199.61 | 0.00 | 0.00 |
June | 342.80 | 179.44 | 237.30 | 42.96 | 194.34 | 0.00 | 0.00 |
July | 412.81 | 157.94 | 246.50 | 63.36 | 183.14 | 0.00 | 0.00 |
August | 437.94 | 153.55 | 247.27 | 84.82 | 162.45 | 0.00 | 0.00 |
September | 413.13 | 226.81 | 260.05 | 116.41 | 143.64 | 0.00 | 0.00 |
October | 314.59 | 300.72 | 230.05 | 122.80 | 107.24 | 0.00 | 0.00 |
November | 140.66 | 383.20 | 140.08 | 70.22 | 69.86 | 0.00 | 0.00 |
December | 144.94 | 474.19 | 141.76 | 83.54 | 58.22 | 0.00 | 0.00 |
Annual Sum or Average | 294.96 | 304.14 | 215.41 | 83.84 | 131.57 | 0.00 | 0.00 |
Minimum of Months | 115.96 | 153.55 | 136.99 | 42.96 | 58.22 | 0.00 | 0.00 |
Maximum of Months | 437.94 | 482.46 | 260.05 | 122.80 | 199.61 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.500855E+09 | 0.955472E+09 | 0.435476E+09 | 0.263316E+09 | 0.172161E+09 | 0.00 | 0.00 |
February | 0.812122E+09 | 0.753622E+09 | 0.601048E+09 | 0.376858E+09 | 0.224191E+09 | 0.00 | 0.00 |
March | 0.101458E+10 | 0.697324E+09 | 0.694294E+09 | 0.367349E+09 | 0.326945E+09 | 0.00 | 0.00 |
April | 0.110839E+10 | 0.548732E+09 | 0.693765E+09 | 0.288834E+09 | 0.404931E+09 | 0.00 | 0.00 |
May | 0.109155E+10 | 0.462403E+09 | 0.660722E+09 | 0.185979E+09 | 0.474744E+09 | 0.00 | 0.00 |
June | 0.982956E+09 | 0.341901E+09 | 0.574154E+09 | 0.136212E+09 | 0.437942E+09 | 0.00 | 0.00 |
July | 0.121524E+10 | 0.321887E+09 | 0.640358E+09 | 0.212780E+09 | 0.427578E+09 | 0.00 | 0.00 |
August | 0.134123E+10 | 0.307244E+09 | 0.689989E+09 | 0.303144E+09 | 0.386844E+09 | 0.00 | 0.00 |
September | 0.133703E+10 | 0.424528E+09 | 0.756774E+09 | 0.408728E+09 | 0.348047E+09 | 0.00 | 0.00 |
October | 0.113833E+10 | 0.587746E+09 | 0.724043E+09 | 0.445601E+09 | 0.278442E+09 | 0.00 | 0.00 |
November | 0.542126E+09 | 0.729239E+09 | 0.424413E+09 | 0.246586E+09 | 0.177827E+09 | 0.00 | 0.00 |
December | 0.597892E+09 | 0.953666E+09 | 0.462039E+09 | 0.303130E+09 | 0.158909E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116823E+11 | 0.708376E+10 | 0.735708E+10 | 0.353852E+10 | 0.381856E+10 | 0.00 | 0.00 |
Minimum of Months | 0.500855E+09 | 0.307244E+09 | 0.424413E+09 | 0.136212E+09 | 0.158909E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134123E+10 | 0.955472E+09 | 0.756774E+09 | 0.445601E+09 | 0.474744E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.139597E+10 | 0.270038E+10 | 0.122627E+10 | 0.741479E+09 | 0.484794E+09 | 0.00 | 0.00 |
February | 0.227845E+10 | 0.212434E+10 | 0.169251E+10 | 0.106121E+10 | 0.631306E+09 | 0.00 | 0.00 |
March | 0.285830E+10 | 0.196400E+10 | 0.195509E+10 | 0.103443E+10 | 0.920656E+09 | 0.00 | 0.00 |
April | 0.314388E+10 | 0.151938E+10 | 0.195360E+10 | 0.813338E+09 | 0.114026E+10 | 0.00 | 0.00 |
May | 0.312543E+10 | 0.124979E+10 | 0.186055E+10 | 0.523704E+09 | 0.133685E+10 | 0.00 | 0.00 |
June | 0.284998E+10 | 0.896099E+09 | 0.161678E+10 | 0.383563E+09 | 0.123322E+10 | 0.00 | 0.00 |
July | 0.354818E+10 | 0.798006E+09 | 0.180321E+10 | 0.599175E+09 | 0.120403E+10 | 0.00 | 0.00 |
August | 0.389254E+10 | 0.760725E+09 | 0.194296E+10 | 0.853634E+09 | 0.108933E+10 | 0.00 | 0.00 |
September | 0.382154E+10 | 0.111764E+10 | 0.213103E+10 | 0.115095E+10 | 0.980076E+09 | 0.00 | 0.00 |
October | 0.322337E+10 | 0.163724E+10 | 0.203886E+10 | 0.125478E+10 | 0.784074E+09 | 0.00 | 0.00 |
November | 0.151543E+10 | 0.206557E+10 | 0.119512E+10 | 0.694369E+09 | 0.500749E+09 | 0.00 | 0.00 |
December | 0.167481E+10 | 0.269471E+10 | 0.130107E+10 | 0.853593E+09 | 0.447478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333279E+11 | 0.195279E+11 | 0.207170E+11 | 0.996423E+10 | 0.107528E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139597E+10 | 0.760725E+09 | 0.119512E+10 | 0.383563E+09 | 0.447478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.389254E+10 | 0.270038E+10 | 0.213103E+10 | 0.125478E+10 | 0.133685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181496E+10 | 0.374901E+10 | 0.159300E+10 | 0.963224E+09 | 0.629775E+09 | 0.00 | 0.00 |
February | 0.296877E+10 | 0.294984E+10 | 0.219867E+10 | 0.137857E+10 | 0.820102E+09 | 0.00 | 0.00 |
March | 0.372998E+10 | 0.275284E+10 | 0.253977E+10 | 0.134378E+10 | 0.119598E+10 | 0.00 | 0.00 |
April | 0.409459E+10 | 0.214638E+10 | 0.253783E+10 | 0.105657E+10 | 0.148126E+10 | 0.00 | 0.00 |
May | 0.405524E+10 | 0.179617E+10 | 0.241696E+10 | 0.680321E+09 | 0.173664E+10 | 0.00 | 0.00 |
June | 0.367753E+10 | 0.131117E+10 | 0.210029E+10 | 0.498270E+09 | 0.160202E+10 | 0.00 | 0.00 |
July | 0.459031E+10 | 0.118024E+10 | 0.234247E+10 | 0.778362E+09 | 0.156410E+10 | 0.00 | 0.00 |
August | 0.504802E+10 | 0.112578E+10 | 0.252402E+10 | 0.110892E+10 | 0.141510E+10 | 0.00 | 0.00 |
September | 0.497720E+10 | 0.160925E+10 | 0.276833E+10 | 0.149515E+10 | 0.127318E+10 | 0.00 | 0.00 |
October | 0.419676E+10 | 0.232241E+10 | 0.264859E+10 | 0.163004E+10 | 0.101856E+10 | 0.00 | 0.00 |
November | 0.196614E+10 | 0.290420E+10 | 0.155253E+10 | 0.902025E+09 | 0.650501E+09 | 0.00 | 0.00 |
December | 0.217729E+10 | 0.374779E+10 | 0.169017E+10 | 0.110887E+10 | 0.581300E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.432968E+11 | 0.275951E+11 | 0.269126E+11 | 0.129441E+11 | 0.139685E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181496E+10 | 0.112578E+10 | 0.155253E+10 | 0.498270E+09 | 0.581300E+09 | 0.00 | 0.00 |
Maximum of Months | 0.504802E+10 | 0.374901E+10 | 0.276833E+10 | 0.163004E+10 | 0.173664E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112943E+09 | 0.564627E+09 | 0.145701E+09 | 69284124.35 | 76416378.12 | 0.00 | 0.00 |
February | 0.232253E+09 | 0.440779E+09 | 0.215447E+09 | 0.110417E+09 | 0.105030E+09 | 0.00 | 0.00 |
March | 0.363881E+09 | 0.399359E+09 | 0.288003E+09 | 0.123586E+09 | 0.164418E+09 | 0.00 | 0.00 |
April | 0.526489E+09 | 0.303559E+09 | 0.359635E+09 | 0.142549E+09 | 0.217086E+09 | 0.00 | 0.00 |
May | 0.675899E+09 | 0.248950E+09 | 0.427677E+09 | 0.158730E+09 | 0.268947E+09 | 0.00 | 0.00 |
June | 0.639810E+09 | 0.174277E+09 | 0.388768E+09 | 0.134212E+09 | 0.254556E+09 | 0.00 | 0.00 |
July | 0.871581E+09 | 0.153245E+09 | 0.479902E+09 | 0.229126E+09 | 0.250775E+09 | 0.00 | 0.00 |
August | 0.799922E+09 | 0.142779E+09 | 0.428991E+09 | 0.210456E+09 | 0.218535E+09 | 0.00 | 0.00 |
September | 0.644114E+09 | 0.221238E+09 | 0.380412E+09 | 0.192634E+09 | 0.187777E+09 | 0.00 | 0.00 |
October | 0.392676E+09 | 0.330095E+09 | 0.278617E+09 | 0.143790E+09 | 0.134827E+09 | 0.00 | 0.00 |
November | 0.144381E+09 | 0.425277E+09 | 0.148389E+09 | 66765110.42 | 81624188.00 | 0.00 | 0.00 |
December | 0.141983E+09 | 0.559022E+09 | 0.147242E+09 | 78855504.12 | 68386920.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.554593E+10 | 0.396321E+10 | 0.368878E+10 | 0.166041E+10 | 0.202838E+10 | 0.00 | 0.00 |
Minimum of Months | 0.112943E+09 | 0.142779E+09 | 0.145701E+09 | 66765110.42 | 68386920.22 | 0.00 | 0.00 |
Maximum of Months | 0.871581E+09 | 0.564627E+09 | 0.479902E+09 | 0.229126E+09 | 0.268947E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26175050.21 | 0.599200E+09 | 78545532.45 | 17222110.70 | 61323421.75 | 0.00 | 0.00 |
February | 87912451.06 | 0.464771E+09 | 0.123237E+09 | 35905768.34 | 87331727.11 | 0.00 | 0.00 |
March | 0.191521E+09 | 0.404718E+09 | 0.194169E+09 | 50954505.48 | 0.143214E+09 | 0.00 | 0.00 |
April | 0.364570E+09 | 0.302206E+09 | 0.282043E+09 | 85691726.84 | 0.196351E+09 | 0.00 | 0.00 |
May | 0.548244E+09 | 0.246729E+09 | 0.375692E+09 | 0.123849E+09 | 0.251843E+09 | 0.00 | 0.00 |
June | 0.542474E+09 | 0.171670E+09 | 0.354964E+09 | 0.111790E+09 | 0.243174E+09 | 0.00 | 0.00 |
July | 0.736696E+09 | 0.155117E+09 | 0.431448E+09 | 0.192321E+09 | 0.239126E+09 | 0.00 | 0.00 |
August | 0.627756E+09 | 0.144957E+09 | 0.356325E+09 | 0.151948E+09 | 0.204377E+09 | 0.00 | 0.00 |
September | 0.430274E+09 | 0.226304E+09 | 0.278898E+09 | 0.111841E+09 | 0.167057E+09 | 0.00 | 0.00 |
October | 0.193685E+09 | 0.335559E+09 | 0.169514E+09 | 55687389.65 | 0.113827E+09 | 0.00 | 0.00 |
November | 47048596.78 | 0.442826E+09 | 85233798.10 | 18010891.45 | 67222906.65 | 0.00 | 0.00 |
December | 34610295.55 | 0.587231E+09 | 71988773.20 | 18921587.65 | 53067185.54 | 0.00 | 0.00 |
Annual Sum or Average | 0.383097E+10 | 0.408129E+10 | 0.280206E+10 | 0.974142E+09 | 0.182792E+10 | 0.00 | 0.00 |
Minimum of Months | 26175050.21 | 0.144957E+09 | 71988773.20 | 17222110.70 | 53067185.54 | 0.00 | 0.00 |
Maximum of Months | 0.736696E+09 | 0.599200E+09 | 0.431448E+09 | 0.192321E+09 | 0.251843E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 80117782.75 | 0.146244E+09 | 68867365.26 | 41641329.58 | 27226035.67 | 0.00 | 0.00 |
February | 0.122751E+09 | 0.136152E+09 | 95051333.39 | 59597125.26 | 35454208.13 | 0.00 | 0.00 |
March | 0.144843E+09 | 0.154168E+09 | 0.109798E+09 | 58093423.53 | 51704182.58 | 0.00 | 0.00 |
April | 0.154077E+09 | 0.127447E+09 | 0.109714E+09 | 45676911.44 | 64037256.93 | 0.00 | 0.00 |
May | 0.149964E+09 | 0.110203E+09 | 0.104489E+09 | 29411083.56 | 75077731.66 | 0.00 | 0.00 |
June | 0.132545E+09 | 84265271.06 | 90798727.29 | 21540830.93 | 69257896.35 | 0.00 | 0.00 |
July | 0.171991E+09 | 77863300.66 | 0.101268E+09 | 33649542.30 | 67618878.78 | 0.00 | 0.00 |
August | 0.192501E+09 | 74939978.58 | 0.109117E+09 | 47939927.61 | 61177066.65 | 0.00 | 0.00 |
September | 0.194372E+09 | 0.100917E+09 | 0.119678E+09 | 64637153.25 | 55041328.66 | 0.00 | 0.00 |
October | 0.162783E+09 | 0.139209E+09 | 0.114502E+09 | 70468405.44 | 44033696.14 | 0.00 | 0.00 |
November | 76654346.24 | 0.150692E+09 | 67117712.59 | 38995620.00 | 28122092.59 | 0.00 | 0.00 |
December | 91669599.67 | 0.160905E+09 | 73068004.29 | 47937599.68 | 25130404.62 | 0.00 | 0.00 |
Annual Sum or Average | 0.167427E+10 | 0.146301E+10 | 0.116347E+10 | 0.559589E+09 | 0.603881E+09 | 0.00 | 0.00 |
Minimum of Months | 76654346.24 | 74939978.58 | 67117712.59 | 21540830.93 | 25130404.62 | 0.00 | 0.00 |
Maximum of Months | 0.194372E+09 | 0.160905E+09 | 0.119678E+09 | 70468405.44 | 75077731.66 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 125702.64 | 0.184083E+09 | 15159094.26 | 0.00 | 15159094.26 | 0.00 | 0.00 |
February | 3393187.89 | 0.142737E+09 | 21305267.12 | 0.00 | 21305267.12 | 0.00 | 0.00 |
March | 15930382.05 | 0.120896E+09 | 34756326.87 | 32.97 | 34756293.91 | 0.00 | 0.00 |
April | 41352435.63 | 87367807.16 | 47668503.24 | 200160.98 | 47468342.26 | 0.00 | 0.00 |
May | 72703199.13 | 67858673.93 | 62930346.23 | 1512146.17 | 61418200.06 | 0.00 | 0.00 |
June | 85114927.58 | 46438625.45 | 63782208.18 | 3607853.18 | 60174355.00 | 0.00 | 0.00 |
July | 98147112.99 | 40394560.57 | 62533445.69 | 4212593.90 | 58320851.79 | 0.00 | 0.00 |
August | 83882209.29 | 37700371.75 | 51013124.97 | 1143294.95 | 49869830.01 | 0.00 | 0.00 |
September | 44097742.12 | 63056116.58 | 38496428.55 | 14996.18 | 38481432.37 | 0.00 | 0.00 |
October | 15343368.01 | 99504941.43 | 27246343.23 | 0.00 | 27246343.23 | 0.00 | 0.00 |
November | 1956266.04 | 0.135563E+09 | 16608861.54 | 0.00 | 16608861.54 | 0.00 | 0.00 |
December | 39196.09 | 0.178881E+09 | 12881321.90 | 0.00 | 12881321.90 | 0.00 | 0.00 |
Annual Sum or Average | 0.462086E+09 | 0.120448E+10 | 0.454381E+09 | 10691078.34 | 0.443690E+09 | 0.00 | 0.00 |
Minimum of Months | 39196.09 | 37700371.75 | 12881321.90 | 0.00 | 12881321.90 | 0.00 | 0.00 |
Maximum of Months | 98147112.99 | 0.184083E+09 | 63782208.18 | 4212593.90 | 61418200.06 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104357E+09 | 0.562323E+09 | 0.142114E+09 | 65651148.87 | 76463304.38 | 0.00 | 0.00 |
February | 0.222802E+09 | 0.436526E+09 | 0.212480E+09 | 0.107324E+09 | 0.105156E+09 | 0.00 | 0.00 |
March | 0.364585E+09 | 0.390583E+09 | 0.293675E+09 | 0.129414E+09 | 0.164261E+09 | 0.00 | 0.00 |
April | 0.535646E+09 | 0.292415E+09 | 0.372231E+09 | 0.155502E+09 | 0.216729E+09 | 0.00 | 0.00 |
May | 0.594999E+09 | 0.240983E+09 | 0.388264E+09 | 0.126866E+09 | 0.261399E+09 | 0.00 | 0.00 |
June | 0.677442E+09 | 0.166778E+09 | 0.412526E+09 | 0.157807E+09 | 0.254719E+09 | 0.00 | 0.00 |
July | 0.739371E+09 | 0.141849E+09 | 0.414533E+09 | 0.172086E+09 | 0.242447E+09 | 0.00 | 0.00 |
August | 0.773635E+09 | 0.132682E+09 | 0.420444E+09 | 0.203207E+09 | 0.217238E+09 | 0.00 | 0.00 |
September | 0.581182E+09 | 0.212295E+09 | 0.352866E+09 | 0.175468E+09 | 0.177398E+09 | 0.00 | 0.00 |
October | 0.389545E+09 | 0.324740E+09 | 0.279462E+09 | 0.146305E+09 | 0.133157E+09 | 0.00 | 0.00 |
November | 0.141632E+09 | 0.422685E+09 | 0.147893E+09 | 66437091.28 | 81455716.70 | 0.00 | 0.00 |
December | 0.133442E+09 | 0.553139E+09 | 0.145156E+09 | 76690585.62 | 68465851.23 | 0.00 | 0.00 |
Annual Sum or Average | 0.525864E+10 | 0.387700E+10 | 0.358164E+10 | 0.158276E+10 | 0.199889E+10 | 0.00 | 0.00 |
Minimum of Months | 0.104357E+09 | 0.132682E+09 | 0.142114E+09 | 65651148.87 | 68465851.23 | 0.00 | 0.00 |
Maximum of Months | 0.773635E+09 | 0.562323E+09 | 0.420444E+09 | 0.203207E+09 | 0.261399E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14410353.55 | 0.593975E+09 | 74959483.22 | 13589135.22 | 61370348.00 | 0.00 | 0.00 |
February | 70584396.53 | 0.452475E+09 | 0.120270E+09 | 32812606.93 | 87457505.75 | 0.00 | 0.00 |
March | 0.186751E+09 | 0.389889E+09 | 0.199840E+09 | 56782455.19 | 0.143058E+09 | 0.00 | 0.00 |
April | 0.372638E+09 | 0.289250E+09 | 0.294638E+09 | 98644708.91 | 0.195994E+09 | 0.00 | 0.00 |
May | 0.471540E+09 | 0.238542E+09 | 0.336280E+09 | 91984412.20 | 0.244295E+09 | 0.00 | 0.00 |
June | 0.585472E+09 | 0.167325E+09 | 0.378722E+09 | 0.135385E+09 | 0.243337E+09 | 0.00 | 0.00 |
July | 0.610769E+09 | 0.143864E+09 | 0.366079E+09 | 0.135280E+09 | 0.230798E+09 | 0.00 | 0.00 |
August | 0.603417E+09 | 0.136593E+09 | 0.347779E+09 | 0.144699E+09 | 0.203080E+09 | 0.00 | 0.00 |
September | 0.367963E+09 | 0.213615E+09 | 0.251352E+09 | 94674574.68 | 0.156678E+09 | 0.00 | 0.00 |
October | 0.185892E+09 | 0.324397E+09 | 0.170360E+09 | 58202454.63 | 0.112157E+09 | 0.00 | 0.00 |
November | 40332741.08 | 0.435908E+09 | 84737307.67 | 17682872.31 | 67054435.35 | 0.00 | 0.00 |
December | 22228254.83 | 0.577449E+09 | 69902785.71 | 16756669.15 | 53146116.56 | 0.00 | 0.00 |
Annual Sum or Average | 0.353200E+10 | 0.396328E+10 | 0.269492E+10 | 0.896494E+09 | 0.179843E+10 | 0.00 | 0.00 |
Minimum of Months | 14410353.55 | 0.136593E+09 | 69902785.71 | 13589135.22 | 53146116.56 | 0.00 | 0.00 |
Maximum of Months | 0.610769E+09 | 0.593975E+09 | 0.378722E+09 | 0.144699E+09 | 0.244295E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136771E+09 | 0.726130E+09 | 0.182056E+09 | 90225181.14 | 91830929.32 | 0.00 | 0.00 |
February | 0.258641E+09 | 0.562472E+09 | 0.252104E+09 | 0.129130E+09 | 0.122974E+09 | 0.00 | 0.00 |
March | 0.378034E+09 | 0.506875E+09 | 0.313195E+09 | 0.125872E+09 | 0.187322E+09 | 0.00 | 0.00 |
April | 0.474910E+09 | 0.381169E+09 | 0.340986E+09 | 99402780.57 | 0.241583E+09 | 0.00 | 0.00 |
May | 0.539134E+09 | 0.308137E+09 | 0.362726E+09 | 67001454.78 | 0.295725E+09 | 0.00 | 0.00 |
June | 0.528245E+09 | 0.214483E+09 | 0.334909E+09 | 54488810.12 | 0.280420E+09 | 0.00 | 0.00 |
July | 0.638497E+09 | 0.192098E+09 | 0.354889E+09 | 82035091.50 | 0.272854E+09 | 0.00 | 0.00 |
August | 0.650898E+09 | 0.186300E+09 | 0.346938E+09 | 0.106349E+09 | 0.240588E+09 | 0.00 | 0.00 |
September | 0.562716E+09 | 0.284376E+09 | 0.342706E+09 | 0.140083E+09 | 0.202623E+09 | 0.00 | 0.00 |
October | 0.421075E+09 | 0.416105E+09 | 0.307119E+09 | 0.152685E+09 | 0.154433E+09 | 0.00 | 0.00 |
November | 0.171616E+09 | 0.544520E+09 | 0.181406E+09 | 84492664.21 | 96913117.56 | 0.00 | 0.00 |
December | 0.173912E+09 | 0.713468E+09 | 0.186223E+09 | 0.103867E+09 | 82355860.90 | 0.00 | 0.00 |
Annual Sum or Average | 0.493445E+10 | 0.503613E+10 | 0.350526E+10 | 0.123563E+10 | 0.226962E+10 | 0.00 | 0.00 |
Minimum of Months | 0.136771E+09 | 0.186300E+09 | 0.181406E+09 | 54488810.12 | 82355860.90 | 0.00 | 0.00 |
Maximum of Months | 0.650898E+09 | 0.726130E+09 | 0.362726E+09 | 0.152685E+09 | 0.295725E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114249E+09 | 0.556960E+09 | 0.145701E+09 | 69284124.35 | 76416378.12 | 0.00 | 0.00 |
February | 0.232718E+09 | 0.435120E+09 | 0.215447E+09 | 0.110417E+09 | 0.105030E+09 | 0.00 | 0.00 |
March | 0.362329E+09 | 0.394459E+09 | 0.288003E+09 | 0.123586E+09 | 0.164418E+09 | 0.00 | 0.00 |
April | 0.521123E+09 | 0.301359E+09 | 0.359635E+09 | 0.142549E+09 | 0.217086E+09 | 0.00 | 0.00 |
May | 0.667401E+09 | 0.247434E+09 | 0.427677E+09 | 0.158730E+09 | 0.268947E+09 | 0.00 | 0.00 |
June | 0.631086E+09 | 0.172997E+09 | 0.388768E+09 | 0.134212E+09 | 0.254556E+09 | 0.00 | 0.00 |
July | 0.862090E+09 | 0.151869E+09 | 0.479902E+09 | 0.229126E+09 | 0.250775E+09 | 0.00 | 0.00 |
August | 0.792898E+09 | 0.140505E+09 | 0.428991E+09 | 0.210456E+09 | 0.218535E+09 | 0.00 | 0.00 |
September | 0.639431E+09 | 0.218431E+09 | 0.380412E+09 | 0.192634E+09 | 0.187777E+09 | 0.00 | 0.00 |
October | 0.391035E+09 | 0.325002E+09 | 0.278617E+09 | 0.143790E+09 | 0.134827E+09 | 0.00 | 0.00 |
November | 0.145232E+09 | 0.418299E+09 | 0.148389E+09 | 66765110.42 | 81624188.00 | 0.00 | 0.00 |
December | 0.143099E+09 | 0.550460E+09 | 0.147242E+09 | 78855504.12 | 68386920.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.550269E+10 | 0.391289E+10 | 0.368878E+10 | 0.166041E+10 | 0.202838E+10 | 0.00 | 0.00 |
Minimum of Months | 0.114249E+09 | 0.140505E+09 | 0.145701E+09 | 66765110.42 | 68386920.22 | 0.00 | 0.00 |
Maximum of Months | 0.862090E+09 | 0.556960E+09 | 0.479902E+09 | 0.229126E+09 | 0.268947E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26844893.72 | 0.590891E+09 | 78545532.45 | 17222110.70 | 61323421.75 | 0.00 | 0.00 |
February | 88861180.29 | 0.458303E+09 | 0.123237E+09 | 35905768.34 | 87331727.11 | 0.00 | 0.00 |
March | 0.191371E+09 | 0.399152E+09 | 0.194169E+09 | 50954505.48 | 0.143214E+09 | 0.00 | 0.00 |
April | 0.360397E+09 | 0.300012E+09 | 0.282043E+09 | 85691726.84 | 0.196351E+09 | 0.00 | 0.00 |
May | 0.538812E+09 | 0.246844E+09 | 0.375692E+09 | 0.123849E+09 | 0.251843E+09 | 0.00 | 0.00 |
June | 0.531997E+09 | 0.172635E+09 | 0.354964E+09 | 0.111790E+09 | 0.243174E+09 | 0.00 | 0.00 |
July | 0.724843E+09 | 0.157107E+09 | 0.431448E+09 | 0.192321E+09 | 0.239126E+09 | 0.00 | 0.00 |
August | 0.620676E+09 | 0.144295E+09 | 0.356325E+09 | 0.151948E+09 | 0.204377E+09 | 0.00 | 0.00 |
September | 0.425101E+09 | 0.225213E+09 | 0.278898E+09 | 0.111841E+09 | 0.167057E+09 | 0.00 | 0.00 |
October | 0.193631E+09 | 0.329596E+09 | 0.169514E+09 | 55687389.65 | 0.113827E+09 | 0.00 | 0.00 |
November | 47962583.45 | 0.434950E+09 | 85233798.10 | 18010891.45 | 67222906.65 | 0.00 | 0.00 |
December | 35569471.74 | 0.577589E+09 | 71988773.20 | 18921587.65 | 53067185.54 | 0.00 | 0.00 |
Annual Sum or Average | 0.378606E+10 | 0.403659E+10 | 0.280206E+10 | 0.974142E+09 | 0.182792E+10 | 0.00 | 0.00 |
Minimum of Months | 26844893.72 | 0.144295E+09 | 71988773.20 | 17222110.70 | 53067185.54 | 0.00 | 0.00 |
Maximum of Months | 0.724843E+09 | 0.590891E+09 | 0.431448E+09 | 0.192321E+09 | 0.251843E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141341E+09 | 0.287092E+09 | 0.126276E+09 | 76353939.43 | 49921918.91 | 0.00 | 0.00 |
February | 0.229246E+09 | 0.227073E+09 | 0.174287E+09 | 0.109278E+09 | 65009174.48 | 0.00 | 0.00 |
March | 0.287278E+09 | 0.209017E+09 | 0.201326E+09 | 0.106521E+09 | 94805282.74 | 0.00 | 0.00 |
April | 0.313848E+09 | 0.161193E+09 | 0.201173E+09 | 83753620.84 | 0.117419E+09 | 0.00 | 0.00 |
May | 0.311172E+09 | 0.130524E+09 | 0.191592E+09 | 53928443.57 | 0.137663E+09 | 0.00 | 0.00 |
June | 0.283418E+09 | 90398863.34 | 0.166489E+09 | 39497473.23 | 0.126992E+09 | 0.00 | 0.00 |
July | 0.356431E+09 | 77729357.20 | 0.185687E+09 | 61700121.98 | 0.123987E+09 | 0.00 | 0.00 |
August | 0.393971E+09 | 71642793.38 | 0.200078E+09 | 87903108.89 | 0.112175E+09 | 0.00 | 0.00 |
September | 0.388379E+09 | 0.113148E+09 | 0.219444E+09 | 0.118519E+09 | 0.100924E+09 | 0.00 | 0.00 |
October | 0.324478E+09 | 0.171217E+09 | 0.209952E+09 | 0.129212E+09 | 80740605.58 | 0.00 | 0.00 |
November | 0.153641E+09 | 0.218277E+09 | 0.123068E+09 | 71502741.08 | 51564937.42 | 0.00 | 0.00 |
December | 0.169669E+09 | 0.284851E+09 | 0.133978E+09 | 87898840.37 | 46079349.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.335287E+10 | 0.204216E+10 | 0.213335E+10 | 0.102607E+10 | 0.110728E+10 | 0.00 | 0.00 |
Minimum of Months | 0.141341E+09 | 71642793.38 | 0.123068E+09 | 39497473.23 | 46079349.80 | 0.00 | 0.00 |
Maximum of Months | 0.393971E+09 | 0.287092E+09 | 0.219444E+09 | 0.129212E+09 | 0.137663E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 983348.22 | 0.161302E+10 | 0.132619E+09 | 0.00 | 0.132619E+09 | 0.00 | 0.00 |
February | 29942473.69 | 0.125352E+10 | 0.186389E+09 | 0.00 | 0.186389E+09 | 0.00 | 0.00 |
March | 0.139616E+09 | 0.106787E+10 | 0.304066E+09 | 288.41 | 0.304066E+09 | 0.00 | 0.00 |
April | 0.365410E+09 | 0.782248E+09 | 0.417028E+09 | 1751110.17 | 0.415277E+09 | 0.00 | 0.00 |
May | 0.643703E+09 | 0.618174E+09 | 0.550547E+09 | 13229024.31 | 0.537318E+09 | 0.00 | 0.00 |
June | 0.755297E+09 | 0.429580E+09 | 0.557999E+09 | 31563335.86 | 0.526436E+09 | 0.00 | 0.00 |
July | 0.876320E+09 | 0.376199E+09 | 0.547074E+09 | 36853915.44 | 0.510220E+09 | 0.00 | 0.00 |
August | 0.752572E+09 | 0.355867E+09 | 0.446289E+09 | 10002126.14 | 0.436287E+09 | 0.00 | 0.00 |
September | 0.396477E+09 | 0.566504E+09 | 0.336786E+09 | 131194.17 | 0.336655E+09 | 0.00 | 0.00 |
October | 0.136787E+09 | 0.885676E+09 | 0.238365E+09 | 0.00 | 0.238365E+09 | 0.00 | 0.00 |
November | 17730046.69 | 0.119009E+10 | 0.145303E+09 | 0.00 | 0.145303E+09 | 0.00 | 0.00 |
December | 311678.64 | 0.156431E+10 | 0.112692E+09 | 0.00 | 0.112692E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.411515E+10 | 0.107031E+11 | 0.397516E+10 | 93530994.50 | 0.388163E+10 | 0.00 | 0.00 |
Minimum of Months | 311678.64 | 0.355867E+09 | 0.112692E+09 | 0.00 | 0.112692E+09 | 0.00 | 0.00 |
Maximum of Months | 0.876320E+09 | 0.161302E+10 | 0.557999E+09 | 36853915.44 | 0.537318E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 591737.63 | 0.167842E+10 | 0.132619E+09 | 0.00 | 0.132619E+09 | 0.00 | 0.00 |
February | 26081716.90 | 0.131035E+10 | 0.186389E+09 | 0.00 | 0.186389E+09 | 0.00 | 0.00 |
March | 0.125804E+09 | 0.112140E+10 | 0.304066E+09 | 288.41 | 0.304066E+09 | 0.00 | 0.00 |
April | 0.344601E+09 | 0.821152E+09 | 0.417028E+09 | 1751110.17 | 0.415277E+09 | 0.00 | 0.00 |
May | 0.619422E+09 | 0.646080E+09 | 0.550547E+09 | 13229024.31 | 0.537318E+09 | 0.00 | 0.00 |
June | 0.729839E+09 | 0.449666E+09 | 0.557999E+09 | 31563335.86 | 0.526436E+09 | 0.00 | 0.00 |
July | 0.851808E+09 | 0.394904E+09 | 0.547074E+09 | 36853915.44 | 0.510220E+09 | 0.00 | 0.00 |
August | 0.729508E+09 | 0.375989E+09 | 0.446289E+09 | 10002126.14 | 0.436287E+09 | 0.00 | 0.00 |
September | 0.379316E+09 | 0.595722E+09 | 0.336786E+09 | 131194.17 | 0.336655E+09 | 0.00 | 0.00 |
October | 0.123902E+09 | 0.935270E+09 | 0.238365E+09 | 0.00 | 0.238365E+09 | 0.00 | 0.00 |
November | 14557625.00 | 0.125231E+10 | 0.145303E+09 | 0.00 | 0.145303E+09 | 0.00 | 0.00 |
December | 133211.87 | 0.163075E+10 | 0.112692E+09 | 0.00 | 0.112692E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.394557E+10 | 0.112120E+11 | 0.397516E+10 | 93530994.50 | 0.388163E+10 | 0.00 | 0.00 |
Minimum of Months | 133211.87 | 0.375989E+09 | 0.112692E+09 | 0.00 | 0.112692E+09 | 0.00 | 0.00 |
Maximum of Months | 0.851808E+09 | 0.167842E+10 | 0.557999E+09 | 36853915.44 | 0.537318E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257499E+09 | 0.810358E+09 | 0.217066E+09 | 79238354.08 | 0.137828E+09 | 0.00 | 0.00 |
February | 0.524810E+09 | 0.659400E+09 | 0.332737E+09 | 0.140132E+09 | 0.192605E+09 | 0.00 | 0.00 |
March | 0.919231E+09 | 0.600630E+09 | 0.493493E+09 | 0.186188E+09 | 0.307304E+09 | 0.00 | 0.00 |
April | 0.138457E+10 | 0.478342E+09 | 0.666835E+09 | 0.254133E+09 | 0.412703E+09 | 0.00 | 0.00 |
May | 0.162201E+10 | 0.399884E+09 | 0.724507E+09 | 0.218837E+09 | 0.505670E+09 | 0.00 | 0.00 |
June | 0.186719E+10 | 0.292137E+09 | 0.791206E+09 | 0.293174E+09 | 0.498032E+09 | 0.00 | 0.00 |
July | 0.200699E+10 | 0.251107E+09 | 0.780570E+09 | 0.307347E+09 | 0.473223E+09 | 0.00 | 0.00 |
August | 0.203701E+10 | 0.235222E+09 | 0.768183E+09 | 0.347885E+09 | 0.420298E+09 | 0.00 | 0.00 |
September | 0.147788E+10 | 0.307633E+09 | 0.604189E+09 | 0.270129E+09 | 0.334060E+09 | 0.00 | 0.00 |
October | 0.962730E+09 | 0.469512E+09 | 0.449803E+09 | 0.204500E+09 | 0.245303E+09 | 0.00 | 0.00 |
November | 0.397150E+09 | 0.574864E+09 | 0.232621E+09 | 84117452.18 | 0.148504E+09 | 0.00 | 0.00 |
December | 0.302246E+09 | 0.782653E+09 | 0.215052E+09 | 93444874.90 | 0.121607E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137593E+11 | 0.586174E+10 | 0.627626E+10 | 0.247913E+10 | 0.379714E+10 | 0.00 | 0.00 |
Minimum of Months | 0.257499E+09 | 0.235222E+09 | 0.215052E+09 | 79238354.08 | 0.121607E+09 | 0.00 | 0.00 |
Maximum of Months | 0.203701E+10 | 0.810358E+09 | 0.791206E+09 | 0.347885E+09 | 0.505670E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.310579E+09 | 0.129222E+10 | 0.366904E+09 | 0.194363E+09 | 0.172541E+09 | 0.00 | 0.00 |
February | 0.554817E+09 | 0.101059E+10 | 0.507552E+09 | 0.278173E+09 | 0.229379E+09 | 0.00 | 0.00 |
March | 0.760669E+09 | 0.946062E+09 | 0.616720E+09 | 0.271154E+09 | 0.345566E+09 | 0.00 | 0.00 |
April | 0.893260E+09 | 0.748471E+09 | 0.655055E+09 | 0.213800E+09 | 0.441255E+09 | 0.00 | 0.00 |
May | 0.949144E+09 | 0.637886E+09 | 0.676435E+09 | 0.141813E+09 | 0.534623E+09 | 0.00 | 0.00 |
June | 0.888539E+09 | 0.465099E+09 | 0.615091E+09 | 0.111363E+09 | 0.503728E+09 | 0.00 | 0.00 |
July | 0.110567E+10 | 0.423028E+09 | 0.660214E+09 | 0.169695E+09 | 0.490519E+09 | 0.00 | 0.00 |
August | 0.117298E+10 | 0.411275E+09 | 0.662298E+09 | 0.227191E+09 | 0.435107E+09 | 0.00 | 0.00 |
September | 0.107083E+10 | 0.587881E+09 | 0.674056E+09 | 0.301742E+09 | 0.372314E+09 | 0.00 | 0.00 |
October | 0.842599E+09 | 0.805445E+09 | 0.616156E+09 | 0.328915E+09 | 0.287241E+09 | 0.00 | 0.00 |
November | 0.364592E+09 | 0.993254E+09 | 0.363085E+09 | 0.182014E+09 | 0.181071E+09 | 0.00 | 0.00 |
December | 0.388200E+09 | 0.127007E+10 | 0.379680E+09 | 0.223751E+09 | 0.155929E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.930188E+10 | 0.959129E+10 | 0.679325E+10 | 0.264397E+10 | 0.414927E+10 | 0.00 | 0.00 |
Minimum of Months | 0.310579E+09 | 0.411275E+09 | 0.363085E+09 | 0.111363E+09 | 0.155929E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117298E+10 | 0.129222E+10 | 0.676435E+09 | 0.328915E+09 | 0.534623E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770419E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413804.5 | 81.21 | 0.00 | 0.00 |
February | 0.696176E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145793138.9 | 81.21 | 0.00 | 0.00 |
March | 0.770288E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413953.9 | 81.21 | 0.00 | 0.00 |
April | 0.746480E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206890.1 | 81.21 | 0.00 | 0.00 |
May | 0.770421E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413384.3 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206392.2 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412479.2 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412162.2 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156205852.3 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413524.9 | 81.21 | 0.00 | 0.00 |
November | 0.744863E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206369.9 | 81.21 | 0.00 | 0.00 |
December | 0.771227E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161413775.4 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907409E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190051E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696176E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161413953.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771227E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145793138.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.119955E+12 | -0.118179E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177589E+10 | 81.27 | 0.00 | 0.00 |
February | 0.108867E+12 | -0.107257E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160968E+10 | 81.27 | 0.00 | 0.00 |
March | 0.119608E+12 | -0.117820E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178842E+10 | 81.27 | 0.00 | 0.00 |
April | 0.113594E+12 | -0.111860E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173388E+10 | 81.26 | 0.00 | 0.00 |
May | 0.114434E+12 | -0.112645E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178893E+10 | 81.26 | 0.00 | 0.00 |
June | 0.107971E+12 | -0.106245E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172599E+10 | 81.26 | 0.00 | 0.00 |
July | 0.109558E+12 | -0.107781E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177683E+10 | 81.25 | 0.00 | 0.00 |
August | 0.108933E+12 | -0.107162E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177114E+10 | 81.26 | 0.00 | 0.00 |
September | 0.106336E+12 | -0.104629E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170716E+10 | 81.26 | 0.00 | 0.00 |
October | 0.112133E+12 | -0.110374E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175844E+10 | 81.26 | 0.00 | 0.00 |
November | 0.111365E+12 | -0.109665E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169947E+10 | 81.26 | 0.00 | 0.00 |
December | 0.117933E+12 | -0.116168E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176473E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.135069E+13 | -0.132979E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209006E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.106336E+12 | -0.118179E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.178893E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.119955E+12 | -0.104629E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160968E+10 | 81.27 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.709469E+11 | -0.694163E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153065E+10 | 58.98 | 0.00 | 0.00 |
February | 0.645388E+11 | -0.631485E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139033E+10 | 58.98 | 0.00 | 0.00 |
March | 0.707190E+11 | -0.691710E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154795E+10 | 58.98 | 0.00 | 0.00 |
April | 0.665552E+11 | -0.650527E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150255E+10 | 58.98 | 0.00 | 0.00 |
May | 0.662524E+11 | -0.647034E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154904E+10 | 58.98 | 0.00 | 0.00 |
June | 0.617489E+11 | -0.602571E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149181E+10 | 58.98 | 0.00 | 0.00 |
July | 0.620122E+11 | -0.604797E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153247E+10 | 58.98 | 0.00 | 0.00 |
August | 0.615335E+11 | -0.600090E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152445E+10 | 58.98 | 0.00 | 0.00 |
September | 0.603027E+11 | -0.588368E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146582E+10 | 58.98 | 0.00 | 0.00 |
October | 0.642190E+11 | -0.627122E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150681E+10 | 58.98 | 0.00 | 0.00 |
November | 0.645973E+11 | -0.631422E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145513E+10 | 58.98 | 0.00 | 0.00 |
December | 0.692063E+11 | -0.676910E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151535E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.782632E+12 | -0.764620E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.180123E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.603027E+11 | -0.694163E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.154904E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.709469E+11 | -0.588368E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139033E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.88 | 0.86 | 01-JAN-10:30 | 1645.13 | 31.52 | 218.33 | 208.00 | 1255.28 | 32.49 | 222.33 | 152.67 |
February | 259.50 | 0.87 | 0.86 | 01-FEB-08:39 | 2877.71 | 32.07 | 231.33 | 233.50 | 1240.64 | 27.81 | 158.67 | 187.00 |
March | 247.00 | 0.87 | 0.86 | 01-MAR-07:40 | 4155.70 | 28.94 | 160.50 | 298.17 | 530.04 | 20.48 | 95.00 | 216.50 |
April | 379.50 | 0.88 | 0.86 | 01-APR-07:19 | 1091.05 | 17.37 | 0.00 | 330.33 | 426.32 | 19.59 | 122.67 | 249.33 |
May | 427.83 | 0.88 | 0.86 | 01-MAY-07:00 | 1004.96 | 17.16 | 0.00 | 368.83 | 388.23 | 19.36 | 123.00 | 262.83 |
June | 375.17 | 0.88 | 0.86 | 01-JUN-07:40 | 849.70 | 17.10 | 0.00 | 373.00 | 343.53 | 19.37 | 72.33 | 267.17 |
July | 471.00 | 0.89 | 0.86 | 01-JUL-10:09 | 732.28 | 15.96 | 0.00 | 360.33 | 295.60 | 18.26 | 77.17 | 218.17 |
August | 366.67 | 0.88 | 0.86 | 01-AUG-06:40 | 846.87 | 17.11 | 0.00 | 348.83 | 347.30 | 19.40 | 63.83 | 249.67 |
September | 301.17 | 0.87 | 0.86 | 01-SEP-07:00 | 2355.46 | 22.81 | 89.67 | 307.50 | 480.66 | 20.51 | 121.33 | 231.17 |
October | 245.33 | 0.87 | 0.86 | 01-OCT-08:20 | 4446.24 | 33.52 | 219.33 | 273.50 | 639.87 | 22.54 | 105.33 | 211.83 |
November | 242.67 | 0.87 | 0.86 | 01-NOV-08:30 | 1852.45 | 31.22 | 218.67 | 215.00 | 1234.59 | 31.48 | 213.50 | 156.83 |
December | 160.33 | 0.87 | 0.86 | 01-DEC-09:39 | 2211.70 | 34.74 | 149.67 | 195.67 | 1814.08 | 35.83 | 150.17 | 127.33 |
Annual Sum or Average | 3714.00 | 0.88 | 1773.57 | 22.98 | 1287.50 | 3512.67 | 637.30 | 22.56 | 1525.33 | 2530.50 | ||
Minimum of Months | 160.33 | 0.87 | 0.86 | 732.28 | 15.96 | 0.00 | 195.67 | 295.60 | 18.26 | 63.83 | 127.33 | |
Maximum of Months | 471.00 | 0.89 | 0.86 | 4446.24 | 34.74 | 231.33 | 373.00 | 1814.08 | 35.83 | 222.33 | 267.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.27 | 0.22 | 01-JAN-09:50 | 1803.61 | 31.64 | 218.83 | 220.67 | 1412.34 | 32.60 | 223.17 | 185.00 |
February | 259.50 | 0.26 | 0.22 | 01-FEB-08:39 | 3092.55 | 32.21 | 232.67 | 244.83 | 1453.66 | 28.07 | 170.50 | 219.00 |
March | 247.00 | 0.27 | 0.22 | 01-MAR-07:30 | 4416.06 | 29.31 | 160.83 | 314.83 | 788.58 | 20.88 | 111.00 | 264.50 |
April | 379.50 | 0.27 | 0.22 | 01-APR-06:00 | 1284.84 | 18.23 | 0.00 | 347.83 | 619.23 | 20.22 | 164.00 | 301.17 |
May | 427.83 | 0.27 | 0.22 | 01-MAY-07:10 | 1172.31 | 18.13 | 0.00 | 387.67 | 554.78 | 20.09 | 165.17 | 338.33 |
June | 375.17 | 0.28 | 0.22 | 01-JUN-05:00 | 1003.46 | 18.08 | 0.00 | 398.00 | 496.70 | 20.10 | 150.83 | 336.00 |
July | 471.00 | 0.31 | 0.22 | 01-JUL-05:30 | 878.69 | 16.97 | 0.00 | 396.83 | 441.49 | 19.02 | 128.50 | 320.00 |
August | 366.67 | 0.29 | 0.22 | 01-AUG-06:10 | 1033.22 | 17.91 | 0.00 | 376.67 | 533.04 | 19.96 | 105.83 | 317.67 |
September | 301.17 | 0.26 | 0.22 | 01-SEP-07:40 | 2602.43 | 23.28 | 89.67 | 321.00 | 726.87 | 20.92 | 130.33 | 282.33 |
October | 245.33 | 0.27 | 0.22 | 01-OCT-07:49 | 4712.59 | 33.72 | 219.83 | 286.00 | 906.35 | 22.80 | 107.67 | 251.00 |
November | 242.67 | 0.26 | 0.22 | 01-NOV-08:09 | 2010.02 | 31.34 | 221.00 | 227.50 | 1391.27 | 31.60 | 214.33 | 193.33 |
December | 160.33 | 0.26 | 0.22 | 01-DEC-09:39 | 2429.44 | 34.89 | 149.67 | 210.33 | 2030.32 | 35.95 | 150.17 | 165.67 |
Annual Sum or Average | 3714.00 | 0.28 | 1964.94 | 23.59 | 1292.50 | 3732.17 | 827.79 | 23.05 | 1821.50 | 3174.00 | ||
Minimum of Months | 160.33 | 0.26 | 0.22 | 878.69 | 16.97 | 0.00 | 210.33 | 441.49 | 19.02 | 105.83 | 165.67 | |
Maximum of Months | 471.00 | 0.31 | 0.22 | 4712.59 | 34.89 | 232.67 | 398.00 | 2030.32 | 35.95 | 223.17 | 338.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.72 | 0.60 | 06-JAN-12:20 | 243.31 | 11.21 | 0.00 | 156.33 | 105.35 | 14.99 | 0.00 | 0.00 |
February | 259.50 | 0.68 | 0.60 | 01-FEB-11:20 | 301.61 | 12.52 | 0.00 | 194.33 | 135.04 | 16.38 | 0.00 | 9.67 |
March | 247.00 | 0.65 | 0.60 | 01-MAR-09:50 | 390.32 | 14.04 | 0.00 | 285.83 | 182.62 | 17.85 | 0.00 | 97.17 |
April | 379.50 | 0.64 | 0.60 | 01-APR-07:40 | 465.70 | 14.92 | 0.00 | 345.33 | 211.46 | 18.60 | 0.00 | 216.17 |
May | 427.83 | 0.63 | 0.60 | 01-MAY-07:30 | 580.08 | 16.27 | 16.83 | 395.17 | 260.55 | 20.33 | 38.17 | 307.00 |
June | 375.17 | 0.62 | 0.60 | 01-JUN-05:40 | 595.57 | 17.61 | 38.50 | 411.00 | 282.97 | 22.02 | 72.17 | 342.67 |
July | 471.00 | 0.64 | 0.60 | 01-JUL-05:10 | 499.71 | 16.45 | 47.00 | 404.00 | 237.18 | 21.04 | 81.17 | 252.50 |
August | 366.67 | 0.64 | 0.60 | 01-AUG-05:49 | 427.66 | 15.60 | 12.83 | 383.67 | 204.54 | 19.33 | 13.17 | 191.50 |
September | 301.17 | 0.64 | 0.60 | 01-SEP-07:00 | 415.84 | 14.90 | 0.00 | 307.50 | 200.50 | 18.68 | 0.00 | 150.33 |
October | 245.33 | 0.67 | 0.60 | 01-OCT-11:39 | 313.22 | 13.11 | 0.00 | 241.83 | 151.67 | 17.06 | 0.00 | 37.50 |
November | 242.67 | 0.71 | 0.60 | 01-NOV-12:09 | 263.17 | 11.68 | 0.00 | 171.67 | 113.21 | 15.44 | 0.00 | 0.50 |
December | 160.33 | 0.73 | 0.60 | 01-DEC-10:30 | 219.94 | 11.21 | 0.00 | 128.50 | 105.24 | 15.33 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.66 | 423.87 | 14.65 | 115.17 | 3425.17 | 197.02 | 18.65 | 204.67 | 1605.00 | ||
Minimum of Months | 160.33 | 0.62 | 0.60 | 219.94 | 11.21 | 0.00 | 128.50 | 105.24 | 14.99 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.73 | 0.60 | 595.57 | 17.61 | 47.00 | 411.00 | 282.97 | 22.02 | 81.17 | 342.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.72 | 0.60 | 06-JAN-12:20 | 243.31 | 11.21 | 0.00 | 156.33 | 105.35 | 14.99 | 0.00 | 0.00 |
February | 259.50 | 0.68 | 0.60 | 01-FEB-11:20 | 301.61 | 12.52 | 0.00 | 194.33 | 135.04 | 16.38 | 0.00 | 9.67 |
March | 247.00 | 0.65 | 0.60 | 01-MAR-09:50 | 390.32 | 14.04 | 0.00 | 285.83 | 182.62 | 17.85 | 0.00 | 97.17 |
April | 379.50 | 0.64 | 0.60 | 01-APR-07:40 | 465.70 | 14.92 | 0.00 | 345.33 | 211.46 | 18.60 | 0.00 | 216.17 |
May | 427.83 | 0.63 | 0.60 | 01-MAY-07:30 | 580.08 | 16.27 | 16.83 | 395.17 | 260.55 | 20.33 | 38.17 | 307.00 |
June | 375.17 | 0.62 | 0.60 | 01-JUN-05:40 | 595.57 | 17.61 | 38.50 | 411.00 | 282.97 | 22.02 | 72.17 | 342.67 |
July | 471.00 | 0.64 | 0.60 | 01-JUL-05:10 | 499.71 | 16.45 | 47.00 | 404.00 | 237.18 | 21.04 | 81.17 | 252.50 |
August | 366.67 | 0.64 | 0.60 | 01-AUG-05:49 | 427.66 | 15.60 | 12.83 | 383.67 | 204.54 | 19.33 | 13.17 | 191.50 |
September | 301.17 | 0.64 | 0.60 | 01-SEP-07:00 | 415.84 | 14.90 | 0.00 | 307.50 | 200.50 | 18.68 | 0.00 | 150.33 |
October | 245.33 | 0.67 | 0.60 | 01-OCT-11:39 | 313.22 | 13.11 | 0.00 | 241.83 | 151.67 | 17.06 | 0.00 | 37.50 |
November | 242.67 | 0.71 | 0.60 | 01-NOV-12:09 | 263.17 | 11.68 | 0.00 | 171.67 | 113.21 | 15.44 | 0.00 | 0.50 |
December | 160.33 | 0.73 | 0.60 | 01-DEC-10:30 | 219.94 | 11.21 | 0.00 | 128.50 | 105.24 | 15.33 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.66 | 423.87 | 14.65 | 115.17 | 3425.17 | 197.02 | 18.65 | 204.67 | 1605.00 | ||
Minimum of Months | 160.33 | 0.62 | 0.60 | 219.94 | 11.21 | 0.00 | 128.50 | 105.24 | 14.99 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.73 | 0.60 | 595.57 | 17.61 | 47.00 | 411.00 | 282.97 | 22.02 | 81.17 | 342.67 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.742494E+11 | 89145.51 | 07-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.575364E+11 | 82101.98 | 13-FEB-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.471442E+11 | 80160.80 | 02-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236338E+11 | 77599.11 | 19-APR-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.863848E+10 | 54434.07 | 11-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.310460E+09 | 17897.10 | 15-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.676959E+09 | 28250.39 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.983025E+10 | 40564.30 | 13-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.512453E+11 | 81935.12 | 11-NOV-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.841237E+11 | 84690.04 | 26-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.841237E+11 | 89145.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179551E+10 | 1344.49 | 16-JAN-17:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107782E+10 | 1425.74 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638528E+09 | 1003.91 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250675E+09 | 768.35 | 18-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67727939.53 | 560.05 | 18-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4351745.74 | 314.22 | 14-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35223934.92 | 533.35 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.312139E+09 | 732.20 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106655E+10 | 1197.67 | 30-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164036E+10 | 1533.97 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.688889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179551E+10 | 1533.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.419755E+09 | 727.97 | 17-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250065E+09 | 678.06 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125061E+09 | 538.44 | 13-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41292409.34 | 504.89 | 18-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5553494.65 | 338.29 | 18-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 689319.20 | 325.12 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1863065.93 | 277.91 | 28-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44427577.34 | 403.36 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206527E+09 | 583.19 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343126E+09 | 739.83 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419755E+09 | 739.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4365130.19 | 180.01 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3231324.01 | 150.48 | 19-FEB-17:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 754461.81 | 61.85 | 26-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8350916.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4365130.19 | 180.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144470E+10 | 834.52 | 07-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109582E+10 | 848.13 | 19-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.790953E+09 | 623.83 | 05-MAR-17:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.428739E+09 | 570.59 | 19-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132716E+09 | 415.04 | 18-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18555158.10 | 293.59 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4721.73 | 7.87 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 60688.59 | 62.07 | 04-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36739999.06 | 335.70 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358451E+09 | 496.56 | 30-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.855882E+09 | 687.84 | 13-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131494E+10 | 842.13 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.647756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4721.73 | 7.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144470E+10 | 848.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.442138E+10 | 6007.82 | 26-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275491E+10 | 6049.67 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216848E+10 | 5326.05 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123456E+10 | 4708.05 | 10-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.905602E+09 | 4459.66 | 17-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583780E+09 | 4194.69 | 14-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.295640E+09 | 3922.22 | 12-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310645E+09 | 3398.09 | 01-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.757047E+09 | 4811.15 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152659E+10 | 5036.42 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319240E+10 | 6048.30 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400058E+10 | 6724.62 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.295640E+09 | 3398.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442138E+10 | 6724.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.269298E+10 | 10048.13 | 17-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128457E+10 | 9172.11 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440721E+09 | 6366.35 | 07-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60250937.44 | 4980.96 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 790548.82 | 1116.38 | 18-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1123686.25 | 924.10 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87716570.03 | 4705.51 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104490E+10 | 7918.00 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227537E+10 | 11007.70 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.788841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269298E+10 | 11007.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.795754E+10 | 6417.06 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.515976E+10 | 6007.21 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292808E+10 | 4760.15 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.989889E+09 | 4088.07 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36594815.57 | 2065.29 | 29-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17892626.41 | 1507.08 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155799E+10 | 4297.51 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.498201E+10 | 5720.13 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.728983E+10 | 6848.56 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.795754E+10 | 6848.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179941E+10 | 1944.41 | 16-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.921085E+09 | 2267.53 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24668665.71 | 695.83 | 05-MAR-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.550263E+09 | 1413.95 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151369E+10 | 2215.17 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179941E+10 | 2267.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100516E+10 | 4345.29 | 09-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.635617E+09 | 4090.24 | 09-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265005E+09 | 3897.76 | 24-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80069251.80 | 3314.62 | 12-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33533728.34 | 2823.04 | 11-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18588227.11 | 2415.78 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8402287.78 | 1112.12 | 03-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13054460.90 | 1564.03 | 22-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34572222.52 | 2942.48 | 28-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126564E+09 | 3309.63 | 24-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.534301E+09 | 3856.97 | 13-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.913007E+09 | 4196.68 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8402287.78 | 1112.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100516E+10 | 4345.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110254E+09 | 2596.85 | 09-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56028009.28 | 2473.44 | 07-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26534339.38 | 2757.87 | 24-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10899913.29 | 1519.63 | 19-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 617690.74 | 657.14 | 18-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 549732.59 | 572.02 | 28-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15246766.64 | 1630.31 | 24-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33395564.49 | 2120.68 | 13-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 95650889.87 | 2438.37 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110254E+09 | 2757.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117605E+09 | 1545.85 | 07-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93491715.05 | 2206.72 | 19-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13199.94 | 19.81 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4304.05 | 0.54 | 29-APR-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6918.95 | 0.54 | 05-MAY-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20115.09 | 0.53 | 21-JUN-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23830.79 | 0.55 | 30-JUL-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26016.37 | 0.54 | 26-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19259.96 | 0.55 | 23-SEP-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3830.19 | 0.53 | 05-OCT-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 139310.27 | 229.87 | 30-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21026763.18 | 2611.61 | 26-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3830.19 | 0.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117605E+09 | 2611.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365252E+10 | 8191.28 | 01-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241282E+10 | 8188.30 | 16-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149849E+10 | 8134.21 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698618E+09 | 7972.91 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.238573E+09 | 4817.93 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 55087139.05 | 3880.92 | 08-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8471572.90 | 3411.81 | 03-JUL-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12565035.25 | 4104.43 | 01-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97419729.58 | 3599.51 | 02-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.823085E+09 | 7976.21 | 31-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.224640E+10 | 8190.47 | 26-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338158E+10 | 8190.78 | 17-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8471572.90 | 3411.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365252E+10 | 8191.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.404271E+10 | 7987.98 | 01-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287195E+10 | 7984.88 | 21-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185838E+10 | 7957.00 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.868012E+09 | 7781.31 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264565E+09 | 4655.98 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57067638.85 | 3907.28 | 12-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8175005.81 | 3507.81 | 25-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9158575.93 | 3885.39 | 01-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118955E+09 | 3656.37 | 10-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109267E+10 | 7801.83 | 31-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256179E+10 | 7987.11 | 26-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379447E+10 | 7987.44 | 17-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8175005.81 | 3507.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.404271E+10 | 7987.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.880795E+10 | 45231.52 | 07-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.593488E+10 | 45101.30 | 19-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170362E+10 | 42503.77 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.409025E+09 | 24583.47 | 19-APR-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82263155.25 | 15973.73 | 18-MAY-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30075141.27 | 16637.28 | 14-JUN-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22620156.18 | 13526.80 | 30-JUL-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29720163.03 | 17703.48 | 11-AUG-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80448669.36 | 15252.58 | 06-SEP-16:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485579E+09 | 22942.54 | 27-OCT-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340444E+10 | 44722.94 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.744432E+10 | 45237.87 | 26-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22620156.18 | 13526.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.880795E+10 | 45237.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367932E+10 | 7938.47 | 01-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242019E+10 | 7935.31 | 16-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146029E+10 | 7872.18 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649885E+09 | 7717.81 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.285262E+09 | 4693.62 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54921540.97 | 3351.92 | 12-JUN-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9985033.63 | 3689.70 | 03-JUL-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10443681.64 | 4247.07 | 01-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122368E+09 | 4386.94 | 30-SEP-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.841684E+09 | 7738.78 | 31-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.224888E+10 | 7937.61 | 26-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339963E+10 | 7937.93 | 17-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9985033.63 | 3351.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.367932E+10 | 7938.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.408169E+10 | 7725.49 | 01-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288698E+10 | 7722.22 | 21-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182573E+10 | 7684.78 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.798645E+09 | 7517.00 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.319036E+09 | 4603.51 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 56786991.41 | 3249.60 | 13-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7131688.57 | 3357.69 | 26-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7798607.76 | 2813.63 | 16-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156215E+09 | 3050.28 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111337E+10 | 7553.80 | 31-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256075E+10 | 7724.58 | 26-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381186E+10 | 7724.92 | 17-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7131688.57 | 2813.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.408169E+10 | 7725.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130484E+10 | 2406.62 | 27-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.887656E+09 | 2406.69 | 15-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.577826E+09 | 2405.69 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282775E+09 | 2371.33 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115703E+09 | 2094.61 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32349807.95 | 875.70 | 08-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4063681.28 | 884.48 | 04-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6787135.73 | 988.54 | 20-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 55990802.66 | 1020.18 | 27-SEP-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350621E+09 | 2374.70 | 31-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.838702E+09 | 2406.47 | 09-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122157E+10 | 2407.46 | 16-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.567888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4063681.28 | 875.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130484E+10 | 2407.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142694E+10 | 2334.17 | 27-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103007E+10 | 2334.24 | 15-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693302E+09 | 2333.31 | 05-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336506E+09 | 2301.59 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120415E+09 | 2026.49 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29488878.24 | 919.86 | 12-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2446765.62 | 758.23 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4475534.28 | 938.30 | 01-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63106528.87 | 1445.17 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444817E+09 | 2311.06 | 31-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.936491E+09 | 2334.28 | 17-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134824E+10 | 2335.05 | 16-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2446765.62 | 758.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142694E+10 | 2335.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.388090E+10 | 12165.22 | 13-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223118E+10 | 12113.54 | 16-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113110E+10 | 11940.70 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.505793E+09 | 8765.65 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195301E+09 | 6480.42 | 30-MAY-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43691028.45 | 5597.56 | 14-JUN-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12431331.38 | 5911.26 | 09-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15830762.02 | 5841.91 | 17-AUG-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77786397.02 | 6139.87 | 03-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.495740E+09 | 10015.20 | 27-OCT-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206172E+10 | 12166.40 | 30-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354124E+10 | 12167.97 | 17-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12431331.38 | 5597.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388090E+10 | 12167.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.133833E+09 | 0.133833E+09 | 4714.27 | 06-JAN-06:10 | 4714.27 | 0.00 |
February | 0.00 | 0.00 | 0.217466E+10 | 0.217466E+10 | 86517.71 | 27-FEB-15:00 | 86517.71 | 0.01 |
March | 0.00 | 0.00 | 0.468935E+10 | 0.468935E+10 | 112800.18 | 18-MAR-16:00 | 112800.18 | 0.02 |
April | 0.00 | 0.00 | 0.302414E+11 | 0.301789E+11 | 206925.09 | 27-APR-17:15 | 191208.04 | 0.08 |
May | 0.00 | 0.00 | 0.593129E+11 | 0.586212E+11 | 219268.66 | 05-MAY-17:15 | 174253.83 | 0.23 |
June | 0.00 | 0.00 | 0.104681E+12 | 0.104181E+12 | 221971.77 | 28-JUN-18:10 | 206366.12 | 0.48 |
July | 0.00 | 0.00 | 0.174201E+12 | 0.167036E+12 | 260555.84 | 15-JUL-18:03 | 180909.79 | 0.69 |
August | 0.00 | 0.00 | 0.215343E+12 | 0.204413E+12 | 278209.08 | 10-AUG-18:10 | 237202.24 | 0.80 |
September | 0.00 | 0.00 | 0.866994E+11 | 0.834142E+11 | 219548.82 | 14-SEP-17:15 | 185559.04 | 0.49 |
October | 0.00 | 0.00 | 0.173006E+11 | 0.172760E+11 | 127248.04 | 04-OCT-15:27 | 127248.04 | 0.11 |
November | 0.00 | 0.00 | 0.397513E+10 | 0.397513E+10 | 111924.20 | 04-NOV-15:13 | 111924.20 | 0.04 |
December | 0.00 | 0.00 | 65945965.06 | 65945965.06 | 4706.19 | 22-DEC-06:10 | 4706.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.698818E+12 | 0.676159E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 65945965.06 | 65945965.06 | 4706.19 | 4706.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215343E+12 | 0.204413E+12 | 278209.08 | 237202.24 | 0.80 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.100185E+09 | 0.100185E+09 | 9453.00 | 27-FEB-16:15 | 9453.00 | 0.00 |
March | 0.00 | 0.00 | 0.213107E+09 | 0.213107E+09 | 12388.66 | 18-MAR-16:00 | 12388.66 | 0.01 |
April | 0.00 | 0.00 | 0.167058E+10 | 0.167058E+10 | 17999.92 | 27-APR-15:11 | 17999.92 | 0.04 |
May | 0.00 | 0.00 | 0.330427E+10 | 0.318830E+10 | 20677.56 | 05-MAY-18:04 | 16125.17 | 0.13 |
June | 0.00 | 0.00 | 0.589822E+10 | 0.589685E+10 | 17796.86 | 28-JUN-15:12 | 17796.86 | 0.31 |
July | 0.00 | 0.00 | 0.110614E+11 | 0.102725E+11 | 23708.15 | 15-JUL-18:03 | 15807.51 | 0.48 |
August | 0.00 | 0.00 | 0.145691E+11 | 0.133624E+11 | 23935.29 | 30-AUG-12:30 | 15345.45 | 0.59 |
September | 0.00 | 0.00 | 0.509662E+10 | 0.476262E+10 | 22616.73 | 14-SEP-12:40 | 15236.67 | 0.31 |
October | 0.00 | 0.00 | 0.823568E+09 | 0.823568E+09 | 14003.41 | 04-OCT-15:12 | 14003.41 | 0.05 |
November | 0.00 | 0.00 | 0.200368E+09 | 0.179941E+09 | 15533.96 | 04-NOV-13:00 | 12509.26 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.429374E+11 | 0.404701E+11 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145691E+11 | 0.133624E+11 | 23935.29 | 17999.92 | 0.59 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9116660.87 | 4985148.34 | 3660.90 | 26-JAN-19:04 | 2336.38 | 0.00 |
February | 0.00 | 0.00 | 41772626.10 | 22535752.30 | 11318.32 | 08-FEB-16:12 | 11318.32 | 0.02 |
March | 0.00 | 0.00 | 0.230730E+09 | 0.158864E+09 | 11726.53 | 01-MAR-16:11 | 11726.53 | 0.06 |
April | 0.00 | 0.00 | 0.970511E+09 | 0.567169E+09 | 11674.06 | 13-APR-18:01 | 11674.06 | 0.25 |
May | 0.00 | 0.00 | 0.205628E+10 | 0.110958E+10 | 11729.34 | 20-MAY-18:01 | 11729.34 | 0.50 |
June | 0.00 | 0.00 | 0.270842E+10 | 0.133764E+10 | 11671.02 | 12-JUN-15:12 | 9123.20 | 0.69 |
July | 0.00 | 0.00 | 0.480545E+10 | 0.256943E+10 | 11969.19 | 16-JUL-15:12 | 9222.55 | 0.84 |
August | 0.00 | 0.00 | 0.485684E+10 | 0.256311E+10 | 12055.54 | 26-AUG-15:11 | 9559.91 | 0.83 |
September | 0.00 | 0.00 | 0.284961E+10 | 0.137365E+10 | 11907.80 | 23-SEP-08:61 | 9273.55 | 0.67 |
October | 0.00 | 0.00 | 0.578002E+09 | 0.287544E+09 | 12079.14 | 01-OCT-15:12 | 9384.09 | 0.21 |
November | 0.00 | 0.00 | 70531863.41 | 27398582.47 | 11282.66 | 05-NOV-15:11 | 9175.84 | 0.03 |
December | 0.00 | 0.00 | 9838585.54 | 5266177.84 | 5539.34 | 05-DEC-16:11 | 4876.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.191871E+11 | 0.100272E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 9116660.87 | 4985148.34 | 3660.90 | 2336.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.485684E+10 | 0.256943E+10 | 12079.14 | 11729.34 | 0.84 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7033570.61 | 3547952.64 | 3539.24 | 03-JAN-19:04 | 2424.94 | 0.00 |
February | 0.00 | 0.00 | 10179305.77 | 5288870.66 | 8657.80 | 26-FEB-16:12 | 8657.80 | 0.01 |
March | 0.00 | 0.00 | 55177440.30 | 31268192.02 | 10204.20 | 01-MAR-16:11 | 10204.20 | 0.02 |
April | 0.00 | 0.00 | 0.473941E+09 | 0.249844E+09 | 11502.93 | 25-APR-17:42 | 11502.93 | 0.17 |
May | 0.00 | 0.00 | 0.106245E+10 | 0.463118E+09 | 11516.50 | 21-MAY-17:42 | 11516.50 | 0.37 |
June | 0.00 | 0.00 | 0.166957E+10 | 0.739791E+09 | 11018.52 | 12-JUN-18:01 | 8572.52 | 0.50 |
July | 0.00 | 0.00 | 0.310157E+10 | 0.157482E+10 | 11497.31 | 15-JUL-21:51 | 9206.86 | 0.59 |
August | 0.00 | 0.00 | 0.320575E+10 | 0.166665E+10 | 11013.63 | 30-AUG-08:52 | 7864.16 | 0.59 |
September | 0.00 | 0.00 | 0.126746E+10 | 0.464400E+09 | 10981.36 | 24-SEP-18:11 | 8457.24 | 0.43 |
October | 0.00 | 0.00 | 0.142120E+09 | 50584802.96 | 10524.52 | 01-OCT-08:62 | 8202.96 | 0.10 |
November | 0.00 | 0.00 | 16568471.10 | 6495312.38 | 10096.63 | 05-NOV-15:11 | 7991.97 | 0.01 |
December | 0.00 | 0.00 | 7478569.27 | 3851862.56 | 3131.89 | 14-DEC-19:04 | 2284.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110193E+11 | 0.525965E+10 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 7033570.61 | 3547952.64 | 3131.89 | 2284.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.320575E+10 | 0.166665E+10 | 11516.50 | 11516.50 | 0.59 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.213278E+10 | 0.207397E+10 | 17699.47 | 18-MAR-13:40 | 17699.47 | 0.01 |
April | 0.00 | 0.00 | 0.786739E+10 | 0.496185E+10 | 25341.33 | 27-APR-13:15 | 16019.98 | 0.25 |
May | 0.00 | 0.00 | 0.126529E+11 | 0.530545E+10 | 24733.78 | 04-MAY-13:15 | 14226.61 | 0.55 |
June | 0.00 | 0.00 | 0.157937E+11 | 0.486235E+10 | 19326.15 | 28-JUN-13:15 | 8947.38 | 0.77 |
July | 0.00 | 0.00 | 0.238912E+11 | 0.830467E+10 | 26351.43 | 31-JUL-13:15 | 14820.62 | 0.91 |
August | 0.00 | 0.00 | 0.281372E+11 | 0.109531E+11 | 32790.68 | 24-AUG-13:00 | 22553.63 | 0.91 |
September | 0.00 | 0.00 | 0.217610E+11 | 0.892307E+10 | 34086.96 | 14-SEP-13:15 | 24637.11 | 0.79 |
October | 0.00 | 0.00 | 0.995156E+10 | 0.523788E+10 | 32057.27 | 04-OCT-13:00 | 27006.42 | 0.34 |
November | 0.00 | 0.00 | 0.861836E+09 | 0.245341E+09 | 20679.02 | 04-NOV-13:25 | 9007.74 | 0.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123050E+12 | 0.508677E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.281372E+11 | 0.109531E+11 | 34086.96 | 27006.42 | 0.91 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.972929E+09 | 0.409968E+09 | 52003.39 | 12-JAN-09:02 | 52003.39 | 0.11 |
February | 0.00 | 0.00 | 0.247813E+10 | 0.100100E+10 | 61807.20 | 25-FEB-09:02 | 54972.41 | 0.19 |
March | 0.00 | 0.00 | 0.552612E+10 | 0.282918E+10 | 61306.40 | 18-MAR-20:42 | 61306.40 | 0.32 |
April | 0.00 | 0.00 | 0.116374E+11 | 0.639453E+10 | 62998.08 | 24-APR-18:01 | 62998.08 | 0.51 |
May | 0.00 | 0.00 | 0.189332E+11 | 0.109097E+11 | 65519.80 | 06-MAY-21:52 | 54570.43 | 0.56 |
June | 0.00 | 0.00 | 0.239658E+11 | 0.147287E+11 | 67013.87 | 12-JUN-18:01 | 55301.52 | 0.53 |
July | 0.00 | 0.00 | 0.289265E+11 | 0.184814E+11 | 68463.74 | 26-JUL-21:51 | 55229.56 | 0.50 |
August | 0.00 | 0.00 | 0.298681E+11 | 0.179277E+11 | 69156.72 | 26-AUG-21:52 | 53346.43 | 0.51 |
September | 0.00 | 0.00 | 0.200664E+11 | 0.102211E+11 | 66793.13 | 15-SEP-21:52 | 54265.26 | 0.52 |
October | 0.00 | 0.00 | 0.971979E+10 | 0.421202E+10 | 62750.09 | 04-OCT-21:12 | 62750.09 | 0.55 |
November | 0.00 | 0.00 | 0.446587E+10 | 0.167093E+10 | 62668.75 | 05-NOV-08:62 | 55210.03 | 0.31 |
December | 0.00 | 0.00 | 0.901958E+09 | 0.443020E+09 | 60931.26 | 03-DEC-09:02 | 60931.26 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.157462E+12 | 0.892292E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.901958E+09 | 0.409968E+09 | 52003.39 | 52003.39 | 0.10 | |
Maximum of Months | 0.00 | 0.00 | 0.298681E+11 | 0.184814E+11 | 69156.72 | 62998.08 | 0.56 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8634411.71 | 4730409.29 | 3280.64 | 03-JAN-19:04 | 2153.66 | 0.00 |
February | 0.00 | 0.00 | 29217694.47 | 15400191.04 | 7797.40 | 12-FEB-09:01 | 7797.40 | 0.02 |
March | 0.00 | 0.00 | 0.172210E+09 | 0.116562E+09 | 10200.70 | 25-MAR-15:11 | 10200.70 | 0.05 |
April | 0.00 | 0.00 | 0.942702E+09 | 0.509126E+09 | 10370.67 | 30-APR-08:62 | 8308.75 | 0.30 |
May | 0.00 | 0.00 | 0.172576E+10 | 0.866790E+09 | 10520.30 | 14-MAY-18:01 | 10520.30 | 0.49 |
June | 0.00 | 0.00 | 0.290533E+10 | 0.147124E+10 | 10451.62 | 12-JUN-15:12 | 8497.58 | 0.75 |
July | 0.00 | 0.00 | 0.412182E+10 | 0.209667E+10 | 10769.25 | 11-JUL-15:11 | 8628.04 | 0.86 |
August | 0.00 | 0.00 | 0.479693E+10 | 0.250353E+10 | 10844.24 | 30-AUG-08:62 | 7575.37 | 0.85 |
September | 0.00 | 0.00 | 0.253638E+10 | 0.121070E+10 | 10749.02 | 24-SEP-15:11 | 8227.07 | 0.63 |
October | 0.00 | 0.00 | 0.551745E+09 | 0.277194E+09 | 10541.25 | 01-OCT-15:12 | 7826.22 | 0.21 |
November | 0.00 | 0.00 | 59140700.91 | 20774775.71 | 10549.83 | 04-NOV-15:11 | 8801.33 | 0.03 |
December | 0.00 | 0.00 | 12514377.15 | 6352749.19 | 3713.65 | 02-DEC-09:02 | 3494.19 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.178624E+11 | 0.909908E+10 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 8634411.71 | 4730409.29 | 3280.64 | 2153.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.479693E+10 | 0.250353E+10 | 10844.24 | 10520.30 | 0.86 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6919177.14 | 3451096.01 | 3658.95 | 03-JAN-19:04 | 2793.52 | 0.00 |
February | 0.00 | 0.00 | 8831195.84 | 4804634.64 | 5287.47 | 25-FEB-09:02 | 2782.74 | 0.00 |
March | 0.00 | 0.00 | 34158710.77 | 21389683.34 | 8928.64 | 25-MAR-08:62 | 8928.64 | 0.01 |
April | 0.00 | 0.00 | 0.475507E+09 | 0.240878E+09 | 9507.11 | 30-APR-08:62 | 7557.06 | 0.19 |
May | 0.00 | 0.00 | 0.986737E+09 | 0.464692E+09 | 9621.63 | 06-MAY-08:51 | 8870.04 | 0.35 |
June | 0.00 | 0.00 | 0.196647E+10 | 0.990624E+09 | 9971.67 | 12-JUN-18:01 | 7818.82 | 0.56 |
July | 0.00 | 0.00 | 0.269080E+10 | 0.135003E+10 | 10381.14 | 31-JUL-08:51 | 9482.38 | 0.62 |
August | 0.00 | 0.00 | 0.317911E+10 | 0.163206E+10 | 10504.39 | 10-AUG-08:51 | 9605.36 | 0.61 |
September | 0.00 | 0.00 | 0.120404E+10 | 0.528709E+09 | 9747.74 | 23-SEP-08:61 | 8003.83 | 0.40 |
October | 0.00 | 0.00 | 0.167989E+09 | 75050738.46 | 9341.45 | 01-OCT-08:62 | 7152.14 | 0.08 |
November | 0.00 | 0.00 | 16223801.67 | 6250788.50 | 7748.56 | 05-NOV-08:62 | 4975.77 | 0.01 |
December | 0.00 | 0.00 | 7358677.53 | 3781304.77 | 3041.87 | 14-DEC-19:04 | 2356.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107442E+11 | 0.532173E+10 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 6919177.14 | 3451096.01 | 3041.87 | 2356.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.317911E+10 | 0.163206E+10 | 10504.39 | 9605.36 | 0.62 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1418694.64 | 712588.37 | 808.13 | 02-JAN-19:05 | 536.91 | 0.00 |
February | 0.00 | 0.00 | 10265027.85 | 5217639.98 | 2919.36 | 08-FEB-16:12 | 2919.36 | 0.01 |
March | 0.00 | 0.00 | 60011746.14 | 42961368.57 | 3049.48 | 01-MAR-16:11 | 3049.48 | 0.05 |
April | 0.00 | 0.00 | 0.265042E+09 | 0.166794E+09 | 3123.03 | 30-APR-08:62 | 2245.36 | 0.22 |
May | 0.00 | 0.00 | 0.567999E+09 | 0.336902E+09 | 3050.08 | 20-MAY-18:01 | 3050.08 | 0.46 |
June | 0.00 | 0.00 | 0.734647E+09 | 0.397152E+09 | 3056.36 | 12-JUN-15:12 | 2402.58 | 0.66 |
July | 0.00 | 0.00 | 0.127967E+10 | 0.734795E+09 | 3125.06 | 16-JUL-15:12 | 2380.57 | 0.84 |
August | 0.00 | 0.00 | 0.124791E+10 | 0.703856E+09 | 3192.47 | 20-AUG-08:62 | 2174.73 | 0.80 |
September | 0.00 | 0.00 | 0.714783E+09 | 0.378388E+09 | 3252.80 | 23-SEP-08:61 | 2211.79 | 0.59 |
October | 0.00 | 0.00 | 0.135582E+09 | 73845902.93 | 3147.23 | 01-OCT-15:12 | 2436.01 | 0.16 |
November | 0.00 | 0.00 | 18261151.72 | 7716265.20 | 2988.36 | 05-NOV-15:11 | 2376.75 | 0.02 |
December | 0.00 | 0.00 | 1620101.13 | 873526.73 | 902.12 | 28-DEC-16:15 | 471.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.503721E+10 | 0.284921E+10 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 1418694.64 | 712588.37 | 808.13 | 471.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127967E+10 | 0.734795E+09 | 3252.80 | 3050.08 | 0.84 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 900553.73 | 450150.41 | 841.51 | 27-JAN-19:05 | 504.73 | 0.00 |
February | 0.00 | 0.00 | 2697755.04 | 1385746.49 | 1938.91 | 26-FEB-16:12 | 1706.91 | 0.00 |
March | 0.00 | 0.00 | 13757941.16 | 7773386.45 | 2628.67 | 01-MAR-16:11 | 2628.67 | 0.02 |
April | 0.00 | 0.00 | 0.129780E+09 | 75280598.83 | 3021.95 | 25-APR-17:42 | 3021.95 | 0.14 |
May | 0.00 | 0.00 | 0.295792E+09 | 0.142642E+09 | 3060.94 | 21-MAY-17:42 | 3060.94 | 0.34 |
June | 0.00 | 0.00 | 0.462660E+09 | 0.223476E+09 | 2879.62 | 12-JUN-18:01 | 2213.77 | 0.49 |
July | 0.00 | 0.00 | 0.860628E+09 | 0.463563E+09 | 3115.33 | 15-JUL-21:51 | 2466.59 | 0.61 |
August | 0.00 | 0.00 | 0.836275E+09 | 0.465363E+09 | 2912.36 | 30-AUG-08:52 | 1943.58 | 0.59 |
September | 0.00 | 0.00 | 0.300318E+09 | 0.118864E+09 | 2941.54 | 23-SEP-08:61 | 1957.38 | 0.37 |
October | 0.00 | 0.00 | 27494511.59 | 10747837.88 | 2829.54 | 01-OCT-08:62 | 1966.11 | 0.06 |
November | 0.00 | 0.00 | 4618432.42 | 1978519.30 | 2641.99 | 05-NOV-15:11 | 2031.31 | 0.00 |
December | 0.00 | 0.00 | 1008267.23 | 466523.90 | 843.52 | 28-DEC-09:05 | 392.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.293593E+10 | 0.151199E+10 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 900553.73 | 450150.41 | 841.51 | 392.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.860628E+09 | 0.465363E+09 | 3115.33 | 3060.94 | 0.61 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 71414583.27 | 34353913.18 | 12876.40 | 20-JAN-16:11 | 12876.40 | 0.02 |
February | 0.00 | 0.00 | 0.595951E+09 | 0.315976E+09 | 17411.61 | 12-FEB-16:11 | 17411.61 | 0.15 |
March | 0.00 | 0.00 | 0.132438E+10 | 0.883219E+09 | 17415.21 | 26-MAR-15:11 | 17415.21 | 0.20 |
April | 0.00 | 0.00 | 0.250532E+10 | 0.133427E+10 | 17169.57 | 30-APR-15:12 | 13787.58 | 0.47 |
May | 0.00 | 0.00 | 0.358171E+10 | 0.176233E+10 | 17412.15 | 14-MAY-18:01 | 17412.15 | 0.63 |
June | 0.00 | 0.00 | 0.446082E+10 | 0.205871E+10 | 17453.68 | 12-JUN-18:01 | 14508.40 | 0.78 |
July | 0.00 | 0.00 | 0.669178E+10 | 0.322885E+10 | 17845.21 | 16-JUL-15:12 | 13341.43 | 0.87 |
August | 0.00 | 0.00 | 0.759347E+10 | 0.388831E+10 | 17706.20 | 16-AUG-15:11 | 14228.16 | 0.86 |
September | 0.00 | 0.00 | 0.569754E+10 | 0.295779E+10 | 17474.98 | 23-SEP-08:61 | 14601.34 | 0.76 |
October | 0.00 | 0.00 | 0.247858E+10 | 0.123640E+10 | 17414.27 | 04-OCT-18:01 | 17414.27 | 0.48 |
November | 0.00 | 0.00 | 0.522024E+09 | 0.206826E+09 | 17059.14 | 05-NOV-15:11 | 14908.59 | 0.13 |
December | 0.00 | 0.00 | 0.276416E+09 | 0.178501E+09 | 16216.74 | 03-DEC-19:02 | 16216.74 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.357994E+11 | 0.180855E+11 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 71414583.27 | 34353913.18 | 12876.40 | 12876.40 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.759347E+10 | 0.388831E+10 | 17845.21 | 17415.21 | 0.87 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2.23 | 1444.15 | 07-JAN-13:10 | 46843.26 | 190252.74 | 16-JAN-16:13 |
February | 14.29 | 1618.04 | 24-FEB-00:10 | 37407.37 | 186238.24 | 18-FEB-16:11 |
March | 25.03 | 1572.40 | 28-MAR-21:05 | 24109.00 | 162764.18 | 05-MAR-16:11 |
April | 20.29 | 1568.56 | 22-APR-22:20 | 11935.01 | 111050.19 | 18-APR-08:62 |
May | 15.42 | 3075.05 | 29-MAY-08:04 | 4215.94 | 83173.72 | 18-MAY-08:62 |
June | 14.20 | 2916.64 | 16-JUN-08:04 | 487.00 | 35760.12 | 06-JUN-15:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 144.87 | 32041.78 | 14-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 151.14 | 31017.15 | 18-AUG-08:04 |
September | 30.98 | 2851.84 | 07-SEP-08:04 | 888.32 | 33826.36 | 26-SEP-15:17 |
October | 69.82 | 2768.83 | 08-OCT-08:20 | 7177.09 | 77906.16 | 31-OCT-15:13 |
November | 28.93 | 1433.45 | 07-NOV-21:00 | 30727.49 | 161924.16 | 23-NOV-16:11 |
December | 0.09 | 91.44 | 03-DEC-11:03 | 48556.93 | 181592.94 | 25-DEC-16:13 |
Annual Sum or Average | 18.42 | 17632.02 | ||||
Minimum of Months | 0.00 | 0.00 | 144.87 | 31017.15 | ||
Maximum of Months | 69.82 | 3075.05 | 48556.93 | 190252.74 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1047.35 | 39928.99 | 22-JAN-09:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3157.37 | 110695.41 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 6589.54 | 163030.37 | 18-MAR-15:11 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 23959.74 | 355796.41 | 27-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 41362.87 | 328132.18 | 05-MAY-15:13 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 66445.42 | 369785.47 | 28-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 100605.47 | 417242.44 | 27-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 120075.48 | 438755.35 | 10-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 59732.30 | 361608.35 | 14-SEP-15:13 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17417.67 | 201107.65 | 04-OCT-15:15 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4787.97 | 182938.52 | 04-NOV-15:13 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 982.19 | 36875.21 | 03-DEC-19:02 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 37442.92 | 0.00 | ||||
Minimum of Months | 982.19 | 36875.21 | 0.00 | 0.00 | ||
Maximum of Months | 120075.48 | 438755.35 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 27483.38 | 55991.03 | 31-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 27669.34 | 56121.67 | 07-FEB-07:53 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 27392.37 | 55899.70 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26666.41 | 54670.26 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 25727.44 | 53007.79 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24820.47 | 50932.33 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24154.44 | 49180.25 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23979.46 | 48465.85 | 29-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24273.54 | 49530.05 | 29-SEP-06:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24986.97 | 51389.33 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25930.62 | 53439.08 | 30-NOV-07:53 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 26841.29 | 55018.31 | 29-DEC-07:55 |
Annual Sum or Average | 0.00 | 25816.44 | ||||
Minimum of Months | 0.00 | 0.00 | 23979.46 | 48465.85 | ||
Maximum of Months | 0.00 | 0.00 | 27669.34 | 56121.67 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261333E+10 | 0.68 | 1299.30 | 01-JAN-00:05 | 0.89 |
February | 0.236042E+10 | 0.68 | 1299.30 | 19-FEB-16:25 | 0.89 |
March | 0.261333E+10 | 0.68 | 1299.30 | 08-MAR-19:05 | 0.89 |
April | 0.252903E+10 | 0.68 | 1299.30 | 01-APR-15:14 | 0.89 |
May | 0.261333E+10 | 0.68 | 1299.30 | 04-MAY-21:56 | 0.89 |
June | 0.252903E+10 | 0.68 | 1299.30 | 27-JUN-22:20 | 0.89 |
July | 0.261333E+10 | 0.68 | 1299.30 | 06-JUL-22:20 | 0.89 |
August | 0.261333E+10 | 0.67 | 1299.30 | 10-AUG-15:40 | 0.88 |
September | 0.252903E+10 | 0.68 | 1299.30 | 06-SEP-08:05 | 0.88 |
October | 0.261333E+10 | 0.68 | 1299.30 | 06-OCT-08:04 | 0.88 |
November | 0.252903E+10 | 0.68 | 1299.30 | 01-NOV-00:50 | 0.89 |
December | 0.261333E+10 | 0.68 | 1299.30 | 01-DEC-00:10 | 0.89 |
Annual Sum or Average | 0.307698E+11 | 0.68 | |||
Minimum of Months | 0.236042E+10 | 0.67 | 1299.30 | 0.88 | |
Maximum of Months | 0.261333E+10 | 0.68 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.419583E+11 | 0.97 | 22036.71 | 12-JAN-20:10 | 1.19 |
February | 0.381147E+11 | 0.97 | 22031.53 | 06-FEB-20:10 | 1.19 |
March | 0.425581E+11 | 0.98 | 22034.40 | 09-MAR-20:20 | 1.18 |
April | 0.414423E+11 | 0.98 | 22199.57 | 27-APR-20:20 | 1.19 |
May | 0.431205E+11 | 0.98 | 22245.91 | 15-MAY-20:10 | 1.19 |
June | 0.421016E+11 | 0.98 | 22588.73 | 28-JUN-20:30 | 1.20 |
July | 0.438244E+11 | 0.99 | 23839.55 | 24-JUL-21:30 | 1.24 |
August | 0.440958E+11 | 0.99 | 25041.48 | 10-AUG-21:20 | 1.28 |
September | 0.419597E+11 | 0.98 | 22459.55 | 14-SEP-20:10 | 1.20 |
October | 0.427776E+11 | 0.98 | 22169.35 | 04-OCT-19:30 | 1.19 |
November | 0.409899E+11 | 0.97 | 22036.71 | 13-NOV-20:10 | 1.19 |
December | 0.420228E+11 | 0.97 | 22036.71 | 04-DEC-20:10 | 1.19 |
Annual Sum or Average | 0.504966E+12 | 0.98 | |||
Minimum of Months | 0.381147E+11 | 0.97 | 22031.53 | 1.18 | |
Maximum of Months | 0.440958E+11 | 0.99 | 25041.48 | 1.28 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:05 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:05 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:10 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:05 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | -0.0 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:10 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.195669E+09 | 0.41 | 575.13 | 01-JAN-09:02 | 0.58 |
February | 0.141520E+09 | 0.40 | 575.13 | 01-FEB-09:02 | 0.58 |
March | 0.115956E+09 | 0.40 | 575.13 | 01-MAR-16:11 | 0.58 |
April | 0.104495E+09 | 0.42 | 575.13 | 01-APR-15:11 | 0.58 |
May | 0.124332E+09 | 0.44 | 575.13 | 02-MAY-15:11 | 0.58 |
June | 0.136621E+09 | 0.45 | 575.13 | 01-JUN-08:62 | 0.58 |
July | 0.217594E+09 | 0.49 | 575.13 | 01-JUL-08:62 | 0.58 |
August | 0.213337E+09 | 0.49 | 575.13 | 01-AUG-08:61 | 0.58 |
September | 0.137981E+09 | 0.46 | 575.13 | 01-SEP-15:11 | 0.58 |
October | 97107243.29 | 0.41 | 575.13 | 01-OCT-08:62 | 0.58 |
November | 0.140705E+09 | 0.40 | 575.13 | 04-NOV-15:11 | 0.58 |
December | 0.185810E+09 | 0.42 | 575.13 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.181113E+10 | 0.43 | |||
Minimum of Months | 97107243.29 | 0.40 | 575.13 | 0.58 | |
Maximum of Months | 0.217594E+09 | 0.49 | 575.13 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199153E+09 | 0.43 | 526.58 | 01-JAN-09:02 | 0.58 |
February | 0.149811E+09 | 0.41 | 526.58 | 01-FEB-09:02 | 0.58 |
March | 0.117493E+09 | 0.39 | 526.58 | 01-MAR-09:02 | 0.58 |
April | 86192311.31 | 0.38 | 526.58 | 01-APR-15:11 | 0.58 |
May | 76321696.22 | 0.36 | 526.58 | 02-MAY-19:12 | 0.58 |
June | 84442574.75 | 0.33 | 526.58 | 01-JUN-08:62 | 0.58 |
July | 0.136788E+09 | 0.34 | 526.58 | 01-JUL-08:62 | 0.58 |
August | 0.140421E+09 | 0.34 | 526.58 | 01-AUG-08:61 | 0.58 |
September | 68583597.30 | 0.33 | 526.58 | 01-SEP-21:42 | 0.58 |
October | 86554169.13 | 0.38 | 526.58 | 01-OCT-08:62 | 0.58 |
November | 0.142953E+09 | 0.40 | 526.58 | 05-NOV-15:11 | 0.58 |
December | 0.190351E+09 | 0.43 | 526.58 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.147906E+10 | 0.38 | |||
Minimum of Months | 68583597.30 | 0.33 | 526.58 | 0.58 | |
Maximum of Months | 0.199153E+09 | 0.43 | 526.58 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.103084E+09 | 0.10 | 624.22 | 18-MAR-13:40 | 0.58 |
April | 0.343441E+09 | 0.27 | 854.76 | 27-APR-13:15 | 0.58 |
May | 0.538055E+09 | 0.37 | 805.17 | 04-MAY-13:30 | 0.58 |
June | 0.653593E+09 | 0.45 | 646.27 | 28-JUN-13:15 | 0.58 |
July | 0.902305E+09 | 0.53 | 823.12 | 31-JUL-13:15 | 0.58 |
August | 0.100855E+10 | 0.53 | 1001.86 | 24-AUG-13:05 | 0.58 |
September | 0.801907E+09 | 0.46 | 1044.39 | 14-SEP-13:30 | 0.58 |
October | 0.409528E+09 | 0.25 | 1140.17 | 04-OCT-13:20 | 0.58 |
November | 35204018.99 | 0.03 | 652.88 | 04-NOV-13:40 | 0.58 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.479567E+10 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100855E+10 | 0.53 | 1140.17 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.621051E+09 | 0.40 | 3173.88 | 01-JAN-09:02 | 0.58 |
February | 0.519116E+09 | 0.39 | 3173.88 | 01-FEB-09:02 | 0.58 |
March | 0.455200E+09 | 0.39 | 3173.88 | 01-MAR-09:02 | 0.58 |
April | 0.613775E+09 | 0.37 | 3173.88 | 01-APR-08:62 | 0.58 |
May | 0.869412E+09 | 0.34 | 3173.88 | 01-MAY-08:62 | 0.58 |
June | 0.103940E+10 | 0.31 | 3173.88 | 01-JUN-08:62 | 0.58 |
July | 0.123258E+10 | 0.29 | 3173.88 | 01-JUL-08:62 | 0.58 |
August | 0.121755E+10 | 0.30 | 3173.88 | 01-AUG-08:61 | 0.58 |
September | 0.819757E+09 | 0.31 | 3173.88 | 01-SEP-08:53 | 0.58 |
October | 0.521242E+09 | 0.38 | 3173.88 | 01-OCT-08:62 | 0.58 |
November | 0.473630E+09 | 0.39 | 3173.88 | 01-NOV-08:62 | 0.58 |
December | 0.556897E+09 | 0.40 | 3173.88 | 01-DEC-16:11 | 0.58 |
Annual Sum or Average | 0.893962E+10 | 0.36 | |||
Minimum of Months | 0.455200E+09 | 0.29 | 3173.88 | 0.58 | |
Maximum of Months | 0.123258E+10 | 0.40 | 3173.88 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182210E+09 | 0.41 | 515.34 | 01-JAN-09:02 | 0.58 |
February | 0.130509E+09 | 0.40 | 515.34 | 02-FEB-09:02 | 0.58 |
March | 0.103008E+09 | 0.40 | 515.34 | 01-MAR-09:02 | 0.58 |
April | 94590307.74 | 0.42 | 515.34 | 01-APR-08:62 | 0.58 |
May | 0.107349E+09 | 0.45 | 515.34 | 01-MAY-18:02 | 0.58 |
June | 0.139901E+09 | 0.48 | 515.34 | 01-JUN-08:62 | 0.58 |
July | 0.181734E+09 | 0.50 | 515.34 | 01-JUL-08:62 | 0.58 |
August | 0.205023E+09 | 0.50 | 515.34 | 01-AUG-08:61 | 0.58 |
September | 0.124435E+09 | 0.46 | 515.34 | 01-SEP-15:11 | 0.58 |
October | 90426740.83 | 0.41 | 515.34 | 01-OCT-08:62 | 0.58 |
November | 0.129652E+09 | 0.40 | 515.34 | 04-NOV-15:11 | 0.58 |
December | 0.172396E+09 | 0.42 | 515.34 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.166123E+10 | 0.44 | |||
Minimum of Months | 90426740.83 | 0.40 | 515.34 | 0.58 | |
Maximum of Months | 0.205023E+09 | 0.50 | 515.34 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.187102E+09 | 0.44 | 471.79 | 01-JAN-09:02 | 0.58 |
February | 0.139568E+09 | 0.41 | 471.79 | 01-FEB-09:02 | 0.58 |
March | 0.106634E+09 | 0.39 | 471.79 | 02-MAR-09:02 | 0.58 |
April | 76542054.32 | 0.38 | 471.79 | 01-APR-08:62 | 0.58 |
May | 73475744.71 | 0.36 | 471.79 | 01-MAY-18:02 | 0.58 |
June | 95379557.41 | 0.37 | 471.79 | 01-JUN-08:62 | 0.58 |
July | 0.120033E+09 | 0.36 | 471.79 | 01-JUL-08:62 | 0.58 |
August | 0.136803E+09 | 0.36 | 471.79 | 01-AUG-08:61 | 0.58 |
September | 68083833.40 | 0.34 | 471.79 | 01-SEP-21:42 | 0.58 |
October | 82418087.63 | 0.38 | 471.79 | 01-OCT-08:62 | 0.58 |
November | 0.132437E+09 | 0.40 | 471.79 | 07-NOV-16:12 | 0.58 |
December | 0.177299E+09 | 0.44 | 471.79 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.139578E+10 | 0.39 | |||
Minimum of Months | 68083833.40 | 0.34 | 471.79 | 0.58 | |
Maximum of Months | 0.187102E+09 | 0.44 | 471.79 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 60453346.64 | 0.46 | 149.60 | 01-JAN-09:02 | 0.58 |
February | 44118823.90 | 0.42 | 149.60 | 01-FEB-09:02 | 0.58 |
March | 36172852.37 | 0.40 | 149.60 | 01-MAR-09:02 | 0.58 |
April | 31721439.50 | 0.42 | 149.60 | 01-APR-15:11 | 0.58 |
May | 36988698.66 | 0.45 | 149.60 | 02-MAY-15:11 | 0.58 |
June | 38361593.15 | 0.47 | 149.60 | 01-JUN-08:62 | 0.58 |
July | 59143548.29 | 0.50 | 149.60 | 01-JUL-08:62 | 0.58 |
August | 56550524.17 | 0.49 | 149.60 | 01-AUG-08:61 | 0.58 |
September | 37188215.13 | 0.46 | 149.60 | 01-SEP-15:11 | 0.58 |
October | 30171132.41 | 0.41 | 149.60 | 01-OCT-08:62 | 0.58 |
November | 44033493.99 | 0.42 | 149.60 | 04-NOV-15:11 | 0.58 |
December | 57594714.05 | 0.45 | 149.60 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.532498E+09 | 0.45 | |||
Minimum of Months | 30171132.41 | 0.40 | 149.60 | 0.58 | |
Maximum of Months | 60453346.64 | 0.50 | 149.60 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 61465733.54 | 0.50 | 136.03 | 01-JAN-09:02 | 0.58 |
February | 46128949.50 | 0.44 | 136.03 | 01-FEB-09:02 | 0.58 |
March | 36156691.68 | 0.39 | 136.03 | 01-MAR-09:02 | 0.58 |
April | 26207189.47 | 0.38 | 136.03 | 01-APR-15:11 | 0.58 |
May | 22975929.63 | 0.37 | 136.03 | 02-MAY-19:12 | 0.58 |
June | 24152193.58 | 0.35 | 136.03 | 01-JUN-08:62 | 0.58 |
July | 38978615.03 | 0.36 | 136.03 | 01-JUL-08:62 | 0.58 |
August | 38277145.09 | 0.36 | 136.03 | 01-AUG-08:61 | 0.58 |
September | 18377521.78 | 0.34 | 136.03 | 01-SEP-21:42 | 0.58 |
October | 27714521.90 | 0.38 | 136.03 | 01-OCT-08:62 | 0.58 |
November | 44556472.09 | 0.43 | 136.03 | 02-NOV-08:62 | 0.58 |
December | 58453443.37 | 0.48 | 136.03 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.443444E+09 | 0.40 | |||
Minimum of Months | 18377521.78 | 0.34 | 136.03 | 0.58 | |
Maximum of Months | 61465733.54 | 0.50 | 136.03 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.230495E+09 | 0.41 | 850.78 | 01-JAN-16:11 | 0.58 |
February | 0.171801E+09 | 0.42 | 850.78 | 01-FEB-16:12 | 0.58 |
March | 0.157578E+09 | 0.43 | 850.78 | 01-MAR-16:11 | 0.58 |
April | 0.168923E+09 | 0.45 | 850.78 | 01-APR-15:11 | 0.58 |
May | 0.190712E+09 | 0.47 | 850.78 | 01-MAY-15:12 | 0.58 |
June | 0.211782E+09 | 0.48 | 850.78 | 01-JUN-08:62 | 0.58 |
July | 0.292606E+09 | 0.51 | 850.78 | 01-JUL-08:62 | 0.58 |
August | 0.321977E+09 | 0.50 | 850.78 | 01-AUG-08:61 | 0.58 |
September | 0.254126E+09 | 0.48 | 850.78 | 01-SEP-15:11 | 0.58 |
October | 0.165523E+09 | 0.45 | 850.78 | 01-OCT-08:62 | 0.58 |
November | 0.164520E+09 | 0.41 | 850.78 | 02-NOV-15:12 | 0.58 |
December | 0.223742E+09 | 0.42 | 850.78 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.255379E+10 | 0.45 | |||
Minimum of Months | 0.157578E+09 | 0.41 | 850.78 | 0.58 | |
Maximum of Months | 0.321977E+09 | 0.51 | 850.78 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.141781E+10 | 0.128879E+10 | 1315.74 | 16-JAN-16:13 | 1196.01 | 1196.01 | 38.10 | 2.08 |
February | 0.103059E+10 | 0.936810E+09 | 1250.79 | 18-FEB-16:11 | 1136.96 | 1136.96 | 36.60 | 1.90 |
March | 0.735734E+09 | 0.668782E+09 | 1067.35 | 05-MAR-16:11 | 970.22 | 970.22 | 33.83 | 1.49 |
April | 0.355562E+09 | 0.323206E+09 | 919.79 | 19-APR-04:10 | 836.09 | 836.09 | 41.97 | 1.21 |
May | 0.139685E+09 | 0.126973E+09 | 626.31 | 18-MAY-08:62 | 569.31 | 569.31 | 33.40 | 0.75 |
June | 24013152.16 | 21827955.32 | 387.64 | 16-JUN-08:04 | 352.36 | 352.36 | 50.51 | 0.43 |
July | 4599569.61 | 4181008.77 | 328.45 | 26-JUL-08:05 | 298.56 | 298.56 | 44.91 | 0.36 |
August | 5459638.65 | 4962811.53 | 363.15 | 18-AUG-08:04 | 330.10 | 330.10 | 41.60 | 0.40 |
September | 46496078.63 | 42264935.48 | 388.38 | 27-SEP-04:00 | 353.03 | 353.03 | 41.58 | 0.43 |
October | 0.300888E+09 | 0.273507E+09 | 588.15 | 31-OCT-15:13 | 534.62 | 534.62 | 33.18 | 0.69 |
November | 0.910742E+09 | 0.827864E+09 | 1125.00 | 13-NOV-09:03 | 1022.63 | 1022.63 | 37.89 | 1.61 |
December | 0.140186E+10 | 0.127429E+10 | 1261.52 | 25-DEC-16:13 | 1146.72 | 1146.72 | 37.50 | 1.93 |
Annual Sum or Average | 0.637344E+10 | 0.579346E+10 | ||||||
Minimum of Months | 4599569.61 | 4181008.77 | 328.45 | 298.56 | 298.56 | 33.18 | 0.36 | |
Maximum of Months | 0.141781E+10 | 0.128879E+10 | 1315.74 | 1196.01 | 1196.01 | 50.51 | 2.08 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 48105649.70 | 43728035.58 | 797.00 | 11-JAN-19:03 | 724.48 | 724.48 | 6.72 | 1.75 |
February | 0.144657E+09 | 0.131493E+09 | 1561.93 | 27-FEB-16:35 | 1419.79 | 1419.79 | 6.72 | 4.22 |
March | 0.390422E+09 | 0.354894E+09 | 1501.94 | 18-MAR-15:13 | 1365.26 | 1365.26 | 6.72 | 3.97 |
April | 0.103646E+10 | 0.942143E+09 | 2288.75 | 01-APR-15:25 | 2080.48 | 2080.48 | 6.72 | 10.12 |
May | 0.175977E+10 | 0.159963E+10 | 2220.48 | 04-MAY-15:11 | 2018.42 | 2018.42 | 6.72 | 8.97 |
June | 0.253328E+10 | 0.230275E+10 | 2290.91 | 28-JUN-18:03 | 2082.44 | 2082.44 | 6.72 | 10.16 |
July | 0.332494E+10 | 0.302237E+10 | 2339.79 | 31-JUL-18:03 | 2126.87 | 2126.87 | 6.72 | 11.17 |
August | 0.355782E+10 | 0.323406E+10 | 2370.19 | 10-AUG-18:03 | 2154.50 | 2154.50 | 6.72 | 11.84 |
September | 0.222939E+10 | 0.202652E+10 | 2244.86 | 14-SEP-15:23 | 2040.58 | 2040.58 | 6.72 | 9.34 |
October | 0.920247E+09 | 0.836505E+09 | 1840.96 | 08-OCT-16:00 | 1673.43 | 1673.43 | 6.72 | 5.60 |
November | 0.240944E+09 | 0.219018E+09 | 1742.31 | 04-NOV-15:13 | 1583.76 | 1583.76 | 6.72 | 5.06 |
December | 52255768.80 | 47500493.84 | 928.32 | 02-DEC-09:02 | 843.84 | 843.84 | 6.72 | 2.10 |
Annual Sum or Average | 0.162383E+11 | 0.147606E+11 | ||||||
Minimum of Months | 48105649.70 | 43728035.58 | 797.00 | 724.48 | 724.48 | 6.72 | 1.75 | |
Maximum of Months | 0.355782E+10 | 0.323406E+10 | 2370.19 | 2154.50 | 2154.50 | 6.72 | 11.84 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.170354E+10 | 0.154851E+10 | 2049.31 | 01-JAN-09:02 | 1862.83 | 1862.83 | 7.01 | 18.31 |
February | 0.226270E+10 | 0.205679E+10 | 2049.31 | 01-FEB-06:10 | 1862.83 | 1862.83 | 6.75 | 18.31 |
March | 0.312805E+10 | 0.284340E+10 | 2049.31 | 01-MAR-00:05 | 1862.83 | 1862.83 | 6.76 | 18.31 |
April | 0.441264E+10 | 0.401109E+10 | 2049.31 | 01-APR-06:10 | 1862.83 | 1862.83 | 6.74 | 18.31 |
May | 0.523179E+10 | 0.475570E+10 | 2049.31 | 01-MAY-00:10 | 1862.83 | 1862.83 | 6.83 | 18.31 |
June | 0.524112E+10 | 0.476418E+10 | 2049.31 | 01-JUN-00:10 | 1862.83 | 1862.83 | 7.08 | 18.31 |
July | 0.548888E+10 | 0.498939E+10 | 2049.31 | 01-JUL-00:10 | 1862.83 | 1862.83 | 7.32 | 18.31 |
August | 0.548888E+10 | 0.498939E+10 | 2049.31 | 01-AUG-00:10 | 1862.83 | 1862.83 | 7.89 | 18.31 |
September | 0.515013E+10 | 0.468147E+10 | 2049.31 | 01-SEP-00:10 | 1862.83 | 1862.83 | 7.52 | 18.31 |
October | 0.433936E+10 | 0.394448E+10 | 2049.31 | 01-OCT-00:10 | 1862.83 | 1862.83 | 6.87 | 18.31 |
November | 0.218278E+10 | 0.198415E+10 | 2049.31 | 01-NOV-00:10 | 1862.83 | 1862.83 | 6.73 | 18.31 |
December | 0.142867E+10 | 0.129866E+10 | 2049.31 | 01-DEC-07:05 | 1862.83 | 1862.83 | 6.74 | 18.31 |
Annual Sum or Average | 0.460585E+11 | 0.418672E+11 | ||||||
Minimum of Months | 0.142867E+10 | 0.129866E+10 | 2049.31 | 1862.83 | 1862.83 | 6.73 | 18.31 | |
Maximum of Months | 0.548888E+10 | 0.498939E+10 | 2049.31 | 1862.83 | 1862.83 | 7.89 | 18.31 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.37 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 49.23 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 48.66 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.87 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 52.13 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.09 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.59 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.58 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.76 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.76 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.31 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 49.59 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.37 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.76 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2.23 | 1444.15 | 07-JAN-13:10 | 51.87 | 51.87 | 46843.26 | 190252.74 | 16-JAN-16:13 |
February | 14.29 | 1618.04 | 24-FEB-00:10 | 50.74 | 50.74 | 37407.37 | 186238.24 | 18-FEB-16:11 |
March | 25.03 | 1572.40 | 28-MAR-21:05 | 51.39 | 51.39 | 24109.00 | 162764.18 | 05-MAR-16:11 |
April | 20.29 | 1568.56 | 22-APR-22:20 | 51.54 | 51.54 | 11935.01 | 111050.19 | 18-APR-08:62 |
May | 15.42 | 3075.05 | 29-MAY-08:04 | 50.72 | 50.72 | 4215.94 | 83173.72 | 18-MAY-08:62 |
June | 14.20 | 2916.64 | 16-JUN-08:04 | 50.51 | 50.51 | 487.00 | 35760.12 | 06-JUN-15:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 37.60 | 37.60 | 144.87 | 32041.78 | 14-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 44.72 | 44.72 | 151.14 | 31017.15 | 18-AUG-08:04 |
September | 30.98 | 2851.84 | 07-SEP-08:04 | 50.53 | 50.53 | 888.32 | 33826.36 | 26-SEP-15:17 |
October | 69.82 | 2768.83 | 08-OCT-08:20 | 51.69 | 51.69 | 7177.09 | 77906.16 | 31-OCT-15:13 |
November | 28.93 | 1433.45 | 07-NOV-21:00 | 51.61 | 51.61 | 30727.49 | 161924.16 | 23-NOV-16:11 |
December | 0.09 | 91.44 | 03-DEC-11:03 | 50.94 | 50.94 | 48556.93 | 181592.94 | 25-DEC-16:13 |
Annual Sum or Average | 18.42 | 17632.02 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.60 | 37.60 | 144.87 | 31017.15 | ||
Maximum of Months | 69.82 | 3075.05 | 51.87 | 51.87 | 48556.93 | 190252.74 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1047.35 | 39928.99 | 22-JAN-09:01 | 7.22 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3157.37 | 110695.41 | 27-FEB-16:00 | 8.14 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 6589.54 | 163030.37 | 18-MAR-15:11 | 8.82 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 23959.74 | 355796.41 | 27-APR-18:03 | 11.34 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 41362.87 | 328132.18 | 05-MAY-15:13 | 10.98 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 66445.42 | 369785.47 | 28-JUN-18:03 | 11.52 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 100605.47 | 417242.44 | 27-JUL-18:03 | 12.14 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 120075.48 | 438755.35 | 10-AUG-18:03 | 12.42 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 59732.30 | 361608.35 | 14-SEP-15:13 | 11.41 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17417.67 | 201107.65 | 04-OCT-15:15 | 9.32 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4787.97 | 182938.52 | 04-NOV-15:13 | 9.08 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 982.19 | 36875.21 | 03-DEC-19:02 | 7.18 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 37442.92 | 0.00 | ||||||
Minimum of Months | 982.19 | 36875.21 | 7.18 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 120075.48 | 438755.35 | 12.42 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.37 | 59.70 | 27483.38 | 55991.03 | 31-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.23 | 59.72 | 27669.34 | 56121.67 | 07-FEB-07:53 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 48.66 | 58.30 | 27392.37 | 55899.70 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.87 | 59.16 | 26666.41 | 54670.26 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.13 | 59.18 | 25727.44 | 53007.79 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.09 | 58.62 | 24820.47 | 50932.33 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.59 | 59.19 | 24154.44 | 49180.25 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.58 | 58.79 | 23979.46 | 48465.85 | 29-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.76 | 59.18 | 24273.54 | 49530.05 | 29-SEP-06:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.76 | 59.09 | 24986.97 | 51389.33 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.31 | 59.10 | 25930.62 | 53439.08 | 30-NOV-07:53 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 49.59 | 59.50 | 26841.29 | 55018.31 | 29-DEC-07:55 |
Annual Sum or Average | 0.00 | 25816.44 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.37 | 58.30 | 23979.46 | 48465.85 | ||
Maximum of Months | 0.00 | 0.00 | 52.76 | 59.72 | 27669.34 | 56121.67 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.959004E+11 | 0.00 | 0.133833E+09 | 0.419583E+11 | 0.00 | 0.00 |
February | 0.707753E+11 | 0.00 | 0.217466E+10 | 0.381147E+11 | 0.00 | 0.00 |
March | 0.545523E+11 | 0.00 | 0.468935E+10 | 0.425581E+11 | 0.00 | 0.00 |
April | 0.267302E+11 | 0.00 | 0.302414E+11 | 0.414423E+11 | 0.00 | 0.00 |
May | 0.982162E+10 | 0.00 | 0.593129E+11 | 0.431205E+11 | 0.00 | 0.00 |
June | 0.936424E+09 | 0.00 | 0.104681E+12 | 0.421016E+11 | 0.00 | 0.00 |
July | 0.304047E+09 | 0.00 | 0.174201E+12 | 0.438244E+11 | 0.00 | 0.00 |
August | 0.323760E+09 | 0.00 | 0.215343E+12 | 0.440958E+11 | 0.00 | 0.00 |
September | 0.156197E+10 | 0.00 | 0.866994E+11 | 0.419597E+11 | 0.00 | 0.00 |
October | 0.138594E+11 | 0.00 | 0.173006E+11 | 0.427776E+11 | 0.00 | 0.00 |
November | 0.637115E+11 | 0.00 | 0.397513E+10 | 0.409899E+11 | 0.00 | 0.00 |
December | 0.103511E+12 | 0.00 | 65945965.06 | 0.420228E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.441988E+12 | 0.00 | 0.698818E+12 | 0.504966E+12 | 0.00 | 0.00 |
Minimum of Months | 0.304047E+09 | 0.00 | 65945965.06 | 0.381147E+11 | 0.00 | 0.00 |
Maximum of Months | 0.103511E+12 | 0.00 | 0.215343E+12 | 0.440958E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.117605E+09 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
February | 93491715.05 | 0.00 | 0.100185E+09 | 0.236042E+10 | 0.00 | 0.00 |
March | 13199.94 | 0.00 | 0.213107E+09 | 0.261333E+10 | 0.00 | 0.00 |
April | 4304.05 | 0.00 | 0.167058E+10 | 0.252903E+10 | 0.00 | 0.00 |
May | 6918.95 | 0.00 | 0.330427E+10 | 0.261333E+10 | 0.00 | 0.00 |
June | 20115.09 | 0.00 | 0.589822E+10 | 0.252903E+10 | 0.00 | 0.00 |
July | 23830.79 | 0.00 | 0.110614E+11 | 0.261333E+10 | 0.00 | 0.00 |
August | 26016.37 | 0.00 | 0.145691E+11 | 0.261333E+10 | 0.00 | 0.00 |
September | 19259.96 | 0.00 | 0.509662E+10 | 0.252903E+10 | 0.00 | 0.00 |
October | 3830.19 | 0.00 | 0.823568E+09 | 0.261333E+10 | 0.00 | 0.00 |
November | 139310.27 | 0.00 | 0.200368E+09 | 0.252903E+10 | 0.00 | 0.00 |
December | 21026763.18 | 0.00 | 0.00 | 0.261333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.232381E+09 | 0.00 | 0.429374E+11 | 0.307698E+11 | 0.00 | 0.00 |
Minimum of Months | 3830.19 | 0.00 | 0.00 | 0.236042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117605E+09 | 0.00 | 0.145691E+11 | 0.261333E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.419583E+11 | 0.133833E+09 | 0.959004E+11 | 0.713613E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381147E+11 | 0.217466E+10 | 0.707753E+11 | 0.486422E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425581E+11 | 0.468935E+10 | 0.545523E+11 | 0.391301E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.414423E+11 | 0.302414E+11 | 0.267302E+11 | 0.115211E+10 | 0.169717E+09 | 0.00 | 0.00 | 0.00 |
May | 0.431205E+11 | 0.593129E+11 | 0.982162E+10 | 0.917636E+09 | 10425332.01 | 0.00 | 0.00 | 0.00 |
June | 0.421016E+11 | 0.104681E+12 | 0.936424E+09 | 0.177103E+10 | 3070423.33 | 0.00 | 0.00 | 0.00 |
July | 0.438244E+11 | 0.174201E+12 | 0.304047E+09 | 0.133909E+10 | 0.209089E+10 | 0.00 | 0.00 | 0.00 |
August | 0.440958E+11 | 0.215343E+12 | 0.323760E+09 | 0.191800E+10 | 0.554861E+10 | 0.00 | 0.00 | 0.00 |
September | 0.419597E+11 | 0.866994E+11 | 0.156197E+10 | 0.579785E+09 | 4454486.21 | 0.00 | 0.00 | 0.00 |
October | 0.427776E+11 | 0.173006E+11 | 0.138594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.409899E+11 | 0.397513E+10 | 0.637115E+11 | 0.696792E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420228E+11 | 65945965.06 | 0.103511E+12 | 0.280347E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.504966E+12 | 0.698818E+12 | 0.441988E+12 | 0.166597E+12 | 0.782717E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.381147E+11 | 65945965.06 | 0.304047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.440958E+11 | 0.215343E+12 | 0.103511E+12 | 0.713613E+11 | 0.554861E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261333E+10 | 0.00 | 0.117605E+09 | 0.392516E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 0.100185E+09 | 93491715.05 | 0.315424E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 0.213107E+09 | 13199.94 | 0.265063E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 0.167058E+10 | 4304.05 | 0.184485E+11 | 54044156.47 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 0.330427E+10 | 6918.95 | 0.121699E+11 | 33741152.24 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 0.589822E+10 | 20115.09 | 0.452870E+10 | 48175758.79 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 0.110614E+11 | 23830.79 | 0.165403E+10 | 0.624025E+09 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 0.145691E+11 | 26016.37 | 0.114175E+10 | 0.143459E+10 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 0.509662E+10 | 19259.96 | 0.457409E+10 | 79116666.10 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 0.823568E+09 | 3830.19 | 0.151103E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 0.200368E+09 | 139310.27 | 0.255704E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 0.00 | 21026763.18 | 0.364639E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.429374E+11 | 0.232381E+09 | 0.216962E+12 | 0.227369E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 0.00 | 3830.19 | 0.114175E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.145691E+11 | 0.117605E+09 | 0.392516E+11 | 0.143459E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.419583E+11 | 0.959004E+11 | 0.133833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381147E+11 | 0.707753E+11 | 0.217466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425581E+11 | 0.545523E+11 | 0.468935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.414423E+11 | 0.267302E+11 | 0.302414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.431205E+11 | 0.982162E+10 | 0.593129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.421016E+11 | 0.936424E+09 | 0.104681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.438244E+11 | 0.304047E+09 | 0.174201E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.440958E+11 | 0.323760E+09 | 0.215343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.419597E+11 | 0.156197E+10 | 0.866994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.427776E+11 | 0.138594E+11 | 0.173006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.409899E+11 | 0.637115E+11 | 0.397513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420228E+11 | 0.103511E+12 | 65945965.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.504966E+12 | 0.441988E+12 | 0.698818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.381147E+11 | 0.304047E+09 | 65945965.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.440958E+11 | 0.103511E+12 | 0.215343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261333E+10 | 0.117605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236042E+10 | 93491715.05 | 0.100185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261333E+10 | 13199.94 | 0.213107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252903E+10 | 4304.05 | 0.167058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261333E+10 | 6918.95 | 0.330427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252903E+10 | 20115.09 | 0.589822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261333E+10 | 23830.79 | 0.110614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261333E+10 | 26016.37 | 0.145691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252903E+10 | 19259.96 | 0.509662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261333E+10 | 3830.19 | 0.823568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252903E+10 | 139310.27 | 0.200368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261333E+10 | 21026763.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307698E+11 | 0.232381E+09 | 0.429374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.236042E+10 | 3830.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261333E+10 | 0.117605E+09 | 0.145691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.493465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.438299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
March | 0.476625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
April | 0.424227E+11 | 0.00 | 0.00 | 0.00 | 7465152.75 | 0.00 | 0.00 | 0.00 | 0.71 |
May | 0.406649E+11 | 0.00 | 0.00 | 0.00 | 447146.66 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 0.351376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
July | 0.312298E+11 | 0.00 | 0.00 | 0.00 | 0.117399E+09 | 0.00 | 0.00 | 0.00 | 0.89 |
August | 0.280464E+11 | 0.00 | 0.00 | 0.00 | 0.337426E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
September | 0.369055E+11 | 0.00 | 0.00 | 0.00 | 1397403.57 | 0.00 | 0.00 | 0.00 | 0.87 |
October | 0.436427E+11 | 0.00 | 0.00 | 10989.75 | 0.00 | 0.00 | 0.352036E+09 | 0.00 | 0.74 |
November | 0.445406E+11 | 0.00 | 0.00 | 181996.01 | 0.00 | 0.00 | 0.204413E+10 | 0.00 | 0.65 |
December | 0.507469E+11 | 0.00 | 0.00 | 264.16 | 0.00 | 0.00 | 24351626.59 | 0.00 | 0.60 |
Annual Sum or Average | 0.494176E+12 | 0.00 | 0.00 | 193249.91 | 0.464134E+09 | 0.00 | 0.242051E+10 | 0.00 | 0.74 |
Minimum of Months | 0.280464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.507469E+11 | 0.00 | 0.00 | 181996.01 | 0.337426E+09 | 0.00 | 0.204413E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160717E+10 | 0.00 | 0.00 | 1.00 |
February | 0.333202E+10 | 0.00 | 0.00 | 26421.87 | 0.00 | 0.698913E+09 | 35754231.66 | 0.00 | 1.06 |
March | 0.428008E+10 | 0.00 | 0.00 | 126804.59 | 0.00 | 52801689.91 | 93642397.98 | 0.00 | 1.09 |
April | 0.384426E+10 | 1027118.36 | 0.00 | 228180.50 | 0.00 | 0.00 | 92968235.86 | 0.00 | 1.20 |
May | 0.363419E+10 | 3863.86 | 0.00 | 381045.96 | 37624.19 | 0.00 | 0.140720E+09 | 0.00 | 1.32 |
June | 0.310620E+10 | 0.00 | 0.00 | 442516.52 | 0.00 | 0.00 | 0.154068E+09 | 0.00 | 1.46 |
July | 0.243108E+10 | 12215854.38 | 0.00 | 1412039.16 | 601744.96 | 0.00 | 0.472070E+09 | 0.00 | 1.52 |
August | 0.212017E+10 | 42923204.08 | 0.00 | 1771900.25 | 349007.32 | 0.00 | 0.497110E+09 | 0.00 | 1.54 |
September | 0.298897E+10 | 247394.35 | 0.00 | 1696610.05 | 0.00 | 0.00 | 0.471007E+09 | 0.00 | 1.53 |
October | 0.388342E+10 | 0.00 | 0.00 | 355391.97 | 0.00 | 0.00 | 0.215239E+09 | 0.00 | 1.26 |
November | 0.394627E+10 | 0.00 | 0.00 | 41871.27 | 0.00 | 0.366132E+09 | 10985807.56 | 0.00 | 1.09 |
December | 0.324109E+10 | 0.00 | 0.00 | 997.18 | 0.00 | 0.146056E+10 | 9108371.87 | 0.00 | 1.00 |
Annual Sum or Average | 0.397791E+11 | 56417435.03 | 0.00 | 6483779.32 | 988376.47 | 0.418558E+10 | 0.219267E+10 | 0.00 | 1.26 |
Minimum of Months | 0.212017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Maximum of Months | 0.428008E+10 | 42923204.08 | 0.00 | 1771900.25 | 601744.96 | 0.160717E+10 | 0.497110E+09 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.529200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
February | 0.470039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
March | 0.511140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
April | 0.454113E+10 | 0.00 | 0.00 | 1590.13 | 800574.32 | 0.00 | 8336877.91 | 0.00 | 1.20 |
May | 0.434359E+10 | 0.00 | 0.00 | 2825.04 | 47952.69 | 0.00 | 17366931.55 | 0.00 | 1.31 |
June | 0.371099E+10 | 0.00 | 0.00 | 17562.61 | 0.00 | 0.00 | 57198420.86 | 0.00 | 1.45 |
July | 0.310531E+10 | 140644.51 | 0.00 | 102671.96 | 12449371.51 | 0.00 | 0.243728E+09 | 0.00 | 1.49 |
August | 0.263767E+10 | 668851.88 | 0.00 | 259164.56 | 35517210.26 | 0.00 | 0.369874E+09 | 0.00 | 1.46 |
September | 0.383891E+10 | 0.00 | 0.00 | 48538.28 | 149859.68 | 0.00 | 0.118849E+09 | 0.00 | 1.46 |
October | 0.471251E+10 | 0.00 | 0.00 | 503.28 | 0.00 | 0.00 | 5550721.96 | 0.00 | 1.25 |
November | 0.499583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
December | 0.544478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Annual Sum or Average | 0.524345E+11 | 809496.39 | 0.00 | 432855.86 | 48964968.47 | 0.00 | 0.820904E+09 | 0.00 | 1.24 |
Minimum of Months | 0.263767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Maximum of Months | 0.544478E+10 | 668851.88 | 0.00 | 259164.56 | 35517210.26 | 0.00 | 0.369874E+09 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70815570.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2567148.83 | 0.00 | 0.00 | 0.01 |
February | 63113494.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1625648.95 | 0.00 | 0.00 | 0.01 |
March | 69874826.67 | 0.00 | 0.00 | 8.03 | 0.00 | 0.00 | 16259.38 | 0.00 | 0.01 |
April | 57383409.33 | 0.00 | 0.00 | 96645.33 | 10946.71 | 0.00 | 43174448.35 | 0.00 | 0.01 |
May | 41060897.16 | 11125.02 | 0.00 | 492440.30 | 0.00 | 0.00 | 0.210341E+09 | 0.00 | 0.04 |
June | 16170523.52 | 0.00 | 0.00 | 1110349.27 | 0.00 | 0.00 | 0.426666E+09 | 0.00 | 0.09 |
July | 2087983.23 | 3382696.77 | 0.00 | 1943319.57 | 0.00 | 0.00 | 0.669750E+09 | 0.00 | 0.15 |
August | 2328710.02 | 9649768.75 | 0.00 | 2079785.80 | 0.00 | 0.00 | 0.668838E+09 | 0.00 | 0.16 |
September | 21195955.82 | 19170.20 | 0.00 | 937408.78 | 0.00 | 0.00 | 0.387806E+09 | 0.00 | 0.08 |
October | 58315367.83 | 0.00 | 0.00 | 109942.04 | 0.00 | 0.00 | 64936161.63 | 0.00 | 0.02 |
November | 67437814.43 | 0.00 | 0.00 | 7243.96 | 0.00 | 0.00 | 4709573.90 | 0.00 | 0.01 |
December | 74072523.97 | 0.00 | 0.00 | 0.00 | 0.00 | 388220.70 | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.543857E+09 | 13062760.74 | 0.00 | 6777143.08 | 10946.71 | 4581018.48 | 0.247624E+10 | 0.00 | 0.05 |
Minimum of Months | 2087983.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 74072523.97 | 9649768.75 | 0.00 | 2079785.80 | 10946.71 | 2567148.83 | 0.669750E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135944E+10 | 0.00 | 0.00 | 0.52 |
February | 0.226848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692880E+09 | 0.00 | 0.00 | 0.54 |
March | 0.321013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10180543.52 | 0.00 | 0.00 | 0.56 |
April | 0.286628E+10 | 0.00 | 0.00 | 0.00 | 504382.32 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.274752E+10 | 0.00 | 0.00 | 0.00 | 30211.42 | 0.00 | 0.00 | 0.00 | 0.68 |
June | 0.237407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.211004E+10 | 0.00 | 0.00 | 0.00 | 7932032.44 | 0.00 | 0.00 | 0.00 | 0.77 |
August | 0.189495E+10 | 0.00 | 0.00 | 0.00 | 22798145.62 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 0.249352E+10 | 0.00 | 0.00 | 0.00 | 94415.44 | 0.00 | 0.00 | 0.00 | 0.75 |
October | 0.297250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
November | 0.301840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129101E+09 | 0.00 | 0.00 | 0.56 |
December | 0.269586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734492E+09 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.306264E+11 | 0.00 | 0.00 | 0.00 | 31359187.24 | 0.292609E+10 | 0.00 | 0.00 | 0.64 |
Minimum of Months | 0.189495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.321013E+10 | 0.00 | 0.00 | 0.00 | 22798145.62 | 0.135944E+10 | 0.00 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.101237E+09 | 0.00 | 0.00 | 0.652460E+11 | 0.00 | 12.28 |
February | 0.00 | 0.00 | 0.00 | 89657232.37 | 0.00 | 0.00 | 0.584350E+11 | 0.00 | 13.04 |
March | 0.00 | 0.00 | 0.00 | 97594605.39 | 0.00 | 0.00 | 0.633702E+11 | 0.00 | 13.68 |
April | 0.00 | 8355633.58 | 0.00 | 99932292.92 | 0.00 | 0.00 | 0.568081E+11 | 0.00 | 15.07 |
May | 0.00 | 736643.03 | 0.00 | 0.112762E+09 | 0.00 | 0.00 | 0.552054E+11 | 0.00 | 16.82 |
June | 0.00 | 0.00 | 0.00 | 0.116142E+09 | 0.00 | 0.00 | 0.476950E+11 | 0.00 | 18.69 |
July | 0.00 | 0.152638E+09 | 0.00 | 0.121497E+09 | 0.00 | 0.00 | 0.419577E+11 | 0.00 | 19.12 |
August | 0.00 | 0.406925E+09 | 0.00 | 0.115111E+09 | 0.00 | 0.00 | 0.376538E+11 | 0.00 | 18.78 |
September | 0.00 | 1538036.38 | 0.00 | 0.110662E+09 | 0.00 | 0.00 | 0.502481E+11 | 0.00 | 18.77 |
October | 0.00 | 0.00 | 0.00 | 99587872.31 | 0.00 | 0.00 | 0.595843E+11 | 0.00 | 15.82 |
November | 0.00 | 0.00 | 0.00 | 95531745.86 | 0.00 | 0.00 | 0.622770E+11 | 0.00 | 13.65 |
December | 0.00 | 0.00 | 0.00 | 0.100727E+09 | 0.00 | 0.00 | 0.667962E+11 | 0.00 | 12.27 |
Annual Sum or Average | 0.00 | 0.570193E+09 | 0.00 | 0.126044E+10 | 0.00 | 0.00 | 0.665277E+12 | 0.00 | 15.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 89657232.37 | 0.00 | 0.00 | 0.376538E+11 | 0.00 | 12.27 |
Maximum of Months | 0.00 | 0.406925E+09 | 0.00 | 0.121497E+09 | 0.00 | 0.00 | 0.667962E+11 | 0.00 | 19.12 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.389137E+11 | 0.00 | 0.00 | 5268.01 | 0.00 | 0.00 | 0.129471E+09 | 0.00 | 3.04 |
February | 0.329787E+11 | 0.00 | 0.00 | 136604.17 | 0.00 | 0.00 | 0.169960E+10 | 0.00 | 3.20 |
March | 0.332455E+11 | 0.00 | 0.00 | 453968.52 | 0.00 | 0.00 | 0.446481E+10 | 0.00 | 3.31 |
April | 0.268869E+11 | 4902806.17 | 0.00 | 1099159.88 | 1003650.35 | 0.00 | 0.667699E+10 | 0.00 | 3.63 |
May | 0.213456E+11 | 0.00 | 0.00 | 1875605.40 | 353784.10 | 0.00 | 0.108267E+11 | 0.00 | 3.98 |
June | 0.160404E+11 | 0.00 | 0.00 | 2925624.91 | 0.00 | 0.00 | 0.117577E+11 | 0.00 | 4.41 |
July | 0.124244E+11 | 27422757.70 | 0.00 | 4367212.71 | 65463536.69 | 0.00 | 0.122804E+11 | 0.00 | 4.53 |
August | 0.101554E+11 | 0.140363E+09 | 0.00 | 6087001.41 | 0.126610E+09 | 0.00 | 0.120290E+11 | 0.00 | 4.44 |
September | 0.166920E+11 | 1073353.62 | 0.00 | 4423963.41 | 32277.26 | 0.00 | 0.125034E+11 | 0.00 | 4.43 |
October | 0.260663E+11 | 0.00 | 0.00 | 1536706.00 | 0.00 | 0.00 | 0.874095E+10 | 0.00 | 3.78 |
November | 0.342277E+11 | 0.00 | 0.00 | 248920.08 | 0.00 | 0.00 | 0.263014E+10 | 0.00 | 3.31 |
December | 0.400841E+11 | 0.00 | 0.00 | 2184.95 | 0.00 | 0.00 | 86234283.03 | 0.00 | 3.04 |
Annual Sum or Average | 0.309061E+12 | 0.173762E+09 | 0.00 | 23162219.44 | 0.193463E+09 | 0.00 | 0.838253E+11 | 0.00 | 3.76 |
Minimum of Months | 0.101554E+11 | 0.00 | 0.00 | 2184.95 | 0.00 | 0.00 | 86234283.03 | 0.00 | 3.04 |
Maximum of Months | 0.400841E+11 | 0.140363E+09 | 0.00 | 6087001.41 | 0.126610E+09 | 0.00 | 0.125034E+11 | 0.00 | 4.53 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109235E+12 | 0.00 | 0.00 | 137.26 | 0.00 | 0.00 | 75309951.36 | 0.00 | 1.23 |
February | 0.962130E+11 | 0.00 | 0.00 | 127467.66 | 0.00 | 0.00 | 0.876671E+09 | 0.00 | 1.30 |
March | 0.102582E+12 | 0.00 | 0.00 | 415606.35 | 0.00 | 0.00 | 0.299704E+10 | 0.00 | 1.34 |
April | 0.844922E+11 | 0.00 | 0.00 | 2193029.86 | 16536421.38 | 0.00 | 0.947811E+10 | 0.00 | 1.47 |
May | 0.707079E+11 | 0.00 | 0.00 | 5427410.05 | 990496.23 | 0.00 | 0.193654E+11 | 0.00 | 1.61 |
June | 0.468423E+11 | 0.00 | 0.00 | 10458324.84 | 0.00 | 0.00 | 0.309822E+11 | 0.00 | 1.79 |
July | 0.321504E+11 | 4250147.82 | 0.00 | 20044713.26 | 0.255805E+09 | 0.00 | 0.370122E+11 | 0.00 | 1.84 |
August | 0.259509E+11 | 26616758.43 | 0.00 | 27201378.07 | 0.720832E+09 | 0.00 | 0.361776E+11 | 0.00 | 1.80 |
September | 0.508933E+11 | 0.00 | 0.00 | 13069144.90 | 3095456.32 | 0.00 | 0.308487E+11 | 0.00 | 1.80 |
October | 0.843362E+11 | 0.00 | 0.00 | 2983262.99 | 0.00 | 0.00 | 0.131157E+11 | 0.00 | 1.53 |
November | 0.101787E+12 | 0.00 | 0.00 | 174479.24 | 0.00 | 0.00 | 0.140556E+10 | 0.00 | 1.34 |
December | 0.112383E+12 | 0.00 | 0.00 | 535.26 | 0.00 | 0.00 | 83073487.96 | 0.00 | 1.23 |
Annual Sum or Average | 0.917572E+12 | 30866906.24 | 0.00 | 82095489.73 | 0.997259E+09 | 0.00 | 0.182418E+12 | 0.00 | 1.52 |
Minimum of Months | 0.259509E+11 | 0.00 | 0.00 | 137.26 | 0.00 | 0.00 | 75309951.36 | 0.00 | 1.23 |
Maximum of Months | 0.112383E+12 | 26616758.43 | 0.00 | 27201378.07 | 0.720832E+09 | 0.00 | 0.370122E+11 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58031882.14 | 0.00 | 0.00 | 119171.29 | 0.00 | 0.128071E+10 | 5428312.82 | 0.00 | 0.34 |
February | 64448328.74 | 0.00 | 0.00 | 334532.74 | 0.00 | 0.105932E+10 | 94534338.10 | 0.00 | 0.34 |
March | 77467050.73 | 0.00 | 0.00 | 1397177.13 | 0.00 | 0.983219E+09 | 0.294277E+09 | 0.00 | 0.34 |
April | 69946877.44 | 586614.28 | 0.00 | 3694426.87 | 0.00 | 0.543874E+09 | 0.639187E+09 | 0.00 | 0.34 |
May | 62546683.12 | 830146.30 | 0.00 | 7442597.20 | 0.00 | 0.191039E+09 | 0.956504E+09 | 0.00 | 0.34 |
June | 46675065.96 | 345710.86 | 0.00 | 8780210.13 | 0.00 | 31061765.13 | 0.942919E+09 | 0.00 | 0.34 |
July | 19963990.28 | 11330943.92 | 0.00 | 10838010.40 | 0.00 | 2467996.51 | 0.809548E+09 | 0.00 | 0.34 |
August | 17449491.13 | 28672919.31 | 0.00 | 8559776.87 | 17024.94 | 3269920.23 | 0.618128E+09 | 0.00 | 0.34 |
September | 41514089.11 | 2099074.23 | 0.00 | 7692967.14 | 0.00 | 61091084.69 | 0.897981E+09 | 0.00 | 0.34 |
October | 70801170.90 | 0.00 | 0.00 | 2620948.06 | 0.00 | 0.651281E+09 | 0.604174E+09 | 0.00 | 0.34 |
November | 60451091.81 | 0.00 | 0.00 | 407256.09 | 0.00 | 0.112569E+10 | 0.110120E+09 | 0.00 | 0.34 |
December | 53771729.62 | 0.00 | 0.00 | 126483.77 | 0.00 | 0.128009E+10 | 10535574.31 | 0.00 | 0.34 |
Annual Sum or Average | 0.643067E+09 | 43865408.91 | 0.00 | 52013557.69 | 17024.94 | 0.721312E+10 | 0.598334E+10 | 0.00 | 0.34 |
Minimum of Months | 17449491.13 | 0.00 | 0.00 | 119171.29 | 0.00 | 2467996.51 | 5428312.82 | 0.00 | 0.34 |
Maximum of Months | 77467050.73 | 28672919.31 | 0.00 | 10838010.40 | 17024.94 | 0.128071E+10 | 0.956504E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 47309405.91 | 0.00 | 0.00 | 95449.68 | 0.00 | 0.129174E+10 | 4990104.56 | 0.00 | 0.34 |
February | 57740585.22 | 0.00 | 0.00 | 126873.61 | 0.00 | 0.111380E+10 | 46825077.61 | 0.00 | 0.34 |
March | 89369437.31 | 0.00 | 0.00 | 453985.45 | 0.00 | 0.110374E+10 | 0.162638E+09 | 0.00 | 0.34 |
April | 0.117686E+09 | 522339.50 | 0.00 | 1942104.06 | 64206.05 | 0.658214E+09 | 0.478713E+09 | 0.00 | 0.34 |
May | 0.182026E+09 | 526187.49 | 0.00 | 4385957.48 | 303861.55 | 0.213360E+09 | 0.817618E+09 | 0.00 | 0.34 |
June | 0.219174E+09 | 317025.96 | 0.00 | 5392761.14 | 28644.40 | 34461343.37 | 0.770287E+09 | 0.00 | 0.34 |
July | 0.211270E+09 | 9369201.00 | 1965.24 | 7252172.16 | 1956888.58 | 2557074.96 | 0.621640E+09 | 1561.52 | 0.34 |
August | 0.175214E+09 | 25168046.89 | 6897.47 | 4961120.14 | 3506962.15 | 2584606.20 | 0.464572E+09 | 4676.29 | 0.34 |
September | 0.201078E+09 | 861608.75 | 0.00 | 3663449.41 | 1237219.54 | 70665199.52 | 0.732754E+09 | 0.00 | 0.34 |
October | 0.116868E+09 | 0.00 | 0.00 | 895276.77 | 0.00 | 0.793849E+09 | 0.417109E+09 | 0.00 | 0.34 |
November | 67380346.63 | 0.00 | 0.00 | 173659.04 | 0.00 | 0.115966E+10 | 69304968.14 | 0.00 | 0.34 |
December | 49998780.83 | 0.00 | 0.00 | 97434.22 | 0.00 | 0.128896E+10 | 5308296.07 | 0.00 | 0.34 |
Annual Sum or Average | 0.153511E+10 | 36764409.59 | 8862.71 | 29440243.17 | 7097782.27 | 0.773360E+10 | 0.459176E+10 | 6237.81 | 0.34 |
Minimum of Months | 47309405.91 | 0.00 | 0.00 | 95449.68 | 0.00 | 2557074.96 | 4990104.56 | 0.00 | 0.34 |
Maximum of Months | 0.219174E+09 | 25168046.89 | 6897.47 | 7252172.16 | 3506962.15 | 0.129174E+10 | 0.817618E+09 | 4676.29 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.584537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 0.845842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.101585E+10 | 0.00 | 0.00 | 289769.80 | 0.00 | 0.00 | 0.319682E+09 | 0.00 | 0.02 |
April | 0.755829E+09 | 5283601.63 | 0.00 | 775502.29 | 0.00 | 0.00 | 0.472708E+09 | 0.00 | 0.02 |
May | 0.544938E+09 | 48001.99 | 0.00 | 1305273.10 | 0.00 | 0.00 | 0.611879E+09 | 0.00 | 0.02 |
June | 0.352059E+09 | 0.00 | 0.00 | 1211258.51 | 0.00 | 0.00 | 0.645392E+09 | 0.00 | 0.02 |
July | 27939502.02 | 23990417.92 | 0.00 | 1884435.14 | 0.00 | 0.00 | 0.486893E+09 | 0.00 | 0.02 |
August | 0.156492E+09 | 79837026.23 | 0.00 | 885342.95 | 0.00 | 0.00 | 0.249793E+09 | 0.00 | 0.02 |
September | 0.351207E+09 | 19375627.41 | 0.00 | 1685329.08 | 0.00 | 0.00 | 0.494882E+09 | 0.00 | 0.02 |
October | 0.729931E+09 | 0.00 | 0.00 | 1231316.57 | 0.00 | 0.00 | 0.624732E+09 | 0.00 | 0.02 |
November | 0.985484E+09 | 0.00 | 0.00 | 115739.42 | 0.00 | 0.00 | 43084783.07 | 0.00 | 0.02 |
December | 0.785119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.713522E+10 | 0.128535E+09 | 0.00 | 9383966.85 | 0.00 | 0.00 | 0.394905E+10 | 0.00 | 0.02 |
Minimum of Months | 27939502.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.101585E+10 | 79837026.23 | 0.00 | 1884435.14 | 0.00 | 0.00 | 0.645392E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.854616E+09 | 0.00 | 0.00 | 11313479.68 | 0.00 | 0.688216E+10 | 0.104843E+11 | 0.00 | 0.39 |
February | 0.891735E+09 | 0.00 | 0.00 | 16072558.31 | 0.00 | 0.503251E+10 | 0.105878E+11 | 0.00 | 0.39 |
March | 0.121224E+10 | 0.00 | 0.00 | 32711881.47 | 0.00 | 0.414033E+09 | 0.167371E+11 | 0.00 | 0.39 |
April | 0.159633E+10 | 7085221.98 | 0.00 | 53981380.02 | 870916.57 | 0.104449E+09 | 0.152896E+11 | 0.00 | 0.39 |
May | 0.247294E+10 | 7046686.66 | 0.00 | 80689815.16 | 4212430.63 | 47423126.04 | 0.139121E+11 | 0.00 | 0.39 |
June | 0.298022E+10 | 4300266.96 | 0.00 | 93018257.75 | 388544.08 | 10079812.14 | 0.108787E+11 | 0.00 | 0.39 |
July | 0.287697E+10 | 0.114944E+09 | 5726.27 | 0.102472E+09 | 38728675.58 | 3681593.33 | 0.844786E+10 | 616.49 | 0.39 |
August | 0.237951E+10 | 0.299209E+09 | 472982.29 | 73019988.73 | 89427182.02 | 4519040.18 | 0.632361E+10 | 6646.71 | 0.39 |
September | 0.272279E+10 | 11687205.82 | 0.00 | 66995102.30 | 16782140.84 | 36691780.44 | 0.108486E+11 | 0.00 | 0.39 |
October | 0.158525E+10 | 0.00 | 0.00 | 43786553.09 | 0.00 | 0.220937E+09 | 0.161733E+11 | 0.00 | 0.39 |
November | 0.953415E+09 | 0.00 | 0.00 | 24449661.22 | 0.00 | 0.165478E+10 | 0.149539E+11 | 0.00 | 0.39 |
December | 0.877830E+09 | 0.00 | 0.00 | 12022955.76 | 0.00 | 0.587145E+10 | 0.114743E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.214039E+11 | 0.444273E+09 | 478708.57 | 0.610533E+09 | 0.150410E+09 | 0.202827E+11 | 0.146111E+12 | 7263.20 | 0.39 |
Minimum of Months | 0.854616E+09 | 0.00 | 0.00 | 11313479.68 | 0.00 | 3681593.33 | 0.632361E+10 | 0.00 | 0.39 |
Maximum of Months | 0.298022E+10 | 0.299209E+09 | 472982.29 | 0.102472E+09 | 89427182.02 | 0.688216E+10 | 0.167371E+11 | 6646.71 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 57717809.32 | 0.00 | 0.00 | 113614.13 | 0.00 | 0.127939E+10 | 7069215.64 | 0.00 | 0.34 |
February | 64446103.99 | 0.00 | 0.00 | 244710.50 | 0.00 | 0.105194E+10 | 0.102003E+09 | 0.00 | 0.34 |
March | 77467050.73 | 0.00 | 0.00 | 1093898.83 | 0.00 | 0.950946E+09 | 0.326853E+09 | 0.00 | 0.34 |
April | 65170948.72 | 586614.28 | 0.00 | 3827404.76 | 0.00 | 0.521537E+09 | 0.666167E+09 | 0.00 | 0.34 |
May | 54399074.15 | 826575.87 | 3378.14 | 6457039.55 | 0.00 | 0.235035E+09 | 0.921641E+09 | 192.29 | 0.34 |
June | 32490000.22 | 345710.86 | 0.00 | 9400283.88 | 0.00 | 37556343.61 | 0.949989E+09 | 0.00 | 0.34 |
July | 14436931.00 | 11330168.29 | 185.55 | 10217026.17 | 0.00 | 2411359.68 | 0.815753E+09 | 590.08 | 0.34 |
August | 15564238.40 | 28673987.27 | 0.00 | 9176560.43 | 15956.98 | 2266058.59 | 0.620400E+09 | 0.00 | 0.34 |
September | 39933431.47 | 2098092.04 | 849.42 | 7124239.14 | 0.00 | 57364589.69 | 0.903857E+09 | 132.77 | 0.34 |
October | 66217535.23 | 0.00 | 0.00 | 2535731.68 | 0.00 | 0.658331E+09 | 0.601792E+09 | 0.00 | 0.34 |
November | 60451091.81 | 0.00 | 0.00 | 394515.89 | 0.00 | 0.110853E+10 | 0.127296E+09 | 0.00 | 0.34 |
December | 53771729.62 | 0.00 | 0.00 | 143308.66 | 0.00 | 0.126137E+10 | 29237729.81 | 0.00 | 0.34 |
Annual Sum or Average | 0.602066E+09 | 43861148.62 | 4413.10 | 50728333.64 | 15956.98 | 0.716669E+10 | 0.607206E+10 | 915.14 | 0.34 |
Minimum of Months | 14436931.00 | 0.00 | 0.00 | 113614.13 | 0.00 | 2266058.59 | 7069215.64 | 0.00 | 0.34 |
Maximum of Months | 77467050.73 | 28673987.27 | 3378.14 | 10217026.17 | 15956.98 | 0.127939E+10 | 0.949989E+09 | 590.08 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 41518010.39 | 0.00 | 0.00 | 95122.93 | 0.00 | 0.129705E+10 | 5470061.35 | 0.00 | 0.34 |
February | 60191996.00 | 0.00 | 0.00 | 114365.80 | 0.00 | 0.111811E+10 | 40073908.59 | 0.00 | 0.34 |
March | 89369437.31 | 0.00 | 0.00 | 273109.19 | 0.00 | 0.110932E+10 | 0.157237E+09 | 0.00 | 0.34 |
April | 0.117677E+09 | 579545.50 | 6492.15 | 2285867.98 | 0.00 | 0.591384E+09 | 0.545208E+09 | 507.90 | 0.34 |
May | 0.179109E+09 | 629276.86 | 2221.80 | 3975289.93 | 197219.26 | 0.273735E+09 | 0.760571E+09 | 1331.11 | 0.34 |
June | 0.212956E+09 | 317025.96 | 0.00 | 6374005.80 | 28644.40 | 38546935.66 | 0.771438E+09 | 0.00 | 0.34 |
July | 0.207014E+09 | 9544941.98 | 14014.99 | 7112233.92 | 1770236.96 | 2585897.19 | 0.626007E+09 | 422.40 | 0.34 |
August | 0.173706E+09 | 26161242.74 | 19414.48 | 5558537.96 | 2503119.05 | 2099314.76 | 0.465967E+09 | 2806.53 | 0.34 |
September | 0.199183E+09 | 1578260.37 | 3214.28 | 3776599.87 | 517052.82 | 92049530.36 | 0.713152E+09 | 300.82 | 0.34 |
October | 0.116868E+09 | 0.00 | 0.00 | 981032.26 | 0.00 | 0.800943E+09 | 0.409929E+09 | 0.00 | 0.34 |
November | 67380346.63 | 0.00 | 0.00 | 164274.62 | 0.00 | 0.115849E+10 | 70489122.32 | 0.00 | 0.34 |
December | 49213180.30 | 0.00 | 0.00 | 96983.65 | 0.00 | 0.128930E+10 | 5757585.74 | 0.00 | 0.34 |
Annual Sum or Average | 0.151419E+10 | 38810293.42 | 45357.70 | 30807423.90 | 5016272.49 | 0.777362E+10 | 0.457130E+10 | 5368.77 | 0.34 |
Minimum of Months | 41518010.39 | 0.00 | 0.00 | 95122.93 | 0.00 | 2099314.76 | 5470061.35 | 0.00 | 0.34 |
Maximum of Months | 0.212956E+09 | 26161242.74 | 19414.48 | 7112233.92 | 2503119.05 | 0.129705E+10 | 0.771438E+09 | 2806.53 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.244104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301067E+10 | 0.00 | 0.00 | 0.34 |
February | 0.232751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108054E+10 | 0.00 | 0.00 | 0.35 |
March | 0.264582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27157271.20 | 0.00 | 0.00 | 0.37 |
April | 0.235736E+11 | 0.00 | 0.00 | 0.00 | 4148272.06 | 0.00 | 0.00 | 0.00 | 0.40 |
May | 0.225968E+11 | 0.00 | 0.00 | 0.00 | 248472.61 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.195254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.173539E+11 | 0.00 | 0.00 | 0.00 | 65236680.95 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.155850E+11 | 0.00 | 0.00 | 0.00 | 0.187502E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.205078E+11 | 0.00 | 0.00 | 0.00 | 776515.95 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.244472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 0.251916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694943E+09 | 0.00 | 0.00 | 0.37 |
December | 0.254332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277957E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.268358E+12 | 0.00 | 0.00 | 0.00 | 0.257912E+09 | 0.759288E+10 | 0.00 | 0.00 | 0.42 |
Minimum of Months | 0.155850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.264582E+11 | 0.00 | 0.00 | 0.00 | 0.187502E+09 | 0.301067E+10 | 0.00 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8858493.52 | 0.00 | 0.00 | 15851.68 | 0.00 | 0.326618E+09 | 580793.15 | 0.00 | 0.34 |
February | 13677362.47 | 0.00 | 0.00 | 70324.00 | 0.00 | 0.278261E+09 | 12650140.15 | 0.00 | 0.34 |
March | 18972423.43 | 0.00 | 0.00 | 330672.44 | 0.00 | 0.272027E+09 | 47759920.49 | 0.00 | 0.34 |
April | 16860256.45 | 146653.57 | 0.00 | 928693.48 | 0.00 | 0.174985E+09 | 0.121402E+09 | 0.00 | 0.34 |
May | 14638760.79 | 207536.58 | 0.00 | 1930792.56 | 0.00 | 90288742.46 | 0.197525E+09 | 0.00 | 0.34 |
June | 8951102.68 | 86427.72 | 0.00 | 2255965.06 | 0.00 | 22283659.36 | 0.223868E+09 | 0.00 | 0.34 |
July | 3044905.20 | 2832735.98 | 0.00 | 2736729.66 | 0.00 | 602664.15 | 0.204320E+09 | 0.00 | 0.34 |
August | 3938231.78 | 7168229.83 | 0.00 | 2040308.54 | 4256.23 | 852674.41 | 0.155021E+09 | 0.00 | 0.34 |
September | 10031755.19 | 524768.56 | 0.00 | 1848525.60 | 0.00 | 39220188.32 | 0.200969E+09 | 0.00 | 0.34 |
October | 17262758.90 | 0.00 | 0.00 | 589200.46 | 0.00 | 0.213772E+09 | 0.100595E+09 | 0.00 | 0.34 |
November | 13259864.45 | 0.00 | 0.00 | 88320.72 | 0.00 | 0.295420E+09 | 15399888.86 | 0.00 | 0.34 |
December | 8700044.34 | 0.00 | 0.00 | 18058.69 | 0.00 | 0.326689E+09 | 724754.78 | 0.00 | 0.34 |
Annual Sum or Average | 0.138196E+09 | 10966352.23 | 0.00 | 12853442.89 | 4256.23 | 0.204102E+10 | 0.128082E+10 | 0.00 | 0.34 |
Minimum of Months | 3044905.20 | 0.00 | 0.00 | 15851.68 | 0.00 | 602664.15 | 580793.15 | 0.00 | 0.34 |
Maximum of Months | 18972423.43 | 7168229.83 | 0.00 | 2736729.66 | 4256.23 | 0.326689E+09 | 0.223868E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2732610.43 | 0.00 | 0.00 | 10428.07 | 0.00 | 0.332405E+09 | 886079.98 | 0.00 | 0.34 |
February | 10763405.77 | 0.00 | 0.00 | 27134.90 | 0.00 | 0.288831E+09 | 5001126.81 | 0.00 | 0.34 |
March | 21754318.00 | 0.00 | 0.00 | 101942.57 | 0.00 | 0.296981E+09 | 20212865.78 | 0.00 | 0.34 |
April | 29419171.32 | 146636.39 | 0.00 | 474925.77 | 0.00 | 0.195610E+09 | 88634066.22 | 0.00 | 0.34 |
May | 44822773.88 | 170771.48 | 0.00 | 1166618.04 | 36740.78 | 93327679.76 | 0.165030E+09 | 0.00 | 0.34 |
June | 53248852.64 | 79256.49 | 0.00 | 1420515.58 | 7161.10 | 22479774.97 | 0.180180E+09 | 0.00 | 0.34 |
July | 51256512.17 | 2389180.04 | 323.96 | 1951651.54 | 442559.24 | 452328.96 | 0.157019E+09 | 340.85 | 0.34 |
August | 43624427.52 | 6566142.36 | 2408.13 | 1173530.38 | 601652.41 | 778591.70 | 0.116256E+09 | 1442.80 | 0.34 |
September | 50064218.94 | 363865.85 | 0.00 | 822141.41 | 160841.22 | 46048839.75 | 0.155105E+09 | 0.00 | 0.34 |
October | 29366891.39 | 0.00 | 0.00 | 166595.52 | 0.00 | 0.245484E+09 | 57162608.27 | 0.00 | 0.34 |
November | 12829074.19 | 0.00 | 0.00 | 35723.58 | 0.00 | 0.305181E+09 | 6083977.15 | 0.00 | 0.34 |
December | 6467932.52 | 0.00 | 0.00 | 11668.50 | 0.00 | 0.328695E+09 | 917899.62 | 0.00 | 0.34 |
Annual Sum or Average | 0.356350E+09 | 9715852.61 | 2732.09 | 7362875.86 | 1248954.75 | 0.215628E+10 | 0.952489E+09 | 1783.64 | 0.34 |
Minimum of Months | 2732610.43 | 0.00 | 0.00 | 10428.07 | 0.00 | 452328.96 | 886079.98 | 0.00 | 0.34 |
Maximum of Months | 53248852.64 | 6566142.36 | 2408.13 | 1951651.54 | 601652.41 | 0.332405E+09 | 0.180180E+09 | 1442.80 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 94766613.42 | 0.00 | 0.00 | 594471.10 | 0.00 | 0.193471E+10 | 0.129025E+09 | 0.00 | 0.39 |
February | 80387988.13 | 0.00 | 0.00 | 2236278.68 | 0.00 | 0.130381E+10 | 0.570839E+09 | 0.00 | 0.39 |
March | 88229479.69 | 0.00 | 0.00 | 4884180.13 | 0.00 | 0.915481E+09 | 0.116989E+10 | 0.00 | 0.39 |
April | 61845331.52 | 942174.30 | 0.00 | 8213717.20 | 0.00 | 0.401056E+09 | 0.154730E+10 | 0.00 | 0.39 |
May | 49275546.35 | 1333316.52 | 0.00 | 11733025.27 | 0.00 | 0.122250E+09 | 0.177225E+10 | 0.00 | 0.39 |
June | 29321484.95 | 555253.94 | 0.00 | 13666420.21 | 0.00 | 17577246.29 | 0.159283E+10 | 0.00 | 0.39 |
July | 15549093.25 | 18198882.12 | 0.00 | 14983400.63 | 0.00 | 3180764.69 | 0.131996E+10 | 0.00 | 0.39 |
August | 20491562.77 | 46053931.40 | 0.00 | 12792527.26 | 25628.87 | 4383343.21 | 0.100215E+10 | 0.00 | 0.39 |
September | 49299629.69 | 3371370.00 | 0.00 | 13449920.18 | 0.00 | 48750378.43 | 0.150792E+10 | 0.00 | 0.39 |
October | 63812510.79 | 0.00 | 0.00 | 7703421.20 | 0.00 | 0.449771E+09 | 0.161305E+10 | 0.00 | 0.39 |
November | 89497623.82 | 0.00 | 0.00 | 1892845.55 | 0.00 | 0.135117E+10 | 0.640054E+09 | 0.00 | 0.39 |
December | 83123892.13 | 0.00 | 0.00 | 1231392.16 | 0.00 | 0.178442E+10 | 0.290698E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.725601E+09 | 70454928.28 | 0.00 | 93381599.55 | 25628.87 | 0.833656E+10 | 0.131560E+11 | 0.00 | 0.39 |
Minimum of Months | 15549093.25 | 0.00 | 0.00 | 594471.10 | 0.00 | 3180764.69 | 0.129025E+09 | 0.00 | 0.39 |
Maximum of Months | 94766613.42 | 46053931.40 | 0.00 | 14983400.63 | 25628.87 | 0.193471E+10 | 0.177225E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.342165E+11 | 0.00 | 0.00 | 12920101.02 | 0.00 | 0.00 | 0.342983E+11 | 0.00 | 3.96 |
February | 0.278439E+11 | 0.00 | 0.00 | 12938009.29 | 0.00 | 0.00 | 0.330099E+11 | 0.00 | 4.17 |
March | 0.250610E+11 | 0.00 | 0.00 | 17839729.02 | 0.00 | 0.00 | 0.411102E+11 | 0.00 | 4.31 |
April | 0.183226E+11 | 4043728.81 | 0.00 | 20631442.71 | 6323149.98 | 0.00 | 0.405693E+11 | 0.00 | 4.72 |
May | 0.152015E+11 | 620953.84 | 0.00 | 26465140.79 | 0.00 | 0.00 | 0.412444E+11 | 0.00 | 5.19 |
June | 0.107810E+11 | 0.00 | 0.00 | 30858541.05 | 0.00 | 0.00 | 0.379929E+11 | 0.00 | 5.74 |
July | 0.735202E+10 | 95154174.10 | 0.00 | 34540666.53 | 67877747.33 | 0.00 | 0.360092E+11 | 0.00 | 5.90 |
August | 0.642950E+10 | 0.248118E+09 | 0.00 | 33747401.76 | 0.220466E+09 | 0.00 | 0.325167E+11 | 0.00 | 5.78 |
September | 0.129751E+11 | 139205.52 | 0.00 | 26534838.42 | 1801372.78 | 0.00 | 0.382492E+11 | 0.00 | 5.77 |
October | 0.207514E+11 | 0.00 | 0.00 | 20226494.44 | 0.00 | 0.00 | 0.403240E+11 | 0.00 | 4.92 |
November | 0.271153E+11 | 0.00 | 0.00 | 15497414.11 | 0.00 | 0.00 | 0.375617E+11 | 0.00 | 4.31 |
December | 0.316892E+11 | 0.00 | 0.00 | 13055013.35 | 0.00 | 0.00 | 0.388038E+11 | 0.00 | 3.96 |
Annual Sum or Average | 0.237739E+12 | 0.348076E+09 | 0.00 | 0.265255E+09 | 0.296469E+09 | 0.00 | 0.451690E+12 | 0.00 | 4.90 |
Minimum of Months | 0.642950E+10 | 0.00 | 0.00 | 12920101.02 | 0.00 | 0.00 | 0.325167E+11 | 0.00 | 3.96 |
Maximum of Months | 0.342165E+11 | 0.248118E+09 | 0.00 | 34540666.53 | 0.220466E+09 | 0.00 | 0.412444E+11 | 0.00 | 5.90 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254904E+11 | 0.00 | 0.00 | 19598242.68 | 0.00 | 0.00 | 0.430724E+11 | 0.00 | 3.96 |
February | 0.202825E+11 | 0.00 | 0.00 | 19487903.36 | 0.00 | 0.00 | 0.406135E+11 | 0.00 | 4.18 |
March | 0.189993E+11 | 0.00 | 0.00 | 25952326.79 | 0.00 | 0.00 | 0.472168E+11 | 0.00 | 4.32 |
April | 0.133377E+11 | 8612177.58 | 0.00 | 28818624.58 | 1762993.43 | 0.00 | 0.456096E+11 | 0.00 | 4.73 |
May | 0.106373E+11 | 621450.53 | 0.00 | 35099632.85 | 0.00 | 0.00 | 0.459093E+11 | 0.00 | 5.21 |
June | 0.682199E+10 | 0.00 | 0.00 | 39283137.91 | 0.00 | 0.00 | 0.421331E+11 | 0.00 | 5.77 |
July | 0.394402E+10 | 0.124012E+09 | 0.00 | 43539031.33 | 39150469.99 | 0.00 | 0.396420E+11 | 0.00 | 5.94 |
August | 0.381011E+10 | 0.360775E+09 | 0.00 | 41926649.79 | 0.108184E+09 | 0.00 | 0.353269E+11 | 0.00 | 5.82 |
September | 0.936432E+10 | 1806520.90 | 0.00 | 34451260.57 | 135609.62 | 0.00 | 0.419596E+11 | 0.00 | 5.79 |
October | 0.160851E+11 | 0.00 | 0.00 | 28286540.92 | 0.00 | 0.00 | 0.450327E+11 | 0.00 | 4.93 |
November | 0.200066E+11 | 0.00 | 0.00 | 23147109.10 | 0.00 | 0.00 | 0.447146E+11 | 0.00 | 4.32 |
December | 0.238723E+11 | 0.00 | 0.00 | 20118144.78 | 0.00 | 0.00 | 0.466701E+11 | 0.00 | 3.97 |
Annual Sum or Average | 0.172652E+12 | 0.495827E+09 | 0.00 | 0.359709E+09 | 0.149233E+09 | 0.00 | 0.517900E+12 | 0.00 | 4.91 |
Minimum of Months | 0.381011E+10 | 0.00 | 0.00 | 19487903.36 | 0.00 | 0.00 | 0.353269E+11 | 0.00 | 3.96 |
Maximum of Months | 0.254904E+11 | 0.360775E+09 | 0.00 | 43539031.33 | 0.108184E+09 | 0.00 | 0.472168E+11 | 0.00 | 5.94 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.102957E+09 | 0.00 | 0.00 | 0.644077E+11 | 0.00 | 12.11 |
February | 0.00 | 0.00 | 0.00 | 91571740.76 | 0.00 | 0.00 | 0.575663E+11 | 0.00 | 13.05 |
March | 0.00 | 0.00 | 0.00 | 0.100573E+09 | 0.00 | 0.00 | 0.625115E+11 | 0.00 | 13.82 |
April | 0.00 | 12514916.71 | 0.00 | 0.104354E+09 | 0.00 | 0.00 | 0.562733E+11 | 0.00 | 15.56 |
May | 0.00 | 749539.92 | 0.00 | 0.118636E+09 | 0.00 | 0.00 | 0.543893E+11 | 0.00 | 17.40 |
June | 0.00 | 0.00 | 0.00 | 0.122730E+09 | 0.00 | 0.00 | 0.468182E+11 | 0.00 | 19.28 |
July | 0.00 | 0.196773E+09 | 0.00 | 0.127389E+09 | 0.00 | 0.00 | 0.403769E+11 | 0.00 | 19.58 |
August | 0.00 | 0.565604E+09 | 0.00 | 0.117457E+09 | 0.00 | 0.00 | 0.359020E+11 | 0.00 | 19.05 |
September | 0.00 | 2343066.45 | 0.00 | 0.116574E+09 | 0.00 | 0.00 | 0.492674E+11 | 0.00 | 19.21 |
October | 0.00 | 0.00 | 0.00 | 0.103354E+09 | 0.00 | 0.00 | 0.588858E+11 | 0.00 | 16.16 |
November | 0.00 | 0.00 | 0.00 | 97507144.25 | 0.00 | 0.00 | 0.611066E+11 | 0.00 | 13.58 |
December | 0.00 | 0.00 | 0.00 | 0.102648E+09 | 0.00 | 0.00 | 0.656355E+11 | 0.00 | 12.17 |
Annual Sum or Average | 0.00 | 0.777985E+09 | 0.00 | 0.130575E+10 | 0.00 | 0.00 | 0.653141E+12 | 0.00 | 15.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 91571740.76 | 0.00 | 0.00 | 0.359020E+11 | 0.00 | 12.11 |
Maximum of Months | 0.00 | 0.565604E+09 | 0.00 | 0.127389E+09 | 0.00 | 0.00 | 0.656355E+11 | 0.00 | 19.58 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.638698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864145E+09 | 0.00 | 0.00 | 0.34 |
February | 0.607389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366605E+09 | 0.00 | 0.00 | 0.35 |
March | 0.700367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
April | 0.616004E+10 | 1340331.15 | 0.00 | 187612.99 | 0.00 | 0.00 | 74097175.42 | 0.00 | 0.40 |
May | 0.552687E+10 | 67762.10 | 0.00 | 1568322.87 | 0.00 | 0.00 | 0.459666E+09 | 0.00 | 0.45 |
June | 0.391487E+10 | 0.00 | 0.00 | 3985211.41 | 0.00 | 0.00 | 0.131826E+10 | 0.00 | 0.51 |
July | 0.237020E+10 | 28647729.05 | 0.00 | 7909846.41 | 0.00 | 0.00 | 0.242430E+10 | 0.00 | 0.57 |
August | 0.225304E+10 | 86708739.86 | 0.00 | 6183246.70 | 3748.43 | 0.00 | 0.203903E+10 | 0.00 | 0.56 |
September | 0.466843E+10 | 359406.05 | 0.00 | 2774073.47 | 0.00 | 0.00 | 0.807086E+09 | 0.00 | 0.51 |
October | 0.645942E+10 | 0.00 | 0.00 | 4583.31 | 0.00 | 0.00 | 5289488.92 | 0.00 | 0.42 |
November | 0.679119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54125016.29 | 0.00 | 0.00 | 0.37 |
December | 0.685212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608350E+09 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.644607E+11 | 0.117124E+09 | 0.00 | 22612897.16 | 3748.43 | 0.189322E+10 | 0.712773E+10 | 0.00 | 0.43 |
Minimum of Months | 0.225304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.700367E+10 | 86708739.86 | 0.00 | 7909846.41 | 3748.43 | 0.864145E+09 | 0.242430E+10 | 0.00 | 0.57 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:55:34
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.508742E+11 | 0.165064E+11 | 0.223232E+12 | 0.574972E+12 | 0.330474E+11 |
February | 0.123644E+12 | 0.138415E+11 | 0.186371E+12 | 0.499151E+12 | 0.330858E+11 |
March | 0.242797E+12 | 0.133131E+11 | 0.176621E+12 | 0.497329E+12 | 0.431628E+11 |
April | 0.397378E+12 | 0.110683E+11 | 0.143687E+12 | 0.442047E+12 | 0.966579E+11 |
May | 0.524719E+12 | 0.986368E+10 | 0.124759E+12 | 0.424395E+12 | 0.158711E+12 |
June | 0.541550E+12 | 0.760602E+10 | 0.950058E+11 | 0.366422E+12 | 0.238101E+12 |
July | 0.564535E+12 | 0.603145E+10 | 0.744256E+11 | 0.317565E+12 | 0.364177E+12 |
August | 0.444354E+12 | 0.509760E+10 | 0.627487E+11 | 0.275535E+12 | 0.431109E+12 |
September | 0.280876E+12 | 0.765829E+10 | 0.994200E+11 | 0.379678E+12 | 0.214299E+12 |
October | 0.182653E+12 | 0.108222E+11 | 0.144398E+12 | 0.456155E+12 | 0.754704E+11 |
November | 0.631965E+11 | 0.129227E+11 | 0.178401E+12 | 0.484321E+12 | 0.383385E+11 |
December | 0.295061E+11 | 0.155948E+11 | 0.211759E+12 | 0.546706E+12 | 0.333283E+11 |
Annual Sum or Average | 0.344608E+13 | 0.130326E+12 | 0.172083E+13 | 0.526428E+13 | 0.175949E+13 |
Minimum of Months | 0.295061E+11 | 0.509760E+10 | 0.627487E+11 | 0.275535E+12 | 0.330474E+11 |